Tag Name,Address,Data Type,Respect Data Type,Client Access,Scan Rate,Scaling,Raw Low,Raw High,Scaled Low,Scaled High,Scaled Data Type,Clamp Low,Clamp High,Eng Units,Description WA3252_CP_0102_1_YL_raw,400109.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Suction Bypass Mode Enabled WA3252_CP_0102_2_YL_raw,400109.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Suction Bypass Mode Enabled WA3252_AFD_0103_1_BM1,400110.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 In Bypass Mode WA3252_AFD_0103_1_BM2,400110.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Discharge Pressure Bypass Mode WA3252_AFD_0103_1_YL1,400109.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Bypass Mode Enabled WA3252_AFD_0103_1_YL2,400108.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Isolation Valve Bypass Mode WA3252_AFD_0103_1_VA,400112.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 PFCC Online WA3252_AFD_0103_2_BM1,400110.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 In Bypass Mode WA3252_AFD_0103_2_BM2,400110.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Discharge Pressure Bypass Mode WA3252_AFD_0103_2_YL1,400109.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Bypass Mode Enabled WA3252_AFD_0103_2_YL2,400108.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Isolation Valve Bypass Mode WA3252_AFD_0103_9_BM1,400110.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 In Bypass Mode WA3252_AFD_0103_9_BM2,400111.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Discharge Pressure Bypass Mode WA3252_AFD_0103_9_YL1_raw,400109.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Bypass Mode Enabled WA3252_AFD_0103_9_YL2,400108.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Isolation Valve Bypass Mode WA3252_AFD_0103_9_VA,400112.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 PFCC Online WA3252_CP_0113_1_BM1_raw,400111.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Pump Room Bypass Enabled WA3252_CP_0113_1_BM2_raw,400111.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Pump Room Bypass Enabled WA3252_ATO_0112_2_JN2,400116.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Main ""A2"" Closed Status" WA3252_ATO_0112_2_JS1,400116.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 ""A2"" Power Available" WA3252_ATO_0112_2_JS2,400116.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Main ""B2"" Closed Status" WA3252_ATO_0112_2_XA1,400116.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 ""B2"" Power Available" WA3252_ATO_0112_2_JS3,400116.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Main ""G2"" Closed Status" WA3252_ATO_0112_2_XA2,400116.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 ""G2"" Power Available" WA3252_ATO_0112_2_XN,400116.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Tie ""No. 2"" Open Status" WA3252_FLT_0112_2_JN,400116.15,Boolean,1,R/W,1000,,,,,,,,,,Active Harmonic Filter Power On WA3252_SWG_0112_2_XN5,400117.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Main ""A2"" Closed Status" WA3252_SWG_0112_2_XN6,400117.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Main ""G2"" Closed Status" WA3252_AFD_0103_1_HS,400100.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Scada Lockout WA3252_AFD_0103_1_BM,400102.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Bypass Mode Command WA3252_AFD_0103_1_ML,400103.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Ready WA3252_FV_0103_1B_YL_raw,400108.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Control Valve Maint. Mode WA3252_FV_0103_1B_ZH,400127.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Control Valve Open Status WA3252_FV_0103_1B_ZL,400127.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Control Valve Closed Status WA3252_AFD_0103_2_ML,400103.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Ready WA3252_AFD_0103_2_VA,400112.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 PFCC Online WA3252_FV_0103_2B_YL,400108.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Control Valve Maint. Mode WA3252_AFD_0103_9_ML,400103.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Ready WA3252_FV_0103_9B_YL_raw,400109.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Control Valve Maint. Mode WA3252_AFD_0103_1_LOCKOUT,400100.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 HMI Lockout Command WA3252_AFD_0103_1_LOCKOUTRST,400100.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 HMI Lockout Reset WA3252_AFD_0103_2_BM,400102.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Bypass Mode Command WA3252_AFD_0103_2_HS,400100.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Scada Lockout WA3252_AFD_0103_2_LOCKOUT,400100.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 HMI Lockout Command WA3252_AFD_0103_2_LOCKOUTRST,400100.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 HMI Lockout Reset WA3252_AFD_0103_9_BM,400102.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Bypass Mode Command WA3252_AFD_0103_9_HS,400101.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Scada Lockout WA3252_AFD_0103_9_LOCKOUT,400101.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 HMI Lockout Command WA3252_AFD_0103_9_LOCKOUTRST,400101.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 HMI Lockout Reset WA3252_ATO_0112_1_JN2,400116.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Main ""A1"" Closed Status" WA3252_ATO_0112_1_JS1,400116.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 ""A1"" Power Available" WA3252_ATO_0112_1_JS2,400116.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Main ""B1"" Closed Status" WA3252_ATO_0112_1_XA1,400116.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 ""B1"" Power Available" WA3252_ATO_0112_1_JS3,400116.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Main ""G1"" Closed Status" WA3252_ATO_0112_1_XA2,400116.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 ""G1"" Power Available" WA3252_ATO_0112_1_XN,400116.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Tie ""No. 1"" Open Status" WA3252_FLT_0112_1_JN,400116.14,Boolean,1,R/W,1000,,,,,,,,,,Active Harmonic Filter Power On WA3252_SWG_0112_1_XN3,400117.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Main ""A1"" Closed Status" WA3252_SWG_0112_1_XN4,400117.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Main ""G1"" Closed Status" WA3252_REC_0131_1_XN1,400128.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 1 Open Status WA3252_REC_0131_1_XN2,400128.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 1 Close Status WA3252_REC_0131_2_XN1,400128.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 2 Open Status WA3252_REC_0131_2_XN2,400128.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 2 Close Status WA3252_PFC_0112_1_XA,400112.09,Boolean,1,R/W,1000,,,,,,,,,,MV Switchgear PFCC 1 Inhibit Signal (PCO-48) WA3252_PFC_0112_2_XA,400112.10,Boolean,1,R/W,1000,,,,,,,,,,MV Switchgear PFCC 2 Inhibit Signal (PCO-48) WA3252_AFD_0103_3_HS,400100.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 3 Scada Lockout WA3252_AFD_0103_4_HS,400100.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 4 Scada Lockout WA3252_AFD_0103_5_HS,400100.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 5 Scada Lockout WA3252_AFD_0103_6_HS,400101.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 6 Scada Lockout WA3252_AFD_0103_7_HS,400101.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 7 Scada Lockout WA3252_AFD_0103_3_BM2,400110.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_3_ML,400103.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 READY WA3252_AFD_0103_3_YL2,400108.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_3_BM3,400111.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_3B_YL,400108.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 CONTROL VALVE MAINT. MODE WA3252_FV_0103_3B_ZH,400127.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 CONTROL VALVE OPEN STATUS WA3252_FV_0103_3B_ZL,400127.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 3 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_4_BM2,400110.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_4_ML,400103.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 READY WA3252_AFD_0103_4_YL2,400108.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_4_BM3,400111.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_4B_YL,400108.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 CONTROL VALVE MAINT. MODE WA3252_FV_0103_4B_ZH,400127.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 CONTROL VALVE OPEN STATUS WA3252_FV_0103_4B_ZL,400127.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 4 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_5_BM2,400110.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_5_ML,400103.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 READY WA3252_AFD_0103_5_YL2,400108.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_5_BM3,400111.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_5B_YL,400108.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 CONTROL VALVE MAINT. MODE WA3252_FV_0103_5B_ZH,400127.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 CONTROL VALVE OPEN STATUS WA3252_FV_0103_5B_ZL,400127.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 5 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_6_BM2,400110.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_6_ML,400103.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 READY WA3252_AFD_0103_6_YL2,400108.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_6_BM3,400111.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_6B_YL,400108.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 CONTROL VALVE MAINT. MODE WA3252_FV_0103_6B_ZH,400127.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 CONTROL VALVE OPEN STATUS WA3252_FV_0103_6B_ZL,400127.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 6 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_7_BM2,400110.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_7_ML,400103.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 READY WA3252_AFD_0103_7_YL2,400108.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_7_BM3,400111.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_7B_YL,400108.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 CONTROL VALVE MAINT. MODE WA3252_FV_0103_7B_ZH,400127.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 CONTROL VALVE OPEN STATUS WA3252_FV_0103_7B_ZL,400127.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 7 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_8_BM2,400111.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 DISCHARGE PRESSURE BYPASS MODE WA3252_AFD_0103_8_ML,400103.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 READY WA3252_AFD_0103_8_YL2,400108.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 ISOLATION VALVE BYPASS MODE WA3252_AFD_0103_8_BM3,400111.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 CONTROL VALVE THROTTLE BYPASS ENABLED WA3252_FV_0103_8B_YL,400109.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 CONTROL VALVE MAINT. MODE WA3252_FV_0103_8B_ZH,400127.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 CONTROL VALVE OPEN STATUS WA3252_FV_0103_8B_ZL,400128.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 CONTROL VALVE CLOSED STATUS WA3252_AFD_0103_8_HS,400101.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PUMP 8 SCADA LOCKOUT WA3252_AFD_0103_3_LOCKOUT,400100.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 3 HMI Lockout Command WA3252_AFD_0103_3_LOCKOUTRST,400100.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 3 HMI Lockout Reset WA3252_AFD_0103_4_LOCKOUT,400100.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 4 HMI Lockout Command WA3252_AFD_0103_4_LOCKOUTRST,400100.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 4 HMI Lockout Reset WA3252_AFD_0103_5_LOCKOUT,400100.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 5 HMI Lockout Command WA3252_AFD_0103_5_LOCKOUTRST,400100.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 5 HMI Lockout Reset WA3252_AFD_0103_6_LOCKOUT,400101.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 6 HMI Lockout Command WA3252_AFD_0103_6_LOCKOUTRST,400101.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 6 HMI Lockout Reset WA3252_AFD_0103_7_LOCKOUT,400101.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 7 HMI Lockout Command WA3252_AFD_0103_7_LOCKOUTRST,400101.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 7 HMI Lockout Reset WA3252_AFD_0103_8_LOCKOUT,400101.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 8 HMI Lockout Command WA3252_AFD_0103_8_LOCKOUTRST,400101.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 8 HMI Lockout Reset North_or_South,400112.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS Select which TSR to use for the Level Indication and Level Switch High (1 = North / 0 = South) AFD_LH_NEXTSTART_REQUEST,400112.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS Low Head Pumps Next Start Requested AFD_LH_NEXTSTART_UNVAIL,400112.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS Low Head Pumps Next Start Unavailable AFD_HH_NEXTSTART_REQUEST,400112.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS High Head Pump Next Start Request AFD_HH_NEXTSTART_UNVAIL,400112.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS High Head Pump Next Start Unavailable WA3252_FV_0103_2B_ZH,400127.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Control Valve Open Status WA3252_FV_0103_2B_ZL,400127.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Control Valve Closed Status WA3252_FV_0103_9B_ZH,400127.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Control Valve Open Status WA3252_FV_0103_9B_ZL,400128.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Control Valve Closed Status WA3252_GEN_0131_1_MN,400104.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Stand-By Generator Run Status WA3252_GEN_0131_1_XA1_raw,400104.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Stand-By Generator Common Alarm WA3252_ATO_0140_1C_JN,400104.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Main ""C3"" Power Mode " WA3252_ATO_0140_1C_JS,400104.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear ""C3"" Power Available " WA3252_ATO_0140_1D_JN,400104.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Main ""D3"" Power Mode " WA3252_ATO_0140_1D_JS,400104.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear ""D3"" Power Available " WA3252_ATO_0140_1_XN1,400104.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS 480V Switchgear Tie No.1 Open Status WA3252_ATO_0140_1_XN2,400104.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS 480V Switchgear Tie No.2 Open Status WA3252_CP_0117_1A_IA,400105.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Northwest Sump Pump Auto Enabled WA3252_CP_0117_1A_MN,400105.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Northwest Sump Pump Run Status WA3252_CP_0117_1B_IA,400105.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southwest By Pump 1 Sump Pump Auto Enabled WA3252_CP_0117_1B_MN,400105.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southwest By Pump 1 Sump Pump Run Status WA3252_CP_0117_1C_IA,400105.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southwest By Pump 4 Sump Pump Auto Enabled WA3252_CP_0117_1C_MN,400105.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southwest By Pump 4 Sump Pump Run Status WA3252_CP_0117_1DE_IA,400105.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Alcove Sump Pump Auto Enabled WA3252_CP_0117_1DE_MN,400105.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Alcove Sump Pump Run Status WA3252_CP_0117_1I_MN,400105.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Northeast Sump Pump Run Status WA3252_CP_0117_1H_IA,400105.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southeast Sump Pump Auto Enabled WA3252_CP_0117_1H_MN,400105.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Southeast Sump Pump Run Status WA3252_CP_0117_1FG_IA,400105.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Alcove Sump Pump Auto Enabled WA3252_CP_0117_1FG_MN,400105.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Alcove Sump Pump Run Status WA3252_CP_0117_1K_IA,400105.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Elevator Sump Pump Auto Enabled WA3252_CP_0117_1K_MN,400105.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Elevator Sump Pump Run Status WA3252_CP_0117_1J_IA,400106.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Elevator Sump Pump Auto Enabled WA3252_CP_0117_1J_MN,400106.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Elevator Sump Pump Run Status WA3252_CP_0117_2A_IA1,400106.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump A Auto Enabled WA3252_CP_0117_2A_MN1,400106.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump A Run Status WA3252_CP_0117_2A_MN2,400106.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump A Stop Status WA3252_CP_0117_2A_IA2,400106.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump B Auto Enabled WA3252_CP_0117_2A_MN3,400106.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump B Run Status WA3252_CP_0117_2A_MN4,400106.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Secondary Dewatering Pump B Stop Status WA3252_CP_0117_2B_IA1,400106.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump C Auto Enabled WA3252_CP_0117_2B_MN1,400106.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump C Run Status WA3252_CP_0117_2B_MN2,400106.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump C Stop Status WA3252_CP_0117_2B_IA2,400106.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump D Auto Enabled WA3252_CP_0117_2B_MN3,400106.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump D Run Status WA3252_CP_0117_2B_MN4,400106.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Secondary Dewatering Pump D Stop Status WA3252_CP_0118_1A_IA,400107.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Dam Collector Pump A Auto Enabled WA3252_CP_0118_1A_MN,400107.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Dam Collector Pump A Run Status WA3252_CP_0118_1B_IA,400107.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Dam Collector Pump B Auto Enabled WA3252_CP_0118_1B_MN,400107.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Dam Collector Pump B Run Status WA3252_CP_0118_2A_IA,400107.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Dam Collector Pump A Auto Enabled WA3252_CP_0118_2A_MN,400107.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Dam Collector Pump A Run Status WA3252_CP_0118_2B_IA,400107.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Dam Collector Pump B Auto Enabled WA3252_SWG_0112_1_XN1,400107.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Main ""B1"" Closed Status " WA3252_SWG_0112_1_XN2,400107.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Tie Breaker 1 Closed Status WA3252_SWG_0112_2_XN3,400107.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Main ""B2"" Closed Status " WA3252_SWG_0112_2_XN4,400107.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Tie Breaker 2 Closed Status WA3252_REC_0131_3_ZH,400107.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 3 Open Status WA3252_REC_0131_3_ZL,400107.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 3 Close Status WA3252_REC_0131_4_ZH,400107.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 4 Open Status WA3252_REC_0131_4_ZL,400107.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS Recloser 4 Close Status WA3252_CP_001_1_R0S2_PLCFault,400120.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 2 Fault WA3252_CP_001_1_R0S4_PLCFault,400120.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 4 Fault WA3252_CP_001_1_R0S5_PLCFault,400120.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 5 Fault WA3252_CP_001_1_R0S6_PLCFault,400120.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 6 Fault WA3252_CP_001_1_R0S7_PLCFault,400120.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 7 Fault WA3252_CP_001_1_R0S8_PLCFault,400120.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 8 Fault WA3252_CP_001_1_R0S9_PLCFault,400120.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 9 Fault WA3252_CP_001_1_R0S10_PLCFault,400120.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 10 Fault WA3252_CP_001_1_R0S11_PLCFault,400120.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 0 Slot 11 Fault WA3252_CP_001_1_R1S0_PLCFault,400121.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 0 Fault WA3252_CP_001_1_R1S1_PLCFault,400121.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 1 Fault WA3252_CP_001_1_R1S2_PLCFault,400121.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 2 Fault WA3252_CP_001_1_R1S3_PLCFault,400121.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 3 Fault WA3252_CP_001_1_R1S4_PLCFault,400121.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 4 Fault WA3252_CP_001_1_R1S5_PLCFault,400121.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 5 Fault WA3252_CP_001_1_R1S6_PLCFault,400121.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 6 Fault WA3252_CP_001_1_R1S7_PLCFault,400121.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 7 Fault WA3252_CP_001_1_R1S8_PLCFault,400121.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 8 Fault WA3252_CP_001_1_R1S9_PLCFault,400121.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 9 Fault WA3252_CP_001_1_R1S10_PLCFault,400121.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 10 Fault WA3252_CP_001_1_R1S11_PLCFault,400121.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 1 Slot 11 Fault WA3252_CP_001_1_R2S0_PLCFault,400122.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 0 Fault WA3252_CP_001_1_R2S7_PLCFault,400122.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 7 Fault WA3252_CP_001_1_R3S7_PLCFault,400123.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 7 Fault WA3252_CP_001_1_R4S0_PLCFault,400124.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 0 Fault WA3252_CP_001_1_R4S1_PLCFault,400124.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 1 Fault WA3252_CP_001_1_R4S2_PLCFault,400124.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 2 Fault WA3252_CP_001_1_R4S3_PLCFault,400124.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 3 Fault WA3252_CP_001_1_R4S4_PLCFault,400124.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 4 Fault WA3252_CP_001_1_R4S5_PLCFault,400124.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 5 Fault WA3252_CP_001_1_R4S6_PLCFault,400124.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 6 Fault WA3252_CP_001_1_R4S7_PLCFault,400124.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 7 Fault WA3252_CP_001_1_R4S8_PLCFault,400124.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 4 Slot 8 Fault WA3252_CP_001_1_R5S0_PLCFault,400125.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 0 Fault WA3252_CP_001_1_R5S1_PLCFault,400125.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 1 Fault WA3252_CP_001_1_R5S2_PLCFault,400125.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 2 Fault WA3252_CP_001_1_R5S3_PLCFault,400125.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 3 Fault WA3252_CP_001_1_R5S5_PLCFault,400125.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 5 Fault WA3252_CP_001_1_R5S6_PLCFault,400125.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 6 Fault WA3252_CP_001_1_R5S7_PLCFault,400125.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 7 Fault WA3252_CP_001_1_R5S8_PLCFault,400125.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 5 Slot 8 Fault WA3252_CP_001_1_R6S0_PLCFault,400126.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 0 Fault WA3252_CP_001_1_R6S1_PLCFault,400126.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 1 Fault WA3252_CP_001_1_R6S2_PLCFault,400126.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 2 Fault WA3252_CP_001_1_R6S3_PLCFault,400126.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 3 Fault WA3252_CP_001_1_R6S4_PLCFault,400126.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 4 Fault WA3252_CP_001_1_R6S5_PLCFault,400126.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 5 Fault WA3252_CP_001_1_R6S6_PLCFault,400126.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 6 Fault WA3252_CP_001_1_R6S7_PLCFault,400126.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 7 Fault WA3252_CP_001_1_R6S8_PLCFault,400126.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 6 Slot 8 Fault WA3252_CP_001_1_R2S1_PLCFault,400122.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 1 Fault WA3252_CP_001_1_R2S2_PLCFault,400122.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 2 Fault WA3252_CP_001_1_R2S3_PLCFault,400122.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 3 Fault WA3252_CP_001_1_R2S4_PLCFault,400122.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 4 Fault WA3252_CP_001_1_R2S5_PLCFault,400122.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 5 Fault WA3252_CP_001_1_R2S6_PLCFault,400122.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 6 Fault WA3252_CP_001_1_R2S8_PLCFault,400122.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 8 Fault WA3252_CP_001_1_R2S9_PLCFault,400122.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 9 Fault WA3252_CP_001_1_R2S10_PLCFault,400122.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 10 Fault WA3252_CP_001_1_R2S11_PLCFault,400122.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 2 Slot 11 Fault WA3252_CP_001_1_R3S0_PLCFault,400123.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 0 Fault WA3252_CP_001_1_R3S1_PLCFault,400123.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 1 Fault WA3252_CP_001_1_R3S2_PLCFault,400123.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 2 Fault WA3252_CP_001_1_R3S3_PLCFault,400123.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 3 Fault WA3252_CP_001_1_R3S4_PLCFault,400123.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 4 Fault WA3252_CP_001_1_R3S5_PLCFault,400123.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 5 Fault WA3252_CP_001_1_R3S6_PLCFault,400123.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 6 Fault WA3252_CP_001_1_R3S8_PLCFault,400123.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 8 Fault WA3252_CP_001_1_R3S9_PLCFault,400123.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 9 Fault WA3252_CP_001_1_R3S10_PLCFault,400123.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 10 Fault WA3252_CP_001_1_R3S11_PLCFault,400123.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC 001-1 Rack 3 Slot 11 Fault WA3252_AFD_0103_NEXTSTP_REQ,400114.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Next Pump Stop Required WA3252_AFD_0103_NEXTSTRT_REQ,400114.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Next Pump Start Required WA3252_FCV_0113_2_PID_AUTO,400114.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID In Auto WA3252_FCV_0113_2A_LEAD,400114.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Reservoir Lead-Lag Valve Order. (1 = Lead; 0 =Lag) WA3252_PLC_001_1_GlobalReset,400115.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS PLC Global Reset WA3252_CP_0117_3B_MN,400106.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS Discharge Maintenance Dewatering Pump Run WA3252_CP_0118_2B_MN,400106.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Dam Collector Pump B Run Status WA3252_CP_0117_1I_IA,400105.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS Northeast Sump Pump Auto Enabled WA3252_FV_0102_1A_INTK,400101.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Intake Valve Command Interlock Alarm WA3252_FV_0102_1B_INTK,400101.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Suction Valve Command Interlock Alarm WA3252_FV_0102_2A_INTK,400101.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS East Intake Valve Command Interlock Alarm WA3252_FV_0102_2B_INTK,400101.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS West Intake Valve Command Interlock WA3252_UPS_001_1_BM,400114.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Scada UPS Panel UPS Bypass Status WA3252_UPS_001_2_BM,400114.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Security UPS Panel UPS Bypass Status WA3252_CP_0117_3A_MN,400107.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS Intake Maintenance Dewatering Pump Run WA3252_FIT_0105_1A_PID_AUTO,400114.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID HMI Auto Command WA3252_TSR_FLOWDEMAND_ENB,400114.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS TSR Demand Enable WA3252_TSR_ALARM_DIS,400114.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS TSR High And Low Level Alarms Disable WA3252_TSR_LSH_BYP,400114.09,Boolean,1,R/W,1000,,,,,,,,,,RWPS High Level Float Switch Bypass WA3252_AFD_0103_IR_PERM_OVERRIDE,400114.10,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pumps Avail Permissive HMI Override WA3252_AFD_0103_IR_RDYALM,400114.11,Boolean,1,R/W,1000,,,,,,,,,,RWPS AFD At Least 1 Pump In Auto And 1 Pump Is Ready in Local WA3252_AFD_0103_NEXTSTART_UNVAIL,400114.12,Boolean,1,R/W,1000,,,,,,,,,,RWPS No Pump is Available for Next Start WA3252_AFD_0103_PMP_SWAP_ACTIVE,400114.13,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump Alternation Active WA3252_AFD_0103_PMP_ALTER_FAIL,400114.14,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump Alternation Failure WA3252_AFD_0103_PMP_ALTER_RST,400114.15,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump Alternation Failure Reset WA3252_AFD_0103_1_MBU,400113.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Scada Unplanned Stop WA3252_AFD_0103_3_MBU,400113.02,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 3 Scada Unplanned Stop WA3252_AFD_0103_4_MBU,400113.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 4 Scada Unplanned Stop WA3252_AFD_0103_5_MBU,400113.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 5 Scada Unplanned stop WA3252_AFD_0103_2_MBU,400113.01,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Scada Unplanned Stop WA3252_AFD_0103_6_MBU,400113.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 6 Scada Unplanned Stop WA3252_AFD_0103_7_MBU,400113.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 7 Scada Unplanned stop WA3252_AFD_0103_8_MBU,400113.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 8 Scada Unplanned Stop WA3252_AFD_0103_9_MBU,400113.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Scada Unplanned Stop WA3252_FIT_0105_1A_PID_AUTO_ST,400115.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS TSR Inlet Flow PID Auto Status (1 = Auto, 0= Man)" WA3252_AFD_0103_Running,459015.00,Boolean,1,R/W,1000,,,,,,,,,,At Least One Pump Is Running Peer to WA3253-PLC-001-1 WA3252_PLC_0001_1_Watchdog,459015.01,Boolean,1,R/W,1000,,,,,,,,,,WA3253-PLC-001-1 Watchdog Timer WA3252_FIT_0113_2A_Tot_AI,400115.03,Boolean,1,R/W,1000,,,,,,,,,,RWPS Flow To Reservoir Flow Total Selection (0 - PULSE / 1 - Timer Event) WA3252_FIT_0113_2A_ResetTotal,400115.04,Boolean,1,R/W,1000,,,,,,,,,,RWPS Flow To Reservoir Total Reset from SCADA WA3252_AFD_0103_AUTO,400115.05,Boolean,1,R/W,1000,,,,,,,,,,RWPS HMI Auto/Manual Command ( 0 = Devices To Manual 1 Devices To Auto) WA3252_FCV_0113_2_AUTO,400115.06,Boolean,1,R/W,1000,,,,,,,,,,RWPS HMI Valves 2A And 2B Auto/Manual Command ( 0 = Devices To Manual 1 Devices To Auto) WA3252_AFD_0103_NEXTSTART_PERM,400115.07,Boolean,1,R/W,1000,,,,,,,,,,RWPS Next Start Permission ( Pump run < 2) WA3260_COMM_SWGBLDG_FAIL,400115.02,Boolean,1,R/W,1000,,,,,,,,,, WA3252_FV_0103_3B_DELAY,400308,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 3 PCV Trip Delay WA3252_FV_0103_4B_DELAY,400310,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 4 PCV Trip Delay WA3252_FV_0103_5B_DELAY,400312,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 5 PCV Trip Delay WA3252_FV_0103_6B_DELAY,400314,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 6 PCV Trip Delay WA3252_FV_0103_7B_DELAY,400316,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 7 PCV Trip Delay WA3252_FV_0103_8B_DELAY,400318,Long,1,R/W,1000,,,,,,,,,,RWPS Pump 8 PCV Trip Delay WA3252_AFD_0103_SWAP_TMR,400302,Long,1,R/W,1000,,,,,,,,,,RWPS Pumps Alternate Timer Setpoint WA3252_PLC_001_1_Day,400150,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Day WA3252_PLC_001_1_Hour,400151,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Hour WA3252_PLC_001_1_Min,400152,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Min WA3252_PLC_001_1_Mon,400153,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Month WA3252_PLC_001_1_Sec,400154,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Second WA3252_PLC_001_1_Year,400155,Short,1,R/W,1000,,,,,,,,,,RWPS PLC Time - Year WA3252_AFD_0103_NEXTSTRT_DLY,400200,Float,1,R/W,1000,,,,,,,,,,RWPS Next Pump Start Delay WA3252_AFD_0103_NEXTSTP_DLY,400202,Float,1,R/W,1000,,,,,,,,,,RWPS Next Pump Stop Delay WA3252_FIT_0113_2_FLSP,400204,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow Setpoint WA3252_FCV_0113_2_PID_OUT,400206,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Output WA3252_FIT_0105_1A_PID_OUT,400208,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Output WA3252_RWPSDEMANDFLOW,400210,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Demand Flow Setpoint WA3252_TSRHIGHLEVELBAND,400212,Float,1,R/W,1000,,,,,,,,,,RWPS TSR High Level Band Setpoint WA3252_TSRLOWLEVELBAND,400214,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Low Level Band Setpoint WA3252_TSRMIDLEVELBAND,400216,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Midband Level Setpoint WA3252_FIT_0113_2A_FTTD,400220,Float,1,R/W,1000,,,,,,,,,,RWPS Flow To Reservoir Flow Total Today WA3252_FIT_0113_2A_FTYD,400222,Float,1,R/W,1000,,,,,,,,,,RWPS Flow To Reservoir Flow Total Yesterday WA3252_FIT_0113_2A_FLOT,400224,Float,1,R/W,1000,,,,,,,,,,RWPS Flow To Reservoir Total Since Last Reset WA3252_TSRLOWLEVELTMR,400218,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Low Level Band Setpoint 100 % Speeds Timer in Min WA3252_FCV_0113_2_VLV_SWAP_TIMER,400300,DWord,1,R/W,1000,,,,,,,,,,RWPS To Reservoir Valve Swap Timer (Days) WA3252_FCV_0113_2_PID.rev_dir,440379.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: 0: direct action of the PID controller 1: opposite action of the PID controller WA3252_FCV_0113_2_PID.en_rcpy,440379.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: 1: the RCPY input is used WA3252_FIT_0105_1A_PID.rev_dir,440359.00,Boolean,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: 0: direct action of the PID controller 1: opposite action of the PID controller WA3252_FIT_0105_1A_PID.en_rcpy,440359.08,Boolean,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: 1: the RCPY input is used BMENOC0311_4.PORT1_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 1 BMENOC0311_4.PORT2_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 2 BMENOC0311_4.PORT3_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet port 3 BMENOC0311_4.ETH_BKP_PORT_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for Ethernet backplane port BMENOC0311_4.HSBY_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Link up/down for HSBY port BMENOC0311_4.REDUNDANCY_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Redundancy status / backup path available BMENOC0311_4.SCANNER_OK,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Scanner OK and scanning at least 1 equipment (if at least 1 equipment configured) BMENOC0311_4.GLOBAL_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: one or more services not operating normally / 1: all operational BMENOC0311_4.NETWORK_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 1: No traffic overload detected / 0: Traffic overload detected (ex: broadcast storm). Check your network topology and configuration. BMENOC0311_4.RSTP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.PORT502_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.SNMP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.MAIN_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Main IP address status (0 in case of duplicate IP or no IP assigned) BMENOC0311_4.ETH_BKP_FAILURE,,Boolean,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: Ethernet backplane hardware status (0: failure, 1: OK)" BMENOC0311_4.ETH_BKP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: Ethernet backplane error (0: error, 1: OK)" BMENOC0311_4.EIP_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.MODBUS_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.NTP_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.SNTP_CLIENT,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.WEB_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.FIRMWARE_UPGRADE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.FTP,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.FDR_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.EIP_ADAPTER,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: EIP adapter (server) service 0: service not operating normally / 1: service operating normally or disabled BMENOC0311_4.A_B_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: IP address A/B status (0 in case of duplicate IP or no IP assigned) BMENOC0311_4.LLDP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: LLDP service status BMENOC0311_4.EVENT_LOG_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 0: event log service not operating normally / 1: event log service operating normally or disabled BMENOC0311_4.LOG_SERVER_NOT_REACHABLE,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: 1: No acknowledgement received from the syslog server / 0: otherwise BMEP58_ECPU_EXT.PORT1_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 1 BMEP58_ECPU_EXT.PORT2_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 2 BMEP58_ECPU_EXT.PORT3_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet port 3 BMEP58_ECPU_EXT.ETH_BKP_PORT_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for Ethernet backplane port BMEP58_ECPU_EXT.HSBY_LINK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Link up/down for HSBY port BMEP58_ECPU_EXT.REDUNDANCY_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Redundancy status / backup path available BMEP58_ECPU_EXT.SCANNER_OK,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Scanner OK and scanning at least 1 equipment (if at least 1 equipment configured) BMEP58_ECPU_EXT.GLOBAL_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: one or more services not operating normally / 1: all operational BMEP58_ECPU_EXT.NETWORK_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 1: No traffic overload detected / 0: Traffic overload detected (ex: broadcast storm). Check your network topology and configuration. BMEP58_ECPU_EXT.RSTP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.PORT502_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.SNMP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.MAIN_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Main IP address status (0 in case of duplicate IP or no IP assigned) BMEP58_ECPU_EXT.ETH_BKP_FAILURE,,Boolean,1,R/W,1000,,,,,,,,,,"Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet backplane hardware status (0: failure, 1: OK)" BMEP58_ECPU_EXT.ETH_BKP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,"Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet backplane error (0: error, 1: OK)" BMEP58_ECPU_EXT.EIP_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.MODBUS_SCANNER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.NTP_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.SNTP_CLIENT,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.WEB_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.FIRMWARE_UPGRADE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.FTP,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.FDR_SERVER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.EIP_ADAPTER,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): EIP adapter (server) service 0: service not operating normally / 1: service operating normally or disabled BMEP58_ECPU_EXT.A_B_IP_ADDRESS_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): IP address A/B status (0 in case of duplicate IP or no IP assigned) BMEP58_ECPU_EXT.LLDP_SERVICE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): LLDP service status BMEP58_ECPU_EXT.EVENT_LOG_STATUS,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 0: event log service not operating normally / 1: event log service operating normally or disabled BMEP58_ECPU_EXT.LOG_SERVER_NOT_REACHABLE,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): 1: No acknowledgement received from the syslog server / 0: otherwise BMEP58_ECPU_EXT.RES_DROP_HEALTH32,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved BMEP58_ECPU_EXT.RES_DROP_CTRL32,,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved Meter_Vault_PLC.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness Meter_Vault_PLC.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_Eaton_Pump1.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_Eaton_Pump1.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_Eaton_Pump2.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_Eaton_Pump2.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_Eaton_Pump9.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_Eaton_Pump9.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_SEL710_Pump1.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_SEL710_Pump1.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_SEL710_Pump2.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_SEL710_Pump2.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object RWPS_SEL710_Pump9.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness RWPS_SEL710_Pump9.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object TSR_PLC.Freshness,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Global Freshness TSR_PLC.Freshness_1,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object TSR_PLC.Freshness_2,,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Freshness of Object AI_R2_S10.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R1_S10.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R0_S10.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R3_S10.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R3_S9.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R0_S9.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R1_S9.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R2_S9.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R4_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R4_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R4_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R5_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R5_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R5_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R5_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R6_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AI_R6_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AO_R1_S11.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AO_R2_S11.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AO_R3_S11.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health AO_R6_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R0_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R0_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R0_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R0_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R2_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S6.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R3_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R0_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R1_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R4_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R5_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R5_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R5_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R5_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R6_S4.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R6_S0.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R6_S1.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R6_S2.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DI_R6_S3.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R0_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R2_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R3_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R1_S8.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R0_S11.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R2_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R3_S7.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health DO_R6_S5.MOD_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Module health WA3252_AFD_0103_1_SI.GlobalReset,401000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_SI.HH_EN,401000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_1_SI.H_EN,401000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_1_SI.L_EN,401000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_1_SI.LL_EN,401000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_1_SI.BLEN,401000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_1_SI.OR_EN,401000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_1_SI.UREN,401000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_1_SI.RC_EN,401000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_1_SI.SuppressAA,401000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_1_SI.SuppressLA,401000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_1_SI.ConfigError,401000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_1_SI.HH_Alarm,401000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_1_SI.H_Alarm,401000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_1_SI.L_Alarm,401000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_1_SI.LL_Alarm,401000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_1_SI.BL_Alarm,401001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_1_SI.OR_Alarm,401001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_1_SI.UR_Alarm,401001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_1_SI.ROC_Alarm,401001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_1_SI.REST,401001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_1_SI.ALRM,401001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_SI.ANUN,401001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_SI.AKED,401001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_SI.Resetable,401001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_SI.HH_Fault,401001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_1_SI.H_Fault,401001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_1_SI.L_Fault,401001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_1_SI.LL_Fault,401001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_1_SI.BL_Fault,401001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_1_SI.OR_Fault,401001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_1_SI.UR_Fault,401001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_1_SI.ROC_Fault,401002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_1_SI.Tot_EN,401002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_1_SI.TAGR,401002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_SI.ACKN,401002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_1_SI.INTK,401002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_1_SI.PLCFault,401002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_SI.PLCIOFault,401002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_SI.INTK_EN,401002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_1_SI.Shelve,401002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_SI.Shelved,401002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_1_SI.Suppress,401002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_SI.Suppressed,401002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_1_SI.PCSuppress,401002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_SI.PCUnSuppress,401002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_SI.PCUnshelve,401002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_SI.GlobalReset,401200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_SI.HH_EN,401200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_2_SI.H_EN,401200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_2_SI.L_EN,401200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_2_SI.LL_EN,401200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_2_SI.BLEN,401200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_2_SI.OR_EN,401200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_2_SI.UREN,401200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_2_SI.RC_EN,401200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_2_SI.SuppressAA,401200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_2_SI.SuppressLA,401200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_2_SI.ConfigError,401200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_2_SI.HH_Alarm,401200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_2_SI.H_Alarm,401200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_2_SI.L_Alarm,401200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_2_SI.LL_Alarm,401200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_2_SI.BL_Alarm,401201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_2_SI.OR_Alarm,401201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_2_SI.UR_Alarm,401201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_2_SI.ROC_Alarm,401201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_2_SI.REST,401201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_2_SI.ALRM,401201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_SI.ANUN,401201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_SI.AKED,401201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_SI.Resetable,401201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_SI.HH_Fault,401201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_2_SI.H_Fault,401201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_2_SI.L_Fault,401201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_2_SI.LL_Fault,401201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_2_SI.BL_Fault,401201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_2_SI.OR_Fault,401201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_2_SI.UR_Fault,401201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_2_SI.ROC_Fault,401202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_2_SI.Tot_EN,401202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_2_SI.TAGR,401202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_SI.ACKN,401202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_2_SI.INTK,401202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_2_SI.PLCFault,401202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_SI.PLCIOFault,401202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_SI.INTK_EN,401202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_2_SI.Shelve,401202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_SI.Shelved,401202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_2_SI.Suppress,401202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_SI.Suppressed,401202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_2_SI.PCSuppress,401202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_SI.PCUnSuppress,401202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_SI.PCUnshelve,401202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_SI.GlobalReset,401400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_SI.HH_EN,401400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_3_SI.H_EN,401400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_3_SI.L_EN,401400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_3_SI.LL_EN,401400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_3_SI.BLEN,401400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_3_SI.OR_EN,401400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_3_SI.UREN,401400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_3_SI.RC_EN,401400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_3_SI.SuppressAA,401400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_3_SI.SuppressLA,401400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_3_SI.ConfigError,401400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_3_SI.HH_Alarm,401400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_3_SI.H_Alarm,401400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_3_SI.L_Alarm,401400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_3_SI.LL_Alarm,401400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_3_SI.BL_Alarm,401401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_3_SI.OR_Alarm,401401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_3_SI.UR_Alarm,401401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_3_SI.ROC_Alarm,401401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_3_SI.REST,401401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_3_SI.ALRM,401401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_SI.ANUN,401401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_SI.AKED,401401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_SI.Resetable,401401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_SI.HH_Fault,401401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_3_SI.H_Fault,401401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_3_SI.L_Fault,401401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_3_SI.LL_Fault,401401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_3_SI.BL_Fault,401401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_3_SI.OR_Fault,401401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_3_SI.UR_Fault,401401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_3_SI.ROC_Fault,401402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_3_SI.Tot_EN,401402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_3_SI.TAGR,401402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_SI.ACKN,401402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_3_SI.INTK,401402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_3_SI.PLCFault,401402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_SI.PLCIOFault,401402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_SI.INTK_EN,401402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_3_SI.Shelve,401402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_SI.Shelved,401402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_3_SI.Suppress,401402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_SI.Suppressed,401402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_3_SI.PCSuppress,401402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_SI.PCUnSuppress,401402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_SI.PCUnshelve,401402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_SI.GlobalReset,401600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_SI.HH_EN,401600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_4_SI.H_EN,401600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_4_SI.L_EN,401600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_4_SI.LL_EN,401600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_4_SI.BLEN,401600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_4_SI.OR_EN,401600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_4_SI.UREN,401600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_4_SI.RC_EN,401600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_4_SI.SuppressAA,401600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_4_SI.SuppressLA,401600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_4_SI.ConfigError,401600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_4_SI.HH_Alarm,401600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_4_SI.H_Alarm,401600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_4_SI.L_Alarm,401600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_4_SI.LL_Alarm,401600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_4_SI.BL_Alarm,401601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_4_SI.OR_Alarm,401601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_4_SI.UR_Alarm,401601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_4_SI.ROC_Alarm,401601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_4_SI.REST,401601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_4_SI.ALRM,401601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_SI.ANUN,401601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_SI.AKED,401601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_SI.Resetable,401601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_SI.HH_Fault,401601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_4_SI.H_Fault,401601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_4_SI.L_Fault,401601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_4_SI.LL_Fault,401601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_4_SI.BL_Fault,401601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_4_SI.OR_Fault,401601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_4_SI.UR_Fault,401601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_4_SI.ROC_Fault,401602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_4_SI.Tot_EN,401602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_4_SI.TAGR,401602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_SI.ACKN,401602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_4_SI.INTK,401602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_4_SI.PLCFault,401602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_SI.PLCIOFault,401602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_SI.INTK_EN,401602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_4_SI.Shelve,401602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_SI.Shelved,401602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_4_SI.Suppress,401602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_SI.Suppressed,401602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_4_SI.PCSuppress,401602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_SI.PCUnSuppress,401602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_SI.PCUnshelve,401602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_SI.GlobalReset,401800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_SI.HH_EN,401800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_5_SI.H_EN,401800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_5_SI.L_EN,401800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_5_SI.LL_EN,401800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_5_SI.BLEN,401800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_5_SI.OR_EN,401800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_5_SI.UREN,401800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_5_SI.RC_EN,401800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_5_SI.SuppressAA,401800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_5_SI.SuppressLA,401800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_5_SI.ConfigError,401800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_5_SI.HH_Alarm,401800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_5_SI.H_Alarm,401800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_5_SI.L_Alarm,401800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_5_SI.LL_Alarm,401800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_5_SI.BL_Alarm,401801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_5_SI.OR_Alarm,401801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_5_SI.UR_Alarm,401801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_5_SI.ROC_Alarm,401801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_5_SI.REST,401801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_5_SI.ALRM,401801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_SI.ANUN,401801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_SI.AKED,401801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_SI.Resetable,401801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_SI.HH_Fault,401801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_5_SI.H_Fault,401801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_5_SI.L_Fault,401801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_5_SI.LL_Fault,401801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_5_SI.BL_Fault,401801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_5_SI.OR_Fault,401801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_5_SI.UR_Fault,401801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_5_SI.ROC_Fault,401802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_5_SI.Tot_EN,401802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_5_SI.TAGR,401802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_SI.ACKN,401802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_5_SI.INTK,401802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_5_SI.PLCFault,401802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_SI.PLCIOFault,401802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_SI.INTK_EN,401802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_5_SI.Shelve,401802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_SI.Shelved,401802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_5_SI.Suppress,401802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_SI.Suppressed,401802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_5_SI.PCSuppress,401802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_SI.PCUnSuppress,401802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_SI.PCUnshelve,401802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_SI.GlobalReset,402000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_SI.HH_EN,402000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_6_SI.H_EN,402000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_6_SI.L_EN,402000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_6_SI.LL_EN,402000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_6_SI.BLEN,402000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_6_SI.OR_EN,402000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_6_SI.UREN,402000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_6_SI.RC_EN,402000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_6_SI.SuppressAA,402000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_6_SI.SuppressLA,402000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_6_SI.ConfigError,402000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_6_SI.HH_Alarm,402000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_6_SI.H_Alarm,402000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_6_SI.L_Alarm,402000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_6_SI.LL_Alarm,402000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_6_SI.BL_Alarm,402001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_6_SI.OR_Alarm,402001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_6_SI.UR_Alarm,402001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_6_SI.ROC_Alarm,402001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_6_SI.REST,402001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_6_SI.ALRM,402001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_SI.ANUN,402001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_SI.AKED,402001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_SI.Resetable,402001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_SI.HH_Fault,402001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_6_SI.H_Fault,402001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_6_SI.L_Fault,402001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_6_SI.LL_Fault,402001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_6_SI.BL_Fault,402001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_6_SI.OR_Fault,402001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_6_SI.UR_Fault,402001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_6_SI.ROC_Fault,402002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_6_SI.Tot_EN,402002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_6_SI.TAGR,402002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_SI.ACKN,402002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_6_SI.INTK,402002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_6_SI.PLCFault,402002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_SI.PLCIOFault,402002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_SI.INTK_EN,402002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_6_SI.Shelve,402002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_SI.Shelved,402002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_6_SI.Suppress,402002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_SI.Suppressed,402002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_6_SI.PCSuppress,402002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_SI.PCUnSuppress,402002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_SI.PCUnshelve,402002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_SI.GlobalReset,402200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_SI.HH_EN,402200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_7_SI.H_EN,402200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_7_SI.L_EN,402200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_7_SI.LL_EN,402200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_7_SI.BLEN,402200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_7_SI.OR_EN,402200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_7_SI.UREN,402200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_7_SI.RC_EN,402200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_7_SI.SuppressAA,402200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_7_SI.SuppressLA,402200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_7_SI.ConfigError,402200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_7_SI.HH_Alarm,402200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_7_SI.H_Alarm,402200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_7_SI.L_Alarm,402200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_7_SI.LL_Alarm,402200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_7_SI.BL_Alarm,402201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_7_SI.OR_Alarm,402201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_7_SI.UR_Alarm,402201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_7_SI.ROC_Alarm,402201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_7_SI.REST,402201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_7_SI.ALRM,402201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_SI.ANUN,402201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_SI.AKED,402201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_SI.Resetable,402201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_SI.HH_Fault,402201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_7_SI.H_Fault,402201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_7_SI.L_Fault,402201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_7_SI.LL_Fault,402201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_7_SI.BL_Fault,402201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_7_SI.OR_Fault,402201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_7_SI.UR_Fault,402201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_7_SI.ROC_Fault,402202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_7_SI.Tot_EN,402202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_7_SI.TAGR,402202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_SI.ACKN,402202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_7_SI.INTK,402202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_7_SI.PLCFault,402202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_SI.PLCIOFault,402202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_SI.INTK_EN,402202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_7_SI.Shelve,402202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_SI.Shelved,402202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_7_SI.Suppress,402202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_SI.Suppressed,402202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_7_SI.PCSuppress,402202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_SI.PCUnSuppress,402202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_SI.PCUnshelve,402202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_SI.GlobalReset,402400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_SI.HH_EN,402400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_8_SI.H_EN,402400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_8_SI.L_EN,402400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_8_SI.LL_EN,402400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_8_SI.BLEN,402400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_8_SI.OR_EN,402400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_8_SI.UREN,402400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_8_SI.RC_EN,402400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_8_SI.SuppressAA,402400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_8_SI.SuppressLA,402400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_8_SI.ConfigError,402400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_8_SI.HH_Alarm,402400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_8_SI.H_Alarm,402400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_8_SI.L_Alarm,402400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_8_SI.LL_Alarm,402400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_8_SI.BL_Alarm,402401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_8_SI.OR_Alarm,402401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_8_SI.UR_Alarm,402401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_8_SI.ROC_Alarm,402401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_8_SI.REST,402401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_8_SI.ALRM,402401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_SI.ANUN,402401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_SI.AKED,402401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_SI.Resetable,402401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_SI.HH_Fault,402401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_8_SI.H_Fault,402401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_8_SI.L_Fault,402401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_8_SI.LL_Fault,402401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_8_SI.BL_Fault,402401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_8_SI.OR_Fault,402401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_8_SI.UR_Fault,402401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_8_SI.ROC_Fault,402402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_8_SI.Tot_EN,402402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_8_SI.TAGR,402402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_SI.ACKN,402402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_8_SI.INTK,402402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_8_SI.PLCFault,402402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_SI.PLCIOFault,402402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_SI.INTK_EN,402402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_8_SI.Shelve,402402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_SI.Shelved,402402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_8_SI.Suppress,402402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_SI.Suppressed,402402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_8_SI.PCSuppress,402402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_SI.PCUnSuppress,402402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_SI.PCUnshelve,402402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_SI.GlobalReset,402600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_SI.HH_EN,402600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_AFD_0103_9_SI.H_EN,402600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_AFD_0103_9_SI.L_EN,402600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_AFD_0103_9_SI.LL_EN,402600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_AFD_0103_9_SI.BLEN,402600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_AFD_0103_9_SI.OR_EN,402600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_AFD_0103_9_SI.UREN,402600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_AFD_0103_9_SI.RC_EN,402600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_AFD_0103_9_SI.SuppressAA,402600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_AFD_0103_9_SI.SuppressLA,402600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_AFD_0103_9_SI.ConfigError,402600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_AFD_0103_9_SI.HH_Alarm,402600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_AFD_0103_9_SI.H_Alarm,402600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_AFD_0103_9_SI.L_Alarm,402600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_AFD_0103_9_SI.LL_Alarm,402600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_AFD_0103_9_SI.BL_Alarm,402601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_AFD_0103_9_SI.OR_Alarm,402601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_AFD_0103_9_SI.UR_Alarm,402601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_AFD_0103_9_SI.ROC_Alarm,402601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_AFD_0103_9_SI.REST,402601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_AFD_0103_9_SI.ALRM,402601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_SI.ANUN,402601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_SI.AKED,402601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_SI.Resetable,402601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_SI.HH_Fault,402601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_AFD_0103_9_SI.H_Fault,402601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_AFD_0103_9_SI.L_Fault,402601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_AFD_0103_9_SI.LL_Fault,402601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_AFD_0103_9_SI.BL_Fault,402601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_AFD_0103_9_SI.OR_Fault,402601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_AFD_0103_9_SI.UR_Fault,402601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_AFD_0103_9_SI.ROC_Fault,402602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_AFD_0103_9_SI.Tot_EN,402602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_AFD_0103_9_SI.TAGR,402602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_SI.ACKN,402602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_9_SI.INTK,402602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_AFD_0103_9_SI.PLCFault,402602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_SI.PLCIOFault,402602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_SI.INTK_EN,402602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_AFD_0103_9_SI.Shelve,402602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_SI.Shelved,402602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_AFD_0103_9_SI.Suppress,402602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_SI.Suppressed,402602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_AFD_0103_9_SI.PCSuppress,402602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_SI.PCUnSuppress,402602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_SI.PCUnshelve,402602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI1.GlobalReset,402800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI1.HH_EN,402800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI1.H_EN,402800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI1.L_EN,402800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI1.LL_EN,402800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI1.BLEN,402800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI1.OR_EN,402800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI1.UREN,402800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI1.RC_EN,402800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI1.SuppressAA,402800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI1.SuppressLA,402800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI1.ConfigError,402800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI1.HH_Alarm,402800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI1.H_Alarm,402800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI1.L_Alarm,402800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI1.LL_Alarm,402800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI1.BL_Alarm,402801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI1.OR_Alarm,402801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI1.UR_Alarm,402801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI1.ROC_Alarm,402801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI1.REST,402801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI1.ALRM,402801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI1.ANUN,402801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI1.AKED,402801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI1.Resetable,402801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI1.HH_Fault,402801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI1.H_Fault,402801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI1.L_Fault,402801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI1.LL_Fault,402801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI1.BL_Fault,402801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI1.OR_Fault,402801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI1.UR_Fault,402801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI1.ROC_Fault,402802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI1.Tot_EN,402802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI1.TAGR,402802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI1.ACKN,402802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI1.INTK,402802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI1.PLCFault,402802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI1.PLCIOFault,402802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI1.INTK_EN,402802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI1.Shelve,402802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI1.Shelved,402802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI1.Suppress,402802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI1.Suppressed,402802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI1.PCSuppress,402802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI1.PCUnSuppress,402802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI1.PCUnshelve,402802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI2.GlobalReset,403000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI2.HH_EN,403000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI2.H_EN,403000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI2.L_EN,403000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI2.LL_EN,403000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI2.BLEN,403000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI2.OR_EN,403000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI2.UREN,403000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI2.RC_EN,403000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI2.SuppressAA,403000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI2.SuppressLA,403000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI2.ConfigError,403000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI2.HH_Alarm,403000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI2.H_Alarm,403000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI2.L_Alarm,403000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI2.LL_Alarm,403000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI2.BL_Alarm,403001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI2.OR_Alarm,403001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI2.UR_Alarm,403001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI2.ROC_Alarm,403001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI2.REST,403001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI2.ALRM,403001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI2.ANUN,403001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI2.AKED,403001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI2.Resetable,403001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI2.HH_Fault,403001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI2.H_Fault,403001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI2.L_Fault,403001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI2.LL_Fault,403001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI2.BL_Fault,403001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI2.OR_Fault,403001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI2.UR_Fault,403001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI2.ROC_Fault,403002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI2.Tot_EN,403002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI2.TAGR,403002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI2.ACKN,403002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI2.INTK,403002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI2.PLCFault,403002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI2.PLCIOFault,403002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI2.INTK_EN,403002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI2.Shelve,403002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI2.Shelved,403002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI2.Suppress,403002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI2.Suppressed,403002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI2.PCSuppress,403002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI2.PCUnSuppress,403002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI2.PCUnshelve,403002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI3.GlobalReset,403200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI3.HH_EN,403200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI3.H_EN,403200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI3.L_EN,403200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI3.LL_EN,403200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI3.BLEN,403200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI3.OR_EN,403200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI3.UREN,403200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI3.RC_EN,403200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI3.SuppressAA,403200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI3.SuppressLA,403200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI3.ConfigError,403200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI3.HH_Alarm,403200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI3.H_Alarm,403200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI3.L_Alarm,403200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI3.LL_Alarm,403200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI3.BL_Alarm,403201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI3.OR_Alarm,403201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI3.UR_Alarm,403201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI3.ROC_Alarm,403201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI3.REST,403201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI3.ALRM,403201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI3.ANUN,403201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI3.AKED,403201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI3.Resetable,403201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI3.HH_Fault,403201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI3.H_Fault,403201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI3.L_Fault,403201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI3.LL_Fault,403201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI3.BL_Fault,403201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI3.OR_Fault,403201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI3.UR_Fault,403201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI3.ROC_Fault,403202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI3.Tot_EN,403202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI3.TAGR,403202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI3.ACKN,403202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI3.INTK,403202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI3.PLCFault,403202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI3.PLCIOFault,403202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI3.INTK_EN,403202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI3.Shelve,403202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI3.Shelved,403202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI3.Suppress,403202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI3.Suppressed,403202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI3.PCSuppress,403202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI3.PCUnSuppress,403202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI3.PCUnshelve,403202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI4.GlobalReset,403400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI4.HH_EN,403400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI4.H_EN,403400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI4.L_EN,403400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI4.LL_EN,403400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI4.BLEN,403400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI4.OR_EN,403400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI4.UREN,403400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI4.RC_EN,403400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI4.SuppressAA,403400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI4.SuppressLA,403400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI4.ConfigError,403400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI4.HH_Alarm,403400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI4.H_Alarm,403400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI4.L_Alarm,403400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI4.LL_Alarm,403400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI4.BL_Alarm,403401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI4.OR_Alarm,403401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI4.UR_Alarm,403401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI4.ROC_Alarm,403401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI4.REST,403401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI4.ALRM,403401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI4.ANUN,403401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI4.AKED,403401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI4.Resetable,403401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI4.HH_Fault,403401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI4.H_Fault,403401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI4.L_Fault,403401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI4.LL_Fault,403401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI4.BL_Fault,403401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI4.OR_Fault,403401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI4.UR_Fault,403401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI4.ROC_Fault,403402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI4.Tot_EN,403402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI4.TAGR,403402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI4.ACKN,403402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI4.INTK,403402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI4.PLCFault,403402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI4.PLCIOFault,403402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI4.INTK_EN,403402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI4.Shelve,403402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI4.Shelved,403402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI4.Suppress,403402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI4.Suppressed,403402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI4.PCSuppress,403402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI4.PCUnSuppress,403402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI4.PCUnshelve,403402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI5.GlobalReset,403600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI5.HH_EN,403600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI5.H_EN,403600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI5.L_EN,403600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI5.LL_EN,403600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI5.BLEN,403600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI5.OR_EN,403600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI5.UREN,403600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI5.RC_EN,403600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI5.SuppressAA,403600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI5.SuppressLA,403600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI5.ConfigError,403600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI5.HH_Alarm,403600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI5.H_Alarm,403600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI5.L_Alarm,403600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI5.LL_Alarm,403600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI5.BL_Alarm,403601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI5.OR_Alarm,403601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI5.UR_Alarm,403601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI5.ROC_Alarm,403601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI5.REST,403601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI5.ALRM,403601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI5.ANUN,403601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI5.AKED,403601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI5.Resetable,403601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI5.HH_Fault,403601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI5.H_Fault,403601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI5.L_Fault,403601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI5.LL_Fault,403601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI5.BL_Fault,403601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI5.OR_Fault,403601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI5.UR_Fault,403601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI5.ROC_Fault,403602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI5.Tot_EN,403602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI5.TAGR,403602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI5.ACKN,403602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI5.INTK,403602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI5.PLCFault,403602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI5.PLCIOFault,403602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI5.INTK_EN,403602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI5.Shelve,403602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI5.Shelved,403602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI5.Suppress,403602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI5.Suppressed,403602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI5.PCSuppress,403602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI5.PCUnSuppress,403602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI5.PCUnshelve,403602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI6.GlobalReset,403800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI6.HH_EN,403800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI6.H_EN,403800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI6.L_EN,403800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI6.LL_EN,403800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI6.BLEN,403800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI6.OR_EN,403800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI6.UREN,403800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI6.RC_EN,403800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI6.SuppressAA,403800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI6.SuppressLA,403800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI6.ConfigError,403800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI6.HH_Alarm,403800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI6.H_Alarm,403800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI6.L_Alarm,403800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI6.LL_Alarm,403800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI6.BL_Alarm,403801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI6.OR_Alarm,403801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI6.UR_Alarm,403801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI6.ROC_Alarm,403801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI6.REST,403801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI6.ALRM,403801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI6.ANUN,403801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI6.AKED,403801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI6.Resetable,403801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI6.HH_Fault,403801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI6.H_Fault,403801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI6.L_Fault,403801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI6.LL_Fault,403801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI6.BL_Fault,403801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI6.OR_Fault,403801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI6.UR_Fault,403801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI6.ROC_Fault,403802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI6.Tot_EN,403802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI6.TAGR,403802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI6.ACKN,403802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI6.INTK,403802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI6.PLCFault,403802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI6.PLCIOFault,403802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI6.INTK_EN,403802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI6.Shelve,403802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI6.Shelved,403802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI6.Suppress,403802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI6.Suppressed,403802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI6.PCSuppress,403802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI6.PCUnSuppress,403802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI6.PCUnshelve,403802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI7.GlobalReset,404000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI7.HH_EN,404000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI7.H_EN,404000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI7.L_EN,404000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI7.LL_EN,404000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI7.BLEN,404000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI7.OR_EN,404000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI7.UREN,404000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI7.RC_EN,404000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI7.SuppressAA,404000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI7.SuppressLA,404000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI7.ConfigError,404000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI7.HH_Alarm,404000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI7.H_Alarm,404000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI7.L_Alarm,404000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI7.LL_Alarm,404000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI7.BL_Alarm,404001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI7.OR_Alarm,404001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI7.UR_Alarm,404001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI7.ROC_Alarm,404001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI7.REST,404001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI7.ALRM,404001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI7.ANUN,404001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI7.AKED,404001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI7.Resetable,404001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI7.HH_Fault,404001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI7.H_Fault,404001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI7.L_Fault,404001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI7.LL_Fault,404001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI7.BL_Fault,404001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI7.OR_Fault,404001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI7.UR_Fault,404001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI7.ROC_Fault,404002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI7.Tot_EN,404002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI7.TAGR,404002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI7.ACKN,404002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI7.INTK,404002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI7.PLCFault,404002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI7.PLCIOFault,404002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI7.INTK_EN,404002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI7.Shelve,404002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI7.Shelved,404002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI7.Suppress,404002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI7.Suppressed,404002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI7.PCSuppress,404002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI7.PCUnSuppress,404002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI7.PCUnshelve,404002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI8.GlobalReset,404200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI8.HH_EN,404200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI8.H_EN,404200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI8.L_EN,404200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI8.LL_EN,404200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI8.BLEN,404200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI8.OR_EN,404200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI8.UREN,404200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI8.RC_EN,404200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI8.SuppressAA,404200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI8.SuppressLA,404200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI8.ConfigError,404200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI8.HH_Alarm,404200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI8.H_Alarm,404200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI8.L_Alarm,404200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI8.LL_Alarm,404200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI8.BL_Alarm,404201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI8.OR_Alarm,404201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI8.UR_Alarm,404201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI8.ROC_Alarm,404201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI8.REST,404201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI8.ALRM,404201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI8.ANUN,404201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI8.AKED,404201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI8.Resetable,404201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI8.HH_Fault,404201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI8.H_Fault,404201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI8.L_Fault,404201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI8.LL_Fault,404201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI8.BL_Fault,404201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI8.OR_Fault,404201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI8.UR_Fault,404201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI8.ROC_Fault,404202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI8.Tot_EN,404202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI8.TAGR,404202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI8.ACKN,404202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI8.INTK,404202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI8.PLCFault,404202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI8.PLCIOFault,404202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI8.INTK_EN,404202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI8.Shelve,404202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI8.Shelved,404202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI8.Suppress,404202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI8.Suppressed,404202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI8.PCSuppress,404202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI8.PCUnSuppress,404202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI8.PCUnshelve,404202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0116_1_FI9.GlobalReset,404400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_CP_0116_1_FI9.HH_EN,404400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_CP_0116_1_FI9.H_EN,404400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_CP_0116_1_FI9.L_EN,404400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_CP_0116_1_FI9.LL_EN,404400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_CP_0116_1_FI9.BLEN,404400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_CP_0116_1_FI9.OR_EN,404400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_CP_0116_1_FI9.UREN,404400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_CP_0116_1_FI9.RC_EN,404400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_CP_0116_1_FI9.SuppressAA,404400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_CP_0116_1_FI9.SuppressLA,404400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_CP_0116_1_FI9.ConfigError,404400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_CP_0116_1_FI9.HH_Alarm,404400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_CP_0116_1_FI9.H_Alarm,404400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_CP_0116_1_FI9.L_Alarm,404400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_CP_0116_1_FI9.LL_Alarm,404400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_CP_0116_1_FI9.BL_Alarm,404401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_CP_0116_1_FI9.OR_Alarm,404401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_CP_0116_1_FI9.UR_Alarm,404401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_CP_0116_1_FI9.ROC_Alarm,404401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_CP_0116_1_FI9.REST,404401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_CP_0116_1_FI9.ALRM,404401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_CP_0116_1_FI9.ANUN,404401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0116_1_FI9.AKED,404401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0116_1_FI9.Resetable,404401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0116_1_FI9.HH_Fault,404401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_CP_0116_1_FI9.H_Fault,404401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_CP_0116_1_FI9.L_Fault,404401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_CP_0116_1_FI9.LL_Fault,404401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_CP_0116_1_FI9.BL_Fault,404401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_CP_0116_1_FI9.OR_Fault,404401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_CP_0116_1_FI9.UR_Fault,404401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_CP_0116_1_FI9.ROC_Fault,404402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_CP_0116_1_FI9.Tot_EN,404402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_CP_0116_1_FI9.TAGR,404402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_CP_0116_1_FI9.ACKN,404402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_CP_0116_1_FI9.INTK,404402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_CP_0116_1_FI9.PLCFault,404402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI9.PLCIOFault,404402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0116_1_FI9.INTK_EN,404402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_CP_0116_1_FI9.Shelve,404402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_CP_0116_1_FI9.Shelved,404402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_CP_0116_1_FI9.Suppress,404402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_CP_0116_1_FI9.Suppressed,404402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_CP_0116_1_FI9.PCSuppress,404402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_CP_0116_1_FI9.PCUnSuppress,404402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0116_1_FI9.PCUnshelve,404402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2A_ZI.GlobalReset,404600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FCV_0113_2A_ZI.HH_EN,404600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FCV_0113_2A_ZI.H_EN,404600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FCV_0113_2A_ZI.L_EN,404600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FCV_0113_2A_ZI.LL_EN,404600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FCV_0113_2A_ZI.BLEN,404600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FCV_0113_2A_ZI.OR_EN,404600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FCV_0113_2A_ZI.UREN,404600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FCV_0113_2A_ZI.RC_EN,404600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FCV_0113_2A_ZI.SuppressAA,404600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FCV_0113_2A_ZI.SuppressLA,404600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FCV_0113_2A_ZI.ConfigError,404600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FCV_0113_2A_ZI.HH_Alarm,404600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FCV_0113_2A_ZI.H_Alarm,404600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FCV_0113_2A_ZI.L_Alarm,404600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FCV_0113_2A_ZI.LL_Alarm,404600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FCV_0113_2A_ZI.BL_Alarm,404601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FCV_0113_2A_ZI.OR_Alarm,404601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FCV_0113_2A_ZI.UR_Alarm,404601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FCV_0113_2A_ZI.ROC_Alarm,404601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FCV_0113_2A_ZI.REST,404601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FCV_0113_2A_ZI.ALRM,404601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FCV_0113_2A_ZI.ANUN,404601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FCV_0113_2A_ZI.AKED,404601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FCV_0113_2A_ZI.Resetable,404601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2A_ZI.HH_Fault,404601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FCV_0113_2A_ZI.H_Fault,404601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FCV_0113_2A_ZI.L_Fault,404601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FCV_0113_2A_ZI.LL_Fault,404601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FCV_0113_2A_ZI.BL_Fault,404601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FCV_0113_2A_ZI.OR_Fault,404601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FCV_0113_2A_ZI.UR_Fault,404601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FCV_0113_2A_ZI.ROC_Fault,404602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FCV_0113_2A_ZI.Tot_EN,404602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FCV_0113_2A_ZI.TAGR,404602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FCV_0113_2A_ZI.ACKN,404602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FCV_0113_2A_ZI.INTK,404602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FCV_0113_2A_ZI.PLCFault,404602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A_ZI.PLCIOFault,404602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A_ZI.INTK_EN,404602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FCV_0113_2A_ZI.Shelve,404602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2A_ZI.Shelved,404602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FCV_0113_2A_ZI.Suppress,404602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2A_ZI.Suppressed,404602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FCV_0113_2A_ZI.PCSuppress,404602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2A_ZI.PCUnSuppress,404602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2A_ZI.PCUnshelve,404602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2B_ZI.GlobalReset,404800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FCV_0113_2B_ZI.HH_EN,404800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FCV_0113_2B_ZI.H_EN,404800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FCV_0113_2B_ZI.L_EN,404800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FCV_0113_2B_ZI.LL_EN,404800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FCV_0113_2B_ZI.BLEN,404800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FCV_0113_2B_ZI.OR_EN,404800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FCV_0113_2B_ZI.UREN,404800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FCV_0113_2B_ZI.RC_EN,404800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FCV_0113_2B_ZI.SuppressAA,404800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FCV_0113_2B_ZI.SuppressLA,404800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FCV_0113_2B_ZI.ConfigError,404800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FCV_0113_2B_ZI.HH_Alarm,404800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FCV_0113_2B_ZI.H_Alarm,404800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FCV_0113_2B_ZI.L_Alarm,404800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FCV_0113_2B_ZI.LL_Alarm,404800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FCV_0113_2B_ZI.BL_Alarm,404801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FCV_0113_2B_ZI.OR_Alarm,404801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FCV_0113_2B_ZI.UR_Alarm,404801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FCV_0113_2B_ZI.ROC_Alarm,404801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FCV_0113_2B_ZI.REST,404801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FCV_0113_2B_ZI.ALRM,404801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FCV_0113_2B_ZI.ANUN,404801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FCV_0113_2B_ZI.AKED,404801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FCV_0113_2B_ZI.Resetable,404801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2B_ZI.HH_Fault,404801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FCV_0113_2B_ZI.H_Fault,404801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FCV_0113_2B_ZI.L_Fault,404801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FCV_0113_2B_ZI.LL_Fault,404801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FCV_0113_2B_ZI.BL_Fault,404801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FCV_0113_2B_ZI.OR_Fault,404801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FCV_0113_2B_ZI.UR_Fault,404801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FCV_0113_2B_ZI.ROC_Fault,404802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FCV_0113_2B_ZI.Tot_EN,404802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FCV_0113_2B_ZI.TAGR,404802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FCV_0113_2B_ZI.ACKN,404802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FCV_0113_2B_ZI.INTK,404802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FCV_0113_2B_ZI.PLCFault,404802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B_ZI.PLCIOFault,404802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B_ZI.INTK_EN,404802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FCV_0113_2B_ZI.Shelve,404802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2B_ZI.Shelved,404802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FCV_0113_2B_ZI.Suppress,404802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2B_ZI.Suppressed,404802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FCV_0113_2B_ZI.PCSuppress,404802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2B_ZI.PCUnSuppress,404802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2B_ZI.PCUnshelve,404802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FIT_0113_2A_FI.GlobalReset,405000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FIT_0113_2A_FI.HH_EN,405000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FIT_0113_2A_FI.H_EN,405000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FIT_0113_2A_FI.L_EN,405000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FIT_0113_2A_FI.LL_EN,405000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FIT_0113_2A_FI.BLEN,405000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FIT_0113_2A_FI.OR_EN,405000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FIT_0113_2A_FI.UREN,405000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FIT_0113_2A_FI.RC_EN,405000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FIT_0113_2A_FI.SuppressAA,405000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FIT_0113_2A_FI.SuppressLA,405000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FIT_0113_2A_FI.ConfigError,405000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FIT_0113_2A_FI.HH_Alarm,405000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FIT_0113_2A_FI.H_Alarm,405000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FIT_0113_2A_FI.L_Alarm,405000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FIT_0113_2A_FI.LL_Alarm,405000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FIT_0113_2A_FI.BL_Alarm,405001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FIT_0113_2A_FI.OR_Alarm,405001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FIT_0113_2A_FI.UR_Alarm,405001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FIT_0113_2A_FI.ROC_Alarm,405001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FIT_0113_2A_FI.REST,405001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FIT_0113_2A_FI.ALRM,405001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FIT_0113_2A_FI.ANUN,405001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FIT_0113_2A_FI.AKED,405001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FIT_0113_2A_FI.Resetable,405001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FIT_0113_2A_FI.HH_Fault,405001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FIT_0113_2A_FI.H_Fault,405001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FIT_0113_2A_FI.L_Fault,405001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FIT_0113_2A_FI.LL_Fault,405001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FIT_0113_2A_FI.BL_Fault,405001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FIT_0113_2A_FI.OR_Fault,405001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FIT_0113_2A_FI.UR_Fault,405001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FIT_0113_2A_FI.ROC_Fault,405002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FIT_0113_2A_FI.Tot_EN,405002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FIT_0113_2A_FI.TAGR,405002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FIT_0113_2A_FI.ACKN,405002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FIT_0113_2A_FI.INTK,405002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FIT_0113_2A_FI.PLCFault,405002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FIT_0113_2A_FI.PLCIOFault,405002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FIT_0113_2A_FI.INTK_EN,405002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FIT_0113_2A_FI.Shelve,405002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FIT_0113_2A_FI.Shelved,405002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FIT_0113_2A_FI.Suppress,405002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FIT_0113_2A_FI.Suppressed,405002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FIT_0113_2A_FI.PCSuppress,405002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FIT_0113_2A_FI.PCUnSuppress,405002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FIT_0113_2A_FI.PCUnshelve,405002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1B_ZI.GlobalReset,405200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_1B_ZI.HH_EN,405200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_1B_ZI.H_EN,405200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_1B_ZI.L_EN,405200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_1B_ZI.LL_EN,405200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_1B_ZI.BLEN,405200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_1B_ZI.OR_EN,405200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_1B_ZI.UREN,405200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_1B_ZI.RC_EN,405200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_1B_ZI.SuppressAA,405200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_1B_ZI.SuppressLA,405200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_1B_ZI.ConfigError,405200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_1B_ZI.HH_Alarm,405200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_1B_ZI.H_Alarm,405200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_1B_ZI.L_Alarm,405200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_1B_ZI.LL_Alarm,405200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_1B_ZI.BL_Alarm,405201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_1B_ZI.OR_Alarm,405201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_1B_ZI.UR_Alarm,405201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_1B_ZI.ROC_Alarm,405201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_1B_ZI.REST,405201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_1B_ZI.ALRM,405201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_1B_ZI.ANUN,405201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_1B_ZI.AKED,405201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_1B_ZI.Resetable,405201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1B_ZI.HH_Fault,405201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_1B_ZI.H_Fault,405201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_1B_ZI.L_Fault,405201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_1B_ZI.LL_Fault,405201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_1B_ZI.BL_Fault,405201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_1B_ZI.OR_Fault,405201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_1B_ZI.UR_Fault,405201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_1B_ZI.ROC_Fault,405202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_1B_ZI.Tot_EN,405202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_1B_ZI.TAGR,405202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_1B_ZI.ACKN,405202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_1B_ZI.INTK,405202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_1B_ZI.PLCFault,405202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZI.PLCIOFault,405202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZI.INTK_EN,405202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_1B_ZI.Shelve,405202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_1B_ZI.Shelved,405202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_1B_ZI.Suppress,405202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_1B_ZI.Suppressed,405202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_1B_ZI.PCSuppress,405202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1B_ZI.PCUnSuppress,405202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1B_ZI.PCUnshelve,405202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2B_ZI.GlobalReset,405400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_2B_ZI.HH_EN,405400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_2B_ZI.H_EN,405400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_2B_ZI.L_EN,405400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_2B_ZI.LL_EN,405400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_2B_ZI.BLEN,405400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_2B_ZI.OR_EN,405400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_2B_ZI.UREN,405400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_2B_ZI.RC_EN,405400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_2B_ZI.SuppressAA,405400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_2B_ZI.SuppressLA,405400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_2B_ZI.ConfigError,405400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_2B_ZI.HH_Alarm,405400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_2B_ZI.H_Alarm,405400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_2B_ZI.L_Alarm,405400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_2B_ZI.LL_Alarm,405400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_2B_ZI.BL_Alarm,405401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_2B_ZI.OR_Alarm,405401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_2B_ZI.UR_Alarm,405401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_2B_ZI.ROC_Alarm,405401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_2B_ZI.REST,405401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_2B_ZI.ALRM,405401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_2B_ZI.ANUN,405401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_2B_ZI.AKED,405401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_2B_ZI.Resetable,405401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2B_ZI.HH_Fault,405401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_2B_ZI.H_Fault,405401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_2B_ZI.L_Fault,405401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_2B_ZI.LL_Fault,405401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_2B_ZI.BL_Fault,405401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_2B_ZI.OR_Fault,405401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_2B_ZI.UR_Fault,405401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_2B_ZI.ROC_Fault,405402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_2B_ZI.Tot_EN,405402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_2B_ZI.TAGR,405402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_2B_ZI.ACKN,405402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_2B_ZI.INTK,405402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_2B_ZI.PLCFault,405402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZI.PLCIOFault,405402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZI.INTK_EN,405402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_2B_ZI.Shelve,405402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_2B_ZI.Shelved,405402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_2B_ZI.Suppress,405402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_2B_ZI.Suppressed,405402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_2B_ZI.PCSuppress,405402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2B_ZI.PCUnSuppress,405402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2B_ZI.PCUnshelve,405402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3B_ZI.GlobalReset,405600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3B_ZI.HH_EN,405600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_3B_ZI.H_EN,405600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_3B_ZI.L_EN,405600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_3B_ZI.LL_EN,405600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_3B_ZI.BLEN,405600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_3B_ZI.OR_EN,405600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_3B_ZI.UREN,405600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_3B_ZI.RC_EN,405600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_3B_ZI.SuppressAA,405600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_3B_ZI.SuppressLA,405600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_3B_ZI.ConfigError,405600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_3B_ZI.HH_Alarm,405600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_3B_ZI.H_Alarm,405600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_3B_ZI.L_Alarm,405600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_3B_ZI.LL_Alarm,405600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_3B_ZI.BL_Alarm,405601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_3B_ZI.OR_Alarm,405601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_3B_ZI.UR_Alarm,405601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_3B_ZI.ROC_Alarm,405601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_3B_ZI.REST,405601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_3B_ZI.ALRM,405601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3B_ZI.ANUN,405601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3B_ZI.AKED,405601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3B_ZI.Resetable,405601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3B_ZI.HH_Fault,405601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_3B_ZI.H_Fault,405601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_3B_ZI.L_Fault,405601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_3B_ZI.LL_Fault,405601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_3B_ZI.BL_Fault,405601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_3B_ZI.OR_Fault,405601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_3B_ZI.UR_Fault,405601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_3B_ZI.ROC_Fault,405602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_3B_ZI.Tot_EN,405602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_3B_ZI.TAGR,405602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_3B_ZI.ACKN,405602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_3B_ZI.INTK,405602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_3B_ZI.PLCFault,405602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZI.PLCIOFault,405602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZI.INTK_EN,405602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_3B_ZI.Shelve,405602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_3B_ZI.Shelved,405602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_3B_ZI.Suppress,405602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_3B_ZI.Suppressed,405602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_3B_ZI.PCSuppress,405602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3B_ZI.PCUnSuppress,405602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3B_ZI.PCUnshelve,405602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4B_ZI.GlobalReset,405800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4B_ZI.HH_EN,405800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_4B_ZI.H_EN,405800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_4B_ZI.L_EN,405800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_4B_ZI.LL_EN,405800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_4B_ZI.BLEN,405800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_4B_ZI.OR_EN,405800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_4B_ZI.UREN,405800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_4B_ZI.RC_EN,405800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_4B_ZI.SuppressAA,405800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_4B_ZI.SuppressLA,405800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_4B_ZI.ConfigError,405800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_4B_ZI.HH_Alarm,405800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_4B_ZI.H_Alarm,405800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_4B_ZI.L_Alarm,405800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_4B_ZI.LL_Alarm,405800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_4B_ZI.BL_Alarm,405801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_4B_ZI.OR_Alarm,405801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_4B_ZI.UR_Alarm,405801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_4B_ZI.ROC_Alarm,405801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_4B_ZI.REST,405801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_4B_ZI.ALRM,405801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4B_ZI.ANUN,405801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4B_ZI.AKED,405801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4B_ZI.Resetable,405801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4B_ZI.HH_Fault,405801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_4B_ZI.H_Fault,405801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_4B_ZI.L_Fault,405801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_4B_ZI.LL_Fault,405801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_4B_ZI.BL_Fault,405801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_4B_ZI.OR_Fault,405801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_4B_ZI.UR_Fault,405801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_4B_ZI.ROC_Fault,405802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_4B_ZI.Tot_EN,405802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_4B_ZI.TAGR,405802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_4B_ZI.ACKN,405802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_4B_ZI.INTK,405802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_4B_ZI.PLCFault,405802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZI.PLCIOFault,405802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZI.INTK_EN,405802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_4B_ZI.Shelve,405802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_4B_ZI.Shelved,405802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_4B_ZI.Suppress,405802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_4B_ZI.Suppressed,405802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_4B_ZI.PCSuppress,405802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4B_ZI.PCUnSuppress,405802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4B_ZI.PCUnshelve,405802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5B_ZI.GlobalReset,406000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5B_ZI.HH_EN,406000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_5B_ZI.H_EN,406000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_5B_ZI.L_EN,406000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_5B_ZI.LL_EN,406000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_5B_ZI.BLEN,406000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_5B_ZI.OR_EN,406000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_5B_ZI.UREN,406000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_5B_ZI.RC_EN,406000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_5B_ZI.SuppressAA,406000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_5B_ZI.SuppressLA,406000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_5B_ZI.ConfigError,406000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_5B_ZI.HH_Alarm,406000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_5B_ZI.H_Alarm,406000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_5B_ZI.L_Alarm,406000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_5B_ZI.LL_Alarm,406000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_5B_ZI.BL_Alarm,406001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_5B_ZI.OR_Alarm,406001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_5B_ZI.UR_Alarm,406001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_5B_ZI.ROC_Alarm,406001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_5B_ZI.REST,406001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_5B_ZI.ALRM,406001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5B_ZI.ANUN,406001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5B_ZI.AKED,406001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5B_ZI.Resetable,406001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5B_ZI.HH_Fault,406001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_5B_ZI.H_Fault,406001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_5B_ZI.L_Fault,406001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_5B_ZI.LL_Fault,406001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_5B_ZI.BL_Fault,406001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_5B_ZI.OR_Fault,406001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_5B_ZI.UR_Fault,406001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_5B_ZI.ROC_Fault,406002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_5B_ZI.Tot_EN,406002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_5B_ZI.TAGR,406002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_5B_ZI.ACKN,406002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_5B_ZI.INTK,406002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_5B_ZI.PLCFault,406002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZI.PLCIOFault,406002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZI.INTK_EN,406002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_5B_ZI.Shelve,406002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_5B_ZI.Shelved,406002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_5B_ZI.Suppress,406002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_5B_ZI.Suppressed,406002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_5B_ZI.PCSuppress,406002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5B_ZI.PCUnSuppress,406002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5B_ZI.PCUnshelve,406002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6B_ZI.GlobalReset,406200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6B_ZI.HH_EN,406200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_6B_ZI.H_EN,406200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_6B_ZI.L_EN,406200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_6B_ZI.LL_EN,406200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_6B_ZI.BLEN,406200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_6B_ZI.OR_EN,406200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_6B_ZI.UREN,406200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_6B_ZI.RC_EN,406200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_6B_ZI.SuppressAA,406200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_6B_ZI.SuppressLA,406200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_6B_ZI.ConfigError,406200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_6B_ZI.HH_Alarm,406200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_6B_ZI.H_Alarm,406200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_6B_ZI.L_Alarm,406200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_6B_ZI.LL_Alarm,406200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_6B_ZI.BL_Alarm,406201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_6B_ZI.OR_Alarm,406201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_6B_ZI.UR_Alarm,406201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_6B_ZI.ROC_Alarm,406201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_6B_ZI.REST,406201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_6B_ZI.ALRM,406201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6B_ZI.ANUN,406201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6B_ZI.AKED,406201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6B_ZI.Resetable,406201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6B_ZI.HH_Fault,406201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_6B_ZI.H_Fault,406201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_6B_ZI.L_Fault,406201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_6B_ZI.LL_Fault,406201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_6B_ZI.BL_Fault,406201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_6B_ZI.OR_Fault,406201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_6B_ZI.UR_Fault,406201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_6B_ZI.ROC_Fault,406202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_6B_ZI.Tot_EN,406202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_6B_ZI.TAGR,406202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_6B_ZI.ACKN,406202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_6B_ZI.INTK,406202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_6B_ZI.PLCFault,406202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZI.PLCIOFault,406202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZI.INTK_EN,406202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_6B_ZI.Shelve,406202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_6B_ZI.Shelved,406202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_6B_ZI.Suppress,406202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_6B_ZI.Suppressed,406202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_6B_ZI.PCSuppress,406202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6B_ZI.PCUnSuppress,406202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6B_ZI.PCUnshelve,406202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7B_ZI.GlobalReset,406400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7B_ZI.HH_EN,406400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_7B_ZI.H_EN,406400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_7B_ZI.L_EN,406400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_7B_ZI.LL_EN,406400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_7B_ZI.BLEN,406400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_7B_ZI.OR_EN,406400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_7B_ZI.UREN,406400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_7B_ZI.RC_EN,406400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_7B_ZI.SuppressAA,406400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_7B_ZI.SuppressLA,406400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_7B_ZI.ConfigError,406400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_7B_ZI.HH_Alarm,406400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_7B_ZI.H_Alarm,406400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_7B_ZI.L_Alarm,406400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_7B_ZI.LL_Alarm,406400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_7B_ZI.BL_Alarm,406401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_7B_ZI.OR_Alarm,406401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_7B_ZI.UR_Alarm,406401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_7B_ZI.ROC_Alarm,406401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_7B_ZI.REST,406401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_7B_ZI.ALRM,406401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7B_ZI.ANUN,406401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7B_ZI.AKED,406401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7B_ZI.Resetable,406401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7B_ZI.HH_Fault,406401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_7B_ZI.H_Fault,406401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_7B_ZI.L_Fault,406401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_7B_ZI.LL_Fault,406401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_7B_ZI.BL_Fault,406401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_7B_ZI.OR_Fault,406401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_7B_ZI.UR_Fault,406401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_7B_ZI.ROC_Fault,406402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_7B_ZI.Tot_EN,406402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_7B_ZI.TAGR,406402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_7B_ZI.ACKN,406402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_7B_ZI.INTK,406402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_7B_ZI.PLCFault,406402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZI.PLCIOFault,406402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZI.INTK_EN,406402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_7B_ZI.Shelve,406402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_7B_ZI.Shelved,406402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_7B_ZI.Suppress,406402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_7B_ZI.Suppressed,406402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_7B_ZI.PCSuppress,406402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7B_ZI.PCUnSuppress,406402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7B_ZI.PCUnshelve,406402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8B_ZI.GlobalReset,406600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8B_ZI.HH_EN,406600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_8B_ZI.H_EN,406600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_8B_ZI.L_EN,406600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_8B_ZI.LL_EN,406600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_8B_ZI.BLEN,406600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_8B_ZI.OR_EN,406600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_8B_ZI.UREN,406600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_8B_ZI.RC_EN,406600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_8B_ZI.SuppressAA,406600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_8B_ZI.SuppressLA,406600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_8B_ZI.ConfigError,406600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_8B_ZI.HH_Alarm,406600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_8B_ZI.H_Alarm,406600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_8B_ZI.L_Alarm,406600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_8B_ZI.LL_Alarm,406600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_8B_ZI.BL_Alarm,406601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_8B_ZI.OR_Alarm,406601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_8B_ZI.UR_Alarm,406601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_8B_ZI.ROC_Alarm,406601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_8B_ZI.REST,406601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_8B_ZI.ALRM,406601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8B_ZI.ANUN,406601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8B_ZI.AKED,406601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8B_ZI.Resetable,406601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8B_ZI.HH_Fault,406601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_8B_ZI.H_Fault,406601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_8B_ZI.L_Fault,406601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_8B_ZI.LL_Fault,406601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_8B_ZI.BL_Fault,406601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_8B_ZI.OR_Fault,406601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_8B_ZI.UR_Fault,406601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_8B_ZI.ROC_Fault,406602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_8B_ZI.Tot_EN,406602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_8B_ZI.TAGR,406602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_8B_ZI.ACKN,406602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_8B_ZI.INTK,406602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_8B_ZI.PLCFault,406602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZI.PLCIOFault,406602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZI.INTK_EN,406602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_8B_ZI.Shelve,406602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_8B_ZI.Shelved,406602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_8B_ZI.Suppress,406602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_8B_ZI.Suppressed,406602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_8B_ZI.PCSuppress,406602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8B_ZI.PCUnSuppress,406602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8B_ZI.PCUnshelve,406602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9B_ZI.GlobalReset,406800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_9B_ZI.HH_EN,406800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_FV_0103_9B_ZI.H_EN,406800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_FV_0103_9B_ZI.L_EN,406800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_FV_0103_9B_ZI.LL_EN,406800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_FV_0103_9B_ZI.BLEN,406800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_FV_0103_9B_ZI.OR_EN,406800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_FV_0103_9B_ZI.UREN,406800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_FV_0103_9B_ZI.RC_EN,406800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_FV_0103_9B_ZI.SuppressAA,406800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_FV_0103_9B_ZI.SuppressLA,406800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_FV_0103_9B_ZI.ConfigError,406800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_FV_0103_9B_ZI.HH_Alarm,406800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_FV_0103_9B_ZI.H_Alarm,406800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_FV_0103_9B_ZI.L_Alarm,406800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_FV_0103_9B_ZI.LL_Alarm,406800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_FV_0103_9B_ZI.BL_Alarm,406801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_FV_0103_9B_ZI.OR_Alarm,406801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_FV_0103_9B_ZI.UR_Alarm,406801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_FV_0103_9B_ZI.ROC_Alarm,406801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_FV_0103_9B_ZI.REST,406801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_FV_0103_9B_ZI.ALRM,406801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_FV_0103_9B_ZI.ANUN,406801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_9B_ZI.AKED,406801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_9B_ZI.Resetable,406801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9B_ZI.HH_Fault,406801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_FV_0103_9B_ZI.H_Fault,406801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_FV_0103_9B_ZI.L_Fault,406801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_FV_0103_9B_ZI.LL_Fault,406801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_FV_0103_9B_ZI.BL_Fault,406801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_FV_0103_9B_ZI.OR_Fault,406801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_FV_0103_9B_ZI.UR_Fault,406801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_FV_0103_9B_ZI.ROC_Fault,406802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_FV_0103_9B_ZI.Tot_EN,406802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_FV_0103_9B_ZI.TAGR,406802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_FV_0103_9B_ZI.ACKN,406802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_FV_0103_9B_ZI.INTK,406802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_FV_0103_9B_ZI.PLCFault,406802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZI.PLCIOFault,406802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZI.INTK_EN,406802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_FV_0103_9B_ZI.Shelve,406802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_FV_0103_9B_ZI.Shelved,406802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_FV_0103_9B_ZI.Suppress,406802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_FV_0103_9B_ZI.Suppressed,406802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_FV_0103_9B_ZI.PCSuppress,406802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9B_ZI.PCUnSuppress,406802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9B_ZI.PCUnshelve,406802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_1_VI1.GlobalReset,407000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_1_VI1.HH_EN,407000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_1_VI1.H_EN,407000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_1_VI1.L_EN,407000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_1_VI1.LL_EN,407000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_1_VI1.BLEN,407000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_1_VI1.OR_EN,407000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_1_VI1.UREN,407000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_1_VI1.RC_EN,407000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_1_VI1.SuppressAA,407000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_1_VI1.SuppressLA,407000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_1_VI1.ConfigError,407000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_1_VI1.HH_Alarm,407000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_1_VI1.H_Alarm,407000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_1_VI1.L_Alarm,407000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_1_VI1.LL_Alarm,407000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_1_VI1.BL_Alarm,407001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_1_VI1.OR_Alarm,407001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_1_VI1.UR_Alarm,407001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_1_VI1.ROC_Alarm,407001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_1_VI1.REST,407001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_1_VI1.ALRM,407001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_1_VI1.ANUN,407001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_1_VI1.AKED,407001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_1_VI1.Resetable,407001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_1_VI1.HH_Fault,407001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_1_VI1.H_Fault,407001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_1_VI1.L_Fault,407001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_1_VI1.LL_Fault,407001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_1_VI1.BL_Fault,407001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_1_VI1.OR_Fault,407001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_1_VI1.UR_Fault,407001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_1_VI1.ROC_Fault,407002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_1_VI1.Tot_EN,407002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_1_VI1.TAGR,407002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_1_VI1.ACKN,407002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_1_VI1.INTK,407002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_1_VI1.PLCFault,407002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI1.PLCIOFault,407002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI1.INTK_EN,407002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_1_VI1.Shelve,407002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_1_VI1.Shelved,407002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_1_VI1.Suppress,407002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_1_VI1.Suppressed,407002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_1_VI1.PCSuppress,407002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_1_VI1.PCUnSuppress,407002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_1_VI1.PCUnshelve,407002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_1_VI2.GlobalReset,407200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_1_VI2.HH_EN,407200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_1_VI2.H_EN,407200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_1_VI2.L_EN,407200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_1_VI2.LL_EN,407200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_1_VI2.BLEN,407200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_1_VI2.OR_EN,407200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_1_VI2.UREN,407200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_1_VI2.RC_EN,407200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_1_VI2.SuppressAA,407200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_1_VI2.SuppressLA,407200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_1_VI2.ConfigError,407200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_1_VI2.HH_Alarm,407200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_1_VI2.H_Alarm,407200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_1_VI2.L_Alarm,407200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_1_VI2.LL_Alarm,407200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_1_VI2.BL_Alarm,407201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_1_VI2.OR_Alarm,407201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_1_VI2.UR_Alarm,407201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_1_VI2.ROC_Alarm,407201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_1_VI2.REST,407201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_1_VI2.ALRM,407201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_1_VI2.ANUN,407201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_1_VI2.AKED,407201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_1_VI2.Resetable,407201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_1_VI2.HH_Fault,407201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_1_VI2.H_Fault,407201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_1_VI2.L_Fault,407201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_1_VI2.LL_Fault,407201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_1_VI2.BL_Fault,407201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_1_VI2.OR_Fault,407201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_1_VI2.UR_Fault,407201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_1_VI2.ROC_Fault,407202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_1_VI2.Tot_EN,407202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_1_VI2.TAGR,407202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_1_VI2.ACKN,407202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_1_VI2.INTK,407202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_1_VI2.PLCFault,407202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI2.PLCIOFault,407202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI2.INTK_EN,407202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_1_VI2.Shelve,407202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_1_VI2.Shelved,407202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_1_VI2.Suppress,407202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_1_VI2.Suppressed,407202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_1_VI2.PCSuppress,407202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_1_VI2.PCUnSuppress,407202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_1_VI2.PCUnshelve,407202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_1_VI3.GlobalReset,407400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_1_VI3.HH_EN,407400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_1_VI3.H_EN,407400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_1_VI3.L_EN,407400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_1_VI3.LL_EN,407400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_1_VI3.BLEN,407400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_1_VI3.OR_EN,407400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_1_VI3.UREN,407400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_1_VI3.RC_EN,407400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_1_VI3.SuppressAA,407400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_1_VI3.SuppressLA,407400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_1_VI3.ConfigError,407400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_1_VI3.HH_Alarm,407400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_1_VI3.H_Alarm,407400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_1_VI3.L_Alarm,407400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_1_VI3.LL_Alarm,407400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_1_VI3.BL_Alarm,407401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_1_VI3.OR_Alarm,407401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_1_VI3.UR_Alarm,407401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_1_VI3.ROC_Alarm,407401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_1_VI3.REST,407401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_1_VI3.ALRM,407401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_1_VI3.ANUN,407401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_1_VI3.AKED,407401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_1_VI3.Resetable,407401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_1_VI3.HH_Fault,407401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_1_VI3.H_Fault,407401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_1_VI3.L_Fault,407401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_1_VI3.LL_Fault,407401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_1_VI3.BL_Fault,407401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_1_VI3.OR_Fault,407401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_1_VI3.UR_Fault,407401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_1_VI3.ROC_Fault,407402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_1_VI3.Tot_EN,407402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_1_VI3.TAGR,407402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_1_VI3.ACKN,407402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_1_VI3.INTK,407402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_1_VI3.PLCFault,407402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI3.PLCIOFault,407402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI3.INTK_EN,407402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_1_VI3.Shelve,407402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_1_VI3.Shelved,407402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_1_VI3.Suppress,407402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_1_VI3.Suppressed,407402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_1_VI3.PCSuppress,407402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_1_VI3.PCUnSuppress,407402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_1_VI3.PCUnshelve,407402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_1_VI4.GlobalReset,407600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_1_VI4.HH_EN,407600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_1_VI4.H_EN,407600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_1_VI4.L_EN,407600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_1_VI4.LL_EN,407600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_1_VI4.BLEN,407600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_1_VI4.OR_EN,407600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_1_VI4.UREN,407600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_1_VI4.RC_EN,407600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_1_VI4.SuppressAA,407600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_1_VI4.SuppressLA,407600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_1_VI4.ConfigError,407600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_1_VI4.HH_Alarm,407600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_1_VI4.H_Alarm,407600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_1_VI4.L_Alarm,407600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_1_VI4.LL_Alarm,407600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_1_VI4.BL_Alarm,407601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_1_VI4.OR_Alarm,407601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_1_VI4.UR_Alarm,407601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_1_VI4.ROC_Alarm,407601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_1_VI4.REST,407601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_1_VI4.ALRM,407601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_1_VI4.ANUN,407601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_1_VI4.AKED,407601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_1_VI4.Resetable,407601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_1_VI4.HH_Fault,407601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_1_VI4.H_Fault,407601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_1_VI4.L_Fault,407601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_1_VI4.LL_Fault,407601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_1_VI4.BL_Fault,407601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_1_VI4.OR_Fault,407601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_1_VI4.UR_Fault,407601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_1_VI4.ROC_Fault,407602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_1_VI4.Tot_EN,407602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_1_VI4.TAGR,407602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_1_VI4.ACKN,407602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_1_VI4.INTK,407602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_1_VI4.PLCFault,407602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI4.PLCIOFault,407602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_1_VI4.INTK_EN,407602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_1_VI4.Shelve,407602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_1_VI4.Shelved,407602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_1_VI4.Suppress,407602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_1_VI4.Suppressed,407602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_1_VI4.PCSuppress,407602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_1_VI4.PCUnSuppress,407602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_1_VI4.PCUnshelve,407602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_2_VI1.GlobalReset,407800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_2_VI1.HH_EN,407800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_2_VI1.H_EN,407800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_2_VI1.L_EN,407800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_2_VI1.LL_EN,407800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_2_VI1.BLEN,407800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_2_VI1.OR_EN,407800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_2_VI1.UREN,407800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_2_VI1.RC_EN,407800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_2_VI1.SuppressAA,407800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_2_VI1.SuppressLA,407800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_2_VI1.ConfigError,407800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_2_VI1.HH_Alarm,407800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_2_VI1.H_Alarm,407800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_2_VI1.L_Alarm,407800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_2_VI1.LL_Alarm,407800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_2_VI1.BL_Alarm,407801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_2_VI1.OR_Alarm,407801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_2_VI1.UR_Alarm,407801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_2_VI1.ROC_Alarm,407801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_2_VI1.REST,407801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_2_VI1.ALRM,407801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_2_VI1.ANUN,407801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_2_VI1.AKED,407801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_2_VI1.Resetable,407801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_2_VI1.HH_Fault,407801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_2_VI1.H_Fault,407801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_2_VI1.L_Fault,407801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_2_VI1.LL_Fault,407801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_2_VI1.BL_Fault,407801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_2_VI1.OR_Fault,407801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_2_VI1.UR_Fault,407801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_2_VI1.ROC_Fault,407802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_2_VI1.Tot_EN,407802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_2_VI1.TAGR,407802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_2_VI1.ACKN,407802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_2_VI1.INTK,407802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_2_VI1.PLCFault,407802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI1.PLCIOFault,407802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI1.INTK_EN,407802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_2_VI1.Shelve,407802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_2_VI1.Shelved,407802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_2_VI1.Suppress,407802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_2_VI1.Suppressed,407802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_2_VI1.PCSuppress,407802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_2_VI1.PCUnSuppress,407802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_2_VI1.PCUnshelve,407802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_2_VI2.GlobalReset,408000.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_2_VI2.HH_EN,408000.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_2_VI2.H_EN,408000.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_2_VI2.L_EN,408000.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_2_VI2.LL_EN,408000.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_2_VI2.BLEN,408000.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_2_VI2.OR_EN,408000.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_2_VI2.UREN,408000.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_2_VI2.RC_EN,408000.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_2_VI2.SuppressAA,408000.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_2_VI2.SuppressLA,408000.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_2_VI2.ConfigError,408000.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_2_VI2.HH_Alarm,408000.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_2_VI2.H_Alarm,408000.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_2_VI2.L_Alarm,408000.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_2_VI2.LL_Alarm,408000.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_2_VI2.BL_Alarm,408001.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_2_VI2.OR_Alarm,408001.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_2_VI2.UR_Alarm,408001.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_2_VI2.ROC_Alarm,408001.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_2_VI2.REST,408001.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_2_VI2.ALRM,408001.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_2_VI2.ANUN,408001.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_2_VI2.AKED,408001.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_2_VI2.Resetable,408001.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_2_VI2.HH_Fault,408001.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_2_VI2.H_Fault,408001.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_2_VI2.L_Fault,408001.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_2_VI2.LL_Fault,408001.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_2_VI2.BL_Fault,408001.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_2_VI2.OR_Fault,408001.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_2_VI2.UR_Fault,408001.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_2_VI2.ROC_Fault,408002.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_2_VI2.Tot_EN,408002.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_2_VI2.TAGR,408002.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_2_VI2.ACKN,408002.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_2_VI2.INTK,408002.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_2_VI2.PLCFault,408002.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI2.PLCIOFault,408002.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI2.INTK_EN,408002.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_2_VI2.Shelve,408002.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_2_VI2.Shelved,408002.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_2_VI2.Suppress,408002.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_2_VI2.Suppressed,408002.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_2_VI2.PCSuppress,408002.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_2_VI2.PCUnSuppress,408002.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_2_VI2.PCUnshelve,408002.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_2_VI3.GlobalReset,408200.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_2_VI3.HH_EN,408200.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_2_VI3.H_EN,408200.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_2_VI3.L_EN,408200.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_2_VI3.LL_EN,408200.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_2_VI3.BLEN,408200.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_2_VI3.OR_EN,408200.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_2_VI3.UREN,408200.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_2_VI3.RC_EN,408200.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_2_VI3.SuppressAA,408200.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_2_VI3.SuppressLA,408200.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_2_VI3.ConfigError,408200.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_2_VI3.HH_Alarm,408200.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_2_VI3.H_Alarm,408200.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_2_VI3.L_Alarm,408200.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_2_VI3.LL_Alarm,408200.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_2_VI3.BL_Alarm,408201.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_2_VI3.OR_Alarm,408201.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_2_VI3.UR_Alarm,408201.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_2_VI3.ROC_Alarm,408201.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_2_VI3.REST,408201.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_2_VI3.ALRM,408201.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_2_VI3.ANUN,408201.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_2_VI3.AKED,408201.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_2_VI3.Resetable,408201.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_2_VI3.HH_Fault,408201.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_2_VI3.H_Fault,408201.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_2_VI3.L_Fault,408201.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_2_VI3.LL_Fault,408201.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_2_VI3.BL_Fault,408201.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_2_VI3.OR_Fault,408201.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_2_VI3.UR_Fault,408201.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_2_VI3.ROC_Fault,408202.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_2_VI3.Tot_EN,408202.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_2_VI3.TAGR,408202.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_2_VI3.ACKN,408202.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_2_VI3.INTK,408202.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_2_VI3.PLCFault,408202.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI3.PLCIOFault,408202.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI3.INTK_EN,408202.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_2_VI3.Shelve,408202.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_2_VI3.Shelved,408202.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_2_VI3.Suppress,408202.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_2_VI3.Suppressed,408202.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_2_VI3.PCSuppress,408202.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_2_VI3.PCUnSuppress,408202.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_2_VI3.PCUnshelve,408202.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_2_VI4.GlobalReset,408400.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_2_VI4.HH_EN,408400.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_2_VI4.H_EN,408400.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_2_VI4.L_EN,408400.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_2_VI4.LL_EN,408400.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_2_VI4.BLEN,408400.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_2_VI4.OR_EN,408400.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_2_VI4.UREN,408400.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_2_VI4.RC_EN,408400.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_2_VI4.SuppressAA,408400.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_2_VI4.SuppressLA,408400.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_2_VI4.ConfigError,408400.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_2_VI4.HH_Alarm,408400.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_2_VI4.H_Alarm,408400.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_2_VI4.L_Alarm,408400.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_2_VI4.LL_Alarm,408400.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_2_VI4.BL_Alarm,408401.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_2_VI4.OR_Alarm,408401.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_2_VI4.UR_Alarm,408401.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_2_VI4.ROC_Alarm,408401.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_2_VI4.REST,408401.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_2_VI4.ALRM,408401.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_2_VI4.ANUN,408401.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_2_VI4.AKED,408401.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_2_VI4.Resetable,408401.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_2_VI4.HH_Fault,408401.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_2_VI4.H_Fault,408401.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_2_VI4.L_Fault,408401.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_2_VI4.LL_Fault,408401.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_2_VI4.BL_Fault,408401.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_2_VI4.OR_Fault,408401.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_2_VI4.UR_Fault,408401.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_2_VI4.ROC_Fault,408402.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_2_VI4.Tot_EN,408402.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_2_VI4.TAGR,408402.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_2_VI4.ACKN,408402.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_2_VI4.INTK,408402.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_2_VI4.PLCFault,408402.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI4.PLCIOFault,408402.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_2_VI4.INTK_EN,408402.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_2_VI4.Shelve,408402.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_2_VI4.Shelved,408402.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_2_VI4.Suppress,408402.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_2_VI4.Suppressed,408402.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_2_VI4.PCSuppress,408402.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_2_VI4.PCUnSuppress,408402.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_2_VI4.PCUnshelve,408402.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_3_VI1.GlobalReset,408600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_3_VI1.HH_EN,408600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_3_VI1.H_EN,408600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_3_VI1.L_EN,408600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_3_VI1.LL_EN,408600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_3_VI1.BLEN,408600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_3_VI1.OR_EN,408600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_3_VI1.UREN,408600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_3_VI1.RC_EN,408600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_3_VI1.SuppressAA,408600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_3_VI1.SuppressLA,408600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_3_VI1.ConfigError,408600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_3_VI1.HH_Alarm,408600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_3_VI1.H_Alarm,408600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_3_VI1.L_Alarm,408600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_3_VI1.LL_Alarm,408600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_3_VI1.BL_Alarm,408601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_3_VI1.OR_Alarm,408601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_3_VI1.UR_Alarm,408601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_3_VI1.ROC_Alarm,408601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_3_VI1.REST,408601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_3_VI1.ALRM,408601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_3_VI1.ANUN,408601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_3_VI1.AKED,408601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_3_VI1.Resetable,408601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_3_VI1.HH_Fault,408601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_3_VI1.H_Fault,408601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_3_VI1.L_Fault,408601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_3_VI1.LL_Fault,408601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_3_VI1.BL_Fault,408601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_3_VI1.OR_Fault,408601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_3_VI1.UR_Fault,408601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_3_VI1.ROC_Fault,408602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_3_VI1.Tot_EN,408602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_3_VI1.TAGR,408602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_3_VI1.ACKN,408602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_3_VI1.INTK,408602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_3_VI1.PLCFault,408602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI1.PLCIOFault,408602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI1.INTK_EN,408602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_3_VI1.Shelve,408602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_3_VI1.Shelved,408602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_3_VI1.Suppress,408602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_3_VI1.Suppressed,408602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_3_VI1.PCSuppress,408602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_3_VI1.PCUnSuppress,408602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_3_VI1.PCUnshelve,408602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_3_VI2.GlobalReset,408800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_3_VI2.HH_EN,408800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_3_VI2.H_EN,408800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_3_VI2.L_EN,408800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_3_VI2.LL_EN,408800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_3_VI2.BLEN,408800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_3_VI2.OR_EN,408800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_3_VI2.UREN,408800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_3_VI2.RC_EN,408800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_3_VI2.SuppressAA,408800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_3_VI2.SuppressLA,408800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_3_VI2.ConfigError,408800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_3_VI2.HH_Alarm,408800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_3_VI2.H_Alarm,408800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_3_VI2.L_Alarm,408800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_3_VI2.LL_Alarm,408800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_3_VI2.BL_Alarm,408801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_3_VI2.OR_Alarm,408801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_3_VI2.UR_Alarm,408801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_3_VI2.ROC_Alarm,408801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_3_VI2.REST,408801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_3_VI2.ALRM,408801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_3_VI2.ANUN,408801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_3_VI2.AKED,408801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_3_VI2.Resetable,408801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_3_VI2.HH_Fault,408801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_3_VI2.H_Fault,408801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_3_VI2.L_Fault,408801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_3_VI2.LL_Fault,408801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_3_VI2.BL_Fault,408801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_3_VI2.OR_Fault,408801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_3_VI2.UR_Fault,408801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_3_VI2.ROC_Fault,408802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_3_VI2.Tot_EN,408802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_3_VI2.TAGR,408802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_3_VI2.ACKN,408802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_3_VI2.INTK,408802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_3_VI2.PLCFault,408802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI2.PLCIOFault,408802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI2.INTK_EN,408802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_3_VI2.Shelve,408802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_3_VI2.Shelved,408802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_3_VI2.Suppress,408802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_3_VI2.Suppressed,408802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_3_VI2.PCSuppress,408802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_3_VI2.PCUnSuppress,408802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_3_VI2.PCUnshelve,408802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_3_VI3.GlobalReset,409000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_3_VI3.HH_EN,409000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_3_VI3.H_EN,409000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_3_VI3.L_EN,409000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_3_VI3.LL_EN,409000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_3_VI3.BLEN,409000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_3_VI3.OR_EN,409000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_3_VI3.UREN,409000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_3_VI3.RC_EN,409000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_3_VI3.SuppressAA,409000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_3_VI3.SuppressLA,409000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_3_VI3.ConfigError,409000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_3_VI3.HH_Alarm,409000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_3_VI3.H_Alarm,409000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_3_VI3.L_Alarm,409000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_3_VI3.LL_Alarm,409000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_3_VI3.BL_Alarm,409001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_3_VI3.OR_Alarm,409001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_3_VI3.UR_Alarm,409001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_3_VI3.ROC_Alarm,409001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_3_VI3.REST,409001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_3_VI3.ALRM,409001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_3_VI3.ANUN,409001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_3_VI3.AKED,409001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_3_VI3.Resetable,409001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_3_VI3.HH_Fault,409001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_3_VI3.H_Fault,409001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_3_VI3.L_Fault,409001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_3_VI3.LL_Fault,409001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_3_VI3.BL_Fault,409001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_3_VI3.OR_Fault,409001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_3_VI3.UR_Fault,409001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_3_VI3.ROC_Fault,409002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_3_VI3.Tot_EN,409002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_3_VI3.TAGR,409002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_3_VI3.ACKN,409002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_3_VI3.INTK,409002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_3_VI3.PLCFault,409002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI3.PLCIOFault,409002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI3.INTK_EN,409002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_3_VI3.Shelve,409002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_3_VI3.Shelved,409002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_3_VI3.Suppress,409002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_3_VI3.Suppressed,409002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_3_VI3.PCSuppress,409002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_3_VI3.PCUnSuppress,409002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_3_VI3.PCUnshelve,409002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_3_VI4.GlobalReset,409200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_3_VI4.HH_EN,409200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_3_VI4.H_EN,409200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_3_VI4.L_EN,409200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_3_VI4.LL_EN,409200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_3_VI4.BLEN,409200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_3_VI4.OR_EN,409200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_3_VI4.UREN,409200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_3_VI4.RC_EN,409200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_3_VI4.SuppressAA,409200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_3_VI4.SuppressLA,409200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_3_VI4.ConfigError,409200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_3_VI4.HH_Alarm,409200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_3_VI4.H_Alarm,409200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_3_VI4.L_Alarm,409200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_3_VI4.LL_Alarm,409200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_3_VI4.BL_Alarm,409201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_3_VI4.OR_Alarm,409201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_3_VI4.UR_Alarm,409201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_3_VI4.ROC_Alarm,409201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_3_VI4.REST,409201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_3_VI4.ALRM,409201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_3_VI4.ANUN,409201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_3_VI4.AKED,409201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_3_VI4.Resetable,409201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_3_VI4.HH_Fault,409201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_3_VI4.H_Fault,409201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_3_VI4.L_Fault,409201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_3_VI4.LL_Fault,409201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_3_VI4.BL_Fault,409201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_3_VI4.OR_Fault,409201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_3_VI4.UR_Fault,409201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_3_VI4.ROC_Fault,409202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_3_VI4.Tot_EN,409202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_3_VI4.TAGR,409202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_3_VI4.ACKN,409202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_3_VI4.INTK,409202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_3_VI4.PLCFault,409202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI4.PLCIOFault,409202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_3_VI4.INTK_EN,409202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_3_VI4.Shelve,409202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_3_VI4.Shelved,409202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_3_VI4.Suppress,409202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_3_VI4.Suppressed,409202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_3_VI4.PCSuppress,409202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_3_VI4.PCUnSuppress,409202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_3_VI4.PCUnshelve,409202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_4_VI1.GlobalReset,409400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_4_VI1.HH_EN,409400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_4_VI1.H_EN,409400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_4_VI1.L_EN,409400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_4_VI1.LL_EN,409400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_4_VI1.BLEN,409400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_4_VI1.OR_EN,409400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_4_VI1.UREN,409400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_4_VI1.RC_EN,409400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_4_VI1.SuppressAA,409400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_4_VI1.SuppressLA,409400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_4_VI1.ConfigError,409400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_4_VI1.HH_Alarm,409400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_4_VI1.H_Alarm,409400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_4_VI1.L_Alarm,409400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_4_VI1.LL_Alarm,409400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_4_VI1.BL_Alarm,409401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_4_VI1.OR_Alarm,409401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_4_VI1.UR_Alarm,409401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_4_VI1.ROC_Alarm,409401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_4_VI1.REST,409401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_4_VI1.ALRM,409401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_4_VI1.ANUN,409401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_4_VI1.AKED,409401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_4_VI1.Resetable,409401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_4_VI1.HH_Fault,409401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_4_VI1.H_Fault,409401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_4_VI1.L_Fault,409401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_4_VI1.LL_Fault,409401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_4_VI1.BL_Fault,409401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_4_VI1.OR_Fault,409401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_4_VI1.UR_Fault,409401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_4_VI1.ROC_Fault,409402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_4_VI1.Tot_EN,409402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_4_VI1.TAGR,409402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_4_VI1.ACKN,409402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_4_VI1.INTK,409402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_4_VI1.PLCFault,409402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI1.PLCIOFault,409402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI1.INTK_EN,409402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_4_VI1.Shelve,409402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_4_VI1.Shelved,409402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_4_VI1.Suppress,409402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_4_VI1.Suppressed,409402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_4_VI1.PCSuppress,409402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_4_VI1.PCUnSuppress,409402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_4_VI1.PCUnshelve,409402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_4_VI2.GlobalReset,409600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_4_VI2.HH_EN,409600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_4_VI2.H_EN,409600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_4_VI2.L_EN,409600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_4_VI2.LL_EN,409600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_4_VI2.BLEN,409600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_4_VI2.OR_EN,409600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_4_VI2.UREN,409600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_4_VI2.RC_EN,409600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_4_VI2.SuppressAA,409600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_4_VI2.SuppressLA,409600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_4_VI2.ConfigError,409600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_4_VI2.HH_Alarm,409600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_4_VI2.H_Alarm,409600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_4_VI2.L_Alarm,409600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_4_VI2.LL_Alarm,409600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_4_VI2.BL_Alarm,409601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_4_VI2.OR_Alarm,409601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_4_VI2.UR_Alarm,409601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_4_VI2.ROC_Alarm,409601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_4_VI2.REST,409601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_4_VI2.ALRM,409601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_4_VI2.ANUN,409601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_4_VI2.AKED,409601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_4_VI2.Resetable,409601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_4_VI2.HH_Fault,409601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_4_VI2.H_Fault,409601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_4_VI2.L_Fault,409601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_4_VI2.LL_Fault,409601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_4_VI2.BL_Fault,409601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_4_VI2.OR_Fault,409601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_4_VI2.UR_Fault,409601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_4_VI2.ROC_Fault,409602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_4_VI2.Tot_EN,409602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_4_VI2.TAGR,409602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_4_VI2.ACKN,409602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_4_VI2.INTK,409602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_4_VI2.PLCFault,409602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI2.PLCIOFault,409602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI2.INTK_EN,409602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_4_VI2.Shelve,409602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_4_VI2.Shelved,409602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_4_VI2.Suppress,409602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_4_VI2.Suppressed,409602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_4_VI2.PCSuppress,409602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_4_VI2.PCUnSuppress,409602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_4_VI2.PCUnshelve,409602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_4_VI3.GlobalReset,409800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_4_VI3.HH_EN,409800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_4_VI3.H_EN,409800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_4_VI3.L_EN,409800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_4_VI3.LL_EN,409800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_4_VI3.BLEN,409800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_4_VI3.OR_EN,409800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_4_VI3.UREN,409800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_4_VI3.RC_EN,409800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_4_VI3.SuppressAA,409800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_4_VI3.SuppressLA,409800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_4_VI3.ConfigError,409800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_4_VI3.HH_Alarm,409800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_4_VI3.H_Alarm,409800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_4_VI3.L_Alarm,409800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_4_VI3.LL_Alarm,409800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_4_VI3.BL_Alarm,409801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_4_VI3.OR_Alarm,409801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_4_VI3.UR_Alarm,409801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_4_VI3.ROC_Alarm,409801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_4_VI3.REST,409801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_4_VI3.ALRM,409801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_4_VI3.ANUN,409801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_4_VI3.AKED,409801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_4_VI3.Resetable,409801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_4_VI3.HH_Fault,409801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_4_VI3.H_Fault,409801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_4_VI3.L_Fault,409801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_4_VI3.LL_Fault,409801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_4_VI3.BL_Fault,409801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_4_VI3.OR_Fault,409801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_4_VI3.UR_Fault,409801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_4_VI3.ROC_Fault,409802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_4_VI3.Tot_EN,409802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_4_VI3.TAGR,409802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_4_VI3.ACKN,409802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_4_VI3.INTK,409802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_4_VI3.PLCFault,409802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI3.PLCIOFault,409802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI3.INTK_EN,409802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_4_VI3.Shelve,409802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_4_VI3.Shelved,409802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_4_VI3.Suppress,409802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_4_VI3.Suppressed,409802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_4_VI3.PCSuppress,409802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_4_VI3.PCUnSuppress,409802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_4_VI3.PCUnshelve,409802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_4_VI4.GlobalReset,410000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_4_VI4.HH_EN,410000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_4_VI4.H_EN,410000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_4_VI4.L_EN,410000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_4_VI4.LL_EN,410000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_4_VI4.BLEN,410000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_4_VI4.OR_EN,410000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_4_VI4.UREN,410000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_4_VI4.RC_EN,410000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_4_VI4.SuppressAA,410000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_4_VI4.SuppressLA,410000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_4_VI4.ConfigError,410000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_4_VI4.HH_Alarm,410000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_4_VI4.H_Alarm,410000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_4_VI4.L_Alarm,410000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_4_VI4.LL_Alarm,410000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_4_VI4.BL_Alarm,410001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_4_VI4.OR_Alarm,410001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_4_VI4.UR_Alarm,410001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_4_VI4.ROC_Alarm,410001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_4_VI4.REST,410001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_4_VI4.ALRM,410001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_4_VI4.ANUN,410001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_4_VI4.AKED,410001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_4_VI4.Resetable,410001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_4_VI4.HH_Fault,410001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_4_VI4.H_Fault,410001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_4_VI4.L_Fault,410001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_4_VI4.LL_Fault,410001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_4_VI4.BL_Fault,410001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_4_VI4.OR_Fault,410001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_4_VI4.UR_Fault,410001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_4_VI4.ROC_Fault,410002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_4_VI4.Tot_EN,410002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_4_VI4.TAGR,410002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_4_VI4.ACKN,410002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_4_VI4.INTK,410002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_4_VI4.PLCFault,410002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI4.PLCIOFault,410002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_4_VI4.INTK_EN,410002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_4_VI4.Shelve,410002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_4_VI4.Shelved,410002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_4_VI4.Suppress,410002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_4_VI4.Suppressed,410002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_4_VI4.PCSuppress,410002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_4_VI4.PCUnSuppress,410002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_4_VI4.PCUnshelve,410002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_5_VI1.GlobalReset,410200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_5_VI1.HH_EN,410200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_5_VI1.H_EN,410200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_5_VI1.L_EN,410200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_5_VI1.LL_EN,410200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_5_VI1.BLEN,410200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_5_VI1.OR_EN,410200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_5_VI1.UREN,410200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_5_VI1.RC_EN,410200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_5_VI1.SuppressAA,410200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_5_VI1.SuppressLA,410200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_5_VI1.ConfigError,410200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_5_VI1.HH_Alarm,410200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_5_VI1.H_Alarm,410200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_5_VI1.L_Alarm,410200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_5_VI1.LL_Alarm,410200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_5_VI1.BL_Alarm,410201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_5_VI1.OR_Alarm,410201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_5_VI1.UR_Alarm,410201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_5_VI1.ROC_Alarm,410201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_5_VI1.REST,410201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_5_VI1.ALRM,410201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_5_VI1.ANUN,410201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_5_VI1.AKED,410201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_5_VI1.Resetable,410201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_5_VI1.HH_Fault,410201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_5_VI1.H_Fault,410201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_5_VI1.L_Fault,410201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_5_VI1.LL_Fault,410201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_5_VI1.BL_Fault,410201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_5_VI1.OR_Fault,410201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_5_VI1.UR_Fault,410201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_5_VI1.ROC_Fault,410202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_5_VI1.Tot_EN,410202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_5_VI1.TAGR,410202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_5_VI1.ACKN,410202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_5_VI1.INTK,410202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_5_VI1.PLCFault,410202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI1.PLCIOFault,410202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI1.INTK_EN,410202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_5_VI1.Shelve,410202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_5_VI1.Shelved,410202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_5_VI1.Suppress,410202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_5_VI1.Suppressed,410202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_5_VI1.PCSuppress,410202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_5_VI1.PCUnSuppress,410202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_5_VI1.PCUnshelve,410202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_5_VI2.GlobalReset,410400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_5_VI2.HH_EN,410400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_5_VI2.H_EN,410400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_5_VI2.L_EN,410400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_5_VI2.LL_EN,410400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_5_VI2.BLEN,410400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_5_VI2.OR_EN,410400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_5_VI2.UREN,410400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_5_VI2.RC_EN,410400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_5_VI2.SuppressAA,410400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_5_VI2.SuppressLA,410400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_5_VI2.ConfigError,410400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_5_VI2.HH_Alarm,410400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_5_VI2.H_Alarm,410400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_5_VI2.L_Alarm,410400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_5_VI2.LL_Alarm,410400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_5_VI2.BL_Alarm,410401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_5_VI2.OR_Alarm,410401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_5_VI2.UR_Alarm,410401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_5_VI2.ROC_Alarm,410401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_5_VI2.REST,410401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_5_VI2.ALRM,410401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_5_VI2.ANUN,410401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_5_VI2.AKED,410401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_5_VI2.Resetable,410401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_5_VI2.HH_Fault,410401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_5_VI2.H_Fault,410401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_5_VI2.L_Fault,410401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_5_VI2.LL_Fault,410401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_5_VI2.BL_Fault,410401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_5_VI2.OR_Fault,410401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_5_VI2.UR_Fault,410401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_5_VI2.ROC_Fault,410402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_5_VI2.Tot_EN,410402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_5_VI2.TAGR,410402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_5_VI2.ACKN,410402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_5_VI2.INTK,410402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_5_VI2.PLCFault,410402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI2.PLCIOFault,410402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI2.INTK_EN,410402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_5_VI2.Shelve,410402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_5_VI2.Shelved,410402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_5_VI2.Suppress,410402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_5_VI2.Suppressed,410402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_5_VI2.PCSuppress,410402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_5_VI2.PCUnSuppress,410402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_5_VI2.PCUnshelve,410402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_5_VI3.GlobalReset,410600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_5_VI3.HH_EN,410600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_5_VI3.H_EN,410600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_5_VI3.L_EN,410600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_5_VI3.LL_EN,410600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_5_VI3.BLEN,410600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_5_VI3.OR_EN,410600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_5_VI3.UREN,410600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_5_VI3.RC_EN,410600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_5_VI3.SuppressAA,410600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_5_VI3.SuppressLA,410600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_5_VI3.ConfigError,410600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_5_VI3.HH_Alarm,410600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_5_VI3.H_Alarm,410600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_5_VI3.L_Alarm,410600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_5_VI3.LL_Alarm,410600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_5_VI3.BL_Alarm,410601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_5_VI3.OR_Alarm,410601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_5_VI3.UR_Alarm,410601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_5_VI3.ROC_Alarm,410601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_5_VI3.REST,410601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_5_VI3.ALRM,410601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_5_VI3.ANUN,410601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_5_VI3.AKED,410601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_5_VI3.Resetable,410601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_5_VI3.HH_Fault,410601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_5_VI3.H_Fault,410601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_5_VI3.L_Fault,410601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_5_VI3.LL_Fault,410601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_5_VI3.BL_Fault,410601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_5_VI3.OR_Fault,410601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_5_VI3.UR_Fault,410601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_5_VI3.ROC_Fault,410602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_5_VI3.Tot_EN,410602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_5_VI3.TAGR,410602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_5_VI3.ACKN,410602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_5_VI3.INTK,410602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_5_VI3.PLCFault,410602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI3.PLCIOFault,410602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI3.INTK_EN,410602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_5_VI3.Shelve,410602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_5_VI3.Shelved,410602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_5_VI3.Suppress,410602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_5_VI3.Suppressed,410602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_5_VI3.PCSuppress,410602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_5_VI3.PCUnSuppress,410602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_5_VI3.PCUnshelve,410602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_5_VI4.GlobalReset,410800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_5_VI4.HH_EN,410800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_5_VI4.H_EN,410800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_5_VI4.L_EN,410800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_5_VI4.LL_EN,410800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_5_VI4.BLEN,410800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_5_VI4.OR_EN,410800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_5_VI4.UREN,410800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_5_VI4.RC_EN,410800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_5_VI4.SuppressAA,410800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_5_VI4.SuppressLA,410800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_5_VI4.ConfigError,410800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_5_VI4.HH_Alarm,410800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_5_VI4.H_Alarm,410800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_5_VI4.L_Alarm,410800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_5_VI4.LL_Alarm,410800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_5_VI4.BL_Alarm,410801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_5_VI4.OR_Alarm,410801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_5_VI4.UR_Alarm,410801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_5_VI4.ROC_Alarm,410801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_5_VI4.REST,410801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_5_VI4.ALRM,410801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_5_VI4.ANUN,410801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_5_VI4.AKED,410801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_5_VI4.Resetable,410801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_5_VI4.HH_Fault,410801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_5_VI4.H_Fault,410801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_5_VI4.L_Fault,410801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_5_VI4.LL_Fault,410801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_5_VI4.BL_Fault,410801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_5_VI4.OR_Fault,410801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_5_VI4.UR_Fault,410801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_5_VI4.ROC_Fault,410802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_5_VI4.Tot_EN,410802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_5_VI4.TAGR,410802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_5_VI4.ACKN,410802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_5_VI4.INTK,410802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_5_VI4.PLCFault,410802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI4.PLCIOFault,410802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_5_VI4.INTK_EN,410802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_5_VI4.Shelve,410802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_5_VI4.Shelved,410802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_5_VI4.Suppress,410802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_5_VI4.Suppressed,410802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_5_VI4.PCSuppress,410802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_5_VI4.PCUnSuppress,410802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_5_VI4.PCUnshelve,410802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_6_VI1.GlobalReset,411000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_6_VI1.HH_EN,411000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_6_VI1.H_EN,411000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_6_VI1.L_EN,411000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_6_VI1.LL_EN,411000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_6_VI1.BLEN,411000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_6_VI1.OR_EN,411000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_6_VI1.UREN,411000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_6_VI1.RC_EN,411000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_6_VI1.SuppressAA,411000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_6_VI1.SuppressLA,411000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_6_VI1.ConfigError,411000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_6_VI1.HH_Alarm,411000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_6_VI1.H_Alarm,411000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_6_VI1.L_Alarm,411000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_6_VI1.LL_Alarm,411000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_6_VI1.BL_Alarm,411001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_6_VI1.OR_Alarm,411001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_6_VI1.UR_Alarm,411001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_6_VI1.ROC_Alarm,411001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_6_VI1.REST,411001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_6_VI1.ALRM,411001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_6_VI1.ANUN,411001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_6_VI1.AKED,411001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_6_VI1.Resetable,411001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_6_VI1.HH_Fault,411001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_6_VI1.H_Fault,411001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_6_VI1.L_Fault,411001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_6_VI1.LL_Fault,411001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_6_VI1.BL_Fault,411001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_6_VI1.OR_Fault,411001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_6_VI1.UR_Fault,411001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_6_VI1.ROC_Fault,411002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_6_VI1.Tot_EN,411002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_6_VI1.TAGR,411002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_6_VI1.ACKN,411002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_6_VI1.INTK,411002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_6_VI1.PLCFault,411002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI1.PLCIOFault,411002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI1.INTK_EN,411002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_6_VI1.Shelve,411002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_6_VI1.Shelved,411002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_6_VI1.Suppress,411002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_6_VI1.Suppressed,411002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_6_VI1.PCSuppress,411002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_6_VI1.PCUnSuppress,411002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_6_VI1.PCUnshelve,411002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_6_VI2.GlobalReset,411200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_6_VI2.HH_EN,411200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_6_VI2.H_EN,411200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_6_VI2.L_EN,411200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_6_VI2.LL_EN,411200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_6_VI2.BLEN,411200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_6_VI2.OR_EN,411200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_6_VI2.UREN,411200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_6_VI2.RC_EN,411200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_6_VI2.SuppressAA,411200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_6_VI2.SuppressLA,411200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_6_VI2.ConfigError,411200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_6_VI2.HH_Alarm,411200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_6_VI2.H_Alarm,411200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_6_VI2.L_Alarm,411200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_6_VI2.LL_Alarm,411200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_6_VI2.BL_Alarm,411201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_6_VI2.OR_Alarm,411201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_6_VI2.UR_Alarm,411201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_6_VI2.ROC_Alarm,411201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_6_VI2.REST,411201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_6_VI2.ALRM,411201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_6_VI2.ANUN,411201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_6_VI2.AKED,411201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_6_VI2.Resetable,411201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_6_VI2.HH_Fault,411201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_6_VI2.H_Fault,411201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_6_VI2.L_Fault,411201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_6_VI2.LL_Fault,411201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_6_VI2.BL_Fault,411201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_6_VI2.OR_Fault,411201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_6_VI2.UR_Fault,411201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_6_VI2.ROC_Fault,411202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_6_VI2.Tot_EN,411202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_6_VI2.TAGR,411202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_6_VI2.ACKN,411202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_6_VI2.INTK,411202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_6_VI2.PLCFault,411202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI2.PLCIOFault,411202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI2.INTK_EN,411202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_6_VI2.Shelve,411202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_6_VI2.Shelved,411202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_6_VI2.Suppress,411202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_6_VI2.Suppressed,411202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_6_VI2.PCSuppress,411202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_6_VI2.PCUnSuppress,411202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_6_VI2.PCUnshelve,411202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_6_VI3.GlobalReset,411400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_6_VI3.HH_EN,411400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_6_VI3.H_EN,411400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_6_VI3.L_EN,411400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_6_VI3.LL_EN,411400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_6_VI3.BLEN,411400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_6_VI3.OR_EN,411400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_6_VI3.UREN,411400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_6_VI3.RC_EN,411400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_6_VI3.SuppressAA,411400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_6_VI3.SuppressLA,411400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_6_VI3.ConfigError,411400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_6_VI3.HH_Alarm,411400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_6_VI3.H_Alarm,411400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_6_VI3.L_Alarm,411400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_6_VI3.LL_Alarm,411400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_6_VI3.BL_Alarm,411401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_6_VI3.OR_Alarm,411401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_6_VI3.UR_Alarm,411401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_6_VI3.ROC_Alarm,411401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_6_VI3.REST,411401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_6_VI3.ALRM,411401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_6_VI3.ANUN,411401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_6_VI3.AKED,411401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_6_VI3.Resetable,411401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_6_VI3.HH_Fault,411401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_6_VI3.H_Fault,411401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_6_VI3.L_Fault,411401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_6_VI3.LL_Fault,411401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_6_VI3.BL_Fault,411401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_6_VI3.OR_Fault,411401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_6_VI3.UR_Fault,411401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_6_VI3.ROC_Fault,411402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_6_VI3.Tot_EN,411402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_6_VI3.TAGR,411402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_6_VI3.ACKN,411402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_6_VI3.INTK,411402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_6_VI3.PLCFault,411402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI3.PLCIOFault,411402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI3.INTK_EN,411402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_6_VI3.Shelve,411402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_6_VI3.Shelved,411402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_6_VI3.Suppress,411402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_6_VI3.Suppressed,411402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_6_VI3.PCSuppress,411402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_6_VI3.PCUnSuppress,411402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_6_VI3.PCUnshelve,411402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_6_VI4.GlobalReset,411600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_6_VI4.HH_EN,411600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_6_VI4.H_EN,411600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_6_VI4.L_EN,411600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_6_VI4.LL_EN,411600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_6_VI4.BLEN,411600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_6_VI4.OR_EN,411600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_6_VI4.UREN,411600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_6_VI4.RC_EN,411600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_6_VI4.SuppressAA,411600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_6_VI4.SuppressLA,411600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_6_VI4.ConfigError,411600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_6_VI4.HH_Alarm,411600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_6_VI4.H_Alarm,411600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_6_VI4.L_Alarm,411600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_6_VI4.LL_Alarm,411600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_6_VI4.BL_Alarm,411601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_6_VI4.OR_Alarm,411601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_6_VI4.UR_Alarm,411601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_6_VI4.ROC_Alarm,411601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_6_VI4.REST,411601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_6_VI4.ALRM,411601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_6_VI4.ANUN,411601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_6_VI4.AKED,411601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_6_VI4.Resetable,411601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_6_VI4.HH_Fault,411601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_6_VI4.H_Fault,411601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_6_VI4.L_Fault,411601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_6_VI4.LL_Fault,411601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_6_VI4.BL_Fault,411601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_6_VI4.OR_Fault,411601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_6_VI4.UR_Fault,411601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_6_VI4.ROC_Fault,411602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_6_VI4.Tot_EN,411602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_6_VI4.TAGR,411602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_6_VI4.ACKN,411602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_6_VI4.INTK,411602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_6_VI4.PLCFault,411602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI4.PLCIOFault,411602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_6_VI4.INTK_EN,411602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_6_VI4.Shelve,411602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_6_VI4.Shelved,411602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_6_VI4.Suppress,411602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_6_VI4.Suppressed,411602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_6_VI4.PCSuppress,411602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_6_VI4.PCUnSuppress,411602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_6_VI4.PCUnshelve,411602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_7_VI1.GlobalReset,411800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_7_VI1.HH_EN,411800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_7_VI1.H_EN,411800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_7_VI1.L_EN,411800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_7_VI1.LL_EN,411800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_7_VI1.BLEN,411800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_7_VI1.OR_EN,411800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_7_VI1.UREN,411800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_7_VI1.RC_EN,411800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_7_VI1.SuppressAA,411800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_7_VI1.SuppressLA,411800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_7_VI1.ConfigError,411800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_7_VI1.HH_Alarm,411800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_7_VI1.H_Alarm,411800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_7_VI1.L_Alarm,411800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_7_VI1.LL_Alarm,411800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_7_VI1.BL_Alarm,411801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_7_VI1.OR_Alarm,411801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_7_VI1.UR_Alarm,411801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_7_VI1.ROC_Alarm,411801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_7_VI1.REST,411801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_7_VI1.ALRM,411801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_7_VI1.ANUN,411801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_7_VI1.AKED,411801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_7_VI1.Resetable,411801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_7_VI1.HH_Fault,411801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_7_VI1.H_Fault,411801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_7_VI1.L_Fault,411801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_7_VI1.LL_Fault,411801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_7_VI1.BL_Fault,411801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_7_VI1.OR_Fault,411801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_7_VI1.UR_Fault,411801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_7_VI1.ROC_Fault,411802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_7_VI1.Tot_EN,411802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_7_VI1.TAGR,411802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_7_VI1.ACKN,411802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_7_VI1.INTK,411802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_7_VI1.PLCFault,411802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI1.PLCIOFault,411802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI1.INTK_EN,411802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_7_VI1.Shelve,411802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_7_VI1.Shelved,411802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_7_VI1.Suppress,411802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_7_VI1.Suppressed,411802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_7_VI1.PCSuppress,411802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_7_VI1.PCUnSuppress,411802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_7_VI1.PCUnshelve,411802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_7_VI2.GlobalReset,412000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_7_VI2.HH_EN,412000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_7_VI2.H_EN,412000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_7_VI2.L_EN,412000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_7_VI2.LL_EN,412000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_7_VI2.BLEN,412000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_7_VI2.OR_EN,412000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_7_VI2.UREN,412000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_7_VI2.RC_EN,412000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_7_VI2.SuppressAA,412000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_7_VI2.SuppressLA,412000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_7_VI2.ConfigError,412000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_7_VI2.HH_Alarm,412000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_7_VI2.H_Alarm,412000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_7_VI2.L_Alarm,412000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_7_VI2.LL_Alarm,412000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_7_VI2.BL_Alarm,412001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_7_VI2.OR_Alarm,412001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_7_VI2.UR_Alarm,412001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_7_VI2.ROC_Alarm,412001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_7_VI2.REST,412001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_7_VI2.ALRM,412001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_7_VI2.ANUN,412001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_7_VI2.AKED,412001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_7_VI2.Resetable,412001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_7_VI2.HH_Fault,412001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_7_VI2.H_Fault,412001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_7_VI2.L_Fault,412001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_7_VI2.LL_Fault,412001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_7_VI2.BL_Fault,412001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_7_VI2.OR_Fault,412001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_7_VI2.UR_Fault,412001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_7_VI2.ROC_Fault,412002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_7_VI2.Tot_EN,412002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_7_VI2.TAGR,412002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_7_VI2.ACKN,412002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_7_VI2.INTK,412002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_7_VI2.PLCFault,412002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI2.PLCIOFault,412002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI2.INTK_EN,412002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_7_VI2.Shelve,412002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_7_VI2.Shelved,412002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_7_VI2.Suppress,412002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_7_VI2.Suppressed,412002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_7_VI2.PCSuppress,412002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_7_VI2.PCUnSuppress,412002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_7_VI2.PCUnshelve,412002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_7_VI3.GlobalReset,412200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_7_VI3.HH_EN,412200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_7_VI3.H_EN,412200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_7_VI3.L_EN,412200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_7_VI3.LL_EN,412200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_7_VI3.BLEN,412200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_7_VI3.OR_EN,412200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_7_VI3.UREN,412200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_7_VI3.RC_EN,412200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_7_VI3.SuppressAA,412200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_7_VI3.SuppressLA,412200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_7_VI3.ConfigError,412200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_7_VI3.HH_Alarm,412200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_7_VI3.H_Alarm,412200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_7_VI3.L_Alarm,412200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_7_VI3.LL_Alarm,412200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_7_VI3.BL_Alarm,412201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_7_VI3.OR_Alarm,412201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_7_VI3.UR_Alarm,412201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_7_VI3.ROC_Alarm,412201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_7_VI3.REST,412201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_7_VI3.ALRM,412201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_7_VI3.ANUN,412201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_7_VI3.AKED,412201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_7_VI3.Resetable,412201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_7_VI3.HH_Fault,412201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_7_VI3.H_Fault,412201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_7_VI3.L_Fault,412201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_7_VI3.LL_Fault,412201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_7_VI3.BL_Fault,412201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_7_VI3.OR_Fault,412201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_7_VI3.UR_Fault,412201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_7_VI3.ROC_Fault,412202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_7_VI3.Tot_EN,412202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_7_VI3.TAGR,412202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_7_VI3.ACKN,412202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_7_VI3.INTK,412202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_7_VI3.PLCFault,412202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI3.PLCIOFault,412202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI3.INTK_EN,412202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_7_VI3.Shelve,412202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_7_VI3.Shelved,412202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_7_VI3.Suppress,412202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_7_VI3.Suppressed,412202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_7_VI3.PCSuppress,412202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_7_VI3.PCUnSuppress,412202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_7_VI3.PCUnshelve,412202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_7_VI4.GlobalReset,412400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_7_VI4.HH_EN,412400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_7_VI4.H_EN,412400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_7_VI4.L_EN,412400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_7_VI4.LL_EN,412400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_7_VI4.BLEN,412400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_7_VI4.OR_EN,412400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_7_VI4.UREN,412400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_7_VI4.RC_EN,412400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_7_VI4.SuppressAA,412400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_7_VI4.SuppressLA,412400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_7_VI4.ConfigError,412400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_7_VI4.HH_Alarm,412400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_7_VI4.H_Alarm,412400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_7_VI4.L_Alarm,412400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_7_VI4.LL_Alarm,412400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_7_VI4.BL_Alarm,412401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_7_VI4.OR_Alarm,412401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_7_VI4.UR_Alarm,412401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_7_VI4.ROC_Alarm,412401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_7_VI4.REST,412401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_7_VI4.ALRM,412401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_7_VI4.ANUN,412401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_7_VI4.AKED,412401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_7_VI4.Resetable,412401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_7_VI4.HH_Fault,412401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_7_VI4.H_Fault,412401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_7_VI4.L_Fault,412401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_7_VI4.LL_Fault,412401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_7_VI4.BL_Fault,412401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_7_VI4.OR_Fault,412401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_7_VI4.UR_Fault,412401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_7_VI4.ROC_Fault,412402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_7_VI4.Tot_EN,412402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_7_VI4.TAGR,412402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_7_VI4.ACKN,412402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_7_VI4.INTK,412402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_7_VI4.PLCFault,412402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI4.PLCIOFault,412402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_7_VI4.INTK_EN,412402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_7_VI4.Shelve,412402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_7_VI4.Shelved,412402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_7_VI4.Suppress,412402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_7_VI4.Suppressed,412402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_7_VI4.PCSuppress,412402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_7_VI4.PCUnSuppress,412402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_7_VI4.PCUnshelve,412402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_8_VI1.GlobalReset,412600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_8_VI1.HH_EN,412600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_8_VI1.H_EN,412600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_8_VI1.L_EN,412600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_8_VI1.LL_EN,412600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_8_VI1.BLEN,412600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_8_VI1.OR_EN,412600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_8_VI1.UREN,412600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_8_VI1.RC_EN,412600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_8_VI1.SuppressAA,412600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_8_VI1.SuppressLA,412600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_8_VI1.ConfigError,412600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_8_VI1.HH_Alarm,412600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_8_VI1.H_Alarm,412600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_8_VI1.L_Alarm,412600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_8_VI1.LL_Alarm,412600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_8_VI1.BL_Alarm,412601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_8_VI1.OR_Alarm,412601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_8_VI1.UR_Alarm,412601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_8_VI1.ROC_Alarm,412601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_8_VI1.REST,412601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_8_VI1.ALRM,412601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_8_VI1.ANUN,412601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_8_VI1.AKED,412601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_8_VI1.Resetable,412601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_8_VI1.HH_Fault,412601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_8_VI1.H_Fault,412601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_8_VI1.L_Fault,412601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_8_VI1.LL_Fault,412601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_8_VI1.BL_Fault,412601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_8_VI1.OR_Fault,412601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_8_VI1.UR_Fault,412601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_8_VI1.ROC_Fault,412602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_8_VI1.Tot_EN,412602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_8_VI1.TAGR,412602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_8_VI1.ACKN,412602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_8_VI1.INTK,412602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_8_VI1.PLCFault,412602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI1.PLCIOFault,412602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI1.INTK_EN,412602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_8_VI1.Shelve,412602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_8_VI1.Shelved,412602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_8_VI1.Suppress,412602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_8_VI1.Suppressed,412602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_8_VI1.PCSuppress,412602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_8_VI1.PCUnSuppress,412602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_8_VI1.PCUnshelve,412602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_8_VI2.GlobalReset,412800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_8_VI2.HH_EN,412800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_8_VI2.H_EN,412800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_8_VI2.L_EN,412800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_8_VI2.LL_EN,412800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_8_VI2.BLEN,412800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_8_VI2.OR_EN,412800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_8_VI2.UREN,412800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_8_VI2.RC_EN,412800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_8_VI2.SuppressAA,412800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_8_VI2.SuppressLA,412800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_8_VI2.ConfigError,412800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_8_VI2.HH_Alarm,412800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_8_VI2.H_Alarm,412800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_8_VI2.L_Alarm,412800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_8_VI2.LL_Alarm,412800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_8_VI2.BL_Alarm,412801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_8_VI2.OR_Alarm,412801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_8_VI2.UR_Alarm,412801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_8_VI2.ROC_Alarm,412801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_8_VI2.REST,412801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_8_VI2.ALRM,412801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_8_VI2.ANUN,412801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_8_VI2.AKED,412801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_8_VI2.Resetable,412801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_8_VI2.HH_Fault,412801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_8_VI2.H_Fault,412801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_8_VI2.L_Fault,412801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_8_VI2.LL_Fault,412801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_8_VI2.BL_Fault,412801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_8_VI2.OR_Fault,412801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_8_VI2.UR_Fault,412801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_8_VI2.ROC_Fault,412802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_8_VI2.Tot_EN,412802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_8_VI2.TAGR,412802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_8_VI2.ACKN,412802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_8_VI2.INTK,412802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_8_VI2.PLCFault,412802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI2.PLCIOFault,412802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI2.INTK_EN,412802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_8_VI2.Shelve,412802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_8_VI2.Shelved,412802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_8_VI2.Suppress,412802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_8_VI2.Suppressed,412802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_8_VI2.PCSuppress,412802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_8_VI2.PCUnSuppress,412802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_8_VI2.PCUnshelve,412802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_8_VI3.GlobalReset,413000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_8_VI3.HH_EN,413000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_8_VI3.H_EN,413000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_8_VI3.L_EN,413000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_8_VI3.LL_EN,413000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_8_VI3.BLEN,413000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_8_VI3.OR_EN,413000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_8_VI3.UREN,413000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_8_VI3.RC_EN,413000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_8_VI3.SuppressAA,413000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_8_VI3.SuppressLA,413000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_8_VI3.ConfigError,413000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_8_VI3.HH_Alarm,413000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_8_VI3.H_Alarm,413000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_8_VI3.L_Alarm,413000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_8_VI3.LL_Alarm,413000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_8_VI3.BL_Alarm,413001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_8_VI3.OR_Alarm,413001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_8_VI3.UR_Alarm,413001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_8_VI3.ROC_Alarm,413001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_8_VI3.REST,413001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_8_VI3.ALRM,413001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_8_VI3.ANUN,413001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_8_VI3.AKED,413001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_8_VI3.Resetable,413001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_8_VI3.HH_Fault,413001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_8_VI3.H_Fault,413001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_8_VI3.L_Fault,413001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_8_VI3.LL_Fault,413001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_8_VI3.BL_Fault,413001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_8_VI3.OR_Fault,413001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_8_VI3.UR_Fault,413001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_8_VI3.ROC_Fault,413002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_8_VI3.Tot_EN,413002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_8_VI3.TAGR,413002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_8_VI3.ACKN,413002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_8_VI3.INTK,413002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_8_VI3.PLCFault,413002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI3.PLCIOFault,413002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI3.INTK_EN,413002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_8_VI3.Shelve,413002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_8_VI3.Shelved,413002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_8_VI3.Suppress,413002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_8_VI3.Suppressed,413002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_8_VI3.PCSuppress,413002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_8_VI3.PCUnSuppress,413002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_8_VI3.PCUnshelve,413002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_8_VI4.GlobalReset,413200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_8_VI4.HH_EN,413200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_8_VI4.H_EN,413200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_8_VI4.L_EN,413200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_8_VI4.LL_EN,413200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_8_VI4.BLEN,413200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_8_VI4.OR_EN,413200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_8_VI4.UREN,413200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_8_VI4.RC_EN,413200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_8_VI4.SuppressAA,413200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_8_VI4.SuppressLA,413200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_8_VI4.ConfigError,413200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_8_VI4.HH_Alarm,413200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_8_VI4.H_Alarm,413200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_8_VI4.L_Alarm,413200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_8_VI4.LL_Alarm,413200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_8_VI4.BL_Alarm,413201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_8_VI4.OR_Alarm,413201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_8_VI4.UR_Alarm,413201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_8_VI4.ROC_Alarm,413201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_8_VI4.REST,413201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_8_VI4.ALRM,413201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_8_VI4.ANUN,413201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_8_VI4.AKED,413201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_8_VI4.Resetable,413201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_8_VI4.HH_Fault,413201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_8_VI4.H_Fault,413201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_8_VI4.L_Fault,413201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_8_VI4.LL_Fault,413201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_8_VI4.BL_Fault,413201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_8_VI4.OR_Fault,413201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_8_VI4.UR_Fault,413201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_8_VI4.ROC_Fault,413202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_8_VI4.Tot_EN,413202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_8_VI4.TAGR,413202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_8_VI4.ACKN,413202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_8_VI4.INTK,413202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_8_VI4.PLCFault,413202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI4.PLCIOFault,413202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_8_VI4.INTK_EN,413202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_8_VI4.Shelve,413202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_8_VI4.Shelved,413202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_8_VI4.Suppress,413202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_8_VI4.Suppressed,413202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_8_VI4.PCSuppress,413202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_8_VI4.PCUnSuppress,413202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_8_VI4.PCUnshelve,413202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_9_VI1.GlobalReset,413400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_9_VI1.HH_EN,413400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_9_VI1.H_EN,413400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_9_VI1.L_EN,413400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_9_VI1.LL_EN,413400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_9_VI1.BLEN,413400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_9_VI1.OR_EN,413400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_9_VI1.UREN,413400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_9_VI1.RC_EN,413400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_9_VI1.SuppressAA,413400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_9_VI1.SuppressLA,413400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_9_VI1.ConfigError,413400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_9_VI1.HH_Alarm,413400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_9_VI1.H_Alarm,413400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_9_VI1.L_Alarm,413400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_9_VI1.LL_Alarm,413400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_9_VI1.BL_Alarm,413401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_9_VI1.OR_Alarm,413401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_9_VI1.UR_Alarm,413401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_9_VI1.ROC_Alarm,413401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_9_VI1.REST,413401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_9_VI1.ALRM,413401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_9_VI1.ANUN,413401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_9_VI1.AKED,413401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_9_VI1.Resetable,413401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_9_VI1.HH_Fault,413401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_9_VI1.H_Fault,413401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_9_VI1.L_Fault,413401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_9_VI1.LL_Fault,413401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_9_VI1.BL_Fault,413401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_9_VI1.OR_Fault,413401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_9_VI1.UR_Fault,413401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_9_VI1.ROC_Fault,413402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_9_VI1.Tot_EN,413402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_9_VI1.TAGR,413402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_9_VI1.ACKN,413402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_9_VI1.INTK,413402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_9_VI1.PLCFault,413402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI1.PLCIOFault,413402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI1.INTK_EN,413402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_9_VI1.Shelve,413402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_9_VI1.Shelved,413402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_9_VI1.Suppress,413402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_9_VI1.Suppressed,413402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_9_VI1.PCSuppress,413402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_9_VI1.PCUnSuppress,413402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_9_VI1.PCUnshelve,413402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_9_VI2.GlobalReset,413600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_9_VI2.HH_EN,413600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_9_VI2.H_EN,413600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_9_VI2.L_EN,413600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_9_VI2.LL_EN,413600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_9_VI2.BLEN,413600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_9_VI2.OR_EN,413600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_9_VI2.UREN,413600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_9_VI2.RC_EN,413600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_9_VI2.SuppressAA,413600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_9_VI2.SuppressLA,413600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_9_VI2.ConfigError,413600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_9_VI2.HH_Alarm,413600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_9_VI2.H_Alarm,413600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_9_VI2.L_Alarm,413600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_9_VI2.LL_Alarm,413600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_9_VI2.BL_Alarm,413601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_9_VI2.OR_Alarm,413601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_9_VI2.UR_Alarm,413601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_9_VI2.ROC_Alarm,413601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_9_VI2.REST,413601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_9_VI2.ALRM,413601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_9_VI2.ANUN,413601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_9_VI2.AKED,413601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_9_VI2.Resetable,413601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_9_VI2.HH_Fault,413601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_9_VI2.H_Fault,413601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_9_VI2.L_Fault,413601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_9_VI2.LL_Fault,413601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_9_VI2.BL_Fault,413601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_9_VI2.OR_Fault,413601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_9_VI2.UR_Fault,413601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_9_VI2.ROC_Fault,413602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_9_VI2.Tot_EN,413602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_9_VI2.TAGR,413602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_9_VI2.ACKN,413602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_9_VI2.INTK,413602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_9_VI2.PLCFault,413602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI2.PLCIOFault,413602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI2.INTK_EN,413602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_9_VI2.Shelve,413602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_9_VI2.Shelved,413602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_9_VI2.Suppress,413602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_9_VI2.Suppressed,413602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_9_VI2.PCSuppress,413602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_9_VI2.PCUnSuppress,413602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_9_VI2.PCUnshelve,413602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_9_VI3.GlobalReset,413800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_9_VI3.HH_EN,413800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_9_VI3.H_EN,413800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_9_VI3.L_EN,413800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_9_VI3.LL_EN,413800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_9_VI3.BLEN,413800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_9_VI3.OR_EN,413800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_9_VI3.UREN,413800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_9_VI3.RC_EN,413800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_9_VI3.SuppressAA,413800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_9_VI3.SuppressLA,413800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_9_VI3.ConfigError,413800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_9_VI3.HH_Alarm,413800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_9_VI3.H_Alarm,413800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_9_VI3.L_Alarm,413800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_9_VI3.LL_Alarm,413800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_9_VI3.BL_Alarm,413801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_9_VI3.OR_Alarm,413801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_9_VI3.UR_Alarm,413801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_9_VI3.ROC_Alarm,413801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_9_VI3.REST,413801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_9_VI3.ALRM,413801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_9_VI3.ANUN,413801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_9_VI3.AKED,413801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_9_VI3.Resetable,413801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_9_VI3.HH_Fault,413801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_9_VI3.H_Fault,413801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_9_VI3.L_Fault,413801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_9_VI3.LL_Fault,413801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_9_VI3.BL_Fault,413801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_9_VI3.OR_Fault,413801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_9_VI3.UR_Fault,413801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_9_VI3.ROC_Fault,413802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_9_VI3.Tot_EN,413802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_9_VI3.TAGR,413802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_9_VI3.ACKN,413802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_9_VI3.INTK,413802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_9_VI3.PLCFault,413802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI3.PLCIOFault,413802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI3.INTK_EN,413802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_9_VI3.Shelve,413802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_9_VI3.Shelved,413802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_9_VI3.Suppress,413802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_9_VI3.Suppressed,413802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_9_VI3.PCSuppress,413802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_9_VI3.PCUnSuppress,413802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_9_VI3.PCUnshelve,413802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_MTR_0103_9_VI4.GlobalReset,414000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_MTR_0103_9_VI4.HH_EN,414000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_MTR_0103_9_VI4.H_EN,414000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_MTR_0103_9_VI4.L_EN,414000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_MTR_0103_9_VI4.LL_EN,414000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_MTR_0103_9_VI4.BLEN,414000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_MTR_0103_9_VI4.OR_EN,414000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_MTR_0103_9_VI4.UREN,414000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_MTR_0103_9_VI4.RC_EN,414000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_MTR_0103_9_VI4.SuppressAA,414000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_MTR_0103_9_VI4.SuppressLA,414000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_MTR_0103_9_VI4.ConfigError,414000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_MTR_0103_9_VI4.HH_Alarm,414000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_MTR_0103_9_VI4.H_Alarm,414000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_MTR_0103_9_VI4.L_Alarm,414000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_MTR_0103_9_VI4.LL_Alarm,414000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_MTR_0103_9_VI4.BL_Alarm,414001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_MTR_0103_9_VI4.OR_Alarm,414001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_MTR_0103_9_VI4.UR_Alarm,414001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_MTR_0103_9_VI4.ROC_Alarm,414001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_MTR_0103_9_VI4.REST,414001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_MTR_0103_9_VI4.ALRM,414001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_MTR_0103_9_VI4.ANUN,414001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_MTR_0103_9_VI4.AKED,414001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_MTR_0103_9_VI4.Resetable,414001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_MTR_0103_9_VI4.HH_Fault,414001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_MTR_0103_9_VI4.H_Fault,414001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_MTR_0103_9_VI4.L_Fault,414001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_MTR_0103_9_VI4.LL_Fault,414001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_MTR_0103_9_VI4.BL_Fault,414001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_MTR_0103_9_VI4.OR_Fault,414001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_MTR_0103_9_VI4.UR_Fault,414001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_MTR_0103_9_VI4.ROC_Fault,414002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_MTR_0103_9_VI4.Tot_EN,414002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_MTR_0103_9_VI4.TAGR,414002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_MTR_0103_9_VI4.ACKN,414002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_MTR_0103_9_VI4.INTK,414002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_MTR_0103_9_VI4.PLCFault,414002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI4.PLCIOFault,414002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_MTR_0103_9_VI4.INTK_EN,414002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_MTR_0103_9_VI4.Shelve,414002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_MTR_0103_9_VI4.Shelved,414002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_MTR_0103_9_VI4.Suppress,414002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_MTR_0103_9_VI4.Suppressed,414002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_MTR_0103_9_VI4.PCSuppress,414002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_MTR_0103_9_VI4.PCUnSuppress,414002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_MTR_0103_9_VI4.PCUnshelve,414002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0102_1_PI.GlobalReset,414200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0102_1_PI.HH_EN,414200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0102_1_PI.H_EN,414200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0102_1_PI.L_EN,414200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0102_1_PI.LL_EN,414200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0102_1_PI.BLEN,414200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0102_1_PI.OR_EN,414200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0102_1_PI.UREN,414200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0102_1_PI.RC_EN,414200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0102_1_PI.SuppressAA,414200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0102_1_PI.SuppressLA,414200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0102_1_PI.ConfigError,414200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0102_1_PI.HH_Alarm,414200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0102_1_PI.H_Alarm,414200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0102_1_PI.L_Alarm,414200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0102_1_PI.LL_Alarm,414200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0102_1_PI.BL_Alarm,414201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0102_1_PI.OR_Alarm,414201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0102_1_PI.UR_Alarm,414201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0102_1_PI.ROC_Alarm,414201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0102_1_PI.REST,414201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0102_1_PI.ALRM,414201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0102_1_PI.ANUN,414201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0102_1_PI.AKED,414201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0102_1_PI.Resetable,414201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0102_1_PI.HH_Fault,414201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0102_1_PI.H_Fault,414201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0102_1_PI.L_Fault,414201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0102_1_PI.LL_Fault,414201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0102_1_PI.BL_Fault,414201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0102_1_PI.OR_Fault,414201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0102_1_PI.UR_Fault,414201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0102_1_PI.ROC_Fault,414202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0102_1_PI.Tot_EN,414202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0102_1_PI.TAGR,414202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0102_1_PI.ACKN,414202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0102_1_PI.INTK,414202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0102_1_PI.PLCFault,414202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_1_PI.PLCIOFault,414202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_1_PI.INTK_EN,414202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0102_1_PI.Shelve,414202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0102_1_PI.Shelved,414202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0102_1_PI.Suppress,414202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0102_1_PI.Suppressed,414202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0102_1_PI.PCSuppress,414202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0102_1_PI.PCUnSuppress,414202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0102_1_PI.PCUnshelve,414202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0102_2_PI.GlobalReset,414400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0102_2_PI.HH_EN,414400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0102_2_PI.H_EN,414400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0102_2_PI.L_EN,414400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0102_2_PI.LL_EN,414400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0102_2_PI.BLEN,414400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0102_2_PI.OR_EN,414400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0102_2_PI.UREN,414400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0102_2_PI.RC_EN,414400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0102_2_PI.SuppressAA,414400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0102_2_PI.SuppressLA,414400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0102_2_PI.ConfigError,414400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0102_2_PI.HH_Alarm,414400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0102_2_PI.H_Alarm,414400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0102_2_PI.L_Alarm,414400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0102_2_PI.LL_Alarm,414400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0102_2_PI.BL_Alarm,414401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0102_2_PI.OR_Alarm,414401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0102_2_PI.UR_Alarm,414401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0102_2_PI.ROC_Alarm,414401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0102_2_PI.REST,414401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0102_2_PI.ALRM,414401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0102_2_PI.ANUN,414401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0102_2_PI.AKED,414401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0102_2_PI.Resetable,414401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0102_2_PI.HH_Fault,414401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0102_2_PI.H_Fault,414401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0102_2_PI.L_Fault,414401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0102_2_PI.LL_Fault,414401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0102_2_PI.BL_Fault,414401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0102_2_PI.OR_Fault,414401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0102_2_PI.UR_Fault,414401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0102_2_PI.ROC_Fault,414402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0102_2_PI.Tot_EN,414402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0102_2_PI.TAGR,414402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0102_2_PI.ACKN,414402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0102_2_PI.INTK,414402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0102_2_PI.PLCFault,414402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_2_PI.PLCIOFault,414402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_2_PI.INTK_EN,414402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0102_2_PI.Shelve,414402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0102_2_PI.Shelved,414402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0102_2_PI.Suppress,414402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0102_2_PI.Suppressed,414402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0102_2_PI.PCSuppress,414402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0102_2_PI.PCUnSuppress,414402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0102_2_PI.PCUnshelve,414402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_1_PI.GlobalReset,414600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_1_PI.HH_EN,414600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_1_PI.H_EN,414600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_1_PI.L_EN,414600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_1_PI.LL_EN,414600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_1_PI.BLEN,414600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_1_PI.OR_EN,414600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_1_PI.UREN,414600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_1_PI.RC_EN,414600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_1_PI.SuppressAA,414600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_1_PI.SuppressLA,414600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_1_PI.ConfigError,414600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_1_PI.HH_Alarm,414600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_1_PI.H_Alarm,414600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_1_PI.L_Alarm,414600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_1_PI.LL_Alarm,414600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_1_PI.BL_Alarm,414601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_1_PI.OR_Alarm,414601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_1_PI.UR_Alarm,414601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_1_PI.ROC_Alarm,414601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_1_PI.REST,414601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_1_PI.ALRM,414601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_1_PI.ANUN,414601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_1_PI.AKED,414601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_1_PI.Resetable,414601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_1_PI.HH_Fault,414601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_1_PI.H_Fault,414601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_1_PI.L_Fault,414601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_1_PI.LL_Fault,414601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_1_PI.BL_Fault,414601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_1_PI.OR_Fault,414601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_1_PI.UR_Fault,414601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_1_PI.ROC_Fault,414602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_1_PI.Tot_EN,414602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_1_PI.TAGR,414602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_1_PI.ACKN,414602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_1_PI.INTK,414602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_1_PI.PLCFault,414602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_1_PI.PLCIOFault,414602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_1_PI.INTK_EN,414602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_1_PI.Shelve,414602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_1_PI.Shelved,414602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_1_PI.Suppress,414602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_1_PI.Suppressed,414602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_1_PI.PCSuppress,414602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_1_PI.PCUnSuppress,414602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_1_PI.PCUnshelve,414602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_2_PI.GlobalReset,414800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_2_PI.HH_EN,414800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_2_PI.H_EN,414800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_2_PI.L_EN,414800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_2_PI.LL_EN,414800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_2_PI.BLEN,414800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_2_PI.OR_EN,414800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_2_PI.UREN,414800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_2_PI.RC_EN,414800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_2_PI.SuppressAA,414800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_2_PI.SuppressLA,414800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_2_PI.ConfigError,414800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_2_PI.HH_Alarm,414800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_2_PI.H_Alarm,414800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_2_PI.L_Alarm,414800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_2_PI.LL_Alarm,414800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_2_PI.BL_Alarm,414801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_2_PI.OR_Alarm,414801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_2_PI.UR_Alarm,414801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_2_PI.ROC_Alarm,414801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_2_PI.REST,414801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_2_PI.ALRM,414801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_2_PI.ANUN,414801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_2_PI.AKED,414801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_2_PI.Resetable,414801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_2_PI.HH_Fault,414801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_2_PI.H_Fault,414801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_2_PI.L_Fault,414801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_2_PI.LL_Fault,414801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_2_PI.BL_Fault,414801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_2_PI.OR_Fault,414801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_2_PI.UR_Fault,414801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_2_PI.ROC_Fault,414802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_2_PI.Tot_EN,414802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_2_PI.TAGR,414802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_2_PI.ACKN,414802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_2_PI.INTK,414802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_2_PI.PLCFault,414802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_2_PI.PLCIOFault,414802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_2_PI.INTK_EN,414802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_2_PI.Shelve,414802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_2_PI.Shelved,414802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_2_PI.Suppress,414802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_2_PI.Suppressed,414802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_2_PI.PCSuppress,414802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_2_PI.PCUnSuppress,414802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_2_PI.PCUnshelve,414802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_3_PI.GlobalReset,415000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_3_PI.HH_EN,415000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_3_PI.H_EN,415000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_3_PI.L_EN,415000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_3_PI.LL_EN,415000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_3_PI.BLEN,415000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_3_PI.OR_EN,415000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_3_PI.UREN,415000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_3_PI.RC_EN,415000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_3_PI.SuppressAA,415000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_3_PI.SuppressLA,415000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_3_PI.ConfigError,415000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_3_PI.HH_Alarm,415000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_3_PI.H_Alarm,415000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_3_PI.L_Alarm,415000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_3_PI.LL_Alarm,415000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_3_PI.BL_Alarm,415001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_3_PI.OR_Alarm,415001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_3_PI.UR_Alarm,415001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_3_PI.ROC_Alarm,415001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_3_PI.REST,415001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_3_PI.ALRM,415001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_3_PI.ANUN,415001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_3_PI.AKED,415001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_3_PI.Resetable,415001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_3_PI.HH_Fault,415001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_3_PI.H_Fault,415001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_3_PI.L_Fault,415001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_3_PI.LL_Fault,415001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_3_PI.BL_Fault,415001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_3_PI.OR_Fault,415001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_3_PI.UR_Fault,415001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_3_PI.ROC_Fault,415002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_3_PI.Tot_EN,415002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_3_PI.TAGR,415002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_3_PI.ACKN,415002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_3_PI.INTK,415002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_3_PI.PLCFault,415002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_3_PI.PLCIOFault,415002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_3_PI.INTK_EN,415002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_3_PI.Shelve,415002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_3_PI.Shelved,415002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_3_PI.Suppress,415002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_3_PI.Suppressed,415002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_3_PI.PCSuppress,415002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_3_PI.PCUnSuppress,415002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_3_PI.PCUnshelve,415002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_4_PI.GlobalReset,415200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_4_PI.HH_EN,415200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_4_PI.H_EN,415200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_4_PI.L_EN,415200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_4_PI.LL_EN,415200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_4_PI.BLEN,415200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_4_PI.OR_EN,415200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_4_PI.UREN,415200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_4_PI.RC_EN,415200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_4_PI.SuppressAA,415200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_4_PI.SuppressLA,415200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_4_PI.ConfigError,415200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_4_PI.HH_Alarm,415200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_4_PI.H_Alarm,415200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_4_PI.L_Alarm,415200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_4_PI.LL_Alarm,415200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_4_PI.BL_Alarm,415201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_4_PI.OR_Alarm,415201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_4_PI.UR_Alarm,415201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_4_PI.ROC_Alarm,415201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_4_PI.REST,415201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_4_PI.ALRM,415201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_4_PI.ANUN,415201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_4_PI.AKED,415201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_4_PI.Resetable,415201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_4_PI.HH_Fault,415201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_4_PI.H_Fault,415201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_4_PI.L_Fault,415201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_4_PI.LL_Fault,415201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_4_PI.BL_Fault,415201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_4_PI.OR_Fault,415201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_4_PI.UR_Fault,415201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_4_PI.ROC_Fault,415202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_4_PI.Tot_EN,415202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_4_PI.TAGR,415202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_4_PI.ACKN,415202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_4_PI.INTK,415202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_4_PI.PLCFault,415202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_4_PI.PLCIOFault,415202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_4_PI.INTK_EN,415202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_4_PI.Shelve,415202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_4_PI.Shelved,415202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_4_PI.Suppress,415202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_4_PI.Suppressed,415202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_4_PI.PCSuppress,415202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_4_PI.PCUnSuppress,415202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_4_PI.PCUnshelve,415202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_5_PI.GlobalReset,415400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_5_PI.HH_EN,415400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_5_PI.H_EN,415400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_5_PI.L_EN,415400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_5_PI.LL_EN,415400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_5_PI.BLEN,415400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_5_PI.OR_EN,415400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_5_PI.UREN,415400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_5_PI.RC_EN,415400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_5_PI.SuppressAA,415400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_5_PI.SuppressLA,415400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_5_PI.ConfigError,415400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_5_PI.HH_Alarm,415400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_5_PI.H_Alarm,415400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_5_PI.L_Alarm,415400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_5_PI.LL_Alarm,415400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_5_PI.BL_Alarm,415401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_5_PI.OR_Alarm,415401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_5_PI.UR_Alarm,415401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_5_PI.ROC_Alarm,415401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_5_PI.REST,415401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_5_PI.ALRM,415401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_5_PI.ANUN,415401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_5_PI.AKED,415401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_5_PI.Resetable,415401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_5_PI.HH_Fault,415401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_5_PI.H_Fault,415401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_5_PI.L_Fault,415401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_5_PI.LL_Fault,415401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_5_PI.BL_Fault,415401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_5_PI.OR_Fault,415401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_5_PI.UR_Fault,415401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_5_PI.ROC_Fault,415402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_5_PI.Tot_EN,415402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_5_PI.TAGR,415402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_5_PI.ACKN,415402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_5_PI.INTK,415402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_5_PI.PLCFault,415402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_5_PI.PLCIOFault,415402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_5_PI.INTK_EN,415402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_5_PI.Shelve,415402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_5_PI.Shelved,415402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_5_PI.Suppress,415402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_5_PI.Suppressed,415402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_5_PI.PCSuppress,415402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_5_PI.PCUnSuppress,415402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_5_PI.PCUnshelve,415402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_6_PI.GlobalReset,415600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_6_PI.HH_EN,415600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_6_PI.H_EN,415600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_6_PI.L_EN,415600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_6_PI.LL_EN,415600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_6_PI.BLEN,415600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_6_PI.OR_EN,415600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_6_PI.UREN,415600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_6_PI.RC_EN,415600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_6_PI.SuppressAA,415600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_6_PI.SuppressLA,415600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_6_PI.ConfigError,415600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_6_PI.HH_Alarm,415600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_6_PI.H_Alarm,415600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_6_PI.L_Alarm,415600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_6_PI.LL_Alarm,415600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_6_PI.BL_Alarm,415601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_6_PI.OR_Alarm,415601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_6_PI.UR_Alarm,415601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_6_PI.ROC_Alarm,415601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_6_PI.REST,415601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_6_PI.ALRM,415601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_6_PI.ANUN,415601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_6_PI.AKED,415601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_6_PI.Resetable,415601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_6_PI.HH_Fault,415601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_6_PI.H_Fault,415601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_6_PI.L_Fault,415601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_6_PI.LL_Fault,415601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_6_PI.BL_Fault,415601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_6_PI.OR_Fault,415601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_6_PI.UR_Fault,415601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_6_PI.ROC_Fault,415602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_6_PI.Tot_EN,415602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_6_PI.TAGR,415602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_6_PI.ACKN,415602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_6_PI.INTK,415602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_6_PI.PLCFault,415602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_6_PI.PLCIOFault,415602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_6_PI.INTK_EN,415602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_6_PI.Shelve,415602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_6_PI.Shelved,415602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_6_PI.Suppress,415602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_6_PI.Suppressed,415602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_6_PI.PCSuppress,415602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_6_PI.PCUnSuppress,415602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_6_PI.PCUnshelve,415602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_7_PI.GlobalReset,415800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_7_PI.HH_EN,415800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_7_PI.H_EN,415800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_7_PI.L_EN,415800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_7_PI.LL_EN,415800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_7_PI.BLEN,415800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_7_PI.OR_EN,415800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_7_PI.UREN,415800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_7_PI.RC_EN,415800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_7_PI.SuppressAA,415800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_7_PI.SuppressLA,415800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_7_PI.ConfigError,415800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_7_PI.HH_Alarm,415800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_7_PI.H_Alarm,415800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_7_PI.L_Alarm,415800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_7_PI.LL_Alarm,415800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_7_PI.BL_Alarm,415801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_7_PI.OR_Alarm,415801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_7_PI.UR_Alarm,415801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_7_PI.ROC_Alarm,415801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_7_PI.REST,415801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_7_PI.ALRM,415801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_7_PI.ANUN,415801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_7_PI.AKED,415801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_7_PI.Resetable,415801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_7_PI.HH_Fault,415801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_7_PI.H_Fault,415801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_7_PI.L_Fault,415801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_7_PI.LL_Fault,415801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_7_PI.BL_Fault,415801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_7_PI.OR_Fault,415801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_7_PI.UR_Fault,415801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_7_PI.ROC_Fault,415802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_7_PI.Tot_EN,415802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_7_PI.TAGR,415802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_7_PI.ACKN,415802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_7_PI.INTK,415802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_7_PI.PLCFault,415802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_7_PI.PLCIOFault,415802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_7_PI.INTK_EN,415802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_7_PI.Shelve,415802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_7_PI.Shelved,415802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_7_PI.Suppress,415802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_7_PI.Suppressed,415802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_7_PI.PCSuppress,415802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_7_PI.PCUnSuppress,415802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_7_PI.PCUnshelve,415802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_8_PI.GlobalReset,416000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_8_PI.HH_EN,416000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_8_PI.H_EN,416000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_8_PI.L_EN,416000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_8_PI.LL_EN,416000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_8_PI.BLEN,416000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_8_PI.OR_EN,416000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_8_PI.UREN,416000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_8_PI.RC_EN,416000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_8_PI.SuppressAA,416000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_8_PI.SuppressLA,416000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_8_PI.ConfigError,416000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_8_PI.HH_Alarm,416000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_8_PI.H_Alarm,416000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_8_PI.L_Alarm,416000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_8_PI.LL_Alarm,416000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_8_PI.BL_Alarm,416001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_8_PI.OR_Alarm,416001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_8_PI.UR_Alarm,416001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_8_PI.ROC_Alarm,416001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_8_PI.REST,416001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_8_PI.ALRM,416001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_8_PI.ANUN,416001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_8_PI.AKED,416001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_8_PI.Resetable,416001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_8_PI.HH_Fault,416001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_8_PI.H_Fault,416001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_8_PI.L_Fault,416001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_8_PI.LL_Fault,416001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_8_PI.BL_Fault,416001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_8_PI.OR_Fault,416001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_8_PI.UR_Fault,416001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_8_PI.ROC_Fault,416002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_8_PI.Tot_EN,416002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_8_PI.TAGR,416002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_8_PI.ACKN,416002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_8_PI.INTK,416002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_8_PI.PLCFault,416002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_8_PI.PLCIOFault,416002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_8_PI.INTK_EN,416002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_8_PI.Shelve,416002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_8_PI.Shelved,416002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_8_PI.Suppress,416002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_8_PI.Suppressed,416002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_8_PI.PCSuppress,416002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_8_PI.PCUnSuppress,416002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_8_PI.PCUnshelve,416002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0103_9_PI.GlobalReset,416200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0103_9_PI.HH_EN,416200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0103_9_PI.H_EN,416200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0103_9_PI.L_EN,416200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0103_9_PI.LL_EN,416200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0103_9_PI.BLEN,416200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0103_9_PI.OR_EN,416200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0103_9_PI.UREN,416200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0103_9_PI.RC_EN,416200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0103_9_PI.SuppressAA,416200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0103_9_PI.SuppressLA,416200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0103_9_PI.ConfigError,416200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0103_9_PI.HH_Alarm,416200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0103_9_PI.H_Alarm,416200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0103_9_PI.L_Alarm,416200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0103_9_PI.LL_Alarm,416200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0103_9_PI.BL_Alarm,416201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0103_9_PI.OR_Alarm,416201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0103_9_PI.UR_Alarm,416201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0103_9_PI.ROC_Alarm,416201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0103_9_PI.REST,416201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0103_9_PI.ALRM,416201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0103_9_PI.ANUN,416201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0103_9_PI.AKED,416201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0103_9_PI.Resetable,416201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0103_9_PI.HH_Fault,416201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0103_9_PI.H_Fault,416201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0103_9_PI.L_Fault,416201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0103_9_PI.LL_Fault,416201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0103_9_PI.BL_Fault,416201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0103_9_PI.OR_Fault,416201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0103_9_PI.UR_Fault,416201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0103_9_PI.ROC_Fault,416202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0103_9_PI.Tot_EN,416202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0103_9_PI.TAGR,416202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0103_9_PI.ACKN,416202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0103_9_PI.INTK,416202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0103_9_PI.PLCFault,416202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_9_PI.PLCIOFault,416202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0103_9_PI.INTK_EN,416202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0103_9_PI.Shelve,416202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0103_9_PI.Shelved,416202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0103_9_PI.Suppress,416202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0103_9_PI.Suppressed,416202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0103_9_PI.PCSuppress,416202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0103_9_PI.PCUnSuppress,416202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0103_9_PI.PCUnshelve,416202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0104_1_PI.GlobalReset,416400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0104_1_PI.HH_EN,416400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PIT_0104_1_PI.H_EN,416400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PIT_0104_1_PI.L_EN,416400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PIT_0104_1_PI.LL_EN,416400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PIT_0104_1_PI.BLEN,416400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PIT_0104_1_PI.OR_EN,416400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PIT_0104_1_PI.UREN,416400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PIT_0104_1_PI.RC_EN,416400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PIT_0104_1_PI.SuppressAA,416400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PIT_0104_1_PI.SuppressLA,416400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PIT_0104_1_PI.ConfigError,416400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PIT_0104_1_PI.HH_Alarm,416400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PIT_0104_1_PI.H_Alarm,416400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PIT_0104_1_PI.L_Alarm,416400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PIT_0104_1_PI.LL_Alarm,416400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PIT_0104_1_PI.BL_Alarm,416401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PIT_0104_1_PI.OR_Alarm,416401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PIT_0104_1_PI.UR_Alarm,416401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PIT_0104_1_PI.ROC_Alarm,416401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PIT_0104_1_PI.REST,416401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PIT_0104_1_PI.ALRM,416401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PIT_0104_1_PI.ANUN,416401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0104_1_PI.AKED,416401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0104_1_PI.Resetable,416401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0104_1_PI.HH_Fault,416401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PIT_0104_1_PI.H_Fault,416401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PIT_0104_1_PI.L_Fault,416401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PIT_0104_1_PI.LL_Fault,416401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PIT_0104_1_PI.BL_Fault,416401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PIT_0104_1_PI.OR_Fault,416401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PIT_0104_1_PI.UR_Fault,416401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PIT_0104_1_PI.ROC_Fault,416402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PIT_0104_1_PI.Tot_EN,416402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PIT_0104_1_PI.TAGR,416402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PIT_0104_1_PI.ACKN,416402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PIT_0104_1_PI.INTK,416402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PIT_0104_1_PI.PLCFault,416402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0104_1_PI.PLCIOFault,416402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0104_1_PI.INTK_EN,416402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PIT_0104_1_PI.Shelve,416402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PIT_0104_1_PI.Shelved,416402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PIT_0104_1_PI.Suppress,416402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PIT_0104_1_PI.Suppressed,416402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PIT_0104_1_PI.PCSuppress,416402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0104_1_PI.PCUnSuppress,416402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0104_1_PI.PCUnshelve,416402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_1_VI1.GlobalReset,416600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_1_VI1.HH_EN,416600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_1_VI1.H_EN,416600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_1_VI1.L_EN,416600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_1_VI1.LL_EN,416600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_1_VI1.BLEN,416600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_1_VI1.OR_EN,416600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_1_VI1.UREN,416600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_1_VI1.RC_EN,416600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_1_VI1.SuppressAA,416600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_1_VI1.SuppressLA,416600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_1_VI1.ConfigError,416600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_1_VI1.HH_Alarm,416600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_1_VI1.H_Alarm,416600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_1_VI1.L_Alarm,416600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_1_VI1.LL_Alarm,416600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_1_VI1.BL_Alarm,416601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_1_VI1.OR_Alarm,416601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_1_VI1.UR_Alarm,416601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_1_VI1.ROC_Alarm,416601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_1_VI1.REST,416601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_1_VI1.ALRM,416601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_1_VI1.ANUN,416601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_1_VI1.AKED,416601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_1_VI1.Resetable,416601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_1_VI1.HH_Fault,416601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_1_VI1.H_Fault,416601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_1_VI1.L_Fault,416601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_1_VI1.LL_Fault,416601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_1_VI1.BL_Fault,416601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_1_VI1.OR_Fault,416601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_1_VI1.UR_Fault,416601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_1_VI1.ROC_Fault,416602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_1_VI1.Tot_EN,416602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_1_VI1.TAGR,416602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_1_VI1.ACKN,416602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_1_VI1.INTK,416602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_1_VI1.PLCFault,416602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI1.PLCIOFault,416602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI1.INTK_EN,416602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_1_VI1.Shelve,416602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_1_VI1.Shelved,416602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_1_VI1.Suppress,416602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_1_VI1.Suppressed,416602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_1_VI1.PCSuppress,416602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_1_VI1.PCUnSuppress,416602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_1_VI1.PCUnshelve,416602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_1_VI2.GlobalReset,416800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_1_VI2.HH_EN,416800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_1_VI2.H_EN,416800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_1_VI2.L_EN,416800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_1_VI2.LL_EN,416800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_1_VI2.BLEN,416800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_1_VI2.OR_EN,416800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_1_VI2.UREN,416800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_1_VI2.RC_EN,416800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_1_VI2.SuppressAA,416800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_1_VI2.SuppressLA,416800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_1_VI2.ConfigError,416800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_1_VI2.HH_Alarm,416800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_1_VI2.H_Alarm,416800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_1_VI2.L_Alarm,416800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_1_VI2.LL_Alarm,416800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_1_VI2.BL_Alarm,416801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_1_VI2.OR_Alarm,416801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_1_VI2.UR_Alarm,416801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_1_VI2.ROC_Alarm,416801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_1_VI2.REST,416801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_1_VI2.ALRM,416801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_1_VI2.ANUN,416801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_1_VI2.AKED,416801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_1_VI2.Resetable,416801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_1_VI2.HH_Fault,416801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_1_VI2.H_Fault,416801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_1_VI2.L_Fault,416801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_1_VI2.LL_Fault,416801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_1_VI2.BL_Fault,416801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_1_VI2.OR_Fault,416801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_1_VI2.UR_Fault,416801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_1_VI2.ROC_Fault,416802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_1_VI2.Tot_EN,416802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_1_VI2.TAGR,416802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_1_VI2.ACKN,416802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_1_VI2.INTK,416802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_1_VI2.PLCFault,416802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI2.PLCIOFault,416802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI2.INTK_EN,416802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_1_VI2.Shelve,416802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_1_VI2.Shelved,416802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_1_VI2.Suppress,416802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_1_VI2.Suppressed,416802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_1_VI2.PCSuppress,416802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_1_VI2.PCUnSuppress,416802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_1_VI2.PCUnshelve,416802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_1_VI3.GlobalReset,417000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_1_VI3.HH_EN,417000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_1_VI3.H_EN,417000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_1_VI3.L_EN,417000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_1_VI3.LL_EN,417000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_1_VI3.BLEN,417000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_1_VI3.OR_EN,417000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_1_VI3.UREN,417000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_1_VI3.RC_EN,417000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_1_VI3.SuppressAA,417000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_1_VI3.SuppressLA,417000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_1_VI3.ConfigError,417000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_1_VI3.HH_Alarm,417000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_1_VI3.H_Alarm,417000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_1_VI3.L_Alarm,417000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_1_VI3.LL_Alarm,417000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_1_VI3.BL_Alarm,417001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_1_VI3.OR_Alarm,417001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_1_VI3.UR_Alarm,417001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_1_VI3.ROC_Alarm,417001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_1_VI3.REST,417001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_1_VI3.ALRM,417001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_1_VI3.ANUN,417001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_1_VI3.AKED,417001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_1_VI3.Resetable,417001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_1_VI3.HH_Fault,417001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_1_VI3.H_Fault,417001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_1_VI3.L_Fault,417001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_1_VI3.LL_Fault,417001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_1_VI3.BL_Fault,417001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_1_VI3.OR_Fault,417001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_1_VI3.UR_Fault,417001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_1_VI3.ROC_Fault,417002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_1_VI3.Tot_EN,417002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_1_VI3.TAGR,417002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_1_VI3.ACKN,417002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_1_VI3.INTK,417002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_1_VI3.PLCFault,417002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI3.PLCIOFault,417002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI3.INTK_EN,417002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_1_VI3.Shelve,417002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_1_VI3.Shelved,417002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_1_VI3.Suppress,417002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_1_VI3.Suppressed,417002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_1_VI3.PCSuppress,417002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_1_VI3.PCUnSuppress,417002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_1_VI3.PCUnshelve,417002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_1_VI4.GlobalReset,417200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_1_VI4.HH_EN,417200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_1_VI4.H_EN,417200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_1_VI4.L_EN,417200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_1_VI4.LL_EN,417200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_1_VI4.BLEN,417200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_1_VI4.OR_EN,417200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_1_VI4.UREN,417200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_1_VI4.RC_EN,417200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_1_VI4.SuppressAA,417200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_1_VI4.SuppressLA,417200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_1_VI4.ConfigError,417200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_1_VI4.HH_Alarm,417200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_1_VI4.H_Alarm,417200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_1_VI4.L_Alarm,417200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_1_VI4.LL_Alarm,417200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_1_VI4.BL_Alarm,417201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_1_VI4.OR_Alarm,417201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_1_VI4.UR_Alarm,417201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_1_VI4.ROC_Alarm,417201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_1_VI4.REST,417201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_1_VI4.ALRM,417201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_1_VI4.ANUN,417201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_1_VI4.AKED,417201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_1_VI4.Resetable,417201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_1_VI4.HH_Fault,417201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_1_VI4.H_Fault,417201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_1_VI4.L_Fault,417201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_1_VI4.LL_Fault,417201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_1_VI4.BL_Fault,417201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_1_VI4.OR_Fault,417201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_1_VI4.UR_Fault,417201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_1_VI4.ROC_Fault,417202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_1_VI4.Tot_EN,417202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_1_VI4.TAGR,417202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_1_VI4.ACKN,417202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_1_VI4.INTK,417202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_1_VI4.PLCFault,417202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI4.PLCIOFault,417202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI4.INTK_EN,417202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_1_VI4.Shelve,417202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_1_VI4.Shelved,417202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_1_VI4.Suppress,417202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_1_VI4.Suppressed,417202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_1_VI4.PCSuppress,417202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_1_VI4.PCUnSuppress,417202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_1_VI4.PCUnshelve,417202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_1_VI5.GlobalReset,417400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_1_VI5.HH_EN,417400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_1_VI5.H_EN,417400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_1_VI5.L_EN,417400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_1_VI5.LL_EN,417400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_1_VI5.BLEN,417400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_1_VI5.OR_EN,417400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_1_VI5.UREN,417400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_1_VI5.RC_EN,417400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_1_VI5.SuppressAA,417400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_1_VI5.SuppressLA,417400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_1_VI5.ConfigError,417400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_1_VI5.HH_Alarm,417400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_1_VI5.H_Alarm,417400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_1_VI5.L_Alarm,417400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_1_VI5.LL_Alarm,417400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_1_VI5.BL_Alarm,417401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_1_VI5.OR_Alarm,417401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_1_VI5.UR_Alarm,417401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_1_VI5.ROC_Alarm,417401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_1_VI5.REST,417401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_1_VI5.ALRM,417401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_1_VI5.ANUN,417401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_1_VI5.AKED,417401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_1_VI5.Resetable,417401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_1_VI5.HH_Fault,417401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_1_VI5.H_Fault,417401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_1_VI5.L_Fault,417401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_1_VI5.LL_Fault,417401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_1_VI5.BL_Fault,417401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_1_VI5.OR_Fault,417401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_1_VI5.UR_Fault,417401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_1_VI5.ROC_Fault,417402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_1_VI5.Tot_EN,417402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_1_VI5.TAGR,417402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_1_VI5.ACKN,417402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_1_VI5.INTK,417402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_1_VI5.PLCFault,417402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI5.PLCIOFault,417402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_1_VI5.INTK_EN,417402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_1_VI5.Shelve,417402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_1_VI5.Shelved,417402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_1_VI5.Suppress,417402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_1_VI5.Suppressed,417402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_1_VI5.PCSuppress,417402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_1_VI5.PCUnSuppress,417402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_1_VI5.PCUnshelve,417402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_2_VI1.GlobalReset,417600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_2_VI1.HH_EN,417600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_2_VI1.H_EN,417600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_2_VI1.L_EN,417600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_2_VI1.LL_EN,417600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_2_VI1.BLEN,417600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_2_VI1.OR_EN,417600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_2_VI1.UREN,417600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_2_VI1.RC_EN,417600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_2_VI1.SuppressAA,417600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_2_VI1.SuppressLA,417600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_2_VI1.ConfigError,417600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_2_VI1.HH_Alarm,417600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_2_VI1.H_Alarm,417600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_2_VI1.L_Alarm,417600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_2_VI1.LL_Alarm,417600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_2_VI1.BL_Alarm,417601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_2_VI1.OR_Alarm,417601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_2_VI1.UR_Alarm,417601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_2_VI1.ROC_Alarm,417601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_2_VI1.REST,417601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_2_VI1.ALRM,417601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_2_VI1.ANUN,417601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_2_VI1.AKED,417601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_2_VI1.Resetable,417601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_2_VI1.HH_Fault,417601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_2_VI1.H_Fault,417601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_2_VI1.L_Fault,417601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_2_VI1.LL_Fault,417601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_2_VI1.BL_Fault,417601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_2_VI1.OR_Fault,417601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_2_VI1.UR_Fault,417601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_2_VI1.ROC_Fault,417602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_2_VI1.Tot_EN,417602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_2_VI1.TAGR,417602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_2_VI1.ACKN,417602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_2_VI1.INTK,417602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_2_VI1.PLCFault,417602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI1.PLCIOFault,417602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI1.INTK_EN,417602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_2_VI1.Shelve,417602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_2_VI1.Shelved,417602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_2_VI1.Suppress,417602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_2_VI1.Suppressed,417602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_2_VI1.PCSuppress,417602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_2_VI1.PCUnSuppress,417602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_2_VI1.PCUnshelve,417602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_2_VI2.GlobalReset,417800.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_2_VI2.HH_EN,417800.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_2_VI2.H_EN,417800.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_2_VI2.L_EN,417800.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_2_VI2.LL_EN,417800.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_2_VI2.BLEN,417800.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_2_VI2.OR_EN,417800.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_2_VI2.UREN,417800.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_2_VI2.RC_EN,417800.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_2_VI2.SuppressAA,417800.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_2_VI2.SuppressLA,417800.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_2_VI2.ConfigError,417800.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_2_VI2.HH_Alarm,417800.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_2_VI2.H_Alarm,417800.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_2_VI2.L_Alarm,417800.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_2_VI2.LL_Alarm,417800.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_2_VI2.BL_Alarm,417801.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_2_VI2.OR_Alarm,417801.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_2_VI2.UR_Alarm,417801.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_2_VI2.ROC_Alarm,417801.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_2_VI2.REST,417801.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_2_VI2.ALRM,417801.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_2_VI2.ANUN,417801.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_2_VI2.AKED,417801.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_2_VI2.Resetable,417801.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_2_VI2.HH_Fault,417801.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_2_VI2.H_Fault,417801.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_2_VI2.L_Fault,417801.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_2_VI2.LL_Fault,417801.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_2_VI2.BL_Fault,417801.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_2_VI2.OR_Fault,417801.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_2_VI2.UR_Fault,417801.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_2_VI2.ROC_Fault,417802.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_2_VI2.Tot_EN,417802.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_2_VI2.TAGR,417802.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_2_VI2.ACKN,417802.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_2_VI2.INTK,417802.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_2_VI2.PLCFault,417802.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI2.PLCIOFault,417802.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI2.INTK_EN,417802.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_2_VI2.Shelve,417802.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_2_VI2.Shelved,417802.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_2_VI2.Suppress,417802.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_2_VI2.Suppressed,417802.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_2_VI2.PCSuppress,417802.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_2_VI2.PCUnSuppress,417802.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_2_VI2.PCUnshelve,417802.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_2_VI3.GlobalReset,418000.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_2_VI3.HH_EN,418000.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_2_VI3.H_EN,418000.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_2_VI3.L_EN,418000.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_2_VI3.LL_EN,418000.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_2_VI3.BLEN,418000.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_2_VI3.OR_EN,418000.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_2_VI3.UREN,418000.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_2_VI3.RC_EN,418000.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_2_VI3.SuppressAA,418000.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_2_VI3.SuppressLA,418000.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_2_VI3.ConfigError,418000.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_2_VI3.HH_Alarm,418000.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_2_VI3.H_Alarm,418000.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_2_VI3.L_Alarm,418000.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_2_VI3.LL_Alarm,418000.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_2_VI3.BL_Alarm,418001.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_2_VI3.OR_Alarm,418001.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_2_VI3.UR_Alarm,418001.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_2_VI3.ROC_Alarm,418001.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_2_VI3.REST,418001.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_2_VI3.ALRM,418001.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_2_VI3.ANUN,418001.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_2_VI3.AKED,418001.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_2_VI3.Resetable,418001.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_2_VI3.HH_Fault,418001.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_2_VI3.H_Fault,418001.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_2_VI3.L_Fault,418001.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_2_VI3.LL_Fault,418001.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_2_VI3.BL_Fault,418001.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_2_VI3.OR_Fault,418001.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_2_VI3.UR_Fault,418001.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_2_VI3.ROC_Fault,418002.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_2_VI3.Tot_EN,418002.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_2_VI3.TAGR,418002.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_2_VI3.ACKN,418002.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_2_VI3.INTK,418002.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_2_VI3.PLCFault,418002.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI3.PLCIOFault,418002.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI3.INTK_EN,418002.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_2_VI3.Shelve,418002.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_2_VI3.Shelved,418002.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_2_VI3.Suppress,418002.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_2_VI3.Suppressed,418002.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_2_VI3.PCSuppress,418002.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_2_VI3.PCUnSuppress,418002.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_2_VI3.PCUnshelve,418002.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_2_VI4.GlobalReset,418200.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_2_VI4.HH_EN,418200.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_2_VI4.H_EN,418200.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_2_VI4.L_EN,418200.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_2_VI4.LL_EN,418200.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_2_VI4.BLEN,418200.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_2_VI4.OR_EN,418200.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_2_VI4.UREN,418200.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_2_VI4.RC_EN,418200.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_2_VI4.SuppressAA,418200.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_2_VI4.SuppressLA,418200.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_2_VI4.ConfigError,418200.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_2_VI4.HH_Alarm,418200.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_2_VI4.H_Alarm,418200.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_2_VI4.L_Alarm,418200.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_2_VI4.LL_Alarm,418200.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_2_VI4.BL_Alarm,418201.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_2_VI4.OR_Alarm,418201.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_2_VI4.UR_Alarm,418201.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_2_VI4.ROC_Alarm,418201.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_2_VI4.REST,418201.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_2_VI4.ALRM,418201.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_2_VI4.ANUN,418201.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_2_VI4.AKED,418201.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_2_VI4.Resetable,418201.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_2_VI4.HH_Fault,418201.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_2_VI4.H_Fault,418201.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_2_VI4.L_Fault,418201.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_2_VI4.LL_Fault,418201.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_2_VI4.BL_Fault,418201.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_2_VI4.OR_Fault,418201.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_2_VI4.UR_Fault,418201.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_2_VI4.ROC_Fault,418202.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_2_VI4.Tot_EN,418202.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_2_VI4.TAGR,418202.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_2_VI4.ACKN,418202.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_2_VI4.INTK,418202.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_2_VI4.PLCFault,418202.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI4.PLCIOFault,418202.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI4.INTK_EN,418202.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_2_VI4.Shelve,418202.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_2_VI4.Shelved,418202.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_2_VI4.Suppress,418202.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_2_VI4.Suppressed,418202.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_2_VI4.PCSuppress,418202.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_2_VI4.PCUnSuppress,418202.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_2_VI4.PCUnshelve,418202.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_2_VI5.GlobalReset,418400.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_2_VI5.HH_EN,418400.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_2_VI5.H_EN,418400.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_2_VI5.L_EN,418400.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_2_VI5.LL_EN,418400.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_2_VI5.BLEN,418400.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_2_VI5.OR_EN,418400.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_2_VI5.UREN,418400.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_2_VI5.RC_EN,418400.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_2_VI5.SuppressAA,418400.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_2_VI5.SuppressLA,418400.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_2_VI5.ConfigError,418400.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_2_VI5.HH_Alarm,418400.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_2_VI5.H_Alarm,418400.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_2_VI5.L_Alarm,418400.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_2_VI5.LL_Alarm,418400.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_2_VI5.BL_Alarm,418401.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_2_VI5.OR_Alarm,418401.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_2_VI5.UR_Alarm,418401.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_2_VI5.ROC_Alarm,418401.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_2_VI5.REST,418401.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_2_VI5.ALRM,418401.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_2_VI5.ANUN,418401.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_2_VI5.AKED,418401.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_2_VI5.Resetable,418401.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_2_VI5.HH_Fault,418401.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_2_VI5.H_Fault,418401.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_2_VI5.L_Fault,418401.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_2_VI5.LL_Fault,418401.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_2_VI5.BL_Fault,418401.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_2_VI5.OR_Fault,418401.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_2_VI5.UR_Fault,418401.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_2_VI5.ROC_Fault,418402.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_2_VI5.Tot_EN,418402.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_2_VI5.TAGR,418402.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_2_VI5.ACKN,418402.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_2_VI5.INTK,418402.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_2_VI5.PLCFault,418402.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI5.PLCIOFault,418402.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_2_VI5.INTK_EN,418402.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_2_VI5.Shelve,418402.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_2_VI5.Shelved,418402.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_2_VI5.Suppress,418402.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_2_VI5.Suppressed,418402.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_2_VI5.PCSuppress,418402.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_2_VI5.PCUnSuppress,418402.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_2_VI5.PCUnshelve,418402.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_3_VI1.GlobalReset,418600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_3_VI1.HH_EN,418600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_3_VI1.H_EN,418600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_3_VI1.L_EN,418600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_3_VI1.LL_EN,418600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_3_VI1.BLEN,418600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_3_VI1.OR_EN,418600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_3_VI1.UREN,418600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_3_VI1.RC_EN,418600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_3_VI1.SuppressAA,418600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_3_VI1.SuppressLA,418600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_3_VI1.ConfigError,418600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_3_VI1.HH_Alarm,418600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_3_VI1.H_Alarm,418600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_3_VI1.L_Alarm,418600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_3_VI1.LL_Alarm,418600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_3_VI1.BL_Alarm,418601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_3_VI1.OR_Alarm,418601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_3_VI1.UR_Alarm,418601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_3_VI1.ROC_Alarm,418601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_3_VI1.REST,418601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_3_VI1.ALRM,418601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_3_VI1.ANUN,418601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_3_VI1.AKED,418601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_3_VI1.Resetable,418601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_3_VI1.HH_Fault,418601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_3_VI1.H_Fault,418601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_3_VI1.L_Fault,418601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_3_VI1.LL_Fault,418601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_3_VI1.BL_Fault,418601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_3_VI1.OR_Fault,418601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_3_VI1.UR_Fault,418601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_3_VI1.ROC_Fault,418602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_3_VI1.Tot_EN,418602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_3_VI1.TAGR,418602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_3_VI1.ACKN,418602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_3_VI1.INTK,418602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_3_VI1.PLCFault,418602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI1.PLCIOFault,418602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI1.INTK_EN,418602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_3_VI1.Shelve,418602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_3_VI1.Shelved,418602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_3_VI1.Suppress,418602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_3_VI1.Suppressed,418602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_3_VI1.PCSuppress,418602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_3_VI1.PCUnSuppress,418602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_3_VI1.PCUnshelve,418602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_3_VI2.GlobalReset,418800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_3_VI2.HH_EN,418800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_3_VI2.H_EN,418800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_3_VI2.L_EN,418800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_3_VI2.LL_EN,418800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_3_VI2.BLEN,418800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_3_VI2.OR_EN,418800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_3_VI2.UREN,418800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_3_VI2.RC_EN,418800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_3_VI2.SuppressAA,418800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_3_VI2.SuppressLA,418800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_3_VI2.ConfigError,418800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_3_VI2.HH_Alarm,418800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_3_VI2.H_Alarm,418800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_3_VI2.L_Alarm,418800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_3_VI2.LL_Alarm,418800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_3_VI2.BL_Alarm,418801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_3_VI2.OR_Alarm,418801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_3_VI2.UR_Alarm,418801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_3_VI2.ROC_Alarm,418801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_3_VI2.REST,418801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_3_VI2.ALRM,418801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_3_VI2.ANUN,418801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_3_VI2.AKED,418801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_3_VI2.Resetable,418801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_3_VI2.HH_Fault,418801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_3_VI2.H_Fault,418801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_3_VI2.L_Fault,418801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_3_VI2.LL_Fault,418801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_3_VI2.BL_Fault,418801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_3_VI2.OR_Fault,418801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_3_VI2.UR_Fault,418801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_3_VI2.ROC_Fault,418802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_3_VI2.Tot_EN,418802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_3_VI2.TAGR,418802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_3_VI2.ACKN,418802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_3_VI2.INTK,418802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_3_VI2.PLCFault,418802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI2.PLCIOFault,418802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI2.INTK_EN,418802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_3_VI2.Shelve,418802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_3_VI2.Shelved,418802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_3_VI2.Suppress,418802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_3_VI2.Suppressed,418802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_3_VI2.PCSuppress,418802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_3_VI2.PCUnSuppress,418802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_3_VI2.PCUnshelve,418802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_3_VI3.GlobalReset,419000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_3_VI3.HH_EN,419000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_3_VI3.H_EN,419000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_3_VI3.L_EN,419000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_3_VI3.LL_EN,419000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_3_VI3.BLEN,419000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_3_VI3.OR_EN,419000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_3_VI3.UREN,419000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_3_VI3.RC_EN,419000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_3_VI3.SuppressAA,419000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_3_VI3.SuppressLA,419000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_3_VI3.ConfigError,419000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_3_VI3.HH_Alarm,419000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_3_VI3.H_Alarm,419000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_3_VI3.L_Alarm,419000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_3_VI3.LL_Alarm,419000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_3_VI3.BL_Alarm,419001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_3_VI3.OR_Alarm,419001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_3_VI3.UR_Alarm,419001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_3_VI3.ROC_Alarm,419001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_3_VI3.REST,419001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_3_VI3.ALRM,419001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_3_VI3.ANUN,419001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_3_VI3.AKED,419001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_3_VI3.Resetable,419001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_3_VI3.HH_Fault,419001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_3_VI3.H_Fault,419001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_3_VI3.L_Fault,419001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_3_VI3.LL_Fault,419001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_3_VI3.BL_Fault,419001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_3_VI3.OR_Fault,419001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_3_VI3.UR_Fault,419001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_3_VI3.ROC_Fault,419002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_3_VI3.Tot_EN,419002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_3_VI3.TAGR,419002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_3_VI3.ACKN,419002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_3_VI3.INTK,419002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_3_VI3.PLCFault,419002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI3.PLCIOFault,419002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI3.INTK_EN,419002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_3_VI3.Shelve,419002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_3_VI3.Shelved,419002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_3_VI3.Suppress,419002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_3_VI3.Suppressed,419002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_3_VI3.PCSuppress,419002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_3_VI3.PCUnSuppress,419002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_3_VI3.PCUnshelve,419002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_3_VI4.GlobalReset,419200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_3_VI4.HH_EN,419200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_3_VI4.H_EN,419200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_3_VI4.L_EN,419200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_3_VI4.LL_EN,419200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_3_VI4.BLEN,419200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_3_VI4.OR_EN,419200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_3_VI4.UREN,419200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_3_VI4.RC_EN,419200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_3_VI4.SuppressAA,419200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_3_VI4.SuppressLA,419200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_3_VI4.ConfigError,419200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_3_VI4.HH_Alarm,419200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_3_VI4.H_Alarm,419200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_3_VI4.L_Alarm,419200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_3_VI4.LL_Alarm,419200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_3_VI4.BL_Alarm,419201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_3_VI4.OR_Alarm,419201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_3_VI4.UR_Alarm,419201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_3_VI4.ROC_Alarm,419201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_3_VI4.REST,419201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_3_VI4.ALRM,419201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_3_VI4.ANUN,419201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_3_VI4.AKED,419201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_3_VI4.Resetable,419201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_3_VI4.HH_Fault,419201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_3_VI4.H_Fault,419201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_3_VI4.L_Fault,419201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_3_VI4.LL_Fault,419201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_3_VI4.BL_Fault,419201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_3_VI4.OR_Fault,419201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_3_VI4.UR_Fault,419201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_3_VI4.ROC_Fault,419202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_3_VI4.Tot_EN,419202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_3_VI4.TAGR,419202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_3_VI4.ACKN,419202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_3_VI4.INTK,419202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_3_VI4.PLCFault,419202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI4.PLCIOFault,419202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI4.INTK_EN,419202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_3_VI4.Shelve,419202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_3_VI4.Shelved,419202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_3_VI4.Suppress,419202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_3_VI4.Suppressed,419202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_3_VI4.PCSuppress,419202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_3_VI4.PCUnSuppress,419202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_3_VI4.PCUnshelve,419202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_3_VI5.GlobalReset,419400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_3_VI5.HH_EN,419400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_3_VI5.H_EN,419400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_3_VI5.L_EN,419400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_3_VI5.LL_EN,419400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_3_VI5.BLEN,419400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_3_VI5.OR_EN,419400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_3_VI5.UREN,419400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_3_VI5.RC_EN,419400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_3_VI5.SuppressAA,419400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_3_VI5.SuppressLA,419400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_3_VI5.ConfigError,419400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_3_VI5.HH_Alarm,419400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_3_VI5.H_Alarm,419400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_3_VI5.L_Alarm,419400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_3_VI5.LL_Alarm,419400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_3_VI5.BL_Alarm,419401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_3_VI5.OR_Alarm,419401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_3_VI5.UR_Alarm,419401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_3_VI5.ROC_Alarm,419401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_3_VI5.REST,419401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_3_VI5.ALRM,419401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_3_VI5.ANUN,419401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_3_VI5.AKED,419401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_3_VI5.Resetable,419401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_3_VI5.HH_Fault,419401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_3_VI5.H_Fault,419401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_3_VI5.L_Fault,419401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_3_VI5.LL_Fault,419401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_3_VI5.BL_Fault,419401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_3_VI5.OR_Fault,419401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_3_VI5.UR_Fault,419401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_3_VI5.ROC_Fault,419402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_3_VI5.Tot_EN,419402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_3_VI5.TAGR,419402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_3_VI5.ACKN,419402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_3_VI5.INTK,419402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_3_VI5.PLCFault,419402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI5.PLCIOFault,419402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_3_VI5.INTK_EN,419402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_3_VI5.Shelve,419402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_3_VI5.Shelved,419402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_3_VI5.Suppress,419402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_3_VI5.Suppressed,419402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_3_VI5.PCSuppress,419402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_3_VI5.PCUnSuppress,419402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_3_VI5.PCUnshelve,419402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_4_VI1.GlobalReset,419600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_4_VI1.HH_EN,419600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_4_VI1.H_EN,419600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_4_VI1.L_EN,419600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_4_VI1.LL_EN,419600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_4_VI1.BLEN,419600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_4_VI1.OR_EN,419600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_4_VI1.UREN,419600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_4_VI1.RC_EN,419600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_4_VI1.SuppressAA,419600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_4_VI1.SuppressLA,419600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_4_VI1.ConfigError,419600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_4_VI1.HH_Alarm,419600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_4_VI1.H_Alarm,419600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_4_VI1.L_Alarm,419600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_4_VI1.LL_Alarm,419600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_4_VI1.BL_Alarm,419601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_4_VI1.OR_Alarm,419601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_4_VI1.UR_Alarm,419601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_4_VI1.ROC_Alarm,419601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_4_VI1.REST,419601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_4_VI1.ALRM,419601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_4_VI1.ANUN,419601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_4_VI1.AKED,419601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_4_VI1.Resetable,419601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_4_VI1.HH_Fault,419601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_4_VI1.H_Fault,419601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_4_VI1.L_Fault,419601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_4_VI1.LL_Fault,419601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_4_VI1.BL_Fault,419601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_4_VI1.OR_Fault,419601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_4_VI1.UR_Fault,419601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_4_VI1.ROC_Fault,419602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_4_VI1.Tot_EN,419602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_4_VI1.TAGR,419602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_4_VI1.ACKN,419602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_4_VI1.INTK,419602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_4_VI1.PLCFault,419602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI1.PLCIOFault,419602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI1.INTK_EN,419602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_4_VI1.Shelve,419602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_4_VI1.Shelved,419602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_4_VI1.Suppress,419602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_4_VI1.Suppressed,419602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_4_VI1.PCSuppress,419602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_4_VI1.PCUnSuppress,419602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_4_VI1.PCUnshelve,419602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_4_VI2.GlobalReset,419800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_4_VI2.HH_EN,419800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_4_VI2.H_EN,419800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_4_VI2.L_EN,419800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_4_VI2.LL_EN,419800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_4_VI2.BLEN,419800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_4_VI2.OR_EN,419800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_4_VI2.UREN,419800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_4_VI2.RC_EN,419800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_4_VI2.SuppressAA,419800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_4_VI2.SuppressLA,419800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_4_VI2.ConfigError,419800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_4_VI2.HH_Alarm,419800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_4_VI2.H_Alarm,419800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_4_VI2.L_Alarm,419800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_4_VI2.LL_Alarm,419800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_4_VI2.BL_Alarm,419801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_4_VI2.OR_Alarm,419801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_4_VI2.UR_Alarm,419801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_4_VI2.ROC_Alarm,419801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_4_VI2.REST,419801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_4_VI2.ALRM,419801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_4_VI2.ANUN,419801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_4_VI2.AKED,419801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_4_VI2.Resetable,419801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_4_VI2.HH_Fault,419801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_4_VI2.H_Fault,419801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_4_VI2.L_Fault,419801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_4_VI2.LL_Fault,419801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_4_VI2.BL_Fault,419801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_4_VI2.OR_Fault,419801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_4_VI2.UR_Fault,419801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_4_VI2.ROC_Fault,419802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_4_VI2.Tot_EN,419802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_4_VI2.TAGR,419802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_4_VI2.ACKN,419802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_4_VI2.INTK,419802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_4_VI2.PLCFault,419802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI2.PLCIOFault,419802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI2.INTK_EN,419802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_4_VI2.Shelve,419802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_4_VI2.Shelved,419802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_4_VI2.Suppress,419802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_4_VI2.Suppressed,419802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_4_VI2.PCSuppress,419802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_4_VI2.PCUnSuppress,419802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_4_VI2.PCUnshelve,419802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_4_VI3.GlobalReset,420000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_4_VI3.HH_EN,420000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_4_VI3.H_EN,420000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_4_VI3.L_EN,420000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_4_VI3.LL_EN,420000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_4_VI3.BLEN,420000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_4_VI3.OR_EN,420000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_4_VI3.UREN,420000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_4_VI3.RC_EN,420000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_4_VI3.SuppressAA,420000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_4_VI3.SuppressLA,420000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_4_VI3.ConfigError,420000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_4_VI3.HH_Alarm,420000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_4_VI3.H_Alarm,420000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_4_VI3.L_Alarm,420000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_4_VI3.LL_Alarm,420000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_4_VI3.BL_Alarm,420001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_4_VI3.OR_Alarm,420001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_4_VI3.UR_Alarm,420001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_4_VI3.ROC_Alarm,420001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_4_VI3.REST,420001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_4_VI3.ALRM,420001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_4_VI3.ANUN,420001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_4_VI3.AKED,420001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_4_VI3.Resetable,420001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_4_VI3.HH_Fault,420001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_4_VI3.H_Fault,420001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_4_VI3.L_Fault,420001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_4_VI3.LL_Fault,420001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_4_VI3.BL_Fault,420001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_4_VI3.OR_Fault,420001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_4_VI3.UR_Fault,420001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_4_VI3.ROC_Fault,420002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_4_VI3.Tot_EN,420002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_4_VI3.TAGR,420002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_4_VI3.ACKN,420002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_4_VI3.INTK,420002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_4_VI3.PLCFault,420002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI3.PLCIOFault,420002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI3.INTK_EN,420002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_4_VI3.Shelve,420002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_4_VI3.Shelved,420002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_4_VI3.Suppress,420002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_4_VI3.Suppressed,420002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_4_VI3.PCSuppress,420002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_4_VI3.PCUnSuppress,420002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_4_VI3.PCUnshelve,420002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_4_VI4.GlobalReset,420200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_4_VI4.HH_EN,420200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_4_VI4.H_EN,420200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_4_VI4.L_EN,420200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_4_VI4.LL_EN,420200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_4_VI4.BLEN,420200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_4_VI4.OR_EN,420200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_4_VI4.UREN,420200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_4_VI4.RC_EN,420200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_4_VI4.SuppressAA,420200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_4_VI4.SuppressLA,420200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_4_VI4.ConfigError,420200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_4_VI4.HH_Alarm,420200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_4_VI4.H_Alarm,420200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_4_VI4.L_Alarm,420200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_4_VI4.LL_Alarm,420200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_4_VI4.BL_Alarm,420201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_4_VI4.OR_Alarm,420201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_4_VI4.UR_Alarm,420201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_4_VI4.ROC_Alarm,420201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_4_VI4.REST,420201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_4_VI4.ALRM,420201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_4_VI4.ANUN,420201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_4_VI4.AKED,420201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_4_VI4.Resetable,420201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_4_VI4.HH_Fault,420201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_4_VI4.H_Fault,420201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_4_VI4.L_Fault,420201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_4_VI4.LL_Fault,420201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_4_VI4.BL_Fault,420201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_4_VI4.OR_Fault,420201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_4_VI4.UR_Fault,420201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_4_VI4.ROC_Fault,420202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_4_VI4.Tot_EN,420202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_4_VI4.TAGR,420202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_4_VI4.ACKN,420202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_4_VI4.INTK,420202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_4_VI4.PLCFault,420202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI4.PLCIOFault,420202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI4.INTK_EN,420202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_4_VI4.Shelve,420202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_4_VI4.Shelved,420202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_4_VI4.Suppress,420202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_4_VI4.Suppressed,420202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_4_VI4.PCSuppress,420202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_4_VI4.PCUnSuppress,420202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_4_VI4.PCUnshelve,420202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_4_VI5.GlobalReset,420400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_4_VI5.HH_EN,420400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_4_VI5.H_EN,420400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_4_VI5.L_EN,420400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_4_VI5.LL_EN,420400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_4_VI5.BLEN,420400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_4_VI5.OR_EN,420400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_4_VI5.UREN,420400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_4_VI5.RC_EN,420400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_4_VI5.SuppressAA,420400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_4_VI5.SuppressLA,420400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_4_VI5.ConfigError,420400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_4_VI5.HH_Alarm,420400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_4_VI5.H_Alarm,420400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_4_VI5.L_Alarm,420400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_4_VI5.LL_Alarm,420400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_4_VI5.BL_Alarm,420401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_4_VI5.OR_Alarm,420401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_4_VI5.UR_Alarm,420401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_4_VI5.ROC_Alarm,420401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_4_VI5.REST,420401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_4_VI5.ALRM,420401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_4_VI5.ANUN,420401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_4_VI5.AKED,420401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_4_VI5.Resetable,420401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_4_VI5.HH_Fault,420401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_4_VI5.H_Fault,420401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_4_VI5.L_Fault,420401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_4_VI5.LL_Fault,420401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_4_VI5.BL_Fault,420401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_4_VI5.OR_Fault,420401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_4_VI5.UR_Fault,420401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_4_VI5.ROC_Fault,420402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_4_VI5.Tot_EN,420402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_4_VI5.TAGR,420402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_4_VI5.ACKN,420402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_4_VI5.INTK,420402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_4_VI5.PLCFault,420402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI5.PLCIOFault,420402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_4_VI5.INTK_EN,420402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_4_VI5.Shelve,420402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_4_VI5.Shelved,420402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_4_VI5.Suppress,420402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_4_VI5.Suppressed,420402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_4_VI5.PCSuppress,420402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_4_VI5.PCUnSuppress,420402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_4_VI5.PCUnshelve,420402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_5_VI1.GlobalReset,420600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_5_VI1.HH_EN,420600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_5_VI1.H_EN,420600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_5_VI1.L_EN,420600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_5_VI1.LL_EN,420600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_5_VI1.BLEN,420600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_5_VI1.OR_EN,420600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_5_VI1.UREN,420600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_5_VI1.RC_EN,420600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_5_VI1.SuppressAA,420600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_5_VI1.SuppressLA,420600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_5_VI1.ConfigError,420600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_5_VI1.HH_Alarm,420600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_5_VI1.H_Alarm,420600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_5_VI1.L_Alarm,420600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_5_VI1.LL_Alarm,420600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_5_VI1.BL_Alarm,420601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_5_VI1.OR_Alarm,420601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_5_VI1.UR_Alarm,420601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_5_VI1.ROC_Alarm,420601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_5_VI1.REST,420601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_5_VI1.ALRM,420601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_5_VI1.ANUN,420601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_5_VI1.AKED,420601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_5_VI1.Resetable,420601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_5_VI1.HH_Fault,420601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_5_VI1.H_Fault,420601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_5_VI1.L_Fault,420601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_5_VI1.LL_Fault,420601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_5_VI1.BL_Fault,420601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_5_VI1.OR_Fault,420601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_5_VI1.UR_Fault,420601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_5_VI1.ROC_Fault,420602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_5_VI1.Tot_EN,420602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_5_VI1.TAGR,420602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_5_VI1.ACKN,420602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_5_VI1.INTK,420602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_5_VI1.PLCFault,420602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI1.PLCIOFault,420602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI1.INTK_EN,420602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_5_VI1.Shelve,420602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_5_VI1.Shelved,420602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_5_VI1.Suppress,420602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_5_VI1.Suppressed,420602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_5_VI1.PCSuppress,420602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_5_VI1.PCUnSuppress,420602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_5_VI1.PCUnshelve,420602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_5_VI2.GlobalReset,420800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_5_VI2.HH_EN,420800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_5_VI2.H_EN,420800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_5_VI2.L_EN,420800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_5_VI2.LL_EN,420800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_5_VI2.BLEN,420800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_5_VI2.OR_EN,420800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_5_VI2.UREN,420800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_5_VI2.RC_EN,420800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_5_VI2.SuppressAA,420800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_5_VI2.SuppressLA,420800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_5_VI2.ConfigError,420800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_5_VI2.HH_Alarm,420800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_5_VI2.H_Alarm,420800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_5_VI2.L_Alarm,420800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_5_VI2.LL_Alarm,420800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_5_VI2.BL_Alarm,420801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_5_VI2.OR_Alarm,420801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_5_VI2.UR_Alarm,420801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_5_VI2.ROC_Alarm,420801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_5_VI2.REST,420801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_5_VI2.ALRM,420801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_5_VI2.ANUN,420801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_5_VI2.AKED,420801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_5_VI2.Resetable,420801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_5_VI2.HH_Fault,420801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_5_VI2.H_Fault,420801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_5_VI2.L_Fault,420801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_5_VI2.LL_Fault,420801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_5_VI2.BL_Fault,420801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_5_VI2.OR_Fault,420801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_5_VI2.UR_Fault,420801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_5_VI2.ROC_Fault,420802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_5_VI2.Tot_EN,420802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_5_VI2.TAGR,420802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_5_VI2.ACKN,420802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_5_VI2.INTK,420802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_5_VI2.PLCFault,420802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI2.PLCIOFault,420802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI2.INTK_EN,420802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_5_VI2.Shelve,420802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_5_VI2.Shelved,420802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_5_VI2.Suppress,420802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_5_VI2.Suppressed,420802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_5_VI2.PCSuppress,420802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_5_VI2.PCUnSuppress,420802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_5_VI2.PCUnshelve,420802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_5_VI3.GlobalReset,421000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_5_VI3.HH_EN,421000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_5_VI3.H_EN,421000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_5_VI3.L_EN,421000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_5_VI3.LL_EN,421000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_5_VI3.BLEN,421000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_5_VI3.OR_EN,421000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_5_VI3.UREN,421000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_5_VI3.RC_EN,421000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_5_VI3.SuppressAA,421000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_5_VI3.SuppressLA,421000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_5_VI3.ConfigError,421000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_5_VI3.HH_Alarm,421000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_5_VI3.H_Alarm,421000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_5_VI3.L_Alarm,421000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_5_VI3.LL_Alarm,421000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_5_VI3.BL_Alarm,421001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_5_VI3.OR_Alarm,421001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_5_VI3.UR_Alarm,421001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_5_VI3.ROC_Alarm,421001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_5_VI3.REST,421001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_5_VI3.ALRM,421001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_5_VI3.ANUN,421001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_5_VI3.AKED,421001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_5_VI3.Resetable,421001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_5_VI3.HH_Fault,421001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_5_VI3.H_Fault,421001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_5_VI3.L_Fault,421001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_5_VI3.LL_Fault,421001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_5_VI3.BL_Fault,421001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_5_VI3.OR_Fault,421001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_5_VI3.UR_Fault,421001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_5_VI3.ROC_Fault,421002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_5_VI3.Tot_EN,421002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_5_VI3.TAGR,421002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_5_VI3.ACKN,421002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_5_VI3.INTK,421002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_5_VI3.PLCFault,421002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI3.PLCIOFault,421002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI3.INTK_EN,421002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_5_VI3.Shelve,421002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_5_VI3.Shelved,421002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_5_VI3.Suppress,421002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_5_VI3.Suppressed,421002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_5_VI3.PCSuppress,421002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_5_VI3.PCUnSuppress,421002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_5_VI3.PCUnshelve,421002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_5_VI4.GlobalReset,421200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_5_VI4.HH_EN,421200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_5_VI4.H_EN,421200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_5_VI4.L_EN,421200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_5_VI4.LL_EN,421200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_5_VI4.BLEN,421200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_5_VI4.OR_EN,421200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_5_VI4.UREN,421200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_5_VI4.RC_EN,421200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_5_VI4.SuppressAA,421200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_5_VI4.SuppressLA,421200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_5_VI4.ConfigError,421200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_5_VI4.HH_Alarm,421200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_5_VI4.H_Alarm,421200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_5_VI4.L_Alarm,421200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_5_VI4.LL_Alarm,421200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_5_VI4.BL_Alarm,421201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_5_VI4.OR_Alarm,421201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_5_VI4.UR_Alarm,421201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_5_VI4.ROC_Alarm,421201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_5_VI4.REST,421201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_5_VI4.ALRM,421201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_5_VI4.ANUN,421201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_5_VI4.AKED,421201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_5_VI4.Resetable,421201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_5_VI4.HH_Fault,421201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_5_VI4.H_Fault,421201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_5_VI4.L_Fault,421201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_5_VI4.LL_Fault,421201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_5_VI4.BL_Fault,421201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_5_VI4.OR_Fault,421201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_5_VI4.UR_Fault,421201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_5_VI4.ROC_Fault,421202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_5_VI4.Tot_EN,421202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_5_VI4.TAGR,421202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_5_VI4.ACKN,421202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_5_VI4.INTK,421202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_5_VI4.PLCFault,421202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI4.PLCIOFault,421202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI4.INTK_EN,421202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_5_VI4.Shelve,421202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_5_VI4.Shelved,421202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_5_VI4.Suppress,421202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_5_VI4.Suppressed,421202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_5_VI4.PCSuppress,421202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_5_VI4.PCUnSuppress,421202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_5_VI4.PCUnshelve,421202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_5_VI5.GlobalReset,421400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_5_VI5.HH_EN,421400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_5_VI5.H_EN,421400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_5_VI5.L_EN,421400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_5_VI5.LL_EN,421400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_5_VI5.BLEN,421400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_5_VI5.OR_EN,421400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_5_VI5.UREN,421400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_5_VI5.RC_EN,421400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_5_VI5.SuppressAA,421400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_5_VI5.SuppressLA,421400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_5_VI5.ConfigError,421400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_5_VI5.HH_Alarm,421400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_5_VI5.H_Alarm,421400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_5_VI5.L_Alarm,421400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_5_VI5.LL_Alarm,421400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_5_VI5.BL_Alarm,421401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_5_VI5.OR_Alarm,421401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_5_VI5.UR_Alarm,421401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_5_VI5.ROC_Alarm,421401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_5_VI5.REST,421401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_5_VI5.ALRM,421401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_5_VI5.ANUN,421401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_5_VI5.AKED,421401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_5_VI5.Resetable,421401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_5_VI5.HH_Fault,421401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_5_VI5.H_Fault,421401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_5_VI5.L_Fault,421401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_5_VI5.LL_Fault,421401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_5_VI5.BL_Fault,421401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_5_VI5.OR_Fault,421401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_5_VI5.UR_Fault,421401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_5_VI5.ROC_Fault,421402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_5_VI5.Tot_EN,421402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_5_VI5.TAGR,421402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_5_VI5.ACKN,421402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_5_VI5.INTK,421402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_5_VI5.PLCFault,421402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI5.PLCIOFault,421402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_5_VI5.INTK_EN,421402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_5_VI5.Shelve,421402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_5_VI5.Shelved,421402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_5_VI5.Suppress,421402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_5_VI5.Suppressed,421402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_5_VI5.PCSuppress,421402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_5_VI5.PCUnSuppress,421402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_5_VI5.PCUnshelve,421402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_6_VI1.GlobalReset,421600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_6_VI1.HH_EN,421600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_6_VI1.H_EN,421600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_6_VI1.L_EN,421600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_6_VI1.LL_EN,421600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_6_VI1.BLEN,421600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_6_VI1.OR_EN,421600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_6_VI1.UREN,421600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_6_VI1.RC_EN,421600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_6_VI1.SuppressAA,421600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_6_VI1.SuppressLA,421600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_6_VI1.ConfigError,421600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_6_VI1.HH_Alarm,421600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_6_VI1.H_Alarm,421600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_6_VI1.L_Alarm,421600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_6_VI1.LL_Alarm,421600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_6_VI1.BL_Alarm,421601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_6_VI1.OR_Alarm,421601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_6_VI1.UR_Alarm,421601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_6_VI1.ROC_Alarm,421601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_6_VI1.REST,421601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_6_VI1.ALRM,421601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_6_VI1.ANUN,421601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_6_VI1.AKED,421601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_6_VI1.Resetable,421601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_6_VI1.HH_Fault,421601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_6_VI1.H_Fault,421601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_6_VI1.L_Fault,421601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_6_VI1.LL_Fault,421601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_6_VI1.BL_Fault,421601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_6_VI1.OR_Fault,421601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_6_VI1.UR_Fault,421601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_6_VI1.ROC_Fault,421602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_6_VI1.Tot_EN,421602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_6_VI1.TAGR,421602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_6_VI1.ACKN,421602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_6_VI1.INTK,421602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_6_VI1.PLCFault,421602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI1.PLCIOFault,421602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI1.INTK_EN,421602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_6_VI1.Shelve,421602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_6_VI1.Shelved,421602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_6_VI1.Suppress,421602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_6_VI1.Suppressed,421602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_6_VI1.PCSuppress,421602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_6_VI1.PCUnSuppress,421602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_6_VI1.PCUnshelve,421602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_6_VI2.GlobalReset,421800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_6_VI2.HH_EN,421800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_6_VI2.H_EN,421800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_6_VI2.L_EN,421800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_6_VI2.LL_EN,421800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_6_VI2.BLEN,421800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_6_VI2.OR_EN,421800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_6_VI2.UREN,421800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_6_VI2.RC_EN,421800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_6_VI2.SuppressAA,421800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_6_VI2.SuppressLA,421800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_6_VI2.ConfigError,421800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_6_VI2.HH_Alarm,421800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_6_VI2.H_Alarm,421800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_6_VI2.L_Alarm,421800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_6_VI2.LL_Alarm,421800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_6_VI2.BL_Alarm,421801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_6_VI2.OR_Alarm,421801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_6_VI2.UR_Alarm,421801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_6_VI2.ROC_Alarm,421801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_6_VI2.REST,421801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_6_VI2.ALRM,421801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_6_VI2.ANUN,421801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_6_VI2.AKED,421801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_6_VI2.Resetable,421801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_6_VI2.HH_Fault,421801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_6_VI2.H_Fault,421801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_6_VI2.L_Fault,421801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_6_VI2.LL_Fault,421801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_6_VI2.BL_Fault,421801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_6_VI2.OR_Fault,421801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_6_VI2.UR_Fault,421801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_6_VI2.ROC_Fault,421802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_6_VI2.Tot_EN,421802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_6_VI2.TAGR,421802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_6_VI2.ACKN,421802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_6_VI2.INTK,421802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_6_VI2.PLCFault,421802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI2.PLCIOFault,421802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI2.INTK_EN,421802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_6_VI2.Shelve,421802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_6_VI2.Shelved,421802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_6_VI2.Suppress,421802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_6_VI2.Suppressed,421802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_6_VI2.PCSuppress,421802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_6_VI2.PCUnSuppress,421802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_6_VI2.PCUnshelve,421802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_6_VI3.GlobalReset,422000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_6_VI3.HH_EN,422000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_6_VI3.H_EN,422000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_6_VI3.L_EN,422000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_6_VI3.LL_EN,422000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_6_VI3.BLEN,422000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_6_VI3.OR_EN,422000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_6_VI3.UREN,422000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_6_VI3.RC_EN,422000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_6_VI3.SuppressAA,422000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_6_VI3.SuppressLA,422000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_6_VI3.ConfigError,422000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_6_VI3.HH_Alarm,422000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_6_VI3.H_Alarm,422000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_6_VI3.L_Alarm,422000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_6_VI3.LL_Alarm,422000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_6_VI3.BL_Alarm,422001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_6_VI3.OR_Alarm,422001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_6_VI3.UR_Alarm,422001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_6_VI3.ROC_Alarm,422001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_6_VI3.REST,422001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_6_VI3.ALRM,422001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_6_VI3.ANUN,422001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_6_VI3.AKED,422001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_6_VI3.Resetable,422001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_6_VI3.HH_Fault,422001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_6_VI3.H_Fault,422001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_6_VI3.L_Fault,422001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_6_VI3.LL_Fault,422001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_6_VI3.BL_Fault,422001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_6_VI3.OR_Fault,422001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_6_VI3.UR_Fault,422001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_6_VI3.ROC_Fault,422002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_6_VI3.Tot_EN,422002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_6_VI3.TAGR,422002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_6_VI3.ACKN,422002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_6_VI3.INTK,422002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_6_VI3.PLCFault,422002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI3.PLCIOFault,422002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI3.INTK_EN,422002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_6_VI3.Shelve,422002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_6_VI3.Shelved,422002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_6_VI3.Suppress,422002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_6_VI3.Suppressed,422002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_6_VI3.PCSuppress,422002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_6_VI3.PCUnSuppress,422002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_6_VI3.PCUnshelve,422002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_6_VI4.GlobalReset,422200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_6_VI4.HH_EN,422200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_6_VI4.H_EN,422200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_6_VI4.L_EN,422200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_6_VI4.LL_EN,422200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_6_VI4.BLEN,422200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_6_VI4.OR_EN,422200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_6_VI4.UREN,422200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_6_VI4.RC_EN,422200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_6_VI4.SuppressAA,422200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_6_VI4.SuppressLA,422200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_6_VI4.ConfigError,422200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_6_VI4.HH_Alarm,422200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_6_VI4.H_Alarm,422200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_6_VI4.L_Alarm,422200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_6_VI4.LL_Alarm,422200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_6_VI4.BL_Alarm,422201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_6_VI4.OR_Alarm,422201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_6_VI4.UR_Alarm,422201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_6_VI4.ROC_Alarm,422201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_6_VI4.REST,422201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_6_VI4.ALRM,422201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_6_VI4.ANUN,422201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_6_VI4.AKED,422201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_6_VI4.Resetable,422201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_6_VI4.HH_Fault,422201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_6_VI4.H_Fault,422201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_6_VI4.L_Fault,422201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_6_VI4.LL_Fault,422201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_6_VI4.BL_Fault,422201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_6_VI4.OR_Fault,422201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_6_VI4.UR_Fault,422201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_6_VI4.ROC_Fault,422202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_6_VI4.Tot_EN,422202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_6_VI4.TAGR,422202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_6_VI4.ACKN,422202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_6_VI4.INTK,422202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_6_VI4.PLCFault,422202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI4.PLCIOFault,422202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI4.INTK_EN,422202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_6_VI4.Shelve,422202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_6_VI4.Shelved,422202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_6_VI4.Suppress,422202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_6_VI4.Suppressed,422202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_6_VI4.PCSuppress,422202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_6_VI4.PCUnSuppress,422202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_6_VI4.PCUnshelve,422202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_6_VI5.GlobalReset,422400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_6_VI5.HH_EN,422400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_6_VI5.H_EN,422400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_6_VI5.L_EN,422400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_6_VI5.LL_EN,422400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_6_VI5.BLEN,422400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_6_VI5.OR_EN,422400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_6_VI5.UREN,422400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_6_VI5.RC_EN,422400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_6_VI5.SuppressAA,422400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_6_VI5.SuppressLA,422400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_6_VI5.ConfigError,422400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_6_VI5.HH_Alarm,422400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_6_VI5.H_Alarm,422400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_6_VI5.L_Alarm,422400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_6_VI5.LL_Alarm,422400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_6_VI5.BL_Alarm,422401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_6_VI5.OR_Alarm,422401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_6_VI5.UR_Alarm,422401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_6_VI5.ROC_Alarm,422401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_6_VI5.REST,422401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_6_VI5.ALRM,422401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_6_VI5.ANUN,422401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_6_VI5.AKED,422401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_6_VI5.Resetable,422401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_6_VI5.HH_Fault,422401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_6_VI5.H_Fault,422401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_6_VI5.L_Fault,422401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_6_VI5.LL_Fault,422401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_6_VI5.BL_Fault,422401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_6_VI5.OR_Fault,422401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_6_VI5.UR_Fault,422401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_6_VI5.ROC_Fault,422402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_6_VI5.Tot_EN,422402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_6_VI5.TAGR,422402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_6_VI5.ACKN,422402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_6_VI5.INTK,422402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_6_VI5.PLCFault,422402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI5.PLCIOFault,422402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_6_VI5.INTK_EN,422402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_6_VI5.Shelve,422402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_6_VI5.Shelved,422402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_6_VI5.Suppress,422402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_6_VI5.Suppressed,422402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_6_VI5.PCSuppress,422402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_6_VI5.PCUnSuppress,422402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_6_VI5.PCUnshelve,422402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_7_VI1.GlobalReset,422600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_7_VI1.HH_EN,422600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_7_VI1.H_EN,422600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_7_VI1.L_EN,422600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_7_VI1.LL_EN,422600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_7_VI1.BLEN,422600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_7_VI1.OR_EN,422600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_7_VI1.UREN,422600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_7_VI1.RC_EN,422600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_7_VI1.SuppressAA,422600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_7_VI1.SuppressLA,422600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_7_VI1.ConfigError,422600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_7_VI1.HH_Alarm,422600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_7_VI1.H_Alarm,422600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_7_VI1.L_Alarm,422600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_7_VI1.LL_Alarm,422600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_7_VI1.BL_Alarm,422601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_7_VI1.OR_Alarm,422601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_7_VI1.UR_Alarm,422601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_7_VI1.ROC_Alarm,422601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_7_VI1.REST,422601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_7_VI1.ALRM,422601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_7_VI1.ANUN,422601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_7_VI1.AKED,422601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_7_VI1.Resetable,422601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_7_VI1.HH_Fault,422601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_7_VI1.H_Fault,422601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_7_VI1.L_Fault,422601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_7_VI1.LL_Fault,422601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_7_VI1.BL_Fault,422601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_7_VI1.OR_Fault,422601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_7_VI1.UR_Fault,422601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_7_VI1.ROC_Fault,422602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_7_VI1.Tot_EN,422602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_7_VI1.TAGR,422602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_7_VI1.ACKN,422602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_7_VI1.INTK,422602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_7_VI1.PLCFault,422602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI1.PLCIOFault,422602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI1.INTK_EN,422602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_7_VI1.Shelve,422602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_7_VI1.Shelved,422602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_7_VI1.Suppress,422602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_7_VI1.Suppressed,422602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_7_VI1.PCSuppress,422602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_7_VI1.PCUnSuppress,422602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_7_VI1.PCUnshelve,422602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_7_VI2.GlobalReset,422800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_7_VI2.HH_EN,422800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_7_VI2.H_EN,422800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_7_VI2.L_EN,422800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_7_VI2.LL_EN,422800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_7_VI2.BLEN,422800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_7_VI2.OR_EN,422800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_7_VI2.UREN,422800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_7_VI2.RC_EN,422800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_7_VI2.SuppressAA,422800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_7_VI2.SuppressLA,422800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_7_VI2.ConfigError,422800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_7_VI2.HH_Alarm,422800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_7_VI2.H_Alarm,422800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_7_VI2.L_Alarm,422800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_7_VI2.LL_Alarm,422800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_7_VI2.BL_Alarm,422801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_7_VI2.OR_Alarm,422801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_7_VI2.UR_Alarm,422801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_7_VI2.ROC_Alarm,422801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_7_VI2.REST,422801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_7_VI2.ALRM,422801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_7_VI2.ANUN,422801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_7_VI2.AKED,422801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_7_VI2.Resetable,422801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_7_VI2.HH_Fault,422801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_7_VI2.H_Fault,422801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_7_VI2.L_Fault,422801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_7_VI2.LL_Fault,422801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_7_VI2.BL_Fault,422801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_7_VI2.OR_Fault,422801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_7_VI2.UR_Fault,422801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_7_VI2.ROC_Fault,422802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_7_VI2.Tot_EN,422802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_7_VI2.TAGR,422802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_7_VI2.ACKN,422802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_7_VI2.INTK,422802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_7_VI2.PLCFault,422802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI2.PLCIOFault,422802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI2.INTK_EN,422802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_7_VI2.Shelve,422802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_7_VI2.Shelved,422802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_7_VI2.Suppress,422802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_7_VI2.Suppressed,422802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_7_VI2.PCSuppress,422802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_7_VI2.PCUnSuppress,422802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_7_VI2.PCUnshelve,422802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_7_VI3.GlobalReset,423000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_7_VI3.HH_EN,423000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_7_VI3.H_EN,423000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_7_VI3.L_EN,423000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_7_VI3.LL_EN,423000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_7_VI3.BLEN,423000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_7_VI3.OR_EN,423000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_7_VI3.UREN,423000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_7_VI3.RC_EN,423000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_7_VI3.SuppressAA,423000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_7_VI3.SuppressLA,423000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_7_VI3.ConfigError,423000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_7_VI3.HH_Alarm,423000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_7_VI3.H_Alarm,423000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_7_VI3.L_Alarm,423000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_7_VI3.LL_Alarm,423000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_7_VI3.BL_Alarm,423001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_7_VI3.OR_Alarm,423001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_7_VI3.UR_Alarm,423001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_7_VI3.ROC_Alarm,423001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_7_VI3.REST,423001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_7_VI3.ALRM,423001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_7_VI3.ANUN,423001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_7_VI3.AKED,423001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_7_VI3.Resetable,423001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_7_VI3.HH_Fault,423001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_7_VI3.H_Fault,423001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_7_VI3.L_Fault,423001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_7_VI3.LL_Fault,423001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_7_VI3.BL_Fault,423001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_7_VI3.OR_Fault,423001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_7_VI3.UR_Fault,423001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_7_VI3.ROC_Fault,423002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_7_VI3.Tot_EN,423002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_7_VI3.TAGR,423002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_7_VI3.ACKN,423002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_7_VI3.INTK,423002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_7_VI3.PLCFault,423002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI3.PLCIOFault,423002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI3.INTK_EN,423002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_7_VI3.Shelve,423002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_7_VI3.Shelved,423002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_7_VI3.Suppress,423002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_7_VI3.Suppressed,423002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_7_VI3.PCSuppress,423002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_7_VI3.PCUnSuppress,423002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_7_VI3.PCUnshelve,423002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_7_VI4.GlobalReset,423200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_7_VI4.HH_EN,423200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_7_VI4.H_EN,423200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_7_VI4.L_EN,423200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_7_VI4.LL_EN,423200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_7_VI4.BLEN,423200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_7_VI4.OR_EN,423200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_7_VI4.UREN,423200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_7_VI4.RC_EN,423200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_7_VI4.SuppressAA,423200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_7_VI4.SuppressLA,423200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_7_VI4.ConfigError,423200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_7_VI4.HH_Alarm,423200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_7_VI4.H_Alarm,423200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_7_VI4.L_Alarm,423200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_7_VI4.LL_Alarm,423200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_7_VI4.BL_Alarm,423201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_7_VI4.OR_Alarm,423201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_7_VI4.UR_Alarm,423201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_7_VI4.ROC_Alarm,423201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_7_VI4.REST,423201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_7_VI4.ALRM,423201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_7_VI4.ANUN,423201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_7_VI4.AKED,423201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_7_VI4.Resetable,423201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_7_VI4.HH_Fault,423201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_7_VI4.H_Fault,423201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_7_VI4.L_Fault,423201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_7_VI4.LL_Fault,423201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_7_VI4.BL_Fault,423201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_7_VI4.OR_Fault,423201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_7_VI4.UR_Fault,423201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_7_VI4.ROC_Fault,423202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_7_VI4.Tot_EN,423202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_7_VI4.TAGR,423202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_7_VI4.ACKN,423202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_7_VI4.INTK,423202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_7_VI4.PLCFault,423202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI4.PLCIOFault,423202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI4.INTK_EN,423202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_7_VI4.Shelve,423202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_7_VI4.Shelved,423202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_7_VI4.Suppress,423202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_7_VI4.Suppressed,423202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_7_VI4.PCSuppress,423202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_7_VI4.PCUnSuppress,423202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_7_VI4.PCUnshelve,423202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_7_VI5.GlobalReset,423400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_7_VI5.HH_EN,423400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_7_VI5.H_EN,423400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_7_VI5.L_EN,423400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_7_VI5.LL_EN,423400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_7_VI5.BLEN,423400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_7_VI5.OR_EN,423400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_7_VI5.UREN,423400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_7_VI5.RC_EN,423400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_7_VI5.SuppressAA,423400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_7_VI5.SuppressLA,423400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_7_VI5.ConfigError,423400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_7_VI5.HH_Alarm,423400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_7_VI5.H_Alarm,423400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_7_VI5.L_Alarm,423400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_7_VI5.LL_Alarm,423400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_7_VI5.BL_Alarm,423401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_7_VI5.OR_Alarm,423401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_7_VI5.UR_Alarm,423401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_7_VI5.ROC_Alarm,423401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_7_VI5.REST,423401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_7_VI5.ALRM,423401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_7_VI5.ANUN,423401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_7_VI5.AKED,423401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_7_VI5.Resetable,423401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_7_VI5.HH_Fault,423401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_7_VI5.H_Fault,423401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_7_VI5.L_Fault,423401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_7_VI5.LL_Fault,423401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_7_VI5.BL_Fault,423401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_7_VI5.OR_Fault,423401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_7_VI5.UR_Fault,423401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_7_VI5.ROC_Fault,423402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_7_VI5.Tot_EN,423402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_7_VI5.TAGR,423402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_7_VI5.ACKN,423402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_7_VI5.INTK,423402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_7_VI5.PLCFault,423402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI5.PLCIOFault,423402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_7_VI5.INTK_EN,423402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_7_VI5.Shelve,423402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_7_VI5.Shelved,423402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_7_VI5.Suppress,423402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_7_VI5.Suppressed,423402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_7_VI5.PCSuppress,423402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_7_VI5.PCUnSuppress,423402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_7_VI5.PCUnshelve,423402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_8_VI1.GlobalReset,423600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_8_VI1.HH_EN,423600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_8_VI1.H_EN,423600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_8_VI1.L_EN,423600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_8_VI1.LL_EN,423600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_8_VI1.BLEN,423600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_8_VI1.OR_EN,423600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_8_VI1.UREN,423600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_8_VI1.RC_EN,423600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_8_VI1.SuppressAA,423600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_8_VI1.SuppressLA,423600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_8_VI1.ConfigError,423600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_8_VI1.HH_Alarm,423600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_8_VI1.H_Alarm,423600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_8_VI1.L_Alarm,423600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_8_VI1.LL_Alarm,423600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_8_VI1.BL_Alarm,423601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_8_VI1.OR_Alarm,423601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_8_VI1.UR_Alarm,423601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_8_VI1.ROC_Alarm,423601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_8_VI1.REST,423601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_8_VI1.ALRM,423601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_8_VI1.ANUN,423601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_8_VI1.AKED,423601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_8_VI1.Resetable,423601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_8_VI1.HH_Fault,423601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_8_VI1.H_Fault,423601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_8_VI1.L_Fault,423601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_8_VI1.LL_Fault,423601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_8_VI1.BL_Fault,423601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_8_VI1.OR_Fault,423601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_8_VI1.UR_Fault,423601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_8_VI1.ROC_Fault,423602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_8_VI1.Tot_EN,423602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_8_VI1.TAGR,423602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_8_VI1.ACKN,423602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_8_VI1.INTK,423602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_8_VI1.PLCFault,423602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI1.PLCIOFault,423602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI1.INTK_EN,423602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_8_VI1.Shelve,423602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_8_VI1.Shelved,423602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_8_VI1.Suppress,423602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_8_VI1.Suppressed,423602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_8_VI1.PCSuppress,423602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_8_VI1.PCUnSuppress,423602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_8_VI1.PCUnshelve,423602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_8_VI2.GlobalReset,423800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_8_VI2.HH_EN,423800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_8_VI2.H_EN,423800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_8_VI2.L_EN,423800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_8_VI2.LL_EN,423800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_8_VI2.BLEN,423800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_8_VI2.OR_EN,423800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_8_VI2.UREN,423800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_8_VI2.RC_EN,423800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_8_VI2.SuppressAA,423800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_8_VI2.SuppressLA,423800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_8_VI2.ConfigError,423800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_8_VI2.HH_Alarm,423800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_8_VI2.H_Alarm,423800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_8_VI2.L_Alarm,423800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_8_VI2.LL_Alarm,423800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_8_VI2.BL_Alarm,423801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_8_VI2.OR_Alarm,423801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_8_VI2.UR_Alarm,423801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_8_VI2.ROC_Alarm,423801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_8_VI2.REST,423801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_8_VI2.ALRM,423801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_8_VI2.ANUN,423801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_8_VI2.AKED,423801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_8_VI2.Resetable,423801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_8_VI2.HH_Fault,423801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_8_VI2.H_Fault,423801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_8_VI2.L_Fault,423801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_8_VI2.LL_Fault,423801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_8_VI2.BL_Fault,423801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_8_VI2.OR_Fault,423801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_8_VI2.UR_Fault,423801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_8_VI2.ROC_Fault,423802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_8_VI2.Tot_EN,423802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_8_VI2.TAGR,423802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_8_VI2.ACKN,423802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_8_VI2.INTK,423802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_8_VI2.PLCFault,423802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI2.PLCIOFault,423802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI2.INTK_EN,423802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_8_VI2.Shelve,423802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_8_VI2.Shelved,423802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_8_VI2.Suppress,423802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_8_VI2.Suppressed,423802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_8_VI2.PCSuppress,423802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_8_VI2.PCUnSuppress,423802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_8_VI2.PCUnshelve,423802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_8_VI3.GlobalReset,424000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_8_VI3.HH_EN,424000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_8_VI3.H_EN,424000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_8_VI3.L_EN,424000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_8_VI3.LL_EN,424000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_8_VI3.BLEN,424000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_8_VI3.OR_EN,424000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_8_VI3.UREN,424000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_8_VI3.RC_EN,424000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_8_VI3.SuppressAA,424000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_8_VI3.SuppressLA,424000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_8_VI3.ConfigError,424000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_8_VI3.HH_Alarm,424000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_8_VI3.H_Alarm,424000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_8_VI3.L_Alarm,424000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_8_VI3.LL_Alarm,424000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_8_VI3.BL_Alarm,424001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_8_VI3.OR_Alarm,424001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_8_VI3.UR_Alarm,424001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_8_VI3.ROC_Alarm,424001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_8_VI3.REST,424001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_8_VI3.ALRM,424001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_8_VI3.ANUN,424001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_8_VI3.AKED,424001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_8_VI3.Resetable,424001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_8_VI3.HH_Fault,424001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_8_VI3.H_Fault,424001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_8_VI3.L_Fault,424001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_8_VI3.LL_Fault,424001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_8_VI3.BL_Fault,424001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_8_VI3.OR_Fault,424001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_8_VI3.UR_Fault,424001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_8_VI3.ROC_Fault,424002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_8_VI3.Tot_EN,424002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_8_VI3.TAGR,424002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_8_VI3.ACKN,424002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_8_VI3.INTK,424002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_8_VI3.PLCFault,424002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI3.PLCIOFault,424002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI3.INTK_EN,424002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_8_VI3.Shelve,424002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_8_VI3.Shelved,424002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_8_VI3.Suppress,424002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_8_VI3.Suppressed,424002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_8_VI3.PCSuppress,424002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_8_VI3.PCUnSuppress,424002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_8_VI3.PCUnshelve,424002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_8_VI4.GlobalReset,424200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_8_VI4.HH_EN,424200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_8_VI4.H_EN,424200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_8_VI4.L_EN,424200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_8_VI4.LL_EN,424200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_8_VI4.BLEN,424200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_8_VI4.OR_EN,424200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_8_VI4.UREN,424200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_8_VI4.RC_EN,424200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_8_VI4.SuppressAA,424200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_8_VI4.SuppressLA,424200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_8_VI4.ConfigError,424200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_8_VI4.HH_Alarm,424200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_8_VI4.H_Alarm,424200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_8_VI4.L_Alarm,424200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_8_VI4.LL_Alarm,424200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_8_VI4.BL_Alarm,424201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_8_VI4.OR_Alarm,424201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_8_VI4.UR_Alarm,424201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_8_VI4.ROC_Alarm,424201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_8_VI4.REST,424201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_8_VI4.ALRM,424201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_8_VI4.ANUN,424201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_8_VI4.AKED,424201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_8_VI4.Resetable,424201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_8_VI4.HH_Fault,424201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_8_VI4.H_Fault,424201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_8_VI4.L_Fault,424201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_8_VI4.LL_Fault,424201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_8_VI4.BL_Fault,424201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_8_VI4.OR_Fault,424201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_8_VI4.UR_Fault,424201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_8_VI4.ROC_Fault,424202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_8_VI4.Tot_EN,424202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_8_VI4.TAGR,424202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_8_VI4.ACKN,424202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_8_VI4.INTK,424202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_8_VI4.PLCFault,424202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI4.PLCIOFault,424202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI4.INTK_EN,424202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_8_VI4.Shelve,424202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_8_VI4.Shelved,424202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_8_VI4.Suppress,424202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_8_VI4.Suppressed,424202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_8_VI4.PCSuppress,424202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_8_VI4.PCUnSuppress,424202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_8_VI4.PCUnshelve,424202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_8_VI5.GlobalReset,424400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_8_VI5.HH_EN,424400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_8_VI5.H_EN,424400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_8_VI5.L_EN,424400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_8_VI5.LL_EN,424400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_8_VI5.BLEN,424400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_8_VI5.OR_EN,424400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_8_VI5.UREN,424400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_8_VI5.RC_EN,424400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_8_VI5.SuppressAA,424400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_8_VI5.SuppressLA,424400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_8_VI5.ConfigError,424400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_8_VI5.HH_Alarm,424400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_8_VI5.H_Alarm,424400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_8_VI5.L_Alarm,424400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_8_VI5.LL_Alarm,424400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_8_VI5.BL_Alarm,424401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_8_VI5.OR_Alarm,424401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_8_VI5.UR_Alarm,424401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_8_VI5.ROC_Alarm,424401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_8_VI5.REST,424401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_8_VI5.ALRM,424401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_8_VI5.ANUN,424401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_8_VI5.AKED,424401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_8_VI5.Resetable,424401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_8_VI5.HH_Fault,424401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_8_VI5.H_Fault,424401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_8_VI5.L_Fault,424401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_8_VI5.LL_Fault,424401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_8_VI5.BL_Fault,424401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_8_VI5.OR_Fault,424401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_8_VI5.UR_Fault,424401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_8_VI5.ROC_Fault,424402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_8_VI5.Tot_EN,424402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_8_VI5.TAGR,424402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_8_VI5.ACKN,424402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_8_VI5.INTK,424402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_8_VI5.PLCFault,424402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI5.PLCIOFault,424402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_8_VI5.INTK_EN,424402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_8_VI5.Shelve,424402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_8_VI5.Shelved,424402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_8_VI5.Suppress,424402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_8_VI5.Suppressed,424402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_8_VI5.PCSuppress,424402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_8_VI5.PCUnSuppress,424402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_8_VI5.PCUnshelve,424402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_9_VI1.GlobalReset,424600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_9_VI1.HH_EN,424600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_9_VI1.H_EN,424600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_9_VI1.L_EN,424600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_9_VI1.LL_EN,424600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_9_VI1.BLEN,424600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_9_VI1.OR_EN,424600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_9_VI1.UREN,424600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_9_VI1.RC_EN,424600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_9_VI1.SuppressAA,424600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_9_VI1.SuppressLA,424600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_9_VI1.ConfigError,424600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_9_VI1.HH_Alarm,424600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_9_VI1.H_Alarm,424600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_9_VI1.L_Alarm,424600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_9_VI1.LL_Alarm,424600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_9_VI1.BL_Alarm,424601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_9_VI1.OR_Alarm,424601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_9_VI1.UR_Alarm,424601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_9_VI1.ROC_Alarm,424601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_9_VI1.REST,424601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_9_VI1.ALRM,424601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_9_VI1.ANUN,424601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_9_VI1.AKED,424601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_9_VI1.Resetable,424601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_9_VI1.HH_Fault,424601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_9_VI1.H_Fault,424601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_9_VI1.L_Fault,424601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_9_VI1.LL_Fault,424601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_9_VI1.BL_Fault,424601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_9_VI1.OR_Fault,424601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_9_VI1.UR_Fault,424601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_9_VI1.ROC_Fault,424602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_9_VI1.Tot_EN,424602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_9_VI1.TAGR,424602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_9_VI1.ACKN,424602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_9_VI1.INTK,424602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_9_VI1.PLCFault,424602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI1.PLCIOFault,424602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI1.INTK_EN,424602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_9_VI1.Shelve,424602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_9_VI1.Shelved,424602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_9_VI1.Suppress,424602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_9_VI1.Suppressed,424602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_9_VI1.PCSuppress,424602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_9_VI1.PCUnSuppress,424602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_9_VI1.PCUnshelve,424602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_9_VI2.GlobalReset,424800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_9_VI2.HH_EN,424800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_9_VI2.H_EN,424800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_9_VI2.L_EN,424800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_9_VI2.LL_EN,424800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_9_VI2.BLEN,424800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_9_VI2.OR_EN,424800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_9_VI2.UREN,424800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_9_VI2.RC_EN,424800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_9_VI2.SuppressAA,424800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_9_VI2.SuppressLA,424800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_9_VI2.ConfigError,424800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_9_VI2.HH_Alarm,424800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_9_VI2.H_Alarm,424800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_9_VI2.L_Alarm,424800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_9_VI2.LL_Alarm,424800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_9_VI2.BL_Alarm,424801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_9_VI2.OR_Alarm,424801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_9_VI2.UR_Alarm,424801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_9_VI2.ROC_Alarm,424801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_9_VI2.REST,424801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_9_VI2.ALRM,424801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_9_VI2.ANUN,424801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_9_VI2.AKED,424801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_9_VI2.Resetable,424801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_9_VI2.HH_Fault,424801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_9_VI2.H_Fault,424801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_9_VI2.L_Fault,424801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_9_VI2.LL_Fault,424801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_9_VI2.BL_Fault,424801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_9_VI2.OR_Fault,424801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_9_VI2.UR_Fault,424801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_9_VI2.ROC_Fault,424802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_9_VI2.Tot_EN,424802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_9_VI2.TAGR,424802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_9_VI2.ACKN,424802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_9_VI2.INTK,424802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_9_VI2.PLCFault,424802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI2.PLCIOFault,424802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI2.INTK_EN,424802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_9_VI2.Shelve,424802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_9_VI2.Shelved,424802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_9_VI2.Suppress,424802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_9_VI2.Suppressed,424802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_9_VI2.PCSuppress,424802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_9_VI2.PCUnSuppress,424802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_9_VI2.PCUnshelve,424802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_9_VI3.GlobalReset,425000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_9_VI3.HH_EN,425000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_9_VI3.H_EN,425000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_9_VI3.L_EN,425000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_9_VI3.LL_EN,425000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_9_VI3.BLEN,425000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_9_VI3.OR_EN,425000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_9_VI3.UREN,425000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_9_VI3.RC_EN,425000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_9_VI3.SuppressAA,425000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_9_VI3.SuppressLA,425000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_9_VI3.ConfigError,425000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_9_VI3.HH_Alarm,425000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_9_VI3.H_Alarm,425000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_9_VI3.L_Alarm,425000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_9_VI3.LL_Alarm,425000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_9_VI3.BL_Alarm,425001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_9_VI3.OR_Alarm,425001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_9_VI3.UR_Alarm,425001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_9_VI3.ROC_Alarm,425001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_9_VI3.REST,425001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_9_VI3.ALRM,425001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_9_VI3.ANUN,425001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_9_VI3.AKED,425001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_9_VI3.Resetable,425001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_9_VI3.HH_Fault,425001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_9_VI3.H_Fault,425001.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_9_VI3.L_Fault,425001.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_9_VI3.LL_Fault,425001.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_9_VI3.BL_Fault,425001.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_9_VI3.OR_Fault,425001.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_9_VI3.UR_Fault,425001.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_9_VI3.ROC_Fault,425002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_9_VI3.Tot_EN,425002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_9_VI3.TAGR,425002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_9_VI3.ACKN,425002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_9_VI3.INTK,425002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_9_VI3.PLCFault,425002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI3.PLCIOFault,425002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI3.INTK_EN,425002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_9_VI3.Shelve,425002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_9_VI3.Shelved,425002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_9_VI3.Suppress,425002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_9_VI3.Suppressed,425002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_9_VI3.PCSuppress,425002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_9_VI3.PCUnSuppress,425002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_9_VI3.PCUnshelve,425002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_9_VI4.GlobalReset,425200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_9_VI4.HH_EN,425200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_9_VI4.H_EN,425200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_9_VI4.L_EN,425200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_9_VI4.LL_EN,425200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_9_VI4.BLEN,425200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_9_VI4.OR_EN,425200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_9_VI4.UREN,425200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_9_VI4.RC_EN,425200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_9_VI4.SuppressAA,425200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_9_VI4.SuppressLA,425200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_9_VI4.ConfigError,425200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_9_VI4.HH_Alarm,425200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_9_VI4.H_Alarm,425200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_9_VI4.L_Alarm,425200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_9_VI4.LL_Alarm,425200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_9_VI4.BL_Alarm,425201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_9_VI4.OR_Alarm,425201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_9_VI4.UR_Alarm,425201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_9_VI4.ROC_Alarm,425201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_9_VI4.REST,425201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_9_VI4.ALRM,425201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_9_VI4.ANUN,425201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_9_VI4.AKED,425201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_9_VI4.Resetable,425201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_9_VI4.HH_Fault,425201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_9_VI4.H_Fault,425201.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_9_VI4.L_Fault,425201.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_9_VI4.LL_Fault,425201.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_9_VI4.BL_Fault,425201.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_9_VI4.OR_Fault,425201.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_9_VI4.UR_Fault,425201.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_9_VI4.ROC_Fault,425202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_9_VI4.Tot_EN,425202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_9_VI4.TAGR,425202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_9_VI4.ACKN,425202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_9_VI4.INTK,425202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_9_VI4.PLCFault,425202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI4.PLCIOFault,425202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI4.INTK_EN,425202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_9_VI4.Shelve,425202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_9_VI4.Shelved,425202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_9_VI4.Suppress,425202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_9_VI4.Suppressed,425202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_9_VI4.PCSuppress,425202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_9_VI4.PCUnSuppress,425202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_9_VI4.PCUnshelve,425202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_PMP_0103_9_VI5.GlobalReset,425400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_PMP_0103_9_VI5.HH_EN,425400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_PMP_0103_9_VI5.H_EN,425400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_PMP_0103_9_VI5.L_EN,425400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_PMP_0103_9_VI5.LL_EN,425400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_PMP_0103_9_VI5.BLEN,425400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_PMP_0103_9_VI5.OR_EN,425400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_PMP_0103_9_VI5.UREN,425400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_PMP_0103_9_VI5.RC_EN,425400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_PMP_0103_9_VI5.SuppressAA,425400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_PMP_0103_9_VI5.SuppressLA,425400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_PMP_0103_9_VI5.ConfigError,425400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_PMP_0103_9_VI5.HH_Alarm,425400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_PMP_0103_9_VI5.H_Alarm,425400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_PMP_0103_9_VI5.L_Alarm,425400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_PMP_0103_9_VI5.LL_Alarm,425400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_PMP_0103_9_VI5.BL_Alarm,425401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_PMP_0103_9_VI5.OR_Alarm,425401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_PMP_0103_9_VI5.UR_Alarm,425401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_PMP_0103_9_VI5.ROC_Alarm,425401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_PMP_0103_9_VI5.REST,425401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_PMP_0103_9_VI5.ALRM,425401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_PMP_0103_9_VI5.ANUN,425401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_PMP_0103_9_VI5.AKED,425401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_PMP_0103_9_VI5.Resetable,425401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PMP_0103_9_VI5.HH_Fault,425401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_PMP_0103_9_VI5.H_Fault,425401.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_PMP_0103_9_VI5.L_Fault,425401.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_PMP_0103_9_VI5.LL_Fault,425401.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_PMP_0103_9_VI5.BL_Fault,425401.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_PMP_0103_9_VI5.OR_Fault,425401.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_PMP_0103_9_VI5.UR_Fault,425401.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_PMP_0103_9_VI5.ROC_Fault,425402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_PMP_0103_9_VI5.Tot_EN,425402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_PMP_0103_9_VI5.TAGR,425402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_PMP_0103_9_VI5.ACKN,425402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_PMP_0103_9_VI5.INTK,425402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_PMP_0103_9_VI5.PLCFault,425402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI5.PLCIOFault,425402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PMP_0103_9_VI5.INTK_EN,425402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_PMP_0103_9_VI5.Shelve,425402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_PMP_0103_9_VI5.Shelved,425402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_PMP_0103_9_VI5.Suppress,425402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_PMP_0103_9_VI5.Suppressed,425402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_PMP_0103_9_VI5.PCSuppress,425402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_PMP_0103_9_VI5.PCUnSuppress,425402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_PMP_0103_9_VI5.PCUnshelve,425402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_TT_0111_1_TI.GlobalReset,425600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_TT_0111_1_TI.HH_EN,425600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_TT_0111_1_TI.H_EN,425600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_TT_0111_1_TI.L_EN,425600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_TT_0111_1_TI.LL_EN,425600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_TT_0111_1_TI.BLEN,425600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_TT_0111_1_TI.OR_EN,425600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_TT_0111_1_TI.UREN,425600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_TT_0111_1_TI.RC_EN,425600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_TT_0111_1_TI.SuppressAA,425600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_TT_0111_1_TI.SuppressLA,425600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_TT_0111_1_TI.ConfigError,425600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_TT_0111_1_TI.HH_Alarm,425600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_TT_0111_1_TI.H_Alarm,425600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_TT_0111_1_TI.L_Alarm,425600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_TT_0111_1_TI.LL_Alarm,425600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_TT_0111_1_TI.BL_Alarm,425601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_TT_0111_1_TI.OR_Alarm,425601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_TT_0111_1_TI.UR_Alarm,425601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_TT_0111_1_TI.ROC_Alarm,425601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_TT_0111_1_TI.REST,425601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_TT_0111_1_TI.ALRM,425601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_TT_0111_1_TI.ANUN,425601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_TT_0111_1_TI.AKED,425601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_TT_0111_1_TI.Resetable,425601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TT_0111_1_TI.HH_Fault,425601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_TT_0111_1_TI.H_Fault,425601.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_TT_0111_1_TI.L_Fault,425601.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_TT_0111_1_TI.LL_Fault,425601.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_TT_0111_1_TI.BL_Fault,425601.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_TT_0111_1_TI.OR_Fault,425601.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_TT_0111_1_TI.UR_Fault,425601.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_TT_0111_1_TI.ROC_Fault,425602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_TT_0111_1_TI.Tot_EN,425602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_TT_0111_1_TI.TAGR,425602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_TT_0111_1_TI.ACKN,425602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_TT_0111_1_TI.INTK,425602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_TT_0111_1_TI.PLCFault,425602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TT_0111_1_TI.PLCIOFault,425602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TT_0111_1_TI.INTK_EN,425602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_TT_0111_1_TI.Shelve,425602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_TT_0111_1_TI.Shelved,425602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_TT_0111_1_TI.Suppress,425602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_TT_0111_1_TI.Suppressed,425602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_TT_0111_1_TI.PCSuppress,425602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_TT_0111_1_TI.PCUnSuppress,425602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_TT_0111_1_TI.PCUnshelve,425602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_TT_0112_1_TI.GlobalReset,425800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms On this PLC" WA3252_TT_0112_1_TI.HH_EN,425800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High High Alarm" WA3252_TT_0112_1_TI.H_EN,425800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable High Alarm" WA3252_TT_0112_1_TI.L_EN,425800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Alarm" WA3252_TT_0112_1_TI.LL_EN,425800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Low Low Alarm" WA3252_TT_0112_1_TI.BLEN,425800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Broken Loop Alarm" WA3252_TT_0112_1_TI.OR_EN,425800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Over Range Alarm" WA3252_TT_0112_1_TI.UREN,425800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Under Range Alarm" WA3252_TT_0112_1_TI.RC_EN,425800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Rate of Change Alarm" WA3252_TT_0112_1_TI.SuppressAA,425800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress All Alarms" WA3252_TT_0112_1_TI.SuppressLA,425800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Level Alarms (LL, L, H, HH, & ROC)" WA3252_TT_0112_1_TI.ConfigError,425800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: RawMin = RawMax: Causes division by zero" WA3252_TT_0112_1_TI.HH_Alarm,425800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm" WA3252_TT_0112_1_TI.H_Alarm,425800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm" WA3252_TT_0112_1_TI.L_Alarm,425800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm" WA3252_TT_0112_1_TI.LL_Alarm,425800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm" WA3252_TT_0112_1_TI.BL_Alarm,425801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm" WA3252_TT_0112_1_TI.OR_Alarm,425801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm" WA3252_TT_0112_1_TI.UR_Alarm,425801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm" WA3252_TT_0112_1_TI.ROC_Alarm,425801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Alarm" WA3252_TT_0112_1_TI.REST,425801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Reset all Alarms in this DFB" WA3252_TT_0112_1_TI.ALRM,425801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Active" WA3252_TT_0112_1_TI.ANUN,425801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Annunciating" WA3252_TT_0112_1_TI.AKED,425801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At Least One Alarm is Acknowledged" WA3252_TT_0112_1_TI.Resetable,425801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TT_0112_1_TI.HH_Fault,425801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Fault" WA3252_TT_0112_1_TI.H_Fault,425801.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Fault" WA3252_TT_0112_1_TI.L_Fault,425801.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Fault" WA3252_TT_0112_1_TI.LL_Fault,425801.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Fault" WA3252_TT_0112_1_TI.BL_Fault,425801.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Fault" WA3252_TT_0112_1_TI.OR_Fault,425801.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Fault" WA3252_TT_0112_1_TI.UR_Fault,425801.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Fault" WA3252_TT_0112_1_TI.ROC_Fault,425802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate of Change Fault" WA3252_TT_0112_1_TI.Tot_EN,425802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set true to totalize flow." WA3252_TT_0112_1_TI.TAGR,425802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Tagged Out of Service" WA3252_TT_0112_1_TI.ACKN,425802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_TT_0112_1_TI.INTK,425802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Locked by program (ESD)" WA3252_TT_0112_1_TI.PLCFault,425802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TT_0112_1_TI.PLCIOFault,425802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TT_0112_1_TI.INTK_EN,425802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Enable Interlock Alarm" WA3252_TT_0112_1_TI.Shelve,425802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelve Command from HMI" WA3252_TT_0112_1_TI.Shelved,425802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Shelved Status" WA3252_TT_0112_1_TI.Suppress,425802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Command from HMI" WA3252_TT_0112_1_TI.Suppressed,425802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppressed Status" WA3252_TT_0112_1_TI.PCSuppress,425802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Suppress Alarm from Program Control" WA3252_TT_0112_1_TI.PCUnSuppress,425802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: UnSuppress Alarm from Program Control" WA3252_TT_0112_1_TI.PCUnshelve,425802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_FA.Fault,426000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_FA.Faulted,426000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_FA.AlarmState,426000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_FA.FaultInAlarm,426000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_FA.Alarm_EN,426000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_FA.REST,426000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_FA.ACKN,426000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_FA.MCmd_Enable,426000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_FA.MCmd_Disable,426000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_FA.ALRM,426000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_FA.ANUN,426000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_FA.AKED,426000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_FA.Resetable,426000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_FA.Shelve,426000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_FA.Suppress,426000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_FA.InputAlarm,426000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_FA.GlobalReset,426001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_FA.PCSuppress,426001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_FA.PCUnSuppress,426001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_FA.PCUnshelve,426001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_FA.Alarm_Fault,426001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_FA.Shelved,426001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_FA.Suppressed,426001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_FA.PLCIOFault,426001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_FA.PLCF,426001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_FA.TAGR,426001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_MF.Fault,426036.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_MF.Faulted,426036.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_MF.AlarmState,426036.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_MF.FaultInAlarm,426036.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MF.Alarm_EN,426036.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_MF.REST,426036.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_MF.ACKN,426036.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_MF.MCmd_Enable,426036.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MF.MCmd_Disable,426036.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MF.ALRM,426036.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_MF.ANUN,426036.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_MF.AKED,426036.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_MF.Resetable,426036.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_MF.Shelve,426036.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_MF.Suppress,426036.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_MF.InputAlarm,426036.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_MF.GlobalReset,426037.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_MF.PCSuppress,426037.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_MF.PCUnSuppress,426037.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_MF.PCUnshelve,426037.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_MF.Alarm_Fault,426037.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_MF.Shelved,426037.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_MF.Suppressed,426037.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_MF.PLCIOFault,426037.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_MF.PLCF,426037.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_MF.TAGR,426037.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_MY.Fault,426070.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_MY.Faulted,426070.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_MY.AlarmState,426070.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_MY.FaultInAlarm,426070.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MY.Alarm_EN,426070.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_MY.REST,426070.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_MY.ACKN,426070.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_MY.MCmd_Enable,426070.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MY.MCmd_Disable,426070.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MY.ALRM,426070.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_MY.ANUN,426070.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_MY.AKED,426070.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_MY.Resetable,426070.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_MY.Shelve,426070.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_MY.Suppress,426070.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_MY.InputAlarm,426070.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_MY.GlobalReset,426071.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_MY.PCSuppress,426071.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_MY.PCUnSuppress,426071.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_MY.PCUnshelve,426071.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_MY.Alarm_Fault,426071.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_MY.Shelved,426071.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_MY.Suppressed,426071.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_MY.PLCIOFault,426071.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_MY.PLCF,426071.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_MY.TAGR,426071.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_UA.Fault,426106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_UA.Faulted,426106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_UA.AlarmState,426106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_UA.FaultInAlarm,426106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UA.Alarm_EN,426106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_UA.REST,426106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_UA.ACKN,426106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_UA.MCmd_Enable,426106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UA.MCmd_Disable,426106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UA.ALRM,426106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_UA.ANUN,426106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_UA.AKED,426106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_UA.Resetable,426106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_UA.Shelve,426106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_UA.Suppress,426106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_UA.InputAlarm,426106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_UA.GlobalReset,426107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_UA.PCSuppress,426107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_UA.PCUnSuppress,426107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_UA.PCUnshelve,426107.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_UA.Alarm_Fault,426107.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_UA.Shelved,426107.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_UA.Suppressed,426107.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_UA.PLCIOFault,426107.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UA.PLCF,426107.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UA.TAGR,426107.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_UH.Fault,426140.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_UH.Faulted,426140.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_UH.AlarmState,426140.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_UH.FaultInAlarm,426140.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UH.Alarm_EN,426140.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_UH.REST,426140.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_UH.ACKN,426140.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_UH.MCmd_Enable,426140.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UH.MCmd_Disable,426140.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UH.ALRM,426140.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_UH.ANUN,426140.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_UH.AKED,426140.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_UH.Resetable,426140.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_UH.Shelve,426140.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_UH.Suppress,426140.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_UH.InputAlarm,426140.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_UH.GlobalReset,426141.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_UH.PCSuppress,426141.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_UH.PCUnSuppress,426141.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_UH.PCUnshelve,426141.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_UH.Alarm_Fault,426141.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_UH.Shelved,426141.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_UH.Suppressed,426141.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_UH.PLCIOFault,426141.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UH.PLCF,426141.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UH.TAGR,426141.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_UY.Fault,426176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_UY.Faulted,426176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_UY.AlarmState,426176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_UY.FaultInAlarm,426176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UY.Alarm_EN,426176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_UY.REST,426176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_UY.ACKN,426176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_UY.MCmd_Enable,426176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UY.MCmd_Disable,426176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UY.ALRM,426176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_UY.ANUN,426176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_UY.AKED,426176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_UY.Resetable,426176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_UY.Shelve,426176.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_UY.Suppress,426176.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_UY.InputAlarm,426176.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_UY.GlobalReset,426177.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_UY.PCSuppress,426177.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_UY.PCUnSuppress,426177.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_UY.PCUnshelve,426177.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_UY.Alarm_Fault,426177.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_UY.Shelved,426177.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_UY.Suppressed,426177.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_UY.PLCIOFault,426177.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UY.PLCF,426177.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_UY.TAGR,426177.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_XF.Fault,426210.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_XF.Faulted,426210.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_XF.AlarmState,426210.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_XF.FaultInAlarm,426210.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_XF.Alarm_EN,426210.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_XF.REST,426210.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_XF.ACKN,426210.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_XF.MCmd_Enable,426210.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_XF.MCmd_Disable,426210.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_XF.ALRM,426210.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_XF.ANUN,426210.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_XF.AKED,426210.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_XF.Resetable,426210.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_XF.Shelve,426210.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_XF.Suppress,426210.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_XF.InputAlarm,426210.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_XF.GlobalReset,426211.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_XF.PCSuppress,426211.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_XF.PCUnSuppress,426211.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_XF.PCUnshelve,426211.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_XF.Alarm_Fault,426211.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_XF.Shelved,426211.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_XF.Suppressed,426211.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_XF.PLCIOFault,426211.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_XF.PLCF,426211.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_XF.TAGR,426211.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1_YA.Fault,426246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_1_YA.Faulted,426246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_1_YA.AlarmState,426246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_1_YA.FaultInAlarm,426246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_YA.Alarm_EN,426246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_1_YA.REST,426246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_1_YA.ACKN,426246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_1_YA.MCmd_Enable,426246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_YA.MCmd_Disable,426246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_YA.ALRM,426246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_1_YA.ANUN,426246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_1_YA.AKED,426246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_1_YA.Resetable,426246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_1_YA.Shelve,426246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1_YA.Suppress,426246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1_YA.InputAlarm,426246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_1_YA.GlobalReset,426247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_1_YA.PCSuppress,426247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1_YA.PCUnSuppress,426247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1_YA.PCUnshelve,426247.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_1_YA.Alarm_Fault,426247.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_1_YA.Shelved,426247.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_1_YA.Suppressed,426247.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_1_YA.PLCIOFault,426247.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_YA.PLCF,426247.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1_YA.TAGR,426247.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_FA.Fault,426280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_FA.Faulted,426280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_FA.AlarmState,426280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_FA.FaultInAlarm,426280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_FA.Alarm_EN,426280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_FA.REST,426280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_FA.ACKN,426280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_FA.MCmd_Enable,426280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_FA.MCmd_Disable,426280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_FA.ALRM,426280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_FA.ANUN,426280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_FA.AKED,426280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_FA.Resetable,426280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_FA.Shelve,426280.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_FA.Suppress,426280.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_FA.InputAlarm,426280.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_FA.GlobalReset,426281.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_FA.PCSuppress,426281.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_FA.PCUnSuppress,426281.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_FA.PCUnshelve,426281.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_FA.Alarm_Fault,426281.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_FA.Shelved,426281.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_FA.Suppressed,426281.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_FA.PLCIOFault,426281.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_FA.PLCF,426281.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_FA.TAGR,426281.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_MF.Fault,426316.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_MF.Faulted,426316.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_MF.AlarmState,426316.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_MF.FaultInAlarm,426316.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MF.Alarm_EN,426316.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_MF.REST,426316.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_MF.ACKN,426316.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_MF.MCmd_Enable,426316.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MF.MCmd_Disable,426316.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MF.ALRM,426316.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_MF.ANUN,426316.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_MF.AKED,426316.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_MF.Resetable,426316.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_MF.Shelve,426316.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_MF.Suppress,426316.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_MF.InputAlarm,426316.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_MF.GlobalReset,426317.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_MF.PCSuppress,426317.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_MF.PCUnSuppress,426317.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_MF.PCUnshelve,426317.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_MF.Alarm_Fault,426317.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_MF.Shelved,426317.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_MF.Suppressed,426317.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_MF.PLCIOFault,426317.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_MF.PLCF,426317.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_MF.TAGR,426317.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_MY.Fault,426350.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_MY.Faulted,426350.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_MY.AlarmState,426350.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_MY.FaultInAlarm,426350.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MY.Alarm_EN,426350.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_MY.REST,426350.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_MY.ACKN,426350.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_MY.MCmd_Enable,426350.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MY.MCmd_Disable,426350.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MY.ALRM,426350.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_MY.ANUN,426350.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_MY.AKED,426350.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_MY.Resetable,426350.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_MY.Shelve,426350.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_MY.Suppress,426350.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_MY.InputAlarm,426350.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_MY.GlobalReset,426351.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_MY.PCSuppress,426351.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_MY.PCUnSuppress,426351.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_MY.PCUnshelve,426351.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_MY.Alarm_Fault,426351.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_MY.Shelved,426351.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_MY.Suppressed,426351.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_MY.PLCIOFault,426351.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_MY.PLCF,426351.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_MY.TAGR,426351.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_UA.Fault,426386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_UA.Faulted,426386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_UA.AlarmState,426386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_UA.FaultInAlarm,426386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UA.Alarm_EN,426386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_UA.REST,426386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_UA.ACKN,426386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_UA.MCmd_Enable,426386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UA.MCmd_Disable,426386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UA.ALRM,426386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_UA.ANUN,426386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_UA.AKED,426386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_UA.Resetable,426386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_UA.Shelve,426386.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_UA.Suppress,426386.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_UA.InputAlarm,426386.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_UA.GlobalReset,426387.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_UA.PCSuppress,426387.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_UA.PCUnSuppress,426387.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_UA.PCUnshelve,426387.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_UA.Alarm_Fault,426387.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_UA.Shelved,426387.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_UA.Suppressed,426387.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_UA.PLCIOFault,426387.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UA.PLCF,426387.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UA.TAGR,426387.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_UH.Fault,426420.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_UH.Faulted,426420.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_UH.AlarmState,426420.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_UH.FaultInAlarm,426420.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UH.Alarm_EN,426420.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_UH.REST,426420.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_UH.ACKN,426420.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_UH.MCmd_Enable,426420.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UH.MCmd_Disable,426420.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UH.ALRM,426420.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_UH.ANUN,426420.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_UH.AKED,426420.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_UH.Resetable,426420.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_UH.Shelve,426420.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_UH.Suppress,426420.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_UH.InputAlarm,426420.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_UH.GlobalReset,426421.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_UH.PCSuppress,426421.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_UH.PCUnSuppress,426421.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_UH.PCUnshelve,426421.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_UH.Alarm_Fault,426421.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_UH.Shelved,426421.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_UH.Suppressed,426421.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_UH.PLCIOFault,426421.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UH.PLCF,426421.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UH.TAGR,426421.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_UY.Fault,426456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_UY.Faulted,426456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_UY.AlarmState,426456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_UY.FaultInAlarm,426456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UY.Alarm_EN,426456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_UY.REST,426456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_UY.ACKN,426456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_UY.MCmd_Enable,426456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UY.MCmd_Disable,426456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UY.ALRM,426456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_UY.ANUN,426456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_UY.AKED,426456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_UY.Resetable,426456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_UY.Shelve,426456.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_UY.Suppress,426456.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_UY.InputAlarm,426456.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_UY.GlobalReset,426457.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_UY.PCSuppress,426457.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_UY.PCUnSuppress,426457.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_UY.PCUnshelve,426457.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_UY.Alarm_Fault,426457.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_UY.Shelved,426457.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_UY.Suppressed,426457.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_UY.PLCIOFault,426457.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UY.PLCF,426457.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_UY.TAGR,426457.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_XF.Fault,426490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_XF.Faulted,426490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_XF.AlarmState,426490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_XF.FaultInAlarm,426490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_XF.Alarm_EN,426490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_XF.REST,426490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_XF.ACKN,426490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_XF.MCmd_Enable,426490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_XF.MCmd_Disable,426490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_XF.ALRM,426490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_XF.ANUN,426490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_XF.AKED,426490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_XF.Resetable,426490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_XF.Shelve,426490.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_XF.Suppress,426490.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_XF.InputAlarm,426490.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_XF.GlobalReset,426491.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_XF.PCSuppress,426491.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_XF.PCUnSuppress,426491.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_XF.PCUnshelve,426491.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_XF.Alarm_Fault,426491.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_XF.Shelved,426491.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_XF.Suppressed,426491.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_XF.PLCIOFault,426491.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_XF.PLCF,426491.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_XF.TAGR,426491.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_2_YA.Fault,426526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_2_YA.Faulted,426526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_2_YA.AlarmState,426526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_2_YA.FaultInAlarm,426526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_YA.Alarm_EN,426526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_2_YA.REST,426526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_2_YA.ACKN,426526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_2_YA.MCmd_Enable,426526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_YA.MCmd_Disable,426526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_YA.ALRM,426526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_2_YA.ANUN,426526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_2_YA.AKED,426526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_2_YA.Resetable,426526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_2_YA.Shelve,426526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2_YA.Suppress,426526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2_YA.InputAlarm,426526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_2_YA.GlobalReset,426527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_2_YA.PCSuppress,426527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2_YA.PCUnSuppress,426527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2_YA.PCUnshelve,426527.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2_YA.Alarm_Fault,426527.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_2_YA.Shelved,426527.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_2_YA.Suppressed,426527.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_2_YA.PLCIOFault,426527.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_YA.PLCF,426527.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2_YA.TAGR,426527.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_FA.Fault,426560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_FA.Faulted,426560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_FA.AlarmState,426560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_FA.FaultInAlarm,426560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_FA.Alarm_EN,426560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_FA.REST,426560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_FA.ACKN,426560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_FA.MCmd_Enable,426560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_FA.MCmd_Disable,426560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_FA.ALRM,426560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_FA.ANUN,426560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_FA.AKED,426560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_FA.Resetable,426560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_FA.Shelve,426560.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_FA.Suppress,426560.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_FA.InputAlarm,426560.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_FA.GlobalReset,426561.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_FA.PCSuppress,426561.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_FA.PCUnSuppress,426561.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_FA.PCUnshelve,426561.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_FA.Alarm_Fault,426561.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_FA.Shelved,426561.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_FA.Suppressed,426561.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_FA.PLCIOFault,426561.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_FA.PLCF,426561.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_FA.TAGR,426561.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_MF.Fault,426596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_MF.Faulted,426596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_MF.AlarmState,426596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_MF.FaultInAlarm,426596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MF.Alarm_EN,426596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_MF.REST,426596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_MF.ACKN,426596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_MF.MCmd_Enable,426596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MF.MCmd_Disable,426596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MF.ALRM,426596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_MF.ANUN,426596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_MF.AKED,426596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_MF.Resetable,426596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_MF.Shelve,426596.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_MF.Suppress,426596.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_MF.InputAlarm,426596.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_MF.GlobalReset,426597.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_MF.PCSuppress,426597.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_MF.PCUnSuppress,426597.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_MF.PCUnshelve,426597.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_MF.Alarm_Fault,426597.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_MF.Shelved,426597.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_MF.Suppressed,426597.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_MF.PLCIOFault,426597.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_MF.PLCF,426597.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_MF.TAGR,426597.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_MY.Fault,426630.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_MY.Faulted,426630.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_MY.AlarmState,426630.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_MY.FaultInAlarm,426630.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MY.Alarm_EN,426630.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_MY.REST,426630.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_MY.ACKN,426630.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_MY.MCmd_Enable,426630.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MY.MCmd_Disable,426630.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MY.ALRM,426630.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_MY.ANUN,426630.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_MY.AKED,426630.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_MY.Resetable,426630.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_MY.Shelve,426630.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_MY.Suppress,426630.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_MY.InputAlarm,426630.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_MY.GlobalReset,426631.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_MY.PCSuppress,426631.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_MY.PCUnSuppress,426631.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_MY.PCUnshelve,426631.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_MY.Alarm_Fault,426631.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_MY.Shelved,426631.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_MY.Suppressed,426631.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_MY.PLCIOFault,426631.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_MY.PLCF,426631.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_MY.TAGR,426631.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_UA.Fault,426666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_UA.Faulted,426666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_UA.AlarmState,426666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_UA.FaultInAlarm,426666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UA.Alarm_EN,426666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_UA.REST,426666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_UA.ACKN,426666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_UA.MCmd_Enable,426666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UA.MCmd_Disable,426666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UA.ALRM,426666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_UA.ANUN,426666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_UA.AKED,426666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_UA.Resetable,426666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_UA.Shelve,426666.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_UA.Suppress,426666.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_UA.InputAlarm,426666.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_UA.GlobalReset,426667.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_UA.PCSuppress,426667.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_UA.PCUnSuppress,426667.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_UA.PCUnshelve,426667.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_UA.Alarm_Fault,426667.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_UA.Shelved,426667.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_UA.Suppressed,426667.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_UA.PLCIOFault,426667.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UA.PLCF,426667.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UA.TAGR,426667.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_UH.Fault,426700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_UH.Faulted,426700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_UH.AlarmState,426700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_UH.FaultInAlarm,426700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UH.Alarm_EN,426700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_UH.REST,426700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_UH.ACKN,426700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_UH.MCmd_Enable,426700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UH.MCmd_Disable,426700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UH.ALRM,426700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_UH.ANUN,426700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_UH.AKED,426700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_UH.Resetable,426700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_UH.Shelve,426700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_UH.Suppress,426700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_UH.InputAlarm,426700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_UH.GlobalReset,426701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_UH.PCSuppress,426701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_UH.PCUnSuppress,426701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_UH.PCUnshelve,426701.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_UH.Alarm_Fault,426701.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_UH.Shelved,426701.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_UH.Suppressed,426701.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_UH.PLCIOFault,426701.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UH.PLCF,426701.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UH.TAGR,426701.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_UY.Fault,426736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_UY.Faulted,426736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_UY.AlarmState,426736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_UY.FaultInAlarm,426736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UY.Alarm_EN,426736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_UY.REST,426736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_UY.ACKN,426736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_UY.MCmd_Enable,426736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UY.MCmd_Disable,426736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UY.ALRM,426736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_UY.ANUN,426736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_UY.AKED,426736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_UY.Resetable,426736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_UY.Shelve,426736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_UY.Suppress,426736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_UY.InputAlarm,426736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_UY.GlobalReset,426737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_UY.PCSuppress,426737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_UY.PCUnSuppress,426737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_UY.PCUnshelve,426737.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_UY.Alarm_Fault,426737.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_UY.Shelved,426737.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_UY.Suppressed,426737.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_UY.PLCIOFault,426737.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UY.PLCF,426737.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_UY.TAGR,426737.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_XF.Fault,426770.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_XF.Faulted,426770.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_XF.AlarmState,426770.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_XF.FaultInAlarm,426770.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_XF.Alarm_EN,426770.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_XF.REST,426770.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_XF.ACKN,426770.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_XF.MCmd_Enable,426770.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_XF.MCmd_Disable,426770.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_XF.ALRM,426770.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_XF.ANUN,426770.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_XF.AKED,426770.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_XF.Resetable,426770.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_XF.Shelve,426770.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_XF.Suppress,426770.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_XF.InputAlarm,426770.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_XF.GlobalReset,426771.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_XF.PCSuppress,426771.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_XF.PCUnSuppress,426771.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_XF.PCUnshelve,426771.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_XF.Alarm_Fault,426771.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_XF.Shelved,426771.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_XF.Suppressed,426771.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_XF.PLCIOFault,426771.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_XF.PLCF,426771.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_XF.TAGR,426771.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_3_YA.Fault,426806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_3_YA.Faulted,426806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_3_YA.AlarmState,426806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_3_YA.FaultInAlarm,426806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_YA.Alarm_EN,426806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_3_YA.REST,426806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_3_YA.ACKN,426806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_3_YA.MCmd_Enable,426806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_YA.MCmd_Disable,426806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_YA.ALRM,426806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_3_YA.ANUN,426806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_3_YA.AKED,426806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_3_YA.Resetable,426806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_3_YA.Shelve,426806.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3_YA.Suppress,426806.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3_YA.InputAlarm,426806.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_3_YA.GlobalReset,426807.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_3_YA.PCSuppress,426807.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3_YA.PCUnSuppress,426807.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3_YA.PCUnshelve,426807.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3_YA.Alarm_Fault,426807.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_3_YA.Shelved,426807.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_3_YA.Suppressed,426807.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_3_YA.PLCIOFault,426807.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_YA.PLCF,426807.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3_YA.TAGR,426807.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_FA.Fault,426840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_FA.Faulted,426840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_FA.AlarmState,426840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_FA.FaultInAlarm,426840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_FA.Alarm_EN,426840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_FA.REST,426840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_FA.ACKN,426840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_FA.MCmd_Enable,426840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_FA.MCmd_Disable,426840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_FA.ALRM,426840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_FA.ANUN,426840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_FA.AKED,426840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_FA.Resetable,426840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_FA.Shelve,426840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_FA.Suppress,426840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_FA.InputAlarm,426840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_FA.GlobalReset,426841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_FA.PCSuppress,426841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_FA.PCUnSuppress,426841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_FA.PCUnshelve,426841.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_FA.Alarm_Fault,426841.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_FA.Shelved,426841.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_FA.Suppressed,426841.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_FA.PLCIOFault,426841.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_FA.PLCF,426841.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_FA.TAGR,426841.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_MF.Fault,426876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_MF.Faulted,426876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_MF.AlarmState,426876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_MF.FaultInAlarm,426876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MF.Alarm_EN,426876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_MF.REST,426876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_MF.ACKN,426876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_MF.MCmd_Enable,426876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MF.MCmd_Disable,426876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MF.ALRM,426876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_MF.ANUN,426876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_MF.AKED,426876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_MF.Resetable,426876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_MF.Shelve,426876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_MF.Suppress,426876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_MF.InputAlarm,426876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_MF.GlobalReset,426877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_MF.PCSuppress,426877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_MF.PCUnSuppress,426877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_MF.PCUnshelve,426877.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_MF.Alarm_Fault,426877.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_MF.Shelved,426877.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_MF.Suppressed,426877.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_MF.PLCIOFault,426877.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_MF.PLCF,426877.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_MF.TAGR,426877.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_MY.Fault,426910.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_MY.Faulted,426910.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_MY.AlarmState,426910.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_MY.FaultInAlarm,426910.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MY.Alarm_EN,426910.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_MY.REST,426910.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_MY.ACKN,426910.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_MY.MCmd_Enable,426910.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MY.MCmd_Disable,426910.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MY.ALRM,426910.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_MY.ANUN,426910.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_MY.AKED,426910.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_MY.Resetable,426910.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_MY.Shelve,426910.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_MY.Suppress,426910.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_MY.InputAlarm,426910.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_MY.GlobalReset,426911.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_MY.PCSuppress,426911.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_MY.PCUnSuppress,426911.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_MY.PCUnshelve,426911.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_MY.Alarm_Fault,426911.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_MY.Shelved,426911.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_MY.Suppressed,426911.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_MY.PLCIOFault,426911.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_MY.PLCF,426911.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_MY.TAGR,426911.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_UA.Fault,426946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_UA.Faulted,426946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_UA.AlarmState,426946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_UA.FaultInAlarm,426946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UA.Alarm_EN,426946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_UA.REST,426946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_UA.ACKN,426946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_UA.MCmd_Enable,426946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UA.MCmd_Disable,426946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UA.ALRM,426946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_UA.ANUN,426946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_UA.AKED,426946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_UA.Resetable,426946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_UA.Shelve,426946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_UA.Suppress,426946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_UA.InputAlarm,426946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_UA.GlobalReset,426947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_UA.PCSuppress,426947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_UA.PCUnSuppress,426947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_UA.PCUnshelve,426947.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_UA.Alarm_Fault,426947.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_UA.Shelved,426947.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_UA.Suppressed,426947.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_UA.PLCIOFault,426947.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UA.PLCF,426947.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UA.TAGR,426947.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_UH.Fault,426980.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_UH.Faulted,426980.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_UH.AlarmState,426980.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_UH.FaultInAlarm,426980.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UH.Alarm_EN,426980.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_UH.REST,426980.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_UH.ACKN,426980.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_UH.MCmd_Enable,426980.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UH.MCmd_Disable,426980.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UH.ALRM,426980.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_UH.ANUN,426980.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_UH.AKED,426980.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_UH.Resetable,426980.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_UH.Shelve,426980.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_UH.Suppress,426980.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_UH.InputAlarm,426980.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_UH.GlobalReset,426981.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_UH.PCSuppress,426981.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_UH.PCUnSuppress,426981.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_UH.PCUnshelve,426981.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_UH.Alarm_Fault,426981.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_UH.Shelved,426981.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_UH.Suppressed,426981.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_UH.PLCIOFault,426981.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UH.PLCF,426981.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UH.TAGR,426981.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_UY.Fault,427016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_UY.Faulted,427016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_UY.AlarmState,427016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_UY.FaultInAlarm,427016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UY.Alarm_EN,427016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_UY.REST,427016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_UY.ACKN,427016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_UY.MCmd_Enable,427016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UY.MCmd_Disable,427016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UY.ALRM,427016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_UY.ANUN,427016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_UY.AKED,427016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_UY.Resetable,427016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_UY.Shelve,427016.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_UY.Suppress,427016.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_UY.InputAlarm,427016.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_UY.GlobalReset,427017.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_UY.PCSuppress,427017.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_UY.PCUnSuppress,427017.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_UY.PCUnshelve,427017.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_UY.Alarm_Fault,427017.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_UY.Shelved,427017.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_UY.Suppressed,427017.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_UY.PLCIOFault,427017.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UY.PLCF,427017.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_UY.TAGR,427017.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_XF.Fault,427050.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_XF.Faulted,427050.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_XF.AlarmState,427050.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_XF.FaultInAlarm,427050.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_XF.Alarm_EN,427050.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_XF.REST,427050.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_XF.ACKN,427050.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_XF.MCmd_Enable,427050.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_XF.MCmd_Disable,427050.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_XF.ALRM,427050.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_XF.ANUN,427050.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_XF.AKED,427050.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_XF.Resetable,427050.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_XF.Shelve,427050.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_XF.Suppress,427050.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_XF.InputAlarm,427050.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_XF.GlobalReset,427051.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_XF.PCSuppress,427051.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_XF.PCUnSuppress,427051.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_XF.PCUnshelve,427051.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_XF.Alarm_Fault,427051.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_XF.Shelved,427051.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_XF.Suppressed,427051.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_XF.PLCIOFault,427051.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_XF.PLCF,427051.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_XF.TAGR,427051.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_4_YA.Fault,427086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_4_YA.Faulted,427086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_4_YA.AlarmState,427086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_4_YA.FaultInAlarm,427086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_YA.Alarm_EN,427086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_4_YA.REST,427086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_4_YA.ACKN,427086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_4_YA.MCmd_Enable,427086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_YA.MCmd_Disable,427086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_YA.ALRM,427086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_4_YA.ANUN,427086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_4_YA.AKED,427086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_4_YA.Resetable,427086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_4_YA.Shelve,427086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4_YA.Suppress,427086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4_YA.InputAlarm,427086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_4_YA.GlobalReset,427087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_4_YA.PCSuppress,427087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4_YA.PCUnSuppress,427087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4_YA.PCUnshelve,427087.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4_YA.Alarm_Fault,427087.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_4_YA.Shelved,427087.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_4_YA.Suppressed,427087.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_4_YA.PLCIOFault,427087.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_YA.PLCF,427087.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4_YA.TAGR,427087.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_FA.Fault,427120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_FA.Faulted,427120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_FA.AlarmState,427120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_FA.FaultInAlarm,427120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_FA.Alarm_EN,427120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_FA.REST,427120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_FA.ACKN,427120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_FA.MCmd_Enable,427120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_FA.MCmd_Disable,427120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_FA.ALRM,427120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_FA.ANUN,427120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_FA.AKED,427120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_FA.Resetable,427120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_FA.Shelve,427120.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_FA.Suppress,427120.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_FA.InputAlarm,427120.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_FA.GlobalReset,427121.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_FA.PCSuppress,427121.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_FA.PCUnSuppress,427121.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_FA.PCUnshelve,427121.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_FA.Alarm_Fault,427121.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_FA.Shelved,427121.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_FA.Suppressed,427121.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_FA.PLCIOFault,427121.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_FA.PLCF,427121.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_FA.TAGR,427121.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_MF.Fault,427156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_MF.Faulted,427156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_MF.AlarmState,427156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_MF.FaultInAlarm,427156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MF.Alarm_EN,427156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_MF.REST,427156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_MF.ACKN,427156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_MF.MCmd_Enable,427156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MF.MCmd_Disable,427156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MF.ALRM,427156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_MF.ANUN,427156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_MF.AKED,427156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_MF.Resetable,427156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_MF.Shelve,427156.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_MF.Suppress,427156.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_MF.InputAlarm,427156.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_MF.GlobalReset,427157.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_MF.PCSuppress,427157.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_MF.PCUnSuppress,427157.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_MF.PCUnshelve,427157.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_MF.Alarm_Fault,427157.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_MF.Shelved,427157.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_MF.Suppressed,427157.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_MF.PLCIOFault,427157.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_MF.PLCF,427157.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_MF.TAGR,427157.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_MY.Fault,427190.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_MY.Faulted,427190.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_MY.AlarmState,427190.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_MY.FaultInAlarm,427190.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MY.Alarm_EN,427190.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_MY.REST,427190.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_MY.ACKN,427190.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_MY.MCmd_Enable,427190.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MY.MCmd_Disable,427190.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MY.ALRM,427190.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_MY.ANUN,427190.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_MY.AKED,427190.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_MY.Resetable,427190.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_MY.Shelve,427190.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_MY.Suppress,427190.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_MY.InputAlarm,427190.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_MY.GlobalReset,427191.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_MY.PCSuppress,427191.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_MY.PCUnSuppress,427191.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_MY.PCUnshelve,427191.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_MY.Alarm_Fault,427191.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_MY.Shelved,427191.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_MY.Suppressed,427191.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_MY.PLCIOFault,427191.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_MY.PLCF,427191.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_MY.TAGR,427191.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_UA.Fault,427226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_UA.Faulted,427226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_UA.AlarmState,427226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_UA.FaultInAlarm,427226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UA.Alarm_EN,427226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_UA.REST,427226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_UA.ACKN,427226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_UA.MCmd_Enable,427226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UA.MCmd_Disable,427226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UA.ALRM,427226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_UA.ANUN,427226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_UA.AKED,427226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_UA.Resetable,427226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_UA.Shelve,427226.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_UA.Suppress,427226.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_UA.InputAlarm,427226.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_UA.GlobalReset,427227.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_UA.PCSuppress,427227.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_UA.PCUnSuppress,427227.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_UA.PCUnshelve,427227.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_UA.Alarm_Fault,427227.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_UA.Shelved,427227.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_UA.Suppressed,427227.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_UA.PLCIOFault,427227.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UA.PLCF,427227.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UA.TAGR,427227.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_UH.Fault,427260.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_UH.Faulted,427260.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_UH.AlarmState,427260.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_UH.FaultInAlarm,427260.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UH.Alarm_EN,427260.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_UH.REST,427260.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_UH.ACKN,427260.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_UH.MCmd_Enable,427260.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UH.MCmd_Disable,427260.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UH.ALRM,427260.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_UH.ANUN,427260.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_UH.AKED,427260.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_UH.Resetable,427260.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_UH.Shelve,427260.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_UH.Suppress,427260.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_UH.InputAlarm,427260.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_UH.GlobalReset,427261.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_UH.PCSuppress,427261.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_UH.PCUnSuppress,427261.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_UH.PCUnshelve,427261.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_UH.Alarm_Fault,427261.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_UH.Shelved,427261.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_UH.Suppressed,427261.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_UH.PLCIOFault,427261.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UH.PLCF,427261.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UH.TAGR,427261.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_UY.Fault,427296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_UY.Faulted,427296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_UY.AlarmState,427296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_UY.FaultInAlarm,427296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UY.Alarm_EN,427296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_UY.REST,427296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_UY.ACKN,427296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_UY.MCmd_Enable,427296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UY.MCmd_Disable,427296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UY.ALRM,427296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_UY.ANUN,427296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_UY.AKED,427296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_UY.Resetable,427296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_UY.Shelve,427296.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_UY.Suppress,427296.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_UY.InputAlarm,427296.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_UY.GlobalReset,427297.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_UY.PCSuppress,427297.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_UY.PCUnSuppress,427297.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_UY.PCUnshelve,427297.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_UY.Alarm_Fault,427297.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_UY.Shelved,427297.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_UY.Suppressed,427297.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_UY.PLCIOFault,427297.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UY.PLCF,427297.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_UY.TAGR,427297.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_XF.Fault,427330.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_XF.Faulted,427330.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_XF.AlarmState,427330.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_XF.FaultInAlarm,427330.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_XF.Alarm_EN,427330.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_XF.REST,427330.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_XF.ACKN,427330.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_XF.MCmd_Enable,427330.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_XF.MCmd_Disable,427330.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_XF.ALRM,427330.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_XF.ANUN,427330.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_XF.AKED,427330.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_XF.Resetable,427330.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_XF.Shelve,427330.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_XF.Suppress,427330.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_XF.InputAlarm,427330.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_XF.GlobalReset,427331.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_XF.PCSuppress,427331.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_XF.PCUnSuppress,427331.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_XF.PCUnshelve,427331.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_XF.Alarm_Fault,427331.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_XF.Shelved,427331.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_XF.Suppressed,427331.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_XF.PLCIOFault,427331.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_XF.PLCF,427331.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_XF.TAGR,427331.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_5_YA.Fault,427366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_5_YA.Faulted,427366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_5_YA.AlarmState,427366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_5_YA.FaultInAlarm,427366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_YA.Alarm_EN,427366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_5_YA.REST,427366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_5_YA.ACKN,427366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_5_YA.MCmd_Enable,427366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_YA.MCmd_Disable,427366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_YA.ALRM,427366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_5_YA.ANUN,427366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_5_YA.AKED,427366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_5_YA.Resetable,427366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_5_YA.Shelve,427366.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5_YA.Suppress,427366.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5_YA.InputAlarm,427366.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_5_YA.GlobalReset,427367.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_5_YA.PCSuppress,427367.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5_YA.PCUnSuppress,427367.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5_YA.PCUnshelve,427367.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5_YA.Alarm_Fault,427367.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_5_YA.Shelved,427367.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_5_YA.Suppressed,427367.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_5_YA.PLCIOFault,427367.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_YA.PLCF,427367.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5_YA.TAGR,427367.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_FA.Fault,427400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_FA.Faulted,427400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_FA.AlarmState,427400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_FA.FaultInAlarm,427400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_FA.Alarm_EN,427400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_FA.REST,427400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_FA.ACKN,427400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_FA.MCmd_Enable,427400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_FA.MCmd_Disable,427400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_FA.ALRM,427400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_FA.ANUN,427400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_FA.AKED,427400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_FA.Resetable,427400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_FA.Shelve,427400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_FA.Suppress,427400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_FA.InputAlarm,427400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_FA.GlobalReset,427401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_FA.PCSuppress,427401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_FA.PCUnSuppress,427401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_FA.PCUnshelve,427401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_FA.Alarm_Fault,427401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_FA.Shelved,427401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_FA.Suppressed,427401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_FA.PLCIOFault,427401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_FA.PLCF,427401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_FA.TAGR,427401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_MF.Fault,427436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_MF.Faulted,427436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_MF.AlarmState,427436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_MF.FaultInAlarm,427436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MF.Alarm_EN,427436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_MF.REST,427436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_MF.ACKN,427436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_MF.MCmd_Enable,427436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MF.MCmd_Disable,427436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MF.ALRM,427436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_MF.ANUN,427436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_MF.AKED,427436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_MF.Resetable,427436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_MF.Shelve,427436.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_MF.Suppress,427436.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_MF.InputAlarm,427436.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_MF.GlobalReset,427437.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_MF.PCSuppress,427437.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_MF.PCUnSuppress,427437.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_MF.PCUnshelve,427437.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_MF.Alarm_Fault,427437.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_MF.Shelved,427437.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_MF.Suppressed,427437.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_MF.PLCIOFault,427437.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_MF.PLCF,427437.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_MF.TAGR,427437.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_MY.Fault,427470.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_MY.Faulted,427470.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_MY.AlarmState,427470.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_MY.FaultInAlarm,427470.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MY.Alarm_EN,427470.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_MY.REST,427470.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_MY.ACKN,427470.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_MY.MCmd_Enable,427470.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MY.MCmd_Disable,427470.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MY.ALRM,427470.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_MY.ANUN,427470.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_MY.AKED,427470.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_MY.Resetable,427470.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_MY.Shelve,427470.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_MY.Suppress,427470.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_MY.InputAlarm,427470.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_MY.GlobalReset,427471.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_MY.PCSuppress,427471.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_MY.PCUnSuppress,427471.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_MY.PCUnshelve,427471.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_MY.Alarm_Fault,427471.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_MY.Shelved,427471.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_MY.Suppressed,427471.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_MY.PLCIOFault,427471.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_MY.PLCF,427471.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_MY.TAGR,427471.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_UA.Fault,427506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_UA.Faulted,427506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_UA.AlarmState,427506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_UA.FaultInAlarm,427506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UA.Alarm_EN,427506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_UA.REST,427506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_UA.ACKN,427506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_UA.MCmd_Enable,427506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UA.MCmd_Disable,427506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UA.ALRM,427506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_UA.ANUN,427506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_UA.AKED,427506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_UA.Resetable,427506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_UA.Shelve,427506.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_UA.Suppress,427506.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_UA.InputAlarm,427506.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_UA.GlobalReset,427507.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_UA.PCSuppress,427507.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_UA.PCUnSuppress,427507.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_UA.PCUnshelve,427507.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_UA.Alarm_Fault,427507.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_UA.Shelved,427507.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_UA.Suppressed,427507.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_UA.PLCIOFault,427507.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UA.PLCF,427507.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UA.TAGR,427507.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_UH.Fault,427540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_UH.Faulted,427540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_UH.AlarmState,427540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_UH.FaultInAlarm,427540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UH.Alarm_EN,427540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_UH.REST,427540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_UH.ACKN,427540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_UH.MCmd_Enable,427540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UH.MCmd_Disable,427540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UH.ALRM,427540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_UH.ANUN,427540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_UH.AKED,427540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_UH.Resetable,427540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_UH.Shelve,427540.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_UH.Suppress,427540.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_UH.InputAlarm,427540.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_UH.GlobalReset,427541.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_UH.PCSuppress,427541.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_UH.PCUnSuppress,427541.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_UH.PCUnshelve,427541.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_UH.Alarm_Fault,427541.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_UH.Shelved,427541.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_UH.Suppressed,427541.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_UH.PLCIOFault,427541.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UH.PLCF,427541.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UH.TAGR,427541.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_UY.Fault,427576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_UY.Faulted,427576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_UY.AlarmState,427576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_UY.FaultInAlarm,427576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UY.Alarm_EN,427576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_UY.REST,427576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_UY.ACKN,427576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_UY.MCmd_Enable,427576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UY.MCmd_Disable,427576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UY.ALRM,427576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_UY.ANUN,427576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_UY.AKED,427576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_UY.Resetable,427576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_UY.Shelve,427576.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_UY.Suppress,427576.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_UY.InputAlarm,427576.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_UY.GlobalReset,427577.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_UY.PCSuppress,427577.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_UY.PCUnSuppress,427577.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_UY.PCUnshelve,427577.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_UY.Alarm_Fault,427577.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_UY.Shelved,427577.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_UY.Suppressed,427577.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_UY.PLCIOFault,427577.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UY.PLCF,427577.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_UY.TAGR,427577.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_XF.Fault,427610.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_XF.Faulted,427610.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_XF.AlarmState,427610.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_XF.FaultInAlarm,427610.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_XF.Alarm_EN,427610.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_XF.REST,427610.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_XF.ACKN,427610.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_XF.MCmd_Enable,427610.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_XF.MCmd_Disable,427610.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_XF.ALRM,427610.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_XF.ANUN,427610.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_XF.AKED,427610.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_XF.Resetable,427610.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_XF.Shelve,427610.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_XF.Suppress,427610.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_XF.InputAlarm,427610.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_XF.GlobalReset,427611.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_XF.PCSuppress,427611.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_XF.PCUnSuppress,427611.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_XF.PCUnshelve,427611.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_XF.Alarm_Fault,427611.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_XF.Shelved,427611.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_XF.Suppressed,427611.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_XF.PLCIOFault,427611.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_XF.PLCF,427611.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_XF.TAGR,427611.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_6_YA.Fault,427646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_6_YA.Faulted,427646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_6_YA.AlarmState,427646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_6_YA.FaultInAlarm,427646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_YA.Alarm_EN,427646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_6_YA.REST,427646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_6_YA.ACKN,427646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_6_YA.MCmd_Enable,427646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_YA.MCmd_Disable,427646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_YA.ALRM,427646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_6_YA.ANUN,427646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_6_YA.AKED,427646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_6_YA.Resetable,427646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_6_YA.Shelve,427646.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6_YA.Suppress,427646.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6_YA.InputAlarm,427646.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_6_YA.GlobalReset,427647.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_6_YA.PCSuppress,427647.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6_YA.PCUnSuppress,427647.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6_YA.PCUnshelve,427647.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6_YA.Alarm_Fault,427647.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_6_YA.Shelved,427647.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_6_YA.Suppressed,427647.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_6_YA.PLCIOFault,427647.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_YA.PLCF,427647.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6_YA.TAGR,427647.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_FA.Fault,427680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_FA.Faulted,427680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_FA.AlarmState,427680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_FA.FaultInAlarm,427680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_FA.Alarm_EN,427680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_FA.REST,427680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_FA.ACKN,427680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_FA.MCmd_Enable,427680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_FA.MCmd_Disable,427680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_FA.ALRM,427680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_FA.ANUN,427680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_FA.AKED,427680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_FA.Resetable,427680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_FA.Shelve,427680.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_FA.Suppress,427680.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_FA.InputAlarm,427680.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_FA.GlobalReset,427681.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_FA.PCSuppress,427681.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_FA.PCUnSuppress,427681.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_FA.PCUnshelve,427681.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_FA.Alarm_Fault,427681.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_FA.Shelved,427681.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_FA.Suppressed,427681.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_FA.PLCIOFault,427681.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_FA.PLCF,427681.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_FA.TAGR,427681.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_MF.Fault,427716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_MF.Faulted,427716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_MF.AlarmState,427716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_MF.FaultInAlarm,427716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MF.Alarm_EN,427716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_MF.REST,427716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_MF.ACKN,427716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_MF.MCmd_Enable,427716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MF.MCmd_Disable,427716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MF.ALRM,427716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_MF.ANUN,427716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_MF.AKED,427716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_MF.Resetable,427716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_MF.Shelve,427716.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_MF.Suppress,427716.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_MF.InputAlarm,427716.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_MF.GlobalReset,427717.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_MF.PCSuppress,427717.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_MF.PCUnSuppress,427717.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_MF.PCUnshelve,427717.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_MF.Alarm_Fault,427717.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_MF.Shelved,427717.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_MF.Suppressed,427717.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_MF.PLCIOFault,427717.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_MF.PLCF,427717.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_MF.TAGR,427717.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_MY.Fault,427750.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_MY.Faulted,427750.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_MY.AlarmState,427750.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_MY.FaultInAlarm,427750.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MY.Alarm_EN,427750.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_MY.REST,427750.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_MY.ACKN,427750.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_MY.MCmd_Enable,427750.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MY.MCmd_Disable,427750.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MY.ALRM,427750.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_MY.ANUN,427750.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_MY.AKED,427750.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_MY.Resetable,427750.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_MY.Shelve,427750.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_MY.Suppress,427750.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_MY.InputAlarm,427750.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_MY.GlobalReset,427751.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_MY.PCSuppress,427751.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_MY.PCUnSuppress,427751.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_MY.PCUnshelve,427751.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_MY.Alarm_Fault,427751.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_MY.Shelved,427751.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_MY.Suppressed,427751.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_MY.PLCIOFault,427751.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_MY.PLCF,427751.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_MY.TAGR,427751.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_UA.Fault,427786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_UA.Faulted,427786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_UA.AlarmState,427786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_UA.FaultInAlarm,427786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UA.Alarm_EN,427786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_UA.REST,427786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_UA.ACKN,427786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_UA.MCmd_Enable,427786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UA.MCmd_Disable,427786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UA.ALRM,427786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_UA.ANUN,427786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_UA.AKED,427786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_UA.Resetable,427786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_UA.Shelve,427786.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_UA.Suppress,427786.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_UA.InputAlarm,427786.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_UA.GlobalReset,427787.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_UA.PCSuppress,427787.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_UA.PCUnSuppress,427787.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_UA.PCUnshelve,427787.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_UA.Alarm_Fault,427787.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_UA.Shelved,427787.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_UA.Suppressed,427787.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_UA.PLCIOFault,427787.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UA.PLCF,427787.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UA.TAGR,427787.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_UH.Fault,427820.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_UH.Faulted,427820.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_UH.AlarmState,427820.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_UH.FaultInAlarm,427820.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UH.Alarm_EN,427820.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_UH.REST,427820.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_UH.ACKN,427820.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_UH.MCmd_Enable,427820.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UH.MCmd_Disable,427820.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UH.ALRM,427820.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_UH.ANUN,427820.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_UH.AKED,427820.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_UH.Resetable,427820.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_UH.Shelve,427820.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_UH.Suppress,427820.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_UH.InputAlarm,427820.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_UH.GlobalReset,427821.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_UH.PCSuppress,427821.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_UH.PCUnSuppress,427821.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_UH.PCUnshelve,427821.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_UH.Alarm_Fault,427821.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_UH.Shelved,427821.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_UH.Suppressed,427821.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_UH.PLCIOFault,427821.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UH.PLCF,427821.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UH.TAGR,427821.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_UY.Fault,427856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_UY.Faulted,427856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_UY.AlarmState,427856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_UY.FaultInAlarm,427856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UY.Alarm_EN,427856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_UY.REST,427856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_UY.ACKN,427856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_UY.MCmd_Enable,427856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UY.MCmd_Disable,427856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UY.ALRM,427856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_UY.ANUN,427856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_UY.AKED,427856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_UY.Resetable,427856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_UY.Shelve,427856.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_UY.Suppress,427856.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_UY.InputAlarm,427856.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_UY.GlobalReset,427857.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_UY.PCSuppress,427857.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_UY.PCUnSuppress,427857.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_UY.PCUnshelve,427857.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_UY.Alarm_Fault,427857.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_UY.Shelved,427857.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_UY.Suppressed,427857.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_UY.PLCIOFault,427857.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UY.PLCF,427857.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_UY.TAGR,427857.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_XF.Fault,427890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_XF.Faulted,427890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_XF.AlarmState,427890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_XF.FaultInAlarm,427890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_XF.Alarm_EN,427890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_XF.REST,427890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_XF.ACKN,427890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_XF.MCmd_Enable,427890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_XF.MCmd_Disable,427890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_XF.ALRM,427890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_XF.ANUN,427890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_XF.AKED,427890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_XF.Resetable,427890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_XF.Shelve,427890.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_XF.Suppress,427890.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_XF.InputAlarm,427890.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_XF.GlobalReset,427891.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_XF.PCSuppress,427891.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_XF.PCUnSuppress,427891.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_XF.PCUnshelve,427891.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_XF.Alarm_Fault,427891.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_XF.Shelved,427891.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_XF.Suppressed,427891.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_XF.PLCIOFault,427891.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_XF.PLCF,427891.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_XF.TAGR,427891.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_7_YA.Fault,427926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_7_YA.Faulted,427926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_7_YA.AlarmState,427926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_7_YA.FaultInAlarm,427926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_YA.Alarm_EN,427926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_7_YA.REST,427926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_7_YA.ACKN,427926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_7_YA.MCmd_Enable,427926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_YA.MCmd_Disable,427926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_YA.ALRM,427926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_7_YA.ANUN,427926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_7_YA.AKED,427926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_7_YA.Resetable,427926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_7_YA.Shelve,427926.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7_YA.Suppress,427926.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7_YA.InputAlarm,427926.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_7_YA.GlobalReset,427927.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_7_YA.PCSuppress,427927.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7_YA.PCUnSuppress,427927.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7_YA.PCUnshelve,427927.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7_YA.Alarm_Fault,427927.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_7_YA.Shelved,427927.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_7_YA.Suppressed,427927.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_7_YA.PLCIOFault,427927.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_YA.PLCF,427927.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7_YA.TAGR,427927.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_FA.Fault,427960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_FA.Faulted,427960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_FA.AlarmState,427960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_FA.FaultInAlarm,427960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_FA.Alarm_EN,427960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_FA.REST,427960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_FA.ACKN,427960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_FA.MCmd_Enable,427960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_FA.MCmd_Disable,427960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_FA.ALRM,427960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_FA.ANUN,427960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_FA.AKED,427960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_FA.Resetable,427960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_FA.Shelve,427960.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_FA.Suppress,427960.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_FA.InputAlarm,427960.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_FA.GlobalReset,427961.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_FA.PCSuppress,427961.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_FA.PCUnSuppress,427961.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_FA.PCUnshelve,427961.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_FA.Alarm_Fault,427961.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_FA.Shelved,427961.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_FA.Suppressed,427961.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_FA.PLCIOFault,427961.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_FA.PLCF,427961.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_FA.TAGR,427961.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_MF.Fault,427996.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_MF.Faulted,427996.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_MF.AlarmState,427996.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_MF.FaultInAlarm,427996.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MF.Alarm_EN,427996.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_MF.REST,427996.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_MF.ACKN,427996.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_MF.MCmd_Enable,427996.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MF.MCmd_Disable,427996.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MF.ALRM,427996.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_MF.ANUN,427996.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_MF.AKED,427996.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_MF.Resetable,427996.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_MF.Shelve,427996.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_MF.Suppress,427996.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_MF.InputAlarm,427996.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_MF.GlobalReset,427997.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_MF.PCSuppress,427997.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_MF.PCUnSuppress,427997.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_MF.PCUnshelve,427997.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_MF.Alarm_Fault,427997.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_MF.Shelved,427997.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_MF.Suppressed,427997.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_MF.PLCIOFault,427997.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_MF.PLCF,427997.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_MF.TAGR,427997.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_MY.Fault,428030.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_MY.Faulted,428030.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_MY.AlarmState,428030.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_MY.FaultInAlarm,428030.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MY.Alarm_EN,428030.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_MY.REST,428030.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_MY.ACKN,428030.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_MY.MCmd_Enable,428030.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MY.MCmd_Disable,428030.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MY.ALRM,428030.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_MY.ANUN,428030.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_MY.AKED,428030.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_MY.Resetable,428030.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_MY.Shelve,428030.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_MY.Suppress,428030.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_MY.InputAlarm,428030.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_MY.GlobalReset,428031.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_MY.PCSuppress,428031.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_MY.PCUnSuppress,428031.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_MY.PCUnshelve,428031.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_MY.Alarm_Fault,428031.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_MY.Shelved,428031.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_MY.Suppressed,428031.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_MY.PLCIOFault,428031.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_MY.PLCF,428031.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_MY.TAGR,428031.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_UA.Fault,428066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_UA.Faulted,428066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_UA.AlarmState,428066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_UA.FaultInAlarm,428066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UA.Alarm_EN,428066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_UA.REST,428066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_UA.ACKN,428066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_UA.MCmd_Enable,428066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UA.MCmd_Disable,428066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UA.ALRM,428066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_UA.ANUN,428066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_UA.AKED,428066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_UA.Resetable,428066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_UA.Shelve,428066.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_UA.Suppress,428066.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_UA.InputAlarm,428066.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_UA.GlobalReset,428067.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_UA.PCSuppress,428067.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_UA.PCUnSuppress,428067.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_UA.PCUnshelve,428067.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_UA.Alarm_Fault,428067.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_UA.Shelved,428067.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_UA.Suppressed,428067.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_UA.PLCIOFault,428067.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UA.PLCF,428067.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UA.TAGR,428067.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_UH.Fault,428100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_UH.Faulted,428100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_UH.AlarmState,428100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_UH.FaultInAlarm,428100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UH.Alarm_EN,428100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_UH.REST,428100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_UH.ACKN,428100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_UH.MCmd_Enable,428100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UH.MCmd_Disable,428100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UH.ALRM,428100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_UH.ANUN,428100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_UH.AKED,428100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_UH.Resetable,428100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_UH.Shelve,428100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_UH.Suppress,428100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_UH.InputAlarm,428100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_UH.GlobalReset,428101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_UH.PCSuppress,428101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_UH.PCUnSuppress,428101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_UH.PCUnshelve,428101.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_UH.Alarm_Fault,428101.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_UH.Shelved,428101.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_UH.Suppressed,428101.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_UH.PLCIOFault,428101.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UH.PLCF,428101.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UH.TAGR,428101.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_UY.Fault,428136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_UY.Faulted,428136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_UY.AlarmState,428136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_UY.FaultInAlarm,428136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UY.Alarm_EN,428136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_UY.REST,428136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_UY.ACKN,428136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_UY.MCmd_Enable,428136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UY.MCmd_Disable,428136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UY.ALRM,428136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_UY.ANUN,428136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_UY.AKED,428136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_UY.Resetable,428136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_UY.Shelve,428136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_UY.Suppress,428136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_UY.InputAlarm,428136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_UY.GlobalReset,428137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_UY.PCSuppress,428137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_UY.PCUnSuppress,428137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_UY.PCUnshelve,428137.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_UY.Alarm_Fault,428137.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_UY.Shelved,428137.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_UY.Suppressed,428137.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_UY.PLCIOFault,428137.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UY.PLCF,428137.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_UY.TAGR,428137.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_XF.Fault,428170.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_XF.Faulted,428170.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_XF.AlarmState,428170.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_XF.FaultInAlarm,428170.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_XF.Alarm_EN,428170.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_XF.REST,428170.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_XF.ACKN,428170.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_XF.MCmd_Enable,428170.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_XF.MCmd_Disable,428170.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_XF.ALRM,428170.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_XF.ANUN,428170.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_XF.AKED,428170.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_XF.Resetable,428170.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_XF.Shelve,428170.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_XF.Suppress,428170.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_XF.InputAlarm,428170.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_XF.GlobalReset,428171.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_XF.PCSuppress,428171.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_XF.PCUnSuppress,428171.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_XF.PCUnshelve,428171.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_XF.Alarm_Fault,428171.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_XF.Shelved,428171.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_XF.Suppressed,428171.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_XF.PLCIOFault,428171.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_XF.PLCF,428171.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_XF.TAGR,428171.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_8_YA.Fault,428206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_8_YA.Faulted,428206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_8_YA.AlarmState,428206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_8_YA.FaultInAlarm,428206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_YA.Alarm_EN,428206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_8_YA.REST,428206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_8_YA.ACKN,428206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_8_YA.MCmd_Enable,428206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_YA.MCmd_Disable,428206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_YA.ALRM,428206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_8_YA.ANUN,428206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_8_YA.AKED,428206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_8_YA.Resetable,428206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_8_YA.Shelve,428206.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8_YA.Suppress,428206.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8_YA.InputAlarm,428206.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_8_YA.GlobalReset,428207.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_8_YA.PCSuppress,428207.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8_YA.PCUnSuppress,428207.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8_YA.PCUnshelve,428207.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8_YA.Alarm_Fault,428207.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_8_YA.Shelved,428207.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_8_YA.Suppressed,428207.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_8_YA.PLCIOFault,428207.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_YA.PLCF,428207.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8_YA.TAGR,428207.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_FA.Fault,428240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_FA.Faulted,428240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_FA.AlarmState,428240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_FA.FaultInAlarm,428240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_FA.Alarm_EN,428240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_FA.REST,428240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_FA.ACKN,428240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_FA.MCmd_Enable,428240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_FA.MCmd_Disable,428240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_FA.ALRM,428240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_FA.ANUN,428240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_FA.AKED,428240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_FA.Resetable,428240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_FA.Shelve,428240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_FA.Suppress,428240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_FA.InputAlarm,428240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_FA.GlobalReset,428241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_FA.PCSuppress,428241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_FA.PCUnSuppress,428241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_FA.PCUnshelve,428241.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_FA.Alarm_Fault,428241.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_FA.Shelved,428241.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_FA.Suppressed,428241.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_FA.PLCIOFault,428241.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_FA.PLCF,428241.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_FA.TAGR,428241.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_MF.Fault,428276.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_MF.Faulted,428276.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_MF.AlarmState,428276.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_MF.FaultInAlarm,428276.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MF.Alarm_EN,428276.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_MF.REST,428276.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_MF.ACKN,428276.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_MF.MCmd_Enable,428276.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MF.MCmd_Disable,428276.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MF.ALRM,428276.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_MF.ANUN,428276.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_MF.AKED,428276.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_MF.Resetable,428276.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_MF.Shelve,428276.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_MF.Suppress,428276.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_MF.InputAlarm,428276.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_MF.GlobalReset,428277.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_MF.PCSuppress,428277.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_MF.PCUnSuppress,428277.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_MF.PCUnshelve,428277.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_MF.Alarm_Fault,428277.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_MF.Shelved,428277.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_MF.Suppressed,428277.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_MF.PLCIOFault,428277.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_MF.PLCF,428277.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_MF.TAGR,428277.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_MY.Fault,428310.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_MY.Faulted,428310.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_MY.AlarmState,428310.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_MY.FaultInAlarm,428310.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MY.Alarm_EN,428310.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_MY.REST,428310.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_MY.ACKN,428310.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_MY.MCmd_Enable,428310.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MY.MCmd_Disable,428310.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MY.ALRM,428310.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_MY.ANUN,428310.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_MY.AKED,428310.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_MY.Resetable,428310.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_MY.Shelve,428310.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_MY.Suppress,428310.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_MY.InputAlarm,428310.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_MY.GlobalReset,428311.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_MY.PCSuppress,428311.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_MY.PCUnSuppress,428311.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_MY.PCUnshelve,428311.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_MY.Alarm_Fault,428311.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_MY.Shelved,428311.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_MY.Suppressed,428311.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_MY.PLCIOFault,428311.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_MY.PLCF,428311.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_MY.TAGR,428311.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_UA.Fault,428346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_UA.Faulted,428346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_UA.AlarmState,428346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_UA.FaultInAlarm,428346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UA.Alarm_EN,428346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_UA.REST,428346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_UA.ACKN,428346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_UA.MCmd_Enable,428346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UA.MCmd_Disable,428346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UA.ALRM,428346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_UA.ANUN,428346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_UA.AKED,428346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_UA.Resetable,428346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_UA.Shelve,428346.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_UA.Suppress,428346.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_UA.InputAlarm,428346.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_UA.GlobalReset,428347.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_UA.PCSuppress,428347.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_UA.PCUnSuppress,428347.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_UA.PCUnshelve,428347.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_UA.Alarm_Fault,428347.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_UA.Shelved,428347.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_UA.Suppressed,428347.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_UA.PLCIOFault,428347.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UA.PLCF,428347.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UA.TAGR,428347.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_UH.Fault,428380.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_UH.Faulted,428380.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_UH.AlarmState,428380.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_UH.FaultInAlarm,428380.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UH.Alarm_EN,428380.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_UH.REST,428380.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_UH.ACKN,428380.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_UH.MCmd_Enable,428380.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UH.MCmd_Disable,428380.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UH.ALRM,428380.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_UH.ANUN,428380.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_UH.AKED,428380.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_UH.Resetable,428380.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_UH.Shelve,428380.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_UH.Suppress,428380.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_UH.InputAlarm,428380.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_UH.GlobalReset,428381.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_UH.PCSuppress,428381.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_UH.PCUnSuppress,428381.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_UH.PCUnshelve,428381.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_UH.Alarm_Fault,428381.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_UH.Shelved,428381.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_UH.Suppressed,428381.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_UH.PLCIOFault,428381.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UH.PLCF,428381.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UH.TAGR,428381.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_UY.Fault,428416.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_UY.Faulted,428416.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_UY.AlarmState,428416.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_UY.FaultInAlarm,428416.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UY.Alarm_EN,428416.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_UY.REST,428416.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_UY.ACKN,428416.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_UY.MCmd_Enable,428416.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UY.MCmd_Disable,428416.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UY.ALRM,428416.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_UY.ANUN,428416.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_UY.AKED,428416.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_UY.Resetable,428416.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_UY.Shelve,428416.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_UY.Suppress,428416.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_UY.InputAlarm,428416.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_UY.GlobalReset,428417.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_UY.PCSuppress,428417.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_UY.PCUnSuppress,428417.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_UY.PCUnshelve,428417.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_UY.Alarm_Fault,428417.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_UY.Shelved,428417.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_UY.Suppressed,428417.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_UY.PLCIOFault,428417.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UY.PLCF,428417.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_UY.TAGR,428417.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_XF.Fault,428450.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_XF.Faulted,428450.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_XF.AlarmState,428450.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_XF.FaultInAlarm,428450.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_XF.Alarm_EN,428450.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_XF.REST,428450.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_XF.ACKN,428450.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_XF.MCmd_Enable,428450.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_XF.MCmd_Disable,428450.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_XF.ALRM,428450.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_XF.ANUN,428450.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_XF.AKED,428450.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_XF.Resetable,428450.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_XF.Shelve,428450.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_XF.Suppress,428450.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_XF.InputAlarm,428450.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_XF.GlobalReset,428451.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_XF.PCSuppress,428451.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_XF.PCUnSuppress,428451.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_XF.PCUnshelve,428451.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_XF.Alarm_Fault,428451.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_XF.Shelved,428451.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_XF.Suppressed,428451.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_XF.PLCIOFault,428451.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_XF.PLCF,428451.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_XF.TAGR,428451.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_9_YA.Fault,428486.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_AFD_0103_9_YA.Faulted,428486.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_AFD_0103_9_YA.AlarmState,428486.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_AFD_0103_9_YA.FaultInAlarm,428486.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_YA.Alarm_EN,428486.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_AFD_0103_9_YA.REST,428486.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_AFD_0103_9_YA.ACKN,428486.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_AFD_0103_9_YA.MCmd_Enable,428486.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_YA.MCmd_Disable,428486.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_YA.ALRM,428486.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_AFD_0103_9_YA.ANUN,428486.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_AFD_0103_9_YA.AKED,428486.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_AFD_0103_9_YA.Resetable,428486.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_AFD_0103_9_YA.Shelve,428486.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9_YA.Suppress,428486.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9_YA.InputAlarm,428486.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_AFD_0103_9_YA.GlobalReset,428487.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_AFD_0103_9_YA.PCSuppress,428487.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9_YA.PCUnSuppress,428487.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9_YA.PCUnshelve,428487.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9_YA.Alarm_Fault,428487.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_AFD_0103_9_YA.Shelved,428487.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_AFD_0103_9_YA.Suppressed,428487.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_AFD_0103_9_YA.PLCIOFault,428487.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_YA.PLCF,428487.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9_YA.TAGR,428487.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0112_1_JA.Fault,428520.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0112_1_JA.Faulted,428520.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0112_1_JA.AlarmState,428520.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0112_1_JA.FaultInAlarm,428520.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JA.Alarm_EN,428520.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0112_1_JA.REST,428520.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0112_1_JA.ACKN,428520.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0112_1_JA.MCmd_Enable,428520.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JA.MCmd_Disable,428520.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JA.ALRM,428520.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0112_1_JA.ANUN,428520.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0112_1_JA.AKED,428520.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0112_1_JA.Resetable,428520.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0112_1_JA.Shelve,428520.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0112_1_JA.Suppress,428520.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0112_1_JA.InputAlarm,428520.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0112_1_JA.GlobalReset,428521.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0112_1_JA.PCSuppress,428521.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0112_1_JA.PCUnSuppress,428521.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0112_1_JA.PCUnshelve,428521.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0112_1_JA.Alarm_Fault,428521.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0112_1_JA.Shelved,428521.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0112_1_JA.Suppressed,428521.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0112_1_JA.PLCIOFault,428521.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_1_JA.PLCF,428521.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_1_JA.TAGR,428521.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0112_1_JN1.Fault,428556.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0112_1_JN1.Faulted,428556.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0112_1_JN1.AlarmState,428556.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0112_1_JN1.FaultInAlarm,428556.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JN1.Alarm_EN,428556.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0112_1_JN1.REST,428556.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0112_1_JN1.ACKN,428556.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0112_1_JN1.MCmd_Enable,428556.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JN1.MCmd_Disable,428556.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JN1.ALRM,428556.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0112_1_JN1.ANUN,428556.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0112_1_JN1.AKED,428556.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0112_1_JN1.Resetable,428556.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0112_1_JN1.Shelve,428556.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0112_1_JN1.Suppress,428556.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0112_1_JN1.InputAlarm,428556.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0112_1_JN1.GlobalReset,428557.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0112_1_JN1.PCSuppress,428557.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0112_1_JN1.PCUnSuppress,428557.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0112_1_JN1.PCUnshelve,428557.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0112_1_JN1.Alarm_Fault,428557.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0112_1_JN1.Shelved,428557.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0112_1_JN1.Suppressed,428557.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0112_1_JN1.PLCIOFault,428557.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_1_JN1.PLCF,428557.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_1_JN1.TAGR,428557.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0112_2_JA.Fault,428590.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0112_2_JA.Faulted,428590.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0112_2_JA.AlarmState,428590.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0112_2_JA.FaultInAlarm,428590.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JA.Alarm_EN,428590.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0112_2_JA.REST,428590.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0112_2_JA.ACKN,428590.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0112_2_JA.MCmd_Enable,428590.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JA.MCmd_Disable,428590.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JA.ALRM,428590.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0112_2_JA.ANUN,428590.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0112_2_JA.AKED,428590.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0112_2_JA.Resetable,428590.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0112_2_JA.Shelve,428590.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0112_2_JA.Suppress,428590.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0112_2_JA.InputAlarm,428590.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0112_2_JA.GlobalReset,428591.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0112_2_JA.PCSuppress,428591.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0112_2_JA.PCUnSuppress,428591.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0112_2_JA.PCUnshelve,428591.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0112_2_JA.Alarm_Fault,428591.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0112_2_JA.Shelved,428591.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0112_2_JA.Suppressed,428591.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0112_2_JA.PLCIOFault,428591.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_2_JA.PLCF,428591.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_2_JA.TAGR,428591.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0112_2_JN1.Fault,428626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0112_2_JN1.Faulted,428626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0112_2_JN1.AlarmState,428626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0112_2_JN1.FaultInAlarm,428626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JN1.Alarm_EN,428626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0112_2_JN1.REST,428626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0112_2_JN1.ACKN,428626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0112_2_JN1.MCmd_Enable,428626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JN1.MCmd_Disable,428626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JN1.ALRM,428626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0112_2_JN1.ANUN,428626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0112_2_JN1.AKED,428626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0112_2_JN1.Resetable,428626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0112_2_JN1.Shelve,428626.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0112_2_JN1.Suppress,428626.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0112_2_JN1.InputAlarm,428626.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0112_2_JN1.GlobalReset,428627.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0112_2_JN1.PCSuppress,428627.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0112_2_JN1.PCUnSuppress,428627.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0112_2_JN1.PCUnshelve,428627.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0112_2_JN1.Alarm_Fault,428627.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0112_2_JN1.Shelved,428627.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0112_2_JN1.Suppressed,428627.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0112_2_JN1.PLCIOFault,428627.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_2_JN1.PLCF,428627.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0112_2_JN1.TAGR,428627.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0140_1_JA.Fault,428660.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0140_1_JA.Faulted,428660.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0140_1_JA.AlarmState,428660.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0140_1_JA.FaultInAlarm,428660.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_JA.Alarm_EN,428660.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0140_1_JA.REST,428660.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0140_1_JA.ACKN,428660.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0140_1_JA.MCmd_Enable,428660.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_JA.MCmd_Disable,428660.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_JA.ALRM,428660.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0140_1_JA.ANUN,428660.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0140_1_JA.AKED,428660.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0140_1_JA.Resetable,428660.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0140_1_JA.Shelve,428660.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0140_1_JA.Suppress,428660.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0140_1_JA.InputAlarm,428660.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0140_1_JA.GlobalReset,428661.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0140_1_JA.PCSuppress,428661.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0140_1_JA.PCUnSuppress,428661.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0140_1_JA.PCUnshelve,428661.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0140_1_JA.Alarm_Fault,428661.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0140_1_JA.Shelved,428661.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0140_1_JA.Suppressed,428661.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0140_1_JA.PLCIOFault,428661.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0140_1_JA.PLCF,428661.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0140_1_JA.TAGR,428661.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_ATO_0140_1_XA.Fault,428696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_ATO_0140_1_XA.Faulted,428696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_ATO_0140_1_XA.AlarmState,428696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_ATO_0140_1_XA.FaultInAlarm,428696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_XA.Alarm_EN,428696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_ATO_0140_1_XA.REST,428696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_ATO_0140_1_XA.ACKN,428696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_ATO_0140_1_XA.MCmd_Enable,428696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_XA.MCmd_Disable,428696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_XA.ALRM,428696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_ATO_0140_1_XA.ANUN,428696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_ATO_0140_1_XA.AKED,428696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_ATO_0140_1_XA.Resetable,428696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_ATO_0140_1_XA.Shelve,428696.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_ATO_0140_1_XA.Suppress,428696.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_ATO_0140_1_XA.InputAlarm,428696.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_ATO_0140_1_XA.GlobalReset,428697.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_ATO_0140_1_XA.PCSuppress,428697.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_ATO_0140_1_XA.PCUnSuppress,428697.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_ATO_0140_1_XA.PCUnshelve,428697.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_ATO_0140_1_XA.Alarm_Fault,428697.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_ATO_0140_1_XA.Shelved,428697.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_ATO_0140_1_XA.Suppressed,428697.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_ATO_0140_1_XA.PLCIOFault,428697.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0140_1_XA.PLCF,428697.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_ATO_0140_1_XA.TAGR,428697.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0114_1_XA.Fault,428730.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0114_1_XA.Faulted,428730.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0114_1_XA.AlarmState,428730.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0114_1_XA.FaultInAlarm,428730.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_1_XA.Alarm_EN,428730.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0114_1_XA.REST,428730.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0114_1_XA.ACKN,428730.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0114_1_XA.MCmd_Enable,428730.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_1_XA.MCmd_Disable,428730.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_1_XA.ALRM,428730.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0114_1_XA.ANUN,428730.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0114_1_XA.AKED,428730.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0114_1_XA.Resetable,428730.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0114_1_XA.Shelve,428730.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0114_1_XA.Suppress,428730.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0114_1_XA.InputAlarm,428730.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0114_1_XA.GlobalReset,428731.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0114_1_XA.PCSuppress,428731.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0114_1_XA.PCUnSuppress,428731.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0114_1_XA.PCUnshelve,428731.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0114_1_XA.Alarm_Fault,428731.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0114_1_XA.Shelved,428731.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0114_1_XA.Suppressed,428731.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0114_1_XA.PLCIOFault,428731.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_1_XA.PLCF,428731.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_1_XA.TAGR,428731.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0114_2_XA.Fault,428766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0114_2_XA.Faulted,428766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0114_2_XA.AlarmState,428766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0114_2_XA.FaultInAlarm,428766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_2_XA.Alarm_EN,428766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0114_2_XA.REST,428766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0114_2_XA.ACKN,428766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0114_2_XA.MCmd_Enable,428766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_2_XA.MCmd_Disable,428766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_2_XA.ALRM,428766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0114_2_XA.ANUN,428766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0114_2_XA.AKED,428766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0114_2_XA.Resetable,428766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0114_2_XA.Shelve,428766.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0114_2_XA.Suppress,428766.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0114_2_XA.InputAlarm,428766.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0114_2_XA.GlobalReset,428767.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0114_2_XA.PCSuppress,428767.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0114_2_XA.PCUnSuppress,428767.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0114_2_XA.PCUnshelve,428767.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0114_2_XA.Alarm_Fault,428767.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0114_2_XA.Shelved,428767.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0114_2_XA.Suppressed,428767.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0114_2_XA.PLCIOFault,428767.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_2_XA.PLCF,428767.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_2_XA.TAGR,428767.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0114_3_LH.Fault,428800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0114_3_LH.Faulted,428800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0114_3_LH.AlarmState,428800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0114_3_LH.FaultInAlarm,428800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_3_LH.Alarm_EN,428800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0114_3_LH.REST,428800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0114_3_LH.ACKN,428800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0114_3_LH.MCmd_Enable,428800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_3_LH.MCmd_Disable,428800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_3_LH.ALRM,428800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0114_3_LH.ANUN,428800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0114_3_LH.AKED,428800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0114_3_LH.Resetable,428800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0114_3_LH.Shelve,428800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0114_3_LH.Suppress,428800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0114_3_LH.InputAlarm,428800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0114_3_LH.GlobalReset,428801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0114_3_LH.PCSuppress,428801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0114_3_LH.PCUnSuppress,428801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0114_3_LH.PCUnshelve,428801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0114_3_LH.Alarm_Fault,428801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0114_3_LH.Shelved,428801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0114_3_LH.Suppressed,428801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0114_3_LH.PLCIOFault,428801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_3_LH.PLCF,428801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0114_3_LH.TAGR,428801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1A_MF.Fault,428836.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1A_MF.Faulted,428836.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1A_MF.AlarmState,428836.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1A_MF.FaultInAlarm,428836.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_MF.Alarm_EN,428836.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1A_MF.REST,428836.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1A_MF.ACKN,428836.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1A_MF.MCmd_Enable,428836.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_MF.MCmd_Disable,428836.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_MF.ALRM,428836.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1A_MF.ANUN,428836.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1A_MF.AKED,428836.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1A_MF.Resetable,428836.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1A_MF.Shelve,428836.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1A_MF.Suppress,428836.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1A_MF.InputAlarm,428836.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1A_MF.GlobalReset,428837.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1A_MF.PCSuppress,428837.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1A_MF.PCUnSuppress,428837.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1A_MF.PCUnshelve,428837.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1A_MF.Alarm_Fault,428837.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1A_MF.Shelved,428837.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1A_MF.Suppressed,428837.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1A_MF.PLCIOFault,428837.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1A_MF.PLCF,428837.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1A_MF.TAGR,428837.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1A_XA.Fault,428870.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1A_XA.Faulted,428870.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1A_XA.AlarmState,428870.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1A_XA.FaultInAlarm,428870.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_XA.Alarm_EN,428870.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1A_XA.REST,428870.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1A_XA.ACKN,428870.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1A_XA.MCmd_Enable,428870.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_XA.MCmd_Disable,428870.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_XA.ALRM,428870.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1A_XA.ANUN,428870.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1A_XA.AKED,428870.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1A_XA.Resetable,428870.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1A_XA.Shelve,428870.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1A_XA.Suppress,428870.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1A_XA.InputAlarm,428870.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1A_XA.GlobalReset,428871.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1A_XA.PCSuppress,428871.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1A_XA.PCUnSuppress,428871.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1A_XA.PCUnshelve,428871.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1A_XA.Alarm_Fault,428871.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1A_XA.Shelved,428871.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1A_XA.Suppressed,428871.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1A_XA.PLCIOFault,428871.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1A_XA.PLCF,428871.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1A_XA.TAGR,428871.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1B_MF.Fault,428906.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1B_MF.Faulted,428906.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1B_MF.AlarmState,428906.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1B_MF.FaultInAlarm,428906.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_MF.Alarm_EN,428906.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1B_MF.REST,428906.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1B_MF.ACKN,428906.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1B_MF.MCmd_Enable,428906.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_MF.MCmd_Disable,428906.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_MF.ALRM,428906.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1B_MF.ANUN,428906.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1B_MF.AKED,428906.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1B_MF.Resetable,428906.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1B_MF.Shelve,428906.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1B_MF.Suppress,428906.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1B_MF.InputAlarm,428906.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1B_MF.GlobalReset,428907.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1B_MF.PCSuppress,428907.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1B_MF.PCUnSuppress,428907.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1B_MF.PCUnshelve,428907.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1B_MF.Alarm_Fault,428907.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1B_MF.Shelved,428907.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1B_MF.Suppressed,428907.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1B_MF.PLCIOFault,428907.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1B_MF.PLCF,428907.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1B_MF.TAGR,428907.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1B_XA.Fault,428940.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1B_XA.Faulted,428940.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1B_XA.AlarmState,428940.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1B_XA.FaultInAlarm,428940.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_XA.Alarm_EN,428940.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1B_XA.REST,428940.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1B_XA.ACKN,428940.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1B_XA.MCmd_Enable,428940.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_XA.MCmd_Disable,428940.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_XA.ALRM,428940.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1B_XA.ANUN,428940.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1B_XA.AKED,428940.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1B_XA.Resetable,428940.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1B_XA.Shelve,428940.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1B_XA.Suppress,428940.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1B_XA.InputAlarm,428940.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1B_XA.GlobalReset,428941.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1B_XA.PCSuppress,428941.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1B_XA.PCUnSuppress,428941.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1B_XA.PCUnshelve,428941.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1B_XA.Alarm_Fault,428941.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1B_XA.Shelved,428941.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1B_XA.Suppressed,428941.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1B_XA.PLCIOFault,428941.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1B_XA.PLCF,428941.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1B_XA.TAGR,428941.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1C_MF.Fault,428976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1C_MF.Faulted,428976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1C_MF.AlarmState,428976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1C_MF.FaultInAlarm,428976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_MF.Alarm_EN,428976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1C_MF.REST,428976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1C_MF.ACKN,428976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1C_MF.MCmd_Enable,428976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_MF.MCmd_Disable,428976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_MF.ALRM,428976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1C_MF.ANUN,428976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1C_MF.AKED,428976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1C_MF.Resetable,428976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1C_MF.Shelve,428976.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1C_MF.Suppress,428976.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1C_MF.InputAlarm,428976.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1C_MF.GlobalReset,428977.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1C_MF.PCSuppress,428977.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1C_MF.PCUnSuppress,428977.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1C_MF.PCUnshelve,428977.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1C_MF.Alarm_Fault,428977.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1C_MF.Shelved,428977.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1C_MF.Suppressed,428977.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1C_MF.PLCIOFault,428977.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1C_MF.PLCF,428977.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1C_MF.TAGR,428977.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1C_XA.Fault,429010.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1C_XA.Faulted,429010.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1C_XA.AlarmState,429010.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1C_XA.FaultInAlarm,429010.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_XA.Alarm_EN,429010.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1C_XA.REST,429010.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1C_XA.ACKN,429010.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1C_XA.MCmd_Enable,429010.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_XA.MCmd_Disable,429010.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_XA.ALRM,429010.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1C_XA.ANUN,429010.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1C_XA.AKED,429010.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1C_XA.Resetable,429010.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1C_XA.Shelve,429010.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1C_XA.Suppress,429010.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1C_XA.InputAlarm,429010.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1C_XA.GlobalReset,429011.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1C_XA.PCSuppress,429011.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1C_XA.PCUnSuppress,429011.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1C_XA.PCUnshelve,429011.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1C_XA.Alarm_Fault,429011.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1C_XA.Shelved,429011.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1C_XA.Suppressed,429011.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1C_XA.PLCIOFault,429011.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1C_XA.PLCF,429011.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1C_XA.TAGR,429011.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1DE_MF.Fault,429046.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1DE_MF.Faulted,429046.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1DE_MF.AlarmState,429046.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1DE_MF.FaultInAlarm,429046.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_MF.Alarm_EN,429046.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1DE_MF.REST,429046.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1DE_MF.ACKN,429046.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1DE_MF.MCmd_Enable,429046.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_MF.MCmd_Disable,429046.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_MF.ALRM,429046.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1DE_MF.ANUN,429046.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1DE_MF.AKED,429046.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1DE_MF.Resetable,429046.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1DE_MF.Shelve,429046.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1DE_MF.Suppress,429046.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1DE_MF.InputAlarm,429046.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1DE_MF.GlobalReset,429047.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1DE_MF.PCSuppress,429047.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1DE_MF.PCUnSuppress,429047.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1DE_MF.PCUnshelve,429047.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1DE_MF.Alarm_Fault,429047.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1DE_MF.Shelved,429047.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1DE_MF.Suppressed,429047.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1DE_MF.PLCIOFault,429047.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1DE_MF.PLCF,429047.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1DE_MF.TAGR,429047.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1DE_XA.Fault,429080.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1DE_XA.Faulted,429080.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1DE_XA.AlarmState,429080.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1DE_XA.FaultInAlarm,429080.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_XA.Alarm_EN,429080.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1DE_XA.REST,429080.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1DE_XA.ACKN,429080.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1DE_XA.MCmd_Enable,429080.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_XA.MCmd_Disable,429080.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_XA.ALRM,429080.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1DE_XA.ANUN,429080.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1DE_XA.AKED,429080.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1DE_XA.Resetable,429080.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1DE_XA.Shelve,429080.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1DE_XA.Suppress,429080.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1DE_XA.InputAlarm,429080.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1DE_XA.GlobalReset,429081.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1DE_XA.PCSuppress,429081.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1DE_XA.PCUnSuppress,429081.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1DE_XA.PCUnshelve,429081.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1DE_XA.Alarm_Fault,429081.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1DE_XA.Shelved,429081.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1DE_XA.Suppressed,429081.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1DE_XA.PLCIOFault,429081.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1DE_XA.PLCF,429081.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1DE_XA.TAGR,429081.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1FG_MF.Fault,429116.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1FG_MF.Faulted,429116.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1FG_MF.AlarmState,429116.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1FG_MF.FaultInAlarm,429116.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_MF.Alarm_EN,429116.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1FG_MF.REST,429116.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1FG_MF.ACKN,429116.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1FG_MF.MCmd_Enable,429116.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_MF.MCmd_Disable,429116.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_MF.ALRM,429116.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1FG_MF.ANUN,429116.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1FG_MF.AKED,429116.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1FG_MF.Resetable,429116.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1FG_MF.Shelve,429116.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1FG_MF.Suppress,429116.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1FG_MF.InputAlarm,429116.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1FG_MF.GlobalReset,429117.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1FG_MF.PCSuppress,429117.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1FG_MF.PCUnSuppress,429117.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1FG_MF.PCUnshelve,429117.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1FG_MF.Alarm_Fault,429117.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1FG_MF.Shelved,429117.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1FG_MF.Suppressed,429117.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1FG_MF.PLCIOFault,429117.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1FG_MF.PLCF,429117.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1FG_MF.TAGR,429117.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1FG_XA.Fault,429150.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1FG_XA.Faulted,429150.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1FG_XA.AlarmState,429150.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1FG_XA.FaultInAlarm,429150.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_XA.Alarm_EN,429150.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1FG_XA.REST,429150.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1FG_XA.ACKN,429150.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1FG_XA.MCmd_Enable,429150.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_XA.MCmd_Disable,429150.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_XA.ALRM,429150.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1FG_XA.ANUN,429150.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1FG_XA.AKED,429150.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1FG_XA.Resetable,429150.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1FG_XA.Shelve,429150.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1FG_XA.Suppress,429150.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1FG_XA.InputAlarm,429150.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1FG_XA.GlobalReset,429151.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1FG_XA.PCSuppress,429151.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1FG_XA.PCUnSuppress,429151.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1FG_XA.PCUnshelve,429151.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1FG_XA.Alarm_Fault,429151.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1FG_XA.Shelved,429151.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1FG_XA.Suppressed,429151.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1FG_XA.PLCIOFault,429151.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1FG_XA.PLCF,429151.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1FG_XA.TAGR,429151.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1H_MF.Fault,429186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1H_MF.Faulted,429186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1H_MF.AlarmState,429186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1H_MF.FaultInAlarm,429186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_MF.Alarm_EN,429186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1H_MF.REST,429186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1H_MF.ACKN,429186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1H_MF.MCmd_Enable,429186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_MF.MCmd_Disable,429186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_MF.ALRM,429186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1H_MF.ANUN,429186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1H_MF.AKED,429186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1H_MF.Resetable,429186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1H_MF.Shelve,429186.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1H_MF.Suppress,429186.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1H_MF.InputAlarm,429186.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1H_MF.GlobalReset,429187.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1H_MF.PCSuppress,429187.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1H_MF.PCUnSuppress,429187.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1H_MF.PCUnshelve,429187.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1H_MF.Alarm_Fault,429187.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1H_MF.Shelved,429187.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1H_MF.Suppressed,429187.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1H_MF.PLCIOFault,429187.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1H_MF.PLCF,429187.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1H_MF.TAGR,429187.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1H_XA.Fault,429220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1H_XA.Faulted,429220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1H_XA.AlarmState,429220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1H_XA.FaultInAlarm,429220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_XA.Alarm_EN,429220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1H_XA.REST,429220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1H_XA.ACKN,429220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1H_XA.MCmd_Enable,429220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_XA.MCmd_Disable,429220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_XA.ALRM,429220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1H_XA.ANUN,429220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1H_XA.AKED,429220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1H_XA.Resetable,429220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1H_XA.Shelve,429220.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1H_XA.Suppress,429220.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1H_XA.InputAlarm,429220.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1H_XA.GlobalReset,429221.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1H_XA.PCSuppress,429221.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1H_XA.PCUnSuppress,429221.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1H_XA.PCUnshelve,429221.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1H_XA.Alarm_Fault,429221.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1H_XA.Shelved,429221.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1H_XA.Suppressed,429221.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1H_XA.PLCIOFault,429221.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1H_XA.PLCF,429221.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1H_XA.TAGR,429221.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1I_MF.Fault,429256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1I_MF.Faulted,429256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1I_MF.AlarmState,429256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1I_MF.FaultInAlarm,429256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_MF.Alarm_EN,429256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1I_MF.REST,429256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1I_MF.ACKN,429256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1I_MF.MCmd_Enable,429256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_MF.MCmd_Disable,429256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_MF.ALRM,429256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1I_MF.ANUN,429256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1I_MF.AKED,429256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1I_MF.Resetable,429256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1I_MF.Shelve,429256.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1I_MF.Suppress,429256.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1I_MF.InputAlarm,429256.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1I_MF.GlobalReset,429257.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1I_MF.PCSuppress,429257.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1I_MF.PCUnSuppress,429257.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1I_MF.PCUnshelve,429257.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1I_MF.Alarm_Fault,429257.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1I_MF.Shelved,429257.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1I_MF.Suppressed,429257.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1I_MF.PLCIOFault,429257.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1I_MF.PLCF,429257.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1I_MF.TAGR,429257.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1I_XA.Fault,429290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1I_XA.Faulted,429290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1I_XA.AlarmState,429290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1I_XA.FaultInAlarm,429290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_XA.Alarm_EN,429290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1I_XA.REST,429290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1I_XA.ACKN,429290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1I_XA.MCmd_Enable,429290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_XA.MCmd_Disable,429290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_XA.ALRM,429290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1I_XA.ANUN,429290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1I_XA.AKED,429290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1I_XA.Resetable,429290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1I_XA.Shelve,429290.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1I_XA.Suppress,429290.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1I_XA.InputAlarm,429290.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1I_XA.GlobalReset,429291.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1I_XA.PCSuppress,429291.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1I_XA.PCUnSuppress,429291.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1I_XA.PCUnshelve,429291.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1I_XA.Alarm_Fault,429291.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1I_XA.Shelved,429291.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1I_XA.Suppressed,429291.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1I_XA.PLCIOFault,429291.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1I_XA.PLCF,429291.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1I_XA.TAGR,429291.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1J_MF.Fault,429326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1J_MF.Faulted,429326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1J_MF.AlarmState,429326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1J_MF.FaultInAlarm,429326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_MF.Alarm_EN,429326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1J_MF.REST,429326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1J_MF.ACKN,429326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1J_MF.MCmd_Enable,429326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_MF.MCmd_Disable,429326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_MF.ALRM,429326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1J_MF.ANUN,429326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1J_MF.AKED,429326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1J_MF.Resetable,429326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1J_MF.Shelve,429326.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1J_MF.Suppress,429326.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1J_MF.InputAlarm,429326.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1J_MF.GlobalReset,429327.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1J_MF.PCSuppress,429327.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1J_MF.PCUnSuppress,429327.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1J_MF.PCUnshelve,429327.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1J_MF.Alarm_Fault,429327.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1J_MF.Shelved,429327.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1J_MF.Suppressed,429327.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1J_MF.PLCIOFault,429327.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1J_MF.PLCF,429327.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1J_MF.TAGR,429327.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1J_XA.Fault,429360.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1J_XA.Faulted,429360.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1J_XA.AlarmState,429360.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1J_XA.FaultInAlarm,429360.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_XA.Alarm_EN,429360.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1J_XA.REST,429360.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1J_XA.ACKN,429360.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1J_XA.MCmd_Enable,429360.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_XA.MCmd_Disable,429360.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_XA.ALRM,429360.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1J_XA.ANUN,429360.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1J_XA.AKED,429360.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1J_XA.Resetable,429360.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1J_XA.Shelve,429360.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1J_XA.Suppress,429360.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1J_XA.InputAlarm,429360.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1J_XA.GlobalReset,429361.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1J_XA.PCSuppress,429361.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1J_XA.PCUnSuppress,429361.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1J_XA.PCUnshelve,429361.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1J_XA.Alarm_Fault,429361.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1J_XA.Shelved,429361.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1J_XA.Suppressed,429361.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1J_XA.PLCIOFault,429361.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1J_XA.PLCF,429361.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1J_XA.TAGR,429361.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1K_MF.Fault,429396.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1K_MF.Faulted,429396.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1K_MF.AlarmState,429396.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1K_MF.FaultInAlarm,429396.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_MF.Alarm_EN,429396.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1K_MF.REST,429396.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1K_MF.ACKN,429396.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1K_MF.MCmd_Enable,429396.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_MF.MCmd_Disable,429396.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_MF.ALRM,429396.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1K_MF.ANUN,429396.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1K_MF.AKED,429396.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1K_MF.Resetable,429396.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1K_MF.Shelve,429396.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1K_MF.Suppress,429396.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1K_MF.InputAlarm,429396.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1K_MF.GlobalReset,429397.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1K_MF.PCSuppress,429397.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1K_MF.PCUnSuppress,429397.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1K_MF.PCUnshelve,429397.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1K_MF.Alarm_Fault,429397.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1K_MF.Shelved,429397.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1K_MF.Suppressed,429397.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1K_MF.PLCIOFault,429397.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1K_MF.PLCF,429397.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1K_MF.TAGR,429397.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_1K_XA.Fault,429430.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_1K_XA.Faulted,429430.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_1K_XA.AlarmState,429430.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_1K_XA.FaultInAlarm,429430.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_XA.Alarm_EN,429430.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_1K_XA.REST,429430.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_1K_XA.ACKN,429430.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_1K_XA.MCmd_Enable,429430.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_XA.MCmd_Disable,429430.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_XA.ALRM,429430.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_1K_XA.ANUN,429430.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_1K_XA.AKED,429430.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_1K_XA.Resetable,429430.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_1K_XA.Shelve,429430.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_1K_XA.Suppress,429430.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_1K_XA.InputAlarm,429430.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_1K_XA.GlobalReset,429431.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_1K_XA.PCSuppress,429431.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_1K_XA.PCUnSuppress,429431.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_1K_XA.PCUnshelve,429431.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_1K_XA.Alarm_Fault,429431.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_1K_XA.Shelved,429431.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_1K_XA.Suppressed,429431.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_1K_XA.PLCIOFault,429431.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1K_XA.PLCF,429431.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_1K_XA.TAGR,429431.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_LH.Fault,429466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_LH.Faulted,429466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_LH.AlarmState,429466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_LH.FaultInAlarm,429466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_LH.Alarm_EN,429466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_LH.REST,429466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_LH.ACKN,429466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_LH.MCmd_Enable,429466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_LH.MCmd_Disable,429466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_LH.ALRM,429466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_LH.ANUN,429466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_LH.AKED,429466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_LH.Resetable,429466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_LH.Shelve,429466.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_LH.Suppress,429466.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_LH.InputAlarm,429466.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_LH.GlobalReset,429467.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_LH.PCSuppress,429467.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_LH.PCUnSuppress,429467.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_LH.PCUnshelve,429467.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_LH.Alarm_Fault,429467.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_LH.Shelved,429467.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_LH.Suppressed,429467.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_LH.PLCIOFault,429467.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_LH.PLCF,429467.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_LH.TAGR,429467.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_MF1.Fault,429500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_MF1.Faulted,429500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_MF1.AlarmState,429500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_MF1.FaultInAlarm,429500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF1.Alarm_EN,429500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_MF1.REST,429500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_MF1.ACKN,429500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_MF1.MCmd_Enable,429500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF1.MCmd_Disable,429500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF1.ALRM,429500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_MF1.ANUN,429500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_MF1.AKED,429500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_MF1.Resetable,429500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_MF1.Shelve,429500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_MF1.Suppress,429500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_MF1.InputAlarm,429500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_MF1.GlobalReset,429501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_MF1.PCSuppress,429501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_MF1.PCUnSuppress,429501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_MF1.PCUnshelve,429501.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_MF1.Alarm_Fault,429501.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_MF1.Shelved,429501.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_MF1.Suppressed,429501.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_MF1.PLCIOFault,429501.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF1.PLCF,429501.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF1.TAGR,429501.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_MF2.Fault,429536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_MF2.Faulted,429536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_MF2.AlarmState,429536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_MF2.FaultInAlarm,429536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF2.Alarm_EN,429536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_MF2.REST,429536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_MF2.ACKN,429536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_MF2.MCmd_Enable,429536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF2.MCmd_Disable,429536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF2.ALRM,429536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_MF2.ANUN,429536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_MF2.AKED,429536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_MF2.Resetable,429536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_MF2.Shelve,429536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_MF2.Suppress,429536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_MF2.InputAlarm,429536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_MF2.GlobalReset,429537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_MF2.PCSuppress,429537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_MF2.PCUnSuppress,429537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_MF2.PCUnshelve,429537.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_MF2.Alarm_Fault,429537.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_MF2.Shelved,429537.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_MF2.Suppressed,429537.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_MF2.PLCIOFault,429537.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF2.PLCF,429537.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF2.TAGR,429537.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_MF3.Fault,429570.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_MF3.Faulted,429570.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_MF3.AlarmState,429570.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_MF3.FaultInAlarm,429570.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF3.Alarm_EN,429570.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_MF3.REST,429570.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_MF3.ACKN,429570.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_MF3.MCmd_Enable,429570.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF3.MCmd_Disable,429570.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF3.ALRM,429570.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_MF3.ANUN,429570.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_MF3.AKED,429570.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_MF3.Resetable,429570.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_MF3.Shelve,429570.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_MF3.Suppress,429570.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_MF3.InputAlarm,429570.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_MF3.GlobalReset,429571.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_MF3.PCSuppress,429571.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_MF3.PCUnSuppress,429571.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_MF3.PCUnshelve,429571.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_MF3.Alarm_Fault,429571.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_MF3.Shelved,429571.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_MF3.Suppressed,429571.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_MF3.PLCIOFault,429571.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF3.PLCF,429571.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF3.TAGR,429571.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_MF4.Fault,429606.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_MF4.Faulted,429606.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_MF4.AlarmState,429606.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_MF4.FaultInAlarm,429606.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF4.Alarm_EN,429606.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_MF4.REST,429606.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_MF4.ACKN,429606.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_MF4.MCmd_Enable,429606.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF4.MCmd_Disable,429606.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF4.ALRM,429606.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_MF4.ANUN,429606.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_MF4.AKED,429606.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_MF4.Resetable,429606.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_MF4.Shelve,429606.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_MF4.Suppress,429606.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_MF4.InputAlarm,429606.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_MF4.GlobalReset,429607.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_MF4.PCSuppress,429607.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_MF4.PCUnSuppress,429607.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_MF4.PCUnshelve,429607.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_MF4.Alarm_Fault,429607.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_MF4.Shelved,429607.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_MF4.Suppressed,429607.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_MF4.PLCIOFault,429607.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF4.PLCF,429607.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_MF4.TAGR,429607.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2A_XA.Fault,429640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2A_XA.Faulted,429640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2A_XA.AlarmState,429640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2A_XA.FaultInAlarm,429640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_XA.Alarm_EN,429640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2A_XA.REST,429640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2A_XA.ACKN,429640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2A_XA.MCmd_Enable,429640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_XA.MCmd_Disable,429640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_XA.ALRM,429640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2A_XA.ANUN,429640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2A_XA.AKED,429640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2A_XA.Resetable,429640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2A_XA.Shelve,429640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2A_XA.Suppress,429640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2A_XA.InputAlarm,429640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2A_XA.GlobalReset,429641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2A_XA.PCSuppress,429641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2A_XA.PCUnSuppress,429641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2A_XA.PCUnshelve,429641.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2A_XA.Alarm_Fault,429641.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2A_XA.Shelved,429641.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2A_XA.Suppressed,429641.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2A_XA.PLCIOFault,429641.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_XA.PLCF,429641.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2A_XA.TAGR,429641.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_LH.Fault,429676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_LH.Faulted,429676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_LH.AlarmState,429676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_LH.FaultInAlarm,429676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_LH.Alarm_EN,429676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_LH.REST,429676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_LH.ACKN,429676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_LH.MCmd_Enable,429676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_LH.MCmd_Disable,429676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_LH.ALRM,429676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_LH.ANUN,429676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_LH.AKED,429676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_LH.Resetable,429676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_LH.Shelve,429676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_LH.Suppress,429676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_LH.InputAlarm,429676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_LH.GlobalReset,429677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_LH.PCSuppress,429677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_LH.PCUnSuppress,429677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_LH.PCUnshelve,429677.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_LH.Alarm_Fault,429677.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_LH.Shelved,429677.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_LH.Suppressed,429677.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_LH.PLCIOFault,429677.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_LH.PLCF,429677.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_LH.TAGR,429677.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_MF1.Fault,429710.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_MF1.Faulted,429710.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_MF1.AlarmState,429710.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_MF1.FaultInAlarm,429710.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF1.Alarm_EN,429710.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_MF1.REST,429710.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_MF1.ACKN,429710.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_MF1.MCmd_Enable,429710.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF1.MCmd_Disable,429710.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF1.ALRM,429710.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_MF1.ANUN,429710.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_MF1.AKED,429710.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_MF1.Resetable,429710.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_MF1.Shelve,429710.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_MF1.Suppress,429710.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_MF1.InputAlarm,429710.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_MF1.GlobalReset,429711.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_MF1.PCSuppress,429711.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_MF1.PCUnSuppress,429711.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_MF1.PCUnshelve,429711.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_MF1.Alarm_Fault,429711.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_MF1.Shelved,429711.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_MF1.Suppressed,429711.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_MF1.PLCIOFault,429711.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF1.PLCF,429711.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF1.TAGR,429711.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_MF2.Fault,429746.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_MF2.Faulted,429746.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_MF2.AlarmState,429746.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_MF2.FaultInAlarm,429746.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF2.Alarm_EN,429746.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_MF2.REST,429746.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_MF2.ACKN,429746.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_MF2.MCmd_Enable,429746.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF2.MCmd_Disable,429746.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF2.ALRM,429746.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_MF2.ANUN,429746.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_MF2.AKED,429746.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_MF2.Resetable,429746.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_MF2.Shelve,429746.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_MF2.Suppress,429746.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_MF2.InputAlarm,429746.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_MF2.GlobalReset,429747.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_MF2.PCSuppress,429747.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_MF2.PCUnSuppress,429747.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_MF2.PCUnshelve,429747.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_MF2.Alarm_Fault,429747.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_MF2.Shelved,429747.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_MF2.Suppressed,429747.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_MF2.PLCIOFault,429747.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF2.PLCF,429747.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF2.TAGR,429747.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_MF3.Fault,429780.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_MF3.Faulted,429780.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_MF3.AlarmState,429780.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_MF3.FaultInAlarm,429780.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF3.Alarm_EN,429780.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_MF3.REST,429780.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_MF3.ACKN,429780.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_MF3.MCmd_Enable,429780.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF3.MCmd_Disable,429780.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF3.ALRM,429780.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_MF3.ANUN,429780.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_MF3.AKED,429780.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_MF3.Resetable,429780.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_MF3.Shelve,429780.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_MF3.Suppress,429780.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_MF3.InputAlarm,429780.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_MF3.GlobalReset,429781.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_MF3.PCSuppress,429781.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_MF3.PCUnSuppress,429781.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_MF3.PCUnshelve,429781.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_MF3.Alarm_Fault,429781.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_MF3.Shelved,429781.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_MF3.Suppressed,429781.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_MF3.PLCIOFault,429781.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF3.PLCF,429781.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF3.TAGR,429781.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_MF4.Fault,429816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_MF4.Faulted,429816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_MF4.AlarmState,429816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_MF4.FaultInAlarm,429816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF4.Alarm_EN,429816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_MF4.REST,429816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_MF4.ACKN,429816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_MF4.MCmd_Enable,429816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF4.MCmd_Disable,429816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF4.ALRM,429816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_MF4.ANUN,429816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_MF4.AKED,429816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_MF4.Resetable,429816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_MF4.Shelve,429816.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_MF4.Suppress,429816.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_MF4.InputAlarm,429816.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_MF4.GlobalReset,429817.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_MF4.PCSuppress,429817.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_MF4.PCUnSuppress,429817.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_MF4.PCUnshelve,429817.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_MF4.Alarm_Fault,429817.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_MF4.Shelved,429817.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_MF4.Suppressed,429817.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_MF4.PLCIOFault,429817.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF4.PLCF,429817.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_MF4.TAGR,429817.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_2B_XA.Fault,429850.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_2B_XA.Faulted,429850.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_2B_XA.AlarmState,429850.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_2B_XA.FaultInAlarm,429850.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_XA.Alarm_EN,429850.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_2B_XA.REST,429850.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_2B_XA.ACKN,429850.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_2B_XA.MCmd_Enable,429850.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_XA.MCmd_Disable,429850.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_XA.ALRM,429850.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_2B_XA.ANUN,429850.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_2B_XA.AKED,429850.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_2B_XA.Resetable,429850.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_2B_XA.Shelve,429850.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_2B_XA.Suppress,429850.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_2B_XA.InputAlarm,429850.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_2B_XA.GlobalReset,429851.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_2B_XA.PCSuppress,429851.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_2B_XA.PCUnSuppress,429851.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_2B_XA.PCUnshelve,429851.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_2B_XA.Alarm_Fault,429851.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_2B_XA.Shelved,429851.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_2B_XA.Suppressed,429851.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_2B_XA.PLCIOFault,429851.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_XA.PLCF,429851.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_2B_XA.TAGR,429851.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_3A_MF.Fault,429886.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_3A_MF.Faulted,429886.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_3A_MF.AlarmState,429886.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_3A_MF.FaultInAlarm,429886.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3A_MF.Alarm_EN,429886.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_3A_MF.REST,429886.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_3A_MF.ACKN,429886.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_3A_MF.MCmd_Enable,429886.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3A_MF.MCmd_Disable,429886.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3A_MF.ALRM,429886.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_3A_MF.ANUN,429886.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_3A_MF.AKED,429886.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_3A_MF.Resetable,429886.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_3A_MF.Shelve,429886.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_3A_MF.Suppress,429886.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_3A_MF.InputAlarm,429886.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_3A_MF.GlobalReset,429887.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_3A_MF.PCSuppress,429887.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_3A_MF.PCUnSuppress,429887.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_3A_MF.PCUnshelve,429887.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_3A_MF.Alarm_Fault,429887.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_3A_MF.Shelved,429887.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_3A_MF.Suppressed,429887.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_3A_MF.PLCIOFault,429887.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_3A_MF.PLCF,429887.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_3A_MF.TAGR,429887.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0117_3B_XF.Fault,429920.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0117_3B_XF.Faulted,429920.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0117_3B_XF.AlarmState,429920.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0117_3B_XF.FaultInAlarm,429920.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3B_XF.Alarm_EN,429920.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0117_3B_XF.REST,429920.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0117_3B_XF.ACKN,429920.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0117_3B_XF.MCmd_Enable,429920.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3B_XF.MCmd_Disable,429920.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3B_XF.ALRM,429920.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0117_3B_XF.ANUN,429920.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0117_3B_XF.AKED,429920.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0117_3B_XF.Resetable,429920.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0117_3B_XF.Shelve,429920.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0117_3B_XF.Suppress,429920.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0117_3B_XF.InputAlarm,429920.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0117_3B_XF.GlobalReset,429921.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0117_3B_XF.PCSuppress,429921.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0117_3B_XF.PCUnSuppress,429921.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0117_3B_XF.PCUnshelve,429921.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0117_3B_XF.Alarm_Fault,429921.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0117_3B_XF.Shelved,429921.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0117_3B_XF.Suppressed,429921.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0117_3B_XF.PLCIOFault,429921.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_3B_XF.PLCF,429921.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0117_3B_XF.TAGR,429921.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_1_LH1.Fault,429956.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_1_LH1.Faulted,429956.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_1_LH1.AlarmState,429956.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_1_LH1.FaultInAlarm,429956.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH1.Alarm_EN,429956.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_1_LH1.REST,429956.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_1_LH1.ACKN,429956.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_1_LH1.MCmd_Enable,429956.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH1.MCmd_Disable,429956.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH1.ALRM,429956.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_1_LH1.ANUN,429956.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_1_LH1.AKED,429956.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_1_LH1.Resetable,429956.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_1_LH1.Shelve,429956.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_1_LH1.Suppress,429956.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_1_LH1.InputAlarm,429956.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_1_LH1.GlobalReset,429957.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_1_LH1.PCSuppress,429957.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_1_LH1.PCUnSuppress,429957.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_1_LH1.PCUnshelve,429957.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_1_LH1.Alarm_Fault,429957.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_1_LH1.Shelved,429957.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_1_LH1.Suppressed,429957.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_1_LH1.PLCIOFault,429957.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_LH1.PLCF,429957.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_LH1.TAGR,429957.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_1_LH2.Fault,429990.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_1_LH2.Faulted,429990.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_1_LH2.AlarmState,429990.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_1_LH2.FaultInAlarm,429990.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH2.Alarm_EN,429990.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_1_LH2.REST,429990.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_1_LH2.ACKN,429990.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_1_LH2.MCmd_Enable,429990.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH2.MCmd_Disable,429990.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH2.ALRM,429990.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_1_LH2.ANUN,429990.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_1_LH2.AKED,429990.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_1_LH2.Resetable,429990.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_1_LH2.Shelve,429990.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_1_LH2.Suppress,429990.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_1_LH2.InputAlarm,429990.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_1_LH2.GlobalReset,429991.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_1_LH2.PCSuppress,429991.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_1_LH2.PCUnSuppress,429991.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_1_LH2.PCUnshelve,429991.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_1_LH2.Alarm_Fault,429991.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_1_LH2.Shelved,429991.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_1_LH2.Suppressed,429991.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_1_LH2.PLCIOFault,429991.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_LH2.PLCF,429991.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_LH2.TAGR,429991.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_1_XA.Fault,430026.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_1_XA.Faulted,430026.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_1_XA.AlarmState,430026.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_1_XA.FaultInAlarm,430026.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_XA.Alarm_EN,430026.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_1_XA.REST,430026.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_1_XA.ACKN,430026.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_1_XA.MCmd_Enable,430026.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_XA.MCmd_Disable,430026.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_XA.ALRM,430026.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_1_XA.ANUN,430026.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_1_XA.AKED,430026.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_1_XA.Resetable,430026.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_1_XA.Shelve,430026.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_1_XA.Suppress,430026.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_1_XA.InputAlarm,430026.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_1_XA.GlobalReset,430027.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_1_XA.PCSuppress,430027.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_1_XA.PCUnSuppress,430027.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_1_XA.PCUnshelve,430027.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_1_XA.Alarm_Fault,430027.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_1_XA.Shelved,430027.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_1_XA.Suppressed,430027.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_1_XA.PLCIOFault,430027.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_XA.PLCF,430027.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1_XA.TAGR,430027.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_1A_MF.Fault,430060.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_1A_MF.Faulted,430060.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_1A_MF.AlarmState,430060.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_1A_MF.FaultInAlarm,430060.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1A_MF.Alarm_EN,430060.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_1A_MF.REST,430060.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_1A_MF.ACKN,430060.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_1A_MF.MCmd_Enable,430060.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1A_MF.MCmd_Disable,430060.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1A_MF.ALRM,430060.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_1A_MF.ANUN,430060.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_1A_MF.AKED,430060.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_1A_MF.Resetable,430060.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_1A_MF.Shelve,430060.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_1A_MF.Suppress,430060.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_1A_MF.InputAlarm,430060.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_1A_MF.GlobalReset,430061.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_1A_MF.PCSuppress,430061.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_1A_MF.PCUnSuppress,430061.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_1A_MF.PCUnshelve,430061.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_1A_MF.Alarm_Fault,430061.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_1A_MF.Shelved,430061.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_1A_MF.Suppressed,430061.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_1A_MF.PLCIOFault,430061.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1A_MF.PLCF,430061.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1A_MF.TAGR,430061.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_1B_MF.Fault,430096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_1B_MF.Faulted,430096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_1B_MF.AlarmState,430096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_1B_MF.FaultInAlarm,430096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1B_MF.Alarm_EN,430096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_1B_MF.REST,430096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_1B_MF.ACKN,430096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_1B_MF.MCmd_Enable,430096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1B_MF.MCmd_Disable,430096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1B_MF.ALRM,430096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_1B_MF.ANUN,430096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_1B_MF.AKED,430096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_1B_MF.Resetable,430096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_1B_MF.Shelve,430096.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_1B_MF.Suppress,430096.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_1B_MF.InputAlarm,430096.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_1B_MF.GlobalReset,430097.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_1B_MF.PCSuppress,430097.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_1B_MF.PCUnSuppress,430097.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_1B_MF.PCUnshelve,430097.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_1B_MF.Alarm_Fault,430097.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_1B_MF.Shelved,430097.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_1B_MF.Suppressed,430097.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_1B_MF.PLCIOFault,430097.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1B_MF.PLCF,430097.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_1B_MF.TAGR,430097.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_2_LH1.Fault,430130.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_2_LH1.Faulted,430130.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_2_LH1.AlarmState,430130.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_2_LH1.FaultInAlarm,430130.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH1.Alarm_EN,430130.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_2_LH1.REST,430130.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_2_LH1.ACKN,430130.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_2_LH1.MCmd_Enable,430130.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH1.MCmd_Disable,430130.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH1.ALRM,430130.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_2_LH1.ANUN,430130.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_2_LH1.AKED,430130.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_2_LH1.Resetable,430130.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_2_LH1.Shelve,430130.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_2_LH1.Suppress,430130.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_2_LH1.InputAlarm,430130.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_2_LH1.GlobalReset,430131.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_2_LH1.PCSuppress,430131.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_2_LH1.PCUnSuppress,430131.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_2_LH1.PCUnshelve,430131.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_2_LH1.Alarm_Fault,430131.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_2_LH1.Shelved,430131.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_2_LH1.Suppressed,430131.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_2_LH1.PLCIOFault,430131.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_LH1.PLCF,430131.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_LH1.TAGR,430131.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_2_LH2.Fault,430166.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_2_LH2.Faulted,430166.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_2_LH2.AlarmState,430166.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_2_LH2.FaultInAlarm,430166.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH2.Alarm_EN,430166.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_2_LH2.REST,430166.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_2_LH2.ACKN,430166.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_2_LH2.MCmd_Enable,430166.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH2.MCmd_Disable,430166.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH2.ALRM,430166.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_2_LH2.ANUN,430166.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_2_LH2.AKED,430166.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_2_LH2.Resetable,430166.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_2_LH2.Shelve,430166.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_2_LH2.Suppress,430166.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_2_LH2.InputAlarm,430166.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_2_LH2.GlobalReset,430167.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_2_LH2.PCSuppress,430167.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_2_LH2.PCUnSuppress,430167.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_2_LH2.PCUnshelve,430167.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_2_LH2.Alarm_Fault,430167.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_2_LH2.Shelved,430167.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_2_LH2.Suppressed,430167.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_2_LH2.PLCIOFault,430167.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_LH2.PLCF,430167.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_LH2.TAGR,430167.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_2_XA.Fault,430200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_2_XA.Faulted,430200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_2_XA.AlarmState,430200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_2_XA.FaultInAlarm,430200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_XA.Alarm_EN,430200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_2_XA.REST,430200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_2_XA.ACKN,430200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_2_XA.MCmd_Enable,430200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_XA.MCmd_Disable,430200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_XA.ALRM,430200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_2_XA.ANUN,430200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_2_XA.AKED,430200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_2_XA.Resetable,430200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_2_XA.Shelve,430200.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_2_XA.Suppress,430200.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_2_XA.InputAlarm,430200.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_2_XA.GlobalReset,430201.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_2_XA.PCSuppress,430201.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_2_XA.PCUnSuppress,430201.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_2_XA.PCUnshelve,430201.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_2_XA.Alarm_Fault,430201.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_2_XA.Shelved,430201.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_2_XA.Suppressed,430201.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_2_XA.PLCIOFault,430201.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_XA.PLCF,430201.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2_XA.TAGR,430201.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_2A_MF.Fault,430236.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_2A_MF.Faulted,430236.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_2A_MF.AlarmState,430236.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_2A_MF.FaultInAlarm,430236.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2A_MF.Alarm_EN,430236.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_2A_MF.REST,430236.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_2A_MF.ACKN,430236.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_2A_MF.MCmd_Enable,430236.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2A_MF.MCmd_Disable,430236.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2A_MF.ALRM,430236.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_2A_MF.ANUN,430236.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_2A_MF.AKED,430236.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_2A_MF.Resetable,430236.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_2A_MF.Shelve,430236.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_2A_MF.Suppress,430236.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_2A_MF.InputAlarm,430236.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_2A_MF.GlobalReset,430237.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_2A_MF.PCSuppress,430237.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_2A_MF.PCUnSuppress,430237.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_2A_MF.PCUnshelve,430237.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_2A_MF.Alarm_Fault,430237.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_2A_MF.Shelved,430237.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_2A_MF.Suppressed,430237.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_2A_MF.PLCIOFault,430237.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2A_MF.PLCF,430237.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2A_MF.TAGR,430237.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_CP_0118_2B_MF.Fault,430270.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_CP_0118_2B_MF.Faulted,430270.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_CP_0118_2B_MF.AlarmState,430270.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_CP_0118_2B_MF.FaultInAlarm,430270.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2B_MF.Alarm_EN,430270.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_CP_0118_2B_MF.REST,430270.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_CP_0118_2B_MF.ACKN,430270.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_CP_0118_2B_MF.MCmd_Enable,430270.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2B_MF.MCmd_Disable,430270.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2B_MF.ALRM,430270.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_CP_0118_2B_MF.ANUN,430270.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_CP_0118_2B_MF.AKED,430270.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_CP_0118_2B_MF.Resetable,430270.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_CP_0118_2B_MF.Shelve,430270.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_CP_0118_2B_MF.Suppress,430270.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_CP_0118_2B_MF.InputAlarm,430270.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_CP_0118_2B_MF.GlobalReset,430271.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_CP_0118_2B_MF.PCSuppress,430271.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_CP_0118_2B_MF.PCUnSuppress,430271.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_CP_0118_2B_MF.PCUnshelve,430271.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_CP_0118_2B_MF.Alarm_Fault,430271.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_CP_0118_2B_MF.Shelved,430271.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_CP_0118_2B_MF.Suppressed,430271.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_CP_0118_2B_MF.PLCIOFault,430271.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2B_MF.PLCF,430271.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_CP_0118_2B_MF.TAGR,430271.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FCV_0113_2A_WH.Fault,430306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FCV_0113_2A_WH.Faulted,430306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FCV_0113_2A_WH.AlarmState,430306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FCV_0113_2A_WH.FaultInAlarm,430306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_WH.Alarm_EN,430306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FCV_0113_2A_WH.REST,430306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FCV_0113_2A_WH.ACKN,430306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FCV_0113_2A_WH.MCmd_Enable,430306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_WH.MCmd_Disable,430306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_WH.ALRM,430306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FCV_0113_2A_WH.ANUN,430306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FCV_0113_2A_WH.AKED,430306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FCV_0113_2A_WH.Resetable,430306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2A_WH.Shelve,430306.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2A_WH.Suppress,430306.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2A_WH.InputAlarm,430306.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FCV_0113_2A_WH.GlobalReset,430307.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FCV_0113_2A_WH.PCSuppress,430307.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2A_WH.PCUnSuppress,430307.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2A_WH.PCUnshelve,430307.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2A_WH.Alarm_Fault,430307.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FCV_0113_2A_WH.Shelved,430307.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FCV_0113_2A_WH.Suppressed,430307.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FCV_0113_2A_WH.PLCIOFault,430307.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A_WH.PLCF,430307.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A_WH.TAGR,430307.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FCV_0113_2B_WH.Fault,430340.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FCV_0113_2B_WH.Faulted,430340.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FCV_0113_2B_WH.AlarmState,430340.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FCV_0113_2B_WH.FaultInAlarm,430340.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_WH.Alarm_EN,430340.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FCV_0113_2B_WH.REST,430340.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FCV_0113_2B_WH.ACKN,430340.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FCV_0113_2B_WH.MCmd_Enable,430340.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_WH.MCmd_Disable,430340.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_WH.ALRM,430340.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FCV_0113_2B_WH.ANUN,430340.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FCV_0113_2B_WH.AKED,430340.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FCV_0113_2B_WH.Resetable,430340.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2B_WH.Shelve,430340.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2B_WH.Suppress,430340.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2B_WH.InputAlarm,430340.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FCV_0113_2B_WH.GlobalReset,430341.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FCV_0113_2B_WH.PCSuppress,430341.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2B_WH.PCUnSuppress,430341.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2B_WH.PCUnshelve,430341.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2B_WH.Alarm_Fault,430341.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FCV_0113_2B_WH.Shelved,430341.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FCV_0113_2B_WH.Suppressed,430341.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FCV_0113_2B_WH.PLCIOFault,430341.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B_WH.PLCF,430341.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B_WH.TAGR,430341.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FLT_0112_1_XA.Fault,430376.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FLT_0112_1_XA.Faulted,430376.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FLT_0112_1_XA.AlarmState,430376.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FLT_0112_1_XA.FaultInAlarm,430376.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_1_XA.Alarm_EN,430376.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FLT_0112_1_XA.REST,430376.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FLT_0112_1_XA.ACKN,430376.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FLT_0112_1_XA.MCmd_Enable,430376.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_1_XA.MCmd_Disable,430376.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_1_XA.ALRM,430376.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FLT_0112_1_XA.ANUN,430376.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FLT_0112_1_XA.AKED,430376.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FLT_0112_1_XA.Resetable,430376.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FLT_0112_1_XA.Shelve,430376.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FLT_0112_1_XA.Suppress,430376.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FLT_0112_1_XA.InputAlarm,430376.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FLT_0112_1_XA.GlobalReset,430377.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FLT_0112_1_XA.PCSuppress,430377.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FLT_0112_1_XA.PCUnSuppress,430377.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FLT_0112_1_XA.PCUnshelve,430377.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FLT_0112_1_XA.Alarm_Fault,430377.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FLT_0112_1_XA.Shelved,430377.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FLT_0112_1_XA.Suppressed,430377.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FLT_0112_1_XA.PLCIOFault,430377.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FLT_0112_1_XA.PLCF,430377.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FLT_0112_1_XA.TAGR,430377.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FLT_0112_2_XA.Fault,430410.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FLT_0112_2_XA.Faulted,430410.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FLT_0112_2_XA.AlarmState,430410.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FLT_0112_2_XA.FaultInAlarm,430410.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_2_XA.Alarm_EN,430410.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FLT_0112_2_XA.REST,430410.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FLT_0112_2_XA.ACKN,430410.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FLT_0112_2_XA.MCmd_Enable,430410.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_2_XA.MCmd_Disable,430410.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_2_XA.ALRM,430410.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FLT_0112_2_XA.ANUN,430410.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FLT_0112_2_XA.AKED,430410.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FLT_0112_2_XA.Resetable,430410.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FLT_0112_2_XA.Shelve,430410.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FLT_0112_2_XA.Suppress,430410.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FLT_0112_2_XA.InputAlarm,430410.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FLT_0112_2_XA.GlobalReset,430411.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FLT_0112_2_XA.PCSuppress,430411.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FLT_0112_2_XA.PCUnSuppress,430411.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FLT_0112_2_XA.PCUnshelve,430411.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FLT_0112_2_XA.Alarm_Fault,430411.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FLT_0112_2_XA.Shelved,430411.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FLT_0112_2_XA.Suppressed,430411.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FLT_0112_2_XA.PLCIOFault,430411.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FLT_0112_2_XA.PLCF,430411.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FLT_0112_2_XA.TAGR,430411.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0102_1A_WH.Fault,430446.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0102_1A_WH.Faulted,430446.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0102_1A_WH.AlarmState,430446.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0102_1A_WH.FaultInAlarm,430446.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A_WH.Alarm_EN,430446.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0102_1A_WH.REST,430446.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0102_1A_WH.ACKN,430446.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0102_1A_WH.MCmd_Enable,430446.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A_WH.MCmd_Disable,430446.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A_WH.ALRM,430446.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0102_1A_WH.ANUN,430446.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0102_1A_WH.AKED,430446.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0102_1A_WH.Resetable,430446.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_1A_WH.Shelve,430446.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0102_1A_WH.Suppress,430446.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0102_1A_WH.InputAlarm,430446.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0102_1A_WH.GlobalReset,430447.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0102_1A_WH.PCSuppress,430447.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_1A_WH.PCUnSuppress,430447.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_1A_WH.PCUnshelve,430447.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_1A_WH.Alarm_Fault,430447.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0102_1A_WH.Shelved,430447.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0102_1A_WH.Suppressed,430447.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0102_1A_WH.PLCIOFault,430447.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1A_WH.PLCF,430447.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1A_WH.TAGR,430447.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0102_1B_WH.Fault,430480.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0102_1B_WH.Faulted,430480.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0102_1B_WH.AlarmState,430480.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0102_1B_WH.FaultInAlarm,430480.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B_WH.Alarm_EN,430480.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0102_1B_WH.REST,430480.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0102_1B_WH.ACKN,430480.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0102_1B_WH.MCmd_Enable,430480.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B_WH.MCmd_Disable,430480.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B_WH.ALRM,430480.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0102_1B_WH.ANUN,430480.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0102_1B_WH.AKED,430480.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0102_1B_WH.Resetable,430480.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_1B_WH.Shelve,430480.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0102_1B_WH.Suppress,430480.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0102_1B_WH.InputAlarm,430480.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0102_1B_WH.GlobalReset,430481.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0102_1B_WH.PCSuppress,430481.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_1B_WH.PCUnSuppress,430481.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_1B_WH.PCUnshelve,430481.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_1B_WH.Alarm_Fault,430481.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0102_1B_WH.Shelved,430481.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0102_1B_WH.Suppressed,430481.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0102_1B_WH.PLCIOFault,430481.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1B_WH.PLCF,430481.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1B_WH.TAGR,430481.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0102_2A_WH.Fault,430516.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0102_2A_WH.Faulted,430516.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0102_2A_WH.AlarmState,430516.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0102_2A_WH.FaultInAlarm,430516.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A_WH.Alarm_EN,430516.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0102_2A_WH.REST,430516.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0102_2A_WH.ACKN,430516.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0102_2A_WH.MCmd_Enable,430516.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A_WH.MCmd_Disable,430516.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A_WH.ALRM,430516.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0102_2A_WH.ANUN,430516.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0102_2A_WH.AKED,430516.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0102_2A_WH.Resetable,430516.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_2A_WH.Shelve,430516.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0102_2A_WH.Suppress,430516.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0102_2A_WH.InputAlarm,430516.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0102_2A_WH.GlobalReset,430517.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0102_2A_WH.PCSuppress,430517.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_2A_WH.PCUnSuppress,430517.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_2A_WH.PCUnshelve,430517.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_2A_WH.Alarm_Fault,430517.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0102_2A_WH.Shelved,430517.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0102_2A_WH.Suppressed,430517.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0102_2A_WH.PLCIOFault,430517.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2A_WH.PLCF,430517.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2A_WH.TAGR,430517.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0102_2B_WH.Fault,430550.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0102_2B_WH.Faulted,430550.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0102_2B_WH.AlarmState,430550.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0102_2B_WH.FaultInAlarm,430550.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B_WH.Alarm_EN,430550.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0102_2B_WH.REST,430550.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0102_2B_WH.ACKN,430550.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0102_2B_WH.MCmd_Enable,430550.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B_WH.MCmd_Disable,430550.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B_WH.ALRM,430550.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0102_2B_WH.ANUN,430550.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0102_2B_WH.AKED,430550.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0102_2B_WH.Resetable,430550.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_2B_WH.Shelve,430550.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0102_2B_WH.Suppress,430550.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0102_2B_WH.InputAlarm,430550.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0102_2B_WH.GlobalReset,430551.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0102_2B_WH.PCSuppress,430551.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_2B_WH.PCUnSuppress,430551.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_2B_WH.PCUnshelve,430551.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_2B_WH.Alarm_Fault,430551.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0102_2B_WH.Shelved,430551.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0102_2B_WH.Suppressed,430551.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0102_2B_WH.PLCIOFault,430551.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2B_WH.PLCF,430551.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2B_WH.TAGR,430551.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_1A_WH.Fault,430586.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_1A_WH.Faulted,430586.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_1A_WH.AlarmState,430586.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_1A_WH.FaultInAlarm,430586.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A_WH.Alarm_EN,430586.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_1A_WH.REST,430586.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_1A_WH.ACKN,430586.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_1A_WH.MCmd_Enable,430586.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A_WH.MCmd_Disable,430586.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A_WH.ALRM,430586.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_1A_WH.ANUN,430586.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_1A_WH.AKED,430586.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_1A_WH.Resetable,430586.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1A_WH.Shelve,430586.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_1A_WH.Suppress,430586.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_1A_WH.InputAlarm,430586.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_1A_WH.GlobalReset,430587.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_1A_WH.PCSuppress,430587.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1A_WH.PCUnSuppress,430587.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1A_WH.PCUnshelve,430587.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1A_WH.Alarm_Fault,430587.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_1A_WH.Shelved,430587.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_1A_WH.Suppressed,430587.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_1A_WH.PLCIOFault,430587.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1A_WH.PLCF,430587.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1A_WH.TAGR,430587.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_1B_ZF.Fault,430620.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_1B_ZF.Faulted,430620.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_1B_ZF.AlarmState,430620.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_1B_ZF.FaultInAlarm,430620.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF.Alarm_EN,430620.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_1B_ZF.REST,430620.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_1B_ZF.ACKN,430620.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_1B_ZF.MCmd_Enable,430620.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF.MCmd_Disable,430620.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF.ALRM,430620.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_1B_ZF.ANUN,430620.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_1B_ZF.AKED,430620.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_1B_ZF.Resetable,430620.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1B_ZF.Shelve,430620.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_1B_ZF.Suppress,430620.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_1B_ZF.InputAlarm,430620.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_1B_ZF.GlobalReset,430621.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_1B_ZF.PCSuppress,430621.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1B_ZF.PCUnSuppress,430621.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1B_ZF.PCUnshelve,430621.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1B_ZF.Alarm_Fault,430621.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_1B_ZF.Shelved,430621.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_1B_ZF.Suppressed,430621.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_1B_ZF.PLCIOFault,430621.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZF.PLCF,430621.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZF.TAGR,430621.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_1B_ZF2.Fault,430656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_1B_ZF2.Faulted,430656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_1B_ZF2.AlarmState,430656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_1B_ZF2.FaultInAlarm,430656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF2.Alarm_EN,430656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_1B_ZF2.REST,430656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_1B_ZF2.ACKN,430656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_1B_ZF2.MCmd_Enable,430656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF2.MCmd_Disable,430656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF2.ALRM,430656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_1B_ZF2.ANUN,430656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_1B_ZF2.AKED,430656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_1B_ZF2.Resetable,430656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1B_ZF2.Shelve,430656.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_1B_ZF2.Suppress,430656.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_1B_ZF2.InputAlarm,430656.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_1B_ZF2.GlobalReset,430657.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_1B_ZF2.PCSuppress,430657.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1B_ZF2.PCUnSuppress,430657.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1B_ZF2.PCUnshelve,430657.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1B_ZF2.Alarm_Fault,430657.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_1B_ZF2.Shelved,430657.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_1B_ZF2.Suppressed,430657.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_1B_ZF2.PLCIOFault,430657.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZF2.PLCF,430657.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1B_ZF2.TAGR,430657.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_1C_WH.Fault,430690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_1C_WH.Faulted,430690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_1C_WH.AlarmState,430690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_1C_WH.FaultInAlarm,430690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C_WH.Alarm_EN,430690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_1C_WH.REST,430690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_1C_WH.ACKN,430690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_1C_WH.MCmd_Enable,430690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C_WH.MCmd_Disable,430690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C_WH.ALRM,430690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_1C_WH.ANUN,430690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_1C_WH.AKED,430690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_1C_WH.Resetable,430690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1C_WH.Shelve,430690.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_1C_WH.Suppress,430690.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_1C_WH.InputAlarm,430690.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_1C_WH.GlobalReset,430691.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_1C_WH.PCSuppress,430691.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1C_WH.PCUnSuppress,430691.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1C_WH.PCUnshelve,430691.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1C_WH.Alarm_Fault,430691.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_1C_WH.Shelved,430691.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_1C_WH.Suppressed,430691.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_1C_WH.PLCIOFault,430691.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1C_WH.PLCF,430691.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1C_WH.TAGR,430691.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_2A_WH.Fault,430726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_2A_WH.Faulted,430726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_2A_WH.AlarmState,430726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_2A_WH.FaultInAlarm,430726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A_WH.Alarm_EN,430726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_2A_WH.REST,430726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_2A_WH.ACKN,430726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_2A_WH.MCmd_Enable,430726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A_WH.MCmd_Disable,430726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A_WH.ALRM,430726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_2A_WH.ANUN,430726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_2A_WH.AKED,430726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_2A_WH.Resetable,430726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2A_WH.Shelve,430726.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_2A_WH.Suppress,430726.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_2A_WH.InputAlarm,430726.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_2A_WH.GlobalReset,430727.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_2A_WH.PCSuppress,430727.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2A_WH.PCUnSuppress,430727.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2A_WH.PCUnshelve,430727.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2A_WH.Alarm_Fault,430727.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_2A_WH.Shelved,430727.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_2A_WH.Suppressed,430727.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_2A_WH.PLCIOFault,430727.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2A_WH.PLCF,430727.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2A_WH.TAGR,430727.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_2B_ZF.Fault,430760.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_2B_ZF.Faulted,430760.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_2B_ZF.AlarmState,430760.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_2B_ZF.FaultInAlarm,430760.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF.Alarm_EN,430760.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_2B_ZF.REST,430760.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_2B_ZF.ACKN,430760.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_2B_ZF.MCmd_Enable,430760.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF.MCmd_Disable,430760.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF.ALRM,430760.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_2B_ZF.ANUN,430760.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_2B_ZF.AKED,430760.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_2B_ZF.Resetable,430760.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2B_ZF.Shelve,430760.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_2B_ZF.Suppress,430760.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_2B_ZF.InputAlarm,430760.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_2B_ZF.GlobalReset,430761.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_2B_ZF.PCSuppress,430761.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2B_ZF.PCUnSuppress,430761.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2B_ZF.PCUnshelve,430761.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2B_ZF.Alarm_Fault,430761.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_2B_ZF.Shelved,430761.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_2B_ZF.Suppressed,430761.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_2B_ZF.PLCIOFault,430761.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZF.PLCF,430761.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZF.TAGR,430761.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_2B_ZF2.Fault,430796.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_2B_ZF2.Faulted,430796.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_2B_ZF2.AlarmState,430796.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_2B_ZF2.FaultInAlarm,430796.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF2.Alarm_EN,430796.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_2B_ZF2.REST,430796.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_2B_ZF2.ACKN,430796.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_2B_ZF2.MCmd_Enable,430796.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF2.MCmd_Disable,430796.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF2.ALRM,430796.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_2B_ZF2.ANUN,430796.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_2B_ZF2.AKED,430796.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_2B_ZF2.Resetable,430796.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2B_ZF2.Shelve,430796.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_2B_ZF2.Suppress,430796.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_2B_ZF2.InputAlarm,430796.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_2B_ZF2.GlobalReset,430797.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_2B_ZF2.PCSuppress,430797.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2B_ZF2.PCUnSuppress,430797.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2B_ZF2.PCUnshelve,430797.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2B_ZF2.Alarm_Fault,430797.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_2B_ZF2.Shelved,430797.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_2B_ZF2.Suppressed,430797.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_2B_ZF2.PLCIOFault,430797.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZF2.PLCF,430797.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2B_ZF2.TAGR,430797.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_2C_WH.Fault,430830.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_2C_WH.Faulted,430830.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_2C_WH.AlarmState,430830.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_2C_WH.FaultInAlarm,430830.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C_WH.Alarm_EN,430830.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_2C_WH.REST,430830.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_2C_WH.ACKN,430830.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_2C_WH.MCmd_Enable,430830.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C_WH.MCmd_Disable,430830.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C_WH.ALRM,430830.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_2C_WH.ANUN,430830.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_2C_WH.AKED,430830.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_2C_WH.Resetable,430830.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2C_WH.Shelve,430830.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_2C_WH.Suppress,430830.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_2C_WH.InputAlarm,430830.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_2C_WH.GlobalReset,430831.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_2C_WH.PCSuppress,430831.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2C_WH.PCUnSuppress,430831.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2C_WH.PCUnshelve,430831.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2C_WH.Alarm_Fault,430831.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_2C_WH.Shelved,430831.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_2C_WH.Suppressed,430831.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_2C_WH.PLCIOFault,430831.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2C_WH.PLCF,430831.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2C_WH.TAGR,430831.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3A_WH.Fault,430866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3A_WH.Faulted,430866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3A_WH.AlarmState,430866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3A_WH.FaultInAlarm,430866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A_WH.Alarm_EN,430866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3A_WH.REST,430866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3A_WH.ACKN,430866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3A_WH.MCmd_Enable,430866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A_WH.MCmd_Disable,430866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A_WH.ALRM,430866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3A_WH.ANUN,430866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3A_WH.AKED,430866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3A_WH.Resetable,430866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3A_WH.Shelve,430866.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3A_WH.Suppress,430866.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3A_WH.InputAlarm,430866.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3A_WH.GlobalReset,430867.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3A_WH.PCSuppress,430867.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3A_WH.PCUnSuppress,430867.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3A_WH.PCUnshelve,430867.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3A_WH.Alarm_Fault,430867.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3A_WH.Shelved,430867.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3A_WH.Suppressed,430867.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3A_WH.PLCIOFault,430867.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3A_WH.PLCF,430867.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3A_WH.TAGR,430867.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3B_ZF.Fault,430900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3B_ZF.Faulted,430900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3B_ZF.AlarmState,430900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3B_ZF.FaultInAlarm,430900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF.Alarm_EN,430900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3B_ZF.REST,430900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3B_ZF.ACKN,430900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3B_ZF.MCmd_Enable,430900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF.MCmd_Disable,430900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF.ALRM,430900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3B_ZF.ANUN,430900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3B_ZF.AKED,430900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3B_ZF.Resetable,430900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3B_ZF.Shelve,430900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3B_ZF.Suppress,430900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3B_ZF.InputAlarm,430900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3B_ZF.GlobalReset,430901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3B_ZF.PCSuppress,430901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3B_ZF.PCUnSuppress,430901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3B_ZF.PCUnshelve,430901.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3B_ZF.Alarm_Fault,430901.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3B_ZF.Shelved,430901.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3B_ZF.Suppressed,430901.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3B_ZF.PLCIOFault,430901.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF.PLCF,430901.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF.TAGR,430901.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3B_ZF3.Fault,430936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3B_ZF3.Faulted,430936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3B_ZF3.AlarmState,430936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3B_ZF3.FaultInAlarm,430936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF3.Alarm_EN,430936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3B_ZF3.REST,430936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3B_ZF3.ACKN,430936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3B_ZF3.MCmd_Enable,430936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF3.MCmd_Disable,430936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF3.ALRM,430936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3B_ZF3.ANUN,430936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3B_ZF3.AKED,430936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3B_ZF3.Resetable,430936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3B_ZF3.Shelve,430936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3B_ZF3.Suppress,430936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3B_ZF3.InputAlarm,430936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3B_ZF3.GlobalReset,430937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3B_ZF3.PCSuppress,430937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3B_ZF3.PCUnSuppress,430937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3B_ZF3.PCUnshelve,430937.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3B_ZF3.Alarm_Fault,430937.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3B_ZF3.Shelved,430937.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3B_ZF3.Suppressed,430937.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3B_ZF3.PLCIOFault,430937.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF3.PLCF,430937.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF3.TAGR,430937.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3B_ZF4.Fault,430970.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3B_ZF4.Faulted,430970.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3B_ZF4.AlarmState,430970.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3B_ZF4.FaultInAlarm,430970.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF4.Alarm_EN,430970.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3B_ZF4.REST,430970.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3B_ZF4.ACKN,430970.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3B_ZF4.MCmd_Enable,430970.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF4.MCmd_Disable,430970.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF4.ALRM,430970.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3B_ZF4.ANUN,430970.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3B_ZF4.AKED,430970.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3B_ZF4.Resetable,430970.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3B_ZF4.Shelve,430970.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3B_ZF4.Suppress,430970.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3B_ZF4.InputAlarm,430970.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3B_ZF4.GlobalReset,430971.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3B_ZF4.PCSuppress,430971.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3B_ZF4.PCUnSuppress,430971.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3B_ZF4.PCUnshelve,430971.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3B_ZF4.Alarm_Fault,430971.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3B_ZF4.Shelved,430971.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3B_ZF4.Suppressed,430971.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3B_ZF4.PLCIOFault,430971.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF4.PLCF,430971.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3B_ZF4.TAGR,430971.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3C_WH.Fault,431006.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3C_WH.Faulted,431006.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3C_WH.AlarmState,431006.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3C_WH.FaultInAlarm,431006.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C_WH.Alarm_EN,431006.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3C_WH.REST,431006.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3C_WH.ACKN,431006.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3C_WH.MCmd_Enable,431006.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C_WH.MCmd_Disable,431006.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C_WH.ALRM,431006.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3C_WH.ANUN,431006.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3C_WH.AKED,431006.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3C_WH.Resetable,431006.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3C_WH.Shelve,431006.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3C_WH.Suppress,431006.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3C_WH.InputAlarm,431006.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3C_WH.GlobalReset,431007.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3C_WH.PCSuppress,431007.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3C_WH.PCUnSuppress,431007.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3C_WH.PCUnshelve,431007.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3C_WH.Alarm_Fault,431007.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3C_WH.Shelved,431007.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3C_WH.Suppressed,431007.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3C_WH.PLCIOFault,431007.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3C_WH.PLCF,431007.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3C_WH.TAGR,431007.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_3D_WH.Fault,431040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_3D_WH.Faulted,431040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_3D_WH.AlarmState,431040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_3D_WH.FaultInAlarm,431040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D_WH.Alarm_EN,431040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_3D_WH.REST,431040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_3D_WH.ACKN,431040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_3D_WH.MCmd_Enable,431040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D_WH.MCmd_Disable,431040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D_WH.ALRM,431040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_3D_WH.ANUN,431040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_3D_WH.AKED,431040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_3D_WH.Resetable,431040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3D_WH.Shelve,431040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_3D_WH.Suppress,431040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_3D_WH.InputAlarm,431040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_3D_WH.GlobalReset,431041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_3D_WH.PCSuppress,431041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3D_WH.PCUnSuppress,431041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3D_WH.PCUnshelve,431041.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3D_WH.Alarm_Fault,431041.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_3D_WH.Shelved,431041.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_3D_WH.Suppressed,431041.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_3D_WH.PLCIOFault,431041.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3D_WH.PLCF,431041.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3D_WH.TAGR,431041.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4A_WH.Fault,431076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4A_WH.Faulted,431076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4A_WH.AlarmState,431076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4A_WH.FaultInAlarm,431076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A_WH.Alarm_EN,431076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4A_WH.REST,431076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4A_WH.ACKN,431076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4A_WH.MCmd_Enable,431076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A_WH.MCmd_Disable,431076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A_WH.ALRM,431076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4A_WH.ANUN,431076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4A_WH.AKED,431076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4A_WH.Resetable,431076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4A_WH.Shelve,431076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4A_WH.Suppress,431076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4A_WH.InputAlarm,431076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4A_WH.GlobalReset,431077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4A_WH.PCSuppress,431077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4A_WH.PCUnSuppress,431077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4A_WH.PCUnshelve,431077.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4A_WH.Alarm_Fault,431077.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4A_WH.Shelved,431077.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4A_WH.Suppressed,431077.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4A_WH.PLCIOFault,431077.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4A_WH.PLCF,431077.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4A_WH.TAGR,431077.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4B_ZF.Fault,431110.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4B_ZF.Faulted,431110.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4B_ZF.AlarmState,431110.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4B_ZF.FaultInAlarm,431110.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF.Alarm_EN,431110.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4B_ZF.REST,431110.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4B_ZF.ACKN,431110.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4B_ZF.MCmd_Enable,431110.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF.MCmd_Disable,431110.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF.ALRM,431110.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4B_ZF.ANUN,431110.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4B_ZF.AKED,431110.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4B_ZF.Resetable,431110.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4B_ZF.Shelve,431110.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4B_ZF.Suppress,431110.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4B_ZF.InputAlarm,431110.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4B_ZF.GlobalReset,431111.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4B_ZF.PCSuppress,431111.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4B_ZF.PCUnSuppress,431111.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4B_ZF.PCUnshelve,431111.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4B_ZF.Alarm_Fault,431111.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4B_ZF.Shelved,431111.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4B_ZF.Suppressed,431111.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4B_ZF.PLCIOFault,431111.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF.PLCF,431111.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF.TAGR,431111.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4B_ZF3.Fault,431146.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4B_ZF3.Faulted,431146.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4B_ZF3.AlarmState,431146.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4B_ZF3.FaultInAlarm,431146.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF3.Alarm_EN,431146.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4B_ZF3.REST,431146.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4B_ZF3.ACKN,431146.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4B_ZF3.MCmd_Enable,431146.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF3.MCmd_Disable,431146.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF3.ALRM,431146.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4B_ZF3.ANUN,431146.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4B_ZF3.AKED,431146.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4B_ZF3.Resetable,431146.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4B_ZF3.Shelve,431146.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4B_ZF3.Suppress,431146.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4B_ZF3.InputAlarm,431146.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4B_ZF3.GlobalReset,431147.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4B_ZF3.PCSuppress,431147.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4B_ZF3.PCUnSuppress,431147.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4B_ZF3.PCUnshelve,431147.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4B_ZF3.Alarm_Fault,431147.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4B_ZF3.Shelved,431147.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4B_ZF3.Suppressed,431147.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4B_ZF3.PLCIOFault,431147.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF3.PLCF,431147.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF3.TAGR,431147.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4B_ZF4.Fault,431180.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4B_ZF4.Faulted,431180.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4B_ZF4.AlarmState,431180.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4B_ZF4.FaultInAlarm,431180.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF4.Alarm_EN,431180.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4B_ZF4.REST,431180.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4B_ZF4.ACKN,431180.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4B_ZF4.MCmd_Enable,431180.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF4.MCmd_Disable,431180.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF4.ALRM,431180.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4B_ZF4.ANUN,431180.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4B_ZF4.AKED,431180.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4B_ZF4.Resetable,431180.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4B_ZF4.Shelve,431180.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4B_ZF4.Suppress,431180.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4B_ZF4.InputAlarm,431180.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4B_ZF4.GlobalReset,431181.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4B_ZF4.PCSuppress,431181.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4B_ZF4.PCUnSuppress,431181.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4B_ZF4.PCUnshelve,431181.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4B_ZF4.Alarm_Fault,431181.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4B_ZF4.Shelved,431181.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4B_ZF4.Suppressed,431181.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4B_ZF4.PLCIOFault,431181.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF4.PLCF,431181.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4B_ZF4.TAGR,431181.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4C_WH.Fault,431216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4C_WH.Faulted,431216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4C_WH.AlarmState,431216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4C_WH.FaultInAlarm,431216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C_WH.Alarm_EN,431216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4C_WH.REST,431216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4C_WH.ACKN,431216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4C_WH.MCmd_Enable,431216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C_WH.MCmd_Disable,431216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C_WH.ALRM,431216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4C_WH.ANUN,431216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4C_WH.AKED,431216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4C_WH.Resetable,431216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4C_WH.Shelve,431216.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4C_WH.Suppress,431216.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4C_WH.InputAlarm,431216.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4C_WH.GlobalReset,431217.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4C_WH.PCSuppress,431217.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4C_WH.PCUnSuppress,431217.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4C_WH.PCUnshelve,431217.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4C_WH.Alarm_Fault,431217.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4C_WH.Shelved,431217.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4C_WH.Suppressed,431217.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4C_WH.PLCIOFault,431217.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4C_WH.PLCF,431217.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4C_WH.TAGR,431217.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_4D_WH.Fault,431250.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_4D_WH.Faulted,431250.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_4D_WH.AlarmState,431250.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_4D_WH.FaultInAlarm,431250.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D_WH.Alarm_EN,431250.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_4D_WH.REST,431250.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_4D_WH.ACKN,431250.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_4D_WH.MCmd_Enable,431250.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D_WH.MCmd_Disable,431250.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D_WH.ALRM,431250.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_4D_WH.ANUN,431250.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_4D_WH.AKED,431250.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_4D_WH.Resetable,431250.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4D_WH.Shelve,431250.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_4D_WH.Suppress,431250.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_4D_WH.InputAlarm,431250.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_4D_WH.GlobalReset,431251.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_4D_WH.PCSuppress,431251.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4D_WH.PCUnSuppress,431251.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4D_WH.PCUnshelve,431251.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4D_WH.Alarm_Fault,431251.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_4D_WH.Shelved,431251.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_4D_WH.Suppressed,431251.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_4D_WH.PLCIOFault,431251.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4D_WH.PLCF,431251.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4D_WH.TAGR,431251.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5A_WH.Fault,431286.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5A_WH.Faulted,431286.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5A_WH.AlarmState,431286.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5A_WH.FaultInAlarm,431286.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A_WH.Alarm_EN,431286.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5A_WH.REST,431286.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5A_WH.ACKN,431286.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5A_WH.MCmd_Enable,431286.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A_WH.MCmd_Disable,431286.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A_WH.ALRM,431286.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5A_WH.ANUN,431286.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5A_WH.AKED,431286.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5A_WH.Resetable,431286.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5A_WH.Shelve,431286.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5A_WH.Suppress,431286.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5A_WH.InputAlarm,431286.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5A_WH.GlobalReset,431287.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5A_WH.PCSuppress,431287.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5A_WH.PCUnSuppress,431287.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5A_WH.PCUnshelve,431287.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5A_WH.Alarm_Fault,431287.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5A_WH.Shelved,431287.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5A_WH.Suppressed,431287.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5A_WH.PLCIOFault,431287.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5A_WH.PLCF,431287.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5A_WH.TAGR,431287.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5B_ZF.Fault,431320.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5B_ZF.Faulted,431320.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5B_ZF.AlarmState,431320.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5B_ZF.FaultInAlarm,431320.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF.Alarm_EN,431320.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5B_ZF.REST,431320.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5B_ZF.ACKN,431320.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5B_ZF.MCmd_Enable,431320.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF.MCmd_Disable,431320.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF.ALRM,431320.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5B_ZF.ANUN,431320.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5B_ZF.AKED,431320.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5B_ZF.Resetable,431320.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5B_ZF.Shelve,431320.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5B_ZF.Suppress,431320.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5B_ZF.InputAlarm,431320.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5B_ZF.GlobalReset,431321.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5B_ZF.PCSuppress,431321.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5B_ZF.PCUnSuppress,431321.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5B_ZF.PCUnshelve,431321.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5B_ZF.Alarm_Fault,431321.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5B_ZF.Shelved,431321.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5B_ZF.Suppressed,431321.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5B_ZF.PLCIOFault,431321.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF.PLCF,431321.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF.TAGR,431321.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5B_ZF3.Fault,431356.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5B_ZF3.Faulted,431356.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5B_ZF3.AlarmState,431356.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5B_ZF3.FaultInAlarm,431356.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF3.Alarm_EN,431356.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5B_ZF3.REST,431356.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5B_ZF3.ACKN,431356.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5B_ZF3.MCmd_Enable,431356.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF3.MCmd_Disable,431356.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF3.ALRM,431356.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5B_ZF3.ANUN,431356.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5B_ZF3.AKED,431356.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5B_ZF3.Resetable,431356.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5B_ZF3.Shelve,431356.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5B_ZF3.Suppress,431356.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5B_ZF3.InputAlarm,431356.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5B_ZF3.GlobalReset,431357.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5B_ZF3.PCSuppress,431357.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5B_ZF3.PCUnSuppress,431357.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5B_ZF3.PCUnshelve,431357.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5B_ZF3.Alarm_Fault,431357.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5B_ZF3.Shelved,431357.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5B_ZF3.Suppressed,431357.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5B_ZF3.PLCIOFault,431357.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF3.PLCF,431357.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF3.TAGR,431357.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5B_ZF4.Fault,431390.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5B_ZF4.Faulted,431390.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5B_ZF4.AlarmState,431390.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5B_ZF4.FaultInAlarm,431390.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF4.Alarm_EN,431390.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5B_ZF4.REST,431390.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5B_ZF4.ACKN,431390.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5B_ZF4.MCmd_Enable,431390.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF4.MCmd_Disable,431390.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF4.ALRM,431390.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5B_ZF4.ANUN,431390.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5B_ZF4.AKED,431390.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5B_ZF4.Resetable,431390.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5B_ZF4.Shelve,431390.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5B_ZF4.Suppress,431390.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5B_ZF4.InputAlarm,431390.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5B_ZF4.GlobalReset,431391.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5B_ZF4.PCSuppress,431391.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5B_ZF4.PCUnSuppress,431391.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5B_ZF4.PCUnshelve,431391.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5B_ZF4.Alarm_Fault,431391.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5B_ZF4.Shelved,431391.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5B_ZF4.Suppressed,431391.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5B_ZF4.PLCIOFault,431391.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF4.PLCF,431391.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5B_ZF4.TAGR,431391.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5C_WH.Fault,431426.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5C_WH.Faulted,431426.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5C_WH.AlarmState,431426.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5C_WH.FaultInAlarm,431426.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C_WH.Alarm_EN,431426.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5C_WH.REST,431426.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5C_WH.ACKN,431426.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5C_WH.MCmd_Enable,431426.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C_WH.MCmd_Disable,431426.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C_WH.ALRM,431426.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5C_WH.ANUN,431426.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5C_WH.AKED,431426.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5C_WH.Resetable,431426.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5C_WH.Shelve,431426.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5C_WH.Suppress,431426.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5C_WH.InputAlarm,431426.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5C_WH.GlobalReset,431427.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5C_WH.PCSuppress,431427.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5C_WH.PCUnSuppress,431427.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5C_WH.PCUnshelve,431427.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5C_WH.Alarm_Fault,431427.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5C_WH.Shelved,431427.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5C_WH.Suppressed,431427.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5C_WH.PLCIOFault,431427.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5C_WH.PLCF,431427.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5C_WH.TAGR,431427.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_5D_WH.Fault,431460.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_5D_WH.Faulted,431460.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_5D_WH.AlarmState,431460.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_5D_WH.FaultInAlarm,431460.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D_WH.Alarm_EN,431460.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_5D_WH.REST,431460.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_5D_WH.ACKN,431460.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_5D_WH.MCmd_Enable,431460.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D_WH.MCmd_Disable,431460.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D_WH.ALRM,431460.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_5D_WH.ANUN,431460.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_5D_WH.AKED,431460.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_5D_WH.Resetable,431460.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5D_WH.Shelve,431460.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_5D_WH.Suppress,431460.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_5D_WH.InputAlarm,431460.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_5D_WH.GlobalReset,431461.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_5D_WH.PCSuppress,431461.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5D_WH.PCUnSuppress,431461.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5D_WH.PCUnshelve,431461.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5D_WH.Alarm_Fault,431461.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_5D_WH.Shelved,431461.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_5D_WH.Suppressed,431461.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_5D_WH.PLCIOFault,431461.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5D_WH.PLCF,431461.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5D_WH.TAGR,431461.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6A_WH.Fault,431496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6A_WH.Faulted,431496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6A_WH.AlarmState,431496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6A_WH.FaultInAlarm,431496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A_WH.Alarm_EN,431496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6A_WH.REST,431496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6A_WH.ACKN,431496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6A_WH.MCmd_Enable,431496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A_WH.MCmd_Disable,431496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A_WH.ALRM,431496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6A_WH.ANUN,431496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6A_WH.AKED,431496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6A_WH.Resetable,431496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6A_WH.Shelve,431496.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6A_WH.Suppress,431496.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6A_WH.InputAlarm,431496.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6A_WH.GlobalReset,431497.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6A_WH.PCSuppress,431497.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6A_WH.PCUnSuppress,431497.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6A_WH.PCUnshelve,431497.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6A_WH.Alarm_Fault,431497.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6A_WH.Shelved,431497.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6A_WH.Suppressed,431497.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6A_WH.PLCIOFault,431497.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6A_WH.PLCF,431497.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6A_WH.TAGR,431497.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6B_ZF.Fault,431530.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6B_ZF.Faulted,431530.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6B_ZF.AlarmState,431530.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6B_ZF.FaultInAlarm,431530.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF.Alarm_EN,431530.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6B_ZF.REST,431530.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6B_ZF.ACKN,431530.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6B_ZF.MCmd_Enable,431530.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF.MCmd_Disable,431530.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF.ALRM,431530.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6B_ZF.ANUN,431530.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6B_ZF.AKED,431530.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6B_ZF.Resetable,431530.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6B_ZF.Shelve,431530.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6B_ZF.Suppress,431530.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6B_ZF.InputAlarm,431530.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6B_ZF.GlobalReset,431531.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6B_ZF.PCSuppress,431531.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6B_ZF.PCUnSuppress,431531.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6B_ZF.PCUnshelve,431531.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6B_ZF.Alarm_Fault,431531.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6B_ZF.Shelved,431531.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6B_ZF.Suppressed,431531.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6B_ZF.PLCIOFault,431531.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF.PLCF,431531.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF.TAGR,431531.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6B_ZF3.Fault,431566.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6B_ZF3.Faulted,431566.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6B_ZF3.AlarmState,431566.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6B_ZF3.FaultInAlarm,431566.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF3.Alarm_EN,431566.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6B_ZF3.REST,431566.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6B_ZF3.ACKN,431566.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6B_ZF3.MCmd_Enable,431566.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF3.MCmd_Disable,431566.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF3.ALRM,431566.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6B_ZF3.ANUN,431566.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6B_ZF3.AKED,431566.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6B_ZF3.Resetable,431566.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6B_ZF3.Shelve,431566.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6B_ZF3.Suppress,431566.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6B_ZF3.InputAlarm,431566.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6B_ZF3.GlobalReset,431567.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6B_ZF3.PCSuppress,431567.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6B_ZF3.PCUnSuppress,431567.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6B_ZF3.PCUnshelve,431567.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6B_ZF3.Alarm_Fault,431567.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6B_ZF3.Shelved,431567.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6B_ZF3.Suppressed,431567.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6B_ZF3.PLCIOFault,431567.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF3.PLCF,431567.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF3.TAGR,431567.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6B_ZF4.Fault,431600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6B_ZF4.Faulted,431600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6B_ZF4.AlarmState,431600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6B_ZF4.FaultInAlarm,431600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF4.Alarm_EN,431600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6B_ZF4.REST,431600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6B_ZF4.ACKN,431600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6B_ZF4.MCmd_Enable,431600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF4.MCmd_Disable,431600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF4.ALRM,431600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6B_ZF4.ANUN,431600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6B_ZF4.AKED,431600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6B_ZF4.Resetable,431600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6B_ZF4.Shelve,431600.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6B_ZF4.Suppress,431600.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6B_ZF4.InputAlarm,431600.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6B_ZF4.GlobalReset,431601.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6B_ZF4.PCSuppress,431601.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6B_ZF4.PCUnSuppress,431601.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6B_ZF4.PCUnshelve,431601.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6B_ZF4.Alarm_Fault,431601.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6B_ZF4.Shelved,431601.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6B_ZF4.Suppressed,431601.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6B_ZF4.PLCIOFault,431601.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF4.PLCF,431601.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6B_ZF4.TAGR,431601.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6C_WH.Fault,431636.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6C_WH.Faulted,431636.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6C_WH.AlarmState,431636.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6C_WH.FaultInAlarm,431636.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C_WH.Alarm_EN,431636.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6C_WH.REST,431636.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6C_WH.ACKN,431636.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6C_WH.MCmd_Enable,431636.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C_WH.MCmd_Disable,431636.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C_WH.ALRM,431636.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6C_WH.ANUN,431636.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6C_WH.AKED,431636.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6C_WH.Resetable,431636.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6C_WH.Shelve,431636.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6C_WH.Suppress,431636.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6C_WH.InputAlarm,431636.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6C_WH.GlobalReset,431637.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6C_WH.PCSuppress,431637.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6C_WH.PCUnSuppress,431637.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6C_WH.PCUnshelve,431637.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6C_WH.Alarm_Fault,431637.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6C_WH.Shelved,431637.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6C_WH.Suppressed,431637.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6C_WH.PLCIOFault,431637.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6C_WH.PLCF,431637.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6C_WH.TAGR,431637.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_6D_WH.Fault,431670.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_6D_WH.Faulted,431670.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_6D_WH.AlarmState,431670.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_6D_WH.FaultInAlarm,431670.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D_WH.Alarm_EN,431670.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_6D_WH.REST,431670.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_6D_WH.ACKN,431670.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_6D_WH.MCmd_Enable,431670.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D_WH.MCmd_Disable,431670.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D_WH.ALRM,431670.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_6D_WH.ANUN,431670.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_6D_WH.AKED,431670.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_6D_WH.Resetable,431670.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6D_WH.Shelve,431670.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_6D_WH.Suppress,431670.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_6D_WH.InputAlarm,431670.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_6D_WH.GlobalReset,431671.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_6D_WH.PCSuppress,431671.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6D_WH.PCUnSuppress,431671.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6D_WH.PCUnshelve,431671.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6D_WH.Alarm_Fault,431671.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_6D_WH.Shelved,431671.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_6D_WH.Suppressed,431671.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_6D_WH.PLCIOFault,431671.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6D_WH.PLCF,431671.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6D_WH.TAGR,431671.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7A_WH.Fault,431706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7A_WH.Faulted,431706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7A_WH.AlarmState,431706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7A_WH.FaultInAlarm,431706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A_WH.Alarm_EN,431706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7A_WH.REST,431706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7A_WH.ACKN,431706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7A_WH.MCmd_Enable,431706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A_WH.MCmd_Disable,431706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A_WH.ALRM,431706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7A_WH.ANUN,431706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7A_WH.AKED,431706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7A_WH.Resetable,431706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7A_WH.Shelve,431706.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7A_WH.Suppress,431706.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7A_WH.InputAlarm,431706.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7A_WH.GlobalReset,431707.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7A_WH.PCSuppress,431707.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7A_WH.PCUnSuppress,431707.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7A_WH.PCUnshelve,431707.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7A_WH.Alarm_Fault,431707.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7A_WH.Shelved,431707.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7A_WH.Suppressed,431707.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7A_WH.PLCIOFault,431707.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7A_WH.PLCF,431707.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7A_WH.TAGR,431707.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7B_ZF.Fault,431740.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7B_ZF.Faulted,431740.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7B_ZF.AlarmState,431740.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7B_ZF.FaultInAlarm,431740.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF.Alarm_EN,431740.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7B_ZF.REST,431740.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7B_ZF.ACKN,431740.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7B_ZF.MCmd_Enable,431740.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF.MCmd_Disable,431740.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF.ALRM,431740.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7B_ZF.ANUN,431740.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7B_ZF.AKED,431740.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7B_ZF.Resetable,431740.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7B_ZF.Shelve,431740.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7B_ZF.Suppress,431740.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7B_ZF.InputAlarm,431740.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7B_ZF.GlobalReset,431741.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7B_ZF.PCSuppress,431741.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7B_ZF.PCUnSuppress,431741.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7B_ZF.PCUnshelve,431741.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7B_ZF.Alarm_Fault,431741.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7B_ZF.Shelved,431741.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7B_ZF.Suppressed,431741.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7B_ZF.PLCIOFault,431741.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF.PLCF,431741.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF.TAGR,431741.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7B_ZF3.Fault,431776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7B_ZF3.Faulted,431776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7B_ZF3.AlarmState,431776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7B_ZF3.FaultInAlarm,431776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF3.Alarm_EN,431776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7B_ZF3.REST,431776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7B_ZF3.ACKN,431776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7B_ZF3.MCmd_Enable,431776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF3.MCmd_Disable,431776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF3.ALRM,431776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7B_ZF3.ANUN,431776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7B_ZF3.AKED,431776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7B_ZF3.Resetable,431776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7B_ZF3.Shelve,431776.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7B_ZF3.Suppress,431776.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7B_ZF3.InputAlarm,431776.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7B_ZF3.GlobalReset,431777.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7B_ZF3.PCSuppress,431777.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7B_ZF3.PCUnSuppress,431777.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7B_ZF3.PCUnshelve,431777.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7B_ZF3.Alarm_Fault,431777.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7B_ZF3.Shelved,431777.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7B_ZF3.Suppressed,431777.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7B_ZF3.PLCIOFault,431777.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF3.PLCF,431777.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF3.TAGR,431777.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7B_ZF4.Fault,431810.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7B_ZF4.Faulted,431810.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7B_ZF4.AlarmState,431810.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7B_ZF4.FaultInAlarm,431810.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF4.Alarm_EN,431810.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7B_ZF4.REST,431810.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7B_ZF4.ACKN,431810.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7B_ZF4.MCmd_Enable,431810.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF4.MCmd_Disable,431810.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF4.ALRM,431810.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7B_ZF4.ANUN,431810.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7B_ZF4.AKED,431810.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7B_ZF4.Resetable,431810.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7B_ZF4.Shelve,431810.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7B_ZF4.Suppress,431810.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7B_ZF4.InputAlarm,431810.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7B_ZF4.GlobalReset,431811.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7B_ZF4.PCSuppress,431811.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7B_ZF4.PCUnSuppress,431811.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7B_ZF4.PCUnshelve,431811.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7B_ZF4.Alarm_Fault,431811.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7B_ZF4.Shelved,431811.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7B_ZF4.Suppressed,431811.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7B_ZF4.PLCIOFault,431811.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF4.PLCF,431811.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7B_ZF4.TAGR,431811.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7C_WH.Fault,431846.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7C_WH.Faulted,431846.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7C_WH.AlarmState,431846.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7C_WH.FaultInAlarm,431846.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C_WH.Alarm_EN,431846.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7C_WH.REST,431846.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7C_WH.ACKN,431846.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7C_WH.MCmd_Enable,431846.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C_WH.MCmd_Disable,431846.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C_WH.ALRM,431846.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7C_WH.ANUN,431846.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7C_WH.AKED,431846.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7C_WH.Resetable,431846.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7C_WH.Shelve,431846.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7C_WH.Suppress,431846.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7C_WH.InputAlarm,431846.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7C_WH.GlobalReset,431847.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7C_WH.PCSuppress,431847.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7C_WH.PCUnSuppress,431847.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7C_WH.PCUnshelve,431847.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7C_WH.Alarm_Fault,431847.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7C_WH.Shelved,431847.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7C_WH.Suppressed,431847.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7C_WH.PLCIOFault,431847.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7C_WH.PLCF,431847.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7C_WH.TAGR,431847.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_7D_WH.Fault,431880.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_7D_WH.Faulted,431880.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_7D_WH.AlarmState,431880.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_7D_WH.FaultInAlarm,431880.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D_WH.Alarm_EN,431880.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_7D_WH.REST,431880.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_7D_WH.ACKN,431880.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_7D_WH.MCmd_Enable,431880.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D_WH.MCmd_Disable,431880.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D_WH.ALRM,431880.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_7D_WH.ANUN,431880.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_7D_WH.AKED,431880.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_7D_WH.Resetable,431880.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7D_WH.Shelve,431880.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_7D_WH.Suppress,431880.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_7D_WH.InputAlarm,431880.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_7D_WH.GlobalReset,431881.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_7D_WH.PCSuppress,431881.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7D_WH.PCUnSuppress,431881.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7D_WH.PCUnshelve,431881.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7D_WH.Alarm_Fault,431881.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_7D_WH.Shelved,431881.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_7D_WH.Suppressed,431881.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_7D_WH.PLCIOFault,431881.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7D_WH.PLCF,431881.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7D_WH.TAGR,431881.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8A_WH.Fault,431916.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8A_WH.Faulted,431916.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8A_WH.AlarmState,431916.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8A_WH.FaultInAlarm,431916.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A_WH.Alarm_EN,431916.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8A_WH.REST,431916.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8A_WH.ACKN,431916.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8A_WH.MCmd_Enable,431916.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A_WH.MCmd_Disable,431916.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A_WH.ALRM,431916.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8A_WH.ANUN,431916.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8A_WH.AKED,431916.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8A_WH.Resetable,431916.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8A_WH.Shelve,431916.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8A_WH.Suppress,431916.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8A_WH.InputAlarm,431916.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8A_WH.GlobalReset,431917.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8A_WH.PCSuppress,431917.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8A_WH.PCUnSuppress,431917.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8A_WH.PCUnshelve,431917.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8A_WH.Alarm_Fault,431917.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8A_WH.Shelved,431917.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8A_WH.Suppressed,431917.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8A_WH.PLCIOFault,431917.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8A_WH.PLCF,431917.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8A_WH.TAGR,431917.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8B_ZF.Fault,431950.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8B_ZF.Faulted,431950.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8B_ZF.AlarmState,431950.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8B_ZF.FaultInAlarm,431950.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF.Alarm_EN,431950.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8B_ZF.REST,431950.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8B_ZF.ACKN,431950.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8B_ZF.MCmd_Enable,431950.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF.MCmd_Disable,431950.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF.ALRM,431950.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8B_ZF.ANUN,431950.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8B_ZF.AKED,431950.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8B_ZF.Resetable,431950.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8B_ZF.Shelve,431950.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8B_ZF.Suppress,431950.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8B_ZF.InputAlarm,431950.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8B_ZF.GlobalReset,431951.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8B_ZF.PCSuppress,431951.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8B_ZF.PCUnSuppress,431951.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8B_ZF.PCUnshelve,431951.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8B_ZF.Alarm_Fault,431951.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8B_ZF.Shelved,431951.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8B_ZF.Suppressed,431951.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8B_ZF.PLCIOFault,431951.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF.PLCF,431951.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF.TAGR,431951.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8B_ZF3.Fault,431986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8B_ZF3.Faulted,431986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8B_ZF3.AlarmState,431986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8B_ZF3.FaultInAlarm,431986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF3.Alarm_EN,431986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8B_ZF3.REST,431986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8B_ZF3.ACKN,431986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8B_ZF3.MCmd_Enable,431986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF3.MCmd_Disable,431986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF3.ALRM,431986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8B_ZF3.ANUN,431986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8B_ZF3.AKED,431986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8B_ZF3.Resetable,431986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8B_ZF3.Shelve,431986.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8B_ZF3.Suppress,431986.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8B_ZF3.InputAlarm,431986.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8B_ZF3.GlobalReset,431987.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8B_ZF3.PCSuppress,431987.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8B_ZF3.PCUnSuppress,431987.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8B_ZF3.PCUnshelve,431987.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8B_ZF3.Alarm_Fault,431987.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8B_ZF3.Shelved,431987.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8B_ZF3.Suppressed,431987.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8B_ZF3.PLCIOFault,431987.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF3.PLCF,431987.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF3.TAGR,431987.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8B_ZF4.Fault,432020.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8B_ZF4.Faulted,432020.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8B_ZF4.AlarmState,432020.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8B_ZF4.FaultInAlarm,432020.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF4.Alarm_EN,432020.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8B_ZF4.REST,432020.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8B_ZF4.ACKN,432020.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8B_ZF4.MCmd_Enable,432020.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF4.MCmd_Disable,432020.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF4.ALRM,432020.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8B_ZF4.ANUN,432020.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8B_ZF4.AKED,432020.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8B_ZF4.Resetable,432020.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8B_ZF4.Shelve,432020.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8B_ZF4.Suppress,432020.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8B_ZF4.InputAlarm,432020.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8B_ZF4.GlobalReset,432021.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8B_ZF4.PCSuppress,432021.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8B_ZF4.PCUnSuppress,432021.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8B_ZF4.PCUnshelve,432021.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8B_ZF4.Alarm_Fault,432021.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8B_ZF4.Shelved,432021.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8B_ZF4.Suppressed,432021.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8B_ZF4.PLCIOFault,432021.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF4.PLCF,432021.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8B_ZF4.TAGR,432021.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8C_WH.Fault,432056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8C_WH.Faulted,432056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8C_WH.AlarmState,432056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8C_WH.FaultInAlarm,432056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C_WH.Alarm_EN,432056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8C_WH.REST,432056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8C_WH.ACKN,432056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8C_WH.MCmd_Enable,432056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C_WH.MCmd_Disable,432056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C_WH.ALRM,432056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8C_WH.ANUN,432056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8C_WH.AKED,432056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8C_WH.Resetable,432056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8C_WH.Shelve,432056.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8C_WH.Suppress,432056.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8C_WH.InputAlarm,432056.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8C_WH.GlobalReset,432057.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8C_WH.PCSuppress,432057.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8C_WH.PCUnSuppress,432057.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8C_WH.PCUnshelve,432057.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8C_WH.Alarm_Fault,432057.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8C_WH.Shelved,432057.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8C_WH.Suppressed,432057.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8C_WH.PLCIOFault,432057.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8C_WH.PLCF,432057.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8C_WH.TAGR,432057.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_8D_WH.Fault,432090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_8D_WH.Faulted,432090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_8D_WH.AlarmState,432090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_8D_WH.FaultInAlarm,432090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D_WH.Alarm_EN,432090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_8D_WH.REST,432090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_8D_WH.ACKN,432090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_8D_WH.MCmd_Enable,432090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D_WH.MCmd_Disable,432090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D_WH.ALRM,432090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_8D_WH.ANUN,432090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_8D_WH.AKED,432090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_8D_WH.Resetable,432090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8D_WH.Shelve,432090.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_8D_WH.Suppress,432090.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_8D_WH.InputAlarm,432090.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_8D_WH.GlobalReset,432091.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_8D_WH.PCSuppress,432091.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8D_WH.PCUnSuppress,432091.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8D_WH.PCUnshelve,432091.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8D_WH.Alarm_Fault,432091.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_8D_WH.Shelved,432091.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_8D_WH.Suppressed,432091.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_8D_WH.PLCIOFault,432091.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8D_WH.PLCF,432091.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8D_WH.TAGR,432091.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_9A_WH.Fault,432126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_9A_WH.Faulted,432126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_9A_WH.AlarmState,432126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_9A_WH.FaultInAlarm,432126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A_WH.Alarm_EN,432126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_9A_WH.REST,432126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_9A_WH.ACKN,432126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_9A_WH.MCmd_Enable,432126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A_WH.MCmd_Disable,432126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A_WH.ALRM,432126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_9A_WH.ANUN,432126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_9A_WH.AKED,432126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_9A_WH.Resetable,432126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9A_WH.Shelve,432126.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_9A_WH.Suppress,432126.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_9A_WH.InputAlarm,432126.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_9A_WH.GlobalReset,432127.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_9A_WH.PCSuppress,432127.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9A_WH.PCUnSuppress,432127.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9A_WH.PCUnshelve,432127.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9A_WH.Alarm_Fault,432127.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_9A_WH.Shelved,432127.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_9A_WH.Suppressed,432127.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_9A_WH.PLCIOFault,432127.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9A_WH.PLCF,432127.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9A_WH.TAGR,432127.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_9B_ZF.Fault,432160.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_9B_ZF.Faulted,432160.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_9B_ZF.AlarmState,432160.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_9B_ZF.FaultInAlarm,432160.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF.Alarm_EN,432160.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_9B_ZF.REST,432160.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_9B_ZF.ACKN,432160.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_9B_ZF.MCmd_Enable,432160.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF.MCmd_Disable,432160.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF.ALRM,432160.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_9B_ZF.ANUN,432160.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_9B_ZF.AKED,432160.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_9B_ZF.Resetable,432160.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9B_ZF.Shelve,432160.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_9B_ZF.Suppress,432160.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_9B_ZF.InputAlarm,432160.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_9B_ZF.GlobalReset,432161.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_9B_ZF.PCSuppress,432161.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9B_ZF.PCUnSuppress,432161.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9B_ZF.PCUnshelve,432161.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9B_ZF.Alarm_Fault,432161.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_9B_ZF.Shelved,432161.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_9B_ZF.Suppressed,432161.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_9B_ZF.PLCIOFault,432161.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZF.PLCF,432161.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZF.TAGR,432161.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_9B_ZF2.Fault,432196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_9B_ZF2.Faulted,432196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_9B_ZF2.AlarmState,432196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_9B_ZF2.FaultInAlarm,432196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF2.Alarm_EN,432196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_9B_ZF2.REST,432196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_9B_ZF2.ACKN,432196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_9B_ZF2.MCmd_Enable,432196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF2.MCmd_Disable,432196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF2.ALRM,432196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_9B_ZF2.ANUN,432196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_9B_ZF2.AKED,432196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_9B_ZF2.Resetable,432196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9B_ZF2.Shelve,432196.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_9B_ZF2.Suppress,432196.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_9B_ZF2.InputAlarm,432196.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_9B_ZF2.GlobalReset,432197.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_9B_ZF2.PCSuppress,432197.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9B_ZF2.PCUnSuppress,432197.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9B_ZF2.PCUnshelve,432197.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9B_ZF2.Alarm_Fault,432197.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_9B_ZF2.Shelved,432197.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_9B_ZF2.Suppressed,432197.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_9B_ZF2.PLCIOFault,432197.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZF2.PLCF,432197.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9B_ZF2.TAGR,432197.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0103_9C_WH.Fault,432230.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0103_9C_WH.Faulted,432230.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0103_9C_WH.AlarmState,432230.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0103_9C_WH.FaultInAlarm,432230.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C_WH.Alarm_EN,432230.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0103_9C_WH.REST,432230.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0103_9C_WH.ACKN,432230.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0103_9C_WH.MCmd_Enable,432230.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C_WH.MCmd_Disable,432230.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C_WH.ALRM,432230.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0103_9C_WH.ANUN,432230.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0103_9C_WH.AKED,432230.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0103_9C_WH.Resetable,432230.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9C_WH.Shelve,432230.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0103_9C_WH.Suppress,432230.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0103_9C_WH.InputAlarm,432230.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0103_9C_WH.GlobalReset,432231.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0103_9C_WH.PCSuppress,432231.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9C_WH.PCUnSuppress,432231.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9C_WH.PCUnshelve,432231.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9C_WH.Alarm_Fault,432231.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0103_9C_WH.Shelved,432231.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0103_9C_WH.Suppressed,432231.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0103_9C_WH.PLCIOFault,432231.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9C_WH.PLCF,432231.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9C_WH.TAGR,432231.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0113_2A_WH.Fault,432266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0113_2A_WH.Faulted,432266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0113_2A_WH.AlarmState,432266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0113_2A_WH.FaultInAlarm,432266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A_WH.Alarm_EN,432266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0113_2A_WH.REST,432266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0113_2A_WH.ACKN,432266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0113_2A_WH.MCmd_Enable,432266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A_WH.MCmd_Disable,432266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A_WH.ALRM,432266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0113_2A_WH.ANUN,432266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0113_2A_WH.AKED,432266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0113_2A_WH.Resetable,432266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2A_WH.Shelve,432266.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0113_2A_WH.Suppress,432266.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0113_2A_WH.InputAlarm,432266.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0113_2A_WH.GlobalReset,432267.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0113_2A_WH.PCSuppress,432267.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2A_WH.PCUnSuppress,432267.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2A_WH.PCUnshelve,432267.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2A_WH.Alarm_Fault,432267.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0113_2A_WH.Shelved,432267.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0113_2A_WH.Suppressed,432267.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0113_2A_WH.PLCIOFault,432267.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2A_WH.PLCF,432267.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2A_WH.TAGR,432267.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0113_2B_WH.Fault,432300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0113_2B_WH.Faulted,432300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0113_2B_WH.AlarmState,432300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0113_2B_WH.FaultInAlarm,432300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B_WH.Alarm_EN,432300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0113_2B_WH.REST,432300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0113_2B_WH.ACKN,432300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0113_2B_WH.MCmd_Enable,432300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B_WH.MCmd_Disable,432300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B_WH.ALRM,432300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0113_2B_WH.ANUN,432300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0113_2B_WH.AKED,432300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0113_2B_WH.Resetable,432300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2B_WH.Shelve,432300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0113_2B_WH.Suppress,432300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0113_2B_WH.InputAlarm,432300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0113_2B_WH.GlobalReset,432301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0113_2B_WH.PCSuppress,432301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2B_WH.PCUnSuppress,432301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2B_WH.PCUnshelve,432301.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2B_WH.Alarm_Fault,432301.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0113_2B_WH.Shelved,432301.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0113_2B_WH.Suppressed,432301.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0113_2B_WH.PLCIOFault,432301.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2B_WH.PLCF,432301.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2B_WH.TAGR,432301.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0113_2C_WH.Fault,432336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0113_2C_WH.Faulted,432336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0113_2C_WH.AlarmState,432336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0113_2C_WH.FaultInAlarm,432336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C_WH.Alarm_EN,432336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0113_2C_WH.REST,432336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0113_2C_WH.ACKN,432336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0113_2C_WH.MCmd_Enable,432336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C_WH.MCmd_Disable,432336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C_WH.ALRM,432336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0113_2C_WH.ANUN,432336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0113_2C_WH.AKED,432336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0113_2C_WH.Resetable,432336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2C_WH.Shelve,432336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0113_2C_WH.Suppress,432336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0113_2C_WH.InputAlarm,432336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0113_2C_WH.GlobalReset,432337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0113_2C_WH.PCSuppress,432337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2C_WH.PCUnSuppress,432337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2C_WH.PCUnshelve,432337.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2C_WH.Alarm_Fault,432337.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0113_2C_WH.Shelved,432337.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0113_2C_WH.Suppressed,432337.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0113_2C_WH.PLCIOFault,432337.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2C_WH.PLCF,432337.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2C_WH.TAGR,432337.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_FV_0113_2D_WH.Fault,432370.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_FV_0113_2D_WH.Faulted,432370.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_FV_0113_2D_WH.AlarmState,432370.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_FV_0113_2D_WH.FaultInAlarm,432370.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D_WH.Alarm_EN,432370.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_FV_0113_2D_WH.REST,432370.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_FV_0113_2D_WH.ACKN,432370.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_FV_0113_2D_WH.MCmd_Enable,432370.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D_WH.MCmd_Disable,432370.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D_WH.ALRM,432370.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_FV_0113_2D_WH.ANUN,432370.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_FV_0113_2D_WH.AKED,432370.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_FV_0113_2D_WH.Resetable,432370.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2D_WH.Shelve,432370.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_FV_0113_2D_WH.Suppress,432370.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_FV_0113_2D_WH.InputAlarm,432370.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_FV_0113_2D_WH.GlobalReset,432371.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_FV_0113_2D_WH.PCSuppress,432371.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2D_WH.PCUnSuppress,432371.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2D_WH.PCUnshelve,432371.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2D_WH.Alarm_Fault,432371.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_FV_0113_2D_WH.Shelved,432371.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_FV_0113_2D_WH.Suppressed,432371.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_FV_0113_2D_WH.PLCIOFault,432371.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2D_WH.PLCF,432371.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2D_WH.TAGR,432371.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_LL.Fault,432406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_LL.Faulted,432406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_LL.AlarmState,432406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_LL.FaultInAlarm,432406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_LL.Alarm_EN,432406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_LL.REST,432406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_LL.ACKN,432406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_LL.MCmd_Enable,432406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_LL.MCmd_Disable,432406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_LL.ALRM,432406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_LL.ANUN,432406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_LL.AKED,432406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_LL.Resetable,432406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_LL.Shelve,432406.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_LL.Suppress,432406.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_LL.InputAlarm,432406.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_LL.GlobalReset,432407.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_LL.PCSuppress,432407.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_LL.PCUnSuppress,432407.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_LL.PCUnshelve,432407.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_LL.Alarm_Fault,432407.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_LL.Shelved,432407.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_LL.Suppressed,432407.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_LL.PLCIOFault,432407.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_LL.PLCF,432407.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_LL.TAGR,432407.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_PL.Fault,432440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_PL.Faulted,432440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_PL.AlarmState,432440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_PL.FaultInAlarm,432440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_PL.Alarm_EN,432440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_PL.REST,432440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_PL.ACKN,432440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_PL.MCmd_Enable,432440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_PL.MCmd_Disable,432440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_PL.ALRM,432440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_PL.ANUN,432440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_PL.AKED,432440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_PL.Resetable,432440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_PL.Shelve,432440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_PL.Suppress,432440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_PL.InputAlarm,432440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_PL.GlobalReset,432441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_PL.PCSuppress,432441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_PL.PCUnSuppress,432441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_PL.PCUnshelve,432441.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_PL.Alarm_Fault,432441.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_PL.Shelved,432441.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_PL.Suppressed,432441.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_PL.PLCIOFault,432441.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_PL.PLCF,432441.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_PL.TAGR,432441.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_SH.Fault,432476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_SH.Faulted,432476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_SH.AlarmState,432476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_SH.FaultInAlarm,432476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_SH.Alarm_EN,432476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_SH.REST,432476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_SH.ACKN,432476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_SH.MCmd_Enable,432476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_SH.MCmd_Disable,432476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_SH.ALRM,432476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_SH.ANUN,432476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_SH.AKED,432476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_SH.Resetable,432476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_SH.Shelve,432476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_SH.Suppress,432476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_SH.InputAlarm,432476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_SH.GlobalReset,432477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_SH.PCSuppress,432477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_SH.PCUnSuppress,432477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_SH.PCUnshelve,432477.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_SH.Alarm_Fault,432477.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_SH.Shelved,432477.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_SH.Suppressed,432477.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_SH.PLCIOFault,432477.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_SH.PLCF,432477.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_SH.TAGR,432477.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_TH.Fault,432510.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_TH.Faulted,432510.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_TH.AlarmState,432510.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_TH.FaultInAlarm,432510.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_TH.Alarm_EN,432510.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_TH.REST,432510.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_TH.ACKN,432510.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_TH.MCmd_Enable,432510.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_TH.MCmd_Disable,432510.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_TH.ALRM,432510.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_TH.ANUN,432510.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_TH.AKED,432510.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_TH.Resetable,432510.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_TH.Shelve,432510.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_TH.Suppress,432510.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_TH.InputAlarm,432510.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_TH.GlobalReset,432511.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_TH.PCSuppress,432511.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_TH.PCUnSuppress,432511.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_TH.PCUnshelve,432511.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_TH.Alarm_Fault,432511.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_TH.Shelved,432511.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_TH.Suppressed,432511.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_TH.PLCIOFault,432511.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_TH.PLCF,432511.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_TH.TAGR,432511.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_XA1.Fault,432546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_XA1.Faulted,432546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_XA1.AlarmState,432546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_XA1.FaultInAlarm,432546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA1.Alarm_EN,432546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_XA1.REST,432546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_XA1.ACKN,432546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_XA1.MCmd_Enable,432546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA1.MCmd_Disable,432546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA1.ALRM,432546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_XA1.ANUN,432546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_XA1.AKED,432546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_XA1.Resetable,432546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_XA1.Shelve,432546.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_XA1.Suppress,432546.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_XA1.InputAlarm,432546.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_XA1.GlobalReset,432547.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_XA1.PCSuppress,432547.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_XA1.PCUnSuppress,432547.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_XA1.PCUnshelve,432547.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_XA1.Alarm_Fault,432547.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_XA1.Shelved,432547.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_XA1.Suppressed,432547.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_XA1.PLCIOFault,432547.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_XA1.PLCF,432547.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_XA1.TAGR,432547.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_GEN_0131_1_XA2.Fault,432580.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_GEN_0131_1_XA2.Faulted,432580.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_GEN_0131_1_XA2.AlarmState,432580.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_GEN_0131_1_XA2.FaultInAlarm,432580.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA2.Alarm_EN,432580.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_GEN_0131_1_XA2.REST,432580.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_GEN_0131_1_XA2.ACKN,432580.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_GEN_0131_1_XA2.MCmd_Enable,432580.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA2.MCmd_Disable,432580.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA2.ALRM,432580.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_GEN_0131_1_XA2.ANUN,432580.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_GEN_0131_1_XA2.AKED,432580.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_GEN_0131_1_XA2.Resetable,432580.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_GEN_0131_1_XA2.Shelve,432580.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_GEN_0131_1_XA2.Suppress,432580.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_GEN_0131_1_XA2.InputAlarm,432580.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_GEN_0131_1_XA2.GlobalReset,432581.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_GEN_0131_1_XA2.PCSuppress,432581.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_GEN_0131_1_XA2.PCUnSuppress,432581.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_GEN_0131_1_XA2.PCUnshelve,432581.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_GEN_0131_1_XA2.Alarm_Fault,432581.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_GEN_0131_1_XA2.Shelved,432581.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_GEN_0131_1_XA2.Suppressed,432581.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_GEN_0131_1_XA2.PLCIOFault,432581.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_XA2.PLCF,432581.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_GEN_0131_1_XA2.TAGR,432581.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_FA.Fault,432616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_FA.Faulted,432616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_FA.AlarmState,432616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_FA.FaultInAlarm,432616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FA.Alarm_EN,432616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_FA.REST,432616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_FA.ACKN,432616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_FA.MCmd_Enable,432616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FA.MCmd_Disable,432616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FA.ALRM,432616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_FA.ANUN,432616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_FA.AKED,432616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_FA.Resetable,432616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_FA.Shelve,432616.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_FA.Suppress,432616.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_FA.InputAlarm,432616.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_FA.GlobalReset,432617.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_FA.PCSuppress,432617.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_FA.PCUnSuppress,432617.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_FA.PCUnshelve,432617.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_FA.Alarm_Fault,432617.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_FA.Shelved,432617.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_FA.Suppressed,432617.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_FA.PLCIOFault,432617.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_FA.PLCF,432617.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_FA.TAGR,432617.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_FH.Fault,432650.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_FH.Faulted,432650.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_FH.AlarmState,432650.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_FH.FaultInAlarm,432650.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FH.Alarm_EN,432650.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_FH.REST,432650.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_FH.ACKN,432650.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_FH.MCmd_Enable,432650.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FH.MCmd_Disable,432650.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FH.ALRM,432650.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_FH.ANUN,432650.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_FH.AKED,432650.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_FH.Resetable,432650.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_FH.Shelve,432650.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_FH.Suppress,432650.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_FH.InputAlarm,432650.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_FH.GlobalReset,432651.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_FH.PCSuppress,432651.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_FH.PCUnSuppress,432651.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_FH.PCUnshelve,432651.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_FH.Alarm_Fault,432651.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_FH.Shelved,432651.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_FH.Suppressed,432651.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_FH.PLCIOFault,432651.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_FH.PLCF,432651.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_FH.TAGR,432651.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_PH.Fault,432686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_PH.Faulted,432686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_PH.AlarmState,432686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_PH.FaultInAlarm,432686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_PH.Alarm_EN,432686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_PH.REST,432686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_PH.ACKN,432686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_PH.MCmd_Enable,432686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_PH.MCmd_Disable,432686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_PH.ALRM,432686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_PH.ANUN,432686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_PH.AKED,432686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_PH.Resetable,432686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_PH.Shelve,432686.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_PH.Suppress,432686.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_PH.InputAlarm,432686.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_PH.GlobalReset,432687.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_PH.PCSuppress,432687.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_PH.PCUnSuppress,432687.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_PH.PCUnshelve,432687.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_PH.Alarm_Fault,432687.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_PH.Shelved,432687.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_PH.Suppressed,432687.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_PH.PLCIOFault,432687.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_PH.PLCF,432687.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_PH.TAGR,432687.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_TH1.Fault,432720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_TH1.Faulted,432720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_TH1.AlarmState,432720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_TH1.FaultInAlarm,432720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH1.Alarm_EN,432720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_TH1.REST,432720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_TH1.ACKN,432720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_TH1.MCmd_Enable,432720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH1.MCmd_Disable,432720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH1.ALRM,432720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_TH1.ANUN,432720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_TH1.AKED,432720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_TH1.Resetable,432720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_TH1.Shelve,432720.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_TH1.Suppress,432720.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_TH1.InputAlarm,432720.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_TH1.GlobalReset,432721.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_TH1.PCSuppress,432721.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_TH1.PCUnSuppress,432721.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_TH1.PCUnshelve,432721.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_TH1.Alarm_Fault,432721.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_TH1.Shelved,432721.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_TH1.Suppressed,432721.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_TH1.PLCIOFault,432721.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH1.PLCF,432721.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH1.TAGR,432721.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_TH2.Fault,432756.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_TH2.Faulted,432756.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_TH2.AlarmState,432756.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_TH2.FaultInAlarm,432756.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH2.Alarm_EN,432756.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_TH2.REST,432756.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_TH2.ACKN,432756.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_TH2.MCmd_Enable,432756.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH2.MCmd_Disable,432756.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH2.ALRM,432756.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_TH2.ANUN,432756.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_TH2.AKED,432756.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_TH2.Resetable,432756.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_TH2.Shelve,432756.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_TH2.Suppress,432756.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_TH2.InputAlarm,432756.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_TH2.GlobalReset,432757.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_TH2.PCSuppress,432757.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_TH2.PCUnSuppress,432757.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_TH2.PCUnshelve,432757.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_TH2.Alarm_Fault,432757.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_TH2.Shelved,432757.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_TH2.Suppressed,432757.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_TH2.PLCIOFault,432757.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH2.PLCF,432757.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH2.TAGR,432757.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_TH3.Fault,432790.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_TH3.Faulted,432790.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_TH3.AlarmState,432790.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_TH3.FaultInAlarm,432790.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH3.Alarm_EN,432790.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_TH3.REST,432790.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_TH3.ACKN,432790.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_TH3.MCmd_Enable,432790.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH3.MCmd_Disable,432790.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH3.ALRM,432790.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_TH3.ANUN,432790.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_TH3.AKED,432790.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_TH3.Resetable,432790.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_TH3.Shelve,432790.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_TH3.Suppress,432790.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_TH3.InputAlarm,432790.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_TH3.GlobalReset,432791.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_TH3.PCSuppress,432791.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_TH3.PCUnSuppress,432791.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_TH3.PCUnshelve,432791.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_TH3.Alarm_Fault,432791.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_TH3.Shelved,432791.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_TH3.Suppressed,432791.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_TH3.PLCIOFault,432791.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH3.PLCF,432791.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TH3.TAGR,432791.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_TL1.Fault,432826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_TL1.Faulted,432826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_TL1.AlarmState,432826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_TL1.FaultInAlarm,432826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL1.Alarm_EN,432826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_TL1.REST,432826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_TL1.ACKN,432826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_TL1.MCmd_Enable,432826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL1.MCmd_Disable,432826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL1.ALRM,432826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_TL1.ANUN,432826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_TL1.AKED,432826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_TL1.Resetable,432826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_TL1.Shelve,432826.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_TL1.Suppress,432826.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_TL1.InputAlarm,432826.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_TL1.GlobalReset,432827.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_TL1.PCSuppress,432827.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_TL1.PCUnSuppress,432827.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_TL1.PCUnshelve,432827.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_TL1.Alarm_Fault,432827.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_TL1.Shelved,432827.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_TL1.Suppressed,432827.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_TL1.PLCIOFault,432827.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TL1.PLCF,432827.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TL1.TAGR,432827.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_TL2.Fault,432860.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_TL2.Faulted,432860.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_TL2.AlarmState,432860.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_TL2.FaultInAlarm,432860.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL2.Alarm_EN,432860.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_TL2.REST,432860.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_TL2.ACKN,432860.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_TL2.MCmd_Enable,432860.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL2.MCmd_Disable,432860.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL2.ALRM,432860.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_TL2.ANUN,432860.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_TL2.AKED,432860.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_TL2.Resetable,432860.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_TL2.Shelve,432860.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_TL2.Suppress,432860.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_TL2.InputAlarm,432860.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_TL2.GlobalReset,432861.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_TL2.PCSuppress,432861.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_TL2.PCUnSuppress,432861.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_TL2.PCUnshelve,432861.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_TL2.Alarm_Fault,432861.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_TL2.Shelved,432861.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_TL2.Suppressed,432861.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_TL2.PLCIOFault,432861.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TL2.PLCF,432861.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_TL2.TAGR,432861.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA1.Fault,432896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA1.Faulted,432896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA1.AlarmState,432896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA1.FaultInAlarm,432896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA1.Alarm_EN,432896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA1.REST,432896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA1.ACKN,432896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA1.MCmd_Enable,432896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA1.MCmd_Disable,432896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA1.ALRM,432896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA1.ANUN,432896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA1.AKED,432896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA1.Resetable,432896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA1.Shelve,432896.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA1.Suppress,432896.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA1.InputAlarm,432896.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA1.GlobalReset,432897.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA1.PCSuppress,432897.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA1.PCUnSuppress,432897.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA1.PCUnshelve,432897.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA1.Alarm_Fault,432897.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA1.Shelved,432897.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA1.Suppressed,432897.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA1.PLCIOFault,432897.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA1.PLCF,432897.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA1.TAGR,432897.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA2.Fault,432930.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA2.Faulted,432930.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA2.AlarmState,432930.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA2.FaultInAlarm,432930.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA2.Alarm_EN,432930.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA2.REST,432930.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA2.ACKN,432930.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA2.MCmd_Enable,432930.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA2.MCmd_Disable,432930.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA2.ALRM,432930.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA2.ANUN,432930.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA2.AKED,432930.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA2.Resetable,432930.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA2.Shelve,432930.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA2.Suppress,432930.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA2.InputAlarm,432930.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA2.GlobalReset,432931.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA2.PCSuppress,432931.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA2.PCUnSuppress,432931.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA2.PCUnshelve,432931.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA2.Alarm_Fault,432931.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA2.Shelved,432931.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA2.Suppressed,432931.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA2.PLCIOFault,432931.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA2.PLCF,432931.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA2.TAGR,432931.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA3.Fault,432966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA3.Faulted,432966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA3.AlarmState,432966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA3.FaultInAlarm,432966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA3.Alarm_EN,432966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA3.REST,432966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA3.ACKN,432966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA3.MCmd_Enable,432966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA3.MCmd_Disable,432966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA3.ALRM,432966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA3.ANUN,432966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA3.AKED,432966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA3.Resetable,432966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA3.Shelve,432966.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA3.Suppress,432966.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA3.InputAlarm,432966.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA3.GlobalReset,432967.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA3.PCSuppress,432967.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA3.PCUnSuppress,432967.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA3.PCUnshelve,432967.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA3.Alarm_Fault,432967.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA3.Shelved,432967.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA3.Suppressed,432967.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA3.PLCIOFault,432967.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA3.PLCF,432967.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA3.TAGR,432967.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA4.Fault,433000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA4.Faulted,433000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA4.AlarmState,433000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA4.FaultInAlarm,433000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA4.Alarm_EN,433000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA4.REST,433000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA4.ACKN,433000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA4.MCmd_Enable,433000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA4.MCmd_Disable,433000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA4.ALRM,433000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA4.ANUN,433000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA4.AKED,433000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA4.Resetable,433000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA4.Shelve,433000.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA4.Suppress,433000.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA4.InputAlarm,433000.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA4.GlobalReset,433001.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA4.PCSuppress,433001.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA4.PCUnSuppress,433001.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA4.PCUnshelve,433001.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA4.Alarm_Fault,433001.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA4.Shelved,433001.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA4.Suppressed,433001.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA4.PLCIOFault,433001.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA4.PLCF,433001.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA4.TAGR,433001.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA5.Fault,433036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA5.Faulted,433036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA5.AlarmState,433036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA5.FaultInAlarm,433036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA5.Alarm_EN,433036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA5.REST,433036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA5.ACKN,433036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA5.MCmd_Enable,433036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA5.MCmd_Disable,433036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA5.ALRM,433036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA5.ANUN,433036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA5.AKED,433036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA5.Resetable,433036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA5.Shelve,433036.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA5.Suppress,433036.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA5.InputAlarm,433036.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA5.GlobalReset,433037.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA5.PCSuppress,433037.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA5.PCUnSuppress,433037.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA5.PCUnshelve,433037.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA5.Alarm_Fault,433037.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA5.Shelved,433037.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA5.Suppressed,433037.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA5.PLCIOFault,433037.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA5.PLCF,433037.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA5.TAGR,433037.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA6.Fault,433070.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA6.Faulted,433070.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA6.AlarmState,433070.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA6.FaultInAlarm,433070.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA6.Alarm_EN,433070.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA6.REST,433070.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA6.ACKN,433070.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA6.MCmd_Enable,433070.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA6.MCmd_Disable,433070.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA6.ALRM,433070.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA6.ANUN,433070.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA6.AKED,433070.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA6.Resetable,433070.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA6.Shelve,433070.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA6.Suppress,433070.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA6.InputAlarm,433070.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA6.GlobalReset,433071.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA6.PCSuppress,433071.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA6.PCUnSuppress,433071.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA6.PCUnshelve,433071.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA6.Alarm_Fault,433071.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA6.Shelved,433071.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA6.Suppressed,433071.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA6.PLCIOFault,433071.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA6.PLCF,433071.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA6.TAGR,433071.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA7.Fault,433106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA7.Faulted,433106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA7.AlarmState,433106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA7.FaultInAlarm,433106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA7.Alarm_EN,433106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA7.REST,433106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA7.ACKN,433106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA7.MCmd_Enable,433106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA7.MCmd_Disable,433106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA7.ALRM,433106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA7.ANUN,433106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA7.AKED,433106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA7.Resetable,433106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA7.Shelve,433106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA7.Suppress,433106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA7.InputAlarm,433106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA7.GlobalReset,433107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA7.PCSuppress,433107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA7.PCUnSuppress,433107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA7.PCUnshelve,433107.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA7.Alarm_Fault,433107.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA7.Shelved,433107.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA7.Suppressed,433107.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA7.PLCIOFault,433107.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA7.PLCF,433107.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA7.TAGR,433107.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA8.Fault,433140.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA8.Faulted,433140.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA8.AlarmState,433140.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA8.FaultInAlarm,433140.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA8.Alarm_EN,433140.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA8.REST,433140.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA8.ACKN,433140.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA8.MCmd_Enable,433140.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA8.MCmd_Disable,433140.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA8.ALRM,433140.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA8.ANUN,433140.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA8.AKED,433140.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA8.Resetable,433140.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA8.Shelve,433140.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA8.Suppress,433140.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA8.InputAlarm,433140.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA8.GlobalReset,433141.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA8.PCSuppress,433141.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA8.PCUnSuppress,433141.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA8.PCUnshelve,433141.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA8.Alarm_Fault,433141.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA8.Shelved,433141.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA8.Suppressed,433141.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA8.PLCIOFault,433141.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA8.PLCF,433141.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA8.TAGR,433141.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA9.Fault,433176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA9.Faulted,433176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA9.AlarmState,433176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA9.FaultInAlarm,433176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA9.Alarm_EN,433176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA9.REST,433176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA9.ACKN,433176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA9.MCmd_Enable,433176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA9.MCmd_Disable,433176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA9.ALRM,433176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA9.ANUN,433176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA9.AKED,433176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA9.Resetable,433176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA9.Shelve,433176.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA9.Suppress,433176.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA9.InputAlarm,433176.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA9.GlobalReset,433177.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA9.PCSuppress,433177.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA9.PCUnSuppress,433177.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA9.PCUnshelve,433177.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA9.Alarm_Fault,433177.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA9.Shelved,433177.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA9.Suppressed,433177.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA9.PLCIOFault,433177.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA9.PLCF,433177.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA9.TAGR,433177.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA10.Fault,433210.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA10.Faulted,433210.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA10.AlarmState,433210.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA10.FaultInAlarm,433210.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA10.Alarm_EN,433210.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA10.REST,433210.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA10.ACKN,433210.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA10.MCmd_Enable,433210.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA10.MCmd_Disable,433210.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA10.ALRM,433210.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA10.ANUN,433210.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA10.AKED,433210.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA10.Resetable,433210.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA10.Shelve,433210.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA10.Suppress,433210.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA10.InputAlarm,433210.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA10.GlobalReset,433211.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA10.PCSuppress,433211.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA10.PCUnSuppress,433211.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA10.PCUnshelve,433211.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA10.Alarm_Fault,433211.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA10.Shelved,433211.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA10.Suppressed,433211.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA10.PLCIOFault,433211.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA10.PLCF,433211.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA10.TAGR,433211.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA11.Fault,433246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA11.Faulted,433246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA11.AlarmState,433246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA11.FaultInAlarm,433246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA11.Alarm_EN,433246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA11.REST,433246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA11.ACKN,433246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA11.MCmd_Enable,433246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA11.MCmd_Disable,433246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA11.ALRM,433246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA11.ANUN,433246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA11.AKED,433246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA11.Resetable,433246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA11.Shelve,433246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA11.Suppress,433246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA11.InputAlarm,433246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA11.GlobalReset,433247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA11.PCSuppress,433247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA11.PCUnSuppress,433247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA11.PCUnshelve,433247.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA11.Alarm_Fault,433247.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA11.Shelved,433247.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA11.Suppressed,433247.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA11.PLCIOFault,433247.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA11.PLCF,433247.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA11.TAGR,433247.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_HCP_001_1_XA12.Fault,433280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_HCP_001_1_XA12.Faulted,433280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_HCP_001_1_XA12.AlarmState,433280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_HCP_001_1_XA12.FaultInAlarm,433280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA12.Alarm_EN,433280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_HCP_001_1_XA12.REST,433280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_HCP_001_1_XA12.ACKN,433280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_HCP_001_1_XA12.MCmd_Enable,433280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA12.MCmd_Disable,433280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA12.ALRM,433280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_HCP_001_1_XA12.ANUN,433280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_HCP_001_1_XA12.AKED,433280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_HCP_001_1_XA12.Resetable,433280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_HCP_001_1_XA12.Shelve,433280.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_HCP_001_1_XA12.Suppress,433280.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_HCP_001_1_XA12.InputAlarm,433280.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_HCP_001_1_XA12.GlobalReset,433281.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_HCP_001_1_XA12.PCSuppress,433281.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_HCP_001_1_XA12.PCUnSuppress,433281.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_HCP_001_1_XA12.PCUnshelve,433281.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_HCP_001_1_XA12.Alarm_Fault,433281.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_HCP_001_1_XA12.Shelved,433281.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_HCP_001_1_XA12.Suppressed,433281.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_HCP_001_1_XA12.PLCIOFault,433281.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA12.PLCF,433281.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_HCP_001_1_XA12.TAGR,433281.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_LSH_0113_1_LH.Fault,433316.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_LSH_0113_1_LH.Faulted,433316.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_LSH_0113_1_LH.AlarmState,433316.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_LSH_0113_1_LH.FaultInAlarm,433316.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_1_LH.Alarm_EN,433316.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_LSH_0113_1_LH.REST,433316.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_LSH_0113_1_LH.ACKN,433316.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_LSH_0113_1_LH.MCmd_Enable,433316.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_1_LH.MCmd_Disable,433316.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_1_LH.ALRM,433316.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_LSH_0113_1_LH.ANUN,433316.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_LSH_0113_1_LH.AKED,433316.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_LSH_0113_1_LH.Resetable,433316.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_LSH_0113_1_LH.Shelve,433316.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_LSH_0113_1_LH.Suppress,433316.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_LSH_0113_1_LH.InputAlarm,433316.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_LSH_0113_1_LH.GlobalReset,433317.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_LSH_0113_1_LH.PCSuppress,433317.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_LSH_0113_1_LH.PCUnSuppress,433317.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_LSH_0113_1_LH.PCUnshelve,433317.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_LSH_0113_1_LH.Alarm_Fault,433317.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_LSH_0113_1_LH.Shelved,433317.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_LSH_0113_1_LH.Suppressed,433317.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_LSH_0113_1_LH.PLCIOFault,433317.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_LSH_0113_1_LH.PLCF,433317.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_LSH_0113_1_LH.TAGR,433317.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_LSH_0113_2_LH.Fault,433350.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_LSH_0113_2_LH.Faulted,433350.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_LSH_0113_2_LH.AlarmState,433350.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_LSH_0113_2_LH.FaultInAlarm,433350.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_2_LH.Alarm_EN,433350.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_LSH_0113_2_LH.REST,433350.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_LSH_0113_2_LH.ACKN,433350.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_LSH_0113_2_LH.MCmd_Enable,433350.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_2_LH.MCmd_Disable,433350.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_2_LH.ALRM,433350.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_LSH_0113_2_LH.ANUN,433350.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_LSH_0113_2_LH.AKED,433350.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_LSH_0113_2_LH.Resetable,433350.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_LSH_0113_2_LH.Shelve,433350.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_LSH_0113_2_LH.Suppress,433350.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_LSH_0113_2_LH.InputAlarm,433350.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_LSH_0113_2_LH.GlobalReset,433351.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_LSH_0113_2_LH.PCSuppress,433351.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_LSH_0113_2_LH.PCUnSuppress,433351.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_LSH_0113_2_LH.PCUnshelve,433351.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_LSH_0113_2_LH.Alarm_Fault,433351.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_LSH_0113_2_LH.Shelved,433351.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_LSH_0113_2_LH.Suppressed,433351.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_LSH_0113_2_LH.PLCIOFault,433351.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_LSH_0113_2_LH.PLCF,433351.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_LSH_0113_2_LH.TAGR,433351.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_NET_001_1_JA.Fault,433386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_NET_001_1_JA.Faulted,433386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_NET_001_1_JA.AlarmState,433386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_NET_001_1_JA.FaultInAlarm,433386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_JA.Alarm_EN,433386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_NET_001_1_JA.REST,433386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_NET_001_1_JA.ACKN,433386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_NET_001_1_JA.MCmd_Enable,433386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_JA.MCmd_Disable,433386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_JA.ALRM,433386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_NET_001_1_JA.ANUN,433386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_NET_001_1_JA.AKED,433386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_NET_001_1_JA.Resetable,433386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_NET_001_1_JA.Shelve,433386.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_NET_001_1_JA.Suppress,433386.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_NET_001_1_JA.InputAlarm,433386.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_NET_001_1_JA.GlobalReset,433387.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_NET_001_1_JA.PCSuppress,433387.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_NET_001_1_JA.PCUnSuppress,433387.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_NET_001_1_JA.PCUnshelve,433387.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_NET_001_1_JA.Alarm_Fault,433387.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_NET_001_1_JA.Shelved,433387.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_NET_001_1_JA.Suppressed,433387.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_NET_001_1_JA.PLCIOFault,433387.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_NET_001_1_JA.PLCF,433387.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_NET_001_1_JA.TAGR,433387.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_NET_001_1_ZS.Fault,433420.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_NET_001_1_ZS.Faulted,433420.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_NET_001_1_ZS.AlarmState,433420.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_NET_001_1_ZS.FaultInAlarm,433420.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_ZS.Alarm_EN,433420.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_NET_001_1_ZS.REST,433420.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_NET_001_1_ZS.ACKN,433420.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_NET_001_1_ZS.MCmd_Enable,433420.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_ZS.MCmd_Disable,433420.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_ZS.ALRM,433420.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_NET_001_1_ZS.ANUN,433420.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_NET_001_1_ZS.AKED,433420.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_NET_001_1_ZS.Resetable,433420.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_NET_001_1_ZS.Shelve,433420.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_NET_001_1_ZS.Suppress,433420.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_NET_001_1_ZS.InputAlarm,433420.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_NET_001_1_ZS.GlobalReset,433421.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_NET_001_1_ZS.PCSuppress,433421.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_NET_001_1_ZS.PCUnSuppress,433421.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_NET_001_1_ZS.PCUnshelve,433421.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_NET_001_1_ZS.Alarm_Fault,433421.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_NET_001_1_ZS.Shelved,433421.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_NET_001_1_ZS.Suppressed,433421.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_NET_001_1_ZS.PLCIOFault,433421.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_NET_001_1_ZS.PLCF,433421.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_NET_001_1_ZS.TAGR,433421.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PFC_0112_INHIBIT.Fault,433456.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PFC_0112_INHIBIT.Faulted,433456.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PFC_0112_INHIBIT.AlarmState,433456.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PFC_0112_INHIBIT.FaultInAlarm,433456.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PFC_0112_INHIBIT.Alarm_EN,433456.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PFC_0112_INHIBIT.REST,433456.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PFC_0112_INHIBIT.ACKN,433456.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PFC_0112_INHIBIT.MCmd_Enable,433456.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PFC_0112_INHIBIT.MCmd_Disable,433456.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PFC_0112_INHIBIT.ALRM,433456.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PFC_0112_INHIBIT.ANUN,433456.10,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PFC_0112_INHIBIT.AKED,433456.11,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PFC_0112_INHIBIT.Resetable,433456.12,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PFC_0112_INHIBIT.Shelve,433456.13,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PFC_0112_INHIBIT.Suppress,433456.14,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PFC_0112_INHIBIT.InputAlarm,433456.15,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PFC_0112_INHIBIT.GlobalReset,433457.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PFC_0112_INHIBIT.PCSuppress,433457.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PFC_0112_INHIBIT.PCUnSuppress,433457.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PFC_0112_INHIBIT.PCUnshelve,433457.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PFC_0112_INHIBIT.Alarm_Fault,433457.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PFC_0112_INHIBIT.Shelved,433457.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PFC_0112_INHIBIT.Suppressed,433457.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PFC_0112_INHIBIT.PLCIOFault,433457.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PFC_0112_INHIBIT.PLCF,433457.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PFC_0112_INHIBIT.TAGR,433457.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PIT_0102_1_PL.Fault,433490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PIT_0102_1_PL.Faulted,433490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PIT_0102_1_PL.AlarmState,433490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PIT_0102_1_PL.FaultInAlarm,433490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PL.Alarm_EN,433490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PIT_0102_1_PL.REST,433490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PIT_0102_1_PL.ACKN,433490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PIT_0102_1_PL.MCmd_Enable,433490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PL.MCmd_Disable,433490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PL.ALRM,433490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PIT_0102_1_PL.ANUN,433490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0102_1_PL.AKED,433490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0102_1_PL.Resetable,433490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0102_1_PL.Shelve,433490.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PIT_0102_1_PL.Suppress,433490.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PIT_0102_1_PL.InputAlarm,433490.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PIT_0102_1_PL.GlobalReset,433491.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0102_1_PL.PCSuppress,433491.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0102_1_PL.PCUnSuppress,433491.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0102_1_PL.PCUnshelve,433491.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0102_1_PL.Alarm_Fault,433491.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PIT_0102_1_PL.Shelved,433491.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PIT_0102_1_PL.Suppressed,433491.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PIT_0102_1_PL.PLCIOFault,433491.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_1_PL.PLCF,433491.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_1_PL.TAGR,433491.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PIT_0102_2_PL.Fault,433526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PIT_0102_2_PL.Faulted,433526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PIT_0102_2_PL.AlarmState,433526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PIT_0102_2_PL.FaultInAlarm,433526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PL.Alarm_EN,433526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PIT_0102_2_PL.REST,433526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PIT_0102_2_PL.ACKN,433526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PIT_0102_2_PL.MCmd_Enable,433526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PL.MCmd_Disable,433526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PL.ALRM,433526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PIT_0102_2_PL.ANUN,433526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PIT_0102_2_PL.AKED,433526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PIT_0102_2_PL.Resetable,433526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PIT_0102_2_PL.Shelve,433526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PIT_0102_2_PL.Suppress,433526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PIT_0102_2_PL.InputAlarm,433526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PIT_0102_2_PL.GlobalReset,433527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PIT_0102_2_PL.PCSuppress,433527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PIT_0102_2_PL.PCUnSuppress,433527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PIT_0102_2_PL.PCUnshelve,433527.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PIT_0102_2_PL.Alarm_Fault,433527.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PIT_0102_2_PL.Shelved,433527.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PIT_0102_2_PL.Suppressed,433527.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PIT_0102_2_PL.PLCIOFault,433527.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_2_PL.PLCF,433527.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PIT_0102_2_PL.TAGR,433527.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PLC_001_1_JA.Fault,433560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PLC_001_1_JA.Faulted,433560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PLC_001_1_JA.AlarmState,433560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PLC_001_1_JA.FaultInAlarm,433560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_JA.Alarm_EN,433560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PLC_001_1_JA.REST,433560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PLC_001_1_JA.ACKN,433560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PLC_001_1_JA.MCmd_Enable,433560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_JA.MCmd_Disable,433560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_JA.ALRM,433560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PLC_001_1_JA.ANUN,433560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PLC_001_1_JA.AKED,433560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PLC_001_1_JA.Resetable,433560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PLC_001_1_JA.Shelve,433560.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PLC_001_1_JA.Suppress,433560.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PLC_001_1_JA.InputAlarm,433560.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PLC_001_1_JA.GlobalReset,433561.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PLC_001_1_JA.PCSuppress,433561.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PLC_001_1_JA.PCUnSuppress,433561.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PLC_001_1_JA.PCUnshelve,433561.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PLC_001_1_JA.Alarm_Fault,433561.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PLC_001_1_JA.Shelved,433561.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PLC_001_1_JA.Suppressed,433561.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PLC_001_1_JA.PLCIOFault,433561.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PLC_001_1_JA.PLCF,433561.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PLC_001_1_JA.TAGR,433561.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PLC_001_1_ZS.Fault,433596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PLC_001_1_ZS.Faulted,433596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PLC_001_1_ZS.AlarmState,433596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PLC_001_1_ZS.FaultInAlarm,433596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_ZS.Alarm_EN,433596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PLC_001_1_ZS.REST,433596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PLC_001_1_ZS.ACKN,433596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PLC_001_1_ZS.MCmd_Enable,433596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_ZS.MCmd_Disable,433596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_ZS.ALRM,433596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PLC_001_1_ZS.ANUN,433596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PLC_001_1_ZS.AKED,433596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PLC_001_1_ZS.Resetable,433596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PLC_001_1_ZS.Shelve,433596.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PLC_001_1_ZS.Suppress,433596.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PLC_001_1_ZS.InputAlarm,433596.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PLC_001_1_ZS.GlobalReset,433597.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PLC_001_1_ZS.PCSuppress,433597.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PLC_001_1_ZS.PCUnSuppress,433597.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PLC_001_1_ZS.PCUnshelve,433597.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PLC_001_1_ZS.Alarm_Fault,433597.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PLC_001_1_ZS.Shelved,433597.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PLC_001_1_ZS.Suppressed,433597.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PLC_001_1_ZS.PLCIOFault,433597.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PLC_001_1_ZS.PLCF,433597.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PLC_001_1_ZS.TAGR,433597.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_1_PL.Fault,433630.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_1_PL.Faulted,433630.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_1_PL.AlarmState,433630.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_1_PL.FaultInAlarm,433630.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_1_PL.Alarm_EN,433630.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_1_PL.REST,433630.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_1_PL.ACKN,433630.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_1_PL.MCmd_Enable,433630.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_1_PL.MCmd_Disable,433630.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_1_PL.ALRM,433630.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_1_PL.ANUN,433630.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_1_PL.AKED,433630.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_1_PL.Resetable,433630.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_1_PL.Shelve,433630.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_1_PL.Suppress,433630.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_1_PL.InputAlarm,433630.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_1_PL.GlobalReset,433631.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_1_PL.PCSuppress,433631.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_1_PL.PCUnSuppress,433631.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_1_PL.PCUnshelve,433631.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_1_PL.Alarm_Fault,433631.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_1_PL.Shelved,433631.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_1_PL.Suppressed,433631.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_1_PL.PLCIOFault,433631.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_1_PL.PLCF,433631.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_1_PL.TAGR,433631.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_2_PL.Fault,433666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_2_PL.Faulted,433666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_2_PL.AlarmState,433666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_2_PL.FaultInAlarm,433666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_2_PL.Alarm_EN,433666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_2_PL.REST,433666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_2_PL.ACKN,433666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_2_PL.MCmd_Enable,433666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_2_PL.MCmd_Disable,433666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_2_PL.ALRM,433666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_2_PL.ANUN,433666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_2_PL.AKED,433666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_2_PL.Resetable,433666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_2_PL.Shelve,433666.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_2_PL.Suppress,433666.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_2_PL.InputAlarm,433666.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_2_PL.GlobalReset,433667.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_2_PL.PCSuppress,433667.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_2_PL.PCUnSuppress,433667.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_2_PL.PCUnshelve,433667.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_2_PL.Alarm_Fault,433667.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_2_PL.Shelved,433667.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_2_PL.Suppressed,433667.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_2_PL.PLCIOFault,433667.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_2_PL.PLCF,433667.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_2_PL.TAGR,433667.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_3_PL.Fault,433700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_3_PL.Faulted,433700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_3_PL.AlarmState,433700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_3_PL.FaultInAlarm,433700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_3_PL.Alarm_EN,433700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_3_PL.REST,433700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_3_PL.ACKN,433700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_3_PL.MCmd_Enable,433700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_3_PL.MCmd_Disable,433700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_3_PL.ALRM,433700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_3_PL.ANUN,433700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_3_PL.AKED,433700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_3_PL.Resetable,433700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_3_PL.Shelve,433700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_3_PL.Suppress,433700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_3_PL.InputAlarm,433700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_3_PL.GlobalReset,433701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_3_PL.PCSuppress,433701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_3_PL.PCUnSuppress,433701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_3_PL.PCUnshelve,433701.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_3_PL.Alarm_Fault,433701.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_3_PL.Shelved,433701.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_3_PL.Suppressed,433701.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_3_PL.PLCIOFault,433701.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_3_PL.PLCF,433701.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_3_PL.TAGR,433701.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_4_PL.Fault,433736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_4_PL.Faulted,433736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_4_PL.AlarmState,433736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_4_PL.FaultInAlarm,433736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_4_PL.Alarm_EN,433736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_4_PL.REST,433736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_4_PL.ACKN,433736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_4_PL.MCmd_Enable,433736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_4_PL.MCmd_Disable,433736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_4_PL.ALRM,433736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_4_PL.ANUN,433736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_4_PL.AKED,433736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_4_PL.Resetable,433736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_4_PL.Shelve,433736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_4_PL.Suppress,433736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_4_PL.InputAlarm,433736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_4_PL.GlobalReset,433737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_4_PL.PCSuppress,433737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_4_PL.PCUnSuppress,433737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_4_PL.PCUnshelve,433737.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_4_PL.Alarm_Fault,433737.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_4_PL.Shelved,433737.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_4_PL.Suppressed,433737.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_4_PL.PLCIOFault,433737.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_4_PL.PLCF,433737.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_4_PL.TAGR,433737.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_5_PL.Fault,433770.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_5_PL.Faulted,433770.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_5_PL.AlarmState,433770.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_5_PL.FaultInAlarm,433770.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_5_PL.Alarm_EN,433770.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_5_PL.REST,433770.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_5_PL.ACKN,433770.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_5_PL.MCmd_Enable,433770.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_5_PL.MCmd_Disable,433770.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_5_PL.ALRM,433770.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_5_PL.ANUN,433770.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_5_PL.AKED,433770.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_5_PL.Resetable,433770.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_5_PL.Shelve,433770.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_5_PL.Suppress,433770.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_5_PL.InputAlarm,433770.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_5_PL.GlobalReset,433771.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_5_PL.PCSuppress,433771.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_5_PL.PCUnSuppress,433771.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_5_PL.PCUnshelve,433771.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_5_PL.Alarm_Fault,433771.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_5_PL.Shelved,433771.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_5_PL.Suppressed,433771.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_5_PL.PLCIOFault,433771.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_5_PL.PLCF,433771.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_5_PL.TAGR,433771.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_6_PL.Fault,433806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_6_PL.Faulted,433806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_6_PL.AlarmState,433806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_6_PL.FaultInAlarm,433806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_6_PL.Alarm_EN,433806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_6_PL.REST,433806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_6_PL.ACKN,433806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_6_PL.MCmd_Enable,433806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_6_PL.MCmd_Disable,433806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_6_PL.ALRM,433806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_6_PL.ANUN,433806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_6_PL.AKED,433806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_6_PL.Resetable,433806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_6_PL.Shelve,433806.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_6_PL.Suppress,433806.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_6_PL.InputAlarm,433806.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_6_PL.GlobalReset,433807.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_6_PL.PCSuppress,433807.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_6_PL.PCUnSuppress,433807.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_6_PL.PCUnshelve,433807.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_6_PL.Alarm_Fault,433807.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_6_PL.Shelved,433807.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_6_PL.Suppressed,433807.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_6_PL.PLCIOFault,433807.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_6_PL.PLCF,433807.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_6_PL.TAGR,433807.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_7_PL.Fault,433840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_7_PL.Faulted,433840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_7_PL.AlarmState,433840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_7_PL.FaultInAlarm,433840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_7_PL.Alarm_EN,433840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_7_PL.REST,433840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_7_PL.ACKN,433840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_7_PL.MCmd_Enable,433840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_7_PL.MCmd_Disable,433840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_7_PL.ALRM,433840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_7_PL.ANUN,433840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_7_PL.AKED,433840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_7_PL.Resetable,433840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_7_PL.Shelve,433840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_7_PL.Suppress,433840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_7_PL.InputAlarm,433840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_7_PL.GlobalReset,433841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_7_PL.PCSuppress,433841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_7_PL.PCUnSuppress,433841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_7_PL.PCUnshelve,433841.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_7_PL.Alarm_Fault,433841.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_7_PL.Shelved,433841.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_7_PL.Suppressed,433841.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_7_PL.PLCIOFault,433841.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_7_PL.PLCF,433841.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_7_PL.TAGR,433841.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_8_PL.Fault,433876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_8_PL.Faulted,433876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_8_PL.AlarmState,433876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_8_PL.FaultInAlarm,433876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_8_PL.Alarm_EN,433876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_8_PL.REST,433876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_8_PL.ACKN,433876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_8_PL.MCmd_Enable,433876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_8_PL.MCmd_Disable,433876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_8_PL.ALRM,433876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_8_PL.ANUN,433876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_8_PL.AKED,433876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_8_PL.Resetable,433876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_8_PL.Shelve,433876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_8_PL.Suppress,433876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_8_PL.InputAlarm,433876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_8_PL.GlobalReset,433877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_8_PL.PCSuppress,433877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_8_PL.PCUnSuppress,433877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_8_PL.PCUnshelve,433877.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_8_PL.Alarm_Fault,433877.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_8_PL.Shelved,433877.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_8_PL.Suppressed,433877.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_8_PL.PLCIOFault,433877.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_8_PL.PLCF,433877.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_8_PL.TAGR,433877.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_PS_0103_9_PL.Fault,433910.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_PS_0103_9_PL.Faulted,433910.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_PS_0103_9_PL.AlarmState,433910.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_PS_0103_9_PL.FaultInAlarm,433910.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_9_PL.Alarm_EN,433910.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_PS_0103_9_PL.REST,433910.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_PS_0103_9_PL.ACKN,433910.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_PS_0103_9_PL.MCmd_Enable,433910.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_9_PL.MCmd_Disable,433910.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_9_PL.ALRM,433910.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_PS_0103_9_PL.ANUN,433910.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_PS_0103_9_PL.AKED,433910.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_PS_0103_9_PL.Resetable,433910.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_PS_0103_9_PL.Shelve,433910.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_PS_0103_9_PL.Suppress,433910.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_PS_0103_9_PL.InputAlarm,433910.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_PS_0103_9_PL.GlobalReset,433911.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_PS_0103_9_PL.PCSuppress,433911.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_PS_0103_9_PL.PCUnSuppress,433911.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_PS_0103_9_PL.PCUnshelve,433911.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_PS_0103_9_PL.Alarm_Fault,433911.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_PS_0103_9_PL.Shelved,433911.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_PS_0103_9_PL.Suppressed,433911.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_PS_0103_9_PL.PLCIOFault,433911.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_9_PL.PLCF,433911.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_PS_0103_9_PL.TAGR,433911.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_REC_0131_1_XA.Fault,433946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_REC_0131_1_XA.Faulted,433946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_REC_0131_1_XA.AlarmState,433946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_REC_0131_1_XA.FaultInAlarm,433946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_1_XA.Alarm_EN,433946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_REC_0131_1_XA.REST,433946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_REC_0131_1_XA.ACKN,433946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_REC_0131_1_XA.MCmd_Enable,433946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_1_XA.MCmd_Disable,433946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_1_XA.ALRM,433946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_REC_0131_1_XA.ANUN,433946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_REC_0131_1_XA.AKED,433946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_REC_0131_1_XA.Resetable,433946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_REC_0131_1_XA.Shelve,433946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_REC_0131_1_XA.Suppress,433946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_REC_0131_1_XA.InputAlarm,433946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_REC_0131_1_XA.GlobalReset,433947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_REC_0131_1_XA.PCSuppress,433947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_REC_0131_1_XA.PCUnSuppress,433947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_REC_0131_1_XA.PCUnshelve,433947.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_REC_0131_1_XA.Alarm_Fault,433947.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_REC_0131_1_XA.Shelved,433947.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_REC_0131_1_XA.Suppressed,433947.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_REC_0131_1_XA.PLCIOFault,433947.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_1_XA.PLCF,433947.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_1_XA.TAGR,433947.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_REC_0131_2_XA.Fault,433980.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_REC_0131_2_XA.Faulted,433980.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_REC_0131_2_XA.AlarmState,433980.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_REC_0131_2_XA.FaultInAlarm,433980.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_2_XA.Alarm_EN,433980.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_REC_0131_2_XA.REST,433980.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_REC_0131_2_XA.ACKN,433980.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_REC_0131_2_XA.MCmd_Enable,433980.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_2_XA.MCmd_Disable,433980.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_2_XA.ALRM,433980.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_REC_0131_2_XA.ANUN,433980.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_REC_0131_2_XA.AKED,433980.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_REC_0131_2_XA.Resetable,433980.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_REC_0131_2_XA.Shelve,433980.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_REC_0131_2_XA.Suppress,433980.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_REC_0131_2_XA.InputAlarm,433980.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_REC_0131_2_XA.GlobalReset,433981.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_REC_0131_2_XA.PCSuppress,433981.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_REC_0131_2_XA.PCUnSuppress,433981.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_REC_0131_2_XA.PCUnshelve,433981.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_REC_0131_2_XA.Alarm_Fault,433981.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_REC_0131_2_XA.Shelved,433981.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_REC_0131_2_XA.Suppressed,433981.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_REC_0131_2_XA.PLCIOFault,433981.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_2_XA.PLCF,433981.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_2_XA.TAGR,433981.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_REC_0131_3_XA.Fault,434016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_REC_0131_3_XA.Faulted,434016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_REC_0131_3_XA.AlarmState,434016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_REC_0131_3_XA.FaultInAlarm,434016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_3_XA.Alarm_EN,434016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_REC_0131_3_XA.REST,434016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_REC_0131_3_XA.ACKN,434016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_REC_0131_3_XA.MCmd_Enable,434016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_3_XA.MCmd_Disable,434016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_3_XA.ALRM,434016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_REC_0131_3_XA.ANUN,434016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_REC_0131_3_XA.AKED,434016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_REC_0131_3_XA.Resetable,434016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_REC_0131_3_XA.Shelve,434016.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_REC_0131_3_XA.Suppress,434016.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_REC_0131_3_XA.InputAlarm,434016.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_REC_0131_3_XA.GlobalReset,434017.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_REC_0131_3_XA.PCSuppress,434017.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_REC_0131_3_XA.PCUnSuppress,434017.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_REC_0131_3_XA.PCUnshelve,434017.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_REC_0131_3_XA.Alarm_Fault,434017.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_REC_0131_3_XA.Shelved,434017.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_REC_0131_3_XA.Suppressed,434017.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_REC_0131_3_XA.PLCIOFault,434017.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_3_XA.PLCF,434017.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_3_XA.TAGR,434017.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_REC_0131_4_XA.Fault,434050.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_REC_0131_4_XA.Faulted,434050.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_REC_0131_4_XA.AlarmState,434050.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_REC_0131_4_XA.FaultInAlarm,434050.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_4_XA.Alarm_EN,434050.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_REC_0131_4_XA.REST,434050.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_REC_0131_4_XA.ACKN,434050.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_REC_0131_4_XA.MCmd_Enable,434050.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_4_XA.MCmd_Disable,434050.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_4_XA.ALRM,434050.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_REC_0131_4_XA.ANUN,434050.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_REC_0131_4_XA.AKED,434050.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_REC_0131_4_XA.Resetable,434050.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_REC_0131_4_XA.Shelve,434050.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_REC_0131_4_XA.Suppress,434050.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_REC_0131_4_XA.InputAlarm,434050.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_REC_0131_4_XA.GlobalReset,434051.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_REC_0131_4_XA.PCSuppress,434051.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_REC_0131_4_XA.PCUnSuppress,434051.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_REC_0131_4_XA.PCUnshelve,434051.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_REC_0131_4_XA.Alarm_Fault,434051.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_REC_0131_4_XA.Shelved,434051.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_REC_0131_4_XA.Suppressed,434051.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_REC_0131_4_XA.PLCIOFault,434051.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_4_XA.PLCF,434051.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_REC_0131_4_XA.TAGR,434051.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SD_0112_1_XA.Fault,434086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SD_0112_1_XA.Faulted,434086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SD_0112_1_XA.AlarmState,434086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SD_0112_1_XA.FaultInAlarm,434086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0112_1_XA.Alarm_EN,434086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SD_0112_1_XA.REST,434086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SD_0112_1_XA.ACKN,434086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SD_0112_1_XA.MCmd_Enable,434086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0112_1_XA.MCmd_Disable,434086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0112_1_XA.ALRM,434086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SD_0112_1_XA.ANUN,434086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SD_0112_1_XA.AKED,434086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SD_0112_1_XA.Resetable,434086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SD_0112_1_XA.Shelve,434086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SD_0112_1_XA.Suppress,434086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SD_0112_1_XA.InputAlarm,434086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SD_0112_1_XA.GlobalReset,434087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SD_0112_1_XA.PCSuppress,434087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SD_0112_1_XA.PCUnSuppress,434087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SD_0112_1_XA.PCUnshelve,434087.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SD_0112_1_XA.Alarm_Fault,434087.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SD_0112_1_XA.Shelved,434087.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SD_0112_1_XA.Suppressed,434087.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SD_0112_1_XA.PLCIOFault,434087.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0112_1_XA.PLCF,434087.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0112_1_XA.TAGR,434087.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SD_0113_1_XA.Fault,434120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SD_0113_1_XA.Faulted,434120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SD_0113_1_XA.AlarmState,434120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SD_0113_1_XA.FaultInAlarm,434120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_1_XA.Alarm_EN,434120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SD_0113_1_XA.REST,434120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SD_0113_1_XA.ACKN,434120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SD_0113_1_XA.MCmd_Enable,434120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_1_XA.MCmd_Disable,434120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_1_XA.ALRM,434120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SD_0113_1_XA.ANUN,434120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SD_0113_1_XA.AKED,434120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SD_0113_1_XA.Resetable,434120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SD_0113_1_XA.Shelve,434120.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SD_0113_1_XA.Suppress,434120.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SD_0113_1_XA.InputAlarm,434120.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SD_0113_1_XA.GlobalReset,434121.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SD_0113_1_XA.PCSuppress,434121.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SD_0113_1_XA.PCUnSuppress,434121.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SD_0113_1_XA.PCUnshelve,434121.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SD_0113_1_XA.Alarm_Fault,434121.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SD_0113_1_XA.Shelved,434121.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SD_0113_1_XA.Suppressed,434121.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SD_0113_1_XA.PLCIOFault,434121.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0113_1_XA.PLCF,434121.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0113_1_XA.TAGR,434121.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SD_0113_2_XA.Fault,434156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SD_0113_2_XA.Faulted,434156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SD_0113_2_XA.AlarmState,434156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SD_0113_2_XA.FaultInAlarm,434156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_2_XA.Alarm_EN,434156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SD_0113_2_XA.REST,434156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SD_0113_2_XA.ACKN,434156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SD_0113_2_XA.MCmd_Enable,434156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_2_XA.MCmd_Disable,434156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_2_XA.ALRM,434156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SD_0113_2_XA.ANUN,434156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SD_0113_2_XA.AKED,434156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SD_0113_2_XA.Resetable,434156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SD_0113_2_XA.Shelve,434156.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SD_0113_2_XA.Suppress,434156.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SD_0113_2_XA.InputAlarm,434156.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SD_0113_2_XA.GlobalReset,434157.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SD_0113_2_XA.PCSuppress,434157.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SD_0113_2_XA.PCUnSuppress,434157.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SD_0113_2_XA.PCUnshelve,434157.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SD_0113_2_XA.Alarm_Fault,434157.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SD_0113_2_XA.Shelved,434157.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SD_0113_2_XA.Suppressed,434157.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SD_0113_2_XA.PLCIOFault,434157.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0113_2_XA.PLCF,434157.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0113_2_XA.TAGR,434157.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SD_0114_1_XA.Fault,434190.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SD_0114_1_XA.Faulted,434190.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SD_0114_1_XA.AlarmState,434190.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SD_0114_1_XA.FaultInAlarm,434190.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_1_XA.Alarm_EN,434190.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SD_0114_1_XA.REST,434190.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SD_0114_1_XA.ACKN,434190.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SD_0114_1_XA.MCmd_Enable,434190.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_1_XA.MCmd_Disable,434190.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_1_XA.ALRM,434190.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SD_0114_1_XA.ANUN,434190.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SD_0114_1_XA.AKED,434190.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SD_0114_1_XA.Resetable,434190.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SD_0114_1_XA.Shelve,434190.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SD_0114_1_XA.Suppress,434190.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SD_0114_1_XA.InputAlarm,434190.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SD_0114_1_XA.GlobalReset,434191.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SD_0114_1_XA.PCSuppress,434191.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SD_0114_1_XA.PCUnSuppress,434191.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SD_0114_1_XA.PCUnshelve,434191.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SD_0114_1_XA.Alarm_Fault,434191.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SD_0114_1_XA.Shelved,434191.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SD_0114_1_XA.Suppressed,434191.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SD_0114_1_XA.PLCIOFault,434191.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0114_1_XA.PLCF,434191.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0114_1_XA.TAGR,434191.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SD_0114_2_XA.Fault,434226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SD_0114_2_XA.Faulted,434226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SD_0114_2_XA.AlarmState,434226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SD_0114_2_XA.FaultInAlarm,434226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_2_XA.Alarm_EN,434226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SD_0114_2_XA.REST,434226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SD_0114_2_XA.ACKN,434226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SD_0114_2_XA.MCmd_Enable,434226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_2_XA.MCmd_Disable,434226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_2_XA.ALRM,434226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SD_0114_2_XA.ANUN,434226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SD_0114_2_XA.AKED,434226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SD_0114_2_XA.Resetable,434226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SD_0114_2_XA.Shelve,434226.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SD_0114_2_XA.Suppress,434226.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SD_0114_2_XA.InputAlarm,434226.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SD_0114_2_XA.GlobalReset,434227.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SD_0114_2_XA.PCSuppress,434227.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SD_0114_2_XA.PCUnSuppress,434227.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SD_0114_2_XA.PCUnshelve,434227.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SD_0114_2_XA.Alarm_Fault,434227.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SD_0114_2_XA.Shelved,434227.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SD_0114_2_XA.Suppressed,434227.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SD_0114_2_XA.PLCIOFault,434227.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0114_2_XA.PLCF,434227.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SD_0114_2_XA.TAGR,434227.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_1_XA.Fault,434260.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_1_XA.Faulted,434260.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_1_XA.AlarmState,434260.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_1_XA.FaultInAlarm,434260.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_1_XA.Alarm_EN,434260.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_1_XA.REST,434260.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_1_XA.ACKN,434260.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_1_XA.MCmd_Enable,434260.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_1_XA.MCmd_Disable,434260.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_1_XA.ALRM,434260.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_1_XA.ANUN,434260.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_1_XA.AKED,434260.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_1_XA.Resetable,434260.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_1_XA.Shelve,434260.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_1_XA.Suppress,434260.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_1_XA.InputAlarm,434260.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_1_XA.GlobalReset,434261.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_1_XA.PCSuppress,434261.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_1_XA.PCUnSuppress,434261.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_1_XA.PCUnshelve,434261.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_1_XA.Alarm_Fault,434261.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_1_XA.Shelved,434261.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_1_XA.Suppressed,434261.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_1_XA.PLCIOFault,434261.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_1_XA.PLCF,434261.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_1_XA.TAGR,434261.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_2_XA.Fault,434296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_2_XA.Faulted,434296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_2_XA.AlarmState,434296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_2_XA.FaultInAlarm,434296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_2_XA.Alarm_EN,434296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_2_XA.REST,434296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_2_XA.ACKN,434296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_2_XA.MCmd_Enable,434296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_2_XA.MCmd_Disable,434296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_2_XA.ALRM,434296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_2_XA.ANUN,434296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_2_XA.AKED,434296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_2_XA.Resetable,434296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_2_XA.Shelve,434296.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_2_XA.Suppress,434296.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_2_XA.InputAlarm,434296.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_2_XA.GlobalReset,434297.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_2_XA.PCSuppress,434297.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_2_XA.PCUnSuppress,434297.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_2_XA.PCUnshelve,434297.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_2_XA.Alarm_Fault,434297.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_2_XA.Shelved,434297.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_2_XA.Suppressed,434297.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_2_XA.PLCIOFault,434297.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_2_XA.PLCF,434297.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_2_XA.TAGR,434297.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_3_XA1.Fault,434330.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_3_XA1.Faulted,434330.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_3_XA1.AlarmState,434330.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_3_XA1.FaultInAlarm,434330.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3_XA1.Alarm_EN,434330.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_3_XA1.REST,434330.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_3_XA1.ACKN,434330.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_3_XA1.MCmd_Enable,434330.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3_XA1.MCmd_Disable,434330.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3_XA1.ALRM,434330.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_3_XA1.ANUN,434330.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_3_XA1.AKED,434330.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_3_XA1.Resetable,434330.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_3_XA1.Shelve,434330.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_3_XA1.Suppress,434330.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_3_XA1.InputAlarm,434330.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_3_XA1.GlobalReset,434331.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_3_XA1.PCSuppress,434331.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_3_XA1.PCUnSuppress,434331.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_3_XA1.PCUnshelve,434331.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_3_XA1.Alarm_Fault,434331.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_3_XA1.Shelved,434331.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_3_XA1.Suppressed,434331.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_3_XA1.PLCIOFault,434331.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3_XA1.PLCF,434331.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3_XA1.TAGR,434331.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_3A_XA.Fault,434366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_3A_XA.Faulted,434366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_3A_XA.AlarmState,434366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_3A_XA.FaultInAlarm,434366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3A_XA.Alarm_EN,434366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_3A_XA.REST,434366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_3A_XA.ACKN,434366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_3A_XA.MCmd_Enable,434366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3A_XA.MCmd_Disable,434366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3A_XA.ALRM,434366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_3A_XA.ANUN,434366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_3A_XA.AKED,434366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_3A_XA.Resetable,434366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_3A_XA.Shelve,434366.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_3A_XA.Suppress,434366.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_3A_XA.InputAlarm,434366.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_3A_XA.GlobalReset,434367.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_3A_XA.PCSuppress,434367.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_3A_XA.PCUnSuppress,434367.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_3A_XA.PCUnshelve,434367.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_3A_XA.Alarm_Fault,434367.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_3A_XA.Shelved,434367.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_3A_XA.Suppressed,434367.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_3A_XA.PLCIOFault,434367.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3A_XA.PLCF,434367.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3A_XA.TAGR,434367.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_3B_XA.Fault,434400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_3B_XA.Faulted,434400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_3B_XA.AlarmState,434400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_3B_XA.FaultInAlarm,434400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3B_XA.Alarm_EN,434400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_3B_XA.REST,434400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_3B_XA.ACKN,434400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_3B_XA.MCmd_Enable,434400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3B_XA.MCmd_Disable,434400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3B_XA.ALRM,434400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_3B_XA.ANUN,434400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_3B_XA.AKED,434400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_3B_XA.Resetable,434400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_3B_XA.Shelve,434400.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_3B_XA.Suppress,434400.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_3B_XA.InputAlarm,434400.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_3B_XA.GlobalReset,434401.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_3B_XA.PCSuppress,434401.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_3B_XA.PCUnSuppress,434401.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_3B_XA.PCUnshelve,434401.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_3B_XA.Alarm_Fault,434401.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_3B_XA.Shelved,434401.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_3B_XA.Suppressed,434401.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_3B_XA.PLCIOFault,434401.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3B_XA.PLCF,434401.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_3B_XA.TAGR,434401.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_4_XA.Fault,434436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_4_XA.Faulted,434436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_4_XA.AlarmState,434436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_4_XA.FaultInAlarm,434436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA.Alarm_EN,434436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_4_XA.REST,434436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_4_XA.ACKN,434436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_4_XA.MCmd_Enable,434436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA.MCmd_Disable,434436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA.ALRM,434436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_4_XA.ANUN,434436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_4_XA.AKED,434436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_4_XA.Resetable,434436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_4_XA.Shelve,434436.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_4_XA.Suppress,434436.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_4_XA.InputAlarm,434436.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_4_XA.GlobalReset,434437.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_4_XA.PCSuppress,434437.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_4_XA.PCUnSuppress,434437.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_4_XA.PCUnshelve,434437.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_4_XA.Alarm_Fault,434437.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_4_XA.Shelved,434437.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_4_XA.Suppressed,434437.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_4_XA.PLCIOFault,434437.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_4_XA.PLCF,434437.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_4_XA.TAGR,434437.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_4_XA1.Fault,434470.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_4_XA1.Faulted,434470.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_4_XA1.AlarmState,434470.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_4_XA1.FaultInAlarm,434470.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA1.Alarm_EN,434470.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_4_XA1.REST,434470.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_4_XA1.ACKN,434470.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_4_XA1.MCmd_Enable,434470.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA1.MCmd_Disable,434470.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA1.ALRM,434470.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_4_XA1.ANUN,434470.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_4_XA1.AKED,434470.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_4_XA1.Resetable,434470.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_4_XA1.Shelve,434470.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_4_XA1.Suppress,434470.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_4_XA1.InputAlarm,434470.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_4_XA1.GlobalReset,434471.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_4_XA1.PCSuppress,434471.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_4_XA1.PCUnSuppress,434471.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_4_XA1.PCUnshelve,434471.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_4_XA1.Alarm_Fault,434471.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_4_XA1.Shelved,434471.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_4_XA1.Suppressed,434471.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_4_XA1.PLCIOFault,434471.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_4_XA1.PLCF,434471.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_4_XA1.TAGR,434471.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_5_XA.Fault,434506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_5_XA.Faulted,434506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_5_XA.AlarmState,434506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_5_XA.FaultInAlarm,434506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_5_XA.Alarm_EN,434506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_5_XA.REST,434506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_5_XA.ACKN,434506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_5_XA.MCmd_Enable,434506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_5_XA.MCmd_Disable,434506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_5_XA.ALRM,434506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_5_XA.ANUN,434506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_5_XA.AKED,434506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_5_XA.Resetable,434506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_5_XA.Shelve,434506.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_5_XA.Suppress,434506.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_5_XA.InputAlarm,434506.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_5_XA.GlobalReset,434507.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_5_XA.PCSuppress,434507.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_5_XA.PCUnSuppress,434507.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_5_XA.PCUnshelve,434507.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_5_XA.Alarm_Fault,434507.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_5_XA.Shelved,434507.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_5_XA.Suppressed,434507.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_5_XA.PLCIOFault,434507.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_5_XA.PLCF,434507.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_5_XA.TAGR,434507.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0112_6_XA.Fault,434540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0112_6_XA.Faulted,434540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0112_6_XA.AlarmState,434540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0112_6_XA.FaultInAlarm,434540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_6_XA.Alarm_EN,434540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0112_6_XA.REST,434540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0112_6_XA.ACKN,434540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0112_6_XA.MCmd_Enable,434540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_6_XA.MCmd_Disable,434540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_6_XA.ALRM,434540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0112_6_XA.ANUN,434540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0112_6_XA.AKED,434540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0112_6_XA.Resetable,434540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0112_6_XA.Shelve,434540.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0112_6_XA.Suppress,434540.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0112_6_XA.InputAlarm,434540.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0112_6_XA.GlobalReset,434541.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0112_6_XA.PCSuppress,434541.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0112_6_XA.PCUnSuppress,434541.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0112_6_XA.PCUnshelve,434541.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0112_6_XA.Alarm_Fault,434541.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0112_6_XA.Shelved,434541.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0112_6_XA.Suppressed,434541.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0112_6_XA.PLCIOFault,434541.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_6_XA.PLCF,434541.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0112_6_XA.TAGR,434541.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0113_1_XA.Fault,434576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0113_1_XA.Faulted,434576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0113_1_XA.AlarmState,434576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0113_1_XA.FaultInAlarm,434576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_1_XA.Alarm_EN,434576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0113_1_XA.REST,434576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0113_1_XA.ACKN,434576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0113_1_XA.MCmd_Enable,434576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_1_XA.MCmd_Disable,434576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_1_XA.ALRM,434576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0113_1_XA.ANUN,434576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0113_1_XA.AKED,434576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0113_1_XA.Resetable,434576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0113_1_XA.Shelve,434576.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0113_1_XA.Suppress,434576.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0113_1_XA.InputAlarm,434576.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0113_1_XA.GlobalReset,434577.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0113_1_XA.PCSuppress,434577.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0113_1_XA.PCUnSuppress,434577.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0113_1_XA.PCUnshelve,434577.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0113_1_XA.Alarm_Fault,434577.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0113_1_XA.Shelved,434577.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0113_1_XA.Suppressed,434577.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0113_1_XA.PLCIOFault,434577.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0113_1_XA.PLCF,434577.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0113_1_XA.TAGR,434577.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_SPD_0113_2_XA.Fault,434610.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_SPD_0113_2_XA.Faulted,434610.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_SPD_0113_2_XA.AlarmState,434610.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_SPD_0113_2_XA.FaultInAlarm,434610.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_2_XA.Alarm_EN,434610.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_SPD_0113_2_XA.REST,434610.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_SPD_0113_2_XA.ACKN,434610.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_SPD_0113_2_XA.MCmd_Enable,434610.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_2_XA.MCmd_Disable,434610.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_2_XA.ALRM,434610.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_SPD_0113_2_XA.ANUN,434610.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_SPD_0113_2_XA.AKED,434610.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_SPD_0113_2_XA.Resetable,434610.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_SPD_0113_2_XA.Shelve,434610.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_SPD_0113_2_XA.Suppress,434610.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_SPD_0113_2_XA.InputAlarm,434610.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_SPD_0113_2_XA.GlobalReset,434611.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_SPD_0113_2_XA.PCSuppress,434611.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_SPD_0113_2_XA.PCUnSuppress,434611.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_SPD_0113_2_XA.PCUnshelve,434611.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_SPD_0113_2_XA.Alarm_Fault,434611.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_SPD_0113_2_XA.Shelved,434611.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_SPD_0113_2_XA.Suppressed,434611.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_SPD_0113_2_XA.PLCIOFault,434611.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0113_2_XA.PLCF,434611.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_SPD_0113_2_XA.TAGR,434611.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0111_1_TH.Fault,434646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0111_1_TH.Faulted,434646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0111_1_TH.AlarmState,434646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0111_1_TH.FaultInAlarm,434646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0111_1_TH.Alarm_EN,434646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0111_1_TH.REST,434646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0111_1_TH.ACKN,434646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0111_1_TH.MCmd_Enable,434646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0111_1_TH.MCmd_Disable,434646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0111_1_TH.ALRM,434646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0111_1_TH.ANUN,434646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0111_1_TH.AKED,434646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0111_1_TH.Resetable,434646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0111_1_TH.Shelve,434646.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0111_1_TH.Suppress,434646.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0111_1_TH.InputAlarm,434646.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0111_1_TH.GlobalReset,434647.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0111_1_TH.PCSuppress,434647.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0111_1_TH.PCUnSuppress,434647.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0111_1_TH.PCUnshelve,434647.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0111_1_TH.Alarm_Fault,434647.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0111_1_TH.Shelved,434647.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0111_1_TH.Suppressed,434647.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0111_1_TH.PLCIOFault,434647.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0111_1_TH.PLCF,434647.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0111_1_TH.TAGR,434647.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0112_1_TH.Fault,434680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0112_1_TH.Faulted,434680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0112_1_TH.AlarmState,434680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0112_1_TH.FaultInAlarm,434680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0112_1_TH.Alarm_EN,434680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0112_1_TH.REST,434680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0112_1_TH.ACKN,434680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0112_1_TH.MCmd_Enable,434680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0112_1_TH.MCmd_Disable,434680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0112_1_TH.ALRM,434680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0112_1_TH.ANUN,434680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0112_1_TH.AKED,434680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0112_1_TH.Resetable,434680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0112_1_TH.Shelve,434680.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0112_1_TH.Suppress,434680.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0112_1_TH.InputAlarm,434680.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0112_1_TH.GlobalReset,434681.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0112_1_TH.PCSuppress,434681.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0112_1_TH.PCUnSuppress,434681.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0112_1_TH.PCUnshelve,434681.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0112_1_TH.Alarm_Fault,434681.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0112_1_TH.Shelved,434681.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0112_1_TH.Suppressed,434681.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0112_1_TH.PLCIOFault,434681.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0112_1_TH.PLCF,434681.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0112_1_TH.TAGR,434681.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0113_1_TH.Fault,434716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0113_1_TH.Faulted,434716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0113_1_TH.AlarmState,434716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0113_1_TH.FaultInAlarm,434716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_1_TH.Alarm_EN,434716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0113_1_TH.REST,434716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0113_1_TH.ACKN,434716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0113_1_TH.MCmd_Enable,434716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_1_TH.MCmd_Disable,434716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_1_TH.ALRM,434716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0113_1_TH.ANUN,434716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0113_1_TH.AKED,434716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0113_1_TH.Resetable,434716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0113_1_TH.Shelve,434716.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0113_1_TH.Suppress,434716.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0113_1_TH.InputAlarm,434716.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0113_1_TH.GlobalReset,434717.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0113_1_TH.PCSuppress,434717.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0113_1_TH.PCUnSuppress,434717.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0113_1_TH.PCUnshelve,434717.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0113_1_TH.Alarm_Fault,434717.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0113_1_TH.Shelved,434717.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0113_1_TH.Suppressed,434717.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0113_1_TH.PLCIOFault,434717.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0113_1_TH.PLCF,434717.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0113_1_TH.TAGR,434717.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0113_2_TH.Fault,434750.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0113_2_TH.Faulted,434750.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0113_2_TH.AlarmState,434750.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0113_2_TH.FaultInAlarm,434750.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_2_TH.Alarm_EN,434750.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0113_2_TH.REST,434750.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0113_2_TH.ACKN,434750.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0113_2_TH.MCmd_Enable,434750.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_2_TH.MCmd_Disable,434750.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_2_TH.ALRM,434750.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0113_2_TH.ANUN,434750.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0113_2_TH.AKED,434750.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0113_2_TH.Resetable,434750.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0113_2_TH.Shelve,434750.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0113_2_TH.Suppress,434750.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0113_2_TH.InputAlarm,434750.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0113_2_TH.GlobalReset,434751.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0113_2_TH.PCSuppress,434751.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0113_2_TH.PCUnSuppress,434751.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0113_2_TH.PCUnshelve,434751.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0113_2_TH.Alarm_Fault,434751.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0113_2_TH.Shelved,434751.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0113_2_TH.Suppressed,434751.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0113_2_TH.PLCIOFault,434751.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0113_2_TH.PLCF,434751.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0113_2_TH.TAGR,434751.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0114_1_TH.Fault,434786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0114_1_TH.Faulted,434786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0114_1_TH.AlarmState,434786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0114_1_TH.FaultInAlarm,434786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_1_TH.Alarm_EN,434786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0114_1_TH.REST,434786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0114_1_TH.ACKN,434786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0114_1_TH.MCmd_Enable,434786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_1_TH.MCmd_Disable,434786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_1_TH.ALRM,434786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0114_1_TH.ANUN,434786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0114_1_TH.AKED,434786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0114_1_TH.Resetable,434786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0114_1_TH.Shelve,434786.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0114_1_TH.Suppress,434786.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0114_1_TH.InputAlarm,434786.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0114_1_TH.GlobalReset,434787.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0114_1_TH.PCSuppress,434787.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0114_1_TH.PCUnSuppress,434787.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0114_1_TH.PCUnshelve,434787.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0114_1_TH.Alarm_Fault,434787.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0114_1_TH.Shelved,434787.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0114_1_TH.Suppressed,434787.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0114_1_TH.PLCIOFault,434787.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0114_1_TH.PLCF,434787.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0114_1_TH.TAGR,434787.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TE_0114_2_TH.Fault,434820.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TE_0114_2_TH.Faulted,434820.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TE_0114_2_TH.AlarmState,434820.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TE_0114_2_TH.FaultInAlarm,434820.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_2_TH.Alarm_EN,434820.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TE_0114_2_TH.REST,434820.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TE_0114_2_TH.ACKN,434820.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TE_0114_2_TH.MCmd_Enable,434820.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_2_TH.MCmd_Disable,434820.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_2_TH.ALRM,434820.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TE_0114_2_TH.ANUN,434820.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TE_0114_2_TH.AKED,434820.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TE_0114_2_TH.Resetable,434820.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TE_0114_2_TH.Shelve,434820.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TE_0114_2_TH.Suppress,434820.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TE_0114_2_TH.InputAlarm,434820.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TE_0114_2_TH.GlobalReset,434821.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TE_0114_2_TH.PCSuppress,434821.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TE_0114_2_TH.PCUnSuppress,434821.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TE_0114_2_TH.PCUnshelve,434821.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TE_0114_2_TH.Alarm_Fault,434821.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TE_0114_2_TH.Shelved,434821.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TE_0114_2_TH.Suppressed,434821.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TE_0114_2_TH.PLCIOFault,434821.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0114_2_TH.PLCF,434821.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TE_0114_2_TH.TAGR,434821.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_1_LL.Fault,434856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_1_LL.Faulted,434856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_1_LL.AlarmState,434856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_1_LL.FaultInAlarm,434856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_LL.Alarm_EN,434856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_1_LL.REST,434856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_1_LL.ACKN,434856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_1_LL.MCmd_Enable,434856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_LL.MCmd_Disable,434856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_LL.ALRM,434856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_1_LL.ANUN,434856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_1_LL.AKED,434856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_1_LL.Resetable,434856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_1_LL.Shelve,434856.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_1_LL.Suppress,434856.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_1_LL.InputAlarm,434856.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_1_LL.GlobalReset,434857.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_1_LL.PCSuppress,434857.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_1_LL.PCUnSuppress,434857.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_1_LL.PCUnshelve,434857.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_1_LL.Alarm_Fault,434857.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_1_LL.Shelved,434857.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_1_LL.Suppressed,434857.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_1_LL.PLCIOFault,434857.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_LL.PLCF,434857.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_LL.TAGR,434857.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_1_TH1.Fault,434890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_1_TH1.Faulted,434890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_1_TH1.AlarmState,434890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_1_TH1.FaultInAlarm,434890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH1.Alarm_EN,434890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_1_TH1.REST,434890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_1_TH1.ACKN,434890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_1_TH1.MCmd_Enable,434890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH1.MCmd_Disable,434890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH1.ALRM,434890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_1_TH1.ANUN,434890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_1_TH1.AKED,434890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_1_TH1.Resetable,434890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_1_TH1.Shelve,434890.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_1_TH1.Suppress,434890.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_1_TH1.InputAlarm,434890.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_1_TH1.GlobalReset,434891.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_1_TH1.PCSuppress,434891.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_1_TH1.PCUnSuppress,434891.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_1_TH1.PCUnshelve,434891.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_1_TH1.Alarm_Fault,434891.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_1_TH1.Shelved,434891.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_1_TH1.Suppressed,434891.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_1_TH1.PLCIOFault,434891.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_TH1.PLCF,434891.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_TH1.TAGR,434891.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_1_TH2.Fault,434926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_1_TH2.Faulted,434926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_1_TH2.AlarmState,434926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_1_TH2.FaultInAlarm,434926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH2.Alarm_EN,434926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_1_TH2.REST,434926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_1_TH2.ACKN,434926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_1_TH2.MCmd_Enable,434926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH2.MCmd_Disable,434926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH2.ALRM,434926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_1_TH2.ANUN,434926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_1_TH2.AKED,434926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_1_TH2.Resetable,434926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_1_TH2.Shelve,434926.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_1_TH2.Suppress,434926.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_1_TH2.InputAlarm,434926.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_1_TH2.GlobalReset,434927.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_1_TH2.PCSuppress,434927.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_1_TH2.PCUnSuppress,434927.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_1_TH2.PCUnshelve,434927.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_1_TH2.Alarm_Fault,434927.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_1_TH2.Shelved,434927.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_1_TH2.Suppressed,434927.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_1_TH2.PLCIOFault,434927.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_TH2.PLCF,434927.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_TH2.TAGR,434927.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_1_XA.Fault,434960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_1_XA.Faulted,434960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_1_XA.AlarmState,434960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_1_XA.FaultInAlarm,434960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_XA.Alarm_EN,434960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_1_XA.REST,434960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_1_XA.ACKN,434960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_1_XA.MCmd_Enable,434960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_XA.MCmd_Disable,434960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_XA.ALRM,434960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_1_XA.ANUN,434960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_1_XA.AKED,434960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_1_XA.Resetable,434960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_1_XA.Shelve,434960.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_1_XA.Suppress,434960.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_1_XA.InputAlarm,434960.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_1_XA.GlobalReset,434961.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_1_XA.PCSuppress,434961.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_1_XA.PCUnSuppress,434961.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_1_XA.PCUnshelve,434961.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_1_XA.Alarm_Fault,434961.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_1_XA.Shelved,434961.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_1_XA.Suppressed,434961.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_1_XA.PLCIOFault,434961.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_XA.PLCF,434961.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_1_XA.TAGR,434961.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_2_LL.Fault,434996.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_2_LL.Faulted,434996.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_2_LL.AlarmState,434996.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_2_LL.FaultInAlarm,434996.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_LL.Alarm_EN,434996.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_2_LL.REST,434996.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_2_LL.ACKN,434996.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_2_LL.MCmd_Enable,434996.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_LL.MCmd_Disable,434996.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_LL.ALRM,434996.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_2_LL.ANUN,434996.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_2_LL.AKED,434996.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_2_LL.Resetable,434996.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_2_LL.Shelve,434996.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_2_LL.Suppress,434996.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_2_LL.InputAlarm,434996.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_2_LL.GlobalReset,434997.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_2_LL.PCSuppress,434997.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_2_LL.PCUnSuppress,434997.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_2_LL.PCUnshelve,434997.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_2_LL.Alarm_Fault,434997.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_2_LL.Shelved,434997.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_2_LL.Suppressed,434997.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_2_LL.PLCIOFault,434997.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_LL.PLCF,434997.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_LL.TAGR,434997.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_2_TH1.Fault,435030.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_2_TH1.Faulted,435030.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_2_TH1.AlarmState,435030.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_2_TH1.FaultInAlarm,435030.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH1.Alarm_EN,435030.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_2_TH1.REST,435030.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_2_TH1.ACKN,435030.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_2_TH1.MCmd_Enable,435030.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH1.MCmd_Disable,435030.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH1.ALRM,435030.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_2_TH1.ANUN,435030.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_2_TH1.AKED,435030.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_2_TH1.Resetable,435030.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_2_TH1.Shelve,435030.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_2_TH1.Suppress,435030.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_2_TH1.InputAlarm,435030.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_2_TH1.GlobalReset,435031.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_2_TH1.PCSuppress,435031.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_2_TH1.PCUnSuppress,435031.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_2_TH1.PCUnshelve,435031.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_2_TH1.Alarm_Fault,435031.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_2_TH1.Shelved,435031.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_2_TH1.Suppressed,435031.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_2_TH1.PLCIOFault,435031.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_TH1.PLCF,435031.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_TH1.TAGR,435031.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_2_TH2.Fault,435066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_2_TH2.Faulted,435066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_2_TH2.AlarmState,435066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_2_TH2.FaultInAlarm,435066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH2.Alarm_EN,435066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_2_TH2.REST,435066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_2_TH2.ACKN,435066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_2_TH2.MCmd_Enable,435066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH2.MCmd_Disable,435066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH2.ALRM,435066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_2_TH2.ANUN,435066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_2_TH2.AKED,435066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_2_TH2.Resetable,435066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_2_TH2.Shelve,435066.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_2_TH2.Suppress,435066.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_2_TH2.InputAlarm,435066.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_2_TH2.GlobalReset,435067.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_2_TH2.PCSuppress,435067.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_2_TH2.PCUnSuppress,435067.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_2_TH2.PCUnshelve,435067.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_2_TH2.Alarm_Fault,435067.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_2_TH2.Shelved,435067.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_2_TH2.Suppressed,435067.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_2_TH2.PLCIOFault,435067.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_TH2.PLCF,435067.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_TH2.TAGR,435067.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_TFR_0131_2_XA.Fault,435100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_TFR_0131_2_XA.Faulted,435100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_TFR_0131_2_XA.AlarmState,435100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_TFR_0131_2_XA.FaultInAlarm,435100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_XA.Alarm_EN,435100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_TFR_0131_2_XA.REST,435100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_TFR_0131_2_XA.ACKN,435100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_TFR_0131_2_XA.MCmd_Enable,435100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_XA.MCmd_Disable,435100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_XA.ALRM,435100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_TFR_0131_2_XA.ANUN,435100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_TFR_0131_2_XA.AKED,435100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_TFR_0131_2_XA.Resetable,435100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_TFR_0131_2_XA.Shelve,435100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_TFR_0131_2_XA.Suppress,435100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_TFR_0131_2_XA.InputAlarm,435100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_TFR_0131_2_XA.GlobalReset,435101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_TFR_0131_2_XA.PCSuppress,435101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_TFR_0131_2_XA.PCUnSuppress,435101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_TFR_0131_2_XA.PCUnshelve,435101.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_TFR_0131_2_XA.Alarm_Fault,435101.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_TFR_0131_2_XA.Shelved,435101.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_TFR_0131_2_XA.Suppressed,435101.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_TFR_0131_2_XA.PLCIOFault,435101.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_XA.PLCF,435101.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_TFR_0131_2_XA.TAGR,435101.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_UPS_001_1_JA.Fault,435136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_UPS_001_1_JA.Faulted,435136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_UPS_001_1_JA.AlarmState,435136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_UPS_001_1_JA.FaultInAlarm,435136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_JA.Alarm_EN,435136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_UPS_001_1_JA.REST,435136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_UPS_001_1_JA.ACKN,435136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_UPS_001_1_JA.MCmd_Enable,435136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_JA.MCmd_Disable,435136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_JA.ALRM,435136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_UPS_001_1_JA.ANUN,435136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_UPS_001_1_JA.AKED,435136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_UPS_001_1_JA.Resetable,435136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_UPS_001_1_JA.Shelve,435136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_UPS_001_1_JA.Suppress,435136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_UPS_001_1_JA.InputAlarm,435136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_UPS_001_1_JA.GlobalReset,435137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_UPS_001_1_JA.PCSuppress,435137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_UPS_001_1_JA.PCUnSuppress,435137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_UPS_001_1_JA.PCUnshelve,435137.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_UPS_001_1_JA.Alarm_Fault,435137.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_UPS_001_1_JA.Shelved,435137.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_UPS_001_1_JA.Suppressed,435137.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_UPS_001_1_JA.PLCIOFault,435137.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_1_JA.PLCF,435137.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_1_JA.TAGR,435137.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_UPS_001_1_ZS.Fault,435170.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_UPS_001_1_ZS.Faulted,435170.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_UPS_001_1_ZS.AlarmState,435170.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_UPS_001_1_ZS.FaultInAlarm,435170.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_ZS.Alarm_EN,435170.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_UPS_001_1_ZS.REST,435170.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_UPS_001_1_ZS.ACKN,435170.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_UPS_001_1_ZS.MCmd_Enable,435170.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_ZS.MCmd_Disable,435170.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_ZS.ALRM,435170.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_UPS_001_1_ZS.ANUN,435170.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_UPS_001_1_ZS.AKED,435170.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_UPS_001_1_ZS.Resetable,435170.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_UPS_001_1_ZS.Shelve,435170.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_UPS_001_1_ZS.Suppress,435170.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_UPS_001_1_ZS.InputAlarm,435170.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_UPS_001_1_ZS.GlobalReset,435171.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_UPS_001_1_ZS.PCSuppress,435171.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_UPS_001_1_ZS.PCUnSuppress,435171.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_UPS_001_1_ZS.PCUnshelve,435171.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_UPS_001_1_ZS.Alarm_Fault,435171.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_UPS_001_1_ZS.Shelved,435171.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_UPS_001_1_ZS.Suppressed,435171.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_UPS_001_1_ZS.PLCIOFault,435171.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_1_ZS.PLCF,435171.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_1_ZS.TAGR,435171.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_UPS_001_2_JA.Fault,435206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_UPS_001_2_JA.Faulted,435206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_UPS_001_2_JA.AlarmState,435206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_UPS_001_2_JA.FaultInAlarm,435206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_JA.Alarm_EN,435206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_UPS_001_2_JA.REST,435206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_UPS_001_2_JA.ACKN,435206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_UPS_001_2_JA.MCmd_Enable,435206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_JA.MCmd_Disable,435206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_JA.ALRM,435206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_UPS_001_2_JA.ANUN,435206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_UPS_001_2_JA.AKED,435206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_UPS_001_2_JA.Resetable,435206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_UPS_001_2_JA.Shelve,435206.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_UPS_001_2_JA.Suppress,435206.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_UPS_001_2_JA.InputAlarm,435206.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_UPS_001_2_JA.GlobalReset,435207.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_UPS_001_2_JA.PCSuppress,435207.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_UPS_001_2_JA.PCUnSuppress,435207.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_UPS_001_2_JA.PCUnshelve,435207.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_UPS_001_2_JA.Alarm_Fault,435207.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_UPS_001_2_JA.Shelved,435207.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_UPS_001_2_JA.Suppressed,435207.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_UPS_001_2_JA.PLCIOFault,435207.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_2_JA.PLCF,435207.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_2_JA.TAGR,435207.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_UPS_001_2_ZS.Fault,435240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_UPS_001_2_ZS.Faulted,435240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_UPS_001_2_ZS.AlarmState,435240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_UPS_001_2_ZS.FaultInAlarm,435240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_ZS.Alarm_EN,435240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_UPS_001_2_ZS.REST,435240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_UPS_001_2_ZS.ACKN,435240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_UPS_001_2_ZS.MCmd_Enable,435240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_ZS.MCmd_Disable,435240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_ZS.ALRM,435240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_UPS_001_2_ZS.ANUN,435240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_UPS_001_2_ZS.AKED,435240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_UPS_001_2_ZS.Resetable,435240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_UPS_001_2_ZS.Shelve,435240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_UPS_001_2_ZS.Suppress,435240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_UPS_001_2_ZS.InputAlarm,435240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_UPS_001_2_ZS.GlobalReset,435241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_UPS_001_2_ZS.PCSuppress,435241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_UPS_001_2_ZS.PCUnSuppress,435241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_UPS_001_2_ZS.PCUnshelve,435241.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_UPS_001_2_ZS.Alarm_Fault,435241.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_UPS_001_2_ZS.Shelved,435241.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_UPS_001_2_ZS.Suppressed,435241.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_UPS_001_2_ZS.PLCIOFault,435241.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_2_ZS.PLCF,435241.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_UPS_001_2_ZS.TAGR,435241.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XE_0112_1A_ZA.Fault,435276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XE_0112_1A_ZA.Faulted,435276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XE_0112_1A_ZA.AlarmState,435276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XE_0112_1A_ZA.FaultInAlarm,435276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0112_1A_ZA.Alarm_EN,435276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XE_0112_1A_ZA.REST,435276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XE_0112_1A_ZA.ACKN,435276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XE_0112_1A_ZA.MCmd_Enable,435276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0112_1A_ZA.MCmd_Disable,435276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0112_1A_ZA.ALRM,435276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XE_0112_1A_ZA.ANUN,435276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XE_0112_1A_ZA.AKED,435276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XE_0112_1A_ZA.Resetable,435276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XE_0112_1A_ZA.Shelve,435276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XE_0112_1A_ZA.Suppress,435276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XE_0112_1A_ZA.InputAlarm,435276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XE_0112_1A_ZA.GlobalReset,435277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XE_0112_1A_ZA.PCSuppress,435277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XE_0112_1A_ZA.PCUnSuppress,435277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XE_0112_1A_ZA.PCUnshelve,435277.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XE_0112_1A_ZA.Alarm_Fault,435277.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XE_0112_1A_ZA.Shelved,435277.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XE_0112_1A_ZA.Suppressed,435277.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XE_0112_1A_ZA.PLCIOFault,435277.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0112_1A_ZA.PLCF,435277.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0112_1A_ZA.TAGR,435277.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XE_0113_1A_ZA.Fault,435310.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XE_0113_1A_ZA.Faulted,435310.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XE_0113_1A_ZA.AlarmState,435310.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XE_0113_1A_ZA.FaultInAlarm,435310.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1A_ZA.Alarm_EN,435310.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XE_0113_1A_ZA.REST,435310.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XE_0113_1A_ZA.ACKN,435310.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XE_0113_1A_ZA.MCmd_Enable,435310.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1A_ZA.MCmd_Disable,435310.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1A_ZA.ALRM,435310.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XE_0113_1A_ZA.ANUN,435310.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XE_0113_1A_ZA.AKED,435310.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XE_0113_1A_ZA.Resetable,435310.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XE_0113_1A_ZA.Shelve,435310.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XE_0113_1A_ZA.Suppress,435310.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XE_0113_1A_ZA.InputAlarm,435310.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XE_0113_1A_ZA.GlobalReset,435311.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XE_0113_1A_ZA.PCSuppress,435311.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XE_0113_1A_ZA.PCUnSuppress,435311.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XE_0113_1A_ZA.PCUnshelve,435311.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XE_0113_1A_ZA.Alarm_Fault,435311.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XE_0113_1A_ZA.Shelved,435311.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XE_0113_1A_ZA.Suppressed,435311.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XE_0113_1A_ZA.PLCIOFault,435311.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_1A_ZA.PLCF,435311.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_1A_ZA.TAGR,435311.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XE_0113_1B_ZA.Fault,435346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XE_0113_1B_ZA.Faulted,435346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XE_0113_1B_ZA.AlarmState,435346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XE_0113_1B_ZA.FaultInAlarm,435346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1B_ZA.Alarm_EN,435346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XE_0113_1B_ZA.REST,435346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XE_0113_1B_ZA.ACKN,435346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XE_0113_1B_ZA.MCmd_Enable,435346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1B_ZA.MCmd_Disable,435346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1B_ZA.ALRM,435346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XE_0113_1B_ZA.ANUN,435346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XE_0113_1B_ZA.AKED,435346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XE_0113_1B_ZA.Resetable,435346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XE_0113_1B_ZA.Shelve,435346.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XE_0113_1B_ZA.Suppress,435346.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XE_0113_1B_ZA.InputAlarm,435346.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XE_0113_1B_ZA.GlobalReset,435347.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XE_0113_1B_ZA.PCSuppress,435347.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XE_0113_1B_ZA.PCUnSuppress,435347.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XE_0113_1B_ZA.PCUnshelve,435347.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XE_0113_1B_ZA.Alarm_Fault,435347.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XE_0113_1B_ZA.Shelved,435347.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XE_0113_1B_ZA.Suppressed,435347.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XE_0113_1B_ZA.PLCIOFault,435347.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_1B_ZA.PLCF,435347.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_1B_ZA.TAGR,435347.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XE_0113_2A_ZA.Fault,435380.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XE_0113_2A_ZA.Faulted,435380.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XE_0113_2A_ZA.AlarmState,435380.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XE_0113_2A_ZA.FaultInAlarm,435380.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2A_ZA.Alarm_EN,435380.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XE_0113_2A_ZA.REST,435380.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XE_0113_2A_ZA.ACKN,435380.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XE_0113_2A_ZA.MCmd_Enable,435380.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2A_ZA.MCmd_Disable,435380.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2A_ZA.ALRM,435380.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XE_0113_2A_ZA.ANUN,435380.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XE_0113_2A_ZA.AKED,435380.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XE_0113_2A_ZA.Resetable,435380.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XE_0113_2A_ZA.Shelve,435380.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XE_0113_2A_ZA.Suppress,435380.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XE_0113_2A_ZA.InputAlarm,435380.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XE_0113_2A_ZA.GlobalReset,435381.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XE_0113_2A_ZA.PCSuppress,435381.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XE_0113_2A_ZA.PCUnSuppress,435381.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XE_0113_2A_ZA.PCUnshelve,435381.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XE_0113_2A_ZA.Alarm_Fault,435381.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XE_0113_2A_ZA.Shelved,435381.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XE_0113_2A_ZA.Suppressed,435381.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XE_0113_2A_ZA.PLCIOFault,435381.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_2A_ZA.PLCF,435381.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_2A_ZA.TAGR,435381.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XE_0113_2B_ZA.Fault,435416.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XE_0113_2B_ZA.Faulted,435416.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XE_0113_2B_ZA.AlarmState,435416.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XE_0113_2B_ZA.FaultInAlarm,435416.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2B_ZA.Alarm_EN,435416.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XE_0113_2B_ZA.REST,435416.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XE_0113_2B_ZA.ACKN,435416.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XE_0113_2B_ZA.MCmd_Enable,435416.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2B_ZA.MCmd_Disable,435416.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2B_ZA.ALRM,435416.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XE_0113_2B_ZA.ANUN,435416.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XE_0113_2B_ZA.AKED,435416.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XE_0113_2B_ZA.Resetable,435416.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XE_0113_2B_ZA.Shelve,435416.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XE_0113_2B_ZA.Suppress,435416.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XE_0113_2B_ZA.InputAlarm,435416.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XE_0113_2B_ZA.GlobalReset,435417.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XE_0113_2B_ZA.PCSuppress,435417.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XE_0113_2B_ZA.PCUnSuppress,435417.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XE_0113_2B_ZA.PCUnshelve,435417.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XE_0113_2B_ZA.Alarm_Fault,435417.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XE_0113_2B_ZA.Shelved,435417.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XE_0113_2B_ZA.Suppressed,435417.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XE_0113_2B_ZA.PLCIOFault,435417.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_2B_ZA.PLCF,435417.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XE_0113_2B_ZA.TAGR,435417.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_3_LL.Fault,435450.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_3_LL.Faulted,435450.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_3_LL.AlarmState,435450.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_3_LL.FaultInAlarm,435450.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_LL.Alarm_EN,435450.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_3_LL.REST,435450.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_3_LL.ACKN,435450.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_3_LL.MCmd_Enable,435450.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_LL.MCmd_Disable,435450.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_LL.ALRM,435450.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_3_LL.ANUN,435450.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_3_LL.AKED,435450.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_3_LL.Resetable,435450.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_3_LL.Shelve,435450.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_3_LL.Suppress,435450.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_3_LL.InputAlarm,435450.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_3_LL.GlobalReset,435451.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_3_LL.PCSuppress,435451.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_3_LL.PCUnSuppress,435451.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_3_LL.PCUnshelve,435451.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_3_LL.Alarm_Fault,435451.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_3_LL.Shelved,435451.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_3_LL.Suppressed,435451.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_3_LL.PLCIOFault,435451.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_LL.PLCF,435451.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_LL.TAGR,435451.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_3_TH1.Fault,435486.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_3_TH1.Faulted,435486.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_3_TH1.AlarmState,435486.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_3_TH1.FaultInAlarm,435486.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH1.Alarm_EN,435486.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_3_TH1.REST,435486.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_3_TH1.ACKN,435486.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_3_TH1.MCmd_Enable,435486.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH1.MCmd_Disable,435486.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH1.ALRM,435486.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_3_TH1.ANUN,435486.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_3_TH1.AKED,435486.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_3_TH1.Resetable,435486.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_3_TH1.Shelve,435486.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_3_TH1.Suppress,435486.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_3_TH1.InputAlarm,435486.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_3_TH1.GlobalReset,435487.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_3_TH1.PCSuppress,435487.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_3_TH1.PCUnSuppress,435487.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_3_TH1.PCUnshelve,435487.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_3_TH1.Alarm_Fault,435487.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_3_TH1.Shelved,435487.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_3_TH1.Suppressed,435487.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_3_TH1.PLCIOFault,435487.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_TH1.PLCF,435487.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_TH1.TAGR,435487.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_3_TH2.Fault,435520.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_3_TH2.Faulted,435520.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_3_TH2.AlarmState,435520.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_3_TH2.FaultInAlarm,435520.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH2.Alarm_EN,435520.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_3_TH2.REST,435520.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_3_TH2.ACKN,435520.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_3_TH2.MCmd_Enable,435520.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH2.MCmd_Disable,435520.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH2.ALRM,435520.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_3_TH2.ANUN,435520.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_3_TH2.AKED,435520.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_3_TH2.Resetable,435520.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_3_TH2.Shelve,435520.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_3_TH2.Suppress,435520.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_3_TH2.InputAlarm,435520.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_3_TH2.GlobalReset,435521.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_3_TH2.PCSuppress,435521.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_3_TH2.PCUnSuppress,435521.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_3_TH2.PCUnshelve,435521.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_3_TH2.Alarm_Fault,435521.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_3_TH2.Shelved,435521.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_3_TH2.Suppressed,435521.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_3_TH2.PLCIOFault,435521.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_TH2.PLCF,435521.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_TH2.TAGR,435521.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_3_XA.Fault,435556.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_3_XA.Faulted,435556.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_3_XA.AlarmState,435556.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_3_XA.FaultInAlarm,435556.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_XA.Alarm_EN,435556.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_3_XA.REST,435556.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_3_XA.ACKN,435556.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_3_XA.MCmd_Enable,435556.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_XA.MCmd_Disable,435556.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_XA.ALRM,435556.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_3_XA.ANUN,435556.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_3_XA.AKED,435556.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_3_XA.Resetable,435556.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_3_XA.Shelve,435556.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_3_XA.Suppress,435556.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_3_XA.InputAlarm,435556.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_3_XA.GlobalReset,435557.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_3_XA.PCSuppress,435557.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_3_XA.PCUnSuppress,435557.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_3_XA.PCUnshelve,435557.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_3_XA.Alarm_Fault,435557.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_3_XA.Shelved,435557.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_3_XA.Suppressed,435557.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_3_XA.PLCIOFault,435557.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_XA.PLCF,435557.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_3_XA.TAGR,435557.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_4_LL.Fault,435590.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_4_LL.Faulted,435590.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_4_LL.AlarmState,435590.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_4_LL.FaultInAlarm,435590.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_LL.Alarm_EN,435590.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_4_LL.REST,435590.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_4_LL.ACKN,435590.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_4_LL.MCmd_Enable,435590.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_LL.MCmd_Disable,435590.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_LL.ALRM,435590.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_4_LL.ANUN,435590.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_4_LL.AKED,435590.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_4_LL.Resetable,435590.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_4_LL.Shelve,435590.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_4_LL.Suppress,435590.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_4_LL.InputAlarm,435590.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_4_LL.GlobalReset,435591.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_4_LL.PCSuppress,435591.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_4_LL.PCUnSuppress,435591.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_4_LL.PCUnshelve,435591.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_4_LL.Alarm_Fault,435591.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_4_LL.Shelved,435591.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_4_LL.Suppressed,435591.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_4_LL.PLCIOFault,435591.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_LL.PLCF,435591.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_LL.TAGR,435591.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_4_TH1.Fault,435626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_4_TH1.Faulted,435626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_4_TH1.AlarmState,435626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_4_TH1.FaultInAlarm,435626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH1.Alarm_EN,435626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_4_TH1.REST,435626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_4_TH1.ACKN,435626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_4_TH1.MCmd_Enable,435626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH1.MCmd_Disable,435626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH1.ALRM,435626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_4_TH1.ANUN,435626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_4_TH1.AKED,435626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_4_TH1.Resetable,435626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_4_TH1.Shelve,435626.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_4_TH1.Suppress,435626.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_4_TH1.InputAlarm,435626.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_4_TH1.GlobalReset,435627.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_4_TH1.PCSuppress,435627.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_4_TH1.PCUnSuppress,435627.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_4_TH1.PCUnshelve,435627.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_4_TH1.Alarm_Fault,435627.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_4_TH1.Shelved,435627.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_4_TH1.Suppressed,435627.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_4_TH1.PLCIOFault,435627.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_TH1.PLCF,435627.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_TH1.TAGR,435627.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_4_TH2.Fault,435660.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_4_TH2.Faulted,435660.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_4_TH2.AlarmState,435660.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_4_TH2.FaultInAlarm,435660.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH2.Alarm_EN,435660.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_4_TH2.REST,435660.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_4_TH2.ACKN,435660.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_4_TH2.MCmd_Enable,435660.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH2.MCmd_Disable,435660.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH2.ALRM,435660.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_4_TH2.ANUN,435660.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_4_TH2.AKED,435660.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_4_TH2.Resetable,435660.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_4_TH2.Shelve,435660.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_4_TH2.Suppress,435660.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_4_TH2.InputAlarm,435660.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_4_TH2.GlobalReset,435661.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_4_TH2.PCSuppress,435661.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_4_TH2.PCUnSuppress,435661.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_4_TH2.PCUnshelve,435661.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_4_TH2.Alarm_Fault,435661.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_4_TH2.Shelved,435661.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_4_TH2.Suppressed,435661.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_4_TH2.PLCIOFault,435661.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_TH2.PLCF,435661.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_TH2.TAGR,435661.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_4_XA.Fault,435696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_4_XA.Faulted,435696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_4_XA.AlarmState,435696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_4_XA.FaultInAlarm,435696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_XA.Alarm_EN,435696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_4_XA.REST,435696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_4_XA.ACKN,435696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_4_XA.MCmd_Enable,435696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_XA.MCmd_Disable,435696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_XA.ALRM,435696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_4_XA.ANUN,435696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_4_XA.AKED,435696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_4_XA.Resetable,435696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_4_XA.Shelve,435696.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_4_XA.Suppress,435696.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_4_XA.InputAlarm,435696.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_4_XA.GlobalReset,435697.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_4_XA.PCSuppress,435697.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_4_XA.PCUnSuppress,435697.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_4_XA.PCUnshelve,435697.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_4_XA.Alarm_Fault,435697.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_4_XA.Shelved,435697.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_4_XA.Suppressed,435697.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_4_XA.PLCIOFault,435697.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_XA.PLCF,435697.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_4_XA.TAGR,435697.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_5_LL.Fault,435730.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_5_LL.Faulted,435730.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_5_LL.AlarmState,435730.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_5_LL.FaultInAlarm,435730.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_LL.Alarm_EN,435730.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_5_LL.REST,435730.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_5_LL.ACKN,435730.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_5_LL.MCmd_Enable,435730.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_LL.MCmd_Disable,435730.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_LL.ALRM,435730.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_5_LL.ANUN,435730.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_5_LL.AKED,435730.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_5_LL.Resetable,435730.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_5_LL.Shelve,435730.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_5_LL.Suppress,435730.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_5_LL.InputAlarm,435730.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_5_LL.GlobalReset,435731.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_5_LL.PCSuppress,435731.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_5_LL.PCUnSuppress,435731.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_5_LL.PCUnshelve,435731.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_5_LL.Alarm_Fault,435731.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_5_LL.Shelved,435731.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_5_LL.Suppressed,435731.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_5_LL.PLCIOFault,435731.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_LL.PLCF,435731.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_LL.TAGR,435731.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_5_TH1.Fault,435766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_5_TH1.Faulted,435766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_5_TH1.AlarmState,435766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_5_TH1.FaultInAlarm,435766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH1.Alarm_EN,435766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_5_TH1.REST,435766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_5_TH1.ACKN,435766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_5_TH1.MCmd_Enable,435766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH1.MCmd_Disable,435766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH1.ALRM,435766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_5_TH1.ANUN,435766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_5_TH1.AKED,435766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_5_TH1.Resetable,435766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_5_TH1.Shelve,435766.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_5_TH1.Suppress,435766.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_5_TH1.InputAlarm,435766.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_5_TH1.GlobalReset,435767.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_5_TH1.PCSuppress,435767.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_5_TH1.PCUnSuppress,435767.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_5_TH1.PCUnshelve,435767.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_5_TH1.Alarm_Fault,435767.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_5_TH1.Shelved,435767.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_5_TH1.Suppressed,435767.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_5_TH1.PLCIOFault,435767.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_TH1.PLCF,435767.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_TH1.TAGR,435767.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_5_TH2.Fault,435800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_5_TH2.Faulted,435800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_5_TH2.AlarmState,435800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_5_TH2.FaultInAlarm,435800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH2.Alarm_EN,435800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_5_TH2.REST,435800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_5_TH2.ACKN,435800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_5_TH2.MCmd_Enable,435800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH2.MCmd_Disable,435800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH2.ALRM,435800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_5_TH2.ANUN,435800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_5_TH2.AKED,435800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_5_TH2.Resetable,435800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_5_TH2.Shelve,435800.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_5_TH2.Suppress,435800.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_5_TH2.InputAlarm,435800.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_5_TH2.GlobalReset,435801.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_5_TH2.PCSuppress,435801.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_5_TH2.PCUnSuppress,435801.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_5_TH2.PCUnshelve,435801.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_5_TH2.Alarm_Fault,435801.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_5_TH2.Shelved,435801.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_5_TH2.Suppressed,435801.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_5_TH2.PLCIOFault,435801.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_TH2.PLCF,435801.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_TH2.TAGR,435801.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_5_XA.Fault,435836.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_5_XA.Faulted,435836.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_5_XA.AlarmState,435836.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_5_XA.FaultInAlarm,435836.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_XA.Alarm_EN,435836.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_5_XA.REST,435836.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_5_XA.ACKN,435836.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_5_XA.MCmd_Enable,435836.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_XA.MCmd_Disable,435836.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_XA.ALRM,435836.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_5_XA.ANUN,435836.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_5_XA.AKED,435836.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_5_XA.Resetable,435836.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_5_XA.Shelve,435836.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_5_XA.Suppress,435836.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_5_XA.InputAlarm,435836.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_5_XA.GlobalReset,435837.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_5_XA.PCSuppress,435837.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_5_XA.PCUnSuppress,435837.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_5_XA.PCUnshelve,435837.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_5_XA.Alarm_Fault,435837.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_5_XA.Shelved,435837.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_5_XA.Suppressed,435837.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_5_XA.PLCIOFault,435837.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_XA.PLCF,435837.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_5_XA.TAGR,435837.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_6_LL.Fault,435870.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_6_LL.Faulted,435870.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_6_LL.AlarmState,435870.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_6_LL.FaultInAlarm,435870.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_LL.Alarm_EN,435870.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_6_LL.REST,435870.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_6_LL.ACKN,435870.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_6_LL.MCmd_Enable,435870.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_LL.MCmd_Disable,435870.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_LL.ALRM,435870.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_6_LL.ANUN,435870.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_6_LL.AKED,435870.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_6_LL.Resetable,435870.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_6_LL.Shelve,435870.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_6_LL.Suppress,435870.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_6_LL.InputAlarm,435870.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_6_LL.GlobalReset,435871.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_6_LL.PCSuppress,435871.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_6_LL.PCUnSuppress,435871.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_6_LL.PCUnshelve,435871.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_6_LL.Alarm_Fault,435871.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_6_LL.Shelved,435871.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_6_LL.Suppressed,435871.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_6_LL.PLCIOFault,435871.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_LL.PLCF,435871.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_LL.TAGR,435871.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_6_TH1.Fault,435906.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_6_TH1.Faulted,435906.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_6_TH1.AlarmState,435906.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_6_TH1.FaultInAlarm,435906.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH1.Alarm_EN,435906.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_6_TH1.REST,435906.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_6_TH1.ACKN,435906.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_6_TH1.MCmd_Enable,435906.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH1.MCmd_Disable,435906.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH1.ALRM,435906.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_6_TH1.ANUN,435906.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_6_TH1.AKED,435906.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_6_TH1.Resetable,435906.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_6_TH1.Shelve,435906.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_6_TH1.Suppress,435906.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_6_TH1.InputAlarm,435906.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_6_TH1.GlobalReset,435907.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_6_TH1.PCSuppress,435907.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_6_TH1.PCUnSuppress,435907.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_6_TH1.PCUnshelve,435907.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_6_TH1.Alarm_Fault,435907.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_6_TH1.Shelved,435907.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_6_TH1.Suppressed,435907.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_6_TH1.PLCIOFault,435907.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_TH1.PLCF,435907.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_TH1.TAGR,435907.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_6_TH2.Fault,435940.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_6_TH2.Faulted,435940.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_6_TH2.AlarmState,435940.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_6_TH2.FaultInAlarm,435940.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH2.Alarm_EN,435940.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_6_TH2.REST,435940.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_6_TH2.ACKN,435940.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_6_TH2.MCmd_Enable,435940.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH2.MCmd_Disable,435940.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH2.ALRM,435940.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_6_TH2.ANUN,435940.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_6_TH2.AKED,435940.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_6_TH2.Resetable,435940.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_6_TH2.Shelve,435940.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_6_TH2.Suppress,435940.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_6_TH2.InputAlarm,435940.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_6_TH2.GlobalReset,435941.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_6_TH2.PCSuppress,435941.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_6_TH2.PCUnSuppress,435941.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_6_TH2.PCUnshelve,435941.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_6_TH2.Alarm_Fault,435941.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_6_TH2.Shelved,435941.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_6_TH2.Suppressed,435941.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_6_TH2.PLCIOFault,435941.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_TH2.PLCF,435941.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_TH2.TAGR,435941.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_XFR_0131_6_XA.Fault,435976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3252_XFR_0131_6_XA.Faulted,435976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3252_XFR_0131_6_XA.AlarmState,435976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3252_XFR_0131_6_XA.FaultInAlarm,435976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_XA.Alarm_EN,435976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3252_XFR_0131_6_XA.REST,435976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3252_XFR_0131_6_XA.ACKN,435976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3252_XFR_0131_6_XA.MCmd_Enable,435976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_XA.MCmd_Disable,435976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_XA.ALRM,435976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3252_XFR_0131_6_XA.ANUN,435976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3252_XFR_0131_6_XA.AKED,435976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3252_XFR_0131_6_XA.Resetable,435976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_XFR_0131_6_XA.Shelve,435976.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3252_XFR_0131_6_XA.Suppress,435976.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3252_XFR_0131_6_XA.InputAlarm,435976.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3252_XFR_0131_6_XA.GlobalReset,435977.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3252_XFR_0131_6_XA.PCSuppress,435977.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3252_XFR_0131_6_XA.PCUnSuppress,435977.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3252_XFR_0131_6_XA.PCUnshelve,435977.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3252_XFR_0131_6_XA.Alarm_Fault,435977.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3252_XFR_0131_6_XA.Shelved,435977.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3252_XFR_0131_6_XA.Suppressed,435977.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3252_XFR_0131_6_XA.PLCIOFault,435977.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_XA.PLCF,435977.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_XFR_0131_6_XA.TAGR,435977.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_EASTMICRO_FAIL.Fault,436010.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_EASTMICRO_FAIL.Faulted,436010.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_EASTMICRO_FAIL.AlarmState,436010.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_EASTMICRO_FAIL.FaultInAlarm,436010.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EASTMICRO_FAIL.Alarm_EN,436010.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_EASTMICRO_FAIL.REST,436010.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_EASTMICRO_FAIL.ACKN,436010.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_EASTMICRO_FAIL.MCmd_Enable,436010.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EASTMICRO_FAIL.MCmd_Disable,436010.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EASTMICRO_FAIL.ALRM,436010.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_EASTMICRO_FAIL.ANUN,436010.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_EASTMICRO_FAIL.AKED,436010.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_EASTMICRO_FAIL.Resetable,436010.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_EASTMICRO_FAIL.Shelve,436010.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_EASTMICRO_FAIL.Suppress,436010.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_EASTMICRO_FAIL.InputAlarm,436010.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_EASTMICRO_FAIL.GlobalReset,436011.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_EASTMICRO_FAIL.PCSuppress,436011.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_EASTMICRO_FAIL.PCUnSuppress,436011.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_EASTMICRO_FAIL.PCUnshelve,436011.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_EASTMICRO_FAIL.Alarm_Fault,436011.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_EASTMICRO_FAIL.Shelved,436011.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_EASTMICRO_FAIL.Suppressed,436011.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_EASTMICRO_FAIL.PLCIOFault,436011.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EASTMICRO_FAIL.PLCF,436011.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EASTMICRO_FAIL.TAGR,436011.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_EATON_PUMP1_FAIL.Fault,436046.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_EATON_PUMP1_FAIL.Faulted,436046.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_EATON_PUMP1_FAIL.AlarmState,436046.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_EATON_PUMP1_FAIL.FaultInAlarm,436046.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP1_FAIL.Alarm_EN,436046.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_EATON_PUMP1_FAIL.REST,436046.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_EATON_PUMP1_FAIL.ACKN,436046.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_EATON_PUMP1_FAIL.MCmd_Enable,436046.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.MCmd_Disable,436046.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.ALRM,436046.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_EATON_PUMP1_FAIL.ANUN,436046.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_EATON_PUMP1_FAIL.AKED,436046.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_EATON_PUMP1_FAIL.Resetable,436046.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_EATON_PUMP1_FAIL.Shelve,436046.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_EATON_PUMP1_FAIL.Suppress,436046.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_EATON_PUMP1_FAIL.InputAlarm,436046.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_EATON_PUMP1_FAIL.GlobalReset,436047.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_EATON_PUMP1_FAIL.PCSuppress,436047.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_EATON_PUMP1_FAIL.PCUnSuppress,436047.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_EATON_PUMP1_FAIL.PCUnshelve,436047.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_EATON_PUMP1_FAIL.Alarm_Fault,436047.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_EATON_PUMP1_FAIL.Shelved,436047.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_EATON_PUMP1_FAIL.Suppressed,436047.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_EATON_PUMP1_FAIL.PLCIOFault,436047.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP1_FAIL.PLCF,436047.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP1_FAIL.TAGR,436047.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_EATON_PUMP2_FAIL.Fault,436080.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_EATON_PUMP2_FAIL.Faulted,436080.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_EATON_PUMP2_FAIL.AlarmState,436080.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_EATON_PUMP2_FAIL.FaultInAlarm,436080.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP2_FAIL.Alarm_EN,436080.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_EATON_PUMP2_FAIL.REST,436080.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_EATON_PUMP2_FAIL.ACKN,436080.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_EATON_PUMP2_FAIL.MCmd_Enable,436080.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.MCmd_Disable,436080.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.ALRM,436080.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_EATON_PUMP2_FAIL.ANUN,436080.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_EATON_PUMP2_FAIL.AKED,436080.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_EATON_PUMP2_FAIL.Resetable,436080.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_EATON_PUMP2_FAIL.Shelve,436080.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_EATON_PUMP2_FAIL.Suppress,436080.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_EATON_PUMP2_FAIL.InputAlarm,436080.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_EATON_PUMP2_FAIL.GlobalReset,436081.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_EATON_PUMP2_FAIL.PCSuppress,436081.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_EATON_PUMP2_FAIL.PCUnSuppress,436081.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_EATON_PUMP2_FAIL.PCUnshelve,436081.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_EATON_PUMP2_FAIL.Alarm_Fault,436081.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_EATON_PUMP2_FAIL.Shelved,436081.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_EATON_PUMP2_FAIL.Suppressed,436081.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_EATON_PUMP2_FAIL.PLCIOFault,436081.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP2_FAIL.PLCF,436081.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP2_FAIL.TAGR,436081.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_EATON_PUMP9_FAIL.Fault,436116.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_EATON_PUMP9_FAIL.Faulted,436116.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_EATON_PUMP9_FAIL.AlarmState,436116.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_EATON_PUMP9_FAIL.FaultInAlarm,436116.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP9_FAIL.Alarm_EN,436116.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_EATON_PUMP9_FAIL.REST,436116.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_EATON_PUMP9_FAIL.ACKN,436116.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_EATON_PUMP9_FAIL.MCmd_Enable,436116.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.MCmd_Disable,436116.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.ALRM,436116.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_EATON_PUMP9_FAIL.ANUN,436116.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_EATON_PUMP9_FAIL.AKED,436116.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_EATON_PUMP9_FAIL.Resetable,436116.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_EATON_PUMP9_FAIL.Shelve,436116.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_EATON_PUMP9_FAIL.Suppress,436116.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_EATON_PUMP9_FAIL.InputAlarm,436116.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_EATON_PUMP9_FAIL.GlobalReset,436117.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_EATON_PUMP9_FAIL.PCSuppress,436117.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_EATON_PUMP9_FAIL.PCUnSuppress,436117.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_EATON_PUMP9_FAIL.PCUnshelve,436117.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_EATON_PUMP9_FAIL.Alarm_Fault,436117.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_EATON_PUMP9_FAIL.Shelved,436117.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_EATON_PUMP9_FAIL.Suppressed,436117.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_EATON_PUMP9_FAIL.PLCIOFault,436117.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP9_FAIL.PLCF,436117.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_EATON_PUMP9_FAIL.TAGR,436117.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_METER_VAULT_FAIL.Fault,436150.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_METER_VAULT_FAIL.Faulted,436150.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_METER_VAULT_FAIL.AlarmState,436150.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_METER_VAULT_FAIL.FaultInAlarm,436150.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_METER_VAULT_FAIL.Alarm_EN,436150.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_METER_VAULT_FAIL.REST,436150.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_METER_VAULT_FAIL.ACKN,436150.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_METER_VAULT_FAIL.MCmd_Enable,436150.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_METER_VAULT_FAIL.MCmd_Disable,436150.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_METER_VAULT_FAIL.ALRM,436150.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_METER_VAULT_FAIL.ANUN,436150.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_METER_VAULT_FAIL.AKED,436150.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_METER_VAULT_FAIL.Resetable,436150.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_METER_VAULT_FAIL.Shelve,436150.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_METER_VAULT_FAIL.Suppress,436150.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_METER_VAULT_FAIL.InputAlarm,436150.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_METER_VAULT_FAIL.GlobalReset,436151.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_METER_VAULT_FAIL.PCSuppress,436151.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_METER_VAULT_FAIL.PCUnSuppress,436151.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_METER_VAULT_FAIL.PCUnshelve,436151.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_METER_VAULT_FAIL.Alarm_Fault,436151.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_METER_VAULT_FAIL.Shelved,436151.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_METER_VAULT_FAIL.Suppressed,436151.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_METER_VAULT_FAIL.PLCIOFault,436151.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_METER_VAULT_FAIL.PLCF,436151.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_METER_VAULT_FAIL.TAGR,436151.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_SEL710_PUMP1_FAIL.Fault,436186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Faulted,436186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_SEL710_PUMP1_FAIL.AlarmState,436186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_SEL710_PUMP1_FAIL.FaultInAlarm,436186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm_EN,436186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_SEL710_PUMP1_FAIL.REST,436186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.ACKN,436186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.MCmd_Enable,436186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.MCmd_Disable,436186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.ALRM,436186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_SEL710_PUMP1_FAIL.ANUN,436186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_SEL710_PUMP1_FAIL.AKED,436186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_SEL710_PUMP1_FAIL.Resetable,436186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_SEL710_PUMP1_FAIL.Shelve,436186.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_SEL710_PUMP1_FAIL.Suppress,436186.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_SEL710_PUMP1_FAIL.InputAlarm,436186.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_SEL710_PUMP1_FAIL.GlobalReset,436187.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_SEL710_PUMP1_FAIL.PCSuppress,436187.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP1_FAIL.PCUnSuppress,436187.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP1_FAIL.PCUnshelve,436187.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm_Fault,436187.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_SEL710_PUMP1_FAIL.Shelved,436187.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_SEL710_PUMP1_FAIL.Suppressed,436187.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_SEL710_PUMP1_FAIL.PLCIOFault,436187.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP1_FAIL.PLCF,436187.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP1_FAIL.TAGR,436187.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_SEL710_PUMP2_FAIL.Fault,436220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Faulted,436220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_SEL710_PUMP2_FAIL.AlarmState,436220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_SEL710_PUMP2_FAIL.FaultInAlarm,436220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm_EN,436220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_SEL710_PUMP2_FAIL.REST,436220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.ACKN,436220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.MCmd_Enable,436220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.MCmd_Disable,436220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.ALRM,436220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_SEL710_PUMP2_FAIL.ANUN,436220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_SEL710_PUMP2_FAIL.AKED,436220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_SEL710_PUMP2_FAIL.Resetable,436220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_SEL710_PUMP2_FAIL.Shelve,436220.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_SEL710_PUMP2_FAIL.Suppress,436220.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_SEL710_PUMP2_FAIL.InputAlarm,436220.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_SEL710_PUMP2_FAIL.GlobalReset,436221.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_SEL710_PUMP2_FAIL.PCSuppress,436221.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP2_FAIL.PCUnSuppress,436221.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP2_FAIL.PCUnshelve,436221.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm_Fault,436221.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_SEL710_PUMP2_FAIL.Shelved,436221.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_SEL710_PUMP2_FAIL.Suppressed,436221.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_SEL710_PUMP2_FAIL.PLCIOFault,436221.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP2_FAIL.PLCF,436221.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP2_FAIL.TAGR,436221.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_SEL710_PUMP9_FAIL.Fault,436256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Faulted,436256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_SEL710_PUMP9_FAIL.AlarmState,436256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_SEL710_PUMP9_FAIL.FaultInAlarm,436256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm_EN,436256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_SEL710_PUMP9_FAIL.REST,436256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.ACKN,436256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.MCmd_Enable,436256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.MCmd_Disable,436256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.ALRM,436256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_SEL710_PUMP9_FAIL.ANUN,436256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_SEL710_PUMP9_FAIL.AKED,436256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_SEL710_PUMP9_FAIL.Resetable,436256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_SEL710_PUMP9_FAIL.Shelve,436256.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_SEL710_PUMP9_FAIL.Suppress,436256.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_SEL710_PUMP9_FAIL.InputAlarm,436256.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_SEL710_PUMP9_FAIL.GlobalReset,436257.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_SEL710_PUMP9_FAIL.PCSuppress,436257.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP9_FAIL.PCUnSuppress,436257.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_SEL710_PUMP9_FAIL.PCUnshelve,436257.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm_Fault,436257.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_SEL710_PUMP9_FAIL.Shelved,436257.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_SEL710_PUMP9_FAIL.Suppressed,436257.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_SEL710_PUMP9_FAIL.PLCIOFault,436257.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP9_FAIL.PLCF,436257.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_SEL710_PUMP9_FAIL.TAGR,436257.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_TSR_PLC_FAIL.Fault,436290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_TSR_PLC_FAIL.Faulted,436290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_TSR_PLC_FAIL.AlarmState,436290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_TSR_PLC_FAIL.FaultInAlarm,436290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_TSR_PLC_FAIL.Alarm_EN,436290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_TSR_PLC_FAIL.REST,436290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_TSR_PLC_FAIL.ACKN,436290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_TSR_PLC_FAIL.MCmd_Enable,436290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_TSR_PLC_FAIL.MCmd_Disable,436290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_TSR_PLC_FAIL.ALRM,436290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_TSR_PLC_FAIL.ANUN,436290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_TSR_PLC_FAIL.AKED,436290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_TSR_PLC_FAIL.Resetable,436290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_TSR_PLC_FAIL.Shelve,436290.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_TSR_PLC_FAIL.Suppress,436290.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_TSR_PLC_FAIL.InputAlarm,436290.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_TSR_PLC_FAIL.GlobalReset,436291.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_TSR_PLC_FAIL.PCSuppress,436291.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_TSR_PLC_FAIL.PCUnSuppress,436291.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_TSR_PLC_FAIL.PCUnshelve,436291.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_TSR_PLC_FAIL.Alarm_Fault,436291.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_TSR_PLC_FAIL.Shelved,436291.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_TSR_PLC_FAIL.Suppressed,436291.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_TSR_PLC_FAIL.PLCIOFault,436291.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_TSR_PLC_FAIL.PLCF,436291.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_TSR_PLC_FAIL.TAGR,436291.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3260_COMM_WESTMICRO_FAIL.Fault,436326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input tag to monitor for alarm" WA3260_COMM_WESTMICRO_FAIL.Faulted,436326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input is in fault" WA3260_COMM_WESTMICRO_FAIL.AlarmState,436326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Input value signifying alarm" WA3260_COMM_WESTMICRO_FAIL.FaultInAlarm,436326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_WESTMICRO_FAIL.Alarm_EN,436326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: 0 = enable alarm" WA3260_COMM_WESTMICRO_FAIL.REST,436326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset Alarm" WA3260_COMM_WESTMICRO_FAIL.ACKN,436326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Acknowledge Alarm" WA3260_COMM_WESTMICRO_FAIL.MCmd_Enable,436326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_WESTMICRO_FAIL.MCmd_Disable,436326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_WESTMICRO_FAIL.ALRM,436326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Active" WA3260_COMM_WESTMICRO_FAIL.ANUN,436326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Annunciating" WA3260_COMM_WESTMICRO_FAIL.AKED,436326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At Least One Alarm is Acknowledged" WA3260_COMM_WESTMICRO_FAIL.Resetable,436326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3260_COMM_WESTMICRO_FAIL.Shelve,436326.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelve Command from HMI" WA3260_COMM_WESTMICRO_FAIL.Suppress,436326.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Command from HMI" WA3260_COMM_WESTMICRO_FAIL.InputAlarm,436326.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: " WA3260_COMM_WESTMICRO_FAIL.GlobalReset,436327.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Reset all Alarms On this PLC" WA3260_COMM_WESTMICRO_FAIL.PCSuppress,436327.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppress Alarm from Program Control" WA3260_COMM_WESTMICRO_FAIL.PCUnSuppress,436327.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: UnSuppress Alarm from Program Control" WA3260_COMM_WESTMICRO_FAIL.PCUnshelve,436327.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Unshelve Alarm from Program Control" WA3260_COMM_WESTMICRO_FAIL.Alarm_Fault,436327.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm is in fault" WA3260_COMM_WESTMICRO_FAIL.Shelved,436327.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Shelved Status" WA3260_COMM_WESTMICRO_FAIL.Suppressed,436327.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Suppressed Status" WA3260_COMM_WESTMICRO_FAIL.PLCIOFault,436327.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_WESTMICRO_FAIL.PLCF,436327.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3260_COMM_WESTMICRO_FAIL.TAGR,436327.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Tagged Out of Service" WA3252_AFD_0103_1.STRT,436360.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_1.STOP,436360.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_1.INFO,436360.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_1.StrtFault,436360.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_1.StopFault,436360.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_1.REST,436360.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_1.ACKN,436360.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_1.IR,436360.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_1.MN,436360.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_1.MF,436360.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_1.RemoteEnable,436360.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_1.AutoEnable,436360.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_1.HzEnable,436360.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_1.ManDisable,436360.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_1.GlobalReset,436360.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_1.AUTO,436360.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_1.INTK,436361.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_1.TAGR,436361.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_1.AutoStrt,436361.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_1.AutoStop,436361.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_1.RSRT,436361.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_1.RSST,436361.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_1.FailToStrt,436361.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_1.FailToStop,436361.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_1.MotorFailure,436361.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_1.ALRM,436361.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_1.AKED,436361.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_1.ANUN,436361.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_1.Resetable,436361.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_1.FAIL,436361.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_1.MD,436361.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_1.AutoRdy,436361.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_1.PLCFault,436362.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1.PLCIOFault,436362.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_1.Shelved,436362.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_1.Suppressed,436362.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_1.Deviation,436362.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_1.DevFault,436362.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_1.Shelve,436362.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_1.Suppress,436362.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_1.PCSuppress,436362.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_1.PCUnSuppress,436362.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_1.PCUnShelve,436362.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_2.STRT,436496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_2.STOP,436496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_2.INFO,436496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_2.StrtFault,436496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_2.StopFault,436496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_2.REST,436496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_2.ACKN,436496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_2.IR,436496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_2.MN,436496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_2.MF,436496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_2.RemoteEnable,436496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_2.AutoEnable,436496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_2.HzEnable,436496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_2.ManDisable,436496.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_2.GlobalReset,436496.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_2.AUTO,436496.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_2.INTK,436497.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_2.TAGR,436497.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_2.AutoStrt,436497.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_2.AutoStop,436497.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_2.RSRT,436497.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_2.RSST,436497.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_2.FailToStrt,436497.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_2.FailToStop,436497.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_2.MotorFailure,436497.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_2.ALRM,436497.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_2.AKED,436497.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_2.ANUN,436497.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_2.Resetable,436497.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_2.FAIL,436497.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_2.MD,436497.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_2.AutoRdy,436497.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_2.PLCFault,436498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2.PLCIOFault,436498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_2.Shelved,436498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_2.Suppressed,436498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_2.Deviation,436498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_2.DevFault,436498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_2.Shelve,436498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_2.Suppress,436498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_2.PCSuppress,436498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_2.PCUnSuppress,436498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_2.PCUnShelve,436498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_3.STRT,436630.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_3.STOP,436630.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_3.INFO,436630.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_3.StrtFault,436630.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_3.StopFault,436630.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_3.REST,436630.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_3.ACKN,436630.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_3.IR,436630.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_3.MN,436630.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_3.MF,436630.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_3.RemoteEnable,436630.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_3.AutoEnable,436630.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_3.HzEnable,436630.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_3.ManDisable,436630.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_3.GlobalReset,436630.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_3.AUTO,436630.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_3.INTK,436631.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_3.TAGR,436631.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_3.AutoStrt,436631.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_3.AutoStop,436631.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_3.RSRT,436631.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_3.RSST,436631.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_3.FailToStrt,436631.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_3.FailToStop,436631.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_3.MotorFailure,436631.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_3.ALRM,436631.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_3.AKED,436631.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_3.ANUN,436631.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_3.Resetable,436631.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_3.FAIL,436631.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_3.MD,436631.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_3.AutoRdy,436631.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_3.PLCFault,436632.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3.PLCIOFault,436632.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_3.Shelved,436632.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_3.Suppressed,436632.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_3.Deviation,436632.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_3.DevFault,436632.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_3.Shelve,436632.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_3.Suppress,436632.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_3.PCSuppress,436632.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_3.PCUnSuppress,436632.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_3.PCUnShelve,436632.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_4.STRT,436766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_4.STOP,436766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_4.INFO,436766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_4.StrtFault,436766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_4.StopFault,436766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_4.REST,436766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_4.ACKN,436766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_4.IR,436766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_4.MN,436766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_4.MF,436766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_4.RemoteEnable,436766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_4.AutoEnable,436766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_4.HzEnable,436766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_4.ManDisable,436766.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_4.GlobalReset,436766.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_4.AUTO,436766.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_4.INTK,436767.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_4.TAGR,436767.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_4.AutoStrt,436767.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_4.AutoStop,436767.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_4.RSRT,436767.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_4.RSST,436767.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_4.FailToStrt,436767.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_4.FailToStop,436767.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_4.MotorFailure,436767.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_4.ALRM,436767.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_4.AKED,436767.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_4.ANUN,436767.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_4.Resetable,436767.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_4.FAIL,436767.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_4.MD,436767.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_4.AutoRdy,436767.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_4.PLCFault,436768.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4.PLCIOFault,436768.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_4.Shelved,436768.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_4.Suppressed,436768.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_4.Deviation,436768.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_4.DevFault,436768.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_4.Shelve,436768.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_4.Suppress,436768.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_4.PCSuppress,436768.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_4.PCUnSuppress,436768.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_4.PCUnShelve,436768.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_5.STRT,436900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_5.STOP,436900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_5.INFO,436900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_5.StrtFault,436900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_5.StopFault,436900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_5.REST,436900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_5.ACKN,436900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_5.IR,436900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_5.MN,436900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_5.MF,436900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_5.RemoteEnable,436900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_5.AutoEnable,436900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_5.HzEnable,436900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_5.ManDisable,436900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_5.GlobalReset,436900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_5.AUTO,436900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_5.INTK,436901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_5.TAGR,436901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_5.AutoStrt,436901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_5.AutoStop,436901.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_5.RSRT,436901.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_5.RSST,436901.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_5.FailToStrt,436901.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_5.FailToStop,436901.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_5.MotorFailure,436901.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_5.ALRM,436901.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_5.AKED,436901.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_5.ANUN,436901.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_5.Resetable,436901.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_5.FAIL,436901.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_5.MD,436901.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_5.AutoRdy,436901.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_5.PLCFault,436902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5.PLCIOFault,436902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_5.Shelved,436902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_5.Suppressed,436902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_5.Deviation,436902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_5.DevFault,436902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_5.Shelve,436902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_5.Suppress,436902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_5.PCSuppress,436902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_5.PCUnSuppress,436902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_5.PCUnShelve,436902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_6.STRT,437036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_6.STOP,437036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_6.INFO,437036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_6.StrtFault,437036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_6.StopFault,437036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_6.REST,437036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_6.ACKN,437036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_6.IR,437036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_6.MN,437036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_6.MF,437036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_6.RemoteEnable,437036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_6.AutoEnable,437036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_6.HzEnable,437036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_6.ManDisable,437036.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_6.GlobalReset,437036.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_6.AUTO,437036.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_6.INTK,437037.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_6.TAGR,437037.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_6.AutoStrt,437037.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_6.AutoStop,437037.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_6.RSRT,437037.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_6.RSST,437037.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_6.FailToStrt,437037.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_6.FailToStop,437037.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_6.MotorFailure,437037.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_6.ALRM,437037.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_6.AKED,437037.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_6.ANUN,437037.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_6.Resetable,437037.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_6.FAIL,437037.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_6.MD,437037.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_6.AutoRdy,437037.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_6.PLCFault,437038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6.PLCIOFault,437038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_6.Shelved,437038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_6.Suppressed,437038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_6.Deviation,437038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_6.DevFault,437038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_6.Shelve,437038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_6.Suppress,437038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_6.PCSuppress,437038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_6.PCUnSuppress,437038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_6.PCUnShelve,437038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_7.STRT,437170.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_7.STOP,437170.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_7.INFO,437170.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_7.StrtFault,437170.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_7.StopFault,437170.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_7.REST,437170.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_7.ACKN,437170.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_7.IR,437170.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_7.MN,437170.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_7.MF,437170.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_7.RemoteEnable,437170.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_7.AutoEnable,437170.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_7.HzEnable,437170.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_7.ManDisable,437170.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_7.GlobalReset,437170.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_7.AUTO,437170.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_7.INTK,437171.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_7.TAGR,437171.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_7.AutoStrt,437171.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_7.AutoStop,437171.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_7.RSRT,437171.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_7.RSST,437171.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_7.FailToStrt,437171.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_7.FailToStop,437171.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_7.MotorFailure,437171.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_7.ALRM,437171.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_7.AKED,437171.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_7.ANUN,437171.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_7.Resetable,437171.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_7.FAIL,437171.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_7.MD,437171.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_7.AutoRdy,437171.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_7.PLCFault,437172.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7.PLCIOFault,437172.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_7.Shelved,437172.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_7.Suppressed,437172.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_7.Deviation,437172.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_7.DevFault,437172.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_7.Shelve,437172.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_7.Suppress,437172.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_7.PCSuppress,437172.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_7.PCUnSuppress,437172.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_7.PCUnShelve,437172.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_8.STRT,437306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_8.STOP,437306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_8.INFO,437306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_8.StrtFault,437306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_8.StopFault,437306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_8.REST,437306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_8.ACKN,437306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_8.IR,437306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_8.MN,437306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_8.MF,437306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_8.RemoteEnable,437306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_8.AutoEnable,437306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_8.HzEnable,437306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_8.ManDisable,437306.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_8.GlobalReset,437306.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_8.AUTO,437306.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_8.INTK,437307.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_8.TAGR,437307.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_8.AutoStrt,437307.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_8.AutoStop,437307.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_8.RSRT,437307.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_8.RSST,437307.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_8.FailToStrt,437307.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_8.FailToStop,437307.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_8.MotorFailure,437307.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_8.ALRM,437307.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_8.AKED,437307.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_8.ANUN,437307.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_8.Resetable,437307.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_8.FAIL,437307.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_8.MD,437307.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_8.AutoRdy,437307.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_8.PLCFault,437308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8.PLCIOFault,437308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_8.Shelved,437308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_8.Suppressed,437308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_8.Deviation,437308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_8.DevFault,437308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_8.Shelve,437308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_8.Suppress,437308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_8.PCSuppress,437308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_8.PCUnSuppress,437308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_8.PCUnShelve,437308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_AFD_0103_9.STRT,437440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start Command from HMI" WA3252_AFD_0103_9.STOP,437440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop Command from HMI" WA3252_AFD_0103_9.INFO,437440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_AFD_0103_9.StrtFault,437440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Start fault is active, this is not the delayed alarm" WA3252_AFD_0103_9.StopFault,437440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Stop fault is active, this is not the delayed alarm" WA3252_AFD_0103_9.REST,437440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset: Command from HMI to Reset all alarms on this device." WA3252_AFD_0103_9.ACKN,437440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledge Command from Logic to Acknowledge All Alarms in this DFB" WA3252_AFD_0103_9.IR,437440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_AFD_0103_9.MN,437440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Running Status" WA3252_AFD_0103_9.MF,437440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Fail Status from Motor Controller" WA3252_AFD_0103_9.RemoteEnable,437440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 remote/local input wired 0 = not wired" WA3252_AFD_0103_9.AutoEnable,437440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_AFD_0103_9.HzEnable,437440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = VFD using Hz (0-60 Hz) 0 = VFD using Percentages (0-100%)" WA3252_AFD_0103_9.ManDisable,437440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: 1 = Manual Mode Disabled, Always in Auto 0 = Operator may run device in Auto or Manual" WA3252_AFD_0103_9.GlobalReset,437440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Used to reset all alarms in the DFB" WA3252_AFD_0103_9.AUTO,437440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 Device in Auto" WA3252_AFD_0103_9.INTK,437441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_AFD_0103_9.TAGR,437441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_AFD_0103_9.AutoStrt,437441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Start from Auto Logic" WA3252_AFD_0103_9.AutoStop,437441.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Auto Stop from Auto Logic" WA3252_AFD_0103_9.RSRT,437441.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Runtime Command from HMI" WA3252_AFD_0103_9.RSST,437441.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Reset Count of Starts Command from HMI" WA3252_AFD_0103_9.FailToStrt,437441.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Start" WA3252_AFD_0103_9.FailToStop,437441.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Failed to Stop" WA3252_AFD_0103_9.MotorFailure,437441.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Failure Alarm from Motor Drive" WA3252_AFD_0103_9.ALRM,437441.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_AFD_0103_9.AKED,437441.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_AFD_0103_9.ANUN,437441.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_AFD_0103_9.Resetable,437441.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: All Alarms can be reset" WA3252_AFD_0103_9.FAIL,437441.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start, Fail to Stop or Motor Failure alarm is active" WA3252_AFD_0103_9.MD,437441.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device Run Command" WA3252_AFD_0103_9.AutoRdy,437441.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_AFD_0103_9.PLCFault,437442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9.PLCIOFault,437442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_AFD_0103_9.Shelved,437442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Shelved State" WA3252_AFD_0103_9.Suppressed,437442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: General Alarm Suppressed State" WA3252_AFD_0103_9.Deviation,437442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Alarm from Logic" WA3252_AFD_0103_9.DevFault,437442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation fault is active, this is not the delayed alarm" WA3252_AFD_0103_9.Shelve,437442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_AFD_0103_9.Suppress,437442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_AFD_0103_9.PCSuppress,437442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_AFD_0103_9.PCUnSuppress,437442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_AFD_0103_9.PCUnShelve,437442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_1A.RemoteEnable,437576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0102_1A.AutoEnable,437576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0102_1A.FeedbackEnable,437576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0102_1A.IR,437576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0102_1A.ZF,437576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0102_1A.PLCFault,437576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1A.ZH,437576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_1A.ZL,437576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_1A.GlobalReset,437576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A.OVRD,437576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0102_1A.INTK,437576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0102_1A.TAGR,437576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0102_1A.AutoOpen,437576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0102_1A.AutoClose,437576.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0102_1A.ZD,437576.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0102_1A.ZB,437576.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0102_1A.ALRM,437577.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0102_1A.ANUN,437577.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0102_1A.AKED,437577.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0102_1A.Resetable,437577.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_1A.FailToOpen,437577.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0102_1A.FailToClose,437577.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0102_1A.ActuatorFaulted,437577.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0102_1A.AutoRdy,437577.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0102_1A.AUTO,437577.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0102_1A.ACKN,437577.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0102_1A.REST,437577.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0102_1A.CLOS,437577.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0102_1A.OPEN,437577.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0102_1A.RSCT,437577.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0102_1A.CloseFault,437577.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1A.OpenFault,437577.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1A.INFO,437578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0102_1A.STOP,437578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0102_1A.ActuatorFault,437578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1A.PLCIOFault,437578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1A.Shelve,437578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0102_1A.Shelved,437578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0102_1A.Suppress,437578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0102_1A.Suppressed,437578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0102_1A.PCSuppress,437578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_1A.PCUnSuppress,437578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_1A.PCUnShelve,437578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_1A.INTK_EN,437578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0102_1A.ZF_EN,437578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0102_1B.RemoteEnable,437656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0102_1B.AutoEnable,437656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0102_1B.FeedbackEnable,437656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0102_1B.IR,437656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0102_1B.ZF,437656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0102_1B.PLCFault,437656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1B.ZH,437656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_1B.ZL,437656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_1B.GlobalReset,437656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B.OVRD,437656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0102_1B.INTK,437656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0102_1B.TAGR,437656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0102_1B.AutoOpen,437656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0102_1B.AutoClose,437656.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0102_1B.ZD,437656.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0102_1B.ZB,437656.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0102_1B.ALRM,437657.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0102_1B.ANUN,437657.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0102_1B.AKED,437657.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0102_1B.Resetable,437657.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_1B.FailToOpen,437657.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0102_1B.FailToClose,437657.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0102_1B.ActuatorFaulted,437657.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0102_1B.AutoRdy,437657.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0102_1B.AUTO,437657.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0102_1B.ACKN,437657.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0102_1B.REST,437657.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0102_1B.CLOS,437657.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0102_1B.OPEN,437657.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0102_1B.RSCT,437657.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0102_1B.CloseFault,437657.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1B.OpenFault,437657.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1B.INFO,437658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0102_1B.STOP,437658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0102_1B.ActuatorFault,437658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_1B.PLCIOFault,437658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_1B.Shelve,437658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0102_1B.Shelved,437658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0102_1B.Suppress,437658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0102_1B.Suppressed,437658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0102_1B.PCSuppress,437658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_1B.PCUnSuppress,437658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_1B.PCUnShelve,437658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_1B.INTK_EN,437658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0102_1B.ZF_EN,437658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0102_2A.RemoteEnable,437736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0102_2A.AutoEnable,437736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0102_2A.FeedbackEnable,437736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0102_2A.IR,437736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0102_2A.ZF,437736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0102_2A.PLCFault,437736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2A.ZH,437736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_2A.ZL,437736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_2A.GlobalReset,437736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A.OVRD,437736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0102_2A.INTK,437736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0102_2A.TAGR,437736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0102_2A.AutoOpen,437736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0102_2A.AutoClose,437736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0102_2A.ZD,437736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0102_2A.ZB,437736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0102_2A.ALRM,437737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0102_2A.ANUN,437737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0102_2A.AKED,437737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0102_2A.Resetable,437737.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_2A.FailToOpen,437737.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0102_2A.FailToClose,437737.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0102_2A.ActuatorFaulted,437737.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0102_2A.AutoRdy,437737.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0102_2A.AUTO,437737.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0102_2A.ACKN,437737.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0102_2A.REST,437737.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0102_2A.CLOS,437737.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0102_2A.OPEN,437737.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0102_2A.RSCT,437737.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0102_2A.CloseFault,437737.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2A.OpenFault,437737.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2A.INFO,437738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0102_2A.STOP,437738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0102_2A.ActuatorFault,437738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2A.PLCIOFault,437738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2A.Shelve,437738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0102_2A.Shelved,437738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0102_2A.Suppress,437738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0102_2A.Suppressed,437738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0102_2A.PCSuppress,437738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_2A.PCUnSuppress,437738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_2A.PCUnShelve,437738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_2A.INTK_EN,437738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0102_2A.ZF_EN,437738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0102_2B.RemoteEnable,437816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0102_2B.AutoEnable,437816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0102_2B.FeedbackEnable,437816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0102_2B.IR,437816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0102_2B.ZF,437816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0102_2B.PLCFault,437816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2B.ZH,437816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_2B.ZL,437816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0102_2B.GlobalReset,437816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B.OVRD,437816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0102_2B.INTK,437816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0102_2B.TAGR,437816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0102_2B.AutoOpen,437816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0102_2B.AutoClose,437816.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0102_2B.ZD,437816.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0102_2B.ZB,437816.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0102_2B.ALRM,437817.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0102_2B.ANUN,437817.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0102_2B.AKED,437817.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0102_2B.Resetable,437817.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0102_2B.FailToOpen,437817.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0102_2B.FailToClose,437817.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0102_2B.ActuatorFaulted,437817.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0102_2B.AutoRdy,437817.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0102_2B.AUTO,437817.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0102_2B.ACKN,437817.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0102_2B.REST,437817.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0102_2B.CLOS,437817.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0102_2B.OPEN,437817.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0102_2B.RSCT,437817.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0102_2B.CloseFault,437817.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2B.OpenFault,437817.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2B.INFO,437818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0102_2B.STOP,437818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0102_2B.ActuatorFault,437818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0102_2B.PLCIOFault,437818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0102_2B.Shelve,437818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0102_2B.Shelved,437818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0102_2B.Suppress,437818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0102_2B.Suppressed,437818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0102_2B.PCSuppress,437818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0102_2B.PCUnSuppress,437818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0102_2B.PCUnShelve,437818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0102_2B.INTK_EN,437818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0102_2B.ZF_EN,437818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_1A.RemoteEnable,437896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_1A.AutoEnable,437896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_1A.FeedbackEnable,437896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_1A.IR,437896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_1A.ZF,437896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_1A.PLCFault,437896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1A.ZH,437896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_1A.ZL,437896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_1A.GlobalReset,437896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A.OVRD,437896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_1A.INTK,437896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_1A.TAGR,437896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_1A.AutoOpen,437896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_1A.AutoClose,437896.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_1A.ZD,437896.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_1A.ZB,437896.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_1A.ALRM,437897.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_1A.ANUN,437897.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_1A.AKED,437897.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_1A.Resetable,437897.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1A.FailToOpen,437897.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_1A.FailToClose,437897.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_1A.ActuatorFaulted,437897.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_1A.AutoRdy,437897.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_1A.AUTO,437897.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_1A.ACKN,437897.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_1A.REST,437897.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_1A.CLOS,437897.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_1A.OPEN,437897.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_1A.RSCT,437897.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_1A.CloseFault,437897.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1A.OpenFault,437897.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1A.INFO,437898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_1A.STOP,437898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_1A.ActuatorFault,437898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1A.PLCIOFault,437898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1A.Shelve,437898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_1A.Shelved,437898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_1A.Suppress,437898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_1A.Suppressed,437898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_1A.PCSuppress,437898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1A.PCUnSuppress,437898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1A.PCUnShelve,437898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1A.INTK_EN,437898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_1A.ZF_EN,437898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_1C.RemoteEnable,437976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_1C.AutoEnable,437976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_1C.FeedbackEnable,437976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_1C.IR,437976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_1C.ZF,437976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_1C.PLCFault,437976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1C.ZH,437976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_1C.ZL,437976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_1C.GlobalReset,437976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C.OVRD,437976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_1C.INTK,437976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_1C.TAGR,437976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_1C.AutoOpen,437976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_1C.AutoClose,437976.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_1C.ZD,437976.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_1C.ZB,437976.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_1C.ALRM,437977.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_1C.ANUN,437977.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_1C.AKED,437977.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_1C.Resetable,437977.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_1C.FailToOpen,437977.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_1C.FailToClose,437977.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_1C.ActuatorFaulted,437977.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_1C.AutoRdy,437977.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_1C.AUTO,437977.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_1C.ACKN,437977.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_1C.REST,437977.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_1C.CLOS,437977.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_1C.OPEN,437977.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_1C.RSCT,437977.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_1C.CloseFault,437977.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1C.OpenFault,437977.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1C.INFO,437978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_1C.STOP,437978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_1C.ActuatorFault,437978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_1C.PLCIOFault,437978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_1C.Shelve,437978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_1C.Shelved,437978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_1C.Suppress,437978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_1C.Suppressed,437978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_1C.PCSuppress,437978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_1C.PCUnSuppress,437978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_1C.PCUnShelve,437978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_1C.INTK_EN,437978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_1C.ZF_EN,437978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_2A.RemoteEnable,438056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_2A.AutoEnable,438056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_2A.FeedbackEnable,438056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_2A.IR,438056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_2A.ZF,438056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_2A.PLCFault,438056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2A.ZH,438056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_2A.ZL,438056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_2A.GlobalReset,438056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A.OVRD,438056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_2A.INTK,438056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_2A.TAGR,438056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_2A.AutoOpen,438056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_2A.AutoClose,438056.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_2A.ZD,438056.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_2A.ZB,438056.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_2A.ALRM,438057.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_2A.ANUN,438057.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_2A.AKED,438057.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_2A.Resetable,438057.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2A.FailToOpen,438057.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_2A.FailToClose,438057.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_2A.ActuatorFaulted,438057.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_2A.AutoRdy,438057.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_2A.AUTO,438057.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_2A.ACKN,438057.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_2A.REST,438057.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_2A.CLOS,438057.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_2A.OPEN,438057.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_2A.RSCT,438057.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_2A.CloseFault,438057.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2A.OpenFault,438057.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2A.INFO,438058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_2A.STOP,438058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_2A.ActuatorFault,438058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2A.PLCIOFault,438058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2A.Shelve,438058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_2A.Shelved,438058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_2A.Suppress,438058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_2A.Suppressed,438058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_2A.PCSuppress,438058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2A.PCUnSuppress,438058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2A.PCUnShelve,438058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2A.INTK_EN,438058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_2A.ZF_EN,438058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_2C.RemoteEnable,438136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_2C.AutoEnable,438136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_2C.FeedbackEnable,438136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_2C.IR,438136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_2C.ZF,438136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_2C.PLCFault,438136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2C.ZH,438136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_2C.ZL,438136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_2C.GlobalReset,438136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C.OVRD,438136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_2C.INTK,438136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_2C.TAGR,438136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_2C.AutoOpen,438136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_2C.AutoClose,438136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_2C.ZD,438136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_2C.ZB,438136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_2C.ALRM,438137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_2C.ANUN,438137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_2C.AKED,438137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_2C.Resetable,438137.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_2C.FailToOpen,438137.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_2C.FailToClose,438137.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_2C.ActuatorFaulted,438137.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_2C.AutoRdy,438137.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_2C.AUTO,438137.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_2C.ACKN,438137.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_2C.REST,438137.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_2C.CLOS,438137.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_2C.OPEN,438137.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_2C.RSCT,438137.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_2C.CloseFault,438137.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2C.OpenFault,438137.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2C.INFO,438138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_2C.STOP,438138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_2C.ActuatorFault,438138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_2C.PLCIOFault,438138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_2C.Shelve,438138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_2C.Shelved,438138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_2C.Suppress,438138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_2C.Suppressed,438138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_2C.PCSuppress,438138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_2C.PCUnSuppress,438138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_2C.PCUnShelve,438138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_2C.INTK_EN,438138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_2C.ZF_EN,438138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_3A.RemoteEnable,438216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_3A.AutoEnable,438216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_3A.FeedbackEnable,438216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_3A.IR,438216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_3A.ZF,438216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_3A.PLCFault,438216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3A.ZH,438216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3A.ZL,438216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3A.GlobalReset,438216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A.OVRD,438216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_3A.INTK,438216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_3A.TAGR,438216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_3A.AutoOpen,438216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_3A.AutoClose,438216.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_3A.ZD,438216.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_3A.ZB,438216.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_3A.ALRM,438217.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_3A.ANUN,438217.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_3A.AKED,438217.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_3A.Resetable,438217.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3A.FailToOpen,438217.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_3A.FailToClose,438217.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_3A.ActuatorFaulted,438217.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_3A.AutoRdy,438217.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_3A.AUTO,438217.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_3A.ACKN,438217.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_3A.REST,438217.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_3A.CLOS,438217.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_3A.OPEN,438217.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_3A.RSCT,438217.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_3A.CloseFault,438217.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3A.OpenFault,438217.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3A.INFO,438218.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_3A.STOP,438218.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_3A.ActuatorFault,438218.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3A.PLCIOFault,438218.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3A.Shelve,438218.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_3A.Shelved,438218.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_3A.Suppress,438218.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_3A.Suppressed,438218.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_3A.PCSuppress,438218.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3A.PCUnSuppress,438218.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3A.PCUnShelve,438218.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3A.INTK_EN,438218.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_3A.ZF_EN,438218.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_3C.RemoteEnable,438296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_3C.AutoEnable,438296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_3C.FeedbackEnable,438296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_3C.IR,438296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_3C.ZF,438296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_3C.PLCFault,438296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3C.ZH,438296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3C.ZL,438296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3C.GlobalReset,438296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C.OVRD,438296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_3C.INTK,438296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_3C.TAGR,438296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_3C.AutoOpen,438296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_3C.AutoClose,438296.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_3C.ZD,438296.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_3C.ZB,438296.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_3C.ALRM,438297.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_3C.ANUN,438297.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_3C.AKED,438297.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_3C.Resetable,438297.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3C.FailToOpen,438297.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_3C.FailToClose,438297.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_3C.ActuatorFaulted,438297.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_3C.AutoRdy,438297.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_3C.AUTO,438297.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_3C.ACKN,438297.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_3C.REST,438297.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_3C.CLOS,438297.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_3C.OPEN,438297.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_3C.RSCT,438297.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_3C.CloseFault,438297.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3C.OpenFault,438297.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3C.INFO,438298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_3C.STOP,438298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_3C.ActuatorFault,438298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3C.PLCIOFault,438298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3C.Shelve,438298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_3C.Shelved,438298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_3C.Suppress,438298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_3C.Suppressed,438298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_3C.PCSuppress,438298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3C.PCUnSuppress,438298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3C.PCUnShelve,438298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3C.INTK_EN,438298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_3C.ZF_EN,438298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_3D.RemoteEnable,438376.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_3D.AutoEnable,438376.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_3D.FeedbackEnable,438376.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_3D.IR,438376.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_3D.ZF,438376.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_3D.PLCFault,438376.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3D.ZH,438376.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3D.ZL,438376.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_3D.GlobalReset,438376.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D.OVRD,438376.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_3D.INTK,438376.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_3D.TAGR,438376.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_3D.AutoOpen,438376.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_3D.AutoClose,438376.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_3D.ZD,438376.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_3D.ZB,438376.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_3D.ALRM,438377.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_3D.ANUN,438377.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_3D.AKED,438377.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_3D.Resetable,438377.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_3D.FailToOpen,438377.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_3D.FailToClose,438377.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_3D.ActuatorFaulted,438377.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_3D.AutoRdy,438377.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_3D.AUTO,438377.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_3D.ACKN,438377.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_3D.REST,438377.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_3D.CLOS,438377.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_3D.OPEN,438377.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_3D.RSCT,438377.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_3D.CloseFault,438377.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3D.OpenFault,438377.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3D.INFO,438378.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_3D.STOP,438378.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_3D.ActuatorFault,438378.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_3D.PLCIOFault,438378.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_3D.Shelve,438378.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_3D.Shelved,438378.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_3D.Suppress,438378.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_3D.Suppressed,438378.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_3D.PCSuppress,438378.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_3D.PCUnSuppress,438378.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_3D.PCUnShelve,438378.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_3D.INTK_EN,438378.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_3D.ZF_EN,438378.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_4A.RemoteEnable,438456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_4A.AutoEnable,438456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_4A.FeedbackEnable,438456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_4A.IR,438456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_4A.ZF,438456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_4A.PLCFault,438456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4A.ZH,438456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4A.ZL,438456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4A.GlobalReset,438456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A.OVRD,438456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_4A.INTK,438456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_4A.TAGR,438456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_4A.AutoOpen,438456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_4A.AutoClose,438456.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_4A.ZD,438456.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_4A.ZB,438456.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_4A.ALRM,438457.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_4A.ANUN,438457.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_4A.AKED,438457.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_4A.Resetable,438457.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4A.FailToOpen,438457.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_4A.FailToClose,438457.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_4A.ActuatorFaulted,438457.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_4A.AutoRdy,438457.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_4A.AUTO,438457.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_4A.ACKN,438457.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_4A.REST,438457.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_4A.CLOS,438457.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_4A.OPEN,438457.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_4A.RSCT,438457.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_4A.CloseFault,438457.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4A.OpenFault,438457.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4A.INFO,438458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_4A.STOP,438458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_4A.ActuatorFault,438458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4A.PLCIOFault,438458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4A.Shelve,438458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_4A.Shelved,438458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_4A.Suppress,438458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_4A.Suppressed,438458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_4A.PCSuppress,438458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4A.PCUnSuppress,438458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4A.PCUnShelve,438458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4A.INTK_EN,438458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_4A.ZF_EN,438458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_4C.RemoteEnable,438536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_4C.AutoEnable,438536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_4C.FeedbackEnable,438536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_4C.IR,438536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_4C.ZF,438536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_4C.PLCFault,438536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4C.ZH,438536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4C.ZL,438536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4C.GlobalReset,438536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C.OVRD,438536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_4C.INTK,438536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_4C.TAGR,438536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_4C.AutoOpen,438536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_4C.AutoClose,438536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_4C.ZD,438536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_4C.ZB,438536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_4C.ALRM,438537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_4C.ANUN,438537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_4C.AKED,438537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_4C.Resetable,438537.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4C.FailToOpen,438537.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_4C.FailToClose,438537.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_4C.ActuatorFaulted,438537.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_4C.AutoRdy,438537.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_4C.AUTO,438537.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_4C.ACKN,438537.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_4C.REST,438537.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_4C.CLOS,438537.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_4C.OPEN,438537.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_4C.RSCT,438537.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_4C.CloseFault,438537.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4C.OpenFault,438537.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4C.INFO,438538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_4C.STOP,438538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_4C.ActuatorFault,438538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4C.PLCIOFault,438538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4C.Shelve,438538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_4C.Shelved,438538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_4C.Suppress,438538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_4C.Suppressed,438538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_4C.PCSuppress,438538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4C.PCUnSuppress,438538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4C.PCUnShelve,438538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4C.INTK_EN,438538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_4C.ZF_EN,438538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_4D.RemoteEnable,438616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_4D.AutoEnable,438616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_4D.FeedbackEnable,438616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_4D.IR,438616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_4D.ZF,438616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_4D.PLCFault,438616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4D.ZH,438616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4D.ZL,438616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_4D.GlobalReset,438616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D.OVRD,438616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_4D.INTK,438616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_4D.TAGR,438616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_4D.AutoOpen,438616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_4D.AutoClose,438616.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_4D.ZD,438616.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_4D.ZB,438616.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_4D.ALRM,438617.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_4D.ANUN,438617.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_4D.AKED,438617.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_4D.Resetable,438617.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_4D.FailToOpen,438617.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_4D.FailToClose,438617.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_4D.ActuatorFaulted,438617.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_4D.AutoRdy,438617.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_4D.AUTO,438617.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_4D.ACKN,438617.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_4D.REST,438617.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_4D.CLOS,438617.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_4D.OPEN,438617.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_4D.RSCT,438617.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_4D.CloseFault,438617.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4D.OpenFault,438617.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4D.INFO,438618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_4D.STOP,438618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_4D.ActuatorFault,438618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_4D.PLCIOFault,438618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_4D.Shelve,438618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_4D.Shelved,438618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_4D.Suppress,438618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_4D.Suppressed,438618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_4D.PCSuppress,438618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_4D.PCUnSuppress,438618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_4D.PCUnShelve,438618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_4D.INTK_EN,438618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_4D.ZF_EN,438618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_5A.RemoteEnable,438696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_5A.AutoEnable,438696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_5A.FeedbackEnable,438696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_5A.IR,438696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_5A.ZF,438696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_5A.PLCFault,438696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5A.ZH,438696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5A.ZL,438696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5A.GlobalReset,438696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A.OVRD,438696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_5A.INTK,438696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_5A.TAGR,438696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_5A.AutoOpen,438696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_5A.AutoClose,438696.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_5A.ZD,438696.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_5A.ZB,438696.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_5A.ALRM,438697.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_5A.ANUN,438697.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_5A.AKED,438697.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_5A.Resetable,438697.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5A.FailToOpen,438697.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_5A.FailToClose,438697.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_5A.ActuatorFaulted,438697.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_5A.AutoRdy,438697.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_5A.AUTO,438697.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_5A.ACKN,438697.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_5A.REST,438697.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_5A.CLOS,438697.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_5A.OPEN,438697.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_5A.RSCT,438697.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_5A.CloseFault,438697.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5A.OpenFault,438697.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5A.INFO,438698.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_5A.STOP,438698.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_5A.ActuatorFault,438698.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5A.PLCIOFault,438698.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5A.Shelve,438698.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_5A.Shelved,438698.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_5A.Suppress,438698.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_5A.Suppressed,438698.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_5A.PCSuppress,438698.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5A.PCUnSuppress,438698.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5A.PCUnShelve,438698.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5A.INTK_EN,438698.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_5A.ZF_EN,438698.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_5C.RemoteEnable,438776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_5C.AutoEnable,438776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_5C.FeedbackEnable,438776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_5C.IR,438776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_5C.ZF,438776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_5C.PLCFault,438776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5C.ZH,438776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5C.ZL,438776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5C.GlobalReset,438776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C.OVRD,438776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_5C.INTK,438776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_5C.TAGR,438776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_5C.AutoOpen,438776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_5C.AutoClose,438776.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_5C.ZD,438776.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_5C.ZB,438776.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_5C.ALRM,438777.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_5C.ANUN,438777.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_5C.AKED,438777.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_5C.Resetable,438777.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5C.FailToOpen,438777.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_5C.FailToClose,438777.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_5C.ActuatorFaulted,438777.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_5C.AutoRdy,438777.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_5C.AUTO,438777.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_5C.ACKN,438777.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_5C.REST,438777.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_5C.CLOS,438777.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_5C.OPEN,438777.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_5C.RSCT,438777.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_5C.CloseFault,438777.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5C.OpenFault,438777.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5C.INFO,438778.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_5C.STOP,438778.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_5C.ActuatorFault,438778.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5C.PLCIOFault,438778.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5C.Shelve,438778.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_5C.Shelved,438778.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_5C.Suppress,438778.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_5C.Suppressed,438778.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_5C.PCSuppress,438778.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5C.PCUnSuppress,438778.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5C.PCUnShelve,438778.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5C.INTK_EN,438778.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_5C.ZF_EN,438778.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_5D.RemoteEnable,438856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_5D.AutoEnable,438856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_5D.FeedbackEnable,438856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_5D.IR,438856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_5D.ZF,438856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_5D.PLCFault,438856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5D.ZH,438856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5D.ZL,438856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_5D.GlobalReset,438856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D.OVRD,438856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_5D.INTK,438856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_5D.TAGR,438856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_5D.AutoOpen,438856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_5D.AutoClose,438856.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_5D.ZD,438856.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_5D.ZB,438856.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_5D.ALRM,438857.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_5D.ANUN,438857.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_5D.AKED,438857.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_5D.Resetable,438857.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_5D.FailToOpen,438857.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_5D.FailToClose,438857.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_5D.ActuatorFaulted,438857.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_5D.AutoRdy,438857.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_5D.AUTO,438857.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_5D.ACKN,438857.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_5D.REST,438857.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_5D.CLOS,438857.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_5D.OPEN,438857.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_5D.RSCT,438857.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_5D.CloseFault,438857.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5D.OpenFault,438857.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5D.INFO,438858.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_5D.STOP,438858.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_5D.ActuatorFault,438858.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_5D.PLCIOFault,438858.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_5D.Shelve,438858.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_5D.Shelved,438858.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_5D.Suppress,438858.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_5D.Suppressed,438858.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_5D.PCSuppress,438858.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_5D.PCUnSuppress,438858.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_5D.PCUnShelve,438858.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_5D.INTK_EN,438858.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_5D.ZF_EN,438858.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_6A.RemoteEnable,438936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_6A.AutoEnable,438936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_6A.FeedbackEnable,438936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_6A.IR,438936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_6A.ZF,438936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_6A.PLCFault,438936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6A.ZH,438936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6A.ZL,438936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6A.GlobalReset,438936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A.OVRD,438936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_6A.INTK,438936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_6A.TAGR,438936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_6A.AutoOpen,438936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_6A.AutoClose,438936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_6A.ZD,438936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_6A.ZB,438936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_6A.ALRM,438937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_6A.ANUN,438937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_6A.AKED,438937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_6A.Resetable,438937.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6A.FailToOpen,438937.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_6A.FailToClose,438937.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_6A.ActuatorFaulted,438937.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_6A.AutoRdy,438937.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_6A.AUTO,438937.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_6A.ACKN,438937.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_6A.REST,438937.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_6A.CLOS,438937.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_6A.OPEN,438937.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_6A.RSCT,438937.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_6A.CloseFault,438937.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6A.OpenFault,438937.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6A.INFO,438938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_6A.STOP,438938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_6A.ActuatorFault,438938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6A.PLCIOFault,438938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6A.Shelve,438938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_6A.Shelved,438938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_6A.Suppress,438938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_6A.Suppressed,438938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_6A.PCSuppress,438938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6A.PCUnSuppress,438938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6A.PCUnShelve,438938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6A.INTK_EN,438938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_6A.ZF_EN,438938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_6C.RemoteEnable,439016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_6C.AutoEnable,439016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_6C.FeedbackEnable,439016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_6C.IR,439016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_6C.ZF,439016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_6C.PLCFault,439016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6C.ZH,439016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6C.ZL,439016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6C.GlobalReset,439016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C.OVRD,439016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_6C.INTK,439016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_6C.TAGR,439016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_6C.AutoOpen,439016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_6C.AutoClose,439016.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_6C.ZD,439016.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_6C.ZB,439016.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_6C.ALRM,439017.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_6C.ANUN,439017.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_6C.AKED,439017.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_6C.Resetable,439017.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6C.FailToOpen,439017.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_6C.FailToClose,439017.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_6C.ActuatorFaulted,439017.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_6C.AutoRdy,439017.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_6C.AUTO,439017.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_6C.ACKN,439017.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_6C.REST,439017.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_6C.CLOS,439017.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_6C.OPEN,439017.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_6C.RSCT,439017.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_6C.CloseFault,439017.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6C.OpenFault,439017.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6C.INFO,439018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_6C.STOP,439018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_6C.ActuatorFault,439018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6C.PLCIOFault,439018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6C.Shelve,439018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_6C.Shelved,439018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_6C.Suppress,439018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_6C.Suppressed,439018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_6C.PCSuppress,439018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6C.PCUnSuppress,439018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6C.PCUnShelve,439018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6C.INTK_EN,439018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_6C.ZF_EN,439018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_6D.RemoteEnable,439096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_6D.AutoEnable,439096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_6D.FeedbackEnable,439096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_6D.IR,439096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_6D.ZF,439096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_6D.PLCFault,439096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6D.ZH,439096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6D.ZL,439096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_6D.GlobalReset,439096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D.OVRD,439096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_6D.INTK,439096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_6D.TAGR,439096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_6D.AutoOpen,439096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_6D.AutoClose,439096.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_6D.ZD,439096.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_6D.ZB,439096.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_6D.ALRM,439097.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_6D.ANUN,439097.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_6D.AKED,439097.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_6D.Resetable,439097.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_6D.FailToOpen,439097.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_6D.FailToClose,439097.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_6D.ActuatorFaulted,439097.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_6D.AutoRdy,439097.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_6D.AUTO,439097.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_6D.ACKN,439097.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_6D.REST,439097.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_6D.CLOS,439097.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_6D.OPEN,439097.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_6D.RSCT,439097.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_6D.CloseFault,439097.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6D.OpenFault,439097.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6D.INFO,439098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_6D.STOP,439098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_6D.ActuatorFault,439098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_6D.PLCIOFault,439098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_6D.Shelve,439098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_6D.Shelved,439098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_6D.Suppress,439098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_6D.Suppressed,439098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_6D.PCSuppress,439098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_6D.PCUnSuppress,439098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_6D.PCUnShelve,439098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_6D.INTK_EN,439098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_6D.ZF_EN,439098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_7A.RemoteEnable,439176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_7A.AutoEnable,439176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_7A.FeedbackEnable,439176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_7A.IR,439176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_7A.ZF,439176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_7A.PLCFault,439176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7A.ZH,439176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7A.ZL,439176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7A.GlobalReset,439176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A.OVRD,439176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_7A.INTK,439176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_7A.TAGR,439176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_7A.AutoOpen,439176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_7A.AutoClose,439176.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_7A.ZD,439176.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_7A.ZB,439176.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_7A.ALRM,439177.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_7A.ANUN,439177.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_7A.AKED,439177.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_7A.Resetable,439177.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7A.FailToOpen,439177.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_7A.FailToClose,439177.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_7A.ActuatorFaulted,439177.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_7A.AutoRdy,439177.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_7A.AUTO,439177.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_7A.ACKN,439177.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_7A.REST,439177.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_7A.CLOS,439177.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_7A.OPEN,439177.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_7A.RSCT,439177.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_7A.CloseFault,439177.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7A.OpenFault,439177.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7A.INFO,439178.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_7A.STOP,439178.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_7A.ActuatorFault,439178.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7A.PLCIOFault,439178.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7A.Shelve,439178.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_7A.Shelved,439178.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_7A.Suppress,439178.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_7A.Suppressed,439178.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_7A.PCSuppress,439178.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7A.PCUnSuppress,439178.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7A.PCUnShelve,439178.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7A.INTK_EN,439178.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_7A.ZF_EN,439178.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_7C.RemoteEnable,439256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_7C.AutoEnable,439256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_7C.FeedbackEnable,439256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_7C.IR,439256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_7C.ZF,439256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_7C.PLCFault,439256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7C.ZH,439256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7C.ZL,439256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7C.GlobalReset,439256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C.OVRD,439256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_7C.INTK,439256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_7C.TAGR,439256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_7C.AutoOpen,439256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_7C.AutoClose,439256.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_7C.ZD,439256.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_7C.ZB,439256.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_7C.ALRM,439257.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_7C.ANUN,439257.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_7C.AKED,439257.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_7C.Resetable,439257.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7C.FailToOpen,439257.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_7C.FailToClose,439257.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_7C.ActuatorFaulted,439257.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_7C.AutoRdy,439257.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_7C.AUTO,439257.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_7C.ACKN,439257.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_7C.REST,439257.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_7C.CLOS,439257.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_7C.OPEN,439257.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_7C.RSCT,439257.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_7C.CloseFault,439257.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7C.OpenFault,439257.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7C.INFO,439258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_7C.STOP,439258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_7C.ActuatorFault,439258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7C.PLCIOFault,439258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7C.Shelve,439258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_7C.Shelved,439258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_7C.Suppress,439258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_7C.Suppressed,439258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_7C.PCSuppress,439258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7C.PCUnSuppress,439258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7C.PCUnShelve,439258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7C.INTK_EN,439258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_7C.ZF_EN,439258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_7D.RemoteEnable,439336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_7D.AutoEnable,439336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_7D.FeedbackEnable,439336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_7D.IR,439336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_7D.ZF,439336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_7D.PLCFault,439336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7D.ZH,439336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7D.ZL,439336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_7D.GlobalReset,439336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D.OVRD,439336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_7D.INTK,439336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_7D.TAGR,439336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_7D.AutoOpen,439336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_7D.AutoClose,439336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_7D.ZD,439336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_7D.ZB,439336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_7D.ALRM,439337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_7D.ANUN,439337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_7D.AKED,439337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_7D.Resetable,439337.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_7D.FailToOpen,439337.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_7D.FailToClose,439337.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_7D.ActuatorFaulted,439337.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_7D.AutoRdy,439337.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_7D.AUTO,439337.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_7D.ACKN,439337.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_7D.REST,439337.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_7D.CLOS,439337.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_7D.OPEN,439337.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_7D.RSCT,439337.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_7D.CloseFault,439337.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7D.OpenFault,439337.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7D.INFO,439338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_7D.STOP,439338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_7D.ActuatorFault,439338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_7D.PLCIOFault,439338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_7D.Shelve,439338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_7D.Shelved,439338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_7D.Suppress,439338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_7D.Suppressed,439338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_7D.PCSuppress,439338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_7D.PCUnSuppress,439338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_7D.PCUnShelve,439338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_7D.INTK_EN,439338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_7D.ZF_EN,439338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_8A.RemoteEnable,439416.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_8A.AutoEnable,439416.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_8A.FeedbackEnable,439416.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_8A.IR,439416.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_8A.ZF,439416.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_8A.PLCFault,439416.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8A.ZH,439416.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8A.ZL,439416.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8A.GlobalReset,439416.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A.OVRD,439416.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_8A.INTK,439416.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_8A.TAGR,439416.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_8A.AutoOpen,439416.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_8A.AutoClose,439416.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_8A.ZD,439416.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_8A.ZB,439416.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_8A.ALRM,439417.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_8A.ANUN,439417.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_8A.AKED,439417.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_8A.Resetable,439417.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8A.FailToOpen,439417.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_8A.FailToClose,439417.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_8A.ActuatorFaulted,439417.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_8A.AutoRdy,439417.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_8A.AUTO,439417.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_8A.ACKN,439417.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_8A.REST,439417.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_8A.CLOS,439417.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_8A.OPEN,439417.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_8A.RSCT,439417.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_8A.CloseFault,439417.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8A.OpenFault,439417.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8A.INFO,439418.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_8A.STOP,439418.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_8A.ActuatorFault,439418.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8A.PLCIOFault,439418.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8A.Shelve,439418.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_8A.Shelved,439418.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_8A.Suppress,439418.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_8A.Suppressed,439418.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_8A.PCSuppress,439418.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8A.PCUnSuppress,439418.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8A.PCUnShelve,439418.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8A.INTK_EN,439418.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_8A.ZF_EN,439418.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_8C.RemoteEnable,439496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_8C.AutoEnable,439496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_8C.FeedbackEnable,439496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_8C.IR,439496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_8C.ZF,439496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_8C.PLCFault,439496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8C.ZH,439496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8C.ZL,439496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8C.GlobalReset,439496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C.OVRD,439496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_8C.INTK,439496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_8C.TAGR,439496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_8C.AutoOpen,439496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_8C.AutoClose,439496.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_8C.ZD,439496.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_8C.ZB,439496.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_8C.ALRM,439497.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_8C.ANUN,439497.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_8C.AKED,439497.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_8C.Resetable,439497.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8C.FailToOpen,439497.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_8C.FailToClose,439497.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_8C.ActuatorFaulted,439497.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_8C.AutoRdy,439497.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_8C.AUTO,439497.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_8C.ACKN,439497.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_8C.REST,439497.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_8C.CLOS,439497.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_8C.OPEN,439497.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_8C.RSCT,439497.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_8C.CloseFault,439497.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8C.OpenFault,439497.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8C.INFO,439498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_8C.STOP,439498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_8C.ActuatorFault,439498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8C.PLCIOFault,439498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8C.Shelve,439498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_8C.Shelved,439498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_8C.Suppress,439498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_8C.Suppressed,439498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_8C.PCSuppress,439498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8C.PCUnSuppress,439498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8C.PCUnShelve,439498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8C.INTK_EN,439498.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_8C.ZF_EN,439498.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_8D.RemoteEnable,439576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_8D.AutoEnable,439576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_8D.FeedbackEnable,439576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_8D.IR,439576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_8D.ZF,439576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_8D.PLCFault,439576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8D.ZH,439576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8D.ZL,439576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_8D.GlobalReset,439576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D.OVRD,439576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_8D.INTK,439576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_8D.TAGR,439576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_8D.AutoOpen,439576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_8D.AutoClose,439576.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_8D.ZD,439576.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_8D.ZB,439576.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_8D.ALRM,439577.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_8D.ANUN,439577.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_8D.AKED,439577.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_8D.Resetable,439577.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_8D.FailToOpen,439577.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_8D.FailToClose,439577.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_8D.ActuatorFaulted,439577.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_8D.AutoRdy,439577.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_8D.AUTO,439577.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_8D.ACKN,439577.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_8D.REST,439577.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_8D.CLOS,439577.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_8D.OPEN,439577.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_8D.RSCT,439577.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_8D.CloseFault,439577.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8D.OpenFault,439577.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8D.INFO,439578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_8D.STOP,439578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_8D.ActuatorFault,439578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_8D.PLCIOFault,439578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_8D.Shelve,439578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_8D.Shelved,439578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_8D.Suppress,439578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_8D.Suppressed,439578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_8D.PCSuppress,439578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_8D.PCUnSuppress,439578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_8D.PCUnShelve,439578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_8D.INTK_EN,439578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_8D.ZF_EN,439578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_9A.RemoteEnable,439656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_9A.AutoEnable,439656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_9A.FeedbackEnable,439656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_9A.IR,439656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_9A.ZF,439656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_9A.PLCFault,439656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9A.ZH,439656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_9A.ZL,439656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_9A.GlobalReset,439656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A.OVRD,439656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_9A.INTK,439656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_9A.TAGR,439656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_9A.AutoOpen,439656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_9A.AutoClose,439656.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_9A.ZD,439656.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_9A.ZB,439656.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_9A.ALRM,439657.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_9A.ANUN,439657.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_9A.AKED,439657.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_9A.Resetable,439657.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9A.FailToOpen,439657.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_9A.FailToClose,439657.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_9A.ActuatorFaulted,439657.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_9A.AutoRdy,439657.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_9A.AUTO,439657.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_9A.ACKN,439657.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_9A.REST,439657.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_9A.CLOS,439657.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_9A.OPEN,439657.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_9A.RSCT,439657.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_9A.CloseFault,439657.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9A.OpenFault,439657.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9A.INFO,439658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_9A.STOP,439658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_9A.ActuatorFault,439658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9A.PLCIOFault,439658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9A.Shelve,439658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_9A.Shelved,439658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_9A.Suppress,439658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_9A.Suppressed,439658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_9A.PCSuppress,439658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9A.PCUnSuppress,439658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9A.PCUnShelve,439658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9A.INTK_EN,439658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_9A.ZF_EN,439658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0103_9C.RemoteEnable,439736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0103_9C.AutoEnable,439736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0103_9C.FeedbackEnable,439736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0103_9C.IR,439736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0103_9C.ZF,439736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0103_9C.PLCFault,439736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9C.ZH,439736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_9C.ZL,439736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0103_9C.GlobalReset,439736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C.OVRD,439736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0103_9C.INTK,439736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0103_9C.TAGR,439736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0103_9C.AutoOpen,439736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0103_9C.AutoClose,439736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0103_9C.ZD,439736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0103_9C.ZB,439736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0103_9C.ALRM,439737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0103_9C.ANUN,439737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0103_9C.AKED,439737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0103_9C.Resetable,439737.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0103_9C.FailToOpen,439737.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0103_9C.FailToClose,439737.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0103_9C.ActuatorFaulted,439737.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0103_9C.AutoRdy,439737.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0103_9C.AUTO,439737.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0103_9C.ACKN,439737.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0103_9C.REST,439737.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0103_9C.CLOS,439737.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0103_9C.OPEN,439737.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0103_9C.RSCT,439737.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0103_9C.CloseFault,439737.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9C.OpenFault,439737.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9C.INFO,439738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0103_9C.STOP,439738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0103_9C.ActuatorFault,439738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0103_9C.PLCIOFault,439738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0103_9C.Shelve,439738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0103_9C.Shelved,439738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0103_9C.Suppress,439738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0103_9C.Suppressed,439738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0103_9C.PCSuppress,439738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0103_9C.PCUnSuppress,439738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0103_9C.PCUnShelve,439738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0103_9C.INTK_EN,439738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0103_9C.ZF_EN,439738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0113_2A.RemoteEnable,439816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0113_2A.AutoEnable,439816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0113_2A.FeedbackEnable,439816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0113_2A.IR,439816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0113_2A.ZF,439816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0113_2A.PLCFault,439816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2A.ZH,439816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2A.ZL,439816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2A.GlobalReset,439816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A.OVRD,439816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0113_2A.INTK,439816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0113_2A.TAGR,439816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0113_2A.AutoOpen,439816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0113_2A.AutoClose,439816.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0113_2A.ZD,439816.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0113_2A.ZB,439816.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0113_2A.ALRM,439817.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0113_2A.ANUN,439817.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0113_2A.AKED,439817.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0113_2A.Resetable,439817.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2A.FailToOpen,439817.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0113_2A.FailToClose,439817.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0113_2A.ActuatorFaulted,439817.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0113_2A.AutoRdy,439817.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0113_2A.AUTO,439817.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0113_2A.ACKN,439817.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0113_2A.REST,439817.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0113_2A.CLOS,439817.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0113_2A.OPEN,439817.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0113_2A.RSCT,439817.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0113_2A.CloseFault,439817.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2A.OpenFault,439817.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2A.INFO,439818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0113_2A.STOP,439818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0113_2A.ActuatorFault,439818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2A.PLCIOFault,439818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2A.Shelve,439818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0113_2A.Shelved,439818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0113_2A.Suppress,439818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0113_2A.Suppressed,439818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0113_2A.PCSuppress,439818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2A.PCUnSuppress,439818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2A.PCUnShelve,439818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2A.INTK_EN,439818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0113_2A.ZF_EN,439818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0113_2B.RemoteEnable,439896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0113_2B.AutoEnable,439896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0113_2B.FeedbackEnable,439896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0113_2B.IR,439896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0113_2B.ZF,439896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0113_2B.PLCFault,439896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2B.ZH,439896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2B.ZL,439896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2B.GlobalReset,439896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B.OVRD,439896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0113_2B.INTK,439896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0113_2B.TAGR,439896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0113_2B.AutoOpen,439896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0113_2B.AutoClose,439896.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0113_2B.ZD,439896.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0113_2B.ZB,439896.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0113_2B.ALRM,439897.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0113_2B.ANUN,439897.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0113_2B.AKED,439897.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0113_2B.Resetable,439897.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2B.FailToOpen,439897.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0113_2B.FailToClose,439897.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0113_2B.ActuatorFaulted,439897.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0113_2B.AutoRdy,439897.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0113_2B.AUTO,439897.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0113_2B.ACKN,439897.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0113_2B.REST,439897.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0113_2B.CLOS,439897.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0113_2B.OPEN,439897.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0113_2B.RSCT,439897.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0113_2B.CloseFault,439897.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2B.OpenFault,439897.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2B.INFO,439898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0113_2B.STOP,439898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0113_2B.ActuatorFault,439898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2B.PLCIOFault,439898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2B.Shelve,439898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0113_2B.Shelved,439898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0113_2B.Suppress,439898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0113_2B.Suppressed,439898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0113_2B.PCSuppress,439898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2B.PCUnSuppress,439898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2B.PCUnShelve,439898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2B.INTK_EN,439898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0113_2B.ZF_EN,439898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0113_2C.RemoteEnable,439976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0113_2C.AutoEnable,439976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0113_2C.FeedbackEnable,439976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0113_2C.IR,439976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0113_2C.ZF,439976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0113_2C.PLCFault,439976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2C.ZH,439976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2C.ZL,439976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2C.GlobalReset,439976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C.OVRD,439976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0113_2C.INTK,439976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0113_2C.TAGR,439976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0113_2C.AutoOpen,439976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0113_2C.AutoClose,439976.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0113_2C.ZD,439976.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0113_2C.ZB,439976.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0113_2C.ALRM,439977.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0113_2C.ANUN,439977.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0113_2C.AKED,439977.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0113_2C.Resetable,439977.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2C.FailToOpen,439977.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0113_2C.FailToClose,439977.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0113_2C.ActuatorFaulted,439977.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0113_2C.AutoRdy,439977.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0113_2C.AUTO,439977.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0113_2C.ACKN,439977.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0113_2C.REST,439977.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0113_2C.CLOS,439977.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0113_2C.OPEN,439977.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0113_2C.RSCT,439977.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0113_2C.CloseFault,439977.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2C.OpenFault,439977.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2C.INFO,439978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0113_2C.STOP,439978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0113_2C.ActuatorFault,439978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2C.PLCIOFault,439978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2C.Shelve,439978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0113_2C.Shelved,439978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0113_2C.Suppress,439978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0113_2C.Suppressed,439978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0113_2C.PCSuppress,439978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2C.PCUnSuppress,439978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2C.PCUnShelve,439978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2C.INTK_EN,439978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0113_2C.ZF_EN,439978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FV_0113_2D.RemoteEnable,440056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FV_0113_2D.AutoEnable,440056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FV_0113_2D.FeedbackEnable,440056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FV_0113_2D.IR,440056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FV_0113_2D.ZF,440056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Failure" WA3252_FV_0113_2D.PLCFault,440056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2D.ZH,440056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2D.ZL,440056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Closed Status from device limit switch (Discrete Input to PLC)" WA3252_FV_0113_2D.GlobalReset,440056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D.OVRD,440056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Invoke Program Override - Regardless of Auto/Manual status" WA3252_FV_0113_2D.INTK,440056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Locked out by program" WA3252_FV_0113_2D.TAGR,440056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Tagged Out of Service" WA3252_FV_0113_2D.AutoOpen,440056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Open from Auto Logic" WA3252_FV_0113_2D.AutoClose,440056.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Auto Close from Auto Logic" WA3252_FV_0113_2D.ZD,440056.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Open Command" WA3252_FV_0113_2D.ZB,440056.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Close Command" WA3252_FV_0113_2D.ALRM,440057.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm on this device is active." WA3252_FV_0113_2D.ANUN,440057.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FV_0113_2D.AKED,440057.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FV_0113_2D.Resetable,440057.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FV_0113_2D.FailToOpen,440057.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Open Alarm is Active" WA3252_FV_0113_2D.FailToClose,440057.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Failed to Close Alarm is Active" WA3252_FV_0113_2D.ActuatorFaulted,440057.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm is Active" WA3252_FV_0113_2D.AutoRdy,440057.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Device is ready for auto control" WA3252_FV_0113_2D.AUTO,440057.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FV_0113_2D.ACKN,440057.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FV_0113_2D.REST,440057.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Reset Command from HMI" WA3252_FV_0113_2D.CLOS,440057.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Close Command from HMI" WA3252_FV_0113_2D.OPEN,440057.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Open Command from HMI" WA3252_FV_0113_2D.RSCT,440057.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Reset Valve Cycle Count" WA3252_FV_0113_2D.CloseFault,440057.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2D.OpenFault,440057.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2D.INFO,440058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: True indicates blue flag should be displayed." WA3252_FV_0113_2D.STOP,440058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Manual Stop Command from HMI" WA3252_FV_0113_2D.ActuatorFault,440058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: May not be in alarm due to alarm delay" WA3252_FV_0113_2D.PLCIOFault,440058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FV_0113_2D.Shelve,440058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelve Command from HMI" WA3252_FV_0113_2D.Shelved,440058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Shelved Status" WA3252_FV_0113_2D.Suppress,440058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Command from HMI" WA3252_FV_0113_2D.Suppressed,440058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppressed Status" WA3252_FV_0113_2D.PCSuppress,440058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Suppress Alarm from Program Control" WA3252_FV_0113_2D.PCUnSuppress,440058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: UnSuppress Alarm from Program Control" WA3252_FV_0113_2D.PCUnShelve,440058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Unshelve Alarm from Program Control" WA3252_FV_0113_2D.INTK_EN,440058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FV_0113_2D.ZF_EN,440058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FCV_0113_2A.RemoteEnable,440136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FCV_0113_2A.AutoEnable,440136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FCV_0113_2A.FeedbackEnable,440136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FCV_0113_2A.First_Scan,440136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC First Scan" WA3252_FCV_0113_2A.IR,440136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FCV_0113_2A.ZF,440136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure" WA3252_FCV_0113_2A.ManDisable,440136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set to 1 if manual control should only be done through a PID Block (never the faceplate for this valve)" WA3252_FCV_0113_2A.PLCFault,440136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A.PLCIOFault,440136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2A.GlobalReset,440136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.INTK,440136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_FCV_0113_2A.FLCL,440136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Fail Closed: 1 for Fail Closed Valves, 0 for Fail Open Valves" WA3252_FCV_0113_2A.BL_EN,440136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Broken Loop Alarm" WA3252_FCV_0113_2A.OR_EN,440136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Over Range Alarm" WA3252_FCV_0113_2A.PF_EN,440136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Failure Alarm Enable" WA3252_FCV_0113_2A.UR_EN,440136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Under Range Alarm" WA3252_FCV_0113_2A.TAGR,440137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_FCV_0113_2A.SupressAA,440137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress All Alarms" WA3252_FCV_0113_2A.ALRM,440137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_FCV_0113_2A.ANUN,440137.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FCV_0113_2A.AKED,440137.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FCV_0113_2A.Resetable,440137.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2A.ZB,440137.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Close Command" WA3252_FCV_0113_2A.ZD,440137.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Open Command" WA3252_FCV_0113_2A.ZH,440137.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Opened Status" WA3252_FCV_0113_2A.ZL,440137.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Closed Status" WA3252_FCV_0113_2A.BL_Alarm,440137.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm" WA3252_FCV_0113_2A.PF_Alarm,440137.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Failure Alarm (position error exceeded deadband for required delay)" WA3252_FCV_0113_2A.PositionFault,440137.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Current Position Error Exceeds Deadband" WA3252_FCV_0113_2A.UR_Alarm,440137.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm" WA3252_FCV_0113_2A.OR_Alarm,440137.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm" WA3252_FCV_0113_2A.Fault,440137.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: One of the alarm conditions is currently set (may not be in alarm yet)" WA3252_FCV_0113_2A.AutoRdy,440138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_FCV_0113_2A.ACKN,440138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FCV_0113_2A.REST,440138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Alarm Reset Command from HMI" WA3252_FCV_0113_2A.AUTO,440138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FCV_0113_2A.UR_Fault,440138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Fault" WA3252_FCV_0113_2A.BL_Fault,440138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Fault" WA3252_FCV_0113_2A.OR_Fault,440138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Fault" WA3252_FCV_0113_2A.INFO,440138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_FCV_0113_2A.Shelve,440138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2A.Shelved,440138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Shelved Status" WA3252_FCV_0113_2A.Suppress,440138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2A.Suppressed,440138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppressed Status" WA3252_FCV_0113_2A.ValveFailure,440138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm" WA3252_FCV_0113_2A.PCSuppress,440138.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2A.PCUnSuppress,440138.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2A.PCUnShelve,440138.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2A.INTK_EN,440139.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FCV_0113_2A.ZF_EN,440139.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" WA3252_FCV_0113_2B.RemoteEnable,440246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = remote/local input wired 0 = not wired" WA3252_FCV_0113_2B.AutoEnable,440246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set to 1 if there is an auto routine. Used to hide or show Auto display on HMI" WA3252_FCV_0113_2B.FeedbackEnable,440246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Open and Close Feedback is Present 0 = No Feedback" WA3252_FCV_0113_2B.First_Scan,440246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC First Scan" WA3252_FCV_0113_2B.IR,440246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Remote: 1 = Device In Remote 0 = Device In Local" WA3252_FCV_0113_2B.ZF,440246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure" WA3252_FCV_0113_2B.ManDisable,440246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set to 1 if manual control should only be done through a PID Block (never the faceplate for this valve)" WA3252_FCV_0113_2B.PLCFault,440246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B.PLCIOFault,440246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set if any of the I/O modules associated with the monitoring or control of the equipment has faulted." WA3252_FCV_0113_2B.GlobalReset,440246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.INTK,440246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Locked by program (ESD)" WA3252_FCV_0113_2B.FLCL,440246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Fail Closed: 1 for Fail Closed Valves, 0 for Fail Open Valves" WA3252_FCV_0113_2B.BL_EN,440246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Broken Loop Alarm" WA3252_FCV_0113_2B.OR_EN,440246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Over Range Alarm" WA3252_FCV_0113_2B.PF_EN,440246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Failure Alarm Enable" WA3252_FCV_0113_2B.UR_EN,440246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Enable Under Range Alarm" WA3252_FCV_0113_2B.TAGR,440247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Tagged Out of Service" WA3252_FCV_0113_2B.SupressAA,440247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress All Alarms" WA3252_FCV_0113_2B.ALRM,440247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm on this device is active." WA3252_FCV_0113_2B.ANUN,440247.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm in Device is annunciating (flash the device symbol)" WA3252_FCV_0113_2B.AKED,440247.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Acknowledged: At least one alarm has been acknowledged." WA3252_FCV_0113_2B.Resetable,440247.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: At least one alarm is latched and all latched alarms are resetable" WA3252_FCV_0113_2B.ZB,440247.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Close Command" WA3252_FCV_0113_2B.ZD,440247.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Open Command" WA3252_FCV_0113_2B.ZH,440247.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Opened Status" WA3252_FCV_0113_2B.ZL,440247.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: HMI to Show Valve Closed Status" WA3252_FCV_0113_2B.BL_Alarm,440247.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm" WA3252_FCV_0113_2B.PF_Alarm,440247.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Failure Alarm (position error exceeded deadband for required delay)" WA3252_FCV_0113_2B.PositionFault,440247.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Current Position Error Exceeds Deadband" WA3252_FCV_0113_2B.UR_Alarm,440247.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm" WA3252_FCV_0113_2B.OR_Alarm,440247.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm" WA3252_FCV_0113_2B.Fault,440247.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: One of the alarm conditions is currently set (may not be in alarm yet)" WA3252_FCV_0113_2B.AutoRdy,440248.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Device is ready for auto control" WA3252_FCV_0113_2B.ACKN,440248.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Acknowledge: HMI input to reset the AlarmAckd bit." WA3252_FCV_0113_2B.REST,440248.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Alarm Reset Command from HMI" WA3252_FCV_0113_2B.AUTO,440248.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Set by HMI 0 = Device in Manual 1 = Device in Auto" WA3252_FCV_0113_2B.UR_Fault,440248.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Fault" WA3252_FCV_0113_2B.BL_Fault,440248.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Fault" WA3252_FCV_0113_2B.OR_Fault,440248.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Fault" WA3252_FCV_0113_2B.INFO,440248.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: True indicates blue flag should be displayed." WA3252_FCV_0113_2B.Shelve,440248.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Shelve Command from HMI" WA3252_FCV_0113_2B.Shelved,440248.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Shelved Status" WA3252_FCV_0113_2B.Suppress,440248.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress Command from HMI" WA3252_FCV_0113_2B.Suppressed,440248.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppressed Status" WA3252_FCV_0113_2B.ValveFailure,440248.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm" WA3252_FCV_0113_2B.PCSuppress,440248.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Suppress Alarm from Program Control" WA3252_FCV_0113_2B.PCUnSuppress,440248.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: UnSuppress Alarm from Program Control" WA3252_FCV_0113_2B.PCUnShelve,440248.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Unshelve Alarm from Program Control" WA3252_FCV_0113_2B.INTK_EN,440249.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Interlock Enabled, 0 = Interlock Disabled" WA3252_FCV_0113_2B.ZF_EN,440249.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: 1 = Valve Failure Enabled, 0 = Valve Failure Disabled" BMENOC0311_4.ETH_PORT_1_2_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet port 1 and 2 status BMENOC0311_4.ETH_PORT3_BKP_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet port 3 and backplane port status BMENOC0311_4.FDR_USAGE,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: % of FDR server usage BMENOC0311_4.RESERVED,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Hidden - Reserved BMEP58_ECPU_EXT.RES_CRA_CNX_HEALTH32,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved BMEP58_ECPU_EXT.ETH_PORT_1_2_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet port 1 and 2 status BMEP58_ECPU_EXT.ETH_PORT3_BKP_STATUS,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet port 3 and backplane port status BMEP58_ECPU_EXT.FDR_USAGE,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): % of FDR server usage BMEP58_ECPU_EXT.RESERVED1,,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved TSR_PLC.Fresh_Reserved,,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved AI_R2_S10.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R1_S10.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R0_S10.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R3_S10.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R3_S9.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R0_S9.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R1_S9.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R2_S9.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R4_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R4_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R4_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R5_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R5_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R5_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R5_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R6_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AI_R6_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AO_R1_S11.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AO_R2_S11.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AO_R3_S11.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults AO_R6_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R0_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R0_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R0_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R0_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R2_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S6.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R3_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R0_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R1_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R4_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R5_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R5_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R5_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R5_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R6_S4.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R6_S0.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R6_S1.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R6_S2.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DI_R6_S3.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R0_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R2_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R3_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R1_S8.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R0_S11.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R2_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R3_S7.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults DO_R6_S5.MOD_FLT,,Byte,1,R/W,1000,,,,,,,,,,Module faults WA3252_AFD_0103_1.RTTodayHrs,436366,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_1.RTTodayMin,436368,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_1.RTTotalHrs,436370,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_1.RTTotalMin,436372,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_1.RTYesterdayHrs,436374,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_1.RTYesterdayMin,436376,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_1.STRS,436378,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_1.STTD,436380,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_1.STYD,436382,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_1.TabIndex,436470,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_2.RTTodayHrs,436502,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_2.RTTodayMin,436504,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_2.RTTotalHrs,436506,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_2.RTTotalMin,436508,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_2.RTYesterdayHrs,436510,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_2.RTYesterdayMin,436512,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_2.STRS,436514,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_2.STTD,436516,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_2.STYD,436518,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_2.TabIndex,436606,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_3.RTTodayHrs,436636,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_3.RTTodayMin,436638,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_3.RTTotalHrs,436640,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_3.RTTotalMin,436642,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_3.RTYesterdayHrs,436644,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_3.RTYesterdayMin,436646,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_3.STRS,436648,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_3.STTD,436650,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_3.STYD,436652,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_3.TabIndex,436740,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_4.RTTodayHrs,436772,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_4.RTTodayMin,436774,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_4.RTTotalHrs,436776,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_4.RTTotalMin,436778,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_4.RTYesterdayHrs,436780,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_4.RTYesterdayMin,436782,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_4.STRS,436784,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_4.STTD,436786,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_4.STYD,436788,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_4.TabIndex,436876,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_5.RTTodayHrs,436906,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_5.RTTodayMin,436908,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_5.RTTotalHrs,436910,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_5.RTTotalMin,436912,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_5.RTYesterdayHrs,436914,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_5.RTYesterdayMin,436916,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_5.STRS,436918,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_5.STTD,436920,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_5.STYD,436922,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_5.TabIndex,437010,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_6.RTTodayHrs,437042,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_6.RTTodayMin,437044,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_6.RTTotalHrs,437046,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_6.RTTotalMin,437048,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_6.RTYesterdayHrs,437050,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_6.RTYesterdayMin,437052,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_6.STRS,437054,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_6.STTD,437056,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_6.STYD,437058,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_6.TabIndex,437146,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_7.RTTodayHrs,437176,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_7.RTTodayMin,437178,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_7.RTTotalHrs,437180,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_7.RTTotalMin,437182,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_7.RTYesterdayHrs,437184,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_7.RTYesterdayMin,437186,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_7.STRS,437188,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_7.STTD,437190,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_7.STYD,437192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_7.TabIndex,437280,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_8.RTTodayHrs,437312,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_8.RTTodayMin,437314,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_8.RTTotalHrs,437316,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_8.RTTotalMin,437318,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_8.RTYesterdayHrs,437320,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_8.RTYesterdayMin,437322,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_8.STRS,437324,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_8.STTD,437326,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_8.STYD,437328,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_8.TabIndex,437416,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_AFD_0103_9.RTTodayHrs,437446,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Today/Current" WA3252_AFD_0103_9.RTTodayMin,437448,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Today" WA3252_AFD_0103_9.RTTotalHrs,437450,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Total Since Last Reset" WA3252_AFD_0103_9.RTTotalMin,437452,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Since Last Reset" WA3252_AFD_0103_9.RTYesterdayHrs,437454,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Hours Yesterday" WA3252_AFD_0103_9.RTYesterdayMin,437456,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Run Time Minutes Yesterday" WA3252_AFD_0103_9.STRS,437458,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Total Count of Device Starts since last starts reset" WA3252_AFD_0103_9.STTD,437460,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Today" WA3252_AFD_0103_9.STYD,437462,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Count of Starts Yesterday" WA3252_AFD_0103_9.TabIndex,437550,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Faceplate Display Index" WA3252_FV_0102_1A.Inp_OvrdCmd,437582,Long,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0102_1A.CLCT,437586,Long,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0102_1A.TabIndex,437594,Long,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0102_1B.Inp_OvrdCmd,437662,Long,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0102_1B.CLCT,437666,Long,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0102_1B.TabIndex,437674,Long,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0102_2A.Inp_OvrdCmd,437742,Long,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0102_2A.CLCT,437746,Long,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0102_2A.TabIndex,437754,Long,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0102_2B.Inp_OvrdCmd,437822,Long,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0102_2B.CLCT,437826,Long,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0102_2B.TabIndex,437834,Long,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_1A.Inp_OvrdCmd,437902,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_1A.CLCT,437906,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_1A.TabIndex,437914,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_1C.Inp_OvrdCmd,437982,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_1C.CLCT,437986,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_1C.TabIndex,437994,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_2A.Inp_OvrdCmd,438062,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_2A.CLCT,438066,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_2A.TabIndex,438074,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_2C.Inp_OvrdCmd,438142,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_2C.CLCT,438146,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_2C.TabIndex,438154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_3A.Inp_OvrdCmd,438222,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_3A.CLCT,438226,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_3A.TabIndex,438234,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_3C.Inp_OvrdCmd,438302,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_3C.CLCT,438306,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_3C.TabIndex,438314,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_3D.Inp_OvrdCmd,438382,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_3D.CLCT,438386,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_3D.TabIndex,438394,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_4A.Inp_OvrdCmd,438462,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_4A.CLCT,438466,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_4A.TabIndex,438474,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_4C.Inp_OvrdCmd,438542,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_4C.CLCT,438546,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_4C.TabIndex,438554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_4D.Inp_OvrdCmd,438622,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_4D.CLCT,438626,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_4D.TabIndex,438634,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_5A.Inp_OvrdCmd,438702,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_5A.CLCT,438706,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_5A.TabIndex,438714,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_5C.Inp_OvrdCmd,438782,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_5C.CLCT,438786,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_5C.TabIndex,438794,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_5D.Inp_OvrdCmd,438862,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_5D.CLCT,438866,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_5D.TabIndex,438874,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_6A.Inp_OvrdCmd,438942,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_6A.CLCT,438946,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_6A.TabIndex,438954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_6C.Inp_OvrdCmd,439022,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_6C.CLCT,439026,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_6C.TabIndex,439034,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_6D.Inp_OvrdCmd,439102,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_6D.CLCT,439106,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_6D.TabIndex,439114,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_7A.Inp_OvrdCmd,439182,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_7A.CLCT,439186,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_7A.TabIndex,439194,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_7C.Inp_OvrdCmd,439262,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_7C.CLCT,439266,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_7C.TabIndex,439274,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_7D.Inp_OvrdCmd,439342,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_7D.CLCT,439346,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_7D.TabIndex,439354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_8A.Inp_OvrdCmd,439422,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_8A.CLCT,439426,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_8A.TabIndex,439434,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_8C.Inp_OvrdCmd,439502,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_8C.CLCT,439506,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_8C.TabIndex,439514,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_8D.Inp_OvrdCmd,439582,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_8D.CLCT,439586,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_8D.TabIndex,439594,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_9A.Inp_OvrdCmd,439662,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_9A.CLCT,439666,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_9A.TabIndex,439674,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0103_9C.Inp_OvrdCmd,439742,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0103_9C.CLCT,439746,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0103_9C.TabIndex,439754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0113_2A.Inp_OvrdCmd,439822,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0113_2A.CLCT,439826,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0113_2A.TabIndex,439834,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0113_2B.Inp_OvrdCmd,439902,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0113_2B.CLCT,439906,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0113_2B.TabIndex,439914,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0113_2C.Inp_OvrdCmd,439982,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0113_2C.CLCT,439986,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0113_2C.TabIndex,439994,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FV_0113_2D.Inp_OvrdCmd,440062,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Override Mode Command 1 = Close, 2 = Open" WA3252_FV_0113_2D.CLCT,440066,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Valve Cycle Count" WA3252_FV_0113_2D.TabIndex,440074,Long,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Faceplate Display Index" WA3252_FCV_0113_2A.ZI,440142,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Feedback 4,000-20,000 (4,000 when closed for fail closed or open for fail open)" WA3252_FCV_0113_2A.ZC,440158,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Command 4,000-20,000 (4,000 when closed for fail closed or open for fail open)" WA3252_FCV_0113_2B.ZI,440252,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Feedback 4,000-20,000 (4,000 when closed for fail closed or open for fail open)" WA3252_FCV_0113_2B.ZC,440268,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Command 4,000-20,000 (4,000 when closed for fail closed or open for fail open)" Write_Test.[0],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[1],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[2],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[3],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[4],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[5],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[6],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[7],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[8],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[9],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[10],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[11],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[12],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[13],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[14],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[15],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[16],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[17],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[18],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[19],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[20],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[21],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[22],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[23],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[24],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[25],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[26],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[27],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[28],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[29],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[30],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[31],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[32],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[33],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[34],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[35],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[36],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[37],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[38],,Short,1,R/W,1000,,,,,,,,,, Write_Test.[39],,Short,1,R/W,1000,,,,,,,,,, MeterVault_PLC.[0],,Short,1,R/W,1000,,,,,,,,,,Meter Vault PLC Read Params MeterVault_PLC.[1],,Short,1,R/W,1000,,,,,,,,,,Meter Vault PLC Read Params MeterVault_PLC.[2],,Short,1,R/W,1000,,,,,,,,,,Meter Vault PLC Read Params MeterVault_PLC.[3],,Short,1,R/W,1000,,,,,,,,,,Meter Vault PLC Read Params CP_002_1_GEST.[0],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_GEST.[1],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_GEST.[2],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_GEST.[3],,Short,1,R/W,1000,,,,,,,,,, Clock.[0],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[1],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[2],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[3],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[4],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[5],,Short,1,R/W,1000,,,,,,,,,,System Time Clock.[6],,Short,1,R/W,1000,,,,,,,,,,System Time CP_002_1_Breakers.[1],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[2],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[3],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[4],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[5],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[6],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[7],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[8],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[9],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[10],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[11],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[12],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[13],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[14],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[15],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[16],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[17],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[18],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[19],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[20],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[21],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[22],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[23],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[24],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[25],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[26],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[27],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[28],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[29],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[30],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[31],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[32],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[33],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[34],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[35],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[36],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[37],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[38],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[39],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[40],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[41],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[42],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[43],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[44],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[45],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[46],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[47],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[48],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[49],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[50],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[51],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[52],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[53],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[54],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[55],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[56],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[57],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[58],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[59],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[60],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[61],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[62],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[63],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[64],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[65],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[66],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[67],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[68],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[69],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[70],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[71],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[72],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[73],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[74],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[75],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[76],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[77],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[78],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[79],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[80],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[81],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[82],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[83],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[84],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[85],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[86],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[87],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[88],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[89],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[90],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[91],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[92],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[93],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[94],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[95],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[96],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[97],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[98],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[99],,Short,1,R/W,1000,,,,,,,,,, CP_002_1_Breakers.[100],,Short,1,R/W,1000,,,,,,,,,, MeterVault_Values.[1],,Short,1,R/W,1000,,,,,,,,,, MeterVault_Values.[2],,Short,1,R/W,1000,,,,,,,,,, MeterVault_Values.[3],,Short,1,R/W,1000,,,,,,,,,, MeterVault_Values.[4],,Short,1,R/W,1000,,,,,,,,,, WA3252_AFD_0103_1_SI.BOOLS1,401000,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.BOOLS2,401001,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.BOOLS3,401002,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_1_SI.BOOLS4,401003,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_1_SI.INT1,401004,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_1_SI.INT2,401005,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_1_SI.Raw,401006,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_1_SI.AENotify,401196,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_SI.BOOLS1,401200,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.BOOLS2,401201,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.BOOLS3,401202,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_2_SI.BOOLS4,401203,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_2_SI.INT1,401204,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_2_SI.INT2,401205,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_2_SI.Raw,401206,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_2_SI.AENotify,401396,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_SI.BOOLS1,401400,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.BOOLS2,401401,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.BOOLS3,401402,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_3_SI.BOOLS4,401403,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_3_SI.INT1,401404,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_3_SI.INT2,401405,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_3_SI.Raw,401406,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_3_SI.AENotify,401596,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_SI.BOOLS1,401600,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.BOOLS2,401601,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.BOOLS3,401602,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_4_SI.BOOLS4,401603,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_4_SI.INT1,401604,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_4_SI.INT2,401605,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_4_SI.Raw,401606,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_4_SI.AENotify,401796,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_SI.BOOLS1,401800,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.BOOLS2,401801,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.BOOLS3,401802,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_5_SI.BOOLS4,401803,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_5_SI.INT1,401804,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_5_SI.INT2,401805,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_5_SI.Raw,401806,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_5_SI.AENotify,401996,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_SI.BOOLS1,402000,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.BOOLS2,402001,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.BOOLS3,402002,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_6_SI.BOOLS4,402003,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_6_SI.INT1,402004,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_6_SI.INT2,402005,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_6_SI.Raw,402006,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_6_SI.AENotify,402196,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_SI.BOOLS1,402200,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.BOOLS2,402201,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.BOOLS3,402202,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_7_SI.BOOLS4,402203,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_7_SI.INT1,402204,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_7_SI.INT2,402205,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_7_SI.Raw,402206,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_7_SI.AENotify,402396,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_SI.BOOLS1,402400,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.BOOLS2,402401,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.BOOLS3,402402,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_8_SI.BOOLS4,402403,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_8_SI.INT1,402404,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_8_SI.INT2,402405,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_8_SI.Raw,402406,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_8_SI.AENotify,402596,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_SI.BOOLS1,402600,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.BOOLS2,402601,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.BOOLS3,402602,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_9_SI.BOOLS4,402603,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_9_SI.INT1,402604,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_9_SI.INT2,402605,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_AFD_0103_9_SI.Raw,402606,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_AFD_0103_9_SI.AENotify,402796,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI1.BOOLS1,402800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.BOOLS2,402801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.BOOLS3,402802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI1.BOOLS4,402803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI1.INT1,402804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI1.INT2,402805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI1.Raw,402806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI1.AENotify,402996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI2.BOOLS1,403000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.BOOLS2,403001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.BOOLS3,403002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI2.BOOLS4,403003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI2.INT1,403004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI2.INT2,403005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI2.Raw,403006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI2.AENotify,403196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI3.BOOLS1,403200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.BOOLS2,403201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.BOOLS3,403202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI3.BOOLS4,403203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI3.INT1,403204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI3.INT2,403205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI3.Raw,403206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI3.AENotify,403396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI4.BOOLS1,403400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.BOOLS2,403401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.BOOLS3,403402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI4.BOOLS4,403403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI4.INT1,403404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI4.INT2,403405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI4.Raw,403406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI4.AENotify,403596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI5.BOOLS1,403600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.BOOLS2,403601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.BOOLS3,403602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI5.BOOLS4,403603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI5.INT1,403604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI5.INT2,403605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI5.Raw,403606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI5.AENotify,403796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI6.BOOLS1,403800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.BOOLS2,403801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.BOOLS3,403802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI6.BOOLS4,403803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI6.INT1,403804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI6.INT2,403805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI6.Raw,403806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI6.AENotify,403996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI7.BOOLS1,404000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.BOOLS2,404001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.BOOLS3,404002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI7.BOOLS4,404003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI7.INT1,404004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI7.INT2,404005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI7.Raw,404006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI7.AENotify,404196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI8.BOOLS1,404200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.BOOLS2,404201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.BOOLS3,404202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI8.BOOLS4,404203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI8.INT1,404204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI8.INT2,404205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI8.Raw,404206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI8.AENotify,404396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0116_1_FI9.BOOLS1,404400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.BOOLS2,404401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.BOOLS3,404402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_CP_0116_1_FI9.BOOLS4,404403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_CP_0116_1_FI9.INT1,404404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI9.INT2,404405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_CP_0116_1_FI9.Raw,404406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_CP_0116_1_FI9.AENotify,404596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2A_ZI.BOOLS1,404600,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.BOOLS2,404601,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.BOOLS3,404602,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FCV_0113_2A_ZI.BOOLS4,404603,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FCV_0113_2A_ZI.INT1,404604,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FCV_0113_2A_ZI.INT2,404605,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FCV_0113_2A_ZI.Raw,404606,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FCV_0113_2A_ZI.AENotify,404796,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2B_ZI.BOOLS1,404800,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.BOOLS2,404801,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.BOOLS3,404802,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FCV_0113_2B_ZI.BOOLS4,404803,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FCV_0113_2B_ZI.INT1,404804,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FCV_0113_2B_ZI.INT2,404805,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FCV_0113_2B_ZI.Raw,404806,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FCV_0113_2B_ZI.AENotify,404996,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FIT_0113_2A_FI.BOOLS1,405000,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.BOOLS2,405001,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.BOOLS3,405002,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FIT_0113_2A_FI.BOOLS4,405003,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FIT_0113_2A_FI.INT1,405004,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FIT_0113_2A_FI.INT2,405005,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FIT_0113_2A_FI.Raw,405006,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FIT_0113_2A_FI.AENotify,405196,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1B_ZI.BOOLS1,405200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.BOOLS2,405201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.BOOLS3,405202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_1B_ZI.BOOLS4,405203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_1B_ZI.INT1,405204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_1B_ZI.INT2,405205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_1B_ZI.Raw,405206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_1B_ZI.AENotify,405396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2B_ZI.BOOLS1,405400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.BOOLS2,405401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.BOOLS3,405402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_2B_ZI.BOOLS4,405403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_2B_ZI.INT1,405404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_2B_ZI.INT2,405405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_2B_ZI.Raw,405406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_2B_ZI.AENotify,405596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3B_ZI.BOOLS1,405600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.BOOLS2,405601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.BOOLS3,405602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_3B_ZI.BOOLS4,405603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_3B_ZI.INT1,405604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_3B_ZI.INT2,405605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_3B_ZI.Raw,405606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_3B_ZI.AENotify,405796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4B_ZI.BOOLS1,405800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.BOOLS2,405801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.BOOLS3,405802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_4B_ZI.BOOLS4,405803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_4B_ZI.INT1,405804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_4B_ZI.INT2,405805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_4B_ZI.Raw,405806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_4B_ZI.AENotify,405996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5B_ZI.BOOLS1,406000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.BOOLS2,406001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.BOOLS3,406002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_5B_ZI.BOOLS4,406003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_5B_ZI.INT1,406004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_5B_ZI.INT2,406005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_5B_ZI.Raw,406006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_5B_ZI.AENotify,406196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6B_ZI.BOOLS1,406200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.BOOLS2,406201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.BOOLS3,406202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_6B_ZI.BOOLS4,406203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_6B_ZI.INT1,406204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_6B_ZI.INT2,406205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_6B_ZI.Raw,406206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_6B_ZI.AENotify,406396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7B_ZI.BOOLS1,406400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.BOOLS2,406401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.BOOLS3,406402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_7B_ZI.BOOLS4,406403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_7B_ZI.INT1,406404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_7B_ZI.INT2,406405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_7B_ZI.Raw,406406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_7B_ZI.AENotify,406596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8B_ZI.BOOLS1,406600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.BOOLS2,406601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.BOOLS3,406602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_8B_ZI.BOOLS4,406603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_8B_ZI.INT1,406604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_8B_ZI.INT2,406605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_8B_ZI.Raw,406606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_8B_ZI.AENotify,406796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9B_ZI.BOOLS1,406800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.BOOLS2,406801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.BOOLS3,406802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_FV_0103_9B_ZI.BOOLS4,406803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_FV_0103_9B_ZI.INT1,406804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_9B_ZI.INT2,406805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_FV_0103_9B_ZI.Raw,406806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_FV_0103_9B_ZI.AENotify,406996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_1_VI1.BOOLS1,407000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.BOOLS2,407001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.BOOLS3,407002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_1_VI1.BOOLS4,407003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_1_VI1.INT1,407004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI1.INT2,407005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI1.Raw,407006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_1_VI1.AENotify,407196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_1_VI2.BOOLS1,407200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.BOOLS2,407201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.BOOLS3,407202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_1_VI2.BOOLS4,407203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_1_VI2.INT1,407204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI2.INT2,407205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI2.Raw,407206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_1_VI2.AENotify,407396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_1_VI3.BOOLS1,407400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.BOOLS2,407401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.BOOLS3,407402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_1_VI3.BOOLS4,407403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_1_VI3.INT1,407404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI3.INT2,407405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI3.Raw,407406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_1_VI3.AENotify,407596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_1_VI4.BOOLS1,407600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.BOOLS2,407601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.BOOLS3,407602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_1_VI4.BOOLS4,407603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_1_VI4.INT1,407604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI4.INT2,407605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_1_VI4.Raw,407606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_1_VI4.AENotify,407796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_2_VI1.BOOLS1,407800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.BOOLS2,407801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.BOOLS3,407802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_2_VI1.BOOLS4,407803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_2_VI1.INT1,407804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI1.INT2,407805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI1.Raw,407806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_2_VI1.AENotify,407996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_2_VI2.BOOLS1,408000,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.BOOLS2,408001,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.BOOLS3,408002,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_2_VI2.BOOLS4,408003,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_2_VI2.INT1,408004,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI2.INT2,408005,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI2.Raw,408006,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_2_VI2.AENotify,408196,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_2_VI3.BOOLS1,408200,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.BOOLS2,408201,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.BOOLS3,408202,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_2_VI3.BOOLS4,408203,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_2_VI3.INT1,408204,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI3.INT2,408205,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI3.Raw,408206,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_2_VI3.AENotify,408396,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_2_VI4.BOOLS1,408400,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.BOOLS2,408401,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.BOOLS3,408402,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_2_VI4.BOOLS4,408403,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_2_VI4.INT1,408404,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI4.INT2,408405,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_2_VI4.Raw,408406,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_2_VI4.AENotify,408596,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_3_VI1.BOOLS1,408600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.BOOLS2,408601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.BOOLS3,408602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_3_VI1.BOOLS4,408603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_3_VI1.INT1,408604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI1.INT2,408605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI1.Raw,408606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_3_VI1.AENotify,408796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_3_VI2.BOOLS1,408800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.BOOLS2,408801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.BOOLS3,408802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_3_VI2.BOOLS4,408803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_3_VI2.INT1,408804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI2.INT2,408805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI2.Raw,408806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_3_VI2.AENotify,408996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_3_VI3.BOOLS1,409000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.BOOLS2,409001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.BOOLS3,409002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_3_VI3.BOOLS4,409003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_3_VI3.INT1,409004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI3.INT2,409005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI3.Raw,409006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_3_VI3.AENotify,409196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_3_VI4.BOOLS1,409200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.BOOLS2,409201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.BOOLS3,409202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_3_VI4.BOOLS4,409203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_3_VI4.INT1,409204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI4.INT2,409205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_3_VI4.Raw,409206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_3_VI4.AENotify,409396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_4_VI1.BOOLS1,409400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.BOOLS2,409401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.BOOLS3,409402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_4_VI1.BOOLS4,409403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_4_VI1.INT1,409404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI1.INT2,409405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI1.Raw,409406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_4_VI1.AENotify,409596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_4_VI2.BOOLS1,409600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.BOOLS2,409601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.BOOLS3,409602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_4_VI2.BOOLS4,409603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_4_VI2.INT1,409604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI2.INT2,409605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI2.Raw,409606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_4_VI2.AENotify,409796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_4_VI3.BOOLS1,409800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.BOOLS2,409801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.BOOLS3,409802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_4_VI3.BOOLS4,409803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_4_VI3.INT1,409804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI3.INT2,409805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI3.Raw,409806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_4_VI3.AENotify,409996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_4_VI4.BOOLS1,410000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.BOOLS2,410001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.BOOLS3,410002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_4_VI4.BOOLS4,410003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_4_VI4.INT1,410004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI4.INT2,410005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_4_VI4.Raw,410006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_4_VI4.AENotify,410196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_5_VI1.BOOLS1,410200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.BOOLS2,410201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.BOOLS3,410202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_5_VI1.BOOLS4,410203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_5_VI1.INT1,410204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI1.INT2,410205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI1.Raw,410206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_5_VI1.AENotify,410396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_5_VI2.BOOLS1,410400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.BOOLS2,410401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.BOOLS3,410402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_5_VI2.BOOLS4,410403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_5_VI2.INT1,410404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI2.INT2,410405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI2.Raw,410406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_5_VI2.AENotify,410596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_5_VI3.BOOLS1,410600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.BOOLS2,410601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.BOOLS3,410602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_5_VI3.BOOLS4,410603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_5_VI3.INT1,410604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI3.INT2,410605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI3.Raw,410606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_5_VI3.AENotify,410796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_5_VI4.BOOLS1,410800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.BOOLS2,410801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.BOOLS3,410802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_5_VI4.BOOLS4,410803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_5_VI4.INT1,410804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI4.INT2,410805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_5_VI4.Raw,410806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_5_VI4.AENotify,410996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_6_VI1.BOOLS1,411000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.BOOLS2,411001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.BOOLS3,411002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_6_VI1.BOOLS4,411003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_6_VI1.INT1,411004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI1.INT2,411005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI1.Raw,411006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_6_VI1.AENotify,411196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_6_VI2.BOOLS1,411200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.BOOLS2,411201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.BOOLS3,411202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_6_VI2.BOOLS4,411203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_6_VI2.INT1,411204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI2.INT2,411205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI2.Raw,411206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_6_VI2.AENotify,411396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_6_VI3.BOOLS1,411400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.BOOLS2,411401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.BOOLS3,411402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_6_VI3.BOOLS4,411403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_6_VI3.INT1,411404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI3.INT2,411405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI3.Raw,411406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_6_VI3.AENotify,411596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_6_VI4.BOOLS1,411600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.BOOLS2,411601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.BOOLS3,411602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_6_VI4.BOOLS4,411603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_6_VI4.INT1,411604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI4.INT2,411605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_6_VI4.Raw,411606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_6_VI4.AENotify,411796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_7_VI1.BOOLS1,411800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.BOOLS2,411801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.BOOLS3,411802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_7_VI1.BOOLS4,411803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_7_VI1.INT1,411804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI1.INT2,411805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI1.Raw,411806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_7_VI1.AENotify,411996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_7_VI2.BOOLS1,412000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.BOOLS2,412001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.BOOLS3,412002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_7_VI2.BOOLS4,412003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_7_VI2.INT1,412004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI2.INT2,412005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI2.Raw,412006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_7_VI2.AENotify,412196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_7_VI3.BOOLS1,412200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.BOOLS2,412201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.BOOLS3,412202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_7_VI3.BOOLS4,412203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_7_VI3.INT1,412204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI3.INT2,412205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI3.Raw,412206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_7_VI3.AENotify,412396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_7_VI4.BOOLS1,412400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.BOOLS2,412401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.BOOLS3,412402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_7_VI4.BOOLS4,412403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_7_VI4.INT1,412404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI4.INT2,412405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_7_VI4.Raw,412406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_7_VI4.AENotify,412596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_8_VI1.BOOLS1,412600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.BOOLS2,412601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.BOOLS3,412602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_8_VI1.BOOLS4,412603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_8_VI1.INT1,412604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI1.INT2,412605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI1.Raw,412606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_8_VI1.AENotify,412796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_8_VI2.BOOLS1,412800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.BOOLS2,412801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.BOOLS3,412802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_8_VI2.BOOLS4,412803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_8_VI2.INT1,412804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI2.INT2,412805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI2.Raw,412806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_8_VI2.AENotify,412996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_8_VI3.BOOLS1,413000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.BOOLS2,413001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.BOOLS3,413002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_8_VI3.BOOLS4,413003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_8_VI3.INT1,413004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI3.INT2,413005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI3.Raw,413006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_8_VI3.AENotify,413196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_8_VI4.BOOLS1,413200,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.BOOLS2,413201,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.BOOLS3,413202,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_8_VI4.BOOLS4,413203,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_8_VI4.INT1,413204,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI4.INT2,413205,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_8_VI4.Raw,413206,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_8_VI4.AENotify,413396,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_9_VI1.BOOLS1,413400,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.BOOLS2,413401,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.BOOLS3,413402,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_9_VI1.BOOLS4,413403,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_9_VI1.INT1,413404,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI1.INT2,413405,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI1.Raw,413406,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_9_VI1.AENotify,413596,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_9_VI2.BOOLS1,413600,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.BOOLS2,413601,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.BOOLS3,413602,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_9_VI2.BOOLS4,413603,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_9_VI2.INT1,413604,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI2.INT2,413605,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI2.Raw,413606,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_9_VI2.AENotify,413796,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_9_VI3.BOOLS1,413800,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.BOOLS2,413801,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.BOOLS3,413802,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_9_VI3.BOOLS4,413803,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_9_VI3.INT1,413804,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI3.INT2,413805,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI3.Raw,413806,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_9_VI3.AENotify,413996,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_MTR_0103_9_VI4.BOOLS1,414000,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.BOOLS2,414001,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.BOOLS3,414002,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_MTR_0103_9_VI4.BOOLS4,414003,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_MTR_0103_9_VI4.INT1,414004,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI4.INT2,414005,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_MTR_0103_9_VI4.Raw,414006,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_MTR_0103_9_VI4.AENotify,414196,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0102_1_PI.BOOLS1,414200,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.BOOLS2,414201,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.BOOLS3,414202,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0102_1_PI.BOOLS4,414203,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0102_1_PI.INT1,414204,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0102_1_PI.INT2,414205,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0102_1_PI.Raw,414206,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0102_1_PI.AENotify,414396,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0102_2_PI.BOOLS1,414400,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.BOOLS2,414401,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.BOOLS3,414402,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0102_2_PI.BOOLS4,414403,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0102_2_PI.INT1,414404,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0102_2_PI.INT2,414405,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0102_2_PI.Raw,414406,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0102_2_PI.AENotify,414596,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_1_PI.BOOLS1,414600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.BOOLS2,414601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.BOOLS3,414602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_1_PI.BOOLS4,414603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_1_PI.INT1,414604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_1_PI.INT2,414605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_1_PI.Raw,414606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_1_PI.AENotify,414796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_2_PI.BOOLS1,414800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.BOOLS2,414801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.BOOLS3,414802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_2_PI.BOOLS4,414803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_2_PI.INT1,414804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_2_PI.INT2,414805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_2_PI.Raw,414806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_2_PI.AENotify,414996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_3_PI.BOOLS1,415000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.BOOLS2,415001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.BOOLS3,415002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_3_PI.BOOLS4,415003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_3_PI.INT1,415004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_3_PI.INT2,415005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_3_PI.Raw,415006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_3_PI.AENotify,415196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_4_PI.BOOLS1,415200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.BOOLS2,415201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.BOOLS3,415202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_4_PI.BOOLS4,415203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_4_PI.INT1,415204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_4_PI.INT2,415205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_4_PI.Raw,415206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_4_PI.AENotify,415396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_5_PI.BOOLS1,415400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.BOOLS2,415401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.BOOLS3,415402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_5_PI.BOOLS4,415403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_5_PI.INT1,415404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_5_PI.INT2,415405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_5_PI.Raw,415406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_5_PI.AENotify,415596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_6_PI.BOOLS1,415600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.BOOLS2,415601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.BOOLS3,415602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_6_PI.BOOLS4,415603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_6_PI.INT1,415604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_6_PI.INT2,415605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_6_PI.Raw,415606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_6_PI.AENotify,415796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_7_PI.BOOLS1,415800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.BOOLS2,415801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.BOOLS3,415802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_7_PI.BOOLS4,415803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_7_PI.INT1,415804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_7_PI.INT2,415805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_7_PI.Raw,415806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_7_PI.AENotify,415996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_8_PI.BOOLS1,416000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.BOOLS2,416001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.BOOLS3,416002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_8_PI.BOOLS4,416003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_8_PI.INT1,416004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_8_PI.INT2,416005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_8_PI.Raw,416006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_8_PI.AENotify,416196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0103_9_PI.BOOLS1,416200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.BOOLS2,416201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.BOOLS3,416202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0103_9_PI.BOOLS4,416203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0103_9_PI.INT1,416204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_9_PI.INT2,416205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0103_9_PI.Raw,416206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0103_9_PI.AENotify,416396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0104_1_PI.BOOLS1,416400,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.BOOLS2,416401,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.BOOLS3,416402,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PIT_0104_1_PI.BOOLS4,416403,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PIT_0104_1_PI.INT1,416404,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0104_1_PI.INT2,416405,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PIT_0104_1_PI.Raw,416406,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PIT_0104_1_PI.AENotify,416596,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_1_VI1.BOOLS1,416600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.BOOLS2,416601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.BOOLS3,416602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_1_VI1.BOOLS4,416603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_1_VI1.INT1,416604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI1.INT2,416605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI1.Raw,416606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_1_VI1.AENotify,416796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_1_VI2.BOOLS1,416800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.BOOLS2,416801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.BOOLS3,416802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_1_VI2.BOOLS4,416803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_1_VI2.INT1,416804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI2.INT2,416805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI2.Raw,416806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_1_VI2.AENotify,416996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_1_VI3.BOOLS1,417000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.BOOLS2,417001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.BOOLS3,417002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_1_VI3.BOOLS4,417003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_1_VI3.INT1,417004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI3.INT2,417005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI3.Raw,417006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_1_VI3.AENotify,417196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_1_VI4.BOOLS1,417200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.BOOLS2,417201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.BOOLS3,417202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_1_VI4.BOOLS4,417203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_1_VI4.INT1,417204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI4.INT2,417205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI4.Raw,417206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_1_VI4.AENotify,417396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_1_VI5.BOOLS1,417400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.BOOLS2,417401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.BOOLS3,417402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_1_VI5.BOOLS4,417403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_1_VI5.INT1,417404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI5.INT2,417405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_1_VI5.Raw,417406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_1_VI5.AENotify,417596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_2_VI1.BOOLS1,417600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.BOOLS2,417601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.BOOLS3,417602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_2_VI1.BOOLS4,417603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_2_VI1.INT1,417604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI1.INT2,417605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI1.Raw,417606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_2_VI1.AENotify,417796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_2_VI2.BOOLS1,417800,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.BOOLS2,417801,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.BOOLS3,417802,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_2_VI2.BOOLS4,417803,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_2_VI2.INT1,417804,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI2.INT2,417805,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI2.Raw,417806,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_2_VI2.AENotify,417996,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_2_VI3.BOOLS1,418000,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.BOOLS2,418001,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.BOOLS3,418002,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_2_VI3.BOOLS4,418003,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_2_VI3.INT1,418004,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI3.INT2,418005,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI3.Raw,418006,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_2_VI3.AENotify,418196,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_2_VI4.BOOLS1,418200,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.BOOLS2,418201,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.BOOLS3,418202,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_2_VI4.BOOLS4,418203,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_2_VI4.INT1,418204,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI4.INT2,418205,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI4.Raw,418206,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_2_VI4.AENotify,418396,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_2_VI5.BOOLS1,418400,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.BOOLS2,418401,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.BOOLS3,418402,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_2_VI5.BOOLS4,418403,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_2_VI5.INT1,418404,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI5.INT2,418405,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_2_VI5.Raw,418406,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_2_VI5.AENotify,418596,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_3_VI1.BOOLS1,418600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.BOOLS2,418601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.BOOLS3,418602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_3_VI1.BOOLS4,418603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_3_VI1.INT1,418604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI1.INT2,418605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI1.Raw,418606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_3_VI1.AENotify,418796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_3_VI2.BOOLS1,418800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.BOOLS2,418801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.BOOLS3,418802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_3_VI2.BOOLS4,418803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_3_VI2.INT1,418804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI2.INT2,418805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI2.Raw,418806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_3_VI2.AENotify,418996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_3_VI3.BOOLS1,419000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.BOOLS2,419001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.BOOLS3,419002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_3_VI3.BOOLS4,419003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_3_VI3.INT1,419004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI3.INT2,419005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI3.Raw,419006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_3_VI3.AENotify,419196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_3_VI4.BOOLS1,419200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.BOOLS2,419201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.BOOLS3,419202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_3_VI4.BOOLS4,419203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_3_VI4.INT1,419204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI4.INT2,419205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI4.Raw,419206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_3_VI4.AENotify,419396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_3_VI5.BOOLS1,419400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.BOOLS2,419401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.BOOLS3,419402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_3_VI5.BOOLS4,419403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_3_VI5.INT1,419404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI5.INT2,419405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_3_VI5.Raw,419406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_3_VI5.AENotify,419596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_4_VI1.BOOLS1,419600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.BOOLS2,419601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.BOOLS3,419602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_4_VI1.BOOLS4,419603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_4_VI1.INT1,419604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI1.INT2,419605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI1.Raw,419606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_4_VI1.AENotify,419796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_4_VI2.BOOLS1,419800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.BOOLS2,419801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.BOOLS3,419802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_4_VI2.BOOLS4,419803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_4_VI2.INT1,419804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI2.INT2,419805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI2.Raw,419806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_4_VI2.AENotify,419996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_4_VI3.BOOLS1,420000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.BOOLS2,420001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.BOOLS3,420002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_4_VI3.BOOLS4,420003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_4_VI3.INT1,420004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI3.INT2,420005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI3.Raw,420006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_4_VI3.AENotify,420196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_4_VI4.BOOLS1,420200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.BOOLS2,420201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.BOOLS3,420202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_4_VI4.BOOLS4,420203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_4_VI4.INT1,420204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI4.INT2,420205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI4.Raw,420206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_4_VI4.AENotify,420396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_4_VI5.BOOLS1,420400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.BOOLS2,420401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.BOOLS3,420402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_4_VI5.BOOLS4,420403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_4_VI5.INT1,420404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI5.INT2,420405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_4_VI5.Raw,420406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_4_VI5.AENotify,420596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_5_VI1.BOOLS1,420600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.BOOLS2,420601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.BOOLS3,420602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_5_VI1.BOOLS4,420603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_5_VI1.INT1,420604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI1.INT2,420605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI1.Raw,420606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_5_VI1.AENotify,420796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_5_VI2.BOOLS1,420800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.BOOLS2,420801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.BOOLS3,420802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_5_VI2.BOOLS4,420803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_5_VI2.INT1,420804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI2.INT2,420805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI2.Raw,420806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_5_VI2.AENotify,420996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_5_VI3.BOOLS1,421000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.BOOLS2,421001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.BOOLS3,421002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_5_VI3.BOOLS4,421003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_5_VI3.INT1,421004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI3.INT2,421005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI3.Raw,421006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_5_VI3.AENotify,421196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_5_VI4.BOOLS1,421200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.BOOLS2,421201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.BOOLS3,421202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_5_VI4.BOOLS4,421203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_5_VI4.INT1,421204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI4.INT2,421205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI4.Raw,421206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_5_VI4.AENotify,421396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_5_VI5.BOOLS1,421400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.BOOLS2,421401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.BOOLS3,421402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_5_VI5.BOOLS4,421403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_5_VI5.INT1,421404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI5.INT2,421405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_5_VI5.Raw,421406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_5_VI5.AENotify,421596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_6_VI1.BOOLS1,421600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.BOOLS2,421601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.BOOLS3,421602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_6_VI1.BOOLS4,421603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_6_VI1.INT1,421604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI1.INT2,421605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI1.Raw,421606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_6_VI1.AENotify,421796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_6_VI2.BOOLS1,421800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.BOOLS2,421801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.BOOLS3,421802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_6_VI2.BOOLS4,421803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_6_VI2.INT1,421804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI2.INT2,421805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI2.Raw,421806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_6_VI2.AENotify,421996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_6_VI3.BOOLS1,422000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.BOOLS2,422001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.BOOLS3,422002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_6_VI3.BOOLS4,422003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_6_VI3.INT1,422004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI3.INT2,422005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI3.Raw,422006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_6_VI3.AENotify,422196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_6_VI4.BOOLS1,422200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.BOOLS2,422201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.BOOLS3,422202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_6_VI4.BOOLS4,422203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_6_VI4.INT1,422204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI4.INT2,422205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI4.Raw,422206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_6_VI4.AENotify,422396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_6_VI5.BOOLS1,422400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.BOOLS2,422401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.BOOLS3,422402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_6_VI5.BOOLS4,422403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_6_VI5.INT1,422404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI5.INT2,422405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_6_VI5.Raw,422406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_6_VI5.AENotify,422596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_7_VI1.BOOLS1,422600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.BOOLS2,422601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.BOOLS3,422602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_7_VI1.BOOLS4,422603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_7_VI1.INT1,422604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI1.INT2,422605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI1.Raw,422606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_7_VI1.AENotify,422796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_7_VI2.BOOLS1,422800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.BOOLS2,422801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.BOOLS3,422802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_7_VI2.BOOLS4,422803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_7_VI2.INT1,422804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI2.INT2,422805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI2.Raw,422806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_7_VI2.AENotify,422996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_7_VI3.BOOLS1,423000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.BOOLS2,423001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.BOOLS3,423002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_7_VI3.BOOLS4,423003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_7_VI3.INT1,423004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI3.INT2,423005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI3.Raw,423006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_7_VI3.AENotify,423196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_7_VI4.BOOLS1,423200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.BOOLS2,423201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.BOOLS3,423202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_7_VI4.BOOLS4,423203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_7_VI4.INT1,423204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI4.INT2,423205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI4.Raw,423206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_7_VI4.AENotify,423396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_7_VI5.BOOLS1,423400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.BOOLS2,423401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.BOOLS3,423402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_7_VI5.BOOLS4,423403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_7_VI5.INT1,423404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI5.INT2,423405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_7_VI5.Raw,423406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_7_VI5.AENotify,423596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_8_VI1.BOOLS1,423600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.BOOLS2,423601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.BOOLS3,423602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_8_VI1.BOOLS4,423603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_8_VI1.INT1,423604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI1.INT2,423605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI1.Raw,423606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_8_VI1.AENotify,423796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_8_VI2.BOOLS1,423800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.BOOLS2,423801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.BOOLS3,423802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_8_VI2.BOOLS4,423803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_8_VI2.INT1,423804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI2.INT2,423805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI2.Raw,423806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_8_VI2.AENotify,423996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_8_VI3.BOOLS1,424000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.BOOLS2,424001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.BOOLS3,424002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_8_VI3.BOOLS4,424003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_8_VI3.INT1,424004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI3.INT2,424005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI3.Raw,424006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_8_VI3.AENotify,424196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_8_VI4.BOOLS1,424200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.BOOLS2,424201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.BOOLS3,424202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_8_VI4.BOOLS4,424203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_8_VI4.INT1,424204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI4.INT2,424205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI4.Raw,424206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_8_VI4.AENotify,424396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_8_VI5.BOOLS1,424400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.BOOLS2,424401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.BOOLS3,424402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_8_VI5.BOOLS4,424403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_8_VI5.INT1,424404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI5.INT2,424405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_8_VI5.Raw,424406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_8_VI5.AENotify,424596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_9_VI1.BOOLS1,424600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.BOOLS2,424601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.BOOLS3,424602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_9_VI1.BOOLS4,424603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_9_VI1.INT1,424604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI1.INT2,424605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI1.Raw,424606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_9_VI1.AENotify,424796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_9_VI2.BOOLS1,424800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.BOOLS2,424801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.BOOLS3,424802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_9_VI2.BOOLS4,424803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_9_VI2.INT1,424804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI2.INT2,424805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI2.Raw,424806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_9_VI2.AENotify,424996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_9_VI3.BOOLS1,425000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.BOOLS2,425001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.BOOLS3,425002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_9_VI3.BOOLS4,425003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_9_VI3.INT1,425004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI3.INT2,425005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI3.Raw,425006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_9_VI3.AENotify,425196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_9_VI4.BOOLS1,425200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.BOOLS2,425201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.BOOLS3,425202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_9_VI4.BOOLS4,425203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_9_VI4.INT1,425204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI4.INT2,425205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI4.Raw,425206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_9_VI4.AENotify,425396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_PMP_0103_9_VI5.BOOLS1,425400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.BOOLS2,425401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.BOOLS3,425402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_PMP_0103_9_VI5.BOOLS4,425403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_PMP_0103_9_VI5.INT1,425404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI5.INT2,425405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_PMP_0103_9_VI5.Raw,425406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_PMP_0103_9_VI5.AENotify,425596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_TT_0111_1_TI.BOOLS1,425600,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.BOOLS2,425601,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.BOOLS3,425602,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_TT_0111_1_TI.BOOLS4,425603,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_TT_0111_1_TI.INT1,425604,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_TT_0111_1_TI.INT2,425605,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_TT_0111_1_TI.Raw,425606,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_TT_0111_1_TI.AENotify,425796,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_TT_0112_1_TI.BOOLS1,425800,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.BOOLS2,425801,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.BOOLS3,425802,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Third Integer of packed Bits" WA3252_TT_0112_1_TI.BOOLS4,425803,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_TT_0112_1_TI.INT1,425804,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_TT_0112_1_TI.INT2,425805,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Spare Integer" WA3252_TT_0112_1_TI.Raw,425806,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw from Input Card" WA3252_TT_0112_1_TI.AENotify,425996,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_FA.BOOLS1,426000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_FA.BOOLS2,426001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_FA.BOOLS3,426002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_FA.BOOLS4,426003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_FA.INT1,426004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_FA.INT2,426005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_FA.AENotify,426032,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_MF.BOOLS1,426036,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_MF.BOOLS2,426037,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_MF.BOOLS3,426038,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_MF.BOOLS4,426039,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_MF.INT1,426040,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_MF.INT2,426041,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_MF.AENotify,426068,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_MY.BOOLS1,426070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_MY.BOOLS2,426071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_MY.BOOLS3,426072,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_MY.BOOLS4,426073,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_MY.INT1,426074,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_MY.INT2,426075,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_MY.AENotify,426102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_UA.BOOLS1,426106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_UA.BOOLS2,426107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_UA.BOOLS3,426108,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_UA.BOOLS4,426109,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_UA.INT1,426110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UA.INT2,426111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UA.AENotify,426138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_UH.BOOLS1,426140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_UH.BOOLS2,426141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_UH.BOOLS3,426142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_UH.BOOLS4,426143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_UH.INT1,426144,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UH.INT2,426145,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UH.AENotify,426172,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_UY.BOOLS1,426176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_UY.BOOLS2,426177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_UY.BOOLS3,426178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_UY.BOOLS4,426179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_UY.INT1,426180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UY.INT2,426181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_UY.AENotify,426208,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_XF.BOOLS1,426210,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_XF.BOOLS2,426211,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_XF.BOOLS3,426212,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_XF.BOOLS4,426213,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_XF.INT1,426214,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_XF.INT2,426215,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_XF.AENotify,426242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1_YA.BOOLS1,426246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_1_YA.BOOLS2,426247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_1_YA.BOOLS3,426248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_1_YA.BOOLS4,426249,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_1_YA.INT1,426250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_YA.INT2,426251,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_1_YA.AENotify,426278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_FA.BOOLS1,426280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_FA.BOOLS2,426281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_FA.BOOLS3,426282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_FA.BOOLS4,426283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_FA.INT1,426284,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_FA.INT2,426285,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_FA.AENotify,426312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_MF.BOOLS1,426316,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_MF.BOOLS2,426317,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_MF.BOOLS3,426318,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_MF.BOOLS4,426319,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_MF.INT1,426320,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_MF.INT2,426321,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_MF.AENotify,426348,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_MY.BOOLS1,426350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_MY.BOOLS2,426351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_MY.BOOLS3,426352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_MY.BOOLS4,426353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_MY.INT1,426354,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_MY.INT2,426355,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_MY.AENotify,426382,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_UA.BOOLS1,426386,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_UA.BOOLS2,426387,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_UA.BOOLS3,426388,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_UA.BOOLS4,426389,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_UA.INT1,426390,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UA.INT2,426391,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UA.AENotify,426418,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_UH.BOOLS1,426420,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_UH.BOOLS2,426421,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_UH.BOOLS3,426422,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_UH.BOOLS4,426423,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_UH.INT1,426424,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UH.INT2,426425,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UH.AENotify,426452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_UY.BOOLS1,426456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_UY.BOOLS2,426457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_UY.BOOLS3,426458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_UY.BOOLS4,426459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_UY.INT1,426460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UY.INT2,426461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_UY.AENotify,426488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_XF.BOOLS1,426490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_XF.BOOLS2,426491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_XF.BOOLS3,426492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_XF.BOOLS4,426493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_XF.INT1,426494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_XF.INT2,426495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_XF.AENotify,426522,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2_YA.BOOLS1,426526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_2_YA.BOOLS2,426527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_2_YA.BOOLS3,426528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_2_YA.BOOLS4,426529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_2_YA.INT1,426530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_YA.INT2,426531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_2_YA.AENotify,426558,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_FA.BOOLS1,426560,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_FA.BOOLS2,426561,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_FA.BOOLS3,426562,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_FA.BOOLS4,426563,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_FA.INT1,426564,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_FA.INT2,426565,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_FA.AENotify,426592,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_MF.BOOLS1,426596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_MF.BOOLS2,426597,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_MF.BOOLS3,426598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_MF.BOOLS4,426599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_MF.INT1,426600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_MF.INT2,426601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_MF.AENotify,426628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_MY.BOOLS1,426630,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_MY.BOOLS2,426631,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_MY.BOOLS3,426632,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_MY.BOOLS4,426633,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_MY.INT1,426634,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_MY.INT2,426635,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_MY.AENotify,426662,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_UA.BOOLS1,426666,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_UA.BOOLS2,426667,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_UA.BOOLS3,426668,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_UA.BOOLS4,426669,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_UA.INT1,426670,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UA.INT2,426671,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UA.AENotify,426698,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_UH.BOOLS1,426700,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_UH.BOOLS2,426701,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_UH.BOOLS3,426702,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_UH.BOOLS4,426703,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_UH.INT1,426704,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UH.INT2,426705,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UH.AENotify,426732,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_UY.BOOLS1,426736,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_UY.BOOLS2,426737,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_UY.BOOLS3,426738,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_UY.BOOLS4,426739,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_UY.INT1,426740,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UY.INT2,426741,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_UY.AENotify,426768,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_XF.BOOLS1,426770,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_XF.BOOLS2,426771,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_XF.BOOLS3,426772,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_XF.BOOLS4,426773,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_XF.INT1,426774,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_XF.INT2,426775,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_XF.AENotify,426802,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3_YA.BOOLS1,426806,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_3_YA.BOOLS2,426807,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_3_YA.BOOLS3,426808,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_3_YA.BOOLS4,426809,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_3_YA.INT1,426810,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_YA.INT2,426811,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_3_YA.AENotify,426838,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_FA.BOOLS1,426840,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_FA.BOOLS2,426841,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_FA.BOOLS3,426842,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_FA.BOOLS4,426843,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_FA.INT1,426844,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_FA.INT2,426845,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_FA.AENotify,426872,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_MF.BOOLS1,426876,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_MF.BOOLS2,426877,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_MF.BOOLS3,426878,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_MF.BOOLS4,426879,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_MF.INT1,426880,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_MF.INT2,426881,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_MF.AENotify,426908,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_MY.BOOLS1,426910,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_MY.BOOLS2,426911,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_MY.BOOLS3,426912,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_MY.BOOLS4,426913,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_MY.INT1,426914,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_MY.INT2,426915,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_MY.AENotify,426942,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_UA.BOOLS1,426946,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_UA.BOOLS2,426947,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_UA.BOOLS3,426948,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_UA.BOOLS4,426949,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_UA.INT1,426950,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UA.INT2,426951,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UA.AENotify,426978,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_UH.BOOLS1,426980,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_UH.BOOLS2,426981,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_UH.BOOLS3,426982,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_UH.BOOLS4,426983,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_UH.INT1,426984,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UH.INT2,426985,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UH.AENotify,427012,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_UY.BOOLS1,427016,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_UY.BOOLS2,427017,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_UY.BOOLS3,427018,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_UY.BOOLS4,427019,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_UY.INT1,427020,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UY.INT2,427021,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_UY.AENotify,427048,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_XF.BOOLS1,427050,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_XF.BOOLS2,427051,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_XF.BOOLS3,427052,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_XF.BOOLS4,427053,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_XF.INT1,427054,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_XF.INT2,427055,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_XF.AENotify,427082,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4_YA.BOOLS1,427086,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_4_YA.BOOLS2,427087,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_4_YA.BOOLS3,427088,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_4_YA.BOOLS4,427089,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_4_YA.INT1,427090,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_YA.INT2,427091,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_4_YA.AENotify,427118,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_FA.BOOLS1,427120,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_FA.BOOLS2,427121,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_FA.BOOLS3,427122,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_FA.BOOLS4,427123,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_FA.INT1,427124,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_FA.INT2,427125,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_FA.AENotify,427152,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_MF.BOOLS1,427156,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_MF.BOOLS2,427157,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_MF.BOOLS3,427158,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_MF.BOOLS4,427159,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_MF.INT1,427160,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_MF.INT2,427161,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_MF.AENotify,427188,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_MY.BOOLS1,427190,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_MY.BOOLS2,427191,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_MY.BOOLS3,427192,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_MY.BOOLS4,427193,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_MY.INT1,427194,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_MY.INT2,427195,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_MY.AENotify,427222,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_UA.BOOLS1,427226,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_UA.BOOLS2,427227,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_UA.BOOLS3,427228,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_UA.BOOLS4,427229,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_UA.INT1,427230,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UA.INT2,427231,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UA.AENotify,427258,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_UH.BOOLS1,427260,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_UH.BOOLS2,427261,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_UH.BOOLS3,427262,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_UH.BOOLS4,427263,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_UH.INT1,427264,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UH.INT2,427265,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UH.AENotify,427292,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_UY.BOOLS1,427296,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_UY.BOOLS2,427297,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_UY.BOOLS3,427298,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_UY.BOOLS4,427299,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_UY.INT1,427300,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UY.INT2,427301,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_UY.AENotify,427328,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_XF.BOOLS1,427330,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_XF.BOOLS2,427331,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_XF.BOOLS3,427332,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_XF.BOOLS4,427333,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_XF.INT1,427334,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_XF.INT2,427335,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_XF.AENotify,427362,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5_YA.BOOLS1,427366,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_5_YA.BOOLS2,427367,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_5_YA.BOOLS3,427368,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_5_YA.BOOLS4,427369,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_5_YA.INT1,427370,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_YA.INT2,427371,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_5_YA.AENotify,427398,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_FA.BOOLS1,427400,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_FA.BOOLS2,427401,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_FA.BOOLS3,427402,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_FA.BOOLS4,427403,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_FA.INT1,427404,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_FA.INT2,427405,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_FA.AENotify,427432,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_MF.BOOLS1,427436,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_MF.BOOLS2,427437,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_MF.BOOLS3,427438,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_MF.BOOLS4,427439,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_MF.INT1,427440,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_MF.INT2,427441,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_MF.AENotify,427468,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_MY.BOOLS1,427470,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_MY.BOOLS2,427471,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_MY.BOOLS3,427472,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_MY.BOOLS4,427473,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_MY.INT1,427474,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_MY.INT2,427475,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_MY.AENotify,427502,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_UA.BOOLS1,427506,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_UA.BOOLS2,427507,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_UA.BOOLS3,427508,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_UA.BOOLS4,427509,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_UA.INT1,427510,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UA.INT2,427511,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UA.AENotify,427538,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_UH.BOOLS1,427540,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_UH.BOOLS2,427541,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_UH.BOOLS3,427542,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_UH.BOOLS4,427543,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_UH.INT1,427544,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UH.INT2,427545,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UH.AENotify,427572,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_UY.BOOLS1,427576,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_UY.BOOLS2,427577,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_UY.BOOLS3,427578,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_UY.BOOLS4,427579,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_UY.INT1,427580,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UY.INT2,427581,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_UY.AENotify,427608,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_XF.BOOLS1,427610,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_XF.BOOLS2,427611,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_XF.BOOLS3,427612,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_XF.BOOLS4,427613,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_XF.INT1,427614,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_XF.INT2,427615,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_XF.AENotify,427642,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6_YA.BOOLS1,427646,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_6_YA.BOOLS2,427647,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_6_YA.BOOLS3,427648,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_6_YA.BOOLS4,427649,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_6_YA.INT1,427650,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_YA.INT2,427651,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_6_YA.AENotify,427678,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_FA.BOOLS1,427680,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_FA.BOOLS2,427681,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_FA.BOOLS3,427682,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_FA.BOOLS4,427683,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_FA.INT1,427684,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_FA.INT2,427685,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_FA.AENotify,427712,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_MF.BOOLS1,427716,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_MF.BOOLS2,427717,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_MF.BOOLS3,427718,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_MF.BOOLS4,427719,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_MF.INT1,427720,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_MF.INT2,427721,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_MF.AENotify,427748,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_MY.BOOLS1,427750,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_MY.BOOLS2,427751,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_MY.BOOLS3,427752,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_MY.BOOLS4,427753,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_MY.INT1,427754,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_MY.INT2,427755,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_MY.AENotify,427782,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_UA.BOOLS1,427786,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_UA.BOOLS2,427787,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_UA.BOOLS3,427788,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_UA.BOOLS4,427789,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_UA.INT1,427790,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UA.INT2,427791,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UA.AENotify,427818,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_UH.BOOLS1,427820,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_UH.BOOLS2,427821,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_UH.BOOLS3,427822,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_UH.BOOLS4,427823,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_UH.INT1,427824,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UH.INT2,427825,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UH.AENotify,427852,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_UY.BOOLS1,427856,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_UY.BOOLS2,427857,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_UY.BOOLS3,427858,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_UY.BOOLS4,427859,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_UY.INT1,427860,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UY.INT2,427861,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_UY.AENotify,427888,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_XF.BOOLS1,427890,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_XF.BOOLS2,427891,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_XF.BOOLS3,427892,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_XF.BOOLS4,427893,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_XF.INT1,427894,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_XF.INT2,427895,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_XF.AENotify,427922,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7_YA.BOOLS1,427926,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_7_YA.BOOLS2,427927,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_7_YA.BOOLS3,427928,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_7_YA.BOOLS4,427929,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_7_YA.INT1,427930,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_YA.INT2,427931,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_7_YA.AENotify,427958,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_FA.BOOLS1,427960,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_FA.BOOLS2,427961,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_FA.BOOLS3,427962,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_FA.BOOLS4,427963,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_FA.INT1,427964,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_FA.INT2,427965,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_FA.AENotify,427992,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_MF.BOOLS1,427996,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_MF.BOOLS2,427997,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_MF.BOOLS3,427998,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_MF.BOOLS4,427999,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_MF.INT1,428000,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_MF.INT2,428001,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_MF.AENotify,428028,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_MY.BOOLS1,428030,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_MY.BOOLS2,428031,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_MY.BOOLS3,428032,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_MY.BOOLS4,428033,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_MY.INT1,428034,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_MY.INT2,428035,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_MY.AENotify,428062,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_UA.BOOLS1,428066,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_UA.BOOLS2,428067,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_UA.BOOLS3,428068,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_UA.BOOLS4,428069,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_UA.INT1,428070,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UA.INT2,428071,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UA.AENotify,428098,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_UH.BOOLS1,428100,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_UH.BOOLS2,428101,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_UH.BOOLS3,428102,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_UH.BOOLS4,428103,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_UH.INT1,428104,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UH.INT2,428105,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UH.AENotify,428132,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_UY.BOOLS1,428136,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_UY.BOOLS2,428137,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_UY.BOOLS3,428138,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_UY.BOOLS4,428139,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_UY.INT1,428140,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UY.INT2,428141,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_UY.AENotify,428168,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_XF.BOOLS1,428170,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_XF.BOOLS2,428171,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_XF.BOOLS3,428172,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_XF.BOOLS4,428173,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_XF.INT1,428174,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_XF.INT2,428175,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_XF.AENotify,428202,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8_YA.BOOLS1,428206,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_8_YA.BOOLS2,428207,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_8_YA.BOOLS3,428208,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_8_YA.BOOLS4,428209,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_8_YA.INT1,428210,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_YA.INT2,428211,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_8_YA.AENotify,428238,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_FA.BOOLS1,428240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_FA.BOOLS2,428241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_FA.BOOLS3,428242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_FA.BOOLS4,428243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_FA.INT1,428244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_FA.INT2,428245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_FA.AENotify,428272,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_MF.BOOLS1,428276,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_MF.BOOLS2,428277,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_MF.BOOLS3,428278,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_MF.BOOLS4,428279,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_MF.INT1,428280,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_MF.INT2,428281,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_MF.AENotify,428308,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_MY.BOOLS1,428310,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_MY.BOOLS2,428311,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_MY.BOOLS3,428312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_MY.BOOLS4,428313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_MY.INT1,428314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_MY.INT2,428315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_MY.AENotify,428342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_UA.BOOLS1,428346,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_UA.BOOLS2,428347,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_UA.BOOLS3,428348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_UA.BOOLS4,428349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_UA.INT1,428350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UA.INT2,428351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UA.AENotify,428378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_UH.BOOLS1,428380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_UH.BOOLS2,428381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_UH.BOOLS3,428382,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_UH.BOOLS4,428383,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_UH.INT1,428384,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UH.INT2,428385,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UH.AENotify,428412,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_UY.BOOLS1,428416,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_UY.BOOLS2,428417,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_UY.BOOLS3,428418,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_UY.BOOLS4,428419,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_UY.INT1,428420,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UY.INT2,428421,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_UY.AENotify,428448,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_XF.BOOLS1,428450,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_XF.BOOLS2,428451,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_XF.BOOLS3,428452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_XF.BOOLS4,428453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_XF.INT1,428454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_XF.INT2,428455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_XF.AENotify,428482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9_YA.BOOLS1,428486,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_AFD_0103_9_YA.BOOLS2,428487,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_AFD_0103_9_YA.BOOLS3,428488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_AFD_0103_9_YA.BOOLS4,428489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_AFD_0103_9_YA.INT1,428490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_YA.INT2,428491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_AFD_0103_9_YA.AENotify,428518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0112_1_JA.BOOLS1,428520,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0112_1_JA.BOOLS2,428521,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0112_1_JA.BOOLS3,428522,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0112_1_JA.BOOLS4,428523,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0112_1_JA.INT1,428524,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_1_JA.INT2,428525,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_1_JA.AENotify,428552,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0112_1_JN1.BOOLS1,428556,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0112_1_JN1.BOOLS2,428557,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0112_1_JN1.BOOLS3,428558,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0112_1_JN1.BOOLS4,428559,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0112_1_JN1.INT1,428560,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_1_JN1.INT2,428561,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_1_JN1.AENotify,428588,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0112_2_JA.BOOLS1,428590,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0112_2_JA.BOOLS2,428591,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0112_2_JA.BOOLS3,428592,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0112_2_JA.BOOLS4,428593,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0112_2_JA.INT1,428594,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_2_JA.INT2,428595,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_2_JA.AENotify,428622,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0112_2_JN1.BOOLS1,428626,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0112_2_JN1.BOOLS2,428627,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0112_2_JN1.BOOLS3,428628,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0112_2_JN1.BOOLS4,428629,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0112_2_JN1.INT1,428630,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_2_JN1.INT2,428631,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0112_2_JN1.AENotify,428658,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0140_1_JA.BOOLS1,428660,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0140_1_JA.BOOLS2,428661,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0140_1_JA.BOOLS3,428662,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0140_1_JA.BOOLS4,428663,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0140_1_JA.INT1,428664,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0140_1_JA.INT2,428665,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0140_1_JA.AENotify,428692,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_ATO_0140_1_XA.BOOLS1,428696,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_ATO_0140_1_XA.BOOLS2,428697,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_ATO_0140_1_XA.BOOLS3,428698,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_ATO_0140_1_XA.BOOLS4,428699,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_ATO_0140_1_XA.INT1,428700,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0140_1_XA.INT2,428701,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_ATO_0140_1_XA.AENotify,428728,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0114_1_XA.BOOLS1,428730,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0114_1_XA.BOOLS2,428731,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0114_1_XA.BOOLS3,428732,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0114_1_XA.BOOLS4,428733,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0114_1_XA.INT1,428734,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_1_XA.INT2,428735,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_1_XA.AENotify,428762,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0114_2_XA.BOOLS1,428766,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0114_2_XA.BOOLS2,428767,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0114_2_XA.BOOLS3,428768,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0114_2_XA.BOOLS4,428769,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0114_2_XA.INT1,428770,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_2_XA.INT2,428771,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_2_XA.AENotify,428798,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0114_3_LH.BOOLS1,428800,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0114_3_LH.BOOLS2,428801,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0114_3_LH.BOOLS3,428802,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0114_3_LH.BOOLS4,428803,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0114_3_LH.INT1,428804,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_3_LH.INT2,428805,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0114_3_LH.AENotify,428832,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1A_MF.BOOLS1,428836,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1A_MF.BOOLS2,428837,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1A_MF.BOOLS3,428838,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1A_MF.BOOLS4,428839,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1A_MF.INT1,428840,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1A_MF.INT2,428841,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1A_MF.AENotify,428868,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1A_XA.BOOLS1,428870,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1A_XA.BOOLS2,428871,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1A_XA.BOOLS3,428872,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1A_XA.BOOLS4,428873,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1A_XA.INT1,428874,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1A_XA.INT2,428875,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1A_XA.AENotify,428902,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1B_MF.BOOLS1,428906,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1B_MF.BOOLS2,428907,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1B_MF.BOOLS3,428908,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1B_MF.BOOLS4,428909,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1B_MF.INT1,428910,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1B_MF.INT2,428911,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1B_MF.AENotify,428938,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1B_XA.BOOLS1,428940,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1B_XA.BOOLS2,428941,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1B_XA.BOOLS3,428942,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1B_XA.BOOLS4,428943,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1B_XA.INT1,428944,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1B_XA.INT2,428945,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1B_XA.AENotify,428972,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1C_MF.BOOLS1,428976,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1C_MF.BOOLS2,428977,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1C_MF.BOOLS3,428978,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1C_MF.BOOLS4,428979,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1C_MF.INT1,428980,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1C_MF.INT2,428981,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1C_MF.AENotify,429008,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1C_XA.BOOLS1,429010,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1C_XA.BOOLS2,429011,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1C_XA.BOOLS3,429012,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1C_XA.BOOLS4,429013,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1C_XA.INT1,429014,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1C_XA.INT2,429015,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1C_XA.AENotify,429042,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1DE_MF.BOOLS1,429046,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1DE_MF.BOOLS2,429047,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1DE_MF.BOOLS3,429048,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1DE_MF.BOOLS4,429049,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1DE_MF.INT1,429050,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1DE_MF.INT2,429051,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1DE_MF.AENotify,429078,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1DE_XA.BOOLS1,429080,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1DE_XA.BOOLS2,429081,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1DE_XA.BOOLS3,429082,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1DE_XA.BOOLS4,429083,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1DE_XA.INT1,429084,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1DE_XA.INT2,429085,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1DE_XA.AENotify,429112,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1FG_MF.BOOLS1,429116,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1FG_MF.BOOLS2,429117,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1FG_MF.BOOLS3,429118,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1FG_MF.BOOLS4,429119,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1FG_MF.INT1,429120,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1FG_MF.INT2,429121,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1FG_MF.AENotify,429148,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1FG_XA.BOOLS1,429150,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1FG_XA.BOOLS2,429151,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1FG_XA.BOOLS3,429152,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1FG_XA.BOOLS4,429153,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1FG_XA.INT1,429154,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1FG_XA.INT2,429155,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1FG_XA.AENotify,429182,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1H_MF.BOOLS1,429186,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1H_MF.BOOLS2,429187,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1H_MF.BOOLS3,429188,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1H_MF.BOOLS4,429189,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1H_MF.INT1,429190,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1H_MF.INT2,429191,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1H_MF.AENotify,429218,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1H_XA.BOOLS1,429220,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1H_XA.BOOLS2,429221,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1H_XA.BOOLS3,429222,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1H_XA.BOOLS4,429223,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1H_XA.INT1,429224,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1H_XA.INT2,429225,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1H_XA.AENotify,429252,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1I_MF.BOOLS1,429256,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1I_MF.BOOLS2,429257,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1I_MF.BOOLS3,429258,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1I_MF.BOOLS4,429259,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1I_MF.INT1,429260,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1I_MF.INT2,429261,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1I_MF.AENotify,429288,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1I_XA.BOOLS1,429290,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1I_XA.BOOLS2,429291,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1I_XA.BOOLS3,429292,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1I_XA.BOOLS4,429293,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1I_XA.INT1,429294,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1I_XA.INT2,429295,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1I_XA.AENotify,429322,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1J_MF.BOOLS1,429326,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1J_MF.BOOLS2,429327,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1J_MF.BOOLS3,429328,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1J_MF.BOOLS4,429329,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1J_MF.INT1,429330,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1J_MF.INT2,429331,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1J_MF.AENotify,429358,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1J_XA.BOOLS1,429360,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1J_XA.BOOLS2,429361,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1J_XA.BOOLS3,429362,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1J_XA.BOOLS4,429363,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1J_XA.INT1,429364,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1J_XA.INT2,429365,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1J_XA.AENotify,429392,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1K_MF.BOOLS1,429396,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1K_MF.BOOLS2,429397,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1K_MF.BOOLS3,429398,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1K_MF.BOOLS4,429399,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1K_MF.INT1,429400,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1K_MF.INT2,429401,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1K_MF.AENotify,429428,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_1K_XA.BOOLS1,429430,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_1K_XA.BOOLS2,429431,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_1K_XA.BOOLS3,429432,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_1K_XA.BOOLS4,429433,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_1K_XA.INT1,429434,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1K_XA.INT2,429435,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_1K_XA.AENotify,429462,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_LH.BOOLS1,429466,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_LH.BOOLS2,429467,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_LH.BOOLS3,429468,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_LH.BOOLS4,429469,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_LH.INT1,429470,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_LH.INT2,429471,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_LH.AENotify,429498,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_MF1.BOOLS1,429500,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_MF1.BOOLS2,429501,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_MF1.BOOLS3,429502,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_MF1.BOOLS4,429503,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_MF1.INT1,429504,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF1.INT2,429505,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF1.AENotify,429532,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_MF2.BOOLS1,429536,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_MF2.BOOLS2,429537,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_MF2.BOOLS3,429538,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_MF2.BOOLS4,429539,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_MF2.INT1,429540,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF2.INT2,429541,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF2.AENotify,429568,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_MF3.BOOLS1,429570,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_MF3.BOOLS2,429571,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_MF3.BOOLS3,429572,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_MF3.BOOLS4,429573,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_MF3.INT1,429574,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF3.INT2,429575,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF3.AENotify,429602,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_MF4.BOOLS1,429606,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_MF4.BOOLS2,429607,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_MF4.BOOLS3,429608,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_MF4.BOOLS4,429609,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_MF4.INT1,429610,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF4.INT2,429611,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_MF4.AENotify,429638,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2A_XA.BOOLS1,429640,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2A_XA.BOOLS2,429641,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2A_XA.BOOLS3,429642,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2A_XA.BOOLS4,429643,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2A_XA.INT1,429644,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_XA.INT2,429645,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2A_XA.AENotify,429672,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_LH.BOOLS1,429676,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_LH.BOOLS2,429677,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_LH.BOOLS3,429678,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_LH.BOOLS4,429679,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_LH.INT1,429680,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_LH.INT2,429681,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_LH.AENotify,429708,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_MF1.BOOLS1,429710,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_MF1.BOOLS2,429711,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_MF1.BOOLS3,429712,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_MF1.BOOLS4,429713,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_MF1.INT1,429714,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF1.INT2,429715,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF1.AENotify,429742,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_MF2.BOOLS1,429746,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_MF2.BOOLS2,429747,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_MF2.BOOLS3,429748,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_MF2.BOOLS4,429749,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_MF2.INT1,429750,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF2.INT2,429751,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF2.AENotify,429778,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_MF3.BOOLS1,429780,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_MF3.BOOLS2,429781,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_MF3.BOOLS3,429782,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_MF3.BOOLS4,429783,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_MF3.INT1,429784,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF3.INT2,429785,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF3.AENotify,429812,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_MF4.BOOLS1,429816,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_MF4.BOOLS2,429817,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_MF4.BOOLS3,429818,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_MF4.BOOLS4,429819,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_MF4.INT1,429820,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF4.INT2,429821,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_MF4.AENotify,429848,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_2B_XA.BOOLS1,429850,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_2B_XA.BOOLS2,429851,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_2B_XA.BOOLS3,429852,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_2B_XA.BOOLS4,429853,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_2B_XA.INT1,429854,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_XA.INT2,429855,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_2B_XA.AENotify,429882,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_3A_MF.BOOLS1,429886,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_3A_MF.BOOLS2,429887,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_3A_MF.BOOLS3,429888,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_3A_MF.BOOLS4,429889,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_3A_MF.INT1,429890,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_3A_MF.INT2,429891,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_3A_MF.AENotify,429918,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0117_3B_XF.BOOLS1,429920,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0117_3B_XF.BOOLS2,429921,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0117_3B_XF.BOOLS3,429922,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0117_3B_XF.BOOLS4,429923,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0117_3B_XF.INT1,429924,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_3B_XF.INT2,429925,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0117_3B_XF.AENotify,429952,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_1_LH1.BOOLS1,429956,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_1_LH1.BOOLS2,429957,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_1_LH1.BOOLS3,429958,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_1_LH1.BOOLS4,429959,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_1_LH1.INT1,429960,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_LH1.INT2,429961,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_LH1.AENotify,429988,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_1_LH2.BOOLS1,429990,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_1_LH2.BOOLS2,429991,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_1_LH2.BOOLS3,429992,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_1_LH2.BOOLS4,429993,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_1_LH2.INT1,429994,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_LH2.INT2,429995,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_LH2.AENotify,430022,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_1_XA.BOOLS1,430026,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_1_XA.BOOLS2,430027,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_1_XA.BOOLS3,430028,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_1_XA.BOOLS4,430029,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_1_XA.INT1,430030,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_XA.INT2,430031,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1_XA.AENotify,430058,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_1A_MF.BOOLS1,430060,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_1A_MF.BOOLS2,430061,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_1A_MF.BOOLS3,430062,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_1A_MF.BOOLS4,430063,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_1A_MF.INT1,430064,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1A_MF.INT2,430065,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1A_MF.AENotify,430092,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_1B_MF.BOOLS1,430096,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_1B_MF.BOOLS2,430097,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_1B_MF.BOOLS3,430098,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_1B_MF.BOOLS4,430099,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_1B_MF.INT1,430100,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1B_MF.INT2,430101,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_1B_MF.AENotify,430128,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_2_LH1.BOOLS1,430130,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_2_LH1.BOOLS2,430131,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_2_LH1.BOOLS3,430132,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_2_LH1.BOOLS4,430133,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_2_LH1.INT1,430134,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_LH1.INT2,430135,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_LH1.AENotify,430162,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_2_LH2.BOOLS1,430166,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_2_LH2.BOOLS2,430167,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_2_LH2.BOOLS3,430168,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_2_LH2.BOOLS4,430169,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_2_LH2.INT1,430170,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_LH2.INT2,430171,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_LH2.AENotify,430198,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_2_XA.BOOLS1,430200,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_2_XA.BOOLS2,430201,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_2_XA.BOOLS3,430202,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_2_XA.BOOLS4,430203,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_2_XA.INT1,430204,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_XA.INT2,430205,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2_XA.AENotify,430232,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_2A_MF.BOOLS1,430236,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_2A_MF.BOOLS2,430237,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_2A_MF.BOOLS3,430238,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_2A_MF.BOOLS4,430239,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_2A_MF.INT1,430240,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2A_MF.INT2,430241,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2A_MF.AENotify,430268,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_CP_0118_2B_MF.BOOLS1,430270,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_CP_0118_2B_MF.BOOLS2,430271,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_CP_0118_2B_MF.BOOLS3,430272,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_CP_0118_2B_MF.BOOLS4,430273,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_CP_0118_2B_MF.INT1,430274,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2B_MF.INT2,430275,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_CP_0118_2B_MF.AENotify,430302,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2A_WH.BOOLS1,430306,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FCV_0113_2A_WH.BOOLS2,430307,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FCV_0113_2A_WH.BOOLS3,430308,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FCV_0113_2A_WH.BOOLS4,430309,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FCV_0113_2A_WH.INT1,430310,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FCV_0113_2A_WH.INT2,430311,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FCV_0113_2A_WH.AENotify,430338,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2B_WH.BOOLS1,430340,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FCV_0113_2B_WH.BOOLS2,430341,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FCV_0113_2B_WH.BOOLS3,430342,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FCV_0113_2B_WH.BOOLS4,430343,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FCV_0113_2B_WH.INT1,430344,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FCV_0113_2B_WH.INT2,430345,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FCV_0113_2B_WH.AENotify,430372,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FLT_0112_1_XA.BOOLS1,430376,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FLT_0112_1_XA.BOOLS2,430377,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FLT_0112_1_XA.BOOLS3,430378,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FLT_0112_1_XA.BOOLS4,430379,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FLT_0112_1_XA.INT1,430380,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FLT_0112_1_XA.INT2,430381,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FLT_0112_1_XA.AENotify,430408,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FLT_0112_2_XA.BOOLS1,430410,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FLT_0112_2_XA.BOOLS2,430411,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FLT_0112_2_XA.BOOLS3,430412,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FLT_0112_2_XA.BOOLS4,430413,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FLT_0112_2_XA.INT1,430414,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FLT_0112_2_XA.INT2,430415,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FLT_0112_2_XA.AENotify,430442,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_1A_WH.BOOLS1,430446,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0102_1A_WH.BOOLS2,430447,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0102_1A_WH.BOOLS3,430448,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0102_1A_WH.BOOLS4,430449,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0102_1A_WH.INT1,430450,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_1A_WH.INT2,430451,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_1A_WH.AENotify,430478,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_1B_WH.BOOLS1,430480,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0102_1B_WH.BOOLS2,430481,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0102_1B_WH.BOOLS3,430482,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0102_1B_WH.BOOLS4,430483,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0102_1B_WH.INT1,430484,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_1B_WH.INT2,430485,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_1B_WH.AENotify,430512,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_2A_WH.BOOLS1,430516,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0102_2A_WH.BOOLS2,430517,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0102_2A_WH.BOOLS3,430518,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0102_2A_WH.BOOLS4,430519,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0102_2A_WH.INT1,430520,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_2A_WH.INT2,430521,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_2A_WH.AENotify,430548,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_2B_WH.BOOLS1,430550,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0102_2B_WH.BOOLS2,430551,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0102_2B_WH.BOOLS3,430552,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0102_2B_WH.BOOLS4,430553,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0102_2B_WH.INT1,430554,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_2B_WH.INT2,430555,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0102_2B_WH.AENotify,430582,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1A_WH.BOOLS1,430586,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_1A_WH.BOOLS2,430587,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_1A_WH.BOOLS3,430588,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_1A_WH.BOOLS4,430589,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_1A_WH.INT1,430590,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1A_WH.INT2,430591,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1A_WH.AENotify,430618,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1B_ZF.BOOLS1,430620,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_1B_ZF.BOOLS2,430621,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_1B_ZF.BOOLS3,430622,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_1B_ZF.BOOLS4,430623,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_1B_ZF.INT1,430624,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1B_ZF.INT2,430625,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1B_ZF.AENotify,430652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1B_ZF2.BOOLS1,430656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_1B_ZF2.BOOLS2,430657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_1B_ZF2.BOOLS3,430658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_1B_ZF2.BOOLS4,430659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_1B_ZF2.INT1,430660,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1B_ZF2.INT2,430661,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1B_ZF2.AENotify,430688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1C_WH.BOOLS1,430690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_1C_WH.BOOLS2,430691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_1C_WH.BOOLS3,430692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_1C_WH.BOOLS4,430693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_1C_WH.INT1,430694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1C_WH.INT2,430695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_1C_WH.AENotify,430722,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2A_WH.BOOLS1,430726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_2A_WH.BOOLS2,430727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_2A_WH.BOOLS3,430728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_2A_WH.BOOLS4,430729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_2A_WH.INT1,430730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2A_WH.INT2,430731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2A_WH.AENotify,430758,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2B_ZF.BOOLS1,430760,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_2B_ZF.BOOLS2,430761,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_2B_ZF.BOOLS3,430762,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_2B_ZF.BOOLS4,430763,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_2B_ZF.INT1,430764,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2B_ZF.INT2,430765,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2B_ZF.AENotify,430792,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2B_ZF2.BOOLS1,430796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_2B_ZF2.BOOLS2,430797,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_2B_ZF2.BOOLS3,430798,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_2B_ZF2.BOOLS4,430799,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_2B_ZF2.INT1,430800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2B_ZF2.INT2,430801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2B_ZF2.AENotify,430828,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2C_WH.BOOLS1,430830,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_2C_WH.BOOLS2,430831,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_2C_WH.BOOLS3,430832,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_2C_WH.BOOLS4,430833,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_2C_WH.INT1,430834,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2C_WH.INT2,430835,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_2C_WH.AENotify,430862,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3A_WH.BOOLS1,430866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3A_WH.BOOLS2,430867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3A_WH.BOOLS3,430868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3A_WH.BOOLS4,430869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3A_WH.INT1,430870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3A_WH.INT2,430871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3A_WH.AENotify,430898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3B_ZF.BOOLS1,430900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3B_ZF.BOOLS2,430901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3B_ZF.BOOLS3,430902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3B_ZF.BOOLS4,430903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3B_ZF.INT1,430904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF.INT2,430905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF.AENotify,430932,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3B_ZF3.BOOLS1,430936,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3B_ZF3.BOOLS2,430937,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3B_ZF3.BOOLS3,430938,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3B_ZF3.BOOLS4,430939,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3B_ZF3.INT1,430940,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF3.INT2,430941,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF3.AENotify,430968,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3B_ZF4.BOOLS1,430970,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3B_ZF4.BOOLS2,430971,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3B_ZF4.BOOLS3,430972,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3B_ZF4.BOOLS4,430973,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3B_ZF4.INT1,430974,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF4.INT2,430975,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3B_ZF4.AENotify,431002,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3C_WH.BOOLS1,431006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3C_WH.BOOLS2,431007,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3C_WH.BOOLS3,431008,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3C_WH.BOOLS4,431009,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3C_WH.INT1,431010,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3C_WH.INT2,431011,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3C_WH.AENotify,431038,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3D_WH.BOOLS1,431040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_3D_WH.BOOLS2,431041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_3D_WH.BOOLS3,431042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_3D_WH.BOOLS4,431043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_3D_WH.INT1,431044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3D_WH.INT2,431045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_3D_WH.AENotify,431072,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4A_WH.BOOLS1,431076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4A_WH.BOOLS2,431077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4A_WH.BOOLS3,431078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4A_WH.BOOLS4,431079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4A_WH.INT1,431080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4A_WH.INT2,431081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4A_WH.AENotify,431108,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4B_ZF.BOOLS1,431110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4B_ZF.BOOLS2,431111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4B_ZF.BOOLS3,431112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4B_ZF.BOOLS4,431113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4B_ZF.INT1,431114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF.INT2,431115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF.AENotify,431142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4B_ZF3.BOOLS1,431146,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4B_ZF3.BOOLS2,431147,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4B_ZF3.BOOLS3,431148,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4B_ZF3.BOOLS4,431149,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4B_ZF3.INT1,431150,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF3.INT2,431151,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF3.AENotify,431178,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4B_ZF4.BOOLS1,431180,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4B_ZF4.BOOLS2,431181,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4B_ZF4.BOOLS3,431182,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4B_ZF4.BOOLS4,431183,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4B_ZF4.INT1,431184,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF4.INT2,431185,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4B_ZF4.AENotify,431212,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4C_WH.BOOLS1,431216,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4C_WH.BOOLS2,431217,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4C_WH.BOOLS3,431218,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4C_WH.BOOLS4,431219,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4C_WH.INT1,431220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4C_WH.INT2,431221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4C_WH.AENotify,431248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4D_WH.BOOLS1,431250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_4D_WH.BOOLS2,431251,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_4D_WH.BOOLS3,431252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_4D_WH.BOOLS4,431253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_4D_WH.INT1,431254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4D_WH.INT2,431255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_4D_WH.AENotify,431282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5A_WH.BOOLS1,431286,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5A_WH.BOOLS2,431287,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5A_WH.BOOLS3,431288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5A_WH.BOOLS4,431289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5A_WH.INT1,431290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5A_WH.INT2,431291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5A_WH.AENotify,431318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5B_ZF.BOOLS1,431320,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5B_ZF.BOOLS2,431321,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5B_ZF.BOOLS3,431322,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5B_ZF.BOOLS4,431323,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5B_ZF.INT1,431324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF.INT2,431325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF.AENotify,431352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5B_ZF3.BOOLS1,431356,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5B_ZF3.BOOLS2,431357,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5B_ZF3.BOOLS3,431358,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5B_ZF3.BOOLS4,431359,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5B_ZF3.INT1,431360,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF3.INT2,431361,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF3.AENotify,431388,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5B_ZF4.BOOLS1,431390,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5B_ZF4.BOOLS2,431391,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5B_ZF4.BOOLS3,431392,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5B_ZF4.BOOLS4,431393,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5B_ZF4.INT1,431394,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF4.INT2,431395,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5B_ZF4.AENotify,431422,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5C_WH.BOOLS1,431426,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5C_WH.BOOLS2,431427,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5C_WH.BOOLS3,431428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5C_WH.BOOLS4,431429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5C_WH.INT1,431430,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5C_WH.INT2,431431,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5C_WH.AENotify,431458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5D_WH.BOOLS1,431460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_5D_WH.BOOLS2,431461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_5D_WH.BOOLS3,431462,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_5D_WH.BOOLS4,431463,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_5D_WH.INT1,431464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5D_WH.INT2,431465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_5D_WH.AENotify,431492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6A_WH.BOOLS1,431496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6A_WH.BOOLS2,431497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6A_WH.BOOLS3,431498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6A_WH.BOOLS4,431499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6A_WH.INT1,431500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6A_WH.INT2,431501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6A_WH.AENotify,431528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6B_ZF.BOOLS1,431530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6B_ZF.BOOLS2,431531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6B_ZF.BOOLS3,431532,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6B_ZF.BOOLS4,431533,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6B_ZF.INT1,431534,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF.INT2,431535,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF.AENotify,431562,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6B_ZF3.BOOLS1,431566,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6B_ZF3.BOOLS2,431567,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6B_ZF3.BOOLS3,431568,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6B_ZF3.BOOLS4,431569,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6B_ZF3.INT1,431570,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF3.INT2,431571,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF3.AENotify,431598,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6B_ZF4.BOOLS1,431600,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6B_ZF4.BOOLS2,431601,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6B_ZF4.BOOLS3,431602,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6B_ZF4.BOOLS4,431603,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6B_ZF4.INT1,431604,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF4.INT2,431605,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6B_ZF4.AENotify,431632,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6C_WH.BOOLS1,431636,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6C_WH.BOOLS2,431637,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6C_WH.BOOLS3,431638,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6C_WH.BOOLS4,431639,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6C_WH.INT1,431640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6C_WH.INT2,431641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6C_WH.AENotify,431668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6D_WH.BOOLS1,431670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_6D_WH.BOOLS2,431671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_6D_WH.BOOLS3,431672,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_6D_WH.BOOLS4,431673,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_6D_WH.INT1,431674,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6D_WH.INT2,431675,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_6D_WH.AENotify,431702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7A_WH.BOOLS1,431706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7A_WH.BOOLS2,431707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7A_WH.BOOLS3,431708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7A_WH.BOOLS4,431709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7A_WH.INT1,431710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7A_WH.INT2,431711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7A_WH.AENotify,431738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7B_ZF.BOOLS1,431740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7B_ZF.BOOLS2,431741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7B_ZF.BOOLS3,431742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7B_ZF.BOOLS4,431743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7B_ZF.INT1,431744,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF.INT2,431745,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF.AENotify,431772,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7B_ZF3.BOOLS1,431776,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7B_ZF3.BOOLS2,431777,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7B_ZF3.BOOLS3,431778,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7B_ZF3.BOOLS4,431779,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7B_ZF3.INT1,431780,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF3.INT2,431781,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF3.AENotify,431808,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7B_ZF4.BOOLS1,431810,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7B_ZF4.BOOLS2,431811,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7B_ZF4.BOOLS3,431812,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7B_ZF4.BOOLS4,431813,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7B_ZF4.INT1,431814,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF4.INT2,431815,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7B_ZF4.AENotify,431842,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7C_WH.BOOLS1,431846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7C_WH.BOOLS2,431847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7C_WH.BOOLS3,431848,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7C_WH.BOOLS4,431849,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7C_WH.INT1,431850,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7C_WH.INT2,431851,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7C_WH.AENotify,431878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7D_WH.BOOLS1,431880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_7D_WH.BOOLS2,431881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_7D_WH.BOOLS3,431882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_7D_WH.BOOLS4,431883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_7D_WH.INT1,431884,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7D_WH.INT2,431885,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_7D_WH.AENotify,431912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8A_WH.BOOLS1,431916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8A_WH.BOOLS2,431917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8A_WH.BOOLS3,431918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8A_WH.BOOLS4,431919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8A_WH.INT1,431920,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8A_WH.INT2,431921,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8A_WH.AENotify,431948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8B_ZF.BOOLS1,431950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8B_ZF.BOOLS2,431951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8B_ZF.BOOLS3,431952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8B_ZF.BOOLS4,431953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8B_ZF.INT1,431954,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF.INT2,431955,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF.AENotify,431982,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8B_ZF3.BOOLS1,431986,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8B_ZF3.BOOLS2,431987,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8B_ZF3.BOOLS3,431988,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8B_ZF3.BOOLS4,431989,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8B_ZF3.INT1,431990,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF3.INT2,431991,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF3.AENotify,432018,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8B_ZF4.BOOLS1,432020,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8B_ZF4.BOOLS2,432021,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8B_ZF4.BOOLS3,432022,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8B_ZF4.BOOLS4,432023,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8B_ZF4.INT1,432024,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF4.INT2,432025,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8B_ZF4.AENotify,432052,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8C_WH.BOOLS1,432056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8C_WH.BOOLS2,432057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8C_WH.BOOLS3,432058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8C_WH.BOOLS4,432059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8C_WH.INT1,432060,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8C_WH.INT2,432061,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8C_WH.AENotify,432088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8D_WH.BOOLS1,432090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_8D_WH.BOOLS2,432091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_8D_WH.BOOLS3,432092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_8D_WH.BOOLS4,432093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_8D_WH.INT1,432094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8D_WH.INT2,432095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_8D_WH.AENotify,432122,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9A_WH.BOOLS1,432126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_9A_WH.BOOLS2,432127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_9A_WH.BOOLS3,432128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_9A_WH.BOOLS4,432129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_9A_WH.INT1,432130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9A_WH.INT2,432131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9A_WH.AENotify,432158,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9B_ZF.BOOLS1,432160,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_9B_ZF.BOOLS2,432161,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_9B_ZF.BOOLS3,432162,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_9B_ZF.BOOLS4,432163,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_9B_ZF.INT1,432164,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9B_ZF.INT2,432165,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9B_ZF.AENotify,432192,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9B_ZF2.BOOLS1,432196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_9B_ZF2.BOOLS2,432197,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_9B_ZF2.BOOLS3,432198,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_9B_ZF2.BOOLS4,432199,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_9B_ZF2.INT1,432200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9B_ZF2.INT2,432201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9B_ZF2.AENotify,432228,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9C_WH.BOOLS1,432230,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0103_9C_WH.BOOLS2,432231,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0103_9C_WH.BOOLS3,432232,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0103_9C_WH.BOOLS4,432233,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0103_9C_WH.INT1,432234,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9C_WH.INT2,432235,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0103_9C_WH.AENotify,432262,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2A_WH.BOOLS1,432266,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0113_2A_WH.BOOLS2,432267,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0113_2A_WH.BOOLS3,432268,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0113_2A_WH.BOOLS4,432269,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0113_2A_WH.INT1,432270,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2A_WH.INT2,432271,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2A_WH.AENotify,432298,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2B_WH.BOOLS1,432300,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0113_2B_WH.BOOLS2,432301,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0113_2B_WH.BOOLS3,432302,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0113_2B_WH.BOOLS4,432303,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0113_2B_WH.INT1,432304,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2B_WH.INT2,432305,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2B_WH.AENotify,432332,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2C_WH.BOOLS1,432336,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0113_2C_WH.BOOLS2,432337,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0113_2C_WH.BOOLS3,432338,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0113_2C_WH.BOOLS4,432339,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0113_2C_WH.INT1,432340,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2C_WH.INT2,432341,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2C_WH.AENotify,432368,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2D_WH.BOOLS1,432370,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_FV_0113_2D_WH.BOOLS2,432371,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_FV_0113_2D_WH.BOOLS3,432372,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_FV_0113_2D_WH.BOOLS4,432373,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_FV_0113_2D_WH.INT1,432374,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2D_WH.INT2,432375,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_FV_0113_2D_WH.AENotify,432402,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_LL.BOOLS1,432406,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_LL.BOOLS2,432407,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_LL.BOOLS3,432408,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_LL.BOOLS4,432409,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_LL.INT1,432410,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_LL.INT2,432411,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_LL.AENotify,432438,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_PL.BOOLS1,432440,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_PL.BOOLS2,432441,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_PL.BOOLS3,432442,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_PL.BOOLS4,432443,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_PL.INT1,432444,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_PL.INT2,432445,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_PL.AENotify,432472,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_SH.BOOLS1,432476,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_SH.BOOLS2,432477,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_SH.BOOLS3,432478,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_SH.BOOLS4,432479,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_SH.INT1,432480,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_SH.INT2,432481,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_SH.AENotify,432508,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_TH.BOOLS1,432510,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_TH.BOOLS2,432511,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_TH.BOOLS3,432512,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_TH.BOOLS4,432513,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_TH.INT1,432514,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_TH.INT2,432515,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_TH.AENotify,432542,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_XA1.BOOLS1,432546,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_XA1.BOOLS2,432547,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_XA1.BOOLS3,432548,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_XA1.BOOLS4,432549,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_XA1.INT1,432550,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_XA1.INT2,432551,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_XA1.AENotify,432578,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_GEN_0131_1_XA2.BOOLS1,432580,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_GEN_0131_1_XA2.BOOLS2,432581,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_GEN_0131_1_XA2.BOOLS3,432582,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_GEN_0131_1_XA2.BOOLS4,432583,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_GEN_0131_1_XA2.INT1,432584,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_XA2.INT2,432585,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_GEN_0131_1_XA2.AENotify,432612,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_FA.BOOLS1,432616,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_FA.BOOLS2,432617,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_FA.BOOLS3,432618,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_FA.BOOLS4,432619,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_FA.INT1,432620,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_FA.INT2,432621,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_FA.AENotify,432648,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_FH.BOOLS1,432650,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_FH.BOOLS2,432651,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_FH.BOOLS3,432652,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_FH.BOOLS4,432653,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_FH.INT1,432654,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_FH.INT2,432655,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_FH.AENotify,432682,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_PH.BOOLS1,432686,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_PH.BOOLS2,432687,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_PH.BOOLS3,432688,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_PH.BOOLS4,432689,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_PH.INT1,432690,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_PH.INT2,432691,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_PH.AENotify,432718,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_TH1.BOOLS1,432720,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_TH1.BOOLS2,432721,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_TH1.BOOLS3,432722,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_TH1.BOOLS4,432723,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_TH1.INT1,432724,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH1.INT2,432725,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH1.AENotify,432752,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_TH2.BOOLS1,432756,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_TH2.BOOLS2,432757,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_TH2.BOOLS3,432758,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_TH2.BOOLS4,432759,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_TH2.INT1,432760,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH2.INT2,432761,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH2.AENotify,432788,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_TH3.BOOLS1,432790,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_TH3.BOOLS2,432791,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_TH3.BOOLS3,432792,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_TH3.BOOLS4,432793,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_TH3.INT1,432794,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH3.INT2,432795,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TH3.AENotify,432822,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_TL1.BOOLS1,432826,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_TL1.BOOLS2,432827,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_TL1.BOOLS3,432828,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_TL1.BOOLS4,432829,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_TL1.INT1,432830,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TL1.INT2,432831,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TL1.AENotify,432858,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_TL2.BOOLS1,432860,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_TL2.BOOLS2,432861,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_TL2.BOOLS3,432862,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_TL2.BOOLS4,432863,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_TL2.INT1,432864,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TL2.INT2,432865,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_TL2.AENotify,432892,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA1.BOOLS1,432896,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA1.BOOLS2,432897,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA1.BOOLS3,432898,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA1.BOOLS4,432899,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA1.INT1,432900,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA1.INT2,432901,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA1.AENotify,432928,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA2.BOOLS1,432930,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA2.BOOLS2,432931,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA2.BOOLS3,432932,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA2.BOOLS4,432933,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA2.INT1,432934,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA2.INT2,432935,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA2.AENotify,432962,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA3.BOOLS1,432966,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA3.BOOLS2,432967,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA3.BOOLS3,432968,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA3.BOOLS4,432969,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA3.INT1,432970,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA3.INT2,432971,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA3.AENotify,432998,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA4.BOOLS1,433000,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA4.BOOLS2,433001,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA4.BOOLS3,433002,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA4.BOOLS4,433003,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA4.INT1,433004,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA4.INT2,433005,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA4.AENotify,433032,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA5.BOOLS1,433036,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA5.BOOLS2,433037,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA5.BOOLS3,433038,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA5.BOOLS4,433039,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA5.INT1,433040,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA5.INT2,433041,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA5.AENotify,433068,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA6.BOOLS1,433070,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA6.BOOLS2,433071,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA6.BOOLS3,433072,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA6.BOOLS4,433073,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA6.INT1,433074,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA6.INT2,433075,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA6.AENotify,433102,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA7.BOOLS1,433106,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA7.BOOLS2,433107,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA7.BOOLS3,433108,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA7.BOOLS4,433109,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA7.INT1,433110,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA7.INT2,433111,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA7.AENotify,433138,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA8.BOOLS1,433140,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA8.BOOLS2,433141,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA8.BOOLS3,433142,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA8.BOOLS4,433143,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA8.INT1,433144,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA8.INT2,433145,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA8.AENotify,433172,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA9.BOOLS1,433176,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA9.BOOLS2,433177,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA9.BOOLS3,433178,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA9.BOOLS4,433179,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA9.INT1,433180,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA9.INT2,433181,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA9.AENotify,433208,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA10.BOOLS1,433210,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA10.BOOLS2,433211,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA10.BOOLS3,433212,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA10.BOOLS4,433213,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA10.INT1,433214,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA10.INT2,433215,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA10.AENotify,433242,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA11.BOOLS1,433246,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA11.BOOLS2,433247,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA11.BOOLS3,433248,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA11.BOOLS4,433249,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA11.INT1,433250,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA11.INT2,433251,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA11.AENotify,433278,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_HCP_001_1_XA12.BOOLS1,433280,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_HCP_001_1_XA12.BOOLS2,433281,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_HCP_001_1_XA12.BOOLS3,433282,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_HCP_001_1_XA12.BOOLS4,433283,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_HCP_001_1_XA12.INT1,433284,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA12.INT2,433285,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_HCP_001_1_XA12.AENotify,433312,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_LSH_0113_1_LH.BOOLS1,433316,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_LSH_0113_1_LH.BOOLS2,433317,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_LSH_0113_1_LH.BOOLS3,433318,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_LSH_0113_1_LH.BOOLS4,433319,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_LSH_0113_1_LH.INT1,433320,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_LSH_0113_1_LH.INT2,433321,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_LSH_0113_1_LH.AENotify,433348,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_LSH_0113_2_LH.BOOLS1,433350,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_LSH_0113_2_LH.BOOLS2,433351,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_LSH_0113_2_LH.BOOLS3,433352,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_LSH_0113_2_LH.BOOLS4,433353,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_LSH_0113_2_LH.INT1,433354,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_LSH_0113_2_LH.INT2,433355,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_LSH_0113_2_LH.AENotify,433382,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_NET_001_1_JA.BOOLS1,433386,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_NET_001_1_JA.BOOLS2,433387,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_NET_001_1_JA.BOOLS3,433388,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_NET_001_1_JA.BOOLS4,433389,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_NET_001_1_JA.INT1,433390,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_NET_001_1_JA.INT2,433391,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_NET_001_1_JA.AENotify,433418,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_NET_001_1_ZS.BOOLS1,433420,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_NET_001_1_ZS.BOOLS2,433421,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_NET_001_1_ZS.BOOLS3,433422,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_NET_001_1_ZS.BOOLS4,433423,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_NET_001_1_ZS.INT1,433424,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_NET_001_1_ZS.INT2,433425,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_NET_001_1_ZS.AENotify,433452,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PFC_0112_INHIBIT.BOOLS1,433456,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PFC_0112_INHIBIT.BOOLS2,433457,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PFC_0112_INHIBIT.BOOLS3,433458,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PFC_0112_INHIBIT.BOOLS4,433459,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PFC_0112_INHIBIT.INT1,433460,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PFC_0112_INHIBIT.INT2,433461,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PFC_0112_INHIBIT.AENotify,433488,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0102_1_PL.BOOLS1,433490,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PIT_0102_1_PL.BOOLS2,433491,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PIT_0102_1_PL.BOOLS3,433492,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PIT_0102_1_PL.BOOLS4,433493,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PIT_0102_1_PL.INT1,433494,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PIT_0102_1_PL.INT2,433495,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PIT_0102_1_PL.AENotify,433522,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PIT_0102_2_PL.BOOLS1,433526,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PIT_0102_2_PL.BOOLS2,433527,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PIT_0102_2_PL.BOOLS3,433528,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PIT_0102_2_PL.BOOLS4,433529,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PIT_0102_2_PL.INT1,433530,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PIT_0102_2_PL.INT2,433531,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PIT_0102_2_PL.AENotify,433558,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PLC_001_1_JA.BOOLS1,433560,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PLC_001_1_JA.BOOLS2,433561,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PLC_001_1_JA.BOOLS3,433562,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PLC_001_1_JA.BOOLS4,433563,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PLC_001_1_JA.INT1,433564,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PLC_001_1_JA.INT2,433565,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PLC_001_1_JA.AENotify,433592,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PLC_001_1_ZS.BOOLS1,433596,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PLC_001_1_ZS.BOOLS2,433597,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PLC_001_1_ZS.BOOLS3,433598,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PLC_001_1_ZS.BOOLS4,433599,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PLC_001_1_ZS.INT1,433600,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PLC_001_1_ZS.INT2,433601,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PLC_001_1_ZS.AENotify,433628,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_1_PL.BOOLS1,433630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_1_PL.BOOLS2,433631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_1_PL.BOOLS3,433632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_1_PL.BOOLS4,433633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_1_PL.INT1,433634,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_1_PL.INT2,433635,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_1_PL.AENotify,433662,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_2_PL.BOOLS1,433666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_2_PL.BOOLS2,433667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_2_PL.BOOLS3,433668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_2_PL.BOOLS4,433669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_2_PL.INT1,433670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_2_PL.INT2,433671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_2_PL.AENotify,433698,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_3_PL.BOOLS1,433700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_3_PL.BOOLS2,433701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_3_PL.BOOLS3,433702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_3_PL.BOOLS4,433703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_3_PL.INT1,433704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_3_PL.INT2,433705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_3_PL.AENotify,433732,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_4_PL.BOOLS1,433736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_4_PL.BOOLS2,433737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_4_PL.BOOLS3,433738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_4_PL.BOOLS4,433739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_4_PL.INT1,433740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_4_PL.INT2,433741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_4_PL.AENotify,433768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_5_PL.BOOLS1,433770,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_5_PL.BOOLS2,433771,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_5_PL.BOOLS3,433772,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_5_PL.BOOLS4,433773,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_5_PL.INT1,433774,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_5_PL.INT2,433775,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_5_PL.AENotify,433802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_6_PL.BOOLS1,433806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_6_PL.BOOLS2,433807,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_6_PL.BOOLS3,433808,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_6_PL.BOOLS4,433809,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_6_PL.INT1,433810,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_6_PL.INT2,433811,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_6_PL.AENotify,433838,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_7_PL.BOOLS1,433840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_7_PL.BOOLS2,433841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_7_PL.BOOLS3,433842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_7_PL.BOOLS4,433843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_7_PL.INT1,433844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_7_PL.INT2,433845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_7_PL.AENotify,433872,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_8_PL.BOOLS1,433876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_8_PL.BOOLS2,433877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_8_PL.BOOLS3,433878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_8_PL.BOOLS4,433879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_8_PL.INT1,433880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_8_PL.INT2,433881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_8_PL.AENotify,433908,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_PS_0103_9_PL.BOOLS1,433910,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_PS_0103_9_PL.BOOLS2,433911,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_PS_0103_9_PL.BOOLS3,433912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_PS_0103_9_PL.BOOLS4,433913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_PS_0103_9_PL.INT1,433914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_9_PL.INT2,433915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_PS_0103_9_PL.AENotify,433942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_REC_0131_1_XA.BOOLS1,433946,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_REC_0131_1_XA.BOOLS2,433947,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_REC_0131_1_XA.BOOLS3,433948,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_REC_0131_1_XA.BOOLS4,433949,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_REC_0131_1_XA.INT1,433950,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_1_XA.INT2,433951,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_1_XA.AENotify,433978,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_REC_0131_2_XA.BOOLS1,433980,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_REC_0131_2_XA.BOOLS2,433981,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_REC_0131_2_XA.BOOLS3,433982,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_REC_0131_2_XA.BOOLS4,433983,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_REC_0131_2_XA.INT1,433984,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_2_XA.INT2,433985,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_2_XA.AENotify,434012,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_REC_0131_3_XA.BOOLS1,434016,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_REC_0131_3_XA.BOOLS2,434017,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_REC_0131_3_XA.BOOLS3,434018,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_REC_0131_3_XA.BOOLS4,434019,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_REC_0131_3_XA.INT1,434020,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_3_XA.INT2,434021,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_3_XA.AENotify,434048,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_REC_0131_4_XA.BOOLS1,434050,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_REC_0131_4_XA.BOOLS2,434051,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_REC_0131_4_XA.BOOLS3,434052,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_REC_0131_4_XA.BOOLS4,434053,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_REC_0131_4_XA.INT1,434054,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_4_XA.INT2,434055,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_REC_0131_4_XA.AENotify,434082,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SD_0112_1_XA.BOOLS1,434086,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SD_0112_1_XA.BOOLS2,434087,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SD_0112_1_XA.BOOLS3,434088,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SD_0112_1_XA.BOOLS4,434089,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SD_0112_1_XA.INT1,434090,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0112_1_XA.INT2,434091,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0112_1_XA.AENotify,434118,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SD_0113_1_XA.BOOLS1,434120,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SD_0113_1_XA.BOOLS2,434121,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SD_0113_1_XA.BOOLS3,434122,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SD_0113_1_XA.BOOLS4,434123,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SD_0113_1_XA.INT1,434124,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0113_1_XA.INT2,434125,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0113_1_XA.AENotify,434152,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SD_0113_2_XA.BOOLS1,434156,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SD_0113_2_XA.BOOLS2,434157,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SD_0113_2_XA.BOOLS3,434158,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SD_0113_2_XA.BOOLS4,434159,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SD_0113_2_XA.INT1,434160,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0113_2_XA.INT2,434161,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0113_2_XA.AENotify,434188,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SD_0114_1_XA.BOOLS1,434190,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SD_0114_1_XA.BOOLS2,434191,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SD_0114_1_XA.BOOLS3,434192,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SD_0114_1_XA.BOOLS4,434193,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SD_0114_1_XA.INT1,434194,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0114_1_XA.INT2,434195,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0114_1_XA.AENotify,434222,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SD_0114_2_XA.BOOLS1,434226,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SD_0114_2_XA.BOOLS2,434227,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SD_0114_2_XA.BOOLS3,434228,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SD_0114_2_XA.BOOLS4,434229,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SD_0114_2_XA.INT1,434230,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0114_2_XA.INT2,434231,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SD_0114_2_XA.AENotify,434258,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_1_XA.BOOLS1,434260,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_1_XA.BOOLS2,434261,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_1_XA.BOOLS3,434262,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_1_XA.BOOLS4,434263,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_1_XA.INT1,434264,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_1_XA.INT2,434265,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_1_XA.AENotify,434292,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_2_XA.BOOLS1,434296,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_2_XA.BOOLS2,434297,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_2_XA.BOOLS3,434298,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_2_XA.BOOLS4,434299,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_2_XA.INT1,434300,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_2_XA.INT2,434301,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_2_XA.AENotify,434328,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_3_XA1.BOOLS1,434330,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_3_XA1.BOOLS2,434331,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_3_XA1.BOOLS3,434332,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_3_XA1.BOOLS4,434333,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_3_XA1.INT1,434334,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3_XA1.INT2,434335,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3_XA1.AENotify,434362,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_3A_XA.BOOLS1,434366,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_3A_XA.BOOLS2,434367,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_3A_XA.BOOLS3,434368,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_3A_XA.BOOLS4,434369,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_3A_XA.INT1,434370,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3A_XA.INT2,434371,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3A_XA.AENotify,434398,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_3B_XA.BOOLS1,434400,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_3B_XA.BOOLS2,434401,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_3B_XA.BOOLS3,434402,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_3B_XA.BOOLS4,434403,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_3B_XA.INT1,434404,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3B_XA.INT2,434405,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_3B_XA.AENotify,434432,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_4_XA.BOOLS1,434436,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_4_XA.BOOLS2,434437,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_4_XA.BOOLS3,434438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_4_XA.BOOLS4,434439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_4_XA.INT1,434440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_4_XA.INT2,434441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_4_XA.AENotify,434468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_4_XA1.BOOLS1,434470,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_4_XA1.BOOLS2,434471,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_4_XA1.BOOLS3,434472,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_4_XA1.BOOLS4,434473,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_4_XA1.INT1,434474,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_4_XA1.INT2,434475,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_4_XA1.AENotify,434502,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_5_XA.BOOLS1,434506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_5_XA.BOOLS2,434507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_5_XA.BOOLS3,434508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_5_XA.BOOLS4,434509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_5_XA.INT1,434510,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_5_XA.INT2,434511,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_5_XA.AENotify,434538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0112_6_XA.BOOLS1,434540,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0112_6_XA.BOOLS2,434541,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0112_6_XA.BOOLS3,434542,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0112_6_XA.BOOLS4,434543,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0112_6_XA.INT1,434544,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_6_XA.INT2,434545,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0112_6_XA.AENotify,434572,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0113_1_XA.BOOLS1,434576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0113_1_XA.BOOLS2,434577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0113_1_XA.BOOLS3,434578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0113_1_XA.BOOLS4,434579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0113_1_XA.INT1,434580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0113_1_XA.INT2,434581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0113_1_XA.AENotify,434608,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_SPD_0113_2_XA.BOOLS1,434610,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_SPD_0113_2_XA.BOOLS2,434611,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_SPD_0113_2_XA.BOOLS3,434612,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_SPD_0113_2_XA.BOOLS4,434613,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_SPD_0113_2_XA.INT1,434614,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0113_2_XA.INT2,434615,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_SPD_0113_2_XA.AENotify,434642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0111_1_TH.BOOLS1,434646,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0111_1_TH.BOOLS2,434647,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0111_1_TH.BOOLS3,434648,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0111_1_TH.BOOLS4,434649,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0111_1_TH.INT1,434650,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0111_1_TH.INT2,434651,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0111_1_TH.AENotify,434678,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0112_1_TH.BOOLS1,434680,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0112_1_TH.BOOLS2,434681,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0112_1_TH.BOOLS3,434682,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0112_1_TH.BOOLS4,434683,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0112_1_TH.INT1,434684,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0112_1_TH.INT2,434685,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0112_1_TH.AENotify,434712,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0113_1_TH.BOOLS1,434716,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0113_1_TH.BOOLS2,434717,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0113_1_TH.BOOLS3,434718,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0113_1_TH.BOOLS4,434719,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0113_1_TH.INT1,434720,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0113_1_TH.INT2,434721,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0113_1_TH.AENotify,434748,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0113_2_TH.BOOLS1,434750,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0113_2_TH.BOOLS2,434751,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0113_2_TH.BOOLS3,434752,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0113_2_TH.BOOLS4,434753,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0113_2_TH.INT1,434754,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0113_2_TH.INT2,434755,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0113_2_TH.AENotify,434782,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0114_1_TH.BOOLS1,434786,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0114_1_TH.BOOLS2,434787,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0114_1_TH.BOOLS3,434788,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0114_1_TH.BOOLS4,434789,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0114_1_TH.INT1,434790,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0114_1_TH.INT2,434791,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0114_1_TH.AENotify,434818,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TE_0114_2_TH.BOOLS1,434820,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TE_0114_2_TH.BOOLS2,434821,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TE_0114_2_TH.BOOLS3,434822,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TE_0114_2_TH.BOOLS4,434823,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TE_0114_2_TH.INT1,434824,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0114_2_TH.INT2,434825,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TE_0114_2_TH.AENotify,434852,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_1_LL.BOOLS1,434856,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_1_LL.BOOLS2,434857,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_1_LL.BOOLS3,434858,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_1_LL.BOOLS4,434859,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_1_LL.INT1,434860,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_LL.INT2,434861,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_LL.AENotify,434888,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_1_TH1.BOOLS1,434890,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_1_TH1.BOOLS2,434891,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_1_TH1.BOOLS3,434892,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_1_TH1.BOOLS4,434893,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_1_TH1.INT1,434894,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_TH1.INT2,434895,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_TH1.AENotify,434922,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_1_TH2.BOOLS1,434926,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_1_TH2.BOOLS2,434927,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_1_TH2.BOOLS3,434928,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_1_TH2.BOOLS4,434929,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_1_TH2.INT1,434930,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_TH2.INT2,434931,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_TH2.AENotify,434958,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_1_XA.BOOLS1,434960,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_1_XA.BOOLS2,434961,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_1_XA.BOOLS3,434962,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_1_XA.BOOLS4,434963,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_1_XA.INT1,434964,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_XA.INT2,434965,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_1_XA.AENotify,434992,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_2_LL.BOOLS1,434996,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_2_LL.BOOLS2,434997,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_2_LL.BOOLS3,434998,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_2_LL.BOOLS4,434999,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_2_LL.INT1,435000,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_LL.INT2,435001,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_LL.AENotify,435028,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_2_TH1.BOOLS1,435030,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_2_TH1.BOOLS2,435031,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_2_TH1.BOOLS3,435032,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_2_TH1.BOOLS4,435033,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_2_TH1.INT1,435034,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_TH1.INT2,435035,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_TH1.AENotify,435062,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_2_TH2.BOOLS1,435066,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_2_TH2.BOOLS2,435067,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_2_TH2.BOOLS3,435068,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_2_TH2.BOOLS4,435069,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_2_TH2.INT1,435070,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_TH2.INT2,435071,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_TH2.AENotify,435098,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_TFR_0131_2_XA.BOOLS1,435100,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_TFR_0131_2_XA.BOOLS2,435101,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_TFR_0131_2_XA.BOOLS3,435102,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_TFR_0131_2_XA.BOOLS4,435103,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_TFR_0131_2_XA.INT1,435104,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_XA.INT2,435105,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_TFR_0131_2_XA.AENotify,435132,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_UPS_001_1_JA.BOOLS1,435136,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_UPS_001_1_JA.BOOLS2,435137,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_UPS_001_1_JA.BOOLS3,435138,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_UPS_001_1_JA.BOOLS4,435139,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_UPS_001_1_JA.INT1,435140,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_1_JA.INT2,435141,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_1_JA.AENotify,435168,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_UPS_001_1_ZS.BOOLS1,435170,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_UPS_001_1_ZS.BOOLS2,435171,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_UPS_001_1_ZS.BOOLS3,435172,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_UPS_001_1_ZS.BOOLS4,435173,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_UPS_001_1_ZS.INT1,435174,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_1_ZS.INT2,435175,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_1_ZS.AENotify,435202,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_UPS_001_2_JA.BOOLS1,435206,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_UPS_001_2_JA.BOOLS2,435207,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_UPS_001_2_JA.BOOLS3,435208,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_UPS_001_2_JA.BOOLS4,435209,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_UPS_001_2_JA.INT1,435210,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_2_JA.INT2,435211,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_2_JA.AENotify,435238,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_UPS_001_2_ZS.BOOLS1,435240,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_UPS_001_2_ZS.BOOLS2,435241,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_UPS_001_2_ZS.BOOLS3,435242,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_UPS_001_2_ZS.BOOLS4,435243,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_UPS_001_2_ZS.INT1,435244,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_2_ZS.INT2,435245,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_UPS_001_2_ZS.AENotify,435272,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XE_0112_1A_ZA.BOOLS1,435276,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XE_0112_1A_ZA.BOOLS2,435277,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XE_0112_1A_ZA.BOOLS3,435278,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XE_0112_1A_ZA.BOOLS4,435279,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XE_0112_1A_ZA.INT1,435280,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0112_1A_ZA.INT2,435281,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0112_1A_ZA.AENotify,435308,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XE_0113_1A_ZA.BOOLS1,435310,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XE_0113_1A_ZA.BOOLS2,435311,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XE_0113_1A_ZA.BOOLS3,435312,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XE_0113_1A_ZA.BOOLS4,435313,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XE_0113_1A_ZA.INT1,435314,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_1A_ZA.INT2,435315,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_1A_ZA.AENotify,435342,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XE_0113_1B_ZA.BOOLS1,435346,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XE_0113_1B_ZA.BOOLS2,435347,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XE_0113_1B_ZA.BOOLS3,435348,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XE_0113_1B_ZA.BOOLS4,435349,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XE_0113_1B_ZA.INT1,435350,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_1B_ZA.INT2,435351,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_1B_ZA.AENotify,435378,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XE_0113_2A_ZA.BOOLS1,435380,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XE_0113_2A_ZA.BOOLS2,435381,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XE_0113_2A_ZA.BOOLS3,435382,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XE_0113_2A_ZA.BOOLS4,435383,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XE_0113_2A_ZA.INT1,435384,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_2A_ZA.INT2,435385,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_2A_ZA.AENotify,435412,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XE_0113_2B_ZA.BOOLS1,435416,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XE_0113_2B_ZA.BOOLS2,435417,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XE_0113_2B_ZA.BOOLS3,435418,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XE_0113_2B_ZA.BOOLS4,435419,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XE_0113_2B_ZA.INT1,435420,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_2B_ZA.INT2,435421,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XE_0113_2B_ZA.AENotify,435448,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_3_LL.BOOLS1,435450,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_3_LL.BOOLS2,435451,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_3_LL.BOOLS3,435452,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_3_LL.BOOLS4,435453,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_3_LL.INT1,435454,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_LL.INT2,435455,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_LL.AENotify,435482,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_3_TH1.BOOLS1,435486,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_3_TH1.BOOLS2,435487,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_3_TH1.BOOLS3,435488,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_3_TH1.BOOLS4,435489,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_3_TH1.INT1,435490,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_TH1.INT2,435491,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_TH1.AENotify,435518,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_3_TH2.BOOLS1,435520,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_3_TH2.BOOLS2,435521,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_3_TH2.BOOLS3,435522,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_3_TH2.BOOLS4,435523,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_3_TH2.INT1,435524,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_TH2.INT2,435525,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_TH2.AENotify,435552,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_3_XA.BOOLS1,435556,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_3_XA.BOOLS2,435557,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_3_XA.BOOLS3,435558,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_3_XA.BOOLS4,435559,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_3_XA.INT1,435560,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_XA.INT2,435561,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_3_XA.AENotify,435588,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_4_LL.BOOLS1,435590,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_4_LL.BOOLS2,435591,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_4_LL.BOOLS3,435592,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_4_LL.BOOLS4,435593,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_4_LL.INT1,435594,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_LL.INT2,435595,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_LL.AENotify,435622,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_4_TH1.BOOLS1,435626,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_4_TH1.BOOLS2,435627,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_4_TH1.BOOLS3,435628,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_4_TH1.BOOLS4,435629,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_4_TH1.INT1,435630,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_TH1.INT2,435631,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_TH1.AENotify,435658,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_4_TH2.BOOLS1,435660,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_4_TH2.BOOLS2,435661,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_4_TH2.BOOLS3,435662,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_4_TH2.BOOLS4,435663,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_4_TH2.INT1,435664,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_TH2.INT2,435665,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_TH2.AENotify,435692,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_4_XA.BOOLS1,435696,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_4_XA.BOOLS2,435697,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_4_XA.BOOLS3,435698,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_4_XA.BOOLS4,435699,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_4_XA.INT1,435700,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_XA.INT2,435701,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_4_XA.AENotify,435728,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_5_LL.BOOLS1,435730,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_5_LL.BOOLS2,435731,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_5_LL.BOOLS3,435732,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_5_LL.BOOLS4,435733,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_5_LL.INT1,435734,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_LL.INT2,435735,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_LL.AENotify,435762,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_5_TH1.BOOLS1,435766,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_5_TH1.BOOLS2,435767,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_5_TH1.BOOLS3,435768,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_5_TH1.BOOLS4,435769,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_5_TH1.INT1,435770,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_TH1.INT2,435771,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_TH1.AENotify,435798,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_5_TH2.BOOLS1,435800,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_5_TH2.BOOLS2,435801,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_5_TH2.BOOLS3,435802,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_5_TH2.BOOLS4,435803,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_5_TH2.INT1,435804,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_TH2.INT2,435805,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_TH2.AENotify,435832,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_5_XA.BOOLS1,435836,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_5_XA.BOOLS2,435837,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_5_XA.BOOLS3,435838,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_5_XA.BOOLS4,435839,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_5_XA.INT1,435840,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_XA.INT2,435841,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_5_XA.AENotify,435868,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_6_LL.BOOLS1,435870,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_6_LL.BOOLS2,435871,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_6_LL.BOOLS3,435872,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_6_LL.BOOLS4,435873,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_6_LL.INT1,435874,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_LL.INT2,435875,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_LL.AENotify,435902,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_6_TH1.BOOLS1,435906,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_6_TH1.BOOLS2,435907,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_6_TH1.BOOLS3,435908,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_6_TH1.BOOLS4,435909,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_6_TH1.INT1,435910,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_TH1.INT2,435911,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_TH1.AENotify,435938,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_6_TH2.BOOLS1,435940,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_6_TH2.BOOLS2,435941,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_6_TH2.BOOLS3,435942,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_6_TH2.BOOLS4,435943,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_6_TH2.INT1,435944,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_TH2.INT2,435945,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_TH2.AENotify,435972,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_XFR_0131_6_XA.BOOLS1,435976,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3252_XFR_0131_6_XA.BOOLS2,435977,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3252_XFR_0131_6_XA.BOOLS3,435978,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3252_XFR_0131_6_XA.BOOLS4,435979,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3252_XFR_0131_6_XA.INT1,435980,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_XA.INT2,435981,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3252_XFR_0131_6_XA.AENotify,436008,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_EASTMICRO_FAIL.BOOLS1,436010,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_EASTMICRO_FAIL.BOOLS2,436011,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_EASTMICRO_FAIL.BOOLS3,436012,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_EASTMICRO_FAIL.BOOLS4,436013,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_EASTMICRO_FAIL.INT1,436014,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EASTMICRO_FAIL.INT2,436015,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EASTMICRO_FAIL.AENotify,436042,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_EATON_PUMP1_FAIL.BOOLS1,436046,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_EATON_PUMP1_FAIL.BOOLS2,436047,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_EATON_PUMP1_FAIL.BOOLS3,436048,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_EATON_PUMP1_FAIL.BOOLS4,436049,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_EATON_PUMP1_FAIL.INT1,436050,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP1_FAIL.INT2,436051,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP1_FAIL.AENotify,436078,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_EATON_PUMP2_FAIL.BOOLS1,436080,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_EATON_PUMP2_FAIL.BOOLS2,436081,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_EATON_PUMP2_FAIL.BOOLS3,436082,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_EATON_PUMP2_FAIL.BOOLS4,436083,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_EATON_PUMP2_FAIL.INT1,436084,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP2_FAIL.INT2,436085,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP2_FAIL.AENotify,436112,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_EATON_PUMP9_FAIL.BOOLS1,436116,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_EATON_PUMP9_FAIL.BOOLS2,436117,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_EATON_PUMP9_FAIL.BOOLS3,436118,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_EATON_PUMP9_FAIL.BOOLS4,436119,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_EATON_PUMP9_FAIL.INT1,436120,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP9_FAIL.INT2,436121,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_EATON_PUMP9_FAIL.AENotify,436148,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_METER_VAULT_FAIL.BOOLS1,436150,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_METER_VAULT_FAIL.BOOLS2,436151,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_METER_VAULT_FAIL.BOOLS3,436152,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_METER_VAULT_FAIL.BOOLS4,436153,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_METER_VAULT_FAIL.INT1,436154,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_METER_VAULT_FAIL.INT2,436155,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_METER_VAULT_FAIL.AENotify,436182,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_SEL710_PUMP1_FAIL.BOOLS1,436186,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_SEL710_PUMP1_FAIL.BOOLS2,436187,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_SEL710_PUMP1_FAIL.BOOLS3,436188,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_SEL710_PUMP1_FAIL.BOOLS4,436189,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_SEL710_PUMP1_FAIL.INT1,436190,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP1_FAIL.INT2,436191,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP1_FAIL.AENotify,436218,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_SEL710_PUMP2_FAIL.BOOLS1,436220,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_SEL710_PUMP2_FAIL.BOOLS2,436221,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_SEL710_PUMP2_FAIL.BOOLS3,436222,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_SEL710_PUMP2_FAIL.BOOLS4,436223,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_SEL710_PUMP2_FAIL.INT1,436224,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP2_FAIL.INT2,436225,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP2_FAIL.AENotify,436252,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_SEL710_PUMP9_FAIL.BOOLS1,436256,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_SEL710_PUMP9_FAIL.BOOLS2,436257,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_SEL710_PUMP9_FAIL.BOOLS3,436258,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_SEL710_PUMP9_FAIL.BOOLS4,436259,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_SEL710_PUMP9_FAIL.INT1,436260,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP9_FAIL.INT2,436261,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_SEL710_PUMP9_FAIL.AENotify,436288,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_TSR_PLC_FAIL.BOOLS1,436290,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_TSR_PLC_FAIL.BOOLS2,436291,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_TSR_PLC_FAIL.BOOLS3,436292,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_TSR_PLC_FAIL.BOOLS4,436293,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_TSR_PLC_FAIL.INT1,436294,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_TSR_PLC_FAIL.INT2,436295,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_TSR_PLC_FAIL.AENotify,436322,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3260_COMM_WESTMICRO_FAIL.BOOLS1,436326,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: First integer of packed bits" WA3260_COMM_WESTMICRO_FAIL.BOOLS2,436327,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Second integer of packed bits" WA3260_COMM_WESTMICRO_FAIL.BOOLS3,436328,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Third integer of packed bits." WA3260_COMM_WESTMICRO_FAIL.BOOLS4,436329,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Fourth integer of packed bits." WA3260_COMM_WESTMICRO_FAIL.INT1,436330,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_WESTMICRO_FAIL.INT2,436331,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Spare Integer" WA3260_COMM_WESTMICRO_FAIL.AENotify,436358,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_1.BOOLS1,436360,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.BOOLS2,436361,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.BOOLS3,436362,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_1.BOOLS4,436363,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_1.INT1,436364,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_1.INT2,436365,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_1.AENotify,436492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_2.BOOLS1,436496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.BOOLS2,436497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.BOOLS3,436498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_2.BOOLS4,436499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_2.INT1,436500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_2.INT2,436501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_2.AENotify,436628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_3.BOOLS1,436630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.BOOLS2,436631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.BOOLS3,436632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_3.BOOLS4,436633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_3.INT1,436634,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_3.INT2,436635,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_3.AENotify,436762,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_4.BOOLS1,436766,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.BOOLS2,436767,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.BOOLS3,436768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_4.BOOLS4,436769,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_4.INT1,436770,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_4.INT2,436771,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_4.AENotify,436898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_5.BOOLS1,436900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.BOOLS2,436901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.BOOLS3,436902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_5.BOOLS4,436903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_5.INT1,436904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_5.INT2,436905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_5.AENotify,437032,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_6.BOOLS1,437036,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.BOOLS2,437037,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.BOOLS3,437038,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_6.BOOLS4,437039,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_6.INT1,437040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_6.INT2,437041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_6.AENotify,437168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_7.BOOLS1,437170,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.BOOLS2,437171,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.BOOLS3,437172,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_7.BOOLS4,437173,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_7.INT1,437174,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_7.INT2,437175,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_7.AENotify,437302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_8.BOOLS1,437306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.BOOLS2,437307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.BOOLS3,437308,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_8.BOOLS4,437309,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_8.INT1,437310,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_8.INT2,437311,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_8.AENotify,437438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_AFD_0103_9.BOOLS1,437440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.BOOLS2,437441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.BOOLS3,437442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Third Integer of packed Bits" WA3252_AFD_0103_9.BOOLS4,437443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fourth Integer of packed Bits (SPARE)" WA3252_AFD_0103_9.INT1,437444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_9.INT2,437445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Spare Integer" WA3252_AFD_0103_9.AENotify,437572,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_1A.BOOLS1,437576,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A.BOOLS2,437577,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A.BOOLS3,437578,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0102_1A.BOOLS4,437579,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0102_1A.INT1,437580,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_1A.INT2,437581,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_1A.AENotify,437650,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_1B.BOOLS1,437656,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B.BOOLS2,437657,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B.BOOLS3,437658,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0102_1B.BOOLS4,437659,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0102_1B.INT1,437660,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_1B.INT2,437661,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_1B.AENotify,437730,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_2A.BOOLS1,437736,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A.BOOLS2,437737,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A.BOOLS3,437738,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0102_2A.BOOLS4,437739,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0102_2A.INT1,437740,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_2A.INT2,437741,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_2A.AENotify,437810,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0102_2B.BOOLS1,437816,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B.BOOLS2,437817,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B.BOOLS3,437818,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0102_2B.BOOLS4,437819,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0102_2B.INT1,437820,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_2B.INT2,437821,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0102_2B.AENotify,437890,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1A.BOOLS1,437896,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A.BOOLS2,437897,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A.BOOLS3,437898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_1A.BOOLS4,437899,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_1A.INT1,437900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_1A.INT2,437901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_1A.AENotify,437970,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_1C.BOOLS1,437976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C.BOOLS2,437977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C.BOOLS3,437978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_1C.BOOLS4,437979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_1C.INT1,437980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_1C.INT2,437981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_1C.AENotify,438050,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2A.BOOLS1,438056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A.BOOLS2,438057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A.BOOLS3,438058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_2A.BOOLS4,438059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_2A.INT1,438060,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_2A.INT2,438061,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_2A.AENotify,438130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_2C.BOOLS1,438136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C.BOOLS2,438137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C.BOOLS3,438138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_2C.BOOLS4,438139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_2C.INT1,438140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_2C.INT2,438141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_2C.AENotify,438210,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3A.BOOLS1,438216,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A.BOOLS2,438217,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A.BOOLS3,438218,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_3A.BOOLS4,438219,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3A.INT1,438220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3A.INT2,438221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3A.AENotify,438290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3C.BOOLS1,438296,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C.BOOLS2,438297,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C.BOOLS3,438298,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_3C.BOOLS4,438299,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3C.INT1,438300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3C.INT2,438301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3C.AENotify,438370,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_3D.BOOLS1,438376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D.BOOLS2,438377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D.BOOLS3,438378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_3D.BOOLS4,438379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3D.INT1,438380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3D.INT2,438381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_3D.AENotify,438450,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4A.BOOLS1,438456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A.BOOLS2,438457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A.BOOLS3,438458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_4A.BOOLS4,438459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4A.INT1,438460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4A.INT2,438461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4A.AENotify,438530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4C.BOOLS1,438536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C.BOOLS2,438537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C.BOOLS3,438538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_4C.BOOLS4,438539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4C.INT1,438540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4C.INT2,438541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4C.AENotify,438610,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_4D.BOOLS1,438616,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D.BOOLS2,438617,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D.BOOLS3,438618,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_4D.BOOLS4,438619,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4D.INT1,438620,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4D.INT2,438621,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_4D.AENotify,438690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5A.BOOLS1,438696,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A.BOOLS2,438697,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A.BOOLS3,438698,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_5A.BOOLS4,438699,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5A.INT1,438700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5A.INT2,438701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5A.AENotify,438770,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5C.BOOLS1,438776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C.BOOLS2,438777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C.BOOLS3,438778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_5C.BOOLS4,438779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5C.INT1,438780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5C.INT2,438781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5C.AENotify,438850,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_5D.BOOLS1,438856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D.BOOLS2,438857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D.BOOLS3,438858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_5D.BOOLS4,438859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5D.INT1,438860,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5D.INT2,438861,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_5D.AENotify,438930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6A.BOOLS1,438936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A.BOOLS2,438937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A.BOOLS3,438938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_6A.BOOLS4,438939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6A.INT1,438940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6A.INT2,438941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6A.AENotify,439010,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6C.BOOLS1,439016,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C.BOOLS2,439017,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C.BOOLS3,439018,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_6C.BOOLS4,439019,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6C.INT1,439020,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6C.INT2,439021,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6C.AENotify,439090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_6D.BOOLS1,439096,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D.BOOLS2,439097,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D.BOOLS3,439098,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_6D.BOOLS4,439099,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6D.INT1,439100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6D.INT2,439101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_6D.AENotify,439170,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7A.BOOLS1,439176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A.BOOLS2,439177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A.BOOLS3,439178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_7A.BOOLS4,439179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7A.INT1,439180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7A.INT2,439181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7A.AENotify,439250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7C.BOOLS1,439256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C.BOOLS2,439257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C.BOOLS3,439258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_7C.BOOLS4,439259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7C.INT1,439260,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7C.INT2,439261,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7C.AENotify,439330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_7D.BOOLS1,439336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D.BOOLS2,439337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D.BOOLS3,439338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_7D.BOOLS4,439339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7D.INT1,439340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7D.INT2,439341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_7D.AENotify,439410,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8A.BOOLS1,439416,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A.BOOLS2,439417,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A.BOOLS3,439418,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_8A.BOOLS4,439419,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8A.INT1,439420,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8A.INT2,439421,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8A.AENotify,439490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8C.BOOLS1,439496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C.BOOLS2,439497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C.BOOLS3,439498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_8C.BOOLS4,439499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8C.INT1,439500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8C.INT2,439501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8C.AENotify,439570,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_8D.BOOLS1,439576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D.BOOLS2,439577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D.BOOLS3,439578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_8D.BOOLS4,439579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8D.INT1,439580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8D.INT2,439581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_8D.AENotify,439650,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9A.BOOLS1,439656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A.BOOLS2,439657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A.BOOLS3,439658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_9A.BOOLS4,439659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_9A.INT1,439660,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_9A.INT2,439661,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_9A.AENotify,439730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0103_9C.BOOLS1,439736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C.BOOLS2,439737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C.BOOLS3,439738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0103_9C.BOOLS4,439739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_9C.INT1,439740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_9C.INT2,439741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0103_9C.AENotify,439810,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2A.BOOLS1,439816,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A.BOOLS2,439817,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A.BOOLS3,439818,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0113_2A.BOOLS4,439819,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0113_2A.INT1,439820,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2A.INT2,439821,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2A.AENotify,439890,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2B.BOOLS1,439896,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B.BOOLS2,439897,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B.BOOLS3,439898,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0113_2B.BOOLS4,439899,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0113_2B.INT1,439900,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2B.INT2,439901,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2B.AENotify,439970,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2C.BOOLS1,439976,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C.BOOLS2,439977,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C.BOOLS3,439978,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0113_2C.BOOLS4,439979,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0113_2C.INT1,439980,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2C.INT2,439981,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2C.AENotify,440050,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FV_0113_2D.BOOLS1,440056,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D.BOOLS2,440057,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D.BOOLS3,440058,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Third Integer of Packed Bits." WA3252_FV_0113_2D.BOOLS4,440059,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0113_2D.INT1,440060,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2D.INT2,440061,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Spare Integer." WA3252_FV_0113_2D.AENotify,440130,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2A.BOOLS1,440136,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.BOOLS2,440137,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.BOOLS3,440138,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Third Integer of packed bits" WA3252_FCV_0113_2A.BOOLS4,440139,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Fourth Integer of packed bits (SPARE)" WA3252_FCV_0113_2A.INT1,440140,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Spare Integer" WA3252_FCV_0113_2A.INT2,440141,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Spare Integer" WA3252_FCV_0113_2A.AENotify,440238,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2B.BOOLS1,440246,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.BOOLS2,440247,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.BOOLS3,440248,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Third Integer of packed bits" WA3252_FCV_0113_2B.BOOLS4,440249,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Fourth Integer of packed bits (SPARE)" WA3252_FCV_0113_2B.INT1,440250,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Spare Integer" WA3252_FCV_0113_2B.INT2,440251,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Spare Integer" WA3252_FCV_0113_2B.AENotify,440348,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Combined Alarm Value Notification for HMI" WA3252_FCV_0113_2_PID.pv_inf,440372,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Lower limit of the process value range WA3252_FCV_0113_2_PID.pv_sup,440374,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Upper limit of the process value range WA3252_FCV_0113_2_PID.out_inf,440376,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Lower limit of the output value range WA3252_FCV_0113_2_PID.out_sup,440378,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Upper limit of the output value range WA3252_FCV_0113_2_PID.kp,440382,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Proportional contribution (gain) WA3252_FCV_0113_2_PID.dband,440386,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Dead zone on deviation WA3252_FCV_0113_2_PID.outbias,440388,Float,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Manual adjustment of static deviation WA3252_FIT_0105_1A_PID.pv_inf,440352,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Lower limit of the process value range WA3252_FIT_0105_1A_PID.pv_sup,440354,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Upper limit of the process value range WA3252_FIT_0105_1A_PID.out_inf,440356,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Lower limit of the output value range WA3252_FIT_0105_1A_PID.out_sup,440358,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Upper limit of the output value range WA3252_FIT_0105_1A_PID.kp,440362,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Proportional contribution (gain) WA3252_FIT_0105_1A_PID.dband,440366,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Dead zone on deviation WA3252_FIT_0105_1A_PID.outbias,440368,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Manual adjustment of static deviation WA3252_FIT_0105_1A_PID_OUT_ramp.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Output Ramp Para for Loop in Process manual: WA3252_FIT_0105_1A_PID_OUT_ramp.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Output Ramp Para for Loop in Process manual: AFD_1_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Ramp Rate Simulation Parameters: AFD_1_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 1 Ramp Rate Simulation Parameters: AFD_2_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Ramp Rate Simulation Parameters: AFD_2_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 2 Ramp Rate Simulation Parameters: AFD_3_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 3 Ramp Rate Simulation Parameters: AFD_3_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 3 Ramp Rate Simulation Parameters: AFD_4_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 4 Ramp Rate Simulation Parameters: AFD_4_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 4 Ramp Rate Simulation Parameters: AFD_5_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 5 Ramp Rate Simulation Parameters: AFD_5_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 5 Ramp Rate Simulation Parameters: AFD_6_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 6 Ramp Rate Simulation Parameters: AFD_6_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 6 Ramp Rate Simulation Parameters: AFD_7_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 7 Ramp Rate Simulation Parameters: AFD_7_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 7 Ramp Rate Simulation Parameters: AFD_8_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 8 Ramp Rate Simulation Parameters: AFD_8_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 8 Ramp Rate Simulation Parameters: AFD_9_PCV_PARA_SIM.inc_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Ramp Rate Simulation Parameters: AFD_9_PCV_PARA_SIM.dec_rate,,Float,1,R/W,1000,,,,,,,,,,RWPS Pump 9 Ramp Rate Simulation Parameters: WA3252_AFD_0103_1_SI.VALU,401008,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_1_SI.Old_Val,401010,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_1_SI.VMIN,401012,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_1_SI.VMAX,401014,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_1_SI.RawMin,401016,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_1_SI.RawMax,401018,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_1_SI.HH_SP,401020,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_1_SI.H_SP,401022,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_1_SI.L_SP,401024,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_1_SI.LL_SP,401026,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_1_SI.BLSP,401028,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_1_SI.ORSP,401030,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_1_SI.URSP,401032,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_1_SI.RCSP,401034,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_1_SI.INTK_SP,401036,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_1_SI.Total,401038,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_1_SI.INTK_Reset_SP,401194,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_2_SI.VALU,401208,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_2_SI.Old_Val,401210,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_2_SI.VMIN,401212,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_2_SI.VMAX,401214,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_2_SI.RawMin,401216,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_2_SI.RawMax,401218,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_2_SI.HH_SP,401220,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_2_SI.H_SP,401222,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_2_SI.L_SP,401224,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_2_SI.LL_SP,401226,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_2_SI.BLSP,401228,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_2_SI.ORSP,401230,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_2_SI.URSP,401232,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_2_SI.RCSP,401234,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_2_SI.INTK_SP,401236,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_2_SI.Total,401238,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_2_SI.INTK_Reset_SP,401394,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_3_SI.VALU,401408,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_3_SI.Old_Val,401410,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_3_SI.VMIN,401412,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_3_SI.VMAX,401414,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_3_SI.RawMin,401416,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_3_SI.RawMax,401418,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_3_SI.HH_SP,401420,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_3_SI.H_SP,401422,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_3_SI.L_SP,401424,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_3_SI.LL_SP,401426,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_3_SI.BLSP,401428,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_3_SI.ORSP,401430,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_3_SI.URSP,401432,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_3_SI.RCSP,401434,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_3_SI.INTK_SP,401436,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_3_SI.Total,401438,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_3_SI.INTK_Reset_SP,401594,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_4_SI.VALU,401608,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_4_SI.Old_Val,401610,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_4_SI.VMIN,401612,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_4_SI.VMAX,401614,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_4_SI.RawMin,401616,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_4_SI.RawMax,401618,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_4_SI.HH_SP,401620,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_4_SI.H_SP,401622,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_4_SI.L_SP,401624,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_4_SI.LL_SP,401626,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_4_SI.BLSP,401628,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_4_SI.ORSP,401630,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_4_SI.URSP,401632,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_4_SI.RCSP,401634,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_4_SI.INTK_SP,401636,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_4_SI.Total,401638,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_4_SI.INTK_Reset_SP,401794,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_5_SI.VALU,401808,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_5_SI.Old_Val,401810,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_5_SI.VMIN,401812,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_5_SI.VMAX,401814,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_5_SI.RawMin,401816,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_5_SI.RawMax,401818,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_5_SI.HH_SP,401820,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_5_SI.H_SP,401822,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_5_SI.L_SP,401824,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_5_SI.LL_SP,401826,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_5_SI.BLSP,401828,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_5_SI.ORSP,401830,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_5_SI.URSP,401832,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_5_SI.RCSP,401834,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_5_SI.INTK_SP,401836,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_5_SI.Total,401838,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_5_SI.INTK_Reset_SP,401994,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_6_SI.VALU,402008,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_6_SI.Old_Val,402010,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_6_SI.VMIN,402012,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_6_SI.VMAX,402014,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_6_SI.RawMin,402016,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_6_SI.RawMax,402018,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_6_SI.HH_SP,402020,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_6_SI.H_SP,402022,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_6_SI.L_SP,402024,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_6_SI.LL_SP,402026,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_6_SI.BLSP,402028,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_6_SI.ORSP,402030,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_6_SI.URSP,402032,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_6_SI.RCSP,402034,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_6_SI.INTK_SP,402036,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_6_SI.Total,402038,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_6_SI.INTK_Reset_SP,402194,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_7_SI.VALU,402208,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_7_SI.Old_Val,402210,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_7_SI.VMIN,402212,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_7_SI.VMAX,402214,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_7_SI.RawMin,402216,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_7_SI.RawMax,402218,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_7_SI.HH_SP,402220,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_7_SI.H_SP,402222,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_7_SI.L_SP,402224,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_7_SI.LL_SP,402226,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_7_SI.BLSP,402228,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_7_SI.ORSP,402230,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_7_SI.URSP,402232,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_7_SI.RCSP,402234,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_7_SI.INTK_SP,402236,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_7_SI.Total,402238,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_7_SI.INTK_Reset_SP,402394,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_8_SI.VALU,402408,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_8_SI.Old_Val,402410,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_8_SI.VMIN,402412,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_8_SI.VMAX,402414,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_8_SI.RawMin,402416,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_8_SI.RawMax,402418,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_8_SI.HH_SP,402420,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_8_SI.H_SP,402422,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_8_SI.L_SP,402424,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_8_SI.LL_SP,402426,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_8_SI.BLSP,402428,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_8_SI.ORSP,402430,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_8_SI.URSP,402432,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_8_SI.RCSP,402434,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_8_SI.INTK_SP,402436,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_8_SI.Total,402438,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_8_SI.INTK_Reset_SP,402594,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_9_SI.VALU,402608,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_AFD_0103_9_SI.Old_Val,402610,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_AFD_0103_9_SI.VMIN,402612,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_AFD_0103_9_SI.VMAX,402614,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_AFD_0103_9_SI.RawMin,402616,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_9_SI.RawMax,402618,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_AFD_0103_9_SI.HH_SP,402620,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_AFD_0103_9_SI.H_SP,402622,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_AFD_0103_9_SI.L_SP,402624,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_AFD_0103_9_SI.LL_SP,402626,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_AFD_0103_9_SI.BLSP,402628,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_AFD_0103_9_SI.ORSP,402630,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_AFD_0103_9_SI.URSP,402632,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_AFD_0103_9_SI.RCSP,402634,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_AFD_0103_9_SI.INTK_SP,402636,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_AFD_0103_9_SI.Total,402638,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_AFD_0103_9_SI.INTK_Reset_SP,402794,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI1.VALU,402808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI1.Old_Val,402810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI1.VMIN,402812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI1.VMAX,402814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI1.RawMin,402816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI1.RawMax,402818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI1.HH_SP,402820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI1.H_SP,402822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI1.L_SP,402824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI1.LL_SP,402826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI1.BLSP,402828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI1.ORSP,402830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI1.URSP,402832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI1.RCSP,402834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI1.INTK_SP,402836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI1.Total,402838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI1.INTK_Reset_SP,402994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI2.VALU,403008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI2.Old_Val,403010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI2.VMIN,403012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI2.VMAX,403014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI2.RawMin,403016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI2.RawMax,403018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI2.HH_SP,403020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI2.H_SP,403022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI2.L_SP,403024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI2.LL_SP,403026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI2.BLSP,403028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI2.ORSP,403030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI2.URSP,403032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI2.RCSP,403034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI2.INTK_SP,403036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI2.Total,403038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI2.INTK_Reset_SP,403194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI3.VALU,403208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI3.Old_Val,403210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI3.VMIN,403212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI3.VMAX,403214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI3.RawMin,403216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI3.RawMax,403218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI3.HH_SP,403220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI3.H_SP,403222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI3.L_SP,403224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI3.LL_SP,403226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI3.BLSP,403228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI3.ORSP,403230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI3.URSP,403232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI3.RCSP,403234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI3.INTK_SP,403236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI3.Total,403238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI3.INTK_Reset_SP,403394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI4.VALU,403408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI4.Old_Val,403410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI4.VMIN,403412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI4.VMAX,403414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI4.RawMin,403416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI4.RawMax,403418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI4.HH_SP,403420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI4.H_SP,403422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI4.L_SP,403424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI4.LL_SP,403426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI4.BLSP,403428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI4.ORSP,403430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI4.URSP,403432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI4.RCSP,403434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI4.INTK_SP,403436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI4.Total,403438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI4.INTK_Reset_SP,403594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI5.VALU,403608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI5.Old_Val,403610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI5.VMIN,403612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI5.VMAX,403614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI5.RawMin,403616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI5.RawMax,403618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI5.HH_SP,403620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI5.H_SP,403622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI5.L_SP,403624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI5.LL_SP,403626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI5.BLSP,403628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI5.ORSP,403630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI5.URSP,403632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI5.RCSP,403634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI5.INTK_SP,403636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI5.Total,403638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI5.INTK_Reset_SP,403794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI6.VALU,403808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI6.Old_Val,403810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI6.VMIN,403812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI6.VMAX,403814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI6.RawMin,403816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI6.RawMax,403818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI6.HH_SP,403820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI6.H_SP,403822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI6.L_SP,403824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI6.LL_SP,403826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI6.BLSP,403828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI6.ORSP,403830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI6.URSP,403832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI6.RCSP,403834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI6.INTK_SP,403836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI6.Total,403838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI6.INTK_Reset_SP,403994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI7.VALU,404008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI7.Old_Val,404010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI7.VMIN,404012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI7.VMAX,404014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI7.RawMin,404016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI7.RawMax,404018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI7.HH_SP,404020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI7.H_SP,404022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI7.L_SP,404024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI7.LL_SP,404026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI7.BLSP,404028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI7.ORSP,404030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI7.URSP,404032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI7.RCSP,404034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI7.INTK_SP,404036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI7.Total,404038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI7.INTK_Reset_SP,404194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI8.VALU,404208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI8.Old_Val,404210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI8.VMIN,404212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI8.VMAX,404214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI8.RawMin,404216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI8.RawMax,404218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI8.HH_SP,404220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI8.H_SP,404222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI8.L_SP,404224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI8.LL_SP,404226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI8.BLSP,404228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI8.ORSP,404230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI8.URSP,404232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI8.RCSP,404234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI8.INTK_SP,404236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI8.Total,404238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI8.INTK_Reset_SP,404394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_CP_0116_1_FI9.VALU,404408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_CP_0116_1_FI9.Old_Val,404410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_CP_0116_1_FI9.VMIN,404412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_CP_0116_1_FI9.VMAX,404414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_CP_0116_1_FI9.RawMin,404416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI9.RawMax,404418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_CP_0116_1_FI9.HH_SP,404420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_CP_0116_1_FI9.H_SP,404422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_CP_0116_1_FI9.L_SP,404424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_CP_0116_1_FI9.LL_SP,404426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_CP_0116_1_FI9.BLSP,404428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_CP_0116_1_FI9.ORSP,404430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_CP_0116_1_FI9.URSP,404432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_CP_0116_1_FI9.RCSP,404434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_CP_0116_1_FI9.INTK_SP,404436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_CP_0116_1_FI9.Total,404438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_CP_0116_1_FI9.INTK_Reset_SP,404594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FCV_0113_2A_ZI.VALU,404608,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FCV_0113_2A_ZI.Old_Val,404610,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FCV_0113_2A_ZI.VMIN,404612,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FCV_0113_2A_ZI.VMAX,404614,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FCV_0113_2A_ZI.RawMin,404616,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FCV_0113_2A_ZI.RawMax,404618,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FCV_0113_2A_ZI.HH_SP,404620,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FCV_0113_2A_ZI.H_SP,404622,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FCV_0113_2A_ZI.L_SP,404624,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FCV_0113_2A_ZI.LL_SP,404626,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FCV_0113_2A_ZI.BLSP,404628,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FCV_0113_2A_ZI.ORSP,404630,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FCV_0113_2A_ZI.URSP,404632,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FCV_0113_2A_ZI.RCSP,404634,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FCV_0113_2A_ZI.INTK_SP,404636,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FCV_0113_2A_ZI.Total,404638,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FCV_0113_2A_ZI.INTK_Reset_SP,404794,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FCV_0113_2B_ZI.VALU,404808,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FCV_0113_2B_ZI.Old_Val,404810,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FCV_0113_2B_ZI.VMIN,404812,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FCV_0113_2B_ZI.VMAX,404814,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FCV_0113_2B_ZI.RawMin,404816,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FCV_0113_2B_ZI.RawMax,404818,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FCV_0113_2B_ZI.HH_SP,404820,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FCV_0113_2B_ZI.H_SP,404822,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FCV_0113_2B_ZI.L_SP,404824,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FCV_0113_2B_ZI.LL_SP,404826,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FCV_0113_2B_ZI.BLSP,404828,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FCV_0113_2B_ZI.ORSP,404830,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FCV_0113_2B_ZI.URSP,404832,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FCV_0113_2B_ZI.RCSP,404834,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FCV_0113_2B_ZI.INTK_SP,404836,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FCV_0113_2B_ZI.Total,404838,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FCV_0113_2B_ZI.INTK_Reset_SP,404994,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FIT_0113_2A_FI.VALU,405008,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FIT_0113_2A_FI.Old_Val,405010,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FIT_0113_2A_FI.VMIN,405012,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FIT_0113_2A_FI.VMAX,405014,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FIT_0113_2A_FI.RawMin,405016,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FIT_0113_2A_FI.RawMax,405018,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FIT_0113_2A_FI.HH_SP,405020,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FIT_0113_2A_FI.H_SP,405022,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FIT_0113_2A_FI.L_SP,405024,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FIT_0113_2A_FI.LL_SP,405026,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FIT_0113_2A_FI.BLSP,405028,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FIT_0113_2A_FI.ORSP,405030,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FIT_0113_2A_FI.URSP,405032,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FIT_0113_2A_FI.RCSP,405034,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FIT_0113_2A_FI.INTK_SP,405036,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FIT_0113_2A_FI.Total,405038,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FIT_0113_2A_FI.INTK_Reset_SP,405194,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_1B_ZI.VALU,405208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_1B_ZI.Old_Val,405210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_1B_ZI.VMIN,405212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_1B_ZI.VMAX,405214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_1B_ZI.RawMin,405216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_1B_ZI.RawMax,405218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_1B_ZI.HH_SP,405220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_1B_ZI.H_SP,405222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_1B_ZI.L_SP,405224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_1B_ZI.LL_SP,405226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_1B_ZI.BLSP,405228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_1B_ZI.ORSP,405230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_1B_ZI.URSP,405232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_1B_ZI.RCSP,405234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_1B_ZI.INTK_SP,405236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_1B_ZI.Total,405238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_1B_ZI.INTK_Reset_SP,405394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_2B_ZI.VALU,405408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_2B_ZI.Old_Val,405410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_2B_ZI.VMIN,405412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_2B_ZI.VMAX,405414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_2B_ZI.RawMin,405416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_2B_ZI.RawMax,405418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_2B_ZI.HH_SP,405420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_2B_ZI.H_SP,405422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_2B_ZI.L_SP,405424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_2B_ZI.LL_SP,405426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_2B_ZI.BLSP,405428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_2B_ZI.ORSP,405430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_2B_ZI.URSP,405432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_2B_ZI.RCSP,405434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_2B_ZI.INTK_SP,405436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_2B_ZI.Total,405438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_2B_ZI.INTK_Reset_SP,405594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_3B_ZI.VALU,405608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_3B_ZI.Old_Val,405610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_3B_ZI.VMIN,405612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_3B_ZI.VMAX,405614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_3B_ZI.RawMin,405616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_3B_ZI.RawMax,405618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_3B_ZI.HH_SP,405620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_3B_ZI.H_SP,405622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_3B_ZI.L_SP,405624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_3B_ZI.LL_SP,405626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_3B_ZI.BLSP,405628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_3B_ZI.ORSP,405630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_3B_ZI.URSP,405632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_3B_ZI.RCSP,405634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_3B_ZI.INTK_SP,405636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_3B_ZI.Total,405638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_3B_ZI.INTK_Reset_SP,405794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_4B_ZI.VALU,405808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_4B_ZI.Old_Val,405810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_4B_ZI.VMIN,405812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_4B_ZI.VMAX,405814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_4B_ZI.RawMin,405816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_4B_ZI.RawMax,405818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_4B_ZI.HH_SP,405820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_4B_ZI.H_SP,405822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_4B_ZI.L_SP,405824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_4B_ZI.LL_SP,405826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_4B_ZI.BLSP,405828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_4B_ZI.ORSP,405830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_4B_ZI.URSP,405832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_4B_ZI.RCSP,405834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_4B_ZI.INTK_SP,405836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_4B_ZI.Total,405838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_4B_ZI.INTK_Reset_SP,405994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_5B_ZI.VALU,406008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_5B_ZI.Old_Val,406010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_5B_ZI.VMIN,406012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_5B_ZI.VMAX,406014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_5B_ZI.RawMin,406016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_5B_ZI.RawMax,406018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_5B_ZI.HH_SP,406020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_5B_ZI.H_SP,406022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_5B_ZI.L_SP,406024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_5B_ZI.LL_SP,406026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_5B_ZI.BLSP,406028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_5B_ZI.ORSP,406030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_5B_ZI.URSP,406032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_5B_ZI.RCSP,406034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_5B_ZI.INTK_SP,406036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_5B_ZI.Total,406038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_5B_ZI.INTK_Reset_SP,406194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_6B_ZI.VALU,406208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_6B_ZI.Old_Val,406210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_6B_ZI.VMIN,406212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_6B_ZI.VMAX,406214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_6B_ZI.RawMin,406216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_6B_ZI.RawMax,406218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_6B_ZI.HH_SP,406220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_6B_ZI.H_SP,406222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_6B_ZI.L_SP,406224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_6B_ZI.LL_SP,406226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_6B_ZI.BLSP,406228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_6B_ZI.ORSP,406230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_6B_ZI.URSP,406232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_6B_ZI.RCSP,406234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_6B_ZI.INTK_SP,406236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_6B_ZI.Total,406238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_6B_ZI.INTK_Reset_SP,406394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_7B_ZI.VALU,406408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_7B_ZI.Old_Val,406410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_7B_ZI.VMIN,406412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_7B_ZI.VMAX,406414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_7B_ZI.RawMin,406416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_7B_ZI.RawMax,406418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_7B_ZI.HH_SP,406420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_7B_ZI.H_SP,406422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_7B_ZI.L_SP,406424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_7B_ZI.LL_SP,406426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_7B_ZI.BLSP,406428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_7B_ZI.ORSP,406430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_7B_ZI.URSP,406432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_7B_ZI.RCSP,406434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_7B_ZI.INTK_SP,406436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_7B_ZI.Total,406438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_7B_ZI.INTK_Reset_SP,406594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_8B_ZI.VALU,406608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_8B_ZI.Old_Val,406610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_8B_ZI.VMIN,406612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_8B_ZI.VMAX,406614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_8B_ZI.RawMin,406616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_8B_ZI.RawMax,406618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_8B_ZI.HH_SP,406620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_8B_ZI.H_SP,406622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_8B_ZI.L_SP,406624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_8B_ZI.LL_SP,406626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_8B_ZI.BLSP,406628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_8B_ZI.ORSP,406630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_8B_ZI.URSP,406632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_8B_ZI.RCSP,406634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_8B_ZI.INTK_SP,406636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_8B_ZI.Total,406638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_8B_ZI.INTK_Reset_SP,406794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_FV_0103_9B_ZI.VALU,406808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_FV_0103_9B_ZI.Old_Val,406810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_FV_0103_9B_ZI.VMIN,406812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_FV_0103_9B_ZI.VMAX,406814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_FV_0103_9B_ZI.RawMin,406816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_9B_ZI.RawMax,406818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_FV_0103_9B_ZI.HH_SP,406820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_FV_0103_9B_ZI.H_SP,406822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_FV_0103_9B_ZI.L_SP,406824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_FV_0103_9B_ZI.LL_SP,406826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_FV_0103_9B_ZI.BLSP,406828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_FV_0103_9B_ZI.ORSP,406830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_FV_0103_9B_ZI.URSP,406832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_FV_0103_9B_ZI.RCSP,406834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_FV_0103_9B_ZI.INTK_SP,406836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_FV_0103_9B_ZI.Total,406838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_FV_0103_9B_ZI.INTK_Reset_SP,406994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_1_VI1.VALU,407008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_1_VI1.Old_Val,407010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_1_VI1.VMIN,407012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_1_VI1.VMAX,407014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_1_VI1.RawMin,407016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI1.RawMax,407018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI1.HH_SP,407020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_1_VI1.H_SP,407022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_1_VI1.L_SP,407024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_1_VI1.LL_SP,407026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_1_VI1.BLSP,407028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_1_VI1.ORSP,407030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_1_VI1.URSP,407032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_1_VI1.RCSP,407034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_1_VI1.INTK_SP,407036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_1_VI1.Total,407038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_1_VI1.INTK_Reset_SP,407194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_1_VI2.VALU,407208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_1_VI2.Old_Val,407210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_1_VI2.VMIN,407212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_1_VI2.VMAX,407214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_1_VI2.RawMin,407216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI2.RawMax,407218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI2.HH_SP,407220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_1_VI2.H_SP,407222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_1_VI2.L_SP,407224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_1_VI2.LL_SP,407226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_1_VI2.BLSP,407228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_1_VI2.ORSP,407230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_1_VI2.URSP,407232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_1_VI2.RCSP,407234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_1_VI2.INTK_SP,407236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_1_VI2.Total,407238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_1_VI2.INTK_Reset_SP,407394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_1_VI3.VALU,407408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_1_VI3.Old_Val,407410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_1_VI3.VMIN,407412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_1_VI3.VMAX,407414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_1_VI3.RawMin,407416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI3.RawMax,407418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI3.HH_SP,407420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_1_VI3.H_SP,407422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_1_VI3.L_SP,407424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_1_VI3.LL_SP,407426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_1_VI3.BLSP,407428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_1_VI3.ORSP,407430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_1_VI3.URSP,407432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_1_VI3.RCSP,407434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_1_VI3.INTK_SP,407436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_1_VI3.Total,407438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_1_VI3.INTK_Reset_SP,407594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_1_VI4.VALU,407608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_1_VI4.Old_Val,407610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_1_VI4.VMIN,407612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_1_VI4.VMAX,407614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_1_VI4.RawMin,407616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI4.RawMax,407618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_1_VI4.HH_SP,407620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_1_VI4.H_SP,407622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_1_VI4.L_SP,407624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_1_VI4.LL_SP,407626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_1_VI4.BLSP,407628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_1_VI4.ORSP,407630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_1_VI4.URSP,407632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_1_VI4.RCSP,407634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_1_VI4.INTK_SP,407636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_1_VI4.Total,407638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_1_VI4.INTK_Reset_SP,407794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_2_VI1.VALU,407808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_2_VI1.Old_Val,407810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_2_VI1.VMIN,407812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_2_VI1.VMAX,407814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_2_VI1.RawMin,407816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI1.RawMax,407818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI1.HH_SP,407820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_2_VI1.H_SP,407822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_2_VI1.L_SP,407824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_2_VI1.LL_SP,407826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_2_VI1.BLSP,407828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_2_VI1.ORSP,407830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_2_VI1.URSP,407832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_2_VI1.RCSP,407834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_2_VI1.INTK_SP,407836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_2_VI1.Total,407838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_2_VI1.INTK_Reset_SP,407994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_2_VI2.VALU,408008,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_2_VI2.Old_Val,408010,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_2_VI2.VMIN,408012,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_2_VI2.VMAX,408014,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_2_VI2.RawMin,408016,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI2.RawMax,408018,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI2.HH_SP,408020,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_2_VI2.H_SP,408022,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_2_VI2.L_SP,408024,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_2_VI2.LL_SP,408026,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_2_VI2.BLSP,408028,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_2_VI2.ORSP,408030,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_2_VI2.URSP,408032,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_2_VI2.RCSP,408034,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_2_VI2.INTK_SP,408036,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_2_VI2.Total,408038,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_2_VI2.INTK_Reset_SP,408194,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_2_VI3.VALU,408208,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_2_VI3.Old_Val,408210,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_2_VI3.VMIN,408212,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_2_VI3.VMAX,408214,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_2_VI3.RawMin,408216,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI3.RawMax,408218,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI3.HH_SP,408220,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_2_VI3.H_SP,408222,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_2_VI3.L_SP,408224,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_2_VI3.LL_SP,408226,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_2_VI3.BLSP,408228,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_2_VI3.ORSP,408230,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_2_VI3.URSP,408232,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_2_VI3.RCSP,408234,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_2_VI3.INTK_SP,408236,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_2_VI3.Total,408238,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_2_VI3.INTK_Reset_SP,408394,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_2_VI4.VALU,408408,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_2_VI4.Old_Val,408410,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_2_VI4.VMIN,408412,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_2_VI4.VMAX,408414,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_2_VI4.RawMin,408416,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI4.RawMax,408418,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_2_VI4.HH_SP,408420,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_2_VI4.H_SP,408422,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_2_VI4.L_SP,408424,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_2_VI4.LL_SP,408426,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_2_VI4.BLSP,408428,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_2_VI4.ORSP,408430,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_2_VI4.URSP,408432,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_2_VI4.RCSP,408434,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_2_VI4.INTK_SP,408436,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_2_VI4.Total,408438,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_2_VI4.INTK_Reset_SP,408594,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_3_VI1.VALU,408608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_3_VI1.Old_Val,408610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_3_VI1.VMIN,408612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_3_VI1.VMAX,408614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_3_VI1.RawMin,408616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI1.RawMax,408618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI1.HH_SP,408620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_3_VI1.H_SP,408622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_3_VI1.L_SP,408624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_3_VI1.LL_SP,408626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_3_VI1.BLSP,408628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_3_VI1.ORSP,408630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_3_VI1.URSP,408632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_3_VI1.RCSP,408634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_3_VI1.INTK_SP,408636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_3_VI1.Total,408638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_3_VI1.INTK_Reset_SP,408794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_3_VI2.VALU,408808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_3_VI2.Old_Val,408810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_3_VI2.VMIN,408812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_3_VI2.VMAX,408814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_3_VI2.RawMin,408816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI2.RawMax,408818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI2.HH_SP,408820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_3_VI2.H_SP,408822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_3_VI2.L_SP,408824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_3_VI2.LL_SP,408826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_3_VI2.BLSP,408828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_3_VI2.ORSP,408830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_3_VI2.URSP,408832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_3_VI2.RCSP,408834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_3_VI2.INTK_SP,408836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_3_VI2.Total,408838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_3_VI2.INTK_Reset_SP,408994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_3_VI3.VALU,409008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_3_VI3.Old_Val,409010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_3_VI3.VMIN,409012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_3_VI3.VMAX,409014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_3_VI3.RawMin,409016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI3.RawMax,409018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI3.HH_SP,409020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_3_VI3.H_SP,409022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_3_VI3.L_SP,409024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_3_VI3.LL_SP,409026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_3_VI3.BLSP,409028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_3_VI3.ORSP,409030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_3_VI3.URSP,409032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_3_VI3.RCSP,409034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_3_VI3.INTK_SP,409036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_3_VI3.Total,409038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_3_VI3.INTK_Reset_SP,409194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_3_VI4.VALU,409208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_3_VI4.Old_Val,409210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_3_VI4.VMIN,409212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_3_VI4.VMAX,409214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_3_VI4.RawMin,409216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI4.RawMax,409218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_3_VI4.HH_SP,409220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_3_VI4.H_SP,409222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_3_VI4.L_SP,409224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_3_VI4.LL_SP,409226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_3_VI4.BLSP,409228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_3_VI4.ORSP,409230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_3_VI4.URSP,409232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_3_VI4.RCSP,409234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_3_VI4.INTK_SP,409236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_3_VI4.Total,409238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_3_VI4.INTK_Reset_SP,409394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_4_VI1.VALU,409408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_4_VI1.Old_Val,409410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_4_VI1.VMIN,409412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_4_VI1.VMAX,409414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_4_VI1.RawMin,409416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI1.RawMax,409418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI1.HH_SP,409420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_4_VI1.H_SP,409422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_4_VI1.L_SP,409424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_4_VI1.LL_SP,409426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_4_VI1.BLSP,409428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_4_VI1.ORSP,409430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_4_VI1.URSP,409432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_4_VI1.RCSP,409434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_4_VI1.INTK_SP,409436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_4_VI1.Total,409438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_4_VI1.INTK_Reset_SP,409594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_4_VI2.VALU,409608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_4_VI2.Old_Val,409610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_4_VI2.VMIN,409612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_4_VI2.VMAX,409614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_4_VI2.RawMin,409616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI2.RawMax,409618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI2.HH_SP,409620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_4_VI2.H_SP,409622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_4_VI2.L_SP,409624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_4_VI2.LL_SP,409626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_4_VI2.BLSP,409628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_4_VI2.ORSP,409630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_4_VI2.URSP,409632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_4_VI2.RCSP,409634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_4_VI2.INTK_SP,409636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_4_VI2.Total,409638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_4_VI2.INTK_Reset_SP,409794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_4_VI3.VALU,409808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_4_VI3.Old_Val,409810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_4_VI3.VMIN,409812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_4_VI3.VMAX,409814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_4_VI3.RawMin,409816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI3.RawMax,409818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI3.HH_SP,409820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_4_VI3.H_SP,409822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_4_VI3.L_SP,409824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_4_VI3.LL_SP,409826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_4_VI3.BLSP,409828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_4_VI3.ORSP,409830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_4_VI3.URSP,409832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_4_VI3.RCSP,409834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_4_VI3.INTK_SP,409836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_4_VI3.Total,409838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_4_VI3.INTK_Reset_SP,409994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_4_VI4.VALU,410008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_4_VI4.Old_Val,410010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_4_VI4.VMIN,410012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_4_VI4.VMAX,410014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_4_VI4.RawMin,410016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI4.RawMax,410018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_4_VI4.HH_SP,410020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_4_VI4.H_SP,410022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_4_VI4.L_SP,410024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_4_VI4.LL_SP,410026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_4_VI4.BLSP,410028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_4_VI4.ORSP,410030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_4_VI4.URSP,410032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_4_VI4.RCSP,410034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_4_VI4.INTK_SP,410036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_4_VI4.Total,410038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_4_VI4.INTK_Reset_SP,410194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_5_VI1.VALU,410208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_5_VI1.Old_Val,410210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_5_VI1.VMIN,410212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_5_VI1.VMAX,410214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_5_VI1.RawMin,410216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI1.RawMax,410218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI1.HH_SP,410220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_5_VI1.H_SP,410222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_5_VI1.L_SP,410224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_5_VI1.LL_SP,410226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_5_VI1.BLSP,410228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_5_VI1.ORSP,410230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_5_VI1.URSP,410232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_5_VI1.RCSP,410234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_5_VI1.INTK_SP,410236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_5_VI1.Total,410238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_5_VI1.INTK_Reset_SP,410394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_5_VI2.VALU,410408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_5_VI2.Old_Val,410410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_5_VI2.VMIN,410412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_5_VI2.VMAX,410414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_5_VI2.RawMin,410416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI2.RawMax,410418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI2.HH_SP,410420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_5_VI2.H_SP,410422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_5_VI2.L_SP,410424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_5_VI2.LL_SP,410426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_5_VI2.BLSP,410428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_5_VI2.ORSP,410430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_5_VI2.URSP,410432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_5_VI2.RCSP,410434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_5_VI2.INTK_SP,410436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_5_VI2.Total,410438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_5_VI2.INTK_Reset_SP,410594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_5_VI3.VALU,410608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_5_VI3.Old_Val,410610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_5_VI3.VMIN,410612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_5_VI3.VMAX,410614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_5_VI3.RawMin,410616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI3.RawMax,410618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI3.HH_SP,410620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_5_VI3.H_SP,410622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_5_VI3.L_SP,410624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_5_VI3.LL_SP,410626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_5_VI3.BLSP,410628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_5_VI3.ORSP,410630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_5_VI3.URSP,410632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_5_VI3.RCSP,410634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_5_VI3.INTK_SP,410636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_5_VI3.Total,410638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_5_VI3.INTK_Reset_SP,410794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_5_VI4.VALU,410808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_5_VI4.Old_Val,410810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_5_VI4.VMIN,410812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_5_VI4.VMAX,410814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_5_VI4.RawMin,410816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI4.RawMax,410818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_5_VI4.HH_SP,410820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_5_VI4.H_SP,410822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_5_VI4.L_SP,410824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_5_VI4.LL_SP,410826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_5_VI4.BLSP,410828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_5_VI4.ORSP,410830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_5_VI4.URSP,410832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_5_VI4.RCSP,410834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_5_VI4.INTK_SP,410836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_5_VI4.Total,410838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_5_VI4.INTK_Reset_SP,410994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_6_VI1.VALU,411008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_6_VI1.Old_Val,411010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_6_VI1.VMIN,411012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_6_VI1.VMAX,411014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_6_VI1.RawMin,411016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI1.RawMax,411018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI1.HH_SP,411020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_6_VI1.H_SP,411022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_6_VI1.L_SP,411024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_6_VI1.LL_SP,411026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_6_VI1.BLSP,411028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_6_VI1.ORSP,411030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_6_VI1.URSP,411032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_6_VI1.RCSP,411034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_6_VI1.INTK_SP,411036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_6_VI1.Total,411038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_6_VI1.INTK_Reset_SP,411194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_6_VI2.VALU,411208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_6_VI2.Old_Val,411210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_6_VI2.VMIN,411212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_6_VI2.VMAX,411214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_6_VI2.RawMin,411216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI2.RawMax,411218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI2.HH_SP,411220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_6_VI2.H_SP,411222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_6_VI2.L_SP,411224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_6_VI2.LL_SP,411226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_6_VI2.BLSP,411228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_6_VI2.ORSP,411230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_6_VI2.URSP,411232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_6_VI2.RCSP,411234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_6_VI2.INTK_SP,411236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_6_VI2.Total,411238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_6_VI2.INTK_Reset_SP,411394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_6_VI3.VALU,411408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_6_VI3.Old_Val,411410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_6_VI3.VMIN,411412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_6_VI3.VMAX,411414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_6_VI3.RawMin,411416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI3.RawMax,411418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI3.HH_SP,411420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_6_VI3.H_SP,411422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_6_VI3.L_SP,411424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_6_VI3.LL_SP,411426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_6_VI3.BLSP,411428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_6_VI3.ORSP,411430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_6_VI3.URSP,411432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_6_VI3.RCSP,411434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_6_VI3.INTK_SP,411436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_6_VI3.Total,411438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_6_VI3.INTK_Reset_SP,411594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_6_VI4.VALU,411608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_6_VI4.Old_Val,411610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_6_VI4.VMIN,411612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_6_VI4.VMAX,411614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_6_VI4.RawMin,411616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI4.RawMax,411618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_6_VI4.HH_SP,411620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_6_VI4.H_SP,411622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_6_VI4.L_SP,411624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_6_VI4.LL_SP,411626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_6_VI4.BLSP,411628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_6_VI4.ORSP,411630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_6_VI4.URSP,411632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_6_VI4.RCSP,411634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_6_VI4.INTK_SP,411636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_6_VI4.Total,411638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_6_VI4.INTK_Reset_SP,411794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_7_VI1.VALU,411808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_7_VI1.Old_Val,411810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_7_VI1.VMIN,411812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_7_VI1.VMAX,411814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_7_VI1.RawMin,411816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI1.RawMax,411818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI1.HH_SP,411820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_7_VI1.H_SP,411822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_7_VI1.L_SP,411824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_7_VI1.LL_SP,411826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_7_VI1.BLSP,411828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_7_VI1.ORSP,411830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_7_VI1.URSP,411832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_7_VI1.RCSP,411834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_7_VI1.INTK_SP,411836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_7_VI1.Total,411838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_7_VI1.INTK_Reset_SP,411994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_7_VI2.VALU,412008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_7_VI2.Old_Val,412010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_7_VI2.VMIN,412012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_7_VI2.VMAX,412014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_7_VI2.RawMin,412016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI2.RawMax,412018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI2.HH_SP,412020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_7_VI2.H_SP,412022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_7_VI2.L_SP,412024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_7_VI2.LL_SP,412026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_7_VI2.BLSP,412028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_7_VI2.ORSP,412030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_7_VI2.URSP,412032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_7_VI2.RCSP,412034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_7_VI2.INTK_SP,412036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_7_VI2.Total,412038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_7_VI2.INTK_Reset_SP,412194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_7_VI3.VALU,412208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_7_VI3.Old_Val,412210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_7_VI3.VMIN,412212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_7_VI3.VMAX,412214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_7_VI3.RawMin,412216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI3.RawMax,412218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI3.HH_SP,412220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_7_VI3.H_SP,412222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_7_VI3.L_SP,412224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_7_VI3.LL_SP,412226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_7_VI3.BLSP,412228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_7_VI3.ORSP,412230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_7_VI3.URSP,412232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_7_VI3.RCSP,412234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_7_VI3.INTK_SP,412236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_7_VI3.Total,412238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_7_VI3.INTK_Reset_SP,412394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_7_VI4.VALU,412408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_7_VI4.Old_Val,412410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_7_VI4.VMIN,412412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_7_VI4.VMAX,412414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_7_VI4.RawMin,412416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI4.RawMax,412418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_7_VI4.HH_SP,412420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_7_VI4.H_SP,412422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_7_VI4.L_SP,412424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_7_VI4.LL_SP,412426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_7_VI4.BLSP,412428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_7_VI4.ORSP,412430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_7_VI4.URSP,412432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_7_VI4.RCSP,412434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_7_VI4.INTK_SP,412436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_7_VI4.Total,412438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_7_VI4.INTK_Reset_SP,412594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_8_VI1.VALU,412608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_8_VI1.Old_Val,412610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_8_VI1.VMIN,412612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_8_VI1.VMAX,412614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_8_VI1.RawMin,412616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI1.RawMax,412618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI1.HH_SP,412620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_8_VI1.H_SP,412622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_8_VI1.L_SP,412624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_8_VI1.LL_SP,412626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_8_VI1.BLSP,412628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_8_VI1.ORSP,412630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_8_VI1.URSP,412632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_8_VI1.RCSP,412634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_8_VI1.INTK_SP,412636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_8_VI1.Total,412638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_8_VI1.INTK_Reset_SP,412794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_8_VI2.VALU,412808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_8_VI2.Old_Val,412810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_8_VI2.VMIN,412812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_8_VI2.VMAX,412814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_8_VI2.RawMin,412816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI2.RawMax,412818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI2.HH_SP,412820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_8_VI2.H_SP,412822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_8_VI2.L_SP,412824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_8_VI2.LL_SP,412826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_8_VI2.BLSP,412828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_8_VI2.ORSP,412830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_8_VI2.URSP,412832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_8_VI2.RCSP,412834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_8_VI2.INTK_SP,412836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_8_VI2.Total,412838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_8_VI2.INTK_Reset_SP,412994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_8_VI3.VALU,413008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_8_VI3.Old_Val,413010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_8_VI3.VMIN,413012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_8_VI3.VMAX,413014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_8_VI3.RawMin,413016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI3.RawMax,413018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI3.HH_SP,413020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_8_VI3.H_SP,413022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_8_VI3.L_SP,413024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_8_VI3.LL_SP,413026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_8_VI3.BLSP,413028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_8_VI3.ORSP,413030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_8_VI3.URSP,413032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_8_VI3.RCSP,413034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_8_VI3.INTK_SP,413036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_8_VI3.Total,413038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_8_VI3.INTK_Reset_SP,413194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_8_VI4.VALU,413208,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_8_VI4.Old_Val,413210,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_8_VI4.VMIN,413212,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_8_VI4.VMAX,413214,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_8_VI4.RawMin,413216,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI4.RawMax,413218,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_8_VI4.HH_SP,413220,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_8_VI4.H_SP,413222,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_8_VI4.L_SP,413224,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_8_VI4.LL_SP,413226,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_8_VI4.BLSP,413228,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_8_VI4.ORSP,413230,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_8_VI4.URSP,413232,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_8_VI4.RCSP,413234,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_8_VI4.INTK_SP,413236,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_8_VI4.Total,413238,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_8_VI4.INTK_Reset_SP,413394,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_9_VI1.VALU,413408,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_9_VI1.Old_Val,413410,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_9_VI1.VMIN,413412,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_9_VI1.VMAX,413414,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_9_VI1.RawMin,413416,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI1.RawMax,413418,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI1.HH_SP,413420,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_9_VI1.H_SP,413422,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_9_VI1.L_SP,413424,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_9_VI1.LL_SP,413426,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_9_VI1.BLSP,413428,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_9_VI1.ORSP,413430,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_9_VI1.URSP,413432,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_9_VI1.RCSP,413434,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_9_VI1.INTK_SP,413436,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_9_VI1.Total,413438,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_9_VI1.INTK_Reset_SP,413594,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_9_VI2.VALU,413608,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_9_VI2.Old_Val,413610,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_9_VI2.VMIN,413612,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_9_VI2.VMAX,413614,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_9_VI2.RawMin,413616,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI2.RawMax,413618,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI2.HH_SP,413620,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_9_VI2.H_SP,413622,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_9_VI2.L_SP,413624,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_9_VI2.LL_SP,413626,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_9_VI2.BLSP,413628,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_9_VI2.ORSP,413630,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_9_VI2.URSP,413632,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_9_VI2.RCSP,413634,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_9_VI2.INTK_SP,413636,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_9_VI2.Total,413638,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_9_VI2.INTK_Reset_SP,413794,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_9_VI3.VALU,413808,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_9_VI3.Old_Val,413810,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_9_VI3.VMIN,413812,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_9_VI3.VMAX,413814,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_9_VI3.RawMin,413816,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI3.RawMax,413818,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI3.HH_SP,413820,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_9_VI3.H_SP,413822,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_9_VI3.L_SP,413824,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_9_VI3.LL_SP,413826,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_9_VI3.BLSP,413828,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_9_VI3.ORSP,413830,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_9_VI3.URSP,413832,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_9_VI3.RCSP,413834,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_9_VI3.INTK_SP,413836,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_9_VI3.Total,413838,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_9_VI3.INTK_Reset_SP,413994,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_MTR_0103_9_VI4.VALU,414008,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_MTR_0103_9_VI4.Old_Val,414010,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_MTR_0103_9_VI4.VMIN,414012,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_MTR_0103_9_VI4.VMAX,414014,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_MTR_0103_9_VI4.RawMin,414016,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI4.RawMax,414018,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_MTR_0103_9_VI4.HH_SP,414020,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_MTR_0103_9_VI4.H_SP,414022,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_MTR_0103_9_VI4.L_SP,414024,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_MTR_0103_9_VI4.LL_SP,414026,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_MTR_0103_9_VI4.BLSP,414028,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_MTR_0103_9_VI4.ORSP,414030,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_MTR_0103_9_VI4.URSP,414032,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_MTR_0103_9_VI4.RCSP,414034,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_MTR_0103_9_VI4.INTK_SP,414036,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_MTR_0103_9_VI4.Total,414038,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_MTR_0103_9_VI4.INTK_Reset_SP,414194,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0102_1_PI.VALU,414208,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0102_1_PI.Old_Val,414210,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0102_1_PI.VMIN,414212,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0102_1_PI.VMAX,414214,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0102_1_PI.RawMin,414216,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0102_1_PI.RawMax,414218,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0102_1_PI.HH_SP,414220,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0102_1_PI.H_SP,414222,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0102_1_PI.L_SP,414224,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0102_1_PI.LL_SP,414226,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0102_1_PI.BLSP,414228,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0102_1_PI.ORSP,414230,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0102_1_PI.URSP,414232,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0102_1_PI.RCSP,414234,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0102_1_PI.INTK_SP,414236,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0102_1_PI.Total,414238,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0102_1_PI.INTK_Reset_SP,414394,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0102_2_PI.VALU,414408,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0102_2_PI.Old_Val,414410,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0102_2_PI.VMIN,414412,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0102_2_PI.VMAX,414414,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0102_2_PI.RawMin,414416,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0102_2_PI.RawMax,414418,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0102_2_PI.HH_SP,414420,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0102_2_PI.H_SP,414422,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0102_2_PI.L_SP,414424,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0102_2_PI.LL_SP,414426,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0102_2_PI.BLSP,414428,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0102_2_PI.ORSP,414430,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0102_2_PI.URSP,414432,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0102_2_PI.RCSP,414434,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0102_2_PI.INTK_SP,414436,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0102_2_PI.Total,414438,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0102_2_PI.INTK_Reset_SP,414594,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_1_PI.VALU,414608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_1_PI.Old_Val,414610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_1_PI.VMIN,414612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_1_PI.VMAX,414614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_1_PI.RawMin,414616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_1_PI.RawMax,414618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_1_PI.HH_SP,414620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_1_PI.H_SP,414622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_1_PI.L_SP,414624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_1_PI.LL_SP,414626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_1_PI.BLSP,414628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_1_PI.ORSP,414630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_1_PI.URSP,414632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_1_PI.RCSP,414634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_1_PI.INTK_SP,414636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_1_PI.Total,414638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_1_PI.INTK_Reset_SP,414794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_2_PI.VALU,414808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_2_PI.Old_Val,414810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_2_PI.VMIN,414812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_2_PI.VMAX,414814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_2_PI.RawMin,414816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_2_PI.RawMax,414818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_2_PI.HH_SP,414820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_2_PI.H_SP,414822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_2_PI.L_SP,414824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_2_PI.LL_SP,414826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_2_PI.BLSP,414828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_2_PI.ORSP,414830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_2_PI.URSP,414832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_2_PI.RCSP,414834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_2_PI.INTK_SP,414836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_2_PI.Total,414838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_2_PI.INTK_Reset_SP,414994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_3_PI.VALU,415008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_3_PI.Old_Val,415010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_3_PI.VMIN,415012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_3_PI.VMAX,415014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_3_PI.RawMin,415016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_3_PI.RawMax,415018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_3_PI.HH_SP,415020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_3_PI.H_SP,415022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_3_PI.L_SP,415024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_3_PI.LL_SP,415026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_3_PI.BLSP,415028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_3_PI.ORSP,415030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_3_PI.URSP,415032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_3_PI.RCSP,415034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_3_PI.INTK_SP,415036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_3_PI.Total,415038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_3_PI.INTK_Reset_SP,415194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_4_PI.VALU,415208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_4_PI.Old_Val,415210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_4_PI.VMIN,415212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_4_PI.VMAX,415214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_4_PI.RawMin,415216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_4_PI.RawMax,415218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_4_PI.HH_SP,415220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_4_PI.H_SP,415222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_4_PI.L_SP,415224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_4_PI.LL_SP,415226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_4_PI.BLSP,415228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_4_PI.ORSP,415230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_4_PI.URSP,415232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_4_PI.RCSP,415234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_4_PI.INTK_SP,415236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_4_PI.Total,415238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_4_PI.INTK_Reset_SP,415394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_5_PI.VALU,415408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_5_PI.Old_Val,415410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_5_PI.VMIN,415412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_5_PI.VMAX,415414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_5_PI.RawMin,415416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_5_PI.RawMax,415418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_5_PI.HH_SP,415420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_5_PI.H_SP,415422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_5_PI.L_SP,415424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_5_PI.LL_SP,415426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_5_PI.BLSP,415428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_5_PI.ORSP,415430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_5_PI.URSP,415432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_5_PI.RCSP,415434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_5_PI.INTK_SP,415436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_5_PI.Total,415438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_5_PI.INTK_Reset_SP,415594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_6_PI.VALU,415608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_6_PI.Old_Val,415610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_6_PI.VMIN,415612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_6_PI.VMAX,415614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_6_PI.RawMin,415616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_6_PI.RawMax,415618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_6_PI.HH_SP,415620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_6_PI.H_SP,415622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_6_PI.L_SP,415624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_6_PI.LL_SP,415626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_6_PI.BLSP,415628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_6_PI.ORSP,415630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_6_PI.URSP,415632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_6_PI.RCSP,415634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_6_PI.INTK_SP,415636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_6_PI.Total,415638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_6_PI.INTK_Reset_SP,415794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_7_PI.VALU,415808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_7_PI.Old_Val,415810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_7_PI.VMIN,415812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_7_PI.VMAX,415814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_7_PI.RawMin,415816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_7_PI.RawMax,415818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_7_PI.HH_SP,415820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_7_PI.H_SP,415822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_7_PI.L_SP,415824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_7_PI.LL_SP,415826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_7_PI.BLSP,415828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_7_PI.ORSP,415830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_7_PI.URSP,415832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_7_PI.RCSP,415834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_7_PI.INTK_SP,415836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_7_PI.Total,415838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_7_PI.INTK_Reset_SP,415994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_8_PI.VALU,416008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_8_PI.Old_Val,416010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_8_PI.VMIN,416012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_8_PI.VMAX,416014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_8_PI.RawMin,416016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_8_PI.RawMax,416018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_8_PI.HH_SP,416020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_8_PI.H_SP,416022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_8_PI.L_SP,416024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_8_PI.LL_SP,416026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_8_PI.BLSP,416028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_8_PI.ORSP,416030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_8_PI.URSP,416032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_8_PI.RCSP,416034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_8_PI.INTK_SP,416036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_8_PI.Total,416038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_8_PI.INTK_Reset_SP,416194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0103_9_PI.VALU,416208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0103_9_PI.Old_Val,416210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0103_9_PI.VMIN,416212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0103_9_PI.VMAX,416214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0103_9_PI.RawMin,416216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_9_PI.RawMax,416218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0103_9_PI.HH_SP,416220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0103_9_PI.H_SP,416222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0103_9_PI.L_SP,416224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0103_9_PI.LL_SP,416226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0103_9_PI.BLSP,416228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0103_9_PI.ORSP,416230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0103_9_PI.URSP,416232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0103_9_PI.RCSP,416234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0103_9_PI.INTK_SP,416236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0103_9_PI.Total,416238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0103_9_PI.INTK_Reset_SP,416394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PIT_0104_1_PI.VALU,416408,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PIT_0104_1_PI.Old_Val,416410,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PIT_0104_1_PI.VMIN,416412,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PIT_0104_1_PI.VMAX,416414,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PIT_0104_1_PI.RawMin,416416,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0104_1_PI.RawMax,416418,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PIT_0104_1_PI.HH_SP,416420,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PIT_0104_1_PI.H_SP,416422,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PIT_0104_1_PI.L_SP,416424,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PIT_0104_1_PI.LL_SP,416426,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PIT_0104_1_PI.BLSP,416428,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PIT_0104_1_PI.ORSP,416430,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PIT_0104_1_PI.URSP,416432,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PIT_0104_1_PI.RCSP,416434,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PIT_0104_1_PI.INTK_SP,416436,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PIT_0104_1_PI.Total,416438,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PIT_0104_1_PI.INTK_Reset_SP,416594,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_1_VI1.VALU,416608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_1_VI1.Old_Val,416610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_1_VI1.VMIN,416612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_1_VI1.VMAX,416614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_1_VI1.RawMin,416616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI1.RawMax,416618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI1.HH_SP,416620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_1_VI1.H_SP,416622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_1_VI1.L_SP,416624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_1_VI1.LL_SP,416626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_1_VI1.BLSP,416628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_1_VI1.ORSP,416630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_1_VI1.URSP,416632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_1_VI1.RCSP,416634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_1_VI1.INTK_SP,416636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_1_VI1.Total,416638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_1_VI1.INTK_Reset_SP,416794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_1_VI2.VALU,416808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_1_VI2.Old_Val,416810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_1_VI2.VMIN,416812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_1_VI2.VMAX,416814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_1_VI2.RawMin,416816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI2.RawMax,416818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI2.HH_SP,416820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_1_VI2.H_SP,416822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_1_VI2.L_SP,416824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_1_VI2.LL_SP,416826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_1_VI2.BLSP,416828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_1_VI2.ORSP,416830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_1_VI2.URSP,416832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_1_VI2.RCSP,416834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_1_VI2.INTK_SP,416836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_1_VI2.Total,416838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_1_VI2.INTK_Reset_SP,416994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_1_VI3.VALU,417008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_1_VI3.Old_Val,417010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_1_VI3.VMIN,417012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_1_VI3.VMAX,417014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_1_VI3.RawMin,417016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI3.RawMax,417018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI3.HH_SP,417020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_1_VI3.H_SP,417022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_1_VI3.L_SP,417024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_1_VI3.LL_SP,417026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_1_VI3.BLSP,417028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_1_VI3.ORSP,417030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_1_VI3.URSP,417032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_1_VI3.RCSP,417034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_1_VI3.INTK_SP,417036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_1_VI3.Total,417038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_1_VI3.INTK_Reset_SP,417194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_1_VI4.VALU,417208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_1_VI4.Old_Val,417210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_1_VI4.VMIN,417212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_1_VI4.VMAX,417214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_1_VI4.RawMin,417216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI4.RawMax,417218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI4.HH_SP,417220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_1_VI4.H_SP,417222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_1_VI4.L_SP,417224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_1_VI4.LL_SP,417226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_1_VI4.BLSP,417228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_1_VI4.ORSP,417230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_1_VI4.URSP,417232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_1_VI4.RCSP,417234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_1_VI4.INTK_SP,417236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_1_VI4.Total,417238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_1_VI4.INTK_Reset_SP,417394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_1_VI5.VALU,417408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_1_VI5.Old_Val,417410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_1_VI5.VMIN,417412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_1_VI5.VMAX,417414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_1_VI5.RawMin,417416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI5.RawMax,417418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_1_VI5.HH_SP,417420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_1_VI5.H_SP,417422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_1_VI5.L_SP,417424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_1_VI5.LL_SP,417426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_1_VI5.BLSP,417428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_1_VI5.ORSP,417430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_1_VI5.URSP,417432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_1_VI5.RCSP,417434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_1_VI5.INTK_SP,417436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_1_VI5.Total,417438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_1_VI5.INTK_Reset_SP,417594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_2_VI1.VALU,417608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_2_VI1.Old_Val,417610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_2_VI1.VMIN,417612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_2_VI1.VMAX,417614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_2_VI1.RawMin,417616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI1.RawMax,417618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI1.HH_SP,417620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_2_VI1.H_SP,417622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_2_VI1.L_SP,417624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_2_VI1.LL_SP,417626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_2_VI1.BLSP,417628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_2_VI1.ORSP,417630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_2_VI1.URSP,417632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_2_VI1.RCSP,417634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_2_VI1.INTK_SP,417636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_2_VI1.Total,417638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_2_VI1.INTK_Reset_SP,417794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_2_VI2.VALU,417808,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_2_VI2.Old_Val,417810,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_2_VI2.VMIN,417812,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_2_VI2.VMAX,417814,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_2_VI2.RawMin,417816,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI2.RawMax,417818,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI2.HH_SP,417820,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_2_VI2.H_SP,417822,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_2_VI2.L_SP,417824,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_2_VI2.LL_SP,417826,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_2_VI2.BLSP,417828,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_2_VI2.ORSP,417830,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_2_VI2.URSP,417832,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_2_VI2.RCSP,417834,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_2_VI2.INTK_SP,417836,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_2_VI2.Total,417838,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_2_VI2.INTK_Reset_SP,417994,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_2_VI3.VALU,418008,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_2_VI3.Old_Val,418010,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_2_VI3.VMIN,418012,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_2_VI3.VMAX,418014,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_2_VI3.RawMin,418016,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI3.RawMax,418018,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI3.HH_SP,418020,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_2_VI3.H_SP,418022,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_2_VI3.L_SP,418024,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_2_VI3.LL_SP,418026,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_2_VI3.BLSP,418028,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_2_VI3.ORSP,418030,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_2_VI3.URSP,418032,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_2_VI3.RCSP,418034,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_2_VI3.INTK_SP,418036,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_2_VI3.Total,418038,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_2_VI3.INTK_Reset_SP,418194,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_2_VI4.VALU,418208,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_2_VI4.Old_Val,418210,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_2_VI4.VMIN,418212,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_2_VI4.VMAX,418214,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_2_VI4.RawMin,418216,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI4.RawMax,418218,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI4.HH_SP,418220,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_2_VI4.H_SP,418222,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_2_VI4.L_SP,418224,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_2_VI4.LL_SP,418226,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_2_VI4.BLSP,418228,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_2_VI4.ORSP,418230,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_2_VI4.URSP,418232,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_2_VI4.RCSP,418234,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_2_VI4.INTK_SP,418236,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_2_VI4.Total,418238,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_2_VI4.INTK_Reset_SP,418394,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_2_VI5.VALU,418408,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_2_VI5.Old_Val,418410,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_2_VI5.VMIN,418412,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_2_VI5.VMAX,418414,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_2_VI5.RawMin,418416,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI5.RawMax,418418,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_2_VI5.HH_SP,418420,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_2_VI5.H_SP,418422,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_2_VI5.L_SP,418424,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_2_VI5.LL_SP,418426,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_2_VI5.BLSP,418428,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_2_VI5.ORSP,418430,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_2_VI5.URSP,418432,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_2_VI5.RCSP,418434,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_2_VI5.INTK_SP,418436,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_2_VI5.Total,418438,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_2_VI5.INTK_Reset_SP,418594,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_3_VI1.VALU,418608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_3_VI1.Old_Val,418610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_3_VI1.VMIN,418612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_3_VI1.VMAX,418614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_3_VI1.RawMin,418616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI1.RawMax,418618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI1.HH_SP,418620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_3_VI1.H_SP,418622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_3_VI1.L_SP,418624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_3_VI1.LL_SP,418626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_3_VI1.BLSP,418628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_3_VI1.ORSP,418630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_3_VI1.URSP,418632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_3_VI1.RCSP,418634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_3_VI1.INTK_SP,418636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_3_VI1.Total,418638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_3_VI1.INTK_Reset_SP,418794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_3_VI2.VALU,418808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_3_VI2.Old_Val,418810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_3_VI2.VMIN,418812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_3_VI2.VMAX,418814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_3_VI2.RawMin,418816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI2.RawMax,418818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI2.HH_SP,418820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_3_VI2.H_SP,418822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_3_VI2.L_SP,418824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_3_VI2.LL_SP,418826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_3_VI2.BLSP,418828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_3_VI2.ORSP,418830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_3_VI2.URSP,418832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_3_VI2.RCSP,418834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_3_VI2.INTK_SP,418836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_3_VI2.Total,418838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_3_VI2.INTK_Reset_SP,418994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_3_VI3.VALU,419008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_3_VI3.Old_Val,419010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_3_VI3.VMIN,419012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_3_VI3.VMAX,419014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_3_VI3.RawMin,419016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI3.RawMax,419018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI3.HH_SP,419020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_3_VI3.H_SP,419022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_3_VI3.L_SP,419024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_3_VI3.LL_SP,419026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_3_VI3.BLSP,419028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_3_VI3.ORSP,419030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_3_VI3.URSP,419032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_3_VI3.RCSP,419034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_3_VI3.INTK_SP,419036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_3_VI3.Total,419038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_3_VI3.INTK_Reset_SP,419194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_3_VI4.VALU,419208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_3_VI4.Old_Val,419210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_3_VI4.VMIN,419212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_3_VI4.VMAX,419214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_3_VI4.RawMin,419216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI4.RawMax,419218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI4.HH_SP,419220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_3_VI4.H_SP,419222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_3_VI4.L_SP,419224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_3_VI4.LL_SP,419226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_3_VI4.BLSP,419228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_3_VI4.ORSP,419230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_3_VI4.URSP,419232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_3_VI4.RCSP,419234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_3_VI4.INTK_SP,419236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_3_VI4.Total,419238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_3_VI4.INTK_Reset_SP,419394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_3_VI5.VALU,419408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_3_VI5.Old_Val,419410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_3_VI5.VMIN,419412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_3_VI5.VMAX,419414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_3_VI5.RawMin,419416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI5.RawMax,419418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_3_VI5.HH_SP,419420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_3_VI5.H_SP,419422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_3_VI5.L_SP,419424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_3_VI5.LL_SP,419426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_3_VI5.BLSP,419428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_3_VI5.ORSP,419430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_3_VI5.URSP,419432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_3_VI5.RCSP,419434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_3_VI5.INTK_SP,419436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_3_VI5.Total,419438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_3_VI5.INTK_Reset_SP,419594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_4_VI1.VALU,419608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_4_VI1.Old_Val,419610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_4_VI1.VMIN,419612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_4_VI1.VMAX,419614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_4_VI1.RawMin,419616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI1.RawMax,419618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI1.HH_SP,419620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_4_VI1.H_SP,419622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_4_VI1.L_SP,419624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_4_VI1.LL_SP,419626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_4_VI1.BLSP,419628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_4_VI1.ORSP,419630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_4_VI1.URSP,419632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_4_VI1.RCSP,419634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_4_VI1.INTK_SP,419636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_4_VI1.Total,419638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_4_VI1.INTK_Reset_SP,419794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_4_VI2.VALU,419808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_4_VI2.Old_Val,419810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_4_VI2.VMIN,419812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_4_VI2.VMAX,419814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_4_VI2.RawMin,419816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI2.RawMax,419818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI2.HH_SP,419820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_4_VI2.H_SP,419822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_4_VI2.L_SP,419824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_4_VI2.LL_SP,419826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_4_VI2.BLSP,419828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_4_VI2.ORSP,419830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_4_VI2.URSP,419832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_4_VI2.RCSP,419834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_4_VI2.INTK_SP,419836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_4_VI2.Total,419838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_4_VI2.INTK_Reset_SP,419994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_4_VI3.VALU,420008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_4_VI3.Old_Val,420010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_4_VI3.VMIN,420012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_4_VI3.VMAX,420014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_4_VI3.RawMin,420016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI3.RawMax,420018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI3.HH_SP,420020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_4_VI3.H_SP,420022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_4_VI3.L_SP,420024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_4_VI3.LL_SP,420026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_4_VI3.BLSP,420028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_4_VI3.ORSP,420030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_4_VI3.URSP,420032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_4_VI3.RCSP,420034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_4_VI3.INTK_SP,420036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_4_VI3.Total,420038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_4_VI3.INTK_Reset_SP,420194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_4_VI4.VALU,420208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_4_VI4.Old_Val,420210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_4_VI4.VMIN,420212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_4_VI4.VMAX,420214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_4_VI4.RawMin,420216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI4.RawMax,420218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI4.HH_SP,420220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_4_VI4.H_SP,420222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_4_VI4.L_SP,420224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_4_VI4.LL_SP,420226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_4_VI4.BLSP,420228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_4_VI4.ORSP,420230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_4_VI4.URSP,420232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_4_VI4.RCSP,420234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_4_VI4.INTK_SP,420236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_4_VI4.Total,420238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_4_VI4.INTK_Reset_SP,420394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_4_VI5.VALU,420408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_4_VI5.Old_Val,420410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_4_VI5.VMIN,420412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_4_VI5.VMAX,420414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_4_VI5.RawMin,420416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI5.RawMax,420418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_4_VI5.HH_SP,420420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_4_VI5.H_SP,420422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_4_VI5.L_SP,420424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_4_VI5.LL_SP,420426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_4_VI5.BLSP,420428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_4_VI5.ORSP,420430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_4_VI5.URSP,420432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_4_VI5.RCSP,420434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_4_VI5.INTK_SP,420436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_4_VI5.Total,420438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_4_VI5.INTK_Reset_SP,420594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_5_VI1.VALU,420608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_5_VI1.Old_Val,420610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_5_VI1.VMIN,420612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_5_VI1.VMAX,420614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_5_VI1.RawMin,420616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI1.RawMax,420618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI1.HH_SP,420620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_5_VI1.H_SP,420622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_5_VI1.L_SP,420624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_5_VI1.LL_SP,420626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_5_VI1.BLSP,420628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_5_VI1.ORSP,420630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_5_VI1.URSP,420632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_5_VI1.RCSP,420634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_5_VI1.INTK_SP,420636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_5_VI1.Total,420638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_5_VI1.INTK_Reset_SP,420794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_5_VI2.VALU,420808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_5_VI2.Old_Val,420810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_5_VI2.VMIN,420812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_5_VI2.VMAX,420814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_5_VI2.RawMin,420816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI2.RawMax,420818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI2.HH_SP,420820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_5_VI2.H_SP,420822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_5_VI2.L_SP,420824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_5_VI2.LL_SP,420826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_5_VI2.BLSP,420828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_5_VI2.ORSP,420830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_5_VI2.URSP,420832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_5_VI2.RCSP,420834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_5_VI2.INTK_SP,420836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_5_VI2.Total,420838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_5_VI2.INTK_Reset_SP,420994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_5_VI3.VALU,421008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_5_VI3.Old_Val,421010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_5_VI3.VMIN,421012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_5_VI3.VMAX,421014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_5_VI3.RawMin,421016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI3.RawMax,421018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI3.HH_SP,421020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_5_VI3.H_SP,421022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_5_VI3.L_SP,421024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_5_VI3.LL_SP,421026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_5_VI3.BLSP,421028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_5_VI3.ORSP,421030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_5_VI3.URSP,421032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_5_VI3.RCSP,421034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_5_VI3.INTK_SP,421036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_5_VI3.Total,421038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_5_VI3.INTK_Reset_SP,421194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_5_VI4.VALU,421208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_5_VI4.Old_Val,421210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_5_VI4.VMIN,421212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_5_VI4.VMAX,421214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_5_VI4.RawMin,421216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI4.RawMax,421218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI4.HH_SP,421220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_5_VI4.H_SP,421222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_5_VI4.L_SP,421224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_5_VI4.LL_SP,421226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_5_VI4.BLSP,421228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_5_VI4.ORSP,421230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_5_VI4.URSP,421232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_5_VI4.RCSP,421234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_5_VI4.INTK_SP,421236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_5_VI4.Total,421238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_5_VI4.INTK_Reset_SP,421394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_5_VI5.VALU,421408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_5_VI5.Old_Val,421410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_5_VI5.VMIN,421412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_5_VI5.VMAX,421414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_5_VI5.RawMin,421416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI5.RawMax,421418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_5_VI5.HH_SP,421420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_5_VI5.H_SP,421422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_5_VI5.L_SP,421424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_5_VI5.LL_SP,421426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_5_VI5.BLSP,421428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_5_VI5.ORSP,421430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_5_VI5.URSP,421432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_5_VI5.RCSP,421434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_5_VI5.INTK_SP,421436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_5_VI5.Total,421438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_5_VI5.INTK_Reset_SP,421594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_6_VI1.VALU,421608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_6_VI1.Old_Val,421610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_6_VI1.VMIN,421612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_6_VI1.VMAX,421614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_6_VI1.RawMin,421616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI1.RawMax,421618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI1.HH_SP,421620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_6_VI1.H_SP,421622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_6_VI1.L_SP,421624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_6_VI1.LL_SP,421626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_6_VI1.BLSP,421628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_6_VI1.ORSP,421630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_6_VI1.URSP,421632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_6_VI1.RCSP,421634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_6_VI1.INTK_SP,421636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_6_VI1.Total,421638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_6_VI1.INTK_Reset_SP,421794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_6_VI2.VALU,421808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_6_VI2.Old_Val,421810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_6_VI2.VMIN,421812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_6_VI2.VMAX,421814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_6_VI2.RawMin,421816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI2.RawMax,421818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI2.HH_SP,421820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_6_VI2.H_SP,421822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_6_VI2.L_SP,421824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_6_VI2.LL_SP,421826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_6_VI2.BLSP,421828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_6_VI2.ORSP,421830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_6_VI2.URSP,421832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_6_VI2.RCSP,421834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_6_VI2.INTK_SP,421836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_6_VI2.Total,421838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_6_VI2.INTK_Reset_SP,421994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_6_VI3.VALU,422008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_6_VI3.Old_Val,422010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_6_VI3.VMIN,422012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_6_VI3.VMAX,422014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_6_VI3.RawMin,422016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI3.RawMax,422018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI3.HH_SP,422020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_6_VI3.H_SP,422022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_6_VI3.L_SP,422024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_6_VI3.LL_SP,422026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_6_VI3.BLSP,422028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_6_VI3.ORSP,422030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_6_VI3.URSP,422032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_6_VI3.RCSP,422034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_6_VI3.INTK_SP,422036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_6_VI3.Total,422038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_6_VI3.INTK_Reset_SP,422194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_6_VI4.VALU,422208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_6_VI4.Old_Val,422210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_6_VI4.VMIN,422212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_6_VI4.VMAX,422214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_6_VI4.RawMin,422216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI4.RawMax,422218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI4.HH_SP,422220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_6_VI4.H_SP,422222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_6_VI4.L_SP,422224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_6_VI4.LL_SP,422226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_6_VI4.BLSP,422228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_6_VI4.ORSP,422230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_6_VI4.URSP,422232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_6_VI4.RCSP,422234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_6_VI4.INTK_SP,422236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_6_VI4.Total,422238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_6_VI4.INTK_Reset_SP,422394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_6_VI5.VALU,422408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_6_VI5.Old_Val,422410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_6_VI5.VMIN,422412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_6_VI5.VMAX,422414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_6_VI5.RawMin,422416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI5.RawMax,422418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_6_VI5.HH_SP,422420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_6_VI5.H_SP,422422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_6_VI5.L_SP,422424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_6_VI5.LL_SP,422426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_6_VI5.BLSP,422428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_6_VI5.ORSP,422430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_6_VI5.URSP,422432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_6_VI5.RCSP,422434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_6_VI5.INTK_SP,422436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_6_VI5.Total,422438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_6_VI5.INTK_Reset_SP,422594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_7_VI1.VALU,422608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_7_VI1.Old_Val,422610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_7_VI1.VMIN,422612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_7_VI1.VMAX,422614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_7_VI1.RawMin,422616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI1.RawMax,422618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI1.HH_SP,422620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_7_VI1.H_SP,422622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_7_VI1.L_SP,422624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_7_VI1.LL_SP,422626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_7_VI1.BLSP,422628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_7_VI1.ORSP,422630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_7_VI1.URSP,422632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_7_VI1.RCSP,422634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_7_VI1.INTK_SP,422636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_7_VI1.Total,422638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_7_VI1.INTK_Reset_SP,422794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_7_VI2.VALU,422808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_7_VI2.Old_Val,422810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_7_VI2.VMIN,422812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_7_VI2.VMAX,422814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_7_VI2.RawMin,422816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI2.RawMax,422818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI2.HH_SP,422820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_7_VI2.H_SP,422822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_7_VI2.L_SP,422824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_7_VI2.LL_SP,422826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_7_VI2.BLSP,422828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_7_VI2.ORSP,422830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_7_VI2.URSP,422832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_7_VI2.RCSP,422834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_7_VI2.INTK_SP,422836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_7_VI2.Total,422838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_7_VI2.INTK_Reset_SP,422994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_7_VI3.VALU,423008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_7_VI3.Old_Val,423010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_7_VI3.VMIN,423012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_7_VI3.VMAX,423014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_7_VI3.RawMin,423016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI3.RawMax,423018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI3.HH_SP,423020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_7_VI3.H_SP,423022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_7_VI3.L_SP,423024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_7_VI3.LL_SP,423026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_7_VI3.BLSP,423028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_7_VI3.ORSP,423030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_7_VI3.URSP,423032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_7_VI3.RCSP,423034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_7_VI3.INTK_SP,423036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_7_VI3.Total,423038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_7_VI3.INTK_Reset_SP,423194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_7_VI4.VALU,423208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_7_VI4.Old_Val,423210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_7_VI4.VMIN,423212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_7_VI4.VMAX,423214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_7_VI4.RawMin,423216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI4.RawMax,423218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI4.HH_SP,423220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_7_VI4.H_SP,423222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_7_VI4.L_SP,423224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_7_VI4.LL_SP,423226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_7_VI4.BLSP,423228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_7_VI4.ORSP,423230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_7_VI4.URSP,423232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_7_VI4.RCSP,423234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_7_VI4.INTK_SP,423236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_7_VI4.Total,423238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_7_VI4.INTK_Reset_SP,423394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_7_VI5.VALU,423408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_7_VI5.Old_Val,423410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_7_VI5.VMIN,423412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_7_VI5.VMAX,423414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_7_VI5.RawMin,423416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI5.RawMax,423418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_7_VI5.HH_SP,423420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_7_VI5.H_SP,423422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_7_VI5.L_SP,423424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_7_VI5.LL_SP,423426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_7_VI5.BLSP,423428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_7_VI5.ORSP,423430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_7_VI5.URSP,423432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_7_VI5.RCSP,423434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_7_VI5.INTK_SP,423436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_7_VI5.Total,423438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_7_VI5.INTK_Reset_SP,423594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_8_VI1.VALU,423608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_8_VI1.Old_Val,423610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_8_VI1.VMIN,423612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_8_VI1.VMAX,423614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_8_VI1.RawMin,423616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI1.RawMax,423618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI1.HH_SP,423620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_8_VI1.H_SP,423622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_8_VI1.L_SP,423624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_8_VI1.LL_SP,423626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_8_VI1.BLSP,423628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_8_VI1.ORSP,423630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_8_VI1.URSP,423632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_8_VI1.RCSP,423634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_8_VI1.INTK_SP,423636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_8_VI1.Total,423638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_8_VI1.INTK_Reset_SP,423794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_8_VI2.VALU,423808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_8_VI2.Old_Val,423810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_8_VI2.VMIN,423812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_8_VI2.VMAX,423814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_8_VI2.RawMin,423816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI2.RawMax,423818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI2.HH_SP,423820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_8_VI2.H_SP,423822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_8_VI2.L_SP,423824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_8_VI2.LL_SP,423826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_8_VI2.BLSP,423828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_8_VI2.ORSP,423830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_8_VI2.URSP,423832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_8_VI2.RCSP,423834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_8_VI2.INTK_SP,423836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_8_VI2.Total,423838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_8_VI2.INTK_Reset_SP,423994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_8_VI3.VALU,424008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_8_VI3.Old_Val,424010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_8_VI3.VMIN,424012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_8_VI3.VMAX,424014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_8_VI3.RawMin,424016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI3.RawMax,424018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI3.HH_SP,424020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_8_VI3.H_SP,424022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_8_VI3.L_SP,424024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_8_VI3.LL_SP,424026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_8_VI3.BLSP,424028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_8_VI3.ORSP,424030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_8_VI3.URSP,424032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_8_VI3.RCSP,424034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_8_VI3.INTK_SP,424036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_8_VI3.Total,424038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_8_VI3.INTK_Reset_SP,424194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_8_VI4.VALU,424208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_8_VI4.Old_Val,424210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_8_VI4.VMIN,424212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_8_VI4.VMAX,424214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_8_VI4.RawMin,424216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI4.RawMax,424218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI4.HH_SP,424220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_8_VI4.H_SP,424222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_8_VI4.L_SP,424224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_8_VI4.LL_SP,424226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_8_VI4.BLSP,424228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_8_VI4.ORSP,424230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_8_VI4.URSP,424232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_8_VI4.RCSP,424234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_8_VI4.INTK_SP,424236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_8_VI4.Total,424238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_8_VI4.INTK_Reset_SP,424394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_8_VI5.VALU,424408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_8_VI5.Old_Val,424410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_8_VI5.VMIN,424412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_8_VI5.VMAX,424414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_8_VI5.RawMin,424416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI5.RawMax,424418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_8_VI5.HH_SP,424420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_8_VI5.H_SP,424422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_8_VI5.L_SP,424424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_8_VI5.LL_SP,424426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_8_VI5.BLSP,424428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_8_VI5.ORSP,424430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_8_VI5.URSP,424432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_8_VI5.RCSP,424434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_8_VI5.INTK_SP,424436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_8_VI5.Total,424438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_8_VI5.INTK_Reset_SP,424594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_9_VI1.VALU,424608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_9_VI1.Old_Val,424610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_9_VI1.VMIN,424612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_9_VI1.VMAX,424614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_9_VI1.RawMin,424616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI1.RawMax,424618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI1.HH_SP,424620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_9_VI1.H_SP,424622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_9_VI1.L_SP,424624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_9_VI1.LL_SP,424626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_9_VI1.BLSP,424628,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_9_VI1.ORSP,424630,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_9_VI1.URSP,424632,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_9_VI1.RCSP,424634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_9_VI1.INTK_SP,424636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_9_VI1.Total,424638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_9_VI1.INTK_Reset_SP,424794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_9_VI2.VALU,424808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_9_VI2.Old_Val,424810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_9_VI2.VMIN,424812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_9_VI2.VMAX,424814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_9_VI2.RawMin,424816,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI2.RawMax,424818,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI2.HH_SP,424820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_9_VI2.H_SP,424822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_9_VI2.L_SP,424824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_9_VI2.LL_SP,424826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_9_VI2.BLSP,424828,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_9_VI2.ORSP,424830,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_9_VI2.URSP,424832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_9_VI2.RCSP,424834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_9_VI2.INTK_SP,424836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_9_VI2.Total,424838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_9_VI2.INTK_Reset_SP,424994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_9_VI3.VALU,425008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_9_VI3.Old_Val,425010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_9_VI3.VMIN,425012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_9_VI3.VMAX,425014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_9_VI3.RawMin,425016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI3.RawMax,425018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI3.HH_SP,425020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_9_VI3.H_SP,425022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_9_VI3.L_SP,425024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_9_VI3.LL_SP,425026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_9_VI3.BLSP,425028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_9_VI3.ORSP,425030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_9_VI3.URSP,425032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_9_VI3.RCSP,425034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_9_VI3.INTK_SP,425036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_9_VI3.Total,425038,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_9_VI3.INTK_Reset_SP,425194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_9_VI4.VALU,425208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_9_VI4.Old_Val,425210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_9_VI4.VMIN,425212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_9_VI4.VMAX,425214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_9_VI4.RawMin,425216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI4.RawMax,425218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI4.HH_SP,425220,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_9_VI4.H_SP,425222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_9_VI4.L_SP,425224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_9_VI4.LL_SP,425226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_9_VI4.BLSP,425228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_9_VI4.ORSP,425230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_9_VI4.URSP,425232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_9_VI4.RCSP,425234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_9_VI4.INTK_SP,425236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_9_VI4.Total,425238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_9_VI4.INTK_Reset_SP,425394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_PMP_0103_9_VI5.VALU,425408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_PMP_0103_9_VI5.Old_Val,425410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_PMP_0103_9_VI5.VMIN,425412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_PMP_0103_9_VI5.VMAX,425414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_PMP_0103_9_VI5.RawMin,425416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI5.RawMax,425418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_PMP_0103_9_VI5.HH_SP,425420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_PMP_0103_9_VI5.H_SP,425422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_PMP_0103_9_VI5.L_SP,425424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_PMP_0103_9_VI5.LL_SP,425426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_PMP_0103_9_VI5.BLSP,425428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_PMP_0103_9_VI5.ORSP,425430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_PMP_0103_9_VI5.URSP,425432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_PMP_0103_9_VI5.RCSP,425434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_PMP_0103_9_VI5.INTK_SP,425436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_PMP_0103_9_VI5.Total,425438,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_PMP_0103_9_VI5.INTK_Reset_SP,425594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_TT_0111_1_TI.VALU,425608,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_TT_0111_1_TI.Old_Val,425610,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_TT_0111_1_TI.VMIN,425612,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_TT_0111_1_TI.VMAX,425614,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_TT_0111_1_TI.RawMin,425616,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_TT_0111_1_TI.RawMax,425618,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_TT_0111_1_TI.HH_SP,425620,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_TT_0111_1_TI.H_SP,425622,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_TT_0111_1_TI.L_SP,425624,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_TT_0111_1_TI.LL_SP,425626,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_TT_0111_1_TI.BLSP,425628,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_TT_0111_1_TI.ORSP,425630,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_TT_0111_1_TI.URSP,425632,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_TT_0111_1_TI.RCSP,425634,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_TT_0111_1_TI.INTK_SP,425636,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_TT_0111_1_TI.Total,425638,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_TT_0111_1_TI.INTK_Reset_SP,425794,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_TT_0112_1_TI.VALU,425808,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value in Engineering Units" WA3252_TT_0112_1_TI.Old_Val,425810,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Prevoius Value for Rate of Change Checking" WA3252_TT_0112_1_TI.VMIN,425812,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMin" WA3252_TT_0112_1_TI.VMAX,425814,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Scaled Value with Raw at RawMax" WA3252_TT_0112_1_TI.RawMin,425816,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_TT_0112_1_TI.RawMax,425818,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Used for Scaling to EU" WA3252_TT_0112_1_TI.HH_SP,425820,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm Limit" WA3252_TT_0112_1_TI.H_SP,425822,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm Limit" WA3252_TT_0112_1_TI.L_SP,425824,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm Limit" WA3252_TT_0112_1_TI.LL_SP,425826,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm Limit" WA3252_TT_0112_1_TI.BLSP,425828,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Raw Low Limit for Broken Loop" WA3252_TT_0112_1_TI.ORSP,425830,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Raw Alarm Limit" WA3252_TT_0112_1_TI.URSP,425832,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Raw Alarm Limit" WA3252_TT_0112_1_TI.RCSP,425834,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Max Absolute Change In EU per Second to trip the Rate Of Change Fault" WA3252_TT_0112_1_TI.INTK_SP,425836,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Alarm Limit" WA3252_TT_0112_1_TI.Total,425838,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: totalized value since totalizer was last reset." WA3252_TT_0112_1_TI.INTK_Reset_SP,425994,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Interlock Reset Setpoint" WA3252_AFD_0103_1_FA.ATRM,426030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_MF.ATRM,426066,Float,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_MY.ATRM,426100,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_UA.ATRM,426136,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_UH.ATRM,426170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_UY.ATRM,426206,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_XF.ATRM,426240,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1_YA.ATRM,426276,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_FA.ATRM,426310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_MF.ATRM,426346,Float,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_MY.ATRM,426380,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_UA.ATRM,426416,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_UH.ATRM,426450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_UY.ATRM,426486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_XF.ATRM,426520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_2_YA.ATRM,426556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_FA.ATRM,426590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_MF.ATRM,426626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_MY.ATRM,426660,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_UA.ATRM,426696,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_UH.ATRM,426730,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_UY.ATRM,426766,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_XF.ATRM,426800,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_3_YA.ATRM,426836,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_FA.ATRM,426870,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_MF.ATRM,426906,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_MY.ATRM,426940,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_UA.ATRM,426976,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_UH.ATRM,427010,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_UY.ATRM,427046,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_XF.ATRM,427080,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_4_YA.ATRM,427116,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_FA.ATRM,427150,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_MF.ATRM,427186,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_MY.ATRM,427220,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_UA.ATRM,427256,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_UH.ATRM,427290,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_UY.ATRM,427326,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_XF.ATRM,427360,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_5_YA.ATRM,427396,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_FA.ATRM,427430,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_MF.ATRM,427466,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_MY.ATRM,427500,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_UA.ATRM,427536,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_UH.ATRM,427570,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_UY.ATRM,427606,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_XF.ATRM,427640,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_6_YA.ATRM,427676,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_FA.ATRM,427710,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_MF.ATRM,427746,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_MY.ATRM,427780,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_UA.ATRM,427816,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_UH.ATRM,427850,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_UY.ATRM,427886,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_XF.ATRM,427920,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_7_YA.ATRM,427956,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_FA.ATRM,427990,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_MF.ATRM,428026,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_MY.ATRM,428060,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_UA.ATRM,428096,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_UH.ATRM,428130,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_UY.ATRM,428166,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_XF.ATRM,428200,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_8_YA.ATRM,428236,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_FA.ATRM,428270,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_MF.ATRM,428306,Float,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_MY.ATRM,428340,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_UA.ATRM,428376,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_UH.ATRM,428410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_UY.ATRM,428446,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_XF.ATRM,428480,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_9_YA.ATRM,428516,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0112_1_JA.ATRM,428550,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0112_1_JN1.ATRM,428586,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0112_2_JA.ATRM,428620,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0112_2_JN1.ATRM,428656,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0140_1_JA.ATRM,428690,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_ATO_0140_1_XA.ATRM,428726,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0114_1_XA.ATRM,428760,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0114_2_XA.ATRM,428796,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0114_3_LH.ATRM,428830,Float,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1A_MF.ATRM,428866,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1A_XA.ATRM,428900,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1B_MF.ATRM,428936,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1B_XA.ATRM,428970,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1C_MF.ATRM,429006,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1C_XA.ATRM,429040,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1DE_MF.ATRM,429076,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1DE_XA.ATRM,429110,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1FG_MF.ATRM,429146,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1FG_XA.ATRM,429180,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1H_MF.ATRM,429216,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1H_XA.ATRM,429250,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1I_MF.ATRM,429286,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1I_XA.ATRM,429320,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1J_MF.ATRM,429356,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1J_XA.ATRM,429390,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1K_MF.ATRM,429426,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_1K_XA.ATRM,429460,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_LH.ATRM,429496,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_MF1.ATRM,429530,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_MF2.ATRM,429566,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_MF3.ATRM,429600,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_MF4.ATRM,429636,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2A_XA.ATRM,429670,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_LH.ATRM,429706,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_MF1.ATRM,429740,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_MF2.ATRM,429776,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_MF3.ATRM,429810,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_MF4.ATRM,429846,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_2B_XA.ATRM,429880,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_3A_MF.ATRM,429916,Float,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0117_3B_XF.ATRM,429950,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_1_LH1.ATRM,429986,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_1_LH2.ATRM,430020,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_1_XA.ATRM,430056,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_1A_MF.ATRM,430090,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_1B_MF.ATRM,430126,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_2_LH1.ATRM,430160,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_2_LH2.ATRM,430196,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_2_XA.ATRM,430230,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_2A_MF.ATRM,430266,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_CP_0118_2B_MF.ATRM,430300,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FCV_0113_2A_WH.ATRM,430336,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FCV_0113_2B_WH.ATRM,430370,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FLT_0112_1_XA.ATRM,430406,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FLT_0112_2_XA.ATRM,430440,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0102_1A_WH.ATRM,430476,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0102_1B_WH.ATRM,430510,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0102_2A_WH.ATRM,430546,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0102_2B_WH.ATRM,430580,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_1A_WH.ATRM,430616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_1B_ZF.ATRM,430650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_1B_ZF2.ATRM,430686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_1C_WH.ATRM,430720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_2A_WH.ATRM,430756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_2B_ZF.ATRM,430790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_2B_ZF2.ATRM,430826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_2C_WH.ATRM,430860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3A_WH.ATRM,430896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3B_ZF.ATRM,430930,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3B_ZF3.ATRM,430966,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3B_ZF4.ATRM,431000,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3C_WH.ATRM,431036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_3D_WH.ATRM,431070,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4A_WH.ATRM,431106,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4B_ZF.ATRM,431140,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4B_ZF3.ATRM,431176,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4B_ZF4.ATRM,431210,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4C_WH.ATRM,431246,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_4D_WH.ATRM,431280,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5A_WH.ATRM,431316,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5B_ZF.ATRM,431350,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5B_ZF3.ATRM,431386,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5B_ZF4.ATRM,431420,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5C_WH.ATRM,431456,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_5D_WH.ATRM,431490,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6A_WH.ATRM,431526,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6B_ZF.ATRM,431560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6B_ZF3.ATRM,431596,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6B_ZF4.ATRM,431630,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6C_WH.ATRM,431666,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_6D_WH.ATRM,431700,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7A_WH.ATRM,431736,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7B_ZF.ATRM,431770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7B_ZF3.ATRM,431806,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7B_ZF4.ATRM,431840,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7C_WH.ATRM,431876,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_7D_WH.ATRM,431910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8A_WH.ATRM,431946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8B_ZF.ATRM,431980,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8B_ZF3.ATRM,432016,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8B_ZF4.ATRM,432050,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8C_WH.ATRM,432086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_8D_WH.ATRM,432120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_9A_WH.ATRM,432156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_9B_ZF.ATRM,432190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_9B_ZF2.ATRM,432226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0103_9C_WH.ATRM,432260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0113_2A_WH.ATRM,432296,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0113_2B_WH.ATRM,432330,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0113_2C_WH.ATRM,432366,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_FV_0113_2D_WH.ATRM,432400,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_LL.ATRM,432436,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_PL.ATRM,432470,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_SH.ATRM,432506,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_TH.ATRM,432540,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_XA1.ATRM,432576,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_GEN_0131_1_XA2.ATRM,432610,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_FA.ATRM,432646,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_FH.ATRM,432680,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_PH.ATRM,432716,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_TH1.ATRM,432750,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_TH2.ATRM,432786,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_TH3.ATRM,432820,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_TL1.ATRM,432856,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_TL2.ATRM,432890,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA1.ATRM,432926,Float,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA2.ATRM,432960,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA3.ATRM,432996,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA4.ATRM,433030,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA5.ATRM,433066,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA6.ATRM,433100,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA7.ATRM,433136,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA8.ATRM,433170,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA9.ATRM,433206,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA10.ATRM,433240,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA11.ATRM,433276,Float,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_HCP_001_1_XA12.ATRM,433310,Float,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_LSH_0113_1_LH.ATRM,433346,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_LSH_0113_2_LH.ATRM,433380,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_NET_001_1_JA.ATRM,433416,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_NET_001_1_ZS.ATRM,433450,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PFC_0112_INHIBIT.ATRM,433486,Float,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PIT_0102_1_PL.ATRM,433520,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PIT_0102_2_PL.ATRM,433556,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PLC_001_1_JA.ATRM,433590,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PLC_001_1_ZS.ATRM,433626,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_1_PL.ATRM,433660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_2_PL.ATRM,433696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_3_PL.ATRM,433730,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_4_PL.ATRM,433766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_5_PL.ATRM,433800,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_6_PL.ATRM,433836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_7_PL.ATRM,433870,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_8_PL.ATRM,433906,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_PS_0103_9_PL.ATRM,433940,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_REC_0131_1_XA.ATRM,433976,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_REC_0131_2_XA.ATRM,434010,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_REC_0131_3_XA.ATRM,434046,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_REC_0131_4_XA.ATRM,434080,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SD_0112_1_XA.ATRM,434116,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SD_0113_1_XA.ATRM,434150,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SD_0113_2_XA.ATRM,434186,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SD_0114_1_XA.ATRM,434220,Float,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SD_0114_2_XA.ATRM,434256,Float,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_1_XA.ATRM,434290,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_2_XA.ATRM,434326,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_3_XA1.ATRM,434360,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_3A_XA.ATRM,434396,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_3B_XA.ATRM,434430,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_4_XA.ATRM,434466,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_4_XA1.ATRM,434500,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_5_XA.ATRM,434536,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0112_6_XA.ATRM,434570,Float,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0113_1_XA.ATRM,434606,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_SPD_0113_2_XA.ATRM,434640,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0111_1_TH.ATRM,434676,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0112_1_TH.ATRM,434710,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0113_1_TH.ATRM,434746,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0113_2_TH.ATRM,434780,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0114_1_TH.ATRM,434816,Float,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TE_0114_2_TH.ATRM,434850,Float,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_1_LL.ATRM,434886,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_1_TH1.ATRM,434920,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_1_TH2.ATRM,434956,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_1_XA.ATRM,434990,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_2_LL.ATRM,435026,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_2_TH1.ATRM,435060,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_2_TH2.ATRM,435096,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_TFR_0131_2_XA.ATRM,435130,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_UPS_001_1_JA.ATRM,435166,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_UPS_001_1_ZS.ATRM,435200,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_UPS_001_2_JA.ATRM,435236,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_UPS_001_2_ZS.ATRM,435270,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XE_0112_1A_ZA.ATRM,435306,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XE_0113_1A_ZA.ATRM,435340,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XE_0113_1B_ZA.ATRM,435376,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XE_0113_2A_ZA.ATRM,435410,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XE_0113_2B_ZA.ATRM,435446,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_3_LL.ATRM,435480,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_3_TH1.ATRM,435516,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_3_TH2.ATRM,435550,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_3_XA.ATRM,435586,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_4_LL.ATRM,435620,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_4_TH1.ATRM,435656,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_4_TH2.ATRM,435690,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_4_XA.ATRM,435726,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_5_LL.ATRM,435760,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_5_TH1.ATRM,435796,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_5_TH2.ATRM,435830,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_5_XA.ATRM,435866,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_6_LL.ATRM,435900,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_6_TH1.ATRM,435936,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_6_TH2.ATRM,435970,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_XFR_0131_6_XA.ATRM,436006,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_EASTMICRO_FAIL.ATRM,436040,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_EATON_PUMP1_FAIL.ATRM,436076,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_EATON_PUMP2_FAIL.ATRM,436110,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_EATON_PUMP9_FAIL.ATRM,436146,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_METER_VAULT_FAIL.ATRM,436180,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_SEL710_PUMP1_FAIL.ATRM,436216,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_SEL710_PUMP2_FAIL.ATRM,436250,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_SEL710_PUMP9_FAIL.ATRM,436286,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_TSR_PLC_FAIL.ATRM,436320,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3260_COMM_WESTMICRO_FAIL.ATRM,436356,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: Alarm Time Remaining" WA3252_AFD_0103_1.RSTD,436402,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_1.RSRM,436404,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_1.ATRM,436406,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_1.VFDOut,436408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_1.Deviation_OVR,436472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_1.Deviation_UNDR,436474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_1.VFDDevTD,436476,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_1.VFDScale,436478,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_1.VFDFB,436480,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_1.VFDMaxSP,436482,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_1.VFDMinSP,436484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_1.VFDSP,436486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_1.DBND,436488,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_1.VFDSPReqPLC,436490,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_2.RSTD,436538,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_2.RSRM,436540,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_2.ATRM,436542,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_2.VFDOut,436544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_2.Deviation_OVR,436608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_2.Deviation_UNDR,436610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_2.VFDDevTD,436612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_2.VFDScale,436614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_2.VFDFB,436616,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_2.VFDMaxSP,436618,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_2.VFDMinSP,436620,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_2.VFDSP,436622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_2.DBND,436624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_2.VFDSPReqPLC,436626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_3.RSTD,436672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_3.RSRM,436674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_3.ATRM,436676,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_3.VFDOut,436678,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_3.Deviation_OVR,436742,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_3.Deviation_UNDR,436744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_3.VFDDevTD,436746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_3.VFDScale,436748,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_3.VFDFB,436750,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_3.VFDMaxSP,436752,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_3.VFDMinSP,436754,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_3.VFDSP,436756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_3.DBND,436758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_3.VFDSPReqPLC,436760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_4.RSTD,436808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_4.RSRM,436810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_4.ATRM,436812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_4.VFDOut,436814,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_4.Deviation_OVR,436878,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_4.Deviation_UNDR,436880,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_4.VFDDevTD,436882,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_4.VFDScale,436884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_4.VFDFB,436886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_4.VFDMaxSP,436888,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_4.VFDMinSP,436890,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_4.VFDSP,436892,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_4.DBND,436894,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_4.VFDSPReqPLC,436896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_5.RSTD,436942,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_5.RSRM,436944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_5.ATRM,436946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_5.VFDOut,436948,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_5.Deviation_OVR,437012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_5.Deviation_UNDR,437014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_5.VFDDevTD,437016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_5.VFDScale,437018,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_5.VFDFB,437020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_5.VFDMaxSP,437022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_5.VFDMinSP,437024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_5.VFDSP,437026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_5.DBND,437028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_5.VFDSPReqPLC,437030,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_6.RSTD,437078,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_6.RSRM,437080,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_6.ATRM,437082,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_6.VFDOut,437084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_6.Deviation_OVR,437148,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_6.Deviation_UNDR,437150,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_6.VFDDevTD,437152,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_6.VFDScale,437154,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_6.VFDFB,437156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_6.VFDMaxSP,437158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_6.VFDMinSP,437160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_6.VFDSP,437162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_6.DBND,437164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_6.VFDSPReqPLC,437166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_7.RSTD,437212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_7.RSRM,437214,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_7.ATRM,437216,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_7.VFDOut,437218,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_7.Deviation_OVR,437282,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_7.Deviation_UNDR,437284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_7.VFDDevTD,437286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_7.VFDScale,437288,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_7.VFDFB,437290,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_7.VFDMaxSP,437292,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_7.VFDMinSP,437294,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_7.VFDSP,437296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_7.DBND,437298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_7.VFDSPReqPLC,437300,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_8.RSTD,437348,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_8.RSRM,437350,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_8.ATRM,437352,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_8.VFDOut,437354,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_8.Deviation_OVR,437418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_8.Deviation_UNDR,437420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_8.VFDDevTD,437422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_8.VFDScale,437424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_8.VFDFB,437426,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_8.VFDMaxSP,437428,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_8.VFDMinSP,437430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_8.VFDSP,437432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_8.DBND,437434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_8.VFDSPReqPLC,437436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_AFD_0103_9.RSTD,437482,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay: Seconds to inhibit motor start after motor stops" WA3252_AFD_0103_9.RSRM,437484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Restart Delay Remaining: in seconds" WA3252_AFD_0103_9.ATRM,437486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_AFD_0103_9.VFDOut,437488,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Output to Physical Device" WA3252_AFD_0103_9.Deviation_OVR,437552,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Maximum Value of Deviation before Timer begins" WA3252_AFD_0103_9.Deviation_UNDR,437554,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Minimum Value of Deviation before Timer begins" WA3252_AFD_0103_9.VFDDevTD,437556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deviation Timer Remain in Seconds" WA3252_AFD_0103_9.VFDScale,437558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Output in EU to be Scaled" WA3252_AFD_0103_9.VFDFB,437560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Indication Feedback from Device" WA3252_AFD_0103_9.VFDMaxSP,437562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MAX SPEED SETPOINT" WA3252_AFD_0103_9.VFDMinSP,437564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD MIN SPEED SETPOINT" WA3252_AFD_0103_9.VFDSP,437566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Setpoint" WA3252_AFD_0103_9.DBND,437568,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Deadband for Deviation Timer" WA3252_AFD_0103_9.VFDSPReqPLC,437570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: VFD Speed Request from PLC" WA3252_FV_0102_1A.ATRM,437584,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0102_1B.ATRM,437664,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0102_2A.ATRM,437744,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0102_2B.ATRM,437824,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_1A.ATRM,437904,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_1C.ATRM,437984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_2A.ATRM,438064,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_2C.ATRM,438144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_3A.ATRM,438224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_3C.ATRM,438304,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_3D.ATRM,438384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_4A.ATRM,438464,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_4C.ATRM,438544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_4D.ATRM,438624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_5A.ATRM,438704,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_5C.ATRM,438784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_5D.ATRM,438864,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_6A.ATRM,438944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_6C.ATRM,439024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_6D.ATRM,439104,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_7A.ATRM,439184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_7C.ATRM,439264,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_7D.ATRM,439344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_8A.ATRM,439424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_8C.ATRM,439504,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_8D.ATRM,439584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_9A.ATRM,439664,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0103_9C.ATRM,439744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0113_2A.ATRM,439824,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0113_2B.ATRM,439904,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0113_2C.ATRM,439984,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FV_0113_2D.ATRM,440064,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FCV_0113_2A.BL_SP,440144,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Raw Low Limit for Broken Loop" WA3252_FCV_0113_2A.OR_SP,440146,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Raw Alarm Limit" WA3252_FCV_0113_2A.PO_DB,440148,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Deadband in % open. Used to trip alarm for feedback vs. command position." WA3252_FCV_0113_2A.UR_SP,440150,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Raw Alarm Limit" WA3252_FCV_0113_2A.AutoPO_SP,440152,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Auto Position Setpoint in % Open" WA3252_FCV_0113_2A.ManPO_SP,440154,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Manual Position Setpoint in % Open" WA3252_FCV_0113_2A.PO_SP,440156,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Setpoint in % open." WA3252_FCV_0113_2A.ATRM,440232,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FCV_0113_2A.PO_FB,440234,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Feedback in % open" WA3252_FCV_0113_2A.PositionError,440236,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: In % Open + is Open Past Setpoint" WA3252_FCV_0113_2B.BL_SP,440254,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Raw Low Limit for Broken Loop" WA3252_FCV_0113_2B.OR_SP,440256,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Raw Alarm Limit" WA3252_FCV_0113_2B.PO_DB,440258,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Deadband in % open. Used to trip alarm for feedback vs. command position." WA3252_FCV_0113_2B.UR_SP,440260,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Raw Alarm Limit" WA3252_FCV_0113_2B.AutoPO_SP,440262,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Auto Position Setpoint in % Open" WA3252_FCV_0113_2B.ManPO_SP,440264,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Manual Position Setpoint in % Open" WA3252_FCV_0113_2B.PO_SP,440266,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Setpoint in % open." WA3252_FCV_0113_2B.ATRM,440342,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Alarm Time Remaining: Seconds Until Alarm Trips If Fault is not Cleared" WA3252_FCV_0113_2B.PO_FB,440344,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Position Feedback in % open" WA3252_FCV_0113_2B.PositionError,440346,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: In % Open + is Open Past Setpoint" WA3252_FCV_0113_2_PID.ti,440384,DWord,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Integral time WA3252_FIT_0105_1A_PID.ti,440364,DWord,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Integral time BMENOC0311_4.CONF_SIG,,DWord,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Signature of all files on local module FDR Server BMEP58_ECPU_EXT.CONF_SIG,,DWord,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Signature of all files on local module FDR Server WA3252_FCV_0113_2_PID.id,440370,Word,1,R/W,1000,,,,,,,,,,RWPS Reservoir Release Flow PID Parameters: Parameters for PI_B function block: Reserved for autotuning WA3252_FIT_0105_1A_PID.id,440350,Word,1,R/W,1000,,,,,,,,,,RWPS TSR Inlet Flow PID Parameters: Parameters for PI_B function block: Reserved for autotuning BMENOC0311_4.IN_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of packets received on interface BMENOC0311_4.IN_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of inbound packets that contain errors BMENOC0311_4.OUT_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of packets sent on interface BMENOC0311_4.OUT_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Number of outbound packets that contain errors BMEP58_ECPU_EXT.IN_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of packets received on interface BMEP58_ECPU_EXT.IN_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of inbound packets that contain errors BMEP58_ECPU_EXT.OUT_PACKETS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of packets sent on interface BMEP58_ECPU_EXT.OUT_ERRORS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Number of outbound packets that contain errors BMENOC0311_4.ETH_STATUS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Ethernet status BMENOC0311_4.SERVICE_STATUS,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: One bit for each user-observable feature BMENOC0311_4.SERVICE_STATUS2,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: One bit for each user-observable feature BMENOC0311_4.FIRMWARE_VERSION,,Word,1,R/W,1000,,,,,,,,,,"Device DDT For BME NOC Factory Cast: MSB=Major Revision, LSB=Minor Revision" BMEP58_ECPU_EXT.ETH_STATUS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Ethernet status BMEP58_ECPU_EXT.SERVICE_STATUS,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): One bit for each user-observable feature BMEP58_ECPU_EXT.SERVICE_STATUS2,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): One bit for each user-observable feature BMEP58_ECPU_EXT.RESERVED2,,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Reserved BMENOC0311_4.DIO_HEALTH.[0],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[17],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[18],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[19],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[20],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[21],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[22],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[23],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[24],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[25],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[26],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[27],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[28],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[29],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[30],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[31],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[32],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[33],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[34],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[35],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[36],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[37],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[38],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[39],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[40],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[41],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[42],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[43],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[44],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[45],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[46],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[47],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[48],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[49],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[50],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[51],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[52],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[53],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[54],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[55],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[56],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[57],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[58],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[59],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[60],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[61],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[62],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[63],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[64],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[65],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[66],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[67],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[68],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[69],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[70],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[71],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[72],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[73],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[74],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[75],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[76],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[77],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[78],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[79],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[80],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[81],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[82],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[83],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[84],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[85],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[86],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[87],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[88],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[89],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[90],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[91],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[92],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[93],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[94],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[95],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[96],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[97],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[98],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[99],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[100],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[101],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[102],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[103],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[104],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[105],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[106],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[107],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[108],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[109],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[110],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[111],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[112],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[113],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[114],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[115],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[116],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[117],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[118],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[119],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[120],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[121],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[122],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[123],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[124],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[125],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[126],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_HEALTH.[127],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO health bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[0],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[17],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[18],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[19],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[20],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[21],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[22],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[23],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[24],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[25],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[26],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[27],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[28],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[29],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[30],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[31],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[32],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[33],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[34],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[35],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[36],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[37],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[38],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[39],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[40],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[41],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[42],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[43],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[44],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[45],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[46],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[47],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[48],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[49],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[50],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[51],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[52],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[53],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[54],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[55],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[56],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[57],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[58],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[59],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[60],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[61],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[62],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[63],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[64],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[65],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[66],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[67],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[68],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[69],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[70],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[71],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[72],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[73],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[74],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[75],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[76],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[77],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[78],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[79],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[80],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[81],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[82],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[83],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[84],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[85],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[86],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[87],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[88],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[89],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[90],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[91],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[92],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[93],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[94],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[95],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[96],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[97],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[98],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[99],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[100],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[101],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[102],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[103],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[104],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[105],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[106],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[107],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[108],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[109],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[110],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[111],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[112],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[113],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[114],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[115],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[116],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[117],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[118],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[119],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[120],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[121],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[122],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[123],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[124],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[125],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[126],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.DIO_CTRL.[127],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO control bits (1 bit per DIO up to 128 DIOs. 112 - 127 are reserved for future extension) BMENOC0311_4.LS_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMENOC0311_4.LS_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Local Slave health bits (Local Slave 1 to 16) BMEP58_ECPU_EXT.DROP_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[4],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[5],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[6],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[7],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[8],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[9],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[10],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[11],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[12],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[13],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[14],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[15],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[16],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[17],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[18],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[19],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[20],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[21],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[22],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[23],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[24],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[25],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[26],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[27],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[28],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[29],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[30],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_HEALTH.[31],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP health bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[4],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[5],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[6],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[7],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[8],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[9],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[10],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[11],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[12],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[13],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[14],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[15],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[16],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[17],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[18],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[19],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[20],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[21],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[22],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[23],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[24],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[25],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[26],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[27],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[28],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[29],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[30],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.DROP_CTRL.[31],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DROP control bits (Drop 1 to 31) BMEP58_ECPU_EXT.LS_HEALTH.[1],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3) BMEP58_ECPU_EXT.LS_HEALTH.[2],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3) BMEP58_ECPU_EXT.LS_HEALTH.[3],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Local Slave health bits (Local Slave 1 to 3) BMEP58_ECPU_EXT.RIO_HEALTH.[257],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[258],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[259],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[260],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[261],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[262],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[263],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[264],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[265],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[266],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[267],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[268],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[269],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[270],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[271],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[272],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[273],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[274],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[275],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[276],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[277],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[278],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[279],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[280],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[281],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[282],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[283],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[284],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[285],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[286],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[287],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[288],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[289],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[290],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[291],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[292],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[293],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[294],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[295],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[296],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[297],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[298],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[299],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[300],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[301],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[302],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[303],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[304],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[305],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[306],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[307],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[308],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[309],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[310],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[311],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[312],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[313],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[314],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[315],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[316],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[317],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[318],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[319],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[320],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[321],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[322],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[323],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[324],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[325],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[326],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[327],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[328],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[329],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[330],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[331],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[332],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[333],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[334],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[335],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[336],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[337],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[338],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[339],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[340],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[341],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[342],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[343],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[344],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[345],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[346],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[347],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[348],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[349],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[350],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[351],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[352],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[353],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[354],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[355],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[356],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[357],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[358],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[359],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[360],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[361],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[362],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[363],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[364],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[365],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[366],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[367],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[368],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[369],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[370],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[371],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[372],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[373],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[374],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[375],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[376],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[377],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[378],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[379],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[380],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[381],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[382],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[383],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_HEALTH.[384],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO health bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[257],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[258],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[259],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[260],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[261],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[262],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[263],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[264],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[265],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[266],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[267],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[268],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[269],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[270],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[271],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[272],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[273],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[274],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[275],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[276],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[277],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[278],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[279],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[280],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[281],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[282],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[283],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[284],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[285],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[286],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[287],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[288],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[289],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[290],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[291],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[292],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[293],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[294],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[295],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[296],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[297],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[298],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[299],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[300],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[301],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[302],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[303],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[304],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[305],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[306],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[307],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[308],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[309],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[310],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[311],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[312],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[313],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[314],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[315],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[316],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[317],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[318],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[319],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[320],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[321],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[322],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[323],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[324],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[325],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[326],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[327],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[328],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[329],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[330],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[331],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[332],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[333],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[334],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[335],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[336],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[337],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[338],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[339],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[340],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[341],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[342],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[343],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[344],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[345],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[346],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[347],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[348],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[349],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[350],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[351],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[352],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[353],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[354],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[355],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[356],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[357],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[358],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[359],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[360],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[361],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[362],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[363],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[364],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[365],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[366],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[367],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[368],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[369],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[370],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[371],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[372],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[373],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[374],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[375],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[376],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[377],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[378],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[379],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[380],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[381],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[382],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[383],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.RIO_CTRL.[384],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): RIO control bits (1 bit per RIO up to 128) BMEP58_ECPU_EXT.DIO_HEALTH.[513],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[514],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[515],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[516],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[517],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[518],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[519],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[520],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[521],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[522],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[523],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[524],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[525],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[526],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[527],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[528],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[529],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[530],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[531],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[532],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[533],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[534],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[535],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[536],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[537],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[538],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[539],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[540],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[541],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[542],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[543],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[544],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[545],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[546],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[547],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[548],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[549],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[550],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[551],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[552],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[553],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[554],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[555],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[556],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[557],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[558],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[559],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[560],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[561],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[562],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[563],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[564],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[565],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[566],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[567],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[568],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[569],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[570],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[571],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[572],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[573],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[574],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[575],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[576],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[577],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[578],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[579],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[580],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[581],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[582],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[583],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[584],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[585],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[586],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[587],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[588],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[589],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[590],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[591],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[592],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[593],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[594],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[595],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[596],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[597],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[598],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[599],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[600],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[601],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[602],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[603],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[604],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[605],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[606],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[607],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[608],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[609],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[610],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[611],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[612],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[613],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[614],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[615],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[616],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[617],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[618],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[619],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[620],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[621],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[622],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[623],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[624],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[625],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[626],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[627],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[628],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[629],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[630],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[631],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[632],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[633],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[634],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[635],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[636],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[637],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[638],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[639],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_HEALTH.[640],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO health bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[513],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[514],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[515],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[516],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[517],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[518],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[519],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[520],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[521],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[522],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[523],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[524],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[525],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[526],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[527],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[528],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[529],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[530],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[531],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[532],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[533],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[534],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[535],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[536],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[537],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[538],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[539],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[540],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[541],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[542],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[543],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[544],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[545],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[546],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[547],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[548],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[549],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[550],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[551],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[552],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[553],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[554],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[555],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[556],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[557],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[558],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[559],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[560],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[561],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[562],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[563],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[564],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[565],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[566],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[567],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[568],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[569],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[570],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[571],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[572],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[573],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[574],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[575],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[576],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[577],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[578],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[579],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[580],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[581],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[582],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[583],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[584],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[585],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[586],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[587],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[588],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[589],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[590],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[591],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[592],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[593],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[594],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[595],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[596],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[597],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[598],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[599],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[600],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[601],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[602],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[603],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[604],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[605],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[606],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[607],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[608],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[609],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[610],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[611],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[612],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[613],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[614],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[615],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[616],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[617],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[618],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[619],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[620],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[621],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[622],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[623],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[624],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[625],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[626],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[627],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[628],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[629],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[630],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[631],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[632],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[633],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[634],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[635],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[636],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[637],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[638],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[639],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) BMEP58_ECPU_EXT.DIO_CTRL.[640],,Boolean,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO control bits (1 bit per DIO up to 128 DIOs) WA3252_AFD_0103_1_SI.almHighHigh.Fault,401040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almHighHigh.AlarmState,401040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almHighHigh.GlobalReset,401040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almHighHigh.FaultInAlarm,401040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almHighHigh.ALRM,401040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almHighHigh.ANUN,401040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almHighHigh.AKED,401040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almHighHigh.Resetable,401040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almHighHigh.REST,401040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almHighHigh.ACKN,401040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almHighHigh.UACK,401040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almHighHigh.MCmd_Enable,401040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almHighHigh.MCmd_Disable,401040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almHighHigh.OCmd_Shelve,401040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almHighHigh.OCmd_Unshelve,401040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almHighHigh.SCmd_Suppress,401040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almHighHigh.SCmd_UnSuppress,401041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almHighHigh.AEShelveTMRDN,401041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almHighHigh.Bad,401041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almHighHigh.Suppress,401042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.UnSuppress,401042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Shelve,401042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.UnShelve,401042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Enable,401042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Disable,401042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Ack,401042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Reset,401042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Suppressed,401042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Shelved,401042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Disabled,401042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Acked,401042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almHighHigh.Alarm,401042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Fault,401052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almHigh.AlarmState,401052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almHigh.GlobalReset,401052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almHigh.FaultInAlarm,401052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almHigh.ALRM,401052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almHigh.ANUN,401052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almHigh.AKED,401052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almHigh.Resetable,401052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almHigh.REST,401052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almHigh.ACKN,401052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almHigh.UACK,401052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almHigh.MCmd_Enable,401052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almHigh.MCmd_Disable,401052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almHigh.OCmd_Shelve,401052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almHigh.OCmd_Unshelve,401052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almHigh.SCmd_Suppress,401052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almHigh.SCmd_UnSuppress,401053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almHigh.AEShelveTMRDN,401053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almHigh.Bad,401053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almHigh.Suppress,401054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.UnSuppress,401054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Shelve,401054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.UnShelve,401054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Enable,401054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Disable,401054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Ack,401054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Reset,401054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almHigh.Suppressed,401054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almHigh.Shelved,401054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almHigh.Disabled,401054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almHigh.Acked,401054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almHigh.Alarm,401054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Fault,401064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almLow.AlarmState,401064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almLow.GlobalReset,401064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almLow.FaultInAlarm,401064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almLow.ALRM,401064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almLow.ANUN,401064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almLow.AKED,401064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almLow.Resetable,401064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almLow.REST,401064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almLow.ACKN,401064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almLow.UACK,401064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almLow.MCmd_Enable,401064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almLow.MCmd_Disable,401064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almLow.OCmd_Shelve,401064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almLow.OCmd_Unshelve,401064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almLow.SCmd_Suppress,401064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almLow.SCmd_UnSuppress,401065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almLow.AEShelveTMRDN,401065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almLow.Bad,401065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almLow.Suppress,401066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.UnSuppress,401066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Shelve,401066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.UnShelve,401066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Enable,401066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Disable,401066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Ack,401066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Reset,401066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almLow.Suppressed,401066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almLow.Shelved,401066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almLow.Disabled,401066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almLow.Acked,401066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almLow.Alarm,401066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Fault,401076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almLowLow.AlarmState,401076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almLowLow.GlobalReset,401076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almLowLow.FaultInAlarm,401076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almLowLow.ALRM,401076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almLowLow.ANUN,401076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almLowLow.AKED,401076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almLowLow.Resetable,401076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almLowLow.REST,401076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almLowLow.ACKN,401076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almLowLow.UACK,401076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almLowLow.MCmd_Enable,401076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almLowLow.MCmd_Disable,401076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almLowLow.OCmd_Shelve,401076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almLowLow.OCmd_Unshelve,401076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almLowLow.SCmd_Suppress,401076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almLowLow.SCmd_UnSuppress,401077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almLowLow.AEShelveTMRDN,401077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almLowLow.Bad,401077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almLowLow.Suppress,401078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.UnSuppress,401078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Shelve,401078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.UnShelve,401078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Enable,401078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Disable,401078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Ack,401078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Reset,401078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almLowLow.Suppressed,401078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almLowLow.Shelved,401078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almLowLow.Disabled,401078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almLowLow.Acked,401078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almLowLow.Alarm,401078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Fault,401088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almBrokenLoop.AlarmState,401088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almBrokenLoop.GlobalReset,401088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almBrokenLoop.FaultInAlarm,401088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almBrokenLoop.ALRM,401088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almBrokenLoop.ANUN,401088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almBrokenLoop.AKED,401088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almBrokenLoop.Resetable,401088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almBrokenLoop.REST,401088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almBrokenLoop.ACKN,401088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almBrokenLoop.UACK,401088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almBrokenLoop.MCmd_Enable,401088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.MCmd_Disable,401088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.OCmd_Shelve,401088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.OCmd_Unshelve,401088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.SCmd_Suppress,401088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.SCmd_UnSuppress,401089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almBrokenLoop.AEShelveTMRDN,401089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almBrokenLoop.Bad,401089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almBrokenLoop.Suppress,401090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.UnSuppress,401090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Shelve,401090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.UnShelve,401090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Enable,401090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Disable,401090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Ack,401090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Reset,401090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Suppressed,401090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Shelved,401090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Disabled,401090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Acked,401090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almBrokenLoop.Alarm,401090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Fault,401100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almOverRange.AlarmState,401100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almOverRange.GlobalReset,401100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almOverRange.FaultInAlarm,401100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almOverRange.ALRM,401100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almOverRange.ANUN,401100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almOverRange.AKED,401100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almOverRange.Resetable,401100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almOverRange.REST,401100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almOverRange.ACKN,401100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almOverRange.UACK,401100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almOverRange.MCmd_Enable,401100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almOverRange.MCmd_Disable,401100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almOverRange.OCmd_Shelve,401100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almOverRange.OCmd_Unshelve,401100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almOverRange.SCmd_Suppress,401100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almOverRange.SCmd_UnSuppress,401101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almOverRange.AEShelveTMRDN,401101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almOverRange.Bad,401101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almOverRange.Suppress,401102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.UnSuppress,401102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Shelve,401102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.UnShelve,401102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Enable,401102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Disable,401102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Ack,401102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Reset,401102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almOverRange.Suppressed,401102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almOverRange.Shelved,401102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almOverRange.Disabled,401102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almOverRange.Acked,401102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almOverRange.Alarm,401102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Fault,401112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almUnderRange.AlarmState,401112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almUnderRange.GlobalReset,401112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almUnderRange.FaultInAlarm,401112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almUnderRange.ALRM,401112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almUnderRange.ANUN,401112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almUnderRange.AKED,401112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almUnderRange.Resetable,401112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almUnderRange.REST,401112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almUnderRange.ACKN,401112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almUnderRange.UACK,401112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almUnderRange.MCmd_Enable,401112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almUnderRange.MCmd_Disable,401112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almUnderRange.OCmd_Shelve,401112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almUnderRange.OCmd_Unshelve,401112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almUnderRange.SCmd_Suppress,401112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almUnderRange.SCmd_UnSuppress,401113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almUnderRange.AEShelveTMRDN,401113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almUnderRange.Bad,401113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almUnderRange.Suppress,401114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.UnSuppress,401114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Shelve,401114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.UnShelve,401114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Enable,401114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Disable,401114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Ack,401114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Reset,401114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Suppressed,401114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Shelved,401114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Disabled,401114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Acked,401114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almUnderRange.Alarm,401114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Fault,401124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almRateOfChange.AlarmState,401124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almRateOfChange.GlobalReset,401124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almRateOfChange.FaultInAlarm,401124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almRateOfChange.ALRM,401124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almRateOfChange.ANUN,401124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almRateOfChange.AKED,401124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almRateOfChange.Resetable,401124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almRateOfChange.REST,401124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almRateOfChange.ACKN,401124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almRateOfChange.UACK,401124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almRateOfChange.MCmd_Enable,401124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.MCmd_Disable,401124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.OCmd_Shelve,401124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.OCmd_Unshelve,401124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.SCmd_Suppress,401124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.SCmd_UnSuppress,401125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almRateOfChange.AEShelveTMRDN,401125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almRateOfChange.Bad,401125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almRateOfChange.Suppress,401126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.UnSuppress,401126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Shelve,401126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.UnShelve,401126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Enable,401126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Disable,401126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Ack,401126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Reset,401126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Suppressed,401126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Shelved,401126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Disabled,401126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Acked,401126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almRateOfChange.Alarm,401126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Fault,401136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_SI.almPLCFault.AlarmState,401136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_SI.almPLCFault.GlobalReset,401136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_SI.almPLCFault.FaultInAlarm,401136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_SI.almPLCFault.ALRM,401136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_SI.almPLCFault.ANUN,401136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_SI.almPLCFault.AKED,401136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_SI.almPLCFault.Resetable,401136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_SI.almPLCFault.REST,401136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_SI.almPLCFault.ACKN,401136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_SI.almPLCFault.UACK,401136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_SI.almPLCFault.MCmd_Enable,401136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_SI.almPLCFault.MCmd_Disable,401136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_SI.almPLCFault.OCmd_Shelve,401136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_SI.almPLCFault.OCmd_Unshelve,401136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_SI.almPLCFault.SCmd_Suppress,401136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_SI.almPLCFault.SCmd_UnSuppress,401137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_SI.almPLCFault.AEShelveTMRDN,401137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_SI.almPLCFault.Bad,401137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_SI.almPLCFault.Suppress,401138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.UnSuppress,401138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Shelve,401138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.UnShelve,401138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Enable,401138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Disable,401138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Ack,401138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Reset,401138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Suppressed,401138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Shelved,401138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Disabled,401138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Acked,401138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_SI.almPLCFault.Alarm,401138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Fault,401240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almHighHigh.AlarmState,401240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almHighHigh.GlobalReset,401240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almHighHigh.FaultInAlarm,401240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almHighHigh.ALRM,401240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almHighHigh.ANUN,401240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almHighHigh.AKED,401240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almHighHigh.Resetable,401240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almHighHigh.REST,401240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almHighHigh.ACKN,401240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almHighHigh.UACK,401240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almHighHigh.MCmd_Enable,401240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almHighHigh.MCmd_Disable,401240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almHighHigh.OCmd_Shelve,401240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almHighHigh.OCmd_Unshelve,401240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almHighHigh.SCmd_Suppress,401240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almHighHigh.SCmd_UnSuppress,401241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almHighHigh.AEShelveTMRDN,401241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almHighHigh.Bad,401241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almHighHigh.Suppress,401242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.UnSuppress,401242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Shelve,401242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.UnShelve,401242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Enable,401242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Disable,401242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Ack,401242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Reset,401242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Suppressed,401242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Shelved,401242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Disabled,401242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Acked,401242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almHighHigh.Alarm,401242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Fault,401252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almHigh.AlarmState,401252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almHigh.GlobalReset,401252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almHigh.FaultInAlarm,401252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almHigh.ALRM,401252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almHigh.ANUN,401252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almHigh.AKED,401252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almHigh.Resetable,401252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almHigh.REST,401252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almHigh.ACKN,401252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almHigh.UACK,401252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almHigh.MCmd_Enable,401252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almHigh.MCmd_Disable,401252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almHigh.OCmd_Shelve,401252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almHigh.OCmd_Unshelve,401252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almHigh.SCmd_Suppress,401252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almHigh.SCmd_UnSuppress,401253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almHigh.AEShelveTMRDN,401253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almHigh.Bad,401253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almHigh.Suppress,401254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.UnSuppress,401254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Shelve,401254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.UnShelve,401254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Enable,401254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Disable,401254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Ack,401254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Reset,401254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almHigh.Suppressed,401254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almHigh.Shelved,401254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almHigh.Disabled,401254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almHigh.Acked,401254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almHigh.Alarm,401254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Fault,401264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almLow.AlarmState,401264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almLow.GlobalReset,401264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almLow.FaultInAlarm,401264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almLow.ALRM,401264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almLow.ANUN,401264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almLow.AKED,401264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almLow.Resetable,401264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almLow.REST,401264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almLow.ACKN,401264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almLow.UACK,401264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almLow.MCmd_Enable,401264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almLow.MCmd_Disable,401264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almLow.OCmd_Shelve,401264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almLow.OCmd_Unshelve,401264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almLow.SCmd_Suppress,401264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almLow.SCmd_UnSuppress,401265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almLow.AEShelveTMRDN,401265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almLow.Bad,401265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almLow.Suppress,401266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.UnSuppress,401266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Shelve,401266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.UnShelve,401266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Enable,401266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Disable,401266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Ack,401266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Reset,401266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almLow.Suppressed,401266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almLow.Shelved,401266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almLow.Disabled,401266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almLow.Acked,401266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almLow.Alarm,401266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Fault,401276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almLowLow.AlarmState,401276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almLowLow.GlobalReset,401276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almLowLow.FaultInAlarm,401276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almLowLow.ALRM,401276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almLowLow.ANUN,401276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almLowLow.AKED,401276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almLowLow.Resetable,401276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almLowLow.REST,401276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almLowLow.ACKN,401276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almLowLow.UACK,401276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almLowLow.MCmd_Enable,401276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almLowLow.MCmd_Disable,401276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almLowLow.OCmd_Shelve,401276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almLowLow.OCmd_Unshelve,401276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almLowLow.SCmd_Suppress,401276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almLowLow.SCmd_UnSuppress,401277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almLowLow.AEShelveTMRDN,401277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almLowLow.Bad,401277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almLowLow.Suppress,401278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.UnSuppress,401278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Shelve,401278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.UnShelve,401278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Enable,401278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Disable,401278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Ack,401278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Reset,401278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almLowLow.Suppressed,401278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almLowLow.Shelved,401278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almLowLow.Disabled,401278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almLowLow.Acked,401278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almLowLow.Alarm,401278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Fault,401288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almBrokenLoop.AlarmState,401288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almBrokenLoop.GlobalReset,401288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almBrokenLoop.FaultInAlarm,401288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almBrokenLoop.ALRM,401288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almBrokenLoop.ANUN,401288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almBrokenLoop.AKED,401288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almBrokenLoop.Resetable,401288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almBrokenLoop.REST,401288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almBrokenLoop.ACKN,401288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almBrokenLoop.UACK,401288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almBrokenLoop.MCmd_Enable,401288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.MCmd_Disable,401288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.OCmd_Shelve,401288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.OCmd_Unshelve,401288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.SCmd_Suppress,401288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.SCmd_UnSuppress,401289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almBrokenLoop.AEShelveTMRDN,401289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almBrokenLoop.Bad,401289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almBrokenLoop.Suppress,401290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.UnSuppress,401290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Shelve,401290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.UnShelve,401290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Enable,401290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Disable,401290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Ack,401290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Reset,401290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Suppressed,401290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Shelved,401290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Disabled,401290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Acked,401290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almBrokenLoop.Alarm,401290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Fault,401300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almOverRange.AlarmState,401300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almOverRange.GlobalReset,401300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almOverRange.FaultInAlarm,401300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almOverRange.ALRM,401300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almOverRange.ANUN,401300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almOverRange.AKED,401300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almOverRange.Resetable,401300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almOverRange.REST,401300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almOverRange.ACKN,401300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almOverRange.UACK,401300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almOverRange.MCmd_Enable,401300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almOverRange.MCmd_Disable,401300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almOverRange.OCmd_Shelve,401300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almOverRange.OCmd_Unshelve,401300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almOverRange.SCmd_Suppress,401300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almOverRange.SCmd_UnSuppress,401301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almOverRange.AEShelveTMRDN,401301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almOverRange.Bad,401301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almOverRange.Suppress,401302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.UnSuppress,401302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Shelve,401302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.UnShelve,401302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Enable,401302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Disable,401302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Ack,401302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Reset,401302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almOverRange.Suppressed,401302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almOverRange.Shelved,401302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almOverRange.Disabled,401302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almOverRange.Acked,401302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almOverRange.Alarm,401302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Fault,401312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almUnderRange.AlarmState,401312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almUnderRange.GlobalReset,401312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almUnderRange.FaultInAlarm,401312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almUnderRange.ALRM,401312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almUnderRange.ANUN,401312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almUnderRange.AKED,401312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almUnderRange.Resetable,401312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almUnderRange.REST,401312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almUnderRange.ACKN,401312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almUnderRange.UACK,401312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almUnderRange.MCmd_Enable,401312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almUnderRange.MCmd_Disable,401312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almUnderRange.OCmd_Shelve,401312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almUnderRange.OCmd_Unshelve,401312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almUnderRange.SCmd_Suppress,401312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almUnderRange.SCmd_UnSuppress,401313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almUnderRange.AEShelveTMRDN,401313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almUnderRange.Bad,401313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almUnderRange.Suppress,401314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.UnSuppress,401314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Shelve,401314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.UnShelve,401314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Enable,401314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Disable,401314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Ack,401314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Reset,401314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Suppressed,401314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Shelved,401314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Disabled,401314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Acked,401314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almUnderRange.Alarm,401314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Fault,401324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almRateOfChange.AlarmState,401324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almRateOfChange.GlobalReset,401324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almRateOfChange.FaultInAlarm,401324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almRateOfChange.ALRM,401324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almRateOfChange.ANUN,401324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almRateOfChange.AKED,401324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almRateOfChange.Resetable,401324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almRateOfChange.REST,401324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almRateOfChange.ACKN,401324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almRateOfChange.UACK,401324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almRateOfChange.MCmd_Enable,401324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.MCmd_Disable,401324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.OCmd_Shelve,401324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.OCmd_Unshelve,401324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.SCmd_Suppress,401324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.SCmd_UnSuppress,401325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almRateOfChange.AEShelveTMRDN,401325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almRateOfChange.Bad,401325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almRateOfChange.Suppress,401326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.UnSuppress,401326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Shelve,401326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.UnShelve,401326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Enable,401326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Disable,401326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Ack,401326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Reset,401326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Suppressed,401326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Shelved,401326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Disabled,401326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Acked,401326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almRateOfChange.Alarm,401326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Fault,401336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_SI.almPLCFault.AlarmState,401336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_SI.almPLCFault.GlobalReset,401336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_SI.almPLCFault.FaultInAlarm,401336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_SI.almPLCFault.ALRM,401336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_SI.almPLCFault.ANUN,401336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_SI.almPLCFault.AKED,401336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_SI.almPLCFault.Resetable,401336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_SI.almPLCFault.REST,401336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_SI.almPLCFault.ACKN,401336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_SI.almPLCFault.UACK,401336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_SI.almPLCFault.MCmd_Enable,401336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_SI.almPLCFault.MCmd_Disable,401336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_SI.almPLCFault.OCmd_Shelve,401336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_SI.almPLCFault.OCmd_Unshelve,401336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_SI.almPLCFault.SCmd_Suppress,401336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_SI.almPLCFault.SCmd_UnSuppress,401337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_SI.almPLCFault.AEShelveTMRDN,401337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_SI.almPLCFault.Bad,401337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_SI.almPLCFault.Suppress,401338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.UnSuppress,401338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Shelve,401338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.UnShelve,401338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Enable,401338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Disable,401338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Ack,401338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Reset,401338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Suppressed,401338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Shelved,401338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Disabled,401338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Acked,401338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_SI.almPLCFault.Alarm,401338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Fault,401440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almHighHigh.AlarmState,401440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almHighHigh.GlobalReset,401440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almHighHigh.FaultInAlarm,401440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almHighHigh.ALRM,401440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almHighHigh.ANUN,401440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almHighHigh.AKED,401440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almHighHigh.Resetable,401440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almHighHigh.REST,401440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almHighHigh.ACKN,401440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almHighHigh.UACK,401440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almHighHigh.MCmd_Enable,401440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almHighHigh.MCmd_Disable,401440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almHighHigh.OCmd_Shelve,401440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almHighHigh.OCmd_Unshelve,401440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almHighHigh.SCmd_Suppress,401440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almHighHigh.SCmd_UnSuppress,401441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almHighHigh.AEShelveTMRDN,401441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almHighHigh.Bad,401441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almHighHigh.Suppress,401442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.UnSuppress,401442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Shelve,401442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.UnShelve,401442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Enable,401442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Disable,401442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Ack,401442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Reset,401442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Suppressed,401442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Shelved,401442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Disabled,401442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Acked,401442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almHighHigh.Alarm,401442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Fault,401452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almHigh.AlarmState,401452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almHigh.GlobalReset,401452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almHigh.FaultInAlarm,401452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almHigh.ALRM,401452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almHigh.ANUN,401452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almHigh.AKED,401452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almHigh.Resetable,401452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almHigh.REST,401452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almHigh.ACKN,401452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almHigh.UACK,401452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almHigh.MCmd_Enable,401452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almHigh.MCmd_Disable,401452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almHigh.OCmd_Shelve,401452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almHigh.OCmd_Unshelve,401452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almHigh.SCmd_Suppress,401452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almHigh.SCmd_UnSuppress,401453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almHigh.AEShelveTMRDN,401453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almHigh.Bad,401453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almHigh.Suppress,401454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.UnSuppress,401454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Shelve,401454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.UnShelve,401454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Enable,401454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Disable,401454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Ack,401454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Reset,401454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almHigh.Suppressed,401454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almHigh.Shelved,401454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almHigh.Disabled,401454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almHigh.Acked,401454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almHigh.Alarm,401454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Fault,401464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almLow.AlarmState,401464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almLow.GlobalReset,401464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almLow.FaultInAlarm,401464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almLow.ALRM,401464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almLow.ANUN,401464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almLow.AKED,401464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almLow.Resetable,401464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almLow.REST,401464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almLow.ACKN,401464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almLow.UACK,401464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almLow.MCmd_Enable,401464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almLow.MCmd_Disable,401464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almLow.OCmd_Shelve,401464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almLow.OCmd_Unshelve,401464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almLow.SCmd_Suppress,401464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almLow.SCmd_UnSuppress,401465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almLow.AEShelveTMRDN,401465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almLow.Bad,401465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almLow.Suppress,401466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.UnSuppress,401466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Shelve,401466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.UnShelve,401466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Enable,401466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Disable,401466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Ack,401466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Reset,401466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almLow.Suppressed,401466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almLow.Shelved,401466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almLow.Disabled,401466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almLow.Acked,401466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almLow.Alarm,401466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Fault,401476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almLowLow.AlarmState,401476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almLowLow.GlobalReset,401476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almLowLow.FaultInAlarm,401476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almLowLow.ALRM,401476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almLowLow.ANUN,401476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almLowLow.AKED,401476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almLowLow.Resetable,401476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almLowLow.REST,401476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almLowLow.ACKN,401476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almLowLow.UACK,401476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almLowLow.MCmd_Enable,401476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almLowLow.MCmd_Disable,401476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almLowLow.OCmd_Shelve,401476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almLowLow.OCmd_Unshelve,401476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almLowLow.SCmd_Suppress,401476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almLowLow.SCmd_UnSuppress,401477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almLowLow.AEShelveTMRDN,401477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almLowLow.Bad,401477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almLowLow.Suppress,401478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.UnSuppress,401478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Shelve,401478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.UnShelve,401478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Enable,401478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Disable,401478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Ack,401478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Reset,401478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almLowLow.Suppressed,401478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almLowLow.Shelved,401478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almLowLow.Disabled,401478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almLowLow.Acked,401478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almLowLow.Alarm,401478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Fault,401488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almBrokenLoop.AlarmState,401488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almBrokenLoop.GlobalReset,401488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almBrokenLoop.FaultInAlarm,401488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almBrokenLoop.ALRM,401488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almBrokenLoop.ANUN,401488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almBrokenLoop.AKED,401488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almBrokenLoop.Resetable,401488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almBrokenLoop.REST,401488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almBrokenLoop.ACKN,401488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almBrokenLoop.UACK,401488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almBrokenLoop.MCmd_Enable,401488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.MCmd_Disable,401488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.OCmd_Shelve,401488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.OCmd_Unshelve,401488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.SCmd_Suppress,401488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.SCmd_UnSuppress,401489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almBrokenLoop.AEShelveTMRDN,401489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almBrokenLoop.Bad,401489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almBrokenLoop.Suppress,401490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.UnSuppress,401490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Shelve,401490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.UnShelve,401490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Enable,401490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Disable,401490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Ack,401490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Reset,401490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Suppressed,401490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Shelved,401490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Disabled,401490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Acked,401490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almBrokenLoop.Alarm,401490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Fault,401500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almOverRange.AlarmState,401500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almOverRange.GlobalReset,401500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almOverRange.FaultInAlarm,401500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almOverRange.ALRM,401500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almOverRange.ANUN,401500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almOverRange.AKED,401500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almOverRange.Resetable,401500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almOverRange.REST,401500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almOverRange.ACKN,401500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almOverRange.UACK,401500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almOverRange.MCmd_Enable,401500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almOverRange.MCmd_Disable,401500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almOverRange.OCmd_Shelve,401500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almOverRange.OCmd_Unshelve,401500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almOverRange.SCmd_Suppress,401500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almOverRange.SCmd_UnSuppress,401501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almOverRange.AEShelveTMRDN,401501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almOverRange.Bad,401501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almOverRange.Suppress,401502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.UnSuppress,401502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Shelve,401502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.UnShelve,401502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Enable,401502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Disable,401502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Ack,401502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Reset,401502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almOverRange.Suppressed,401502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almOverRange.Shelved,401502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almOverRange.Disabled,401502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almOverRange.Acked,401502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almOverRange.Alarm,401502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Fault,401512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almUnderRange.AlarmState,401512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almUnderRange.GlobalReset,401512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almUnderRange.FaultInAlarm,401512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almUnderRange.ALRM,401512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almUnderRange.ANUN,401512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almUnderRange.AKED,401512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almUnderRange.Resetable,401512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almUnderRange.REST,401512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almUnderRange.ACKN,401512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almUnderRange.UACK,401512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almUnderRange.MCmd_Enable,401512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almUnderRange.MCmd_Disable,401512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almUnderRange.OCmd_Shelve,401512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almUnderRange.OCmd_Unshelve,401512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almUnderRange.SCmd_Suppress,401512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almUnderRange.SCmd_UnSuppress,401513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almUnderRange.AEShelveTMRDN,401513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almUnderRange.Bad,401513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almUnderRange.Suppress,401514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.UnSuppress,401514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Shelve,401514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.UnShelve,401514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Enable,401514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Disable,401514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Ack,401514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Reset,401514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Suppressed,401514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Shelved,401514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Disabled,401514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Acked,401514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almUnderRange.Alarm,401514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Fault,401524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almRateOfChange.AlarmState,401524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almRateOfChange.GlobalReset,401524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almRateOfChange.FaultInAlarm,401524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almRateOfChange.ALRM,401524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almRateOfChange.ANUN,401524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almRateOfChange.AKED,401524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almRateOfChange.Resetable,401524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almRateOfChange.REST,401524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almRateOfChange.ACKN,401524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almRateOfChange.UACK,401524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almRateOfChange.MCmd_Enable,401524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.MCmd_Disable,401524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.OCmd_Shelve,401524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.OCmd_Unshelve,401524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.SCmd_Suppress,401524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.SCmd_UnSuppress,401525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almRateOfChange.AEShelveTMRDN,401525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almRateOfChange.Bad,401525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almRateOfChange.Suppress,401526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.UnSuppress,401526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Shelve,401526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.UnShelve,401526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Enable,401526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Disable,401526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Ack,401526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Reset,401526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Suppressed,401526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Shelved,401526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Disabled,401526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Acked,401526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almRateOfChange.Alarm,401526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Fault,401536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_SI.almPLCFault.AlarmState,401536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_SI.almPLCFault.GlobalReset,401536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_SI.almPLCFault.FaultInAlarm,401536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_SI.almPLCFault.ALRM,401536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_SI.almPLCFault.ANUN,401536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_SI.almPLCFault.AKED,401536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_SI.almPLCFault.Resetable,401536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_SI.almPLCFault.REST,401536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_SI.almPLCFault.ACKN,401536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_SI.almPLCFault.UACK,401536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_SI.almPLCFault.MCmd_Enable,401536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_SI.almPLCFault.MCmd_Disable,401536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_SI.almPLCFault.OCmd_Shelve,401536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_SI.almPLCFault.OCmd_Unshelve,401536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_SI.almPLCFault.SCmd_Suppress,401536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_SI.almPLCFault.SCmd_UnSuppress,401537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_SI.almPLCFault.AEShelveTMRDN,401537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_SI.almPLCFault.Bad,401537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_SI.almPLCFault.Suppress,401538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.UnSuppress,401538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Shelve,401538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.UnShelve,401538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Enable,401538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Disable,401538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Ack,401538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Reset,401538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Suppressed,401538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Shelved,401538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Disabled,401538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Acked,401538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_SI.almPLCFault.Alarm,401538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Fault,401640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almHighHigh.AlarmState,401640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almHighHigh.GlobalReset,401640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almHighHigh.FaultInAlarm,401640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almHighHigh.ALRM,401640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almHighHigh.ANUN,401640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almHighHigh.AKED,401640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almHighHigh.Resetable,401640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almHighHigh.REST,401640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almHighHigh.ACKN,401640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almHighHigh.UACK,401640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almHighHigh.MCmd_Enable,401640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almHighHigh.MCmd_Disable,401640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almHighHigh.OCmd_Shelve,401640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almHighHigh.OCmd_Unshelve,401640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almHighHigh.SCmd_Suppress,401640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almHighHigh.SCmd_UnSuppress,401641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almHighHigh.AEShelveTMRDN,401641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almHighHigh.Bad,401641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almHighHigh.Suppress,401642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.UnSuppress,401642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Shelve,401642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.UnShelve,401642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Enable,401642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Disable,401642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Ack,401642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Reset,401642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Suppressed,401642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Shelved,401642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Disabled,401642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Acked,401642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almHighHigh.Alarm,401642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Fault,401652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almHigh.AlarmState,401652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almHigh.GlobalReset,401652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almHigh.FaultInAlarm,401652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almHigh.ALRM,401652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almHigh.ANUN,401652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almHigh.AKED,401652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almHigh.Resetable,401652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almHigh.REST,401652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almHigh.ACKN,401652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almHigh.UACK,401652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almHigh.MCmd_Enable,401652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almHigh.MCmd_Disable,401652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almHigh.OCmd_Shelve,401652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almHigh.OCmd_Unshelve,401652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almHigh.SCmd_Suppress,401652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almHigh.SCmd_UnSuppress,401653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almHigh.AEShelveTMRDN,401653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almHigh.Bad,401653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almHigh.Suppress,401654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.UnSuppress,401654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Shelve,401654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.UnShelve,401654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Enable,401654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Disable,401654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Ack,401654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Reset,401654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almHigh.Suppressed,401654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almHigh.Shelved,401654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almHigh.Disabled,401654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almHigh.Acked,401654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almHigh.Alarm,401654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Fault,401664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almLow.AlarmState,401664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almLow.GlobalReset,401664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almLow.FaultInAlarm,401664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almLow.ALRM,401664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almLow.ANUN,401664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almLow.AKED,401664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almLow.Resetable,401664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almLow.REST,401664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almLow.ACKN,401664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almLow.UACK,401664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almLow.MCmd_Enable,401664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almLow.MCmd_Disable,401664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almLow.OCmd_Shelve,401664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almLow.OCmd_Unshelve,401664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almLow.SCmd_Suppress,401664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almLow.SCmd_UnSuppress,401665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almLow.AEShelveTMRDN,401665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almLow.Bad,401665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almLow.Suppress,401666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.UnSuppress,401666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Shelve,401666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.UnShelve,401666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Enable,401666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Disable,401666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Ack,401666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Reset,401666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almLow.Suppressed,401666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almLow.Shelved,401666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almLow.Disabled,401666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almLow.Acked,401666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almLow.Alarm,401666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Fault,401676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almLowLow.AlarmState,401676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almLowLow.GlobalReset,401676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almLowLow.FaultInAlarm,401676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almLowLow.ALRM,401676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almLowLow.ANUN,401676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almLowLow.AKED,401676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almLowLow.Resetable,401676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almLowLow.REST,401676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almLowLow.ACKN,401676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almLowLow.UACK,401676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almLowLow.MCmd_Enable,401676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almLowLow.MCmd_Disable,401676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almLowLow.OCmd_Shelve,401676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almLowLow.OCmd_Unshelve,401676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almLowLow.SCmd_Suppress,401676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almLowLow.SCmd_UnSuppress,401677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almLowLow.AEShelveTMRDN,401677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almLowLow.Bad,401677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almLowLow.Suppress,401678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.UnSuppress,401678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Shelve,401678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.UnShelve,401678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Enable,401678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Disable,401678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Ack,401678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Reset,401678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almLowLow.Suppressed,401678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almLowLow.Shelved,401678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almLowLow.Disabled,401678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almLowLow.Acked,401678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almLowLow.Alarm,401678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Fault,401688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almBrokenLoop.AlarmState,401688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almBrokenLoop.GlobalReset,401688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almBrokenLoop.FaultInAlarm,401688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almBrokenLoop.ALRM,401688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almBrokenLoop.ANUN,401688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almBrokenLoop.AKED,401688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almBrokenLoop.Resetable,401688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almBrokenLoop.REST,401688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almBrokenLoop.ACKN,401688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almBrokenLoop.UACK,401688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almBrokenLoop.MCmd_Enable,401688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.MCmd_Disable,401688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.OCmd_Shelve,401688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.OCmd_Unshelve,401688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.SCmd_Suppress,401688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.SCmd_UnSuppress,401689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almBrokenLoop.AEShelveTMRDN,401689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almBrokenLoop.Bad,401689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almBrokenLoop.Suppress,401690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.UnSuppress,401690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Shelve,401690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.UnShelve,401690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Enable,401690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Disable,401690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Ack,401690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Reset,401690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Suppressed,401690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Shelved,401690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Disabled,401690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Acked,401690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almBrokenLoop.Alarm,401690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Fault,401700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almOverRange.AlarmState,401700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almOverRange.GlobalReset,401700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almOverRange.FaultInAlarm,401700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almOverRange.ALRM,401700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almOverRange.ANUN,401700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almOverRange.AKED,401700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almOverRange.Resetable,401700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almOverRange.REST,401700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almOverRange.ACKN,401700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almOverRange.UACK,401700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almOverRange.MCmd_Enable,401700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almOverRange.MCmd_Disable,401700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almOverRange.OCmd_Shelve,401700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almOverRange.OCmd_Unshelve,401700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almOverRange.SCmd_Suppress,401700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almOverRange.SCmd_UnSuppress,401701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almOverRange.AEShelveTMRDN,401701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almOverRange.Bad,401701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almOverRange.Suppress,401702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.UnSuppress,401702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Shelve,401702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.UnShelve,401702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Enable,401702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Disable,401702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Ack,401702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Reset,401702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almOverRange.Suppressed,401702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almOverRange.Shelved,401702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almOverRange.Disabled,401702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almOverRange.Acked,401702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almOverRange.Alarm,401702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Fault,401712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almUnderRange.AlarmState,401712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almUnderRange.GlobalReset,401712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almUnderRange.FaultInAlarm,401712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almUnderRange.ALRM,401712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almUnderRange.ANUN,401712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almUnderRange.AKED,401712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almUnderRange.Resetable,401712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almUnderRange.REST,401712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almUnderRange.ACKN,401712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almUnderRange.UACK,401712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almUnderRange.MCmd_Enable,401712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almUnderRange.MCmd_Disable,401712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almUnderRange.OCmd_Shelve,401712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almUnderRange.OCmd_Unshelve,401712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almUnderRange.SCmd_Suppress,401712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almUnderRange.SCmd_UnSuppress,401713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almUnderRange.AEShelveTMRDN,401713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almUnderRange.Bad,401713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almUnderRange.Suppress,401714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.UnSuppress,401714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Shelve,401714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.UnShelve,401714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Enable,401714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Disable,401714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Ack,401714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Reset,401714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Suppressed,401714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Shelved,401714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Disabled,401714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Acked,401714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almUnderRange.Alarm,401714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Fault,401724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almRateOfChange.AlarmState,401724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almRateOfChange.GlobalReset,401724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almRateOfChange.FaultInAlarm,401724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almRateOfChange.ALRM,401724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almRateOfChange.ANUN,401724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almRateOfChange.AKED,401724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almRateOfChange.Resetable,401724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almRateOfChange.REST,401724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almRateOfChange.ACKN,401724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almRateOfChange.UACK,401724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almRateOfChange.MCmd_Enable,401724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.MCmd_Disable,401724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.OCmd_Shelve,401724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.OCmd_Unshelve,401724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.SCmd_Suppress,401724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.SCmd_UnSuppress,401725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almRateOfChange.AEShelveTMRDN,401725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almRateOfChange.Bad,401725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almRateOfChange.Suppress,401726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.UnSuppress,401726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Shelve,401726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.UnShelve,401726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Enable,401726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Disable,401726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Ack,401726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Reset,401726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Suppressed,401726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Shelved,401726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Disabled,401726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Acked,401726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almRateOfChange.Alarm,401726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Fault,401736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_SI.almPLCFault.AlarmState,401736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_SI.almPLCFault.GlobalReset,401736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_SI.almPLCFault.FaultInAlarm,401736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_SI.almPLCFault.ALRM,401736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_SI.almPLCFault.ANUN,401736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_SI.almPLCFault.AKED,401736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_SI.almPLCFault.Resetable,401736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_SI.almPLCFault.REST,401736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_SI.almPLCFault.ACKN,401736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_SI.almPLCFault.UACK,401736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_SI.almPLCFault.MCmd_Enable,401736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_SI.almPLCFault.MCmd_Disable,401736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_SI.almPLCFault.OCmd_Shelve,401736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_SI.almPLCFault.OCmd_Unshelve,401736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_SI.almPLCFault.SCmd_Suppress,401736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_SI.almPLCFault.SCmd_UnSuppress,401737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_SI.almPLCFault.AEShelveTMRDN,401737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_SI.almPLCFault.Bad,401737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_SI.almPLCFault.Suppress,401738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.UnSuppress,401738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Shelve,401738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.UnShelve,401738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Enable,401738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Disable,401738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Ack,401738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Reset,401738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Suppressed,401738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Shelved,401738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Disabled,401738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Acked,401738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_SI.almPLCFault.Alarm,401738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Fault,401840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almHighHigh.AlarmState,401840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almHighHigh.GlobalReset,401840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almHighHigh.FaultInAlarm,401840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almHighHigh.ALRM,401840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almHighHigh.ANUN,401840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almHighHigh.AKED,401840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almHighHigh.Resetable,401840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almHighHigh.REST,401840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almHighHigh.ACKN,401840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almHighHigh.UACK,401840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almHighHigh.MCmd_Enable,401840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almHighHigh.MCmd_Disable,401840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almHighHigh.OCmd_Shelve,401840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almHighHigh.OCmd_Unshelve,401840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almHighHigh.SCmd_Suppress,401840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almHighHigh.SCmd_UnSuppress,401841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almHighHigh.AEShelveTMRDN,401841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almHighHigh.Bad,401841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almHighHigh.Suppress,401842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.UnSuppress,401842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Shelve,401842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.UnShelve,401842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Enable,401842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Disable,401842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Ack,401842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Reset,401842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Suppressed,401842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Shelved,401842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Disabled,401842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Acked,401842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almHighHigh.Alarm,401842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Fault,401852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almHigh.AlarmState,401852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almHigh.GlobalReset,401852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almHigh.FaultInAlarm,401852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almHigh.ALRM,401852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almHigh.ANUN,401852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almHigh.AKED,401852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almHigh.Resetable,401852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almHigh.REST,401852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almHigh.ACKN,401852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almHigh.UACK,401852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almHigh.MCmd_Enable,401852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almHigh.MCmd_Disable,401852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almHigh.OCmd_Shelve,401852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almHigh.OCmd_Unshelve,401852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almHigh.SCmd_Suppress,401852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almHigh.SCmd_UnSuppress,401853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almHigh.AEShelveTMRDN,401853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almHigh.Bad,401853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almHigh.Suppress,401854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.UnSuppress,401854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Shelve,401854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.UnShelve,401854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Enable,401854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Disable,401854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Ack,401854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Reset,401854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almHigh.Suppressed,401854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almHigh.Shelved,401854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almHigh.Disabled,401854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almHigh.Acked,401854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almHigh.Alarm,401854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Fault,401864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almLow.AlarmState,401864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almLow.GlobalReset,401864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almLow.FaultInAlarm,401864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almLow.ALRM,401864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almLow.ANUN,401864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almLow.AKED,401864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almLow.Resetable,401864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almLow.REST,401864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almLow.ACKN,401864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almLow.UACK,401864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almLow.MCmd_Enable,401864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almLow.MCmd_Disable,401864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almLow.OCmd_Shelve,401864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almLow.OCmd_Unshelve,401864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almLow.SCmd_Suppress,401864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almLow.SCmd_UnSuppress,401865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almLow.AEShelveTMRDN,401865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almLow.Bad,401865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almLow.Suppress,401866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.UnSuppress,401866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Shelve,401866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.UnShelve,401866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Enable,401866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Disable,401866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Ack,401866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Reset,401866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almLow.Suppressed,401866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almLow.Shelved,401866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almLow.Disabled,401866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almLow.Acked,401866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almLow.Alarm,401866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Fault,401876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almLowLow.AlarmState,401876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almLowLow.GlobalReset,401876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almLowLow.FaultInAlarm,401876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almLowLow.ALRM,401876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almLowLow.ANUN,401876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almLowLow.AKED,401876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almLowLow.Resetable,401876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almLowLow.REST,401876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almLowLow.ACKN,401876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almLowLow.UACK,401876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almLowLow.MCmd_Enable,401876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almLowLow.MCmd_Disable,401876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almLowLow.OCmd_Shelve,401876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almLowLow.OCmd_Unshelve,401876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almLowLow.SCmd_Suppress,401876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almLowLow.SCmd_UnSuppress,401877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almLowLow.AEShelveTMRDN,401877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almLowLow.Bad,401877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almLowLow.Suppress,401878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.UnSuppress,401878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Shelve,401878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.UnShelve,401878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Enable,401878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Disable,401878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Ack,401878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Reset,401878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almLowLow.Suppressed,401878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almLowLow.Shelved,401878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almLowLow.Disabled,401878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almLowLow.Acked,401878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almLowLow.Alarm,401878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Fault,401888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almBrokenLoop.AlarmState,401888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almBrokenLoop.GlobalReset,401888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almBrokenLoop.FaultInAlarm,401888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almBrokenLoop.ALRM,401888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almBrokenLoop.ANUN,401888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almBrokenLoop.AKED,401888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almBrokenLoop.Resetable,401888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almBrokenLoop.REST,401888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almBrokenLoop.ACKN,401888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almBrokenLoop.UACK,401888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almBrokenLoop.MCmd_Enable,401888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.MCmd_Disable,401888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.OCmd_Shelve,401888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.OCmd_Unshelve,401888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.SCmd_Suppress,401888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.SCmd_UnSuppress,401889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almBrokenLoop.AEShelveTMRDN,401889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almBrokenLoop.Bad,401889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almBrokenLoop.Suppress,401890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.UnSuppress,401890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Shelve,401890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.UnShelve,401890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Enable,401890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Disable,401890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Ack,401890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Reset,401890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Suppressed,401890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Shelved,401890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Disabled,401890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Acked,401890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almBrokenLoop.Alarm,401890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Fault,401900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almOverRange.AlarmState,401900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almOverRange.GlobalReset,401900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almOverRange.FaultInAlarm,401900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almOverRange.ALRM,401900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almOverRange.ANUN,401900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almOverRange.AKED,401900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almOverRange.Resetable,401900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almOverRange.REST,401900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almOverRange.ACKN,401900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almOverRange.UACK,401900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almOverRange.MCmd_Enable,401900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almOverRange.MCmd_Disable,401900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almOverRange.OCmd_Shelve,401900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almOverRange.OCmd_Unshelve,401900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almOverRange.SCmd_Suppress,401900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almOverRange.SCmd_UnSuppress,401901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almOverRange.AEShelveTMRDN,401901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almOverRange.Bad,401901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almOverRange.Suppress,401902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.UnSuppress,401902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Shelve,401902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.UnShelve,401902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Enable,401902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Disable,401902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Ack,401902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Reset,401902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almOverRange.Suppressed,401902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almOverRange.Shelved,401902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almOverRange.Disabled,401902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almOverRange.Acked,401902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almOverRange.Alarm,401902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Fault,401912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almUnderRange.AlarmState,401912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almUnderRange.GlobalReset,401912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almUnderRange.FaultInAlarm,401912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almUnderRange.ALRM,401912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almUnderRange.ANUN,401912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almUnderRange.AKED,401912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almUnderRange.Resetable,401912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almUnderRange.REST,401912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almUnderRange.ACKN,401912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almUnderRange.UACK,401912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almUnderRange.MCmd_Enable,401912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almUnderRange.MCmd_Disable,401912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almUnderRange.OCmd_Shelve,401912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almUnderRange.OCmd_Unshelve,401912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almUnderRange.SCmd_Suppress,401912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almUnderRange.SCmd_UnSuppress,401913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almUnderRange.AEShelveTMRDN,401913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almUnderRange.Bad,401913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almUnderRange.Suppress,401914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.UnSuppress,401914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Shelve,401914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.UnShelve,401914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Enable,401914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Disable,401914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Ack,401914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Reset,401914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Suppressed,401914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Shelved,401914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Disabled,401914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Acked,401914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almUnderRange.Alarm,401914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Fault,401924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almRateOfChange.AlarmState,401924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almRateOfChange.GlobalReset,401924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almRateOfChange.FaultInAlarm,401924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almRateOfChange.ALRM,401924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almRateOfChange.ANUN,401924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almRateOfChange.AKED,401924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almRateOfChange.Resetable,401924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almRateOfChange.REST,401924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almRateOfChange.ACKN,401924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almRateOfChange.UACK,401924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almRateOfChange.MCmd_Enable,401924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.MCmd_Disable,401924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.OCmd_Shelve,401924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.OCmd_Unshelve,401924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.SCmd_Suppress,401924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.SCmd_UnSuppress,401925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almRateOfChange.AEShelveTMRDN,401925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almRateOfChange.Bad,401925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almRateOfChange.Suppress,401926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.UnSuppress,401926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Shelve,401926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.UnShelve,401926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Enable,401926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Disable,401926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Ack,401926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Reset,401926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Suppressed,401926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Shelved,401926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Disabled,401926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Acked,401926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almRateOfChange.Alarm,401926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Fault,401936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_SI.almPLCFault.AlarmState,401936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_SI.almPLCFault.GlobalReset,401936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_SI.almPLCFault.FaultInAlarm,401936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_SI.almPLCFault.ALRM,401936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_SI.almPLCFault.ANUN,401936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_SI.almPLCFault.AKED,401936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_SI.almPLCFault.Resetable,401936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_SI.almPLCFault.REST,401936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_SI.almPLCFault.ACKN,401936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_SI.almPLCFault.UACK,401936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_SI.almPLCFault.MCmd_Enable,401936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_SI.almPLCFault.MCmd_Disable,401936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_SI.almPLCFault.OCmd_Shelve,401936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_SI.almPLCFault.OCmd_Unshelve,401936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_SI.almPLCFault.SCmd_Suppress,401936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_SI.almPLCFault.SCmd_UnSuppress,401937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_SI.almPLCFault.AEShelveTMRDN,401937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_SI.almPLCFault.Bad,401937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_SI.almPLCFault.Suppress,401938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.UnSuppress,401938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Shelve,401938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.UnShelve,401938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Enable,401938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Disable,401938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Ack,401938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Reset,401938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Suppressed,401938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Shelved,401938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Disabled,401938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Acked,401938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_SI.almPLCFault.Alarm,401938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Fault,402040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almHighHigh.AlarmState,402040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almHighHigh.GlobalReset,402040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almHighHigh.FaultInAlarm,402040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almHighHigh.ALRM,402040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almHighHigh.ANUN,402040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almHighHigh.AKED,402040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almHighHigh.Resetable,402040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almHighHigh.REST,402040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almHighHigh.ACKN,402040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almHighHigh.UACK,402040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almHighHigh.MCmd_Enable,402040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almHighHigh.MCmd_Disable,402040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almHighHigh.OCmd_Shelve,402040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almHighHigh.OCmd_Unshelve,402040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almHighHigh.SCmd_Suppress,402040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almHighHigh.SCmd_UnSuppress,402041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almHighHigh.AEShelveTMRDN,402041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almHighHigh.Bad,402041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almHighHigh.Suppress,402042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.UnSuppress,402042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Shelve,402042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.UnShelve,402042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Enable,402042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Disable,402042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Ack,402042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Reset,402042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Suppressed,402042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Shelved,402042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Disabled,402042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Acked,402042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almHighHigh.Alarm,402042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Fault,402052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almHigh.AlarmState,402052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almHigh.GlobalReset,402052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almHigh.FaultInAlarm,402052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almHigh.ALRM,402052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almHigh.ANUN,402052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almHigh.AKED,402052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almHigh.Resetable,402052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almHigh.REST,402052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almHigh.ACKN,402052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almHigh.UACK,402052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almHigh.MCmd_Enable,402052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almHigh.MCmd_Disable,402052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almHigh.OCmd_Shelve,402052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almHigh.OCmd_Unshelve,402052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almHigh.SCmd_Suppress,402052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almHigh.SCmd_UnSuppress,402053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almHigh.AEShelveTMRDN,402053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almHigh.Bad,402053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almHigh.Suppress,402054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.UnSuppress,402054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Shelve,402054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.UnShelve,402054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Enable,402054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Disable,402054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Ack,402054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Reset,402054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almHigh.Suppressed,402054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almHigh.Shelved,402054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almHigh.Disabled,402054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almHigh.Acked,402054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almHigh.Alarm,402054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Fault,402064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almLow.AlarmState,402064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almLow.GlobalReset,402064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almLow.FaultInAlarm,402064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almLow.ALRM,402064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almLow.ANUN,402064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almLow.AKED,402064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almLow.Resetable,402064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almLow.REST,402064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almLow.ACKN,402064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almLow.UACK,402064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almLow.MCmd_Enable,402064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almLow.MCmd_Disable,402064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almLow.OCmd_Shelve,402064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almLow.OCmd_Unshelve,402064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almLow.SCmd_Suppress,402064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almLow.SCmd_UnSuppress,402065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almLow.AEShelveTMRDN,402065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almLow.Bad,402065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almLow.Suppress,402066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.UnSuppress,402066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Shelve,402066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.UnShelve,402066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Enable,402066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Disable,402066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Ack,402066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Reset,402066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almLow.Suppressed,402066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almLow.Shelved,402066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almLow.Disabled,402066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almLow.Acked,402066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almLow.Alarm,402066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Fault,402076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almLowLow.AlarmState,402076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almLowLow.GlobalReset,402076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almLowLow.FaultInAlarm,402076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almLowLow.ALRM,402076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almLowLow.ANUN,402076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almLowLow.AKED,402076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almLowLow.Resetable,402076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almLowLow.REST,402076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almLowLow.ACKN,402076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almLowLow.UACK,402076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almLowLow.MCmd_Enable,402076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almLowLow.MCmd_Disable,402076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almLowLow.OCmd_Shelve,402076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almLowLow.OCmd_Unshelve,402076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almLowLow.SCmd_Suppress,402076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almLowLow.SCmd_UnSuppress,402077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almLowLow.AEShelveTMRDN,402077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almLowLow.Bad,402077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almLowLow.Suppress,402078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.UnSuppress,402078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Shelve,402078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.UnShelve,402078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Enable,402078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Disable,402078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Ack,402078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Reset,402078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almLowLow.Suppressed,402078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almLowLow.Shelved,402078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almLowLow.Disabled,402078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almLowLow.Acked,402078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almLowLow.Alarm,402078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Fault,402088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almBrokenLoop.AlarmState,402088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almBrokenLoop.GlobalReset,402088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almBrokenLoop.FaultInAlarm,402088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almBrokenLoop.ALRM,402088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almBrokenLoop.ANUN,402088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almBrokenLoop.AKED,402088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almBrokenLoop.Resetable,402088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almBrokenLoop.REST,402088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almBrokenLoop.ACKN,402088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almBrokenLoop.UACK,402088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almBrokenLoop.MCmd_Enable,402088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.MCmd_Disable,402088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.OCmd_Shelve,402088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.OCmd_Unshelve,402088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.SCmd_Suppress,402088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.SCmd_UnSuppress,402089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almBrokenLoop.AEShelveTMRDN,402089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almBrokenLoop.Bad,402089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almBrokenLoop.Suppress,402090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.UnSuppress,402090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Shelve,402090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.UnShelve,402090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Enable,402090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Disable,402090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Ack,402090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Reset,402090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Suppressed,402090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Shelved,402090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Disabled,402090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Acked,402090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almBrokenLoop.Alarm,402090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Fault,402100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almOverRange.AlarmState,402100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almOverRange.GlobalReset,402100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almOverRange.FaultInAlarm,402100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almOverRange.ALRM,402100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almOverRange.ANUN,402100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almOverRange.AKED,402100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almOverRange.Resetable,402100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almOverRange.REST,402100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almOverRange.ACKN,402100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almOverRange.UACK,402100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almOverRange.MCmd_Enable,402100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almOverRange.MCmd_Disable,402100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almOverRange.OCmd_Shelve,402100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almOverRange.OCmd_Unshelve,402100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almOverRange.SCmd_Suppress,402100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almOverRange.SCmd_UnSuppress,402101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almOverRange.AEShelveTMRDN,402101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almOverRange.Bad,402101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almOverRange.Suppress,402102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.UnSuppress,402102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Shelve,402102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.UnShelve,402102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Enable,402102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Disable,402102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Ack,402102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Reset,402102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almOverRange.Suppressed,402102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almOverRange.Shelved,402102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almOverRange.Disabled,402102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almOverRange.Acked,402102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almOverRange.Alarm,402102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Fault,402112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almUnderRange.AlarmState,402112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almUnderRange.GlobalReset,402112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almUnderRange.FaultInAlarm,402112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almUnderRange.ALRM,402112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almUnderRange.ANUN,402112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almUnderRange.AKED,402112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almUnderRange.Resetable,402112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almUnderRange.REST,402112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almUnderRange.ACKN,402112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almUnderRange.UACK,402112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almUnderRange.MCmd_Enable,402112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almUnderRange.MCmd_Disable,402112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almUnderRange.OCmd_Shelve,402112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almUnderRange.OCmd_Unshelve,402112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almUnderRange.SCmd_Suppress,402112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almUnderRange.SCmd_UnSuppress,402113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almUnderRange.AEShelveTMRDN,402113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almUnderRange.Bad,402113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almUnderRange.Suppress,402114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.UnSuppress,402114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Shelve,402114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.UnShelve,402114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Enable,402114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Disable,402114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Ack,402114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Reset,402114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Suppressed,402114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Shelved,402114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Disabled,402114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Acked,402114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almUnderRange.Alarm,402114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Fault,402124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almRateOfChange.AlarmState,402124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almRateOfChange.GlobalReset,402124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almRateOfChange.FaultInAlarm,402124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almRateOfChange.ALRM,402124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almRateOfChange.ANUN,402124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almRateOfChange.AKED,402124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almRateOfChange.Resetable,402124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almRateOfChange.REST,402124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almRateOfChange.ACKN,402124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almRateOfChange.UACK,402124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almRateOfChange.MCmd_Enable,402124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.MCmd_Disable,402124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.OCmd_Shelve,402124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.OCmd_Unshelve,402124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.SCmd_Suppress,402124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.SCmd_UnSuppress,402125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almRateOfChange.AEShelveTMRDN,402125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almRateOfChange.Bad,402125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almRateOfChange.Suppress,402126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.UnSuppress,402126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Shelve,402126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.UnShelve,402126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Enable,402126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Disable,402126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Ack,402126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Reset,402126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Suppressed,402126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Shelved,402126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Disabled,402126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Acked,402126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almRateOfChange.Alarm,402126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Fault,402136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_SI.almPLCFault.AlarmState,402136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_SI.almPLCFault.GlobalReset,402136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_SI.almPLCFault.FaultInAlarm,402136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_SI.almPLCFault.ALRM,402136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_SI.almPLCFault.ANUN,402136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_SI.almPLCFault.AKED,402136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_SI.almPLCFault.Resetable,402136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_SI.almPLCFault.REST,402136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_SI.almPLCFault.ACKN,402136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_SI.almPLCFault.UACK,402136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_SI.almPLCFault.MCmd_Enable,402136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_SI.almPLCFault.MCmd_Disable,402136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_SI.almPLCFault.OCmd_Shelve,402136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_SI.almPLCFault.OCmd_Unshelve,402136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_SI.almPLCFault.SCmd_Suppress,402136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_SI.almPLCFault.SCmd_UnSuppress,402137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_SI.almPLCFault.AEShelveTMRDN,402137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_SI.almPLCFault.Bad,402137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_SI.almPLCFault.Suppress,402138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.UnSuppress,402138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Shelve,402138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.UnShelve,402138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Enable,402138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Disable,402138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Ack,402138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Reset,402138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Suppressed,402138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Shelved,402138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Disabled,402138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Acked,402138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_SI.almPLCFault.Alarm,402138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Fault,402240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almHighHigh.AlarmState,402240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almHighHigh.GlobalReset,402240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almHighHigh.FaultInAlarm,402240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almHighHigh.ALRM,402240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almHighHigh.ANUN,402240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almHighHigh.AKED,402240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almHighHigh.Resetable,402240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almHighHigh.REST,402240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almHighHigh.ACKN,402240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almHighHigh.UACK,402240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almHighHigh.MCmd_Enable,402240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almHighHigh.MCmd_Disable,402240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almHighHigh.OCmd_Shelve,402240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almHighHigh.OCmd_Unshelve,402240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almHighHigh.SCmd_Suppress,402240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almHighHigh.SCmd_UnSuppress,402241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almHighHigh.AEShelveTMRDN,402241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almHighHigh.Bad,402241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almHighHigh.Suppress,402242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.UnSuppress,402242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Shelve,402242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.UnShelve,402242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Enable,402242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Disable,402242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Ack,402242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Reset,402242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Suppressed,402242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Shelved,402242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Disabled,402242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Acked,402242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almHighHigh.Alarm,402242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Fault,402252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almHigh.AlarmState,402252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almHigh.GlobalReset,402252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almHigh.FaultInAlarm,402252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almHigh.ALRM,402252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almHigh.ANUN,402252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almHigh.AKED,402252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almHigh.Resetable,402252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almHigh.REST,402252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almHigh.ACKN,402252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almHigh.UACK,402252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almHigh.MCmd_Enable,402252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almHigh.MCmd_Disable,402252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almHigh.OCmd_Shelve,402252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almHigh.OCmd_Unshelve,402252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almHigh.SCmd_Suppress,402252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almHigh.SCmd_UnSuppress,402253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almHigh.AEShelveTMRDN,402253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almHigh.Bad,402253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almHigh.Suppress,402254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.UnSuppress,402254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Shelve,402254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.UnShelve,402254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Enable,402254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Disable,402254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Ack,402254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Reset,402254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almHigh.Suppressed,402254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almHigh.Shelved,402254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almHigh.Disabled,402254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almHigh.Acked,402254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almHigh.Alarm,402254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Fault,402264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almLow.AlarmState,402264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almLow.GlobalReset,402264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almLow.FaultInAlarm,402264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almLow.ALRM,402264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almLow.ANUN,402264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almLow.AKED,402264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almLow.Resetable,402264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almLow.REST,402264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almLow.ACKN,402264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almLow.UACK,402264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almLow.MCmd_Enable,402264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almLow.MCmd_Disable,402264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almLow.OCmd_Shelve,402264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almLow.OCmd_Unshelve,402264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almLow.SCmd_Suppress,402264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almLow.SCmd_UnSuppress,402265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almLow.AEShelveTMRDN,402265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almLow.Bad,402265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almLow.Suppress,402266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.UnSuppress,402266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Shelve,402266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.UnShelve,402266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Enable,402266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Disable,402266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Ack,402266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Reset,402266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almLow.Suppressed,402266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almLow.Shelved,402266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almLow.Disabled,402266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almLow.Acked,402266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almLow.Alarm,402266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Fault,402276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almLowLow.AlarmState,402276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almLowLow.GlobalReset,402276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almLowLow.FaultInAlarm,402276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almLowLow.ALRM,402276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almLowLow.ANUN,402276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almLowLow.AKED,402276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almLowLow.Resetable,402276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almLowLow.REST,402276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almLowLow.ACKN,402276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almLowLow.UACK,402276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almLowLow.MCmd_Enable,402276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almLowLow.MCmd_Disable,402276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almLowLow.OCmd_Shelve,402276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almLowLow.OCmd_Unshelve,402276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almLowLow.SCmd_Suppress,402276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almLowLow.SCmd_UnSuppress,402277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almLowLow.AEShelveTMRDN,402277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almLowLow.Bad,402277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almLowLow.Suppress,402278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.UnSuppress,402278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Shelve,402278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.UnShelve,402278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Enable,402278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Disable,402278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Ack,402278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Reset,402278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almLowLow.Suppressed,402278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almLowLow.Shelved,402278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almLowLow.Disabled,402278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almLowLow.Acked,402278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almLowLow.Alarm,402278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Fault,402288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almBrokenLoop.AlarmState,402288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almBrokenLoop.GlobalReset,402288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almBrokenLoop.FaultInAlarm,402288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almBrokenLoop.ALRM,402288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almBrokenLoop.ANUN,402288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almBrokenLoop.AKED,402288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almBrokenLoop.Resetable,402288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almBrokenLoop.REST,402288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almBrokenLoop.ACKN,402288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almBrokenLoop.UACK,402288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almBrokenLoop.MCmd_Enable,402288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.MCmd_Disable,402288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.OCmd_Shelve,402288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.OCmd_Unshelve,402288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.SCmd_Suppress,402288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.SCmd_UnSuppress,402289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almBrokenLoop.AEShelveTMRDN,402289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almBrokenLoop.Bad,402289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almBrokenLoop.Suppress,402290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.UnSuppress,402290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Shelve,402290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.UnShelve,402290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Enable,402290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Disable,402290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Ack,402290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Reset,402290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Suppressed,402290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Shelved,402290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Disabled,402290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Acked,402290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almBrokenLoop.Alarm,402290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Fault,402300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almOverRange.AlarmState,402300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almOverRange.GlobalReset,402300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almOverRange.FaultInAlarm,402300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almOverRange.ALRM,402300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almOverRange.ANUN,402300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almOverRange.AKED,402300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almOverRange.Resetable,402300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almOverRange.REST,402300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almOverRange.ACKN,402300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almOverRange.UACK,402300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almOverRange.MCmd_Enable,402300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almOverRange.MCmd_Disable,402300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almOverRange.OCmd_Shelve,402300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almOverRange.OCmd_Unshelve,402300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almOverRange.SCmd_Suppress,402300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almOverRange.SCmd_UnSuppress,402301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almOverRange.AEShelveTMRDN,402301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almOverRange.Bad,402301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almOverRange.Suppress,402302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.UnSuppress,402302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Shelve,402302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.UnShelve,402302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Enable,402302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Disable,402302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Ack,402302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Reset,402302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almOverRange.Suppressed,402302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almOverRange.Shelved,402302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almOverRange.Disabled,402302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almOverRange.Acked,402302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almOverRange.Alarm,402302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Fault,402312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almUnderRange.AlarmState,402312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almUnderRange.GlobalReset,402312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almUnderRange.FaultInAlarm,402312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almUnderRange.ALRM,402312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almUnderRange.ANUN,402312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almUnderRange.AKED,402312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almUnderRange.Resetable,402312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almUnderRange.REST,402312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almUnderRange.ACKN,402312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almUnderRange.UACK,402312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almUnderRange.MCmd_Enable,402312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almUnderRange.MCmd_Disable,402312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almUnderRange.OCmd_Shelve,402312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almUnderRange.OCmd_Unshelve,402312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almUnderRange.SCmd_Suppress,402312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almUnderRange.SCmd_UnSuppress,402313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almUnderRange.AEShelveTMRDN,402313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almUnderRange.Bad,402313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almUnderRange.Suppress,402314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.UnSuppress,402314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Shelve,402314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.UnShelve,402314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Enable,402314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Disable,402314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Ack,402314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Reset,402314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Suppressed,402314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Shelved,402314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Disabled,402314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Acked,402314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almUnderRange.Alarm,402314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Fault,402324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almRateOfChange.AlarmState,402324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almRateOfChange.GlobalReset,402324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almRateOfChange.FaultInAlarm,402324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almRateOfChange.ALRM,402324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almRateOfChange.ANUN,402324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almRateOfChange.AKED,402324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almRateOfChange.Resetable,402324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almRateOfChange.REST,402324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almRateOfChange.ACKN,402324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almRateOfChange.UACK,402324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almRateOfChange.MCmd_Enable,402324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.MCmd_Disable,402324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.OCmd_Shelve,402324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.OCmd_Unshelve,402324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.SCmd_Suppress,402324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.SCmd_UnSuppress,402325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almRateOfChange.AEShelveTMRDN,402325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almRateOfChange.Bad,402325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almRateOfChange.Suppress,402326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.UnSuppress,402326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Shelve,402326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.UnShelve,402326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Enable,402326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Disable,402326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Ack,402326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Reset,402326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Suppressed,402326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Shelved,402326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Disabled,402326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Acked,402326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almRateOfChange.Alarm,402326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Fault,402336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_SI.almPLCFault.AlarmState,402336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_SI.almPLCFault.GlobalReset,402336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_SI.almPLCFault.FaultInAlarm,402336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_SI.almPLCFault.ALRM,402336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_SI.almPLCFault.ANUN,402336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_SI.almPLCFault.AKED,402336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_SI.almPLCFault.Resetable,402336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_SI.almPLCFault.REST,402336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_SI.almPLCFault.ACKN,402336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_SI.almPLCFault.UACK,402336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_SI.almPLCFault.MCmd_Enable,402336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_SI.almPLCFault.MCmd_Disable,402336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_SI.almPLCFault.OCmd_Shelve,402336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_SI.almPLCFault.OCmd_Unshelve,402336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_SI.almPLCFault.SCmd_Suppress,402336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_SI.almPLCFault.SCmd_UnSuppress,402337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_SI.almPLCFault.AEShelveTMRDN,402337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_SI.almPLCFault.Bad,402337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_SI.almPLCFault.Suppress,402338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.UnSuppress,402338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Shelve,402338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.UnShelve,402338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Enable,402338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Disable,402338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Ack,402338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Reset,402338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Suppressed,402338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Shelved,402338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Disabled,402338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Acked,402338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_SI.almPLCFault.Alarm,402338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Fault,402440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almHighHigh.AlarmState,402440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almHighHigh.GlobalReset,402440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almHighHigh.FaultInAlarm,402440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almHighHigh.ALRM,402440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almHighHigh.ANUN,402440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almHighHigh.AKED,402440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almHighHigh.Resetable,402440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almHighHigh.REST,402440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almHighHigh.ACKN,402440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almHighHigh.UACK,402440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almHighHigh.MCmd_Enable,402440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almHighHigh.MCmd_Disable,402440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almHighHigh.OCmd_Shelve,402440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almHighHigh.OCmd_Unshelve,402440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almHighHigh.SCmd_Suppress,402440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almHighHigh.SCmd_UnSuppress,402441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almHighHigh.AEShelveTMRDN,402441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almHighHigh.Bad,402441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almHighHigh.Suppress,402442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.UnSuppress,402442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Shelve,402442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.UnShelve,402442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Enable,402442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Disable,402442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Ack,402442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Reset,402442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Suppressed,402442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Shelved,402442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Disabled,402442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Acked,402442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almHighHigh.Alarm,402442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Fault,402452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almHigh.AlarmState,402452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almHigh.GlobalReset,402452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almHigh.FaultInAlarm,402452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almHigh.ALRM,402452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almHigh.ANUN,402452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almHigh.AKED,402452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almHigh.Resetable,402452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almHigh.REST,402452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almHigh.ACKN,402452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almHigh.UACK,402452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almHigh.MCmd_Enable,402452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almHigh.MCmd_Disable,402452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almHigh.OCmd_Shelve,402452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almHigh.OCmd_Unshelve,402452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almHigh.SCmd_Suppress,402452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almHigh.SCmd_UnSuppress,402453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almHigh.AEShelveTMRDN,402453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almHigh.Bad,402453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almHigh.Suppress,402454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.UnSuppress,402454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Shelve,402454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.UnShelve,402454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Enable,402454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Disable,402454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Ack,402454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Reset,402454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almHigh.Suppressed,402454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almHigh.Shelved,402454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almHigh.Disabled,402454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almHigh.Acked,402454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almHigh.Alarm,402454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Fault,402464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almLow.AlarmState,402464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almLow.GlobalReset,402464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almLow.FaultInAlarm,402464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almLow.ALRM,402464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almLow.ANUN,402464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almLow.AKED,402464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almLow.Resetable,402464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almLow.REST,402464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almLow.ACKN,402464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almLow.UACK,402464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almLow.MCmd_Enable,402464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almLow.MCmd_Disable,402464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almLow.OCmd_Shelve,402464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almLow.OCmd_Unshelve,402464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almLow.SCmd_Suppress,402464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almLow.SCmd_UnSuppress,402465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almLow.AEShelveTMRDN,402465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almLow.Bad,402465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almLow.Suppress,402466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.UnSuppress,402466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Shelve,402466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.UnShelve,402466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Enable,402466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Disable,402466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Ack,402466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Reset,402466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almLow.Suppressed,402466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almLow.Shelved,402466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almLow.Disabled,402466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almLow.Acked,402466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almLow.Alarm,402466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Fault,402476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almLowLow.AlarmState,402476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almLowLow.GlobalReset,402476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almLowLow.FaultInAlarm,402476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almLowLow.ALRM,402476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almLowLow.ANUN,402476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almLowLow.AKED,402476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almLowLow.Resetable,402476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almLowLow.REST,402476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almLowLow.ACKN,402476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almLowLow.UACK,402476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almLowLow.MCmd_Enable,402476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almLowLow.MCmd_Disable,402476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almLowLow.OCmd_Shelve,402476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almLowLow.OCmd_Unshelve,402476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almLowLow.SCmd_Suppress,402476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almLowLow.SCmd_UnSuppress,402477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almLowLow.AEShelveTMRDN,402477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almLowLow.Bad,402477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almLowLow.Suppress,402478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.UnSuppress,402478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Shelve,402478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.UnShelve,402478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Enable,402478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Disable,402478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Ack,402478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Reset,402478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almLowLow.Suppressed,402478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almLowLow.Shelved,402478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almLowLow.Disabled,402478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almLowLow.Acked,402478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almLowLow.Alarm,402478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Fault,402488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almBrokenLoop.AlarmState,402488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almBrokenLoop.GlobalReset,402488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almBrokenLoop.FaultInAlarm,402488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almBrokenLoop.ALRM,402488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almBrokenLoop.ANUN,402488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almBrokenLoop.AKED,402488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almBrokenLoop.Resetable,402488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almBrokenLoop.REST,402488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almBrokenLoop.ACKN,402488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almBrokenLoop.UACK,402488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almBrokenLoop.MCmd_Enable,402488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.MCmd_Disable,402488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.OCmd_Shelve,402488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.OCmd_Unshelve,402488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.SCmd_Suppress,402488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.SCmd_UnSuppress,402489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almBrokenLoop.AEShelveTMRDN,402489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almBrokenLoop.Bad,402489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almBrokenLoop.Suppress,402490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.UnSuppress,402490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Shelve,402490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.UnShelve,402490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Enable,402490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Disable,402490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Ack,402490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Reset,402490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Suppressed,402490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Shelved,402490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Disabled,402490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Acked,402490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almBrokenLoop.Alarm,402490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Fault,402500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almOverRange.AlarmState,402500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almOverRange.GlobalReset,402500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almOverRange.FaultInAlarm,402500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almOverRange.ALRM,402500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almOverRange.ANUN,402500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almOverRange.AKED,402500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almOverRange.Resetable,402500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almOverRange.REST,402500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almOverRange.ACKN,402500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almOverRange.UACK,402500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almOverRange.MCmd_Enable,402500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almOverRange.MCmd_Disable,402500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almOverRange.OCmd_Shelve,402500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almOverRange.OCmd_Unshelve,402500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almOverRange.SCmd_Suppress,402500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almOverRange.SCmd_UnSuppress,402501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almOverRange.AEShelveTMRDN,402501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almOverRange.Bad,402501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almOverRange.Suppress,402502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.UnSuppress,402502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Shelve,402502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.UnShelve,402502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Enable,402502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Disable,402502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Ack,402502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Reset,402502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almOverRange.Suppressed,402502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almOverRange.Shelved,402502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almOverRange.Disabled,402502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almOverRange.Acked,402502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almOverRange.Alarm,402502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Fault,402512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almUnderRange.AlarmState,402512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almUnderRange.GlobalReset,402512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almUnderRange.FaultInAlarm,402512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almUnderRange.ALRM,402512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almUnderRange.ANUN,402512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almUnderRange.AKED,402512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almUnderRange.Resetable,402512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almUnderRange.REST,402512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almUnderRange.ACKN,402512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almUnderRange.UACK,402512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almUnderRange.MCmd_Enable,402512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almUnderRange.MCmd_Disable,402512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almUnderRange.OCmd_Shelve,402512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almUnderRange.OCmd_Unshelve,402512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almUnderRange.SCmd_Suppress,402512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almUnderRange.SCmd_UnSuppress,402513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almUnderRange.AEShelveTMRDN,402513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almUnderRange.Bad,402513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almUnderRange.Suppress,402514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.UnSuppress,402514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Shelve,402514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.UnShelve,402514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Enable,402514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Disable,402514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Ack,402514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Reset,402514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Suppressed,402514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Shelved,402514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Disabled,402514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Acked,402514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almUnderRange.Alarm,402514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Fault,402524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almRateOfChange.AlarmState,402524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almRateOfChange.GlobalReset,402524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almRateOfChange.FaultInAlarm,402524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almRateOfChange.ALRM,402524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almRateOfChange.ANUN,402524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almRateOfChange.AKED,402524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almRateOfChange.Resetable,402524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almRateOfChange.REST,402524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almRateOfChange.ACKN,402524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almRateOfChange.UACK,402524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almRateOfChange.MCmd_Enable,402524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.MCmd_Disable,402524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.OCmd_Shelve,402524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.OCmd_Unshelve,402524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.SCmd_Suppress,402524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.SCmd_UnSuppress,402525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almRateOfChange.AEShelveTMRDN,402525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almRateOfChange.Bad,402525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almRateOfChange.Suppress,402526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.UnSuppress,402526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Shelve,402526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.UnShelve,402526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Enable,402526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Disable,402526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Ack,402526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Reset,402526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Suppressed,402526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Shelved,402526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Disabled,402526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Acked,402526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almRateOfChange.Alarm,402526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Fault,402536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_SI.almPLCFault.AlarmState,402536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_SI.almPLCFault.GlobalReset,402536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_SI.almPLCFault.FaultInAlarm,402536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_SI.almPLCFault.ALRM,402536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_SI.almPLCFault.ANUN,402536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_SI.almPLCFault.AKED,402536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_SI.almPLCFault.Resetable,402536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_SI.almPLCFault.REST,402536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_SI.almPLCFault.ACKN,402536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_SI.almPLCFault.UACK,402536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_SI.almPLCFault.MCmd_Enable,402536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_SI.almPLCFault.MCmd_Disable,402536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_SI.almPLCFault.OCmd_Shelve,402536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_SI.almPLCFault.OCmd_Unshelve,402536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_SI.almPLCFault.SCmd_Suppress,402536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_SI.almPLCFault.SCmd_UnSuppress,402537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_SI.almPLCFault.AEShelveTMRDN,402537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_SI.almPLCFault.Bad,402537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_SI.almPLCFault.Suppress,402538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.UnSuppress,402538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Shelve,402538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.UnShelve,402538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Enable,402538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Disable,402538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Ack,402538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Reset,402538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Suppressed,402538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Shelved,402538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Disabled,402538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Acked,402538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_SI.almPLCFault.Alarm,402538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Fault,402640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almHighHigh.AlarmState,402640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almHighHigh.GlobalReset,402640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almHighHigh.FaultInAlarm,402640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almHighHigh.ALRM,402640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almHighHigh.ANUN,402640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almHighHigh.AKED,402640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almHighHigh.Resetable,402640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almHighHigh.REST,402640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almHighHigh.ACKN,402640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almHighHigh.UACK,402640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almHighHigh.MCmd_Enable,402640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almHighHigh.MCmd_Disable,402640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almHighHigh.OCmd_Shelve,402640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almHighHigh.OCmd_Unshelve,402640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almHighHigh.SCmd_Suppress,402640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almHighHigh.SCmd_UnSuppress,402641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almHighHigh.AEShelveTMRDN,402641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almHighHigh.Bad,402641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almHighHigh.Suppress,402642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.UnSuppress,402642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Shelve,402642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.UnShelve,402642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Enable,402642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Disable,402642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Ack,402642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Reset,402642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Suppressed,402642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Shelved,402642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Disabled,402642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Acked,402642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almHighHigh.Alarm,402642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Fault,402652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almHigh.AlarmState,402652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almHigh.GlobalReset,402652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almHigh.FaultInAlarm,402652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almHigh.ALRM,402652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almHigh.ANUN,402652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almHigh.AKED,402652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almHigh.Resetable,402652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almHigh.REST,402652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almHigh.ACKN,402652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almHigh.UACK,402652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almHigh.MCmd_Enable,402652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almHigh.MCmd_Disable,402652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almHigh.OCmd_Shelve,402652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almHigh.OCmd_Unshelve,402652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almHigh.SCmd_Suppress,402652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almHigh.SCmd_UnSuppress,402653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almHigh.AEShelveTMRDN,402653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almHigh.Bad,402653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almHigh.Suppress,402654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.UnSuppress,402654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Shelve,402654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.UnShelve,402654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Enable,402654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Disable,402654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Ack,402654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Reset,402654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almHigh.Suppressed,402654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almHigh.Shelved,402654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almHigh.Disabled,402654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almHigh.Acked,402654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almHigh.Alarm,402654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Fault,402664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almLow.AlarmState,402664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almLow.GlobalReset,402664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almLow.FaultInAlarm,402664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almLow.ALRM,402664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almLow.ANUN,402664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almLow.AKED,402664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almLow.Resetable,402664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almLow.REST,402664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almLow.ACKN,402664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almLow.UACK,402664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almLow.MCmd_Enable,402664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almLow.MCmd_Disable,402664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almLow.OCmd_Shelve,402664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almLow.OCmd_Unshelve,402664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almLow.SCmd_Suppress,402664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almLow.SCmd_UnSuppress,402665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almLow.AEShelveTMRDN,402665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almLow.Bad,402665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almLow.Suppress,402666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.UnSuppress,402666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Shelve,402666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.UnShelve,402666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Enable,402666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Disable,402666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Ack,402666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Reset,402666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almLow.Suppressed,402666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almLow.Shelved,402666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almLow.Disabled,402666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almLow.Acked,402666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almLow.Alarm,402666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Fault,402676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almLowLow.AlarmState,402676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almLowLow.GlobalReset,402676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almLowLow.FaultInAlarm,402676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almLowLow.ALRM,402676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almLowLow.ANUN,402676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almLowLow.AKED,402676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almLowLow.Resetable,402676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almLowLow.REST,402676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almLowLow.ACKN,402676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almLowLow.UACK,402676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almLowLow.MCmd_Enable,402676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almLowLow.MCmd_Disable,402676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almLowLow.OCmd_Shelve,402676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almLowLow.OCmd_Unshelve,402676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almLowLow.SCmd_Suppress,402676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almLowLow.SCmd_UnSuppress,402677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almLowLow.AEShelveTMRDN,402677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almLowLow.Bad,402677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almLowLow.Suppress,402678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.UnSuppress,402678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Shelve,402678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.UnShelve,402678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Enable,402678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Disable,402678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Ack,402678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Reset,402678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almLowLow.Suppressed,402678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almLowLow.Shelved,402678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almLowLow.Disabled,402678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almLowLow.Acked,402678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almLowLow.Alarm,402678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Fault,402688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almBrokenLoop.AlarmState,402688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almBrokenLoop.GlobalReset,402688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almBrokenLoop.FaultInAlarm,402688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almBrokenLoop.ALRM,402688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almBrokenLoop.ANUN,402688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almBrokenLoop.AKED,402688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almBrokenLoop.Resetable,402688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almBrokenLoop.REST,402688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almBrokenLoop.ACKN,402688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almBrokenLoop.UACK,402688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almBrokenLoop.MCmd_Enable,402688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.MCmd_Disable,402688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.OCmd_Shelve,402688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.OCmd_Unshelve,402688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.SCmd_Suppress,402688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.SCmd_UnSuppress,402689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almBrokenLoop.AEShelveTMRDN,402689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almBrokenLoop.Bad,402689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almBrokenLoop.Suppress,402690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.UnSuppress,402690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Shelve,402690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.UnShelve,402690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Enable,402690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Disable,402690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Ack,402690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Reset,402690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Suppressed,402690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Shelved,402690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Disabled,402690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Acked,402690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almBrokenLoop.Alarm,402690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Fault,402700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almOverRange.AlarmState,402700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almOverRange.GlobalReset,402700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almOverRange.FaultInAlarm,402700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almOverRange.ALRM,402700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almOverRange.ANUN,402700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almOverRange.AKED,402700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almOverRange.Resetable,402700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almOverRange.REST,402700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almOverRange.ACKN,402700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almOverRange.UACK,402700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almOverRange.MCmd_Enable,402700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almOverRange.MCmd_Disable,402700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almOverRange.OCmd_Shelve,402700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almOverRange.OCmd_Unshelve,402700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almOverRange.SCmd_Suppress,402700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almOverRange.SCmd_UnSuppress,402701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almOverRange.AEShelveTMRDN,402701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almOverRange.Bad,402701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almOverRange.Suppress,402702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.UnSuppress,402702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Shelve,402702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.UnShelve,402702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Enable,402702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Disable,402702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Ack,402702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Reset,402702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almOverRange.Suppressed,402702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almOverRange.Shelved,402702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almOverRange.Disabled,402702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almOverRange.Acked,402702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almOverRange.Alarm,402702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Fault,402712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almUnderRange.AlarmState,402712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almUnderRange.GlobalReset,402712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almUnderRange.FaultInAlarm,402712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almUnderRange.ALRM,402712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almUnderRange.ANUN,402712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almUnderRange.AKED,402712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almUnderRange.Resetable,402712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almUnderRange.REST,402712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almUnderRange.ACKN,402712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almUnderRange.UACK,402712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almUnderRange.MCmd_Enable,402712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almUnderRange.MCmd_Disable,402712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almUnderRange.OCmd_Shelve,402712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almUnderRange.OCmd_Unshelve,402712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almUnderRange.SCmd_Suppress,402712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almUnderRange.SCmd_UnSuppress,402713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almUnderRange.AEShelveTMRDN,402713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almUnderRange.Bad,402713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almUnderRange.Suppress,402714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.UnSuppress,402714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Shelve,402714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.UnShelve,402714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Enable,402714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Disable,402714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Ack,402714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Reset,402714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Suppressed,402714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Shelved,402714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Disabled,402714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Acked,402714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almUnderRange.Alarm,402714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Fault,402724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almRateOfChange.AlarmState,402724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almRateOfChange.GlobalReset,402724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almRateOfChange.FaultInAlarm,402724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almRateOfChange.ALRM,402724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almRateOfChange.ANUN,402724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almRateOfChange.AKED,402724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almRateOfChange.Resetable,402724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almRateOfChange.REST,402724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almRateOfChange.ACKN,402724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almRateOfChange.UACK,402724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almRateOfChange.MCmd_Enable,402724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.MCmd_Disable,402724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.OCmd_Shelve,402724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.OCmd_Unshelve,402724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.SCmd_Suppress,402724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.SCmd_UnSuppress,402725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almRateOfChange.AEShelveTMRDN,402725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almRateOfChange.Bad,402725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almRateOfChange.Suppress,402726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.UnSuppress,402726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Shelve,402726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.UnShelve,402726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Enable,402726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Disable,402726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Ack,402726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Reset,402726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Suppressed,402726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Shelved,402726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Disabled,402726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Acked,402726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almRateOfChange.Alarm,402726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Fault,402736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_SI.almPLCFault.AlarmState,402736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_SI.almPLCFault.GlobalReset,402736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_SI.almPLCFault.FaultInAlarm,402736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_SI.almPLCFault.ALRM,402736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_SI.almPLCFault.ANUN,402736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_SI.almPLCFault.AKED,402736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_SI.almPLCFault.Resetable,402736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_SI.almPLCFault.REST,402736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_SI.almPLCFault.ACKN,402736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_SI.almPLCFault.UACK,402736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_SI.almPLCFault.MCmd_Enable,402736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_SI.almPLCFault.MCmd_Disable,402736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_SI.almPLCFault.OCmd_Shelve,402736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_SI.almPLCFault.OCmd_Unshelve,402736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_SI.almPLCFault.SCmd_Suppress,402736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_SI.almPLCFault.SCmd_UnSuppress,402737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_SI.almPLCFault.AEShelveTMRDN,402737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_SI.almPLCFault.Bad,402737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_SI.almPLCFault.Suppress,402738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.UnSuppress,402738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Shelve,402738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.UnShelve,402738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Enable,402738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Disable,402738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Ack,402738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Reset,402738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Suppressed,402738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Shelved,402738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Disabled,402738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Acked,402738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_SI.almPLCFault.Alarm,402738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Fault,402840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almHighHigh.AlarmState,402840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almHighHigh.GlobalReset,402840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almHighHigh.FaultInAlarm,402840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almHighHigh.ALRM,402840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almHighHigh.ANUN,402840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almHighHigh.AKED,402840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almHighHigh.Resetable,402840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almHighHigh.REST,402840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almHighHigh.ACKN,402840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almHighHigh.UACK,402840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almHighHigh.MCmd_Enable,402840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almHighHigh.MCmd_Disable,402840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almHighHigh.OCmd_Shelve,402840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almHighHigh.OCmd_Unshelve,402840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almHighHigh.SCmd_Suppress,402840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almHighHigh.SCmd_UnSuppress,402841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almHighHigh.AEShelveTMRDN,402841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almHighHigh.Bad,402841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almHighHigh.Suppress,402842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.UnSuppress,402842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Shelve,402842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.UnShelve,402842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Enable,402842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Disable,402842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Ack,402842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Reset,402842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Suppressed,402842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Shelved,402842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Disabled,402842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Acked,402842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almHighHigh.Alarm,402842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Fault,402852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almHigh.AlarmState,402852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almHigh.GlobalReset,402852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almHigh.FaultInAlarm,402852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almHigh.ALRM,402852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almHigh.ANUN,402852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almHigh.AKED,402852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almHigh.Resetable,402852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almHigh.REST,402852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almHigh.ACKN,402852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almHigh.UACK,402852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almHigh.MCmd_Enable,402852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almHigh.MCmd_Disable,402852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almHigh.OCmd_Shelve,402852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almHigh.OCmd_Unshelve,402852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almHigh.SCmd_Suppress,402852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almHigh.SCmd_UnSuppress,402853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almHigh.AEShelveTMRDN,402853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almHigh.Bad,402853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almHigh.Suppress,402854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.UnSuppress,402854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Shelve,402854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.UnShelve,402854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Enable,402854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Disable,402854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Ack,402854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Reset,402854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almHigh.Suppressed,402854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almHigh.Shelved,402854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almHigh.Disabled,402854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almHigh.Acked,402854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almHigh.Alarm,402854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Fault,402864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almLow.AlarmState,402864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almLow.GlobalReset,402864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almLow.FaultInAlarm,402864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almLow.ALRM,402864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almLow.ANUN,402864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almLow.AKED,402864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almLow.Resetable,402864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almLow.REST,402864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almLow.ACKN,402864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almLow.UACK,402864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almLow.MCmd_Enable,402864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almLow.MCmd_Disable,402864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almLow.OCmd_Shelve,402864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almLow.OCmd_Unshelve,402864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almLow.SCmd_Suppress,402864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almLow.SCmd_UnSuppress,402865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almLow.AEShelveTMRDN,402865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almLow.Bad,402865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almLow.Suppress,402866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.UnSuppress,402866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Shelve,402866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.UnShelve,402866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Enable,402866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Disable,402866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Ack,402866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Reset,402866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almLow.Suppressed,402866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almLow.Shelved,402866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almLow.Disabled,402866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almLow.Acked,402866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almLow.Alarm,402866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Fault,402876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almLowLow.AlarmState,402876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almLowLow.GlobalReset,402876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almLowLow.FaultInAlarm,402876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almLowLow.ALRM,402876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almLowLow.ANUN,402876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almLowLow.AKED,402876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almLowLow.Resetable,402876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almLowLow.REST,402876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almLowLow.ACKN,402876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almLowLow.UACK,402876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almLowLow.MCmd_Enable,402876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almLowLow.MCmd_Disable,402876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almLowLow.OCmd_Shelve,402876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almLowLow.OCmd_Unshelve,402876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almLowLow.SCmd_Suppress,402876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almLowLow.SCmd_UnSuppress,402877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almLowLow.AEShelveTMRDN,402877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almLowLow.Bad,402877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almLowLow.Suppress,402878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.UnSuppress,402878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Shelve,402878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.UnShelve,402878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Enable,402878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Disable,402878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Ack,402878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Reset,402878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almLowLow.Suppressed,402878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almLowLow.Shelved,402878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almLowLow.Disabled,402878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almLowLow.Acked,402878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almLowLow.Alarm,402878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Fault,402888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almBrokenLoop.AlarmState,402888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almBrokenLoop.GlobalReset,402888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almBrokenLoop.FaultInAlarm,402888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almBrokenLoop.ALRM,402888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almBrokenLoop.ANUN,402888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almBrokenLoop.AKED,402888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almBrokenLoop.Resetable,402888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almBrokenLoop.REST,402888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almBrokenLoop.ACKN,402888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almBrokenLoop.UACK,402888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almBrokenLoop.MCmd_Enable,402888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.MCmd_Disable,402888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.OCmd_Shelve,402888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.OCmd_Unshelve,402888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.SCmd_Suppress,402888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.SCmd_UnSuppress,402889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almBrokenLoop.AEShelveTMRDN,402889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almBrokenLoop.Bad,402889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almBrokenLoop.Suppress,402890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.UnSuppress,402890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Shelve,402890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.UnShelve,402890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Enable,402890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Disable,402890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Ack,402890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Reset,402890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Suppressed,402890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Shelved,402890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Disabled,402890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Acked,402890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almBrokenLoop.Alarm,402890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Fault,402900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almOverRange.AlarmState,402900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almOverRange.GlobalReset,402900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almOverRange.FaultInAlarm,402900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almOverRange.ALRM,402900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almOverRange.ANUN,402900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almOverRange.AKED,402900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almOverRange.Resetable,402900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almOverRange.REST,402900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almOverRange.ACKN,402900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almOverRange.UACK,402900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almOverRange.MCmd_Enable,402900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almOverRange.MCmd_Disable,402900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almOverRange.OCmd_Shelve,402900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almOverRange.OCmd_Unshelve,402900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almOverRange.SCmd_Suppress,402900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almOverRange.SCmd_UnSuppress,402901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almOverRange.AEShelveTMRDN,402901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almOverRange.Bad,402901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almOverRange.Suppress,402902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.UnSuppress,402902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Shelve,402902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.UnShelve,402902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Enable,402902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Disable,402902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Ack,402902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Reset,402902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almOverRange.Suppressed,402902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almOverRange.Shelved,402902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almOverRange.Disabled,402902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almOverRange.Acked,402902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almOverRange.Alarm,402902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Fault,402912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almUnderRange.AlarmState,402912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almUnderRange.GlobalReset,402912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almUnderRange.FaultInAlarm,402912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almUnderRange.ALRM,402912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almUnderRange.ANUN,402912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almUnderRange.AKED,402912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almUnderRange.Resetable,402912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almUnderRange.REST,402912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almUnderRange.ACKN,402912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almUnderRange.UACK,402912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almUnderRange.MCmd_Enable,402912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almUnderRange.MCmd_Disable,402912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almUnderRange.OCmd_Shelve,402912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almUnderRange.OCmd_Unshelve,402912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almUnderRange.SCmd_Suppress,402912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almUnderRange.SCmd_UnSuppress,402913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almUnderRange.AEShelveTMRDN,402913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almUnderRange.Bad,402913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almUnderRange.Suppress,402914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.UnSuppress,402914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Shelve,402914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.UnShelve,402914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Enable,402914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Disable,402914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Ack,402914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Reset,402914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Suppressed,402914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Shelved,402914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Disabled,402914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Acked,402914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almUnderRange.Alarm,402914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Fault,402924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almRateOfChange.AlarmState,402924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almRateOfChange.GlobalReset,402924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almRateOfChange.FaultInAlarm,402924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almRateOfChange.ALRM,402924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almRateOfChange.ANUN,402924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almRateOfChange.AKED,402924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almRateOfChange.Resetable,402924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almRateOfChange.REST,402924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almRateOfChange.ACKN,402924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almRateOfChange.UACK,402924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almRateOfChange.MCmd_Enable,402924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.MCmd_Disable,402924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.OCmd_Shelve,402924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.OCmd_Unshelve,402924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.SCmd_Suppress,402924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.SCmd_UnSuppress,402925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almRateOfChange.AEShelveTMRDN,402925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almRateOfChange.Bad,402925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almRateOfChange.Suppress,402926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.UnSuppress,402926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Shelve,402926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.UnShelve,402926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Enable,402926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Disable,402926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Ack,402926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Reset,402926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Suppressed,402926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Shelved,402926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Disabled,402926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Acked,402926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almRateOfChange.Alarm,402926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Fault,402936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI1.almPLCFault.AlarmState,402936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI1.almPLCFault.GlobalReset,402936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI1.almPLCFault.FaultInAlarm,402936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI1.almPLCFault.ALRM,402936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI1.almPLCFault.ANUN,402936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI1.almPLCFault.AKED,402936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI1.almPLCFault.Resetable,402936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI1.almPLCFault.REST,402936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI1.almPLCFault.ACKN,402936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI1.almPLCFault.UACK,402936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI1.almPLCFault.MCmd_Enable,402936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI1.almPLCFault.MCmd_Disable,402936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI1.almPLCFault.OCmd_Shelve,402936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI1.almPLCFault.OCmd_Unshelve,402936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI1.almPLCFault.SCmd_Suppress,402936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI1.almPLCFault.SCmd_UnSuppress,402937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI1.almPLCFault.AEShelveTMRDN,402937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI1.almPLCFault.Bad,402937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI1.almPLCFault.Suppress,402938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.UnSuppress,402938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Shelve,402938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.UnShelve,402938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Enable,402938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Disable,402938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Ack,402938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Reset,402938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Suppressed,402938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Shelved,402938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Disabled,402938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Acked,402938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI1.almPLCFault.Alarm,402938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Fault,403040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almHighHigh.AlarmState,403040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almHighHigh.GlobalReset,403040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almHighHigh.FaultInAlarm,403040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almHighHigh.ALRM,403040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almHighHigh.ANUN,403040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almHighHigh.AKED,403040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almHighHigh.Resetable,403040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almHighHigh.REST,403040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almHighHigh.ACKN,403040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almHighHigh.UACK,403040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almHighHigh.MCmd_Enable,403040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almHighHigh.MCmd_Disable,403040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almHighHigh.OCmd_Shelve,403040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almHighHigh.OCmd_Unshelve,403040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almHighHigh.SCmd_Suppress,403040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almHighHigh.SCmd_UnSuppress,403041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almHighHigh.AEShelveTMRDN,403041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almHighHigh.Bad,403041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almHighHigh.Suppress,403042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.UnSuppress,403042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Shelve,403042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.UnShelve,403042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Enable,403042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Disable,403042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Ack,403042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Reset,403042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Suppressed,403042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Shelved,403042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Disabled,403042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Acked,403042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almHighHigh.Alarm,403042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Fault,403052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almHigh.AlarmState,403052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almHigh.GlobalReset,403052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almHigh.FaultInAlarm,403052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almHigh.ALRM,403052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almHigh.ANUN,403052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almHigh.AKED,403052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almHigh.Resetable,403052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almHigh.REST,403052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almHigh.ACKN,403052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almHigh.UACK,403052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almHigh.MCmd_Enable,403052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almHigh.MCmd_Disable,403052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almHigh.OCmd_Shelve,403052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almHigh.OCmd_Unshelve,403052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almHigh.SCmd_Suppress,403052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almHigh.SCmd_UnSuppress,403053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almHigh.AEShelveTMRDN,403053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almHigh.Bad,403053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almHigh.Suppress,403054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.UnSuppress,403054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Shelve,403054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.UnShelve,403054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Enable,403054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Disable,403054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Ack,403054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Reset,403054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almHigh.Suppressed,403054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almHigh.Shelved,403054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almHigh.Disabled,403054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almHigh.Acked,403054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almHigh.Alarm,403054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Fault,403064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almLow.AlarmState,403064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almLow.GlobalReset,403064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almLow.FaultInAlarm,403064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almLow.ALRM,403064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almLow.ANUN,403064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almLow.AKED,403064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almLow.Resetable,403064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almLow.REST,403064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almLow.ACKN,403064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almLow.UACK,403064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almLow.MCmd_Enable,403064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almLow.MCmd_Disable,403064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almLow.OCmd_Shelve,403064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almLow.OCmd_Unshelve,403064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almLow.SCmd_Suppress,403064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almLow.SCmd_UnSuppress,403065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almLow.AEShelveTMRDN,403065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almLow.Bad,403065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almLow.Suppress,403066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.UnSuppress,403066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Shelve,403066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.UnShelve,403066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Enable,403066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Disable,403066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Ack,403066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Reset,403066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almLow.Suppressed,403066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almLow.Shelved,403066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almLow.Disabled,403066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almLow.Acked,403066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almLow.Alarm,403066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Fault,403076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almLowLow.AlarmState,403076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almLowLow.GlobalReset,403076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almLowLow.FaultInAlarm,403076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almLowLow.ALRM,403076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almLowLow.ANUN,403076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almLowLow.AKED,403076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almLowLow.Resetable,403076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almLowLow.REST,403076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almLowLow.ACKN,403076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almLowLow.UACK,403076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almLowLow.MCmd_Enable,403076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almLowLow.MCmd_Disable,403076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almLowLow.OCmd_Shelve,403076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almLowLow.OCmd_Unshelve,403076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almLowLow.SCmd_Suppress,403076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almLowLow.SCmd_UnSuppress,403077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almLowLow.AEShelveTMRDN,403077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almLowLow.Bad,403077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almLowLow.Suppress,403078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.UnSuppress,403078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Shelve,403078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.UnShelve,403078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Enable,403078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Disable,403078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Ack,403078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Reset,403078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almLowLow.Suppressed,403078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almLowLow.Shelved,403078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almLowLow.Disabled,403078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almLowLow.Acked,403078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almLowLow.Alarm,403078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Fault,403088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almBrokenLoop.AlarmState,403088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almBrokenLoop.GlobalReset,403088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almBrokenLoop.FaultInAlarm,403088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almBrokenLoop.ALRM,403088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almBrokenLoop.ANUN,403088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almBrokenLoop.AKED,403088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almBrokenLoop.Resetable,403088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almBrokenLoop.REST,403088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almBrokenLoop.ACKN,403088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almBrokenLoop.UACK,403088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almBrokenLoop.MCmd_Enable,403088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.MCmd_Disable,403088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.OCmd_Shelve,403088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.OCmd_Unshelve,403088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.SCmd_Suppress,403088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.SCmd_UnSuppress,403089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almBrokenLoop.AEShelveTMRDN,403089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almBrokenLoop.Bad,403089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almBrokenLoop.Suppress,403090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.UnSuppress,403090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Shelve,403090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.UnShelve,403090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Enable,403090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Disable,403090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Ack,403090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Reset,403090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Suppressed,403090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Shelved,403090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Disabled,403090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Acked,403090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almBrokenLoop.Alarm,403090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Fault,403100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almOverRange.AlarmState,403100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almOverRange.GlobalReset,403100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almOverRange.FaultInAlarm,403100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almOverRange.ALRM,403100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almOverRange.ANUN,403100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almOverRange.AKED,403100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almOverRange.Resetable,403100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almOverRange.REST,403100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almOverRange.ACKN,403100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almOverRange.UACK,403100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almOverRange.MCmd_Enable,403100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almOverRange.MCmd_Disable,403100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almOverRange.OCmd_Shelve,403100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almOverRange.OCmd_Unshelve,403100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almOverRange.SCmd_Suppress,403100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almOverRange.SCmd_UnSuppress,403101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almOverRange.AEShelveTMRDN,403101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almOverRange.Bad,403101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almOverRange.Suppress,403102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.UnSuppress,403102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Shelve,403102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.UnShelve,403102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Enable,403102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Disable,403102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Ack,403102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Reset,403102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almOverRange.Suppressed,403102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almOverRange.Shelved,403102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almOverRange.Disabled,403102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almOverRange.Acked,403102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almOverRange.Alarm,403102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Fault,403112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almUnderRange.AlarmState,403112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almUnderRange.GlobalReset,403112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almUnderRange.FaultInAlarm,403112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almUnderRange.ALRM,403112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almUnderRange.ANUN,403112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almUnderRange.AKED,403112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almUnderRange.Resetable,403112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almUnderRange.REST,403112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almUnderRange.ACKN,403112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almUnderRange.UACK,403112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almUnderRange.MCmd_Enable,403112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almUnderRange.MCmd_Disable,403112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almUnderRange.OCmd_Shelve,403112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almUnderRange.OCmd_Unshelve,403112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almUnderRange.SCmd_Suppress,403112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almUnderRange.SCmd_UnSuppress,403113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almUnderRange.AEShelveTMRDN,403113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almUnderRange.Bad,403113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almUnderRange.Suppress,403114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.UnSuppress,403114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Shelve,403114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.UnShelve,403114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Enable,403114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Disable,403114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Ack,403114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Reset,403114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Suppressed,403114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Shelved,403114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Disabled,403114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Acked,403114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almUnderRange.Alarm,403114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Fault,403124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almRateOfChange.AlarmState,403124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almRateOfChange.GlobalReset,403124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almRateOfChange.FaultInAlarm,403124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almRateOfChange.ALRM,403124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almRateOfChange.ANUN,403124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almRateOfChange.AKED,403124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almRateOfChange.Resetable,403124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almRateOfChange.REST,403124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almRateOfChange.ACKN,403124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almRateOfChange.UACK,403124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almRateOfChange.MCmd_Enable,403124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.MCmd_Disable,403124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.OCmd_Shelve,403124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.OCmd_Unshelve,403124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.SCmd_Suppress,403124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.SCmd_UnSuppress,403125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almRateOfChange.AEShelveTMRDN,403125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almRateOfChange.Bad,403125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almRateOfChange.Suppress,403126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.UnSuppress,403126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Shelve,403126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.UnShelve,403126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Enable,403126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Disable,403126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Ack,403126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Reset,403126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Suppressed,403126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Shelved,403126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Disabled,403126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Acked,403126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almRateOfChange.Alarm,403126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Fault,403136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI2.almPLCFault.AlarmState,403136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI2.almPLCFault.GlobalReset,403136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI2.almPLCFault.FaultInAlarm,403136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI2.almPLCFault.ALRM,403136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI2.almPLCFault.ANUN,403136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI2.almPLCFault.AKED,403136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI2.almPLCFault.Resetable,403136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI2.almPLCFault.REST,403136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI2.almPLCFault.ACKN,403136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI2.almPLCFault.UACK,403136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI2.almPLCFault.MCmd_Enable,403136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI2.almPLCFault.MCmd_Disable,403136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI2.almPLCFault.OCmd_Shelve,403136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI2.almPLCFault.OCmd_Unshelve,403136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI2.almPLCFault.SCmd_Suppress,403136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI2.almPLCFault.SCmd_UnSuppress,403137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI2.almPLCFault.AEShelveTMRDN,403137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI2.almPLCFault.Bad,403137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI2.almPLCFault.Suppress,403138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.UnSuppress,403138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Shelve,403138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.UnShelve,403138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Enable,403138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Disable,403138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Ack,403138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Reset,403138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Suppressed,403138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Shelved,403138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Disabled,403138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Acked,403138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI2.almPLCFault.Alarm,403138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Fault,403240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almHighHigh.AlarmState,403240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almHighHigh.GlobalReset,403240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almHighHigh.FaultInAlarm,403240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almHighHigh.ALRM,403240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almHighHigh.ANUN,403240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almHighHigh.AKED,403240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almHighHigh.Resetable,403240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almHighHigh.REST,403240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almHighHigh.ACKN,403240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almHighHigh.UACK,403240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almHighHigh.MCmd_Enable,403240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almHighHigh.MCmd_Disable,403240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almHighHigh.OCmd_Shelve,403240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almHighHigh.OCmd_Unshelve,403240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almHighHigh.SCmd_Suppress,403240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almHighHigh.SCmd_UnSuppress,403241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almHighHigh.AEShelveTMRDN,403241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almHighHigh.Bad,403241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almHighHigh.Suppress,403242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.UnSuppress,403242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Shelve,403242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.UnShelve,403242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Enable,403242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Disable,403242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Ack,403242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Reset,403242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Suppressed,403242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Shelved,403242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Disabled,403242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Acked,403242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almHighHigh.Alarm,403242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Fault,403252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almHigh.AlarmState,403252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almHigh.GlobalReset,403252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almHigh.FaultInAlarm,403252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almHigh.ALRM,403252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almHigh.ANUN,403252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almHigh.AKED,403252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almHigh.Resetable,403252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almHigh.REST,403252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almHigh.ACKN,403252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almHigh.UACK,403252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almHigh.MCmd_Enable,403252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almHigh.MCmd_Disable,403252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almHigh.OCmd_Shelve,403252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almHigh.OCmd_Unshelve,403252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almHigh.SCmd_Suppress,403252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almHigh.SCmd_UnSuppress,403253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almHigh.AEShelveTMRDN,403253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almHigh.Bad,403253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almHigh.Suppress,403254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.UnSuppress,403254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Shelve,403254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.UnShelve,403254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Enable,403254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Disable,403254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Ack,403254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Reset,403254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almHigh.Suppressed,403254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almHigh.Shelved,403254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almHigh.Disabled,403254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almHigh.Acked,403254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almHigh.Alarm,403254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Fault,403264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almLow.AlarmState,403264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almLow.GlobalReset,403264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almLow.FaultInAlarm,403264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almLow.ALRM,403264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almLow.ANUN,403264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almLow.AKED,403264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almLow.Resetable,403264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almLow.REST,403264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almLow.ACKN,403264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almLow.UACK,403264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almLow.MCmd_Enable,403264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almLow.MCmd_Disable,403264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almLow.OCmd_Shelve,403264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almLow.OCmd_Unshelve,403264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almLow.SCmd_Suppress,403264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almLow.SCmd_UnSuppress,403265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almLow.AEShelveTMRDN,403265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almLow.Bad,403265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almLow.Suppress,403266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.UnSuppress,403266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Shelve,403266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.UnShelve,403266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Enable,403266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Disable,403266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Ack,403266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Reset,403266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almLow.Suppressed,403266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almLow.Shelved,403266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almLow.Disabled,403266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almLow.Acked,403266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almLow.Alarm,403266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Fault,403276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almLowLow.AlarmState,403276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almLowLow.GlobalReset,403276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almLowLow.FaultInAlarm,403276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almLowLow.ALRM,403276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almLowLow.ANUN,403276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almLowLow.AKED,403276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almLowLow.Resetable,403276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almLowLow.REST,403276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almLowLow.ACKN,403276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almLowLow.UACK,403276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almLowLow.MCmd_Enable,403276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almLowLow.MCmd_Disable,403276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almLowLow.OCmd_Shelve,403276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almLowLow.OCmd_Unshelve,403276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almLowLow.SCmd_Suppress,403276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almLowLow.SCmd_UnSuppress,403277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almLowLow.AEShelveTMRDN,403277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almLowLow.Bad,403277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almLowLow.Suppress,403278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.UnSuppress,403278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Shelve,403278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.UnShelve,403278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Enable,403278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Disable,403278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Ack,403278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Reset,403278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almLowLow.Suppressed,403278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almLowLow.Shelved,403278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almLowLow.Disabled,403278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almLowLow.Acked,403278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almLowLow.Alarm,403278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Fault,403288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almBrokenLoop.AlarmState,403288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almBrokenLoop.GlobalReset,403288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almBrokenLoop.FaultInAlarm,403288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almBrokenLoop.ALRM,403288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almBrokenLoop.ANUN,403288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almBrokenLoop.AKED,403288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almBrokenLoop.Resetable,403288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almBrokenLoop.REST,403288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almBrokenLoop.ACKN,403288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almBrokenLoop.UACK,403288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almBrokenLoop.MCmd_Enable,403288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.MCmd_Disable,403288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.OCmd_Shelve,403288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.OCmd_Unshelve,403288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.SCmd_Suppress,403288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.SCmd_UnSuppress,403289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almBrokenLoop.AEShelveTMRDN,403289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almBrokenLoop.Bad,403289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almBrokenLoop.Suppress,403290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.UnSuppress,403290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Shelve,403290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.UnShelve,403290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Enable,403290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Disable,403290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Ack,403290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Reset,403290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Suppressed,403290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Shelved,403290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Disabled,403290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Acked,403290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almBrokenLoop.Alarm,403290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Fault,403300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almOverRange.AlarmState,403300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almOverRange.GlobalReset,403300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almOverRange.FaultInAlarm,403300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almOverRange.ALRM,403300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almOverRange.ANUN,403300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almOverRange.AKED,403300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almOverRange.Resetable,403300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almOverRange.REST,403300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almOverRange.ACKN,403300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almOverRange.UACK,403300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almOverRange.MCmd_Enable,403300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almOverRange.MCmd_Disable,403300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almOverRange.OCmd_Shelve,403300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almOverRange.OCmd_Unshelve,403300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almOverRange.SCmd_Suppress,403300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almOverRange.SCmd_UnSuppress,403301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almOverRange.AEShelveTMRDN,403301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almOverRange.Bad,403301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almOverRange.Suppress,403302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.UnSuppress,403302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Shelve,403302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.UnShelve,403302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Enable,403302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Disable,403302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Ack,403302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Reset,403302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almOverRange.Suppressed,403302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almOverRange.Shelved,403302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almOverRange.Disabled,403302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almOverRange.Acked,403302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almOverRange.Alarm,403302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Fault,403312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almUnderRange.AlarmState,403312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almUnderRange.GlobalReset,403312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almUnderRange.FaultInAlarm,403312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almUnderRange.ALRM,403312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almUnderRange.ANUN,403312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almUnderRange.AKED,403312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almUnderRange.Resetable,403312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almUnderRange.REST,403312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almUnderRange.ACKN,403312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almUnderRange.UACK,403312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almUnderRange.MCmd_Enable,403312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almUnderRange.MCmd_Disable,403312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almUnderRange.OCmd_Shelve,403312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almUnderRange.OCmd_Unshelve,403312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almUnderRange.SCmd_Suppress,403312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almUnderRange.SCmd_UnSuppress,403313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almUnderRange.AEShelveTMRDN,403313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almUnderRange.Bad,403313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almUnderRange.Suppress,403314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.UnSuppress,403314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Shelve,403314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.UnShelve,403314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Enable,403314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Disable,403314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Ack,403314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Reset,403314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Suppressed,403314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Shelved,403314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Disabled,403314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Acked,403314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almUnderRange.Alarm,403314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Fault,403324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almRateOfChange.AlarmState,403324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almRateOfChange.GlobalReset,403324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almRateOfChange.FaultInAlarm,403324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almRateOfChange.ALRM,403324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almRateOfChange.ANUN,403324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almRateOfChange.AKED,403324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almRateOfChange.Resetable,403324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almRateOfChange.REST,403324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almRateOfChange.ACKN,403324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almRateOfChange.UACK,403324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almRateOfChange.MCmd_Enable,403324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.MCmd_Disable,403324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.OCmd_Shelve,403324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.OCmd_Unshelve,403324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.SCmd_Suppress,403324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.SCmd_UnSuppress,403325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almRateOfChange.AEShelveTMRDN,403325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almRateOfChange.Bad,403325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almRateOfChange.Suppress,403326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.UnSuppress,403326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Shelve,403326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.UnShelve,403326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Enable,403326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Disable,403326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Ack,403326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Reset,403326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Suppressed,403326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Shelved,403326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Disabled,403326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Acked,403326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almRateOfChange.Alarm,403326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Fault,403336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI3.almPLCFault.AlarmState,403336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI3.almPLCFault.GlobalReset,403336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI3.almPLCFault.FaultInAlarm,403336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI3.almPLCFault.ALRM,403336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI3.almPLCFault.ANUN,403336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI3.almPLCFault.AKED,403336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI3.almPLCFault.Resetable,403336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI3.almPLCFault.REST,403336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI3.almPLCFault.ACKN,403336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI3.almPLCFault.UACK,403336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI3.almPLCFault.MCmd_Enable,403336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI3.almPLCFault.MCmd_Disable,403336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI3.almPLCFault.OCmd_Shelve,403336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI3.almPLCFault.OCmd_Unshelve,403336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI3.almPLCFault.SCmd_Suppress,403336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI3.almPLCFault.SCmd_UnSuppress,403337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI3.almPLCFault.AEShelveTMRDN,403337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI3.almPLCFault.Bad,403337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI3.almPLCFault.Suppress,403338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.UnSuppress,403338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Shelve,403338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.UnShelve,403338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Enable,403338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Disable,403338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Ack,403338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Reset,403338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Suppressed,403338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Shelved,403338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Disabled,403338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Acked,403338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI3.almPLCFault.Alarm,403338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Fault,403440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almHighHigh.AlarmState,403440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almHighHigh.GlobalReset,403440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almHighHigh.FaultInAlarm,403440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almHighHigh.ALRM,403440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almHighHigh.ANUN,403440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almHighHigh.AKED,403440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almHighHigh.Resetable,403440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almHighHigh.REST,403440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almHighHigh.ACKN,403440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almHighHigh.UACK,403440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almHighHigh.MCmd_Enable,403440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almHighHigh.MCmd_Disable,403440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almHighHigh.OCmd_Shelve,403440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almHighHigh.OCmd_Unshelve,403440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almHighHigh.SCmd_Suppress,403440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almHighHigh.SCmd_UnSuppress,403441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almHighHigh.AEShelveTMRDN,403441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almHighHigh.Bad,403441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almHighHigh.Suppress,403442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.UnSuppress,403442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Shelve,403442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.UnShelve,403442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Enable,403442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Disable,403442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Ack,403442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Reset,403442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Suppressed,403442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Shelved,403442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Disabled,403442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Acked,403442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almHighHigh.Alarm,403442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Fault,403452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almHigh.AlarmState,403452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almHigh.GlobalReset,403452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almHigh.FaultInAlarm,403452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almHigh.ALRM,403452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almHigh.ANUN,403452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almHigh.AKED,403452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almHigh.Resetable,403452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almHigh.REST,403452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almHigh.ACKN,403452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almHigh.UACK,403452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almHigh.MCmd_Enable,403452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almHigh.MCmd_Disable,403452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almHigh.OCmd_Shelve,403452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almHigh.OCmd_Unshelve,403452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almHigh.SCmd_Suppress,403452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almHigh.SCmd_UnSuppress,403453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almHigh.AEShelveTMRDN,403453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almHigh.Bad,403453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almHigh.Suppress,403454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.UnSuppress,403454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Shelve,403454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.UnShelve,403454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Enable,403454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Disable,403454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Ack,403454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Reset,403454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almHigh.Suppressed,403454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almHigh.Shelved,403454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almHigh.Disabled,403454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almHigh.Acked,403454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almHigh.Alarm,403454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Fault,403464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almLow.AlarmState,403464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almLow.GlobalReset,403464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almLow.FaultInAlarm,403464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almLow.ALRM,403464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almLow.ANUN,403464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almLow.AKED,403464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almLow.Resetable,403464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almLow.REST,403464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almLow.ACKN,403464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almLow.UACK,403464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almLow.MCmd_Enable,403464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almLow.MCmd_Disable,403464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almLow.OCmd_Shelve,403464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almLow.OCmd_Unshelve,403464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almLow.SCmd_Suppress,403464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almLow.SCmd_UnSuppress,403465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almLow.AEShelveTMRDN,403465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almLow.Bad,403465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almLow.Suppress,403466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.UnSuppress,403466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Shelve,403466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.UnShelve,403466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Enable,403466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Disable,403466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Ack,403466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Reset,403466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almLow.Suppressed,403466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almLow.Shelved,403466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almLow.Disabled,403466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almLow.Acked,403466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almLow.Alarm,403466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Fault,403476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almLowLow.AlarmState,403476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almLowLow.GlobalReset,403476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almLowLow.FaultInAlarm,403476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almLowLow.ALRM,403476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almLowLow.ANUN,403476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almLowLow.AKED,403476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almLowLow.Resetable,403476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almLowLow.REST,403476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almLowLow.ACKN,403476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almLowLow.UACK,403476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almLowLow.MCmd_Enable,403476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almLowLow.MCmd_Disable,403476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almLowLow.OCmd_Shelve,403476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almLowLow.OCmd_Unshelve,403476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almLowLow.SCmd_Suppress,403476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almLowLow.SCmd_UnSuppress,403477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almLowLow.AEShelveTMRDN,403477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almLowLow.Bad,403477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almLowLow.Suppress,403478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.UnSuppress,403478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Shelve,403478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.UnShelve,403478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Enable,403478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Disable,403478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Ack,403478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Reset,403478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almLowLow.Suppressed,403478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almLowLow.Shelved,403478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almLowLow.Disabled,403478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almLowLow.Acked,403478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almLowLow.Alarm,403478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Fault,403488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almBrokenLoop.AlarmState,403488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almBrokenLoop.GlobalReset,403488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almBrokenLoop.FaultInAlarm,403488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almBrokenLoop.ALRM,403488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almBrokenLoop.ANUN,403488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almBrokenLoop.AKED,403488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almBrokenLoop.Resetable,403488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almBrokenLoop.REST,403488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almBrokenLoop.ACKN,403488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almBrokenLoop.UACK,403488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almBrokenLoop.MCmd_Enable,403488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.MCmd_Disable,403488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.OCmd_Shelve,403488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.OCmd_Unshelve,403488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.SCmd_Suppress,403488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.SCmd_UnSuppress,403489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almBrokenLoop.AEShelveTMRDN,403489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almBrokenLoop.Bad,403489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almBrokenLoop.Suppress,403490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.UnSuppress,403490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Shelve,403490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.UnShelve,403490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Enable,403490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Disable,403490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Ack,403490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Reset,403490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Suppressed,403490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Shelved,403490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Disabled,403490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Acked,403490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almBrokenLoop.Alarm,403490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Fault,403500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almOverRange.AlarmState,403500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almOverRange.GlobalReset,403500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almOverRange.FaultInAlarm,403500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almOverRange.ALRM,403500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almOverRange.ANUN,403500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almOverRange.AKED,403500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almOverRange.Resetable,403500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almOverRange.REST,403500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almOverRange.ACKN,403500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almOverRange.UACK,403500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almOverRange.MCmd_Enable,403500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almOverRange.MCmd_Disable,403500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almOverRange.OCmd_Shelve,403500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almOverRange.OCmd_Unshelve,403500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almOverRange.SCmd_Suppress,403500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almOverRange.SCmd_UnSuppress,403501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almOverRange.AEShelveTMRDN,403501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almOverRange.Bad,403501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almOverRange.Suppress,403502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.UnSuppress,403502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Shelve,403502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.UnShelve,403502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Enable,403502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Disable,403502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Ack,403502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Reset,403502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almOverRange.Suppressed,403502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almOverRange.Shelved,403502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almOverRange.Disabled,403502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almOverRange.Acked,403502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almOverRange.Alarm,403502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Fault,403512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almUnderRange.AlarmState,403512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almUnderRange.GlobalReset,403512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almUnderRange.FaultInAlarm,403512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almUnderRange.ALRM,403512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almUnderRange.ANUN,403512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almUnderRange.AKED,403512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almUnderRange.Resetable,403512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almUnderRange.REST,403512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almUnderRange.ACKN,403512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almUnderRange.UACK,403512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almUnderRange.MCmd_Enable,403512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almUnderRange.MCmd_Disable,403512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almUnderRange.OCmd_Shelve,403512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almUnderRange.OCmd_Unshelve,403512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almUnderRange.SCmd_Suppress,403512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almUnderRange.SCmd_UnSuppress,403513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almUnderRange.AEShelveTMRDN,403513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almUnderRange.Bad,403513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almUnderRange.Suppress,403514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.UnSuppress,403514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Shelve,403514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.UnShelve,403514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Enable,403514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Disable,403514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Ack,403514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Reset,403514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Suppressed,403514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Shelved,403514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Disabled,403514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Acked,403514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almUnderRange.Alarm,403514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Fault,403524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almRateOfChange.AlarmState,403524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almRateOfChange.GlobalReset,403524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almRateOfChange.FaultInAlarm,403524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almRateOfChange.ALRM,403524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almRateOfChange.ANUN,403524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almRateOfChange.AKED,403524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almRateOfChange.Resetable,403524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almRateOfChange.REST,403524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almRateOfChange.ACKN,403524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almRateOfChange.UACK,403524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almRateOfChange.MCmd_Enable,403524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.MCmd_Disable,403524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.OCmd_Shelve,403524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.OCmd_Unshelve,403524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.SCmd_Suppress,403524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.SCmd_UnSuppress,403525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almRateOfChange.AEShelveTMRDN,403525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almRateOfChange.Bad,403525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almRateOfChange.Suppress,403526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.UnSuppress,403526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Shelve,403526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.UnShelve,403526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Enable,403526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Disable,403526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Ack,403526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Reset,403526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Suppressed,403526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Shelved,403526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Disabled,403526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Acked,403526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almRateOfChange.Alarm,403526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Fault,403536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI4.almPLCFault.AlarmState,403536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI4.almPLCFault.GlobalReset,403536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI4.almPLCFault.FaultInAlarm,403536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI4.almPLCFault.ALRM,403536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI4.almPLCFault.ANUN,403536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI4.almPLCFault.AKED,403536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI4.almPLCFault.Resetable,403536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI4.almPLCFault.REST,403536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI4.almPLCFault.ACKN,403536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI4.almPLCFault.UACK,403536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI4.almPLCFault.MCmd_Enable,403536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI4.almPLCFault.MCmd_Disable,403536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI4.almPLCFault.OCmd_Shelve,403536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI4.almPLCFault.OCmd_Unshelve,403536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI4.almPLCFault.SCmd_Suppress,403536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI4.almPLCFault.SCmd_UnSuppress,403537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI4.almPLCFault.AEShelveTMRDN,403537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI4.almPLCFault.Bad,403537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI4.almPLCFault.Suppress,403538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.UnSuppress,403538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Shelve,403538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.UnShelve,403538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Enable,403538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Disable,403538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Ack,403538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Reset,403538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Suppressed,403538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Shelved,403538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Disabled,403538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Acked,403538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI4.almPLCFault.Alarm,403538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Fault,403640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almHighHigh.AlarmState,403640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almHighHigh.GlobalReset,403640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almHighHigh.FaultInAlarm,403640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almHighHigh.ALRM,403640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almHighHigh.ANUN,403640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almHighHigh.AKED,403640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almHighHigh.Resetable,403640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almHighHigh.REST,403640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almHighHigh.ACKN,403640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almHighHigh.UACK,403640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almHighHigh.MCmd_Enable,403640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almHighHigh.MCmd_Disable,403640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almHighHigh.OCmd_Shelve,403640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almHighHigh.OCmd_Unshelve,403640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almHighHigh.SCmd_Suppress,403640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almHighHigh.SCmd_UnSuppress,403641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almHighHigh.AEShelveTMRDN,403641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almHighHigh.Bad,403641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almHighHigh.Suppress,403642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.UnSuppress,403642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Shelve,403642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.UnShelve,403642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Enable,403642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Disable,403642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Ack,403642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Reset,403642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Suppressed,403642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Shelved,403642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Disabled,403642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Acked,403642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almHighHigh.Alarm,403642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Fault,403652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almHigh.AlarmState,403652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almHigh.GlobalReset,403652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almHigh.FaultInAlarm,403652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almHigh.ALRM,403652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almHigh.ANUN,403652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almHigh.AKED,403652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almHigh.Resetable,403652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almHigh.REST,403652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almHigh.ACKN,403652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almHigh.UACK,403652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almHigh.MCmd_Enable,403652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almHigh.MCmd_Disable,403652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almHigh.OCmd_Shelve,403652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almHigh.OCmd_Unshelve,403652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almHigh.SCmd_Suppress,403652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almHigh.SCmd_UnSuppress,403653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almHigh.AEShelveTMRDN,403653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almHigh.Bad,403653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almHigh.Suppress,403654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.UnSuppress,403654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Shelve,403654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.UnShelve,403654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Enable,403654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Disable,403654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Ack,403654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Reset,403654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almHigh.Suppressed,403654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almHigh.Shelved,403654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almHigh.Disabled,403654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almHigh.Acked,403654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almHigh.Alarm,403654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Fault,403664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almLow.AlarmState,403664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almLow.GlobalReset,403664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almLow.FaultInAlarm,403664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almLow.ALRM,403664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almLow.ANUN,403664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almLow.AKED,403664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almLow.Resetable,403664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almLow.REST,403664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almLow.ACKN,403664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almLow.UACK,403664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almLow.MCmd_Enable,403664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almLow.MCmd_Disable,403664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almLow.OCmd_Shelve,403664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almLow.OCmd_Unshelve,403664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almLow.SCmd_Suppress,403664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almLow.SCmd_UnSuppress,403665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almLow.AEShelveTMRDN,403665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almLow.Bad,403665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almLow.Suppress,403666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.UnSuppress,403666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Shelve,403666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.UnShelve,403666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Enable,403666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Disable,403666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Ack,403666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Reset,403666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almLow.Suppressed,403666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almLow.Shelved,403666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almLow.Disabled,403666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almLow.Acked,403666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almLow.Alarm,403666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Fault,403676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almLowLow.AlarmState,403676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almLowLow.GlobalReset,403676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almLowLow.FaultInAlarm,403676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almLowLow.ALRM,403676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almLowLow.ANUN,403676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almLowLow.AKED,403676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almLowLow.Resetable,403676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almLowLow.REST,403676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almLowLow.ACKN,403676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almLowLow.UACK,403676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almLowLow.MCmd_Enable,403676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almLowLow.MCmd_Disable,403676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almLowLow.OCmd_Shelve,403676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almLowLow.OCmd_Unshelve,403676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almLowLow.SCmd_Suppress,403676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almLowLow.SCmd_UnSuppress,403677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almLowLow.AEShelveTMRDN,403677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almLowLow.Bad,403677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almLowLow.Suppress,403678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.UnSuppress,403678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Shelve,403678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.UnShelve,403678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Enable,403678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Disable,403678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Ack,403678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Reset,403678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almLowLow.Suppressed,403678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almLowLow.Shelved,403678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almLowLow.Disabled,403678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almLowLow.Acked,403678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almLowLow.Alarm,403678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Fault,403688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almBrokenLoop.AlarmState,403688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almBrokenLoop.GlobalReset,403688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almBrokenLoop.FaultInAlarm,403688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almBrokenLoop.ALRM,403688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almBrokenLoop.ANUN,403688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almBrokenLoop.AKED,403688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almBrokenLoop.Resetable,403688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almBrokenLoop.REST,403688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almBrokenLoop.ACKN,403688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almBrokenLoop.UACK,403688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almBrokenLoop.MCmd_Enable,403688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.MCmd_Disable,403688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.OCmd_Shelve,403688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.OCmd_Unshelve,403688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.SCmd_Suppress,403688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.SCmd_UnSuppress,403689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almBrokenLoop.AEShelveTMRDN,403689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almBrokenLoop.Bad,403689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almBrokenLoop.Suppress,403690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.UnSuppress,403690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Shelve,403690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.UnShelve,403690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Enable,403690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Disable,403690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Ack,403690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Reset,403690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Suppressed,403690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Shelved,403690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Disabled,403690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Acked,403690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almBrokenLoop.Alarm,403690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Fault,403700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almOverRange.AlarmState,403700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almOverRange.GlobalReset,403700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almOverRange.FaultInAlarm,403700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almOverRange.ALRM,403700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almOverRange.ANUN,403700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almOverRange.AKED,403700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almOverRange.Resetable,403700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almOverRange.REST,403700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almOverRange.ACKN,403700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almOverRange.UACK,403700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almOverRange.MCmd_Enable,403700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almOverRange.MCmd_Disable,403700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almOverRange.OCmd_Shelve,403700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almOverRange.OCmd_Unshelve,403700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almOverRange.SCmd_Suppress,403700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almOverRange.SCmd_UnSuppress,403701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almOverRange.AEShelveTMRDN,403701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almOverRange.Bad,403701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almOverRange.Suppress,403702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.UnSuppress,403702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Shelve,403702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.UnShelve,403702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Enable,403702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Disable,403702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Ack,403702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Reset,403702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almOverRange.Suppressed,403702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almOverRange.Shelved,403702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almOverRange.Disabled,403702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almOverRange.Acked,403702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almOverRange.Alarm,403702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Fault,403712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almUnderRange.AlarmState,403712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almUnderRange.GlobalReset,403712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almUnderRange.FaultInAlarm,403712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almUnderRange.ALRM,403712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almUnderRange.ANUN,403712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almUnderRange.AKED,403712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almUnderRange.Resetable,403712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almUnderRange.REST,403712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almUnderRange.ACKN,403712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almUnderRange.UACK,403712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almUnderRange.MCmd_Enable,403712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almUnderRange.MCmd_Disable,403712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almUnderRange.OCmd_Shelve,403712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almUnderRange.OCmd_Unshelve,403712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almUnderRange.SCmd_Suppress,403712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almUnderRange.SCmd_UnSuppress,403713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almUnderRange.AEShelveTMRDN,403713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almUnderRange.Bad,403713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almUnderRange.Suppress,403714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.UnSuppress,403714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Shelve,403714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.UnShelve,403714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Enable,403714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Disable,403714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Ack,403714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Reset,403714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Suppressed,403714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Shelved,403714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Disabled,403714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Acked,403714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almUnderRange.Alarm,403714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Fault,403724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almRateOfChange.AlarmState,403724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almRateOfChange.GlobalReset,403724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almRateOfChange.FaultInAlarm,403724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almRateOfChange.ALRM,403724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almRateOfChange.ANUN,403724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almRateOfChange.AKED,403724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almRateOfChange.Resetable,403724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almRateOfChange.REST,403724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almRateOfChange.ACKN,403724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almRateOfChange.UACK,403724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almRateOfChange.MCmd_Enable,403724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.MCmd_Disable,403724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.OCmd_Shelve,403724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.OCmd_Unshelve,403724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.SCmd_Suppress,403724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.SCmd_UnSuppress,403725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almRateOfChange.AEShelveTMRDN,403725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almRateOfChange.Bad,403725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almRateOfChange.Suppress,403726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.UnSuppress,403726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Shelve,403726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.UnShelve,403726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Enable,403726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Disable,403726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Ack,403726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Reset,403726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Suppressed,403726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Shelved,403726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Disabled,403726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Acked,403726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almRateOfChange.Alarm,403726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Fault,403736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI5.almPLCFault.AlarmState,403736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI5.almPLCFault.GlobalReset,403736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI5.almPLCFault.FaultInAlarm,403736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI5.almPLCFault.ALRM,403736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI5.almPLCFault.ANUN,403736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI5.almPLCFault.AKED,403736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI5.almPLCFault.Resetable,403736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI5.almPLCFault.REST,403736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI5.almPLCFault.ACKN,403736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI5.almPLCFault.UACK,403736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI5.almPLCFault.MCmd_Enable,403736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI5.almPLCFault.MCmd_Disable,403736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI5.almPLCFault.OCmd_Shelve,403736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI5.almPLCFault.OCmd_Unshelve,403736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI5.almPLCFault.SCmd_Suppress,403736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI5.almPLCFault.SCmd_UnSuppress,403737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI5.almPLCFault.AEShelveTMRDN,403737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI5.almPLCFault.Bad,403737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI5.almPLCFault.Suppress,403738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.UnSuppress,403738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Shelve,403738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.UnShelve,403738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Enable,403738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Disable,403738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Ack,403738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Reset,403738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Suppressed,403738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Shelved,403738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Disabled,403738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Acked,403738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI5.almPLCFault.Alarm,403738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Fault,403840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almHighHigh.AlarmState,403840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almHighHigh.GlobalReset,403840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almHighHigh.FaultInAlarm,403840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almHighHigh.ALRM,403840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almHighHigh.ANUN,403840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almHighHigh.AKED,403840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almHighHigh.Resetable,403840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almHighHigh.REST,403840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almHighHigh.ACKN,403840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almHighHigh.UACK,403840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almHighHigh.MCmd_Enable,403840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almHighHigh.MCmd_Disable,403840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almHighHigh.OCmd_Shelve,403840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almHighHigh.OCmd_Unshelve,403840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almHighHigh.SCmd_Suppress,403840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almHighHigh.SCmd_UnSuppress,403841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almHighHigh.AEShelveTMRDN,403841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almHighHigh.Bad,403841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almHighHigh.Suppress,403842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.UnSuppress,403842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Shelve,403842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.UnShelve,403842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Enable,403842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Disable,403842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Ack,403842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Reset,403842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Suppressed,403842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Shelved,403842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Disabled,403842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Acked,403842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almHighHigh.Alarm,403842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Fault,403852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almHigh.AlarmState,403852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almHigh.GlobalReset,403852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almHigh.FaultInAlarm,403852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almHigh.ALRM,403852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almHigh.ANUN,403852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almHigh.AKED,403852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almHigh.Resetable,403852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almHigh.REST,403852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almHigh.ACKN,403852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almHigh.UACK,403852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almHigh.MCmd_Enable,403852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almHigh.MCmd_Disable,403852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almHigh.OCmd_Shelve,403852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almHigh.OCmd_Unshelve,403852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almHigh.SCmd_Suppress,403852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almHigh.SCmd_UnSuppress,403853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almHigh.AEShelveTMRDN,403853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almHigh.Bad,403853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almHigh.Suppress,403854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.UnSuppress,403854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Shelve,403854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.UnShelve,403854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Enable,403854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Disable,403854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Ack,403854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Reset,403854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almHigh.Suppressed,403854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almHigh.Shelved,403854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almHigh.Disabled,403854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almHigh.Acked,403854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almHigh.Alarm,403854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Fault,403864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almLow.AlarmState,403864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almLow.GlobalReset,403864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almLow.FaultInAlarm,403864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almLow.ALRM,403864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almLow.ANUN,403864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almLow.AKED,403864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almLow.Resetable,403864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almLow.REST,403864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almLow.ACKN,403864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almLow.UACK,403864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almLow.MCmd_Enable,403864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almLow.MCmd_Disable,403864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almLow.OCmd_Shelve,403864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almLow.OCmd_Unshelve,403864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almLow.SCmd_Suppress,403864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almLow.SCmd_UnSuppress,403865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almLow.AEShelveTMRDN,403865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almLow.Bad,403865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almLow.Suppress,403866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.UnSuppress,403866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Shelve,403866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.UnShelve,403866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Enable,403866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Disable,403866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Ack,403866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Reset,403866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almLow.Suppressed,403866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almLow.Shelved,403866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almLow.Disabled,403866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almLow.Acked,403866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almLow.Alarm,403866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Fault,403876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almLowLow.AlarmState,403876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almLowLow.GlobalReset,403876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almLowLow.FaultInAlarm,403876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almLowLow.ALRM,403876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almLowLow.ANUN,403876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almLowLow.AKED,403876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almLowLow.Resetable,403876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almLowLow.REST,403876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almLowLow.ACKN,403876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almLowLow.UACK,403876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almLowLow.MCmd_Enable,403876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almLowLow.MCmd_Disable,403876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almLowLow.OCmd_Shelve,403876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almLowLow.OCmd_Unshelve,403876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almLowLow.SCmd_Suppress,403876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almLowLow.SCmd_UnSuppress,403877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almLowLow.AEShelveTMRDN,403877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almLowLow.Bad,403877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almLowLow.Suppress,403878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.UnSuppress,403878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Shelve,403878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.UnShelve,403878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Enable,403878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Disable,403878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Ack,403878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Reset,403878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almLowLow.Suppressed,403878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almLowLow.Shelved,403878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almLowLow.Disabled,403878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almLowLow.Acked,403878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almLowLow.Alarm,403878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Fault,403888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almBrokenLoop.AlarmState,403888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almBrokenLoop.GlobalReset,403888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almBrokenLoop.FaultInAlarm,403888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almBrokenLoop.ALRM,403888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almBrokenLoop.ANUN,403888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almBrokenLoop.AKED,403888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almBrokenLoop.Resetable,403888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almBrokenLoop.REST,403888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almBrokenLoop.ACKN,403888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almBrokenLoop.UACK,403888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almBrokenLoop.MCmd_Enable,403888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.MCmd_Disable,403888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.OCmd_Shelve,403888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.OCmd_Unshelve,403888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.SCmd_Suppress,403888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.SCmd_UnSuppress,403889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almBrokenLoop.AEShelveTMRDN,403889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almBrokenLoop.Bad,403889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almBrokenLoop.Suppress,403890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.UnSuppress,403890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Shelve,403890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.UnShelve,403890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Enable,403890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Disable,403890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Ack,403890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Reset,403890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Suppressed,403890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Shelved,403890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Disabled,403890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Acked,403890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almBrokenLoop.Alarm,403890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Fault,403900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almOverRange.AlarmState,403900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almOverRange.GlobalReset,403900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almOverRange.FaultInAlarm,403900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almOverRange.ALRM,403900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almOverRange.ANUN,403900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almOverRange.AKED,403900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almOverRange.Resetable,403900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almOverRange.REST,403900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almOverRange.ACKN,403900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almOverRange.UACK,403900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almOverRange.MCmd_Enable,403900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almOverRange.MCmd_Disable,403900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almOverRange.OCmd_Shelve,403900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almOverRange.OCmd_Unshelve,403900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almOverRange.SCmd_Suppress,403900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almOverRange.SCmd_UnSuppress,403901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almOverRange.AEShelveTMRDN,403901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almOverRange.Bad,403901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almOverRange.Suppress,403902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.UnSuppress,403902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Shelve,403902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.UnShelve,403902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Enable,403902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Disable,403902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Ack,403902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Reset,403902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almOverRange.Suppressed,403902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almOverRange.Shelved,403902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almOverRange.Disabled,403902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almOverRange.Acked,403902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almOverRange.Alarm,403902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Fault,403912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almUnderRange.AlarmState,403912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almUnderRange.GlobalReset,403912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almUnderRange.FaultInAlarm,403912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almUnderRange.ALRM,403912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almUnderRange.ANUN,403912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almUnderRange.AKED,403912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almUnderRange.Resetable,403912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almUnderRange.REST,403912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almUnderRange.ACKN,403912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almUnderRange.UACK,403912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almUnderRange.MCmd_Enable,403912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almUnderRange.MCmd_Disable,403912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almUnderRange.OCmd_Shelve,403912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almUnderRange.OCmd_Unshelve,403912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almUnderRange.SCmd_Suppress,403912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almUnderRange.SCmd_UnSuppress,403913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almUnderRange.AEShelveTMRDN,403913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almUnderRange.Bad,403913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almUnderRange.Suppress,403914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.UnSuppress,403914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Shelve,403914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.UnShelve,403914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Enable,403914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Disable,403914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Ack,403914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Reset,403914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Suppressed,403914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Shelved,403914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Disabled,403914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Acked,403914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almUnderRange.Alarm,403914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Fault,403924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almRateOfChange.AlarmState,403924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almRateOfChange.GlobalReset,403924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almRateOfChange.FaultInAlarm,403924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almRateOfChange.ALRM,403924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almRateOfChange.ANUN,403924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almRateOfChange.AKED,403924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almRateOfChange.Resetable,403924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almRateOfChange.REST,403924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almRateOfChange.ACKN,403924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almRateOfChange.UACK,403924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almRateOfChange.MCmd_Enable,403924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.MCmd_Disable,403924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.OCmd_Shelve,403924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.OCmd_Unshelve,403924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.SCmd_Suppress,403924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.SCmd_UnSuppress,403925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almRateOfChange.AEShelveTMRDN,403925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almRateOfChange.Bad,403925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almRateOfChange.Suppress,403926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.UnSuppress,403926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Shelve,403926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.UnShelve,403926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Enable,403926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Disable,403926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Ack,403926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Reset,403926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Suppressed,403926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Shelved,403926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Disabled,403926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Acked,403926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almRateOfChange.Alarm,403926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Fault,403936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI6.almPLCFault.AlarmState,403936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI6.almPLCFault.GlobalReset,403936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI6.almPLCFault.FaultInAlarm,403936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI6.almPLCFault.ALRM,403936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI6.almPLCFault.ANUN,403936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI6.almPLCFault.AKED,403936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI6.almPLCFault.Resetable,403936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI6.almPLCFault.REST,403936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI6.almPLCFault.ACKN,403936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI6.almPLCFault.UACK,403936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI6.almPLCFault.MCmd_Enable,403936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI6.almPLCFault.MCmd_Disable,403936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI6.almPLCFault.OCmd_Shelve,403936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI6.almPLCFault.OCmd_Unshelve,403936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI6.almPLCFault.SCmd_Suppress,403936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI6.almPLCFault.SCmd_UnSuppress,403937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI6.almPLCFault.AEShelveTMRDN,403937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI6.almPLCFault.Bad,403937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI6.almPLCFault.Suppress,403938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.UnSuppress,403938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Shelve,403938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.UnShelve,403938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Enable,403938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Disable,403938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Ack,403938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Reset,403938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Suppressed,403938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Shelved,403938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Disabled,403938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Acked,403938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI6.almPLCFault.Alarm,403938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Fault,404040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almHighHigh.AlarmState,404040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almHighHigh.GlobalReset,404040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almHighHigh.FaultInAlarm,404040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almHighHigh.ALRM,404040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almHighHigh.ANUN,404040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almHighHigh.AKED,404040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almHighHigh.Resetable,404040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almHighHigh.REST,404040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almHighHigh.ACKN,404040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almHighHigh.UACK,404040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almHighHigh.MCmd_Enable,404040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almHighHigh.MCmd_Disable,404040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almHighHigh.OCmd_Shelve,404040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almHighHigh.OCmd_Unshelve,404040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almHighHigh.SCmd_Suppress,404040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almHighHigh.SCmd_UnSuppress,404041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almHighHigh.AEShelveTMRDN,404041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almHighHigh.Bad,404041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almHighHigh.Suppress,404042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.UnSuppress,404042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Shelve,404042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.UnShelve,404042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Enable,404042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Disable,404042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Ack,404042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Reset,404042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Suppressed,404042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Shelved,404042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Disabled,404042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Acked,404042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almHighHigh.Alarm,404042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Fault,404052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almHigh.AlarmState,404052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almHigh.GlobalReset,404052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almHigh.FaultInAlarm,404052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almHigh.ALRM,404052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almHigh.ANUN,404052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almHigh.AKED,404052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almHigh.Resetable,404052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almHigh.REST,404052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almHigh.ACKN,404052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almHigh.UACK,404052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almHigh.MCmd_Enable,404052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almHigh.MCmd_Disable,404052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almHigh.OCmd_Shelve,404052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almHigh.OCmd_Unshelve,404052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almHigh.SCmd_Suppress,404052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almHigh.SCmd_UnSuppress,404053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almHigh.AEShelveTMRDN,404053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almHigh.Bad,404053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almHigh.Suppress,404054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.UnSuppress,404054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Shelve,404054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.UnShelve,404054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Enable,404054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Disable,404054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Ack,404054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Reset,404054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almHigh.Suppressed,404054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almHigh.Shelved,404054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almHigh.Disabled,404054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almHigh.Acked,404054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almHigh.Alarm,404054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Fault,404064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almLow.AlarmState,404064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almLow.GlobalReset,404064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almLow.FaultInAlarm,404064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almLow.ALRM,404064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almLow.ANUN,404064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almLow.AKED,404064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almLow.Resetable,404064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almLow.REST,404064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almLow.ACKN,404064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almLow.UACK,404064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almLow.MCmd_Enable,404064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almLow.MCmd_Disable,404064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almLow.OCmd_Shelve,404064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almLow.OCmd_Unshelve,404064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almLow.SCmd_Suppress,404064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almLow.SCmd_UnSuppress,404065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almLow.AEShelveTMRDN,404065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almLow.Bad,404065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almLow.Suppress,404066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.UnSuppress,404066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Shelve,404066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.UnShelve,404066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Enable,404066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Disable,404066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Ack,404066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Reset,404066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almLow.Suppressed,404066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almLow.Shelved,404066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almLow.Disabled,404066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almLow.Acked,404066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almLow.Alarm,404066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Fault,404076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almLowLow.AlarmState,404076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almLowLow.GlobalReset,404076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almLowLow.FaultInAlarm,404076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almLowLow.ALRM,404076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almLowLow.ANUN,404076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almLowLow.AKED,404076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almLowLow.Resetable,404076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almLowLow.REST,404076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almLowLow.ACKN,404076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almLowLow.UACK,404076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almLowLow.MCmd_Enable,404076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almLowLow.MCmd_Disable,404076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almLowLow.OCmd_Shelve,404076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almLowLow.OCmd_Unshelve,404076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almLowLow.SCmd_Suppress,404076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almLowLow.SCmd_UnSuppress,404077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almLowLow.AEShelveTMRDN,404077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almLowLow.Bad,404077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almLowLow.Suppress,404078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.UnSuppress,404078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Shelve,404078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.UnShelve,404078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Enable,404078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Disable,404078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Ack,404078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Reset,404078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almLowLow.Suppressed,404078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almLowLow.Shelved,404078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almLowLow.Disabled,404078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almLowLow.Acked,404078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almLowLow.Alarm,404078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Fault,404088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almBrokenLoop.AlarmState,404088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almBrokenLoop.GlobalReset,404088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almBrokenLoop.FaultInAlarm,404088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almBrokenLoop.ALRM,404088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almBrokenLoop.ANUN,404088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almBrokenLoop.AKED,404088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almBrokenLoop.Resetable,404088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almBrokenLoop.REST,404088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almBrokenLoop.ACKN,404088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almBrokenLoop.UACK,404088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almBrokenLoop.MCmd_Enable,404088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.MCmd_Disable,404088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.OCmd_Shelve,404088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.OCmd_Unshelve,404088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.SCmd_Suppress,404088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.SCmd_UnSuppress,404089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almBrokenLoop.AEShelveTMRDN,404089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almBrokenLoop.Bad,404089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almBrokenLoop.Suppress,404090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.UnSuppress,404090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Shelve,404090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.UnShelve,404090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Enable,404090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Disable,404090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Ack,404090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Reset,404090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Suppressed,404090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Shelved,404090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Disabled,404090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Acked,404090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almBrokenLoop.Alarm,404090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Fault,404100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almOverRange.AlarmState,404100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almOverRange.GlobalReset,404100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almOverRange.FaultInAlarm,404100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almOverRange.ALRM,404100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almOverRange.ANUN,404100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almOverRange.AKED,404100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almOverRange.Resetable,404100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almOverRange.REST,404100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almOverRange.ACKN,404100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almOverRange.UACK,404100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almOverRange.MCmd_Enable,404100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almOverRange.MCmd_Disable,404100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almOverRange.OCmd_Shelve,404100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almOverRange.OCmd_Unshelve,404100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almOverRange.SCmd_Suppress,404100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almOverRange.SCmd_UnSuppress,404101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almOverRange.AEShelveTMRDN,404101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almOverRange.Bad,404101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almOverRange.Suppress,404102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.UnSuppress,404102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Shelve,404102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.UnShelve,404102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Enable,404102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Disable,404102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Ack,404102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Reset,404102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almOverRange.Suppressed,404102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almOverRange.Shelved,404102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almOverRange.Disabled,404102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almOverRange.Acked,404102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almOverRange.Alarm,404102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Fault,404112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almUnderRange.AlarmState,404112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almUnderRange.GlobalReset,404112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almUnderRange.FaultInAlarm,404112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almUnderRange.ALRM,404112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almUnderRange.ANUN,404112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almUnderRange.AKED,404112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almUnderRange.Resetable,404112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almUnderRange.REST,404112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almUnderRange.ACKN,404112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almUnderRange.UACK,404112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almUnderRange.MCmd_Enable,404112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almUnderRange.MCmd_Disable,404112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almUnderRange.OCmd_Shelve,404112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almUnderRange.OCmd_Unshelve,404112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almUnderRange.SCmd_Suppress,404112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almUnderRange.SCmd_UnSuppress,404113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almUnderRange.AEShelveTMRDN,404113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almUnderRange.Bad,404113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almUnderRange.Suppress,404114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.UnSuppress,404114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Shelve,404114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.UnShelve,404114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Enable,404114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Disable,404114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Ack,404114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Reset,404114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Suppressed,404114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Shelved,404114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Disabled,404114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Acked,404114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almUnderRange.Alarm,404114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Fault,404124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almRateOfChange.AlarmState,404124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almRateOfChange.GlobalReset,404124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almRateOfChange.FaultInAlarm,404124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almRateOfChange.ALRM,404124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almRateOfChange.ANUN,404124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almRateOfChange.AKED,404124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almRateOfChange.Resetable,404124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almRateOfChange.REST,404124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almRateOfChange.ACKN,404124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almRateOfChange.UACK,404124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almRateOfChange.MCmd_Enable,404124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.MCmd_Disable,404124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.OCmd_Shelve,404124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.OCmd_Unshelve,404124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.SCmd_Suppress,404124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.SCmd_UnSuppress,404125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almRateOfChange.AEShelveTMRDN,404125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almRateOfChange.Bad,404125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almRateOfChange.Suppress,404126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.UnSuppress,404126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Shelve,404126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.UnShelve,404126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Enable,404126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Disable,404126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Ack,404126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Reset,404126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Suppressed,404126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Shelved,404126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Disabled,404126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Acked,404126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almRateOfChange.Alarm,404126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Fault,404136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI7.almPLCFault.AlarmState,404136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI7.almPLCFault.GlobalReset,404136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI7.almPLCFault.FaultInAlarm,404136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI7.almPLCFault.ALRM,404136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI7.almPLCFault.ANUN,404136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI7.almPLCFault.AKED,404136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI7.almPLCFault.Resetable,404136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI7.almPLCFault.REST,404136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI7.almPLCFault.ACKN,404136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI7.almPLCFault.UACK,404136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI7.almPLCFault.MCmd_Enable,404136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI7.almPLCFault.MCmd_Disable,404136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI7.almPLCFault.OCmd_Shelve,404136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI7.almPLCFault.OCmd_Unshelve,404136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI7.almPLCFault.SCmd_Suppress,404136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI7.almPLCFault.SCmd_UnSuppress,404137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI7.almPLCFault.AEShelveTMRDN,404137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI7.almPLCFault.Bad,404137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI7.almPLCFault.Suppress,404138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.UnSuppress,404138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Shelve,404138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.UnShelve,404138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Enable,404138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Disable,404138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Ack,404138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Reset,404138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Suppressed,404138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Shelved,404138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Disabled,404138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Acked,404138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI7.almPLCFault.Alarm,404138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Fault,404240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almHighHigh.AlarmState,404240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almHighHigh.GlobalReset,404240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almHighHigh.FaultInAlarm,404240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almHighHigh.ALRM,404240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almHighHigh.ANUN,404240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almHighHigh.AKED,404240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almHighHigh.Resetable,404240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almHighHigh.REST,404240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almHighHigh.ACKN,404240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almHighHigh.UACK,404240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almHighHigh.MCmd_Enable,404240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almHighHigh.MCmd_Disable,404240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almHighHigh.OCmd_Shelve,404240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almHighHigh.OCmd_Unshelve,404240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almHighHigh.SCmd_Suppress,404240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almHighHigh.SCmd_UnSuppress,404241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almHighHigh.AEShelveTMRDN,404241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almHighHigh.Bad,404241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almHighHigh.Suppress,404242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.UnSuppress,404242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Shelve,404242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.UnShelve,404242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Enable,404242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Disable,404242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Ack,404242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Reset,404242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Suppressed,404242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Shelved,404242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Disabled,404242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Acked,404242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almHighHigh.Alarm,404242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Fault,404252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almHigh.AlarmState,404252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almHigh.GlobalReset,404252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almHigh.FaultInAlarm,404252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almHigh.ALRM,404252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almHigh.ANUN,404252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almHigh.AKED,404252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almHigh.Resetable,404252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almHigh.REST,404252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almHigh.ACKN,404252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almHigh.UACK,404252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almHigh.MCmd_Enable,404252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almHigh.MCmd_Disable,404252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almHigh.OCmd_Shelve,404252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almHigh.OCmd_Unshelve,404252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almHigh.SCmd_Suppress,404252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almHigh.SCmd_UnSuppress,404253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almHigh.AEShelveTMRDN,404253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almHigh.Bad,404253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almHigh.Suppress,404254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.UnSuppress,404254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Shelve,404254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.UnShelve,404254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Enable,404254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Disable,404254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Ack,404254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Reset,404254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almHigh.Suppressed,404254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almHigh.Shelved,404254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almHigh.Disabled,404254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almHigh.Acked,404254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almHigh.Alarm,404254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Fault,404264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almLow.AlarmState,404264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almLow.GlobalReset,404264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almLow.FaultInAlarm,404264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almLow.ALRM,404264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almLow.ANUN,404264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almLow.AKED,404264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almLow.Resetable,404264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almLow.REST,404264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almLow.ACKN,404264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almLow.UACK,404264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almLow.MCmd_Enable,404264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almLow.MCmd_Disable,404264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almLow.OCmd_Shelve,404264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almLow.OCmd_Unshelve,404264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almLow.SCmd_Suppress,404264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almLow.SCmd_UnSuppress,404265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almLow.AEShelveTMRDN,404265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almLow.Bad,404265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almLow.Suppress,404266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.UnSuppress,404266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Shelve,404266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.UnShelve,404266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Enable,404266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Disable,404266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Ack,404266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Reset,404266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almLow.Suppressed,404266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almLow.Shelved,404266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almLow.Disabled,404266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almLow.Acked,404266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almLow.Alarm,404266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Fault,404276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almLowLow.AlarmState,404276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almLowLow.GlobalReset,404276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almLowLow.FaultInAlarm,404276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almLowLow.ALRM,404276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almLowLow.ANUN,404276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almLowLow.AKED,404276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almLowLow.Resetable,404276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almLowLow.REST,404276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almLowLow.ACKN,404276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almLowLow.UACK,404276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almLowLow.MCmd_Enable,404276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almLowLow.MCmd_Disable,404276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almLowLow.OCmd_Shelve,404276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almLowLow.OCmd_Unshelve,404276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almLowLow.SCmd_Suppress,404276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almLowLow.SCmd_UnSuppress,404277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almLowLow.AEShelveTMRDN,404277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almLowLow.Bad,404277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almLowLow.Suppress,404278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.UnSuppress,404278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Shelve,404278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.UnShelve,404278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Enable,404278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Disable,404278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Ack,404278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Reset,404278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almLowLow.Suppressed,404278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almLowLow.Shelved,404278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almLowLow.Disabled,404278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almLowLow.Acked,404278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almLowLow.Alarm,404278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Fault,404288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almBrokenLoop.AlarmState,404288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almBrokenLoop.GlobalReset,404288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almBrokenLoop.FaultInAlarm,404288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almBrokenLoop.ALRM,404288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almBrokenLoop.ANUN,404288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almBrokenLoop.AKED,404288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almBrokenLoop.Resetable,404288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almBrokenLoop.REST,404288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almBrokenLoop.ACKN,404288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almBrokenLoop.UACK,404288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almBrokenLoop.MCmd_Enable,404288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.MCmd_Disable,404288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.OCmd_Shelve,404288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.OCmd_Unshelve,404288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.SCmd_Suppress,404288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.SCmd_UnSuppress,404289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almBrokenLoop.AEShelveTMRDN,404289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almBrokenLoop.Bad,404289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almBrokenLoop.Suppress,404290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.UnSuppress,404290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Shelve,404290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.UnShelve,404290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Enable,404290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Disable,404290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Ack,404290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Reset,404290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Suppressed,404290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Shelved,404290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Disabled,404290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Acked,404290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almBrokenLoop.Alarm,404290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Fault,404300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almOverRange.AlarmState,404300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almOverRange.GlobalReset,404300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almOverRange.FaultInAlarm,404300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almOverRange.ALRM,404300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almOverRange.ANUN,404300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almOverRange.AKED,404300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almOverRange.Resetable,404300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almOverRange.REST,404300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almOverRange.ACKN,404300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almOverRange.UACK,404300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almOverRange.MCmd_Enable,404300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almOverRange.MCmd_Disable,404300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almOverRange.OCmd_Shelve,404300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almOverRange.OCmd_Unshelve,404300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almOverRange.SCmd_Suppress,404300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almOverRange.SCmd_UnSuppress,404301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almOverRange.AEShelveTMRDN,404301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almOverRange.Bad,404301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almOverRange.Suppress,404302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.UnSuppress,404302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Shelve,404302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.UnShelve,404302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Enable,404302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Disable,404302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Ack,404302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Reset,404302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almOverRange.Suppressed,404302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almOverRange.Shelved,404302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almOverRange.Disabled,404302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almOverRange.Acked,404302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almOverRange.Alarm,404302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Fault,404312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almUnderRange.AlarmState,404312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almUnderRange.GlobalReset,404312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almUnderRange.FaultInAlarm,404312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almUnderRange.ALRM,404312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almUnderRange.ANUN,404312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almUnderRange.AKED,404312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almUnderRange.Resetable,404312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almUnderRange.REST,404312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almUnderRange.ACKN,404312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almUnderRange.UACK,404312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almUnderRange.MCmd_Enable,404312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almUnderRange.MCmd_Disable,404312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almUnderRange.OCmd_Shelve,404312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almUnderRange.OCmd_Unshelve,404312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almUnderRange.SCmd_Suppress,404312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almUnderRange.SCmd_UnSuppress,404313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almUnderRange.AEShelveTMRDN,404313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almUnderRange.Bad,404313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almUnderRange.Suppress,404314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.UnSuppress,404314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Shelve,404314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.UnShelve,404314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Enable,404314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Disable,404314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Ack,404314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Reset,404314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Suppressed,404314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Shelved,404314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Disabled,404314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Acked,404314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almUnderRange.Alarm,404314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Fault,404324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almRateOfChange.AlarmState,404324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almRateOfChange.GlobalReset,404324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almRateOfChange.FaultInAlarm,404324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almRateOfChange.ALRM,404324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almRateOfChange.ANUN,404324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almRateOfChange.AKED,404324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almRateOfChange.Resetable,404324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almRateOfChange.REST,404324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almRateOfChange.ACKN,404324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almRateOfChange.UACK,404324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almRateOfChange.MCmd_Enable,404324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.MCmd_Disable,404324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.OCmd_Shelve,404324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.OCmd_Unshelve,404324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.SCmd_Suppress,404324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.SCmd_UnSuppress,404325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almRateOfChange.AEShelveTMRDN,404325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almRateOfChange.Bad,404325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almRateOfChange.Suppress,404326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.UnSuppress,404326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Shelve,404326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.UnShelve,404326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Enable,404326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Disable,404326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Ack,404326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Reset,404326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Suppressed,404326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Shelved,404326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Disabled,404326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Acked,404326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almRateOfChange.Alarm,404326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Fault,404336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI8.almPLCFault.AlarmState,404336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI8.almPLCFault.GlobalReset,404336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI8.almPLCFault.FaultInAlarm,404336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI8.almPLCFault.ALRM,404336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI8.almPLCFault.ANUN,404336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI8.almPLCFault.AKED,404336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI8.almPLCFault.Resetable,404336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI8.almPLCFault.REST,404336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI8.almPLCFault.ACKN,404336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI8.almPLCFault.UACK,404336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI8.almPLCFault.MCmd_Enable,404336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI8.almPLCFault.MCmd_Disable,404336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI8.almPLCFault.OCmd_Shelve,404336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI8.almPLCFault.OCmd_Unshelve,404336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI8.almPLCFault.SCmd_Suppress,404336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI8.almPLCFault.SCmd_UnSuppress,404337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI8.almPLCFault.AEShelveTMRDN,404337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI8.almPLCFault.Bad,404337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI8.almPLCFault.Suppress,404338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.UnSuppress,404338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Shelve,404338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.UnShelve,404338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Enable,404338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Disable,404338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Ack,404338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Reset,404338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Suppressed,404338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Shelved,404338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Disabled,404338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Acked,404338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI8.almPLCFault.Alarm,404338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Fault,404440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almHighHigh.AlarmState,404440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almHighHigh.GlobalReset,404440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almHighHigh.FaultInAlarm,404440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almHighHigh.ALRM,404440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almHighHigh.ANUN,404440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almHighHigh.AKED,404440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almHighHigh.Resetable,404440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almHighHigh.REST,404440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almHighHigh.ACKN,404440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almHighHigh.UACK,404440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almHighHigh.MCmd_Enable,404440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almHighHigh.MCmd_Disable,404440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almHighHigh.OCmd_Shelve,404440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almHighHigh.OCmd_Unshelve,404440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almHighHigh.SCmd_Suppress,404440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almHighHigh.SCmd_UnSuppress,404441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almHighHigh.AEShelveTMRDN,404441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almHighHigh.Bad,404441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almHighHigh.Suppress,404442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.UnSuppress,404442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Shelve,404442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.UnShelve,404442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Enable,404442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Disable,404442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Ack,404442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Reset,404442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Suppressed,404442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Shelved,404442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Disabled,404442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Acked,404442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almHighHigh.Alarm,404442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Fault,404452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almHigh.AlarmState,404452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almHigh.GlobalReset,404452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almHigh.FaultInAlarm,404452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almHigh.ALRM,404452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almHigh.ANUN,404452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almHigh.AKED,404452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almHigh.Resetable,404452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almHigh.REST,404452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almHigh.ACKN,404452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almHigh.UACK,404452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almHigh.MCmd_Enable,404452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almHigh.MCmd_Disable,404452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almHigh.OCmd_Shelve,404452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almHigh.OCmd_Unshelve,404452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almHigh.SCmd_Suppress,404452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almHigh.SCmd_UnSuppress,404453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almHigh.AEShelveTMRDN,404453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almHigh.Bad,404453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almHigh.Suppress,404454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.UnSuppress,404454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Shelve,404454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.UnShelve,404454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Enable,404454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Disable,404454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Ack,404454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Reset,404454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almHigh.Suppressed,404454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almHigh.Shelved,404454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almHigh.Disabled,404454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almHigh.Acked,404454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almHigh.Alarm,404454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Fault,404464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almLow.AlarmState,404464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almLow.GlobalReset,404464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almLow.FaultInAlarm,404464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almLow.ALRM,404464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almLow.ANUN,404464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almLow.AKED,404464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almLow.Resetable,404464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almLow.REST,404464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almLow.ACKN,404464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almLow.UACK,404464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almLow.MCmd_Enable,404464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almLow.MCmd_Disable,404464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almLow.OCmd_Shelve,404464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almLow.OCmd_Unshelve,404464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almLow.SCmd_Suppress,404464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almLow.SCmd_UnSuppress,404465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almLow.AEShelveTMRDN,404465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almLow.Bad,404465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almLow.Suppress,404466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.UnSuppress,404466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Shelve,404466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.UnShelve,404466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Enable,404466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Disable,404466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Ack,404466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Reset,404466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almLow.Suppressed,404466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almLow.Shelved,404466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almLow.Disabled,404466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almLow.Acked,404466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almLow.Alarm,404466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Fault,404476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almLowLow.AlarmState,404476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almLowLow.GlobalReset,404476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almLowLow.FaultInAlarm,404476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almLowLow.ALRM,404476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almLowLow.ANUN,404476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almLowLow.AKED,404476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almLowLow.Resetable,404476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almLowLow.REST,404476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almLowLow.ACKN,404476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almLowLow.UACK,404476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almLowLow.MCmd_Enable,404476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almLowLow.MCmd_Disable,404476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almLowLow.OCmd_Shelve,404476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almLowLow.OCmd_Unshelve,404476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almLowLow.SCmd_Suppress,404476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almLowLow.SCmd_UnSuppress,404477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almLowLow.AEShelveTMRDN,404477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almLowLow.Bad,404477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almLowLow.Suppress,404478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.UnSuppress,404478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Shelve,404478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.UnShelve,404478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Enable,404478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Disable,404478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Ack,404478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Reset,404478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almLowLow.Suppressed,404478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almLowLow.Shelved,404478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almLowLow.Disabled,404478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almLowLow.Acked,404478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almLowLow.Alarm,404478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Fault,404488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almBrokenLoop.AlarmState,404488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almBrokenLoop.GlobalReset,404488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almBrokenLoop.FaultInAlarm,404488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almBrokenLoop.ALRM,404488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almBrokenLoop.ANUN,404488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almBrokenLoop.AKED,404488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almBrokenLoop.Resetable,404488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almBrokenLoop.REST,404488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almBrokenLoop.ACKN,404488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almBrokenLoop.UACK,404488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almBrokenLoop.MCmd_Enable,404488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.MCmd_Disable,404488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.OCmd_Shelve,404488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.OCmd_Unshelve,404488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.SCmd_Suppress,404488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.SCmd_UnSuppress,404489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almBrokenLoop.AEShelveTMRDN,404489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almBrokenLoop.Bad,404489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almBrokenLoop.Suppress,404490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.UnSuppress,404490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Shelve,404490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.UnShelve,404490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Enable,404490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Disable,404490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Ack,404490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Reset,404490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Suppressed,404490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Shelved,404490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Disabled,404490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Acked,404490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almBrokenLoop.Alarm,404490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Fault,404500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almOverRange.AlarmState,404500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almOverRange.GlobalReset,404500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almOverRange.FaultInAlarm,404500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almOverRange.ALRM,404500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almOverRange.ANUN,404500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almOverRange.AKED,404500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almOverRange.Resetable,404500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almOverRange.REST,404500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almOverRange.ACKN,404500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almOverRange.UACK,404500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almOverRange.MCmd_Enable,404500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almOverRange.MCmd_Disable,404500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almOverRange.OCmd_Shelve,404500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almOverRange.OCmd_Unshelve,404500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almOverRange.SCmd_Suppress,404500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almOverRange.SCmd_UnSuppress,404501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almOverRange.AEShelveTMRDN,404501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almOverRange.Bad,404501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almOverRange.Suppress,404502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.UnSuppress,404502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Shelve,404502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.UnShelve,404502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Enable,404502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Disable,404502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Ack,404502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Reset,404502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almOverRange.Suppressed,404502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almOverRange.Shelved,404502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almOverRange.Disabled,404502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almOverRange.Acked,404502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almOverRange.Alarm,404502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Fault,404512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almUnderRange.AlarmState,404512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almUnderRange.GlobalReset,404512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almUnderRange.FaultInAlarm,404512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almUnderRange.ALRM,404512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almUnderRange.ANUN,404512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almUnderRange.AKED,404512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almUnderRange.Resetable,404512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almUnderRange.REST,404512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almUnderRange.ACKN,404512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almUnderRange.UACK,404512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almUnderRange.MCmd_Enable,404512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almUnderRange.MCmd_Disable,404512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almUnderRange.OCmd_Shelve,404512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almUnderRange.OCmd_Unshelve,404512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almUnderRange.SCmd_Suppress,404512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almUnderRange.SCmd_UnSuppress,404513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almUnderRange.AEShelveTMRDN,404513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almUnderRange.Bad,404513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almUnderRange.Suppress,404514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.UnSuppress,404514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Shelve,404514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.UnShelve,404514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Enable,404514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Disable,404514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Ack,404514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Reset,404514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Suppressed,404514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Shelved,404514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Disabled,404514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Acked,404514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almUnderRange.Alarm,404514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Fault,404524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almRateOfChange.AlarmState,404524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almRateOfChange.GlobalReset,404524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almRateOfChange.FaultInAlarm,404524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almRateOfChange.ALRM,404524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almRateOfChange.ANUN,404524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almRateOfChange.AKED,404524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almRateOfChange.Resetable,404524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almRateOfChange.REST,404524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almRateOfChange.ACKN,404524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almRateOfChange.UACK,404524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almRateOfChange.MCmd_Enable,404524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.MCmd_Disable,404524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.OCmd_Shelve,404524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.OCmd_Unshelve,404524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.SCmd_Suppress,404524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.SCmd_UnSuppress,404525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almRateOfChange.AEShelveTMRDN,404525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almRateOfChange.Bad,404525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almRateOfChange.Suppress,404526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.UnSuppress,404526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Shelve,404526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.UnShelve,404526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Enable,404526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Disable,404526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Ack,404526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Reset,404526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Suppressed,404526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Shelved,404526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Disabled,404526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Acked,404526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almRateOfChange.Alarm,404526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Fault,404536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0116_1_FI9.almPLCFault.AlarmState,404536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0116_1_FI9.almPLCFault.GlobalReset,404536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0116_1_FI9.almPLCFault.FaultInAlarm,404536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0116_1_FI9.almPLCFault.ALRM,404536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0116_1_FI9.almPLCFault.ANUN,404536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0116_1_FI9.almPLCFault.AKED,404536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0116_1_FI9.almPLCFault.Resetable,404536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0116_1_FI9.almPLCFault.REST,404536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0116_1_FI9.almPLCFault.ACKN,404536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0116_1_FI9.almPLCFault.UACK,404536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0116_1_FI9.almPLCFault.MCmd_Enable,404536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0116_1_FI9.almPLCFault.MCmd_Disable,404536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0116_1_FI9.almPLCFault.OCmd_Shelve,404536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0116_1_FI9.almPLCFault.OCmd_Unshelve,404536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0116_1_FI9.almPLCFault.SCmd_Suppress,404536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0116_1_FI9.almPLCFault.SCmd_UnSuppress,404537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0116_1_FI9.almPLCFault.AEShelveTMRDN,404537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0116_1_FI9.almPLCFault.Bad,404537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0116_1_FI9.almPLCFault.Suppress,404538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.UnSuppress,404538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Shelve,404538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.UnShelve,404538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Enable,404538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Disable,404538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Ack,404538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Reset,404538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Suppressed,404538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Shelved,404538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Disabled,404538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Acked,404538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0116_1_FI9.almPLCFault.Alarm,404538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Fault,404640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almHighHigh.AlarmState,404640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almHighHigh.GlobalReset,404640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almHighHigh.FaultInAlarm,404640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almHighHigh.ALRM,404640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almHighHigh.ANUN,404640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almHighHigh.AKED,404640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almHighHigh.Resetable,404640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almHighHigh.REST,404640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almHighHigh.ACKN,404640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almHighHigh.UACK,404640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almHighHigh.MCmd_Enable,404640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.MCmd_Disable,404640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.OCmd_Shelve,404640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.OCmd_Unshelve,404640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.SCmd_Suppress,404640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.SCmd_UnSuppress,404641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almHighHigh.AEShelveTMRDN,404641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almHighHigh.Bad,404641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almHighHigh.Suppress,404642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.UnSuppress,404642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Shelve,404642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.UnShelve,404642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Enable,404642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Disable,404642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Ack,404642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Reset,404642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Suppressed,404642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Shelved,404642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Disabled,404642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Acked,404642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almHighHigh.Alarm,404642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Fault,404652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almHigh.AlarmState,404652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almHigh.GlobalReset,404652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almHigh.FaultInAlarm,404652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almHigh.ALRM,404652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almHigh.ANUN,404652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almHigh.AKED,404652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almHigh.Resetable,404652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almHigh.REST,404652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almHigh.ACKN,404652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almHigh.UACK,404652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almHigh.MCmd_Enable,404652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almHigh.MCmd_Disable,404652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almHigh.OCmd_Shelve,404652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almHigh.OCmd_Unshelve,404652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almHigh.SCmd_Suppress,404652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almHigh.SCmd_UnSuppress,404653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almHigh.AEShelveTMRDN,404653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almHigh.Bad,404653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almHigh.Suppress,404654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.UnSuppress,404654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Shelve,404654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.UnShelve,404654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Enable,404654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Disable,404654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Ack,404654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Reset,404654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Suppressed,404654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Shelved,404654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Disabled,404654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Acked,404654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almHigh.Alarm,404654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Fault,404664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almLow.AlarmState,404664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almLow.GlobalReset,404664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almLow.FaultInAlarm,404664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almLow.ALRM,404664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almLow.ANUN,404664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almLow.AKED,404664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almLow.Resetable,404664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almLow.REST,404664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almLow.ACKN,404664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almLow.UACK,404664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almLow.MCmd_Enable,404664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almLow.MCmd_Disable,404664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almLow.OCmd_Shelve,404664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almLow.OCmd_Unshelve,404664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almLow.SCmd_Suppress,404664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almLow.SCmd_UnSuppress,404665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almLow.AEShelveTMRDN,404665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almLow.Bad,404665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almLow.Suppress,404666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.UnSuppress,404666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Shelve,404666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.UnShelve,404666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Enable,404666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Disable,404666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Ack,404666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Reset,404666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almLow.Suppressed,404666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almLow.Shelved,404666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almLow.Disabled,404666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almLow.Acked,404666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almLow.Alarm,404666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Fault,404676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almLowLow.AlarmState,404676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almLowLow.GlobalReset,404676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almLowLow.FaultInAlarm,404676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almLowLow.ALRM,404676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almLowLow.ANUN,404676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almLowLow.AKED,404676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almLowLow.Resetable,404676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almLowLow.REST,404676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almLowLow.ACKN,404676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almLowLow.UACK,404676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almLowLow.MCmd_Enable,404676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.MCmd_Disable,404676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.OCmd_Shelve,404676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.OCmd_Unshelve,404676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.SCmd_Suppress,404676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.SCmd_UnSuppress,404677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almLowLow.AEShelveTMRDN,404677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almLowLow.Bad,404677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almLowLow.Suppress,404678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.UnSuppress,404678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Shelve,404678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.UnShelve,404678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Enable,404678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Disable,404678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Ack,404678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Reset,404678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Suppressed,404678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Shelved,404678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Disabled,404678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Acked,404678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almLowLow.Alarm,404678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Fault,404688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almBrokenLoop.AlarmState,404688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almBrokenLoop.GlobalReset,404688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almBrokenLoop.FaultInAlarm,404688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almBrokenLoop.ALRM,404688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almBrokenLoop.ANUN,404688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almBrokenLoop.AKED,404688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Resetable,404688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almBrokenLoop.REST,404688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almBrokenLoop.ACKN,404688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almBrokenLoop.UACK,404688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almBrokenLoop.MCmd_Enable,404688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.MCmd_Disable,404688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.OCmd_Shelve,404688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.OCmd_Unshelve,404688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.SCmd_Suppress,404688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.SCmd_UnSuppress,404689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almBrokenLoop.AEShelveTMRDN,404689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Bad,404689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Suppress,404690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.UnSuppress,404690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Shelve,404690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.UnShelve,404690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Enable,404690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Disable,404690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Ack,404690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Reset,404690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Suppressed,404690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Shelved,404690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Disabled,404690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Acked,404690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.Alarm,404690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Fault,404700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almOverRange.AlarmState,404700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almOverRange.GlobalReset,404700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almOverRange.FaultInAlarm,404700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almOverRange.ALRM,404700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almOverRange.ANUN,404700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almOverRange.AKED,404700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almOverRange.Resetable,404700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almOverRange.REST,404700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almOverRange.ACKN,404700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almOverRange.UACK,404700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almOverRange.MCmd_Enable,404700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.MCmd_Disable,404700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.OCmd_Shelve,404700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.OCmd_Unshelve,404700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.SCmd_Suppress,404700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.SCmd_UnSuppress,404701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almOverRange.AEShelveTMRDN,404701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almOverRange.Bad,404701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almOverRange.Suppress,404702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.UnSuppress,404702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Shelve,404702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.UnShelve,404702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Enable,404702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Disable,404702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Ack,404702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Reset,404702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Suppressed,404702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Shelved,404702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Disabled,404702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Acked,404702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almOverRange.Alarm,404702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Fault,404712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almUnderRange.AlarmState,404712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almUnderRange.GlobalReset,404712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almUnderRange.FaultInAlarm,404712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almUnderRange.ALRM,404712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almUnderRange.ANUN,404712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almUnderRange.AKED,404712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almUnderRange.Resetable,404712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almUnderRange.REST,404712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almUnderRange.ACKN,404712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almUnderRange.UACK,404712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almUnderRange.MCmd_Enable,404712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.MCmd_Disable,404712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.OCmd_Shelve,404712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.OCmd_Unshelve,404712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.SCmd_Suppress,404712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.SCmd_UnSuppress,404713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almUnderRange.AEShelveTMRDN,404713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almUnderRange.Bad,404713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almUnderRange.Suppress,404714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.UnSuppress,404714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Shelve,404714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.UnShelve,404714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Enable,404714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Disable,404714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Ack,404714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Reset,404714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Suppressed,404714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Shelved,404714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Disabled,404714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Acked,404714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almUnderRange.Alarm,404714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Fault,404724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almRateOfChange.AlarmState,404724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almRateOfChange.GlobalReset,404724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almRateOfChange.FaultInAlarm,404724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almRateOfChange.ALRM,404724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almRateOfChange.ANUN,404724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almRateOfChange.AKED,404724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almRateOfChange.Resetable,404724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almRateOfChange.REST,404724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almRateOfChange.ACKN,404724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almRateOfChange.UACK,404724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almRateOfChange.MCmd_Enable,404724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.MCmd_Disable,404724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.OCmd_Shelve,404724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.OCmd_Unshelve,404724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.SCmd_Suppress,404724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.SCmd_UnSuppress,404725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almRateOfChange.AEShelveTMRDN,404725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almRateOfChange.Bad,404725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almRateOfChange.Suppress,404726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.UnSuppress,404726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Shelve,404726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.UnShelve,404726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Enable,404726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Disable,404726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Ack,404726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Reset,404726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Suppressed,404726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Shelved,404726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Disabled,404726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Acked,404726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.Alarm,404726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Fault,404736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_ZI.almPLCFault.AlarmState,404736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_ZI.almPLCFault.GlobalReset,404736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_ZI.almPLCFault.FaultInAlarm,404736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_ZI.almPLCFault.ALRM,404736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_ZI.almPLCFault.ANUN,404736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_ZI.almPLCFault.AKED,404736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_ZI.almPLCFault.Resetable,404736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_ZI.almPLCFault.REST,404736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_ZI.almPLCFault.ACKN,404736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_ZI.almPLCFault.UACK,404736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_ZI.almPLCFault.MCmd_Enable,404736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.MCmd_Disable,404736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.OCmd_Shelve,404736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.OCmd_Unshelve,404736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.SCmd_Suppress,404736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.SCmd_UnSuppress,404737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_ZI.almPLCFault.AEShelveTMRDN,404737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_ZI.almPLCFault.Bad,404737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_ZI.almPLCFault.Suppress,404738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.UnSuppress,404738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Shelve,404738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.UnShelve,404738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Enable,404738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Disable,404738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Ack,404738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Reset,404738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Suppressed,404738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Shelved,404738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Disabled,404738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Acked,404738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_ZI.almPLCFault.Alarm,404738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Fault,404840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almHighHigh.AlarmState,404840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almHighHigh.GlobalReset,404840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almHighHigh.FaultInAlarm,404840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almHighHigh.ALRM,404840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almHighHigh.ANUN,404840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almHighHigh.AKED,404840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almHighHigh.Resetable,404840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almHighHigh.REST,404840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almHighHigh.ACKN,404840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almHighHigh.UACK,404840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almHighHigh.MCmd_Enable,404840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.MCmd_Disable,404840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.OCmd_Shelve,404840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.OCmd_Unshelve,404840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.SCmd_Suppress,404840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.SCmd_UnSuppress,404841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almHighHigh.AEShelveTMRDN,404841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almHighHigh.Bad,404841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almHighHigh.Suppress,404842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.UnSuppress,404842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Shelve,404842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.UnShelve,404842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Enable,404842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Disable,404842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Ack,404842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Reset,404842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Suppressed,404842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Shelved,404842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Disabled,404842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Acked,404842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almHighHigh.Alarm,404842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Fault,404852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almHigh.AlarmState,404852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almHigh.GlobalReset,404852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almHigh.FaultInAlarm,404852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almHigh.ALRM,404852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almHigh.ANUN,404852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almHigh.AKED,404852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almHigh.Resetable,404852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almHigh.REST,404852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almHigh.ACKN,404852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almHigh.UACK,404852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almHigh.MCmd_Enable,404852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almHigh.MCmd_Disable,404852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almHigh.OCmd_Shelve,404852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almHigh.OCmd_Unshelve,404852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almHigh.SCmd_Suppress,404852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almHigh.SCmd_UnSuppress,404853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almHigh.AEShelveTMRDN,404853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almHigh.Bad,404853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almHigh.Suppress,404854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.UnSuppress,404854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Shelve,404854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.UnShelve,404854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Enable,404854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Disable,404854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Ack,404854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Reset,404854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Suppressed,404854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Shelved,404854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Disabled,404854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Acked,404854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almHigh.Alarm,404854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Fault,404864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almLow.AlarmState,404864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almLow.GlobalReset,404864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almLow.FaultInAlarm,404864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almLow.ALRM,404864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almLow.ANUN,404864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almLow.AKED,404864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almLow.Resetable,404864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almLow.REST,404864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almLow.ACKN,404864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almLow.UACK,404864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almLow.MCmd_Enable,404864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almLow.MCmd_Disable,404864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almLow.OCmd_Shelve,404864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almLow.OCmd_Unshelve,404864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almLow.SCmd_Suppress,404864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almLow.SCmd_UnSuppress,404865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almLow.AEShelveTMRDN,404865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almLow.Bad,404865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almLow.Suppress,404866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.UnSuppress,404866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Shelve,404866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.UnShelve,404866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Enable,404866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Disable,404866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Ack,404866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Reset,404866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almLow.Suppressed,404866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almLow.Shelved,404866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almLow.Disabled,404866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almLow.Acked,404866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almLow.Alarm,404866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Fault,404876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almLowLow.AlarmState,404876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almLowLow.GlobalReset,404876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almLowLow.FaultInAlarm,404876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almLowLow.ALRM,404876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almLowLow.ANUN,404876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almLowLow.AKED,404876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almLowLow.Resetable,404876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almLowLow.REST,404876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almLowLow.ACKN,404876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almLowLow.UACK,404876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almLowLow.MCmd_Enable,404876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.MCmd_Disable,404876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.OCmd_Shelve,404876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.OCmd_Unshelve,404876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.SCmd_Suppress,404876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.SCmd_UnSuppress,404877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almLowLow.AEShelveTMRDN,404877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almLowLow.Bad,404877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almLowLow.Suppress,404878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.UnSuppress,404878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Shelve,404878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.UnShelve,404878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Enable,404878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Disable,404878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Ack,404878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Reset,404878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Suppressed,404878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Shelved,404878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Disabled,404878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Acked,404878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almLowLow.Alarm,404878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Fault,404888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almBrokenLoop.AlarmState,404888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almBrokenLoop.GlobalReset,404888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almBrokenLoop.FaultInAlarm,404888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almBrokenLoop.ALRM,404888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almBrokenLoop.ANUN,404888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almBrokenLoop.AKED,404888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Resetable,404888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almBrokenLoop.REST,404888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almBrokenLoop.ACKN,404888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almBrokenLoop.UACK,404888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almBrokenLoop.MCmd_Enable,404888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.MCmd_Disable,404888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.OCmd_Shelve,404888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.OCmd_Unshelve,404888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.SCmd_Suppress,404888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.SCmd_UnSuppress,404889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almBrokenLoop.AEShelveTMRDN,404889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Bad,404889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Suppress,404890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.UnSuppress,404890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Shelve,404890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.UnShelve,404890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Enable,404890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Disable,404890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Ack,404890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Reset,404890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Suppressed,404890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Shelved,404890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Disabled,404890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Acked,404890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.Alarm,404890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Fault,404900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almOverRange.AlarmState,404900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almOverRange.GlobalReset,404900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almOverRange.FaultInAlarm,404900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almOverRange.ALRM,404900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almOverRange.ANUN,404900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almOverRange.AKED,404900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almOverRange.Resetable,404900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almOverRange.REST,404900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almOverRange.ACKN,404900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almOverRange.UACK,404900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almOverRange.MCmd_Enable,404900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.MCmd_Disable,404900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.OCmd_Shelve,404900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.OCmd_Unshelve,404900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.SCmd_Suppress,404900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.SCmd_UnSuppress,404901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almOverRange.AEShelveTMRDN,404901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almOverRange.Bad,404901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almOverRange.Suppress,404902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.UnSuppress,404902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Shelve,404902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.UnShelve,404902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Enable,404902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Disable,404902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Ack,404902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Reset,404902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Suppressed,404902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Shelved,404902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Disabled,404902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Acked,404902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almOverRange.Alarm,404902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Fault,404912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almUnderRange.AlarmState,404912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almUnderRange.GlobalReset,404912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almUnderRange.FaultInAlarm,404912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almUnderRange.ALRM,404912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almUnderRange.ANUN,404912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almUnderRange.AKED,404912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almUnderRange.Resetable,404912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almUnderRange.REST,404912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almUnderRange.ACKN,404912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almUnderRange.UACK,404912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almUnderRange.MCmd_Enable,404912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.MCmd_Disable,404912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.OCmd_Shelve,404912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.OCmd_Unshelve,404912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.SCmd_Suppress,404912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.SCmd_UnSuppress,404913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almUnderRange.AEShelveTMRDN,404913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almUnderRange.Bad,404913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almUnderRange.Suppress,404914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.UnSuppress,404914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Shelve,404914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.UnShelve,404914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Enable,404914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Disable,404914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Ack,404914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Reset,404914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Suppressed,404914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Shelved,404914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Disabled,404914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Acked,404914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almUnderRange.Alarm,404914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Fault,404924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almRateOfChange.AlarmState,404924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almRateOfChange.GlobalReset,404924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almRateOfChange.FaultInAlarm,404924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almRateOfChange.ALRM,404924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almRateOfChange.ANUN,404924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almRateOfChange.AKED,404924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almRateOfChange.Resetable,404924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almRateOfChange.REST,404924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almRateOfChange.ACKN,404924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almRateOfChange.UACK,404924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almRateOfChange.MCmd_Enable,404924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.MCmd_Disable,404924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.OCmd_Shelve,404924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.OCmd_Unshelve,404924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.SCmd_Suppress,404924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.SCmd_UnSuppress,404925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almRateOfChange.AEShelveTMRDN,404925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almRateOfChange.Bad,404925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almRateOfChange.Suppress,404926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.UnSuppress,404926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Shelve,404926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.UnShelve,404926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Enable,404926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Disable,404926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Ack,404926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Reset,404926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Suppressed,404926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Shelved,404926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Disabled,404926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Acked,404926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.Alarm,404926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Fault,404936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_ZI.almPLCFault.AlarmState,404936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_ZI.almPLCFault.GlobalReset,404936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_ZI.almPLCFault.FaultInAlarm,404936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_ZI.almPLCFault.ALRM,404936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_ZI.almPLCFault.ANUN,404936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_ZI.almPLCFault.AKED,404936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_ZI.almPLCFault.Resetable,404936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_ZI.almPLCFault.REST,404936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_ZI.almPLCFault.ACKN,404936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_ZI.almPLCFault.UACK,404936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_ZI.almPLCFault.MCmd_Enable,404936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.MCmd_Disable,404936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.OCmd_Shelve,404936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.OCmd_Unshelve,404936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.SCmd_Suppress,404936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.SCmd_UnSuppress,404937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_ZI.almPLCFault.AEShelveTMRDN,404937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_ZI.almPLCFault.Bad,404937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_ZI.almPLCFault.Suppress,404938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.UnSuppress,404938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Shelve,404938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.UnShelve,404938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Enable,404938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Disable,404938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Ack,404938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Reset,404938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Suppressed,404938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Shelved,404938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Disabled,404938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Acked,404938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_ZI.almPLCFault.Alarm,404938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Fault,405040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almHighHigh.AlarmState,405040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almHighHigh.GlobalReset,405040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almHighHigh.FaultInAlarm,405040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almHighHigh.ALRM,405040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almHighHigh.ANUN,405040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almHighHigh.AKED,405040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almHighHigh.Resetable,405040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almHighHigh.REST,405040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almHighHigh.ACKN,405040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almHighHigh.UACK,405040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almHighHigh.MCmd_Enable,405040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.MCmd_Disable,405040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.OCmd_Shelve,405040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.OCmd_Unshelve,405040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.SCmd_Suppress,405040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.SCmd_UnSuppress,405041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almHighHigh.AEShelveTMRDN,405041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almHighHigh.Bad,405041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almHighHigh.Suppress,405042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.UnSuppress,405042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Shelve,405042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.UnShelve,405042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Enable,405042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Disable,405042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Ack,405042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Reset,405042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Suppressed,405042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Shelved,405042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Disabled,405042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Acked,405042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almHighHigh.Alarm,405042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Fault,405052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almHigh.AlarmState,405052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almHigh.GlobalReset,405052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almHigh.FaultInAlarm,405052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almHigh.ALRM,405052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almHigh.ANUN,405052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almHigh.AKED,405052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almHigh.Resetable,405052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almHigh.REST,405052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almHigh.ACKN,405052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almHigh.UACK,405052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almHigh.MCmd_Enable,405052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almHigh.MCmd_Disable,405052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almHigh.OCmd_Shelve,405052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almHigh.OCmd_Unshelve,405052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almHigh.SCmd_Suppress,405052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almHigh.SCmd_UnSuppress,405053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almHigh.AEShelveTMRDN,405053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almHigh.Bad,405053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almHigh.Suppress,405054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.UnSuppress,405054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Shelve,405054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.UnShelve,405054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Enable,405054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Disable,405054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Ack,405054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Reset,405054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almHigh.Suppressed,405054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almHigh.Shelved,405054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almHigh.Disabled,405054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almHigh.Acked,405054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almHigh.Alarm,405054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Fault,405064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almLow.AlarmState,405064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almLow.GlobalReset,405064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almLow.FaultInAlarm,405064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almLow.ALRM,405064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almLow.ANUN,405064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almLow.AKED,405064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almLow.Resetable,405064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almLow.REST,405064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almLow.ACKN,405064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almLow.UACK,405064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almLow.MCmd_Enable,405064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almLow.MCmd_Disable,405064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almLow.OCmd_Shelve,405064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almLow.OCmd_Unshelve,405064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almLow.SCmd_Suppress,405064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almLow.SCmd_UnSuppress,405065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almLow.AEShelveTMRDN,405065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almLow.Bad,405065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almLow.Suppress,405066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.UnSuppress,405066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Shelve,405066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.UnShelve,405066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Enable,405066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Disable,405066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Ack,405066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Reset,405066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almLow.Suppressed,405066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almLow.Shelved,405066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almLow.Disabled,405066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almLow.Acked,405066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almLow.Alarm,405066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Fault,405076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almLowLow.AlarmState,405076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almLowLow.GlobalReset,405076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almLowLow.FaultInAlarm,405076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almLowLow.ALRM,405076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almLowLow.ANUN,405076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almLowLow.AKED,405076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almLowLow.Resetable,405076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almLowLow.REST,405076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almLowLow.ACKN,405076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almLowLow.UACK,405076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almLowLow.MCmd_Enable,405076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almLowLow.MCmd_Disable,405076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almLowLow.OCmd_Shelve,405076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almLowLow.OCmd_Unshelve,405076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almLowLow.SCmd_Suppress,405076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almLowLow.SCmd_UnSuppress,405077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almLowLow.AEShelveTMRDN,405077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almLowLow.Bad,405077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almLowLow.Suppress,405078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.UnSuppress,405078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Shelve,405078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.UnShelve,405078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Enable,405078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Disable,405078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Ack,405078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Reset,405078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Suppressed,405078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Shelved,405078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Disabled,405078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Acked,405078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almLowLow.Alarm,405078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Fault,405088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almBrokenLoop.AlarmState,405088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almBrokenLoop.GlobalReset,405088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almBrokenLoop.FaultInAlarm,405088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almBrokenLoop.ALRM,405088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almBrokenLoop.ANUN,405088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almBrokenLoop.AKED,405088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almBrokenLoop.Resetable,405088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almBrokenLoop.REST,405088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almBrokenLoop.ACKN,405088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almBrokenLoop.UACK,405088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almBrokenLoop.MCmd_Enable,405088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.MCmd_Disable,405088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.OCmd_Shelve,405088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.OCmd_Unshelve,405088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.SCmd_Suppress,405088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.SCmd_UnSuppress,405089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almBrokenLoop.AEShelveTMRDN,405089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almBrokenLoop.Bad,405089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almBrokenLoop.Suppress,405090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.UnSuppress,405090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Shelve,405090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.UnShelve,405090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Enable,405090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Disable,405090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Ack,405090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Reset,405090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Suppressed,405090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Shelved,405090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Disabled,405090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Acked,405090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.Alarm,405090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Fault,405100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almOverRange.AlarmState,405100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almOverRange.GlobalReset,405100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almOverRange.FaultInAlarm,405100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almOverRange.ALRM,405100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almOverRange.ANUN,405100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almOverRange.AKED,405100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almOverRange.Resetable,405100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almOverRange.REST,405100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almOverRange.ACKN,405100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almOverRange.UACK,405100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almOverRange.MCmd_Enable,405100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almOverRange.MCmd_Disable,405100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almOverRange.OCmd_Shelve,405100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almOverRange.OCmd_Unshelve,405100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almOverRange.SCmd_Suppress,405100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almOverRange.SCmd_UnSuppress,405101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almOverRange.AEShelveTMRDN,405101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almOverRange.Bad,405101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almOverRange.Suppress,405102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.UnSuppress,405102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Shelve,405102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.UnShelve,405102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Enable,405102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Disable,405102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Ack,405102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Reset,405102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Suppressed,405102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Shelved,405102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Disabled,405102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Acked,405102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almOverRange.Alarm,405102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Fault,405112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almUnderRange.AlarmState,405112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almUnderRange.GlobalReset,405112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almUnderRange.FaultInAlarm,405112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almUnderRange.ALRM,405112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almUnderRange.ANUN,405112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almUnderRange.AKED,405112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almUnderRange.Resetable,405112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almUnderRange.REST,405112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almUnderRange.ACKN,405112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almUnderRange.UACK,405112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almUnderRange.MCmd_Enable,405112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.MCmd_Disable,405112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.OCmd_Shelve,405112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.OCmd_Unshelve,405112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.SCmd_Suppress,405112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.SCmd_UnSuppress,405113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almUnderRange.AEShelveTMRDN,405113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almUnderRange.Bad,405113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almUnderRange.Suppress,405114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.UnSuppress,405114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Shelve,405114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.UnShelve,405114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Enable,405114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Disable,405114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Ack,405114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Reset,405114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Suppressed,405114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Shelved,405114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Disabled,405114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Acked,405114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almUnderRange.Alarm,405114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Fault,405124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almRateOfChange.AlarmState,405124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almRateOfChange.GlobalReset,405124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almRateOfChange.FaultInAlarm,405124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almRateOfChange.ALRM,405124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almRateOfChange.ANUN,405124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almRateOfChange.AKED,405124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almRateOfChange.Resetable,405124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almRateOfChange.REST,405124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almRateOfChange.ACKN,405124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almRateOfChange.UACK,405124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almRateOfChange.MCmd_Enable,405124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.MCmd_Disable,405124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.OCmd_Shelve,405124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.OCmd_Unshelve,405124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.SCmd_Suppress,405124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.SCmd_UnSuppress,405125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almRateOfChange.AEShelveTMRDN,405125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almRateOfChange.Bad,405125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almRateOfChange.Suppress,405126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.UnSuppress,405126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Shelve,405126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.UnShelve,405126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Enable,405126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Disable,405126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Ack,405126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Reset,405126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Suppressed,405126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Shelved,405126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Disabled,405126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Acked,405126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almRateOfChange.Alarm,405126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Fault,405136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FIT_0113_2A_FI.almPLCFault.AlarmState,405136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FIT_0113_2A_FI.almPLCFault.GlobalReset,405136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FIT_0113_2A_FI.almPLCFault.FaultInAlarm,405136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FIT_0113_2A_FI.almPLCFault.ALRM,405136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FIT_0113_2A_FI.almPLCFault.ANUN,405136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FIT_0113_2A_FI.almPLCFault.AKED,405136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FIT_0113_2A_FI.almPLCFault.Resetable,405136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FIT_0113_2A_FI.almPLCFault.REST,405136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FIT_0113_2A_FI.almPLCFault.ACKN,405136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FIT_0113_2A_FI.almPLCFault.UACK,405136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FIT_0113_2A_FI.almPLCFault.MCmd_Enable,405136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.MCmd_Disable,405136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.OCmd_Shelve,405136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.OCmd_Unshelve,405136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.SCmd_Suppress,405136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.SCmd_UnSuppress,405137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FIT_0113_2A_FI.almPLCFault.AEShelveTMRDN,405137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FIT_0113_2A_FI.almPLCFault.Bad,405137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FIT_0113_2A_FI.almPLCFault.Suppress,405138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.UnSuppress,405138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Shelve,405138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.UnShelve,405138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Enable,405138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Disable,405138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Ack,405138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Reset,405138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Suppressed,405138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Shelved,405138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Disabled,405138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Acked,405138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FIT_0113_2A_FI.almPLCFault.Alarm,405138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Fault,405240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almHighHigh.AlarmState,405240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almHighHigh.GlobalReset,405240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almHighHigh.FaultInAlarm,405240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almHighHigh.ALRM,405240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almHighHigh.ANUN,405240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almHighHigh.AKED,405240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almHighHigh.Resetable,405240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almHighHigh.REST,405240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almHighHigh.ACKN,405240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almHighHigh.UACK,405240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almHighHigh.MCmd_Enable,405240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.MCmd_Disable,405240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.OCmd_Shelve,405240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.OCmd_Unshelve,405240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.SCmd_Suppress,405240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.SCmd_UnSuppress,405241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almHighHigh.AEShelveTMRDN,405241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almHighHigh.Bad,405241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almHighHigh.Suppress,405242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.UnSuppress,405242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Shelve,405242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.UnShelve,405242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Enable,405242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Disable,405242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Ack,405242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Reset,405242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Suppressed,405242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Shelved,405242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Disabled,405242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Acked,405242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almHighHigh.Alarm,405242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Fault,405252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almHigh.AlarmState,405252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almHigh.GlobalReset,405252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almHigh.FaultInAlarm,405252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almHigh.ALRM,405252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almHigh.ANUN,405252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almHigh.AKED,405252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almHigh.Resetable,405252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almHigh.REST,405252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almHigh.ACKN,405252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almHigh.UACK,405252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almHigh.MCmd_Enable,405252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almHigh.MCmd_Disable,405252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almHigh.OCmd_Shelve,405252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almHigh.OCmd_Unshelve,405252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almHigh.SCmd_Suppress,405252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almHigh.SCmd_UnSuppress,405253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almHigh.AEShelveTMRDN,405253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almHigh.Bad,405253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almHigh.Suppress,405254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.UnSuppress,405254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Shelve,405254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.UnShelve,405254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Enable,405254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Disable,405254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Ack,405254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Reset,405254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almHigh.Suppressed,405254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almHigh.Shelved,405254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almHigh.Disabled,405254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almHigh.Acked,405254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almHigh.Alarm,405254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Fault,405264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almLow.AlarmState,405264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almLow.GlobalReset,405264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almLow.FaultInAlarm,405264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almLow.ALRM,405264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almLow.ANUN,405264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almLow.AKED,405264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almLow.Resetable,405264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almLow.REST,405264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almLow.ACKN,405264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almLow.UACK,405264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almLow.MCmd_Enable,405264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almLow.MCmd_Disable,405264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almLow.OCmd_Shelve,405264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almLow.OCmd_Unshelve,405264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almLow.SCmd_Suppress,405264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almLow.SCmd_UnSuppress,405265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almLow.AEShelveTMRDN,405265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almLow.Bad,405265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almLow.Suppress,405266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.UnSuppress,405266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Shelve,405266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.UnShelve,405266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Enable,405266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Disable,405266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Ack,405266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Reset,405266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almLow.Suppressed,405266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almLow.Shelved,405266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almLow.Disabled,405266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almLow.Acked,405266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almLow.Alarm,405266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Fault,405276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almLowLow.AlarmState,405276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almLowLow.GlobalReset,405276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almLowLow.FaultInAlarm,405276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almLowLow.ALRM,405276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almLowLow.ANUN,405276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almLowLow.AKED,405276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almLowLow.Resetable,405276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almLowLow.REST,405276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almLowLow.ACKN,405276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almLowLow.UACK,405276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almLowLow.MCmd_Enable,405276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almLowLow.MCmd_Disable,405276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almLowLow.OCmd_Shelve,405276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almLowLow.OCmd_Unshelve,405276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almLowLow.SCmd_Suppress,405276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almLowLow.SCmd_UnSuppress,405277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almLowLow.AEShelveTMRDN,405277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almLowLow.Bad,405277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almLowLow.Suppress,405278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.UnSuppress,405278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Shelve,405278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.UnShelve,405278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Enable,405278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Disable,405278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Ack,405278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Reset,405278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Suppressed,405278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Shelved,405278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Disabled,405278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Acked,405278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almLowLow.Alarm,405278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Fault,405288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almBrokenLoop.AlarmState,405288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almBrokenLoop.GlobalReset,405288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almBrokenLoop.FaultInAlarm,405288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almBrokenLoop.ALRM,405288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almBrokenLoop.ANUN,405288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almBrokenLoop.AKED,405288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almBrokenLoop.Resetable,405288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almBrokenLoop.REST,405288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almBrokenLoop.ACKN,405288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almBrokenLoop.UACK,405288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almBrokenLoop.MCmd_Enable,405288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.MCmd_Disable,405288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.OCmd_Shelve,405288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.OCmd_Unshelve,405288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.SCmd_Suppress,405288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.SCmd_UnSuppress,405289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almBrokenLoop.AEShelveTMRDN,405289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almBrokenLoop.Bad,405289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almBrokenLoop.Suppress,405290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.UnSuppress,405290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Shelve,405290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.UnShelve,405290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Enable,405290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Disable,405290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Ack,405290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Reset,405290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Suppressed,405290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Shelved,405290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Disabled,405290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Acked,405290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.Alarm,405290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Fault,405300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almOverRange.AlarmState,405300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almOverRange.GlobalReset,405300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almOverRange.FaultInAlarm,405300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almOverRange.ALRM,405300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almOverRange.ANUN,405300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almOverRange.AKED,405300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almOverRange.Resetable,405300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almOverRange.REST,405300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almOverRange.ACKN,405300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almOverRange.UACK,405300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almOverRange.MCmd_Enable,405300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almOverRange.MCmd_Disable,405300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almOverRange.OCmd_Shelve,405300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almOverRange.OCmd_Unshelve,405300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almOverRange.SCmd_Suppress,405300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almOverRange.SCmd_UnSuppress,405301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almOverRange.AEShelveTMRDN,405301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almOverRange.Bad,405301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almOverRange.Suppress,405302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.UnSuppress,405302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Shelve,405302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.UnShelve,405302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Enable,405302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Disable,405302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Ack,405302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Reset,405302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Suppressed,405302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Shelved,405302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Disabled,405302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Acked,405302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almOverRange.Alarm,405302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Fault,405312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almUnderRange.AlarmState,405312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almUnderRange.GlobalReset,405312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almUnderRange.FaultInAlarm,405312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almUnderRange.ALRM,405312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almUnderRange.ANUN,405312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almUnderRange.AKED,405312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almUnderRange.Resetable,405312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almUnderRange.REST,405312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almUnderRange.ACKN,405312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almUnderRange.UACK,405312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almUnderRange.MCmd_Enable,405312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.MCmd_Disable,405312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.OCmd_Shelve,405312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.OCmd_Unshelve,405312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.SCmd_Suppress,405312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.SCmd_UnSuppress,405313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almUnderRange.AEShelveTMRDN,405313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almUnderRange.Bad,405313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almUnderRange.Suppress,405314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.UnSuppress,405314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Shelve,405314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.UnShelve,405314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Enable,405314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Disable,405314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Ack,405314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Reset,405314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Suppressed,405314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Shelved,405314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Disabled,405314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Acked,405314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almUnderRange.Alarm,405314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Fault,405324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almRateOfChange.AlarmState,405324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almRateOfChange.GlobalReset,405324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almRateOfChange.FaultInAlarm,405324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almRateOfChange.ALRM,405324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almRateOfChange.ANUN,405324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almRateOfChange.AKED,405324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almRateOfChange.Resetable,405324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almRateOfChange.REST,405324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almRateOfChange.ACKN,405324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almRateOfChange.UACK,405324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almRateOfChange.MCmd_Enable,405324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.MCmd_Disable,405324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.OCmd_Shelve,405324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.OCmd_Unshelve,405324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.SCmd_Suppress,405324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.SCmd_UnSuppress,405325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almRateOfChange.AEShelveTMRDN,405325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almRateOfChange.Bad,405325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almRateOfChange.Suppress,405326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.UnSuppress,405326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Shelve,405326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.UnShelve,405326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Enable,405326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Disable,405326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Ack,405326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Reset,405326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Suppressed,405326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Shelved,405326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Disabled,405326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Acked,405326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almRateOfChange.Alarm,405326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Fault,405336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZI.almPLCFault.AlarmState,405336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZI.almPLCFault.GlobalReset,405336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZI.almPLCFault.FaultInAlarm,405336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZI.almPLCFault.ALRM,405336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZI.almPLCFault.ANUN,405336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZI.almPLCFault.AKED,405336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZI.almPLCFault.Resetable,405336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZI.almPLCFault.REST,405336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZI.almPLCFault.ACKN,405336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZI.almPLCFault.UACK,405336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZI.almPLCFault.MCmd_Enable,405336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.MCmd_Disable,405336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.OCmd_Shelve,405336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.OCmd_Unshelve,405336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.SCmd_Suppress,405336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.SCmd_UnSuppress,405337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZI.almPLCFault.AEShelveTMRDN,405337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZI.almPLCFault.Bad,405337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZI.almPLCFault.Suppress,405338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.UnSuppress,405338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Shelve,405338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.UnShelve,405338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Enable,405338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Disable,405338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Ack,405338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Reset,405338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Suppressed,405338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Shelved,405338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Disabled,405338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Acked,405338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZI.almPLCFault.Alarm,405338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Fault,405440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almHighHigh.AlarmState,405440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almHighHigh.GlobalReset,405440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almHighHigh.FaultInAlarm,405440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almHighHigh.ALRM,405440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almHighHigh.ANUN,405440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almHighHigh.AKED,405440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almHighHigh.Resetable,405440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almHighHigh.REST,405440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almHighHigh.ACKN,405440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almHighHigh.UACK,405440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almHighHigh.MCmd_Enable,405440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.MCmd_Disable,405440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.OCmd_Shelve,405440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.OCmd_Unshelve,405440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.SCmd_Suppress,405440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.SCmd_UnSuppress,405441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almHighHigh.AEShelveTMRDN,405441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almHighHigh.Bad,405441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almHighHigh.Suppress,405442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.UnSuppress,405442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Shelve,405442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.UnShelve,405442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Enable,405442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Disable,405442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Ack,405442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Reset,405442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Suppressed,405442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Shelved,405442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Disabled,405442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Acked,405442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almHighHigh.Alarm,405442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Fault,405452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almHigh.AlarmState,405452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almHigh.GlobalReset,405452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almHigh.FaultInAlarm,405452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almHigh.ALRM,405452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almHigh.ANUN,405452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almHigh.AKED,405452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almHigh.Resetable,405452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almHigh.REST,405452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almHigh.ACKN,405452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almHigh.UACK,405452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almHigh.MCmd_Enable,405452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almHigh.MCmd_Disable,405452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almHigh.OCmd_Shelve,405452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almHigh.OCmd_Unshelve,405452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almHigh.SCmd_Suppress,405452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almHigh.SCmd_UnSuppress,405453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almHigh.AEShelveTMRDN,405453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almHigh.Bad,405453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almHigh.Suppress,405454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.UnSuppress,405454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Shelve,405454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.UnShelve,405454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Enable,405454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Disable,405454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Ack,405454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Reset,405454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almHigh.Suppressed,405454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almHigh.Shelved,405454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almHigh.Disabled,405454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almHigh.Acked,405454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almHigh.Alarm,405454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Fault,405464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almLow.AlarmState,405464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almLow.GlobalReset,405464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almLow.FaultInAlarm,405464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almLow.ALRM,405464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almLow.ANUN,405464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almLow.AKED,405464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almLow.Resetable,405464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almLow.REST,405464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almLow.ACKN,405464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almLow.UACK,405464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almLow.MCmd_Enable,405464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almLow.MCmd_Disable,405464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almLow.OCmd_Shelve,405464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almLow.OCmd_Unshelve,405464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almLow.SCmd_Suppress,405464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almLow.SCmd_UnSuppress,405465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almLow.AEShelveTMRDN,405465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almLow.Bad,405465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almLow.Suppress,405466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.UnSuppress,405466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Shelve,405466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.UnShelve,405466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Enable,405466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Disable,405466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Ack,405466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Reset,405466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almLow.Suppressed,405466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almLow.Shelved,405466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almLow.Disabled,405466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almLow.Acked,405466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almLow.Alarm,405466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Fault,405476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almLowLow.AlarmState,405476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almLowLow.GlobalReset,405476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almLowLow.FaultInAlarm,405476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almLowLow.ALRM,405476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almLowLow.ANUN,405476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almLowLow.AKED,405476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almLowLow.Resetable,405476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almLowLow.REST,405476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almLowLow.ACKN,405476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almLowLow.UACK,405476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almLowLow.MCmd_Enable,405476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almLowLow.MCmd_Disable,405476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almLowLow.OCmd_Shelve,405476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almLowLow.OCmd_Unshelve,405476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almLowLow.SCmd_Suppress,405476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almLowLow.SCmd_UnSuppress,405477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almLowLow.AEShelveTMRDN,405477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almLowLow.Bad,405477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almLowLow.Suppress,405478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.UnSuppress,405478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Shelve,405478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.UnShelve,405478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Enable,405478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Disable,405478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Ack,405478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Reset,405478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Suppressed,405478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Shelved,405478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Disabled,405478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Acked,405478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almLowLow.Alarm,405478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Fault,405488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almBrokenLoop.AlarmState,405488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almBrokenLoop.GlobalReset,405488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almBrokenLoop.FaultInAlarm,405488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almBrokenLoop.ALRM,405488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almBrokenLoop.ANUN,405488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almBrokenLoop.AKED,405488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almBrokenLoop.Resetable,405488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almBrokenLoop.REST,405488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almBrokenLoop.ACKN,405488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almBrokenLoop.UACK,405488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almBrokenLoop.MCmd_Enable,405488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.MCmd_Disable,405488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.OCmd_Shelve,405488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.OCmd_Unshelve,405488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.SCmd_Suppress,405488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.SCmd_UnSuppress,405489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almBrokenLoop.AEShelveTMRDN,405489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almBrokenLoop.Bad,405489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almBrokenLoop.Suppress,405490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.UnSuppress,405490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Shelve,405490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.UnShelve,405490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Enable,405490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Disable,405490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Ack,405490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Reset,405490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Suppressed,405490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Shelved,405490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Disabled,405490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Acked,405490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.Alarm,405490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Fault,405500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almOverRange.AlarmState,405500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almOverRange.GlobalReset,405500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almOverRange.FaultInAlarm,405500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almOverRange.ALRM,405500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almOverRange.ANUN,405500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almOverRange.AKED,405500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almOverRange.Resetable,405500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almOverRange.REST,405500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almOverRange.ACKN,405500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almOverRange.UACK,405500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almOverRange.MCmd_Enable,405500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almOverRange.MCmd_Disable,405500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almOverRange.OCmd_Shelve,405500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almOverRange.OCmd_Unshelve,405500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almOverRange.SCmd_Suppress,405500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almOverRange.SCmd_UnSuppress,405501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almOverRange.AEShelveTMRDN,405501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almOverRange.Bad,405501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almOverRange.Suppress,405502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.UnSuppress,405502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Shelve,405502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.UnShelve,405502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Enable,405502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Disable,405502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Ack,405502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Reset,405502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Suppressed,405502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Shelved,405502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Disabled,405502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Acked,405502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almOverRange.Alarm,405502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Fault,405512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almUnderRange.AlarmState,405512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almUnderRange.GlobalReset,405512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almUnderRange.FaultInAlarm,405512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almUnderRange.ALRM,405512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almUnderRange.ANUN,405512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almUnderRange.AKED,405512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almUnderRange.Resetable,405512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almUnderRange.REST,405512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almUnderRange.ACKN,405512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almUnderRange.UACK,405512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almUnderRange.MCmd_Enable,405512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.MCmd_Disable,405512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.OCmd_Shelve,405512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.OCmd_Unshelve,405512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.SCmd_Suppress,405512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.SCmd_UnSuppress,405513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almUnderRange.AEShelveTMRDN,405513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almUnderRange.Bad,405513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almUnderRange.Suppress,405514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.UnSuppress,405514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Shelve,405514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.UnShelve,405514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Enable,405514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Disable,405514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Ack,405514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Reset,405514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Suppressed,405514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Shelved,405514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Disabled,405514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Acked,405514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almUnderRange.Alarm,405514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Fault,405524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almRateOfChange.AlarmState,405524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almRateOfChange.GlobalReset,405524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almRateOfChange.FaultInAlarm,405524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almRateOfChange.ALRM,405524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almRateOfChange.ANUN,405524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almRateOfChange.AKED,405524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almRateOfChange.Resetable,405524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almRateOfChange.REST,405524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almRateOfChange.ACKN,405524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almRateOfChange.UACK,405524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almRateOfChange.MCmd_Enable,405524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.MCmd_Disable,405524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.OCmd_Shelve,405524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.OCmd_Unshelve,405524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.SCmd_Suppress,405524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.SCmd_UnSuppress,405525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almRateOfChange.AEShelveTMRDN,405525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almRateOfChange.Bad,405525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almRateOfChange.Suppress,405526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.UnSuppress,405526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Shelve,405526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.UnShelve,405526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Enable,405526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Disable,405526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Ack,405526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Reset,405526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Suppressed,405526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Shelved,405526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Disabled,405526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Acked,405526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almRateOfChange.Alarm,405526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Fault,405536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZI.almPLCFault.AlarmState,405536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZI.almPLCFault.GlobalReset,405536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZI.almPLCFault.FaultInAlarm,405536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZI.almPLCFault.ALRM,405536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZI.almPLCFault.ANUN,405536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZI.almPLCFault.AKED,405536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZI.almPLCFault.Resetable,405536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZI.almPLCFault.REST,405536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZI.almPLCFault.ACKN,405536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZI.almPLCFault.UACK,405536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZI.almPLCFault.MCmd_Enable,405536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.MCmd_Disable,405536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.OCmd_Shelve,405536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.OCmd_Unshelve,405536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.SCmd_Suppress,405536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.SCmd_UnSuppress,405537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZI.almPLCFault.AEShelveTMRDN,405537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZI.almPLCFault.Bad,405537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZI.almPLCFault.Suppress,405538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.UnSuppress,405538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Shelve,405538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.UnShelve,405538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Enable,405538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Disable,405538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Ack,405538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Reset,405538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Suppressed,405538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Shelved,405538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Disabled,405538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Acked,405538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZI.almPLCFault.Alarm,405538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Fault,405640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almHighHigh.AlarmState,405640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almHighHigh.GlobalReset,405640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almHighHigh.FaultInAlarm,405640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almHighHigh.ALRM,405640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almHighHigh.ANUN,405640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almHighHigh.AKED,405640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almHighHigh.Resetable,405640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almHighHigh.REST,405640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almHighHigh.ACKN,405640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almHighHigh.UACK,405640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almHighHigh.MCmd_Enable,405640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.MCmd_Disable,405640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.OCmd_Shelve,405640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.OCmd_Unshelve,405640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.SCmd_Suppress,405640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.SCmd_UnSuppress,405641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almHighHigh.AEShelveTMRDN,405641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almHighHigh.Bad,405641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almHighHigh.Suppress,405642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.UnSuppress,405642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Shelve,405642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.UnShelve,405642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Enable,405642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Disable,405642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Ack,405642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Reset,405642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Suppressed,405642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Shelved,405642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Disabled,405642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Acked,405642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almHighHigh.Alarm,405642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Fault,405652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almHigh.AlarmState,405652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almHigh.GlobalReset,405652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almHigh.FaultInAlarm,405652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almHigh.ALRM,405652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almHigh.ANUN,405652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almHigh.AKED,405652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almHigh.Resetable,405652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almHigh.REST,405652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almHigh.ACKN,405652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almHigh.UACK,405652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almHigh.MCmd_Enable,405652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almHigh.MCmd_Disable,405652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almHigh.OCmd_Shelve,405652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almHigh.OCmd_Unshelve,405652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almHigh.SCmd_Suppress,405652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almHigh.SCmd_UnSuppress,405653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almHigh.AEShelveTMRDN,405653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almHigh.Bad,405653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almHigh.Suppress,405654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.UnSuppress,405654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Shelve,405654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.UnShelve,405654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Enable,405654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Disable,405654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Ack,405654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Reset,405654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almHigh.Suppressed,405654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almHigh.Shelved,405654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almHigh.Disabled,405654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almHigh.Acked,405654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almHigh.Alarm,405654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Fault,405664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almLow.AlarmState,405664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almLow.GlobalReset,405664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almLow.FaultInAlarm,405664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almLow.ALRM,405664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almLow.ANUN,405664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almLow.AKED,405664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almLow.Resetable,405664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almLow.REST,405664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almLow.ACKN,405664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almLow.UACK,405664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almLow.MCmd_Enable,405664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almLow.MCmd_Disable,405664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almLow.OCmd_Shelve,405664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almLow.OCmd_Unshelve,405664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almLow.SCmd_Suppress,405664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almLow.SCmd_UnSuppress,405665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almLow.AEShelveTMRDN,405665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almLow.Bad,405665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almLow.Suppress,405666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.UnSuppress,405666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Shelve,405666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.UnShelve,405666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Enable,405666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Disable,405666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Ack,405666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Reset,405666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almLow.Suppressed,405666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almLow.Shelved,405666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almLow.Disabled,405666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almLow.Acked,405666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almLow.Alarm,405666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Fault,405676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almLowLow.AlarmState,405676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almLowLow.GlobalReset,405676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almLowLow.FaultInAlarm,405676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almLowLow.ALRM,405676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almLowLow.ANUN,405676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almLowLow.AKED,405676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almLowLow.Resetable,405676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almLowLow.REST,405676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almLowLow.ACKN,405676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almLowLow.UACK,405676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almLowLow.MCmd_Enable,405676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almLowLow.MCmd_Disable,405676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almLowLow.OCmd_Shelve,405676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almLowLow.OCmd_Unshelve,405676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almLowLow.SCmd_Suppress,405676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almLowLow.SCmd_UnSuppress,405677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almLowLow.AEShelveTMRDN,405677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almLowLow.Bad,405677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almLowLow.Suppress,405678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.UnSuppress,405678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Shelve,405678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.UnShelve,405678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Enable,405678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Disable,405678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Ack,405678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Reset,405678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Suppressed,405678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Shelved,405678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Disabled,405678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Acked,405678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almLowLow.Alarm,405678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Fault,405688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almBrokenLoop.AlarmState,405688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almBrokenLoop.GlobalReset,405688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almBrokenLoop.FaultInAlarm,405688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almBrokenLoop.ALRM,405688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almBrokenLoop.ANUN,405688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almBrokenLoop.AKED,405688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almBrokenLoop.Resetable,405688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almBrokenLoop.REST,405688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almBrokenLoop.ACKN,405688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almBrokenLoop.UACK,405688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almBrokenLoop.MCmd_Enable,405688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.MCmd_Disable,405688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.OCmd_Shelve,405688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.OCmd_Unshelve,405688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.SCmd_Suppress,405688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.SCmd_UnSuppress,405689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almBrokenLoop.AEShelveTMRDN,405689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almBrokenLoop.Bad,405689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almBrokenLoop.Suppress,405690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.UnSuppress,405690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Shelve,405690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.UnShelve,405690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Enable,405690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Disable,405690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Ack,405690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Reset,405690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Suppressed,405690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Shelved,405690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Disabled,405690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Acked,405690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.Alarm,405690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Fault,405700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almOverRange.AlarmState,405700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almOverRange.GlobalReset,405700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almOverRange.FaultInAlarm,405700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almOverRange.ALRM,405700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almOverRange.ANUN,405700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almOverRange.AKED,405700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almOverRange.Resetable,405700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almOverRange.REST,405700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almOverRange.ACKN,405700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almOverRange.UACK,405700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almOverRange.MCmd_Enable,405700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almOverRange.MCmd_Disable,405700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almOverRange.OCmd_Shelve,405700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almOverRange.OCmd_Unshelve,405700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almOverRange.SCmd_Suppress,405700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almOverRange.SCmd_UnSuppress,405701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almOverRange.AEShelveTMRDN,405701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almOverRange.Bad,405701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almOverRange.Suppress,405702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.UnSuppress,405702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Shelve,405702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.UnShelve,405702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Enable,405702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Disable,405702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Ack,405702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Reset,405702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Suppressed,405702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Shelved,405702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Disabled,405702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Acked,405702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almOverRange.Alarm,405702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Fault,405712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almUnderRange.AlarmState,405712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almUnderRange.GlobalReset,405712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almUnderRange.FaultInAlarm,405712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almUnderRange.ALRM,405712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almUnderRange.ANUN,405712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almUnderRange.AKED,405712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almUnderRange.Resetable,405712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almUnderRange.REST,405712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almUnderRange.ACKN,405712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almUnderRange.UACK,405712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almUnderRange.MCmd_Enable,405712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.MCmd_Disable,405712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.OCmd_Shelve,405712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.OCmd_Unshelve,405712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.SCmd_Suppress,405712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.SCmd_UnSuppress,405713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almUnderRange.AEShelveTMRDN,405713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almUnderRange.Bad,405713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almUnderRange.Suppress,405714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.UnSuppress,405714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Shelve,405714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.UnShelve,405714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Enable,405714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Disable,405714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Ack,405714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Reset,405714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Suppressed,405714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Shelved,405714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Disabled,405714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Acked,405714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almUnderRange.Alarm,405714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Fault,405724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almRateOfChange.AlarmState,405724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almRateOfChange.GlobalReset,405724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almRateOfChange.FaultInAlarm,405724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almRateOfChange.ALRM,405724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almRateOfChange.ANUN,405724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almRateOfChange.AKED,405724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almRateOfChange.Resetable,405724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almRateOfChange.REST,405724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almRateOfChange.ACKN,405724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almRateOfChange.UACK,405724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almRateOfChange.MCmd_Enable,405724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.MCmd_Disable,405724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.OCmd_Shelve,405724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.OCmd_Unshelve,405724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.SCmd_Suppress,405724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.SCmd_UnSuppress,405725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almRateOfChange.AEShelveTMRDN,405725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almRateOfChange.Bad,405725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almRateOfChange.Suppress,405726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.UnSuppress,405726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Shelve,405726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.UnShelve,405726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Enable,405726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Disable,405726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Ack,405726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Reset,405726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Suppressed,405726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Shelved,405726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Disabled,405726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Acked,405726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almRateOfChange.Alarm,405726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Fault,405736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZI.almPLCFault.AlarmState,405736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZI.almPLCFault.GlobalReset,405736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZI.almPLCFault.FaultInAlarm,405736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZI.almPLCFault.ALRM,405736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZI.almPLCFault.ANUN,405736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZI.almPLCFault.AKED,405736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZI.almPLCFault.Resetable,405736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZI.almPLCFault.REST,405736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZI.almPLCFault.ACKN,405736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZI.almPLCFault.UACK,405736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZI.almPLCFault.MCmd_Enable,405736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.MCmd_Disable,405736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.OCmd_Shelve,405736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.OCmd_Unshelve,405736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.SCmd_Suppress,405736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.SCmd_UnSuppress,405737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZI.almPLCFault.AEShelveTMRDN,405737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZI.almPLCFault.Bad,405737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZI.almPLCFault.Suppress,405738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.UnSuppress,405738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Shelve,405738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.UnShelve,405738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Enable,405738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Disable,405738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Ack,405738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Reset,405738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Suppressed,405738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Shelved,405738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Disabled,405738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Acked,405738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZI.almPLCFault.Alarm,405738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Fault,405840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almHighHigh.AlarmState,405840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almHighHigh.GlobalReset,405840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almHighHigh.FaultInAlarm,405840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almHighHigh.ALRM,405840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almHighHigh.ANUN,405840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almHighHigh.AKED,405840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almHighHigh.Resetable,405840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almHighHigh.REST,405840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almHighHigh.ACKN,405840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almHighHigh.UACK,405840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almHighHigh.MCmd_Enable,405840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.MCmd_Disable,405840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.OCmd_Shelve,405840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.OCmd_Unshelve,405840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.SCmd_Suppress,405840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.SCmd_UnSuppress,405841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almHighHigh.AEShelveTMRDN,405841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almHighHigh.Bad,405841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almHighHigh.Suppress,405842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.UnSuppress,405842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Shelve,405842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.UnShelve,405842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Enable,405842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Disable,405842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Ack,405842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Reset,405842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Suppressed,405842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Shelved,405842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Disabled,405842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Acked,405842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almHighHigh.Alarm,405842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Fault,405852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almHigh.AlarmState,405852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almHigh.GlobalReset,405852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almHigh.FaultInAlarm,405852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almHigh.ALRM,405852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almHigh.ANUN,405852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almHigh.AKED,405852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almHigh.Resetable,405852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almHigh.REST,405852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almHigh.ACKN,405852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almHigh.UACK,405852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almHigh.MCmd_Enable,405852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almHigh.MCmd_Disable,405852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almHigh.OCmd_Shelve,405852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almHigh.OCmd_Unshelve,405852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almHigh.SCmd_Suppress,405852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almHigh.SCmd_UnSuppress,405853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almHigh.AEShelveTMRDN,405853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almHigh.Bad,405853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almHigh.Suppress,405854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.UnSuppress,405854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Shelve,405854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.UnShelve,405854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Enable,405854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Disable,405854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Ack,405854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Reset,405854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almHigh.Suppressed,405854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almHigh.Shelved,405854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almHigh.Disabled,405854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almHigh.Acked,405854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almHigh.Alarm,405854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Fault,405864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almLow.AlarmState,405864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almLow.GlobalReset,405864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almLow.FaultInAlarm,405864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almLow.ALRM,405864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almLow.ANUN,405864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almLow.AKED,405864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almLow.Resetable,405864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almLow.REST,405864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almLow.ACKN,405864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almLow.UACK,405864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almLow.MCmd_Enable,405864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almLow.MCmd_Disable,405864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almLow.OCmd_Shelve,405864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almLow.OCmd_Unshelve,405864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almLow.SCmd_Suppress,405864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almLow.SCmd_UnSuppress,405865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almLow.AEShelveTMRDN,405865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almLow.Bad,405865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almLow.Suppress,405866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.UnSuppress,405866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Shelve,405866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.UnShelve,405866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Enable,405866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Disable,405866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Ack,405866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Reset,405866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almLow.Suppressed,405866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almLow.Shelved,405866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almLow.Disabled,405866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almLow.Acked,405866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almLow.Alarm,405866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Fault,405876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almLowLow.AlarmState,405876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almLowLow.GlobalReset,405876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almLowLow.FaultInAlarm,405876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almLowLow.ALRM,405876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almLowLow.ANUN,405876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almLowLow.AKED,405876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almLowLow.Resetable,405876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almLowLow.REST,405876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almLowLow.ACKN,405876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almLowLow.UACK,405876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almLowLow.MCmd_Enable,405876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almLowLow.MCmd_Disable,405876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almLowLow.OCmd_Shelve,405876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almLowLow.OCmd_Unshelve,405876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almLowLow.SCmd_Suppress,405876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almLowLow.SCmd_UnSuppress,405877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almLowLow.AEShelveTMRDN,405877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almLowLow.Bad,405877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almLowLow.Suppress,405878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.UnSuppress,405878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Shelve,405878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.UnShelve,405878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Enable,405878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Disable,405878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Ack,405878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Reset,405878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Suppressed,405878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Shelved,405878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Disabled,405878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Acked,405878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almLowLow.Alarm,405878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Fault,405888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almBrokenLoop.AlarmState,405888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almBrokenLoop.GlobalReset,405888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almBrokenLoop.FaultInAlarm,405888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almBrokenLoop.ALRM,405888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almBrokenLoop.ANUN,405888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almBrokenLoop.AKED,405888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almBrokenLoop.Resetable,405888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almBrokenLoop.REST,405888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almBrokenLoop.ACKN,405888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almBrokenLoop.UACK,405888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almBrokenLoop.MCmd_Enable,405888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.MCmd_Disable,405888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.OCmd_Shelve,405888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.OCmd_Unshelve,405888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.SCmd_Suppress,405888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.SCmd_UnSuppress,405889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almBrokenLoop.AEShelveTMRDN,405889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almBrokenLoop.Bad,405889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almBrokenLoop.Suppress,405890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.UnSuppress,405890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Shelve,405890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.UnShelve,405890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Enable,405890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Disable,405890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Ack,405890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Reset,405890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Suppressed,405890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Shelved,405890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Disabled,405890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Acked,405890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.Alarm,405890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Fault,405900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almOverRange.AlarmState,405900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almOverRange.GlobalReset,405900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almOverRange.FaultInAlarm,405900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almOverRange.ALRM,405900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almOverRange.ANUN,405900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almOverRange.AKED,405900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almOverRange.Resetable,405900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almOverRange.REST,405900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almOverRange.ACKN,405900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almOverRange.UACK,405900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almOverRange.MCmd_Enable,405900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almOverRange.MCmd_Disable,405900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almOverRange.OCmd_Shelve,405900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almOverRange.OCmd_Unshelve,405900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almOverRange.SCmd_Suppress,405900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almOverRange.SCmd_UnSuppress,405901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almOverRange.AEShelveTMRDN,405901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almOverRange.Bad,405901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almOverRange.Suppress,405902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.UnSuppress,405902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Shelve,405902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.UnShelve,405902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Enable,405902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Disable,405902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Ack,405902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Reset,405902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Suppressed,405902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Shelved,405902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Disabled,405902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Acked,405902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almOverRange.Alarm,405902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Fault,405912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almUnderRange.AlarmState,405912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almUnderRange.GlobalReset,405912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almUnderRange.FaultInAlarm,405912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almUnderRange.ALRM,405912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almUnderRange.ANUN,405912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almUnderRange.AKED,405912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almUnderRange.Resetable,405912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almUnderRange.REST,405912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almUnderRange.ACKN,405912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almUnderRange.UACK,405912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almUnderRange.MCmd_Enable,405912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.MCmd_Disable,405912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.OCmd_Shelve,405912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.OCmd_Unshelve,405912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.SCmd_Suppress,405912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.SCmd_UnSuppress,405913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almUnderRange.AEShelveTMRDN,405913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almUnderRange.Bad,405913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almUnderRange.Suppress,405914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.UnSuppress,405914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Shelve,405914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.UnShelve,405914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Enable,405914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Disable,405914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Ack,405914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Reset,405914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Suppressed,405914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Shelved,405914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Disabled,405914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Acked,405914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almUnderRange.Alarm,405914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Fault,405924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almRateOfChange.AlarmState,405924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almRateOfChange.GlobalReset,405924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almRateOfChange.FaultInAlarm,405924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almRateOfChange.ALRM,405924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almRateOfChange.ANUN,405924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almRateOfChange.AKED,405924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almRateOfChange.Resetable,405924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almRateOfChange.REST,405924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almRateOfChange.ACKN,405924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almRateOfChange.UACK,405924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almRateOfChange.MCmd_Enable,405924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.MCmd_Disable,405924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.OCmd_Shelve,405924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.OCmd_Unshelve,405924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.SCmd_Suppress,405924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.SCmd_UnSuppress,405925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almRateOfChange.AEShelveTMRDN,405925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almRateOfChange.Bad,405925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almRateOfChange.Suppress,405926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.UnSuppress,405926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Shelve,405926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.UnShelve,405926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Enable,405926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Disable,405926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Ack,405926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Reset,405926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Suppressed,405926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Shelved,405926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Disabled,405926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Acked,405926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almRateOfChange.Alarm,405926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Fault,405936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZI.almPLCFault.AlarmState,405936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZI.almPLCFault.GlobalReset,405936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZI.almPLCFault.FaultInAlarm,405936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZI.almPLCFault.ALRM,405936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZI.almPLCFault.ANUN,405936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZI.almPLCFault.AKED,405936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZI.almPLCFault.Resetable,405936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZI.almPLCFault.REST,405936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZI.almPLCFault.ACKN,405936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZI.almPLCFault.UACK,405936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZI.almPLCFault.MCmd_Enable,405936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.MCmd_Disable,405936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.OCmd_Shelve,405936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.OCmd_Unshelve,405936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.SCmd_Suppress,405936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.SCmd_UnSuppress,405937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZI.almPLCFault.AEShelveTMRDN,405937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZI.almPLCFault.Bad,405937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZI.almPLCFault.Suppress,405938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.UnSuppress,405938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Shelve,405938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.UnShelve,405938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Enable,405938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Disable,405938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Ack,405938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Reset,405938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Suppressed,405938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Shelved,405938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Disabled,405938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Acked,405938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZI.almPLCFault.Alarm,405938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Fault,406040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almHighHigh.AlarmState,406040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almHighHigh.GlobalReset,406040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almHighHigh.FaultInAlarm,406040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almHighHigh.ALRM,406040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almHighHigh.ANUN,406040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almHighHigh.AKED,406040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almHighHigh.Resetable,406040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almHighHigh.REST,406040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almHighHigh.ACKN,406040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almHighHigh.UACK,406040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almHighHigh.MCmd_Enable,406040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.MCmd_Disable,406040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.OCmd_Shelve,406040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.OCmd_Unshelve,406040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.SCmd_Suppress,406040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.SCmd_UnSuppress,406041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almHighHigh.AEShelveTMRDN,406041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almHighHigh.Bad,406041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almHighHigh.Suppress,406042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.UnSuppress,406042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Shelve,406042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.UnShelve,406042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Enable,406042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Disable,406042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Ack,406042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Reset,406042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Suppressed,406042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Shelved,406042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Disabled,406042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Acked,406042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almHighHigh.Alarm,406042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Fault,406052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almHigh.AlarmState,406052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almHigh.GlobalReset,406052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almHigh.FaultInAlarm,406052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almHigh.ALRM,406052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almHigh.ANUN,406052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almHigh.AKED,406052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almHigh.Resetable,406052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almHigh.REST,406052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almHigh.ACKN,406052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almHigh.UACK,406052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almHigh.MCmd_Enable,406052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almHigh.MCmd_Disable,406052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almHigh.OCmd_Shelve,406052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almHigh.OCmd_Unshelve,406052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almHigh.SCmd_Suppress,406052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almHigh.SCmd_UnSuppress,406053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almHigh.AEShelveTMRDN,406053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almHigh.Bad,406053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almHigh.Suppress,406054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.UnSuppress,406054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Shelve,406054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.UnShelve,406054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Enable,406054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Disable,406054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Ack,406054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Reset,406054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almHigh.Suppressed,406054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almHigh.Shelved,406054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almHigh.Disabled,406054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almHigh.Acked,406054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almHigh.Alarm,406054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Fault,406064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almLow.AlarmState,406064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almLow.GlobalReset,406064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almLow.FaultInAlarm,406064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almLow.ALRM,406064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almLow.ANUN,406064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almLow.AKED,406064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almLow.Resetable,406064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almLow.REST,406064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almLow.ACKN,406064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almLow.UACK,406064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almLow.MCmd_Enable,406064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almLow.MCmd_Disable,406064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almLow.OCmd_Shelve,406064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almLow.OCmd_Unshelve,406064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almLow.SCmd_Suppress,406064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almLow.SCmd_UnSuppress,406065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almLow.AEShelveTMRDN,406065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almLow.Bad,406065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almLow.Suppress,406066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.UnSuppress,406066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Shelve,406066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.UnShelve,406066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Enable,406066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Disable,406066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Ack,406066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Reset,406066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almLow.Suppressed,406066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almLow.Shelved,406066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almLow.Disabled,406066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almLow.Acked,406066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almLow.Alarm,406066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Fault,406076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almLowLow.AlarmState,406076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almLowLow.GlobalReset,406076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almLowLow.FaultInAlarm,406076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almLowLow.ALRM,406076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almLowLow.ANUN,406076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almLowLow.AKED,406076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almLowLow.Resetable,406076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almLowLow.REST,406076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almLowLow.ACKN,406076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almLowLow.UACK,406076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almLowLow.MCmd_Enable,406076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almLowLow.MCmd_Disable,406076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almLowLow.OCmd_Shelve,406076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almLowLow.OCmd_Unshelve,406076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almLowLow.SCmd_Suppress,406076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almLowLow.SCmd_UnSuppress,406077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almLowLow.AEShelveTMRDN,406077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almLowLow.Bad,406077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almLowLow.Suppress,406078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.UnSuppress,406078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Shelve,406078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.UnShelve,406078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Enable,406078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Disable,406078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Ack,406078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Reset,406078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Suppressed,406078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Shelved,406078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Disabled,406078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Acked,406078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almLowLow.Alarm,406078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Fault,406088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almBrokenLoop.AlarmState,406088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almBrokenLoop.GlobalReset,406088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almBrokenLoop.FaultInAlarm,406088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almBrokenLoop.ALRM,406088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almBrokenLoop.ANUN,406088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almBrokenLoop.AKED,406088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almBrokenLoop.Resetable,406088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almBrokenLoop.REST,406088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almBrokenLoop.ACKN,406088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almBrokenLoop.UACK,406088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almBrokenLoop.MCmd_Enable,406088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.MCmd_Disable,406088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.OCmd_Shelve,406088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.OCmd_Unshelve,406088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.SCmd_Suppress,406088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.SCmd_UnSuppress,406089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almBrokenLoop.AEShelveTMRDN,406089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almBrokenLoop.Bad,406089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almBrokenLoop.Suppress,406090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.UnSuppress,406090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Shelve,406090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.UnShelve,406090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Enable,406090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Disable,406090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Ack,406090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Reset,406090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Suppressed,406090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Shelved,406090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Disabled,406090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Acked,406090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.Alarm,406090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Fault,406100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almOverRange.AlarmState,406100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almOverRange.GlobalReset,406100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almOverRange.FaultInAlarm,406100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almOverRange.ALRM,406100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almOverRange.ANUN,406100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almOverRange.AKED,406100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almOverRange.Resetable,406100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almOverRange.REST,406100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almOverRange.ACKN,406100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almOverRange.UACK,406100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almOverRange.MCmd_Enable,406100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almOverRange.MCmd_Disable,406100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almOverRange.OCmd_Shelve,406100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almOverRange.OCmd_Unshelve,406100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almOverRange.SCmd_Suppress,406100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almOverRange.SCmd_UnSuppress,406101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almOverRange.AEShelveTMRDN,406101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almOverRange.Bad,406101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almOverRange.Suppress,406102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.UnSuppress,406102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Shelve,406102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.UnShelve,406102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Enable,406102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Disable,406102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Ack,406102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Reset,406102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Suppressed,406102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Shelved,406102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Disabled,406102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Acked,406102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almOverRange.Alarm,406102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Fault,406112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almUnderRange.AlarmState,406112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almUnderRange.GlobalReset,406112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almUnderRange.FaultInAlarm,406112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almUnderRange.ALRM,406112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almUnderRange.ANUN,406112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almUnderRange.AKED,406112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almUnderRange.Resetable,406112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almUnderRange.REST,406112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almUnderRange.ACKN,406112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almUnderRange.UACK,406112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almUnderRange.MCmd_Enable,406112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.MCmd_Disable,406112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.OCmd_Shelve,406112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.OCmd_Unshelve,406112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.SCmd_Suppress,406112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.SCmd_UnSuppress,406113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almUnderRange.AEShelveTMRDN,406113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almUnderRange.Bad,406113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almUnderRange.Suppress,406114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.UnSuppress,406114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Shelve,406114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.UnShelve,406114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Enable,406114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Disable,406114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Ack,406114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Reset,406114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Suppressed,406114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Shelved,406114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Disabled,406114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Acked,406114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almUnderRange.Alarm,406114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Fault,406124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almRateOfChange.AlarmState,406124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almRateOfChange.GlobalReset,406124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almRateOfChange.FaultInAlarm,406124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almRateOfChange.ALRM,406124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almRateOfChange.ANUN,406124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almRateOfChange.AKED,406124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almRateOfChange.Resetable,406124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almRateOfChange.REST,406124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almRateOfChange.ACKN,406124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almRateOfChange.UACK,406124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almRateOfChange.MCmd_Enable,406124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.MCmd_Disable,406124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.OCmd_Shelve,406124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.OCmd_Unshelve,406124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.SCmd_Suppress,406124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.SCmd_UnSuppress,406125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almRateOfChange.AEShelveTMRDN,406125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almRateOfChange.Bad,406125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almRateOfChange.Suppress,406126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.UnSuppress,406126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Shelve,406126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.UnShelve,406126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Enable,406126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Disable,406126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Ack,406126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Reset,406126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Suppressed,406126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Shelved,406126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Disabled,406126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Acked,406126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almRateOfChange.Alarm,406126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Fault,406136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZI.almPLCFault.AlarmState,406136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZI.almPLCFault.GlobalReset,406136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZI.almPLCFault.FaultInAlarm,406136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZI.almPLCFault.ALRM,406136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZI.almPLCFault.ANUN,406136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZI.almPLCFault.AKED,406136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZI.almPLCFault.Resetable,406136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZI.almPLCFault.REST,406136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZI.almPLCFault.ACKN,406136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZI.almPLCFault.UACK,406136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZI.almPLCFault.MCmd_Enable,406136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.MCmd_Disable,406136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.OCmd_Shelve,406136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.OCmd_Unshelve,406136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.SCmd_Suppress,406136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.SCmd_UnSuppress,406137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZI.almPLCFault.AEShelveTMRDN,406137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZI.almPLCFault.Bad,406137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZI.almPLCFault.Suppress,406138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.UnSuppress,406138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Shelve,406138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.UnShelve,406138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Enable,406138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Disable,406138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Ack,406138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Reset,406138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Suppressed,406138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Shelved,406138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Disabled,406138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Acked,406138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZI.almPLCFault.Alarm,406138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Fault,406240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almHighHigh.AlarmState,406240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almHighHigh.GlobalReset,406240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almHighHigh.FaultInAlarm,406240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almHighHigh.ALRM,406240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almHighHigh.ANUN,406240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almHighHigh.AKED,406240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almHighHigh.Resetable,406240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almHighHigh.REST,406240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almHighHigh.ACKN,406240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almHighHigh.UACK,406240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almHighHigh.MCmd_Enable,406240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.MCmd_Disable,406240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.OCmd_Shelve,406240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.OCmd_Unshelve,406240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.SCmd_Suppress,406240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.SCmd_UnSuppress,406241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almHighHigh.AEShelveTMRDN,406241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almHighHigh.Bad,406241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almHighHigh.Suppress,406242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.UnSuppress,406242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Shelve,406242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.UnShelve,406242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Enable,406242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Disable,406242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Ack,406242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Reset,406242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Suppressed,406242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Shelved,406242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Disabled,406242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Acked,406242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almHighHigh.Alarm,406242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Fault,406252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almHigh.AlarmState,406252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almHigh.GlobalReset,406252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almHigh.FaultInAlarm,406252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almHigh.ALRM,406252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almHigh.ANUN,406252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almHigh.AKED,406252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almHigh.Resetable,406252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almHigh.REST,406252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almHigh.ACKN,406252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almHigh.UACK,406252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almHigh.MCmd_Enable,406252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almHigh.MCmd_Disable,406252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almHigh.OCmd_Shelve,406252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almHigh.OCmd_Unshelve,406252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almHigh.SCmd_Suppress,406252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almHigh.SCmd_UnSuppress,406253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almHigh.AEShelveTMRDN,406253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almHigh.Bad,406253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almHigh.Suppress,406254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.UnSuppress,406254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Shelve,406254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.UnShelve,406254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Enable,406254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Disable,406254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Ack,406254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Reset,406254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almHigh.Suppressed,406254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almHigh.Shelved,406254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almHigh.Disabled,406254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almHigh.Acked,406254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almHigh.Alarm,406254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Fault,406264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almLow.AlarmState,406264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almLow.GlobalReset,406264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almLow.FaultInAlarm,406264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almLow.ALRM,406264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almLow.ANUN,406264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almLow.AKED,406264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almLow.Resetable,406264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almLow.REST,406264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almLow.ACKN,406264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almLow.UACK,406264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almLow.MCmd_Enable,406264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almLow.MCmd_Disable,406264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almLow.OCmd_Shelve,406264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almLow.OCmd_Unshelve,406264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almLow.SCmd_Suppress,406264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almLow.SCmd_UnSuppress,406265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almLow.AEShelveTMRDN,406265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almLow.Bad,406265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almLow.Suppress,406266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.UnSuppress,406266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Shelve,406266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.UnShelve,406266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Enable,406266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Disable,406266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Ack,406266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Reset,406266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almLow.Suppressed,406266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almLow.Shelved,406266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almLow.Disabled,406266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almLow.Acked,406266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almLow.Alarm,406266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Fault,406276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almLowLow.AlarmState,406276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almLowLow.GlobalReset,406276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almLowLow.FaultInAlarm,406276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almLowLow.ALRM,406276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almLowLow.ANUN,406276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almLowLow.AKED,406276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almLowLow.Resetable,406276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almLowLow.REST,406276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almLowLow.ACKN,406276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almLowLow.UACK,406276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almLowLow.MCmd_Enable,406276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almLowLow.MCmd_Disable,406276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almLowLow.OCmd_Shelve,406276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almLowLow.OCmd_Unshelve,406276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almLowLow.SCmd_Suppress,406276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almLowLow.SCmd_UnSuppress,406277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almLowLow.AEShelveTMRDN,406277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almLowLow.Bad,406277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almLowLow.Suppress,406278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.UnSuppress,406278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Shelve,406278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.UnShelve,406278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Enable,406278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Disable,406278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Ack,406278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Reset,406278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Suppressed,406278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Shelved,406278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Disabled,406278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Acked,406278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almLowLow.Alarm,406278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Fault,406288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almBrokenLoop.AlarmState,406288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almBrokenLoop.GlobalReset,406288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almBrokenLoop.FaultInAlarm,406288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almBrokenLoop.ALRM,406288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almBrokenLoop.ANUN,406288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almBrokenLoop.AKED,406288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almBrokenLoop.Resetable,406288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almBrokenLoop.REST,406288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almBrokenLoop.ACKN,406288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almBrokenLoop.UACK,406288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almBrokenLoop.MCmd_Enable,406288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.MCmd_Disable,406288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.OCmd_Shelve,406288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.OCmd_Unshelve,406288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.SCmd_Suppress,406288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.SCmd_UnSuppress,406289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almBrokenLoop.AEShelveTMRDN,406289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almBrokenLoop.Bad,406289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almBrokenLoop.Suppress,406290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.UnSuppress,406290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Shelve,406290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.UnShelve,406290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Enable,406290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Disable,406290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Ack,406290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Reset,406290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Suppressed,406290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Shelved,406290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Disabled,406290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Acked,406290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.Alarm,406290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Fault,406300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almOverRange.AlarmState,406300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almOverRange.GlobalReset,406300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almOverRange.FaultInAlarm,406300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almOverRange.ALRM,406300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almOverRange.ANUN,406300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almOverRange.AKED,406300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almOverRange.Resetable,406300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almOverRange.REST,406300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almOverRange.ACKN,406300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almOverRange.UACK,406300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almOverRange.MCmd_Enable,406300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almOverRange.MCmd_Disable,406300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almOverRange.OCmd_Shelve,406300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almOverRange.OCmd_Unshelve,406300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almOverRange.SCmd_Suppress,406300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almOverRange.SCmd_UnSuppress,406301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almOverRange.AEShelveTMRDN,406301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almOverRange.Bad,406301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almOverRange.Suppress,406302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.UnSuppress,406302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Shelve,406302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.UnShelve,406302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Enable,406302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Disable,406302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Ack,406302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Reset,406302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Suppressed,406302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Shelved,406302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Disabled,406302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Acked,406302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almOverRange.Alarm,406302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Fault,406312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almUnderRange.AlarmState,406312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almUnderRange.GlobalReset,406312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almUnderRange.FaultInAlarm,406312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almUnderRange.ALRM,406312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almUnderRange.ANUN,406312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almUnderRange.AKED,406312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almUnderRange.Resetable,406312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almUnderRange.REST,406312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almUnderRange.ACKN,406312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almUnderRange.UACK,406312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almUnderRange.MCmd_Enable,406312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.MCmd_Disable,406312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.OCmd_Shelve,406312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.OCmd_Unshelve,406312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.SCmd_Suppress,406312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.SCmd_UnSuppress,406313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almUnderRange.AEShelveTMRDN,406313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almUnderRange.Bad,406313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almUnderRange.Suppress,406314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.UnSuppress,406314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Shelve,406314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.UnShelve,406314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Enable,406314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Disable,406314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Ack,406314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Reset,406314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Suppressed,406314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Shelved,406314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Disabled,406314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Acked,406314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almUnderRange.Alarm,406314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Fault,406324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almRateOfChange.AlarmState,406324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almRateOfChange.GlobalReset,406324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almRateOfChange.FaultInAlarm,406324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almRateOfChange.ALRM,406324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almRateOfChange.ANUN,406324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almRateOfChange.AKED,406324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almRateOfChange.Resetable,406324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almRateOfChange.REST,406324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almRateOfChange.ACKN,406324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almRateOfChange.UACK,406324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almRateOfChange.MCmd_Enable,406324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.MCmd_Disable,406324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.OCmd_Shelve,406324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.OCmd_Unshelve,406324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.SCmd_Suppress,406324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.SCmd_UnSuppress,406325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almRateOfChange.AEShelveTMRDN,406325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almRateOfChange.Bad,406325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almRateOfChange.Suppress,406326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.UnSuppress,406326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Shelve,406326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.UnShelve,406326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Enable,406326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Disable,406326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Ack,406326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Reset,406326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Suppressed,406326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Shelved,406326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Disabled,406326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Acked,406326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almRateOfChange.Alarm,406326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Fault,406336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZI.almPLCFault.AlarmState,406336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZI.almPLCFault.GlobalReset,406336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZI.almPLCFault.FaultInAlarm,406336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZI.almPLCFault.ALRM,406336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZI.almPLCFault.ANUN,406336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZI.almPLCFault.AKED,406336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZI.almPLCFault.Resetable,406336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZI.almPLCFault.REST,406336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZI.almPLCFault.ACKN,406336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZI.almPLCFault.UACK,406336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZI.almPLCFault.MCmd_Enable,406336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.MCmd_Disable,406336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.OCmd_Shelve,406336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.OCmd_Unshelve,406336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.SCmd_Suppress,406336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.SCmd_UnSuppress,406337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZI.almPLCFault.AEShelveTMRDN,406337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZI.almPLCFault.Bad,406337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZI.almPLCFault.Suppress,406338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.UnSuppress,406338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Shelve,406338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.UnShelve,406338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Enable,406338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Disable,406338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Ack,406338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Reset,406338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Suppressed,406338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Shelved,406338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Disabled,406338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Acked,406338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZI.almPLCFault.Alarm,406338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Fault,406440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almHighHigh.AlarmState,406440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almHighHigh.GlobalReset,406440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almHighHigh.FaultInAlarm,406440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almHighHigh.ALRM,406440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almHighHigh.ANUN,406440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almHighHigh.AKED,406440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almHighHigh.Resetable,406440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almHighHigh.REST,406440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almHighHigh.ACKN,406440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almHighHigh.UACK,406440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almHighHigh.MCmd_Enable,406440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.MCmd_Disable,406440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.OCmd_Shelve,406440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.OCmd_Unshelve,406440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.SCmd_Suppress,406440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.SCmd_UnSuppress,406441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almHighHigh.AEShelveTMRDN,406441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almHighHigh.Bad,406441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almHighHigh.Suppress,406442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.UnSuppress,406442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Shelve,406442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.UnShelve,406442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Enable,406442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Disable,406442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Ack,406442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Reset,406442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Suppressed,406442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Shelved,406442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Disabled,406442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Acked,406442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almHighHigh.Alarm,406442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Fault,406452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almHigh.AlarmState,406452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almHigh.GlobalReset,406452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almHigh.FaultInAlarm,406452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almHigh.ALRM,406452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almHigh.ANUN,406452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almHigh.AKED,406452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almHigh.Resetable,406452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almHigh.REST,406452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almHigh.ACKN,406452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almHigh.UACK,406452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almHigh.MCmd_Enable,406452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almHigh.MCmd_Disable,406452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almHigh.OCmd_Shelve,406452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almHigh.OCmd_Unshelve,406452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almHigh.SCmd_Suppress,406452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almHigh.SCmd_UnSuppress,406453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almHigh.AEShelveTMRDN,406453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almHigh.Bad,406453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almHigh.Suppress,406454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.UnSuppress,406454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Shelve,406454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.UnShelve,406454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Enable,406454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Disable,406454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Ack,406454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Reset,406454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almHigh.Suppressed,406454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almHigh.Shelved,406454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almHigh.Disabled,406454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almHigh.Acked,406454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almHigh.Alarm,406454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Fault,406464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almLow.AlarmState,406464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almLow.GlobalReset,406464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almLow.FaultInAlarm,406464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almLow.ALRM,406464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almLow.ANUN,406464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almLow.AKED,406464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almLow.Resetable,406464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almLow.REST,406464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almLow.ACKN,406464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almLow.UACK,406464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almLow.MCmd_Enable,406464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almLow.MCmd_Disable,406464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almLow.OCmd_Shelve,406464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almLow.OCmd_Unshelve,406464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almLow.SCmd_Suppress,406464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almLow.SCmd_UnSuppress,406465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almLow.AEShelveTMRDN,406465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almLow.Bad,406465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almLow.Suppress,406466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.UnSuppress,406466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Shelve,406466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.UnShelve,406466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Enable,406466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Disable,406466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Ack,406466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Reset,406466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almLow.Suppressed,406466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almLow.Shelved,406466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almLow.Disabled,406466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almLow.Acked,406466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almLow.Alarm,406466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Fault,406476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almLowLow.AlarmState,406476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almLowLow.GlobalReset,406476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almLowLow.FaultInAlarm,406476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almLowLow.ALRM,406476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almLowLow.ANUN,406476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almLowLow.AKED,406476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almLowLow.Resetable,406476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almLowLow.REST,406476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almLowLow.ACKN,406476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almLowLow.UACK,406476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almLowLow.MCmd_Enable,406476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almLowLow.MCmd_Disable,406476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almLowLow.OCmd_Shelve,406476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almLowLow.OCmd_Unshelve,406476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almLowLow.SCmd_Suppress,406476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almLowLow.SCmd_UnSuppress,406477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almLowLow.AEShelveTMRDN,406477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almLowLow.Bad,406477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almLowLow.Suppress,406478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.UnSuppress,406478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Shelve,406478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.UnShelve,406478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Enable,406478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Disable,406478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Ack,406478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Reset,406478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Suppressed,406478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Shelved,406478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Disabled,406478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Acked,406478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almLowLow.Alarm,406478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Fault,406488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almBrokenLoop.AlarmState,406488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almBrokenLoop.GlobalReset,406488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almBrokenLoop.FaultInAlarm,406488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almBrokenLoop.ALRM,406488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almBrokenLoop.ANUN,406488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almBrokenLoop.AKED,406488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almBrokenLoop.Resetable,406488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almBrokenLoop.REST,406488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almBrokenLoop.ACKN,406488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almBrokenLoop.UACK,406488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almBrokenLoop.MCmd_Enable,406488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.MCmd_Disable,406488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.OCmd_Shelve,406488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.OCmd_Unshelve,406488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.SCmd_Suppress,406488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.SCmd_UnSuppress,406489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almBrokenLoop.AEShelveTMRDN,406489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almBrokenLoop.Bad,406489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almBrokenLoop.Suppress,406490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.UnSuppress,406490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Shelve,406490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.UnShelve,406490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Enable,406490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Disable,406490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Ack,406490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Reset,406490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Suppressed,406490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Shelved,406490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Disabled,406490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Acked,406490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.Alarm,406490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Fault,406500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almOverRange.AlarmState,406500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almOverRange.GlobalReset,406500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almOverRange.FaultInAlarm,406500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almOverRange.ALRM,406500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almOverRange.ANUN,406500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almOverRange.AKED,406500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almOverRange.Resetable,406500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almOverRange.REST,406500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almOverRange.ACKN,406500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almOverRange.UACK,406500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almOverRange.MCmd_Enable,406500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almOverRange.MCmd_Disable,406500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almOverRange.OCmd_Shelve,406500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almOverRange.OCmd_Unshelve,406500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almOverRange.SCmd_Suppress,406500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almOverRange.SCmd_UnSuppress,406501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almOverRange.AEShelveTMRDN,406501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almOverRange.Bad,406501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almOverRange.Suppress,406502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.UnSuppress,406502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Shelve,406502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.UnShelve,406502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Enable,406502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Disable,406502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Ack,406502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Reset,406502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Suppressed,406502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Shelved,406502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Disabled,406502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Acked,406502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almOverRange.Alarm,406502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Fault,406512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almUnderRange.AlarmState,406512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almUnderRange.GlobalReset,406512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almUnderRange.FaultInAlarm,406512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almUnderRange.ALRM,406512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almUnderRange.ANUN,406512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almUnderRange.AKED,406512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almUnderRange.Resetable,406512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almUnderRange.REST,406512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almUnderRange.ACKN,406512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almUnderRange.UACK,406512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almUnderRange.MCmd_Enable,406512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.MCmd_Disable,406512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.OCmd_Shelve,406512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.OCmd_Unshelve,406512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.SCmd_Suppress,406512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.SCmd_UnSuppress,406513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almUnderRange.AEShelveTMRDN,406513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almUnderRange.Bad,406513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almUnderRange.Suppress,406514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.UnSuppress,406514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Shelve,406514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.UnShelve,406514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Enable,406514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Disable,406514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Ack,406514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Reset,406514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Suppressed,406514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Shelved,406514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Disabled,406514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Acked,406514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almUnderRange.Alarm,406514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Fault,406524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almRateOfChange.AlarmState,406524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almRateOfChange.GlobalReset,406524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almRateOfChange.FaultInAlarm,406524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almRateOfChange.ALRM,406524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almRateOfChange.ANUN,406524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almRateOfChange.AKED,406524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almRateOfChange.Resetable,406524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almRateOfChange.REST,406524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almRateOfChange.ACKN,406524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almRateOfChange.UACK,406524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almRateOfChange.MCmd_Enable,406524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.MCmd_Disable,406524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.OCmd_Shelve,406524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.OCmd_Unshelve,406524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.SCmd_Suppress,406524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.SCmd_UnSuppress,406525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almRateOfChange.AEShelveTMRDN,406525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almRateOfChange.Bad,406525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almRateOfChange.Suppress,406526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.UnSuppress,406526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Shelve,406526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.UnShelve,406526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Enable,406526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Disable,406526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Ack,406526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Reset,406526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Suppressed,406526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Shelved,406526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Disabled,406526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Acked,406526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almRateOfChange.Alarm,406526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Fault,406536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZI.almPLCFault.AlarmState,406536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZI.almPLCFault.GlobalReset,406536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZI.almPLCFault.FaultInAlarm,406536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZI.almPLCFault.ALRM,406536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZI.almPLCFault.ANUN,406536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZI.almPLCFault.AKED,406536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZI.almPLCFault.Resetable,406536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZI.almPLCFault.REST,406536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZI.almPLCFault.ACKN,406536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZI.almPLCFault.UACK,406536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZI.almPLCFault.MCmd_Enable,406536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.MCmd_Disable,406536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.OCmd_Shelve,406536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.OCmd_Unshelve,406536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.SCmd_Suppress,406536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.SCmd_UnSuppress,406537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZI.almPLCFault.AEShelveTMRDN,406537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZI.almPLCFault.Bad,406537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZI.almPLCFault.Suppress,406538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.UnSuppress,406538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Shelve,406538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.UnShelve,406538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Enable,406538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Disable,406538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Ack,406538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Reset,406538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Suppressed,406538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Shelved,406538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Disabled,406538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Acked,406538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZI.almPLCFault.Alarm,406538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Fault,406640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almHighHigh.AlarmState,406640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almHighHigh.GlobalReset,406640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almHighHigh.FaultInAlarm,406640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almHighHigh.ALRM,406640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almHighHigh.ANUN,406640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almHighHigh.AKED,406640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almHighHigh.Resetable,406640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almHighHigh.REST,406640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almHighHigh.ACKN,406640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almHighHigh.UACK,406640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almHighHigh.MCmd_Enable,406640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.MCmd_Disable,406640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.OCmd_Shelve,406640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.OCmd_Unshelve,406640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.SCmd_Suppress,406640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.SCmd_UnSuppress,406641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almHighHigh.AEShelveTMRDN,406641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almHighHigh.Bad,406641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almHighHigh.Suppress,406642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.UnSuppress,406642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Shelve,406642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.UnShelve,406642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Enable,406642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Disable,406642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Ack,406642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Reset,406642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Suppressed,406642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Shelved,406642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Disabled,406642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Acked,406642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almHighHigh.Alarm,406642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Fault,406652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almHigh.AlarmState,406652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almHigh.GlobalReset,406652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almHigh.FaultInAlarm,406652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almHigh.ALRM,406652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almHigh.ANUN,406652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almHigh.AKED,406652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almHigh.Resetable,406652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almHigh.REST,406652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almHigh.ACKN,406652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almHigh.UACK,406652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almHigh.MCmd_Enable,406652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almHigh.MCmd_Disable,406652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almHigh.OCmd_Shelve,406652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almHigh.OCmd_Unshelve,406652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almHigh.SCmd_Suppress,406652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almHigh.SCmd_UnSuppress,406653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almHigh.AEShelveTMRDN,406653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almHigh.Bad,406653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almHigh.Suppress,406654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.UnSuppress,406654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Shelve,406654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.UnShelve,406654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Enable,406654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Disable,406654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Ack,406654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Reset,406654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almHigh.Suppressed,406654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almHigh.Shelved,406654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almHigh.Disabled,406654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almHigh.Acked,406654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almHigh.Alarm,406654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Fault,406664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almLow.AlarmState,406664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almLow.GlobalReset,406664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almLow.FaultInAlarm,406664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almLow.ALRM,406664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almLow.ANUN,406664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almLow.AKED,406664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almLow.Resetable,406664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almLow.REST,406664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almLow.ACKN,406664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almLow.UACK,406664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almLow.MCmd_Enable,406664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almLow.MCmd_Disable,406664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almLow.OCmd_Shelve,406664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almLow.OCmd_Unshelve,406664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almLow.SCmd_Suppress,406664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almLow.SCmd_UnSuppress,406665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almLow.AEShelveTMRDN,406665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almLow.Bad,406665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almLow.Suppress,406666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.UnSuppress,406666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Shelve,406666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.UnShelve,406666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Enable,406666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Disable,406666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Ack,406666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Reset,406666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almLow.Suppressed,406666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almLow.Shelved,406666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almLow.Disabled,406666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almLow.Acked,406666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almLow.Alarm,406666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Fault,406676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almLowLow.AlarmState,406676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almLowLow.GlobalReset,406676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almLowLow.FaultInAlarm,406676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almLowLow.ALRM,406676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almLowLow.ANUN,406676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almLowLow.AKED,406676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almLowLow.Resetable,406676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almLowLow.REST,406676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almLowLow.ACKN,406676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almLowLow.UACK,406676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almLowLow.MCmd_Enable,406676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almLowLow.MCmd_Disable,406676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almLowLow.OCmd_Shelve,406676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almLowLow.OCmd_Unshelve,406676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almLowLow.SCmd_Suppress,406676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almLowLow.SCmd_UnSuppress,406677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almLowLow.AEShelveTMRDN,406677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almLowLow.Bad,406677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almLowLow.Suppress,406678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.UnSuppress,406678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Shelve,406678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.UnShelve,406678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Enable,406678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Disable,406678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Ack,406678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Reset,406678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Suppressed,406678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Shelved,406678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Disabled,406678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Acked,406678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almLowLow.Alarm,406678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Fault,406688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almBrokenLoop.AlarmState,406688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almBrokenLoop.GlobalReset,406688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almBrokenLoop.FaultInAlarm,406688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almBrokenLoop.ALRM,406688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almBrokenLoop.ANUN,406688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almBrokenLoop.AKED,406688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almBrokenLoop.Resetable,406688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almBrokenLoop.REST,406688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almBrokenLoop.ACKN,406688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almBrokenLoop.UACK,406688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almBrokenLoop.MCmd_Enable,406688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.MCmd_Disable,406688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.OCmd_Shelve,406688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.OCmd_Unshelve,406688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.SCmd_Suppress,406688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.SCmd_UnSuppress,406689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almBrokenLoop.AEShelveTMRDN,406689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almBrokenLoop.Bad,406689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almBrokenLoop.Suppress,406690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.UnSuppress,406690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Shelve,406690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.UnShelve,406690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Enable,406690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Disable,406690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Ack,406690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Reset,406690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Suppressed,406690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Shelved,406690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Disabled,406690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Acked,406690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.Alarm,406690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Fault,406700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almOverRange.AlarmState,406700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almOverRange.GlobalReset,406700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almOverRange.FaultInAlarm,406700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almOverRange.ALRM,406700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almOverRange.ANUN,406700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almOverRange.AKED,406700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almOverRange.Resetable,406700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almOverRange.REST,406700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almOverRange.ACKN,406700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almOverRange.UACK,406700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almOverRange.MCmd_Enable,406700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almOverRange.MCmd_Disable,406700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almOverRange.OCmd_Shelve,406700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almOverRange.OCmd_Unshelve,406700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almOverRange.SCmd_Suppress,406700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almOverRange.SCmd_UnSuppress,406701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almOverRange.AEShelveTMRDN,406701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almOverRange.Bad,406701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almOverRange.Suppress,406702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.UnSuppress,406702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Shelve,406702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.UnShelve,406702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Enable,406702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Disable,406702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Ack,406702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Reset,406702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Suppressed,406702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Shelved,406702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Disabled,406702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Acked,406702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almOverRange.Alarm,406702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Fault,406712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almUnderRange.AlarmState,406712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almUnderRange.GlobalReset,406712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almUnderRange.FaultInAlarm,406712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almUnderRange.ALRM,406712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almUnderRange.ANUN,406712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almUnderRange.AKED,406712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almUnderRange.Resetable,406712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almUnderRange.REST,406712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almUnderRange.ACKN,406712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almUnderRange.UACK,406712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almUnderRange.MCmd_Enable,406712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.MCmd_Disable,406712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.OCmd_Shelve,406712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.OCmd_Unshelve,406712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.SCmd_Suppress,406712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.SCmd_UnSuppress,406713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almUnderRange.AEShelveTMRDN,406713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almUnderRange.Bad,406713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almUnderRange.Suppress,406714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.UnSuppress,406714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Shelve,406714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.UnShelve,406714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Enable,406714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Disable,406714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Ack,406714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Reset,406714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Suppressed,406714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Shelved,406714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Disabled,406714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Acked,406714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almUnderRange.Alarm,406714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Fault,406724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almRateOfChange.AlarmState,406724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almRateOfChange.GlobalReset,406724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almRateOfChange.FaultInAlarm,406724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almRateOfChange.ALRM,406724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almRateOfChange.ANUN,406724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almRateOfChange.AKED,406724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almRateOfChange.Resetable,406724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almRateOfChange.REST,406724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almRateOfChange.ACKN,406724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almRateOfChange.UACK,406724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almRateOfChange.MCmd_Enable,406724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.MCmd_Disable,406724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.OCmd_Shelve,406724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.OCmd_Unshelve,406724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.SCmd_Suppress,406724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.SCmd_UnSuppress,406725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almRateOfChange.AEShelveTMRDN,406725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almRateOfChange.Bad,406725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almRateOfChange.Suppress,406726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.UnSuppress,406726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Shelve,406726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.UnShelve,406726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Enable,406726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Disable,406726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Ack,406726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Reset,406726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Suppressed,406726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Shelved,406726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Disabled,406726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Acked,406726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almRateOfChange.Alarm,406726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Fault,406736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZI.almPLCFault.AlarmState,406736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZI.almPLCFault.GlobalReset,406736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZI.almPLCFault.FaultInAlarm,406736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZI.almPLCFault.ALRM,406736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZI.almPLCFault.ANUN,406736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZI.almPLCFault.AKED,406736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZI.almPLCFault.Resetable,406736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZI.almPLCFault.REST,406736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZI.almPLCFault.ACKN,406736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZI.almPLCFault.UACK,406736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZI.almPLCFault.MCmd_Enable,406736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.MCmd_Disable,406736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.OCmd_Shelve,406736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.OCmd_Unshelve,406736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.SCmd_Suppress,406736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.SCmd_UnSuppress,406737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZI.almPLCFault.AEShelveTMRDN,406737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZI.almPLCFault.Bad,406737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZI.almPLCFault.Suppress,406738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.UnSuppress,406738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Shelve,406738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.UnShelve,406738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Enable,406738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Disable,406738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Ack,406738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Reset,406738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Suppressed,406738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Shelved,406738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Disabled,406738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Acked,406738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZI.almPLCFault.Alarm,406738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Fault,406840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almHighHigh.AlarmState,406840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almHighHigh.GlobalReset,406840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almHighHigh.FaultInAlarm,406840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almHighHigh.ALRM,406840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almHighHigh.ANUN,406840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almHighHigh.AKED,406840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almHighHigh.Resetable,406840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almHighHigh.REST,406840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almHighHigh.ACKN,406840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almHighHigh.UACK,406840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almHighHigh.MCmd_Enable,406840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.MCmd_Disable,406840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.OCmd_Shelve,406840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.OCmd_Unshelve,406840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.SCmd_Suppress,406840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.SCmd_UnSuppress,406841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almHighHigh.AEShelveTMRDN,406841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almHighHigh.Bad,406841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almHighHigh.Suppress,406842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.UnSuppress,406842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Shelve,406842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.UnShelve,406842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Enable,406842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Disable,406842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Ack,406842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Reset,406842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Suppressed,406842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Shelved,406842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Disabled,406842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Acked,406842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almHighHigh.Alarm,406842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Fault,406852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almHigh.AlarmState,406852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almHigh.GlobalReset,406852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almHigh.FaultInAlarm,406852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almHigh.ALRM,406852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almHigh.ANUN,406852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almHigh.AKED,406852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almHigh.Resetable,406852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almHigh.REST,406852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almHigh.ACKN,406852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almHigh.UACK,406852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almHigh.MCmd_Enable,406852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almHigh.MCmd_Disable,406852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almHigh.OCmd_Shelve,406852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almHigh.OCmd_Unshelve,406852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almHigh.SCmd_Suppress,406852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almHigh.SCmd_UnSuppress,406853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almHigh.AEShelveTMRDN,406853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almHigh.Bad,406853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almHigh.Suppress,406854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.UnSuppress,406854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Shelve,406854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.UnShelve,406854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Enable,406854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Disable,406854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Ack,406854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Reset,406854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almHigh.Suppressed,406854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almHigh.Shelved,406854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almHigh.Disabled,406854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almHigh.Acked,406854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almHigh.Alarm,406854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Fault,406864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almLow.AlarmState,406864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almLow.GlobalReset,406864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almLow.FaultInAlarm,406864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almLow.ALRM,406864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almLow.ANUN,406864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almLow.AKED,406864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almLow.Resetable,406864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almLow.REST,406864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almLow.ACKN,406864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almLow.UACK,406864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almLow.MCmd_Enable,406864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almLow.MCmd_Disable,406864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almLow.OCmd_Shelve,406864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almLow.OCmd_Unshelve,406864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almLow.SCmd_Suppress,406864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almLow.SCmd_UnSuppress,406865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almLow.AEShelveTMRDN,406865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almLow.Bad,406865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almLow.Suppress,406866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.UnSuppress,406866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Shelve,406866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.UnShelve,406866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Enable,406866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Disable,406866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Ack,406866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Reset,406866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almLow.Suppressed,406866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almLow.Shelved,406866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almLow.Disabled,406866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almLow.Acked,406866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almLow.Alarm,406866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Fault,406876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almLowLow.AlarmState,406876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almLowLow.GlobalReset,406876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almLowLow.FaultInAlarm,406876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almLowLow.ALRM,406876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almLowLow.ANUN,406876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almLowLow.AKED,406876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almLowLow.Resetable,406876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almLowLow.REST,406876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almLowLow.ACKN,406876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almLowLow.UACK,406876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almLowLow.MCmd_Enable,406876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almLowLow.MCmd_Disable,406876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almLowLow.OCmd_Shelve,406876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almLowLow.OCmd_Unshelve,406876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almLowLow.SCmd_Suppress,406876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almLowLow.SCmd_UnSuppress,406877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almLowLow.AEShelveTMRDN,406877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almLowLow.Bad,406877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almLowLow.Suppress,406878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.UnSuppress,406878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Shelve,406878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.UnShelve,406878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Enable,406878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Disable,406878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Ack,406878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Reset,406878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Suppressed,406878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Shelved,406878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Disabled,406878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Acked,406878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almLowLow.Alarm,406878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Fault,406888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almBrokenLoop.AlarmState,406888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almBrokenLoop.GlobalReset,406888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almBrokenLoop.FaultInAlarm,406888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almBrokenLoop.ALRM,406888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almBrokenLoop.ANUN,406888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almBrokenLoop.AKED,406888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almBrokenLoop.Resetable,406888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almBrokenLoop.REST,406888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almBrokenLoop.ACKN,406888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almBrokenLoop.UACK,406888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almBrokenLoop.MCmd_Enable,406888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.MCmd_Disable,406888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.OCmd_Shelve,406888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.OCmd_Unshelve,406888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.SCmd_Suppress,406888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.SCmd_UnSuppress,406889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almBrokenLoop.AEShelveTMRDN,406889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almBrokenLoop.Bad,406889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almBrokenLoop.Suppress,406890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.UnSuppress,406890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Shelve,406890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.UnShelve,406890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Enable,406890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Disable,406890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Ack,406890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Reset,406890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Suppressed,406890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Shelved,406890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Disabled,406890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Acked,406890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.Alarm,406890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Fault,406900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almOverRange.AlarmState,406900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almOverRange.GlobalReset,406900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almOverRange.FaultInAlarm,406900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almOverRange.ALRM,406900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almOverRange.ANUN,406900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almOverRange.AKED,406900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almOverRange.Resetable,406900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almOverRange.REST,406900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almOverRange.ACKN,406900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almOverRange.UACK,406900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almOverRange.MCmd_Enable,406900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almOverRange.MCmd_Disable,406900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almOverRange.OCmd_Shelve,406900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almOverRange.OCmd_Unshelve,406900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almOverRange.SCmd_Suppress,406900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almOverRange.SCmd_UnSuppress,406901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almOverRange.AEShelveTMRDN,406901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almOverRange.Bad,406901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almOverRange.Suppress,406902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.UnSuppress,406902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Shelve,406902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.UnShelve,406902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Enable,406902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Disable,406902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Ack,406902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Reset,406902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Suppressed,406902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Shelved,406902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Disabled,406902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Acked,406902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almOverRange.Alarm,406902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Fault,406912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almUnderRange.AlarmState,406912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almUnderRange.GlobalReset,406912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almUnderRange.FaultInAlarm,406912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almUnderRange.ALRM,406912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almUnderRange.ANUN,406912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almUnderRange.AKED,406912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almUnderRange.Resetable,406912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almUnderRange.REST,406912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almUnderRange.ACKN,406912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almUnderRange.UACK,406912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almUnderRange.MCmd_Enable,406912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.MCmd_Disable,406912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.OCmd_Shelve,406912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.OCmd_Unshelve,406912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.SCmd_Suppress,406912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.SCmd_UnSuppress,406913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almUnderRange.AEShelveTMRDN,406913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almUnderRange.Bad,406913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almUnderRange.Suppress,406914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.UnSuppress,406914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Shelve,406914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.UnShelve,406914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Enable,406914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Disable,406914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Ack,406914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Reset,406914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Suppressed,406914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Shelved,406914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Disabled,406914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Acked,406914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almUnderRange.Alarm,406914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Fault,406924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almRateOfChange.AlarmState,406924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almRateOfChange.GlobalReset,406924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almRateOfChange.FaultInAlarm,406924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almRateOfChange.ALRM,406924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almRateOfChange.ANUN,406924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almRateOfChange.AKED,406924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almRateOfChange.Resetable,406924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almRateOfChange.REST,406924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almRateOfChange.ACKN,406924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almRateOfChange.UACK,406924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almRateOfChange.MCmd_Enable,406924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.MCmd_Disable,406924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.OCmd_Shelve,406924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.OCmd_Unshelve,406924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.SCmd_Suppress,406924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.SCmd_UnSuppress,406925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almRateOfChange.AEShelveTMRDN,406925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almRateOfChange.Bad,406925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almRateOfChange.Suppress,406926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.UnSuppress,406926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Shelve,406926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.UnShelve,406926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Enable,406926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Disable,406926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Ack,406926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Reset,406926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Suppressed,406926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Shelved,406926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Disabled,406926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Acked,406926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almRateOfChange.Alarm,406926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Fault,406936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZI.almPLCFault.AlarmState,406936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZI.almPLCFault.GlobalReset,406936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZI.almPLCFault.FaultInAlarm,406936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZI.almPLCFault.ALRM,406936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZI.almPLCFault.ANUN,406936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZI.almPLCFault.AKED,406936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZI.almPLCFault.Resetable,406936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZI.almPLCFault.REST,406936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZI.almPLCFault.ACKN,406936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZI.almPLCFault.UACK,406936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZI.almPLCFault.MCmd_Enable,406936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.MCmd_Disable,406936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.OCmd_Shelve,406936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.OCmd_Unshelve,406936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.SCmd_Suppress,406936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.SCmd_UnSuppress,406937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZI.almPLCFault.AEShelveTMRDN,406937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZI.almPLCFault.Bad,406937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZI.almPLCFault.Suppress,406938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.UnSuppress,406938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Shelve,406938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.UnShelve,406938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Enable,406938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Disable,406938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Ack,406938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Reset,406938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Suppressed,406938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Shelved,406938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Disabled,406938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Acked,406938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZI.almPLCFault.Alarm,406938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Fault,407040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almHighHigh.AlarmState,407040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almHighHigh.GlobalReset,407040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almHighHigh.FaultInAlarm,407040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almHighHigh.ALRM,407040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almHighHigh.ANUN,407040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almHighHigh.AKED,407040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almHighHigh.Resetable,407040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almHighHigh.REST,407040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almHighHigh.ACKN,407040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almHighHigh.UACK,407040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almHighHigh.MCmd_Enable,407040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.MCmd_Disable,407040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.OCmd_Shelve,407040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.OCmd_Unshelve,407040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.SCmd_Suppress,407040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.SCmd_UnSuppress,407041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almHighHigh.AEShelveTMRDN,407041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almHighHigh.Bad,407041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almHighHigh.Suppress,407042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.UnSuppress,407042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Shelve,407042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.UnShelve,407042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Enable,407042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Disable,407042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Ack,407042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Reset,407042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Suppressed,407042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Shelved,407042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Disabled,407042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Acked,407042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almHighHigh.Alarm,407042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Fault,407052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almHigh.AlarmState,407052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almHigh.GlobalReset,407052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almHigh.FaultInAlarm,407052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almHigh.ALRM,407052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almHigh.ANUN,407052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almHigh.AKED,407052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almHigh.Resetable,407052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almHigh.REST,407052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almHigh.ACKN,407052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almHigh.UACK,407052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almHigh.MCmd_Enable,407052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almHigh.MCmd_Disable,407052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almHigh.OCmd_Shelve,407052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almHigh.OCmd_Unshelve,407052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almHigh.SCmd_Suppress,407052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almHigh.SCmd_UnSuppress,407053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almHigh.AEShelveTMRDN,407053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almHigh.Bad,407053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almHigh.Suppress,407054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.UnSuppress,407054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Shelve,407054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.UnShelve,407054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Enable,407054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Disable,407054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Ack,407054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Reset,407054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almHigh.Suppressed,407054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almHigh.Shelved,407054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almHigh.Disabled,407054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almHigh.Acked,407054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almHigh.Alarm,407054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Fault,407064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almLow.AlarmState,407064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almLow.GlobalReset,407064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almLow.FaultInAlarm,407064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almLow.ALRM,407064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almLow.ANUN,407064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almLow.AKED,407064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almLow.Resetable,407064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almLow.REST,407064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almLow.ACKN,407064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almLow.UACK,407064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almLow.MCmd_Enable,407064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almLow.MCmd_Disable,407064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almLow.OCmd_Shelve,407064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almLow.OCmd_Unshelve,407064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almLow.SCmd_Suppress,407064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almLow.SCmd_UnSuppress,407065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almLow.AEShelveTMRDN,407065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almLow.Bad,407065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almLow.Suppress,407066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.UnSuppress,407066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Shelve,407066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.UnShelve,407066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Enable,407066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Disable,407066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Ack,407066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Reset,407066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almLow.Suppressed,407066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almLow.Shelved,407066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almLow.Disabled,407066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almLow.Acked,407066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almLow.Alarm,407066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Fault,407076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almLowLow.AlarmState,407076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almLowLow.GlobalReset,407076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almLowLow.FaultInAlarm,407076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almLowLow.ALRM,407076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almLowLow.ANUN,407076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almLowLow.AKED,407076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almLowLow.Resetable,407076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almLowLow.REST,407076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almLowLow.ACKN,407076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almLowLow.UACK,407076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almLowLow.MCmd_Enable,407076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almLowLow.MCmd_Disable,407076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almLowLow.OCmd_Shelve,407076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almLowLow.OCmd_Unshelve,407076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almLowLow.SCmd_Suppress,407076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almLowLow.SCmd_UnSuppress,407077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almLowLow.AEShelveTMRDN,407077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almLowLow.Bad,407077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almLowLow.Suppress,407078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.UnSuppress,407078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Shelve,407078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.UnShelve,407078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Enable,407078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Disable,407078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Ack,407078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Reset,407078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Suppressed,407078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Shelved,407078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Disabled,407078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Acked,407078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almLowLow.Alarm,407078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Fault,407088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almBrokenLoop.AlarmState,407088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almBrokenLoop.GlobalReset,407088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almBrokenLoop.FaultInAlarm,407088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almBrokenLoop.ALRM,407088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almBrokenLoop.ANUN,407088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almBrokenLoop.AKED,407088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almBrokenLoop.Resetable,407088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almBrokenLoop.REST,407088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almBrokenLoop.ACKN,407088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almBrokenLoop.UACK,407088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almBrokenLoop.MCmd_Enable,407088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.MCmd_Disable,407088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.OCmd_Shelve,407088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.OCmd_Unshelve,407088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.SCmd_Suppress,407088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.SCmd_UnSuppress,407089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almBrokenLoop.AEShelveTMRDN,407089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almBrokenLoop.Bad,407089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almBrokenLoop.Suppress,407090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.UnSuppress,407090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Shelve,407090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.UnShelve,407090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Enable,407090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Disable,407090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Ack,407090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Reset,407090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Suppressed,407090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Shelved,407090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Disabled,407090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Acked,407090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.Alarm,407090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Fault,407100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almOverRange.AlarmState,407100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almOverRange.GlobalReset,407100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almOverRange.FaultInAlarm,407100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almOverRange.ALRM,407100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almOverRange.ANUN,407100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almOverRange.AKED,407100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almOverRange.Resetable,407100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almOverRange.REST,407100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almOverRange.ACKN,407100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almOverRange.UACK,407100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almOverRange.MCmd_Enable,407100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almOverRange.MCmd_Disable,407100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almOverRange.OCmd_Shelve,407100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almOverRange.OCmd_Unshelve,407100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almOverRange.SCmd_Suppress,407100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almOverRange.SCmd_UnSuppress,407101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almOverRange.AEShelveTMRDN,407101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almOverRange.Bad,407101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almOverRange.Suppress,407102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.UnSuppress,407102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Shelve,407102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.UnShelve,407102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Enable,407102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Disable,407102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Ack,407102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Reset,407102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Suppressed,407102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Shelved,407102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Disabled,407102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Acked,407102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almOverRange.Alarm,407102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Fault,407112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almUnderRange.AlarmState,407112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almUnderRange.GlobalReset,407112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almUnderRange.FaultInAlarm,407112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almUnderRange.ALRM,407112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almUnderRange.ANUN,407112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almUnderRange.AKED,407112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almUnderRange.Resetable,407112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almUnderRange.REST,407112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almUnderRange.ACKN,407112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almUnderRange.UACK,407112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almUnderRange.MCmd_Enable,407112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.MCmd_Disable,407112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.OCmd_Shelve,407112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.OCmd_Unshelve,407112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.SCmd_Suppress,407112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.SCmd_UnSuppress,407113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almUnderRange.AEShelveTMRDN,407113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almUnderRange.Bad,407113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almUnderRange.Suppress,407114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.UnSuppress,407114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Shelve,407114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.UnShelve,407114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Enable,407114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Disable,407114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Ack,407114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Reset,407114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Suppressed,407114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Shelved,407114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Disabled,407114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Acked,407114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almUnderRange.Alarm,407114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Fault,407124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almRateOfChange.AlarmState,407124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almRateOfChange.GlobalReset,407124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almRateOfChange.FaultInAlarm,407124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almRateOfChange.ALRM,407124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almRateOfChange.ANUN,407124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almRateOfChange.AKED,407124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almRateOfChange.Resetable,407124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almRateOfChange.REST,407124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almRateOfChange.ACKN,407124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almRateOfChange.UACK,407124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almRateOfChange.MCmd_Enable,407124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.MCmd_Disable,407124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.OCmd_Shelve,407124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.OCmd_Unshelve,407124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.SCmd_Suppress,407124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.SCmd_UnSuppress,407125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almRateOfChange.AEShelveTMRDN,407125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almRateOfChange.Bad,407125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almRateOfChange.Suppress,407126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.UnSuppress,407126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Shelve,407126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.UnShelve,407126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Enable,407126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Disable,407126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Ack,407126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Reset,407126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Suppressed,407126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Shelved,407126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Disabled,407126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Acked,407126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almRateOfChange.Alarm,407126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Fault,407136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI1.almPLCFault.AlarmState,407136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI1.almPLCFault.GlobalReset,407136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI1.almPLCFault.FaultInAlarm,407136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI1.almPLCFault.ALRM,407136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI1.almPLCFault.ANUN,407136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI1.almPLCFault.AKED,407136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI1.almPLCFault.Resetable,407136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI1.almPLCFault.REST,407136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI1.almPLCFault.ACKN,407136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI1.almPLCFault.UACK,407136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI1.almPLCFault.MCmd_Enable,407136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.MCmd_Disable,407136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.OCmd_Shelve,407136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.OCmd_Unshelve,407136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.SCmd_Suppress,407136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.SCmd_UnSuppress,407137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI1.almPLCFault.AEShelveTMRDN,407137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI1.almPLCFault.Bad,407137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI1.almPLCFault.Suppress,407138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.UnSuppress,407138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Shelve,407138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.UnShelve,407138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Enable,407138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Disable,407138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Ack,407138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Reset,407138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Suppressed,407138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Shelved,407138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Disabled,407138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Acked,407138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI1.almPLCFault.Alarm,407138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Fault,407240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almHighHigh.AlarmState,407240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almHighHigh.GlobalReset,407240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almHighHigh.FaultInAlarm,407240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almHighHigh.ALRM,407240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almHighHigh.ANUN,407240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almHighHigh.AKED,407240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almHighHigh.Resetable,407240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almHighHigh.REST,407240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almHighHigh.ACKN,407240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almHighHigh.UACK,407240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almHighHigh.MCmd_Enable,407240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.MCmd_Disable,407240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.OCmd_Shelve,407240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.OCmd_Unshelve,407240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.SCmd_Suppress,407240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.SCmd_UnSuppress,407241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almHighHigh.AEShelveTMRDN,407241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almHighHigh.Bad,407241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almHighHigh.Suppress,407242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.UnSuppress,407242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Shelve,407242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.UnShelve,407242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Enable,407242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Disable,407242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Ack,407242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Reset,407242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Suppressed,407242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Shelved,407242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Disabled,407242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Acked,407242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almHighHigh.Alarm,407242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Fault,407252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almHigh.AlarmState,407252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almHigh.GlobalReset,407252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almHigh.FaultInAlarm,407252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almHigh.ALRM,407252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almHigh.ANUN,407252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almHigh.AKED,407252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almHigh.Resetable,407252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almHigh.REST,407252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almHigh.ACKN,407252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almHigh.UACK,407252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almHigh.MCmd_Enable,407252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almHigh.MCmd_Disable,407252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almHigh.OCmd_Shelve,407252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almHigh.OCmd_Unshelve,407252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almHigh.SCmd_Suppress,407252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almHigh.SCmd_UnSuppress,407253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almHigh.AEShelveTMRDN,407253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almHigh.Bad,407253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almHigh.Suppress,407254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.UnSuppress,407254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Shelve,407254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.UnShelve,407254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Enable,407254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Disable,407254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Ack,407254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Reset,407254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almHigh.Suppressed,407254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almHigh.Shelved,407254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almHigh.Disabled,407254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almHigh.Acked,407254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almHigh.Alarm,407254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Fault,407264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almLow.AlarmState,407264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almLow.GlobalReset,407264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almLow.FaultInAlarm,407264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almLow.ALRM,407264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almLow.ANUN,407264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almLow.AKED,407264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almLow.Resetable,407264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almLow.REST,407264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almLow.ACKN,407264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almLow.UACK,407264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almLow.MCmd_Enable,407264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almLow.MCmd_Disable,407264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almLow.OCmd_Shelve,407264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almLow.OCmd_Unshelve,407264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almLow.SCmd_Suppress,407264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almLow.SCmd_UnSuppress,407265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almLow.AEShelveTMRDN,407265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almLow.Bad,407265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almLow.Suppress,407266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.UnSuppress,407266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Shelve,407266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.UnShelve,407266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Enable,407266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Disable,407266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Ack,407266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Reset,407266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almLow.Suppressed,407266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almLow.Shelved,407266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almLow.Disabled,407266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almLow.Acked,407266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almLow.Alarm,407266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Fault,407276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almLowLow.AlarmState,407276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almLowLow.GlobalReset,407276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almLowLow.FaultInAlarm,407276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almLowLow.ALRM,407276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almLowLow.ANUN,407276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almLowLow.AKED,407276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almLowLow.Resetable,407276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almLowLow.REST,407276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almLowLow.ACKN,407276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almLowLow.UACK,407276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almLowLow.MCmd_Enable,407276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almLowLow.MCmd_Disable,407276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almLowLow.OCmd_Shelve,407276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almLowLow.OCmd_Unshelve,407276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almLowLow.SCmd_Suppress,407276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almLowLow.SCmd_UnSuppress,407277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almLowLow.AEShelveTMRDN,407277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almLowLow.Bad,407277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almLowLow.Suppress,407278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.UnSuppress,407278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Shelve,407278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.UnShelve,407278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Enable,407278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Disable,407278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Ack,407278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Reset,407278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Suppressed,407278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Shelved,407278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Disabled,407278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Acked,407278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almLowLow.Alarm,407278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Fault,407288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almBrokenLoop.AlarmState,407288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almBrokenLoop.GlobalReset,407288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almBrokenLoop.FaultInAlarm,407288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almBrokenLoop.ALRM,407288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almBrokenLoop.ANUN,407288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almBrokenLoop.AKED,407288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almBrokenLoop.Resetable,407288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almBrokenLoop.REST,407288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almBrokenLoop.ACKN,407288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almBrokenLoop.UACK,407288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almBrokenLoop.MCmd_Enable,407288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.MCmd_Disable,407288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.OCmd_Shelve,407288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.OCmd_Unshelve,407288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.SCmd_Suppress,407288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.SCmd_UnSuppress,407289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almBrokenLoop.AEShelveTMRDN,407289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almBrokenLoop.Bad,407289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almBrokenLoop.Suppress,407290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.UnSuppress,407290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Shelve,407290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.UnShelve,407290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Enable,407290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Disable,407290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Ack,407290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Reset,407290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Suppressed,407290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Shelved,407290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Disabled,407290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Acked,407290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.Alarm,407290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Fault,407300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almOverRange.AlarmState,407300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almOverRange.GlobalReset,407300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almOverRange.FaultInAlarm,407300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almOverRange.ALRM,407300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almOverRange.ANUN,407300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almOverRange.AKED,407300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almOverRange.Resetable,407300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almOverRange.REST,407300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almOverRange.ACKN,407300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almOverRange.UACK,407300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almOverRange.MCmd_Enable,407300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almOverRange.MCmd_Disable,407300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almOverRange.OCmd_Shelve,407300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almOverRange.OCmd_Unshelve,407300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almOverRange.SCmd_Suppress,407300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almOverRange.SCmd_UnSuppress,407301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almOverRange.AEShelveTMRDN,407301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almOverRange.Bad,407301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almOverRange.Suppress,407302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.UnSuppress,407302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Shelve,407302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.UnShelve,407302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Enable,407302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Disable,407302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Ack,407302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Reset,407302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Suppressed,407302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Shelved,407302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Disabled,407302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Acked,407302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almOverRange.Alarm,407302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Fault,407312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almUnderRange.AlarmState,407312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almUnderRange.GlobalReset,407312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almUnderRange.FaultInAlarm,407312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almUnderRange.ALRM,407312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almUnderRange.ANUN,407312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almUnderRange.AKED,407312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almUnderRange.Resetable,407312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almUnderRange.REST,407312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almUnderRange.ACKN,407312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almUnderRange.UACK,407312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almUnderRange.MCmd_Enable,407312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.MCmd_Disable,407312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.OCmd_Shelve,407312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.OCmd_Unshelve,407312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.SCmd_Suppress,407312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.SCmd_UnSuppress,407313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almUnderRange.AEShelveTMRDN,407313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almUnderRange.Bad,407313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almUnderRange.Suppress,407314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.UnSuppress,407314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Shelve,407314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.UnShelve,407314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Enable,407314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Disable,407314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Ack,407314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Reset,407314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Suppressed,407314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Shelved,407314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Disabled,407314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Acked,407314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almUnderRange.Alarm,407314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Fault,407324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almRateOfChange.AlarmState,407324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almRateOfChange.GlobalReset,407324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almRateOfChange.FaultInAlarm,407324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almRateOfChange.ALRM,407324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almRateOfChange.ANUN,407324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almRateOfChange.AKED,407324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almRateOfChange.Resetable,407324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almRateOfChange.REST,407324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almRateOfChange.ACKN,407324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almRateOfChange.UACK,407324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almRateOfChange.MCmd_Enable,407324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.MCmd_Disable,407324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.OCmd_Shelve,407324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.OCmd_Unshelve,407324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.SCmd_Suppress,407324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.SCmd_UnSuppress,407325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almRateOfChange.AEShelveTMRDN,407325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almRateOfChange.Bad,407325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almRateOfChange.Suppress,407326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.UnSuppress,407326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Shelve,407326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.UnShelve,407326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Enable,407326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Disable,407326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Ack,407326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Reset,407326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Suppressed,407326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Shelved,407326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Disabled,407326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Acked,407326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almRateOfChange.Alarm,407326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Fault,407336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI2.almPLCFault.AlarmState,407336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI2.almPLCFault.GlobalReset,407336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI2.almPLCFault.FaultInAlarm,407336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI2.almPLCFault.ALRM,407336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI2.almPLCFault.ANUN,407336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI2.almPLCFault.AKED,407336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI2.almPLCFault.Resetable,407336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI2.almPLCFault.REST,407336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI2.almPLCFault.ACKN,407336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI2.almPLCFault.UACK,407336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI2.almPLCFault.MCmd_Enable,407336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.MCmd_Disable,407336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.OCmd_Shelve,407336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.OCmd_Unshelve,407336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.SCmd_Suppress,407336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.SCmd_UnSuppress,407337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI2.almPLCFault.AEShelveTMRDN,407337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI2.almPLCFault.Bad,407337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI2.almPLCFault.Suppress,407338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.UnSuppress,407338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Shelve,407338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.UnShelve,407338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Enable,407338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Disable,407338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Ack,407338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Reset,407338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Suppressed,407338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Shelved,407338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Disabled,407338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Acked,407338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI2.almPLCFault.Alarm,407338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Fault,407440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almHighHigh.AlarmState,407440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almHighHigh.GlobalReset,407440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almHighHigh.FaultInAlarm,407440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almHighHigh.ALRM,407440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almHighHigh.ANUN,407440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almHighHigh.AKED,407440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almHighHigh.Resetable,407440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almHighHigh.REST,407440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almHighHigh.ACKN,407440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almHighHigh.UACK,407440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almHighHigh.MCmd_Enable,407440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.MCmd_Disable,407440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.OCmd_Shelve,407440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.OCmd_Unshelve,407440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.SCmd_Suppress,407440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.SCmd_UnSuppress,407441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almHighHigh.AEShelveTMRDN,407441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almHighHigh.Bad,407441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almHighHigh.Suppress,407442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.UnSuppress,407442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Shelve,407442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.UnShelve,407442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Enable,407442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Disable,407442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Ack,407442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Reset,407442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Suppressed,407442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Shelved,407442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Disabled,407442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Acked,407442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almHighHigh.Alarm,407442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Fault,407452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almHigh.AlarmState,407452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almHigh.GlobalReset,407452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almHigh.FaultInAlarm,407452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almHigh.ALRM,407452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almHigh.ANUN,407452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almHigh.AKED,407452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almHigh.Resetable,407452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almHigh.REST,407452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almHigh.ACKN,407452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almHigh.UACK,407452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almHigh.MCmd_Enable,407452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almHigh.MCmd_Disable,407452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almHigh.OCmd_Shelve,407452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almHigh.OCmd_Unshelve,407452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almHigh.SCmd_Suppress,407452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almHigh.SCmd_UnSuppress,407453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almHigh.AEShelveTMRDN,407453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almHigh.Bad,407453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almHigh.Suppress,407454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.UnSuppress,407454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Shelve,407454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.UnShelve,407454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Enable,407454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Disable,407454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Ack,407454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Reset,407454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almHigh.Suppressed,407454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almHigh.Shelved,407454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almHigh.Disabled,407454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almHigh.Acked,407454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almHigh.Alarm,407454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Fault,407464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almLow.AlarmState,407464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almLow.GlobalReset,407464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almLow.FaultInAlarm,407464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almLow.ALRM,407464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almLow.ANUN,407464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almLow.AKED,407464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almLow.Resetable,407464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almLow.REST,407464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almLow.ACKN,407464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almLow.UACK,407464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almLow.MCmd_Enable,407464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almLow.MCmd_Disable,407464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almLow.OCmd_Shelve,407464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almLow.OCmd_Unshelve,407464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almLow.SCmd_Suppress,407464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almLow.SCmd_UnSuppress,407465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almLow.AEShelveTMRDN,407465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almLow.Bad,407465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almLow.Suppress,407466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.UnSuppress,407466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Shelve,407466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.UnShelve,407466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Enable,407466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Disable,407466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Ack,407466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Reset,407466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almLow.Suppressed,407466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almLow.Shelved,407466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almLow.Disabled,407466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almLow.Acked,407466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almLow.Alarm,407466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Fault,407476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almLowLow.AlarmState,407476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almLowLow.GlobalReset,407476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almLowLow.FaultInAlarm,407476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almLowLow.ALRM,407476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almLowLow.ANUN,407476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almLowLow.AKED,407476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almLowLow.Resetable,407476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almLowLow.REST,407476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almLowLow.ACKN,407476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almLowLow.UACK,407476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almLowLow.MCmd_Enable,407476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almLowLow.MCmd_Disable,407476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almLowLow.OCmd_Shelve,407476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almLowLow.OCmd_Unshelve,407476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almLowLow.SCmd_Suppress,407476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almLowLow.SCmd_UnSuppress,407477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almLowLow.AEShelveTMRDN,407477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almLowLow.Bad,407477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almLowLow.Suppress,407478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.UnSuppress,407478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Shelve,407478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.UnShelve,407478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Enable,407478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Disable,407478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Ack,407478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Reset,407478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Suppressed,407478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Shelved,407478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Disabled,407478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Acked,407478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almLowLow.Alarm,407478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Fault,407488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almBrokenLoop.AlarmState,407488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almBrokenLoop.GlobalReset,407488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almBrokenLoop.FaultInAlarm,407488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almBrokenLoop.ALRM,407488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almBrokenLoop.ANUN,407488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almBrokenLoop.AKED,407488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almBrokenLoop.Resetable,407488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almBrokenLoop.REST,407488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almBrokenLoop.ACKN,407488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almBrokenLoop.UACK,407488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almBrokenLoop.MCmd_Enable,407488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.MCmd_Disable,407488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.OCmd_Shelve,407488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.OCmd_Unshelve,407488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.SCmd_Suppress,407488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.SCmd_UnSuppress,407489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almBrokenLoop.AEShelveTMRDN,407489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almBrokenLoop.Bad,407489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almBrokenLoop.Suppress,407490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.UnSuppress,407490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Shelve,407490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.UnShelve,407490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Enable,407490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Disable,407490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Ack,407490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Reset,407490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Suppressed,407490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Shelved,407490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Disabled,407490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Acked,407490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.Alarm,407490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Fault,407500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almOverRange.AlarmState,407500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almOverRange.GlobalReset,407500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almOverRange.FaultInAlarm,407500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almOverRange.ALRM,407500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almOverRange.ANUN,407500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almOverRange.AKED,407500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almOverRange.Resetable,407500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almOverRange.REST,407500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almOverRange.ACKN,407500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almOverRange.UACK,407500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almOverRange.MCmd_Enable,407500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almOverRange.MCmd_Disable,407500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almOverRange.OCmd_Shelve,407500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almOverRange.OCmd_Unshelve,407500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almOverRange.SCmd_Suppress,407500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almOverRange.SCmd_UnSuppress,407501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almOverRange.AEShelveTMRDN,407501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almOverRange.Bad,407501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almOverRange.Suppress,407502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.UnSuppress,407502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Shelve,407502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.UnShelve,407502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Enable,407502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Disable,407502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Ack,407502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Reset,407502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Suppressed,407502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Shelved,407502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Disabled,407502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Acked,407502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almOverRange.Alarm,407502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Fault,407512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almUnderRange.AlarmState,407512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almUnderRange.GlobalReset,407512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almUnderRange.FaultInAlarm,407512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almUnderRange.ALRM,407512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almUnderRange.ANUN,407512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almUnderRange.AKED,407512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almUnderRange.Resetable,407512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almUnderRange.REST,407512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almUnderRange.ACKN,407512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almUnderRange.UACK,407512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almUnderRange.MCmd_Enable,407512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.MCmd_Disable,407512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.OCmd_Shelve,407512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.OCmd_Unshelve,407512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.SCmd_Suppress,407512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.SCmd_UnSuppress,407513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almUnderRange.AEShelveTMRDN,407513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almUnderRange.Bad,407513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almUnderRange.Suppress,407514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.UnSuppress,407514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Shelve,407514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.UnShelve,407514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Enable,407514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Disable,407514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Ack,407514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Reset,407514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Suppressed,407514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Shelved,407514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Disabled,407514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Acked,407514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almUnderRange.Alarm,407514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Fault,407524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almRateOfChange.AlarmState,407524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almRateOfChange.GlobalReset,407524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almRateOfChange.FaultInAlarm,407524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almRateOfChange.ALRM,407524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almRateOfChange.ANUN,407524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almRateOfChange.AKED,407524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almRateOfChange.Resetable,407524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almRateOfChange.REST,407524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almRateOfChange.ACKN,407524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almRateOfChange.UACK,407524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almRateOfChange.MCmd_Enable,407524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.MCmd_Disable,407524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.OCmd_Shelve,407524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.OCmd_Unshelve,407524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.SCmd_Suppress,407524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.SCmd_UnSuppress,407525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almRateOfChange.AEShelveTMRDN,407525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almRateOfChange.Bad,407525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almRateOfChange.Suppress,407526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.UnSuppress,407526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Shelve,407526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.UnShelve,407526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Enable,407526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Disable,407526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Ack,407526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Reset,407526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Suppressed,407526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Shelved,407526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Disabled,407526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Acked,407526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almRateOfChange.Alarm,407526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Fault,407536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI3.almPLCFault.AlarmState,407536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI3.almPLCFault.GlobalReset,407536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI3.almPLCFault.FaultInAlarm,407536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI3.almPLCFault.ALRM,407536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI3.almPLCFault.ANUN,407536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI3.almPLCFault.AKED,407536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI3.almPLCFault.Resetable,407536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI3.almPLCFault.REST,407536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI3.almPLCFault.ACKN,407536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI3.almPLCFault.UACK,407536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI3.almPLCFault.MCmd_Enable,407536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.MCmd_Disable,407536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.OCmd_Shelve,407536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.OCmd_Unshelve,407536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.SCmd_Suppress,407536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.SCmd_UnSuppress,407537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI3.almPLCFault.AEShelveTMRDN,407537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI3.almPLCFault.Bad,407537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI3.almPLCFault.Suppress,407538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.UnSuppress,407538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Shelve,407538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.UnShelve,407538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Enable,407538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Disable,407538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Ack,407538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Reset,407538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Suppressed,407538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Shelved,407538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Disabled,407538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Acked,407538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI3.almPLCFault.Alarm,407538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Fault,407640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almHighHigh.AlarmState,407640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almHighHigh.GlobalReset,407640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almHighHigh.FaultInAlarm,407640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almHighHigh.ALRM,407640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almHighHigh.ANUN,407640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almHighHigh.AKED,407640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almHighHigh.Resetable,407640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almHighHigh.REST,407640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almHighHigh.ACKN,407640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almHighHigh.UACK,407640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almHighHigh.MCmd_Enable,407640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.MCmd_Disable,407640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.OCmd_Shelve,407640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.OCmd_Unshelve,407640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.SCmd_Suppress,407640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.SCmd_UnSuppress,407641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almHighHigh.AEShelveTMRDN,407641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almHighHigh.Bad,407641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almHighHigh.Suppress,407642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.UnSuppress,407642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Shelve,407642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.UnShelve,407642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Enable,407642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Disable,407642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Ack,407642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Reset,407642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Suppressed,407642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Shelved,407642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Disabled,407642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Acked,407642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almHighHigh.Alarm,407642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Fault,407652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almHigh.AlarmState,407652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almHigh.GlobalReset,407652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almHigh.FaultInAlarm,407652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almHigh.ALRM,407652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almHigh.ANUN,407652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almHigh.AKED,407652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almHigh.Resetable,407652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almHigh.REST,407652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almHigh.ACKN,407652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almHigh.UACK,407652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almHigh.MCmd_Enable,407652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almHigh.MCmd_Disable,407652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almHigh.OCmd_Shelve,407652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almHigh.OCmd_Unshelve,407652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almHigh.SCmd_Suppress,407652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almHigh.SCmd_UnSuppress,407653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almHigh.AEShelveTMRDN,407653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almHigh.Bad,407653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almHigh.Suppress,407654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.UnSuppress,407654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Shelve,407654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.UnShelve,407654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Enable,407654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Disable,407654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Ack,407654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Reset,407654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almHigh.Suppressed,407654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almHigh.Shelved,407654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almHigh.Disabled,407654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almHigh.Acked,407654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almHigh.Alarm,407654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Fault,407664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almLow.AlarmState,407664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almLow.GlobalReset,407664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almLow.FaultInAlarm,407664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almLow.ALRM,407664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almLow.ANUN,407664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almLow.AKED,407664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almLow.Resetable,407664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almLow.REST,407664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almLow.ACKN,407664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almLow.UACK,407664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almLow.MCmd_Enable,407664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almLow.MCmd_Disable,407664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almLow.OCmd_Shelve,407664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almLow.OCmd_Unshelve,407664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almLow.SCmd_Suppress,407664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almLow.SCmd_UnSuppress,407665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almLow.AEShelveTMRDN,407665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almLow.Bad,407665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almLow.Suppress,407666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.UnSuppress,407666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Shelve,407666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.UnShelve,407666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Enable,407666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Disable,407666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Ack,407666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Reset,407666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almLow.Suppressed,407666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almLow.Shelved,407666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almLow.Disabled,407666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almLow.Acked,407666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almLow.Alarm,407666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Fault,407676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almLowLow.AlarmState,407676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almLowLow.GlobalReset,407676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almLowLow.FaultInAlarm,407676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almLowLow.ALRM,407676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almLowLow.ANUN,407676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almLowLow.AKED,407676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almLowLow.Resetable,407676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almLowLow.REST,407676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almLowLow.ACKN,407676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almLowLow.UACK,407676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almLowLow.MCmd_Enable,407676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almLowLow.MCmd_Disable,407676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almLowLow.OCmd_Shelve,407676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almLowLow.OCmd_Unshelve,407676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almLowLow.SCmd_Suppress,407676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almLowLow.SCmd_UnSuppress,407677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almLowLow.AEShelveTMRDN,407677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almLowLow.Bad,407677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almLowLow.Suppress,407678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.UnSuppress,407678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Shelve,407678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.UnShelve,407678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Enable,407678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Disable,407678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Ack,407678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Reset,407678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Suppressed,407678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Shelved,407678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Disabled,407678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Acked,407678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almLowLow.Alarm,407678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Fault,407688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almBrokenLoop.AlarmState,407688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almBrokenLoop.GlobalReset,407688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almBrokenLoop.FaultInAlarm,407688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almBrokenLoop.ALRM,407688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almBrokenLoop.ANUN,407688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almBrokenLoop.AKED,407688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almBrokenLoop.Resetable,407688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almBrokenLoop.REST,407688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almBrokenLoop.ACKN,407688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almBrokenLoop.UACK,407688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almBrokenLoop.MCmd_Enable,407688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.MCmd_Disable,407688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.OCmd_Shelve,407688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.OCmd_Unshelve,407688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.SCmd_Suppress,407688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.SCmd_UnSuppress,407689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almBrokenLoop.AEShelveTMRDN,407689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almBrokenLoop.Bad,407689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almBrokenLoop.Suppress,407690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.UnSuppress,407690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Shelve,407690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.UnShelve,407690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Enable,407690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Disable,407690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Ack,407690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Reset,407690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Suppressed,407690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Shelved,407690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Disabled,407690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Acked,407690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.Alarm,407690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Fault,407700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almOverRange.AlarmState,407700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almOverRange.GlobalReset,407700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almOverRange.FaultInAlarm,407700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almOverRange.ALRM,407700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almOverRange.ANUN,407700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almOverRange.AKED,407700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almOverRange.Resetable,407700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almOverRange.REST,407700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almOverRange.ACKN,407700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almOverRange.UACK,407700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almOverRange.MCmd_Enable,407700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almOverRange.MCmd_Disable,407700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almOverRange.OCmd_Shelve,407700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almOverRange.OCmd_Unshelve,407700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almOverRange.SCmd_Suppress,407700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almOverRange.SCmd_UnSuppress,407701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almOverRange.AEShelveTMRDN,407701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almOverRange.Bad,407701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almOverRange.Suppress,407702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.UnSuppress,407702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Shelve,407702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.UnShelve,407702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Enable,407702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Disable,407702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Ack,407702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Reset,407702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Suppressed,407702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Shelved,407702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Disabled,407702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Acked,407702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almOverRange.Alarm,407702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Fault,407712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almUnderRange.AlarmState,407712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almUnderRange.GlobalReset,407712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almUnderRange.FaultInAlarm,407712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almUnderRange.ALRM,407712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almUnderRange.ANUN,407712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almUnderRange.AKED,407712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almUnderRange.Resetable,407712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almUnderRange.REST,407712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almUnderRange.ACKN,407712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almUnderRange.UACK,407712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almUnderRange.MCmd_Enable,407712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.MCmd_Disable,407712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.OCmd_Shelve,407712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.OCmd_Unshelve,407712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.SCmd_Suppress,407712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.SCmd_UnSuppress,407713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almUnderRange.AEShelveTMRDN,407713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almUnderRange.Bad,407713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almUnderRange.Suppress,407714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.UnSuppress,407714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Shelve,407714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.UnShelve,407714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Enable,407714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Disable,407714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Ack,407714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Reset,407714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Suppressed,407714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Shelved,407714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Disabled,407714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Acked,407714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almUnderRange.Alarm,407714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Fault,407724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almRateOfChange.AlarmState,407724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almRateOfChange.GlobalReset,407724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almRateOfChange.FaultInAlarm,407724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almRateOfChange.ALRM,407724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almRateOfChange.ANUN,407724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almRateOfChange.AKED,407724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almRateOfChange.Resetable,407724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almRateOfChange.REST,407724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almRateOfChange.ACKN,407724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almRateOfChange.UACK,407724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almRateOfChange.MCmd_Enable,407724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.MCmd_Disable,407724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.OCmd_Shelve,407724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.OCmd_Unshelve,407724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.SCmd_Suppress,407724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.SCmd_UnSuppress,407725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almRateOfChange.AEShelveTMRDN,407725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almRateOfChange.Bad,407725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almRateOfChange.Suppress,407726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.UnSuppress,407726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Shelve,407726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.UnShelve,407726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Enable,407726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Disable,407726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Ack,407726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Reset,407726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Suppressed,407726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Shelved,407726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Disabled,407726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Acked,407726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almRateOfChange.Alarm,407726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Fault,407736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_1_VI4.almPLCFault.AlarmState,407736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_1_VI4.almPLCFault.GlobalReset,407736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_1_VI4.almPLCFault.FaultInAlarm,407736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_1_VI4.almPLCFault.ALRM,407736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_1_VI4.almPLCFault.ANUN,407736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_1_VI4.almPLCFault.AKED,407736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_1_VI4.almPLCFault.Resetable,407736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_1_VI4.almPLCFault.REST,407736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_1_VI4.almPLCFault.ACKN,407736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_1_VI4.almPLCFault.UACK,407736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_1_VI4.almPLCFault.MCmd_Enable,407736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.MCmd_Disable,407736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.OCmd_Shelve,407736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.OCmd_Unshelve,407736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.SCmd_Suppress,407736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.SCmd_UnSuppress,407737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_1_VI4.almPLCFault.AEShelveTMRDN,407737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_1_VI4.almPLCFault.Bad,407737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_1_VI4.almPLCFault.Suppress,407738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.UnSuppress,407738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Shelve,407738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.UnShelve,407738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Enable,407738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Disable,407738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Ack,407738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Reset,407738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Suppressed,407738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Shelved,407738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Disabled,407738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Acked,407738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_1_VI4.almPLCFault.Alarm,407738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Fault,407840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almHighHigh.AlarmState,407840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almHighHigh.GlobalReset,407840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almHighHigh.FaultInAlarm,407840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almHighHigh.ALRM,407840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almHighHigh.ANUN,407840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almHighHigh.AKED,407840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almHighHigh.Resetable,407840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almHighHigh.REST,407840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almHighHigh.ACKN,407840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almHighHigh.UACK,407840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almHighHigh.MCmd_Enable,407840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.MCmd_Disable,407840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.OCmd_Shelve,407840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.OCmd_Unshelve,407840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.SCmd_Suppress,407840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.SCmd_UnSuppress,407841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almHighHigh.AEShelveTMRDN,407841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almHighHigh.Bad,407841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almHighHigh.Suppress,407842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.UnSuppress,407842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Shelve,407842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.UnShelve,407842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Enable,407842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Disable,407842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Ack,407842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Reset,407842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Suppressed,407842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Shelved,407842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Disabled,407842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Acked,407842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almHighHigh.Alarm,407842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Fault,407852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almHigh.AlarmState,407852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almHigh.GlobalReset,407852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almHigh.FaultInAlarm,407852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almHigh.ALRM,407852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almHigh.ANUN,407852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almHigh.AKED,407852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almHigh.Resetable,407852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almHigh.REST,407852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almHigh.ACKN,407852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almHigh.UACK,407852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almHigh.MCmd_Enable,407852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almHigh.MCmd_Disable,407852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almHigh.OCmd_Shelve,407852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almHigh.OCmd_Unshelve,407852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almHigh.SCmd_Suppress,407852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almHigh.SCmd_UnSuppress,407853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almHigh.AEShelveTMRDN,407853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almHigh.Bad,407853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almHigh.Suppress,407854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.UnSuppress,407854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Shelve,407854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.UnShelve,407854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Enable,407854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Disable,407854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Ack,407854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Reset,407854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almHigh.Suppressed,407854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almHigh.Shelved,407854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almHigh.Disabled,407854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almHigh.Acked,407854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almHigh.Alarm,407854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Fault,407864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almLow.AlarmState,407864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almLow.GlobalReset,407864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almLow.FaultInAlarm,407864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almLow.ALRM,407864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almLow.ANUN,407864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almLow.AKED,407864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almLow.Resetable,407864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almLow.REST,407864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almLow.ACKN,407864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almLow.UACK,407864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almLow.MCmd_Enable,407864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almLow.MCmd_Disable,407864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almLow.OCmd_Shelve,407864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almLow.OCmd_Unshelve,407864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almLow.SCmd_Suppress,407864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almLow.SCmd_UnSuppress,407865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almLow.AEShelveTMRDN,407865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almLow.Bad,407865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almLow.Suppress,407866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.UnSuppress,407866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Shelve,407866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.UnShelve,407866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Enable,407866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Disable,407866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Ack,407866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Reset,407866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almLow.Suppressed,407866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almLow.Shelved,407866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almLow.Disabled,407866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almLow.Acked,407866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almLow.Alarm,407866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Fault,407876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almLowLow.AlarmState,407876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almLowLow.GlobalReset,407876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almLowLow.FaultInAlarm,407876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almLowLow.ALRM,407876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almLowLow.ANUN,407876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almLowLow.AKED,407876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almLowLow.Resetable,407876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almLowLow.REST,407876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almLowLow.ACKN,407876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almLowLow.UACK,407876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almLowLow.MCmd_Enable,407876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almLowLow.MCmd_Disable,407876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almLowLow.OCmd_Shelve,407876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almLowLow.OCmd_Unshelve,407876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almLowLow.SCmd_Suppress,407876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almLowLow.SCmd_UnSuppress,407877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almLowLow.AEShelveTMRDN,407877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almLowLow.Bad,407877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almLowLow.Suppress,407878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.UnSuppress,407878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Shelve,407878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.UnShelve,407878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Enable,407878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Disable,407878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Ack,407878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Reset,407878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Suppressed,407878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Shelved,407878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Disabled,407878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Acked,407878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almLowLow.Alarm,407878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Fault,407888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almBrokenLoop.AlarmState,407888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almBrokenLoop.GlobalReset,407888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almBrokenLoop.FaultInAlarm,407888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almBrokenLoop.ALRM,407888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almBrokenLoop.ANUN,407888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almBrokenLoop.AKED,407888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almBrokenLoop.Resetable,407888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almBrokenLoop.REST,407888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almBrokenLoop.ACKN,407888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almBrokenLoop.UACK,407888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almBrokenLoop.MCmd_Enable,407888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.MCmd_Disable,407888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.OCmd_Shelve,407888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.OCmd_Unshelve,407888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.SCmd_Suppress,407888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.SCmd_UnSuppress,407889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almBrokenLoop.AEShelveTMRDN,407889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almBrokenLoop.Bad,407889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almBrokenLoop.Suppress,407890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.UnSuppress,407890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Shelve,407890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.UnShelve,407890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Enable,407890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Disable,407890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Ack,407890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Reset,407890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Suppressed,407890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Shelved,407890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Disabled,407890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Acked,407890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.Alarm,407890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Fault,407900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almOverRange.AlarmState,407900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almOverRange.GlobalReset,407900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almOverRange.FaultInAlarm,407900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almOverRange.ALRM,407900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almOverRange.ANUN,407900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almOverRange.AKED,407900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almOverRange.Resetable,407900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almOverRange.REST,407900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almOverRange.ACKN,407900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almOverRange.UACK,407900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almOverRange.MCmd_Enable,407900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almOverRange.MCmd_Disable,407900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almOverRange.OCmd_Shelve,407900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almOverRange.OCmd_Unshelve,407900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almOverRange.SCmd_Suppress,407900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almOverRange.SCmd_UnSuppress,407901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almOverRange.AEShelveTMRDN,407901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almOverRange.Bad,407901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almOverRange.Suppress,407902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.UnSuppress,407902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Shelve,407902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.UnShelve,407902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Enable,407902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Disable,407902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Ack,407902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Reset,407902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Suppressed,407902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Shelved,407902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Disabled,407902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Acked,407902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almOverRange.Alarm,407902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Fault,407912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almUnderRange.AlarmState,407912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almUnderRange.GlobalReset,407912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almUnderRange.FaultInAlarm,407912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almUnderRange.ALRM,407912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almUnderRange.ANUN,407912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almUnderRange.AKED,407912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almUnderRange.Resetable,407912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almUnderRange.REST,407912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almUnderRange.ACKN,407912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almUnderRange.UACK,407912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almUnderRange.MCmd_Enable,407912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.MCmd_Disable,407912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.OCmd_Shelve,407912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.OCmd_Unshelve,407912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.SCmd_Suppress,407912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.SCmd_UnSuppress,407913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almUnderRange.AEShelveTMRDN,407913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almUnderRange.Bad,407913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almUnderRange.Suppress,407914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.UnSuppress,407914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Shelve,407914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.UnShelve,407914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Enable,407914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Disable,407914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Ack,407914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Reset,407914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Suppressed,407914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Shelved,407914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Disabled,407914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Acked,407914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almUnderRange.Alarm,407914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Fault,407924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almRateOfChange.AlarmState,407924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almRateOfChange.GlobalReset,407924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almRateOfChange.FaultInAlarm,407924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almRateOfChange.ALRM,407924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almRateOfChange.ANUN,407924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almRateOfChange.AKED,407924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almRateOfChange.Resetable,407924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almRateOfChange.REST,407924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almRateOfChange.ACKN,407924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almRateOfChange.UACK,407924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almRateOfChange.MCmd_Enable,407924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.MCmd_Disable,407924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.OCmd_Shelve,407924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.OCmd_Unshelve,407924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.SCmd_Suppress,407924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.SCmd_UnSuppress,407925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almRateOfChange.AEShelveTMRDN,407925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almRateOfChange.Bad,407925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almRateOfChange.Suppress,407926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.UnSuppress,407926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Shelve,407926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.UnShelve,407926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Enable,407926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Disable,407926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Ack,407926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Reset,407926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Suppressed,407926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Shelved,407926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Disabled,407926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Acked,407926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almRateOfChange.Alarm,407926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Fault,407936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI1.almPLCFault.AlarmState,407936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI1.almPLCFault.GlobalReset,407936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI1.almPLCFault.FaultInAlarm,407936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI1.almPLCFault.ALRM,407936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI1.almPLCFault.ANUN,407936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI1.almPLCFault.AKED,407936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI1.almPLCFault.Resetable,407936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI1.almPLCFault.REST,407936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI1.almPLCFault.ACKN,407936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI1.almPLCFault.UACK,407936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI1.almPLCFault.MCmd_Enable,407936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.MCmd_Disable,407936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.OCmd_Shelve,407936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.OCmd_Unshelve,407936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.SCmd_Suppress,407936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.SCmd_UnSuppress,407937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI1.almPLCFault.AEShelveTMRDN,407937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI1.almPLCFault.Bad,407937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI1.almPLCFault.Suppress,407938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.UnSuppress,407938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Shelve,407938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.UnShelve,407938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Enable,407938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Disable,407938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Ack,407938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Reset,407938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Suppressed,407938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Shelved,407938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Disabled,407938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Acked,407938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI1.almPLCFault.Alarm,407938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Fault,408040.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almHighHigh.AlarmState,408040.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almHighHigh.GlobalReset,408040.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almHighHigh.FaultInAlarm,408040.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almHighHigh.ALRM,408040.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almHighHigh.ANUN,408040.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almHighHigh.AKED,408040.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almHighHigh.Resetable,408040.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almHighHigh.REST,408040.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almHighHigh.ACKN,408040.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almHighHigh.UACK,408040.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almHighHigh.MCmd_Enable,408040.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.MCmd_Disable,408040.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.OCmd_Shelve,408040.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.OCmd_Unshelve,408040.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.SCmd_Suppress,408040.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.SCmd_UnSuppress,408041.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almHighHigh.AEShelveTMRDN,408041.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almHighHigh.Bad,408041.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almHighHigh.Suppress,408042.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.UnSuppress,408042.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Shelve,408042.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.UnShelve,408042.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Enable,408042.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Disable,408042.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Ack,408042.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Reset,408042.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Suppressed,408042.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Shelved,408042.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Disabled,408042.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Acked,408042.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almHighHigh.Alarm,408042.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Fault,408052.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almHigh.AlarmState,408052.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almHigh.GlobalReset,408052.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almHigh.FaultInAlarm,408052.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almHigh.ALRM,408052.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almHigh.ANUN,408052.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almHigh.AKED,408052.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almHigh.Resetable,408052.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almHigh.REST,408052.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almHigh.ACKN,408052.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almHigh.UACK,408052.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almHigh.MCmd_Enable,408052.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almHigh.MCmd_Disable,408052.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almHigh.OCmd_Shelve,408052.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almHigh.OCmd_Unshelve,408052.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almHigh.SCmd_Suppress,408052.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almHigh.SCmd_UnSuppress,408053.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almHigh.AEShelveTMRDN,408053.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almHigh.Bad,408053.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almHigh.Suppress,408054.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.UnSuppress,408054.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Shelve,408054.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.UnShelve,408054.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Enable,408054.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Disable,408054.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Ack,408054.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Reset,408054.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almHigh.Suppressed,408054.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almHigh.Shelved,408054.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almHigh.Disabled,408054.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almHigh.Acked,408054.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almHigh.Alarm,408054.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Fault,408064.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almLow.AlarmState,408064.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almLow.GlobalReset,408064.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almLow.FaultInAlarm,408064.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almLow.ALRM,408064.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almLow.ANUN,408064.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almLow.AKED,408064.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almLow.Resetable,408064.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almLow.REST,408064.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almLow.ACKN,408064.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almLow.UACK,408064.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almLow.MCmd_Enable,408064.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almLow.MCmd_Disable,408064.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almLow.OCmd_Shelve,408064.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almLow.OCmd_Unshelve,408064.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almLow.SCmd_Suppress,408064.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almLow.SCmd_UnSuppress,408065.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almLow.AEShelveTMRDN,408065.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almLow.Bad,408065.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almLow.Suppress,408066.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.UnSuppress,408066.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Shelve,408066.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.UnShelve,408066.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Enable,408066.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Disable,408066.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Ack,408066.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Reset,408066.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almLow.Suppressed,408066.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almLow.Shelved,408066.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almLow.Disabled,408066.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almLow.Acked,408066.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almLow.Alarm,408066.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Fault,408076.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almLowLow.AlarmState,408076.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almLowLow.GlobalReset,408076.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almLowLow.FaultInAlarm,408076.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almLowLow.ALRM,408076.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almLowLow.ANUN,408076.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almLowLow.AKED,408076.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almLowLow.Resetable,408076.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almLowLow.REST,408076.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almLowLow.ACKN,408076.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almLowLow.UACK,408076.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almLowLow.MCmd_Enable,408076.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almLowLow.MCmd_Disable,408076.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almLowLow.OCmd_Shelve,408076.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almLowLow.OCmd_Unshelve,408076.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almLowLow.SCmd_Suppress,408076.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almLowLow.SCmd_UnSuppress,408077.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almLowLow.AEShelveTMRDN,408077.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almLowLow.Bad,408077.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almLowLow.Suppress,408078.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.UnSuppress,408078.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Shelve,408078.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.UnShelve,408078.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Enable,408078.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Disable,408078.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Ack,408078.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Reset,408078.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Suppressed,408078.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Shelved,408078.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Disabled,408078.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Acked,408078.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almLowLow.Alarm,408078.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Fault,408088.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almBrokenLoop.AlarmState,408088.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almBrokenLoop.GlobalReset,408088.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almBrokenLoop.FaultInAlarm,408088.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almBrokenLoop.ALRM,408088.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almBrokenLoop.ANUN,408088.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almBrokenLoop.AKED,408088.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almBrokenLoop.Resetable,408088.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almBrokenLoop.REST,408088.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almBrokenLoop.ACKN,408088.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almBrokenLoop.UACK,408088.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almBrokenLoop.MCmd_Enable,408088.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.MCmd_Disable,408088.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.OCmd_Shelve,408088.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.OCmd_Unshelve,408088.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.SCmd_Suppress,408088.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.SCmd_UnSuppress,408089.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almBrokenLoop.AEShelveTMRDN,408089.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almBrokenLoop.Bad,408089.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almBrokenLoop.Suppress,408090.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.UnSuppress,408090.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Shelve,408090.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.UnShelve,408090.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Enable,408090.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Disable,408090.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Ack,408090.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Reset,408090.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Suppressed,408090.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Shelved,408090.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Disabled,408090.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Acked,408090.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.Alarm,408090.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Fault,408100.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almOverRange.AlarmState,408100.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almOverRange.GlobalReset,408100.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almOverRange.FaultInAlarm,408100.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almOverRange.ALRM,408100.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almOverRange.ANUN,408100.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almOverRange.AKED,408100.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almOverRange.Resetable,408100.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almOverRange.REST,408100.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almOverRange.ACKN,408100.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almOverRange.UACK,408100.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almOverRange.MCmd_Enable,408100.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almOverRange.MCmd_Disable,408100.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almOverRange.OCmd_Shelve,408100.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almOverRange.OCmd_Unshelve,408100.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almOverRange.SCmd_Suppress,408100.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almOverRange.SCmd_UnSuppress,408101.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almOverRange.AEShelveTMRDN,408101.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almOverRange.Bad,408101.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almOverRange.Suppress,408102.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.UnSuppress,408102.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Shelve,408102.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.UnShelve,408102.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Enable,408102.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Disable,408102.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Ack,408102.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Reset,408102.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Suppressed,408102.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Shelved,408102.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Disabled,408102.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Acked,408102.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almOverRange.Alarm,408102.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Fault,408112.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almUnderRange.AlarmState,408112.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almUnderRange.GlobalReset,408112.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almUnderRange.FaultInAlarm,408112.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almUnderRange.ALRM,408112.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almUnderRange.ANUN,408112.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almUnderRange.AKED,408112.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almUnderRange.Resetable,408112.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almUnderRange.REST,408112.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almUnderRange.ACKN,408112.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almUnderRange.UACK,408112.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almUnderRange.MCmd_Enable,408112.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.MCmd_Disable,408112.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.OCmd_Shelve,408112.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.OCmd_Unshelve,408112.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.SCmd_Suppress,408112.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.SCmd_UnSuppress,408113.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almUnderRange.AEShelveTMRDN,408113.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almUnderRange.Bad,408113.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almUnderRange.Suppress,408114.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.UnSuppress,408114.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Shelve,408114.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.UnShelve,408114.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Enable,408114.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Disable,408114.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Ack,408114.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Reset,408114.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Suppressed,408114.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Shelved,408114.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Disabled,408114.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Acked,408114.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almUnderRange.Alarm,408114.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Fault,408124.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almRateOfChange.AlarmState,408124.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almRateOfChange.GlobalReset,408124.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almRateOfChange.FaultInAlarm,408124.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almRateOfChange.ALRM,408124.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almRateOfChange.ANUN,408124.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almRateOfChange.AKED,408124.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almRateOfChange.Resetable,408124.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almRateOfChange.REST,408124.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almRateOfChange.ACKN,408124.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almRateOfChange.UACK,408124.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almRateOfChange.MCmd_Enable,408124.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.MCmd_Disable,408124.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.OCmd_Shelve,408124.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.OCmd_Unshelve,408124.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.SCmd_Suppress,408124.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.SCmd_UnSuppress,408125.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almRateOfChange.AEShelveTMRDN,408125.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almRateOfChange.Bad,408125.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almRateOfChange.Suppress,408126.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.UnSuppress,408126.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Shelve,408126.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.UnShelve,408126.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Enable,408126.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Disable,408126.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Ack,408126.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Reset,408126.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Suppressed,408126.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Shelved,408126.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Disabled,408126.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Acked,408126.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almRateOfChange.Alarm,408126.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Fault,408136.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI2.almPLCFault.AlarmState,408136.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI2.almPLCFault.GlobalReset,408136.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI2.almPLCFault.FaultInAlarm,408136.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI2.almPLCFault.ALRM,408136.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI2.almPLCFault.ANUN,408136.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI2.almPLCFault.AKED,408136.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI2.almPLCFault.Resetable,408136.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI2.almPLCFault.REST,408136.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI2.almPLCFault.ACKN,408136.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI2.almPLCFault.UACK,408136.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI2.almPLCFault.MCmd_Enable,408136.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.MCmd_Disable,408136.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.OCmd_Shelve,408136.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.OCmd_Unshelve,408136.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.SCmd_Suppress,408136.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.SCmd_UnSuppress,408137.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI2.almPLCFault.AEShelveTMRDN,408137.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI2.almPLCFault.Bad,408137.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI2.almPLCFault.Suppress,408138.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.UnSuppress,408138.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Shelve,408138.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.UnShelve,408138.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Enable,408138.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Disable,408138.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Ack,408138.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Reset,408138.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Suppressed,408138.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Shelved,408138.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Disabled,408138.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Acked,408138.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI2.almPLCFault.Alarm,408138.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Fault,408240.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almHighHigh.AlarmState,408240.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almHighHigh.GlobalReset,408240.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almHighHigh.FaultInAlarm,408240.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almHighHigh.ALRM,408240.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almHighHigh.ANUN,408240.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almHighHigh.AKED,408240.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almHighHigh.Resetable,408240.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almHighHigh.REST,408240.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almHighHigh.ACKN,408240.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almHighHigh.UACK,408240.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almHighHigh.MCmd_Enable,408240.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.MCmd_Disable,408240.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.OCmd_Shelve,408240.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.OCmd_Unshelve,408240.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.SCmd_Suppress,408240.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.SCmd_UnSuppress,408241.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almHighHigh.AEShelveTMRDN,408241.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almHighHigh.Bad,408241.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almHighHigh.Suppress,408242.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.UnSuppress,408242.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Shelve,408242.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.UnShelve,408242.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Enable,408242.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Disable,408242.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Ack,408242.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Reset,408242.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Suppressed,408242.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Shelved,408242.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Disabled,408242.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Acked,408242.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almHighHigh.Alarm,408242.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Fault,408252.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almHigh.AlarmState,408252.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almHigh.GlobalReset,408252.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almHigh.FaultInAlarm,408252.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almHigh.ALRM,408252.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almHigh.ANUN,408252.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almHigh.AKED,408252.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almHigh.Resetable,408252.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almHigh.REST,408252.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almHigh.ACKN,408252.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almHigh.UACK,408252.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almHigh.MCmd_Enable,408252.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almHigh.MCmd_Disable,408252.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almHigh.OCmd_Shelve,408252.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almHigh.OCmd_Unshelve,408252.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almHigh.SCmd_Suppress,408252.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almHigh.SCmd_UnSuppress,408253.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almHigh.AEShelveTMRDN,408253.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almHigh.Bad,408253.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almHigh.Suppress,408254.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.UnSuppress,408254.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Shelve,408254.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.UnShelve,408254.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Enable,408254.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Disable,408254.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Ack,408254.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Reset,408254.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almHigh.Suppressed,408254.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almHigh.Shelved,408254.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almHigh.Disabled,408254.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almHigh.Acked,408254.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almHigh.Alarm,408254.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Fault,408264.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almLow.AlarmState,408264.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almLow.GlobalReset,408264.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almLow.FaultInAlarm,408264.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almLow.ALRM,408264.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almLow.ANUN,408264.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almLow.AKED,408264.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almLow.Resetable,408264.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almLow.REST,408264.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almLow.ACKN,408264.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almLow.UACK,408264.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almLow.MCmd_Enable,408264.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almLow.MCmd_Disable,408264.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almLow.OCmd_Shelve,408264.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almLow.OCmd_Unshelve,408264.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almLow.SCmd_Suppress,408264.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almLow.SCmd_UnSuppress,408265.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almLow.AEShelveTMRDN,408265.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almLow.Bad,408265.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almLow.Suppress,408266.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.UnSuppress,408266.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Shelve,408266.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.UnShelve,408266.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Enable,408266.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Disable,408266.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Ack,408266.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Reset,408266.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almLow.Suppressed,408266.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almLow.Shelved,408266.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almLow.Disabled,408266.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almLow.Acked,408266.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almLow.Alarm,408266.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Fault,408276.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almLowLow.AlarmState,408276.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almLowLow.GlobalReset,408276.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almLowLow.FaultInAlarm,408276.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almLowLow.ALRM,408276.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almLowLow.ANUN,408276.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almLowLow.AKED,408276.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almLowLow.Resetable,408276.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almLowLow.REST,408276.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almLowLow.ACKN,408276.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almLowLow.UACK,408276.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almLowLow.MCmd_Enable,408276.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almLowLow.MCmd_Disable,408276.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almLowLow.OCmd_Shelve,408276.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almLowLow.OCmd_Unshelve,408276.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almLowLow.SCmd_Suppress,408276.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almLowLow.SCmd_UnSuppress,408277.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almLowLow.AEShelveTMRDN,408277.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almLowLow.Bad,408277.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almLowLow.Suppress,408278.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.UnSuppress,408278.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Shelve,408278.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.UnShelve,408278.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Enable,408278.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Disable,408278.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Ack,408278.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Reset,408278.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Suppressed,408278.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Shelved,408278.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Disabled,408278.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Acked,408278.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almLowLow.Alarm,408278.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Fault,408288.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almBrokenLoop.AlarmState,408288.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almBrokenLoop.GlobalReset,408288.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almBrokenLoop.FaultInAlarm,408288.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almBrokenLoop.ALRM,408288.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almBrokenLoop.ANUN,408288.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almBrokenLoop.AKED,408288.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almBrokenLoop.Resetable,408288.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almBrokenLoop.REST,408288.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almBrokenLoop.ACKN,408288.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almBrokenLoop.UACK,408288.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almBrokenLoop.MCmd_Enable,408288.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.MCmd_Disable,408288.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.OCmd_Shelve,408288.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.OCmd_Unshelve,408288.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.SCmd_Suppress,408288.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.SCmd_UnSuppress,408289.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almBrokenLoop.AEShelveTMRDN,408289.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almBrokenLoop.Bad,408289.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almBrokenLoop.Suppress,408290.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.UnSuppress,408290.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Shelve,408290.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.UnShelve,408290.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Enable,408290.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Disable,408290.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Ack,408290.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Reset,408290.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Suppressed,408290.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Shelved,408290.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Disabled,408290.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Acked,408290.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.Alarm,408290.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Fault,408300.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almOverRange.AlarmState,408300.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almOverRange.GlobalReset,408300.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almOverRange.FaultInAlarm,408300.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almOverRange.ALRM,408300.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almOverRange.ANUN,408300.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almOverRange.AKED,408300.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almOverRange.Resetable,408300.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almOverRange.REST,408300.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almOverRange.ACKN,408300.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almOverRange.UACK,408300.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almOverRange.MCmd_Enable,408300.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almOverRange.MCmd_Disable,408300.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almOverRange.OCmd_Shelve,408300.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almOverRange.OCmd_Unshelve,408300.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almOverRange.SCmd_Suppress,408300.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almOverRange.SCmd_UnSuppress,408301.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almOverRange.AEShelveTMRDN,408301.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almOverRange.Bad,408301.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almOverRange.Suppress,408302.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.UnSuppress,408302.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Shelve,408302.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.UnShelve,408302.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Enable,408302.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Disable,408302.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Ack,408302.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Reset,408302.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Suppressed,408302.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Shelved,408302.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Disabled,408302.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Acked,408302.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almOverRange.Alarm,408302.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Fault,408312.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almUnderRange.AlarmState,408312.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almUnderRange.GlobalReset,408312.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almUnderRange.FaultInAlarm,408312.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almUnderRange.ALRM,408312.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almUnderRange.ANUN,408312.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almUnderRange.AKED,408312.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almUnderRange.Resetable,408312.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almUnderRange.REST,408312.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almUnderRange.ACKN,408312.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almUnderRange.UACK,408312.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almUnderRange.MCmd_Enable,408312.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.MCmd_Disable,408312.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.OCmd_Shelve,408312.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.OCmd_Unshelve,408312.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.SCmd_Suppress,408312.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.SCmd_UnSuppress,408313.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almUnderRange.AEShelveTMRDN,408313.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almUnderRange.Bad,408313.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almUnderRange.Suppress,408314.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.UnSuppress,408314.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Shelve,408314.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.UnShelve,408314.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Enable,408314.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Disable,408314.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Ack,408314.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Reset,408314.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Suppressed,408314.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Shelved,408314.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Disabled,408314.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Acked,408314.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almUnderRange.Alarm,408314.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Fault,408324.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almRateOfChange.AlarmState,408324.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almRateOfChange.GlobalReset,408324.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almRateOfChange.FaultInAlarm,408324.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almRateOfChange.ALRM,408324.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almRateOfChange.ANUN,408324.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almRateOfChange.AKED,408324.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almRateOfChange.Resetable,408324.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almRateOfChange.REST,408324.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almRateOfChange.ACKN,408324.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almRateOfChange.UACK,408324.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almRateOfChange.MCmd_Enable,408324.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.MCmd_Disable,408324.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.OCmd_Shelve,408324.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.OCmd_Unshelve,408324.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.SCmd_Suppress,408324.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.SCmd_UnSuppress,408325.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almRateOfChange.AEShelveTMRDN,408325.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almRateOfChange.Bad,408325.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almRateOfChange.Suppress,408326.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.UnSuppress,408326.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Shelve,408326.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.UnShelve,408326.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Enable,408326.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Disable,408326.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Ack,408326.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Reset,408326.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Suppressed,408326.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Shelved,408326.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Disabled,408326.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Acked,408326.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almRateOfChange.Alarm,408326.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Fault,408336.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI3.almPLCFault.AlarmState,408336.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI3.almPLCFault.GlobalReset,408336.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI3.almPLCFault.FaultInAlarm,408336.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI3.almPLCFault.ALRM,408336.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI3.almPLCFault.ANUN,408336.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI3.almPLCFault.AKED,408336.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI3.almPLCFault.Resetable,408336.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI3.almPLCFault.REST,408336.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI3.almPLCFault.ACKN,408336.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI3.almPLCFault.UACK,408336.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI3.almPLCFault.MCmd_Enable,408336.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.MCmd_Disable,408336.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.OCmd_Shelve,408336.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.OCmd_Unshelve,408336.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.SCmd_Suppress,408336.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.SCmd_UnSuppress,408337.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI3.almPLCFault.AEShelveTMRDN,408337.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI3.almPLCFault.Bad,408337.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI3.almPLCFault.Suppress,408338.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.UnSuppress,408338.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Shelve,408338.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.UnShelve,408338.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Enable,408338.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Disable,408338.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Ack,408338.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Reset,408338.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Suppressed,408338.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Shelved,408338.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Disabled,408338.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Acked,408338.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI3.almPLCFault.Alarm,408338.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Fault,408440.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almHighHigh.AlarmState,408440.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almHighHigh.GlobalReset,408440.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almHighHigh.FaultInAlarm,408440.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almHighHigh.ALRM,408440.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almHighHigh.ANUN,408440.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almHighHigh.AKED,408440.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almHighHigh.Resetable,408440.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almHighHigh.REST,408440.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almHighHigh.ACKN,408440.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almHighHigh.UACK,408440.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almHighHigh.MCmd_Enable,408440.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.MCmd_Disable,408440.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.OCmd_Shelve,408440.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.OCmd_Unshelve,408440.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.SCmd_Suppress,408440.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.SCmd_UnSuppress,408441.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almHighHigh.AEShelveTMRDN,408441.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almHighHigh.Bad,408441.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almHighHigh.Suppress,408442.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.UnSuppress,408442.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Shelve,408442.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.UnShelve,408442.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Enable,408442.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Disable,408442.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Ack,408442.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Reset,408442.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Suppressed,408442.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Shelved,408442.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Disabled,408442.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Acked,408442.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almHighHigh.Alarm,408442.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Fault,408452.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almHigh.AlarmState,408452.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almHigh.GlobalReset,408452.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almHigh.FaultInAlarm,408452.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almHigh.ALRM,408452.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almHigh.ANUN,408452.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almHigh.AKED,408452.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almHigh.Resetable,408452.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almHigh.REST,408452.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almHigh.ACKN,408452.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almHigh.UACK,408452.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almHigh.MCmd_Enable,408452.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almHigh.MCmd_Disable,408452.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almHigh.OCmd_Shelve,408452.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almHigh.OCmd_Unshelve,408452.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almHigh.SCmd_Suppress,408452.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almHigh.SCmd_UnSuppress,408453.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almHigh.AEShelveTMRDN,408453.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almHigh.Bad,408453.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almHigh.Suppress,408454.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.UnSuppress,408454.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Shelve,408454.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.UnShelve,408454.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Enable,408454.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Disable,408454.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Ack,408454.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Reset,408454.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almHigh.Suppressed,408454.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almHigh.Shelved,408454.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almHigh.Disabled,408454.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almHigh.Acked,408454.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almHigh.Alarm,408454.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Fault,408464.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almLow.AlarmState,408464.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almLow.GlobalReset,408464.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almLow.FaultInAlarm,408464.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almLow.ALRM,408464.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almLow.ANUN,408464.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almLow.AKED,408464.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almLow.Resetable,408464.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almLow.REST,408464.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almLow.ACKN,408464.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almLow.UACK,408464.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almLow.MCmd_Enable,408464.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almLow.MCmd_Disable,408464.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almLow.OCmd_Shelve,408464.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almLow.OCmd_Unshelve,408464.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almLow.SCmd_Suppress,408464.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almLow.SCmd_UnSuppress,408465.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almLow.AEShelveTMRDN,408465.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almLow.Bad,408465.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almLow.Suppress,408466.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.UnSuppress,408466.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Shelve,408466.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.UnShelve,408466.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Enable,408466.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Disable,408466.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Ack,408466.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Reset,408466.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almLow.Suppressed,408466.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almLow.Shelved,408466.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almLow.Disabled,408466.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almLow.Acked,408466.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almLow.Alarm,408466.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Fault,408476.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almLowLow.AlarmState,408476.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almLowLow.GlobalReset,408476.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almLowLow.FaultInAlarm,408476.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almLowLow.ALRM,408476.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almLowLow.ANUN,408476.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almLowLow.AKED,408476.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almLowLow.Resetable,408476.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almLowLow.REST,408476.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almLowLow.ACKN,408476.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almLowLow.UACK,408476.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almLowLow.MCmd_Enable,408476.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almLowLow.MCmd_Disable,408476.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almLowLow.OCmd_Shelve,408476.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almLowLow.OCmd_Unshelve,408476.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almLowLow.SCmd_Suppress,408476.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almLowLow.SCmd_UnSuppress,408477.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almLowLow.AEShelveTMRDN,408477.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almLowLow.Bad,408477.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almLowLow.Suppress,408478.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.UnSuppress,408478.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Shelve,408478.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.UnShelve,408478.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Enable,408478.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Disable,408478.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Ack,408478.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Reset,408478.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Suppressed,408478.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Shelved,408478.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Disabled,408478.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Acked,408478.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almLowLow.Alarm,408478.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Fault,408488.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almBrokenLoop.AlarmState,408488.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almBrokenLoop.GlobalReset,408488.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almBrokenLoop.FaultInAlarm,408488.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almBrokenLoop.ALRM,408488.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almBrokenLoop.ANUN,408488.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almBrokenLoop.AKED,408488.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almBrokenLoop.Resetable,408488.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almBrokenLoop.REST,408488.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almBrokenLoop.ACKN,408488.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almBrokenLoop.UACK,408488.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almBrokenLoop.MCmd_Enable,408488.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.MCmd_Disable,408488.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.OCmd_Shelve,408488.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.OCmd_Unshelve,408488.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.SCmd_Suppress,408488.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.SCmd_UnSuppress,408489.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almBrokenLoop.AEShelveTMRDN,408489.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almBrokenLoop.Bad,408489.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almBrokenLoop.Suppress,408490.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.UnSuppress,408490.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Shelve,408490.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.UnShelve,408490.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Enable,408490.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Disable,408490.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Ack,408490.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Reset,408490.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Suppressed,408490.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Shelved,408490.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Disabled,408490.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Acked,408490.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.Alarm,408490.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Fault,408500.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almOverRange.AlarmState,408500.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almOverRange.GlobalReset,408500.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almOverRange.FaultInAlarm,408500.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almOverRange.ALRM,408500.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almOverRange.ANUN,408500.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almOverRange.AKED,408500.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almOverRange.Resetable,408500.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almOverRange.REST,408500.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almOverRange.ACKN,408500.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almOverRange.UACK,408500.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almOverRange.MCmd_Enable,408500.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almOverRange.MCmd_Disable,408500.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almOverRange.OCmd_Shelve,408500.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almOverRange.OCmd_Unshelve,408500.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almOverRange.SCmd_Suppress,408500.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almOverRange.SCmd_UnSuppress,408501.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almOverRange.AEShelveTMRDN,408501.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almOverRange.Bad,408501.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almOverRange.Suppress,408502.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.UnSuppress,408502.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Shelve,408502.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.UnShelve,408502.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Enable,408502.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Disable,408502.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Ack,408502.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Reset,408502.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Suppressed,408502.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Shelved,408502.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Disabled,408502.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Acked,408502.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almOverRange.Alarm,408502.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Fault,408512.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almUnderRange.AlarmState,408512.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almUnderRange.GlobalReset,408512.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almUnderRange.FaultInAlarm,408512.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almUnderRange.ALRM,408512.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almUnderRange.ANUN,408512.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almUnderRange.AKED,408512.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almUnderRange.Resetable,408512.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almUnderRange.REST,408512.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almUnderRange.ACKN,408512.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almUnderRange.UACK,408512.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almUnderRange.MCmd_Enable,408512.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.MCmd_Disable,408512.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.OCmd_Shelve,408512.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.OCmd_Unshelve,408512.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.SCmd_Suppress,408512.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.SCmd_UnSuppress,408513.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almUnderRange.AEShelveTMRDN,408513.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almUnderRange.Bad,408513.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almUnderRange.Suppress,408514.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.UnSuppress,408514.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Shelve,408514.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.UnShelve,408514.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Enable,408514.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Disable,408514.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Ack,408514.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Reset,408514.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Suppressed,408514.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Shelved,408514.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Disabled,408514.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Acked,408514.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almUnderRange.Alarm,408514.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Fault,408524.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almRateOfChange.AlarmState,408524.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almRateOfChange.GlobalReset,408524.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almRateOfChange.FaultInAlarm,408524.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almRateOfChange.ALRM,408524.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almRateOfChange.ANUN,408524.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almRateOfChange.AKED,408524.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almRateOfChange.Resetable,408524.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almRateOfChange.REST,408524.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almRateOfChange.ACKN,408524.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almRateOfChange.UACK,408524.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almRateOfChange.MCmd_Enable,408524.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.MCmd_Disable,408524.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.OCmd_Shelve,408524.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.OCmd_Unshelve,408524.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.SCmd_Suppress,408524.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.SCmd_UnSuppress,408525.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almRateOfChange.AEShelveTMRDN,408525.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almRateOfChange.Bad,408525.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almRateOfChange.Suppress,408526.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.UnSuppress,408526.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Shelve,408526.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.UnShelve,408526.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Enable,408526.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Disable,408526.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Ack,408526.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Reset,408526.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Suppressed,408526.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Shelved,408526.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Disabled,408526.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Acked,408526.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almRateOfChange.Alarm,408526.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Fault,408536.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_2_VI4.almPLCFault.AlarmState,408536.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_2_VI4.almPLCFault.GlobalReset,408536.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_2_VI4.almPLCFault.FaultInAlarm,408536.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_2_VI4.almPLCFault.ALRM,408536.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_2_VI4.almPLCFault.ANUN,408536.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_2_VI4.almPLCFault.AKED,408536.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_2_VI4.almPLCFault.Resetable,408536.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_2_VI4.almPLCFault.REST,408536.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_2_VI4.almPLCFault.ACKN,408536.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_2_VI4.almPLCFault.UACK,408536.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_2_VI4.almPLCFault.MCmd_Enable,408536.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.MCmd_Disable,408536.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.OCmd_Shelve,408536.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.OCmd_Unshelve,408536.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.SCmd_Suppress,408536.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.SCmd_UnSuppress,408537.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_2_VI4.almPLCFault.AEShelveTMRDN,408537.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_2_VI4.almPLCFault.Bad,408537.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_2_VI4.almPLCFault.Suppress,408538.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.UnSuppress,408538.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Shelve,408538.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.UnShelve,408538.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Enable,408538.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Disable,408538.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Ack,408538.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Reset,408538.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Suppressed,408538.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Shelved,408538.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Disabled,408538.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Acked,408538.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_2_VI4.almPLCFault.Alarm,408538.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Fault,408640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almHighHigh.AlarmState,408640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almHighHigh.GlobalReset,408640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almHighHigh.FaultInAlarm,408640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almHighHigh.ALRM,408640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almHighHigh.ANUN,408640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almHighHigh.AKED,408640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almHighHigh.Resetable,408640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almHighHigh.REST,408640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almHighHigh.ACKN,408640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almHighHigh.UACK,408640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almHighHigh.MCmd_Enable,408640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.MCmd_Disable,408640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.OCmd_Shelve,408640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.OCmd_Unshelve,408640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.SCmd_Suppress,408640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.SCmd_UnSuppress,408641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almHighHigh.AEShelveTMRDN,408641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almHighHigh.Bad,408641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almHighHigh.Suppress,408642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.UnSuppress,408642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Shelve,408642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.UnShelve,408642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Enable,408642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Disable,408642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Ack,408642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Reset,408642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Suppressed,408642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Shelved,408642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Disabled,408642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Acked,408642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almHighHigh.Alarm,408642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Fault,408652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almHigh.AlarmState,408652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almHigh.GlobalReset,408652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almHigh.FaultInAlarm,408652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almHigh.ALRM,408652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almHigh.ANUN,408652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almHigh.AKED,408652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almHigh.Resetable,408652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almHigh.REST,408652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almHigh.ACKN,408652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almHigh.UACK,408652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almHigh.MCmd_Enable,408652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almHigh.MCmd_Disable,408652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almHigh.OCmd_Shelve,408652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almHigh.OCmd_Unshelve,408652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almHigh.SCmd_Suppress,408652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almHigh.SCmd_UnSuppress,408653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almHigh.AEShelveTMRDN,408653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almHigh.Bad,408653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almHigh.Suppress,408654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.UnSuppress,408654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Shelve,408654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.UnShelve,408654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Enable,408654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Disable,408654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Ack,408654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Reset,408654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almHigh.Suppressed,408654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almHigh.Shelved,408654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almHigh.Disabled,408654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almHigh.Acked,408654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almHigh.Alarm,408654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Fault,408664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almLow.AlarmState,408664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almLow.GlobalReset,408664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almLow.FaultInAlarm,408664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almLow.ALRM,408664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almLow.ANUN,408664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almLow.AKED,408664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almLow.Resetable,408664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almLow.REST,408664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almLow.ACKN,408664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almLow.UACK,408664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almLow.MCmd_Enable,408664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almLow.MCmd_Disable,408664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almLow.OCmd_Shelve,408664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almLow.OCmd_Unshelve,408664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almLow.SCmd_Suppress,408664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almLow.SCmd_UnSuppress,408665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almLow.AEShelveTMRDN,408665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almLow.Bad,408665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almLow.Suppress,408666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.UnSuppress,408666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Shelve,408666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.UnShelve,408666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Enable,408666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Disable,408666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Ack,408666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Reset,408666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almLow.Suppressed,408666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almLow.Shelved,408666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almLow.Disabled,408666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almLow.Acked,408666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almLow.Alarm,408666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Fault,408676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almLowLow.AlarmState,408676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almLowLow.GlobalReset,408676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almLowLow.FaultInAlarm,408676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almLowLow.ALRM,408676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almLowLow.ANUN,408676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almLowLow.AKED,408676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almLowLow.Resetable,408676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almLowLow.REST,408676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almLowLow.ACKN,408676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almLowLow.UACK,408676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almLowLow.MCmd_Enable,408676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almLowLow.MCmd_Disable,408676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almLowLow.OCmd_Shelve,408676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almLowLow.OCmd_Unshelve,408676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almLowLow.SCmd_Suppress,408676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almLowLow.SCmd_UnSuppress,408677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almLowLow.AEShelveTMRDN,408677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almLowLow.Bad,408677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almLowLow.Suppress,408678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.UnSuppress,408678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Shelve,408678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.UnShelve,408678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Enable,408678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Disable,408678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Ack,408678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Reset,408678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Suppressed,408678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Shelved,408678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Disabled,408678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Acked,408678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almLowLow.Alarm,408678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Fault,408688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almBrokenLoop.AlarmState,408688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almBrokenLoop.GlobalReset,408688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almBrokenLoop.FaultInAlarm,408688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almBrokenLoop.ALRM,408688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almBrokenLoop.ANUN,408688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almBrokenLoop.AKED,408688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almBrokenLoop.Resetable,408688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almBrokenLoop.REST,408688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almBrokenLoop.ACKN,408688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almBrokenLoop.UACK,408688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almBrokenLoop.MCmd_Enable,408688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.MCmd_Disable,408688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.OCmd_Shelve,408688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.OCmd_Unshelve,408688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.SCmd_Suppress,408688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.SCmd_UnSuppress,408689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almBrokenLoop.AEShelveTMRDN,408689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almBrokenLoop.Bad,408689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almBrokenLoop.Suppress,408690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.UnSuppress,408690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Shelve,408690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.UnShelve,408690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Enable,408690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Disable,408690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Ack,408690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Reset,408690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Suppressed,408690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Shelved,408690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Disabled,408690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Acked,408690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.Alarm,408690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Fault,408700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almOverRange.AlarmState,408700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almOverRange.GlobalReset,408700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almOverRange.FaultInAlarm,408700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almOverRange.ALRM,408700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almOverRange.ANUN,408700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almOverRange.AKED,408700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almOverRange.Resetable,408700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almOverRange.REST,408700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almOverRange.ACKN,408700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almOverRange.UACK,408700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almOverRange.MCmd_Enable,408700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almOverRange.MCmd_Disable,408700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almOverRange.OCmd_Shelve,408700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almOverRange.OCmd_Unshelve,408700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almOverRange.SCmd_Suppress,408700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almOverRange.SCmd_UnSuppress,408701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almOverRange.AEShelveTMRDN,408701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almOverRange.Bad,408701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almOverRange.Suppress,408702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.UnSuppress,408702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Shelve,408702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.UnShelve,408702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Enable,408702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Disable,408702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Ack,408702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Reset,408702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Suppressed,408702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Shelved,408702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Disabled,408702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Acked,408702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almOverRange.Alarm,408702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Fault,408712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almUnderRange.AlarmState,408712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almUnderRange.GlobalReset,408712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almUnderRange.FaultInAlarm,408712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almUnderRange.ALRM,408712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almUnderRange.ANUN,408712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almUnderRange.AKED,408712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almUnderRange.Resetable,408712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almUnderRange.REST,408712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almUnderRange.ACKN,408712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almUnderRange.UACK,408712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almUnderRange.MCmd_Enable,408712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.MCmd_Disable,408712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.OCmd_Shelve,408712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.OCmd_Unshelve,408712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.SCmd_Suppress,408712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.SCmd_UnSuppress,408713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almUnderRange.AEShelveTMRDN,408713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almUnderRange.Bad,408713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almUnderRange.Suppress,408714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.UnSuppress,408714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Shelve,408714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.UnShelve,408714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Enable,408714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Disable,408714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Ack,408714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Reset,408714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Suppressed,408714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Shelved,408714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Disabled,408714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Acked,408714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almUnderRange.Alarm,408714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Fault,408724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almRateOfChange.AlarmState,408724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almRateOfChange.GlobalReset,408724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almRateOfChange.FaultInAlarm,408724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almRateOfChange.ALRM,408724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almRateOfChange.ANUN,408724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almRateOfChange.AKED,408724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almRateOfChange.Resetable,408724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almRateOfChange.REST,408724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almRateOfChange.ACKN,408724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almRateOfChange.UACK,408724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almRateOfChange.MCmd_Enable,408724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.MCmd_Disable,408724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.OCmd_Shelve,408724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.OCmd_Unshelve,408724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.SCmd_Suppress,408724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.SCmd_UnSuppress,408725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almRateOfChange.AEShelveTMRDN,408725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almRateOfChange.Bad,408725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almRateOfChange.Suppress,408726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.UnSuppress,408726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Shelve,408726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.UnShelve,408726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Enable,408726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Disable,408726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Ack,408726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Reset,408726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Suppressed,408726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Shelved,408726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Disabled,408726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Acked,408726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almRateOfChange.Alarm,408726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Fault,408736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI1.almPLCFault.AlarmState,408736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI1.almPLCFault.GlobalReset,408736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI1.almPLCFault.FaultInAlarm,408736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI1.almPLCFault.ALRM,408736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI1.almPLCFault.ANUN,408736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI1.almPLCFault.AKED,408736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI1.almPLCFault.Resetable,408736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI1.almPLCFault.REST,408736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI1.almPLCFault.ACKN,408736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI1.almPLCFault.UACK,408736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI1.almPLCFault.MCmd_Enable,408736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.MCmd_Disable,408736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.OCmd_Shelve,408736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.OCmd_Unshelve,408736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.SCmd_Suppress,408736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.SCmd_UnSuppress,408737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI1.almPLCFault.AEShelveTMRDN,408737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI1.almPLCFault.Bad,408737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI1.almPLCFault.Suppress,408738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.UnSuppress,408738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Shelve,408738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.UnShelve,408738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Enable,408738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Disable,408738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Ack,408738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Reset,408738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Suppressed,408738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Shelved,408738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Disabled,408738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Acked,408738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI1.almPLCFault.Alarm,408738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Fault,408840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almHighHigh.AlarmState,408840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almHighHigh.GlobalReset,408840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almHighHigh.FaultInAlarm,408840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almHighHigh.ALRM,408840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almHighHigh.ANUN,408840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almHighHigh.AKED,408840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almHighHigh.Resetable,408840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almHighHigh.REST,408840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almHighHigh.ACKN,408840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almHighHigh.UACK,408840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almHighHigh.MCmd_Enable,408840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.MCmd_Disable,408840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.OCmd_Shelve,408840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.OCmd_Unshelve,408840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.SCmd_Suppress,408840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.SCmd_UnSuppress,408841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almHighHigh.AEShelveTMRDN,408841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almHighHigh.Bad,408841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almHighHigh.Suppress,408842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.UnSuppress,408842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Shelve,408842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.UnShelve,408842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Enable,408842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Disable,408842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Ack,408842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Reset,408842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Suppressed,408842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Shelved,408842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Disabled,408842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Acked,408842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almHighHigh.Alarm,408842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Fault,408852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almHigh.AlarmState,408852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almHigh.GlobalReset,408852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almHigh.FaultInAlarm,408852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almHigh.ALRM,408852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almHigh.ANUN,408852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almHigh.AKED,408852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almHigh.Resetable,408852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almHigh.REST,408852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almHigh.ACKN,408852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almHigh.UACK,408852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almHigh.MCmd_Enable,408852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almHigh.MCmd_Disable,408852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almHigh.OCmd_Shelve,408852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almHigh.OCmd_Unshelve,408852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almHigh.SCmd_Suppress,408852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almHigh.SCmd_UnSuppress,408853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almHigh.AEShelveTMRDN,408853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almHigh.Bad,408853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almHigh.Suppress,408854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.UnSuppress,408854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Shelve,408854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.UnShelve,408854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Enable,408854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Disable,408854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Ack,408854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Reset,408854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almHigh.Suppressed,408854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almHigh.Shelved,408854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almHigh.Disabled,408854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almHigh.Acked,408854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almHigh.Alarm,408854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Fault,408864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almLow.AlarmState,408864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almLow.GlobalReset,408864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almLow.FaultInAlarm,408864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almLow.ALRM,408864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almLow.ANUN,408864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almLow.AKED,408864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almLow.Resetable,408864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almLow.REST,408864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almLow.ACKN,408864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almLow.UACK,408864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almLow.MCmd_Enable,408864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almLow.MCmd_Disable,408864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almLow.OCmd_Shelve,408864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almLow.OCmd_Unshelve,408864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almLow.SCmd_Suppress,408864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almLow.SCmd_UnSuppress,408865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almLow.AEShelveTMRDN,408865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almLow.Bad,408865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almLow.Suppress,408866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.UnSuppress,408866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Shelve,408866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.UnShelve,408866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Enable,408866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Disable,408866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Ack,408866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Reset,408866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almLow.Suppressed,408866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almLow.Shelved,408866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almLow.Disabled,408866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almLow.Acked,408866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almLow.Alarm,408866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Fault,408876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almLowLow.AlarmState,408876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almLowLow.GlobalReset,408876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almLowLow.FaultInAlarm,408876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almLowLow.ALRM,408876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almLowLow.ANUN,408876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almLowLow.AKED,408876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almLowLow.Resetable,408876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almLowLow.REST,408876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almLowLow.ACKN,408876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almLowLow.UACK,408876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almLowLow.MCmd_Enable,408876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almLowLow.MCmd_Disable,408876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almLowLow.OCmd_Shelve,408876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almLowLow.OCmd_Unshelve,408876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almLowLow.SCmd_Suppress,408876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almLowLow.SCmd_UnSuppress,408877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almLowLow.AEShelveTMRDN,408877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almLowLow.Bad,408877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almLowLow.Suppress,408878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.UnSuppress,408878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Shelve,408878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.UnShelve,408878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Enable,408878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Disable,408878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Ack,408878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Reset,408878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Suppressed,408878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Shelved,408878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Disabled,408878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Acked,408878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almLowLow.Alarm,408878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Fault,408888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almBrokenLoop.AlarmState,408888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almBrokenLoop.GlobalReset,408888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almBrokenLoop.FaultInAlarm,408888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almBrokenLoop.ALRM,408888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almBrokenLoop.ANUN,408888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almBrokenLoop.AKED,408888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almBrokenLoop.Resetable,408888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almBrokenLoop.REST,408888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almBrokenLoop.ACKN,408888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almBrokenLoop.UACK,408888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almBrokenLoop.MCmd_Enable,408888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.MCmd_Disable,408888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.OCmd_Shelve,408888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.OCmd_Unshelve,408888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.SCmd_Suppress,408888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.SCmd_UnSuppress,408889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almBrokenLoop.AEShelveTMRDN,408889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almBrokenLoop.Bad,408889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almBrokenLoop.Suppress,408890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.UnSuppress,408890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Shelve,408890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.UnShelve,408890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Enable,408890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Disable,408890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Ack,408890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Reset,408890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Suppressed,408890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Shelved,408890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Disabled,408890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Acked,408890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.Alarm,408890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Fault,408900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almOverRange.AlarmState,408900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almOverRange.GlobalReset,408900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almOverRange.FaultInAlarm,408900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almOverRange.ALRM,408900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almOverRange.ANUN,408900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almOverRange.AKED,408900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almOverRange.Resetable,408900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almOverRange.REST,408900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almOverRange.ACKN,408900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almOverRange.UACK,408900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almOverRange.MCmd_Enable,408900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almOverRange.MCmd_Disable,408900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almOverRange.OCmd_Shelve,408900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almOverRange.OCmd_Unshelve,408900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almOverRange.SCmd_Suppress,408900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almOverRange.SCmd_UnSuppress,408901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almOverRange.AEShelveTMRDN,408901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almOverRange.Bad,408901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almOverRange.Suppress,408902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.UnSuppress,408902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Shelve,408902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.UnShelve,408902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Enable,408902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Disable,408902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Ack,408902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Reset,408902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Suppressed,408902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Shelved,408902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Disabled,408902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Acked,408902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almOverRange.Alarm,408902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Fault,408912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almUnderRange.AlarmState,408912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almUnderRange.GlobalReset,408912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almUnderRange.FaultInAlarm,408912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almUnderRange.ALRM,408912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almUnderRange.ANUN,408912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almUnderRange.AKED,408912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almUnderRange.Resetable,408912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almUnderRange.REST,408912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almUnderRange.ACKN,408912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almUnderRange.UACK,408912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almUnderRange.MCmd_Enable,408912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.MCmd_Disable,408912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.OCmd_Shelve,408912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.OCmd_Unshelve,408912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.SCmd_Suppress,408912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.SCmd_UnSuppress,408913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almUnderRange.AEShelveTMRDN,408913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almUnderRange.Bad,408913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almUnderRange.Suppress,408914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.UnSuppress,408914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Shelve,408914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.UnShelve,408914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Enable,408914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Disable,408914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Ack,408914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Reset,408914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Suppressed,408914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Shelved,408914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Disabled,408914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Acked,408914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almUnderRange.Alarm,408914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Fault,408924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almRateOfChange.AlarmState,408924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almRateOfChange.GlobalReset,408924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almRateOfChange.FaultInAlarm,408924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almRateOfChange.ALRM,408924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almRateOfChange.ANUN,408924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almRateOfChange.AKED,408924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almRateOfChange.Resetable,408924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almRateOfChange.REST,408924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almRateOfChange.ACKN,408924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almRateOfChange.UACK,408924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almRateOfChange.MCmd_Enable,408924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.MCmd_Disable,408924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.OCmd_Shelve,408924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.OCmd_Unshelve,408924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.SCmd_Suppress,408924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.SCmd_UnSuppress,408925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almRateOfChange.AEShelveTMRDN,408925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almRateOfChange.Bad,408925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almRateOfChange.Suppress,408926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.UnSuppress,408926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Shelve,408926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.UnShelve,408926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Enable,408926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Disable,408926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Ack,408926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Reset,408926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Suppressed,408926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Shelved,408926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Disabled,408926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Acked,408926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almRateOfChange.Alarm,408926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Fault,408936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI2.almPLCFault.AlarmState,408936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI2.almPLCFault.GlobalReset,408936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI2.almPLCFault.FaultInAlarm,408936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI2.almPLCFault.ALRM,408936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI2.almPLCFault.ANUN,408936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI2.almPLCFault.AKED,408936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI2.almPLCFault.Resetable,408936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI2.almPLCFault.REST,408936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI2.almPLCFault.ACKN,408936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI2.almPLCFault.UACK,408936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI2.almPLCFault.MCmd_Enable,408936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.MCmd_Disable,408936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.OCmd_Shelve,408936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.OCmd_Unshelve,408936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.SCmd_Suppress,408936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.SCmd_UnSuppress,408937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI2.almPLCFault.AEShelveTMRDN,408937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI2.almPLCFault.Bad,408937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI2.almPLCFault.Suppress,408938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.UnSuppress,408938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Shelve,408938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.UnShelve,408938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Enable,408938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Disable,408938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Ack,408938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Reset,408938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Suppressed,408938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Shelved,408938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Disabled,408938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Acked,408938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI2.almPLCFault.Alarm,408938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Fault,409040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almHighHigh.AlarmState,409040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almHighHigh.GlobalReset,409040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almHighHigh.FaultInAlarm,409040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almHighHigh.ALRM,409040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almHighHigh.ANUN,409040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almHighHigh.AKED,409040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almHighHigh.Resetable,409040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almHighHigh.REST,409040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almHighHigh.ACKN,409040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almHighHigh.UACK,409040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almHighHigh.MCmd_Enable,409040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.MCmd_Disable,409040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.OCmd_Shelve,409040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.OCmd_Unshelve,409040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.SCmd_Suppress,409040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.SCmd_UnSuppress,409041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almHighHigh.AEShelveTMRDN,409041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almHighHigh.Bad,409041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almHighHigh.Suppress,409042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.UnSuppress,409042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Shelve,409042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.UnShelve,409042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Enable,409042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Disable,409042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Ack,409042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Reset,409042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Suppressed,409042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Shelved,409042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Disabled,409042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Acked,409042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almHighHigh.Alarm,409042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Fault,409052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almHigh.AlarmState,409052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almHigh.GlobalReset,409052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almHigh.FaultInAlarm,409052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almHigh.ALRM,409052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almHigh.ANUN,409052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almHigh.AKED,409052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almHigh.Resetable,409052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almHigh.REST,409052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almHigh.ACKN,409052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almHigh.UACK,409052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almHigh.MCmd_Enable,409052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almHigh.MCmd_Disable,409052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almHigh.OCmd_Shelve,409052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almHigh.OCmd_Unshelve,409052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almHigh.SCmd_Suppress,409052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almHigh.SCmd_UnSuppress,409053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almHigh.AEShelveTMRDN,409053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almHigh.Bad,409053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almHigh.Suppress,409054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.UnSuppress,409054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Shelve,409054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.UnShelve,409054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Enable,409054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Disable,409054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Ack,409054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Reset,409054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almHigh.Suppressed,409054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almHigh.Shelved,409054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almHigh.Disabled,409054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almHigh.Acked,409054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almHigh.Alarm,409054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Fault,409064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almLow.AlarmState,409064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almLow.GlobalReset,409064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almLow.FaultInAlarm,409064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almLow.ALRM,409064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almLow.ANUN,409064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almLow.AKED,409064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almLow.Resetable,409064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almLow.REST,409064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almLow.ACKN,409064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almLow.UACK,409064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almLow.MCmd_Enable,409064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almLow.MCmd_Disable,409064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almLow.OCmd_Shelve,409064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almLow.OCmd_Unshelve,409064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almLow.SCmd_Suppress,409064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almLow.SCmd_UnSuppress,409065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almLow.AEShelveTMRDN,409065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almLow.Bad,409065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almLow.Suppress,409066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.UnSuppress,409066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Shelve,409066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.UnShelve,409066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Enable,409066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Disable,409066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Ack,409066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Reset,409066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almLow.Suppressed,409066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almLow.Shelved,409066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almLow.Disabled,409066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almLow.Acked,409066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almLow.Alarm,409066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Fault,409076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almLowLow.AlarmState,409076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almLowLow.GlobalReset,409076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almLowLow.FaultInAlarm,409076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almLowLow.ALRM,409076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almLowLow.ANUN,409076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almLowLow.AKED,409076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almLowLow.Resetable,409076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almLowLow.REST,409076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almLowLow.ACKN,409076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almLowLow.UACK,409076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almLowLow.MCmd_Enable,409076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almLowLow.MCmd_Disable,409076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almLowLow.OCmd_Shelve,409076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almLowLow.OCmd_Unshelve,409076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almLowLow.SCmd_Suppress,409076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almLowLow.SCmd_UnSuppress,409077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almLowLow.AEShelveTMRDN,409077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almLowLow.Bad,409077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almLowLow.Suppress,409078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.UnSuppress,409078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Shelve,409078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.UnShelve,409078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Enable,409078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Disable,409078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Ack,409078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Reset,409078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Suppressed,409078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Shelved,409078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Disabled,409078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Acked,409078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almLowLow.Alarm,409078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Fault,409088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almBrokenLoop.AlarmState,409088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almBrokenLoop.GlobalReset,409088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almBrokenLoop.FaultInAlarm,409088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almBrokenLoop.ALRM,409088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almBrokenLoop.ANUN,409088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almBrokenLoop.AKED,409088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almBrokenLoop.Resetable,409088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almBrokenLoop.REST,409088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almBrokenLoop.ACKN,409088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almBrokenLoop.UACK,409088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almBrokenLoop.MCmd_Enable,409088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.MCmd_Disable,409088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.OCmd_Shelve,409088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.OCmd_Unshelve,409088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.SCmd_Suppress,409088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.SCmd_UnSuppress,409089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almBrokenLoop.AEShelveTMRDN,409089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almBrokenLoop.Bad,409089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almBrokenLoop.Suppress,409090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.UnSuppress,409090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Shelve,409090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.UnShelve,409090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Enable,409090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Disable,409090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Ack,409090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Reset,409090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Suppressed,409090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Shelved,409090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Disabled,409090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Acked,409090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.Alarm,409090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Fault,409100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almOverRange.AlarmState,409100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almOverRange.GlobalReset,409100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almOverRange.FaultInAlarm,409100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almOverRange.ALRM,409100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almOverRange.ANUN,409100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almOverRange.AKED,409100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almOverRange.Resetable,409100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almOverRange.REST,409100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almOverRange.ACKN,409100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almOverRange.UACK,409100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almOverRange.MCmd_Enable,409100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almOverRange.MCmd_Disable,409100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almOverRange.OCmd_Shelve,409100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almOverRange.OCmd_Unshelve,409100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almOverRange.SCmd_Suppress,409100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almOverRange.SCmd_UnSuppress,409101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almOverRange.AEShelveTMRDN,409101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almOverRange.Bad,409101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almOverRange.Suppress,409102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.UnSuppress,409102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Shelve,409102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.UnShelve,409102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Enable,409102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Disable,409102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Ack,409102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Reset,409102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Suppressed,409102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Shelved,409102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Disabled,409102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Acked,409102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almOverRange.Alarm,409102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Fault,409112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almUnderRange.AlarmState,409112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almUnderRange.GlobalReset,409112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almUnderRange.FaultInAlarm,409112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almUnderRange.ALRM,409112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almUnderRange.ANUN,409112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almUnderRange.AKED,409112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almUnderRange.Resetable,409112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almUnderRange.REST,409112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almUnderRange.ACKN,409112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almUnderRange.UACK,409112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almUnderRange.MCmd_Enable,409112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.MCmd_Disable,409112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.OCmd_Shelve,409112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.OCmd_Unshelve,409112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.SCmd_Suppress,409112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.SCmd_UnSuppress,409113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almUnderRange.AEShelveTMRDN,409113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almUnderRange.Bad,409113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almUnderRange.Suppress,409114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.UnSuppress,409114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Shelve,409114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.UnShelve,409114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Enable,409114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Disable,409114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Ack,409114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Reset,409114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Suppressed,409114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Shelved,409114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Disabled,409114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Acked,409114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almUnderRange.Alarm,409114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Fault,409124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almRateOfChange.AlarmState,409124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almRateOfChange.GlobalReset,409124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almRateOfChange.FaultInAlarm,409124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almRateOfChange.ALRM,409124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almRateOfChange.ANUN,409124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almRateOfChange.AKED,409124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almRateOfChange.Resetable,409124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almRateOfChange.REST,409124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almRateOfChange.ACKN,409124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almRateOfChange.UACK,409124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almRateOfChange.MCmd_Enable,409124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.MCmd_Disable,409124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.OCmd_Shelve,409124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.OCmd_Unshelve,409124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.SCmd_Suppress,409124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.SCmd_UnSuppress,409125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almRateOfChange.AEShelveTMRDN,409125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almRateOfChange.Bad,409125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almRateOfChange.Suppress,409126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.UnSuppress,409126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Shelve,409126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.UnShelve,409126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Enable,409126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Disable,409126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Ack,409126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Reset,409126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Suppressed,409126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Shelved,409126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Disabled,409126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Acked,409126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almRateOfChange.Alarm,409126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Fault,409136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI3.almPLCFault.AlarmState,409136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI3.almPLCFault.GlobalReset,409136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI3.almPLCFault.FaultInAlarm,409136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI3.almPLCFault.ALRM,409136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI3.almPLCFault.ANUN,409136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI3.almPLCFault.AKED,409136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI3.almPLCFault.Resetable,409136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI3.almPLCFault.REST,409136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI3.almPLCFault.ACKN,409136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI3.almPLCFault.UACK,409136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI3.almPLCFault.MCmd_Enable,409136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.MCmd_Disable,409136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.OCmd_Shelve,409136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.OCmd_Unshelve,409136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.SCmd_Suppress,409136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.SCmd_UnSuppress,409137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI3.almPLCFault.AEShelveTMRDN,409137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI3.almPLCFault.Bad,409137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI3.almPLCFault.Suppress,409138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.UnSuppress,409138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Shelve,409138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.UnShelve,409138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Enable,409138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Disable,409138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Ack,409138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Reset,409138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Suppressed,409138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Shelved,409138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Disabled,409138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Acked,409138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI3.almPLCFault.Alarm,409138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Fault,409240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almHighHigh.AlarmState,409240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almHighHigh.GlobalReset,409240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almHighHigh.FaultInAlarm,409240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almHighHigh.ALRM,409240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almHighHigh.ANUN,409240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almHighHigh.AKED,409240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almHighHigh.Resetable,409240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almHighHigh.REST,409240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almHighHigh.ACKN,409240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almHighHigh.UACK,409240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almHighHigh.MCmd_Enable,409240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.MCmd_Disable,409240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.OCmd_Shelve,409240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.OCmd_Unshelve,409240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.SCmd_Suppress,409240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.SCmd_UnSuppress,409241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almHighHigh.AEShelveTMRDN,409241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almHighHigh.Bad,409241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almHighHigh.Suppress,409242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.UnSuppress,409242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Shelve,409242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.UnShelve,409242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Enable,409242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Disable,409242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Ack,409242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Reset,409242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Suppressed,409242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Shelved,409242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Disabled,409242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Acked,409242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almHighHigh.Alarm,409242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Fault,409252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almHigh.AlarmState,409252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almHigh.GlobalReset,409252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almHigh.FaultInAlarm,409252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almHigh.ALRM,409252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almHigh.ANUN,409252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almHigh.AKED,409252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almHigh.Resetable,409252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almHigh.REST,409252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almHigh.ACKN,409252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almHigh.UACK,409252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almHigh.MCmd_Enable,409252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almHigh.MCmd_Disable,409252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almHigh.OCmd_Shelve,409252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almHigh.OCmd_Unshelve,409252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almHigh.SCmd_Suppress,409252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almHigh.SCmd_UnSuppress,409253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almHigh.AEShelveTMRDN,409253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almHigh.Bad,409253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almHigh.Suppress,409254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.UnSuppress,409254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Shelve,409254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.UnShelve,409254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Enable,409254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Disable,409254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Ack,409254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Reset,409254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almHigh.Suppressed,409254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almHigh.Shelved,409254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almHigh.Disabled,409254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almHigh.Acked,409254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almHigh.Alarm,409254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Fault,409264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almLow.AlarmState,409264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almLow.GlobalReset,409264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almLow.FaultInAlarm,409264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almLow.ALRM,409264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almLow.ANUN,409264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almLow.AKED,409264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almLow.Resetable,409264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almLow.REST,409264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almLow.ACKN,409264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almLow.UACK,409264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almLow.MCmd_Enable,409264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almLow.MCmd_Disable,409264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almLow.OCmd_Shelve,409264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almLow.OCmd_Unshelve,409264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almLow.SCmd_Suppress,409264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almLow.SCmd_UnSuppress,409265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almLow.AEShelveTMRDN,409265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almLow.Bad,409265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almLow.Suppress,409266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.UnSuppress,409266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Shelve,409266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.UnShelve,409266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Enable,409266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Disable,409266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Ack,409266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Reset,409266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almLow.Suppressed,409266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almLow.Shelved,409266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almLow.Disabled,409266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almLow.Acked,409266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almLow.Alarm,409266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Fault,409276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almLowLow.AlarmState,409276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almLowLow.GlobalReset,409276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almLowLow.FaultInAlarm,409276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almLowLow.ALRM,409276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almLowLow.ANUN,409276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almLowLow.AKED,409276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almLowLow.Resetable,409276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almLowLow.REST,409276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almLowLow.ACKN,409276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almLowLow.UACK,409276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almLowLow.MCmd_Enable,409276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almLowLow.MCmd_Disable,409276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almLowLow.OCmd_Shelve,409276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almLowLow.OCmd_Unshelve,409276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almLowLow.SCmd_Suppress,409276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almLowLow.SCmd_UnSuppress,409277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almLowLow.AEShelveTMRDN,409277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almLowLow.Bad,409277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almLowLow.Suppress,409278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.UnSuppress,409278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Shelve,409278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.UnShelve,409278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Enable,409278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Disable,409278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Ack,409278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Reset,409278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Suppressed,409278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Shelved,409278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Disabled,409278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Acked,409278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almLowLow.Alarm,409278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Fault,409288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almBrokenLoop.AlarmState,409288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almBrokenLoop.GlobalReset,409288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almBrokenLoop.FaultInAlarm,409288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almBrokenLoop.ALRM,409288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almBrokenLoop.ANUN,409288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almBrokenLoop.AKED,409288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almBrokenLoop.Resetable,409288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almBrokenLoop.REST,409288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almBrokenLoop.ACKN,409288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almBrokenLoop.UACK,409288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almBrokenLoop.MCmd_Enable,409288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.MCmd_Disable,409288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.OCmd_Shelve,409288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.OCmd_Unshelve,409288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.SCmd_Suppress,409288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.SCmd_UnSuppress,409289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almBrokenLoop.AEShelveTMRDN,409289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almBrokenLoop.Bad,409289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almBrokenLoop.Suppress,409290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.UnSuppress,409290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Shelve,409290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.UnShelve,409290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Enable,409290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Disable,409290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Ack,409290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Reset,409290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Suppressed,409290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Shelved,409290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Disabled,409290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Acked,409290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.Alarm,409290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Fault,409300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almOverRange.AlarmState,409300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almOverRange.GlobalReset,409300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almOverRange.FaultInAlarm,409300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almOverRange.ALRM,409300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almOverRange.ANUN,409300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almOverRange.AKED,409300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almOverRange.Resetable,409300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almOverRange.REST,409300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almOverRange.ACKN,409300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almOverRange.UACK,409300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almOverRange.MCmd_Enable,409300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almOverRange.MCmd_Disable,409300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almOverRange.OCmd_Shelve,409300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almOverRange.OCmd_Unshelve,409300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almOverRange.SCmd_Suppress,409300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almOverRange.SCmd_UnSuppress,409301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almOverRange.AEShelveTMRDN,409301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almOverRange.Bad,409301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almOverRange.Suppress,409302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.UnSuppress,409302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Shelve,409302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.UnShelve,409302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Enable,409302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Disable,409302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Ack,409302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Reset,409302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Suppressed,409302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Shelved,409302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Disabled,409302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Acked,409302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almOverRange.Alarm,409302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Fault,409312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almUnderRange.AlarmState,409312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almUnderRange.GlobalReset,409312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almUnderRange.FaultInAlarm,409312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almUnderRange.ALRM,409312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almUnderRange.ANUN,409312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almUnderRange.AKED,409312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almUnderRange.Resetable,409312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almUnderRange.REST,409312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almUnderRange.ACKN,409312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almUnderRange.UACK,409312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almUnderRange.MCmd_Enable,409312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.MCmd_Disable,409312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.OCmd_Shelve,409312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.OCmd_Unshelve,409312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.SCmd_Suppress,409312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.SCmd_UnSuppress,409313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almUnderRange.AEShelveTMRDN,409313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almUnderRange.Bad,409313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almUnderRange.Suppress,409314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.UnSuppress,409314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Shelve,409314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.UnShelve,409314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Enable,409314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Disable,409314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Ack,409314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Reset,409314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Suppressed,409314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Shelved,409314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Disabled,409314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Acked,409314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almUnderRange.Alarm,409314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Fault,409324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almRateOfChange.AlarmState,409324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almRateOfChange.GlobalReset,409324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almRateOfChange.FaultInAlarm,409324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almRateOfChange.ALRM,409324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almRateOfChange.ANUN,409324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almRateOfChange.AKED,409324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almRateOfChange.Resetable,409324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almRateOfChange.REST,409324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almRateOfChange.ACKN,409324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almRateOfChange.UACK,409324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almRateOfChange.MCmd_Enable,409324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.MCmd_Disable,409324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.OCmd_Shelve,409324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.OCmd_Unshelve,409324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.SCmd_Suppress,409324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.SCmd_UnSuppress,409325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almRateOfChange.AEShelveTMRDN,409325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almRateOfChange.Bad,409325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almRateOfChange.Suppress,409326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.UnSuppress,409326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Shelve,409326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.UnShelve,409326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Enable,409326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Disable,409326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Ack,409326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Reset,409326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Suppressed,409326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Shelved,409326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Disabled,409326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Acked,409326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almRateOfChange.Alarm,409326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Fault,409336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_3_VI4.almPLCFault.AlarmState,409336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_3_VI4.almPLCFault.GlobalReset,409336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_3_VI4.almPLCFault.FaultInAlarm,409336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_3_VI4.almPLCFault.ALRM,409336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_3_VI4.almPLCFault.ANUN,409336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_3_VI4.almPLCFault.AKED,409336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_3_VI4.almPLCFault.Resetable,409336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_3_VI4.almPLCFault.REST,409336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_3_VI4.almPLCFault.ACKN,409336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_3_VI4.almPLCFault.UACK,409336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_3_VI4.almPLCFault.MCmd_Enable,409336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.MCmd_Disable,409336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.OCmd_Shelve,409336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.OCmd_Unshelve,409336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.SCmd_Suppress,409336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.SCmd_UnSuppress,409337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_3_VI4.almPLCFault.AEShelveTMRDN,409337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_3_VI4.almPLCFault.Bad,409337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_3_VI4.almPLCFault.Suppress,409338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.UnSuppress,409338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Shelve,409338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.UnShelve,409338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Enable,409338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Disable,409338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Ack,409338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Reset,409338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Suppressed,409338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Shelved,409338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Disabled,409338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Acked,409338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_3_VI4.almPLCFault.Alarm,409338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Fault,409440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almHighHigh.AlarmState,409440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almHighHigh.GlobalReset,409440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almHighHigh.FaultInAlarm,409440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almHighHigh.ALRM,409440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almHighHigh.ANUN,409440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almHighHigh.AKED,409440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almHighHigh.Resetable,409440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almHighHigh.REST,409440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almHighHigh.ACKN,409440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almHighHigh.UACK,409440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almHighHigh.MCmd_Enable,409440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.MCmd_Disable,409440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.OCmd_Shelve,409440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.OCmd_Unshelve,409440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.SCmd_Suppress,409440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.SCmd_UnSuppress,409441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almHighHigh.AEShelveTMRDN,409441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almHighHigh.Bad,409441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almHighHigh.Suppress,409442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.UnSuppress,409442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Shelve,409442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.UnShelve,409442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Enable,409442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Disable,409442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Ack,409442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Reset,409442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Suppressed,409442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Shelved,409442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Disabled,409442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Acked,409442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almHighHigh.Alarm,409442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Fault,409452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almHigh.AlarmState,409452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almHigh.GlobalReset,409452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almHigh.FaultInAlarm,409452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almHigh.ALRM,409452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almHigh.ANUN,409452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almHigh.AKED,409452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almHigh.Resetable,409452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almHigh.REST,409452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almHigh.ACKN,409452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almHigh.UACK,409452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almHigh.MCmd_Enable,409452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almHigh.MCmd_Disable,409452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almHigh.OCmd_Shelve,409452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almHigh.OCmd_Unshelve,409452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almHigh.SCmd_Suppress,409452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almHigh.SCmd_UnSuppress,409453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almHigh.AEShelveTMRDN,409453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almHigh.Bad,409453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almHigh.Suppress,409454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.UnSuppress,409454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Shelve,409454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.UnShelve,409454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Enable,409454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Disable,409454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Ack,409454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Reset,409454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almHigh.Suppressed,409454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almHigh.Shelved,409454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almHigh.Disabled,409454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almHigh.Acked,409454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almHigh.Alarm,409454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Fault,409464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almLow.AlarmState,409464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almLow.GlobalReset,409464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almLow.FaultInAlarm,409464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almLow.ALRM,409464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almLow.ANUN,409464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almLow.AKED,409464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almLow.Resetable,409464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almLow.REST,409464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almLow.ACKN,409464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almLow.UACK,409464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almLow.MCmd_Enable,409464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almLow.MCmd_Disable,409464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almLow.OCmd_Shelve,409464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almLow.OCmd_Unshelve,409464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almLow.SCmd_Suppress,409464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almLow.SCmd_UnSuppress,409465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almLow.AEShelveTMRDN,409465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almLow.Bad,409465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almLow.Suppress,409466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.UnSuppress,409466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Shelve,409466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.UnShelve,409466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Enable,409466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Disable,409466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Ack,409466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Reset,409466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almLow.Suppressed,409466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almLow.Shelved,409466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almLow.Disabled,409466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almLow.Acked,409466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almLow.Alarm,409466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Fault,409476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almLowLow.AlarmState,409476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almLowLow.GlobalReset,409476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almLowLow.FaultInAlarm,409476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almLowLow.ALRM,409476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almLowLow.ANUN,409476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almLowLow.AKED,409476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almLowLow.Resetable,409476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almLowLow.REST,409476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almLowLow.ACKN,409476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almLowLow.UACK,409476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almLowLow.MCmd_Enable,409476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almLowLow.MCmd_Disable,409476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almLowLow.OCmd_Shelve,409476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almLowLow.OCmd_Unshelve,409476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almLowLow.SCmd_Suppress,409476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almLowLow.SCmd_UnSuppress,409477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almLowLow.AEShelveTMRDN,409477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almLowLow.Bad,409477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almLowLow.Suppress,409478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.UnSuppress,409478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Shelve,409478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.UnShelve,409478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Enable,409478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Disable,409478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Ack,409478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Reset,409478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Suppressed,409478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Shelved,409478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Disabled,409478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Acked,409478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almLowLow.Alarm,409478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Fault,409488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almBrokenLoop.AlarmState,409488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almBrokenLoop.GlobalReset,409488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almBrokenLoop.FaultInAlarm,409488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almBrokenLoop.ALRM,409488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almBrokenLoop.ANUN,409488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almBrokenLoop.AKED,409488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almBrokenLoop.Resetable,409488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almBrokenLoop.REST,409488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almBrokenLoop.ACKN,409488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almBrokenLoop.UACK,409488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almBrokenLoop.MCmd_Enable,409488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.MCmd_Disable,409488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.OCmd_Shelve,409488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.OCmd_Unshelve,409488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.SCmd_Suppress,409488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.SCmd_UnSuppress,409489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almBrokenLoop.AEShelveTMRDN,409489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almBrokenLoop.Bad,409489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almBrokenLoop.Suppress,409490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.UnSuppress,409490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Shelve,409490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.UnShelve,409490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Enable,409490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Disable,409490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Ack,409490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Reset,409490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Suppressed,409490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Shelved,409490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Disabled,409490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Acked,409490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.Alarm,409490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Fault,409500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almOverRange.AlarmState,409500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almOverRange.GlobalReset,409500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almOverRange.FaultInAlarm,409500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almOverRange.ALRM,409500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almOverRange.ANUN,409500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almOverRange.AKED,409500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almOverRange.Resetable,409500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almOverRange.REST,409500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almOverRange.ACKN,409500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almOverRange.UACK,409500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almOverRange.MCmd_Enable,409500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almOverRange.MCmd_Disable,409500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almOverRange.OCmd_Shelve,409500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almOverRange.OCmd_Unshelve,409500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almOverRange.SCmd_Suppress,409500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almOverRange.SCmd_UnSuppress,409501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almOverRange.AEShelveTMRDN,409501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almOverRange.Bad,409501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almOverRange.Suppress,409502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.UnSuppress,409502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Shelve,409502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.UnShelve,409502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Enable,409502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Disable,409502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Ack,409502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Reset,409502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Suppressed,409502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Shelved,409502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Disabled,409502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Acked,409502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almOverRange.Alarm,409502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Fault,409512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almUnderRange.AlarmState,409512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almUnderRange.GlobalReset,409512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almUnderRange.FaultInAlarm,409512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almUnderRange.ALRM,409512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almUnderRange.ANUN,409512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almUnderRange.AKED,409512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almUnderRange.Resetable,409512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almUnderRange.REST,409512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almUnderRange.ACKN,409512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almUnderRange.UACK,409512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almUnderRange.MCmd_Enable,409512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.MCmd_Disable,409512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.OCmd_Shelve,409512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.OCmd_Unshelve,409512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.SCmd_Suppress,409512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.SCmd_UnSuppress,409513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almUnderRange.AEShelveTMRDN,409513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almUnderRange.Bad,409513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almUnderRange.Suppress,409514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.UnSuppress,409514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Shelve,409514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.UnShelve,409514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Enable,409514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Disable,409514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Ack,409514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Reset,409514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Suppressed,409514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Shelved,409514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Disabled,409514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Acked,409514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almUnderRange.Alarm,409514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Fault,409524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almRateOfChange.AlarmState,409524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almRateOfChange.GlobalReset,409524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almRateOfChange.FaultInAlarm,409524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almRateOfChange.ALRM,409524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almRateOfChange.ANUN,409524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almRateOfChange.AKED,409524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almRateOfChange.Resetable,409524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almRateOfChange.REST,409524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almRateOfChange.ACKN,409524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almRateOfChange.UACK,409524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almRateOfChange.MCmd_Enable,409524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.MCmd_Disable,409524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.OCmd_Shelve,409524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.OCmd_Unshelve,409524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.SCmd_Suppress,409524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.SCmd_UnSuppress,409525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almRateOfChange.AEShelveTMRDN,409525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almRateOfChange.Bad,409525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almRateOfChange.Suppress,409526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.UnSuppress,409526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Shelve,409526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.UnShelve,409526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Enable,409526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Disable,409526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Ack,409526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Reset,409526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Suppressed,409526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Shelved,409526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Disabled,409526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Acked,409526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almRateOfChange.Alarm,409526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Fault,409536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI1.almPLCFault.AlarmState,409536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI1.almPLCFault.GlobalReset,409536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI1.almPLCFault.FaultInAlarm,409536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI1.almPLCFault.ALRM,409536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI1.almPLCFault.ANUN,409536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI1.almPLCFault.AKED,409536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI1.almPLCFault.Resetable,409536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI1.almPLCFault.REST,409536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI1.almPLCFault.ACKN,409536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI1.almPLCFault.UACK,409536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI1.almPLCFault.MCmd_Enable,409536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.MCmd_Disable,409536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.OCmd_Shelve,409536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.OCmd_Unshelve,409536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.SCmd_Suppress,409536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.SCmd_UnSuppress,409537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI1.almPLCFault.AEShelveTMRDN,409537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI1.almPLCFault.Bad,409537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI1.almPLCFault.Suppress,409538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.UnSuppress,409538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Shelve,409538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.UnShelve,409538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Enable,409538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Disable,409538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Ack,409538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Reset,409538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Suppressed,409538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Shelved,409538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Disabled,409538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Acked,409538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI1.almPLCFault.Alarm,409538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Fault,409640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almHighHigh.AlarmState,409640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almHighHigh.GlobalReset,409640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almHighHigh.FaultInAlarm,409640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almHighHigh.ALRM,409640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almHighHigh.ANUN,409640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almHighHigh.AKED,409640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almHighHigh.Resetable,409640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almHighHigh.REST,409640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almHighHigh.ACKN,409640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almHighHigh.UACK,409640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almHighHigh.MCmd_Enable,409640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.MCmd_Disable,409640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.OCmd_Shelve,409640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.OCmd_Unshelve,409640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.SCmd_Suppress,409640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.SCmd_UnSuppress,409641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almHighHigh.AEShelveTMRDN,409641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almHighHigh.Bad,409641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almHighHigh.Suppress,409642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.UnSuppress,409642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Shelve,409642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.UnShelve,409642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Enable,409642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Disable,409642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Ack,409642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Reset,409642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Suppressed,409642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Shelved,409642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Disabled,409642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Acked,409642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almHighHigh.Alarm,409642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Fault,409652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almHigh.AlarmState,409652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almHigh.GlobalReset,409652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almHigh.FaultInAlarm,409652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almHigh.ALRM,409652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almHigh.ANUN,409652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almHigh.AKED,409652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almHigh.Resetable,409652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almHigh.REST,409652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almHigh.ACKN,409652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almHigh.UACK,409652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almHigh.MCmd_Enable,409652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almHigh.MCmd_Disable,409652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almHigh.OCmd_Shelve,409652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almHigh.OCmd_Unshelve,409652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almHigh.SCmd_Suppress,409652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almHigh.SCmd_UnSuppress,409653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almHigh.AEShelveTMRDN,409653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almHigh.Bad,409653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almHigh.Suppress,409654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.UnSuppress,409654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Shelve,409654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.UnShelve,409654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Enable,409654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Disable,409654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Ack,409654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Reset,409654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almHigh.Suppressed,409654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almHigh.Shelved,409654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almHigh.Disabled,409654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almHigh.Acked,409654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almHigh.Alarm,409654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Fault,409664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almLow.AlarmState,409664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almLow.GlobalReset,409664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almLow.FaultInAlarm,409664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almLow.ALRM,409664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almLow.ANUN,409664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almLow.AKED,409664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almLow.Resetable,409664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almLow.REST,409664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almLow.ACKN,409664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almLow.UACK,409664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almLow.MCmd_Enable,409664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almLow.MCmd_Disable,409664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almLow.OCmd_Shelve,409664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almLow.OCmd_Unshelve,409664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almLow.SCmd_Suppress,409664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almLow.SCmd_UnSuppress,409665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almLow.AEShelveTMRDN,409665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almLow.Bad,409665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almLow.Suppress,409666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.UnSuppress,409666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Shelve,409666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.UnShelve,409666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Enable,409666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Disable,409666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Ack,409666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Reset,409666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almLow.Suppressed,409666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almLow.Shelved,409666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almLow.Disabled,409666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almLow.Acked,409666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almLow.Alarm,409666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Fault,409676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almLowLow.AlarmState,409676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almLowLow.GlobalReset,409676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almLowLow.FaultInAlarm,409676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almLowLow.ALRM,409676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almLowLow.ANUN,409676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almLowLow.AKED,409676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almLowLow.Resetable,409676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almLowLow.REST,409676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almLowLow.ACKN,409676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almLowLow.UACK,409676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almLowLow.MCmd_Enable,409676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almLowLow.MCmd_Disable,409676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almLowLow.OCmd_Shelve,409676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almLowLow.OCmd_Unshelve,409676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almLowLow.SCmd_Suppress,409676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almLowLow.SCmd_UnSuppress,409677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almLowLow.AEShelveTMRDN,409677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almLowLow.Bad,409677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almLowLow.Suppress,409678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.UnSuppress,409678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Shelve,409678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.UnShelve,409678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Enable,409678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Disable,409678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Ack,409678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Reset,409678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Suppressed,409678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Shelved,409678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Disabled,409678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Acked,409678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almLowLow.Alarm,409678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Fault,409688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almBrokenLoop.AlarmState,409688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almBrokenLoop.GlobalReset,409688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almBrokenLoop.FaultInAlarm,409688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almBrokenLoop.ALRM,409688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almBrokenLoop.ANUN,409688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almBrokenLoop.AKED,409688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almBrokenLoop.Resetable,409688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almBrokenLoop.REST,409688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almBrokenLoop.ACKN,409688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almBrokenLoop.UACK,409688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almBrokenLoop.MCmd_Enable,409688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.MCmd_Disable,409688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.OCmd_Shelve,409688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.OCmd_Unshelve,409688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.SCmd_Suppress,409688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.SCmd_UnSuppress,409689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almBrokenLoop.AEShelveTMRDN,409689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almBrokenLoop.Bad,409689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almBrokenLoop.Suppress,409690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.UnSuppress,409690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Shelve,409690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.UnShelve,409690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Enable,409690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Disable,409690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Ack,409690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Reset,409690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Suppressed,409690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Shelved,409690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Disabled,409690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Acked,409690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.Alarm,409690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Fault,409700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almOverRange.AlarmState,409700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almOverRange.GlobalReset,409700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almOverRange.FaultInAlarm,409700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almOverRange.ALRM,409700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almOverRange.ANUN,409700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almOverRange.AKED,409700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almOverRange.Resetable,409700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almOverRange.REST,409700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almOverRange.ACKN,409700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almOverRange.UACK,409700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almOverRange.MCmd_Enable,409700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almOverRange.MCmd_Disable,409700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almOverRange.OCmd_Shelve,409700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almOverRange.OCmd_Unshelve,409700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almOverRange.SCmd_Suppress,409700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almOverRange.SCmd_UnSuppress,409701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almOverRange.AEShelveTMRDN,409701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almOverRange.Bad,409701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almOverRange.Suppress,409702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.UnSuppress,409702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Shelve,409702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.UnShelve,409702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Enable,409702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Disable,409702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Ack,409702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Reset,409702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Suppressed,409702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Shelved,409702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Disabled,409702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Acked,409702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almOverRange.Alarm,409702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Fault,409712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almUnderRange.AlarmState,409712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almUnderRange.GlobalReset,409712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almUnderRange.FaultInAlarm,409712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almUnderRange.ALRM,409712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almUnderRange.ANUN,409712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almUnderRange.AKED,409712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almUnderRange.Resetable,409712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almUnderRange.REST,409712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almUnderRange.ACKN,409712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almUnderRange.UACK,409712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almUnderRange.MCmd_Enable,409712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.MCmd_Disable,409712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.OCmd_Shelve,409712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.OCmd_Unshelve,409712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.SCmd_Suppress,409712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.SCmd_UnSuppress,409713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almUnderRange.AEShelveTMRDN,409713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almUnderRange.Bad,409713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almUnderRange.Suppress,409714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.UnSuppress,409714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Shelve,409714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.UnShelve,409714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Enable,409714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Disable,409714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Ack,409714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Reset,409714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Suppressed,409714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Shelved,409714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Disabled,409714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Acked,409714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almUnderRange.Alarm,409714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Fault,409724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almRateOfChange.AlarmState,409724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almRateOfChange.GlobalReset,409724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almRateOfChange.FaultInAlarm,409724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almRateOfChange.ALRM,409724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almRateOfChange.ANUN,409724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almRateOfChange.AKED,409724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almRateOfChange.Resetable,409724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almRateOfChange.REST,409724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almRateOfChange.ACKN,409724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almRateOfChange.UACK,409724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almRateOfChange.MCmd_Enable,409724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.MCmd_Disable,409724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.OCmd_Shelve,409724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.OCmd_Unshelve,409724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.SCmd_Suppress,409724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.SCmd_UnSuppress,409725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almRateOfChange.AEShelveTMRDN,409725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almRateOfChange.Bad,409725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almRateOfChange.Suppress,409726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.UnSuppress,409726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Shelve,409726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.UnShelve,409726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Enable,409726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Disable,409726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Ack,409726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Reset,409726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Suppressed,409726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Shelved,409726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Disabled,409726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Acked,409726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almRateOfChange.Alarm,409726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Fault,409736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI2.almPLCFault.AlarmState,409736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI2.almPLCFault.GlobalReset,409736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI2.almPLCFault.FaultInAlarm,409736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI2.almPLCFault.ALRM,409736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI2.almPLCFault.ANUN,409736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI2.almPLCFault.AKED,409736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI2.almPLCFault.Resetable,409736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI2.almPLCFault.REST,409736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI2.almPLCFault.ACKN,409736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI2.almPLCFault.UACK,409736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI2.almPLCFault.MCmd_Enable,409736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.MCmd_Disable,409736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.OCmd_Shelve,409736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.OCmd_Unshelve,409736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.SCmd_Suppress,409736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.SCmd_UnSuppress,409737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI2.almPLCFault.AEShelveTMRDN,409737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI2.almPLCFault.Bad,409737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI2.almPLCFault.Suppress,409738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.UnSuppress,409738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Shelve,409738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.UnShelve,409738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Enable,409738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Disable,409738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Ack,409738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Reset,409738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Suppressed,409738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Shelved,409738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Disabled,409738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Acked,409738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI2.almPLCFault.Alarm,409738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Fault,409840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almHighHigh.AlarmState,409840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almHighHigh.GlobalReset,409840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almHighHigh.FaultInAlarm,409840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almHighHigh.ALRM,409840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almHighHigh.ANUN,409840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almHighHigh.AKED,409840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almHighHigh.Resetable,409840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almHighHigh.REST,409840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almHighHigh.ACKN,409840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almHighHigh.UACK,409840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almHighHigh.MCmd_Enable,409840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.MCmd_Disable,409840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.OCmd_Shelve,409840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.OCmd_Unshelve,409840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.SCmd_Suppress,409840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.SCmd_UnSuppress,409841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almHighHigh.AEShelveTMRDN,409841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almHighHigh.Bad,409841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almHighHigh.Suppress,409842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.UnSuppress,409842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Shelve,409842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.UnShelve,409842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Enable,409842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Disable,409842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Ack,409842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Reset,409842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Suppressed,409842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Shelved,409842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Disabled,409842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Acked,409842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almHighHigh.Alarm,409842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Fault,409852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almHigh.AlarmState,409852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almHigh.GlobalReset,409852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almHigh.FaultInAlarm,409852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almHigh.ALRM,409852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almHigh.ANUN,409852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almHigh.AKED,409852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almHigh.Resetable,409852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almHigh.REST,409852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almHigh.ACKN,409852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almHigh.UACK,409852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almHigh.MCmd_Enable,409852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almHigh.MCmd_Disable,409852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almHigh.OCmd_Shelve,409852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almHigh.OCmd_Unshelve,409852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almHigh.SCmd_Suppress,409852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almHigh.SCmd_UnSuppress,409853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almHigh.AEShelveTMRDN,409853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almHigh.Bad,409853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almHigh.Suppress,409854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.UnSuppress,409854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Shelve,409854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.UnShelve,409854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Enable,409854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Disable,409854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Ack,409854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Reset,409854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almHigh.Suppressed,409854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almHigh.Shelved,409854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almHigh.Disabled,409854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almHigh.Acked,409854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almHigh.Alarm,409854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Fault,409864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almLow.AlarmState,409864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almLow.GlobalReset,409864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almLow.FaultInAlarm,409864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almLow.ALRM,409864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almLow.ANUN,409864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almLow.AKED,409864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almLow.Resetable,409864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almLow.REST,409864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almLow.ACKN,409864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almLow.UACK,409864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almLow.MCmd_Enable,409864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almLow.MCmd_Disable,409864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almLow.OCmd_Shelve,409864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almLow.OCmd_Unshelve,409864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almLow.SCmd_Suppress,409864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almLow.SCmd_UnSuppress,409865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almLow.AEShelveTMRDN,409865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almLow.Bad,409865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almLow.Suppress,409866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.UnSuppress,409866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Shelve,409866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.UnShelve,409866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Enable,409866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Disable,409866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Ack,409866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Reset,409866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almLow.Suppressed,409866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almLow.Shelved,409866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almLow.Disabled,409866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almLow.Acked,409866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almLow.Alarm,409866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Fault,409876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almLowLow.AlarmState,409876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almLowLow.GlobalReset,409876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almLowLow.FaultInAlarm,409876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almLowLow.ALRM,409876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almLowLow.ANUN,409876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almLowLow.AKED,409876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almLowLow.Resetable,409876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almLowLow.REST,409876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almLowLow.ACKN,409876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almLowLow.UACK,409876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almLowLow.MCmd_Enable,409876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almLowLow.MCmd_Disable,409876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almLowLow.OCmd_Shelve,409876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almLowLow.OCmd_Unshelve,409876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almLowLow.SCmd_Suppress,409876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almLowLow.SCmd_UnSuppress,409877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almLowLow.AEShelveTMRDN,409877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almLowLow.Bad,409877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almLowLow.Suppress,409878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.UnSuppress,409878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Shelve,409878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.UnShelve,409878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Enable,409878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Disable,409878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Ack,409878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Reset,409878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Suppressed,409878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Shelved,409878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Disabled,409878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Acked,409878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almLowLow.Alarm,409878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Fault,409888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almBrokenLoop.AlarmState,409888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almBrokenLoop.GlobalReset,409888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almBrokenLoop.FaultInAlarm,409888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almBrokenLoop.ALRM,409888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almBrokenLoop.ANUN,409888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almBrokenLoop.AKED,409888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almBrokenLoop.Resetable,409888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almBrokenLoop.REST,409888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almBrokenLoop.ACKN,409888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almBrokenLoop.UACK,409888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almBrokenLoop.MCmd_Enable,409888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.MCmd_Disable,409888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.OCmd_Shelve,409888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.OCmd_Unshelve,409888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.SCmd_Suppress,409888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.SCmd_UnSuppress,409889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almBrokenLoop.AEShelveTMRDN,409889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almBrokenLoop.Bad,409889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almBrokenLoop.Suppress,409890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.UnSuppress,409890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Shelve,409890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.UnShelve,409890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Enable,409890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Disable,409890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Ack,409890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Reset,409890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Suppressed,409890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Shelved,409890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Disabled,409890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Acked,409890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.Alarm,409890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Fault,409900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almOverRange.AlarmState,409900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almOverRange.GlobalReset,409900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almOverRange.FaultInAlarm,409900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almOverRange.ALRM,409900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almOverRange.ANUN,409900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almOverRange.AKED,409900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almOverRange.Resetable,409900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almOverRange.REST,409900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almOverRange.ACKN,409900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almOverRange.UACK,409900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almOverRange.MCmd_Enable,409900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almOverRange.MCmd_Disable,409900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almOverRange.OCmd_Shelve,409900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almOverRange.OCmd_Unshelve,409900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almOverRange.SCmd_Suppress,409900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almOverRange.SCmd_UnSuppress,409901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almOverRange.AEShelveTMRDN,409901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almOverRange.Bad,409901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almOverRange.Suppress,409902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.UnSuppress,409902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Shelve,409902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.UnShelve,409902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Enable,409902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Disable,409902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Ack,409902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Reset,409902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Suppressed,409902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Shelved,409902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Disabled,409902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Acked,409902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almOverRange.Alarm,409902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Fault,409912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almUnderRange.AlarmState,409912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almUnderRange.GlobalReset,409912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almUnderRange.FaultInAlarm,409912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almUnderRange.ALRM,409912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almUnderRange.ANUN,409912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almUnderRange.AKED,409912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almUnderRange.Resetable,409912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almUnderRange.REST,409912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almUnderRange.ACKN,409912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almUnderRange.UACK,409912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almUnderRange.MCmd_Enable,409912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.MCmd_Disable,409912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.OCmd_Shelve,409912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.OCmd_Unshelve,409912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.SCmd_Suppress,409912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.SCmd_UnSuppress,409913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almUnderRange.AEShelveTMRDN,409913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almUnderRange.Bad,409913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almUnderRange.Suppress,409914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.UnSuppress,409914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Shelve,409914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.UnShelve,409914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Enable,409914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Disable,409914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Ack,409914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Reset,409914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Suppressed,409914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Shelved,409914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Disabled,409914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Acked,409914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almUnderRange.Alarm,409914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Fault,409924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almRateOfChange.AlarmState,409924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almRateOfChange.GlobalReset,409924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almRateOfChange.FaultInAlarm,409924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almRateOfChange.ALRM,409924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almRateOfChange.ANUN,409924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almRateOfChange.AKED,409924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almRateOfChange.Resetable,409924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almRateOfChange.REST,409924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almRateOfChange.ACKN,409924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almRateOfChange.UACK,409924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almRateOfChange.MCmd_Enable,409924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.MCmd_Disable,409924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.OCmd_Shelve,409924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.OCmd_Unshelve,409924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.SCmd_Suppress,409924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.SCmd_UnSuppress,409925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almRateOfChange.AEShelveTMRDN,409925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almRateOfChange.Bad,409925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almRateOfChange.Suppress,409926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.UnSuppress,409926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Shelve,409926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.UnShelve,409926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Enable,409926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Disable,409926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Ack,409926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Reset,409926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Suppressed,409926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Shelved,409926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Disabled,409926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Acked,409926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almRateOfChange.Alarm,409926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Fault,409936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI3.almPLCFault.AlarmState,409936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI3.almPLCFault.GlobalReset,409936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI3.almPLCFault.FaultInAlarm,409936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI3.almPLCFault.ALRM,409936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI3.almPLCFault.ANUN,409936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI3.almPLCFault.AKED,409936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI3.almPLCFault.Resetable,409936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI3.almPLCFault.REST,409936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI3.almPLCFault.ACKN,409936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI3.almPLCFault.UACK,409936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI3.almPLCFault.MCmd_Enable,409936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.MCmd_Disable,409936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.OCmd_Shelve,409936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.OCmd_Unshelve,409936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.SCmd_Suppress,409936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.SCmd_UnSuppress,409937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI3.almPLCFault.AEShelveTMRDN,409937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI3.almPLCFault.Bad,409937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI3.almPLCFault.Suppress,409938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.UnSuppress,409938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Shelve,409938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.UnShelve,409938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Enable,409938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Disable,409938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Ack,409938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Reset,409938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Suppressed,409938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Shelved,409938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Disabled,409938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Acked,409938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI3.almPLCFault.Alarm,409938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Fault,410040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almHighHigh.AlarmState,410040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almHighHigh.GlobalReset,410040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almHighHigh.FaultInAlarm,410040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almHighHigh.ALRM,410040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almHighHigh.ANUN,410040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almHighHigh.AKED,410040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almHighHigh.Resetable,410040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almHighHigh.REST,410040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almHighHigh.ACKN,410040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almHighHigh.UACK,410040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almHighHigh.MCmd_Enable,410040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.MCmd_Disable,410040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.OCmd_Shelve,410040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.OCmd_Unshelve,410040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.SCmd_Suppress,410040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.SCmd_UnSuppress,410041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almHighHigh.AEShelveTMRDN,410041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almHighHigh.Bad,410041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almHighHigh.Suppress,410042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.UnSuppress,410042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Shelve,410042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.UnShelve,410042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Enable,410042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Disable,410042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Ack,410042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Reset,410042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Suppressed,410042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Shelved,410042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Disabled,410042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Acked,410042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almHighHigh.Alarm,410042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Fault,410052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almHigh.AlarmState,410052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almHigh.GlobalReset,410052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almHigh.FaultInAlarm,410052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almHigh.ALRM,410052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almHigh.ANUN,410052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almHigh.AKED,410052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almHigh.Resetable,410052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almHigh.REST,410052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almHigh.ACKN,410052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almHigh.UACK,410052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almHigh.MCmd_Enable,410052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almHigh.MCmd_Disable,410052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almHigh.OCmd_Shelve,410052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almHigh.OCmd_Unshelve,410052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almHigh.SCmd_Suppress,410052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almHigh.SCmd_UnSuppress,410053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almHigh.AEShelveTMRDN,410053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almHigh.Bad,410053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almHigh.Suppress,410054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.UnSuppress,410054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Shelve,410054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.UnShelve,410054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Enable,410054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Disable,410054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Ack,410054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Reset,410054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almHigh.Suppressed,410054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almHigh.Shelved,410054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almHigh.Disabled,410054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almHigh.Acked,410054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almHigh.Alarm,410054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Fault,410064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almLow.AlarmState,410064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almLow.GlobalReset,410064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almLow.FaultInAlarm,410064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almLow.ALRM,410064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almLow.ANUN,410064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almLow.AKED,410064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almLow.Resetable,410064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almLow.REST,410064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almLow.ACKN,410064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almLow.UACK,410064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almLow.MCmd_Enable,410064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almLow.MCmd_Disable,410064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almLow.OCmd_Shelve,410064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almLow.OCmd_Unshelve,410064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almLow.SCmd_Suppress,410064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almLow.SCmd_UnSuppress,410065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almLow.AEShelveTMRDN,410065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almLow.Bad,410065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almLow.Suppress,410066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.UnSuppress,410066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Shelve,410066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.UnShelve,410066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Enable,410066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Disable,410066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Ack,410066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Reset,410066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almLow.Suppressed,410066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almLow.Shelved,410066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almLow.Disabled,410066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almLow.Acked,410066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almLow.Alarm,410066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Fault,410076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almLowLow.AlarmState,410076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almLowLow.GlobalReset,410076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almLowLow.FaultInAlarm,410076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almLowLow.ALRM,410076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almLowLow.ANUN,410076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almLowLow.AKED,410076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almLowLow.Resetable,410076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almLowLow.REST,410076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almLowLow.ACKN,410076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almLowLow.UACK,410076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almLowLow.MCmd_Enable,410076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almLowLow.MCmd_Disable,410076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almLowLow.OCmd_Shelve,410076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almLowLow.OCmd_Unshelve,410076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almLowLow.SCmd_Suppress,410076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almLowLow.SCmd_UnSuppress,410077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almLowLow.AEShelveTMRDN,410077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almLowLow.Bad,410077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almLowLow.Suppress,410078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.UnSuppress,410078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Shelve,410078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.UnShelve,410078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Enable,410078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Disable,410078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Ack,410078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Reset,410078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Suppressed,410078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Shelved,410078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Disabled,410078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Acked,410078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almLowLow.Alarm,410078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Fault,410088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almBrokenLoop.AlarmState,410088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almBrokenLoop.GlobalReset,410088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almBrokenLoop.FaultInAlarm,410088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almBrokenLoop.ALRM,410088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almBrokenLoop.ANUN,410088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almBrokenLoop.AKED,410088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almBrokenLoop.Resetable,410088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almBrokenLoop.REST,410088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almBrokenLoop.ACKN,410088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almBrokenLoop.UACK,410088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almBrokenLoop.MCmd_Enable,410088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.MCmd_Disable,410088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.OCmd_Shelve,410088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.OCmd_Unshelve,410088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.SCmd_Suppress,410088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.SCmd_UnSuppress,410089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almBrokenLoop.AEShelveTMRDN,410089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almBrokenLoop.Bad,410089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almBrokenLoop.Suppress,410090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.UnSuppress,410090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Shelve,410090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.UnShelve,410090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Enable,410090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Disable,410090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Ack,410090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Reset,410090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Suppressed,410090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Shelved,410090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Disabled,410090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Acked,410090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.Alarm,410090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Fault,410100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almOverRange.AlarmState,410100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almOverRange.GlobalReset,410100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almOverRange.FaultInAlarm,410100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almOverRange.ALRM,410100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almOverRange.ANUN,410100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almOverRange.AKED,410100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almOverRange.Resetable,410100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almOverRange.REST,410100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almOverRange.ACKN,410100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almOverRange.UACK,410100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almOverRange.MCmd_Enable,410100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almOverRange.MCmd_Disable,410100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almOverRange.OCmd_Shelve,410100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almOverRange.OCmd_Unshelve,410100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almOverRange.SCmd_Suppress,410100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almOverRange.SCmd_UnSuppress,410101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almOverRange.AEShelveTMRDN,410101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almOverRange.Bad,410101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almOverRange.Suppress,410102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.UnSuppress,410102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Shelve,410102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.UnShelve,410102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Enable,410102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Disable,410102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Ack,410102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Reset,410102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Suppressed,410102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Shelved,410102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Disabled,410102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Acked,410102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almOverRange.Alarm,410102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Fault,410112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almUnderRange.AlarmState,410112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almUnderRange.GlobalReset,410112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almUnderRange.FaultInAlarm,410112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almUnderRange.ALRM,410112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almUnderRange.ANUN,410112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almUnderRange.AKED,410112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almUnderRange.Resetable,410112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almUnderRange.REST,410112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almUnderRange.ACKN,410112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almUnderRange.UACK,410112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almUnderRange.MCmd_Enable,410112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.MCmd_Disable,410112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.OCmd_Shelve,410112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.OCmd_Unshelve,410112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.SCmd_Suppress,410112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.SCmd_UnSuppress,410113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almUnderRange.AEShelveTMRDN,410113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almUnderRange.Bad,410113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almUnderRange.Suppress,410114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.UnSuppress,410114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Shelve,410114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.UnShelve,410114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Enable,410114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Disable,410114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Ack,410114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Reset,410114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Suppressed,410114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Shelved,410114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Disabled,410114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Acked,410114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almUnderRange.Alarm,410114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Fault,410124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almRateOfChange.AlarmState,410124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almRateOfChange.GlobalReset,410124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almRateOfChange.FaultInAlarm,410124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almRateOfChange.ALRM,410124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almRateOfChange.ANUN,410124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almRateOfChange.AKED,410124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almRateOfChange.Resetable,410124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almRateOfChange.REST,410124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almRateOfChange.ACKN,410124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almRateOfChange.UACK,410124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almRateOfChange.MCmd_Enable,410124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.MCmd_Disable,410124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.OCmd_Shelve,410124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.OCmd_Unshelve,410124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.SCmd_Suppress,410124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.SCmd_UnSuppress,410125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almRateOfChange.AEShelveTMRDN,410125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almRateOfChange.Bad,410125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almRateOfChange.Suppress,410126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.UnSuppress,410126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Shelve,410126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.UnShelve,410126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Enable,410126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Disable,410126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Ack,410126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Reset,410126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Suppressed,410126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Shelved,410126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Disabled,410126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Acked,410126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almRateOfChange.Alarm,410126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Fault,410136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_4_VI4.almPLCFault.AlarmState,410136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_4_VI4.almPLCFault.GlobalReset,410136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_4_VI4.almPLCFault.FaultInAlarm,410136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_4_VI4.almPLCFault.ALRM,410136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_4_VI4.almPLCFault.ANUN,410136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_4_VI4.almPLCFault.AKED,410136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_4_VI4.almPLCFault.Resetable,410136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_4_VI4.almPLCFault.REST,410136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_4_VI4.almPLCFault.ACKN,410136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_4_VI4.almPLCFault.UACK,410136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_4_VI4.almPLCFault.MCmd_Enable,410136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.MCmd_Disable,410136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.OCmd_Shelve,410136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.OCmd_Unshelve,410136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.SCmd_Suppress,410136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.SCmd_UnSuppress,410137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_4_VI4.almPLCFault.AEShelveTMRDN,410137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_4_VI4.almPLCFault.Bad,410137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_4_VI4.almPLCFault.Suppress,410138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.UnSuppress,410138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Shelve,410138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.UnShelve,410138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Enable,410138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Disable,410138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Ack,410138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Reset,410138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Suppressed,410138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Shelved,410138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Disabled,410138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Acked,410138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_4_VI4.almPLCFault.Alarm,410138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Fault,410240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almHighHigh.AlarmState,410240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almHighHigh.GlobalReset,410240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almHighHigh.FaultInAlarm,410240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almHighHigh.ALRM,410240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almHighHigh.ANUN,410240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almHighHigh.AKED,410240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almHighHigh.Resetable,410240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almHighHigh.REST,410240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almHighHigh.ACKN,410240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almHighHigh.UACK,410240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almHighHigh.MCmd_Enable,410240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.MCmd_Disable,410240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.OCmd_Shelve,410240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.OCmd_Unshelve,410240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.SCmd_Suppress,410240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.SCmd_UnSuppress,410241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almHighHigh.AEShelveTMRDN,410241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almHighHigh.Bad,410241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almHighHigh.Suppress,410242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.UnSuppress,410242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Shelve,410242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.UnShelve,410242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Enable,410242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Disable,410242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Ack,410242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Reset,410242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Suppressed,410242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Shelved,410242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Disabled,410242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Acked,410242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almHighHigh.Alarm,410242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Fault,410252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almHigh.AlarmState,410252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almHigh.GlobalReset,410252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almHigh.FaultInAlarm,410252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almHigh.ALRM,410252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almHigh.ANUN,410252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almHigh.AKED,410252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almHigh.Resetable,410252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almHigh.REST,410252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almHigh.ACKN,410252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almHigh.UACK,410252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almHigh.MCmd_Enable,410252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almHigh.MCmd_Disable,410252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almHigh.OCmd_Shelve,410252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almHigh.OCmd_Unshelve,410252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almHigh.SCmd_Suppress,410252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almHigh.SCmd_UnSuppress,410253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almHigh.AEShelveTMRDN,410253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almHigh.Bad,410253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almHigh.Suppress,410254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.UnSuppress,410254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Shelve,410254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.UnShelve,410254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Enable,410254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Disable,410254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Ack,410254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Reset,410254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almHigh.Suppressed,410254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almHigh.Shelved,410254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almHigh.Disabled,410254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almHigh.Acked,410254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almHigh.Alarm,410254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Fault,410264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almLow.AlarmState,410264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almLow.GlobalReset,410264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almLow.FaultInAlarm,410264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almLow.ALRM,410264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almLow.ANUN,410264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almLow.AKED,410264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almLow.Resetable,410264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almLow.REST,410264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almLow.ACKN,410264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almLow.UACK,410264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almLow.MCmd_Enable,410264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almLow.MCmd_Disable,410264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almLow.OCmd_Shelve,410264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almLow.OCmd_Unshelve,410264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almLow.SCmd_Suppress,410264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almLow.SCmd_UnSuppress,410265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almLow.AEShelveTMRDN,410265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almLow.Bad,410265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almLow.Suppress,410266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.UnSuppress,410266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Shelve,410266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.UnShelve,410266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Enable,410266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Disable,410266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Ack,410266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Reset,410266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almLow.Suppressed,410266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almLow.Shelved,410266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almLow.Disabled,410266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almLow.Acked,410266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almLow.Alarm,410266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Fault,410276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almLowLow.AlarmState,410276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almLowLow.GlobalReset,410276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almLowLow.FaultInAlarm,410276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almLowLow.ALRM,410276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almLowLow.ANUN,410276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almLowLow.AKED,410276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almLowLow.Resetable,410276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almLowLow.REST,410276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almLowLow.ACKN,410276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almLowLow.UACK,410276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almLowLow.MCmd_Enable,410276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almLowLow.MCmd_Disable,410276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almLowLow.OCmd_Shelve,410276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almLowLow.OCmd_Unshelve,410276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almLowLow.SCmd_Suppress,410276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almLowLow.SCmd_UnSuppress,410277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almLowLow.AEShelveTMRDN,410277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almLowLow.Bad,410277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almLowLow.Suppress,410278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.UnSuppress,410278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Shelve,410278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.UnShelve,410278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Enable,410278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Disable,410278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Ack,410278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Reset,410278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Suppressed,410278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Shelved,410278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Disabled,410278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Acked,410278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almLowLow.Alarm,410278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Fault,410288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almBrokenLoop.AlarmState,410288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almBrokenLoop.GlobalReset,410288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almBrokenLoop.FaultInAlarm,410288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almBrokenLoop.ALRM,410288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almBrokenLoop.ANUN,410288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almBrokenLoop.AKED,410288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almBrokenLoop.Resetable,410288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almBrokenLoop.REST,410288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almBrokenLoop.ACKN,410288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almBrokenLoop.UACK,410288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almBrokenLoop.MCmd_Enable,410288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.MCmd_Disable,410288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.OCmd_Shelve,410288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.OCmd_Unshelve,410288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.SCmd_Suppress,410288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.SCmd_UnSuppress,410289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almBrokenLoop.AEShelveTMRDN,410289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almBrokenLoop.Bad,410289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almBrokenLoop.Suppress,410290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.UnSuppress,410290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Shelve,410290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.UnShelve,410290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Enable,410290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Disable,410290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Ack,410290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Reset,410290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Suppressed,410290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Shelved,410290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Disabled,410290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Acked,410290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.Alarm,410290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Fault,410300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almOverRange.AlarmState,410300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almOverRange.GlobalReset,410300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almOverRange.FaultInAlarm,410300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almOverRange.ALRM,410300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almOverRange.ANUN,410300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almOverRange.AKED,410300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almOverRange.Resetable,410300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almOverRange.REST,410300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almOverRange.ACKN,410300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almOverRange.UACK,410300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almOverRange.MCmd_Enable,410300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almOverRange.MCmd_Disable,410300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almOverRange.OCmd_Shelve,410300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almOverRange.OCmd_Unshelve,410300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almOverRange.SCmd_Suppress,410300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almOverRange.SCmd_UnSuppress,410301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almOverRange.AEShelveTMRDN,410301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almOverRange.Bad,410301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almOverRange.Suppress,410302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.UnSuppress,410302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Shelve,410302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.UnShelve,410302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Enable,410302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Disable,410302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Ack,410302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Reset,410302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Suppressed,410302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Shelved,410302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Disabled,410302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Acked,410302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almOverRange.Alarm,410302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Fault,410312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almUnderRange.AlarmState,410312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almUnderRange.GlobalReset,410312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almUnderRange.FaultInAlarm,410312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almUnderRange.ALRM,410312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almUnderRange.ANUN,410312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almUnderRange.AKED,410312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almUnderRange.Resetable,410312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almUnderRange.REST,410312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almUnderRange.ACKN,410312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almUnderRange.UACK,410312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almUnderRange.MCmd_Enable,410312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.MCmd_Disable,410312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.OCmd_Shelve,410312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.OCmd_Unshelve,410312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.SCmd_Suppress,410312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.SCmd_UnSuppress,410313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almUnderRange.AEShelveTMRDN,410313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almUnderRange.Bad,410313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almUnderRange.Suppress,410314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.UnSuppress,410314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Shelve,410314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.UnShelve,410314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Enable,410314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Disable,410314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Ack,410314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Reset,410314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Suppressed,410314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Shelved,410314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Disabled,410314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Acked,410314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almUnderRange.Alarm,410314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Fault,410324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almRateOfChange.AlarmState,410324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almRateOfChange.GlobalReset,410324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almRateOfChange.FaultInAlarm,410324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almRateOfChange.ALRM,410324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almRateOfChange.ANUN,410324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almRateOfChange.AKED,410324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almRateOfChange.Resetable,410324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almRateOfChange.REST,410324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almRateOfChange.ACKN,410324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almRateOfChange.UACK,410324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almRateOfChange.MCmd_Enable,410324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.MCmd_Disable,410324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.OCmd_Shelve,410324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.OCmd_Unshelve,410324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.SCmd_Suppress,410324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.SCmd_UnSuppress,410325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almRateOfChange.AEShelveTMRDN,410325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almRateOfChange.Bad,410325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almRateOfChange.Suppress,410326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.UnSuppress,410326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Shelve,410326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.UnShelve,410326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Enable,410326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Disable,410326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Ack,410326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Reset,410326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Suppressed,410326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Shelved,410326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Disabled,410326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Acked,410326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almRateOfChange.Alarm,410326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Fault,410336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI1.almPLCFault.AlarmState,410336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI1.almPLCFault.GlobalReset,410336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI1.almPLCFault.FaultInAlarm,410336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI1.almPLCFault.ALRM,410336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI1.almPLCFault.ANUN,410336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI1.almPLCFault.AKED,410336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI1.almPLCFault.Resetable,410336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI1.almPLCFault.REST,410336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI1.almPLCFault.ACKN,410336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI1.almPLCFault.UACK,410336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI1.almPLCFault.MCmd_Enable,410336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.MCmd_Disable,410336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.OCmd_Shelve,410336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.OCmd_Unshelve,410336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.SCmd_Suppress,410336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.SCmd_UnSuppress,410337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI1.almPLCFault.AEShelveTMRDN,410337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI1.almPLCFault.Bad,410337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI1.almPLCFault.Suppress,410338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.UnSuppress,410338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Shelve,410338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.UnShelve,410338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Enable,410338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Disable,410338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Ack,410338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Reset,410338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Suppressed,410338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Shelved,410338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Disabled,410338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Acked,410338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI1.almPLCFault.Alarm,410338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Fault,410440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almHighHigh.AlarmState,410440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almHighHigh.GlobalReset,410440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almHighHigh.FaultInAlarm,410440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almHighHigh.ALRM,410440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almHighHigh.ANUN,410440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almHighHigh.AKED,410440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almHighHigh.Resetable,410440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almHighHigh.REST,410440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almHighHigh.ACKN,410440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almHighHigh.UACK,410440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almHighHigh.MCmd_Enable,410440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.MCmd_Disable,410440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.OCmd_Shelve,410440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.OCmd_Unshelve,410440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.SCmd_Suppress,410440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.SCmd_UnSuppress,410441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almHighHigh.AEShelveTMRDN,410441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almHighHigh.Bad,410441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almHighHigh.Suppress,410442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.UnSuppress,410442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Shelve,410442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.UnShelve,410442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Enable,410442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Disable,410442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Ack,410442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Reset,410442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Suppressed,410442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Shelved,410442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Disabled,410442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Acked,410442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almHighHigh.Alarm,410442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Fault,410452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almHigh.AlarmState,410452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almHigh.GlobalReset,410452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almHigh.FaultInAlarm,410452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almHigh.ALRM,410452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almHigh.ANUN,410452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almHigh.AKED,410452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almHigh.Resetable,410452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almHigh.REST,410452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almHigh.ACKN,410452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almHigh.UACK,410452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almHigh.MCmd_Enable,410452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almHigh.MCmd_Disable,410452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almHigh.OCmd_Shelve,410452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almHigh.OCmd_Unshelve,410452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almHigh.SCmd_Suppress,410452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almHigh.SCmd_UnSuppress,410453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almHigh.AEShelveTMRDN,410453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almHigh.Bad,410453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almHigh.Suppress,410454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.UnSuppress,410454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Shelve,410454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.UnShelve,410454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Enable,410454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Disable,410454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Ack,410454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Reset,410454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almHigh.Suppressed,410454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almHigh.Shelved,410454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almHigh.Disabled,410454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almHigh.Acked,410454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almHigh.Alarm,410454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Fault,410464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almLow.AlarmState,410464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almLow.GlobalReset,410464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almLow.FaultInAlarm,410464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almLow.ALRM,410464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almLow.ANUN,410464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almLow.AKED,410464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almLow.Resetable,410464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almLow.REST,410464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almLow.ACKN,410464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almLow.UACK,410464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almLow.MCmd_Enable,410464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almLow.MCmd_Disable,410464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almLow.OCmd_Shelve,410464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almLow.OCmd_Unshelve,410464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almLow.SCmd_Suppress,410464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almLow.SCmd_UnSuppress,410465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almLow.AEShelveTMRDN,410465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almLow.Bad,410465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almLow.Suppress,410466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.UnSuppress,410466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Shelve,410466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.UnShelve,410466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Enable,410466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Disable,410466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Ack,410466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Reset,410466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almLow.Suppressed,410466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almLow.Shelved,410466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almLow.Disabled,410466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almLow.Acked,410466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almLow.Alarm,410466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Fault,410476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almLowLow.AlarmState,410476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almLowLow.GlobalReset,410476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almLowLow.FaultInAlarm,410476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almLowLow.ALRM,410476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almLowLow.ANUN,410476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almLowLow.AKED,410476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almLowLow.Resetable,410476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almLowLow.REST,410476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almLowLow.ACKN,410476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almLowLow.UACK,410476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almLowLow.MCmd_Enable,410476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almLowLow.MCmd_Disable,410476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almLowLow.OCmd_Shelve,410476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almLowLow.OCmd_Unshelve,410476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almLowLow.SCmd_Suppress,410476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almLowLow.SCmd_UnSuppress,410477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almLowLow.AEShelveTMRDN,410477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almLowLow.Bad,410477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almLowLow.Suppress,410478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.UnSuppress,410478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Shelve,410478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.UnShelve,410478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Enable,410478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Disable,410478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Ack,410478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Reset,410478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Suppressed,410478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Shelved,410478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Disabled,410478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Acked,410478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almLowLow.Alarm,410478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Fault,410488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almBrokenLoop.AlarmState,410488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almBrokenLoop.GlobalReset,410488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almBrokenLoop.FaultInAlarm,410488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almBrokenLoop.ALRM,410488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almBrokenLoop.ANUN,410488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almBrokenLoop.AKED,410488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almBrokenLoop.Resetable,410488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almBrokenLoop.REST,410488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almBrokenLoop.ACKN,410488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almBrokenLoop.UACK,410488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almBrokenLoop.MCmd_Enable,410488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.MCmd_Disable,410488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.OCmd_Shelve,410488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.OCmd_Unshelve,410488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.SCmd_Suppress,410488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.SCmd_UnSuppress,410489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almBrokenLoop.AEShelveTMRDN,410489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almBrokenLoop.Bad,410489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almBrokenLoop.Suppress,410490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.UnSuppress,410490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Shelve,410490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.UnShelve,410490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Enable,410490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Disable,410490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Ack,410490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Reset,410490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Suppressed,410490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Shelved,410490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Disabled,410490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Acked,410490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.Alarm,410490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Fault,410500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almOverRange.AlarmState,410500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almOverRange.GlobalReset,410500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almOverRange.FaultInAlarm,410500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almOverRange.ALRM,410500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almOverRange.ANUN,410500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almOverRange.AKED,410500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almOverRange.Resetable,410500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almOverRange.REST,410500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almOverRange.ACKN,410500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almOverRange.UACK,410500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almOverRange.MCmd_Enable,410500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almOverRange.MCmd_Disable,410500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almOverRange.OCmd_Shelve,410500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almOverRange.OCmd_Unshelve,410500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almOverRange.SCmd_Suppress,410500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almOverRange.SCmd_UnSuppress,410501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almOverRange.AEShelveTMRDN,410501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almOverRange.Bad,410501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almOverRange.Suppress,410502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.UnSuppress,410502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Shelve,410502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.UnShelve,410502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Enable,410502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Disable,410502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Ack,410502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Reset,410502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Suppressed,410502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Shelved,410502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Disabled,410502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Acked,410502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almOverRange.Alarm,410502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Fault,410512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almUnderRange.AlarmState,410512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almUnderRange.GlobalReset,410512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almUnderRange.FaultInAlarm,410512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almUnderRange.ALRM,410512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almUnderRange.ANUN,410512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almUnderRange.AKED,410512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almUnderRange.Resetable,410512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almUnderRange.REST,410512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almUnderRange.ACKN,410512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almUnderRange.UACK,410512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almUnderRange.MCmd_Enable,410512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.MCmd_Disable,410512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.OCmd_Shelve,410512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.OCmd_Unshelve,410512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.SCmd_Suppress,410512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.SCmd_UnSuppress,410513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almUnderRange.AEShelveTMRDN,410513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almUnderRange.Bad,410513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almUnderRange.Suppress,410514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.UnSuppress,410514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Shelve,410514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.UnShelve,410514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Enable,410514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Disable,410514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Ack,410514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Reset,410514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Suppressed,410514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Shelved,410514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Disabled,410514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Acked,410514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almUnderRange.Alarm,410514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Fault,410524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almRateOfChange.AlarmState,410524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almRateOfChange.GlobalReset,410524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almRateOfChange.FaultInAlarm,410524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almRateOfChange.ALRM,410524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almRateOfChange.ANUN,410524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almRateOfChange.AKED,410524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almRateOfChange.Resetable,410524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almRateOfChange.REST,410524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almRateOfChange.ACKN,410524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almRateOfChange.UACK,410524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almRateOfChange.MCmd_Enable,410524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.MCmd_Disable,410524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.OCmd_Shelve,410524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.OCmd_Unshelve,410524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.SCmd_Suppress,410524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.SCmd_UnSuppress,410525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almRateOfChange.AEShelveTMRDN,410525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almRateOfChange.Bad,410525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almRateOfChange.Suppress,410526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.UnSuppress,410526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Shelve,410526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.UnShelve,410526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Enable,410526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Disable,410526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Ack,410526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Reset,410526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Suppressed,410526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Shelved,410526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Disabled,410526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Acked,410526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almRateOfChange.Alarm,410526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Fault,410536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI2.almPLCFault.AlarmState,410536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI2.almPLCFault.GlobalReset,410536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI2.almPLCFault.FaultInAlarm,410536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI2.almPLCFault.ALRM,410536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI2.almPLCFault.ANUN,410536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI2.almPLCFault.AKED,410536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI2.almPLCFault.Resetable,410536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI2.almPLCFault.REST,410536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI2.almPLCFault.ACKN,410536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI2.almPLCFault.UACK,410536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI2.almPLCFault.MCmd_Enable,410536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.MCmd_Disable,410536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.OCmd_Shelve,410536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.OCmd_Unshelve,410536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.SCmd_Suppress,410536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.SCmd_UnSuppress,410537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI2.almPLCFault.AEShelveTMRDN,410537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI2.almPLCFault.Bad,410537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI2.almPLCFault.Suppress,410538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.UnSuppress,410538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Shelve,410538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.UnShelve,410538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Enable,410538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Disable,410538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Ack,410538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Reset,410538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Suppressed,410538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Shelved,410538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Disabled,410538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Acked,410538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI2.almPLCFault.Alarm,410538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Fault,410640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almHighHigh.AlarmState,410640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almHighHigh.GlobalReset,410640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almHighHigh.FaultInAlarm,410640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almHighHigh.ALRM,410640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almHighHigh.ANUN,410640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almHighHigh.AKED,410640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almHighHigh.Resetable,410640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almHighHigh.REST,410640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almHighHigh.ACKN,410640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almHighHigh.UACK,410640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almHighHigh.MCmd_Enable,410640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.MCmd_Disable,410640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.OCmd_Shelve,410640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.OCmd_Unshelve,410640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.SCmd_Suppress,410640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.SCmd_UnSuppress,410641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almHighHigh.AEShelveTMRDN,410641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almHighHigh.Bad,410641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almHighHigh.Suppress,410642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.UnSuppress,410642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Shelve,410642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.UnShelve,410642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Enable,410642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Disable,410642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Ack,410642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Reset,410642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Suppressed,410642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Shelved,410642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Disabled,410642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Acked,410642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almHighHigh.Alarm,410642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Fault,410652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almHigh.AlarmState,410652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almHigh.GlobalReset,410652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almHigh.FaultInAlarm,410652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almHigh.ALRM,410652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almHigh.ANUN,410652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almHigh.AKED,410652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almHigh.Resetable,410652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almHigh.REST,410652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almHigh.ACKN,410652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almHigh.UACK,410652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almHigh.MCmd_Enable,410652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almHigh.MCmd_Disable,410652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almHigh.OCmd_Shelve,410652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almHigh.OCmd_Unshelve,410652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almHigh.SCmd_Suppress,410652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almHigh.SCmd_UnSuppress,410653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almHigh.AEShelveTMRDN,410653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almHigh.Bad,410653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almHigh.Suppress,410654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.UnSuppress,410654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Shelve,410654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.UnShelve,410654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Enable,410654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Disable,410654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Ack,410654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Reset,410654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almHigh.Suppressed,410654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almHigh.Shelved,410654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almHigh.Disabled,410654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almHigh.Acked,410654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almHigh.Alarm,410654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Fault,410664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almLow.AlarmState,410664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almLow.GlobalReset,410664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almLow.FaultInAlarm,410664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almLow.ALRM,410664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almLow.ANUN,410664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almLow.AKED,410664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almLow.Resetable,410664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almLow.REST,410664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almLow.ACKN,410664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almLow.UACK,410664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almLow.MCmd_Enable,410664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almLow.MCmd_Disable,410664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almLow.OCmd_Shelve,410664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almLow.OCmd_Unshelve,410664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almLow.SCmd_Suppress,410664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almLow.SCmd_UnSuppress,410665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almLow.AEShelveTMRDN,410665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almLow.Bad,410665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almLow.Suppress,410666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.UnSuppress,410666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Shelve,410666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.UnShelve,410666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Enable,410666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Disable,410666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Ack,410666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Reset,410666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almLow.Suppressed,410666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almLow.Shelved,410666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almLow.Disabled,410666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almLow.Acked,410666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almLow.Alarm,410666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Fault,410676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almLowLow.AlarmState,410676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almLowLow.GlobalReset,410676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almLowLow.FaultInAlarm,410676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almLowLow.ALRM,410676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almLowLow.ANUN,410676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almLowLow.AKED,410676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almLowLow.Resetable,410676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almLowLow.REST,410676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almLowLow.ACKN,410676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almLowLow.UACK,410676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almLowLow.MCmd_Enable,410676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almLowLow.MCmd_Disable,410676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almLowLow.OCmd_Shelve,410676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almLowLow.OCmd_Unshelve,410676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almLowLow.SCmd_Suppress,410676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almLowLow.SCmd_UnSuppress,410677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almLowLow.AEShelveTMRDN,410677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almLowLow.Bad,410677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almLowLow.Suppress,410678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.UnSuppress,410678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Shelve,410678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.UnShelve,410678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Enable,410678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Disable,410678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Ack,410678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Reset,410678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Suppressed,410678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Shelved,410678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Disabled,410678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Acked,410678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almLowLow.Alarm,410678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Fault,410688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almBrokenLoop.AlarmState,410688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almBrokenLoop.GlobalReset,410688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almBrokenLoop.FaultInAlarm,410688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almBrokenLoop.ALRM,410688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almBrokenLoop.ANUN,410688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almBrokenLoop.AKED,410688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almBrokenLoop.Resetable,410688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almBrokenLoop.REST,410688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almBrokenLoop.ACKN,410688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almBrokenLoop.UACK,410688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almBrokenLoop.MCmd_Enable,410688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.MCmd_Disable,410688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.OCmd_Shelve,410688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.OCmd_Unshelve,410688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.SCmd_Suppress,410688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.SCmd_UnSuppress,410689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almBrokenLoop.AEShelveTMRDN,410689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almBrokenLoop.Bad,410689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almBrokenLoop.Suppress,410690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.UnSuppress,410690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Shelve,410690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.UnShelve,410690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Enable,410690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Disable,410690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Ack,410690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Reset,410690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Suppressed,410690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Shelved,410690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Disabled,410690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Acked,410690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.Alarm,410690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Fault,410700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almOverRange.AlarmState,410700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almOverRange.GlobalReset,410700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almOverRange.FaultInAlarm,410700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almOverRange.ALRM,410700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almOverRange.ANUN,410700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almOverRange.AKED,410700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almOverRange.Resetable,410700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almOverRange.REST,410700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almOverRange.ACKN,410700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almOverRange.UACK,410700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almOverRange.MCmd_Enable,410700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almOverRange.MCmd_Disable,410700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almOverRange.OCmd_Shelve,410700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almOverRange.OCmd_Unshelve,410700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almOverRange.SCmd_Suppress,410700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almOverRange.SCmd_UnSuppress,410701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almOverRange.AEShelveTMRDN,410701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almOverRange.Bad,410701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almOverRange.Suppress,410702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.UnSuppress,410702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Shelve,410702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.UnShelve,410702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Enable,410702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Disable,410702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Ack,410702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Reset,410702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Suppressed,410702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Shelved,410702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Disabled,410702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Acked,410702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almOverRange.Alarm,410702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Fault,410712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almUnderRange.AlarmState,410712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almUnderRange.GlobalReset,410712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almUnderRange.FaultInAlarm,410712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almUnderRange.ALRM,410712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almUnderRange.ANUN,410712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almUnderRange.AKED,410712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almUnderRange.Resetable,410712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almUnderRange.REST,410712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almUnderRange.ACKN,410712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almUnderRange.UACK,410712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almUnderRange.MCmd_Enable,410712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.MCmd_Disable,410712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.OCmd_Shelve,410712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.OCmd_Unshelve,410712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.SCmd_Suppress,410712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.SCmd_UnSuppress,410713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almUnderRange.AEShelveTMRDN,410713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almUnderRange.Bad,410713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almUnderRange.Suppress,410714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.UnSuppress,410714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Shelve,410714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.UnShelve,410714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Enable,410714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Disable,410714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Ack,410714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Reset,410714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Suppressed,410714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Shelved,410714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Disabled,410714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Acked,410714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almUnderRange.Alarm,410714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Fault,410724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almRateOfChange.AlarmState,410724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almRateOfChange.GlobalReset,410724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almRateOfChange.FaultInAlarm,410724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almRateOfChange.ALRM,410724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almRateOfChange.ANUN,410724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almRateOfChange.AKED,410724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almRateOfChange.Resetable,410724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almRateOfChange.REST,410724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almRateOfChange.ACKN,410724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almRateOfChange.UACK,410724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almRateOfChange.MCmd_Enable,410724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.MCmd_Disable,410724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.OCmd_Shelve,410724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.OCmd_Unshelve,410724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.SCmd_Suppress,410724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.SCmd_UnSuppress,410725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almRateOfChange.AEShelveTMRDN,410725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almRateOfChange.Bad,410725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almRateOfChange.Suppress,410726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.UnSuppress,410726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Shelve,410726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.UnShelve,410726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Enable,410726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Disable,410726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Ack,410726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Reset,410726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Suppressed,410726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Shelved,410726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Disabled,410726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Acked,410726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almRateOfChange.Alarm,410726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Fault,410736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI3.almPLCFault.AlarmState,410736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI3.almPLCFault.GlobalReset,410736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI3.almPLCFault.FaultInAlarm,410736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI3.almPLCFault.ALRM,410736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI3.almPLCFault.ANUN,410736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI3.almPLCFault.AKED,410736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI3.almPLCFault.Resetable,410736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI3.almPLCFault.REST,410736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI3.almPLCFault.ACKN,410736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI3.almPLCFault.UACK,410736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI3.almPLCFault.MCmd_Enable,410736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.MCmd_Disable,410736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.OCmd_Shelve,410736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.OCmd_Unshelve,410736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.SCmd_Suppress,410736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.SCmd_UnSuppress,410737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI3.almPLCFault.AEShelveTMRDN,410737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI3.almPLCFault.Bad,410737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI3.almPLCFault.Suppress,410738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.UnSuppress,410738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Shelve,410738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.UnShelve,410738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Enable,410738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Disable,410738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Ack,410738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Reset,410738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Suppressed,410738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Shelved,410738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Disabled,410738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Acked,410738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI3.almPLCFault.Alarm,410738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Fault,410840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almHighHigh.AlarmState,410840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almHighHigh.GlobalReset,410840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almHighHigh.FaultInAlarm,410840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almHighHigh.ALRM,410840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almHighHigh.ANUN,410840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almHighHigh.AKED,410840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almHighHigh.Resetable,410840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almHighHigh.REST,410840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almHighHigh.ACKN,410840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almHighHigh.UACK,410840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almHighHigh.MCmd_Enable,410840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.MCmd_Disable,410840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.OCmd_Shelve,410840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.OCmd_Unshelve,410840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.SCmd_Suppress,410840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.SCmd_UnSuppress,410841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almHighHigh.AEShelveTMRDN,410841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almHighHigh.Bad,410841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almHighHigh.Suppress,410842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.UnSuppress,410842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Shelve,410842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.UnShelve,410842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Enable,410842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Disable,410842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Ack,410842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Reset,410842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Suppressed,410842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Shelved,410842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Disabled,410842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Acked,410842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almHighHigh.Alarm,410842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Fault,410852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almHigh.AlarmState,410852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almHigh.GlobalReset,410852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almHigh.FaultInAlarm,410852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almHigh.ALRM,410852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almHigh.ANUN,410852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almHigh.AKED,410852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almHigh.Resetable,410852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almHigh.REST,410852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almHigh.ACKN,410852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almHigh.UACK,410852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almHigh.MCmd_Enable,410852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almHigh.MCmd_Disable,410852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almHigh.OCmd_Shelve,410852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almHigh.OCmd_Unshelve,410852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almHigh.SCmd_Suppress,410852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almHigh.SCmd_UnSuppress,410853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almHigh.AEShelveTMRDN,410853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almHigh.Bad,410853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almHigh.Suppress,410854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.UnSuppress,410854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Shelve,410854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.UnShelve,410854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Enable,410854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Disable,410854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Ack,410854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Reset,410854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almHigh.Suppressed,410854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almHigh.Shelved,410854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almHigh.Disabled,410854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almHigh.Acked,410854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almHigh.Alarm,410854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Fault,410864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almLow.AlarmState,410864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almLow.GlobalReset,410864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almLow.FaultInAlarm,410864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almLow.ALRM,410864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almLow.ANUN,410864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almLow.AKED,410864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almLow.Resetable,410864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almLow.REST,410864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almLow.ACKN,410864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almLow.UACK,410864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almLow.MCmd_Enable,410864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almLow.MCmd_Disable,410864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almLow.OCmd_Shelve,410864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almLow.OCmd_Unshelve,410864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almLow.SCmd_Suppress,410864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almLow.SCmd_UnSuppress,410865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almLow.AEShelveTMRDN,410865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almLow.Bad,410865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almLow.Suppress,410866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.UnSuppress,410866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Shelve,410866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.UnShelve,410866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Enable,410866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Disable,410866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Ack,410866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Reset,410866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almLow.Suppressed,410866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almLow.Shelved,410866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almLow.Disabled,410866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almLow.Acked,410866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almLow.Alarm,410866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Fault,410876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almLowLow.AlarmState,410876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almLowLow.GlobalReset,410876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almLowLow.FaultInAlarm,410876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almLowLow.ALRM,410876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almLowLow.ANUN,410876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almLowLow.AKED,410876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almLowLow.Resetable,410876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almLowLow.REST,410876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almLowLow.ACKN,410876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almLowLow.UACK,410876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almLowLow.MCmd_Enable,410876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almLowLow.MCmd_Disable,410876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almLowLow.OCmd_Shelve,410876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almLowLow.OCmd_Unshelve,410876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almLowLow.SCmd_Suppress,410876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almLowLow.SCmd_UnSuppress,410877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almLowLow.AEShelveTMRDN,410877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almLowLow.Bad,410877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almLowLow.Suppress,410878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.UnSuppress,410878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Shelve,410878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.UnShelve,410878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Enable,410878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Disable,410878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Ack,410878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Reset,410878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Suppressed,410878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Shelved,410878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Disabled,410878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Acked,410878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almLowLow.Alarm,410878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Fault,410888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almBrokenLoop.AlarmState,410888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almBrokenLoop.GlobalReset,410888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almBrokenLoop.FaultInAlarm,410888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almBrokenLoop.ALRM,410888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almBrokenLoop.ANUN,410888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almBrokenLoop.AKED,410888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almBrokenLoop.Resetable,410888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almBrokenLoop.REST,410888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almBrokenLoop.ACKN,410888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almBrokenLoop.UACK,410888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almBrokenLoop.MCmd_Enable,410888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.MCmd_Disable,410888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.OCmd_Shelve,410888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.OCmd_Unshelve,410888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.SCmd_Suppress,410888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.SCmd_UnSuppress,410889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almBrokenLoop.AEShelveTMRDN,410889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almBrokenLoop.Bad,410889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almBrokenLoop.Suppress,410890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.UnSuppress,410890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Shelve,410890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.UnShelve,410890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Enable,410890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Disable,410890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Ack,410890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Reset,410890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Suppressed,410890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Shelved,410890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Disabled,410890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Acked,410890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.Alarm,410890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Fault,410900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almOverRange.AlarmState,410900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almOverRange.GlobalReset,410900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almOverRange.FaultInAlarm,410900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almOverRange.ALRM,410900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almOverRange.ANUN,410900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almOverRange.AKED,410900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almOverRange.Resetable,410900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almOverRange.REST,410900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almOverRange.ACKN,410900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almOverRange.UACK,410900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almOverRange.MCmd_Enable,410900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almOverRange.MCmd_Disable,410900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almOverRange.OCmd_Shelve,410900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almOverRange.OCmd_Unshelve,410900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almOverRange.SCmd_Suppress,410900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almOverRange.SCmd_UnSuppress,410901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almOverRange.AEShelveTMRDN,410901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almOverRange.Bad,410901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almOverRange.Suppress,410902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.UnSuppress,410902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Shelve,410902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.UnShelve,410902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Enable,410902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Disable,410902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Ack,410902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Reset,410902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Suppressed,410902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Shelved,410902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Disabled,410902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Acked,410902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almOverRange.Alarm,410902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Fault,410912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almUnderRange.AlarmState,410912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almUnderRange.GlobalReset,410912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almUnderRange.FaultInAlarm,410912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almUnderRange.ALRM,410912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almUnderRange.ANUN,410912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almUnderRange.AKED,410912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almUnderRange.Resetable,410912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almUnderRange.REST,410912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almUnderRange.ACKN,410912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almUnderRange.UACK,410912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almUnderRange.MCmd_Enable,410912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.MCmd_Disable,410912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.OCmd_Shelve,410912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.OCmd_Unshelve,410912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.SCmd_Suppress,410912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.SCmd_UnSuppress,410913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almUnderRange.AEShelveTMRDN,410913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almUnderRange.Bad,410913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almUnderRange.Suppress,410914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.UnSuppress,410914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Shelve,410914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.UnShelve,410914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Enable,410914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Disable,410914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Ack,410914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Reset,410914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Suppressed,410914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Shelved,410914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Disabled,410914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Acked,410914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almUnderRange.Alarm,410914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Fault,410924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almRateOfChange.AlarmState,410924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almRateOfChange.GlobalReset,410924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almRateOfChange.FaultInAlarm,410924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almRateOfChange.ALRM,410924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almRateOfChange.ANUN,410924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almRateOfChange.AKED,410924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almRateOfChange.Resetable,410924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almRateOfChange.REST,410924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almRateOfChange.ACKN,410924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almRateOfChange.UACK,410924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almRateOfChange.MCmd_Enable,410924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.MCmd_Disable,410924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.OCmd_Shelve,410924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.OCmd_Unshelve,410924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.SCmd_Suppress,410924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.SCmd_UnSuppress,410925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almRateOfChange.AEShelveTMRDN,410925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almRateOfChange.Bad,410925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almRateOfChange.Suppress,410926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.UnSuppress,410926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Shelve,410926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.UnShelve,410926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Enable,410926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Disable,410926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Ack,410926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Reset,410926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Suppressed,410926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Shelved,410926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Disabled,410926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Acked,410926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almRateOfChange.Alarm,410926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Fault,410936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_5_VI4.almPLCFault.AlarmState,410936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_5_VI4.almPLCFault.GlobalReset,410936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_5_VI4.almPLCFault.FaultInAlarm,410936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_5_VI4.almPLCFault.ALRM,410936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_5_VI4.almPLCFault.ANUN,410936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_5_VI4.almPLCFault.AKED,410936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_5_VI4.almPLCFault.Resetable,410936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_5_VI4.almPLCFault.REST,410936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_5_VI4.almPLCFault.ACKN,410936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_5_VI4.almPLCFault.UACK,410936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_5_VI4.almPLCFault.MCmd_Enable,410936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.MCmd_Disable,410936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.OCmd_Shelve,410936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.OCmd_Unshelve,410936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.SCmd_Suppress,410936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.SCmd_UnSuppress,410937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_5_VI4.almPLCFault.AEShelveTMRDN,410937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_5_VI4.almPLCFault.Bad,410937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_5_VI4.almPLCFault.Suppress,410938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.UnSuppress,410938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Shelve,410938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.UnShelve,410938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Enable,410938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Disable,410938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Ack,410938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Reset,410938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Suppressed,410938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Shelved,410938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Disabled,410938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Acked,410938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_5_VI4.almPLCFault.Alarm,410938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Fault,411040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almHighHigh.AlarmState,411040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almHighHigh.GlobalReset,411040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almHighHigh.FaultInAlarm,411040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almHighHigh.ALRM,411040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almHighHigh.ANUN,411040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almHighHigh.AKED,411040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almHighHigh.Resetable,411040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almHighHigh.REST,411040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almHighHigh.ACKN,411040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almHighHigh.UACK,411040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almHighHigh.MCmd_Enable,411040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.MCmd_Disable,411040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.OCmd_Shelve,411040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.OCmd_Unshelve,411040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.SCmd_Suppress,411040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.SCmd_UnSuppress,411041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almHighHigh.AEShelveTMRDN,411041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almHighHigh.Bad,411041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almHighHigh.Suppress,411042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.UnSuppress,411042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Shelve,411042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.UnShelve,411042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Enable,411042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Disable,411042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Ack,411042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Reset,411042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Suppressed,411042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Shelved,411042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Disabled,411042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Acked,411042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almHighHigh.Alarm,411042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Fault,411052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almHigh.AlarmState,411052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almHigh.GlobalReset,411052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almHigh.FaultInAlarm,411052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almHigh.ALRM,411052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almHigh.ANUN,411052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almHigh.AKED,411052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almHigh.Resetable,411052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almHigh.REST,411052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almHigh.ACKN,411052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almHigh.UACK,411052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almHigh.MCmd_Enable,411052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almHigh.MCmd_Disable,411052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almHigh.OCmd_Shelve,411052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almHigh.OCmd_Unshelve,411052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almHigh.SCmd_Suppress,411052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almHigh.SCmd_UnSuppress,411053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almHigh.AEShelveTMRDN,411053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almHigh.Bad,411053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almHigh.Suppress,411054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.UnSuppress,411054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Shelve,411054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.UnShelve,411054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Enable,411054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Disable,411054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Ack,411054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Reset,411054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almHigh.Suppressed,411054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almHigh.Shelved,411054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almHigh.Disabled,411054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almHigh.Acked,411054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almHigh.Alarm,411054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Fault,411064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almLow.AlarmState,411064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almLow.GlobalReset,411064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almLow.FaultInAlarm,411064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almLow.ALRM,411064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almLow.ANUN,411064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almLow.AKED,411064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almLow.Resetable,411064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almLow.REST,411064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almLow.ACKN,411064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almLow.UACK,411064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almLow.MCmd_Enable,411064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almLow.MCmd_Disable,411064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almLow.OCmd_Shelve,411064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almLow.OCmd_Unshelve,411064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almLow.SCmd_Suppress,411064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almLow.SCmd_UnSuppress,411065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almLow.AEShelveTMRDN,411065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almLow.Bad,411065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almLow.Suppress,411066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.UnSuppress,411066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Shelve,411066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.UnShelve,411066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Enable,411066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Disable,411066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Ack,411066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Reset,411066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almLow.Suppressed,411066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almLow.Shelved,411066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almLow.Disabled,411066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almLow.Acked,411066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almLow.Alarm,411066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Fault,411076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almLowLow.AlarmState,411076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almLowLow.GlobalReset,411076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almLowLow.FaultInAlarm,411076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almLowLow.ALRM,411076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almLowLow.ANUN,411076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almLowLow.AKED,411076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almLowLow.Resetable,411076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almLowLow.REST,411076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almLowLow.ACKN,411076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almLowLow.UACK,411076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almLowLow.MCmd_Enable,411076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almLowLow.MCmd_Disable,411076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almLowLow.OCmd_Shelve,411076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almLowLow.OCmd_Unshelve,411076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almLowLow.SCmd_Suppress,411076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almLowLow.SCmd_UnSuppress,411077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almLowLow.AEShelveTMRDN,411077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almLowLow.Bad,411077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almLowLow.Suppress,411078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.UnSuppress,411078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Shelve,411078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.UnShelve,411078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Enable,411078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Disable,411078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Ack,411078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Reset,411078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Suppressed,411078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Shelved,411078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Disabled,411078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Acked,411078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almLowLow.Alarm,411078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Fault,411088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almBrokenLoop.AlarmState,411088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almBrokenLoop.GlobalReset,411088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almBrokenLoop.FaultInAlarm,411088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almBrokenLoop.ALRM,411088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almBrokenLoop.ANUN,411088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almBrokenLoop.AKED,411088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almBrokenLoop.Resetable,411088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almBrokenLoop.REST,411088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almBrokenLoop.ACKN,411088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almBrokenLoop.UACK,411088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almBrokenLoop.MCmd_Enable,411088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.MCmd_Disable,411088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.OCmd_Shelve,411088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.OCmd_Unshelve,411088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.SCmd_Suppress,411088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.SCmd_UnSuppress,411089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almBrokenLoop.AEShelveTMRDN,411089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almBrokenLoop.Bad,411089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almBrokenLoop.Suppress,411090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.UnSuppress,411090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Shelve,411090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.UnShelve,411090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Enable,411090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Disable,411090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Ack,411090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Reset,411090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Suppressed,411090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Shelved,411090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Disabled,411090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Acked,411090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.Alarm,411090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Fault,411100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almOverRange.AlarmState,411100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almOverRange.GlobalReset,411100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almOverRange.FaultInAlarm,411100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almOverRange.ALRM,411100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almOverRange.ANUN,411100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almOverRange.AKED,411100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almOverRange.Resetable,411100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almOverRange.REST,411100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almOverRange.ACKN,411100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almOverRange.UACK,411100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almOverRange.MCmd_Enable,411100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almOverRange.MCmd_Disable,411100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almOverRange.OCmd_Shelve,411100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almOverRange.OCmd_Unshelve,411100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almOverRange.SCmd_Suppress,411100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almOverRange.SCmd_UnSuppress,411101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almOverRange.AEShelveTMRDN,411101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almOverRange.Bad,411101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almOverRange.Suppress,411102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.UnSuppress,411102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Shelve,411102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.UnShelve,411102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Enable,411102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Disable,411102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Ack,411102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Reset,411102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Suppressed,411102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Shelved,411102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Disabled,411102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Acked,411102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almOverRange.Alarm,411102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Fault,411112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almUnderRange.AlarmState,411112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almUnderRange.GlobalReset,411112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almUnderRange.FaultInAlarm,411112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almUnderRange.ALRM,411112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almUnderRange.ANUN,411112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almUnderRange.AKED,411112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almUnderRange.Resetable,411112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almUnderRange.REST,411112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almUnderRange.ACKN,411112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almUnderRange.UACK,411112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almUnderRange.MCmd_Enable,411112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.MCmd_Disable,411112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.OCmd_Shelve,411112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.OCmd_Unshelve,411112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.SCmd_Suppress,411112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.SCmd_UnSuppress,411113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almUnderRange.AEShelveTMRDN,411113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almUnderRange.Bad,411113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almUnderRange.Suppress,411114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.UnSuppress,411114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Shelve,411114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.UnShelve,411114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Enable,411114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Disable,411114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Ack,411114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Reset,411114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Suppressed,411114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Shelved,411114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Disabled,411114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Acked,411114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almUnderRange.Alarm,411114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Fault,411124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almRateOfChange.AlarmState,411124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almRateOfChange.GlobalReset,411124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almRateOfChange.FaultInAlarm,411124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almRateOfChange.ALRM,411124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almRateOfChange.ANUN,411124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almRateOfChange.AKED,411124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almRateOfChange.Resetable,411124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almRateOfChange.REST,411124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almRateOfChange.ACKN,411124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almRateOfChange.UACK,411124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almRateOfChange.MCmd_Enable,411124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.MCmd_Disable,411124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.OCmd_Shelve,411124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.OCmd_Unshelve,411124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.SCmd_Suppress,411124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.SCmd_UnSuppress,411125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almRateOfChange.AEShelveTMRDN,411125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almRateOfChange.Bad,411125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almRateOfChange.Suppress,411126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.UnSuppress,411126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Shelve,411126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.UnShelve,411126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Enable,411126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Disable,411126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Ack,411126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Reset,411126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Suppressed,411126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Shelved,411126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Disabled,411126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Acked,411126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almRateOfChange.Alarm,411126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Fault,411136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI1.almPLCFault.AlarmState,411136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI1.almPLCFault.GlobalReset,411136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI1.almPLCFault.FaultInAlarm,411136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI1.almPLCFault.ALRM,411136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI1.almPLCFault.ANUN,411136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI1.almPLCFault.AKED,411136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI1.almPLCFault.Resetable,411136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI1.almPLCFault.REST,411136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI1.almPLCFault.ACKN,411136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI1.almPLCFault.UACK,411136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI1.almPLCFault.MCmd_Enable,411136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.MCmd_Disable,411136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.OCmd_Shelve,411136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.OCmd_Unshelve,411136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.SCmd_Suppress,411136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.SCmd_UnSuppress,411137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI1.almPLCFault.AEShelveTMRDN,411137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI1.almPLCFault.Bad,411137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI1.almPLCFault.Suppress,411138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.UnSuppress,411138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Shelve,411138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.UnShelve,411138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Enable,411138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Disable,411138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Ack,411138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Reset,411138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Suppressed,411138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Shelved,411138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Disabled,411138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Acked,411138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI1.almPLCFault.Alarm,411138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Fault,411240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almHighHigh.AlarmState,411240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almHighHigh.GlobalReset,411240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almHighHigh.FaultInAlarm,411240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almHighHigh.ALRM,411240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almHighHigh.ANUN,411240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almHighHigh.AKED,411240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almHighHigh.Resetable,411240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almHighHigh.REST,411240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almHighHigh.ACKN,411240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almHighHigh.UACK,411240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almHighHigh.MCmd_Enable,411240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.MCmd_Disable,411240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.OCmd_Shelve,411240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.OCmd_Unshelve,411240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.SCmd_Suppress,411240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.SCmd_UnSuppress,411241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almHighHigh.AEShelveTMRDN,411241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almHighHigh.Bad,411241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almHighHigh.Suppress,411242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.UnSuppress,411242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Shelve,411242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.UnShelve,411242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Enable,411242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Disable,411242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Ack,411242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Reset,411242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Suppressed,411242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Shelved,411242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Disabled,411242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Acked,411242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almHighHigh.Alarm,411242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Fault,411252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almHigh.AlarmState,411252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almHigh.GlobalReset,411252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almHigh.FaultInAlarm,411252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almHigh.ALRM,411252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almHigh.ANUN,411252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almHigh.AKED,411252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almHigh.Resetable,411252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almHigh.REST,411252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almHigh.ACKN,411252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almHigh.UACK,411252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almHigh.MCmd_Enable,411252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almHigh.MCmd_Disable,411252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almHigh.OCmd_Shelve,411252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almHigh.OCmd_Unshelve,411252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almHigh.SCmd_Suppress,411252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almHigh.SCmd_UnSuppress,411253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almHigh.AEShelveTMRDN,411253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almHigh.Bad,411253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almHigh.Suppress,411254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.UnSuppress,411254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Shelve,411254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.UnShelve,411254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Enable,411254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Disable,411254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Ack,411254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Reset,411254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almHigh.Suppressed,411254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almHigh.Shelved,411254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almHigh.Disabled,411254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almHigh.Acked,411254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almHigh.Alarm,411254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Fault,411264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almLow.AlarmState,411264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almLow.GlobalReset,411264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almLow.FaultInAlarm,411264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almLow.ALRM,411264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almLow.ANUN,411264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almLow.AKED,411264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almLow.Resetable,411264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almLow.REST,411264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almLow.ACKN,411264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almLow.UACK,411264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almLow.MCmd_Enable,411264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almLow.MCmd_Disable,411264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almLow.OCmd_Shelve,411264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almLow.OCmd_Unshelve,411264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almLow.SCmd_Suppress,411264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almLow.SCmd_UnSuppress,411265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almLow.AEShelveTMRDN,411265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almLow.Bad,411265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almLow.Suppress,411266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.UnSuppress,411266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Shelve,411266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.UnShelve,411266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Enable,411266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Disable,411266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Ack,411266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Reset,411266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almLow.Suppressed,411266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almLow.Shelved,411266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almLow.Disabled,411266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almLow.Acked,411266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almLow.Alarm,411266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Fault,411276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almLowLow.AlarmState,411276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almLowLow.GlobalReset,411276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almLowLow.FaultInAlarm,411276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almLowLow.ALRM,411276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almLowLow.ANUN,411276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almLowLow.AKED,411276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almLowLow.Resetable,411276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almLowLow.REST,411276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almLowLow.ACKN,411276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almLowLow.UACK,411276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almLowLow.MCmd_Enable,411276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almLowLow.MCmd_Disable,411276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almLowLow.OCmd_Shelve,411276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almLowLow.OCmd_Unshelve,411276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almLowLow.SCmd_Suppress,411276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almLowLow.SCmd_UnSuppress,411277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almLowLow.AEShelveTMRDN,411277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almLowLow.Bad,411277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almLowLow.Suppress,411278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.UnSuppress,411278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Shelve,411278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.UnShelve,411278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Enable,411278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Disable,411278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Ack,411278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Reset,411278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Suppressed,411278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Shelved,411278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Disabled,411278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Acked,411278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almLowLow.Alarm,411278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Fault,411288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almBrokenLoop.AlarmState,411288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almBrokenLoop.GlobalReset,411288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almBrokenLoop.FaultInAlarm,411288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almBrokenLoop.ALRM,411288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almBrokenLoop.ANUN,411288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almBrokenLoop.AKED,411288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almBrokenLoop.Resetable,411288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almBrokenLoop.REST,411288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almBrokenLoop.ACKN,411288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almBrokenLoop.UACK,411288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almBrokenLoop.MCmd_Enable,411288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.MCmd_Disable,411288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.OCmd_Shelve,411288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.OCmd_Unshelve,411288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.SCmd_Suppress,411288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.SCmd_UnSuppress,411289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almBrokenLoop.AEShelveTMRDN,411289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almBrokenLoop.Bad,411289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almBrokenLoop.Suppress,411290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.UnSuppress,411290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Shelve,411290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.UnShelve,411290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Enable,411290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Disable,411290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Ack,411290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Reset,411290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Suppressed,411290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Shelved,411290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Disabled,411290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Acked,411290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.Alarm,411290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Fault,411300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almOverRange.AlarmState,411300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almOverRange.GlobalReset,411300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almOverRange.FaultInAlarm,411300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almOverRange.ALRM,411300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almOverRange.ANUN,411300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almOverRange.AKED,411300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almOverRange.Resetable,411300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almOverRange.REST,411300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almOverRange.ACKN,411300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almOverRange.UACK,411300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almOverRange.MCmd_Enable,411300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almOverRange.MCmd_Disable,411300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almOverRange.OCmd_Shelve,411300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almOverRange.OCmd_Unshelve,411300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almOverRange.SCmd_Suppress,411300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almOverRange.SCmd_UnSuppress,411301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almOverRange.AEShelveTMRDN,411301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almOverRange.Bad,411301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almOverRange.Suppress,411302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.UnSuppress,411302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Shelve,411302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.UnShelve,411302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Enable,411302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Disable,411302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Ack,411302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Reset,411302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Suppressed,411302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Shelved,411302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Disabled,411302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Acked,411302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almOverRange.Alarm,411302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Fault,411312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almUnderRange.AlarmState,411312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almUnderRange.GlobalReset,411312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almUnderRange.FaultInAlarm,411312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almUnderRange.ALRM,411312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almUnderRange.ANUN,411312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almUnderRange.AKED,411312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almUnderRange.Resetable,411312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almUnderRange.REST,411312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almUnderRange.ACKN,411312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almUnderRange.UACK,411312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almUnderRange.MCmd_Enable,411312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.MCmd_Disable,411312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.OCmd_Shelve,411312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.OCmd_Unshelve,411312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.SCmd_Suppress,411312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.SCmd_UnSuppress,411313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almUnderRange.AEShelveTMRDN,411313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almUnderRange.Bad,411313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almUnderRange.Suppress,411314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.UnSuppress,411314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Shelve,411314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.UnShelve,411314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Enable,411314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Disable,411314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Ack,411314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Reset,411314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Suppressed,411314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Shelved,411314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Disabled,411314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Acked,411314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almUnderRange.Alarm,411314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Fault,411324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almRateOfChange.AlarmState,411324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almRateOfChange.GlobalReset,411324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almRateOfChange.FaultInAlarm,411324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almRateOfChange.ALRM,411324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almRateOfChange.ANUN,411324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almRateOfChange.AKED,411324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almRateOfChange.Resetable,411324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almRateOfChange.REST,411324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almRateOfChange.ACKN,411324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almRateOfChange.UACK,411324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almRateOfChange.MCmd_Enable,411324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.MCmd_Disable,411324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.OCmd_Shelve,411324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.OCmd_Unshelve,411324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.SCmd_Suppress,411324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.SCmd_UnSuppress,411325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almRateOfChange.AEShelveTMRDN,411325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almRateOfChange.Bad,411325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almRateOfChange.Suppress,411326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.UnSuppress,411326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Shelve,411326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.UnShelve,411326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Enable,411326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Disable,411326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Ack,411326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Reset,411326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Suppressed,411326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Shelved,411326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Disabled,411326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Acked,411326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almRateOfChange.Alarm,411326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Fault,411336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI2.almPLCFault.AlarmState,411336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI2.almPLCFault.GlobalReset,411336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI2.almPLCFault.FaultInAlarm,411336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI2.almPLCFault.ALRM,411336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI2.almPLCFault.ANUN,411336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI2.almPLCFault.AKED,411336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI2.almPLCFault.Resetable,411336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI2.almPLCFault.REST,411336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI2.almPLCFault.ACKN,411336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI2.almPLCFault.UACK,411336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI2.almPLCFault.MCmd_Enable,411336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.MCmd_Disable,411336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.OCmd_Shelve,411336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.OCmd_Unshelve,411336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.SCmd_Suppress,411336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.SCmd_UnSuppress,411337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI2.almPLCFault.AEShelveTMRDN,411337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI2.almPLCFault.Bad,411337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI2.almPLCFault.Suppress,411338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.UnSuppress,411338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Shelve,411338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.UnShelve,411338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Enable,411338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Disable,411338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Ack,411338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Reset,411338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Suppressed,411338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Shelved,411338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Disabled,411338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Acked,411338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI2.almPLCFault.Alarm,411338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Fault,411440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almHighHigh.AlarmState,411440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almHighHigh.GlobalReset,411440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almHighHigh.FaultInAlarm,411440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almHighHigh.ALRM,411440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almHighHigh.ANUN,411440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almHighHigh.AKED,411440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almHighHigh.Resetable,411440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almHighHigh.REST,411440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almHighHigh.ACKN,411440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almHighHigh.UACK,411440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almHighHigh.MCmd_Enable,411440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.MCmd_Disable,411440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.OCmd_Shelve,411440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.OCmd_Unshelve,411440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.SCmd_Suppress,411440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.SCmd_UnSuppress,411441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almHighHigh.AEShelveTMRDN,411441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almHighHigh.Bad,411441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almHighHigh.Suppress,411442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.UnSuppress,411442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Shelve,411442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.UnShelve,411442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Enable,411442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Disable,411442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Ack,411442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Reset,411442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Suppressed,411442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Shelved,411442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Disabled,411442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Acked,411442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almHighHigh.Alarm,411442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Fault,411452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almHigh.AlarmState,411452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almHigh.GlobalReset,411452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almHigh.FaultInAlarm,411452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almHigh.ALRM,411452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almHigh.ANUN,411452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almHigh.AKED,411452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almHigh.Resetable,411452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almHigh.REST,411452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almHigh.ACKN,411452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almHigh.UACK,411452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almHigh.MCmd_Enable,411452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almHigh.MCmd_Disable,411452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almHigh.OCmd_Shelve,411452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almHigh.OCmd_Unshelve,411452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almHigh.SCmd_Suppress,411452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almHigh.SCmd_UnSuppress,411453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almHigh.AEShelveTMRDN,411453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almHigh.Bad,411453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almHigh.Suppress,411454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.UnSuppress,411454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Shelve,411454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.UnShelve,411454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Enable,411454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Disable,411454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Ack,411454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Reset,411454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almHigh.Suppressed,411454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almHigh.Shelved,411454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almHigh.Disabled,411454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almHigh.Acked,411454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almHigh.Alarm,411454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Fault,411464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almLow.AlarmState,411464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almLow.GlobalReset,411464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almLow.FaultInAlarm,411464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almLow.ALRM,411464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almLow.ANUN,411464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almLow.AKED,411464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almLow.Resetable,411464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almLow.REST,411464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almLow.ACKN,411464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almLow.UACK,411464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almLow.MCmd_Enable,411464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almLow.MCmd_Disable,411464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almLow.OCmd_Shelve,411464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almLow.OCmd_Unshelve,411464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almLow.SCmd_Suppress,411464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almLow.SCmd_UnSuppress,411465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almLow.AEShelveTMRDN,411465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almLow.Bad,411465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almLow.Suppress,411466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.UnSuppress,411466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Shelve,411466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.UnShelve,411466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Enable,411466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Disable,411466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Ack,411466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Reset,411466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almLow.Suppressed,411466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almLow.Shelved,411466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almLow.Disabled,411466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almLow.Acked,411466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almLow.Alarm,411466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Fault,411476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almLowLow.AlarmState,411476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almLowLow.GlobalReset,411476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almLowLow.FaultInAlarm,411476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almLowLow.ALRM,411476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almLowLow.ANUN,411476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almLowLow.AKED,411476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almLowLow.Resetable,411476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almLowLow.REST,411476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almLowLow.ACKN,411476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almLowLow.UACK,411476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almLowLow.MCmd_Enable,411476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almLowLow.MCmd_Disable,411476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almLowLow.OCmd_Shelve,411476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almLowLow.OCmd_Unshelve,411476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almLowLow.SCmd_Suppress,411476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almLowLow.SCmd_UnSuppress,411477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almLowLow.AEShelveTMRDN,411477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almLowLow.Bad,411477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almLowLow.Suppress,411478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.UnSuppress,411478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Shelve,411478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.UnShelve,411478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Enable,411478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Disable,411478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Ack,411478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Reset,411478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Suppressed,411478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Shelved,411478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Disabled,411478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Acked,411478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almLowLow.Alarm,411478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Fault,411488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almBrokenLoop.AlarmState,411488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almBrokenLoop.GlobalReset,411488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almBrokenLoop.FaultInAlarm,411488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almBrokenLoop.ALRM,411488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almBrokenLoop.ANUN,411488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almBrokenLoop.AKED,411488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almBrokenLoop.Resetable,411488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almBrokenLoop.REST,411488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almBrokenLoop.ACKN,411488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almBrokenLoop.UACK,411488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almBrokenLoop.MCmd_Enable,411488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.MCmd_Disable,411488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.OCmd_Shelve,411488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.OCmd_Unshelve,411488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.SCmd_Suppress,411488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.SCmd_UnSuppress,411489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almBrokenLoop.AEShelveTMRDN,411489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almBrokenLoop.Bad,411489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almBrokenLoop.Suppress,411490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.UnSuppress,411490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Shelve,411490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.UnShelve,411490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Enable,411490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Disable,411490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Ack,411490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Reset,411490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Suppressed,411490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Shelved,411490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Disabled,411490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Acked,411490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.Alarm,411490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Fault,411500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almOverRange.AlarmState,411500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almOverRange.GlobalReset,411500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almOverRange.FaultInAlarm,411500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almOverRange.ALRM,411500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almOverRange.ANUN,411500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almOverRange.AKED,411500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almOverRange.Resetable,411500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almOverRange.REST,411500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almOverRange.ACKN,411500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almOverRange.UACK,411500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almOverRange.MCmd_Enable,411500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almOverRange.MCmd_Disable,411500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almOverRange.OCmd_Shelve,411500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almOverRange.OCmd_Unshelve,411500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almOverRange.SCmd_Suppress,411500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almOverRange.SCmd_UnSuppress,411501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almOverRange.AEShelveTMRDN,411501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almOverRange.Bad,411501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almOverRange.Suppress,411502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.UnSuppress,411502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Shelve,411502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.UnShelve,411502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Enable,411502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Disable,411502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Ack,411502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Reset,411502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Suppressed,411502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Shelved,411502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Disabled,411502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Acked,411502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almOverRange.Alarm,411502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Fault,411512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almUnderRange.AlarmState,411512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almUnderRange.GlobalReset,411512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almUnderRange.FaultInAlarm,411512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almUnderRange.ALRM,411512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almUnderRange.ANUN,411512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almUnderRange.AKED,411512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almUnderRange.Resetable,411512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almUnderRange.REST,411512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almUnderRange.ACKN,411512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almUnderRange.UACK,411512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almUnderRange.MCmd_Enable,411512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.MCmd_Disable,411512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.OCmd_Shelve,411512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.OCmd_Unshelve,411512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.SCmd_Suppress,411512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.SCmd_UnSuppress,411513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almUnderRange.AEShelveTMRDN,411513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almUnderRange.Bad,411513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almUnderRange.Suppress,411514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.UnSuppress,411514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Shelve,411514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.UnShelve,411514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Enable,411514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Disable,411514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Ack,411514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Reset,411514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Suppressed,411514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Shelved,411514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Disabled,411514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Acked,411514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almUnderRange.Alarm,411514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Fault,411524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almRateOfChange.AlarmState,411524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almRateOfChange.GlobalReset,411524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almRateOfChange.FaultInAlarm,411524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almRateOfChange.ALRM,411524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almRateOfChange.ANUN,411524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almRateOfChange.AKED,411524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almRateOfChange.Resetable,411524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almRateOfChange.REST,411524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almRateOfChange.ACKN,411524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almRateOfChange.UACK,411524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almRateOfChange.MCmd_Enable,411524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.MCmd_Disable,411524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.OCmd_Shelve,411524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.OCmd_Unshelve,411524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.SCmd_Suppress,411524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.SCmd_UnSuppress,411525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almRateOfChange.AEShelveTMRDN,411525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almRateOfChange.Bad,411525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almRateOfChange.Suppress,411526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.UnSuppress,411526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Shelve,411526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.UnShelve,411526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Enable,411526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Disable,411526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Ack,411526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Reset,411526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Suppressed,411526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Shelved,411526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Disabled,411526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Acked,411526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almRateOfChange.Alarm,411526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Fault,411536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI3.almPLCFault.AlarmState,411536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI3.almPLCFault.GlobalReset,411536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI3.almPLCFault.FaultInAlarm,411536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI3.almPLCFault.ALRM,411536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI3.almPLCFault.ANUN,411536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI3.almPLCFault.AKED,411536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI3.almPLCFault.Resetable,411536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI3.almPLCFault.REST,411536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI3.almPLCFault.ACKN,411536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI3.almPLCFault.UACK,411536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI3.almPLCFault.MCmd_Enable,411536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.MCmd_Disable,411536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.OCmd_Shelve,411536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.OCmd_Unshelve,411536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.SCmd_Suppress,411536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.SCmd_UnSuppress,411537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI3.almPLCFault.AEShelveTMRDN,411537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI3.almPLCFault.Bad,411537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI3.almPLCFault.Suppress,411538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.UnSuppress,411538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Shelve,411538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.UnShelve,411538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Enable,411538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Disable,411538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Ack,411538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Reset,411538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Suppressed,411538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Shelved,411538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Disabled,411538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Acked,411538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI3.almPLCFault.Alarm,411538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Fault,411640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almHighHigh.AlarmState,411640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almHighHigh.GlobalReset,411640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almHighHigh.FaultInAlarm,411640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almHighHigh.ALRM,411640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almHighHigh.ANUN,411640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almHighHigh.AKED,411640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almHighHigh.Resetable,411640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almHighHigh.REST,411640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almHighHigh.ACKN,411640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almHighHigh.UACK,411640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almHighHigh.MCmd_Enable,411640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.MCmd_Disable,411640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.OCmd_Shelve,411640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.OCmd_Unshelve,411640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.SCmd_Suppress,411640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.SCmd_UnSuppress,411641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almHighHigh.AEShelveTMRDN,411641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almHighHigh.Bad,411641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almHighHigh.Suppress,411642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.UnSuppress,411642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Shelve,411642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.UnShelve,411642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Enable,411642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Disable,411642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Ack,411642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Reset,411642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Suppressed,411642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Shelved,411642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Disabled,411642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Acked,411642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almHighHigh.Alarm,411642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Fault,411652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almHigh.AlarmState,411652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almHigh.GlobalReset,411652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almHigh.FaultInAlarm,411652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almHigh.ALRM,411652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almHigh.ANUN,411652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almHigh.AKED,411652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almHigh.Resetable,411652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almHigh.REST,411652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almHigh.ACKN,411652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almHigh.UACK,411652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almHigh.MCmd_Enable,411652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almHigh.MCmd_Disable,411652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almHigh.OCmd_Shelve,411652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almHigh.OCmd_Unshelve,411652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almHigh.SCmd_Suppress,411652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almHigh.SCmd_UnSuppress,411653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almHigh.AEShelveTMRDN,411653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almHigh.Bad,411653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almHigh.Suppress,411654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.UnSuppress,411654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Shelve,411654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.UnShelve,411654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Enable,411654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Disable,411654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Ack,411654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Reset,411654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almHigh.Suppressed,411654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almHigh.Shelved,411654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almHigh.Disabled,411654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almHigh.Acked,411654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almHigh.Alarm,411654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Fault,411664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almLow.AlarmState,411664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almLow.GlobalReset,411664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almLow.FaultInAlarm,411664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almLow.ALRM,411664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almLow.ANUN,411664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almLow.AKED,411664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almLow.Resetable,411664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almLow.REST,411664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almLow.ACKN,411664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almLow.UACK,411664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almLow.MCmd_Enable,411664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almLow.MCmd_Disable,411664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almLow.OCmd_Shelve,411664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almLow.OCmd_Unshelve,411664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almLow.SCmd_Suppress,411664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almLow.SCmd_UnSuppress,411665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almLow.AEShelveTMRDN,411665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almLow.Bad,411665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almLow.Suppress,411666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.UnSuppress,411666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Shelve,411666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.UnShelve,411666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Enable,411666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Disable,411666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Ack,411666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Reset,411666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almLow.Suppressed,411666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almLow.Shelved,411666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almLow.Disabled,411666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almLow.Acked,411666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almLow.Alarm,411666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Fault,411676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almLowLow.AlarmState,411676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almLowLow.GlobalReset,411676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almLowLow.FaultInAlarm,411676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almLowLow.ALRM,411676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almLowLow.ANUN,411676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almLowLow.AKED,411676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almLowLow.Resetable,411676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almLowLow.REST,411676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almLowLow.ACKN,411676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almLowLow.UACK,411676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almLowLow.MCmd_Enable,411676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almLowLow.MCmd_Disable,411676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almLowLow.OCmd_Shelve,411676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almLowLow.OCmd_Unshelve,411676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almLowLow.SCmd_Suppress,411676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almLowLow.SCmd_UnSuppress,411677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almLowLow.AEShelveTMRDN,411677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almLowLow.Bad,411677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almLowLow.Suppress,411678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.UnSuppress,411678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Shelve,411678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.UnShelve,411678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Enable,411678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Disable,411678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Ack,411678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Reset,411678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Suppressed,411678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Shelved,411678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Disabled,411678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Acked,411678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almLowLow.Alarm,411678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Fault,411688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almBrokenLoop.AlarmState,411688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almBrokenLoop.GlobalReset,411688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almBrokenLoop.FaultInAlarm,411688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almBrokenLoop.ALRM,411688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almBrokenLoop.ANUN,411688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almBrokenLoop.AKED,411688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almBrokenLoop.Resetable,411688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almBrokenLoop.REST,411688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almBrokenLoop.ACKN,411688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almBrokenLoop.UACK,411688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almBrokenLoop.MCmd_Enable,411688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.MCmd_Disable,411688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.OCmd_Shelve,411688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.OCmd_Unshelve,411688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.SCmd_Suppress,411688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.SCmd_UnSuppress,411689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almBrokenLoop.AEShelveTMRDN,411689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almBrokenLoop.Bad,411689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almBrokenLoop.Suppress,411690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.UnSuppress,411690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Shelve,411690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.UnShelve,411690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Enable,411690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Disable,411690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Ack,411690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Reset,411690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Suppressed,411690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Shelved,411690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Disabled,411690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Acked,411690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.Alarm,411690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Fault,411700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almOverRange.AlarmState,411700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almOverRange.GlobalReset,411700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almOverRange.FaultInAlarm,411700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almOverRange.ALRM,411700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almOverRange.ANUN,411700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almOverRange.AKED,411700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almOverRange.Resetable,411700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almOverRange.REST,411700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almOverRange.ACKN,411700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almOverRange.UACK,411700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almOverRange.MCmd_Enable,411700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almOverRange.MCmd_Disable,411700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almOverRange.OCmd_Shelve,411700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almOverRange.OCmd_Unshelve,411700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almOverRange.SCmd_Suppress,411700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almOverRange.SCmd_UnSuppress,411701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almOverRange.AEShelveTMRDN,411701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almOverRange.Bad,411701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almOverRange.Suppress,411702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.UnSuppress,411702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Shelve,411702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.UnShelve,411702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Enable,411702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Disable,411702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Ack,411702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Reset,411702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Suppressed,411702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Shelved,411702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Disabled,411702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Acked,411702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almOverRange.Alarm,411702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Fault,411712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almUnderRange.AlarmState,411712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almUnderRange.GlobalReset,411712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almUnderRange.FaultInAlarm,411712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almUnderRange.ALRM,411712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almUnderRange.ANUN,411712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almUnderRange.AKED,411712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almUnderRange.Resetable,411712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almUnderRange.REST,411712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almUnderRange.ACKN,411712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almUnderRange.UACK,411712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almUnderRange.MCmd_Enable,411712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.MCmd_Disable,411712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.OCmd_Shelve,411712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.OCmd_Unshelve,411712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.SCmd_Suppress,411712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.SCmd_UnSuppress,411713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almUnderRange.AEShelveTMRDN,411713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almUnderRange.Bad,411713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almUnderRange.Suppress,411714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.UnSuppress,411714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Shelve,411714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.UnShelve,411714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Enable,411714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Disable,411714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Ack,411714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Reset,411714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Suppressed,411714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Shelved,411714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Disabled,411714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Acked,411714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almUnderRange.Alarm,411714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Fault,411724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almRateOfChange.AlarmState,411724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almRateOfChange.GlobalReset,411724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almRateOfChange.FaultInAlarm,411724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almRateOfChange.ALRM,411724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almRateOfChange.ANUN,411724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almRateOfChange.AKED,411724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almRateOfChange.Resetable,411724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almRateOfChange.REST,411724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almRateOfChange.ACKN,411724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almRateOfChange.UACK,411724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almRateOfChange.MCmd_Enable,411724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.MCmd_Disable,411724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.OCmd_Shelve,411724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.OCmd_Unshelve,411724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.SCmd_Suppress,411724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.SCmd_UnSuppress,411725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almRateOfChange.AEShelveTMRDN,411725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almRateOfChange.Bad,411725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almRateOfChange.Suppress,411726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.UnSuppress,411726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Shelve,411726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.UnShelve,411726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Enable,411726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Disable,411726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Ack,411726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Reset,411726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Suppressed,411726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Shelved,411726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Disabled,411726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Acked,411726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almRateOfChange.Alarm,411726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Fault,411736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_6_VI4.almPLCFault.AlarmState,411736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_6_VI4.almPLCFault.GlobalReset,411736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_6_VI4.almPLCFault.FaultInAlarm,411736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_6_VI4.almPLCFault.ALRM,411736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_6_VI4.almPLCFault.ANUN,411736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_6_VI4.almPLCFault.AKED,411736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_6_VI4.almPLCFault.Resetable,411736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_6_VI4.almPLCFault.REST,411736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_6_VI4.almPLCFault.ACKN,411736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_6_VI4.almPLCFault.UACK,411736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_6_VI4.almPLCFault.MCmd_Enable,411736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.MCmd_Disable,411736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.OCmd_Shelve,411736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.OCmd_Unshelve,411736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.SCmd_Suppress,411736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.SCmd_UnSuppress,411737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_6_VI4.almPLCFault.AEShelveTMRDN,411737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_6_VI4.almPLCFault.Bad,411737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_6_VI4.almPLCFault.Suppress,411738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.UnSuppress,411738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Shelve,411738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.UnShelve,411738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Enable,411738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Disable,411738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Ack,411738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Reset,411738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Suppressed,411738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Shelved,411738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Disabled,411738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Acked,411738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_6_VI4.almPLCFault.Alarm,411738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Fault,411840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almHighHigh.AlarmState,411840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almHighHigh.GlobalReset,411840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almHighHigh.FaultInAlarm,411840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almHighHigh.ALRM,411840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almHighHigh.ANUN,411840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almHighHigh.AKED,411840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almHighHigh.Resetable,411840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almHighHigh.REST,411840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almHighHigh.ACKN,411840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almHighHigh.UACK,411840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almHighHigh.MCmd_Enable,411840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.MCmd_Disable,411840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.OCmd_Shelve,411840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.OCmd_Unshelve,411840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.SCmd_Suppress,411840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.SCmd_UnSuppress,411841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almHighHigh.AEShelveTMRDN,411841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almHighHigh.Bad,411841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almHighHigh.Suppress,411842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.UnSuppress,411842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Shelve,411842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.UnShelve,411842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Enable,411842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Disable,411842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Ack,411842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Reset,411842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Suppressed,411842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Shelved,411842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Disabled,411842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Acked,411842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almHighHigh.Alarm,411842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Fault,411852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almHigh.AlarmState,411852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almHigh.GlobalReset,411852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almHigh.FaultInAlarm,411852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almHigh.ALRM,411852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almHigh.ANUN,411852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almHigh.AKED,411852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almHigh.Resetable,411852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almHigh.REST,411852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almHigh.ACKN,411852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almHigh.UACK,411852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almHigh.MCmd_Enable,411852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almHigh.MCmd_Disable,411852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almHigh.OCmd_Shelve,411852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almHigh.OCmd_Unshelve,411852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almHigh.SCmd_Suppress,411852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almHigh.SCmd_UnSuppress,411853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almHigh.AEShelveTMRDN,411853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almHigh.Bad,411853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almHigh.Suppress,411854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.UnSuppress,411854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Shelve,411854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.UnShelve,411854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Enable,411854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Disable,411854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Ack,411854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Reset,411854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almHigh.Suppressed,411854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almHigh.Shelved,411854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almHigh.Disabled,411854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almHigh.Acked,411854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almHigh.Alarm,411854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Fault,411864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almLow.AlarmState,411864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almLow.GlobalReset,411864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almLow.FaultInAlarm,411864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almLow.ALRM,411864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almLow.ANUN,411864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almLow.AKED,411864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almLow.Resetable,411864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almLow.REST,411864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almLow.ACKN,411864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almLow.UACK,411864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almLow.MCmd_Enable,411864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almLow.MCmd_Disable,411864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almLow.OCmd_Shelve,411864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almLow.OCmd_Unshelve,411864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almLow.SCmd_Suppress,411864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almLow.SCmd_UnSuppress,411865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almLow.AEShelveTMRDN,411865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almLow.Bad,411865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almLow.Suppress,411866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.UnSuppress,411866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Shelve,411866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.UnShelve,411866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Enable,411866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Disable,411866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Ack,411866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Reset,411866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almLow.Suppressed,411866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almLow.Shelved,411866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almLow.Disabled,411866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almLow.Acked,411866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almLow.Alarm,411866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Fault,411876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almLowLow.AlarmState,411876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almLowLow.GlobalReset,411876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almLowLow.FaultInAlarm,411876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almLowLow.ALRM,411876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almLowLow.ANUN,411876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almLowLow.AKED,411876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almLowLow.Resetable,411876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almLowLow.REST,411876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almLowLow.ACKN,411876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almLowLow.UACK,411876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almLowLow.MCmd_Enable,411876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almLowLow.MCmd_Disable,411876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almLowLow.OCmd_Shelve,411876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almLowLow.OCmd_Unshelve,411876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almLowLow.SCmd_Suppress,411876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almLowLow.SCmd_UnSuppress,411877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almLowLow.AEShelveTMRDN,411877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almLowLow.Bad,411877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almLowLow.Suppress,411878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.UnSuppress,411878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Shelve,411878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.UnShelve,411878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Enable,411878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Disable,411878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Ack,411878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Reset,411878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Suppressed,411878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Shelved,411878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Disabled,411878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Acked,411878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almLowLow.Alarm,411878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Fault,411888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almBrokenLoop.AlarmState,411888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almBrokenLoop.GlobalReset,411888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almBrokenLoop.FaultInAlarm,411888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almBrokenLoop.ALRM,411888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almBrokenLoop.ANUN,411888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almBrokenLoop.AKED,411888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almBrokenLoop.Resetable,411888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almBrokenLoop.REST,411888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almBrokenLoop.ACKN,411888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almBrokenLoop.UACK,411888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almBrokenLoop.MCmd_Enable,411888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.MCmd_Disable,411888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.OCmd_Shelve,411888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.OCmd_Unshelve,411888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.SCmd_Suppress,411888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.SCmd_UnSuppress,411889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almBrokenLoop.AEShelveTMRDN,411889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almBrokenLoop.Bad,411889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almBrokenLoop.Suppress,411890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.UnSuppress,411890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Shelve,411890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.UnShelve,411890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Enable,411890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Disable,411890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Ack,411890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Reset,411890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Suppressed,411890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Shelved,411890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Disabled,411890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Acked,411890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.Alarm,411890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Fault,411900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almOverRange.AlarmState,411900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almOverRange.GlobalReset,411900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almOverRange.FaultInAlarm,411900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almOverRange.ALRM,411900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almOverRange.ANUN,411900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almOverRange.AKED,411900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almOverRange.Resetable,411900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almOverRange.REST,411900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almOverRange.ACKN,411900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almOverRange.UACK,411900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almOverRange.MCmd_Enable,411900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almOverRange.MCmd_Disable,411900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almOverRange.OCmd_Shelve,411900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almOverRange.OCmd_Unshelve,411900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almOverRange.SCmd_Suppress,411900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almOverRange.SCmd_UnSuppress,411901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almOverRange.AEShelveTMRDN,411901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almOverRange.Bad,411901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almOverRange.Suppress,411902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.UnSuppress,411902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Shelve,411902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.UnShelve,411902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Enable,411902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Disable,411902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Ack,411902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Reset,411902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Suppressed,411902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Shelved,411902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Disabled,411902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Acked,411902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almOverRange.Alarm,411902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Fault,411912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almUnderRange.AlarmState,411912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almUnderRange.GlobalReset,411912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almUnderRange.FaultInAlarm,411912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almUnderRange.ALRM,411912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almUnderRange.ANUN,411912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almUnderRange.AKED,411912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almUnderRange.Resetable,411912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almUnderRange.REST,411912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almUnderRange.ACKN,411912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almUnderRange.UACK,411912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almUnderRange.MCmd_Enable,411912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.MCmd_Disable,411912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.OCmd_Shelve,411912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.OCmd_Unshelve,411912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.SCmd_Suppress,411912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.SCmd_UnSuppress,411913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almUnderRange.AEShelveTMRDN,411913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almUnderRange.Bad,411913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almUnderRange.Suppress,411914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.UnSuppress,411914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Shelve,411914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.UnShelve,411914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Enable,411914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Disable,411914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Ack,411914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Reset,411914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Suppressed,411914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Shelved,411914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Disabled,411914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Acked,411914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almUnderRange.Alarm,411914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Fault,411924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almRateOfChange.AlarmState,411924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almRateOfChange.GlobalReset,411924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almRateOfChange.FaultInAlarm,411924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almRateOfChange.ALRM,411924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almRateOfChange.ANUN,411924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almRateOfChange.AKED,411924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almRateOfChange.Resetable,411924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almRateOfChange.REST,411924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almRateOfChange.ACKN,411924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almRateOfChange.UACK,411924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almRateOfChange.MCmd_Enable,411924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.MCmd_Disable,411924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.OCmd_Shelve,411924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.OCmd_Unshelve,411924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.SCmd_Suppress,411924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.SCmd_UnSuppress,411925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almRateOfChange.AEShelveTMRDN,411925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almRateOfChange.Bad,411925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almRateOfChange.Suppress,411926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.UnSuppress,411926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Shelve,411926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.UnShelve,411926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Enable,411926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Disable,411926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Ack,411926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Reset,411926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Suppressed,411926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Shelved,411926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Disabled,411926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Acked,411926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almRateOfChange.Alarm,411926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Fault,411936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI1.almPLCFault.AlarmState,411936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI1.almPLCFault.GlobalReset,411936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI1.almPLCFault.FaultInAlarm,411936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI1.almPLCFault.ALRM,411936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI1.almPLCFault.ANUN,411936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI1.almPLCFault.AKED,411936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI1.almPLCFault.Resetable,411936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI1.almPLCFault.REST,411936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI1.almPLCFault.ACKN,411936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI1.almPLCFault.UACK,411936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI1.almPLCFault.MCmd_Enable,411936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.MCmd_Disable,411936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.OCmd_Shelve,411936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.OCmd_Unshelve,411936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.SCmd_Suppress,411936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.SCmd_UnSuppress,411937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI1.almPLCFault.AEShelveTMRDN,411937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI1.almPLCFault.Bad,411937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI1.almPLCFault.Suppress,411938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.UnSuppress,411938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Shelve,411938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.UnShelve,411938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Enable,411938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Disable,411938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Ack,411938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Reset,411938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Suppressed,411938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Shelved,411938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Disabled,411938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Acked,411938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI1.almPLCFault.Alarm,411938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Fault,412040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almHighHigh.AlarmState,412040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almHighHigh.GlobalReset,412040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almHighHigh.FaultInAlarm,412040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almHighHigh.ALRM,412040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almHighHigh.ANUN,412040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almHighHigh.AKED,412040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almHighHigh.Resetable,412040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almHighHigh.REST,412040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almHighHigh.ACKN,412040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almHighHigh.UACK,412040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almHighHigh.MCmd_Enable,412040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.MCmd_Disable,412040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.OCmd_Shelve,412040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.OCmd_Unshelve,412040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.SCmd_Suppress,412040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.SCmd_UnSuppress,412041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almHighHigh.AEShelveTMRDN,412041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almHighHigh.Bad,412041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almHighHigh.Suppress,412042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.UnSuppress,412042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Shelve,412042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.UnShelve,412042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Enable,412042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Disable,412042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Ack,412042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Reset,412042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Suppressed,412042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Shelved,412042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Disabled,412042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Acked,412042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almHighHigh.Alarm,412042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Fault,412052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almHigh.AlarmState,412052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almHigh.GlobalReset,412052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almHigh.FaultInAlarm,412052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almHigh.ALRM,412052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almHigh.ANUN,412052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almHigh.AKED,412052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almHigh.Resetable,412052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almHigh.REST,412052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almHigh.ACKN,412052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almHigh.UACK,412052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almHigh.MCmd_Enable,412052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almHigh.MCmd_Disable,412052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almHigh.OCmd_Shelve,412052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almHigh.OCmd_Unshelve,412052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almHigh.SCmd_Suppress,412052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almHigh.SCmd_UnSuppress,412053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almHigh.AEShelveTMRDN,412053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almHigh.Bad,412053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almHigh.Suppress,412054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.UnSuppress,412054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Shelve,412054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.UnShelve,412054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Enable,412054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Disable,412054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Ack,412054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Reset,412054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almHigh.Suppressed,412054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almHigh.Shelved,412054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almHigh.Disabled,412054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almHigh.Acked,412054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almHigh.Alarm,412054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Fault,412064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almLow.AlarmState,412064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almLow.GlobalReset,412064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almLow.FaultInAlarm,412064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almLow.ALRM,412064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almLow.ANUN,412064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almLow.AKED,412064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almLow.Resetable,412064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almLow.REST,412064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almLow.ACKN,412064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almLow.UACK,412064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almLow.MCmd_Enable,412064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almLow.MCmd_Disable,412064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almLow.OCmd_Shelve,412064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almLow.OCmd_Unshelve,412064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almLow.SCmd_Suppress,412064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almLow.SCmd_UnSuppress,412065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almLow.AEShelveTMRDN,412065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almLow.Bad,412065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almLow.Suppress,412066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.UnSuppress,412066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Shelve,412066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.UnShelve,412066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Enable,412066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Disable,412066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Ack,412066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Reset,412066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almLow.Suppressed,412066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almLow.Shelved,412066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almLow.Disabled,412066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almLow.Acked,412066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almLow.Alarm,412066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Fault,412076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almLowLow.AlarmState,412076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almLowLow.GlobalReset,412076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almLowLow.FaultInAlarm,412076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almLowLow.ALRM,412076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almLowLow.ANUN,412076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almLowLow.AKED,412076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almLowLow.Resetable,412076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almLowLow.REST,412076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almLowLow.ACKN,412076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almLowLow.UACK,412076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almLowLow.MCmd_Enable,412076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almLowLow.MCmd_Disable,412076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almLowLow.OCmd_Shelve,412076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almLowLow.OCmd_Unshelve,412076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almLowLow.SCmd_Suppress,412076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almLowLow.SCmd_UnSuppress,412077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almLowLow.AEShelveTMRDN,412077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almLowLow.Bad,412077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almLowLow.Suppress,412078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.UnSuppress,412078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Shelve,412078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.UnShelve,412078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Enable,412078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Disable,412078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Ack,412078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Reset,412078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Suppressed,412078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Shelved,412078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Disabled,412078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Acked,412078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almLowLow.Alarm,412078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Fault,412088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almBrokenLoop.AlarmState,412088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almBrokenLoop.GlobalReset,412088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almBrokenLoop.FaultInAlarm,412088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almBrokenLoop.ALRM,412088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almBrokenLoop.ANUN,412088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almBrokenLoop.AKED,412088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almBrokenLoop.Resetable,412088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almBrokenLoop.REST,412088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almBrokenLoop.ACKN,412088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almBrokenLoop.UACK,412088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almBrokenLoop.MCmd_Enable,412088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.MCmd_Disable,412088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.OCmd_Shelve,412088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.OCmd_Unshelve,412088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.SCmd_Suppress,412088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.SCmd_UnSuppress,412089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almBrokenLoop.AEShelveTMRDN,412089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almBrokenLoop.Bad,412089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almBrokenLoop.Suppress,412090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.UnSuppress,412090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Shelve,412090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.UnShelve,412090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Enable,412090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Disable,412090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Ack,412090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Reset,412090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Suppressed,412090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Shelved,412090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Disabled,412090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Acked,412090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.Alarm,412090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Fault,412100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almOverRange.AlarmState,412100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almOverRange.GlobalReset,412100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almOverRange.FaultInAlarm,412100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almOverRange.ALRM,412100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almOverRange.ANUN,412100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almOverRange.AKED,412100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almOverRange.Resetable,412100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almOverRange.REST,412100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almOverRange.ACKN,412100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almOverRange.UACK,412100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almOverRange.MCmd_Enable,412100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almOverRange.MCmd_Disable,412100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almOverRange.OCmd_Shelve,412100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almOverRange.OCmd_Unshelve,412100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almOverRange.SCmd_Suppress,412100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almOverRange.SCmd_UnSuppress,412101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almOverRange.AEShelveTMRDN,412101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almOverRange.Bad,412101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almOverRange.Suppress,412102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.UnSuppress,412102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Shelve,412102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.UnShelve,412102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Enable,412102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Disable,412102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Ack,412102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Reset,412102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Suppressed,412102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Shelved,412102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Disabled,412102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Acked,412102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almOverRange.Alarm,412102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Fault,412112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almUnderRange.AlarmState,412112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almUnderRange.GlobalReset,412112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almUnderRange.FaultInAlarm,412112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almUnderRange.ALRM,412112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almUnderRange.ANUN,412112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almUnderRange.AKED,412112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almUnderRange.Resetable,412112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almUnderRange.REST,412112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almUnderRange.ACKN,412112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almUnderRange.UACK,412112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almUnderRange.MCmd_Enable,412112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.MCmd_Disable,412112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.OCmd_Shelve,412112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.OCmd_Unshelve,412112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.SCmd_Suppress,412112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.SCmd_UnSuppress,412113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almUnderRange.AEShelveTMRDN,412113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almUnderRange.Bad,412113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almUnderRange.Suppress,412114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.UnSuppress,412114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Shelve,412114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.UnShelve,412114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Enable,412114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Disable,412114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Ack,412114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Reset,412114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Suppressed,412114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Shelved,412114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Disabled,412114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Acked,412114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almUnderRange.Alarm,412114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Fault,412124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almRateOfChange.AlarmState,412124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almRateOfChange.GlobalReset,412124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almRateOfChange.FaultInAlarm,412124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almRateOfChange.ALRM,412124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almRateOfChange.ANUN,412124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almRateOfChange.AKED,412124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almRateOfChange.Resetable,412124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almRateOfChange.REST,412124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almRateOfChange.ACKN,412124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almRateOfChange.UACK,412124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almRateOfChange.MCmd_Enable,412124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.MCmd_Disable,412124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.OCmd_Shelve,412124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.OCmd_Unshelve,412124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.SCmd_Suppress,412124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.SCmd_UnSuppress,412125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almRateOfChange.AEShelveTMRDN,412125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almRateOfChange.Bad,412125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almRateOfChange.Suppress,412126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.UnSuppress,412126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Shelve,412126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.UnShelve,412126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Enable,412126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Disable,412126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Ack,412126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Reset,412126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Suppressed,412126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Shelved,412126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Disabled,412126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Acked,412126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almRateOfChange.Alarm,412126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Fault,412136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI2.almPLCFault.AlarmState,412136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI2.almPLCFault.GlobalReset,412136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI2.almPLCFault.FaultInAlarm,412136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI2.almPLCFault.ALRM,412136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI2.almPLCFault.ANUN,412136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI2.almPLCFault.AKED,412136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI2.almPLCFault.Resetable,412136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI2.almPLCFault.REST,412136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI2.almPLCFault.ACKN,412136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI2.almPLCFault.UACK,412136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI2.almPLCFault.MCmd_Enable,412136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.MCmd_Disable,412136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.OCmd_Shelve,412136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.OCmd_Unshelve,412136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.SCmd_Suppress,412136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.SCmd_UnSuppress,412137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI2.almPLCFault.AEShelveTMRDN,412137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI2.almPLCFault.Bad,412137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI2.almPLCFault.Suppress,412138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.UnSuppress,412138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Shelve,412138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.UnShelve,412138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Enable,412138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Disable,412138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Ack,412138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Reset,412138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Suppressed,412138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Shelved,412138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Disabled,412138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Acked,412138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI2.almPLCFault.Alarm,412138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Fault,412240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almHighHigh.AlarmState,412240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almHighHigh.GlobalReset,412240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almHighHigh.FaultInAlarm,412240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almHighHigh.ALRM,412240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almHighHigh.ANUN,412240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almHighHigh.AKED,412240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almHighHigh.Resetable,412240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almHighHigh.REST,412240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almHighHigh.ACKN,412240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almHighHigh.UACK,412240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almHighHigh.MCmd_Enable,412240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.MCmd_Disable,412240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.OCmd_Shelve,412240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.OCmd_Unshelve,412240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.SCmd_Suppress,412240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.SCmd_UnSuppress,412241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almHighHigh.AEShelveTMRDN,412241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almHighHigh.Bad,412241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almHighHigh.Suppress,412242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.UnSuppress,412242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Shelve,412242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.UnShelve,412242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Enable,412242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Disable,412242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Ack,412242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Reset,412242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Suppressed,412242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Shelved,412242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Disabled,412242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Acked,412242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almHighHigh.Alarm,412242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Fault,412252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almHigh.AlarmState,412252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almHigh.GlobalReset,412252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almHigh.FaultInAlarm,412252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almHigh.ALRM,412252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almHigh.ANUN,412252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almHigh.AKED,412252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almHigh.Resetable,412252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almHigh.REST,412252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almHigh.ACKN,412252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almHigh.UACK,412252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almHigh.MCmd_Enable,412252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almHigh.MCmd_Disable,412252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almHigh.OCmd_Shelve,412252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almHigh.OCmd_Unshelve,412252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almHigh.SCmd_Suppress,412252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almHigh.SCmd_UnSuppress,412253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almHigh.AEShelveTMRDN,412253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almHigh.Bad,412253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almHigh.Suppress,412254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.UnSuppress,412254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Shelve,412254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.UnShelve,412254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Enable,412254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Disable,412254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Ack,412254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Reset,412254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almHigh.Suppressed,412254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almHigh.Shelved,412254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almHigh.Disabled,412254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almHigh.Acked,412254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almHigh.Alarm,412254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Fault,412264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almLow.AlarmState,412264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almLow.GlobalReset,412264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almLow.FaultInAlarm,412264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almLow.ALRM,412264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almLow.ANUN,412264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almLow.AKED,412264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almLow.Resetable,412264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almLow.REST,412264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almLow.ACKN,412264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almLow.UACK,412264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almLow.MCmd_Enable,412264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almLow.MCmd_Disable,412264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almLow.OCmd_Shelve,412264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almLow.OCmd_Unshelve,412264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almLow.SCmd_Suppress,412264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almLow.SCmd_UnSuppress,412265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almLow.AEShelveTMRDN,412265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almLow.Bad,412265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almLow.Suppress,412266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.UnSuppress,412266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Shelve,412266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.UnShelve,412266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Enable,412266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Disable,412266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Ack,412266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Reset,412266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almLow.Suppressed,412266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almLow.Shelved,412266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almLow.Disabled,412266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almLow.Acked,412266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almLow.Alarm,412266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Fault,412276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almLowLow.AlarmState,412276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almLowLow.GlobalReset,412276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almLowLow.FaultInAlarm,412276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almLowLow.ALRM,412276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almLowLow.ANUN,412276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almLowLow.AKED,412276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almLowLow.Resetable,412276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almLowLow.REST,412276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almLowLow.ACKN,412276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almLowLow.UACK,412276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almLowLow.MCmd_Enable,412276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almLowLow.MCmd_Disable,412276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almLowLow.OCmd_Shelve,412276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almLowLow.OCmd_Unshelve,412276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almLowLow.SCmd_Suppress,412276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almLowLow.SCmd_UnSuppress,412277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almLowLow.AEShelveTMRDN,412277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almLowLow.Bad,412277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almLowLow.Suppress,412278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.UnSuppress,412278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Shelve,412278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.UnShelve,412278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Enable,412278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Disable,412278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Ack,412278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Reset,412278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Suppressed,412278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Shelved,412278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Disabled,412278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Acked,412278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almLowLow.Alarm,412278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Fault,412288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almBrokenLoop.AlarmState,412288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almBrokenLoop.GlobalReset,412288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almBrokenLoop.FaultInAlarm,412288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almBrokenLoop.ALRM,412288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almBrokenLoop.ANUN,412288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almBrokenLoop.AKED,412288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almBrokenLoop.Resetable,412288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almBrokenLoop.REST,412288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almBrokenLoop.ACKN,412288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almBrokenLoop.UACK,412288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almBrokenLoop.MCmd_Enable,412288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.MCmd_Disable,412288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.OCmd_Shelve,412288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.OCmd_Unshelve,412288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.SCmd_Suppress,412288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.SCmd_UnSuppress,412289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almBrokenLoop.AEShelveTMRDN,412289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almBrokenLoop.Bad,412289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almBrokenLoop.Suppress,412290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.UnSuppress,412290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Shelve,412290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.UnShelve,412290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Enable,412290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Disable,412290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Ack,412290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Reset,412290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Suppressed,412290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Shelved,412290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Disabled,412290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Acked,412290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.Alarm,412290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Fault,412300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almOverRange.AlarmState,412300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almOverRange.GlobalReset,412300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almOverRange.FaultInAlarm,412300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almOverRange.ALRM,412300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almOverRange.ANUN,412300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almOverRange.AKED,412300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almOverRange.Resetable,412300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almOverRange.REST,412300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almOverRange.ACKN,412300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almOverRange.UACK,412300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almOverRange.MCmd_Enable,412300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almOverRange.MCmd_Disable,412300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almOverRange.OCmd_Shelve,412300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almOverRange.OCmd_Unshelve,412300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almOverRange.SCmd_Suppress,412300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almOverRange.SCmd_UnSuppress,412301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almOverRange.AEShelveTMRDN,412301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almOverRange.Bad,412301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almOverRange.Suppress,412302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.UnSuppress,412302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Shelve,412302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.UnShelve,412302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Enable,412302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Disable,412302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Ack,412302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Reset,412302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Suppressed,412302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Shelved,412302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Disabled,412302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Acked,412302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almOverRange.Alarm,412302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Fault,412312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almUnderRange.AlarmState,412312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almUnderRange.GlobalReset,412312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almUnderRange.FaultInAlarm,412312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almUnderRange.ALRM,412312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almUnderRange.ANUN,412312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almUnderRange.AKED,412312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almUnderRange.Resetable,412312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almUnderRange.REST,412312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almUnderRange.ACKN,412312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almUnderRange.UACK,412312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almUnderRange.MCmd_Enable,412312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.MCmd_Disable,412312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.OCmd_Shelve,412312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.OCmd_Unshelve,412312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.SCmd_Suppress,412312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.SCmd_UnSuppress,412313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almUnderRange.AEShelveTMRDN,412313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almUnderRange.Bad,412313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almUnderRange.Suppress,412314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.UnSuppress,412314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Shelve,412314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.UnShelve,412314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Enable,412314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Disable,412314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Ack,412314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Reset,412314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Suppressed,412314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Shelved,412314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Disabled,412314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Acked,412314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almUnderRange.Alarm,412314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Fault,412324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almRateOfChange.AlarmState,412324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almRateOfChange.GlobalReset,412324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almRateOfChange.FaultInAlarm,412324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almRateOfChange.ALRM,412324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almRateOfChange.ANUN,412324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almRateOfChange.AKED,412324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almRateOfChange.Resetable,412324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almRateOfChange.REST,412324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almRateOfChange.ACKN,412324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almRateOfChange.UACK,412324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almRateOfChange.MCmd_Enable,412324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.MCmd_Disable,412324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.OCmd_Shelve,412324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.OCmd_Unshelve,412324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.SCmd_Suppress,412324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.SCmd_UnSuppress,412325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almRateOfChange.AEShelveTMRDN,412325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almRateOfChange.Bad,412325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almRateOfChange.Suppress,412326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.UnSuppress,412326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Shelve,412326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.UnShelve,412326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Enable,412326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Disable,412326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Ack,412326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Reset,412326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Suppressed,412326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Shelved,412326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Disabled,412326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Acked,412326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almRateOfChange.Alarm,412326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Fault,412336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI3.almPLCFault.AlarmState,412336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI3.almPLCFault.GlobalReset,412336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI3.almPLCFault.FaultInAlarm,412336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI3.almPLCFault.ALRM,412336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI3.almPLCFault.ANUN,412336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI3.almPLCFault.AKED,412336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI3.almPLCFault.Resetable,412336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI3.almPLCFault.REST,412336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI3.almPLCFault.ACKN,412336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI3.almPLCFault.UACK,412336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI3.almPLCFault.MCmd_Enable,412336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.MCmd_Disable,412336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.OCmd_Shelve,412336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.OCmd_Unshelve,412336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.SCmd_Suppress,412336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.SCmd_UnSuppress,412337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI3.almPLCFault.AEShelveTMRDN,412337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI3.almPLCFault.Bad,412337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI3.almPLCFault.Suppress,412338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.UnSuppress,412338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Shelve,412338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.UnShelve,412338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Enable,412338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Disable,412338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Ack,412338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Reset,412338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Suppressed,412338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Shelved,412338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Disabled,412338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Acked,412338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI3.almPLCFault.Alarm,412338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Fault,412440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almHighHigh.AlarmState,412440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almHighHigh.GlobalReset,412440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almHighHigh.FaultInAlarm,412440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almHighHigh.ALRM,412440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almHighHigh.ANUN,412440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almHighHigh.AKED,412440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almHighHigh.Resetable,412440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almHighHigh.REST,412440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almHighHigh.ACKN,412440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almHighHigh.UACK,412440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almHighHigh.MCmd_Enable,412440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.MCmd_Disable,412440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.OCmd_Shelve,412440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.OCmd_Unshelve,412440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.SCmd_Suppress,412440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.SCmd_UnSuppress,412441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almHighHigh.AEShelveTMRDN,412441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almHighHigh.Bad,412441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almHighHigh.Suppress,412442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.UnSuppress,412442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Shelve,412442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.UnShelve,412442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Enable,412442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Disable,412442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Ack,412442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Reset,412442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Suppressed,412442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Shelved,412442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Disabled,412442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Acked,412442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almHighHigh.Alarm,412442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Fault,412452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almHigh.AlarmState,412452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almHigh.GlobalReset,412452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almHigh.FaultInAlarm,412452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almHigh.ALRM,412452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almHigh.ANUN,412452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almHigh.AKED,412452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almHigh.Resetable,412452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almHigh.REST,412452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almHigh.ACKN,412452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almHigh.UACK,412452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almHigh.MCmd_Enable,412452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almHigh.MCmd_Disable,412452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almHigh.OCmd_Shelve,412452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almHigh.OCmd_Unshelve,412452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almHigh.SCmd_Suppress,412452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almHigh.SCmd_UnSuppress,412453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almHigh.AEShelveTMRDN,412453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almHigh.Bad,412453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almHigh.Suppress,412454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.UnSuppress,412454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Shelve,412454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.UnShelve,412454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Enable,412454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Disable,412454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Ack,412454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Reset,412454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almHigh.Suppressed,412454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almHigh.Shelved,412454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almHigh.Disabled,412454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almHigh.Acked,412454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almHigh.Alarm,412454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Fault,412464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almLow.AlarmState,412464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almLow.GlobalReset,412464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almLow.FaultInAlarm,412464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almLow.ALRM,412464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almLow.ANUN,412464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almLow.AKED,412464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almLow.Resetable,412464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almLow.REST,412464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almLow.ACKN,412464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almLow.UACK,412464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almLow.MCmd_Enable,412464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almLow.MCmd_Disable,412464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almLow.OCmd_Shelve,412464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almLow.OCmd_Unshelve,412464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almLow.SCmd_Suppress,412464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almLow.SCmd_UnSuppress,412465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almLow.AEShelveTMRDN,412465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almLow.Bad,412465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almLow.Suppress,412466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.UnSuppress,412466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Shelve,412466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.UnShelve,412466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Enable,412466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Disable,412466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Ack,412466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Reset,412466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almLow.Suppressed,412466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almLow.Shelved,412466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almLow.Disabled,412466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almLow.Acked,412466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almLow.Alarm,412466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Fault,412476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almLowLow.AlarmState,412476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almLowLow.GlobalReset,412476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almLowLow.FaultInAlarm,412476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almLowLow.ALRM,412476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almLowLow.ANUN,412476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almLowLow.AKED,412476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almLowLow.Resetable,412476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almLowLow.REST,412476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almLowLow.ACKN,412476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almLowLow.UACK,412476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almLowLow.MCmd_Enable,412476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almLowLow.MCmd_Disable,412476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almLowLow.OCmd_Shelve,412476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almLowLow.OCmd_Unshelve,412476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almLowLow.SCmd_Suppress,412476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almLowLow.SCmd_UnSuppress,412477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almLowLow.AEShelveTMRDN,412477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almLowLow.Bad,412477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almLowLow.Suppress,412478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.UnSuppress,412478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Shelve,412478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.UnShelve,412478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Enable,412478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Disable,412478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Ack,412478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Reset,412478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Suppressed,412478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Shelved,412478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Disabled,412478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Acked,412478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almLowLow.Alarm,412478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Fault,412488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almBrokenLoop.AlarmState,412488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almBrokenLoop.GlobalReset,412488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almBrokenLoop.FaultInAlarm,412488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almBrokenLoop.ALRM,412488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almBrokenLoop.ANUN,412488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almBrokenLoop.AKED,412488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almBrokenLoop.Resetable,412488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almBrokenLoop.REST,412488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almBrokenLoop.ACKN,412488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almBrokenLoop.UACK,412488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almBrokenLoop.MCmd_Enable,412488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.MCmd_Disable,412488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.OCmd_Shelve,412488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.OCmd_Unshelve,412488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.SCmd_Suppress,412488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.SCmd_UnSuppress,412489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almBrokenLoop.AEShelveTMRDN,412489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almBrokenLoop.Bad,412489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almBrokenLoop.Suppress,412490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.UnSuppress,412490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Shelve,412490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.UnShelve,412490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Enable,412490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Disable,412490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Ack,412490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Reset,412490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Suppressed,412490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Shelved,412490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Disabled,412490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Acked,412490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.Alarm,412490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Fault,412500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almOverRange.AlarmState,412500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almOverRange.GlobalReset,412500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almOverRange.FaultInAlarm,412500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almOverRange.ALRM,412500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almOverRange.ANUN,412500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almOverRange.AKED,412500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almOverRange.Resetable,412500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almOverRange.REST,412500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almOverRange.ACKN,412500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almOverRange.UACK,412500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almOverRange.MCmd_Enable,412500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almOverRange.MCmd_Disable,412500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almOverRange.OCmd_Shelve,412500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almOverRange.OCmd_Unshelve,412500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almOverRange.SCmd_Suppress,412500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almOverRange.SCmd_UnSuppress,412501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almOverRange.AEShelveTMRDN,412501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almOverRange.Bad,412501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almOverRange.Suppress,412502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.UnSuppress,412502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Shelve,412502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.UnShelve,412502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Enable,412502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Disable,412502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Ack,412502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Reset,412502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Suppressed,412502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Shelved,412502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Disabled,412502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Acked,412502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almOverRange.Alarm,412502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Fault,412512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almUnderRange.AlarmState,412512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almUnderRange.GlobalReset,412512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almUnderRange.FaultInAlarm,412512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almUnderRange.ALRM,412512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almUnderRange.ANUN,412512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almUnderRange.AKED,412512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almUnderRange.Resetable,412512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almUnderRange.REST,412512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almUnderRange.ACKN,412512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almUnderRange.UACK,412512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almUnderRange.MCmd_Enable,412512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.MCmd_Disable,412512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.OCmd_Shelve,412512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.OCmd_Unshelve,412512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.SCmd_Suppress,412512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.SCmd_UnSuppress,412513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almUnderRange.AEShelveTMRDN,412513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almUnderRange.Bad,412513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almUnderRange.Suppress,412514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.UnSuppress,412514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Shelve,412514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.UnShelve,412514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Enable,412514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Disable,412514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Ack,412514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Reset,412514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Suppressed,412514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Shelved,412514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Disabled,412514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Acked,412514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almUnderRange.Alarm,412514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Fault,412524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almRateOfChange.AlarmState,412524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almRateOfChange.GlobalReset,412524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almRateOfChange.FaultInAlarm,412524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almRateOfChange.ALRM,412524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almRateOfChange.ANUN,412524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almRateOfChange.AKED,412524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almRateOfChange.Resetable,412524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almRateOfChange.REST,412524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almRateOfChange.ACKN,412524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almRateOfChange.UACK,412524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almRateOfChange.MCmd_Enable,412524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.MCmd_Disable,412524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.OCmd_Shelve,412524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.OCmd_Unshelve,412524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.SCmd_Suppress,412524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.SCmd_UnSuppress,412525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almRateOfChange.AEShelveTMRDN,412525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almRateOfChange.Bad,412525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almRateOfChange.Suppress,412526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.UnSuppress,412526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Shelve,412526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.UnShelve,412526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Enable,412526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Disable,412526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Ack,412526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Reset,412526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Suppressed,412526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Shelved,412526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Disabled,412526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Acked,412526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almRateOfChange.Alarm,412526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Fault,412536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_7_VI4.almPLCFault.AlarmState,412536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_7_VI4.almPLCFault.GlobalReset,412536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_7_VI4.almPLCFault.FaultInAlarm,412536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_7_VI4.almPLCFault.ALRM,412536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_7_VI4.almPLCFault.ANUN,412536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_7_VI4.almPLCFault.AKED,412536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_7_VI4.almPLCFault.Resetable,412536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_7_VI4.almPLCFault.REST,412536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_7_VI4.almPLCFault.ACKN,412536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_7_VI4.almPLCFault.UACK,412536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_7_VI4.almPLCFault.MCmd_Enable,412536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.MCmd_Disable,412536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.OCmd_Shelve,412536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.OCmd_Unshelve,412536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.SCmd_Suppress,412536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.SCmd_UnSuppress,412537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_7_VI4.almPLCFault.AEShelveTMRDN,412537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_7_VI4.almPLCFault.Bad,412537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_7_VI4.almPLCFault.Suppress,412538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.UnSuppress,412538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Shelve,412538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.UnShelve,412538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Enable,412538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Disable,412538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Ack,412538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Reset,412538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Suppressed,412538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Shelved,412538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Disabled,412538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Acked,412538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_7_VI4.almPLCFault.Alarm,412538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Fault,412640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almHighHigh.AlarmState,412640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almHighHigh.GlobalReset,412640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almHighHigh.FaultInAlarm,412640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almHighHigh.ALRM,412640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almHighHigh.ANUN,412640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almHighHigh.AKED,412640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almHighHigh.Resetable,412640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almHighHigh.REST,412640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almHighHigh.ACKN,412640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almHighHigh.UACK,412640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almHighHigh.MCmd_Enable,412640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.MCmd_Disable,412640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.OCmd_Shelve,412640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.OCmd_Unshelve,412640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.SCmd_Suppress,412640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.SCmd_UnSuppress,412641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almHighHigh.AEShelveTMRDN,412641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almHighHigh.Bad,412641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almHighHigh.Suppress,412642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.UnSuppress,412642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Shelve,412642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.UnShelve,412642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Enable,412642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Disable,412642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Ack,412642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Reset,412642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Suppressed,412642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Shelved,412642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Disabled,412642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Acked,412642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almHighHigh.Alarm,412642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Fault,412652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almHigh.AlarmState,412652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almHigh.GlobalReset,412652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almHigh.FaultInAlarm,412652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almHigh.ALRM,412652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almHigh.ANUN,412652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almHigh.AKED,412652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almHigh.Resetable,412652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almHigh.REST,412652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almHigh.ACKN,412652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almHigh.UACK,412652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almHigh.MCmd_Enable,412652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almHigh.MCmd_Disable,412652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almHigh.OCmd_Shelve,412652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almHigh.OCmd_Unshelve,412652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almHigh.SCmd_Suppress,412652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almHigh.SCmd_UnSuppress,412653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almHigh.AEShelveTMRDN,412653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almHigh.Bad,412653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almHigh.Suppress,412654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.UnSuppress,412654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Shelve,412654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.UnShelve,412654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Enable,412654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Disable,412654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Ack,412654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Reset,412654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almHigh.Suppressed,412654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almHigh.Shelved,412654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almHigh.Disabled,412654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almHigh.Acked,412654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almHigh.Alarm,412654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Fault,412664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almLow.AlarmState,412664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almLow.GlobalReset,412664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almLow.FaultInAlarm,412664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almLow.ALRM,412664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almLow.ANUN,412664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almLow.AKED,412664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almLow.Resetable,412664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almLow.REST,412664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almLow.ACKN,412664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almLow.UACK,412664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almLow.MCmd_Enable,412664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almLow.MCmd_Disable,412664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almLow.OCmd_Shelve,412664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almLow.OCmd_Unshelve,412664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almLow.SCmd_Suppress,412664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almLow.SCmd_UnSuppress,412665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almLow.AEShelveTMRDN,412665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almLow.Bad,412665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almLow.Suppress,412666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.UnSuppress,412666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Shelve,412666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.UnShelve,412666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Enable,412666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Disable,412666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Ack,412666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Reset,412666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almLow.Suppressed,412666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almLow.Shelved,412666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almLow.Disabled,412666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almLow.Acked,412666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almLow.Alarm,412666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Fault,412676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almLowLow.AlarmState,412676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almLowLow.GlobalReset,412676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almLowLow.FaultInAlarm,412676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almLowLow.ALRM,412676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almLowLow.ANUN,412676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almLowLow.AKED,412676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almLowLow.Resetable,412676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almLowLow.REST,412676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almLowLow.ACKN,412676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almLowLow.UACK,412676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almLowLow.MCmd_Enable,412676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almLowLow.MCmd_Disable,412676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almLowLow.OCmd_Shelve,412676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almLowLow.OCmd_Unshelve,412676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almLowLow.SCmd_Suppress,412676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almLowLow.SCmd_UnSuppress,412677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almLowLow.AEShelveTMRDN,412677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almLowLow.Bad,412677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almLowLow.Suppress,412678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.UnSuppress,412678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Shelve,412678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.UnShelve,412678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Enable,412678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Disable,412678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Ack,412678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Reset,412678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Suppressed,412678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Shelved,412678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Disabled,412678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Acked,412678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almLowLow.Alarm,412678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Fault,412688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almBrokenLoop.AlarmState,412688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almBrokenLoop.GlobalReset,412688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almBrokenLoop.FaultInAlarm,412688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almBrokenLoop.ALRM,412688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almBrokenLoop.ANUN,412688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almBrokenLoop.AKED,412688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almBrokenLoop.Resetable,412688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almBrokenLoop.REST,412688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almBrokenLoop.ACKN,412688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almBrokenLoop.UACK,412688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almBrokenLoop.MCmd_Enable,412688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.MCmd_Disable,412688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.OCmd_Shelve,412688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.OCmd_Unshelve,412688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.SCmd_Suppress,412688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.SCmd_UnSuppress,412689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almBrokenLoop.AEShelveTMRDN,412689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almBrokenLoop.Bad,412689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almBrokenLoop.Suppress,412690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.UnSuppress,412690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Shelve,412690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.UnShelve,412690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Enable,412690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Disable,412690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Ack,412690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Reset,412690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Suppressed,412690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Shelved,412690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Disabled,412690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Acked,412690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.Alarm,412690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Fault,412700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almOverRange.AlarmState,412700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almOverRange.GlobalReset,412700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almOverRange.FaultInAlarm,412700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almOverRange.ALRM,412700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almOverRange.ANUN,412700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almOverRange.AKED,412700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almOverRange.Resetable,412700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almOverRange.REST,412700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almOverRange.ACKN,412700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almOverRange.UACK,412700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almOverRange.MCmd_Enable,412700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almOverRange.MCmd_Disable,412700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almOverRange.OCmd_Shelve,412700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almOverRange.OCmd_Unshelve,412700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almOverRange.SCmd_Suppress,412700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almOverRange.SCmd_UnSuppress,412701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almOverRange.AEShelveTMRDN,412701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almOverRange.Bad,412701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almOverRange.Suppress,412702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.UnSuppress,412702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Shelve,412702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.UnShelve,412702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Enable,412702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Disable,412702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Ack,412702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Reset,412702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Suppressed,412702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Shelved,412702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Disabled,412702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Acked,412702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almOverRange.Alarm,412702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Fault,412712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almUnderRange.AlarmState,412712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almUnderRange.GlobalReset,412712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almUnderRange.FaultInAlarm,412712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almUnderRange.ALRM,412712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almUnderRange.ANUN,412712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almUnderRange.AKED,412712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almUnderRange.Resetable,412712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almUnderRange.REST,412712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almUnderRange.ACKN,412712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almUnderRange.UACK,412712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almUnderRange.MCmd_Enable,412712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.MCmd_Disable,412712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.OCmd_Shelve,412712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.OCmd_Unshelve,412712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.SCmd_Suppress,412712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.SCmd_UnSuppress,412713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almUnderRange.AEShelveTMRDN,412713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almUnderRange.Bad,412713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almUnderRange.Suppress,412714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.UnSuppress,412714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Shelve,412714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.UnShelve,412714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Enable,412714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Disable,412714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Ack,412714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Reset,412714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Suppressed,412714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Shelved,412714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Disabled,412714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Acked,412714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almUnderRange.Alarm,412714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Fault,412724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almRateOfChange.AlarmState,412724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almRateOfChange.GlobalReset,412724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almRateOfChange.FaultInAlarm,412724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almRateOfChange.ALRM,412724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almRateOfChange.ANUN,412724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almRateOfChange.AKED,412724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almRateOfChange.Resetable,412724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almRateOfChange.REST,412724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almRateOfChange.ACKN,412724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almRateOfChange.UACK,412724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almRateOfChange.MCmd_Enable,412724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.MCmd_Disable,412724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.OCmd_Shelve,412724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.OCmd_Unshelve,412724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.SCmd_Suppress,412724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.SCmd_UnSuppress,412725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almRateOfChange.AEShelveTMRDN,412725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almRateOfChange.Bad,412725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almRateOfChange.Suppress,412726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.UnSuppress,412726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Shelve,412726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.UnShelve,412726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Enable,412726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Disable,412726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Ack,412726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Reset,412726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Suppressed,412726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Shelved,412726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Disabled,412726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Acked,412726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almRateOfChange.Alarm,412726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Fault,412736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI1.almPLCFault.AlarmState,412736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI1.almPLCFault.GlobalReset,412736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI1.almPLCFault.FaultInAlarm,412736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI1.almPLCFault.ALRM,412736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI1.almPLCFault.ANUN,412736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI1.almPLCFault.AKED,412736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI1.almPLCFault.Resetable,412736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI1.almPLCFault.REST,412736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI1.almPLCFault.ACKN,412736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI1.almPLCFault.UACK,412736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI1.almPLCFault.MCmd_Enable,412736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.MCmd_Disable,412736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.OCmd_Shelve,412736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.OCmd_Unshelve,412736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.SCmd_Suppress,412736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.SCmd_UnSuppress,412737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI1.almPLCFault.AEShelveTMRDN,412737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI1.almPLCFault.Bad,412737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI1.almPLCFault.Suppress,412738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.UnSuppress,412738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Shelve,412738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.UnShelve,412738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Enable,412738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Disable,412738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Ack,412738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Reset,412738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Suppressed,412738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Shelved,412738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Disabled,412738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Acked,412738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI1.almPLCFault.Alarm,412738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Fault,412840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almHighHigh.AlarmState,412840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almHighHigh.GlobalReset,412840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almHighHigh.FaultInAlarm,412840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almHighHigh.ALRM,412840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almHighHigh.ANUN,412840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almHighHigh.AKED,412840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almHighHigh.Resetable,412840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almHighHigh.REST,412840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almHighHigh.ACKN,412840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almHighHigh.UACK,412840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almHighHigh.MCmd_Enable,412840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.MCmd_Disable,412840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.OCmd_Shelve,412840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.OCmd_Unshelve,412840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.SCmd_Suppress,412840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.SCmd_UnSuppress,412841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almHighHigh.AEShelveTMRDN,412841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almHighHigh.Bad,412841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almHighHigh.Suppress,412842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.UnSuppress,412842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Shelve,412842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.UnShelve,412842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Enable,412842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Disable,412842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Ack,412842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Reset,412842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Suppressed,412842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Shelved,412842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Disabled,412842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Acked,412842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almHighHigh.Alarm,412842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Fault,412852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almHigh.AlarmState,412852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almHigh.GlobalReset,412852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almHigh.FaultInAlarm,412852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almHigh.ALRM,412852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almHigh.ANUN,412852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almHigh.AKED,412852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almHigh.Resetable,412852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almHigh.REST,412852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almHigh.ACKN,412852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almHigh.UACK,412852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almHigh.MCmd_Enable,412852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almHigh.MCmd_Disable,412852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almHigh.OCmd_Shelve,412852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almHigh.OCmd_Unshelve,412852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almHigh.SCmd_Suppress,412852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almHigh.SCmd_UnSuppress,412853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almHigh.AEShelveTMRDN,412853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almHigh.Bad,412853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almHigh.Suppress,412854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.UnSuppress,412854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Shelve,412854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.UnShelve,412854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Enable,412854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Disable,412854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Ack,412854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Reset,412854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almHigh.Suppressed,412854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almHigh.Shelved,412854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almHigh.Disabled,412854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almHigh.Acked,412854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almHigh.Alarm,412854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Fault,412864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almLow.AlarmState,412864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almLow.GlobalReset,412864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almLow.FaultInAlarm,412864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almLow.ALRM,412864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almLow.ANUN,412864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almLow.AKED,412864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almLow.Resetable,412864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almLow.REST,412864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almLow.ACKN,412864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almLow.UACK,412864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almLow.MCmd_Enable,412864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almLow.MCmd_Disable,412864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almLow.OCmd_Shelve,412864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almLow.OCmd_Unshelve,412864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almLow.SCmd_Suppress,412864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almLow.SCmd_UnSuppress,412865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almLow.AEShelveTMRDN,412865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almLow.Bad,412865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almLow.Suppress,412866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.UnSuppress,412866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Shelve,412866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.UnShelve,412866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Enable,412866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Disable,412866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Ack,412866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Reset,412866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almLow.Suppressed,412866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almLow.Shelved,412866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almLow.Disabled,412866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almLow.Acked,412866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almLow.Alarm,412866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Fault,412876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almLowLow.AlarmState,412876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almLowLow.GlobalReset,412876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almLowLow.FaultInAlarm,412876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almLowLow.ALRM,412876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almLowLow.ANUN,412876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almLowLow.AKED,412876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almLowLow.Resetable,412876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almLowLow.REST,412876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almLowLow.ACKN,412876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almLowLow.UACK,412876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almLowLow.MCmd_Enable,412876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almLowLow.MCmd_Disable,412876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almLowLow.OCmd_Shelve,412876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almLowLow.OCmd_Unshelve,412876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almLowLow.SCmd_Suppress,412876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almLowLow.SCmd_UnSuppress,412877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almLowLow.AEShelveTMRDN,412877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almLowLow.Bad,412877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almLowLow.Suppress,412878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.UnSuppress,412878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Shelve,412878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.UnShelve,412878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Enable,412878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Disable,412878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Ack,412878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Reset,412878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Suppressed,412878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Shelved,412878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Disabled,412878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Acked,412878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almLowLow.Alarm,412878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Fault,412888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almBrokenLoop.AlarmState,412888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almBrokenLoop.GlobalReset,412888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almBrokenLoop.FaultInAlarm,412888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almBrokenLoop.ALRM,412888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almBrokenLoop.ANUN,412888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almBrokenLoop.AKED,412888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almBrokenLoop.Resetable,412888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almBrokenLoop.REST,412888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almBrokenLoop.ACKN,412888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almBrokenLoop.UACK,412888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almBrokenLoop.MCmd_Enable,412888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.MCmd_Disable,412888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.OCmd_Shelve,412888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.OCmd_Unshelve,412888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.SCmd_Suppress,412888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.SCmd_UnSuppress,412889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almBrokenLoop.AEShelveTMRDN,412889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almBrokenLoop.Bad,412889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almBrokenLoop.Suppress,412890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.UnSuppress,412890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Shelve,412890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.UnShelve,412890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Enable,412890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Disable,412890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Ack,412890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Reset,412890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Suppressed,412890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Shelved,412890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Disabled,412890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Acked,412890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.Alarm,412890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Fault,412900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almOverRange.AlarmState,412900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almOverRange.GlobalReset,412900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almOverRange.FaultInAlarm,412900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almOverRange.ALRM,412900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almOverRange.ANUN,412900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almOverRange.AKED,412900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almOverRange.Resetable,412900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almOverRange.REST,412900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almOverRange.ACKN,412900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almOverRange.UACK,412900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almOverRange.MCmd_Enable,412900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almOverRange.MCmd_Disable,412900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almOverRange.OCmd_Shelve,412900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almOverRange.OCmd_Unshelve,412900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almOverRange.SCmd_Suppress,412900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almOverRange.SCmd_UnSuppress,412901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almOverRange.AEShelveTMRDN,412901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almOverRange.Bad,412901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almOverRange.Suppress,412902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.UnSuppress,412902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Shelve,412902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.UnShelve,412902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Enable,412902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Disable,412902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Ack,412902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Reset,412902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Suppressed,412902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Shelved,412902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Disabled,412902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Acked,412902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almOverRange.Alarm,412902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Fault,412912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almUnderRange.AlarmState,412912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almUnderRange.GlobalReset,412912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almUnderRange.FaultInAlarm,412912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almUnderRange.ALRM,412912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almUnderRange.ANUN,412912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almUnderRange.AKED,412912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almUnderRange.Resetable,412912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almUnderRange.REST,412912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almUnderRange.ACKN,412912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almUnderRange.UACK,412912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almUnderRange.MCmd_Enable,412912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.MCmd_Disable,412912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.OCmd_Shelve,412912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.OCmd_Unshelve,412912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.SCmd_Suppress,412912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.SCmd_UnSuppress,412913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almUnderRange.AEShelveTMRDN,412913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almUnderRange.Bad,412913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almUnderRange.Suppress,412914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.UnSuppress,412914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Shelve,412914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.UnShelve,412914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Enable,412914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Disable,412914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Ack,412914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Reset,412914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Suppressed,412914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Shelved,412914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Disabled,412914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Acked,412914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almUnderRange.Alarm,412914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Fault,412924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almRateOfChange.AlarmState,412924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almRateOfChange.GlobalReset,412924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almRateOfChange.FaultInAlarm,412924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almRateOfChange.ALRM,412924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almRateOfChange.ANUN,412924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almRateOfChange.AKED,412924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almRateOfChange.Resetable,412924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almRateOfChange.REST,412924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almRateOfChange.ACKN,412924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almRateOfChange.UACK,412924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almRateOfChange.MCmd_Enable,412924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.MCmd_Disable,412924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.OCmd_Shelve,412924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.OCmd_Unshelve,412924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.SCmd_Suppress,412924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.SCmd_UnSuppress,412925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almRateOfChange.AEShelveTMRDN,412925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almRateOfChange.Bad,412925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almRateOfChange.Suppress,412926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.UnSuppress,412926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Shelve,412926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.UnShelve,412926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Enable,412926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Disable,412926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Ack,412926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Reset,412926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Suppressed,412926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Shelved,412926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Disabled,412926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Acked,412926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almRateOfChange.Alarm,412926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Fault,412936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI2.almPLCFault.AlarmState,412936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI2.almPLCFault.GlobalReset,412936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI2.almPLCFault.FaultInAlarm,412936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI2.almPLCFault.ALRM,412936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI2.almPLCFault.ANUN,412936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI2.almPLCFault.AKED,412936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI2.almPLCFault.Resetable,412936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI2.almPLCFault.REST,412936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI2.almPLCFault.ACKN,412936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI2.almPLCFault.UACK,412936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI2.almPLCFault.MCmd_Enable,412936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.MCmd_Disable,412936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.OCmd_Shelve,412936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.OCmd_Unshelve,412936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.SCmd_Suppress,412936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.SCmd_UnSuppress,412937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI2.almPLCFault.AEShelveTMRDN,412937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI2.almPLCFault.Bad,412937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI2.almPLCFault.Suppress,412938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.UnSuppress,412938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Shelve,412938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.UnShelve,412938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Enable,412938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Disable,412938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Ack,412938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Reset,412938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Suppressed,412938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Shelved,412938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Disabled,412938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Acked,412938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI2.almPLCFault.Alarm,412938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Fault,413040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almHighHigh.AlarmState,413040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almHighHigh.GlobalReset,413040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almHighHigh.FaultInAlarm,413040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almHighHigh.ALRM,413040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almHighHigh.ANUN,413040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almHighHigh.AKED,413040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almHighHigh.Resetable,413040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almHighHigh.REST,413040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almHighHigh.ACKN,413040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almHighHigh.UACK,413040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almHighHigh.MCmd_Enable,413040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.MCmd_Disable,413040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.OCmd_Shelve,413040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.OCmd_Unshelve,413040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.SCmd_Suppress,413040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.SCmd_UnSuppress,413041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almHighHigh.AEShelveTMRDN,413041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almHighHigh.Bad,413041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almHighHigh.Suppress,413042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.UnSuppress,413042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Shelve,413042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.UnShelve,413042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Enable,413042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Disable,413042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Ack,413042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Reset,413042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Suppressed,413042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Shelved,413042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Disabled,413042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Acked,413042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almHighHigh.Alarm,413042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Fault,413052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almHigh.AlarmState,413052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almHigh.GlobalReset,413052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almHigh.FaultInAlarm,413052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almHigh.ALRM,413052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almHigh.ANUN,413052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almHigh.AKED,413052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almHigh.Resetable,413052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almHigh.REST,413052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almHigh.ACKN,413052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almHigh.UACK,413052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almHigh.MCmd_Enable,413052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almHigh.MCmd_Disable,413052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almHigh.OCmd_Shelve,413052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almHigh.OCmd_Unshelve,413052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almHigh.SCmd_Suppress,413052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almHigh.SCmd_UnSuppress,413053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almHigh.AEShelveTMRDN,413053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almHigh.Bad,413053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almHigh.Suppress,413054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.UnSuppress,413054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Shelve,413054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.UnShelve,413054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Enable,413054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Disable,413054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Ack,413054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Reset,413054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almHigh.Suppressed,413054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almHigh.Shelved,413054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almHigh.Disabled,413054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almHigh.Acked,413054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almHigh.Alarm,413054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Fault,413064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almLow.AlarmState,413064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almLow.GlobalReset,413064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almLow.FaultInAlarm,413064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almLow.ALRM,413064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almLow.ANUN,413064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almLow.AKED,413064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almLow.Resetable,413064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almLow.REST,413064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almLow.ACKN,413064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almLow.UACK,413064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almLow.MCmd_Enable,413064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almLow.MCmd_Disable,413064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almLow.OCmd_Shelve,413064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almLow.OCmd_Unshelve,413064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almLow.SCmd_Suppress,413064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almLow.SCmd_UnSuppress,413065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almLow.AEShelveTMRDN,413065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almLow.Bad,413065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almLow.Suppress,413066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.UnSuppress,413066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Shelve,413066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.UnShelve,413066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Enable,413066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Disable,413066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Ack,413066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Reset,413066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almLow.Suppressed,413066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almLow.Shelved,413066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almLow.Disabled,413066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almLow.Acked,413066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almLow.Alarm,413066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Fault,413076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almLowLow.AlarmState,413076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almLowLow.GlobalReset,413076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almLowLow.FaultInAlarm,413076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almLowLow.ALRM,413076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almLowLow.ANUN,413076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almLowLow.AKED,413076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almLowLow.Resetable,413076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almLowLow.REST,413076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almLowLow.ACKN,413076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almLowLow.UACK,413076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almLowLow.MCmd_Enable,413076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almLowLow.MCmd_Disable,413076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almLowLow.OCmd_Shelve,413076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almLowLow.OCmd_Unshelve,413076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almLowLow.SCmd_Suppress,413076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almLowLow.SCmd_UnSuppress,413077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almLowLow.AEShelveTMRDN,413077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almLowLow.Bad,413077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almLowLow.Suppress,413078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.UnSuppress,413078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Shelve,413078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.UnShelve,413078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Enable,413078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Disable,413078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Ack,413078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Reset,413078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Suppressed,413078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Shelved,413078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Disabled,413078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Acked,413078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almLowLow.Alarm,413078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Fault,413088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almBrokenLoop.AlarmState,413088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almBrokenLoop.GlobalReset,413088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almBrokenLoop.FaultInAlarm,413088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almBrokenLoop.ALRM,413088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almBrokenLoop.ANUN,413088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almBrokenLoop.AKED,413088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almBrokenLoop.Resetable,413088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almBrokenLoop.REST,413088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almBrokenLoop.ACKN,413088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almBrokenLoop.UACK,413088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almBrokenLoop.MCmd_Enable,413088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.MCmd_Disable,413088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.OCmd_Shelve,413088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.OCmd_Unshelve,413088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.SCmd_Suppress,413088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.SCmd_UnSuppress,413089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almBrokenLoop.AEShelveTMRDN,413089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almBrokenLoop.Bad,413089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almBrokenLoop.Suppress,413090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.UnSuppress,413090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Shelve,413090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.UnShelve,413090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Enable,413090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Disable,413090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Ack,413090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Reset,413090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Suppressed,413090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Shelved,413090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Disabled,413090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Acked,413090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.Alarm,413090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Fault,413100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almOverRange.AlarmState,413100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almOverRange.GlobalReset,413100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almOverRange.FaultInAlarm,413100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almOverRange.ALRM,413100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almOverRange.ANUN,413100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almOverRange.AKED,413100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almOverRange.Resetable,413100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almOverRange.REST,413100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almOverRange.ACKN,413100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almOverRange.UACK,413100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almOverRange.MCmd_Enable,413100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almOverRange.MCmd_Disable,413100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almOverRange.OCmd_Shelve,413100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almOverRange.OCmd_Unshelve,413100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almOverRange.SCmd_Suppress,413100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almOverRange.SCmd_UnSuppress,413101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almOverRange.AEShelveTMRDN,413101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almOverRange.Bad,413101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almOverRange.Suppress,413102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.UnSuppress,413102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Shelve,413102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.UnShelve,413102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Enable,413102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Disable,413102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Ack,413102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Reset,413102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Suppressed,413102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Shelved,413102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Disabled,413102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Acked,413102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almOverRange.Alarm,413102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Fault,413112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almUnderRange.AlarmState,413112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almUnderRange.GlobalReset,413112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almUnderRange.FaultInAlarm,413112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almUnderRange.ALRM,413112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almUnderRange.ANUN,413112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almUnderRange.AKED,413112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almUnderRange.Resetable,413112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almUnderRange.REST,413112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almUnderRange.ACKN,413112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almUnderRange.UACK,413112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almUnderRange.MCmd_Enable,413112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.MCmd_Disable,413112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.OCmd_Shelve,413112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.OCmd_Unshelve,413112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.SCmd_Suppress,413112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.SCmd_UnSuppress,413113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almUnderRange.AEShelveTMRDN,413113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almUnderRange.Bad,413113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almUnderRange.Suppress,413114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.UnSuppress,413114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Shelve,413114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.UnShelve,413114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Enable,413114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Disable,413114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Ack,413114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Reset,413114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Suppressed,413114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Shelved,413114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Disabled,413114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Acked,413114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almUnderRange.Alarm,413114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Fault,413124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almRateOfChange.AlarmState,413124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almRateOfChange.GlobalReset,413124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almRateOfChange.FaultInAlarm,413124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almRateOfChange.ALRM,413124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almRateOfChange.ANUN,413124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almRateOfChange.AKED,413124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almRateOfChange.Resetable,413124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almRateOfChange.REST,413124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almRateOfChange.ACKN,413124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almRateOfChange.UACK,413124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almRateOfChange.MCmd_Enable,413124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.MCmd_Disable,413124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.OCmd_Shelve,413124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.OCmd_Unshelve,413124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.SCmd_Suppress,413124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.SCmd_UnSuppress,413125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almRateOfChange.AEShelveTMRDN,413125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almRateOfChange.Bad,413125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almRateOfChange.Suppress,413126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.UnSuppress,413126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Shelve,413126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.UnShelve,413126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Enable,413126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Disable,413126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Ack,413126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Reset,413126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Suppressed,413126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Shelved,413126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Disabled,413126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Acked,413126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almRateOfChange.Alarm,413126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Fault,413136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI3.almPLCFault.AlarmState,413136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI3.almPLCFault.GlobalReset,413136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI3.almPLCFault.FaultInAlarm,413136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI3.almPLCFault.ALRM,413136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI3.almPLCFault.ANUN,413136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI3.almPLCFault.AKED,413136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI3.almPLCFault.Resetable,413136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI3.almPLCFault.REST,413136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI3.almPLCFault.ACKN,413136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI3.almPLCFault.UACK,413136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI3.almPLCFault.MCmd_Enable,413136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.MCmd_Disable,413136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.OCmd_Shelve,413136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.OCmd_Unshelve,413136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.SCmd_Suppress,413136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.SCmd_UnSuppress,413137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI3.almPLCFault.AEShelveTMRDN,413137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI3.almPLCFault.Bad,413137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI3.almPLCFault.Suppress,413138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.UnSuppress,413138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Shelve,413138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.UnShelve,413138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Enable,413138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Disable,413138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Ack,413138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Reset,413138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Suppressed,413138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Shelved,413138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Disabled,413138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Acked,413138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI3.almPLCFault.Alarm,413138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Fault,413240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almHighHigh.AlarmState,413240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almHighHigh.GlobalReset,413240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almHighHigh.FaultInAlarm,413240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almHighHigh.ALRM,413240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almHighHigh.ANUN,413240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almHighHigh.AKED,413240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almHighHigh.Resetable,413240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almHighHigh.REST,413240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almHighHigh.ACKN,413240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almHighHigh.UACK,413240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almHighHigh.MCmd_Enable,413240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.MCmd_Disable,413240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.OCmd_Shelve,413240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.OCmd_Unshelve,413240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.SCmd_Suppress,413240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.SCmd_UnSuppress,413241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almHighHigh.AEShelveTMRDN,413241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almHighHigh.Bad,413241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almHighHigh.Suppress,413242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.UnSuppress,413242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Shelve,413242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.UnShelve,413242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Enable,413242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Disable,413242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Ack,413242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Reset,413242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Suppressed,413242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Shelved,413242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Disabled,413242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Acked,413242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almHighHigh.Alarm,413242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Fault,413252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almHigh.AlarmState,413252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almHigh.GlobalReset,413252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almHigh.FaultInAlarm,413252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almHigh.ALRM,413252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almHigh.ANUN,413252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almHigh.AKED,413252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almHigh.Resetable,413252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almHigh.REST,413252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almHigh.ACKN,413252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almHigh.UACK,413252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almHigh.MCmd_Enable,413252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almHigh.MCmd_Disable,413252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almHigh.OCmd_Shelve,413252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almHigh.OCmd_Unshelve,413252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almHigh.SCmd_Suppress,413252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almHigh.SCmd_UnSuppress,413253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almHigh.AEShelveTMRDN,413253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almHigh.Bad,413253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almHigh.Suppress,413254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.UnSuppress,413254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Shelve,413254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.UnShelve,413254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Enable,413254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Disable,413254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Ack,413254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Reset,413254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almHigh.Suppressed,413254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almHigh.Shelved,413254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almHigh.Disabled,413254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almHigh.Acked,413254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almHigh.Alarm,413254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Fault,413264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almLow.AlarmState,413264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almLow.GlobalReset,413264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almLow.FaultInAlarm,413264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almLow.ALRM,413264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almLow.ANUN,413264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almLow.AKED,413264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almLow.Resetable,413264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almLow.REST,413264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almLow.ACKN,413264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almLow.UACK,413264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almLow.MCmd_Enable,413264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almLow.MCmd_Disable,413264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almLow.OCmd_Shelve,413264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almLow.OCmd_Unshelve,413264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almLow.SCmd_Suppress,413264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almLow.SCmd_UnSuppress,413265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almLow.AEShelveTMRDN,413265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almLow.Bad,413265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almLow.Suppress,413266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.UnSuppress,413266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Shelve,413266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.UnShelve,413266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Enable,413266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Disable,413266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Ack,413266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Reset,413266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almLow.Suppressed,413266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almLow.Shelved,413266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almLow.Disabled,413266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almLow.Acked,413266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almLow.Alarm,413266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Fault,413276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almLowLow.AlarmState,413276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almLowLow.GlobalReset,413276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almLowLow.FaultInAlarm,413276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almLowLow.ALRM,413276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almLowLow.ANUN,413276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almLowLow.AKED,413276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almLowLow.Resetable,413276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almLowLow.REST,413276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almLowLow.ACKN,413276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almLowLow.UACK,413276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almLowLow.MCmd_Enable,413276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almLowLow.MCmd_Disable,413276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almLowLow.OCmd_Shelve,413276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almLowLow.OCmd_Unshelve,413276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almLowLow.SCmd_Suppress,413276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almLowLow.SCmd_UnSuppress,413277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almLowLow.AEShelveTMRDN,413277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almLowLow.Bad,413277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almLowLow.Suppress,413278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.UnSuppress,413278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Shelve,413278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.UnShelve,413278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Enable,413278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Disable,413278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Ack,413278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Reset,413278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Suppressed,413278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Shelved,413278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Disabled,413278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Acked,413278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almLowLow.Alarm,413278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Fault,413288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almBrokenLoop.AlarmState,413288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almBrokenLoop.GlobalReset,413288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almBrokenLoop.FaultInAlarm,413288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almBrokenLoop.ALRM,413288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almBrokenLoop.ANUN,413288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almBrokenLoop.AKED,413288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almBrokenLoop.Resetable,413288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almBrokenLoop.REST,413288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almBrokenLoop.ACKN,413288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almBrokenLoop.UACK,413288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almBrokenLoop.MCmd_Enable,413288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.MCmd_Disable,413288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.OCmd_Shelve,413288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.OCmd_Unshelve,413288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.SCmd_Suppress,413288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.SCmd_UnSuppress,413289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almBrokenLoop.AEShelveTMRDN,413289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almBrokenLoop.Bad,413289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almBrokenLoop.Suppress,413290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.UnSuppress,413290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Shelve,413290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.UnShelve,413290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Enable,413290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Disable,413290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Ack,413290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Reset,413290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Suppressed,413290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Shelved,413290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Disabled,413290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Acked,413290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.Alarm,413290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Fault,413300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almOverRange.AlarmState,413300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almOverRange.GlobalReset,413300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almOverRange.FaultInAlarm,413300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almOverRange.ALRM,413300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almOverRange.ANUN,413300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almOverRange.AKED,413300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almOverRange.Resetable,413300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almOverRange.REST,413300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almOverRange.ACKN,413300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almOverRange.UACK,413300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almOverRange.MCmd_Enable,413300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almOverRange.MCmd_Disable,413300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almOverRange.OCmd_Shelve,413300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almOverRange.OCmd_Unshelve,413300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almOverRange.SCmd_Suppress,413300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almOverRange.SCmd_UnSuppress,413301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almOverRange.AEShelveTMRDN,413301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almOverRange.Bad,413301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almOverRange.Suppress,413302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.UnSuppress,413302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Shelve,413302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.UnShelve,413302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Enable,413302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Disable,413302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Ack,413302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Reset,413302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Suppressed,413302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Shelved,413302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Disabled,413302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Acked,413302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almOverRange.Alarm,413302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Fault,413312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almUnderRange.AlarmState,413312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almUnderRange.GlobalReset,413312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almUnderRange.FaultInAlarm,413312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almUnderRange.ALRM,413312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almUnderRange.ANUN,413312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almUnderRange.AKED,413312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almUnderRange.Resetable,413312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almUnderRange.REST,413312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almUnderRange.ACKN,413312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almUnderRange.UACK,413312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almUnderRange.MCmd_Enable,413312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.MCmd_Disable,413312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.OCmd_Shelve,413312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.OCmd_Unshelve,413312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.SCmd_Suppress,413312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.SCmd_UnSuppress,413313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almUnderRange.AEShelveTMRDN,413313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almUnderRange.Bad,413313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almUnderRange.Suppress,413314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.UnSuppress,413314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Shelve,413314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.UnShelve,413314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Enable,413314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Disable,413314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Ack,413314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Reset,413314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Suppressed,413314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Shelved,413314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Disabled,413314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Acked,413314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almUnderRange.Alarm,413314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Fault,413324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almRateOfChange.AlarmState,413324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almRateOfChange.GlobalReset,413324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almRateOfChange.FaultInAlarm,413324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almRateOfChange.ALRM,413324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almRateOfChange.ANUN,413324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almRateOfChange.AKED,413324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almRateOfChange.Resetable,413324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almRateOfChange.REST,413324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almRateOfChange.ACKN,413324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almRateOfChange.UACK,413324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almRateOfChange.MCmd_Enable,413324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.MCmd_Disable,413324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.OCmd_Shelve,413324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.OCmd_Unshelve,413324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.SCmd_Suppress,413324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.SCmd_UnSuppress,413325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almRateOfChange.AEShelveTMRDN,413325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almRateOfChange.Bad,413325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almRateOfChange.Suppress,413326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.UnSuppress,413326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Shelve,413326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.UnShelve,413326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Enable,413326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Disable,413326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Ack,413326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Reset,413326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Suppressed,413326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Shelved,413326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Disabled,413326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Acked,413326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almRateOfChange.Alarm,413326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Fault,413336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_8_VI4.almPLCFault.AlarmState,413336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_8_VI4.almPLCFault.GlobalReset,413336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_8_VI4.almPLCFault.FaultInAlarm,413336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_8_VI4.almPLCFault.ALRM,413336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_8_VI4.almPLCFault.ANUN,413336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_8_VI4.almPLCFault.AKED,413336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_8_VI4.almPLCFault.Resetable,413336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_8_VI4.almPLCFault.REST,413336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_8_VI4.almPLCFault.ACKN,413336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_8_VI4.almPLCFault.UACK,413336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_8_VI4.almPLCFault.MCmd_Enable,413336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.MCmd_Disable,413336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.OCmd_Shelve,413336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.OCmd_Unshelve,413336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.SCmd_Suppress,413336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.SCmd_UnSuppress,413337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_8_VI4.almPLCFault.AEShelveTMRDN,413337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_8_VI4.almPLCFault.Bad,413337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_8_VI4.almPLCFault.Suppress,413338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.UnSuppress,413338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Shelve,413338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.UnShelve,413338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Enable,413338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Disable,413338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Ack,413338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Reset,413338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Suppressed,413338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Shelved,413338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Disabled,413338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Acked,413338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_8_VI4.almPLCFault.Alarm,413338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Fault,413440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almHighHigh.AlarmState,413440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almHighHigh.GlobalReset,413440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almHighHigh.FaultInAlarm,413440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almHighHigh.ALRM,413440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almHighHigh.ANUN,413440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almHighHigh.AKED,413440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almHighHigh.Resetable,413440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almHighHigh.REST,413440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almHighHigh.ACKN,413440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almHighHigh.UACK,413440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almHighHigh.MCmd_Enable,413440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.MCmd_Disable,413440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.OCmd_Shelve,413440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.OCmd_Unshelve,413440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.SCmd_Suppress,413440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.SCmd_UnSuppress,413441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almHighHigh.AEShelveTMRDN,413441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almHighHigh.Bad,413441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almHighHigh.Suppress,413442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.UnSuppress,413442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Shelve,413442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.UnShelve,413442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Enable,413442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Disable,413442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Ack,413442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Reset,413442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Suppressed,413442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Shelved,413442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Disabled,413442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Acked,413442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almHighHigh.Alarm,413442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Fault,413452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almHigh.AlarmState,413452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almHigh.GlobalReset,413452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almHigh.FaultInAlarm,413452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almHigh.ALRM,413452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almHigh.ANUN,413452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almHigh.AKED,413452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almHigh.Resetable,413452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almHigh.REST,413452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almHigh.ACKN,413452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almHigh.UACK,413452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almHigh.MCmd_Enable,413452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almHigh.MCmd_Disable,413452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almHigh.OCmd_Shelve,413452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almHigh.OCmd_Unshelve,413452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almHigh.SCmd_Suppress,413452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almHigh.SCmd_UnSuppress,413453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almHigh.AEShelveTMRDN,413453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almHigh.Bad,413453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almHigh.Suppress,413454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.UnSuppress,413454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Shelve,413454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.UnShelve,413454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Enable,413454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Disable,413454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Ack,413454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Reset,413454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almHigh.Suppressed,413454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almHigh.Shelved,413454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almHigh.Disabled,413454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almHigh.Acked,413454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almHigh.Alarm,413454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Fault,413464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almLow.AlarmState,413464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almLow.GlobalReset,413464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almLow.FaultInAlarm,413464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almLow.ALRM,413464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almLow.ANUN,413464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almLow.AKED,413464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almLow.Resetable,413464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almLow.REST,413464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almLow.ACKN,413464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almLow.UACK,413464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almLow.MCmd_Enable,413464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almLow.MCmd_Disable,413464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almLow.OCmd_Shelve,413464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almLow.OCmd_Unshelve,413464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almLow.SCmd_Suppress,413464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almLow.SCmd_UnSuppress,413465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almLow.AEShelveTMRDN,413465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almLow.Bad,413465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almLow.Suppress,413466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.UnSuppress,413466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Shelve,413466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.UnShelve,413466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Enable,413466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Disable,413466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Ack,413466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Reset,413466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almLow.Suppressed,413466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almLow.Shelved,413466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almLow.Disabled,413466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almLow.Acked,413466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almLow.Alarm,413466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Fault,413476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almLowLow.AlarmState,413476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almLowLow.GlobalReset,413476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almLowLow.FaultInAlarm,413476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almLowLow.ALRM,413476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almLowLow.ANUN,413476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almLowLow.AKED,413476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almLowLow.Resetable,413476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almLowLow.REST,413476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almLowLow.ACKN,413476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almLowLow.UACK,413476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almLowLow.MCmd_Enable,413476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almLowLow.MCmd_Disable,413476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almLowLow.OCmd_Shelve,413476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almLowLow.OCmd_Unshelve,413476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almLowLow.SCmd_Suppress,413476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almLowLow.SCmd_UnSuppress,413477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almLowLow.AEShelveTMRDN,413477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almLowLow.Bad,413477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almLowLow.Suppress,413478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.UnSuppress,413478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Shelve,413478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.UnShelve,413478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Enable,413478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Disable,413478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Ack,413478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Reset,413478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Suppressed,413478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Shelved,413478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Disabled,413478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Acked,413478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almLowLow.Alarm,413478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Fault,413488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almBrokenLoop.AlarmState,413488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almBrokenLoop.GlobalReset,413488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almBrokenLoop.FaultInAlarm,413488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almBrokenLoop.ALRM,413488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almBrokenLoop.ANUN,413488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almBrokenLoop.AKED,413488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almBrokenLoop.Resetable,413488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almBrokenLoop.REST,413488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almBrokenLoop.ACKN,413488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almBrokenLoop.UACK,413488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almBrokenLoop.MCmd_Enable,413488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.MCmd_Disable,413488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.OCmd_Shelve,413488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.OCmd_Unshelve,413488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.SCmd_Suppress,413488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.SCmd_UnSuppress,413489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almBrokenLoop.AEShelveTMRDN,413489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almBrokenLoop.Bad,413489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almBrokenLoop.Suppress,413490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.UnSuppress,413490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Shelve,413490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.UnShelve,413490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Enable,413490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Disable,413490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Ack,413490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Reset,413490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Suppressed,413490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Shelved,413490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Disabled,413490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Acked,413490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.Alarm,413490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Fault,413500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almOverRange.AlarmState,413500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almOverRange.GlobalReset,413500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almOverRange.FaultInAlarm,413500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almOverRange.ALRM,413500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almOverRange.ANUN,413500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almOverRange.AKED,413500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almOverRange.Resetable,413500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almOverRange.REST,413500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almOverRange.ACKN,413500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almOverRange.UACK,413500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almOverRange.MCmd_Enable,413500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almOverRange.MCmd_Disable,413500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almOverRange.OCmd_Shelve,413500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almOverRange.OCmd_Unshelve,413500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almOverRange.SCmd_Suppress,413500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almOverRange.SCmd_UnSuppress,413501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almOverRange.AEShelveTMRDN,413501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almOverRange.Bad,413501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almOverRange.Suppress,413502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.UnSuppress,413502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Shelve,413502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.UnShelve,413502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Enable,413502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Disable,413502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Ack,413502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Reset,413502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Suppressed,413502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Shelved,413502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Disabled,413502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Acked,413502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almOverRange.Alarm,413502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Fault,413512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almUnderRange.AlarmState,413512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almUnderRange.GlobalReset,413512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almUnderRange.FaultInAlarm,413512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almUnderRange.ALRM,413512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almUnderRange.ANUN,413512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almUnderRange.AKED,413512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almUnderRange.Resetable,413512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almUnderRange.REST,413512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almUnderRange.ACKN,413512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almUnderRange.UACK,413512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almUnderRange.MCmd_Enable,413512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.MCmd_Disable,413512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.OCmd_Shelve,413512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.OCmd_Unshelve,413512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.SCmd_Suppress,413512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.SCmd_UnSuppress,413513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almUnderRange.AEShelveTMRDN,413513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almUnderRange.Bad,413513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almUnderRange.Suppress,413514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.UnSuppress,413514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Shelve,413514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.UnShelve,413514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Enable,413514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Disable,413514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Ack,413514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Reset,413514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Suppressed,413514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Shelved,413514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Disabled,413514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Acked,413514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almUnderRange.Alarm,413514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Fault,413524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almRateOfChange.AlarmState,413524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almRateOfChange.GlobalReset,413524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almRateOfChange.FaultInAlarm,413524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almRateOfChange.ALRM,413524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almRateOfChange.ANUN,413524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almRateOfChange.AKED,413524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almRateOfChange.Resetable,413524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almRateOfChange.REST,413524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almRateOfChange.ACKN,413524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almRateOfChange.UACK,413524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almRateOfChange.MCmd_Enable,413524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.MCmd_Disable,413524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.OCmd_Shelve,413524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.OCmd_Unshelve,413524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.SCmd_Suppress,413524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.SCmd_UnSuppress,413525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almRateOfChange.AEShelveTMRDN,413525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almRateOfChange.Bad,413525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almRateOfChange.Suppress,413526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.UnSuppress,413526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Shelve,413526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.UnShelve,413526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Enable,413526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Disable,413526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Ack,413526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Reset,413526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Suppressed,413526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Shelved,413526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Disabled,413526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Acked,413526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almRateOfChange.Alarm,413526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Fault,413536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI1.almPLCFault.AlarmState,413536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI1.almPLCFault.GlobalReset,413536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI1.almPLCFault.FaultInAlarm,413536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI1.almPLCFault.ALRM,413536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI1.almPLCFault.ANUN,413536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI1.almPLCFault.AKED,413536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI1.almPLCFault.Resetable,413536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI1.almPLCFault.REST,413536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI1.almPLCFault.ACKN,413536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI1.almPLCFault.UACK,413536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI1.almPLCFault.MCmd_Enable,413536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.MCmd_Disable,413536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.OCmd_Shelve,413536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.OCmd_Unshelve,413536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.SCmd_Suppress,413536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.SCmd_UnSuppress,413537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI1.almPLCFault.AEShelveTMRDN,413537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI1.almPLCFault.Bad,413537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI1.almPLCFault.Suppress,413538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.UnSuppress,413538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Shelve,413538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.UnShelve,413538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Enable,413538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Disable,413538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Ack,413538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Reset,413538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Suppressed,413538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Shelved,413538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Disabled,413538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Acked,413538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI1.almPLCFault.Alarm,413538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Fault,413640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almHighHigh.AlarmState,413640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almHighHigh.GlobalReset,413640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almHighHigh.FaultInAlarm,413640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almHighHigh.ALRM,413640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almHighHigh.ANUN,413640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almHighHigh.AKED,413640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almHighHigh.Resetable,413640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almHighHigh.REST,413640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almHighHigh.ACKN,413640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almHighHigh.UACK,413640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almHighHigh.MCmd_Enable,413640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.MCmd_Disable,413640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.OCmd_Shelve,413640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.OCmd_Unshelve,413640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.SCmd_Suppress,413640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.SCmd_UnSuppress,413641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almHighHigh.AEShelveTMRDN,413641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almHighHigh.Bad,413641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almHighHigh.Suppress,413642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.UnSuppress,413642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Shelve,413642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.UnShelve,413642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Enable,413642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Disable,413642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Ack,413642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Reset,413642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Suppressed,413642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Shelved,413642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Disabled,413642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Acked,413642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almHighHigh.Alarm,413642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Fault,413652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almHigh.AlarmState,413652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almHigh.GlobalReset,413652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almHigh.FaultInAlarm,413652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almHigh.ALRM,413652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almHigh.ANUN,413652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almHigh.AKED,413652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almHigh.Resetable,413652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almHigh.REST,413652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almHigh.ACKN,413652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almHigh.UACK,413652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almHigh.MCmd_Enable,413652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almHigh.MCmd_Disable,413652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almHigh.OCmd_Shelve,413652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almHigh.OCmd_Unshelve,413652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almHigh.SCmd_Suppress,413652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almHigh.SCmd_UnSuppress,413653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almHigh.AEShelveTMRDN,413653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almHigh.Bad,413653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almHigh.Suppress,413654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.UnSuppress,413654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Shelve,413654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.UnShelve,413654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Enable,413654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Disable,413654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Ack,413654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Reset,413654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almHigh.Suppressed,413654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almHigh.Shelved,413654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almHigh.Disabled,413654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almHigh.Acked,413654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almHigh.Alarm,413654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Fault,413664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almLow.AlarmState,413664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almLow.GlobalReset,413664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almLow.FaultInAlarm,413664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almLow.ALRM,413664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almLow.ANUN,413664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almLow.AKED,413664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almLow.Resetable,413664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almLow.REST,413664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almLow.ACKN,413664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almLow.UACK,413664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almLow.MCmd_Enable,413664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almLow.MCmd_Disable,413664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almLow.OCmd_Shelve,413664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almLow.OCmd_Unshelve,413664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almLow.SCmd_Suppress,413664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almLow.SCmd_UnSuppress,413665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almLow.AEShelveTMRDN,413665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almLow.Bad,413665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almLow.Suppress,413666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.UnSuppress,413666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Shelve,413666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.UnShelve,413666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Enable,413666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Disable,413666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Ack,413666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Reset,413666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almLow.Suppressed,413666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almLow.Shelved,413666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almLow.Disabled,413666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almLow.Acked,413666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almLow.Alarm,413666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Fault,413676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almLowLow.AlarmState,413676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almLowLow.GlobalReset,413676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almLowLow.FaultInAlarm,413676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almLowLow.ALRM,413676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almLowLow.ANUN,413676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almLowLow.AKED,413676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almLowLow.Resetable,413676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almLowLow.REST,413676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almLowLow.ACKN,413676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almLowLow.UACK,413676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almLowLow.MCmd_Enable,413676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almLowLow.MCmd_Disable,413676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almLowLow.OCmd_Shelve,413676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almLowLow.OCmd_Unshelve,413676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almLowLow.SCmd_Suppress,413676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almLowLow.SCmd_UnSuppress,413677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almLowLow.AEShelveTMRDN,413677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almLowLow.Bad,413677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almLowLow.Suppress,413678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.UnSuppress,413678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Shelve,413678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.UnShelve,413678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Enable,413678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Disable,413678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Ack,413678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Reset,413678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Suppressed,413678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Shelved,413678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Disabled,413678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Acked,413678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almLowLow.Alarm,413678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Fault,413688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almBrokenLoop.AlarmState,413688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almBrokenLoop.GlobalReset,413688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almBrokenLoop.FaultInAlarm,413688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almBrokenLoop.ALRM,413688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almBrokenLoop.ANUN,413688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almBrokenLoop.AKED,413688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almBrokenLoop.Resetable,413688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almBrokenLoop.REST,413688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almBrokenLoop.ACKN,413688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almBrokenLoop.UACK,413688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almBrokenLoop.MCmd_Enable,413688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.MCmd_Disable,413688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.OCmd_Shelve,413688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.OCmd_Unshelve,413688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.SCmd_Suppress,413688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.SCmd_UnSuppress,413689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almBrokenLoop.AEShelveTMRDN,413689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almBrokenLoop.Bad,413689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almBrokenLoop.Suppress,413690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.UnSuppress,413690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Shelve,413690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.UnShelve,413690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Enable,413690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Disable,413690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Ack,413690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Reset,413690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Suppressed,413690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Shelved,413690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Disabled,413690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Acked,413690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.Alarm,413690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Fault,413700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almOverRange.AlarmState,413700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almOverRange.GlobalReset,413700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almOverRange.FaultInAlarm,413700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almOverRange.ALRM,413700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almOverRange.ANUN,413700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almOverRange.AKED,413700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almOverRange.Resetable,413700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almOverRange.REST,413700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almOverRange.ACKN,413700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almOverRange.UACK,413700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almOverRange.MCmd_Enable,413700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almOverRange.MCmd_Disable,413700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almOverRange.OCmd_Shelve,413700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almOverRange.OCmd_Unshelve,413700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almOverRange.SCmd_Suppress,413700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almOverRange.SCmd_UnSuppress,413701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almOverRange.AEShelveTMRDN,413701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almOverRange.Bad,413701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almOverRange.Suppress,413702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.UnSuppress,413702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Shelve,413702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.UnShelve,413702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Enable,413702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Disable,413702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Ack,413702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Reset,413702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Suppressed,413702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Shelved,413702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Disabled,413702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Acked,413702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almOverRange.Alarm,413702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Fault,413712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almUnderRange.AlarmState,413712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almUnderRange.GlobalReset,413712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almUnderRange.FaultInAlarm,413712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almUnderRange.ALRM,413712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almUnderRange.ANUN,413712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almUnderRange.AKED,413712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almUnderRange.Resetable,413712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almUnderRange.REST,413712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almUnderRange.ACKN,413712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almUnderRange.UACK,413712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almUnderRange.MCmd_Enable,413712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.MCmd_Disable,413712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.OCmd_Shelve,413712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.OCmd_Unshelve,413712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.SCmd_Suppress,413712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.SCmd_UnSuppress,413713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almUnderRange.AEShelveTMRDN,413713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almUnderRange.Bad,413713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almUnderRange.Suppress,413714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.UnSuppress,413714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Shelve,413714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.UnShelve,413714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Enable,413714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Disable,413714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Ack,413714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Reset,413714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Suppressed,413714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Shelved,413714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Disabled,413714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Acked,413714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almUnderRange.Alarm,413714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Fault,413724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almRateOfChange.AlarmState,413724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almRateOfChange.GlobalReset,413724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almRateOfChange.FaultInAlarm,413724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almRateOfChange.ALRM,413724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almRateOfChange.ANUN,413724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almRateOfChange.AKED,413724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almRateOfChange.Resetable,413724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almRateOfChange.REST,413724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almRateOfChange.ACKN,413724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almRateOfChange.UACK,413724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almRateOfChange.MCmd_Enable,413724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.MCmd_Disable,413724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.OCmd_Shelve,413724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.OCmd_Unshelve,413724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.SCmd_Suppress,413724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.SCmd_UnSuppress,413725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almRateOfChange.AEShelveTMRDN,413725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almRateOfChange.Bad,413725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almRateOfChange.Suppress,413726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.UnSuppress,413726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Shelve,413726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.UnShelve,413726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Enable,413726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Disable,413726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Ack,413726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Reset,413726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Suppressed,413726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Shelved,413726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Disabled,413726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Acked,413726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almRateOfChange.Alarm,413726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Fault,413736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI2.almPLCFault.AlarmState,413736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI2.almPLCFault.GlobalReset,413736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI2.almPLCFault.FaultInAlarm,413736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI2.almPLCFault.ALRM,413736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI2.almPLCFault.ANUN,413736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI2.almPLCFault.AKED,413736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI2.almPLCFault.Resetable,413736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI2.almPLCFault.REST,413736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI2.almPLCFault.ACKN,413736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI2.almPLCFault.UACK,413736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI2.almPLCFault.MCmd_Enable,413736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.MCmd_Disable,413736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.OCmd_Shelve,413736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.OCmd_Unshelve,413736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.SCmd_Suppress,413736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.SCmd_UnSuppress,413737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI2.almPLCFault.AEShelveTMRDN,413737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI2.almPLCFault.Bad,413737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI2.almPLCFault.Suppress,413738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.UnSuppress,413738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Shelve,413738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.UnShelve,413738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Enable,413738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Disable,413738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Ack,413738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Reset,413738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Suppressed,413738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Shelved,413738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Disabled,413738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Acked,413738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI2.almPLCFault.Alarm,413738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Fault,413840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almHighHigh.AlarmState,413840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almHighHigh.GlobalReset,413840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almHighHigh.FaultInAlarm,413840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almHighHigh.ALRM,413840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almHighHigh.ANUN,413840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almHighHigh.AKED,413840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almHighHigh.Resetable,413840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almHighHigh.REST,413840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almHighHigh.ACKN,413840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almHighHigh.UACK,413840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almHighHigh.MCmd_Enable,413840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.MCmd_Disable,413840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.OCmd_Shelve,413840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.OCmd_Unshelve,413840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.SCmd_Suppress,413840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.SCmd_UnSuppress,413841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almHighHigh.AEShelveTMRDN,413841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almHighHigh.Bad,413841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almHighHigh.Suppress,413842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.UnSuppress,413842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Shelve,413842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.UnShelve,413842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Enable,413842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Disable,413842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Ack,413842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Reset,413842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Suppressed,413842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Shelved,413842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Disabled,413842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Acked,413842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almHighHigh.Alarm,413842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Fault,413852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almHigh.AlarmState,413852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almHigh.GlobalReset,413852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almHigh.FaultInAlarm,413852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almHigh.ALRM,413852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almHigh.ANUN,413852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almHigh.AKED,413852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almHigh.Resetable,413852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almHigh.REST,413852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almHigh.ACKN,413852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almHigh.UACK,413852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almHigh.MCmd_Enable,413852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almHigh.MCmd_Disable,413852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almHigh.OCmd_Shelve,413852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almHigh.OCmd_Unshelve,413852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almHigh.SCmd_Suppress,413852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almHigh.SCmd_UnSuppress,413853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almHigh.AEShelveTMRDN,413853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almHigh.Bad,413853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almHigh.Suppress,413854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.UnSuppress,413854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Shelve,413854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.UnShelve,413854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Enable,413854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Disable,413854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Ack,413854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Reset,413854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almHigh.Suppressed,413854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almHigh.Shelved,413854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almHigh.Disabled,413854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almHigh.Acked,413854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almHigh.Alarm,413854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Fault,413864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almLow.AlarmState,413864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almLow.GlobalReset,413864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almLow.FaultInAlarm,413864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almLow.ALRM,413864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almLow.ANUN,413864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almLow.AKED,413864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almLow.Resetable,413864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almLow.REST,413864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almLow.ACKN,413864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almLow.UACK,413864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almLow.MCmd_Enable,413864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almLow.MCmd_Disable,413864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almLow.OCmd_Shelve,413864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almLow.OCmd_Unshelve,413864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almLow.SCmd_Suppress,413864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almLow.SCmd_UnSuppress,413865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almLow.AEShelveTMRDN,413865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almLow.Bad,413865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almLow.Suppress,413866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.UnSuppress,413866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Shelve,413866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.UnShelve,413866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Enable,413866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Disable,413866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Ack,413866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Reset,413866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almLow.Suppressed,413866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almLow.Shelved,413866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almLow.Disabled,413866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almLow.Acked,413866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almLow.Alarm,413866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Fault,413876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almLowLow.AlarmState,413876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almLowLow.GlobalReset,413876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almLowLow.FaultInAlarm,413876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almLowLow.ALRM,413876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almLowLow.ANUN,413876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almLowLow.AKED,413876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almLowLow.Resetable,413876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almLowLow.REST,413876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almLowLow.ACKN,413876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almLowLow.UACK,413876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almLowLow.MCmd_Enable,413876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almLowLow.MCmd_Disable,413876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almLowLow.OCmd_Shelve,413876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almLowLow.OCmd_Unshelve,413876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almLowLow.SCmd_Suppress,413876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almLowLow.SCmd_UnSuppress,413877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almLowLow.AEShelveTMRDN,413877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almLowLow.Bad,413877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almLowLow.Suppress,413878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.UnSuppress,413878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Shelve,413878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.UnShelve,413878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Enable,413878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Disable,413878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Ack,413878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Reset,413878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Suppressed,413878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Shelved,413878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Disabled,413878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Acked,413878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almLowLow.Alarm,413878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Fault,413888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almBrokenLoop.AlarmState,413888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almBrokenLoop.GlobalReset,413888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almBrokenLoop.FaultInAlarm,413888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almBrokenLoop.ALRM,413888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almBrokenLoop.ANUN,413888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almBrokenLoop.AKED,413888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almBrokenLoop.Resetable,413888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almBrokenLoop.REST,413888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almBrokenLoop.ACKN,413888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almBrokenLoop.UACK,413888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almBrokenLoop.MCmd_Enable,413888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.MCmd_Disable,413888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.OCmd_Shelve,413888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.OCmd_Unshelve,413888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.SCmd_Suppress,413888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.SCmd_UnSuppress,413889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almBrokenLoop.AEShelveTMRDN,413889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almBrokenLoop.Bad,413889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almBrokenLoop.Suppress,413890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.UnSuppress,413890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Shelve,413890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.UnShelve,413890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Enable,413890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Disable,413890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Ack,413890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Reset,413890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Suppressed,413890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Shelved,413890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Disabled,413890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Acked,413890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.Alarm,413890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Fault,413900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almOverRange.AlarmState,413900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almOverRange.GlobalReset,413900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almOverRange.FaultInAlarm,413900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almOverRange.ALRM,413900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almOverRange.ANUN,413900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almOverRange.AKED,413900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almOverRange.Resetable,413900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almOverRange.REST,413900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almOverRange.ACKN,413900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almOverRange.UACK,413900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almOverRange.MCmd_Enable,413900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almOverRange.MCmd_Disable,413900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almOverRange.OCmd_Shelve,413900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almOverRange.OCmd_Unshelve,413900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almOverRange.SCmd_Suppress,413900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almOverRange.SCmd_UnSuppress,413901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almOverRange.AEShelveTMRDN,413901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almOverRange.Bad,413901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almOverRange.Suppress,413902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.UnSuppress,413902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Shelve,413902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.UnShelve,413902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Enable,413902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Disable,413902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Ack,413902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Reset,413902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Suppressed,413902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Shelved,413902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Disabled,413902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Acked,413902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almOverRange.Alarm,413902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Fault,413912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almUnderRange.AlarmState,413912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almUnderRange.GlobalReset,413912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almUnderRange.FaultInAlarm,413912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almUnderRange.ALRM,413912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almUnderRange.ANUN,413912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almUnderRange.AKED,413912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almUnderRange.Resetable,413912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almUnderRange.REST,413912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almUnderRange.ACKN,413912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almUnderRange.UACK,413912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almUnderRange.MCmd_Enable,413912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.MCmd_Disable,413912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.OCmd_Shelve,413912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.OCmd_Unshelve,413912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.SCmd_Suppress,413912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.SCmd_UnSuppress,413913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almUnderRange.AEShelveTMRDN,413913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almUnderRange.Bad,413913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almUnderRange.Suppress,413914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.UnSuppress,413914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Shelve,413914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.UnShelve,413914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Enable,413914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Disable,413914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Ack,413914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Reset,413914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Suppressed,413914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Shelved,413914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Disabled,413914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Acked,413914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almUnderRange.Alarm,413914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Fault,413924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almRateOfChange.AlarmState,413924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almRateOfChange.GlobalReset,413924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almRateOfChange.FaultInAlarm,413924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almRateOfChange.ALRM,413924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almRateOfChange.ANUN,413924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almRateOfChange.AKED,413924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almRateOfChange.Resetable,413924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almRateOfChange.REST,413924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almRateOfChange.ACKN,413924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almRateOfChange.UACK,413924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almRateOfChange.MCmd_Enable,413924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.MCmd_Disable,413924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.OCmd_Shelve,413924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.OCmd_Unshelve,413924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.SCmd_Suppress,413924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.SCmd_UnSuppress,413925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almRateOfChange.AEShelveTMRDN,413925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almRateOfChange.Bad,413925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almRateOfChange.Suppress,413926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.UnSuppress,413926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Shelve,413926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.UnShelve,413926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Enable,413926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Disable,413926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Ack,413926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Reset,413926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Suppressed,413926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Shelved,413926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Disabled,413926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Acked,413926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almRateOfChange.Alarm,413926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Fault,413936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI3.almPLCFault.AlarmState,413936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI3.almPLCFault.GlobalReset,413936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI3.almPLCFault.FaultInAlarm,413936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI3.almPLCFault.ALRM,413936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI3.almPLCFault.ANUN,413936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI3.almPLCFault.AKED,413936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI3.almPLCFault.Resetable,413936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI3.almPLCFault.REST,413936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI3.almPLCFault.ACKN,413936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI3.almPLCFault.UACK,413936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI3.almPLCFault.MCmd_Enable,413936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.MCmd_Disable,413936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.OCmd_Shelve,413936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.OCmd_Unshelve,413936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.SCmd_Suppress,413936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.SCmd_UnSuppress,413937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI3.almPLCFault.AEShelveTMRDN,413937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI3.almPLCFault.Bad,413937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI3.almPLCFault.Suppress,413938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.UnSuppress,413938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Shelve,413938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.UnShelve,413938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Enable,413938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Disable,413938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Ack,413938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Reset,413938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Suppressed,413938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Shelved,413938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Disabled,413938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Acked,413938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI3.almPLCFault.Alarm,413938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Fault,414040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almHighHigh.AlarmState,414040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almHighHigh.GlobalReset,414040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almHighHigh.FaultInAlarm,414040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almHighHigh.ALRM,414040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almHighHigh.ANUN,414040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almHighHigh.AKED,414040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almHighHigh.Resetable,414040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almHighHigh.REST,414040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almHighHigh.ACKN,414040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almHighHigh.UACK,414040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almHighHigh.MCmd_Enable,414040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.MCmd_Disable,414040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.OCmd_Shelve,414040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.OCmd_Unshelve,414040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.SCmd_Suppress,414040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.SCmd_UnSuppress,414041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almHighHigh.AEShelveTMRDN,414041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almHighHigh.Bad,414041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almHighHigh.Suppress,414042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.UnSuppress,414042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Shelve,414042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.UnShelve,414042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Enable,414042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Disable,414042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Ack,414042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Reset,414042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Suppressed,414042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Shelved,414042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Disabled,414042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Acked,414042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almHighHigh.Alarm,414042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Fault,414052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almHigh.AlarmState,414052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almHigh.GlobalReset,414052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almHigh.FaultInAlarm,414052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almHigh.ALRM,414052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almHigh.ANUN,414052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almHigh.AKED,414052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almHigh.Resetable,414052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almHigh.REST,414052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almHigh.ACKN,414052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almHigh.UACK,414052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almHigh.MCmd_Enable,414052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almHigh.MCmd_Disable,414052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almHigh.OCmd_Shelve,414052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almHigh.OCmd_Unshelve,414052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almHigh.SCmd_Suppress,414052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almHigh.SCmd_UnSuppress,414053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almHigh.AEShelveTMRDN,414053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almHigh.Bad,414053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almHigh.Suppress,414054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.UnSuppress,414054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Shelve,414054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.UnShelve,414054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Enable,414054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Disable,414054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Ack,414054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Reset,414054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almHigh.Suppressed,414054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almHigh.Shelved,414054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almHigh.Disabled,414054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almHigh.Acked,414054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almHigh.Alarm,414054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Fault,414064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almLow.AlarmState,414064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almLow.GlobalReset,414064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almLow.FaultInAlarm,414064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almLow.ALRM,414064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almLow.ANUN,414064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almLow.AKED,414064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almLow.Resetable,414064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almLow.REST,414064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almLow.ACKN,414064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almLow.UACK,414064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almLow.MCmd_Enable,414064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almLow.MCmd_Disable,414064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almLow.OCmd_Shelve,414064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almLow.OCmd_Unshelve,414064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almLow.SCmd_Suppress,414064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almLow.SCmd_UnSuppress,414065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almLow.AEShelveTMRDN,414065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almLow.Bad,414065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almLow.Suppress,414066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.UnSuppress,414066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Shelve,414066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.UnShelve,414066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Enable,414066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Disable,414066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Ack,414066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Reset,414066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almLow.Suppressed,414066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almLow.Shelved,414066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almLow.Disabled,414066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almLow.Acked,414066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almLow.Alarm,414066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Fault,414076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almLowLow.AlarmState,414076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almLowLow.GlobalReset,414076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almLowLow.FaultInAlarm,414076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almLowLow.ALRM,414076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almLowLow.ANUN,414076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almLowLow.AKED,414076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almLowLow.Resetable,414076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almLowLow.REST,414076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almLowLow.ACKN,414076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almLowLow.UACK,414076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almLowLow.MCmd_Enable,414076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almLowLow.MCmd_Disable,414076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almLowLow.OCmd_Shelve,414076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almLowLow.OCmd_Unshelve,414076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almLowLow.SCmd_Suppress,414076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almLowLow.SCmd_UnSuppress,414077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almLowLow.AEShelveTMRDN,414077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almLowLow.Bad,414077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almLowLow.Suppress,414078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.UnSuppress,414078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Shelve,414078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.UnShelve,414078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Enable,414078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Disable,414078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Ack,414078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Reset,414078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Suppressed,414078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Shelved,414078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Disabled,414078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Acked,414078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almLowLow.Alarm,414078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Fault,414088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almBrokenLoop.AlarmState,414088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almBrokenLoop.GlobalReset,414088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almBrokenLoop.FaultInAlarm,414088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almBrokenLoop.ALRM,414088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almBrokenLoop.ANUN,414088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almBrokenLoop.AKED,414088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almBrokenLoop.Resetable,414088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almBrokenLoop.REST,414088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almBrokenLoop.ACKN,414088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almBrokenLoop.UACK,414088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almBrokenLoop.MCmd_Enable,414088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.MCmd_Disable,414088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.OCmd_Shelve,414088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.OCmd_Unshelve,414088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.SCmd_Suppress,414088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.SCmd_UnSuppress,414089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almBrokenLoop.AEShelveTMRDN,414089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almBrokenLoop.Bad,414089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almBrokenLoop.Suppress,414090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.UnSuppress,414090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Shelve,414090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.UnShelve,414090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Enable,414090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Disable,414090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Ack,414090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Reset,414090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Suppressed,414090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Shelved,414090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Disabled,414090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Acked,414090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.Alarm,414090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Fault,414100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almOverRange.AlarmState,414100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almOverRange.GlobalReset,414100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almOverRange.FaultInAlarm,414100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almOverRange.ALRM,414100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almOverRange.ANUN,414100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almOverRange.AKED,414100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almOverRange.Resetable,414100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almOverRange.REST,414100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almOverRange.ACKN,414100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almOverRange.UACK,414100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almOverRange.MCmd_Enable,414100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almOverRange.MCmd_Disable,414100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almOverRange.OCmd_Shelve,414100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almOverRange.OCmd_Unshelve,414100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almOverRange.SCmd_Suppress,414100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almOverRange.SCmd_UnSuppress,414101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almOverRange.AEShelveTMRDN,414101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almOverRange.Bad,414101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almOverRange.Suppress,414102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.UnSuppress,414102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Shelve,414102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.UnShelve,414102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Enable,414102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Disable,414102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Ack,414102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Reset,414102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Suppressed,414102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Shelved,414102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Disabled,414102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Acked,414102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almOverRange.Alarm,414102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Fault,414112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almUnderRange.AlarmState,414112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almUnderRange.GlobalReset,414112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almUnderRange.FaultInAlarm,414112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almUnderRange.ALRM,414112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almUnderRange.ANUN,414112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almUnderRange.AKED,414112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almUnderRange.Resetable,414112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almUnderRange.REST,414112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almUnderRange.ACKN,414112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almUnderRange.UACK,414112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almUnderRange.MCmd_Enable,414112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.MCmd_Disable,414112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.OCmd_Shelve,414112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.OCmd_Unshelve,414112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.SCmd_Suppress,414112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.SCmd_UnSuppress,414113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almUnderRange.AEShelveTMRDN,414113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almUnderRange.Bad,414113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almUnderRange.Suppress,414114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.UnSuppress,414114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Shelve,414114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.UnShelve,414114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Enable,414114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Disable,414114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Ack,414114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Reset,414114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Suppressed,414114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Shelved,414114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Disabled,414114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Acked,414114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almUnderRange.Alarm,414114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Fault,414124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almRateOfChange.AlarmState,414124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almRateOfChange.GlobalReset,414124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almRateOfChange.FaultInAlarm,414124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almRateOfChange.ALRM,414124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almRateOfChange.ANUN,414124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almRateOfChange.AKED,414124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almRateOfChange.Resetable,414124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almRateOfChange.REST,414124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almRateOfChange.ACKN,414124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almRateOfChange.UACK,414124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almRateOfChange.MCmd_Enable,414124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.MCmd_Disable,414124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.OCmd_Shelve,414124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.OCmd_Unshelve,414124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.SCmd_Suppress,414124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.SCmd_UnSuppress,414125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almRateOfChange.AEShelveTMRDN,414125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almRateOfChange.Bad,414125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almRateOfChange.Suppress,414126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.UnSuppress,414126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Shelve,414126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.UnShelve,414126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Enable,414126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Disable,414126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Ack,414126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Reset,414126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Suppressed,414126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Shelved,414126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Disabled,414126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Acked,414126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almRateOfChange.Alarm,414126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Fault,414136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_MTR_0103_9_VI4.almPLCFault.AlarmState,414136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_MTR_0103_9_VI4.almPLCFault.GlobalReset,414136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_MTR_0103_9_VI4.almPLCFault.FaultInAlarm,414136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_MTR_0103_9_VI4.almPLCFault.ALRM,414136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_MTR_0103_9_VI4.almPLCFault.ANUN,414136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_MTR_0103_9_VI4.almPLCFault.AKED,414136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_MTR_0103_9_VI4.almPLCFault.Resetable,414136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_MTR_0103_9_VI4.almPLCFault.REST,414136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_MTR_0103_9_VI4.almPLCFault.ACKN,414136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_MTR_0103_9_VI4.almPLCFault.UACK,414136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_MTR_0103_9_VI4.almPLCFault.MCmd_Enable,414136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.MCmd_Disable,414136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.OCmd_Shelve,414136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.OCmd_Unshelve,414136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.SCmd_Suppress,414136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.SCmd_UnSuppress,414137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_MTR_0103_9_VI4.almPLCFault.AEShelveTMRDN,414137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_MTR_0103_9_VI4.almPLCFault.Bad,414137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_MTR_0103_9_VI4.almPLCFault.Suppress,414138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.UnSuppress,414138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Shelve,414138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.UnShelve,414138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Enable,414138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Disable,414138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Ack,414138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Reset,414138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Suppressed,414138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Shelved,414138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Disabled,414138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Acked,414138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_MTR_0103_9_VI4.almPLCFault.Alarm,414138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Fault,414240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almHighHigh.AlarmState,414240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almHighHigh.GlobalReset,414240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almHighHigh.FaultInAlarm,414240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almHighHigh.ALRM,414240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almHighHigh.ANUN,414240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almHighHigh.AKED,414240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almHighHigh.Resetable,414240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almHighHigh.REST,414240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almHighHigh.ACKN,414240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almHighHigh.UACK,414240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almHighHigh.MCmd_Enable,414240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almHighHigh.MCmd_Disable,414240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almHighHigh.OCmd_Shelve,414240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almHighHigh.OCmd_Unshelve,414240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almHighHigh.SCmd_Suppress,414240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almHighHigh.SCmd_UnSuppress,414241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almHighHigh.AEShelveTMRDN,414241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almHighHigh.Bad,414241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almHighHigh.Suppress,414242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.UnSuppress,414242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Shelve,414242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.UnShelve,414242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Enable,414242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Disable,414242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Ack,414242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Reset,414242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Suppressed,414242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Shelved,414242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Disabled,414242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Acked,414242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almHighHigh.Alarm,414242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Fault,414252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almHigh.AlarmState,414252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almHigh.GlobalReset,414252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almHigh.FaultInAlarm,414252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almHigh.ALRM,414252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almHigh.ANUN,414252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almHigh.AKED,414252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almHigh.Resetable,414252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almHigh.REST,414252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almHigh.ACKN,414252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almHigh.UACK,414252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almHigh.MCmd_Enable,414252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almHigh.MCmd_Disable,414252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almHigh.OCmd_Shelve,414252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almHigh.OCmd_Unshelve,414252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almHigh.SCmd_Suppress,414252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almHigh.SCmd_UnSuppress,414253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almHigh.AEShelveTMRDN,414253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almHigh.Bad,414253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almHigh.Suppress,414254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.UnSuppress,414254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Shelve,414254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.UnShelve,414254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Enable,414254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Disable,414254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Ack,414254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Reset,414254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almHigh.Suppressed,414254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almHigh.Shelved,414254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almHigh.Disabled,414254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almHigh.Acked,414254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almHigh.Alarm,414254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Fault,414264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almLow.AlarmState,414264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almLow.GlobalReset,414264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almLow.FaultInAlarm,414264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almLow.ALRM,414264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almLow.ANUN,414264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almLow.AKED,414264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almLow.Resetable,414264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almLow.REST,414264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almLow.ACKN,414264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almLow.UACK,414264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almLow.MCmd_Enable,414264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almLow.MCmd_Disable,414264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almLow.OCmd_Shelve,414264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almLow.OCmd_Unshelve,414264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almLow.SCmd_Suppress,414264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almLow.SCmd_UnSuppress,414265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almLow.AEShelveTMRDN,414265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almLow.Bad,414265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almLow.Suppress,414266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.UnSuppress,414266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Shelve,414266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.UnShelve,414266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Enable,414266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Disable,414266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Ack,414266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Reset,414266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almLow.Suppressed,414266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almLow.Shelved,414266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almLow.Disabled,414266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almLow.Acked,414266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almLow.Alarm,414266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Fault,414276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almLowLow.AlarmState,414276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almLowLow.GlobalReset,414276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almLowLow.FaultInAlarm,414276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almLowLow.ALRM,414276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almLowLow.ANUN,414276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almLowLow.AKED,414276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almLowLow.Resetable,414276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almLowLow.REST,414276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almLowLow.ACKN,414276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almLowLow.UACK,414276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almLowLow.MCmd_Enable,414276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almLowLow.MCmd_Disable,414276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almLowLow.OCmd_Shelve,414276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almLowLow.OCmd_Unshelve,414276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almLowLow.SCmd_Suppress,414276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almLowLow.SCmd_UnSuppress,414277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almLowLow.AEShelveTMRDN,414277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almLowLow.Bad,414277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almLowLow.Suppress,414278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.UnSuppress,414278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Shelve,414278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.UnShelve,414278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Enable,414278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Disable,414278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Ack,414278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Reset,414278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almLowLow.Suppressed,414278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almLowLow.Shelved,414278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almLowLow.Disabled,414278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almLowLow.Acked,414278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almLowLow.Alarm,414278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Fault,414288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almBrokenLoop.AlarmState,414288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almBrokenLoop.GlobalReset,414288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almBrokenLoop.FaultInAlarm,414288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almBrokenLoop.ALRM,414288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almBrokenLoop.ANUN,414288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almBrokenLoop.AKED,414288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almBrokenLoop.Resetable,414288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almBrokenLoop.REST,414288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almBrokenLoop.ACKN,414288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almBrokenLoop.UACK,414288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almBrokenLoop.MCmd_Enable,414288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.MCmd_Disable,414288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.OCmd_Shelve,414288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.OCmd_Unshelve,414288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.SCmd_Suppress,414288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.SCmd_UnSuppress,414289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almBrokenLoop.AEShelveTMRDN,414289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almBrokenLoop.Bad,414289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almBrokenLoop.Suppress,414290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.UnSuppress,414290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Shelve,414290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.UnShelve,414290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Enable,414290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Disable,414290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Ack,414290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Reset,414290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Suppressed,414290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Shelved,414290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Disabled,414290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Acked,414290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almBrokenLoop.Alarm,414290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Fault,414300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almOverRange.AlarmState,414300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almOverRange.GlobalReset,414300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almOverRange.FaultInAlarm,414300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almOverRange.ALRM,414300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almOverRange.ANUN,414300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almOverRange.AKED,414300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almOverRange.Resetable,414300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almOverRange.REST,414300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almOverRange.ACKN,414300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almOverRange.UACK,414300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almOverRange.MCmd_Enable,414300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almOverRange.MCmd_Disable,414300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almOverRange.OCmd_Shelve,414300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almOverRange.OCmd_Unshelve,414300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almOverRange.SCmd_Suppress,414300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almOverRange.SCmd_UnSuppress,414301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almOverRange.AEShelveTMRDN,414301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almOverRange.Bad,414301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almOverRange.Suppress,414302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.UnSuppress,414302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Shelve,414302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.UnShelve,414302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Enable,414302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Disable,414302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Ack,414302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Reset,414302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almOverRange.Suppressed,414302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almOverRange.Shelved,414302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almOverRange.Disabled,414302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almOverRange.Acked,414302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almOverRange.Alarm,414302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Fault,414312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almUnderRange.AlarmState,414312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almUnderRange.GlobalReset,414312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almUnderRange.FaultInAlarm,414312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almUnderRange.ALRM,414312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almUnderRange.ANUN,414312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almUnderRange.AKED,414312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almUnderRange.Resetable,414312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almUnderRange.REST,414312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almUnderRange.ACKN,414312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almUnderRange.UACK,414312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almUnderRange.MCmd_Enable,414312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almUnderRange.MCmd_Disable,414312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almUnderRange.OCmd_Shelve,414312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almUnderRange.OCmd_Unshelve,414312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almUnderRange.SCmd_Suppress,414312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almUnderRange.SCmd_UnSuppress,414313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almUnderRange.AEShelveTMRDN,414313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almUnderRange.Bad,414313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almUnderRange.Suppress,414314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.UnSuppress,414314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Shelve,414314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.UnShelve,414314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Enable,414314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Disable,414314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Ack,414314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Reset,414314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Suppressed,414314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Shelved,414314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Disabled,414314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Acked,414314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almUnderRange.Alarm,414314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Fault,414324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almRateOfChange.AlarmState,414324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almRateOfChange.GlobalReset,414324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almRateOfChange.FaultInAlarm,414324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almRateOfChange.ALRM,414324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almRateOfChange.ANUN,414324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almRateOfChange.AKED,414324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almRateOfChange.Resetable,414324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almRateOfChange.REST,414324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almRateOfChange.ACKN,414324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almRateOfChange.UACK,414324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almRateOfChange.MCmd_Enable,414324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.MCmd_Disable,414324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.OCmd_Shelve,414324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.OCmd_Unshelve,414324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.SCmd_Suppress,414324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.SCmd_UnSuppress,414325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almRateOfChange.AEShelveTMRDN,414325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almRateOfChange.Bad,414325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almRateOfChange.Suppress,414326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.UnSuppress,414326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Shelve,414326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.UnShelve,414326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Enable,414326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Disable,414326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Ack,414326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Reset,414326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Suppressed,414326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Shelved,414326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Disabled,414326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Acked,414326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almRateOfChange.Alarm,414326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Fault,414336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PI.almPLCFault.AlarmState,414336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PI.almPLCFault.GlobalReset,414336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PI.almPLCFault.FaultInAlarm,414336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PI.almPLCFault.ALRM,414336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PI.almPLCFault.ANUN,414336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PI.almPLCFault.AKED,414336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PI.almPLCFault.Resetable,414336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PI.almPLCFault.REST,414336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PI.almPLCFault.ACKN,414336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PI.almPLCFault.UACK,414336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PI.almPLCFault.MCmd_Enable,414336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PI.almPLCFault.MCmd_Disable,414336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PI.almPLCFault.OCmd_Shelve,414336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PI.almPLCFault.OCmd_Unshelve,414336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PI.almPLCFault.SCmd_Suppress,414336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PI.almPLCFault.SCmd_UnSuppress,414337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PI.almPLCFault.AEShelveTMRDN,414337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PI.almPLCFault.Bad,414337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PI.almPLCFault.Suppress,414338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.UnSuppress,414338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Shelve,414338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.UnShelve,414338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Enable,414338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Disable,414338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Ack,414338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Reset,414338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Suppressed,414338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Shelved,414338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Disabled,414338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Acked,414338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PI.almPLCFault.Alarm,414338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Fault,414440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almHighHigh.AlarmState,414440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almHighHigh.GlobalReset,414440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almHighHigh.FaultInAlarm,414440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almHighHigh.ALRM,414440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almHighHigh.ANUN,414440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almHighHigh.AKED,414440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almHighHigh.Resetable,414440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almHighHigh.REST,414440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almHighHigh.ACKN,414440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almHighHigh.UACK,414440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almHighHigh.MCmd_Enable,414440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almHighHigh.MCmd_Disable,414440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almHighHigh.OCmd_Shelve,414440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almHighHigh.OCmd_Unshelve,414440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almHighHigh.SCmd_Suppress,414440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almHighHigh.SCmd_UnSuppress,414441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almHighHigh.AEShelveTMRDN,414441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almHighHigh.Bad,414441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almHighHigh.Suppress,414442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.UnSuppress,414442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Shelve,414442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.UnShelve,414442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Enable,414442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Disable,414442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Ack,414442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Reset,414442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Suppressed,414442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Shelved,414442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Disabled,414442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Acked,414442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almHighHigh.Alarm,414442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Fault,414452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almHigh.AlarmState,414452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almHigh.GlobalReset,414452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almHigh.FaultInAlarm,414452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almHigh.ALRM,414452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almHigh.ANUN,414452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almHigh.AKED,414452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almHigh.Resetable,414452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almHigh.REST,414452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almHigh.ACKN,414452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almHigh.UACK,414452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almHigh.MCmd_Enable,414452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almHigh.MCmd_Disable,414452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almHigh.OCmd_Shelve,414452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almHigh.OCmd_Unshelve,414452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almHigh.SCmd_Suppress,414452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almHigh.SCmd_UnSuppress,414453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almHigh.AEShelveTMRDN,414453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almHigh.Bad,414453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almHigh.Suppress,414454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.UnSuppress,414454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Shelve,414454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.UnShelve,414454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Enable,414454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Disable,414454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Ack,414454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Reset,414454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almHigh.Suppressed,414454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almHigh.Shelved,414454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almHigh.Disabled,414454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almHigh.Acked,414454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almHigh.Alarm,414454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Fault,414464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almLow.AlarmState,414464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almLow.GlobalReset,414464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almLow.FaultInAlarm,414464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almLow.ALRM,414464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almLow.ANUN,414464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almLow.AKED,414464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almLow.Resetable,414464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almLow.REST,414464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almLow.ACKN,414464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almLow.UACK,414464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almLow.MCmd_Enable,414464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almLow.MCmd_Disable,414464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almLow.OCmd_Shelve,414464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almLow.OCmd_Unshelve,414464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almLow.SCmd_Suppress,414464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almLow.SCmd_UnSuppress,414465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almLow.AEShelveTMRDN,414465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almLow.Bad,414465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almLow.Suppress,414466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.UnSuppress,414466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Shelve,414466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.UnShelve,414466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Enable,414466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Disable,414466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Ack,414466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Reset,414466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almLow.Suppressed,414466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almLow.Shelved,414466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almLow.Disabled,414466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almLow.Acked,414466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almLow.Alarm,414466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Fault,414476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almLowLow.AlarmState,414476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almLowLow.GlobalReset,414476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almLowLow.FaultInAlarm,414476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almLowLow.ALRM,414476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almLowLow.ANUN,414476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almLowLow.AKED,414476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almLowLow.Resetable,414476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almLowLow.REST,414476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almLowLow.ACKN,414476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almLowLow.UACK,414476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almLowLow.MCmd_Enable,414476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almLowLow.MCmd_Disable,414476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almLowLow.OCmd_Shelve,414476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almLowLow.OCmd_Unshelve,414476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almLowLow.SCmd_Suppress,414476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almLowLow.SCmd_UnSuppress,414477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almLowLow.AEShelveTMRDN,414477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almLowLow.Bad,414477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almLowLow.Suppress,414478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.UnSuppress,414478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Shelve,414478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.UnShelve,414478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Enable,414478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Disable,414478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Ack,414478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Reset,414478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almLowLow.Suppressed,414478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almLowLow.Shelved,414478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almLowLow.Disabled,414478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almLowLow.Acked,414478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almLowLow.Alarm,414478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Fault,414488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almBrokenLoop.AlarmState,414488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almBrokenLoop.GlobalReset,414488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almBrokenLoop.FaultInAlarm,414488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almBrokenLoop.ALRM,414488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almBrokenLoop.ANUN,414488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almBrokenLoop.AKED,414488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almBrokenLoop.Resetable,414488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almBrokenLoop.REST,414488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almBrokenLoop.ACKN,414488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almBrokenLoop.UACK,414488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almBrokenLoop.MCmd_Enable,414488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.MCmd_Disable,414488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.OCmd_Shelve,414488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.OCmd_Unshelve,414488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.SCmd_Suppress,414488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.SCmd_UnSuppress,414489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almBrokenLoop.AEShelveTMRDN,414489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almBrokenLoop.Bad,414489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almBrokenLoop.Suppress,414490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.UnSuppress,414490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Shelve,414490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.UnShelve,414490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Enable,414490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Disable,414490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Ack,414490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Reset,414490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Suppressed,414490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Shelved,414490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Disabled,414490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Acked,414490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almBrokenLoop.Alarm,414490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Fault,414500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almOverRange.AlarmState,414500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almOverRange.GlobalReset,414500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almOverRange.FaultInAlarm,414500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almOverRange.ALRM,414500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almOverRange.ANUN,414500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almOverRange.AKED,414500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almOverRange.Resetable,414500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almOverRange.REST,414500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almOverRange.ACKN,414500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almOverRange.UACK,414500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almOverRange.MCmd_Enable,414500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almOverRange.MCmd_Disable,414500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almOverRange.OCmd_Shelve,414500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almOverRange.OCmd_Unshelve,414500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almOverRange.SCmd_Suppress,414500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almOverRange.SCmd_UnSuppress,414501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almOverRange.AEShelveTMRDN,414501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almOverRange.Bad,414501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almOverRange.Suppress,414502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.UnSuppress,414502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Shelve,414502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.UnShelve,414502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Enable,414502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Disable,414502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Ack,414502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Reset,414502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almOverRange.Suppressed,414502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almOverRange.Shelved,414502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almOverRange.Disabled,414502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almOverRange.Acked,414502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almOverRange.Alarm,414502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Fault,414512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almUnderRange.AlarmState,414512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almUnderRange.GlobalReset,414512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almUnderRange.FaultInAlarm,414512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almUnderRange.ALRM,414512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almUnderRange.ANUN,414512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almUnderRange.AKED,414512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almUnderRange.Resetable,414512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almUnderRange.REST,414512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almUnderRange.ACKN,414512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almUnderRange.UACK,414512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almUnderRange.MCmd_Enable,414512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almUnderRange.MCmd_Disable,414512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almUnderRange.OCmd_Shelve,414512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almUnderRange.OCmd_Unshelve,414512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almUnderRange.SCmd_Suppress,414512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almUnderRange.SCmd_UnSuppress,414513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almUnderRange.AEShelveTMRDN,414513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almUnderRange.Bad,414513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almUnderRange.Suppress,414514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.UnSuppress,414514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Shelve,414514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.UnShelve,414514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Enable,414514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Disable,414514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Ack,414514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Reset,414514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Suppressed,414514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Shelved,414514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Disabled,414514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Acked,414514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almUnderRange.Alarm,414514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Fault,414524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almRateOfChange.AlarmState,414524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almRateOfChange.GlobalReset,414524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almRateOfChange.FaultInAlarm,414524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almRateOfChange.ALRM,414524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almRateOfChange.ANUN,414524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almRateOfChange.AKED,414524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almRateOfChange.Resetable,414524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almRateOfChange.REST,414524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almRateOfChange.ACKN,414524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almRateOfChange.UACK,414524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almRateOfChange.MCmd_Enable,414524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.MCmd_Disable,414524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.OCmd_Shelve,414524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.OCmd_Unshelve,414524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.SCmd_Suppress,414524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.SCmd_UnSuppress,414525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almRateOfChange.AEShelveTMRDN,414525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almRateOfChange.Bad,414525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almRateOfChange.Suppress,414526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.UnSuppress,414526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Shelve,414526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.UnShelve,414526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Enable,414526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Disable,414526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Ack,414526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Reset,414526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Suppressed,414526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Shelved,414526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Disabled,414526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Acked,414526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almRateOfChange.Alarm,414526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Fault,414536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PI.almPLCFault.AlarmState,414536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PI.almPLCFault.GlobalReset,414536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PI.almPLCFault.FaultInAlarm,414536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PI.almPLCFault.ALRM,414536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PI.almPLCFault.ANUN,414536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PI.almPLCFault.AKED,414536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PI.almPLCFault.Resetable,414536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PI.almPLCFault.REST,414536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PI.almPLCFault.ACKN,414536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PI.almPLCFault.UACK,414536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PI.almPLCFault.MCmd_Enable,414536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PI.almPLCFault.MCmd_Disable,414536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PI.almPLCFault.OCmd_Shelve,414536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PI.almPLCFault.OCmd_Unshelve,414536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PI.almPLCFault.SCmd_Suppress,414536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PI.almPLCFault.SCmd_UnSuppress,414537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PI.almPLCFault.AEShelveTMRDN,414537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PI.almPLCFault.Bad,414537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PI.almPLCFault.Suppress,414538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.UnSuppress,414538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Shelve,414538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.UnShelve,414538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Enable,414538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Disable,414538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Ack,414538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Reset,414538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Suppressed,414538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Shelved,414538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Disabled,414538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Acked,414538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PI.almPLCFault.Alarm,414538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Fault,414640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almHighHigh.AlarmState,414640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almHighHigh.GlobalReset,414640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almHighHigh.FaultInAlarm,414640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almHighHigh.ALRM,414640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almHighHigh.ANUN,414640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almHighHigh.AKED,414640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almHighHigh.Resetable,414640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almHighHigh.REST,414640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almHighHigh.ACKN,414640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almHighHigh.UACK,414640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almHighHigh.MCmd_Enable,414640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almHighHigh.MCmd_Disable,414640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almHighHigh.OCmd_Shelve,414640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almHighHigh.OCmd_Unshelve,414640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almHighHigh.SCmd_Suppress,414640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almHighHigh.SCmd_UnSuppress,414641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almHighHigh.AEShelveTMRDN,414641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almHighHigh.Bad,414641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almHighHigh.Suppress,414642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.UnSuppress,414642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Shelve,414642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.UnShelve,414642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Enable,414642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Disable,414642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Ack,414642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Reset,414642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Suppressed,414642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Shelved,414642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Disabled,414642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Acked,414642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almHighHigh.Alarm,414642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Fault,414652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almHigh.AlarmState,414652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almHigh.GlobalReset,414652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almHigh.FaultInAlarm,414652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almHigh.ALRM,414652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almHigh.ANUN,414652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almHigh.AKED,414652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almHigh.Resetable,414652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almHigh.REST,414652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almHigh.ACKN,414652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almHigh.UACK,414652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almHigh.MCmd_Enable,414652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almHigh.MCmd_Disable,414652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almHigh.OCmd_Shelve,414652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almHigh.OCmd_Unshelve,414652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almHigh.SCmd_Suppress,414652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almHigh.SCmd_UnSuppress,414653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almHigh.AEShelveTMRDN,414653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almHigh.Bad,414653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almHigh.Suppress,414654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.UnSuppress,414654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Shelve,414654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.UnShelve,414654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Enable,414654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Disable,414654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Ack,414654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Reset,414654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almHigh.Suppressed,414654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almHigh.Shelved,414654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almHigh.Disabled,414654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almHigh.Acked,414654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almHigh.Alarm,414654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Fault,414664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almLow.AlarmState,414664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almLow.GlobalReset,414664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almLow.FaultInAlarm,414664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almLow.ALRM,414664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almLow.ANUN,414664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almLow.AKED,414664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almLow.Resetable,414664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almLow.REST,414664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almLow.ACKN,414664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almLow.UACK,414664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almLow.MCmd_Enable,414664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almLow.MCmd_Disable,414664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almLow.OCmd_Shelve,414664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almLow.OCmd_Unshelve,414664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almLow.SCmd_Suppress,414664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almLow.SCmd_UnSuppress,414665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almLow.AEShelveTMRDN,414665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almLow.Bad,414665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almLow.Suppress,414666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.UnSuppress,414666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Shelve,414666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.UnShelve,414666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Enable,414666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Disable,414666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Ack,414666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Reset,414666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almLow.Suppressed,414666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almLow.Shelved,414666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almLow.Disabled,414666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almLow.Acked,414666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almLow.Alarm,414666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Fault,414676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almLowLow.AlarmState,414676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almLowLow.GlobalReset,414676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almLowLow.FaultInAlarm,414676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almLowLow.ALRM,414676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almLowLow.ANUN,414676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almLowLow.AKED,414676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almLowLow.Resetable,414676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almLowLow.REST,414676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almLowLow.ACKN,414676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almLowLow.UACK,414676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almLowLow.MCmd_Enable,414676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almLowLow.MCmd_Disable,414676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almLowLow.OCmd_Shelve,414676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almLowLow.OCmd_Unshelve,414676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almLowLow.SCmd_Suppress,414676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almLowLow.SCmd_UnSuppress,414677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almLowLow.AEShelveTMRDN,414677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almLowLow.Bad,414677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almLowLow.Suppress,414678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.UnSuppress,414678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Shelve,414678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.UnShelve,414678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Enable,414678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Disable,414678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Ack,414678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Reset,414678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almLowLow.Suppressed,414678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almLowLow.Shelved,414678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almLowLow.Disabled,414678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almLowLow.Acked,414678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almLowLow.Alarm,414678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Fault,414688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almBrokenLoop.AlarmState,414688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almBrokenLoop.GlobalReset,414688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almBrokenLoop.FaultInAlarm,414688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almBrokenLoop.ALRM,414688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almBrokenLoop.ANUN,414688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almBrokenLoop.AKED,414688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almBrokenLoop.Resetable,414688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almBrokenLoop.REST,414688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almBrokenLoop.ACKN,414688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almBrokenLoop.UACK,414688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almBrokenLoop.MCmd_Enable,414688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.MCmd_Disable,414688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.OCmd_Shelve,414688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.OCmd_Unshelve,414688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.SCmd_Suppress,414688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.SCmd_UnSuppress,414689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almBrokenLoop.AEShelveTMRDN,414689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almBrokenLoop.Bad,414689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almBrokenLoop.Suppress,414690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.UnSuppress,414690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Shelve,414690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.UnShelve,414690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Enable,414690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Disable,414690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Ack,414690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Reset,414690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Suppressed,414690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Shelved,414690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Disabled,414690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Acked,414690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almBrokenLoop.Alarm,414690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Fault,414700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almOverRange.AlarmState,414700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almOverRange.GlobalReset,414700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almOverRange.FaultInAlarm,414700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almOverRange.ALRM,414700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almOverRange.ANUN,414700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almOverRange.AKED,414700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almOverRange.Resetable,414700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almOverRange.REST,414700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almOverRange.ACKN,414700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almOverRange.UACK,414700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almOverRange.MCmd_Enable,414700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almOverRange.MCmd_Disable,414700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almOverRange.OCmd_Shelve,414700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almOverRange.OCmd_Unshelve,414700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almOverRange.SCmd_Suppress,414700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almOverRange.SCmd_UnSuppress,414701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almOverRange.AEShelveTMRDN,414701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almOverRange.Bad,414701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almOverRange.Suppress,414702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.UnSuppress,414702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Shelve,414702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.UnShelve,414702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Enable,414702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Disable,414702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Ack,414702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Reset,414702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almOverRange.Suppressed,414702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almOverRange.Shelved,414702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almOverRange.Disabled,414702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almOverRange.Acked,414702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almOverRange.Alarm,414702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Fault,414712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almUnderRange.AlarmState,414712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almUnderRange.GlobalReset,414712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almUnderRange.FaultInAlarm,414712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almUnderRange.ALRM,414712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almUnderRange.ANUN,414712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almUnderRange.AKED,414712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almUnderRange.Resetable,414712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almUnderRange.REST,414712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almUnderRange.ACKN,414712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almUnderRange.UACK,414712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almUnderRange.MCmd_Enable,414712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almUnderRange.MCmd_Disable,414712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almUnderRange.OCmd_Shelve,414712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almUnderRange.OCmd_Unshelve,414712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almUnderRange.SCmd_Suppress,414712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almUnderRange.SCmd_UnSuppress,414713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almUnderRange.AEShelveTMRDN,414713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almUnderRange.Bad,414713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almUnderRange.Suppress,414714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.UnSuppress,414714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Shelve,414714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.UnShelve,414714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Enable,414714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Disable,414714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Ack,414714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Reset,414714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Suppressed,414714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Shelved,414714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Disabled,414714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Acked,414714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almUnderRange.Alarm,414714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Fault,414724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almRateOfChange.AlarmState,414724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almRateOfChange.GlobalReset,414724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almRateOfChange.FaultInAlarm,414724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almRateOfChange.ALRM,414724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almRateOfChange.ANUN,414724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almRateOfChange.AKED,414724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almRateOfChange.Resetable,414724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almRateOfChange.REST,414724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almRateOfChange.ACKN,414724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almRateOfChange.UACK,414724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almRateOfChange.MCmd_Enable,414724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.MCmd_Disable,414724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.OCmd_Shelve,414724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.OCmd_Unshelve,414724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.SCmd_Suppress,414724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.SCmd_UnSuppress,414725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almRateOfChange.AEShelveTMRDN,414725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almRateOfChange.Bad,414725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almRateOfChange.Suppress,414726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.UnSuppress,414726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Shelve,414726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.UnShelve,414726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Enable,414726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Disable,414726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Ack,414726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Reset,414726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Suppressed,414726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Shelved,414726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Disabled,414726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Acked,414726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almRateOfChange.Alarm,414726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Fault,414736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_1_PI.almPLCFault.AlarmState,414736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_1_PI.almPLCFault.GlobalReset,414736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_1_PI.almPLCFault.FaultInAlarm,414736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_1_PI.almPLCFault.ALRM,414736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_1_PI.almPLCFault.ANUN,414736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_1_PI.almPLCFault.AKED,414736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_1_PI.almPLCFault.Resetable,414736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_1_PI.almPLCFault.REST,414736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_1_PI.almPLCFault.ACKN,414736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_1_PI.almPLCFault.UACK,414736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_1_PI.almPLCFault.MCmd_Enable,414736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_1_PI.almPLCFault.MCmd_Disable,414736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_1_PI.almPLCFault.OCmd_Shelve,414736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_1_PI.almPLCFault.OCmd_Unshelve,414736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_1_PI.almPLCFault.SCmd_Suppress,414736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_1_PI.almPLCFault.SCmd_UnSuppress,414737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_1_PI.almPLCFault.AEShelveTMRDN,414737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_1_PI.almPLCFault.Bad,414737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_1_PI.almPLCFault.Suppress,414738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.UnSuppress,414738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Shelve,414738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.UnShelve,414738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Enable,414738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Disable,414738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Ack,414738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Reset,414738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Suppressed,414738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Shelved,414738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Disabled,414738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Acked,414738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_1_PI.almPLCFault.Alarm,414738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Fault,414840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almHighHigh.AlarmState,414840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almHighHigh.GlobalReset,414840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almHighHigh.FaultInAlarm,414840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almHighHigh.ALRM,414840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almHighHigh.ANUN,414840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almHighHigh.AKED,414840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almHighHigh.Resetable,414840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almHighHigh.REST,414840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almHighHigh.ACKN,414840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almHighHigh.UACK,414840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almHighHigh.MCmd_Enable,414840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almHighHigh.MCmd_Disable,414840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almHighHigh.OCmd_Shelve,414840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almHighHigh.OCmd_Unshelve,414840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almHighHigh.SCmd_Suppress,414840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almHighHigh.SCmd_UnSuppress,414841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almHighHigh.AEShelveTMRDN,414841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almHighHigh.Bad,414841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almHighHigh.Suppress,414842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.UnSuppress,414842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Shelve,414842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.UnShelve,414842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Enable,414842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Disable,414842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Ack,414842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Reset,414842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Suppressed,414842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Shelved,414842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Disabled,414842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Acked,414842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almHighHigh.Alarm,414842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Fault,414852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almHigh.AlarmState,414852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almHigh.GlobalReset,414852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almHigh.FaultInAlarm,414852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almHigh.ALRM,414852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almHigh.ANUN,414852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almHigh.AKED,414852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almHigh.Resetable,414852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almHigh.REST,414852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almHigh.ACKN,414852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almHigh.UACK,414852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almHigh.MCmd_Enable,414852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almHigh.MCmd_Disable,414852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almHigh.OCmd_Shelve,414852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almHigh.OCmd_Unshelve,414852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almHigh.SCmd_Suppress,414852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almHigh.SCmd_UnSuppress,414853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almHigh.AEShelveTMRDN,414853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almHigh.Bad,414853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almHigh.Suppress,414854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.UnSuppress,414854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Shelve,414854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.UnShelve,414854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Enable,414854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Disable,414854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Ack,414854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Reset,414854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almHigh.Suppressed,414854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almHigh.Shelved,414854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almHigh.Disabled,414854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almHigh.Acked,414854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almHigh.Alarm,414854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Fault,414864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almLow.AlarmState,414864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almLow.GlobalReset,414864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almLow.FaultInAlarm,414864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almLow.ALRM,414864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almLow.ANUN,414864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almLow.AKED,414864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almLow.Resetable,414864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almLow.REST,414864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almLow.ACKN,414864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almLow.UACK,414864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almLow.MCmd_Enable,414864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almLow.MCmd_Disable,414864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almLow.OCmd_Shelve,414864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almLow.OCmd_Unshelve,414864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almLow.SCmd_Suppress,414864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almLow.SCmd_UnSuppress,414865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almLow.AEShelveTMRDN,414865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almLow.Bad,414865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almLow.Suppress,414866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.UnSuppress,414866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Shelve,414866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.UnShelve,414866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Enable,414866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Disable,414866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Ack,414866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Reset,414866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almLow.Suppressed,414866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almLow.Shelved,414866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almLow.Disabled,414866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almLow.Acked,414866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almLow.Alarm,414866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Fault,414876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almLowLow.AlarmState,414876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almLowLow.GlobalReset,414876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almLowLow.FaultInAlarm,414876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almLowLow.ALRM,414876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almLowLow.ANUN,414876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almLowLow.AKED,414876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almLowLow.Resetable,414876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almLowLow.REST,414876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almLowLow.ACKN,414876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almLowLow.UACK,414876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almLowLow.MCmd_Enable,414876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almLowLow.MCmd_Disable,414876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almLowLow.OCmd_Shelve,414876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almLowLow.OCmd_Unshelve,414876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almLowLow.SCmd_Suppress,414876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almLowLow.SCmd_UnSuppress,414877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almLowLow.AEShelveTMRDN,414877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almLowLow.Bad,414877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almLowLow.Suppress,414878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.UnSuppress,414878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Shelve,414878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.UnShelve,414878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Enable,414878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Disable,414878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Ack,414878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Reset,414878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almLowLow.Suppressed,414878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almLowLow.Shelved,414878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almLowLow.Disabled,414878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almLowLow.Acked,414878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almLowLow.Alarm,414878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Fault,414888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almBrokenLoop.AlarmState,414888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almBrokenLoop.GlobalReset,414888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almBrokenLoop.FaultInAlarm,414888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almBrokenLoop.ALRM,414888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almBrokenLoop.ANUN,414888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almBrokenLoop.AKED,414888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almBrokenLoop.Resetable,414888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almBrokenLoop.REST,414888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almBrokenLoop.ACKN,414888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almBrokenLoop.UACK,414888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almBrokenLoop.MCmd_Enable,414888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.MCmd_Disable,414888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.OCmd_Shelve,414888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.OCmd_Unshelve,414888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.SCmd_Suppress,414888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.SCmd_UnSuppress,414889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almBrokenLoop.AEShelveTMRDN,414889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almBrokenLoop.Bad,414889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almBrokenLoop.Suppress,414890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.UnSuppress,414890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Shelve,414890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.UnShelve,414890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Enable,414890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Disable,414890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Ack,414890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Reset,414890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Suppressed,414890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Shelved,414890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Disabled,414890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Acked,414890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almBrokenLoop.Alarm,414890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Fault,414900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almOverRange.AlarmState,414900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almOverRange.GlobalReset,414900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almOverRange.FaultInAlarm,414900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almOverRange.ALRM,414900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almOverRange.ANUN,414900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almOverRange.AKED,414900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almOverRange.Resetable,414900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almOverRange.REST,414900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almOverRange.ACKN,414900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almOverRange.UACK,414900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almOverRange.MCmd_Enable,414900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almOverRange.MCmd_Disable,414900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almOverRange.OCmd_Shelve,414900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almOverRange.OCmd_Unshelve,414900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almOverRange.SCmd_Suppress,414900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almOverRange.SCmd_UnSuppress,414901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almOverRange.AEShelveTMRDN,414901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almOverRange.Bad,414901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almOverRange.Suppress,414902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.UnSuppress,414902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Shelve,414902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.UnShelve,414902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Enable,414902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Disable,414902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Ack,414902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Reset,414902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almOverRange.Suppressed,414902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almOverRange.Shelved,414902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almOverRange.Disabled,414902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almOverRange.Acked,414902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almOverRange.Alarm,414902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Fault,414912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almUnderRange.AlarmState,414912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almUnderRange.GlobalReset,414912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almUnderRange.FaultInAlarm,414912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almUnderRange.ALRM,414912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almUnderRange.ANUN,414912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almUnderRange.AKED,414912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almUnderRange.Resetable,414912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almUnderRange.REST,414912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almUnderRange.ACKN,414912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almUnderRange.UACK,414912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almUnderRange.MCmd_Enable,414912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almUnderRange.MCmd_Disable,414912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almUnderRange.OCmd_Shelve,414912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almUnderRange.OCmd_Unshelve,414912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almUnderRange.SCmd_Suppress,414912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almUnderRange.SCmd_UnSuppress,414913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almUnderRange.AEShelveTMRDN,414913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almUnderRange.Bad,414913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almUnderRange.Suppress,414914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.UnSuppress,414914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Shelve,414914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.UnShelve,414914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Enable,414914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Disable,414914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Ack,414914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Reset,414914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Suppressed,414914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Shelved,414914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Disabled,414914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Acked,414914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almUnderRange.Alarm,414914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Fault,414924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almRateOfChange.AlarmState,414924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almRateOfChange.GlobalReset,414924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almRateOfChange.FaultInAlarm,414924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almRateOfChange.ALRM,414924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almRateOfChange.ANUN,414924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almRateOfChange.AKED,414924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almRateOfChange.Resetable,414924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almRateOfChange.REST,414924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almRateOfChange.ACKN,414924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almRateOfChange.UACK,414924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almRateOfChange.MCmd_Enable,414924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.MCmd_Disable,414924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.OCmd_Shelve,414924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.OCmd_Unshelve,414924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.SCmd_Suppress,414924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.SCmd_UnSuppress,414925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almRateOfChange.AEShelveTMRDN,414925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almRateOfChange.Bad,414925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almRateOfChange.Suppress,414926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.UnSuppress,414926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Shelve,414926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.UnShelve,414926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Enable,414926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Disable,414926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Ack,414926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Reset,414926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Suppressed,414926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Shelved,414926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Disabled,414926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Acked,414926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almRateOfChange.Alarm,414926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Fault,414936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_2_PI.almPLCFault.AlarmState,414936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_2_PI.almPLCFault.GlobalReset,414936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_2_PI.almPLCFault.FaultInAlarm,414936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_2_PI.almPLCFault.ALRM,414936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_2_PI.almPLCFault.ANUN,414936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_2_PI.almPLCFault.AKED,414936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_2_PI.almPLCFault.Resetable,414936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_2_PI.almPLCFault.REST,414936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_2_PI.almPLCFault.ACKN,414936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_2_PI.almPLCFault.UACK,414936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_2_PI.almPLCFault.MCmd_Enable,414936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_2_PI.almPLCFault.MCmd_Disable,414936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_2_PI.almPLCFault.OCmd_Shelve,414936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_2_PI.almPLCFault.OCmd_Unshelve,414936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_2_PI.almPLCFault.SCmd_Suppress,414936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_2_PI.almPLCFault.SCmd_UnSuppress,414937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_2_PI.almPLCFault.AEShelveTMRDN,414937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_2_PI.almPLCFault.Bad,414937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_2_PI.almPLCFault.Suppress,414938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.UnSuppress,414938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Shelve,414938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.UnShelve,414938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Enable,414938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Disable,414938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Ack,414938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Reset,414938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Suppressed,414938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Shelved,414938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Disabled,414938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Acked,414938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_2_PI.almPLCFault.Alarm,414938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Fault,415040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almHighHigh.AlarmState,415040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almHighHigh.GlobalReset,415040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almHighHigh.FaultInAlarm,415040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almHighHigh.ALRM,415040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almHighHigh.ANUN,415040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almHighHigh.AKED,415040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almHighHigh.Resetable,415040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almHighHigh.REST,415040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almHighHigh.ACKN,415040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almHighHigh.UACK,415040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almHighHigh.MCmd_Enable,415040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almHighHigh.MCmd_Disable,415040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almHighHigh.OCmd_Shelve,415040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almHighHigh.OCmd_Unshelve,415040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almHighHigh.SCmd_Suppress,415040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almHighHigh.SCmd_UnSuppress,415041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almHighHigh.AEShelveTMRDN,415041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almHighHigh.Bad,415041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almHighHigh.Suppress,415042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.UnSuppress,415042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Shelve,415042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.UnShelve,415042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Enable,415042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Disable,415042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Ack,415042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Reset,415042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Suppressed,415042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Shelved,415042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Disabled,415042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Acked,415042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almHighHigh.Alarm,415042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Fault,415052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almHigh.AlarmState,415052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almHigh.GlobalReset,415052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almHigh.FaultInAlarm,415052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almHigh.ALRM,415052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almHigh.ANUN,415052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almHigh.AKED,415052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almHigh.Resetable,415052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almHigh.REST,415052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almHigh.ACKN,415052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almHigh.UACK,415052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almHigh.MCmd_Enable,415052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almHigh.MCmd_Disable,415052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almHigh.OCmd_Shelve,415052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almHigh.OCmd_Unshelve,415052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almHigh.SCmd_Suppress,415052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almHigh.SCmd_UnSuppress,415053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almHigh.AEShelveTMRDN,415053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almHigh.Bad,415053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almHigh.Suppress,415054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.UnSuppress,415054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Shelve,415054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.UnShelve,415054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Enable,415054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Disable,415054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Ack,415054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Reset,415054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almHigh.Suppressed,415054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almHigh.Shelved,415054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almHigh.Disabled,415054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almHigh.Acked,415054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almHigh.Alarm,415054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Fault,415064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almLow.AlarmState,415064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almLow.GlobalReset,415064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almLow.FaultInAlarm,415064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almLow.ALRM,415064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almLow.ANUN,415064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almLow.AKED,415064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almLow.Resetable,415064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almLow.REST,415064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almLow.ACKN,415064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almLow.UACK,415064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almLow.MCmd_Enable,415064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almLow.MCmd_Disable,415064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almLow.OCmd_Shelve,415064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almLow.OCmd_Unshelve,415064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almLow.SCmd_Suppress,415064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almLow.SCmd_UnSuppress,415065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almLow.AEShelveTMRDN,415065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almLow.Bad,415065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almLow.Suppress,415066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.UnSuppress,415066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Shelve,415066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.UnShelve,415066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Enable,415066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Disable,415066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Ack,415066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Reset,415066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almLow.Suppressed,415066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almLow.Shelved,415066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almLow.Disabled,415066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almLow.Acked,415066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almLow.Alarm,415066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Fault,415076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almLowLow.AlarmState,415076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almLowLow.GlobalReset,415076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almLowLow.FaultInAlarm,415076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almLowLow.ALRM,415076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almLowLow.ANUN,415076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almLowLow.AKED,415076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almLowLow.Resetable,415076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almLowLow.REST,415076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almLowLow.ACKN,415076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almLowLow.UACK,415076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almLowLow.MCmd_Enable,415076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almLowLow.MCmd_Disable,415076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almLowLow.OCmd_Shelve,415076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almLowLow.OCmd_Unshelve,415076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almLowLow.SCmd_Suppress,415076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almLowLow.SCmd_UnSuppress,415077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almLowLow.AEShelveTMRDN,415077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almLowLow.Bad,415077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almLowLow.Suppress,415078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.UnSuppress,415078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Shelve,415078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.UnShelve,415078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Enable,415078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Disable,415078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Ack,415078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Reset,415078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almLowLow.Suppressed,415078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almLowLow.Shelved,415078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almLowLow.Disabled,415078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almLowLow.Acked,415078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almLowLow.Alarm,415078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Fault,415088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almBrokenLoop.AlarmState,415088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almBrokenLoop.GlobalReset,415088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almBrokenLoop.FaultInAlarm,415088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almBrokenLoop.ALRM,415088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almBrokenLoop.ANUN,415088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almBrokenLoop.AKED,415088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almBrokenLoop.Resetable,415088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almBrokenLoop.REST,415088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almBrokenLoop.ACKN,415088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almBrokenLoop.UACK,415088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almBrokenLoop.MCmd_Enable,415088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.MCmd_Disable,415088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.OCmd_Shelve,415088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.OCmd_Unshelve,415088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.SCmd_Suppress,415088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.SCmd_UnSuppress,415089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almBrokenLoop.AEShelveTMRDN,415089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almBrokenLoop.Bad,415089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almBrokenLoop.Suppress,415090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.UnSuppress,415090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Shelve,415090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.UnShelve,415090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Enable,415090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Disable,415090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Ack,415090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Reset,415090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Suppressed,415090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Shelved,415090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Disabled,415090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Acked,415090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almBrokenLoop.Alarm,415090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Fault,415100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almOverRange.AlarmState,415100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almOverRange.GlobalReset,415100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almOverRange.FaultInAlarm,415100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almOverRange.ALRM,415100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almOverRange.ANUN,415100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almOverRange.AKED,415100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almOverRange.Resetable,415100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almOverRange.REST,415100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almOverRange.ACKN,415100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almOverRange.UACK,415100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almOverRange.MCmd_Enable,415100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almOverRange.MCmd_Disable,415100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almOverRange.OCmd_Shelve,415100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almOverRange.OCmd_Unshelve,415100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almOverRange.SCmd_Suppress,415100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almOverRange.SCmd_UnSuppress,415101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almOverRange.AEShelveTMRDN,415101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almOverRange.Bad,415101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almOverRange.Suppress,415102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.UnSuppress,415102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Shelve,415102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.UnShelve,415102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Enable,415102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Disable,415102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Ack,415102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Reset,415102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almOverRange.Suppressed,415102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almOverRange.Shelved,415102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almOverRange.Disabled,415102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almOverRange.Acked,415102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almOverRange.Alarm,415102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Fault,415112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almUnderRange.AlarmState,415112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almUnderRange.GlobalReset,415112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almUnderRange.FaultInAlarm,415112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almUnderRange.ALRM,415112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almUnderRange.ANUN,415112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almUnderRange.AKED,415112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almUnderRange.Resetable,415112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almUnderRange.REST,415112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almUnderRange.ACKN,415112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almUnderRange.UACK,415112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almUnderRange.MCmd_Enable,415112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almUnderRange.MCmd_Disable,415112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almUnderRange.OCmd_Shelve,415112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almUnderRange.OCmd_Unshelve,415112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almUnderRange.SCmd_Suppress,415112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almUnderRange.SCmd_UnSuppress,415113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almUnderRange.AEShelveTMRDN,415113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almUnderRange.Bad,415113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almUnderRange.Suppress,415114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.UnSuppress,415114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Shelve,415114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.UnShelve,415114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Enable,415114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Disable,415114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Ack,415114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Reset,415114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Suppressed,415114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Shelved,415114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Disabled,415114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Acked,415114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almUnderRange.Alarm,415114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Fault,415124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almRateOfChange.AlarmState,415124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almRateOfChange.GlobalReset,415124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almRateOfChange.FaultInAlarm,415124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almRateOfChange.ALRM,415124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almRateOfChange.ANUN,415124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almRateOfChange.AKED,415124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almRateOfChange.Resetable,415124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almRateOfChange.REST,415124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almRateOfChange.ACKN,415124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almRateOfChange.UACK,415124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almRateOfChange.MCmd_Enable,415124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.MCmd_Disable,415124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.OCmd_Shelve,415124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.OCmd_Unshelve,415124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.SCmd_Suppress,415124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.SCmd_UnSuppress,415125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almRateOfChange.AEShelveTMRDN,415125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almRateOfChange.Bad,415125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almRateOfChange.Suppress,415126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.UnSuppress,415126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Shelve,415126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.UnShelve,415126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Enable,415126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Disable,415126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Ack,415126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Reset,415126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Suppressed,415126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Shelved,415126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Disabled,415126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Acked,415126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almRateOfChange.Alarm,415126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Fault,415136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_3_PI.almPLCFault.AlarmState,415136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_3_PI.almPLCFault.GlobalReset,415136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_3_PI.almPLCFault.FaultInAlarm,415136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_3_PI.almPLCFault.ALRM,415136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_3_PI.almPLCFault.ANUN,415136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_3_PI.almPLCFault.AKED,415136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_3_PI.almPLCFault.Resetable,415136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_3_PI.almPLCFault.REST,415136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_3_PI.almPLCFault.ACKN,415136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_3_PI.almPLCFault.UACK,415136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_3_PI.almPLCFault.MCmd_Enable,415136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_3_PI.almPLCFault.MCmd_Disable,415136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_3_PI.almPLCFault.OCmd_Shelve,415136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_3_PI.almPLCFault.OCmd_Unshelve,415136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_3_PI.almPLCFault.SCmd_Suppress,415136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_3_PI.almPLCFault.SCmd_UnSuppress,415137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_3_PI.almPLCFault.AEShelveTMRDN,415137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_3_PI.almPLCFault.Bad,415137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_3_PI.almPLCFault.Suppress,415138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.UnSuppress,415138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Shelve,415138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.UnShelve,415138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Enable,415138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Disable,415138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Ack,415138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Reset,415138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Suppressed,415138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Shelved,415138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Disabled,415138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Acked,415138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_3_PI.almPLCFault.Alarm,415138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Fault,415240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almHighHigh.AlarmState,415240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almHighHigh.GlobalReset,415240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almHighHigh.FaultInAlarm,415240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almHighHigh.ALRM,415240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almHighHigh.ANUN,415240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almHighHigh.AKED,415240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almHighHigh.Resetable,415240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almHighHigh.REST,415240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almHighHigh.ACKN,415240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almHighHigh.UACK,415240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almHighHigh.MCmd_Enable,415240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almHighHigh.MCmd_Disable,415240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almHighHigh.OCmd_Shelve,415240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almHighHigh.OCmd_Unshelve,415240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almHighHigh.SCmd_Suppress,415240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almHighHigh.SCmd_UnSuppress,415241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almHighHigh.AEShelveTMRDN,415241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almHighHigh.Bad,415241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almHighHigh.Suppress,415242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.UnSuppress,415242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Shelve,415242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.UnShelve,415242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Enable,415242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Disable,415242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Ack,415242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Reset,415242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Suppressed,415242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Shelved,415242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Disabled,415242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Acked,415242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almHighHigh.Alarm,415242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Fault,415252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almHigh.AlarmState,415252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almHigh.GlobalReset,415252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almHigh.FaultInAlarm,415252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almHigh.ALRM,415252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almHigh.ANUN,415252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almHigh.AKED,415252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almHigh.Resetable,415252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almHigh.REST,415252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almHigh.ACKN,415252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almHigh.UACK,415252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almHigh.MCmd_Enable,415252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almHigh.MCmd_Disable,415252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almHigh.OCmd_Shelve,415252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almHigh.OCmd_Unshelve,415252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almHigh.SCmd_Suppress,415252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almHigh.SCmd_UnSuppress,415253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almHigh.AEShelveTMRDN,415253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almHigh.Bad,415253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almHigh.Suppress,415254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.UnSuppress,415254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Shelve,415254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.UnShelve,415254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Enable,415254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Disable,415254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Ack,415254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Reset,415254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almHigh.Suppressed,415254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almHigh.Shelved,415254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almHigh.Disabled,415254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almHigh.Acked,415254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almHigh.Alarm,415254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Fault,415264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almLow.AlarmState,415264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almLow.GlobalReset,415264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almLow.FaultInAlarm,415264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almLow.ALRM,415264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almLow.ANUN,415264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almLow.AKED,415264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almLow.Resetable,415264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almLow.REST,415264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almLow.ACKN,415264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almLow.UACK,415264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almLow.MCmd_Enable,415264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almLow.MCmd_Disable,415264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almLow.OCmd_Shelve,415264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almLow.OCmd_Unshelve,415264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almLow.SCmd_Suppress,415264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almLow.SCmd_UnSuppress,415265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almLow.AEShelveTMRDN,415265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almLow.Bad,415265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almLow.Suppress,415266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.UnSuppress,415266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Shelve,415266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.UnShelve,415266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Enable,415266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Disable,415266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Ack,415266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Reset,415266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almLow.Suppressed,415266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almLow.Shelved,415266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almLow.Disabled,415266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almLow.Acked,415266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almLow.Alarm,415266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Fault,415276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almLowLow.AlarmState,415276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almLowLow.GlobalReset,415276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almLowLow.FaultInAlarm,415276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almLowLow.ALRM,415276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almLowLow.ANUN,415276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almLowLow.AKED,415276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almLowLow.Resetable,415276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almLowLow.REST,415276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almLowLow.ACKN,415276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almLowLow.UACK,415276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almLowLow.MCmd_Enable,415276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almLowLow.MCmd_Disable,415276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almLowLow.OCmd_Shelve,415276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almLowLow.OCmd_Unshelve,415276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almLowLow.SCmd_Suppress,415276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almLowLow.SCmd_UnSuppress,415277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almLowLow.AEShelveTMRDN,415277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almLowLow.Bad,415277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almLowLow.Suppress,415278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.UnSuppress,415278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Shelve,415278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.UnShelve,415278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Enable,415278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Disable,415278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Ack,415278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Reset,415278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almLowLow.Suppressed,415278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almLowLow.Shelved,415278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almLowLow.Disabled,415278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almLowLow.Acked,415278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almLowLow.Alarm,415278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Fault,415288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almBrokenLoop.AlarmState,415288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almBrokenLoop.GlobalReset,415288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almBrokenLoop.FaultInAlarm,415288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almBrokenLoop.ALRM,415288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almBrokenLoop.ANUN,415288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almBrokenLoop.AKED,415288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almBrokenLoop.Resetable,415288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almBrokenLoop.REST,415288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almBrokenLoop.ACKN,415288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almBrokenLoop.UACK,415288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almBrokenLoop.MCmd_Enable,415288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.MCmd_Disable,415288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.OCmd_Shelve,415288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.OCmd_Unshelve,415288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.SCmd_Suppress,415288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.SCmd_UnSuppress,415289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almBrokenLoop.AEShelveTMRDN,415289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almBrokenLoop.Bad,415289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almBrokenLoop.Suppress,415290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.UnSuppress,415290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Shelve,415290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.UnShelve,415290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Enable,415290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Disable,415290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Ack,415290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Reset,415290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Suppressed,415290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Shelved,415290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Disabled,415290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Acked,415290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almBrokenLoop.Alarm,415290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Fault,415300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almOverRange.AlarmState,415300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almOverRange.GlobalReset,415300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almOverRange.FaultInAlarm,415300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almOverRange.ALRM,415300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almOverRange.ANUN,415300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almOverRange.AKED,415300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almOverRange.Resetable,415300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almOverRange.REST,415300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almOverRange.ACKN,415300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almOverRange.UACK,415300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almOverRange.MCmd_Enable,415300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almOverRange.MCmd_Disable,415300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almOverRange.OCmd_Shelve,415300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almOverRange.OCmd_Unshelve,415300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almOverRange.SCmd_Suppress,415300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almOverRange.SCmd_UnSuppress,415301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almOverRange.AEShelveTMRDN,415301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almOverRange.Bad,415301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almOverRange.Suppress,415302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.UnSuppress,415302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Shelve,415302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.UnShelve,415302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Enable,415302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Disable,415302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Ack,415302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Reset,415302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almOverRange.Suppressed,415302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almOverRange.Shelved,415302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almOverRange.Disabled,415302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almOverRange.Acked,415302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almOverRange.Alarm,415302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Fault,415312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almUnderRange.AlarmState,415312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almUnderRange.GlobalReset,415312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almUnderRange.FaultInAlarm,415312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almUnderRange.ALRM,415312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almUnderRange.ANUN,415312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almUnderRange.AKED,415312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almUnderRange.Resetable,415312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almUnderRange.REST,415312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almUnderRange.ACKN,415312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almUnderRange.UACK,415312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almUnderRange.MCmd_Enable,415312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almUnderRange.MCmd_Disable,415312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almUnderRange.OCmd_Shelve,415312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almUnderRange.OCmd_Unshelve,415312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almUnderRange.SCmd_Suppress,415312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almUnderRange.SCmd_UnSuppress,415313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almUnderRange.AEShelveTMRDN,415313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almUnderRange.Bad,415313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almUnderRange.Suppress,415314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.UnSuppress,415314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Shelve,415314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.UnShelve,415314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Enable,415314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Disable,415314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Ack,415314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Reset,415314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Suppressed,415314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Shelved,415314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Disabled,415314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Acked,415314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almUnderRange.Alarm,415314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Fault,415324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almRateOfChange.AlarmState,415324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almRateOfChange.GlobalReset,415324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almRateOfChange.FaultInAlarm,415324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almRateOfChange.ALRM,415324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almRateOfChange.ANUN,415324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almRateOfChange.AKED,415324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almRateOfChange.Resetable,415324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almRateOfChange.REST,415324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almRateOfChange.ACKN,415324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almRateOfChange.UACK,415324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almRateOfChange.MCmd_Enable,415324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.MCmd_Disable,415324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.OCmd_Shelve,415324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.OCmd_Unshelve,415324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.SCmd_Suppress,415324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.SCmd_UnSuppress,415325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almRateOfChange.AEShelveTMRDN,415325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almRateOfChange.Bad,415325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almRateOfChange.Suppress,415326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.UnSuppress,415326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Shelve,415326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.UnShelve,415326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Enable,415326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Disable,415326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Ack,415326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Reset,415326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Suppressed,415326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Shelved,415326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Disabled,415326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Acked,415326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almRateOfChange.Alarm,415326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Fault,415336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_4_PI.almPLCFault.AlarmState,415336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_4_PI.almPLCFault.GlobalReset,415336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_4_PI.almPLCFault.FaultInAlarm,415336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_4_PI.almPLCFault.ALRM,415336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_4_PI.almPLCFault.ANUN,415336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_4_PI.almPLCFault.AKED,415336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_4_PI.almPLCFault.Resetable,415336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_4_PI.almPLCFault.REST,415336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_4_PI.almPLCFault.ACKN,415336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_4_PI.almPLCFault.UACK,415336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_4_PI.almPLCFault.MCmd_Enable,415336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_4_PI.almPLCFault.MCmd_Disable,415336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_4_PI.almPLCFault.OCmd_Shelve,415336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_4_PI.almPLCFault.OCmd_Unshelve,415336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_4_PI.almPLCFault.SCmd_Suppress,415336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_4_PI.almPLCFault.SCmd_UnSuppress,415337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_4_PI.almPLCFault.AEShelveTMRDN,415337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_4_PI.almPLCFault.Bad,415337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_4_PI.almPLCFault.Suppress,415338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.UnSuppress,415338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Shelve,415338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.UnShelve,415338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Enable,415338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Disable,415338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Ack,415338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Reset,415338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Suppressed,415338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Shelved,415338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Disabled,415338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Acked,415338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_4_PI.almPLCFault.Alarm,415338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Fault,415440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almHighHigh.AlarmState,415440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almHighHigh.GlobalReset,415440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almHighHigh.FaultInAlarm,415440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almHighHigh.ALRM,415440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almHighHigh.ANUN,415440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almHighHigh.AKED,415440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almHighHigh.Resetable,415440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almHighHigh.REST,415440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almHighHigh.ACKN,415440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almHighHigh.UACK,415440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almHighHigh.MCmd_Enable,415440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almHighHigh.MCmd_Disable,415440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almHighHigh.OCmd_Shelve,415440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almHighHigh.OCmd_Unshelve,415440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almHighHigh.SCmd_Suppress,415440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almHighHigh.SCmd_UnSuppress,415441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almHighHigh.AEShelveTMRDN,415441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almHighHigh.Bad,415441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almHighHigh.Suppress,415442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.UnSuppress,415442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Shelve,415442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.UnShelve,415442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Enable,415442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Disable,415442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Ack,415442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Reset,415442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Suppressed,415442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Shelved,415442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Disabled,415442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Acked,415442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almHighHigh.Alarm,415442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Fault,415452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almHigh.AlarmState,415452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almHigh.GlobalReset,415452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almHigh.FaultInAlarm,415452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almHigh.ALRM,415452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almHigh.ANUN,415452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almHigh.AKED,415452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almHigh.Resetable,415452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almHigh.REST,415452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almHigh.ACKN,415452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almHigh.UACK,415452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almHigh.MCmd_Enable,415452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almHigh.MCmd_Disable,415452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almHigh.OCmd_Shelve,415452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almHigh.OCmd_Unshelve,415452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almHigh.SCmd_Suppress,415452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almHigh.SCmd_UnSuppress,415453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almHigh.AEShelveTMRDN,415453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almHigh.Bad,415453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almHigh.Suppress,415454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.UnSuppress,415454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Shelve,415454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.UnShelve,415454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Enable,415454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Disable,415454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Ack,415454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Reset,415454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almHigh.Suppressed,415454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almHigh.Shelved,415454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almHigh.Disabled,415454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almHigh.Acked,415454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almHigh.Alarm,415454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Fault,415464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almLow.AlarmState,415464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almLow.GlobalReset,415464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almLow.FaultInAlarm,415464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almLow.ALRM,415464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almLow.ANUN,415464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almLow.AKED,415464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almLow.Resetable,415464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almLow.REST,415464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almLow.ACKN,415464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almLow.UACK,415464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almLow.MCmd_Enable,415464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almLow.MCmd_Disable,415464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almLow.OCmd_Shelve,415464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almLow.OCmd_Unshelve,415464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almLow.SCmd_Suppress,415464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almLow.SCmd_UnSuppress,415465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almLow.AEShelveTMRDN,415465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almLow.Bad,415465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almLow.Suppress,415466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.UnSuppress,415466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Shelve,415466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.UnShelve,415466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Enable,415466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Disable,415466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Ack,415466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Reset,415466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almLow.Suppressed,415466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almLow.Shelved,415466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almLow.Disabled,415466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almLow.Acked,415466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almLow.Alarm,415466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Fault,415476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almLowLow.AlarmState,415476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almLowLow.GlobalReset,415476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almLowLow.FaultInAlarm,415476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almLowLow.ALRM,415476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almLowLow.ANUN,415476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almLowLow.AKED,415476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almLowLow.Resetable,415476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almLowLow.REST,415476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almLowLow.ACKN,415476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almLowLow.UACK,415476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almLowLow.MCmd_Enable,415476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almLowLow.MCmd_Disable,415476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almLowLow.OCmd_Shelve,415476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almLowLow.OCmd_Unshelve,415476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almLowLow.SCmd_Suppress,415476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almLowLow.SCmd_UnSuppress,415477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almLowLow.AEShelveTMRDN,415477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almLowLow.Bad,415477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almLowLow.Suppress,415478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.UnSuppress,415478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Shelve,415478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.UnShelve,415478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Enable,415478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Disable,415478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Ack,415478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Reset,415478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almLowLow.Suppressed,415478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almLowLow.Shelved,415478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almLowLow.Disabled,415478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almLowLow.Acked,415478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almLowLow.Alarm,415478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Fault,415488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almBrokenLoop.AlarmState,415488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almBrokenLoop.GlobalReset,415488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almBrokenLoop.FaultInAlarm,415488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almBrokenLoop.ALRM,415488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almBrokenLoop.ANUN,415488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almBrokenLoop.AKED,415488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almBrokenLoop.Resetable,415488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almBrokenLoop.REST,415488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almBrokenLoop.ACKN,415488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almBrokenLoop.UACK,415488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almBrokenLoop.MCmd_Enable,415488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.MCmd_Disable,415488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.OCmd_Shelve,415488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.OCmd_Unshelve,415488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.SCmd_Suppress,415488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.SCmd_UnSuppress,415489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almBrokenLoop.AEShelveTMRDN,415489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almBrokenLoop.Bad,415489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almBrokenLoop.Suppress,415490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.UnSuppress,415490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Shelve,415490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.UnShelve,415490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Enable,415490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Disable,415490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Ack,415490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Reset,415490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Suppressed,415490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Shelved,415490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Disabled,415490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Acked,415490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almBrokenLoop.Alarm,415490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Fault,415500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almOverRange.AlarmState,415500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almOverRange.GlobalReset,415500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almOverRange.FaultInAlarm,415500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almOverRange.ALRM,415500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almOverRange.ANUN,415500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almOverRange.AKED,415500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almOverRange.Resetable,415500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almOverRange.REST,415500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almOverRange.ACKN,415500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almOverRange.UACK,415500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almOverRange.MCmd_Enable,415500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almOverRange.MCmd_Disable,415500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almOverRange.OCmd_Shelve,415500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almOverRange.OCmd_Unshelve,415500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almOverRange.SCmd_Suppress,415500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almOverRange.SCmd_UnSuppress,415501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almOverRange.AEShelveTMRDN,415501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almOverRange.Bad,415501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almOverRange.Suppress,415502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.UnSuppress,415502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Shelve,415502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.UnShelve,415502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Enable,415502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Disable,415502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Ack,415502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Reset,415502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almOverRange.Suppressed,415502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almOverRange.Shelved,415502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almOverRange.Disabled,415502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almOverRange.Acked,415502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almOverRange.Alarm,415502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Fault,415512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almUnderRange.AlarmState,415512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almUnderRange.GlobalReset,415512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almUnderRange.FaultInAlarm,415512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almUnderRange.ALRM,415512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almUnderRange.ANUN,415512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almUnderRange.AKED,415512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almUnderRange.Resetable,415512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almUnderRange.REST,415512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almUnderRange.ACKN,415512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almUnderRange.UACK,415512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almUnderRange.MCmd_Enable,415512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almUnderRange.MCmd_Disable,415512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almUnderRange.OCmd_Shelve,415512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almUnderRange.OCmd_Unshelve,415512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almUnderRange.SCmd_Suppress,415512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almUnderRange.SCmd_UnSuppress,415513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almUnderRange.AEShelveTMRDN,415513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almUnderRange.Bad,415513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almUnderRange.Suppress,415514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.UnSuppress,415514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Shelve,415514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.UnShelve,415514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Enable,415514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Disable,415514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Ack,415514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Reset,415514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Suppressed,415514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Shelved,415514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Disabled,415514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Acked,415514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almUnderRange.Alarm,415514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Fault,415524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almRateOfChange.AlarmState,415524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almRateOfChange.GlobalReset,415524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almRateOfChange.FaultInAlarm,415524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almRateOfChange.ALRM,415524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almRateOfChange.ANUN,415524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almRateOfChange.AKED,415524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almRateOfChange.Resetable,415524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almRateOfChange.REST,415524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almRateOfChange.ACKN,415524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almRateOfChange.UACK,415524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almRateOfChange.MCmd_Enable,415524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.MCmd_Disable,415524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.OCmd_Shelve,415524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.OCmd_Unshelve,415524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.SCmd_Suppress,415524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.SCmd_UnSuppress,415525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almRateOfChange.AEShelveTMRDN,415525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almRateOfChange.Bad,415525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almRateOfChange.Suppress,415526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.UnSuppress,415526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Shelve,415526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.UnShelve,415526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Enable,415526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Disable,415526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Ack,415526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Reset,415526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Suppressed,415526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Shelved,415526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Disabled,415526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Acked,415526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almRateOfChange.Alarm,415526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Fault,415536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_5_PI.almPLCFault.AlarmState,415536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_5_PI.almPLCFault.GlobalReset,415536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_5_PI.almPLCFault.FaultInAlarm,415536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_5_PI.almPLCFault.ALRM,415536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_5_PI.almPLCFault.ANUN,415536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_5_PI.almPLCFault.AKED,415536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_5_PI.almPLCFault.Resetable,415536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_5_PI.almPLCFault.REST,415536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_5_PI.almPLCFault.ACKN,415536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_5_PI.almPLCFault.UACK,415536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_5_PI.almPLCFault.MCmd_Enable,415536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_5_PI.almPLCFault.MCmd_Disable,415536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_5_PI.almPLCFault.OCmd_Shelve,415536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_5_PI.almPLCFault.OCmd_Unshelve,415536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_5_PI.almPLCFault.SCmd_Suppress,415536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_5_PI.almPLCFault.SCmd_UnSuppress,415537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_5_PI.almPLCFault.AEShelveTMRDN,415537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_5_PI.almPLCFault.Bad,415537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_5_PI.almPLCFault.Suppress,415538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.UnSuppress,415538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Shelve,415538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.UnShelve,415538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Enable,415538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Disable,415538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Ack,415538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Reset,415538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Suppressed,415538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Shelved,415538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Disabled,415538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Acked,415538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_5_PI.almPLCFault.Alarm,415538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Fault,415640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almHighHigh.AlarmState,415640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almHighHigh.GlobalReset,415640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almHighHigh.FaultInAlarm,415640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almHighHigh.ALRM,415640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almHighHigh.ANUN,415640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almHighHigh.AKED,415640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almHighHigh.Resetable,415640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almHighHigh.REST,415640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almHighHigh.ACKN,415640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almHighHigh.UACK,415640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almHighHigh.MCmd_Enable,415640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almHighHigh.MCmd_Disable,415640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almHighHigh.OCmd_Shelve,415640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almHighHigh.OCmd_Unshelve,415640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almHighHigh.SCmd_Suppress,415640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almHighHigh.SCmd_UnSuppress,415641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almHighHigh.AEShelveTMRDN,415641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almHighHigh.Bad,415641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almHighHigh.Suppress,415642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.UnSuppress,415642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Shelve,415642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.UnShelve,415642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Enable,415642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Disable,415642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Ack,415642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Reset,415642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Suppressed,415642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Shelved,415642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Disabled,415642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Acked,415642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almHighHigh.Alarm,415642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Fault,415652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almHigh.AlarmState,415652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almHigh.GlobalReset,415652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almHigh.FaultInAlarm,415652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almHigh.ALRM,415652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almHigh.ANUN,415652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almHigh.AKED,415652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almHigh.Resetable,415652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almHigh.REST,415652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almHigh.ACKN,415652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almHigh.UACK,415652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almHigh.MCmd_Enable,415652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almHigh.MCmd_Disable,415652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almHigh.OCmd_Shelve,415652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almHigh.OCmd_Unshelve,415652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almHigh.SCmd_Suppress,415652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almHigh.SCmd_UnSuppress,415653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almHigh.AEShelveTMRDN,415653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almHigh.Bad,415653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almHigh.Suppress,415654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.UnSuppress,415654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Shelve,415654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.UnShelve,415654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Enable,415654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Disable,415654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Ack,415654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Reset,415654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almHigh.Suppressed,415654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almHigh.Shelved,415654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almHigh.Disabled,415654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almHigh.Acked,415654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almHigh.Alarm,415654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Fault,415664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almLow.AlarmState,415664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almLow.GlobalReset,415664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almLow.FaultInAlarm,415664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almLow.ALRM,415664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almLow.ANUN,415664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almLow.AKED,415664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almLow.Resetable,415664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almLow.REST,415664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almLow.ACKN,415664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almLow.UACK,415664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almLow.MCmd_Enable,415664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almLow.MCmd_Disable,415664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almLow.OCmd_Shelve,415664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almLow.OCmd_Unshelve,415664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almLow.SCmd_Suppress,415664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almLow.SCmd_UnSuppress,415665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almLow.AEShelveTMRDN,415665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almLow.Bad,415665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almLow.Suppress,415666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.UnSuppress,415666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Shelve,415666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.UnShelve,415666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Enable,415666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Disable,415666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Ack,415666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Reset,415666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almLow.Suppressed,415666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almLow.Shelved,415666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almLow.Disabled,415666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almLow.Acked,415666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almLow.Alarm,415666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Fault,415676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almLowLow.AlarmState,415676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almLowLow.GlobalReset,415676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almLowLow.FaultInAlarm,415676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almLowLow.ALRM,415676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almLowLow.ANUN,415676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almLowLow.AKED,415676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almLowLow.Resetable,415676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almLowLow.REST,415676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almLowLow.ACKN,415676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almLowLow.UACK,415676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almLowLow.MCmd_Enable,415676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almLowLow.MCmd_Disable,415676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almLowLow.OCmd_Shelve,415676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almLowLow.OCmd_Unshelve,415676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almLowLow.SCmd_Suppress,415676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almLowLow.SCmd_UnSuppress,415677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almLowLow.AEShelveTMRDN,415677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almLowLow.Bad,415677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almLowLow.Suppress,415678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.UnSuppress,415678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Shelve,415678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.UnShelve,415678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Enable,415678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Disable,415678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Ack,415678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Reset,415678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almLowLow.Suppressed,415678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almLowLow.Shelved,415678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almLowLow.Disabled,415678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almLowLow.Acked,415678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almLowLow.Alarm,415678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Fault,415688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almBrokenLoop.AlarmState,415688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almBrokenLoop.GlobalReset,415688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almBrokenLoop.FaultInAlarm,415688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almBrokenLoop.ALRM,415688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almBrokenLoop.ANUN,415688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almBrokenLoop.AKED,415688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almBrokenLoop.Resetable,415688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almBrokenLoop.REST,415688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almBrokenLoop.ACKN,415688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almBrokenLoop.UACK,415688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almBrokenLoop.MCmd_Enable,415688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.MCmd_Disable,415688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.OCmd_Shelve,415688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.OCmd_Unshelve,415688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.SCmd_Suppress,415688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.SCmd_UnSuppress,415689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almBrokenLoop.AEShelveTMRDN,415689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almBrokenLoop.Bad,415689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almBrokenLoop.Suppress,415690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.UnSuppress,415690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Shelve,415690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.UnShelve,415690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Enable,415690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Disable,415690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Ack,415690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Reset,415690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Suppressed,415690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Shelved,415690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Disabled,415690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Acked,415690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almBrokenLoop.Alarm,415690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Fault,415700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almOverRange.AlarmState,415700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almOverRange.GlobalReset,415700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almOverRange.FaultInAlarm,415700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almOverRange.ALRM,415700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almOverRange.ANUN,415700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almOverRange.AKED,415700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almOverRange.Resetable,415700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almOverRange.REST,415700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almOverRange.ACKN,415700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almOverRange.UACK,415700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almOverRange.MCmd_Enable,415700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almOverRange.MCmd_Disable,415700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almOverRange.OCmd_Shelve,415700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almOverRange.OCmd_Unshelve,415700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almOverRange.SCmd_Suppress,415700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almOverRange.SCmd_UnSuppress,415701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almOverRange.AEShelveTMRDN,415701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almOverRange.Bad,415701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almOverRange.Suppress,415702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.UnSuppress,415702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Shelve,415702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.UnShelve,415702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Enable,415702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Disable,415702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Ack,415702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Reset,415702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almOverRange.Suppressed,415702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almOverRange.Shelved,415702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almOverRange.Disabled,415702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almOverRange.Acked,415702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almOverRange.Alarm,415702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Fault,415712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almUnderRange.AlarmState,415712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almUnderRange.GlobalReset,415712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almUnderRange.FaultInAlarm,415712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almUnderRange.ALRM,415712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almUnderRange.ANUN,415712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almUnderRange.AKED,415712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almUnderRange.Resetable,415712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almUnderRange.REST,415712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almUnderRange.ACKN,415712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almUnderRange.UACK,415712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almUnderRange.MCmd_Enable,415712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almUnderRange.MCmd_Disable,415712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almUnderRange.OCmd_Shelve,415712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almUnderRange.OCmd_Unshelve,415712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almUnderRange.SCmd_Suppress,415712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almUnderRange.SCmd_UnSuppress,415713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almUnderRange.AEShelveTMRDN,415713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almUnderRange.Bad,415713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almUnderRange.Suppress,415714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.UnSuppress,415714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Shelve,415714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.UnShelve,415714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Enable,415714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Disable,415714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Ack,415714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Reset,415714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Suppressed,415714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Shelved,415714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Disabled,415714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Acked,415714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almUnderRange.Alarm,415714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Fault,415724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almRateOfChange.AlarmState,415724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almRateOfChange.GlobalReset,415724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almRateOfChange.FaultInAlarm,415724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almRateOfChange.ALRM,415724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almRateOfChange.ANUN,415724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almRateOfChange.AKED,415724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almRateOfChange.Resetable,415724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almRateOfChange.REST,415724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almRateOfChange.ACKN,415724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almRateOfChange.UACK,415724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almRateOfChange.MCmd_Enable,415724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.MCmd_Disable,415724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.OCmd_Shelve,415724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.OCmd_Unshelve,415724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.SCmd_Suppress,415724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.SCmd_UnSuppress,415725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almRateOfChange.AEShelveTMRDN,415725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almRateOfChange.Bad,415725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almRateOfChange.Suppress,415726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.UnSuppress,415726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Shelve,415726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.UnShelve,415726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Enable,415726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Disable,415726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Ack,415726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Reset,415726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Suppressed,415726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Shelved,415726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Disabled,415726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Acked,415726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almRateOfChange.Alarm,415726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Fault,415736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_6_PI.almPLCFault.AlarmState,415736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_6_PI.almPLCFault.GlobalReset,415736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_6_PI.almPLCFault.FaultInAlarm,415736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_6_PI.almPLCFault.ALRM,415736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_6_PI.almPLCFault.ANUN,415736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_6_PI.almPLCFault.AKED,415736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_6_PI.almPLCFault.Resetable,415736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_6_PI.almPLCFault.REST,415736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_6_PI.almPLCFault.ACKN,415736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_6_PI.almPLCFault.UACK,415736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_6_PI.almPLCFault.MCmd_Enable,415736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_6_PI.almPLCFault.MCmd_Disable,415736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_6_PI.almPLCFault.OCmd_Shelve,415736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_6_PI.almPLCFault.OCmd_Unshelve,415736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_6_PI.almPLCFault.SCmd_Suppress,415736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_6_PI.almPLCFault.SCmd_UnSuppress,415737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_6_PI.almPLCFault.AEShelveTMRDN,415737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_6_PI.almPLCFault.Bad,415737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_6_PI.almPLCFault.Suppress,415738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.UnSuppress,415738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Shelve,415738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.UnShelve,415738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Enable,415738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Disable,415738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Ack,415738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Reset,415738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Suppressed,415738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Shelved,415738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Disabled,415738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Acked,415738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_6_PI.almPLCFault.Alarm,415738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Fault,415840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almHighHigh.AlarmState,415840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almHighHigh.GlobalReset,415840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almHighHigh.FaultInAlarm,415840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almHighHigh.ALRM,415840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almHighHigh.ANUN,415840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almHighHigh.AKED,415840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almHighHigh.Resetable,415840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almHighHigh.REST,415840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almHighHigh.ACKN,415840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almHighHigh.UACK,415840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almHighHigh.MCmd_Enable,415840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almHighHigh.MCmd_Disable,415840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almHighHigh.OCmd_Shelve,415840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almHighHigh.OCmd_Unshelve,415840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almHighHigh.SCmd_Suppress,415840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almHighHigh.SCmd_UnSuppress,415841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almHighHigh.AEShelveTMRDN,415841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almHighHigh.Bad,415841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almHighHigh.Suppress,415842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.UnSuppress,415842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Shelve,415842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.UnShelve,415842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Enable,415842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Disable,415842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Ack,415842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Reset,415842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Suppressed,415842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Shelved,415842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Disabled,415842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Acked,415842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almHighHigh.Alarm,415842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Fault,415852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almHigh.AlarmState,415852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almHigh.GlobalReset,415852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almHigh.FaultInAlarm,415852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almHigh.ALRM,415852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almHigh.ANUN,415852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almHigh.AKED,415852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almHigh.Resetable,415852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almHigh.REST,415852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almHigh.ACKN,415852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almHigh.UACK,415852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almHigh.MCmd_Enable,415852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almHigh.MCmd_Disable,415852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almHigh.OCmd_Shelve,415852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almHigh.OCmd_Unshelve,415852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almHigh.SCmd_Suppress,415852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almHigh.SCmd_UnSuppress,415853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almHigh.AEShelveTMRDN,415853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almHigh.Bad,415853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almHigh.Suppress,415854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.UnSuppress,415854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Shelve,415854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.UnShelve,415854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Enable,415854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Disable,415854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Ack,415854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Reset,415854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almHigh.Suppressed,415854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almHigh.Shelved,415854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almHigh.Disabled,415854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almHigh.Acked,415854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almHigh.Alarm,415854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Fault,415864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almLow.AlarmState,415864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almLow.GlobalReset,415864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almLow.FaultInAlarm,415864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almLow.ALRM,415864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almLow.ANUN,415864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almLow.AKED,415864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almLow.Resetable,415864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almLow.REST,415864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almLow.ACKN,415864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almLow.UACK,415864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almLow.MCmd_Enable,415864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almLow.MCmd_Disable,415864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almLow.OCmd_Shelve,415864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almLow.OCmd_Unshelve,415864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almLow.SCmd_Suppress,415864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almLow.SCmd_UnSuppress,415865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almLow.AEShelveTMRDN,415865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almLow.Bad,415865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almLow.Suppress,415866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.UnSuppress,415866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Shelve,415866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.UnShelve,415866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Enable,415866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Disable,415866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Ack,415866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Reset,415866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almLow.Suppressed,415866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almLow.Shelved,415866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almLow.Disabled,415866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almLow.Acked,415866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almLow.Alarm,415866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Fault,415876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almLowLow.AlarmState,415876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almLowLow.GlobalReset,415876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almLowLow.FaultInAlarm,415876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almLowLow.ALRM,415876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almLowLow.ANUN,415876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almLowLow.AKED,415876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almLowLow.Resetable,415876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almLowLow.REST,415876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almLowLow.ACKN,415876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almLowLow.UACK,415876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almLowLow.MCmd_Enable,415876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almLowLow.MCmd_Disable,415876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almLowLow.OCmd_Shelve,415876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almLowLow.OCmd_Unshelve,415876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almLowLow.SCmd_Suppress,415876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almLowLow.SCmd_UnSuppress,415877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almLowLow.AEShelveTMRDN,415877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almLowLow.Bad,415877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almLowLow.Suppress,415878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.UnSuppress,415878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Shelve,415878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.UnShelve,415878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Enable,415878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Disable,415878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Ack,415878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Reset,415878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almLowLow.Suppressed,415878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almLowLow.Shelved,415878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almLowLow.Disabled,415878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almLowLow.Acked,415878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almLowLow.Alarm,415878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Fault,415888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almBrokenLoop.AlarmState,415888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almBrokenLoop.GlobalReset,415888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almBrokenLoop.FaultInAlarm,415888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almBrokenLoop.ALRM,415888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almBrokenLoop.ANUN,415888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almBrokenLoop.AKED,415888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almBrokenLoop.Resetable,415888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almBrokenLoop.REST,415888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almBrokenLoop.ACKN,415888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almBrokenLoop.UACK,415888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almBrokenLoop.MCmd_Enable,415888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.MCmd_Disable,415888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.OCmd_Shelve,415888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.OCmd_Unshelve,415888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.SCmd_Suppress,415888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.SCmd_UnSuppress,415889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almBrokenLoop.AEShelveTMRDN,415889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almBrokenLoop.Bad,415889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almBrokenLoop.Suppress,415890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.UnSuppress,415890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Shelve,415890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.UnShelve,415890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Enable,415890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Disable,415890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Ack,415890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Reset,415890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Suppressed,415890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Shelved,415890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Disabled,415890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Acked,415890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almBrokenLoop.Alarm,415890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Fault,415900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almOverRange.AlarmState,415900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almOverRange.GlobalReset,415900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almOverRange.FaultInAlarm,415900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almOverRange.ALRM,415900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almOverRange.ANUN,415900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almOverRange.AKED,415900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almOverRange.Resetable,415900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almOverRange.REST,415900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almOverRange.ACKN,415900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almOverRange.UACK,415900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almOverRange.MCmd_Enable,415900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almOverRange.MCmd_Disable,415900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almOverRange.OCmd_Shelve,415900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almOverRange.OCmd_Unshelve,415900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almOverRange.SCmd_Suppress,415900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almOverRange.SCmd_UnSuppress,415901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almOverRange.AEShelveTMRDN,415901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almOverRange.Bad,415901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almOverRange.Suppress,415902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.UnSuppress,415902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Shelve,415902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.UnShelve,415902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Enable,415902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Disable,415902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Ack,415902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Reset,415902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almOverRange.Suppressed,415902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almOverRange.Shelved,415902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almOverRange.Disabled,415902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almOverRange.Acked,415902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almOverRange.Alarm,415902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Fault,415912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almUnderRange.AlarmState,415912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almUnderRange.GlobalReset,415912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almUnderRange.FaultInAlarm,415912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almUnderRange.ALRM,415912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almUnderRange.ANUN,415912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almUnderRange.AKED,415912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almUnderRange.Resetable,415912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almUnderRange.REST,415912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almUnderRange.ACKN,415912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almUnderRange.UACK,415912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almUnderRange.MCmd_Enable,415912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almUnderRange.MCmd_Disable,415912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almUnderRange.OCmd_Shelve,415912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almUnderRange.OCmd_Unshelve,415912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almUnderRange.SCmd_Suppress,415912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almUnderRange.SCmd_UnSuppress,415913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almUnderRange.AEShelveTMRDN,415913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almUnderRange.Bad,415913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almUnderRange.Suppress,415914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.UnSuppress,415914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Shelve,415914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.UnShelve,415914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Enable,415914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Disable,415914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Ack,415914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Reset,415914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Suppressed,415914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Shelved,415914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Disabled,415914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Acked,415914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almUnderRange.Alarm,415914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Fault,415924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almRateOfChange.AlarmState,415924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almRateOfChange.GlobalReset,415924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almRateOfChange.FaultInAlarm,415924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almRateOfChange.ALRM,415924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almRateOfChange.ANUN,415924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almRateOfChange.AKED,415924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almRateOfChange.Resetable,415924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almRateOfChange.REST,415924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almRateOfChange.ACKN,415924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almRateOfChange.UACK,415924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almRateOfChange.MCmd_Enable,415924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.MCmd_Disable,415924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.OCmd_Shelve,415924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.OCmd_Unshelve,415924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.SCmd_Suppress,415924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.SCmd_UnSuppress,415925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almRateOfChange.AEShelveTMRDN,415925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almRateOfChange.Bad,415925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almRateOfChange.Suppress,415926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.UnSuppress,415926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Shelve,415926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.UnShelve,415926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Enable,415926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Disable,415926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Ack,415926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Reset,415926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Suppressed,415926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Shelved,415926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Disabled,415926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Acked,415926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almRateOfChange.Alarm,415926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Fault,415936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_7_PI.almPLCFault.AlarmState,415936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_7_PI.almPLCFault.GlobalReset,415936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_7_PI.almPLCFault.FaultInAlarm,415936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_7_PI.almPLCFault.ALRM,415936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_7_PI.almPLCFault.ANUN,415936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_7_PI.almPLCFault.AKED,415936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_7_PI.almPLCFault.Resetable,415936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_7_PI.almPLCFault.REST,415936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_7_PI.almPLCFault.ACKN,415936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_7_PI.almPLCFault.UACK,415936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_7_PI.almPLCFault.MCmd_Enable,415936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_7_PI.almPLCFault.MCmd_Disable,415936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_7_PI.almPLCFault.OCmd_Shelve,415936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_7_PI.almPLCFault.OCmd_Unshelve,415936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_7_PI.almPLCFault.SCmd_Suppress,415936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_7_PI.almPLCFault.SCmd_UnSuppress,415937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_7_PI.almPLCFault.AEShelveTMRDN,415937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_7_PI.almPLCFault.Bad,415937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_7_PI.almPLCFault.Suppress,415938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.UnSuppress,415938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Shelve,415938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.UnShelve,415938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Enable,415938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Disable,415938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Ack,415938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Reset,415938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Suppressed,415938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Shelved,415938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Disabled,415938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Acked,415938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_7_PI.almPLCFault.Alarm,415938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Fault,416040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almHighHigh.AlarmState,416040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almHighHigh.GlobalReset,416040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almHighHigh.FaultInAlarm,416040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almHighHigh.ALRM,416040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almHighHigh.ANUN,416040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almHighHigh.AKED,416040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almHighHigh.Resetable,416040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almHighHigh.REST,416040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almHighHigh.ACKN,416040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almHighHigh.UACK,416040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almHighHigh.MCmd_Enable,416040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almHighHigh.MCmd_Disable,416040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almHighHigh.OCmd_Shelve,416040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almHighHigh.OCmd_Unshelve,416040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almHighHigh.SCmd_Suppress,416040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almHighHigh.SCmd_UnSuppress,416041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almHighHigh.AEShelveTMRDN,416041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almHighHigh.Bad,416041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almHighHigh.Suppress,416042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.UnSuppress,416042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Shelve,416042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.UnShelve,416042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Enable,416042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Disable,416042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Ack,416042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Reset,416042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Suppressed,416042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Shelved,416042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Disabled,416042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Acked,416042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almHighHigh.Alarm,416042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Fault,416052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almHigh.AlarmState,416052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almHigh.GlobalReset,416052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almHigh.FaultInAlarm,416052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almHigh.ALRM,416052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almHigh.ANUN,416052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almHigh.AKED,416052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almHigh.Resetable,416052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almHigh.REST,416052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almHigh.ACKN,416052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almHigh.UACK,416052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almHigh.MCmd_Enable,416052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almHigh.MCmd_Disable,416052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almHigh.OCmd_Shelve,416052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almHigh.OCmd_Unshelve,416052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almHigh.SCmd_Suppress,416052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almHigh.SCmd_UnSuppress,416053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almHigh.AEShelveTMRDN,416053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almHigh.Bad,416053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almHigh.Suppress,416054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.UnSuppress,416054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Shelve,416054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.UnShelve,416054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Enable,416054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Disable,416054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Ack,416054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Reset,416054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almHigh.Suppressed,416054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almHigh.Shelved,416054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almHigh.Disabled,416054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almHigh.Acked,416054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almHigh.Alarm,416054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Fault,416064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almLow.AlarmState,416064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almLow.GlobalReset,416064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almLow.FaultInAlarm,416064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almLow.ALRM,416064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almLow.ANUN,416064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almLow.AKED,416064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almLow.Resetable,416064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almLow.REST,416064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almLow.ACKN,416064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almLow.UACK,416064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almLow.MCmd_Enable,416064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almLow.MCmd_Disable,416064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almLow.OCmd_Shelve,416064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almLow.OCmd_Unshelve,416064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almLow.SCmd_Suppress,416064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almLow.SCmd_UnSuppress,416065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almLow.AEShelveTMRDN,416065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almLow.Bad,416065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almLow.Suppress,416066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.UnSuppress,416066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Shelve,416066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.UnShelve,416066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Enable,416066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Disable,416066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Ack,416066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Reset,416066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almLow.Suppressed,416066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almLow.Shelved,416066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almLow.Disabled,416066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almLow.Acked,416066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almLow.Alarm,416066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Fault,416076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almLowLow.AlarmState,416076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almLowLow.GlobalReset,416076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almLowLow.FaultInAlarm,416076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almLowLow.ALRM,416076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almLowLow.ANUN,416076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almLowLow.AKED,416076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almLowLow.Resetable,416076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almLowLow.REST,416076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almLowLow.ACKN,416076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almLowLow.UACK,416076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almLowLow.MCmd_Enable,416076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almLowLow.MCmd_Disable,416076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almLowLow.OCmd_Shelve,416076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almLowLow.OCmd_Unshelve,416076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almLowLow.SCmd_Suppress,416076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almLowLow.SCmd_UnSuppress,416077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almLowLow.AEShelveTMRDN,416077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almLowLow.Bad,416077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almLowLow.Suppress,416078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.UnSuppress,416078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Shelve,416078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.UnShelve,416078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Enable,416078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Disable,416078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Ack,416078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Reset,416078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almLowLow.Suppressed,416078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almLowLow.Shelved,416078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almLowLow.Disabled,416078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almLowLow.Acked,416078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almLowLow.Alarm,416078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Fault,416088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almBrokenLoop.AlarmState,416088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almBrokenLoop.GlobalReset,416088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almBrokenLoop.FaultInAlarm,416088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almBrokenLoop.ALRM,416088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almBrokenLoop.ANUN,416088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almBrokenLoop.AKED,416088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almBrokenLoop.Resetable,416088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almBrokenLoop.REST,416088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almBrokenLoop.ACKN,416088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almBrokenLoop.UACK,416088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almBrokenLoop.MCmd_Enable,416088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.MCmd_Disable,416088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.OCmd_Shelve,416088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.OCmd_Unshelve,416088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.SCmd_Suppress,416088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.SCmd_UnSuppress,416089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almBrokenLoop.AEShelveTMRDN,416089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almBrokenLoop.Bad,416089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almBrokenLoop.Suppress,416090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.UnSuppress,416090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Shelve,416090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.UnShelve,416090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Enable,416090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Disable,416090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Ack,416090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Reset,416090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Suppressed,416090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Shelved,416090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Disabled,416090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Acked,416090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almBrokenLoop.Alarm,416090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Fault,416100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almOverRange.AlarmState,416100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almOverRange.GlobalReset,416100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almOverRange.FaultInAlarm,416100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almOverRange.ALRM,416100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almOverRange.ANUN,416100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almOverRange.AKED,416100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almOverRange.Resetable,416100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almOverRange.REST,416100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almOverRange.ACKN,416100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almOverRange.UACK,416100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almOverRange.MCmd_Enable,416100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almOverRange.MCmd_Disable,416100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almOverRange.OCmd_Shelve,416100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almOverRange.OCmd_Unshelve,416100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almOverRange.SCmd_Suppress,416100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almOverRange.SCmd_UnSuppress,416101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almOverRange.AEShelveTMRDN,416101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almOverRange.Bad,416101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almOverRange.Suppress,416102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.UnSuppress,416102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Shelve,416102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.UnShelve,416102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Enable,416102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Disable,416102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Ack,416102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Reset,416102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almOverRange.Suppressed,416102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almOverRange.Shelved,416102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almOverRange.Disabled,416102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almOverRange.Acked,416102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almOverRange.Alarm,416102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Fault,416112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almUnderRange.AlarmState,416112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almUnderRange.GlobalReset,416112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almUnderRange.FaultInAlarm,416112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almUnderRange.ALRM,416112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almUnderRange.ANUN,416112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almUnderRange.AKED,416112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almUnderRange.Resetable,416112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almUnderRange.REST,416112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almUnderRange.ACKN,416112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almUnderRange.UACK,416112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almUnderRange.MCmd_Enable,416112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almUnderRange.MCmd_Disable,416112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almUnderRange.OCmd_Shelve,416112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almUnderRange.OCmd_Unshelve,416112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almUnderRange.SCmd_Suppress,416112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almUnderRange.SCmd_UnSuppress,416113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almUnderRange.AEShelveTMRDN,416113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almUnderRange.Bad,416113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almUnderRange.Suppress,416114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.UnSuppress,416114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Shelve,416114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.UnShelve,416114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Enable,416114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Disable,416114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Ack,416114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Reset,416114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Suppressed,416114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Shelved,416114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Disabled,416114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Acked,416114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almUnderRange.Alarm,416114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Fault,416124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almRateOfChange.AlarmState,416124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almRateOfChange.GlobalReset,416124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almRateOfChange.FaultInAlarm,416124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almRateOfChange.ALRM,416124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almRateOfChange.ANUN,416124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almRateOfChange.AKED,416124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almRateOfChange.Resetable,416124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almRateOfChange.REST,416124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almRateOfChange.ACKN,416124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almRateOfChange.UACK,416124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almRateOfChange.MCmd_Enable,416124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.MCmd_Disable,416124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.OCmd_Shelve,416124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.OCmd_Unshelve,416124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.SCmd_Suppress,416124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.SCmd_UnSuppress,416125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almRateOfChange.AEShelveTMRDN,416125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almRateOfChange.Bad,416125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almRateOfChange.Suppress,416126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.UnSuppress,416126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Shelve,416126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.UnShelve,416126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Enable,416126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Disable,416126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Ack,416126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Reset,416126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Suppressed,416126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Shelved,416126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Disabled,416126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Acked,416126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almRateOfChange.Alarm,416126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Fault,416136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_8_PI.almPLCFault.AlarmState,416136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_8_PI.almPLCFault.GlobalReset,416136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_8_PI.almPLCFault.FaultInAlarm,416136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_8_PI.almPLCFault.ALRM,416136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_8_PI.almPLCFault.ANUN,416136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_8_PI.almPLCFault.AKED,416136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_8_PI.almPLCFault.Resetable,416136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_8_PI.almPLCFault.REST,416136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_8_PI.almPLCFault.ACKN,416136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_8_PI.almPLCFault.UACK,416136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_8_PI.almPLCFault.MCmd_Enable,416136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_8_PI.almPLCFault.MCmd_Disable,416136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_8_PI.almPLCFault.OCmd_Shelve,416136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_8_PI.almPLCFault.OCmd_Unshelve,416136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_8_PI.almPLCFault.SCmd_Suppress,416136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_8_PI.almPLCFault.SCmd_UnSuppress,416137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_8_PI.almPLCFault.AEShelveTMRDN,416137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_8_PI.almPLCFault.Bad,416137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_8_PI.almPLCFault.Suppress,416138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.UnSuppress,416138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Shelve,416138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.UnShelve,416138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Enable,416138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Disable,416138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Ack,416138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Reset,416138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Suppressed,416138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Shelved,416138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Disabled,416138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Acked,416138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_8_PI.almPLCFault.Alarm,416138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Fault,416240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almHighHigh.AlarmState,416240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almHighHigh.GlobalReset,416240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almHighHigh.FaultInAlarm,416240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almHighHigh.ALRM,416240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almHighHigh.ANUN,416240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almHighHigh.AKED,416240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almHighHigh.Resetable,416240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almHighHigh.REST,416240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almHighHigh.ACKN,416240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almHighHigh.UACK,416240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almHighHigh.MCmd_Enable,416240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almHighHigh.MCmd_Disable,416240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almHighHigh.OCmd_Shelve,416240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almHighHigh.OCmd_Unshelve,416240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almHighHigh.SCmd_Suppress,416240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almHighHigh.SCmd_UnSuppress,416241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almHighHigh.AEShelveTMRDN,416241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almHighHigh.Bad,416241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almHighHigh.Suppress,416242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.UnSuppress,416242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Shelve,416242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.UnShelve,416242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Enable,416242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Disable,416242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Ack,416242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Reset,416242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Suppressed,416242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Shelved,416242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Disabled,416242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Acked,416242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almHighHigh.Alarm,416242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Fault,416252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almHigh.AlarmState,416252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almHigh.GlobalReset,416252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almHigh.FaultInAlarm,416252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almHigh.ALRM,416252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almHigh.ANUN,416252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almHigh.AKED,416252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almHigh.Resetable,416252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almHigh.REST,416252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almHigh.ACKN,416252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almHigh.UACK,416252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almHigh.MCmd_Enable,416252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almHigh.MCmd_Disable,416252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almHigh.OCmd_Shelve,416252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almHigh.OCmd_Unshelve,416252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almHigh.SCmd_Suppress,416252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almHigh.SCmd_UnSuppress,416253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almHigh.AEShelveTMRDN,416253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almHigh.Bad,416253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almHigh.Suppress,416254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.UnSuppress,416254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Shelve,416254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.UnShelve,416254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Enable,416254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Disable,416254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Ack,416254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Reset,416254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almHigh.Suppressed,416254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almHigh.Shelved,416254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almHigh.Disabled,416254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almHigh.Acked,416254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almHigh.Alarm,416254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Fault,416264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almLow.AlarmState,416264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almLow.GlobalReset,416264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almLow.FaultInAlarm,416264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almLow.ALRM,416264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almLow.ANUN,416264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almLow.AKED,416264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almLow.Resetable,416264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almLow.REST,416264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almLow.ACKN,416264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almLow.UACK,416264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almLow.MCmd_Enable,416264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almLow.MCmd_Disable,416264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almLow.OCmd_Shelve,416264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almLow.OCmd_Unshelve,416264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almLow.SCmd_Suppress,416264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almLow.SCmd_UnSuppress,416265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almLow.AEShelveTMRDN,416265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almLow.Bad,416265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almLow.Suppress,416266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.UnSuppress,416266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Shelve,416266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.UnShelve,416266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Enable,416266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Disable,416266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Ack,416266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Reset,416266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almLow.Suppressed,416266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almLow.Shelved,416266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almLow.Disabled,416266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almLow.Acked,416266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almLow.Alarm,416266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Fault,416276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almLowLow.AlarmState,416276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almLowLow.GlobalReset,416276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almLowLow.FaultInAlarm,416276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almLowLow.ALRM,416276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almLowLow.ANUN,416276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almLowLow.AKED,416276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almLowLow.Resetable,416276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almLowLow.REST,416276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almLowLow.ACKN,416276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almLowLow.UACK,416276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almLowLow.MCmd_Enable,416276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almLowLow.MCmd_Disable,416276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almLowLow.OCmd_Shelve,416276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almLowLow.OCmd_Unshelve,416276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almLowLow.SCmd_Suppress,416276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almLowLow.SCmd_UnSuppress,416277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almLowLow.AEShelveTMRDN,416277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almLowLow.Bad,416277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almLowLow.Suppress,416278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.UnSuppress,416278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Shelve,416278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.UnShelve,416278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Enable,416278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Disable,416278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Ack,416278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Reset,416278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almLowLow.Suppressed,416278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almLowLow.Shelved,416278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almLowLow.Disabled,416278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almLowLow.Acked,416278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almLowLow.Alarm,416278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Fault,416288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almBrokenLoop.AlarmState,416288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almBrokenLoop.GlobalReset,416288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almBrokenLoop.FaultInAlarm,416288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almBrokenLoop.ALRM,416288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almBrokenLoop.ANUN,416288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almBrokenLoop.AKED,416288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almBrokenLoop.Resetable,416288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almBrokenLoop.REST,416288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almBrokenLoop.ACKN,416288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almBrokenLoop.UACK,416288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almBrokenLoop.MCmd_Enable,416288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.MCmd_Disable,416288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.OCmd_Shelve,416288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.OCmd_Unshelve,416288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.SCmd_Suppress,416288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.SCmd_UnSuppress,416289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almBrokenLoop.AEShelveTMRDN,416289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almBrokenLoop.Bad,416289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almBrokenLoop.Suppress,416290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.UnSuppress,416290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Shelve,416290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.UnShelve,416290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Enable,416290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Disable,416290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Ack,416290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Reset,416290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Suppressed,416290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Shelved,416290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Disabled,416290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Acked,416290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almBrokenLoop.Alarm,416290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Fault,416300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almOverRange.AlarmState,416300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almOverRange.GlobalReset,416300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almOverRange.FaultInAlarm,416300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almOverRange.ALRM,416300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almOverRange.ANUN,416300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almOverRange.AKED,416300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almOverRange.Resetable,416300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almOverRange.REST,416300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almOverRange.ACKN,416300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almOverRange.UACK,416300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almOverRange.MCmd_Enable,416300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almOverRange.MCmd_Disable,416300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almOverRange.OCmd_Shelve,416300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almOverRange.OCmd_Unshelve,416300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almOverRange.SCmd_Suppress,416300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almOverRange.SCmd_UnSuppress,416301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almOverRange.AEShelveTMRDN,416301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almOverRange.Bad,416301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almOverRange.Suppress,416302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.UnSuppress,416302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Shelve,416302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.UnShelve,416302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Enable,416302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Disable,416302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Ack,416302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Reset,416302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almOverRange.Suppressed,416302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almOverRange.Shelved,416302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almOverRange.Disabled,416302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almOverRange.Acked,416302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almOverRange.Alarm,416302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Fault,416312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almUnderRange.AlarmState,416312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almUnderRange.GlobalReset,416312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almUnderRange.FaultInAlarm,416312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almUnderRange.ALRM,416312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almUnderRange.ANUN,416312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almUnderRange.AKED,416312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almUnderRange.Resetable,416312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almUnderRange.REST,416312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almUnderRange.ACKN,416312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almUnderRange.UACK,416312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almUnderRange.MCmd_Enable,416312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almUnderRange.MCmd_Disable,416312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almUnderRange.OCmd_Shelve,416312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almUnderRange.OCmd_Unshelve,416312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almUnderRange.SCmd_Suppress,416312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almUnderRange.SCmd_UnSuppress,416313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almUnderRange.AEShelveTMRDN,416313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almUnderRange.Bad,416313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almUnderRange.Suppress,416314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.UnSuppress,416314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Shelve,416314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.UnShelve,416314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Enable,416314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Disable,416314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Ack,416314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Reset,416314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Suppressed,416314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Shelved,416314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Disabled,416314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Acked,416314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almUnderRange.Alarm,416314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Fault,416324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almRateOfChange.AlarmState,416324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almRateOfChange.GlobalReset,416324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almRateOfChange.FaultInAlarm,416324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almRateOfChange.ALRM,416324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almRateOfChange.ANUN,416324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almRateOfChange.AKED,416324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almRateOfChange.Resetable,416324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almRateOfChange.REST,416324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almRateOfChange.ACKN,416324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almRateOfChange.UACK,416324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almRateOfChange.MCmd_Enable,416324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.MCmd_Disable,416324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.OCmd_Shelve,416324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.OCmd_Unshelve,416324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.SCmd_Suppress,416324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.SCmd_UnSuppress,416325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almRateOfChange.AEShelveTMRDN,416325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almRateOfChange.Bad,416325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almRateOfChange.Suppress,416326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.UnSuppress,416326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Shelve,416326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.UnShelve,416326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Enable,416326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Disable,416326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Ack,416326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Reset,416326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Suppressed,416326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Shelved,416326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Disabled,416326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Acked,416326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almRateOfChange.Alarm,416326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Fault,416336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0103_9_PI.almPLCFault.AlarmState,416336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0103_9_PI.almPLCFault.GlobalReset,416336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0103_9_PI.almPLCFault.FaultInAlarm,416336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0103_9_PI.almPLCFault.ALRM,416336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0103_9_PI.almPLCFault.ANUN,416336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0103_9_PI.almPLCFault.AKED,416336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0103_9_PI.almPLCFault.Resetable,416336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0103_9_PI.almPLCFault.REST,416336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0103_9_PI.almPLCFault.ACKN,416336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0103_9_PI.almPLCFault.UACK,416336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0103_9_PI.almPLCFault.MCmd_Enable,416336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0103_9_PI.almPLCFault.MCmd_Disable,416336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0103_9_PI.almPLCFault.OCmd_Shelve,416336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0103_9_PI.almPLCFault.OCmd_Unshelve,416336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0103_9_PI.almPLCFault.SCmd_Suppress,416336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0103_9_PI.almPLCFault.SCmd_UnSuppress,416337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0103_9_PI.almPLCFault.AEShelveTMRDN,416337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0103_9_PI.almPLCFault.Bad,416337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0103_9_PI.almPLCFault.Suppress,416338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.UnSuppress,416338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Shelve,416338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.UnShelve,416338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Enable,416338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Disable,416338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Ack,416338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Reset,416338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Suppressed,416338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Shelved,416338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Disabled,416338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Acked,416338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0103_9_PI.almPLCFault.Alarm,416338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Fault,416440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almHighHigh.AlarmState,416440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almHighHigh.GlobalReset,416440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almHighHigh.FaultInAlarm,416440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almHighHigh.ALRM,416440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almHighHigh.ANUN,416440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almHighHigh.AKED,416440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almHighHigh.Resetable,416440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almHighHigh.REST,416440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almHighHigh.ACKN,416440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almHighHigh.UACK,416440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almHighHigh.MCmd_Enable,416440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almHighHigh.MCmd_Disable,416440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almHighHigh.OCmd_Shelve,416440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almHighHigh.OCmd_Unshelve,416440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almHighHigh.SCmd_Suppress,416440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almHighHigh.SCmd_UnSuppress,416441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almHighHigh.AEShelveTMRDN,416441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almHighHigh.Bad,416441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almHighHigh.Suppress,416442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.UnSuppress,416442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Shelve,416442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.UnShelve,416442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Enable,416442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Disable,416442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Ack,416442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Reset,416442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Suppressed,416442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Shelved,416442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Disabled,416442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Acked,416442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almHighHigh.Alarm,416442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Fault,416452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almHigh.AlarmState,416452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almHigh.GlobalReset,416452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almHigh.FaultInAlarm,416452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almHigh.ALRM,416452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almHigh.ANUN,416452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almHigh.AKED,416452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almHigh.Resetable,416452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almHigh.REST,416452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almHigh.ACKN,416452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almHigh.UACK,416452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almHigh.MCmd_Enable,416452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almHigh.MCmd_Disable,416452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almHigh.OCmd_Shelve,416452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almHigh.OCmd_Unshelve,416452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almHigh.SCmd_Suppress,416452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almHigh.SCmd_UnSuppress,416453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almHigh.AEShelveTMRDN,416453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almHigh.Bad,416453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almHigh.Suppress,416454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.UnSuppress,416454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Shelve,416454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.UnShelve,416454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Enable,416454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Disable,416454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Ack,416454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Reset,416454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almHigh.Suppressed,416454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almHigh.Shelved,416454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almHigh.Disabled,416454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almHigh.Acked,416454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almHigh.Alarm,416454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Fault,416464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almLow.AlarmState,416464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almLow.GlobalReset,416464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almLow.FaultInAlarm,416464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almLow.ALRM,416464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almLow.ANUN,416464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almLow.AKED,416464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almLow.Resetable,416464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almLow.REST,416464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almLow.ACKN,416464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almLow.UACK,416464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almLow.MCmd_Enable,416464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almLow.MCmd_Disable,416464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almLow.OCmd_Shelve,416464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almLow.OCmd_Unshelve,416464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almLow.SCmd_Suppress,416464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almLow.SCmd_UnSuppress,416465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almLow.AEShelveTMRDN,416465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almLow.Bad,416465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almLow.Suppress,416466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.UnSuppress,416466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Shelve,416466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.UnShelve,416466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Enable,416466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Disable,416466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Ack,416466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Reset,416466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almLow.Suppressed,416466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almLow.Shelved,416466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almLow.Disabled,416466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almLow.Acked,416466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almLow.Alarm,416466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Fault,416476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almLowLow.AlarmState,416476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almLowLow.GlobalReset,416476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almLowLow.FaultInAlarm,416476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almLowLow.ALRM,416476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almLowLow.ANUN,416476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almLowLow.AKED,416476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almLowLow.Resetable,416476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almLowLow.REST,416476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almLowLow.ACKN,416476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almLowLow.UACK,416476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almLowLow.MCmd_Enable,416476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almLowLow.MCmd_Disable,416476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almLowLow.OCmd_Shelve,416476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almLowLow.OCmd_Unshelve,416476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almLowLow.SCmd_Suppress,416476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almLowLow.SCmd_UnSuppress,416477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almLowLow.AEShelveTMRDN,416477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almLowLow.Bad,416477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almLowLow.Suppress,416478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.UnSuppress,416478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Shelve,416478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.UnShelve,416478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Enable,416478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Disable,416478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Ack,416478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Reset,416478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almLowLow.Suppressed,416478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almLowLow.Shelved,416478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almLowLow.Disabled,416478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almLowLow.Acked,416478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almLowLow.Alarm,416478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Fault,416488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almBrokenLoop.AlarmState,416488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almBrokenLoop.GlobalReset,416488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almBrokenLoop.FaultInAlarm,416488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almBrokenLoop.ALRM,416488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almBrokenLoop.ANUN,416488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almBrokenLoop.AKED,416488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almBrokenLoop.Resetable,416488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almBrokenLoop.REST,416488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almBrokenLoop.ACKN,416488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almBrokenLoop.UACK,416488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almBrokenLoop.MCmd_Enable,416488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.MCmd_Disable,416488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.OCmd_Shelve,416488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.OCmd_Unshelve,416488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.SCmd_Suppress,416488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.SCmd_UnSuppress,416489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almBrokenLoop.AEShelveTMRDN,416489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almBrokenLoop.Bad,416489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almBrokenLoop.Suppress,416490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.UnSuppress,416490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Shelve,416490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.UnShelve,416490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Enable,416490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Disable,416490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Ack,416490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Reset,416490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Suppressed,416490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Shelved,416490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Disabled,416490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Acked,416490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almBrokenLoop.Alarm,416490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Fault,416500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almOverRange.AlarmState,416500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almOverRange.GlobalReset,416500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almOverRange.FaultInAlarm,416500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almOverRange.ALRM,416500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almOverRange.ANUN,416500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almOverRange.AKED,416500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almOverRange.Resetable,416500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almOverRange.REST,416500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almOverRange.ACKN,416500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almOverRange.UACK,416500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almOverRange.MCmd_Enable,416500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almOverRange.MCmd_Disable,416500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almOverRange.OCmd_Shelve,416500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almOverRange.OCmd_Unshelve,416500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almOverRange.SCmd_Suppress,416500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almOverRange.SCmd_UnSuppress,416501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almOverRange.AEShelveTMRDN,416501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almOverRange.Bad,416501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almOverRange.Suppress,416502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.UnSuppress,416502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Shelve,416502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.UnShelve,416502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Enable,416502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Disable,416502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Ack,416502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Reset,416502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almOverRange.Suppressed,416502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almOverRange.Shelved,416502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almOverRange.Disabled,416502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almOverRange.Acked,416502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almOverRange.Alarm,416502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Fault,416512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almUnderRange.AlarmState,416512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almUnderRange.GlobalReset,416512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almUnderRange.FaultInAlarm,416512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almUnderRange.ALRM,416512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almUnderRange.ANUN,416512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almUnderRange.AKED,416512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almUnderRange.Resetable,416512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almUnderRange.REST,416512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almUnderRange.ACKN,416512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almUnderRange.UACK,416512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almUnderRange.MCmd_Enable,416512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almUnderRange.MCmd_Disable,416512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almUnderRange.OCmd_Shelve,416512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almUnderRange.OCmd_Unshelve,416512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almUnderRange.SCmd_Suppress,416512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almUnderRange.SCmd_UnSuppress,416513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almUnderRange.AEShelveTMRDN,416513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almUnderRange.Bad,416513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almUnderRange.Suppress,416514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.UnSuppress,416514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Shelve,416514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.UnShelve,416514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Enable,416514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Disable,416514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Ack,416514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Reset,416514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Suppressed,416514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Shelved,416514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Disabled,416514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Acked,416514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almUnderRange.Alarm,416514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Fault,416524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almRateOfChange.AlarmState,416524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almRateOfChange.GlobalReset,416524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almRateOfChange.FaultInAlarm,416524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almRateOfChange.ALRM,416524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almRateOfChange.ANUN,416524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almRateOfChange.AKED,416524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almRateOfChange.Resetable,416524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almRateOfChange.REST,416524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almRateOfChange.ACKN,416524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almRateOfChange.UACK,416524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almRateOfChange.MCmd_Enable,416524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.MCmd_Disable,416524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.OCmd_Shelve,416524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.OCmd_Unshelve,416524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.SCmd_Suppress,416524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.SCmd_UnSuppress,416525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almRateOfChange.AEShelveTMRDN,416525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almRateOfChange.Bad,416525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almRateOfChange.Suppress,416526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.UnSuppress,416526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Shelve,416526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.UnShelve,416526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Enable,416526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Disable,416526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Ack,416526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Reset,416526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Suppressed,416526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Shelved,416526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Disabled,416526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Acked,416526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almRateOfChange.Alarm,416526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Fault,416536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0104_1_PI.almPLCFault.AlarmState,416536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0104_1_PI.almPLCFault.GlobalReset,416536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0104_1_PI.almPLCFault.FaultInAlarm,416536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0104_1_PI.almPLCFault.ALRM,416536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0104_1_PI.almPLCFault.ANUN,416536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0104_1_PI.almPLCFault.AKED,416536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0104_1_PI.almPLCFault.Resetable,416536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0104_1_PI.almPLCFault.REST,416536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0104_1_PI.almPLCFault.ACKN,416536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0104_1_PI.almPLCFault.UACK,416536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0104_1_PI.almPLCFault.MCmd_Enable,416536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0104_1_PI.almPLCFault.MCmd_Disable,416536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0104_1_PI.almPLCFault.OCmd_Shelve,416536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0104_1_PI.almPLCFault.OCmd_Unshelve,416536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0104_1_PI.almPLCFault.SCmd_Suppress,416536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0104_1_PI.almPLCFault.SCmd_UnSuppress,416537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0104_1_PI.almPLCFault.AEShelveTMRDN,416537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0104_1_PI.almPLCFault.Bad,416537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0104_1_PI.almPLCFault.Suppress,416538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.UnSuppress,416538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Shelve,416538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.UnShelve,416538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Enable,416538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Disable,416538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Ack,416538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Reset,416538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Suppressed,416538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Shelved,416538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Disabled,416538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Acked,416538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0104_1_PI.almPLCFault.Alarm,416538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Fault,416640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almHighHigh.AlarmState,416640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almHighHigh.GlobalReset,416640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almHighHigh.FaultInAlarm,416640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almHighHigh.ALRM,416640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almHighHigh.ANUN,416640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almHighHigh.AKED,416640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almHighHigh.Resetable,416640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almHighHigh.REST,416640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almHighHigh.ACKN,416640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almHighHigh.UACK,416640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almHighHigh.MCmd_Enable,416640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.MCmd_Disable,416640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.OCmd_Shelve,416640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.OCmd_Unshelve,416640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.SCmd_Suppress,416640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.SCmd_UnSuppress,416641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almHighHigh.AEShelveTMRDN,416641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almHighHigh.Bad,416641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almHighHigh.Suppress,416642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.UnSuppress,416642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Shelve,416642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.UnShelve,416642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Enable,416642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Disable,416642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Ack,416642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Reset,416642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Suppressed,416642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Shelved,416642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Disabled,416642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Acked,416642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almHighHigh.Alarm,416642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Fault,416652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almHigh.AlarmState,416652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almHigh.GlobalReset,416652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almHigh.FaultInAlarm,416652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almHigh.ALRM,416652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almHigh.ANUN,416652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almHigh.AKED,416652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almHigh.Resetable,416652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almHigh.REST,416652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almHigh.ACKN,416652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almHigh.UACK,416652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almHigh.MCmd_Enable,416652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almHigh.MCmd_Disable,416652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almHigh.OCmd_Shelve,416652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almHigh.OCmd_Unshelve,416652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almHigh.SCmd_Suppress,416652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almHigh.SCmd_UnSuppress,416653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almHigh.AEShelveTMRDN,416653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almHigh.Bad,416653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almHigh.Suppress,416654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.UnSuppress,416654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Shelve,416654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.UnShelve,416654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Enable,416654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Disable,416654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Ack,416654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Reset,416654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almHigh.Suppressed,416654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almHigh.Shelved,416654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almHigh.Disabled,416654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almHigh.Acked,416654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almHigh.Alarm,416654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Fault,416664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almLow.AlarmState,416664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almLow.GlobalReset,416664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almLow.FaultInAlarm,416664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almLow.ALRM,416664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almLow.ANUN,416664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almLow.AKED,416664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almLow.Resetable,416664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almLow.REST,416664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almLow.ACKN,416664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almLow.UACK,416664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almLow.MCmd_Enable,416664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almLow.MCmd_Disable,416664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almLow.OCmd_Shelve,416664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almLow.OCmd_Unshelve,416664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almLow.SCmd_Suppress,416664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almLow.SCmd_UnSuppress,416665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almLow.AEShelveTMRDN,416665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almLow.Bad,416665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almLow.Suppress,416666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.UnSuppress,416666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Shelve,416666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.UnShelve,416666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Enable,416666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Disable,416666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Ack,416666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Reset,416666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almLow.Suppressed,416666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almLow.Shelved,416666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almLow.Disabled,416666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almLow.Acked,416666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almLow.Alarm,416666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Fault,416676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almLowLow.AlarmState,416676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almLowLow.GlobalReset,416676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almLowLow.FaultInAlarm,416676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almLowLow.ALRM,416676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almLowLow.ANUN,416676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almLowLow.AKED,416676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almLowLow.Resetable,416676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almLowLow.REST,416676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almLowLow.ACKN,416676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almLowLow.UACK,416676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almLowLow.MCmd_Enable,416676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almLowLow.MCmd_Disable,416676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almLowLow.OCmd_Shelve,416676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almLowLow.OCmd_Unshelve,416676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almLowLow.SCmd_Suppress,416676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almLowLow.SCmd_UnSuppress,416677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almLowLow.AEShelveTMRDN,416677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almLowLow.Bad,416677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almLowLow.Suppress,416678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.UnSuppress,416678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Shelve,416678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.UnShelve,416678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Enable,416678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Disable,416678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Ack,416678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Reset,416678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Suppressed,416678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Shelved,416678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Disabled,416678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Acked,416678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almLowLow.Alarm,416678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Fault,416688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almBrokenLoop.AlarmState,416688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almBrokenLoop.GlobalReset,416688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almBrokenLoop.FaultInAlarm,416688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almBrokenLoop.ALRM,416688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almBrokenLoop.ANUN,416688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almBrokenLoop.AKED,416688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almBrokenLoop.Resetable,416688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almBrokenLoop.REST,416688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almBrokenLoop.ACKN,416688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almBrokenLoop.UACK,416688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almBrokenLoop.MCmd_Enable,416688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.MCmd_Disable,416688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.OCmd_Shelve,416688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.OCmd_Unshelve,416688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.SCmd_Suppress,416688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.SCmd_UnSuppress,416689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almBrokenLoop.AEShelveTMRDN,416689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almBrokenLoop.Bad,416689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almBrokenLoop.Suppress,416690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.UnSuppress,416690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Shelve,416690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.UnShelve,416690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Enable,416690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Disable,416690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Ack,416690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Reset,416690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Suppressed,416690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Shelved,416690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Disabled,416690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Acked,416690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.Alarm,416690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Fault,416700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almOverRange.AlarmState,416700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almOverRange.GlobalReset,416700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almOverRange.FaultInAlarm,416700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almOverRange.ALRM,416700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almOverRange.ANUN,416700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almOverRange.AKED,416700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almOverRange.Resetable,416700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almOverRange.REST,416700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almOverRange.ACKN,416700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almOverRange.UACK,416700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almOverRange.MCmd_Enable,416700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almOverRange.MCmd_Disable,416700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almOverRange.OCmd_Shelve,416700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almOverRange.OCmd_Unshelve,416700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almOverRange.SCmd_Suppress,416700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almOverRange.SCmd_UnSuppress,416701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almOverRange.AEShelveTMRDN,416701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almOverRange.Bad,416701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almOverRange.Suppress,416702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.UnSuppress,416702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Shelve,416702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.UnShelve,416702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Enable,416702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Disable,416702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Ack,416702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Reset,416702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Suppressed,416702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Shelved,416702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Disabled,416702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Acked,416702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almOverRange.Alarm,416702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Fault,416712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almUnderRange.AlarmState,416712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almUnderRange.GlobalReset,416712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almUnderRange.FaultInAlarm,416712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almUnderRange.ALRM,416712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almUnderRange.ANUN,416712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almUnderRange.AKED,416712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almUnderRange.Resetable,416712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almUnderRange.REST,416712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almUnderRange.ACKN,416712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almUnderRange.UACK,416712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almUnderRange.MCmd_Enable,416712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.MCmd_Disable,416712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.OCmd_Shelve,416712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.OCmd_Unshelve,416712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.SCmd_Suppress,416712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.SCmd_UnSuppress,416713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almUnderRange.AEShelveTMRDN,416713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almUnderRange.Bad,416713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almUnderRange.Suppress,416714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.UnSuppress,416714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Shelve,416714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.UnShelve,416714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Enable,416714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Disable,416714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Ack,416714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Reset,416714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Suppressed,416714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Shelved,416714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Disabled,416714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Acked,416714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almUnderRange.Alarm,416714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Fault,416724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almRateOfChange.AlarmState,416724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almRateOfChange.GlobalReset,416724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almRateOfChange.FaultInAlarm,416724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almRateOfChange.ALRM,416724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almRateOfChange.ANUN,416724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almRateOfChange.AKED,416724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almRateOfChange.Resetable,416724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almRateOfChange.REST,416724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almRateOfChange.ACKN,416724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almRateOfChange.UACK,416724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almRateOfChange.MCmd_Enable,416724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.MCmd_Disable,416724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.OCmd_Shelve,416724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.OCmd_Unshelve,416724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.SCmd_Suppress,416724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.SCmd_UnSuppress,416725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almRateOfChange.AEShelveTMRDN,416725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almRateOfChange.Bad,416725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almRateOfChange.Suppress,416726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.UnSuppress,416726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Shelve,416726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.UnShelve,416726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Enable,416726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Disable,416726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Ack,416726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Reset,416726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Suppressed,416726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Shelved,416726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Disabled,416726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Acked,416726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almRateOfChange.Alarm,416726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Fault,416736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI1.almPLCFault.AlarmState,416736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI1.almPLCFault.GlobalReset,416736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI1.almPLCFault.FaultInAlarm,416736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI1.almPLCFault.ALRM,416736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI1.almPLCFault.ANUN,416736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI1.almPLCFault.AKED,416736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI1.almPLCFault.Resetable,416736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI1.almPLCFault.REST,416736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI1.almPLCFault.ACKN,416736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI1.almPLCFault.UACK,416736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI1.almPLCFault.MCmd_Enable,416736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.MCmd_Disable,416736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.OCmd_Shelve,416736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.OCmd_Unshelve,416736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.SCmd_Suppress,416736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.SCmd_UnSuppress,416737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI1.almPLCFault.AEShelveTMRDN,416737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI1.almPLCFault.Bad,416737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI1.almPLCFault.Suppress,416738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.UnSuppress,416738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Shelve,416738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.UnShelve,416738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Enable,416738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Disable,416738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Ack,416738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Reset,416738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Suppressed,416738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Shelved,416738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Disabled,416738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Acked,416738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI1.almPLCFault.Alarm,416738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Fault,416840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almHighHigh.AlarmState,416840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almHighHigh.GlobalReset,416840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almHighHigh.FaultInAlarm,416840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almHighHigh.ALRM,416840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almHighHigh.ANUN,416840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almHighHigh.AKED,416840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almHighHigh.Resetable,416840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almHighHigh.REST,416840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almHighHigh.ACKN,416840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almHighHigh.UACK,416840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almHighHigh.MCmd_Enable,416840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.MCmd_Disable,416840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.OCmd_Shelve,416840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.OCmd_Unshelve,416840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.SCmd_Suppress,416840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.SCmd_UnSuppress,416841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almHighHigh.AEShelveTMRDN,416841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almHighHigh.Bad,416841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almHighHigh.Suppress,416842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.UnSuppress,416842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Shelve,416842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.UnShelve,416842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Enable,416842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Disable,416842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Ack,416842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Reset,416842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Suppressed,416842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Shelved,416842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Disabled,416842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Acked,416842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almHighHigh.Alarm,416842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Fault,416852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almHigh.AlarmState,416852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almHigh.GlobalReset,416852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almHigh.FaultInAlarm,416852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almHigh.ALRM,416852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almHigh.ANUN,416852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almHigh.AKED,416852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almHigh.Resetable,416852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almHigh.REST,416852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almHigh.ACKN,416852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almHigh.UACK,416852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almHigh.MCmd_Enable,416852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almHigh.MCmd_Disable,416852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almHigh.OCmd_Shelve,416852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almHigh.OCmd_Unshelve,416852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almHigh.SCmd_Suppress,416852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almHigh.SCmd_UnSuppress,416853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almHigh.AEShelveTMRDN,416853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almHigh.Bad,416853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almHigh.Suppress,416854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.UnSuppress,416854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Shelve,416854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.UnShelve,416854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Enable,416854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Disable,416854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Ack,416854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Reset,416854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almHigh.Suppressed,416854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almHigh.Shelved,416854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almHigh.Disabled,416854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almHigh.Acked,416854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almHigh.Alarm,416854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Fault,416864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almLow.AlarmState,416864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almLow.GlobalReset,416864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almLow.FaultInAlarm,416864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almLow.ALRM,416864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almLow.ANUN,416864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almLow.AKED,416864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almLow.Resetable,416864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almLow.REST,416864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almLow.ACKN,416864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almLow.UACK,416864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almLow.MCmd_Enable,416864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almLow.MCmd_Disable,416864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almLow.OCmd_Shelve,416864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almLow.OCmd_Unshelve,416864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almLow.SCmd_Suppress,416864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almLow.SCmd_UnSuppress,416865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almLow.AEShelveTMRDN,416865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almLow.Bad,416865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almLow.Suppress,416866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.UnSuppress,416866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Shelve,416866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.UnShelve,416866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Enable,416866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Disable,416866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Ack,416866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Reset,416866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almLow.Suppressed,416866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almLow.Shelved,416866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almLow.Disabled,416866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almLow.Acked,416866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almLow.Alarm,416866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Fault,416876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almLowLow.AlarmState,416876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almLowLow.GlobalReset,416876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almLowLow.FaultInAlarm,416876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almLowLow.ALRM,416876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almLowLow.ANUN,416876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almLowLow.AKED,416876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almLowLow.Resetable,416876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almLowLow.REST,416876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almLowLow.ACKN,416876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almLowLow.UACK,416876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almLowLow.MCmd_Enable,416876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almLowLow.MCmd_Disable,416876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almLowLow.OCmd_Shelve,416876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almLowLow.OCmd_Unshelve,416876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almLowLow.SCmd_Suppress,416876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almLowLow.SCmd_UnSuppress,416877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almLowLow.AEShelveTMRDN,416877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almLowLow.Bad,416877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almLowLow.Suppress,416878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.UnSuppress,416878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Shelve,416878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.UnShelve,416878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Enable,416878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Disable,416878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Ack,416878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Reset,416878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Suppressed,416878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Shelved,416878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Disabled,416878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Acked,416878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almLowLow.Alarm,416878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Fault,416888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almBrokenLoop.AlarmState,416888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almBrokenLoop.GlobalReset,416888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almBrokenLoop.FaultInAlarm,416888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almBrokenLoop.ALRM,416888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almBrokenLoop.ANUN,416888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almBrokenLoop.AKED,416888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almBrokenLoop.Resetable,416888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almBrokenLoop.REST,416888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almBrokenLoop.ACKN,416888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almBrokenLoop.UACK,416888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almBrokenLoop.MCmd_Enable,416888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.MCmd_Disable,416888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.OCmd_Shelve,416888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.OCmd_Unshelve,416888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.SCmd_Suppress,416888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.SCmd_UnSuppress,416889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almBrokenLoop.AEShelveTMRDN,416889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almBrokenLoop.Bad,416889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almBrokenLoop.Suppress,416890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.UnSuppress,416890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Shelve,416890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.UnShelve,416890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Enable,416890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Disable,416890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Ack,416890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Reset,416890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Suppressed,416890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Shelved,416890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Disabled,416890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Acked,416890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.Alarm,416890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Fault,416900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almOverRange.AlarmState,416900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almOverRange.GlobalReset,416900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almOverRange.FaultInAlarm,416900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almOverRange.ALRM,416900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almOverRange.ANUN,416900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almOverRange.AKED,416900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almOverRange.Resetable,416900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almOverRange.REST,416900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almOverRange.ACKN,416900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almOverRange.UACK,416900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almOverRange.MCmd_Enable,416900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almOverRange.MCmd_Disable,416900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almOverRange.OCmd_Shelve,416900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almOverRange.OCmd_Unshelve,416900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almOverRange.SCmd_Suppress,416900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almOverRange.SCmd_UnSuppress,416901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almOverRange.AEShelveTMRDN,416901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almOverRange.Bad,416901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almOverRange.Suppress,416902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.UnSuppress,416902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Shelve,416902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.UnShelve,416902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Enable,416902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Disable,416902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Ack,416902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Reset,416902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Suppressed,416902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Shelved,416902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Disabled,416902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Acked,416902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almOverRange.Alarm,416902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Fault,416912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almUnderRange.AlarmState,416912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almUnderRange.GlobalReset,416912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almUnderRange.FaultInAlarm,416912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almUnderRange.ALRM,416912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almUnderRange.ANUN,416912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almUnderRange.AKED,416912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almUnderRange.Resetable,416912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almUnderRange.REST,416912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almUnderRange.ACKN,416912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almUnderRange.UACK,416912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almUnderRange.MCmd_Enable,416912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.MCmd_Disable,416912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.OCmd_Shelve,416912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.OCmd_Unshelve,416912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.SCmd_Suppress,416912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.SCmd_UnSuppress,416913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almUnderRange.AEShelveTMRDN,416913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almUnderRange.Bad,416913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almUnderRange.Suppress,416914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.UnSuppress,416914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Shelve,416914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.UnShelve,416914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Enable,416914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Disable,416914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Ack,416914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Reset,416914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Suppressed,416914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Shelved,416914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Disabled,416914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Acked,416914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almUnderRange.Alarm,416914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Fault,416924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almRateOfChange.AlarmState,416924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almRateOfChange.GlobalReset,416924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almRateOfChange.FaultInAlarm,416924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almRateOfChange.ALRM,416924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almRateOfChange.ANUN,416924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almRateOfChange.AKED,416924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almRateOfChange.Resetable,416924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almRateOfChange.REST,416924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almRateOfChange.ACKN,416924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almRateOfChange.UACK,416924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almRateOfChange.MCmd_Enable,416924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.MCmd_Disable,416924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.OCmd_Shelve,416924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.OCmd_Unshelve,416924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.SCmd_Suppress,416924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.SCmd_UnSuppress,416925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almRateOfChange.AEShelveTMRDN,416925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almRateOfChange.Bad,416925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almRateOfChange.Suppress,416926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.UnSuppress,416926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Shelve,416926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.UnShelve,416926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Enable,416926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Disable,416926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Ack,416926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Reset,416926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Suppressed,416926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Shelved,416926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Disabled,416926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Acked,416926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almRateOfChange.Alarm,416926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Fault,416936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI2.almPLCFault.AlarmState,416936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI2.almPLCFault.GlobalReset,416936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI2.almPLCFault.FaultInAlarm,416936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI2.almPLCFault.ALRM,416936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI2.almPLCFault.ANUN,416936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI2.almPLCFault.AKED,416936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI2.almPLCFault.Resetable,416936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI2.almPLCFault.REST,416936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI2.almPLCFault.ACKN,416936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI2.almPLCFault.UACK,416936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI2.almPLCFault.MCmd_Enable,416936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.MCmd_Disable,416936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.OCmd_Shelve,416936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.OCmd_Unshelve,416936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.SCmd_Suppress,416936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.SCmd_UnSuppress,416937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI2.almPLCFault.AEShelveTMRDN,416937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI2.almPLCFault.Bad,416937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI2.almPLCFault.Suppress,416938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.UnSuppress,416938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Shelve,416938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.UnShelve,416938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Enable,416938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Disable,416938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Ack,416938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Reset,416938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Suppressed,416938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Shelved,416938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Disabled,416938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Acked,416938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI2.almPLCFault.Alarm,416938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Fault,417040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almHighHigh.AlarmState,417040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almHighHigh.GlobalReset,417040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almHighHigh.FaultInAlarm,417040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almHighHigh.ALRM,417040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almHighHigh.ANUN,417040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almHighHigh.AKED,417040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almHighHigh.Resetable,417040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almHighHigh.REST,417040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almHighHigh.ACKN,417040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almHighHigh.UACK,417040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almHighHigh.MCmd_Enable,417040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.MCmd_Disable,417040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.OCmd_Shelve,417040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.OCmd_Unshelve,417040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.SCmd_Suppress,417040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.SCmd_UnSuppress,417041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almHighHigh.AEShelveTMRDN,417041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almHighHigh.Bad,417041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almHighHigh.Suppress,417042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.UnSuppress,417042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Shelve,417042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.UnShelve,417042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Enable,417042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Disable,417042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Ack,417042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Reset,417042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Suppressed,417042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Shelved,417042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Disabled,417042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Acked,417042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almHighHigh.Alarm,417042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Fault,417052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almHigh.AlarmState,417052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almHigh.GlobalReset,417052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almHigh.FaultInAlarm,417052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almHigh.ALRM,417052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almHigh.ANUN,417052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almHigh.AKED,417052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almHigh.Resetable,417052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almHigh.REST,417052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almHigh.ACKN,417052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almHigh.UACK,417052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almHigh.MCmd_Enable,417052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almHigh.MCmd_Disable,417052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almHigh.OCmd_Shelve,417052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almHigh.OCmd_Unshelve,417052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almHigh.SCmd_Suppress,417052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almHigh.SCmd_UnSuppress,417053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almHigh.AEShelveTMRDN,417053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almHigh.Bad,417053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almHigh.Suppress,417054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.UnSuppress,417054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Shelve,417054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.UnShelve,417054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Enable,417054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Disable,417054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Ack,417054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Reset,417054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almHigh.Suppressed,417054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almHigh.Shelved,417054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almHigh.Disabled,417054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almHigh.Acked,417054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almHigh.Alarm,417054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Fault,417064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almLow.AlarmState,417064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almLow.GlobalReset,417064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almLow.FaultInAlarm,417064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almLow.ALRM,417064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almLow.ANUN,417064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almLow.AKED,417064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almLow.Resetable,417064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almLow.REST,417064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almLow.ACKN,417064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almLow.UACK,417064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almLow.MCmd_Enable,417064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almLow.MCmd_Disable,417064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almLow.OCmd_Shelve,417064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almLow.OCmd_Unshelve,417064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almLow.SCmd_Suppress,417064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almLow.SCmd_UnSuppress,417065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almLow.AEShelveTMRDN,417065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almLow.Bad,417065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almLow.Suppress,417066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.UnSuppress,417066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Shelve,417066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.UnShelve,417066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Enable,417066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Disable,417066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Ack,417066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Reset,417066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almLow.Suppressed,417066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almLow.Shelved,417066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almLow.Disabled,417066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almLow.Acked,417066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almLow.Alarm,417066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Fault,417076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almLowLow.AlarmState,417076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almLowLow.GlobalReset,417076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almLowLow.FaultInAlarm,417076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almLowLow.ALRM,417076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almLowLow.ANUN,417076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almLowLow.AKED,417076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almLowLow.Resetable,417076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almLowLow.REST,417076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almLowLow.ACKN,417076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almLowLow.UACK,417076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almLowLow.MCmd_Enable,417076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almLowLow.MCmd_Disable,417076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almLowLow.OCmd_Shelve,417076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almLowLow.OCmd_Unshelve,417076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almLowLow.SCmd_Suppress,417076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almLowLow.SCmd_UnSuppress,417077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almLowLow.AEShelveTMRDN,417077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almLowLow.Bad,417077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almLowLow.Suppress,417078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.UnSuppress,417078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Shelve,417078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.UnShelve,417078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Enable,417078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Disable,417078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Ack,417078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Reset,417078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Suppressed,417078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Shelved,417078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Disabled,417078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Acked,417078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almLowLow.Alarm,417078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Fault,417088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almBrokenLoop.AlarmState,417088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almBrokenLoop.GlobalReset,417088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almBrokenLoop.FaultInAlarm,417088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almBrokenLoop.ALRM,417088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almBrokenLoop.ANUN,417088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almBrokenLoop.AKED,417088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almBrokenLoop.Resetable,417088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almBrokenLoop.REST,417088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almBrokenLoop.ACKN,417088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almBrokenLoop.UACK,417088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almBrokenLoop.MCmd_Enable,417088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.MCmd_Disable,417088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.OCmd_Shelve,417088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.OCmd_Unshelve,417088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.SCmd_Suppress,417088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.SCmd_UnSuppress,417089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almBrokenLoop.AEShelveTMRDN,417089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almBrokenLoop.Bad,417089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almBrokenLoop.Suppress,417090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.UnSuppress,417090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Shelve,417090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.UnShelve,417090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Enable,417090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Disable,417090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Ack,417090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Reset,417090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Suppressed,417090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Shelved,417090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Disabled,417090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Acked,417090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.Alarm,417090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Fault,417100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almOverRange.AlarmState,417100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almOverRange.GlobalReset,417100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almOverRange.FaultInAlarm,417100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almOverRange.ALRM,417100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almOverRange.ANUN,417100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almOverRange.AKED,417100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almOverRange.Resetable,417100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almOverRange.REST,417100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almOverRange.ACKN,417100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almOverRange.UACK,417100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almOverRange.MCmd_Enable,417100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almOverRange.MCmd_Disable,417100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almOverRange.OCmd_Shelve,417100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almOverRange.OCmd_Unshelve,417100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almOverRange.SCmd_Suppress,417100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almOverRange.SCmd_UnSuppress,417101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almOverRange.AEShelveTMRDN,417101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almOverRange.Bad,417101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almOverRange.Suppress,417102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.UnSuppress,417102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Shelve,417102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.UnShelve,417102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Enable,417102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Disable,417102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Ack,417102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Reset,417102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Suppressed,417102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Shelved,417102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Disabled,417102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Acked,417102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almOverRange.Alarm,417102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Fault,417112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almUnderRange.AlarmState,417112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almUnderRange.GlobalReset,417112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almUnderRange.FaultInAlarm,417112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almUnderRange.ALRM,417112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almUnderRange.ANUN,417112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almUnderRange.AKED,417112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almUnderRange.Resetable,417112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almUnderRange.REST,417112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almUnderRange.ACKN,417112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almUnderRange.UACK,417112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almUnderRange.MCmd_Enable,417112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.MCmd_Disable,417112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.OCmd_Shelve,417112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.OCmd_Unshelve,417112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.SCmd_Suppress,417112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.SCmd_UnSuppress,417113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almUnderRange.AEShelveTMRDN,417113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almUnderRange.Bad,417113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almUnderRange.Suppress,417114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.UnSuppress,417114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Shelve,417114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.UnShelve,417114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Enable,417114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Disable,417114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Ack,417114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Reset,417114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Suppressed,417114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Shelved,417114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Disabled,417114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Acked,417114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almUnderRange.Alarm,417114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Fault,417124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almRateOfChange.AlarmState,417124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almRateOfChange.GlobalReset,417124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almRateOfChange.FaultInAlarm,417124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almRateOfChange.ALRM,417124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almRateOfChange.ANUN,417124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almRateOfChange.AKED,417124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almRateOfChange.Resetable,417124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almRateOfChange.REST,417124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almRateOfChange.ACKN,417124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almRateOfChange.UACK,417124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almRateOfChange.MCmd_Enable,417124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.MCmd_Disable,417124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.OCmd_Shelve,417124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.OCmd_Unshelve,417124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.SCmd_Suppress,417124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.SCmd_UnSuppress,417125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almRateOfChange.AEShelveTMRDN,417125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almRateOfChange.Bad,417125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almRateOfChange.Suppress,417126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.UnSuppress,417126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Shelve,417126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.UnShelve,417126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Enable,417126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Disable,417126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Ack,417126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Reset,417126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Suppressed,417126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Shelved,417126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Disabled,417126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Acked,417126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almRateOfChange.Alarm,417126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Fault,417136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI3.almPLCFault.AlarmState,417136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI3.almPLCFault.GlobalReset,417136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI3.almPLCFault.FaultInAlarm,417136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI3.almPLCFault.ALRM,417136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI3.almPLCFault.ANUN,417136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI3.almPLCFault.AKED,417136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI3.almPLCFault.Resetable,417136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI3.almPLCFault.REST,417136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI3.almPLCFault.ACKN,417136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI3.almPLCFault.UACK,417136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI3.almPLCFault.MCmd_Enable,417136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.MCmd_Disable,417136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.OCmd_Shelve,417136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.OCmd_Unshelve,417136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.SCmd_Suppress,417136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.SCmd_UnSuppress,417137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI3.almPLCFault.AEShelveTMRDN,417137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI3.almPLCFault.Bad,417137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI3.almPLCFault.Suppress,417138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.UnSuppress,417138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Shelve,417138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.UnShelve,417138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Enable,417138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Disable,417138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Ack,417138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Reset,417138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Suppressed,417138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Shelved,417138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Disabled,417138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Acked,417138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI3.almPLCFault.Alarm,417138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Fault,417240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almHighHigh.AlarmState,417240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almHighHigh.GlobalReset,417240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almHighHigh.FaultInAlarm,417240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almHighHigh.ALRM,417240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almHighHigh.ANUN,417240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almHighHigh.AKED,417240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almHighHigh.Resetable,417240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almHighHigh.REST,417240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almHighHigh.ACKN,417240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almHighHigh.UACK,417240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almHighHigh.MCmd_Enable,417240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.MCmd_Disable,417240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.OCmd_Shelve,417240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.OCmd_Unshelve,417240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.SCmd_Suppress,417240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.SCmd_UnSuppress,417241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almHighHigh.AEShelveTMRDN,417241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almHighHigh.Bad,417241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almHighHigh.Suppress,417242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.UnSuppress,417242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Shelve,417242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.UnShelve,417242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Enable,417242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Disable,417242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Ack,417242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Reset,417242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Suppressed,417242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Shelved,417242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Disabled,417242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Acked,417242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almHighHigh.Alarm,417242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Fault,417252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almHigh.AlarmState,417252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almHigh.GlobalReset,417252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almHigh.FaultInAlarm,417252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almHigh.ALRM,417252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almHigh.ANUN,417252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almHigh.AKED,417252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almHigh.Resetable,417252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almHigh.REST,417252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almHigh.ACKN,417252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almHigh.UACK,417252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almHigh.MCmd_Enable,417252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almHigh.MCmd_Disable,417252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almHigh.OCmd_Shelve,417252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almHigh.OCmd_Unshelve,417252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almHigh.SCmd_Suppress,417252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almHigh.SCmd_UnSuppress,417253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almHigh.AEShelveTMRDN,417253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almHigh.Bad,417253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almHigh.Suppress,417254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.UnSuppress,417254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Shelve,417254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.UnShelve,417254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Enable,417254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Disable,417254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Ack,417254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Reset,417254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almHigh.Suppressed,417254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almHigh.Shelved,417254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almHigh.Disabled,417254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almHigh.Acked,417254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almHigh.Alarm,417254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Fault,417264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almLow.AlarmState,417264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almLow.GlobalReset,417264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almLow.FaultInAlarm,417264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almLow.ALRM,417264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almLow.ANUN,417264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almLow.AKED,417264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almLow.Resetable,417264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almLow.REST,417264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almLow.ACKN,417264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almLow.UACK,417264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almLow.MCmd_Enable,417264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almLow.MCmd_Disable,417264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almLow.OCmd_Shelve,417264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almLow.OCmd_Unshelve,417264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almLow.SCmd_Suppress,417264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almLow.SCmd_UnSuppress,417265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almLow.AEShelveTMRDN,417265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almLow.Bad,417265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almLow.Suppress,417266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.UnSuppress,417266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Shelve,417266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.UnShelve,417266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Enable,417266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Disable,417266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Ack,417266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Reset,417266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almLow.Suppressed,417266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almLow.Shelved,417266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almLow.Disabled,417266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almLow.Acked,417266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almLow.Alarm,417266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Fault,417276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almLowLow.AlarmState,417276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almLowLow.GlobalReset,417276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almLowLow.FaultInAlarm,417276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almLowLow.ALRM,417276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almLowLow.ANUN,417276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almLowLow.AKED,417276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almLowLow.Resetable,417276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almLowLow.REST,417276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almLowLow.ACKN,417276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almLowLow.UACK,417276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almLowLow.MCmd_Enable,417276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almLowLow.MCmd_Disable,417276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almLowLow.OCmd_Shelve,417276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almLowLow.OCmd_Unshelve,417276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almLowLow.SCmd_Suppress,417276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almLowLow.SCmd_UnSuppress,417277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almLowLow.AEShelveTMRDN,417277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almLowLow.Bad,417277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almLowLow.Suppress,417278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.UnSuppress,417278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Shelve,417278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.UnShelve,417278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Enable,417278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Disable,417278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Ack,417278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Reset,417278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Suppressed,417278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Shelved,417278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Disabled,417278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Acked,417278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almLowLow.Alarm,417278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Fault,417288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almBrokenLoop.AlarmState,417288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almBrokenLoop.GlobalReset,417288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almBrokenLoop.FaultInAlarm,417288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almBrokenLoop.ALRM,417288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almBrokenLoop.ANUN,417288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almBrokenLoop.AKED,417288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almBrokenLoop.Resetable,417288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almBrokenLoop.REST,417288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almBrokenLoop.ACKN,417288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almBrokenLoop.UACK,417288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almBrokenLoop.MCmd_Enable,417288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.MCmd_Disable,417288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.OCmd_Shelve,417288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.OCmd_Unshelve,417288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.SCmd_Suppress,417288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.SCmd_UnSuppress,417289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almBrokenLoop.AEShelveTMRDN,417289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almBrokenLoop.Bad,417289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almBrokenLoop.Suppress,417290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.UnSuppress,417290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Shelve,417290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.UnShelve,417290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Enable,417290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Disable,417290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Ack,417290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Reset,417290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Suppressed,417290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Shelved,417290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Disabled,417290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Acked,417290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.Alarm,417290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Fault,417300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almOverRange.AlarmState,417300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almOverRange.GlobalReset,417300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almOverRange.FaultInAlarm,417300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almOverRange.ALRM,417300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almOverRange.ANUN,417300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almOverRange.AKED,417300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almOverRange.Resetable,417300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almOverRange.REST,417300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almOverRange.ACKN,417300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almOverRange.UACK,417300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almOverRange.MCmd_Enable,417300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almOverRange.MCmd_Disable,417300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almOverRange.OCmd_Shelve,417300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almOverRange.OCmd_Unshelve,417300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almOverRange.SCmd_Suppress,417300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almOverRange.SCmd_UnSuppress,417301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almOverRange.AEShelveTMRDN,417301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almOverRange.Bad,417301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almOverRange.Suppress,417302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.UnSuppress,417302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Shelve,417302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.UnShelve,417302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Enable,417302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Disable,417302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Ack,417302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Reset,417302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Suppressed,417302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Shelved,417302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Disabled,417302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Acked,417302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almOverRange.Alarm,417302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Fault,417312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almUnderRange.AlarmState,417312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almUnderRange.GlobalReset,417312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almUnderRange.FaultInAlarm,417312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almUnderRange.ALRM,417312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almUnderRange.ANUN,417312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almUnderRange.AKED,417312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almUnderRange.Resetable,417312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almUnderRange.REST,417312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almUnderRange.ACKN,417312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almUnderRange.UACK,417312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almUnderRange.MCmd_Enable,417312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.MCmd_Disable,417312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.OCmd_Shelve,417312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.OCmd_Unshelve,417312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.SCmd_Suppress,417312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.SCmd_UnSuppress,417313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almUnderRange.AEShelveTMRDN,417313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almUnderRange.Bad,417313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almUnderRange.Suppress,417314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.UnSuppress,417314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Shelve,417314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.UnShelve,417314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Enable,417314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Disable,417314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Ack,417314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Reset,417314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Suppressed,417314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Shelved,417314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Disabled,417314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Acked,417314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almUnderRange.Alarm,417314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Fault,417324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almRateOfChange.AlarmState,417324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almRateOfChange.GlobalReset,417324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almRateOfChange.FaultInAlarm,417324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almRateOfChange.ALRM,417324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almRateOfChange.ANUN,417324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almRateOfChange.AKED,417324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almRateOfChange.Resetable,417324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almRateOfChange.REST,417324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almRateOfChange.ACKN,417324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almRateOfChange.UACK,417324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almRateOfChange.MCmd_Enable,417324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.MCmd_Disable,417324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.OCmd_Shelve,417324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.OCmd_Unshelve,417324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.SCmd_Suppress,417324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.SCmd_UnSuppress,417325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almRateOfChange.AEShelveTMRDN,417325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almRateOfChange.Bad,417325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almRateOfChange.Suppress,417326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.UnSuppress,417326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Shelve,417326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.UnShelve,417326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Enable,417326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Disable,417326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Ack,417326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Reset,417326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Suppressed,417326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Shelved,417326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Disabled,417326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Acked,417326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almRateOfChange.Alarm,417326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Fault,417336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI4.almPLCFault.AlarmState,417336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI4.almPLCFault.GlobalReset,417336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI4.almPLCFault.FaultInAlarm,417336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI4.almPLCFault.ALRM,417336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI4.almPLCFault.ANUN,417336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI4.almPLCFault.AKED,417336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI4.almPLCFault.Resetable,417336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI4.almPLCFault.REST,417336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI4.almPLCFault.ACKN,417336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI4.almPLCFault.UACK,417336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI4.almPLCFault.MCmd_Enable,417336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.MCmd_Disable,417336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.OCmd_Shelve,417336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.OCmd_Unshelve,417336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.SCmd_Suppress,417336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.SCmd_UnSuppress,417337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI4.almPLCFault.AEShelveTMRDN,417337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI4.almPLCFault.Bad,417337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI4.almPLCFault.Suppress,417338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.UnSuppress,417338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Shelve,417338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.UnShelve,417338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Enable,417338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Disable,417338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Ack,417338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Reset,417338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Suppressed,417338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Shelved,417338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Disabled,417338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Acked,417338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI4.almPLCFault.Alarm,417338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Fault,417440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almHighHigh.AlarmState,417440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almHighHigh.GlobalReset,417440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almHighHigh.FaultInAlarm,417440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almHighHigh.ALRM,417440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almHighHigh.ANUN,417440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almHighHigh.AKED,417440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almHighHigh.Resetable,417440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almHighHigh.REST,417440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almHighHigh.ACKN,417440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almHighHigh.UACK,417440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almHighHigh.MCmd_Enable,417440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.MCmd_Disable,417440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.OCmd_Shelve,417440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.OCmd_Unshelve,417440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.SCmd_Suppress,417440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.SCmd_UnSuppress,417441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almHighHigh.AEShelveTMRDN,417441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almHighHigh.Bad,417441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almHighHigh.Suppress,417442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.UnSuppress,417442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Shelve,417442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.UnShelve,417442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Enable,417442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Disable,417442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Ack,417442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Reset,417442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Suppressed,417442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Shelved,417442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Disabled,417442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Acked,417442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almHighHigh.Alarm,417442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Fault,417452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almHigh.AlarmState,417452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almHigh.GlobalReset,417452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almHigh.FaultInAlarm,417452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almHigh.ALRM,417452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almHigh.ANUN,417452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almHigh.AKED,417452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almHigh.Resetable,417452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almHigh.REST,417452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almHigh.ACKN,417452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almHigh.UACK,417452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almHigh.MCmd_Enable,417452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almHigh.MCmd_Disable,417452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almHigh.OCmd_Shelve,417452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almHigh.OCmd_Unshelve,417452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almHigh.SCmd_Suppress,417452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almHigh.SCmd_UnSuppress,417453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almHigh.AEShelveTMRDN,417453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almHigh.Bad,417453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almHigh.Suppress,417454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.UnSuppress,417454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Shelve,417454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.UnShelve,417454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Enable,417454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Disable,417454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Ack,417454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Reset,417454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almHigh.Suppressed,417454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almHigh.Shelved,417454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almHigh.Disabled,417454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almHigh.Acked,417454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almHigh.Alarm,417454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Fault,417464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almLow.AlarmState,417464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almLow.GlobalReset,417464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almLow.FaultInAlarm,417464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almLow.ALRM,417464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almLow.ANUN,417464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almLow.AKED,417464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almLow.Resetable,417464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almLow.REST,417464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almLow.ACKN,417464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almLow.UACK,417464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almLow.MCmd_Enable,417464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almLow.MCmd_Disable,417464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almLow.OCmd_Shelve,417464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almLow.OCmd_Unshelve,417464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almLow.SCmd_Suppress,417464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almLow.SCmd_UnSuppress,417465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almLow.AEShelveTMRDN,417465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almLow.Bad,417465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almLow.Suppress,417466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.UnSuppress,417466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Shelve,417466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.UnShelve,417466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Enable,417466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Disable,417466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Ack,417466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Reset,417466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almLow.Suppressed,417466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almLow.Shelved,417466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almLow.Disabled,417466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almLow.Acked,417466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almLow.Alarm,417466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Fault,417476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almLowLow.AlarmState,417476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almLowLow.GlobalReset,417476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almLowLow.FaultInAlarm,417476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almLowLow.ALRM,417476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almLowLow.ANUN,417476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almLowLow.AKED,417476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almLowLow.Resetable,417476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almLowLow.REST,417476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almLowLow.ACKN,417476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almLowLow.UACK,417476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almLowLow.MCmd_Enable,417476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almLowLow.MCmd_Disable,417476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almLowLow.OCmd_Shelve,417476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almLowLow.OCmd_Unshelve,417476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almLowLow.SCmd_Suppress,417476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almLowLow.SCmd_UnSuppress,417477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almLowLow.AEShelveTMRDN,417477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almLowLow.Bad,417477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almLowLow.Suppress,417478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.UnSuppress,417478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Shelve,417478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.UnShelve,417478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Enable,417478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Disable,417478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Ack,417478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Reset,417478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Suppressed,417478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Shelved,417478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Disabled,417478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Acked,417478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almLowLow.Alarm,417478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Fault,417488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almBrokenLoop.AlarmState,417488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almBrokenLoop.GlobalReset,417488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almBrokenLoop.FaultInAlarm,417488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almBrokenLoop.ALRM,417488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almBrokenLoop.ANUN,417488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almBrokenLoop.AKED,417488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almBrokenLoop.Resetable,417488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almBrokenLoop.REST,417488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almBrokenLoop.ACKN,417488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almBrokenLoop.UACK,417488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almBrokenLoop.MCmd_Enable,417488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.MCmd_Disable,417488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.OCmd_Shelve,417488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.OCmd_Unshelve,417488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.SCmd_Suppress,417488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.SCmd_UnSuppress,417489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almBrokenLoop.AEShelveTMRDN,417489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almBrokenLoop.Bad,417489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almBrokenLoop.Suppress,417490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.UnSuppress,417490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Shelve,417490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.UnShelve,417490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Enable,417490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Disable,417490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Ack,417490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Reset,417490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Suppressed,417490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Shelved,417490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Disabled,417490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Acked,417490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.Alarm,417490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Fault,417500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almOverRange.AlarmState,417500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almOverRange.GlobalReset,417500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almOverRange.FaultInAlarm,417500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almOverRange.ALRM,417500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almOverRange.ANUN,417500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almOverRange.AKED,417500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almOverRange.Resetable,417500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almOverRange.REST,417500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almOverRange.ACKN,417500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almOverRange.UACK,417500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almOverRange.MCmd_Enable,417500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almOverRange.MCmd_Disable,417500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almOverRange.OCmd_Shelve,417500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almOverRange.OCmd_Unshelve,417500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almOverRange.SCmd_Suppress,417500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almOverRange.SCmd_UnSuppress,417501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almOverRange.AEShelveTMRDN,417501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almOverRange.Bad,417501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almOverRange.Suppress,417502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.UnSuppress,417502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Shelve,417502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.UnShelve,417502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Enable,417502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Disable,417502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Ack,417502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Reset,417502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Suppressed,417502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Shelved,417502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Disabled,417502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Acked,417502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almOverRange.Alarm,417502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Fault,417512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almUnderRange.AlarmState,417512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almUnderRange.GlobalReset,417512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almUnderRange.FaultInAlarm,417512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almUnderRange.ALRM,417512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almUnderRange.ANUN,417512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almUnderRange.AKED,417512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almUnderRange.Resetable,417512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almUnderRange.REST,417512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almUnderRange.ACKN,417512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almUnderRange.UACK,417512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almUnderRange.MCmd_Enable,417512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.MCmd_Disable,417512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.OCmd_Shelve,417512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.OCmd_Unshelve,417512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.SCmd_Suppress,417512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.SCmd_UnSuppress,417513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almUnderRange.AEShelveTMRDN,417513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almUnderRange.Bad,417513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almUnderRange.Suppress,417514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.UnSuppress,417514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Shelve,417514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.UnShelve,417514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Enable,417514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Disable,417514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Ack,417514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Reset,417514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Suppressed,417514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Shelved,417514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Disabled,417514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Acked,417514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almUnderRange.Alarm,417514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Fault,417524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almRateOfChange.AlarmState,417524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almRateOfChange.GlobalReset,417524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almRateOfChange.FaultInAlarm,417524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almRateOfChange.ALRM,417524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almRateOfChange.ANUN,417524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almRateOfChange.AKED,417524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almRateOfChange.Resetable,417524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almRateOfChange.REST,417524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almRateOfChange.ACKN,417524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almRateOfChange.UACK,417524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almRateOfChange.MCmd_Enable,417524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.MCmd_Disable,417524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.OCmd_Shelve,417524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.OCmd_Unshelve,417524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.SCmd_Suppress,417524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.SCmd_UnSuppress,417525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almRateOfChange.AEShelveTMRDN,417525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almRateOfChange.Bad,417525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almRateOfChange.Suppress,417526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.UnSuppress,417526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Shelve,417526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.UnShelve,417526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Enable,417526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Disable,417526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Ack,417526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Reset,417526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Suppressed,417526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Shelved,417526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Disabled,417526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Acked,417526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almRateOfChange.Alarm,417526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Fault,417536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_1_VI5.almPLCFault.AlarmState,417536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_1_VI5.almPLCFault.GlobalReset,417536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_1_VI5.almPLCFault.FaultInAlarm,417536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_1_VI5.almPLCFault.ALRM,417536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_1_VI5.almPLCFault.ANUN,417536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_1_VI5.almPLCFault.AKED,417536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_1_VI5.almPLCFault.Resetable,417536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_1_VI5.almPLCFault.REST,417536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_1_VI5.almPLCFault.ACKN,417536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_1_VI5.almPLCFault.UACK,417536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_1_VI5.almPLCFault.MCmd_Enable,417536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.MCmd_Disable,417536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.OCmd_Shelve,417536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.OCmd_Unshelve,417536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.SCmd_Suppress,417536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.SCmd_UnSuppress,417537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_1_VI5.almPLCFault.AEShelveTMRDN,417537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_1_VI5.almPLCFault.Bad,417537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_1_VI5.almPLCFault.Suppress,417538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.UnSuppress,417538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Shelve,417538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.UnShelve,417538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Enable,417538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Disable,417538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Ack,417538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Reset,417538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Suppressed,417538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Shelved,417538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Disabled,417538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Acked,417538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_1_VI5.almPLCFault.Alarm,417538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Fault,417640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almHighHigh.AlarmState,417640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almHighHigh.GlobalReset,417640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almHighHigh.FaultInAlarm,417640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almHighHigh.ALRM,417640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almHighHigh.ANUN,417640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almHighHigh.AKED,417640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almHighHigh.Resetable,417640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almHighHigh.REST,417640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almHighHigh.ACKN,417640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almHighHigh.UACK,417640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almHighHigh.MCmd_Enable,417640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.MCmd_Disable,417640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.OCmd_Shelve,417640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.OCmd_Unshelve,417640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.SCmd_Suppress,417640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.SCmd_UnSuppress,417641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almHighHigh.AEShelveTMRDN,417641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almHighHigh.Bad,417641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almHighHigh.Suppress,417642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.UnSuppress,417642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Shelve,417642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.UnShelve,417642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Enable,417642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Disable,417642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Ack,417642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Reset,417642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Suppressed,417642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Shelved,417642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Disabled,417642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Acked,417642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almHighHigh.Alarm,417642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Fault,417652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almHigh.AlarmState,417652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almHigh.GlobalReset,417652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almHigh.FaultInAlarm,417652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almHigh.ALRM,417652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almHigh.ANUN,417652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almHigh.AKED,417652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almHigh.Resetable,417652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almHigh.REST,417652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almHigh.ACKN,417652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almHigh.UACK,417652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almHigh.MCmd_Enable,417652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almHigh.MCmd_Disable,417652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almHigh.OCmd_Shelve,417652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almHigh.OCmd_Unshelve,417652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almHigh.SCmd_Suppress,417652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almHigh.SCmd_UnSuppress,417653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almHigh.AEShelveTMRDN,417653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almHigh.Bad,417653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almHigh.Suppress,417654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.UnSuppress,417654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Shelve,417654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.UnShelve,417654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Enable,417654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Disable,417654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Ack,417654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Reset,417654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almHigh.Suppressed,417654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almHigh.Shelved,417654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almHigh.Disabled,417654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almHigh.Acked,417654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almHigh.Alarm,417654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Fault,417664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almLow.AlarmState,417664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almLow.GlobalReset,417664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almLow.FaultInAlarm,417664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almLow.ALRM,417664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almLow.ANUN,417664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almLow.AKED,417664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almLow.Resetable,417664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almLow.REST,417664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almLow.ACKN,417664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almLow.UACK,417664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almLow.MCmd_Enable,417664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almLow.MCmd_Disable,417664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almLow.OCmd_Shelve,417664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almLow.OCmd_Unshelve,417664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almLow.SCmd_Suppress,417664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almLow.SCmd_UnSuppress,417665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almLow.AEShelveTMRDN,417665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almLow.Bad,417665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almLow.Suppress,417666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.UnSuppress,417666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Shelve,417666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.UnShelve,417666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Enable,417666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Disable,417666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Ack,417666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Reset,417666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almLow.Suppressed,417666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almLow.Shelved,417666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almLow.Disabled,417666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almLow.Acked,417666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almLow.Alarm,417666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Fault,417676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almLowLow.AlarmState,417676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almLowLow.GlobalReset,417676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almLowLow.FaultInAlarm,417676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almLowLow.ALRM,417676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almLowLow.ANUN,417676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almLowLow.AKED,417676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almLowLow.Resetable,417676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almLowLow.REST,417676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almLowLow.ACKN,417676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almLowLow.UACK,417676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almLowLow.MCmd_Enable,417676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almLowLow.MCmd_Disable,417676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almLowLow.OCmd_Shelve,417676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almLowLow.OCmd_Unshelve,417676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almLowLow.SCmd_Suppress,417676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almLowLow.SCmd_UnSuppress,417677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almLowLow.AEShelveTMRDN,417677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almLowLow.Bad,417677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almLowLow.Suppress,417678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.UnSuppress,417678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Shelve,417678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.UnShelve,417678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Enable,417678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Disable,417678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Ack,417678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Reset,417678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Suppressed,417678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Shelved,417678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Disabled,417678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Acked,417678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almLowLow.Alarm,417678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Fault,417688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almBrokenLoop.AlarmState,417688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almBrokenLoop.GlobalReset,417688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almBrokenLoop.FaultInAlarm,417688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almBrokenLoop.ALRM,417688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almBrokenLoop.ANUN,417688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almBrokenLoop.AKED,417688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almBrokenLoop.Resetable,417688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almBrokenLoop.REST,417688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almBrokenLoop.ACKN,417688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almBrokenLoop.UACK,417688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almBrokenLoop.MCmd_Enable,417688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.MCmd_Disable,417688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.OCmd_Shelve,417688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.OCmd_Unshelve,417688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.SCmd_Suppress,417688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.SCmd_UnSuppress,417689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almBrokenLoop.AEShelveTMRDN,417689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almBrokenLoop.Bad,417689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almBrokenLoop.Suppress,417690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.UnSuppress,417690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Shelve,417690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.UnShelve,417690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Enable,417690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Disable,417690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Ack,417690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Reset,417690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Suppressed,417690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Shelved,417690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Disabled,417690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Acked,417690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.Alarm,417690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Fault,417700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almOverRange.AlarmState,417700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almOverRange.GlobalReset,417700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almOverRange.FaultInAlarm,417700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almOverRange.ALRM,417700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almOverRange.ANUN,417700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almOverRange.AKED,417700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almOverRange.Resetable,417700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almOverRange.REST,417700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almOverRange.ACKN,417700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almOverRange.UACK,417700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almOverRange.MCmd_Enable,417700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almOverRange.MCmd_Disable,417700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almOverRange.OCmd_Shelve,417700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almOverRange.OCmd_Unshelve,417700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almOverRange.SCmd_Suppress,417700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almOverRange.SCmd_UnSuppress,417701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almOverRange.AEShelveTMRDN,417701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almOverRange.Bad,417701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almOverRange.Suppress,417702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.UnSuppress,417702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Shelve,417702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.UnShelve,417702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Enable,417702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Disable,417702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Ack,417702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Reset,417702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Suppressed,417702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Shelved,417702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Disabled,417702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Acked,417702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almOverRange.Alarm,417702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Fault,417712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almUnderRange.AlarmState,417712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almUnderRange.GlobalReset,417712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almUnderRange.FaultInAlarm,417712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almUnderRange.ALRM,417712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almUnderRange.ANUN,417712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almUnderRange.AKED,417712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almUnderRange.Resetable,417712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almUnderRange.REST,417712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almUnderRange.ACKN,417712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almUnderRange.UACK,417712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almUnderRange.MCmd_Enable,417712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.MCmd_Disable,417712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.OCmd_Shelve,417712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.OCmd_Unshelve,417712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.SCmd_Suppress,417712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.SCmd_UnSuppress,417713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almUnderRange.AEShelveTMRDN,417713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almUnderRange.Bad,417713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almUnderRange.Suppress,417714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.UnSuppress,417714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Shelve,417714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.UnShelve,417714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Enable,417714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Disable,417714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Ack,417714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Reset,417714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Suppressed,417714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Shelved,417714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Disabled,417714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Acked,417714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almUnderRange.Alarm,417714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Fault,417724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almRateOfChange.AlarmState,417724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almRateOfChange.GlobalReset,417724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almRateOfChange.FaultInAlarm,417724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almRateOfChange.ALRM,417724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almRateOfChange.ANUN,417724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almRateOfChange.AKED,417724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almRateOfChange.Resetable,417724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almRateOfChange.REST,417724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almRateOfChange.ACKN,417724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almRateOfChange.UACK,417724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almRateOfChange.MCmd_Enable,417724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.MCmd_Disable,417724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.OCmd_Shelve,417724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.OCmd_Unshelve,417724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.SCmd_Suppress,417724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.SCmd_UnSuppress,417725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almRateOfChange.AEShelveTMRDN,417725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almRateOfChange.Bad,417725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almRateOfChange.Suppress,417726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.UnSuppress,417726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Shelve,417726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.UnShelve,417726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Enable,417726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Disable,417726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Ack,417726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Reset,417726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Suppressed,417726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Shelved,417726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Disabled,417726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Acked,417726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almRateOfChange.Alarm,417726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Fault,417736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI1.almPLCFault.AlarmState,417736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI1.almPLCFault.GlobalReset,417736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI1.almPLCFault.FaultInAlarm,417736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI1.almPLCFault.ALRM,417736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI1.almPLCFault.ANUN,417736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI1.almPLCFault.AKED,417736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI1.almPLCFault.Resetable,417736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI1.almPLCFault.REST,417736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI1.almPLCFault.ACKN,417736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI1.almPLCFault.UACK,417736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI1.almPLCFault.MCmd_Enable,417736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.MCmd_Disable,417736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.OCmd_Shelve,417736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.OCmd_Unshelve,417736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.SCmd_Suppress,417736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.SCmd_UnSuppress,417737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI1.almPLCFault.AEShelveTMRDN,417737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI1.almPLCFault.Bad,417737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI1.almPLCFault.Suppress,417738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.UnSuppress,417738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Shelve,417738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.UnShelve,417738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Enable,417738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Disable,417738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Ack,417738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Reset,417738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Suppressed,417738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Shelved,417738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Disabled,417738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Acked,417738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI1.almPLCFault.Alarm,417738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Fault,417840.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almHighHigh.AlarmState,417840.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almHighHigh.GlobalReset,417840.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almHighHigh.FaultInAlarm,417840.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almHighHigh.ALRM,417840.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almHighHigh.ANUN,417840.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almHighHigh.AKED,417840.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almHighHigh.Resetable,417840.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almHighHigh.REST,417840.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almHighHigh.ACKN,417840.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almHighHigh.UACK,417840.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almHighHigh.MCmd_Enable,417840.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.MCmd_Disable,417840.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.OCmd_Shelve,417840.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.OCmd_Unshelve,417840.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.SCmd_Suppress,417840.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.SCmd_UnSuppress,417841.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almHighHigh.AEShelveTMRDN,417841.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almHighHigh.Bad,417841.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almHighHigh.Suppress,417842.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.UnSuppress,417842.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Shelve,417842.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.UnShelve,417842.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Enable,417842.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Disable,417842.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Ack,417842.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Reset,417842.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Suppressed,417842.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Shelved,417842.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Disabled,417842.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Acked,417842.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almHighHigh.Alarm,417842.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Fault,417852.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almHigh.AlarmState,417852.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almHigh.GlobalReset,417852.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almHigh.FaultInAlarm,417852.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almHigh.ALRM,417852.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almHigh.ANUN,417852.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almHigh.AKED,417852.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almHigh.Resetable,417852.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almHigh.REST,417852.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almHigh.ACKN,417852.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almHigh.UACK,417852.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almHigh.MCmd_Enable,417852.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almHigh.MCmd_Disable,417852.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almHigh.OCmd_Shelve,417852.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almHigh.OCmd_Unshelve,417852.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almHigh.SCmd_Suppress,417852.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almHigh.SCmd_UnSuppress,417853.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almHigh.AEShelveTMRDN,417853.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almHigh.Bad,417853.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almHigh.Suppress,417854.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.UnSuppress,417854.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Shelve,417854.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.UnShelve,417854.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Enable,417854.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Disable,417854.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Ack,417854.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Reset,417854.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almHigh.Suppressed,417854.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almHigh.Shelved,417854.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almHigh.Disabled,417854.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almHigh.Acked,417854.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almHigh.Alarm,417854.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Fault,417864.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almLow.AlarmState,417864.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almLow.GlobalReset,417864.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almLow.FaultInAlarm,417864.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almLow.ALRM,417864.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almLow.ANUN,417864.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almLow.AKED,417864.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almLow.Resetable,417864.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almLow.REST,417864.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almLow.ACKN,417864.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almLow.UACK,417864.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almLow.MCmd_Enable,417864.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almLow.MCmd_Disable,417864.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almLow.OCmd_Shelve,417864.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almLow.OCmd_Unshelve,417864.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almLow.SCmd_Suppress,417864.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almLow.SCmd_UnSuppress,417865.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almLow.AEShelveTMRDN,417865.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almLow.Bad,417865.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almLow.Suppress,417866.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.UnSuppress,417866.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Shelve,417866.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.UnShelve,417866.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Enable,417866.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Disable,417866.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Ack,417866.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Reset,417866.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almLow.Suppressed,417866.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almLow.Shelved,417866.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almLow.Disabled,417866.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almLow.Acked,417866.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almLow.Alarm,417866.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Fault,417876.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almLowLow.AlarmState,417876.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almLowLow.GlobalReset,417876.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almLowLow.FaultInAlarm,417876.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almLowLow.ALRM,417876.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almLowLow.ANUN,417876.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almLowLow.AKED,417876.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almLowLow.Resetable,417876.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almLowLow.REST,417876.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almLowLow.ACKN,417876.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almLowLow.UACK,417876.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almLowLow.MCmd_Enable,417876.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almLowLow.MCmd_Disable,417876.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almLowLow.OCmd_Shelve,417876.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almLowLow.OCmd_Unshelve,417876.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almLowLow.SCmd_Suppress,417876.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almLowLow.SCmd_UnSuppress,417877.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almLowLow.AEShelveTMRDN,417877.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almLowLow.Bad,417877.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almLowLow.Suppress,417878.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.UnSuppress,417878.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Shelve,417878.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.UnShelve,417878.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Enable,417878.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Disable,417878.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Ack,417878.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Reset,417878.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Suppressed,417878.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Shelved,417878.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Disabled,417878.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Acked,417878.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almLowLow.Alarm,417878.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Fault,417888.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almBrokenLoop.AlarmState,417888.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almBrokenLoop.GlobalReset,417888.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almBrokenLoop.FaultInAlarm,417888.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almBrokenLoop.ALRM,417888.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almBrokenLoop.ANUN,417888.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almBrokenLoop.AKED,417888.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almBrokenLoop.Resetable,417888.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almBrokenLoop.REST,417888.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almBrokenLoop.ACKN,417888.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almBrokenLoop.UACK,417888.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almBrokenLoop.MCmd_Enable,417888.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.MCmd_Disable,417888.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.OCmd_Shelve,417888.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.OCmd_Unshelve,417888.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.SCmd_Suppress,417888.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.SCmd_UnSuppress,417889.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almBrokenLoop.AEShelveTMRDN,417889.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almBrokenLoop.Bad,417889.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almBrokenLoop.Suppress,417890.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.UnSuppress,417890.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Shelve,417890.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.UnShelve,417890.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Enable,417890.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Disable,417890.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Ack,417890.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Reset,417890.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Suppressed,417890.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Shelved,417890.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Disabled,417890.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Acked,417890.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.Alarm,417890.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Fault,417900.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almOverRange.AlarmState,417900.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almOverRange.GlobalReset,417900.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almOverRange.FaultInAlarm,417900.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almOverRange.ALRM,417900.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almOverRange.ANUN,417900.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almOverRange.AKED,417900.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almOverRange.Resetable,417900.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almOverRange.REST,417900.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almOverRange.ACKN,417900.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almOverRange.UACK,417900.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almOverRange.MCmd_Enable,417900.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almOverRange.MCmd_Disable,417900.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almOverRange.OCmd_Shelve,417900.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almOverRange.OCmd_Unshelve,417900.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almOverRange.SCmd_Suppress,417900.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almOverRange.SCmd_UnSuppress,417901.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almOverRange.AEShelveTMRDN,417901.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almOverRange.Bad,417901.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almOverRange.Suppress,417902.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.UnSuppress,417902.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Shelve,417902.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.UnShelve,417902.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Enable,417902.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Disable,417902.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Ack,417902.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Reset,417902.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Suppressed,417902.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Shelved,417902.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Disabled,417902.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Acked,417902.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almOverRange.Alarm,417902.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Fault,417912.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almUnderRange.AlarmState,417912.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almUnderRange.GlobalReset,417912.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almUnderRange.FaultInAlarm,417912.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almUnderRange.ALRM,417912.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almUnderRange.ANUN,417912.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almUnderRange.AKED,417912.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almUnderRange.Resetable,417912.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almUnderRange.REST,417912.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almUnderRange.ACKN,417912.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almUnderRange.UACK,417912.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almUnderRange.MCmd_Enable,417912.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.MCmd_Disable,417912.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.OCmd_Shelve,417912.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.OCmd_Unshelve,417912.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.SCmd_Suppress,417912.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.SCmd_UnSuppress,417913.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almUnderRange.AEShelveTMRDN,417913.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almUnderRange.Bad,417913.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almUnderRange.Suppress,417914.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.UnSuppress,417914.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Shelve,417914.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.UnShelve,417914.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Enable,417914.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Disable,417914.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Ack,417914.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Reset,417914.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Suppressed,417914.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Shelved,417914.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Disabled,417914.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Acked,417914.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almUnderRange.Alarm,417914.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Fault,417924.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almRateOfChange.AlarmState,417924.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almRateOfChange.GlobalReset,417924.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almRateOfChange.FaultInAlarm,417924.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almRateOfChange.ALRM,417924.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almRateOfChange.ANUN,417924.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almRateOfChange.AKED,417924.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almRateOfChange.Resetable,417924.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almRateOfChange.REST,417924.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almRateOfChange.ACKN,417924.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almRateOfChange.UACK,417924.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almRateOfChange.MCmd_Enable,417924.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.MCmd_Disable,417924.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.OCmd_Shelve,417924.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.OCmd_Unshelve,417924.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.SCmd_Suppress,417924.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.SCmd_UnSuppress,417925.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almRateOfChange.AEShelveTMRDN,417925.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almRateOfChange.Bad,417925.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almRateOfChange.Suppress,417926.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.UnSuppress,417926.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Shelve,417926.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.UnShelve,417926.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Enable,417926.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Disable,417926.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Ack,417926.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Reset,417926.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Suppressed,417926.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Shelved,417926.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Disabled,417926.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Acked,417926.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almRateOfChange.Alarm,417926.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Fault,417936.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI2.almPLCFault.AlarmState,417936.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI2.almPLCFault.GlobalReset,417936.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI2.almPLCFault.FaultInAlarm,417936.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI2.almPLCFault.ALRM,417936.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI2.almPLCFault.ANUN,417936.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI2.almPLCFault.AKED,417936.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI2.almPLCFault.Resetable,417936.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI2.almPLCFault.REST,417936.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI2.almPLCFault.ACKN,417936.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI2.almPLCFault.UACK,417936.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI2.almPLCFault.MCmd_Enable,417936.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.MCmd_Disable,417936.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.OCmd_Shelve,417936.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.OCmd_Unshelve,417936.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.SCmd_Suppress,417936.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.SCmd_UnSuppress,417937.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI2.almPLCFault.AEShelveTMRDN,417937.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI2.almPLCFault.Bad,417937.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI2.almPLCFault.Suppress,417938.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.UnSuppress,417938.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Shelve,417938.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.UnShelve,417938.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Enable,417938.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Disable,417938.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Ack,417938.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Reset,417938.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Suppressed,417938.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Shelved,417938.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Disabled,417938.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Acked,417938.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI2.almPLCFault.Alarm,417938.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Fault,418040.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almHighHigh.AlarmState,418040.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almHighHigh.GlobalReset,418040.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almHighHigh.FaultInAlarm,418040.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almHighHigh.ALRM,418040.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almHighHigh.ANUN,418040.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almHighHigh.AKED,418040.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almHighHigh.Resetable,418040.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almHighHigh.REST,418040.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almHighHigh.ACKN,418040.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almHighHigh.UACK,418040.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almHighHigh.MCmd_Enable,418040.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.MCmd_Disable,418040.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.OCmd_Shelve,418040.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.OCmd_Unshelve,418040.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.SCmd_Suppress,418040.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.SCmd_UnSuppress,418041.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almHighHigh.AEShelveTMRDN,418041.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almHighHigh.Bad,418041.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almHighHigh.Suppress,418042.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.UnSuppress,418042.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Shelve,418042.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.UnShelve,418042.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Enable,418042.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Disable,418042.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Ack,418042.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Reset,418042.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Suppressed,418042.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Shelved,418042.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Disabled,418042.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Acked,418042.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almHighHigh.Alarm,418042.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Fault,418052.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almHigh.AlarmState,418052.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almHigh.GlobalReset,418052.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almHigh.FaultInAlarm,418052.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almHigh.ALRM,418052.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almHigh.ANUN,418052.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almHigh.AKED,418052.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almHigh.Resetable,418052.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almHigh.REST,418052.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almHigh.ACKN,418052.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almHigh.UACK,418052.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almHigh.MCmd_Enable,418052.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almHigh.MCmd_Disable,418052.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almHigh.OCmd_Shelve,418052.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almHigh.OCmd_Unshelve,418052.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almHigh.SCmd_Suppress,418052.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almHigh.SCmd_UnSuppress,418053.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almHigh.AEShelveTMRDN,418053.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almHigh.Bad,418053.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almHigh.Suppress,418054.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.UnSuppress,418054.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Shelve,418054.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.UnShelve,418054.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Enable,418054.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Disable,418054.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Ack,418054.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Reset,418054.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almHigh.Suppressed,418054.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almHigh.Shelved,418054.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almHigh.Disabled,418054.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almHigh.Acked,418054.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almHigh.Alarm,418054.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Fault,418064.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almLow.AlarmState,418064.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almLow.GlobalReset,418064.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almLow.FaultInAlarm,418064.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almLow.ALRM,418064.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almLow.ANUN,418064.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almLow.AKED,418064.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almLow.Resetable,418064.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almLow.REST,418064.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almLow.ACKN,418064.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almLow.UACK,418064.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almLow.MCmd_Enable,418064.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almLow.MCmd_Disable,418064.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almLow.OCmd_Shelve,418064.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almLow.OCmd_Unshelve,418064.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almLow.SCmd_Suppress,418064.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almLow.SCmd_UnSuppress,418065.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almLow.AEShelveTMRDN,418065.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almLow.Bad,418065.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almLow.Suppress,418066.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.UnSuppress,418066.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Shelve,418066.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.UnShelve,418066.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Enable,418066.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Disable,418066.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Ack,418066.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Reset,418066.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almLow.Suppressed,418066.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almLow.Shelved,418066.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almLow.Disabled,418066.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almLow.Acked,418066.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almLow.Alarm,418066.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Fault,418076.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almLowLow.AlarmState,418076.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almLowLow.GlobalReset,418076.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almLowLow.FaultInAlarm,418076.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almLowLow.ALRM,418076.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almLowLow.ANUN,418076.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almLowLow.AKED,418076.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almLowLow.Resetable,418076.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almLowLow.REST,418076.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almLowLow.ACKN,418076.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almLowLow.UACK,418076.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almLowLow.MCmd_Enable,418076.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almLowLow.MCmd_Disable,418076.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almLowLow.OCmd_Shelve,418076.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almLowLow.OCmd_Unshelve,418076.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almLowLow.SCmd_Suppress,418076.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almLowLow.SCmd_UnSuppress,418077.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almLowLow.AEShelveTMRDN,418077.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almLowLow.Bad,418077.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almLowLow.Suppress,418078.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.UnSuppress,418078.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Shelve,418078.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.UnShelve,418078.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Enable,418078.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Disable,418078.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Ack,418078.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Reset,418078.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Suppressed,418078.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Shelved,418078.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Disabled,418078.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Acked,418078.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almLowLow.Alarm,418078.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Fault,418088.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almBrokenLoop.AlarmState,418088.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almBrokenLoop.GlobalReset,418088.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almBrokenLoop.FaultInAlarm,418088.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almBrokenLoop.ALRM,418088.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almBrokenLoop.ANUN,418088.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almBrokenLoop.AKED,418088.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almBrokenLoop.Resetable,418088.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almBrokenLoop.REST,418088.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almBrokenLoop.ACKN,418088.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almBrokenLoop.UACK,418088.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almBrokenLoop.MCmd_Enable,418088.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.MCmd_Disable,418088.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.OCmd_Shelve,418088.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.OCmd_Unshelve,418088.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.SCmd_Suppress,418088.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.SCmd_UnSuppress,418089.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almBrokenLoop.AEShelveTMRDN,418089.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almBrokenLoop.Bad,418089.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almBrokenLoop.Suppress,418090.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.UnSuppress,418090.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Shelve,418090.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.UnShelve,418090.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Enable,418090.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Disable,418090.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Ack,418090.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Reset,418090.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Suppressed,418090.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Shelved,418090.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Disabled,418090.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Acked,418090.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.Alarm,418090.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Fault,418100.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almOverRange.AlarmState,418100.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almOverRange.GlobalReset,418100.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almOverRange.FaultInAlarm,418100.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almOverRange.ALRM,418100.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almOverRange.ANUN,418100.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almOverRange.AKED,418100.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almOverRange.Resetable,418100.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almOverRange.REST,418100.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almOverRange.ACKN,418100.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almOverRange.UACK,418100.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almOverRange.MCmd_Enable,418100.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almOverRange.MCmd_Disable,418100.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almOverRange.OCmd_Shelve,418100.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almOverRange.OCmd_Unshelve,418100.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almOverRange.SCmd_Suppress,418100.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almOverRange.SCmd_UnSuppress,418101.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almOverRange.AEShelveTMRDN,418101.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almOverRange.Bad,418101.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almOverRange.Suppress,418102.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.UnSuppress,418102.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Shelve,418102.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.UnShelve,418102.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Enable,418102.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Disable,418102.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Ack,418102.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Reset,418102.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Suppressed,418102.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Shelved,418102.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Disabled,418102.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Acked,418102.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almOverRange.Alarm,418102.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Fault,418112.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almUnderRange.AlarmState,418112.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almUnderRange.GlobalReset,418112.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almUnderRange.FaultInAlarm,418112.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almUnderRange.ALRM,418112.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almUnderRange.ANUN,418112.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almUnderRange.AKED,418112.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almUnderRange.Resetable,418112.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almUnderRange.REST,418112.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almUnderRange.ACKN,418112.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almUnderRange.UACK,418112.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almUnderRange.MCmd_Enable,418112.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.MCmd_Disable,418112.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.OCmd_Shelve,418112.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.OCmd_Unshelve,418112.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.SCmd_Suppress,418112.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.SCmd_UnSuppress,418113.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almUnderRange.AEShelveTMRDN,418113.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almUnderRange.Bad,418113.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almUnderRange.Suppress,418114.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.UnSuppress,418114.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Shelve,418114.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.UnShelve,418114.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Enable,418114.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Disable,418114.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Ack,418114.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Reset,418114.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Suppressed,418114.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Shelved,418114.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Disabled,418114.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Acked,418114.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almUnderRange.Alarm,418114.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Fault,418124.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almRateOfChange.AlarmState,418124.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almRateOfChange.GlobalReset,418124.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almRateOfChange.FaultInAlarm,418124.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almRateOfChange.ALRM,418124.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almRateOfChange.ANUN,418124.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almRateOfChange.AKED,418124.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almRateOfChange.Resetable,418124.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almRateOfChange.REST,418124.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almRateOfChange.ACKN,418124.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almRateOfChange.UACK,418124.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almRateOfChange.MCmd_Enable,418124.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.MCmd_Disable,418124.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.OCmd_Shelve,418124.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.OCmd_Unshelve,418124.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.SCmd_Suppress,418124.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.SCmd_UnSuppress,418125.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almRateOfChange.AEShelveTMRDN,418125.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almRateOfChange.Bad,418125.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almRateOfChange.Suppress,418126.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.UnSuppress,418126.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Shelve,418126.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.UnShelve,418126.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Enable,418126.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Disable,418126.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Ack,418126.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Reset,418126.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Suppressed,418126.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Shelved,418126.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Disabled,418126.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Acked,418126.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almRateOfChange.Alarm,418126.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Fault,418136.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI3.almPLCFault.AlarmState,418136.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI3.almPLCFault.GlobalReset,418136.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI3.almPLCFault.FaultInAlarm,418136.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI3.almPLCFault.ALRM,418136.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI3.almPLCFault.ANUN,418136.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI3.almPLCFault.AKED,418136.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI3.almPLCFault.Resetable,418136.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI3.almPLCFault.REST,418136.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI3.almPLCFault.ACKN,418136.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI3.almPLCFault.UACK,418136.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI3.almPLCFault.MCmd_Enable,418136.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.MCmd_Disable,418136.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.OCmd_Shelve,418136.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.OCmd_Unshelve,418136.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.SCmd_Suppress,418136.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.SCmd_UnSuppress,418137.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI3.almPLCFault.AEShelveTMRDN,418137.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI3.almPLCFault.Bad,418137.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI3.almPLCFault.Suppress,418138.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.UnSuppress,418138.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Shelve,418138.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.UnShelve,418138.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Enable,418138.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Disable,418138.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Ack,418138.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Reset,418138.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Suppressed,418138.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Shelved,418138.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Disabled,418138.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Acked,418138.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI3.almPLCFault.Alarm,418138.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Fault,418240.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almHighHigh.AlarmState,418240.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almHighHigh.GlobalReset,418240.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almHighHigh.FaultInAlarm,418240.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almHighHigh.ALRM,418240.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almHighHigh.ANUN,418240.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almHighHigh.AKED,418240.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almHighHigh.Resetable,418240.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almHighHigh.REST,418240.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almHighHigh.ACKN,418240.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almHighHigh.UACK,418240.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almHighHigh.MCmd_Enable,418240.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.MCmd_Disable,418240.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.OCmd_Shelve,418240.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.OCmd_Unshelve,418240.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.SCmd_Suppress,418240.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.SCmd_UnSuppress,418241.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almHighHigh.AEShelveTMRDN,418241.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almHighHigh.Bad,418241.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almHighHigh.Suppress,418242.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.UnSuppress,418242.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Shelve,418242.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.UnShelve,418242.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Enable,418242.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Disable,418242.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Ack,418242.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Reset,418242.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Suppressed,418242.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Shelved,418242.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Disabled,418242.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Acked,418242.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almHighHigh.Alarm,418242.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Fault,418252.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almHigh.AlarmState,418252.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almHigh.GlobalReset,418252.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almHigh.FaultInAlarm,418252.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almHigh.ALRM,418252.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almHigh.ANUN,418252.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almHigh.AKED,418252.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almHigh.Resetable,418252.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almHigh.REST,418252.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almHigh.ACKN,418252.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almHigh.UACK,418252.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almHigh.MCmd_Enable,418252.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almHigh.MCmd_Disable,418252.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almHigh.OCmd_Shelve,418252.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almHigh.OCmd_Unshelve,418252.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almHigh.SCmd_Suppress,418252.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almHigh.SCmd_UnSuppress,418253.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almHigh.AEShelveTMRDN,418253.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almHigh.Bad,418253.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almHigh.Suppress,418254.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.UnSuppress,418254.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Shelve,418254.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.UnShelve,418254.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Enable,418254.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Disable,418254.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Ack,418254.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Reset,418254.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almHigh.Suppressed,418254.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almHigh.Shelved,418254.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almHigh.Disabled,418254.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almHigh.Acked,418254.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almHigh.Alarm,418254.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Fault,418264.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almLow.AlarmState,418264.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almLow.GlobalReset,418264.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almLow.FaultInAlarm,418264.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almLow.ALRM,418264.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almLow.ANUN,418264.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almLow.AKED,418264.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almLow.Resetable,418264.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almLow.REST,418264.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almLow.ACKN,418264.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almLow.UACK,418264.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almLow.MCmd_Enable,418264.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almLow.MCmd_Disable,418264.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almLow.OCmd_Shelve,418264.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almLow.OCmd_Unshelve,418264.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almLow.SCmd_Suppress,418264.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almLow.SCmd_UnSuppress,418265.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almLow.AEShelveTMRDN,418265.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almLow.Bad,418265.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almLow.Suppress,418266.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.UnSuppress,418266.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Shelve,418266.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.UnShelve,418266.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Enable,418266.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Disable,418266.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Ack,418266.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Reset,418266.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almLow.Suppressed,418266.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almLow.Shelved,418266.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almLow.Disabled,418266.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almLow.Acked,418266.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almLow.Alarm,418266.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Fault,418276.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almLowLow.AlarmState,418276.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almLowLow.GlobalReset,418276.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almLowLow.FaultInAlarm,418276.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almLowLow.ALRM,418276.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almLowLow.ANUN,418276.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almLowLow.AKED,418276.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almLowLow.Resetable,418276.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almLowLow.REST,418276.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almLowLow.ACKN,418276.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almLowLow.UACK,418276.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almLowLow.MCmd_Enable,418276.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almLowLow.MCmd_Disable,418276.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almLowLow.OCmd_Shelve,418276.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almLowLow.OCmd_Unshelve,418276.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almLowLow.SCmd_Suppress,418276.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almLowLow.SCmd_UnSuppress,418277.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almLowLow.AEShelveTMRDN,418277.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almLowLow.Bad,418277.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almLowLow.Suppress,418278.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.UnSuppress,418278.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Shelve,418278.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.UnShelve,418278.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Enable,418278.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Disable,418278.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Ack,418278.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Reset,418278.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Suppressed,418278.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Shelved,418278.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Disabled,418278.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Acked,418278.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almLowLow.Alarm,418278.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Fault,418288.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almBrokenLoop.AlarmState,418288.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almBrokenLoop.GlobalReset,418288.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almBrokenLoop.FaultInAlarm,418288.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almBrokenLoop.ALRM,418288.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almBrokenLoop.ANUN,418288.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almBrokenLoop.AKED,418288.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almBrokenLoop.Resetable,418288.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almBrokenLoop.REST,418288.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almBrokenLoop.ACKN,418288.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almBrokenLoop.UACK,418288.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almBrokenLoop.MCmd_Enable,418288.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.MCmd_Disable,418288.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.OCmd_Shelve,418288.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.OCmd_Unshelve,418288.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.SCmd_Suppress,418288.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.SCmd_UnSuppress,418289.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almBrokenLoop.AEShelveTMRDN,418289.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almBrokenLoop.Bad,418289.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almBrokenLoop.Suppress,418290.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.UnSuppress,418290.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Shelve,418290.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.UnShelve,418290.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Enable,418290.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Disable,418290.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Ack,418290.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Reset,418290.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Suppressed,418290.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Shelved,418290.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Disabled,418290.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Acked,418290.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.Alarm,418290.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Fault,418300.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almOverRange.AlarmState,418300.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almOverRange.GlobalReset,418300.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almOverRange.FaultInAlarm,418300.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almOverRange.ALRM,418300.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almOverRange.ANUN,418300.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almOverRange.AKED,418300.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almOverRange.Resetable,418300.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almOverRange.REST,418300.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almOverRange.ACKN,418300.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almOverRange.UACK,418300.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almOverRange.MCmd_Enable,418300.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almOverRange.MCmd_Disable,418300.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almOverRange.OCmd_Shelve,418300.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almOverRange.OCmd_Unshelve,418300.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almOverRange.SCmd_Suppress,418300.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almOverRange.SCmd_UnSuppress,418301.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almOverRange.AEShelveTMRDN,418301.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almOverRange.Bad,418301.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almOverRange.Suppress,418302.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.UnSuppress,418302.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Shelve,418302.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.UnShelve,418302.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Enable,418302.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Disable,418302.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Ack,418302.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Reset,418302.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Suppressed,418302.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Shelved,418302.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Disabled,418302.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Acked,418302.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almOverRange.Alarm,418302.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Fault,418312.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almUnderRange.AlarmState,418312.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almUnderRange.GlobalReset,418312.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almUnderRange.FaultInAlarm,418312.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almUnderRange.ALRM,418312.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almUnderRange.ANUN,418312.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almUnderRange.AKED,418312.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almUnderRange.Resetable,418312.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almUnderRange.REST,418312.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almUnderRange.ACKN,418312.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almUnderRange.UACK,418312.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almUnderRange.MCmd_Enable,418312.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.MCmd_Disable,418312.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.OCmd_Shelve,418312.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.OCmd_Unshelve,418312.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.SCmd_Suppress,418312.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.SCmd_UnSuppress,418313.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almUnderRange.AEShelveTMRDN,418313.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almUnderRange.Bad,418313.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almUnderRange.Suppress,418314.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.UnSuppress,418314.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Shelve,418314.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.UnShelve,418314.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Enable,418314.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Disable,418314.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Ack,418314.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Reset,418314.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Suppressed,418314.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Shelved,418314.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Disabled,418314.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Acked,418314.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almUnderRange.Alarm,418314.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Fault,418324.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almRateOfChange.AlarmState,418324.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almRateOfChange.GlobalReset,418324.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almRateOfChange.FaultInAlarm,418324.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almRateOfChange.ALRM,418324.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almRateOfChange.ANUN,418324.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almRateOfChange.AKED,418324.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almRateOfChange.Resetable,418324.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almRateOfChange.REST,418324.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almRateOfChange.ACKN,418324.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almRateOfChange.UACK,418324.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almRateOfChange.MCmd_Enable,418324.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.MCmd_Disable,418324.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.OCmd_Shelve,418324.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.OCmd_Unshelve,418324.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.SCmd_Suppress,418324.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.SCmd_UnSuppress,418325.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almRateOfChange.AEShelveTMRDN,418325.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almRateOfChange.Bad,418325.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almRateOfChange.Suppress,418326.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.UnSuppress,418326.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Shelve,418326.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.UnShelve,418326.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Enable,418326.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Disable,418326.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Ack,418326.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Reset,418326.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Suppressed,418326.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Shelved,418326.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Disabled,418326.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Acked,418326.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almRateOfChange.Alarm,418326.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Fault,418336.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI4.almPLCFault.AlarmState,418336.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI4.almPLCFault.GlobalReset,418336.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI4.almPLCFault.FaultInAlarm,418336.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI4.almPLCFault.ALRM,418336.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI4.almPLCFault.ANUN,418336.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI4.almPLCFault.AKED,418336.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI4.almPLCFault.Resetable,418336.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI4.almPLCFault.REST,418336.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI4.almPLCFault.ACKN,418336.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI4.almPLCFault.UACK,418336.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI4.almPLCFault.MCmd_Enable,418336.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.MCmd_Disable,418336.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.OCmd_Shelve,418336.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.OCmd_Unshelve,418336.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.SCmd_Suppress,418336.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.SCmd_UnSuppress,418337.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI4.almPLCFault.AEShelveTMRDN,418337.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI4.almPLCFault.Bad,418337.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI4.almPLCFault.Suppress,418338.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.UnSuppress,418338.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Shelve,418338.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.UnShelve,418338.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Enable,418338.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Disable,418338.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Ack,418338.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Reset,418338.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Suppressed,418338.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Shelved,418338.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Disabled,418338.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Acked,418338.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI4.almPLCFault.Alarm,418338.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Fault,418440.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almHighHigh.AlarmState,418440.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almHighHigh.GlobalReset,418440.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almHighHigh.FaultInAlarm,418440.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almHighHigh.ALRM,418440.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almHighHigh.ANUN,418440.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almHighHigh.AKED,418440.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almHighHigh.Resetable,418440.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almHighHigh.REST,418440.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almHighHigh.ACKN,418440.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almHighHigh.UACK,418440.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almHighHigh.MCmd_Enable,418440.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.MCmd_Disable,418440.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.OCmd_Shelve,418440.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.OCmd_Unshelve,418440.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.SCmd_Suppress,418440.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.SCmd_UnSuppress,418441.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almHighHigh.AEShelveTMRDN,418441.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almHighHigh.Bad,418441.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almHighHigh.Suppress,418442.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.UnSuppress,418442.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Shelve,418442.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.UnShelve,418442.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Enable,418442.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Disable,418442.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Ack,418442.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Reset,418442.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Suppressed,418442.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Shelved,418442.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Disabled,418442.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Acked,418442.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almHighHigh.Alarm,418442.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Fault,418452.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almHigh.AlarmState,418452.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almHigh.GlobalReset,418452.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almHigh.FaultInAlarm,418452.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almHigh.ALRM,418452.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almHigh.ANUN,418452.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almHigh.AKED,418452.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almHigh.Resetable,418452.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almHigh.REST,418452.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almHigh.ACKN,418452.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almHigh.UACK,418452.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almHigh.MCmd_Enable,418452.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almHigh.MCmd_Disable,418452.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almHigh.OCmd_Shelve,418452.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almHigh.OCmd_Unshelve,418452.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almHigh.SCmd_Suppress,418452.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almHigh.SCmd_UnSuppress,418453.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almHigh.AEShelveTMRDN,418453.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almHigh.Bad,418453.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almHigh.Suppress,418454.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.UnSuppress,418454.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Shelve,418454.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.UnShelve,418454.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Enable,418454.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Disable,418454.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Ack,418454.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Reset,418454.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almHigh.Suppressed,418454.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almHigh.Shelved,418454.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almHigh.Disabled,418454.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almHigh.Acked,418454.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almHigh.Alarm,418454.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Fault,418464.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almLow.AlarmState,418464.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almLow.GlobalReset,418464.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almLow.FaultInAlarm,418464.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almLow.ALRM,418464.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almLow.ANUN,418464.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almLow.AKED,418464.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almLow.Resetable,418464.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almLow.REST,418464.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almLow.ACKN,418464.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almLow.UACK,418464.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almLow.MCmd_Enable,418464.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almLow.MCmd_Disable,418464.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almLow.OCmd_Shelve,418464.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almLow.OCmd_Unshelve,418464.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almLow.SCmd_Suppress,418464.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almLow.SCmd_UnSuppress,418465.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almLow.AEShelveTMRDN,418465.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almLow.Bad,418465.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almLow.Suppress,418466.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.UnSuppress,418466.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Shelve,418466.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.UnShelve,418466.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Enable,418466.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Disable,418466.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Ack,418466.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Reset,418466.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almLow.Suppressed,418466.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almLow.Shelved,418466.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almLow.Disabled,418466.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almLow.Acked,418466.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almLow.Alarm,418466.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Fault,418476.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almLowLow.AlarmState,418476.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almLowLow.GlobalReset,418476.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almLowLow.FaultInAlarm,418476.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almLowLow.ALRM,418476.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almLowLow.ANUN,418476.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almLowLow.AKED,418476.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almLowLow.Resetable,418476.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almLowLow.REST,418476.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almLowLow.ACKN,418476.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almLowLow.UACK,418476.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almLowLow.MCmd_Enable,418476.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almLowLow.MCmd_Disable,418476.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almLowLow.OCmd_Shelve,418476.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almLowLow.OCmd_Unshelve,418476.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almLowLow.SCmd_Suppress,418476.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almLowLow.SCmd_UnSuppress,418477.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almLowLow.AEShelveTMRDN,418477.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almLowLow.Bad,418477.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almLowLow.Suppress,418478.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.UnSuppress,418478.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Shelve,418478.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.UnShelve,418478.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Enable,418478.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Disable,418478.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Ack,418478.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Reset,418478.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Suppressed,418478.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Shelved,418478.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Disabled,418478.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Acked,418478.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almLowLow.Alarm,418478.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Fault,418488.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almBrokenLoop.AlarmState,418488.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almBrokenLoop.GlobalReset,418488.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almBrokenLoop.FaultInAlarm,418488.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almBrokenLoop.ALRM,418488.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almBrokenLoop.ANUN,418488.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almBrokenLoop.AKED,418488.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almBrokenLoop.Resetable,418488.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almBrokenLoop.REST,418488.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almBrokenLoop.ACKN,418488.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almBrokenLoop.UACK,418488.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almBrokenLoop.MCmd_Enable,418488.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.MCmd_Disable,418488.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.OCmd_Shelve,418488.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.OCmd_Unshelve,418488.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.SCmd_Suppress,418488.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.SCmd_UnSuppress,418489.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almBrokenLoop.AEShelveTMRDN,418489.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almBrokenLoop.Bad,418489.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almBrokenLoop.Suppress,418490.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.UnSuppress,418490.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Shelve,418490.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.UnShelve,418490.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Enable,418490.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Disable,418490.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Ack,418490.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Reset,418490.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Suppressed,418490.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Shelved,418490.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Disabled,418490.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Acked,418490.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.Alarm,418490.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Fault,418500.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almOverRange.AlarmState,418500.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almOverRange.GlobalReset,418500.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almOverRange.FaultInAlarm,418500.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almOverRange.ALRM,418500.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almOverRange.ANUN,418500.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almOverRange.AKED,418500.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almOverRange.Resetable,418500.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almOverRange.REST,418500.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almOverRange.ACKN,418500.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almOverRange.UACK,418500.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almOverRange.MCmd_Enable,418500.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almOverRange.MCmd_Disable,418500.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almOverRange.OCmd_Shelve,418500.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almOverRange.OCmd_Unshelve,418500.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almOverRange.SCmd_Suppress,418500.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almOverRange.SCmd_UnSuppress,418501.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almOverRange.AEShelveTMRDN,418501.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almOverRange.Bad,418501.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almOverRange.Suppress,418502.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.UnSuppress,418502.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Shelve,418502.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.UnShelve,418502.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Enable,418502.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Disable,418502.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Ack,418502.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Reset,418502.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Suppressed,418502.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Shelved,418502.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Disabled,418502.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Acked,418502.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almOverRange.Alarm,418502.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Fault,418512.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almUnderRange.AlarmState,418512.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almUnderRange.GlobalReset,418512.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almUnderRange.FaultInAlarm,418512.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almUnderRange.ALRM,418512.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almUnderRange.ANUN,418512.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almUnderRange.AKED,418512.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almUnderRange.Resetable,418512.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almUnderRange.REST,418512.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almUnderRange.ACKN,418512.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almUnderRange.UACK,418512.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almUnderRange.MCmd_Enable,418512.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.MCmd_Disable,418512.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.OCmd_Shelve,418512.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.OCmd_Unshelve,418512.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.SCmd_Suppress,418512.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.SCmd_UnSuppress,418513.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almUnderRange.AEShelveTMRDN,418513.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almUnderRange.Bad,418513.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almUnderRange.Suppress,418514.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.UnSuppress,418514.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Shelve,418514.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.UnShelve,418514.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Enable,418514.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Disable,418514.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Ack,418514.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Reset,418514.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Suppressed,418514.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Shelved,418514.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Disabled,418514.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Acked,418514.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almUnderRange.Alarm,418514.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Fault,418524.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almRateOfChange.AlarmState,418524.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almRateOfChange.GlobalReset,418524.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almRateOfChange.FaultInAlarm,418524.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almRateOfChange.ALRM,418524.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almRateOfChange.ANUN,418524.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almRateOfChange.AKED,418524.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almRateOfChange.Resetable,418524.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almRateOfChange.REST,418524.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almRateOfChange.ACKN,418524.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almRateOfChange.UACK,418524.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almRateOfChange.MCmd_Enable,418524.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.MCmd_Disable,418524.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.OCmd_Shelve,418524.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.OCmd_Unshelve,418524.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.SCmd_Suppress,418524.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.SCmd_UnSuppress,418525.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almRateOfChange.AEShelveTMRDN,418525.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almRateOfChange.Bad,418525.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almRateOfChange.Suppress,418526.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.UnSuppress,418526.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Shelve,418526.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.UnShelve,418526.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Enable,418526.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Disable,418526.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Ack,418526.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Reset,418526.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Suppressed,418526.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Shelved,418526.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Disabled,418526.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Acked,418526.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almRateOfChange.Alarm,418526.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Fault,418536.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_2_VI5.almPLCFault.AlarmState,418536.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_2_VI5.almPLCFault.GlobalReset,418536.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_2_VI5.almPLCFault.FaultInAlarm,418536.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_2_VI5.almPLCFault.ALRM,418536.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_2_VI5.almPLCFault.ANUN,418536.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_2_VI5.almPLCFault.AKED,418536.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_2_VI5.almPLCFault.Resetable,418536.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_2_VI5.almPLCFault.REST,418536.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_2_VI5.almPLCFault.ACKN,418536.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_2_VI5.almPLCFault.UACK,418536.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_2_VI5.almPLCFault.MCmd_Enable,418536.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.MCmd_Disable,418536.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.OCmd_Shelve,418536.13,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.OCmd_Unshelve,418536.14,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.SCmd_Suppress,418536.15,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.SCmd_UnSuppress,418537.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_2_VI5.almPLCFault.AEShelveTMRDN,418537.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_2_VI5.almPLCFault.Bad,418537.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_2_VI5.almPLCFault.Suppress,418538.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.UnSuppress,418538.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Shelve,418538.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.UnShelve,418538.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Enable,418538.04,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Disable,418538.05,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Ack,418538.06,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Reset,418538.07,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Suppressed,418538.08,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Shelved,418538.09,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Disabled,418538.10,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Acked,418538.11,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_2_VI5.almPLCFault.Alarm,418538.12,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Fault,418640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almHighHigh.AlarmState,418640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almHighHigh.GlobalReset,418640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almHighHigh.FaultInAlarm,418640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almHighHigh.ALRM,418640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almHighHigh.ANUN,418640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almHighHigh.AKED,418640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almHighHigh.Resetable,418640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almHighHigh.REST,418640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almHighHigh.ACKN,418640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almHighHigh.UACK,418640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almHighHigh.MCmd_Enable,418640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.MCmd_Disable,418640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.OCmd_Shelve,418640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.OCmd_Unshelve,418640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.SCmd_Suppress,418640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.SCmd_UnSuppress,418641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almHighHigh.AEShelveTMRDN,418641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almHighHigh.Bad,418641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almHighHigh.Suppress,418642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.UnSuppress,418642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Shelve,418642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.UnShelve,418642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Enable,418642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Disable,418642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Ack,418642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Reset,418642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Suppressed,418642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Shelved,418642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Disabled,418642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Acked,418642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almHighHigh.Alarm,418642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Fault,418652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almHigh.AlarmState,418652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almHigh.GlobalReset,418652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almHigh.FaultInAlarm,418652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almHigh.ALRM,418652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almHigh.ANUN,418652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almHigh.AKED,418652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almHigh.Resetable,418652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almHigh.REST,418652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almHigh.ACKN,418652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almHigh.UACK,418652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almHigh.MCmd_Enable,418652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almHigh.MCmd_Disable,418652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almHigh.OCmd_Shelve,418652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almHigh.OCmd_Unshelve,418652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almHigh.SCmd_Suppress,418652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almHigh.SCmd_UnSuppress,418653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almHigh.AEShelveTMRDN,418653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almHigh.Bad,418653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almHigh.Suppress,418654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.UnSuppress,418654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Shelve,418654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.UnShelve,418654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Enable,418654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Disable,418654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Ack,418654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Reset,418654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almHigh.Suppressed,418654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almHigh.Shelved,418654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almHigh.Disabled,418654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almHigh.Acked,418654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almHigh.Alarm,418654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Fault,418664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almLow.AlarmState,418664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almLow.GlobalReset,418664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almLow.FaultInAlarm,418664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almLow.ALRM,418664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almLow.ANUN,418664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almLow.AKED,418664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almLow.Resetable,418664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almLow.REST,418664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almLow.ACKN,418664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almLow.UACK,418664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almLow.MCmd_Enable,418664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almLow.MCmd_Disable,418664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almLow.OCmd_Shelve,418664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almLow.OCmd_Unshelve,418664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almLow.SCmd_Suppress,418664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almLow.SCmd_UnSuppress,418665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almLow.AEShelveTMRDN,418665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almLow.Bad,418665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almLow.Suppress,418666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.UnSuppress,418666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Shelve,418666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.UnShelve,418666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Enable,418666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Disable,418666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Ack,418666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Reset,418666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almLow.Suppressed,418666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almLow.Shelved,418666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almLow.Disabled,418666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almLow.Acked,418666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almLow.Alarm,418666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Fault,418676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almLowLow.AlarmState,418676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almLowLow.GlobalReset,418676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almLowLow.FaultInAlarm,418676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almLowLow.ALRM,418676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almLowLow.ANUN,418676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almLowLow.AKED,418676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almLowLow.Resetable,418676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almLowLow.REST,418676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almLowLow.ACKN,418676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almLowLow.UACK,418676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almLowLow.MCmd_Enable,418676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almLowLow.MCmd_Disable,418676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almLowLow.OCmd_Shelve,418676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almLowLow.OCmd_Unshelve,418676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almLowLow.SCmd_Suppress,418676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almLowLow.SCmd_UnSuppress,418677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almLowLow.AEShelveTMRDN,418677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almLowLow.Bad,418677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almLowLow.Suppress,418678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.UnSuppress,418678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Shelve,418678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.UnShelve,418678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Enable,418678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Disable,418678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Ack,418678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Reset,418678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Suppressed,418678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Shelved,418678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Disabled,418678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Acked,418678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almLowLow.Alarm,418678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Fault,418688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almBrokenLoop.AlarmState,418688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almBrokenLoop.GlobalReset,418688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almBrokenLoop.FaultInAlarm,418688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almBrokenLoop.ALRM,418688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almBrokenLoop.ANUN,418688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almBrokenLoop.AKED,418688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almBrokenLoop.Resetable,418688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almBrokenLoop.REST,418688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almBrokenLoop.ACKN,418688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almBrokenLoop.UACK,418688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almBrokenLoop.MCmd_Enable,418688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.MCmd_Disable,418688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.OCmd_Shelve,418688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.OCmd_Unshelve,418688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.SCmd_Suppress,418688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.SCmd_UnSuppress,418689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almBrokenLoop.AEShelveTMRDN,418689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almBrokenLoop.Bad,418689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almBrokenLoop.Suppress,418690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.UnSuppress,418690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Shelve,418690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.UnShelve,418690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Enable,418690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Disable,418690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Ack,418690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Reset,418690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Suppressed,418690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Shelved,418690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Disabled,418690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Acked,418690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.Alarm,418690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Fault,418700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almOverRange.AlarmState,418700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almOverRange.GlobalReset,418700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almOverRange.FaultInAlarm,418700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almOverRange.ALRM,418700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almOverRange.ANUN,418700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almOverRange.AKED,418700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almOverRange.Resetable,418700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almOverRange.REST,418700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almOverRange.ACKN,418700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almOverRange.UACK,418700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almOverRange.MCmd_Enable,418700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almOverRange.MCmd_Disable,418700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almOverRange.OCmd_Shelve,418700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almOverRange.OCmd_Unshelve,418700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almOverRange.SCmd_Suppress,418700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almOverRange.SCmd_UnSuppress,418701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almOverRange.AEShelveTMRDN,418701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almOverRange.Bad,418701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almOverRange.Suppress,418702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.UnSuppress,418702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Shelve,418702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.UnShelve,418702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Enable,418702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Disable,418702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Ack,418702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Reset,418702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Suppressed,418702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Shelved,418702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Disabled,418702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Acked,418702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almOverRange.Alarm,418702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Fault,418712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almUnderRange.AlarmState,418712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almUnderRange.GlobalReset,418712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almUnderRange.FaultInAlarm,418712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almUnderRange.ALRM,418712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almUnderRange.ANUN,418712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almUnderRange.AKED,418712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almUnderRange.Resetable,418712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almUnderRange.REST,418712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almUnderRange.ACKN,418712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almUnderRange.UACK,418712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almUnderRange.MCmd_Enable,418712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.MCmd_Disable,418712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.OCmd_Shelve,418712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.OCmd_Unshelve,418712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.SCmd_Suppress,418712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.SCmd_UnSuppress,418713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almUnderRange.AEShelveTMRDN,418713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almUnderRange.Bad,418713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almUnderRange.Suppress,418714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.UnSuppress,418714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Shelve,418714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.UnShelve,418714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Enable,418714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Disable,418714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Ack,418714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Reset,418714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Suppressed,418714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Shelved,418714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Disabled,418714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Acked,418714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almUnderRange.Alarm,418714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Fault,418724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almRateOfChange.AlarmState,418724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almRateOfChange.GlobalReset,418724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almRateOfChange.FaultInAlarm,418724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almRateOfChange.ALRM,418724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almRateOfChange.ANUN,418724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almRateOfChange.AKED,418724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almRateOfChange.Resetable,418724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almRateOfChange.REST,418724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almRateOfChange.ACKN,418724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almRateOfChange.UACK,418724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almRateOfChange.MCmd_Enable,418724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.MCmd_Disable,418724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.OCmd_Shelve,418724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.OCmd_Unshelve,418724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.SCmd_Suppress,418724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.SCmd_UnSuppress,418725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almRateOfChange.AEShelveTMRDN,418725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almRateOfChange.Bad,418725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almRateOfChange.Suppress,418726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.UnSuppress,418726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Shelve,418726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.UnShelve,418726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Enable,418726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Disable,418726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Ack,418726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Reset,418726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Suppressed,418726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Shelved,418726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Disabled,418726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Acked,418726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almRateOfChange.Alarm,418726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Fault,418736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI1.almPLCFault.AlarmState,418736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI1.almPLCFault.GlobalReset,418736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI1.almPLCFault.FaultInAlarm,418736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI1.almPLCFault.ALRM,418736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI1.almPLCFault.ANUN,418736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI1.almPLCFault.AKED,418736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI1.almPLCFault.Resetable,418736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI1.almPLCFault.REST,418736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI1.almPLCFault.ACKN,418736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI1.almPLCFault.UACK,418736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI1.almPLCFault.MCmd_Enable,418736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.MCmd_Disable,418736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.OCmd_Shelve,418736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.OCmd_Unshelve,418736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.SCmd_Suppress,418736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.SCmd_UnSuppress,418737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI1.almPLCFault.AEShelveTMRDN,418737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI1.almPLCFault.Bad,418737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI1.almPLCFault.Suppress,418738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.UnSuppress,418738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Shelve,418738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.UnShelve,418738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Enable,418738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Disable,418738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Ack,418738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Reset,418738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Suppressed,418738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Shelved,418738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Disabled,418738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Acked,418738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI1.almPLCFault.Alarm,418738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Fault,418840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almHighHigh.AlarmState,418840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almHighHigh.GlobalReset,418840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almHighHigh.FaultInAlarm,418840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almHighHigh.ALRM,418840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almHighHigh.ANUN,418840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almHighHigh.AKED,418840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almHighHigh.Resetable,418840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almHighHigh.REST,418840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almHighHigh.ACKN,418840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almHighHigh.UACK,418840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almHighHigh.MCmd_Enable,418840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.MCmd_Disable,418840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.OCmd_Shelve,418840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.OCmd_Unshelve,418840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.SCmd_Suppress,418840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.SCmd_UnSuppress,418841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almHighHigh.AEShelveTMRDN,418841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almHighHigh.Bad,418841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almHighHigh.Suppress,418842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.UnSuppress,418842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Shelve,418842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.UnShelve,418842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Enable,418842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Disable,418842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Ack,418842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Reset,418842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Suppressed,418842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Shelved,418842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Disabled,418842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Acked,418842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almHighHigh.Alarm,418842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Fault,418852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almHigh.AlarmState,418852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almHigh.GlobalReset,418852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almHigh.FaultInAlarm,418852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almHigh.ALRM,418852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almHigh.ANUN,418852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almHigh.AKED,418852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almHigh.Resetable,418852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almHigh.REST,418852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almHigh.ACKN,418852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almHigh.UACK,418852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almHigh.MCmd_Enable,418852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almHigh.MCmd_Disable,418852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almHigh.OCmd_Shelve,418852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almHigh.OCmd_Unshelve,418852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almHigh.SCmd_Suppress,418852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almHigh.SCmd_UnSuppress,418853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almHigh.AEShelveTMRDN,418853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almHigh.Bad,418853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almHigh.Suppress,418854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.UnSuppress,418854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Shelve,418854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.UnShelve,418854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Enable,418854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Disable,418854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Ack,418854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Reset,418854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almHigh.Suppressed,418854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almHigh.Shelved,418854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almHigh.Disabled,418854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almHigh.Acked,418854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almHigh.Alarm,418854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Fault,418864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almLow.AlarmState,418864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almLow.GlobalReset,418864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almLow.FaultInAlarm,418864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almLow.ALRM,418864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almLow.ANUN,418864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almLow.AKED,418864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almLow.Resetable,418864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almLow.REST,418864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almLow.ACKN,418864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almLow.UACK,418864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almLow.MCmd_Enable,418864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almLow.MCmd_Disable,418864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almLow.OCmd_Shelve,418864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almLow.OCmd_Unshelve,418864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almLow.SCmd_Suppress,418864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almLow.SCmd_UnSuppress,418865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almLow.AEShelveTMRDN,418865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almLow.Bad,418865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almLow.Suppress,418866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.UnSuppress,418866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Shelve,418866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.UnShelve,418866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Enable,418866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Disable,418866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Ack,418866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Reset,418866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almLow.Suppressed,418866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almLow.Shelved,418866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almLow.Disabled,418866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almLow.Acked,418866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almLow.Alarm,418866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Fault,418876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almLowLow.AlarmState,418876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almLowLow.GlobalReset,418876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almLowLow.FaultInAlarm,418876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almLowLow.ALRM,418876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almLowLow.ANUN,418876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almLowLow.AKED,418876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almLowLow.Resetable,418876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almLowLow.REST,418876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almLowLow.ACKN,418876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almLowLow.UACK,418876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almLowLow.MCmd_Enable,418876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almLowLow.MCmd_Disable,418876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almLowLow.OCmd_Shelve,418876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almLowLow.OCmd_Unshelve,418876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almLowLow.SCmd_Suppress,418876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almLowLow.SCmd_UnSuppress,418877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almLowLow.AEShelveTMRDN,418877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almLowLow.Bad,418877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almLowLow.Suppress,418878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.UnSuppress,418878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Shelve,418878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.UnShelve,418878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Enable,418878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Disable,418878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Ack,418878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Reset,418878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Suppressed,418878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Shelved,418878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Disabled,418878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Acked,418878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almLowLow.Alarm,418878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Fault,418888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almBrokenLoop.AlarmState,418888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almBrokenLoop.GlobalReset,418888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almBrokenLoop.FaultInAlarm,418888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almBrokenLoop.ALRM,418888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almBrokenLoop.ANUN,418888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almBrokenLoop.AKED,418888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almBrokenLoop.Resetable,418888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almBrokenLoop.REST,418888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almBrokenLoop.ACKN,418888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almBrokenLoop.UACK,418888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almBrokenLoop.MCmd_Enable,418888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.MCmd_Disable,418888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.OCmd_Shelve,418888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.OCmd_Unshelve,418888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.SCmd_Suppress,418888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.SCmd_UnSuppress,418889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almBrokenLoop.AEShelveTMRDN,418889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almBrokenLoop.Bad,418889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almBrokenLoop.Suppress,418890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.UnSuppress,418890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Shelve,418890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.UnShelve,418890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Enable,418890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Disable,418890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Ack,418890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Reset,418890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Suppressed,418890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Shelved,418890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Disabled,418890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Acked,418890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.Alarm,418890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Fault,418900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almOverRange.AlarmState,418900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almOverRange.GlobalReset,418900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almOverRange.FaultInAlarm,418900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almOverRange.ALRM,418900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almOverRange.ANUN,418900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almOverRange.AKED,418900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almOverRange.Resetable,418900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almOverRange.REST,418900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almOverRange.ACKN,418900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almOverRange.UACK,418900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almOverRange.MCmd_Enable,418900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almOverRange.MCmd_Disable,418900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almOverRange.OCmd_Shelve,418900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almOverRange.OCmd_Unshelve,418900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almOverRange.SCmd_Suppress,418900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almOverRange.SCmd_UnSuppress,418901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almOverRange.AEShelveTMRDN,418901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almOverRange.Bad,418901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almOverRange.Suppress,418902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.UnSuppress,418902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Shelve,418902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.UnShelve,418902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Enable,418902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Disable,418902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Ack,418902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Reset,418902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Suppressed,418902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Shelved,418902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Disabled,418902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Acked,418902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almOverRange.Alarm,418902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Fault,418912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almUnderRange.AlarmState,418912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almUnderRange.GlobalReset,418912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almUnderRange.FaultInAlarm,418912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almUnderRange.ALRM,418912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almUnderRange.ANUN,418912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almUnderRange.AKED,418912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almUnderRange.Resetable,418912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almUnderRange.REST,418912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almUnderRange.ACKN,418912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almUnderRange.UACK,418912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almUnderRange.MCmd_Enable,418912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.MCmd_Disable,418912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.OCmd_Shelve,418912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.OCmd_Unshelve,418912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.SCmd_Suppress,418912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.SCmd_UnSuppress,418913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almUnderRange.AEShelveTMRDN,418913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almUnderRange.Bad,418913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almUnderRange.Suppress,418914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.UnSuppress,418914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Shelve,418914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.UnShelve,418914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Enable,418914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Disable,418914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Ack,418914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Reset,418914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Suppressed,418914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Shelved,418914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Disabled,418914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Acked,418914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almUnderRange.Alarm,418914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Fault,418924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almRateOfChange.AlarmState,418924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almRateOfChange.GlobalReset,418924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almRateOfChange.FaultInAlarm,418924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almRateOfChange.ALRM,418924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almRateOfChange.ANUN,418924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almRateOfChange.AKED,418924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almRateOfChange.Resetable,418924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almRateOfChange.REST,418924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almRateOfChange.ACKN,418924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almRateOfChange.UACK,418924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almRateOfChange.MCmd_Enable,418924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.MCmd_Disable,418924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.OCmd_Shelve,418924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.OCmd_Unshelve,418924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.SCmd_Suppress,418924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.SCmd_UnSuppress,418925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almRateOfChange.AEShelveTMRDN,418925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almRateOfChange.Bad,418925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almRateOfChange.Suppress,418926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.UnSuppress,418926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Shelve,418926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.UnShelve,418926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Enable,418926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Disable,418926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Ack,418926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Reset,418926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Suppressed,418926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Shelved,418926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Disabled,418926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Acked,418926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almRateOfChange.Alarm,418926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Fault,418936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI2.almPLCFault.AlarmState,418936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI2.almPLCFault.GlobalReset,418936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI2.almPLCFault.FaultInAlarm,418936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI2.almPLCFault.ALRM,418936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI2.almPLCFault.ANUN,418936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI2.almPLCFault.AKED,418936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI2.almPLCFault.Resetable,418936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI2.almPLCFault.REST,418936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI2.almPLCFault.ACKN,418936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI2.almPLCFault.UACK,418936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI2.almPLCFault.MCmd_Enable,418936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.MCmd_Disable,418936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.OCmd_Shelve,418936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.OCmd_Unshelve,418936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.SCmd_Suppress,418936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.SCmd_UnSuppress,418937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI2.almPLCFault.AEShelveTMRDN,418937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI2.almPLCFault.Bad,418937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI2.almPLCFault.Suppress,418938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.UnSuppress,418938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Shelve,418938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.UnShelve,418938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Enable,418938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Disable,418938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Ack,418938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Reset,418938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Suppressed,418938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Shelved,418938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Disabled,418938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Acked,418938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI2.almPLCFault.Alarm,418938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Fault,419040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almHighHigh.AlarmState,419040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almHighHigh.GlobalReset,419040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almHighHigh.FaultInAlarm,419040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almHighHigh.ALRM,419040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almHighHigh.ANUN,419040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almHighHigh.AKED,419040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almHighHigh.Resetable,419040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almHighHigh.REST,419040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almHighHigh.ACKN,419040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almHighHigh.UACK,419040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almHighHigh.MCmd_Enable,419040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.MCmd_Disable,419040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.OCmd_Shelve,419040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.OCmd_Unshelve,419040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.SCmd_Suppress,419040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.SCmd_UnSuppress,419041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almHighHigh.AEShelveTMRDN,419041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almHighHigh.Bad,419041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almHighHigh.Suppress,419042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.UnSuppress,419042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Shelve,419042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.UnShelve,419042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Enable,419042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Disable,419042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Ack,419042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Reset,419042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Suppressed,419042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Shelved,419042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Disabled,419042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Acked,419042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almHighHigh.Alarm,419042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Fault,419052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almHigh.AlarmState,419052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almHigh.GlobalReset,419052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almHigh.FaultInAlarm,419052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almHigh.ALRM,419052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almHigh.ANUN,419052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almHigh.AKED,419052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almHigh.Resetable,419052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almHigh.REST,419052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almHigh.ACKN,419052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almHigh.UACK,419052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almHigh.MCmd_Enable,419052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almHigh.MCmd_Disable,419052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almHigh.OCmd_Shelve,419052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almHigh.OCmd_Unshelve,419052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almHigh.SCmd_Suppress,419052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almHigh.SCmd_UnSuppress,419053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almHigh.AEShelveTMRDN,419053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almHigh.Bad,419053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almHigh.Suppress,419054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.UnSuppress,419054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Shelve,419054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.UnShelve,419054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Enable,419054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Disable,419054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Ack,419054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Reset,419054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almHigh.Suppressed,419054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almHigh.Shelved,419054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almHigh.Disabled,419054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almHigh.Acked,419054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almHigh.Alarm,419054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Fault,419064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almLow.AlarmState,419064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almLow.GlobalReset,419064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almLow.FaultInAlarm,419064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almLow.ALRM,419064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almLow.ANUN,419064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almLow.AKED,419064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almLow.Resetable,419064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almLow.REST,419064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almLow.ACKN,419064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almLow.UACK,419064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almLow.MCmd_Enable,419064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almLow.MCmd_Disable,419064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almLow.OCmd_Shelve,419064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almLow.OCmd_Unshelve,419064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almLow.SCmd_Suppress,419064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almLow.SCmd_UnSuppress,419065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almLow.AEShelveTMRDN,419065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almLow.Bad,419065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almLow.Suppress,419066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.UnSuppress,419066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Shelve,419066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.UnShelve,419066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Enable,419066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Disable,419066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Ack,419066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Reset,419066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almLow.Suppressed,419066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almLow.Shelved,419066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almLow.Disabled,419066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almLow.Acked,419066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almLow.Alarm,419066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Fault,419076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almLowLow.AlarmState,419076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almLowLow.GlobalReset,419076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almLowLow.FaultInAlarm,419076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almLowLow.ALRM,419076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almLowLow.ANUN,419076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almLowLow.AKED,419076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almLowLow.Resetable,419076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almLowLow.REST,419076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almLowLow.ACKN,419076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almLowLow.UACK,419076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almLowLow.MCmd_Enable,419076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almLowLow.MCmd_Disable,419076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almLowLow.OCmd_Shelve,419076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almLowLow.OCmd_Unshelve,419076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almLowLow.SCmd_Suppress,419076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almLowLow.SCmd_UnSuppress,419077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almLowLow.AEShelveTMRDN,419077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almLowLow.Bad,419077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almLowLow.Suppress,419078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.UnSuppress,419078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Shelve,419078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.UnShelve,419078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Enable,419078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Disable,419078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Ack,419078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Reset,419078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Suppressed,419078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Shelved,419078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Disabled,419078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Acked,419078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almLowLow.Alarm,419078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Fault,419088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almBrokenLoop.AlarmState,419088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almBrokenLoop.GlobalReset,419088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almBrokenLoop.FaultInAlarm,419088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almBrokenLoop.ALRM,419088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almBrokenLoop.ANUN,419088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almBrokenLoop.AKED,419088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almBrokenLoop.Resetable,419088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almBrokenLoop.REST,419088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almBrokenLoop.ACKN,419088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almBrokenLoop.UACK,419088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almBrokenLoop.MCmd_Enable,419088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.MCmd_Disable,419088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.OCmd_Shelve,419088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.OCmd_Unshelve,419088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.SCmd_Suppress,419088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.SCmd_UnSuppress,419089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almBrokenLoop.AEShelveTMRDN,419089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almBrokenLoop.Bad,419089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almBrokenLoop.Suppress,419090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.UnSuppress,419090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Shelve,419090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.UnShelve,419090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Enable,419090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Disable,419090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Ack,419090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Reset,419090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Suppressed,419090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Shelved,419090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Disabled,419090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Acked,419090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.Alarm,419090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Fault,419100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almOverRange.AlarmState,419100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almOverRange.GlobalReset,419100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almOverRange.FaultInAlarm,419100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almOverRange.ALRM,419100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almOverRange.ANUN,419100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almOverRange.AKED,419100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almOverRange.Resetable,419100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almOverRange.REST,419100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almOverRange.ACKN,419100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almOverRange.UACK,419100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almOverRange.MCmd_Enable,419100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almOverRange.MCmd_Disable,419100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almOverRange.OCmd_Shelve,419100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almOverRange.OCmd_Unshelve,419100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almOverRange.SCmd_Suppress,419100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almOverRange.SCmd_UnSuppress,419101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almOverRange.AEShelveTMRDN,419101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almOverRange.Bad,419101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almOverRange.Suppress,419102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.UnSuppress,419102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Shelve,419102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.UnShelve,419102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Enable,419102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Disable,419102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Ack,419102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Reset,419102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Suppressed,419102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Shelved,419102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Disabled,419102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Acked,419102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almOverRange.Alarm,419102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Fault,419112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almUnderRange.AlarmState,419112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almUnderRange.GlobalReset,419112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almUnderRange.FaultInAlarm,419112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almUnderRange.ALRM,419112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almUnderRange.ANUN,419112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almUnderRange.AKED,419112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almUnderRange.Resetable,419112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almUnderRange.REST,419112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almUnderRange.ACKN,419112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almUnderRange.UACK,419112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almUnderRange.MCmd_Enable,419112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.MCmd_Disable,419112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.OCmd_Shelve,419112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.OCmd_Unshelve,419112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.SCmd_Suppress,419112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.SCmd_UnSuppress,419113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almUnderRange.AEShelveTMRDN,419113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almUnderRange.Bad,419113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almUnderRange.Suppress,419114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.UnSuppress,419114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Shelve,419114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.UnShelve,419114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Enable,419114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Disable,419114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Ack,419114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Reset,419114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Suppressed,419114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Shelved,419114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Disabled,419114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Acked,419114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almUnderRange.Alarm,419114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Fault,419124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almRateOfChange.AlarmState,419124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almRateOfChange.GlobalReset,419124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almRateOfChange.FaultInAlarm,419124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almRateOfChange.ALRM,419124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almRateOfChange.ANUN,419124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almRateOfChange.AKED,419124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almRateOfChange.Resetable,419124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almRateOfChange.REST,419124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almRateOfChange.ACKN,419124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almRateOfChange.UACK,419124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almRateOfChange.MCmd_Enable,419124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.MCmd_Disable,419124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.OCmd_Shelve,419124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.OCmd_Unshelve,419124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.SCmd_Suppress,419124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.SCmd_UnSuppress,419125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almRateOfChange.AEShelveTMRDN,419125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almRateOfChange.Bad,419125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almRateOfChange.Suppress,419126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.UnSuppress,419126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Shelve,419126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.UnShelve,419126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Enable,419126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Disable,419126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Ack,419126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Reset,419126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Suppressed,419126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Shelved,419126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Disabled,419126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Acked,419126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almRateOfChange.Alarm,419126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Fault,419136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI3.almPLCFault.AlarmState,419136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI3.almPLCFault.GlobalReset,419136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI3.almPLCFault.FaultInAlarm,419136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI3.almPLCFault.ALRM,419136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI3.almPLCFault.ANUN,419136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI3.almPLCFault.AKED,419136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI3.almPLCFault.Resetable,419136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI3.almPLCFault.REST,419136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI3.almPLCFault.ACKN,419136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI3.almPLCFault.UACK,419136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI3.almPLCFault.MCmd_Enable,419136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.MCmd_Disable,419136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.OCmd_Shelve,419136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.OCmd_Unshelve,419136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.SCmd_Suppress,419136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.SCmd_UnSuppress,419137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI3.almPLCFault.AEShelveTMRDN,419137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI3.almPLCFault.Bad,419137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI3.almPLCFault.Suppress,419138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.UnSuppress,419138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Shelve,419138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.UnShelve,419138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Enable,419138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Disable,419138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Ack,419138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Reset,419138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Suppressed,419138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Shelved,419138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Disabled,419138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Acked,419138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI3.almPLCFault.Alarm,419138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Fault,419240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almHighHigh.AlarmState,419240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almHighHigh.GlobalReset,419240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almHighHigh.FaultInAlarm,419240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almHighHigh.ALRM,419240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almHighHigh.ANUN,419240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almHighHigh.AKED,419240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almHighHigh.Resetable,419240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almHighHigh.REST,419240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almHighHigh.ACKN,419240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almHighHigh.UACK,419240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almHighHigh.MCmd_Enable,419240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.MCmd_Disable,419240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.OCmd_Shelve,419240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.OCmd_Unshelve,419240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.SCmd_Suppress,419240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.SCmd_UnSuppress,419241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almHighHigh.AEShelveTMRDN,419241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almHighHigh.Bad,419241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almHighHigh.Suppress,419242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.UnSuppress,419242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Shelve,419242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.UnShelve,419242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Enable,419242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Disable,419242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Ack,419242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Reset,419242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Suppressed,419242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Shelved,419242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Disabled,419242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Acked,419242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almHighHigh.Alarm,419242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Fault,419252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almHigh.AlarmState,419252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almHigh.GlobalReset,419252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almHigh.FaultInAlarm,419252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almHigh.ALRM,419252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almHigh.ANUN,419252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almHigh.AKED,419252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almHigh.Resetable,419252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almHigh.REST,419252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almHigh.ACKN,419252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almHigh.UACK,419252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almHigh.MCmd_Enable,419252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almHigh.MCmd_Disable,419252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almHigh.OCmd_Shelve,419252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almHigh.OCmd_Unshelve,419252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almHigh.SCmd_Suppress,419252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almHigh.SCmd_UnSuppress,419253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almHigh.AEShelveTMRDN,419253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almHigh.Bad,419253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almHigh.Suppress,419254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.UnSuppress,419254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Shelve,419254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.UnShelve,419254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Enable,419254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Disable,419254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Ack,419254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Reset,419254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almHigh.Suppressed,419254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almHigh.Shelved,419254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almHigh.Disabled,419254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almHigh.Acked,419254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almHigh.Alarm,419254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Fault,419264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almLow.AlarmState,419264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almLow.GlobalReset,419264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almLow.FaultInAlarm,419264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almLow.ALRM,419264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almLow.ANUN,419264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almLow.AKED,419264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almLow.Resetable,419264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almLow.REST,419264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almLow.ACKN,419264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almLow.UACK,419264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almLow.MCmd_Enable,419264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almLow.MCmd_Disable,419264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almLow.OCmd_Shelve,419264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almLow.OCmd_Unshelve,419264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almLow.SCmd_Suppress,419264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almLow.SCmd_UnSuppress,419265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almLow.AEShelveTMRDN,419265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almLow.Bad,419265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almLow.Suppress,419266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.UnSuppress,419266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Shelve,419266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.UnShelve,419266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Enable,419266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Disable,419266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Ack,419266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Reset,419266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almLow.Suppressed,419266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almLow.Shelved,419266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almLow.Disabled,419266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almLow.Acked,419266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almLow.Alarm,419266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Fault,419276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almLowLow.AlarmState,419276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almLowLow.GlobalReset,419276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almLowLow.FaultInAlarm,419276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almLowLow.ALRM,419276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almLowLow.ANUN,419276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almLowLow.AKED,419276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almLowLow.Resetable,419276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almLowLow.REST,419276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almLowLow.ACKN,419276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almLowLow.UACK,419276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almLowLow.MCmd_Enable,419276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almLowLow.MCmd_Disable,419276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almLowLow.OCmd_Shelve,419276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almLowLow.OCmd_Unshelve,419276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almLowLow.SCmd_Suppress,419276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almLowLow.SCmd_UnSuppress,419277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almLowLow.AEShelveTMRDN,419277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almLowLow.Bad,419277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almLowLow.Suppress,419278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.UnSuppress,419278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Shelve,419278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.UnShelve,419278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Enable,419278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Disable,419278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Ack,419278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Reset,419278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Suppressed,419278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Shelved,419278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Disabled,419278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Acked,419278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almLowLow.Alarm,419278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Fault,419288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almBrokenLoop.AlarmState,419288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almBrokenLoop.GlobalReset,419288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almBrokenLoop.FaultInAlarm,419288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almBrokenLoop.ALRM,419288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almBrokenLoop.ANUN,419288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almBrokenLoop.AKED,419288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almBrokenLoop.Resetable,419288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almBrokenLoop.REST,419288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almBrokenLoop.ACKN,419288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almBrokenLoop.UACK,419288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almBrokenLoop.MCmd_Enable,419288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.MCmd_Disable,419288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.OCmd_Shelve,419288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.OCmd_Unshelve,419288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.SCmd_Suppress,419288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.SCmd_UnSuppress,419289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almBrokenLoop.AEShelveTMRDN,419289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almBrokenLoop.Bad,419289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almBrokenLoop.Suppress,419290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.UnSuppress,419290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Shelve,419290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.UnShelve,419290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Enable,419290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Disable,419290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Ack,419290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Reset,419290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Suppressed,419290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Shelved,419290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Disabled,419290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Acked,419290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.Alarm,419290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Fault,419300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almOverRange.AlarmState,419300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almOverRange.GlobalReset,419300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almOverRange.FaultInAlarm,419300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almOverRange.ALRM,419300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almOverRange.ANUN,419300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almOverRange.AKED,419300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almOverRange.Resetable,419300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almOverRange.REST,419300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almOverRange.ACKN,419300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almOverRange.UACK,419300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almOverRange.MCmd_Enable,419300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almOverRange.MCmd_Disable,419300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almOverRange.OCmd_Shelve,419300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almOverRange.OCmd_Unshelve,419300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almOverRange.SCmd_Suppress,419300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almOverRange.SCmd_UnSuppress,419301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almOverRange.AEShelveTMRDN,419301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almOverRange.Bad,419301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almOverRange.Suppress,419302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.UnSuppress,419302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Shelve,419302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.UnShelve,419302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Enable,419302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Disable,419302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Ack,419302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Reset,419302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Suppressed,419302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Shelved,419302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Disabled,419302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Acked,419302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almOverRange.Alarm,419302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Fault,419312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almUnderRange.AlarmState,419312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almUnderRange.GlobalReset,419312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almUnderRange.FaultInAlarm,419312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almUnderRange.ALRM,419312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almUnderRange.ANUN,419312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almUnderRange.AKED,419312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almUnderRange.Resetable,419312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almUnderRange.REST,419312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almUnderRange.ACKN,419312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almUnderRange.UACK,419312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almUnderRange.MCmd_Enable,419312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.MCmd_Disable,419312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.OCmd_Shelve,419312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.OCmd_Unshelve,419312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.SCmd_Suppress,419312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.SCmd_UnSuppress,419313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almUnderRange.AEShelveTMRDN,419313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almUnderRange.Bad,419313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almUnderRange.Suppress,419314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.UnSuppress,419314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Shelve,419314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.UnShelve,419314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Enable,419314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Disable,419314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Ack,419314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Reset,419314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Suppressed,419314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Shelved,419314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Disabled,419314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Acked,419314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almUnderRange.Alarm,419314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Fault,419324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almRateOfChange.AlarmState,419324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almRateOfChange.GlobalReset,419324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almRateOfChange.FaultInAlarm,419324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almRateOfChange.ALRM,419324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almRateOfChange.ANUN,419324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almRateOfChange.AKED,419324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almRateOfChange.Resetable,419324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almRateOfChange.REST,419324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almRateOfChange.ACKN,419324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almRateOfChange.UACK,419324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almRateOfChange.MCmd_Enable,419324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.MCmd_Disable,419324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.OCmd_Shelve,419324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.OCmd_Unshelve,419324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.SCmd_Suppress,419324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.SCmd_UnSuppress,419325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almRateOfChange.AEShelveTMRDN,419325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almRateOfChange.Bad,419325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almRateOfChange.Suppress,419326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.UnSuppress,419326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Shelve,419326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.UnShelve,419326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Enable,419326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Disable,419326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Ack,419326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Reset,419326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Suppressed,419326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Shelved,419326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Disabled,419326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Acked,419326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almRateOfChange.Alarm,419326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Fault,419336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI4.almPLCFault.AlarmState,419336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI4.almPLCFault.GlobalReset,419336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI4.almPLCFault.FaultInAlarm,419336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI4.almPLCFault.ALRM,419336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI4.almPLCFault.ANUN,419336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI4.almPLCFault.AKED,419336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI4.almPLCFault.Resetable,419336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI4.almPLCFault.REST,419336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI4.almPLCFault.ACKN,419336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI4.almPLCFault.UACK,419336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI4.almPLCFault.MCmd_Enable,419336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.MCmd_Disable,419336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.OCmd_Shelve,419336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.OCmd_Unshelve,419336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.SCmd_Suppress,419336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.SCmd_UnSuppress,419337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI4.almPLCFault.AEShelveTMRDN,419337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI4.almPLCFault.Bad,419337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI4.almPLCFault.Suppress,419338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.UnSuppress,419338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Shelve,419338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.UnShelve,419338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Enable,419338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Disable,419338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Ack,419338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Reset,419338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Suppressed,419338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Shelved,419338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Disabled,419338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Acked,419338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI4.almPLCFault.Alarm,419338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Fault,419440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almHighHigh.AlarmState,419440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almHighHigh.GlobalReset,419440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almHighHigh.FaultInAlarm,419440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almHighHigh.ALRM,419440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almHighHigh.ANUN,419440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almHighHigh.AKED,419440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almHighHigh.Resetable,419440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almHighHigh.REST,419440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almHighHigh.ACKN,419440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almHighHigh.UACK,419440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almHighHigh.MCmd_Enable,419440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.MCmd_Disable,419440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.OCmd_Shelve,419440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.OCmd_Unshelve,419440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.SCmd_Suppress,419440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.SCmd_UnSuppress,419441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almHighHigh.AEShelveTMRDN,419441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almHighHigh.Bad,419441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almHighHigh.Suppress,419442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.UnSuppress,419442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Shelve,419442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.UnShelve,419442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Enable,419442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Disable,419442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Ack,419442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Reset,419442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Suppressed,419442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Shelved,419442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Disabled,419442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Acked,419442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almHighHigh.Alarm,419442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Fault,419452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almHigh.AlarmState,419452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almHigh.GlobalReset,419452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almHigh.FaultInAlarm,419452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almHigh.ALRM,419452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almHigh.ANUN,419452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almHigh.AKED,419452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almHigh.Resetable,419452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almHigh.REST,419452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almHigh.ACKN,419452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almHigh.UACK,419452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almHigh.MCmd_Enable,419452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almHigh.MCmd_Disable,419452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almHigh.OCmd_Shelve,419452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almHigh.OCmd_Unshelve,419452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almHigh.SCmd_Suppress,419452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almHigh.SCmd_UnSuppress,419453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almHigh.AEShelveTMRDN,419453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almHigh.Bad,419453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almHigh.Suppress,419454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.UnSuppress,419454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Shelve,419454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.UnShelve,419454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Enable,419454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Disable,419454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Ack,419454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Reset,419454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almHigh.Suppressed,419454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almHigh.Shelved,419454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almHigh.Disabled,419454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almHigh.Acked,419454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almHigh.Alarm,419454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Fault,419464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almLow.AlarmState,419464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almLow.GlobalReset,419464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almLow.FaultInAlarm,419464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almLow.ALRM,419464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almLow.ANUN,419464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almLow.AKED,419464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almLow.Resetable,419464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almLow.REST,419464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almLow.ACKN,419464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almLow.UACK,419464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almLow.MCmd_Enable,419464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almLow.MCmd_Disable,419464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almLow.OCmd_Shelve,419464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almLow.OCmd_Unshelve,419464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almLow.SCmd_Suppress,419464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almLow.SCmd_UnSuppress,419465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almLow.AEShelveTMRDN,419465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almLow.Bad,419465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almLow.Suppress,419466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.UnSuppress,419466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Shelve,419466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.UnShelve,419466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Enable,419466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Disable,419466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Ack,419466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Reset,419466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almLow.Suppressed,419466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almLow.Shelved,419466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almLow.Disabled,419466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almLow.Acked,419466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almLow.Alarm,419466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Fault,419476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almLowLow.AlarmState,419476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almLowLow.GlobalReset,419476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almLowLow.FaultInAlarm,419476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almLowLow.ALRM,419476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almLowLow.ANUN,419476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almLowLow.AKED,419476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almLowLow.Resetable,419476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almLowLow.REST,419476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almLowLow.ACKN,419476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almLowLow.UACK,419476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almLowLow.MCmd_Enable,419476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almLowLow.MCmd_Disable,419476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almLowLow.OCmd_Shelve,419476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almLowLow.OCmd_Unshelve,419476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almLowLow.SCmd_Suppress,419476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almLowLow.SCmd_UnSuppress,419477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almLowLow.AEShelveTMRDN,419477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almLowLow.Bad,419477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almLowLow.Suppress,419478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.UnSuppress,419478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Shelve,419478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.UnShelve,419478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Enable,419478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Disable,419478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Ack,419478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Reset,419478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Suppressed,419478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Shelved,419478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Disabled,419478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Acked,419478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almLowLow.Alarm,419478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Fault,419488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almBrokenLoop.AlarmState,419488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almBrokenLoop.GlobalReset,419488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almBrokenLoop.FaultInAlarm,419488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almBrokenLoop.ALRM,419488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almBrokenLoop.ANUN,419488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almBrokenLoop.AKED,419488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almBrokenLoop.Resetable,419488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almBrokenLoop.REST,419488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almBrokenLoop.ACKN,419488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almBrokenLoop.UACK,419488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almBrokenLoop.MCmd_Enable,419488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.MCmd_Disable,419488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.OCmd_Shelve,419488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.OCmd_Unshelve,419488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.SCmd_Suppress,419488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.SCmd_UnSuppress,419489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almBrokenLoop.AEShelveTMRDN,419489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almBrokenLoop.Bad,419489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almBrokenLoop.Suppress,419490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.UnSuppress,419490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Shelve,419490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.UnShelve,419490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Enable,419490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Disable,419490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Ack,419490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Reset,419490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Suppressed,419490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Shelved,419490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Disabled,419490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Acked,419490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.Alarm,419490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Fault,419500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almOverRange.AlarmState,419500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almOverRange.GlobalReset,419500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almOverRange.FaultInAlarm,419500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almOverRange.ALRM,419500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almOverRange.ANUN,419500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almOverRange.AKED,419500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almOverRange.Resetable,419500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almOverRange.REST,419500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almOverRange.ACKN,419500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almOverRange.UACK,419500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almOverRange.MCmd_Enable,419500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almOverRange.MCmd_Disable,419500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almOverRange.OCmd_Shelve,419500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almOverRange.OCmd_Unshelve,419500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almOverRange.SCmd_Suppress,419500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almOverRange.SCmd_UnSuppress,419501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almOverRange.AEShelveTMRDN,419501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almOverRange.Bad,419501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almOverRange.Suppress,419502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.UnSuppress,419502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Shelve,419502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.UnShelve,419502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Enable,419502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Disable,419502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Ack,419502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Reset,419502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Suppressed,419502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Shelved,419502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Disabled,419502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Acked,419502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almOverRange.Alarm,419502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Fault,419512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almUnderRange.AlarmState,419512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almUnderRange.GlobalReset,419512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almUnderRange.FaultInAlarm,419512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almUnderRange.ALRM,419512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almUnderRange.ANUN,419512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almUnderRange.AKED,419512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almUnderRange.Resetable,419512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almUnderRange.REST,419512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almUnderRange.ACKN,419512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almUnderRange.UACK,419512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almUnderRange.MCmd_Enable,419512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.MCmd_Disable,419512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.OCmd_Shelve,419512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.OCmd_Unshelve,419512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.SCmd_Suppress,419512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.SCmd_UnSuppress,419513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almUnderRange.AEShelveTMRDN,419513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almUnderRange.Bad,419513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almUnderRange.Suppress,419514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.UnSuppress,419514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Shelve,419514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.UnShelve,419514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Enable,419514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Disable,419514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Ack,419514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Reset,419514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Suppressed,419514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Shelved,419514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Disabled,419514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Acked,419514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almUnderRange.Alarm,419514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Fault,419524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almRateOfChange.AlarmState,419524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almRateOfChange.GlobalReset,419524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almRateOfChange.FaultInAlarm,419524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almRateOfChange.ALRM,419524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almRateOfChange.ANUN,419524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almRateOfChange.AKED,419524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almRateOfChange.Resetable,419524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almRateOfChange.REST,419524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almRateOfChange.ACKN,419524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almRateOfChange.UACK,419524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almRateOfChange.MCmd_Enable,419524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.MCmd_Disable,419524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.OCmd_Shelve,419524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.OCmd_Unshelve,419524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.SCmd_Suppress,419524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.SCmd_UnSuppress,419525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almRateOfChange.AEShelveTMRDN,419525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almRateOfChange.Bad,419525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almRateOfChange.Suppress,419526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.UnSuppress,419526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Shelve,419526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.UnShelve,419526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Enable,419526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Disable,419526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Ack,419526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Reset,419526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Suppressed,419526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Shelved,419526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Disabled,419526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Acked,419526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almRateOfChange.Alarm,419526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Fault,419536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_3_VI5.almPLCFault.AlarmState,419536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_3_VI5.almPLCFault.GlobalReset,419536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_3_VI5.almPLCFault.FaultInAlarm,419536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_3_VI5.almPLCFault.ALRM,419536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_3_VI5.almPLCFault.ANUN,419536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_3_VI5.almPLCFault.AKED,419536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_3_VI5.almPLCFault.Resetable,419536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_3_VI5.almPLCFault.REST,419536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_3_VI5.almPLCFault.ACKN,419536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_3_VI5.almPLCFault.UACK,419536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_3_VI5.almPLCFault.MCmd_Enable,419536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.MCmd_Disable,419536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.OCmd_Shelve,419536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.OCmd_Unshelve,419536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.SCmd_Suppress,419536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.SCmd_UnSuppress,419537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_3_VI5.almPLCFault.AEShelveTMRDN,419537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_3_VI5.almPLCFault.Bad,419537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_3_VI5.almPLCFault.Suppress,419538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.UnSuppress,419538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Shelve,419538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.UnShelve,419538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Enable,419538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Disable,419538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Ack,419538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Reset,419538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Suppressed,419538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Shelved,419538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Disabled,419538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Acked,419538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_3_VI5.almPLCFault.Alarm,419538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Fault,419640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almHighHigh.AlarmState,419640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almHighHigh.GlobalReset,419640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almHighHigh.FaultInAlarm,419640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almHighHigh.ALRM,419640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almHighHigh.ANUN,419640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almHighHigh.AKED,419640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almHighHigh.Resetable,419640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almHighHigh.REST,419640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almHighHigh.ACKN,419640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almHighHigh.UACK,419640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almHighHigh.MCmd_Enable,419640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.MCmd_Disable,419640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.OCmd_Shelve,419640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.OCmd_Unshelve,419640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.SCmd_Suppress,419640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.SCmd_UnSuppress,419641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almHighHigh.AEShelveTMRDN,419641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almHighHigh.Bad,419641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almHighHigh.Suppress,419642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.UnSuppress,419642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Shelve,419642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.UnShelve,419642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Enable,419642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Disable,419642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Ack,419642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Reset,419642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Suppressed,419642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Shelved,419642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Disabled,419642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Acked,419642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almHighHigh.Alarm,419642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Fault,419652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almHigh.AlarmState,419652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almHigh.GlobalReset,419652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almHigh.FaultInAlarm,419652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almHigh.ALRM,419652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almHigh.ANUN,419652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almHigh.AKED,419652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almHigh.Resetable,419652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almHigh.REST,419652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almHigh.ACKN,419652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almHigh.UACK,419652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almHigh.MCmd_Enable,419652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almHigh.MCmd_Disable,419652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almHigh.OCmd_Shelve,419652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almHigh.OCmd_Unshelve,419652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almHigh.SCmd_Suppress,419652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almHigh.SCmd_UnSuppress,419653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almHigh.AEShelveTMRDN,419653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almHigh.Bad,419653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almHigh.Suppress,419654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.UnSuppress,419654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Shelve,419654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.UnShelve,419654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Enable,419654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Disable,419654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Ack,419654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Reset,419654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almHigh.Suppressed,419654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almHigh.Shelved,419654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almHigh.Disabled,419654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almHigh.Acked,419654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almHigh.Alarm,419654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Fault,419664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almLow.AlarmState,419664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almLow.GlobalReset,419664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almLow.FaultInAlarm,419664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almLow.ALRM,419664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almLow.ANUN,419664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almLow.AKED,419664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almLow.Resetable,419664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almLow.REST,419664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almLow.ACKN,419664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almLow.UACK,419664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almLow.MCmd_Enable,419664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almLow.MCmd_Disable,419664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almLow.OCmd_Shelve,419664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almLow.OCmd_Unshelve,419664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almLow.SCmd_Suppress,419664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almLow.SCmd_UnSuppress,419665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almLow.AEShelveTMRDN,419665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almLow.Bad,419665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almLow.Suppress,419666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.UnSuppress,419666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Shelve,419666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.UnShelve,419666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Enable,419666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Disable,419666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Ack,419666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Reset,419666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almLow.Suppressed,419666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almLow.Shelved,419666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almLow.Disabled,419666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almLow.Acked,419666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almLow.Alarm,419666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Fault,419676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almLowLow.AlarmState,419676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almLowLow.GlobalReset,419676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almLowLow.FaultInAlarm,419676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almLowLow.ALRM,419676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almLowLow.ANUN,419676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almLowLow.AKED,419676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almLowLow.Resetable,419676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almLowLow.REST,419676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almLowLow.ACKN,419676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almLowLow.UACK,419676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almLowLow.MCmd_Enable,419676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almLowLow.MCmd_Disable,419676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almLowLow.OCmd_Shelve,419676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almLowLow.OCmd_Unshelve,419676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almLowLow.SCmd_Suppress,419676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almLowLow.SCmd_UnSuppress,419677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almLowLow.AEShelveTMRDN,419677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almLowLow.Bad,419677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almLowLow.Suppress,419678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.UnSuppress,419678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Shelve,419678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.UnShelve,419678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Enable,419678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Disable,419678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Ack,419678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Reset,419678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Suppressed,419678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Shelved,419678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Disabled,419678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Acked,419678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almLowLow.Alarm,419678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Fault,419688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almBrokenLoop.AlarmState,419688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almBrokenLoop.GlobalReset,419688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almBrokenLoop.FaultInAlarm,419688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almBrokenLoop.ALRM,419688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almBrokenLoop.ANUN,419688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almBrokenLoop.AKED,419688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almBrokenLoop.Resetable,419688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almBrokenLoop.REST,419688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almBrokenLoop.ACKN,419688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almBrokenLoop.UACK,419688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almBrokenLoop.MCmd_Enable,419688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.MCmd_Disable,419688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.OCmd_Shelve,419688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.OCmd_Unshelve,419688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.SCmd_Suppress,419688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.SCmd_UnSuppress,419689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almBrokenLoop.AEShelveTMRDN,419689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almBrokenLoop.Bad,419689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almBrokenLoop.Suppress,419690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.UnSuppress,419690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Shelve,419690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.UnShelve,419690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Enable,419690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Disable,419690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Ack,419690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Reset,419690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Suppressed,419690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Shelved,419690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Disabled,419690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Acked,419690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.Alarm,419690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Fault,419700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almOverRange.AlarmState,419700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almOverRange.GlobalReset,419700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almOverRange.FaultInAlarm,419700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almOverRange.ALRM,419700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almOverRange.ANUN,419700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almOverRange.AKED,419700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almOverRange.Resetable,419700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almOverRange.REST,419700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almOverRange.ACKN,419700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almOverRange.UACK,419700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almOverRange.MCmd_Enable,419700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almOverRange.MCmd_Disable,419700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almOverRange.OCmd_Shelve,419700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almOverRange.OCmd_Unshelve,419700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almOverRange.SCmd_Suppress,419700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almOverRange.SCmd_UnSuppress,419701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almOverRange.AEShelveTMRDN,419701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almOverRange.Bad,419701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almOverRange.Suppress,419702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.UnSuppress,419702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Shelve,419702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.UnShelve,419702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Enable,419702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Disable,419702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Ack,419702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Reset,419702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Suppressed,419702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Shelved,419702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Disabled,419702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Acked,419702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almOverRange.Alarm,419702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Fault,419712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almUnderRange.AlarmState,419712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almUnderRange.GlobalReset,419712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almUnderRange.FaultInAlarm,419712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almUnderRange.ALRM,419712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almUnderRange.ANUN,419712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almUnderRange.AKED,419712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almUnderRange.Resetable,419712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almUnderRange.REST,419712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almUnderRange.ACKN,419712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almUnderRange.UACK,419712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almUnderRange.MCmd_Enable,419712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.MCmd_Disable,419712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.OCmd_Shelve,419712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.OCmd_Unshelve,419712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.SCmd_Suppress,419712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.SCmd_UnSuppress,419713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almUnderRange.AEShelveTMRDN,419713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almUnderRange.Bad,419713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almUnderRange.Suppress,419714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.UnSuppress,419714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Shelve,419714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.UnShelve,419714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Enable,419714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Disable,419714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Ack,419714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Reset,419714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Suppressed,419714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Shelved,419714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Disabled,419714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Acked,419714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almUnderRange.Alarm,419714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Fault,419724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almRateOfChange.AlarmState,419724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almRateOfChange.GlobalReset,419724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almRateOfChange.FaultInAlarm,419724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almRateOfChange.ALRM,419724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almRateOfChange.ANUN,419724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almRateOfChange.AKED,419724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almRateOfChange.Resetable,419724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almRateOfChange.REST,419724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almRateOfChange.ACKN,419724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almRateOfChange.UACK,419724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almRateOfChange.MCmd_Enable,419724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.MCmd_Disable,419724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.OCmd_Shelve,419724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.OCmd_Unshelve,419724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.SCmd_Suppress,419724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.SCmd_UnSuppress,419725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almRateOfChange.AEShelveTMRDN,419725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almRateOfChange.Bad,419725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almRateOfChange.Suppress,419726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.UnSuppress,419726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Shelve,419726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.UnShelve,419726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Enable,419726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Disable,419726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Ack,419726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Reset,419726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Suppressed,419726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Shelved,419726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Disabled,419726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Acked,419726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almRateOfChange.Alarm,419726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Fault,419736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI1.almPLCFault.AlarmState,419736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI1.almPLCFault.GlobalReset,419736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI1.almPLCFault.FaultInAlarm,419736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI1.almPLCFault.ALRM,419736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI1.almPLCFault.ANUN,419736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI1.almPLCFault.AKED,419736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI1.almPLCFault.Resetable,419736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI1.almPLCFault.REST,419736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI1.almPLCFault.ACKN,419736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI1.almPLCFault.UACK,419736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI1.almPLCFault.MCmd_Enable,419736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.MCmd_Disable,419736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.OCmd_Shelve,419736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.OCmd_Unshelve,419736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.SCmd_Suppress,419736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.SCmd_UnSuppress,419737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI1.almPLCFault.AEShelveTMRDN,419737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI1.almPLCFault.Bad,419737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI1.almPLCFault.Suppress,419738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.UnSuppress,419738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Shelve,419738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.UnShelve,419738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Enable,419738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Disable,419738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Ack,419738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Reset,419738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Suppressed,419738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Shelved,419738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Disabled,419738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Acked,419738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI1.almPLCFault.Alarm,419738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Fault,419840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almHighHigh.AlarmState,419840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almHighHigh.GlobalReset,419840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almHighHigh.FaultInAlarm,419840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almHighHigh.ALRM,419840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almHighHigh.ANUN,419840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almHighHigh.AKED,419840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almHighHigh.Resetable,419840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almHighHigh.REST,419840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almHighHigh.ACKN,419840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almHighHigh.UACK,419840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almHighHigh.MCmd_Enable,419840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.MCmd_Disable,419840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.OCmd_Shelve,419840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.OCmd_Unshelve,419840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.SCmd_Suppress,419840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.SCmd_UnSuppress,419841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almHighHigh.AEShelveTMRDN,419841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almHighHigh.Bad,419841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almHighHigh.Suppress,419842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.UnSuppress,419842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Shelve,419842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.UnShelve,419842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Enable,419842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Disable,419842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Ack,419842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Reset,419842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Suppressed,419842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Shelved,419842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Disabled,419842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Acked,419842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almHighHigh.Alarm,419842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Fault,419852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almHigh.AlarmState,419852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almHigh.GlobalReset,419852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almHigh.FaultInAlarm,419852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almHigh.ALRM,419852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almHigh.ANUN,419852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almHigh.AKED,419852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almHigh.Resetable,419852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almHigh.REST,419852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almHigh.ACKN,419852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almHigh.UACK,419852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almHigh.MCmd_Enable,419852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almHigh.MCmd_Disable,419852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almHigh.OCmd_Shelve,419852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almHigh.OCmd_Unshelve,419852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almHigh.SCmd_Suppress,419852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almHigh.SCmd_UnSuppress,419853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almHigh.AEShelveTMRDN,419853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almHigh.Bad,419853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almHigh.Suppress,419854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.UnSuppress,419854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Shelve,419854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.UnShelve,419854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Enable,419854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Disable,419854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Ack,419854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Reset,419854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almHigh.Suppressed,419854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almHigh.Shelved,419854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almHigh.Disabled,419854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almHigh.Acked,419854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almHigh.Alarm,419854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Fault,419864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almLow.AlarmState,419864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almLow.GlobalReset,419864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almLow.FaultInAlarm,419864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almLow.ALRM,419864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almLow.ANUN,419864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almLow.AKED,419864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almLow.Resetable,419864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almLow.REST,419864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almLow.ACKN,419864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almLow.UACK,419864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almLow.MCmd_Enable,419864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almLow.MCmd_Disable,419864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almLow.OCmd_Shelve,419864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almLow.OCmd_Unshelve,419864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almLow.SCmd_Suppress,419864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almLow.SCmd_UnSuppress,419865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almLow.AEShelveTMRDN,419865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almLow.Bad,419865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almLow.Suppress,419866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.UnSuppress,419866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Shelve,419866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.UnShelve,419866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Enable,419866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Disable,419866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Ack,419866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Reset,419866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almLow.Suppressed,419866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almLow.Shelved,419866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almLow.Disabled,419866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almLow.Acked,419866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almLow.Alarm,419866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Fault,419876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almLowLow.AlarmState,419876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almLowLow.GlobalReset,419876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almLowLow.FaultInAlarm,419876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almLowLow.ALRM,419876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almLowLow.ANUN,419876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almLowLow.AKED,419876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almLowLow.Resetable,419876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almLowLow.REST,419876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almLowLow.ACKN,419876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almLowLow.UACK,419876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almLowLow.MCmd_Enable,419876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almLowLow.MCmd_Disable,419876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almLowLow.OCmd_Shelve,419876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almLowLow.OCmd_Unshelve,419876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almLowLow.SCmd_Suppress,419876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almLowLow.SCmd_UnSuppress,419877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almLowLow.AEShelveTMRDN,419877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almLowLow.Bad,419877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almLowLow.Suppress,419878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.UnSuppress,419878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Shelve,419878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.UnShelve,419878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Enable,419878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Disable,419878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Ack,419878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Reset,419878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Suppressed,419878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Shelved,419878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Disabled,419878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Acked,419878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almLowLow.Alarm,419878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Fault,419888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almBrokenLoop.AlarmState,419888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almBrokenLoop.GlobalReset,419888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almBrokenLoop.FaultInAlarm,419888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almBrokenLoop.ALRM,419888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almBrokenLoop.ANUN,419888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almBrokenLoop.AKED,419888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almBrokenLoop.Resetable,419888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almBrokenLoop.REST,419888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almBrokenLoop.ACKN,419888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almBrokenLoop.UACK,419888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almBrokenLoop.MCmd_Enable,419888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.MCmd_Disable,419888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.OCmd_Shelve,419888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.OCmd_Unshelve,419888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.SCmd_Suppress,419888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.SCmd_UnSuppress,419889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almBrokenLoop.AEShelveTMRDN,419889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almBrokenLoop.Bad,419889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almBrokenLoop.Suppress,419890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.UnSuppress,419890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Shelve,419890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.UnShelve,419890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Enable,419890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Disable,419890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Ack,419890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Reset,419890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Suppressed,419890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Shelved,419890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Disabled,419890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Acked,419890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.Alarm,419890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Fault,419900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almOverRange.AlarmState,419900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almOverRange.GlobalReset,419900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almOverRange.FaultInAlarm,419900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almOverRange.ALRM,419900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almOverRange.ANUN,419900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almOverRange.AKED,419900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almOverRange.Resetable,419900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almOverRange.REST,419900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almOverRange.ACKN,419900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almOverRange.UACK,419900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almOverRange.MCmd_Enable,419900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almOverRange.MCmd_Disable,419900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almOverRange.OCmd_Shelve,419900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almOverRange.OCmd_Unshelve,419900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almOverRange.SCmd_Suppress,419900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almOverRange.SCmd_UnSuppress,419901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almOverRange.AEShelveTMRDN,419901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almOverRange.Bad,419901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almOverRange.Suppress,419902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.UnSuppress,419902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Shelve,419902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.UnShelve,419902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Enable,419902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Disable,419902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Ack,419902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Reset,419902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Suppressed,419902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Shelved,419902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Disabled,419902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Acked,419902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almOverRange.Alarm,419902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Fault,419912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almUnderRange.AlarmState,419912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almUnderRange.GlobalReset,419912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almUnderRange.FaultInAlarm,419912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almUnderRange.ALRM,419912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almUnderRange.ANUN,419912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almUnderRange.AKED,419912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almUnderRange.Resetable,419912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almUnderRange.REST,419912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almUnderRange.ACKN,419912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almUnderRange.UACK,419912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almUnderRange.MCmd_Enable,419912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.MCmd_Disable,419912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.OCmd_Shelve,419912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.OCmd_Unshelve,419912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.SCmd_Suppress,419912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.SCmd_UnSuppress,419913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almUnderRange.AEShelveTMRDN,419913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almUnderRange.Bad,419913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almUnderRange.Suppress,419914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.UnSuppress,419914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Shelve,419914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.UnShelve,419914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Enable,419914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Disable,419914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Ack,419914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Reset,419914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Suppressed,419914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Shelved,419914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Disabled,419914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Acked,419914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almUnderRange.Alarm,419914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Fault,419924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almRateOfChange.AlarmState,419924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almRateOfChange.GlobalReset,419924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almRateOfChange.FaultInAlarm,419924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almRateOfChange.ALRM,419924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almRateOfChange.ANUN,419924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almRateOfChange.AKED,419924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almRateOfChange.Resetable,419924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almRateOfChange.REST,419924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almRateOfChange.ACKN,419924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almRateOfChange.UACK,419924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almRateOfChange.MCmd_Enable,419924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.MCmd_Disable,419924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.OCmd_Shelve,419924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.OCmd_Unshelve,419924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.SCmd_Suppress,419924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.SCmd_UnSuppress,419925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almRateOfChange.AEShelveTMRDN,419925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almRateOfChange.Bad,419925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almRateOfChange.Suppress,419926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.UnSuppress,419926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Shelve,419926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.UnShelve,419926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Enable,419926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Disable,419926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Ack,419926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Reset,419926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Suppressed,419926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Shelved,419926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Disabled,419926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Acked,419926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almRateOfChange.Alarm,419926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Fault,419936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI2.almPLCFault.AlarmState,419936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI2.almPLCFault.GlobalReset,419936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI2.almPLCFault.FaultInAlarm,419936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI2.almPLCFault.ALRM,419936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI2.almPLCFault.ANUN,419936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI2.almPLCFault.AKED,419936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI2.almPLCFault.Resetable,419936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI2.almPLCFault.REST,419936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI2.almPLCFault.ACKN,419936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI2.almPLCFault.UACK,419936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI2.almPLCFault.MCmd_Enable,419936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.MCmd_Disable,419936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.OCmd_Shelve,419936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.OCmd_Unshelve,419936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.SCmd_Suppress,419936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.SCmd_UnSuppress,419937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI2.almPLCFault.AEShelveTMRDN,419937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI2.almPLCFault.Bad,419937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI2.almPLCFault.Suppress,419938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.UnSuppress,419938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Shelve,419938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.UnShelve,419938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Enable,419938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Disable,419938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Ack,419938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Reset,419938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Suppressed,419938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Shelved,419938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Disabled,419938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Acked,419938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI2.almPLCFault.Alarm,419938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Fault,420040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almHighHigh.AlarmState,420040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almHighHigh.GlobalReset,420040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almHighHigh.FaultInAlarm,420040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almHighHigh.ALRM,420040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almHighHigh.ANUN,420040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almHighHigh.AKED,420040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almHighHigh.Resetable,420040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almHighHigh.REST,420040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almHighHigh.ACKN,420040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almHighHigh.UACK,420040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almHighHigh.MCmd_Enable,420040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.MCmd_Disable,420040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.OCmd_Shelve,420040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.OCmd_Unshelve,420040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.SCmd_Suppress,420040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.SCmd_UnSuppress,420041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almHighHigh.AEShelveTMRDN,420041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almHighHigh.Bad,420041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almHighHigh.Suppress,420042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.UnSuppress,420042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Shelve,420042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.UnShelve,420042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Enable,420042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Disable,420042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Ack,420042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Reset,420042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Suppressed,420042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Shelved,420042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Disabled,420042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Acked,420042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almHighHigh.Alarm,420042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Fault,420052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almHigh.AlarmState,420052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almHigh.GlobalReset,420052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almHigh.FaultInAlarm,420052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almHigh.ALRM,420052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almHigh.ANUN,420052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almHigh.AKED,420052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almHigh.Resetable,420052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almHigh.REST,420052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almHigh.ACKN,420052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almHigh.UACK,420052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almHigh.MCmd_Enable,420052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almHigh.MCmd_Disable,420052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almHigh.OCmd_Shelve,420052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almHigh.OCmd_Unshelve,420052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almHigh.SCmd_Suppress,420052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almHigh.SCmd_UnSuppress,420053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almHigh.AEShelveTMRDN,420053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almHigh.Bad,420053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almHigh.Suppress,420054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.UnSuppress,420054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Shelve,420054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.UnShelve,420054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Enable,420054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Disable,420054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Ack,420054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Reset,420054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almHigh.Suppressed,420054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almHigh.Shelved,420054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almHigh.Disabled,420054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almHigh.Acked,420054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almHigh.Alarm,420054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Fault,420064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almLow.AlarmState,420064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almLow.GlobalReset,420064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almLow.FaultInAlarm,420064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almLow.ALRM,420064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almLow.ANUN,420064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almLow.AKED,420064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almLow.Resetable,420064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almLow.REST,420064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almLow.ACKN,420064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almLow.UACK,420064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almLow.MCmd_Enable,420064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almLow.MCmd_Disable,420064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almLow.OCmd_Shelve,420064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almLow.OCmd_Unshelve,420064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almLow.SCmd_Suppress,420064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almLow.SCmd_UnSuppress,420065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almLow.AEShelveTMRDN,420065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almLow.Bad,420065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almLow.Suppress,420066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.UnSuppress,420066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Shelve,420066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.UnShelve,420066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Enable,420066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Disable,420066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Ack,420066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Reset,420066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almLow.Suppressed,420066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almLow.Shelved,420066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almLow.Disabled,420066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almLow.Acked,420066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almLow.Alarm,420066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Fault,420076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almLowLow.AlarmState,420076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almLowLow.GlobalReset,420076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almLowLow.FaultInAlarm,420076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almLowLow.ALRM,420076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almLowLow.ANUN,420076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almLowLow.AKED,420076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almLowLow.Resetable,420076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almLowLow.REST,420076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almLowLow.ACKN,420076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almLowLow.UACK,420076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almLowLow.MCmd_Enable,420076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almLowLow.MCmd_Disable,420076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almLowLow.OCmd_Shelve,420076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almLowLow.OCmd_Unshelve,420076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almLowLow.SCmd_Suppress,420076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almLowLow.SCmd_UnSuppress,420077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almLowLow.AEShelveTMRDN,420077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almLowLow.Bad,420077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almLowLow.Suppress,420078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.UnSuppress,420078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Shelve,420078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.UnShelve,420078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Enable,420078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Disable,420078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Ack,420078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Reset,420078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Suppressed,420078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Shelved,420078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Disabled,420078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Acked,420078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almLowLow.Alarm,420078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Fault,420088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almBrokenLoop.AlarmState,420088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almBrokenLoop.GlobalReset,420088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almBrokenLoop.FaultInAlarm,420088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almBrokenLoop.ALRM,420088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almBrokenLoop.ANUN,420088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almBrokenLoop.AKED,420088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almBrokenLoop.Resetable,420088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almBrokenLoop.REST,420088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almBrokenLoop.ACKN,420088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almBrokenLoop.UACK,420088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almBrokenLoop.MCmd_Enable,420088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.MCmd_Disable,420088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.OCmd_Shelve,420088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.OCmd_Unshelve,420088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.SCmd_Suppress,420088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.SCmd_UnSuppress,420089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almBrokenLoop.AEShelveTMRDN,420089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almBrokenLoop.Bad,420089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almBrokenLoop.Suppress,420090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.UnSuppress,420090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Shelve,420090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.UnShelve,420090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Enable,420090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Disable,420090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Ack,420090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Reset,420090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Suppressed,420090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Shelved,420090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Disabled,420090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Acked,420090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.Alarm,420090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Fault,420100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almOverRange.AlarmState,420100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almOverRange.GlobalReset,420100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almOverRange.FaultInAlarm,420100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almOverRange.ALRM,420100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almOverRange.ANUN,420100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almOverRange.AKED,420100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almOverRange.Resetable,420100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almOverRange.REST,420100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almOverRange.ACKN,420100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almOverRange.UACK,420100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almOverRange.MCmd_Enable,420100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almOverRange.MCmd_Disable,420100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almOverRange.OCmd_Shelve,420100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almOverRange.OCmd_Unshelve,420100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almOverRange.SCmd_Suppress,420100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almOverRange.SCmd_UnSuppress,420101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almOverRange.AEShelveTMRDN,420101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almOverRange.Bad,420101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almOverRange.Suppress,420102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.UnSuppress,420102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Shelve,420102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.UnShelve,420102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Enable,420102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Disable,420102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Ack,420102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Reset,420102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Suppressed,420102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Shelved,420102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Disabled,420102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Acked,420102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almOverRange.Alarm,420102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Fault,420112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almUnderRange.AlarmState,420112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almUnderRange.GlobalReset,420112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almUnderRange.FaultInAlarm,420112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almUnderRange.ALRM,420112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almUnderRange.ANUN,420112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almUnderRange.AKED,420112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almUnderRange.Resetable,420112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almUnderRange.REST,420112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almUnderRange.ACKN,420112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almUnderRange.UACK,420112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almUnderRange.MCmd_Enable,420112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.MCmd_Disable,420112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.OCmd_Shelve,420112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.OCmd_Unshelve,420112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.SCmd_Suppress,420112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.SCmd_UnSuppress,420113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almUnderRange.AEShelveTMRDN,420113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almUnderRange.Bad,420113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almUnderRange.Suppress,420114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.UnSuppress,420114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Shelve,420114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.UnShelve,420114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Enable,420114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Disable,420114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Ack,420114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Reset,420114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Suppressed,420114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Shelved,420114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Disabled,420114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Acked,420114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almUnderRange.Alarm,420114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Fault,420124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almRateOfChange.AlarmState,420124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almRateOfChange.GlobalReset,420124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almRateOfChange.FaultInAlarm,420124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almRateOfChange.ALRM,420124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almRateOfChange.ANUN,420124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almRateOfChange.AKED,420124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almRateOfChange.Resetable,420124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almRateOfChange.REST,420124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almRateOfChange.ACKN,420124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almRateOfChange.UACK,420124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almRateOfChange.MCmd_Enable,420124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.MCmd_Disable,420124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.OCmd_Shelve,420124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.OCmd_Unshelve,420124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.SCmd_Suppress,420124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.SCmd_UnSuppress,420125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almRateOfChange.AEShelveTMRDN,420125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almRateOfChange.Bad,420125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almRateOfChange.Suppress,420126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.UnSuppress,420126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Shelve,420126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.UnShelve,420126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Enable,420126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Disable,420126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Ack,420126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Reset,420126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Suppressed,420126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Shelved,420126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Disabled,420126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Acked,420126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almRateOfChange.Alarm,420126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Fault,420136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI3.almPLCFault.AlarmState,420136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI3.almPLCFault.GlobalReset,420136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI3.almPLCFault.FaultInAlarm,420136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI3.almPLCFault.ALRM,420136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI3.almPLCFault.ANUN,420136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI3.almPLCFault.AKED,420136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI3.almPLCFault.Resetable,420136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI3.almPLCFault.REST,420136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI3.almPLCFault.ACKN,420136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI3.almPLCFault.UACK,420136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI3.almPLCFault.MCmd_Enable,420136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.MCmd_Disable,420136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.OCmd_Shelve,420136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.OCmd_Unshelve,420136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.SCmd_Suppress,420136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.SCmd_UnSuppress,420137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI3.almPLCFault.AEShelveTMRDN,420137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI3.almPLCFault.Bad,420137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI3.almPLCFault.Suppress,420138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.UnSuppress,420138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Shelve,420138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.UnShelve,420138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Enable,420138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Disable,420138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Ack,420138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Reset,420138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Suppressed,420138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Shelved,420138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Disabled,420138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Acked,420138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI3.almPLCFault.Alarm,420138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Fault,420240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almHighHigh.AlarmState,420240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almHighHigh.GlobalReset,420240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almHighHigh.FaultInAlarm,420240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almHighHigh.ALRM,420240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almHighHigh.ANUN,420240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almHighHigh.AKED,420240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almHighHigh.Resetable,420240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almHighHigh.REST,420240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almHighHigh.ACKN,420240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almHighHigh.UACK,420240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almHighHigh.MCmd_Enable,420240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.MCmd_Disable,420240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.OCmd_Shelve,420240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.OCmd_Unshelve,420240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.SCmd_Suppress,420240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.SCmd_UnSuppress,420241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almHighHigh.AEShelveTMRDN,420241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almHighHigh.Bad,420241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almHighHigh.Suppress,420242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.UnSuppress,420242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Shelve,420242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.UnShelve,420242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Enable,420242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Disable,420242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Ack,420242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Reset,420242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Suppressed,420242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Shelved,420242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Disabled,420242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Acked,420242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almHighHigh.Alarm,420242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Fault,420252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almHigh.AlarmState,420252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almHigh.GlobalReset,420252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almHigh.FaultInAlarm,420252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almHigh.ALRM,420252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almHigh.ANUN,420252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almHigh.AKED,420252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almHigh.Resetable,420252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almHigh.REST,420252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almHigh.ACKN,420252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almHigh.UACK,420252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almHigh.MCmd_Enable,420252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almHigh.MCmd_Disable,420252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almHigh.OCmd_Shelve,420252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almHigh.OCmd_Unshelve,420252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almHigh.SCmd_Suppress,420252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almHigh.SCmd_UnSuppress,420253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almHigh.AEShelveTMRDN,420253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almHigh.Bad,420253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almHigh.Suppress,420254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.UnSuppress,420254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Shelve,420254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.UnShelve,420254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Enable,420254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Disable,420254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Ack,420254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Reset,420254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almHigh.Suppressed,420254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almHigh.Shelved,420254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almHigh.Disabled,420254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almHigh.Acked,420254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almHigh.Alarm,420254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Fault,420264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almLow.AlarmState,420264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almLow.GlobalReset,420264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almLow.FaultInAlarm,420264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almLow.ALRM,420264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almLow.ANUN,420264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almLow.AKED,420264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almLow.Resetable,420264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almLow.REST,420264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almLow.ACKN,420264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almLow.UACK,420264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almLow.MCmd_Enable,420264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almLow.MCmd_Disable,420264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almLow.OCmd_Shelve,420264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almLow.OCmd_Unshelve,420264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almLow.SCmd_Suppress,420264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almLow.SCmd_UnSuppress,420265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almLow.AEShelveTMRDN,420265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almLow.Bad,420265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almLow.Suppress,420266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.UnSuppress,420266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Shelve,420266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.UnShelve,420266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Enable,420266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Disable,420266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Ack,420266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Reset,420266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almLow.Suppressed,420266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almLow.Shelved,420266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almLow.Disabled,420266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almLow.Acked,420266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almLow.Alarm,420266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Fault,420276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almLowLow.AlarmState,420276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almLowLow.GlobalReset,420276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almLowLow.FaultInAlarm,420276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almLowLow.ALRM,420276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almLowLow.ANUN,420276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almLowLow.AKED,420276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almLowLow.Resetable,420276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almLowLow.REST,420276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almLowLow.ACKN,420276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almLowLow.UACK,420276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almLowLow.MCmd_Enable,420276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almLowLow.MCmd_Disable,420276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almLowLow.OCmd_Shelve,420276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almLowLow.OCmd_Unshelve,420276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almLowLow.SCmd_Suppress,420276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almLowLow.SCmd_UnSuppress,420277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almLowLow.AEShelveTMRDN,420277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almLowLow.Bad,420277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almLowLow.Suppress,420278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.UnSuppress,420278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Shelve,420278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.UnShelve,420278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Enable,420278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Disable,420278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Ack,420278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Reset,420278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Suppressed,420278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Shelved,420278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Disabled,420278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Acked,420278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almLowLow.Alarm,420278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Fault,420288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almBrokenLoop.AlarmState,420288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almBrokenLoop.GlobalReset,420288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almBrokenLoop.FaultInAlarm,420288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almBrokenLoop.ALRM,420288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almBrokenLoop.ANUN,420288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almBrokenLoop.AKED,420288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almBrokenLoop.Resetable,420288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almBrokenLoop.REST,420288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almBrokenLoop.ACKN,420288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almBrokenLoop.UACK,420288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almBrokenLoop.MCmd_Enable,420288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.MCmd_Disable,420288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.OCmd_Shelve,420288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.OCmd_Unshelve,420288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.SCmd_Suppress,420288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.SCmd_UnSuppress,420289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almBrokenLoop.AEShelveTMRDN,420289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almBrokenLoop.Bad,420289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almBrokenLoop.Suppress,420290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.UnSuppress,420290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Shelve,420290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.UnShelve,420290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Enable,420290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Disable,420290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Ack,420290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Reset,420290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Suppressed,420290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Shelved,420290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Disabled,420290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Acked,420290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.Alarm,420290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Fault,420300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almOverRange.AlarmState,420300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almOverRange.GlobalReset,420300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almOverRange.FaultInAlarm,420300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almOverRange.ALRM,420300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almOverRange.ANUN,420300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almOverRange.AKED,420300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almOverRange.Resetable,420300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almOverRange.REST,420300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almOverRange.ACKN,420300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almOverRange.UACK,420300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almOverRange.MCmd_Enable,420300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almOverRange.MCmd_Disable,420300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almOverRange.OCmd_Shelve,420300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almOverRange.OCmd_Unshelve,420300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almOverRange.SCmd_Suppress,420300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almOverRange.SCmd_UnSuppress,420301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almOverRange.AEShelveTMRDN,420301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almOverRange.Bad,420301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almOverRange.Suppress,420302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.UnSuppress,420302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Shelve,420302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.UnShelve,420302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Enable,420302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Disable,420302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Ack,420302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Reset,420302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Suppressed,420302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Shelved,420302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Disabled,420302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Acked,420302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almOverRange.Alarm,420302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Fault,420312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almUnderRange.AlarmState,420312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almUnderRange.GlobalReset,420312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almUnderRange.FaultInAlarm,420312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almUnderRange.ALRM,420312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almUnderRange.ANUN,420312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almUnderRange.AKED,420312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almUnderRange.Resetable,420312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almUnderRange.REST,420312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almUnderRange.ACKN,420312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almUnderRange.UACK,420312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almUnderRange.MCmd_Enable,420312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.MCmd_Disable,420312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.OCmd_Shelve,420312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.OCmd_Unshelve,420312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.SCmd_Suppress,420312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.SCmd_UnSuppress,420313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almUnderRange.AEShelveTMRDN,420313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almUnderRange.Bad,420313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almUnderRange.Suppress,420314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.UnSuppress,420314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Shelve,420314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.UnShelve,420314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Enable,420314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Disable,420314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Ack,420314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Reset,420314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Suppressed,420314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Shelved,420314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Disabled,420314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Acked,420314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almUnderRange.Alarm,420314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Fault,420324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almRateOfChange.AlarmState,420324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almRateOfChange.GlobalReset,420324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almRateOfChange.FaultInAlarm,420324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almRateOfChange.ALRM,420324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almRateOfChange.ANUN,420324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almRateOfChange.AKED,420324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almRateOfChange.Resetable,420324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almRateOfChange.REST,420324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almRateOfChange.ACKN,420324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almRateOfChange.UACK,420324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almRateOfChange.MCmd_Enable,420324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.MCmd_Disable,420324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.OCmd_Shelve,420324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.OCmd_Unshelve,420324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.SCmd_Suppress,420324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.SCmd_UnSuppress,420325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almRateOfChange.AEShelveTMRDN,420325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almRateOfChange.Bad,420325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almRateOfChange.Suppress,420326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.UnSuppress,420326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Shelve,420326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.UnShelve,420326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Enable,420326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Disable,420326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Ack,420326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Reset,420326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Suppressed,420326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Shelved,420326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Disabled,420326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Acked,420326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almRateOfChange.Alarm,420326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Fault,420336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI4.almPLCFault.AlarmState,420336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI4.almPLCFault.GlobalReset,420336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI4.almPLCFault.FaultInAlarm,420336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI4.almPLCFault.ALRM,420336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI4.almPLCFault.ANUN,420336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI4.almPLCFault.AKED,420336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI4.almPLCFault.Resetable,420336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI4.almPLCFault.REST,420336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI4.almPLCFault.ACKN,420336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI4.almPLCFault.UACK,420336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI4.almPLCFault.MCmd_Enable,420336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.MCmd_Disable,420336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.OCmd_Shelve,420336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.OCmd_Unshelve,420336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.SCmd_Suppress,420336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.SCmd_UnSuppress,420337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI4.almPLCFault.AEShelveTMRDN,420337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI4.almPLCFault.Bad,420337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI4.almPLCFault.Suppress,420338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.UnSuppress,420338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Shelve,420338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.UnShelve,420338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Enable,420338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Disable,420338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Ack,420338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Reset,420338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Suppressed,420338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Shelved,420338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Disabled,420338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Acked,420338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI4.almPLCFault.Alarm,420338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Fault,420440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almHighHigh.AlarmState,420440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almHighHigh.GlobalReset,420440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almHighHigh.FaultInAlarm,420440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almHighHigh.ALRM,420440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almHighHigh.ANUN,420440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almHighHigh.AKED,420440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almHighHigh.Resetable,420440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almHighHigh.REST,420440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almHighHigh.ACKN,420440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almHighHigh.UACK,420440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almHighHigh.MCmd_Enable,420440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.MCmd_Disable,420440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.OCmd_Shelve,420440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.OCmd_Unshelve,420440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.SCmd_Suppress,420440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.SCmd_UnSuppress,420441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almHighHigh.AEShelveTMRDN,420441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almHighHigh.Bad,420441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almHighHigh.Suppress,420442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.UnSuppress,420442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Shelve,420442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.UnShelve,420442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Enable,420442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Disable,420442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Ack,420442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Reset,420442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Suppressed,420442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Shelved,420442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Disabled,420442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Acked,420442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almHighHigh.Alarm,420442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Fault,420452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almHigh.AlarmState,420452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almHigh.GlobalReset,420452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almHigh.FaultInAlarm,420452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almHigh.ALRM,420452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almHigh.ANUN,420452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almHigh.AKED,420452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almHigh.Resetable,420452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almHigh.REST,420452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almHigh.ACKN,420452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almHigh.UACK,420452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almHigh.MCmd_Enable,420452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almHigh.MCmd_Disable,420452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almHigh.OCmd_Shelve,420452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almHigh.OCmd_Unshelve,420452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almHigh.SCmd_Suppress,420452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almHigh.SCmd_UnSuppress,420453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almHigh.AEShelveTMRDN,420453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almHigh.Bad,420453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almHigh.Suppress,420454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.UnSuppress,420454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Shelve,420454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.UnShelve,420454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Enable,420454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Disable,420454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Ack,420454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Reset,420454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almHigh.Suppressed,420454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almHigh.Shelved,420454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almHigh.Disabled,420454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almHigh.Acked,420454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almHigh.Alarm,420454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Fault,420464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almLow.AlarmState,420464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almLow.GlobalReset,420464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almLow.FaultInAlarm,420464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almLow.ALRM,420464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almLow.ANUN,420464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almLow.AKED,420464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almLow.Resetable,420464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almLow.REST,420464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almLow.ACKN,420464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almLow.UACK,420464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almLow.MCmd_Enable,420464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almLow.MCmd_Disable,420464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almLow.OCmd_Shelve,420464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almLow.OCmd_Unshelve,420464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almLow.SCmd_Suppress,420464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almLow.SCmd_UnSuppress,420465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almLow.AEShelveTMRDN,420465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almLow.Bad,420465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almLow.Suppress,420466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.UnSuppress,420466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Shelve,420466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.UnShelve,420466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Enable,420466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Disable,420466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Ack,420466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Reset,420466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almLow.Suppressed,420466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almLow.Shelved,420466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almLow.Disabled,420466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almLow.Acked,420466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almLow.Alarm,420466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Fault,420476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almLowLow.AlarmState,420476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almLowLow.GlobalReset,420476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almLowLow.FaultInAlarm,420476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almLowLow.ALRM,420476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almLowLow.ANUN,420476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almLowLow.AKED,420476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almLowLow.Resetable,420476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almLowLow.REST,420476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almLowLow.ACKN,420476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almLowLow.UACK,420476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almLowLow.MCmd_Enable,420476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almLowLow.MCmd_Disable,420476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almLowLow.OCmd_Shelve,420476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almLowLow.OCmd_Unshelve,420476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almLowLow.SCmd_Suppress,420476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almLowLow.SCmd_UnSuppress,420477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almLowLow.AEShelveTMRDN,420477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almLowLow.Bad,420477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almLowLow.Suppress,420478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.UnSuppress,420478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Shelve,420478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.UnShelve,420478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Enable,420478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Disable,420478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Ack,420478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Reset,420478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Suppressed,420478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Shelved,420478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Disabled,420478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Acked,420478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almLowLow.Alarm,420478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Fault,420488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almBrokenLoop.AlarmState,420488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almBrokenLoop.GlobalReset,420488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almBrokenLoop.FaultInAlarm,420488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almBrokenLoop.ALRM,420488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almBrokenLoop.ANUN,420488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almBrokenLoop.AKED,420488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almBrokenLoop.Resetable,420488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almBrokenLoop.REST,420488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almBrokenLoop.ACKN,420488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almBrokenLoop.UACK,420488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almBrokenLoop.MCmd_Enable,420488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.MCmd_Disable,420488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.OCmd_Shelve,420488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.OCmd_Unshelve,420488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.SCmd_Suppress,420488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.SCmd_UnSuppress,420489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almBrokenLoop.AEShelveTMRDN,420489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almBrokenLoop.Bad,420489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almBrokenLoop.Suppress,420490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.UnSuppress,420490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Shelve,420490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.UnShelve,420490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Enable,420490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Disable,420490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Ack,420490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Reset,420490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Suppressed,420490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Shelved,420490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Disabled,420490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Acked,420490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.Alarm,420490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Fault,420500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almOverRange.AlarmState,420500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almOverRange.GlobalReset,420500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almOverRange.FaultInAlarm,420500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almOverRange.ALRM,420500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almOverRange.ANUN,420500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almOverRange.AKED,420500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almOverRange.Resetable,420500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almOverRange.REST,420500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almOverRange.ACKN,420500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almOverRange.UACK,420500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almOverRange.MCmd_Enable,420500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almOverRange.MCmd_Disable,420500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almOverRange.OCmd_Shelve,420500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almOverRange.OCmd_Unshelve,420500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almOverRange.SCmd_Suppress,420500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almOverRange.SCmd_UnSuppress,420501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almOverRange.AEShelveTMRDN,420501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almOverRange.Bad,420501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almOverRange.Suppress,420502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.UnSuppress,420502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Shelve,420502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.UnShelve,420502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Enable,420502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Disable,420502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Ack,420502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Reset,420502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Suppressed,420502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Shelved,420502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Disabled,420502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Acked,420502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almOverRange.Alarm,420502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Fault,420512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almUnderRange.AlarmState,420512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almUnderRange.GlobalReset,420512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almUnderRange.FaultInAlarm,420512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almUnderRange.ALRM,420512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almUnderRange.ANUN,420512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almUnderRange.AKED,420512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almUnderRange.Resetable,420512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almUnderRange.REST,420512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almUnderRange.ACKN,420512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almUnderRange.UACK,420512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almUnderRange.MCmd_Enable,420512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.MCmd_Disable,420512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.OCmd_Shelve,420512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.OCmd_Unshelve,420512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.SCmd_Suppress,420512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.SCmd_UnSuppress,420513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almUnderRange.AEShelveTMRDN,420513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almUnderRange.Bad,420513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almUnderRange.Suppress,420514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.UnSuppress,420514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Shelve,420514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.UnShelve,420514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Enable,420514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Disable,420514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Ack,420514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Reset,420514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Suppressed,420514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Shelved,420514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Disabled,420514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Acked,420514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almUnderRange.Alarm,420514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Fault,420524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almRateOfChange.AlarmState,420524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almRateOfChange.GlobalReset,420524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almRateOfChange.FaultInAlarm,420524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almRateOfChange.ALRM,420524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almRateOfChange.ANUN,420524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almRateOfChange.AKED,420524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almRateOfChange.Resetable,420524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almRateOfChange.REST,420524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almRateOfChange.ACKN,420524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almRateOfChange.UACK,420524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almRateOfChange.MCmd_Enable,420524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.MCmd_Disable,420524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.OCmd_Shelve,420524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.OCmd_Unshelve,420524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.SCmd_Suppress,420524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.SCmd_UnSuppress,420525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almRateOfChange.AEShelveTMRDN,420525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almRateOfChange.Bad,420525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almRateOfChange.Suppress,420526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.UnSuppress,420526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Shelve,420526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.UnShelve,420526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Enable,420526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Disable,420526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Ack,420526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Reset,420526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Suppressed,420526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Shelved,420526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Disabled,420526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Acked,420526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almRateOfChange.Alarm,420526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Fault,420536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_4_VI5.almPLCFault.AlarmState,420536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_4_VI5.almPLCFault.GlobalReset,420536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_4_VI5.almPLCFault.FaultInAlarm,420536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_4_VI5.almPLCFault.ALRM,420536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_4_VI5.almPLCFault.ANUN,420536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_4_VI5.almPLCFault.AKED,420536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_4_VI5.almPLCFault.Resetable,420536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_4_VI5.almPLCFault.REST,420536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_4_VI5.almPLCFault.ACKN,420536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_4_VI5.almPLCFault.UACK,420536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_4_VI5.almPLCFault.MCmd_Enable,420536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.MCmd_Disable,420536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.OCmd_Shelve,420536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.OCmd_Unshelve,420536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.SCmd_Suppress,420536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.SCmd_UnSuppress,420537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_4_VI5.almPLCFault.AEShelveTMRDN,420537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_4_VI5.almPLCFault.Bad,420537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_4_VI5.almPLCFault.Suppress,420538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.UnSuppress,420538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Shelve,420538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.UnShelve,420538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Enable,420538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Disable,420538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Ack,420538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Reset,420538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Suppressed,420538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Shelved,420538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Disabled,420538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Acked,420538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_4_VI5.almPLCFault.Alarm,420538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Fault,420640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almHighHigh.AlarmState,420640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almHighHigh.GlobalReset,420640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almHighHigh.FaultInAlarm,420640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almHighHigh.ALRM,420640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almHighHigh.ANUN,420640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almHighHigh.AKED,420640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almHighHigh.Resetable,420640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almHighHigh.REST,420640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almHighHigh.ACKN,420640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almHighHigh.UACK,420640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almHighHigh.MCmd_Enable,420640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.MCmd_Disable,420640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.OCmd_Shelve,420640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.OCmd_Unshelve,420640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.SCmd_Suppress,420640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.SCmd_UnSuppress,420641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almHighHigh.AEShelveTMRDN,420641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almHighHigh.Bad,420641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almHighHigh.Suppress,420642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.UnSuppress,420642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Shelve,420642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.UnShelve,420642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Enable,420642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Disable,420642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Ack,420642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Reset,420642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Suppressed,420642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Shelved,420642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Disabled,420642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Acked,420642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almHighHigh.Alarm,420642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Fault,420652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almHigh.AlarmState,420652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almHigh.GlobalReset,420652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almHigh.FaultInAlarm,420652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almHigh.ALRM,420652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almHigh.ANUN,420652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almHigh.AKED,420652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almHigh.Resetable,420652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almHigh.REST,420652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almHigh.ACKN,420652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almHigh.UACK,420652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almHigh.MCmd_Enable,420652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almHigh.MCmd_Disable,420652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almHigh.OCmd_Shelve,420652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almHigh.OCmd_Unshelve,420652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almHigh.SCmd_Suppress,420652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almHigh.SCmd_UnSuppress,420653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almHigh.AEShelveTMRDN,420653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almHigh.Bad,420653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almHigh.Suppress,420654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.UnSuppress,420654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Shelve,420654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.UnShelve,420654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Enable,420654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Disable,420654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Ack,420654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Reset,420654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almHigh.Suppressed,420654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almHigh.Shelved,420654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almHigh.Disabled,420654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almHigh.Acked,420654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almHigh.Alarm,420654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Fault,420664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almLow.AlarmState,420664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almLow.GlobalReset,420664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almLow.FaultInAlarm,420664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almLow.ALRM,420664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almLow.ANUN,420664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almLow.AKED,420664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almLow.Resetable,420664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almLow.REST,420664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almLow.ACKN,420664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almLow.UACK,420664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almLow.MCmd_Enable,420664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almLow.MCmd_Disable,420664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almLow.OCmd_Shelve,420664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almLow.OCmd_Unshelve,420664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almLow.SCmd_Suppress,420664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almLow.SCmd_UnSuppress,420665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almLow.AEShelveTMRDN,420665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almLow.Bad,420665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almLow.Suppress,420666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.UnSuppress,420666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Shelve,420666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.UnShelve,420666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Enable,420666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Disable,420666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Ack,420666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Reset,420666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almLow.Suppressed,420666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almLow.Shelved,420666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almLow.Disabled,420666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almLow.Acked,420666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almLow.Alarm,420666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Fault,420676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almLowLow.AlarmState,420676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almLowLow.GlobalReset,420676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almLowLow.FaultInAlarm,420676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almLowLow.ALRM,420676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almLowLow.ANUN,420676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almLowLow.AKED,420676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almLowLow.Resetable,420676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almLowLow.REST,420676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almLowLow.ACKN,420676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almLowLow.UACK,420676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almLowLow.MCmd_Enable,420676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almLowLow.MCmd_Disable,420676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almLowLow.OCmd_Shelve,420676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almLowLow.OCmd_Unshelve,420676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almLowLow.SCmd_Suppress,420676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almLowLow.SCmd_UnSuppress,420677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almLowLow.AEShelveTMRDN,420677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almLowLow.Bad,420677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almLowLow.Suppress,420678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.UnSuppress,420678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Shelve,420678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.UnShelve,420678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Enable,420678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Disable,420678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Ack,420678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Reset,420678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Suppressed,420678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Shelved,420678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Disabled,420678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Acked,420678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almLowLow.Alarm,420678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Fault,420688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almBrokenLoop.AlarmState,420688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almBrokenLoop.GlobalReset,420688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almBrokenLoop.FaultInAlarm,420688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almBrokenLoop.ALRM,420688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almBrokenLoop.ANUN,420688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almBrokenLoop.AKED,420688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almBrokenLoop.Resetable,420688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almBrokenLoop.REST,420688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almBrokenLoop.ACKN,420688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almBrokenLoop.UACK,420688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almBrokenLoop.MCmd_Enable,420688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.MCmd_Disable,420688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.OCmd_Shelve,420688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.OCmd_Unshelve,420688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.SCmd_Suppress,420688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.SCmd_UnSuppress,420689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almBrokenLoop.AEShelveTMRDN,420689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almBrokenLoop.Bad,420689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almBrokenLoop.Suppress,420690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.UnSuppress,420690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Shelve,420690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.UnShelve,420690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Enable,420690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Disable,420690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Ack,420690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Reset,420690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Suppressed,420690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Shelved,420690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Disabled,420690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Acked,420690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.Alarm,420690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Fault,420700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almOverRange.AlarmState,420700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almOverRange.GlobalReset,420700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almOverRange.FaultInAlarm,420700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almOverRange.ALRM,420700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almOverRange.ANUN,420700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almOverRange.AKED,420700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almOverRange.Resetable,420700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almOverRange.REST,420700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almOverRange.ACKN,420700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almOverRange.UACK,420700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almOverRange.MCmd_Enable,420700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almOverRange.MCmd_Disable,420700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almOverRange.OCmd_Shelve,420700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almOverRange.OCmd_Unshelve,420700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almOverRange.SCmd_Suppress,420700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almOverRange.SCmd_UnSuppress,420701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almOverRange.AEShelveTMRDN,420701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almOverRange.Bad,420701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almOverRange.Suppress,420702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.UnSuppress,420702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Shelve,420702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.UnShelve,420702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Enable,420702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Disable,420702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Ack,420702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Reset,420702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Suppressed,420702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Shelved,420702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Disabled,420702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Acked,420702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almOverRange.Alarm,420702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Fault,420712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almUnderRange.AlarmState,420712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almUnderRange.GlobalReset,420712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almUnderRange.FaultInAlarm,420712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almUnderRange.ALRM,420712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almUnderRange.ANUN,420712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almUnderRange.AKED,420712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almUnderRange.Resetable,420712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almUnderRange.REST,420712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almUnderRange.ACKN,420712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almUnderRange.UACK,420712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almUnderRange.MCmd_Enable,420712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.MCmd_Disable,420712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.OCmd_Shelve,420712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.OCmd_Unshelve,420712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.SCmd_Suppress,420712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.SCmd_UnSuppress,420713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almUnderRange.AEShelveTMRDN,420713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almUnderRange.Bad,420713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almUnderRange.Suppress,420714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.UnSuppress,420714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Shelve,420714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.UnShelve,420714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Enable,420714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Disable,420714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Ack,420714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Reset,420714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Suppressed,420714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Shelved,420714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Disabled,420714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Acked,420714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almUnderRange.Alarm,420714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Fault,420724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almRateOfChange.AlarmState,420724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almRateOfChange.GlobalReset,420724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almRateOfChange.FaultInAlarm,420724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almRateOfChange.ALRM,420724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almRateOfChange.ANUN,420724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almRateOfChange.AKED,420724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almRateOfChange.Resetable,420724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almRateOfChange.REST,420724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almRateOfChange.ACKN,420724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almRateOfChange.UACK,420724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almRateOfChange.MCmd_Enable,420724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.MCmd_Disable,420724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.OCmd_Shelve,420724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.OCmd_Unshelve,420724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.SCmd_Suppress,420724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.SCmd_UnSuppress,420725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almRateOfChange.AEShelveTMRDN,420725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almRateOfChange.Bad,420725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almRateOfChange.Suppress,420726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.UnSuppress,420726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Shelve,420726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.UnShelve,420726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Enable,420726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Disable,420726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Ack,420726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Reset,420726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Suppressed,420726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Shelved,420726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Disabled,420726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Acked,420726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almRateOfChange.Alarm,420726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Fault,420736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI1.almPLCFault.AlarmState,420736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI1.almPLCFault.GlobalReset,420736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI1.almPLCFault.FaultInAlarm,420736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI1.almPLCFault.ALRM,420736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI1.almPLCFault.ANUN,420736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI1.almPLCFault.AKED,420736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI1.almPLCFault.Resetable,420736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI1.almPLCFault.REST,420736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI1.almPLCFault.ACKN,420736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI1.almPLCFault.UACK,420736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI1.almPLCFault.MCmd_Enable,420736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.MCmd_Disable,420736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.OCmd_Shelve,420736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.OCmd_Unshelve,420736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.SCmd_Suppress,420736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.SCmd_UnSuppress,420737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI1.almPLCFault.AEShelveTMRDN,420737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI1.almPLCFault.Bad,420737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI1.almPLCFault.Suppress,420738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.UnSuppress,420738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Shelve,420738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.UnShelve,420738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Enable,420738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Disable,420738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Ack,420738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Reset,420738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Suppressed,420738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Shelved,420738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Disabled,420738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Acked,420738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI1.almPLCFault.Alarm,420738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Fault,420840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almHighHigh.AlarmState,420840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almHighHigh.GlobalReset,420840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almHighHigh.FaultInAlarm,420840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almHighHigh.ALRM,420840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almHighHigh.ANUN,420840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almHighHigh.AKED,420840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almHighHigh.Resetable,420840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almHighHigh.REST,420840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almHighHigh.ACKN,420840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almHighHigh.UACK,420840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almHighHigh.MCmd_Enable,420840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.MCmd_Disable,420840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.OCmd_Shelve,420840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.OCmd_Unshelve,420840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.SCmd_Suppress,420840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.SCmd_UnSuppress,420841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almHighHigh.AEShelveTMRDN,420841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almHighHigh.Bad,420841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almHighHigh.Suppress,420842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.UnSuppress,420842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Shelve,420842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.UnShelve,420842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Enable,420842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Disable,420842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Ack,420842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Reset,420842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Suppressed,420842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Shelved,420842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Disabled,420842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Acked,420842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almHighHigh.Alarm,420842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Fault,420852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almHigh.AlarmState,420852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almHigh.GlobalReset,420852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almHigh.FaultInAlarm,420852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almHigh.ALRM,420852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almHigh.ANUN,420852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almHigh.AKED,420852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almHigh.Resetable,420852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almHigh.REST,420852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almHigh.ACKN,420852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almHigh.UACK,420852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almHigh.MCmd_Enable,420852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almHigh.MCmd_Disable,420852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almHigh.OCmd_Shelve,420852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almHigh.OCmd_Unshelve,420852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almHigh.SCmd_Suppress,420852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almHigh.SCmd_UnSuppress,420853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almHigh.AEShelveTMRDN,420853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almHigh.Bad,420853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almHigh.Suppress,420854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.UnSuppress,420854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Shelve,420854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.UnShelve,420854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Enable,420854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Disable,420854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Ack,420854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Reset,420854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almHigh.Suppressed,420854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almHigh.Shelved,420854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almHigh.Disabled,420854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almHigh.Acked,420854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almHigh.Alarm,420854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Fault,420864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almLow.AlarmState,420864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almLow.GlobalReset,420864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almLow.FaultInAlarm,420864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almLow.ALRM,420864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almLow.ANUN,420864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almLow.AKED,420864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almLow.Resetable,420864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almLow.REST,420864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almLow.ACKN,420864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almLow.UACK,420864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almLow.MCmd_Enable,420864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almLow.MCmd_Disable,420864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almLow.OCmd_Shelve,420864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almLow.OCmd_Unshelve,420864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almLow.SCmd_Suppress,420864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almLow.SCmd_UnSuppress,420865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almLow.AEShelveTMRDN,420865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almLow.Bad,420865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almLow.Suppress,420866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.UnSuppress,420866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Shelve,420866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.UnShelve,420866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Enable,420866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Disable,420866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Ack,420866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Reset,420866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almLow.Suppressed,420866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almLow.Shelved,420866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almLow.Disabled,420866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almLow.Acked,420866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almLow.Alarm,420866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Fault,420876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almLowLow.AlarmState,420876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almLowLow.GlobalReset,420876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almLowLow.FaultInAlarm,420876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almLowLow.ALRM,420876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almLowLow.ANUN,420876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almLowLow.AKED,420876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almLowLow.Resetable,420876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almLowLow.REST,420876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almLowLow.ACKN,420876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almLowLow.UACK,420876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almLowLow.MCmd_Enable,420876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almLowLow.MCmd_Disable,420876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almLowLow.OCmd_Shelve,420876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almLowLow.OCmd_Unshelve,420876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almLowLow.SCmd_Suppress,420876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almLowLow.SCmd_UnSuppress,420877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almLowLow.AEShelveTMRDN,420877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almLowLow.Bad,420877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almLowLow.Suppress,420878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.UnSuppress,420878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Shelve,420878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.UnShelve,420878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Enable,420878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Disable,420878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Ack,420878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Reset,420878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Suppressed,420878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Shelved,420878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Disabled,420878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Acked,420878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almLowLow.Alarm,420878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Fault,420888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almBrokenLoop.AlarmState,420888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almBrokenLoop.GlobalReset,420888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almBrokenLoop.FaultInAlarm,420888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almBrokenLoop.ALRM,420888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almBrokenLoop.ANUN,420888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almBrokenLoop.AKED,420888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almBrokenLoop.Resetable,420888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almBrokenLoop.REST,420888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almBrokenLoop.ACKN,420888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almBrokenLoop.UACK,420888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almBrokenLoop.MCmd_Enable,420888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.MCmd_Disable,420888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.OCmd_Shelve,420888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.OCmd_Unshelve,420888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.SCmd_Suppress,420888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.SCmd_UnSuppress,420889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almBrokenLoop.AEShelveTMRDN,420889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almBrokenLoop.Bad,420889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almBrokenLoop.Suppress,420890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.UnSuppress,420890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Shelve,420890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.UnShelve,420890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Enable,420890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Disable,420890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Ack,420890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Reset,420890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Suppressed,420890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Shelved,420890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Disabled,420890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Acked,420890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.Alarm,420890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Fault,420900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almOverRange.AlarmState,420900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almOverRange.GlobalReset,420900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almOverRange.FaultInAlarm,420900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almOverRange.ALRM,420900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almOverRange.ANUN,420900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almOverRange.AKED,420900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almOverRange.Resetable,420900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almOverRange.REST,420900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almOverRange.ACKN,420900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almOverRange.UACK,420900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almOverRange.MCmd_Enable,420900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almOverRange.MCmd_Disable,420900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almOverRange.OCmd_Shelve,420900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almOverRange.OCmd_Unshelve,420900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almOverRange.SCmd_Suppress,420900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almOverRange.SCmd_UnSuppress,420901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almOverRange.AEShelveTMRDN,420901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almOverRange.Bad,420901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almOverRange.Suppress,420902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.UnSuppress,420902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Shelve,420902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.UnShelve,420902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Enable,420902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Disable,420902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Ack,420902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Reset,420902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Suppressed,420902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Shelved,420902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Disabled,420902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Acked,420902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almOverRange.Alarm,420902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Fault,420912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almUnderRange.AlarmState,420912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almUnderRange.GlobalReset,420912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almUnderRange.FaultInAlarm,420912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almUnderRange.ALRM,420912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almUnderRange.ANUN,420912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almUnderRange.AKED,420912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almUnderRange.Resetable,420912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almUnderRange.REST,420912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almUnderRange.ACKN,420912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almUnderRange.UACK,420912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almUnderRange.MCmd_Enable,420912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.MCmd_Disable,420912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.OCmd_Shelve,420912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.OCmd_Unshelve,420912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.SCmd_Suppress,420912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.SCmd_UnSuppress,420913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almUnderRange.AEShelveTMRDN,420913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almUnderRange.Bad,420913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almUnderRange.Suppress,420914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.UnSuppress,420914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Shelve,420914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.UnShelve,420914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Enable,420914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Disable,420914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Ack,420914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Reset,420914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Suppressed,420914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Shelved,420914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Disabled,420914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Acked,420914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almUnderRange.Alarm,420914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Fault,420924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almRateOfChange.AlarmState,420924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almRateOfChange.GlobalReset,420924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almRateOfChange.FaultInAlarm,420924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almRateOfChange.ALRM,420924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almRateOfChange.ANUN,420924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almRateOfChange.AKED,420924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almRateOfChange.Resetable,420924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almRateOfChange.REST,420924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almRateOfChange.ACKN,420924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almRateOfChange.UACK,420924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almRateOfChange.MCmd_Enable,420924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.MCmd_Disable,420924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.OCmd_Shelve,420924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.OCmd_Unshelve,420924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.SCmd_Suppress,420924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.SCmd_UnSuppress,420925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almRateOfChange.AEShelveTMRDN,420925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almRateOfChange.Bad,420925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almRateOfChange.Suppress,420926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.UnSuppress,420926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Shelve,420926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.UnShelve,420926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Enable,420926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Disable,420926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Ack,420926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Reset,420926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Suppressed,420926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Shelved,420926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Disabled,420926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Acked,420926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almRateOfChange.Alarm,420926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Fault,420936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI2.almPLCFault.AlarmState,420936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI2.almPLCFault.GlobalReset,420936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI2.almPLCFault.FaultInAlarm,420936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI2.almPLCFault.ALRM,420936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI2.almPLCFault.ANUN,420936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI2.almPLCFault.AKED,420936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI2.almPLCFault.Resetable,420936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI2.almPLCFault.REST,420936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI2.almPLCFault.ACKN,420936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI2.almPLCFault.UACK,420936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI2.almPLCFault.MCmd_Enable,420936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.MCmd_Disable,420936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.OCmd_Shelve,420936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.OCmd_Unshelve,420936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.SCmd_Suppress,420936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.SCmd_UnSuppress,420937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI2.almPLCFault.AEShelveTMRDN,420937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI2.almPLCFault.Bad,420937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI2.almPLCFault.Suppress,420938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.UnSuppress,420938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Shelve,420938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.UnShelve,420938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Enable,420938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Disable,420938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Ack,420938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Reset,420938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Suppressed,420938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Shelved,420938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Disabled,420938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Acked,420938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI2.almPLCFault.Alarm,420938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Fault,421040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almHighHigh.AlarmState,421040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almHighHigh.GlobalReset,421040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almHighHigh.FaultInAlarm,421040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almHighHigh.ALRM,421040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almHighHigh.ANUN,421040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almHighHigh.AKED,421040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almHighHigh.Resetable,421040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almHighHigh.REST,421040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almHighHigh.ACKN,421040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almHighHigh.UACK,421040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almHighHigh.MCmd_Enable,421040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.MCmd_Disable,421040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.OCmd_Shelve,421040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.OCmd_Unshelve,421040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.SCmd_Suppress,421040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.SCmd_UnSuppress,421041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almHighHigh.AEShelveTMRDN,421041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almHighHigh.Bad,421041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almHighHigh.Suppress,421042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.UnSuppress,421042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Shelve,421042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.UnShelve,421042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Enable,421042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Disable,421042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Ack,421042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Reset,421042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Suppressed,421042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Shelved,421042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Disabled,421042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Acked,421042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almHighHigh.Alarm,421042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Fault,421052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almHigh.AlarmState,421052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almHigh.GlobalReset,421052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almHigh.FaultInAlarm,421052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almHigh.ALRM,421052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almHigh.ANUN,421052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almHigh.AKED,421052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almHigh.Resetable,421052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almHigh.REST,421052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almHigh.ACKN,421052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almHigh.UACK,421052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almHigh.MCmd_Enable,421052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almHigh.MCmd_Disable,421052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almHigh.OCmd_Shelve,421052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almHigh.OCmd_Unshelve,421052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almHigh.SCmd_Suppress,421052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almHigh.SCmd_UnSuppress,421053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almHigh.AEShelveTMRDN,421053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almHigh.Bad,421053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almHigh.Suppress,421054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.UnSuppress,421054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Shelve,421054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.UnShelve,421054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Enable,421054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Disable,421054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Ack,421054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Reset,421054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almHigh.Suppressed,421054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almHigh.Shelved,421054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almHigh.Disabled,421054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almHigh.Acked,421054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almHigh.Alarm,421054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Fault,421064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almLow.AlarmState,421064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almLow.GlobalReset,421064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almLow.FaultInAlarm,421064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almLow.ALRM,421064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almLow.ANUN,421064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almLow.AKED,421064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almLow.Resetable,421064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almLow.REST,421064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almLow.ACKN,421064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almLow.UACK,421064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almLow.MCmd_Enable,421064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almLow.MCmd_Disable,421064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almLow.OCmd_Shelve,421064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almLow.OCmd_Unshelve,421064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almLow.SCmd_Suppress,421064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almLow.SCmd_UnSuppress,421065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almLow.AEShelveTMRDN,421065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almLow.Bad,421065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almLow.Suppress,421066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.UnSuppress,421066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Shelve,421066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.UnShelve,421066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Enable,421066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Disable,421066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Ack,421066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Reset,421066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almLow.Suppressed,421066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almLow.Shelved,421066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almLow.Disabled,421066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almLow.Acked,421066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almLow.Alarm,421066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Fault,421076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almLowLow.AlarmState,421076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almLowLow.GlobalReset,421076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almLowLow.FaultInAlarm,421076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almLowLow.ALRM,421076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almLowLow.ANUN,421076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almLowLow.AKED,421076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almLowLow.Resetable,421076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almLowLow.REST,421076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almLowLow.ACKN,421076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almLowLow.UACK,421076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almLowLow.MCmd_Enable,421076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almLowLow.MCmd_Disable,421076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almLowLow.OCmd_Shelve,421076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almLowLow.OCmd_Unshelve,421076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almLowLow.SCmd_Suppress,421076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almLowLow.SCmd_UnSuppress,421077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almLowLow.AEShelveTMRDN,421077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almLowLow.Bad,421077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almLowLow.Suppress,421078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.UnSuppress,421078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Shelve,421078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.UnShelve,421078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Enable,421078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Disable,421078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Ack,421078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Reset,421078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Suppressed,421078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Shelved,421078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Disabled,421078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Acked,421078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almLowLow.Alarm,421078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Fault,421088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almBrokenLoop.AlarmState,421088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almBrokenLoop.GlobalReset,421088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almBrokenLoop.FaultInAlarm,421088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almBrokenLoop.ALRM,421088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almBrokenLoop.ANUN,421088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almBrokenLoop.AKED,421088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almBrokenLoop.Resetable,421088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almBrokenLoop.REST,421088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almBrokenLoop.ACKN,421088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almBrokenLoop.UACK,421088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almBrokenLoop.MCmd_Enable,421088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.MCmd_Disable,421088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.OCmd_Shelve,421088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.OCmd_Unshelve,421088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.SCmd_Suppress,421088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.SCmd_UnSuppress,421089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almBrokenLoop.AEShelveTMRDN,421089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almBrokenLoop.Bad,421089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almBrokenLoop.Suppress,421090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.UnSuppress,421090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Shelve,421090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.UnShelve,421090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Enable,421090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Disable,421090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Ack,421090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Reset,421090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Suppressed,421090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Shelved,421090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Disabled,421090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Acked,421090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.Alarm,421090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Fault,421100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almOverRange.AlarmState,421100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almOverRange.GlobalReset,421100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almOverRange.FaultInAlarm,421100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almOverRange.ALRM,421100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almOverRange.ANUN,421100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almOverRange.AKED,421100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almOverRange.Resetable,421100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almOverRange.REST,421100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almOverRange.ACKN,421100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almOverRange.UACK,421100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almOverRange.MCmd_Enable,421100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almOverRange.MCmd_Disable,421100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almOverRange.OCmd_Shelve,421100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almOverRange.OCmd_Unshelve,421100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almOverRange.SCmd_Suppress,421100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almOverRange.SCmd_UnSuppress,421101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almOverRange.AEShelveTMRDN,421101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almOverRange.Bad,421101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almOverRange.Suppress,421102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.UnSuppress,421102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Shelve,421102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.UnShelve,421102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Enable,421102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Disable,421102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Ack,421102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Reset,421102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Suppressed,421102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Shelved,421102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Disabled,421102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Acked,421102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almOverRange.Alarm,421102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Fault,421112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almUnderRange.AlarmState,421112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almUnderRange.GlobalReset,421112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almUnderRange.FaultInAlarm,421112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almUnderRange.ALRM,421112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almUnderRange.ANUN,421112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almUnderRange.AKED,421112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almUnderRange.Resetable,421112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almUnderRange.REST,421112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almUnderRange.ACKN,421112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almUnderRange.UACK,421112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almUnderRange.MCmd_Enable,421112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.MCmd_Disable,421112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.OCmd_Shelve,421112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.OCmd_Unshelve,421112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.SCmd_Suppress,421112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.SCmd_UnSuppress,421113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almUnderRange.AEShelveTMRDN,421113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almUnderRange.Bad,421113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almUnderRange.Suppress,421114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.UnSuppress,421114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Shelve,421114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.UnShelve,421114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Enable,421114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Disable,421114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Ack,421114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Reset,421114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Suppressed,421114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Shelved,421114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Disabled,421114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Acked,421114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almUnderRange.Alarm,421114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Fault,421124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almRateOfChange.AlarmState,421124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almRateOfChange.GlobalReset,421124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almRateOfChange.FaultInAlarm,421124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almRateOfChange.ALRM,421124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almRateOfChange.ANUN,421124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almRateOfChange.AKED,421124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almRateOfChange.Resetable,421124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almRateOfChange.REST,421124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almRateOfChange.ACKN,421124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almRateOfChange.UACK,421124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almRateOfChange.MCmd_Enable,421124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.MCmd_Disable,421124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.OCmd_Shelve,421124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.OCmd_Unshelve,421124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.SCmd_Suppress,421124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.SCmd_UnSuppress,421125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almRateOfChange.AEShelveTMRDN,421125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almRateOfChange.Bad,421125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almRateOfChange.Suppress,421126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.UnSuppress,421126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Shelve,421126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.UnShelve,421126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Enable,421126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Disable,421126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Ack,421126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Reset,421126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Suppressed,421126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Shelved,421126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Disabled,421126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Acked,421126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almRateOfChange.Alarm,421126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Fault,421136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI3.almPLCFault.AlarmState,421136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI3.almPLCFault.GlobalReset,421136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI3.almPLCFault.FaultInAlarm,421136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI3.almPLCFault.ALRM,421136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI3.almPLCFault.ANUN,421136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI3.almPLCFault.AKED,421136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI3.almPLCFault.Resetable,421136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI3.almPLCFault.REST,421136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI3.almPLCFault.ACKN,421136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI3.almPLCFault.UACK,421136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI3.almPLCFault.MCmd_Enable,421136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.MCmd_Disable,421136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.OCmd_Shelve,421136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.OCmd_Unshelve,421136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.SCmd_Suppress,421136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.SCmd_UnSuppress,421137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI3.almPLCFault.AEShelveTMRDN,421137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI3.almPLCFault.Bad,421137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI3.almPLCFault.Suppress,421138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.UnSuppress,421138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Shelve,421138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.UnShelve,421138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Enable,421138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Disable,421138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Ack,421138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Reset,421138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Suppressed,421138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Shelved,421138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Disabled,421138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Acked,421138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI3.almPLCFault.Alarm,421138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Fault,421240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almHighHigh.AlarmState,421240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almHighHigh.GlobalReset,421240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almHighHigh.FaultInAlarm,421240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almHighHigh.ALRM,421240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almHighHigh.ANUN,421240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almHighHigh.AKED,421240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almHighHigh.Resetable,421240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almHighHigh.REST,421240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almHighHigh.ACKN,421240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almHighHigh.UACK,421240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almHighHigh.MCmd_Enable,421240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.MCmd_Disable,421240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.OCmd_Shelve,421240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.OCmd_Unshelve,421240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.SCmd_Suppress,421240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.SCmd_UnSuppress,421241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almHighHigh.AEShelveTMRDN,421241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almHighHigh.Bad,421241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almHighHigh.Suppress,421242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.UnSuppress,421242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Shelve,421242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.UnShelve,421242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Enable,421242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Disable,421242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Ack,421242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Reset,421242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Suppressed,421242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Shelved,421242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Disabled,421242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Acked,421242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almHighHigh.Alarm,421242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Fault,421252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almHigh.AlarmState,421252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almHigh.GlobalReset,421252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almHigh.FaultInAlarm,421252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almHigh.ALRM,421252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almHigh.ANUN,421252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almHigh.AKED,421252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almHigh.Resetable,421252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almHigh.REST,421252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almHigh.ACKN,421252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almHigh.UACK,421252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almHigh.MCmd_Enable,421252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almHigh.MCmd_Disable,421252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almHigh.OCmd_Shelve,421252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almHigh.OCmd_Unshelve,421252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almHigh.SCmd_Suppress,421252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almHigh.SCmd_UnSuppress,421253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almHigh.AEShelveTMRDN,421253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almHigh.Bad,421253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almHigh.Suppress,421254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.UnSuppress,421254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Shelve,421254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.UnShelve,421254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Enable,421254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Disable,421254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Ack,421254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Reset,421254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almHigh.Suppressed,421254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almHigh.Shelved,421254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almHigh.Disabled,421254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almHigh.Acked,421254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almHigh.Alarm,421254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Fault,421264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almLow.AlarmState,421264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almLow.GlobalReset,421264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almLow.FaultInAlarm,421264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almLow.ALRM,421264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almLow.ANUN,421264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almLow.AKED,421264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almLow.Resetable,421264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almLow.REST,421264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almLow.ACKN,421264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almLow.UACK,421264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almLow.MCmd_Enable,421264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almLow.MCmd_Disable,421264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almLow.OCmd_Shelve,421264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almLow.OCmd_Unshelve,421264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almLow.SCmd_Suppress,421264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almLow.SCmd_UnSuppress,421265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almLow.AEShelveTMRDN,421265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almLow.Bad,421265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almLow.Suppress,421266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.UnSuppress,421266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Shelve,421266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.UnShelve,421266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Enable,421266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Disable,421266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Ack,421266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Reset,421266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almLow.Suppressed,421266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almLow.Shelved,421266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almLow.Disabled,421266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almLow.Acked,421266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almLow.Alarm,421266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Fault,421276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almLowLow.AlarmState,421276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almLowLow.GlobalReset,421276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almLowLow.FaultInAlarm,421276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almLowLow.ALRM,421276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almLowLow.ANUN,421276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almLowLow.AKED,421276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almLowLow.Resetable,421276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almLowLow.REST,421276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almLowLow.ACKN,421276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almLowLow.UACK,421276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almLowLow.MCmd_Enable,421276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almLowLow.MCmd_Disable,421276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almLowLow.OCmd_Shelve,421276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almLowLow.OCmd_Unshelve,421276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almLowLow.SCmd_Suppress,421276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almLowLow.SCmd_UnSuppress,421277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almLowLow.AEShelveTMRDN,421277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almLowLow.Bad,421277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almLowLow.Suppress,421278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.UnSuppress,421278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Shelve,421278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.UnShelve,421278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Enable,421278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Disable,421278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Ack,421278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Reset,421278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Suppressed,421278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Shelved,421278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Disabled,421278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Acked,421278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almLowLow.Alarm,421278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Fault,421288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almBrokenLoop.AlarmState,421288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almBrokenLoop.GlobalReset,421288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almBrokenLoop.FaultInAlarm,421288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almBrokenLoop.ALRM,421288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almBrokenLoop.ANUN,421288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almBrokenLoop.AKED,421288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almBrokenLoop.Resetable,421288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almBrokenLoop.REST,421288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almBrokenLoop.ACKN,421288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almBrokenLoop.UACK,421288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almBrokenLoop.MCmd_Enable,421288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.MCmd_Disable,421288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.OCmd_Shelve,421288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.OCmd_Unshelve,421288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.SCmd_Suppress,421288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.SCmd_UnSuppress,421289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almBrokenLoop.AEShelveTMRDN,421289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almBrokenLoop.Bad,421289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almBrokenLoop.Suppress,421290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.UnSuppress,421290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Shelve,421290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.UnShelve,421290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Enable,421290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Disable,421290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Ack,421290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Reset,421290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Suppressed,421290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Shelved,421290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Disabled,421290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Acked,421290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.Alarm,421290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Fault,421300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almOverRange.AlarmState,421300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almOverRange.GlobalReset,421300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almOverRange.FaultInAlarm,421300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almOverRange.ALRM,421300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almOverRange.ANUN,421300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almOverRange.AKED,421300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almOverRange.Resetable,421300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almOverRange.REST,421300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almOverRange.ACKN,421300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almOverRange.UACK,421300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almOverRange.MCmd_Enable,421300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almOverRange.MCmd_Disable,421300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almOverRange.OCmd_Shelve,421300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almOverRange.OCmd_Unshelve,421300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almOverRange.SCmd_Suppress,421300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almOverRange.SCmd_UnSuppress,421301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almOverRange.AEShelveTMRDN,421301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almOverRange.Bad,421301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almOverRange.Suppress,421302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.UnSuppress,421302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Shelve,421302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.UnShelve,421302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Enable,421302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Disable,421302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Ack,421302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Reset,421302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Suppressed,421302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Shelved,421302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Disabled,421302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Acked,421302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almOverRange.Alarm,421302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Fault,421312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almUnderRange.AlarmState,421312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almUnderRange.GlobalReset,421312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almUnderRange.FaultInAlarm,421312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almUnderRange.ALRM,421312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almUnderRange.ANUN,421312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almUnderRange.AKED,421312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almUnderRange.Resetable,421312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almUnderRange.REST,421312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almUnderRange.ACKN,421312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almUnderRange.UACK,421312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almUnderRange.MCmd_Enable,421312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.MCmd_Disable,421312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.OCmd_Shelve,421312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.OCmd_Unshelve,421312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.SCmd_Suppress,421312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.SCmd_UnSuppress,421313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almUnderRange.AEShelveTMRDN,421313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almUnderRange.Bad,421313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almUnderRange.Suppress,421314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.UnSuppress,421314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Shelve,421314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.UnShelve,421314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Enable,421314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Disable,421314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Ack,421314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Reset,421314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Suppressed,421314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Shelved,421314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Disabled,421314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Acked,421314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almUnderRange.Alarm,421314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Fault,421324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almRateOfChange.AlarmState,421324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almRateOfChange.GlobalReset,421324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almRateOfChange.FaultInAlarm,421324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almRateOfChange.ALRM,421324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almRateOfChange.ANUN,421324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almRateOfChange.AKED,421324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almRateOfChange.Resetable,421324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almRateOfChange.REST,421324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almRateOfChange.ACKN,421324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almRateOfChange.UACK,421324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almRateOfChange.MCmd_Enable,421324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.MCmd_Disable,421324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.OCmd_Shelve,421324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.OCmd_Unshelve,421324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.SCmd_Suppress,421324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.SCmd_UnSuppress,421325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almRateOfChange.AEShelveTMRDN,421325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almRateOfChange.Bad,421325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almRateOfChange.Suppress,421326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.UnSuppress,421326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Shelve,421326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.UnShelve,421326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Enable,421326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Disable,421326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Ack,421326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Reset,421326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Suppressed,421326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Shelved,421326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Disabled,421326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Acked,421326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almRateOfChange.Alarm,421326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Fault,421336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI4.almPLCFault.AlarmState,421336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI4.almPLCFault.GlobalReset,421336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI4.almPLCFault.FaultInAlarm,421336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI4.almPLCFault.ALRM,421336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI4.almPLCFault.ANUN,421336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI4.almPLCFault.AKED,421336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI4.almPLCFault.Resetable,421336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI4.almPLCFault.REST,421336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI4.almPLCFault.ACKN,421336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI4.almPLCFault.UACK,421336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI4.almPLCFault.MCmd_Enable,421336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.MCmd_Disable,421336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.OCmd_Shelve,421336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.OCmd_Unshelve,421336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.SCmd_Suppress,421336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.SCmd_UnSuppress,421337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI4.almPLCFault.AEShelveTMRDN,421337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI4.almPLCFault.Bad,421337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI4.almPLCFault.Suppress,421338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.UnSuppress,421338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Shelve,421338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.UnShelve,421338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Enable,421338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Disable,421338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Ack,421338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Reset,421338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Suppressed,421338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Shelved,421338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Disabled,421338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Acked,421338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI4.almPLCFault.Alarm,421338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Fault,421440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almHighHigh.AlarmState,421440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almHighHigh.GlobalReset,421440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almHighHigh.FaultInAlarm,421440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almHighHigh.ALRM,421440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almHighHigh.ANUN,421440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almHighHigh.AKED,421440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almHighHigh.Resetable,421440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almHighHigh.REST,421440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almHighHigh.ACKN,421440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almHighHigh.UACK,421440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almHighHigh.MCmd_Enable,421440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.MCmd_Disable,421440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.OCmd_Shelve,421440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.OCmd_Unshelve,421440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.SCmd_Suppress,421440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.SCmd_UnSuppress,421441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almHighHigh.AEShelveTMRDN,421441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almHighHigh.Bad,421441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almHighHigh.Suppress,421442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.UnSuppress,421442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Shelve,421442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.UnShelve,421442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Enable,421442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Disable,421442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Ack,421442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Reset,421442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Suppressed,421442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Shelved,421442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Disabled,421442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Acked,421442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almHighHigh.Alarm,421442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Fault,421452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almHigh.AlarmState,421452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almHigh.GlobalReset,421452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almHigh.FaultInAlarm,421452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almHigh.ALRM,421452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almHigh.ANUN,421452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almHigh.AKED,421452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almHigh.Resetable,421452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almHigh.REST,421452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almHigh.ACKN,421452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almHigh.UACK,421452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almHigh.MCmd_Enable,421452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almHigh.MCmd_Disable,421452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almHigh.OCmd_Shelve,421452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almHigh.OCmd_Unshelve,421452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almHigh.SCmd_Suppress,421452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almHigh.SCmd_UnSuppress,421453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almHigh.AEShelveTMRDN,421453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almHigh.Bad,421453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almHigh.Suppress,421454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.UnSuppress,421454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Shelve,421454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.UnShelve,421454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Enable,421454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Disable,421454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Ack,421454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Reset,421454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almHigh.Suppressed,421454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almHigh.Shelved,421454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almHigh.Disabled,421454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almHigh.Acked,421454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almHigh.Alarm,421454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Fault,421464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almLow.AlarmState,421464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almLow.GlobalReset,421464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almLow.FaultInAlarm,421464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almLow.ALRM,421464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almLow.ANUN,421464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almLow.AKED,421464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almLow.Resetable,421464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almLow.REST,421464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almLow.ACKN,421464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almLow.UACK,421464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almLow.MCmd_Enable,421464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almLow.MCmd_Disable,421464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almLow.OCmd_Shelve,421464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almLow.OCmd_Unshelve,421464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almLow.SCmd_Suppress,421464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almLow.SCmd_UnSuppress,421465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almLow.AEShelveTMRDN,421465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almLow.Bad,421465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almLow.Suppress,421466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.UnSuppress,421466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Shelve,421466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.UnShelve,421466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Enable,421466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Disable,421466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Ack,421466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Reset,421466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almLow.Suppressed,421466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almLow.Shelved,421466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almLow.Disabled,421466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almLow.Acked,421466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almLow.Alarm,421466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Fault,421476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almLowLow.AlarmState,421476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almLowLow.GlobalReset,421476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almLowLow.FaultInAlarm,421476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almLowLow.ALRM,421476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almLowLow.ANUN,421476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almLowLow.AKED,421476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almLowLow.Resetable,421476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almLowLow.REST,421476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almLowLow.ACKN,421476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almLowLow.UACK,421476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almLowLow.MCmd_Enable,421476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almLowLow.MCmd_Disable,421476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almLowLow.OCmd_Shelve,421476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almLowLow.OCmd_Unshelve,421476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almLowLow.SCmd_Suppress,421476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almLowLow.SCmd_UnSuppress,421477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almLowLow.AEShelveTMRDN,421477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almLowLow.Bad,421477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almLowLow.Suppress,421478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.UnSuppress,421478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Shelve,421478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.UnShelve,421478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Enable,421478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Disable,421478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Ack,421478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Reset,421478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Suppressed,421478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Shelved,421478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Disabled,421478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Acked,421478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almLowLow.Alarm,421478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Fault,421488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almBrokenLoop.AlarmState,421488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almBrokenLoop.GlobalReset,421488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almBrokenLoop.FaultInAlarm,421488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almBrokenLoop.ALRM,421488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almBrokenLoop.ANUN,421488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almBrokenLoop.AKED,421488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almBrokenLoop.Resetable,421488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almBrokenLoop.REST,421488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almBrokenLoop.ACKN,421488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almBrokenLoop.UACK,421488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almBrokenLoop.MCmd_Enable,421488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.MCmd_Disable,421488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.OCmd_Shelve,421488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.OCmd_Unshelve,421488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.SCmd_Suppress,421488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.SCmd_UnSuppress,421489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almBrokenLoop.AEShelveTMRDN,421489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almBrokenLoop.Bad,421489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almBrokenLoop.Suppress,421490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.UnSuppress,421490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Shelve,421490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.UnShelve,421490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Enable,421490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Disable,421490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Ack,421490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Reset,421490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Suppressed,421490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Shelved,421490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Disabled,421490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Acked,421490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.Alarm,421490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Fault,421500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almOverRange.AlarmState,421500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almOverRange.GlobalReset,421500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almOverRange.FaultInAlarm,421500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almOverRange.ALRM,421500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almOverRange.ANUN,421500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almOverRange.AKED,421500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almOverRange.Resetable,421500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almOverRange.REST,421500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almOverRange.ACKN,421500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almOverRange.UACK,421500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almOverRange.MCmd_Enable,421500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almOverRange.MCmd_Disable,421500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almOverRange.OCmd_Shelve,421500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almOverRange.OCmd_Unshelve,421500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almOverRange.SCmd_Suppress,421500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almOverRange.SCmd_UnSuppress,421501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almOverRange.AEShelveTMRDN,421501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almOverRange.Bad,421501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almOverRange.Suppress,421502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.UnSuppress,421502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Shelve,421502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.UnShelve,421502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Enable,421502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Disable,421502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Ack,421502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Reset,421502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Suppressed,421502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Shelved,421502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Disabled,421502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Acked,421502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almOverRange.Alarm,421502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Fault,421512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almUnderRange.AlarmState,421512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almUnderRange.GlobalReset,421512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almUnderRange.FaultInAlarm,421512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almUnderRange.ALRM,421512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almUnderRange.ANUN,421512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almUnderRange.AKED,421512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almUnderRange.Resetable,421512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almUnderRange.REST,421512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almUnderRange.ACKN,421512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almUnderRange.UACK,421512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almUnderRange.MCmd_Enable,421512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.MCmd_Disable,421512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.OCmd_Shelve,421512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.OCmd_Unshelve,421512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.SCmd_Suppress,421512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.SCmd_UnSuppress,421513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almUnderRange.AEShelveTMRDN,421513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almUnderRange.Bad,421513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almUnderRange.Suppress,421514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.UnSuppress,421514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Shelve,421514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.UnShelve,421514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Enable,421514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Disable,421514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Ack,421514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Reset,421514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Suppressed,421514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Shelved,421514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Disabled,421514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Acked,421514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almUnderRange.Alarm,421514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Fault,421524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almRateOfChange.AlarmState,421524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almRateOfChange.GlobalReset,421524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almRateOfChange.FaultInAlarm,421524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almRateOfChange.ALRM,421524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almRateOfChange.ANUN,421524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almRateOfChange.AKED,421524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almRateOfChange.Resetable,421524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almRateOfChange.REST,421524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almRateOfChange.ACKN,421524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almRateOfChange.UACK,421524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almRateOfChange.MCmd_Enable,421524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.MCmd_Disable,421524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.OCmd_Shelve,421524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.OCmd_Unshelve,421524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.SCmd_Suppress,421524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.SCmd_UnSuppress,421525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almRateOfChange.AEShelveTMRDN,421525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almRateOfChange.Bad,421525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almRateOfChange.Suppress,421526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.UnSuppress,421526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Shelve,421526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.UnShelve,421526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Enable,421526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Disable,421526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Ack,421526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Reset,421526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Suppressed,421526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Shelved,421526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Disabled,421526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Acked,421526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almRateOfChange.Alarm,421526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Fault,421536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_5_VI5.almPLCFault.AlarmState,421536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_5_VI5.almPLCFault.GlobalReset,421536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_5_VI5.almPLCFault.FaultInAlarm,421536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_5_VI5.almPLCFault.ALRM,421536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_5_VI5.almPLCFault.ANUN,421536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_5_VI5.almPLCFault.AKED,421536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_5_VI5.almPLCFault.Resetable,421536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_5_VI5.almPLCFault.REST,421536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_5_VI5.almPLCFault.ACKN,421536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_5_VI5.almPLCFault.UACK,421536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_5_VI5.almPLCFault.MCmd_Enable,421536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.MCmd_Disable,421536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.OCmd_Shelve,421536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.OCmd_Unshelve,421536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.SCmd_Suppress,421536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.SCmd_UnSuppress,421537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_5_VI5.almPLCFault.AEShelveTMRDN,421537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_5_VI5.almPLCFault.Bad,421537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_5_VI5.almPLCFault.Suppress,421538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.UnSuppress,421538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Shelve,421538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.UnShelve,421538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Enable,421538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Disable,421538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Ack,421538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Reset,421538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Suppressed,421538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Shelved,421538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Disabled,421538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Acked,421538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_5_VI5.almPLCFault.Alarm,421538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Fault,421640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almHighHigh.AlarmState,421640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almHighHigh.GlobalReset,421640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almHighHigh.FaultInAlarm,421640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almHighHigh.ALRM,421640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almHighHigh.ANUN,421640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almHighHigh.AKED,421640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almHighHigh.Resetable,421640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almHighHigh.REST,421640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almHighHigh.ACKN,421640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almHighHigh.UACK,421640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almHighHigh.MCmd_Enable,421640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.MCmd_Disable,421640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.OCmd_Shelve,421640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.OCmd_Unshelve,421640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.SCmd_Suppress,421640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.SCmd_UnSuppress,421641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almHighHigh.AEShelveTMRDN,421641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almHighHigh.Bad,421641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almHighHigh.Suppress,421642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.UnSuppress,421642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Shelve,421642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.UnShelve,421642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Enable,421642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Disable,421642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Ack,421642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Reset,421642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Suppressed,421642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Shelved,421642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Disabled,421642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Acked,421642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almHighHigh.Alarm,421642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Fault,421652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almHigh.AlarmState,421652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almHigh.GlobalReset,421652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almHigh.FaultInAlarm,421652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almHigh.ALRM,421652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almHigh.ANUN,421652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almHigh.AKED,421652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almHigh.Resetable,421652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almHigh.REST,421652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almHigh.ACKN,421652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almHigh.UACK,421652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almHigh.MCmd_Enable,421652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almHigh.MCmd_Disable,421652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almHigh.OCmd_Shelve,421652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almHigh.OCmd_Unshelve,421652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almHigh.SCmd_Suppress,421652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almHigh.SCmd_UnSuppress,421653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almHigh.AEShelveTMRDN,421653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almHigh.Bad,421653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almHigh.Suppress,421654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.UnSuppress,421654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Shelve,421654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.UnShelve,421654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Enable,421654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Disable,421654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Ack,421654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Reset,421654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almHigh.Suppressed,421654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almHigh.Shelved,421654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almHigh.Disabled,421654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almHigh.Acked,421654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almHigh.Alarm,421654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Fault,421664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almLow.AlarmState,421664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almLow.GlobalReset,421664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almLow.FaultInAlarm,421664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almLow.ALRM,421664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almLow.ANUN,421664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almLow.AKED,421664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almLow.Resetable,421664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almLow.REST,421664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almLow.ACKN,421664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almLow.UACK,421664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almLow.MCmd_Enable,421664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almLow.MCmd_Disable,421664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almLow.OCmd_Shelve,421664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almLow.OCmd_Unshelve,421664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almLow.SCmd_Suppress,421664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almLow.SCmd_UnSuppress,421665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almLow.AEShelveTMRDN,421665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almLow.Bad,421665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almLow.Suppress,421666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.UnSuppress,421666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Shelve,421666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.UnShelve,421666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Enable,421666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Disable,421666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Ack,421666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Reset,421666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almLow.Suppressed,421666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almLow.Shelved,421666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almLow.Disabled,421666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almLow.Acked,421666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almLow.Alarm,421666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Fault,421676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almLowLow.AlarmState,421676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almLowLow.GlobalReset,421676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almLowLow.FaultInAlarm,421676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almLowLow.ALRM,421676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almLowLow.ANUN,421676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almLowLow.AKED,421676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almLowLow.Resetable,421676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almLowLow.REST,421676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almLowLow.ACKN,421676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almLowLow.UACK,421676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almLowLow.MCmd_Enable,421676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almLowLow.MCmd_Disable,421676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almLowLow.OCmd_Shelve,421676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almLowLow.OCmd_Unshelve,421676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almLowLow.SCmd_Suppress,421676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almLowLow.SCmd_UnSuppress,421677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almLowLow.AEShelveTMRDN,421677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almLowLow.Bad,421677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almLowLow.Suppress,421678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.UnSuppress,421678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Shelve,421678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.UnShelve,421678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Enable,421678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Disable,421678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Ack,421678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Reset,421678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Suppressed,421678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Shelved,421678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Disabled,421678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Acked,421678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almLowLow.Alarm,421678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Fault,421688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almBrokenLoop.AlarmState,421688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almBrokenLoop.GlobalReset,421688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almBrokenLoop.FaultInAlarm,421688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almBrokenLoop.ALRM,421688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almBrokenLoop.ANUN,421688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almBrokenLoop.AKED,421688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almBrokenLoop.Resetable,421688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almBrokenLoop.REST,421688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almBrokenLoop.ACKN,421688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almBrokenLoop.UACK,421688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almBrokenLoop.MCmd_Enable,421688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.MCmd_Disable,421688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.OCmd_Shelve,421688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.OCmd_Unshelve,421688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.SCmd_Suppress,421688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.SCmd_UnSuppress,421689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almBrokenLoop.AEShelveTMRDN,421689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almBrokenLoop.Bad,421689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almBrokenLoop.Suppress,421690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.UnSuppress,421690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Shelve,421690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.UnShelve,421690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Enable,421690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Disable,421690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Ack,421690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Reset,421690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Suppressed,421690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Shelved,421690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Disabled,421690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Acked,421690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.Alarm,421690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Fault,421700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almOverRange.AlarmState,421700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almOverRange.GlobalReset,421700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almOverRange.FaultInAlarm,421700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almOverRange.ALRM,421700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almOverRange.ANUN,421700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almOverRange.AKED,421700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almOverRange.Resetable,421700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almOverRange.REST,421700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almOverRange.ACKN,421700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almOverRange.UACK,421700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almOverRange.MCmd_Enable,421700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almOverRange.MCmd_Disable,421700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almOverRange.OCmd_Shelve,421700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almOverRange.OCmd_Unshelve,421700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almOverRange.SCmd_Suppress,421700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almOverRange.SCmd_UnSuppress,421701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almOverRange.AEShelveTMRDN,421701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almOverRange.Bad,421701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almOverRange.Suppress,421702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.UnSuppress,421702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Shelve,421702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.UnShelve,421702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Enable,421702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Disable,421702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Ack,421702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Reset,421702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Suppressed,421702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Shelved,421702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Disabled,421702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Acked,421702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almOverRange.Alarm,421702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Fault,421712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almUnderRange.AlarmState,421712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almUnderRange.GlobalReset,421712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almUnderRange.FaultInAlarm,421712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almUnderRange.ALRM,421712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almUnderRange.ANUN,421712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almUnderRange.AKED,421712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almUnderRange.Resetable,421712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almUnderRange.REST,421712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almUnderRange.ACKN,421712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almUnderRange.UACK,421712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almUnderRange.MCmd_Enable,421712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.MCmd_Disable,421712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.OCmd_Shelve,421712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.OCmd_Unshelve,421712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.SCmd_Suppress,421712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.SCmd_UnSuppress,421713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almUnderRange.AEShelveTMRDN,421713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almUnderRange.Bad,421713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almUnderRange.Suppress,421714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.UnSuppress,421714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Shelve,421714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.UnShelve,421714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Enable,421714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Disable,421714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Ack,421714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Reset,421714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Suppressed,421714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Shelved,421714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Disabled,421714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Acked,421714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almUnderRange.Alarm,421714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Fault,421724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almRateOfChange.AlarmState,421724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almRateOfChange.GlobalReset,421724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almRateOfChange.FaultInAlarm,421724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almRateOfChange.ALRM,421724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almRateOfChange.ANUN,421724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almRateOfChange.AKED,421724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almRateOfChange.Resetable,421724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almRateOfChange.REST,421724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almRateOfChange.ACKN,421724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almRateOfChange.UACK,421724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almRateOfChange.MCmd_Enable,421724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.MCmd_Disable,421724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.OCmd_Shelve,421724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.OCmd_Unshelve,421724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.SCmd_Suppress,421724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.SCmd_UnSuppress,421725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almRateOfChange.AEShelveTMRDN,421725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almRateOfChange.Bad,421725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almRateOfChange.Suppress,421726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.UnSuppress,421726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Shelve,421726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.UnShelve,421726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Enable,421726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Disable,421726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Ack,421726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Reset,421726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Suppressed,421726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Shelved,421726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Disabled,421726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Acked,421726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almRateOfChange.Alarm,421726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Fault,421736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI1.almPLCFault.AlarmState,421736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI1.almPLCFault.GlobalReset,421736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI1.almPLCFault.FaultInAlarm,421736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI1.almPLCFault.ALRM,421736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI1.almPLCFault.ANUN,421736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI1.almPLCFault.AKED,421736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI1.almPLCFault.Resetable,421736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI1.almPLCFault.REST,421736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI1.almPLCFault.ACKN,421736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI1.almPLCFault.UACK,421736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI1.almPLCFault.MCmd_Enable,421736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.MCmd_Disable,421736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.OCmd_Shelve,421736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.OCmd_Unshelve,421736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.SCmd_Suppress,421736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.SCmd_UnSuppress,421737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI1.almPLCFault.AEShelveTMRDN,421737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI1.almPLCFault.Bad,421737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI1.almPLCFault.Suppress,421738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.UnSuppress,421738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Shelve,421738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.UnShelve,421738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Enable,421738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Disable,421738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Ack,421738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Reset,421738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Suppressed,421738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Shelved,421738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Disabled,421738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Acked,421738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI1.almPLCFault.Alarm,421738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Fault,421840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almHighHigh.AlarmState,421840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almHighHigh.GlobalReset,421840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almHighHigh.FaultInAlarm,421840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almHighHigh.ALRM,421840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almHighHigh.ANUN,421840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almHighHigh.AKED,421840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almHighHigh.Resetable,421840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almHighHigh.REST,421840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almHighHigh.ACKN,421840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almHighHigh.UACK,421840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almHighHigh.MCmd_Enable,421840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.MCmd_Disable,421840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.OCmd_Shelve,421840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.OCmd_Unshelve,421840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.SCmd_Suppress,421840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.SCmd_UnSuppress,421841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almHighHigh.AEShelveTMRDN,421841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almHighHigh.Bad,421841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almHighHigh.Suppress,421842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.UnSuppress,421842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Shelve,421842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.UnShelve,421842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Enable,421842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Disable,421842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Ack,421842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Reset,421842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Suppressed,421842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Shelved,421842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Disabled,421842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Acked,421842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almHighHigh.Alarm,421842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Fault,421852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almHigh.AlarmState,421852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almHigh.GlobalReset,421852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almHigh.FaultInAlarm,421852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almHigh.ALRM,421852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almHigh.ANUN,421852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almHigh.AKED,421852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almHigh.Resetable,421852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almHigh.REST,421852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almHigh.ACKN,421852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almHigh.UACK,421852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almHigh.MCmd_Enable,421852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almHigh.MCmd_Disable,421852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almHigh.OCmd_Shelve,421852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almHigh.OCmd_Unshelve,421852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almHigh.SCmd_Suppress,421852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almHigh.SCmd_UnSuppress,421853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almHigh.AEShelveTMRDN,421853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almHigh.Bad,421853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almHigh.Suppress,421854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.UnSuppress,421854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Shelve,421854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.UnShelve,421854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Enable,421854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Disable,421854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Ack,421854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Reset,421854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almHigh.Suppressed,421854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almHigh.Shelved,421854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almHigh.Disabled,421854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almHigh.Acked,421854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almHigh.Alarm,421854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Fault,421864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almLow.AlarmState,421864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almLow.GlobalReset,421864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almLow.FaultInAlarm,421864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almLow.ALRM,421864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almLow.ANUN,421864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almLow.AKED,421864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almLow.Resetable,421864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almLow.REST,421864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almLow.ACKN,421864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almLow.UACK,421864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almLow.MCmd_Enable,421864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almLow.MCmd_Disable,421864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almLow.OCmd_Shelve,421864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almLow.OCmd_Unshelve,421864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almLow.SCmd_Suppress,421864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almLow.SCmd_UnSuppress,421865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almLow.AEShelveTMRDN,421865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almLow.Bad,421865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almLow.Suppress,421866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.UnSuppress,421866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Shelve,421866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.UnShelve,421866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Enable,421866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Disable,421866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Ack,421866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Reset,421866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almLow.Suppressed,421866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almLow.Shelved,421866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almLow.Disabled,421866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almLow.Acked,421866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almLow.Alarm,421866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Fault,421876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almLowLow.AlarmState,421876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almLowLow.GlobalReset,421876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almLowLow.FaultInAlarm,421876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almLowLow.ALRM,421876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almLowLow.ANUN,421876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almLowLow.AKED,421876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almLowLow.Resetable,421876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almLowLow.REST,421876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almLowLow.ACKN,421876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almLowLow.UACK,421876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almLowLow.MCmd_Enable,421876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almLowLow.MCmd_Disable,421876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almLowLow.OCmd_Shelve,421876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almLowLow.OCmd_Unshelve,421876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almLowLow.SCmd_Suppress,421876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almLowLow.SCmd_UnSuppress,421877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almLowLow.AEShelveTMRDN,421877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almLowLow.Bad,421877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almLowLow.Suppress,421878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.UnSuppress,421878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Shelve,421878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.UnShelve,421878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Enable,421878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Disable,421878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Ack,421878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Reset,421878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Suppressed,421878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Shelved,421878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Disabled,421878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Acked,421878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almLowLow.Alarm,421878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Fault,421888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almBrokenLoop.AlarmState,421888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almBrokenLoop.GlobalReset,421888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almBrokenLoop.FaultInAlarm,421888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almBrokenLoop.ALRM,421888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almBrokenLoop.ANUN,421888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almBrokenLoop.AKED,421888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almBrokenLoop.Resetable,421888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almBrokenLoop.REST,421888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almBrokenLoop.ACKN,421888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almBrokenLoop.UACK,421888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almBrokenLoop.MCmd_Enable,421888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.MCmd_Disable,421888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.OCmd_Shelve,421888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.OCmd_Unshelve,421888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.SCmd_Suppress,421888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.SCmd_UnSuppress,421889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almBrokenLoop.AEShelveTMRDN,421889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almBrokenLoop.Bad,421889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almBrokenLoop.Suppress,421890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.UnSuppress,421890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Shelve,421890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.UnShelve,421890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Enable,421890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Disable,421890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Ack,421890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Reset,421890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Suppressed,421890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Shelved,421890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Disabled,421890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Acked,421890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.Alarm,421890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Fault,421900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almOverRange.AlarmState,421900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almOverRange.GlobalReset,421900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almOverRange.FaultInAlarm,421900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almOverRange.ALRM,421900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almOverRange.ANUN,421900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almOverRange.AKED,421900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almOverRange.Resetable,421900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almOverRange.REST,421900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almOverRange.ACKN,421900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almOverRange.UACK,421900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almOverRange.MCmd_Enable,421900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almOverRange.MCmd_Disable,421900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almOverRange.OCmd_Shelve,421900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almOverRange.OCmd_Unshelve,421900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almOverRange.SCmd_Suppress,421900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almOverRange.SCmd_UnSuppress,421901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almOverRange.AEShelveTMRDN,421901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almOverRange.Bad,421901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almOverRange.Suppress,421902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.UnSuppress,421902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Shelve,421902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.UnShelve,421902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Enable,421902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Disable,421902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Ack,421902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Reset,421902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Suppressed,421902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Shelved,421902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Disabled,421902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Acked,421902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almOverRange.Alarm,421902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Fault,421912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almUnderRange.AlarmState,421912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almUnderRange.GlobalReset,421912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almUnderRange.FaultInAlarm,421912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almUnderRange.ALRM,421912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almUnderRange.ANUN,421912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almUnderRange.AKED,421912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almUnderRange.Resetable,421912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almUnderRange.REST,421912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almUnderRange.ACKN,421912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almUnderRange.UACK,421912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almUnderRange.MCmd_Enable,421912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.MCmd_Disable,421912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.OCmd_Shelve,421912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.OCmd_Unshelve,421912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.SCmd_Suppress,421912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.SCmd_UnSuppress,421913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almUnderRange.AEShelveTMRDN,421913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almUnderRange.Bad,421913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almUnderRange.Suppress,421914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.UnSuppress,421914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Shelve,421914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.UnShelve,421914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Enable,421914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Disable,421914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Ack,421914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Reset,421914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Suppressed,421914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Shelved,421914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Disabled,421914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Acked,421914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almUnderRange.Alarm,421914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Fault,421924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almRateOfChange.AlarmState,421924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almRateOfChange.GlobalReset,421924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almRateOfChange.FaultInAlarm,421924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almRateOfChange.ALRM,421924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almRateOfChange.ANUN,421924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almRateOfChange.AKED,421924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almRateOfChange.Resetable,421924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almRateOfChange.REST,421924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almRateOfChange.ACKN,421924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almRateOfChange.UACK,421924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almRateOfChange.MCmd_Enable,421924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.MCmd_Disable,421924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.OCmd_Shelve,421924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.OCmd_Unshelve,421924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.SCmd_Suppress,421924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.SCmd_UnSuppress,421925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almRateOfChange.AEShelveTMRDN,421925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almRateOfChange.Bad,421925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almRateOfChange.Suppress,421926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.UnSuppress,421926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Shelve,421926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.UnShelve,421926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Enable,421926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Disable,421926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Ack,421926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Reset,421926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Suppressed,421926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Shelved,421926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Disabled,421926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Acked,421926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almRateOfChange.Alarm,421926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Fault,421936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI2.almPLCFault.AlarmState,421936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI2.almPLCFault.GlobalReset,421936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI2.almPLCFault.FaultInAlarm,421936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI2.almPLCFault.ALRM,421936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI2.almPLCFault.ANUN,421936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI2.almPLCFault.AKED,421936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI2.almPLCFault.Resetable,421936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI2.almPLCFault.REST,421936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI2.almPLCFault.ACKN,421936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI2.almPLCFault.UACK,421936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI2.almPLCFault.MCmd_Enable,421936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.MCmd_Disable,421936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.OCmd_Shelve,421936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.OCmd_Unshelve,421936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.SCmd_Suppress,421936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.SCmd_UnSuppress,421937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI2.almPLCFault.AEShelveTMRDN,421937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI2.almPLCFault.Bad,421937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI2.almPLCFault.Suppress,421938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.UnSuppress,421938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Shelve,421938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.UnShelve,421938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Enable,421938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Disable,421938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Ack,421938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Reset,421938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Suppressed,421938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Shelved,421938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Disabled,421938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Acked,421938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI2.almPLCFault.Alarm,421938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Fault,422040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almHighHigh.AlarmState,422040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almHighHigh.GlobalReset,422040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almHighHigh.FaultInAlarm,422040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almHighHigh.ALRM,422040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almHighHigh.ANUN,422040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almHighHigh.AKED,422040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almHighHigh.Resetable,422040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almHighHigh.REST,422040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almHighHigh.ACKN,422040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almHighHigh.UACK,422040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almHighHigh.MCmd_Enable,422040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.MCmd_Disable,422040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.OCmd_Shelve,422040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.OCmd_Unshelve,422040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.SCmd_Suppress,422040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.SCmd_UnSuppress,422041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almHighHigh.AEShelveTMRDN,422041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almHighHigh.Bad,422041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almHighHigh.Suppress,422042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.UnSuppress,422042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Shelve,422042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.UnShelve,422042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Enable,422042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Disable,422042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Ack,422042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Reset,422042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Suppressed,422042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Shelved,422042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Disabled,422042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Acked,422042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almHighHigh.Alarm,422042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Fault,422052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almHigh.AlarmState,422052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almHigh.GlobalReset,422052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almHigh.FaultInAlarm,422052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almHigh.ALRM,422052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almHigh.ANUN,422052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almHigh.AKED,422052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almHigh.Resetable,422052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almHigh.REST,422052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almHigh.ACKN,422052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almHigh.UACK,422052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almHigh.MCmd_Enable,422052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almHigh.MCmd_Disable,422052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almHigh.OCmd_Shelve,422052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almHigh.OCmd_Unshelve,422052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almHigh.SCmd_Suppress,422052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almHigh.SCmd_UnSuppress,422053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almHigh.AEShelveTMRDN,422053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almHigh.Bad,422053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almHigh.Suppress,422054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.UnSuppress,422054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Shelve,422054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.UnShelve,422054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Enable,422054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Disable,422054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Ack,422054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Reset,422054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almHigh.Suppressed,422054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almHigh.Shelved,422054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almHigh.Disabled,422054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almHigh.Acked,422054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almHigh.Alarm,422054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Fault,422064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almLow.AlarmState,422064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almLow.GlobalReset,422064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almLow.FaultInAlarm,422064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almLow.ALRM,422064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almLow.ANUN,422064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almLow.AKED,422064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almLow.Resetable,422064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almLow.REST,422064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almLow.ACKN,422064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almLow.UACK,422064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almLow.MCmd_Enable,422064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almLow.MCmd_Disable,422064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almLow.OCmd_Shelve,422064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almLow.OCmd_Unshelve,422064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almLow.SCmd_Suppress,422064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almLow.SCmd_UnSuppress,422065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almLow.AEShelveTMRDN,422065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almLow.Bad,422065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almLow.Suppress,422066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.UnSuppress,422066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Shelve,422066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.UnShelve,422066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Enable,422066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Disable,422066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Ack,422066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Reset,422066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almLow.Suppressed,422066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almLow.Shelved,422066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almLow.Disabled,422066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almLow.Acked,422066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almLow.Alarm,422066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Fault,422076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almLowLow.AlarmState,422076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almLowLow.GlobalReset,422076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almLowLow.FaultInAlarm,422076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almLowLow.ALRM,422076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almLowLow.ANUN,422076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almLowLow.AKED,422076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almLowLow.Resetable,422076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almLowLow.REST,422076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almLowLow.ACKN,422076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almLowLow.UACK,422076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almLowLow.MCmd_Enable,422076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almLowLow.MCmd_Disable,422076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almLowLow.OCmd_Shelve,422076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almLowLow.OCmd_Unshelve,422076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almLowLow.SCmd_Suppress,422076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almLowLow.SCmd_UnSuppress,422077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almLowLow.AEShelveTMRDN,422077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almLowLow.Bad,422077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almLowLow.Suppress,422078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.UnSuppress,422078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Shelve,422078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.UnShelve,422078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Enable,422078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Disable,422078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Ack,422078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Reset,422078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Suppressed,422078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Shelved,422078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Disabled,422078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Acked,422078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almLowLow.Alarm,422078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Fault,422088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almBrokenLoop.AlarmState,422088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almBrokenLoop.GlobalReset,422088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almBrokenLoop.FaultInAlarm,422088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almBrokenLoop.ALRM,422088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almBrokenLoop.ANUN,422088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almBrokenLoop.AKED,422088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almBrokenLoop.Resetable,422088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almBrokenLoop.REST,422088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almBrokenLoop.ACKN,422088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almBrokenLoop.UACK,422088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almBrokenLoop.MCmd_Enable,422088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.MCmd_Disable,422088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.OCmd_Shelve,422088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.OCmd_Unshelve,422088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.SCmd_Suppress,422088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.SCmd_UnSuppress,422089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almBrokenLoop.AEShelveTMRDN,422089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almBrokenLoop.Bad,422089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almBrokenLoop.Suppress,422090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.UnSuppress,422090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Shelve,422090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.UnShelve,422090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Enable,422090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Disable,422090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Ack,422090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Reset,422090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Suppressed,422090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Shelved,422090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Disabled,422090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Acked,422090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.Alarm,422090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Fault,422100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almOverRange.AlarmState,422100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almOverRange.GlobalReset,422100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almOverRange.FaultInAlarm,422100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almOverRange.ALRM,422100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almOverRange.ANUN,422100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almOverRange.AKED,422100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almOverRange.Resetable,422100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almOverRange.REST,422100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almOverRange.ACKN,422100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almOverRange.UACK,422100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almOverRange.MCmd_Enable,422100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almOverRange.MCmd_Disable,422100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almOverRange.OCmd_Shelve,422100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almOverRange.OCmd_Unshelve,422100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almOverRange.SCmd_Suppress,422100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almOverRange.SCmd_UnSuppress,422101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almOverRange.AEShelveTMRDN,422101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almOverRange.Bad,422101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almOverRange.Suppress,422102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.UnSuppress,422102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Shelve,422102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.UnShelve,422102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Enable,422102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Disable,422102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Ack,422102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Reset,422102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Suppressed,422102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Shelved,422102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Disabled,422102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Acked,422102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almOverRange.Alarm,422102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Fault,422112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almUnderRange.AlarmState,422112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almUnderRange.GlobalReset,422112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almUnderRange.FaultInAlarm,422112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almUnderRange.ALRM,422112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almUnderRange.ANUN,422112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almUnderRange.AKED,422112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almUnderRange.Resetable,422112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almUnderRange.REST,422112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almUnderRange.ACKN,422112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almUnderRange.UACK,422112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almUnderRange.MCmd_Enable,422112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.MCmd_Disable,422112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.OCmd_Shelve,422112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.OCmd_Unshelve,422112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.SCmd_Suppress,422112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.SCmd_UnSuppress,422113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almUnderRange.AEShelveTMRDN,422113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almUnderRange.Bad,422113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almUnderRange.Suppress,422114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.UnSuppress,422114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Shelve,422114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.UnShelve,422114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Enable,422114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Disable,422114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Ack,422114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Reset,422114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Suppressed,422114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Shelved,422114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Disabled,422114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Acked,422114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almUnderRange.Alarm,422114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Fault,422124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almRateOfChange.AlarmState,422124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almRateOfChange.GlobalReset,422124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almRateOfChange.FaultInAlarm,422124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almRateOfChange.ALRM,422124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almRateOfChange.ANUN,422124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almRateOfChange.AKED,422124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almRateOfChange.Resetable,422124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almRateOfChange.REST,422124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almRateOfChange.ACKN,422124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almRateOfChange.UACK,422124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almRateOfChange.MCmd_Enable,422124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.MCmd_Disable,422124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.OCmd_Shelve,422124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.OCmd_Unshelve,422124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.SCmd_Suppress,422124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.SCmd_UnSuppress,422125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almRateOfChange.AEShelveTMRDN,422125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almRateOfChange.Bad,422125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almRateOfChange.Suppress,422126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.UnSuppress,422126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Shelve,422126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.UnShelve,422126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Enable,422126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Disable,422126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Ack,422126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Reset,422126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Suppressed,422126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Shelved,422126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Disabled,422126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Acked,422126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almRateOfChange.Alarm,422126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Fault,422136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI3.almPLCFault.AlarmState,422136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI3.almPLCFault.GlobalReset,422136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI3.almPLCFault.FaultInAlarm,422136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI3.almPLCFault.ALRM,422136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI3.almPLCFault.ANUN,422136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI3.almPLCFault.AKED,422136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI3.almPLCFault.Resetable,422136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI3.almPLCFault.REST,422136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI3.almPLCFault.ACKN,422136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI3.almPLCFault.UACK,422136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI3.almPLCFault.MCmd_Enable,422136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.MCmd_Disable,422136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.OCmd_Shelve,422136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.OCmd_Unshelve,422136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.SCmd_Suppress,422136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.SCmd_UnSuppress,422137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI3.almPLCFault.AEShelveTMRDN,422137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI3.almPLCFault.Bad,422137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI3.almPLCFault.Suppress,422138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.UnSuppress,422138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Shelve,422138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.UnShelve,422138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Enable,422138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Disable,422138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Ack,422138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Reset,422138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Suppressed,422138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Shelved,422138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Disabled,422138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Acked,422138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI3.almPLCFault.Alarm,422138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Fault,422240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almHighHigh.AlarmState,422240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almHighHigh.GlobalReset,422240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almHighHigh.FaultInAlarm,422240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almHighHigh.ALRM,422240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almHighHigh.ANUN,422240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almHighHigh.AKED,422240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almHighHigh.Resetable,422240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almHighHigh.REST,422240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almHighHigh.ACKN,422240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almHighHigh.UACK,422240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almHighHigh.MCmd_Enable,422240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.MCmd_Disable,422240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.OCmd_Shelve,422240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.OCmd_Unshelve,422240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.SCmd_Suppress,422240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.SCmd_UnSuppress,422241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almHighHigh.AEShelveTMRDN,422241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almHighHigh.Bad,422241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almHighHigh.Suppress,422242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.UnSuppress,422242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Shelve,422242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.UnShelve,422242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Enable,422242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Disable,422242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Ack,422242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Reset,422242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Suppressed,422242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Shelved,422242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Disabled,422242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Acked,422242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almHighHigh.Alarm,422242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Fault,422252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almHigh.AlarmState,422252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almHigh.GlobalReset,422252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almHigh.FaultInAlarm,422252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almHigh.ALRM,422252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almHigh.ANUN,422252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almHigh.AKED,422252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almHigh.Resetable,422252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almHigh.REST,422252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almHigh.ACKN,422252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almHigh.UACK,422252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almHigh.MCmd_Enable,422252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almHigh.MCmd_Disable,422252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almHigh.OCmd_Shelve,422252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almHigh.OCmd_Unshelve,422252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almHigh.SCmd_Suppress,422252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almHigh.SCmd_UnSuppress,422253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almHigh.AEShelveTMRDN,422253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almHigh.Bad,422253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almHigh.Suppress,422254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.UnSuppress,422254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Shelve,422254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.UnShelve,422254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Enable,422254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Disable,422254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Ack,422254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Reset,422254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almHigh.Suppressed,422254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almHigh.Shelved,422254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almHigh.Disabled,422254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almHigh.Acked,422254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almHigh.Alarm,422254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Fault,422264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almLow.AlarmState,422264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almLow.GlobalReset,422264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almLow.FaultInAlarm,422264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almLow.ALRM,422264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almLow.ANUN,422264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almLow.AKED,422264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almLow.Resetable,422264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almLow.REST,422264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almLow.ACKN,422264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almLow.UACK,422264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almLow.MCmd_Enable,422264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almLow.MCmd_Disable,422264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almLow.OCmd_Shelve,422264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almLow.OCmd_Unshelve,422264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almLow.SCmd_Suppress,422264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almLow.SCmd_UnSuppress,422265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almLow.AEShelveTMRDN,422265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almLow.Bad,422265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almLow.Suppress,422266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.UnSuppress,422266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Shelve,422266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.UnShelve,422266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Enable,422266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Disable,422266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Ack,422266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Reset,422266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almLow.Suppressed,422266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almLow.Shelved,422266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almLow.Disabled,422266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almLow.Acked,422266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almLow.Alarm,422266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Fault,422276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almLowLow.AlarmState,422276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almLowLow.GlobalReset,422276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almLowLow.FaultInAlarm,422276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almLowLow.ALRM,422276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almLowLow.ANUN,422276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almLowLow.AKED,422276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almLowLow.Resetable,422276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almLowLow.REST,422276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almLowLow.ACKN,422276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almLowLow.UACK,422276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almLowLow.MCmd_Enable,422276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almLowLow.MCmd_Disable,422276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almLowLow.OCmd_Shelve,422276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almLowLow.OCmd_Unshelve,422276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almLowLow.SCmd_Suppress,422276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almLowLow.SCmd_UnSuppress,422277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almLowLow.AEShelveTMRDN,422277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almLowLow.Bad,422277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almLowLow.Suppress,422278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.UnSuppress,422278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Shelve,422278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.UnShelve,422278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Enable,422278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Disable,422278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Ack,422278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Reset,422278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Suppressed,422278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Shelved,422278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Disabled,422278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Acked,422278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almLowLow.Alarm,422278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Fault,422288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almBrokenLoop.AlarmState,422288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almBrokenLoop.GlobalReset,422288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almBrokenLoop.FaultInAlarm,422288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almBrokenLoop.ALRM,422288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almBrokenLoop.ANUN,422288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almBrokenLoop.AKED,422288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almBrokenLoop.Resetable,422288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almBrokenLoop.REST,422288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almBrokenLoop.ACKN,422288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almBrokenLoop.UACK,422288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almBrokenLoop.MCmd_Enable,422288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.MCmd_Disable,422288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.OCmd_Shelve,422288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.OCmd_Unshelve,422288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.SCmd_Suppress,422288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.SCmd_UnSuppress,422289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almBrokenLoop.AEShelveTMRDN,422289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almBrokenLoop.Bad,422289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almBrokenLoop.Suppress,422290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.UnSuppress,422290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Shelve,422290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.UnShelve,422290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Enable,422290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Disable,422290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Ack,422290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Reset,422290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Suppressed,422290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Shelved,422290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Disabled,422290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Acked,422290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.Alarm,422290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Fault,422300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almOverRange.AlarmState,422300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almOverRange.GlobalReset,422300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almOverRange.FaultInAlarm,422300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almOverRange.ALRM,422300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almOverRange.ANUN,422300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almOverRange.AKED,422300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almOverRange.Resetable,422300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almOverRange.REST,422300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almOverRange.ACKN,422300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almOverRange.UACK,422300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almOverRange.MCmd_Enable,422300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almOverRange.MCmd_Disable,422300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almOverRange.OCmd_Shelve,422300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almOverRange.OCmd_Unshelve,422300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almOverRange.SCmd_Suppress,422300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almOverRange.SCmd_UnSuppress,422301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almOverRange.AEShelveTMRDN,422301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almOverRange.Bad,422301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almOverRange.Suppress,422302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.UnSuppress,422302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Shelve,422302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.UnShelve,422302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Enable,422302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Disable,422302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Ack,422302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Reset,422302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Suppressed,422302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Shelved,422302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Disabled,422302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Acked,422302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almOverRange.Alarm,422302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Fault,422312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almUnderRange.AlarmState,422312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almUnderRange.GlobalReset,422312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almUnderRange.FaultInAlarm,422312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almUnderRange.ALRM,422312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almUnderRange.ANUN,422312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almUnderRange.AKED,422312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almUnderRange.Resetable,422312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almUnderRange.REST,422312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almUnderRange.ACKN,422312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almUnderRange.UACK,422312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almUnderRange.MCmd_Enable,422312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.MCmd_Disable,422312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.OCmd_Shelve,422312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.OCmd_Unshelve,422312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.SCmd_Suppress,422312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.SCmd_UnSuppress,422313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almUnderRange.AEShelveTMRDN,422313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almUnderRange.Bad,422313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almUnderRange.Suppress,422314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.UnSuppress,422314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Shelve,422314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.UnShelve,422314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Enable,422314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Disable,422314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Ack,422314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Reset,422314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Suppressed,422314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Shelved,422314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Disabled,422314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Acked,422314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almUnderRange.Alarm,422314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Fault,422324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almRateOfChange.AlarmState,422324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almRateOfChange.GlobalReset,422324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almRateOfChange.FaultInAlarm,422324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almRateOfChange.ALRM,422324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almRateOfChange.ANUN,422324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almRateOfChange.AKED,422324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almRateOfChange.Resetable,422324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almRateOfChange.REST,422324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almRateOfChange.ACKN,422324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almRateOfChange.UACK,422324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almRateOfChange.MCmd_Enable,422324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.MCmd_Disable,422324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.OCmd_Shelve,422324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.OCmd_Unshelve,422324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.SCmd_Suppress,422324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.SCmd_UnSuppress,422325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almRateOfChange.AEShelveTMRDN,422325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almRateOfChange.Bad,422325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almRateOfChange.Suppress,422326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.UnSuppress,422326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Shelve,422326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.UnShelve,422326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Enable,422326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Disable,422326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Ack,422326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Reset,422326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Suppressed,422326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Shelved,422326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Disabled,422326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Acked,422326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almRateOfChange.Alarm,422326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Fault,422336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI4.almPLCFault.AlarmState,422336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI4.almPLCFault.GlobalReset,422336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI4.almPLCFault.FaultInAlarm,422336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI4.almPLCFault.ALRM,422336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI4.almPLCFault.ANUN,422336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI4.almPLCFault.AKED,422336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI4.almPLCFault.Resetable,422336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI4.almPLCFault.REST,422336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI4.almPLCFault.ACKN,422336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI4.almPLCFault.UACK,422336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI4.almPLCFault.MCmd_Enable,422336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.MCmd_Disable,422336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.OCmd_Shelve,422336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.OCmd_Unshelve,422336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.SCmd_Suppress,422336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.SCmd_UnSuppress,422337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI4.almPLCFault.AEShelveTMRDN,422337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI4.almPLCFault.Bad,422337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI4.almPLCFault.Suppress,422338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.UnSuppress,422338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Shelve,422338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.UnShelve,422338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Enable,422338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Disable,422338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Ack,422338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Reset,422338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Suppressed,422338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Shelved,422338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Disabled,422338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Acked,422338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI4.almPLCFault.Alarm,422338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Fault,422440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almHighHigh.AlarmState,422440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almHighHigh.GlobalReset,422440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almHighHigh.FaultInAlarm,422440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almHighHigh.ALRM,422440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almHighHigh.ANUN,422440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almHighHigh.AKED,422440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almHighHigh.Resetable,422440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almHighHigh.REST,422440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almHighHigh.ACKN,422440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almHighHigh.UACK,422440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almHighHigh.MCmd_Enable,422440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.MCmd_Disable,422440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.OCmd_Shelve,422440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.OCmd_Unshelve,422440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.SCmd_Suppress,422440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.SCmd_UnSuppress,422441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almHighHigh.AEShelveTMRDN,422441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almHighHigh.Bad,422441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almHighHigh.Suppress,422442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.UnSuppress,422442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Shelve,422442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.UnShelve,422442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Enable,422442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Disable,422442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Ack,422442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Reset,422442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Suppressed,422442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Shelved,422442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Disabled,422442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Acked,422442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almHighHigh.Alarm,422442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Fault,422452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almHigh.AlarmState,422452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almHigh.GlobalReset,422452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almHigh.FaultInAlarm,422452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almHigh.ALRM,422452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almHigh.ANUN,422452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almHigh.AKED,422452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almHigh.Resetable,422452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almHigh.REST,422452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almHigh.ACKN,422452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almHigh.UACK,422452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almHigh.MCmd_Enable,422452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almHigh.MCmd_Disable,422452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almHigh.OCmd_Shelve,422452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almHigh.OCmd_Unshelve,422452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almHigh.SCmd_Suppress,422452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almHigh.SCmd_UnSuppress,422453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almHigh.AEShelveTMRDN,422453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almHigh.Bad,422453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almHigh.Suppress,422454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.UnSuppress,422454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Shelve,422454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.UnShelve,422454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Enable,422454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Disable,422454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Ack,422454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Reset,422454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almHigh.Suppressed,422454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almHigh.Shelved,422454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almHigh.Disabled,422454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almHigh.Acked,422454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almHigh.Alarm,422454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Fault,422464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almLow.AlarmState,422464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almLow.GlobalReset,422464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almLow.FaultInAlarm,422464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almLow.ALRM,422464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almLow.ANUN,422464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almLow.AKED,422464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almLow.Resetable,422464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almLow.REST,422464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almLow.ACKN,422464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almLow.UACK,422464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almLow.MCmd_Enable,422464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almLow.MCmd_Disable,422464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almLow.OCmd_Shelve,422464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almLow.OCmd_Unshelve,422464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almLow.SCmd_Suppress,422464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almLow.SCmd_UnSuppress,422465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almLow.AEShelveTMRDN,422465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almLow.Bad,422465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almLow.Suppress,422466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.UnSuppress,422466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Shelve,422466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.UnShelve,422466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Enable,422466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Disable,422466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Ack,422466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Reset,422466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almLow.Suppressed,422466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almLow.Shelved,422466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almLow.Disabled,422466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almLow.Acked,422466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almLow.Alarm,422466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Fault,422476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almLowLow.AlarmState,422476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almLowLow.GlobalReset,422476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almLowLow.FaultInAlarm,422476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almLowLow.ALRM,422476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almLowLow.ANUN,422476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almLowLow.AKED,422476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almLowLow.Resetable,422476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almLowLow.REST,422476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almLowLow.ACKN,422476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almLowLow.UACK,422476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almLowLow.MCmd_Enable,422476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almLowLow.MCmd_Disable,422476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almLowLow.OCmd_Shelve,422476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almLowLow.OCmd_Unshelve,422476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almLowLow.SCmd_Suppress,422476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almLowLow.SCmd_UnSuppress,422477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almLowLow.AEShelveTMRDN,422477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almLowLow.Bad,422477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almLowLow.Suppress,422478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.UnSuppress,422478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Shelve,422478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.UnShelve,422478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Enable,422478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Disable,422478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Ack,422478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Reset,422478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Suppressed,422478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Shelved,422478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Disabled,422478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Acked,422478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almLowLow.Alarm,422478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Fault,422488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almBrokenLoop.AlarmState,422488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almBrokenLoop.GlobalReset,422488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almBrokenLoop.FaultInAlarm,422488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almBrokenLoop.ALRM,422488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almBrokenLoop.ANUN,422488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almBrokenLoop.AKED,422488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almBrokenLoop.Resetable,422488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almBrokenLoop.REST,422488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almBrokenLoop.ACKN,422488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almBrokenLoop.UACK,422488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almBrokenLoop.MCmd_Enable,422488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.MCmd_Disable,422488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.OCmd_Shelve,422488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.OCmd_Unshelve,422488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.SCmd_Suppress,422488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.SCmd_UnSuppress,422489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almBrokenLoop.AEShelveTMRDN,422489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almBrokenLoop.Bad,422489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almBrokenLoop.Suppress,422490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.UnSuppress,422490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Shelve,422490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.UnShelve,422490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Enable,422490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Disable,422490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Ack,422490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Reset,422490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Suppressed,422490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Shelved,422490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Disabled,422490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Acked,422490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.Alarm,422490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Fault,422500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almOverRange.AlarmState,422500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almOverRange.GlobalReset,422500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almOverRange.FaultInAlarm,422500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almOverRange.ALRM,422500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almOverRange.ANUN,422500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almOverRange.AKED,422500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almOverRange.Resetable,422500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almOverRange.REST,422500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almOverRange.ACKN,422500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almOverRange.UACK,422500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almOverRange.MCmd_Enable,422500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almOverRange.MCmd_Disable,422500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almOverRange.OCmd_Shelve,422500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almOverRange.OCmd_Unshelve,422500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almOverRange.SCmd_Suppress,422500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almOverRange.SCmd_UnSuppress,422501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almOverRange.AEShelveTMRDN,422501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almOverRange.Bad,422501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almOverRange.Suppress,422502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.UnSuppress,422502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Shelve,422502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.UnShelve,422502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Enable,422502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Disable,422502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Ack,422502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Reset,422502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Suppressed,422502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Shelved,422502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Disabled,422502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Acked,422502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almOverRange.Alarm,422502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Fault,422512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almUnderRange.AlarmState,422512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almUnderRange.GlobalReset,422512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almUnderRange.FaultInAlarm,422512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almUnderRange.ALRM,422512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almUnderRange.ANUN,422512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almUnderRange.AKED,422512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almUnderRange.Resetable,422512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almUnderRange.REST,422512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almUnderRange.ACKN,422512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almUnderRange.UACK,422512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almUnderRange.MCmd_Enable,422512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.MCmd_Disable,422512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.OCmd_Shelve,422512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.OCmd_Unshelve,422512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.SCmd_Suppress,422512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.SCmd_UnSuppress,422513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almUnderRange.AEShelveTMRDN,422513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almUnderRange.Bad,422513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almUnderRange.Suppress,422514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.UnSuppress,422514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Shelve,422514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.UnShelve,422514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Enable,422514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Disable,422514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Ack,422514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Reset,422514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Suppressed,422514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Shelved,422514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Disabled,422514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Acked,422514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almUnderRange.Alarm,422514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Fault,422524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almRateOfChange.AlarmState,422524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almRateOfChange.GlobalReset,422524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almRateOfChange.FaultInAlarm,422524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almRateOfChange.ALRM,422524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almRateOfChange.ANUN,422524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almRateOfChange.AKED,422524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almRateOfChange.Resetable,422524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almRateOfChange.REST,422524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almRateOfChange.ACKN,422524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almRateOfChange.UACK,422524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almRateOfChange.MCmd_Enable,422524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.MCmd_Disable,422524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.OCmd_Shelve,422524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.OCmd_Unshelve,422524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.SCmd_Suppress,422524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.SCmd_UnSuppress,422525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almRateOfChange.AEShelveTMRDN,422525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almRateOfChange.Bad,422525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almRateOfChange.Suppress,422526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.UnSuppress,422526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Shelve,422526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.UnShelve,422526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Enable,422526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Disable,422526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Ack,422526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Reset,422526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Suppressed,422526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Shelved,422526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Disabled,422526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Acked,422526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almRateOfChange.Alarm,422526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Fault,422536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_6_VI5.almPLCFault.AlarmState,422536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_6_VI5.almPLCFault.GlobalReset,422536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_6_VI5.almPLCFault.FaultInAlarm,422536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_6_VI5.almPLCFault.ALRM,422536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_6_VI5.almPLCFault.ANUN,422536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_6_VI5.almPLCFault.AKED,422536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_6_VI5.almPLCFault.Resetable,422536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_6_VI5.almPLCFault.REST,422536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_6_VI5.almPLCFault.ACKN,422536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_6_VI5.almPLCFault.UACK,422536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_6_VI5.almPLCFault.MCmd_Enable,422536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.MCmd_Disable,422536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.OCmd_Shelve,422536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.OCmd_Unshelve,422536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.SCmd_Suppress,422536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.SCmd_UnSuppress,422537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_6_VI5.almPLCFault.AEShelveTMRDN,422537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_6_VI5.almPLCFault.Bad,422537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_6_VI5.almPLCFault.Suppress,422538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.UnSuppress,422538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Shelve,422538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.UnShelve,422538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Enable,422538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Disable,422538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Ack,422538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Reset,422538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Suppressed,422538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Shelved,422538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Disabled,422538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Acked,422538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_6_VI5.almPLCFault.Alarm,422538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Fault,422640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almHighHigh.AlarmState,422640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almHighHigh.GlobalReset,422640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almHighHigh.FaultInAlarm,422640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almHighHigh.ALRM,422640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almHighHigh.ANUN,422640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almHighHigh.AKED,422640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almHighHigh.Resetable,422640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almHighHigh.REST,422640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almHighHigh.ACKN,422640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almHighHigh.UACK,422640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almHighHigh.MCmd_Enable,422640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.MCmd_Disable,422640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.OCmd_Shelve,422640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.OCmd_Unshelve,422640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.SCmd_Suppress,422640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.SCmd_UnSuppress,422641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almHighHigh.AEShelveTMRDN,422641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almHighHigh.Bad,422641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almHighHigh.Suppress,422642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.UnSuppress,422642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Shelve,422642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.UnShelve,422642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Enable,422642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Disable,422642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Ack,422642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Reset,422642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Suppressed,422642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Shelved,422642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Disabled,422642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Acked,422642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almHighHigh.Alarm,422642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Fault,422652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almHigh.AlarmState,422652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almHigh.GlobalReset,422652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almHigh.FaultInAlarm,422652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almHigh.ALRM,422652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almHigh.ANUN,422652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almHigh.AKED,422652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almHigh.Resetable,422652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almHigh.REST,422652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almHigh.ACKN,422652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almHigh.UACK,422652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almHigh.MCmd_Enable,422652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almHigh.MCmd_Disable,422652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almHigh.OCmd_Shelve,422652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almHigh.OCmd_Unshelve,422652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almHigh.SCmd_Suppress,422652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almHigh.SCmd_UnSuppress,422653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almHigh.AEShelveTMRDN,422653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almHigh.Bad,422653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almHigh.Suppress,422654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.UnSuppress,422654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Shelve,422654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.UnShelve,422654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Enable,422654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Disable,422654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Ack,422654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Reset,422654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almHigh.Suppressed,422654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almHigh.Shelved,422654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almHigh.Disabled,422654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almHigh.Acked,422654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almHigh.Alarm,422654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Fault,422664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almLow.AlarmState,422664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almLow.GlobalReset,422664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almLow.FaultInAlarm,422664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almLow.ALRM,422664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almLow.ANUN,422664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almLow.AKED,422664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almLow.Resetable,422664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almLow.REST,422664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almLow.ACKN,422664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almLow.UACK,422664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almLow.MCmd_Enable,422664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almLow.MCmd_Disable,422664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almLow.OCmd_Shelve,422664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almLow.OCmd_Unshelve,422664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almLow.SCmd_Suppress,422664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almLow.SCmd_UnSuppress,422665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almLow.AEShelveTMRDN,422665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almLow.Bad,422665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almLow.Suppress,422666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.UnSuppress,422666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Shelve,422666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.UnShelve,422666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Enable,422666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Disable,422666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Ack,422666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Reset,422666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almLow.Suppressed,422666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almLow.Shelved,422666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almLow.Disabled,422666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almLow.Acked,422666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almLow.Alarm,422666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Fault,422676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almLowLow.AlarmState,422676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almLowLow.GlobalReset,422676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almLowLow.FaultInAlarm,422676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almLowLow.ALRM,422676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almLowLow.ANUN,422676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almLowLow.AKED,422676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almLowLow.Resetable,422676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almLowLow.REST,422676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almLowLow.ACKN,422676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almLowLow.UACK,422676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almLowLow.MCmd_Enable,422676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almLowLow.MCmd_Disable,422676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almLowLow.OCmd_Shelve,422676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almLowLow.OCmd_Unshelve,422676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almLowLow.SCmd_Suppress,422676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almLowLow.SCmd_UnSuppress,422677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almLowLow.AEShelveTMRDN,422677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almLowLow.Bad,422677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almLowLow.Suppress,422678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.UnSuppress,422678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Shelve,422678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.UnShelve,422678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Enable,422678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Disable,422678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Ack,422678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Reset,422678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Suppressed,422678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Shelved,422678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Disabled,422678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Acked,422678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almLowLow.Alarm,422678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Fault,422688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almBrokenLoop.AlarmState,422688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almBrokenLoop.GlobalReset,422688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almBrokenLoop.FaultInAlarm,422688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almBrokenLoop.ALRM,422688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almBrokenLoop.ANUN,422688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almBrokenLoop.AKED,422688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almBrokenLoop.Resetable,422688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almBrokenLoop.REST,422688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almBrokenLoop.ACKN,422688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almBrokenLoop.UACK,422688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almBrokenLoop.MCmd_Enable,422688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.MCmd_Disable,422688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.OCmd_Shelve,422688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.OCmd_Unshelve,422688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.SCmd_Suppress,422688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.SCmd_UnSuppress,422689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almBrokenLoop.AEShelveTMRDN,422689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almBrokenLoop.Bad,422689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almBrokenLoop.Suppress,422690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.UnSuppress,422690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Shelve,422690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.UnShelve,422690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Enable,422690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Disable,422690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Ack,422690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Reset,422690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Suppressed,422690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Shelved,422690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Disabled,422690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Acked,422690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.Alarm,422690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Fault,422700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almOverRange.AlarmState,422700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almOverRange.GlobalReset,422700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almOverRange.FaultInAlarm,422700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almOverRange.ALRM,422700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almOverRange.ANUN,422700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almOverRange.AKED,422700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almOverRange.Resetable,422700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almOverRange.REST,422700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almOverRange.ACKN,422700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almOverRange.UACK,422700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almOverRange.MCmd_Enable,422700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almOverRange.MCmd_Disable,422700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almOverRange.OCmd_Shelve,422700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almOverRange.OCmd_Unshelve,422700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almOverRange.SCmd_Suppress,422700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almOverRange.SCmd_UnSuppress,422701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almOverRange.AEShelveTMRDN,422701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almOverRange.Bad,422701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almOverRange.Suppress,422702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.UnSuppress,422702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Shelve,422702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.UnShelve,422702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Enable,422702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Disable,422702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Ack,422702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Reset,422702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Suppressed,422702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Shelved,422702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Disabled,422702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Acked,422702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almOverRange.Alarm,422702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Fault,422712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almUnderRange.AlarmState,422712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almUnderRange.GlobalReset,422712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almUnderRange.FaultInAlarm,422712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almUnderRange.ALRM,422712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almUnderRange.ANUN,422712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almUnderRange.AKED,422712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almUnderRange.Resetable,422712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almUnderRange.REST,422712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almUnderRange.ACKN,422712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almUnderRange.UACK,422712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almUnderRange.MCmd_Enable,422712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.MCmd_Disable,422712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.OCmd_Shelve,422712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.OCmd_Unshelve,422712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.SCmd_Suppress,422712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.SCmd_UnSuppress,422713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almUnderRange.AEShelveTMRDN,422713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almUnderRange.Bad,422713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almUnderRange.Suppress,422714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.UnSuppress,422714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Shelve,422714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.UnShelve,422714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Enable,422714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Disable,422714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Ack,422714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Reset,422714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Suppressed,422714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Shelved,422714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Disabled,422714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Acked,422714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almUnderRange.Alarm,422714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Fault,422724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almRateOfChange.AlarmState,422724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almRateOfChange.GlobalReset,422724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almRateOfChange.FaultInAlarm,422724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almRateOfChange.ALRM,422724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almRateOfChange.ANUN,422724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almRateOfChange.AKED,422724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almRateOfChange.Resetable,422724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almRateOfChange.REST,422724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almRateOfChange.ACKN,422724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almRateOfChange.UACK,422724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almRateOfChange.MCmd_Enable,422724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.MCmd_Disable,422724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.OCmd_Shelve,422724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.OCmd_Unshelve,422724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.SCmd_Suppress,422724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.SCmd_UnSuppress,422725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almRateOfChange.AEShelveTMRDN,422725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almRateOfChange.Bad,422725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almRateOfChange.Suppress,422726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.UnSuppress,422726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Shelve,422726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.UnShelve,422726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Enable,422726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Disable,422726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Ack,422726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Reset,422726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Suppressed,422726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Shelved,422726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Disabled,422726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Acked,422726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almRateOfChange.Alarm,422726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Fault,422736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI1.almPLCFault.AlarmState,422736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI1.almPLCFault.GlobalReset,422736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI1.almPLCFault.FaultInAlarm,422736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI1.almPLCFault.ALRM,422736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI1.almPLCFault.ANUN,422736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI1.almPLCFault.AKED,422736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI1.almPLCFault.Resetable,422736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI1.almPLCFault.REST,422736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI1.almPLCFault.ACKN,422736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI1.almPLCFault.UACK,422736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI1.almPLCFault.MCmd_Enable,422736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.MCmd_Disable,422736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.OCmd_Shelve,422736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.OCmd_Unshelve,422736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.SCmd_Suppress,422736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.SCmd_UnSuppress,422737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI1.almPLCFault.AEShelveTMRDN,422737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI1.almPLCFault.Bad,422737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI1.almPLCFault.Suppress,422738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.UnSuppress,422738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Shelve,422738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.UnShelve,422738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Enable,422738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Disable,422738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Ack,422738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Reset,422738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Suppressed,422738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Shelved,422738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Disabled,422738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Acked,422738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI1.almPLCFault.Alarm,422738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Fault,422840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almHighHigh.AlarmState,422840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almHighHigh.GlobalReset,422840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almHighHigh.FaultInAlarm,422840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almHighHigh.ALRM,422840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almHighHigh.ANUN,422840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almHighHigh.AKED,422840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almHighHigh.Resetable,422840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almHighHigh.REST,422840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almHighHigh.ACKN,422840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almHighHigh.UACK,422840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almHighHigh.MCmd_Enable,422840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.MCmd_Disable,422840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.OCmd_Shelve,422840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.OCmd_Unshelve,422840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.SCmd_Suppress,422840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.SCmd_UnSuppress,422841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almHighHigh.AEShelveTMRDN,422841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almHighHigh.Bad,422841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almHighHigh.Suppress,422842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.UnSuppress,422842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Shelve,422842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.UnShelve,422842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Enable,422842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Disable,422842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Ack,422842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Reset,422842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Suppressed,422842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Shelved,422842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Disabled,422842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Acked,422842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almHighHigh.Alarm,422842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Fault,422852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almHigh.AlarmState,422852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almHigh.GlobalReset,422852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almHigh.FaultInAlarm,422852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almHigh.ALRM,422852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almHigh.ANUN,422852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almHigh.AKED,422852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almHigh.Resetable,422852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almHigh.REST,422852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almHigh.ACKN,422852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almHigh.UACK,422852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almHigh.MCmd_Enable,422852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almHigh.MCmd_Disable,422852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almHigh.OCmd_Shelve,422852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almHigh.OCmd_Unshelve,422852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almHigh.SCmd_Suppress,422852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almHigh.SCmd_UnSuppress,422853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almHigh.AEShelveTMRDN,422853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almHigh.Bad,422853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almHigh.Suppress,422854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.UnSuppress,422854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Shelve,422854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.UnShelve,422854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Enable,422854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Disable,422854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Ack,422854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Reset,422854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almHigh.Suppressed,422854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almHigh.Shelved,422854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almHigh.Disabled,422854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almHigh.Acked,422854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almHigh.Alarm,422854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Fault,422864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almLow.AlarmState,422864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almLow.GlobalReset,422864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almLow.FaultInAlarm,422864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almLow.ALRM,422864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almLow.ANUN,422864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almLow.AKED,422864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almLow.Resetable,422864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almLow.REST,422864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almLow.ACKN,422864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almLow.UACK,422864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almLow.MCmd_Enable,422864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almLow.MCmd_Disable,422864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almLow.OCmd_Shelve,422864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almLow.OCmd_Unshelve,422864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almLow.SCmd_Suppress,422864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almLow.SCmd_UnSuppress,422865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almLow.AEShelveTMRDN,422865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almLow.Bad,422865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almLow.Suppress,422866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.UnSuppress,422866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Shelve,422866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.UnShelve,422866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Enable,422866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Disable,422866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Ack,422866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Reset,422866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almLow.Suppressed,422866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almLow.Shelved,422866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almLow.Disabled,422866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almLow.Acked,422866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almLow.Alarm,422866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Fault,422876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almLowLow.AlarmState,422876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almLowLow.GlobalReset,422876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almLowLow.FaultInAlarm,422876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almLowLow.ALRM,422876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almLowLow.ANUN,422876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almLowLow.AKED,422876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almLowLow.Resetable,422876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almLowLow.REST,422876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almLowLow.ACKN,422876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almLowLow.UACK,422876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almLowLow.MCmd_Enable,422876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almLowLow.MCmd_Disable,422876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almLowLow.OCmd_Shelve,422876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almLowLow.OCmd_Unshelve,422876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almLowLow.SCmd_Suppress,422876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almLowLow.SCmd_UnSuppress,422877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almLowLow.AEShelveTMRDN,422877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almLowLow.Bad,422877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almLowLow.Suppress,422878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.UnSuppress,422878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Shelve,422878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.UnShelve,422878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Enable,422878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Disable,422878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Ack,422878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Reset,422878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Suppressed,422878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Shelved,422878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Disabled,422878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Acked,422878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almLowLow.Alarm,422878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Fault,422888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almBrokenLoop.AlarmState,422888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almBrokenLoop.GlobalReset,422888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almBrokenLoop.FaultInAlarm,422888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almBrokenLoop.ALRM,422888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almBrokenLoop.ANUN,422888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almBrokenLoop.AKED,422888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almBrokenLoop.Resetable,422888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almBrokenLoop.REST,422888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almBrokenLoop.ACKN,422888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almBrokenLoop.UACK,422888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almBrokenLoop.MCmd_Enable,422888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.MCmd_Disable,422888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.OCmd_Shelve,422888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.OCmd_Unshelve,422888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.SCmd_Suppress,422888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.SCmd_UnSuppress,422889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almBrokenLoop.AEShelveTMRDN,422889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almBrokenLoop.Bad,422889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almBrokenLoop.Suppress,422890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.UnSuppress,422890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Shelve,422890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.UnShelve,422890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Enable,422890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Disable,422890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Ack,422890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Reset,422890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Suppressed,422890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Shelved,422890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Disabled,422890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Acked,422890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.Alarm,422890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Fault,422900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almOverRange.AlarmState,422900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almOverRange.GlobalReset,422900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almOverRange.FaultInAlarm,422900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almOverRange.ALRM,422900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almOverRange.ANUN,422900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almOverRange.AKED,422900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almOverRange.Resetable,422900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almOverRange.REST,422900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almOverRange.ACKN,422900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almOverRange.UACK,422900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almOverRange.MCmd_Enable,422900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almOverRange.MCmd_Disable,422900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almOverRange.OCmd_Shelve,422900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almOverRange.OCmd_Unshelve,422900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almOverRange.SCmd_Suppress,422900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almOverRange.SCmd_UnSuppress,422901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almOverRange.AEShelveTMRDN,422901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almOverRange.Bad,422901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almOverRange.Suppress,422902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.UnSuppress,422902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Shelve,422902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.UnShelve,422902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Enable,422902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Disable,422902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Ack,422902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Reset,422902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Suppressed,422902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Shelved,422902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Disabled,422902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Acked,422902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almOverRange.Alarm,422902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Fault,422912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almUnderRange.AlarmState,422912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almUnderRange.GlobalReset,422912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almUnderRange.FaultInAlarm,422912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almUnderRange.ALRM,422912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almUnderRange.ANUN,422912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almUnderRange.AKED,422912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almUnderRange.Resetable,422912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almUnderRange.REST,422912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almUnderRange.ACKN,422912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almUnderRange.UACK,422912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almUnderRange.MCmd_Enable,422912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.MCmd_Disable,422912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.OCmd_Shelve,422912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.OCmd_Unshelve,422912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.SCmd_Suppress,422912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.SCmd_UnSuppress,422913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almUnderRange.AEShelveTMRDN,422913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almUnderRange.Bad,422913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almUnderRange.Suppress,422914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.UnSuppress,422914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Shelve,422914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.UnShelve,422914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Enable,422914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Disable,422914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Ack,422914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Reset,422914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Suppressed,422914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Shelved,422914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Disabled,422914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Acked,422914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almUnderRange.Alarm,422914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Fault,422924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almRateOfChange.AlarmState,422924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almRateOfChange.GlobalReset,422924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almRateOfChange.FaultInAlarm,422924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almRateOfChange.ALRM,422924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almRateOfChange.ANUN,422924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almRateOfChange.AKED,422924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almRateOfChange.Resetable,422924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almRateOfChange.REST,422924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almRateOfChange.ACKN,422924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almRateOfChange.UACK,422924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almRateOfChange.MCmd_Enable,422924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.MCmd_Disable,422924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.OCmd_Shelve,422924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.OCmd_Unshelve,422924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.SCmd_Suppress,422924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.SCmd_UnSuppress,422925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almRateOfChange.AEShelveTMRDN,422925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almRateOfChange.Bad,422925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almRateOfChange.Suppress,422926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.UnSuppress,422926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Shelve,422926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.UnShelve,422926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Enable,422926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Disable,422926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Ack,422926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Reset,422926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Suppressed,422926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Shelved,422926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Disabled,422926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Acked,422926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almRateOfChange.Alarm,422926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Fault,422936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI2.almPLCFault.AlarmState,422936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI2.almPLCFault.GlobalReset,422936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI2.almPLCFault.FaultInAlarm,422936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI2.almPLCFault.ALRM,422936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI2.almPLCFault.ANUN,422936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI2.almPLCFault.AKED,422936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI2.almPLCFault.Resetable,422936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI2.almPLCFault.REST,422936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI2.almPLCFault.ACKN,422936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI2.almPLCFault.UACK,422936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI2.almPLCFault.MCmd_Enable,422936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.MCmd_Disable,422936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.OCmd_Shelve,422936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.OCmd_Unshelve,422936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.SCmd_Suppress,422936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.SCmd_UnSuppress,422937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI2.almPLCFault.AEShelveTMRDN,422937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI2.almPLCFault.Bad,422937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI2.almPLCFault.Suppress,422938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.UnSuppress,422938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Shelve,422938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.UnShelve,422938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Enable,422938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Disable,422938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Ack,422938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Reset,422938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Suppressed,422938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Shelved,422938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Disabled,422938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Acked,422938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI2.almPLCFault.Alarm,422938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Fault,423040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almHighHigh.AlarmState,423040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almHighHigh.GlobalReset,423040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almHighHigh.FaultInAlarm,423040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almHighHigh.ALRM,423040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almHighHigh.ANUN,423040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almHighHigh.AKED,423040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almHighHigh.Resetable,423040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almHighHigh.REST,423040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almHighHigh.ACKN,423040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almHighHigh.UACK,423040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almHighHigh.MCmd_Enable,423040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.MCmd_Disable,423040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.OCmd_Shelve,423040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.OCmd_Unshelve,423040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.SCmd_Suppress,423040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.SCmd_UnSuppress,423041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almHighHigh.AEShelveTMRDN,423041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almHighHigh.Bad,423041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almHighHigh.Suppress,423042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.UnSuppress,423042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Shelve,423042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.UnShelve,423042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Enable,423042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Disable,423042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Ack,423042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Reset,423042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Suppressed,423042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Shelved,423042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Disabled,423042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Acked,423042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almHighHigh.Alarm,423042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Fault,423052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almHigh.AlarmState,423052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almHigh.GlobalReset,423052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almHigh.FaultInAlarm,423052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almHigh.ALRM,423052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almHigh.ANUN,423052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almHigh.AKED,423052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almHigh.Resetable,423052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almHigh.REST,423052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almHigh.ACKN,423052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almHigh.UACK,423052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almHigh.MCmd_Enable,423052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almHigh.MCmd_Disable,423052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almHigh.OCmd_Shelve,423052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almHigh.OCmd_Unshelve,423052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almHigh.SCmd_Suppress,423052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almHigh.SCmd_UnSuppress,423053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almHigh.AEShelveTMRDN,423053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almHigh.Bad,423053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almHigh.Suppress,423054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.UnSuppress,423054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Shelve,423054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.UnShelve,423054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Enable,423054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Disable,423054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Ack,423054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Reset,423054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almHigh.Suppressed,423054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almHigh.Shelved,423054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almHigh.Disabled,423054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almHigh.Acked,423054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almHigh.Alarm,423054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Fault,423064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almLow.AlarmState,423064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almLow.GlobalReset,423064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almLow.FaultInAlarm,423064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almLow.ALRM,423064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almLow.ANUN,423064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almLow.AKED,423064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almLow.Resetable,423064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almLow.REST,423064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almLow.ACKN,423064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almLow.UACK,423064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almLow.MCmd_Enable,423064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almLow.MCmd_Disable,423064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almLow.OCmd_Shelve,423064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almLow.OCmd_Unshelve,423064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almLow.SCmd_Suppress,423064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almLow.SCmd_UnSuppress,423065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almLow.AEShelveTMRDN,423065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almLow.Bad,423065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almLow.Suppress,423066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.UnSuppress,423066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Shelve,423066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.UnShelve,423066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Enable,423066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Disable,423066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Ack,423066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Reset,423066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almLow.Suppressed,423066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almLow.Shelved,423066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almLow.Disabled,423066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almLow.Acked,423066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almLow.Alarm,423066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Fault,423076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almLowLow.AlarmState,423076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almLowLow.GlobalReset,423076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almLowLow.FaultInAlarm,423076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almLowLow.ALRM,423076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almLowLow.ANUN,423076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almLowLow.AKED,423076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almLowLow.Resetable,423076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almLowLow.REST,423076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almLowLow.ACKN,423076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almLowLow.UACK,423076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almLowLow.MCmd_Enable,423076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almLowLow.MCmd_Disable,423076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almLowLow.OCmd_Shelve,423076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almLowLow.OCmd_Unshelve,423076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almLowLow.SCmd_Suppress,423076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almLowLow.SCmd_UnSuppress,423077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almLowLow.AEShelveTMRDN,423077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almLowLow.Bad,423077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almLowLow.Suppress,423078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.UnSuppress,423078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Shelve,423078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.UnShelve,423078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Enable,423078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Disable,423078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Ack,423078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Reset,423078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Suppressed,423078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Shelved,423078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Disabled,423078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Acked,423078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almLowLow.Alarm,423078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Fault,423088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almBrokenLoop.AlarmState,423088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almBrokenLoop.GlobalReset,423088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almBrokenLoop.FaultInAlarm,423088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almBrokenLoop.ALRM,423088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almBrokenLoop.ANUN,423088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almBrokenLoop.AKED,423088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almBrokenLoop.Resetable,423088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almBrokenLoop.REST,423088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almBrokenLoop.ACKN,423088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almBrokenLoop.UACK,423088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almBrokenLoop.MCmd_Enable,423088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.MCmd_Disable,423088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.OCmd_Shelve,423088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.OCmd_Unshelve,423088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.SCmd_Suppress,423088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.SCmd_UnSuppress,423089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almBrokenLoop.AEShelveTMRDN,423089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almBrokenLoop.Bad,423089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almBrokenLoop.Suppress,423090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.UnSuppress,423090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Shelve,423090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.UnShelve,423090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Enable,423090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Disable,423090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Ack,423090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Reset,423090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Suppressed,423090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Shelved,423090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Disabled,423090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Acked,423090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.Alarm,423090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Fault,423100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almOverRange.AlarmState,423100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almOverRange.GlobalReset,423100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almOverRange.FaultInAlarm,423100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almOverRange.ALRM,423100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almOverRange.ANUN,423100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almOverRange.AKED,423100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almOverRange.Resetable,423100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almOverRange.REST,423100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almOverRange.ACKN,423100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almOverRange.UACK,423100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almOverRange.MCmd_Enable,423100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almOverRange.MCmd_Disable,423100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almOverRange.OCmd_Shelve,423100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almOverRange.OCmd_Unshelve,423100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almOverRange.SCmd_Suppress,423100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almOverRange.SCmd_UnSuppress,423101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almOverRange.AEShelveTMRDN,423101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almOverRange.Bad,423101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almOverRange.Suppress,423102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.UnSuppress,423102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Shelve,423102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.UnShelve,423102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Enable,423102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Disable,423102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Ack,423102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Reset,423102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Suppressed,423102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Shelved,423102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Disabled,423102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Acked,423102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almOverRange.Alarm,423102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Fault,423112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almUnderRange.AlarmState,423112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almUnderRange.GlobalReset,423112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almUnderRange.FaultInAlarm,423112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almUnderRange.ALRM,423112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almUnderRange.ANUN,423112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almUnderRange.AKED,423112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almUnderRange.Resetable,423112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almUnderRange.REST,423112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almUnderRange.ACKN,423112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almUnderRange.UACK,423112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almUnderRange.MCmd_Enable,423112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.MCmd_Disable,423112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.OCmd_Shelve,423112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.OCmd_Unshelve,423112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.SCmd_Suppress,423112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.SCmd_UnSuppress,423113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almUnderRange.AEShelveTMRDN,423113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almUnderRange.Bad,423113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almUnderRange.Suppress,423114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.UnSuppress,423114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Shelve,423114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.UnShelve,423114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Enable,423114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Disable,423114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Ack,423114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Reset,423114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Suppressed,423114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Shelved,423114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Disabled,423114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Acked,423114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almUnderRange.Alarm,423114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Fault,423124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almRateOfChange.AlarmState,423124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almRateOfChange.GlobalReset,423124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almRateOfChange.FaultInAlarm,423124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almRateOfChange.ALRM,423124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almRateOfChange.ANUN,423124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almRateOfChange.AKED,423124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almRateOfChange.Resetable,423124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almRateOfChange.REST,423124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almRateOfChange.ACKN,423124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almRateOfChange.UACK,423124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almRateOfChange.MCmd_Enable,423124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.MCmd_Disable,423124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.OCmd_Shelve,423124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.OCmd_Unshelve,423124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.SCmd_Suppress,423124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.SCmd_UnSuppress,423125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almRateOfChange.AEShelveTMRDN,423125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almRateOfChange.Bad,423125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almRateOfChange.Suppress,423126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.UnSuppress,423126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Shelve,423126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.UnShelve,423126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Enable,423126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Disable,423126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Ack,423126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Reset,423126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Suppressed,423126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Shelved,423126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Disabled,423126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Acked,423126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almRateOfChange.Alarm,423126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Fault,423136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI3.almPLCFault.AlarmState,423136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI3.almPLCFault.GlobalReset,423136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI3.almPLCFault.FaultInAlarm,423136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI3.almPLCFault.ALRM,423136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI3.almPLCFault.ANUN,423136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI3.almPLCFault.AKED,423136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI3.almPLCFault.Resetable,423136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI3.almPLCFault.REST,423136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI3.almPLCFault.ACKN,423136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI3.almPLCFault.UACK,423136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI3.almPLCFault.MCmd_Enable,423136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.MCmd_Disable,423136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.OCmd_Shelve,423136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.OCmd_Unshelve,423136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.SCmd_Suppress,423136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.SCmd_UnSuppress,423137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI3.almPLCFault.AEShelveTMRDN,423137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI3.almPLCFault.Bad,423137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI3.almPLCFault.Suppress,423138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.UnSuppress,423138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Shelve,423138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.UnShelve,423138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Enable,423138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Disable,423138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Ack,423138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Reset,423138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Suppressed,423138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Shelved,423138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Disabled,423138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Acked,423138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI3.almPLCFault.Alarm,423138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Fault,423240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almHighHigh.AlarmState,423240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almHighHigh.GlobalReset,423240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almHighHigh.FaultInAlarm,423240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almHighHigh.ALRM,423240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almHighHigh.ANUN,423240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almHighHigh.AKED,423240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almHighHigh.Resetable,423240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almHighHigh.REST,423240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almHighHigh.ACKN,423240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almHighHigh.UACK,423240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almHighHigh.MCmd_Enable,423240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.MCmd_Disable,423240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.OCmd_Shelve,423240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.OCmd_Unshelve,423240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.SCmd_Suppress,423240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.SCmd_UnSuppress,423241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almHighHigh.AEShelveTMRDN,423241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almHighHigh.Bad,423241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almHighHigh.Suppress,423242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.UnSuppress,423242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Shelve,423242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.UnShelve,423242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Enable,423242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Disable,423242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Ack,423242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Reset,423242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Suppressed,423242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Shelved,423242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Disabled,423242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Acked,423242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almHighHigh.Alarm,423242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Fault,423252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almHigh.AlarmState,423252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almHigh.GlobalReset,423252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almHigh.FaultInAlarm,423252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almHigh.ALRM,423252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almHigh.ANUN,423252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almHigh.AKED,423252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almHigh.Resetable,423252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almHigh.REST,423252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almHigh.ACKN,423252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almHigh.UACK,423252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almHigh.MCmd_Enable,423252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almHigh.MCmd_Disable,423252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almHigh.OCmd_Shelve,423252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almHigh.OCmd_Unshelve,423252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almHigh.SCmd_Suppress,423252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almHigh.SCmd_UnSuppress,423253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almHigh.AEShelveTMRDN,423253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almHigh.Bad,423253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almHigh.Suppress,423254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.UnSuppress,423254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Shelve,423254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.UnShelve,423254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Enable,423254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Disable,423254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Ack,423254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Reset,423254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almHigh.Suppressed,423254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almHigh.Shelved,423254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almHigh.Disabled,423254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almHigh.Acked,423254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almHigh.Alarm,423254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Fault,423264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almLow.AlarmState,423264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almLow.GlobalReset,423264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almLow.FaultInAlarm,423264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almLow.ALRM,423264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almLow.ANUN,423264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almLow.AKED,423264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almLow.Resetable,423264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almLow.REST,423264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almLow.ACKN,423264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almLow.UACK,423264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almLow.MCmd_Enable,423264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almLow.MCmd_Disable,423264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almLow.OCmd_Shelve,423264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almLow.OCmd_Unshelve,423264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almLow.SCmd_Suppress,423264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almLow.SCmd_UnSuppress,423265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almLow.AEShelveTMRDN,423265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almLow.Bad,423265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almLow.Suppress,423266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.UnSuppress,423266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Shelve,423266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.UnShelve,423266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Enable,423266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Disable,423266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Ack,423266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Reset,423266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almLow.Suppressed,423266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almLow.Shelved,423266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almLow.Disabled,423266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almLow.Acked,423266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almLow.Alarm,423266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Fault,423276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almLowLow.AlarmState,423276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almLowLow.GlobalReset,423276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almLowLow.FaultInAlarm,423276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almLowLow.ALRM,423276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almLowLow.ANUN,423276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almLowLow.AKED,423276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almLowLow.Resetable,423276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almLowLow.REST,423276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almLowLow.ACKN,423276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almLowLow.UACK,423276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almLowLow.MCmd_Enable,423276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almLowLow.MCmd_Disable,423276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almLowLow.OCmd_Shelve,423276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almLowLow.OCmd_Unshelve,423276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almLowLow.SCmd_Suppress,423276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almLowLow.SCmd_UnSuppress,423277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almLowLow.AEShelveTMRDN,423277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almLowLow.Bad,423277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almLowLow.Suppress,423278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.UnSuppress,423278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Shelve,423278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.UnShelve,423278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Enable,423278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Disable,423278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Ack,423278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Reset,423278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Suppressed,423278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Shelved,423278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Disabled,423278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Acked,423278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almLowLow.Alarm,423278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Fault,423288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almBrokenLoop.AlarmState,423288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almBrokenLoop.GlobalReset,423288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almBrokenLoop.FaultInAlarm,423288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almBrokenLoop.ALRM,423288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almBrokenLoop.ANUN,423288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almBrokenLoop.AKED,423288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almBrokenLoop.Resetable,423288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almBrokenLoop.REST,423288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almBrokenLoop.ACKN,423288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almBrokenLoop.UACK,423288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almBrokenLoop.MCmd_Enable,423288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.MCmd_Disable,423288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.OCmd_Shelve,423288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.OCmd_Unshelve,423288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.SCmd_Suppress,423288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.SCmd_UnSuppress,423289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almBrokenLoop.AEShelveTMRDN,423289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almBrokenLoop.Bad,423289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almBrokenLoop.Suppress,423290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.UnSuppress,423290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Shelve,423290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.UnShelve,423290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Enable,423290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Disable,423290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Ack,423290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Reset,423290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Suppressed,423290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Shelved,423290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Disabled,423290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Acked,423290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.Alarm,423290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Fault,423300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almOverRange.AlarmState,423300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almOverRange.GlobalReset,423300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almOverRange.FaultInAlarm,423300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almOverRange.ALRM,423300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almOverRange.ANUN,423300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almOverRange.AKED,423300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almOverRange.Resetable,423300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almOverRange.REST,423300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almOverRange.ACKN,423300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almOverRange.UACK,423300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almOverRange.MCmd_Enable,423300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almOverRange.MCmd_Disable,423300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almOverRange.OCmd_Shelve,423300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almOverRange.OCmd_Unshelve,423300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almOverRange.SCmd_Suppress,423300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almOverRange.SCmd_UnSuppress,423301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almOverRange.AEShelveTMRDN,423301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almOverRange.Bad,423301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almOverRange.Suppress,423302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.UnSuppress,423302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Shelve,423302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.UnShelve,423302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Enable,423302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Disable,423302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Ack,423302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Reset,423302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Suppressed,423302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Shelved,423302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Disabled,423302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Acked,423302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almOverRange.Alarm,423302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Fault,423312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almUnderRange.AlarmState,423312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almUnderRange.GlobalReset,423312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almUnderRange.FaultInAlarm,423312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almUnderRange.ALRM,423312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almUnderRange.ANUN,423312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almUnderRange.AKED,423312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almUnderRange.Resetable,423312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almUnderRange.REST,423312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almUnderRange.ACKN,423312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almUnderRange.UACK,423312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almUnderRange.MCmd_Enable,423312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.MCmd_Disable,423312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.OCmd_Shelve,423312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.OCmd_Unshelve,423312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.SCmd_Suppress,423312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.SCmd_UnSuppress,423313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almUnderRange.AEShelveTMRDN,423313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almUnderRange.Bad,423313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almUnderRange.Suppress,423314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.UnSuppress,423314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Shelve,423314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.UnShelve,423314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Enable,423314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Disable,423314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Ack,423314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Reset,423314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Suppressed,423314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Shelved,423314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Disabled,423314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Acked,423314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almUnderRange.Alarm,423314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Fault,423324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almRateOfChange.AlarmState,423324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almRateOfChange.GlobalReset,423324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almRateOfChange.FaultInAlarm,423324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almRateOfChange.ALRM,423324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almRateOfChange.ANUN,423324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almRateOfChange.AKED,423324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almRateOfChange.Resetable,423324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almRateOfChange.REST,423324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almRateOfChange.ACKN,423324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almRateOfChange.UACK,423324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almRateOfChange.MCmd_Enable,423324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.MCmd_Disable,423324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.OCmd_Shelve,423324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.OCmd_Unshelve,423324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.SCmd_Suppress,423324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.SCmd_UnSuppress,423325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almRateOfChange.AEShelveTMRDN,423325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almRateOfChange.Bad,423325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almRateOfChange.Suppress,423326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.UnSuppress,423326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Shelve,423326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.UnShelve,423326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Enable,423326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Disable,423326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Ack,423326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Reset,423326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Suppressed,423326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Shelved,423326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Disabled,423326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Acked,423326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almRateOfChange.Alarm,423326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Fault,423336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI4.almPLCFault.AlarmState,423336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI4.almPLCFault.GlobalReset,423336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI4.almPLCFault.FaultInAlarm,423336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI4.almPLCFault.ALRM,423336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI4.almPLCFault.ANUN,423336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI4.almPLCFault.AKED,423336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI4.almPLCFault.Resetable,423336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI4.almPLCFault.REST,423336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI4.almPLCFault.ACKN,423336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI4.almPLCFault.UACK,423336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI4.almPLCFault.MCmd_Enable,423336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.MCmd_Disable,423336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.OCmd_Shelve,423336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.OCmd_Unshelve,423336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.SCmd_Suppress,423336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.SCmd_UnSuppress,423337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI4.almPLCFault.AEShelveTMRDN,423337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI4.almPLCFault.Bad,423337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI4.almPLCFault.Suppress,423338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.UnSuppress,423338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Shelve,423338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.UnShelve,423338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Enable,423338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Disable,423338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Ack,423338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Reset,423338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Suppressed,423338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Shelved,423338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Disabled,423338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Acked,423338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI4.almPLCFault.Alarm,423338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Fault,423440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almHighHigh.AlarmState,423440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almHighHigh.GlobalReset,423440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almHighHigh.FaultInAlarm,423440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almHighHigh.ALRM,423440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almHighHigh.ANUN,423440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almHighHigh.AKED,423440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almHighHigh.Resetable,423440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almHighHigh.REST,423440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almHighHigh.ACKN,423440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almHighHigh.UACK,423440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almHighHigh.MCmd_Enable,423440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.MCmd_Disable,423440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.OCmd_Shelve,423440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.OCmd_Unshelve,423440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.SCmd_Suppress,423440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.SCmd_UnSuppress,423441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almHighHigh.AEShelveTMRDN,423441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almHighHigh.Bad,423441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almHighHigh.Suppress,423442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.UnSuppress,423442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Shelve,423442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.UnShelve,423442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Enable,423442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Disable,423442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Ack,423442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Reset,423442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Suppressed,423442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Shelved,423442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Disabled,423442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Acked,423442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almHighHigh.Alarm,423442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Fault,423452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almHigh.AlarmState,423452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almHigh.GlobalReset,423452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almHigh.FaultInAlarm,423452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almHigh.ALRM,423452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almHigh.ANUN,423452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almHigh.AKED,423452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almHigh.Resetable,423452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almHigh.REST,423452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almHigh.ACKN,423452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almHigh.UACK,423452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almHigh.MCmd_Enable,423452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almHigh.MCmd_Disable,423452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almHigh.OCmd_Shelve,423452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almHigh.OCmd_Unshelve,423452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almHigh.SCmd_Suppress,423452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almHigh.SCmd_UnSuppress,423453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almHigh.AEShelveTMRDN,423453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almHigh.Bad,423453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almHigh.Suppress,423454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.UnSuppress,423454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Shelve,423454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.UnShelve,423454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Enable,423454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Disable,423454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Ack,423454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Reset,423454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almHigh.Suppressed,423454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almHigh.Shelved,423454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almHigh.Disabled,423454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almHigh.Acked,423454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almHigh.Alarm,423454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Fault,423464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almLow.AlarmState,423464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almLow.GlobalReset,423464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almLow.FaultInAlarm,423464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almLow.ALRM,423464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almLow.ANUN,423464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almLow.AKED,423464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almLow.Resetable,423464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almLow.REST,423464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almLow.ACKN,423464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almLow.UACK,423464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almLow.MCmd_Enable,423464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almLow.MCmd_Disable,423464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almLow.OCmd_Shelve,423464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almLow.OCmd_Unshelve,423464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almLow.SCmd_Suppress,423464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almLow.SCmd_UnSuppress,423465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almLow.AEShelveTMRDN,423465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almLow.Bad,423465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almLow.Suppress,423466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.UnSuppress,423466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Shelve,423466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.UnShelve,423466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Enable,423466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Disable,423466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Ack,423466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Reset,423466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almLow.Suppressed,423466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almLow.Shelved,423466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almLow.Disabled,423466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almLow.Acked,423466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almLow.Alarm,423466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Fault,423476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almLowLow.AlarmState,423476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almLowLow.GlobalReset,423476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almLowLow.FaultInAlarm,423476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almLowLow.ALRM,423476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almLowLow.ANUN,423476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almLowLow.AKED,423476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almLowLow.Resetable,423476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almLowLow.REST,423476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almLowLow.ACKN,423476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almLowLow.UACK,423476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almLowLow.MCmd_Enable,423476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almLowLow.MCmd_Disable,423476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almLowLow.OCmd_Shelve,423476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almLowLow.OCmd_Unshelve,423476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almLowLow.SCmd_Suppress,423476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almLowLow.SCmd_UnSuppress,423477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almLowLow.AEShelveTMRDN,423477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almLowLow.Bad,423477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almLowLow.Suppress,423478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.UnSuppress,423478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Shelve,423478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.UnShelve,423478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Enable,423478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Disable,423478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Ack,423478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Reset,423478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Suppressed,423478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Shelved,423478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Disabled,423478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Acked,423478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almLowLow.Alarm,423478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Fault,423488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almBrokenLoop.AlarmState,423488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almBrokenLoop.GlobalReset,423488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almBrokenLoop.FaultInAlarm,423488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almBrokenLoop.ALRM,423488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almBrokenLoop.ANUN,423488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almBrokenLoop.AKED,423488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almBrokenLoop.Resetable,423488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almBrokenLoop.REST,423488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almBrokenLoop.ACKN,423488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almBrokenLoop.UACK,423488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almBrokenLoop.MCmd_Enable,423488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.MCmd_Disable,423488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.OCmd_Shelve,423488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.OCmd_Unshelve,423488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.SCmd_Suppress,423488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.SCmd_UnSuppress,423489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almBrokenLoop.AEShelveTMRDN,423489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almBrokenLoop.Bad,423489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almBrokenLoop.Suppress,423490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.UnSuppress,423490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Shelve,423490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.UnShelve,423490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Enable,423490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Disable,423490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Ack,423490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Reset,423490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Suppressed,423490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Shelved,423490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Disabled,423490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Acked,423490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.Alarm,423490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Fault,423500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almOverRange.AlarmState,423500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almOverRange.GlobalReset,423500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almOverRange.FaultInAlarm,423500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almOverRange.ALRM,423500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almOverRange.ANUN,423500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almOverRange.AKED,423500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almOverRange.Resetable,423500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almOverRange.REST,423500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almOverRange.ACKN,423500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almOverRange.UACK,423500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almOverRange.MCmd_Enable,423500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almOverRange.MCmd_Disable,423500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almOverRange.OCmd_Shelve,423500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almOverRange.OCmd_Unshelve,423500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almOverRange.SCmd_Suppress,423500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almOverRange.SCmd_UnSuppress,423501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almOverRange.AEShelveTMRDN,423501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almOverRange.Bad,423501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almOverRange.Suppress,423502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.UnSuppress,423502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Shelve,423502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.UnShelve,423502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Enable,423502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Disable,423502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Ack,423502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Reset,423502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Suppressed,423502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Shelved,423502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Disabled,423502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Acked,423502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almOverRange.Alarm,423502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Fault,423512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almUnderRange.AlarmState,423512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almUnderRange.GlobalReset,423512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almUnderRange.FaultInAlarm,423512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almUnderRange.ALRM,423512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almUnderRange.ANUN,423512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almUnderRange.AKED,423512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almUnderRange.Resetable,423512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almUnderRange.REST,423512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almUnderRange.ACKN,423512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almUnderRange.UACK,423512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almUnderRange.MCmd_Enable,423512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.MCmd_Disable,423512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.OCmd_Shelve,423512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.OCmd_Unshelve,423512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.SCmd_Suppress,423512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.SCmd_UnSuppress,423513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almUnderRange.AEShelveTMRDN,423513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almUnderRange.Bad,423513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almUnderRange.Suppress,423514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.UnSuppress,423514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Shelve,423514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.UnShelve,423514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Enable,423514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Disable,423514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Ack,423514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Reset,423514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Suppressed,423514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Shelved,423514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Disabled,423514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Acked,423514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almUnderRange.Alarm,423514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Fault,423524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almRateOfChange.AlarmState,423524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almRateOfChange.GlobalReset,423524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almRateOfChange.FaultInAlarm,423524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almRateOfChange.ALRM,423524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almRateOfChange.ANUN,423524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almRateOfChange.AKED,423524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almRateOfChange.Resetable,423524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almRateOfChange.REST,423524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almRateOfChange.ACKN,423524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almRateOfChange.UACK,423524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almRateOfChange.MCmd_Enable,423524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.MCmd_Disable,423524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.OCmd_Shelve,423524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.OCmd_Unshelve,423524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.SCmd_Suppress,423524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.SCmd_UnSuppress,423525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almRateOfChange.AEShelveTMRDN,423525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almRateOfChange.Bad,423525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almRateOfChange.Suppress,423526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.UnSuppress,423526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Shelve,423526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.UnShelve,423526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Enable,423526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Disable,423526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Ack,423526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Reset,423526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Suppressed,423526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Shelved,423526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Disabled,423526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Acked,423526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almRateOfChange.Alarm,423526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Fault,423536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_7_VI5.almPLCFault.AlarmState,423536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_7_VI5.almPLCFault.GlobalReset,423536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_7_VI5.almPLCFault.FaultInAlarm,423536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_7_VI5.almPLCFault.ALRM,423536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_7_VI5.almPLCFault.ANUN,423536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_7_VI5.almPLCFault.AKED,423536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_7_VI5.almPLCFault.Resetable,423536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_7_VI5.almPLCFault.REST,423536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_7_VI5.almPLCFault.ACKN,423536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_7_VI5.almPLCFault.UACK,423536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_7_VI5.almPLCFault.MCmd_Enable,423536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.MCmd_Disable,423536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.OCmd_Shelve,423536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.OCmd_Unshelve,423536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.SCmd_Suppress,423536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.SCmd_UnSuppress,423537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_7_VI5.almPLCFault.AEShelveTMRDN,423537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_7_VI5.almPLCFault.Bad,423537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_7_VI5.almPLCFault.Suppress,423538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.UnSuppress,423538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Shelve,423538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.UnShelve,423538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Enable,423538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Disable,423538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Ack,423538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Reset,423538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Suppressed,423538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Shelved,423538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Disabled,423538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Acked,423538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_7_VI5.almPLCFault.Alarm,423538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Fault,423640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almHighHigh.AlarmState,423640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almHighHigh.GlobalReset,423640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almHighHigh.FaultInAlarm,423640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almHighHigh.ALRM,423640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almHighHigh.ANUN,423640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almHighHigh.AKED,423640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almHighHigh.Resetable,423640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almHighHigh.REST,423640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almHighHigh.ACKN,423640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almHighHigh.UACK,423640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almHighHigh.MCmd_Enable,423640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.MCmd_Disable,423640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.OCmd_Shelve,423640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.OCmd_Unshelve,423640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.SCmd_Suppress,423640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.SCmd_UnSuppress,423641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almHighHigh.AEShelveTMRDN,423641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almHighHigh.Bad,423641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almHighHigh.Suppress,423642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.UnSuppress,423642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Shelve,423642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.UnShelve,423642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Enable,423642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Disable,423642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Ack,423642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Reset,423642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Suppressed,423642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Shelved,423642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Disabled,423642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Acked,423642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almHighHigh.Alarm,423642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Fault,423652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almHigh.AlarmState,423652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almHigh.GlobalReset,423652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almHigh.FaultInAlarm,423652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almHigh.ALRM,423652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almHigh.ANUN,423652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almHigh.AKED,423652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almHigh.Resetable,423652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almHigh.REST,423652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almHigh.ACKN,423652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almHigh.UACK,423652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almHigh.MCmd_Enable,423652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almHigh.MCmd_Disable,423652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almHigh.OCmd_Shelve,423652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almHigh.OCmd_Unshelve,423652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almHigh.SCmd_Suppress,423652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almHigh.SCmd_UnSuppress,423653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almHigh.AEShelveTMRDN,423653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almHigh.Bad,423653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almHigh.Suppress,423654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.UnSuppress,423654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Shelve,423654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.UnShelve,423654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Enable,423654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Disable,423654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Ack,423654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Reset,423654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almHigh.Suppressed,423654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almHigh.Shelved,423654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almHigh.Disabled,423654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almHigh.Acked,423654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almHigh.Alarm,423654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Fault,423664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almLow.AlarmState,423664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almLow.GlobalReset,423664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almLow.FaultInAlarm,423664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almLow.ALRM,423664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almLow.ANUN,423664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almLow.AKED,423664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almLow.Resetable,423664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almLow.REST,423664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almLow.ACKN,423664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almLow.UACK,423664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almLow.MCmd_Enable,423664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almLow.MCmd_Disable,423664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almLow.OCmd_Shelve,423664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almLow.OCmd_Unshelve,423664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almLow.SCmd_Suppress,423664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almLow.SCmd_UnSuppress,423665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almLow.AEShelveTMRDN,423665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almLow.Bad,423665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almLow.Suppress,423666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.UnSuppress,423666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Shelve,423666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.UnShelve,423666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Enable,423666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Disable,423666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Ack,423666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Reset,423666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almLow.Suppressed,423666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almLow.Shelved,423666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almLow.Disabled,423666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almLow.Acked,423666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almLow.Alarm,423666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Fault,423676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almLowLow.AlarmState,423676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almLowLow.GlobalReset,423676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almLowLow.FaultInAlarm,423676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almLowLow.ALRM,423676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almLowLow.ANUN,423676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almLowLow.AKED,423676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almLowLow.Resetable,423676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almLowLow.REST,423676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almLowLow.ACKN,423676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almLowLow.UACK,423676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almLowLow.MCmd_Enable,423676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almLowLow.MCmd_Disable,423676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almLowLow.OCmd_Shelve,423676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almLowLow.OCmd_Unshelve,423676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almLowLow.SCmd_Suppress,423676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almLowLow.SCmd_UnSuppress,423677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almLowLow.AEShelveTMRDN,423677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almLowLow.Bad,423677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almLowLow.Suppress,423678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.UnSuppress,423678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Shelve,423678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.UnShelve,423678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Enable,423678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Disable,423678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Ack,423678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Reset,423678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Suppressed,423678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Shelved,423678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Disabled,423678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Acked,423678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almLowLow.Alarm,423678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Fault,423688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almBrokenLoop.AlarmState,423688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almBrokenLoop.GlobalReset,423688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almBrokenLoop.FaultInAlarm,423688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almBrokenLoop.ALRM,423688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almBrokenLoop.ANUN,423688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almBrokenLoop.AKED,423688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almBrokenLoop.Resetable,423688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almBrokenLoop.REST,423688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almBrokenLoop.ACKN,423688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almBrokenLoop.UACK,423688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almBrokenLoop.MCmd_Enable,423688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.MCmd_Disable,423688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.OCmd_Shelve,423688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.OCmd_Unshelve,423688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.SCmd_Suppress,423688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.SCmd_UnSuppress,423689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almBrokenLoop.AEShelveTMRDN,423689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almBrokenLoop.Bad,423689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almBrokenLoop.Suppress,423690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.UnSuppress,423690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Shelve,423690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.UnShelve,423690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Enable,423690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Disable,423690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Ack,423690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Reset,423690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Suppressed,423690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Shelved,423690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Disabled,423690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Acked,423690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.Alarm,423690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Fault,423700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almOverRange.AlarmState,423700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almOverRange.GlobalReset,423700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almOverRange.FaultInAlarm,423700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almOverRange.ALRM,423700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almOverRange.ANUN,423700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almOverRange.AKED,423700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almOverRange.Resetable,423700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almOverRange.REST,423700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almOverRange.ACKN,423700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almOverRange.UACK,423700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almOverRange.MCmd_Enable,423700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almOverRange.MCmd_Disable,423700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almOverRange.OCmd_Shelve,423700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almOverRange.OCmd_Unshelve,423700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almOverRange.SCmd_Suppress,423700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almOverRange.SCmd_UnSuppress,423701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almOverRange.AEShelveTMRDN,423701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almOverRange.Bad,423701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almOverRange.Suppress,423702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.UnSuppress,423702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Shelve,423702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.UnShelve,423702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Enable,423702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Disable,423702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Ack,423702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Reset,423702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Suppressed,423702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Shelved,423702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Disabled,423702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Acked,423702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almOverRange.Alarm,423702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Fault,423712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almUnderRange.AlarmState,423712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almUnderRange.GlobalReset,423712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almUnderRange.FaultInAlarm,423712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almUnderRange.ALRM,423712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almUnderRange.ANUN,423712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almUnderRange.AKED,423712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almUnderRange.Resetable,423712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almUnderRange.REST,423712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almUnderRange.ACKN,423712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almUnderRange.UACK,423712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almUnderRange.MCmd_Enable,423712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.MCmd_Disable,423712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.OCmd_Shelve,423712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.OCmd_Unshelve,423712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.SCmd_Suppress,423712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.SCmd_UnSuppress,423713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almUnderRange.AEShelveTMRDN,423713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almUnderRange.Bad,423713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almUnderRange.Suppress,423714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.UnSuppress,423714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Shelve,423714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.UnShelve,423714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Enable,423714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Disable,423714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Ack,423714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Reset,423714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Suppressed,423714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Shelved,423714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Disabled,423714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Acked,423714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almUnderRange.Alarm,423714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Fault,423724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almRateOfChange.AlarmState,423724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almRateOfChange.GlobalReset,423724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almRateOfChange.FaultInAlarm,423724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almRateOfChange.ALRM,423724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almRateOfChange.ANUN,423724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almRateOfChange.AKED,423724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almRateOfChange.Resetable,423724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almRateOfChange.REST,423724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almRateOfChange.ACKN,423724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almRateOfChange.UACK,423724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almRateOfChange.MCmd_Enable,423724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.MCmd_Disable,423724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.OCmd_Shelve,423724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.OCmd_Unshelve,423724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.SCmd_Suppress,423724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.SCmd_UnSuppress,423725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almRateOfChange.AEShelveTMRDN,423725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almRateOfChange.Bad,423725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almRateOfChange.Suppress,423726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.UnSuppress,423726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Shelve,423726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.UnShelve,423726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Enable,423726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Disable,423726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Ack,423726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Reset,423726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Suppressed,423726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Shelved,423726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Disabled,423726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Acked,423726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almRateOfChange.Alarm,423726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Fault,423736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI1.almPLCFault.AlarmState,423736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI1.almPLCFault.GlobalReset,423736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI1.almPLCFault.FaultInAlarm,423736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI1.almPLCFault.ALRM,423736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI1.almPLCFault.ANUN,423736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI1.almPLCFault.AKED,423736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI1.almPLCFault.Resetable,423736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI1.almPLCFault.REST,423736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI1.almPLCFault.ACKN,423736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI1.almPLCFault.UACK,423736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI1.almPLCFault.MCmd_Enable,423736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.MCmd_Disable,423736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.OCmd_Shelve,423736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.OCmd_Unshelve,423736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.SCmd_Suppress,423736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.SCmd_UnSuppress,423737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI1.almPLCFault.AEShelveTMRDN,423737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI1.almPLCFault.Bad,423737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI1.almPLCFault.Suppress,423738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.UnSuppress,423738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Shelve,423738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.UnShelve,423738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Enable,423738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Disable,423738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Ack,423738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Reset,423738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Suppressed,423738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Shelved,423738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Disabled,423738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Acked,423738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI1.almPLCFault.Alarm,423738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Fault,423840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almHighHigh.AlarmState,423840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almHighHigh.GlobalReset,423840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almHighHigh.FaultInAlarm,423840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almHighHigh.ALRM,423840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almHighHigh.ANUN,423840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almHighHigh.AKED,423840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almHighHigh.Resetable,423840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almHighHigh.REST,423840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almHighHigh.ACKN,423840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almHighHigh.UACK,423840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almHighHigh.MCmd_Enable,423840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.MCmd_Disable,423840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.OCmd_Shelve,423840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.OCmd_Unshelve,423840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.SCmd_Suppress,423840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.SCmd_UnSuppress,423841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almHighHigh.AEShelveTMRDN,423841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almHighHigh.Bad,423841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almHighHigh.Suppress,423842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.UnSuppress,423842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Shelve,423842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.UnShelve,423842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Enable,423842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Disable,423842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Ack,423842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Reset,423842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Suppressed,423842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Shelved,423842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Disabled,423842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Acked,423842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almHighHigh.Alarm,423842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Fault,423852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almHigh.AlarmState,423852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almHigh.GlobalReset,423852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almHigh.FaultInAlarm,423852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almHigh.ALRM,423852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almHigh.ANUN,423852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almHigh.AKED,423852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almHigh.Resetable,423852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almHigh.REST,423852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almHigh.ACKN,423852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almHigh.UACK,423852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almHigh.MCmd_Enable,423852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almHigh.MCmd_Disable,423852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almHigh.OCmd_Shelve,423852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almHigh.OCmd_Unshelve,423852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almHigh.SCmd_Suppress,423852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almHigh.SCmd_UnSuppress,423853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almHigh.AEShelveTMRDN,423853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almHigh.Bad,423853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almHigh.Suppress,423854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.UnSuppress,423854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Shelve,423854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.UnShelve,423854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Enable,423854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Disable,423854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Ack,423854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Reset,423854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almHigh.Suppressed,423854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almHigh.Shelved,423854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almHigh.Disabled,423854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almHigh.Acked,423854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almHigh.Alarm,423854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Fault,423864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almLow.AlarmState,423864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almLow.GlobalReset,423864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almLow.FaultInAlarm,423864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almLow.ALRM,423864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almLow.ANUN,423864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almLow.AKED,423864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almLow.Resetable,423864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almLow.REST,423864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almLow.ACKN,423864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almLow.UACK,423864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almLow.MCmd_Enable,423864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almLow.MCmd_Disable,423864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almLow.OCmd_Shelve,423864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almLow.OCmd_Unshelve,423864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almLow.SCmd_Suppress,423864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almLow.SCmd_UnSuppress,423865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almLow.AEShelveTMRDN,423865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almLow.Bad,423865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almLow.Suppress,423866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.UnSuppress,423866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Shelve,423866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.UnShelve,423866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Enable,423866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Disable,423866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Ack,423866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Reset,423866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almLow.Suppressed,423866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almLow.Shelved,423866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almLow.Disabled,423866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almLow.Acked,423866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almLow.Alarm,423866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Fault,423876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almLowLow.AlarmState,423876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almLowLow.GlobalReset,423876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almLowLow.FaultInAlarm,423876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almLowLow.ALRM,423876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almLowLow.ANUN,423876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almLowLow.AKED,423876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almLowLow.Resetable,423876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almLowLow.REST,423876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almLowLow.ACKN,423876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almLowLow.UACK,423876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almLowLow.MCmd_Enable,423876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almLowLow.MCmd_Disable,423876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almLowLow.OCmd_Shelve,423876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almLowLow.OCmd_Unshelve,423876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almLowLow.SCmd_Suppress,423876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almLowLow.SCmd_UnSuppress,423877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almLowLow.AEShelveTMRDN,423877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almLowLow.Bad,423877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almLowLow.Suppress,423878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.UnSuppress,423878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Shelve,423878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.UnShelve,423878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Enable,423878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Disable,423878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Ack,423878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Reset,423878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Suppressed,423878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Shelved,423878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Disabled,423878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Acked,423878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almLowLow.Alarm,423878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Fault,423888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almBrokenLoop.AlarmState,423888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almBrokenLoop.GlobalReset,423888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almBrokenLoop.FaultInAlarm,423888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almBrokenLoop.ALRM,423888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almBrokenLoop.ANUN,423888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almBrokenLoop.AKED,423888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almBrokenLoop.Resetable,423888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almBrokenLoop.REST,423888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almBrokenLoop.ACKN,423888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almBrokenLoop.UACK,423888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almBrokenLoop.MCmd_Enable,423888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.MCmd_Disable,423888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.OCmd_Shelve,423888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.OCmd_Unshelve,423888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.SCmd_Suppress,423888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.SCmd_UnSuppress,423889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almBrokenLoop.AEShelveTMRDN,423889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almBrokenLoop.Bad,423889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almBrokenLoop.Suppress,423890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.UnSuppress,423890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Shelve,423890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.UnShelve,423890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Enable,423890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Disable,423890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Ack,423890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Reset,423890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Suppressed,423890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Shelved,423890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Disabled,423890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Acked,423890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.Alarm,423890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Fault,423900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almOverRange.AlarmState,423900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almOverRange.GlobalReset,423900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almOverRange.FaultInAlarm,423900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almOverRange.ALRM,423900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almOverRange.ANUN,423900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almOverRange.AKED,423900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almOverRange.Resetable,423900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almOverRange.REST,423900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almOverRange.ACKN,423900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almOverRange.UACK,423900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almOverRange.MCmd_Enable,423900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almOverRange.MCmd_Disable,423900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almOverRange.OCmd_Shelve,423900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almOverRange.OCmd_Unshelve,423900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almOverRange.SCmd_Suppress,423900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almOverRange.SCmd_UnSuppress,423901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almOverRange.AEShelveTMRDN,423901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almOverRange.Bad,423901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almOverRange.Suppress,423902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.UnSuppress,423902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Shelve,423902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.UnShelve,423902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Enable,423902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Disable,423902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Ack,423902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Reset,423902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Suppressed,423902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Shelved,423902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Disabled,423902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Acked,423902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almOverRange.Alarm,423902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Fault,423912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almUnderRange.AlarmState,423912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almUnderRange.GlobalReset,423912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almUnderRange.FaultInAlarm,423912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almUnderRange.ALRM,423912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almUnderRange.ANUN,423912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almUnderRange.AKED,423912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almUnderRange.Resetable,423912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almUnderRange.REST,423912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almUnderRange.ACKN,423912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almUnderRange.UACK,423912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almUnderRange.MCmd_Enable,423912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.MCmd_Disable,423912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.OCmd_Shelve,423912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.OCmd_Unshelve,423912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.SCmd_Suppress,423912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.SCmd_UnSuppress,423913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almUnderRange.AEShelveTMRDN,423913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almUnderRange.Bad,423913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almUnderRange.Suppress,423914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.UnSuppress,423914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Shelve,423914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.UnShelve,423914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Enable,423914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Disable,423914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Ack,423914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Reset,423914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Suppressed,423914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Shelved,423914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Disabled,423914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Acked,423914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almUnderRange.Alarm,423914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Fault,423924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almRateOfChange.AlarmState,423924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almRateOfChange.GlobalReset,423924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almRateOfChange.FaultInAlarm,423924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almRateOfChange.ALRM,423924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almRateOfChange.ANUN,423924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almRateOfChange.AKED,423924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almRateOfChange.Resetable,423924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almRateOfChange.REST,423924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almRateOfChange.ACKN,423924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almRateOfChange.UACK,423924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almRateOfChange.MCmd_Enable,423924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.MCmd_Disable,423924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.OCmd_Shelve,423924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.OCmd_Unshelve,423924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.SCmd_Suppress,423924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.SCmd_UnSuppress,423925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almRateOfChange.AEShelveTMRDN,423925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almRateOfChange.Bad,423925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almRateOfChange.Suppress,423926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.UnSuppress,423926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Shelve,423926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.UnShelve,423926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Enable,423926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Disable,423926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Ack,423926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Reset,423926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Suppressed,423926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Shelved,423926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Disabled,423926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Acked,423926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almRateOfChange.Alarm,423926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Fault,423936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI2.almPLCFault.AlarmState,423936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI2.almPLCFault.GlobalReset,423936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI2.almPLCFault.FaultInAlarm,423936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI2.almPLCFault.ALRM,423936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI2.almPLCFault.ANUN,423936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI2.almPLCFault.AKED,423936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI2.almPLCFault.Resetable,423936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI2.almPLCFault.REST,423936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI2.almPLCFault.ACKN,423936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI2.almPLCFault.UACK,423936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI2.almPLCFault.MCmd_Enable,423936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.MCmd_Disable,423936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.OCmd_Shelve,423936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.OCmd_Unshelve,423936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.SCmd_Suppress,423936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.SCmd_UnSuppress,423937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI2.almPLCFault.AEShelveTMRDN,423937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI2.almPLCFault.Bad,423937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI2.almPLCFault.Suppress,423938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.UnSuppress,423938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Shelve,423938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.UnShelve,423938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Enable,423938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Disable,423938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Ack,423938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Reset,423938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Suppressed,423938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Shelved,423938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Disabled,423938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Acked,423938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI2.almPLCFault.Alarm,423938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Fault,424040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almHighHigh.AlarmState,424040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almHighHigh.GlobalReset,424040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almHighHigh.FaultInAlarm,424040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almHighHigh.ALRM,424040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almHighHigh.ANUN,424040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almHighHigh.AKED,424040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almHighHigh.Resetable,424040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almHighHigh.REST,424040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almHighHigh.ACKN,424040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almHighHigh.UACK,424040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almHighHigh.MCmd_Enable,424040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.MCmd_Disable,424040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.OCmd_Shelve,424040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.OCmd_Unshelve,424040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.SCmd_Suppress,424040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.SCmd_UnSuppress,424041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almHighHigh.AEShelveTMRDN,424041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almHighHigh.Bad,424041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almHighHigh.Suppress,424042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.UnSuppress,424042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Shelve,424042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.UnShelve,424042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Enable,424042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Disable,424042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Ack,424042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Reset,424042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Suppressed,424042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Shelved,424042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Disabled,424042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Acked,424042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almHighHigh.Alarm,424042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Fault,424052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almHigh.AlarmState,424052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almHigh.GlobalReset,424052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almHigh.FaultInAlarm,424052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almHigh.ALRM,424052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almHigh.ANUN,424052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almHigh.AKED,424052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almHigh.Resetable,424052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almHigh.REST,424052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almHigh.ACKN,424052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almHigh.UACK,424052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almHigh.MCmd_Enable,424052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almHigh.MCmd_Disable,424052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almHigh.OCmd_Shelve,424052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almHigh.OCmd_Unshelve,424052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almHigh.SCmd_Suppress,424052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almHigh.SCmd_UnSuppress,424053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almHigh.AEShelveTMRDN,424053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almHigh.Bad,424053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almHigh.Suppress,424054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.UnSuppress,424054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Shelve,424054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.UnShelve,424054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Enable,424054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Disable,424054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Ack,424054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Reset,424054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almHigh.Suppressed,424054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almHigh.Shelved,424054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almHigh.Disabled,424054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almHigh.Acked,424054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almHigh.Alarm,424054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Fault,424064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almLow.AlarmState,424064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almLow.GlobalReset,424064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almLow.FaultInAlarm,424064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almLow.ALRM,424064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almLow.ANUN,424064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almLow.AKED,424064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almLow.Resetable,424064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almLow.REST,424064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almLow.ACKN,424064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almLow.UACK,424064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almLow.MCmd_Enable,424064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almLow.MCmd_Disable,424064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almLow.OCmd_Shelve,424064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almLow.OCmd_Unshelve,424064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almLow.SCmd_Suppress,424064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almLow.SCmd_UnSuppress,424065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almLow.AEShelveTMRDN,424065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almLow.Bad,424065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almLow.Suppress,424066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.UnSuppress,424066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Shelve,424066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.UnShelve,424066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Enable,424066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Disable,424066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Ack,424066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Reset,424066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almLow.Suppressed,424066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almLow.Shelved,424066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almLow.Disabled,424066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almLow.Acked,424066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almLow.Alarm,424066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Fault,424076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almLowLow.AlarmState,424076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almLowLow.GlobalReset,424076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almLowLow.FaultInAlarm,424076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almLowLow.ALRM,424076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almLowLow.ANUN,424076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almLowLow.AKED,424076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almLowLow.Resetable,424076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almLowLow.REST,424076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almLowLow.ACKN,424076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almLowLow.UACK,424076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almLowLow.MCmd_Enable,424076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almLowLow.MCmd_Disable,424076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almLowLow.OCmd_Shelve,424076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almLowLow.OCmd_Unshelve,424076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almLowLow.SCmd_Suppress,424076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almLowLow.SCmd_UnSuppress,424077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almLowLow.AEShelveTMRDN,424077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almLowLow.Bad,424077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almLowLow.Suppress,424078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.UnSuppress,424078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Shelve,424078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.UnShelve,424078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Enable,424078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Disable,424078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Ack,424078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Reset,424078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Suppressed,424078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Shelved,424078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Disabled,424078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Acked,424078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almLowLow.Alarm,424078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Fault,424088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almBrokenLoop.AlarmState,424088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almBrokenLoop.GlobalReset,424088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almBrokenLoop.FaultInAlarm,424088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almBrokenLoop.ALRM,424088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almBrokenLoop.ANUN,424088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almBrokenLoop.AKED,424088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almBrokenLoop.Resetable,424088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almBrokenLoop.REST,424088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almBrokenLoop.ACKN,424088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almBrokenLoop.UACK,424088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almBrokenLoop.MCmd_Enable,424088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.MCmd_Disable,424088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.OCmd_Shelve,424088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.OCmd_Unshelve,424088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.SCmd_Suppress,424088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.SCmd_UnSuppress,424089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almBrokenLoop.AEShelveTMRDN,424089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almBrokenLoop.Bad,424089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almBrokenLoop.Suppress,424090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.UnSuppress,424090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Shelve,424090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.UnShelve,424090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Enable,424090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Disable,424090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Ack,424090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Reset,424090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Suppressed,424090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Shelved,424090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Disabled,424090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Acked,424090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.Alarm,424090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Fault,424100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almOverRange.AlarmState,424100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almOverRange.GlobalReset,424100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almOverRange.FaultInAlarm,424100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almOverRange.ALRM,424100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almOverRange.ANUN,424100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almOverRange.AKED,424100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almOverRange.Resetable,424100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almOverRange.REST,424100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almOverRange.ACKN,424100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almOverRange.UACK,424100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almOverRange.MCmd_Enable,424100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almOverRange.MCmd_Disable,424100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almOverRange.OCmd_Shelve,424100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almOverRange.OCmd_Unshelve,424100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almOverRange.SCmd_Suppress,424100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almOverRange.SCmd_UnSuppress,424101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almOverRange.AEShelveTMRDN,424101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almOverRange.Bad,424101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almOverRange.Suppress,424102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.UnSuppress,424102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Shelve,424102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.UnShelve,424102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Enable,424102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Disable,424102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Ack,424102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Reset,424102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Suppressed,424102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Shelved,424102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Disabled,424102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Acked,424102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almOverRange.Alarm,424102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Fault,424112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almUnderRange.AlarmState,424112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almUnderRange.GlobalReset,424112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almUnderRange.FaultInAlarm,424112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almUnderRange.ALRM,424112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almUnderRange.ANUN,424112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almUnderRange.AKED,424112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almUnderRange.Resetable,424112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almUnderRange.REST,424112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almUnderRange.ACKN,424112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almUnderRange.UACK,424112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almUnderRange.MCmd_Enable,424112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.MCmd_Disable,424112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.OCmd_Shelve,424112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.OCmd_Unshelve,424112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.SCmd_Suppress,424112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.SCmd_UnSuppress,424113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almUnderRange.AEShelveTMRDN,424113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almUnderRange.Bad,424113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almUnderRange.Suppress,424114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.UnSuppress,424114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Shelve,424114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.UnShelve,424114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Enable,424114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Disable,424114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Ack,424114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Reset,424114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Suppressed,424114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Shelved,424114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Disabled,424114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Acked,424114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almUnderRange.Alarm,424114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Fault,424124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almRateOfChange.AlarmState,424124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almRateOfChange.GlobalReset,424124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almRateOfChange.FaultInAlarm,424124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almRateOfChange.ALRM,424124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almRateOfChange.ANUN,424124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almRateOfChange.AKED,424124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almRateOfChange.Resetable,424124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almRateOfChange.REST,424124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almRateOfChange.ACKN,424124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almRateOfChange.UACK,424124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almRateOfChange.MCmd_Enable,424124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.MCmd_Disable,424124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.OCmd_Shelve,424124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.OCmd_Unshelve,424124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.SCmd_Suppress,424124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.SCmd_UnSuppress,424125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almRateOfChange.AEShelveTMRDN,424125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almRateOfChange.Bad,424125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almRateOfChange.Suppress,424126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.UnSuppress,424126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Shelve,424126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.UnShelve,424126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Enable,424126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Disable,424126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Ack,424126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Reset,424126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Suppressed,424126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Shelved,424126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Disabled,424126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Acked,424126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almRateOfChange.Alarm,424126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Fault,424136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI3.almPLCFault.AlarmState,424136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI3.almPLCFault.GlobalReset,424136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI3.almPLCFault.FaultInAlarm,424136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI3.almPLCFault.ALRM,424136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI3.almPLCFault.ANUN,424136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI3.almPLCFault.AKED,424136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI3.almPLCFault.Resetable,424136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI3.almPLCFault.REST,424136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI3.almPLCFault.ACKN,424136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI3.almPLCFault.UACK,424136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI3.almPLCFault.MCmd_Enable,424136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.MCmd_Disable,424136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.OCmd_Shelve,424136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.OCmd_Unshelve,424136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.SCmd_Suppress,424136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.SCmd_UnSuppress,424137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI3.almPLCFault.AEShelveTMRDN,424137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI3.almPLCFault.Bad,424137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI3.almPLCFault.Suppress,424138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.UnSuppress,424138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Shelve,424138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.UnShelve,424138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Enable,424138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Disable,424138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Ack,424138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Reset,424138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Suppressed,424138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Shelved,424138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Disabled,424138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Acked,424138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI3.almPLCFault.Alarm,424138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Fault,424240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almHighHigh.AlarmState,424240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almHighHigh.GlobalReset,424240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almHighHigh.FaultInAlarm,424240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almHighHigh.ALRM,424240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almHighHigh.ANUN,424240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almHighHigh.AKED,424240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almHighHigh.Resetable,424240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almHighHigh.REST,424240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almHighHigh.ACKN,424240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almHighHigh.UACK,424240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almHighHigh.MCmd_Enable,424240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.MCmd_Disable,424240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.OCmd_Shelve,424240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.OCmd_Unshelve,424240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.SCmd_Suppress,424240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.SCmd_UnSuppress,424241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almHighHigh.AEShelveTMRDN,424241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almHighHigh.Bad,424241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almHighHigh.Suppress,424242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.UnSuppress,424242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Shelve,424242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.UnShelve,424242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Enable,424242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Disable,424242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Ack,424242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Reset,424242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Suppressed,424242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Shelved,424242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Disabled,424242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Acked,424242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almHighHigh.Alarm,424242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Fault,424252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almHigh.AlarmState,424252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almHigh.GlobalReset,424252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almHigh.FaultInAlarm,424252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almHigh.ALRM,424252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almHigh.ANUN,424252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almHigh.AKED,424252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almHigh.Resetable,424252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almHigh.REST,424252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almHigh.ACKN,424252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almHigh.UACK,424252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almHigh.MCmd_Enable,424252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almHigh.MCmd_Disable,424252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almHigh.OCmd_Shelve,424252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almHigh.OCmd_Unshelve,424252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almHigh.SCmd_Suppress,424252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almHigh.SCmd_UnSuppress,424253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almHigh.AEShelveTMRDN,424253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almHigh.Bad,424253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almHigh.Suppress,424254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.UnSuppress,424254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Shelve,424254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.UnShelve,424254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Enable,424254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Disable,424254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Ack,424254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Reset,424254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almHigh.Suppressed,424254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almHigh.Shelved,424254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almHigh.Disabled,424254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almHigh.Acked,424254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almHigh.Alarm,424254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Fault,424264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almLow.AlarmState,424264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almLow.GlobalReset,424264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almLow.FaultInAlarm,424264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almLow.ALRM,424264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almLow.ANUN,424264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almLow.AKED,424264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almLow.Resetable,424264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almLow.REST,424264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almLow.ACKN,424264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almLow.UACK,424264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almLow.MCmd_Enable,424264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almLow.MCmd_Disable,424264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almLow.OCmd_Shelve,424264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almLow.OCmd_Unshelve,424264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almLow.SCmd_Suppress,424264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almLow.SCmd_UnSuppress,424265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almLow.AEShelveTMRDN,424265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almLow.Bad,424265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almLow.Suppress,424266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.UnSuppress,424266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Shelve,424266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.UnShelve,424266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Enable,424266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Disable,424266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Ack,424266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Reset,424266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almLow.Suppressed,424266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almLow.Shelved,424266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almLow.Disabled,424266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almLow.Acked,424266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almLow.Alarm,424266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Fault,424276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almLowLow.AlarmState,424276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almLowLow.GlobalReset,424276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almLowLow.FaultInAlarm,424276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almLowLow.ALRM,424276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almLowLow.ANUN,424276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almLowLow.AKED,424276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almLowLow.Resetable,424276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almLowLow.REST,424276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almLowLow.ACKN,424276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almLowLow.UACK,424276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almLowLow.MCmd_Enable,424276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almLowLow.MCmd_Disable,424276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almLowLow.OCmd_Shelve,424276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almLowLow.OCmd_Unshelve,424276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almLowLow.SCmd_Suppress,424276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almLowLow.SCmd_UnSuppress,424277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almLowLow.AEShelveTMRDN,424277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almLowLow.Bad,424277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almLowLow.Suppress,424278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.UnSuppress,424278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Shelve,424278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.UnShelve,424278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Enable,424278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Disable,424278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Ack,424278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Reset,424278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Suppressed,424278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Shelved,424278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Disabled,424278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Acked,424278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almLowLow.Alarm,424278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Fault,424288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almBrokenLoop.AlarmState,424288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almBrokenLoop.GlobalReset,424288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almBrokenLoop.FaultInAlarm,424288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almBrokenLoop.ALRM,424288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almBrokenLoop.ANUN,424288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almBrokenLoop.AKED,424288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almBrokenLoop.Resetable,424288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almBrokenLoop.REST,424288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almBrokenLoop.ACKN,424288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almBrokenLoop.UACK,424288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almBrokenLoop.MCmd_Enable,424288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.MCmd_Disable,424288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.OCmd_Shelve,424288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.OCmd_Unshelve,424288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.SCmd_Suppress,424288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.SCmd_UnSuppress,424289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almBrokenLoop.AEShelveTMRDN,424289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almBrokenLoop.Bad,424289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almBrokenLoop.Suppress,424290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.UnSuppress,424290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Shelve,424290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.UnShelve,424290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Enable,424290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Disable,424290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Ack,424290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Reset,424290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Suppressed,424290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Shelved,424290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Disabled,424290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Acked,424290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.Alarm,424290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Fault,424300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almOverRange.AlarmState,424300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almOverRange.GlobalReset,424300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almOverRange.FaultInAlarm,424300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almOverRange.ALRM,424300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almOverRange.ANUN,424300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almOverRange.AKED,424300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almOverRange.Resetable,424300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almOverRange.REST,424300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almOverRange.ACKN,424300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almOverRange.UACK,424300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almOverRange.MCmd_Enable,424300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almOverRange.MCmd_Disable,424300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almOverRange.OCmd_Shelve,424300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almOverRange.OCmd_Unshelve,424300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almOverRange.SCmd_Suppress,424300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almOverRange.SCmd_UnSuppress,424301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almOverRange.AEShelveTMRDN,424301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almOverRange.Bad,424301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almOverRange.Suppress,424302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.UnSuppress,424302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Shelve,424302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.UnShelve,424302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Enable,424302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Disable,424302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Ack,424302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Reset,424302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Suppressed,424302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Shelved,424302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Disabled,424302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Acked,424302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almOverRange.Alarm,424302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Fault,424312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almUnderRange.AlarmState,424312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almUnderRange.GlobalReset,424312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almUnderRange.FaultInAlarm,424312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almUnderRange.ALRM,424312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almUnderRange.ANUN,424312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almUnderRange.AKED,424312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almUnderRange.Resetable,424312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almUnderRange.REST,424312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almUnderRange.ACKN,424312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almUnderRange.UACK,424312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almUnderRange.MCmd_Enable,424312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.MCmd_Disable,424312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.OCmd_Shelve,424312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.OCmd_Unshelve,424312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.SCmd_Suppress,424312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.SCmd_UnSuppress,424313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almUnderRange.AEShelveTMRDN,424313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almUnderRange.Bad,424313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almUnderRange.Suppress,424314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.UnSuppress,424314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Shelve,424314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.UnShelve,424314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Enable,424314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Disable,424314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Ack,424314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Reset,424314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Suppressed,424314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Shelved,424314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Disabled,424314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Acked,424314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almUnderRange.Alarm,424314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Fault,424324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almRateOfChange.AlarmState,424324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almRateOfChange.GlobalReset,424324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almRateOfChange.FaultInAlarm,424324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almRateOfChange.ALRM,424324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almRateOfChange.ANUN,424324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almRateOfChange.AKED,424324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almRateOfChange.Resetable,424324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almRateOfChange.REST,424324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almRateOfChange.ACKN,424324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almRateOfChange.UACK,424324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almRateOfChange.MCmd_Enable,424324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.MCmd_Disable,424324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.OCmd_Shelve,424324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.OCmd_Unshelve,424324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.SCmd_Suppress,424324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.SCmd_UnSuppress,424325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almRateOfChange.AEShelveTMRDN,424325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almRateOfChange.Bad,424325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almRateOfChange.Suppress,424326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.UnSuppress,424326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Shelve,424326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.UnShelve,424326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Enable,424326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Disable,424326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Ack,424326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Reset,424326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Suppressed,424326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Shelved,424326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Disabled,424326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Acked,424326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almRateOfChange.Alarm,424326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Fault,424336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI4.almPLCFault.AlarmState,424336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI4.almPLCFault.GlobalReset,424336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI4.almPLCFault.FaultInAlarm,424336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI4.almPLCFault.ALRM,424336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI4.almPLCFault.ANUN,424336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI4.almPLCFault.AKED,424336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI4.almPLCFault.Resetable,424336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI4.almPLCFault.REST,424336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI4.almPLCFault.ACKN,424336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI4.almPLCFault.UACK,424336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI4.almPLCFault.MCmd_Enable,424336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.MCmd_Disable,424336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.OCmd_Shelve,424336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.OCmd_Unshelve,424336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.SCmd_Suppress,424336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.SCmd_UnSuppress,424337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI4.almPLCFault.AEShelveTMRDN,424337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI4.almPLCFault.Bad,424337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI4.almPLCFault.Suppress,424338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.UnSuppress,424338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Shelve,424338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.UnShelve,424338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Enable,424338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Disable,424338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Ack,424338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Reset,424338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Suppressed,424338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Shelved,424338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Disabled,424338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Acked,424338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI4.almPLCFault.Alarm,424338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Fault,424440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almHighHigh.AlarmState,424440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almHighHigh.GlobalReset,424440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almHighHigh.FaultInAlarm,424440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almHighHigh.ALRM,424440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almHighHigh.ANUN,424440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almHighHigh.AKED,424440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almHighHigh.Resetable,424440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almHighHigh.REST,424440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almHighHigh.ACKN,424440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almHighHigh.UACK,424440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almHighHigh.MCmd_Enable,424440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.MCmd_Disable,424440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.OCmd_Shelve,424440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.OCmd_Unshelve,424440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.SCmd_Suppress,424440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.SCmd_UnSuppress,424441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almHighHigh.AEShelveTMRDN,424441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almHighHigh.Bad,424441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almHighHigh.Suppress,424442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.UnSuppress,424442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Shelve,424442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.UnShelve,424442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Enable,424442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Disable,424442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Ack,424442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Reset,424442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Suppressed,424442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Shelved,424442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Disabled,424442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Acked,424442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almHighHigh.Alarm,424442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Fault,424452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almHigh.AlarmState,424452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almHigh.GlobalReset,424452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almHigh.FaultInAlarm,424452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almHigh.ALRM,424452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almHigh.ANUN,424452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almHigh.AKED,424452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almHigh.Resetable,424452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almHigh.REST,424452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almHigh.ACKN,424452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almHigh.UACK,424452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almHigh.MCmd_Enable,424452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almHigh.MCmd_Disable,424452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almHigh.OCmd_Shelve,424452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almHigh.OCmd_Unshelve,424452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almHigh.SCmd_Suppress,424452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almHigh.SCmd_UnSuppress,424453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almHigh.AEShelveTMRDN,424453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almHigh.Bad,424453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almHigh.Suppress,424454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.UnSuppress,424454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Shelve,424454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.UnShelve,424454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Enable,424454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Disable,424454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Ack,424454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Reset,424454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almHigh.Suppressed,424454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almHigh.Shelved,424454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almHigh.Disabled,424454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almHigh.Acked,424454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almHigh.Alarm,424454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Fault,424464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almLow.AlarmState,424464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almLow.GlobalReset,424464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almLow.FaultInAlarm,424464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almLow.ALRM,424464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almLow.ANUN,424464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almLow.AKED,424464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almLow.Resetable,424464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almLow.REST,424464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almLow.ACKN,424464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almLow.UACK,424464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almLow.MCmd_Enable,424464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almLow.MCmd_Disable,424464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almLow.OCmd_Shelve,424464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almLow.OCmd_Unshelve,424464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almLow.SCmd_Suppress,424464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almLow.SCmd_UnSuppress,424465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almLow.AEShelveTMRDN,424465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almLow.Bad,424465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almLow.Suppress,424466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.UnSuppress,424466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Shelve,424466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.UnShelve,424466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Enable,424466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Disable,424466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Ack,424466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Reset,424466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almLow.Suppressed,424466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almLow.Shelved,424466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almLow.Disabled,424466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almLow.Acked,424466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almLow.Alarm,424466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Fault,424476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almLowLow.AlarmState,424476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almLowLow.GlobalReset,424476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almLowLow.FaultInAlarm,424476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almLowLow.ALRM,424476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almLowLow.ANUN,424476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almLowLow.AKED,424476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almLowLow.Resetable,424476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almLowLow.REST,424476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almLowLow.ACKN,424476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almLowLow.UACK,424476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almLowLow.MCmd_Enable,424476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almLowLow.MCmd_Disable,424476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almLowLow.OCmd_Shelve,424476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almLowLow.OCmd_Unshelve,424476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almLowLow.SCmd_Suppress,424476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almLowLow.SCmd_UnSuppress,424477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almLowLow.AEShelveTMRDN,424477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almLowLow.Bad,424477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almLowLow.Suppress,424478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.UnSuppress,424478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Shelve,424478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.UnShelve,424478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Enable,424478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Disable,424478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Ack,424478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Reset,424478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Suppressed,424478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Shelved,424478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Disabled,424478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Acked,424478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almLowLow.Alarm,424478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Fault,424488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almBrokenLoop.AlarmState,424488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almBrokenLoop.GlobalReset,424488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almBrokenLoop.FaultInAlarm,424488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almBrokenLoop.ALRM,424488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almBrokenLoop.ANUN,424488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almBrokenLoop.AKED,424488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almBrokenLoop.Resetable,424488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almBrokenLoop.REST,424488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almBrokenLoop.ACKN,424488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almBrokenLoop.UACK,424488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almBrokenLoop.MCmd_Enable,424488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.MCmd_Disable,424488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.OCmd_Shelve,424488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.OCmd_Unshelve,424488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.SCmd_Suppress,424488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.SCmd_UnSuppress,424489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almBrokenLoop.AEShelveTMRDN,424489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almBrokenLoop.Bad,424489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almBrokenLoop.Suppress,424490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.UnSuppress,424490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Shelve,424490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.UnShelve,424490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Enable,424490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Disable,424490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Ack,424490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Reset,424490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Suppressed,424490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Shelved,424490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Disabled,424490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Acked,424490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.Alarm,424490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Fault,424500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almOverRange.AlarmState,424500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almOverRange.GlobalReset,424500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almOverRange.FaultInAlarm,424500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almOverRange.ALRM,424500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almOverRange.ANUN,424500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almOverRange.AKED,424500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almOverRange.Resetable,424500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almOverRange.REST,424500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almOverRange.ACKN,424500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almOverRange.UACK,424500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almOverRange.MCmd_Enable,424500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almOverRange.MCmd_Disable,424500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almOverRange.OCmd_Shelve,424500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almOverRange.OCmd_Unshelve,424500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almOverRange.SCmd_Suppress,424500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almOverRange.SCmd_UnSuppress,424501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almOverRange.AEShelveTMRDN,424501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almOverRange.Bad,424501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almOverRange.Suppress,424502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.UnSuppress,424502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Shelve,424502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.UnShelve,424502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Enable,424502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Disable,424502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Ack,424502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Reset,424502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Suppressed,424502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Shelved,424502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Disabled,424502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Acked,424502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almOverRange.Alarm,424502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Fault,424512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almUnderRange.AlarmState,424512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almUnderRange.GlobalReset,424512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almUnderRange.FaultInAlarm,424512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almUnderRange.ALRM,424512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almUnderRange.ANUN,424512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almUnderRange.AKED,424512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almUnderRange.Resetable,424512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almUnderRange.REST,424512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almUnderRange.ACKN,424512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almUnderRange.UACK,424512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almUnderRange.MCmd_Enable,424512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.MCmd_Disable,424512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.OCmd_Shelve,424512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.OCmd_Unshelve,424512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.SCmd_Suppress,424512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.SCmd_UnSuppress,424513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almUnderRange.AEShelveTMRDN,424513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almUnderRange.Bad,424513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almUnderRange.Suppress,424514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.UnSuppress,424514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Shelve,424514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.UnShelve,424514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Enable,424514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Disable,424514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Ack,424514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Reset,424514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Suppressed,424514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Shelved,424514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Disabled,424514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Acked,424514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almUnderRange.Alarm,424514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Fault,424524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almRateOfChange.AlarmState,424524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almRateOfChange.GlobalReset,424524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almRateOfChange.FaultInAlarm,424524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almRateOfChange.ALRM,424524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almRateOfChange.ANUN,424524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almRateOfChange.AKED,424524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almRateOfChange.Resetable,424524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almRateOfChange.REST,424524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almRateOfChange.ACKN,424524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almRateOfChange.UACK,424524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almRateOfChange.MCmd_Enable,424524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.MCmd_Disable,424524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.OCmd_Shelve,424524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.OCmd_Unshelve,424524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.SCmd_Suppress,424524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.SCmd_UnSuppress,424525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almRateOfChange.AEShelveTMRDN,424525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almRateOfChange.Bad,424525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almRateOfChange.Suppress,424526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.UnSuppress,424526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Shelve,424526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.UnShelve,424526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Enable,424526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Disable,424526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Ack,424526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Reset,424526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Suppressed,424526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Shelved,424526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Disabled,424526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Acked,424526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almRateOfChange.Alarm,424526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Fault,424536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_8_VI5.almPLCFault.AlarmState,424536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_8_VI5.almPLCFault.GlobalReset,424536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_8_VI5.almPLCFault.FaultInAlarm,424536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_8_VI5.almPLCFault.ALRM,424536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_8_VI5.almPLCFault.ANUN,424536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_8_VI5.almPLCFault.AKED,424536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_8_VI5.almPLCFault.Resetable,424536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_8_VI5.almPLCFault.REST,424536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_8_VI5.almPLCFault.ACKN,424536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_8_VI5.almPLCFault.UACK,424536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_8_VI5.almPLCFault.MCmd_Enable,424536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.MCmd_Disable,424536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.OCmd_Shelve,424536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.OCmd_Unshelve,424536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.SCmd_Suppress,424536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.SCmd_UnSuppress,424537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_8_VI5.almPLCFault.AEShelveTMRDN,424537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_8_VI5.almPLCFault.Bad,424537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_8_VI5.almPLCFault.Suppress,424538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.UnSuppress,424538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Shelve,424538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.UnShelve,424538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Enable,424538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Disable,424538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Ack,424538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Reset,424538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Suppressed,424538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Shelved,424538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Disabled,424538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Acked,424538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_8_VI5.almPLCFault.Alarm,424538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Fault,424640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almHighHigh.AlarmState,424640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almHighHigh.GlobalReset,424640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almHighHigh.FaultInAlarm,424640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almHighHigh.ALRM,424640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almHighHigh.ANUN,424640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almHighHigh.AKED,424640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almHighHigh.Resetable,424640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almHighHigh.REST,424640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almHighHigh.ACKN,424640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almHighHigh.UACK,424640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almHighHigh.MCmd_Enable,424640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.MCmd_Disable,424640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.OCmd_Shelve,424640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.OCmd_Unshelve,424640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.SCmd_Suppress,424640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.SCmd_UnSuppress,424641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almHighHigh.AEShelveTMRDN,424641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almHighHigh.Bad,424641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almHighHigh.Suppress,424642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.UnSuppress,424642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Shelve,424642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.UnShelve,424642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Enable,424642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Disable,424642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Ack,424642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Reset,424642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Suppressed,424642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Shelved,424642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Disabled,424642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Acked,424642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almHighHigh.Alarm,424642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Fault,424652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almHigh.AlarmState,424652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almHigh.GlobalReset,424652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almHigh.FaultInAlarm,424652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almHigh.ALRM,424652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almHigh.ANUN,424652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almHigh.AKED,424652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almHigh.Resetable,424652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almHigh.REST,424652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almHigh.ACKN,424652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almHigh.UACK,424652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almHigh.MCmd_Enable,424652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almHigh.MCmd_Disable,424652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almHigh.OCmd_Shelve,424652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almHigh.OCmd_Unshelve,424652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almHigh.SCmd_Suppress,424652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almHigh.SCmd_UnSuppress,424653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almHigh.AEShelveTMRDN,424653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almHigh.Bad,424653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almHigh.Suppress,424654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.UnSuppress,424654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Shelve,424654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.UnShelve,424654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Enable,424654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Disable,424654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Ack,424654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Reset,424654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almHigh.Suppressed,424654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almHigh.Shelved,424654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almHigh.Disabled,424654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almHigh.Acked,424654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almHigh.Alarm,424654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Fault,424664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almLow.AlarmState,424664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almLow.GlobalReset,424664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almLow.FaultInAlarm,424664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almLow.ALRM,424664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almLow.ANUN,424664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almLow.AKED,424664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almLow.Resetable,424664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almLow.REST,424664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almLow.ACKN,424664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almLow.UACK,424664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almLow.MCmd_Enable,424664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almLow.MCmd_Disable,424664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almLow.OCmd_Shelve,424664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almLow.OCmd_Unshelve,424664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almLow.SCmd_Suppress,424664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almLow.SCmd_UnSuppress,424665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almLow.AEShelveTMRDN,424665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almLow.Bad,424665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almLow.Suppress,424666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.UnSuppress,424666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Shelve,424666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.UnShelve,424666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Enable,424666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Disable,424666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Ack,424666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Reset,424666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almLow.Suppressed,424666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almLow.Shelved,424666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almLow.Disabled,424666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almLow.Acked,424666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almLow.Alarm,424666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Fault,424676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almLowLow.AlarmState,424676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almLowLow.GlobalReset,424676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almLowLow.FaultInAlarm,424676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almLowLow.ALRM,424676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almLowLow.ANUN,424676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almLowLow.AKED,424676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almLowLow.Resetable,424676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almLowLow.REST,424676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almLowLow.ACKN,424676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almLowLow.UACK,424676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almLowLow.MCmd_Enable,424676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almLowLow.MCmd_Disable,424676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almLowLow.OCmd_Shelve,424676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almLowLow.OCmd_Unshelve,424676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almLowLow.SCmd_Suppress,424676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almLowLow.SCmd_UnSuppress,424677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almLowLow.AEShelveTMRDN,424677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almLowLow.Bad,424677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almLowLow.Suppress,424678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.UnSuppress,424678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Shelve,424678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.UnShelve,424678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Enable,424678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Disable,424678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Ack,424678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Reset,424678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Suppressed,424678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Shelved,424678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Disabled,424678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Acked,424678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almLowLow.Alarm,424678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Fault,424688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almBrokenLoop.AlarmState,424688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almBrokenLoop.GlobalReset,424688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almBrokenLoop.FaultInAlarm,424688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almBrokenLoop.ALRM,424688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almBrokenLoop.ANUN,424688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almBrokenLoop.AKED,424688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almBrokenLoop.Resetable,424688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almBrokenLoop.REST,424688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almBrokenLoop.ACKN,424688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almBrokenLoop.UACK,424688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almBrokenLoop.MCmd_Enable,424688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.MCmd_Disable,424688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.OCmd_Shelve,424688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.OCmd_Unshelve,424688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.SCmd_Suppress,424688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.SCmd_UnSuppress,424689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almBrokenLoop.AEShelveTMRDN,424689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almBrokenLoop.Bad,424689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almBrokenLoop.Suppress,424690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.UnSuppress,424690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Shelve,424690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.UnShelve,424690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Enable,424690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Disable,424690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Ack,424690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Reset,424690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Suppressed,424690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Shelved,424690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Disabled,424690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Acked,424690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.Alarm,424690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Fault,424700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almOverRange.AlarmState,424700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almOverRange.GlobalReset,424700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almOverRange.FaultInAlarm,424700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almOverRange.ALRM,424700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almOverRange.ANUN,424700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almOverRange.AKED,424700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almOverRange.Resetable,424700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almOverRange.REST,424700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almOverRange.ACKN,424700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almOverRange.UACK,424700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almOverRange.MCmd_Enable,424700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almOverRange.MCmd_Disable,424700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almOverRange.OCmd_Shelve,424700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almOverRange.OCmd_Unshelve,424700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almOverRange.SCmd_Suppress,424700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almOverRange.SCmd_UnSuppress,424701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almOverRange.AEShelveTMRDN,424701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almOverRange.Bad,424701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almOverRange.Suppress,424702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.UnSuppress,424702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Shelve,424702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.UnShelve,424702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Enable,424702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Disable,424702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Ack,424702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Reset,424702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Suppressed,424702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Shelved,424702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Disabled,424702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Acked,424702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almOverRange.Alarm,424702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Fault,424712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almUnderRange.AlarmState,424712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almUnderRange.GlobalReset,424712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almUnderRange.FaultInAlarm,424712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almUnderRange.ALRM,424712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almUnderRange.ANUN,424712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almUnderRange.AKED,424712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almUnderRange.Resetable,424712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almUnderRange.REST,424712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almUnderRange.ACKN,424712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almUnderRange.UACK,424712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almUnderRange.MCmd_Enable,424712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.MCmd_Disable,424712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.OCmd_Shelve,424712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.OCmd_Unshelve,424712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.SCmd_Suppress,424712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.SCmd_UnSuppress,424713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almUnderRange.AEShelveTMRDN,424713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almUnderRange.Bad,424713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almUnderRange.Suppress,424714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.UnSuppress,424714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Shelve,424714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.UnShelve,424714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Enable,424714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Disable,424714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Ack,424714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Reset,424714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Suppressed,424714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Shelved,424714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Disabled,424714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Acked,424714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almUnderRange.Alarm,424714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Fault,424724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almRateOfChange.AlarmState,424724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almRateOfChange.GlobalReset,424724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almRateOfChange.FaultInAlarm,424724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almRateOfChange.ALRM,424724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almRateOfChange.ANUN,424724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almRateOfChange.AKED,424724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almRateOfChange.Resetable,424724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almRateOfChange.REST,424724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almRateOfChange.ACKN,424724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almRateOfChange.UACK,424724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almRateOfChange.MCmd_Enable,424724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.MCmd_Disable,424724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.OCmd_Shelve,424724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.OCmd_Unshelve,424724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.SCmd_Suppress,424724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.SCmd_UnSuppress,424725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almRateOfChange.AEShelveTMRDN,424725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almRateOfChange.Bad,424725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almRateOfChange.Suppress,424726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.UnSuppress,424726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Shelve,424726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.UnShelve,424726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Enable,424726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Disable,424726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Ack,424726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Reset,424726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Suppressed,424726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Shelved,424726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Disabled,424726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Acked,424726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almRateOfChange.Alarm,424726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Fault,424736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI1.almPLCFault.AlarmState,424736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI1.almPLCFault.GlobalReset,424736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI1.almPLCFault.FaultInAlarm,424736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI1.almPLCFault.ALRM,424736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI1.almPLCFault.ANUN,424736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI1.almPLCFault.AKED,424736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI1.almPLCFault.Resetable,424736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI1.almPLCFault.REST,424736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI1.almPLCFault.ACKN,424736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI1.almPLCFault.UACK,424736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI1.almPLCFault.MCmd_Enable,424736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.MCmd_Disable,424736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.OCmd_Shelve,424736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.OCmd_Unshelve,424736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.SCmd_Suppress,424736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.SCmd_UnSuppress,424737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI1.almPLCFault.AEShelveTMRDN,424737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI1.almPLCFault.Bad,424737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI1.almPLCFault.Suppress,424738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.UnSuppress,424738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Shelve,424738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.UnShelve,424738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Enable,424738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Disable,424738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Ack,424738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Reset,424738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Suppressed,424738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Shelved,424738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Disabled,424738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Acked,424738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI1.almPLCFault.Alarm,424738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Fault,424840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almHighHigh.AlarmState,424840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almHighHigh.GlobalReset,424840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almHighHigh.FaultInAlarm,424840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almHighHigh.ALRM,424840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almHighHigh.ANUN,424840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almHighHigh.AKED,424840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almHighHigh.Resetable,424840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almHighHigh.REST,424840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almHighHigh.ACKN,424840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almHighHigh.UACK,424840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almHighHigh.MCmd_Enable,424840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.MCmd_Disable,424840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.OCmd_Shelve,424840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.OCmd_Unshelve,424840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.SCmd_Suppress,424840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.SCmd_UnSuppress,424841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almHighHigh.AEShelveTMRDN,424841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almHighHigh.Bad,424841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almHighHigh.Suppress,424842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.UnSuppress,424842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Shelve,424842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.UnShelve,424842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Enable,424842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Disable,424842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Ack,424842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Reset,424842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Suppressed,424842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Shelved,424842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Disabled,424842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Acked,424842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almHighHigh.Alarm,424842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Fault,424852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almHigh.AlarmState,424852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almHigh.GlobalReset,424852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almHigh.FaultInAlarm,424852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almHigh.ALRM,424852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almHigh.ANUN,424852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almHigh.AKED,424852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almHigh.Resetable,424852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almHigh.REST,424852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almHigh.ACKN,424852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almHigh.UACK,424852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almHigh.MCmd_Enable,424852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almHigh.MCmd_Disable,424852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almHigh.OCmd_Shelve,424852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almHigh.OCmd_Unshelve,424852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almHigh.SCmd_Suppress,424852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almHigh.SCmd_UnSuppress,424853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almHigh.AEShelveTMRDN,424853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almHigh.Bad,424853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almHigh.Suppress,424854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.UnSuppress,424854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Shelve,424854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.UnShelve,424854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Enable,424854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Disable,424854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Ack,424854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Reset,424854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almHigh.Suppressed,424854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almHigh.Shelved,424854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almHigh.Disabled,424854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almHigh.Acked,424854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almHigh.Alarm,424854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Fault,424864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almLow.AlarmState,424864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almLow.GlobalReset,424864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almLow.FaultInAlarm,424864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almLow.ALRM,424864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almLow.ANUN,424864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almLow.AKED,424864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almLow.Resetable,424864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almLow.REST,424864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almLow.ACKN,424864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almLow.UACK,424864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almLow.MCmd_Enable,424864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almLow.MCmd_Disable,424864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almLow.OCmd_Shelve,424864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almLow.OCmd_Unshelve,424864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almLow.SCmd_Suppress,424864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almLow.SCmd_UnSuppress,424865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almLow.AEShelveTMRDN,424865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almLow.Bad,424865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almLow.Suppress,424866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.UnSuppress,424866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Shelve,424866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.UnShelve,424866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Enable,424866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Disable,424866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Ack,424866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Reset,424866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almLow.Suppressed,424866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almLow.Shelved,424866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almLow.Disabled,424866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almLow.Acked,424866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almLow.Alarm,424866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Fault,424876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almLowLow.AlarmState,424876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almLowLow.GlobalReset,424876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almLowLow.FaultInAlarm,424876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almLowLow.ALRM,424876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almLowLow.ANUN,424876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almLowLow.AKED,424876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almLowLow.Resetable,424876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almLowLow.REST,424876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almLowLow.ACKN,424876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almLowLow.UACK,424876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almLowLow.MCmd_Enable,424876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almLowLow.MCmd_Disable,424876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almLowLow.OCmd_Shelve,424876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almLowLow.OCmd_Unshelve,424876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almLowLow.SCmd_Suppress,424876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almLowLow.SCmd_UnSuppress,424877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almLowLow.AEShelveTMRDN,424877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almLowLow.Bad,424877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almLowLow.Suppress,424878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.UnSuppress,424878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Shelve,424878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.UnShelve,424878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Enable,424878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Disable,424878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Ack,424878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Reset,424878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Suppressed,424878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Shelved,424878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Disabled,424878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Acked,424878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almLowLow.Alarm,424878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Fault,424888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almBrokenLoop.AlarmState,424888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almBrokenLoop.GlobalReset,424888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almBrokenLoop.FaultInAlarm,424888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almBrokenLoop.ALRM,424888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almBrokenLoop.ANUN,424888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almBrokenLoop.AKED,424888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almBrokenLoop.Resetable,424888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almBrokenLoop.REST,424888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almBrokenLoop.ACKN,424888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almBrokenLoop.UACK,424888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almBrokenLoop.MCmd_Enable,424888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.MCmd_Disable,424888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.OCmd_Shelve,424888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.OCmd_Unshelve,424888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.SCmd_Suppress,424888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.SCmd_UnSuppress,424889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almBrokenLoop.AEShelveTMRDN,424889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almBrokenLoop.Bad,424889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almBrokenLoop.Suppress,424890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.UnSuppress,424890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Shelve,424890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.UnShelve,424890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Enable,424890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Disable,424890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Ack,424890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Reset,424890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Suppressed,424890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Shelved,424890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Disabled,424890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Acked,424890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.Alarm,424890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Fault,424900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almOverRange.AlarmState,424900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almOverRange.GlobalReset,424900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almOverRange.FaultInAlarm,424900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almOverRange.ALRM,424900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almOverRange.ANUN,424900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almOverRange.AKED,424900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almOverRange.Resetable,424900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almOverRange.REST,424900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almOverRange.ACKN,424900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almOverRange.UACK,424900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almOverRange.MCmd_Enable,424900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almOverRange.MCmd_Disable,424900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almOverRange.OCmd_Shelve,424900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almOverRange.OCmd_Unshelve,424900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almOverRange.SCmd_Suppress,424900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almOverRange.SCmd_UnSuppress,424901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almOverRange.AEShelveTMRDN,424901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almOverRange.Bad,424901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almOverRange.Suppress,424902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.UnSuppress,424902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Shelve,424902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.UnShelve,424902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Enable,424902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Disable,424902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Ack,424902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Reset,424902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Suppressed,424902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Shelved,424902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Disabled,424902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Acked,424902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almOverRange.Alarm,424902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Fault,424912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almUnderRange.AlarmState,424912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almUnderRange.GlobalReset,424912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almUnderRange.FaultInAlarm,424912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almUnderRange.ALRM,424912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almUnderRange.ANUN,424912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almUnderRange.AKED,424912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almUnderRange.Resetable,424912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almUnderRange.REST,424912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almUnderRange.ACKN,424912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almUnderRange.UACK,424912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almUnderRange.MCmd_Enable,424912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.MCmd_Disable,424912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.OCmd_Shelve,424912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.OCmd_Unshelve,424912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.SCmd_Suppress,424912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.SCmd_UnSuppress,424913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almUnderRange.AEShelveTMRDN,424913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almUnderRange.Bad,424913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almUnderRange.Suppress,424914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.UnSuppress,424914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Shelve,424914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.UnShelve,424914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Enable,424914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Disable,424914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Ack,424914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Reset,424914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Suppressed,424914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Shelved,424914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Disabled,424914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Acked,424914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almUnderRange.Alarm,424914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Fault,424924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almRateOfChange.AlarmState,424924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almRateOfChange.GlobalReset,424924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almRateOfChange.FaultInAlarm,424924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almRateOfChange.ALRM,424924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almRateOfChange.ANUN,424924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almRateOfChange.AKED,424924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almRateOfChange.Resetable,424924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almRateOfChange.REST,424924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almRateOfChange.ACKN,424924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almRateOfChange.UACK,424924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almRateOfChange.MCmd_Enable,424924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.MCmd_Disable,424924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.OCmd_Shelve,424924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.OCmd_Unshelve,424924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.SCmd_Suppress,424924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.SCmd_UnSuppress,424925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almRateOfChange.AEShelveTMRDN,424925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almRateOfChange.Bad,424925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almRateOfChange.Suppress,424926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.UnSuppress,424926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Shelve,424926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.UnShelve,424926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Enable,424926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Disable,424926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Ack,424926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Reset,424926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Suppressed,424926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Shelved,424926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Disabled,424926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Acked,424926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almRateOfChange.Alarm,424926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Fault,424936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI2.almPLCFault.AlarmState,424936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI2.almPLCFault.GlobalReset,424936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI2.almPLCFault.FaultInAlarm,424936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI2.almPLCFault.ALRM,424936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI2.almPLCFault.ANUN,424936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI2.almPLCFault.AKED,424936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI2.almPLCFault.Resetable,424936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI2.almPLCFault.REST,424936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI2.almPLCFault.ACKN,424936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI2.almPLCFault.UACK,424936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI2.almPLCFault.MCmd_Enable,424936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.MCmd_Disable,424936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.OCmd_Shelve,424936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.OCmd_Unshelve,424936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.SCmd_Suppress,424936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.SCmd_UnSuppress,424937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI2.almPLCFault.AEShelveTMRDN,424937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI2.almPLCFault.Bad,424937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI2.almPLCFault.Suppress,424938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.UnSuppress,424938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Shelve,424938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.UnShelve,424938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Enable,424938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Disable,424938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Ack,424938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Reset,424938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Suppressed,424938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Shelved,424938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Disabled,424938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Acked,424938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI2.almPLCFault.Alarm,424938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Fault,425040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almHighHigh.AlarmState,425040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almHighHigh.GlobalReset,425040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almHighHigh.FaultInAlarm,425040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almHighHigh.ALRM,425040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almHighHigh.ANUN,425040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almHighHigh.AKED,425040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almHighHigh.Resetable,425040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almHighHigh.REST,425040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almHighHigh.ACKN,425040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almHighHigh.UACK,425040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almHighHigh.MCmd_Enable,425040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.MCmd_Disable,425040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.OCmd_Shelve,425040.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.OCmd_Unshelve,425040.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.SCmd_Suppress,425040.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.SCmd_UnSuppress,425041.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almHighHigh.AEShelveTMRDN,425041.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almHighHigh.Bad,425041.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almHighHigh.Suppress,425042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.UnSuppress,425042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Shelve,425042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.UnShelve,425042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Enable,425042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Disable,425042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Ack,425042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Reset,425042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Suppressed,425042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Shelved,425042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Disabled,425042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Acked,425042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almHighHigh.Alarm,425042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Fault,425052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almHigh.AlarmState,425052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almHigh.GlobalReset,425052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almHigh.FaultInAlarm,425052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almHigh.ALRM,425052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almHigh.ANUN,425052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almHigh.AKED,425052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almHigh.Resetable,425052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almHigh.REST,425052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almHigh.ACKN,425052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almHigh.UACK,425052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almHigh.MCmd_Enable,425052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almHigh.MCmd_Disable,425052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almHigh.OCmd_Shelve,425052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almHigh.OCmd_Unshelve,425052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almHigh.SCmd_Suppress,425052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almHigh.SCmd_UnSuppress,425053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almHigh.AEShelveTMRDN,425053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almHigh.Bad,425053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almHigh.Suppress,425054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.UnSuppress,425054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Shelve,425054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.UnShelve,425054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Enable,425054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Disable,425054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Ack,425054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Reset,425054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almHigh.Suppressed,425054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almHigh.Shelved,425054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almHigh.Disabled,425054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almHigh.Acked,425054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almHigh.Alarm,425054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Fault,425064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almLow.AlarmState,425064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almLow.GlobalReset,425064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almLow.FaultInAlarm,425064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almLow.ALRM,425064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almLow.ANUN,425064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almLow.AKED,425064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almLow.Resetable,425064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almLow.REST,425064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almLow.ACKN,425064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almLow.UACK,425064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almLow.MCmd_Enable,425064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almLow.MCmd_Disable,425064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almLow.OCmd_Shelve,425064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almLow.OCmd_Unshelve,425064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almLow.SCmd_Suppress,425064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almLow.SCmd_UnSuppress,425065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almLow.AEShelveTMRDN,425065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almLow.Bad,425065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almLow.Suppress,425066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.UnSuppress,425066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Shelve,425066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.UnShelve,425066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Enable,425066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Disable,425066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Ack,425066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Reset,425066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almLow.Suppressed,425066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almLow.Shelved,425066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almLow.Disabled,425066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almLow.Acked,425066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almLow.Alarm,425066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Fault,425076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almLowLow.AlarmState,425076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almLowLow.GlobalReset,425076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almLowLow.FaultInAlarm,425076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almLowLow.ALRM,425076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almLowLow.ANUN,425076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almLowLow.AKED,425076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almLowLow.Resetable,425076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almLowLow.REST,425076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almLowLow.ACKN,425076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almLowLow.UACK,425076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almLowLow.MCmd_Enable,425076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almLowLow.MCmd_Disable,425076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almLowLow.OCmd_Shelve,425076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almLowLow.OCmd_Unshelve,425076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almLowLow.SCmd_Suppress,425076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almLowLow.SCmd_UnSuppress,425077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almLowLow.AEShelveTMRDN,425077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almLowLow.Bad,425077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almLowLow.Suppress,425078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.UnSuppress,425078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Shelve,425078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.UnShelve,425078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Enable,425078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Disable,425078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Ack,425078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Reset,425078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Suppressed,425078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Shelved,425078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Disabled,425078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Acked,425078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almLowLow.Alarm,425078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Fault,425088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almBrokenLoop.AlarmState,425088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almBrokenLoop.GlobalReset,425088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almBrokenLoop.FaultInAlarm,425088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almBrokenLoop.ALRM,425088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almBrokenLoop.ANUN,425088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almBrokenLoop.AKED,425088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almBrokenLoop.Resetable,425088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almBrokenLoop.REST,425088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almBrokenLoop.ACKN,425088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almBrokenLoop.UACK,425088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almBrokenLoop.MCmd_Enable,425088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.MCmd_Disable,425088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.OCmd_Shelve,425088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.OCmd_Unshelve,425088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.SCmd_Suppress,425088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.SCmd_UnSuppress,425089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almBrokenLoop.AEShelveTMRDN,425089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almBrokenLoop.Bad,425089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almBrokenLoop.Suppress,425090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.UnSuppress,425090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Shelve,425090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.UnShelve,425090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Enable,425090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Disable,425090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Ack,425090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Reset,425090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Suppressed,425090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Shelved,425090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Disabled,425090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Acked,425090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.Alarm,425090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Fault,425100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almOverRange.AlarmState,425100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almOverRange.GlobalReset,425100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almOverRange.FaultInAlarm,425100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almOverRange.ALRM,425100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almOverRange.ANUN,425100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almOverRange.AKED,425100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almOverRange.Resetable,425100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almOverRange.REST,425100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almOverRange.ACKN,425100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almOverRange.UACK,425100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almOverRange.MCmd_Enable,425100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almOverRange.MCmd_Disable,425100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almOverRange.OCmd_Shelve,425100.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almOverRange.OCmd_Unshelve,425100.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almOverRange.SCmd_Suppress,425100.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almOverRange.SCmd_UnSuppress,425101.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almOverRange.AEShelveTMRDN,425101.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almOverRange.Bad,425101.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almOverRange.Suppress,425102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.UnSuppress,425102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Shelve,425102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.UnShelve,425102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Enable,425102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Disable,425102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Ack,425102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Reset,425102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Suppressed,425102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Shelved,425102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Disabled,425102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Acked,425102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almOverRange.Alarm,425102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Fault,425112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almUnderRange.AlarmState,425112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almUnderRange.GlobalReset,425112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almUnderRange.FaultInAlarm,425112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almUnderRange.ALRM,425112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almUnderRange.ANUN,425112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almUnderRange.AKED,425112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almUnderRange.Resetable,425112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almUnderRange.REST,425112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almUnderRange.ACKN,425112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almUnderRange.UACK,425112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almUnderRange.MCmd_Enable,425112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.MCmd_Disable,425112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.OCmd_Shelve,425112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.OCmd_Unshelve,425112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.SCmd_Suppress,425112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.SCmd_UnSuppress,425113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almUnderRange.AEShelveTMRDN,425113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almUnderRange.Bad,425113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almUnderRange.Suppress,425114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.UnSuppress,425114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Shelve,425114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.UnShelve,425114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Enable,425114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Disable,425114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Ack,425114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Reset,425114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Suppressed,425114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Shelved,425114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Disabled,425114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Acked,425114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almUnderRange.Alarm,425114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Fault,425124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almRateOfChange.AlarmState,425124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almRateOfChange.GlobalReset,425124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almRateOfChange.FaultInAlarm,425124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almRateOfChange.ALRM,425124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almRateOfChange.ANUN,425124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almRateOfChange.AKED,425124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almRateOfChange.Resetable,425124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almRateOfChange.REST,425124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almRateOfChange.ACKN,425124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almRateOfChange.UACK,425124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almRateOfChange.MCmd_Enable,425124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.MCmd_Disable,425124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.OCmd_Shelve,425124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.OCmd_Unshelve,425124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.SCmd_Suppress,425124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.SCmd_UnSuppress,425125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almRateOfChange.AEShelveTMRDN,425125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almRateOfChange.Bad,425125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almRateOfChange.Suppress,425126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.UnSuppress,425126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Shelve,425126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.UnShelve,425126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Enable,425126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Disable,425126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Ack,425126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Reset,425126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Suppressed,425126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Shelved,425126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Disabled,425126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Acked,425126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almRateOfChange.Alarm,425126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Fault,425136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI3.almPLCFault.AlarmState,425136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI3.almPLCFault.GlobalReset,425136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI3.almPLCFault.FaultInAlarm,425136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI3.almPLCFault.ALRM,425136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI3.almPLCFault.ANUN,425136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI3.almPLCFault.AKED,425136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI3.almPLCFault.Resetable,425136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI3.almPLCFault.REST,425136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI3.almPLCFault.ACKN,425136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI3.almPLCFault.UACK,425136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI3.almPLCFault.MCmd_Enable,425136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.MCmd_Disable,425136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.OCmd_Shelve,425136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.OCmd_Unshelve,425136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.SCmd_Suppress,425136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.SCmd_UnSuppress,425137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI3.almPLCFault.AEShelveTMRDN,425137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI3.almPLCFault.Bad,425137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI3.almPLCFault.Suppress,425138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.UnSuppress,425138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Shelve,425138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.UnShelve,425138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Enable,425138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Disable,425138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Ack,425138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Reset,425138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Suppressed,425138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Shelved,425138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Disabled,425138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Acked,425138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI3.almPLCFault.Alarm,425138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Fault,425240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almHighHigh.AlarmState,425240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almHighHigh.GlobalReset,425240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almHighHigh.FaultInAlarm,425240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almHighHigh.ALRM,425240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almHighHigh.ANUN,425240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almHighHigh.AKED,425240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almHighHigh.Resetable,425240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almHighHigh.REST,425240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almHighHigh.ACKN,425240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almHighHigh.UACK,425240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almHighHigh.MCmd_Enable,425240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.MCmd_Disable,425240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.OCmd_Shelve,425240.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.OCmd_Unshelve,425240.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.SCmd_Suppress,425240.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.SCmd_UnSuppress,425241.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almHighHigh.AEShelveTMRDN,425241.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almHighHigh.Bad,425241.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almHighHigh.Suppress,425242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.UnSuppress,425242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Shelve,425242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.UnShelve,425242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Enable,425242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Disable,425242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Ack,425242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Reset,425242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Suppressed,425242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Shelved,425242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Disabled,425242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Acked,425242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almHighHigh.Alarm,425242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Fault,425252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almHigh.AlarmState,425252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almHigh.GlobalReset,425252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almHigh.FaultInAlarm,425252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almHigh.ALRM,425252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almHigh.ANUN,425252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almHigh.AKED,425252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almHigh.Resetable,425252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almHigh.REST,425252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almHigh.ACKN,425252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almHigh.UACK,425252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almHigh.MCmd_Enable,425252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almHigh.MCmd_Disable,425252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almHigh.OCmd_Shelve,425252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almHigh.OCmd_Unshelve,425252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almHigh.SCmd_Suppress,425252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almHigh.SCmd_UnSuppress,425253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almHigh.AEShelveTMRDN,425253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almHigh.Bad,425253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almHigh.Suppress,425254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.UnSuppress,425254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Shelve,425254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.UnShelve,425254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Enable,425254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Disable,425254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Ack,425254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Reset,425254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almHigh.Suppressed,425254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almHigh.Shelved,425254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almHigh.Disabled,425254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almHigh.Acked,425254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almHigh.Alarm,425254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Fault,425264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almLow.AlarmState,425264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almLow.GlobalReset,425264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almLow.FaultInAlarm,425264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almLow.ALRM,425264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almLow.ANUN,425264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almLow.AKED,425264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almLow.Resetable,425264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almLow.REST,425264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almLow.ACKN,425264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almLow.UACK,425264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almLow.MCmd_Enable,425264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almLow.MCmd_Disable,425264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almLow.OCmd_Shelve,425264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almLow.OCmd_Unshelve,425264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almLow.SCmd_Suppress,425264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almLow.SCmd_UnSuppress,425265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almLow.AEShelveTMRDN,425265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almLow.Bad,425265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almLow.Suppress,425266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.UnSuppress,425266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Shelve,425266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.UnShelve,425266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Enable,425266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Disable,425266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Ack,425266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Reset,425266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almLow.Suppressed,425266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almLow.Shelved,425266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almLow.Disabled,425266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almLow.Acked,425266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almLow.Alarm,425266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Fault,425276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almLowLow.AlarmState,425276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almLowLow.GlobalReset,425276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almLowLow.FaultInAlarm,425276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almLowLow.ALRM,425276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almLowLow.ANUN,425276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almLowLow.AKED,425276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almLowLow.Resetable,425276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almLowLow.REST,425276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almLowLow.ACKN,425276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almLowLow.UACK,425276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almLowLow.MCmd_Enable,425276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almLowLow.MCmd_Disable,425276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almLowLow.OCmd_Shelve,425276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almLowLow.OCmd_Unshelve,425276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almLowLow.SCmd_Suppress,425276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almLowLow.SCmd_UnSuppress,425277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almLowLow.AEShelveTMRDN,425277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almLowLow.Bad,425277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almLowLow.Suppress,425278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.UnSuppress,425278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Shelve,425278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.UnShelve,425278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Enable,425278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Disable,425278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Ack,425278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Reset,425278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Suppressed,425278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Shelved,425278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Disabled,425278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Acked,425278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almLowLow.Alarm,425278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Fault,425288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almBrokenLoop.AlarmState,425288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almBrokenLoop.GlobalReset,425288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almBrokenLoop.FaultInAlarm,425288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almBrokenLoop.ALRM,425288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almBrokenLoop.ANUN,425288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almBrokenLoop.AKED,425288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almBrokenLoop.Resetable,425288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almBrokenLoop.REST,425288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almBrokenLoop.ACKN,425288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almBrokenLoop.UACK,425288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almBrokenLoop.MCmd_Enable,425288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.MCmd_Disable,425288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.OCmd_Shelve,425288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.OCmd_Unshelve,425288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.SCmd_Suppress,425288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.SCmd_UnSuppress,425289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almBrokenLoop.AEShelveTMRDN,425289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almBrokenLoop.Bad,425289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almBrokenLoop.Suppress,425290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.UnSuppress,425290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Shelve,425290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.UnShelve,425290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Enable,425290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Disable,425290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Ack,425290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Reset,425290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Suppressed,425290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Shelved,425290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Disabled,425290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Acked,425290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.Alarm,425290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Fault,425300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almOverRange.AlarmState,425300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almOverRange.GlobalReset,425300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almOverRange.FaultInAlarm,425300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almOverRange.ALRM,425300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almOverRange.ANUN,425300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almOverRange.AKED,425300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almOverRange.Resetable,425300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almOverRange.REST,425300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almOverRange.ACKN,425300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almOverRange.UACK,425300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almOverRange.MCmd_Enable,425300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almOverRange.MCmd_Disable,425300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almOverRange.OCmd_Shelve,425300.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almOverRange.OCmd_Unshelve,425300.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almOverRange.SCmd_Suppress,425300.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almOverRange.SCmd_UnSuppress,425301.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almOverRange.AEShelveTMRDN,425301.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almOverRange.Bad,425301.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almOverRange.Suppress,425302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.UnSuppress,425302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Shelve,425302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.UnShelve,425302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Enable,425302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Disable,425302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Ack,425302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Reset,425302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Suppressed,425302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Shelved,425302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Disabled,425302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Acked,425302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almOverRange.Alarm,425302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Fault,425312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almUnderRange.AlarmState,425312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almUnderRange.GlobalReset,425312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almUnderRange.FaultInAlarm,425312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almUnderRange.ALRM,425312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almUnderRange.ANUN,425312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almUnderRange.AKED,425312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almUnderRange.Resetable,425312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almUnderRange.REST,425312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almUnderRange.ACKN,425312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almUnderRange.UACK,425312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almUnderRange.MCmd_Enable,425312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.MCmd_Disable,425312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.OCmd_Shelve,425312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.OCmd_Unshelve,425312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.SCmd_Suppress,425312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.SCmd_UnSuppress,425313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almUnderRange.AEShelveTMRDN,425313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almUnderRange.Bad,425313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almUnderRange.Suppress,425314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.UnSuppress,425314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Shelve,425314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.UnShelve,425314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Enable,425314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Disable,425314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Ack,425314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Reset,425314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Suppressed,425314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Shelved,425314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Disabled,425314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Acked,425314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almUnderRange.Alarm,425314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Fault,425324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almRateOfChange.AlarmState,425324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almRateOfChange.GlobalReset,425324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almRateOfChange.FaultInAlarm,425324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almRateOfChange.ALRM,425324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almRateOfChange.ANUN,425324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almRateOfChange.AKED,425324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almRateOfChange.Resetable,425324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almRateOfChange.REST,425324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almRateOfChange.ACKN,425324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almRateOfChange.UACK,425324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almRateOfChange.MCmd_Enable,425324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.MCmd_Disable,425324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.OCmd_Shelve,425324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.OCmd_Unshelve,425324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.SCmd_Suppress,425324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.SCmd_UnSuppress,425325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almRateOfChange.AEShelveTMRDN,425325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almRateOfChange.Bad,425325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almRateOfChange.Suppress,425326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.UnSuppress,425326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Shelve,425326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.UnShelve,425326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Enable,425326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Disable,425326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Ack,425326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Reset,425326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Suppressed,425326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Shelved,425326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Disabled,425326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Acked,425326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almRateOfChange.Alarm,425326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Fault,425336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI4.almPLCFault.AlarmState,425336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI4.almPLCFault.GlobalReset,425336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI4.almPLCFault.FaultInAlarm,425336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI4.almPLCFault.ALRM,425336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI4.almPLCFault.ANUN,425336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI4.almPLCFault.AKED,425336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI4.almPLCFault.Resetable,425336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI4.almPLCFault.REST,425336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI4.almPLCFault.ACKN,425336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI4.almPLCFault.UACK,425336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI4.almPLCFault.MCmd_Enable,425336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.MCmd_Disable,425336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.OCmd_Shelve,425336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.OCmd_Unshelve,425336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.SCmd_Suppress,425336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.SCmd_UnSuppress,425337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI4.almPLCFault.AEShelveTMRDN,425337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI4.almPLCFault.Bad,425337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI4.almPLCFault.Suppress,425338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.UnSuppress,425338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Shelve,425338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.UnShelve,425338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Enable,425338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Disable,425338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Ack,425338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Reset,425338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Suppressed,425338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Shelved,425338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Disabled,425338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Acked,425338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI4.almPLCFault.Alarm,425338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Fault,425440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almHighHigh.AlarmState,425440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almHighHigh.GlobalReset,425440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almHighHigh.FaultInAlarm,425440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almHighHigh.ALRM,425440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almHighHigh.ANUN,425440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almHighHigh.AKED,425440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almHighHigh.Resetable,425440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almHighHigh.REST,425440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almHighHigh.ACKN,425440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almHighHigh.UACK,425440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almHighHigh.MCmd_Enable,425440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.MCmd_Disable,425440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.OCmd_Shelve,425440.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.OCmd_Unshelve,425440.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.SCmd_Suppress,425440.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.SCmd_UnSuppress,425441.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almHighHigh.AEShelveTMRDN,425441.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almHighHigh.Bad,425441.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almHighHigh.Suppress,425442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.UnSuppress,425442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Shelve,425442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.UnShelve,425442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Enable,425442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Disable,425442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Ack,425442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Reset,425442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Suppressed,425442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Shelved,425442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Disabled,425442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Acked,425442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almHighHigh.Alarm,425442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Fault,425452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almHigh.AlarmState,425452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almHigh.GlobalReset,425452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almHigh.FaultInAlarm,425452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almHigh.ALRM,425452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almHigh.ANUN,425452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almHigh.AKED,425452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almHigh.Resetable,425452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almHigh.REST,425452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almHigh.ACKN,425452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almHigh.UACK,425452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almHigh.MCmd_Enable,425452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almHigh.MCmd_Disable,425452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almHigh.OCmd_Shelve,425452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almHigh.OCmd_Unshelve,425452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almHigh.SCmd_Suppress,425452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almHigh.SCmd_UnSuppress,425453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almHigh.AEShelveTMRDN,425453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almHigh.Bad,425453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almHigh.Suppress,425454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.UnSuppress,425454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Shelve,425454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.UnShelve,425454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Enable,425454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Disable,425454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Ack,425454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Reset,425454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almHigh.Suppressed,425454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almHigh.Shelved,425454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almHigh.Disabled,425454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almHigh.Acked,425454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almHigh.Alarm,425454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Fault,425464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almLow.AlarmState,425464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almLow.GlobalReset,425464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almLow.FaultInAlarm,425464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almLow.ALRM,425464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almLow.ANUN,425464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almLow.AKED,425464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almLow.Resetable,425464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almLow.REST,425464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almLow.ACKN,425464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almLow.UACK,425464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almLow.MCmd_Enable,425464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almLow.MCmd_Disable,425464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almLow.OCmd_Shelve,425464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almLow.OCmd_Unshelve,425464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almLow.SCmd_Suppress,425464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almLow.SCmd_UnSuppress,425465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almLow.AEShelveTMRDN,425465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almLow.Bad,425465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almLow.Suppress,425466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.UnSuppress,425466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Shelve,425466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.UnShelve,425466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Enable,425466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Disable,425466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Ack,425466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Reset,425466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almLow.Suppressed,425466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almLow.Shelved,425466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almLow.Disabled,425466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almLow.Acked,425466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almLow.Alarm,425466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Fault,425476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almLowLow.AlarmState,425476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almLowLow.GlobalReset,425476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almLowLow.FaultInAlarm,425476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almLowLow.ALRM,425476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almLowLow.ANUN,425476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almLowLow.AKED,425476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almLowLow.Resetable,425476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almLowLow.REST,425476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almLowLow.ACKN,425476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almLowLow.UACK,425476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almLowLow.MCmd_Enable,425476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almLowLow.MCmd_Disable,425476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almLowLow.OCmd_Shelve,425476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almLowLow.OCmd_Unshelve,425476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almLowLow.SCmd_Suppress,425476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almLowLow.SCmd_UnSuppress,425477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almLowLow.AEShelveTMRDN,425477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almLowLow.Bad,425477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almLowLow.Suppress,425478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.UnSuppress,425478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Shelve,425478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.UnShelve,425478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Enable,425478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Disable,425478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Ack,425478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Reset,425478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Suppressed,425478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Shelved,425478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Disabled,425478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Acked,425478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almLowLow.Alarm,425478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Fault,425488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almBrokenLoop.AlarmState,425488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almBrokenLoop.GlobalReset,425488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almBrokenLoop.FaultInAlarm,425488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almBrokenLoop.ALRM,425488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almBrokenLoop.ANUN,425488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almBrokenLoop.AKED,425488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almBrokenLoop.Resetable,425488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almBrokenLoop.REST,425488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almBrokenLoop.ACKN,425488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almBrokenLoop.UACK,425488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almBrokenLoop.MCmd_Enable,425488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.MCmd_Disable,425488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.OCmd_Shelve,425488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.OCmd_Unshelve,425488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.SCmd_Suppress,425488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.SCmd_UnSuppress,425489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almBrokenLoop.AEShelveTMRDN,425489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almBrokenLoop.Bad,425489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almBrokenLoop.Suppress,425490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.UnSuppress,425490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Shelve,425490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.UnShelve,425490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Enable,425490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Disable,425490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Ack,425490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Reset,425490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Suppressed,425490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Shelved,425490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Disabled,425490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Acked,425490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.Alarm,425490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Fault,425500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almOverRange.AlarmState,425500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almOverRange.GlobalReset,425500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almOverRange.FaultInAlarm,425500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almOverRange.ALRM,425500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almOverRange.ANUN,425500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almOverRange.AKED,425500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almOverRange.Resetable,425500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almOverRange.REST,425500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almOverRange.ACKN,425500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almOverRange.UACK,425500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almOverRange.MCmd_Enable,425500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almOverRange.MCmd_Disable,425500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almOverRange.OCmd_Shelve,425500.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almOverRange.OCmd_Unshelve,425500.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almOverRange.SCmd_Suppress,425500.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almOverRange.SCmd_UnSuppress,425501.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almOverRange.AEShelveTMRDN,425501.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almOverRange.Bad,425501.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almOverRange.Suppress,425502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.UnSuppress,425502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Shelve,425502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.UnShelve,425502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Enable,425502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Disable,425502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Ack,425502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Reset,425502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Suppressed,425502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Shelved,425502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Disabled,425502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Acked,425502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almOverRange.Alarm,425502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Fault,425512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almUnderRange.AlarmState,425512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almUnderRange.GlobalReset,425512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almUnderRange.FaultInAlarm,425512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almUnderRange.ALRM,425512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almUnderRange.ANUN,425512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almUnderRange.AKED,425512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almUnderRange.Resetable,425512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almUnderRange.REST,425512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almUnderRange.ACKN,425512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almUnderRange.UACK,425512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almUnderRange.MCmd_Enable,425512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.MCmd_Disable,425512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.OCmd_Shelve,425512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.OCmd_Unshelve,425512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.SCmd_Suppress,425512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.SCmd_UnSuppress,425513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almUnderRange.AEShelveTMRDN,425513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almUnderRange.Bad,425513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almUnderRange.Suppress,425514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.UnSuppress,425514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Shelve,425514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.UnShelve,425514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Enable,425514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Disable,425514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Ack,425514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Reset,425514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Suppressed,425514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Shelved,425514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Disabled,425514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Acked,425514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almUnderRange.Alarm,425514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Fault,425524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almRateOfChange.AlarmState,425524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almRateOfChange.GlobalReset,425524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almRateOfChange.FaultInAlarm,425524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almRateOfChange.ALRM,425524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almRateOfChange.ANUN,425524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almRateOfChange.AKED,425524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almRateOfChange.Resetable,425524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almRateOfChange.REST,425524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almRateOfChange.ACKN,425524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almRateOfChange.UACK,425524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almRateOfChange.MCmd_Enable,425524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.MCmd_Disable,425524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.OCmd_Shelve,425524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.OCmd_Unshelve,425524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.SCmd_Suppress,425524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.SCmd_UnSuppress,425525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almRateOfChange.AEShelveTMRDN,425525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almRateOfChange.Bad,425525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almRateOfChange.Suppress,425526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.UnSuppress,425526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Shelve,425526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.UnShelve,425526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Enable,425526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Disable,425526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Ack,425526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Reset,425526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Suppressed,425526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Shelved,425526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Disabled,425526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Acked,425526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almRateOfChange.Alarm,425526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Fault,425536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PMP_0103_9_VI5.almPLCFault.AlarmState,425536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PMP_0103_9_VI5.almPLCFault.GlobalReset,425536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PMP_0103_9_VI5.almPLCFault.FaultInAlarm,425536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PMP_0103_9_VI5.almPLCFault.ALRM,425536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PMP_0103_9_VI5.almPLCFault.ANUN,425536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PMP_0103_9_VI5.almPLCFault.AKED,425536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PMP_0103_9_VI5.almPLCFault.Resetable,425536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PMP_0103_9_VI5.almPLCFault.REST,425536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PMP_0103_9_VI5.almPLCFault.ACKN,425536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PMP_0103_9_VI5.almPLCFault.UACK,425536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PMP_0103_9_VI5.almPLCFault.MCmd_Enable,425536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.MCmd_Disable,425536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.OCmd_Shelve,425536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.OCmd_Unshelve,425536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.SCmd_Suppress,425536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.SCmd_UnSuppress,425537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PMP_0103_9_VI5.almPLCFault.AEShelveTMRDN,425537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PMP_0103_9_VI5.almPLCFault.Bad,425537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PMP_0103_9_VI5.almPLCFault.Suppress,425538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.UnSuppress,425538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Shelve,425538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.UnShelve,425538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Enable,425538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Disable,425538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Ack,425538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Reset,425538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Suppressed,425538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Shelved,425538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Disabled,425538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Acked,425538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PMP_0103_9_VI5.almPLCFault.Alarm,425538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Fault,425640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almHighHigh.AlarmState,425640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almHighHigh.GlobalReset,425640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almHighHigh.FaultInAlarm,425640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almHighHigh.ALRM,425640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almHighHigh.ANUN,425640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almHighHigh.AKED,425640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almHighHigh.Resetable,425640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almHighHigh.REST,425640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almHighHigh.ACKN,425640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almHighHigh.UACK,425640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almHighHigh.MCmd_Enable,425640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almHighHigh.MCmd_Disable,425640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almHighHigh.OCmd_Shelve,425640.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almHighHigh.OCmd_Unshelve,425640.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almHighHigh.SCmd_Suppress,425640.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almHighHigh.SCmd_UnSuppress,425641.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almHighHigh.AEShelveTMRDN,425641.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almHighHigh.Bad,425641.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almHighHigh.Suppress,425642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.UnSuppress,425642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Shelve,425642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.UnShelve,425642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Enable,425642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Disable,425642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Ack,425642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Reset,425642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almHighHigh.Suppressed,425642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almHighHigh.Shelved,425642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almHighHigh.Disabled,425642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almHighHigh.Acked,425642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almHighHigh.Alarm,425642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Fault,425652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almHigh.AlarmState,425652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almHigh.GlobalReset,425652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almHigh.FaultInAlarm,425652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almHigh.ALRM,425652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almHigh.ANUN,425652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almHigh.AKED,425652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almHigh.Resetable,425652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almHigh.REST,425652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almHigh.ACKN,425652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almHigh.UACK,425652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almHigh.MCmd_Enable,425652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almHigh.MCmd_Disable,425652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almHigh.OCmd_Shelve,425652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almHigh.OCmd_Unshelve,425652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almHigh.SCmd_Suppress,425652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almHigh.SCmd_UnSuppress,425653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almHigh.AEShelveTMRDN,425653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almHigh.Bad,425653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almHigh.Suppress,425654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.UnSuppress,425654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Shelve,425654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.UnShelve,425654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Enable,425654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Disable,425654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Ack,425654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Reset,425654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almHigh.Suppressed,425654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almHigh.Shelved,425654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almHigh.Disabled,425654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almHigh.Acked,425654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almHigh.Alarm,425654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.Fault,425664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almLow.AlarmState,425664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almLow.GlobalReset,425664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almLow.FaultInAlarm,425664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almLow.ALRM,425664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almLow.ANUN,425664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almLow.AKED,425664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almLow.Resetable,425664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almLow.REST,425664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almLow.ACKN,425664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almLow.UACK,425664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almLow.MCmd_Enable,425664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almLow.MCmd_Disable,425664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almLow.OCmd_Shelve,425664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almLow.OCmd_Unshelve,425664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almLow.SCmd_Suppress,425664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almLow.SCmd_UnSuppress,425665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almLow.AEShelveTMRDN,425665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almLow.Bad,425665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almLow.Suppress,425666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.UnSuppress,425666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.Shelve,425666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.UnShelve,425666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.Enable,425666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.Disable,425666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLow.Ack,425666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almLow.Reset,425666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almLow.Suppressed,425666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almLow.Shelved,425666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almLow.Disabled,425666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almLow.Acked,425666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almLow.Alarm,425666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Fault,425676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almLowLow.AlarmState,425676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almLowLow.GlobalReset,425676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almLowLow.FaultInAlarm,425676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almLowLow.ALRM,425676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almLowLow.ANUN,425676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almLowLow.AKED,425676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almLowLow.Resetable,425676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almLowLow.REST,425676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almLowLow.ACKN,425676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almLowLow.UACK,425676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almLowLow.MCmd_Enable,425676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almLowLow.MCmd_Disable,425676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almLowLow.OCmd_Shelve,425676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almLowLow.OCmd_Unshelve,425676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almLowLow.SCmd_Suppress,425676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almLowLow.SCmd_UnSuppress,425677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almLowLow.AEShelveTMRDN,425677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almLowLow.Bad,425677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almLowLow.Suppress,425678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.UnSuppress,425678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Shelve,425678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.UnShelve,425678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Enable,425678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Disable,425678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Ack,425678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Reset,425678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almLowLow.Suppressed,425678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almLowLow.Shelved,425678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almLowLow.Disabled,425678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almLowLow.Acked,425678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almLowLow.Alarm,425678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Fault,425688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almBrokenLoop.AlarmState,425688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almBrokenLoop.GlobalReset,425688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almBrokenLoop.FaultInAlarm,425688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almBrokenLoop.ALRM,425688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almBrokenLoop.ANUN,425688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almBrokenLoop.AKED,425688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almBrokenLoop.Resetable,425688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almBrokenLoop.REST,425688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almBrokenLoop.ACKN,425688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almBrokenLoop.UACK,425688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almBrokenLoop.MCmd_Enable,425688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.MCmd_Disable,425688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.OCmd_Shelve,425688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.OCmd_Unshelve,425688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.SCmd_Suppress,425688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.SCmd_UnSuppress,425689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almBrokenLoop.AEShelveTMRDN,425689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almBrokenLoop.Bad,425689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almBrokenLoop.Suppress,425690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.UnSuppress,425690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Shelve,425690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.UnShelve,425690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Enable,425690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Disable,425690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Ack,425690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Reset,425690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Suppressed,425690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Shelved,425690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Disabled,425690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Acked,425690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almBrokenLoop.Alarm,425690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Fault,425700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almOverRange.AlarmState,425700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almOverRange.GlobalReset,425700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almOverRange.FaultInAlarm,425700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almOverRange.ALRM,425700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almOverRange.ANUN,425700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almOverRange.AKED,425700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almOverRange.Resetable,425700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almOverRange.REST,425700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almOverRange.ACKN,425700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almOverRange.UACK,425700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almOverRange.MCmd_Enable,425700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almOverRange.MCmd_Disable,425700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almOverRange.OCmd_Shelve,425700.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almOverRange.OCmd_Unshelve,425700.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almOverRange.SCmd_Suppress,425700.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almOverRange.SCmd_UnSuppress,425701.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almOverRange.AEShelveTMRDN,425701.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almOverRange.Bad,425701.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almOverRange.Suppress,425702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.UnSuppress,425702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Shelve,425702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.UnShelve,425702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Enable,425702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Disable,425702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Ack,425702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Reset,425702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almOverRange.Suppressed,425702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almOverRange.Shelved,425702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almOverRange.Disabled,425702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almOverRange.Acked,425702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almOverRange.Alarm,425702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Fault,425712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almUnderRange.AlarmState,425712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almUnderRange.GlobalReset,425712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almUnderRange.FaultInAlarm,425712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almUnderRange.ALRM,425712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almUnderRange.ANUN,425712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almUnderRange.AKED,425712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almUnderRange.Resetable,425712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almUnderRange.REST,425712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almUnderRange.ACKN,425712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almUnderRange.UACK,425712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almUnderRange.MCmd_Enable,425712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almUnderRange.MCmd_Disable,425712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almUnderRange.OCmd_Shelve,425712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almUnderRange.OCmd_Unshelve,425712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almUnderRange.SCmd_Suppress,425712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almUnderRange.SCmd_UnSuppress,425713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almUnderRange.AEShelveTMRDN,425713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almUnderRange.Bad,425713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almUnderRange.Suppress,425714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.UnSuppress,425714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Shelve,425714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.UnShelve,425714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Enable,425714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Disable,425714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Ack,425714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Reset,425714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almUnderRange.Suppressed,425714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almUnderRange.Shelved,425714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almUnderRange.Disabled,425714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almUnderRange.Acked,425714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almUnderRange.Alarm,425714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Fault,425724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almRateOfChange.AlarmState,425724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almRateOfChange.GlobalReset,425724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almRateOfChange.FaultInAlarm,425724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almRateOfChange.ALRM,425724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almRateOfChange.ANUN,425724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almRateOfChange.AKED,425724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almRateOfChange.Resetable,425724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almRateOfChange.REST,425724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almRateOfChange.ACKN,425724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almRateOfChange.UACK,425724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almRateOfChange.MCmd_Enable,425724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almRateOfChange.MCmd_Disable,425724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almRateOfChange.OCmd_Shelve,425724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almRateOfChange.OCmd_Unshelve,425724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almRateOfChange.SCmd_Suppress,425724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almRateOfChange.SCmd_UnSuppress,425725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almRateOfChange.AEShelveTMRDN,425725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almRateOfChange.Bad,425725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almRateOfChange.Suppress,425726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.UnSuppress,425726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Shelve,425726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.UnShelve,425726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Enable,425726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Disable,425726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Ack,425726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Reset,425726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Suppressed,425726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Shelved,425726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Disabled,425726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Acked,425726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almRateOfChange.Alarm,425726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Fault,425736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0111_1_TI.almPLCFault.AlarmState,425736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0111_1_TI.almPLCFault.GlobalReset,425736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0111_1_TI.almPLCFault.FaultInAlarm,425736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0111_1_TI.almPLCFault.ALRM,425736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0111_1_TI.almPLCFault.ANUN,425736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0111_1_TI.almPLCFault.AKED,425736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0111_1_TI.almPLCFault.Resetable,425736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0111_1_TI.almPLCFault.REST,425736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0111_1_TI.almPLCFault.ACKN,425736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0111_1_TI.almPLCFault.UACK,425736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0111_1_TI.almPLCFault.MCmd_Enable,425736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0111_1_TI.almPLCFault.MCmd_Disable,425736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0111_1_TI.almPLCFault.OCmd_Shelve,425736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0111_1_TI.almPLCFault.OCmd_Unshelve,425736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0111_1_TI.almPLCFault.SCmd_Suppress,425736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0111_1_TI.almPLCFault.SCmd_UnSuppress,425737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0111_1_TI.almPLCFault.AEShelveTMRDN,425737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0111_1_TI.almPLCFault.Bad,425737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0111_1_TI.almPLCFault.Suppress,425738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.UnSuppress,425738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Shelve,425738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.UnShelve,425738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Enable,425738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Disable,425738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Ack,425738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Reset,425738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0111_1_TI.almPLCFault.Suppressed,425738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0111_1_TI.almPLCFault.Shelved,425738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0111_1_TI.almPLCFault.Disabled,425738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0111_1_TI.almPLCFault.Acked,425738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0111_1_TI.almPLCFault.Alarm,425738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Fault,425840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almHighHigh.AlarmState,425840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almHighHigh.GlobalReset,425840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almHighHigh.FaultInAlarm,425840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almHighHigh.ALRM,425840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almHighHigh.ANUN,425840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almHighHigh.AKED,425840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almHighHigh.Resetable,425840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almHighHigh.REST,425840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almHighHigh.ACKN,425840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almHighHigh.UACK,425840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almHighHigh.MCmd_Enable,425840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almHighHigh.MCmd_Disable,425840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almHighHigh.OCmd_Shelve,425840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almHighHigh.OCmd_Unshelve,425840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almHighHigh.SCmd_Suppress,425840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almHighHigh.SCmd_UnSuppress,425841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almHighHigh.AEShelveTMRDN,425841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almHighHigh.Bad,425841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almHighHigh.Suppress,425842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.UnSuppress,425842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Shelve,425842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.UnShelve,425842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Enable,425842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Disable,425842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Ack,425842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Reset,425842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almHighHigh.Suppressed,425842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almHighHigh.Shelved,425842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almHighHigh.Disabled,425842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almHighHigh.Acked,425842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almHighHigh.Alarm,425842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Fault,425852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almHigh.AlarmState,425852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almHigh.GlobalReset,425852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almHigh.FaultInAlarm,425852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almHigh.ALRM,425852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almHigh.ANUN,425852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almHigh.AKED,425852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almHigh.Resetable,425852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almHigh.REST,425852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almHigh.ACKN,425852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almHigh.UACK,425852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almHigh.MCmd_Enable,425852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almHigh.MCmd_Disable,425852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almHigh.OCmd_Shelve,425852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almHigh.OCmd_Unshelve,425852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almHigh.SCmd_Suppress,425852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almHigh.SCmd_UnSuppress,425853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almHigh.AEShelveTMRDN,425853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almHigh.Bad,425853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almHigh.Suppress,425854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.UnSuppress,425854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Shelve,425854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.UnShelve,425854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Enable,425854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Disable,425854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Ack,425854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Reset,425854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almHigh.Suppressed,425854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almHigh.Shelved,425854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almHigh.Disabled,425854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almHigh.Acked,425854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almHigh.Alarm,425854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.Fault,425864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almLow.AlarmState,425864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almLow.GlobalReset,425864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almLow.FaultInAlarm,425864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almLow.ALRM,425864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almLow.ANUN,425864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almLow.AKED,425864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almLow.Resetable,425864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almLow.REST,425864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almLow.ACKN,425864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almLow.UACK,425864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almLow.MCmd_Enable,425864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almLow.MCmd_Disable,425864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almLow.OCmd_Shelve,425864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almLow.OCmd_Unshelve,425864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almLow.SCmd_Suppress,425864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almLow.SCmd_UnSuppress,425865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almLow.AEShelveTMRDN,425865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almLow.Bad,425865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almLow.Suppress,425866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.UnSuppress,425866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.Shelve,425866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.UnShelve,425866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.Enable,425866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.Disable,425866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLow.Ack,425866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almLow.Reset,425866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almLow.Suppressed,425866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almLow.Shelved,425866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almLow.Disabled,425866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almLow.Acked,425866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almLow.Alarm,425866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Fault,425876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almLowLow.AlarmState,425876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almLowLow.GlobalReset,425876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almLowLow.FaultInAlarm,425876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almLowLow.ALRM,425876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almLowLow.ANUN,425876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almLowLow.AKED,425876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almLowLow.Resetable,425876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almLowLow.REST,425876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almLowLow.ACKN,425876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almLowLow.UACK,425876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almLowLow.MCmd_Enable,425876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almLowLow.MCmd_Disable,425876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almLowLow.OCmd_Shelve,425876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almLowLow.OCmd_Unshelve,425876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almLowLow.SCmd_Suppress,425876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almLowLow.SCmd_UnSuppress,425877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almLowLow.AEShelveTMRDN,425877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almLowLow.Bad,425877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almLowLow.Suppress,425878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.UnSuppress,425878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Shelve,425878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.UnShelve,425878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Enable,425878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Disable,425878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Ack,425878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Reset,425878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almLowLow.Suppressed,425878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almLowLow.Shelved,425878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almLowLow.Disabled,425878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almLowLow.Acked,425878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almLowLow.Alarm,425878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Fault,425888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almBrokenLoop.AlarmState,425888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almBrokenLoop.GlobalReset,425888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almBrokenLoop.FaultInAlarm,425888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almBrokenLoop.ALRM,425888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almBrokenLoop.ANUN,425888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almBrokenLoop.AKED,425888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almBrokenLoop.Resetable,425888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almBrokenLoop.REST,425888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almBrokenLoop.ACKN,425888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almBrokenLoop.UACK,425888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almBrokenLoop.MCmd_Enable,425888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.MCmd_Disable,425888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.OCmd_Shelve,425888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.OCmd_Unshelve,425888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.SCmd_Suppress,425888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.SCmd_UnSuppress,425889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almBrokenLoop.AEShelveTMRDN,425889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almBrokenLoop.Bad,425889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almBrokenLoop.Suppress,425890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.UnSuppress,425890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Shelve,425890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.UnShelve,425890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Enable,425890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Disable,425890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Ack,425890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Reset,425890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Suppressed,425890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Shelved,425890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Disabled,425890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Acked,425890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almBrokenLoop.Alarm,425890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Fault,425900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almOverRange.AlarmState,425900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almOverRange.GlobalReset,425900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almOverRange.FaultInAlarm,425900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almOverRange.ALRM,425900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almOverRange.ANUN,425900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almOverRange.AKED,425900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almOverRange.Resetable,425900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almOverRange.REST,425900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almOverRange.ACKN,425900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almOverRange.UACK,425900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almOverRange.MCmd_Enable,425900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almOverRange.MCmd_Disable,425900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almOverRange.OCmd_Shelve,425900.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almOverRange.OCmd_Unshelve,425900.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almOverRange.SCmd_Suppress,425900.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almOverRange.SCmd_UnSuppress,425901.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almOverRange.AEShelveTMRDN,425901.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almOverRange.Bad,425901.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almOverRange.Suppress,425902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.UnSuppress,425902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Shelve,425902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.UnShelve,425902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Enable,425902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Disable,425902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Ack,425902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Reset,425902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almOverRange.Suppressed,425902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almOverRange.Shelved,425902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almOverRange.Disabled,425902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almOverRange.Acked,425902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almOverRange.Alarm,425902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Fault,425912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almUnderRange.AlarmState,425912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almUnderRange.GlobalReset,425912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almUnderRange.FaultInAlarm,425912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almUnderRange.ALRM,425912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almUnderRange.ANUN,425912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almUnderRange.AKED,425912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almUnderRange.Resetable,425912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almUnderRange.REST,425912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almUnderRange.ACKN,425912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almUnderRange.UACK,425912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almUnderRange.MCmd_Enable,425912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almUnderRange.MCmd_Disable,425912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almUnderRange.OCmd_Shelve,425912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almUnderRange.OCmd_Unshelve,425912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almUnderRange.SCmd_Suppress,425912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almUnderRange.SCmd_UnSuppress,425913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almUnderRange.AEShelveTMRDN,425913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almUnderRange.Bad,425913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almUnderRange.Suppress,425914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.UnSuppress,425914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Shelve,425914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.UnShelve,425914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Enable,425914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Disable,425914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Ack,425914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Reset,425914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almUnderRange.Suppressed,425914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almUnderRange.Shelved,425914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almUnderRange.Disabled,425914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almUnderRange.Acked,425914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almUnderRange.Alarm,425914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Fault,425924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almRateOfChange.AlarmState,425924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almRateOfChange.GlobalReset,425924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almRateOfChange.FaultInAlarm,425924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almRateOfChange.ALRM,425924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almRateOfChange.ANUN,425924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almRateOfChange.AKED,425924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almRateOfChange.Resetable,425924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almRateOfChange.REST,425924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almRateOfChange.ACKN,425924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almRateOfChange.UACK,425924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almRateOfChange.MCmd_Enable,425924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almRateOfChange.MCmd_Disable,425924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almRateOfChange.OCmd_Shelve,425924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almRateOfChange.OCmd_Unshelve,425924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almRateOfChange.SCmd_Suppress,425924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almRateOfChange.SCmd_UnSuppress,425925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almRateOfChange.AEShelveTMRDN,425925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almRateOfChange.Bad,425925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almRateOfChange.Suppress,425926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.UnSuppress,425926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Shelve,425926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.UnShelve,425926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Enable,425926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Disable,425926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Ack,425926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Reset,425926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Suppressed,425926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Shelved,425926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Disabled,425926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Acked,425926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almRateOfChange.Alarm,425926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Fault,425936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TT_0112_1_TI.almPLCFault.AlarmState,425936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TT_0112_1_TI.almPLCFault.GlobalReset,425936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TT_0112_1_TI.almPLCFault.FaultInAlarm,425936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TT_0112_1_TI.almPLCFault.ALRM,425936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TT_0112_1_TI.almPLCFault.ANUN,425936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TT_0112_1_TI.almPLCFault.AKED,425936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TT_0112_1_TI.almPLCFault.Resetable,425936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TT_0112_1_TI.almPLCFault.REST,425936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TT_0112_1_TI.almPLCFault.ACKN,425936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TT_0112_1_TI.almPLCFault.UACK,425936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TT_0112_1_TI.almPLCFault.MCmd_Enable,425936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TT_0112_1_TI.almPLCFault.MCmd_Disable,425936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TT_0112_1_TI.almPLCFault.OCmd_Shelve,425936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TT_0112_1_TI.almPLCFault.OCmd_Unshelve,425936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TT_0112_1_TI.almPLCFault.SCmd_Suppress,425936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TT_0112_1_TI.almPLCFault.SCmd_UnSuppress,425937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TT_0112_1_TI.almPLCFault.AEShelveTMRDN,425937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TT_0112_1_TI.almPLCFault.Bad,425937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TT_0112_1_TI.almPLCFault.Suppress,425938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.UnSuppress,425938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Shelve,425938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.UnShelve,425938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Enable,425938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Disable,425938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Ack,425938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Reset,425938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TT_0112_1_TI.almPLCFault.Suppressed,425938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TT_0112_1_TI.almPLCFault.Shelved,425938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TT_0112_1_TI.almPLCFault.Disabled,425938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TT_0112_1_TI.almPLCFault.Acked,425938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TT_0112_1_TI.almPLCFault.Alarm,425938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Fault,426006.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_FA.Alarm.AlarmState,426006.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_FA.Alarm.GlobalReset,426006.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_FA.Alarm.FaultInAlarm,426006.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_FA.Alarm.ALRM,426006.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_FA.Alarm.ANUN,426006.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_FA.Alarm.AKED,426006.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_FA.Alarm.Resetable,426006.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_FA.Alarm.REST,426006.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_FA.Alarm.ACKN,426006.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_FA.Alarm.UACK,426006.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_FA.Alarm.MCmd_Enable,426006.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_FA.Alarm.MCmd_Disable,426006.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_FA.Alarm.OCmd_Shelve,426006.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_FA.Alarm.OCmd_Unshelve,426006.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_FA.Alarm.SCmd_Suppress,426006.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_FA.Alarm.SCmd_UnSuppress,426007.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_FA.Alarm.AEShelveTMRDN,426007.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_FA.Alarm.Bad,426007.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_FA.Alarm.Suppress,426008.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.UnSuppress,426008.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Shelve,426008.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.UnShelve,426008.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Enable,426008.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Disable,426008.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Ack,426008.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Reset,426008.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_FA.Alarm.Suppressed,426008.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_FA.Alarm.Shelved,426008.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_FA.Alarm.Disabled,426008.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_FA.Alarm.Acked,426008.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_FA.Alarm.Alarm,426008.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Fault,426018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_FA.almPLCFault.AlarmState,426018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_FA.almPLCFault.GlobalReset,426018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_FA.almPLCFault.FaultInAlarm,426018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_FA.almPLCFault.ALRM,426018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_FA.almPLCFault.ANUN,426018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_FA.almPLCFault.AKED,426018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_FA.almPLCFault.Resetable,426018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_FA.almPLCFault.REST,426018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_FA.almPLCFault.ACKN,426018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_FA.almPLCFault.UACK,426018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_FA.almPLCFault.MCmd_Enable,426018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_FA.almPLCFault.MCmd_Disable,426018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_FA.almPLCFault.OCmd_Shelve,426018.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_FA.almPLCFault.OCmd_Unshelve,426018.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_FA.almPLCFault.SCmd_Suppress,426018.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_FA.almPLCFault.SCmd_UnSuppress,426019.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_FA.almPLCFault.AEShelveTMRDN,426019.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_FA.almPLCFault.Bad,426019.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_FA.almPLCFault.Suppress,426020.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.UnSuppress,426020.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Shelve,426020.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.UnShelve,426020.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Enable,426020.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Disable,426020.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Ack,426020.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Reset,426020.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Suppressed,426020.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Shelved,426020.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Disabled,426020.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Acked,426020.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_FA.almPLCFault.Alarm,426020.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Fault,426042.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_MF.Alarm.AlarmState,426042.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_MF.Alarm.GlobalReset,426042.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_MF.Alarm.FaultInAlarm,426042.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MF.Alarm.ALRM,426042.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_MF.Alarm.ANUN,426042.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_MF.Alarm.AKED,426042.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_MF.Alarm.Resetable,426042.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_MF.Alarm.REST,426042.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_MF.Alarm.ACKN,426042.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_MF.Alarm.UACK,426042.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_MF.Alarm.MCmd_Enable,426042.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MF.Alarm.MCmd_Disable,426042.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MF.Alarm.OCmd_Shelve,426042.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_MF.Alarm.OCmd_Unshelve,426042.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_MF.Alarm.SCmd_Suppress,426042.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_MF.Alarm.SCmd_UnSuppress,426043.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_MF.Alarm.AEShelveTMRDN,426043.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_MF.Alarm.Bad,426043.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_MF.Alarm.Suppress,426044.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.UnSuppress,426044.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Shelve,426044.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.UnShelve,426044.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Enable,426044.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Disable,426044.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Ack,426044.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Reset,426044.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_MF.Alarm.Suppressed,426044.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_MF.Alarm.Shelved,426044.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_MF.Alarm.Disabled,426044.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_MF.Alarm.Acked,426044.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_MF.Alarm.Alarm,426044.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Fault,426054.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_MF.almPLCFault.AlarmState,426054.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_MF.almPLCFault.GlobalReset,426054.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_MF.almPLCFault.FaultInAlarm,426054.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MF.almPLCFault.ALRM,426054.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_MF.almPLCFault.ANUN,426054.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_MF.almPLCFault.AKED,426054.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_MF.almPLCFault.Resetable,426054.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_MF.almPLCFault.REST,426054.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_MF.almPLCFault.ACKN,426054.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_MF.almPLCFault.UACK,426054.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_MF.almPLCFault.MCmd_Enable,426054.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MF.almPLCFault.MCmd_Disable,426054.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MF.almPLCFault.OCmd_Shelve,426054.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_MF.almPLCFault.OCmd_Unshelve,426054.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_MF.almPLCFault.SCmd_Suppress,426054.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_MF.almPLCFault.SCmd_UnSuppress,426055.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_MF.almPLCFault.AEShelveTMRDN,426055.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_MF.almPLCFault.Bad,426055.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_MF.almPLCFault.Suppress,426056.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.UnSuppress,426056.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Shelve,426056.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.UnShelve,426056.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Enable,426056.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Disable,426056.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Ack,426056.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Reset,426056.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Suppressed,426056.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Shelved,426056.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Disabled,426056.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Acked,426056.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_MF.almPLCFault.Alarm,426056.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Fault,426076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_MY.Alarm.AlarmState,426076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_MY.Alarm.GlobalReset,426076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_MY.Alarm.FaultInAlarm,426076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MY.Alarm.ALRM,426076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_MY.Alarm.ANUN,426076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_MY.Alarm.AKED,426076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_MY.Alarm.Resetable,426076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_MY.Alarm.REST,426076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_MY.Alarm.ACKN,426076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_MY.Alarm.UACK,426076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_MY.Alarm.MCmd_Enable,426076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MY.Alarm.MCmd_Disable,426076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MY.Alarm.OCmd_Shelve,426076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_MY.Alarm.OCmd_Unshelve,426076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_MY.Alarm.SCmd_Suppress,426076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_MY.Alarm.SCmd_UnSuppress,426077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_MY.Alarm.AEShelveTMRDN,426077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_MY.Alarm.Bad,426077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_MY.Alarm.Suppress,426078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.UnSuppress,426078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Shelve,426078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.UnShelve,426078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Enable,426078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Disable,426078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Ack,426078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Reset,426078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_MY.Alarm.Suppressed,426078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_MY.Alarm.Shelved,426078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_MY.Alarm.Disabled,426078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_MY.Alarm.Acked,426078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_MY.Alarm.Alarm,426078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Fault,426088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_MY.almPLCFault.AlarmState,426088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_MY.almPLCFault.GlobalReset,426088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_MY.almPLCFault.FaultInAlarm,426088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_MY.almPLCFault.ALRM,426088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_MY.almPLCFault.ANUN,426088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_MY.almPLCFault.AKED,426088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_MY.almPLCFault.Resetable,426088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_MY.almPLCFault.REST,426088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_MY.almPLCFault.ACKN,426088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_MY.almPLCFault.UACK,426088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_MY.almPLCFault.MCmd_Enable,426088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_MY.almPLCFault.MCmd_Disable,426088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_MY.almPLCFault.OCmd_Shelve,426088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_MY.almPLCFault.OCmd_Unshelve,426088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_MY.almPLCFault.SCmd_Suppress,426088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_MY.almPLCFault.SCmd_UnSuppress,426089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_MY.almPLCFault.AEShelveTMRDN,426089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_MY.almPLCFault.Bad,426089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_MY.almPLCFault.Suppress,426090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.UnSuppress,426090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Shelve,426090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.UnShelve,426090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Enable,426090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Disable,426090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Ack,426090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Reset,426090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Suppressed,426090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Shelved,426090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Disabled,426090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Acked,426090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_MY.almPLCFault.Alarm,426090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Fault,426112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UA.Alarm.AlarmState,426112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UA.Alarm.GlobalReset,426112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UA.Alarm.FaultInAlarm,426112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UA.Alarm.ALRM,426112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UA.Alarm.ANUN,426112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UA.Alarm.AKED,426112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UA.Alarm.Resetable,426112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UA.Alarm.REST,426112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UA.Alarm.ACKN,426112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UA.Alarm.UACK,426112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UA.Alarm.MCmd_Enable,426112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UA.Alarm.MCmd_Disable,426112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UA.Alarm.OCmd_Shelve,426112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UA.Alarm.OCmd_Unshelve,426112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UA.Alarm.SCmd_Suppress,426112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UA.Alarm.SCmd_UnSuppress,426113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UA.Alarm.AEShelveTMRDN,426113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UA.Alarm.Bad,426113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UA.Alarm.Suppress,426114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.UnSuppress,426114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Shelve,426114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.UnShelve,426114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Enable,426114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Disable,426114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Ack,426114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Reset,426114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UA.Alarm.Suppressed,426114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UA.Alarm.Shelved,426114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UA.Alarm.Disabled,426114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UA.Alarm.Acked,426114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UA.Alarm.Alarm,426114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Fault,426124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UA.almPLCFault.AlarmState,426124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UA.almPLCFault.GlobalReset,426124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UA.almPLCFault.FaultInAlarm,426124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UA.almPLCFault.ALRM,426124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UA.almPLCFault.ANUN,426124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UA.almPLCFault.AKED,426124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UA.almPLCFault.Resetable,426124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UA.almPLCFault.REST,426124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UA.almPLCFault.ACKN,426124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UA.almPLCFault.UACK,426124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UA.almPLCFault.MCmd_Enable,426124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UA.almPLCFault.MCmd_Disable,426124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UA.almPLCFault.OCmd_Shelve,426124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UA.almPLCFault.OCmd_Unshelve,426124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UA.almPLCFault.SCmd_Suppress,426124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UA.almPLCFault.SCmd_UnSuppress,426125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UA.almPLCFault.AEShelveTMRDN,426125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UA.almPLCFault.Bad,426125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UA.almPLCFault.Suppress,426126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.UnSuppress,426126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Shelve,426126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.UnShelve,426126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Enable,426126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Disable,426126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Ack,426126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Reset,426126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Suppressed,426126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Shelved,426126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Disabled,426126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Acked,426126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UA.almPLCFault.Alarm,426126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Fault,426146.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UH.Alarm.AlarmState,426146.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UH.Alarm.GlobalReset,426146.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UH.Alarm.FaultInAlarm,426146.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UH.Alarm.ALRM,426146.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UH.Alarm.ANUN,426146.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UH.Alarm.AKED,426146.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UH.Alarm.Resetable,426146.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UH.Alarm.REST,426146.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UH.Alarm.ACKN,426146.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UH.Alarm.UACK,426146.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UH.Alarm.MCmd_Enable,426146.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UH.Alarm.MCmd_Disable,426146.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UH.Alarm.OCmd_Shelve,426146.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UH.Alarm.OCmd_Unshelve,426146.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UH.Alarm.SCmd_Suppress,426146.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UH.Alarm.SCmd_UnSuppress,426147.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UH.Alarm.AEShelveTMRDN,426147.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UH.Alarm.Bad,426147.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UH.Alarm.Suppress,426148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.UnSuppress,426148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Shelve,426148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.UnShelve,426148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Enable,426148.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Disable,426148.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Ack,426148.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Reset,426148.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UH.Alarm.Suppressed,426148.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UH.Alarm.Shelved,426148.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UH.Alarm.Disabled,426148.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UH.Alarm.Acked,426148.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UH.Alarm.Alarm,426148.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Fault,426158.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UH.almPLCFault.AlarmState,426158.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UH.almPLCFault.GlobalReset,426158.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UH.almPLCFault.FaultInAlarm,426158.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UH.almPLCFault.ALRM,426158.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UH.almPLCFault.ANUN,426158.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UH.almPLCFault.AKED,426158.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UH.almPLCFault.Resetable,426158.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UH.almPLCFault.REST,426158.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UH.almPLCFault.ACKN,426158.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UH.almPLCFault.UACK,426158.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UH.almPLCFault.MCmd_Enable,426158.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UH.almPLCFault.MCmd_Disable,426158.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UH.almPLCFault.OCmd_Shelve,426158.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UH.almPLCFault.OCmd_Unshelve,426158.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UH.almPLCFault.SCmd_Suppress,426158.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UH.almPLCFault.SCmd_UnSuppress,426159.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UH.almPLCFault.AEShelveTMRDN,426159.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UH.almPLCFault.Bad,426159.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UH.almPLCFault.Suppress,426160.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.UnSuppress,426160.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Shelve,426160.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.UnShelve,426160.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Enable,426160.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Disable,426160.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Ack,426160.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Reset,426160.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Suppressed,426160.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Shelved,426160.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Disabled,426160.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Acked,426160.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UH.almPLCFault.Alarm,426160.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Fault,426182.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UY.Alarm.AlarmState,426182.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UY.Alarm.GlobalReset,426182.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UY.Alarm.FaultInAlarm,426182.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UY.Alarm.ALRM,426182.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UY.Alarm.ANUN,426182.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UY.Alarm.AKED,426182.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UY.Alarm.Resetable,426182.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UY.Alarm.REST,426182.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UY.Alarm.ACKN,426182.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UY.Alarm.UACK,426182.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UY.Alarm.MCmd_Enable,426182.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UY.Alarm.MCmd_Disable,426182.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UY.Alarm.OCmd_Shelve,426182.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UY.Alarm.OCmd_Unshelve,426182.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UY.Alarm.SCmd_Suppress,426182.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UY.Alarm.SCmd_UnSuppress,426183.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UY.Alarm.AEShelveTMRDN,426183.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UY.Alarm.Bad,426183.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UY.Alarm.Suppress,426184.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.UnSuppress,426184.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Shelve,426184.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.UnShelve,426184.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Enable,426184.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Disable,426184.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Ack,426184.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Reset,426184.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UY.Alarm.Suppressed,426184.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UY.Alarm.Shelved,426184.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UY.Alarm.Disabled,426184.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UY.Alarm.Acked,426184.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UY.Alarm.Alarm,426184.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Fault,426194.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_UY.almPLCFault.AlarmState,426194.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_UY.almPLCFault.GlobalReset,426194.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_UY.almPLCFault.FaultInAlarm,426194.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_UY.almPLCFault.ALRM,426194.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_UY.almPLCFault.ANUN,426194.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_UY.almPLCFault.AKED,426194.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_UY.almPLCFault.Resetable,426194.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_UY.almPLCFault.REST,426194.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_UY.almPLCFault.ACKN,426194.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_UY.almPLCFault.UACK,426194.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_UY.almPLCFault.MCmd_Enable,426194.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_UY.almPLCFault.MCmd_Disable,426194.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_UY.almPLCFault.OCmd_Shelve,426194.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_UY.almPLCFault.OCmd_Unshelve,426194.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_UY.almPLCFault.SCmd_Suppress,426194.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_UY.almPLCFault.SCmd_UnSuppress,426195.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_UY.almPLCFault.AEShelveTMRDN,426195.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_UY.almPLCFault.Bad,426195.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_UY.almPLCFault.Suppress,426196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.UnSuppress,426196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Shelve,426196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.UnShelve,426196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Enable,426196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Disable,426196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Ack,426196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Reset,426196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Suppressed,426196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Shelved,426196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Disabled,426196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Acked,426196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_UY.almPLCFault.Alarm,426196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Fault,426216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_XF.Alarm.AlarmState,426216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_XF.Alarm.GlobalReset,426216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_XF.Alarm.FaultInAlarm,426216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_XF.Alarm.ALRM,426216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_XF.Alarm.ANUN,426216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_XF.Alarm.AKED,426216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_XF.Alarm.Resetable,426216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_XF.Alarm.REST,426216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_XF.Alarm.ACKN,426216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_XF.Alarm.UACK,426216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_XF.Alarm.MCmd_Enable,426216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_XF.Alarm.MCmd_Disable,426216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_XF.Alarm.OCmd_Shelve,426216.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_XF.Alarm.OCmd_Unshelve,426216.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_XF.Alarm.SCmd_Suppress,426216.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_XF.Alarm.SCmd_UnSuppress,426217.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_XF.Alarm.AEShelveTMRDN,426217.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_XF.Alarm.Bad,426217.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_XF.Alarm.Suppress,426218.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.UnSuppress,426218.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Shelve,426218.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.UnShelve,426218.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Enable,426218.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Disable,426218.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Ack,426218.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Reset,426218.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_XF.Alarm.Suppressed,426218.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_XF.Alarm.Shelved,426218.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_XF.Alarm.Disabled,426218.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_XF.Alarm.Acked,426218.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_XF.Alarm.Alarm,426218.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Fault,426228.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_XF.almPLCFault.AlarmState,426228.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_XF.almPLCFault.GlobalReset,426228.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_XF.almPLCFault.FaultInAlarm,426228.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_XF.almPLCFault.ALRM,426228.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_XF.almPLCFault.ANUN,426228.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_XF.almPLCFault.AKED,426228.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_XF.almPLCFault.Resetable,426228.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_XF.almPLCFault.REST,426228.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_XF.almPLCFault.ACKN,426228.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_XF.almPLCFault.UACK,426228.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_XF.almPLCFault.MCmd_Enable,426228.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_XF.almPLCFault.MCmd_Disable,426228.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_XF.almPLCFault.OCmd_Shelve,426228.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_XF.almPLCFault.OCmd_Unshelve,426228.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_XF.almPLCFault.SCmd_Suppress,426228.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_XF.almPLCFault.SCmd_UnSuppress,426229.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_XF.almPLCFault.AEShelveTMRDN,426229.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_XF.almPLCFault.Bad,426229.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_XF.almPLCFault.Suppress,426230.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.UnSuppress,426230.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Shelve,426230.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.UnShelve,426230.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Enable,426230.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Disable,426230.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Ack,426230.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Reset,426230.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Suppressed,426230.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Shelved,426230.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Disabled,426230.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Acked,426230.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_XF.almPLCFault.Alarm,426230.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Fault,426252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_YA.Alarm.AlarmState,426252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_YA.Alarm.GlobalReset,426252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_YA.Alarm.FaultInAlarm,426252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_YA.Alarm.ALRM,426252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_YA.Alarm.ANUN,426252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_YA.Alarm.AKED,426252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_YA.Alarm.Resetable,426252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_YA.Alarm.REST,426252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_YA.Alarm.ACKN,426252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_YA.Alarm.UACK,426252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_YA.Alarm.MCmd_Enable,426252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_YA.Alarm.MCmd_Disable,426252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_YA.Alarm.OCmd_Shelve,426252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_YA.Alarm.OCmd_Unshelve,426252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_YA.Alarm.SCmd_Suppress,426252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_YA.Alarm.SCmd_UnSuppress,426253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_YA.Alarm.AEShelveTMRDN,426253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_YA.Alarm.Bad,426253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_YA.Alarm.Suppress,426254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.UnSuppress,426254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Shelve,426254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.UnShelve,426254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Enable,426254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Disable,426254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Ack,426254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Reset,426254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_YA.Alarm.Suppressed,426254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_YA.Alarm.Shelved,426254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_YA.Alarm.Disabled,426254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_YA.Alarm.Acked,426254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_YA.Alarm.Alarm,426254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Fault,426264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1_YA.almPLCFault.AlarmState,426264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1_YA.almPLCFault.GlobalReset,426264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1_YA.almPLCFault.FaultInAlarm,426264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1_YA.almPLCFault.ALRM,426264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1_YA.almPLCFault.ANUN,426264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1_YA.almPLCFault.AKED,426264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1_YA.almPLCFault.Resetable,426264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1_YA.almPLCFault.REST,426264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1_YA.almPLCFault.ACKN,426264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1_YA.almPLCFault.UACK,426264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1_YA.almPLCFault.MCmd_Enable,426264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1_YA.almPLCFault.MCmd_Disable,426264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1_YA.almPLCFault.OCmd_Shelve,426264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1_YA.almPLCFault.OCmd_Unshelve,426264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1_YA.almPLCFault.SCmd_Suppress,426264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1_YA.almPLCFault.SCmd_UnSuppress,426265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1_YA.almPLCFault.AEShelveTMRDN,426265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1_YA.almPLCFault.Bad,426265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1_YA.almPLCFault.Suppress,426266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.UnSuppress,426266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Shelve,426266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.UnShelve,426266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Enable,426266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Disable,426266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Ack,426266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Reset,426266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Suppressed,426266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Shelved,426266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Disabled,426266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Acked,426266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1_YA.almPLCFault.Alarm,426266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Fault,426286.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_FA.Alarm.AlarmState,426286.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_FA.Alarm.GlobalReset,426286.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_FA.Alarm.FaultInAlarm,426286.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_FA.Alarm.ALRM,426286.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_FA.Alarm.ANUN,426286.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_FA.Alarm.AKED,426286.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_FA.Alarm.Resetable,426286.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_FA.Alarm.REST,426286.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_FA.Alarm.ACKN,426286.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_FA.Alarm.UACK,426286.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_FA.Alarm.MCmd_Enable,426286.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_FA.Alarm.MCmd_Disable,426286.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_FA.Alarm.OCmd_Shelve,426286.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_FA.Alarm.OCmd_Unshelve,426286.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_FA.Alarm.SCmd_Suppress,426286.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_FA.Alarm.SCmd_UnSuppress,426287.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_FA.Alarm.AEShelveTMRDN,426287.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_FA.Alarm.Bad,426287.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_FA.Alarm.Suppress,426288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.UnSuppress,426288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Shelve,426288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.UnShelve,426288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Enable,426288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Disable,426288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Ack,426288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Reset,426288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_FA.Alarm.Suppressed,426288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_FA.Alarm.Shelved,426288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_FA.Alarm.Disabled,426288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_FA.Alarm.Acked,426288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_FA.Alarm.Alarm,426288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Fault,426298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_FA.almPLCFault.AlarmState,426298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_FA.almPLCFault.GlobalReset,426298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_FA.almPLCFault.FaultInAlarm,426298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_FA.almPLCFault.ALRM,426298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_FA.almPLCFault.ANUN,426298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_FA.almPLCFault.AKED,426298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_FA.almPLCFault.Resetable,426298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_FA.almPLCFault.REST,426298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_FA.almPLCFault.ACKN,426298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_FA.almPLCFault.UACK,426298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_FA.almPLCFault.MCmd_Enable,426298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_FA.almPLCFault.MCmd_Disable,426298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_FA.almPLCFault.OCmd_Shelve,426298.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_FA.almPLCFault.OCmd_Unshelve,426298.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_FA.almPLCFault.SCmd_Suppress,426298.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_FA.almPLCFault.SCmd_UnSuppress,426299.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_FA.almPLCFault.AEShelveTMRDN,426299.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_FA.almPLCFault.Bad,426299.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_FA.almPLCFault.Suppress,426300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.UnSuppress,426300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Shelve,426300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.UnShelve,426300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Enable,426300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Disable,426300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Ack,426300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Reset,426300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Suppressed,426300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Shelved,426300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Disabled,426300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Acked,426300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_FA.almPLCFault.Alarm,426300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Fault,426322.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_MF.Alarm.AlarmState,426322.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_MF.Alarm.GlobalReset,426322.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_MF.Alarm.FaultInAlarm,426322.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MF.Alarm.ALRM,426322.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_MF.Alarm.ANUN,426322.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_MF.Alarm.AKED,426322.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_MF.Alarm.Resetable,426322.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_MF.Alarm.REST,426322.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_MF.Alarm.ACKN,426322.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_MF.Alarm.UACK,426322.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_MF.Alarm.MCmd_Enable,426322.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MF.Alarm.MCmd_Disable,426322.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MF.Alarm.OCmd_Shelve,426322.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_MF.Alarm.OCmd_Unshelve,426322.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_MF.Alarm.SCmd_Suppress,426322.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_MF.Alarm.SCmd_UnSuppress,426323.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_MF.Alarm.AEShelveTMRDN,426323.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_MF.Alarm.Bad,426323.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_MF.Alarm.Suppress,426324.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.UnSuppress,426324.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Shelve,426324.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.UnShelve,426324.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Enable,426324.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Disable,426324.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Ack,426324.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Reset,426324.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_MF.Alarm.Suppressed,426324.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_MF.Alarm.Shelved,426324.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_MF.Alarm.Disabled,426324.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_MF.Alarm.Acked,426324.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_MF.Alarm.Alarm,426324.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Fault,426334.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_MF.almPLCFault.AlarmState,426334.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_MF.almPLCFault.GlobalReset,426334.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_MF.almPLCFault.FaultInAlarm,426334.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MF.almPLCFault.ALRM,426334.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_MF.almPLCFault.ANUN,426334.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_MF.almPLCFault.AKED,426334.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_MF.almPLCFault.Resetable,426334.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_MF.almPLCFault.REST,426334.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_MF.almPLCFault.ACKN,426334.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_MF.almPLCFault.UACK,426334.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_MF.almPLCFault.MCmd_Enable,426334.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MF.almPLCFault.MCmd_Disable,426334.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MF.almPLCFault.OCmd_Shelve,426334.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_MF.almPLCFault.OCmd_Unshelve,426334.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_MF.almPLCFault.SCmd_Suppress,426334.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_MF.almPLCFault.SCmd_UnSuppress,426335.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_MF.almPLCFault.AEShelveTMRDN,426335.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_MF.almPLCFault.Bad,426335.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_MF.almPLCFault.Suppress,426336.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.UnSuppress,426336.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Shelve,426336.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.UnShelve,426336.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Enable,426336.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Disable,426336.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Ack,426336.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Reset,426336.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Suppressed,426336.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Shelved,426336.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Disabled,426336.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Acked,426336.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_MF.almPLCFault.Alarm,426336.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Fault,426356.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_MY.Alarm.AlarmState,426356.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_MY.Alarm.GlobalReset,426356.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_MY.Alarm.FaultInAlarm,426356.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MY.Alarm.ALRM,426356.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_MY.Alarm.ANUN,426356.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_MY.Alarm.AKED,426356.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_MY.Alarm.Resetable,426356.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_MY.Alarm.REST,426356.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_MY.Alarm.ACKN,426356.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_MY.Alarm.UACK,426356.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_MY.Alarm.MCmd_Enable,426356.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MY.Alarm.MCmd_Disable,426356.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MY.Alarm.OCmd_Shelve,426356.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_MY.Alarm.OCmd_Unshelve,426356.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_MY.Alarm.SCmd_Suppress,426356.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_MY.Alarm.SCmd_UnSuppress,426357.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_MY.Alarm.AEShelveTMRDN,426357.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_MY.Alarm.Bad,426357.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_MY.Alarm.Suppress,426358.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.UnSuppress,426358.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Shelve,426358.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.UnShelve,426358.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Enable,426358.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Disable,426358.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Ack,426358.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Reset,426358.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_MY.Alarm.Suppressed,426358.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_MY.Alarm.Shelved,426358.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_MY.Alarm.Disabled,426358.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_MY.Alarm.Acked,426358.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_MY.Alarm.Alarm,426358.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Fault,426368.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_MY.almPLCFault.AlarmState,426368.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_MY.almPLCFault.GlobalReset,426368.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_MY.almPLCFault.FaultInAlarm,426368.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_MY.almPLCFault.ALRM,426368.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_MY.almPLCFault.ANUN,426368.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_MY.almPLCFault.AKED,426368.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_MY.almPLCFault.Resetable,426368.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_MY.almPLCFault.REST,426368.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_MY.almPLCFault.ACKN,426368.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_MY.almPLCFault.UACK,426368.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_MY.almPLCFault.MCmd_Enable,426368.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_MY.almPLCFault.MCmd_Disable,426368.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_MY.almPLCFault.OCmd_Shelve,426368.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_MY.almPLCFault.OCmd_Unshelve,426368.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_MY.almPLCFault.SCmd_Suppress,426368.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_MY.almPLCFault.SCmd_UnSuppress,426369.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_MY.almPLCFault.AEShelveTMRDN,426369.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_MY.almPLCFault.Bad,426369.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_MY.almPLCFault.Suppress,426370.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.UnSuppress,426370.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Shelve,426370.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.UnShelve,426370.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Enable,426370.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Disable,426370.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Ack,426370.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Reset,426370.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Suppressed,426370.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Shelved,426370.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Disabled,426370.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Acked,426370.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_MY.almPLCFault.Alarm,426370.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Fault,426392.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UA.Alarm.AlarmState,426392.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UA.Alarm.GlobalReset,426392.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UA.Alarm.FaultInAlarm,426392.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UA.Alarm.ALRM,426392.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UA.Alarm.ANUN,426392.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UA.Alarm.AKED,426392.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UA.Alarm.Resetable,426392.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UA.Alarm.REST,426392.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UA.Alarm.ACKN,426392.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UA.Alarm.UACK,426392.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UA.Alarm.MCmd_Enable,426392.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UA.Alarm.MCmd_Disable,426392.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UA.Alarm.OCmd_Shelve,426392.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UA.Alarm.OCmd_Unshelve,426392.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UA.Alarm.SCmd_Suppress,426392.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UA.Alarm.SCmd_UnSuppress,426393.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UA.Alarm.AEShelveTMRDN,426393.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UA.Alarm.Bad,426393.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UA.Alarm.Suppress,426394.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.UnSuppress,426394.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Shelve,426394.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.UnShelve,426394.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Enable,426394.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Disable,426394.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Ack,426394.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Reset,426394.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UA.Alarm.Suppressed,426394.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UA.Alarm.Shelved,426394.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UA.Alarm.Disabled,426394.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UA.Alarm.Acked,426394.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UA.Alarm.Alarm,426394.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Fault,426404.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UA.almPLCFault.AlarmState,426404.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UA.almPLCFault.GlobalReset,426404.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UA.almPLCFault.FaultInAlarm,426404.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UA.almPLCFault.ALRM,426404.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UA.almPLCFault.ANUN,426404.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UA.almPLCFault.AKED,426404.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UA.almPLCFault.Resetable,426404.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UA.almPLCFault.REST,426404.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UA.almPLCFault.ACKN,426404.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UA.almPLCFault.UACK,426404.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UA.almPLCFault.MCmd_Enable,426404.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UA.almPLCFault.MCmd_Disable,426404.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UA.almPLCFault.OCmd_Shelve,426404.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UA.almPLCFault.OCmd_Unshelve,426404.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UA.almPLCFault.SCmd_Suppress,426404.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UA.almPLCFault.SCmd_UnSuppress,426405.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UA.almPLCFault.AEShelveTMRDN,426405.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UA.almPLCFault.Bad,426405.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UA.almPLCFault.Suppress,426406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.UnSuppress,426406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Shelve,426406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.UnShelve,426406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Enable,426406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Disable,426406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Ack,426406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Reset,426406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Suppressed,426406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Shelved,426406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Disabled,426406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Acked,426406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UA.almPLCFault.Alarm,426406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Fault,426426.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UH.Alarm.AlarmState,426426.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UH.Alarm.GlobalReset,426426.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UH.Alarm.FaultInAlarm,426426.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UH.Alarm.ALRM,426426.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UH.Alarm.ANUN,426426.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UH.Alarm.AKED,426426.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UH.Alarm.Resetable,426426.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UH.Alarm.REST,426426.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UH.Alarm.ACKN,426426.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UH.Alarm.UACK,426426.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UH.Alarm.MCmd_Enable,426426.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UH.Alarm.MCmd_Disable,426426.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UH.Alarm.OCmd_Shelve,426426.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UH.Alarm.OCmd_Unshelve,426426.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UH.Alarm.SCmd_Suppress,426426.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UH.Alarm.SCmd_UnSuppress,426427.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UH.Alarm.AEShelveTMRDN,426427.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UH.Alarm.Bad,426427.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UH.Alarm.Suppress,426428.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.UnSuppress,426428.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Shelve,426428.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.UnShelve,426428.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Enable,426428.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Disable,426428.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Ack,426428.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Reset,426428.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UH.Alarm.Suppressed,426428.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UH.Alarm.Shelved,426428.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UH.Alarm.Disabled,426428.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UH.Alarm.Acked,426428.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UH.Alarm.Alarm,426428.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Fault,426438.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UH.almPLCFault.AlarmState,426438.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UH.almPLCFault.GlobalReset,426438.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UH.almPLCFault.FaultInAlarm,426438.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UH.almPLCFault.ALRM,426438.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UH.almPLCFault.ANUN,426438.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UH.almPLCFault.AKED,426438.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UH.almPLCFault.Resetable,426438.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UH.almPLCFault.REST,426438.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UH.almPLCFault.ACKN,426438.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UH.almPLCFault.UACK,426438.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UH.almPLCFault.MCmd_Enable,426438.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UH.almPLCFault.MCmd_Disable,426438.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UH.almPLCFault.OCmd_Shelve,426438.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UH.almPLCFault.OCmd_Unshelve,426438.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UH.almPLCFault.SCmd_Suppress,426438.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UH.almPLCFault.SCmd_UnSuppress,426439.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UH.almPLCFault.AEShelveTMRDN,426439.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UH.almPLCFault.Bad,426439.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UH.almPLCFault.Suppress,426440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.UnSuppress,426440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Shelve,426440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.UnShelve,426440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Enable,426440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Disable,426440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Ack,426440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Reset,426440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Suppressed,426440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Shelved,426440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Disabled,426440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Acked,426440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UH.almPLCFault.Alarm,426440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Fault,426462.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UY.Alarm.AlarmState,426462.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UY.Alarm.GlobalReset,426462.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UY.Alarm.FaultInAlarm,426462.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UY.Alarm.ALRM,426462.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UY.Alarm.ANUN,426462.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UY.Alarm.AKED,426462.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UY.Alarm.Resetable,426462.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UY.Alarm.REST,426462.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UY.Alarm.ACKN,426462.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UY.Alarm.UACK,426462.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UY.Alarm.MCmd_Enable,426462.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UY.Alarm.MCmd_Disable,426462.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UY.Alarm.OCmd_Shelve,426462.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UY.Alarm.OCmd_Unshelve,426462.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UY.Alarm.SCmd_Suppress,426462.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UY.Alarm.SCmd_UnSuppress,426463.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UY.Alarm.AEShelveTMRDN,426463.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UY.Alarm.Bad,426463.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UY.Alarm.Suppress,426464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.UnSuppress,426464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Shelve,426464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.UnShelve,426464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Enable,426464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Disable,426464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Ack,426464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Reset,426464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UY.Alarm.Suppressed,426464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UY.Alarm.Shelved,426464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UY.Alarm.Disabled,426464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UY.Alarm.Acked,426464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UY.Alarm.Alarm,426464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Fault,426474.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_UY.almPLCFault.AlarmState,426474.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_UY.almPLCFault.GlobalReset,426474.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_UY.almPLCFault.FaultInAlarm,426474.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_UY.almPLCFault.ALRM,426474.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_UY.almPLCFault.ANUN,426474.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_UY.almPLCFault.AKED,426474.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_UY.almPLCFault.Resetable,426474.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_UY.almPLCFault.REST,426474.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_UY.almPLCFault.ACKN,426474.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_UY.almPLCFault.UACK,426474.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_UY.almPLCFault.MCmd_Enable,426474.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_UY.almPLCFault.MCmd_Disable,426474.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_UY.almPLCFault.OCmd_Shelve,426474.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_UY.almPLCFault.OCmd_Unshelve,426474.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_UY.almPLCFault.SCmd_Suppress,426474.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_UY.almPLCFault.SCmd_UnSuppress,426475.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_UY.almPLCFault.AEShelveTMRDN,426475.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_UY.almPLCFault.Bad,426475.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_UY.almPLCFault.Suppress,426476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.UnSuppress,426476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Shelve,426476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.UnShelve,426476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Enable,426476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Disable,426476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Ack,426476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Reset,426476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Suppressed,426476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Shelved,426476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Disabled,426476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Acked,426476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_UY.almPLCFault.Alarm,426476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Fault,426496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_XF.Alarm.AlarmState,426496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_XF.Alarm.GlobalReset,426496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_XF.Alarm.FaultInAlarm,426496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_XF.Alarm.ALRM,426496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_XF.Alarm.ANUN,426496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_XF.Alarm.AKED,426496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_XF.Alarm.Resetable,426496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_XF.Alarm.REST,426496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_XF.Alarm.ACKN,426496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_XF.Alarm.UACK,426496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_XF.Alarm.MCmd_Enable,426496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_XF.Alarm.MCmd_Disable,426496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_XF.Alarm.OCmd_Shelve,426496.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_XF.Alarm.OCmd_Unshelve,426496.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_XF.Alarm.SCmd_Suppress,426496.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_XF.Alarm.SCmd_UnSuppress,426497.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_XF.Alarm.AEShelveTMRDN,426497.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_XF.Alarm.Bad,426497.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_XF.Alarm.Suppress,426498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.UnSuppress,426498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Shelve,426498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.UnShelve,426498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Enable,426498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Disable,426498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Ack,426498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Reset,426498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_XF.Alarm.Suppressed,426498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_XF.Alarm.Shelved,426498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_XF.Alarm.Disabled,426498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_XF.Alarm.Acked,426498.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_XF.Alarm.Alarm,426498.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Fault,426508.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_XF.almPLCFault.AlarmState,426508.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_XF.almPLCFault.GlobalReset,426508.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_XF.almPLCFault.FaultInAlarm,426508.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_XF.almPLCFault.ALRM,426508.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_XF.almPLCFault.ANUN,426508.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_XF.almPLCFault.AKED,426508.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_XF.almPLCFault.Resetable,426508.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_XF.almPLCFault.REST,426508.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_XF.almPLCFault.ACKN,426508.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_XF.almPLCFault.UACK,426508.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_XF.almPLCFault.MCmd_Enable,426508.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_XF.almPLCFault.MCmd_Disable,426508.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_XF.almPLCFault.OCmd_Shelve,426508.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_XF.almPLCFault.OCmd_Unshelve,426508.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_XF.almPLCFault.SCmd_Suppress,426508.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_XF.almPLCFault.SCmd_UnSuppress,426509.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_XF.almPLCFault.AEShelveTMRDN,426509.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_XF.almPLCFault.Bad,426509.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_XF.almPLCFault.Suppress,426510.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.UnSuppress,426510.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Shelve,426510.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.UnShelve,426510.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Enable,426510.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Disable,426510.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Ack,426510.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Reset,426510.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Suppressed,426510.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Shelved,426510.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Disabled,426510.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Acked,426510.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_XF.almPLCFault.Alarm,426510.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Fault,426532.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_YA.Alarm.AlarmState,426532.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_YA.Alarm.GlobalReset,426532.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_YA.Alarm.FaultInAlarm,426532.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_YA.Alarm.ALRM,426532.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_YA.Alarm.ANUN,426532.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_YA.Alarm.AKED,426532.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_YA.Alarm.Resetable,426532.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_YA.Alarm.REST,426532.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_YA.Alarm.ACKN,426532.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_YA.Alarm.UACK,426532.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_YA.Alarm.MCmd_Enable,426532.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_YA.Alarm.MCmd_Disable,426532.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_YA.Alarm.OCmd_Shelve,426532.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_YA.Alarm.OCmd_Unshelve,426532.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_YA.Alarm.SCmd_Suppress,426532.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_YA.Alarm.SCmd_UnSuppress,426533.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_YA.Alarm.AEShelveTMRDN,426533.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_YA.Alarm.Bad,426533.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_YA.Alarm.Suppress,426534.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.UnSuppress,426534.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Shelve,426534.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.UnShelve,426534.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Enable,426534.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Disable,426534.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Ack,426534.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Reset,426534.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_YA.Alarm.Suppressed,426534.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_YA.Alarm.Shelved,426534.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_YA.Alarm.Disabled,426534.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_YA.Alarm.Acked,426534.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_YA.Alarm.Alarm,426534.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Fault,426544.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2_YA.almPLCFault.AlarmState,426544.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2_YA.almPLCFault.GlobalReset,426544.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2_YA.almPLCFault.FaultInAlarm,426544.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2_YA.almPLCFault.ALRM,426544.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2_YA.almPLCFault.ANUN,426544.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2_YA.almPLCFault.AKED,426544.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2_YA.almPLCFault.Resetable,426544.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2_YA.almPLCFault.REST,426544.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2_YA.almPLCFault.ACKN,426544.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2_YA.almPLCFault.UACK,426544.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2_YA.almPLCFault.MCmd_Enable,426544.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2_YA.almPLCFault.MCmd_Disable,426544.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2_YA.almPLCFault.OCmd_Shelve,426544.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2_YA.almPLCFault.OCmd_Unshelve,426544.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2_YA.almPLCFault.SCmd_Suppress,426544.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2_YA.almPLCFault.SCmd_UnSuppress,426545.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2_YA.almPLCFault.AEShelveTMRDN,426545.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2_YA.almPLCFault.Bad,426545.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2_YA.almPLCFault.Suppress,426546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.UnSuppress,426546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Shelve,426546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.UnShelve,426546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Enable,426546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Disable,426546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Ack,426546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Reset,426546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Suppressed,426546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Shelved,426546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Disabled,426546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Acked,426546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2_YA.almPLCFault.Alarm,426546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Fault,426566.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_FA.Alarm.AlarmState,426566.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_FA.Alarm.GlobalReset,426566.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_FA.Alarm.FaultInAlarm,426566.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_FA.Alarm.ALRM,426566.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_FA.Alarm.ANUN,426566.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_FA.Alarm.AKED,426566.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_FA.Alarm.Resetable,426566.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_FA.Alarm.REST,426566.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_FA.Alarm.ACKN,426566.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_FA.Alarm.UACK,426566.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_FA.Alarm.MCmd_Enable,426566.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_FA.Alarm.MCmd_Disable,426566.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_FA.Alarm.OCmd_Shelve,426566.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_FA.Alarm.OCmd_Unshelve,426566.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_FA.Alarm.SCmd_Suppress,426566.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_FA.Alarm.SCmd_UnSuppress,426567.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_FA.Alarm.AEShelveTMRDN,426567.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_FA.Alarm.Bad,426567.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_FA.Alarm.Suppress,426568.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.UnSuppress,426568.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Shelve,426568.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.UnShelve,426568.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Enable,426568.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Disable,426568.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Ack,426568.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Reset,426568.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_FA.Alarm.Suppressed,426568.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_FA.Alarm.Shelved,426568.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_FA.Alarm.Disabled,426568.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_FA.Alarm.Acked,426568.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_FA.Alarm.Alarm,426568.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Fault,426578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_FA.almPLCFault.AlarmState,426578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_FA.almPLCFault.GlobalReset,426578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_FA.almPLCFault.FaultInAlarm,426578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_FA.almPLCFault.ALRM,426578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_FA.almPLCFault.ANUN,426578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_FA.almPLCFault.AKED,426578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_FA.almPLCFault.Resetable,426578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_FA.almPLCFault.REST,426578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_FA.almPLCFault.ACKN,426578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_FA.almPLCFault.UACK,426578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_FA.almPLCFault.MCmd_Enable,426578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_FA.almPLCFault.MCmd_Disable,426578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_FA.almPLCFault.OCmd_Shelve,426578.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_FA.almPLCFault.OCmd_Unshelve,426578.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_FA.almPLCFault.SCmd_Suppress,426578.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_FA.almPLCFault.SCmd_UnSuppress,426579.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_FA.almPLCFault.AEShelveTMRDN,426579.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_FA.almPLCFault.Bad,426579.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_FA.almPLCFault.Suppress,426580.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.UnSuppress,426580.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Shelve,426580.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.UnShelve,426580.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Enable,426580.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Disable,426580.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Ack,426580.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Reset,426580.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Suppressed,426580.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Shelved,426580.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Disabled,426580.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Acked,426580.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_FA.almPLCFault.Alarm,426580.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Fault,426602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_MF.Alarm.AlarmState,426602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_MF.Alarm.GlobalReset,426602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_MF.Alarm.FaultInAlarm,426602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MF.Alarm.ALRM,426602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_MF.Alarm.ANUN,426602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_MF.Alarm.AKED,426602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_MF.Alarm.Resetable,426602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_MF.Alarm.REST,426602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_MF.Alarm.ACKN,426602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_MF.Alarm.UACK,426602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_MF.Alarm.MCmd_Enable,426602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MF.Alarm.MCmd_Disable,426602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MF.Alarm.OCmd_Shelve,426602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_MF.Alarm.OCmd_Unshelve,426602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_MF.Alarm.SCmd_Suppress,426602.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_MF.Alarm.SCmd_UnSuppress,426603.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_MF.Alarm.AEShelveTMRDN,426603.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_MF.Alarm.Bad,426603.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_MF.Alarm.Suppress,426604.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.UnSuppress,426604.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Shelve,426604.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.UnShelve,426604.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Enable,426604.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Disable,426604.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Ack,426604.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Reset,426604.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_MF.Alarm.Suppressed,426604.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_MF.Alarm.Shelved,426604.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_MF.Alarm.Disabled,426604.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_MF.Alarm.Acked,426604.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_MF.Alarm.Alarm,426604.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Fault,426614.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_MF.almPLCFault.AlarmState,426614.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_MF.almPLCFault.GlobalReset,426614.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_MF.almPLCFault.FaultInAlarm,426614.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MF.almPLCFault.ALRM,426614.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_MF.almPLCFault.ANUN,426614.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_MF.almPLCFault.AKED,426614.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_MF.almPLCFault.Resetable,426614.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_MF.almPLCFault.REST,426614.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_MF.almPLCFault.ACKN,426614.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_MF.almPLCFault.UACK,426614.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_MF.almPLCFault.MCmd_Enable,426614.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MF.almPLCFault.MCmd_Disable,426614.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MF.almPLCFault.OCmd_Shelve,426614.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_MF.almPLCFault.OCmd_Unshelve,426614.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_MF.almPLCFault.SCmd_Suppress,426614.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_MF.almPLCFault.SCmd_UnSuppress,426615.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_MF.almPLCFault.AEShelveTMRDN,426615.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_MF.almPLCFault.Bad,426615.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_MF.almPLCFault.Suppress,426616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.UnSuppress,426616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Shelve,426616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.UnShelve,426616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Enable,426616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Disable,426616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Ack,426616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Reset,426616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Suppressed,426616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Shelved,426616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Disabled,426616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Acked,426616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_MF.almPLCFault.Alarm,426616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Fault,426636.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_MY.Alarm.AlarmState,426636.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_MY.Alarm.GlobalReset,426636.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_MY.Alarm.FaultInAlarm,426636.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MY.Alarm.ALRM,426636.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_MY.Alarm.ANUN,426636.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_MY.Alarm.AKED,426636.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_MY.Alarm.Resetable,426636.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_MY.Alarm.REST,426636.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_MY.Alarm.ACKN,426636.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_MY.Alarm.UACK,426636.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_MY.Alarm.MCmd_Enable,426636.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MY.Alarm.MCmd_Disable,426636.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MY.Alarm.OCmd_Shelve,426636.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_MY.Alarm.OCmd_Unshelve,426636.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_MY.Alarm.SCmd_Suppress,426636.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_MY.Alarm.SCmd_UnSuppress,426637.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_MY.Alarm.AEShelveTMRDN,426637.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_MY.Alarm.Bad,426637.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_MY.Alarm.Suppress,426638.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.UnSuppress,426638.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Shelve,426638.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.UnShelve,426638.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Enable,426638.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Disable,426638.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Ack,426638.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Reset,426638.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_MY.Alarm.Suppressed,426638.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_MY.Alarm.Shelved,426638.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_MY.Alarm.Disabled,426638.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_MY.Alarm.Acked,426638.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_MY.Alarm.Alarm,426638.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Fault,426648.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_MY.almPLCFault.AlarmState,426648.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_MY.almPLCFault.GlobalReset,426648.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_MY.almPLCFault.FaultInAlarm,426648.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_MY.almPLCFault.ALRM,426648.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_MY.almPLCFault.ANUN,426648.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_MY.almPLCFault.AKED,426648.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_MY.almPLCFault.Resetable,426648.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_MY.almPLCFault.REST,426648.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_MY.almPLCFault.ACKN,426648.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_MY.almPLCFault.UACK,426648.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_MY.almPLCFault.MCmd_Enable,426648.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_MY.almPLCFault.MCmd_Disable,426648.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_MY.almPLCFault.OCmd_Shelve,426648.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_MY.almPLCFault.OCmd_Unshelve,426648.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_MY.almPLCFault.SCmd_Suppress,426648.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_MY.almPLCFault.SCmd_UnSuppress,426649.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_MY.almPLCFault.AEShelveTMRDN,426649.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_MY.almPLCFault.Bad,426649.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_MY.almPLCFault.Suppress,426650.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.UnSuppress,426650.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Shelve,426650.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.UnShelve,426650.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Enable,426650.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Disable,426650.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Ack,426650.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Reset,426650.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Suppressed,426650.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Shelved,426650.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Disabled,426650.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Acked,426650.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_MY.almPLCFault.Alarm,426650.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Fault,426672.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UA.Alarm.AlarmState,426672.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UA.Alarm.GlobalReset,426672.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UA.Alarm.FaultInAlarm,426672.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UA.Alarm.ALRM,426672.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UA.Alarm.ANUN,426672.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UA.Alarm.AKED,426672.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UA.Alarm.Resetable,426672.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UA.Alarm.REST,426672.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UA.Alarm.ACKN,426672.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UA.Alarm.UACK,426672.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UA.Alarm.MCmd_Enable,426672.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UA.Alarm.MCmd_Disable,426672.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UA.Alarm.OCmd_Shelve,426672.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UA.Alarm.OCmd_Unshelve,426672.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UA.Alarm.SCmd_Suppress,426672.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UA.Alarm.SCmd_UnSuppress,426673.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UA.Alarm.AEShelveTMRDN,426673.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UA.Alarm.Bad,426673.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UA.Alarm.Suppress,426674.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.UnSuppress,426674.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Shelve,426674.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.UnShelve,426674.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Enable,426674.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Disable,426674.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Ack,426674.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Reset,426674.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UA.Alarm.Suppressed,426674.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UA.Alarm.Shelved,426674.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UA.Alarm.Disabled,426674.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UA.Alarm.Acked,426674.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UA.Alarm.Alarm,426674.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Fault,426684.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UA.almPLCFault.AlarmState,426684.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UA.almPLCFault.GlobalReset,426684.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UA.almPLCFault.FaultInAlarm,426684.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UA.almPLCFault.ALRM,426684.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UA.almPLCFault.ANUN,426684.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UA.almPLCFault.AKED,426684.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UA.almPLCFault.Resetable,426684.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UA.almPLCFault.REST,426684.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UA.almPLCFault.ACKN,426684.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UA.almPLCFault.UACK,426684.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UA.almPLCFault.MCmd_Enable,426684.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UA.almPLCFault.MCmd_Disable,426684.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UA.almPLCFault.OCmd_Shelve,426684.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UA.almPLCFault.OCmd_Unshelve,426684.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UA.almPLCFault.SCmd_Suppress,426684.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UA.almPLCFault.SCmd_UnSuppress,426685.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UA.almPLCFault.AEShelveTMRDN,426685.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UA.almPLCFault.Bad,426685.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UA.almPLCFault.Suppress,426686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.UnSuppress,426686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Shelve,426686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.UnShelve,426686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Enable,426686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Disable,426686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Ack,426686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Reset,426686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Suppressed,426686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Shelved,426686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Disabled,426686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Acked,426686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UA.almPLCFault.Alarm,426686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Fault,426706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UH.Alarm.AlarmState,426706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UH.Alarm.GlobalReset,426706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UH.Alarm.FaultInAlarm,426706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UH.Alarm.ALRM,426706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UH.Alarm.ANUN,426706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UH.Alarm.AKED,426706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UH.Alarm.Resetable,426706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UH.Alarm.REST,426706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UH.Alarm.ACKN,426706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UH.Alarm.UACK,426706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UH.Alarm.MCmd_Enable,426706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UH.Alarm.MCmd_Disable,426706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UH.Alarm.OCmd_Shelve,426706.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UH.Alarm.OCmd_Unshelve,426706.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UH.Alarm.SCmd_Suppress,426706.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UH.Alarm.SCmd_UnSuppress,426707.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UH.Alarm.AEShelveTMRDN,426707.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UH.Alarm.Bad,426707.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UH.Alarm.Suppress,426708.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.UnSuppress,426708.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Shelve,426708.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.UnShelve,426708.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Enable,426708.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Disable,426708.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Ack,426708.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Reset,426708.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UH.Alarm.Suppressed,426708.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UH.Alarm.Shelved,426708.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UH.Alarm.Disabled,426708.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UH.Alarm.Acked,426708.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UH.Alarm.Alarm,426708.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Fault,426718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UH.almPLCFault.AlarmState,426718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UH.almPLCFault.GlobalReset,426718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UH.almPLCFault.FaultInAlarm,426718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UH.almPLCFault.ALRM,426718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UH.almPLCFault.ANUN,426718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UH.almPLCFault.AKED,426718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UH.almPLCFault.Resetable,426718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UH.almPLCFault.REST,426718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UH.almPLCFault.ACKN,426718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UH.almPLCFault.UACK,426718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UH.almPLCFault.MCmd_Enable,426718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UH.almPLCFault.MCmd_Disable,426718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UH.almPLCFault.OCmd_Shelve,426718.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UH.almPLCFault.OCmd_Unshelve,426718.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UH.almPLCFault.SCmd_Suppress,426718.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UH.almPLCFault.SCmd_UnSuppress,426719.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UH.almPLCFault.AEShelveTMRDN,426719.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UH.almPLCFault.Bad,426719.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UH.almPLCFault.Suppress,426720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.UnSuppress,426720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Shelve,426720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.UnShelve,426720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Enable,426720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Disable,426720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Ack,426720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Reset,426720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Suppressed,426720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Shelved,426720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Disabled,426720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Acked,426720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UH.almPLCFault.Alarm,426720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Fault,426742.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UY.Alarm.AlarmState,426742.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UY.Alarm.GlobalReset,426742.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UY.Alarm.FaultInAlarm,426742.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UY.Alarm.ALRM,426742.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UY.Alarm.ANUN,426742.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UY.Alarm.AKED,426742.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UY.Alarm.Resetable,426742.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UY.Alarm.REST,426742.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UY.Alarm.ACKN,426742.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UY.Alarm.UACK,426742.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UY.Alarm.MCmd_Enable,426742.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UY.Alarm.MCmd_Disable,426742.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UY.Alarm.OCmd_Shelve,426742.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UY.Alarm.OCmd_Unshelve,426742.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UY.Alarm.SCmd_Suppress,426742.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UY.Alarm.SCmd_UnSuppress,426743.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UY.Alarm.AEShelveTMRDN,426743.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UY.Alarm.Bad,426743.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UY.Alarm.Suppress,426744.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.UnSuppress,426744.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Shelve,426744.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.UnShelve,426744.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Enable,426744.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Disable,426744.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Ack,426744.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Reset,426744.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UY.Alarm.Suppressed,426744.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UY.Alarm.Shelved,426744.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UY.Alarm.Disabled,426744.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UY.Alarm.Acked,426744.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UY.Alarm.Alarm,426744.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Fault,426754.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_UY.almPLCFault.AlarmState,426754.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_UY.almPLCFault.GlobalReset,426754.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_UY.almPLCFault.FaultInAlarm,426754.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_UY.almPLCFault.ALRM,426754.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_UY.almPLCFault.ANUN,426754.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_UY.almPLCFault.AKED,426754.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_UY.almPLCFault.Resetable,426754.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_UY.almPLCFault.REST,426754.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_UY.almPLCFault.ACKN,426754.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_UY.almPLCFault.UACK,426754.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_UY.almPLCFault.MCmd_Enable,426754.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_UY.almPLCFault.MCmd_Disable,426754.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_UY.almPLCFault.OCmd_Shelve,426754.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_UY.almPLCFault.OCmd_Unshelve,426754.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_UY.almPLCFault.SCmd_Suppress,426754.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_UY.almPLCFault.SCmd_UnSuppress,426755.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_UY.almPLCFault.AEShelveTMRDN,426755.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_UY.almPLCFault.Bad,426755.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_UY.almPLCFault.Suppress,426756.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.UnSuppress,426756.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Shelve,426756.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.UnShelve,426756.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Enable,426756.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Disable,426756.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Ack,426756.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Reset,426756.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Suppressed,426756.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Shelved,426756.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Disabled,426756.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Acked,426756.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_UY.almPLCFault.Alarm,426756.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Fault,426776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_XF.Alarm.AlarmState,426776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_XF.Alarm.GlobalReset,426776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_XF.Alarm.FaultInAlarm,426776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_XF.Alarm.ALRM,426776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_XF.Alarm.ANUN,426776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_XF.Alarm.AKED,426776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_XF.Alarm.Resetable,426776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_XF.Alarm.REST,426776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_XF.Alarm.ACKN,426776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_XF.Alarm.UACK,426776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_XF.Alarm.MCmd_Enable,426776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_XF.Alarm.MCmd_Disable,426776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_XF.Alarm.OCmd_Shelve,426776.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_XF.Alarm.OCmd_Unshelve,426776.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_XF.Alarm.SCmd_Suppress,426776.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_XF.Alarm.SCmd_UnSuppress,426777.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_XF.Alarm.AEShelveTMRDN,426777.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_XF.Alarm.Bad,426777.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_XF.Alarm.Suppress,426778.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.UnSuppress,426778.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Shelve,426778.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.UnShelve,426778.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Enable,426778.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Disable,426778.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Ack,426778.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Reset,426778.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_XF.Alarm.Suppressed,426778.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_XF.Alarm.Shelved,426778.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_XF.Alarm.Disabled,426778.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_XF.Alarm.Acked,426778.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_XF.Alarm.Alarm,426778.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Fault,426788.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_XF.almPLCFault.AlarmState,426788.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_XF.almPLCFault.GlobalReset,426788.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_XF.almPLCFault.FaultInAlarm,426788.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_XF.almPLCFault.ALRM,426788.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_XF.almPLCFault.ANUN,426788.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_XF.almPLCFault.AKED,426788.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_XF.almPLCFault.Resetable,426788.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_XF.almPLCFault.REST,426788.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_XF.almPLCFault.ACKN,426788.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_XF.almPLCFault.UACK,426788.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_XF.almPLCFault.MCmd_Enable,426788.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_XF.almPLCFault.MCmd_Disable,426788.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_XF.almPLCFault.OCmd_Shelve,426788.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_XF.almPLCFault.OCmd_Unshelve,426788.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_XF.almPLCFault.SCmd_Suppress,426788.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_XF.almPLCFault.SCmd_UnSuppress,426789.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_XF.almPLCFault.AEShelveTMRDN,426789.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_XF.almPLCFault.Bad,426789.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_XF.almPLCFault.Suppress,426790.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.UnSuppress,426790.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Shelve,426790.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.UnShelve,426790.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Enable,426790.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Disable,426790.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Ack,426790.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Reset,426790.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Suppressed,426790.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Shelved,426790.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Disabled,426790.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Acked,426790.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_XF.almPLCFault.Alarm,426790.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Fault,426812.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_YA.Alarm.AlarmState,426812.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_YA.Alarm.GlobalReset,426812.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_YA.Alarm.FaultInAlarm,426812.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_YA.Alarm.ALRM,426812.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_YA.Alarm.ANUN,426812.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_YA.Alarm.AKED,426812.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_YA.Alarm.Resetable,426812.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_YA.Alarm.REST,426812.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_YA.Alarm.ACKN,426812.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_YA.Alarm.UACK,426812.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_YA.Alarm.MCmd_Enable,426812.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_YA.Alarm.MCmd_Disable,426812.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_YA.Alarm.OCmd_Shelve,426812.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_YA.Alarm.OCmd_Unshelve,426812.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_YA.Alarm.SCmd_Suppress,426812.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_YA.Alarm.SCmd_UnSuppress,426813.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_YA.Alarm.AEShelveTMRDN,426813.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_YA.Alarm.Bad,426813.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_YA.Alarm.Suppress,426814.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.UnSuppress,426814.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Shelve,426814.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.UnShelve,426814.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Enable,426814.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Disable,426814.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Ack,426814.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Reset,426814.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_YA.Alarm.Suppressed,426814.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_YA.Alarm.Shelved,426814.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_YA.Alarm.Disabled,426814.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_YA.Alarm.Acked,426814.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_YA.Alarm.Alarm,426814.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Fault,426824.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3_YA.almPLCFault.AlarmState,426824.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3_YA.almPLCFault.GlobalReset,426824.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3_YA.almPLCFault.FaultInAlarm,426824.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3_YA.almPLCFault.ALRM,426824.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3_YA.almPLCFault.ANUN,426824.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3_YA.almPLCFault.AKED,426824.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3_YA.almPLCFault.Resetable,426824.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3_YA.almPLCFault.REST,426824.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3_YA.almPLCFault.ACKN,426824.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3_YA.almPLCFault.UACK,426824.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3_YA.almPLCFault.MCmd_Enable,426824.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3_YA.almPLCFault.MCmd_Disable,426824.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3_YA.almPLCFault.OCmd_Shelve,426824.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3_YA.almPLCFault.OCmd_Unshelve,426824.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3_YA.almPLCFault.SCmd_Suppress,426824.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3_YA.almPLCFault.SCmd_UnSuppress,426825.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3_YA.almPLCFault.AEShelveTMRDN,426825.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3_YA.almPLCFault.Bad,426825.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3_YA.almPLCFault.Suppress,426826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.UnSuppress,426826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Shelve,426826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.UnShelve,426826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Enable,426826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Disable,426826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Ack,426826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Reset,426826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Suppressed,426826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Shelved,426826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Disabled,426826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Acked,426826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3_YA.almPLCFault.Alarm,426826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Fault,426846.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_FA.Alarm.AlarmState,426846.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_FA.Alarm.GlobalReset,426846.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_FA.Alarm.FaultInAlarm,426846.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_FA.Alarm.ALRM,426846.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_FA.Alarm.ANUN,426846.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_FA.Alarm.AKED,426846.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_FA.Alarm.Resetable,426846.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_FA.Alarm.REST,426846.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_FA.Alarm.ACKN,426846.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_FA.Alarm.UACK,426846.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_FA.Alarm.MCmd_Enable,426846.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_FA.Alarm.MCmd_Disable,426846.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_FA.Alarm.OCmd_Shelve,426846.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_FA.Alarm.OCmd_Unshelve,426846.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_FA.Alarm.SCmd_Suppress,426846.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_FA.Alarm.SCmd_UnSuppress,426847.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_FA.Alarm.AEShelveTMRDN,426847.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_FA.Alarm.Bad,426847.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_FA.Alarm.Suppress,426848.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.UnSuppress,426848.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Shelve,426848.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.UnShelve,426848.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Enable,426848.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Disable,426848.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Ack,426848.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Reset,426848.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_FA.Alarm.Suppressed,426848.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_FA.Alarm.Shelved,426848.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_FA.Alarm.Disabled,426848.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_FA.Alarm.Acked,426848.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_FA.Alarm.Alarm,426848.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Fault,426858.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_FA.almPLCFault.AlarmState,426858.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_FA.almPLCFault.GlobalReset,426858.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_FA.almPLCFault.FaultInAlarm,426858.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_FA.almPLCFault.ALRM,426858.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_FA.almPLCFault.ANUN,426858.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_FA.almPLCFault.AKED,426858.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_FA.almPLCFault.Resetable,426858.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_FA.almPLCFault.REST,426858.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_FA.almPLCFault.ACKN,426858.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_FA.almPLCFault.UACK,426858.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_FA.almPLCFault.MCmd_Enable,426858.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_FA.almPLCFault.MCmd_Disable,426858.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_FA.almPLCFault.OCmd_Shelve,426858.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_FA.almPLCFault.OCmd_Unshelve,426858.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_FA.almPLCFault.SCmd_Suppress,426858.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_FA.almPLCFault.SCmd_UnSuppress,426859.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_FA.almPLCFault.AEShelveTMRDN,426859.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_FA.almPLCFault.Bad,426859.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_FA.almPLCFault.Suppress,426860.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.UnSuppress,426860.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Shelve,426860.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.UnShelve,426860.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Enable,426860.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Disable,426860.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Ack,426860.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Reset,426860.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Suppressed,426860.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Shelved,426860.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Disabled,426860.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Acked,426860.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_FA.almPLCFault.Alarm,426860.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Fault,426882.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_MF.Alarm.AlarmState,426882.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_MF.Alarm.GlobalReset,426882.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_MF.Alarm.FaultInAlarm,426882.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MF.Alarm.ALRM,426882.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_MF.Alarm.ANUN,426882.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_MF.Alarm.AKED,426882.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_MF.Alarm.Resetable,426882.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_MF.Alarm.REST,426882.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_MF.Alarm.ACKN,426882.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_MF.Alarm.UACK,426882.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_MF.Alarm.MCmd_Enable,426882.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MF.Alarm.MCmd_Disable,426882.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MF.Alarm.OCmd_Shelve,426882.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_MF.Alarm.OCmd_Unshelve,426882.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_MF.Alarm.SCmd_Suppress,426882.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_MF.Alarm.SCmd_UnSuppress,426883.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_MF.Alarm.AEShelveTMRDN,426883.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_MF.Alarm.Bad,426883.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_MF.Alarm.Suppress,426884.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.UnSuppress,426884.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Shelve,426884.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.UnShelve,426884.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Enable,426884.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Disable,426884.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Ack,426884.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Reset,426884.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_MF.Alarm.Suppressed,426884.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_MF.Alarm.Shelved,426884.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_MF.Alarm.Disabled,426884.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_MF.Alarm.Acked,426884.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_MF.Alarm.Alarm,426884.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Fault,426894.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_MF.almPLCFault.AlarmState,426894.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_MF.almPLCFault.GlobalReset,426894.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_MF.almPLCFault.FaultInAlarm,426894.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MF.almPLCFault.ALRM,426894.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_MF.almPLCFault.ANUN,426894.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_MF.almPLCFault.AKED,426894.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_MF.almPLCFault.Resetable,426894.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_MF.almPLCFault.REST,426894.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_MF.almPLCFault.ACKN,426894.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_MF.almPLCFault.UACK,426894.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_MF.almPLCFault.MCmd_Enable,426894.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MF.almPLCFault.MCmd_Disable,426894.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MF.almPLCFault.OCmd_Shelve,426894.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_MF.almPLCFault.OCmd_Unshelve,426894.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_MF.almPLCFault.SCmd_Suppress,426894.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_MF.almPLCFault.SCmd_UnSuppress,426895.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_MF.almPLCFault.AEShelveTMRDN,426895.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_MF.almPLCFault.Bad,426895.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_MF.almPLCFault.Suppress,426896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.UnSuppress,426896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Shelve,426896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.UnShelve,426896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Enable,426896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Disable,426896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Ack,426896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Reset,426896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Suppressed,426896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Shelved,426896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Disabled,426896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Acked,426896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_MF.almPLCFault.Alarm,426896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Fault,426916.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_MY.Alarm.AlarmState,426916.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_MY.Alarm.GlobalReset,426916.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_MY.Alarm.FaultInAlarm,426916.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MY.Alarm.ALRM,426916.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_MY.Alarm.ANUN,426916.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_MY.Alarm.AKED,426916.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_MY.Alarm.Resetable,426916.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_MY.Alarm.REST,426916.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_MY.Alarm.ACKN,426916.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_MY.Alarm.UACK,426916.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_MY.Alarm.MCmd_Enable,426916.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MY.Alarm.MCmd_Disable,426916.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MY.Alarm.OCmd_Shelve,426916.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_MY.Alarm.OCmd_Unshelve,426916.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_MY.Alarm.SCmd_Suppress,426916.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_MY.Alarm.SCmd_UnSuppress,426917.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_MY.Alarm.AEShelveTMRDN,426917.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_MY.Alarm.Bad,426917.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_MY.Alarm.Suppress,426918.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.UnSuppress,426918.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Shelve,426918.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.UnShelve,426918.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Enable,426918.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Disable,426918.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Ack,426918.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Reset,426918.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_MY.Alarm.Suppressed,426918.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_MY.Alarm.Shelved,426918.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_MY.Alarm.Disabled,426918.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_MY.Alarm.Acked,426918.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_MY.Alarm.Alarm,426918.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Fault,426928.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_MY.almPLCFault.AlarmState,426928.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_MY.almPLCFault.GlobalReset,426928.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_MY.almPLCFault.FaultInAlarm,426928.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_MY.almPLCFault.ALRM,426928.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_MY.almPLCFault.ANUN,426928.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_MY.almPLCFault.AKED,426928.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_MY.almPLCFault.Resetable,426928.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_MY.almPLCFault.REST,426928.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_MY.almPLCFault.ACKN,426928.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_MY.almPLCFault.UACK,426928.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_MY.almPLCFault.MCmd_Enable,426928.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_MY.almPLCFault.MCmd_Disable,426928.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_MY.almPLCFault.OCmd_Shelve,426928.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_MY.almPLCFault.OCmd_Unshelve,426928.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_MY.almPLCFault.SCmd_Suppress,426928.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_MY.almPLCFault.SCmd_UnSuppress,426929.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_MY.almPLCFault.AEShelveTMRDN,426929.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_MY.almPLCFault.Bad,426929.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_MY.almPLCFault.Suppress,426930.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.UnSuppress,426930.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Shelve,426930.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.UnShelve,426930.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Enable,426930.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Disable,426930.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Ack,426930.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Reset,426930.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Suppressed,426930.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Shelved,426930.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Disabled,426930.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Acked,426930.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_MY.almPLCFault.Alarm,426930.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Fault,426952.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UA.Alarm.AlarmState,426952.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UA.Alarm.GlobalReset,426952.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UA.Alarm.FaultInAlarm,426952.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UA.Alarm.ALRM,426952.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UA.Alarm.ANUN,426952.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UA.Alarm.AKED,426952.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UA.Alarm.Resetable,426952.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UA.Alarm.REST,426952.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UA.Alarm.ACKN,426952.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UA.Alarm.UACK,426952.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UA.Alarm.MCmd_Enable,426952.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UA.Alarm.MCmd_Disable,426952.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UA.Alarm.OCmd_Shelve,426952.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UA.Alarm.OCmd_Unshelve,426952.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UA.Alarm.SCmd_Suppress,426952.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UA.Alarm.SCmd_UnSuppress,426953.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UA.Alarm.AEShelveTMRDN,426953.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UA.Alarm.Bad,426953.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UA.Alarm.Suppress,426954.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.UnSuppress,426954.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Shelve,426954.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.UnShelve,426954.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Enable,426954.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Disable,426954.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Ack,426954.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Reset,426954.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UA.Alarm.Suppressed,426954.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UA.Alarm.Shelved,426954.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UA.Alarm.Disabled,426954.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UA.Alarm.Acked,426954.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UA.Alarm.Alarm,426954.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Fault,426964.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UA.almPLCFault.AlarmState,426964.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UA.almPLCFault.GlobalReset,426964.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UA.almPLCFault.FaultInAlarm,426964.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UA.almPLCFault.ALRM,426964.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UA.almPLCFault.ANUN,426964.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UA.almPLCFault.AKED,426964.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UA.almPLCFault.Resetable,426964.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UA.almPLCFault.REST,426964.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UA.almPLCFault.ACKN,426964.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UA.almPLCFault.UACK,426964.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UA.almPLCFault.MCmd_Enable,426964.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UA.almPLCFault.MCmd_Disable,426964.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UA.almPLCFault.OCmd_Shelve,426964.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UA.almPLCFault.OCmd_Unshelve,426964.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UA.almPLCFault.SCmd_Suppress,426964.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UA.almPLCFault.SCmd_UnSuppress,426965.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UA.almPLCFault.AEShelveTMRDN,426965.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UA.almPLCFault.Bad,426965.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UA.almPLCFault.Suppress,426966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.UnSuppress,426966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Shelve,426966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.UnShelve,426966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Enable,426966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Disable,426966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Ack,426966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Reset,426966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Suppressed,426966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Shelved,426966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Disabled,426966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Acked,426966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UA.almPLCFault.Alarm,426966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Fault,426986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UH.Alarm.AlarmState,426986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UH.Alarm.GlobalReset,426986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UH.Alarm.FaultInAlarm,426986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UH.Alarm.ALRM,426986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UH.Alarm.ANUN,426986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UH.Alarm.AKED,426986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UH.Alarm.Resetable,426986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UH.Alarm.REST,426986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UH.Alarm.ACKN,426986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UH.Alarm.UACK,426986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UH.Alarm.MCmd_Enable,426986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UH.Alarm.MCmd_Disable,426986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UH.Alarm.OCmd_Shelve,426986.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UH.Alarm.OCmd_Unshelve,426986.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UH.Alarm.SCmd_Suppress,426986.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UH.Alarm.SCmd_UnSuppress,426987.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UH.Alarm.AEShelveTMRDN,426987.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UH.Alarm.Bad,426987.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UH.Alarm.Suppress,426988.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.UnSuppress,426988.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Shelve,426988.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.UnShelve,426988.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Enable,426988.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Disable,426988.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Ack,426988.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Reset,426988.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UH.Alarm.Suppressed,426988.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UH.Alarm.Shelved,426988.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UH.Alarm.Disabled,426988.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UH.Alarm.Acked,426988.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UH.Alarm.Alarm,426988.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Fault,426998.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UH.almPLCFault.AlarmState,426998.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UH.almPLCFault.GlobalReset,426998.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UH.almPLCFault.FaultInAlarm,426998.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UH.almPLCFault.ALRM,426998.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UH.almPLCFault.ANUN,426998.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UH.almPLCFault.AKED,426998.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UH.almPLCFault.Resetable,426998.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UH.almPLCFault.REST,426998.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UH.almPLCFault.ACKN,426998.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UH.almPLCFault.UACK,426998.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UH.almPLCFault.MCmd_Enable,426998.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UH.almPLCFault.MCmd_Disable,426998.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UH.almPLCFault.OCmd_Shelve,426998.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UH.almPLCFault.OCmd_Unshelve,426998.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UH.almPLCFault.SCmd_Suppress,426998.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UH.almPLCFault.SCmd_UnSuppress,426999.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UH.almPLCFault.AEShelveTMRDN,426999.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UH.almPLCFault.Bad,426999.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UH.almPLCFault.Suppress,427000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.UnSuppress,427000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Shelve,427000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.UnShelve,427000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Enable,427000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Disable,427000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Ack,427000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Reset,427000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Suppressed,427000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Shelved,427000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Disabled,427000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Acked,427000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UH.almPLCFault.Alarm,427000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Fault,427022.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UY.Alarm.AlarmState,427022.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UY.Alarm.GlobalReset,427022.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UY.Alarm.FaultInAlarm,427022.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UY.Alarm.ALRM,427022.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UY.Alarm.ANUN,427022.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UY.Alarm.AKED,427022.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UY.Alarm.Resetable,427022.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UY.Alarm.REST,427022.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UY.Alarm.ACKN,427022.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UY.Alarm.UACK,427022.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UY.Alarm.MCmd_Enable,427022.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UY.Alarm.MCmd_Disable,427022.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UY.Alarm.OCmd_Shelve,427022.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UY.Alarm.OCmd_Unshelve,427022.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UY.Alarm.SCmd_Suppress,427022.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UY.Alarm.SCmd_UnSuppress,427023.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UY.Alarm.AEShelveTMRDN,427023.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UY.Alarm.Bad,427023.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UY.Alarm.Suppress,427024.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.UnSuppress,427024.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Shelve,427024.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.UnShelve,427024.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Enable,427024.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Disable,427024.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Ack,427024.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Reset,427024.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UY.Alarm.Suppressed,427024.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UY.Alarm.Shelved,427024.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UY.Alarm.Disabled,427024.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UY.Alarm.Acked,427024.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UY.Alarm.Alarm,427024.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Fault,427034.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_UY.almPLCFault.AlarmState,427034.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_UY.almPLCFault.GlobalReset,427034.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_UY.almPLCFault.FaultInAlarm,427034.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_UY.almPLCFault.ALRM,427034.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_UY.almPLCFault.ANUN,427034.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_UY.almPLCFault.AKED,427034.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_UY.almPLCFault.Resetable,427034.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_UY.almPLCFault.REST,427034.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_UY.almPLCFault.ACKN,427034.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_UY.almPLCFault.UACK,427034.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_UY.almPLCFault.MCmd_Enable,427034.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_UY.almPLCFault.MCmd_Disable,427034.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_UY.almPLCFault.OCmd_Shelve,427034.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_UY.almPLCFault.OCmd_Unshelve,427034.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_UY.almPLCFault.SCmd_Suppress,427034.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_UY.almPLCFault.SCmd_UnSuppress,427035.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_UY.almPLCFault.AEShelveTMRDN,427035.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_UY.almPLCFault.Bad,427035.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_UY.almPLCFault.Suppress,427036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.UnSuppress,427036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Shelve,427036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.UnShelve,427036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Enable,427036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Disable,427036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Ack,427036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Reset,427036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Suppressed,427036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Shelved,427036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Disabled,427036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Acked,427036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_UY.almPLCFault.Alarm,427036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Fault,427056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_XF.Alarm.AlarmState,427056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_XF.Alarm.GlobalReset,427056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_XF.Alarm.FaultInAlarm,427056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_XF.Alarm.ALRM,427056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_XF.Alarm.ANUN,427056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_XF.Alarm.AKED,427056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_XF.Alarm.Resetable,427056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_XF.Alarm.REST,427056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_XF.Alarm.ACKN,427056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_XF.Alarm.UACK,427056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_XF.Alarm.MCmd_Enable,427056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_XF.Alarm.MCmd_Disable,427056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_XF.Alarm.OCmd_Shelve,427056.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_XF.Alarm.OCmd_Unshelve,427056.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_XF.Alarm.SCmd_Suppress,427056.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_XF.Alarm.SCmd_UnSuppress,427057.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_XF.Alarm.AEShelveTMRDN,427057.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_XF.Alarm.Bad,427057.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_XF.Alarm.Suppress,427058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.UnSuppress,427058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Shelve,427058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.UnShelve,427058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Enable,427058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Disable,427058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Ack,427058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Reset,427058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_XF.Alarm.Suppressed,427058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_XF.Alarm.Shelved,427058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_XF.Alarm.Disabled,427058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_XF.Alarm.Acked,427058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_XF.Alarm.Alarm,427058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Fault,427068.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_XF.almPLCFault.AlarmState,427068.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_XF.almPLCFault.GlobalReset,427068.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_XF.almPLCFault.FaultInAlarm,427068.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_XF.almPLCFault.ALRM,427068.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_XF.almPLCFault.ANUN,427068.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_XF.almPLCFault.AKED,427068.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_XF.almPLCFault.Resetable,427068.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_XF.almPLCFault.REST,427068.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_XF.almPLCFault.ACKN,427068.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_XF.almPLCFault.UACK,427068.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_XF.almPLCFault.MCmd_Enable,427068.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_XF.almPLCFault.MCmd_Disable,427068.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_XF.almPLCFault.OCmd_Shelve,427068.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_XF.almPLCFault.OCmd_Unshelve,427068.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_XF.almPLCFault.SCmd_Suppress,427068.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_XF.almPLCFault.SCmd_UnSuppress,427069.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_XF.almPLCFault.AEShelveTMRDN,427069.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_XF.almPLCFault.Bad,427069.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_XF.almPLCFault.Suppress,427070.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.UnSuppress,427070.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Shelve,427070.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.UnShelve,427070.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Enable,427070.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Disable,427070.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Ack,427070.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Reset,427070.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Suppressed,427070.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Shelved,427070.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Disabled,427070.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Acked,427070.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_XF.almPLCFault.Alarm,427070.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Fault,427092.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_YA.Alarm.AlarmState,427092.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_YA.Alarm.GlobalReset,427092.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_YA.Alarm.FaultInAlarm,427092.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_YA.Alarm.ALRM,427092.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_YA.Alarm.ANUN,427092.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_YA.Alarm.AKED,427092.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_YA.Alarm.Resetable,427092.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_YA.Alarm.REST,427092.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_YA.Alarm.ACKN,427092.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_YA.Alarm.UACK,427092.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_YA.Alarm.MCmd_Enable,427092.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_YA.Alarm.MCmd_Disable,427092.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_YA.Alarm.OCmd_Shelve,427092.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_YA.Alarm.OCmd_Unshelve,427092.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_YA.Alarm.SCmd_Suppress,427092.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_YA.Alarm.SCmd_UnSuppress,427093.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_YA.Alarm.AEShelveTMRDN,427093.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_YA.Alarm.Bad,427093.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_YA.Alarm.Suppress,427094.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.UnSuppress,427094.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Shelve,427094.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.UnShelve,427094.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Enable,427094.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Disable,427094.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Ack,427094.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Reset,427094.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_YA.Alarm.Suppressed,427094.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_YA.Alarm.Shelved,427094.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_YA.Alarm.Disabled,427094.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_YA.Alarm.Acked,427094.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_YA.Alarm.Alarm,427094.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Fault,427104.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4_YA.almPLCFault.AlarmState,427104.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4_YA.almPLCFault.GlobalReset,427104.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4_YA.almPLCFault.FaultInAlarm,427104.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4_YA.almPLCFault.ALRM,427104.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4_YA.almPLCFault.ANUN,427104.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4_YA.almPLCFault.AKED,427104.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4_YA.almPLCFault.Resetable,427104.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4_YA.almPLCFault.REST,427104.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4_YA.almPLCFault.ACKN,427104.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4_YA.almPLCFault.UACK,427104.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4_YA.almPLCFault.MCmd_Enable,427104.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4_YA.almPLCFault.MCmd_Disable,427104.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4_YA.almPLCFault.OCmd_Shelve,427104.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4_YA.almPLCFault.OCmd_Unshelve,427104.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4_YA.almPLCFault.SCmd_Suppress,427104.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4_YA.almPLCFault.SCmd_UnSuppress,427105.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4_YA.almPLCFault.AEShelveTMRDN,427105.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4_YA.almPLCFault.Bad,427105.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4_YA.almPLCFault.Suppress,427106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.UnSuppress,427106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Shelve,427106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.UnShelve,427106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Enable,427106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Disable,427106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Ack,427106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Reset,427106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Suppressed,427106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Shelved,427106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Disabled,427106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Acked,427106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4_YA.almPLCFault.Alarm,427106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Fault,427126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_FA.Alarm.AlarmState,427126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_FA.Alarm.GlobalReset,427126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_FA.Alarm.FaultInAlarm,427126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_FA.Alarm.ALRM,427126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_FA.Alarm.ANUN,427126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_FA.Alarm.AKED,427126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_FA.Alarm.Resetable,427126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_FA.Alarm.REST,427126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_FA.Alarm.ACKN,427126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_FA.Alarm.UACK,427126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_FA.Alarm.MCmd_Enable,427126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_FA.Alarm.MCmd_Disable,427126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_FA.Alarm.OCmd_Shelve,427126.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_FA.Alarm.OCmd_Unshelve,427126.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_FA.Alarm.SCmd_Suppress,427126.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_FA.Alarm.SCmd_UnSuppress,427127.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_FA.Alarm.AEShelveTMRDN,427127.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_FA.Alarm.Bad,427127.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_FA.Alarm.Suppress,427128.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.UnSuppress,427128.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Shelve,427128.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.UnShelve,427128.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Enable,427128.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Disable,427128.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Ack,427128.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Reset,427128.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_FA.Alarm.Suppressed,427128.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_FA.Alarm.Shelved,427128.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_FA.Alarm.Disabled,427128.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_FA.Alarm.Acked,427128.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_FA.Alarm.Alarm,427128.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Fault,427138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_FA.almPLCFault.AlarmState,427138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_FA.almPLCFault.GlobalReset,427138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_FA.almPLCFault.FaultInAlarm,427138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_FA.almPLCFault.ALRM,427138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_FA.almPLCFault.ANUN,427138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_FA.almPLCFault.AKED,427138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_FA.almPLCFault.Resetable,427138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_FA.almPLCFault.REST,427138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_FA.almPLCFault.ACKN,427138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_FA.almPLCFault.UACK,427138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_FA.almPLCFault.MCmd_Enable,427138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_FA.almPLCFault.MCmd_Disable,427138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_FA.almPLCFault.OCmd_Shelve,427138.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_FA.almPLCFault.OCmd_Unshelve,427138.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_FA.almPLCFault.SCmd_Suppress,427138.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_FA.almPLCFault.SCmd_UnSuppress,427139.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_FA.almPLCFault.AEShelveTMRDN,427139.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_FA.almPLCFault.Bad,427139.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_FA.almPLCFault.Suppress,427140.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.UnSuppress,427140.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Shelve,427140.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.UnShelve,427140.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Enable,427140.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Disable,427140.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Ack,427140.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Reset,427140.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Suppressed,427140.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Shelved,427140.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Disabled,427140.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Acked,427140.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_FA.almPLCFault.Alarm,427140.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Fault,427162.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_MF.Alarm.AlarmState,427162.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_MF.Alarm.GlobalReset,427162.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_MF.Alarm.FaultInAlarm,427162.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MF.Alarm.ALRM,427162.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_MF.Alarm.ANUN,427162.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_MF.Alarm.AKED,427162.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_MF.Alarm.Resetable,427162.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_MF.Alarm.REST,427162.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_MF.Alarm.ACKN,427162.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_MF.Alarm.UACK,427162.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_MF.Alarm.MCmd_Enable,427162.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MF.Alarm.MCmd_Disable,427162.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MF.Alarm.OCmd_Shelve,427162.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_MF.Alarm.OCmd_Unshelve,427162.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_MF.Alarm.SCmd_Suppress,427162.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_MF.Alarm.SCmd_UnSuppress,427163.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_MF.Alarm.AEShelveTMRDN,427163.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_MF.Alarm.Bad,427163.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_MF.Alarm.Suppress,427164.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.UnSuppress,427164.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Shelve,427164.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.UnShelve,427164.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Enable,427164.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Disable,427164.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Ack,427164.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Reset,427164.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_MF.Alarm.Suppressed,427164.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_MF.Alarm.Shelved,427164.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_MF.Alarm.Disabled,427164.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_MF.Alarm.Acked,427164.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_MF.Alarm.Alarm,427164.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Fault,427174.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_MF.almPLCFault.AlarmState,427174.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_MF.almPLCFault.GlobalReset,427174.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_MF.almPLCFault.FaultInAlarm,427174.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MF.almPLCFault.ALRM,427174.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_MF.almPLCFault.ANUN,427174.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_MF.almPLCFault.AKED,427174.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_MF.almPLCFault.Resetable,427174.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_MF.almPLCFault.REST,427174.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_MF.almPLCFault.ACKN,427174.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_MF.almPLCFault.UACK,427174.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_MF.almPLCFault.MCmd_Enable,427174.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MF.almPLCFault.MCmd_Disable,427174.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MF.almPLCFault.OCmd_Shelve,427174.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_MF.almPLCFault.OCmd_Unshelve,427174.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_MF.almPLCFault.SCmd_Suppress,427174.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_MF.almPLCFault.SCmd_UnSuppress,427175.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_MF.almPLCFault.AEShelveTMRDN,427175.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_MF.almPLCFault.Bad,427175.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_MF.almPLCFault.Suppress,427176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.UnSuppress,427176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Shelve,427176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.UnShelve,427176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Enable,427176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Disable,427176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Ack,427176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Reset,427176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Suppressed,427176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Shelved,427176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Disabled,427176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Acked,427176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_MF.almPLCFault.Alarm,427176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Fault,427196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_MY.Alarm.AlarmState,427196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_MY.Alarm.GlobalReset,427196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_MY.Alarm.FaultInAlarm,427196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MY.Alarm.ALRM,427196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_MY.Alarm.ANUN,427196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_MY.Alarm.AKED,427196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_MY.Alarm.Resetable,427196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_MY.Alarm.REST,427196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_MY.Alarm.ACKN,427196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_MY.Alarm.UACK,427196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_MY.Alarm.MCmd_Enable,427196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MY.Alarm.MCmd_Disable,427196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MY.Alarm.OCmd_Shelve,427196.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_MY.Alarm.OCmd_Unshelve,427196.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_MY.Alarm.SCmd_Suppress,427196.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_MY.Alarm.SCmd_UnSuppress,427197.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_MY.Alarm.AEShelveTMRDN,427197.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_MY.Alarm.Bad,427197.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_MY.Alarm.Suppress,427198.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.UnSuppress,427198.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Shelve,427198.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.UnShelve,427198.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Enable,427198.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Disable,427198.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Ack,427198.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Reset,427198.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_MY.Alarm.Suppressed,427198.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_MY.Alarm.Shelved,427198.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_MY.Alarm.Disabled,427198.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_MY.Alarm.Acked,427198.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_MY.Alarm.Alarm,427198.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Fault,427208.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_MY.almPLCFault.AlarmState,427208.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_MY.almPLCFault.GlobalReset,427208.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_MY.almPLCFault.FaultInAlarm,427208.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_MY.almPLCFault.ALRM,427208.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_MY.almPLCFault.ANUN,427208.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_MY.almPLCFault.AKED,427208.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_MY.almPLCFault.Resetable,427208.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_MY.almPLCFault.REST,427208.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_MY.almPLCFault.ACKN,427208.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_MY.almPLCFault.UACK,427208.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_MY.almPLCFault.MCmd_Enable,427208.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_MY.almPLCFault.MCmd_Disable,427208.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_MY.almPLCFault.OCmd_Shelve,427208.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_MY.almPLCFault.OCmd_Unshelve,427208.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_MY.almPLCFault.SCmd_Suppress,427208.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_MY.almPLCFault.SCmd_UnSuppress,427209.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_MY.almPLCFault.AEShelveTMRDN,427209.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_MY.almPLCFault.Bad,427209.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_MY.almPLCFault.Suppress,427210.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.UnSuppress,427210.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Shelve,427210.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.UnShelve,427210.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Enable,427210.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Disable,427210.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Ack,427210.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Reset,427210.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Suppressed,427210.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Shelved,427210.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Disabled,427210.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Acked,427210.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_MY.almPLCFault.Alarm,427210.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Fault,427232.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UA.Alarm.AlarmState,427232.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UA.Alarm.GlobalReset,427232.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UA.Alarm.FaultInAlarm,427232.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UA.Alarm.ALRM,427232.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UA.Alarm.ANUN,427232.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UA.Alarm.AKED,427232.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UA.Alarm.Resetable,427232.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UA.Alarm.REST,427232.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UA.Alarm.ACKN,427232.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UA.Alarm.UACK,427232.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UA.Alarm.MCmd_Enable,427232.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UA.Alarm.MCmd_Disable,427232.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UA.Alarm.OCmd_Shelve,427232.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UA.Alarm.OCmd_Unshelve,427232.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UA.Alarm.SCmd_Suppress,427232.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UA.Alarm.SCmd_UnSuppress,427233.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UA.Alarm.AEShelveTMRDN,427233.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UA.Alarm.Bad,427233.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UA.Alarm.Suppress,427234.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.UnSuppress,427234.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Shelve,427234.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.UnShelve,427234.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Enable,427234.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Disable,427234.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Ack,427234.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Reset,427234.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UA.Alarm.Suppressed,427234.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UA.Alarm.Shelved,427234.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UA.Alarm.Disabled,427234.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UA.Alarm.Acked,427234.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UA.Alarm.Alarm,427234.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Fault,427244.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UA.almPLCFault.AlarmState,427244.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UA.almPLCFault.GlobalReset,427244.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UA.almPLCFault.FaultInAlarm,427244.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UA.almPLCFault.ALRM,427244.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UA.almPLCFault.ANUN,427244.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UA.almPLCFault.AKED,427244.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UA.almPLCFault.Resetable,427244.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UA.almPLCFault.REST,427244.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UA.almPLCFault.ACKN,427244.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UA.almPLCFault.UACK,427244.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UA.almPLCFault.MCmd_Enable,427244.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UA.almPLCFault.MCmd_Disable,427244.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UA.almPLCFault.OCmd_Shelve,427244.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UA.almPLCFault.OCmd_Unshelve,427244.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UA.almPLCFault.SCmd_Suppress,427244.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UA.almPLCFault.SCmd_UnSuppress,427245.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UA.almPLCFault.AEShelveTMRDN,427245.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UA.almPLCFault.Bad,427245.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UA.almPLCFault.Suppress,427246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.UnSuppress,427246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Shelve,427246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.UnShelve,427246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Enable,427246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Disable,427246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Ack,427246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Reset,427246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Suppressed,427246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Shelved,427246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Disabled,427246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Acked,427246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UA.almPLCFault.Alarm,427246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Fault,427266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UH.Alarm.AlarmState,427266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UH.Alarm.GlobalReset,427266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UH.Alarm.FaultInAlarm,427266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UH.Alarm.ALRM,427266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UH.Alarm.ANUN,427266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UH.Alarm.AKED,427266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UH.Alarm.Resetable,427266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UH.Alarm.REST,427266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UH.Alarm.ACKN,427266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UH.Alarm.UACK,427266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UH.Alarm.MCmd_Enable,427266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UH.Alarm.MCmd_Disable,427266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UH.Alarm.OCmd_Shelve,427266.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UH.Alarm.OCmd_Unshelve,427266.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UH.Alarm.SCmd_Suppress,427266.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UH.Alarm.SCmd_UnSuppress,427267.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UH.Alarm.AEShelveTMRDN,427267.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UH.Alarm.Bad,427267.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UH.Alarm.Suppress,427268.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.UnSuppress,427268.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Shelve,427268.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.UnShelve,427268.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Enable,427268.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Disable,427268.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Ack,427268.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Reset,427268.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UH.Alarm.Suppressed,427268.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UH.Alarm.Shelved,427268.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UH.Alarm.Disabled,427268.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UH.Alarm.Acked,427268.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UH.Alarm.Alarm,427268.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Fault,427278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UH.almPLCFault.AlarmState,427278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UH.almPLCFault.GlobalReset,427278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UH.almPLCFault.FaultInAlarm,427278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UH.almPLCFault.ALRM,427278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UH.almPLCFault.ANUN,427278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UH.almPLCFault.AKED,427278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UH.almPLCFault.Resetable,427278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UH.almPLCFault.REST,427278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UH.almPLCFault.ACKN,427278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UH.almPLCFault.UACK,427278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UH.almPLCFault.MCmd_Enable,427278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UH.almPLCFault.MCmd_Disable,427278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UH.almPLCFault.OCmd_Shelve,427278.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UH.almPLCFault.OCmd_Unshelve,427278.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UH.almPLCFault.SCmd_Suppress,427278.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UH.almPLCFault.SCmd_UnSuppress,427279.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UH.almPLCFault.AEShelveTMRDN,427279.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UH.almPLCFault.Bad,427279.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UH.almPLCFault.Suppress,427280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.UnSuppress,427280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Shelve,427280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.UnShelve,427280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Enable,427280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Disable,427280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Ack,427280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Reset,427280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Suppressed,427280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Shelved,427280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Disabled,427280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Acked,427280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UH.almPLCFault.Alarm,427280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Fault,427302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UY.Alarm.AlarmState,427302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UY.Alarm.GlobalReset,427302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UY.Alarm.FaultInAlarm,427302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UY.Alarm.ALRM,427302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UY.Alarm.ANUN,427302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UY.Alarm.AKED,427302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UY.Alarm.Resetable,427302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UY.Alarm.REST,427302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UY.Alarm.ACKN,427302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UY.Alarm.UACK,427302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UY.Alarm.MCmd_Enable,427302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UY.Alarm.MCmd_Disable,427302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UY.Alarm.OCmd_Shelve,427302.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UY.Alarm.OCmd_Unshelve,427302.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UY.Alarm.SCmd_Suppress,427302.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UY.Alarm.SCmd_UnSuppress,427303.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UY.Alarm.AEShelveTMRDN,427303.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UY.Alarm.Bad,427303.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UY.Alarm.Suppress,427304.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.UnSuppress,427304.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Shelve,427304.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.UnShelve,427304.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Enable,427304.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Disable,427304.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Ack,427304.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Reset,427304.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UY.Alarm.Suppressed,427304.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UY.Alarm.Shelved,427304.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UY.Alarm.Disabled,427304.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UY.Alarm.Acked,427304.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UY.Alarm.Alarm,427304.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Fault,427314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_UY.almPLCFault.AlarmState,427314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_UY.almPLCFault.GlobalReset,427314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_UY.almPLCFault.FaultInAlarm,427314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_UY.almPLCFault.ALRM,427314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_UY.almPLCFault.ANUN,427314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_UY.almPLCFault.AKED,427314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_UY.almPLCFault.Resetable,427314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_UY.almPLCFault.REST,427314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_UY.almPLCFault.ACKN,427314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_UY.almPLCFault.UACK,427314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_UY.almPLCFault.MCmd_Enable,427314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_UY.almPLCFault.MCmd_Disable,427314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_UY.almPLCFault.OCmd_Shelve,427314.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_UY.almPLCFault.OCmd_Unshelve,427314.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_UY.almPLCFault.SCmd_Suppress,427314.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_UY.almPLCFault.SCmd_UnSuppress,427315.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_UY.almPLCFault.AEShelveTMRDN,427315.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_UY.almPLCFault.Bad,427315.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_UY.almPLCFault.Suppress,427316.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.UnSuppress,427316.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Shelve,427316.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.UnShelve,427316.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Enable,427316.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Disable,427316.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Ack,427316.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Reset,427316.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Suppressed,427316.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Shelved,427316.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Disabled,427316.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Acked,427316.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_UY.almPLCFault.Alarm,427316.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Fault,427336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_XF.Alarm.AlarmState,427336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_XF.Alarm.GlobalReset,427336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_XF.Alarm.FaultInAlarm,427336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_XF.Alarm.ALRM,427336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_XF.Alarm.ANUN,427336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_XF.Alarm.AKED,427336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_XF.Alarm.Resetable,427336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_XF.Alarm.REST,427336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_XF.Alarm.ACKN,427336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_XF.Alarm.UACK,427336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_XF.Alarm.MCmd_Enable,427336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_XF.Alarm.MCmd_Disable,427336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_XF.Alarm.OCmd_Shelve,427336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_XF.Alarm.OCmd_Unshelve,427336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_XF.Alarm.SCmd_Suppress,427336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_XF.Alarm.SCmd_UnSuppress,427337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_XF.Alarm.AEShelveTMRDN,427337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_XF.Alarm.Bad,427337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_XF.Alarm.Suppress,427338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.UnSuppress,427338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Shelve,427338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.UnShelve,427338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Enable,427338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Disable,427338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Ack,427338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Reset,427338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_XF.Alarm.Suppressed,427338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_XF.Alarm.Shelved,427338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_XF.Alarm.Disabled,427338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_XF.Alarm.Acked,427338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_XF.Alarm.Alarm,427338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Fault,427348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_XF.almPLCFault.AlarmState,427348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_XF.almPLCFault.GlobalReset,427348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_XF.almPLCFault.FaultInAlarm,427348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_XF.almPLCFault.ALRM,427348.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_XF.almPLCFault.ANUN,427348.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_XF.almPLCFault.AKED,427348.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_XF.almPLCFault.Resetable,427348.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_XF.almPLCFault.REST,427348.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_XF.almPLCFault.ACKN,427348.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_XF.almPLCFault.UACK,427348.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_XF.almPLCFault.MCmd_Enable,427348.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_XF.almPLCFault.MCmd_Disable,427348.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_XF.almPLCFault.OCmd_Shelve,427348.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_XF.almPLCFault.OCmd_Unshelve,427348.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_XF.almPLCFault.SCmd_Suppress,427348.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_XF.almPLCFault.SCmd_UnSuppress,427349.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_XF.almPLCFault.AEShelveTMRDN,427349.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_XF.almPLCFault.Bad,427349.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_XF.almPLCFault.Suppress,427350.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.UnSuppress,427350.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Shelve,427350.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.UnShelve,427350.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Enable,427350.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Disable,427350.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Ack,427350.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Reset,427350.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Suppressed,427350.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Shelved,427350.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Disabled,427350.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Acked,427350.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_XF.almPLCFault.Alarm,427350.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Fault,427372.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_YA.Alarm.AlarmState,427372.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_YA.Alarm.GlobalReset,427372.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_YA.Alarm.FaultInAlarm,427372.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_YA.Alarm.ALRM,427372.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_YA.Alarm.ANUN,427372.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_YA.Alarm.AKED,427372.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_YA.Alarm.Resetable,427372.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_YA.Alarm.REST,427372.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_YA.Alarm.ACKN,427372.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_YA.Alarm.UACK,427372.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_YA.Alarm.MCmd_Enable,427372.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_YA.Alarm.MCmd_Disable,427372.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_YA.Alarm.OCmd_Shelve,427372.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_YA.Alarm.OCmd_Unshelve,427372.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_YA.Alarm.SCmd_Suppress,427372.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_YA.Alarm.SCmd_UnSuppress,427373.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_YA.Alarm.AEShelveTMRDN,427373.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_YA.Alarm.Bad,427373.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_YA.Alarm.Suppress,427374.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.UnSuppress,427374.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Shelve,427374.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.UnShelve,427374.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Enable,427374.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Disable,427374.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Ack,427374.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Reset,427374.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_YA.Alarm.Suppressed,427374.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_YA.Alarm.Shelved,427374.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_YA.Alarm.Disabled,427374.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_YA.Alarm.Acked,427374.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_YA.Alarm.Alarm,427374.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Fault,427384.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5_YA.almPLCFault.AlarmState,427384.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5_YA.almPLCFault.GlobalReset,427384.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5_YA.almPLCFault.FaultInAlarm,427384.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5_YA.almPLCFault.ALRM,427384.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5_YA.almPLCFault.ANUN,427384.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5_YA.almPLCFault.AKED,427384.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5_YA.almPLCFault.Resetable,427384.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5_YA.almPLCFault.REST,427384.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5_YA.almPLCFault.ACKN,427384.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5_YA.almPLCFault.UACK,427384.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5_YA.almPLCFault.MCmd_Enable,427384.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5_YA.almPLCFault.MCmd_Disable,427384.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5_YA.almPLCFault.OCmd_Shelve,427384.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5_YA.almPLCFault.OCmd_Unshelve,427384.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5_YA.almPLCFault.SCmd_Suppress,427384.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5_YA.almPLCFault.SCmd_UnSuppress,427385.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5_YA.almPLCFault.AEShelveTMRDN,427385.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5_YA.almPLCFault.Bad,427385.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5_YA.almPLCFault.Suppress,427386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.UnSuppress,427386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Shelve,427386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.UnShelve,427386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Enable,427386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Disable,427386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Ack,427386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Reset,427386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Suppressed,427386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Shelved,427386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Disabled,427386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Acked,427386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5_YA.almPLCFault.Alarm,427386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Fault,427406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_FA.Alarm.AlarmState,427406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_FA.Alarm.GlobalReset,427406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_FA.Alarm.FaultInAlarm,427406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_FA.Alarm.ALRM,427406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_FA.Alarm.ANUN,427406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_FA.Alarm.AKED,427406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_FA.Alarm.Resetable,427406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_FA.Alarm.REST,427406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_FA.Alarm.ACKN,427406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_FA.Alarm.UACK,427406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_FA.Alarm.MCmd_Enable,427406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_FA.Alarm.MCmd_Disable,427406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_FA.Alarm.OCmd_Shelve,427406.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_FA.Alarm.OCmd_Unshelve,427406.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_FA.Alarm.SCmd_Suppress,427406.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_FA.Alarm.SCmd_UnSuppress,427407.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_FA.Alarm.AEShelveTMRDN,427407.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_FA.Alarm.Bad,427407.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_FA.Alarm.Suppress,427408.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.UnSuppress,427408.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Shelve,427408.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.UnShelve,427408.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Enable,427408.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Disable,427408.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Ack,427408.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Reset,427408.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_FA.Alarm.Suppressed,427408.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_FA.Alarm.Shelved,427408.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_FA.Alarm.Disabled,427408.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_FA.Alarm.Acked,427408.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_FA.Alarm.Alarm,427408.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Fault,427418.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_FA.almPLCFault.AlarmState,427418.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_FA.almPLCFault.GlobalReset,427418.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_FA.almPLCFault.FaultInAlarm,427418.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_FA.almPLCFault.ALRM,427418.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_FA.almPLCFault.ANUN,427418.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_FA.almPLCFault.AKED,427418.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_FA.almPLCFault.Resetable,427418.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_FA.almPLCFault.REST,427418.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_FA.almPLCFault.ACKN,427418.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_FA.almPLCFault.UACK,427418.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_FA.almPLCFault.MCmd_Enable,427418.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_FA.almPLCFault.MCmd_Disable,427418.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_FA.almPLCFault.OCmd_Shelve,427418.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_FA.almPLCFault.OCmd_Unshelve,427418.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_FA.almPLCFault.SCmd_Suppress,427418.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_FA.almPLCFault.SCmd_UnSuppress,427419.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_FA.almPLCFault.AEShelveTMRDN,427419.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_FA.almPLCFault.Bad,427419.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_FA.almPLCFault.Suppress,427420.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.UnSuppress,427420.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Shelve,427420.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.UnShelve,427420.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Enable,427420.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Disable,427420.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Ack,427420.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Reset,427420.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Suppressed,427420.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Shelved,427420.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Disabled,427420.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Acked,427420.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_FA.almPLCFault.Alarm,427420.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Fault,427442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_MF.Alarm.AlarmState,427442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_MF.Alarm.GlobalReset,427442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_MF.Alarm.FaultInAlarm,427442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MF.Alarm.ALRM,427442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_MF.Alarm.ANUN,427442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_MF.Alarm.AKED,427442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_MF.Alarm.Resetable,427442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_MF.Alarm.REST,427442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_MF.Alarm.ACKN,427442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_MF.Alarm.UACK,427442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_MF.Alarm.MCmd_Enable,427442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MF.Alarm.MCmd_Disable,427442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MF.Alarm.OCmd_Shelve,427442.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_MF.Alarm.OCmd_Unshelve,427442.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_MF.Alarm.SCmd_Suppress,427442.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_MF.Alarm.SCmd_UnSuppress,427443.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_MF.Alarm.AEShelveTMRDN,427443.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_MF.Alarm.Bad,427443.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_MF.Alarm.Suppress,427444.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.UnSuppress,427444.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Shelve,427444.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.UnShelve,427444.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Enable,427444.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Disable,427444.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Ack,427444.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Reset,427444.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_MF.Alarm.Suppressed,427444.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_MF.Alarm.Shelved,427444.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_MF.Alarm.Disabled,427444.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_MF.Alarm.Acked,427444.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_MF.Alarm.Alarm,427444.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Fault,427454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_MF.almPLCFault.AlarmState,427454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_MF.almPLCFault.GlobalReset,427454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_MF.almPLCFault.FaultInAlarm,427454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MF.almPLCFault.ALRM,427454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_MF.almPLCFault.ANUN,427454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_MF.almPLCFault.AKED,427454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_MF.almPLCFault.Resetable,427454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_MF.almPLCFault.REST,427454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_MF.almPLCFault.ACKN,427454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_MF.almPLCFault.UACK,427454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_MF.almPLCFault.MCmd_Enable,427454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MF.almPLCFault.MCmd_Disable,427454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MF.almPLCFault.OCmd_Shelve,427454.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_MF.almPLCFault.OCmd_Unshelve,427454.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_MF.almPLCFault.SCmd_Suppress,427454.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_MF.almPLCFault.SCmd_UnSuppress,427455.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_MF.almPLCFault.AEShelveTMRDN,427455.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_MF.almPLCFault.Bad,427455.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_MF.almPLCFault.Suppress,427456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.UnSuppress,427456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Shelve,427456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.UnShelve,427456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Enable,427456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Disable,427456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Ack,427456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Reset,427456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Suppressed,427456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Shelved,427456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Disabled,427456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Acked,427456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_MF.almPLCFault.Alarm,427456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Fault,427476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_MY.Alarm.AlarmState,427476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_MY.Alarm.GlobalReset,427476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_MY.Alarm.FaultInAlarm,427476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MY.Alarm.ALRM,427476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_MY.Alarm.ANUN,427476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_MY.Alarm.AKED,427476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_MY.Alarm.Resetable,427476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_MY.Alarm.REST,427476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_MY.Alarm.ACKN,427476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_MY.Alarm.UACK,427476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_MY.Alarm.MCmd_Enable,427476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MY.Alarm.MCmd_Disable,427476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MY.Alarm.OCmd_Shelve,427476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_MY.Alarm.OCmd_Unshelve,427476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_MY.Alarm.SCmd_Suppress,427476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_MY.Alarm.SCmd_UnSuppress,427477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_MY.Alarm.AEShelveTMRDN,427477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_MY.Alarm.Bad,427477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_MY.Alarm.Suppress,427478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.UnSuppress,427478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Shelve,427478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.UnShelve,427478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Enable,427478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Disable,427478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Ack,427478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Reset,427478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_MY.Alarm.Suppressed,427478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_MY.Alarm.Shelved,427478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_MY.Alarm.Disabled,427478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_MY.Alarm.Acked,427478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_MY.Alarm.Alarm,427478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Fault,427488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_MY.almPLCFault.AlarmState,427488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_MY.almPLCFault.GlobalReset,427488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_MY.almPLCFault.FaultInAlarm,427488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_MY.almPLCFault.ALRM,427488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_MY.almPLCFault.ANUN,427488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_MY.almPLCFault.AKED,427488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_MY.almPLCFault.Resetable,427488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_MY.almPLCFault.REST,427488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_MY.almPLCFault.ACKN,427488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_MY.almPLCFault.UACK,427488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_MY.almPLCFault.MCmd_Enable,427488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_MY.almPLCFault.MCmd_Disable,427488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_MY.almPLCFault.OCmd_Shelve,427488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_MY.almPLCFault.OCmd_Unshelve,427488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_MY.almPLCFault.SCmd_Suppress,427488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_MY.almPLCFault.SCmd_UnSuppress,427489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_MY.almPLCFault.AEShelveTMRDN,427489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_MY.almPLCFault.Bad,427489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_MY.almPLCFault.Suppress,427490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.UnSuppress,427490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Shelve,427490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.UnShelve,427490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Enable,427490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Disable,427490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Ack,427490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Reset,427490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Suppressed,427490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Shelved,427490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Disabled,427490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Acked,427490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_MY.almPLCFault.Alarm,427490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Fault,427512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UA.Alarm.AlarmState,427512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UA.Alarm.GlobalReset,427512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UA.Alarm.FaultInAlarm,427512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UA.Alarm.ALRM,427512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UA.Alarm.ANUN,427512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UA.Alarm.AKED,427512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UA.Alarm.Resetable,427512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UA.Alarm.REST,427512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UA.Alarm.ACKN,427512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UA.Alarm.UACK,427512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UA.Alarm.MCmd_Enable,427512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UA.Alarm.MCmd_Disable,427512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UA.Alarm.OCmd_Shelve,427512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UA.Alarm.OCmd_Unshelve,427512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UA.Alarm.SCmd_Suppress,427512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UA.Alarm.SCmd_UnSuppress,427513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UA.Alarm.AEShelveTMRDN,427513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UA.Alarm.Bad,427513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UA.Alarm.Suppress,427514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.UnSuppress,427514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Shelve,427514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.UnShelve,427514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Enable,427514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Disable,427514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Ack,427514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Reset,427514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UA.Alarm.Suppressed,427514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UA.Alarm.Shelved,427514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UA.Alarm.Disabled,427514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UA.Alarm.Acked,427514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UA.Alarm.Alarm,427514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Fault,427524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UA.almPLCFault.AlarmState,427524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UA.almPLCFault.GlobalReset,427524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UA.almPLCFault.FaultInAlarm,427524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UA.almPLCFault.ALRM,427524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UA.almPLCFault.ANUN,427524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UA.almPLCFault.AKED,427524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UA.almPLCFault.Resetable,427524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UA.almPLCFault.REST,427524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UA.almPLCFault.ACKN,427524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UA.almPLCFault.UACK,427524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UA.almPLCFault.MCmd_Enable,427524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UA.almPLCFault.MCmd_Disable,427524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UA.almPLCFault.OCmd_Shelve,427524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UA.almPLCFault.OCmd_Unshelve,427524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UA.almPLCFault.SCmd_Suppress,427524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UA.almPLCFault.SCmd_UnSuppress,427525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UA.almPLCFault.AEShelveTMRDN,427525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UA.almPLCFault.Bad,427525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UA.almPLCFault.Suppress,427526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.UnSuppress,427526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Shelve,427526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.UnShelve,427526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Enable,427526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Disable,427526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Ack,427526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Reset,427526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Suppressed,427526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Shelved,427526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Disabled,427526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Acked,427526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UA.almPLCFault.Alarm,427526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Fault,427546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UH.Alarm.AlarmState,427546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UH.Alarm.GlobalReset,427546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UH.Alarm.FaultInAlarm,427546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UH.Alarm.ALRM,427546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UH.Alarm.ANUN,427546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UH.Alarm.AKED,427546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UH.Alarm.Resetable,427546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UH.Alarm.REST,427546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UH.Alarm.ACKN,427546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UH.Alarm.UACK,427546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UH.Alarm.MCmd_Enable,427546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UH.Alarm.MCmd_Disable,427546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UH.Alarm.OCmd_Shelve,427546.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UH.Alarm.OCmd_Unshelve,427546.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UH.Alarm.SCmd_Suppress,427546.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UH.Alarm.SCmd_UnSuppress,427547.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UH.Alarm.AEShelveTMRDN,427547.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UH.Alarm.Bad,427547.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UH.Alarm.Suppress,427548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.UnSuppress,427548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Shelve,427548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.UnShelve,427548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Enable,427548.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Disable,427548.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Ack,427548.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Reset,427548.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UH.Alarm.Suppressed,427548.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UH.Alarm.Shelved,427548.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UH.Alarm.Disabled,427548.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UH.Alarm.Acked,427548.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UH.Alarm.Alarm,427548.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Fault,427558.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UH.almPLCFault.AlarmState,427558.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UH.almPLCFault.GlobalReset,427558.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UH.almPLCFault.FaultInAlarm,427558.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UH.almPLCFault.ALRM,427558.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UH.almPLCFault.ANUN,427558.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UH.almPLCFault.AKED,427558.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UH.almPLCFault.Resetable,427558.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UH.almPLCFault.REST,427558.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UH.almPLCFault.ACKN,427558.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UH.almPLCFault.UACK,427558.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UH.almPLCFault.MCmd_Enable,427558.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UH.almPLCFault.MCmd_Disable,427558.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UH.almPLCFault.OCmd_Shelve,427558.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UH.almPLCFault.OCmd_Unshelve,427558.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UH.almPLCFault.SCmd_Suppress,427558.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UH.almPLCFault.SCmd_UnSuppress,427559.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UH.almPLCFault.AEShelveTMRDN,427559.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UH.almPLCFault.Bad,427559.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UH.almPLCFault.Suppress,427560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.UnSuppress,427560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Shelve,427560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.UnShelve,427560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Enable,427560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Disable,427560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Ack,427560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Reset,427560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Suppressed,427560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Shelved,427560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Disabled,427560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Acked,427560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UH.almPLCFault.Alarm,427560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Fault,427582.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UY.Alarm.AlarmState,427582.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UY.Alarm.GlobalReset,427582.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UY.Alarm.FaultInAlarm,427582.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UY.Alarm.ALRM,427582.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UY.Alarm.ANUN,427582.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UY.Alarm.AKED,427582.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UY.Alarm.Resetable,427582.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UY.Alarm.REST,427582.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UY.Alarm.ACKN,427582.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UY.Alarm.UACK,427582.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UY.Alarm.MCmd_Enable,427582.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UY.Alarm.MCmd_Disable,427582.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UY.Alarm.OCmd_Shelve,427582.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UY.Alarm.OCmd_Unshelve,427582.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UY.Alarm.SCmd_Suppress,427582.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UY.Alarm.SCmd_UnSuppress,427583.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UY.Alarm.AEShelveTMRDN,427583.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UY.Alarm.Bad,427583.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UY.Alarm.Suppress,427584.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.UnSuppress,427584.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Shelve,427584.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.UnShelve,427584.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Enable,427584.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Disable,427584.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Ack,427584.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Reset,427584.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UY.Alarm.Suppressed,427584.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UY.Alarm.Shelved,427584.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UY.Alarm.Disabled,427584.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UY.Alarm.Acked,427584.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UY.Alarm.Alarm,427584.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Fault,427594.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_UY.almPLCFault.AlarmState,427594.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_UY.almPLCFault.GlobalReset,427594.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_UY.almPLCFault.FaultInAlarm,427594.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_UY.almPLCFault.ALRM,427594.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_UY.almPLCFault.ANUN,427594.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_UY.almPLCFault.AKED,427594.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_UY.almPLCFault.Resetable,427594.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_UY.almPLCFault.REST,427594.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_UY.almPLCFault.ACKN,427594.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_UY.almPLCFault.UACK,427594.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_UY.almPLCFault.MCmd_Enable,427594.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_UY.almPLCFault.MCmd_Disable,427594.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_UY.almPLCFault.OCmd_Shelve,427594.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_UY.almPLCFault.OCmd_Unshelve,427594.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_UY.almPLCFault.SCmd_Suppress,427594.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_UY.almPLCFault.SCmd_UnSuppress,427595.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_UY.almPLCFault.AEShelveTMRDN,427595.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_UY.almPLCFault.Bad,427595.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_UY.almPLCFault.Suppress,427596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.UnSuppress,427596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Shelve,427596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.UnShelve,427596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Enable,427596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Disable,427596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Ack,427596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Reset,427596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Suppressed,427596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Shelved,427596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Disabled,427596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Acked,427596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_UY.almPLCFault.Alarm,427596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Fault,427616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_XF.Alarm.AlarmState,427616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_XF.Alarm.GlobalReset,427616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_XF.Alarm.FaultInAlarm,427616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_XF.Alarm.ALRM,427616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_XF.Alarm.ANUN,427616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_XF.Alarm.AKED,427616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_XF.Alarm.Resetable,427616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_XF.Alarm.REST,427616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_XF.Alarm.ACKN,427616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_XF.Alarm.UACK,427616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_XF.Alarm.MCmd_Enable,427616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_XF.Alarm.MCmd_Disable,427616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_XF.Alarm.OCmd_Shelve,427616.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_XF.Alarm.OCmd_Unshelve,427616.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_XF.Alarm.SCmd_Suppress,427616.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_XF.Alarm.SCmd_UnSuppress,427617.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_XF.Alarm.AEShelveTMRDN,427617.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_XF.Alarm.Bad,427617.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_XF.Alarm.Suppress,427618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.UnSuppress,427618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Shelve,427618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.UnShelve,427618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Enable,427618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Disable,427618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Ack,427618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Reset,427618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_XF.Alarm.Suppressed,427618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_XF.Alarm.Shelved,427618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_XF.Alarm.Disabled,427618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_XF.Alarm.Acked,427618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_XF.Alarm.Alarm,427618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Fault,427628.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_XF.almPLCFault.AlarmState,427628.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_XF.almPLCFault.GlobalReset,427628.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_XF.almPLCFault.FaultInAlarm,427628.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_XF.almPLCFault.ALRM,427628.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_XF.almPLCFault.ANUN,427628.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_XF.almPLCFault.AKED,427628.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_XF.almPLCFault.Resetable,427628.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_XF.almPLCFault.REST,427628.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_XF.almPLCFault.ACKN,427628.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_XF.almPLCFault.UACK,427628.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_XF.almPLCFault.MCmd_Enable,427628.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_XF.almPLCFault.MCmd_Disable,427628.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_XF.almPLCFault.OCmd_Shelve,427628.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_XF.almPLCFault.OCmd_Unshelve,427628.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_XF.almPLCFault.SCmd_Suppress,427628.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_XF.almPLCFault.SCmd_UnSuppress,427629.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_XF.almPLCFault.AEShelveTMRDN,427629.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_XF.almPLCFault.Bad,427629.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_XF.almPLCFault.Suppress,427630.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.UnSuppress,427630.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Shelve,427630.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.UnShelve,427630.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Enable,427630.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Disable,427630.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Ack,427630.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Reset,427630.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Suppressed,427630.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Shelved,427630.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Disabled,427630.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Acked,427630.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_XF.almPLCFault.Alarm,427630.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Fault,427652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_YA.Alarm.AlarmState,427652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_YA.Alarm.GlobalReset,427652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_YA.Alarm.FaultInAlarm,427652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_YA.Alarm.ALRM,427652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_YA.Alarm.ANUN,427652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_YA.Alarm.AKED,427652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_YA.Alarm.Resetable,427652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_YA.Alarm.REST,427652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_YA.Alarm.ACKN,427652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_YA.Alarm.UACK,427652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_YA.Alarm.MCmd_Enable,427652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_YA.Alarm.MCmd_Disable,427652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_YA.Alarm.OCmd_Shelve,427652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_YA.Alarm.OCmd_Unshelve,427652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_YA.Alarm.SCmd_Suppress,427652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_YA.Alarm.SCmd_UnSuppress,427653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_YA.Alarm.AEShelveTMRDN,427653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_YA.Alarm.Bad,427653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_YA.Alarm.Suppress,427654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.UnSuppress,427654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Shelve,427654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.UnShelve,427654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Enable,427654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Disable,427654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Ack,427654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Reset,427654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_YA.Alarm.Suppressed,427654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_YA.Alarm.Shelved,427654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_YA.Alarm.Disabled,427654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_YA.Alarm.Acked,427654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_YA.Alarm.Alarm,427654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Fault,427664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6_YA.almPLCFault.AlarmState,427664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6_YA.almPLCFault.GlobalReset,427664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6_YA.almPLCFault.FaultInAlarm,427664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6_YA.almPLCFault.ALRM,427664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6_YA.almPLCFault.ANUN,427664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6_YA.almPLCFault.AKED,427664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6_YA.almPLCFault.Resetable,427664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6_YA.almPLCFault.REST,427664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6_YA.almPLCFault.ACKN,427664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6_YA.almPLCFault.UACK,427664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6_YA.almPLCFault.MCmd_Enable,427664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6_YA.almPLCFault.MCmd_Disable,427664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6_YA.almPLCFault.OCmd_Shelve,427664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6_YA.almPLCFault.OCmd_Unshelve,427664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6_YA.almPLCFault.SCmd_Suppress,427664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6_YA.almPLCFault.SCmd_UnSuppress,427665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6_YA.almPLCFault.AEShelveTMRDN,427665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6_YA.almPLCFault.Bad,427665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6_YA.almPLCFault.Suppress,427666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.UnSuppress,427666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Shelve,427666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.UnShelve,427666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Enable,427666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Disable,427666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Ack,427666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Reset,427666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Suppressed,427666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Shelved,427666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Disabled,427666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Acked,427666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6_YA.almPLCFault.Alarm,427666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Fault,427686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_FA.Alarm.AlarmState,427686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_FA.Alarm.GlobalReset,427686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_FA.Alarm.FaultInAlarm,427686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_FA.Alarm.ALRM,427686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_FA.Alarm.ANUN,427686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_FA.Alarm.AKED,427686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_FA.Alarm.Resetable,427686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_FA.Alarm.REST,427686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_FA.Alarm.ACKN,427686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_FA.Alarm.UACK,427686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_FA.Alarm.MCmd_Enable,427686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_FA.Alarm.MCmd_Disable,427686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_FA.Alarm.OCmd_Shelve,427686.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_FA.Alarm.OCmd_Unshelve,427686.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_FA.Alarm.SCmd_Suppress,427686.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_FA.Alarm.SCmd_UnSuppress,427687.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_FA.Alarm.AEShelveTMRDN,427687.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_FA.Alarm.Bad,427687.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_FA.Alarm.Suppress,427688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.UnSuppress,427688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Shelve,427688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.UnShelve,427688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Enable,427688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Disable,427688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Ack,427688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Reset,427688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_FA.Alarm.Suppressed,427688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_FA.Alarm.Shelved,427688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_FA.Alarm.Disabled,427688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_FA.Alarm.Acked,427688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_FA.Alarm.Alarm,427688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Fault,427698.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_FA.almPLCFault.AlarmState,427698.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_FA.almPLCFault.GlobalReset,427698.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_FA.almPLCFault.FaultInAlarm,427698.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_FA.almPLCFault.ALRM,427698.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_FA.almPLCFault.ANUN,427698.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_FA.almPLCFault.AKED,427698.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_FA.almPLCFault.Resetable,427698.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_FA.almPLCFault.REST,427698.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_FA.almPLCFault.ACKN,427698.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_FA.almPLCFault.UACK,427698.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_FA.almPLCFault.MCmd_Enable,427698.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_FA.almPLCFault.MCmd_Disable,427698.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_FA.almPLCFault.OCmd_Shelve,427698.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_FA.almPLCFault.OCmd_Unshelve,427698.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_FA.almPLCFault.SCmd_Suppress,427698.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_FA.almPLCFault.SCmd_UnSuppress,427699.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_FA.almPLCFault.AEShelveTMRDN,427699.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_FA.almPLCFault.Bad,427699.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_FA.almPLCFault.Suppress,427700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.UnSuppress,427700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Shelve,427700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.UnShelve,427700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Enable,427700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Disable,427700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Ack,427700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Reset,427700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Suppressed,427700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Shelved,427700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Disabled,427700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Acked,427700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_FA.almPLCFault.Alarm,427700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Fault,427722.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_MF.Alarm.AlarmState,427722.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_MF.Alarm.GlobalReset,427722.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_MF.Alarm.FaultInAlarm,427722.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MF.Alarm.ALRM,427722.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_MF.Alarm.ANUN,427722.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_MF.Alarm.AKED,427722.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_MF.Alarm.Resetable,427722.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_MF.Alarm.REST,427722.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_MF.Alarm.ACKN,427722.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_MF.Alarm.UACK,427722.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_MF.Alarm.MCmd_Enable,427722.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MF.Alarm.MCmd_Disable,427722.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MF.Alarm.OCmd_Shelve,427722.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_MF.Alarm.OCmd_Unshelve,427722.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_MF.Alarm.SCmd_Suppress,427722.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_MF.Alarm.SCmd_UnSuppress,427723.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_MF.Alarm.AEShelveTMRDN,427723.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_MF.Alarm.Bad,427723.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_MF.Alarm.Suppress,427724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.UnSuppress,427724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Shelve,427724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.UnShelve,427724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Enable,427724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Disable,427724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Ack,427724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Reset,427724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_MF.Alarm.Suppressed,427724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_MF.Alarm.Shelved,427724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_MF.Alarm.Disabled,427724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_MF.Alarm.Acked,427724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_MF.Alarm.Alarm,427724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Fault,427734.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_MF.almPLCFault.AlarmState,427734.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_MF.almPLCFault.GlobalReset,427734.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_MF.almPLCFault.FaultInAlarm,427734.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MF.almPLCFault.ALRM,427734.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_MF.almPLCFault.ANUN,427734.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_MF.almPLCFault.AKED,427734.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_MF.almPLCFault.Resetable,427734.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_MF.almPLCFault.REST,427734.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_MF.almPLCFault.ACKN,427734.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_MF.almPLCFault.UACK,427734.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_MF.almPLCFault.MCmd_Enable,427734.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MF.almPLCFault.MCmd_Disable,427734.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MF.almPLCFault.OCmd_Shelve,427734.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_MF.almPLCFault.OCmd_Unshelve,427734.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_MF.almPLCFault.SCmd_Suppress,427734.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_MF.almPLCFault.SCmd_UnSuppress,427735.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_MF.almPLCFault.AEShelveTMRDN,427735.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_MF.almPLCFault.Bad,427735.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_MF.almPLCFault.Suppress,427736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.UnSuppress,427736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Shelve,427736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.UnShelve,427736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Enable,427736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Disable,427736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Ack,427736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Reset,427736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Suppressed,427736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Shelved,427736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Disabled,427736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Acked,427736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_MF.almPLCFault.Alarm,427736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Fault,427756.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_MY.Alarm.AlarmState,427756.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_MY.Alarm.GlobalReset,427756.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_MY.Alarm.FaultInAlarm,427756.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MY.Alarm.ALRM,427756.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_MY.Alarm.ANUN,427756.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_MY.Alarm.AKED,427756.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_MY.Alarm.Resetable,427756.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_MY.Alarm.REST,427756.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_MY.Alarm.ACKN,427756.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_MY.Alarm.UACK,427756.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_MY.Alarm.MCmd_Enable,427756.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MY.Alarm.MCmd_Disable,427756.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MY.Alarm.OCmd_Shelve,427756.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_MY.Alarm.OCmd_Unshelve,427756.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_MY.Alarm.SCmd_Suppress,427756.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_MY.Alarm.SCmd_UnSuppress,427757.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_MY.Alarm.AEShelveTMRDN,427757.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_MY.Alarm.Bad,427757.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_MY.Alarm.Suppress,427758.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.UnSuppress,427758.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Shelve,427758.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.UnShelve,427758.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Enable,427758.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Disable,427758.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Ack,427758.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Reset,427758.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_MY.Alarm.Suppressed,427758.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_MY.Alarm.Shelved,427758.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_MY.Alarm.Disabled,427758.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_MY.Alarm.Acked,427758.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_MY.Alarm.Alarm,427758.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Fault,427768.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_MY.almPLCFault.AlarmState,427768.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_MY.almPLCFault.GlobalReset,427768.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_MY.almPLCFault.FaultInAlarm,427768.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_MY.almPLCFault.ALRM,427768.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_MY.almPLCFault.ANUN,427768.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_MY.almPLCFault.AKED,427768.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_MY.almPLCFault.Resetable,427768.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_MY.almPLCFault.REST,427768.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_MY.almPLCFault.ACKN,427768.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_MY.almPLCFault.UACK,427768.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_MY.almPLCFault.MCmd_Enable,427768.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_MY.almPLCFault.MCmd_Disable,427768.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_MY.almPLCFault.OCmd_Shelve,427768.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_MY.almPLCFault.OCmd_Unshelve,427768.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_MY.almPLCFault.SCmd_Suppress,427768.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_MY.almPLCFault.SCmd_UnSuppress,427769.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_MY.almPLCFault.AEShelveTMRDN,427769.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_MY.almPLCFault.Bad,427769.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_MY.almPLCFault.Suppress,427770.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.UnSuppress,427770.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Shelve,427770.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.UnShelve,427770.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Enable,427770.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Disable,427770.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Ack,427770.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Reset,427770.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Suppressed,427770.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Shelved,427770.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Disabled,427770.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Acked,427770.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_MY.almPLCFault.Alarm,427770.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Fault,427792.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UA.Alarm.AlarmState,427792.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UA.Alarm.GlobalReset,427792.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UA.Alarm.FaultInAlarm,427792.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UA.Alarm.ALRM,427792.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UA.Alarm.ANUN,427792.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UA.Alarm.AKED,427792.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UA.Alarm.Resetable,427792.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UA.Alarm.REST,427792.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UA.Alarm.ACKN,427792.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UA.Alarm.UACK,427792.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UA.Alarm.MCmd_Enable,427792.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UA.Alarm.MCmd_Disable,427792.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UA.Alarm.OCmd_Shelve,427792.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UA.Alarm.OCmd_Unshelve,427792.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UA.Alarm.SCmd_Suppress,427792.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UA.Alarm.SCmd_UnSuppress,427793.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UA.Alarm.AEShelveTMRDN,427793.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UA.Alarm.Bad,427793.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UA.Alarm.Suppress,427794.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.UnSuppress,427794.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Shelve,427794.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.UnShelve,427794.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Enable,427794.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Disable,427794.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Ack,427794.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Reset,427794.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UA.Alarm.Suppressed,427794.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UA.Alarm.Shelved,427794.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UA.Alarm.Disabled,427794.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UA.Alarm.Acked,427794.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UA.Alarm.Alarm,427794.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Fault,427804.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UA.almPLCFault.AlarmState,427804.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UA.almPLCFault.GlobalReset,427804.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UA.almPLCFault.FaultInAlarm,427804.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UA.almPLCFault.ALRM,427804.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UA.almPLCFault.ANUN,427804.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UA.almPLCFault.AKED,427804.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UA.almPLCFault.Resetable,427804.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UA.almPLCFault.REST,427804.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UA.almPLCFault.ACKN,427804.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UA.almPLCFault.UACK,427804.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UA.almPLCFault.MCmd_Enable,427804.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UA.almPLCFault.MCmd_Disable,427804.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UA.almPLCFault.OCmd_Shelve,427804.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UA.almPLCFault.OCmd_Unshelve,427804.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UA.almPLCFault.SCmd_Suppress,427804.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UA.almPLCFault.SCmd_UnSuppress,427805.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UA.almPLCFault.AEShelveTMRDN,427805.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UA.almPLCFault.Bad,427805.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UA.almPLCFault.Suppress,427806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.UnSuppress,427806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Shelve,427806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.UnShelve,427806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Enable,427806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Disable,427806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Ack,427806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Reset,427806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Suppressed,427806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Shelved,427806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Disabled,427806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Acked,427806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UA.almPLCFault.Alarm,427806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Fault,427826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UH.Alarm.AlarmState,427826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UH.Alarm.GlobalReset,427826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UH.Alarm.FaultInAlarm,427826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UH.Alarm.ALRM,427826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UH.Alarm.ANUN,427826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UH.Alarm.AKED,427826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UH.Alarm.Resetable,427826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UH.Alarm.REST,427826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UH.Alarm.ACKN,427826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UH.Alarm.UACK,427826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UH.Alarm.MCmd_Enable,427826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UH.Alarm.MCmd_Disable,427826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UH.Alarm.OCmd_Shelve,427826.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UH.Alarm.OCmd_Unshelve,427826.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UH.Alarm.SCmd_Suppress,427826.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UH.Alarm.SCmd_UnSuppress,427827.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UH.Alarm.AEShelveTMRDN,427827.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UH.Alarm.Bad,427827.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UH.Alarm.Suppress,427828.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.UnSuppress,427828.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Shelve,427828.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.UnShelve,427828.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Enable,427828.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Disable,427828.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Ack,427828.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Reset,427828.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UH.Alarm.Suppressed,427828.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UH.Alarm.Shelved,427828.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UH.Alarm.Disabled,427828.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UH.Alarm.Acked,427828.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UH.Alarm.Alarm,427828.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Fault,427838.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UH.almPLCFault.AlarmState,427838.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UH.almPLCFault.GlobalReset,427838.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UH.almPLCFault.FaultInAlarm,427838.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UH.almPLCFault.ALRM,427838.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UH.almPLCFault.ANUN,427838.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UH.almPLCFault.AKED,427838.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UH.almPLCFault.Resetable,427838.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UH.almPLCFault.REST,427838.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UH.almPLCFault.ACKN,427838.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UH.almPLCFault.UACK,427838.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UH.almPLCFault.MCmd_Enable,427838.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UH.almPLCFault.MCmd_Disable,427838.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UH.almPLCFault.OCmd_Shelve,427838.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UH.almPLCFault.OCmd_Unshelve,427838.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UH.almPLCFault.SCmd_Suppress,427838.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UH.almPLCFault.SCmd_UnSuppress,427839.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UH.almPLCFault.AEShelveTMRDN,427839.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UH.almPLCFault.Bad,427839.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UH.almPLCFault.Suppress,427840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.UnSuppress,427840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Shelve,427840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.UnShelve,427840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Enable,427840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Disable,427840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Ack,427840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Reset,427840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Suppressed,427840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Shelved,427840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Disabled,427840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Acked,427840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UH.almPLCFault.Alarm,427840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Fault,427862.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UY.Alarm.AlarmState,427862.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UY.Alarm.GlobalReset,427862.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UY.Alarm.FaultInAlarm,427862.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UY.Alarm.ALRM,427862.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UY.Alarm.ANUN,427862.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UY.Alarm.AKED,427862.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UY.Alarm.Resetable,427862.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UY.Alarm.REST,427862.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UY.Alarm.ACKN,427862.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UY.Alarm.UACK,427862.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UY.Alarm.MCmd_Enable,427862.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UY.Alarm.MCmd_Disable,427862.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UY.Alarm.OCmd_Shelve,427862.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UY.Alarm.OCmd_Unshelve,427862.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UY.Alarm.SCmd_Suppress,427862.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UY.Alarm.SCmd_UnSuppress,427863.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UY.Alarm.AEShelveTMRDN,427863.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UY.Alarm.Bad,427863.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UY.Alarm.Suppress,427864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.UnSuppress,427864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Shelve,427864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.UnShelve,427864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Enable,427864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Disable,427864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Ack,427864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Reset,427864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UY.Alarm.Suppressed,427864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UY.Alarm.Shelved,427864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UY.Alarm.Disabled,427864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UY.Alarm.Acked,427864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UY.Alarm.Alarm,427864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Fault,427874.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_UY.almPLCFault.AlarmState,427874.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_UY.almPLCFault.GlobalReset,427874.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_UY.almPLCFault.FaultInAlarm,427874.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_UY.almPLCFault.ALRM,427874.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_UY.almPLCFault.ANUN,427874.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_UY.almPLCFault.AKED,427874.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_UY.almPLCFault.Resetable,427874.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_UY.almPLCFault.REST,427874.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_UY.almPLCFault.ACKN,427874.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_UY.almPLCFault.UACK,427874.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_UY.almPLCFault.MCmd_Enable,427874.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_UY.almPLCFault.MCmd_Disable,427874.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_UY.almPLCFault.OCmd_Shelve,427874.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_UY.almPLCFault.OCmd_Unshelve,427874.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_UY.almPLCFault.SCmd_Suppress,427874.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_UY.almPLCFault.SCmd_UnSuppress,427875.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_UY.almPLCFault.AEShelveTMRDN,427875.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_UY.almPLCFault.Bad,427875.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_UY.almPLCFault.Suppress,427876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.UnSuppress,427876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Shelve,427876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.UnShelve,427876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Enable,427876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Disable,427876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Ack,427876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Reset,427876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Suppressed,427876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Shelved,427876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Disabled,427876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Acked,427876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_UY.almPLCFault.Alarm,427876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Fault,427896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_XF.Alarm.AlarmState,427896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_XF.Alarm.GlobalReset,427896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_XF.Alarm.FaultInAlarm,427896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_XF.Alarm.ALRM,427896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_XF.Alarm.ANUN,427896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_XF.Alarm.AKED,427896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_XF.Alarm.Resetable,427896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_XF.Alarm.REST,427896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_XF.Alarm.ACKN,427896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_XF.Alarm.UACK,427896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_XF.Alarm.MCmd_Enable,427896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_XF.Alarm.MCmd_Disable,427896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_XF.Alarm.OCmd_Shelve,427896.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_XF.Alarm.OCmd_Unshelve,427896.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_XF.Alarm.SCmd_Suppress,427896.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_XF.Alarm.SCmd_UnSuppress,427897.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_XF.Alarm.AEShelveTMRDN,427897.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_XF.Alarm.Bad,427897.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_XF.Alarm.Suppress,427898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.UnSuppress,427898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Shelve,427898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.UnShelve,427898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Enable,427898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Disable,427898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Ack,427898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Reset,427898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_XF.Alarm.Suppressed,427898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_XF.Alarm.Shelved,427898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_XF.Alarm.Disabled,427898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_XF.Alarm.Acked,427898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_XF.Alarm.Alarm,427898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Fault,427908.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_XF.almPLCFault.AlarmState,427908.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_XF.almPLCFault.GlobalReset,427908.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_XF.almPLCFault.FaultInAlarm,427908.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_XF.almPLCFault.ALRM,427908.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_XF.almPLCFault.ANUN,427908.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_XF.almPLCFault.AKED,427908.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_XF.almPLCFault.Resetable,427908.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_XF.almPLCFault.REST,427908.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_XF.almPLCFault.ACKN,427908.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_XF.almPLCFault.UACK,427908.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_XF.almPLCFault.MCmd_Enable,427908.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_XF.almPLCFault.MCmd_Disable,427908.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_XF.almPLCFault.OCmd_Shelve,427908.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_XF.almPLCFault.OCmd_Unshelve,427908.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_XF.almPLCFault.SCmd_Suppress,427908.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_XF.almPLCFault.SCmd_UnSuppress,427909.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_XF.almPLCFault.AEShelveTMRDN,427909.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_XF.almPLCFault.Bad,427909.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_XF.almPLCFault.Suppress,427910.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.UnSuppress,427910.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Shelve,427910.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.UnShelve,427910.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Enable,427910.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Disable,427910.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Ack,427910.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Reset,427910.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Suppressed,427910.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Shelved,427910.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Disabled,427910.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Acked,427910.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_XF.almPLCFault.Alarm,427910.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Fault,427932.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_YA.Alarm.AlarmState,427932.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_YA.Alarm.GlobalReset,427932.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_YA.Alarm.FaultInAlarm,427932.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_YA.Alarm.ALRM,427932.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_YA.Alarm.ANUN,427932.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_YA.Alarm.AKED,427932.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_YA.Alarm.Resetable,427932.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_YA.Alarm.REST,427932.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_YA.Alarm.ACKN,427932.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_YA.Alarm.UACK,427932.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_YA.Alarm.MCmd_Enable,427932.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_YA.Alarm.MCmd_Disable,427932.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_YA.Alarm.OCmd_Shelve,427932.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_YA.Alarm.OCmd_Unshelve,427932.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_YA.Alarm.SCmd_Suppress,427932.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_YA.Alarm.SCmd_UnSuppress,427933.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_YA.Alarm.AEShelveTMRDN,427933.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_YA.Alarm.Bad,427933.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_YA.Alarm.Suppress,427934.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.UnSuppress,427934.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Shelve,427934.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.UnShelve,427934.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Enable,427934.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Disable,427934.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Ack,427934.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Reset,427934.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_YA.Alarm.Suppressed,427934.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_YA.Alarm.Shelved,427934.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_YA.Alarm.Disabled,427934.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_YA.Alarm.Acked,427934.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_YA.Alarm.Alarm,427934.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Fault,427944.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7_YA.almPLCFault.AlarmState,427944.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7_YA.almPLCFault.GlobalReset,427944.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7_YA.almPLCFault.FaultInAlarm,427944.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7_YA.almPLCFault.ALRM,427944.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7_YA.almPLCFault.ANUN,427944.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7_YA.almPLCFault.AKED,427944.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7_YA.almPLCFault.Resetable,427944.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7_YA.almPLCFault.REST,427944.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7_YA.almPLCFault.ACKN,427944.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7_YA.almPLCFault.UACK,427944.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7_YA.almPLCFault.MCmd_Enable,427944.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7_YA.almPLCFault.MCmd_Disable,427944.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7_YA.almPLCFault.OCmd_Shelve,427944.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7_YA.almPLCFault.OCmd_Unshelve,427944.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7_YA.almPLCFault.SCmd_Suppress,427944.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7_YA.almPLCFault.SCmd_UnSuppress,427945.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7_YA.almPLCFault.AEShelveTMRDN,427945.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7_YA.almPLCFault.Bad,427945.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7_YA.almPLCFault.Suppress,427946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.UnSuppress,427946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Shelve,427946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.UnShelve,427946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Enable,427946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Disable,427946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Ack,427946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Reset,427946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Suppressed,427946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Shelved,427946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Disabled,427946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Acked,427946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7_YA.almPLCFault.Alarm,427946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Fault,427966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_FA.Alarm.AlarmState,427966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_FA.Alarm.GlobalReset,427966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_FA.Alarm.FaultInAlarm,427966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_FA.Alarm.ALRM,427966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_FA.Alarm.ANUN,427966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_FA.Alarm.AKED,427966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_FA.Alarm.Resetable,427966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_FA.Alarm.REST,427966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_FA.Alarm.ACKN,427966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_FA.Alarm.UACK,427966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_FA.Alarm.MCmd_Enable,427966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_FA.Alarm.MCmd_Disable,427966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_FA.Alarm.OCmd_Shelve,427966.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_FA.Alarm.OCmd_Unshelve,427966.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_FA.Alarm.SCmd_Suppress,427966.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_FA.Alarm.SCmd_UnSuppress,427967.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_FA.Alarm.AEShelveTMRDN,427967.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_FA.Alarm.Bad,427967.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_FA.Alarm.Suppress,427968.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.UnSuppress,427968.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Shelve,427968.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.UnShelve,427968.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Enable,427968.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Disable,427968.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Ack,427968.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Reset,427968.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_FA.Alarm.Suppressed,427968.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_FA.Alarm.Shelved,427968.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_FA.Alarm.Disabled,427968.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_FA.Alarm.Acked,427968.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_FA.Alarm.Alarm,427968.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Fault,427978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_FA.almPLCFault.AlarmState,427978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_FA.almPLCFault.GlobalReset,427978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_FA.almPLCFault.FaultInAlarm,427978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_FA.almPLCFault.ALRM,427978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_FA.almPLCFault.ANUN,427978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_FA.almPLCFault.AKED,427978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_FA.almPLCFault.Resetable,427978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_FA.almPLCFault.REST,427978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_FA.almPLCFault.ACKN,427978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_FA.almPLCFault.UACK,427978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_FA.almPLCFault.MCmd_Enable,427978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_FA.almPLCFault.MCmd_Disable,427978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_FA.almPLCFault.OCmd_Shelve,427978.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_FA.almPLCFault.OCmd_Unshelve,427978.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_FA.almPLCFault.SCmd_Suppress,427978.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_FA.almPLCFault.SCmd_UnSuppress,427979.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_FA.almPLCFault.AEShelveTMRDN,427979.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_FA.almPLCFault.Bad,427979.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_FA.almPLCFault.Suppress,427980.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.UnSuppress,427980.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Shelve,427980.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.UnShelve,427980.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Enable,427980.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Disable,427980.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Ack,427980.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Reset,427980.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Suppressed,427980.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Shelved,427980.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Disabled,427980.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Acked,427980.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_FA.almPLCFault.Alarm,427980.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Fault,428002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_MF.Alarm.AlarmState,428002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_MF.Alarm.GlobalReset,428002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_MF.Alarm.FaultInAlarm,428002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MF.Alarm.ALRM,428002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_MF.Alarm.ANUN,428002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_MF.Alarm.AKED,428002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_MF.Alarm.Resetable,428002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_MF.Alarm.REST,428002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_MF.Alarm.ACKN,428002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_MF.Alarm.UACK,428002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_MF.Alarm.MCmd_Enable,428002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MF.Alarm.MCmd_Disable,428002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MF.Alarm.OCmd_Shelve,428002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_MF.Alarm.OCmd_Unshelve,428002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_MF.Alarm.SCmd_Suppress,428002.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_MF.Alarm.SCmd_UnSuppress,428003.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_MF.Alarm.AEShelveTMRDN,428003.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_MF.Alarm.Bad,428003.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_MF.Alarm.Suppress,428004.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.UnSuppress,428004.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Shelve,428004.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.UnShelve,428004.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Enable,428004.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Disable,428004.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Ack,428004.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Reset,428004.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_MF.Alarm.Suppressed,428004.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_MF.Alarm.Shelved,428004.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_MF.Alarm.Disabled,428004.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_MF.Alarm.Acked,428004.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_MF.Alarm.Alarm,428004.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Fault,428014.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_MF.almPLCFault.AlarmState,428014.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_MF.almPLCFault.GlobalReset,428014.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_MF.almPLCFault.FaultInAlarm,428014.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MF.almPLCFault.ALRM,428014.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_MF.almPLCFault.ANUN,428014.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_MF.almPLCFault.AKED,428014.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_MF.almPLCFault.Resetable,428014.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_MF.almPLCFault.REST,428014.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_MF.almPLCFault.ACKN,428014.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_MF.almPLCFault.UACK,428014.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_MF.almPLCFault.MCmd_Enable,428014.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MF.almPLCFault.MCmd_Disable,428014.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MF.almPLCFault.OCmd_Shelve,428014.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_MF.almPLCFault.OCmd_Unshelve,428014.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_MF.almPLCFault.SCmd_Suppress,428014.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_MF.almPLCFault.SCmd_UnSuppress,428015.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_MF.almPLCFault.AEShelveTMRDN,428015.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_MF.almPLCFault.Bad,428015.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_MF.almPLCFault.Suppress,428016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.UnSuppress,428016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Shelve,428016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.UnShelve,428016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Enable,428016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Disable,428016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Ack,428016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Reset,428016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Suppressed,428016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Shelved,428016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Disabled,428016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Acked,428016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_MF.almPLCFault.Alarm,428016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Fault,428036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_MY.Alarm.AlarmState,428036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_MY.Alarm.GlobalReset,428036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_MY.Alarm.FaultInAlarm,428036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MY.Alarm.ALRM,428036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_MY.Alarm.ANUN,428036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_MY.Alarm.AKED,428036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_MY.Alarm.Resetable,428036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_MY.Alarm.REST,428036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_MY.Alarm.ACKN,428036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_MY.Alarm.UACK,428036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_MY.Alarm.MCmd_Enable,428036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MY.Alarm.MCmd_Disable,428036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MY.Alarm.OCmd_Shelve,428036.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_MY.Alarm.OCmd_Unshelve,428036.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_MY.Alarm.SCmd_Suppress,428036.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_MY.Alarm.SCmd_UnSuppress,428037.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_MY.Alarm.AEShelveTMRDN,428037.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_MY.Alarm.Bad,428037.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_MY.Alarm.Suppress,428038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.UnSuppress,428038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Shelve,428038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.UnShelve,428038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Enable,428038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Disable,428038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Ack,428038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Reset,428038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_MY.Alarm.Suppressed,428038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_MY.Alarm.Shelved,428038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_MY.Alarm.Disabled,428038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_MY.Alarm.Acked,428038.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_MY.Alarm.Alarm,428038.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Fault,428048.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_MY.almPLCFault.AlarmState,428048.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_MY.almPLCFault.GlobalReset,428048.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_MY.almPLCFault.FaultInAlarm,428048.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_MY.almPLCFault.ALRM,428048.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_MY.almPLCFault.ANUN,428048.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_MY.almPLCFault.AKED,428048.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_MY.almPLCFault.Resetable,428048.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_MY.almPLCFault.REST,428048.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_MY.almPLCFault.ACKN,428048.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_MY.almPLCFault.UACK,428048.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_MY.almPLCFault.MCmd_Enable,428048.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_MY.almPLCFault.MCmd_Disable,428048.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_MY.almPLCFault.OCmd_Shelve,428048.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_MY.almPLCFault.OCmd_Unshelve,428048.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_MY.almPLCFault.SCmd_Suppress,428048.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_MY.almPLCFault.SCmd_UnSuppress,428049.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_MY.almPLCFault.AEShelveTMRDN,428049.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_MY.almPLCFault.Bad,428049.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_MY.almPLCFault.Suppress,428050.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.UnSuppress,428050.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Shelve,428050.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.UnShelve,428050.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Enable,428050.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Disable,428050.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Ack,428050.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Reset,428050.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Suppressed,428050.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Shelved,428050.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Disabled,428050.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Acked,428050.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_MY.almPLCFault.Alarm,428050.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Fault,428072.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UA.Alarm.AlarmState,428072.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UA.Alarm.GlobalReset,428072.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UA.Alarm.FaultInAlarm,428072.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UA.Alarm.ALRM,428072.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UA.Alarm.ANUN,428072.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UA.Alarm.AKED,428072.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UA.Alarm.Resetable,428072.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UA.Alarm.REST,428072.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UA.Alarm.ACKN,428072.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UA.Alarm.UACK,428072.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UA.Alarm.MCmd_Enable,428072.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UA.Alarm.MCmd_Disable,428072.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UA.Alarm.OCmd_Shelve,428072.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UA.Alarm.OCmd_Unshelve,428072.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UA.Alarm.SCmd_Suppress,428072.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UA.Alarm.SCmd_UnSuppress,428073.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UA.Alarm.AEShelveTMRDN,428073.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UA.Alarm.Bad,428073.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UA.Alarm.Suppress,428074.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.UnSuppress,428074.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Shelve,428074.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.UnShelve,428074.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Enable,428074.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Disable,428074.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Ack,428074.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Reset,428074.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UA.Alarm.Suppressed,428074.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UA.Alarm.Shelved,428074.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UA.Alarm.Disabled,428074.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UA.Alarm.Acked,428074.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UA.Alarm.Alarm,428074.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Fault,428084.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UA.almPLCFault.AlarmState,428084.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UA.almPLCFault.GlobalReset,428084.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UA.almPLCFault.FaultInAlarm,428084.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UA.almPLCFault.ALRM,428084.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UA.almPLCFault.ANUN,428084.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UA.almPLCFault.AKED,428084.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UA.almPLCFault.Resetable,428084.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UA.almPLCFault.REST,428084.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UA.almPLCFault.ACKN,428084.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UA.almPLCFault.UACK,428084.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UA.almPLCFault.MCmd_Enable,428084.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UA.almPLCFault.MCmd_Disable,428084.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UA.almPLCFault.OCmd_Shelve,428084.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UA.almPLCFault.OCmd_Unshelve,428084.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UA.almPLCFault.SCmd_Suppress,428084.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UA.almPLCFault.SCmd_UnSuppress,428085.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UA.almPLCFault.AEShelveTMRDN,428085.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UA.almPLCFault.Bad,428085.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UA.almPLCFault.Suppress,428086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.UnSuppress,428086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Shelve,428086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.UnShelve,428086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Enable,428086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Disable,428086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Ack,428086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Reset,428086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Suppressed,428086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Shelved,428086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Disabled,428086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Acked,428086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UA.almPLCFault.Alarm,428086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Fault,428106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UH.Alarm.AlarmState,428106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UH.Alarm.GlobalReset,428106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UH.Alarm.FaultInAlarm,428106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UH.Alarm.ALRM,428106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UH.Alarm.ANUN,428106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UH.Alarm.AKED,428106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UH.Alarm.Resetable,428106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UH.Alarm.REST,428106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UH.Alarm.ACKN,428106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UH.Alarm.UACK,428106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UH.Alarm.MCmd_Enable,428106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UH.Alarm.MCmd_Disable,428106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UH.Alarm.OCmd_Shelve,428106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UH.Alarm.OCmd_Unshelve,428106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UH.Alarm.SCmd_Suppress,428106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UH.Alarm.SCmd_UnSuppress,428107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UH.Alarm.AEShelveTMRDN,428107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UH.Alarm.Bad,428107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UH.Alarm.Suppress,428108.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.UnSuppress,428108.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Shelve,428108.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.UnShelve,428108.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Enable,428108.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Disable,428108.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Ack,428108.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Reset,428108.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UH.Alarm.Suppressed,428108.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UH.Alarm.Shelved,428108.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UH.Alarm.Disabled,428108.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UH.Alarm.Acked,428108.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UH.Alarm.Alarm,428108.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Fault,428118.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UH.almPLCFault.AlarmState,428118.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UH.almPLCFault.GlobalReset,428118.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UH.almPLCFault.FaultInAlarm,428118.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UH.almPLCFault.ALRM,428118.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UH.almPLCFault.ANUN,428118.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UH.almPLCFault.AKED,428118.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UH.almPLCFault.Resetable,428118.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UH.almPLCFault.REST,428118.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UH.almPLCFault.ACKN,428118.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UH.almPLCFault.UACK,428118.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UH.almPLCFault.MCmd_Enable,428118.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UH.almPLCFault.MCmd_Disable,428118.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UH.almPLCFault.OCmd_Shelve,428118.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UH.almPLCFault.OCmd_Unshelve,428118.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UH.almPLCFault.SCmd_Suppress,428118.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UH.almPLCFault.SCmd_UnSuppress,428119.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UH.almPLCFault.AEShelveTMRDN,428119.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UH.almPLCFault.Bad,428119.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UH.almPLCFault.Suppress,428120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.UnSuppress,428120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Shelve,428120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.UnShelve,428120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Enable,428120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Disable,428120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Ack,428120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Reset,428120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Suppressed,428120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Shelved,428120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Disabled,428120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Acked,428120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UH.almPLCFault.Alarm,428120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Fault,428142.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UY.Alarm.AlarmState,428142.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UY.Alarm.GlobalReset,428142.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UY.Alarm.FaultInAlarm,428142.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UY.Alarm.ALRM,428142.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UY.Alarm.ANUN,428142.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UY.Alarm.AKED,428142.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UY.Alarm.Resetable,428142.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UY.Alarm.REST,428142.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UY.Alarm.ACKN,428142.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UY.Alarm.UACK,428142.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UY.Alarm.MCmd_Enable,428142.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UY.Alarm.MCmd_Disable,428142.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UY.Alarm.OCmd_Shelve,428142.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UY.Alarm.OCmd_Unshelve,428142.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UY.Alarm.SCmd_Suppress,428142.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UY.Alarm.SCmd_UnSuppress,428143.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UY.Alarm.AEShelveTMRDN,428143.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UY.Alarm.Bad,428143.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UY.Alarm.Suppress,428144.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.UnSuppress,428144.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Shelve,428144.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.UnShelve,428144.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Enable,428144.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Disable,428144.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Ack,428144.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Reset,428144.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UY.Alarm.Suppressed,428144.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UY.Alarm.Shelved,428144.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UY.Alarm.Disabled,428144.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UY.Alarm.Acked,428144.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UY.Alarm.Alarm,428144.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Fault,428154.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_UY.almPLCFault.AlarmState,428154.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_UY.almPLCFault.GlobalReset,428154.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_UY.almPLCFault.FaultInAlarm,428154.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_UY.almPLCFault.ALRM,428154.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_UY.almPLCFault.ANUN,428154.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_UY.almPLCFault.AKED,428154.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_UY.almPLCFault.Resetable,428154.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_UY.almPLCFault.REST,428154.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_UY.almPLCFault.ACKN,428154.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_UY.almPLCFault.UACK,428154.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_UY.almPLCFault.MCmd_Enable,428154.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_UY.almPLCFault.MCmd_Disable,428154.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_UY.almPLCFault.OCmd_Shelve,428154.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_UY.almPLCFault.OCmd_Unshelve,428154.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_UY.almPLCFault.SCmd_Suppress,428154.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_UY.almPLCFault.SCmd_UnSuppress,428155.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_UY.almPLCFault.AEShelveTMRDN,428155.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_UY.almPLCFault.Bad,428155.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_UY.almPLCFault.Suppress,428156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.UnSuppress,428156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Shelve,428156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.UnShelve,428156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Enable,428156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Disable,428156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Ack,428156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Reset,428156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Suppressed,428156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Shelved,428156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Disabled,428156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Acked,428156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_UY.almPLCFault.Alarm,428156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Fault,428176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_XF.Alarm.AlarmState,428176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_XF.Alarm.GlobalReset,428176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_XF.Alarm.FaultInAlarm,428176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_XF.Alarm.ALRM,428176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_XF.Alarm.ANUN,428176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_XF.Alarm.AKED,428176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_XF.Alarm.Resetable,428176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_XF.Alarm.REST,428176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_XF.Alarm.ACKN,428176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_XF.Alarm.UACK,428176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_XF.Alarm.MCmd_Enable,428176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_XF.Alarm.MCmd_Disable,428176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_XF.Alarm.OCmd_Shelve,428176.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_XF.Alarm.OCmd_Unshelve,428176.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_XF.Alarm.SCmd_Suppress,428176.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_XF.Alarm.SCmd_UnSuppress,428177.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_XF.Alarm.AEShelveTMRDN,428177.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_XF.Alarm.Bad,428177.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_XF.Alarm.Suppress,428178.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.UnSuppress,428178.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Shelve,428178.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.UnShelve,428178.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Enable,428178.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Disable,428178.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Ack,428178.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Reset,428178.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_XF.Alarm.Suppressed,428178.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_XF.Alarm.Shelved,428178.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_XF.Alarm.Disabled,428178.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_XF.Alarm.Acked,428178.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_XF.Alarm.Alarm,428178.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Fault,428188.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_XF.almPLCFault.AlarmState,428188.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_XF.almPLCFault.GlobalReset,428188.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_XF.almPLCFault.FaultInAlarm,428188.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_XF.almPLCFault.ALRM,428188.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_XF.almPLCFault.ANUN,428188.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_XF.almPLCFault.AKED,428188.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_XF.almPLCFault.Resetable,428188.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_XF.almPLCFault.REST,428188.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_XF.almPLCFault.ACKN,428188.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_XF.almPLCFault.UACK,428188.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_XF.almPLCFault.MCmd_Enable,428188.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_XF.almPLCFault.MCmd_Disable,428188.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_XF.almPLCFault.OCmd_Shelve,428188.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_XF.almPLCFault.OCmd_Unshelve,428188.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_XF.almPLCFault.SCmd_Suppress,428188.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_XF.almPLCFault.SCmd_UnSuppress,428189.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_XF.almPLCFault.AEShelveTMRDN,428189.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_XF.almPLCFault.Bad,428189.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_XF.almPLCFault.Suppress,428190.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.UnSuppress,428190.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Shelve,428190.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.UnShelve,428190.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Enable,428190.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Disable,428190.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Ack,428190.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Reset,428190.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Suppressed,428190.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Shelved,428190.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Disabled,428190.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Acked,428190.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_XF.almPLCFault.Alarm,428190.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Fault,428212.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_YA.Alarm.AlarmState,428212.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_YA.Alarm.GlobalReset,428212.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_YA.Alarm.FaultInAlarm,428212.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_YA.Alarm.ALRM,428212.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_YA.Alarm.ANUN,428212.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_YA.Alarm.AKED,428212.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_YA.Alarm.Resetable,428212.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_YA.Alarm.REST,428212.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_YA.Alarm.ACKN,428212.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_YA.Alarm.UACK,428212.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_YA.Alarm.MCmd_Enable,428212.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_YA.Alarm.MCmd_Disable,428212.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_YA.Alarm.OCmd_Shelve,428212.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_YA.Alarm.OCmd_Unshelve,428212.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_YA.Alarm.SCmd_Suppress,428212.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_YA.Alarm.SCmd_UnSuppress,428213.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_YA.Alarm.AEShelveTMRDN,428213.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_YA.Alarm.Bad,428213.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_YA.Alarm.Suppress,428214.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.UnSuppress,428214.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Shelve,428214.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.UnShelve,428214.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Enable,428214.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Disable,428214.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Ack,428214.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Reset,428214.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_YA.Alarm.Suppressed,428214.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_YA.Alarm.Shelved,428214.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_YA.Alarm.Disabled,428214.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_YA.Alarm.Acked,428214.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_YA.Alarm.Alarm,428214.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Fault,428224.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8_YA.almPLCFault.AlarmState,428224.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8_YA.almPLCFault.GlobalReset,428224.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8_YA.almPLCFault.FaultInAlarm,428224.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8_YA.almPLCFault.ALRM,428224.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8_YA.almPLCFault.ANUN,428224.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8_YA.almPLCFault.AKED,428224.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8_YA.almPLCFault.Resetable,428224.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8_YA.almPLCFault.REST,428224.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8_YA.almPLCFault.ACKN,428224.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8_YA.almPLCFault.UACK,428224.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8_YA.almPLCFault.MCmd_Enable,428224.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8_YA.almPLCFault.MCmd_Disable,428224.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8_YA.almPLCFault.OCmd_Shelve,428224.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8_YA.almPLCFault.OCmd_Unshelve,428224.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8_YA.almPLCFault.SCmd_Suppress,428224.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8_YA.almPLCFault.SCmd_UnSuppress,428225.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8_YA.almPLCFault.AEShelveTMRDN,428225.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8_YA.almPLCFault.Bad,428225.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8_YA.almPLCFault.Suppress,428226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.UnSuppress,428226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Shelve,428226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.UnShelve,428226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Enable,428226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Disable,428226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Ack,428226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Reset,428226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Suppressed,428226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Shelved,428226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Disabled,428226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Acked,428226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8_YA.almPLCFault.Alarm,428226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Fault,428246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_FA.Alarm.AlarmState,428246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_FA.Alarm.GlobalReset,428246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_FA.Alarm.FaultInAlarm,428246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_FA.Alarm.ALRM,428246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_FA.Alarm.ANUN,428246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_FA.Alarm.AKED,428246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_FA.Alarm.Resetable,428246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_FA.Alarm.REST,428246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_FA.Alarm.ACKN,428246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_FA.Alarm.UACK,428246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_FA.Alarm.MCmd_Enable,428246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_FA.Alarm.MCmd_Disable,428246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_FA.Alarm.OCmd_Shelve,428246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_FA.Alarm.OCmd_Unshelve,428246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_FA.Alarm.SCmd_Suppress,428246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_FA.Alarm.SCmd_UnSuppress,428247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_FA.Alarm.AEShelveTMRDN,428247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_FA.Alarm.Bad,428247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_FA.Alarm.Suppress,428248.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.UnSuppress,428248.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Shelve,428248.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.UnShelve,428248.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Enable,428248.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Disable,428248.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Ack,428248.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Reset,428248.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_FA.Alarm.Suppressed,428248.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_FA.Alarm.Shelved,428248.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_FA.Alarm.Disabled,428248.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_FA.Alarm.Acked,428248.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_FA.Alarm.Alarm,428248.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Fault,428258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_FA.almPLCFault.AlarmState,428258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_FA.almPLCFault.GlobalReset,428258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_FA.almPLCFault.FaultInAlarm,428258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_FA.almPLCFault.ALRM,428258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_FA.almPLCFault.ANUN,428258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_FA.almPLCFault.AKED,428258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_FA.almPLCFault.Resetable,428258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_FA.almPLCFault.REST,428258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_FA.almPLCFault.ACKN,428258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_FA.almPLCFault.UACK,428258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_FA.almPLCFault.MCmd_Enable,428258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_FA.almPLCFault.MCmd_Disable,428258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_FA.almPLCFault.OCmd_Shelve,428258.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_FA.almPLCFault.OCmd_Unshelve,428258.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_FA.almPLCFault.SCmd_Suppress,428258.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_FA.almPLCFault.SCmd_UnSuppress,428259.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_FA.almPLCFault.AEShelveTMRDN,428259.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_FA.almPLCFault.Bad,428259.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_FA.almPLCFault.Suppress,428260.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.UnSuppress,428260.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Shelve,428260.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.UnShelve,428260.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Enable,428260.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Disable,428260.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Ack,428260.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Reset,428260.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Suppressed,428260.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Shelved,428260.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Disabled,428260.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Acked,428260.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_FA.almPLCFault.Alarm,428260.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Fault,428282.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_MF.Alarm.AlarmState,428282.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_MF.Alarm.GlobalReset,428282.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_MF.Alarm.FaultInAlarm,428282.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MF.Alarm.ALRM,428282.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_MF.Alarm.ANUN,428282.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_MF.Alarm.AKED,428282.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_MF.Alarm.Resetable,428282.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_MF.Alarm.REST,428282.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_MF.Alarm.ACKN,428282.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_MF.Alarm.UACK,428282.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_MF.Alarm.MCmd_Enable,428282.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MF.Alarm.MCmd_Disable,428282.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MF.Alarm.OCmd_Shelve,428282.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_MF.Alarm.OCmd_Unshelve,428282.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_MF.Alarm.SCmd_Suppress,428282.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_MF.Alarm.SCmd_UnSuppress,428283.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_MF.Alarm.AEShelveTMRDN,428283.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_MF.Alarm.Bad,428283.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_MF.Alarm.Suppress,428284.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.UnSuppress,428284.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Shelve,428284.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.UnShelve,428284.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Enable,428284.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Disable,428284.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Ack,428284.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Reset,428284.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_MF.Alarm.Suppressed,428284.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_MF.Alarm.Shelved,428284.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_MF.Alarm.Disabled,428284.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_MF.Alarm.Acked,428284.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_MF.Alarm.Alarm,428284.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Fault,428294.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_MF.almPLCFault.AlarmState,428294.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_MF.almPLCFault.GlobalReset,428294.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_MF.almPLCFault.FaultInAlarm,428294.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MF.almPLCFault.ALRM,428294.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_MF.almPLCFault.ANUN,428294.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_MF.almPLCFault.AKED,428294.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_MF.almPLCFault.Resetable,428294.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_MF.almPLCFault.REST,428294.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_MF.almPLCFault.ACKN,428294.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_MF.almPLCFault.UACK,428294.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_MF.almPLCFault.MCmd_Enable,428294.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MF.almPLCFault.MCmd_Disable,428294.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MF.almPLCFault.OCmd_Shelve,428294.13,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_MF.almPLCFault.OCmd_Unshelve,428294.14,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_MF.almPLCFault.SCmd_Suppress,428294.15,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_MF.almPLCFault.SCmd_UnSuppress,428295.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_MF.almPLCFault.AEShelveTMRDN,428295.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_MF.almPLCFault.Bad,428295.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_MF.almPLCFault.Suppress,428296.00,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.UnSuppress,428296.01,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Shelve,428296.02,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.UnShelve,428296.03,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Enable,428296.04,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Disable,428296.05,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Ack,428296.06,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Reset,428296.07,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Suppressed,428296.08,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Shelved,428296.09,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Disabled,428296.10,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Acked,428296.11,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_MF.almPLCFault.Alarm,428296.12,Boolean,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Fault,428316.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_MY.Alarm.AlarmState,428316.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_MY.Alarm.GlobalReset,428316.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_MY.Alarm.FaultInAlarm,428316.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MY.Alarm.ALRM,428316.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_MY.Alarm.ANUN,428316.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_MY.Alarm.AKED,428316.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_MY.Alarm.Resetable,428316.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_MY.Alarm.REST,428316.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_MY.Alarm.ACKN,428316.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_MY.Alarm.UACK,428316.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_MY.Alarm.MCmd_Enable,428316.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MY.Alarm.MCmd_Disable,428316.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MY.Alarm.OCmd_Shelve,428316.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_MY.Alarm.OCmd_Unshelve,428316.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_MY.Alarm.SCmd_Suppress,428316.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_MY.Alarm.SCmd_UnSuppress,428317.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_MY.Alarm.AEShelveTMRDN,428317.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_MY.Alarm.Bad,428317.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_MY.Alarm.Suppress,428318.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.UnSuppress,428318.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Shelve,428318.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.UnShelve,428318.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Enable,428318.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Disable,428318.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Ack,428318.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Reset,428318.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_MY.Alarm.Suppressed,428318.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_MY.Alarm.Shelved,428318.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_MY.Alarm.Disabled,428318.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_MY.Alarm.Acked,428318.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_MY.Alarm.Alarm,428318.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Fault,428328.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_MY.almPLCFault.AlarmState,428328.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_MY.almPLCFault.GlobalReset,428328.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_MY.almPLCFault.FaultInAlarm,428328.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_MY.almPLCFault.ALRM,428328.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_MY.almPLCFault.ANUN,428328.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_MY.almPLCFault.AKED,428328.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_MY.almPLCFault.Resetable,428328.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_MY.almPLCFault.REST,428328.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_MY.almPLCFault.ACKN,428328.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_MY.almPLCFault.UACK,428328.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_MY.almPLCFault.MCmd_Enable,428328.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_MY.almPLCFault.MCmd_Disable,428328.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_MY.almPLCFault.OCmd_Shelve,428328.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_MY.almPLCFault.OCmd_Unshelve,428328.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_MY.almPLCFault.SCmd_Suppress,428328.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_MY.almPLCFault.SCmd_UnSuppress,428329.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_MY.almPLCFault.AEShelveTMRDN,428329.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_MY.almPLCFault.Bad,428329.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_MY.almPLCFault.Suppress,428330.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.UnSuppress,428330.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Shelve,428330.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.UnShelve,428330.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Enable,428330.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Disable,428330.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Ack,428330.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Reset,428330.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Suppressed,428330.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Shelved,428330.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Disabled,428330.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Acked,428330.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_MY.almPLCFault.Alarm,428330.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Fault,428352.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UA.Alarm.AlarmState,428352.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UA.Alarm.GlobalReset,428352.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UA.Alarm.FaultInAlarm,428352.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UA.Alarm.ALRM,428352.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UA.Alarm.ANUN,428352.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UA.Alarm.AKED,428352.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UA.Alarm.Resetable,428352.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UA.Alarm.REST,428352.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UA.Alarm.ACKN,428352.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UA.Alarm.UACK,428352.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UA.Alarm.MCmd_Enable,428352.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UA.Alarm.MCmd_Disable,428352.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UA.Alarm.OCmd_Shelve,428352.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UA.Alarm.OCmd_Unshelve,428352.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UA.Alarm.SCmd_Suppress,428352.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UA.Alarm.SCmd_UnSuppress,428353.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UA.Alarm.AEShelveTMRDN,428353.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UA.Alarm.Bad,428353.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UA.Alarm.Suppress,428354.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.UnSuppress,428354.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Shelve,428354.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.UnShelve,428354.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Enable,428354.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Disable,428354.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Ack,428354.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Reset,428354.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UA.Alarm.Suppressed,428354.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UA.Alarm.Shelved,428354.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UA.Alarm.Disabled,428354.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UA.Alarm.Acked,428354.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UA.Alarm.Alarm,428354.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Fault,428364.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UA.almPLCFault.AlarmState,428364.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UA.almPLCFault.GlobalReset,428364.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UA.almPLCFault.FaultInAlarm,428364.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UA.almPLCFault.ALRM,428364.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UA.almPLCFault.ANUN,428364.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UA.almPLCFault.AKED,428364.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UA.almPLCFault.Resetable,428364.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UA.almPLCFault.REST,428364.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UA.almPLCFault.ACKN,428364.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UA.almPLCFault.UACK,428364.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UA.almPLCFault.MCmd_Enable,428364.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UA.almPLCFault.MCmd_Disable,428364.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UA.almPLCFault.OCmd_Shelve,428364.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UA.almPLCFault.OCmd_Unshelve,428364.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UA.almPLCFault.SCmd_Suppress,428364.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UA.almPLCFault.SCmd_UnSuppress,428365.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UA.almPLCFault.AEShelveTMRDN,428365.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UA.almPLCFault.Bad,428365.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UA.almPLCFault.Suppress,428366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.UnSuppress,428366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Shelve,428366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.UnShelve,428366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Enable,428366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Disable,428366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Ack,428366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Reset,428366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Suppressed,428366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Shelved,428366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Disabled,428366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Acked,428366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UA.almPLCFault.Alarm,428366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Fault,428386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UH.Alarm.AlarmState,428386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UH.Alarm.GlobalReset,428386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UH.Alarm.FaultInAlarm,428386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UH.Alarm.ALRM,428386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UH.Alarm.ANUN,428386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UH.Alarm.AKED,428386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UH.Alarm.Resetable,428386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UH.Alarm.REST,428386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UH.Alarm.ACKN,428386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UH.Alarm.UACK,428386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UH.Alarm.MCmd_Enable,428386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UH.Alarm.MCmd_Disable,428386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UH.Alarm.OCmd_Shelve,428386.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UH.Alarm.OCmd_Unshelve,428386.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UH.Alarm.SCmd_Suppress,428386.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UH.Alarm.SCmd_UnSuppress,428387.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UH.Alarm.AEShelveTMRDN,428387.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UH.Alarm.Bad,428387.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UH.Alarm.Suppress,428388.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.UnSuppress,428388.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Shelve,428388.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.UnShelve,428388.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Enable,428388.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Disable,428388.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Ack,428388.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Reset,428388.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UH.Alarm.Suppressed,428388.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UH.Alarm.Shelved,428388.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UH.Alarm.Disabled,428388.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UH.Alarm.Acked,428388.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UH.Alarm.Alarm,428388.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Fault,428398.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UH.almPLCFault.AlarmState,428398.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UH.almPLCFault.GlobalReset,428398.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UH.almPLCFault.FaultInAlarm,428398.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UH.almPLCFault.ALRM,428398.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UH.almPLCFault.ANUN,428398.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UH.almPLCFault.AKED,428398.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UH.almPLCFault.Resetable,428398.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UH.almPLCFault.REST,428398.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UH.almPLCFault.ACKN,428398.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UH.almPLCFault.UACK,428398.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UH.almPLCFault.MCmd_Enable,428398.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UH.almPLCFault.MCmd_Disable,428398.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UH.almPLCFault.OCmd_Shelve,428398.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UH.almPLCFault.OCmd_Unshelve,428398.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UH.almPLCFault.SCmd_Suppress,428398.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UH.almPLCFault.SCmd_UnSuppress,428399.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UH.almPLCFault.AEShelveTMRDN,428399.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UH.almPLCFault.Bad,428399.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UH.almPLCFault.Suppress,428400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.UnSuppress,428400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Shelve,428400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.UnShelve,428400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Enable,428400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Disable,428400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Ack,428400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Reset,428400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Suppressed,428400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Shelved,428400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Disabled,428400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Acked,428400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UH.almPLCFault.Alarm,428400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Fault,428422.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UY.Alarm.AlarmState,428422.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UY.Alarm.GlobalReset,428422.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UY.Alarm.FaultInAlarm,428422.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UY.Alarm.ALRM,428422.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UY.Alarm.ANUN,428422.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UY.Alarm.AKED,428422.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UY.Alarm.Resetable,428422.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UY.Alarm.REST,428422.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UY.Alarm.ACKN,428422.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UY.Alarm.UACK,428422.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UY.Alarm.MCmd_Enable,428422.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UY.Alarm.MCmd_Disable,428422.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UY.Alarm.OCmd_Shelve,428422.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UY.Alarm.OCmd_Unshelve,428422.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UY.Alarm.SCmd_Suppress,428422.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UY.Alarm.SCmd_UnSuppress,428423.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UY.Alarm.AEShelveTMRDN,428423.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UY.Alarm.Bad,428423.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UY.Alarm.Suppress,428424.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.UnSuppress,428424.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Shelve,428424.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.UnShelve,428424.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Enable,428424.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Disable,428424.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Ack,428424.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Reset,428424.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UY.Alarm.Suppressed,428424.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UY.Alarm.Shelved,428424.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UY.Alarm.Disabled,428424.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UY.Alarm.Acked,428424.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UY.Alarm.Alarm,428424.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Fault,428434.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_UY.almPLCFault.AlarmState,428434.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_UY.almPLCFault.GlobalReset,428434.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_UY.almPLCFault.FaultInAlarm,428434.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_UY.almPLCFault.ALRM,428434.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_UY.almPLCFault.ANUN,428434.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_UY.almPLCFault.AKED,428434.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_UY.almPLCFault.Resetable,428434.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_UY.almPLCFault.REST,428434.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_UY.almPLCFault.ACKN,428434.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_UY.almPLCFault.UACK,428434.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_UY.almPLCFault.MCmd_Enable,428434.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_UY.almPLCFault.MCmd_Disable,428434.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_UY.almPLCFault.OCmd_Shelve,428434.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_UY.almPLCFault.OCmd_Unshelve,428434.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_UY.almPLCFault.SCmd_Suppress,428434.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_UY.almPLCFault.SCmd_UnSuppress,428435.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_UY.almPLCFault.AEShelveTMRDN,428435.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_UY.almPLCFault.Bad,428435.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_UY.almPLCFault.Suppress,428436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.UnSuppress,428436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Shelve,428436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.UnShelve,428436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Enable,428436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Disable,428436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Ack,428436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Reset,428436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Suppressed,428436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Shelved,428436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Disabled,428436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Acked,428436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_UY.almPLCFault.Alarm,428436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Fault,428456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_XF.Alarm.AlarmState,428456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_XF.Alarm.GlobalReset,428456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_XF.Alarm.FaultInAlarm,428456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_XF.Alarm.ALRM,428456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_XF.Alarm.ANUN,428456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_XF.Alarm.AKED,428456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_XF.Alarm.Resetable,428456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_XF.Alarm.REST,428456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_XF.Alarm.ACKN,428456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_XF.Alarm.UACK,428456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_XF.Alarm.MCmd_Enable,428456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_XF.Alarm.MCmd_Disable,428456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_XF.Alarm.OCmd_Shelve,428456.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_XF.Alarm.OCmd_Unshelve,428456.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_XF.Alarm.SCmd_Suppress,428456.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_XF.Alarm.SCmd_UnSuppress,428457.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_XF.Alarm.AEShelveTMRDN,428457.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_XF.Alarm.Bad,428457.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_XF.Alarm.Suppress,428458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.UnSuppress,428458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Shelve,428458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.UnShelve,428458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Enable,428458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Disable,428458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Ack,428458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Reset,428458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_XF.Alarm.Suppressed,428458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_XF.Alarm.Shelved,428458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_XF.Alarm.Disabled,428458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_XF.Alarm.Acked,428458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_XF.Alarm.Alarm,428458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Fault,428468.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_XF.almPLCFault.AlarmState,428468.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_XF.almPLCFault.GlobalReset,428468.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_XF.almPLCFault.FaultInAlarm,428468.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_XF.almPLCFault.ALRM,428468.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_XF.almPLCFault.ANUN,428468.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_XF.almPLCFault.AKED,428468.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_XF.almPLCFault.Resetable,428468.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_XF.almPLCFault.REST,428468.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_XF.almPLCFault.ACKN,428468.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_XF.almPLCFault.UACK,428468.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_XF.almPLCFault.MCmd_Enable,428468.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_XF.almPLCFault.MCmd_Disable,428468.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_XF.almPLCFault.OCmd_Shelve,428468.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_XF.almPLCFault.OCmd_Unshelve,428468.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_XF.almPLCFault.SCmd_Suppress,428468.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_XF.almPLCFault.SCmd_UnSuppress,428469.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_XF.almPLCFault.AEShelveTMRDN,428469.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_XF.almPLCFault.Bad,428469.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_XF.almPLCFault.Suppress,428470.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.UnSuppress,428470.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Shelve,428470.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.UnShelve,428470.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Enable,428470.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Disable,428470.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Ack,428470.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Reset,428470.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Suppressed,428470.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Shelved,428470.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Disabled,428470.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Acked,428470.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_XF.almPLCFault.Alarm,428470.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Fault,428492.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_YA.Alarm.AlarmState,428492.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_YA.Alarm.GlobalReset,428492.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_YA.Alarm.FaultInAlarm,428492.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_YA.Alarm.ALRM,428492.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_YA.Alarm.ANUN,428492.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_YA.Alarm.AKED,428492.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_YA.Alarm.Resetable,428492.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_YA.Alarm.REST,428492.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_YA.Alarm.ACKN,428492.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_YA.Alarm.UACK,428492.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_YA.Alarm.MCmd_Enable,428492.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_YA.Alarm.MCmd_Disable,428492.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_YA.Alarm.OCmd_Shelve,428492.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_YA.Alarm.OCmd_Unshelve,428492.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_YA.Alarm.SCmd_Suppress,428492.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_YA.Alarm.SCmd_UnSuppress,428493.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_YA.Alarm.AEShelveTMRDN,428493.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_YA.Alarm.Bad,428493.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_YA.Alarm.Suppress,428494.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.UnSuppress,428494.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Shelve,428494.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.UnShelve,428494.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Enable,428494.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Disable,428494.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Ack,428494.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Reset,428494.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_YA.Alarm.Suppressed,428494.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_YA.Alarm.Shelved,428494.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_YA.Alarm.Disabled,428494.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_YA.Alarm.Acked,428494.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_YA.Alarm.Alarm,428494.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Fault,428504.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9_YA.almPLCFault.AlarmState,428504.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9_YA.almPLCFault.GlobalReset,428504.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9_YA.almPLCFault.FaultInAlarm,428504.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9_YA.almPLCFault.ALRM,428504.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9_YA.almPLCFault.ANUN,428504.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9_YA.almPLCFault.AKED,428504.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9_YA.almPLCFault.Resetable,428504.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9_YA.almPLCFault.REST,428504.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9_YA.almPLCFault.ACKN,428504.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9_YA.almPLCFault.UACK,428504.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9_YA.almPLCFault.MCmd_Enable,428504.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9_YA.almPLCFault.MCmd_Disable,428504.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9_YA.almPLCFault.OCmd_Shelve,428504.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9_YA.almPLCFault.OCmd_Unshelve,428504.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9_YA.almPLCFault.SCmd_Suppress,428504.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9_YA.almPLCFault.SCmd_UnSuppress,428505.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9_YA.almPLCFault.AEShelveTMRDN,428505.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9_YA.almPLCFault.Bad,428505.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9_YA.almPLCFault.Suppress,428506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.UnSuppress,428506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Shelve,428506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.UnShelve,428506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Enable,428506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Disable,428506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Ack,428506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Reset,428506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Suppressed,428506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Shelved,428506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Disabled,428506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Acked,428506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9_YA.almPLCFault.Alarm,428506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Fault,428526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_1_JA.Alarm.AlarmState,428526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_1_JA.Alarm.GlobalReset,428526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_1_JA.Alarm.FaultInAlarm,428526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JA.Alarm.ALRM,428526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_1_JA.Alarm.ANUN,428526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_1_JA.Alarm.AKED,428526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_1_JA.Alarm.Resetable,428526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_1_JA.Alarm.REST,428526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_1_JA.Alarm.ACKN,428526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_1_JA.Alarm.UACK,428526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_1_JA.Alarm.MCmd_Enable,428526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JA.Alarm.MCmd_Disable,428526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JA.Alarm.OCmd_Shelve,428526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_1_JA.Alarm.OCmd_Unshelve,428526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_1_JA.Alarm.SCmd_Suppress,428526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_1_JA.Alarm.SCmd_UnSuppress,428527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_1_JA.Alarm.AEShelveTMRDN,428527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_1_JA.Alarm.Bad,428527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_1_JA.Alarm.Suppress,428528.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.UnSuppress,428528.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Shelve,428528.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.UnShelve,428528.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Enable,428528.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Disable,428528.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Ack,428528.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Reset,428528.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_1_JA.Alarm.Suppressed,428528.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_1_JA.Alarm.Shelved,428528.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_1_JA.Alarm.Disabled,428528.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_1_JA.Alarm.Acked,428528.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_1_JA.Alarm.Alarm,428528.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Fault,428538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_1_JA.almPLCFault.AlarmState,428538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_1_JA.almPLCFault.GlobalReset,428538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_1_JA.almPLCFault.FaultInAlarm,428538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JA.almPLCFault.ALRM,428538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_1_JA.almPLCFault.ANUN,428538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_1_JA.almPLCFault.AKED,428538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_1_JA.almPLCFault.Resetable,428538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_1_JA.almPLCFault.REST,428538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_1_JA.almPLCFault.ACKN,428538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_1_JA.almPLCFault.UACK,428538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_1_JA.almPLCFault.MCmd_Enable,428538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JA.almPLCFault.MCmd_Disable,428538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JA.almPLCFault.OCmd_Shelve,428538.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_1_JA.almPLCFault.OCmd_Unshelve,428538.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_1_JA.almPLCFault.SCmd_Suppress,428538.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_1_JA.almPLCFault.SCmd_UnSuppress,428539.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_1_JA.almPLCFault.AEShelveTMRDN,428539.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_1_JA.almPLCFault.Bad,428539.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_1_JA.almPLCFault.Suppress,428540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.UnSuppress,428540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Shelve,428540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.UnShelve,428540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Enable,428540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Disable,428540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Ack,428540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Reset,428540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Suppressed,428540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Shelved,428540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Disabled,428540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Acked,428540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_1_JA.almPLCFault.Alarm,428540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Fault,428562.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_1_JN1.Alarm.AlarmState,428562.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_1_JN1.Alarm.GlobalReset,428562.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_1_JN1.Alarm.FaultInAlarm,428562.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JN1.Alarm.ALRM,428562.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_1_JN1.Alarm.ANUN,428562.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_1_JN1.Alarm.AKED,428562.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_1_JN1.Alarm.Resetable,428562.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_1_JN1.Alarm.REST,428562.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_1_JN1.Alarm.ACKN,428562.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_1_JN1.Alarm.UACK,428562.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_1_JN1.Alarm.MCmd_Enable,428562.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JN1.Alarm.MCmd_Disable,428562.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JN1.Alarm.OCmd_Shelve,428562.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_1_JN1.Alarm.OCmd_Unshelve,428562.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_1_JN1.Alarm.SCmd_Suppress,428562.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_1_JN1.Alarm.SCmd_UnSuppress,428563.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_1_JN1.Alarm.AEShelveTMRDN,428563.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_1_JN1.Alarm.Bad,428563.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_1_JN1.Alarm.Suppress,428564.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.UnSuppress,428564.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Shelve,428564.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.UnShelve,428564.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Enable,428564.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Disable,428564.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Ack,428564.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Reset,428564.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_1_JN1.Alarm.Suppressed,428564.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_1_JN1.Alarm.Shelved,428564.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_1_JN1.Alarm.Disabled,428564.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_1_JN1.Alarm.Acked,428564.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_1_JN1.Alarm.Alarm,428564.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Fault,428574.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_1_JN1.almPLCFault.AlarmState,428574.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_1_JN1.almPLCFault.GlobalReset,428574.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_1_JN1.almPLCFault.FaultInAlarm,428574.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_1_JN1.almPLCFault.ALRM,428574.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_1_JN1.almPLCFault.ANUN,428574.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_1_JN1.almPLCFault.AKED,428574.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_1_JN1.almPLCFault.Resetable,428574.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_1_JN1.almPLCFault.REST,428574.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_1_JN1.almPLCFault.ACKN,428574.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_1_JN1.almPLCFault.UACK,428574.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_1_JN1.almPLCFault.MCmd_Enable,428574.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.MCmd_Disable,428574.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.OCmd_Shelve,428574.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.OCmd_Unshelve,428574.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.SCmd_Suppress,428574.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.SCmd_UnSuppress,428575.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_1_JN1.almPLCFault.AEShelveTMRDN,428575.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_1_JN1.almPLCFault.Bad,428575.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_1_JN1.almPLCFault.Suppress,428576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.UnSuppress,428576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Shelve,428576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.UnShelve,428576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Enable,428576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Disable,428576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Ack,428576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Reset,428576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Suppressed,428576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Shelved,428576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Disabled,428576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Acked,428576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_1_JN1.almPLCFault.Alarm,428576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Fault,428596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_2_JA.Alarm.AlarmState,428596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_2_JA.Alarm.GlobalReset,428596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_2_JA.Alarm.FaultInAlarm,428596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JA.Alarm.ALRM,428596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_2_JA.Alarm.ANUN,428596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_2_JA.Alarm.AKED,428596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_2_JA.Alarm.Resetable,428596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_2_JA.Alarm.REST,428596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_2_JA.Alarm.ACKN,428596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_2_JA.Alarm.UACK,428596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_2_JA.Alarm.MCmd_Enable,428596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JA.Alarm.MCmd_Disable,428596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JA.Alarm.OCmd_Shelve,428596.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_2_JA.Alarm.OCmd_Unshelve,428596.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_2_JA.Alarm.SCmd_Suppress,428596.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_2_JA.Alarm.SCmd_UnSuppress,428597.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_2_JA.Alarm.AEShelveTMRDN,428597.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_2_JA.Alarm.Bad,428597.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_2_JA.Alarm.Suppress,428598.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.UnSuppress,428598.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Shelve,428598.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.UnShelve,428598.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Enable,428598.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Disable,428598.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Ack,428598.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Reset,428598.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_2_JA.Alarm.Suppressed,428598.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_2_JA.Alarm.Shelved,428598.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_2_JA.Alarm.Disabled,428598.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_2_JA.Alarm.Acked,428598.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_2_JA.Alarm.Alarm,428598.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Fault,428608.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_2_JA.almPLCFault.AlarmState,428608.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_2_JA.almPLCFault.GlobalReset,428608.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_2_JA.almPLCFault.FaultInAlarm,428608.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JA.almPLCFault.ALRM,428608.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_2_JA.almPLCFault.ANUN,428608.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_2_JA.almPLCFault.AKED,428608.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_2_JA.almPLCFault.Resetable,428608.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_2_JA.almPLCFault.REST,428608.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_2_JA.almPLCFault.ACKN,428608.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_2_JA.almPLCFault.UACK,428608.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_2_JA.almPLCFault.MCmd_Enable,428608.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JA.almPLCFault.MCmd_Disable,428608.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JA.almPLCFault.OCmd_Shelve,428608.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_2_JA.almPLCFault.OCmd_Unshelve,428608.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_2_JA.almPLCFault.SCmd_Suppress,428608.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_2_JA.almPLCFault.SCmd_UnSuppress,428609.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_2_JA.almPLCFault.AEShelveTMRDN,428609.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_2_JA.almPLCFault.Bad,428609.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_2_JA.almPLCFault.Suppress,428610.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.UnSuppress,428610.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Shelve,428610.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.UnShelve,428610.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Enable,428610.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Disable,428610.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Ack,428610.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Reset,428610.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Suppressed,428610.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Shelved,428610.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Disabled,428610.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Acked,428610.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_2_JA.almPLCFault.Alarm,428610.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Fault,428632.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_2_JN1.Alarm.AlarmState,428632.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_2_JN1.Alarm.GlobalReset,428632.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_2_JN1.Alarm.FaultInAlarm,428632.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JN1.Alarm.ALRM,428632.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_2_JN1.Alarm.ANUN,428632.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_2_JN1.Alarm.AKED,428632.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_2_JN1.Alarm.Resetable,428632.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_2_JN1.Alarm.REST,428632.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_2_JN1.Alarm.ACKN,428632.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_2_JN1.Alarm.UACK,428632.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_2_JN1.Alarm.MCmd_Enable,428632.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JN1.Alarm.MCmd_Disable,428632.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JN1.Alarm.OCmd_Shelve,428632.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_2_JN1.Alarm.OCmd_Unshelve,428632.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_2_JN1.Alarm.SCmd_Suppress,428632.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_2_JN1.Alarm.SCmd_UnSuppress,428633.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_2_JN1.Alarm.AEShelveTMRDN,428633.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_2_JN1.Alarm.Bad,428633.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_2_JN1.Alarm.Suppress,428634.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.UnSuppress,428634.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Shelve,428634.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.UnShelve,428634.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Enable,428634.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Disable,428634.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Ack,428634.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Reset,428634.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_2_JN1.Alarm.Suppressed,428634.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_2_JN1.Alarm.Shelved,428634.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_2_JN1.Alarm.Disabled,428634.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_2_JN1.Alarm.Acked,428634.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_2_JN1.Alarm.Alarm,428634.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Fault,428644.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0112_2_JN1.almPLCFault.AlarmState,428644.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0112_2_JN1.almPLCFault.GlobalReset,428644.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0112_2_JN1.almPLCFault.FaultInAlarm,428644.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0112_2_JN1.almPLCFault.ALRM,428644.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0112_2_JN1.almPLCFault.ANUN,428644.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0112_2_JN1.almPLCFault.AKED,428644.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0112_2_JN1.almPLCFault.Resetable,428644.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0112_2_JN1.almPLCFault.REST,428644.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0112_2_JN1.almPLCFault.ACKN,428644.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0112_2_JN1.almPLCFault.UACK,428644.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0112_2_JN1.almPLCFault.MCmd_Enable,428644.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.MCmd_Disable,428644.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.OCmd_Shelve,428644.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.OCmd_Unshelve,428644.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.SCmd_Suppress,428644.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.SCmd_UnSuppress,428645.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0112_2_JN1.almPLCFault.AEShelveTMRDN,428645.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0112_2_JN1.almPLCFault.Bad,428645.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0112_2_JN1.almPLCFault.Suppress,428646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.UnSuppress,428646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Shelve,428646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.UnShelve,428646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Enable,428646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Disable,428646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Ack,428646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Reset,428646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Suppressed,428646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Shelved,428646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Disabled,428646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Acked,428646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0112_2_JN1.almPLCFault.Alarm,428646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Fault,428666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0140_1_JA.Alarm.AlarmState,428666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0140_1_JA.Alarm.GlobalReset,428666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0140_1_JA.Alarm.FaultInAlarm,428666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_JA.Alarm.ALRM,428666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0140_1_JA.Alarm.ANUN,428666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0140_1_JA.Alarm.AKED,428666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0140_1_JA.Alarm.Resetable,428666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0140_1_JA.Alarm.REST,428666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0140_1_JA.Alarm.ACKN,428666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0140_1_JA.Alarm.UACK,428666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0140_1_JA.Alarm.MCmd_Enable,428666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_JA.Alarm.MCmd_Disable,428666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_JA.Alarm.OCmd_Shelve,428666.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0140_1_JA.Alarm.OCmd_Unshelve,428666.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0140_1_JA.Alarm.SCmd_Suppress,428666.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0140_1_JA.Alarm.SCmd_UnSuppress,428667.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0140_1_JA.Alarm.AEShelveTMRDN,428667.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0140_1_JA.Alarm.Bad,428667.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0140_1_JA.Alarm.Suppress,428668.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.UnSuppress,428668.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Shelve,428668.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.UnShelve,428668.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Enable,428668.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Disable,428668.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Ack,428668.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Reset,428668.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0140_1_JA.Alarm.Suppressed,428668.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0140_1_JA.Alarm.Shelved,428668.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0140_1_JA.Alarm.Disabled,428668.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0140_1_JA.Alarm.Acked,428668.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0140_1_JA.Alarm.Alarm,428668.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Fault,428678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0140_1_JA.almPLCFault.AlarmState,428678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0140_1_JA.almPLCFault.GlobalReset,428678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0140_1_JA.almPLCFault.FaultInAlarm,428678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_JA.almPLCFault.ALRM,428678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0140_1_JA.almPLCFault.ANUN,428678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0140_1_JA.almPLCFault.AKED,428678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0140_1_JA.almPLCFault.Resetable,428678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0140_1_JA.almPLCFault.REST,428678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0140_1_JA.almPLCFault.ACKN,428678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0140_1_JA.almPLCFault.UACK,428678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0140_1_JA.almPLCFault.MCmd_Enable,428678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_JA.almPLCFault.MCmd_Disable,428678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_JA.almPLCFault.OCmd_Shelve,428678.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0140_1_JA.almPLCFault.OCmd_Unshelve,428678.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0140_1_JA.almPLCFault.SCmd_Suppress,428678.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0140_1_JA.almPLCFault.SCmd_UnSuppress,428679.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0140_1_JA.almPLCFault.AEShelveTMRDN,428679.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0140_1_JA.almPLCFault.Bad,428679.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0140_1_JA.almPLCFault.Suppress,428680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.UnSuppress,428680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Shelve,428680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.UnShelve,428680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Enable,428680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Disable,428680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Ack,428680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Reset,428680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Suppressed,428680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Shelved,428680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Disabled,428680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Acked,428680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0140_1_JA.almPLCFault.Alarm,428680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Fault,428702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0140_1_XA.Alarm.AlarmState,428702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0140_1_XA.Alarm.GlobalReset,428702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0140_1_XA.Alarm.FaultInAlarm,428702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_XA.Alarm.ALRM,428702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0140_1_XA.Alarm.ANUN,428702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0140_1_XA.Alarm.AKED,428702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0140_1_XA.Alarm.Resetable,428702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0140_1_XA.Alarm.REST,428702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0140_1_XA.Alarm.ACKN,428702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0140_1_XA.Alarm.UACK,428702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0140_1_XA.Alarm.MCmd_Enable,428702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_XA.Alarm.MCmd_Disable,428702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_XA.Alarm.OCmd_Shelve,428702.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0140_1_XA.Alarm.OCmd_Unshelve,428702.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0140_1_XA.Alarm.SCmd_Suppress,428702.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0140_1_XA.Alarm.SCmd_UnSuppress,428703.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0140_1_XA.Alarm.AEShelveTMRDN,428703.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0140_1_XA.Alarm.Bad,428703.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0140_1_XA.Alarm.Suppress,428704.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.UnSuppress,428704.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Shelve,428704.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.UnShelve,428704.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Enable,428704.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Disable,428704.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Ack,428704.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Reset,428704.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0140_1_XA.Alarm.Suppressed,428704.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0140_1_XA.Alarm.Shelved,428704.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0140_1_XA.Alarm.Disabled,428704.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0140_1_XA.Alarm.Acked,428704.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0140_1_XA.Alarm.Alarm,428704.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Fault,428714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_ATO_0140_1_XA.almPLCFault.AlarmState,428714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_ATO_0140_1_XA.almPLCFault.GlobalReset,428714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_ATO_0140_1_XA.almPLCFault.FaultInAlarm,428714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_ATO_0140_1_XA.almPLCFault.ALRM,428714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_ATO_0140_1_XA.almPLCFault.ANUN,428714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_ATO_0140_1_XA.almPLCFault.AKED,428714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_ATO_0140_1_XA.almPLCFault.Resetable,428714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_ATO_0140_1_XA.almPLCFault.REST,428714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_ATO_0140_1_XA.almPLCFault.ACKN,428714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_ATO_0140_1_XA.almPLCFault.UACK,428714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_ATO_0140_1_XA.almPLCFault.MCmd_Enable,428714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_ATO_0140_1_XA.almPLCFault.MCmd_Disable,428714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_ATO_0140_1_XA.almPLCFault.OCmd_Shelve,428714.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_ATO_0140_1_XA.almPLCFault.OCmd_Unshelve,428714.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_ATO_0140_1_XA.almPLCFault.SCmd_Suppress,428714.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_ATO_0140_1_XA.almPLCFault.SCmd_UnSuppress,428715.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_ATO_0140_1_XA.almPLCFault.AEShelveTMRDN,428715.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_ATO_0140_1_XA.almPLCFault.Bad,428715.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_ATO_0140_1_XA.almPLCFault.Suppress,428716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.UnSuppress,428716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Shelve,428716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.UnShelve,428716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Enable,428716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Disable,428716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Ack,428716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Reset,428716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Suppressed,428716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Shelved,428716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Disabled,428716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Acked,428716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_ATO_0140_1_XA.almPLCFault.Alarm,428716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Fault,428736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_1_XA.Alarm.AlarmState,428736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_1_XA.Alarm.GlobalReset,428736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_1_XA.Alarm.FaultInAlarm,428736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_1_XA.Alarm.ALRM,428736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_1_XA.Alarm.ANUN,428736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_1_XA.Alarm.AKED,428736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_1_XA.Alarm.Resetable,428736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_1_XA.Alarm.REST,428736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_1_XA.Alarm.ACKN,428736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_1_XA.Alarm.UACK,428736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_1_XA.Alarm.MCmd_Enable,428736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_1_XA.Alarm.MCmd_Disable,428736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_1_XA.Alarm.OCmd_Shelve,428736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_1_XA.Alarm.OCmd_Unshelve,428736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_1_XA.Alarm.SCmd_Suppress,428736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_1_XA.Alarm.SCmd_UnSuppress,428737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_1_XA.Alarm.AEShelveTMRDN,428737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_1_XA.Alarm.Bad,428737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_1_XA.Alarm.Suppress,428738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.UnSuppress,428738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Shelve,428738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.UnShelve,428738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Enable,428738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Disable,428738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Ack,428738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Reset,428738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_1_XA.Alarm.Suppressed,428738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_1_XA.Alarm.Shelved,428738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_1_XA.Alarm.Disabled,428738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_1_XA.Alarm.Acked,428738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_1_XA.Alarm.Alarm,428738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Fault,428748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_1_XA.almPLCFault.AlarmState,428748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_1_XA.almPLCFault.GlobalReset,428748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_1_XA.almPLCFault.FaultInAlarm,428748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_1_XA.almPLCFault.ALRM,428748.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_1_XA.almPLCFault.ANUN,428748.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_1_XA.almPLCFault.AKED,428748.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_1_XA.almPLCFault.Resetable,428748.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_1_XA.almPLCFault.REST,428748.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_1_XA.almPLCFault.ACKN,428748.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_1_XA.almPLCFault.UACK,428748.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_1_XA.almPLCFault.MCmd_Enable,428748.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_1_XA.almPLCFault.MCmd_Disable,428748.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_1_XA.almPLCFault.OCmd_Shelve,428748.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_1_XA.almPLCFault.OCmd_Unshelve,428748.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_1_XA.almPLCFault.SCmd_Suppress,428748.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_1_XA.almPLCFault.SCmd_UnSuppress,428749.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_1_XA.almPLCFault.AEShelveTMRDN,428749.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_1_XA.almPLCFault.Bad,428749.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_1_XA.almPLCFault.Suppress,428750.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.UnSuppress,428750.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Shelve,428750.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.UnShelve,428750.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Enable,428750.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Disable,428750.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Ack,428750.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Reset,428750.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_1_XA.almPLCFault.Suppressed,428750.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_1_XA.almPLCFault.Shelved,428750.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_1_XA.almPLCFault.Disabled,428750.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_1_XA.almPLCFault.Acked,428750.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_1_XA.almPLCFault.Alarm,428750.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Fault,428772.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_2_XA.Alarm.AlarmState,428772.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_2_XA.Alarm.GlobalReset,428772.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_2_XA.Alarm.FaultInAlarm,428772.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_2_XA.Alarm.ALRM,428772.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_2_XA.Alarm.ANUN,428772.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_2_XA.Alarm.AKED,428772.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_2_XA.Alarm.Resetable,428772.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_2_XA.Alarm.REST,428772.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_2_XA.Alarm.ACKN,428772.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_2_XA.Alarm.UACK,428772.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_2_XA.Alarm.MCmd_Enable,428772.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_2_XA.Alarm.MCmd_Disable,428772.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_2_XA.Alarm.OCmd_Shelve,428772.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_2_XA.Alarm.OCmd_Unshelve,428772.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_2_XA.Alarm.SCmd_Suppress,428772.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_2_XA.Alarm.SCmd_UnSuppress,428773.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_2_XA.Alarm.AEShelveTMRDN,428773.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_2_XA.Alarm.Bad,428773.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_2_XA.Alarm.Suppress,428774.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.UnSuppress,428774.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Shelve,428774.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.UnShelve,428774.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Enable,428774.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Disable,428774.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Ack,428774.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Reset,428774.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_2_XA.Alarm.Suppressed,428774.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_2_XA.Alarm.Shelved,428774.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_2_XA.Alarm.Disabled,428774.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_2_XA.Alarm.Acked,428774.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_2_XA.Alarm.Alarm,428774.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Fault,428784.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_2_XA.almPLCFault.AlarmState,428784.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_2_XA.almPLCFault.GlobalReset,428784.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_2_XA.almPLCFault.FaultInAlarm,428784.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_2_XA.almPLCFault.ALRM,428784.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_2_XA.almPLCFault.ANUN,428784.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_2_XA.almPLCFault.AKED,428784.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_2_XA.almPLCFault.Resetable,428784.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_2_XA.almPLCFault.REST,428784.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_2_XA.almPLCFault.ACKN,428784.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_2_XA.almPLCFault.UACK,428784.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_2_XA.almPLCFault.MCmd_Enable,428784.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_2_XA.almPLCFault.MCmd_Disable,428784.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_2_XA.almPLCFault.OCmd_Shelve,428784.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_2_XA.almPLCFault.OCmd_Unshelve,428784.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_2_XA.almPLCFault.SCmd_Suppress,428784.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_2_XA.almPLCFault.SCmd_UnSuppress,428785.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_2_XA.almPLCFault.AEShelveTMRDN,428785.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_2_XA.almPLCFault.Bad,428785.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_2_XA.almPLCFault.Suppress,428786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.UnSuppress,428786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Shelve,428786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.UnShelve,428786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Enable,428786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Disable,428786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Ack,428786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Reset,428786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_2_XA.almPLCFault.Suppressed,428786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_2_XA.almPLCFault.Shelved,428786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_2_XA.almPLCFault.Disabled,428786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_2_XA.almPLCFault.Acked,428786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_2_XA.almPLCFault.Alarm,428786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Fault,428806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_3_LH.Alarm.AlarmState,428806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_3_LH.Alarm.GlobalReset,428806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_3_LH.Alarm.FaultInAlarm,428806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_3_LH.Alarm.ALRM,428806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_3_LH.Alarm.ANUN,428806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_3_LH.Alarm.AKED,428806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_3_LH.Alarm.Resetable,428806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_3_LH.Alarm.REST,428806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_3_LH.Alarm.ACKN,428806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_3_LH.Alarm.UACK,428806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_3_LH.Alarm.MCmd_Enable,428806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_3_LH.Alarm.MCmd_Disable,428806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_3_LH.Alarm.OCmd_Shelve,428806.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_3_LH.Alarm.OCmd_Unshelve,428806.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_3_LH.Alarm.SCmd_Suppress,428806.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_3_LH.Alarm.SCmd_UnSuppress,428807.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_3_LH.Alarm.AEShelveTMRDN,428807.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_3_LH.Alarm.Bad,428807.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_3_LH.Alarm.Suppress,428808.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.UnSuppress,428808.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Shelve,428808.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.UnShelve,428808.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Enable,428808.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Disable,428808.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Ack,428808.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Reset,428808.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_3_LH.Alarm.Suppressed,428808.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_3_LH.Alarm.Shelved,428808.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_3_LH.Alarm.Disabled,428808.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_3_LH.Alarm.Acked,428808.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_3_LH.Alarm.Alarm,428808.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Fault,428818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0114_3_LH.almPLCFault.AlarmState,428818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0114_3_LH.almPLCFault.GlobalReset,428818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0114_3_LH.almPLCFault.FaultInAlarm,428818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0114_3_LH.almPLCFault.ALRM,428818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0114_3_LH.almPLCFault.ANUN,428818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0114_3_LH.almPLCFault.AKED,428818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0114_3_LH.almPLCFault.Resetable,428818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0114_3_LH.almPLCFault.REST,428818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0114_3_LH.almPLCFault.ACKN,428818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0114_3_LH.almPLCFault.UACK,428818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0114_3_LH.almPLCFault.MCmd_Enable,428818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0114_3_LH.almPLCFault.MCmd_Disable,428818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0114_3_LH.almPLCFault.OCmd_Shelve,428818.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0114_3_LH.almPLCFault.OCmd_Unshelve,428818.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0114_3_LH.almPLCFault.SCmd_Suppress,428818.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0114_3_LH.almPLCFault.SCmd_UnSuppress,428819.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0114_3_LH.almPLCFault.AEShelveTMRDN,428819.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0114_3_LH.almPLCFault.Bad,428819.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0114_3_LH.almPLCFault.Suppress,428820.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.UnSuppress,428820.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Shelve,428820.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.UnShelve,428820.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Enable,428820.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Disable,428820.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Ack,428820.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Reset,428820.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0114_3_LH.almPLCFault.Suppressed,428820.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0114_3_LH.almPLCFault.Shelved,428820.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0114_3_LH.almPLCFault.Disabled,428820.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0114_3_LH.almPLCFault.Acked,428820.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0114_3_LH.almPLCFault.Alarm,428820.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Fault,428842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1A_MF.Alarm.AlarmState,428842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1A_MF.Alarm.GlobalReset,428842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1A_MF.Alarm.FaultInAlarm,428842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_MF.Alarm.ALRM,428842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1A_MF.Alarm.ANUN,428842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1A_MF.Alarm.AKED,428842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1A_MF.Alarm.Resetable,428842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1A_MF.Alarm.REST,428842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1A_MF.Alarm.ACKN,428842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1A_MF.Alarm.UACK,428842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1A_MF.Alarm.MCmd_Enable,428842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_MF.Alarm.MCmd_Disable,428842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_MF.Alarm.OCmd_Shelve,428842.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1A_MF.Alarm.OCmd_Unshelve,428842.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1A_MF.Alarm.SCmd_Suppress,428842.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1A_MF.Alarm.SCmd_UnSuppress,428843.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1A_MF.Alarm.AEShelveTMRDN,428843.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1A_MF.Alarm.Bad,428843.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1A_MF.Alarm.Suppress,428844.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.UnSuppress,428844.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Shelve,428844.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.UnShelve,428844.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Enable,428844.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Disable,428844.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Ack,428844.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Reset,428844.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1A_MF.Alarm.Suppressed,428844.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1A_MF.Alarm.Shelved,428844.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1A_MF.Alarm.Disabled,428844.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1A_MF.Alarm.Acked,428844.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1A_MF.Alarm.Alarm,428844.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Fault,428854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1A_MF.almPLCFault.AlarmState,428854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1A_MF.almPLCFault.GlobalReset,428854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1A_MF.almPLCFault.FaultInAlarm,428854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_MF.almPLCFault.ALRM,428854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1A_MF.almPLCFault.ANUN,428854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1A_MF.almPLCFault.AKED,428854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1A_MF.almPLCFault.Resetable,428854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1A_MF.almPLCFault.REST,428854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1A_MF.almPLCFault.ACKN,428854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1A_MF.almPLCFault.UACK,428854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1A_MF.almPLCFault.MCmd_Enable,428854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_MF.almPLCFault.MCmd_Disable,428854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_MF.almPLCFault.OCmd_Shelve,428854.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1A_MF.almPLCFault.OCmd_Unshelve,428854.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1A_MF.almPLCFault.SCmd_Suppress,428854.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1A_MF.almPLCFault.SCmd_UnSuppress,428855.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1A_MF.almPLCFault.AEShelveTMRDN,428855.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1A_MF.almPLCFault.Bad,428855.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1A_MF.almPLCFault.Suppress,428856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.UnSuppress,428856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Shelve,428856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.UnShelve,428856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Enable,428856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Disable,428856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Ack,428856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Reset,428856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Suppressed,428856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Shelved,428856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Disabled,428856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Acked,428856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1A_MF.almPLCFault.Alarm,428856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Fault,428876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1A_XA.Alarm.AlarmState,428876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1A_XA.Alarm.GlobalReset,428876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1A_XA.Alarm.FaultInAlarm,428876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_XA.Alarm.ALRM,428876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1A_XA.Alarm.ANUN,428876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1A_XA.Alarm.AKED,428876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1A_XA.Alarm.Resetable,428876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1A_XA.Alarm.REST,428876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1A_XA.Alarm.ACKN,428876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1A_XA.Alarm.UACK,428876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1A_XA.Alarm.MCmd_Enable,428876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_XA.Alarm.MCmd_Disable,428876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_XA.Alarm.OCmd_Shelve,428876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1A_XA.Alarm.OCmd_Unshelve,428876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1A_XA.Alarm.SCmd_Suppress,428876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1A_XA.Alarm.SCmd_UnSuppress,428877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1A_XA.Alarm.AEShelveTMRDN,428877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1A_XA.Alarm.Bad,428877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1A_XA.Alarm.Suppress,428878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.UnSuppress,428878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Shelve,428878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.UnShelve,428878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Enable,428878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Disable,428878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Ack,428878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Reset,428878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1A_XA.Alarm.Suppressed,428878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1A_XA.Alarm.Shelved,428878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1A_XA.Alarm.Disabled,428878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1A_XA.Alarm.Acked,428878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1A_XA.Alarm.Alarm,428878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Fault,428888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1A_XA.almPLCFault.AlarmState,428888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1A_XA.almPLCFault.GlobalReset,428888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1A_XA.almPLCFault.FaultInAlarm,428888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1A_XA.almPLCFault.ALRM,428888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1A_XA.almPLCFault.ANUN,428888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1A_XA.almPLCFault.AKED,428888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1A_XA.almPLCFault.Resetable,428888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1A_XA.almPLCFault.REST,428888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1A_XA.almPLCFault.ACKN,428888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1A_XA.almPLCFault.UACK,428888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1A_XA.almPLCFault.MCmd_Enable,428888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1A_XA.almPLCFault.MCmd_Disable,428888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1A_XA.almPLCFault.OCmd_Shelve,428888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1A_XA.almPLCFault.OCmd_Unshelve,428888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1A_XA.almPLCFault.SCmd_Suppress,428888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1A_XA.almPLCFault.SCmd_UnSuppress,428889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1A_XA.almPLCFault.AEShelveTMRDN,428889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1A_XA.almPLCFault.Bad,428889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1A_XA.almPLCFault.Suppress,428890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.UnSuppress,428890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Shelve,428890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.UnShelve,428890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Enable,428890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Disable,428890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Ack,428890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Reset,428890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Suppressed,428890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Shelved,428890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Disabled,428890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Acked,428890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1A_XA.almPLCFault.Alarm,428890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Fault,428912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1B_MF.Alarm.AlarmState,428912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1B_MF.Alarm.GlobalReset,428912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1B_MF.Alarm.FaultInAlarm,428912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_MF.Alarm.ALRM,428912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1B_MF.Alarm.ANUN,428912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1B_MF.Alarm.AKED,428912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1B_MF.Alarm.Resetable,428912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1B_MF.Alarm.REST,428912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1B_MF.Alarm.ACKN,428912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1B_MF.Alarm.UACK,428912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1B_MF.Alarm.MCmd_Enable,428912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_MF.Alarm.MCmd_Disable,428912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_MF.Alarm.OCmd_Shelve,428912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1B_MF.Alarm.OCmd_Unshelve,428912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1B_MF.Alarm.SCmd_Suppress,428912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1B_MF.Alarm.SCmd_UnSuppress,428913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1B_MF.Alarm.AEShelveTMRDN,428913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1B_MF.Alarm.Bad,428913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1B_MF.Alarm.Suppress,428914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.UnSuppress,428914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Shelve,428914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.UnShelve,428914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Enable,428914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Disable,428914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Ack,428914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Reset,428914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1B_MF.Alarm.Suppressed,428914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1B_MF.Alarm.Shelved,428914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1B_MF.Alarm.Disabled,428914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1B_MF.Alarm.Acked,428914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1B_MF.Alarm.Alarm,428914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Fault,428924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1B_MF.almPLCFault.AlarmState,428924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1B_MF.almPLCFault.GlobalReset,428924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1B_MF.almPLCFault.FaultInAlarm,428924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_MF.almPLCFault.ALRM,428924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1B_MF.almPLCFault.ANUN,428924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1B_MF.almPLCFault.AKED,428924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1B_MF.almPLCFault.Resetable,428924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1B_MF.almPLCFault.REST,428924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1B_MF.almPLCFault.ACKN,428924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1B_MF.almPLCFault.UACK,428924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1B_MF.almPLCFault.MCmd_Enable,428924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_MF.almPLCFault.MCmd_Disable,428924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_MF.almPLCFault.OCmd_Shelve,428924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1B_MF.almPLCFault.OCmd_Unshelve,428924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1B_MF.almPLCFault.SCmd_Suppress,428924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1B_MF.almPLCFault.SCmd_UnSuppress,428925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1B_MF.almPLCFault.AEShelveTMRDN,428925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1B_MF.almPLCFault.Bad,428925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1B_MF.almPLCFault.Suppress,428926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.UnSuppress,428926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Shelve,428926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.UnShelve,428926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Enable,428926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Disable,428926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Ack,428926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Reset,428926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Suppressed,428926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Shelved,428926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Disabled,428926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Acked,428926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1B_MF.almPLCFault.Alarm,428926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Fault,428946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1B_XA.Alarm.AlarmState,428946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1B_XA.Alarm.GlobalReset,428946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1B_XA.Alarm.FaultInAlarm,428946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_XA.Alarm.ALRM,428946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1B_XA.Alarm.ANUN,428946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1B_XA.Alarm.AKED,428946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1B_XA.Alarm.Resetable,428946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1B_XA.Alarm.REST,428946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1B_XA.Alarm.ACKN,428946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1B_XA.Alarm.UACK,428946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1B_XA.Alarm.MCmd_Enable,428946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_XA.Alarm.MCmd_Disable,428946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_XA.Alarm.OCmd_Shelve,428946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1B_XA.Alarm.OCmd_Unshelve,428946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1B_XA.Alarm.SCmd_Suppress,428946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1B_XA.Alarm.SCmd_UnSuppress,428947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1B_XA.Alarm.AEShelveTMRDN,428947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1B_XA.Alarm.Bad,428947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1B_XA.Alarm.Suppress,428948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.UnSuppress,428948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Shelve,428948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.UnShelve,428948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Enable,428948.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Disable,428948.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Ack,428948.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Reset,428948.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1B_XA.Alarm.Suppressed,428948.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1B_XA.Alarm.Shelved,428948.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1B_XA.Alarm.Disabled,428948.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1B_XA.Alarm.Acked,428948.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1B_XA.Alarm.Alarm,428948.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Fault,428958.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1B_XA.almPLCFault.AlarmState,428958.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1B_XA.almPLCFault.GlobalReset,428958.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1B_XA.almPLCFault.FaultInAlarm,428958.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1B_XA.almPLCFault.ALRM,428958.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1B_XA.almPLCFault.ANUN,428958.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1B_XA.almPLCFault.AKED,428958.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1B_XA.almPLCFault.Resetable,428958.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1B_XA.almPLCFault.REST,428958.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1B_XA.almPLCFault.ACKN,428958.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1B_XA.almPLCFault.UACK,428958.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1B_XA.almPLCFault.MCmd_Enable,428958.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1B_XA.almPLCFault.MCmd_Disable,428958.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1B_XA.almPLCFault.OCmd_Shelve,428958.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1B_XA.almPLCFault.OCmd_Unshelve,428958.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1B_XA.almPLCFault.SCmd_Suppress,428958.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1B_XA.almPLCFault.SCmd_UnSuppress,428959.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1B_XA.almPLCFault.AEShelveTMRDN,428959.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1B_XA.almPLCFault.Bad,428959.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1B_XA.almPLCFault.Suppress,428960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.UnSuppress,428960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Shelve,428960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.UnShelve,428960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Enable,428960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Disable,428960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Ack,428960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Reset,428960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Suppressed,428960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Shelved,428960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Disabled,428960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Acked,428960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1B_XA.almPLCFault.Alarm,428960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Fault,428982.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1C_MF.Alarm.AlarmState,428982.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1C_MF.Alarm.GlobalReset,428982.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1C_MF.Alarm.FaultInAlarm,428982.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_MF.Alarm.ALRM,428982.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1C_MF.Alarm.ANUN,428982.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1C_MF.Alarm.AKED,428982.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1C_MF.Alarm.Resetable,428982.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1C_MF.Alarm.REST,428982.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1C_MF.Alarm.ACKN,428982.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1C_MF.Alarm.UACK,428982.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1C_MF.Alarm.MCmd_Enable,428982.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_MF.Alarm.MCmd_Disable,428982.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_MF.Alarm.OCmd_Shelve,428982.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1C_MF.Alarm.OCmd_Unshelve,428982.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1C_MF.Alarm.SCmd_Suppress,428982.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1C_MF.Alarm.SCmd_UnSuppress,428983.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1C_MF.Alarm.AEShelveTMRDN,428983.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1C_MF.Alarm.Bad,428983.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1C_MF.Alarm.Suppress,428984.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.UnSuppress,428984.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Shelve,428984.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.UnShelve,428984.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Enable,428984.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Disable,428984.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Ack,428984.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Reset,428984.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1C_MF.Alarm.Suppressed,428984.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1C_MF.Alarm.Shelved,428984.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1C_MF.Alarm.Disabled,428984.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1C_MF.Alarm.Acked,428984.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1C_MF.Alarm.Alarm,428984.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Fault,428994.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1C_MF.almPLCFault.AlarmState,428994.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1C_MF.almPLCFault.GlobalReset,428994.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1C_MF.almPLCFault.FaultInAlarm,428994.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_MF.almPLCFault.ALRM,428994.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1C_MF.almPLCFault.ANUN,428994.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1C_MF.almPLCFault.AKED,428994.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1C_MF.almPLCFault.Resetable,428994.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1C_MF.almPLCFault.REST,428994.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1C_MF.almPLCFault.ACKN,428994.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1C_MF.almPLCFault.UACK,428994.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1C_MF.almPLCFault.MCmd_Enable,428994.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_MF.almPLCFault.MCmd_Disable,428994.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_MF.almPLCFault.OCmd_Shelve,428994.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1C_MF.almPLCFault.OCmd_Unshelve,428994.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1C_MF.almPLCFault.SCmd_Suppress,428994.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1C_MF.almPLCFault.SCmd_UnSuppress,428995.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1C_MF.almPLCFault.AEShelveTMRDN,428995.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1C_MF.almPLCFault.Bad,428995.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1C_MF.almPLCFault.Suppress,428996.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.UnSuppress,428996.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Shelve,428996.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.UnShelve,428996.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Enable,428996.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Disable,428996.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Ack,428996.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Reset,428996.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Suppressed,428996.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Shelved,428996.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Disabled,428996.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Acked,428996.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1C_MF.almPLCFault.Alarm,428996.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Fault,429016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1C_XA.Alarm.AlarmState,429016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1C_XA.Alarm.GlobalReset,429016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1C_XA.Alarm.FaultInAlarm,429016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_XA.Alarm.ALRM,429016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1C_XA.Alarm.ANUN,429016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1C_XA.Alarm.AKED,429016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1C_XA.Alarm.Resetable,429016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1C_XA.Alarm.REST,429016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1C_XA.Alarm.ACKN,429016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1C_XA.Alarm.UACK,429016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1C_XA.Alarm.MCmd_Enable,429016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_XA.Alarm.MCmd_Disable,429016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_XA.Alarm.OCmd_Shelve,429016.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1C_XA.Alarm.OCmd_Unshelve,429016.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1C_XA.Alarm.SCmd_Suppress,429016.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1C_XA.Alarm.SCmd_UnSuppress,429017.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1C_XA.Alarm.AEShelveTMRDN,429017.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1C_XA.Alarm.Bad,429017.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1C_XA.Alarm.Suppress,429018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.UnSuppress,429018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Shelve,429018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.UnShelve,429018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Enable,429018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Disable,429018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Ack,429018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Reset,429018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1C_XA.Alarm.Suppressed,429018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1C_XA.Alarm.Shelved,429018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1C_XA.Alarm.Disabled,429018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1C_XA.Alarm.Acked,429018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1C_XA.Alarm.Alarm,429018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Fault,429028.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1C_XA.almPLCFault.AlarmState,429028.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1C_XA.almPLCFault.GlobalReset,429028.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1C_XA.almPLCFault.FaultInAlarm,429028.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1C_XA.almPLCFault.ALRM,429028.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1C_XA.almPLCFault.ANUN,429028.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1C_XA.almPLCFault.AKED,429028.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1C_XA.almPLCFault.Resetable,429028.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1C_XA.almPLCFault.REST,429028.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1C_XA.almPLCFault.ACKN,429028.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1C_XA.almPLCFault.UACK,429028.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1C_XA.almPLCFault.MCmd_Enable,429028.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1C_XA.almPLCFault.MCmd_Disable,429028.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1C_XA.almPLCFault.OCmd_Shelve,429028.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1C_XA.almPLCFault.OCmd_Unshelve,429028.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1C_XA.almPLCFault.SCmd_Suppress,429028.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1C_XA.almPLCFault.SCmd_UnSuppress,429029.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1C_XA.almPLCFault.AEShelveTMRDN,429029.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1C_XA.almPLCFault.Bad,429029.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1C_XA.almPLCFault.Suppress,429030.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.UnSuppress,429030.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Shelve,429030.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.UnShelve,429030.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Enable,429030.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Disable,429030.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Ack,429030.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Reset,429030.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Suppressed,429030.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Shelved,429030.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Disabled,429030.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Acked,429030.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1C_XA.almPLCFault.Alarm,429030.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Fault,429052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1DE_MF.Alarm.AlarmState,429052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1DE_MF.Alarm.GlobalReset,429052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1DE_MF.Alarm.FaultInAlarm,429052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_MF.Alarm.ALRM,429052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1DE_MF.Alarm.ANUN,429052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1DE_MF.Alarm.AKED,429052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1DE_MF.Alarm.Resetable,429052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1DE_MF.Alarm.REST,429052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1DE_MF.Alarm.ACKN,429052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1DE_MF.Alarm.UACK,429052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1DE_MF.Alarm.MCmd_Enable,429052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_MF.Alarm.MCmd_Disable,429052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_MF.Alarm.OCmd_Shelve,429052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1DE_MF.Alarm.OCmd_Unshelve,429052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1DE_MF.Alarm.SCmd_Suppress,429052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1DE_MF.Alarm.SCmd_UnSuppress,429053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1DE_MF.Alarm.AEShelveTMRDN,429053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1DE_MF.Alarm.Bad,429053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1DE_MF.Alarm.Suppress,429054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.UnSuppress,429054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Shelve,429054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.UnShelve,429054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Enable,429054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Disable,429054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Ack,429054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Reset,429054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1DE_MF.Alarm.Suppressed,429054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1DE_MF.Alarm.Shelved,429054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1DE_MF.Alarm.Disabled,429054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1DE_MF.Alarm.Acked,429054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1DE_MF.Alarm.Alarm,429054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Fault,429064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1DE_MF.almPLCFault.AlarmState,429064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1DE_MF.almPLCFault.GlobalReset,429064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1DE_MF.almPLCFault.FaultInAlarm,429064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_MF.almPLCFault.ALRM,429064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1DE_MF.almPLCFault.ANUN,429064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1DE_MF.almPLCFault.AKED,429064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1DE_MF.almPLCFault.Resetable,429064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1DE_MF.almPLCFault.REST,429064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1DE_MF.almPLCFault.ACKN,429064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1DE_MF.almPLCFault.UACK,429064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1DE_MF.almPLCFault.MCmd_Enable,429064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.MCmd_Disable,429064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.OCmd_Shelve,429064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.OCmd_Unshelve,429064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.SCmd_Suppress,429064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.SCmd_UnSuppress,429065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1DE_MF.almPLCFault.AEShelveTMRDN,429065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1DE_MF.almPLCFault.Bad,429065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1DE_MF.almPLCFault.Suppress,429066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.UnSuppress,429066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Shelve,429066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.UnShelve,429066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Enable,429066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Disable,429066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Ack,429066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Reset,429066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Suppressed,429066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Shelved,429066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Disabled,429066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Acked,429066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1DE_MF.almPLCFault.Alarm,429066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Fault,429086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1DE_XA.Alarm.AlarmState,429086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1DE_XA.Alarm.GlobalReset,429086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1DE_XA.Alarm.FaultInAlarm,429086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_XA.Alarm.ALRM,429086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1DE_XA.Alarm.ANUN,429086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1DE_XA.Alarm.AKED,429086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1DE_XA.Alarm.Resetable,429086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1DE_XA.Alarm.REST,429086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1DE_XA.Alarm.ACKN,429086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1DE_XA.Alarm.UACK,429086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1DE_XA.Alarm.MCmd_Enable,429086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_XA.Alarm.MCmd_Disable,429086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_XA.Alarm.OCmd_Shelve,429086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1DE_XA.Alarm.OCmd_Unshelve,429086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1DE_XA.Alarm.SCmd_Suppress,429086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1DE_XA.Alarm.SCmd_UnSuppress,429087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1DE_XA.Alarm.AEShelveTMRDN,429087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1DE_XA.Alarm.Bad,429087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1DE_XA.Alarm.Suppress,429088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.UnSuppress,429088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Shelve,429088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.UnShelve,429088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Enable,429088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Disable,429088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Ack,429088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Reset,429088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1DE_XA.Alarm.Suppressed,429088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1DE_XA.Alarm.Shelved,429088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1DE_XA.Alarm.Disabled,429088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1DE_XA.Alarm.Acked,429088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1DE_XA.Alarm.Alarm,429088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Fault,429098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1DE_XA.almPLCFault.AlarmState,429098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1DE_XA.almPLCFault.GlobalReset,429098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1DE_XA.almPLCFault.FaultInAlarm,429098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1DE_XA.almPLCFault.ALRM,429098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1DE_XA.almPLCFault.ANUN,429098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1DE_XA.almPLCFault.AKED,429098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1DE_XA.almPLCFault.Resetable,429098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1DE_XA.almPLCFault.REST,429098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1DE_XA.almPLCFault.ACKN,429098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1DE_XA.almPLCFault.UACK,429098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1DE_XA.almPLCFault.MCmd_Enable,429098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.MCmd_Disable,429098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.OCmd_Shelve,429098.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.OCmd_Unshelve,429098.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.SCmd_Suppress,429098.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.SCmd_UnSuppress,429099.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1DE_XA.almPLCFault.AEShelveTMRDN,429099.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1DE_XA.almPLCFault.Bad,429099.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1DE_XA.almPLCFault.Suppress,429100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.UnSuppress,429100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Shelve,429100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.UnShelve,429100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Enable,429100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Disable,429100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Ack,429100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Reset,429100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Suppressed,429100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Shelved,429100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Disabled,429100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Acked,429100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1DE_XA.almPLCFault.Alarm,429100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Fault,429122.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1FG_MF.Alarm.AlarmState,429122.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1FG_MF.Alarm.GlobalReset,429122.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1FG_MF.Alarm.FaultInAlarm,429122.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_MF.Alarm.ALRM,429122.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1FG_MF.Alarm.ANUN,429122.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1FG_MF.Alarm.AKED,429122.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1FG_MF.Alarm.Resetable,429122.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1FG_MF.Alarm.REST,429122.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1FG_MF.Alarm.ACKN,429122.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1FG_MF.Alarm.UACK,429122.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1FG_MF.Alarm.MCmd_Enable,429122.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_MF.Alarm.MCmd_Disable,429122.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_MF.Alarm.OCmd_Shelve,429122.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1FG_MF.Alarm.OCmd_Unshelve,429122.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1FG_MF.Alarm.SCmd_Suppress,429122.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1FG_MF.Alarm.SCmd_UnSuppress,429123.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1FG_MF.Alarm.AEShelveTMRDN,429123.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1FG_MF.Alarm.Bad,429123.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1FG_MF.Alarm.Suppress,429124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.UnSuppress,429124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Shelve,429124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.UnShelve,429124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Enable,429124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Disable,429124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Ack,429124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Reset,429124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1FG_MF.Alarm.Suppressed,429124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1FG_MF.Alarm.Shelved,429124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1FG_MF.Alarm.Disabled,429124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1FG_MF.Alarm.Acked,429124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1FG_MF.Alarm.Alarm,429124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Fault,429134.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1FG_MF.almPLCFault.AlarmState,429134.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1FG_MF.almPLCFault.GlobalReset,429134.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1FG_MF.almPLCFault.FaultInAlarm,429134.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_MF.almPLCFault.ALRM,429134.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1FG_MF.almPLCFault.ANUN,429134.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1FG_MF.almPLCFault.AKED,429134.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1FG_MF.almPLCFault.Resetable,429134.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1FG_MF.almPLCFault.REST,429134.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1FG_MF.almPLCFault.ACKN,429134.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1FG_MF.almPLCFault.UACK,429134.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1FG_MF.almPLCFault.MCmd_Enable,429134.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.MCmd_Disable,429134.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.OCmd_Shelve,429134.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.OCmd_Unshelve,429134.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.SCmd_Suppress,429134.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.SCmd_UnSuppress,429135.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1FG_MF.almPLCFault.AEShelveTMRDN,429135.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1FG_MF.almPLCFault.Bad,429135.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1FG_MF.almPLCFault.Suppress,429136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.UnSuppress,429136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Shelve,429136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.UnShelve,429136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Enable,429136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Disable,429136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Ack,429136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Reset,429136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Suppressed,429136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Shelved,429136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Disabled,429136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Acked,429136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1FG_MF.almPLCFault.Alarm,429136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Fault,429156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1FG_XA.Alarm.AlarmState,429156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1FG_XA.Alarm.GlobalReset,429156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1FG_XA.Alarm.FaultInAlarm,429156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_XA.Alarm.ALRM,429156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1FG_XA.Alarm.ANUN,429156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1FG_XA.Alarm.AKED,429156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1FG_XA.Alarm.Resetable,429156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1FG_XA.Alarm.REST,429156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1FG_XA.Alarm.ACKN,429156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1FG_XA.Alarm.UACK,429156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1FG_XA.Alarm.MCmd_Enable,429156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_XA.Alarm.MCmd_Disable,429156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_XA.Alarm.OCmd_Shelve,429156.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1FG_XA.Alarm.OCmd_Unshelve,429156.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1FG_XA.Alarm.SCmd_Suppress,429156.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1FG_XA.Alarm.SCmd_UnSuppress,429157.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1FG_XA.Alarm.AEShelveTMRDN,429157.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1FG_XA.Alarm.Bad,429157.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1FG_XA.Alarm.Suppress,429158.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.UnSuppress,429158.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Shelve,429158.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.UnShelve,429158.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Enable,429158.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Disable,429158.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Ack,429158.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Reset,429158.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1FG_XA.Alarm.Suppressed,429158.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1FG_XA.Alarm.Shelved,429158.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1FG_XA.Alarm.Disabled,429158.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1FG_XA.Alarm.Acked,429158.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1FG_XA.Alarm.Alarm,429158.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Fault,429168.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1FG_XA.almPLCFault.AlarmState,429168.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1FG_XA.almPLCFault.GlobalReset,429168.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1FG_XA.almPLCFault.FaultInAlarm,429168.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1FG_XA.almPLCFault.ALRM,429168.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1FG_XA.almPLCFault.ANUN,429168.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1FG_XA.almPLCFault.AKED,429168.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1FG_XA.almPLCFault.Resetable,429168.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1FG_XA.almPLCFault.REST,429168.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1FG_XA.almPLCFault.ACKN,429168.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1FG_XA.almPLCFault.UACK,429168.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1FG_XA.almPLCFault.MCmd_Enable,429168.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.MCmd_Disable,429168.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.OCmd_Shelve,429168.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.OCmd_Unshelve,429168.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.SCmd_Suppress,429168.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.SCmd_UnSuppress,429169.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1FG_XA.almPLCFault.AEShelveTMRDN,429169.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1FG_XA.almPLCFault.Bad,429169.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1FG_XA.almPLCFault.Suppress,429170.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.UnSuppress,429170.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Shelve,429170.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.UnShelve,429170.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Enable,429170.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Disable,429170.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Ack,429170.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Reset,429170.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Suppressed,429170.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Shelved,429170.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Disabled,429170.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Acked,429170.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1FG_XA.almPLCFault.Alarm,429170.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Fault,429192.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1H_MF.Alarm.AlarmState,429192.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1H_MF.Alarm.GlobalReset,429192.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1H_MF.Alarm.FaultInAlarm,429192.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_MF.Alarm.ALRM,429192.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1H_MF.Alarm.ANUN,429192.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1H_MF.Alarm.AKED,429192.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1H_MF.Alarm.Resetable,429192.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1H_MF.Alarm.REST,429192.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1H_MF.Alarm.ACKN,429192.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1H_MF.Alarm.UACK,429192.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1H_MF.Alarm.MCmd_Enable,429192.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_MF.Alarm.MCmd_Disable,429192.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_MF.Alarm.OCmd_Shelve,429192.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1H_MF.Alarm.OCmd_Unshelve,429192.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1H_MF.Alarm.SCmd_Suppress,429192.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1H_MF.Alarm.SCmd_UnSuppress,429193.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1H_MF.Alarm.AEShelveTMRDN,429193.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1H_MF.Alarm.Bad,429193.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1H_MF.Alarm.Suppress,429194.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.UnSuppress,429194.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Shelve,429194.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.UnShelve,429194.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Enable,429194.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Disable,429194.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Ack,429194.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Reset,429194.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1H_MF.Alarm.Suppressed,429194.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1H_MF.Alarm.Shelved,429194.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1H_MF.Alarm.Disabled,429194.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1H_MF.Alarm.Acked,429194.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1H_MF.Alarm.Alarm,429194.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Fault,429204.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1H_MF.almPLCFault.AlarmState,429204.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1H_MF.almPLCFault.GlobalReset,429204.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1H_MF.almPLCFault.FaultInAlarm,429204.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_MF.almPLCFault.ALRM,429204.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1H_MF.almPLCFault.ANUN,429204.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1H_MF.almPLCFault.AKED,429204.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1H_MF.almPLCFault.Resetable,429204.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1H_MF.almPLCFault.REST,429204.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1H_MF.almPLCFault.ACKN,429204.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1H_MF.almPLCFault.UACK,429204.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1H_MF.almPLCFault.MCmd_Enable,429204.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_MF.almPLCFault.MCmd_Disable,429204.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_MF.almPLCFault.OCmd_Shelve,429204.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1H_MF.almPLCFault.OCmd_Unshelve,429204.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1H_MF.almPLCFault.SCmd_Suppress,429204.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1H_MF.almPLCFault.SCmd_UnSuppress,429205.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1H_MF.almPLCFault.AEShelveTMRDN,429205.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1H_MF.almPLCFault.Bad,429205.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1H_MF.almPLCFault.Suppress,429206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.UnSuppress,429206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Shelve,429206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.UnShelve,429206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Enable,429206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Disable,429206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Ack,429206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Reset,429206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Suppressed,429206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Shelved,429206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Disabled,429206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Acked,429206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1H_MF.almPLCFault.Alarm,429206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Fault,429226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1H_XA.Alarm.AlarmState,429226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1H_XA.Alarm.GlobalReset,429226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1H_XA.Alarm.FaultInAlarm,429226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_XA.Alarm.ALRM,429226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1H_XA.Alarm.ANUN,429226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1H_XA.Alarm.AKED,429226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1H_XA.Alarm.Resetable,429226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1H_XA.Alarm.REST,429226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1H_XA.Alarm.ACKN,429226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1H_XA.Alarm.UACK,429226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1H_XA.Alarm.MCmd_Enable,429226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_XA.Alarm.MCmd_Disable,429226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_XA.Alarm.OCmd_Shelve,429226.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1H_XA.Alarm.OCmd_Unshelve,429226.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1H_XA.Alarm.SCmd_Suppress,429226.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1H_XA.Alarm.SCmd_UnSuppress,429227.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1H_XA.Alarm.AEShelveTMRDN,429227.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1H_XA.Alarm.Bad,429227.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1H_XA.Alarm.Suppress,429228.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.UnSuppress,429228.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Shelve,429228.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.UnShelve,429228.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Enable,429228.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Disable,429228.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Ack,429228.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Reset,429228.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1H_XA.Alarm.Suppressed,429228.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1H_XA.Alarm.Shelved,429228.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1H_XA.Alarm.Disabled,429228.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1H_XA.Alarm.Acked,429228.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1H_XA.Alarm.Alarm,429228.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Fault,429238.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1H_XA.almPLCFault.AlarmState,429238.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1H_XA.almPLCFault.GlobalReset,429238.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1H_XA.almPLCFault.FaultInAlarm,429238.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1H_XA.almPLCFault.ALRM,429238.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1H_XA.almPLCFault.ANUN,429238.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1H_XA.almPLCFault.AKED,429238.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1H_XA.almPLCFault.Resetable,429238.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1H_XA.almPLCFault.REST,429238.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1H_XA.almPLCFault.ACKN,429238.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1H_XA.almPLCFault.UACK,429238.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1H_XA.almPLCFault.MCmd_Enable,429238.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1H_XA.almPLCFault.MCmd_Disable,429238.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1H_XA.almPLCFault.OCmd_Shelve,429238.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1H_XA.almPLCFault.OCmd_Unshelve,429238.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1H_XA.almPLCFault.SCmd_Suppress,429238.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1H_XA.almPLCFault.SCmd_UnSuppress,429239.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1H_XA.almPLCFault.AEShelveTMRDN,429239.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1H_XA.almPLCFault.Bad,429239.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1H_XA.almPLCFault.Suppress,429240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.UnSuppress,429240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Shelve,429240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.UnShelve,429240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Enable,429240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Disable,429240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Ack,429240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Reset,429240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Suppressed,429240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Shelved,429240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Disabled,429240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Acked,429240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1H_XA.almPLCFault.Alarm,429240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Fault,429262.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1I_MF.Alarm.AlarmState,429262.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1I_MF.Alarm.GlobalReset,429262.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1I_MF.Alarm.FaultInAlarm,429262.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_MF.Alarm.ALRM,429262.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1I_MF.Alarm.ANUN,429262.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1I_MF.Alarm.AKED,429262.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1I_MF.Alarm.Resetable,429262.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1I_MF.Alarm.REST,429262.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1I_MF.Alarm.ACKN,429262.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1I_MF.Alarm.UACK,429262.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1I_MF.Alarm.MCmd_Enable,429262.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_MF.Alarm.MCmd_Disable,429262.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_MF.Alarm.OCmd_Shelve,429262.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1I_MF.Alarm.OCmd_Unshelve,429262.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1I_MF.Alarm.SCmd_Suppress,429262.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1I_MF.Alarm.SCmd_UnSuppress,429263.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1I_MF.Alarm.AEShelveTMRDN,429263.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1I_MF.Alarm.Bad,429263.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1I_MF.Alarm.Suppress,429264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.UnSuppress,429264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Shelve,429264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.UnShelve,429264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Enable,429264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Disable,429264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Ack,429264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Reset,429264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1I_MF.Alarm.Suppressed,429264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1I_MF.Alarm.Shelved,429264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1I_MF.Alarm.Disabled,429264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1I_MF.Alarm.Acked,429264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1I_MF.Alarm.Alarm,429264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Fault,429274.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1I_MF.almPLCFault.AlarmState,429274.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1I_MF.almPLCFault.GlobalReset,429274.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1I_MF.almPLCFault.FaultInAlarm,429274.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_MF.almPLCFault.ALRM,429274.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1I_MF.almPLCFault.ANUN,429274.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1I_MF.almPLCFault.AKED,429274.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1I_MF.almPLCFault.Resetable,429274.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1I_MF.almPLCFault.REST,429274.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1I_MF.almPLCFault.ACKN,429274.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1I_MF.almPLCFault.UACK,429274.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1I_MF.almPLCFault.MCmd_Enable,429274.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_MF.almPLCFault.MCmd_Disable,429274.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_MF.almPLCFault.OCmd_Shelve,429274.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1I_MF.almPLCFault.OCmd_Unshelve,429274.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1I_MF.almPLCFault.SCmd_Suppress,429274.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1I_MF.almPLCFault.SCmd_UnSuppress,429275.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1I_MF.almPLCFault.AEShelveTMRDN,429275.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1I_MF.almPLCFault.Bad,429275.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1I_MF.almPLCFault.Suppress,429276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.UnSuppress,429276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Shelve,429276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.UnShelve,429276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Enable,429276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Disable,429276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Ack,429276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Reset,429276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Suppressed,429276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Shelved,429276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Disabled,429276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Acked,429276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1I_MF.almPLCFault.Alarm,429276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Fault,429296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1I_XA.Alarm.AlarmState,429296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1I_XA.Alarm.GlobalReset,429296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1I_XA.Alarm.FaultInAlarm,429296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_XA.Alarm.ALRM,429296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1I_XA.Alarm.ANUN,429296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1I_XA.Alarm.AKED,429296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1I_XA.Alarm.Resetable,429296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1I_XA.Alarm.REST,429296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1I_XA.Alarm.ACKN,429296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1I_XA.Alarm.UACK,429296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1I_XA.Alarm.MCmd_Enable,429296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_XA.Alarm.MCmd_Disable,429296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_XA.Alarm.OCmd_Shelve,429296.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1I_XA.Alarm.OCmd_Unshelve,429296.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1I_XA.Alarm.SCmd_Suppress,429296.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1I_XA.Alarm.SCmd_UnSuppress,429297.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1I_XA.Alarm.AEShelveTMRDN,429297.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1I_XA.Alarm.Bad,429297.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1I_XA.Alarm.Suppress,429298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.UnSuppress,429298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Shelve,429298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.UnShelve,429298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Enable,429298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Disable,429298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Ack,429298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Reset,429298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1I_XA.Alarm.Suppressed,429298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1I_XA.Alarm.Shelved,429298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1I_XA.Alarm.Disabled,429298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1I_XA.Alarm.Acked,429298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1I_XA.Alarm.Alarm,429298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Fault,429308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1I_XA.almPLCFault.AlarmState,429308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1I_XA.almPLCFault.GlobalReset,429308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1I_XA.almPLCFault.FaultInAlarm,429308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1I_XA.almPLCFault.ALRM,429308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1I_XA.almPLCFault.ANUN,429308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1I_XA.almPLCFault.AKED,429308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1I_XA.almPLCFault.Resetable,429308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1I_XA.almPLCFault.REST,429308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1I_XA.almPLCFault.ACKN,429308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1I_XA.almPLCFault.UACK,429308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1I_XA.almPLCFault.MCmd_Enable,429308.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1I_XA.almPLCFault.MCmd_Disable,429308.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1I_XA.almPLCFault.OCmd_Shelve,429308.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1I_XA.almPLCFault.OCmd_Unshelve,429308.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1I_XA.almPLCFault.SCmd_Suppress,429308.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1I_XA.almPLCFault.SCmd_UnSuppress,429309.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1I_XA.almPLCFault.AEShelveTMRDN,429309.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1I_XA.almPLCFault.Bad,429309.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1I_XA.almPLCFault.Suppress,429310.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.UnSuppress,429310.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Shelve,429310.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.UnShelve,429310.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Enable,429310.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Disable,429310.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Ack,429310.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Reset,429310.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Suppressed,429310.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Shelved,429310.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Disabled,429310.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Acked,429310.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1I_XA.almPLCFault.Alarm,429310.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Fault,429332.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1J_MF.Alarm.AlarmState,429332.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1J_MF.Alarm.GlobalReset,429332.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1J_MF.Alarm.FaultInAlarm,429332.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_MF.Alarm.ALRM,429332.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1J_MF.Alarm.ANUN,429332.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1J_MF.Alarm.AKED,429332.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1J_MF.Alarm.Resetable,429332.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1J_MF.Alarm.REST,429332.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1J_MF.Alarm.ACKN,429332.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1J_MF.Alarm.UACK,429332.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1J_MF.Alarm.MCmd_Enable,429332.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_MF.Alarm.MCmd_Disable,429332.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_MF.Alarm.OCmd_Shelve,429332.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1J_MF.Alarm.OCmd_Unshelve,429332.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1J_MF.Alarm.SCmd_Suppress,429332.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1J_MF.Alarm.SCmd_UnSuppress,429333.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1J_MF.Alarm.AEShelveTMRDN,429333.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1J_MF.Alarm.Bad,429333.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1J_MF.Alarm.Suppress,429334.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.UnSuppress,429334.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Shelve,429334.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.UnShelve,429334.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Enable,429334.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Disable,429334.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Ack,429334.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Reset,429334.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1J_MF.Alarm.Suppressed,429334.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1J_MF.Alarm.Shelved,429334.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1J_MF.Alarm.Disabled,429334.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1J_MF.Alarm.Acked,429334.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1J_MF.Alarm.Alarm,429334.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Fault,429344.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1J_MF.almPLCFault.AlarmState,429344.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1J_MF.almPLCFault.GlobalReset,429344.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1J_MF.almPLCFault.FaultInAlarm,429344.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_MF.almPLCFault.ALRM,429344.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1J_MF.almPLCFault.ANUN,429344.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1J_MF.almPLCFault.AKED,429344.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1J_MF.almPLCFault.Resetable,429344.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1J_MF.almPLCFault.REST,429344.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1J_MF.almPLCFault.ACKN,429344.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1J_MF.almPLCFault.UACK,429344.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1J_MF.almPLCFault.MCmd_Enable,429344.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_MF.almPLCFault.MCmd_Disable,429344.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_MF.almPLCFault.OCmd_Shelve,429344.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1J_MF.almPLCFault.OCmd_Unshelve,429344.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1J_MF.almPLCFault.SCmd_Suppress,429344.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1J_MF.almPLCFault.SCmd_UnSuppress,429345.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1J_MF.almPLCFault.AEShelveTMRDN,429345.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1J_MF.almPLCFault.Bad,429345.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1J_MF.almPLCFault.Suppress,429346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.UnSuppress,429346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Shelve,429346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.UnShelve,429346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Enable,429346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Disable,429346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Ack,429346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Reset,429346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Suppressed,429346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Shelved,429346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Disabled,429346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Acked,429346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1J_MF.almPLCFault.Alarm,429346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Fault,429366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1J_XA.Alarm.AlarmState,429366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1J_XA.Alarm.GlobalReset,429366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1J_XA.Alarm.FaultInAlarm,429366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_XA.Alarm.ALRM,429366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1J_XA.Alarm.ANUN,429366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1J_XA.Alarm.AKED,429366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1J_XA.Alarm.Resetable,429366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1J_XA.Alarm.REST,429366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1J_XA.Alarm.ACKN,429366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1J_XA.Alarm.UACK,429366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1J_XA.Alarm.MCmd_Enable,429366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_XA.Alarm.MCmd_Disable,429366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_XA.Alarm.OCmd_Shelve,429366.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1J_XA.Alarm.OCmd_Unshelve,429366.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1J_XA.Alarm.SCmd_Suppress,429366.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1J_XA.Alarm.SCmd_UnSuppress,429367.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1J_XA.Alarm.AEShelveTMRDN,429367.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1J_XA.Alarm.Bad,429367.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1J_XA.Alarm.Suppress,429368.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.UnSuppress,429368.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Shelve,429368.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.UnShelve,429368.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Enable,429368.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Disable,429368.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Ack,429368.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Reset,429368.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1J_XA.Alarm.Suppressed,429368.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1J_XA.Alarm.Shelved,429368.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1J_XA.Alarm.Disabled,429368.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1J_XA.Alarm.Acked,429368.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1J_XA.Alarm.Alarm,429368.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Fault,429378.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1J_XA.almPLCFault.AlarmState,429378.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1J_XA.almPLCFault.GlobalReset,429378.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1J_XA.almPLCFault.FaultInAlarm,429378.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1J_XA.almPLCFault.ALRM,429378.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1J_XA.almPLCFault.ANUN,429378.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1J_XA.almPLCFault.AKED,429378.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1J_XA.almPLCFault.Resetable,429378.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1J_XA.almPLCFault.REST,429378.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1J_XA.almPLCFault.ACKN,429378.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1J_XA.almPLCFault.UACK,429378.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1J_XA.almPLCFault.MCmd_Enable,429378.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1J_XA.almPLCFault.MCmd_Disable,429378.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1J_XA.almPLCFault.OCmd_Shelve,429378.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1J_XA.almPLCFault.OCmd_Unshelve,429378.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1J_XA.almPLCFault.SCmd_Suppress,429378.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1J_XA.almPLCFault.SCmd_UnSuppress,429379.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1J_XA.almPLCFault.AEShelveTMRDN,429379.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1J_XA.almPLCFault.Bad,429379.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1J_XA.almPLCFault.Suppress,429380.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.UnSuppress,429380.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Shelve,429380.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.UnShelve,429380.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Enable,429380.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Disable,429380.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Ack,429380.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Reset,429380.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Suppressed,429380.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Shelved,429380.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Disabled,429380.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Acked,429380.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1J_XA.almPLCFault.Alarm,429380.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Fault,429402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1K_MF.Alarm.AlarmState,429402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1K_MF.Alarm.GlobalReset,429402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1K_MF.Alarm.FaultInAlarm,429402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_MF.Alarm.ALRM,429402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1K_MF.Alarm.ANUN,429402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1K_MF.Alarm.AKED,429402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1K_MF.Alarm.Resetable,429402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1K_MF.Alarm.REST,429402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1K_MF.Alarm.ACKN,429402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1K_MF.Alarm.UACK,429402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1K_MF.Alarm.MCmd_Enable,429402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_MF.Alarm.MCmd_Disable,429402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_MF.Alarm.OCmd_Shelve,429402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1K_MF.Alarm.OCmd_Unshelve,429402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1K_MF.Alarm.SCmd_Suppress,429402.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1K_MF.Alarm.SCmd_UnSuppress,429403.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1K_MF.Alarm.AEShelveTMRDN,429403.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1K_MF.Alarm.Bad,429403.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1K_MF.Alarm.Suppress,429404.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.UnSuppress,429404.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Shelve,429404.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.UnShelve,429404.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Enable,429404.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Disable,429404.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Ack,429404.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Reset,429404.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1K_MF.Alarm.Suppressed,429404.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1K_MF.Alarm.Shelved,429404.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1K_MF.Alarm.Disabled,429404.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1K_MF.Alarm.Acked,429404.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1K_MF.Alarm.Alarm,429404.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Fault,429414.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1K_MF.almPLCFault.AlarmState,429414.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1K_MF.almPLCFault.GlobalReset,429414.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1K_MF.almPLCFault.FaultInAlarm,429414.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_MF.almPLCFault.ALRM,429414.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1K_MF.almPLCFault.ANUN,429414.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1K_MF.almPLCFault.AKED,429414.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1K_MF.almPLCFault.Resetable,429414.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1K_MF.almPLCFault.REST,429414.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1K_MF.almPLCFault.ACKN,429414.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1K_MF.almPLCFault.UACK,429414.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1K_MF.almPLCFault.MCmd_Enable,429414.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_MF.almPLCFault.MCmd_Disable,429414.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_MF.almPLCFault.OCmd_Shelve,429414.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1K_MF.almPLCFault.OCmd_Unshelve,429414.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1K_MF.almPLCFault.SCmd_Suppress,429414.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1K_MF.almPLCFault.SCmd_UnSuppress,429415.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1K_MF.almPLCFault.AEShelveTMRDN,429415.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1K_MF.almPLCFault.Bad,429415.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1K_MF.almPLCFault.Suppress,429416.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.UnSuppress,429416.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Shelve,429416.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.UnShelve,429416.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Enable,429416.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Disable,429416.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Ack,429416.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Reset,429416.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Suppressed,429416.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Shelved,429416.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Disabled,429416.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Acked,429416.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1K_MF.almPLCFault.Alarm,429416.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Fault,429436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1K_XA.Alarm.AlarmState,429436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1K_XA.Alarm.GlobalReset,429436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1K_XA.Alarm.FaultInAlarm,429436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_XA.Alarm.ALRM,429436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1K_XA.Alarm.ANUN,429436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1K_XA.Alarm.AKED,429436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1K_XA.Alarm.Resetable,429436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1K_XA.Alarm.REST,429436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1K_XA.Alarm.ACKN,429436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1K_XA.Alarm.UACK,429436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1K_XA.Alarm.MCmd_Enable,429436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_XA.Alarm.MCmd_Disable,429436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_XA.Alarm.OCmd_Shelve,429436.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1K_XA.Alarm.OCmd_Unshelve,429436.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1K_XA.Alarm.SCmd_Suppress,429436.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1K_XA.Alarm.SCmd_UnSuppress,429437.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1K_XA.Alarm.AEShelveTMRDN,429437.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1K_XA.Alarm.Bad,429437.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1K_XA.Alarm.Suppress,429438.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.UnSuppress,429438.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Shelve,429438.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.UnShelve,429438.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Enable,429438.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Disable,429438.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Ack,429438.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Reset,429438.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1K_XA.Alarm.Suppressed,429438.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1K_XA.Alarm.Shelved,429438.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1K_XA.Alarm.Disabled,429438.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1K_XA.Alarm.Acked,429438.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1K_XA.Alarm.Alarm,429438.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Fault,429448.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_1K_XA.almPLCFault.AlarmState,429448.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_1K_XA.almPLCFault.GlobalReset,429448.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_1K_XA.almPLCFault.FaultInAlarm,429448.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_1K_XA.almPLCFault.ALRM,429448.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_1K_XA.almPLCFault.ANUN,429448.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_1K_XA.almPLCFault.AKED,429448.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_1K_XA.almPLCFault.Resetable,429448.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_1K_XA.almPLCFault.REST,429448.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_1K_XA.almPLCFault.ACKN,429448.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_1K_XA.almPLCFault.UACK,429448.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_1K_XA.almPLCFault.MCmd_Enable,429448.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_1K_XA.almPLCFault.MCmd_Disable,429448.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_1K_XA.almPLCFault.OCmd_Shelve,429448.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_1K_XA.almPLCFault.OCmd_Unshelve,429448.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_1K_XA.almPLCFault.SCmd_Suppress,429448.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_1K_XA.almPLCFault.SCmd_UnSuppress,429449.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_1K_XA.almPLCFault.AEShelveTMRDN,429449.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_1K_XA.almPLCFault.Bad,429449.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_1K_XA.almPLCFault.Suppress,429450.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.UnSuppress,429450.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Shelve,429450.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.UnShelve,429450.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Enable,429450.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Disable,429450.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Ack,429450.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Reset,429450.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Suppressed,429450.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Shelved,429450.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Disabled,429450.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Acked,429450.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_1K_XA.almPLCFault.Alarm,429450.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Fault,429472.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_LH.Alarm.AlarmState,429472.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_LH.Alarm.GlobalReset,429472.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_LH.Alarm.FaultInAlarm,429472.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_LH.Alarm.ALRM,429472.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_LH.Alarm.ANUN,429472.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_LH.Alarm.AKED,429472.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_LH.Alarm.Resetable,429472.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_LH.Alarm.REST,429472.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_LH.Alarm.ACKN,429472.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_LH.Alarm.UACK,429472.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_LH.Alarm.MCmd_Enable,429472.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_LH.Alarm.MCmd_Disable,429472.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_LH.Alarm.OCmd_Shelve,429472.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_LH.Alarm.OCmd_Unshelve,429472.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_LH.Alarm.SCmd_Suppress,429472.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_LH.Alarm.SCmd_UnSuppress,429473.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_LH.Alarm.AEShelveTMRDN,429473.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_LH.Alarm.Bad,429473.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_LH.Alarm.Suppress,429474.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.UnSuppress,429474.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Shelve,429474.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.UnShelve,429474.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Enable,429474.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Disable,429474.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Ack,429474.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Reset,429474.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_LH.Alarm.Suppressed,429474.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_LH.Alarm.Shelved,429474.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_LH.Alarm.Disabled,429474.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_LH.Alarm.Acked,429474.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_LH.Alarm.Alarm,429474.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Fault,429484.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_LH.almPLCFault.AlarmState,429484.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_LH.almPLCFault.GlobalReset,429484.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_LH.almPLCFault.FaultInAlarm,429484.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_LH.almPLCFault.ALRM,429484.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_LH.almPLCFault.ANUN,429484.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_LH.almPLCFault.AKED,429484.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_LH.almPLCFault.Resetable,429484.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_LH.almPLCFault.REST,429484.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_LH.almPLCFault.ACKN,429484.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_LH.almPLCFault.UACK,429484.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_LH.almPLCFault.MCmd_Enable,429484.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_LH.almPLCFault.MCmd_Disable,429484.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_LH.almPLCFault.OCmd_Shelve,429484.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_LH.almPLCFault.OCmd_Unshelve,429484.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_LH.almPLCFault.SCmd_Suppress,429484.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_LH.almPLCFault.SCmd_UnSuppress,429485.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_LH.almPLCFault.AEShelveTMRDN,429485.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_LH.almPLCFault.Bad,429485.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_LH.almPLCFault.Suppress,429486.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.UnSuppress,429486.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Shelve,429486.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.UnShelve,429486.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Enable,429486.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Disable,429486.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Ack,429486.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Reset,429486.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Suppressed,429486.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Shelved,429486.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Disabled,429486.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Acked,429486.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_LH.almPLCFault.Alarm,429486.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Fault,429506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF1.Alarm.AlarmState,429506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF1.Alarm.GlobalReset,429506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF1.Alarm.FaultInAlarm,429506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF1.Alarm.ALRM,429506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF1.Alarm.ANUN,429506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF1.Alarm.AKED,429506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF1.Alarm.Resetable,429506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF1.Alarm.REST,429506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF1.Alarm.ACKN,429506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF1.Alarm.UACK,429506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF1.Alarm.MCmd_Enable,429506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF1.Alarm.MCmd_Disable,429506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF1.Alarm.OCmd_Shelve,429506.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF1.Alarm.OCmd_Unshelve,429506.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF1.Alarm.SCmd_Suppress,429506.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF1.Alarm.SCmd_UnSuppress,429507.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF1.Alarm.AEShelveTMRDN,429507.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF1.Alarm.Bad,429507.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF1.Alarm.Suppress,429508.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.UnSuppress,429508.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Shelve,429508.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.UnShelve,429508.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Enable,429508.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Disable,429508.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Ack,429508.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Reset,429508.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF1.Alarm.Suppressed,429508.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF1.Alarm.Shelved,429508.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF1.Alarm.Disabled,429508.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF1.Alarm.Acked,429508.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF1.Alarm.Alarm,429508.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Fault,429518.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF1.almPLCFault.AlarmState,429518.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF1.almPLCFault.GlobalReset,429518.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF1.almPLCFault.FaultInAlarm,429518.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF1.almPLCFault.ALRM,429518.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF1.almPLCFault.ANUN,429518.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF1.almPLCFault.AKED,429518.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF1.almPLCFault.Resetable,429518.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF1.almPLCFault.REST,429518.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF1.almPLCFault.ACKN,429518.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF1.almPLCFault.UACK,429518.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF1.almPLCFault.MCmd_Enable,429518.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.MCmd_Disable,429518.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.OCmd_Shelve,429518.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.OCmd_Unshelve,429518.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.SCmd_Suppress,429518.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.SCmd_UnSuppress,429519.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF1.almPLCFault.AEShelveTMRDN,429519.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF1.almPLCFault.Bad,429519.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF1.almPLCFault.Suppress,429520.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.UnSuppress,429520.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Shelve,429520.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.UnShelve,429520.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Enable,429520.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Disable,429520.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Ack,429520.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Reset,429520.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Suppressed,429520.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Shelved,429520.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Disabled,429520.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Acked,429520.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF1.almPLCFault.Alarm,429520.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Fault,429542.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF2.Alarm.AlarmState,429542.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF2.Alarm.GlobalReset,429542.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF2.Alarm.FaultInAlarm,429542.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF2.Alarm.ALRM,429542.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF2.Alarm.ANUN,429542.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF2.Alarm.AKED,429542.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF2.Alarm.Resetable,429542.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF2.Alarm.REST,429542.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF2.Alarm.ACKN,429542.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF2.Alarm.UACK,429542.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF2.Alarm.MCmd_Enable,429542.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF2.Alarm.MCmd_Disable,429542.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF2.Alarm.OCmd_Shelve,429542.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF2.Alarm.OCmd_Unshelve,429542.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF2.Alarm.SCmd_Suppress,429542.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF2.Alarm.SCmd_UnSuppress,429543.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF2.Alarm.AEShelveTMRDN,429543.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF2.Alarm.Bad,429543.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF2.Alarm.Suppress,429544.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.UnSuppress,429544.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Shelve,429544.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.UnShelve,429544.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Enable,429544.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Disable,429544.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Ack,429544.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Reset,429544.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF2.Alarm.Suppressed,429544.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF2.Alarm.Shelved,429544.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF2.Alarm.Disabled,429544.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF2.Alarm.Acked,429544.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF2.Alarm.Alarm,429544.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Fault,429554.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF2.almPLCFault.AlarmState,429554.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF2.almPLCFault.GlobalReset,429554.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF2.almPLCFault.FaultInAlarm,429554.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF2.almPLCFault.ALRM,429554.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF2.almPLCFault.ANUN,429554.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF2.almPLCFault.AKED,429554.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF2.almPLCFault.Resetable,429554.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF2.almPLCFault.REST,429554.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF2.almPLCFault.ACKN,429554.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF2.almPLCFault.UACK,429554.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF2.almPLCFault.MCmd_Enable,429554.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.MCmd_Disable,429554.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.OCmd_Shelve,429554.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.OCmd_Unshelve,429554.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.SCmd_Suppress,429554.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.SCmd_UnSuppress,429555.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF2.almPLCFault.AEShelveTMRDN,429555.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF2.almPLCFault.Bad,429555.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF2.almPLCFault.Suppress,429556.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.UnSuppress,429556.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Shelve,429556.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.UnShelve,429556.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Enable,429556.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Disable,429556.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Ack,429556.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Reset,429556.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Suppressed,429556.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Shelved,429556.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Disabled,429556.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Acked,429556.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF2.almPLCFault.Alarm,429556.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Fault,429576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF3.Alarm.AlarmState,429576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF3.Alarm.GlobalReset,429576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF3.Alarm.FaultInAlarm,429576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF3.Alarm.ALRM,429576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF3.Alarm.ANUN,429576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF3.Alarm.AKED,429576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF3.Alarm.Resetable,429576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF3.Alarm.REST,429576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF3.Alarm.ACKN,429576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF3.Alarm.UACK,429576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF3.Alarm.MCmd_Enable,429576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF3.Alarm.MCmd_Disable,429576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF3.Alarm.OCmd_Shelve,429576.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF3.Alarm.OCmd_Unshelve,429576.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF3.Alarm.SCmd_Suppress,429576.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF3.Alarm.SCmd_UnSuppress,429577.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF3.Alarm.AEShelveTMRDN,429577.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF3.Alarm.Bad,429577.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF3.Alarm.Suppress,429578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.UnSuppress,429578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Shelve,429578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.UnShelve,429578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Enable,429578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Disable,429578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Ack,429578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Reset,429578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF3.Alarm.Suppressed,429578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF3.Alarm.Shelved,429578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF3.Alarm.Disabled,429578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF3.Alarm.Acked,429578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF3.Alarm.Alarm,429578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Fault,429588.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF3.almPLCFault.AlarmState,429588.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF3.almPLCFault.GlobalReset,429588.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF3.almPLCFault.FaultInAlarm,429588.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF3.almPLCFault.ALRM,429588.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF3.almPLCFault.ANUN,429588.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF3.almPLCFault.AKED,429588.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF3.almPLCFault.Resetable,429588.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF3.almPLCFault.REST,429588.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF3.almPLCFault.ACKN,429588.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF3.almPLCFault.UACK,429588.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF3.almPLCFault.MCmd_Enable,429588.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.MCmd_Disable,429588.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.OCmd_Shelve,429588.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.OCmd_Unshelve,429588.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.SCmd_Suppress,429588.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.SCmd_UnSuppress,429589.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF3.almPLCFault.AEShelveTMRDN,429589.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF3.almPLCFault.Bad,429589.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF3.almPLCFault.Suppress,429590.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.UnSuppress,429590.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Shelve,429590.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.UnShelve,429590.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Enable,429590.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Disable,429590.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Ack,429590.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Reset,429590.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Suppressed,429590.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Shelved,429590.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Disabled,429590.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Acked,429590.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF3.almPLCFault.Alarm,429590.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Fault,429612.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF4.Alarm.AlarmState,429612.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF4.Alarm.GlobalReset,429612.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF4.Alarm.FaultInAlarm,429612.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF4.Alarm.ALRM,429612.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF4.Alarm.ANUN,429612.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF4.Alarm.AKED,429612.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF4.Alarm.Resetable,429612.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF4.Alarm.REST,429612.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF4.Alarm.ACKN,429612.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF4.Alarm.UACK,429612.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF4.Alarm.MCmd_Enable,429612.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF4.Alarm.MCmd_Disable,429612.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF4.Alarm.OCmd_Shelve,429612.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF4.Alarm.OCmd_Unshelve,429612.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF4.Alarm.SCmd_Suppress,429612.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF4.Alarm.SCmd_UnSuppress,429613.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF4.Alarm.AEShelveTMRDN,429613.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF4.Alarm.Bad,429613.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF4.Alarm.Suppress,429614.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.UnSuppress,429614.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Shelve,429614.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.UnShelve,429614.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Enable,429614.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Disable,429614.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Ack,429614.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Reset,429614.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF4.Alarm.Suppressed,429614.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF4.Alarm.Shelved,429614.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF4.Alarm.Disabled,429614.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF4.Alarm.Acked,429614.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF4.Alarm.Alarm,429614.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Fault,429624.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_MF4.almPLCFault.AlarmState,429624.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_MF4.almPLCFault.GlobalReset,429624.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_MF4.almPLCFault.FaultInAlarm,429624.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_MF4.almPLCFault.ALRM,429624.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_MF4.almPLCFault.ANUN,429624.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_MF4.almPLCFault.AKED,429624.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_MF4.almPLCFault.Resetable,429624.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_MF4.almPLCFault.REST,429624.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_MF4.almPLCFault.ACKN,429624.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_MF4.almPLCFault.UACK,429624.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_MF4.almPLCFault.MCmd_Enable,429624.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.MCmd_Disable,429624.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.OCmd_Shelve,429624.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.OCmd_Unshelve,429624.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.SCmd_Suppress,429624.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.SCmd_UnSuppress,429625.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_MF4.almPLCFault.AEShelveTMRDN,429625.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_MF4.almPLCFault.Bad,429625.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_MF4.almPLCFault.Suppress,429626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.UnSuppress,429626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Shelve,429626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.UnShelve,429626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Enable,429626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Disable,429626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Ack,429626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Reset,429626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Suppressed,429626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Shelved,429626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Disabled,429626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Acked,429626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_MF4.almPLCFault.Alarm,429626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Fault,429646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_XA.Alarm.AlarmState,429646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_XA.Alarm.GlobalReset,429646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_XA.Alarm.FaultInAlarm,429646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_XA.Alarm.ALRM,429646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_XA.Alarm.ANUN,429646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_XA.Alarm.AKED,429646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_XA.Alarm.Resetable,429646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_XA.Alarm.REST,429646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_XA.Alarm.ACKN,429646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_XA.Alarm.UACK,429646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_XA.Alarm.MCmd_Enable,429646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_XA.Alarm.MCmd_Disable,429646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_XA.Alarm.OCmd_Shelve,429646.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_XA.Alarm.OCmd_Unshelve,429646.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_XA.Alarm.SCmd_Suppress,429646.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_XA.Alarm.SCmd_UnSuppress,429647.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_XA.Alarm.AEShelveTMRDN,429647.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_XA.Alarm.Bad,429647.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_XA.Alarm.Suppress,429648.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.UnSuppress,429648.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Shelve,429648.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.UnShelve,429648.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Enable,429648.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Disable,429648.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Ack,429648.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Reset,429648.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_XA.Alarm.Suppressed,429648.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_XA.Alarm.Shelved,429648.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_XA.Alarm.Disabled,429648.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_XA.Alarm.Acked,429648.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_XA.Alarm.Alarm,429648.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Fault,429658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2A_XA.almPLCFault.AlarmState,429658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2A_XA.almPLCFault.GlobalReset,429658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2A_XA.almPLCFault.FaultInAlarm,429658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2A_XA.almPLCFault.ALRM,429658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2A_XA.almPLCFault.ANUN,429658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2A_XA.almPLCFault.AKED,429658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2A_XA.almPLCFault.Resetable,429658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2A_XA.almPLCFault.REST,429658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2A_XA.almPLCFault.ACKN,429658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2A_XA.almPLCFault.UACK,429658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2A_XA.almPLCFault.MCmd_Enable,429658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2A_XA.almPLCFault.MCmd_Disable,429658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2A_XA.almPLCFault.OCmd_Shelve,429658.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2A_XA.almPLCFault.OCmd_Unshelve,429658.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2A_XA.almPLCFault.SCmd_Suppress,429658.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2A_XA.almPLCFault.SCmd_UnSuppress,429659.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2A_XA.almPLCFault.AEShelveTMRDN,429659.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2A_XA.almPLCFault.Bad,429659.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2A_XA.almPLCFault.Suppress,429660.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.UnSuppress,429660.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Shelve,429660.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.UnShelve,429660.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Enable,429660.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Disable,429660.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Ack,429660.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Reset,429660.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Suppressed,429660.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Shelved,429660.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Disabled,429660.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Acked,429660.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2A_XA.almPLCFault.Alarm,429660.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Fault,429682.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_LH.Alarm.AlarmState,429682.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_LH.Alarm.GlobalReset,429682.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_LH.Alarm.FaultInAlarm,429682.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_LH.Alarm.ALRM,429682.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_LH.Alarm.ANUN,429682.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_LH.Alarm.AKED,429682.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_LH.Alarm.Resetable,429682.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_LH.Alarm.REST,429682.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_LH.Alarm.ACKN,429682.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_LH.Alarm.UACK,429682.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_LH.Alarm.MCmd_Enable,429682.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_LH.Alarm.MCmd_Disable,429682.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_LH.Alarm.OCmd_Shelve,429682.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_LH.Alarm.OCmd_Unshelve,429682.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_LH.Alarm.SCmd_Suppress,429682.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_LH.Alarm.SCmd_UnSuppress,429683.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_LH.Alarm.AEShelveTMRDN,429683.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_LH.Alarm.Bad,429683.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_LH.Alarm.Suppress,429684.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.UnSuppress,429684.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Shelve,429684.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.UnShelve,429684.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Enable,429684.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Disable,429684.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Ack,429684.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Reset,429684.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_LH.Alarm.Suppressed,429684.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_LH.Alarm.Shelved,429684.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_LH.Alarm.Disabled,429684.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_LH.Alarm.Acked,429684.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_LH.Alarm.Alarm,429684.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Fault,429694.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_LH.almPLCFault.AlarmState,429694.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_LH.almPLCFault.GlobalReset,429694.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_LH.almPLCFault.FaultInAlarm,429694.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_LH.almPLCFault.ALRM,429694.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_LH.almPLCFault.ANUN,429694.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_LH.almPLCFault.AKED,429694.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_LH.almPLCFault.Resetable,429694.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_LH.almPLCFault.REST,429694.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_LH.almPLCFault.ACKN,429694.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_LH.almPLCFault.UACK,429694.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_LH.almPLCFault.MCmd_Enable,429694.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_LH.almPLCFault.MCmd_Disable,429694.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_LH.almPLCFault.OCmd_Shelve,429694.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_LH.almPLCFault.OCmd_Unshelve,429694.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_LH.almPLCFault.SCmd_Suppress,429694.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_LH.almPLCFault.SCmd_UnSuppress,429695.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_LH.almPLCFault.AEShelveTMRDN,429695.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_LH.almPLCFault.Bad,429695.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_LH.almPLCFault.Suppress,429696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.UnSuppress,429696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Shelve,429696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.UnShelve,429696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Enable,429696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Disable,429696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Ack,429696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Reset,429696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Suppressed,429696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Shelved,429696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Disabled,429696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Acked,429696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_LH.almPLCFault.Alarm,429696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Fault,429716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF1.Alarm.AlarmState,429716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF1.Alarm.GlobalReset,429716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF1.Alarm.FaultInAlarm,429716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF1.Alarm.ALRM,429716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF1.Alarm.ANUN,429716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF1.Alarm.AKED,429716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF1.Alarm.Resetable,429716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF1.Alarm.REST,429716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF1.Alarm.ACKN,429716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF1.Alarm.UACK,429716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF1.Alarm.MCmd_Enable,429716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF1.Alarm.MCmd_Disable,429716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF1.Alarm.OCmd_Shelve,429716.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF1.Alarm.OCmd_Unshelve,429716.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF1.Alarm.SCmd_Suppress,429716.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF1.Alarm.SCmd_UnSuppress,429717.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF1.Alarm.AEShelveTMRDN,429717.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF1.Alarm.Bad,429717.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF1.Alarm.Suppress,429718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.UnSuppress,429718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Shelve,429718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.UnShelve,429718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Enable,429718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Disable,429718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Ack,429718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Reset,429718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF1.Alarm.Suppressed,429718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF1.Alarm.Shelved,429718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF1.Alarm.Disabled,429718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF1.Alarm.Acked,429718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF1.Alarm.Alarm,429718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Fault,429728.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF1.almPLCFault.AlarmState,429728.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF1.almPLCFault.GlobalReset,429728.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF1.almPLCFault.FaultInAlarm,429728.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF1.almPLCFault.ALRM,429728.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF1.almPLCFault.ANUN,429728.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF1.almPLCFault.AKED,429728.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF1.almPLCFault.Resetable,429728.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF1.almPLCFault.REST,429728.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF1.almPLCFault.ACKN,429728.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF1.almPLCFault.UACK,429728.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF1.almPLCFault.MCmd_Enable,429728.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.MCmd_Disable,429728.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.OCmd_Shelve,429728.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.OCmd_Unshelve,429728.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.SCmd_Suppress,429728.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.SCmd_UnSuppress,429729.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF1.almPLCFault.AEShelveTMRDN,429729.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF1.almPLCFault.Bad,429729.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF1.almPLCFault.Suppress,429730.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.UnSuppress,429730.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Shelve,429730.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.UnShelve,429730.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Enable,429730.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Disable,429730.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Ack,429730.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Reset,429730.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Suppressed,429730.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Shelved,429730.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Disabled,429730.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Acked,429730.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF1.almPLCFault.Alarm,429730.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Fault,429752.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF2.Alarm.AlarmState,429752.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF2.Alarm.GlobalReset,429752.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF2.Alarm.FaultInAlarm,429752.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF2.Alarm.ALRM,429752.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF2.Alarm.ANUN,429752.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF2.Alarm.AKED,429752.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF2.Alarm.Resetable,429752.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF2.Alarm.REST,429752.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF2.Alarm.ACKN,429752.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF2.Alarm.UACK,429752.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF2.Alarm.MCmd_Enable,429752.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF2.Alarm.MCmd_Disable,429752.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF2.Alarm.OCmd_Shelve,429752.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF2.Alarm.OCmd_Unshelve,429752.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF2.Alarm.SCmd_Suppress,429752.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF2.Alarm.SCmd_UnSuppress,429753.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF2.Alarm.AEShelveTMRDN,429753.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF2.Alarm.Bad,429753.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF2.Alarm.Suppress,429754.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.UnSuppress,429754.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Shelve,429754.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.UnShelve,429754.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Enable,429754.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Disable,429754.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Ack,429754.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Reset,429754.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF2.Alarm.Suppressed,429754.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF2.Alarm.Shelved,429754.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF2.Alarm.Disabled,429754.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF2.Alarm.Acked,429754.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF2.Alarm.Alarm,429754.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Fault,429764.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF2.almPLCFault.AlarmState,429764.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF2.almPLCFault.GlobalReset,429764.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF2.almPLCFault.FaultInAlarm,429764.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF2.almPLCFault.ALRM,429764.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF2.almPLCFault.ANUN,429764.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF2.almPLCFault.AKED,429764.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF2.almPLCFault.Resetable,429764.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF2.almPLCFault.REST,429764.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF2.almPLCFault.ACKN,429764.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF2.almPLCFault.UACK,429764.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF2.almPLCFault.MCmd_Enable,429764.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.MCmd_Disable,429764.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.OCmd_Shelve,429764.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.OCmd_Unshelve,429764.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.SCmd_Suppress,429764.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.SCmd_UnSuppress,429765.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF2.almPLCFault.AEShelveTMRDN,429765.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF2.almPLCFault.Bad,429765.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF2.almPLCFault.Suppress,429766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.UnSuppress,429766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Shelve,429766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.UnShelve,429766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Enable,429766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Disable,429766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Ack,429766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Reset,429766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Suppressed,429766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Shelved,429766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Disabled,429766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Acked,429766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF2.almPLCFault.Alarm,429766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Fault,429786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF3.Alarm.AlarmState,429786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF3.Alarm.GlobalReset,429786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF3.Alarm.FaultInAlarm,429786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF3.Alarm.ALRM,429786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF3.Alarm.ANUN,429786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF3.Alarm.AKED,429786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF3.Alarm.Resetable,429786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF3.Alarm.REST,429786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF3.Alarm.ACKN,429786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF3.Alarm.UACK,429786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF3.Alarm.MCmd_Enable,429786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF3.Alarm.MCmd_Disable,429786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF3.Alarm.OCmd_Shelve,429786.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF3.Alarm.OCmd_Unshelve,429786.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF3.Alarm.SCmd_Suppress,429786.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF3.Alarm.SCmd_UnSuppress,429787.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF3.Alarm.AEShelveTMRDN,429787.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF3.Alarm.Bad,429787.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF3.Alarm.Suppress,429788.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.UnSuppress,429788.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Shelve,429788.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.UnShelve,429788.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Enable,429788.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Disable,429788.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Ack,429788.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Reset,429788.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF3.Alarm.Suppressed,429788.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF3.Alarm.Shelved,429788.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF3.Alarm.Disabled,429788.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF3.Alarm.Acked,429788.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF3.Alarm.Alarm,429788.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Fault,429798.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF3.almPLCFault.AlarmState,429798.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF3.almPLCFault.GlobalReset,429798.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF3.almPLCFault.FaultInAlarm,429798.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF3.almPLCFault.ALRM,429798.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF3.almPLCFault.ANUN,429798.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF3.almPLCFault.AKED,429798.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF3.almPLCFault.Resetable,429798.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF3.almPLCFault.REST,429798.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF3.almPLCFault.ACKN,429798.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF3.almPLCFault.UACK,429798.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF3.almPLCFault.MCmd_Enable,429798.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.MCmd_Disable,429798.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.OCmd_Shelve,429798.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.OCmd_Unshelve,429798.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.SCmd_Suppress,429798.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.SCmd_UnSuppress,429799.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF3.almPLCFault.AEShelveTMRDN,429799.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF3.almPLCFault.Bad,429799.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF3.almPLCFault.Suppress,429800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.UnSuppress,429800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Shelve,429800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.UnShelve,429800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Enable,429800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Disable,429800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Ack,429800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Reset,429800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Suppressed,429800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Shelved,429800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Disabled,429800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Acked,429800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF3.almPLCFault.Alarm,429800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Fault,429822.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF4.Alarm.AlarmState,429822.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF4.Alarm.GlobalReset,429822.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF4.Alarm.FaultInAlarm,429822.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF4.Alarm.ALRM,429822.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF4.Alarm.ANUN,429822.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF4.Alarm.AKED,429822.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF4.Alarm.Resetable,429822.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF4.Alarm.REST,429822.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF4.Alarm.ACKN,429822.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF4.Alarm.UACK,429822.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF4.Alarm.MCmd_Enable,429822.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF4.Alarm.MCmd_Disable,429822.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF4.Alarm.OCmd_Shelve,429822.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF4.Alarm.OCmd_Unshelve,429822.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF4.Alarm.SCmd_Suppress,429822.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF4.Alarm.SCmd_UnSuppress,429823.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF4.Alarm.AEShelveTMRDN,429823.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF4.Alarm.Bad,429823.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF4.Alarm.Suppress,429824.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.UnSuppress,429824.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Shelve,429824.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.UnShelve,429824.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Enable,429824.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Disable,429824.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Ack,429824.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Reset,429824.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF4.Alarm.Suppressed,429824.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF4.Alarm.Shelved,429824.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF4.Alarm.Disabled,429824.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF4.Alarm.Acked,429824.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF4.Alarm.Alarm,429824.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Fault,429834.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_MF4.almPLCFault.AlarmState,429834.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_MF4.almPLCFault.GlobalReset,429834.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_MF4.almPLCFault.FaultInAlarm,429834.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_MF4.almPLCFault.ALRM,429834.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_MF4.almPLCFault.ANUN,429834.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_MF4.almPLCFault.AKED,429834.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_MF4.almPLCFault.Resetable,429834.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_MF4.almPLCFault.REST,429834.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_MF4.almPLCFault.ACKN,429834.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_MF4.almPLCFault.UACK,429834.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_MF4.almPLCFault.MCmd_Enable,429834.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.MCmd_Disable,429834.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.OCmd_Shelve,429834.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.OCmd_Unshelve,429834.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.SCmd_Suppress,429834.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.SCmd_UnSuppress,429835.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_MF4.almPLCFault.AEShelveTMRDN,429835.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_MF4.almPLCFault.Bad,429835.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_MF4.almPLCFault.Suppress,429836.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.UnSuppress,429836.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Shelve,429836.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.UnShelve,429836.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Enable,429836.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Disable,429836.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Ack,429836.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Reset,429836.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Suppressed,429836.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Shelved,429836.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Disabled,429836.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Acked,429836.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_MF4.almPLCFault.Alarm,429836.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Fault,429856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_XA.Alarm.AlarmState,429856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_XA.Alarm.GlobalReset,429856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_XA.Alarm.FaultInAlarm,429856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_XA.Alarm.ALRM,429856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_XA.Alarm.ANUN,429856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_XA.Alarm.AKED,429856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_XA.Alarm.Resetable,429856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_XA.Alarm.REST,429856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_XA.Alarm.ACKN,429856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_XA.Alarm.UACK,429856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_XA.Alarm.MCmd_Enable,429856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_XA.Alarm.MCmd_Disable,429856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_XA.Alarm.OCmd_Shelve,429856.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_XA.Alarm.OCmd_Unshelve,429856.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_XA.Alarm.SCmd_Suppress,429856.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_XA.Alarm.SCmd_UnSuppress,429857.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_XA.Alarm.AEShelveTMRDN,429857.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_XA.Alarm.Bad,429857.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_XA.Alarm.Suppress,429858.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.UnSuppress,429858.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Shelve,429858.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.UnShelve,429858.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Enable,429858.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Disable,429858.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Ack,429858.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Reset,429858.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_XA.Alarm.Suppressed,429858.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_XA.Alarm.Shelved,429858.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_XA.Alarm.Disabled,429858.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_XA.Alarm.Acked,429858.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_XA.Alarm.Alarm,429858.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Fault,429868.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_2B_XA.almPLCFault.AlarmState,429868.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_2B_XA.almPLCFault.GlobalReset,429868.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_2B_XA.almPLCFault.FaultInAlarm,429868.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_2B_XA.almPLCFault.ALRM,429868.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_2B_XA.almPLCFault.ANUN,429868.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_2B_XA.almPLCFault.AKED,429868.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_2B_XA.almPLCFault.Resetable,429868.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_2B_XA.almPLCFault.REST,429868.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_2B_XA.almPLCFault.ACKN,429868.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_2B_XA.almPLCFault.UACK,429868.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_2B_XA.almPLCFault.MCmd_Enable,429868.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_2B_XA.almPLCFault.MCmd_Disable,429868.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_2B_XA.almPLCFault.OCmd_Shelve,429868.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_2B_XA.almPLCFault.OCmd_Unshelve,429868.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_2B_XA.almPLCFault.SCmd_Suppress,429868.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_2B_XA.almPLCFault.SCmd_UnSuppress,429869.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_2B_XA.almPLCFault.AEShelveTMRDN,429869.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_2B_XA.almPLCFault.Bad,429869.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_2B_XA.almPLCFault.Suppress,429870.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.UnSuppress,429870.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Shelve,429870.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.UnShelve,429870.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Enable,429870.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Disable,429870.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Ack,429870.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Reset,429870.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Suppressed,429870.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Shelved,429870.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Disabled,429870.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Acked,429870.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_2B_XA.almPLCFault.Alarm,429870.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Fault,429892.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_3A_MF.Alarm.AlarmState,429892.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_3A_MF.Alarm.GlobalReset,429892.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_3A_MF.Alarm.FaultInAlarm,429892.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3A_MF.Alarm.ALRM,429892.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_3A_MF.Alarm.ANUN,429892.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_3A_MF.Alarm.AKED,429892.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_3A_MF.Alarm.Resetable,429892.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_3A_MF.Alarm.REST,429892.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_3A_MF.Alarm.ACKN,429892.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_3A_MF.Alarm.UACK,429892.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_3A_MF.Alarm.MCmd_Enable,429892.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3A_MF.Alarm.MCmd_Disable,429892.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3A_MF.Alarm.OCmd_Shelve,429892.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_3A_MF.Alarm.OCmd_Unshelve,429892.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_3A_MF.Alarm.SCmd_Suppress,429892.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_3A_MF.Alarm.SCmd_UnSuppress,429893.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_3A_MF.Alarm.AEShelveTMRDN,429893.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_3A_MF.Alarm.Bad,429893.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_3A_MF.Alarm.Suppress,429894.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.UnSuppress,429894.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Shelve,429894.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.UnShelve,429894.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Enable,429894.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Disable,429894.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Ack,429894.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Reset,429894.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_3A_MF.Alarm.Suppressed,429894.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_3A_MF.Alarm.Shelved,429894.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_3A_MF.Alarm.Disabled,429894.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_3A_MF.Alarm.Acked,429894.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_3A_MF.Alarm.Alarm,429894.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Fault,429904.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_3A_MF.almPLCFault.AlarmState,429904.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_3A_MF.almPLCFault.GlobalReset,429904.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_3A_MF.almPLCFault.FaultInAlarm,429904.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3A_MF.almPLCFault.ALRM,429904.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_3A_MF.almPLCFault.ANUN,429904.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_3A_MF.almPLCFault.AKED,429904.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_3A_MF.almPLCFault.Resetable,429904.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_3A_MF.almPLCFault.REST,429904.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_3A_MF.almPLCFault.ACKN,429904.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_3A_MF.almPLCFault.UACK,429904.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_3A_MF.almPLCFault.MCmd_Enable,429904.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3A_MF.almPLCFault.MCmd_Disable,429904.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3A_MF.almPLCFault.OCmd_Shelve,429904.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_3A_MF.almPLCFault.OCmd_Unshelve,429904.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_3A_MF.almPLCFault.SCmd_Suppress,429904.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_3A_MF.almPLCFault.SCmd_UnSuppress,429905.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_3A_MF.almPLCFault.AEShelveTMRDN,429905.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_3A_MF.almPLCFault.Bad,429905.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_3A_MF.almPLCFault.Suppress,429906.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.UnSuppress,429906.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Shelve,429906.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.UnShelve,429906.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Enable,429906.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Disable,429906.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Ack,429906.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Reset,429906.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Suppressed,429906.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Shelved,429906.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Disabled,429906.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Acked,429906.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_3A_MF.almPLCFault.Alarm,429906.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Fault,429926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_3B_XF.Alarm.AlarmState,429926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_3B_XF.Alarm.GlobalReset,429926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_3B_XF.Alarm.FaultInAlarm,429926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3B_XF.Alarm.ALRM,429926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_3B_XF.Alarm.ANUN,429926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_3B_XF.Alarm.AKED,429926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_3B_XF.Alarm.Resetable,429926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_3B_XF.Alarm.REST,429926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_3B_XF.Alarm.ACKN,429926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_3B_XF.Alarm.UACK,429926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_3B_XF.Alarm.MCmd_Enable,429926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3B_XF.Alarm.MCmd_Disable,429926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3B_XF.Alarm.OCmd_Shelve,429926.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_3B_XF.Alarm.OCmd_Unshelve,429926.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_3B_XF.Alarm.SCmd_Suppress,429926.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_3B_XF.Alarm.SCmd_UnSuppress,429927.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_3B_XF.Alarm.AEShelveTMRDN,429927.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_3B_XF.Alarm.Bad,429927.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_3B_XF.Alarm.Suppress,429928.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.UnSuppress,429928.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Shelve,429928.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.UnShelve,429928.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Enable,429928.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Disable,429928.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Ack,429928.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Reset,429928.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_3B_XF.Alarm.Suppressed,429928.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_3B_XF.Alarm.Shelved,429928.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_3B_XF.Alarm.Disabled,429928.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_3B_XF.Alarm.Acked,429928.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_3B_XF.Alarm.Alarm,429928.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Fault,429938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0117_3B_XF.almPLCFault.AlarmState,429938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0117_3B_XF.almPLCFault.GlobalReset,429938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0117_3B_XF.almPLCFault.FaultInAlarm,429938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0117_3B_XF.almPLCFault.ALRM,429938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0117_3B_XF.almPLCFault.ANUN,429938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0117_3B_XF.almPLCFault.AKED,429938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0117_3B_XF.almPLCFault.Resetable,429938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0117_3B_XF.almPLCFault.REST,429938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0117_3B_XF.almPLCFault.ACKN,429938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0117_3B_XF.almPLCFault.UACK,429938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0117_3B_XF.almPLCFault.MCmd_Enable,429938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0117_3B_XF.almPLCFault.MCmd_Disable,429938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0117_3B_XF.almPLCFault.OCmd_Shelve,429938.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0117_3B_XF.almPLCFault.OCmd_Unshelve,429938.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0117_3B_XF.almPLCFault.SCmd_Suppress,429938.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0117_3B_XF.almPLCFault.SCmd_UnSuppress,429939.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0117_3B_XF.almPLCFault.AEShelveTMRDN,429939.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0117_3B_XF.almPLCFault.Bad,429939.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0117_3B_XF.almPLCFault.Suppress,429940.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.UnSuppress,429940.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Shelve,429940.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.UnShelve,429940.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Enable,429940.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Disable,429940.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Ack,429940.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Reset,429940.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Suppressed,429940.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Shelved,429940.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Disabled,429940.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Acked,429940.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0117_3B_XF.almPLCFault.Alarm,429940.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Fault,429962.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_LH1.Alarm.AlarmState,429962.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_LH1.Alarm.GlobalReset,429962.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_LH1.Alarm.FaultInAlarm,429962.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH1.Alarm.ALRM,429962.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_LH1.Alarm.ANUN,429962.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_LH1.Alarm.AKED,429962.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_LH1.Alarm.Resetable,429962.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_LH1.Alarm.REST,429962.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_LH1.Alarm.ACKN,429962.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_LH1.Alarm.UACK,429962.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_LH1.Alarm.MCmd_Enable,429962.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH1.Alarm.MCmd_Disable,429962.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH1.Alarm.OCmd_Shelve,429962.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_LH1.Alarm.OCmd_Unshelve,429962.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_LH1.Alarm.SCmd_Suppress,429962.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_LH1.Alarm.SCmd_UnSuppress,429963.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_LH1.Alarm.AEShelveTMRDN,429963.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_LH1.Alarm.Bad,429963.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_LH1.Alarm.Suppress,429964.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.UnSuppress,429964.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Shelve,429964.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.UnShelve,429964.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Enable,429964.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Disable,429964.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Ack,429964.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Reset,429964.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_LH1.Alarm.Suppressed,429964.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_LH1.Alarm.Shelved,429964.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_LH1.Alarm.Disabled,429964.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_LH1.Alarm.Acked,429964.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_LH1.Alarm.Alarm,429964.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Fault,429974.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_LH1.almPLCFault.AlarmState,429974.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_LH1.almPLCFault.GlobalReset,429974.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_LH1.almPLCFault.FaultInAlarm,429974.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH1.almPLCFault.ALRM,429974.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_LH1.almPLCFault.ANUN,429974.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_LH1.almPLCFault.AKED,429974.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_LH1.almPLCFault.Resetable,429974.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_LH1.almPLCFault.REST,429974.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_LH1.almPLCFault.ACKN,429974.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_LH1.almPLCFault.UACK,429974.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_LH1.almPLCFault.MCmd_Enable,429974.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH1.almPLCFault.MCmd_Disable,429974.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH1.almPLCFault.OCmd_Shelve,429974.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_LH1.almPLCFault.OCmd_Unshelve,429974.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_LH1.almPLCFault.SCmd_Suppress,429974.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_LH1.almPLCFault.SCmd_UnSuppress,429975.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_LH1.almPLCFault.AEShelveTMRDN,429975.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_LH1.almPLCFault.Bad,429975.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_LH1.almPLCFault.Suppress,429976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.UnSuppress,429976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Shelve,429976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.UnShelve,429976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Enable,429976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Disable,429976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Ack,429976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Reset,429976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Suppressed,429976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Shelved,429976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Disabled,429976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Acked,429976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_LH1.almPLCFault.Alarm,429976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Fault,429996.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_LH2.Alarm.AlarmState,429996.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_LH2.Alarm.GlobalReset,429996.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_LH2.Alarm.FaultInAlarm,429996.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH2.Alarm.ALRM,429996.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_LH2.Alarm.ANUN,429996.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_LH2.Alarm.AKED,429996.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_LH2.Alarm.Resetable,429996.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_LH2.Alarm.REST,429996.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_LH2.Alarm.ACKN,429996.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_LH2.Alarm.UACK,429996.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_LH2.Alarm.MCmd_Enable,429996.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH2.Alarm.MCmd_Disable,429996.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH2.Alarm.OCmd_Shelve,429996.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_LH2.Alarm.OCmd_Unshelve,429996.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_LH2.Alarm.SCmd_Suppress,429996.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_LH2.Alarm.SCmd_UnSuppress,429997.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_LH2.Alarm.AEShelveTMRDN,429997.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_LH2.Alarm.Bad,429997.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_LH2.Alarm.Suppress,429998.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.UnSuppress,429998.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Shelve,429998.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.UnShelve,429998.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Enable,429998.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Disable,429998.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Ack,429998.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Reset,429998.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_LH2.Alarm.Suppressed,429998.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_LH2.Alarm.Shelved,429998.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_LH2.Alarm.Disabled,429998.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_LH2.Alarm.Acked,429998.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_LH2.Alarm.Alarm,429998.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Fault,430008.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_LH2.almPLCFault.AlarmState,430008.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_LH2.almPLCFault.GlobalReset,430008.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_LH2.almPLCFault.FaultInAlarm,430008.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_LH2.almPLCFault.ALRM,430008.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_LH2.almPLCFault.ANUN,430008.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_LH2.almPLCFault.AKED,430008.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_LH2.almPLCFault.Resetable,430008.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_LH2.almPLCFault.REST,430008.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_LH2.almPLCFault.ACKN,430008.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_LH2.almPLCFault.UACK,430008.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_LH2.almPLCFault.MCmd_Enable,430008.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_LH2.almPLCFault.MCmd_Disable,430008.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_LH2.almPLCFault.OCmd_Shelve,430008.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_LH2.almPLCFault.OCmd_Unshelve,430008.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_LH2.almPLCFault.SCmd_Suppress,430008.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_LH2.almPLCFault.SCmd_UnSuppress,430009.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_LH2.almPLCFault.AEShelveTMRDN,430009.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_LH2.almPLCFault.Bad,430009.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_LH2.almPLCFault.Suppress,430010.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.UnSuppress,430010.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Shelve,430010.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.UnShelve,430010.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Enable,430010.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Disable,430010.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Ack,430010.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Reset,430010.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Suppressed,430010.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Shelved,430010.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Disabled,430010.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Acked,430010.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_LH2.almPLCFault.Alarm,430010.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Fault,430032.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_XA.Alarm.AlarmState,430032.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_XA.Alarm.GlobalReset,430032.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_XA.Alarm.FaultInAlarm,430032.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_XA.Alarm.ALRM,430032.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_XA.Alarm.ANUN,430032.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_XA.Alarm.AKED,430032.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_XA.Alarm.Resetable,430032.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_XA.Alarm.REST,430032.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_XA.Alarm.ACKN,430032.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_XA.Alarm.UACK,430032.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_XA.Alarm.MCmd_Enable,430032.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_XA.Alarm.MCmd_Disable,430032.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_XA.Alarm.OCmd_Shelve,430032.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_XA.Alarm.OCmd_Unshelve,430032.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_XA.Alarm.SCmd_Suppress,430032.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_XA.Alarm.SCmd_UnSuppress,430033.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_XA.Alarm.AEShelveTMRDN,430033.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_XA.Alarm.Bad,430033.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_XA.Alarm.Suppress,430034.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.UnSuppress,430034.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Shelve,430034.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.UnShelve,430034.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Enable,430034.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Disable,430034.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Ack,430034.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Reset,430034.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_XA.Alarm.Suppressed,430034.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_XA.Alarm.Shelved,430034.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_XA.Alarm.Disabled,430034.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_XA.Alarm.Acked,430034.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_XA.Alarm.Alarm,430034.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Fault,430044.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1_XA.almPLCFault.AlarmState,430044.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1_XA.almPLCFault.GlobalReset,430044.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1_XA.almPLCFault.FaultInAlarm,430044.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1_XA.almPLCFault.ALRM,430044.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1_XA.almPLCFault.ANUN,430044.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1_XA.almPLCFault.AKED,430044.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1_XA.almPLCFault.Resetable,430044.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1_XA.almPLCFault.REST,430044.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1_XA.almPLCFault.ACKN,430044.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1_XA.almPLCFault.UACK,430044.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1_XA.almPLCFault.MCmd_Enable,430044.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1_XA.almPLCFault.MCmd_Disable,430044.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1_XA.almPLCFault.OCmd_Shelve,430044.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1_XA.almPLCFault.OCmd_Unshelve,430044.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1_XA.almPLCFault.SCmd_Suppress,430044.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1_XA.almPLCFault.SCmd_UnSuppress,430045.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1_XA.almPLCFault.AEShelveTMRDN,430045.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1_XA.almPLCFault.Bad,430045.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1_XA.almPLCFault.Suppress,430046.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.UnSuppress,430046.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Shelve,430046.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.UnShelve,430046.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Enable,430046.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Disable,430046.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Ack,430046.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Reset,430046.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1_XA.almPLCFault.Suppressed,430046.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1_XA.almPLCFault.Shelved,430046.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1_XA.almPLCFault.Disabled,430046.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1_XA.almPLCFault.Acked,430046.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1_XA.almPLCFault.Alarm,430046.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Fault,430066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1A_MF.Alarm.AlarmState,430066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1A_MF.Alarm.GlobalReset,430066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1A_MF.Alarm.FaultInAlarm,430066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1A_MF.Alarm.ALRM,430066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1A_MF.Alarm.ANUN,430066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1A_MF.Alarm.AKED,430066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1A_MF.Alarm.Resetable,430066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1A_MF.Alarm.REST,430066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1A_MF.Alarm.ACKN,430066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1A_MF.Alarm.UACK,430066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1A_MF.Alarm.MCmd_Enable,430066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1A_MF.Alarm.MCmd_Disable,430066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1A_MF.Alarm.OCmd_Shelve,430066.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1A_MF.Alarm.OCmd_Unshelve,430066.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1A_MF.Alarm.SCmd_Suppress,430066.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1A_MF.Alarm.SCmd_UnSuppress,430067.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1A_MF.Alarm.AEShelveTMRDN,430067.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1A_MF.Alarm.Bad,430067.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1A_MF.Alarm.Suppress,430068.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.UnSuppress,430068.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Shelve,430068.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.UnShelve,430068.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Enable,430068.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Disable,430068.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Ack,430068.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Reset,430068.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1A_MF.Alarm.Suppressed,430068.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1A_MF.Alarm.Shelved,430068.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1A_MF.Alarm.Disabled,430068.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1A_MF.Alarm.Acked,430068.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1A_MF.Alarm.Alarm,430068.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Fault,430078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1A_MF.almPLCFault.AlarmState,430078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1A_MF.almPLCFault.GlobalReset,430078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1A_MF.almPLCFault.FaultInAlarm,430078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1A_MF.almPLCFault.ALRM,430078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1A_MF.almPLCFault.ANUN,430078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1A_MF.almPLCFault.AKED,430078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1A_MF.almPLCFault.Resetable,430078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1A_MF.almPLCFault.REST,430078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1A_MF.almPLCFault.ACKN,430078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1A_MF.almPLCFault.UACK,430078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1A_MF.almPLCFault.MCmd_Enable,430078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1A_MF.almPLCFault.MCmd_Disable,430078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1A_MF.almPLCFault.OCmd_Shelve,430078.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1A_MF.almPLCFault.OCmd_Unshelve,430078.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1A_MF.almPLCFault.SCmd_Suppress,430078.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1A_MF.almPLCFault.SCmd_UnSuppress,430079.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1A_MF.almPLCFault.AEShelveTMRDN,430079.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1A_MF.almPLCFault.Bad,430079.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1A_MF.almPLCFault.Suppress,430080.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.UnSuppress,430080.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Shelve,430080.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.UnShelve,430080.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Enable,430080.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Disable,430080.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Ack,430080.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Reset,430080.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Suppressed,430080.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Shelved,430080.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Disabled,430080.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Acked,430080.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1A_MF.almPLCFault.Alarm,430080.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Fault,430102.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1B_MF.Alarm.AlarmState,430102.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1B_MF.Alarm.GlobalReset,430102.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1B_MF.Alarm.FaultInAlarm,430102.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1B_MF.Alarm.ALRM,430102.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1B_MF.Alarm.ANUN,430102.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1B_MF.Alarm.AKED,430102.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1B_MF.Alarm.Resetable,430102.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1B_MF.Alarm.REST,430102.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1B_MF.Alarm.ACKN,430102.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1B_MF.Alarm.UACK,430102.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1B_MF.Alarm.MCmd_Enable,430102.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1B_MF.Alarm.MCmd_Disable,430102.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1B_MF.Alarm.OCmd_Shelve,430102.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1B_MF.Alarm.OCmd_Unshelve,430102.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1B_MF.Alarm.SCmd_Suppress,430102.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1B_MF.Alarm.SCmd_UnSuppress,430103.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1B_MF.Alarm.AEShelveTMRDN,430103.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1B_MF.Alarm.Bad,430103.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1B_MF.Alarm.Suppress,430104.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.UnSuppress,430104.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Shelve,430104.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.UnShelve,430104.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Enable,430104.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Disable,430104.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Ack,430104.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Reset,430104.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1B_MF.Alarm.Suppressed,430104.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1B_MF.Alarm.Shelved,430104.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1B_MF.Alarm.Disabled,430104.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1B_MF.Alarm.Acked,430104.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1B_MF.Alarm.Alarm,430104.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Fault,430114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_1B_MF.almPLCFault.AlarmState,430114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_1B_MF.almPLCFault.GlobalReset,430114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_1B_MF.almPLCFault.FaultInAlarm,430114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_1B_MF.almPLCFault.ALRM,430114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_1B_MF.almPLCFault.ANUN,430114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_1B_MF.almPLCFault.AKED,430114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_1B_MF.almPLCFault.Resetable,430114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_1B_MF.almPLCFault.REST,430114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_1B_MF.almPLCFault.ACKN,430114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_1B_MF.almPLCFault.UACK,430114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_1B_MF.almPLCFault.MCmd_Enable,430114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_1B_MF.almPLCFault.MCmd_Disable,430114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_1B_MF.almPLCFault.OCmd_Shelve,430114.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_1B_MF.almPLCFault.OCmd_Unshelve,430114.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_1B_MF.almPLCFault.SCmd_Suppress,430114.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_1B_MF.almPLCFault.SCmd_UnSuppress,430115.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_1B_MF.almPLCFault.AEShelveTMRDN,430115.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_1B_MF.almPLCFault.Bad,430115.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_1B_MF.almPLCFault.Suppress,430116.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.UnSuppress,430116.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Shelve,430116.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.UnShelve,430116.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Enable,430116.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Disable,430116.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Ack,430116.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Reset,430116.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Suppressed,430116.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Shelved,430116.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Disabled,430116.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Acked,430116.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_1B_MF.almPLCFault.Alarm,430116.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Fault,430136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_LH1.Alarm.AlarmState,430136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_LH1.Alarm.GlobalReset,430136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_LH1.Alarm.FaultInAlarm,430136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH1.Alarm.ALRM,430136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_LH1.Alarm.ANUN,430136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_LH1.Alarm.AKED,430136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_LH1.Alarm.Resetable,430136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_LH1.Alarm.REST,430136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_LH1.Alarm.ACKN,430136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_LH1.Alarm.UACK,430136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_LH1.Alarm.MCmd_Enable,430136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH1.Alarm.MCmd_Disable,430136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH1.Alarm.OCmd_Shelve,430136.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_LH1.Alarm.OCmd_Unshelve,430136.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_LH1.Alarm.SCmd_Suppress,430136.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_LH1.Alarm.SCmd_UnSuppress,430137.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_LH1.Alarm.AEShelveTMRDN,430137.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_LH1.Alarm.Bad,430137.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_LH1.Alarm.Suppress,430138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.UnSuppress,430138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Shelve,430138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.UnShelve,430138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Enable,430138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Disable,430138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Ack,430138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Reset,430138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_LH1.Alarm.Suppressed,430138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_LH1.Alarm.Shelved,430138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_LH1.Alarm.Disabled,430138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_LH1.Alarm.Acked,430138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_LH1.Alarm.Alarm,430138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Fault,430148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_LH1.almPLCFault.AlarmState,430148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_LH1.almPLCFault.GlobalReset,430148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_LH1.almPLCFault.FaultInAlarm,430148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH1.almPLCFault.ALRM,430148.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_LH1.almPLCFault.ANUN,430148.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_LH1.almPLCFault.AKED,430148.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_LH1.almPLCFault.Resetable,430148.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_LH1.almPLCFault.REST,430148.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_LH1.almPLCFault.ACKN,430148.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_LH1.almPLCFault.UACK,430148.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_LH1.almPLCFault.MCmd_Enable,430148.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH1.almPLCFault.MCmd_Disable,430148.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH1.almPLCFault.OCmd_Shelve,430148.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_LH1.almPLCFault.OCmd_Unshelve,430148.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_LH1.almPLCFault.SCmd_Suppress,430148.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_LH1.almPLCFault.SCmd_UnSuppress,430149.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_LH1.almPLCFault.AEShelveTMRDN,430149.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_LH1.almPLCFault.Bad,430149.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_LH1.almPLCFault.Suppress,430150.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.UnSuppress,430150.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Shelve,430150.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.UnShelve,430150.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Enable,430150.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Disable,430150.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Ack,430150.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Reset,430150.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Suppressed,430150.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Shelved,430150.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Disabled,430150.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Acked,430150.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_LH1.almPLCFault.Alarm,430150.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Fault,430172.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_LH2.Alarm.AlarmState,430172.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_LH2.Alarm.GlobalReset,430172.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_LH2.Alarm.FaultInAlarm,430172.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH2.Alarm.ALRM,430172.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_LH2.Alarm.ANUN,430172.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_LH2.Alarm.AKED,430172.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_LH2.Alarm.Resetable,430172.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_LH2.Alarm.REST,430172.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_LH2.Alarm.ACKN,430172.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_LH2.Alarm.UACK,430172.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_LH2.Alarm.MCmd_Enable,430172.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH2.Alarm.MCmd_Disable,430172.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH2.Alarm.OCmd_Shelve,430172.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_LH2.Alarm.OCmd_Unshelve,430172.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_LH2.Alarm.SCmd_Suppress,430172.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_LH2.Alarm.SCmd_UnSuppress,430173.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_LH2.Alarm.AEShelveTMRDN,430173.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_LH2.Alarm.Bad,430173.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_LH2.Alarm.Suppress,430174.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.UnSuppress,430174.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Shelve,430174.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.UnShelve,430174.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Enable,430174.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Disable,430174.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Ack,430174.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Reset,430174.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_LH2.Alarm.Suppressed,430174.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_LH2.Alarm.Shelved,430174.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_LH2.Alarm.Disabled,430174.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_LH2.Alarm.Acked,430174.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_LH2.Alarm.Alarm,430174.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Fault,430184.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_LH2.almPLCFault.AlarmState,430184.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_LH2.almPLCFault.GlobalReset,430184.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_LH2.almPLCFault.FaultInAlarm,430184.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_LH2.almPLCFault.ALRM,430184.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_LH2.almPLCFault.ANUN,430184.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_LH2.almPLCFault.AKED,430184.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_LH2.almPLCFault.Resetable,430184.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_LH2.almPLCFault.REST,430184.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_LH2.almPLCFault.ACKN,430184.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_LH2.almPLCFault.UACK,430184.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_LH2.almPLCFault.MCmd_Enable,430184.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_LH2.almPLCFault.MCmd_Disable,430184.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_LH2.almPLCFault.OCmd_Shelve,430184.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_LH2.almPLCFault.OCmd_Unshelve,430184.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_LH2.almPLCFault.SCmd_Suppress,430184.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_LH2.almPLCFault.SCmd_UnSuppress,430185.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_LH2.almPLCFault.AEShelveTMRDN,430185.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_LH2.almPLCFault.Bad,430185.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_LH2.almPLCFault.Suppress,430186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.UnSuppress,430186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Shelve,430186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.UnShelve,430186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Enable,430186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Disable,430186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Ack,430186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Reset,430186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Suppressed,430186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Shelved,430186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Disabled,430186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Acked,430186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_LH2.almPLCFault.Alarm,430186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Fault,430206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_XA.Alarm.AlarmState,430206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_XA.Alarm.GlobalReset,430206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_XA.Alarm.FaultInAlarm,430206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_XA.Alarm.ALRM,430206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_XA.Alarm.ANUN,430206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_XA.Alarm.AKED,430206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_XA.Alarm.Resetable,430206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_XA.Alarm.REST,430206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_XA.Alarm.ACKN,430206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_XA.Alarm.UACK,430206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_XA.Alarm.MCmd_Enable,430206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_XA.Alarm.MCmd_Disable,430206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_XA.Alarm.OCmd_Shelve,430206.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_XA.Alarm.OCmd_Unshelve,430206.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_XA.Alarm.SCmd_Suppress,430206.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_XA.Alarm.SCmd_UnSuppress,430207.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_XA.Alarm.AEShelveTMRDN,430207.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_XA.Alarm.Bad,430207.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_XA.Alarm.Suppress,430208.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.UnSuppress,430208.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Shelve,430208.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.UnShelve,430208.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Enable,430208.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Disable,430208.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Ack,430208.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Reset,430208.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_XA.Alarm.Suppressed,430208.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_XA.Alarm.Shelved,430208.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_XA.Alarm.Disabled,430208.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_XA.Alarm.Acked,430208.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_XA.Alarm.Alarm,430208.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Fault,430218.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2_XA.almPLCFault.AlarmState,430218.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2_XA.almPLCFault.GlobalReset,430218.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2_XA.almPLCFault.FaultInAlarm,430218.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2_XA.almPLCFault.ALRM,430218.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2_XA.almPLCFault.ANUN,430218.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2_XA.almPLCFault.AKED,430218.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2_XA.almPLCFault.Resetable,430218.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2_XA.almPLCFault.REST,430218.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2_XA.almPLCFault.ACKN,430218.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2_XA.almPLCFault.UACK,430218.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2_XA.almPLCFault.MCmd_Enable,430218.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2_XA.almPLCFault.MCmd_Disable,430218.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2_XA.almPLCFault.OCmd_Shelve,430218.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2_XA.almPLCFault.OCmd_Unshelve,430218.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2_XA.almPLCFault.SCmd_Suppress,430218.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2_XA.almPLCFault.SCmd_UnSuppress,430219.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2_XA.almPLCFault.AEShelveTMRDN,430219.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2_XA.almPLCFault.Bad,430219.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2_XA.almPLCFault.Suppress,430220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.UnSuppress,430220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Shelve,430220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.UnShelve,430220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Enable,430220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Disable,430220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Ack,430220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Reset,430220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2_XA.almPLCFault.Suppressed,430220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2_XA.almPLCFault.Shelved,430220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2_XA.almPLCFault.Disabled,430220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2_XA.almPLCFault.Acked,430220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2_XA.almPLCFault.Alarm,430220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Fault,430242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2A_MF.Alarm.AlarmState,430242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2A_MF.Alarm.GlobalReset,430242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2A_MF.Alarm.FaultInAlarm,430242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2A_MF.Alarm.ALRM,430242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2A_MF.Alarm.ANUN,430242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2A_MF.Alarm.AKED,430242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2A_MF.Alarm.Resetable,430242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2A_MF.Alarm.REST,430242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2A_MF.Alarm.ACKN,430242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2A_MF.Alarm.UACK,430242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2A_MF.Alarm.MCmd_Enable,430242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2A_MF.Alarm.MCmd_Disable,430242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2A_MF.Alarm.OCmd_Shelve,430242.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2A_MF.Alarm.OCmd_Unshelve,430242.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2A_MF.Alarm.SCmd_Suppress,430242.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2A_MF.Alarm.SCmd_UnSuppress,430243.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2A_MF.Alarm.AEShelveTMRDN,430243.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2A_MF.Alarm.Bad,430243.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2A_MF.Alarm.Suppress,430244.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.UnSuppress,430244.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Shelve,430244.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.UnShelve,430244.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Enable,430244.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Disable,430244.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Ack,430244.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Reset,430244.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2A_MF.Alarm.Suppressed,430244.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2A_MF.Alarm.Shelved,430244.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2A_MF.Alarm.Disabled,430244.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2A_MF.Alarm.Acked,430244.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2A_MF.Alarm.Alarm,430244.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Fault,430254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2A_MF.almPLCFault.AlarmState,430254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2A_MF.almPLCFault.GlobalReset,430254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2A_MF.almPLCFault.FaultInAlarm,430254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2A_MF.almPLCFault.ALRM,430254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2A_MF.almPLCFault.ANUN,430254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2A_MF.almPLCFault.AKED,430254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2A_MF.almPLCFault.Resetable,430254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2A_MF.almPLCFault.REST,430254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2A_MF.almPLCFault.ACKN,430254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2A_MF.almPLCFault.UACK,430254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2A_MF.almPLCFault.MCmd_Enable,430254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2A_MF.almPLCFault.MCmd_Disable,430254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2A_MF.almPLCFault.OCmd_Shelve,430254.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2A_MF.almPLCFault.OCmd_Unshelve,430254.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2A_MF.almPLCFault.SCmd_Suppress,430254.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2A_MF.almPLCFault.SCmd_UnSuppress,430255.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2A_MF.almPLCFault.AEShelveTMRDN,430255.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2A_MF.almPLCFault.Bad,430255.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2A_MF.almPLCFault.Suppress,430256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.UnSuppress,430256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Shelve,430256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.UnShelve,430256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Enable,430256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Disable,430256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Ack,430256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Reset,430256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Suppressed,430256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Shelved,430256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Disabled,430256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Acked,430256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2A_MF.almPLCFault.Alarm,430256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Fault,430276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2B_MF.Alarm.AlarmState,430276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2B_MF.Alarm.GlobalReset,430276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2B_MF.Alarm.FaultInAlarm,430276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2B_MF.Alarm.ALRM,430276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2B_MF.Alarm.ANUN,430276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2B_MF.Alarm.AKED,430276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2B_MF.Alarm.Resetable,430276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2B_MF.Alarm.REST,430276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2B_MF.Alarm.ACKN,430276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2B_MF.Alarm.UACK,430276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2B_MF.Alarm.MCmd_Enable,430276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2B_MF.Alarm.MCmd_Disable,430276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2B_MF.Alarm.OCmd_Shelve,430276.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2B_MF.Alarm.OCmd_Unshelve,430276.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2B_MF.Alarm.SCmd_Suppress,430276.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2B_MF.Alarm.SCmd_UnSuppress,430277.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2B_MF.Alarm.AEShelveTMRDN,430277.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2B_MF.Alarm.Bad,430277.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2B_MF.Alarm.Suppress,430278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.UnSuppress,430278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Shelve,430278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.UnShelve,430278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Enable,430278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Disable,430278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Ack,430278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Reset,430278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2B_MF.Alarm.Suppressed,430278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2B_MF.Alarm.Shelved,430278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2B_MF.Alarm.Disabled,430278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2B_MF.Alarm.Acked,430278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2B_MF.Alarm.Alarm,430278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Fault,430288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_CP_0118_2B_MF.almPLCFault.AlarmState,430288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_CP_0118_2B_MF.almPLCFault.GlobalReset,430288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_CP_0118_2B_MF.almPLCFault.FaultInAlarm,430288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_CP_0118_2B_MF.almPLCFault.ALRM,430288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_CP_0118_2B_MF.almPLCFault.ANUN,430288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_CP_0118_2B_MF.almPLCFault.AKED,430288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_CP_0118_2B_MF.almPLCFault.Resetable,430288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_CP_0118_2B_MF.almPLCFault.REST,430288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_CP_0118_2B_MF.almPLCFault.ACKN,430288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_CP_0118_2B_MF.almPLCFault.UACK,430288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_CP_0118_2B_MF.almPLCFault.MCmd_Enable,430288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_CP_0118_2B_MF.almPLCFault.MCmd_Disable,430288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_CP_0118_2B_MF.almPLCFault.OCmd_Shelve,430288.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_CP_0118_2B_MF.almPLCFault.OCmd_Unshelve,430288.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_CP_0118_2B_MF.almPLCFault.SCmd_Suppress,430288.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_CP_0118_2B_MF.almPLCFault.SCmd_UnSuppress,430289.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_CP_0118_2B_MF.almPLCFault.AEShelveTMRDN,430289.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_CP_0118_2B_MF.almPLCFault.Bad,430289.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_CP_0118_2B_MF.almPLCFault.Suppress,430290.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.UnSuppress,430290.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Shelve,430290.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.UnShelve,430290.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Enable,430290.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Disable,430290.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Ack,430290.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Reset,430290.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Suppressed,430290.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Shelved,430290.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Disabled,430290.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Acked,430290.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_CP_0118_2B_MF.almPLCFault.Alarm,430290.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Fault,430312.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_WH.Alarm.AlarmState,430312.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_WH.Alarm.GlobalReset,430312.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_WH.Alarm.FaultInAlarm,430312.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_WH.Alarm.ALRM,430312.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_WH.Alarm.ANUN,430312.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_WH.Alarm.AKED,430312.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_WH.Alarm.Resetable,430312.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_WH.Alarm.REST,430312.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_WH.Alarm.ACKN,430312.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_WH.Alarm.UACK,430312.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_WH.Alarm.MCmd_Enable,430312.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_WH.Alarm.MCmd_Disable,430312.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_WH.Alarm.OCmd_Shelve,430312.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_WH.Alarm.OCmd_Unshelve,430312.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_WH.Alarm.SCmd_Suppress,430312.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_WH.Alarm.SCmd_UnSuppress,430313.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_WH.Alarm.AEShelveTMRDN,430313.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_WH.Alarm.Bad,430313.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_WH.Alarm.Suppress,430314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.UnSuppress,430314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Shelve,430314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.UnShelve,430314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Enable,430314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Disable,430314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Ack,430314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Reset,430314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_WH.Alarm.Suppressed,430314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_WH.Alarm.Shelved,430314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_WH.Alarm.Disabled,430314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_WH.Alarm.Acked,430314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_WH.Alarm.Alarm,430314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Fault,430324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A_WH.almPLCFault.AlarmState,430324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A_WH.almPLCFault.GlobalReset,430324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A_WH.almPLCFault.FaultInAlarm,430324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A_WH.almPLCFault.ALRM,430324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A_WH.almPLCFault.ANUN,430324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A_WH.almPLCFault.AKED,430324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A_WH.almPLCFault.Resetable,430324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A_WH.almPLCFault.REST,430324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A_WH.almPLCFault.ACKN,430324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A_WH.almPLCFault.UACK,430324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A_WH.almPLCFault.MCmd_Enable,430324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.MCmd_Disable,430324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.OCmd_Shelve,430324.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.OCmd_Unshelve,430324.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.SCmd_Suppress,430324.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.SCmd_UnSuppress,430325.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A_WH.almPLCFault.AEShelveTMRDN,430325.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A_WH.almPLCFault.Bad,430325.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A_WH.almPLCFault.Suppress,430326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.UnSuppress,430326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Shelve,430326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.UnShelve,430326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Enable,430326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Disable,430326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Ack,430326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Reset,430326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Suppressed,430326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Shelved,430326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Disabled,430326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Acked,430326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A_WH.almPLCFault.Alarm,430326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Fault,430346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_WH.Alarm.AlarmState,430346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_WH.Alarm.GlobalReset,430346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_WH.Alarm.FaultInAlarm,430346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_WH.Alarm.ALRM,430346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_WH.Alarm.ANUN,430346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_WH.Alarm.AKED,430346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_WH.Alarm.Resetable,430346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_WH.Alarm.REST,430346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_WH.Alarm.ACKN,430346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_WH.Alarm.UACK,430346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_WH.Alarm.MCmd_Enable,430346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_WH.Alarm.MCmd_Disable,430346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_WH.Alarm.OCmd_Shelve,430346.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_WH.Alarm.OCmd_Unshelve,430346.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_WH.Alarm.SCmd_Suppress,430346.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_WH.Alarm.SCmd_UnSuppress,430347.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_WH.Alarm.AEShelveTMRDN,430347.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_WH.Alarm.Bad,430347.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_WH.Alarm.Suppress,430348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.UnSuppress,430348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Shelve,430348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.UnShelve,430348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Enable,430348.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Disable,430348.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Ack,430348.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Reset,430348.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_WH.Alarm.Suppressed,430348.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_WH.Alarm.Shelved,430348.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_WH.Alarm.Disabled,430348.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_WH.Alarm.Acked,430348.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_WH.Alarm.Alarm,430348.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Fault,430358.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B_WH.almPLCFault.AlarmState,430358.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B_WH.almPLCFault.GlobalReset,430358.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B_WH.almPLCFault.FaultInAlarm,430358.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B_WH.almPLCFault.ALRM,430358.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B_WH.almPLCFault.ANUN,430358.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B_WH.almPLCFault.AKED,430358.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B_WH.almPLCFault.Resetable,430358.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B_WH.almPLCFault.REST,430358.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B_WH.almPLCFault.ACKN,430358.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B_WH.almPLCFault.UACK,430358.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B_WH.almPLCFault.MCmd_Enable,430358.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.MCmd_Disable,430358.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.OCmd_Shelve,430358.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.OCmd_Unshelve,430358.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.SCmd_Suppress,430358.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.SCmd_UnSuppress,430359.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B_WH.almPLCFault.AEShelveTMRDN,430359.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B_WH.almPLCFault.Bad,430359.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B_WH.almPLCFault.Suppress,430360.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.UnSuppress,430360.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Shelve,430360.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.UnShelve,430360.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Enable,430360.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Disable,430360.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Ack,430360.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Reset,430360.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Suppressed,430360.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Shelved,430360.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Disabled,430360.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Acked,430360.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B_WH.almPLCFault.Alarm,430360.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Fault,430382.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FLT_0112_1_XA.Alarm.AlarmState,430382.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FLT_0112_1_XA.Alarm.GlobalReset,430382.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FLT_0112_1_XA.Alarm.FaultInAlarm,430382.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_1_XA.Alarm.ALRM,430382.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FLT_0112_1_XA.Alarm.ANUN,430382.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FLT_0112_1_XA.Alarm.AKED,430382.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FLT_0112_1_XA.Alarm.Resetable,430382.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FLT_0112_1_XA.Alarm.REST,430382.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FLT_0112_1_XA.Alarm.ACKN,430382.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FLT_0112_1_XA.Alarm.UACK,430382.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FLT_0112_1_XA.Alarm.MCmd_Enable,430382.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_1_XA.Alarm.MCmd_Disable,430382.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_1_XA.Alarm.OCmd_Shelve,430382.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FLT_0112_1_XA.Alarm.OCmd_Unshelve,430382.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FLT_0112_1_XA.Alarm.SCmd_Suppress,430382.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FLT_0112_1_XA.Alarm.SCmd_UnSuppress,430383.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FLT_0112_1_XA.Alarm.AEShelveTMRDN,430383.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FLT_0112_1_XA.Alarm.Bad,430383.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FLT_0112_1_XA.Alarm.Suppress,430384.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.UnSuppress,430384.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Shelve,430384.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.UnShelve,430384.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Enable,430384.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Disable,430384.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Ack,430384.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Reset,430384.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FLT_0112_1_XA.Alarm.Suppressed,430384.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FLT_0112_1_XA.Alarm.Shelved,430384.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FLT_0112_1_XA.Alarm.Disabled,430384.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FLT_0112_1_XA.Alarm.Acked,430384.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FLT_0112_1_XA.Alarm.Alarm,430384.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Fault,430394.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FLT_0112_1_XA.almPLCFault.AlarmState,430394.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FLT_0112_1_XA.almPLCFault.GlobalReset,430394.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FLT_0112_1_XA.almPLCFault.FaultInAlarm,430394.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_1_XA.almPLCFault.ALRM,430394.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FLT_0112_1_XA.almPLCFault.ANUN,430394.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FLT_0112_1_XA.almPLCFault.AKED,430394.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FLT_0112_1_XA.almPLCFault.Resetable,430394.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FLT_0112_1_XA.almPLCFault.REST,430394.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FLT_0112_1_XA.almPLCFault.ACKN,430394.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FLT_0112_1_XA.almPLCFault.UACK,430394.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FLT_0112_1_XA.almPLCFault.MCmd_Enable,430394.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_1_XA.almPLCFault.MCmd_Disable,430394.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_1_XA.almPLCFault.OCmd_Shelve,430394.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FLT_0112_1_XA.almPLCFault.OCmd_Unshelve,430394.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FLT_0112_1_XA.almPLCFault.SCmd_Suppress,430394.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FLT_0112_1_XA.almPLCFault.SCmd_UnSuppress,430395.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FLT_0112_1_XA.almPLCFault.AEShelveTMRDN,430395.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FLT_0112_1_XA.almPLCFault.Bad,430395.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FLT_0112_1_XA.almPLCFault.Suppress,430396.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.UnSuppress,430396.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Shelve,430396.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.UnShelve,430396.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Enable,430396.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Disable,430396.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Ack,430396.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Reset,430396.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Suppressed,430396.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Shelved,430396.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Disabled,430396.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Acked,430396.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FLT_0112_1_XA.almPLCFault.Alarm,430396.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Fault,430416.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FLT_0112_2_XA.Alarm.AlarmState,430416.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FLT_0112_2_XA.Alarm.GlobalReset,430416.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FLT_0112_2_XA.Alarm.FaultInAlarm,430416.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_2_XA.Alarm.ALRM,430416.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FLT_0112_2_XA.Alarm.ANUN,430416.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FLT_0112_2_XA.Alarm.AKED,430416.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FLT_0112_2_XA.Alarm.Resetable,430416.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FLT_0112_2_XA.Alarm.REST,430416.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FLT_0112_2_XA.Alarm.ACKN,430416.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FLT_0112_2_XA.Alarm.UACK,430416.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FLT_0112_2_XA.Alarm.MCmd_Enable,430416.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_2_XA.Alarm.MCmd_Disable,430416.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_2_XA.Alarm.OCmd_Shelve,430416.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FLT_0112_2_XA.Alarm.OCmd_Unshelve,430416.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FLT_0112_2_XA.Alarm.SCmd_Suppress,430416.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FLT_0112_2_XA.Alarm.SCmd_UnSuppress,430417.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FLT_0112_2_XA.Alarm.AEShelveTMRDN,430417.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FLT_0112_2_XA.Alarm.Bad,430417.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FLT_0112_2_XA.Alarm.Suppress,430418.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.UnSuppress,430418.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Shelve,430418.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.UnShelve,430418.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Enable,430418.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Disable,430418.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Ack,430418.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Reset,430418.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FLT_0112_2_XA.Alarm.Suppressed,430418.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FLT_0112_2_XA.Alarm.Shelved,430418.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FLT_0112_2_XA.Alarm.Disabled,430418.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FLT_0112_2_XA.Alarm.Acked,430418.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FLT_0112_2_XA.Alarm.Alarm,430418.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Fault,430428.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FLT_0112_2_XA.almPLCFault.AlarmState,430428.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FLT_0112_2_XA.almPLCFault.GlobalReset,430428.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FLT_0112_2_XA.almPLCFault.FaultInAlarm,430428.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FLT_0112_2_XA.almPLCFault.ALRM,430428.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FLT_0112_2_XA.almPLCFault.ANUN,430428.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FLT_0112_2_XA.almPLCFault.AKED,430428.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FLT_0112_2_XA.almPLCFault.Resetable,430428.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FLT_0112_2_XA.almPLCFault.REST,430428.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FLT_0112_2_XA.almPLCFault.ACKN,430428.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FLT_0112_2_XA.almPLCFault.UACK,430428.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FLT_0112_2_XA.almPLCFault.MCmd_Enable,430428.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FLT_0112_2_XA.almPLCFault.MCmd_Disable,430428.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FLT_0112_2_XA.almPLCFault.OCmd_Shelve,430428.13,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FLT_0112_2_XA.almPLCFault.OCmd_Unshelve,430428.14,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FLT_0112_2_XA.almPLCFault.SCmd_Suppress,430428.15,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FLT_0112_2_XA.almPLCFault.SCmd_UnSuppress,430429.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FLT_0112_2_XA.almPLCFault.AEShelveTMRDN,430429.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FLT_0112_2_XA.almPLCFault.Bad,430429.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FLT_0112_2_XA.almPLCFault.Suppress,430430.00,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.UnSuppress,430430.01,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Shelve,430430.02,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.UnShelve,430430.03,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Enable,430430.04,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Disable,430430.05,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Ack,430430.06,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Reset,430430.07,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Suppressed,430430.08,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Shelved,430430.09,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Disabled,430430.10,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Acked,430430.11,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FLT_0112_2_XA.almPLCFault.Alarm,430430.12,Boolean,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Fault,430452.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A_WH.Alarm.AlarmState,430452.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A_WH.Alarm.GlobalReset,430452.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A_WH.Alarm.FaultInAlarm,430452.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A_WH.Alarm.ALRM,430452.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A_WH.Alarm.ANUN,430452.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A_WH.Alarm.AKED,430452.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A_WH.Alarm.Resetable,430452.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A_WH.Alarm.REST,430452.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A_WH.Alarm.ACKN,430452.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A_WH.Alarm.UACK,430452.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A_WH.Alarm.MCmd_Enable,430452.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A_WH.Alarm.MCmd_Disable,430452.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A_WH.Alarm.OCmd_Shelve,430452.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A_WH.Alarm.OCmd_Unshelve,430452.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A_WH.Alarm.SCmd_Suppress,430452.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A_WH.Alarm.SCmd_UnSuppress,430453.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A_WH.Alarm.AEShelveTMRDN,430453.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A_WH.Alarm.Bad,430453.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A_WH.Alarm.Suppress,430454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.UnSuppress,430454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Shelve,430454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.UnShelve,430454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Enable,430454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Disable,430454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Ack,430454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Reset,430454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A_WH.Alarm.Suppressed,430454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A_WH.Alarm.Shelved,430454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A_WH.Alarm.Disabled,430454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A_WH.Alarm.Acked,430454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A_WH.Alarm.Alarm,430454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Fault,430464.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A_WH.almPLCFault.AlarmState,430464.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A_WH.almPLCFault.GlobalReset,430464.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A_WH.almPLCFault.FaultInAlarm,430464.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A_WH.almPLCFault.ALRM,430464.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A_WH.almPLCFault.ANUN,430464.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A_WH.almPLCFault.AKED,430464.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A_WH.almPLCFault.Resetable,430464.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A_WH.almPLCFault.REST,430464.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A_WH.almPLCFault.ACKN,430464.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A_WH.almPLCFault.UACK,430464.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A_WH.almPLCFault.MCmd_Enable,430464.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A_WH.almPLCFault.MCmd_Disable,430464.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A_WH.almPLCFault.OCmd_Shelve,430464.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A_WH.almPLCFault.OCmd_Unshelve,430464.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A_WH.almPLCFault.SCmd_Suppress,430464.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A_WH.almPLCFault.SCmd_UnSuppress,430465.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A_WH.almPLCFault.AEShelveTMRDN,430465.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A_WH.almPLCFault.Bad,430465.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A_WH.almPLCFault.Suppress,430466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.UnSuppress,430466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Shelve,430466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.UnShelve,430466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Enable,430466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Disable,430466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Ack,430466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Reset,430466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Suppressed,430466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Shelved,430466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Disabled,430466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Acked,430466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A_WH.almPLCFault.Alarm,430466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Fault,430486.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B_WH.Alarm.AlarmState,430486.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B_WH.Alarm.GlobalReset,430486.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B_WH.Alarm.FaultInAlarm,430486.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B_WH.Alarm.ALRM,430486.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B_WH.Alarm.ANUN,430486.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B_WH.Alarm.AKED,430486.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B_WH.Alarm.Resetable,430486.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B_WH.Alarm.REST,430486.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B_WH.Alarm.ACKN,430486.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B_WH.Alarm.UACK,430486.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B_WH.Alarm.MCmd_Enable,430486.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B_WH.Alarm.MCmd_Disable,430486.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B_WH.Alarm.OCmd_Shelve,430486.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B_WH.Alarm.OCmd_Unshelve,430486.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B_WH.Alarm.SCmd_Suppress,430486.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B_WH.Alarm.SCmd_UnSuppress,430487.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B_WH.Alarm.AEShelveTMRDN,430487.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B_WH.Alarm.Bad,430487.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B_WH.Alarm.Suppress,430488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.UnSuppress,430488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Shelve,430488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.UnShelve,430488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Enable,430488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Disable,430488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Ack,430488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Reset,430488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B_WH.Alarm.Suppressed,430488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B_WH.Alarm.Shelved,430488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B_WH.Alarm.Disabled,430488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B_WH.Alarm.Acked,430488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B_WH.Alarm.Alarm,430488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Fault,430498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B_WH.almPLCFault.AlarmState,430498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B_WH.almPLCFault.GlobalReset,430498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B_WH.almPLCFault.FaultInAlarm,430498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B_WH.almPLCFault.ALRM,430498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B_WH.almPLCFault.ANUN,430498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B_WH.almPLCFault.AKED,430498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B_WH.almPLCFault.Resetable,430498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B_WH.almPLCFault.REST,430498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B_WH.almPLCFault.ACKN,430498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B_WH.almPLCFault.UACK,430498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B_WH.almPLCFault.MCmd_Enable,430498.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B_WH.almPLCFault.MCmd_Disable,430498.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B_WH.almPLCFault.OCmd_Shelve,430498.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B_WH.almPLCFault.OCmd_Unshelve,430498.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B_WH.almPLCFault.SCmd_Suppress,430498.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B_WH.almPLCFault.SCmd_UnSuppress,430499.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B_WH.almPLCFault.AEShelveTMRDN,430499.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B_WH.almPLCFault.Bad,430499.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B_WH.almPLCFault.Suppress,430500.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.UnSuppress,430500.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Shelve,430500.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.UnShelve,430500.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Enable,430500.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Disable,430500.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Ack,430500.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Reset,430500.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Suppressed,430500.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Shelved,430500.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Disabled,430500.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Acked,430500.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B_WH.almPLCFault.Alarm,430500.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Fault,430522.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A_WH.Alarm.AlarmState,430522.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A_WH.Alarm.GlobalReset,430522.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A_WH.Alarm.FaultInAlarm,430522.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A_WH.Alarm.ALRM,430522.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A_WH.Alarm.ANUN,430522.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A_WH.Alarm.AKED,430522.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A_WH.Alarm.Resetable,430522.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A_WH.Alarm.REST,430522.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A_WH.Alarm.ACKN,430522.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A_WH.Alarm.UACK,430522.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A_WH.Alarm.MCmd_Enable,430522.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A_WH.Alarm.MCmd_Disable,430522.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A_WH.Alarm.OCmd_Shelve,430522.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A_WH.Alarm.OCmd_Unshelve,430522.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A_WH.Alarm.SCmd_Suppress,430522.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A_WH.Alarm.SCmd_UnSuppress,430523.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A_WH.Alarm.AEShelveTMRDN,430523.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A_WH.Alarm.Bad,430523.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A_WH.Alarm.Suppress,430524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.UnSuppress,430524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Shelve,430524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.UnShelve,430524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Enable,430524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Disable,430524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Ack,430524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Reset,430524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A_WH.Alarm.Suppressed,430524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A_WH.Alarm.Shelved,430524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A_WH.Alarm.Disabled,430524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A_WH.Alarm.Acked,430524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A_WH.Alarm.Alarm,430524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Fault,430534.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A_WH.almPLCFault.AlarmState,430534.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A_WH.almPLCFault.GlobalReset,430534.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A_WH.almPLCFault.FaultInAlarm,430534.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A_WH.almPLCFault.ALRM,430534.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A_WH.almPLCFault.ANUN,430534.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A_WH.almPLCFault.AKED,430534.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A_WH.almPLCFault.Resetable,430534.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A_WH.almPLCFault.REST,430534.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A_WH.almPLCFault.ACKN,430534.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A_WH.almPLCFault.UACK,430534.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A_WH.almPLCFault.MCmd_Enable,430534.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A_WH.almPLCFault.MCmd_Disable,430534.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A_WH.almPLCFault.OCmd_Shelve,430534.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A_WH.almPLCFault.OCmd_Unshelve,430534.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A_WH.almPLCFault.SCmd_Suppress,430534.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A_WH.almPLCFault.SCmd_UnSuppress,430535.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A_WH.almPLCFault.AEShelveTMRDN,430535.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A_WH.almPLCFault.Bad,430535.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A_WH.almPLCFault.Suppress,430536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.UnSuppress,430536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Shelve,430536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.UnShelve,430536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Enable,430536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Disable,430536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Ack,430536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Reset,430536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Suppressed,430536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Shelved,430536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Disabled,430536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Acked,430536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A_WH.almPLCFault.Alarm,430536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Fault,430556.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B_WH.Alarm.AlarmState,430556.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B_WH.Alarm.GlobalReset,430556.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B_WH.Alarm.FaultInAlarm,430556.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B_WH.Alarm.ALRM,430556.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B_WH.Alarm.ANUN,430556.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B_WH.Alarm.AKED,430556.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B_WH.Alarm.Resetable,430556.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B_WH.Alarm.REST,430556.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B_WH.Alarm.ACKN,430556.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B_WH.Alarm.UACK,430556.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B_WH.Alarm.MCmd_Enable,430556.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B_WH.Alarm.MCmd_Disable,430556.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B_WH.Alarm.OCmd_Shelve,430556.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B_WH.Alarm.OCmd_Unshelve,430556.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B_WH.Alarm.SCmd_Suppress,430556.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B_WH.Alarm.SCmd_UnSuppress,430557.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B_WH.Alarm.AEShelveTMRDN,430557.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B_WH.Alarm.Bad,430557.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B_WH.Alarm.Suppress,430558.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.UnSuppress,430558.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Shelve,430558.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.UnShelve,430558.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Enable,430558.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Disable,430558.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Ack,430558.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Reset,430558.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B_WH.Alarm.Suppressed,430558.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B_WH.Alarm.Shelved,430558.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B_WH.Alarm.Disabled,430558.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B_WH.Alarm.Acked,430558.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B_WH.Alarm.Alarm,430558.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Fault,430568.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B_WH.almPLCFault.AlarmState,430568.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B_WH.almPLCFault.GlobalReset,430568.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B_WH.almPLCFault.FaultInAlarm,430568.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B_WH.almPLCFault.ALRM,430568.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B_WH.almPLCFault.ANUN,430568.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B_WH.almPLCFault.AKED,430568.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B_WH.almPLCFault.Resetable,430568.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B_WH.almPLCFault.REST,430568.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B_WH.almPLCFault.ACKN,430568.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B_WH.almPLCFault.UACK,430568.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B_WH.almPLCFault.MCmd_Enable,430568.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B_WH.almPLCFault.MCmd_Disable,430568.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B_WH.almPLCFault.OCmd_Shelve,430568.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B_WH.almPLCFault.OCmd_Unshelve,430568.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B_WH.almPLCFault.SCmd_Suppress,430568.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B_WH.almPLCFault.SCmd_UnSuppress,430569.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B_WH.almPLCFault.AEShelveTMRDN,430569.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B_WH.almPLCFault.Bad,430569.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B_WH.almPLCFault.Suppress,430570.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.UnSuppress,430570.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Shelve,430570.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.UnShelve,430570.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Enable,430570.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Disable,430570.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Ack,430570.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Reset,430570.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Suppressed,430570.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Shelved,430570.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Disabled,430570.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Acked,430570.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B_WH.almPLCFault.Alarm,430570.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Fault,430592.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A_WH.Alarm.AlarmState,430592.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A_WH.Alarm.GlobalReset,430592.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A_WH.Alarm.FaultInAlarm,430592.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A_WH.Alarm.ALRM,430592.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A_WH.Alarm.ANUN,430592.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A_WH.Alarm.AKED,430592.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A_WH.Alarm.Resetable,430592.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A_WH.Alarm.REST,430592.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A_WH.Alarm.ACKN,430592.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A_WH.Alarm.UACK,430592.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A_WH.Alarm.MCmd_Enable,430592.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A_WH.Alarm.MCmd_Disable,430592.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A_WH.Alarm.OCmd_Shelve,430592.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A_WH.Alarm.OCmd_Unshelve,430592.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A_WH.Alarm.SCmd_Suppress,430592.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A_WH.Alarm.SCmd_UnSuppress,430593.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A_WH.Alarm.AEShelveTMRDN,430593.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A_WH.Alarm.Bad,430593.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A_WH.Alarm.Suppress,430594.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.UnSuppress,430594.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Shelve,430594.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.UnShelve,430594.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Enable,430594.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Disable,430594.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Ack,430594.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Reset,430594.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A_WH.Alarm.Suppressed,430594.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A_WH.Alarm.Shelved,430594.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A_WH.Alarm.Disabled,430594.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A_WH.Alarm.Acked,430594.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A_WH.Alarm.Alarm,430594.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Fault,430604.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A_WH.almPLCFault.AlarmState,430604.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A_WH.almPLCFault.GlobalReset,430604.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A_WH.almPLCFault.FaultInAlarm,430604.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A_WH.almPLCFault.ALRM,430604.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A_WH.almPLCFault.ANUN,430604.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A_WH.almPLCFault.AKED,430604.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A_WH.almPLCFault.Resetable,430604.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A_WH.almPLCFault.REST,430604.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A_WH.almPLCFault.ACKN,430604.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A_WH.almPLCFault.UACK,430604.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A_WH.almPLCFault.MCmd_Enable,430604.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A_WH.almPLCFault.MCmd_Disable,430604.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A_WH.almPLCFault.OCmd_Shelve,430604.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A_WH.almPLCFault.OCmd_Unshelve,430604.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A_WH.almPLCFault.SCmd_Suppress,430604.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A_WH.almPLCFault.SCmd_UnSuppress,430605.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A_WH.almPLCFault.AEShelveTMRDN,430605.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A_WH.almPLCFault.Bad,430605.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A_WH.almPLCFault.Suppress,430606.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.UnSuppress,430606.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Shelve,430606.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.UnShelve,430606.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Enable,430606.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Disable,430606.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Ack,430606.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Reset,430606.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Suppressed,430606.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Shelved,430606.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Disabled,430606.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Acked,430606.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A_WH.almPLCFault.Alarm,430606.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Fault,430626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZF.Alarm.AlarmState,430626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZF.Alarm.GlobalReset,430626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZF.Alarm.FaultInAlarm,430626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF.Alarm.ALRM,430626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZF.Alarm.ANUN,430626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZF.Alarm.AKED,430626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZF.Alarm.Resetable,430626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZF.Alarm.REST,430626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZF.Alarm.ACKN,430626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZF.Alarm.UACK,430626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZF.Alarm.MCmd_Enable,430626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF.Alarm.MCmd_Disable,430626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF.Alarm.OCmd_Shelve,430626.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZF.Alarm.OCmd_Unshelve,430626.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZF.Alarm.SCmd_Suppress,430626.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZF.Alarm.SCmd_UnSuppress,430627.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZF.Alarm.AEShelveTMRDN,430627.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZF.Alarm.Bad,430627.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZF.Alarm.Suppress,430628.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.UnSuppress,430628.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Shelve,430628.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.UnShelve,430628.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Enable,430628.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Disable,430628.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Ack,430628.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Reset,430628.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZF.Alarm.Suppressed,430628.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZF.Alarm.Shelved,430628.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZF.Alarm.Disabled,430628.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZF.Alarm.Acked,430628.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZF.Alarm.Alarm,430628.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Fault,430638.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZF.almPLCFault.AlarmState,430638.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZF.almPLCFault.GlobalReset,430638.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZF.almPLCFault.FaultInAlarm,430638.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF.almPLCFault.ALRM,430638.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZF.almPLCFault.ANUN,430638.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZF.almPLCFault.AKED,430638.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZF.almPLCFault.Resetable,430638.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZF.almPLCFault.REST,430638.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZF.almPLCFault.ACKN,430638.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZF.almPLCFault.UACK,430638.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZF.almPLCFault.MCmd_Enable,430638.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.MCmd_Disable,430638.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.OCmd_Shelve,430638.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.OCmd_Unshelve,430638.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.SCmd_Suppress,430638.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.SCmd_UnSuppress,430639.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZF.almPLCFault.AEShelveTMRDN,430639.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZF.almPLCFault.Bad,430639.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZF.almPLCFault.Suppress,430640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.UnSuppress,430640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Shelve,430640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.UnShelve,430640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Enable,430640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Disable,430640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Ack,430640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Reset,430640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Suppressed,430640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Shelved,430640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Disabled,430640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Acked,430640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZF.almPLCFault.Alarm,430640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Fault,430662.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZF2.Alarm.AlarmState,430662.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZF2.Alarm.GlobalReset,430662.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZF2.Alarm.FaultInAlarm,430662.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF2.Alarm.ALRM,430662.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZF2.Alarm.ANUN,430662.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZF2.Alarm.AKED,430662.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZF2.Alarm.Resetable,430662.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZF2.Alarm.REST,430662.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZF2.Alarm.ACKN,430662.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZF2.Alarm.UACK,430662.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZF2.Alarm.MCmd_Enable,430662.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF2.Alarm.MCmd_Disable,430662.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF2.Alarm.OCmd_Shelve,430662.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZF2.Alarm.OCmd_Unshelve,430662.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZF2.Alarm.SCmd_Suppress,430662.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZF2.Alarm.SCmd_UnSuppress,430663.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZF2.Alarm.AEShelveTMRDN,430663.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZF2.Alarm.Bad,430663.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZF2.Alarm.Suppress,430664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.UnSuppress,430664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Shelve,430664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.UnShelve,430664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Enable,430664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Disable,430664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Ack,430664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Reset,430664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Suppressed,430664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Shelved,430664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Disabled,430664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Acked,430664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZF2.Alarm.Alarm,430664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Fault,430674.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1B_ZF2.almPLCFault.AlarmState,430674.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1B_ZF2.almPLCFault.GlobalReset,430674.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1B_ZF2.almPLCFault.FaultInAlarm,430674.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1B_ZF2.almPLCFault.ALRM,430674.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1B_ZF2.almPLCFault.ANUN,430674.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1B_ZF2.almPLCFault.AKED,430674.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1B_ZF2.almPLCFault.Resetable,430674.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1B_ZF2.almPLCFault.REST,430674.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1B_ZF2.almPLCFault.ACKN,430674.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1B_ZF2.almPLCFault.UACK,430674.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1B_ZF2.almPLCFault.MCmd_Enable,430674.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.MCmd_Disable,430674.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.OCmd_Shelve,430674.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.OCmd_Unshelve,430674.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.SCmd_Suppress,430674.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.SCmd_UnSuppress,430675.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1B_ZF2.almPLCFault.AEShelveTMRDN,430675.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1B_ZF2.almPLCFault.Bad,430675.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1B_ZF2.almPLCFault.Suppress,430676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.UnSuppress,430676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Shelve,430676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.UnShelve,430676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Enable,430676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Disable,430676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Ack,430676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Reset,430676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Suppressed,430676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Shelved,430676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Disabled,430676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Acked,430676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1B_ZF2.almPLCFault.Alarm,430676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Fault,430696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C_WH.Alarm.AlarmState,430696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C_WH.Alarm.GlobalReset,430696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C_WH.Alarm.FaultInAlarm,430696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C_WH.Alarm.ALRM,430696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C_WH.Alarm.ANUN,430696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C_WH.Alarm.AKED,430696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C_WH.Alarm.Resetable,430696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C_WH.Alarm.REST,430696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C_WH.Alarm.ACKN,430696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C_WH.Alarm.UACK,430696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C_WH.Alarm.MCmd_Enable,430696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C_WH.Alarm.MCmd_Disable,430696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C_WH.Alarm.OCmd_Shelve,430696.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C_WH.Alarm.OCmd_Unshelve,430696.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C_WH.Alarm.SCmd_Suppress,430696.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C_WH.Alarm.SCmd_UnSuppress,430697.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C_WH.Alarm.AEShelveTMRDN,430697.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C_WH.Alarm.Bad,430697.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C_WH.Alarm.Suppress,430698.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.UnSuppress,430698.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Shelve,430698.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.UnShelve,430698.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Enable,430698.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Disable,430698.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Ack,430698.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Reset,430698.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C_WH.Alarm.Suppressed,430698.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C_WH.Alarm.Shelved,430698.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C_WH.Alarm.Disabled,430698.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C_WH.Alarm.Acked,430698.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C_WH.Alarm.Alarm,430698.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Fault,430708.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C_WH.almPLCFault.AlarmState,430708.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C_WH.almPLCFault.GlobalReset,430708.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C_WH.almPLCFault.FaultInAlarm,430708.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C_WH.almPLCFault.ALRM,430708.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C_WH.almPLCFault.ANUN,430708.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C_WH.almPLCFault.AKED,430708.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C_WH.almPLCFault.Resetable,430708.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C_WH.almPLCFault.REST,430708.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C_WH.almPLCFault.ACKN,430708.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C_WH.almPLCFault.UACK,430708.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C_WH.almPLCFault.MCmd_Enable,430708.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C_WH.almPLCFault.MCmd_Disable,430708.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C_WH.almPLCFault.OCmd_Shelve,430708.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C_WH.almPLCFault.OCmd_Unshelve,430708.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C_WH.almPLCFault.SCmd_Suppress,430708.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C_WH.almPLCFault.SCmd_UnSuppress,430709.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C_WH.almPLCFault.AEShelveTMRDN,430709.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C_WH.almPLCFault.Bad,430709.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C_WH.almPLCFault.Suppress,430710.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.UnSuppress,430710.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Shelve,430710.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.UnShelve,430710.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Enable,430710.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Disable,430710.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Ack,430710.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Reset,430710.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Suppressed,430710.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Shelved,430710.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Disabled,430710.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Acked,430710.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C_WH.almPLCFault.Alarm,430710.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Fault,430732.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A_WH.Alarm.AlarmState,430732.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A_WH.Alarm.GlobalReset,430732.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A_WH.Alarm.FaultInAlarm,430732.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A_WH.Alarm.ALRM,430732.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A_WH.Alarm.ANUN,430732.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A_WH.Alarm.AKED,430732.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A_WH.Alarm.Resetable,430732.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A_WH.Alarm.REST,430732.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A_WH.Alarm.ACKN,430732.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A_WH.Alarm.UACK,430732.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A_WH.Alarm.MCmd_Enable,430732.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A_WH.Alarm.MCmd_Disable,430732.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A_WH.Alarm.OCmd_Shelve,430732.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A_WH.Alarm.OCmd_Unshelve,430732.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A_WH.Alarm.SCmd_Suppress,430732.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A_WH.Alarm.SCmd_UnSuppress,430733.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A_WH.Alarm.AEShelveTMRDN,430733.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A_WH.Alarm.Bad,430733.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A_WH.Alarm.Suppress,430734.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.UnSuppress,430734.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Shelve,430734.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.UnShelve,430734.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Enable,430734.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Disable,430734.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Ack,430734.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Reset,430734.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A_WH.Alarm.Suppressed,430734.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A_WH.Alarm.Shelved,430734.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A_WH.Alarm.Disabled,430734.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A_WH.Alarm.Acked,430734.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A_WH.Alarm.Alarm,430734.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Fault,430744.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A_WH.almPLCFault.AlarmState,430744.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A_WH.almPLCFault.GlobalReset,430744.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A_WH.almPLCFault.FaultInAlarm,430744.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A_WH.almPLCFault.ALRM,430744.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A_WH.almPLCFault.ANUN,430744.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A_WH.almPLCFault.AKED,430744.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A_WH.almPLCFault.Resetable,430744.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A_WH.almPLCFault.REST,430744.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A_WH.almPLCFault.ACKN,430744.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A_WH.almPLCFault.UACK,430744.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A_WH.almPLCFault.MCmd_Enable,430744.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A_WH.almPLCFault.MCmd_Disable,430744.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A_WH.almPLCFault.OCmd_Shelve,430744.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A_WH.almPLCFault.OCmd_Unshelve,430744.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A_WH.almPLCFault.SCmd_Suppress,430744.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A_WH.almPLCFault.SCmd_UnSuppress,430745.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A_WH.almPLCFault.AEShelveTMRDN,430745.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A_WH.almPLCFault.Bad,430745.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A_WH.almPLCFault.Suppress,430746.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.UnSuppress,430746.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Shelve,430746.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.UnShelve,430746.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Enable,430746.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Disable,430746.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Ack,430746.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Reset,430746.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Suppressed,430746.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Shelved,430746.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Disabled,430746.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Acked,430746.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A_WH.almPLCFault.Alarm,430746.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Fault,430766.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZF.Alarm.AlarmState,430766.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZF.Alarm.GlobalReset,430766.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZF.Alarm.FaultInAlarm,430766.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF.Alarm.ALRM,430766.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZF.Alarm.ANUN,430766.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZF.Alarm.AKED,430766.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZF.Alarm.Resetable,430766.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZF.Alarm.REST,430766.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZF.Alarm.ACKN,430766.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZF.Alarm.UACK,430766.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZF.Alarm.MCmd_Enable,430766.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF.Alarm.MCmd_Disable,430766.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF.Alarm.OCmd_Shelve,430766.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZF.Alarm.OCmd_Unshelve,430766.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZF.Alarm.SCmd_Suppress,430766.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZF.Alarm.SCmd_UnSuppress,430767.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZF.Alarm.AEShelveTMRDN,430767.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZF.Alarm.Bad,430767.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZF.Alarm.Suppress,430768.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.UnSuppress,430768.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Shelve,430768.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.UnShelve,430768.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Enable,430768.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Disable,430768.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Ack,430768.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Reset,430768.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZF.Alarm.Suppressed,430768.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZF.Alarm.Shelved,430768.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZF.Alarm.Disabled,430768.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZF.Alarm.Acked,430768.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZF.Alarm.Alarm,430768.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Fault,430778.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZF.almPLCFault.AlarmState,430778.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZF.almPLCFault.GlobalReset,430778.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZF.almPLCFault.FaultInAlarm,430778.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF.almPLCFault.ALRM,430778.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZF.almPLCFault.ANUN,430778.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZF.almPLCFault.AKED,430778.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZF.almPLCFault.Resetable,430778.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZF.almPLCFault.REST,430778.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZF.almPLCFault.ACKN,430778.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZF.almPLCFault.UACK,430778.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZF.almPLCFault.MCmd_Enable,430778.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.MCmd_Disable,430778.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.OCmd_Shelve,430778.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.OCmd_Unshelve,430778.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.SCmd_Suppress,430778.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.SCmd_UnSuppress,430779.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZF.almPLCFault.AEShelveTMRDN,430779.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZF.almPLCFault.Bad,430779.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZF.almPLCFault.Suppress,430780.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.UnSuppress,430780.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Shelve,430780.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.UnShelve,430780.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Enable,430780.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Disable,430780.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Ack,430780.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Reset,430780.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Suppressed,430780.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Shelved,430780.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Disabled,430780.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Acked,430780.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZF.almPLCFault.Alarm,430780.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Fault,430802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZF2.Alarm.AlarmState,430802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZF2.Alarm.GlobalReset,430802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZF2.Alarm.FaultInAlarm,430802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF2.Alarm.ALRM,430802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZF2.Alarm.ANUN,430802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZF2.Alarm.AKED,430802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZF2.Alarm.Resetable,430802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZF2.Alarm.REST,430802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZF2.Alarm.ACKN,430802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZF2.Alarm.UACK,430802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZF2.Alarm.MCmd_Enable,430802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF2.Alarm.MCmd_Disable,430802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF2.Alarm.OCmd_Shelve,430802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZF2.Alarm.OCmd_Unshelve,430802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZF2.Alarm.SCmd_Suppress,430802.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZF2.Alarm.SCmd_UnSuppress,430803.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZF2.Alarm.AEShelveTMRDN,430803.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZF2.Alarm.Bad,430803.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZF2.Alarm.Suppress,430804.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.UnSuppress,430804.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Shelve,430804.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.UnShelve,430804.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Enable,430804.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Disable,430804.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Ack,430804.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Reset,430804.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Suppressed,430804.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Shelved,430804.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Disabled,430804.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Acked,430804.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZF2.Alarm.Alarm,430804.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Fault,430814.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2B_ZF2.almPLCFault.AlarmState,430814.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2B_ZF2.almPLCFault.GlobalReset,430814.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2B_ZF2.almPLCFault.FaultInAlarm,430814.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2B_ZF2.almPLCFault.ALRM,430814.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2B_ZF2.almPLCFault.ANUN,430814.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2B_ZF2.almPLCFault.AKED,430814.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2B_ZF2.almPLCFault.Resetable,430814.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2B_ZF2.almPLCFault.REST,430814.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2B_ZF2.almPLCFault.ACKN,430814.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2B_ZF2.almPLCFault.UACK,430814.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2B_ZF2.almPLCFault.MCmd_Enable,430814.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.MCmd_Disable,430814.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.OCmd_Shelve,430814.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.OCmd_Unshelve,430814.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.SCmd_Suppress,430814.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.SCmd_UnSuppress,430815.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2B_ZF2.almPLCFault.AEShelveTMRDN,430815.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2B_ZF2.almPLCFault.Bad,430815.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2B_ZF2.almPLCFault.Suppress,430816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.UnSuppress,430816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Shelve,430816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.UnShelve,430816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Enable,430816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Disable,430816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Ack,430816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Reset,430816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Suppressed,430816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Shelved,430816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Disabled,430816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Acked,430816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2B_ZF2.almPLCFault.Alarm,430816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Fault,430836.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C_WH.Alarm.AlarmState,430836.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C_WH.Alarm.GlobalReset,430836.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C_WH.Alarm.FaultInAlarm,430836.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C_WH.Alarm.ALRM,430836.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C_WH.Alarm.ANUN,430836.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C_WH.Alarm.AKED,430836.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C_WH.Alarm.Resetable,430836.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C_WH.Alarm.REST,430836.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C_WH.Alarm.ACKN,430836.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C_WH.Alarm.UACK,430836.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C_WH.Alarm.MCmd_Enable,430836.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C_WH.Alarm.MCmd_Disable,430836.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C_WH.Alarm.OCmd_Shelve,430836.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C_WH.Alarm.OCmd_Unshelve,430836.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C_WH.Alarm.SCmd_Suppress,430836.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C_WH.Alarm.SCmd_UnSuppress,430837.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C_WH.Alarm.AEShelveTMRDN,430837.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C_WH.Alarm.Bad,430837.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C_WH.Alarm.Suppress,430838.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.UnSuppress,430838.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Shelve,430838.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.UnShelve,430838.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Enable,430838.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Disable,430838.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Ack,430838.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Reset,430838.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C_WH.Alarm.Suppressed,430838.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C_WH.Alarm.Shelved,430838.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C_WH.Alarm.Disabled,430838.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C_WH.Alarm.Acked,430838.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C_WH.Alarm.Alarm,430838.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Fault,430848.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C_WH.almPLCFault.AlarmState,430848.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C_WH.almPLCFault.GlobalReset,430848.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C_WH.almPLCFault.FaultInAlarm,430848.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C_WH.almPLCFault.ALRM,430848.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C_WH.almPLCFault.ANUN,430848.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C_WH.almPLCFault.AKED,430848.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C_WH.almPLCFault.Resetable,430848.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C_WH.almPLCFault.REST,430848.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C_WH.almPLCFault.ACKN,430848.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C_WH.almPLCFault.UACK,430848.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C_WH.almPLCFault.MCmd_Enable,430848.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C_WH.almPLCFault.MCmd_Disable,430848.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C_WH.almPLCFault.OCmd_Shelve,430848.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C_WH.almPLCFault.OCmd_Unshelve,430848.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C_WH.almPLCFault.SCmd_Suppress,430848.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C_WH.almPLCFault.SCmd_UnSuppress,430849.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C_WH.almPLCFault.AEShelveTMRDN,430849.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C_WH.almPLCFault.Bad,430849.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C_WH.almPLCFault.Suppress,430850.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.UnSuppress,430850.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Shelve,430850.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.UnShelve,430850.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Enable,430850.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Disable,430850.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Ack,430850.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Reset,430850.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Suppressed,430850.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Shelved,430850.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Disabled,430850.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Acked,430850.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C_WH.almPLCFault.Alarm,430850.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Fault,430872.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A_WH.Alarm.AlarmState,430872.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A_WH.Alarm.GlobalReset,430872.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A_WH.Alarm.FaultInAlarm,430872.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A_WH.Alarm.ALRM,430872.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A_WH.Alarm.ANUN,430872.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A_WH.Alarm.AKED,430872.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A_WH.Alarm.Resetable,430872.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A_WH.Alarm.REST,430872.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A_WH.Alarm.ACKN,430872.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A_WH.Alarm.UACK,430872.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A_WH.Alarm.MCmd_Enable,430872.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A_WH.Alarm.MCmd_Disable,430872.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A_WH.Alarm.OCmd_Shelve,430872.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A_WH.Alarm.OCmd_Unshelve,430872.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A_WH.Alarm.SCmd_Suppress,430872.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A_WH.Alarm.SCmd_UnSuppress,430873.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A_WH.Alarm.AEShelveTMRDN,430873.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A_WH.Alarm.Bad,430873.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A_WH.Alarm.Suppress,430874.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.UnSuppress,430874.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Shelve,430874.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.UnShelve,430874.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Enable,430874.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Disable,430874.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Ack,430874.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Reset,430874.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A_WH.Alarm.Suppressed,430874.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A_WH.Alarm.Shelved,430874.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A_WH.Alarm.Disabled,430874.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A_WH.Alarm.Acked,430874.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A_WH.Alarm.Alarm,430874.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Fault,430884.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A_WH.almPLCFault.AlarmState,430884.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A_WH.almPLCFault.GlobalReset,430884.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A_WH.almPLCFault.FaultInAlarm,430884.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A_WH.almPLCFault.ALRM,430884.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A_WH.almPLCFault.ANUN,430884.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A_WH.almPLCFault.AKED,430884.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A_WH.almPLCFault.Resetable,430884.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A_WH.almPLCFault.REST,430884.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A_WH.almPLCFault.ACKN,430884.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A_WH.almPLCFault.UACK,430884.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A_WH.almPLCFault.MCmd_Enable,430884.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A_WH.almPLCFault.MCmd_Disable,430884.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A_WH.almPLCFault.OCmd_Shelve,430884.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A_WH.almPLCFault.OCmd_Unshelve,430884.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A_WH.almPLCFault.SCmd_Suppress,430884.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A_WH.almPLCFault.SCmd_UnSuppress,430885.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A_WH.almPLCFault.AEShelveTMRDN,430885.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A_WH.almPLCFault.Bad,430885.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A_WH.almPLCFault.Suppress,430886.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.UnSuppress,430886.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Shelve,430886.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.UnShelve,430886.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Enable,430886.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Disable,430886.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Ack,430886.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Reset,430886.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Suppressed,430886.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Shelved,430886.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Disabled,430886.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Acked,430886.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A_WH.almPLCFault.Alarm,430886.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Fault,430906.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF.Alarm.AlarmState,430906.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF.Alarm.GlobalReset,430906.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF.Alarm.FaultInAlarm,430906.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF.Alarm.ALRM,430906.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF.Alarm.ANUN,430906.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF.Alarm.AKED,430906.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF.Alarm.Resetable,430906.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF.Alarm.REST,430906.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF.Alarm.ACKN,430906.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF.Alarm.UACK,430906.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF.Alarm.MCmd_Enable,430906.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF.Alarm.MCmd_Disable,430906.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF.Alarm.OCmd_Shelve,430906.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF.Alarm.OCmd_Unshelve,430906.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF.Alarm.SCmd_Suppress,430906.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF.Alarm.SCmd_UnSuppress,430907.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF.Alarm.AEShelveTMRDN,430907.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF.Alarm.Bad,430907.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF.Alarm.Suppress,430908.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.UnSuppress,430908.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Shelve,430908.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.UnShelve,430908.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Enable,430908.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Disable,430908.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Ack,430908.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Reset,430908.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF.Alarm.Suppressed,430908.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF.Alarm.Shelved,430908.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF.Alarm.Disabled,430908.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF.Alarm.Acked,430908.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF.Alarm.Alarm,430908.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Fault,430918.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF.almPLCFault.AlarmState,430918.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF.almPLCFault.GlobalReset,430918.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF.almPLCFault.FaultInAlarm,430918.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF.almPLCFault.ALRM,430918.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF.almPLCFault.ANUN,430918.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF.almPLCFault.AKED,430918.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF.almPLCFault.Resetable,430918.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF.almPLCFault.REST,430918.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF.almPLCFault.ACKN,430918.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF.almPLCFault.UACK,430918.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF.almPLCFault.MCmd_Enable,430918.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.MCmd_Disable,430918.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.OCmd_Shelve,430918.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.OCmd_Unshelve,430918.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.SCmd_Suppress,430918.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.SCmd_UnSuppress,430919.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF.almPLCFault.AEShelveTMRDN,430919.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF.almPLCFault.Bad,430919.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF.almPLCFault.Suppress,430920.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.UnSuppress,430920.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Shelve,430920.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.UnShelve,430920.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Enable,430920.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Disable,430920.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Ack,430920.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Reset,430920.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Suppressed,430920.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Shelved,430920.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Disabled,430920.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Acked,430920.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF.almPLCFault.Alarm,430920.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Fault,430942.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF3.Alarm.AlarmState,430942.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF3.Alarm.GlobalReset,430942.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF3.Alarm.FaultInAlarm,430942.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF3.Alarm.ALRM,430942.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF3.Alarm.ANUN,430942.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF3.Alarm.AKED,430942.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF3.Alarm.Resetable,430942.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF3.Alarm.REST,430942.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF3.Alarm.ACKN,430942.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF3.Alarm.UACK,430942.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF3.Alarm.MCmd_Enable,430942.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF3.Alarm.MCmd_Disable,430942.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF3.Alarm.OCmd_Shelve,430942.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF3.Alarm.OCmd_Unshelve,430942.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF3.Alarm.SCmd_Suppress,430942.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF3.Alarm.SCmd_UnSuppress,430943.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF3.Alarm.AEShelveTMRDN,430943.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF3.Alarm.Bad,430943.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF3.Alarm.Suppress,430944.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.UnSuppress,430944.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Shelve,430944.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.UnShelve,430944.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Enable,430944.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Disable,430944.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Ack,430944.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Reset,430944.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Suppressed,430944.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Shelved,430944.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Disabled,430944.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Acked,430944.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF3.Alarm.Alarm,430944.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Fault,430954.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF3.almPLCFault.AlarmState,430954.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF3.almPLCFault.GlobalReset,430954.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF3.almPLCFault.FaultInAlarm,430954.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF3.almPLCFault.ALRM,430954.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF3.almPLCFault.ANUN,430954.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF3.almPLCFault.AKED,430954.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF3.almPLCFault.Resetable,430954.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF3.almPLCFault.REST,430954.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF3.almPLCFault.ACKN,430954.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF3.almPLCFault.UACK,430954.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF3.almPLCFault.MCmd_Enable,430954.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.MCmd_Disable,430954.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.OCmd_Shelve,430954.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.OCmd_Unshelve,430954.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.SCmd_Suppress,430954.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.SCmd_UnSuppress,430955.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF3.almPLCFault.AEShelveTMRDN,430955.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF3.almPLCFault.Bad,430955.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF3.almPLCFault.Suppress,430956.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.UnSuppress,430956.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Shelve,430956.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.UnShelve,430956.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Enable,430956.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Disable,430956.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Ack,430956.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Reset,430956.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Suppressed,430956.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Shelved,430956.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Disabled,430956.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Acked,430956.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF3.almPLCFault.Alarm,430956.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Fault,430976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF4.Alarm.AlarmState,430976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF4.Alarm.GlobalReset,430976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF4.Alarm.FaultInAlarm,430976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF4.Alarm.ALRM,430976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF4.Alarm.ANUN,430976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF4.Alarm.AKED,430976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF4.Alarm.Resetable,430976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF4.Alarm.REST,430976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF4.Alarm.ACKN,430976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF4.Alarm.UACK,430976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF4.Alarm.MCmd_Enable,430976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF4.Alarm.MCmd_Disable,430976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF4.Alarm.OCmd_Shelve,430976.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF4.Alarm.OCmd_Unshelve,430976.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF4.Alarm.SCmd_Suppress,430976.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF4.Alarm.SCmd_UnSuppress,430977.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF4.Alarm.AEShelveTMRDN,430977.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF4.Alarm.Bad,430977.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF4.Alarm.Suppress,430978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.UnSuppress,430978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Shelve,430978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.UnShelve,430978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Enable,430978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Disable,430978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Ack,430978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Reset,430978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Suppressed,430978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Shelved,430978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Disabled,430978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Acked,430978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF4.Alarm.Alarm,430978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Fault,430988.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3B_ZF4.almPLCFault.AlarmState,430988.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3B_ZF4.almPLCFault.GlobalReset,430988.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3B_ZF4.almPLCFault.FaultInAlarm,430988.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3B_ZF4.almPLCFault.ALRM,430988.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3B_ZF4.almPLCFault.ANUN,430988.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3B_ZF4.almPLCFault.AKED,430988.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3B_ZF4.almPLCFault.Resetable,430988.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3B_ZF4.almPLCFault.REST,430988.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3B_ZF4.almPLCFault.ACKN,430988.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3B_ZF4.almPLCFault.UACK,430988.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3B_ZF4.almPLCFault.MCmd_Enable,430988.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.MCmd_Disable,430988.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.OCmd_Shelve,430988.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.OCmd_Unshelve,430988.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.SCmd_Suppress,430988.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.SCmd_UnSuppress,430989.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3B_ZF4.almPLCFault.AEShelveTMRDN,430989.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3B_ZF4.almPLCFault.Bad,430989.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3B_ZF4.almPLCFault.Suppress,430990.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.UnSuppress,430990.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Shelve,430990.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.UnShelve,430990.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Enable,430990.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Disable,430990.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Ack,430990.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Reset,430990.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Suppressed,430990.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Shelved,430990.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Disabled,430990.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Acked,430990.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3B_ZF4.almPLCFault.Alarm,430990.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Fault,431012.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C_WH.Alarm.AlarmState,431012.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C_WH.Alarm.GlobalReset,431012.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C_WH.Alarm.FaultInAlarm,431012.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C_WH.Alarm.ALRM,431012.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C_WH.Alarm.ANUN,431012.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C_WH.Alarm.AKED,431012.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C_WH.Alarm.Resetable,431012.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C_WH.Alarm.REST,431012.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C_WH.Alarm.ACKN,431012.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C_WH.Alarm.UACK,431012.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C_WH.Alarm.MCmd_Enable,431012.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C_WH.Alarm.MCmd_Disable,431012.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C_WH.Alarm.OCmd_Shelve,431012.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C_WH.Alarm.OCmd_Unshelve,431012.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C_WH.Alarm.SCmd_Suppress,431012.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C_WH.Alarm.SCmd_UnSuppress,431013.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C_WH.Alarm.AEShelveTMRDN,431013.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C_WH.Alarm.Bad,431013.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C_WH.Alarm.Suppress,431014.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.UnSuppress,431014.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Shelve,431014.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.UnShelve,431014.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Enable,431014.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Disable,431014.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Ack,431014.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Reset,431014.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C_WH.Alarm.Suppressed,431014.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C_WH.Alarm.Shelved,431014.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C_WH.Alarm.Disabled,431014.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C_WH.Alarm.Acked,431014.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C_WH.Alarm.Alarm,431014.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Fault,431024.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C_WH.almPLCFault.AlarmState,431024.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C_WH.almPLCFault.GlobalReset,431024.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C_WH.almPLCFault.FaultInAlarm,431024.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C_WH.almPLCFault.ALRM,431024.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C_WH.almPLCFault.ANUN,431024.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C_WH.almPLCFault.AKED,431024.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C_WH.almPLCFault.Resetable,431024.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C_WH.almPLCFault.REST,431024.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C_WH.almPLCFault.ACKN,431024.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C_WH.almPLCFault.UACK,431024.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C_WH.almPLCFault.MCmd_Enable,431024.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C_WH.almPLCFault.MCmd_Disable,431024.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C_WH.almPLCFault.OCmd_Shelve,431024.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C_WH.almPLCFault.OCmd_Unshelve,431024.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C_WH.almPLCFault.SCmd_Suppress,431024.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C_WH.almPLCFault.SCmd_UnSuppress,431025.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C_WH.almPLCFault.AEShelveTMRDN,431025.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C_WH.almPLCFault.Bad,431025.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C_WH.almPLCFault.Suppress,431026.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.UnSuppress,431026.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Shelve,431026.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.UnShelve,431026.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Enable,431026.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Disable,431026.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Ack,431026.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Reset,431026.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Suppressed,431026.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Shelved,431026.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Disabled,431026.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Acked,431026.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C_WH.almPLCFault.Alarm,431026.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Fault,431046.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D_WH.Alarm.AlarmState,431046.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D_WH.Alarm.GlobalReset,431046.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D_WH.Alarm.FaultInAlarm,431046.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D_WH.Alarm.ALRM,431046.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D_WH.Alarm.ANUN,431046.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D_WH.Alarm.AKED,431046.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D_WH.Alarm.Resetable,431046.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D_WH.Alarm.REST,431046.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D_WH.Alarm.ACKN,431046.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D_WH.Alarm.UACK,431046.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D_WH.Alarm.MCmd_Enable,431046.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D_WH.Alarm.MCmd_Disable,431046.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D_WH.Alarm.OCmd_Shelve,431046.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D_WH.Alarm.OCmd_Unshelve,431046.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D_WH.Alarm.SCmd_Suppress,431046.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D_WH.Alarm.SCmd_UnSuppress,431047.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D_WH.Alarm.AEShelveTMRDN,431047.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D_WH.Alarm.Bad,431047.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D_WH.Alarm.Suppress,431048.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.UnSuppress,431048.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Shelve,431048.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.UnShelve,431048.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Enable,431048.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Disable,431048.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Ack,431048.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Reset,431048.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D_WH.Alarm.Suppressed,431048.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D_WH.Alarm.Shelved,431048.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D_WH.Alarm.Disabled,431048.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D_WH.Alarm.Acked,431048.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D_WH.Alarm.Alarm,431048.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Fault,431058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D_WH.almPLCFault.AlarmState,431058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D_WH.almPLCFault.GlobalReset,431058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D_WH.almPLCFault.FaultInAlarm,431058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D_WH.almPLCFault.ALRM,431058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D_WH.almPLCFault.ANUN,431058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D_WH.almPLCFault.AKED,431058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D_WH.almPLCFault.Resetable,431058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D_WH.almPLCFault.REST,431058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D_WH.almPLCFault.ACKN,431058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D_WH.almPLCFault.UACK,431058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D_WH.almPLCFault.MCmd_Enable,431058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D_WH.almPLCFault.MCmd_Disable,431058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D_WH.almPLCFault.OCmd_Shelve,431058.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D_WH.almPLCFault.OCmd_Unshelve,431058.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D_WH.almPLCFault.SCmd_Suppress,431058.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D_WH.almPLCFault.SCmd_UnSuppress,431059.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D_WH.almPLCFault.AEShelveTMRDN,431059.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D_WH.almPLCFault.Bad,431059.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D_WH.almPLCFault.Suppress,431060.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.UnSuppress,431060.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Shelve,431060.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.UnShelve,431060.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Enable,431060.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Disable,431060.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Ack,431060.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Reset,431060.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Suppressed,431060.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Shelved,431060.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Disabled,431060.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Acked,431060.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D_WH.almPLCFault.Alarm,431060.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Fault,431082.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A_WH.Alarm.AlarmState,431082.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A_WH.Alarm.GlobalReset,431082.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A_WH.Alarm.FaultInAlarm,431082.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A_WH.Alarm.ALRM,431082.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A_WH.Alarm.ANUN,431082.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A_WH.Alarm.AKED,431082.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A_WH.Alarm.Resetable,431082.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A_WH.Alarm.REST,431082.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A_WH.Alarm.ACKN,431082.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A_WH.Alarm.UACK,431082.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A_WH.Alarm.MCmd_Enable,431082.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A_WH.Alarm.MCmd_Disable,431082.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A_WH.Alarm.OCmd_Shelve,431082.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A_WH.Alarm.OCmd_Unshelve,431082.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A_WH.Alarm.SCmd_Suppress,431082.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A_WH.Alarm.SCmd_UnSuppress,431083.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A_WH.Alarm.AEShelveTMRDN,431083.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A_WH.Alarm.Bad,431083.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A_WH.Alarm.Suppress,431084.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.UnSuppress,431084.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Shelve,431084.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.UnShelve,431084.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Enable,431084.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Disable,431084.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Ack,431084.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Reset,431084.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A_WH.Alarm.Suppressed,431084.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A_WH.Alarm.Shelved,431084.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A_WH.Alarm.Disabled,431084.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A_WH.Alarm.Acked,431084.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A_WH.Alarm.Alarm,431084.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Fault,431094.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A_WH.almPLCFault.AlarmState,431094.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A_WH.almPLCFault.GlobalReset,431094.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A_WH.almPLCFault.FaultInAlarm,431094.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A_WH.almPLCFault.ALRM,431094.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A_WH.almPLCFault.ANUN,431094.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A_WH.almPLCFault.AKED,431094.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A_WH.almPLCFault.Resetable,431094.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A_WH.almPLCFault.REST,431094.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A_WH.almPLCFault.ACKN,431094.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A_WH.almPLCFault.UACK,431094.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A_WH.almPLCFault.MCmd_Enable,431094.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A_WH.almPLCFault.MCmd_Disable,431094.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A_WH.almPLCFault.OCmd_Shelve,431094.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A_WH.almPLCFault.OCmd_Unshelve,431094.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A_WH.almPLCFault.SCmd_Suppress,431094.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A_WH.almPLCFault.SCmd_UnSuppress,431095.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A_WH.almPLCFault.AEShelveTMRDN,431095.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A_WH.almPLCFault.Bad,431095.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A_WH.almPLCFault.Suppress,431096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.UnSuppress,431096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Shelve,431096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.UnShelve,431096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Enable,431096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Disable,431096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Ack,431096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Reset,431096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Suppressed,431096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Shelved,431096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Disabled,431096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Acked,431096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A_WH.almPLCFault.Alarm,431096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Fault,431116.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF.Alarm.AlarmState,431116.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF.Alarm.GlobalReset,431116.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF.Alarm.FaultInAlarm,431116.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF.Alarm.ALRM,431116.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF.Alarm.ANUN,431116.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF.Alarm.AKED,431116.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF.Alarm.Resetable,431116.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF.Alarm.REST,431116.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF.Alarm.ACKN,431116.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF.Alarm.UACK,431116.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF.Alarm.MCmd_Enable,431116.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF.Alarm.MCmd_Disable,431116.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF.Alarm.OCmd_Shelve,431116.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF.Alarm.OCmd_Unshelve,431116.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF.Alarm.SCmd_Suppress,431116.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF.Alarm.SCmd_UnSuppress,431117.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF.Alarm.AEShelveTMRDN,431117.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF.Alarm.Bad,431117.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF.Alarm.Suppress,431118.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.UnSuppress,431118.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Shelve,431118.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.UnShelve,431118.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Enable,431118.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Disable,431118.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Ack,431118.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Reset,431118.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF.Alarm.Suppressed,431118.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF.Alarm.Shelved,431118.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF.Alarm.Disabled,431118.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF.Alarm.Acked,431118.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF.Alarm.Alarm,431118.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Fault,431128.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF.almPLCFault.AlarmState,431128.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF.almPLCFault.GlobalReset,431128.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF.almPLCFault.FaultInAlarm,431128.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF.almPLCFault.ALRM,431128.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF.almPLCFault.ANUN,431128.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF.almPLCFault.AKED,431128.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF.almPLCFault.Resetable,431128.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF.almPLCFault.REST,431128.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF.almPLCFault.ACKN,431128.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF.almPLCFault.UACK,431128.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF.almPLCFault.MCmd_Enable,431128.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.MCmd_Disable,431128.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.OCmd_Shelve,431128.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.OCmd_Unshelve,431128.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.SCmd_Suppress,431128.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.SCmd_UnSuppress,431129.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF.almPLCFault.AEShelveTMRDN,431129.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF.almPLCFault.Bad,431129.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF.almPLCFault.Suppress,431130.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.UnSuppress,431130.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Shelve,431130.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.UnShelve,431130.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Enable,431130.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Disable,431130.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Ack,431130.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Reset,431130.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Suppressed,431130.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Shelved,431130.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Disabled,431130.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Acked,431130.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF.almPLCFault.Alarm,431130.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Fault,431152.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF3.Alarm.AlarmState,431152.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF3.Alarm.GlobalReset,431152.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF3.Alarm.FaultInAlarm,431152.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF3.Alarm.ALRM,431152.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF3.Alarm.ANUN,431152.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF3.Alarm.AKED,431152.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF3.Alarm.Resetable,431152.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF3.Alarm.REST,431152.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF3.Alarm.ACKN,431152.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF3.Alarm.UACK,431152.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF3.Alarm.MCmd_Enable,431152.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF3.Alarm.MCmd_Disable,431152.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF3.Alarm.OCmd_Shelve,431152.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF3.Alarm.OCmd_Unshelve,431152.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF3.Alarm.SCmd_Suppress,431152.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF3.Alarm.SCmd_UnSuppress,431153.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF3.Alarm.AEShelveTMRDN,431153.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF3.Alarm.Bad,431153.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF3.Alarm.Suppress,431154.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.UnSuppress,431154.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Shelve,431154.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.UnShelve,431154.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Enable,431154.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Disable,431154.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Ack,431154.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Reset,431154.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Suppressed,431154.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Shelved,431154.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Disabled,431154.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Acked,431154.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF3.Alarm.Alarm,431154.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Fault,431164.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF3.almPLCFault.AlarmState,431164.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF3.almPLCFault.GlobalReset,431164.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF3.almPLCFault.FaultInAlarm,431164.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF3.almPLCFault.ALRM,431164.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF3.almPLCFault.ANUN,431164.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF3.almPLCFault.AKED,431164.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF3.almPLCFault.Resetable,431164.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF3.almPLCFault.REST,431164.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF3.almPLCFault.ACKN,431164.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF3.almPLCFault.UACK,431164.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF3.almPLCFault.MCmd_Enable,431164.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.MCmd_Disable,431164.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.OCmd_Shelve,431164.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.OCmd_Unshelve,431164.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.SCmd_Suppress,431164.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.SCmd_UnSuppress,431165.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF3.almPLCFault.AEShelveTMRDN,431165.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF3.almPLCFault.Bad,431165.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF3.almPLCFault.Suppress,431166.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.UnSuppress,431166.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Shelve,431166.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.UnShelve,431166.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Enable,431166.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Disable,431166.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Ack,431166.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Reset,431166.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Suppressed,431166.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Shelved,431166.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Disabled,431166.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Acked,431166.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF3.almPLCFault.Alarm,431166.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Fault,431186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF4.Alarm.AlarmState,431186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF4.Alarm.GlobalReset,431186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF4.Alarm.FaultInAlarm,431186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF4.Alarm.ALRM,431186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF4.Alarm.ANUN,431186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF4.Alarm.AKED,431186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF4.Alarm.Resetable,431186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF4.Alarm.REST,431186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF4.Alarm.ACKN,431186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF4.Alarm.UACK,431186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF4.Alarm.MCmd_Enable,431186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF4.Alarm.MCmd_Disable,431186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF4.Alarm.OCmd_Shelve,431186.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF4.Alarm.OCmd_Unshelve,431186.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF4.Alarm.SCmd_Suppress,431186.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF4.Alarm.SCmd_UnSuppress,431187.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF4.Alarm.AEShelveTMRDN,431187.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF4.Alarm.Bad,431187.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF4.Alarm.Suppress,431188.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.UnSuppress,431188.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Shelve,431188.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.UnShelve,431188.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Enable,431188.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Disable,431188.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Ack,431188.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Reset,431188.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Suppressed,431188.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Shelved,431188.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Disabled,431188.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Acked,431188.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF4.Alarm.Alarm,431188.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Fault,431198.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4B_ZF4.almPLCFault.AlarmState,431198.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4B_ZF4.almPLCFault.GlobalReset,431198.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4B_ZF4.almPLCFault.FaultInAlarm,431198.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4B_ZF4.almPLCFault.ALRM,431198.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4B_ZF4.almPLCFault.ANUN,431198.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4B_ZF4.almPLCFault.AKED,431198.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4B_ZF4.almPLCFault.Resetable,431198.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4B_ZF4.almPLCFault.REST,431198.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4B_ZF4.almPLCFault.ACKN,431198.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4B_ZF4.almPLCFault.UACK,431198.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4B_ZF4.almPLCFault.MCmd_Enable,431198.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.MCmd_Disable,431198.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.OCmd_Shelve,431198.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.OCmd_Unshelve,431198.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.SCmd_Suppress,431198.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.SCmd_UnSuppress,431199.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4B_ZF4.almPLCFault.AEShelveTMRDN,431199.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4B_ZF4.almPLCFault.Bad,431199.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4B_ZF4.almPLCFault.Suppress,431200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.UnSuppress,431200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Shelve,431200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.UnShelve,431200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Enable,431200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Disable,431200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Ack,431200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Reset,431200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Suppressed,431200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Shelved,431200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Disabled,431200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Acked,431200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4B_ZF4.almPLCFault.Alarm,431200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Fault,431222.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C_WH.Alarm.AlarmState,431222.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C_WH.Alarm.GlobalReset,431222.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C_WH.Alarm.FaultInAlarm,431222.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C_WH.Alarm.ALRM,431222.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C_WH.Alarm.ANUN,431222.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C_WH.Alarm.AKED,431222.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C_WH.Alarm.Resetable,431222.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C_WH.Alarm.REST,431222.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C_WH.Alarm.ACKN,431222.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C_WH.Alarm.UACK,431222.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C_WH.Alarm.MCmd_Enable,431222.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C_WH.Alarm.MCmd_Disable,431222.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C_WH.Alarm.OCmd_Shelve,431222.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C_WH.Alarm.OCmd_Unshelve,431222.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C_WH.Alarm.SCmd_Suppress,431222.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C_WH.Alarm.SCmd_UnSuppress,431223.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C_WH.Alarm.AEShelveTMRDN,431223.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C_WH.Alarm.Bad,431223.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C_WH.Alarm.Suppress,431224.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.UnSuppress,431224.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Shelve,431224.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.UnShelve,431224.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Enable,431224.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Disable,431224.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Ack,431224.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Reset,431224.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C_WH.Alarm.Suppressed,431224.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C_WH.Alarm.Shelved,431224.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C_WH.Alarm.Disabled,431224.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C_WH.Alarm.Acked,431224.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C_WH.Alarm.Alarm,431224.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Fault,431234.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C_WH.almPLCFault.AlarmState,431234.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C_WH.almPLCFault.GlobalReset,431234.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C_WH.almPLCFault.FaultInAlarm,431234.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C_WH.almPLCFault.ALRM,431234.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C_WH.almPLCFault.ANUN,431234.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C_WH.almPLCFault.AKED,431234.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C_WH.almPLCFault.Resetable,431234.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C_WH.almPLCFault.REST,431234.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C_WH.almPLCFault.ACKN,431234.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C_WH.almPLCFault.UACK,431234.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C_WH.almPLCFault.MCmd_Enable,431234.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C_WH.almPLCFault.MCmd_Disable,431234.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C_WH.almPLCFault.OCmd_Shelve,431234.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C_WH.almPLCFault.OCmd_Unshelve,431234.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C_WH.almPLCFault.SCmd_Suppress,431234.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C_WH.almPLCFault.SCmd_UnSuppress,431235.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C_WH.almPLCFault.AEShelveTMRDN,431235.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C_WH.almPLCFault.Bad,431235.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C_WH.almPLCFault.Suppress,431236.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.UnSuppress,431236.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Shelve,431236.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.UnShelve,431236.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Enable,431236.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Disable,431236.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Ack,431236.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Reset,431236.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Suppressed,431236.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Shelved,431236.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Disabled,431236.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Acked,431236.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C_WH.almPLCFault.Alarm,431236.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Fault,431256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D_WH.Alarm.AlarmState,431256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D_WH.Alarm.GlobalReset,431256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D_WH.Alarm.FaultInAlarm,431256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D_WH.Alarm.ALRM,431256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D_WH.Alarm.ANUN,431256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D_WH.Alarm.AKED,431256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D_WH.Alarm.Resetable,431256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D_WH.Alarm.REST,431256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D_WH.Alarm.ACKN,431256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D_WH.Alarm.UACK,431256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D_WH.Alarm.MCmd_Enable,431256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D_WH.Alarm.MCmd_Disable,431256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D_WH.Alarm.OCmd_Shelve,431256.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D_WH.Alarm.OCmd_Unshelve,431256.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D_WH.Alarm.SCmd_Suppress,431256.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D_WH.Alarm.SCmd_UnSuppress,431257.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D_WH.Alarm.AEShelveTMRDN,431257.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D_WH.Alarm.Bad,431257.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D_WH.Alarm.Suppress,431258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.UnSuppress,431258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Shelve,431258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.UnShelve,431258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Enable,431258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Disable,431258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Ack,431258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Reset,431258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D_WH.Alarm.Suppressed,431258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D_WH.Alarm.Shelved,431258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D_WH.Alarm.Disabled,431258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D_WH.Alarm.Acked,431258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D_WH.Alarm.Alarm,431258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Fault,431268.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D_WH.almPLCFault.AlarmState,431268.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D_WH.almPLCFault.GlobalReset,431268.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D_WH.almPLCFault.FaultInAlarm,431268.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D_WH.almPLCFault.ALRM,431268.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D_WH.almPLCFault.ANUN,431268.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D_WH.almPLCFault.AKED,431268.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D_WH.almPLCFault.Resetable,431268.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D_WH.almPLCFault.REST,431268.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D_WH.almPLCFault.ACKN,431268.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D_WH.almPLCFault.UACK,431268.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D_WH.almPLCFault.MCmd_Enable,431268.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D_WH.almPLCFault.MCmd_Disable,431268.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D_WH.almPLCFault.OCmd_Shelve,431268.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D_WH.almPLCFault.OCmd_Unshelve,431268.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D_WH.almPLCFault.SCmd_Suppress,431268.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D_WH.almPLCFault.SCmd_UnSuppress,431269.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D_WH.almPLCFault.AEShelveTMRDN,431269.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D_WH.almPLCFault.Bad,431269.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D_WH.almPLCFault.Suppress,431270.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.UnSuppress,431270.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Shelve,431270.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.UnShelve,431270.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Enable,431270.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Disable,431270.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Ack,431270.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Reset,431270.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Suppressed,431270.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Shelved,431270.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Disabled,431270.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Acked,431270.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D_WH.almPLCFault.Alarm,431270.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Fault,431292.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A_WH.Alarm.AlarmState,431292.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A_WH.Alarm.GlobalReset,431292.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A_WH.Alarm.FaultInAlarm,431292.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A_WH.Alarm.ALRM,431292.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A_WH.Alarm.ANUN,431292.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A_WH.Alarm.AKED,431292.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A_WH.Alarm.Resetable,431292.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A_WH.Alarm.REST,431292.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A_WH.Alarm.ACKN,431292.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A_WH.Alarm.UACK,431292.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A_WH.Alarm.MCmd_Enable,431292.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A_WH.Alarm.MCmd_Disable,431292.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A_WH.Alarm.OCmd_Shelve,431292.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A_WH.Alarm.OCmd_Unshelve,431292.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A_WH.Alarm.SCmd_Suppress,431292.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A_WH.Alarm.SCmd_UnSuppress,431293.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A_WH.Alarm.AEShelveTMRDN,431293.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A_WH.Alarm.Bad,431293.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A_WH.Alarm.Suppress,431294.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.UnSuppress,431294.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Shelve,431294.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.UnShelve,431294.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Enable,431294.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Disable,431294.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Ack,431294.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Reset,431294.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A_WH.Alarm.Suppressed,431294.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A_WH.Alarm.Shelved,431294.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A_WH.Alarm.Disabled,431294.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A_WH.Alarm.Acked,431294.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A_WH.Alarm.Alarm,431294.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Fault,431304.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A_WH.almPLCFault.AlarmState,431304.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A_WH.almPLCFault.GlobalReset,431304.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A_WH.almPLCFault.FaultInAlarm,431304.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A_WH.almPLCFault.ALRM,431304.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A_WH.almPLCFault.ANUN,431304.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A_WH.almPLCFault.AKED,431304.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A_WH.almPLCFault.Resetable,431304.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A_WH.almPLCFault.REST,431304.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A_WH.almPLCFault.ACKN,431304.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A_WH.almPLCFault.UACK,431304.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A_WH.almPLCFault.MCmd_Enable,431304.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A_WH.almPLCFault.MCmd_Disable,431304.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A_WH.almPLCFault.OCmd_Shelve,431304.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A_WH.almPLCFault.OCmd_Unshelve,431304.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A_WH.almPLCFault.SCmd_Suppress,431304.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A_WH.almPLCFault.SCmd_UnSuppress,431305.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A_WH.almPLCFault.AEShelveTMRDN,431305.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A_WH.almPLCFault.Bad,431305.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A_WH.almPLCFault.Suppress,431306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.UnSuppress,431306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Shelve,431306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.UnShelve,431306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Enable,431306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Disable,431306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Ack,431306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Reset,431306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Suppressed,431306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Shelved,431306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Disabled,431306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Acked,431306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A_WH.almPLCFault.Alarm,431306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Fault,431326.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF.Alarm.AlarmState,431326.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF.Alarm.GlobalReset,431326.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF.Alarm.FaultInAlarm,431326.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF.Alarm.ALRM,431326.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF.Alarm.ANUN,431326.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF.Alarm.AKED,431326.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF.Alarm.Resetable,431326.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF.Alarm.REST,431326.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF.Alarm.ACKN,431326.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF.Alarm.UACK,431326.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF.Alarm.MCmd_Enable,431326.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF.Alarm.MCmd_Disable,431326.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF.Alarm.OCmd_Shelve,431326.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF.Alarm.OCmd_Unshelve,431326.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF.Alarm.SCmd_Suppress,431326.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF.Alarm.SCmd_UnSuppress,431327.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF.Alarm.AEShelveTMRDN,431327.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF.Alarm.Bad,431327.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF.Alarm.Suppress,431328.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.UnSuppress,431328.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Shelve,431328.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.UnShelve,431328.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Enable,431328.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Disable,431328.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Ack,431328.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Reset,431328.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF.Alarm.Suppressed,431328.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF.Alarm.Shelved,431328.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF.Alarm.Disabled,431328.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF.Alarm.Acked,431328.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF.Alarm.Alarm,431328.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Fault,431338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF.almPLCFault.AlarmState,431338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF.almPLCFault.GlobalReset,431338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF.almPLCFault.FaultInAlarm,431338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF.almPLCFault.ALRM,431338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF.almPLCFault.ANUN,431338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF.almPLCFault.AKED,431338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF.almPLCFault.Resetable,431338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF.almPLCFault.REST,431338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF.almPLCFault.ACKN,431338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF.almPLCFault.UACK,431338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF.almPLCFault.MCmd_Enable,431338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.MCmd_Disable,431338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.OCmd_Shelve,431338.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.OCmd_Unshelve,431338.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.SCmd_Suppress,431338.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.SCmd_UnSuppress,431339.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF.almPLCFault.AEShelveTMRDN,431339.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF.almPLCFault.Bad,431339.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF.almPLCFault.Suppress,431340.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.UnSuppress,431340.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Shelve,431340.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.UnShelve,431340.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Enable,431340.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Disable,431340.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Ack,431340.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Reset,431340.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Suppressed,431340.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Shelved,431340.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Disabled,431340.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Acked,431340.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF.almPLCFault.Alarm,431340.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Fault,431362.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF3.Alarm.AlarmState,431362.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF3.Alarm.GlobalReset,431362.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF3.Alarm.FaultInAlarm,431362.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF3.Alarm.ALRM,431362.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF3.Alarm.ANUN,431362.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF3.Alarm.AKED,431362.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF3.Alarm.Resetable,431362.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF3.Alarm.REST,431362.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF3.Alarm.ACKN,431362.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF3.Alarm.UACK,431362.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF3.Alarm.MCmd_Enable,431362.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF3.Alarm.MCmd_Disable,431362.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF3.Alarm.OCmd_Shelve,431362.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF3.Alarm.OCmd_Unshelve,431362.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF3.Alarm.SCmd_Suppress,431362.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF3.Alarm.SCmd_UnSuppress,431363.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF3.Alarm.AEShelveTMRDN,431363.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF3.Alarm.Bad,431363.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF3.Alarm.Suppress,431364.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.UnSuppress,431364.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Shelve,431364.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.UnShelve,431364.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Enable,431364.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Disable,431364.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Ack,431364.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Reset,431364.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Suppressed,431364.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Shelved,431364.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Disabled,431364.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Acked,431364.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF3.Alarm.Alarm,431364.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Fault,431374.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF3.almPLCFault.AlarmState,431374.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF3.almPLCFault.GlobalReset,431374.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF3.almPLCFault.FaultInAlarm,431374.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF3.almPLCFault.ALRM,431374.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF3.almPLCFault.ANUN,431374.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF3.almPLCFault.AKED,431374.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF3.almPLCFault.Resetable,431374.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF3.almPLCFault.REST,431374.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF3.almPLCFault.ACKN,431374.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF3.almPLCFault.UACK,431374.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF3.almPLCFault.MCmd_Enable,431374.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.MCmd_Disable,431374.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.OCmd_Shelve,431374.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.OCmd_Unshelve,431374.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.SCmd_Suppress,431374.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.SCmd_UnSuppress,431375.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF3.almPLCFault.AEShelveTMRDN,431375.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF3.almPLCFault.Bad,431375.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF3.almPLCFault.Suppress,431376.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.UnSuppress,431376.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Shelve,431376.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.UnShelve,431376.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Enable,431376.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Disable,431376.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Ack,431376.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Reset,431376.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Suppressed,431376.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Shelved,431376.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Disabled,431376.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Acked,431376.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF3.almPLCFault.Alarm,431376.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Fault,431396.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF4.Alarm.AlarmState,431396.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF4.Alarm.GlobalReset,431396.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF4.Alarm.FaultInAlarm,431396.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF4.Alarm.ALRM,431396.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF4.Alarm.ANUN,431396.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF4.Alarm.AKED,431396.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF4.Alarm.Resetable,431396.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF4.Alarm.REST,431396.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF4.Alarm.ACKN,431396.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF4.Alarm.UACK,431396.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF4.Alarm.MCmd_Enable,431396.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF4.Alarm.MCmd_Disable,431396.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF4.Alarm.OCmd_Shelve,431396.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF4.Alarm.OCmd_Unshelve,431396.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF4.Alarm.SCmd_Suppress,431396.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF4.Alarm.SCmd_UnSuppress,431397.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF4.Alarm.AEShelveTMRDN,431397.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF4.Alarm.Bad,431397.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF4.Alarm.Suppress,431398.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.UnSuppress,431398.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Shelve,431398.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.UnShelve,431398.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Enable,431398.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Disable,431398.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Ack,431398.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Reset,431398.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Suppressed,431398.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Shelved,431398.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Disabled,431398.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Acked,431398.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF4.Alarm.Alarm,431398.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Fault,431408.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5B_ZF4.almPLCFault.AlarmState,431408.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5B_ZF4.almPLCFault.GlobalReset,431408.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5B_ZF4.almPLCFault.FaultInAlarm,431408.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5B_ZF4.almPLCFault.ALRM,431408.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5B_ZF4.almPLCFault.ANUN,431408.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5B_ZF4.almPLCFault.AKED,431408.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5B_ZF4.almPLCFault.Resetable,431408.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5B_ZF4.almPLCFault.REST,431408.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5B_ZF4.almPLCFault.ACKN,431408.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5B_ZF4.almPLCFault.UACK,431408.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5B_ZF4.almPLCFault.MCmd_Enable,431408.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.MCmd_Disable,431408.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.OCmd_Shelve,431408.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.OCmd_Unshelve,431408.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.SCmd_Suppress,431408.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.SCmd_UnSuppress,431409.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5B_ZF4.almPLCFault.AEShelveTMRDN,431409.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5B_ZF4.almPLCFault.Bad,431409.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5B_ZF4.almPLCFault.Suppress,431410.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.UnSuppress,431410.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Shelve,431410.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.UnShelve,431410.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Enable,431410.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Disable,431410.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Ack,431410.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Reset,431410.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Suppressed,431410.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Shelved,431410.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Disabled,431410.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Acked,431410.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5B_ZF4.almPLCFault.Alarm,431410.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Fault,431432.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C_WH.Alarm.AlarmState,431432.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C_WH.Alarm.GlobalReset,431432.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C_WH.Alarm.FaultInAlarm,431432.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C_WH.Alarm.ALRM,431432.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C_WH.Alarm.ANUN,431432.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C_WH.Alarm.AKED,431432.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C_WH.Alarm.Resetable,431432.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C_WH.Alarm.REST,431432.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C_WH.Alarm.ACKN,431432.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C_WH.Alarm.UACK,431432.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C_WH.Alarm.MCmd_Enable,431432.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C_WH.Alarm.MCmd_Disable,431432.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C_WH.Alarm.OCmd_Shelve,431432.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C_WH.Alarm.OCmd_Unshelve,431432.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C_WH.Alarm.SCmd_Suppress,431432.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C_WH.Alarm.SCmd_UnSuppress,431433.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C_WH.Alarm.AEShelveTMRDN,431433.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C_WH.Alarm.Bad,431433.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C_WH.Alarm.Suppress,431434.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.UnSuppress,431434.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Shelve,431434.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.UnShelve,431434.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Enable,431434.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Disable,431434.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Ack,431434.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Reset,431434.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C_WH.Alarm.Suppressed,431434.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C_WH.Alarm.Shelved,431434.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C_WH.Alarm.Disabled,431434.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C_WH.Alarm.Acked,431434.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C_WH.Alarm.Alarm,431434.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Fault,431444.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C_WH.almPLCFault.AlarmState,431444.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C_WH.almPLCFault.GlobalReset,431444.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C_WH.almPLCFault.FaultInAlarm,431444.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C_WH.almPLCFault.ALRM,431444.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C_WH.almPLCFault.ANUN,431444.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C_WH.almPLCFault.AKED,431444.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C_WH.almPLCFault.Resetable,431444.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C_WH.almPLCFault.REST,431444.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C_WH.almPLCFault.ACKN,431444.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C_WH.almPLCFault.UACK,431444.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C_WH.almPLCFault.MCmd_Enable,431444.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C_WH.almPLCFault.MCmd_Disable,431444.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C_WH.almPLCFault.OCmd_Shelve,431444.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C_WH.almPLCFault.OCmd_Unshelve,431444.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C_WH.almPLCFault.SCmd_Suppress,431444.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C_WH.almPLCFault.SCmd_UnSuppress,431445.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C_WH.almPLCFault.AEShelveTMRDN,431445.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C_WH.almPLCFault.Bad,431445.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C_WH.almPLCFault.Suppress,431446.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.UnSuppress,431446.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Shelve,431446.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.UnShelve,431446.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Enable,431446.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Disable,431446.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Ack,431446.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Reset,431446.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Suppressed,431446.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Shelved,431446.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Disabled,431446.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Acked,431446.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C_WH.almPLCFault.Alarm,431446.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Fault,431466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D_WH.Alarm.AlarmState,431466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D_WH.Alarm.GlobalReset,431466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D_WH.Alarm.FaultInAlarm,431466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D_WH.Alarm.ALRM,431466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D_WH.Alarm.ANUN,431466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D_WH.Alarm.AKED,431466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D_WH.Alarm.Resetable,431466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D_WH.Alarm.REST,431466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D_WH.Alarm.ACKN,431466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D_WH.Alarm.UACK,431466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D_WH.Alarm.MCmd_Enable,431466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D_WH.Alarm.MCmd_Disable,431466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D_WH.Alarm.OCmd_Shelve,431466.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D_WH.Alarm.OCmd_Unshelve,431466.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D_WH.Alarm.SCmd_Suppress,431466.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D_WH.Alarm.SCmd_UnSuppress,431467.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D_WH.Alarm.AEShelveTMRDN,431467.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D_WH.Alarm.Bad,431467.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D_WH.Alarm.Suppress,431468.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.UnSuppress,431468.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Shelve,431468.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.UnShelve,431468.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Enable,431468.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Disable,431468.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Ack,431468.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Reset,431468.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D_WH.Alarm.Suppressed,431468.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D_WH.Alarm.Shelved,431468.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D_WH.Alarm.Disabled,431468.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D_WH.Alarm.Acked,431468.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D_WH.Alarm.Alarm,431468.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Fault,431478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D_WH.almPLCFault.AlarmState,431478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D_WH.almPLCFault.GlobalReset,431478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D_WH.almPLCFault.FaultInAlarm,431478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D_WH.almPLCFault.ALRM,431478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D_WH.almPLCFault.ANUN,431478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D_WH.almPLCFault.AKED,431478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D_WH.almPLCFault.Resetable,431478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D_WH.almPLCFault.REST,431478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D_WH.almPLCFault.ACKN,431478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D_WH.almPLCFault.UACK,431478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D_WH.almPLCFault.MCmd_Enable,431478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D_WH.almPLCFault.MCmd_Disable,431478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D_WH.almPLCFault.OCmd_Shelve,431478.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D_WH.almPLCFault.OCmd_Unshelve,431478.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D_WH.almPLCFault.SCmd_Suppress,431478.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D_WH.almPLCFault.SCmd_UnSuppress,431479.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D_WH.almPLCFault.AEShelveTMRDN,431479.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D_WH.almPLCFault.Bad,431479.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D_WH.almPLCFault.Suppress,431480.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.UnSuppress,431480.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Shelve,431480.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.UnShelve,431480.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Enable,431480.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Disable,431480.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Ack,431480.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Reset,431480.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Suppressed,431480.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Shelved,431480.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Disabled,431480.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Acked,431480.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D_WH.almPLCFault.Alarm,431480.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Fault,431502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A_WH.Alarm.AlarmState,431502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A_WH.Alarm.GlobalReset,431502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A_WH.Alarm.FaultInAlarm,431502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A_WH.Alarm.ALRM,431502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A_WH.Alarm.ANUN,431502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A_WH.Alarm.AKED,431502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A_WH.Alarm.Resetable,431502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A_WH.Alarm.REST,431502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A_WH.Alarm.ACKN,431502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A_WH.Alarm.UACK,431502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A_WH.Alarm.MCmd_Enable,431502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A_WH.Alarm.MCmd_Disable,431502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A_WH.Alarm.OCmd_Shelve,431502.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A_WH.Alarm.OCmd_Unshelve,431502.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A_WH.Alarm.SCmd_Suppress,431502.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A_WH.Alarm.SCmd_UnSuppress,431503.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A_WH.Alarm.AEShelveTMRDN,431503.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A_WH.Alarm.Bad,431503.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A_WH.Alarm.Suppress,431504.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.UnSuppress,431504.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Shelve,431504.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.UnShelve,431504.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Enable,431504.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Disable,431504.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Ack,431504.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Reset,431504.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A_WH.Alarm.Suppressed,431504.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A_WH.Alarm.Shelved,431504.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A_WH.Alarm.Disabled,431504.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A_WH.Alarm.Acked,431504.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A_WH.Alarm.Alarm,431504.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Fault,431514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A_WH.almPLCFault.AlarmState,431514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A_WH.almPLCFault.GlobalReset,431514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A_WH.almPLCFault.FaultInAlarm,431514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A_WH.almPLCFault.ALRM,431514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A_WH.almPLCFault.ANUN,431514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A_WH.almPLCFault.AKED,431514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A_WH.almPLCFault.Resetable,431514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A_WH.almPLCFault.REST,431514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A_WH.almPLCFault.ACKN,431514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A_WH.almPLCFault.UACK,431514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A_WH.almPLCFault.MCmd_Enable,431514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A_WH.almPLCFault.MCmd_Disable,431514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A_WH.almPLCFault.OCmd_Shelve,431514.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A_WH.almPLCFault.OCmd_Unshelve,431514.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A_WH.almPLCFault.SCmd_Suppress,431514.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A_WH.almPLCFault.SCmd_UnSuppress,431515.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A_WH.almPLCFault.AEShelveTMRDN,431515.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A_WH.almPLCFault.Bad,431515.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A_WH.almPLCFault.Suppress,431516.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.UnSuppress,431516.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Shelve,431516.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.UnShelve,431516.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Enable,431516.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Disable,431516.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Ack,431516.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Reset,431516.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Suppressed,431516.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Shelved,431516.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Disabled,431516.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Acked,431516.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A_WH.almPLCFault.Alarm,431516.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Fault,431536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF.Alarm.AlarmState,431536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF.Alarm.GlobalReset,431536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF.Alarm.FaultInAlarm,431536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF.Alarm.ALRM,431536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF.Alarm.ANUN,431536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF.Alarm.AKED,431536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF.Alarm.Resetable,431536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF.Alarm.REST,431536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF.Alarm.ACKN,431536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF.Alarm.UACK,431536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF.Alarm.MCmd_Enable,431536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF.Alarm.MCmd_Disable,431536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF.Alarm.OCmd_Shelve,431536.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF.Alarm.OCmd_Unshelve,431536.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF.Alarm.SCmd_Suppress,431536.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF.Alarm.SCmd_UnSuppress,431537.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF.Alarm.AEShelveTMRDN,431537.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF.Alarm.Bad,431537.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF.Alarm.Suppress,431538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.UnSuppress,431538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Shelve,431538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.UnShelve,431538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Enable,431538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Disable,431538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Ack,431538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Reset,431538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF.Alarm.Suppressed,431538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF.Alarm.Shelved,431538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF.Alarm.Disabled,431538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF.Alarm.Acked,431538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF.Alarm.Alarm,431538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Fault,431548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF.almPLCFault.AlarmState,431548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF.almPLCFault.GlobalReset,431548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF.almPLCFault.FaultInAlarm,431548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF.almPLCFault.ALRM,431548.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF.almPLCFault.ANUN,431548.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF.almPLCFault.AKED,431548.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF.almPLCFault.Resetable,431548.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF.almPLCFault.REST,431548.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF.almPLCFault.ACKN,431548.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF.almPLCFault.UACK,431548.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF.almPLCFault.MCmd_Enable,431548.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.MCmd_Disable,431548.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.OCmd_Shelve,431548.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.OCmd_Unshelve,431548.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.SCmd_Suppress,431548.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.SCmd_UnSuppress,431549.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF.almPLCFault.AEShelveTMRDN,431549.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF.almPLCFault.Bad,431549.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF.almPLCFault.Suppress,431550.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.UnSuppress,431550.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Shelve,431550.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.UnShelve,431550.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Enable,431550.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Disable,431550.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Ack,431550.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Reset,431550.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Suppressed,431550.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Shelved,431550.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Disabled,431550.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Acked,431550.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF.almPLCFault.Alarm,431550.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Fault,431572.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF3.Alarm.AlarmState,431572.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF3.Alarm.GlobalReset,431572.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF3.Alarm.FaultInAlarm,431572.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF3.Alarm.ALRM,431572.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF3.Alarm.ANUN,431572.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF3.Alarm.AKED,431572.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF3.Alarm.Resetable,431572.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF3.Alarm.REST,431572.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF3.Alarm.ACKN,431572.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF3.Alarm.UACK,431572.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF3.Alarm.MCmd_Enable,431572.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF3.Alarm.MCmd_Disable,431572.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF3.Alarm.OCmd_Shelve,431572.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF3.Alarm.OCmd_Unshelve,431572.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF3.Alarm.SCmd_Suppress,431572.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF3.Alarm.SCmd_UnSuppress,431573.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF3.Alarm.AEShelveTMRDN,431573.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF3.Alarm.Bad,431573.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF3.Alarm.Suppress,431574.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.UnSuppress,431574.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Shelve,431574.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.UnShelve,431574.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Enable,431574.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Disable,431574.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Ack,431574.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Reset,431574.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Suppressed,431574.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Shelved,431574.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Disabled,431574.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Acked,431574.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF3.Alarm.Alarm,431574.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Fault,431584.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF3.almPLCFault.AlarmState,431584.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF3.almPLCFault.GlobalReset,431584.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF3.almPLCFault.FaultInAlarm,431584.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF3.almPLCFault.ALRM,431584.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF3.almPLCFault.ANUN,431584.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF3.almPLCFault.AKED,431584.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF3.almPLCFault.Resetable,431584.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF3.almPLCFault.REST,431584.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF3.almPLCFault.ACKN,431584.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF3.almPLCFault.UACK,431584.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF3.almPLCFault.MCmd_Enable,431584.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.MCmd_Disable,431584.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.OCmd_Shelve,431584.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.OCmd_Unshelve,431584.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.SCmd_Suppress,431584.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.SCmd_UnSuppress,431585.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF3.almPLCFault.AEShelveTMRDN,431585.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF3.almPLCFault.Bad,431585.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF3.almPLCFault.Suppress,431586.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.UnSuppress,431586.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Shelve,431586.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.UnShelve,431586.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Enable,431586.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Disable,431586.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Ack,431586.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Reset,431586.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Suppressed,431586.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Shelved,431586.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Disabled,431586.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Acked,431586.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF3.almPLCFault.Alarm,431586.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Fault,431606.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF4.Alarm.AlarmState,431606.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF4.Alarm.GlobalReset,431606.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF4.Alarm.FaultInAlarm,431606.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF4.Alarm.ALRM,431606.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF4.Alarm.ANUN,431606.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF4.Alarm.AKED,431606.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF4.Alarm.Resetable,431606.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF4.Alarm.REST,431606.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF4.Alarm.ACKN,431606.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF4.Alarm.UACK,431606.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF4.Alarm.MCmd_Enable,431606.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF4.Alarm.MCmd_Disable,431606.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF4.Alarm.OCmd_Shelve,431606.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF4.Alarm.OCmd_Unshelve,431606.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF4.Alarm.SCmd_Suppress,431606.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF4.Alarm.SCmd_UnSuppress,431607.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF4.Alarm.AEShelveTMRDN,431607.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF4.Alarm.Bad,431607.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF4.Alarm.Suppress,431608.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.UnSuppress,431608.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Shelve,431608.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.UnShelve,431608.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Enable,431608.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Disable,431608.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Ack,431608.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Reset,431608.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Suppressed,431608.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Shelved,431608.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Disabled,431608.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Acked,431608.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF4.Alarm.Alarm,431608.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Fault,431618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6B_ZF4.almPLCFault.AlarmState,431618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6B_ZF4.almPLCFault.GlobalReset,431618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6B_ZF4.almPLCFault.FaultInAlarm,431618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6B_ZF4.almPLCFault.ALRM,431618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6B_ZF4.almPLCFault.ANUN,431618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6B_ZF4.almPLCFault.AKED,431618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6B_ZF4.almPLCFault.Resetable,431618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6B_ZF4.almPLCFault.REST,431618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6B_ZF4.almPLCFault.ACKN,431618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6B_ZF4.almPLCFault.UACK,431618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6B_ZF4.almPLCFault.MCmd_Enable,431618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.MCmd_Disable,431618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.OCmd_Shelve,431618.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.OCmd_Unshelve,431618.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.SCmd_Suppress,431618.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.SCmd_UnSuppress,431619.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6B_ZF4.almPLCFault.AEShelveTMRDN,431619.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6B_ZF4.almPLCFault.Bad,431619.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6B_ZF4.almPLCFault.Suppress,431620.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.UnSuppress,431620.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Shelve,431620.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.UnShelve,431620.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Enable,431620.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Disable,431620.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Ack,431620.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Reset,431620.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Suppressed,431620.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Shelved,431620.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Disabled,431620.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Acked,431620.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6B_ZF4.almPLCFault.Alarm,431620.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Fault,431642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C_WH.Alarm.AlarmState,431642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C_WH.Alarm.GlobalReset,431642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C_WH.Alarm.FaultInAlarm,431642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C_WH.Alarm.ALRM,431642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C_WH.Alarm.ANUN,431642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C_WH.Alarm.AKED,431642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C_WH.Alarm.Resetable,431642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C_WH.Alarm.REST,431642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C_WH.Alarm.ACKN,431642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C_WH.Alarm.UACK,431642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C_WH.Alarm.MCmd_Enable,431642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C_WH.Alarm.MCmd_Disable,431642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C_WH.Alarm.OCmd_Shelve,431642.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C_WH.Alarm.OCmd_Unshelve,431642.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C_WH.Alarm.SCmd_Suppress,431642.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C_WH.Alarm.SCmd_UnSuppress,431643.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C_WH.Alarm.AEShelveTMRDN,431643.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C_WH.Alarm.Bad,431643.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C_WH.Alarm.Suppress,431644.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.UnSuppress,431644.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Shelve,431644.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.UnShelve,431644.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Enable,431644.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Disable,431644.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Ack,431644.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Reset,431644.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C_WH.Alarm.Suppressed,431644.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C_WH.Alarm.Shelved,431644.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C_WH.Alarm.Disabled,431644.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C_WH.Alarm.Acked,431644.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C_WH.Alarm.Alarm,431644.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Fault,431654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C_WH.almPLCFault.AlarmState,431654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C_WH.almPLCFault.GlobalReset,431654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C_WH.almPLCFault.FaultInAlarm,431654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C_WH.almPLCFault.ALRM,431654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C_WH.almPLCFault.ANUN,431654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C_WH.almPLCFault.AKED,431654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C_WH.almPLCFault.Resetable,431654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C_WH.almPLCFault.REST,431654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C_WH.almPLCFault.ACKN,431654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C_WH.almPLCFault.UACK,431654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C_WH.almPLCFault.MCmd_Enable,431654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C_WH.almPLCFault.MCmd_Disable,431654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C_WH.almPLCFault.OCmd_Shelve,431654.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C_WH.almPLCFault.OCmd_Unshelve,431654.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C_WH.almPLCFault.SCmd_Suppress,431654.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C_WH.almPLCFault.SCmd_UnSuppress,431655.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C_WH.almPLCFault.AEShelveTMRDN,431655.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C_WH.almPLCFault.Bad,431655.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C_WH.almPLCFault.Suppress,431656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.UnSuppress,431656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Shelve,431656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.UnShelve,431656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Enable,431656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Disable,431656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Ack,431656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Reset,431656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Suppressed,431656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Shelved,431656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Disabled,431656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Acked,431656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C_WH.almPLCFault.Alarm,431656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Fault,431676.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D_WH.Alarm.AlarmState,431676.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D_WH.Alarm.GlobalReset,431676.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D_WH.Alarm.FaultInAlarm,431676.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D_WH.Alarm.ALRM,431676.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D_WH.Alarm.ANUN,431676.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D_WH.Alarm.AKED,431676.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D_WH.Alarm.Resetable,431676.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D_WH.Alarm.REST,431676.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D_WH.Alarm.ACKN,431676.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D_WH.Alarm.UACK,431676.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D_WH.Alarm.MCmd_Enable,431676.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D_WH.Alarm.MCmd_Disable,431676.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D_WH.Alarm.OCmd_Shelve,431676.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D_WH.Alarm.OCmd_Unshelve,431676.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D_WH.Alarm.SCmd_Suppress,431676.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D_WH.Alarm.SCmd_UnSuppress,431677.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D_WH.Alarm.AEShelveTMRDN,431677.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D_WH.Alarm.Bad,431677.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D_WH.Alarm.Suppress,431678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.UnSuppress,431678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Shelve,431678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.UnShelve,431678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Enable,431678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Disable,431678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Ack,431678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Reset,431678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D_WH.Alarm.Suppressed,431678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D_WH.Alarm.Shelved,431678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D_WH.Alarm.Disabled,431678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D_WH.Alarm.Acked,431678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D_WH.Alarm.Alarm,431678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Fault,431688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D_WH.almPLCFault.AlarmState,431688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D_WH.almPLCFault.GlobalReset,431688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D_WH.almPLCFault.FaultInAlarm,431688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D_WH.almPLCFault.ALRM,431688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D_WH.almPLCFault.ANUN,431688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D_WH.almPLCFault.AKED,431688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D_WH.almPLCFault.Resetable,431688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D_WH.almPLCFault.REST,431688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D_WH.almPLCFault.ACKN,431688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D_WH.almPLCFault.UACK,431688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D_WH.almPLCFault.MCmd_Enable,431688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D_WH.almPLCFault.MCmd_Disable,431688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D_WH.almPLCFault.OCmd_Shelve,431688.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D_WH.almPLCFault.OCmd_Unshelve,431688.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D_WH.almPLCFault.SCmd_Suppress,431688.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D_WH.almPLCFault.SCmd_UnSuppress,431689.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D_WH.almPLCFault.AEShelveTMRDN,431689.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D_WH.almPLCFault.Bad,431689.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D_WH.almPLCFault.Suppress,431690.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.UnSuppress,431690.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Shelve,431690.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.UnShelve,431690.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Enable,431690.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Disable,431690.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Ack,431690.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Reset,431690.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Suppressed,431690.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Shelved,431690.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Disabled,431690.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Acked,431690.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D_WH.almPLCFault.Alarm,431690.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Fault,431712.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A_WH.Alarm.AlarmState,431712.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A_WH.Alarm.GlobalReset,431712.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A_WH.Alarm.FaultInAlarm,431712.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A_WH.Alarm.ALRM,431712.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A_WH.Alarm.ANUN,431712.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A_WH.Alarm.AKED,431712.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A_WH.Alarm.Resetable,431712.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A_WH.Alarm.REST,431712.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A_WH.Alarm.ACKN,431712.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A_WH.Alarm.UACK,431712.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A_WH.Alarm.MCmd_Enable,431712.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A_WH.Alarm.MCmd_Disable,431712.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A_WH.Alarm.OCmd_Shelve,431712.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A_WH.Alarm.OCmd_Unshelve,431712.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A_WH.Alarm.SCmd_Suppress,431712.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A_WH.Alarm.SCmd_UnSuppress,431713.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A_WH.Alarm.AEShelveTMRDN,431713.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A_WH.Alarm.Bad,431713.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A_WH.Alarm.Suppress,431714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.UnSuppress,431714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Shelve,431714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.UnShelve,431714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Enable,431714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Disable,431714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Ack,431714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Reset,431714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A_WH.Alarm.Suppressed,431714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A_WH.Alarm.Shelved,431714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A_WH.Alarm.Disabled,431714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A_WH.Alarm.Acked,431714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A_WH.Alarm.Alarm,431714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Fault,431724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A_WH.almPLCFault.AlarmState,431724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A_WH.almPLCFault.GlobalReset,431724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A_WH.almPLCFault.FaultInAlarm,431724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A_WH.almPLCFault.ALRM,431724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A_WH.almPLCFault.ANUN,431724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A_WH.almPLCFault.AKED,431724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A_WH.almPLCFault.Resetable,431724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A_WH.almPLCFault.REST,431724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A_WH.almPLCFault.ACKN,431724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A_WH.almPLCFault.UACK,431724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A_WH.almPLCFault.MCmd_Enable,431724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A_WH.almPLCFault.MCmd_Disable,431724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A_WH.almPLCFault.OCmd_Shelve,431724.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A_WH.almPLCFault.OCmd_Unshelve,431724.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A_WH.almPLCFault.SCmd_Suppress,431724.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A_WH.almPLCFault.SCmd_UnSuppress,431725.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A_WH.almPLCFault.AEShelveTMRDN,431725.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A_WH.almPLCFault.Bad,431725.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A_WH.almPLCFault.Suppress,431726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.UnSuppress,431726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Shelve,431726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.UnShelve,431726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Enable,431726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Disable,431726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Ack,431726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Reset,431726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Suppressed,431726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Shelved,431726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Disabled,431726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Acked,431726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A_WH.almPLCFault.Alarm,431726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Fault,431746.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF.Alarm.AlarmState,431746.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF.Alarm.GlobalReset,431746.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF.Alarm.FaultInAlarm,431746.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF.Alarm.ALRM,431746.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF.Alarm.ANUN,431746.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF.Alarm.AKED,431746.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF.Alarm.Resetable,431746.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF.Alarm.REST,431746.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF.Alarm.ACKN,431746.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF.Alarm.UACK,431746.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF.Alarm.MCmd_Enable,431746.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF.Alarm.MCmd_Disable,431746.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF.Alarm.OCmd_Shelve,431746.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF.Alarm.OCmd_Unshelve,431746.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF.Alarm.SCmd_Suppress,431746.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF.Alarm.SCmd_UnSuppress,431747.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF.Alarm.AEShelveTMRDN,431747.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF.Alarm.Bad,431747.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF.Alarm.Suppress,431748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.UnSuppress,431748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Shelve,431748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.UnShelve,431748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Enable,431748.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Disable,431748.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Ack,431748.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Reset,431748.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF.Alarm.Suppressed,431748.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF.Alarm.Shelved,431748.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF.Alarm.Disabled,431748.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF.Alarm.Acked,431748.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF.Alarm.Alarm,431748.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Fault,431758.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF.almPLCFault.AlarmState,431758.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF.almPLCFault.GlobalReset,431758.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF.almPLCFault.FaultInAlarm,431758.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF.almPLCFault.ALRM,431758.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF.almPLCFault.ANUN,431758.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF.almPLCFault.AKED,431758.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF.almPLCFault.Resetable,431758.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF.almPLCFault.REST,431758.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF.almPLCFault.ACKN,431758.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF.almPLCFault.UACK,431758.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF.almPLCFault.MCmd_Enable,431758.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.MCmd_Disable,431758.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.OCmd_Shelve,431758.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.OCmd_Unshelve,431758.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.SCmd_Suppress,431758.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.SCmd_UnSuppress,431759.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF.almPLCFault.AEShelveTMRDN,431759.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF.almPLCFault.Bad,431759.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF.almPLCFault.Suppress,431760.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.UnSuppress,431760.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Shelve,431760.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.UnShelve,431760.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Enable,431760.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Disable,431760.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Ack,431760.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Reset,431760.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Suppressed,431760.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Shelved,431760.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Disabled,431760.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Acked,431760.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF.almPLCFault.Alarm,431760.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Fault,431782.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF3.Alarm.AlarmState,431782.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF3.Alarm.GlobalReset,431782.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF3.Alarm.FaultInAlarm,431782.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF3.Alarm.ALRM,431782.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF3.Alarm.ANUN,431782.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF3.Alarm.AKED,431782.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF3.Alarm.Resetable,431782.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF3.Alarm.REST,431782.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF3.Alarm.ACKN,431782.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF3.Alarm.UACK,431782.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF3.Alarm.MCmd_Enable,431782.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF3.Alarm.MCmd_Disable,431782.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF3.Alarm.OCmd_Shelve,431782.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF3.Alarm.OCmd_Unshelve,431782.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF3.Alarm.SCmd_Suppress,431782.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF3.Alarm.SCmd_UnSuppress,431783.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF3.Alarm.AEShelveTMRDN,431783.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF3.Alarm.Bad,431783.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF3.Alarm.Suppress,431784.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.UnSuppress,431784.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Shelve,431784.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.UnShelve,431784.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Enable,431784.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Disable,431784.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Ack,431784.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Reset,431784.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Suppressed,431784.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Shelved,431784.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Disabled,431784.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Acked,431784.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF3.Alarm.Alarm,431784.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Fault,431794.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF3.almPLCFault.AlarmState,431794.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF3.almPLCFault.GlobalReset,431794.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF3.almPLCFault.FaultInAlarm,431794.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF3.almPLCFault.ALRM,431794.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF3.almPLCFault.ANUN,431794.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF3.almPLCFault.AKED,431794.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF3.almPLCFault.Resetable,431794.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF3.almPLCFault.REST,431794.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF3.almPLCFault.ACKN,431794.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF3.almPLCFault.UACK,431794.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF3.almPLCFault.MCmd_Enable,431794.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.MCmd_Disable,431794.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.OCmd_Shelve,431794.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.OCmd_Unshelve,431794.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.SCmd_Suppress,431794.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.SCmd_UnSuppress,431795.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF3.almPLCFault.AEShelveTMRDN,431795.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF3.almPLCFault.Bad,431795.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF3.almPLCFault.Suppress,431796.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.UnSuppress,431796.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Shelve,431796.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.UnShelve,431796.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Enable,431796.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Disable,431796.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Ack,431796.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Reset,431796.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Suppressed,431796.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Shelved,431796.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Disabled,431796.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Acked,431796.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF3.almPLCFault.Alarm,431796.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Fault,431816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF4.Alarm.AlarmState,431816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF4.Alarm.GlobalReset,431816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF4.Alarm.FaultInAlarm,431816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF4.Alarm.ALRM,431816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF4.Alarm.ANUN,431816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF4.Alarm.AKED,431816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF4.Alarm.Resetable,431816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF4.Alarm.REST,431816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF4.Alarm.ACKN,431816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF4.Alarm.UACK,431816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF4.Alarm.MCmd_Enable,431816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF4.Alarm.MCmd_Disable,431816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF4.Alarm.OCmd_Shelve,431816.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF4.Alarm.OCmd_Unshelve,431816.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF4.Alarm.SCmd_Suppress,431816.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF4.Alarm.SCmd_UnSuppress,431817.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF4.Alarm.AEShelveTMRDN,431817.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF4.Alarm.Bad,431817.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF4.Alarm.Suppress,431818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.UnSuppress,431818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Shelve,431818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.UnShelve,431818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Enable,431818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Disable,431818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Ack,431818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Reset,431818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Suppressed,431818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Shelved,431818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Disabled,431818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Acked,431818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF4.Alarm.Alarm,431818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Fault,431828.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7B_ZF4.almPLCFault.AlarmState,431828.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7B_ZF4.almPLCFault.GlobalReset,431828.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7B_ZF4.almPLCFault.FaultInAlarm,431828.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7B_ZF4.almPLCFault.ALRM,431828.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7B_ZF4.almPLCFault.ANUN,431828.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7B_ZF4.almPLCFault.AKED,431828.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7B_ZF4.almPLCFault.Resetable,431828.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7B_ZF4.almPLCFault.REST,431828.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7B_ZF4.almPLCFault.ACKN,431828.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7B_ZF4.almPLCFault.UACK,431828.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7B_ZF4.almPLCFault.MCmd_Enable,431828.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.MCmd_Disable,431828.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.OCmd_Shelve,431828.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.OCmd_Unshelve,431828.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.SCmd_Suppress,431828.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.SCmd_UnSuppress,431829.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7B_ZF4.almPLCFault.AEShelveTMRDN,431829.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7B_ZF4.almPLCFault.Bad,431829.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7B_ZF4.almPLCFault.Suppress,431830.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.UnSuppress,431830.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Shelve,431830.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.UnShelve,431830.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Enable,431830.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Disable,431830.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Ack,431830.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Reset,431830.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Suppressed,431830.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Shelved,431830.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Disabled,431830.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Acked,431830.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7B_ZF4.almPLCFault.Alarm,431830.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Fault,431852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C_WH.Alarm.AlarmState,431852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C_WH.Alarm.GlobalReset,431852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C_WH.Alarm.FaultInAlarm,431852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C_WH.Alarm.ALRM,431852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C_WH.Alarm.ANUN,431852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C_WH.Alarm.AKED,431852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C_WH.Alarm.Resetable,431852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C_WH.Alarm.REST,431852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C_WH.Alarm.ACKN,431852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C_WH.Alarm.UACK,431852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C_WH.Alarm.MCmd_Enable,431852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C_WH.Alarm.MCmd_Disable,431852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C_WH.Alarm.OCmd_Shelve,431852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C_WH.Alarm.OCmd_Unshelve,431852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C_WH.Alarm.SCmd_Suppress,431852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C_WH.Alarm.SCmd_UnSuppress,431853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C_WH.Alarm.AEShelveTMRDN,431853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C_WH.Alarm.Bad,431853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C_WH.Alarm.Suppress,431854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.UnSuppress,431854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Shelve,431854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.UnShelve,431854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Enable,431854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Disable,431854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Ack,431854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Reset,431854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C_WH.Alarm.Suppressed,431854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C_WH.Alarm.Shelved,431854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C_WH.Alarm.Disabled,431854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C_WH.Alarm.Acked,431854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C_WH.Alarm.Alarm,431854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Fault,431864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C_WH.almPLCFault.AlarmState,431864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C_WH.almPLCFault.GlobalReset,431864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C_WH.almPLCFault.FaultInAlarm,431864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C_WH.almPLCFault.ALRM,431864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C_WH.almPLCFault.ANUN,431864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C_WH.almPLCFault.AKED,431864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C_WH.almPLCFault.Resetable,431864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C_WH.almPLCFault.REST,431864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C_WH.almPLCFault.ACKN,431864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C_WH.almPLCFault.UACK,431864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C_WH.almPLCFault.MCmd_Enable,431864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C_WH.almPLCFault.MCmd_Disable,431864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C_WH.almPLCFault.OCmd_Shelve,431864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C_WH.almPLCFault.OCmd_Unshelve,431864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C_WH.almPLCFault.SCmd_Suppress,431864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C_WH.almPLCFault.SCmd_UnSuppress,431865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C_WH.almPLCFault.AEShelveTMRDN,431865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C_WH.almPLCFault.Bad,431865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C_WH.almPLCFault.Suppress,431866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.UnSuppress,431866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Shelve,431866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.UnShelve,431866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Enable,431866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Disable,431866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Ack,431866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Reset,431866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Suppressed,431866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Shelved,431866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Disabled,431866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Acked,431866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C_WH.almPLCFault.Alarm,431866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Fault,431886.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D_WH.Alarm.AlarmState,431886.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D_WH.Alarm.GlobalReset,431886.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D_WH.Alarm.FaultInAlarm,431886.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D_WH.Alarm.ALRM,431886.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D_WH.Alarm.ANUN,431886.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D_WH.Alarm.AKED,431886.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D_WH.Alarm.Resetable,431886.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D_WH.Alarm.REST,431886.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D_WH.Alarm.ACKN,431886.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D_WH.Alarm.UACK,431886.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D_WH.Alarm.MCmd_Enable,431886.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D_WH.Alarm.MCmd_Disable,431886.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D_WH.Alarm.OCmd_Shelve,431886.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D_WH.Alarm.OCmd_Unshelve,431886.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D_WH.Alarm.SCmd_Suppress,431886.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D_WH.Alarm.SCmd_UnSuppress,431887.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D_WH.Alarm.AEShelveTMRDN,431887.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D_WH.Alarm.Bad,431887.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D_WH.Alarm.Suppress,431888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.UnSuppress,431888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Shelve,431888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.UnShelve,431888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Enable,431888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Disable,431888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Ack,431888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Reset,431888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D_WH.Alarm.Suppressed,431888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D_WH.Alarm.Shelved,431888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D_WH.Alarm.Disabled,431888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D_WH.Alarm.Acked,431888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D_WH.Alarm.Alarm,431888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Fault,431898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D_WH.almPLCFault.AlarmState,431898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D_WH.almPLCFault.GlobalReset,431898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D_WH.almPLCFault.FaultInAlarm,431898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D_WH.almPLCFault.ALRM,431898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D_WH.almPLCFault.ANUN,431898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D_WH.almPLCFault.AKED,431898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D_WH.almPLCFault.Resetable,431898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D_WH.almPLCFault.REST,431898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D_WH.almPLCFault.ACKN,431898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D_WH.almPLCFault.UACK,431898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D_WH.almPLCFault.MCmd_Enable,431898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D_WH.almPLCFault.MCmd_Disable,431898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D_WH.almPLCFault.OCmd_Shelve,431898.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D_WH.almPLCFault.OCmd_Unshelve,431898.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D_WH.almPLCFault.SCmd_Suppress,431898.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D_WH.almPLCFault.SCmd_UnSuppress,431899.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D_WH.almPLCFault.AEShelveTMRDN,431899.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D_WH.almPLCFault.Bad,431899.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D_WH.almPLCFault.Suppress,431900.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.UnSuppress,431900.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Shelve,431900.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.UnShelve,431900.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Enable,431900.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Disable,431900.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Ack,431900.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Reset,431900.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Suppressed,431900.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Shelved,431900.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Disabled,431900.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Acked,431900.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D_WH.almPLCFault.Alarm,431900.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Fault,431922.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A_WH.Alarm.AlarmState,431922.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A_WH.Alarm.GlobalReset,431922.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A_WH.Alarm.FaultInAlarm,431922.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A_WH.Alarm.ALRM,431922.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A_WH.Alarm.ANUN,431922.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A_WH.Alarm.AKED,431922.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A_WH.Alarm.Resetable,431922.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A_WH.Alarm.REST,431922.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A_WH.Alarm.ACKN,431922.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A_WH.Alarm.UACK,431922.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A_WH.Alarm.MCmd_Enable,431922.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A_WH.Alarm.MCmd_Disable,431922.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A_WH.Alarm.OCmd_Shelve,431922.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A_WH.Alarm.OCmd_Unshelve,431922.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A_WH.Alarm.SCmd_Suppress,431922.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A_WH.Alarm.SCmd_UnSuppress,431923.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A_WH.Alarm.AEShelveTMRDN,431923.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A_WH.Alarm.Bad,431923.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A_WH.Alarm.Suppress,431924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.UnSuppress,431924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Shelve,431924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.UnShelve,431924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Enable,431924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Disable,431924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Ack,431924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Reset,431924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A_WH.Alarm.Suppressed,431924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A_WH.Alarm.Shelved,431924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A_WH.Alarm.Disabled,431924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A_WH.Alarm.Acked,431924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A_WH.Alarm.Alarm,431924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Fault,431934.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A_WH.almPLCFault.AlarmState,431934.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A_WH.almPLCFault.GlobalReset,431934.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A_WH.almPLCFault.FaultInAlarm,431934.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A_WH.almPLCFault.ALRM,431934.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A_WH.almPLCFault.ANUN,431934.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A_WH.almPLCFault.AKED,431934.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A_WH.almPLCFault.Resetable,431934.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A_WH.almPLCFault.REST,431934.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A_WH.almPLCFault.ACKN,431934.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A_WH.almPLCFault.UACK,431934.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A_WH.almPLCFault.MCmd_Enable,431934.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A_WH.almPLCFault.MCmd_Disable,431934.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A_WH.almPLCFault.OCmd_Shelve,431934.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A_WH.almPLCFault.OCmd_Unshelve,431934.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A_WH.almPLCFault.SCmd_Suppress,431934.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A_WH.almPLCFault.SCmd_UnSuppress,431935.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A_WH.almPLCFault.AEShelveTMRDN,431935.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A_WH.almPLCFault.Bad,431935.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A_WH.almPLCFault.Suppress,431936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.UnSuppress,431936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Shelve,431936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.UnShelve,431936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Enable,431936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Disable,431936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Ack,431936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Reset,431936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Suppressed,431936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Shelved,431936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Disabled,431936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Acked,431936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A_WH.almPLCFault.Alarm,431936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Fault,431956.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF.Alarm.AlarmState,431956.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF.Alarm.GlobalReset,431956.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF.Alarm.FaultInAlarm,431956.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF.Alarm.ALRM,431956.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF.Alarm.ANUN,431956.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF.Alarm.AKED,431956.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF.Alarm.Resetable,431956.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF.Alarm.REST,431956.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF.Alarm.ACKN,431956.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF.Alarm.UACK,431956.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF.Alarm.MCmd_Enable,431956.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF.Alarm.MCmd_Disable,431956.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF.Alarm.OCmd_Shelve,431956.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF.Alarm.OCmd_Unshelve,431956.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF.Alarm.SCmd_Suppress,431956.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF.Alarm.SCmd_UnSuppress,431957.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF.Alarm.AEShelveTMRDN,431957.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF.Alarm.Bad,431957.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF.Alarm.Suppress,431958.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.UnSuppress,431958.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Shelve,431958.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.UnShelve,431958.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Enable,431958.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Disable,431958.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Ack,431958.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Reset,431958.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF.Alarm.Suppressed,431958.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF.Alarm.Shelved,431958.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF.Alarm.Disabled,431958.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF.Alarm.Acked,431958.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF.Alarm.Alarm,431958.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Fault,431968.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF.almPLCFault.AlarmState,431968.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF.almPLCFault.GlobalReset,431968.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF.almPLCFault.FaultInAlarm,431968.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF.almPLCFault.ALRM,431968.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF.almPLCFault.ANUN,431968.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF.almPLCFault.AKED,431968.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF.almPLCFault.Resetable,431968.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF.almPLCFault.REST,431968.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF.almPLCFault.ACKN,431968.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF.almPLCFault.UACK,431968.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF.almPLCFault.MCmd_Enable,431968.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.MCmd_Disable,431968.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.OCmd_Shelve,431968.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.OCmd_Unshelve,431968.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.SCmd_Suppress,431968.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.SCmd_UnSuppress,431969.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF.almPLCFault.AEShelveTMRDN,431969.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF.almPLCFault.Bad,431969.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF.almPLCFault.Suppress,431970.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.UnSuppress,431970.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Shelve,431970.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.UnShelve,431970.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Enable,431970.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Disable,431970.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Ack,431970.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Reset,431970.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Suppressed,431970.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Shelved,431970.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Disabled,431970.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Acked,431970.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF.almPLCFault.Alarm,431970.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Fault,431992.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF3.Alarm.AlarmState,431992.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF3.Alarm.GlobalReset,431992.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF3.Alarm.FaultInAlarm,431992.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF3.Alarm.ALRM,431992.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF3.Alarm.ANUN,431992.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF3.Alarm.AKED,431992.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF3.Alarm.Resetable,431992.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF3.Alarm.REST,431992.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF3.Alarm.ACKN,431992.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF3.Alarm.UACK,431992.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF3.Alarm.MCmd_Enable,431992.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF3.Alarm.MCmd_Disable,431992.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF3.Alarm.OCmd_Shelve,431992.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF3.Alarm.OCmd_Unshelve,431992.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF3.Alarm.SCmd_Suppress,431992.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF3.Alarm.SCmd_UnSuppress,431993.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF3.Alarm.AEShelveTMRDN,431993.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF3.Alarm.Bad,431993.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF3.Alarm.Suppress,431994.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.UnSuppress,431994.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Shelve,431994.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.UnShelve,431994.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Enable,431994.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Disable,431994.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Ack,431994.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Reset,431994.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Suppressed,431994.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Shelved,431994.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Disabled,431994.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Acked,431994.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF3.Alarm.Alarm,431994.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Fault,432004.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF3.almPLCFault.AlarmState,432004.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF3.almPLCFault.GlobalReset,432004.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF3.almPLCFault.FaultInAlarm,432004.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF3.almPLCFault.ALRM,432004.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF3.almPLCFault.ANUN,432004.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF3.almPLCFault.AKED,432004.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF3.almPLCFault.Resetable,432004.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF3.almPLCFault.REST,432004.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF3.almPLCFault.ACKN,432004.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF3.almPLCFault.UACK,432004.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF3.almPLCFault.MCmd_Enable,432004.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.MCmd_Disable,432004.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.OCmd_Shelve,432004.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.OCmd_Unshelve,432004.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.SCmd_Suppress,432004.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.SCmd_UnSuppress,432005.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF3.almPLCFault.AEShelveTMRDN,432005.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF3.almPLCFault.Bad,432005.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF3.almPLCFault.Suppress,432006.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.UnSuppress,432006.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Shelve,432006.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.UnShelve,432006.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Enable,432006.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Disable,432006.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Ack,432006.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Reset,432006.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Suppressed,432006.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Shelved,432006.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Disabled,432006.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Acked,432006.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF3.almPLCFault.Alarm,432006.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Fault,432026.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF4.Alarm.AlarmState,432026.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF4.Alarm.GlobalReset,432026.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF4.Alarm.FaultInAlarm,432026.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF4.Alarm.ALRM,432026.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF4.Alarm.ANUN,432026.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF4.Alarm.AKED,432026.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF4.Alarm.Resetable,432026.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF4.Alarm.REST,432026.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF4.Alarm.ACKN,432026.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF4.Alarm.UACK,432026.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF4.Alarm.MCmd_Enable,432026.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF4.Alarm.MCmd_Disable,432026.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF4.Alarm.OCmd_Shelve,432026.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF4.Alarm.OCmd_Unshelve,432026.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF4.Alarm.SCmd_Suppress,432026.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF4.Alarm.SCmd_UnSuppress,432027.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF4.Alarm.AEShelveTMRDN,432027.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF4.Alarm.Bad,432027.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF4.Alarm.Suppress,432028.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.UnSuppress,432028.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Shelve,432028.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.UnShelve,432028.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Enable,432028.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Disable,432028.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Ack,432028.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Reset,432028.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Suppressed,432028.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Shelved,432028.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Disabled,432028.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Acked,432028.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF4.Alarm.Alarm,432028.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Fault,432038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8B_ZF4.almPLCFault.AlarmState,432038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8B_ZF4.almPLCFault.GlobalReset,432038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8B_ZF4.almPLCFault.FaultInAlarm,432038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8B_ZF4.almPLCFault.ALRM,432038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8B_ZF4.almPLCFault.ANUN,432038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8B_ZF4.almPLCFault.AKED,432038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8B_ZF4.almPLCFault.Resetable,432038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8B_ZF4.almPLCFault.REST,432038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8B_ZF4.almPLCFault.ACKN,432038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8B_ZF4.almPLCFault.UACK,432038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8B_ZF4.almPLCFault.MCmd_Enable,432038.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.MCmd_Disable,432038.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.OCmd_Shelve,432038.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.OCmd_Unshelve,432038.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.SCmd_Suppress,432038.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.SCmd_UnSuppress,432039.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8B_ZF4.almPLCFault.AEShelveTMRDN,432039.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8B_ZF4.almPLCFault.Bad,432039.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8B_ZF4.almPLCFault.Suppress,432040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.UnSuppress,432040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Shelve,432040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.UnShelve,432040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Enable,432040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Disable,432040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Ack,432040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Reset,432040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Suppressed,432040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Shelved,432040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Disabled,432040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Acked,432040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8B_ZF4.almPLCFault.Alarm,432040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Fault,432062.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C_WH.Alarm.AlarmState,432062.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C_WH.Alarm.GlobalReset,432062.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C_WH.Alarm.FaultInAlarm,432062.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C_WH.Alarm.ALRM,432062.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C_WH.Alarm.ANUN,432062.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C_WH.Alarm.AKED,432062.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C_WH.Alarm.Resetable,432062.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C_WH.Alarm.REST,432062.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C_WH.Alarm.ACKN,432062.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C_WH.Alarm.UACK,432062.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C_WH.Alarm.MCmd_Enable,432062.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C_WH.Alarm.MCmd_Disable,432062.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C_WH.Alarm.OCmd_Shelve,432062.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C_WH.Alarm.OCmd_Unshelve,432062.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C_WH.Alarm.SCmd_Suppress,432062.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C_WH.Alarm.SCmd_UnSuppress,432063.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C_WH.Alarm.AEShelveTMRDN,432063.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C_WH.Alarm.Bad,432063.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C_WH.Alarm.Suppress,432064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.UnSuppress,432064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Shelve,432064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.UnShelve,432064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Enable,432064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Disable,432064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Ack,432064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Reset,432064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C_WH.Alarm.Suppressed,432064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C_WH.Alarm.Shelved,432064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C_WH.Alarm.Disabled,432064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C_WH.Alarm.Acked,432064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C_WH.Alarm.Alarm,432064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Fault,432074.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C_WH.almPLCFault.AlarmState,432074.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C_WH.almPLCFault.GlobalReset,432074.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C_WH.almPLCFault.FaultInAlarm,432074.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C_WH.almPLCFault.ALRM,432074.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C_WH.almPLCFault.ANUN,432074.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C_WH.almPLCFault.AKED,432074.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C_WH.almPLCFault.Resetable,432074.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C_WH.almPLCFault.REST,432074.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C_WH.almPLCFault.ACKN,432074.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C_WH.almPLCFault.UACK,432074.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C_WH.almPLCFault.MCmd_Enable,432074.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C_WH.almPLCFault.MCmd_Disable,432074.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C_WH.almPLCFault.OCmd_Shelve,432074.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C_WH.almPLCFault.OCmd_Unshelve,432074.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C_WH.almPLCFault.SCmd_Suppress,432074.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C_WH.almPLCFault.SCmd_UnSuppress,432075.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C_WH.almPLCFault.AEShelveTMRDN,432075.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C_WH.almPLCFault.Bad,432075.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C_WH.almPLCFault.Suppress,432076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.UnSuppress,432076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Shelve,432076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.UnShelve,432076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Enable,432076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Disable,432076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Ack,432076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Reset,432076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Suppressed,432076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Shelved,432076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Disabled,432076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Acked,432076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C_WH.almPLCFault.Alarm,432076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Fault,432096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D_WH.Alarm.AlarmState,432096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D_WH.Alarm.GlobalReset,432096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D_WH.Alarm.FaultInAlarm,432096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D_WH.Alarm.ALRM,432096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D_WH.Alarm.ANUN,432096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D_WH.Alarm.AKED,432096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D_WH.Alarm.Resetable,432096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D_WH.Alarm.REST,432096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D_WH.Alarm.ACKN,432096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D_WH.Alarm.UACK,432096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D_WH.Alarm.MCmd_Enable,432096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D_WH.Alarm.MCmd_Disable,432096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D_WH.Alarm.OCmd_Shelve,432096.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D_WH.Alarm.OCmd_Unshelve,432096.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D_WH.Alarm.SCmd_Suppress,432096.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D_WH.Alarm.SCmd_UnSuppress,432097.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D_WH.Alarm.AEShelveTMRDN,432097.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D_WH.Alarm.Bad,432097.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D_WH.Alarm.Suppress,432098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.UnSuppress,432098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Shelve,432098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.UnShelve,432098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Enable,432098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Disable,432098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Ack,432098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Reset,432098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D_WH.Alarm.Suppressed,432098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D_WH.Alarm.Shelved,432098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D_WH.Alarm.Disabled,432098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D_WH.Alarm.Acked,432098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D_WH.Alarm.Alarm,432098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Fault,432108.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D_WH.almPLCFault.AlarmState,432108.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D_WH.almPLCFault.GlobalReset,432108.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D_WH.almPLCFault.FaultInAlarm,432108.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D_WH.almPLCFault.ALRM,432108.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D_WH.almPLCFault.ANUN,432108.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D_WH.almPLCFault.AKED,432108.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D_WH.almPLCFault.Resetable,432108.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D_WH.almPLCFault.REST,432108.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D_WH.almPLCFault.ACKN,432108.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D_WH.almPLCFault.UACK,432108.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D_WH.almPLCFault.MCmd_Enable,432108.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D_WH.almPLCFault.MCmd_Disable,432108.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D_WH.almPLCFault.OCmd_Shelve,432108.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D_WH.almPLCFault.OCmd_Unshelve,432108.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D_WH.almPLCFault.SCmd_Suppress,432108.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D_WH.almPLCFault.SCmd_UnSuppress,432109.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D_WH.almPLCFault.AEShelveTMRDN,432109.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D_WH.almPLCFault.Bad,432109.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D_WH.almPLCFault.Suppress,432110.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.UnSuppress,432110.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Shelve,432110.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.UnShelve,432110.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Enable,432110.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Disable,432110.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Ack,432110.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Reset,432110.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Suppressed,432110.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Shelved,432110.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Disabled,432110.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Acked,432110.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D_WH.almPLCFault.Alarm,432110.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Fault,432132.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A_WH.Alarm.AlarmState,432132.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A_WH.Alarm.GlobalReset,432132.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A_WH.Alarm.FaultInAlarm,432132.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A_WH.Alarm.ALRM,432132.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A_WH.Alarm.ANUN,432132.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A_WH.Alarm.AKED,432132.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A_WH.Alarm.Resetable,432132.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A_WH.Alarm.REST,432132.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A_WH.Alarm.ACKN,432132.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A_WH.Alarm.UACK,432132.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A_WH.Alarm.MCmd_Enable,432132.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A_WH.Alarm.MCmd_Disable,432132.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A_WH.Alarm.OCmd_Shelve,432132.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A_WH.Alarm.OCmd_Unshelve,432132.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A_WH.Alarm.SCmd_Suppress,432132.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A_WH.Alarm.SCmd_UnSuppress,432133.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A_WH.Alarm.AEShelveTMRDN,432133.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A_WH.Alarm.Bad,432133.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A_WH.Alarm.Suppress,432134.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.UnSuppress,432134.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Shelve,432134.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.UnShelve,432134.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Enable,432134.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Disable,432134.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Ack,432134.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Reset,432134.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A_WH.Alarm.Suppressed,432134.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A_WH.Alarm.Shelved,432134.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A_WH.Alarm.Disabled,432134.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A_WH.Alarm.Acked,432134.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A_WH.Alarm.Alarm,432134.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Fault,432144.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A_WH.almPLCFault.AlarmState,432144.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A_WH.almPLCFault.GlobalReset,432144.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A_WH.almPLCFault.FaultInAlarm,432144.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A_WH.almPLCFault.ALRM,432144.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A_WH.almPLCFault.ANUN,432144.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A_WH.almPLCFault.AKED,432144.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A_WH.almPLCFault.Resetable,432144.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A_WH.almPLCFault.REST,432144.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A_WH.almPLCFault.ACKN,432144.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A_WH.almPLCFault.UACK,432144.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A_WH.almPLCFault.MCmd_Enable,432144.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A_WH.almPLCFault.MCmd_Disable,432144.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A_WH.almPLCFault.OCmd_Shelve,432144.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A_WH.almPLCFault.OCmd_Unshelve,432144.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A_WH.almPLCFault.SCmd_Suppress,432144.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A_WH.almPLCFault.SCmd_UnSuppress,432145.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A_WH.almPLCFault.AEShelveTMRDN,432145.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A_WH.almPLCFault.Bad,432145.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A_WH.almPLCFault.Suppress,432146.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.UnSuppress,432146.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Shelve,432146.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.UnShelve,432146.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Enable,432146.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Disable,432146.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Ack,432146.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Reset,432146.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Suppressed,432146.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Shelved,432146.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Disabled,432146.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Acked,432146.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A_WH.almPLCFault.Alarm,432146.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Fault,432166.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZF.Alarm.AlarmState,432166.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZF.Alarm.GlobalReset,432166.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZF.Alarm.FaultInAlarm,432166.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF.Alarm.ALRM,432166.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZF.Alarm.ANUN,432166.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZF.Alarm.AKED,432166.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZF.Alarm.Resetable,432166.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZF.Alarm.REST,432166.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZF.Alarm.ACKN,432166.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZF.Alarm.UACK,432166.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZF.Alarm.MCmd_Enable,432166.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF.Alarm.MCmd_Disable,432166.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF.Alarm.OCmd_Shelve,432166.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZF.Alarm.OCmd_Unshelve,432166.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZF.Alarm.SCmd_Suppress,432166.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZF.Alarm.SCmd_UnSuppress,432167.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZF.Alarm.AEShelveTMRDN,432167.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZF.Alarm.Bad,432167.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZF.Alarm.Suppress,432168.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.UnSuppress,432168.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Shelve,432168.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.UnShelve,432168.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Enable,432168.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Disable,432168.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Ack,432168.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Reset,432168.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZF.Alarm.Suppressed,432168.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZF.Alarm.Shelved,432168.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZF.Alarm.Disabled,432168.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZF.Alarm.Acked,432168.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZF.Alarm.Alarm,432168.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Fault,432178.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZF.almPLCFault.AlarmState,432178.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZF.almPLCFault.GlobalReset,432178.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZF.almPLCFault.FaultInAlarm,432178.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF.almPLCFault.ALRM,432178.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZF.almPLCFault.ANUN,432178.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZF.almPLCFault.AKED,432178.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZF.almPLCFault.Resetable,432178.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZF.almPLCFault.REST,432178.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZF.almPLCFault.ACKN,432178.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZF.almPLCFault.UACK,432178.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZF.almPLCFault.MCmd_Enable,432178.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.MCmd_Disable,432178.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.OCmd_Shelve,432178.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.OCmd_Unshelve,432178.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.SCmd_Suppress,432178.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.SCmd_UnSuppress,432179.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZF.almPLCFault.AEShelveTMRDN,432179.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZF.almPLCFault.Bad,432179.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZF.almPLCFault.Suppress,432180.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.UnSuppress,432180.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Shelve,432180.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.UnShelve,432180.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Enable,432180.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Disable,432180.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Ack,432180.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Reset,432180.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Suppressed,432180.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Shelved,432180.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Disabled,432180.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Acked,432180.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZF.almPLCFault.Alarm,432180.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Fault,432202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZF2.Alarm.AlarmState,432202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZF2.Alarm.GlobalReset,432202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZF2.Alarm.FaultInAlarm,432202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF2.Alarm.ALRM,432202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZF2.Alarm.ANUN,432202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZF2.Alarm.AKED,432202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZF2.Alarm.Resetable,432202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZF2.Alarm.REST,432202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZF2.Alarm.ACKN,432202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZF2.Alarm.UACK,432202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZF2.Alarm.MCmd_Enable,432202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF2.Alarm.MCmd_Disable,432202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF2.Alarm.OCmd_Shelve,432202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZF2.Alarm.OCmd_Unshelve,432202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZF2.Alarm.SCmd_Suppress,432202.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZF2.Alarm.SCmd_UnSuppress,432203.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZF2.Alarm.AEShelveTMRDN,432203.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZF2.Alarm.Bad,432203.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZF2.Alarm.Suppress,432204.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.UnSuppress,432204.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Shelve,432204.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.UnShelve,432204.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Enable,432204.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Disable,432204.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Ack,432204.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Reset,432204.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Suppressed,432204.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Shelved,432204.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Disabled,432204.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Acked,432204.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZF2.Alarm.Alarm,432204.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Fault,432214.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9B_ZF2.almPLCFault.AlarmState,432214.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9B_ZF2.almPLCFault.GlobalReset,432214.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9B_ZF2.almPLCFault.FaultInAlarm,432214.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9B_ZF2.almPLCFault.ALRM,432214.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9B_ZF2.almPLCFault.ANUN,432214.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9B_ZF2.almPLCFault.AKED,432214.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9B_ZF2.almPLCFault.Resetable,432214.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9B_ZF2.almPLCFault.REST,432214.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9B_ZF2.almPLCFault.ACKN,432214.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9B_ZF2.almPLCFault.UACK,432214.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9B_ZF2.almPLCFault.MCmd_Enable,432214.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.MCmd_Disable,432214.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.OCmd_Shelve,432214.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.OCmd_Unshelve,432214.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.SCmd_Suppress,432214.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.SCmd_UnSuppress,432215.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9B_ZF2.almPLCFault.AEShelveTMRDN,432215.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9B_ZF2.almPLCFault.Bad,432215.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9B_ZF2.almPLCFault.Suppress,432216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.UnSuppress,432216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Shelve,432216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.UnShelve,432216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Enable,432216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Disable,432216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Ack,432216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Reset,432216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Suppressed,432216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Shelved,432216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Disabled,432216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Acked,432216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9B_ZF2.almPLCFault.Alarm,432216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Fault,432236.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C_WH.Alarm.AlarmState,432236.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C_WH.Alarm.GlobalReset,432236.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C_WH.Alarm.FaultInAlarm,432236.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C_WH.Alarm.ALRM,432236.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C_WH.Alarm.ANUN,432236.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C_WH.Alarm.AKED,432236.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C_WH.Alarm.Resetable,432236.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C_WH.Alarm.REST,432236.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C_WH.Alarm.ACKN,432236.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C_WH.Alarm.UACK,432236.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C_WH.Alarm.MCmd_Enable,432236.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C_WH.Alarm.MCmd_Disable,432236.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C_WH.Alarm.OCmd_Shelve,432236.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C_WH.Alarm.OCmd_Unshelve,432236.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C_WH.Alarm.SCmd_Suppress,432236.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C_WH.Alarm.SCmd_UnSuppress,432237.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C_WH.Alarm.AEShelveTMRDN,432237.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C_WH.Alarm.Bad,432237.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C_WH.Alarm.Suppress,432238.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.UnSuppress,432238.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Shelve,432238.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.UnShelve,432238.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Enable,432238.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Disable,432238.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Ack,432238.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Reset,432238.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C_WH.Alarm.Suppressed,432238.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C_WH.Alarm.Shelved,432238.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C_WH.Alarm.Disabled,432238.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C_WH.Alarm.Acked,432238.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C_WH.Alarm.Alarm,432238.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Fault,432248.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C_WH.almPLCFault.AlarmState,432248.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C_WH.almPLCFault.GlobalReset,432248.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C_WH.almPLCFault.FaultInAlarm,432248.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C_WH.almPLCFault.ALRM,432248.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C_WH.almPLCFault.ANUN,432248.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C_WH.almPLCFault.AKED,432248.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C_WH.almPLCFault.Resetable,432248.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C_WH.almPLCFault.REST,432248.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C_WH.almPLCFault.ACKN,432248.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C_WH.almPLCFault.UACK,432248.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C_WH.almPLCFault.MCmd_Enable,432248.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C_WH.almPLCFault.MCmd_Disable,432248.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C_WH.almPLCFault.OCmd_Shelve,432248.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C_WH.almPLCFault.OCmd_Unshelve,432248.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C_WH.almPLCFault.SCmd_Suppress,432248.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C_WH.almPLCFault.SCmd_UnSuppress,432249.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C_WH.almPLCFault.AEShelveTMRDN,432249.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C_WH.almPLCFault.Bad,432249.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C_WH.almPLCFault.Suppress,432250.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.UnSuppress,432250.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Shelve,432250.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.UnShelve,432250.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Enable,432250.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Disable,432250.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Ack,432250.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Reset,432250.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Suppressed,432250.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Shelved,432250.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Disabled,432250.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Acked,432250.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C_WH.almPLCFault.Alarm,432250.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Fault,432272.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A_WH.Alarm.AlarmState,432272.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A_WH.Alarm.GlobalReset,432272.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A_WH.Alarm.FaultInAlarm,432272.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A_WH.Alarm.ALRM,432272.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A_WH.Alarm.ANUN,432272.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A_WH.Alarm.AKED,432272.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A_WH.Alarm.Resetable,432272.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A_WH.Alarm.REST,432272.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A_WH.Alarm.ACKN,432272.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A_WH.Alarm.UACK,432272.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A_WH.Alarm.MCmd_Enable,432272.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A_WH.Alarm.MCmd_Disable,432272.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A_WH.Alarm.OCmd_Shelve,432272.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A_WH.Alarm.OCmd_Unshelve,432272.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A_WH.Alarm.SCmd_Suppress,432272.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A_WH.Alarm.SCmd_UnSuppress,432273.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A_WH.Alarm.AEShelveTMRDN,432273.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A_WH.Alarm.Bad,432273.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A_WH.Alarm.Suppress,432274.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.UnSuppress,432274.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Shelve,432274.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.UnShelve,432274.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Enable,432274.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Disable,432274.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Ack,432274.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Reset,432274.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A_WH.Alarm.Suppressed,432274.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A_WH.Alarm.Shelved,432274.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A_WH.Alarm.Disabled,432274.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A_WH.Alarm.Acked,432274.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A_WH.Alarm.Alarm,432274.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Fault,432284.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A_WH.almPLCFault.AlarmState,432284.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A_WH.almPLCFault.GlobalReset,432284.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A_WH.almPLCFault.FaultInAlarm,432284.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A_WH.almPLCFault.ALRM,432284.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A_WH.almPLCFault.ANUN,432284.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A_WH.almPLCFault.AKED,432284.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A_WH.almPLCFault.Resetable,432284.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A_WH.almPLCFault.REST,432284.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A_WH.almPLCFault.ACKN,432284.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A_WH.almPLCFault.UACK,432284.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A_WH.almPLCFault.MCmd_Enable,432284.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A_WH.almPLCFault.MCmd_Disable,432284.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A_WH.almPLCFault.OCmd_Shelve,432284.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A_WH.almPLCFault.OCmd_Unshelve,432284.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A_WH.almPLCFault.SCmd_Suppress,432284.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A_WH.almPLCFault.SCmd_UnSuppress,432285.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A_WH.almPLCFault.AEShelveTMRDN,432285.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A_WH.almPLCFault.Bad,432285.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A_WH.almPLCFault.Suppress,432286.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.UnSuppress,432286.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Shelve,432286.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.UnShelve,432286.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Enable,432286.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Disable,432286.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Ack,432286.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Reset,432286.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Suppressed,432286.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Shelved,432286.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Disabled,432286.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Acked,432286.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A_WH.almPLCFault.Alarm,432286.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Fault,432306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B_WH.Alarm.AlarmState,432306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B_WH.Alarm.GlobalReset,432306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B_WH.Alarm.FaultInAlarm,432306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B_WH.Alarm.ALRM,432306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B_WH.Alarm.ANUN,432306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B_WH.Alarm.AKED,432306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B_WH.Alarm.Resetable,432306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B_WH.Alarm.REST,432306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B_WH.Alarm.ACKN,432306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B_WH.Alarm.UACK,432306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B_WH.Alarm.MCmd_Enable,432306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B_WH.Alarm.MCmd_Disable,432306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B_WH.Alarm.OCmd_Shelve,432306.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B_WH.Alarm.OCmd_Unshelve,432306.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B_WH.Alarm.SCmd_Suppress,432306.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B_WH.Alarm.SCmd_UnSuppress,432307.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B_WH.Alarm.AEShelveTMRDN,432307.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B_WH.Alarm.Bad,432307.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B_WH.Alarm.Suppress,432308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.UnSuppress,432308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Shelve,432308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.UnShelve,432308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Enable,432308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Disable,432308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Ack,432308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Reset,432308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B_WH.Alarm.Suppressed,432308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B_WH.Alarm.Shelved,432308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B_WH.Alarm.Disabled,432308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B_WH.Alarm.Acked,432308.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B_WH.Alarm.Alarm,432308.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Fault,432318.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B_WH.almPLCFault.AlarmState,432318.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B_WH.almPLCFault.GlobalReset,432318.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B_WH.almPLCFault.FaultInAlarm,432318.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B_WH.almPLCFault.ALRM,432318.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B_WH.almPLCFault.ANUN,432318.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B_WH.almPLCFault.AKED,432318.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B_WH.almPLCFault.Resetable,432318.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B_WH.almPLCFault.REST,432318.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B_WH.almPLCFault.ACKN,432318.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B_WH.almPLCFault.UACK,432318.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B_WH.almPLCFault.MCmd_Enable,432318.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B_WH.almPLCFault.MCmd_Disable,432318.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B_WH.almPLCFault.OCmd_Shelve,432318.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B_WH.almPLCFault.OCmd_Unshelve,432318.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B_WH.almPLCFault.SCmd_Suppress,432318.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B_WH.almPLCFault.SCmd_UnSuppress,432319.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B_WH.almPLCFault.AEShelveTMRDN,432319.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B_WH.almPLCFault.Bad,432319.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B_WH.almPLCFault.Suppress,432320.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.UnSuppress,432320.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Shelve,432320.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.UnShelve,432320.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Enable,432320.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Disable,432320.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Ack,432320.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Reset,432320.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Suppressed,432320.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Shelved,432320.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Disabled,432320.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Acked,432320.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B_WH.almPLCFault.Alarm,432320.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Fault,432342.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C_WH.Alarm.AlarmState,432342.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C_WH.Alarm.GlobalReset,432342.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C_WH.Alarm.FaultInAlarm,432342.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C_WH.Alarm.ALRM,432342.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C_WH.Alarm.ANUN,432342.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C_WH.Alarm.AKED,432342.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C_WH.Alarm.Resetable,432342.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C_WH.Alarm.REST,432342.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C_WH.Alarm.ACKN,432342.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C_WH.Alarm.UACK,432342.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C_WH.Alarm.MCmd_Enable,432342.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C_WH.Alarm.MCmd_Disable,432342.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C_WH.Alarm.OCmd_Shelve,432342.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C_WH.Alarm.OCmd_Unshelve,432342.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C_WH.Alarm.SCmd_Suppress,432342.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C_WH.Alarm.SCmd_UnSuppress,432343.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C_WH.Alarm.AEShelveTMRDN,432343.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C_WH.Alarm.Bad,432343.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C_WH.Alarm.Suppress,432344.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.UnSuppress,432344.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Shelve,432344.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.UnShelve,432344.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Enable,432344.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Disable,432344.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Ack,432344.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Reset,432344.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C_WH.Alarm.Suppressed,432344.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C_WH.Alarm.Shelved,432344.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C_WH.Alarm.Disabled,432344.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C_WH.Alarm.Acked,432344.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C_WH.Alarm.Alarm,432344.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Fault,432354.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C_WH.almPLCFault.AlarmState,432354.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C_WH.almPLCFault.GlobalReset,432354.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C_WH.almPLCFault.FaultInAlarm,432354.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C_WH.almPLCFault.ALRM,432354.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C_WH.almPLCFault.ANUN,432354.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C_WH.almPLCFault.AKED,432354.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C_WH.almPLCFault.Resetable,432354.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C_WH.almPLCFault.REST,432354.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C_WH.almPLCFault.ACKN,432354.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C_WH.almPLCFault.UACK,432354.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C_WH.almPLCFault.MCmd_Enable,432354.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C_WH.almPLCFault.MCmd_Disable,432354.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C_WH.almPLCFault.OCmd_Shelve,432354.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C_WH.almPLCFault.OCmd_Unshelve,432354.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C_WH.almPLCFault.SCmd_Suppress,432354.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C_WH.almPLCFault.SCmd_UnSuppress,432355.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C_WH.almPLCFault.AEShelveTMRDN,432355.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C_WH.almPLCFault.Bad,432355.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C_WH.almPLCFault.Suppress,432356.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.UnSuppress,432356.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Shelve,432356.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.UnShelve,432356.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Enable,432356.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Disable,432356.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Ack,432356.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Reset,432356.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Suppressed,432356.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Shelved,432356.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Disabled,432356.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Acked,432356.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C_WH.almPLCFault.Alarm,432356.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Fault,432376.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D_WH.Alarm.AlarmState,432376.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D_WH.Alarm.GlobalReset,432376.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D_WH.Alarm.FaultInAlarm,432376.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D_WH.Alarm.ALRM,432376.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D_WH.Alarm.ANUN,432376.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D_WH.Alarm.AKED,432376.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D_WH.Alarm.Resetable,432376.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D_WH.Alarm.REST,432376.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D_WH.Alarm.ACKN,432376.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D_WH.Alarm.UACK,432376.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D_WH.Alarm.MCmd_Enable,432376.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D_WH.Alarm.MCmd_Disable,432376.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D_WH.Alarm.OCmd_Shelve,432376.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D_WH.Alarm.OCmd_Unshelve,432376.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D_WH.Alarm.SCmd_Suppress,432376.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D_WH.Alarm.SCmd_UnSuppress,432377.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D_WH.Alarm.AEShelveTMRDN,432377.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D_WH.Alarm.Bad,432377.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D_WH.Alarm.Suppress,432378.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.UnSuppress,432378.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Shelve,432378.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.UnShelve,432378.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Enable,432378.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Disable,432378.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Ack,432378.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Reset,432378.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D_WH.Alarm.Suppressed,432378.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D_WH.Alarm.Shelved,432378.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D_WH.Alarm.Disabled,432378.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D_WH.Alarm.Acked,432378.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D_WH.Alarm.Alarm,432378.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Fault,432388.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D_WH.almPLCFault.AlarmState,432388.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D_WH.almPLCFault.GlobalReset,432388.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D_WH.almPLCFault.FaultInAlarm,432388.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D_WH.almPLCFault.ALRM,432388.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D_WH.almPLCFault.ANUN,432388.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D_WH.almPLCFault.AKED,432388.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D_WH.almPLCFault.Resetable,432388.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D_WH.almPLCFault.REST,432388.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D_WH.almPLCFault.ACKN,432388.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D_WH.almPLCFault.UACK,432388.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D_WH.almPLCFault.MCmd_Enable,432388.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D_WH.almPLCFault.MCmd_Disable,432388.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D_WH.almPLCFault.OCmd_Shelve,432388.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D_WH.almPLCFault.OCmd_Unshelve,432388.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D_WH.almPLCFault.SCmd_Suppress,432388.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D_WH.almPLCFault.SCmd_UnSuppress,432389.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D_WH.almPLCFault.AEShelveTMRDN,432389.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D_WH.almPLCFault.Bad,432389.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D_WH.almPLCFault.Suppress,432390.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.UnSuppress,432390.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Shelve,432390.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.UnShelve,432390.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Enable,432390.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Disable,432390.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Ack,432390.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Reset,432390.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Suppressed,432390.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Shelved,432390.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Disabled,432390.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Acked,432390.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D_WH.almPLCFault.Alarm,432390.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Fault,432412.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_LL.Alarm.AlarmState,432412.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_LL.Alarm.GlobalReset,432412.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_LL.Alarm.FaultInAlarm,432412.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_LL.Alarm.ALRM,432412.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_LL.Alarm.ANUN,432412.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_LL.Alarm.AKED,432412.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_LL.Alarm.Resetable,432412.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_LL.Alarm.REST,432412.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_LL.Alarm.ACKN,432412.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_LL.Alarm.UACK,432412.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_LL.Alarm.MCmd_Enable,432412.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_LL.Alarm.MCmd_Disable,432412.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_LL.Alarm.OCmd_Shelve,432412.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_LL.Alarm.OCmd_Unshelve,432412.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_LL.Alarm.SCmd_Suppress,432412.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_LL.Alarm.SCmd_UnSuppress,432413.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_LL.Alarm.AEShelveTMRDN,432413.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_LL.Alarm.Bad,432413.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_LL.Alarm.Suppress,432414.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.UnSuppress,432414.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Shelve,432414.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.UnShelve,432414.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Enable,432414.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Disable,432414.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Ack,432414.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Reset,432414.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_LL.Alarm.Suppressed,432414.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_LL.Alarm.Shelved,432414.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_LL.Alarm.Disabled,432414.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_LL.Alarm.Acked,432414.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_LL.Alarm.Alarm,432414.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Fault,432424.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_LL.almPLCFault.AlarmState,432424.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_LL.almPLCFault.GlobalReset,432424.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_LL.almPLCFault.FaultInAlarm,432424.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_LL.almPLCFault.ALRM,432424.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_LL.almPLCFault.ANUN,432424.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_LL.almPLCFault.AKED,432424.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_LL.almPLCFault.Resetable,432424.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_LL.almPLCFault.REST,432424.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_LL.almPLCFault.ACKN,432424.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_LL.almPLCFault.UACK,432424.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_LL.almPLCFault.MCmd_Enable,432424.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_LL.almPLCFault.MCmd_Disable,432424.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_LL.almPLCFault.OCmd_Shelve,432424.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_LL.almPLCFault.OCmd_Unshelve,432424.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_LL.almPLCFault.SCmd_Suppress,432424.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_LL.almPLCFault.SCmd_UnSuppress,432425.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_LL.almPLCFault.AEShelveTMRDN,432425.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_LL.almPLCFault.Bad,432425.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_LL.almPLCFault.Suppress,432426.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.UnSuppress,432426.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Shelve,432426.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.UnShelve,432426.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Enable,432426.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Disable,432426.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Ack,432426.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Reset,432426.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Suppressed,432426.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Shelved,432426.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Disabled,432426.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Acked,432426.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_LL.almPLCFault.Alarm,432426.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Fault,432446.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_PL.Alarm.AlarmState,432446.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_PL.Alarm.GlobalReset,432446.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_PL.Alarm.FaultInAlarm,432446.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_PL.Alarm.ALRM,432446.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_PL.Alarm.ANUN,432446.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_PL.Alarm.AKED,432446.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_PL.Alarm.Resetable,432446.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_PL.Alarm.REST,432446.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_PL.Alarm.ACKN,432446.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_PL.Alarm.UACK,432446.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_PL.Alarm.MCmd_Enable,432446.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_PL.Alarm.MCmd_Disable,432446.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_PL.Alarm.OCmd_Shelve,432446.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_PL.Alarm.OCmd_Unshelve,432446.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_PL.Alarm.SCmd_Suppress,432446.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_PL.Alarm.SCmd_UnSuppress,432447.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_PL.Alarm.AEShelveTMRDN,432447.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_PL.Alarm.Bad,432447.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_PL.Alarm.Suppress,432448.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.UnSuppress,432448.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Shelve,432448.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.UnShelve,432448.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Enable,432448.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Disable,432448.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Ack,432448.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Reset,432448.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_PL.Alarm.Suppressed,432448.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_PL.Alarm.Shelved,432448.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_PL.Alarm.Disabled,432448.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_PL.Alarm.Acked,432448.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_PL.Alarm.Alarm,432448.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Fault,432458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_PL.almPLCFault.AlarmState,432458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_PL.almPLCFault.GlobalReset,432458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_PL.almPLCFault.FaultInAlarm,432458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_PL.almPLCFault.ALRM,432458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_PL.almPLCFault.ANUN,432458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_PL.almPLCFault.AKED,432458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_PL.almPLCFault.Resetable,432458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_PL.almPLCFault.REST,432458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_PL.almPLCFault.ACKN,432458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_PL.almPLCFault.UACK,432458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_PL.almPLCFault.MCmd_Enable,432458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_PL.almPLCFault.MCmd_Disable,432458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_PL.almPLCFault.OCmd_Shelve,432458.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_PL.almPLCFault.OCmd_Unshelve,432458.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_PL.almPLCFault.SCmd_Suppress,432458.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_PL.almPLCFault.SCmd_UnSuppress,432459.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_PL.almPLCFault.AEShelveTMRDN,432459.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_PL.almPLCFault.Bad,432459.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_PL.almPLCFault.Suppress,432460.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.UnSuppress,432460.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Shelve,432460.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.UnShelve,432460.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Enable,432460.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Disable,432460.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Ack,432460.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Reset,432460.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Suppressed,432460.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Shelved,432460.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Disabled,432460.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Acked,432460.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_PL.almPLCFault.Alarm,432460.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Fault,432482.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_SH.Alarm.AlarmState,432482.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_SH.Alarm.GlobalReset,432482.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_SH.Alarm.FaultInAlarm,432482.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_SH.Alarm.ALRM,432482.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_SH.Alarm.ANUN,432482.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_SH.Alarm.AKED,432482.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_SH.Alarm.Resetable,432482.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_SH.Alarm.REST,432482.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_SH.Alarm.ACKN,432482.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_SH.Alarm.UACK,432482.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_SH.Alarm.MCmd_Enable,432482.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_SH.Alarm.MCmd_Disable,432482.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_SH.Alarm.OCmd_Shelve,432482.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_SH.Alarm.OCmd_Unshelve,432482.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_SH.Alarm.SCmd_Suppress,432482.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_SH.Alarm.SCmd_UnSuppress,432483.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_SH.Alarm.AEShelveTMRDN,432483.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_SH.Alarm.Bad,432483.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_SH.Alarm.Suppress,432484.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.UnSuppress,432484.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Shelve,432484.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.UnShelve,432484.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Enable,432484.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Disable,432484.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Ack,432484.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Reset,432484.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_SH.Alarm.Suppressed,432484.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_SH.Alarm.Shelved,432484.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_SH.Alarm.Disabled,432484.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_SH.Alarm.Acked,432484.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_SH.Alarm.Alarm,432484.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Fault,432494.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_SH.almPLCFault.AlarmState,432494.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_SH.almPLCFault.GlobalReset,432494.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_SH.almPLCFault.FaultInAlarm,432494.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_SH.almPLCFault.ALRM,432494.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_SH.almPLCFault.ANUN,432494.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_SH.almPLCFault.AKED,432494.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_SH.almPLCFault.Resetable,432494.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_SH.almPLCFault.REST,432494.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_SH.almPLCFault.ACKN,432494.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_SH.almPLCFault.UACK,432494.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_SH.almPLCFault.MCmd_Enable,432494.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_SH.almPLCFault.MCmd_Disable,432494.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_SH.almPLCFault.OCmd_Shelve,432494.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_SH.almPLCFault.OCmd_Unshelve,432494.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_SH.almPLCFault.SCmd_Suppress,432494.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_SH.almPLCFault.SCmd_UnSuppress,432495.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_SH.almPLCFault.AEShelveTMRDN,432495.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_SH.almPLCFault.Bad,432495.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_SH.almPLCFault.Suppress,432496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.UnSuppress,432496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Shelve,432496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.UnShelve,432496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Enable,432496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Disable,432496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Ack,432496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Reset,432496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Suppressed,432496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Shelved,432496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Disabled,432496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Acked,432496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_SH.almPLCFault.Alarm,432496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Fault,432516.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_TH.Alarm.AlarmState,432516.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_TH.Alarm.GlobalReset,432516.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_TH.Alarm.FaultInAlarm,432516.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_TH.Alarm.ALRM,432516.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_TH.Alarm.ANUN,432516.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_TH.Alarm.AKED,432516.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_TH.Alarm.Resetable,432516.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_TH.Alarm.REST,432516.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_TH.Alarm.ACKN,432516.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_TH.Alarm.UACK,432516.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_TH.Alarm.MCmd_Enable,432516.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_TH.Alarm.MCmd_Disable,432516.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_TH.Alarm.OCmd_Shelve,432516.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_TH.Alarm.OCmd_Unshelve,432516.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_TH.Alarm.SCmd_Suppress,432516.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_TH.Alarm.SCmd_UnSuppress,432517.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_TH.Alarm.AEShelveTMRDN,432517.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_TH.Alarm.Bad,432517.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_TH.Alarm.Suppress,432518.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.UnSuppress,432518.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Shelve,432518.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.UnShelve,432518.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Enable,432518.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Disable,432518.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Ack,432518.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Reset,432518.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_TH.Alarm.Suppressed,432518.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_TH.Alarm.Shelved,432518.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_TH.Alarm.Disabled,432518.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_TH.Alarm.Acked,432518.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_TH.Alarm.Alarm,432518.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Fault,432528.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_TH.almPLCFault.AlarmState,432528.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_TH.almPLCFault.GlobalReset,432528.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_TH.almPLCFault.FaultInAlarm,432528.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_TH.almPLCFault.ALRM,432528.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_TH.almPLCFault.ANUN,432528.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_TH.almPLCFault.AKED,432528.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_TH.almPLCFault.Resetable,432528.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_TH.almPLCFault.REST,432528.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_TH.almPLCFault.ACKN,432528.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_TH.almPLCFault.UACK,432528.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_TH.almPLCFault.MCmd_Enable,432528.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_TH.almPLCFault.MCmd_Disable,432528.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_TH.almPLCFault.OCmd_Shelve,432528.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_TH.almPLCFault.OCmd_Unshelve,432528.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_TH.almPLCFault.SCmd_Suppress,432528.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_TH.almPLCFault.SCmd_UnSuppress,432529.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_TH.almPLCFault.AEShelveTMRDN,432529.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_TH.almPLCFault.Bad,432529.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_TH.almPLCFault.Suppress,432530.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.UnSuppress,432530.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Shelve,432530.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.UnShelve,432530.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Enable,432530.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Disable,432530.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Ack,432530.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Reset,432530.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Suppressed,432530.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Shelved,432530.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Disabled,432530.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Acked,432530.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_TH.almPLCFault.Alarm,432530.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Fault,432552.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_XA1.Alarm.AlarmState,432552.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_XA1.Alarm.GlobalReset,432552.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_XA1.Alarm.FaultInAlarm,432552.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA1.Alarm.ALRM,432552.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_XA1.Alarm.ANUN,432552.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_XA1.Alarm.AKED,432552.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_XA1.Alarm.Resetable,432552.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_XA1.Alarm.REST,432552.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_XA1.Alarm.ACKN,432552.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_XA1.Alarm.UACK,432552.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_XA1.Alarm.MCmd_Enable,432552.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA1.Alarm.MCmd_Disable,432552.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA1.Alarm.OCmd_Shelve,432552.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_XA1.Alarm.OCmd_Unshelve,432552.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_XA1.Alarm.SCmd_Suppress,432552.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_XA1.Alarm.SCmd_UnSuppress,432553.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_XA1.Alarm.AEShelveTMRDN,432553.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_XA1.Alarm.Bad,432553.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_XA1.Alarm.Suppress,432554.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.UnSuppress,432554.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Shelve,432554.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.UnShelve,432554.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Enable,432554.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Disable,432554.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Ack,432554.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Reset,432554.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_XA1.Alarm.Suppressed,432554.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_XA1.Alarm.Shelved,432554.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_XA1.Alarm.Disabled,432554.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_XA1.Alarm.Acked,432554.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_XA1.Alarm.Alarm,432554.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Fault,432564.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_XA1.almPLCFault.AlarmState,432564.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_XA1.almPLCFault.GlobalReset,432564.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_XA1.almPLCFault.FaultInAlarm,432564.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA1.almPLCFault.ALRM,432564.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_XA1.almPLCFault.ANUN,432564.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_XA1.almPLCFault.AKED,432564.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_XA1.almPLCFault.Resetable,432564.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_XA1.almPLCFault.REST,432564.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_XA1.almPLCFault.ACKN,432564.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_XA1.almPLCFault.UACK,432564.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_XA1.almPLCFault.MCmd_Enable,432564.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.MCmd_Disable,432564.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.OCmd_Shelve,432564.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.OCmd_Unshelve,432564.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.SCmd_Suppress,432564.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.SCmd_UnSuppress,432565.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_XA1.almPLCFault.AEShelveTMRDN,432565.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_XA1.almPLCFault.Bad,432565.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_XA1.almPLCFault.Suppress,432566.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.UnSuppress,432566.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Shelve,432566.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.UnShelve,432566.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Enable,432566.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Disable,432566.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Ack,432566.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Reset,432566.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Suppressed,432566.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Shelved,432566.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Disabled,432566.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Acked,432566.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_XA1.almPLCFault.Alarm,432566.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Fault,432586.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_XA2.Alarm.AlarmState,432586.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_XA2.Alarm.GlobalReset,432586.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_XA2.Alarm.FaultInAlarm,432586.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA2.Alarm.ALRM,432586.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_XA2.Alarm.ANUN,432586.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_XA2.Alarm.AKED,432586.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_XA2.Alarm.Resetable,432586.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_XA2.Alarm.REST,432586.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_XA2.Alarm.ACKN,432586.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_XA2.Alarm.UACK,432586.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_XA2.Alarm.MCmd_Enable,432586.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA2.Alarm.MCmd_Disable,432586.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA2.Alarm.OCmd_Shelve,432586.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_XA2.Alarm.OCmd_Unshelve,432586.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_XA2.Alarm.SCmd_Suppress,432586.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_XA2.Alarm.SCmd_UnSuppress,432587.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_XA2.Alarm.AEShelveTMRDN,432587.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_XA2.Alarm.Bad,432587.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_XA2.Alarm.Suppress,432588.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.UnSuppress,432588.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Shelve,432588.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.UnShelve,432588.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Enable,432588.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Disable,432588.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Ack,432588.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Reset,432588.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_XA2.Alarm.Suppressed,432588.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_XA2.Alarm.Shelved,432588.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_XA2.Alarm.Disabled,432588.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_XA2.Alarm.Acked,432588.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_XA2.Alarm.Alarm,432588.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Fault,432598.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_GEN_0131_1_XA2.almPLCFault.AlarmState,432598.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_GEN_0131_1_XA2.almPLCFault.GlobalReset,432598.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_GEN_0131_1_XA2.almPLCFault.FaultInAlarm,432598.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_GEN_0131_1_XA2.almPLCFault.ALRM,432598.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_GEN_0131_1_XA2.almPLCFault.ANUN,432598.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_GEN_0131_1_XA2.almPLCFault.AKED,432598.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_GEN_0131_1_XA2.almPLCFault.Resetable,432598.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_GEN_0131_1_XA2.almPLCFault.REST,432598.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_GEN_0131_1_XA2.almPLCFault.ACKN,432598.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_GEN_0131_1_XA2.almPLCFault.UACK,432598.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_GEN_0131_1_XA2.almPLCFault.MCmd_Enable,432598.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.MCmd_Disable,432598.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.OCmd_Shelve,432598.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.OCmd_Unshelve,432598.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.SCmd_Suppress,432598.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.SCmd_UnSuppress,432599.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_GEN_0131_1_XA2.almPLCFault.AEShelveTMRDN,432599.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_GEN_0131_1_XA2.almPLCFault.Bad,432599.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_GEN_0131_1_XA2.almPLCFault.Suppress,432600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.UnSuppress,432600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Shelve,432600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.UnShelve,432600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Enable,432600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Disable,432600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Ack,432600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Reset,432600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Suppressed,432600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Shelved,432600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Disabled,432600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Acked,432600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_GEN_0131_1_XA2.almPLCFault.Alarm,432600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Fault,432622.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_FA.Alarm.AlarmState,432622.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_FA.Alarm.GlobalReset,432622.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_FA.Alarm.FaultInAlarm,432622.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FA.Alarm.ALRM,432622.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_FA.Alarm.ANUN,432622.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_FA.Alarm.AKED,432622.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_FA.Alarm.Resetable,432622.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_FA.Alarm.REST,432622.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_FA.Alarm.ACKN,432622.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_FA.Alarm.UACK,432622.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_FA.Alarm.MCmd_Enable,432622.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FA.Alarm.MCmd_Disable,432622.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FA.Alarm.OCmd_Shelve,432622.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_FA.Alarm.OCmd_Unshelve,432622.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_FA.Alarm.SCmd_Suppress,432622.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_FA.Alarm.SCmd_UnSuppress,432623.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_FA.Alarm.AEShelveTMRDN,432623.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_FA.Alarm.Bad,432623.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_FA.Alarm.Suppress,432624.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.UnSuppress,432624.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Shelve,432624.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.UnShelve,432624.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Enable,432624.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Disable,432624.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Ack,432624.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Reset,432624.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_FA.Alarm.Suppressed,432624.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_FA.Alarm.Shelved,432624.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_FA.Alarm.Disabled,432624.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_FA.Alarm.Acked,432624.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_FA.Alarm.Alarm,432624.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Fault,432634.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_FA.almPLCFault.AlarmState,432634.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_FA.almPLCFault.GlobalReset,432634.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_FA.almPLCFault.FaultInAlarm,432634.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FA.almPLCFault.ALRM,432634.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_FA.almPLCFault.ANUN,432634.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_FA.almPLCFault.AKED,432634.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_FA.almPLCFault.Resetable,432634.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_FA.almPLCFault.REST,432634.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_FA.almPLCFault.ACKN,432634.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_FA.almPLCFault.UACK,432634.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_FA.almPLCFault.MCmd_Enable,432634.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FA.almPLCFault.MCmd_Disable,432634.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FA.almPLCFault.OCmd_Shelve,432634.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_FA.almPLCFault.OCmd_Unshelve,432634.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_FA.almPLCFault.SCmd_Suppress,432634.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_FA.almPLCFault.SCmd_UnSuppress,432635.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_FA.almPLCFault.AEShelveTMRDN,432635.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_FA.almPLCFault.Bad,432635.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_FA.almPLCFault.Suppress,432636.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.UnSuppress,432636.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Shelve,432636.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.UnShelve,432636.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Enable,432636.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Disable,432636.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Ack,432636.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Reset,432636.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_FA.almPLCFault.Suppressed,432636.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_FA.almPLCFault.Shelved,432636.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_FA.almPLCFault.Disabled,432636.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_FA.almPLCFault.Acked,432636.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_FA.almPLCFault.Alarm,432636.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Fault,432656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_FH.Alarm.AlarmState,432656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_FH.Alarm.GlobalReset,432656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_FH.Alarm.FaultInAlarm,432656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FH.Alarm.ALRM,432656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_FH.Alarm.ANUN,432656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_FH.Alarm.AKED,432656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_FH.Alarm.Resetable,432656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_FH.Alarm.REST,432656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_FH.Alarm.ACKN,432656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_FH.Alarm.UACK,432656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_FH.Alarm.MCmd_Enable,432656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FH.Alarm.MCmd_Disable,432656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FH.Alarm.OCmd_Shelve,432656.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_FH.Alarm.OCmd_Unshelve,432656.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_FH.Alarm.SCmd_Suppress,432656.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_FH.Alarm.SCmd_UnSuppress,432657.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_FH.Alarm.AEShelveTMRDN,432657.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_FH.Alarm.Bad,432657.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_FH.Alarm.Suppress,432658.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.UnSuppress,432658.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Shelve,432658.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.UnShelve,432658.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Enable,432658.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Disable,432658.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Ack,432658.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Reset,432658.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_FH.Alarm.Suppressed,432658.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_FH.Alarm.Shelved,432658.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_FH.Alarm.Disabled,432658.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_FH.Alarm.Acked,432658.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_FH.Alarm.Alarm,432658.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Fault,432668.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_FH.almPLCFault.AlarmState,432668.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_FH.almPLCFault.GlobalReset,432668.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_FH.almPLCFault.FaultInAlarm,432668.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_FH.almPLCFault.ALRM,432668.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_FH.almPLCFault.ANUN,432668.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_FH.almPLCFault.AKED,432668.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_FH.almPLCFault.Resetable,432668.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_FH.almPLCFault.REST,432668.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_FH.almPLCFault.ACKN,432668.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_FH.almPLCFault.UACK,432668.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_FH.almPLCFault.MCmd_Enable,432668.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_FH.almPLCFault.MCmd_Disable,432668.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_FH.almPLCFault.OCmd_Shelve,432668.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_FH.almPLCFault.OCmd_Unshelve,432668.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_FH.almPLCFault.SCmd_Suppress,432668.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_FH.almPLCFault.SCmd_UnSuppress,432669.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_FH.almPLCFault.AEShelveTMRDN,432669.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_FH.almPLCFault.Bad,432669.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_FH.almPLCFault.Suppress,432670.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.UnSuppress,432670.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Shelve,432670.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.UnShelve,432670.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Enable,432670.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Disable,432670.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Ack,432670.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Reset,432670.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_FH.almPLCFault.Suppressed,432670.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_FH.almPLCFault.Shelved,432670.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_FH.almPLCFault.Disabled,432670.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_FH.almPLCFault.Acked,432670.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_FH.almPLCFault.Alarm,432670.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Fault,432692.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_PH.Alarm.AlarmState,432692.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_PH.Alarm.GlobalReset,432692.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_PH.Alarm.FaultInAlarm,432692.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_PH.Alarm.ALRM,432692.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_PH.Alarm.ANUN,432692.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_PH.Alarm.AKED,432692.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_PH.Alarm.Resetable,432692.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_PH.Alarm.REST,432692.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_PH.Alarm.ACKN,432692.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_PH.Alarm.UACK,432692.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_PH.Alarm.MCmd_Enable,432692.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_PH.Alarm.MCmd_Disable,432692.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_PH.Alarm.OCmd_Shelve,432692.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_PH.Alarm.OCmd_Unshelve,432692.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_PH.Alarm.SCmd_Suppress,432692.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_PH.Alarm.SCmd_UnSuppress,432693.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_PH.Alarm.AEShelveTMRDN,432693.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_PH.Alarm.Bad,432693.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_PH.Alarm.Suppress,432694.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.UnSuppress,432694.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Shelve,432694.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.UnShelve,432694.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Enable,432694.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Disable,432694.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Ack,432694.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Reset,432694.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_PH.Alarm.Suppressed,432694.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_PH.Alarm.Shelved,432694.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_PH.Alarm.Disabled,432694.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_PH.Alarm.Acked,432694.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_PH.Alarm.Alarm,432694.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Fault,432704.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_PH.almPLCFault.AlarmState,432704.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_PH.almPLCFault.GlobalReset,432704.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_PH.almPLCFault.FaultInAlarm,432704.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_PH.almPLCFault.ALRM,432704.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_PH.almPLCFault.ANUN,432704.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_PH.almPLCFault.AKED,432704.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_PH.almPLCFault.Resetable,432704.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_PH.almPLCFault.REST,432704.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_PH.almPLCFault.ACKN,432704.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_PH.almPLCFault.UACK,432704.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_PH.almPLCFault.MCmd_Enable,432704.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_PH.almPLCFault.MCmd_Disable,432704.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_PH.almPLCFault.OCmd_Shelve,432704.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_PH.almPLCFault.OCmd_Unshelve,432704.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_PH.almPLCFault.SCmd_Suppress,432704.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_PH.almPLCFault.SCmd_UnSuppress,432705.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_PH.almPLCFault.AEShelveTMRDN,432705.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_PH.almPLCFault.Bad,432705.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_PH.almPLCFault.Suppress,432706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.UnSuppress,432706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Shelve,432706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.UnShelve,432706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Enable,432706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Disable,432706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Ack,432706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Reset,432706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_PH.almPLCFault.Suppressed,432706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_PH.almPLCFault.Shelved,432706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_PH.almPLCFault.Disabled,432706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_PH.almPLCFault.Acked,432706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_PH.almPLCFault.Alarm,432706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Fault,432726.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH1.Alarm.AlarmState,432726.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH1.Alarm.GlobalReset,432726.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH1.Alarm.FaultInAlarm,432726.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH1.Alarm.ALRM,432726.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH1.Alarm.ANUN,432726.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH1.Alarm.AKED,432726.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH1.Alarm.Resetable,432726.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH1.Alarm.REST,432726.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH1.Alarm.ACKN,432726.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH1.Alarm.UACK,432726.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH1.Alarm.MCmd_Enable,432726.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH1.Alarm.MCmd_Disable,432726.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH1.Alarm.OCmd_Shelve,432726.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH1.Alarm.OCmd_Unshelve,432726.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH1.Alarm.SCmd_Suppress,432726.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH1.Alarm.SCmd_UnSuppress,432727.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH1.Alarm.AEShelveTMRDN,432727.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH1.Alarm.Bad,432727.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH1.Alarm.Suppress,432728.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.UnSuppress,432728.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Shelve,432728.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.UnShelve,432728.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Enable,432728.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Disable,432728.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Ack,432728.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Reset,432728.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH1.Alarm.Suppressed,432728.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH1.Alarm.Shelved,432728.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH1.Alarm.Disabled,432728.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH1.Alarm.Acked,432728.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH1.Alarm.Alarm,432728.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Fault,432738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH1.almPLCFault.AlarmState,432738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH1.almPLCFault.GlobalReset,432738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH1.almPLCFault.FaultInAlarm,432738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH1.almPLCFault.ALRM,432738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH1.almPLCFault.ANUN,432738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH1.almPLCFault.AKED,432738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH1.almPLCFault.Resetable,432738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH1.almPLCFault.REST,432738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH1.almPLCFault.ACKN,432738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH1.almPLCFault.UACK,432738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH1.almPLCFault.MCmd_Enable,432738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH1.almPLCFault.MCmd_Disable,432738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH1.almPLCFault.OCmd_Shelve,432738.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH1.almPLCFault.OCmd_Unshelve,432738.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH1.almPLCFault.SCmd_Suppress,432738.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH1.almPLCFault.SCmd_UnSuppress,432739.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH1.almPLCFault.AEShelveTMRDN,432739.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH1.almPLCFault.Bad,432739.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH1.almPLCFault.Suppress,432740.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.UnSuppress,432740.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Shelve,432740.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.UnShelve,432740.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Enable,432740.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Disable,432740.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Ack,432740.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Reset,432740.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Suppressed,432740.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Shelved,432740.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Disabled,432740.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Acked,432740.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH1.almPLCFault.Alarm,432740.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Fault,432762.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH2.Alarm.AlarmState,432762.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH2.Alarm.GlobalReset,432762.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH2.Alarm.FaultInAlarm,432762.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH2.Alarm.ALRM,432762.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH2.Alarm.ANUN,432762.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH2.Alarm.AKED,432762.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH2.Alarm.Resetable,432762.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH2.Alarm.REST,432762.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH2.Alarm.ACKN,432762.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH2.Alarm.UACK,432762.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH2.Alarm.MCmd_Enable,432762.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH2.Alarm.MCmd_Disable,432762.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH2.Alarm.OCmd_Shelve,432762.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH2.Alarm.OCmd_Unshelve,432762.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH2.Alarm.SCmd_Suppress,432762.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH2.Alarm.SCmd_UnSuppress,432763.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH2.Alarm.AEShelveTMRDN,432763.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH2.Alarm.Bad,432763.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH2.Alarm.Suppress,432764.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.UnSuppress,432764.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Shelve,432764.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.UnShelve,432764.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Enable,432764.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Disable,432764.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Ack,432764.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Reset,432764.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH2.Alarm.Suppressed,432764.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH2.Alarm.Shelved,432764.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH2.Alarm.Disabled,432764.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH2.Alarm.Acked,432764.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH2.Alarm.Alarm,432764.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Fault,432774.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH2.almPLCFault.AlarmState,432774.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH2.almPLCFault.GlobalReset,432774.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH2.almPLCFault.FaultInAlarm,432774.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH2.almPLCFault.ALRM,432774.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH2.almPLCFault.ANUN,432774.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH2.almPLCFault.AKED,432774.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH2.almPLCFault.Resetable,432774.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH2.almPLCFault.REST,432774.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH2.almPLCFault.ACKN,432774.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH2.almPLCFault.UACK,432774.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH2.almPLCFault.MCmd_Enable,432774.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH2.almPLCFault.MCmd_Disable,432774.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH2.almPLCFault.OCmd_Shelve,432774.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH2.almPLCFault.OCmd_Unshelve,432774.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH2.almPLCFault.SCmd_Suppress,432774.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH2.almPLCFault.SCmd_UnSuppress,432775.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH2.almPLCFault.AEShelveTMRDN,432775.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH2.almPLCFault.Bad,432775.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH2.almPLCFault.Suppress,432776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.UnSuppress,432776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Shelve,432776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.UnShelve,432776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Enable,432776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Disable,432776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Ack,432776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Reset,432776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Suppressed,432776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Shelved,432776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Disabled,432776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Acked,432776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH2.almPLCFault.Alarm,432776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Fault,432796.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH3.Alarm.AlarmState,432796.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH3.Alarm.GlobalReset,432796.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH3.Alarm.FaultInAlarm,432796.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH3.Alarm.ALRM,432796.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH3.Alarm.ANUN,432796.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH3.Alarm.AKED,432796.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH3.Alarm.Resetable,432796.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH3.Alarm.REST,432796.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH3.Alarm.ACKN,432796.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH3.Alarm.UACK,432796.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH3.Alarm.MCmd_Enable,432796.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH3.Alarm.MCmd_Disable,432796.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH3.Alarm.OCmd_Shelve,432796.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH3.Alarm.OCmd_Unshelve,432796.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH3.Alarm.SCmd_Suppress,432796.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH3.Alarm.SCmd_UnSuppress,432797.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH3.Alarm.AEShelveTMRDN,432797.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH3.Alarm.Bad,432797.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH3.Alarm.Suppress,432798.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.UnSuppress,432798.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Shelve,432798.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.UnShelve,432798.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Enable,432798.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Disable,432798.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Ack,432798.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Reset,432798.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH3.Alarm.Suppressed,432798.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH3.Alarm.Shelved,432798.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH3.Alarm.Disabled,432798.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH3.Alarm.Acked,432798.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH3.Alarm.Alarm,432798.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Fault,432808.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TH3.almPLCFault.AlarmState,432808.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TH3.almPLCFault.GlobalReset,432808.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TH3.almPLCFault.FaultInAlarm,432808.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TH3.almPLCFault.ALRM,432808.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TH3.almPLCFault.ANUN,432808.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TH3.almPLCFault.AKED,432808.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TH3.almPLCFault.Resetable,432808.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TH3.almPLCFault.REST,432808.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TH3.almPLCFault.ACKN,432808.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TH3.almPLCFault.UACK,432808.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TH3.almPLCFault.MCmd_Enable,432808.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TH3.almPLCFault.MCmd_Disable,432808.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TH3.almPLCFault.OCmd_Shelve,432808.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TH3.almPLCFault.OCmd_Unshelve,432808.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TH3.almPLCFault.SCmd_Suppress,432808.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TH3.almPLCFault.SCmd_UnSuppress,432809.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TH3.almPLCFault.AEShelveTMRDN,432809.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TH3.almPLCFault.Bad,432809.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TH3.almPLCFault.Suppress,432810.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.UnSuppress,432810.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Shelve,432810.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.UnShelve,432810.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Enable,432810.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Disable,432810.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Ack,432810.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Reset,432810.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Suppressed,432810.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Shelved,432810.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Disabled,432810.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Acked,432810.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TH3.almPLCFault.Alarm,432810.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Fault,432832.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TL1.Alarm.AlarmState,432832.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TL1.Alarm.GlobalReset,432832.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TL1.Alarm.FaultInAlarm,432832.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL1.Alarm.ALRM,432832.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TL1.Alarm.ANUN,432832.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TL1.Alarm.AKED,432832.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TL1.Alarm.Resetable,432832.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TL1.Alarm.REST,432832.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TL1.Alarm.ACKN,432832.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TL1.Alarm.UACK,432832.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TL1.Alarm.MCmd_Enable,432832.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL1.Alarm.MCmd_Disable,432832.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL1.Alarm.OCmd_Shelve,432832.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TL1.Alarm.OCmd_Unshelve,432832.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TL1.Alarm.SCmd_Suppress,432832.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TL1.Alarm.SCmd_UnSuppress,432833.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TL1.Alarm.AEShelveTMRDN,432833.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TL1.Alarm.Bad,432833.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TL1.Alarm.Suppress,432834.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.UnSuppress,432834.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Shelve,432834.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.UnShelve,432834.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Enable,432834.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Disable,432834.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Ack,432834.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Reset,432834.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TL1.Alarm.Suppressed,432834.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TL1.Alarm.Shelved,432834.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TL1.Alarm.Disabled,432834.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TL1.Alarm.Acked,432834.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TL1.Alarm.Alarm,432834.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Fault,432844.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TL1.almPLCFault.AlarmState,432844.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TL1.almPLCFault.GlobalReset,432844.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TL1.almPLCFault.FaultInAlarm,432844.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL1.almPLCFault.ALRM,432844.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TL1.almPLCFault.ANUN,432844.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TL1.almPLCFault.AKED,432844.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TL1.almPLCFault.Resetable,432844.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TL1.almPLCFault.REST,432844.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TL1.almPLCFault.ACKN,432844.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TL1.almPLCFault.UACK,432844.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TL1.almPLCFault.MCmd_Enable,432844.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL1.almPLCFault.MCmd_Disable,432844.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL1.almPLCFault.OCmd_Shelve,432844.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TL1.almPLCFault.OCmd_Unshelve,432844.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TL1.almPLCFault.SCmd_Suppress,432844.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TL1.almPLCFault.SCmd_UnSuppress,432845.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TL1.almPLCFault.AEShelveTMRDN,432845.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TL1.almPLCFault.Bad,432845.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TL1.almPLCFault.Suppress,432846.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.UnSuppress,432846.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Shelve,432846.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.UnShelve,432846.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Enable,432846.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Disable,432846.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Ack,432846.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Reset,432846.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Suppressed,432846.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Shelved,432846.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Disabled,432846.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Acked,432846.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TL1.almPLCFault.Alarm,432846.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Fault,432866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TL2.Alarm.AlarmState,432866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TL2.Alarm.GlobalReset,432866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TL2.Alarm.FaultInAlarm,432866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL2.Alarm.ALRM,432866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TL2.Alarm.ANUN,432866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TL2.Alarm.AKED,432866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TL2.Alarm.Resetable,432866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TL2.Alarm.REST,432866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TL2.Alarm.ACKN,432866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TL2.Alarm.UACK,432866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TL2.Alarm.MCmd_Enable,432866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL2.Alarm.MCmd_Disable,432866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL2.Alarm.OCmd_Shelve,432866.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TL2.Alarm.OCmd_Unshelve,432866.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TL2.Alarm.SCmd_Suppress,432866.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TL2.Alarm.SCmd_UnSuppress,432867.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TL2.Alarm.AEShelveTMRDN,432867.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TL2.Alarm.Bad,432867.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TL2.Alarm.Suppress,432868.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.UnSuppress,432868.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Shelve,432868.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.UnShelve,432868.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Enable,432868.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Disable,432868.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Ack,432868.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Reset,432868.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TL2.Alarm.Suppressed,432868.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TL2.Alarm.Shelved,432868.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TL2.Alarm.Disabled,432868.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TL2.Alarm.Acked,432868.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TL2.Alarm.Alarm,432868.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Fault,432878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_TL2.almPLCFault.AlarmState,432878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_TL2.almPLCFault.GlobalReset,432878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_TL2.almPLCFault.FaultInAlarm,432878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_TL2.almPLCFault.ALRM,432878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_TL2.almPLCFault.ANUN,432878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_TL2.almPLCFault.AKED,432878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_TL2.almPLCFault.Resetable,432878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_TL2.almPLCFault.REST,432878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_TL2.almPLCFault.ACKN,432878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_TL2.almPLCFault.UACK,432878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_TL2.almPLCFault.MCmd_Enable,432878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_TL2.almPLCFault.MCmd_Disable,432878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_TL2.almPLCFault.OCmd_Shelve,432878.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_TL2.almPLCFault.OCmd_Unshelve,432878.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_TL2.almPLCFault.SCmd_Suppress,432878.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_TL2.almPLCFault.SCmd_UnSuppress,432879.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_TL2.almPLCFault.AEShelveTMRDN,432879.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_TL2.almPLCFault.Bad,432879.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_TL2.almPLCFault.Suppress,432880.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.UnSuppress,432880.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Shelve,432880.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.UnShelve,432880.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Enable,432880.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Disable,432880.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Ack,432880.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Reset,432880.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Suppressed,432880.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Shelved,432880.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Disabled,432880.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Acked,432880.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_TL2.almPLCFault.Alarm,432880.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Fault,432902.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA1.Alarm.AlarmState,432902.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA1.Alarm.GlobalReset,432902.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA1.Alarm.FaultInAlarm,432902.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA1.Alarm.ALRM,432902.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA1.Alarm.ANUN,432902.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA1.Alarm.AKED,432902.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA1.Alarm.Resetable,432902.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA1.Alarm.REST,432902.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA1.Alarm.ACKN,432902.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA1.Alarm.UACK,432902.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA1.Alarm.MCmd_Enable,432902.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA1.Alarm.MCmd_Disable,432902.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA1.Alarm.OCmd_Shelve,432902.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA1.Alarm.OCmd_Unshelve,432902.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA1.Alarm.SCmd_Suppress,432902.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA1.Alarm.SCmd_UnSuppress,432903.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA1.Alarm.AEShelveTMRDN,432903.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA1.Alarm.Bad,432903.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA1.Alarm.Suppress,432904.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.UnSuppress,432904.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Shelve,432904.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.UnShelve,432904.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Enable,432904.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Disable,432904.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Ack,432904.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Reset,432904.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA1.Alarm.Suppressed,432904.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA1.Alarm.Shelved,432904.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA1.Alarm.Disabled,432904.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA1.Alarm.Acked,432904.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA1.Alarm.Alarm,432904.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Fault,432914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA1.almPLCFault.AlarmState,432914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA1.almPLCFault.GlobalReset,432914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA1.almPLCFault.FaultInAlarm,432914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA1.almPLCFault.ALRM,432914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA1.almPLCFault.ANUN,432914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA1.almPLCFault.AKED,432914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA1.almPLCFault.Resetable,432914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA1.almPLCFault.REST,432914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA1.almPLCFault.ACKN,432914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA1.almPLCFault.UACK,432914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA1.almPLCFault.MCmd_Enable,432914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA1.almPLCFault.MCmd_Disable,432914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA1.almPLCFault.OCmd_Shelve,432914.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA1.almPLCFault.OCmd_Unshelve,432914.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA1.almPLCFault.SCmd_Suppress,432914.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA1.almPLCFault.SCmd_UnSuppress,432915.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA1.almPLCFault.AEShelveTMRDN,432915.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA1.almPLCFault.Bad,432915.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA1.almPLCFault.Suppress,432916.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.UnSuppress,432916.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Shelve,432916.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.UnShelve,432916.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Enable,432916.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Disable,432916.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Ack,432916.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Reset,432916.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Suppressed,432916.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Shelved,432916.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Disabled,432916.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Acked,432916.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA1.almPLCFault.Alarm,432916.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Fault,432936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA2.Alarm.AlarmState,432936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA2.Alarm.GlobalReset,432936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA2.Alarm.FaultInAlarm,432936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA2.Alarm.ALRM,432936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA2.Alarm.ANUN,432936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA2.Alarm.AKED,432936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA2.Alarm.Resetable,432936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA2.Alarm.REST,432936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA2.Alarm.ACKN,432936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA2.Alarm.UACK,432936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA2.Alarm.MCmd_Enable,432936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA2.Alarm.MCmd_Disable,432936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA2.Alarm.OCmd_Shelve,432936.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA2.Alarm.OCmd_Unshelve,432936.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA2.Alarm.SCmd_Suppress,432936.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA2.Alarm.SCmd_UnSuppress,432937.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA2.Alarm.AEShelveTMRDN,432937.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA2.Alarm.Bad,432937.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA2.Alarm.Suppress,432938.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.UnSuppress,432938.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Shelve,432938.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.UnShelve,432938.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Enable,432938.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Disable,432938.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Ack,432938.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Reset,432938.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA2.Alarm.Suppressed,432938.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA2.Alarm.Shelved,432938.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA2.Alarm.Disabled,432938.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA2.Alarm.Acked,432938.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA2.Alarm.Alarm,432938.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Fault,432948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA2.almPLCFault.AlarmState,432948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA2.almPLCFault.GlobalReset,432948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA2.almPLCFault.FaultInAlarm,432948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA2.almPLCFault.ALRM,432948.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA2.almPLCFault.ANUN,432948.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA2.almPLCFault.AKED,432948.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA2.almPLCFault.Resetable,432948.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA2.almPLCFault.REST,432948.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA2.almPLCFault.ACKN,432948.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA2.almPLCFault.UACK,432948.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA2.almPLCFault.MCmd_Enable,432948.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA2.almPLCFault.MCmd_Disable,432948.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA2.almPLCFault.OCmd_Shelve,432948.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA2.almPLCFault.OCmd_Unshelve,432948.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA2.almPLCFault.SCmd_Suppress,432948.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA2.almPLCFault.SCmd_UnSuppress,432949.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA2.almPLCFault.AEShelveTMRDN,432949.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA2.almPLCFault.Bad,432949.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA2.almPLCFault.Suppress,432950.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.UnSuppress,432950.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Shelve,432950.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.UnShelve,432950.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Enable,432950.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Disable,432950.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Ack,432950.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Reset,432950.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Suppressed,432950.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Shelved,432950.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Disabled,432950.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Acked,432950.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA2.almPLCFault.Alarm,432950.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Fault,432972.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA3.Alarm.AlarmState,432972.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA3.Alarm.GlobalReset,432972.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA3.Alarm.FaultInAlarm,432972.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA3.Alarm.ALRM,432972.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA3.Alarm.ANUN,432972.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA3.Alarm.AKED,432972.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA3.Alarm.Resetable,432972.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA3.Alarm.REST,432972.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA3.Alarm.ACKN,432972.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA3.Alarm.UACK,432972.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA3.Alarm.MCmd_Enable,432972.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA3.Alarm.MCmd_Disable,432972.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA3.Alarm.OCmd_Shelve,432972.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA3.Alarm.OCmd_Unshelve,432972.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA3.Alarm.SCmd_Suppress,432972.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA3.Alarm.SCmd_UnSuppress,432973.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA3.Alarm.AEShelveTMRDN,432973.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA3.Alarm.Bad,432973.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA3.Alarm.Suppress,432974.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.UnSuppress,432974.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Shelve,432974.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.UnShelve,432974.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Enable,432974.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Disable,432974.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Ack,432974.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Reset,432974.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA3.Alarm.Suppressed,432974.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA3.Alarm.Shelved,432974.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA3.Alarm.Disabled,432974.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA3.Alarm.Acked,432974.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA3.Alarm.Alarm,432974.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Fault,432984.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA3.almPLCFault.AlarmState,432984.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA3.almPLCFault.GlobalReset,432984.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA3.almPLCFault.FaultInAlarm,432984.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA3.almPLCFault.ALRM,432984.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA3.almPLCFault.ANUN,432984.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA3.almPLCFault.AKED,432984.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA3.almPLCFault.Resetable,432984.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA3.almPLCFault.REST,432984.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA3.almPLCFault.ACKN,432984.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA3.almPLCFault.UACK,432984.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA3.almPLCFault.MCmd_Enable,432984.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA3.almPLCFault.MCmd_Disable,432984.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA3.almPLCFault.OCmd_Shelve,432984.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA3.almPLCFault.OCmd_Unshelve,432984.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA3.almPLCFault.SCmd_Suppress,432984.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA3.almPLCFault.SCmd_UnSuppress,432985.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA3.almPLCFault.AEShelveTMRDN,432985.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA3.almPLCFault.Bad,432985.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA3.almPLCFault.Suppress,432986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.UnSuppress,432986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Shelve,432986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.UnShelve,432986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Enable,432986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Disable,432986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Ack,432986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Reset,432986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Suppressed,432986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Shelved,432986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Disabled,432986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Acked,432986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA3.almPLCFault.Alarm,432986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Fault,433006.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA4.Alarm.AlarmState,433006.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA4.Alarm.GlobalReset,433006.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA4.Alarm.FaultInAlarm,433006.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA4.Alarm.ALRM,433006.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA4.Alarm.ANUN,433006.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA4.Alarm.AKED,433006.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA4.Alarm.Resetable,433006.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA4.Alarm.REST,433006.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA4.Alarm.ACKN,433006.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA4.Alarm.UACK,433006.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA4.Alarm.MCmd_Enable,433006.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA4.Alarm.MCmd_Disable,433006.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA4.Alarm.OCmd_Shelve,433006.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA4.Alarm.OCmd_Unshelve,433006.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA4.Alarm.SCmd_Suppress,433006.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA4.Alarm.SCmd_UnSuppress,433007.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA4.Alarm.AEShelveTMRDN,433007.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA4.Alarm.Bad,433007.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA4.Alarm.Suppress,433008.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.UnSuppress,433008.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Shelve,433008.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.UnShelve,433008.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Enable,433008.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Disable,433008.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Ack,433008.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Reset,433008.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA4.Alarm.Suppressed,433008.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA4.Alarm.Shelved,433008.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA4.Alarm.Disabled,433008.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA4.Alarm.Acked,433008.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA4.Alarm.Alarm,433008.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Fault,433018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA4.almPLCFault.AlarmState,433018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA4.almPLCFault.GlobalReset,433018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA4.almPLCFault.FaultInAlarm,433018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA4.almPLCFault.ALRM,433018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA4.almPLCFault.ANUN,433018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA4.almPLCFault.AKED,433018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA4.almPLCFault.Resetable,433018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA4.almPLCFault.REST,433018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA4.almPLCFault.ACKN,433018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA4.almPLCFault.UACK,433018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA4.almPLCFault.MCmd_Enable,433018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA4.almPLCFault.MCmd_Disable,433018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA4.almPLCFault.OCmd_Shelve,433018.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA4.almPLCFault.OCmd_Unshelve,433018.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA4.almPLCFault.SCmd_Suppress,433018.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA4.almPLCFault.SCmd_UnSuppress,433019.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA4.almPLCFault.AEShelveTMRDN,433019.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA4.almPLCFault.Bad,433019.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA4.almPLCFault.Suppress,433020.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.UnSuppress,433020.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Shelve,433020.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.UnShelve,433020.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Enable,433020.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Disable,433020.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Ack,433020.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Reset,433020.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Suppressed,433020.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Shelved,433020.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Disabled,433020.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Acked,433020.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA4.almPLCFault.Alarm,433020.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Fault,433042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA5.Alarm.AlarmState,433042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA5.Alarm.GlobalReset,433042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA5.Alarm.FaultInAlarm,433042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA5.Alarm.ALRM,433042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA5.Alarm.ANUN,433042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA5.Alarm.AKED,433042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA5.Alarm.Resetable,433042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA5.Alarm.REST,433042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA5.Alarm.ACKN,433042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA5.Alarm.UACK,433042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA5.Alarm.MCmd_Enable,433042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA5.Alarm.MCmd_Disable,433042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA5.Alarm.OCmd_Shelve,433042.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA5.Alarm.OCmd_Unshelve,433042.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA5.Alarm.SCmd_Suppress,433042.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA5.Alarm.SCmd_UnSuppress,433043.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA5.Alarm.AEShelveTMRDN,433043.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA5.Alarm.Bad,433043.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA5.Alarm.Suppress,433044.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.UnSuppress,433044.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Shelve,433044.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.UnShelve,433044.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Enable,433044.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Disable,433044.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Ack,433044.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Reset,433044.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA5.Alarm.Suppressed,433044.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA5.Alarm.Shelved,433044.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA5.Alarm.Disabled,433044.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA5.Alarm.Acked,433044.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA5.Alarm.Alarm,433044.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Fault,433054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA5.almPLCFault.AlarmState,433054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA5.almPLCFault.GlobalReset,433054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA5.almPLCFault.FaultInAlarm,433054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA5.almPLCFault.ALRM,433054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA5.almPLCFault.ANUN,433054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA5.almPLCFault.AKED,433054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA5.almPLCFault.Resetable,433054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA5.almPLCFault.REST,433054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA5.almPLCFault.ACKN,433054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA5.almPLCFault.UACK,433054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA5.almPLCFault.MCmd_Enable,433054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA5.almPLCFault.MCmd_Disable,433054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA5.almPLCFault.OCmd_Shelve,433054.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA5.almPLCFault.OCmd_Unshelve,433054.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA5.almPLCFault.SCmd_Suppress,433054.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA5.almPLCFault.SCmd_UnSuppress,433055.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA5.almPLCFault.AEShelveTMRDN,433055.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA5.almPLCFault.Bad,433055.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA5.almPLCFault.Suppress,433056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.UnSuppress,433056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Shelve,433056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.UnShelve,433056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Enable,433056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Disable,433056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Ack,433056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Reset,433056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Suppressed,433056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Shelved,433056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Disabled,433056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Acked,433056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA5.almPLCFault.Alarm,433056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Fault,433076.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA6.Alarm.AlarmState,433076.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA6.Alarm.GlobalReset,433076.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA6.Alarm.FaultInAlarm,433076.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA6.Alarm.ALRM,433076.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA6.Alarm.ANUN,433076.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA6.Alarm.AKED,433076.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA6.Alarm.Resetable,433076.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA6.Alarm.REST,433076.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA6.Alarm.ACKN,433076.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA6.Alarm.UACK,433076.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA6.Alarm.MCmd_Enable,433076.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA6.Alarm.MCmd_Disable,433076.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA6.Alarm.OCmd_Shelve,433076.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA6.Alarm.OCmd_Unshelve,433076.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA6.Alarm.SCmd_Suppress,433076.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA6.Alarm.SCmd_UnSuppress,433077.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA6.Alarm.AEShelveTMRDN,433077.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA6.Alarm.Bad,433077.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA6.Alarm.Suppress,433078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.UnSuppress,433078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Shelve,433078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.UnShelve,433078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Enable,433078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Disable,433078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Ack,433078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Reset,433078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA6.Alarm.Suppressed,433078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA6.Alarm.Shelved,433078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA6.Alarm.Disabled,433078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA6.Alarm.Acked,433078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA6.Alarm.Alarm,433078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Fault,433088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA6.almPLCFault.AlarmState,433088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA6.almPLCFault.GlobalReset,433088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA6.almPLCFault.FaultInAlarm,433088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA6.almPLCFault.ALRM,433088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA6.almPLCFault.ANUN,433088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA6.almPLCFault.AKED,433088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA6.almPLCFault.Resetable,433088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA6.almPLCFault.REST,433088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA6.almPLCFault.ACKN,433088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA6.almPLCFault.UACK,433088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA6.almPLCFault.MCmd_Enable,433088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA6.almPLCFault.MCmd_Disable,433088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA6.almPLCFault.OCmd_Shelve,433088.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA6.almPLCFault.OCmd_Unshelve,433088.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA6.almPLCFault.SCmd_Suppress,433088.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA6.almPLCFault.SCmd_UnSuppress,433089.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA6.almPLCFault.AEShelveTMRDN,433089.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA6.almPLCFault.Bad,433089.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA6.almPLCFault.Suppress,433090.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.UnSuppress,433090.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Shelve,433090.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.UnShelve,433090.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Enable,433090.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Disable,433090.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Ack,433090.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Reset,433090.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Suppressed,433090.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Shelved,433090.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Disabled,433090.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Acked,433090.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA6.almPLCFault.Alarm,433090.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Fault,433112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA7.Alarm.AlarmState,433112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA7.Alarm.GlobalReset,433112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA7.Alarm.FaultInAlarm,433112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA7.Alarm.ALRM,433112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA7.Alarm.ANUN,433112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA7.Alarm.AKED,433112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA7.Alarm.Resetable,433112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA7.Alarm.REST,433112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA7.Alarm.ACKN,433112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA7.Alarm.UACK,433112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA7.Alarm.MCmd_Enable,433112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA7.Alarm.MCmd_Disable,433112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA7.Alarm.OCmd_Shelve,433112.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA7.Alarm.OCmd_Unshelve,433112.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA7.Alarm.SCmd_Suppress,433112.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA7.Alarm.SCmd_UnSuppress,433113.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA7.Alarm.AEShelveTMRDN,433113.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA7.Alarm.Bad,433113.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA7.Alarm.Suppress,433114.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.UnSuppress,433114.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Shelve,433114.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.UnShelve,433114.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Enable,433114.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Disable,433114.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Ack,433114.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Reset,433114.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA7.Alarm.Suppressed,433114.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA7.Alarm.Shelved,433114.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA7.Alarm.Disabled,433114.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA7.Alarm.Acked,433114.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA7.Alarm.Alarm,433114.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Fault,433124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA7.almPLCFault.AlarmState,433124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA7.almPLCFault.GlobalReset,433124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA7.almPLCFault.FaultInAlarm,433124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA7.almPLCFault.ALRM,433124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA7.almPLCFault.ANUN,433124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA7.almPLCFault.AKED,433124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA7.almPLCFault.Resetable,433124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA7.almPLCFault.REST,433124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA7.almPLCFault.ACKN,433124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA7.almPLCFault.UACK,433124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA7.almPLCFault.MCmd_Enable,433124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA7.almPLCFault.MCmd_Disable,433124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA7.almPLCFault.OCmd_Shelve,433124.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA7.almPLCFault.OCmd_Unshelve,433124.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA7.almPLCFault.SCmd_Suppress,433124.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA7.almPLCFault.SCmd_UnSuppress,433125.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA7.almPLCFault.AEShelveTMRDN,433125.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA7.almPLCFault.Bad,433125.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA7.almPLCFault.Suppress,433126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.UnSuppress,433126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Shelve,433126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.UnShelve,433126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Enable,433126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Disable,433126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Ack,433126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Reset,433126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Suppressed,433126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Shelved,433126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Disabled,433126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Acked,433126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA7.almPLCFault.Alarm,433126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Fault,433146.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA8.Alarm.AlarmState,433146.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA8.Alarm.GlobalReset,433146.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA8.Alarm.FaultInAlarm,433146.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA8.Alarm.ALRM,433146.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA8.Alarm.ANUN,433146.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA8.Alarm.AKED,433146.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA8.Alarm.Resetable,433146.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA8.Alarm.REST,433146.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA8.Alarm.ACKN,433146.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA8.Alarm.UACK,433146.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA8.Alarm.MCmd_Enable,433146.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA8.Alarm.MCmd_Disable,433146.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA8.Alarm.OCmd_Shelve,433146.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA8.Alarm.OCmd_Unshelve,433146.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA8.Alarm.SCmd_Suppress,433146.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA8.Alarm.SCmd_UnSuppress,433147.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA8.Alarm.AEShelveTMRDN,433147.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA8.Alarm.Bad,433147.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA8.Alarm.Suppress,433148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.UnSuppress,433148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Shelve,433148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.UnShelve,433148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Enable,433148.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Disable,433148.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Ack,433148.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Reset,433148.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA8.Alarm.Suppressed,433148.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA8.Alarm.Shelved,433148.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA8.Alarm.Disabled,433148.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA8.Alarm.Acked,433148.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA8.Alarm.Alarm,433148.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Fault,433158.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA8.almPLCFault.AlarmState,433158.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA8.almPLCFault.GlobalReset,433158.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA8.almPLCFault.FaultInAlarm,433158.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA8.almPLCFault.ALRM,433158.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA8.almPLCFault.ANUN,433158.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA8.almPLCFault.AKED,433158.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA8.almPLCFault.Resetable,433158.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA8.almPLCFault.REST,433158.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA8.almPLCFault.ACKN,433158.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA8.almPLCFault.UACK,433158.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA8.almPLCFault.MCmd_Enable,433158.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA8.almPLCFault.MCmd_Disable,433158.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA8.almPLCFault.OCmd_Shelve,433158.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA8.almPLCFault.OCmd_Unshelve,433158.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA8.almPLCFault.SCmd_Suppress,433158.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA8.almPLCFault.SCmd_UnSuppress,433159.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA8.almPLCFault.AEShelveTMRDN,433159.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA8.almPLCFault.Bad,433159.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA8.almPLCFault.Suppress,433160.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.UnSuppress,433160.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Shelve,433160.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.UnShelve,433160.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Enable,433160.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Disable,433160.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Ack,433160.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Reset,433160.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Suppressed,433160.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Shelved,433160.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Disabled,433160.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Acked,433160.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA8.almPLCFault.Alarm,433160.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Fault,433182.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA9.Alarm.AlarmState,433182.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA9.Alarm.GlobalReset,433182.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA9.Alarm.FaultInAlarm,433182.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA9.Alarm.ALRM,433182.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA9.Alarm.ANUN,433182.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA9.Alarm.AKED,433182.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA9.Alarm.Resetable,433182.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA9.Alarm.REST,433182.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA9.Alarm.ACKN,433182.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA9.Alarm.UACK,433182.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA9.Alarm.MCmd_Enable,433182.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA9.Alarm.MCmd_Disable,433182.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA9.Alarm.OCmd_Shelve,433182.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA9.Alarm.OCmd_Unshelve,433182.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA9.Alarm.SCmd_Suppress,433182.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA9.Alarm.SCmd_UnSuppress,433183.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA9.Alarm.AEShelveTMRDN,433183.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA9.Alarm.Bad,433183.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA9.Alarm.Suppress,433184.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.UnSuppress,433184.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Shelve,433184.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.UnShelve,433184.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Enable,433184.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Disable,433184.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Ack,433184.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Reset,433184.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA9.Alarm.Suppressed,433184.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA9.Alarm.Shelved,433184.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA9.Alarm.Disabled,433184.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA9.Alarm.Acked,433184.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA9.Alarm.Alarm,433184.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Fault,433194.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA9.almPLCFault.AlarmState,433194.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA9.almPLCFault.GlobalReset,433194.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA9.almPLCFault.FaultInAlarm,433194.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA9.almPLCFault.ALRM,433194.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA9.almPLCFault.ANUN,433194.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA9.almPLCFault.AKED,433194.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA9.almPLCFault.Resetable,433194.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA9.almPLCFault.REST,433194.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA9.almPLCFault.ACKN,433194.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA9.almPLCFault.UACK,433194.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA9.almPLCFault.MCmd_Enable,433194.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA9.almPLCFault.MCmd_Disable,433194.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA9.almPLCFault.OCmd_Shelve,433194.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA9.almPLCFault.OCmd_Unshelve,433194.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA9.almPLCFault.SCmd_Suppress,433194.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA9.almPLCFault.SCmd_UnSuppress,433195.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA9.almPLCFault.AEShelveTMRDN,433195.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA9.almPLCFault.Bad,433195.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA9.almPLCFault.Suppress,433196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.UnSuppress,433196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Shelve,433196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.UnShelve,433196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Enable,433196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Disable,433196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Ack,433196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Reset,433196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Suppressed,433196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Shelved,433196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Disabled,433196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Acked,433196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA9.almPLCFault.Alarm,433196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Fault,433216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA10.Alarm.AlarmState,433216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA10.Alarm.GlobalReset,433216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA10.Alarm.FaultInAlarm,433216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA10.Alarm.ALRM,433216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA10.Alarm.ANUN,433216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA10.Alarm.AKED,433216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA10.Alarm.Resetable,433216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA10.Alarm.REST,433216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA10.Alarm.ACKN,433216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA10.Alarm.UACK,433216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA10.Alarm.MCmd_Enable,433216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA10.Alarm.MCmd_Disable,433216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA10.Alarm.OCmd_Shelve,433216.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA10.Alarm.OCmd_Unshelve,433216.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA10.Alarm.SCmd_Suppress,433216.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA10.Alarm.SCmd_UnSuppress,433217.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA10.Alarm.AEShelveTMRDN,433217.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA10.Alarm.Bad,433217.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA10.Alarm.Suppress,433218.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.UnSuppress,433218.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Shelve,433218.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.UnShelve,433218.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Enable,433218.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Disable,433218.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Ack,433218.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Reset,433218.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA10.Alarm.Suppressed,433218.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA10.Alarm.Shelved,433218.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA10.Alarm.Disabled,433218.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA10.Alarm.Acked,433218.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA10.Alarm.Alarm,433218.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Fault,433228.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA10.almPLCFault.AlarmState,433228.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA10.almPLCFault.GlobalReset,433228.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA10.almPLCFault.FaultInAlarm,433228.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA10.almPLCFault.ALRM,433228.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA10.almPLCFault.ANUN,433228.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA10.almPLCFault.AKED,433228.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA10.almPLCFault.Resetable,433228.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA10.almPLCFault.REST,433228.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA10.almPLCFault.ACKN,433228.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA10.almPLCFault.UACK,433228.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA10.almPLCFault.MCmd_Enable,433228.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA10.almPLCFault.MCmd_Disable,433228.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA10.almPLCFault.OCmd_Shelve,433228.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA10.almPLCFault.OCmd_Unshelve,433228.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA10.almPLCFault.SCmd_Suppress,433228.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA10.almPLCFault.SCmd_UnSuppress,433229.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA10.almPLCFault.AEShelveTMRDN,433229.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA10.almPLCFault.Bad,433229.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA10.almPLCFault.Suppress,433230.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.UnSuppress,433230.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Shelve,433230.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.UnShelve,433230.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Enable,433230.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Disable,433230.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Ack,433230.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Reset,433230.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Suppressed,433230.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Shelved,433230.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Disabled,433230.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Acked,433230.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA10.almPLCFault.Alarm,433230.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Fault,433252.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA11.Alarm.AlarmState,433252.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA11.Alarm.GlobalReset,433252.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA11.Alarm.FaultInAlarm,433252.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA11.Alarm.ALRM,433252.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA11.Alarm.ANUN,433252.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA11.Alarm.AKED,433252.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA11.Alarm.Resetable,433252.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA11.Alarm.REST,433252.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA11.Alarm.ACKN,433252.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA11.Alarm.UACK,433252.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA11.Alarm.MCmd_Enable,433252.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA11.Alarm.MCmd_Disable,433252.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA11.Alarm.OCmd_Shelve,433252.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA11.Alarm.OCmd_Unshelve,433252.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA11.Alarm.SCmd_Suppress,433252.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA11.Alarm.SCmd_UnSuppress,433253.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA11.Alarm.AEShelveTMRDN,433253.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA11.Alarm.Bad,433253.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA11.Alarm.Suppress,433254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.UnSuppress,433254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Shelve,433254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.UnShelve,433254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Enable,433254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Disable,433254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Ack,433254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Reset,433254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA11.Alarm.Suppressed,433254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA11.Alarm.Shelved,433254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA11.Alarm.Disabled,433254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA11.Alarm.Acked,433254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA11.Alarm.Alarm,433254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Fault,433264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA11.almPLCFault.AlarmState,433264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA11.almPLCFault.GlobalReset,433264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA11.almPLCFault.FaultInAlarm,433264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA11.almPLCFault.ALRM,433264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA11.almPLCFault.ANUN,433264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA11.almPLCFault.AKED,433264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA11.almPLCFault.Resetable,433264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA11.almPLCFault.REST,433264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA11.almPLCFault.ACKN,433264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA11.almPLCFault.UACK,433264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA11.almPLCFault.MCmd_Enable,433264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA11.almPLCFault.MCmd_Disable,433264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA11.almPLCFault.OCmd_Shelve,433264.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA11.almPLCFault.OCmd_Unshelve,433264.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA11.almPLCFault.SCmd_Suppress,433264.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA11.almPLCFault.SCmd_UnSuppress,433265.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA11.almPLCFault.AEShelveTMRDN,433265.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA11.almPLCFault.Bad,433265.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA11.almPLCFault.Suppress,433266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.UnSuppress,433266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Shelve,433266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.UnShelve,433266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Enable,433266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Disable,433266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Ack,433266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Reset,433266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Suppressed,433266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Shelved,433266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Disabled,433266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Acked,433266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA11.almPLCFault.Alarm,433266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Fault,433286.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA12.Alarm.AlarmState,433286.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA12.Alarm.GlobalReset,433286.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA12.Alarm.FaultInAlarm,433286.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA12.Alarm.ALRM,433286.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA12.Alarm.ANUN,433286.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA12.Alarm.AKED,433286.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA12.Alarm.Resetable,433286.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA12.Alarm.REST,433286.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA12.Alarm.ACKN,433286.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA12.Alarm.UACK,433286.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA12.Alarm.MCmd_Enable,433286.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA12.Alarm.MCmd_Disable,433286.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA12.Alarm.OCmd_Shelve,433286.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA12.Alarm.OCmd_Unshelve,433286.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA12.Alarm.SCmd_Suppress,433286.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA12.Alarm.SCmd_UnSuppress,433287.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA12.Alarm.AEShelveTMRDN,433287.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA12.Alarm.Bad,433287.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA12.Alarm.Suppress,433288.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.UnSuppress,433288.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Shelve,433288.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.UnShelve,433288.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Enable,433288.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Disable,433288.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Ack,433288.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Reset,433288.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA12.Alarm.Suppressed,433288.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA12.Alarm.Shelved,433288.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA12.Alarm.Disabled,433288.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA12.Alarm.Acked,433288.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA12.Alarm.Alarm,433288.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Fault,433298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_HCP_001_1_XA12.almPLCFault.AlarmState,433298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_HCP_001_1_XA12.almPLCFault.GlobalReset,433298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_HCP_001_1_XA12.almPLCFault.FaultInAlarm,433298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_HCP_001_1_XA12.almPLCFault.ALRM,433298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_HCP_001_1_XA12.almPLCFault.ANUN,433298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_HCP_001_1_XA12.almPLCFault.AKED,433298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_HCP_001_1_XA12.almPLCFault.Resetable,433298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_HCP_001_1_XA12.almPLCFault.REST,433298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_HCP_001_1_XA12.almPLCFault.ACKN,433298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_HCP_001_1_XA12.almPLCFault.UACK,433298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_HCP_001_1_XA12.almPLCFault.MCmd_Enable,433298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_HCP_001_1_XA12.almPLCFault.MCmd_Disable,433298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_HCP_001_1_XA12.almPLCFault.OCmd_Shelve,433298.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_HCP_001_1_XA12.almPLCFault.OCmd_Unshelve,433298.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_HCP_001_1_XA12.almPLCFault.SCmd_Suppress,433298.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_HCP_001_1_XA12.almPLCFault.SCmd_UnSuppress,433299.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_HCP_001_1_XA12.almPLCFault.AEShelveTMRDN,433299.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_HCP_001_1_XA12.almPLCFault.Bad,433299.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_HCP_001_1_XA12.almPLCFault.Suppress,433300.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.UnSuppress,433300.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Shelve,433300.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.UnShelve,433300.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Enable,433300.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Disable,433300.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Ack,433300.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Reset,433300.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Suppressed,433300.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Shelved,433300.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Disabled,433300.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Acked,433300.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_HCP_001_1_XA12.almPLCFault.Alarm,433300.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Fault,433322.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_LSH_0113_1_LH.Alarm.AlarmState,433322.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_LSH_0113_1_LH.Alarm.GlobalReset,433322.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_LSH_0113_1_LH.Alarm.FaultInAlarm,433322.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_1_LH.Alarm.ALRM,433322.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_LSH_0113_1_LH.Alarm.ANUN,433322.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_LSH_0113_1_LH.Alarm.AKED,433322.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_LSH_0113_1_LH.Alarm.Resetable,433322.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_LSH_0113_1_LH.Alarm.REST,433322.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_LSH_0113_1_LH.Alarm.ACKN,433322.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_LSH_0113_1_LH.Alarm.UACK,433322.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_LSH_0113_1_LH.Alarm.MCmd_Enable,433322.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_1_LH.Alarm.MCmd_Disable,433322.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_1_LH.Alarm.OCmd_Shelve,433322.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_LSH_0113_1_LH.Alarm.OCmd_Unshelve,433322.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_LSH_0113_1_LH.Alarm.SCmd_Suppress,433322.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_LSH_0113_1_LH.Alarm.SCmd_UnSuppress,433323.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_LSH_0113_1_LH.Alarm.AEShelveTMRDN,433323.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_LSH_0113_1_LH.Alarm.Bad,433323.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_LSH_0113_1_LH.Alarm.Suppress,433324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.UnSuppress,433324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Shelve,433324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.UnShelve,433324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Enable,433324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Disable,433324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Ack,433324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Reset,433324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_LSH_0113_1_LH.Alarm.Suppressed,433324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_LSH_0113_1_LH.Alarm.Shelved,433324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_LSH_0113_1_LH.Alarm.Disabled,433324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_LSH_0113_1_LH.Alarm.Acked,433324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_LSH_0113_1_LH.Alarm.Alarm,433324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Fault,433334.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_LSH_0113_1_LH.almPLCFault.AlarmState,433334.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_LSH_0113_1_LH.almPLCFault.GlobalReset,433334.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_LSH_0113_1_LH.almPLCFault.FaultInAlarm,433334.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_1_LH.almPLCFault.ALRM,433334.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_LSH_0113_1_LH.almPLCFault.ANUN,433334.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_LSH_0113_1_LH.almPLCFault.AKED,433334.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_LSH_0113_1_LH.almPLCFault.Resetable,433334.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_LSH_0113_1_LH.almPLCFault.REST,433334.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_LSH_0113_1_LH.almPLCFault.ACKN,433334.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_LSH_0113_1_LH.almPLCFault.UACK,433334.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_LSH_0113_1_LH.almPLCFault.MCmd_Enable,433334.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_1_LH.almPLCFault.MCmd_Disable,433334.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_1_LH.almPLCFault.OCmd_Shelve,433334.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_LSH_0113_1_LH.almPLCFault.OCmd_Unshelve,433334.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_LSH_0113_1_LH.almPLCFault.SCmd_Suppress,433334.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_LSH_0113_1_LH.almPLCFault.SCmd_UnSuppress,433335.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_LSH_0113_1_LH.almPLCFault.AEShelveTMRDN,433335.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_LSH_0113_1_LH.almPLCFault.Bad,433335.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_LSH_0113_1_LH.almPLCFault.Suppress,433336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.UnSuppress,433336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Shelve,433336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.UnShelve,433336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Enable,433336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Disable,433336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Ack,433336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Reset,433336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Suppressed,433336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Shelved,433336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Disabled,433336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Acked,433336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_LSH_0113_1_LH.almPLCFault.Alarm,433336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Fault,433356.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_LSH_0113_2_LH.Alarm.AlarmState,433356.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_LSH_0113_2_LH.Alarm.GlobalReset,433356.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_LSH_0113_2_LH.Alarm.FaultInAlarm,433356.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_2_LH.Alarm.ALRM,433356.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_LSH_0113_2_LH.Alarm.ANUN,433356.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_LSH_0113_2_LH.Alarm.AKED,433356.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_LSH_0113_2_LH.Alarm.Resetable,433356.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_LSH_0113_2_LH.Alarm.REST,433356.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_LSH_0113_2_LH.Alarm.ACKN,433356.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_LSH_0113_2_LH.Alarm.UACK,433356.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_LSH_0113_2_LH.Alarm.MCmd_Enable,433356.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_2_LH.Alarm.MCmd_Disable,433356.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_2_LH.Alarm.OCmd_Shelve,433356.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_LSH_0113_2_LH.Alarm.OCmd_Unshelve,433356.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_LSH_0113_2_LH.Alarm.SCmd_Suppress,433356.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_LSH_0113_2_LH.Alarm.SCmd_UnSuppress,433357.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_LSH_0113_2_LH.Alarm.AEShelveTMRDN,433357.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_LSH_0113_2_LH.Alarm.Bad,433357.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_LSH_0113_2_LH.Alarm.Suppress,433358.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.UnSuppress,433358.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Shelve,433358.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.UnShelve,433358.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Enable,433358.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Disable,433358.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Ack,433358.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Reset,433358.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_LSH_0113_2_LH.Alarm.Suppressed,433358.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_LSH_0113_2_LH.Alarm.Shelved,433358.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_LSH_0113_2_LH.Alarm.Disabled,433358.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_LSH_0113_2_LH.Alarm.Acked,433358.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_LSH_0113_2_LH.Alarm.Alarm,433358.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Fault,433368.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_LSH_0113_2_LH.almPLCFault.AlarmState,433368.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_LSH_0113_2_LH.almPLCFault.GlobalReset,433368.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_LSH_0113_2_LH.almPLCFault.FaultInAlarm,433368.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_LSH_0113_2_LH.almPLCFault.ALRM,433368.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_LSH_0113_2_LH.almPLCFault.ANUN,433368.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_LSH_0113_2_LH.almPLCFault.AKED,433368.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_LSH_0113_2_LH.almPLCFault.Resetable,433368.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_LSH_0113_2_LH.almPLCFault.REST,433368.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_LSH_0113_2_LH.almPLCFault.ACKN,433368.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_LSH_0113_2_LH.almPLCFault.UACK,433368.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_LSH_0113_2_LH.almPLCFault.MCmd_Enable,433368.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_LSH_0113_2_LH.almPLCFault.MCmd_Disable,433368.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_LSH_0113_2_LH.almPLCFault.OCmd_Shelve,433368.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_LSH_0113_2_LH.almPLCFault.OCmd_Unshelve,433368.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_LSH_0113_2_LH.almPLCFault.SCmd_Suppress,433368.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_LSH_0113_2_LH.almPLCFault.SCmd_UnSuppress,433369.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_LSH_0113_2_LH.almPLCFault.AEShelveTMRDN,433369.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_LSH_0113_2_LH.almPLCFault.Bad,433369.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_LSH_0113_2_LH.almPLCFault.Suppress,433370.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.UnSuppress,433370.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Shelve,433370.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.UnShelve,433370.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Enable,433370.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Disable,433370.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Ack,433370.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Reset,433370.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Suppressed,433370.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Shelved,433370.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Disabled,433370.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Acked,433370.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_LSH_0113_2_LH.almPLCFault.Alarm,433370.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.Fault,433392.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_NET_001_1_JA.Alarm.AlarmState,433392.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_NET_001_1_JA.Alarm.GlobalReset,433392.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_NET_001_1_JA.Alarm.FaultInAlarm,433392.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_JA.Alarm.ALRM,433392.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_NET_001_1_JA.Alarm.ANUN,433392.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_NET_001_1_JA.Alarm.AKED,433392.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_NET_001_1_JA.Alarm.Resetable,433392.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_NET_001_1_JA.Alarm.REST,433392.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_NET_001_1_JA.Alarm.ACKN,433392.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_NET_001_1_JA.Alarm.UACK,433392.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_NET_001_1_JA.Alarm.MCmd_Enable,433392.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_JA.Alarm.MCmd_Disable,433392.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_JA.Alarm.OCmd_Shelve,433392.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_NET_001_1_JA.Alarm.OCmd_Unshelve,433392.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_NET_001_1_JA.Alarm.SCmd_Suppress,433392.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_NET_001_1_JA.Alarm.SCmd_UnSuppress,433393.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_NET_001_1_JA.Alarm.AEShelveTMRDN,433393.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_NET_001_1_JA.Alarm.Bad,433393.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_NET_001_1_JA.Alarm.Suppress,433394.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.UnSuppress,433394.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.Shelve,433394.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.UnShelve,433394.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.Enable,433394.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.Disable,433394.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_NET_001_1_JA.Alarm.Ack,433394.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_NET_001_1_JA.Alarm.Reset,433394.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_NET_001_1_JA.Alarm.Suppressed,433394.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_NET_001_1_JA.Alarm.Shelved,433394.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_NET_001_1_JA.Alarm.Disabled,433394.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_NET_001_1_JA.Alarm.Acked,433394.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_NET_001_1_JA.Alarm.Alarm,433394.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Fault,433404.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_NET_001_1_JA.almPLCFault.AlarmState,433404.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_NET_001_1_JA.almPLCFault.GlobalReset,433404.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_NET_001_1_JA.almPLCFault.FaultInAlarm,433404.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_JA.almPLCFault.ALRM,433404.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_NET_001_1_JA.almPLCFault.ANUN,433404.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_NET_001_1_JA.almPLCFault.AKED,433404.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_NET_001_1_JA.almPLCFault.Resetable,433404.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_NET_001_1_JA.almPLCFault.REST,433404.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_NET_001_1_JA.almPLCFault.ACKN,433404.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_NET_001_1_JA.almPLCFault.UACK,433404.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_NET_001_1_JA.almPLCFault.MCmd_Enable,433404.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_JA.almPLCFault.MCmd_Disable,433404.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_JA.almPLCFault.OCmd_Shelve,433404.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_NET_001_1_JA.almPLCFault.OCmd_Unshelve,433404.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_NET_001_1_JA.almPLCFault.SCmd_Suppress,433404.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_NET_001_1_JA.almPLCFault.SCmd_UnSuppress,433405.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_NET_001_1_JA.almPLCFault.AEShelveTMRDN,433405.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_NET_001_1_JA.almPLCFault.Bad,433405.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_NET_001_1_JA.almPLCFault.Suppress,433406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.UnSuppress,433406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Shelve,433406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.UnShelve,433406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Enable,433406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Disable,433406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Ack,433406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Reset,433406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_NET_001_1_JA.almPLCFault.Suppressed,433406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_NET_001_1_JA.almPLCFault.Shelved,433406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_NET_001_1_JA.almPLCFault.Disabled,433406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_NET_001_1_JA.almPLCFault.Acked,433406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_NET_001_1_JA.almPLCFault.Alarm,433406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Fault,433426.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_NET_001_1_ZS.Alarm.AlarmState,433426.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_NET_001_1_ZS.Alarm.GlobalReset,433426.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_NET_001_1_ZS.Alarm.FaultInAlarm,433426.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_ZS.Alarm.ALRM,433426.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_NET_001_1_ZS.Alarm.ANUN,433426.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_NET_001_1_ZS.Alarm.AKED,433426.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_NET_001_1_ZS.Alarm.Resetable,433426.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_NET_001_1_ZS.Alarm.REST,433426.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_NET_001_1_ZS.Alarm.ACKN,433426.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_NET_001_1_ZS.Alarm.UACK,433426.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_NET_001_1_ZS.Alarm.MCmd_Enable,433426.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_ZS.Alarm.MCmd_Disable,433426.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_ZS.Alarm.OCmd_Shelve,433426.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_NET_001_1_ZS.Alarm.OCmd_Unshelve,433426.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_NET_001_1_ZS.Alarm.SCmd_Suppress,433426.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_NET_001_1_ZS.Alarm.SCmd_UnSuppress,433427.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_NET_001_1_ZS.Alarm.AEShelveTMRDN,433427.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_NET_001_1_ZS.Alarm.Bad,433427.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_NET_001_1_ZS.Alarm.Suppress,433428.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.UnSuppress,433428.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Shelve,433428.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.UnShelve,433428.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Enable,433428.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Disable,433428.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Ack,433428.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Reset,433428.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_NET_001_1_ZS.Alarm.Suppressed,433428.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_NET_001_1_ZS.Alarm.Shelved,433428.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_NET_001_1_ZS.Alarm.Disabled,433428.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_NET_001_1_ZS.Alarm.Acked,433428.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_NET_001_1_ZS.Alarm.Alarm,433428.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Fault,433438.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_NET_001_1_ZS.almPLCFault.AlarmState,433438.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_NET_001_1_ZS.almPLCFault.GlobalReset,433438.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_NET_001_1_ZS.almPLCFault.FaultInAlarm,433438.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_NET_001_1_ZS.almPLCFault.ALRM,433438.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_NET_001_1_ZS.almPLCFault.ANUN,433438.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_NET_001_1_ZS.almPLCFault.AKED,433438.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_NET_001_1_ZS.almPLCFault.Resetable,433438.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_NET_001_1_ZS.almPLCFault.REST,433438.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_NET_001_1_ZS.almPLCFault.ACKN,433438.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_NET_001_1_ZS.almPLCFault.UACK,433438.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_NET_001_1_ZS.almPLCFault.MCmd_Enable,433438.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_NET_001_1_ZS.almPLCFault.MCmd_Disable,433438.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_NET_001_1_ZS.almPLCFault.OCmd_Shelve,433438.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_NET_001_1_ZS.almPLCFault.OCmd_Unshelve,433438.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_NET_001_1_ZS.almPLCFault.SCmd_Suppress,433438.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_NET_001_1_ZS.almPLCFault.SCmd_UnSuppress,433439.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_NET_001_1_ZS.almPLCFault.AEShelveTMRDN,433439.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_NET_001_1_ZS.almPLCFault.Bad,433439.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_NET_001_1_ZS.almPLCFault.Suppress,433440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.UnSuppress,433440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Shelve,433440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.UnShelve,433440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Enable,433440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Disable,433440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Ack,433440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Reset,433440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_NET_001_1_ZS.almPLCFault.Suppressed,433440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_NET_001_1_ZS.almPLCFault.Shelved,433440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_NET_001_1_ZS.almPLCFault.Disabled,433440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_NET_001_1_ZS.almPLCFault.Acked,433440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_NET_001_1_ZS.almPLCFault.Alarm,433440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Fault,433462.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PFC_0112_INHIBIT.Alarm.AlarmState,433462.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PFC_0112_INHIBIT.Alarm.GlobalReset,433462.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PFC_0112_INHIBIT.Alarm.FaultInAlarm,433462.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PFC_0112_INHIBIT.Alarm.ALRM,433462.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PFC_0112_INHIBIT.Alarm.ANUN,433462.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PFC_0112_INHIBIT.Alarm.AKED,433462.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PFC_0112_INHIBIT.Alarm.Resetable,433462.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PFC_0112_INHIBIT.Alarm.REST,433462.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PFC_0112_INHIBIT.Alarm.ACKN,433462.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PFC_0112_INHIBIT.Alarm.UACK,433462.10,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PFC_0112_INHIBIT.Alarm.MCmd_Enable,433462.11,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PFC_0112_INHIBIT.Alarm.MCmd_Disable,433462.12,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PFC_0112_INHIBIT.Alarm.OCmd_Shelve,433462.13,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PFC_0112_INHIBIT.Alarm.OCmd_Unshelve,433462.14,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PFC_0112_INHIBIT.Alarm.SCmd_Suppress,433462.15,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PFC_0112_INHIBIT.Alarm.SCmd_UnSuppress,433463.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PFC_0112_INHIBIT.Alarm.AEShelveTMRDN,433463.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PFC_0112_INHIBIT.Alarm.Bad,433463.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PFC_0112_INHIBIT.Alarm.Suppress,433464.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.UnSuppress,433464.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Shelve,433464.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.UnShelve,433464.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Enable,433464.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Disable,433464.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Ack,433464.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Reset,433464.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Suppressed,433464.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Shelved,433464.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Disabled,433464.10,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Acked,433464.11,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PFC_0112_INHIBIT.Alarm.Alarm,433464.12,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Fault,433474.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PFC_0112_INHIBIT.almPLCFault.AlarmState,433474.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PFC_0112_INHIBIT.almPLCFault.GlobalReset,433474.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PFC_0112_INHIBIT.almPLCFault.FaultInAlarm,433474.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PFC_0112_INHIBIT.almPLCFault.ALRM,433474.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PFC_0112_INHIBIT.almPLCFault.ANUN,433474.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PFC_0112_INHIBIT.almPLCFault.AKED,433474.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PFC_0112_INHIBIT.almPLCFault.Resetable,433474.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PFC_0112_INHIBIT.almPLCFault.REST,433474.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PFC_0112_INHIBIT.almPLCFault.ACKN,433474.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PFC_0112_INHIBIT.almPLCFault.UACK,433474.10,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PFC_0112_INHIBIT.almPLCFault.MCmd_Enable,433474.11,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.MCmd_Disable,433474.12,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.OCmd_Shelve,433474.13,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.OCmd_Unshelve,433474.14,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.SCmd_Suppress,433474.15,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.SCmd_UnSuppress,433475.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PFC_0112_INHIBIT.almPLCFault.AEShelveTMRDN,433475.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PFC_0112_INHIBIT.almPLCFault.Bad,433475.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PFC_0112_INHIBIT.almPLCFault.Suppress,433476.00,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.UnSuppress,433476.01,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Shelve,433476.02,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.UnShelve,433476.03,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Enable,433476.04,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Disable,433476.05,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Ack,433476.06,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Reset,433476.07,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Suppressed,433476.08,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Shelved,433476.09,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Disabled,433476.10,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Acked,433476.11,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PFC_0112_INHIBIT.almPLCFault.Alarm,433476.12,Boolean,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Fault,433496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PL.Alarm.AlarmState,433496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PL.Alarm.GlobalReset,433496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PL.Alarm.FaultInAlarm,433496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PL.Alarm.ALRM,433496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PL.Alarm.ANUN,433496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PL.Alarm.AKED,433496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PL.Alarm.Resetable,433496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PL.Alarm.REST,433496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PL.Alarm.ACKN,433496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PL.Alarm.UACK,433496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PL.Alarm.MCmd_Enable,433496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PL.Alarm.MCmd_Disable,433496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PL.Alarm.OCmd_Shelve,433496.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PL.Alarm.OCmd_Unshelve,433496.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PL.Alarm.SCmd_Suppress,433496.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PL.Alarm.SCmd_UnSuppress,433497.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PL.Alarm.AEShelveTMRDN,433497.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PL.Alarm.Bad,433497.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PL.Alarm.Suppress,433498.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.UnSuppress,433498.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Shelve,433498.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.UnShelve,433498.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Enable,433498.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Disable,433498.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Ack,433498.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Reset,433498.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PL.Alarm.Suppressed,433498.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PL.Alarm.Shelved,433498.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PL.Alarm.Disabled,433498.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PL.Alarm.Acked,433498.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PL.Alarm.Alarm,433498.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Fault,433508.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_1_PL.almPLCFault.AlarmState,433508.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_1_PL.almPLCFault.GlobalReset,433508.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_1_PL.almPLCFault.FaultInAlarm,433508.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_1_PL.almPLCFault.ALRM,433508.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_1_PL.almPLCFault.ANUN,433508.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_1_PL.almPLCFault.AKED,433508.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_1_PL.almPLCFault.Resetable,433508.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_1_PL.almPLCFault.REST,433508.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_1_PL.almPLCFault.ACKN,433508.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_1_PL.almPLCFault.UACK,433508.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_1_PL.almPLCFault.MCmd_Enable,433508.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_1_PL.almPLCFault.MCmd_Disable,433508.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_1_PL.almPLCFault.OCmd_Shelve,433508.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_1_PL.almPLCFault.OCmd_Unshelve,433508.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_1_PL.almPLCFault.SCmd_Suppress,433508.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_1_PL.almPLCFault.SCmd_UnSuppress,433509.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_1_PL.almPLCFault.AEShelveTMRDN,433509.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_1_PL.almPLCFault.Bad,433509.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_1_PL.almPLCFault.Suppress,433510.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.UnSuppress,433510.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Shelve,433510.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.UnShelve,433510.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Enable,433510.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Disable,433510.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Ack,433510.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Reset,433510.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Suppressed,433510.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Shelved,433510.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Disabled,433510.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Acked,433510.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_1_PL.almPLCFault.Alarm,433510.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Fault,433532.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PL.Alarm.AlarmState,433532.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PL.Alarm.GlobalReset,433532.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PL.Alarm.FaultInAlarm,433532.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PL.Alarm.ALRM,433532.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PL.Alarm.ANUN,433532.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PL.Alarm.AKED,433532.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PL.Alarm.Resetable,433532.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PL.Alarm.REST,433532.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PL.Alarm.ACKN,433532.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PL.Alarm.UACK,433532.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PL.Alarm.MCmd_Enable,433532.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PL.Alarm.MCmd_Disable,433532.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PL.Alarm.OCmd_Shelve,433532.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PL.Alarm.OCmd_Unshelve,433532.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PL.Alarm.SCmd_Suppress,433532.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PL.Alarm.SCmd_UnSuppress,433533.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PL.Alarm.AEShelveTMRDN,433533.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PL.Alarm.Bad,433533.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PL.Alarm.Suppress,433534.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.UnSuppress,433534.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Shelve,433534.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.UnShelve,433534.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Enable,433534.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Disable,433534.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Ack,433534.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Reset,433534.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PL.Alarm.Suppressed,433534.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PL.Alarm.Shelved,433534.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PL.Alarm.Disabled,433534.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PL.Alarm.Acked,433534.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PL.Alarm.Alarm,433534.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Fault,433544.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PIT_0102_2_PL.almPLCFault.AlarmState,433544.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PIT_0102_2_PL.almPLCFault.GlobalReset,433544.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PIT_0102_2_PL.almPLCFault.FaultInAlarm,433544.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PIT_0102_2_PL.almPLCFault.ALRM,433544.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PIT_0102_2_PL.almPLCFault.ANUN,433544.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PIT_0102_2_PL.almPLCFault.AKED,433544.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PIT_0102_2_PL.almPLCFault.Resetable,433544.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PIT_0102_2_PL.almPLCFault.REST,433544.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PIT_0102_2_PL.almPLCFault.ACKN,433544.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PIT_0102_2_PL.almPLCFault.UACK,433544.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PIT_0102_2_PL.almPLCFault.MCmd_Enable,433544.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PIT_0102_2_PL.almPLCFault.MCmd_Disable,433544.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PIT_0102_2_PL.almPLCFault.OCmd_Shelve,433544.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PIT_0102_2_PL.almPLCFault.OCmd_Unshelve,433544.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PIT_0102_2_PL.almPLCFault.SCmd_Suppress,433544.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PIT_0102_2_PL.almPLCFault.SCmd_UnSuppress,433545.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PIT_0102_2_PL.almPLCFault.AEShelveTMRDN,433545.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PIT_0102_2_PL.almPLCFault.Bad,433545.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PIT_0102_2_PL.almPLCFault.Suppress,433546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.UnSuppress,433546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Shelve,433546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.UnShelve,433546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Enable,433546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Disable,433546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Ack,433546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Reset,433546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Suppressed,433546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Shelved,433546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Disabled,433546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Acked,433546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PIT_0102_2_PL.almPLCFault.Alarm,433546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Fault,433566.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PLC_001_1_JA.Alarm.AlarmState,433566.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PLC_001_1_JA.Alarm.GlobalReset,433566.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PLC_001_1_JA.Alarm.FaultInAlarm,433566.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_JA.Alarm.ALRM,433566.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PLC_001_1_JA.Alarm.ANUN,433566.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PLC_001_1_JA.Alarm.AKED,433566.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PLC_001_1_JA.Alarm.Resetable,433566.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PLC_001_1_JA.Alarm.REST,433566.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PLC_001_1_JA.Alarm.ACKN,433566.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PLC_001_1_JA.Alarm.UACK,433566.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PLC_001_1_JA.Alarm.MCmd_Enable,433566.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_JA.Alarm.MCmd_Disable,433566.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_JA.Alarm.OCmd_Shelve,433566.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PLC_001_1_JA.Alarm.OCmd_Unshelve,433566.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PLC_001_1_JA.Alarm.SCmd_Suppress,433566.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PLC_001_1_JA.Alarm.SCmd_UnSuppress,433567.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PLC_001_1_JA.Alarm.AEShelveTMRDN,433567.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PLC_001_1_JA.Alarm.Bad,433567.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PLC_001_1_JA.Alarm.Suppress,433568.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.UnSuppress,433568.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Shelve,433568.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.UnShelve,433568.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Enable,433568.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Disable,433568.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Ack,433568.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Reset,433568.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PLC_001_1_JA.Alarm.Suppressed,433568.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PLC_001_1_JA.Alarm.Shelved,433568.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PLC_001_1_JA.Alarm.Disabled,433568.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PLC_001_1_JA.Alarm.Acked,433568.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PLC_001_1_JA.Alarm.Alarm,433568.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Fault,433578.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PLC_001_1_JA.almPLCFault.AlarmState,433578.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PLC_001_1_JA.almPLCFault.GlobalReset,433578.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PLC_001_1_JA.almPLCFault.FaultInAlarm,433578.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_JA.almPLCFault.ALRM,433578.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PLC_001_1_JA.almPLCFault.ANUN,433578.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PLC_001_1_JA.almPLCFault.AKED,433578.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PLC_001_1_JA.almPLCFault.Resetable,433578.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PLC_001_1_JA.almPLCFault.REST,433578.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PLC_001_1_JA.almPLCFault.ACKN,433578.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PLC_001_1_JA.almPLCFault.UACK,433578.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PLC_001_1_JA.almPLCFault.MCmd_Enable,433578.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_JA.almPLCFault.MCmd_Disable,433578.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_JA.almPLCFault.OCmd_Shelve,433578.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PLC_001_1_JA.almPLCFault.OCmd_Unshelve,433578.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PLC_001_1_JA.almPLCFault.SCmd_Suppress,433578.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PLC_001_1_JA.almPLCFault.SCmd_UnSuppress,433579.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PLC_001_1_JA.almPLCFault.AEShelveTMRDN,433579.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PLC_001_1_JA.almPLCFault.Bad,433579.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PLC_001_1_JA.almPLCFault.Suppress,433580.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.UnSuppress,433580.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Shelve,433580.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.UnShelve,433580.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Enable,433580.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Disable,433580.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Ack,433580.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Reset,433580.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PLC_001_1_JA.almPLCFault.Suppressed,433580.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PLC_001_1_JA.almPLCFault.Shelved,433580.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PLC_001_1_JA.almPLCFault.Disabled,433580.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PLC_001_1_JA.almPLCFault.Acked,433580.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PLC_001_1_JA.almPLCFault.Alarm,433580.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Fault,433602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PLC_001_1_ZS.Alarm.AlarmState,433602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PLC_001_1_ZS.Alarm.GlobalReset,433602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PLC_001_1_ZS.Alarm.FaultInAlarm,433602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_ZS.Alarm.ALRM,433602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PLC_001_1_ZS.Alarm.ANUN,433602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PLC_001_1_ZS.Alarm.AKED,433602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PLC_001_1_ZS.Alarm.Resetable,433602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PLC_001_1_ZS.Alarm.REST,433602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PLC_001_1_ZS.Alarm.ACKN,433602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PLC_001_1_ZS.Alarm.UACK,433602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PLC_001_1_ZS.Alarm.MCmd_Enable,433602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_ZS.Alarm.MCmd_Disable,433602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_ZS.Alarm.OCmd_Shelve,433602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PLC_001_1_ZS.Alarm.OCmd_Unshelve,433602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PLC_001_1_ZS.Alarm.SCmd_Suppress,433602.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PLC_001_1_ZS.Alarm.SCmd_UnSuppress,433603.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PLC_001_1_ZS.Alarm.AEShelveTMRDN,433603.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PLC_001_1_ZS.Alarm.Bad,433603.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PLC_001_1_ZS.Alarm.Suppress,433604.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.UnSuppress,433604.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Shelve,433604.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.UnShelve,433604.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Enable,433604.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Disable,433604.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Ack,433604.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Reset,433604.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PLC_001_1_ZS.Alarm.Suppressed,433604.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PLC_001_1_ZS.Alarm.Shelved,433604.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PLC_001_1_ZS.Alarm.Disabled,433604.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PLC_001_1_ZS.Alarm.Acked,433604.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PLC_001_1_ZS.Alarm.Alarm,433604.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Fault,433614.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PLC_001_1_ZS.almPLCFault.AlarmState,433614.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PLC_001_1_ZS.almPLCFault.GlobalReset,433614.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PLC_001_1_ZS.almPLCFault.FaultInAlarm,433614.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PLC_001_1_ZS.almPLCFault.ALRM,433614.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PLC_001_1_ZS.almPLCFault.ANUN,433614.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PLC_001_1_ZS.almPLCFault.AKED,433614.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PLC_001_1_ZS.almPLCFault.Resetable,433614.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PLC_001_1_ZS.almPLCFault.REST,433614.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PLC_001_1_ZS.almPLCFault.ACKN,433614.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PLC_001_1_ZS.almPLCFault.UACK,433614.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PLC_001_1_ZS.almPLCFault.MCmd_Enable,433614.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PLC_001_1_ZS.almPLCFault.MCmd_Disable,433614.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PLC_001_1_ZS.almPLCFault.OCmd_Shelve,433614.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PLC_001_1_ZS.almPLCFault.OCmd_Unshelve,433614.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PLC_001_1_ZS.almPLCFault.SCmd_Suppress,433614.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PLC_001_1_ZS.almPLCFault.SCmd_UnSuppress,433615.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PLC_001_1_ZS.almPLCFault.AEShelveTMRDN,433615.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PLC_001_1_ZS.almPLCFault.Bad,433615.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PLC_001_1_ZS.almPLCFault.Suppress,433616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.UnSuppress,433616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Shelve,433616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.UnShelve,433616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Enable,433616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Disable,433616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Ack,433616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Reset,433616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Suppressed,433616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Shelved,433616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Disabled,433616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Acked,433616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PLC_001_1_ZS.almPLCFault.Alarm,433616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Fault,433636.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_1_PL.Alarm.AlarmState,433636.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_1_PL.Alarm.GlobalReset,433636.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_1_PL.Alarm.FaultInAlarm,433636.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_1_PL.Alarm.ALRM,433636.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_1_PL.Alarm.ANUN,433636.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_1_PL.Alarm.AKED,433636.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_1_PL.Alarm.Resetable,433636.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_1_PL.Alarm.REST,433636.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_1_PL.Alarm.ACKN,433636.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_1_PL.Alarm.UACK,433636.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_1_PL.Alarm.MCmd_Enable,433636.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_1_PL.Alarm.MCmd_Disable,433636.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_1_PL.Alarm.OCmd_Shelve,433636.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_1_PL.Alarm.OCmd_Unshelve,433636.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_1_PL.Alarm.SCmd_Suppress,433636.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_1_PL.Alarm.SCmd_UnSuppress,433637.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_1_PL.Alarm.AEShelveTMRDN,433637.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_1_PL.Alarm.Bad,433637.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_1_PL.Alarm.Suppress,433638.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.UnSuppress,433638.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Shelve,433638.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.UnShelve,433638.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Enable,433638.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Disable,433638.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Ack,433638.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Reset,433638.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_1_PL.Alarm.Suppressed,433638.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_1_PL.Alarm.Shelved,433638.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_1_PL.Alarm.Disabled,433638.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_1_PL.Alarm.Acked,433638.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_1_PL.Alarm.Alarm,433638.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Fault,433648.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_1_PL.almPLCFault.AlarmState,433648.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_1_PL.almPLCFault.GlobalReset,433648.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_1_PL.almPLCFault.FaultInAlarm,433648.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_1_PL.almPLCFault.ALRM,433648.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_1_PL.almPLCFault.ANUN,433648.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_1_PL.almPLCFault.AKED,433648.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_1_PL.almPLCFault.Resetable,433648.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_1_PL.almPLCFault.REST,433648.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_1_PL.almPLCFault.ACKN,433648.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_1_PL.almPLCFault.UACK,433648.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_1_PL.almPLCFault.MCmd_Enable,433648.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_1_PL.almPLCFault.MCmd_Disable,433648.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_1_PL.almPLCFault.OCmd_Shelve,433648.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_1_PL.almPLCFault.OCmd_Unshelve,433648.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_1_PL.almPLCFault.SCmd_Suppress,433648.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_1_PL.almPLCFault.SCmd_UnSuppress,433649.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_1_PL.almPLCFault.AEShelveTMRDN,433649.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_1_PL.almPLCFault.Bad,433649.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_1_PL.almPLCFault.Suppress,433650.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.UnSuppress,433650.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Shelve,433650.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.UnShelve,433650.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Enable,433650.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Disable,433650.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Ack,433650.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Reset,433650.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_1_PL.almPLCFault.Suppressed,433650.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_1_PL.almPLCFault.Shelved,433650.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_1_PL.almPLCFault.Disabled,433650.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_1_PL.almPLCFault.Acked,433650.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_1_PL.almPLCFault.Alarm,433650.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Fault,433672.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_2_PL.Alarm.AlarmState,433672.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_2_PL.Alarm.GlobalReset,433672.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_2_PL.Alarm.FaultInAlarm,433672.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_2_PL.Alarm.ALRM,433672.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_2_PL.Alarm.ANUN,433672.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_2_PL.Alarm.AKED,433672.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_2_PL.Alarm.Resetable,433672.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_2_PL.Alarm.REST,433672.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_2_PL.Alarm.ACKN,433672.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_2_PL.Alarm.UACK,433672.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_2_PL.Alarm.MCmd_Enable,433672.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_2_PL.Alarm.MCmd_Disable,433672.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_2_PL.Alarm.OCmd_Shelve,433672.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_2_PL.Alarm.OCmd_Unshelve,433672.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_2_PL.Alarm.SCmd_Suppress,433672.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_2_PL.Alarm.SCmd_UnSuppress,433673.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_2_PL.Alarm.AEShelveTMRDN,433673.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_2_PL.Alarm.Bad,433673.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_2_PL.Alarm.Suppress,433674.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.UnSuppress,433674.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Shelve,433674.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.UnShelve,433674.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Enable,433674.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Disable,433674.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Ack,433674.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Reset,433674.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_2_PL.Alarm.Suppressed,433674.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_2_PL.Alarm.Shelved,433674.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_2_PL.Alarm.Disabled,433674.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_2_PL.Alarm.Acked,433674.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_2_PL.Alarm.Alarm,433674.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Fault,433684.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_2_PL.almPLCFault.AlarmState,433684.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_2_PL.almPLCFault.GlobalReset,433684.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_2_PL.almPLCFault.FaultInAlarm,433684.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_2_PL.almPLCFault.ALRM,433684.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_2_PL.almPLCFault.ANUN,433684.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_2_PL.almPLCFault.AKED,433684.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_2_PL.almPLCFault.Resetable,433684.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_2_PL.almPLCFault.REST,433684.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_2_PL.almPLCFault.ACKN,433684.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_2_PL.almPLCFault.UACK,433684.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_2_PL.almPLCFault.MCmd_Enable,433684.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_2_PL.almPLCFault.MCmd_Disable,433684.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_2_PL.almPLCFault.OCmd_Shelve,433684.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_2_PL.almPLCFault.OCmd_Unshelve,433684.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_2_PL.almPLCFault.SCmd_Suppress,433684.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_2_PL.almPLCFault.SCmd_UnSuppress,433685.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_2_PL.almPLCFault.AEShelveTMRDN,433685.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_2_PL.almPLCFault.Bad,433685.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_2_PL.almPLCFault.Suppress,433686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.UnSuppress,433686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Shelve,433686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.UnShelve,433686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Enable,433686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Disable,433686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Ack,433686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Reset,433686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_2_PL.almPLCFault.Suppressed,433686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_2_PL.almPLCFault.Shelved,433686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_2_PL.almPLCFault.Disabled,433686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_2_PL.almPLCFault.Acked,433686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_2_PL.almPLCFault.Alarm,433686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Fault,433706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_3_PL.Alarm.AlarmState,433706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_3_PL.Alarm.GlobalReset,433706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_3_PL.Alarm.FaultInAlarm,433706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_3_PL.Alarm.ALRM,433706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_3_PL.Alarm.ANUN,433706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_3_PL.Alarm.AKED,433706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_3_PL.Alarm.Resetable,433706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_3_PL.Alarm.REST,433706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_3_PL.Alarm.ACKN,433706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_3_PL.Alarm.UACK,433706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_3_PL.Alarm.MCmd_Enable,433706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_3_PL.Alarm.MCmd_Disable,433706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_3_PL.Alarm.OCmd_Shelve,433706.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_3_PL.Alarm.OCmd_Unshelve,433706.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_3_PL.Alarm.SCmd_Suppress,433706.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_3_PL.Alarm.SCmd_UnSuppress,433707.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_3_PL.Alarm.AEShelveTMRDN,433707.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_3_PL.Alarm.Bad,433707.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_3_PL.Alarm.Suppress,433708.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.UnSuppress,433708.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Shelve,433708.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.UnShelve,433708.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Enable,433708.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Disable,433708.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Ack,433708.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Reset,433708.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_3_PL.Alarm.Suppressed,433708.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_3_PL.Alarm.Shelved,433708.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_3_PL.Alarm.Disabled,433708.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_3_PL.Alarm.Acked,433708.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_3_PL.Alarm.Alarm,433708.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Fault,433718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_3_PL.almPLCFault.AlarmState,433718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_3_PL.almPLCFault.GlobalReset,433718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_3_PL.almPLCFault.FaultInAlarm,433718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_3_PL.almPLCFault.ALRM,433718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_3_PL.almPLCFault.ANUN,433718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_3_PL.almPLCFault.AKED,433718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_3_PL.almPLCFault.Resetable,433718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_3_PL.almPLCFault.REST,433718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_3_PL.almPLCFault.ACKN,433718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_3_PL.almPLCFault.UACK,433718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_3_PL.almPLCFault.MCmd_Enable,433718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_3_PL.almPLCFault.MCmd_Disable,433718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_3_PL.almPLCFault.OCmd_Shelve,433718.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_3_PL.almPLCFault.OCmd_Unshelve,433718.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_3_PL.almPLCFault.SCmd_Suppress,433718.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_3_PL.almPLCFault.SCmd_UnSuppress,433719.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_3_PL.almPLCFault.AEShelveTMRDN,433719.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_3_PL.almPLCFault.Bad,433719.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_3_PL.almPLCFault.Suppress,433720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.UnSuppress,433720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Shelve,433720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.UnShelve,433720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Enable,433720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Disable,433720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Ack,433720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Reset,433720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_3_PL.almPLCFault.Suppressed,433720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_3_PL.almPLCFault.Shelved,433720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_3_PL.almPLCFault.Disabled,433720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_3_PL.almPLCFault.Acked,433720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_3_PL.almPLCFault.Alarm,433720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Fault,433742.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_4_PL.Alarm.AlarmState,433742.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_4_PL.Alarm.GlobalReset,433742.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_4_PL.Alarm.FaultInAlarm,433742.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_4_PL.Alarm.ALRM,433742.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_4_PL.Alarm.ANUN,433742.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_4_PL.Alarm.AKED,433742.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_4_PL.Alarm.Resetable,433742.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_4_PL.Alarm.REST,433742.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_4_PL.Alarm.ACKN,433742.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_4_PL.Alarm.UACK,433742.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_4_PL.Alarm.MCmd_Enable,433742.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_4_PL.Alarm.MCmd_Disable,433742.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_4_PL.Alarm.OCmd_Shelve,433742.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_4_PL.Alarm.OCmd_Unshelve,433742.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_4_PL.Alarm.SCmd_Suppress,433742.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_4_PL.Alarm.SCmd_UnSuppress,433743.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_4_PL.Alarm.AEShelveTMRDN,433743.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_4_PL.Alarm.Bad,433743.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_4_PL.Alarm.Suppress,433744.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.UnSuppress,433744.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Shelve,433744.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.UnShelve,433744.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Enable,433744.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Disable,433744.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Ack,433744.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Reset,433744.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_4_PL.Alarm.Suppressed,433744.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_4_PL.Alarm.Shelved,433744.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_4_PL.Alarm.Disabled,433744.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_4_PL.Alarm.Acked,433744.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_4_PL.Alarm.Alarm,433744.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Fault,433754.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_4_PL.almPLCFault.AlarmState,433754.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_4_PL.almPLCFault.GlobalReset,433754.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_4_PL.almPLCFault.FaultInAlarm,433754.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_4_PL.almPLCFault.ALRM,433754.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_4_PL.almPLCFault.ANUN,433754.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_4_PL.almPLCFault.AKED,433754.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_4_PL.almPLCFault.Resetable,433754.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_4_PL.almPLCFault.REST,433754.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_4_PL.almPLCFault.ACKN,433754.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_4_PL.almPLCFault.UACK,433754.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_4_PL.almPLCFault.MCmd_Enable,433754.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_4_PL.almPLCFault.MCmd_Disable,433754.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_4_PL.almPLCFault.OCmd_Shelve,433754.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_4_PL.almPLCFault.OCmd_Unshelve,433754.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_4_PL.almPLCFault.SCmd_Suppress,433754.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_4_PL.almPLCFault.SCmd_UnSuppress,433755.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_4_PL.almPLCFault.AEShelveTMRDN,433755.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_4_PL.almPLCFault.Bad,433755.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_4_PL.almPLCFault.Suppress,433756.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.UnSuppress,433756.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Shelve,433756.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.UnShelve,433756.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Enable,433756.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Disable,433756.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Ack,433756.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Reset,433756.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_4_PL.almPLCFault.Suppressed,433756.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_4_PL.almPLCFault.Shelved,433756.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_4_PL.almPLCFault.Disabled,433756.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_4_PL.almPLCFault.Acked,433756.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_4_PL.almPLCFault.Alarm,433756.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Fault,433776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_5_PL.Alarm.AlarmState,433776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_5_PL.Alarm.GlobalReset,433776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_5_PL.Alarm.FaultInAlarm,433776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_5_PL.Alarm.ALRM,433776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_5_PL.Alarm.ANUN,433776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_5_PL.Alarm.AKED,433776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_5_PL.Alarm.Resetable,433776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_5_PL.Alarm.REST,433776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_5_PL.Alarm.ACKN,433776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_5_PL.Alarm.UACK,433776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_5_PL.Alarm.MCmd_Enable,433776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_5_PL.Alarm.MCmd_Disable,433776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_5_PL.Alarm.OCmd_Shelve,433776.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_5_PL.Alarm.OCmd_Unshelve,433776.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_5_PL.Alarm.SCmd_Suppress,433776.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_5_PL.Alarm.SCmd_UnSuppress,433777.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_5_PL.Alarm.AEShelveTMRDN,433777.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_5_PL.Alarm.Bad,433777.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_5_PL.Alarm.Suppress,433778.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.UnSuppress,433778.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Shelve,433778.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.UnShelve,433778.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Enable,433778.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Disable,433778.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Ack,433778.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Reset,433778.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_5_PL.Alarm.Suppressed,433778.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_5_PL.Alarm.Shelved,433778.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_5_PL.Alarm.Disabled,433778.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_5_PL.Alarm.Acked,433778.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_5_PL.Alarm.Alarm,433778.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Fault,433788.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_5_PL.almPLCFault.AlarmState,433788.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_5_PL.almPLCFault.GlobalReset,433788.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_5_PL.almPLCFault.FaultInAlarm,433788.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_5_PL.almPLCFault.ALRM,433788.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_5_PL.almPLCFault.ANUN,433788.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_5_PL.almPLCFault.AKED,433788.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_5_PL.almPLCFault.Resetable,433788.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_5_PL.almPLCFault.REST,433788.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_5_PL.almPLCFault.ACKN,433788.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_5_PL.almPLCFault.UACK,433788.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_5_PL.almPLCFault.MCmd_Enable,433788.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_5_PL.almPLCFault.MCmd_Disable,433788.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_5_PL.almPLCFault.OCmd_Shelve,433788.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_5_PL.almPLCFault.OCmd_Unshelve,433788.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_5_PL.almPLCFault.SCmd_Suppress,433788.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_5_PL.almPLCFault.SCmd_UnSuppress,433789.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_5_PL.almPLCFault.AEShelveTMRDN,433789.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_5_PL.almPLCFault.Bad,433789.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_5_PL.almPLCFault.Suppress,433790.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.UnSuppress,433790.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Shelve,433790.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.UnShelve,433790.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Enable,433790.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Disable,433790.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Ack,433790.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Reset,433790.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_5_PL.almPLCFault.Suppressed,433790.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_5_PL.almPLCFault.Shelved,433790.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_5_PL.almPLCFault.Disabled,433790.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_5_PL.almPLCFault.Acked,433790.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_5_PL.almPLCFault.Alarm,433790.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Fault,433812.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_6_PL.Alarm.AlarmState,433812.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_6_PL.Alarm.GlobalReset,433812.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_6_PL.Alarm.FaultInAlarm,433812.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_6_PL.Alarm.ALRM,433812.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_6_PL.Alarm.ANUN,433812.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_6_PL.Alarm.AKED,433812.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_6_PL.Alarm.Resetable,433812.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_6_PL.Alarm.REST,433812.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_6_PL.Alarm.ACKN,433812.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_6_PL.Alarm.UACK,433812.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_6_PL.Alarm.MCmd_Enable,433812.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_6_PL.Alarm.MCmd_Disable,433812.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_6_PL.Alarm.OCmd_Shelve,433812.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_6_PL.Alarm.OCmd_Unshelve,433812.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_6_PL.Alarm.SCmd_Suppress,433812.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_6_PL.Alarm.SCmd_UnSuppress,433813.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_6_PL.Alarm.AEShelveTMRDN,433813.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_6_PL.Alarm.Bad,433813.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_6_PL.Alarm.Suppress,433814.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.UnSuppress,433814.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Shelve,433814.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.UnShelve,433814.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Enable,433814.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Disable,433814.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Ack,433814.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Reset,433814.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_6_PL.Alarm.Suppressed,433814.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_6_PL.Alarm.Shelved,433814.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_6_PL.Alarm.Disabled,433814.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_6_PL.Alarm.Acked,433814.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_6_PL.Alarm.Alarm,433814.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Fault,433824.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_6_PL.almPLCFault.AlarmState,433824.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_6_PL.almPLCFault.GlobalReset,433824.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_6_PL.almPLCFault.FaultInAlarm,433824.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_6_PL.almPLCFault.ALRM,433824.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_6_PL.almPLCFault.ANUN,433824.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_6_PL.almPLCFault.AKED,433824.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_6_PL.almPLCFault.Resetable,433824.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_6_PL.almPLCFault.REST,433824.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_6_PL.almPLCFault.ACKN,433824.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_6_PL.almPLCFault.UACK,433824.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_6_PL.almPLCFault.MCmd_Enable,433824.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_6_PL.almPLCFault.MCmd_Disable,433824.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_6_PL.almPLCFault.OCmd_Shelve,433824.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_6_PL.almPLCFault.OCmd_Unshelve,433824.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_6_PL.almPLCFault.SCmd_Suppress,433824.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_6_PL.almPLCFault.SCmd_UnSuppress,433825.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_6_PL.almPLCFault.AEShelveTMRDN,433825.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_6_PL.almPLCFault.Bad,433825.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_6_PL.almPLCFault.Suppress,433826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.UnSuppress,433826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Shelve,433826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.UnShelve,433826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Enable,433826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Disable,433826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Ack,433826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Reset,433826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_6_PL.almPLCFault.Suppressed,433826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_6_PL.almPLCFault.Shelved,433826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_6_PL.almPLCFault.Disabled,433826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_6_PL.almPLCFault.Acked,433826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_6_PL.almPLCFault.Alarm,433826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Fault,433846.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_7_PL.Alarm.AlarmState,433846.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_7_PL.Alarm.GlobalReset,433846.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_7_PL.Alarm.FaultInAlarm,433846.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_7_PL.Alarm.ALRM,433846.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_7_PL.Alarm.ANUN,433846.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_7_PL.Alarm.AKED,433846.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_7_PL.Alarm.Resetable,433846.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_7_PL.Alarm.REST,433846.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_7_PL.Alarm.ACKN,433846.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_7_PL.Alarm.UACK,433846.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_7_PL.Alarm.MCmd_Enable,433846.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_7_PL.Alarm.MCmd_Disable,433846.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_7_PL.Alarm.OCmd_Shelve,433846.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_7_PL.Alarm.OCmd_Unshelve,433846.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_7_PL.Alarm.SCmd_Suppress,433846.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_7_PL.Alarm.SCmd_UnSuppress,433847.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_7_PL.Alarm.AEShelveTMRDN,433847.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_7_PL.Alarm.Bad,433847.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_7_PL.Alarm.Suppress,433848.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.UnSuppress,433848.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Shelve,433848.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.UnShelve,433848.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Enable,433848.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Disable,433848.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Ack,433848.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Reset,433848.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_7_PL.Alarm.Suppressed,433848.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_7_PL.Alarm.Shelved,433848.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_7_PL.Alarm.Disabled,433848.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_7_PL.Alarm.Acked,433848.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_7_PL.Alarm.Alarm,433848.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Fault,433858.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_7_PL.almPLCFault.AlarmState,433858.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_7_PL.almPLCFault.GlobalReset,433858.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_7_PL.almPLCFault.FaultInAlarm,433858.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_7_PL.almPLCFault.ALRM,433858.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_7_PL.almPLCFault.ANUN,433858.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_7_PL.almPLCFault.AKED,433858.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_7_PL.almPLCFault.Resetable,433858.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_7_PL.almPLCFault.REST,433858.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_7_PL.almPLCFault.ACKN,433858.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_7_PL.almPLCFault.UACK,433858.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_7_PL.almPLCFault.MCmd_Enable,433858.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_7_PL.almPLCFault.MCmd_Disable,433858.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_7_PL.almPLCFault.OCmd_Shelve,433858.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_7_PL.almPLCFault.OCmd_Unshelve,433858.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_7_PL.almPLCFault.SCmd_Suppress,433858.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_7_PL.almPLCFault.SCmd_UnSuppress,433859.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_7_PL.almPLCFault.AEShelveTMRDN,433859.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_7_PL.almPLCFault.Bad,433859.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_7_PL.almPLCFault.Suppress,433860.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.UnSuppress,433860.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Shelve,433860.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.UnShelve,433860.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Enable,433860.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Disable,433860.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Ack,433860.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Reset,433860.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_7_PL.almPLCFault.Suppressed,433860.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_7_PL.almPLCFault.Shelved,433860.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_7_PL.almPLCFault.Disabled,433860.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_7_PL.almPLCFault.Acked,433860.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_7_PL.almPLCFault.Alarm,433860.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Fault,433882.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_8_PL.Alarm.AlarmState,433882.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_8_PL.Alarm.GlobalReset,433882.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_8_PL.Alarm.FaultInAlarm,433882.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_8_PL.Alarm.ALRM,433882.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_8_PL.Alarm.ANUN,433882.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_8_PL.Alarm.AKED,433882.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_8_PL.Alarm.Resetable,433882.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_8_PL.Alarm.REST,433882.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_8_PL.Alarm.ACKN,433882.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_8_PL.Alarm.UACK,433882.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_8_PL.Alarm.MCmd_Enable,433882.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_8_PL.Alarm.MCmd_Disable,433882.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_8_PL.Alarm.OCmd_Shelve,433882.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_8_PL.Alarm.OCmd_Unshelve,433882.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_8_PL.Alarm.SCmd_Suppress,433882.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_8_PL.Alarm.SCmd_UnSuppress,433883.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_8_PL.Alarm.AEShelveTMRDN,433883.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_8_PL.Alarm.Bad,433883.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_8_PL.Alarm.Suppress,433884.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.UnSuppress,433884.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Shelve,433884.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.UnShelve,433884.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Enable,433884.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Disable,433884.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Ack,433884.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Reset,433884.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_8_PL.Alarm.Suppressed,433884.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_8_PL.Alarm.Shelved,433884.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_8_PL.Alarm.Disabled,433884.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_8_PL.Alarm.Acked,433884.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_8_PL.Alarm.Alarm,433884.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Fault,433894.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_8_PL.almPLCFault.AlarmState,433894.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_8_PL.almPLCFault.GlobalReset,433894.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_8_PL.almPLCFault.FaultInAlarm,433894.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_8_PL.almPLCFault.ALRM,433894.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_8_PL.almPLCFault.ANUN,433894.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_8_PL.almPLCFault.AKED,433894.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_8_PL.almPLCFault.Resetable,433894.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_8_PL.almPLCFault.REST,433894.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_8_PL.almPLCFault.ACKN,433894.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_8_PL.almPLCFault.UACK,433894.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_8_PL.almPLCFault.MCmd_Enable,433894.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_8_PL.almPLCFault.MCmd_Disable,433894.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_8_PL.almPLCFault.OCmd_Shelve,433894.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_8_PL.almPLCFault.OCmd_Unshelve,433894.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_8_PL.almPLCFault.SCmd_Suppress,433894.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_8_PL.almPLCFault.SCmd_UnSuppress,433895.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_8_PL.almPLCFault.AEShelveTMRDN,433895.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_8_PL.almPLCFault.Bad,433895.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_8_PL.almPLCFault.Suppress,433896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.UnSuppress,433896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Shelve,433896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.UnShelve,433896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Enable,433896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Disable,433896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Ack,433896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Reset,433896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_8_PL.almPLCFault.Suppressed,433896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_8_PL.almPLCFault.Shelved,433896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_8_PL.almPLCFault.Disabled,433896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_8_PL.almPLCFault.Acked,433896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_8_PL.almPLCFault.Alarm,433896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Fault,433916.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_9_PL.Alarm.AlarmState,433916.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_9_PL.Alarm.GlobalReset,433916.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_9_PL.Alarm.FaultInAlarm,433916.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_9_PL.Alarm.ALRM,433916.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_9_PL.Alarm.ANUN,433916.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_9_PL.Alarm.AKED,433916.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_9_PL.Alarm.Resetable,433916.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_9_PL.Alarm.REST,433916.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_9_PL.Alarm.ACKN,433916.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_9_PL.Alarm.UACK,433916.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_9_PL.Alarm.MCmd_Enable,433916.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_9_PL.Alarm.MCmd_Disable,433916.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_9_PL.Alarm.OCmd_Shelve,433916.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_9_PL.Alarm.OCmd_Unshelve,433916.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_9_PL.Alarm.SCmd_Suppress,433916.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_9_PL.Alarm.SCmd_UnSuppress,433917.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_9_PL.Alarm.AEShelveTMRDN,433917.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_9_PL.Alarm.Bad,433917.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_9_PL.Alarm.Suppress,433918.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.UnSuppress,433918.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Shelve,433918.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.UnShelve,433918.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Enable,433918.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Disable,433918.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Ack,433918.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Reset,433918.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_9_PL.Alarm.Suppressed,433918.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_9_PL.Alarm.Shelved,433918.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_9_PL.Alarm.Disabled,433918.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_9_PL.Alarm.Acked,433918.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_9_PL.Alarm.Alarm,433918.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Fault,433928.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_PS_0103_9_PL.almPLCFault.AlarmState,433928.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_PS_0103_9_PL.almPLCFault.GlobalReset,433928.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_PS_0103_9_PL.almPLCFault.FaultInAlarm,433928.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_PS_0103_9_PL.almPLCFault.ALRM,433928.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_PS_0103_9_PL.almPLCFault.ANUN,433928.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_PS_0103_9_PL.almPLCFault.AKED,433928.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_PS_0103_9_PL.almPLCFault.Resetable,433928.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_PS_0103_9_PL.almPLCFault.REST,433928.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_PS_0103_9_PL.almPLCFault.ACKN,433928.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_PS_0103_9_PL.almPLCFault.UACK,433928.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_PS_0103_9_PL.almPLCFault.MCmd_Enable,433928.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_PS_0103_9_PL.almPLCFault.MCmd_Disable,433928.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_PS_0103_9_PL.almPLCFault.OCmd_Shelve,433928.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_PS_0103_9_PL.almPLCFault.OCmd_Unshelve,433928.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_PS_0103_9_PL.almPLCFault.SCmd_Suppress,433928.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_PS_0103_9_PL.almPLCFault.SCmd_UnSuppress,433929.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_PS_0103_9_PL.almPLCFault.AEShelveTMRDN,433929.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_PS_0103_9_PL.almPLCFault.Bad,433929.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_PS_0103_9_PL.almPLCFault.Suppress,433930.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.UnSuppress,433930.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Shelve,433930.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.UnShelve,433930.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Enable,433930.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Disable,433930.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Ack,433930.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Reset,433930.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_PS_0103_9_PL.almPLCFault.Suppressed,433930.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_PS_0103_9_PL.almPLCFault.Shelved,433930.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_PS_0103_9_PL.almPLCFault.Disabled,433930.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_PS_0103_9_PL.almPLCFault.Acked,433930.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_PS_0103_9_PL.almPLCFault.Alarm,433930.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Fault,433952.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_1_XA.Alarm.AlarmState,433952.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_1_XA.Alarm.GlobalReset,433952.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_1_XA.Alarm.FaultInAlarm,433952.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_1_XA.Alarm.ALRM,433952.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_1_XA.Alarm.ANUN,433952.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_1_XA.Alarm.AKED,433952.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_1_XA.Alarm.Resetable,433952.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_1_XA.Alarm.REST,433952.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_1_XA.Alarm.ACKN,433952.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_1_XA.Alarm.UACK,433952.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_1_XA.Alarm.MCmd_Enable,433952.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_1_XA.Alarm.MCmd_Disable,433952.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_1_XA.Alarm.OCmd_Shelve,433952.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_1_XA.Alarm.OCmd_Unshelve,433952.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_1_XA.Alarm.SCmd_Suppress,433952.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_1_XA.Alarm.SCmd_UnSuppress,433953.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_1_XA.Alarm.AEShelveTMRDN,433953.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_1_XA.Alarm.Bad,433953.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_1_XA.Alarm.Suppress,433954.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.UnSuppress,433954.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Shelve,433954.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.UnShelve,433954.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Enable,433954.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Disable,433954.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Ack,433954.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Reset,433954.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_1_XA.Alarm.Suppressed,433954.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_1_XA.Alarm.Shelved,433954.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_1_XA.Alarm.Disabled,433954.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_1_XA.Alarm.Acked,433954.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_1_XA.Alarm.Alarm,433954.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Fault,433964.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_1_XA.almPLCFault.AlarmState,433964.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_1_XA.almPLCFault.GlobalReset,433964.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_1_XA.almPLCFault.FaultInAlarm,433964.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_1_XA.almPLCFault.ALRM,433964.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_1_XA.almPLCFault.ANUN,433964.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_1_XA.almPLCFault.AKED,433964.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_1_XA.almPLCFault.Resetable,433964.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_1_XA.almPLCFault.REST,433964.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_1_XA.almPLCFault.ACKN,433964.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_1_XA.almPLCFault.UACK,433964.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_1_XA.almPLCFault.MCmd_Enable,433964.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_1_XA.almPLCFault.MCmd_Disable,433964.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_1_XA.almPLCFault.OCmd_Shelve,433964.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_1_XA.almPLCFault.OCmd_Unshelve,433964.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_1_XA.almPLCFault.SCmd_Suppress,433964.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_1_XA.almPLCFault.SCmd_UnSuppress,433965.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_1_XA.almPLCFault.AEShelveTMRDN,433965.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_1_XA.almPLCFault.Bad,433965.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_1_XA.almPLCFault.Suppress,433966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.UnSuppress,433966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Shelve,433966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.UnShelve,433966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Enable,433966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Disable,433966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Ack,433966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Reset,433966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_1_XA.almPLCFault.Suppressed,433966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_1_XA.almPLCFault.Shelved,433966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_1_XA.almPLCFault.Disabled,433966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_1_XA.almPLCFault.Acked,433966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_1_XA.almPLCFault.Alarm,433966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Fault,433986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_2_XA.Alarm.AlarmState,433986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_2_XA.Alarm.GlobalReset,433986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_2_XA.Alarm.FaultInAlarm,433986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_2_XA.Alarm.ALRM,433986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_2_XA.Alarm.ANUN,433986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_2_XA.Alarm.AKED,433986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_2_XA.Alarm.Resetable,433986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_2_XA.Alarm.REST,433986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_2_XA.Alarm.ACKN,433986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_2_XA.Alarm.UACK,433986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_2_XA.Alarm.MCmd_Enable,433986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_2_XA.Alarm.MCmd_Disable,433986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_2_XA.Alarm.OCmd_Shelve,433986.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_2_XA.Alarm.OCmd_Unshelve,433986.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_2_XA.Alarm.SCmd_Suppress,433986.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_2_XA.Alarm.SCmd_UnSuppress,433987.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_2_XA.Alarm.AEShelveTMRDN,433987.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_2_XA.Alarm.Bad,433987.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_2_XA.Alarm.Suppress,433988.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.UnSuppress,433988.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Shelve,433988.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.UnShelve,433988.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Enable,433988.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Disable,433988.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Ack,433988.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Reset,433988.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_2_XA.Alarm.Suppressed,433988.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_2_XA.Alarm.Shelved,433988.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_2_XA.Alarm.Disabled,433988.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_2_XA.Alarm.Acked,433988.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_2_XA.Alarm.Alarm,433988.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Fault,433998.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_2_XA.almPLCFault.AlarmState,433998.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_2_XA.almPLCFault.GlobalReset,433998.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_2_XA.almPLCFault.FaultInAlarm,433998.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_2_XA.almPLCFault.ALRM,433998.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_2_XA.almPLCFault.ANUN,433998.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_2_XA.almPLCFault.AKED,433998.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_2_XA.almPLCFault.Resetable,433998.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_2_XA.almPLCFault.REST,433998.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_2_XA.almPLCFault.ACKN,433998.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_2_XA.almPLCFault.UACK,433998.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_2_XA.almPLCFault.MCmd_Enable,433998.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_2_XA.almPLCFault.MCmd_Disable,433998.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_2_XA.almPLCFault.OCmd_Shelve,433998.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_2_XA.almPLCFault.OCmd_Unshelve,433998.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_2_XA.almPLCFault.SCmd_Suppress,433998.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_2_XA.almPLCFault.SCmd_UnSuppress,433999.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_2_XA.almPLCFault.AEShelveTMRDN,433999.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_2_XA.almPLCFault.Bad,433999.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_2_XA.almPLCFault.Suppress,434000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.UnSuppress,434000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Shelve,434000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.UnShelve,434000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Enable,434000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Disable,434000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Ack,434000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Reset,434000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_2_XA.almPLCFault.Suppressed,434000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_2_XA.almPLCFault.Shelved,434000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_2_XA.almPLCFault.Disabled,434000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_2_XA.almPLCFault.Acked,434000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_2_XA.almPLCFault.Alarm,434000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Fault,434022.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_3_XA.Alarm.AlarmState,434022.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_3_XA.Alarm.GlobalReset,434022.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_3_XA.Alarm.FaultInAlarm,434022.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_3_XA.Alarm.ALRM,434022.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_3_XA.Alarm.ANUN,434022.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_3_XA.Alarm.AKED,434022.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_3_XA.Alarm.Resetable,434022.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_3_XA.Alarm.REST,434022.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_3_XA.Alarm.ACKN,434022.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_3_XA.Alarm.UACK,434022.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_3_XA.Alarm.MCmd_Enable,434022.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_3_XA.Alarm.MCmd_Disable,434022.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_3_XA.Alarm.OCmd_Shelve,434022.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_3_XA.Alarm.OCmd_Unshelve,434022.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_3_XA.Alarm.SCmd_Suppress,434022.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_3_XA.Alarm.SCmd_UnSuppress,434023.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_3_XA.Alarm.AEShelveTMRDN,434023.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_3_XA.Alarm.Bad,434023.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_3_XA.Alarm.Suppress,434024.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.UnSuppress,434024.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Shelve,434024.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.UnShelve,434024.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Enable,434024.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Disable,434024.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Ack,434024.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Reset,434024.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_3_XA.Alarm.Suppressed,434024.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_3_XA.Alarm.Shelved,434024.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_3_XA.Alarm.Disabled,434024.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_3_XA.Alarm.Acked,434024.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_3_XA.Alarm.Alarm,434024.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Fault,434034.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_3_XA.almPLCFault.AlarmState,434034.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_3_XA.almPLCFault.GlobalReset,434034.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_3_XA.almPLCFault.FaultInAlarm,434034.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_3_XA.almPLCFault.ALRM,434034.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_3_XA.almPLCFault.ANUN,434034.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_3_XA.almPLCFault.AKED,434034.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_3_XA.almPLCFault.Resetable,434034.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_3_XA.almPLCFault.REST,434034.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_3_XA.almPLCFault.ACKN,434034.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_3_XA.almPLCFault.UACK,434034.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_3_XA.almPLCFault.MCmd_Enable,434034.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_3_XA.almPLCFault.MCmd_Disable,434034.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_3_XA.almPLCFault.OCmd_Shelve,434034.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_3_XA.almPLCFault.OCmd_Unshelve,434034.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_3_XA.almPLCFault.SCmd_Suppress,434034.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_3_XA.almPLCFault.SCmd_UnSuppress,434035.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_3_XA.almPLCFault.AEShelveTMRDN,434035.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_3_XA.almPLCFault.Bad,434035.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_3_XA.almPLCFault.Suppress,434036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.UnSuppress,434036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Shelve,434036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.UnShelve,434036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Enable,434036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Disable,434036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Ack,434036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Reset,434036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_3_XA.almPLCFault.Suppressed,434036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_3_XA.almPLCFault.Shelved,434036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_3_XA.almPLCFault.Disabled,434036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_3_XA.almPLCFault.Acked,434036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_3_XA.almPLCFault.Alarm,434036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Fault,434056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_4_XA.Alarm.AlarmState,434056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_4_XA.Alarm.GlobalReset,434056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_4_XA.Alarm.FaultInAlarm,434056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_4_XA.Alarm.ALRM,434056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_4_XA.Alarm.ANUN,434056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_4_XA.Alarm.AKED,434056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_4_XA.Alarm.Resetable,434056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_4_XA.Alarm.REST,434056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_4_XA.Alarm.ACKN,434056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_4_XA.Alarm.UACK,434056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_4_XA.Alarm.MCmd_Enable,434056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_4_XA.Alarm.MCmd_Disable,434056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_4_XA.Alarm.OCmd_Shelve,434056.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_4_XA.Alarm.OCmd_Unshelve,434056.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_4_XA.Alarm.SCmd_Suppress,434056.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_4_XA.Alarm.SCmd_UnSuppress,434057.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_4_XA.Alarm.AEShelveTMRDN,434057.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_4_XA.Alarm.Bad,434057.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_4_XA.Alarm.Suppress,434058.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.UnSuppress,434058.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Shelve,434058.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.UnShelve,434058.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Enable,434058.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Disable,434058.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Ack,434058.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Reset,434058.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_4_XA.Alarm.Suppressed,434058.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_4_XA.Alarm.Shelved,434058.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_4_XA.Alarm.Disabled,434058.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_4_XA.Alarm.Acked,434058.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_4_XA.Alarm.Alarm,434058.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Fault,434068.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_REC_0131_4_XA.almPLCFault.AlarmState,434068.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_REC_0131_4_XA.almPLCFault.GlobalReset,434068.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_REC_0131_4_XA.almPLCFault.FaultInAlarm,434068.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_REC_0131_4_XA.almPLCFault.ALRM,434068.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_REC_0131_4_XA.almPLCFault.ANUN,434068.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_REC_0131_4_XA.almPLCFault.AKED,434068.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_REC_0131_4_XA.almPLCFault.Resetable,434068.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_REC_0131_4_XA.almPLCFault.REST,434068.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_REC_0131_4_XA.almPLCFault.ACKN,434068.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_REC_0131_4_XA.almPLCFault.UACK,434068.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_REC_0131_4_XA.almPLCFault.MCmd_Enable,434068.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_REC_0131_4_XA.almPLCFault.MCmd_Disable,434068.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_REC_0131_4_XA.almPLCFault.OCmd_Shelve,434068.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_REC_0131_4_XA.almPLCFault.OCmd_Unshelve,434068.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_REC_0131_4_XA.almPLCFault.SCmd_Suppress,434068.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_REC_0131_4_XA.almPLCFault.SCmd_UnSuppress,434069.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_REC_0131_4_XA.almPLCFault.AEShelveTMRDN,434069.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_REC_0131_4_XA.almPLCFault.Bad,434069.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_REC_0131_4_XA.almPLCFault.Suppress,434070.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.UnSuppress,434070.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Shelve,434070.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.UnShelve,434070.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Enable,434070.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Disable,434070.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Ack,434070.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Reset,434070.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_REC_0131_4_XA.almPLCFault.Suppressed,434070.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_REC_0131_4_XA.almPLCFault.Shelved,434070.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_REC_0131_4_XA.almPLCFault.Disabled,434070.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_REC_0131_4_XA.almPLCFault.Acked,434070.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_REC_0131_4_XA.almPLCFault.Alarm,434070.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Fault,434092.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0112_1_XA.Alarm.AlarmState,434092.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0112_1_XA.Alarm.GlobalReset,434092.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0112_1_XA.Alarm.FaultInAlarm,434092.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0112_1_XA.Alarm.ALRM,434092.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0112_1_XA.Alarm.ANUN,434092.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0112_1_XA.Alarm.AKED,434092.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0112_1_XA.Alarm.Resetable,434092.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0112_1_XA.Alarm.REST,434092.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0112_1_XA.Alarm.ACKN,434092.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0112_1_XA.Alarm.UACK,434092.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0112_1_XA.Alarm.MCmd_Enable,434092.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0112_1_XA.Alarm.MCmd_Disable,434092.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0112_1_XA.Alarm.OCmd_Shelve,434092.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0112_1_XA.Alarm.OCmd_Unshelve,434092.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0112_1_XA.Alarm.SCmd_Suppress,434092.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0112_1_XA.Alarm.SCmd_UnSuppress,434093.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0112_1_XA.Alarm.AEShelveTMRDN,434093.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0112_1_XA.Alarm.Bad,434093.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0112_1_XA.Alarm.Suppress,434094.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.UnSuppress,434094.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Shelve,434094.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.UnShelve,434094.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Enable,434094.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Disable,434094.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Ack,434094.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Reset,434094.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0112_1_XA.Alarm.Suppressed,434094.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0112_1_XA.Alarm.Shelved,434094.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0112_1_XA.Alarm.Disabled,434094.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0112_1_XA.Alarm.Acked,434094.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0112_1_XA.Alarm.Alarm,434094.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Fault,434104.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0112_1_XA.almPLCFault.AlarmState,434104.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0112_1_XA.almPLCFault.GlobalReset,434104.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0112_1_XA.almPLCFault.FaultInAlarm,434104.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0112_1_XA.almPLCFault.ALRM,434104.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0112_1_XA.almPLCFault.ANUN,434104.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0112_1_XA.almPLCFault.AKED,434104.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0112_1_XA.almPLCFault.Resetable,434104.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0112_1_XA.almPLCFault.REST,434104.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0112_1_XA.almPLCFault.ACKN,434104.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0112_1_XA.almPLCFault.UACK,434104.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0112_1_XA.almPLCFault.MCmd_Enable,434104.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0112_1_XA.almPLCFault.MCmd_Disable,434104.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0112_1_XA.almPLCFault.OCmd_Shelve,434104.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0112_1_XA.almPLCFault.OCmd_Unshelve,434104.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0112_1_XA.almPLCFault.SCmd_Suppress,434104.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0112_1_XA.almPLCFault.SCmd_UnSuppress,434105.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0112_1_XA.almPLCFault.AEShelveTMRDN,434105.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0112_1_XA.almPLCFault.Bad,434105.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0112_1_XA.almPLCFault.Suppress,434106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.UnSuppress,434106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Shelve,434106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.UnShelve,434106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Enable,434106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Disable,434106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Ack,434106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Reset,434106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0112_1_XA.almPLCFault.Suppressed,434106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0112_1_XA.almPLCFault.Shelved,434106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0112_1_XA.almPLCFault.Disabled,434106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0112_1_XA.almPLCFault.Acked,434106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0112_1_XA.almPLCFault.Alarm,434106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Fault,434126.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0113_1_XA.Alarm.AlarmState,434126.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0113_1_XA.Alarm.GlobalReset,434126.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0113_1_XA.Alarm.FaultInAlarm,434126.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_1_XA.Alarm.ALRM,434126.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0113_1_XA.Alarm.ANUN,434126.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0113_1_XA.Alarm.AKED,434126.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0113_1_XA.Alarm.Resetable,434126.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0113_1_XA.Alarm.REST,434126.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0113_1_XA.Alarm.ACKN,434126.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0113_1_XA.Alarm.UACK,434126.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0113_1_XA.Alarm.MCmd_Enable,434126.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_1_XA.Alarm.MCmd_Disable,434126.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_1_XA.Alarm.OCmd_Shelve,434126.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0113_1_XA.Alarm.OCmd_Unshelve,434126.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0113_1_XA.Alarm.SCmd_Suppress,434126.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0113_1_XA.Alarm.SCmd_UnSuppress,434127.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0113_1_XA.Alarm.AEShelveTMRDN,434127.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0113_1_XA.Alarm.Bad,434127.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0113_1_XA.Alarm.Suppress,434128.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.UnSuppress,434128.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Shelve,434128.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.UnShelve,434128.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Enable,434128.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Disable,434128.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Ack,434128.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Reset,434128.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0113_1_XA.Alarm.Suppressed,434128.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0113_1_XA.Alarm.Shelved,434128.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0113_1_XA.Alarm.Disabled,434128.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0113_1_XA.Alarm.Acked,434128.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0113_1_XA.Alarm.Alarm,434128.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Fault,434138.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0113_1_XA.almPLCFault.AlarmState,434138.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0113_1_XA.almPLCFault.GlobalReset,434138.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0113_1_XA.almPLCFault.FaultInAlarm,434138.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_1_XA.almPLCFault.ALRM,434138.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0113_1_XA.almPLCFault.ANUN,434138.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0113_1_XA.almPLCFault.AKED,434138.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0113_1_XA.almPLCFault.Resetable,434138.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0113_1_XA.almPLCFault.REST,434138.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0113_1_XA.almPLCFault.ACKN,434138.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0113_1_XA.almPLCFault.UACK,434138.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0113_1_XA.almPLCFault.MCmd_Enable,434138.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_1_XA.almPLCFault.MCmd_Disable,434138.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_1_XA.almPLCFault.OCmd_Shelve,434138.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0113_1_XA.almPLCFault.OCmd_Unshelve,434138.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0113_1_XA.almPLCFault.SCmd_Suppress,434138.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0113_1_XA.almPLCFault.SCmd_UnSuppress,434139.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0113_1_XA.almPLCFault.AEShelveTMRDN,434139.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0113_1_XA.almPLCFault.Bad,434139.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0113_1_XA.almPLCFault.Suppress,434140.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.UnSuppress,434140.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Shelve,434140.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.UnShelve,434140.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Enable,434140.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Disable,434140.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Ack,434140.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Reset,434140.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0113_1_XA.almPLCFault.Suppressed,434140.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0113_1_XA.almPLCFault.Shelved,434140.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0113_1_XA.almPLCFault.Disabled,434140.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0113_1_XA.almPLCFault.Acked,434140.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0113_1_XA.almPLCFault.Alarm,434140.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Fault,434162.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0113_2_XA.Alarm.AlarmState,434162.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0113_2_XA.Alarm.GlobalReset,434162.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0113_2_XA.Alarm.FaultInAlarm,434162.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_2_XA.Alarm.ALRM,434162.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0113_2_XA.Alarm.ANUN,434162.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0113_2_XA.Alarm.AKED,434162.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0113_2_XA.Alarm.Resetable,434162.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0113_2_XA.Alarm.REST,434162.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0113_2_XA.Alarm.ACKN,434162.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0113_2_XA.Alarm.UACK,434162.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0113_2_XA.Alarm.MCmd_Enable,434162.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_2_XA.Alarm.MCmd_Disable,434162.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_2_XA.Alarm.OCmd_Shelve,434162.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0113_2_XA.Alarm.OCmd_Unshelve,434162.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0113_2_XA.Alarm.SCmd_Suppress,434162.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0113_2_XA.Alarm.SCmd_UnSuppress,434163.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0113_2_XA.Alarm.AEShelveTMRDN,434163.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0113_2_XA.Alarm.Bad,434163.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0113_2_XA.Alarm.Suppress,434164.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.UnSuppress,434164.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Shelve,434164.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.UnShelve,434164.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Enable,434164.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Disable,434164.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Ack,434164.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Reset,434164.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0113_2_XA.Alarm.Suppressed,434164.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0113_2_XA.Alarm.Shelved,434164.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0113_2_XA.Alarm.Disabled,434164.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0113_2_XA.Alarm.Acked,434164.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0113_2_XA.Alarm.Alarm,434164.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Fault,434174.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0113_2_XA.almPLCFault.AlarmState,434174.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0113_2_XA.almPLCFault.GlobalReset,434174.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0113_2_XA.almPLCFault.FaultInAlarm,434174.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0113_2_XA.almPLCFault.ALRM,434174.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0113_2_XA.almPLCFault.ANUN,434174.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0113_2_XA.almPLCFault.AKED,434174.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0113_2_XA.almPLCFault.Resetable,434174.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0113_2_XA.almPLCFault.REST,434174.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0113_2_XA.almPLCFault.ACKN,434174.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0113_2_XA.almPLCFault.UACK,434174.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0113_2_XA.almPLCFault.MCmd_Enable,434174.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0113_2_XA.almPLCFault.MCmd_Disable,434174.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0113_2_XA.almPLCFault.OCmd_Shelve,434174.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0113_2_XA.almPLCFault.OCmd_Unshelve,434174.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0113_2_XA.almPLCFault.SCmd_Suppress,434174.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0113_2_XA.almPLCFault.SCmd_UnSuppress,434175.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0113_2_XA.almPLCFault.AEShelveTMRDN,434175.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0113_2_XA.almPLCFault.Bad,434175.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0113_2_XA.almPLCFault.Suppress,434176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.UnSuppress,434176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Shelve,434176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.UnShelve,434176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Enable,434176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Disable,434176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Ack,434176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Reset,434176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0113_2_XA.almPLCFault.Suppressed,434176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0113_2_XA.almPLCFault.Shelved,434176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0113_2_XA.almPLCFault.Disabled,434176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0113_2_XA.almPLCFault.Acked,434176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0113_2_XA.almPLCFault.Alarm,434176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Fault,434196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0114_1_XA.Alarm.AlarmState,434196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0114_1_XA.Alarm.GlobalReset,434196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0114_1_XA.Alarm.FaultInAlarm,434196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_1_XA.Alarm.ALRM,434196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0114_1_XA.Alarm.ANUN,434196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0114_1_XA.Alarm.AKED,434196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0114_1_XA.Alarm.Resetable,434196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0114_1_XA.Alarm.REST,434196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0114_1_XA.Alarm.ACKN,434196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0114_1_XA.Alarm.UACK,434196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0114_1_XA.Alarm.MCmd_Enable,434196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_1_XA.Alarm.MCmd_Disable,434196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_1_XA.Alarm.OCmd_Shelve,434196.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0114_1_XA.Alarm.OCmd_Unshelve,434196.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0114_1_XA.Alarm.SCmd_Suppress,434196.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0114_1_XA.Alarm.SCmd_UnSuppress,434197.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0114_1_XA.Alarm.AEShelveTMRDN,434197.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0114_1_XA.Alarm.Bad,434197.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0114_1_XA.Alarm.Suppress,434198.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.UnSuppress,434198.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Shelve,434198.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.UnShelve,434198.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Enable,434198.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Disable,434198.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Ack,434198.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Reset,434198.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0114_1_XA.Alarm.Suppressed,434198.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0114_1_XA.Alarm.Shelved,434198.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0114_1_XA.Alarm.Disabled,434198.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0114_1_XA.Alarm.Acked,434198.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0114_1_XA.Alarm.Alarm,434198.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Fault,434208.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0114_1_XA.almPLCFault.AlarmState,434208.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0114_1_XA.almPLCFault.GlobalReset,434208.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0114_1_XA.almPLCFault.FaultInAlarm,434208.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_1_XA.almPLCFault.ALRM,434208.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0114_1_XA.almPLCFault.ANUN,434208.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0114_1_XA.almPLCFault.AKED,434208.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0114_1_XA.almPLCFault.Resetable,434208.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0114_1_XA.almPLCFault.REST,434208.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0114_1_XA.almPLCFault.ACKN,434208.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0114_1_XA.almPLCFault.UACK,434208.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0114_1_XA.almPLCFault.MCmd_Enable,434208.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_1_XA.almPLCFault.MCmd_Disable,434208.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_1_XA.almPLCFault.OCmd_Shelve,434208.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0114_1_XA.almPLCFault.OCmd_Unshelve,434208.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0114_1_XA.almPLCFault.SCmd_Suppress,434208.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0114_1_XA.almPLCFault.SCmd_UnSuppress,434209.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0114_1_XA.almPLCFault.AEShelveTMRDN,434209.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0114_1_XA.almPLCFault.Bad,434209.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0114_1_XA.almPLCFault.Suppress,434210.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.UnSuppress,434210.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Shelve,434210.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.UnShelve,434210.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Enable,434210.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Disable,434210.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Ack,434210.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Reset,434210.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0114_1_XA.almPLCFault.Suppressed,434210.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0114_1_XA.almPLCFault.Shelved,434210.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0114_1_XA.almPLCFault.Disabled,434210.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0114_1_XA.almPLCFault.Acked,434210.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0114_1_XA.almPLCFault.Alarm,434210.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Fault,434232.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0114_2_XA.Alarm.AlarmState,434232.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0114_2_XA.Alarm.GlobalReset,434232.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0114_2_XA.Alarm.FaultInAlarm,434232.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_2_XA.Alarm.ALRM,434232.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0114_2_XA.Alarm.ANUN,434232.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0114_2_XA.Alarm.AKED,434232.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0114_2_XA.Alarm.Resetable,434232.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0114_2_XA.Alarm.REST,434232.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0114_2_XA.Alarm.ACKN,434232.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0114_2_XA.Alarm.UACK,434232.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0114_2_XA.Alarm.MCmd_Enable,434232.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_2_XA.Alarm.MCmd_Disable,434232.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_2_XA.Alarm.OCmd_Shelve,434232.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0114_2_XA.Alarm.OCmd_Unshelve,434232.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0114_2_XA.Alarm.SCmd_Suppress,434232.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0114_2_XA.Alarm.SCmd_UnSuppress,434233.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0114_2_XA.Alarm.AEShelveTMRDN,434233.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0114_2_XA.Alarm.Bad,434233.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0114_2_XA.Alarm.Suppress,434234.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.UnSuppress,434234.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Shelve,434234.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.UnShelve,434234.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Enable,434234.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Disable,434234.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Ack,434234.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Reset,434234.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0114_2_XA.Alarm.Suppressed,434234.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0114_2_XA.Alarm.Shelved,434234.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0114_2_XA.Alarm.Disabled,434234.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0114_2_XA.Alarm.Acked,434234.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0114_2_XA.Alarm.Alarm,434234.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Fault,434244.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SD_0114_2_XA.almPLCFault.AlarmState,434244.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SD_0114_2_XA.almPLCFault.GlobalReset,434244.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SD_0114_2_XA.almPLCFault.FaultInAlarm,434244.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SD_0114_2_XA.almPLCFault.ALRM,434244.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SD_0114_2_XA.almPLCFault.ANUN,434244.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SD_0114_2_XA.almPLCFault.AKED,434244.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SD_0114_2_XA.almPLCFault.Resetable,434244.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SD_0114_2_XA.almPLCFault.REST,434244.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SD_0114_2_XA.almPLCFault.ACKN,434244.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SD_0114_2_XA.almPLCFault.UACK,434244.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SD_0114_2_XA.almPLCFault.MCmd_Enable,434244.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SD_0114_2_XA.almPLCFault.MCmd_Disable,434244.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SD_0114_2_XA.almPLCFault.OCmd_Shelve,434244.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SD_0114_2_XA.almPLCFault.OCmd_Unshelve,434244.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SD_0114_2_XA.almPLCFault.SCmd_Suppress,434244.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SD_0114_2_XA.almPLCFault.SCmd_UnSuppress,434245.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SD_0114_2_XA.almPLCFault.AEShelveTMRDN,434245.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SD_0114_2_XA.almPLCFault.Bad,434245.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SD_0114_2_XA.almPLCFault.Suppress,434246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.UnSuppress,434246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Shelve,434246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.UnShelve,434246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Enable,434246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Disable,434246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Ack,434246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Reset,434246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SD_0114_2_XA.almPLCFault.Suppressed,434246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SD_0114_2_XA.almPLCFault.Shelved,434246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SD_0114_2_XA.almPLCFault.Disabled,434246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SD_0114_2_XA.almPLCFault.Acked,434246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SD_0114_2_XA.almPLCFault.Alarm,434246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Fault,434266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_1_XA.Alarm.AlarmState,434266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_1_XA.Alarm.GlobalReset,434266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_1_XA.Alarm.FaultInAlarm,434266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_1_XA.Alarm.ALRM,434266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_1_XA.Alarm.ANUN,434266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_1_XA.Alarm.AKED,434266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_1_XA.Alarm.Resetable,434266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_1_XA.Alarm.REST,434266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_1_XA.Alarm.ACKN,434266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_1_XA.Alarm.UACK,434266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_1_XA.Alarm.MCmd_Enable,434266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_1_XA.Alarm.MCmd_Disable,434266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_1_XA.Alarm.OCmd_Shelve,434266.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_1_XA.Alarm.OCmd_Unshelve,434266.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_1_XA.Alarm.SCmd_Suppress,434266.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_1_XA.Alarm.SCmd_UnSuppress,434267.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_1_XA.Alarm.AEShelveTMRDN,434267.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_1_XA.Alarm.Bad,434267.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_1_XA.Alarm.Suppress,434268.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.UnSuppress,434268.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Shelve,434268.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.UnShelve,434268.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Enable,434268.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Disable,434268.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Ack,434268.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Reset,434268.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_1_XA.Alarm.Suppressed,434268.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_1_XA.Alarm.Shelved,434268.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_1_XA.Alarm.Disabled,434268.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_1_XA.Alarm.Acked,434268.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_1_XA.Alarm.Alarm,434268.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Fault,434278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_1_XA.almPLCFault.AlarmState,434278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_1_XA.almPLCFault.GlobalReset,434278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_1_XA.almPLCFault.FaultInAlarm,434278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_1_XA.almPLCFault.ALRM,434278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_1_XA.almPLCFault.ANUN,434278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_1_XA.almPLCFault.AKED,434278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_1_XA.almPLCFault.Resetable,434278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_1_XA.almPLCFault.REST,434278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_1_XA.almPLCFault.ACKN,434278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_1_XA.almPLCFault.UACK,434278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_1_XA.almPLCFault.MCmd_Enable,434278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_1_XA.almPLCFault.MCmd_Disable,434278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_1_XA.almPLCFault.OCmd_Shelve,434278.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_1_XA.almPLCFault.OCmd_Unshelve,434278.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_1_XA.almPLCFault.SCmd_Suppress,434278.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_1_XA.almPLCFault.SCmd_UnSuppress,434279.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_1_XA.almPLCFault.AEShelveTMRDN,434279.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_1_XA.almPLCFault.Bad,434279.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_1_XA.almPLCFault.Suppress,434280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.UnSuppress,434280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Shelve,434280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.UnShelve,434280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Enable,434280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Disable,434280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Ack,434280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Reset,434280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Suppressed,434280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Shelved,434280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Disabled,434280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Acked,434280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_1_XA.almPLCFault.Alarm,434280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Fault,434302.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_2_XA.Alarm.AlarmState,434302.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_2_XA.Alarm.GlobalReset,434302.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_2_XA.Alarm.FaultInAlarm,434302.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_2_XA.Alarm.ALRM,434302.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_2_XA.Alarm.ANUN,434302.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_2_XA.Alarm.AKED,434302.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_2_XA.Alarm.Resetable,434302.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_2_XA.Alarm.REST,434302.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_2_XA.Alarm.ACKN,434302.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_2_XA.Alarm.UACK,434302.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_2_XA.Alarm.MCmd_Enable,434302.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_2_XA.Alarm.MCmd_Disable,434302.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_2_XA.Alarm.OCmd_Shelve,434302.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_2_XA.Alarm.OCmd_Unshelve,434302.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_2_XA.Alarm.SCmd_Suppress,434302.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_2_XA.Alarm.SCmd_UnSuppress,434303.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_2_XA.Alarm.AEShelveTMRDN,434303.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_2_XA.Alarm.Bad,434303.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_2_XA.Alarm.Suppress,434304.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.UnSuppress,434304.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Shelve,434304.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.UnShelve,434304.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Enable,434304.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Disable,434304.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Ack,434304.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Reset,434304.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_2_XA.Alarm.Suppressed,434304.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_2_XA.Alarm.Shelved,434304.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_2_XA.Alarm.Disabled,434304.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_2_XA.Alarm.Acked,434304.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_2_XA.Alarm.Alarm,434304.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Fault,434314.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_2_XA.almPLCFault.AlarmState,434314.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_2_XA.almPLCFault.GlobalReset,434314.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_2_XA.almPLCFault.FaultInAlarm,434314.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_2_XA.almPLCFault.ALRM,434314.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_2_XA.almPLCFault.ANUN,434314.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_2_XA.almPLCFault.AKED,434314.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_2_XA.almPLCFault.Resetable,434314.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_2_XA.almPLCFault.REST,434314.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_2_XA.almPLCFault.ACKN,434314.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_2_XA.almPLCFault.UACK,434314.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_2_XA.almPLCFault.MCmd_Enable,434314.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_2_XA.almPLCFault.MCmd_Disable,434314.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_2_XA.almPLCFault.OCmd_Shelve,434314.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_2_XA.almPLCFault.OCmd_Unshelve,434314.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_2_XA.almPLCFault.SCmd_Suppress,434314.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_2_XA.almPLCFault.SCmd_UnSuppress,434315.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_2_XA.almPLCFault.AEShelveTMRDN,434315.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_2_XA.almPLCFault.Bad,434315.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_2_XA.almPLCFault.Suppress,434316.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.UnSuppress,434316.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Shelve,434316.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.UnShelve,434316.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Enable,434316.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Disable,434316.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Ack,434316.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Reset,434316.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Suppressed,434316.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Shelved,434316.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Disabled,434316.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Acked,434316.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_2_XA.almPLCFault.Alarm,434316.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Fault,434336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3_XA1.Alarm.AlarmState,434336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3_XA1.Alarm.GlobalReset,434336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3_XA1.Alarm.FaultInAlarm,434336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3_XA1.Alarm.ALRM,434336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3_XA1.Alarm.ANUN,434336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3_XA1.Alarm.AKED,434336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3_XA1.Alarm.Resetable,434336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3_XA1.Alarm.REST,434336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3_XA1.Alarm.ACKN,434336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3_XA1.Alarm.UACK,434336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3_XA1.Alarm.MCmd_Enable,434336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3_XA1.Alarm.MCmd_Disable,434336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3_XA1.Alarm.OCmd_Shelve,434336.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3_XA1.Alarm.OCmd_Unshelve,434336.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3_XA1.Alarm.SCmd_Suppress,434336.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3_XA1.Alarm.SCmd_UnSuppress,434337.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3_XA1.Alarm.AEShelveTMRDN,434337.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3_XA1.Alarm.Bad,434337.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3_XA1.Alarm.Suppress,434338.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.UnSuppress,434338.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Shelve,434338.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.UnShelve,434338.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Enable,434338.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Disable,434338.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Ack,434338.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Reset,434338.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3_XA1.Alarm.Suppressed,434338.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3_XA1.Alarm.Shelved,434338.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3_XA1.Alarm.Disabled,434338.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3_XA1.Alarm.Acked,434338.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3_XA1.Alarm.Alarm,434338.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Fault,434348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3_XA1.almPLCFault.AlarmState,434348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3_XA1.almPLCFault.GlobalReset,434348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3_XA1.almPLCFault.FaultInAlarm,434348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3_XA1.almPLCFault.ALRM,434348.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3_XA1.almPLCFault.ANUN,434348.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3_XA1.almPLCFault.AKED,434348.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3_XA1.almPLCFault.Resetable,434348.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3_XA1.almPLCFault.REST,434348.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3_XA1.almPLCFault.ACKN,434348.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3_XA1.almPLCFault.UACK,434348.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3_XA1.almPLCFault.MCmd_Enable,434348.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.MCmd_Disable,434348.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.OCmd_Shelve,434348.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.OCmd_Unshelve,434348.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.SCmd_Suppress,434348.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.SCmd_UnSuppress,434349.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3_XA1.almPLCFault.AEShelveTMRDN,434349.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3_XA1.almPLCFault.Bad,434349.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3_XA1.almPLCFault.Suppress,434350.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.UnSuppress,434350.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Shelve,434350.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.UnShelve,434350.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Enable,434350.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Disable,434350.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Ack,434350.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Reset,434350.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Suppressed,434350.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Shelved,434350.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Disabled,434350.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Acked,434350.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3_XA1.almPLCFault.Alarm,434350.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Fault,434372.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3A_XA.Alarm.AlarmState,434372.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3A_XA.Alarm.GlobalReset,434372.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3A_XA.Alarm.FaultInAlarm,434372.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3A_XA.Alarm.ALRM,434372.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3A_XA.Alarm.ANUN,434372.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3A_XA.Alarm.AKED,434372.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3A_XA.Alarm.Resetable,434372.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3A_XA.Alarm.REST,434372.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3A_XA.Alarm.ACKN,434372.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3A_XA.Alarm.UACK,434372.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3A_XA.Alarm.MCmd_Enable,434372.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3A_XA.Alarm.MCmd_Disable,434372.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3A_XA.Alarm.OCmd_Shelve,434372.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3A_XA.Alarm.OCmd_Unshelve,434372.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3A_XA.Alarm.SCmd_Suppress,434372.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3A_XA.Alarm.SCmd_UnSuppress,434373.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3A_XA.Alarm.AEShelveTMRDN,434373.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3A_XA.Alarm.Bad,434373.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3A_XA.Alarm.Suppress,434374.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.UnSuppress,434374.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Shelve,434374.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.UnShelve,434374.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Enable,434374.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Disable,434374.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Ack,434374.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Reset,434374.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3A_XA.Alarm.Suppressed,434374.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3A_XA.Alarm.Shelved,434374.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3A_XA.Alarm.Disabled,434374.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3A_XA.Alarm.Acked,434374.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3A_XA.Alarm.Alarm,434374.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Fault,434384.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3A_XA.almPLCFault.AlarmState,434384.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3A_XA.almPLCFault.GlobalReset,434384.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3A_XA.almPLCFault.FaultInAlarm,434384.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3A_XA.almPLCFault.ALRM,434384.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3A_XA.almPLCFault.ANUN,434384.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3A_XA.almPLCFault.AKED,434384.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3A_XA.almPLCFault.Resetable,434384.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3A_XA.almPLCFault.REST,434384.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3A_XA.almPLCFault.ACKN,434384.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3A_XA.almPLCFault.UACK,434384.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3A_XA.almPLCFault.MCmd_Enable,434384.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.MCmd_Disable,434384.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.OCmd_Shelve,434384.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.OCmd_Unshelve,434384.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.SCmd_Suppress,434384.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.SCmd_UnSuppress,434385.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3A_XA.almPLCFault.AEShelveTMRDN,434385.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3A_XA.almPLCFault.Bad,434385.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3A_XA.almPLCFault.Suppress,434386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.UnSuppress,434386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Shelve,434386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.UnShelve,434386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Enable,434386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Disable,434386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Ack,434386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Reset,434386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Suppressed,434386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Shelved,434386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Disabled,434386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Acked,434386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3A_XA.almPLCFault.Alarm,434386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Fault,434406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3B_XA.Alarm.AlarmState,434406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3B_XA.Alarm.GlobalReset,434406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3B_XA.Alarm.FaultInAlarm,434406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3B_XA.Alarm.ALRM,434406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3B_XA.Alarm.ANUN,434406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3B_XA.Alarm.AKED,434406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3B_XA.Alarm.Resetable,434406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3B_XA.Alarm.REST,434406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3B_XA.Alarm.ACKN,434406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3B_XA.Alarm.UACK,434406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3B_XA.Alarm.MCmd_Enable,434406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3B_XA.Alarm.MCmd_Disable,434406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3B_XA.Alarm.OCmd_Shelve,434406.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3B_XA.Alarm.OCmd_Unshelve,434406.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3B_XA.Alarm.SCmd_Suppress,434406.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3B_XA.Alarm.SCmd_UnSuppress,434407.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3B_XA.Alarm.AEShelveTMRDN,434407.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3B_XA.Alarm.Bad,434407.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3B_XA.Alarm.Suppress,434408.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.UnSuppress,434408.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Shelve,434408.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.UnShelve,434408.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Enable,434408.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Disable,434408.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Ack,434408.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Reset,434408.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3B_XA.Alarm.Suppressed,434408.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3B_XA.Alarm.Shelved,434408.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3B_XA.Alarm.Disabled,434408.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3B_XA.Alarm.Acked,434408.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3B_XA.Alarm.Alarm,434408.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Fault,434418.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_3B_XA.almPLCFault.AlarmState,434418.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_3B_XA.almPLCFault.GlobalReset,434418.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_3B_XA.almPLCFault.FaultInAlarm,434418.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_3B_XA.almPLCFault.ALRM,434418.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_3B_XA.almPLCFault.ANUN,434418.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_3B_XA.almPLCFault.AKED,434418.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_3B_XA.almPLCFault.Resetable,434418.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_3B_XA.almPLCFault.REST,434418.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_3B_XA.almPLCFault.ACKN,434418.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_3B_XA.almPLCFault.UACK,434418.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_3B_XA.almPLCFault.MCmd_Enable,434418.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.MCmd_Disable,434418.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.OCmd_Shelve,434418.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.OCmd_Unshelve,434418.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.SCmd_Suppress,434418.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.SCmd_UnSuppress,434419.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_3B_XA.almPLCFault.AEShelveTMRDN,434419.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_3B_XA.almPLCFault.Bad,434419.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_3B_XA.almPLCFault.Suppress,434420.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.UnSuppress,434420.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Shelve,434420.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.UnShelve,434420.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Enable,434420.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Disable,434420.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Ack,434420.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Reset,434420.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Suppressed,434420.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Shelved,434420.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Disabled,434420.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Acked,434420.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_3B_XA.almPLCFault.Alarm,434420.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Fault,434442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_4_XA.Alarm.AlarmState,434442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_4_XA.Alarm.GlobalReset,434442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_4_XA.Alarm.FaultInAlarm,434442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA.Alarm.ALRM,434442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_4_XA.Alarm.ANUN,434442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_4_XA.Alarm.AKED,434442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_4_XA.Alarm.Resetable,434442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_4_XA.Alarm.REST,434442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_4_XA.Alarm.ACKN,434442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_4_XA.Alarm.UACK,434442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_4_XA.Alarm.MCmd_Enable,434442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA.Alarm.MCmd_Disable,434442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA.Alarm.OCmd_Shelve,434442.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_4_XA.Alarm.OCmd_Unshelve,434442.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_4_XA.Alarm.SCmd_Suppress,434442.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_4_XA.Alarm.SCmd_UnSuppress,434443.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_4_XA.Alarm.AEShelveTMRDN,434443.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_4_XA.Alarm.Bad,434443.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_4_XA.Alarm.Suppress,434444.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.UnSuppress,434444.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Shelve,434444.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.UnShelve,434444.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Enable,434444.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Disable,434444.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Ack,434444.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Reset,434444.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_4_XA.Alarm.Suppressed,434444.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_4_XA.Alarm.Shelved,434444.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_4_XA.Alarm.Disabled,434444.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_4_XA.Alarm.Acked,434444.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_4_XA.Alarm.Alarm,434444.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Fault,434454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_4_XA.almPLCFault.AlarmState,434454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_4_XA.almPLCFault.GlobalReset,434454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_4_XA.almPLCFault.FaultInAlarm,434454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA.almPLCFault.ALRM,434454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_4_XA.almPLCFault.ANUN,434454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_4_XA.almPLCFault.AKED,434454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_4_XA.almPLCFault.Resetable,434454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_4_XA.almPLCFault.REST,434454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_4_XA.almPLCFault.ACKN,434454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_4_XA.almPLCFault.UACK,434454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_4_XA.almPLCFault.MCmd_Enable,434454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA.almPLCFault.MCmd_Disable,434454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA.almPLCFault.OCmd_Shelve,434454.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_4_XA.almPLCFault.OCmd_Unshelve,434454.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_4_XA.almPLCFault.SCmd_Suppress,434454.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_4_XA.almPLCFault.SCmd_UnSuppress,434455.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_4_XA.almPLCFault.AEShelveTMRDN,434455.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_4_XA.almPLCFault.Bad,434455.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_4_XA.almPLCFault.Suppress,434456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.UnSuppress,434456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Shelve,434456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.UnShelve,434456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Enable,434456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Disable,434456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Ack,434456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Reset,434456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Suppressed,434456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Shelved,434456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Disabled,434456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Acked,434456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_4_XA.almPLCFault.Alarm,434456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Fault,434476.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_4_XA1.Alarm.AlarmState,434476.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_4_XA1.Alarm.GlobalReset,434476.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_4_XA1.Alarm.FaultInAlarm,434476.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA1.Alarm.ALRM,434476.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_4_XA1.Alarm.ANUN,434476.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_4_XA1.Alarm.AKED,434476.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_4_XA1.Alarm.Resetable,434476.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_4_XA1.Alarm.REST,434476.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_4_XA1.Alarm.ACKN,434476.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_4_XA1.Alarm.UACK,434476.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_4_XA1.Alarm.MCmd_Enable,434476.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA1.Alarm.MCmd_Disable,434476.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA1.Alarm.OCmd_Shelve,434476.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_4_XA1.Alarm.OCmd_Unshelve,434476.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_4_XA1.Alarm.SCmd_Suppress,434476.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_4_XA1.Alarm.SCmd_UnSuppress,434477.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_4_XA1.Alarm.AEShelveTMRDN,434477.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_4_XA1.Alarm.Bad,434477.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_4_XA1.Alarm.Suppress,434478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.UnSuppress,434478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Shelve,434478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.UnShelve,434478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Enable,434478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Disable,434478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Ack,434478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Reset,434478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_4_XA1.Alarm.Suppressed,434478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_4_XA1.Alarm.Shelved,434478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_4_XA1.Alarm.Disabled,434478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_4_XA1.Alarm.Acked,434478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_4_XA1.Alarm.Alarm,434478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Fault,434488.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_4_XA1.almPLCFault.AlarmState,434488.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_4_XA1.almPLCFault.GlobalReset,434488.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_4_XA1.almPLCFault.FaultInAlarm,434488.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_4_XA1.almPLCFault.ALRM,434488.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_4_XA1.almPLCFault.ANUN,434488.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_4_XA1.almPLCFault.AKED,434488.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_4_XA1.almPLCFault.Resetable,434488.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_4_XA1.almPLCFault.REST,434488.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_4_XA1.almPLCFault.ACKN,434488.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_4_XA1.almPLCFault.UACK,434488.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_4_XA1.almPLCFault.MCmd_Enable,434488.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.MCmd_Disable,434488.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.OCmd_Shelve,434488.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.OCmd_Unshelve,434488.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.SCmd_Suppress,434488.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.SCmd_UnSuppress,434489.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_4_XA1.almPLCFault.AEShelveTMRDN,434489.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_4_XA1.almPLCFault.Bad,434489.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_4_XA1.almPLCFault.Suppress,434490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.UnSuppress,434490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Shelve,434490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.UnShelve,434490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Enable,434490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Disable,434490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Ack,434490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Reset,434490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Suppressed,434490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Shelved,434490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Disabled,434490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Acked,434490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_4_XA1.almPLCFault.Alarm,434490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Fault,434512.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_5_XA.Alarm.AlarmState,434512.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_5_XA.Alarm.GlobalReset,434512.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_5_XA.Alarm.FaultInAlarm,434512.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_5_XA.Alarm.ALRM,434512.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_5_XA.Alarm.ANUN,434512.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_5_XA.Alarm.AKED,434512.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_5_XA.Alarm.Resetable,434512.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_5_XA.Alarm.REST,434512.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_5_XA.Alarm.ACKN,434512.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_5_XA.Alarm.UACK,434512.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_5_XA.Alarm.MCmd_Enable,434512.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_5_XA.Alarm.MCmd_Disable,434512.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_5_XA.Alarm.OCmd_Shelve,434512.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_5_XA.Alarm.OCmd_Unshelve,434512.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_5_XA.Alarm.SCmd_Suppress,434512.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_5_XA.Alarm.SCmd_UnSuppress,434513.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_5_XA.Alarm.AEShelveTMRDN,434513.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_5_XA.Alarm.Bad,434513.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_5_XA.Alarm.Suppress,434514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.UnSuppress,434514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Shelve,434514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.UnShelve,434514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Enable,434514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Disable,434514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Ack,434514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Reset,434514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_5_XA.Alarm.Suppressed,434514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_5_XA.Alarm.Shelved,434514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_5_XA.Alarm.Disabled,434514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_5_XA.Alarm.Acked,434514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_5_XA.Alarm.Alarm,434514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Fault,434524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_5_XA.almPLCFault.AlarmState,434524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_5_XA.almPLCFault.GlobalReset,434524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_5_XA.almPLCFault.FaultInAlarm,434524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_5_XA.almPLCFault.ALRM,434524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_5_XA.almPLCFault.ANUN,434524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_5_XA.almPLCFault.AKED,434524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_5_XA.almPLCFault.Resetable,434524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_5_XA.almPLCFault.REST,434524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_5_XA.almPLCFault.ACKN,434524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_5_XA.almPLCFault.UACK,434524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_5_XA.almPLCFault.MCmd_Enable,434524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_5_XA.almPLCFault.MCmd_Disable,434524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_5_XA.almPLCFault.OCmd_Shelve,434524.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_5_XA.almPLCFault.OCmd_Unshelve,434524.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_5_XA.almPLCFault.SCmd_Suppress,434524.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_5_XA.almPLCFault.SCmd_UnSuppress,434525.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_5_XA.almPLCFault.AEShelveTMRDN,434525.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_5_XA.almPLCFault.Bad,434525.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_5_XA.almPLCFault.Suppress,434526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.UnSuppress,434526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Shelve,434526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.UnShelve,434526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Enable,434526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Disable,434526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Ack,434526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Reset,434526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Suppressed,434526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Shelved,434526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Disabled,434526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Acked,434526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_5_XA.almPLCFault.Alarm,434526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Fault,434546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_6_XA.Alarm.AlarmState,434546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_6_XA.Alarm.GlobalReset,434546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_6_XA.Alarm.FaultInAlarm,434546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_6_XA.Alarm.ALRM,434546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_6_XA.Alarm.ANUN,434546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_6_XA.Alarm.AKED,434546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_6_XA.Alarm.Resetable,434546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_6_XA.Alarm.REST,434546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_6_XA.Alarm.ACKN,434546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_6_XA.Alarm.UACK,434546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_6_XA.Alarm.MCmd_Enable,434546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_6_XA.Alarm.MCmd_Disable,434546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_6_XA.Alarm.OCmd_Shelve,434546.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_6_XA.Alarm.OCmd_Unshelve,434546.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_6_XA.Alarm.SCmd_Suppress,434546.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_6_XA.Alarm.SCmd_UnSuppress,434547.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_6_XA.Alarm.AEShelveTMRDN,434547.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_6_XA.Alarm.Bad,434547.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_6_XA.Alarm.Suppress,434548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.UnSuppress,434548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Shelve,434548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.UnShelve,434548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Enable,434548.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Disable,434548.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Ack,434548.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Reset,434548.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_6_XA.Alarm.Suppressed,434548.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_6_XA.Alarm.Shelved,434548.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_6_XA.Alarm.Disabled,434548.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_6_XA.Alarm.Acked,434548.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_6_XA.Alarm.Alarm,434548.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Fault,434558.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0112_6_XA.almPLCFault.AlarmState,434558.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0112_6_XA.almPLCFault.GlobalReset,434558.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0112_6_XA.almPLCFault.FaultInAlarm,434558.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0112_6_XA.almPLCFault.ALRM,434558.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0112_6_XA.almPLCFault.ANUN,434558.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0112_6_XA.almPLCFault.AKED,434558.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0112_6_XA.almPLCFault.Resetable,434558.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0112_6_XA.almPLCFault.REST,434558.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0112_6_XA.almPLCFault.ACKN,434558.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0112_6_XA.almPLCFault.UACK,434558.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0112_6_XA.almPLCFault.MCmd_Enable,434558.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0112_6_XA.almPLCFault.MCmd_Disable,434558.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0112_6_XA.almPLCFault.OCmd_Shelve,434558.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0112_6_XA.almPLCFault.OCmd_Unshelve,434558.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0112_6_XA.almPLCFault.SCmd_Suppress,434558.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0112_6_XA.almPLCFault.SCmd_UnSuppress,434559.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0112_6_XA.almPLCFault.AEShelveTMRDN,434559.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0112_6_XA.almPLCFault.Bad,434559.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0112_6_XA.almPLCFault.Suppress,434560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.UnSuppress,434560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Shelve,434560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.UnShelve,434560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Enable,434560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Disable,434560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Ack,434560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Reset,434560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Suppressed,434560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Shelved,434560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Disabled,434560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Acked,434560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0112_6_XA.almPLCFault.Alarm,434560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Fault,434582.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0113_1_XA.Alarm.AlarmState,434582.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0113_1_XA.Alarm.GlobalReset,434582.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0113_1_XA.Alarm.FaultInAlarm,434582.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_1_XA.Alarm.ALRM,434582.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0113_1_XA.Alarm.ANUN,434582.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0113_1_XA.Alarm.AKED,434582.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0113_1_XA.Alarm.Resetable,434582.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0113_1_XA.Alarm.REST,434582.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0113_1_XA.Alarm.ACKN,434582.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0113_1_XA.Alarm.UACK,434582.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0113_1_XA.Alarm.MCmd_Enable,434582.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_1_XA.Alarm.MCmd_Disable,434582.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_1_XA.Alarm.OCmd_Shelve,434582.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0113_1_XA.Alarm.OCmd_Unshelve,434582.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0113_1_XA.Alarm.SCmd_Suppress,434582.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0113_1_XA.Alarm.SCmd_UnSuppress,434583.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0113_1_XA.Alarm.AEShelveTMRDN,434583.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0113_1_XA.Alarm.Bad,434583.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0113_1_XA.Alarm.Suppress,434584.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.UnSuppress,434584.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Shelve,434584.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.UnShelve,434584.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Enable,434584.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Disable,434584.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Ack,434584.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Reset,434584.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0113_1_XA.Alarm.Suppressed,434584.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0113_1_XA.Alarm.Shelved,434584.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0113_1_XA.Alarm.Disabled,434584.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0113_1_XA.Alarm.Acked,434584.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0113_1_XA.Alarm.Alarm,434584.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Fault,434594.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0113_1_XA.almPLCFault.AlarmState,434594.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0113_1_XA.almPLCFault.GlobalReset,434594.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0113_1_XA.almPLCFault.FaultInAlarm,434594.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_1_XA.almPLCFault.ALRM,434594.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0113_1_XA.almPLCFault.ANUN,434594.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0113_1_XA.almPLCFault.AKED,434594.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0113_1_XA.almPLCFault.Resetable,434594.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0113_1_XA.almPLCFault.REST,434594.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0113_1_XA.almPLCFault.ACKN,434594.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0113_1_XA.almPLCFault.UACK,434594.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0113_1_XA.almPLCFault.MCmd_Enable,434594.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_1_XA.almPLCFault.MCmd_Disable,434594.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_1_XA.almPLCFault.OCmd_Shelve,434594.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0113_1_XA.almPLCFault.OCmd_Unshelve,434594.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0113_1_XA.almPLCFault.SCmd_Suppress,434594.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0113_1_XA.almPLCFault.SCmd_UnSuppress,434595.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0113_1_XA.almPLCFault.AEShelveTMRDN,434595.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0113_1_XA.almPLCFault.Bad,434595.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0113_1_XA.almPLCFault.Suppress,434596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.UnSuppress,434596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Shelve,434596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.UnShelve,434596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Enable,434596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Disable,434596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Ack,434596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Reset,434596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Suppressed,434596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Shelved,434596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Disabled,434596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Acked,434596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0113_1_XA.almPLCFault.Alarm,434596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Fault,434616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0113_2_XA.Alarm.AlarmState,434616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0113_2_XA.Alarm.GlobalReset,434616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0113_2_XA.Alarm.FaultInAlarm,434616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_2_XA.Alarm.ALRM,434616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0113_2_XA.Alarm.ANUN,434616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0113_2_XA.Alarm.AKED,434616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0113_2_XA.Alarm.Resetable,434616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0113_2_XA.Alarm.REST,434616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0113_2_XA.Alarm.ACKN,434616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0113_2_XA.Alarm.UACK,434616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0113_2_XA.Alarm.MCmd_Enable,434616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_2_XA.Alarm.MCmd_Disable,434616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_2_XA.Alarm.OCmd_Shelve,434616.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0113_2_XA.Alarm.OCmd_Unshelve,434616.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0113_2_XA.Alarm.SCmd_Suppress,434616.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0113_2_XA.Alarm.SCmd_UnSuppress,434617.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0113_2_XA.Alarm.AEShelveTMRDN,434617.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0113_2_XA.Alarm.Bad,434617.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0113_2_XA.Alarm.Suppress,434618.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.UnSuppress,434618.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Shelve,434618.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.UnShelve,434618.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Enable,434618.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Disable,434618.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Ack,434618.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Reset,434618.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0113_2_XA.Alarm.Suppressed,434618.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0113_2_XA.Alarm.Shelved,434618.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0113_2_XA.Alarm.Disabled,434618.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0113_2_XA.Alarm.Acked,434618.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0113_2_XA.Alarm.Alarm,434618.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Fault,434628.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_SPD_0113_2_XA.almPLCFault.AlarmState,434628.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_SPD_0113_2_XA.almPLCFault.GlobalReset,434628.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_SPD_0113_2_XA.almPLCFault.FaultInAlarm,434628.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_SPD_0113_2_XA.almPLCFault.ALRM,434628.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_SPD_0113_2_XA.almPLCFault.ANUN,434628.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_SPD_0113_2_XA.almPLCFault.AKED,434628.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_SPD_0113_2_XA.almPLCFault.Resetable,434628.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_SPD_0113_2_XA.almPLCFault.REST,434628.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_SPD_0113_2_XA.almPLCFault.ACKN,434628.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_SPD_0113_2_XA.almPLCFault.UACK,434628.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_SPD_0113_2_XA.almPLCFault.MCmd_Enable,434628.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_SPD_0113_2_XA.almPLCFault.MCmd_Disable,434628.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_SPD_0113_2_XA.almPLCFault.OCmd_Shelve,434628.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_SPD_0113_2_XA.almPLCFault.OCmd_Unshelve,434628.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_SPD_0113_2_XA.almPLCFault.SCmd_Suppress,434628.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_SPD_0113_2_XA.almPLCFault.SCmd_UnSuppress,434629.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_SPD_0113_2_XA.almPLCFault.AEShelveTMRDN,434629.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_SPD_0113_2_XA.almPLCFault.Bad,434629.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_SPD_0113_2_XA.almPLCFault.Suppress,434630.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.UnSuppress,434630.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Shelve,434630.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.UnShelve,434630.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Enable,434630.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Disable,434630.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Ack,434630.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Reset,434630.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Suppressed,434630.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Shelved,434630.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Disabled,434630.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Acked,434630.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_SPD_0113_2_XA.almPLCFault.Alarm,434630.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Fault,434652.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0111_1_TH.Alarm.AlarmState,434652.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0111_1_TH.Alarm.GlobalReset,434652.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0111_1_TH.Alarm.FaultInAlarm,434652.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0111_1_TH.Alarm.ALRM,434652.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0111_1_TH.Alarm.ANUN,434652.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0111_1_TH.Alarm.AKED,434652.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0111_1_TH.Alarm.Resetable,434652.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0111_1_TH.Alarm.REST,434652.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0111_1_TH.Alarm.ACKN,434652.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0111_1_TH.Alarm.UACK,434652.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0111_1_TH.Alarm.MCmd_Enable,434652.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0111_1_TH.Alarm.MCmd_Disable,434652.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0111_1_TH.Alarm.OCmd_Shelve,434652.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0111_1_TH.Alarm.OCmd_Unshelve,434652.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0111_1_TH.Alarm.SCmd_Suppress,434652.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0111_1_TH.Alarm.SCmd_UnSuppress,434653.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0111_1_TH.Alarm.AEShelveTMRDN,434653.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0111_1_TH.Alarm.Bad,434653.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0111_1_TH.Alarm.Suppress,434654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.UnSuppress,434654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Shelve,434654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.UnShelve,434654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Enable,434654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Disable,434654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Ack,434654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Reset,434654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0111_1_TH.Alarm.Suppressed,434654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0111_1_TH.Alarm.Shelved,434654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0111_1_TH.Alarm.Disabled,434654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0111_1_TH.Alarm.Acked,434654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0111_1_TH.Alarm.Alarm,434654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Fault,434664.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0111_1_TH.almPLCFault.AlarmState,434664.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0111_1_TH.almPLCFault.GlobalReset,434664.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0111_1_TH.almPLCFault.FaultInAlarm,434664.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0111_1_TH.almPLCFault.ALRM,434664.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0111_1_TH.almPLCFault.ANUN,434664.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0111_1_TH.almPLCFault.AKED,434664.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0111_1_TH.almPLCFault.Resetable,434664.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0111_1_TH.almPLCFault.REST,434664.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0111_1_TH.almPLCFault.ACKN,434664.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0111_1_TH.almPLCFault.UACK,434664.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0111_1_TH.almPLCFault.MCmd_Enable,434664.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0111_1_TH.almPLCFault.MCmd_Disable,434664.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0111_1_TH.almPLCFault.OCmd_Shelve,434664.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0111_1_TH.almPLCFault.OCmd_Unshelve,434664.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0111_1_TH.almPLCFault.SCmd_Suppress,434664.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0111_1_TH.almPLCFault.SCmd_UnSuppress,434665.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0111_1_TH.almPLCFault.AEShelveTMRDN,434665.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0111_1_TH.almPLCFault.Bad,434665.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0111_1_TH.almPLCFault.Suppress,434666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.UnSuppress,434666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Shelve,434666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.UnShelve,434666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Enable,434666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Disable,434666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Ack,434666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Reset,434666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0111_1_TH.almPLCFault.Suppressed,434666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0111_1_TH.almPLCFault.Shelved,434666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0111_1_TH.almPLCFault.Disabled,434666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0111_1_TH.almPLCFault.Acked,434666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0111_1_TH.almPLCFault.Alarm,434666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Fault,434686.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0112_1_TH.Alarm.AlarmState,434686.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0112_1_TH.Alarm.GlobalReset,434686.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0112_1_TH.Alarm.FaultInAlarm,434686.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0112_1_TH.Alarm.ALRM,434686.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0112_1_TH.Alarm.ANUN,434686.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0112_1_TH.Alarm.AKED,434686.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0112_1_TH.Alarm.Resetable,434686.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0112_1_TH.Alarm.REST,434686.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0112_1_TH.Alarm.ACKN,434686.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0112_1_TH.Alarm.UACK,434686.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0112_1_TH.Alarm.MCmd_Enable,434686.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0112_1_TH.Alarm.MCmd_Disable,434686.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0112_1_TH.Alarm.OCmd_Shelve,434686.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0112_1_TH.Alarm.OCmd_Unshelve,434686.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0112_1_TH.Alarm.SCmd_Suppress,434686.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0112_1_TH.Alarm.SCmd_UnSuppress,434687.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0112_1_TH.Alarm.AEShelveTMRDN,434687.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0112_1_TH.Alarm.Bad,434687.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0112_1_TH.Alarm.Suppress,434688.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.UnSuppress,434688.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Shelve,434688.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.UnShelve,434688.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Enable,434688.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Disable,434688.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Ack,434688.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Reset,434688.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0112_1_TH.Alarm.Suppressed,434688.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0112_1_TH.Alarm.Shelved,434688.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0112_1_TH.Alarm.Disabled,434688.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0112_1_TH.Alarm.Acked,434688.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0112_1_TH.Alarm.Alarm,434688.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Fault,434698.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0112_1_TH.almPLCFault.AlarmState,434698.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0112_1_TH.almPLCFault.GlobalReset,434698.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0112_1_TH.almPLCFault.FaultInAlarm,434698.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0112_1_TH.almPLCFault.ALRM,434698.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0112_1_TH.almPLCFault.ANUN,434698.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0112_1_TH.almPLCFault.AKED,434698.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0112_1_TH.almPLCFault.Resetable,434698.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0112_1_TH.almPLCFault.REST,434698.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0112_1_TH.almPLCFault.ACKN,434698.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0112_1_TH.almPLCFault.UACK,434698.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0112_1_TH.almPLCFault.MCmd_Enable,434698.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0112_1_TH.almPLCFault.MCmd_Disable,434698.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0112_1_TH.almPLCFault.OCmd_Shelve,434698.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0112_1_TH.almPLCFault.OCmd_Unshelve,434698.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0112_1_TH.almPLCFault.SCmd_Suppress,434698.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0112_1_TH.almPLCFault.SCmd_UnSuppress,434699.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0112_1_TH.almPLCFault.AEShelveTMRDN,434699.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0112_1_TH.almPLCFault.Bad,434699.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0112_1_TH.almPLCFault.Suppress,434700.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.UnSuppress,434700.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Shelve,434700.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.UnShelve,434700.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Enable,434700.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Disable,434700.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Ack,434700.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Reset,434700.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0112_1_TH.almPLCFault.Suppressed,434700.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0112_1_TH.almPLCFault.Shelved,434700.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0112_1_TH.almPLCFault.Disabled,434700.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0112_1_TH.almPLCFault.Acked,434700.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0112_1_TH.almPLCFault.Alarm,434700.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Fault,434722.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0113_1_TH.Alarm.AlarmState,434722.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0113_1_TH.Alarm.GlobalReset,434722.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0113_1_TH.Alarm.FaultInAlarm,434722.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_1_TH.Alarm.ALRM,434722.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0113_1_TH.Alarm.ANUN,434722.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0113_1_TH.Alarm.AKED,434722.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0113_1_TH.Alarm.Resetable,434722.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0113_1_TH.Alarm.REST,434722.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0113_1_TH.Alarm.ACKN,434722.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0113_1_TH.Alarm.UACK,434722.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0113_1_TH.Alarm.MCmd_Enable,434722.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_1_TH.Alarm.MCmd_Disable,434722.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_1_TH.Alarm.OCmd_Shelve,434722.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0113_1_TH.Alarm.OCmd_Unshelve,434722.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0113_1_TH.Alarm.SCmd_Suppress,434722.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0113_1_TH.Alarm.SCmd_UnSuppress,434723.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0113_1_TH.Alarm.AEShelveTMRDN,434723.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0113_1_TH.Alarm.Bad,434723.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0113_1_TH.Alarm.Suppress,434724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.UnSuppress,434724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Shelve,434724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.UnShelve,434724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Enable,434724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Disable,434724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Ack,434724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Reset,434724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0113_1_TH.Alarm.Suppressed,434724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0113_1_TH.Alarm.Shelved,434724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0113_1_TH.Alarm.Disabled,434724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0113_1_TH.Alarm.Acked,434724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0113_1_TH.Alarm.Alarm,434724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Fault,434734.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0113_1_TH.almPLCFault.AlarmState,434734.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0113_1_TH.almPLCFault.GlobalReset,434734.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0113_1_TH.almPLCFault.FaultInAlarm,434734.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_1_TH.almPLCFault.ALRM,434734.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0113_1_TH.almPLCFault.ANUN,434734.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0113_1_TH.almPLCFault.AKED,434734.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0113_1_TH.almPLCFault.Resetable,434734.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0113_1_TH.almPLCFault.REST,434734.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0113_1_TH.almPLCFault.ACKN,434734.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0113_1_TH.almPLCFault.UACK,434734.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0113_1_TH.almPLCFault.MCmd_Enable,434734.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_1_TH.almPLCFault.MCmd_Disable,434734.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_1_TH.almPLCFault.OCmd_Shelve,434734.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0113_1_TH.almPLCFault.OCmd_Unshelve,434734.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0113_1_TH.almPLCFault.SCmd_Suppress,434734.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0113_1_TH.almPLCFault.SCmd_UnSuppress,434735.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0113_1_TH.almPLCFault.AEShelveTMRDN,434735.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0113_1_TH.almPLCFault.Bad,434735.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0113_1_TH.almPLCFault.Suppress,434736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.UnSuppress,434736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Shelve,434736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.UnShelve,434736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Enable,434736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Disable,434736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Ack,434736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Reset,434736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0113_1_TH.almPLCFault.Suppressed,434736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0113_1_TH.almPLCFault.Shelved,434736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0113_1_TH.almPLCFault.Disabled,434736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0113_1_TH.almPLCFault.Acked,434736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0113_1_TH.almPLCFault.Alarm,434736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Fault,434756.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0113_2_TH.Alarm.AlarmState,434756.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0113_2_TH.Alarm.GlobalReset,434756.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0113_2_TH.Alarm.FaultInAlarm,434756.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_2_TH.Alarm.ALRM,434756.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0113_2_TH.Alarm.ANUN,434756.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0113_2_TH.Alarm.AKED,434756.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0113_2_TH.Alarm.Resetable,434756.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0113_2_TH.Alarm.REST,434756.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0113_2_TH.Alarm.ACKN,434756.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0113_2_TH.Alarm.UACK,434756.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0113_2_TH.Alarm.MCmd_Enable,434756.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_2_TH.Alarm.MCmd_Disable,434756.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_2_TH.Alarm.OCmd_Shelve,434756.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0113_2_TH.Alarm.OCmd_Unshelve,434756.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0113_2_TH.Alarm.SCmd_Suppress,434756.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0113_2_TH.Alarm.SCmd_UnSuppress,434757.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0113_2_TH.Alarm.AEShelveTMRDN,434757.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0113_2_TH.Alarm.Bad,434757.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0113_2_TH.Alarm.Suppress,434758.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.UnSuppress,434758.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Shelve,434758.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.UnShelve,434758.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Enable,434758.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Disable,434758.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Ack,434758.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Reset,434758.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0113_2_TH.Alarm.Suppressed,434758.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0113_2_TH.Alarm.Shelved,434758.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0113_2_TH.Alarm.Disabled,434758.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0113_2_TH.Alarm.Acked,434758.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0113_2_TH.Alarm.Alarm,434758.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Fault,434768.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0113_2_TH.almPLCFault.AlarmState,434768.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0113_2_TH.almPLCFault.GlobalReset,434768.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0113_2_TH.almPLCFault.FaultInAlarm,434768.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0113_2_TH.almPLCFault.ALRM,434768.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0113_2_TH.almPLCFault.ANUN,434768.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0113_2_TH.almPLCFault.AKED,434768.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0113_2_TH.almPLCFault.Resetable,434768.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0113_2_TH.almPLCFault.REST,434768.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0113_2_TH.almPLCFault.ACKN,434768.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0113_2_TH.almPLCFault.UACK,434768.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0113_2_TH.almPLCFault.MCmd_Enable,434768.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0113_2_TH.almPLCFault.MCmd_Disable,434768.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0113_2_TH.almPLCFault.OCmd_Shelve,434768.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0113_2_TH.almPLCFault.OCmd_Unshelve,434768.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0113_2_TH.almPLCFault.SCmd_Suppress,434768.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0113_2_TH.almPLCFault.SCmd_UnSuppress,434769.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0113_2_TH.almPLCFault.AEShelveTMRDN,434769.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0113_2_TH.almPLCFault.Bad,434769.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0113_2_TH.almPLCFault.Suppress,434770.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.UnSuppress,434770.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Shelve,434770.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.UnShelve,434770.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Enable,434770.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Disable,434770.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Ack,434770.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Reset,434770.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0113_2_TH.almPLCFault.Suppressed,434770.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0113_2_TH.almPLCFault.Shelved,434770.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0113_2_TH.almPLCFault.Disabled,434770.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0113_2_TH.almPLCFault.Acked,434770.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0113_2_TH.almPLCFault.Alarm,434770.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Fault,434792.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0114_1_TH.Alarm.AlarmState,434792.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0114_1_TH.Alarm.GlobalReset,434792.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0114_1_TH.Alarm.FaultInAlarm,434792.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_1_TH.Alarm.ALRM,434792.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0114_1_TH.Alarm.ANUN,434792.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0114_1_TH.Alarm.AKED,434792.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0114_1_TH.Alarm.Resetable,434792.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0114_1_TH.Alarm.REST,434792.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0114_1_TH.Alarm.ACKN,434792.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0114_1_TH.Alarm.UACK,434792.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0114_1_TH.Alarm.MCmd_Enable,434792.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_1_TH.Alarm.MCmd_Disable,434792.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_1_TH.Alarm.OCmd_Shelve,434792.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0114_1_TH.Alarm.OCmd_Unshelve,434792.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0114_1_TH.Alarm.SCmd_Suppress,434792.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0114_1_TH.Alarm.SCmd_UnSuppress,434793.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0114_1_TH.Alarm.AEShelveTMRDN,434793.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0114_1_TH.Alarm.Bad,434793.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0114_1_TH.Alarm.Suppress,434794.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.UnSuppress,434794.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Shelve,434794.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.UnShelve,434794.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Enable,434794.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Disable,434794.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Ack,434794.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Reset,434794.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0114_1_TH.Alarm.Suppressed,434794.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0114_1_TH.Alarm.Shelved,434794.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0114_1_TH.Alarm.Disabled,434794.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0114_1_TH.Alarm.Acked,434794.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0114_1_TH.Alarm.Alarm,434794.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Fault,434804.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0114_1_TH.almPLCFault.AlarmState,434804.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0114_1_TH.almPLCFault.GlobalReset,434804.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0114_1_TH.almPLCFault.FaultInAlarm,434804.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_1_TH.almPLCFault.ALRM,434804.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0114_1_TH.almPLCFault.ANUN,434804.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0114_1_TH.almPLCFault.AKED,434804.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0114_1_TH.almPLCFault.Resetable,434804.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0114_1_TH.almPLCFault.REST,434804.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0114_1_TH.almPLCFault.ACKN,434804.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0114_1_TH.almPLCFault.UACK,434804.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0114_1_TH.almPLCFault.MCmd_Enable,434804.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_1_TH.almPLCFault.MCmd_Disable,434804.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_1_TH.almPLCFault.OCmd_Shelve,434804.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0114_1_TH.almPLCFault.OCmd_Unshelve,434804.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0114_1_TH.almPLCFault.SCmd_Suppress,434804.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0114_1_TH.almPLCFault.SCmd_UnSuppress,434805.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0114_1_TH.almPLCFault.AEShelveTMRDN,434805.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0114_1_TH.almPLCFault.Bad,434805.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0114_1_TH.almPLCFault.Suppress,434806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.UnSuppress,434806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Shelve,434806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.UnShelve,434806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Enable,434806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Disable,434806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Ack,434806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Reset,434806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0114_1_TH.almPLCFault.Suppressed,434806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0114_1_TH.almPLCFault.Shelved,434806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0114_1_TH.almPLCFault.Disabled,434806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0114_1_TH.almPLCFault.Acked,434806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0114_1_TH.almPLCFault.Alarm,434806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Fault,434826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0114_2_TH.Alarm.AlarmState,434826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0114_2_TH.Alarm.GlobalReset,434826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0114_2_TH.Alarm.FaultInAlarm,434826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_2_TH.Alarm.ALRM,434826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0114_2_TH.Alarm.ANUN,434826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0114_2_TH.Alarm.AKED,434826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0114_2_TH.Alarm.Resetable,434826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0114_2_TH.Alarm.REST,434826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0114_2_TH.Alarm.ACKN,434826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0114_2_TH.Alarm.UACK,434826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0114_2_TH.Alarm.MCmd_Enable,434826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_2_TH.Alarm.MCmd_Disable,434826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_2_TH.Alarm.OCmd_Shelve,434826.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0114_2_TH.Alarm.OCmd_Unshelve,434826.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0114_2_TH.Alarm.SCmd_Suppress,434826.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0114_2_TH.Alarm.SCmd_UnSuppress,434827.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0114_2_TH.Alarm.AEShelveTMRDN,434827.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0114_2_TH.Alarm.Bad,434827.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0114_2_TH.Alarm.Suppress,434828.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.UnSuppress,434828.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Shelve,434828.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.UnShelve,434828.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Enable,434828.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Disable,434828.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Ack,434828.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Reset,434828.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0114_2_TH.Alarm.Suppressed,434828.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0114_2_TH.Alarm.Shelved,434828.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0114_2_TH.Alarm.Disabled,434828.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0114_2_TH.Alarm.Acked,434828.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0114_2_TH.Alarm.Alarm,434828.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Fault,434838.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TE_0114_2_TH.almPLCFault.AlarmState,434838.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TE_0114_2_TH.almPLCFault.GlobalReset,434838.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TE_0114_2_TH.almPLCFault.FaultInAlarm,434838.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TE_0114_2_TH.almPLCFault.ALRM,434838.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TE_0114_2_TH.almPLCFault.ANUN,434838.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TE_0114_2_TH.almPLCFault.AKED,434838.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TE_0114_2_TH.almPLCFault.Resetable,434838.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TE_0114_2_TH.almPLCFault.REST,434838.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TE_0114_2_TH.almPLCFault.ACKN,434838.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TE_0114_2_TH.almPLCFault.UACK,434838.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TE_0114_2_TH.almPLCFault.MCmd_Enable,434838.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TE_0114_2_TH.almPLCFault.MCmd_Disable,434838.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TE_0114_2_TH.almPLCFault.OCmd_Shelve,434838.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TE_0114_2_TH.almPLCFault.OCmd_Unshelve,434838.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TE_0114_2_TH.almPLCFault.SCmd_Suppress,434838.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TE_0114_2_TH.almPLCFault.SCmd_UnSuppress,434839.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TE_0114_2_TH.almPLCFault.AEShelveTMRDN,434839.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TE_0114_2_TH.almPLCFault.Bad,434839.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TE_0114_2_TH.almPLCFault.Suppress,434840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.UnSuppress,434840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Shelve,434840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.UnShelve,434840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Enable,434840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Disable,434840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Ack,434840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Reset,434840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TE_0114_2_TH.almPLCFault.Suppressed,434840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TE_0114_2_TH.almPLCFault.Shelved,434840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TE_0114_2_TH.almPLCFault.Disabled,434840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TE_0114_2_TH.almPLCFault.Acked,434840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TE_0114_2_TH.almPLCFault.Alarm,434840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Fault,434862.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_LL.Alarm.AlarmState,434862.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_LL.Alarm.GlobalReset,434862.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_LL.Alarm.FaultInAlarm,434862.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_LL.Alarm.ALRM,434862.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_LL.Alarm.ANUN,434862.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_LL.Alarm.AKED,434862.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_LL.Alarm.Resetable,434862.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_LL.Alarm.REST,434862.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_LL.Alarm.ACKN,434862.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_LL.Alarm.UACK,434862.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_LL.Alarm.MCmd_Enable,434862.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_LL.Alarm.MCmd_Disable,434862.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_LL.Alarm.OCmd_Shelve,434862.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_LL.Alarm.OCmd_Unshelve,434862.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_LL.Alarm.SCmd_Suppress,434862.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_LL.Alarm.SCmd_UnSuppress,434863.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_LL.Alarm.AEShelveTMRDN,434863.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_LL.Alarm.Bad,434863.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_LL.Alarm.Suppress,434864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.UnSuppress,434864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Shelve,434864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.UnShelve,434864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Enable,434864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Disable,434864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Ack,434864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Reset,434864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_LL.Alarm.Suppressed,434864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_LL.Alarm.Shelved,434864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_LL.Alarm.Disabled,434864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_LL.Alarm.Acked,434864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_LL.Alarm.Alarm,434864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Fault,434874.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_LL.almPLCFault.AlarmState,434874.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_LL.almPLCFault.GlobalReset,434874.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_LL.almPLCFault.FaultInAlarm,434874.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_LL.almPLCFault.ALRM,434874.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_LL.almPLCFault.ANUN,434874.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_LL.almPLCFault.AKED,434874.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_LL.almPLCFault.Resetable,434874.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_LL.almPLCFault.REST,434874.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_LL.almPLCFault.ACKN,434874.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_LL.almPLCFault.UACK,434874.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_LL.almPLCFault.MCmd_Enable,434874.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_LL.almPLCFault.MCmd_Disable,434874.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_LL.almPLCFault.OCmd_Shelve,434874.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_LL.almPLCFault.OCmd_Unshelve,434874.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_LL.almPLCFault.SCmd_Suppress,434874.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_LL.almPLCFault.SCmd_UnSuppress,434875.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_LL.almPLCFault.AEShelveTMRDN,434875.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_LL.almPLCFault.Bad,434875.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_LL.almPLCFault.Suppress,434876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.UnSuppress,434876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Shelve,434876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.UnShelve,434876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Enable,434876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Disable,434876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Ack,434876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Reset,434876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Suppressed,434876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Shelved,434876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Disabled,434876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Acked,434876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_LL.almPLCFault.Alarm,434876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Fault,434896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_TH1.Alarm.AlarmState,434896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_TH1.Alarm.GlobalReset,434896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_TH1.Alarm.FaultInAlarm,434896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH1.Alarm.ALRM,434896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_TH1.Alarm.ANUN,434896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_TH1.Alarm.AKED,434896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_TH1.Alarm.Resetable,434896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_TH1.Alarm.REST,434896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_TH1.Alarm.ACKN,434896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_TH1.Alarm.UACK,434896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_TH1.Alarm.MCmd_Enable,434896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH1.Alarm.MCmd_Disable,434896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH1.Alarm.OCmd_Shelve,434896.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_TH1.Alarm.OCmd_Unshelve,434896.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_TH1.Alarm.SCmd_Suppress,434896.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_TH1.Alarm.SCmd_UnSuppress,434897.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_TH1.Alarm.AEShelveTMRDN,434897.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_TH1.Alarm.Bad,434897.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_TH1.Alarm.Suppress,434898.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.UnSuppress,434898.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Shelve,434898.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.UnShelve,434898.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Enable,434898.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Disable,434898.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Ack,434898.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Reset,434898.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_TH1.Alarm.Suppressed,434898.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_TH1.Alarm.Shelved,434898.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_TH1.Alarm.Disabled,434898.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_TH1.Alarm.Acked,434898.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_TH1.Alarm.Alarm,434898.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Fault,434908.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_TH1.almPLCFault.AlarmState,434908.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_TH1.almPLCFault.GlobalReset,434908.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_TH1.almPLCFault.FaultInAlarm,434908.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH1.almPLCFault.ALRM,434908.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_TH1.almPLCFault.ANUN,434908.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_TH1.almPLCFault.AKED,434908.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_TH1.almPLCFault.Resetable,434908.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_TH1.almPLCFault.REST,434908.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_TH1.almPLCFault.ACKN,434908.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_TH1.almPLCFault.UACK,434908.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_TH1.almPLCFault.MCmd_Enable,434908.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.MCmd_Disable,434908.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.OCmd_Shelve,434908.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.OCmd_Unshelve,434908.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.SCmd_Suppress,434908.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.SCmd_UnSuppress,434909.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_TH1.almPLCFault.AEShelveTMRDN,434909.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_TH1.almPLCFault.Bad,434909.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_TH1.almPLCFault.Suppress,434910.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.UnSuppress,434910.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Shelve,434910.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.UnShelve,434910.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Enable,434910.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Disable,434910.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Ack,434910.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Reset,434910.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Suppressed,434910.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Shelved,434910.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Disabled,434910.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Acked,434910.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_TH1.almPLCFault.Alarm,434910.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Fault,434932.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_TH2.Alarm.AlarmState,434932.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_TH2.Alarm.GlobalReset,434932.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_TH2.Alarm.FaultInAlarm,434932.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH2.Alarm.ALRM,434932.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_TH2.Alarm.ANUN,434932.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_TH2.Alarm.AKED,434932.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_TH2.Alarm.Resetable,434932.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_TH2.Alarm.REST,434932.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_TH2.Alarm.ACKN,434932.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_TH2.Alarm.UACK,434932.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_TH2.Alarm.MCmd_Enable,434932.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH2.Alarm.MCmd_Disable,434932.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH2.Alarm.OCmd_Shelve,434932.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_TH2.Alarm.OCmd_Unshelve,434932.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_TH2.Alarm.SCmd_Suppress,434932.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_TH2.Alarm.SCmd_UnSuppress,434933.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_TH2.Alarm.AEShelveTMRDN,434933.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_TH2.Alarm.Bad,434933.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_TH2.Alarm.Suppress,434934.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.UnSuppress,434934.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Shelve,434934.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.UnShelve,434934.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Enable,434934.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Disable,434934.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Ack,434934.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Reset,434934.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_TH2.Alarm.Suppressed,434934.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_TH2.Alarm.Shelved,434934.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_TH2.Alarm.Disabled,434934.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_TH2.Alarm.Acked,434934.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_TH2.Alarm.Alarm,434934.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Fault,434944.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_TH2.almPLCFault.AlarmState,434944.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_TH2.almPLCFault.GlobalReset,434944.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_TH2.almPLCFault.FaultInAlarm,434944.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_TH2.almPLCFault.ALRM,434944.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_TH2.almPLCFault.ANUN,434944.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_TH2.almPLCFault.AKED,434944.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_TH2.almPLCFault.Resetable,434944.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_TH2.almPLCFault.REST,434944.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_TH2.almPLCFault.ACKN,434944.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_TH2.almPLCFault.UACK,434944.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_TH2.almPLCFault.MCmd_Enable,434944.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.MCmd_Disable,434944.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.OCmd_Shelve,434944.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.OCmd_Unshelve,434944.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.SCmd_Suppress,434944.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.SCmd_UnSuppress,434945.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_TH2.almPLCFault.AEShelveTMRDN,434945.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_TH2.almPLCFault.Bad,434945.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_TH2.almPLCFault.Suppress,434946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.UnSuppress,434946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Shelve,434946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.UnShelve,434946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Enable,434946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Disable,434946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Ack,434946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Reset,434946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Suppressed,434946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Shelved,434946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Disabled,434946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Acked,434946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_TH2.almPLCFault.Alarm,434946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Fault,434966.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_XA.Alarm.AlarmState,434966.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_XA.Alarm.GlobalReset,434966.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_XA.Alarm.FaultInAlarm,434966.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_XA.Alarm.ALRM,434966.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_XA.Alarm.ANUN,434966.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_XA.Alarm.AKED,434966.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_XA.Alarm.Resetable,434966.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_XA.Alarm.REST,434966.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_XA.Alarm.ACKN,434966.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_XA.Alarm.UACK,434966.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_XA.Alarm.MCmd_Enable,434966.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_XA.Alarm.MCmd_Disable,434966.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_XA.Alarm.OCmd_Shelve,434966.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_XA.Alarm.OCmd_Unshelve,434966.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_XA.Alarm.SCmd_Suppress,434966.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_XA.Alarm.SCmd_UnSuppress,434967.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_XA.Alarm.AEShelveTMRDN,434967.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_XA.Alarm.Bad,434967.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_XA.Alarm.Suppress,434968.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.UnSuppress,434968.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Shelve,434968.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.UnShelve,434968.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Enable,434968.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Disable,434968.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Ack,434968.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Reset,434968.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_XA.Alarm.Suppressed,434968.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_XA.Alarm.Shelved,434968.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_XA.Alarm.Disabled,434968.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_XA.Alarm.Acked,434968.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_XA.Alarm.Alarm,434968.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Fault,434978.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_1_XA.almPLCFault.AlarmState,434978.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_1_XA.almPLCFault.GlobalReset,434978.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_1_XA.almPLCFault.FaultInAlarm,434978.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_1_XA.almPLCFault.ALRM,434978.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_1_XA.almPLCFault.ANUN,434978.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_1_XA.almPLCFault.AKED,434978.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_1_XA.almPLCFault.Resetable,434978.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_1_XA.almPLCFault.REST,434978.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_1_XA.almPLCFault.ACKN,434978.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_1_XA.almPLCFault.UACK,434978.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_1_XA.almPLCFault.MCmd_Enable,434978.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_1_XA.almPLCFault.MCmd_Disable,434978.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_1_XA.almPLCFault.OCmd_Shelve,434978.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_1_XA.almPLCFault.OCmd_Unshelve,434978.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_1_XA.almPLCFault.SCmd_Suppress,434978.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_1_XA.almPLCFault.SCmd_UnSuppress,434979.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_1_XA.almPLCFault.AEShelveTMRDN,434979.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_1_XA.almPLCFault.Bad,434979.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_1_XA.almPLCFault.Suppress,434980.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.UnSuppress,434980.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Shelve,434980.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.UnShelve,434980.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Enable,434980.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Disable,434980.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Ack,434980.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Reset,434980.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Suppressed,434980.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Shelved,434980.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Disabled,434980.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Acked,434980.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_1_XA.almPLCFault.Alarm,434980.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Fault,435002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_LL.Alarm.AlarmState,435002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_LL.Alarm.GlobalReset,435002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_LL.Alarm.FaultInAlarm,435002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_LL.Alarm.ALRM,435002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_LL.Alarm.ANUN,435002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_LL.Alarm.AKED,435002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_LL.Alarm.Resetable,435002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_LL.Alarm.REST,435002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_LL.Alarm.ACKN,435002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_LL.Alarm.UACK,435002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_LL.Alarm.MCmd_Enable,435002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_LL.Alarm.MCmd_Disable,435002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_LL.Alarm.OCmd_Shelve,435002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_LL.Alarm.OCmd_Unshelve,435002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_LL.Alarm.SCmd_Suppress,435002.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_LL.Alarm.SCmd_UnSuppress,435003.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_LL.Alarm.AEShelveTMRDN,435003.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_LL.Alarm.Bad,435003.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_LL.Alarm.Suppress,435004.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.UnSuppress,435004.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Shelve,435004.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.UnShelve,435004.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Enable,435004.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Disable,435004.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Ack,435004.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Reset,435004.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_LL.Alarm.Suppressed,435004.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_LL.Alarm.Shelved,435004.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_LL.Alarm.Disabled,435004.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_LL.Alarm.Acked,435004.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_LL.Alarm.Alarm,435004.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Fault,435014.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_LL.almPLCFault.AlarmState,435014.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_LL.almPLCFault.GlobalReset,435014.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_LL.almPLCFault.FaultInAlarm,435014.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_LL.almPLCFault.ALRM,435014.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_LL.almPLCFault.ANUN,435014.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_LL.almPLCFault.AKED,435014.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_LL.almPLCFault.Resetable,435014.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_LL.almPLCFault.REST,435014.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_LL.almPLCFault.ACKN,435014.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_LL.almPLCFault.UACK,435014.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_LL.almPLCFault.MCmd_Enable,435014.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_LL.almPLCFault.MCmd_Disable,435014.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_LL.almPLCFault.OCmd_Shelve,435014.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_LL.almPLCFault.OCmd_Unshelve,435014.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_LL.almPLCFault.SCmd_Suppress,435014.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_LL.almPLCFault.SCmd_UnSuppress,435015.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_LL.almPLCFault.AEShelveTMRDN,435015.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_LL.almPLCFault.Bad,435015.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_LL.almPLCFault.Suppress,435016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.UnSuppress,435016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Shelve,435016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.UnShelve,435016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Enable,435016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Disable,435016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Ack,435016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Reset,435016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Suppressed,435016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Shelved,435016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Disabled,435016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Acked,435016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_LL.almPLCFault.Alarm,435016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Fault,435036.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_TH1.Alarm.AlarmState,435036.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_TH1.Alarm.GlobalReset,435036.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_TH1.Alarm.FaultInAlarm,435036.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH1.Alarm.ALRM,435036.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_TH1.Alarm.ANUN,435036.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_TH1.Alarm.AKED,435036.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_TH1.Alarm.Resetable,435036.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_TH1.Alarm.REST,435036.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_TH1.Alarm.ACKN,435036.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_TH1.Alarm.UACK,435036.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_TH1.Alarm.MCmd_Enable,435036.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH1.Alarm.MCmd_Disable,435036.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH1.Alarm.OCmd_Shelve,435036.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_TH1.Alarm.OCmd_Unshelve,435036.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_TH1.Alarm.SCmd_Suppress,435036.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_TH1.Alarm.SCmd_UnSuppress,435037.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_TH1.Alarm.AEShelveTMRDN,435037.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_TH1.Alarm.Bad,435037.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_TH1.Alarm.Suppress,435038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.UnSuppress,435038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Shelve,435038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.UnShelve,435038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Enable,435038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Disable,435038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Ack,435038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Reset,435038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_TH1.Alarm.Suppressed,435038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_TH1.Alarm.Shelved,435038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_TH1.Alarm.Disabled,435038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_TH1.Alarm.Acked,435038.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_TH1.Alarm.Alarm,435038.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Fault,435048.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_TH1.almPLCFault.AlarmState,435048.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_TH1.almPLCFault.GlobalReset,435048.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_TH1.almPLCFault.FaultInAlarm,435048.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH1.almPLCFault.ALRM,435048.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_TH1.almPLCFault.ANUN,435048.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_TH1.almPLCFault.AKED,435048.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_TH1.almPLCFault.Resetable,435048.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_TH1.almPLCFault.REST,435048.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_TH1.almPLCFault.ACKN,435048.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_TH1.almPLCFault.UACK,435048.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_TH1.almPLCFault.MCmd_Enable,435048.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.MCmd_Disable,435048.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.OCmd_Shelve,435048.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.OCmd_Unshelve,435048.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.SCmd_Suppress,435048.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.SCmd_UnSuppress,435049.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_TH1.almPLCFault.AEShelveTMRDN,435049.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_TH1.almPLCFault.Bad,435049.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_TH1.almPLCFault.Suppress,435050.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.UnSuppress,435050.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Shelve,435050.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.UnShelve,435050.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Enable,435050.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Disable,435050.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Ack,435050.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Reset,435050.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Suppressed,435050.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Shelved,435050.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Disabled,435050.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Acked,435050.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_TH1.almPLCFault.Alarm,435050.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Fault,435072.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_TH2.Alarm.AlarmState,435072.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_TH2.Alarm.GlobalReset,435072.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_TH2.Alarm.FaultInAlarm,435072.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH2.Alarm.ALRM,435072.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_TH2.Alarm.ANUN,435072.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_TH2.Alarm.AKED,435072.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_TH2.Alarm.Resetable,435072.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_TH2.Alarm.REST,435072.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_TH2.Alarm.ACKN,435072.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_TH2.Alarm.UACK,435072.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_TH2.Alarm.MCmd_Enable,435072.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH2.Alarm.MCmd_Disable,435072.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH2.Alarm.OCmd_Shelve,435072.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_TH2.Alarm.OCmd_Unshelve,435072.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_TH2.Alarm.SCmd_Suppress,435072.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_TH2.Alarm.SCmd_UnSuppress,435073.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_TH2.Alarm.AEShelveTMRDN,435073.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_TH2.Alarm.Bad,435073.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_TH2.Alarm.Suppress,435074.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.UnSuppress,435074.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Shelve,435074.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.UnShelve,435074.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Enable,435074.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Disable,435074.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Ack,435074.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Reset,435074.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_TH2.Alarm.Suppressed,435074.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_TH2.Alarm.Shelved,435074.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_TH2.Alarm.Disabled,435074.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_TH2.Alarm.Acked,435074.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_TH2.Alarm.Alarm,435074.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Fault,435084.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_TH2.almPLCFault.AlarmState,435084.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_TH2.almPLCFault.GlobalReset,435084.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_TH2.almPLCFault.FaultInAlarm,435084.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_TH2.almPLCFault.ALRM,435084.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_TH2.almPLCFault.ANUN,435084.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_TH2.almPLCFault.AKED,435084.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_TH2.almPLCFault.Resetable,435084.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_TH2.almPLCFault.REST,435084.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_TH2.almPLCFault.ACKN,435084.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_TH2.almPLCFault.UACK,435084.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_TH2.almPLCFault.MCmd_Enable,435084.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.MCmd_Disable,435084.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.OCmd_Shelve,435084.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.OCmd_Unshelve,435084.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.SCmd_Suppress,435084.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.SCmd_UnSuppress,435085.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_TH2.almPLCFault.AEShelveTMRDN,435085.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_TH2.almPLCFault.Bad,435085.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_TH2.almPLCFault.Suppress,435086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.UnSuppress,435086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Shelve,435086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.UnShelve,435086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Enable,435086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Disable,435086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Ack,435086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Reset,435086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Suppressed,435086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Shelved,435086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Disabled,435086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Acked,435086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_TH2.almPLCFault.Alarm,435086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Fault,435106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_XA.Alarm.AlarmState,435106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_XA.Alarm.GlobalReset,435106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_XA.Alarm.FaultInAlarm,435106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_XA.Alarm.ALRM,435106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_XA.Alarm.ANUN,435106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_XA.Alarm.AKED,435106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_XA.Alarm.Resetable,435106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_XA.Alarm.REST,435106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_XA.Alarm.ACKN,435106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_XA.Alarm.UACK,435106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_XA.Alarm.MCmd_Enable,435106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_XA.Alarm.MCmd_Disable,435106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_XA.Alarm.OCmd_Shelve,435106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_XA.Alarm.OCmd_Unshelve,435106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_XA.Alarm.SCmd_Suppress,435106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_XA.Alarm.SCmd_UnSuppress,435107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_XA.Alarm.AEShelveTMRDN,435107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_XA.Alarm.Bad,435107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_XA.Alarm.Suppress,435108.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.UnSuppress,435108.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Shelve,435108.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.UnShelve,435108.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Enable,435108.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Disable,435108.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Ack,435108.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Reset,435108.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_XA.Alarm.Suppressed,435108.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_XA.Alarm.Shelved,435108.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_XA.Alarm.Disabled,435108.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_XA.Alarm.Acked,435108.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_XA.Alarm.Alarm,435108.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Fault,435118.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_TFR_0131_2_XA.almPLCFault.AlarmState,435118.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_TFR_0131_2_XA.almPLCFault.GlobalReset,435118.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_TFR_0131_2_XA.almPLCFault.FaultInAlarm,435118.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_TFR_0131_2_XA.almPLCFault.ALRM,435118.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_TFR_0131_2_XA.almPLCFault.ANUN,435118.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_TFR_0131_2_XA.almPLCFault.AKED,435118.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_TFR_0131_2_XA.almPLCFault.Resetable,435118.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_TFR_0131_2_XA.almPLCFault.REST,435118.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_TFR_0131_2_XA.almPLCFault.ACKN,435118.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_TFR_0131_2_XA.almPLCFault.UACK,435118.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_TFR_0131_2_XA.almPLCFault.MCmd_Enable,435118.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_TFR_0131_2_XA.almPLCFault.MCmd_Disable,435118.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_TFR_0131_2_XA.almPLCFault.OCmd_Shelve,435118.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_TFR_0131_2_XA.almPLCFault.OCmd_Unshelve,435118.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_TFR_0131_2_XA.almPLCFault.SCmd_Suppress,435118.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_TFR_0131_2_XA.almPLCFault.SCmd_UnSuppress,435119.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_TFR_0131_2_XA.almPLCFault.AEShelveTMRDN,435119.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_TFR_0131_2_XA.almPLCFault.Bad,435119.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_TFR_0131_2_XA.almPLCFault.Suppress,435120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.UnSuppress,435120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Shelve,435120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.UnShelve,435120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Enable,435120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Disable,435120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Ack,435120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Reset,435120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Suppressed,435120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Shelved,435120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Disabled,435120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Acked,435120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_TFR_0131_2_XA.almPLCFault.Alarm,435120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Fault,435142.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_1_JA.Alarm.AlarmState,435142.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_1_JA.Alarm.GlobalReset,435142.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_1_JA.Alarm.FaultInAlarm,435142.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_JA.Alarm.ALRM,435142.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_1_JA.Alarm.ANUN,435142.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_1_JA.Alarm.AKED,435142.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_1_JA.Alarm.Resetable,435142.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_1_JA.Alarm.REST,435142.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_1_JA.Alarm.ACKN,435142.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_1_JA.Alarm.UACK,435142.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_1_JA.Alarm.MCmd_Enable,435142.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_JA.Alarm.MCmd_Disable,435142.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_JA.Alarm.OCmd_Shelve,435142.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_1_JA.Alarm.OCmd_Unshelve,435142.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_1_JA.Alarm.SCmd_Suppress,435142.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_1_JA.Alarm.SCmd_UnSuppress,435143.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_1_JA.Alarm.AEShelveTMRDN,435143.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_1_JA.Alarm.Bad,435143.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_1_JA.Alarm.Suppress,435144.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.UnSuppress,435144.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Shelve,435144.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.UnShelve,435144.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Enable,435144.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Disable,435144.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Ack,435144.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Reset,435144.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_1_JA.Alarm.Suppressed,435144.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_1_JA.Alarm.Shelved,435144.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_1_JA.Alarm.Disabled,435144.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_1_JA.Alarm.Acked,435144.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_1_JA.Alarm.Alarm,435144.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Fault,435154.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_1_JA.almPLCFault.AlarmState,435154.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_1_JA.almPLCFault.GlobalReset,435154.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_1_JA.almPLCFault.FaultInAlarm,435154.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_JA.almPLCFault.ALRM,435154.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_1_JA.almPLCFault.ANUN,435154.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_1_JA.almPLCFault.AKED,435154.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_1_JA.almPLCFault.Resetable,435154.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_1_JA.almPLCFault.REST,435154.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_1_JA.almPLCFault.ACKN,435154.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_1_JA.almPLCFault.UACK,435154.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_1_JA.almPLCFault.MCmd_Enable,435154.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_JA.almPLCFault.MCmd_Disable,435154.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_JA.almPLCFault.OCmd_Shelve,435154.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_1_JA.almPLCFault.OCmd_Unshelve,435154.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_1_JA.almPLCFault.SCmd_Suppress,435154.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_1_JA.almPLCFault.SCmd_UnSuppress,435155.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_1_JA.almPLCFault.AEShelveTMRDN,435155.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_1_JA.almPLCFault.Bad,435155.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_1_JA.almPLCFault.Suppress,435156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.UnSuppress,435156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Shelve,435156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.UnShelve,435156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Enable,435156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Disable,435156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Ack,435156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Reset,435156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_1_JA.almPLCFault.Suppressed,435156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_1_JA.almPLCFault.Shelved,435156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_1_JA.almPLCFault.Disabled,435156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_1_JA.almPLCFault.Acked,435156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_1_JA.almPLCFault.Alarm,435156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Fault,435176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_1_ZS.Alarm.AlarmState,435176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_1_ZS.Alarm.GlobalReset,435176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_1_ZS.Alarm.FaultInAlarm,435176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_ZS.Alarm.ALRM,435176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_1_ZS.Alarm.ANUN,435176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_1_ZS.Alarm.AKED,435176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_1_ZS.Alarm.Resetable,435176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_1_ZS.Alarm.REST,435176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_1_ZS.Alarm.ACKN,435176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_1_ZS.Alarm.UACK,435176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_1_ZS.Alarm.MCmd_Enable,435176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_ZS.Alarm.MCmd_Disable,435176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_ZS.Alarm.OCmd_Shelve,435176.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_1_ZS.Alarm.OCmd_Unshelve,435176.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_1_ZS.Alarm.SCmd_Suppress,435176.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_1_ZS.Alarm.SCmd_UnSuppress,435177.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_1_ZS.Alarm.AEShelveTMRDN,435177.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_1_ZS.Alarm.Bad,435177.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_1_ZS.Alarm.Suppress,435178.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.UnSuppress,435178.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Shelve,435178.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.UnShelve,435178.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Enable,435178.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Disable,435178.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Ack,435178.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Reset,435178.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_1_ZS.Alarm.Suppressed,435178.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_1_ZS.Alarm.Shelved,435178.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_1_ZS.Alarm.Disabled,435178.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_1_ZS.Alarm.Acked,435178.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_1_ZS.Alarm.Alarm,435178.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Fault,435188.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_1_ZS.almPLCFault.AlarmState,435188.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_1_ZS.almPLCFault.GlobalReset,435188.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_1_ZS.almPLCFault.FaultInAlarm,435188.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_1_ZS.almPLCFault.ALRM,435188.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_1_ZS.almPLCFault.ANUN,435188.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_1_ZS.almPLCFault.AKED,435188.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_1_ZS.almPLCFault.Resetable,435188.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_1_ZS.almPLCFault.REST,435188.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_1_ZS.almPLCFault.ACKN,435188.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_1_ZS.almPLCFault.UACK,435188.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_1_ZS.almPLCFault.MCmd_Enable,435188.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_1_ZS.almPLCFault.MCmd_Disable,435188.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_1_ZS.almPLCFault.OCmd_Shelve,435188.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_1_ZS.almPLCFault.OCmd_Unshelve,435188.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_1_ZS.almPLCFault.SCmd_Suppress,435188.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_1_ZS.almPLCFault.SCmd_UnSuppress,435189.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_1_ZS.almPLCFault.AEShelveTMRDN,435189.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_1_ZS.almPLCFault.Bad,435189.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_1_ZS.almPLCFault.Suppress,435190.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.UnSuppress,435190.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Shelve,435190.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.UnShelve,435190.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Enable,435190.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Disable,435190.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Ack,435190.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Reset,435190.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Suppressed,435190.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Shelved,435190.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Disabled,435190.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Acked,435190.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_1_ZS.almPLCFault.Alarm,435190.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Fault,435212.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_2_JA.Alarm.AlarmState,435212.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_2_JA.Alarm.GlobalReset,435212.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_2_JA.Alarm.FaultInAlarm,435212.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_JA.Alarm.ALRM,435212.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_2_JA.Alarm.ANUN,435212.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_2_JA.Alarm.AKED,435212.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_2_JA.Alarm.Resetable,435212.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_2_JA.Alarm.REST,435212.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_2_JA.Alarm.ACKN,435212.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_2_JA.Alarm.UACK,435212.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_2_JA.Alarm.MCmd_Enable,435212.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_JA.Alarm.MCmd_Disable,435212.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_JA.Alarm.OCmd_Shelve,435212.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_2_JA.Alarm.OCmd_Unshelve,435212.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_2_JA.Alarm.SCmd_Suppress,435212.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_2_JA.Alarm.SCmd_UnSuppress,435213.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_2_JA.Alarm.AEShelveTMRDN,435213.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_2_JA.Alarm.Bad,435213.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_2_JA.Alarm.Suppress,435214.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.UnSuppress,435214.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Shelve,435214.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.UnShelve,435214.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Enable,435214.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Disable,435214.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Ack,435214.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Reset,435214.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_2_JA.Alarm.Suppressed,435214.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_2_JA.Alarm.Shelved,435214.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_2_JA.Alarm.Disabled,435214.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_2_JA.Alarm.Acked,435214.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_2_JA.Alarm.Alarm,435214.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Fault,435224.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_2_JA.almPLCFault.AlarmState,435224.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_2_JA.almPLCFault.GlobalReset,435224.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_2_JA.almPLCFault.FaultInAlarm,435224.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_JA.almPLCFault.ALRM,435224.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_2_JA.almPLCFault.ANUN,435224.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_2_JA.almPLCFault.AKED,435224.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_2_JA.almPLCFault.Resetable,435224.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_2_JA.almPLCFault.REST,435224.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_2_JA.almPLCFault.ACKN,435224.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_2_JA.almPLCFault.UACK,435224.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_2_JA.almPLCFault.MCmd_Enable,435224.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_JA.almPLCFault.MCmd_Disable,435224.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_JA.almPLCFault.OCmd_Shelve,435224.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_2_JA.almPLCFault.OCmd_Unshelve,435224.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_2_JA.almPLCFault.SCmd_Suppress,435224.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_2_JA.almPLCFault.SCmd_UnSuppress,435225.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_2_JA.almPLCFault.AEShelveTMRDN,435225.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_2_JA.almPLCFault.Bad,435225.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_2_JA.almPLCFault.Suppress,435226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.UnSuppress,435226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Shelve,435226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.UnShelve,435226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Enable,435226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Disable,435226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Ack,435226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Reset,435226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_2_JA.almPLCFault.Suppressed,435226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_2_JA.almPLCFault.Shelved,435226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_2_JA.almPLCFault.Disabled,435226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_2_JA.almPLCFault.Acked,435226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_2_JA.almPLCFault.Alarm,435226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Fault,435246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_2_ZS.Alarm.AlarmState,435246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_2_ZS.Alarm.GlobalReset,435246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_2_ZS.Alarm.FaultInAlarm,435246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_ZS.Alarm.ALRM,435246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_2_ZS.Alarm.ANUN,435246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_2_ZS.Alarm.AKED,435246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_2_ZS.Alarm.Resetable,435246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_2_ZS.Alarm.REST,435246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_2_ZS.Alarm.ACKN,435246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_2_ZS.Alarm.UACK,435246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_2_ZS.Alarm.MCmd_Enable,435246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_ZS.Alarm.MCmd_Disable,435246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_ZS.Alarm.OCmd_Shelve,435246.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_2_ZS.Alarm.OCmd_Unshelve,435246.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_2_ZS.Alarm.SCmd_Suppress,435246.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_2_ZS.Alarm.SCmd_UnSuppress,435247.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_2_ZS.Alarm.AEShelveTMRDN,435247.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_2_ZS.Alarm.Bad,435247.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_2_ZS.Alarm.Suppress,435248.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.UnSuppress,435248.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Shelve,435248.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.UnShelve,435248.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Enable,435248.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Disable,435248.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Ack,435248.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Reset,435248.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_2_ZS.Alarm.Suppressed,435248.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_2_ZS.Alarm.Shelved,435248.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_2_ZS.Alarm.Disabled,435248.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_2_ZS.Alarm.Acked,435248.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_2_ZS.Alarm.Alarm,435248.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Fault,435258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_UPS_001_2_ZS.almPLCFault.AlarmState,435258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_UPS_001_2_ZS.almPLCFault.GlobalReset,435258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_UPS_001_2_ZS.almPLCFault.FaultInAlarm,435258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_UPS_001_2_ZS.almPLCFault.ALRM,435258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_UPS_001_2_ZS.almPLCFault.ANUN,435258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_UPS_001_2_ZS.almPLCFault.AKED,435258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_UPS_001_2_ZS.almPLCFault.Resetable,435258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_UPS_001_2_ZS.almPLCFault.REST,435258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_UPS_001_2_ZS.almPLCFault.ACKN,435258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_UPS_001_2_ZS.almPLCFault.UACK,435258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_UPS_001_2_ZS.almPLCFault.MCmd_Enable,435258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_UPS_001_2_ZS.almPLCFault.MCmd_Disable,435258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_UPS_001_2_ZS.almPLCFault.OCmd_Shelve,435258.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_UPS_001_2_ZS.almPLCFault.OCmd_Unshelve,435258.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_UPS_001_2_ZS.almPLCFault.SCmd_Suppress,435258.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_UPS_001_2_ZS.almPLCFault.SCmd_UnSuppress,435259.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_UPS_001_2_ZS.almPLCFault.AEShelveTMRDN,435259.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_UPS_001_2_ZS.almPLCFault.Bad,435259.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_UPS_001_2_ZS.almPLCFault.Suppress,435260.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.UnSuppress,435260.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Shelve,435260.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.UnShelve,435260.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Enable,435260.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Disable,435260.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Ack,435260.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Reset,435260.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Suppressed,435260.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Shelved,435260.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Disabled,435260.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Acked,435260.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_UPS_001_2_ZS.almPLCFault.Alarm,435260.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Fault,435282.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0112_1A_ZA.Alarm.AlarmState,435282.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0112_1A_ZA.Alarm.GlobalReset,435282.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0112_1A_ZA.Alarm.FaultInAlarm,435282.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0112_1A_ZA.Alarm.ALRM,435282.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0112_1A_ZA.Alarm.ANUN,435282.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0112_1A_ZA.Alarm.AKED,435282.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0112_1A_ZA.Alarm.Resetable,435282.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0112_1A_ZA.Alarm.REST,435282.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0112_1A_ZA.Alarm.ACKN,435282.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0112_1A_ZA.Alarm.UACK,435282.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0112_1A_ZA.Alarm.MCmd_Enable,435282.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0112_1A_ZA.Alarm.MCmd_Disable,435282.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0112_1A_ZA.Alarm.OCmd_Shelve,435282.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0112_1A_ZA.Alarm.OCmd_Unshelve,435282.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0112_1A_ZA.Alarm.SCmd_Suppress,435282.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0112_1A_ZA.Alarm.SCmd_UnSuppress,435283.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0112_1A_ZA.Alarm.AEShelveTMRDN,435283.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0112_1A_ZA.Alarm.Bad,435283.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0112_1A_ZA.Alarm.Suppress,435284.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.UnSuppress,435284.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Shelve,435284.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.UnShelve,435284.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Enable,435284.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Disable,435284.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Ack,435284.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Reset,435284.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0112_1A_ZA.Alarm.Suppressed,435284.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0112_1A_ZA.Alarm.Shelved,435284.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0112_1A_ZA.Alarm.Disabled,435284.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0112_1A_ZA.Alarm.Acked,435284.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0112_1A_ZA.Alarm.Alarm,435284.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Fault,435294.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0112_1A_ZA.almPLCFault.AlarmState,435294.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0112_1A_ZA.almPLCFault.GlobalReset,435294.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0112_1A_ZA.almPLCFault.FaultInAlarm,435294.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0112_1A_ZA.almPLCFault.ALRM,435294.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0112_1A_ZA.almPLCFault.ANUN,435294.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0112_1A_ZA.almPLCFault.AKED,435294.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0112_1A_ZA.almPLCFault.Resetable,435294.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0112_1A_ZA.almPLCFault.REST,435294.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0112_1A_ZA.almPLCFault.ACKN,435294.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0112_1A_ZA.almPLCFault.UACK,435294.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0112_1A_ZA.almPLCFault.MCmd_Enable,435294.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.MCmd_Disable,435294.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.OCmd_Shelve,435294.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.OCmd_Unshelve,435294.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.SCmd_Suppress,435294.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.SCmd_UnSuppress,435295.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0112_1A_ZA.almPLCFault.AEShelveTMRDN,435295.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0112_1A_ZA.almPLCFault.Bad,435295.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0112_1A_ZA.almPLCFault.Suppress,435296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.UnSuppress,435296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Shelve,435296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.UnShelve,435296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Enable,435296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Disable,435296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Ack,435296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Reset,435296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Suppressed,435296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Shelved,435296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Disabled,435296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Acked,435296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0112_1A_ZA.almPLCFault.Alarm,435296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Fault,435316.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_1A_ZA.Alarm.AlarmState,435316.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_1A_ZA.Alarm.GlobalReset,435316.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_1A_ZA.Alarm.FaultInAlarm,435316.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1A_ZA.Alarm.ALRM,435316.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_1A_ZA.Alarm.ANUN,435316.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_1A_ZA.Alarm.AKED,435316.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_1A_ZA.Alarm.Resetable,435316.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_1A_ZA.Alarm.REST,435316.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_1A_ZA.Alarm.ACKN,435316.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_1A_ZA.Alarm.UACK,435316.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_1A_ZA.Alarm.MCmd_Enable,435316.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1A_ZA.Alarm.MCmd_Disable,435316.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1A_ZA.Alarm.OCmd_Shelve,435316.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_1A_ZA.Alarm.OCmd_Unshelve,435316.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_1A_ZA.Alarm.SCmd_Suppress,435316.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_1A_ZA.Alarm.SCmd_UnSuppress,435317.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_1A_ZA.Alarm.AEShelveTMRDN,435317.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_1A_ZA.Alarm.Bad,435317.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_1A_ZA.Alarm.Suppress,435318.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.UnSuppress,435318.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Shelve,435318.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.UnShelve,435318.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Enable,435318.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Disable,435318.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Ack,435318.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Reset,435318.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_1A_ZA.Alarm.Suppressed,435318.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_1A_ZA.Alarm.Shelved,435318.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_1A_ZA.Alarm.Disabled,435318.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_1A_ZA.Alarm.Acked,435318.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_1A_ZA.Alarm.Alarm,435318.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Fault,435328.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_1A_ZA.almPLCFault.AlarmState,435328.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_1A_ZA.almPLCFault.GlobalReset,435328.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_1A_ZA.almPLCFault.FaultInAlarm,435328.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1A_ZA.almPLCFault.ALRM,435328.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_1A_ZA.almPLCFault.ANUN,435328.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_1A_ZA.almPLCFault.AKED,435328.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_1A_ZA.almPLCFault.Resetable,435328.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_1A_ZA.almPLCFault.REST,435328.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_1A_ZA.almPLCFault.ACKN,435328.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_1A_ZA.almPLCFault.UACK,435328.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_1A_ZA.almPLCFault.MCmd_Enable,435328.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.MCmd_Disable,435328.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.OCmd_Shelve,435328.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.OCmd_Unshelve,435328.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.SCmd_Suppress,435328.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.SCmd_UnSuppress,435329.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_1A_ZA.almPLCFault.AEShelveTMRDN,435329.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_1A_ZA.almPLCFault.Bad,435329.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_1A_ZA.almPLCFault.Suppress,435330.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.UnSuppress,435330.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Shelve,435330.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.UnShelve,435330.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Enable,435330.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Disable,435330.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Ack,435330.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Reset,435330.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Suppressed,435330.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Shelved,435330.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Disabled,435330.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Acked,435330.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_1A_ZA.almPLCFault.Alarm,435330.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Fault,435352.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_1B_ZA.Alarm.AlarmState,435352.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_1B_ZA.Alarm.GlobalReset,435352.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_1B_ZA.Alarm.FaultInAlarm,435352.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1B_ZA.Alarm.ALRM,435352.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_1B_ZA.Alarm.ANUN,435352.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_1B_ZA.Alarm.AKED,435352.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_1B_ZA.Alarm.Resetable,435352.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_1B_ZA.Alarm.REST,435352.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_1B_ZA.Alarm.ACKN,435352.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_1B_ZA.Alarm.UACK,435352.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_1B_ZA.Alarm.MCmd_Enable,435352.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1B_ZA.Alarm.MCmd_Disable,435352.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1B_ZA.Alarm.OCmd_Shelve,435352.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_1B_ZA.Alarm.OCmd_Unshelve,435352.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_1B_ZA.Alarm.SCmd_Suppress,435352.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_1B_ZA.Alarm.SCmd_UnSuppress,435353.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_1B_ZA.Alarm.AEShelveTMRDN,435353.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_1B_ZA.Alarm.Bad,435353.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_1B_ZA.Alarm.Suppress,435354.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.UnSuppress,435354.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Shelve,435354.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.UnShelve,435354.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Enable,435354.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Disable,435354.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Ack,435354.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Reset,435354.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_1B_ZA.Alarm.Suppressed,435354.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_1B_ZA.Alarm.Shelved,435354.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_1B_ZA.Alarm.Disabled,435354.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_1B_ZA.Alarm.Acked,435354.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_1B_ZA.Alarm.Alarm,435354.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Fault,435364.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_1B_ZA.almPLCFault.AlarmState,435364.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_1B_ZA.almPLCFault.GlobalReset,435364.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_1B_ZA.almPLCFault.FaultInAlarm,435364.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_1B_ZA.almPLCFault.ALRM,435364.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_1B_ZA.almPLCFault.ANUN,435364.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_1B_ZA.almPLCFault.AKED,435364.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_1B_ZA.almPLCFault.Resetable,435364.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_1B_ZA.almPLCFault.REST,435364.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_1B_ZA.almPLCFault.ACKN,435364.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_1B_ZA.almPLCFault.UACK,435364.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_1B_ZA.almPLCFault.MCmd_Enable,435364.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.MCmd_Disable,435364.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.OCmd_Shelve,435364.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.OCmd_Unshelve,435364.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.SCmd_Suppress,435364.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.SCmd_UnSuppress,435365.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_1B_ZA.almPLCFault.AEShelveTMRDN,435365.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_1B_ZA.almPLCFault.Bad,435365.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_1B_ZA.almPLCFault.Suppress,435366.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.UnSuppress,435366.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Shelve,435366.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.UnShelve,435366.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Enable,435366.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Disable,435366.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Ack,435366.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Reset,435366.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Suppressed,435366.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Shelved,435366.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Disabled,435366.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Acked,435366.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_1B_ZA.almPLCFault.Alarm,435366.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Fault,435386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_2A_ZA.Alarm.AlarmState,435386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_2A_ZA.Alarm.GlobalReset,435386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_2A_ZA.Alarm.FaultInAlarm,435386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2A_ZA.Alarm.ALRM,435386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_2A_ZA.Alarm.ANUN,435386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_2A_ZA.Alarm.AKED,435386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_2A_ZA.Alarm.Resetable,435386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_2A_ZA.Alarm.REST,435386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_2A_ZA.Alarm.ACKN,435386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_2A_ZA.Alarm.UACK,435386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_2A_ZA.Alarm.MCmd_Enable,435386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2A_ZA.Alarm.MCmd_Disable,435386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2A_ZA.Alarm.OCmd_Shelve,435386.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_2A_ZA.Alarm.OCmd_Unshelve,435386.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_2A_ZA.Alarm.SCmd_Suppress,435386.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_2A_ZA.Alarm.SCmd_UnSuppress,435387.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_2A_ZA.Alarm.AEShelveTMRDN,435387.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_2A_ZA.Alarm.Bad,435387.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_2A_ZA.Alarm.Suppress,435388.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.UnSuppress,435388.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Shelve,435388.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.UnShelve,435388.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Enable,435388.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Disable,435388.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Ack,435388.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Reset,435388.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_2A_ZA.Alarm.Suppressed,435388.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_2A_ZA.Alarm.Shelved,435388.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_2A_ZA.Alarm.Disabled,435388.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_2A_ZA.Alarm.Acked,435388.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_2A_ZA.Alarm.Alarm,435388.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Fault,435398.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_2A_ZA.almPLCFault.AlarmState,435398.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_2A_ZA.almPLCFault.GlobalReset,435398.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_2A_ZA.almPLCFault.FaultInAlarm,435398.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2A_ZA.almPLCFault.ALRM,435398.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_2A_ZA.almPLCFault.ANUN,435398.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_2A_ZA.almPLCFault.AKED,435398.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_2A_ZA.almPLCFault.Resetable,435398.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_2A_ZA.almPLCFault.REST,435398.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_2A_ZA.almPLCFault.ACKN,435398.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_2A_ZA.almPLCFault.UACK,435398.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_2A_ZA.almPLCFault.MCmd_Enable,435398.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.MCmd_Disable,435398.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.OCmd_Shelve,435398.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.OCmd_Unshelve,435398.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.SCmd_Suppress,435398.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.SCmd_UnSuppress,435399.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_2A_ZA.almPLCFault.AEShelveTMRDN,435399.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_2A_ZA.almPLCFault.Bad,435399.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_2A_ZA.almPLCFault.Suppress,435400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.UnSuppress,435400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Shelve,435400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.UnShelve,435400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Enable,435400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Disable,435400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Ack,435400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Reset,435400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Suppressed,435400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Shelved,435400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Disabled,435400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Acked,435400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_2A_ZA.almPLCFault.Alarm,435400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Fault,435422.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_2B_ZA.Alarm.AlarmState,435422.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_2B_ZA.Alarm.GlobalReset,435422.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_2B_ZA.Alarm.FaultInAlarm,435422.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2B_ZA.Alarm.ALRM,435422.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_2B_ZA.Alarm.ANUN,435422.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_2B_ZA.Alarm.AKED,435422.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_2B_ZA.Alarm.Resetable,435422.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_2B_ZA.Alarm.REST,435422.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_2B_ZA.Alarm.ACKN,435422.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_2B_ZA.Alarm.UACK,435422.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_2B_ZA.Alarm.MCmd_Enable,435422.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2B_ZA.Alarm.MCmd_Disable,435422.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2B_ZA.Alarm.OCmd_Shelve,435422.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_2B_ZA.Alarm.OCmd_Unshelve,435422.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_2B_ZA.Alarm.SCmd_Suppress,435422.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_2B_ZA.Alarm.SCmd_UnSuppress,435423.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_2B_ZA.Alarm.AEShelveTMRDN,435423.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_2B_ZA.Alarm.Bad,435423.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_2B_ZA.Alarm.Suppress,435424.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.UnSuppress,435424.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Shelve,435424.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.UnShelve,435424.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Enable,435424.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Disable,435424.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Ack,435424.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Reset,435424.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_2B_ZA.Alarm.Suppressed,435424.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_2B_ZA.Alarm.Shelved,435424.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_2B_ZA.Alarm.Disabled,435424.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_2B_ZA.Alarm.Acked,435424.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_2B_ZA.Alarm.Alarm,435424.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Fault,435434.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XE_0113_2B_ZA.almPLCFault.AlarmState,435434.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XE_0113_2B_ZA.almPLCFault.GlobalReset,435434.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XE_0113_2B_ZA.almPLCFault.FaultInAlarm,435434.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XE_0113_2B_ZA.almPLCFault.ALRM,435434.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XE_0113_2B_ZA.almPLCFault.ANUN,435434.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XE_0113_2B_ZA.almPLCFault.AKED,435434.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XE_0113_2B_ZA.almPLCFault.Resetable,435434.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XE_0113_2B_ZA.almPLCFault.REST,435434.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XE_0113_2B_ZA.almPLCFault.ACKN,435434.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XE_0113_2B_ZA.almPLCFault.UACK,435434.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XE_0113_2B_ZA.almPLCFault.MCmd_Enable,435434.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.MCmd_Disable,435434.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.OCmd_Shelve,435434.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.OCmd_Unshelve,435434.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.SCmd_Suppress,435434.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.SCmd_UnSuppress,435435.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XE_0113_2B_ZA.almPLCFault.AEShelveTMRDN,435435.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XE_0113_2B_ZA.almPLCFault.Bad,435435.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XE_0113_2B_ZA.almPLCFault.Suppress,435436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.UnSuppress,435436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Shelve,435436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.UnShelve,435436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Enable,435436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Disable,435436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Ack,435436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Reset,435436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Suppressed,435436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Shelved,435436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Disabled,435436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Acked,435436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XE_0113_2B_ZA.almPLCFault.Alarm,435436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Fault,435456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_LL.Alarm.AlarmState,435456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_LL.Alarm.GlobalReset,435456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_LL.Alarm.FaultInAlarm,435456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_LL.Alarm.ALRM,435456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_LL.Alarm.ANUN,435456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_LL.Alarm.AKED,435456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_LL.Alarm.Resetable,435456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_LL.Alarm.REST,435456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_LL.Alarm.ACKN,435456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_LL.Alarm.UACK,435456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_LL.Alarm.MCmd_Enable,435456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_LL.Alarm.MCmd_Disable,435456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_LL.Alarm.OCmd_Shelve,435456.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_LL.Alarm.OCmd_Unshelve,435456.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_LL.Alarm.SCmd_Suppress,435456.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_LL.Alarm.SCmd_UnSuppress,435457.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_LL.Alarm.AEShelveTMRDN,435457.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_LL.Alarm.Bad,435457.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_LL.Alarm.Suppress,435458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.UnSuppress,435458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Shelve,435458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.UnShelve,435458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Enable,435458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Disable,435458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Ack,435458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Reset,435458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_LL.Alarm.Suppressed,435458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_LL.Alarm.Shelved,435458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_LL.Alarm.Disabled,435458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_LL.Alarm.Acked,435458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_LL.Alarm.Alarm,435458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Fault,435468.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_LL.almPLCFault.AlarmState,435468.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_LL.almPLCFault.GlobalReset,435468.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_LL.almPLCFault.FaultInAlarm,435468.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_LL.almPLCFault.ALRM,435468.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_LL.almPLCFault.ANUN,435468.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_LL.almPLCFault.AKED,435468.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_LL.almPLCFault.Resetable,435468.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_LL.almPLCFault.REST,435468.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_LL.almPLCFault.ACKN,435468.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_LL.almPLCFault.UACK,435468.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_LL.almPLCFault.MCmd_Enable,435468.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_LL.almPLCFault.MCmd_Disable,435468.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_LL.almPLCFault.OCmd_Shelve,435468.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_LL.almPLCFault.OCmd_Unshelve,435468.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_LL.almPLCFault.SCmd_Suppress,435468.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_LL.almPLCFault.SCmd_UnSuppress,435469.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_LL.almPLCFault.AEShelveTMRDN,435469.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_LL.almPLCFault.Bad,435469.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_LL.almPLCFault.Suppress,435470.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.UnSuppress,435470.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Shelve,435470.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.UnShelve,435470.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Enable,435470.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Disable,435470.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Ack,435470.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Reset,435470.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Suppressed,435470.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Shelved,435470.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Disabled,435470.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Acked,435470.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_LL.almPLCFault.Alarm,435470.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Fault,435492.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_TH1.Alarm.AlarmState,435492.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_TH1.Alarm.GlobalReset,435492.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_TH1.Alarm.FaultInAlarm,435492.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH1.Alarm.ALRM,435492.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_TH1.Alarm.ANUN,435492.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_TH1.Alarm.AKED,435492.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_TH1.Alarm.Resetable,435492.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_TH1.Alarm.REST,435492.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_TH1.Alarm.ACKN,435492.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_TH1.Alarm.UACK,435492.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_TH1.Alarm.MCmd_Enable,435492.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH1.Alarm.MCmd_Disable,435492.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH1.Alarm.OCmd_Shelve,435492.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_TH1.Alarm.OCmd_Unshelve,435492.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_TH1.Alarm.SCmd_Suppress,435492.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_TH1.Alarm.SCmd_UnSuppress,435493.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_TH1.Alarm.AEShelveTMRDN,435493.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_TH1.Alarm.Bad,435493.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_TH1.Alarm.Suppress,435494.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.UnSuppress,435494.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Shelve,435494.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.UnShelve,435494.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Enable,435494.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Disable,435494.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Ack,435494.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Reset,435494.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_TH1.Alarm.Suppressed,435494.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_TH1.Alarm.Shelved,435494.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_TH1.Alarm.Disabled,435494.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_TH1.Alarm.Acked,435494.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_TH1.Alarm.Alarm,435494.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Fault,435504.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_TH1.almPLCFault.AlarmState,435504.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_TH1.almPLCFault.GlobalReset,435504.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_TH1.almPLCFault.FaultInAlarm,435504.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH1.almPLCFault.ALRM,435504.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_TH1.almPLCFault.ANUN,435504.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_TH1.almPLCFault.AKED,435504.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_TH1.almPLCFault.Resetable,435504.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_TH1.almPLCFault.REST,435504.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_TH1.almPLCFault.ACKN,435504.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_TH1.almPLCFault.UACK,435504.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_TH1.almPLCFault.MCmd_Enable,435504.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.MCmd_Disable,435504.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.OCmd_Shelve,435504.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.OCmd_Unshelve,435504.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.SCmd_Suppress,435504.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.SCmd_UnSuppress,435505.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_TH1.almPLCFault.AEShelveTMRDN,435505.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_TH1.almPLCFault.Bad,435505.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_TH1.almPLCFault.Suppress,435506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.UnSuppress,435506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Shelve,435506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.UnShelve,435506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Enable,435506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Disable,435506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Ack,435506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Reset,435506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Suppressed,435506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Shelved,435506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Disabled,435506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Acked,435506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_TH1.almPLCFault.Alarm,435506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Fault,435526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_TH2.Alarm.AlarmState,435526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_TH2.Alarm.GlobalReset,435526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_TH2.Alarm.FaultInAlarm,435526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH2.Alarm.ALRM,435526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_TH2.Alarm.ANUN,435526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_TH2.Alarm.AKED,435526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_TH2.Alarm.Resetable,435526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_TH2.Alarm.REST,435526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_TH2.Alarm.ACKN,435526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_TH2.Alarm.UACK,435526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_TH2.Alarm.MCmd_Enable,435526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH2.Alarm.MCmd_Disable,435526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH2.Alarm.OCmd_Shelve,435526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_TH2.Alarm.OCmd_Unshelve,435526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_TH2.Alarm.SCmd_Suppress,435526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_TH2.Alarm.SCmd_UnSuppress,435527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_TH2.Alarm.AEShelveTMRDN,435527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_TH2.Alarm.Bad,435527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_TH2.Alarm.Suppress,435528.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.UnSuppress,435528.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Shelve,435528.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.UnShelve,435528.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Enable,435528.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Disable,435528.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Ack,435528.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Reset,435528.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_TH2.Alarm.Suppressed,435528.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_TH2.Alarm.Shelved,435528.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_TH2.Alarm.Disabled,435528.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_TH2.Alarm.Acked,435528.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_TH2.Alarm.Alarm,435528.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Fault,435538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_TH2.almPLCFault.AlarmState,435538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_TH2.almPLCFault.GlobalReset,435538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_TH2.almPLCFault.FaultInAlarm,435538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_TH2.almPLCFault.ALRM,435538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_TH2.almPLCFault.ANUN,435538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_TH2.almPLCFault.AKED,435538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_TH2.almPLCFault.Resetable,435538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_TH2.almPLCFault.REST,435538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_TH2.almPLCFault.ACKN,435538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_TH2.almPLCFault.UACK,435538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_TH2.almPLCFault.MCmd_Enable,435538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.MCmd_Disable,435538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.OCmd_Shelve,435538.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.OCmd_Unshelve,435538.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.SCmd_Suppress,435538.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.SCmd_UnSuppress,435539.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_TH2.almPLCFault.AEShelveTMRDN,435539.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_TH2.almPLCFault.Bad,435539.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_TH2.almPLCFault.Suppress,435540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.UnSuppress,435540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Shelve,435540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.UnShelve,435540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Enable,435540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Disable,435540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Ack,435540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Reset,435540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Suppressed,435540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Shelved,435540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Disabled,435540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Acked,435540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_TH2.almPLCFault.Alarm,435540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Fault,435562.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_XA.Alarm.AlarmState,435562.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_XA.Alarm.GlobalReset,435562.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_XA.Alarm.FaultInAlarm,435562.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_XA.Alarm.ALRM,435562.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_XA.Alarm.ANUN,435562.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_XA.Alarm.AKED,435562.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_XA.Alarm.Resetable,435562.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_XA.Alarm.REST,435562.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_XA.Alarm.ACKN,435562.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_XA.Alarm.UACK,435562.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_XA.Alarm.MCmd_Enable,435562.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_XA.Alarm.MCmd_Disable,435562.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_XA.Alarm.OCmd_Shelve,435562.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_XA.Alarm.OCmd_Unshelve,435562.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_XA.Alarm.SCmd_Suppress,435562.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_XA.Alarm.SCmd_UnSuppress,435563.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_XA.Alarm.AEShelveTMRDN,435563.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_XA.Alarm.Bad,435563.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_XA.Alarm.Suppress,435564.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.UnSuppress,435564.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Shelve,435564.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.UnShelve,435564.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Enable,435564.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Disable,435564.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Ack,435564.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Reset,435564.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_XA.Alarm.Suppressed,435564.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_XA.Alarm.Shelved,435564.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_XA.Alarm.Disabled,435564.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_XA.Alarm.Acked,435564.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_XA.Alarm.Alarm,435564.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Fault,435574.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_3_XA.almPLCFault.AlarmState,435574.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_3_XA.almPLCFault.GlobalReset,435574.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_3_XA.almPLCFault.FaultInAlarm,435574.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_3_XA.almPLCFault.ALRM,435574.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_3_XA.almPLCFault.ANUN,435574.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_3_XA.almPLCFault.AKED,435574.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_3_XA.almPLCFault.Resetable,435574.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_3_XA.almPLCFault.REST,435574.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_3_XA.almPLCFault.ACKN,435574.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_3_XA.almPLCFault.UACK,435574.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_3_XA.almPLCFault.MCmd_Enable,435574.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_3_XA.almPLCFault.MCmd_Disable,435574.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_3_XA.almPLCFault.OCmd_Shelve,435574.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_3_XA.almPLCFault.OCmd_Unshelve,435574.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_3_XA.almPLCFault.SCmd_Suppress,435574.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_3_XA.almPLCFault.SCmd_UnSuppress,435575.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_3_XA.almPLCFault.AEShelveTMRDN,435575.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_3_XA.almPLCFault.Bad,435575.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_3_XA.almPLCFault.Suppress,435576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.UnSuppress,435576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Shelve,435576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.UnShelve,435576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Enable,435576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Disable,435576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Ack,435576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Reset,435576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Suppressed,435576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Shelved,435576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Disabled,435576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Acked,435576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_3_XA.almPLCFault.Alarm,435576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Fault,435596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_LL.Alarm.AlarmState,435596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_LL.Alarm.GlobalReset,435596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_LL.Alarm.FaultInAlarm,435596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_LL.Alarm.ALRM,435596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_LL.Alarm.ANUN,435596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_LL.Alarm.AKED,435596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_LL.Alarm.Resetable,435596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_LL.Alarm.REST,435596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_LL.Alarm.ACKN,435596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_LL.Alarm.UACK,435596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_LL.Alarm.MCmd_Enable,435596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_LL.Alarm.MCmd_Disable,435596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_LL.Alarm.OCmd_Shelve,435596.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_LL.Alarm.OCmd_Unshelve,435596.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_LL.Alarm.SCmd_Suppress,435596.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_LL.Alarm.SCmd_UnSuppress,435597.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_LL.Alarm.AEShelveTMRDN,435597.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_LL.Alarm.Bad,435597.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_LL.Alarm.Suppress,435598.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.UnSuppress,435598.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Shelve,435598.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.UnShelve,435598.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Enable,435598.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Disable,435598.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Ack,435598.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Reset,435598.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_LL.Alarm.Suppressed,435598.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_LL.Alarm.Shelved,435598.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_LL.Alarm.Disabled,435598.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_LL.Alarm.Acked,435598.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_LL.Alarm.Alarm,435598.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Fault,435608.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_LL.almPLCFault.AlarmState,435608.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_LL.almPLCFault.GlobalReset,435608.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_LL.almPLCFault.FaultInAlarm,435608.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_LL.almPLCFault.ALRM,435608.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_LL.almPLCFault.ANUN,435608.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_LL.almPLCFault.AKED,435608.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_LL.almPLCFault.Resetable,435608.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_LL.almPLCFault.REST,435608.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_LL.almPLCFault.ACKN,435608.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_LL.almPLCFault.UACK,435608.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_LL.almPLCFault.MCmd_Enable,435608.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_LL.almPLCFault.MCmd_Disable,435608.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_LL.almPLCFault.OCmd_Shelve,435608.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_LL.almPLCFault.OCmd_Unshelve,435608.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_LL.almPLCFault.SCmd_Suppress,435608.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_LL.almPLCFault.SCmd_UnSuppress,435609.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_LL.almPLCFault.AEShelveTMRDN,435609.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_LL.almPLCFault.Bad,435609.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_LL.almPLCFault.Suppress,435610.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.UnSuppress,435610.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Shelve,435610.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.UnShelve,435610.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Enable,435610.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Disable,435610.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Ack,435610.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Reset,435610.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Suppressed,435610.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Shelved,435610.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Disabled,435610.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Acked,435610.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_LL.almPLCFault.Alarm,435610.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Fault,435632.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_TH1.Alarm.AlarmState,435632.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_TH1.Alarm.GlobalReset,435632.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_TH1.Alarm.FaultInAlarm,435632.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH1.Alarm.ALRM,435632.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_TH1.Alarm.ANUN,435632.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_TH1.Alarm.AKED,435632.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_TH1.Alarm.Resetable,435632.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_TH1.Alarm.REST,435632.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_TH1.Alarm.ACKN,435632.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_TH1.Alarm.UACK,435632.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_TH1.Alarm.MCmd_Enable,435632.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH1.Alarm.MCmd_Disable,435632.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH1.Alarm.OCmd_Shelve,435632.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_TH1.Alarm.OCmd_Unshelve,435632.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_TH1.Alarm.SCmd_Suppress,435632.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_TH1.Alarm.SCmd_UnSuppress,435633.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_TH1.Alarm.AEShelveTMRDN,435633.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_TH1.Alarm.Bad,435633.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_TH1.Alarm.Suppress,435634.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.UnSuppress,435634.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Shelve,435634.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.UnShelve,435634.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Enable,435634.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Disable,435634.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Ack,435634.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Reset,435634.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_TH1.Alarm.Suppressed,435634.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_TH1.Alarm.Shelved,435634.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_TH1.Alarm.Disabled,435634.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_TH1.Alarm.Acked,435634.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_TH1.Alarm.Alarm,435634.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Fault,435644.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_TH1.almPLCFault.AlarmState,435644.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_TH1.almPLCFault.GlobalReset,435644.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_TH1.almPLCFault.FaultInAlarm,435644.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH1.almPLCFault.ALRM,435644.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_TH1.almPLCFault.ANUN,435644.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_TH1.almPLCFault.AKED,435644.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_TH1.almPLCFault.Resetable,435644.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_TH1.almPLCFault.REST,435644.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_TH1.almPLCFault.ACKN,435644.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_TH1.almPLCFault.UACK,435644.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_TH1.almPLCFault.MCmd_Enable,435644.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.MCmd_Disable,435644.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.OCmd_Shelve,435644.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.OCmd_Unshelve,435644.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.SCmd_Suppress,435644.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.SCmd_UnSuppress,435645.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_TH1.almPLCFault.AEShelveTMRDN,435645.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_TH1.almPLCFault.Bad,435645.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_TH1.almPLCFault.Suppress,435646.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.UnSuppress,435646.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Shelve,435646.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.UnShelve,435646.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Enable,435646.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Disable,435646.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Ack,435646.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Reset,435646.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Suppressed,435646.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Shelved,435646.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Disabled,435646.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Acked,435646.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_TH1.almPLCFault.Alarm,435646.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Fault,435666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_TH2.Alarm.AlarmState,435666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_TH2.Alarm.GlobalReset,435666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_TH2.Alarm.FaultInAlarm,435666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH2.Alarm.ALRM,435666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_TH2.Alarm.ANUN,435666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_TH2.Alarm.AKED,435666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_TH2.Alarm.Resetable,435666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_TH2.Alarm.REST,435666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_TH2.Alarm.ACKN,435666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_TH2.Alarm.UACK,435666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_TH2.Alarm.MCmd_Enable,435666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH2.Alarm.MCmd_Disable,435666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH2.Alarm.OCmd_Shelve,435666.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_TH2.Alarm.OCmd_Unshelve,435666.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_TH2.Alarm.SCmd_Suppress,435666.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_TH2.Alarm.SCmd_UnSuppress,435667.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_TH2.Alarm.AEShelveTMRDN,435667.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_TH2.Alarm.Bad,435667.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_TH2.Alarm.Suppress,435668.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.UnSuppress,435668.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Shelve,435668.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.UnShelve,435668.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Enable,435668.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Disable,435668.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Ack,435668.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Reset,435668.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_TH2.Alarm.Suppressed,435668.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_TH2.Alarm.Shelved,435668.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_TH2.Alarm.Disabled,435668.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_TH2.Alarm.Acked,435668.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_TH2.Alarm.Alarm,435668.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Fault,435678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_TH2.almPLCFault.AlarmState,435678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_TH2.almPLCFault.GlobalReset,435678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_TH2.almPLCFault.FaultInAlarm,435678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_TH2.almPLCFault.ALRM,435678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_TH2.almPLCFault.ANUN,435678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_TH2.almPLCFault.AKED,435678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_TH2.almPLCFault.Resetable,435678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_TH2.almPLCFault.REST,435678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_TH2.almPLCFault.ACKN,435678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_TH2.almPLCFault.UACK,435678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_TH2.almPLCFault.MCmd_Enable,435678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.MCmd_Disable,435678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.OCmd_Shelve,435678.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.OCmd_Unshelve,435678.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.SCmd_Suppress,435678.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.SCmd_UnSuppress,435679.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_TH2.almPLCFault.AEShelveTMRDN,435679.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_TH2.almPLCFault.Bad,435679.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_TH2.almPLCFault.Suppress,435680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.UnSuppress,435680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Shelve,435680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.UnShelve,435680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Enable,435680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Disable,435680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Ack,435680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Reset,435680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Suppressed,435680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Shelved,435680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Disabled,435680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Acked,435680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_TH2.almPLCFault.Alarm,435680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Fault,435702.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_XA.Alarm.AlarmState,435702.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_XA.Alarm.GlobalReset,435702.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_XA.Alarm.FaultInAlarm,435702.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_XA.Alarm.ALRM,435702.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_XA.Alarm.ANUN,435702.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_XA.Alarm.AKED,435702.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_XA.Alarm.Resetable,435702.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_XA.Alarm.REST,435702.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_XA.Alarm.ACKN,435702.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_XA.Alarm.UACK,435702.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_XA.Alarm.MCmd_Enable,435702.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_XA.Alarm.MCmd_Disable,435702.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_XA.Alarm.OCmd_Shelve,435702.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_XA.Alarm.OCmd_Unshelve,435702.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_XA.Alarm.SCmd_Suppress,435702.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_XA.Alarm.SCmd_UnSuppress,435703.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_XA.Alarm.AEShelveTMRDN,435703.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_XA.Alarm.Bad,435703.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_XA.Alarm.Suppress,435704.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.UnSuppress,435704.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Shelve,435704.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.UnShelve,435704.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Enable,435704.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Disable,435704.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Ack,435704.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Reset,435704.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_XA.Alarm.Suppressed,435704.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_XA.Alarm.Shelved,435704.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_XA.Alarm.Disabled,435704.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_XA.Alarm.Acked,435704.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_XA.Alarm.Alarm,435704.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Fault,435714.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_4_XA.almPLCFault.AlarmState,435714.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_4_XA.almPLCFault.GlobalReset,435714.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_4_XA.almPLCFault.FaultInAlarm,435714.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_4_XA.almPLCFault.ALRM,435714.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_4_XA.almPLCFault.ANUN,435714.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_4_XA.almPLCFault.AKED,435714.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_4_XA.almPLCFault.Resetable,435714.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_4_XA.almPLCFault.REST,435714.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_4_XA.almPLCFault.ACKN,435714.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_4_XA.almPLCFault.UACK,435714.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_4_XA.almPLCFault.MCmd_Enable,435714.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_4_XA.almPLCFault.MCmd_Disable,435714.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_4_XA.almPLCFault.OCmd_Shelve,435714.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_4_XA.almPLCFault.OCmd_Unshelve,435714.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_4_XA.almPLCFault.SCmd_Suppress,435714.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_4_XA.almPLCFault.SCmd_UnSuppress,435715.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_4_XA.almPLCFault.AEShelveTMRDN,435715.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_4_XA.almPLCFault.Bad,435715.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_4_XA.almPLCFault.Suppress,435716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.UnSuppress,435716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Shelve,435716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.UnShelve,435716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Enable,435716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Disable,435716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Ack,435716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Reset,435716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Suppressed,435716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Shelved,435716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Disabled,435716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Acked,435716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_4_XA.almPLCFault.Alarm,435716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Fault,435736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_LL.Alarm.AlarmState,435736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_LL.Alarm.GlobalReset,435736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_LL.Alarm.FaultInAlarm,435736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_LL.Alarm.ALRM,435736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_LL.Alarm.ANUN,435736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_LL.Alarm.AKED,435736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_LL.Alarm.Resetable,435736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_LL.Alarm.REST,435736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_LL.Alarm.ACKN,435736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_LL.Alarm.UACK,435736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_LL.Alarm.MCmd_Enable,435736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_LL.Alarm.MCmd_Disable,435736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_LL.Alarm.OCmd_Shelve,435736.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_LL.Alarm.OCmd_Unshelve,435736.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_LL.Alarm.SCmd_Suppress,435736.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_LL.Alarm.SCmd_UnSuppress,435737.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_LL.Alarm.AEShelveTMRDN,435737.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_LL.Alarm.Bad,435737.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_LL.Alarm.Suppress,435738.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.UnSuppress,435738.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Shelve,435738.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.UnShelve,435738.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Enable,435738.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Disable,435738.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Ack,435738.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Reset,435738.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_LL.Alarm.Suppressed,435738.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_LL.Alarm.Shelved,435738.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_LL.Alarm.Disabled,435738.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_LL.Alarm.Acked,435738.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_LL.Alarm.Alarm,435738.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Fault,435748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_LL.almPLCFault.AlarmState,435748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_LL.almPLCFault.GlobalReset,435748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_LL.almPLCFault.FaultInAlarm,435748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_LL.almPLCFault.ALRM,435748.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_LL.almPLCFault.ANUN,435748.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_LL.almPLCFault.AKED,435748.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_LL.almPLCFault.Resetable,435748.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_LL.almPLCFault.REST,435748.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_LL.almPLCFault.ACKN,435748.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_LL.almPLCFault.UACK,435748.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_LL.almPLCFault.MCmd_Enable,435748.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_LL.almPLCFault.MCmd_Disable,435748.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_LL.almPLCFault.OCmd_Shelve,435748.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_LL.almPLCFault.OCmd_Unshelve,435748.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_LL.almPLCFault.SCmd_Suppress,435748.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_LL.almPLCFault.SCmd_UnSuppress,435749.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_LL.almPLCFault.AEShelveTMRDN,435749.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_LL.almPLCFault.Bad,435749.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_LL.almPLCFault.Suppress,435750.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.UnSuppress,435750.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Shelve,435750.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.UnShelve,435750.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Enable,435750.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Disable,435750.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Ack,435750.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Reset,435750.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Suppressed,435750.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Shelved,435750.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Disabled,435750.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Acked,435750.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_LL.almPLCFault.Alarm,435750.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Fault,435772.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_TH1.Alarm.AlarmState,435772.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_TH1.Alarm.GlobalReset,435772.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_TH1.Alarm.FaultInAlarm,435772.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH1.Alarm.ALRM,435772.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_TH1.Alarm.ANUN,435772.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_TH1.Alarm.AKED,435772.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_TH1.Alarm.Resetable,435772.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_TH1.Alarm.REST,435772.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_TH1.Alarm.ACKN,435772.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_TH1.Alarm.UACK,435772.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_TH1.Alarm.MCmd_Enable,435772.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH1.Alarm.MCmd_Disable,435772.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH1.Alarm.OCmd_Shelve,435772.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_TH1.Alarm.OCmd_Unshelve,435772.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_TH1.Alarm.SCmd_Suppress,435772.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_TH1.Alarm.SCmd_UnSuppress,435773.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_TH1.Alarm.AEShelveTMRDN,435773.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_TH1.Alarm.Bad,435773.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_TH1.Alarm.Suppress,435774.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.UnSuppress,435774.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Shelve,435774.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.UnShelve,435774.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Enable,435774.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Disable,435774.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Ack,435774.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Reset,435774.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_TH1.Alarm.Suppressed,435774.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_TH1.Alarm.Shelved,435774.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_TH1.Alarm.Disabled,435774.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_TH1.Alarm.Acked,435774.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_TH1.Alarm.Alarm,435774.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Fault,435784.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_TH1.almPLCFault.AlarmState,435784.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_TH1.almPLCFault.GlobalReset,435784.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_TH1.almPLCFault.FaultInAlarm,435784.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH1.almPLCFault.ALRM,435784.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_TH1.almPLCFault.ANUN,435784.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_TH1.almPLCFault.AKED,435784.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_TH1.almPLCFault.Resetable,435784.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_TH1.almPLCFault.REST,435784.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_TH1.almPLCFault.ACKN,435784.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_TH1.almPLCFault.UACK,435784.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_TH1.almPLCFault.MCmd_Enable,435784.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.MCmd_Disable,435784.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.OCmd_Shelve,435784.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.OCmd_Unshelve,435784.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.SCmd_Suppress,435784.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.SCmd_UnSuppress,435785.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_TH1.almPLCFault.AEShelveTMRDN,435785.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_TH1.almPLCFault.Bad,435785.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_TH1.almPLCFault.Suppress,435786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.UnSuppress,435786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Shelve,435786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.UnShelve,435786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Enable,435786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Disable,435786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Ack,435786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Reset,435786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Suppressed,435786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Shelved,435786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Disabled,435786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Acked,435786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_TH1.almPLCFault.Alarm,435786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Fault,435806.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_TH2.Alarm.AlarmState,435806.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_TH2.Alarm.GlobalReset,435806.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_TH2.Alarm.FaultInAlarm,435806.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH2.Alarm.ALRM,435806.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_TH2.Alarm.ANUN,435806.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_TH2.Alarm.AKED,435806.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_TH2.Alarm.Resetable,435806.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_TH2.Alarm.REST,435806.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_TH2.Alarm.ACKN,435806.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_TH2.Alarm.UACK,435806.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_TH2.Alarm.MCmd_Enable,435806.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH2.Alarm.MCmd_Disable,435806.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH2.Alarm.OCmd_Shelve,435806.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_TH2.Alarm.OCmd_Unshelve,435806.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_TH2.Alarm.SCmd_Suppress,435806.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_TH2.Alarm.SCmd_UnSuppress,435807.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_TH2.Alarm.AEShelveTMRDN,435807.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_TH2.Alarm.Bad,435807.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_TH2.Alarm.Suppress,435808.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.UnSuppress,435808.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Shelve,435808.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.UnShelve,435808.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Enable,435808.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Disable,435808.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Ack,435808.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Reset,435808.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_TH2.Alarm.Suppressed,435808.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_TH2.Alarm.Shelved,435808.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_TH2.Alarm.Disabled,435808.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_TH2.Alarm.Acked,435808.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_TH2.Alarm.Alarm,435808.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Fault,435818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_TH2.almPLCFault.AlarmState,435818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_TH2.almPLCFault.GlobalReset,435818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_TH2.almPLCFault.FaultInAlarm,435818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_TH2.almPLCFault.ALRM,435818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_TH2.almPLCFault.ANUN,435818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_TH2.almPLCFault.AKED,435818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_TH2.almPLCFault.Resetable,435818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_TH2.almPLCFault.REST,435818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_TH2.almPLCFault.ACKN,435818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_TH2.almPLCFault.UACK,435818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_TH2.almPLCFault.MCmd_Enable,435818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.MCmd_Disable,435818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.OCmd_Shelve,435818.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.OCmd_Unshelve,435818.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.SCmd_Suppress,435818.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.SCmd_UnSuppress,435819.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_TH2.almPLCFault.AEShelveTMRDN,435819.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_TH2.almPLCFault.Bad,435819.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_TH2.almPLCFault.Suppress,435820.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.UnSuppress,435820.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Shelve,435820.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.UnShelve,435820.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Enable,435820.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Disable,435820.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Ack,435820.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Reset,435820.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Suppressed,435820.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Shelved,435820.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Disabled,435820.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Acked,435820.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_TH2.almPLCFault.Alarm,435820.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Fault,435842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_XA.Alarm.AlarmState,435842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_XA.Alarm.GlobalReset,435842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_XA.Alarm.FaultInAlarm,435842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_XA.Alarm.ALRM,435842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_XA.Alarm.ANUN,435842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_XA.Alarm.AKED,435842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_XA.Alarm.Resetable,435842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_XA.Alarm.REST,435842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_XA.Alarm.ACKN,435842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_XA.Alarm.UACK,435842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_XA.Alarm.MCmd_Enable,435842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_XA.Alarm.MCmd_Disable,435842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_XA.Alarm.OCmd_Shelve,435842.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_XA.Alarm.OCmd_Unshelve,435842.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_XA.Alarm.SCmd_Suppress,435842.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_XA.Alarm.SCmd_UnSuppress,435843.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_XA.Alarm.AEShelveTMRDN,435843.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_XA.Alarm.Bad,435843.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_XA.Alarm.Suppress,435844.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.UnSuppress,435844.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Shelve,435844.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.UnShelve,435844.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Enable,435844.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Disable,435844.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Ack,435844.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Reset,435844.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_XA.Alarm.Suppressed,435844.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_XA.Alarm.Shelved,435844.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_XA.Alarm.Disabled,435844.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_XA.Alarm.Acked,435844.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_XA.Alarm.Alarm,435844.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Fault,435854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_5_XA.almPLCFault.AlarmState,435854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_5_XA.almPLCFault.GlobalReset,435854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_5_XA.almPLCFault.FaultInAlarm,435854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_5_XA.almPLCFault.ALRM,435854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_5_XA.almPLCFault.ANUN,435854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_5_XA.almPLCFault.AKED,435854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_5_XA.almPLCFault.Resetable,435854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_5_XA.almPLCFault.REST,435854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_5_XA.almPLCFault.ACKN,435854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_5_XA.almPLCFault.UACK,435854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_5_XA.almPLCFault.MCmd_Enable,435854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_5_XA.almPLCFault.MCmd_Disable,435854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_5_XA.almPLCFault.OCmd_Shelve,435854.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_5_XA.almPLCFault.OCmd_Unshelve,435854.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_5_XA.almPLCFault.SCmd_Suppress,435854.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_5_XA.almPLCFault.SCmd_UnSuppress,435855.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_5_XA.almPLCFault.AEShelveTMRDN,435855.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_5_XA.almPLCFault.Bad,435855.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_5_XA.almPLCFault.Suppress,435856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.UnSuppress,435856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Shelve,435856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.UnShelve,435856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Enable,435856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Disable,435856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Ack,435856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Reset,435856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Suppressed,435856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Shelved,435856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Disabled,435856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Acked,435856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_5_XA.almPLCFault.Alarm,435856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Fault,435876.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_LL.Alarm.AlarmState,435876.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_LL.Alarm.GlobalReset,435876.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_LL.Alarm.FaultInAlarm,435876.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_LL.Alarm.ALRM,435876.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_LL.Alarm.ANUN,435876.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_LL.Alarm.AKED,435876.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_LL.Alarm.Resetable,435876.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_LL.Alarm.REST,435876.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_LL.Alarm.ACKN,435876.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_LL.Alarm.UACK,435876.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_LL.Alarm.MCmd_Enable,435876.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_LL.Alarm.MCmd_Disable,435876.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_LL.Alarm.OCmd_Shelve,435876.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_LL.Alarm.OCmd_Unshelve,435876.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_LL.Alarm.SCmd_Suppress,435876.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_LL.Alarm.SCmd_UnSuppress,435877.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_LL.Alarm.AEShelveTMRDN,435877.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_LL.Alarm.Bad,435877.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_LL.Alarm.Suppress,435878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.UnSuppress,435878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Shelve,435878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.UnShelve,435878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Enable,435878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Disable,435878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Ack,435878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Reset,435878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_LL.Alarm.Suppressed,435878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_LL.Alarm.Shelved,435878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_LL.Alarm.Disabled,435878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_LL.Alarm.Acked,435878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_LL.Alarm.Alarm,435878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Fault,435888.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_LL.almPLCFault.AlarmState,435888.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_LL.almPLCFault.GlobalReset,435888.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_LL.almPLCFault.FaultInAlarm,435888.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_LL.almPLCFault.ALRM,435888.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_LL.almPLCFault.ANUN,435888.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_LL.almPLCFault.AKED,435888.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_LL.almPLCFault.Resetable,435888.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_LL.almPLCFault.REST,435888.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_LL.almPLCFault.ACKN,435888.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_LL.almPLCFault.UACK,435888.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_LL.almPLCFault.MCmd_Enable,435888.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_LL.almPLCFault.MCmd_Disable,435888.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_LL.almPLCFault.OCmd_Shelve,435888.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_LL.almPLCFault.OCmd_Unshelve,435888.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_LL.almPLCFault.SCmd_Suppress,435888.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_LL.almPLCFault.SCmd_UnSuppress,435889.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_LL.almPLCFault.AEShelveTMRDN,435889.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_LL.almPLCFault.Bad,435889.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_LL.almPLCFault.Suppress,435890.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.UnSuppress,435890.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Shelve,435890.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.UnShelve,435890.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Enable,435890.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Disable,435890.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Ack,435890.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Reset,435890.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Suppressed,435890.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Shelved,435890.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Disabled,435890.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Acked,435890.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_LL.almPLCFault.Alarm,435890.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Fault,435912.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_TH1.Alarm.AlarmState,435912.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_TH1.Alarm.GlobalReset,435912.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_TH1.Alarm.FaultInAlarm,435912.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH1.Alarm.ALRM,435912.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_TH1.Alarm.ANUN,435912.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_TH1.Alarm.AKED,435912.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_TH1.Alarm.Resetable,435912.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_TH1.Alarm.REST,435912.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_TH1.Alarm.ACKN,435912.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_TH1.Alarm.UACK,435912.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_TH1.Alarm.MCmd_Enable,435912.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH1.Alarm.MCmd_Disable,435912.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH1.Alarm.OCmd_Shelve,435912.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_TH1.Alarm.OCmd_Unshelve,435912.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_TH1.Alarm.SCmd_Suppress,435912.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_TH1.Alarm.SCmd_UnSuppress,435913.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_TH1.Alarm.AEShelveTMRDN,435913.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_TH1.Alarm.Bad,435913.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_TH1.Alarm.Suppress,435914.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.UnSuppress,435914.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Shelve,435914.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.UnShelve,435914.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Enable,435914.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Disable,435914.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Ack,435914.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Reset,435914.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_TH1.Alarm.Suppressed,435914.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_TH1.Alarm.Shelved,435914.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_TH1.Alarm.Disabled,435914.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_TH1.Alarm.Acked,435914.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_TH1.Alarm.Alarm,435914.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Fault,435924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_TH1.almPLCFault.AlarmState,435924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_TH1.almPLCFault.GlobalReset,435924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_TH1.almPLCFault.FaultInAlarm,435924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH1.almPLCFault.ALRM,435924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_TH1.almPLCFault.ANUN,435924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_TH1.almPLCFault.AKED,435924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_TH1.almPLCFault.Resetable,435924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_TH1.almPLCFault.REST,435924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_TH1.almPLCFault.ACKN,435924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_TH1.almPLCFault.UACK,435924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_TH1.almPLCFault.MCmd_Enable,435924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.MCmd_Disable,435924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.OCmd_Shelve,435924.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.OCmd_Unshelve,435924.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.SCmd_Suppress,435924.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.SCmd_UnSuppress,435925.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_TH1.almPLCFault.AEShelveTMRDN,435925.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_TH1.almPLCFault.Bad,435925.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_TH1.almPLCFault.Suppress,435926.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.UnSuppress,435926.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Shelve,435926.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.UnShelve,435926.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Enable,435926.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Disable,435926.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Ack,435926.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Reset,435926.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Suppressed,435926.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Shelved,435926.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Disabled,435926.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Acked,435926.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_TH1.almPLCFault.Alarm,435926.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Fault,435946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_TH2.Alarm.AlarmState,435946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_TH2.Alarm.GlobalReset,435946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_TH2.Alarm.FaultInAlarm,435946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH2.Alarm.ALRM,435946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_TH2.Alarm.ANUN,435946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_TH2.Alarm.AKED,435946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_TH2.Alarm.Resetable,435946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_TH2.Alarm.REST,435946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_TH2.Alarm.ACKN,435946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_TH2.Alarm.UACK,435946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_TH2.Alarm.MCmd_Enable,435946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH2.Alarm.MCmd_Disable,435946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH2.Alarm.OCmd_Shelve,435946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_TH2.Alarm.OCmd_Unshelve,435946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_TH2.Alarm.SCmd_Suppress,435946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_TH2.Alarm.SCmd_UnSuppress,435947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_TH2.Alarm.AEShelveTMRDN,435947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_TH2.Alarm.Bad,435947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_TH2.Alarm.Suppress,435948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.UnSuppress,435948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Shelve,435948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.UnShelve,435948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Enable,435948.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Disable,435948.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Ack,435948.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Reset,435948.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_TH2.Alarm.Suppressed,435948.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_TH2.Alarm.Shelved,435948.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_TH2.Alarm.Disabled,435948.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_TH2.Alarm.Acked,435948.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_TH2.Alarm.Alarm,435948.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Fault,435958.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_TH2.almPLCFault.AlarmState,435958.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_TH2.almPLCFault.GlobalReset,435958.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_TH2.almPLCFault.FaultInAlarm,435958.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_TH2.almPLCFault.ALRM,435958.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_TH2.almPLCFault.ANUN,435958.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_TH2.almPLCFault.AKED,435958.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_TH2.almPLCFault.Resetable,435958.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_TH2.almPLCFault.REST,435958.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_TH2.almPLCFault.ACKN,435958.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_TH2.almPLCFault.UACK,435958.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_TH2.almPLCFault.MCmd_Enable,435958.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.MCmd_Disable,435958.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.OCmd_Shelve,435958.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.OCmd_Unshelve,435958.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.SCmd_Suppress,435958.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.SCmd_UnSuppress,435959.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_TH2.almPLCFault.AEShelveTMRDN,435959.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_TH2.almPLCFault.Bad,435959.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_TH2.almPLCFault.Suppress,435960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.UnSuppress,435960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Shelve,435960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.UnShelve,435960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Enable,435960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Disable,435960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Ack,435960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Reset,435960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Suppressed,435960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Shelved,435960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Disabled,435960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Acked,435960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_TH2.almPLCFault.Alarm,435960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Fault,435982.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_XA.Alarm.AlarmState,435982.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_XA.Alarm.GlobalReset,435982.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_XA.Alarm.FaultInAlarm,435982.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_XA.Alarm.ALRM,435982.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_XA.Alarm.ANUN,435982.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_XA.Alarm.AKED,435982.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_XA.Alarm.Resetable,435982.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_XA.Alarm.REST,435982.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_XA.Alarm.ACKN,435982.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_XA.Alarm.UACK,435982.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_XA.Alarm.MCmd_Enable,435982.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_XA.Alarm.MCmd_Disable,435982.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_XA.Alarm.OCmd_Shelve,435982.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_XA.Alarm.OCmd_Unshelve,435982.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_XA.Alarm.SCmd_Suppress,435982.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_XA.Alarm.SCmd_UnSuppress,435983.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_XA.Alarm.AEShelveTMRDN,435983.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_XA.Alarm.Bad,435983.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_XA.Alarm.Suppress,435984.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.UnSuppress,435984.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Shelve,435984.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.UnShelve,435984.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Enable,435984.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Disable,435984.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Ack,435984.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Reset,435984.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_XA.Alarm.Suppressed,435984.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_XA.Alarm.Shelved,435984.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_XA.Alarm.Disabled,435984.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_XA.Alarm.Acked,435984.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_XA.Alarm.Alarm,435984.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Fault,435994.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_XFR_0131_6_XA.almPLCFault.AlarmState,435994.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_XFR_0131_6_XA.almPLCFault.GlobalReset,435994.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_XFR_0131_6_XA.almPLCFault.FaultInAlarm,435994.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_XFR_0131_6_XA.almPLCFault.ALRM,435994.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_XFR_0131_6_XA.almPLCFault.ANUN,435994.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_XFR_0131_6_XA.almPLCFault.AKED,435994.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_XFR_0131_6_XA.almPLCFault.Resetable,435994.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_XFR_0131_6_XA.almPLCFault.REST,435994.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_XFR_0131_6_XA.almPLCFault.ACKN,435994.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_XFR_0131_6_XA.almPLCFault.UACK,435994.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_XFR_0131_6_XA.almPLCFault.MCmd_Enable,435994.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_XFR_0131_6_XA.almPLCFault.MCmd_Disable,435994.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_XFR_0131_6_XA.almPLCFault.OCmd_Shelve,435994.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_XFR_0131_6_XA.almPLCFault.OCmd_Unshelve,435994.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_XFR_0131_6_XA.almPLCFault.SCmd_Suppress,435994.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_XFR_0131_6_XA.almPLCFault.SCmd_UnSuppress,435995.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_XFR_0131_6_XA.almPLCFault.AEShelveTMRDN,435995.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_XFR_0131_6_XA.almPLCFault.Bad,435995.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_XFR_0131_6_XA.almPLCFault.Suppress,435996.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.UnSuppress,435996.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Shelve,435996.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.UnShelve,435996.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Enable,435996.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Disable,435996.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Ack,435996.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Reset,435996.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Suppressed,435996.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Shelved,435996.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Disabled,435996.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Acked,435996.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_XFR_0131_6_XA.almPLCFault.Alarm,435996.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Fault,436016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EASTMICRO_FAIL.Alarm.AlarmState,436016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EASTMICRO_FAIL.Alarm.GlobalReset,436016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EASTMICRO_FAIL.Alarm.FaultInAlarm,436016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EASTMICRO_FAIL.Alarm.ALRM,436016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EASTMICRO_FAIL.Alarm.ANUN,436016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EASTMICRO_FAIL.Alarm.AKED,436016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EASTMICRO_FAIL.Alarm.Resetable,436016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EASTMICRO_FAIL.Alarm.REST,436016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EASTMICRO_FAIL.Alarm.ACKN,436016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EASTMICRO_FAIL.Alarm.UACK,436016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EASTMICRO_FAIL.Alarm.MCmd_Enable,436016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.MCmd_Disable,436016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.OCmd_Shelve,436016.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.OCmd_Unshelve,436016.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.SCmd_Suppress,436016.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.SCmd_UnSuppress,436017.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EASTMICRO_FAIL.Alarm.AEShelveTMRDN,436017.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EASTMICRO_FAIL.Alarm.Bad,436017.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EASTMICRO_FAIL.Alarm.Suppress,436018.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.UnSuppress,436018.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Shelve,436018.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.UnShelve,436018.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Enable,436018.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Disable,436018.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Ack,436018.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Reset,436018.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Suppressed,436018.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Shelved,436018.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Disabled,436018.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Acked,436018.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.Alarm,436018.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Fault,436028.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AlarmState,436028.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.GlobalReset,436028.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.FaultInAlarm,436028.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.ALRM,436028.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EASTMICRO_FAIL.almPLCFault.ANUN,436028.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AKED,436028.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Resetable,436028.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EASTMICRO_FAIL.almPLCFault.REST,436028.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.ACKN,436028.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.UACK,436028.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.MCmd_Enable,436028.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.MCmd_Disable,436028.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.OCmd_Shelve,436028.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.OCmd_Unshelve,436028.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.SCmd_Suppress,436028.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.SCmd_UnSuppress,436029.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AEShelveTMRDN,436029.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Bad,436029.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Suppress,436030.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.UnSuppress,436030.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Shelve,436030.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.UnShelve,436030.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Enable,436030.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Disable,436030.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Ack,436030.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Reset,436030.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Suppressed,436030.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Shelved,436030.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Disabled,436030.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Acked,436030.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.Alarm,436030.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Fault,436052.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AlarmState,436052.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.GlobalReset,436052.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.FaultInAlarm,436052.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.ALRM,436052.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP1_FAIL.Alarm.ANUN,436052.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AKED,436052.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Resetable,436052.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP1_FAIL.Alarm.REST,436052.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.ACKN,436052.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.UACK,436052.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.MCmd_Enable,436052.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.MCmd_Disable,436052.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.OCmd_Shelve,436052.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.OCmd_Unshelve,436052.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.SCmd_Suppress,436052.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.SCmd_UnSuppress,436053.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AEShelveTMRDN,436053.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Bad,436053.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Suppress,436054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.UnSuppress,436054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Shelve,436054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.UnShelve,436054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Enable,436054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Disable,436054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Ack,436054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Reset,436054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Suppressed,436054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Shelved,436054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Disabled,436054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Acked,436054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.Alarm,436054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Fault,436064.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AlarmState,436064.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.GlobalReset,436064.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.FaultInAlarm,436064.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.ALRM,436064.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.ANUN,436064.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AKED,436064.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Resetable,436064.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.REST,436064.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.ACKN,436064.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.UACK,436064.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.MCmd_Enable,436064.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.MCmd_Disable,436064.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.OCmd_Shelve,436064.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.OCmd_Unshelve,436064.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.SCmd_Suppress,436064.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.SCmd_UnSuppress,436065.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AEShelveTMRDN,436065.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Bad,436065.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Suppress,436066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.UnSuppress,436066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Shelve,436066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.UnShelve,436066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Enable,436066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Disable,436066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Ack,436066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Reset,436066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Suppressed,436066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Shelved,436066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Disabled,436066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Acked,436066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.Alarm,436066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Fault,436086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AlarmState,436086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.GlobalReset,436086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.FaultInAlarm,436086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.ALRM,436086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP2_FAIL.Alarm.ANUN,436086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AKED,436086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Resetable,436086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP2_FAIL.Alarm.REST,436086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.ACKN,436086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.UACK,436086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.MCmd_Enable,436086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.MCmd_Disable,436086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.OCmd_Shelve,436086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.OCmd_Unshelve,436086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.SCmd_Suppress,436086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.SCmd_UnSuppress,436087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AEShelveTMRDN,436087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Bad,436087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Suppress,436088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.UnSuppress,436088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Shelve,436088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.UnShelve,436088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Enable,436088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Disable,436088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Ack,436088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Reset,436088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Suppressed,436088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Shelved,436088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Disabled,436088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Acked,436088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.Alarm,436088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Fault,436098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AlarmState,436098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.GlobalReset,436098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.FaultInAlarm,436098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.ALRM,436098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.ANUN,436098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AKED,436098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Resetable,436098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.REST,436098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.ACKN,436098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.UACK,436098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.MCmd_Enable,436098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.MCmd_Disable,436098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.OCmd_Shelve,436098.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.OCmd_Unshelve,436098.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.SCmd_Suppress,436098.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.SCmd_UnSuppress,436099.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AEShelveTMRDN,436099.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Bad,436099.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Suppress,436100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.UnSuppress,436100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Shelve,436100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.UnShelve,436100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Enable,436100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Disable,436100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Ack,436100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Reset,436100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Suppressed,436100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Shelved,436100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Disabled,436100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Acked,436100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.Alarm,436100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Fault,436122.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AlarmState,436122.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.GlobalReset,436122.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.FaultInAlarm,436122.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.ALRM,436122.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP9_FAIL.Alarm.ANUN,436122.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AKED,436122.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Resetable,436122.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP9_FAIL.Alarm.REST,436122.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.ACKN,436122.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.UACK,436122.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.MCmd_Enable,436122.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.MCmd_Disable,436122.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.OCmd_Shelve,436122.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.OCmd_Unshelve,436122.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.SCmd_Suppress,436122.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.SCmd_UnSuppress,436123.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AEShelveTMRDN,436123.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Bad,436123.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Suppress,436124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.UnSuppress,436124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Shelve,436124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.UnShelve,436124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Enable,436124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Disable,436124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Ack,436124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Reset,436124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Suppressed,436124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Shelved,436124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Disabled,436124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Acked,436124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.Alarm,436124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Fault,436134.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AlarmState,436134.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.GlobalReset,436134.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.FaultInAlarm,436134.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.ALRM,436134.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.ANUN,436134.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AKED,436134.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Resetable,436134.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.REST,436134.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.ACKN,436134.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.UACK,436134.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.MCmd_Enable,436134.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.MCmd_Disable,436134.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.OCmd_Shelve,436134.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.OCmd_Unshelve,436134.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.SCmd_Suppress,436134.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.SCmd_UnSuppress,436135.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AEShelveTMRDN,436135.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Bad,436135.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Suppress,436136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.UnSuppress,436136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Shelve,436136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.UnShelve,436136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Enable,436136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Disable,436136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Ack,436136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Reset,436136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Suppressed,436136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Shelved,436136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Disabled,436136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Acked,436136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.Alarm,436136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Fault,436156.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_METER_VAULT_FAIL.Alarm.AlarmState,436156.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_METER_VAULT_FAIL.Alarm.GlobalReset,436156.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_METER_VAULT_FAIL.Alarm.FaultInAlarm,436156.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_METER_VAULT_FAIL.Alarm.ALRM,436156.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_METER_VAULT_FAIL.Alarm.ANUN,436156.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_METER_VAULT_FAIL.Alarm.AKED,436156.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_METER_VAULT_FAIL.Alarm.Resetable,436156.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_METER_VAULT_FAIL.Alarm.REST,436156.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_METER_VAULT_FAIL.Alarm.ACKN,436156.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_METER_VAULT_FAIL.Alarm.UACK,436156.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_METER_VAULT_FAIL.Alarm.MCmd_Enable,436156.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.MCmd_Disable,436156.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.OCmd_Shelve,436156.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.OCmd_Unshelve,436156.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.SCmd_Suppress,436156.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.SCmd_UnSuppress,436157.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_METER_VAULT_FAIL.Alarm.AEShelveTMRDN,436157.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_METER_VAULT_FAIL.Alarm.Bad,436157.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_METER_VAULT_FAIL.Alarm.Suppress,436158.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.UnSuppress,436158.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Shelve,436158.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.UnShelve,436158.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Enable,436158.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Disable,436158.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Ack,436158.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Reset,436158.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Suppressed,436158.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Shelved,436158.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Disabled,436158.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Acked,436158.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.Alarm,436158.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Fault,436168.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AlarmState,436168.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.GlobalReset,436168.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.FaultInAlarm,436168.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.ALRM,436168.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_METER_VAULT_FAIL.almPLCFault.ANUN,436168.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AKED,436168.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Resetable,436168.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_METER_VAULT_FAIL.almPLCFault.REST,436168.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.ACKN,436168.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.UACK,436168.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.MCmd_Enable,436168.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.MCmd_Disable,436168.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.OCmd_Shelve,436168.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.OCmd_Unshelve,436168.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.SCmd_Suppress,436168.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.SCmd_UnSuppress,436169.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AEShelveTMRDN,436169.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Bad,436169.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Suppress,436170.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.UnSuppress,436170.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Shelve,436170.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.UnShelve,436170.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Enable,436170.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Disable,436170.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Ack,436170.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Reset,436170.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Suppressed,436170.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Shelved,436170.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Disabled,436170.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Acked,436170.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.Alarm,436170.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Fault,436192.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AlarmState,436192.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.GlobalReset,436192.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.FaultInAlarm,436192.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.ALRM,436192.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.ANUN,436192.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AKED,436192.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Resetable,436192.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.REST,436192.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.ACKN,436192.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.UACK,436192.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.MCmd_Enable,436192.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.MCmd_Disable,436192.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.OCmd_Shelve,436192.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.OCmd_Unshelve,436192.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.SCmd_Suppress,436192.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.SCmd_UnSuppress,436193.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AEShelveTMRDN,436193.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Bad,436193.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Suppress,436194.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.UnSuppress,436194.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Shelve,436194.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.UnShelve,436194.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Enable,436194.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Disable,436194.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Ack,436194.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Reset,436194.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Suppressed,436194.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Shelved,436194.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Disabled,436194.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Acked,436194.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.Alarm,436194.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Fault,436204.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AlarmState,436204.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.GlobalReset,436204.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.FaultInAlarm,436204.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.ALRM,436204.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.ANUN,436204.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AKED,436204.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Resetable,436204.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.REST,436204.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.ACKN,436204.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.UACK,436204.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.MCmd_Enable,436204.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.MCmd_Disable,436204.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.OCmd_Shelve,436204.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.OCmd_Unshelve,436204.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.SCmd_Suppress,436204.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.SCmd_UnSuppress,436205.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AEShelveTMRDN,436205.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Bad,436205.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Suppress,436206.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.UnSuppress,436206.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Shelve,436206.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.UnShelve,436206.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Enable,436206.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Disable,436206.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Ack,436206.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Reset,436206.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Suppressed,436206.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Shelved,436206.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Disabled,436206.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Acked,436206.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.Alarm,436206.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Fault,436226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AlarmState,436226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.GlobalReset,436226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.FaultInAlarm,436226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.ALRM,436226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.ANUN,436226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AKED,436226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Resetable,436226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.REST,436226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.ACKN,436226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.UACK,436226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.MCmd_Enable,436226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.MCmd_Disable,436226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.OCmd_Shelve,436226.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.OCmd_Unshelve,436226.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.SCmd_Suppress,436226.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.SCmd_UnSuppress,436227.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AEShelveTMRDN,436227.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Bad,436227.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Suppress,436228.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.UnSuppress,436228.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Shelve,436228.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.UnShelve,436228.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Enable,436228.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Disable,436228.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Ack,436228.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Reset,436228.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Suppressed,436228.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Shelved,436228.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Disabled,436228.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Acked,436228.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.Alarm,436228.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Fault,436238.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AlarmState,436238.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.GlobalReset,436238.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.FaultInAlarm,436238.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.ALRM,436238.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.ANUN,436238.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AKED,436238.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Resetable,436238.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.REST,436238.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.ACKN,436238.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.UACK,436238.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.MCmd_Enable,436238.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.MCmd_Disable,436238.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.OCmd_Shelve,436238.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.OCmd_Unshelve,436238.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.SCmd_Suppress,436238.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.SCmd_UnSuppress,436239.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AEShelveTMRDN,436239.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Bad,436239.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Suppress,436240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.UnSuppress,436240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Shelve,436240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.UnShelve,436240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Enable,436240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Disable,436240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Ack,436240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Reset,436240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Suppressed,436240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Shelved,436240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Disabled,436240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Acked,436240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.Alarm,436240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Fault,436262.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AlarmState,436262.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.GlobalReset,436262.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.FaultInAlarm,436262.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.ALRM,436262.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.ANUN,436262.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AKED,436262.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Resetable,436262.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.REST,436262.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.ACKN,436262.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.UACK,436262.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.MCmd_Enable,436262.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.MCmd_Disable,436262.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.OCmd_Shelve,436262.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.OCmd_Unshelve,436262.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.SCmd_Suppress,436262.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.SCmd_UnSuppress,436263.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AEShelveTMRDN,436263.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Bad,436263.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Suppress,436264.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.UnSuppress,436264.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Shelve,436264.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.UnShelve,436264.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Enable,436264.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Disable,436264.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Ack,436264.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Reset,436264.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Suppressed,436264.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Shelved,436264.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Disabled,436264.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Acked,436264.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.Alarm,436264.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Fault,436274.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AlarmState,436274.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.GlobalReset,436274.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.FaultInAlarm,436274.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.ALRM,436274.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.ANUN,436274.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AKED,436274.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Resetable,436274.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.REST,436274.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.ACKN,436274.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.UACK,436274.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.MCmd_Enable,436274.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.MCmd_Disable,436274.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.OCmd_Shelve,436274.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.OCmd_Unshelve,436274.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.SCmd_Suppress,436274.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.SCmd_UnSuppress,436275.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AEShelveTMRDN,436275.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Bad,436275.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Suppress,436276.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.UnSuppress,436276.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Shelve,436276.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.UnShelve,436276.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Enable,436276.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Disable,436276.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Ack,436276.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Reset,436276.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Suppressed,436276.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Shelved,436276.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Disabled,436276.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Acked,436276.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.Alarm,436276.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Fault,436296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_TSR_PLC_FAIL.Alarm.AlarmState,436296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_TSR_PLC_FAIL.Alarm.GlobalReset,436296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_TSR_PLC_FAIL.Alarm.FaultInAlarm,436296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_TSR_PLC_FAIL.Alarm.ALRM,436296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_TSR_PLC_FAIL.Alarm.ANUN,436296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_TSR_PLC_FAIL.Alarm.AKED,436296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_TSR_PLC_FAIL.Alarm.Resetable,436296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_TSR_PLC_FAIL.Alarm.REST,436296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_TSR_PLC_FAIL.Alarm.ACKN,436296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_TSR_PLC_FAIL.Alarm.UACK,436296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_TSR_PLC_FAIL.Alarm.MCmd_Enable,436296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.MCmd_Disable,436296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.OCmd_Shelve,436296.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.OCmd_Unshelve,436296.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.SCmd_Suppress,436296.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.SCmd_UnSuppress,436297.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_TSR_PLC_FAIL.Alarm.AEShelveTMRDN,436297.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_TSR_PLC_FAIL.Alarm.Bad,436297.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_TSR_PLC_FAIL.Alarm.Suppress,436298.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.UnSuppress,436298.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Shelve,436298.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.UnShelve,436298.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Enable,436298.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Disable,436298.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Ack,436298.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Reset,436298.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Suppressed,436298.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Shelved,436298.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Disabled,436298.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Acked,436298.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.Alarm,436298.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Fault,436308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AlarmState,436308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.GlobalReset,436308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.FaultInAlarm,436308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.ALRM,436308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_TSR_PLC_FAIL.almPLCFault.ANUN,436308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AKED,436308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Resetable,436308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_TSR_PLC_FAIL.almPLCFault.REST,436308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.ACKN,436308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.UACK,436308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.MCmd_Enable,436308.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.MCmd_Disable,436308.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.OCmd_Shelve,436308.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.OCmd_Unshelve,436308.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.SCmd_Suppress,436308.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.SCmd_UnSuppress,436309.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AEShelveTMRDN,436309.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Bad,436309.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Suppress,436310.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.UnSuppress,436310.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Shelve,436310.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.UnShelve,436310.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Enable,436310.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Disable,436310.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Ack,436310.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Reset,436310.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Suppressed,436310.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Shelved,436310.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Disabled,436310.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Acked,436310.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.Alarm,436310.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Fault,436332.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_WESTMICRO_FAIL.Alarm.AlarmState,436332.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_WESTMICRO_FAIL.Alarm.GlobalReset,436332.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_WESTMICRO_FAIL.Alarm.FaultInAlarm,436332.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_WESTMICRO_FAIL.Alarm.ALRM,436332.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_WESTMICRO_FAIL.Alarm.ANUN,436332.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_WESTMICRO_FAIL.Alarm.AKED,436332.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_WESTMICRO_FAIL.Alarm.Resetable,436332.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_WESTMICRO_FAIL.Alarm.REST,436332.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_WESTMICRO_FAIL.Alarm.ACKN,436332.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_WESTMICRO_FAIL.Alarm.UACK,436332.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_WESTMICRO_FAIL.Alarm.MCmd_Enable,436332.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.MCmd_Disable,436332.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.OCmd_Shelve,436332.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.OCmd_Unshelve,436332.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.SCmd_Suppress,436332.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.SCmd_UnSuppress,436333.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_WESTMICRO_FAIL.Alarm.AEShelveTMRDN,436333.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_WESTMICRO_FAIL.Alarm.Bad,436333.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_WESTMICRO_FAIL.Alarm.Suppress,436334.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.UnSuppress,436334.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Shelve,436334.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.UnShelve,436334.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Enable,436334.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Disable,436334.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Ack,436334.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Reset,436334.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Suppressed,436334.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Shelved,436334.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Disabled,436334.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Acked,436334.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.Alarm,436334.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Fault,436344.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AlarmState,436344.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.GlobalReset,436344.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.FaultInAlarm,436344.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.ALRM,436344.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3260_COMM_WESTMICRO_FAIL.almPLCFault.ANUN,436344.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AKED,436344.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Resetable,436344.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3260_COMM_WESTMICRO_FAIL.almPLCFault.REST,436344.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.ACKN,436344.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.UACK,436344.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.MCmd_Enable,436344.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.MCmd_Disable,436344.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.OCmd_Shelve,436344.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.OCmd_Unshelve,436344.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.SCmd_Suppress,436344.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.SCmd_UnSuppress,436345.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AEShelveTMRDN,436345.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Bad,436345.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Suppress,436346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.UnSuppress,436346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Shelve,436346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.UnShelve,436346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Enable,436346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Disable,436346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Ack,436346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Reset,436346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Suppressed,436346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Shelved,436346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Disabled,436346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Acked,436346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.Alarm,436346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Fault,436410.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1.almFailToStrt.AlarmState,436410.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1.almFailToStrt.GlobalReset,436410.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1.almFailToStrt.FaultInAlarm,436410.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1.almFailToStrt.ALRM,436410.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1.almFailToStrt.ANUN,436410.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1.almFailToStrt.AKED,436410.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1.almFailToStrt.Resetable,436410.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1.almFailToStrt.REST,436410.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1.almFailToStrt.ACKN,436410.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1.almFailToStrt.UACK,436410.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1.almFailToStrt.MCmd_Enable,436410.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1.almFailToStrt.MCmd_Disable,436410.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1.almFailToStrt.OCmd_Shelve,436410.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1.almFailToStrt.OCmd_Unshelve,436410.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1.almFailToStrt.SCmd_Suppress,436410.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1.almFailToStrt.SCmd_UnSuppress,436411.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1.almFailToStrt.AEShelveTMRDN,436411.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1.almFailToStrt.Bad,436411.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1.almFailToStrt.Suppress,436412.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.UnSuppress,436412.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Shelve,436412.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.UnShelve,436412.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Enable,436412.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Disable,436412.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Ack,436412.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Reset,436412.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1.almFailToStrt.Suppressed,436412.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1.almFailToStrt.Shelved,436412.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1.almFailToStrt.Disabled,436412.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1.almFailToStrt.Acked,436412.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1.almFailToStrt.Alarm,436412.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Fault,436422.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1.almFailToStop.AlarmState,436422.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1.almFailToStop.GlobalReset,436422.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1.almFailToStop.FaultInAlarm,436422.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1.almFailToStop.ALRM,436422.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1.almFailToStop.ANUN,436422.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1.almFailToStop.AKED,436422.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1.almFailToStop.Resetable,436422.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1.almFailToStop.REST,436422.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1.almFailToStop.ACKN,436422.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1.almFailToStop.UACK,436422.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1.almFailToStop.MCmd_Enable,436422.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1.almFailToStop.MCmd_Disable,436422.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1.almFailToStop.OCmd_Shelve,436422.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1.almFailToStop.OCmd_Unshelve,436422.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1.almFailToStop.SCmd_Suppress,436422.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1.almFailToStop.SCmd_UnSuppress,436423.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1.almFailToStop.AEShelveTMRDN,436423.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1.almFailToStop.Bad,436423.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1.almFailToStop.Suppress,436424.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.UnSuppress,436424.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Shelve,436424.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.UnShelve,436424.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Enable,436424.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Disable,436424.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Ack,436424.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Reset,436424.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1.almFailToStop.Suppressed,436424.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1.almFailToStop.Shelved,436424.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1.almFailToStop.Disabled,436424.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1.almFailToStop.Acked,436424.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1.almFailToStop.Alarm,436424.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Fault,436434.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1.almMotorFailure.AlarmState,436434.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1.almMotorFailure.GlobalReset,436434.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1.almMotorFailure.FaultInAlarm,436434.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1.almMotorFailure.ALRM,436434.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1.almMotorFailure.ANUN,436434.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1.almMotorFailure.AKED,436434.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1.almMotorFailure.Resetable,436434.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1.almMotorFailure.REST,436434.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1.almMotorFailure.ACKN,436434.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1.almMotorFailure.UACK,436434.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1.almMotorFailure.MCmd_Enable,436434.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1.almMotorFailure.MCmd_Disable,436434.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1.almMotorFailure.OCmd_Shelve,436434.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1.almMotorFailure.OCmd_Unshelve,436434.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1.almMotorFailure.SCmd_Suppress,436434.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1.almMotorFailure.SCmd_UnSuppress,436435.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1.almMotorFailure.AEShelveTMRDN,436435.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1.almMotorFailure.Bad,436435.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1.almMotorFailure.Suppress,436436.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.UnSuppress,436436.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Shelve,436436.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.UnShelve,436436.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Enable,436436.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Disable,436436.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Ack,436436.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Reset,436436.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1.almMotorFailure.Suppressed,436436.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1.almMotorFailure.Shelved,436436.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1.almMotorFailure.Disabled,436436.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1.almMotorFailure.Acked,436436.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1.almMotorFailure.Alarm,436436.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Fault,436446.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1.almPLCFault.AlarmState,436446.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1.almPLCFault.GlobalReset,436446.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1.almPLCFault.FaultInAlarm,436446.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1.almPLCFault.ALRM,436446.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1.almPLCFault.ANUN,436446.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1.almPLCFault.AKED,436446.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1.almPLCFault.Resetable,436446.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1.almPLCFault.REST,436446.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1.almPLCFault.ACKN,436446.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1.almPLCFault.UACK,436446.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1.almPLCFault.MCmd_Enable,436446.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1.almPLCFault.MCmd_Disable,436446.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1.almPLCFault.OCmd_Shelve,436446.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1.almPLCFault.OCmd_Unshelve,436446.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1.almPLCFault.SCmd_Suppress,436446.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1.almPLCFault.SCmd_UnSuppress,436447.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1.almPLCFault.AEShelveTMRDN,436447.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1.almPLCFault.Bad,436447.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1.almPLCFault.Suppress,436448.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.UnSuppress,436448.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Shelve,436448.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.UnShelve,436448.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Enable,436448.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Disable,436448.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Ack,436448.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Reset,436448.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1.almPLCFault.Suppressed,436448.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1.almPLCFault.Shelved,436448.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1.almPLCFault.Disabled,436448.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1.almPLCFault.Acked,436448.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1.almPLCFault.Alarm,436448.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Fault,436458.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_1.almSpeedDeviation.AlarmState,436458.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_1.almSpeedDeviation.GlobalReset,436458.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_1.almSpeedDeviation.FaultInAlarm,436458.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_1.almSpeedDeviation.ALRM,436458.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_1.almSpeedDeviation.ANUN,436458.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_1.almSpeedDeviation.AKED,436458.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_1.almSpeedDeviation.Resetable,436458.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_1.almSpeedDeviation.REST,436458.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_1.almSpeedDeviation.ACKN,436458.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_1.almSpeedDeviation.UACK,436458.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_1.almSpeedDeviation.MCmd_Enable,436458.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_1.almSpeedDeviation.MCmd_Disable,436458.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_1.almSpeedDeviation.OCmd_Shelve,436458.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_1.almSpeedDeviation.OCmd_Unshelve,436458.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_1.almSpeedDeviation.SCmd_Suppress,436458.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_1.almSpeedDeviation.SCmd_UnSuppress,436459.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_1.almSpeedDeviation.AEShelveTMRDN,436459.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_1.almSpeedDeviation.Bad,436459.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_1.almSpeedDeviation.Suppress,436460.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.UnSuppress,436460.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Shelve,436460.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.UnShelve,436460.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Enable,436460.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Disable,436460.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Ack,436460.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Reset,436460.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Suppressed,436460.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Shelved,436460.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Disabled,436460.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Acked,436460.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_1.almSpeedDeviation.Alarm,436460.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Fault,436546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2.almFailToStrt.AlarmState,436546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2.almFailToStrt.GlobalReset,436546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2.almFailToStrt.FaultInAlarm,436546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2.almFailToStrt.ALRM,436546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2.almFailToStrt.ANUN,436546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2.almFailToStrt.AKED,436546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2.almFailToStrt.Resetable,436546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2.almFailToStrt.REST,436546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2.almFailToStrt.ACKN,436546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2.almFailToStrt.UACK,436546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2.almFailToStrt.MCmd_Enable,436546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2.almFailToStrt.MCmd_Disable,436546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2.almFailToStrt.OCmd_Shelve,436546.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2.almFailToStrt.OCmd_Unshelve,436546.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2.almFailToStrt.SCmd_Suppress,436546.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2.almFailToStrt.SCmd_UnSuppress,436547.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2.almFailToStrt.AEShelveTMRDN,436547.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2.almFailToStrt.Bad,436547.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2.almFailToStrt.Suppress,436548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.UnSuppress,436548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Shelve,436548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.UnShelve,436548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Enable,436548.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Disable,436548.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Ack,436548.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Reset,436548.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2.almFailToStrt.Suppressed,436548.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2.almFailToStrt.Shelved,436548.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2.almFailToStrt.Disabled,436548.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2.almFailToStrt.Acked,436548.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2.almFailToStrt.Alarm,436548.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Fault,436558.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2.almFailToStop.AlarmState,436558.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2.almFailToStop.GlobalReset,436558.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2.almFailToStop.FaultInAlarm,436558.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2.almFailToStop.ALRM,436558.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2.almFailToStop.ANUN,436558.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2.almFailToStop.AKED,436558.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2.almFailToStop.Resetable,436558.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2.almFailToStop.REST,436558.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2.almFailToStop.ACKN,436558.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2.almFailToStop.UACK,436558.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2.almFailToStop.MCmd_Enable,436558.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2.almFailToStop.MCmd_Disable,436558.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2.almFailToStop.OCmd_Shelve,436558.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2.almFailToStop.OCmd_Unshelve,436558.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2.almFailToStop.SCmd_Suppress,436558.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2.almFailToStop.SCmd_UnSuppress,436559.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2.almFailToStop.AEShelveTMRDN,436559.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2.almFailToStop.Bad,436559.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2.almFailToStop.Suppress,436560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.UnSuppress,436560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Shelve,436560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.UnShelve,436560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Enable,436560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Disable,436560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Ack,436560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Reset,436560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2.almFailToStop.Suppressed,436560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2.almFailToStop.Shelved,436560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2.almFailToStop.Disabled,436560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2.almFailToStop.Acked,436560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2.almFailToStop.Alarm,436560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Fault,436570.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2.almMotorFailure.AlarmState,436570.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2.almMotorFailure.GlobalReset,436570.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2.almMotorFailure.FaultInAlarm,436570.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2.almMotorFailure.ALRM,436570.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2.almMotorFailure.ANUN,436570.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2.almMotorFailure.AKED,436570.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2.almMotorFailure.Resetable,436570.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2.almMotorFailure.REST,436570.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2.almMotorFailure.ACKN,436570.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2.almMotorFailure.UACK,436570.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2.almMotorFailure.MCmd_Enable,436570.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2.almMotorFailure.MCmd_Disable,436570.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2.almMotorFailure.OCmd_Shelve,436570.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2.almMotorFailure.OCmd_Unshelve,436570.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2.almMotorFailure.SCmd_Suppress,436570.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2.almMotorFailure.SCmd_UnSuppress,436571.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2.almMotorFailure.AEShelveTMRDN,436571.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2.almMotorFailure.Bad,436571.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2.almMotorFailure.Suppress,436572.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.UnSuppress,436572.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Shelve,436572.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.UnShelve,436572.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Enable,436572.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Disable,436572.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Ack,436572.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Reset,436572.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2.almMotorFailure.Suppressed,436572.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2.almMotorFailure.Shelved,436572.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2.almMotorFailure.Disabled,436572.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2.almMotorFailure.Acked,436572.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2.almMotorFailure.Alarm,436572.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Fault,436582.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2.almPLCFault.AlarmState,436582.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2.almPLCFault.GlobalReset,436582.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2.almPLCFault.FaultInAlarm,436582.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2.almPLCFault.ALRM,436582.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2.almPLCFault.ANUN,436582.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2.almPLCFault.AKED,436582.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2.almPLCFault.Resetable,436582.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2.almPLCFault.REST,436582.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2.almPLCFault.ACKN,436582.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2.almPLCFault.UACK,436582.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2.almPLCFault.MCmd_Enable,436582.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2.almPLCFault.MCmd_Disable,436582.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2.almPLCFault.OCmd_Shelve,436582.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2.almPLCFault.OCmd_Unshelve,436582.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2.almPLCFault.SCmd_Suppress,436582.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2.almPLCFault.SCmd_UnSuppress,436583.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2.almPLCFault.AEShelveTMRDN,436583.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2.almPLCFault.Bad,436583.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2.almPLCFault.Suppress,436584.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.UnSuppress,436584.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Shelve,436584.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.UnShelve,436584.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Enable,436584.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Disable,436584.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Ack,436584.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Reset,436584.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2.almPLCFault.Suppressed,436584.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2.almPLCFault.Shelved,436584.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2.almPLCFault.Disabled,436584.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2.almPLCFault.Acked,436584.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2.almPLCFault.Alarm,436584.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Fault,436594.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_2.almSpeedDeviation.AlarmState,436594.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_2.almSpeedDeviation.GlobalReset,436594.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_2.almSpeedDeviation.FaultInAlarm,436594.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_2.almSpeedDeviation.ALRM,436594.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_2.almSpeedDeviation.ANUN,436594.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_2.almSpeedDeviation.AKED,436594.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_2.almSpeedDeviation.Resetable,436594.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_2.almSpeedDeviation.REST,436594.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_2.almSpeedDeviation.ACKN,436594.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_2.almSpeedDeviation.UACK,436594.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_2.almSpeedDeviation.MCmd_Enable,436594.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_2.almSpeedDeviation.MCmd_Disable,436594.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_2.almSpeedDeviation.OCmd_Shelve,436594.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_2.almSpeedDeviation.OCmd_Unshelve,436594.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_2.almSpeedDeviation.SCmd_Suppress,436594.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_2.almSpeedDeviation.SCmd_UnSuppress,436595.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_2.almSpeedDeviation.AEShelveTMRDN,436595.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_2.almSpeedDeviation.Bad,436595.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_2.almSpeedDeviation.Suppress,436596.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.UnSuppress,436596.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Shelve,436596.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.UnShelve,436596.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Enable,436596.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Disable,436596.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Ack,436596.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Reset,436596.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Suppressed,436596.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Shelved,436596.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Disabled,436596.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Acked,436596.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_2.almSpeedDeviation.Alarm,436596.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Fault,436680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3.almFailToStrt.AlarmState,436680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3.almFailToStrt.GlobalReset,436680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3.almFailToStrt.FaultInAlarm,436680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3.almFailToStrt.ALRM,436680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3.almFailToStrt.ANUN,436680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3.almFailToStrt.AKED,436680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3.almFailToStrt.Resetable,436680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3.almFailToStrt.REST,436680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3.almFailToStrt.ACKN,436680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3.almFailToStrt.UACK,436680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3.almFailToStrt.MCmd_Enable,436680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3.almFailToStrt.MCmd_Disable,436680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3.almFailToStrt.OCmd_Shelve,436680.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3.almFailToStrt.OCmd_Unshelve,436680.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3.almFailToStrt.SCmd_Suppress,436680.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3.almFailToStrt.SCmd_UnSuppress,436681.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3.almFailToStrt.AEShelveTMRDN,436681.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3.almFailToStrt.Bad,436681.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3.almFailToStrt.Suppress,436682.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.UnSuppress,436682.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Shelve,436682.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.UnShelve,436682.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Enable,436682.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Disable,436682.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Ack,436682.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Reset,436682.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3.almFailToStrt.Suppressed,436682.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3.almFailToStrt.Shelved,436682.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3.almFailToStrt.Disabled,436682.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3.almFailToStrt.Acked,436682.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3.almFailToStrt.Alarm,436682.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Fault,436692.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3.almFailToStop.AlarmState,436692.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3.almFailToStop.GlobalReset,436692.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3.almFailToStop.FaultInAlarm,436692.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3.almFailToStop.ALRM,436692.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3.almFailToStop.ANUN,436692.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3.almFailToStop.AKED,436692.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3.almFailToStop.Resetable,436692.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3.almFailToStop.REST,436692.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3.almFailToStop.ACKN,436692.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3.almFailToStop.UACK,436692.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3.almFailToStop.MCmd_Enable,436692.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3.almFailToStop.MCmd_Disable,436692.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3.almFailToStop.OCmd_Shelve,436692.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3.almFailToStop.OCmd_Unshelve,436692.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3.almFailToStop.SCmd_Suppress,436692.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3.almFailToStop.SCmd_UnSuppress,436693.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3.almFailToStop.AEShelveTMRDN,436693.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3.almFailToStop.Bad,436693.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3.almFailToStop.Suppress,436694.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.UnSuppress,436694.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Shelve,436694.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.UnShelve,436694.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Enable,436694.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Disable,436694.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Ack,436694.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Reset,436694.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3.almFailToStop.Suppressed,436694.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3.almFailToStop.Shelved,436694.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3.almFailToStop.Disabled,436694.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3.almFailToStop.Acked,436694.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3.almFailToStop.Alarm,436694.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Fault,436704.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3.almMotorFailure.AlarmState,436704.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3.almMotorFailure.GlobalReset,436704.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3.almMotorFailure.FaultInAlarm,436704.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3.almMotorFailure.ALRM,436704.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3.almMotorFailure.ANUN,436704.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3.almMotorFailure.AKED,436704.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3.almMotorFailure.Resetable,436704.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3.almMotorFailure.REST,436704.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3.almMotorFailure.ACKN,436704.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3.almMotorFailure.UACK,436704.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3.almMotorFailure.MCmd_Enable,436704.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3.almMotorFailure.MCmd_Disable,436704.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3.almMotorFailure.OCmd_Shelve,436704.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3.almMotorFailure.OCmd_Unshelve,436704.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3.almMotorFailure.SCmd_Suppress,436704.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3.almMotorFailure.SCmd_UnSuppress,436705.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3.almMotorFailure.AEShelveTMRDN,436705.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3.almMotorFailure.Bad,436705.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3.almMotorFailure.Suppress,436706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.UnSuppress,436706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Shelve,436706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.UnShelve,436706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Enable,436706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Disable,436706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Ack,436706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Reset,436706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3.almMotorFailure.Suppressed,436706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3.almMotorFailure.Shelved,436706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3.almMotorFailure.Disabled,436706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3.almMotorFailure.Acked,436706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3.almMotorFailure.Alarm,436706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Fault,436716.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3.almPLCFault.AlarmState,436716.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3.almPLCFault.GlobalReset,436716.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3.almPLCFault.FaultInAlarm,436716.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3.almPLCFault.ALRM,436716.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3.almPLCFault.ANUN,436716.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3.almPLCFault.AKED,436716.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3.almPLCFault.Resetable,436716.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3.almPLCFault.REST,436716.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3.almPLCFault.ACKN,436716.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3.almPLCFault.UACK,436716.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3.almPLCFault.MCmd_Enable,436716.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3.almPLCFault.MCmd_Disable,436716.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3.almPLCFault.OCmd_Shelve,436716.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3.almPLCFault.OCmd_Unshelve,436716.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3.almPLCFault.SCmd_Suppress,436716.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3.almPLCFault.SCmd_UnSuppress,436717.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3.almPLCFault.AEShelveTMRDN,436717.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3.almPLCFault.Bad,436717.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3.almPLCFault.Suppress,436718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.UnSuppress,436718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Shelve,436718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.UnShelve,436718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Enable,436718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Disable,436718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Ack,436718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Reset,436718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3.almPLCFault.Suppressed,436718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3.almPLCFault.Shelved,436718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3.almPLCFault.Disabled,436718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3.almPLCFault.Acked,436718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3.almPLCFault.Alarm,436718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Fault,436728.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_3.almSpeedDeviation.AlarmState,436728.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_3.almSpeedDeviation.GlobalReset,436728.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_3.almSpeedDeviation.FaultInAlarm,436728.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_3.almSpeedDeviation.ALRM,436728.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_3.almSpeedDeviation.ANUN,436728.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_3.almSpeedDeviation.AKED,436728.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_3.almSpeedDeviation.Resetable,436728.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_3.almSpeedDeviation.REST,436728.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_3.almSpeedDeviation.ACKN,436728.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_3.almSpeedDeviation.UACK,436728.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_3.almSpeedDeviation.MCmd_Enable,436728.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_3.almSpeedDeviation.MCmd_Disable,436728.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_3.almSpeedDeviation.OCmd_Shelve,436728.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_3.almSpeedDeviation.OCmd_Unshelve,436728.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_3.almSpeedDeviation.SCmd_Suppress,436728.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_3.almSpeedDeviation.SCmd_UnSuppress,436729.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_3.almSpeedDeviation.AEShelveTMRDN,436729.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_3.almSpeedDeviation.Bad,436729.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_3.almSpeedDeviation.Suppress,436730.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.UnSuppress,436730.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Shelve,436730.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.UnShelve,436730.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Enable,436730.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Disable,436730.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Ack,436730.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Reset,436730.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Suppressed,436730.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Shelved,436730.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Disabled,436730.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Acked,436730.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_3.almSpeedDeviation.Alarm,436730.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Fault,436816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4.almFailToStrt.AlarmState,436816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4.almFailToStrt.GlobalReset,436816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4.almFailToStrt.FaultInAlarm,436816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4.almFailToStrt.ALRM,436816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4.almFailToStrt.ANUN,436816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4.almFailToStrt.AKED,436816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4.almFailToStrt.Resetable,436816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4.almFailToStrt.REST,436816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4.almFailToStrt.ACKN,436816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4.almFailToStrt.UACK,436816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4.almFailToStrt.MCmd_Enable,436816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4.almFailToStrt.MCmd_Disable,436816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4.almFailToStrt.OCmd_Shelve,436816.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4.almFailToStrt.OCmd_Unshelve,436816.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4.almFailToStrt.SCmd_Suppress,436816.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4.almFailToStrt.SCmd_UnSuppress,436817.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4.almFailToStrt.AEShelveTMRDN,436817.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4.almFailToStrt.Bad,436817.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4.almFailToStrt.Suppress,436818.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.UnSuppress,436818.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Shelve,436818.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.UnShelve,436818.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Enable,436818.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Disable,436818.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Ack,436818.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Reset,436818.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4.almFailToStrt.Suppressed,436818.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4.almFailToStrt.Shelved,436818.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4.almFailToStrt.Disabled,436818.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4.almFailToStrt.Acked,436818.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4.almFailToStrt.Alarm,436818.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Fault,436828.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4.almFailToStop.AlarmState,436828.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4.almFailToStop.GlobalReset,436828.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4.almFailToStop.FaultInAlarm,436828.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4.almFailToStop.ALRM,436828.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4.almFailToStop.ANUN,436828.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4.almFailToStop.AKED,436828.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4.almFailToStop.Resetable,436828.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4.almFailToStop.REST,436828.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4.almFailToStop.ACKN,436828.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4.almFailToStop.UACK,436828.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4.almFailToStop.MCmd_Enable,436828.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4.almFailToStop.MCmd_Disable,436828.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4.almFailToStop.OCmd_Shelve,436828.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4.almFailToStop.OCmd_Unshelve,436828.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4.almFailToStop.SCmd_Suppress,436828.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4.almFailToStop.SCmd_UnSuppress,436829.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4.almFailToStop.AEShelveTMRDN,436829.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4.almFailToStop.Bad,436829.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4.almFailToStop.Suppress,436830.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.UnSuppress,436830.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Shelve,436830.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.UnShelve,436830.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Enable,436830.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Disable,436830.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Ack,436830.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Reset,436830.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4.almFailToStop.Suppressed,436830.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4.almFailToStop.Shelved,436830.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4.almFailToStop.Disabled,436830.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4.almFailToStop.Acked,436830.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4.almFailToStop.Alarm,436830.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Fault,436840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4.almMotorFailure.AlarmState,436840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4.almMotorFailure.GlobalReset,436840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4.almMotorFailure.FaultInAlarm,436840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4.almMotorFailure.ALRM,436840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4.almMotorFailure.ANUN,436840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4.almMotorFailure.AKED,436840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4.almMotorFailure.Resetable,436840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4.almMotorFailure.REST,436840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4.almMotorFailure.ACKN,436840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4.almMotorFailure.UACK,436840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4.almMotorFailure.MCmd_Enable,436840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4.almMotorFailure.MCmd_Disable,436840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4.almMotorFailure.OCmd_Shelve,436840.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4.almMotorFailure.OCmd_Unshelve,436840.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4.almMotorFailure.SCmd_Suppress,436840.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4.almMotorFailure.SCmd_UnSuppress,436841.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4.almMotorFailure.AEShelveTMRDN,436841.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4.almMotorFailure.Bad,436841.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4.almMotorFailure.Suppress,436842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.UnSuppress,436842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Shelve,436842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.UnShelve,436842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Enable,436842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Disable,436842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Ack,436842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Reset,436842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4.almMotorFailure.Suppressed,436842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4.almMotorFailure.Shelved,436842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4.almMotorFailure.Disabled,436842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4.almMotorFailure.Acked,436842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4.almMotorFailure.Alarm,436842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Fault,436852.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4.almPLCFault.AlarmState,436852.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4.almPLCFault.GlobalReset,436852.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4.almPLCFault.FaultInAlarm,436852.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4.almPLCFault.ALRM,436852.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4.almPLCFault.ANUN,436852.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4.almPLCFault.AKED,436852.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4.almPLCFault.Resetable,436852.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4.almPLCFault.REST,436852.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4.almPLCFault.ACKN,436852.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4.almPLCFault.UACK,436852.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4.almPLCFault.MCmd_Enable,436852.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4.almPLCFault.MCmd_Disable,436852.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4.almPLCFault.OCmd_Shelve,436852.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4.almPLCFault.OCmd_Unshelve,436852.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4.almPLCFault.SCmd_Suppress,436852.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4.almPLCFault.SCmd_UnSuppress,436853.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4.almPLCFault.AEShelveTMRDN,436853.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4.almPLCFault.Bad,436853.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4.almPLCFault.Suppress,436854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.UnSuppress,436854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Shelve,436854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.UnShelve,436854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Enable,436854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Disable,436854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Ack,436854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Reset,436854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4.almPLCFault.Suppressed,436854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4.almPLCFault.Shelved,436854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4.almPLCFault.Disabled,436854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4.almPLCFault.Acked,436854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4.almPLCFault.Alarm,436854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Fault,436864.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_4.almSpeedDeviation.AlarmState,436864.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_4.almSpeedDeviation.GlobalReset,436864.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_4.almSpeedDeviation.FaultInAlarm,436864.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_4.almSpeedDeviation.ALRM,436864.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_4.almSpeedDeviation.ANUN,436864.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_4.almSpeedDeviation.AKED,436864.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_4.almSpeedDeviation.Resetable,436864.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_4.almSpeedDeviation.REST,436864.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_4.almSpeedDeviation.ACKN,436864.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_4.almSpeedDeviation.UACK,436864.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_4.almSpeedDeviation.MCmd_Enable,436864.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_4.almSpeedDeviation.MCmd_Disable,436864.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_4.almSpeedDeviation.OCmd_Shelve,436864.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_4.almSpeedDeviation.OCmd_Unshelve,436864.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_4.almSpeedDeviation.SCmd_Suppress,436864.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_4.almSpeedDeviation.SCmd_UnSuppress,436865.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_4.almSpeedDeviation.AEShelveTMRDN,436865.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_4.almSpeedDeviation.Bad,436865.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_4.almSpeedDeviation.Suppress,436866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.UnSuppress,436866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Shelve,436866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.UnShelve,436866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Enable,436866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Disable,436866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Ack,436866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Reset,436866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Suppressed,436866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Shelved,436866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Disabled,436866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Acked,436866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_4.almSpeedDeviation.Alarm,436866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Fault,436950.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5.almFailToStrt.AlarmState,436950.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5.almFailToStrt.GlobalReset,436950.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5.almFailToStrt.FaultInAlarm,436950.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5.almFailToStrt.ALRM,436950.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5.almFailToStrt.ANUN,436950.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5.almFailToStrt.AKED,436950.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5.almFailToStrt.Resetable,436950.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5.almFailToStrt.REST,436950.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5.almFailToStrt.ACKN,436950.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5.almFailToStrt.UACK,436950.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5.almFailToStrt.MCmd_Enable,436950.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5.almFailToStrt.MCmd_Disable,436950.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5.almFailToStrt.OCmd_Shelve,436950.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5.almFailToStrt.OCmd_Unshelve,436950.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5.almFailToStrt.SCmd_Suppress,436950.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5.almFailToStrt.SCmd_UnSuppress,436951.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5.almFailToStrt.AEShelveTMRDN,436951.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5.almFailToStrt.Bad,436951.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5.almFailToStrt.Suppress,436952.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.UnSuppress,436952.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Shelve,436952.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.UnShelve,436952.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Enable,436952.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Disable,436952.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Ack,436952.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Reset,436952.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5.almFailToStrt.Suppressed,436952.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5.almFailToStrt.Shelved,436952.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5.almFailToStrt.Disabled,436952.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5.almFailToStrt.Acked,436952.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5.almFailToStrt.Alarm,436952.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Fault,436962.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5.almFailToStop.AlarmState,436962.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5.almFailToStop.GlobalReset,436962.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5.almFailToStop.FaultInAlarm,436962.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5.almFailToStop.ALRM,436962.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5.almFailToStop.ANUN,436962.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5.almFailToStop.AKED,436962.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5.almFailToStop.Resetable,436962.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5.almFailToStop.REST,436962.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5.almFailToStop.ACKN,436962.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5.almFailToStop.UACK,436962.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5.almFailToStop.MCmd_Enable,436962.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5.almFailToStop.MCmd_Disable,436962.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5.almFailToStop.OCmd_Shelve,436962.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5.almFailToStop.OCmd_Unshelve,436962.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5.almFailToStop.SCmd_Suppress,436962.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5.almFailToStop.SCmd_UnSuppress,436963.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5.almFailToStop.AEShelveTMRDN,436963.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5.almFailToStop.Bad,436963.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5.almFailToStop.Suppress,436964.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.UnSuppress,436964.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Shelve,436964.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.UnShelve,436964.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Enable,436964.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Disable,436964.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Ack,436964.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Reset,436964.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5.almFailToStop.Suppressed,436964.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5.almFailToStop.Shelved,436964.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5.almFailToStop.Disabled,436964.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5.almFailToStop.Acked,436964.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5.almFailToStop.Alarm,436964.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Fault,436974.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5.almMotorFailure.AlarmState,436974.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5.almMotorFailure.GlobalReset,436974.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5.almMotorFailure.FaultInAlarm,436974.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5.almMotorFailure.ALRM,436974.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5.almMotorFailure.ANUN,436974.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5.almMotorFailure.AKED,436974.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5.almMotorFailure.Resetable,436974.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5.almMotorFailure.REST,436974.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5.almMotorFailure.ACKN,436974.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5.almMotorFailure.UACK,436974.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5.almMotorFailure.MCmd_Enable,436974.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5.almMotorFailure.MCmd_Disable,436974.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5.almMotorFailure.OCmd_Shelve,436974.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5.almMotorFailure.OCmd_Unshelve,436974.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5.almMotorFailure.SCmd_Suppress,436974.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5.almMotorFailure.SCmd_UnSuppress,436975.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5.almMotorFailure.AEShelveTMRDN,436975.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5.almMotorFailure.Bad,436975.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5.almMotorFailure.Suppress,436976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.UnSuppress,436976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Shelve,436976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.UnShelve,436976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Enable,436976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Disable,436976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Ack,436976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Reset,436976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5.almMotorFailure.Suppressed,436976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5.almMotorFailure.Shelved,436976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5.almMotorFailure.Disabled,436976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5.almMotorFailure.Acked,436976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5.almMotorFailure.Alarm,436976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Fault,436986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5.almPLCFault.AlarmState,436986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5.almPLCFault.GlobalReset,436986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5.almPLCFault.FaultInAlarm,436986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5.almPLCFault.ALRM,436986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5.almPLCFault.ANUN,436986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5.almPLCFault.AKED,436986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5.almPLCFault.Resetable,436986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5.almPLCFault.REST,436986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5.almPLCFault.ACKN,436986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5.almPLCFault.UACK,436986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5.almPLCFault.MCmd_Enable,436986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5.almPLCFault.MCmd_Disable,436986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5.almPLCFault.OCmd_Shelve,436986.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5.almPLCFault.OCmd_Unshelve,436986.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5.almPLCFault.SCmd_Suppress,436986.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5.almPLCFault.SCmd_UnSuppress,436987.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5.almPLCFault.AEShelveTMRDN,436987.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5.almPLCFault.Bad,436987.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5.almPLCFault.Suppress,436988.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.UnSuppress,436988.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Shelve,436988.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.UnShelve,436988.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Enable,436988.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Disable,436988.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Ack,436988.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Reset,436988.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5.almPLCFault.Suppressed,436988.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5.almPLCFault.Shelved,436988.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5.almPLCFault.Disabled,436988.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5.almPLCFault.Acked,436988.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5.almPLCFault.Alarm,436988.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Fault,436998.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_5.almSpeedDeviation.AlarmState,436998.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_5.almSpeedDeviation.GlobalReset,436998.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_5.almSpeedDeviation.FaultInAlarm,436998.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_5.almSpeedDeviation.ALRM,436998.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_5.almSpeedDeviation.ANUN,436998.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_5.almSpeedDeviation.AKED,436998.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_5.almSpeedDeviation.Resetable,436998.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_5.almSpeedDeviation.REST,436998.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_5.almSpeedDeviation.ACKN,436998.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_5.almSpeedDeviation.UACK,436998.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_5.almSpeedDeviation.MCmd_Enable,436998.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_5.almSpeedDeviation.MCmd_Disable,436998.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_5.almSpeedDeviation.OCmd_Shelve,436998.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_5.almSpeedDeviation.OCmd_Unshelve,436998.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_5.almSpeedDeviation.SCmd_Suppress,436998.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_5.almSpeedDeviation.SCmd_UnSuppress,436999.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_5.almSpeedDeviation.AEShelveTMRDN,436999.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_5.almSpeedDeviation.Bad,436999.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_5.almSpeedDeviation.Suppress,437000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.UnSuppress,437000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Shelve,437000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.UnShelve,437000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Enable,437000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Disable,437000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Ack,437000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Reset,437000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Suppressed,437000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Shelved,437000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Disabled,437000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Acked,437000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_5.almSpeedDeviation.Alarm,437000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Fault,437086.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6.almFailToStrt.AlarmState,437086.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6.almFailToStrt.GlobalReset,437086.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6.almFailToStrt.FaultInAlarm,437086.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6.almFailToStrt.ALRM,437086.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6.almFailToStrt.ANUN,437086.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6.almFailToStrt.AKED,437086.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6.almFailToStrt.Resetable,437086.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6.almFailToStrt.REST,437086.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6.almFailToStrt.ACKN,437086.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6.almFailToStrt.UACK,437086.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6.almFailToStrt.MCmd_Enable,437086.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6.almFailToStrt.MCmd_Disable,437086.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6.almFailToStrt.OCmd_Shelve,437086.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6.almFailToStrt.OCmd_Unshelve,437086.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6.almFailToStrt.SCmd_Suppress,437086.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6.almFailToStrt.SCmd_UnSuppress,437087.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6.almFailToStrt.AEShelveTMRDN,437087.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6.almFailToStrt.Bad,437087.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6.almFailToStrt.Suppress,437088.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.UnSuppress,437088.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Shelve,437088.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.UnShelve,437088.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Enable,437088.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Disable,437088.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Ack,437088.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Reset,437088.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6.almFailToStrt.Suppressed,437088.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6.almFailToStrt.Shelved,437088.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6.almFailToStrt.Disabled,437088.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6.almFailToStrt.Acked,437088.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6.almFailToStrt.Alarm,437088.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Fault,437098.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6.almFailToStop.AlarmState,437098.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6.almFailToStop.GlobalReset,437098.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6.almFailToStop.FaultInAlarm,437098.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6.almFailToStop.ALRM,437098.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6.almFailToStop.ANUN,437098.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6.almFailToStop.AKED,437098.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6.almFailToStop.Resetable,437098.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6.almFailToStop.REST,437098.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6.almFailToStop.ACKN,437098.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6.almFailToStop.UACK,437098.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6.almFailToStop.MCmd_Enable,437098.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6.almFailToStop.MCmd_Disable,437098.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6.almFailToStop.OCmd_Shelve,437098.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6.almFailToStop.OCmd_Unshelve,437098.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6.almFailToStop.SCmd_Suppress,437098.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6.almFailToStop.SCmd_UnSuppress,437099.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6.almFailToStop.AEShelveTMRDN,437099.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6.almFailToStop.Bad,437099.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6.almFailToStop.Suppress,437100.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.UnSuppress,437100.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Shelve,437100.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.UnShelve,437100.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Enable,437100.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Disable,437100.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Ack,437100.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Reset,437100.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6.almFailToStop.Suppressed,437100.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6.almFailToStop.Shelved,437100.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6.almFailToStop.Disabled,437100.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6.almFailToStop.Acked,437100.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6.almFailToStop.Alarm,437100.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Fault,437110.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6.almMotorFailure.AlarmState,437110.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6.almMotorFailure.GlobalReset,437110.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6.almMotorFailure.FaultInAlarm,437110.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6.almMotorFailure.ALRM,437110.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6.almMotorFailure.ANUN,437110.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6.almMotorFailure.AKED,437110.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6.almMotorFailure.Resetable,437110.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6.almMotorFailure.REST,437110.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6.almMotorFailure.ACKN,437110.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6.almMotorFailure.UACK,437110.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6.almMotorFailure.MCmd_Enable,437110.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6.almMotorFailure.MCmd_Disable,437110.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6.almMotorFailure.OCmd_Shelve,437110.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6.almMotorFailure.OCmd_Unshelve,437110.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6.almMotorFailure.SCmd_Suppress,437110.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6.almMotorFailure.SCmd_UnSuppress,437111.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6.almMotorFailure.AEShelveTMRDN,437111.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6.almMotorFailure.Bad,437111.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6.almMotorFailure.Suppress,437112.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.UnSuppress,437112.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Shelve,437112.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.UnShelve,437112.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Enable,437112.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Disable,437112.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Ack,437112.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Reset,437112.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6.almMotorFailure.Suppressed,437112.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6.almMotorFailure.Shelved,437112.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6.almMotorFailure.Disabled,437112.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6.almMotorFailure.Acked,437112.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6.almMotorFailure.Alarm,437112.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Fault,437122.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6.almPLCFault.AlarmState,437122.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6.almPLCFault.GlobalReset,437122.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6.almPLCFault.FaultInAlarm,437122.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6.almPLCFault.ALRM,437122.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6.almPLCFault.ANUN,437122.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6.almPLCFault.AKED,437122.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6.almPLCFault.Resetable,437122.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6.almPLCFault.REST,437122.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6.almPLCFault.ACKN,437122.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6.almPLCFault.UACK,437122.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6.almPLCFault.MCmd_Enable,437122.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6.almPLCFault.MCmd_Disable,437122.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6.almPLCFault.OCmd_Shelve,437122.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6.almPLCFault.OCmd_Unshelve,437122.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6.almPLCFault.SCmd_Suppress,437122.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6.almPLCFault.SCmd_UnSuppress,437123.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6.almPLCFault.AEShelveTMRDN,437123.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6.almPLCFault.Bad,437123.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6.almPLCFault.Suppress,437124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.UnSuppress,437124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Shelve,437124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.UnShelve,437124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Enable,437124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Disable,437124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Ack,437124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Reset,437124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6.almPLCFault.Suppressed,437124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6.almPLCFault.Shelved,437124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6.almPLCFault.Disabled,437124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6.almPLCFault.Acked,437124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6.almPLCFault.Alarm,437124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Fault,437134.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_6.almSpeedDeviation.AlarmState,437134.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_6.almSpeedDeviation.GlobalReset,437134.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_6.almSpeedDeviation.FaultInAlarm,437134.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_6.almSpeedDeviation.ALRM,437134.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_6.almSpeedDeviation.ANUN,437134.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_6.almSpeedDeviation.AKED,437134.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_6.almSpeedDeviation.Resetable,437134.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_6.almSpeedDeviation.REST,437134.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_6.almSpeedDeviation.ACKN,437134.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_6.almSpeedDeviation.UACK,437134.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_6.almSpeedDeviation.MCmd_Enable,437134.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_6.almSpeedDeviation.MCmd_Disable,437134.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_6.almSpeedDeviation.OCmd_Shelve,437134.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_6.almSpeedDeviation.OCmd_Unshelve,437134.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_6.almSpeedDeviation.SCmd_Suppress,437134.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_6.almSpeedDeviation.SCmd_UnSuppress,437135.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_6.almSpeedDeviation.AEShelveTMRDN,437135.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_6.almSpeedDeviation.Bad,437135.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_6.almSpeedDeviation.Suppress,437136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.UnSuppress,437136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Shelve,437136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.UnShelve,437136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Enable,437136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Disable,437136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Ack,437136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Reset,437136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Suppressed,437136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Shelved,437136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Disabled,437136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Acked,437136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_6.almSpeedDeviation.Alarm,437136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Fault,437220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7.almFailToStrt.AlarmState,437220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7.almFailToStrt.GlobalReset,437220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7.almFailToStrt.FaultInAlarm,437220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7.almFailToStrt.ALRM,437220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7.almFailToStrt.ANUN,437220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7.almFailToStrt.AKED,437220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7.almFailToStrt.Resetable,437220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7.almFailToStrt.REST,437220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7.almFailToStrt.ACKN,437220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7.almFailToStrt.UACK,437220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7.almFailToStrt.MCmd_Enable,437220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7.almFailToStrt.MCmd_Disable,437220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7.almFailToStrt.OCmd_Shelve,437220.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7.almFailToStrt.OCmd_Unshelve,437220.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7.almFailToStrt.SCmd_Suppress,437220.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7.almFailToStrt.SCmd_UnSuppress,437221.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7.almFailToStrt.AEShelveTMRDN,437221.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7.almFailToStrt.Bad,437221.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7.almFailToStrt.Suppress,437222.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.UnSuppress,437222.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Shelve,437222.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.UnShelve,437222.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Enable,437222.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Disable,437222.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Ack,437222.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Reset,437222.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7.almFailToStrt.Suppressed,437222.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7.almFailToStrt.Shelved,437222.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7.almFailToStrt.Disabled,437222.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7.almFailToStrt.Acked,437222.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7.almFailToStrt.Alarm,437222.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Fault,437232.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7.almFailToStop.AlarmState,437232.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7.almFailToStop.GlobalReset,437232.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7.almFailToStop.FaultInAlarm,437232.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7.almFailToStop.ALRM,437232.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7.almFailToStop.ANUN,437232.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7.almFailToStop.AKED,437232.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7.almFailToStop.Resetable,437232.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7.almFailToStop.REST,437232.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7.almFailToStop.ACKN,437232.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7.almFailToStop.UACK,437232.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7.almFailToStop.MCmd_Enable,437232.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7.almFailToStop.MCmd_Disable,437232.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7.almFailToStop.OCmd_Shelve,437232.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7.almFailToStop.OCmd_Unshelve,437232.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7.almFailToStop.SCmd_Suppress,437232.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7.almFailToStop.SCmd_UnSuppress,437233.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7.almFailToStop.AEShelveTMRDN,437233.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7.almFailToStop.Bad,437233.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7.almFailToStop.Suppress,437234.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.UnSuppress,437234.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Shelve,437234.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.UnShelve,437234.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Enable,437234.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Disable,437234.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Ack,437234.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Reset,437234.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7.almFailToStop.Suppressed,437234.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7.almFailToStop.Shelved,437234.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7.almFailToStop.Disabled,437234.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7.almFailToStop.Acked,437234.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7.almFailToStop.Alarm,437234.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Fault,437244.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7.almMotorFailure.AlarmState,437244.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7.almMotorFailure.GlobalReset,437244.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7.almMotorFailure.FaultInAlarm,437244.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7.almMotorFailure.ALRM,437244.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7.almMotorFailure.ANUN,437244.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7.almMotorFailure.AKED,437244.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7.almMotorFailure.Resetable,437244.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7.almMotorFailure.REST,437244.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7.almMotorFailure.ACKN,437244.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7.almMotorFailure.UACK,437244.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7.almMotorFailure.MCmd_Enable,437244.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7.almMotorFailure.MCmd_Disable,437244.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7.almMotorFailure.OCmd_Shelve,437244.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7.almMotorFailure.OCmd_Unshelve,437244.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7.almMotorFailure.SCmd_Suppress,437244.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7.almMotorFailure.SCmd_UnSuppress,437245.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7.almMotorFailure.AEShelveTMRDN,437245.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7.almMotorFailure.Bad,437245.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7.almMotorFailure.Suppress,437246.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.UnSuppress,437246.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Shelve,437246.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.UnShelve,437246.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Enable,437246.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Disable,437246.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Ack,437246.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Reset,437246.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7.almMotorFailure.Suppressed,437246.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7.almMotorFailure.Shelved,437246.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7.almMotorFailure.Disabled,437246.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7.almMotorFailure.Acked,437246.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7.almMotorFailure.Alarm,437246.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Fault,437256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7.almPLCFault.AlarmState,437256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7.almPLCFault.GlobalReset,437256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7.almPLCFault.FaultInAlarm,437256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7.almPLCFault.ALRM,437256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7.almPLCFault.ANUN,437256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7.almPLCFault.AKED,437256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7.almPLCFault.Resetable,437256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7.almPLCFault.REST,437256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7.almPLCFault.ACKN,437256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7.almPLCFault.UACK,437256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7.almPLCFault.MCmd_Enable,437256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7.almPLCFault.MCmd_Disable,437256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7.almPLCFault.OCmd_Shelve,437256.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7.almPLCFault.OCmd_Unshelve,437256.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7.almPLCFault.SCmd_Suppress,437256.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7.almPLCFault.SCmd_UnSuppress,437257.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7.almPLCFault.AEShelveTMRDN,437257.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7.almPLCFault.Bad,437257.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7.almPLCFault.Suppress,437258.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.UnSuppress,437258.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Shelve,437258.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.UnShelve,437258.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Enable,437258.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Disable,437258.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Ack,437258.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Reset,437258.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7.almPLCFault.Suppressed,437258.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7.almPLCFault.Shelved,437258.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7.almPLCFault.Disabled,437258.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7.almPLCFault.Acked,437258.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7.almPLCFault.Alarm,437258.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Fault,437268.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_7.almSpeedDeviation.AlarmState,437268.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_7.almSpeedDeviation.GlobalReset,437268.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_7.almSpeedDeviation.FaultInAlarm,437268.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_7.almSpeedDeviation.ALRM,437268.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_7.almSpeedDeviation.ANUN,437268.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_7.almSpeedDeviation.AKED,437268.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_7.almSpeedDeviation.Resetable,437268.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_7.almSpeedDeviation.REST,437268.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_7.almSpeedDeviation.ACKN,437268.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_7.almSpeedDeviation.UACK,437268.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_7.almSpeedDeviation.MCmd_Enable,437268.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_7.almSpeedDeviation.MCmd_Disable,437268.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_7.almSpeedDeviation.OCmd_Shelve,437268.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_7.almSpeedDeviation.OCmd_Unshelve,437268.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_7.almSpeedDeviation.SCmd_Suppress,437268.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_7.almSpeedDeviation.SCmd_UnSuppress,437269.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_7.almSpeedDeviation.AEShelveTMRDN,437269.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_7.almSpeedDeviation.Bad,437269.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_7.almSpeedDeviation.Suppress,437270.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.UnSuppress,437270.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Shelve,437270.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.UnShelve,437270.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Enable,437270.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Disable,437270.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Ack,437270.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Reset,437270.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Suppressed,437270.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Shelved,437270.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Disabled,437270.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Acked,437270.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_7.almSpeedDeviation.Alarm,437270.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Fault,437356.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8.almFailToStrt.AlarmState,437356.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8.almFailToStrt.GlobalReset,437356.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8.almFailToStrt.FaultInAlarm,437356.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8.almFailToStrt.ALRM,437356.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8.almFailToStrt.ANUN,437356.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8.almFailToStrt.AKED,437356.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8.almFailToStrt.Resetable,437356.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8.almFailToStrt.REST,437356.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8.almFailToStrt.ACKN,437356.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8.almFailToStrt.UACK,437356.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8.almFailToStrt.MCmd_Enable,437356.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8.almFailToStrt.MCmd_Disable,437356.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8.almFailToStrt.OCmd_Shelve,437356.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8.almFailToStrt.OCmd_Unshelve,437356.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8.almFailToStrt.SCmd_Suppress,437356.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8.almFailToStrt.SCmd_UnSuppress,437357.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8.almFailToStrt.AEShelveTMRDN,437357.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8.almFailToStrt.Bad,437357.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8.almFailToStrt.Suppress,437358.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.UnSuppress,437358.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Shelve,437358.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.UnShelve,437358.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Enable,437358.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Disable,437358.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Ack,437358.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Reset,437358.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8.almFailToStrt.Suppressed,437358.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8.almFailToStrt.Shelved,437358.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8.almFailToStrt.Disabled,437358.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8.almFailToStrt.Acked,437358.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8.almFailToStrt.Alarm,437358.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Fault,437368.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8.almFailToStop.AlarmState,437368.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8.almFailToStop.GlobalReset,437368.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8.almFailToStop.FaultInAlarm,437368.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8.almFailToStop.ALRM,437368.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8.almFailToStop.ANUN,437368.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8.almFailToStop.AKED,437368.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8.almFailToStop.Resetable,437368.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8.almFailToStop.REST,437368.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8.almFailToStop.ACKN,437368.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8.almFailToStop.UACK,437368.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8.almFailToStop.MCmd_Enable,437368.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8.almFailToStop.MCmd_Disable,437368.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8.almFailToStop.OCmd_Shelve,437368.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8.almFailToStop.OCmd_Unshelve,437368.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8.almFailToStop.SCmd_Suppress,437368.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8.almFailToStop.SCmd_UnSuppress,437369.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8.almFailToStop.AEShelveTMRDN,437369.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8.almFailToStop.Bad,437369.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8.almFailToStop.Suppress,437370.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.UnSuppress,437370.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Shelve,437370.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.UnShelve,437370.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Enable,437370.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Disable,437370.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Ack,437370.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Reset,437370.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8.almFailToStop.Suppressed,437370.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8.almFailToStop.Shelved,437370.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8.almFailToStop.Disabled,437370.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8.almFailToStop.Acked,437370.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8.almFailToStop.Alarm,437370.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Fault,437380.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8.almMotorFailure.AlarmState,437380.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8.almMotorFailure.GlobalReset,437380.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8.almMotorFailure.FaultInAlarm,437380.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8.almMotorFailure.ALRM,437380.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8.almMotorFailure.ANUN,437380.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8.almMotorFailure.AKED,437380.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8.almMotorFailure.Resetable,437380.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8.almMotorFailure.REST,437380.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8.almMotorFailure.ACKN,437380.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8.almMotorFailure.UACK,437380.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8.almMotorFailure.MCmd_Enable,437380.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8.almMotorFailure.MCmd_Disable,437380.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8.almMotorFailure.OCmd_Shelve,437380.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8.almMotorFailure.OCmd_Unshelve,437380.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8.almMotorFailure.SCmd_Suppress,437380.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8.almMotorFailure.SCmd_UnSuppress,437381.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8.almMotorFailure.AEShelveTMRDN,437381.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8.almMotorFailure.Bad,437381.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8.almMotorFailure.Suppress,437382.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.UnSuppress,437382.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Shelve,437382.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.UnShelve,437382.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Enable,437382.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Disable,437382.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Ack,437382.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Reset,437382.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8.almMotorFailure.Suppressed,437382.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8.almMotorFailure.Shelved,437382.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8.almMotorFailure.Disabled,437382.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8.almMotorFailure.Acked,437382.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8.almMotorFailure.Alarm,437382.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Fault,437392.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8.almPLCFault.AlarmState,437392.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8.almPLCFault.GlobalReset,437392.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8.almPLCFault.FaultInAlarm,437392.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8.almPLCFault.ALRM,437392.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8.almPLCFault.ANUN,437392.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8.almPLCFault.AKED,437392.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8.almPLCFault.Resetable,437392.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8.almPLCFault.REST,437392.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8.almPLCFault.ACKN,437392.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8.almPLCFault.UACK,437392.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8.almPLCFault.MCmd_Enable,437392.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8.almPLCFault.MCmd_Disable,437392.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8.almPLCFault.OCmd_Shelve,437392.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8.almPLCFault.OCmd_Unshelve,437392.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8.almPLCFault.SCmd_Suppress,437392.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8.almPLCFault.SCmd_UnSuppress,437393.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8.almPLCFault.AEShelveTMRDN,437393.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8.almPLCFault.Bad,437393.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8.almPLCFault.Suppress,437394.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.UnSuppress,437394.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Shelve,437394.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.UnShelve,437394.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Enable,437394.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Disable,437394.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Ack,437394.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Reset,437394.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8.almPLCFault.Suppressed,437394.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8.almPLCFault.Shelved,437394.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8.almPLCFault.Disabled,437394.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8.almPLCFault.Acked,437394.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8.almPLCFault.Alarm,437394.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Fault,437404.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_8.almSpeedDeviation.AlarmState,437404.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_8.almSpeedDeviation.GlobalReset,437404.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_8.almSpeedDeviation.FaultInAlarm,437404.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_8.almSpeedDeviation.ALRM,437404.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_8.almSpeedDeviation.ANUN,437404.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_8.almSpeedDeviation.AKED,437404.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_8.almSpeedDeviation.Resetable,437404.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_8.almSpeedDeviation.REST,437404.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_8.almSpeedDeviation.ACKN,437404.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_8.almSpeedDeviation.UACK,437404.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_8.almSpeedDeviation.MCmd_Enable,437404.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_8.almSpeedDeviation.MCmd_Disable,437404.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_8.almSpeedDeviation.OCmd_Shelve,437404.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_8.almSpeedDeviation.OCmd_Unshelve,437404.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_8.almSpeedDeviation.SCmd_Suppress,437404.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_8.almSpeedDeviation.SCmd_UnSuppress,437405.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_8.almSpeedDeviation.AEShelveTMRDN,437405.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_8.almSpeedDeviation.Bad,437405.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_8.almSpeedDeviation.Suppress,437406.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.UnSuppress,437406.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Shelve,437406.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.UnShelve,437406.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Enable,437406.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Disable,437406.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Ack,437406.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Reset,437406.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Suppressed,437406.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Shelved,437406.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Disabled,437406.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Acked,437406.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_8.almSpeedDeviation.Alarm,437406.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Fault,437490.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9.almFailToStrt.AlarmState,437490.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9.almFailToStrt.GlobalReset,437490.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9.almFailToStrt.FaultInAlarm,437490.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9.almFailToStrt.ALRM,437490.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9.almFailToStrt.ANUN,437490.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9.almFailToStrt.AKED,437490.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9.almFailToStrt.Resetable,437490.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9.almFailToStrt.REST,437490.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9.almFailToStrt.ACKN,437490.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9.almFailToStrt.UACK,437490.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9.almFailToStrt.MCmd_Enable,437490.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9.almFailToStrt.MCmd_Disable,437490.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9.almFailToStrt.OCmd_Shelve,437490.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9.almFailToStrt.OCmd_Unshelve,437490.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9.almFailToStrt.SCmd_Suppress,437490.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9.almFailToStrt.SCmd_UnSuppress,437491.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9.almFailToStrt.AEShelveTMRDN,437491.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9.almFailToStrt.Bad,437491.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9.almFailToStrt.Suppress,437492.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.UnSuppress,437492.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Shelve,437492.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.UnShelve,437492.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Enable,437492.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Disable,437492.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Ack,437492.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Reset,437492.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9.almFailToStrt.Suppressed,437492.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9.almFailToStrt.Shelved,437492.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9.almFailToStrt.Disabled,437492.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9.almFailToStrt.Acked,437492.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9.almFailToStrt.Alarm,437492.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Fault,437502.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9.almFailToStop.AlarmState,437502.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9.almFailToStop.GlobalReset,437502.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9.almFailToStop.FaultInAlarm,437502.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9.almFailToStop.ALRM,437502.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9.almFailToStop.ANUN,437502.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9.almFailToStop.AKED,437502.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9.almFailToStop.Resetable,437502.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9.almFailToStop.REST,437502.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9.almFailToStop.ACKN,437502.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9.almFailToStop.UACK,437502.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9.almFailToStop.MCmd_Enable,437502.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9.almFailToStop.MCmd_Disable,437502.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9.almFailToStop.OCmd_Shelve,437502.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9.almFailToStop.OCmd_Unshelve,437502.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9.almFailToStop.SCmd_Suppress,437502.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9.almFailToStop.SCmd_UnSuppress,437503.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9.almFailToStop.AEShelveTMRDN,437503.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9.almFailToStop.Bad,437503.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9.almFailToStop.Suppress,437504.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.UnSuppress,437504.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Shelve,437504.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.UnShelve,437504.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Enable,437504.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Disable,437504.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Ack,437504.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Reset,437504.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9.almFailToStop.Suppressed,437504.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9.almFailToStop.Shelved,437504.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9.almFailToStop.Disabled,437504.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9.almFailToStop.Acked,437504.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9.almFailToStop.Alarm,437504.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Fault,437514.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9.almMotorFailure.AlarmState,437514.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9.almMotorFailure.GlobalReset,437514.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9.almMotorFailure.FaultInAlarm,437514.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9.almMotorFailure.ALRM,437514.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9.almMotorFailure.ANUN,437514.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9.almMotorFailure.AKED,437514.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9.almMotorFailure.Resetable,437514.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9.almMotorFailure.REST,437514.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9.almMotorFailure.ACKN,437514.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9.almMotorFailure.UACK,437514.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9.almMotorFailure.MCmd_Enable,437514.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9.almMotorFailure.MCmd_Disable,437514.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9.almMotorFailure.OCmd_Shelve,437514.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9.almMotorFailure.OCmd_Unshelve,437514.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9.almMotorFailure.SCmd_Suppress,437514.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9.almMotorFailure.SCmd_UnSuppress,437515.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9.almMotorFailure.AEShelveTMRDN,437515.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9.almMotorFailure.Bad,437515.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9.almMotorFailure.Suppress,437516.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.UnSuppress,437516.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Shelve,437516.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.UnShelve,437516.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Enable,437516.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Disable,437516.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Ack,437516.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Reset,437516.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9.almMotorFailure.Suppressed,437516.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9.almMotorFailure.Shelved,437516.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9.almMotorFailure.Disabled,437516.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9.almMotorFailure.Acked,437516.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9.almMotorFailure.Alarm,437516.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Fault,437526.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9.almPLCFault.AlarmState,437526.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9.almPLCFault.GlobalReset,437526.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9.almPLCFault.FaultInAlarm,437526.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9.almPLCFault.ALRM,437526.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9.almPLCFault.ANUN,437526.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9.almPLCFault.AKED,437526.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9.almPLCFault.Resetable,437526.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9.almPLCFault.REST,437526.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9.almPLCFault.ACKN,437526.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9.almPLCFault.UACK,437526.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9.almPLCFault.MCmd_Enable,437526.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9.almPLCFault.MCmd_Disable,437526.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9.almPLCFault.OCmd_Shelve,437526.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9.almPLCFault.OCmd_Unshelve,437526.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9.almPLCFault.SCmd_Suppress,437526.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9.almPLCFault.SCmd_UnSuppress,437527.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9.almPLCFault.AEShelveTMRDN,437527.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9.almPLCFault.Bad,437527.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9.almPLCFault.Suppress,437528.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.UnSuppress,437528.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Shelve,437528.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.UnShelve,437528.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Enable,437528.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Disable,437528.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Ack,437528.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Reset,437528.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9.almPLCFault.Suppressed,437528.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9.almPLCFault.Shelved,437528.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9.almPLCFault.Disabled,437528.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9.almPLCFault.Acked,437528.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9.almPLCFault.Alarm,437528.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Fault,437538.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_AFD_0103_9.almSpeedDeviation.AlarmState,437538.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_AFD_0103_9.almSpeedDeviation.GlobalReset,437538.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_AFD_0103_9.almSpeedDeviation.FaultInAlarm,437538.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_AFD_0103_9.almSpeedDeviation.ALRM,437538.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_AFD_0103_9.almSpeedDeviation.ANUN,437538.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_AFD_0103_9.almSpeedDeviation.AKED,437538.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_AFD_0103_9.almSpeedDeviation.Resetable,437538.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_AFD_0103_9.almSpeedDeviation.REST,437538.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_AFD_0103_9.almSpeedDeviation.ACKN,437538.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_AFD_0103_9.almSpeedDeviation.UACK,437538.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_AFD_0103_9.almSpeedDeviation.MCmd_Enable,437538.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_AFD_0103_9.almSpeedDeviation.MCmd_Disable,437538.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_AFD_0103_9.almSpeedDeviation.OCmd_Shelve,437538.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_AFD_0103_9.almSpeedDeviation.OCmd_Unshelve,437538.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_AFD_0103_9.almSpeedDeviation.SCmd_Suppress,437538.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_AFD_0103_9.almSpeedDeviation.SCmd_UnSuppress,437539.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_AFD_0103_9.almSpeedDeviation.AEShelveTMRDN,437539.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_AFD_0103_9.almSpeedDeviation.Bad,437539.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_AFD_0103_9.almSpeedDeviation.Suppress,437540.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.UnSuppress,437540.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Shelve,437540.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.UnShelve,437540.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Enable,437540.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Disable,437540.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Ack,437540.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Reset,437540.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Suppressed,437540.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Shelved,437540.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Disabled,437540.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Acked,437540.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_AFD_0103_9.almSpeedDeviation.Alarm,437540.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Fault,437602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A.almFailToOpen.AlarmState,437602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A.almFailToOpen.GlobalReset,437602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A.almFailToOpen.FaultInAlarm,437602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A.almFailToOpen.ALRM,437602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A.almFailToOpen.ANUN,437602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A.almFailToOpen.AKED,437602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A.almFailToOpen.Resetable,437602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A.almFailToOpen.REST,437602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A.almFailToOpen.ACKN,437602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A.almFailToOpen.UACK,437602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A.almFailToOpen.MCmd_Enable,437602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A.almFailToOpen.MCmd_Disable,437602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A.almFailToOpen.OCmd_Shelve,437602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A.almFailToOpen.OCmd_Unshelve,437602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A.almFailToOpen.SCmd_Suppress,437602.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A.almFailToOpen.SCmd_UnSuppress,437603.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A.almFailToOpen.AEShelveTMRDN,437603.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A.almFailToOpen.Bad,437603.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A.almFailToOpen.Suppress,437604.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.UnSuppress,437604.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Shelve,437604.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.UnShelve,437604.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Enable,437604.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Disable,437604.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Ack,437604.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Reset,437604.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A.almFailToOpen.Suppressed,437604.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A.almFailToOpen.Shelved,437604.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A.almFailToOpen.Disabled,437604.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A.almFailToOpen.Acked,437604.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A.almFailToOpen.Alarm,437604.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Fault,437614.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A.almFailToClose.AlarmState,437614.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A.almFailToClose.GlobalReset,437614.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A.almFailToClose.FaultInAlarm,437614.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A.almFailToClose.ALRM,437614.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A.almFailToClose.ANUN,437614.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A.almFailToClose.AKED,437614.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A.almFailToClose.Resetable,437614.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A.almFailToClose.REST,437614.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A.almFailToClose.ACKN,437614.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A.almFailToClose.UACK,437614.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A.almFailToClose.MCmd_Enable,437614.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A.almFailToClose.MCmd_Disable,437614.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A.almFailToClose.OCmd_Shelve,437614.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A.almFailToClose.OCmd_Unshelve,437614.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A.almFailToClose.SCmd_Suppress,437614.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A.almFailToClose.SCmd_UnSuppress,437615.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A.almFailToClose.AEShelveTMRDN,437615.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A.almFailToClose.Bad,437615.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A.almFailToClose.Suppress,437616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.UnSuppress,437616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Shelve,437616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.UnShelve,437616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Enable,437616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Disable,437616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Ack,437616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Reset,437616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A.almFailToClose.Suppressed,437616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A.almFailToClose.Shelved,437616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A.almFailToClose.Disabled,437616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A.almFailToClose.Acked,437616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A.almFailToClose.Alarm,437616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Fault,437626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A.almActuatorFault.AlarmState,437626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A.almActuatorFault.GlobalReset,437626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A.almActuatorFault.FaultInAlarm,437626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A.almActuatorFault.ALRM,437626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A.almActuatorFault.ANUN,437626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A.almActuatorFault.AKED,437626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A.almActuatorFault.Resetable,437626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A.almActuatorFault.REST,437626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A.almActuatorFault.ACKN,437626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A.almActuatorFault.UACK,437626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A.almActuatorFault.MCmd_Enable,437626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A.almActuatorFault.MCmd_Disable,437626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A.almActuatorFault.OCmd_Shelve,437626.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A.almActuatorFault.OCmd_Unshelve,437626.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A.almActuatorFault.SCmd_Suppress,437626.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A.almActuatorFault.SCmd_UnSuppress,437627.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A.almActuatorFault.AEShelveTMRDN,437627.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A.almActuatorFault.Bad,437627.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A.almActuatorFault.Suppress,437628.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.UnSuppress,437628.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Shelve,437628.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.UnShelve,437628.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Enable,437628.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Disable,437628.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Ack,437628.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Reset,437628.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A.almActuatorFault.Suppressed,437628.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A.almActuatorFault.Shelved,437628.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A.almActuatorFault.Disabled,437628.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A.almActuatorFault.Acked,437628.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A.almActuatorFault.Alarm,437628.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Fault,437638.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1A.almPLCFault.AlarmState,437638.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1A.almPLCFault.GlobalReset,437638.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1A.almPLCFault.FaultInAlarm,437638.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1A.almPLCFault.ALRM,437638.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1A.almPLCFault.ANUN,437638.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1A.almPLCFault.AKED,437638.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1A.almPLCFault.Resetable,437638.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1A.almPLCFault.REST,437638.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1A.almPLCFault.ACKN,437638.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1A.almPLCFault.UACK,437638.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1A.almPLCFault.MCmd_Enable,437638.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1A.almPLCFault.MCmd_Disable,437638.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1A.almPLCFault.OCmd_Shelve,437638.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1A.almPLCFault.OCmd_Unshelve,437638.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1A.almPLCFault.SCmd_Suppress,437638.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1A.almPLCFault.SCmd_UnSuppress,437639.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1A.almPLCFault.AEShelveTMRDN,437639.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1A.almPLCFault.Bad,437639.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1A.almPLCFault.Suppress,437640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.UnSuppress,437640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Shelve,437640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.UnShelve,437640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Enable,437640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Disable,437640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Ack,437640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Reset,437640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1A.almPLCFault.Suppressed,437640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1A.almPLCFault.Shelved,437640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1A.almPLCFault.Disabled,437640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1A.almPLCFault.Acked,437640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1A.almPLCFault.Alarm,437640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Fault,437682.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B.almFailToOpen.AlarmState,437682.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B.almFailToOpen.GlobalReset,437682.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B.almFailToOpen.FaultInAlarm,437682.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B.almFailToOpen.ALRM,437682.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B.almFailToOpen.ANUN,437682.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B.almFailToOpen.AKED,437682.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B.almFailToOpen.Resetable,437682.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B.almFailToOpen.REST,437682.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B.almFailToOpen.ACKN,437682.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B.almFailToOpen.UACK,437682.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B.almFailToOpen.MCmd_Enable,437682.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B.almFailToOpen.MCmd_Disable,437682.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B.almFailToOpen.OCmd_Shelve,437682.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B.almFailToOpen.OCmd_Unshelve,437682.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B.almFailToOpen.SCmd_Suppress,437682.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B.almFailToOpen.SCmd_UnSuppress,437683.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B.almFailToOpen.AEShelveTMRDN,437683.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B.almFailToOpen.Bad,437683.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B.almFailToOpen.Suppress,437684.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.UnSuppress,437684.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Shelve,437684.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.UnShelve,437684.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Enable,437684.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Disable,437684.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Ack,437684.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Reset,437684.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B.almFailToOpen.Suppressed,437684.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B.almFailToOpen.Shelved,437684.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B.almFailToOpen.Disabled,437684.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B.almFailToOpen.Acked,437684.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B.almFailToOpen.Alarm,437684.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Fault,437694.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B.almFailToClose.AlarmState,437694.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B.almFailToClose.GlobalReset,437694.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B.almFailToClose.FaultInAlarm,437694.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B.almFailToClose.ALRM,437694.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B.almFailToClose.ANUN,437694.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B.almFailToClose.AKED,437694.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B.almFailToClose.Resetable,437694.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B.almFailToClose.REST,437694.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B.almFailToClose.ACKN,437694.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B.almFailToClose.UACK,437694.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B.almFailToClose.MCmd_Enable,437694.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B.almFailToClose.MCmd_Disable,437694.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B.almFailToClose.OCmd_Shelve,437694.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B.almFailToClose.OCmd_Unshelve,437694.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B.almFailToClose.SCmd_Suppress,437694.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B.almFailToClose.SCmd_UnSuppress,437695.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B.almFailToClose.AEShelveTMRDN,437695.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B.almFailToClose.Bad,437695.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B.almFailToClose.Suppress,437696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.UnSuppress,437696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Shelve,437696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.UnShelve,437696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Enable,437696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Disable,437696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Ack,437696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Reset,437696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B.almFailToClose.Suppressed,437696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B.almFailToClose.Shelved,437696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B.almFailToClose.Disabled,437696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B.almFailToClose.Acked,437696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B.almFailToClose.Alarm,437696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Fault,437706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B.almActuatorFault.AlarmState,437706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B.almActuatorFault.GlobalReset,437706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B.almActuatorFault.FaultInAlarm,437706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B.almActuatorFault.ALRM,437706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B.almActuatorFault.ANUN,437706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B.almActuatorFault.AKED,437706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B.almActuatorFault.Resetable,437706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B.almActuatorFault.REST,437706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B.almActuatorFault.ACKN,437706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B.almActuatorFault.UACK,437706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B.almActuatorFault.MCmd_Enable,437706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B.almActuatorFault.MCmd_Disable,437706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B.almActuatorFault.OCmd_Shelve,437706.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B.almActuatorFault.OCmd_Unshelve,437706.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B.almActuatorFault.SCmd_Suppress,437706.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B.almActuatorFault.SCmd_UnSuppress,437707.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B.almActuatorFault.AEShelveTMRDN,437707.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B.almActuatorFault.Bad,437707.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B.almActuatorFault.Suppress,437708.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.UnSuppress,437708.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Shelve,437708.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.UnShelve,437708.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Enable,437708.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Disable,437708.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Ack,437708.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Reset,437708.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B.almActuatorFault.Suppressed,437708.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B.almActuatorFault.Shelved,437708.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B.almActuatorFault.Disabled,437708.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B.almActuatorFault.Acked,437708.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B.almActuatorFault.Alarm,437708.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Fault,437718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_1B.almPLCFault.AlarmState,437718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_1B.almPLCFault.GlobalReset,437718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_1B.almPLCFault.FaultInAlarm,437718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_1B.almPLCFault.ALRM,437718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_1B.almPLCFault.ANUN,437718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_1B.almPLCFault.AKED,437718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_1B.almPLCFault.Resetable,437718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_1B.almPLCFault.REST,437718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_1B.almPLCFault.ACKN,437718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_1B.almPLCFault.UACK,437718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_1B.almPLCFault.MCmd_Enable,437718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_1B.almPLCFault.MCmd_Disable,437718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_1B.almPLCFault.OCmd_Shelve,437718.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_1B.almPLCFault.OCmd_Unshelve,437718.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_1B.almPLCFault.SCmd_Suppress,437718.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_1B.almPLCFault.SCmd_UnSuppress,437719.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_1B.almPLCFault.AEShelveTMRDN,437719.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_1B.almPLCFault.Bad,437719.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_1B.almPLCFault.Suppress,437720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.UnSuppress,437720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Shelve,437720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.UnShelve,437720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Enable,437720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Disable,437720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Ack,437720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Reset,437720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_1B.almPLCFault.Suppressed,437720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_1B.almPLCFault.Shelved,437720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_1B.almPLCFault.Disabled,437720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_1B.almPLCFault.Acked,437720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_1B.almPLCFault.Alarm,437720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Fault,437762.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A.almFailToOpen.AlarmState,437762.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A.almFailToOpen.GlobalReset,437762.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A.almFailToOpen.FaultInAlarm,437762.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A.almFailToOpen.ALRM,437762.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A.almFailToOpen.ANUN,437762.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A.almFailToOpen.AKED,437762.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A.almFailToOpen.Resetable,437762.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A.almFailToOpen.REST,437762.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A.almFailToOpen.ACKN,437762.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A.almFailToOpen.UACK,437762.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A.almFailToOpen.MCmd_Enable,437762.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A.almFailToOpen.MCmd_Disable,437762.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A.almFailToOpen.OCmd_Shelve,437762.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A.almFailToOpen.OCmd_Unshelve,437762.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A.almFailToOpen.SCmd_Suppress,437762.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A.almFailToOpen.SCmd_UnSuppress,437763.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A.almFailToOpen.AEShelveTMRDN,437763.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A.almFailToOpen.Bad,437763.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A.almFailToOpen.Suppress,437764.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.UnSuppress,437764.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Shelve,437764.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.UnShelve,437764.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Enable,437764.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Disable,437764.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Ack,437764.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Reset,437764.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A.almFailToOpen.Suppressed,437764.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A.almFailToOpen.Shelved,437764.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A.almFailToOpen.Disabled,437764.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A.almFailToOpen.Acked,437764.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A.almFailToOpen.Alarm,437764.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Fault,437774.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A.almFailToClose.AlarmState,437774.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A.almFailToClose.GlobalReset,437774.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A.almFailToClose.FaultInAlarm,437774.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A.almFailToClose.ALRM,437774.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A.almFailToClose.ANUN,437774.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A.almFailToClose.AKED,437774.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A.almFailToClose.Resetable,437774.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A.almFailToClose.REST,437774.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A.almFailToClose.ACKN,437774.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A.almFailToClose.UACK,437774.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A.almFailToClose.MCmd_Enable,437774.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A.almFailToClose.MCmd_Disable,437774.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A.almFailToClose.OCmd_Shelve,437774.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A.almFailToClose.OCmd_Unshelve,437774.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A.almFailToClose.SCmd_Suppress,437774.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A.almFailToClose.SCmd_UnSuppress,437775.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A.almFailToClose.AEShelveTMRDN,437775.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A.almFailToClose.Bad,437775.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A.almFailToClose.Suppress,437776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.UnSuppress,437776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Shelve,437776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.UnShelve,437776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Enable,437776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Disable,437776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Ack,437776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Reset,437776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A.almFailToClose.Suppressed,437776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A.almFailToClose.Shelved,437776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A.almFailToClose.Disabled,437776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A.almFailToClose.Acked,437776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A.almFailToClose.Alarm,437776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Fault,437786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A.almActuatorFault.AlarmState,437786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A.almActuatorFault.GlobalReset,437786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A.almActuatorFault.FaultInAlarm,437786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A.almActuatorFault.ALRM,437786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A.almActuatorFault.ANUN,437786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A.almActuatorFault.AKED,437786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A.almActuatorFault.Resetable,437786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A.almActuatorFault.REST,437786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A.almActuatorFault.ACKN,437786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A.almActuatorFault.UACK,437786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A.almActuatorFault.MCmd_Enable,437786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A.almActuatorFault.MCmd_Disable,437786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A.almActuatorFault.OCmd_Shelve,437786.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A.almActuatorFault.OCmd_Unshelve,437786.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A.almActuatorFault.SCmd_Suppress,437786.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A.almActuatorFault.SCmd_UnSuppress,437787.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A.almActuatorFault.AEShelveTMRDN,437787.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A.almActuatorFault.Bad,437787.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A.almActuatorFault.Suppress,437788.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.UnSuppress,437788.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Shelve,437788.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.UnShelve,437788.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Enable,437788.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Disable,437788.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Ack,437788.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Reset,437788.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A.almActuatorFault.Suppressed,437788.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A.almActuatorFault.Shelved,437788.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A.almActuatorFault.Disabled,437788.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A.almActuatorFault.Acked,437788.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A.almActuatorFault.Alarm,437788.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Fault,437798.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2A.almPLCFault.AlarmState,437798.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2A.almPLCFault.GlobalReset,437798.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2A.almPLCFault.FaultInAlarm,437798.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2A.almPLCFault.ALRM,437798.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2A.almPLCFault.ANUN,437798.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2A.almPLCFault.AKED,437798.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2A.almPLCFault.Resetable,437798.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2A.almPLCFault.REST,437798.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2A.almPLCFault.ACKN,437798.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2A.almPLCFault.UACK,437798.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2A.almPLCFault.MCmd_Enable,437798.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2A.almPLCFault.MCmd_Disable,437798.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2A.almPLCFault.OCmd_Shelve,437798.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2A.almPLCFault.OCmd_Unshelve,437798.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2A.almPLCFault.SCmd_Suppress,437798.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2A.almPLCFault.SCmd_UnSuppress,437799.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2A.almPLCFault.AEShelveTMRDN,437799.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2A.almPLCFault.Bad,437799.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2A.almPLCFault.Suppress,437800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.UnSuppress,437800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Shelve,437800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.UnShelve,437800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Enable,437800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Disable,437800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Ack,437800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Reset,437800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2A.almPLCFault.Suppressed,437800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2A.almPLCFault.Shelved,437800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2A.almPLCFault.Disabled,437800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2A.almPLCFault.Acked,437800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2A.almPLCFault.Alarm,437800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Fault,437842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B.almFailToOpen.AlarmState,437842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B.almFailToOpen.GlobalReset,437842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B.almFailToOpen.FaultInAlarm,437842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B.almFailToOpen.ALRM,437842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B.almFailToOpen.ANUN,437842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B.almFailToOpen.AKED,437842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B.almFailToOpen.Resetable,437842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B.almFailToOpen.REST,437842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B.almFailToOpen.ACKN,437842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B.almFailToOpen.UACK,437842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B.almFailToOpen.MCmd_Enable,437842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B.almFailToOpen.MCmd_Disable,437842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B.almFailToOpen.OCmd_Shelve,437842.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B.almFailToOpen.OCmd_Unshelve,437842.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B.almFailToOpen.SCmd_Suppress,437842.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B.almFailToOpen.SCmd_UnSuppress,437843.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B.almFailToOpen.AEShelveTMRDN,437843.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B.almFailToOpen.Bad,437843.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B.almFailToOpen.Suppress,437844.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.UnSuppress,437844.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Shelve,437844.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.UnShelve,437844.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Enable,437844.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Disable,437844.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Ack,437844.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Reset,437844.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B.almFailToOpen.Suppressed,437844.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B.almFailToOpen.Shelved,437844.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B.almFailToOpen.Disabled,437844.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B.almFailToOpen.Acked,437844.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B.almFailToOpen.Alarm,437844.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Fault,437854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B.almFailToClose.AlarmState,437854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B.almFailToClose.GlobalReset,437854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B.almFailToClose.FaultInAlarm,437854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B.almFailToClose.ALRM,437854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B.almFailToClose.ANUN,437854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B.almFailToClose.AKED,437854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B.almFailToClose.Resetable,437854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B.almFailToClose.REST,437854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B.almFailToClose.ACKN,437854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B.almFailToClose.UACK,437854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B.almFailToClose.MCmd_Enable,437854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B.almFailToClose.MCmd_Disable,437854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B.almFailToClose.OCmd_Shelve,437854.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B.almFailToClose.OCmd_Unshelve,437854.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B.almFailToClose.SCmd_Suppress,437854.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B.almFailToClose.SCmd_UnSuppress,437855.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B.almFailToClose.AEShelveTMRDN,437855.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B.almFailToClose.Bad,437855.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B.almFailToClose.Suppress,437856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.UnSuppress,437856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Shelve,437856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.UnShelve,437856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Enable,437856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Disable,437856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Ack,437856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Reset,437856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B.almFailToClose.Suppressed,437856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B.almFailToClose.Shelved,437856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B.almFailToClose.Disabled,437856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B.almFailToClose.Acked,437856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B.almFailToClose.Alarm,437856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Fault,437866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B.almActuatorFault.AlarmState,437866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B.almActuatorFault.GlobalReset,437866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B.almActuatorFault.FaultInAlarm,437866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B.almActuatorFault.ALRM,437866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B.almActuatorFault.ANUN,437866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B.almActuatorFault.AKED,437866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B.almActuatorFault.Resetable,437866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B.almActuatorFault.REST,437866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B.almActuatorFault.ACKN,437866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B.almActuatorFault.UACK,437866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B.almActuatorFault.MCmd_Enable,437866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B.almActuatorFault.MCmd_Disable,437866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B.almActuatorFault.OCmd_Shelve,437866.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B.almActuatorFault.OCmd_Unshelve,437866.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B.almActuatorFault.SCmd_Suppress,437866.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B.almActuatorFault.SCmd_UnSuppress,437867.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B.almActuatorFault.AEShelveTMRDN,437867.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B.almActuatorFault.Bad,437867.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B.almActuatorFault.Suppress,437868.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.UnSuppress,437868.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Shelve,437868.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.UnShelve,437868.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Enable,437868.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Disable,437868.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Ack,437868.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Reset,437868.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B.almActuatorFault.Suppressed,437868.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B.almActuatorFault.Shelved,437868.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B.almActuatorFault.Disabled,437868.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B.almActuatorFault.Acked,437868.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B.almActuatorFault.Alarm,437868.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Fault,437878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0102_2B.almPLCFault.AlarmState,437878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0102_2B.almPLCFault.GlobalReset,437878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0102_2B.almPLCFault.FaultInAlarm,437878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0102_2B.almPLCFault.ALRM,437878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0102_2B.almPLCFault.ANUN,437878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0102_2B.almPLCFault.AKED,437878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0102_2B.almPLCFault.Resetable,437878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0102_2B.almPLCFault.REST,437878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0102_2B.almPLCFault.ACKN,437878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0102_2B.almPLCFault.UACK,437878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0102_2B.almPLCFault.MCmd_Enable,437878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0102_2B.almPLCFault.MCmd_Disable,437878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0102_2B.almPLCFault.OCmd_Shelve,437878.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0102_2B.almPLCFault.OCmd_Unshelve,437878.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0102_2B.almPLCFault.SCmd_Suppress,437878.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0102_2B.almPLCFault.SCmd_UnSuppress,437879.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0102_2B.almPLCFault.AEShelveTMRDN,437879.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0102_2B.almPLCFault.Bad,437879.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0102_2B.almPLCFault.Suppress,437880.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.UnSuppress,437880.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Shelve,437880.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.UnShelve,437880.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Enable,437880.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Disable,437880.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Ack,437880.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Reset,437880.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0102_2B.almPLCFault.Suppressed,437880.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0102_2B.almPLCFault.Shelved,437880.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0102_2B.almPLCFault.Disabled,437880.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0102_2B.almPLCFault.Acked,437880.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0102_2B.almPLCFault.Alarm,437880.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Fault,437922.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A.almFailToOpen.AlarmState,437922.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A.almFailToOpen.GlobalReset,437922.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A.almFailToOpen.FaultInAlarm,437922.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A.almFailToOpen.ALRM,437922.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A.almFailToOpen.ANUN,437922.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A.almFailToOpen.AKED,437922.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A.almFailToOpen.Resetable,437922.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A.almFailToOpen.REST,437922.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A.almFailToOpen.ACKN,437922.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A.almFailToOpen.UACK,437922.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A.almFailToOpen.MCmd_Enable,437922.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A.almFailToOpen.MCmd_Disable,437922.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A.almFailToOpen.OCmd_Shelve,437922.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A.almFailToOpen.OCmd_Unshelve,437922.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A.almFailToOpen.SCmd_Suppress,437922.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A.almFailToOpen.SCmd_UnSuppress,437923.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A.almFailToOpen.AEShelveTMRDN,437923.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A.almFailToOpen.Bad,437923.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A.almFailToOpen.Suppress,437924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.UnSuppress,437924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Shelve,437924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.UnShelve,437924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Enable,437924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Disable,437924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Ack,437924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Reset,437924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A.almFailToOpen.Suppressed,437924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A.almFailToOpen.Shelved,437924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A.almFailToOpen.Disabled,437924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A.almFailToOpen.Acked,437924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A.almFailToOpen.Alarm,437924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Fault,437934.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A.almFailToClose.AlarmState,437934.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A.almFailToClose.GlobalReset,437934.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A.almFailToClose.FaultInAlarm,437934.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A.almFailToClose.ALRM,437934.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A.almFailToClose.ANUN,437934.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A.almFailToClose.AKED,437934.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A.almFailToClose.Resetable,437934.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A.almFailToClose.REST,437934.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A.almFailToClose.ACKN,437934.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A.almFailToClose.UACK,437934.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A.almFailToClose.MCmd_Enable,437934.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A.almFailToClose.MCmd_Disable,437934.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A.almFailToClose.OCmd_Shelve,437934.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A.almFailToClose.OCmd_Unshelve,437934.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A.almFailToClose.SCmd_Suppress,437934.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A.almFailToClose.SCmd_UnSuppress,437935.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A.almFailToClose.AEShelveTMRDN,437935.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A.almFailToClose.Bad,437935.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A.almFailToClose.Suppress,437936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.UnSuppress,437936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Shelve,437936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.UnShelve,437936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Enable,437936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Disable,437936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Ack,437936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Reset,437936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A.almFailToClose.Suppressed,437936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A.almFailToClose.Shelved,437936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A.almFailToClose.Disabled,437936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A.almFailToClose.Acked,437936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A.almFailToClose.Alarm,437936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Fault,437946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A.almActuatorFault.AlarmState,437946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A.almActuatorFault.GlobalReset,437946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A.almActuatorFault.FaultInAlarm,437946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A.almActuatorFault.ALRM,437946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A.almActuatorFault.ANUN,437946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A.almActuatorFault.AKED,437946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A.almActuatorFault.Resetable,437946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A.almActuatorFault.REST,437946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A.almActuatorFault.ACKN,437946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A.almActuatorFault.UACK,437946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A.almActuatorFault.MCmd_Enable,437946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A.almActuatorFault.MCmd_Disable,437946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A.almActuatorFault.OCmd_Shelve,437946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A.almActuatorFault.OCmd_Unshelve,437946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A.almActuatorFault.SCmd_Suppress,437946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A.almActuatorFault.SCmd_UnSuppress,437947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A.almActuatorFault.AEShelveTMRDN,437947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A.almActuatorFault.Bad,437947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A.almActuatorFault.Suppress,437948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.UnSuppress,437948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Shelve,437948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.UnShelve,437948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Enable,437948.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Disable,437948.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Ack,437948.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Reset,437948.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A.almActuatorFault.Suppressed,437948.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A.almActuatorFault.Shelved,437948.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A.almActuatorFault.Disabled,437948.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A.almActuatorFault.Acked,437948.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A.almActuatorFault.Alarm,437948.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Fault,437958.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1A.almPLCFault.AlarmState,437958.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1A.almPLCFault.GlobalReset,437958.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1A.almPLCFault.FaultInAlarm,437958.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1A.almPLCFault.ALRM,437958.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1A.almPLCFault.ANUN,437958.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1A.almPLCFault.AKED,437958.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1A.almPLCFault.Resetable,437958.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1A.almPLCFault.REST,437958.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1A.almPLCFault.ACKN,437958.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1A.almPLCFault.UACK,437958.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1A.almPLCFault.MCmd_Enable,437958.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1A.almPLCFault.MCmd_Disable,437958.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1A.almPLCFault.OCmd_Shelve,437958.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1A.almPLCFault.OCmd_Unshelve,437958.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1A.almPLCFault.SCmd_Suppress,437958.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1A.almPLCFault.SCmd_UnSuppress,437959.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1A.almPLCFault.AEShelveTMRDN,437959.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1A.almPLCFault.Bad,437959.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1A.almPLCFault.Suppress,437960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.UnSuppress,437960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Shelve,437960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.UnShelve,437960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Enable,437960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Disable,437960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Ack,437960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Reset,437960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1A.almPLCFault.Suppressed,437960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1A.almPLCFault.Shelved,437960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1A.almPLCFault.Disabled,437960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1A.almPLCFault.Acked,437960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1A.almPLCFault.Alarm,437960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Fault,438002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C.almFailToOpen.AlarmState,438002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C.almFailToOpen.GlobalReset,438002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C.almFailToOpen.FaultInAlarm,438002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C.almFailToOpen.ALRM,438002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C.almFailToOpen.ANUN,438002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C.almFailToOpen.AKED,438002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C.almFailToOpen.Resetable,438002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C.almFailToOpen.REST,438002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C.almFailToOpen.ACKN,438002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C.almFailToOpen.UACK,438002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C.almFailToOpen.MCmd_Enable,438002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C.almFailToOpen.MCmd_Disable,438002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C.almFailToOpen.OCmd_Shelve,438002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C.almFailToOpen.OCmd_Unshelve,438002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C.almFailToOpen.SCmd_Suppress,438002.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C.almFailToOpen.SCmd_UnSuppress,438003.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C.almFailToOpen.AEShelveTMRDN,438003.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C.almFailToOpen.Bad,438003.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C.almFailToOpen.Suppress,438004.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.UnSuppress,438004.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Shelve,438004.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.UnShelve,438004.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Enable,438004.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Disable,438004.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Ack,438004.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Reset,438004.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C.almFailToOpen.Suppressed,438004.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C.almFailToOpen.Shelved,438004.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C.almFailToOpen.Disabled,438004.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C.almFailToOpen.Acked,438004.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C.almFailToOpen.Alarm,438004.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Fault,438014.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C.almFailToClose.AlarmState,438014.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C.almFailToClose.GlobalReset,438014.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C.almFailToClose.FaultInAlarm,438014.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C.almFailToClose.ALRM,438014.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C.almFailToClose.ANUN,438014.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C.almFailToClose.AKED,438014.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C.almFailToClose.Resetable,438014.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C.almFailToClose.REST,438014.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C.almFailToClose.ACKN,438014.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C.almFailToClose.UACK,438014.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C.almFailToClose.MCmd_Enable,438014.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C.almFailToClose.MCmd_Disable,438014.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C.almFailToClose.OCmd_Shelve,438014.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C.almFailToClose.OCmd_Unshelve,438014.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C.almFailToClose.SCmd_Suppress,438014.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C.almFailToClose.SCmd_UnSuppress,438015.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C.almFailToClose.AEShelveTMRDN,438015.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C.almFailToClose.Bad,438015.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C.almFailToClose.Suppress,438016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.UnSuppress,438016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Shelve,438016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.UnShelve,438016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Enable,438016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Disable,438016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Ack,438016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Reset,438016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C.almFailToClose.Suppressed,438016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C.almFailToClose.Shelved,438016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C.almFailToClose.Disabled,438016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C.almFailToClose.Acked,438016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C.almFailToClose.Alarm,438016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Fault,438026.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C.almActuatorFault.AlarmState,438026.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C.almActuatorFault.GlobalReset,438026.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C.almActuatorFault.FaultInAlarm,438026.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C.almActuatorFault.ALRM,438026.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C.almActuatorFault.ANUN,438026.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C.almActuatorFault.AKED,438026.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C.almActuatorFault.Resetable,438026.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C.almActuatorFault.REST,438026.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C.almActuatorFault.ACKN,438026.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C.almActuatorFault.UACK,438026.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C.almActuatorFault.MCmd_Enable,438026.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C.almActuatorFault.MCmd_Disable,438026.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C.almActuatorFault.OCmd_Shelve,438026.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C.almActuatorFault.OCmd_Unshelve,438026.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C.almActuatorFault.SCmd_Suppress,438026.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C.almActuatorFault.SCmd_UnSuppress,438027.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C.almActuatorFault.AEShelveTMRDN,438027.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C.almActuatorFault.Bad,438027.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C.almActuatorFault.Suppress,438028.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.UnSuppress,438028.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Shelve,438028.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.UnShelve,438028.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Enable,438028.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Disable,438028.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Ack,438028.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Reset,438028.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C.almActuatorFault.Suppressed,438028.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C.almActuatorFault.Shelved,438028.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C.almActuatorFault.Disabled,438028.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C.almActuatorFault.Acked,438028.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C.almActuatorFault.Alarm,438028.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Fault,438038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_1C.almPLCFault.AlarmState,438038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_1C.almPLCFault.GlobalReset,438038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_1C.almPLCFault.FaultInAlarm,438038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_1C.almPLCFault.ALRM,438038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_1C.almPLCFault.ANUN,438038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_1C.almPLCFault.AKED,438038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_1C.almPLCFault.Resetable,438038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_1C.almPLCFault.REST,438038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_1C.almPLCFault.ACKN,438038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_1C.almPLCFault.UACK,438038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_1C.almPLCFault.MCmd_Enable,438038.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_1C.almPLCFault.MCmd_Disable,438038.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_1C.almPLCFault.OCmd_Shelve,438038.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_1C.almPLCFault.OCmd_Unshelve,438038.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_1C.almPLCFault.SCmd_Suppress,438038.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_1C.almPLCFault.SCmd_UnSuppress,438039.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_1C.almPLCFault.AEShelveTMRDN,438039.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_1C.almPLCFault.Bad,438039.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_1C.almPLCFault.Suppress,438040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.UnSuppress,438040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Shelve,438040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.UnShelve,438040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Enable,438040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Disable,438040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Ack,438040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Reset,438040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_1C.almPLCFault.Suppressed,438040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_1C.almPLCFault.Shelved,438040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_1C.almPLCFault.Disabled,438040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_1C.almPLCFault.Acked,438040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_1C.almPLCFault.Alarm,438040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Fault,438082.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A.almFailToOpen.AlarmState,438082.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A.almFailToOpen.GlobalReset,438082.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A.almFailToOpen.FaultInAlarm,438082.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A.almFailToOpen.ALRM,438082.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A.almFailToOpen.ANUN,438082.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A.almFailToOpen.AKED,438082.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A.almFailToOpen.Resetable,438082.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A.almFailToOpen.REST,438082.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A.almFailToOpen.ACKN,438082.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A.almFailToOpen.UACK,438082.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A.almFailToOpen.MCmd_Enable,438082.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A.almFailToOpen.MCmd_Disable,438082.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A.almFailToOpen.OCmd_Shelve,438082.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A.almFailToOpen.OCmd_Unshelve,438082.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A.almFailToOpen.SCmd_Suppress,438082.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A.almFailToOpen.SCmd_UnSuppress,438083.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A.almFailToOpen.AEShelveTMRDN,438083.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A.almFailToOpen.Bad,438083.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A.almFailToOpen.Suppress,438084.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.UnSuppress,438084.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Shelve,438084.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.UnShelve,438084.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Enable,438084.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Disable,438084.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Ack,438084.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Reset,438084.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A.almFailToOpen.Suppressed,438084.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A.almFailToOpen.Shelved,438084.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A.almFailToOpen.Disabled,438084.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A.almFailToOpen.Acked,438084.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A.almFailToOpen.Alarm,438084.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Fault,438094.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A.almFailToClose.AlarmState,438094.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A.almFailToClose.GlobalReset,438094.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A.almFailToClose.FaultInAlarm,438094.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A.almFailToClose.ALRM,438094.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A.almFailToClose.ANUN,438094.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A.almFailToClose.AKED,438094.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A.almFailToClose.Resetable,438094.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A.almFailToClose.REST,438094.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A.almFailToClose.ACKN,438094.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A.almFailToClose.UACK,438094.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A.almFailToClose.MCmd_Enable,438094.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A.almFailToClose.MCmd_Disable,438094.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A.almFailToClose.OCmd_Shelve,438094.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A.almFailToClose.OCmd_Unshelve,438094.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A.almFailToClose.SCmd_Suppress,438094.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A.almFailToClose.SCmd_UnSuppress,438095.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A.almFailToClose.AEShelveTMRDN,438095.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A.almFailToClose.Bad,438095.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A.almFailToClose.Suppress,438096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.UnSuppress,438096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Shelve,438096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.UnShelve,438096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Enable,438096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Disable,438096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Ack,438096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Reset,438096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A.almFailToClose.Suppressed,438096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A.almFailToClose.Shelved,438096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A.almFailToClose.Disabled,438096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A.almFailToClose.Acked,438096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A.almFailToClose.Alarm,438096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Fault,438106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A.almActuatorFault.AlarmState,438106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A.almActuatorFault.GlobalReset,438106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A.almActuatorFault.FaultInAlarm,438106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A.almActuatorFault.ALRM,438106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A.almActuatorFault.ANUN,438106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A.almActuatorFault.AKED,438106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A.almActuatorFault.Resetable,438106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A.almActuatorFault.REST,438106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A.almActuatorFault.ACKN,438106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A.almActuatorFault.UACK,438106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A.almActuatorFault.MCmd_Enable,438106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A.almActuatorFault.MCmd_Disable,438106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A.almActuatorFault.OCmd_Shelve,438106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A.almActuatorFault.OCmd_Unshelve,438106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A.almActuatorFault.SCmd_Suppress,438106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A.almActuatorFault.SCmd_UnSuppress,438107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A.almActuatorFault.AEShelveTMRDN,438107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A.almActuatorFault.Bad,438107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A.almActuatorFault.Suppress,438108.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.UnSuppress,438108.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Shelve,438108.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.UnShelve,438108.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Enable,438108.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Disable,438108.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Ack,438108.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Reset,438108.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A.almActuatorFault.Suppressed,438108.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A.almActuatorFault.Shelved,438108.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A.almActuatorFault.Disabled,438108.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A.almActuatorFault.Acked,438108.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A.almActuatorFault.Alarm,438108.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Fault,438118.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2A.almPLCFault.AlarmState,438118.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2A.almPLCFault.GlobalReset,438118.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2A.almPLCFault.FaultInAlarm,438118.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2A.almPLCFault.ALRM,438118.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2A.almPLCFault.ANUN,438118.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2A.almPLCFault.AKED,438118.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2A.almPLCFault.Resetable,438118.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2A.almPLCFault.REST,438118.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2A.almPLCFault.ACKN,438118.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2A.almPLCFault.UACK,438118.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2A.almPLCFault.MCmd_Enable,438118.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2A.almPLCFault.MCmd_Disable,438118.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2A.almPLCFault.OCmd_Shelve,438118.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2A.almPLCFault.OCmd_Unshelve,438118.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2A.almPLCFault.SCmd_Suppress,438118.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2A.almPLCFault.SCmd_UnSuppress,438119.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2A.almPLCFault.AEShelveTMRDN,438119.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2A.almPLCFault.Bad,438119.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2A.almPLCFault.Suppress,438120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.UnSuppress,438120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Shelve,438120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.UnShelve,438120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Enable,438120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Disable,438120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Ack,438120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Reset,438120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2A.almPLCFault.Suppressed,438120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2A.almPLCFault.Shelved,438120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2A.almPLCFault.Disabled,438120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2A.almPLCFault.Acked,438120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2A.almPLCFault.Alarm,438120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Fault,438162.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C.almFailToOpen.AlarmState,438162.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C.almFailToOpen.GlobalReset,438162.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C.almFailToOpen.FaultInAlarm,438162.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C.almFailToOpen.ALRM,438162.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C.almFailToOpen.ANUN,438162.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C.almFailToOpen.AKED,438162.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C.almFailToOpen.Resetable,438162.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C.almFailToOpen.REST,438162.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C.almFailToOpen.ACKN,438162.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C.almFailToOpen.UACK,438162.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C.almFailToOpen.MCmd_Enable,438162.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C.almFailToOpen.MCmd_Disable,438162.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C.almFailToOpen.OCmd_Shelve,438162.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C.almFailToOpen.OCmd_Unshelve,438162.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C.almFailToOpen.SCmd_Suppress,438162.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C.almFailToOpen.SCmd_UnSuppress,438163.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C.almFailToOpen.AEShelveTMRDN,438163.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C.almFailToOpen.Bad,438163.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C.almFailToOpen.Suppress,438164.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.UnSuppress,438164.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Shelve,438164.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.UnShelve,438164.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Enable,438164.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Disable,438164.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Ack,438164.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Reset,438164.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C.almFailToOpen.Suppressed,438164.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C.almFailToOpen.Shelved,438164.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C.almFailToOpen.Disabled,438164.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C.almFailToOpen.Acked,438164.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C.almFailToOpen.Alarm,438164.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Fault,438174.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C.almFailToClose.AlarmState,438174.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C.almFailToClose.GlobalReset,438174.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C.almFailToClose.FaultInAlarm,438174.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C.almFailToClose.ALRM,438174.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C.almFailToClose.ANUN,438174.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C.almFailToClose.AKED,438174.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C.almFailToClose.Resetable,438174.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C.almFailToClose.REST,438174.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C.almFailToClose.ACKN,438174.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C.almFailToClose.UACK,438174.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C.almFailToClose.MCmd_Enable,438174.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C.almFailToClose.MCmd_Disable,438174.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C.almFailToClose.OCmd_Shelve,438174.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C.almFailToClose.OCmd_Unshelve,438174.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C.almFailToClose.SCmd_Suppress,438174.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C.almFailToClose.SCmd_UnSuppress,438175.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C.almFailToClose.AEShelveTMRDN,438175.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C.almFailToClose.Bad,438175.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C.almFailToClose.Suppress,438176.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.UnSuppress,438176.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Shelve,438176.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.UnShelve,438176.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Enable,438176.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Disable,438176.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Ack,438176.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Reset,438176.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C.almFailToClose.Suppressed,438176.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C.almFailToClose.Shelved,438176.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C.almFailToClose.Disabled,438176.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C.almFailToClose.Acked,438176.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C.almFailToClose.Alarm,438176.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Fault,438186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C.almActuatorFault.AlarmState,438186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C.almActuatorFault.GlobalReset,438186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C.almActuatorFault.FaultInAlarm,438186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C.almActuatorFault.ALRM,438186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C.almActuatorFault.ANUN,438186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C.almActuatorFault.AKED,438186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C.almActuatorFault.Resetable,438186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C.almActuatorFault.REST,438186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C.almActuatorFault.ACKN,438186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C.almActuatorFault.UACK,438186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C.almActuatorFault.MCmd_Enable,438186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C.almActuatorFault.MCmd_Disable,438186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C.almActuatorFault.OCmd_Shelve,438186.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C.almActuatorFault.OCmd_Unshelve,438186.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C.almActuatorFault.SCmd_Suppress,438186.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C.almActuatorFault.SCmd_UnSuppress,438187.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C.almActuatorFault.AEShelveTMRDN,438187.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C.almActuatorFault.Bad,438187.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C.almActuatorFault.Suppress,438188.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.UnSuppress,438188.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Shelve,438188.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.UnShelve,438188.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Enable,438188.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Disable,438188.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Ack,438188.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Reset,438188.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C.almActuatorFault.Suppressed,438188.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C.almActuatorFault.Shelved,438188.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C.almActuatorFault.Disabled,438188.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C.almActuatorFault.Acked,438188.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C.almActuatorFault.Alarm,438188.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Fault,438198.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_2C.almPLCFault.AlarmState,438198.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_2C.almPLCFault.GlobalReset,438198.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_2C.almPLCFault.FaultInAlarm,438198.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_2C.almPLCFault.ALRM,438198.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_2C.almPLCFault.ANUN,438198.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_2C.almPLCFault.AKED,438198.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_2C.almPLCFault.Resetable,438198.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_2C.almPLCFault.REST,438198.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_2C.almPLCFault.ACKN,438198.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_2C.almPLCFault.UACK,438198.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_2C.almPLCFault.MCmd_Enable,438198.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_2C.almPLCFault.MCmd_Disable,438198.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_2C.almPLCFault.OCmd_Shelve,438198.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_2C.almPLCFault.OCmd_Unshelve,438198.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_2C.almPLCFault.SCmd_Suppress,438198.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_2C.almPLCFault.SCmd_UnSuppress,438199.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_2C.almPLCFault.AEShelveTMRDN,438199.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_2C.almPLCFault.Bad,438199.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_2C.almPLCFault.Suppress,438200.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.UnSuppress,438200.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Shelve,438200.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.UnShelve,438200.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Enable,438200.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Disable,438200.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Ack,438200.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Reset,438200.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_2C.almPLCFault.Suppressed,438200.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_2C.almPLCFault.Shelved,438200.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_2C.almPLCFault.Disabled,438200.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_2C.almPLCFault.Acked,438200.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_2C.almPLCFault.Alarm,438200.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Fault,438242.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A.almFailToOpen.AlarmState,438242.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A.almFailToOpen.GlobalReset,438242.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A.almFailToOpen.FaultInAlarm,438242.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A.almFailToOpen.ALRM,438242.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A.almFailToOpen.ANUN,438242.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A.almFailToOpen.AKED,438242.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A.almFailToOpen.Resetable,438242.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A.almFailToOpen.REST,438242.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A.almFailToOpen.ACKN,438242.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A.almFailToOpen.UACK,438242.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A.almFailToOpen.MCmd_Enable,438242.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A.almFailToOpen.MCmd_Disable,438242.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A.almFailToOpen.OCmd_Shelve,438242.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A.almFailToOpen.OCmd_Unshelve,438242.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A.almFailToOpen.SCmd_Suppress,438242.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A.almFailToOpen.SCmd_UnSuppress,438243.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A.almFailToOpen.AEShelveTMRDN,438243.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A.almFailToOpen.Bad,438243.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A.almFailToOpen.Suppress,438244.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.UnSuppress,438244.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Shelve,438244.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.UnShelve,438244.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Enable,438244.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Disable,438244.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Ack,438244.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Reset,438244.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A.almFailToOpen.Suppressed,438244.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A.almFailToOpen.Shelved,438244.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A.almFailToOpen.Disabled,438244.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A.almFailToOpen.Acked,438244.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A.almFailToOpen.Alarm,438244.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Fault,438254.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A.almFailToClose.AlarmState,438254.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A.almFailToClose.GlobalReset,438254.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A.almFailToClose.FaultInAlarm,438254.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A.almFailToClose.ALRM,438254.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A.almFailToClose.ANUN,438254.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A.almFailToClose.AKED,438254.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A.almFailToClose.Resetable,438254.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A.almFailToClose.REST,438254.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A.almFailToClose.ACKN,438254.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A.almFailToClose.UACK,438254.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A.almFailToClose.MCmd_Enable,438254.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A.almFailToClose.MCmd_Disable,438254.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A.almFailToClose.OCmd_Shelve,438254.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A.almFailToClose.OCmd_Unshelve,438254.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A.almFailToClose.SCmd_Suppress,438254.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A.almFailToClose.SCmd_UnSuppress,438255.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A.almFailToClose.AEShelveTMRDN,438255.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A.almFailToClose.Bad,438255.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A.almFailToClose.Suppress,438256.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.UnSuppress,438256.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Shelve,438256.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.UnShelve,438256.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Enable,438256.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Disable,438256.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Ack,438256.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Reset,438256.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A.almFailToClose.Suppressed,438256.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A.almFailToClose.Shelved,438256.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A.almFailToClose.Disabled,438256.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A.almFailToClose.Acked,438256.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A.almFailToClose.Alarm,438256.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Fault,438266.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A.almActuatorFault.AlarmState,438266.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A.almActuatorFault.GlobalReset,438266.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A.almActuatorFault.FaultInAlarm,438266.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A.almActuatorFault.ALRM,438266.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A.almActuatorFault.ANUN,438266.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A.almActuatorFault.AKED,438266.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A.almActuatorFault.Resetable,438266.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A.almActuatorFault.REST,438266.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A.almActuatorFault.ACKN,438266.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A.almActuatorFault.UACK,438266.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A.almActuatorFault.MCmd_Enable,438266.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A.almActuatorFault.MCmd_Disable,438266.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A.almActuatorFault.OCmd_Shelve,438266.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A.almActuatorFault.OCmd_Unshelve,438266.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A.almActuatorFault.SCmd_Suppress,438266.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A.almActuatorFault.SCmd_UnSuppress,438267.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A.almActuatorFault.AEShelveTMRDN,438267.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A.almActuatorFault.Bad,438267.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A.almActuatorFault.Suppress,438268.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.UnSuppress,438268.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Shelve,438268.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.UnShelve,438268.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Enable,438268.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Disable,438268.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Ack,438268.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Reset,438268.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A.almActuatorFault.Suppressed,438268.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A.almActuatorFault.Shelved,438268.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A.almActuatorFault.Disabled,438268.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A.almActuatorFault.Acked,438268.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A.almActuatorFault.Alarm,438268.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Fault,438278.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3A.almPLCFault.AlarmState,438278.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3A.almPLCFault.GlobalReset,438278.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3A.almPLCFault.FaultInAlarm,438278.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3A.almPLCFault.ALRM,438278.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3A.almPLCFault.ANUN,438278.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3A.almPLCFault.AKED,438278.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3A.almPLCFault.Resetable,438278.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3A.almPLCFault.REST,438278.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3A.almPLCFault.ACKN,438278.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3A.almPLCFault.UACK,438278.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3A.almPLCFault.MCmd_Enable,438278.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3A.almPLCFault.MCmd_Disable,438278.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3A.almPLCFault.OCmd_Shelve,438278.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3A.almPLCFault.OCmd_Unshelve,438278.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3A.almPLCFault.SCmd_Suppress,438278.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3A.almPLCFault.SCmd_UnSuppress,438279.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3A.almPLCFault.AEShelveTMRDN,438279.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3A.almPLCFault.Bad,438279.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3A.almPLCFault.Suppress,438280.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.UnSuppress,438280.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Shelve,438280.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.UnShelve,438280.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Enable,438280.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Disable,438280.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Ack,438280.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Reset,438280.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3A.almPLCFault.Suppressed,438280.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3A.almPLCFault.Shelved,438280.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3A.almPLCFault.Disabled,438280.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3A.almPLCFault.Acked,438280.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3A.almPLCFault.Alarm,438280.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Fault,438322.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C.almFailToOpen.AlarmState,438322.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C.almFailToOpen.GlobalReset,438322.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C.almFailToOpen.FaultInAlarm,438322.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C.almFailToOpen.ALRM,438322.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C.almFailToOpen.ANUN,438322.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C.almFailToOpen.AKED,438322.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C.almFailToOpen.Resetable,438322.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C.almFailToOpen.REST,438322.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C.almFailToOpen.ACKN,438322.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C.almFailToOpen.UACK,438322.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C.almFailToOpen.MCmd_Enable,438322.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C.almFailToOpen.MCmd_Disable,438322.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C.almFailToOpen.OCmd_Shelve,438322.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C.almFailToOpen.OCmd_Unshelve,438322.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C.almFailToOpen.SCmd_Suppress,438322.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C.almFailToOpen.SCmd_UnSuppress,438323.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C.almFailToOpen.AEShelveTMRDN,438323.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C.almFailToOpen.Bad,438323.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C.almFailToOpen.Suppress,438324.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.UnSuppress,438324.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Shelve,438324.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.UnShelve,438324.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Enable,438324.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Disable,438324.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Ack,438324.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Reset,438324.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C.almFailToOpen.Suppressed,438324.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C.almFailToOpen.Shelved,438324.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C.almFailToOpen.Disabled,438324.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C.almFailToOpen.Acked,438324.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C.almFailToOpen.Alarm,438324.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Fault,438334.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C.almFailToClose.AlarmState,438334.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C.almFailToClose.GlobalReset,438334.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C.almFailToClose.FaultInAlarm,438334.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C.almFailToClose.ALRM,438334.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C.almFailToClose.ANUN,438334.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C.almFailToClose.AKED,438334.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C.almFailToClose.Resetable,438334.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C.almFailToClose.REST,438334.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C.almFailToClose.ACKN,438334.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C.almFailToClose.UACK,438334.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C.almFailToClose.MCmd_Enable,438334.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C.almFailToClose.MCmd_Disable,438334.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C.almFailToClose.OCmd_Shelve,438334.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C.almFailToClose.OCmd_Unshelve,438334.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C.almFailToClose.SCmd_Suppress,438334.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C.almFailToClose.SCmd_UnSuppress,438335.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C.almFailToClose.AEShelveTMRDN,438335.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C.almFailToClose.Bad,438335.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C.almFailToClose.Suppress,438336.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.UnSuppress,438336.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Shelve,438336.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.UnShelve,438336.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Enable,438336.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Disable,438336.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Ack,438336.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Reset,438336.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C.almFailToClose.Suppressed,438336.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C.almFailToClose.Shelved,438336.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C.almFailToClose.Disabled,438336.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C.almFailToClose.Acked,438336.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C.almFailToClose.Alarm,438336.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Fault,438346.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C.almActuatorFault.AlarmState,438346.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C.almActuatorFault.GlobalReset,438346.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C.almActuatorFault.FaultInAlarm,438346.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C.almActuatorFault.ALRM,438346.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C.almActuatorFault.ANUN,438346.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C.almActuatorFault.AKED,438346.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C.almActuatorFault.Resetable,438346.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C.almActuatorFault.REST,438346.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C.almActuatorFault.ACKN,438346.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C.almActuatorFault.UACK,438346.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C.almActuatorFault.MCmd_Enable,438346.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C.almActuatorFault.MCmd_Disable,438346.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C.almActuatorFault.OCmd_Shelve,438346.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C.almActuatorFault.OCmd_Unshelve,438346.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C.almActuatorFault.SCmd_Suppress,438346.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C.almActuatorFault.SCmd_UnSuppress,438347.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C.almActuatorFault.AEShelveTMRDN,438347.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C.almActuatorFault.Bad,438347.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C.almActuatorFault.Suppress,438348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.UnSuppress,438348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Shelve,438348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.UnShelve,438348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Enable,438348.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Disable,438348.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Ack,438348.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Reset,438348.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C.almActuatorFault.Suppressed,438348.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C.almActuatorFault.Shelved,438348.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C.almActuatorFault.Disabled,438348.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C.almActuatorFault.Acked,438348.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C.almActuatorFault.Alarm,438348.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Fault,438358.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3C.almPLCFault.AlarmState,438358.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3C.almPLCFault.GlobalReset,438358.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3C.almPLCFault.FaultInAlarm,438358.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3C.almPLCFault.ALRM,438358.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3C.almPLCFault.ANUN,438358.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3C.almPLCFault.AKED,438358.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3C.almPLCFault.Resetable,438358.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3C.almPLCFault.REST,438358.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3C.almPLCFault.ACKN,438358.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3C.almPLCFault.UACK,438358.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3C.almPLCFault.MCmd_Enable,438358.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3C.almPLCFault.MCmd_Disable,438358.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3C.almPLCFault.OCmd_Shelve,438358.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3C.almPLCFault.OCmd_Unshelve,438358.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3C.almPLCFault.SCmd_Suppress,438358.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3C.almPLCFault.SCmd_UnSuppress,438359.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3C.almPLCFault.AEShelveTMRDN,438359.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3C.almPLCFault.Bad,438359.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3C.almPLCFault.Suppress,438360.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.UnSuppress,438360.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Shelve,438360.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.UnShelve,438360.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Enable,438360.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Disable,438360.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Ack,438360.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Reset,438360.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3C.almPLCFault.Suppressed,438360.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3C.almPLCFault.Shelved,438360.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3C.almPLCFault.Disabled,438360.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3C.almPLCFault.Acked,438360.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3C.almPLCFault.Alarm,438360.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Fault,438402.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D.almFailToOpen.AlarmState,438402.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D.almFailToOpen.GlobalReset,438402.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D.almFailToOpen.FaultInAlarm,438402.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D.almFailToOpen.ALRM,438402.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D.almFailToOpen.ANUN,438402.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D.almFailToOpen.AKED,438402.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D.almFailToOpen.Resetable,438402.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D.almFailToOpen.REST,438402.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D.almFailToOpen.ACKN,438402.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D.almFailToOpen.UACK,438402.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D.almFailToOpen.MCmd_Enable,438402.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D.almFailToOpen.MCmd_Disable,438402.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D.almFailToOpen.OCmd_Shelve,438402.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D.almFailToOpen.OCmd_Unshelve,438402.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D.almFailToOpen.SCmd_Suppress,438402.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D.almFailToOpen.SCmd_UnSuppress,438403.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D.almFailToOpen.AEShelveTMRDN,438403.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D.almFailToOpen.Bad,438403.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D.almFailToOpen.Suppress,438404.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.UnSuppress,438404.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Shelve,438404.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.UnShelve,438404.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Enable,438404.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Disable,438404.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Ack,438404.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Reset,438404.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D.almFailToOpen.Suppressed,438404.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D.almFailToOpen.Shelved,438404.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D.almFailToOpen.Disabled,438404.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D.almFailToOpen.Acked,438404.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D.almFailToOpen.Alarm,438404.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Fault,438414.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D.almFailToClose.AlarmState,438414.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D.almFailToClose.GlobalReset,438414.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D.almFailToClose.FaultInAlarm,438414.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D.almFailToClose.ALRM,438414.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D.almFailToClose.ANUN,438414.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D.almFailToClose.AKED,438414.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D.almFailToClose.Resetable,438414.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D.almFailToClose.REST,438414.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D.almFailToClose.ACKN,438414.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D.almFailToClose.UACK,438414.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D.almFailToClose.MCmd_Enable,438414.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D.almFailToClose.MCmd_Disable,438414.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D.almFailToClose.OCmd_Shelve,438414.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D.almFailToClose.OCmd_Unshelve,438414.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D.almFailToClose.SCmd_Suppress,438414.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D.almFailToClose.SCmd_UnSuppress,438415.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D.almFailToClose.AEShelveTMRDN,438415.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D.almFailToClose.Bad,438415.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D.almFailToClose.Suppress,438416.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.UnSuppress,438416.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Shelve,438416.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.UnShelve,438416.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Enable,438416.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Disable,438416.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Ack,438416.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Reset,438416.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D.almFailToClose.Suppressed,438416.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D.almFailToClose.Shelved,438416.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D.almFailToClose.Disabled,438416.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D.almFailToClose.Acked,438416.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D.almFailToClose.Alarm,438416.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Fault,438426.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D.almActuatorFault.AlarmState,438426.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D.almActuatorFault.GlobalReset,438426.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D.almActuatorFault.FaultInAlarm,438426.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D.almActuatorFault.ALRM,438426.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D.almActuatorFault.ANUN,438426.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D.almActuatorFault.AKED,438426.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D.almActuatorFault.Resetable,438426.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D.almActuatorFault.REST,438426.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D.almActuatorFault.ACKN,438426.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D.almActuatorFault.UACK,438426.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D.almActuatorFault.MCmd_Enable,438426.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D.almActuatorFault.MCmd_Disable,438426.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D.almActuatorFault.OCmd_Shelve,438426.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D.almActuatorFault.OCmd_Unshelve,438426.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D.almActuatorFault.SCmd_Suppress,438426.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D.almActuatorFault.SCmd_UnSuppress,438427.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D.almActuatorFault.AEShelveTMRDN,438427.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D.almActuatorFault.Bad,438427.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D.almActuatorFault.Suppress,438428.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.UnSuppress,438428.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Shelve,438428.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.UnShelve,438428.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Enable,438428.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Disable,438428.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Ack,438428.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Reset,438428.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D.almActuatorFault.Suppressed,438428.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D.almActuatorFault.Shelved,438428.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D.almActuatorFault.Disabled,438428.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D.almActuatorFault.Acked,438428.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D.almActuatorFault.Alarm,438428.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Fault,438438.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_3D.almPLCFault.AlarmState,438438.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_3D.almPLCFault.GlobalReset,438438.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_3D.almPLCFault.FaultInAlarm,438438.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_3D.almPLCFault.ALRM,438438.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_3D.almPLCFault.ANUN,438438.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_3D.almPLCFault.AKED,438438.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_3D.almPLCFault.Resetable,438438.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_3D.almPLCFault.REST,438438.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_3D.almPLCFault.ACKN,438438.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_3D.almPLCFault.UACK,438438.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_3D.almPLCFault.MCmd_Enable,438438.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_3D.almPLCFault.MCmd_Disable,438438.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_3D.almPLCFault.OCmd_Shelve,438438.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_3D.almPLCFault.OCmd_Unshelve,438438.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_3D.almPLCFault.SCmd_Suppress,438438.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_3D.almPLCFault.SCmd_UnSuppress,438439.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_3D.almPLCFault.AEShelveTMRDN,438439.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_3D.almPLCFault.Bad,438439.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_3D.almPLCFault.Suppress,438440.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.UnSuppress,438440.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Shelve,438440.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.UnShelve,438440.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Enable,438440.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Disable,438440.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Ack,438440.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Reset,438440.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_3D.almPLCFault.Suppressed,438440.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_3D.almPLCFault.Shelved,438440.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_3D.almPLCFault.Disabled,438440.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_3D.almPLCFault.Acked,438440.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_3D.almPLCFault.Alarm,438440.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Fault,438482.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A.almFailToOpen.AlarmState,438482.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A.almFailToOpen.GlobalReset,438482.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A.almFailToOpen.FaultInAlarm,438482.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A.almFailToOpen.ALRM,438482.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A.almFailToOpen.ANUN,438482.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A.almFailToOpen.AKED,438482.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A.almFailToOpen.Resetable,438482.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A.almFailToOpen.REST,438482.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A.almFailToOpen.ACKN,438482.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A.almFailToOpen.UACK,438482.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A.almFailToOpen.MCmd_Enable,438482.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A.almFailToOpen.MCmd_Disable,438482.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A.almFailToOpen.OCmd_Shelve,438482.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A.almFailToOpen.OCmd_Unshelve,438482.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A.almFailToOpen.SCmd_Suppress,438482.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A.almFailToOpen.SCmd_UnSuppress,438483.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A.almFailToOpen.AEShelveTMRDN,438483.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A.almFailToOpen.Bad,438483.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A.almFailToOpen.Suppress,438484.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.UnSuppress,438484.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Shelve,438484.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.UnShelve,438484.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Enable,438484.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Disable,438484.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Ack,438484.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Reset,438484.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A.almFailToOpen.Suppressed,438484.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A.almFailToOpen.Shelved,438484.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A.almFailToOpen.Disabled,438484.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A.almFailToOpen.Acked,438484.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A.almFailToOpen.Alarm,438484.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Fault,438494.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A.almFailToClose.AlarmState,438494.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A.almFailToClose.GlobalReset,438494.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A.almFailToClose.FaultInAlarm,438494.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A.almFailToClose.ALRM,438494.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A.almFailToClose.ANUN,438494.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A.almFailToClose.AKED,438494.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A.almFailToClose.Resetable,438494.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A.almFailToClose.REST,438494.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A.almFailToClose.ACKN,438494.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A.almFailToClose.UACK,438494.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A.almFailToClose.MCmd_Enable,438494.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A.almFailToClose.MCmd_Disable,438494.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A.almFailToClose.OCmd_Shelve,438494.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A.almFailToClose.OCmd_Unshelve,438494.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A.almFailToClose.SCmd_Suppress,438494.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A.almFailToClose.SCmd_UnSuppress,438495.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A.almFailToClose.AEShelveTMRDN,438495.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A.almFailToClose.Bad,438495.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A.almFailToClose.Suppress,438496.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.UnSuppress,438496.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Shelve,438496.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.UnShelve,438496.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Enable,438496.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Disable,438496.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Ack,438496.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Reset,438496.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A.almFailToClose.Suppressed,438496.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A.almFailToClose.Shelved,438496.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A.almFailToClose.Disabled,438496.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A.almFailToClose.Acked,438496.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A.almFailToClose.Alarm,438496.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Fault,438506.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A.almActuatorFault.AlarmState,438506.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A.almActuatorFault.GlobalReset,438506.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A.almActuatorFault.FaultInAlarm,438506.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A.almActuatorFault.ALRM,438506.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A.almActuatorFault.ANUN,438506.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A.almActuatorFault.AKED,438506.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A.almActuatorFault.Resetable,438506.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A.almActuatorFault.REST,438506.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A.almActuatorFault.ACKN,438506.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A.almActuatorFault.UACK,438506.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A.almActuatorFault.MCmd_Enable,438506.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A.almActuatorFault.MCmd_Disable,438506.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A.almActuatorFault.OCmd_Shelve,438506.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A.almActuatorFault.OCmd_Unshelve,438506.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A.almActuatorFault.SCmd_Suppress,438506.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A.almActuatorFault.SCmd_UnSuppress,438507.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A.almActuatorFault.AEShelveTMRDN,438507.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A.almActuatorFault.Bad,438507.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A.almActuatorFault.Suppress,438508.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.UnSuppress,438508.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Shelve,438508.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.UnShelve,438508.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Enable,438508.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Disable,438508.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Ack,438508.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Reset,438508.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A.almActuatorFault.Suppressed,438508.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A.almActuatorFault.Shelved,438508.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A.almActuatorFault.Disabled,438508.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A.almActuatorFault.Acked,438508.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A.almActuatorFault.Alarm,438508.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Fault,438518.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4A.almPLCFault.AlarmState,438518.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4A.almPLCFault.GlobalReset,438518.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4A.almPLCFault.FaultInAlarm,438518.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4A.almPLCFault.ALRM,438518.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4A.almPLCFault.ANUN,438518.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4A.almPLCFault.AKED,438518.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4A.almPLCFault.Resetable,438518.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4A.almPLCFault.REST,438518.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4A.almPLCFault.ACKN,438518.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4A.almPLCFault.UACK,438518.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4A.almPLCFault.MCmd_Enable,438518.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4A.almPLCFault.MCmd_Disable,438518.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4A.almPLCFault.OCmd_Shelve,438518.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4A.almPLCFault.OCmd_Unshelve,438518.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4A.almPLCFault.SCmd_Suppress,438518.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4A.almPLCFault.SCmd_UnSuppress,438519.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4A.almPLCFault.AEShelveTMRDN,438519.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4A.almPLCFault.Bad,438519.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4A.almPLCFault.Suppress,438520.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.UnSuppress,438520.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Shelve,438520.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.UnShelve,438520.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Enable,438520.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Disable,438520.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Ack,438520.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Reset,438520.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4A.almPLCFault.Suppressed,438520.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4A.almPLCFault.Shelved,438520.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4A.almPLCFault.Disabled,438520.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4A.almPLCFault.Acked,438520.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4A.almPLCFault.Alarm,438520.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Fault,438562.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C.almFailToOpen.AlarmState,438562.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C.almFailToOpen.GlobalReset,438562.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C.almFailToOpen.FaultInAlarm,438562.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C.almFailToOpen.ALRM,438562.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C.almFailToOpen.ANUN,438562.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C.almFailToOpen.AKED,438562.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C.almFailToOpen.Resetable,438562.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C.almFailToOpen.REST,438562.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C.almFailToOpen.ACKN,438562.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C.almFailToOpen.UACK,438562.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C.almFailToOpen.MCmd_Enable,438562.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C.almFailToOpen.MCmd_Disable,438562.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C.almFailToOpen.OCmd_Shelve,438562.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C.almFailToOpen.OCmd_Unshelve,438562.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C.almFailToOpen.SCmd_Suppress,438562.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C.almFailToOpen.SCmd_UnSuppress,438563.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C.almFailToOpen.AEShelveTMRDN,438563.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C.almFailToOpen.Bad,438563.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C.almFailToOpen.Suppress,438564.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.UnSuppress,438564.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Shelve,438564.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.UnShelve,438564.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Enable,438564.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Disable,438564.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Ack,438564.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Reset,438564.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C.almFailToOpen.Suppressed,438564.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C.almFailToOpen.Shelved,438564.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C.almFailToOpen.Disabled,438564.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C.almFailToOpen.Acked,438564.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C.almFailToOpen.Alarm,438564.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Fault,438574.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C.almFailToClose.AlarmState,438574.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C.almFailToClose.GlobalReset,438574.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C.almFailToClose.FaultInAlarm,438574.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C.almFailToClose.ALRM,438574.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C.almFailToClose.ANUN,438574.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C.almFailToClose.AKED,438574.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C.almFailToClose.Resetable,438574.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C.almFailToClose.REST,438574.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C.almFailToClose.ACKN,438574.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C.almFailToClose.UACK,438574.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C.almFailToClose.MCmd_Enable,438574.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C.almFailToClose.MCmd_Disable,438574.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C.almFailToClose.OCmd_Shelve,438574.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C.almFailToClose.OCmd_Unshelve,438574.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C.almFailToClose.SCmd_Suppress,438574.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C.almFailToClose.SCmd_UnSuppress,438575.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C.almFailToClose.AEShelveTMRDN,438575.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C.almFailToClose.Bad,438575.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C.almFailToClose.Suppress,438576.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.UnSuppress,438576.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Shelve,438576.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.UnShelve,438576.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Enable,438576.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Disable,438576.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Ack,438576.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Reset,438576.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C.almFailToClose.Suppressed,438576.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C.almFailToClose.Shelved,438576.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C.almFailToClose.Disabled,438576.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C.almFailToClose.Acked,438576.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C.almFailToClose.Alarm,438576.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Fault,438586.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C.almActuatorFault.AlarmState,438586.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C.almActuatorFault.GlobalReset,438586.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C.almActuatorFault.FaultInAlarm,438586.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C.almActuatorFault.ALRM,438586.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C.almActuatorFault.ANUN,438586.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C.almActuatorFault.AKED,438586.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C.almActuatorFault.Resetable,438586.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C.almActuatorFault.REST,438586.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C.almActuatorFault.ACKN,438586.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C.almActuatorFault.UACK,438586.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C.almActuatorFault.MCmd_Enable,438586.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C.almActuatorFault.MCmd_Disable,438586.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C.almActuatorFault.OCmd_Shelve,438586.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C.almActuatorFault.OCmd_Unshelve,438586.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C.almActuatorFault.SCmd_Suppress,438586.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C.almActuatorFault.SCmd_UnSuppress,438587.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C.almActuatorFault.AEShelveTMRDN,438587.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C.almActuatorFault.Bad,438587.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C.almActuatorFault.Suppress,438588.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.UnSuppress,438588.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Shelve,438588.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.UnShelve,438588.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Enable,438588.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Disable,438588.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Ack,438588.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Reset,438588.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C.almActuatorFault.Suppressed,438588.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C.almActuatorFault.Shelved,438588.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C.almActuatorFault.Disabled,438588.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C.almActuatorFault.Acked,438588.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C.almActuatorFault.Alarm,438588.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Fault,438598.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4C.almPLCFault.AlarmState,438598.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4C.almPLCFault.GlobalReset,438598.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4C.almPLCFault.FaultInAlarm,438598.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4C.almPLCFault.ALRM,438598.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4C.almPLCFault.ANUN,438598.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4C.almPLCFault.AKED,438598.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4C.almPLCFault.Resetable,438598.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4C.almPLCFault.REST,438598.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4C.almPLCFault.ACKN,438598.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4C.almPLCFault.UACK,438598.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4C.almPLCFault.MCmd_Enable,438598.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4C.almPLCFault.MCmd_Disable,438598.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4C.almPLCFault.OCmd_Shelve,438598.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4C.almPLCFault.OCmd_Unshelve,438598.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4C.almPLCFault.SCmd_Suppress,438598.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4C.almPLCFault.SCmd_UnSuppress,438599.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4C.almPLCFault.AEShelveTMRDN,438599.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4C.almPLCFault.Bad,438599.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4C.almPLCFault.Suppress,438600.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.UnSuppress,438600.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Shelve,438600.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.UnShelve,438600.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Enable,438600.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Disable,438600.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Ack,438600.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Reset,438600.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4C.almPLCFault.Suppressed,438600.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4C.almPLCFault.Shelved,438600.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4C.almPLCFault.Disabled,438600.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4C.almPLCFault.Acked,438600.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4C.almPLCFault.Alarm,438600.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Fault,438642.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D.almFailToOpen.AlarmState,438642.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D.almFailToOpen.GlobalReset,438642.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D.almFailToOpen.FaultInAlarm,438642.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D.almFailToOpen.ALRM,438642.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D.almFailToOpen.ANUN,438642.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D.almFailToOpen.AKED,438642.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D.almFailToOpen.Resetable,438642.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D.almFailToOpen.REST,438642.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D.almFailToOpen.ACKN,438642.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D.almFailToOpen.UACK,438642.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D.almFailToOpen.MCmd_Enable,438642.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D.almFailToOpen.MCmd_Disable,438642.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D.almFailToOpen.OCmd_Shelve,438642.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D.almFailToOpen.OCmd_Unshelve,438642.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D.almFailToOpen.SCmd_Suppress,438642.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D.almFailToOpen.SCmd_UnSuppress,438643.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D.almFailToOpen.AEShelveTMRDN,438643.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D.almFailToOpen.Bad,438643.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D.almFailToOpen.Suppress,438644.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.UnSuppress,438644.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Shelve,438644.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.UnShelve,438644.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Enable,438644.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Disable,438644.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Ack,438644.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Reset,438644.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D.almFailToOpen.Suppressed,438644.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D.almFailToOpen.Shelved,438644.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D.almFailToOpen.Disabled,438644.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D.almFailToOpen.Acked,438644.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D.almFailToOpen.Alarm,438644.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Fault,438654.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D.almFailToClose.AlarmState,438654.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D.almFailToClose.GlobalReset,438654.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D.almFailToClose.FaultInAlarm,438654.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D.almFailToClose.ALRM,438654.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D.almFailToClose.ANUN,438654.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D.almFailToClose.AKED,438654.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D.almFailToClose.Resetable,438654.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D.almFailToClose.REST,438654.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D.almFailToClose.ACKN,438654.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D.almFailToClose.UACK,438654.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D.almFailToClose.MCmd_Enable,438654.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D.almFailToClose.MCmd_Disable,438654.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D.almFailToClose.OCmd_Shelve,438654.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D.almFailToClose.OCmd_Unshelve,438654.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D.almFailToClose.SCmd_Suppress,438654.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D.almFailToClose.SCmd_UnSuppress,438655.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D.almFailToClose.AEShelveTMRDN,438655.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D.almFailToClose.Bad,438655.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D.almFailToClose.Suppress,438656.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.UnSuppress,438656.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Shelve,438656.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.UnShelve,438656.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Enable,438656.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Disable,438656.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Ack,438656.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Reset,438656.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D.almFailToClose.Suppressed,438656.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D.almFailToClose.Shelved,438656.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D.almFailToClose.Disabled,438656.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D.almFailToClose.Acked,438656.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D.almFailToClose.Alarm,438656.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Fault,438666.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D.almActuatorFault.AlarmState,438666.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D.almActuatorFault.GlobalReset,438666.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D.almActuatorFault.FaultInAlarm,438666.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D.almActuatorFault.ALRM,438666.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D.almActuatorFault.ANUN,438666.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D.almActuatorFault.AKED,438666.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D.almActuatorFault.Resetable,438666.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D.almActuatorFault.REST,438666.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D.almActuatorFault.ACKN,438666.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D.almActuatorFault.UACK,438666.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D.almActuatorFault.MCmd_Enable,438666.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D.almActuatorFault.MCmd_Disable,438666.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D.almActuatorFault.OCmd_Shelve,438666.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D.almActuatorFault.OCmd_Unshelve,438666.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D.almActuatorFault.SCmd_Suppress,438666.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D.almActuatorFault.SCmd_UnSuppress,438667.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D.almActuatorFault.AEShelveTMRDN,438667.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D.almActuatorFault.Bad,438667.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D.almActuatorFault.Suppress,438668.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.UnSuppress,438668.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Shelve,438668.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.UnShelve,438668.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Enable,438668.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Disable,438668.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Ack,438668.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Reset,438668.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D.almActuatorFault.Suppressed,438668.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D.almActuatorFault.Shelved,438668.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D.almActuatorFault.Disabled,438668.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D.almActuatorFault.Acked,438668.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D.almActuatorFault.Alarm,438668.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Fault,438678.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_4D.almPLCFault.AlarmState,438678.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_4D.almPLCFault.GlobalReset,438678.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_4D.almPLCFault.FaultInAlarm,438678.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_4D.almPLCFault.ALRM,438678.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_4D.almPLCFault.ANUN,438678.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_4D.almPLCFault.AKED,438678.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_4D.almPLCFault.Resetable,438678.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_4D.almPLCFault.REST,438678.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_4D.almPLCFault.ACKN,438678.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_4D.almPLCFault.UACK,438678.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_4D.almPLCFault.MCmd_Enable,438678.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_4D.almPLCFault.MCmd_Disable,438678.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_4D.almPLCFault.OCmd_Shelve,438678.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_4D.almPLCFault.OCmd_Unshelve,438678.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_4D.almPLCFault.SCmd_Suppress,438678.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_4D.almPLCFault.SCmd_UnSuppress,438679.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_4D.almPLCFault.AEShelveTMRDN,438679.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_4D.almPLCFault.Bad,438679.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_4D.almPLCFault.Suppress,438680.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.UnSuppress,438680.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Shelve,438680.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.UnShelve,438680.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Enable,438680.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Disable,438680.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Ack,438680.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Reset,438680.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_4D.almPLCFault.Suppressed,438680.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_4D.almPLCFault.Shelved,438680.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_4D.almPLCFault.Disabled,438680.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_4D.almPLCFault.Acked,438680.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_4D.almPLCFault.Alarm,438680.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Fault,438722.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A.almFailToOpen.AlarmState,438722.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A.almFailToOpen.GlobalReset,438722.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A.almFailToOpen.FaultInAlarm,438722.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A.almFailToOpen.ALRM,438722.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A.almFailToOpen.ANUN,438722.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A.almFailToOpen.AKED,438722.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A.almFailToOpen.Resetable,438722.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A.almFailToOpen.REST,438722.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A.almFailToOpen.ACKN,438722.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A.almFailToOpen.UACK,438722.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A.almFailToOpen.MCmd_Enable,438722.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A.almFailToOpen.MCmd_Disable,438722.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A.almFailToOpen.OCmd_Shelve,438722.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A.almFailToOpen.OCmd_Unshelve,438722.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A.almFailToOpen.SCmd_Suppress,438722.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A.almFailToOpen.SCmd_UnSuppress,438723.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A.almFailToOpen.AEShelveTMRDN,438723.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A.almFailToOpen.Bad,438723.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A.almFailToOpen.Suppress,438724.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.UnSuppress,438724.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Shelve,438724.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.UnShelve,438724.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Enable,438724.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Disable,438724.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Ack,438724.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Reset,438724.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A.almFailToOpen.Suppressed,438724.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A.almFailToOpen.Shelved,438724.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A.almFailToOpen.Disabled,438724.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A.almFailToOpen.Acked,438724.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A.almFailToOpen.Alarm,438724.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Fault,438734.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A.almFailToClose.AlarmState,438734.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A.almFailToClose.GlobalReset,438734.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A.almFailToClose.FaultInAlarm,438734.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A.almFailToClose.ALRM,438734.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A.almFailToClose.ANUN,438734.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A.almFailToClose.AKED,438734.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A.almFailToClose.Resetable,438734.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A.almFailToClose.REST,438734.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A.almFailToClose.ACKN,438734.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A.almFailToClose.UACK,438734.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A.almFailToClose.MCmd_Enable,438734.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A.almFailToClose.MCmd_Disable,438734.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A.almFailToClose.OCmd_Shelve,438734.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A.almFailToClose.OCmd_Unshelve,438734.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A.almFailToClose.SCmd_Suppress,438734.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A.almFailToClose.SCmd_UnSuppress,438735.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A.almFailToClose.AEShelveTMRDN,438735.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A.almFailToClose.Bad,438735.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A.almFailToClose.Suppress,438736.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.UnSuppress,438736.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Shelve,438736.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.UnShelve,438736.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Enable,438736.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Disable,438736.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Ack,438736.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Reset,438736.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A.almFailToClose.Suppressed,438736.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A.almFailToClose.Shelved,438736.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A.almFailToClose.Disabled,438736.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A.almFailToClose.Acked,438736.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A.almFailToClose.Alarm,438736.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Fault,438746.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A.almActuatorFault.AlarmState,438746.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A.almActuatorFault.GlobalReset,438746.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A.almActuatorFault.FaultInAlarm,438746.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A.almActuatorFault.ALRM,438746.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A.almActuatorFault.ANUN,438746.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A.almActuatorFault.AKED,438746.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A.almActuatorFault.Resetable,438746.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A.almActuatorFault.REST,438746.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A.almActuatorFault.ACKN,438746.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A.almActuatorFault.UACK,438746.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A.almActuatorFault.MCmd_Enable,438746.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A.almActuatorFault.MCmd_Disable,438746.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A.almActuatorFault.OCmd_Shelve,438746.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A.almActuatorFault.OCmd_Unshelve,438746.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A.almActuatorFault.SCmd_Suppress,438746.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A.almActuatorFault.SCmd_UnSuppress,438747.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A.almActuatorFault.AEShelveTMRDN,438747.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A.almActuatorFault.Bad,438747.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A.almActuatorFault.Suppress,438748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.UnSuppress,438748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Shelve,438748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.UnShelve,438748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Enable,438748.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Disable,438748.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Ack,438748.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Reset,438748.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A.almActuatorFault.Suppressed,438748.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A.almActuatorFault.Shelved,438748.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A.almActuatorFault.Disabled,438748.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A.almActuatorFault.Acked,438748.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A.almActuatorFault.Alarm,438748.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Fault,438758.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5A.almPLCFault.AlarmState,438758.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5A.almPLCFault.GlobalReset,438758.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5A.almPLCFault.FaultInAlarm,438758.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5A.almPLCFault.ALRM,438758.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5A.almPLCFault.ANUN,438758.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5A.almPLCFault.AKED,438758.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5A.almPLCFault.Resetable,438758.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5A.almPLCFault.REST,438758.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5A.almPLCFault.ACKN,438758.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5A.almPLCFault.UACK,438758.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5A.almPLCFault.MCmd_Enable,438758.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5A.almPLCFault.MCmd_Disable,438758.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5A.almPLCFault.OCmd_Shelve,438758.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5A.almPLCFault.OCmd_Unshelve,438758.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5A.almPLCFault.SCmd_Suppress,438758.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5A.almPLCFault.SCmd_UnSuppress,438759.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5A.almPLCFault.AEShelveTMRDN,438759.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5A.almPLCFault.Bad,438759.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5A.almPLCFault.Suppress,438760.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.UnSuppress,438760.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Shelve,438760.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.UnShelve,438760.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Enable,438760.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Disable,438760.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Ack,438760.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Reset,438760.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5A.almPLCFault.Suppressed,438760.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5A.almPLCFault.Shelved,438760.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5A.almPLCFault.Disabled,438760.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5A.almPLCFault.Acked,438760.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5A.almPLCFault.Alarm,438760.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Fault,438802.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C.almFailToOpen.AlarmState,438802.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C.almFailToOpen.GlobalReset,438802.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C.almFailToOpen.FaultInAlarm,438802.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C.almFailToOpen.ALRM,438802.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C.almFailToOpen.ANUN,438802.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C.almFailToOpen.AKED,438802.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C.almFailToOpen.Resetable,438802.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C.almFailToOpen.REST,438802.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C.almFailToOpen.ACKN,438802.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C.almFailToOpen.UACK,438802.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C.almFailToOpen.MCmd_Enable,438802.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C.almFailToOpen.MCmd_Disable,438802.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C.almFailToOpen.OCmd_Shelve,438802.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C.almFailToOpen.OCmd_Unshelve,438802.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C.almFailToOpen.SCmd_Suppress,438802.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C.almFailToOpen.SCmd_UnSuppress,438803.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C.almFailToOpen.AEShelveTMRDN,438803.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C.almFailToOpen.Bad,438803.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C.almFailToOpen.Suppress,438804.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.UnSuppress,438804.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Shelve,438804.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.UnShelve,438804.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Enable,438804.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Disable,438804.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Ack,438804.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Reset,438804.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C.almFailToOpen.Suppressed,438804.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C.almFailToOpen.Shelved,438804.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C.almFailToOpen.Disabled,438804.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C.almFailToOpen.Acked,438804.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C.almFailToOpen.Alarm,438804.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Fault,438814.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C.almFailToClose.AlarmState,438814.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C.almFailToClose.GlobalReset,438814.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C.almFailToClose.FaultInAlarm,438814.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C.almFailToClose.ALRM,438814.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C.almFailToClose.ANUN,438814.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C.almFailToClose.AKED,438814.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C.almFailToClose.Resetable,438814.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C.almFailToClose.REST,438814.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C.almFailToClose.ACKN,438814.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C.almFailToClose.UACK,438814.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C.almFailToClose.MCmd_Enable,438814.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C.almFailToClose.MCmd_Disable,438814.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C.almFailToClose.OCmd_Shelve,438814.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C.almFailToClose.OCmd_Unshelve,438814.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C.almFailToClose.SCmd_Suppress,438814.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C.almFailToClose.SCmd_UnSuppress,438815.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C.almFailToClose.AEShelveTMRDN,438815.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C.almFailToClose.Bad,438815.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C.almFailToClose.Suppress,438816.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.UnSuppress,438816.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Shelve,438816.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.UnShelve,438816.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Enable,438816.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Disable,438816.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Ack,438816.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Reset,438816.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C.almFailToClose.Suppressed,438816.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C.almFailToClose.Shelved,438816.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C.almFailToClose.Disabled,438816.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C.almFailToClose.Acked,438816.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C.almFailToClose.Alarm,438816.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Fault,438826.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C.almActuatorFault.AlarmState,438826.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C.almActuatorFault.GlobalReset,438826.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C.almActuatorFault.FaultInAlarm,438826.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C.almActuatorFault.ALRM,438826.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C.almActuatorFault.ANUN,438826.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C.almActuatorFault.AKED,438826.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C.almActuatorFault.Resetable,438826.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C.almActuatorFault.REST,438826.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C.almActuatorFault.ACKN,438826.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C.almActuatorFault.UACK,438826.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C.almActuatorFault.MCmd_Enable,438826.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C.almActuatorFault.MCmd_Disable,438826.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C.almActuatorFault.OCmd_Shelve,438826.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C.almActuatorFault.OCmd_Unshelve,438826.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C.almActuatorFault.SCmd_Suppress,438826.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C.almActuatorFault.SCmd_UnSuppress,438827.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C.almActuatorFault.AEShelveTMRDN,438827.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C.almActuatorFault.Bad,438827.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C.almActuatorFault.Suppress,438828.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.UnSuppress,438828.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Shelve,438828.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.UnShelve,438828.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Enable,438828.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Disable,438828.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Ack,438828.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Reset,438828.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C.almActuatorFault.Suppressed,438828.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C.almActuatorFault.Shelved,438828.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C.almActuatorFault.Disabled,438828.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C.almActuatorFault.Acked,438828.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C.almActuatorFault.Alarm,438828.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Fault,438838.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5C.almPLCFault.AlarmState,438838.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5C.almPLCFault.GlobalReset,438838.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5C.almPLCFault.FaultInAlarm,438838.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5C.almPLCFault.ALRM,438838.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5C.almPLCFault.ANUN,438838.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5C.almPLCFault.AKED,438838.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5C.almPLCFault.Resetable,438838.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5C.almPLCFault.REST,438838.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5C.almPLCFault.ACKN,438838.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5C.almPLCFault.UACK,438838.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5C.almPLCFault.MCmd_Enable,438838.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5C.almPLCFault.MCmd_Disable,438838.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5C.almPLCFault.OCmd_Shelve,438838.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5C.almPLCFault.OCmd_Unshelve,438838.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5C.almPLCFault.SCmd_Suppress,438838.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5C.almPLCFault.SCmd_UnSuppress,438839.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5C.almPLCFault.AEShelveTMRDN,438839.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5C.almPLCFault.Bad,438839.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5C.almPLCFault.Suppress,438840.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.UnSuppress,438840.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Shelve,438840.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.UnShelve,438840.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Enable,438840.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Disable,438840.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Ack,438840.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Reset,438840.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5C.almPLCFault.Suppressed,438840.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5C.almPLCFault.Shelved,438840.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5C.almPLCFault.Disabled,438840.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5C.almPLCFault.Acked,438840.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5C.almPLCFault.Alarm,438840.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Fault,438882.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D.almFailToOpen.AlarmState,438882.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D.almFailToOpen.GlobalReset,438882.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D.almFailToOpen.FaultInAlarm,438882.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D.almFailToOpen.ALRM,438882.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D.almFailToOpen.ANUN,438882.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D.almFailToOpen.AKED,438882.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D.almFailToOpen.Resetable,438882.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D.almFailToOpen.REST,438882.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D.almFailToOpen.ACKN,438882.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D.almFailToOpen.UACK,438882.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D.almFailToOpen.MCmd_Enable,438882.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D.almFailToOpen.MCmd_Disable,438882.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D.almFailToOpen.OCmd_Shelve,438882.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D.almFailToOpen.OCmd_Unshelve,438882.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D.almFailToOpen.SCmd_Suppress,438882.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D.almFailToOpen.SCmd_UnSuppress,438883.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D.almFailToOpen.AEShelveTMRDN,438883.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D.almFailToOpen.Bad,438883.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D.almFailToOpen.Suppress,438884.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.UnSuppress,438884.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Shelve,438884.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.UnShelve,438884.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Enable,438884.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Disable,438884.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Ack,438884.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Reset,438884.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D.almFailToOpen.Suppressed,438884.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D.almFailToOpen.Shelved,438884.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D.almFailToOpen.Disabled,438884.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D.almFailToOpen.Acked,438884.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D.almFailToOpen.Alarm,438884.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Fault,438894.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D.almFailToClose.AlarmState,438894.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D.almFailToClose.GlobalReset,438894.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D.almFailToClose.FaultInAlarm,438894.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D.almFailToClose.ALRM,438894.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D.almFailToClose.ANUN,438894.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D.almFailToClose.AKED,438894.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D.almFailToClose.Resetable,438894.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D.almFailToClose.REST,438894.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D.almFailToClose.ACKN,438894.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D.almFailToClose.UACK,438894.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D.almFailToClose.MCmd_Enable,438894.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D.almFailToClose.MCmd_Disable,438894.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D.almFailToClose.OCmd_Shelve,438894.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D.almFailToClose.OCmd_Unshelve,438894.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D.almFailToClose.SCmd_Suppress,438894.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D.almFailToClose.SCmd_UnSuppress,438895.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D.almFailToClose.AEShelveTMRDN,438895.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D.almFailToClose.Bad,438895.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D.almFailToClose.Suppress,438896.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.UnSuppress,438896.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Shelve,438896.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.UnShelve,438896.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Enable,438896.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Disable,438896.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Ack,438896.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Reset,438896.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D.almFailToClose.Suppressed,438896.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D.almFailToClose.Shelved,438896.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D.almFailToClose.Disabled,438896.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D.almFailToClose.Acked,438896.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D.almFailToClose.Alarm,438896.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Fault,438906.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D.almActuatorFault.AlarmState,438906.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D.almActuatorFault.GlobalReset,438906.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D.almActuatorFault.FaultInAlarm,438906.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D.almActuatorFault.ALRM,438906.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D.almActuatorFault.ANUN,438906.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D.almActuatorFault.AKED,438906.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D.almActuatorFault.Resetable,438906.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D.almActuatorFault.REST,438906.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D.almActuatorFault.ACKN,438906.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D.almActuatorFault.UACK,438906.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D.almActuatorFault.MCmd_Enable,438906.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D.almActuatorFault.MCmd_Disable,438906.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D.almActuatorFault.OCmd_Shelve,438906.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D.almActuatorFault.OCmd_Unshelve,438906.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D.almActuatorFault.SCmd_Suppress,438906.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D.almActuatorFault.SCmd_UnSuppress,438907.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D.almActuatorFault.AEShelveTMRDN,438907.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D.almActuatorFault.Bad,438907.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D.almActuatorFault.Suppress,438908.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.UnSuppress,438908.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Shelve,438908.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.UnShelve,438908.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Enable,438908.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Disable,438908.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Ack,438908.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Reset,438908.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D.almActuatorFault.Suppressed,438908.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D.almActuatorFault.Shelved,438908.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D.almActuatorFault.Disabled,438908.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D.almActuatorFault.Acked,438908.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D.almActuatorFault.Alarm,438908.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Fault,438918.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_5D.almPLCFault.AlarmState,438918.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_5D.almPLCFault.GlobalReset,438918.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_5D.almPLCFault.FaultInAlarm,438918.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_5D.almPLCFault.ALRM,438918.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_5D.almPLCFault.ANUN,438918.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_5D.almPLCFault.AKED,438918.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_5D.almPLCFault.Resetable,438918.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_5D.almPLCFault.REST,438918.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_5D.almPLCFault.ACKN,438918.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_5D.almPLCFault.UACK,438918.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_5D.almPLCFault.MCmd_Enable,438918.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_5D.almPLCFault.MCmd_Disable,438918.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_5D.almPLCFault.OCmd_Shelve,438918.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_5D.almPLCFault.OCmd_Unshelve,438918.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_5D.almPLCFault.SCmd_Suppress,438918.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_5D.almPLCFault.SCmd_UnSuppress,438919.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_5D.almPLCFault.AEShelveTMRDN,438919.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_5D.almPLCFault.Bad,438919.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_5D.almPLCFault.Suppress,438920.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.UnSuppress,438920.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Shelve,438920.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.UnShelve,438920.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Enable,438920.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Disable,438920.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Ack,438920.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Reset,438920.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_5D.almPLCFault.Suppressed,438920.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_5D.almPLCFault.Shelved,438920.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_5D.almPLCFault.Disabled,438920.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_5D.almPLCFault.Acked,438920.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_5D.almPLCFault.Alarm,438920.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Fault,438962.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A.almFailToOpen.AlarmState,438962.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A.almFailToOpen.GlobalReset,438962.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A.almFailToOpen.FaultInAlarm,438962.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A.almFailToOpen.ALRM,438962.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A.almFailToOpen.ANUN,438962.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A.almFailToOpen.AKED,438962.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A.almFailToOpen.Resetable,438962.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A.almFailToOpen.REST,438962.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A.almFailToOpen.ACKN,438962.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A.almFailToOpen.UACK,438962.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A.almFailToOpen.MCmd_Enable,438962.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A.almFailToOpen.MCmd_Disable,438962.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A.almFailToOpen.OCmd_Shelve,438962.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A.almFailToOpen.OCmd_Unshelve,438962.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A.almFailToOpen.SCmd_Suppress,438962.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A.almFailToOpen.SCmd_UnSuppress,438963.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A.almFailToOpen.AEShelveTMRDN,438963.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A.almFailToOpen.Bad,438963.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A.almFailToOpen.Suppress,438964.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.UnSuppress,438964.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Shelve,438964.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.UnShelve,438964.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Enable,438964.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Disable,438964.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Ack,438964.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Reset,438964.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A.almFailToOpen.Suppressed,438964.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A.almFailToOpen.Shelved,438964.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A.almFailToOpen.Disabled,438964.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A.almFailToOpen.Acked,438964.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A.almFailToOpen.Alarm,438964.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Fault,438974.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A.almFailToClose.AlarmState,438974.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A.almFailToClose.GlobalReset,438974.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A.almFailToClose.FaultInAlarm,438974.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A.almFailToClose.ALRM,438974.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A.almFailToClose.ANUN,438974.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A.almFailToClose.AKED,438974.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A.almFailToClose.Resetable,438974.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A.almFailToClose.REST,438974.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A.almFailToClose.ACKN,438974.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A.almFailToClose.UACK,438974.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A.almFailToClose.MCmd_Enable,438974.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A.almFailToClose.MCmd_Disable,438974.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A.almFailToClose.OCmd_Shelve,438974.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A.almFailToClose.OCmd_Unshelve,438974.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A.almFailToClose.SCmd_Suppress,438974.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A.almFailToClose.SCmd_UnSuppress,438975.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A.almFailToClose.AEShelveTMRDN,438975.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A.almFailToClose.Bad,438975.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A.almFailToClose.Suppress,438976.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.UnSuppress,438976.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Shelve,438976.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.UnShelve,438976.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Enable,438976.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Disable,438976.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Ack,438976.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Reset,438976.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A.almFailToClose.Suppressed,438976.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A.almFailToClose.Shelved,438976.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A.almFailToClose.Disabled,438976.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A.almFailToClose.Acked,438976.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A.almFailToClose.Alarm,438976.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Fault,438986.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A.almActuatorFault.AlarmState,438986.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A.almActuatorFault.GlobalReset,438986.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A.almActuatorFault.FaultInAlarm,438986.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A.almActuatorFault.ALRM,438986.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A.almActuatorFault.ANUN,438986.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A.almActuatorFault.AKED,438986.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A.almActuatorFault.Resetable,438986.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A.almActuatorFault.REST,438986.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A.almActuatorFault.ACKN,438986.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A.almActuatorFault.UACK,438986.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A.almActuatorFault.MCmd_Enable,438986.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A.almActuatorFault.MCmd_Disable,438986.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A.almActuatorFault.OCmd_Shelve,438986.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A.almActuatorFault.OCmd_Unshelve,438986.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A.almActuatorFault.SCmd_Suppress,438986.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A.almActuatorFault.SCmd_UnSuppress,438987.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A.almActuatorFault.AEShelveTMRDN,438987.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A.almActuatorFault.Bad,438987.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A.almActuatorFault.Suppress,438988.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.UnSuppress,438988.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Shelve,438988.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.UnShelve,438988.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Enable,438988.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Disable,438988.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Ack,438988.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Reset,438988.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A.almActuatorFault.Suppressed,438988.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A.almActuatorFault.Shelved,438988.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A.almActuatorFault.Disabled,438988.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A.almActuatorFault.Acked,438988.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A.almActuatorFault.Alarm,438988.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Fault,438998.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6A.almPLCFault.AlarmState,438998.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6A.almPLCFault.GlobalReset,438998.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6A.almPLCFault.FaultInAlarm,438998.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6A.almPLCFault.ALRM,438998.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6A.almPLCFault.ANUN,438998.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6A.almPLCFault.AKED,438998.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6A.almPLCFault.Resetable,438998.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6A.almPLCFault.REST,438998.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6A.almPLCFault.ACKN,438998.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6A.almPLCFault.UACK,438998.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6A.almPLCFault.MCmd_Enable,438998.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6A.almPLCFault.MCmd_Disable,438998.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6A.almPLCFault.OCmd_Shelve,438998.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6A.almPLCFault.OCmd_Unshelve,438998.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6A.almPLCFault.SCmd_Suppress,438998.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6A.almPLCFault.SCmd_UnSuppress,438999.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6A.almPLCFault.AEShelveTMRDN,438999.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6A.almPLCFault.Bad,438999.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6A.almPLCFault.Suppress,439000.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.UnSuppress,439000.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Shelve,439000.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.UnShelve,439000.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Enable,439000.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Disable,439000.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Ack,439000.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Reset,439000.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6A.almPLCFault.Suppressed,439000.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6A.almPLCFault.Shelved,439000.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6A.almPLCFault.Disabled,439000.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6A.almPLCFault.Acked,439000.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6A.almPLCFault.Alarm,439000.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Fault,439042.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C.almFailToOpen.AlarmState,439042.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C.almFailToOpen.GlobalReset,439042.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C.almFailToOpen.FaultInAlarm,439042.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C.almFailToOpen.ALRM,439042.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C.almFailToOpen.ANUN,439042.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C.almFailToOpen.AKED,439042.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C.almFailToOpen.Resetable,439042.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C.almFailToOpen.REST,439042.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C.almFailToOpen.ACKN,439042.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C.almFailToOpen.UACK,439042.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C.almFailToOpen.MCmd_Enable,439042.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C.almFailToOpen.MCmd_Disable,439042.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C.almFailToOpen.OCmd_Shelve,439042.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C.almFailToOpen.OCmd_Unshelve,439042.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C.almFailToOpen.SCmd_Suppress,439042.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C.almFailToOpen.SCmd_UnSuppress,439043.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C.almFailToOpen.AEShelveTMRDN,439043.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C.almFailToOpen.Bad,439043.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C.almFailToOpen.Suppress,439044.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.UnSuppress,439044.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Shelve,439044.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.UnShelve,439044.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Enable,439044.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Disable,439044.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Ack,439044.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Reset,439044.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C.almFailToOpen.Suppressed,439044.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C.almFailToOpen.Shelved,439044.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C.almFailToOpen.Disabled,439044.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C.almFailToOpen.Acked,439044.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C.almFailToOpen.Alarm,439044.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Fault,439054.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C.almFailToClose.AlarmState,439054.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C.almFailToClose.GlobalReset,439054.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C.almFailToClose.FaultInAlarm,439054.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C.almFailToClose.ALRM,439054.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C.almFailToClose.ANUN,439054.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C.almFailToClose.AKED,439054.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C.almFailToClose.Resetable,439054.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C.almFailToClose.REST,439054.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C.almFailToClose.ACKN,439054.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C.almFailToClose.UACK,439054.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C.almFailToClose.MCmd_Enable,439054.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C.almFailToClose.MCmd_Disable,439054.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C.almFailToClose.OCmd_Shelve,439054.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C.almFailToClose.OCmd_Unshelve,439054.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C.almFailToClose.SCmd_Suppress,439054.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C.almFailToClose.SCmd_UnSuppress,439055.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C.almFailToClose.AEShelveTMRDN,439055.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C.almFailToClose.Bad,439055.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C.almFailToClose.Suppress,439056.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.UnSuppress,439056.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Shelve,439056.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.UnShelve,439056.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Enable,439056.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Disable,439056.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Ack,439056.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Reset,439056.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C.almFailToClose.Suppressed,439056.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C.almFailToClose.Shelved,439056.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C.almFailToClose.Disabled,439056.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C.almFailToClose.Acked,439056.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C.almFailToClose.Alarm,439056.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Fault,439066.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C.almActuatorFault.AlarmState,439066.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C.almActuatorFault.GlobalReset,439066.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C.almActuatorFault.FaultInAlarm,439066.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C.almActuatorFault.ALRM,439066.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C.almActuatorFault.ANUN,439066.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C.almActuatorFault.AKED,439066.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C.almActuatorFault.Resetable,439066.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C.almActuatorFault.REST,439066.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C.almActuatorFault.ACKN,439066.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C.almActuatorFault.UACK,439066.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C.almActuatorFault.MCmd_Enable,439066.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C.almActuatorFault.MCmd_Disable,439066.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C.almActuatorFault.OCmd_Shelve,439066.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C.almActuatorFault.OCmd_Unshelve,439066.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C.almActuatorFault.SCmd_Suppress,439066.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C.almActuatorFault.SCmd_UnSuppress,439067.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C.almActuatorFault.AEShelveTMRDN,439067.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C.almActuatorFault.Bad,439067.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C.almActuatorFault.Suppress,439068.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.UnSuppress,439068.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Shelve,439068.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.UnShelve,439068.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Enable,439068.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Disable,439068.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Ack,439068.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Reset,439068.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C.almActuatorFault.Suppressed,439068.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C.almActuatorFault.Shelved,439068.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C.almActuatorFault.Disabled,439068.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C.almActuatorFault.Acked,439068.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C.almActuatorFault.Alarm,439068.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Fault,439078.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6C.almPLCFault.AlarmState,439078.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6C.almPLCFault.GlobalReset,439078.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6C.almPLCFault.FaultInAlarm,439078.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6C.almPLCFault.ALRM,439078.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6C.almPLCFault.ANUN,439078.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6C.almPLCFault.AKED,439078.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6C.almPLCFault.Resetable,439078.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6C.almPLCFault.REST,439078.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6C.almPLCFault.ACKN,439078.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6C.almPLCFault.UACK,439078.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6C.almPLCFault.MCmd_Enable,439078.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6C.almPLCFault.MCmd_Disable,439078.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6C.almPLCFault.OCmd_Shelve,439078.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6C.almPLCFault.OCmd_Unshelve,439078.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6C.almPLCFault.SCmd_Suppress,439078.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6C.almPLCFault.SCmd_UnSuppress,439079.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6C.almPLCFault.AEShelveTMRDN,439079.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6C.almPLCFault.Bad,439079.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6C.almPLCFault.Suppress,439080.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.UnSuppress,439080.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Shelve,439080.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.UnShelve,439080.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Enable,439080.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Disable,439080.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Ack,439080.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Reset,439080.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6C.almPLCFault.Suppressed,439080.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6C.almPLCFault.Shelved,439080.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6C.almPLCFault.Disabled,439080.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6C.almPLCFault.Acked,439080.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6C.almPLCFault.Alarm,439080.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Fault,439122.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D.almFailToOpen.AlarmState,439122.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D.almFailToOpen.GlobalReset,439122.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D.almFailToOpen.FaultInAlarm,439122.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D.almFailToOpen.ALRM,439122.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D.almFailToOpen.ANUN,439122.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D.almFailToOpen.AKED,439122.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D.almFailToOpen.Resetable,439122.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D.almFailToOpen.REST,439122.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D.almFailToOpen.ACKN,439122.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D.almFailToOpen.UACK,439122.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D.almFailToOpen.MCmd_Enable,439122.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D.almFailToOpen.MCmd_Disable,439122.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D.almFailToOpen.OCmd_Shelve,439122.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D.almFailToOpen.OCmd_Unshelve,439122.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D.almFailToOpen.SCmd_Suppress,439122.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D.almFailToOpen.SCmd_UnSuppress,439123.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D.almFailToOpen.AEShelveTMRDN,439123.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D.almFailToOpen.Bad,439123.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D.almFailToOpen.Suppress,439124.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.UnSuppress,439124.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Shelve,439124.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.UnShelve,439124.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Enable,439124.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Disable,439124.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Ack,439124.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Reset,439124.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D.almFailToOpen.Suppressed,439124.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D.almFailToOpen.Shelved,439124.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D.almFailToOpen.Disabled,439124.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D.almFailToOpen.Acked,439124.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D.almFailToOpen.Alarm,439124.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Fault,439134.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D.almFailToClose.AlarmState,439134.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D.almFailToClose.GlobalReset,439134.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D.almFailToClose.FaultInAlarm,439134.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D.almFailToClose.ALRM,439134.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D.almFailToClose.ANUN,439134.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D.almFailToClose.AKED,439134.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D.almFailToClose.Resetable,439134.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D.almFailToClose.REST,439134.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D.almFailToClose.ACKN,439134.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D.almFailToClose.UACK,439134.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D.almFailToClose.MCmd_Enable,439134.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D.almFailToClose.MCmd_Disable,439134.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D.almFailToClose.OCmd_Shelve,439134.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D.almFailToClose.OCmd_Unshelve,439134.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D.almFailToClose.SCmd_Suppress,439134.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D.almFailToClose.SCmd_UnSuppress,439135.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D.almFailToClose.AEShelveTMRDN,439135.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D.almFailToClose.Bad,439135.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D.almFailToClose.Suppress,439136.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.UnSuppress,439136.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Shelve,439136.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.UnShelve,439136.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Enable,439136.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Disable,439136.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Ack,439136.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Reset,439136.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D.almFailToClose.Suppressed,439136.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D.almFailToClose.Shelved,439136.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D.almFailToClose.Disabled,439136.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D.almFailToClose.Acked,439136.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D.almFailToClose.Alarm,439136.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Fault,439146.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D.almActuatorFault.AlarmState,439146.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D.almActuatorFault.GlobalReset,439146.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D.almActuatorFault.FaultInAlarm,439146.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D.almActuatorFault.ALRM,439146.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D.almActuatorFault.ANUN,439146.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D.almActuatorFault.AKED,439146.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D.almActuatorFault.Resetable,439146.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D.almActuatorFault.REST,439146.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D.almActuatorFault.ACKN,439146.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D.almActuatorFault.UACK,439146.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D.almActuatorFault.MCmd_Enable,439146.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D.almActuatorFault.MCmd_Disable,439146.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D.almActuatorFault.OCmd_Shelve,439146.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D.almActuatorFault.OCmd_Unshelve,439146.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D.almActuatorFault.SCmd_Suppress,439146.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D.almActuatorFault.SCmd_UnSuppress,439147.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D.almActuatorFault.AEShelveTMRDN,439147.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D.almActuatorFault.Bad,439147.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D.almActuatorFault.Suppress,439148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.UnSuppress,439148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Shelve,439148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.UnShelve,439148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Enable,439148.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Disable,439148.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Ack,439148.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Reset,439148.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D.almActuatorFault.Suppressed,439148.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D.almActuatorFault.Shelved,439148.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D.almActuatorFault.Disabled,439148.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D.almActuatorFault.Acked,439148.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D.almActuatorFault.Alarm,439148.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Fault,439158.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_6D.almPLCFault.AlarmState,439158.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_6D.almPLCFault.GlobalReset,439158.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_6D.almPLCFault.FaultInAlarm,439158.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_6D.almPLCFault.ALRM,439158.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_6D.almPLCFault.ANUN,439158.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_6D.almPLCFault.AKED,439158.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_6D.almPLCFault.Resetable,439158.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_6D.almPLCFault.REST,439158.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_6D.almPLCFault.ACKN,439158.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_6D.almPLCFault.UACK,439158.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_6D.almPLCFault.MCmd_Enable,439158.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_6D.almPLCFault.MCmd_Disable,439158.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_6D.almPLCFault.OCmd_Shelve,439158.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_6D.almPLCFault.OCmd_Unshelve,439158.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_6D.almPLCFault.SCmd_Suppress,439158.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_6D.almPLCFault.SCmd_UnSuppress,439159.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_6D.almPLCFault.AEShelveTMRDN,439159.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_6D.almPLCFault.Bad,439159.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_6D.almPLCFault.Suppress,439160.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.UnSuppress,439160.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Shelve,439160.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.UnShelve,439160.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Enable,439160.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Disable,439160.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Ack,439160.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Reset,439160.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_6D.almPLCFault.Suppressed,439160.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_6D.almPLCFault.Shelved,439160.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_6D.almPLCFault.Disabled,439160.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_6D.almPLCFault.Acked,439160.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_6D.almPLCFault.Alarm,439160.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Fault,439202.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A.almFailToOpen.AlarmState,439202.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A.almFailToOpen.GlobalReset,439202.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A.almFailToOpen.FaultInAlarm,439202.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A.almFailToOpen.ALRM,439202.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A.almFailToOpen.ANUN,439202.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A.almFailToOpen.AKED,439202.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A.almFailToOpen.Resetable,439202.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A.almFailToOpen.REST,439202.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A.almFailToOpen.ACKN,439202.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A.almFailToOpen.UACK,439202.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A.almFailToOpen.MCmd_Enable,439202.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A.almFailToOpen.MCmd_Disable,439202.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A.almFailToOpen.OCmd_Shelve,439202.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A.almFailToOpen.OCmd_Unshelve,439202.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A.almFailToOpen.SCmd_Suppress,439202.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A.almFailToOpen.SCmd_UnSuppress,439203.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A.almFailToOpen.AEShelveTMRDN,439203.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A.almFailToOpen.Bad,439203.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A.almFailToOpen.Suppress,439204.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.UnSuppress,439204.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Shelve,439204.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.UnShelve,439204.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Enable,439204.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Disable,439204.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Ack,439204.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Reset,439204.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A.almFailToOpen.Suppressed,439204.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A.almFailToOpen.Shelved,439204.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A.almFailToOpen.Disabled,439204.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A.almFailToOpen.Acked,439204.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A.almFailToOpen.Alarm,439204.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Fault,439214.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A.almFailToClose.AlarmState,439214.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A.almFailToClose.GlobalReset,439214.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A.almFailToClose.FaultInAlarm,439214.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A.almFailToClose.ALRM,439214.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A.almFailToClose.ANUN,439214.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A.almFailToClose.AKED,439214.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A.almFailToClose.Resetable,439214.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A.almFailToClose.REST,439214.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A.almFailToClose.ACKN,439214.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A.almFailToClose.UACK,439214.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A.almFailToClose.MCmd_Enable,439214.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A.almFailToClose.MCmd_Disable,439214.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A.almFailToClose.OCmd_Shelve,439214.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A.almFailToClose.OCmd_Unshelve,439214.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A.almFailToClose.SCmd_Suppress,439214.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A.almFailToClose.SCmd_UnSuppress,439215.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A.almFailToClose.AEShelveTMRDN,439215.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A.almFailToClose.Bad,439215.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A.almFailToClose.Suppress,439216.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.UnSuppress,439216.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Shelve,439216.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.UnShelve,439216.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Enable,439216.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Disable,439216.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Ack,439216.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Reset,439216.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A.almFailToClose.Suppressed,439216.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A.almFailToClose.Shelved,439216.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A.almFailToClose.Disabled,439216.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A.almFailToClose.Acked,439216.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A.almFailToClose.Alarm,439216.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Fault,439226.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A.almActuatorFault.AlarmState,439226.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A.almActuatorFault.GlobalReset,439226.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A.almActuatorFault.FaultInAlarm,439226.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A.almActuatorFault.ALRM,439226.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A.almActuatorFault.ANUN,439226.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A.almActuatorFault.AKED,439226.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A.almActuatorFault.Resetable,439226.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A.almActuatorFault.REST,439226.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A.almActuatorFault.ACKN,439226.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A.almActuatorFault.UACK,439226.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A.almActuatorFault.MCmd_Enable,439226.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A.almActuatorFault.MCmd_Disable,439226.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A.almActuatorFault.OCmd_Shelve,439226.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A.almActuatorFault.OCmd_Unshelve,439226.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A.almActuatorFault.SCmd_Suppress,439226.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A.almActuatorFault.SCmd_UnSuppress,439227.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A.almActuatorFault.AEShelveTMRDN,439227.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A.almActuatorFault.Bad,439227.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A.almActuatorFault.Suppress,439228.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.UnSuppress,439228.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Shelve,439228.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.UnShelve,439228.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Enable,439228.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Disable,439228.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Ack,439228.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Reset,439228.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A.almActuatorFault.Suppressed,439228.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A.almActuatorFault.Shelved,439228.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A.almActuatorFault.Disabled,439228.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A.almActuatorFault.Acked,439228.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A.almActuatorFault.Alarm,439228.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Fault,439238.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7A.almPLCFault.AlarmState,439238.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7A.almPLCFault.GlobalReset,439238.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7A.almPLCFault.FaultInAlarm,439238.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7A.almPLCFault.ALRM,439238.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7A.almPLCFault.ANUN,439238.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7A.almPLCFault.AKED,439238.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7A.almPLCFault.Resetable,439238.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7A.almPLCFault.REST,439238.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7A.almPLCFault.ACKN,439238.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7A.almPLCFault.UACK,439238.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7A.almPLCFault.MCmd_Enable,439238.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7A.almPLCFault.MCmd_Disable,439238.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7A.almPLCFault.OCmd_Shelve,439238.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7A.almPLCFault.OCmd_Unshelve,439238.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7A.almPLCFault.SCmd_Suppress,439238.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7A.almPLCFault.SCmd_UnSuppress,439239.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7A.almPLCFault.AEShelveTMRDN,439239.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7A.almPLCFault.Bad,439239.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7A.almPLCFault.Suppress,439240.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.UnSuppress,439240.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Shelve,439240.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.UnShelve,439240.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Enable,439240.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Disable,439240.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Ack,439240.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Reset,439240.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7A.almPLCFault.Suppressed,439240.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7A.almPLCFault.Shelved,439240.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7A.almPLCFault.Disabled,439240.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7A.almPLCFault.Acked,439240.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7A.almPLCFault.Alarm,439240.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Fault,439282.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C.almFailToOpen.AlarmState,439282.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C.almFailToOpen.GlobalReset,439282.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C.almFailToOpen.FaultInAlarm,439282.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C.almFailToOpen.ALRM,439282.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C.almFailToOpen.ANUN,439282.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C.almFailToOpen.AKED,439282.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C.almFailToOpen.Resetable,439282.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C.almFailToOpen.REST,439282.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C.almFailToOpen.ACKN,439282.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C.almFailToOpen.UACK,439282.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C.almFailToOpen.MCmd_Enable,439282.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C.almFailToOpen.MCmd_Disable,439282.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C.almFailToOpen.OCmd_Shelve,439282.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C.almFailToOpen.OCmd_Unshelve,439282.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C.almFailToOpen.SCmd_Suppress,439282.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C.almFailToOpen.SCmd_UnSuppress,439283.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C.almFailToOpen.AEShelveTMRDN,439283.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C.almFailToOpen.Bad,439283.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C.almFailToOpen.Suppress,439284.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.UnSuppress,439284.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Shelve,439284.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.UnShelve,439284.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Enable,439284.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Disable,439284.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Ack,439284.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Reset,439284.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C.almFailToOpen.Suppressed,439284.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C.almFailToOpen.Shelved,439284.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C.almFailToOpen.Disabled,439284.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C.almFailToOpen.Acked,439284.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C.almFailToOpen.Alarm,439284.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Fault,439294.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C.almFailToClose.AlarmState,439294.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C.almFailToClose.GlobalReset,439294.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C.almFailToClose.FaultInAlarm,439294.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C.almFailToClose.ALRM,439294.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C.almFailToClose.ANUN,439294.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C.almFailToClose.AKED,439294.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C.almFailToClose.Resetable,439294.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C.almFailToClose.REST,439294.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C.almFailToClose.ACKN,439294.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C.almFailToClose.UACK,439294.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C.almFailToClose.MCmd_Enable,439294.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C.almFailToClose.MCmd_Disable,439294.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C.almFailToClose.OCmd_Shelve,439294.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C.almFailToClose.OCmd_Unshelve,439294.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C.almFailToClose.SCmd_Suppress,439294.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C.almFailToClose.SCmd_UnSuppress,439295.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C.almFailToClose.AEShelveTMRDN,439295.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C.almFailToClose.Bad,439295.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C.almFailToClose.Suppress,439296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.UnSuppress,439296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Shelve,439296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.UnShelve,439296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Enable,439296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Disable,439296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Ack,439296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Reset,439296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C.almFailToClose.Suppressed,439296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C.almFailToClose.Shelved,439296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C.almFailToClose.Disabled,439296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C.almFailToClose.Acked,439296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C.almFailToClose.Alarm,439296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Fault,439306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C.almActuatorFault.AlarmState,439306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C.almActuatorFault.GlobalReset,439306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C.almActuatorFault.FaultInAlarm,439306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C.almActuatorFault.ALRM,439306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C.almActuatorFault.ANUN,439306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C.almActuatorFault.AKED,439306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C.almActuatorFault.Resetable,439306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C.almActuatorFault.REST,439306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C.almActuatorFault.ACKN,439306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C.almActuatorFault.UACK,439306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C.almActuatorFault.MCmd_Enable,439306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C.almActuatorFault.MCmd_Disable,439306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C.almActuatorFault.OCmd_Shelve,439306.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C.almActuatorFault.OCmd_Unshelve,439306.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C.almActuatorFault.SCmd_Suppress,439306.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C.almActuatorFault.SCmd_UnSuppress,439307.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C.almActuatorFault.AEShelveTMRDN,439307.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C.almActuatorFault.Bad,439307.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C.almActuatorFault.Suppress,439308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.UnSuppress,439308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Shelve,439308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.UnShelve,439308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Enable,439308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Disable,439308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Ack,439308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Reset,439308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C.almActuatorFault.Suppressed,439308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C.almActuatorFault.Shelved,439308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C.almActuatorFault.Disabled,439308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C.almActuatorFault.Acked,439308.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C.almActuatorFault.Alarm,439308.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Fault,439318.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7C.almPLCFault.AlarmState,439318.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7C.almPLCFault.GlobalReset,439318.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7C.almPLCFault.FaultInAlarm,439318.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7C.almPLCFault.ALRM,439318.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7C.almPLCFault.ANUN,439318.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7C.almPLCFault.AKED,439318.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7C.almPLCFault.Resetable,439318.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7C.almPLCFault.REST,439318.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7C.almPLCFault.ACKN,439318.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7C.almPLCFault.UACK,439318.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7C.almPLCFault.MCmd_Enable,439318.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7C.almPLCFault.MCmd_Disable,439318.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7C.almPLCFault.OCmd_Shelve,439318.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7C.almPLCFault.OCmd_Unshelve,439318.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7C.almPLCFault.SCmd_Suppress,439318.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7C.almPLCFault.SCmd_UnSuppress,439319.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7C.almPLCFault.AEShelveTMRDN,439319.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7C.almPLCFault.Bad,439319.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7C.almPLCFault.Suppress,439320.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.UnSuppress,439320.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Shelve,439320.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.UnShelve,439320.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Enable,439320.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Disable,439320.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Ack,439320.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Reset,439320.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7C.almPLCFault.Suppressed,439320.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7C.almPLCFault.Shelved,439320.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7C.almPLCFault.Disabled,439320.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7C.almPLCFault.Acked,439320.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7C.almPLCFault.Alarm,439320.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Fault,439362.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D.almFailToOpen.AlarmState,439362.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D.almFailToOpen.GlobalReset,439362.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D.almFailToOpen.FaultInAlarm,439362.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D.almFailToOpen.ALRM,439362.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D.almFailToOpen.ANUN,439362.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D.almFailToOpen.AKED,439362.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D.almFailToOpen.Resetable,439362.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D.almFailToOpen.REST,439362.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D.almFailToOpen.ACKN,439362.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D.almFailToOpen.UACK,439362.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D.almFailToOpen.MCmd_Enable,439362.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D.almFailToOpen.MCmd_Disable,439362.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D.almFailToOpen.OCmd_Shelve,439362.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D.almFailToOpen.OCmd_Unshelve,439362.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D.almFailToOpen.SCmd_Suppress,439362.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D.almFailToOpen.SCmd_UnSuppress,439363.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D.almFailToOpen.AEShelveTMRDN,439363.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D.almFailToOpen.Bad,439363.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D.almFailToOpen.Suppress,439364.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.UnSuppress,439364.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Shelve,439364.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.UnShelve,439364.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Enable,439364.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Disable,439364.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Ack,439364.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Reset,439364.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D.almFailToOpen.Suppressed,439364.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D.almFailToOpen.Shelved,439364.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D.almFailToOpen.Disabled,439364.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D.almFailToOpen.Acked,439364.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D.almFailToOpen.Alarm,439364.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Fault,439374.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D.almFailToClose.AlarmState,439374.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D.almFailToClose.GlobalReset,439374.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D.almFailToClose.FaultInAlarm,439374.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D.almFailToClose.ALRM,439374.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D.almFailToClose.ANUN,439374.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D.almFailToClose.AKED,439374.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D.almFailToClose.Resetable,439374.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D.almFailToClose.REST,439374.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D.almFailToClose.ACKN,439374.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D.almFailToClose.UACK,439374.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D.almFailToClose.MCmd_Enable,439374.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D.almFailToClose.MCmd_Disable,439374.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D.almFailToClose.OCmd_Shelve,439374.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D.almFailToClose.OCmd_Unshelve,439374.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D.almFailToClose.SCmd_Suppress,439374.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D.almFailToClose.SCmd_UnSuppress,439375.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D.almFailToClose.AEShelveTMRDN,439375.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D.almFailToClose.Bad,439375.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D.almFailToClose.Suppress,439376.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.UnSuppress,439376.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Shelve,439376.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.UnShelve,439376.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Enable,439376.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Disable,439376.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Ack,439376.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Reset,439376.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D.almFailToClose.Suppressed,439376.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D.almFailToClose.Shelved,439376.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D.almFailToClose.Disabled,439376.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D.almFailToClose.Acked,439376.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D.almFailToClose.Alarm,439376.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Fault,439386.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D.almActuatorFault.AlarmState,439386.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D.almActuatorFault.GlobalReset,439386.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D.almActuatorFault.FaultInAlarm,439386.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D.almActuatorFault.ALRM,439386.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D.almActuatorFault.ANUN,439386.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D.almActuatorFault.AKED,439386.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D.almActuatorFault.Resetable,439386.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D.almActuatorFault.REST,439386.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D.almActuatorFault.ACKN,439386.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D.almActuatorFault.UACK,439386.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D.almActuatorFault.MCmd_Enable,439386.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D.almActuatorFault.MCmd_Disable,439386.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D.almActuatorFault.OCmd_Shelve,439386.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D.almActuatorFault.OCmd_Unshelve,439386.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D.almActuatorFault.SCmd_Suppress,439386.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D.almActuatorFault.SCmd_UnSuppress,439387.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D.almActuatorFault.AEShelveTMRDN,439387.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D.almActuatorFault.Bad,439387.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D.almActuatorFault.Suppress,439388.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.UnSuppress,439388.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Shelve,439388.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.UnShelve,439388.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Enable,439388.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Disable,439388.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Ack,439388.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Reset,439388.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D.almActuatorFault.Suppressed,439388.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D.almActuatorFault.Shelved,439388.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D.almActuatorFault.Disabled,439388.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D.almActuatorFault.Acked,439388.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D.almActuatorFault.Alarm,439388.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Fault,439398.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_7D.almPLCFault.AlarmState,439398.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_7D.almPLCFault.GlobalReset,439398.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_7D.almPLCFault.FaultInAlarm,439398.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_7D.almPLCFault.ALRM,439398.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_7D.almPLCFault.ANUN,439398.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_7D.almPLCFault.AKED,439398.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_7D.almPLCFault.Resetable,439398.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_7D.almPLCFault.REST,439398.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_7D.almPLCFault.ACKN,439398.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_7D.almPLCFault.UACK,439398.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_7D.almPLCFault.MCmd_Enable,439398.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_7D.almPLCFault.MCmd_Disable,439398.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_7D.almPLCFault.OCmd_Shelve,439398.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_7D.almPLCFault.OCmd_Unshelve,439398.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_7D.almPLCFault.SCmd_Suppress,439398.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_7D.almPLCFault.SCmd_UnSuppress,439399.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_7D.almPLCFault.AEShelveTMRDN,439399.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_7D.almPLCFault.Bad,439399.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_7D.almPLCFault.Suppress,439400.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.UnSuppress,439400.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Shelve,439400.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.UnShelve,439400.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Enable,439400.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Disable,439400.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Ack,439400.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Reset,439400.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_7D.almPLCFault.Suppressed,439400.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_7D.almPLCFault.Shelved,439400.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_7D.almPLCFault.Disabled,439400.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_7D.almPLCFault.Acked,439400.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_7D.almPLCFault.Alarm,439400.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Fault,439442.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A.almFailToOpen.AlarmState,439442.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A.almFailToOpen.GlobalReset,439442.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A.almFailToOpen.FaultInAlarm,439442.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A.almFailToOpen.ALRM,439442.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A.almFailToOpen.ANUN,439442.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A.almFailToOpen.AKED,439442.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A.almFailToOpen.Resetable,439442.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A.almFailToOpen.REST,439442.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A.almFailToOpen.ACKN,439442.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A.almFailToOpen.UACK,439442.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A.almFailToOpen.MCmd_Enable,439442.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A.almFailToOpen.MCmd_Disable,439442.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A.almFailToOpen.OCmd_Shelve,439442.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A.almFailToOpen.OCmd_Unshelve,439442.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A.almFailToOpen.SCmd_Suppress,439442.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A.almFailToOpen.SCmd_UnSuppress,439443.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A.almFailToOpen.AEShelveTMRDN,439443.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A.almFailToOpen.Bad,439443.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A.almFailToOpen.Suppress,439444.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.UnSuppress,439444.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Shelve,439444.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.UnShelve,439444.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Enable,439444.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Disable,439444.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Ack,439444.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Reset,439444.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A.almFailToOpen.Suppressed,439444.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A.almFailToOpen.Shelved,439444.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A.almFailToOpen.Disabled,439444.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A.almFailToOpen.Acked,439444.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A.almFailToOpen.Alarm,439444.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Fault,439454.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A.almFailToClose.AlarmState,439454.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A.almFailToClose.GlobalReset,439454.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A.almFailToClose.FaultInAlarm,439454.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A.almFailToClose.ALRM,439454.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A.almFailToClose.ANUN,439454.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A.almFailToClose.AKED,439454.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A.almFailToClose.Resetable,439454.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A.almFailToClose.REST,439454.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A.almFailToClose.ACKN,439454.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A.almFailToClose.UACK,439454.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A.almFailToClose.MCmd_Enable,439454.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A.almFailToClose.MCmd_Disable,439454.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A.almFailToClose.OCmd_Shelve,439454.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A.almFailToClose.OCmd_Unshelve,439454.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A.almFailToClose.SCmd_Suppress,439454.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A.almFailToClose.SCmd_UnSuppress,439455.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A.almFailToClose.AEShelveTMRDN,439455.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A.almFailToClose.Bad,439455.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A.almFailToClose.Suppress,439456.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.UnSuppress,439456.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Shelve,439456.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.UnShelve,439456.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Enable,439456.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Disable,439456.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Ack,439456.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Reset,439456.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A.almFailToClose.Suppressed,439456.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A.almFailToClose.Shelved,439456.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A.almFailToClose.Disabled,439456.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A.almFailToClose.Acked,439456.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A.almFailToClose.Alarm,439456.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Fault,439466.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A.almActuatorFault.AlarmState,439466.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A.almActuatorFault.GlobalReset,439466.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A.almActuatorFault.FaultInAlarm,439466.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A.almActuatorFault.ALRM,439466.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A.almActuatorFault.ANUN,439466.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A.almActuatorFault.AKED,439466.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A.almActuatorFault.Resetable,439466.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A.almActuatorFault.REST,439466.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A.almActuatorFault.ACKN,439466.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A.almActuatorFault.UACK,439466.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A.almActuatorFault.MCmd_Enable,439466.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A.almActuatorFault.MCmd_Disable,439466.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A.almActuatorFault.OCmd_Shelve,439466.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A.almActuatorFault.OCmd_Unshelve,439466.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A.almActuatorFault.SCmd_Suppress,439466.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A.almActuatorFault.SCmd_UnSuppress,439467.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A.almActuatorFault.AEShelveTMRDN,439467.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A.almActuatorFault.Bad,439467.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A.almActuatorFault.Suppress,439468.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.UnSuppress,439468.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Shelve,439468.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.UnShelve,439468.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Enable,439468.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Disable,439468.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Ack,439468.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Reset,439468.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A.almActuatorFault.Suppressed,439468.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A.almActuatorFault.Shelved,439468.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A.almActuatorFault.Disabled,439468.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A.almActuatorFault.Acked,439468.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A.almActuatorFault.Alarm,439468.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Fault,439478.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8A.almPLCFault.AlarmState,439478.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8A.almPLCFault.GlobalReset,439478.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8A.almPLCFault.FaultInAlarm,439478.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8A.almPLCFault.ALRM,439478.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8A.almPLCFault.ANUN,439478.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8A.almPLCFault.AKED,439478.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8A.almPLCFault.Resetable,439478.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8A.almPLCFault.REST,439478.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8A.almPLCFault.ACKN,439478.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8A.almPLCFault.UACK,439478.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8A.almPLCFault.MCmd_Enable,439478.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8A.almPLCFault.MCmd_Disable,439478.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8A.almPLCFault.OCmd_Shelve,439478.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8A.almPLCFault.OCmd_Unshelve,439478.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8A.almPLCFault.SCmd_Suppress,439478.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8A.almPLCFault.SCmd_UnSuppress,439479.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8A.almPLCFault.AEShelveTMRDN,439479.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8A.almPLCFault.Bad,439479.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8A.almPLCFault.Suppress,439480.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.UnSuppress,439480.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Shelve,439480.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.UnShelve,439480.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Enable,439480.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Disable,439480.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Ack,439480.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Reset,439480.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8A.almPLCFault.Suppressed,439480.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8A.almPLCFault.Shelved,439480.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8A.almPLCFault.Disabled,439480.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8A.almPLCFault.Acked,439480.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8A.almPLCFault.Alarm,439480.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Fault,439522.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C.almFailToOpen.AlarmState,439522.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C.almFailToOpen.GlobalReset,439522.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C.almFailToOpen.FaultInAlarm,439522.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C.almFailToOpen.ALRM,439522.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C.almFailToOpen.ANUN,439522.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C.almFailToOpen.AKED,439522.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C.almFailToOpen.Resetable,439522.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C.almFailToOpen.REST,439522.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C.almFailToOpen.ACKN,439522.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C.almFailToOpen.UACK,439522.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C.almFailToOpen.MCmd_Enable,439522.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C.almFailToOpen.MCmd_Disable,439522.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C.almFailToOpen.OCmd_Shelve,439522.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C.almFailToOpen.OCmd_Unshelve,439522.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C.almFailToOpen.SCmd_Suppress,439522.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C.almFailToOpen.SCmd_UnSuppress,439523.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C.almFailToOpen.AEShelveTMRDN,439523.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C.almFailToOpen.Bad,439523.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C.almFailToOpen.Suppress,439524.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.UnSuppress,439524.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Shelve,439524.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.UnShelve,439524.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Enable,439524.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Disable,439524.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Ack,439524.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Reset,439524.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C.almFailToOpen.Suppressed,439524.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C.almFailToOpen.Shelved,439524.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C.almFailToOpen.Disabled,439524.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C.almFailToOpen.Acked,439524.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C.almFailToOpen.Alarm,439524.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Fault,439534.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C.almFailToClose.AlarmState,439534.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C.almFailToClose.GlobalReset,439534.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C.almFailToClose.FaultInAlarm,439534.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C.almFailToClose.ALRM,439534.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C.almFailToClose.ANUN,439534.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C.almFailToClose.AKED,439534.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C.almFailToClose.Resetable,439534.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C.almFailToClose.REST,439534.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C.almFailToClose.ACKN,439534.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C.almFailToClose.UACK,439534.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C.almFailToClose.MCmd_Enable,439534.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C.almFailToClose.MCmd_Disable,439534.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C.almFailToClose.OCmd_Shelve,439534.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C.almFailToClose.OCmd_Unshelve,439534.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C.almFailToClose.SCmd_Suppress,439534.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C.almFailToClose.SCmd_UnSuppress,439535.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C.almFailToClose.AEShelveTMRDN,439535.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C.almFailToClose.Bad,439535.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C.almFailToClose.Suppress,439536.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.UnSuppress,439536.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Shelve,439536.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.UnShelve,439536.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Enable,439536.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Disable,439536.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Ack,439536.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Reset,439536.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C.almFailToClose.Suppressed,439536.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C.almFailToClose.Shelved,439536.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C.almFailToClose.Disabled,439536.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C.almFailToClose.Acked,439536.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C.almFailToClose.Alarm,439536.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Fault,439546.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C.almActuatorFault.AlarmState,439546.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C.almActuatorFault.GlobalReset,439546.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C.almActuatorFault.FaultInAlarm,439546.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C.almActuatorFault.ALRM,439546.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C.almActuatorFault.ANUN,439546.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C.almActuatorFault.AKED,439546.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C.almActuatorFault.Resetable,439546.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C.almActuatorFault.REST,439546.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C.almActuatorFault.ACKN,439546.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C.almActuatorFault.UACK,439546.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C.almActuatorFault.MCmd_Enable,439546.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C.almActuatorFault.MCmd_Disable,439546.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C.almActuatorFault.OCmd_Shelve,439546.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C.almActuatorFault.OCmd_Unshelve,439546.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C.almActuatorFault.SCmd_Suppress,439546.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C.almActuatorFault.SCmd_UnSuppress,439547.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C.almActuatorFault.AEShelveTMRDN,439547.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C.almActuatorFault.Bad,439547.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C.almActuatorFault.Suppress,439548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.UnSuppress,439548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Shelve,439548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.UnShelve,439548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Enable,439548.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Disable,439548.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Ack,439548.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Reset,439548.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C.almActuatorFault.Suppressed,439548.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C.almActuatorFault.Shelved,439548.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C.almActuatorFault.Disabled,439548.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C.almActuatorFault.Acked,439548.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C.almActuatorFault.Alarm,439548.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Fault,439558.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8C.almPLCFault.AlarmState,439558.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8C.almPLCFault.GlobalReset,439558.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8C.almPLCFault.FaultInAlarm,439558.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8C.almPLCFault.ALRM,439558.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8C.almPLCFault.ANUN,439558.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8C.almPLCFault.AKED,439558.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8C.almPLCFault.Resetable,439558.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8C.almPLCFault.REST,439558.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8C.almPLCFault.ACKN,439558.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8C.almPLCFault.UACK,439558.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8C.almPLCFault.MCmd_Enable,439558.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8C.almPLCFault.MCmd_Disable,439558.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8C.almPLCFault.OCmd_Shelve,439558.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8C.almPLCFault.OCmd_Unshelve,439558.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8C.almPLCFault.SCmd_Suppress,439558.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8C.almPLCFault.SCmd_UnSuppress,439559.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8C.almPLCFault.AEShelveTMRDN,439559.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8C.almPLCFault.Bad,439559.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8C.almPLCFault.Suppress,439560.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.UnSuppress,439560.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Shelve,439560.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.UnShelve,439560.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Enable,439560.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Disable,439560.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Ack,439560.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Reset,439560.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8C.almPLCFault.Suppressed,439560.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8C.almPLCFault.Shelved,439560.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8C.almPLCFault.Disabled,439560.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8C.almPLCFault.Acked,439560.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8C.almPLCFault.Alarm,439560.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Fault,439602.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D.almFailToOpen.AlarmState,439602.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D.almFailToOpen.GlobalReset,439602.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D.almFailToOpen.FaultInAlarm,439602.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D.almFailToOpen.ALRM,439602.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D.almFailToOpen.ANUN,439602.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D.almFailToOpen.AKED,439602.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D.almFailToOpen.Resetable,439602.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D.almFailToOpen.REST,439602.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D.almFailToOpen.ACKN,439602.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D.almFailToOpen.UACK,439602.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D.almFailToOpen.MCmd_Enable,439602.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D.almFailToOpen.MCmd_Disable,439602.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D.almFailToOpen.OCmd_Shelve,439602.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D.almFailToOpen.OCmd_Unshelve,439602.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D.almFailToOpen.SCmd_Suppress,439602.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D.almFailToOpen.SCmd_UnSuppress,439603.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D.almFailToOpen.AEShelveTMRDN,439603.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D.almFailToOpen.Bad,439603.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D.almFailToOpen.Suppress,439604.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.UnSuppress,439604.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Shelve,439604.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.UnShelve,439604.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Enable,439604.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Disable,439604.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Ack,439604.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Reset,439604.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D.almFailToOpen.Suppressed,439604.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D.almFailToOpen.Shelved,439604.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D.almFailToOpen.Disabled,439604.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D.almFailToOpen.Acked,439604.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D.almFailToOpen.Alarm,439604.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Fault,439614.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D.almFailToClose.AlarmState,439614.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D.almFailToClose.GlobalReset,439614.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D.almFailToClose.FaultInAlarm,439614.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D.almFailToClose.ALRM,439614.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D.almFailToClose.ANUN,439614.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D.almFailToClose.AKED,439614.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D.almFailToClose.Resetable,439614.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D.almFailToClose.REST,439614.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D.almFailToClose.ACKN,439614.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D.almFailToClose.UACK,439614.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D.almFailToClose.MCmd_Enable,439614.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D.almFailToClose.MCmd_Disable,439614.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D.almFailToClose.OCmd_Shelve,439614.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D.almFailToClose.OCmd_Unshelve,439614.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D.almFailToClose.SCmd_Suppress,439614.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D.almFailToClose.SCmd_UnSuppress,439615.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D.almFailToClose.AEShelveTMRDN,439615.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D.almFailToClose.Bad,439615.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D.almFailToClose.Suppress,439616.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.UnSuppress,439616.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Shelve,439616.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.UnShelve,439616.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Enable,439616.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Disable,439616.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Ack,439616.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Reset,439616.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D.almFailToClose.Suppressed,439616.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D.almFailToClose.Shelved,439616.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D.almFailToClose.Disabled,439616.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D.almFailToClose.Acked,439616.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D.almFailToClose.Alarm,439616.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Fault,439626.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D.almActuatorFault.AlarmState,439626.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D.almActuatorFault.GlobalReset,439626.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D.almActuatorFault.FaultInAlarm,439626.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D.almActuatorFault.ALRM,439626.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D.almActuatorFault.ANUN,439626.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D.almActuatorFault.AKED,439626.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D.almActuatorFault.Resetable,439626.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D.almActuatorFault.REST,439626.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D.almActuatorFault.ACKN,439626.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D.almActuatorFault.UACK,439626.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D.almActuatorFault.MCmd_Enable,439626.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D.almActuatorFault.MCmd_Disable,439626.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D.almActuatorFault.OCmd_Shelve,439626.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D.almActuatorFault.OCmd_Unshelve,439626.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D.almActuatorFault.SCmd_Suppress,439626.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D.almActuatorFault.SCmd_UnSuppress,439627.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D.almActuatorFault.AEShelveTMRDN,439627.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D.almActuatorFault.Bad,439627.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D.almActuatorFault.Suppress,439628.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.UnSuppress,439628.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Shelve,439628.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.UnShelve,439628.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Enable,439628.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Disable,439628.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Ack,439628.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Reset,439628.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D.almActuatorFault.Suppressed,439628.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D.almActuatorFault.Shelved,439628.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D.almActuatorFault.Disabled,439628.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D.almActuatorFault.Acked,439628.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D.almActuatorFault.Alarm,439628.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Fault,439638.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_8D.almPLCFault.AlarmState,439638.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_8D.almPLCFault.GlobalReset,439638.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_8D.almPLCFault.FaultInAlarm,439638.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_8D.almPLCFault.ALRM,439638.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_8D.almPLCFault.ANUN,439638.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_8D.almPLCFault.AKED,439638.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_8D.almPLCFault.Resetable,439638.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_8D.almPLCFault.REST,439638.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_8D.almPLCFault.ACKN,439638.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_8D.almPLCFault.UACK,439638.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_8D.almPLCFault.MCmd_Enable,439638.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_8D.almPLCFault.MCmd_Disable,439638.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_8D.almPLCFault.OCmd_Shelve,439638.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_8D.almPLCFault.OCmd_Unshelve,439638.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_8D.almPLCFault.SCmd_Suppress,439638.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_8D.almPLCFault.SCmd_UnSuppress,439639.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_8D.almPLCFault.AEShelveTMRDN,439639.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_8D.almPLCFault.Bad,439639.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_8D.almPLCFault.Suppress,439640.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.UnSuppress,439640.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Shelve,439640.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.UnShelve,439640.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Enable,439640.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Disable,439640.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Ack,439640.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Reset,439640.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_8D.almPLCFault.Suppressed,439640.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_8D.almPLCFault.Shelved,439640.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_8D.almPLCFault.Disabled,439640.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_8D.almPLCFault.Acked,439640.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_8D.almPLCFault.Alarm,439640.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Fault,439682.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A.almFailToOpen.AlarmState,439682.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A.almFailToOpen.GlobalReset,439682.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A.almFailToOpen.FaultInAlarm,439682.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A.almFailToOpen.ALRM,439682.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A.almFailToOpen.ANUN,439682.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A.almFailToOpen.AKED,439682.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A.almFailToOpen.Resetable,439682.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A.almFailToOpen.REST,439682.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A.almFailToOpen.ACKN,439682.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A.almFailToOpen.UACK,439682.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A.almFailToOpen.MCmd_Enable,439682.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A.almFailToOpen.MCmd_Disable,439682.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A.almFailToOpen.OCmd_Shelve,439682.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A.almFailToOpen.OCmd_Unshelve,439682.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A.almFailToOpen.SCmd_Suppress,439682.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A.almFailToOpen.SCmd_UnSuppress,439683.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A.almFailToOpen.AEShelveTMRDN,439683.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A.almFailToOpen.Bad,439683.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A.almFailToOpen.Suppress,439684.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.UnSuppress,439684.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Shelve,439684.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.UnShelve,439684.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Enable,439684.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Disable,439684.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Ack,439684.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Reset,439684.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A.almFailToOpen.Suppressed,439684.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A.almFailToOpen.Shelved,439684.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A.almFailToOpen.Disabled,439684.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A.almFailToOpen.Acked,439684.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A.almFailToOpen.Alarm,439684.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Fault,439694.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A.almFailToClose.AlarmState,439694.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A.almFailToClose.GlobalReset,439694.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A.almFailToClose.FaultInAlarm,439694.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A.almFailToClose.ALRM,439694.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A.almFailToClose.ANUN,439694.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A.almFailToClose.AKED,439694.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A.almFailToClose.Resetable,439694.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A.almFailToClose.REST,439694.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A.almFailToClose.ACKN,439694.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A.almFailToClose.UACK,439694.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A.almFailToClose.MCmd_Enable,439694.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A.almFailToClose.MCmd_Disable,439694.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A.almFailToClose.OCmd_Shelve,439694.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A.almFailToClose.OCmd_Unshelve,439694.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A.almFailToClose.SCmd_Suppress,439694.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A.almFailToClose.SCmd_UnSuppress,439695.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A.almFailToClose.AEShelveTMRDN,439695.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A.almFailToClose.Bad,439695.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A.almFailToClose.Suppress,439696.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.UnSuppress,439696.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Shelve,439696.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.UnShelve,439696.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Enable,439696.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Disable,439696.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Ack,439696.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Reset,439696.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A.almFailToClose.Suppressed,439696.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A.almFailToClose.Shelved,439696.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A.almFailToClose.Disabled,439696.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A.almFailToClose.Acked,439696.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A.almFailToClose.Alarm,439696.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Fault,439706.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A.almActuatorFault.AlarmState,439706.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A.almActuatorFault.GlobalReset,439706.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A.almActuatorFault.FaultInAlarm,439706.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A.almActuatorFault.ALRM,439706.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A.almActuatorFault.ANUN,439706.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A.almActuatorFault.AKED,439706.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A.almActuatorFault.Resetable,439706.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A.almActuatorFault.REST,439706.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A.almActuatorFault.ACKN,439706.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A.almActuatorFault.UACK,439706.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A.almActuatorFault.MCmd_Enable,439706.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A.almActuatorFault.MCmd_Disable,439706.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A.almActuatorFault.OCmd_Shelve,439706.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A.almActuatorFault.OCmd_Unshelve,439706.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A.almActuatorFault.SCmd_Suppress,439706.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A.almActuatorFault.SCmd_UnSuppress,439707.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A.almActuatorFault.AEShelveTMRDN,439707.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A.almActuatorFault.Bad,439707.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A.almActuatorFault.Suppress,439708.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.UnSuppress,439708.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Shelve,439708.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.UnShelve,439708.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Enable,439708.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Disable,439708.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Ack,439708.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Reset,439708.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A.almActuatorFault.Suppressed,439708.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A.almActuatorFault.Shelved,439708.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A.almActuatorFault.Disabled,439708.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A.almActuatorFault.Acked,439708.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A.almActuatorFault.Alarm,439708.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Fault,439718.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9A.almPLCFault.AlarmState,439718.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9A.almPLCFault.GlobalReset,439718.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9A.almPLCFault.FaultInAlarm,439718.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9A.almPLCFault.ALRM,439718.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9A.almPLCFault.ANUN,439718.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9A.almPLCFault.AKED,439718.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9A.almPLCFault.Resetable,439718.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9A.almPLCFault.REST,439718.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9A.almPLCFault.ACKN,439718.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9A.almPLCFault.UACK,439718.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9A.almPLCFault.MCmd_Enable,439718.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9A.almPLCFault.MCmd_Disable,439718.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9A.almPLCFault.OCmd_Shelve,439718.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9A.almPLCFault.OCmd_Unshelve,439718.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9A.almPLCFault.SCmd_Suppress,439718.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9A.almPLCFault.SCmd_UnSuppress,439719.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9A.almPLCFault.AEShelveTMRDN,439719.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9A.almPLCFault.Bad,439719.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9A.almPLCFault.Suppress,439720.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.UnSuppress,439720.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Shelve,439720.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.UnShelve,439720.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Enable,439720.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Disable,439720.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Ack,439720.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Reset,439720.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9A.almPLCFault.Suppressed,439720.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9A.almPLCFault.Shelved,439720.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9A.almPLCFault.Disabled,439720.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9A.almPLCFault.Acked,439720.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9A.almPLCFault.Alarm,439720.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Fault,439762.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C.almFailToOpen.AlarmState,439762.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C.almFailToOpen.GlobalReset,439762.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C.almFailToOpen.FaultInAlarm,439762.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C.almFailToOpen.ALRM,439762.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C.almFailToOpen.ANUN,439762.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C.almFailToOpen.AKED,439762.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C.almFailToOpen.Resetable,439762.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C.almFailToOpen.REST,439762.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C.almFailToOpen.ACKN,439762.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C.almFailToOpen.UACK,439762.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C.almFailToOpen.MCmd_Enable,439762.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C.almFailToOpen.MCmd_Disable,439762.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C.almFailToOpen.OCmd_Shelve,439762.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C.almFailToOpen.OCmd_Unshelve,439762.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C.almFailToOpen.SCmd_Suppress,439762.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C.almFailToOpen.SCmd_UnSuppress,439763.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C.almFailToOpen.AEShelveTMRDN,439763.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C.almFailToOpen.Bad,439763.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C.almFailToOpen.Suppress,439764.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.UnSuppress,439764.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Shelve,439764.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.UnShelve,439764.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Enable,439764.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Disable,439764.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Ack,439764.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Reset,439764.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C.almFailToOpen.Suppressed,439764.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C.almFailToOpen.Shelved,439764.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C.almFailToOpen.Disabled,439764.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C.almFailToOpen.Acked,439764.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C.almFailToOpen.Alarm,439764.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Fault,439774.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C.almFailToClose.AlarmState,439774.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C.almFailToClose.GlobalReset,439774.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C.almFailToClose.FaultInAlarm,439774.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C.almFailToClose.ALRM,439774.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C.almFailToClose.ANUN,439774.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C.almFailToClose.AKED,439774.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C.almFailToClose.Resetable,439774.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C.almFailToClose.REST,439774.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C.almFailToClose.ACKN,439774.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C.almFailToClose.UACK,439774.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C.almFailToClose.MCmd_Enable,439774.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C.almFailToClose.MCmd_Disable,439774.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C.almFailToClose.OCmd_Shelve,439774.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C.almFailToClose.OCmd_Unshelve,439774.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C.almFailToClose.SCmd_Suppress,439774.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C.almFailToClose.SCmd_UnSuppress,439775.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C.almFailToClose.AEShelveTMRDN,439775.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C.almFailToClose.Bad,439775.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C.almFailToClose.Suppress,439776.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.UnSuppress,439776.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Shelve,439776.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.UnShelve,439776.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Enable,439776.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Disable,439776.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Ack,439776.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Reset,439776.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C.almFailToClose.Suppressed,439776.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C.almFailToClose.Shelved,439776.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C.almFailToClose.Disabled,439776.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C.almFailToClose.Acked,439776.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C.almFailToClose.Alarm,439776.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Fault,439786.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C.almActuatorFault.AlarmState,439786.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C.almActuatorFault.GlobalReset,439786.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C.almActuatorFault.FaultInAlarm,439786.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C.almActuatorFault.ALRM,439786.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C.almActuatorFault.ANUN,439786.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C.almActuatorFault.AKED,439786.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C.almActuatorFault.Resetable,439786.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C.almActuatorFault.REST,439786.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C.almActuatorFault.ACKN,439786.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C.almActuatorFault.UACK,439786.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C.almActuatorFault.MCmd_Enable,439786.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C.almActuatorFault.MCmd_Disable,439786.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C.almActuatorFault.OCmd_Shelve,439786.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C.almActuatorFault.OCmd_Unshelve,439786.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C.almActuatorFault.SCmd_Suppress,439786.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C.almActuatorFault.SCmd_UnSuppress,439787.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C.almActuatorFault.AEShelveTMRDN,439787.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C.almActuatorFault.Bad,439787.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C.almActuatorFault.Suppress,439788.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.UnSuppress,439788.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Shelve,439788.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.UnShelve,439788.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Enable,439788.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Disable,439788.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Ack,439788.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Reset,439788.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C.almActuatorFault.Suppressed,439788.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C.almActuatorFault.Shelved,439788.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C.almActuatorFault.Disabled,439788.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C.almActuatorFault.Acked,439788.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C.almActuatorFault.Alarm,439788.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Fault,439798.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0103_9C.almPLCFault.AlarmState,439798.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0103_9C.almPLCFault.GlobalReset,439798.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0103_9C.almPLCFault.FaultInAlarm,439798.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0103_9C.almPLCFault.ALRM,439798.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0103_9C.almPLCFault.ANUN,439798.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0103_9C.almPLCFault.AKED,439798.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0103_9C.almPLCFault.Resetable,439798.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0103_9C.almPLCFault.REST,439798.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0103_9C.almPLCFault.ACKN,439798.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0103_9C.almPLCFault.UACK,439798.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0103_9C.almPLCFault.MCmd_Enable,439798.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0103_9C.almPLCFault.MCmd_Disable,439798.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0103_9C.almPLCFault.OCmd_Shelve,439798.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0103_9C.almPLCFault.OCmd_Unshelve,439798.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0103_9C.almPLCFault.SCmd_Suppress,439798.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0103_9C.almPLCFault.SCmd_UnSuppress,439799.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0103_9C.almPLCFault.AEShelveTMRDN,439799.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0103_9C.almPLCFault.Bad,439799.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0103_9C.almPLCFault.Suppress,439800.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.UnSuppress,439800.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Shelve,439800.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.UnShelve,439800.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Enable,439800.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Disable,439800.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Ack,439800.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Reset,439800.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0103_9C.almPLCFault.Suppressed,439800.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0103_9C.almPLCFault.Shelved,439800.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0103_9C.almPLCFault.Disabled,439800.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0103_9C.almPLCFault.Acked,439800.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0103_9C.almPLCFault.Alarm,439800.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Fault,439842.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A.almFailToOpen.AlarmState,439842.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A.almFailToOpen.GlobalReset,439842.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A.almFailToOpen.FaultInAlarm,439842.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A.almFailToOpen.ALRM,439842.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A.almFailToOpen.ANUN,439842.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A.almFailToOpen.AKED,439842.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A.almFailToOpen.Resetable,439842.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A.almFailToOpen.REST,439842.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A.almFailToOpen.ACKN,439842.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A.almFailToOpen.UACK,439842.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A.almFailToOpen.MCmd_Enable,439842.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A.almFailToOpen.MCmd_Disable,439842.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A.almFailToOpen.OCmd_Shelve,439842.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A.almFailToOpen.OCmd_Unshelve,439842.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A.almFailToOpen.SCmd_Suppress,439842.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A.almFailToOpen.SCmd_UnSuppress,439843.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A.almFailToOpen.AEShelveTMRDN,439843.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A.almFailToOpen.Bad,439843.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A.almFailToOpen.Suppress,439844.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.UnSuppress,439844.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Shelve,439844.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.UnShelve,439844.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Enable,439844.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Disable,439844.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Ack,439844.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Reset,439844.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A.almFailToOpen.Suppressed,439844.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A.almFailToOpen.Shelved,439844.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A.almFailToOpen.Disabled,439844.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A.almFailToOpen.Acked,439844.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A.almFailToOpen.Alarm,439844.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Fault,439854.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A.almFailToClose.AlarmState,439854.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A.almFailToClose.GlobalReset,439854.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A.almFailToClose.FaultInAlarm,439854.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A.almFailToClose.ALRM,439854.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A.almFailToClose.ANUN,439854.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A.almFailToClose.AKED,439854.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A.almFailToClose.Resetable,439854.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A.almFailToClose.REST,439854.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A.almFailToClose.ACKN,439854.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A.almFailToClose.UACK,439854.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A.almFailToClose.MCmd_Enable,439854.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A.almFailToClose.MCmd_Disable,439854.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A.almFailToClose.OCmd_Shelve,439854.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A.almFailToClose.OCmd_Unshelve,439854.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A.almFailToClose.SCmd_Suppress,439854.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A.almFailToClose.SCmd_UnSuppress,439855.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A.almFailToClose.AEShelveTMRDN,439855.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A.almFailToClose.Bad,439855.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A.almFailToClose.Suppress,439856.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.UnSuppress,439856.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Shelve,439856.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.UnShelve,439856.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Enable,439856.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Disable,439856.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Ack,439856.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Reset,439856.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A.almFailToClose.Suppressed,439856.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A.almFailToClose.Shelved,439856.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A.almFailToClose.Disabled,439856.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A.almFailToClose.Acked,439856.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A.almFailToClose.Alarm,439856.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Fault,439866.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A.almActuatorFault.AlarmState,439866.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A.almActuatorFault.GlobalReset,439866.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A.almActuatorFault.FaultInAlarm,439866.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A.almActuatorFault.ALRM,439866.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A.almActuatorFault.ANUN,439866.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A.almActuatorFault.AKED,439866.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A.almActuatorFault.Resetable,439866.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A.almActuatorFault.REST,439866.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A.almActuatorFault.ACKN,439866.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A.almActuatorFault.UACK,439866.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A.almActuatorFault.MCmd_Enable,439866.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A.almActuatorFault.MCmd_Disable,439866.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A.almActuatorFault.OCmd_Shelve,439866.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A.almActuatorFault.OCmd_Unshelve,439866.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A.almActuatorFault.SCmd_Suppress,439866.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A.almActuatorFault.SCmd_UnSuppress,439867.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A.almActuatorFault.AEShelveTMRDN,439867.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A.almActuatorFault.Bad,439867.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A.almActuatorFault.Suppress,439868.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.UnSuppress,439868.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Shelve,439868.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.UnShelve,439868.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Enable,439868.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Disable,439868.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Ack,439868.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Reset,439868.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A.almActuatorFault.Suppressed,439868.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A.almActuatorFault.Shelved,439868.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A.almActuatorFault.Disabled,439868.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A.almActuatorFault.Acked,439868.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A.almActuatorFault.Alarm,439868.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Fault,439878.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2A.almPLCFault.AlarmState,439878.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2A.almPLCFault.GlobalReset,439878.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2A.almPLCFault.FaultInAlarm,439878.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2A.almPLCFault.ALRM,439878.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2A.almPLCFault.ANUN,439878.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2A.almPLCFault.AKED,439878.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2A.almPLCFault.Resetable,439878.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2A.almPLCFault.REST,439878.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2A.almPLCFault.ACKN,439878.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2A.almPLCFault.UACK,439878.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2A.almPLCFault.MCmd_Enable,439878.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2A.almPLCFault.MCmd_Disable,439878.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2A.almPLCFault.OCmd_Shelve,439878.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2A.almPLCFault.OCmd_Unshelve,439878.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2A.almPLCFault.SCmd_Suppress,439878.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2A.almPLCFault.SCmd_UnSuppress,439879.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2A.almPLCFault.AEShelveTMRDN,439879.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2A.almPLCFault.Bad,439879.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2A.almPLCFault.Suppress,439880.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.UnSuppress,439880.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Shelve,439880.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.UnShelve,439880.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Enable,439880.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Disable,439880.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Ack,439880.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Reset,439880.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2A.almPLCFault.Suppressed,439880.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2A.almPLCFault.Shelved,439880.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2A.almPLCFault.Disabled,439880.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2A.almPLCFault.Acked,439880.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2A.almPLCFault.Alarm,439880.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Fault,439922.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B.almFailToOpen.AlarmState,439922.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B.almFailToOpen.GlobalReset,439922.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B.almFailToOpen.FaultInAlarm,439922.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B.almFailToOpen.ALRM,439922.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B.almFailToOpen.ANUN,439922.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B.almFailToOpen.AKED,439922.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B.almFailToOpen.Resetable,439922.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B.almFailToOpen.REST,439922.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B.almFailToOpen.ACKN,439922.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B.almFailToOpen.UACK,439922.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B.almFailToOpen.MCmd_Enable,439922.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B.almFailToOpen.MCmd_Disable,439922.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B.almFailToOpen.OCmd_Shelve,439922.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B.almFailToOpen.OCmd_Unshelve,439922.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B.almFailToOpen.SCmd_Suppress,439922.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B.almFailToOpen.SCmd_UnSuppress,439923.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B.almFailToOpen.AEShelveTMRDN,439923.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B.almFailToOpen.Bad,439923.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B.almFailToOpen.Suppress,439924.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.UnSuppress,439924.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Shelve,439924.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.UnShelve,439924.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Enable,439924.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Disable,439924.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Ack,439924.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Reset,439924.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B.almFailToOpen.Suppressed,439924.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B.almFailToOpen.Shelved,439924.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B.almFailToOpen.Disabled,439924.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B.almFailToOpen.Acked,439924.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B.almFailToOpen.Alarm,439924.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Fault,439934.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B.almFailToClose.AlarmState,439934.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B.almFailToClose.GlobalReset,439934.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B.almFailToClose.FaultInAlarm,439934.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B.almFailToClose.ALRM,439934.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B.almFailToClose.ANUN,439934.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B.almFailToClose.AKED,439934.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B.almFailToClose.Resetable,439934.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B.almFailToClose.REST,439934.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B.almFailToClose.ACKN,439934.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B.almFailToClose.UACK,439934.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B.almFailToClose.MCmd_Enable,439934.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B.almFailToClose.MCmd_Disable,439934.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B.almFailToClose.OCmd_Shelve,439934.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B.almFailToClose.OCmd_Unshelve,439934.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B.almFailToClose.SCmd_Suppress,439934.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B.almFailToClose.SCmd_UnSuppress,439935.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B.almFailToClose.AEShelveTMRDN,439935.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B.almFailToClose.Bad,439935.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B.almFailToClose.Suppress,439936.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.UnSuppress,439936.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Shelve,439936.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.UnShelve,439936.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Enable,439936.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Disable,439936.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Ack,439936.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Reset,439936.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B.almFailToClose.Suppressed,439936.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B.almFailToClose.Shelved,439936.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B.almFailToClose.Disabled,439936.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B.almFailToClose.Acked,439936.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B.almFailToClose.Alarm,439936.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Fault,439946.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B.almActuatorFault.AlarmState,439946.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B.almActuatorFault.GlobalReset,439946.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B.almActuatorFault.FaultInAlarm,439946.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B.almActuatorFault.ALRM,439946.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B.almActuatorFault.ANUN,439946.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B.almActuatorFault.AKED,439946.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B.almActuatorFault.Resetable,439946.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B.almActuatorFault.REST,439946.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B.almActuatorFault.ACKN,439946.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B.almActuatorFault.UACK,439946.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B.almActuatorFault.MCmd_Enable,439946.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B.almActuatorFault.MCmd_Disable,439946.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B.almActuatorFault.OCmd_Shelve,439946.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B.almActuatorFault.OCmd_Unshelve,439946.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B.almActuatorFault.SCmd_Suppress,439946.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B.almActuatorFault.SCmd_UnSuppress,439947.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B.almActuatorFault.AEShelveTMRDN,439947.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B.almActuatorFault.Bad,439947.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B.almActuatorFault.Suppress,439948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.UnSuppress,439948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Shelve,439948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.UnShelve,439948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Enable,439948.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Disable,439948.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Ack,439948.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Reset,439948.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B.almActuatorFault.Suppressed,439948.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B.almActuatorFault.Shelved,439948.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B.almActuatorFault.Disabled,439948.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B.almActuatorFault.Acked,439948.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B.almActuatorFault.Alarm,439948.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Fault,439958.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2B.almPLCFault.AlarmState,439958.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2B.almPLCFault.GlobalReset,439958.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2B.almPLCFault.FaultInAlarm,439958.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2B.almPLCFault.ALRM,439958.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2B.almPLCFault.ANUN,439958.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2B.almPLCFault.AKED,439958.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2B.almPLCFault.Resetable,439958.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2B.almPLCFault.REST,439958.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2B.almPLCFault.ACKN,439958.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2B.almPLCFault.UACK,439958.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2B.almPLCFault.MCmd_Enable,439958.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2B.almPLCFault.MCmd_Disable,439958.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2B.almPLCFault.OCmd_Shelve,439958.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2B.almPLCFault.OCmd_Unshelve,439958.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2B.almPLCFault.SCmd_Suppress,439958.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2B.almPLCFault.SCmd_UnSuppress,439959.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2B.almPLCFault.AEShelveTMRDN,439959.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2B.almPLCFault.Bad,439959.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2B.almPLCFault.Suppress,439960.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.UnSuppress,439960.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Shelve,439960.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.UnShelve,439960.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Enable,439960.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Disable,439960.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Ack,439960.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Reset,439960.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2B.almPLCFault.Suppressed,439960.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2B.almPLCFault.Shelved,439960.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2B.almPLCFault.Disabled,439960.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2B.almPLCFault.Acked,439960.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2B.almPLCFault.Alarm,439960.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Fault,440002.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C.almFailToOpen.AlarmState,440002.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C.almFailToOpen.GlobalReset,440002.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C.almFailToOpen.FaultInAlarm,440002.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C.almFailToOpen.ALRM,440002.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C.almFailToOpen.ANUN,440002.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C.almFailToOpen.AKED,440002.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C.almFailToOpen.Resetable,440002.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C.almFailToOpen.REST,440002.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C.almFailToOpen.ACKN,440002.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C.almFailToOpen.UACK,440002.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C.almFailToOpen.MCmd_Enable,440002.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C.almFailToOpen.MCmd_Disable,440002.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C.almFailToOpen.OCmd_Shelve,440002.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C.almFailToOpen.OCmd_Unshelve,440002.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C.almFailToOpen.SCmd_Suppress,440002.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C.almFailToOpen.SCmd_UnSuppress,440003.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C.almFailToOpen.AEShelveTMRDN,440003.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C.almFailToOpen.Bad,440003.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C.almFailToOpen.Suppress,440004.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.UnSuppress,440004.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Shelve,440004.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.UnShelve,440004.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Enable,440004.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Disable,440004.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Ack,440004.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Reset,440004.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C.almFailToOpen.Suppressed,440004.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C.almFailToOpen.Shelved,440004.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C.almFailToOpen.Disabled,440004.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C.almFailToOpen.Acked,440004.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C.almFailToOpen.Alarm,440004.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Fault,440014.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C.almFailToClose.AlarmState,440014.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C.almFailToClose.GlobalReset,440014.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C.almFailToClose.FaultInAlarm,440014.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C.almFailToClose.ALRM,440014.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C.almFailToClose.ANUN,440014.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C.almFailToClose.AKED,440014.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C.almFailToClose.Resetable,440014.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C.almFailToClose.REST,440014.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C.almFailToClose.ACKN,440014.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C.almFailToClose.UACK,440014.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C.almFailToClose.MCmd_Enable,440014.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C.almFailToClose.MCmd_Disable,440014.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C.almFailToClose.OCmd_Shelve,440014.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C.almFailToClose.OCmd_Unshelve,440014.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C.almFailToClose.SCmd_Suppress,440014.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C.almFailToClose.SCmd_UnSuppress,440015.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C.almFailToClose.AEShelveTMRDN,440015.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C.almFailToClose.Bad,440015.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C.almFailToClose.Suppress,440016.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.UnSuppress,440016.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Shelve,440016.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.UnShelve,440016.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Enable,440016.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Disable,440016.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Ack,440016.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Reset,440016.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C.almFailToClose.Suppressed,440016.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C.almFailToClose.Shelved,440016.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C.almFailToClose.Disabled,440016.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C.almFailToClose.Acked,440016.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C.almFailToClose.Alarm,440016.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Fault,440026.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C.almActuatorFault.AlarmState,440026.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C.almActuatorFault.GlobalReset,440026.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C.almActuatorFault.FaultInAlarm,440026.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C.almActuatorFault.ALRM,440026.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C.almActuatorFault.ANUN,440026.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C.almActuatorFault.AKED,440026.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C.almActuatorFault.Resetable,440026.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C.almActuatorFault.REST,440026.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C.almActuatorFault.ACKN,440026.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C.almActuatorFault.UACK,440026.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C.almActuatorFault.MCmd_Enable,440026.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C.almActuatorFault.MCmd_Disable,440026.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C.almActuatorFault.OCmd_Shelve,440026.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C.almActuatorFault.OCmd_Unshelve,440026.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C.almActuatorFault.SCmd_Suppress,440026.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C.almActuatorFault.SCmd_UnSuppress,440027.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C.almActuatorFault.AEShelveTMRDN,440027.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C.almActuatorFault.Bad,440027.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C.almActuatorFault.Suppress,440028.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.UnSuppress,440028.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Shelve,440028.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.UnShelve,440028.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Enable,440028.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Disable,440028.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Ack,440028.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Reset,440028.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C.almActuatorFault.Suppressed,440028.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C.almActuatorFault.Shelved,440028.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C.almActuatorFault.Disabled,440028.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C.almActuatorFault.Acked,440028.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C.almActuatorFault.Alarm,440028.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Fault,440038.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2C.almPLCFault.AlarmState,440038.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2C.almPLCFault.GlobalReset,440038.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2C.almPLCFault.FaultInAlarm,440038.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2C.almPLCFault.ALRM,440038.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2C.almPLCFault.ANUN,440038.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2C.almPLCFault.AKED,440038.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2C.almPLCFault.Resetable,440038.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2C.almPLCFault.REST,440038.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2C.almPLCFault.ACKN,440038.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2C.almPLCFault.UACK,440038.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2C.almPLCFault.MCmd_Enable,440038.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2C.almPLCFault.MCmd_Disable,440038.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2C.almPLCFault.OCmd_Shelve,440038.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2C.almPLCFault.OCmd_Unshelve,440038.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2C.almPLCFault.SCmd_Suppress,440038.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2C.almPLCFault.SCmd_UnSuppress,440039.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2C.almPLCFault.AEShelveTMRDN,440039.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2C.almPLCFault.Bad,440039.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2C.almPLCFault.Suppress,440040.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.UnSuppress,440040.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Shelve,440040.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.UnShelve,440040.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Enable,440040.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Disable,440040.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Ack,440040.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Reset,440040.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2C.almPLCFault.Suppressed,440040.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2C.almPLCFault.Shelved,440040.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2C.almPLCFault.Disabled,440040.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2C.almPLCFault.Acked,440040.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2C.almPLCFault.Alarm,440040.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Fault,440082.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D.almFailToOpen.AlarmState,440082.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D.almFailToOpen.GlobalReset,440082.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D.almFailToOpen.FaultInAlarm,440082.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D.almFailToOpen.ALRM,440082.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D.almFailToOpen.ANUN,440082.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D.almFailToOpen.AKED,440082.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D.almFailToOpen.Resetable,440082.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D.almFailToOpen.REST,440082.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D.almFailToOpen.ACKN,440082.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D.almFailToOpen.UACK,440082.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D.almFailToOpen.MCmd_Enable,440082.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D.almFailToOpen.MCmd_Disable,440082.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D.almFailToOpen.OCmd_Shelve,440082.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D.almFailToOpen.OCmd_Unshelve,440082.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D.almFailToOpen.SCmd_Suppress,440082.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D.almFailToOpen.SCmd_UnSuppress,440083.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D.almFailToOpen.AEShelveTMRDN,440083.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D.almFailToOpen.Bad,440083.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D.almFailToOpen.Suppress,440084.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.UnSuppress,440084.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Shelve,440084.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.UnShelve,440084.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Enable,440084.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Disable,440084.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Ack,440084.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Reset,440084.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D.almFailToOpen.Suppressed,440084.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D.almFailToOpen.Shelved,440084.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D.almFailToOpen.Disabled,440084.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D.almFailToOpen.Acked,440084.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D.almFailToOpen.Alarm,440084.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Fault,440094.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D.almFailToClose.AlarmState,440094.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D.almFailToClose.GlobalReset,440094.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D.almFailToClose.FaultInAlarm,440094.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D.almFailToClose.ALRM,440094.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D.almFailToClose.ANUN,440094.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D.almFailToClose.AKED,440094.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D.almFailToClose.Resetable,440094.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D.almFailToClose.REST,440094.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D.almFailToClose.ACKN,440094.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D.almFailToClose.UACK,440094.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D.almFailToClose.MCmd_Enable,440094.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D.almFailToClose.MCmd_Disable,440094.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D.almFailToClose.OCmd_Shelve,440094.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D.almFailToClose.OCmd_Unshelve,440094.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D.almFailToClose.SCmd_Suppress,440094.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D.almFailToClose.SCmd_UnSuppress,440095.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D.almFailToClose.AEShelveTMRDN,440095.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D.almFailToClose.Bad,440095.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D.almFailToClose.Suppress,440096.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.UnSuppress,440096.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Shelve,440096.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.UnShelve,440096.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Enable,440096.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Disable,440096.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Ack,440096.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Reset,440096.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D.almFailToClose.Suppressed,440096.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D.almFailToClose.Shelved,440096.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D.almFailToClose.Disabled,440096.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D.almFailToClose.Acked,440096.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D.almFailToClose.Alarm,440096.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Fault,440106.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D.almActuatorFault.AlarmState,440106.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D.almActuatorFault.GlobalReset,440106.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D.almActuatorFault.FaultInAlarm,440106.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D.almActuatorFault.ALRM,440106.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D.almActuatorFault.ANUN,440106.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D.almActuatorFault.AKED,440106.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D.almActuatorFault.Resetable,440106.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D.almActuatorFault.REST,440106.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D.almActuatorFault.ACKN,440106.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D.almActuatorFault.UACK,440106.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D.almActuatorFault.MCmd_Enable,440106.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D.almActuatorFault.MCmd_Disable,440106.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D.almActuatorFault.OCmd_Shelve,440106.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D.almActuatorFault.OCmd_Unshelve,440106.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D.almActuatorFault.SCmd_Suppress,440106.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D.almActuatorFault.SCmd_UnSuppress,440107.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D.almActuatorFault.AEShelveTMRDN,440107.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D.almActuatorFault.Bad,440107.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D.almActuatorFault.Suppress,440108.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.UnSuppress,440108.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Shelve,440108.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.UnShelve,440108.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Enable,440108.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Disable,440108.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Ack,440108.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Reset,440108.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D.almActuatorFault.Suppressed,440108.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D.almActuatorFault.Shelved,440108.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D.almActuatorFault.Disabled,440108.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D.almActuatorFault.Acked,440108.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D.almActuatorFault.Alarm,440108.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Fault,440118.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FV_0113_2D.almPLCFault.AlarmState,440118.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FV_0113_2D.almPLCFault.GlobalReset,440118.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FV_0113_2D.almPLCFault.FaultInAlarm,440118.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FV_0113_2D.almPLCFault.ALRM,440118.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FV_0113_2D.almPLCFault.ANUN,440118.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FV_0113_2D.almPLCFault.AKED,440118.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FV_0113_2D.almPLCFault.Resetable,440118.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FV_0113_2D.almPLCFault.REST,440118.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FV_0113_2D.almPLCFault.ACKN,440118.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FV_0113_2D.almPLCFault.UACK,440118.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FV_0113_2D.almPLCFault.MCmd_Enable,440118.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FV_0113_2D.almPLCFault.MCmd_Disable,440118.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FV_0113_2D.almPLCFault.OCmd_Shelve,440118.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FV_0113_2D.almPLCFault.OCmd_Unshelve,440118.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FV_0113_2D.almPLCFault.SCmd_Suppress,440118.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FV_0113_2D.almPLCFault.SCmd_UnSuppress,440119.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FV_0113_2D.almPLCFault.AEShelveTMRDN,440119.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FV_0113_2D.almPLCFault.Bad,440119.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FV_0113_2D.almPLCFault.Suppress,440120.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.UnSuppress,440120.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Shelve,440120.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.UnShelve,440120.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Enable,440120.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Disable,440120.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Ack,440120.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Reset,440120.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FV_0113_2D.almPLCFault.Suppressed,440120.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FV_0113_2D.almPLCFault.Shelved,440120.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FV_0113_2D.almPLCFault.Disabled,440120.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FV_0113_2D.almPLCFault.Acked,440120.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FV_0113_2D.almPLCFault.Alarm,440120.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Fault,440160.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almBrokenLoop.AlarmState,440160.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almBrokenLoop.GlobalReset,440160.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almBrokenLoop.FaultInAlarm,440160.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almBrokenLoop.ALRM,440160.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almBrokenLoop.ANUN,440160.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almBrokenLoop.AKED,440160.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almBrokenLoop.Resetable,440160.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almBrokenLoop.REST,440160.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almBrokenLoop.ACKN,440160.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almBrokenLoop.UACK,440160.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almBrokenLoop.MCmd_Enable,440160.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almBrokenLoop.MCmd_Disable,440160.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almBrokenLoop.OCmd_Shelve,440160.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almBrokenLoop.OCmd_Unshelve,440160.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almBrokenLoop.SCmd_Suppress,440160.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almBrokenLoop.SCmd_UnSuppress,440161.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almBrokenLoop.AEShelveTMRDN,440161.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almBrokenLoop.Bad,440161.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almBrokenLoop.Suppress,440162.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.UnSuppress,440162.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Shelve,440162.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.UnShelve,440162.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Enable,440162.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Disable,440162.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Ack,440162.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Reset,440162.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Suppressed,440162.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Shelved,440162.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Disabled,440162.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Acked,440162.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almBrokenLoop.Alarm,440162.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Fault,440172.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almUnderRange.AlarmState,440172.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almUnderRange.GlobalReset,440172.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almUnderRange.FaultInAlarm,440172.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almUnderRange.ALRM,440172.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almUnderRange.ANUN,440172.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almUnderRange.AKED,440172.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almUnderRange.Resetable,440172.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almUnderRange.REST,440172.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almUnderRange.ACKN,440172.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almUnderRange.UACK,440172.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almUnderRange.MCmd_Enable,440172.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almUnderRange.MCmd_Disable,440172.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almUnderRange.OCmd_Shelve,440172.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almUnderRange.OCmd_Unshelve,440172.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almUnderRange.SCmd_Suppress,440172.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almUnderRange.SCmd_UnSuppress,440173.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almUnderRange.AEShelveTMRDN,440173.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almUnderRange.Bad,440173.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almUnderRange.Suppress,440174.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.UnSuppress,440174.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Shelve,440174.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.UnShelve,440174.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Enable,440174.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Disable,440174.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Ack,440174.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Reset,440174.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almUnderRange.Suppressed,440174.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almUnderRange.Shelved,440174.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almUnderRange.Disabled,440174.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almUnderRange.Acked,440174.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almUnderRange.Alarm,440174.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Fault,440184.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almOverRange.AlarmState,440184.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almOverRange.GlobalReset,440184.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almOverRange.FaultInAlarm,440184.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almOverRange.ALRM,440184.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almOverRange.ANUN,440184.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almOverRange.AKED,440184.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almOverRange.Resetable,440184.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almOverRange.REST,440184.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almOverRange.ACKN,440184.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almOverRange.UACK,440184.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almOverRange.MCmd_Enable,440184.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almOverRange.MCmd_Disable,440184.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almOverRange.OCmd_Shelve,440184.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almOverRange.OCmd_Unshelve,440184.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almOverRange.SCmd_Suppress,440184.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almOverRange.SCmd_UnSuppress,440185.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almOverRange.AEShelveTMRDN,440185.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almOverRange.Bad,440185.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almOverRange.Suppress,440186.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.UnSuppress,440186.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Shelve,440186.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.UnShelve,440186.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Enable,440186.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Disable,440186.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Ack,440186.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Reset,440186.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almOverRange.Suppressed,440186.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almOverRange.Shelved,440186.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almOverRange.Disabled,440186.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almOverRange.Acked,440186.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almOverRange.Alarm,440186.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Fault,440196.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almPositionFailure.AlarmState,440196.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almPositionFailure.GlobalReset,440196.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almPositionFailure.FaultInAlarm,440196.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almPositionFailure.ALRM,440196.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almPositionFailure.ANUN,440196.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almPositionFailure.AKED,440196.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almPositionFailure.Resetable,440196.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almPositionFailure.REST,440196.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almPositionFailure.ACKN,440196.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almPositionFailure.UACK,440196.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almPositionFailure.MCmd_Enable,440196.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almPositionFailure.MCmd_Disable,440196.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almPositionFailure.OCmd_Shelve,440196.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almPositionFailure.OCmd_Unshelve,440196.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almPositionFailure.SCmd_Suppress,440196.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almPositionFailure.SCmd_UnSuppress,440197.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almPositionFailure.AEShelveTMRDN,440197.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almPositionFailure.Bad,440197.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almPositionFailure.Suppress,440198.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.UnSuppress,440198.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Shelve,440198.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.UnShelve,440198.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Enable,440198.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Disable,440198.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Ack,440198.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Reset,440198.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almPositionFailure.Suppressed,440198.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almPositionFailure.Shelved,440198.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almPositionFailure.Disabled,440198.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almPositionFailure.Acked,440198.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almPositionFailure.Alarm,440198.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Fault,440208.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almPLCFault.AlarmState,440208.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almPLCFault.GlobalReset,440208.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almPLCFault.FaultInAlarm,440208.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almPLCFault.ALRM,440208.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almPLCFault.ANUN,440208.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almPLCFault.AKED,440208.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almPLCFault.Resetable,440208.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almPLCFault.REST,440208.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almPLCFault.ACKN,440208.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almPLCFault.UACK,440208.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almPLCFault.MCmd_Enable,440208.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almPLCFault.MCmd_Disable,440208.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almPLCFault.OCmd_Shelve,440208.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almPLCFault.OCmd_Unshelve,440208.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almPLCFault.SCmd_Suppress,440208.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almPLCFault.SCmd_UnSuppress,440209.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almPLCFault.AEShelveTMRDN,440209.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almPLCFault.Bad,440209.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almPLCFault.Suppress,440210.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.UnSuppress,440210.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Shelve,440210.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.UnShelve,440210.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Enable,440210.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Disable,440210.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Ack,440210.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Reset,440210.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almPLCFault.Suppressed,440210.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almPLCFault.Shelved,440210.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almPLCFault.Disabled,440210.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almPLCFault.Acked,440210.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almPLCFault.Alarm,440210.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Fault,440220.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2A.almValveFailure.AlarmState,440220.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2A.almValveFailure.GlobalReset,440220.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2A.almValveFailure.FaultInAlarm,440220.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2A.almValveFailure.ALRM,440220.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2A.almValveFailure.ANUN,440220.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2A.almValveFailure.AKED,440220.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2A.almValveFailure.Resetable,440220.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2A.almValveFailure.REST,440220.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2A.almValveFailure.ACKN,440220.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2A.almValveFailure.UACK,440220.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2A.almValveFailure.MCmd_Enable,440220.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2A.almValveFailure.MCmd_Disable,440220.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2A.almValveFailure.OCmd_Shelve,440220.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2A.almValveFailure.OCmd_Unshelve,440220.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2A.almValveFailure.SCmd_Suppress,440220.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2A.almValveFailure.SCmd_UnSuppress,440221.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2A.almValveFailure.AEShelveTMRDN,440221.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2A.almValveFailure.Bad,440221.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2A.almValveFailure.Suppress,440222.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.UnSuppress,440222.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Shelve,440222.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.UnShelve,440222.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Enable,440222.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Disable,440222.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Ack,440222.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Reset,440222.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2A.almValveFailure.Suppressed,440222.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2A.almValveFailure.Shelved,440222.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2A.almValveFailure.Disabled,440222.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2A.almValveFailure.Acked,440222.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2A.almValveFailure.Alarm,440222.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Fault,440270.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almBrokenLoop.AlarmState,440270.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almBrokenLoop.GlobalReset,440270.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almBrokenLoop.FaultInAlarm,440270.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almBrokenLoop.ALRM,440270.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almBrokenLoop.ANUN,440270.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almBrokenLoop.AKED,440270.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almBrokenLoop.Resetable,440270.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almBrokenLoop.REST,440270.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almBrokenLoop.ACKN,440270.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almBrokenLoop.UACK,440270.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almBrokenLoop.MCmd_Enable,440270.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almBrokenLoop.MCmd_Disable,440270.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almBrokenLoop.OCmd_Shelve,440270.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almBrokenLoop.OCmd_Unshelve,440270.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almBrokenLoop.SCmd_Suppress,440270.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almBrokenLoop.SCmd_UnSuppress,440271.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almBrokenLoop.AEShelveTMRDN,440271.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almBrokenLoop.Bad,440271.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almBrokenLoop.Suppress,440272.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.UnSuppress,440272.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Shelve,440272.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.UnShelve,440272.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Enable,440272.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Disable,440272.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Ack,440272.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Reset,440272.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Suppressed,440272.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Shelved,440272.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Disabled,440272.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Acked,440272.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almBrokenLoop.Alarm,440272.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Fault,440282.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almUnderRange.AlarmState,440282.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almUnderRange.GlobalReset,440282.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almUnderRange.FaultInAlarm,440282.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almUnderRange.ALRM,440282.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almUnderRange.ANUN,440282.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almUnderRange.AKED,440282.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almUnderRange.Resetable,440282.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almUnderRange.REST,440282.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almUnderRange.ACKN,440282.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almUnderRange.UACK,440282.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almUnderRange.MCmd_Enable,440282.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almUnderRange.MCmd_Disable,440282.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almUnderRange.OCmd_Shelve,440282.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almUnderRange.OCmd_Unshelve,440282.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almUnderRange.SCmd_Suppress,440282.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almUnderRange.SCmd_UnSuppress,440283.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almUnderRange.AEShelveTMRDN,440283.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almUnderRange.Bad,440283.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almUnderRange.Suppress,440284.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.UnSuppress,440284.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Shelve,440284.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.UnShelve,440284.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Enable,440284.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Disable,440284.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Ack,440284.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Reset,440284.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almUnderRange.Suppressed,440284.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almUnderRange.Shelved,440284.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almUnderRange.Disabled,440284.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almUnderRange.Acked,440284.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almUnderRange.Alarm,440284.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Fault,440294.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almOverRange.AlarmState,440294.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almOverRange.GlobalReset,440294.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almOverRange.FaultInAlarm,440294.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almOverRange.ALRM,440294.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almOverRange.ANUN,440294.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almOverRange.AKED,440294.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almOverRange.Resetable,440294.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almOverRange.REST,440294.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almOverRange.ACKN,440294.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almOverRange.UACK,440294.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almOverRange.MCmd_Enable,440294.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almOverRange.MCmd_Disable,440294.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almOverRange.OCmd_Shelve,440294.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almOverRange.OCmd_Unshelve,440294.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almOverRange.SCmd_Suppress,440294.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almOverRange.SCmd_UnSuppress,440295.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almOverRange.AEShelveTMRDN,440295.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almOverRange.Bad,440295.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almOverRange.Suppress,440296.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.UnSuppress,440296.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Shelve,440296.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.UnShelve,440296.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Enable,440296.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Disable,440296.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Ack,440296.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Reset,440296.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almOverRange.Suppressed,440296.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almOverRange.Shelved,440296.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almOverRange.Disabled,440296.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almOverRange.Acked,440296.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almOverRange.Alarm,440296.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Fault,440306.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almPositionFailure.AlarmState,440306.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almPositionFailure.GlobalReset,440306.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almPositionFailure.FaultInAlarm,440306.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almPositionFailure.ALRM,440306.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almPositionFailure.ANUN,440306.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almPositionFailure.AKED,440306.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almPositionFailure.Resetable,440306.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almPositionFailure.REST,440306.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almPositionFailure.ACKN,440306.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almPositionFailure.UACK,440306.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almPositionFailure.MCmd_Enable,440306.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almPositionFailure.MCmd_Disable,440306.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almPositionFailure.OCmd_Shelve,440306.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almPositionFailure.OCmd_Unshelve,440306.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almPositionFailure.SCmd_Suppress,440306.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almPositionFailure.SCmd_UnSuppress,440307.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almPositionFailure.AEShelveTMRDN,440307.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almPositionFailure.Bad,440307.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almPositionFailure.Suppress,440308.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.UnSuppress,440308.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Shelve,440308.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.UnShelve,440308.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Enable,440308.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Disable,440308.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Ack,440308.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Reset,440308.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almPositionFailure.Suppressed,440308.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almPositionFailure.Shelved,440308.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almPositionFailure.Disabled,440308.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almPositionFailure.Acked,440308.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almPositionFailure.Alarm,440308.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Fault,440318.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almPLCFault.AlarmState,440318.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almPLCFault.GlobalReset,440318.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almPLCFault.FaultInAlarm,440318.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almPLCFault.ALRM,440318.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almPLCFault.ANUN,440318.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almPLCFault.AKED,440318.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almPLCFault.Resetable,440318.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almPLCFault.REST,440318.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almPLCFault.ACKN,440318.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almPLCFault.UACK,440318.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almPLCFault.MCmd_Enable,440318.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almPLCFault.MCmd_Disable,440318.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almPLCFault.OCmd_Shelve,440318.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almPLCFault.OCmd_Unshelve,440318.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almPLCFault.SCmd_Suppress,440318.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almPLCFault.SCmd_UnSuppress,440319.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almPLCFault.AEShelveTMRDN,440319.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almPLCFault.Bad,440319.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almPLCFault.Suppress,440320.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.UnSuppress,440320.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Shelve,440320.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.UnShelve,440320.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Enable,440320.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Disable,440320.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Ack,440320.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Reset,440320.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almPLCFault.Suppressed,440320.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almPLCFault.Shelved,440320.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almPLCFault.Disabled,440320.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almPLCFault.Acked,440320.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almPLCFault.Alarm,440320.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Fault,440330.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete input condition indicating a faulted state." WA3252_FCV_0113_2B.almValveFailure.AlarmState,440330.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Value of the Fault input that indicates an alarm condition" WA3252_FCV_0113_2B.almValveFailure.GlobalReset,440330.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Used to reset all alarms in the PLC" WA3252_FCV_0113_2B.almValveFailure.FaultInAlarm,440330.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Fault Is In Alarm (on longer than the delay)" WA3252_FCV_0113_2B.almValveFailure.ALRM,440330.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm: Output indicating a fault has progressed to alarm state." WA3252_FCV_0113_2B.almValveFailure.ANUN,440330.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Annunciate, indicator to flash alarm on HMI. Set once a fault has reached alarm status. Setting Ack will reset Annuciate and will only set again once the fault transitions from False to True again." WA3252_FCV_0113_2B.almValveFailure.AKED,440330.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledged: Alarm has been acknowledged, will stop the individual alarms from blinking on the popups" WA3252_FCV_0113_2B.almValveFailure.Resetable,440330.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm is latched but can be reset becasue condition is cleared." WA3252_FCV_0113_2B.almValveFailure.REST,440330.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset this alarm only" WA3252_FCV_0113_2B.almValveFailure.ACKN,440330.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowledge Command" WA3252_FCV_0113_2B.almValveFailure.UACK,440330.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Remove the Acknowledge Status" WA3252_FCV_0113_2B.almValveFailure.MCmd_Enable,440330.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Enable Alarm" WA3252_FCV_0113_2B.almValveFailure.MCmd_Disable,440330.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Maintenance Command to Disable Alarm" WA3252_FCV_0113_2B.almValveFailure.OCmd_Shelve,440330.13,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to Shelve Alarm" WA3252_FCV_0113_2B.almValveFailure.OCmd_Unshelve,440330.14,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Operator Command to UnShelve Alarm" WA3252_FCV_0113_2B.almValveFailure.SCmd_Suppress,440330.15,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Suppress Alarm" WA3252_FCV_0113_2B.almValveFailure.SCmd_UnSuppress,440331.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Supervisor Command to Unsuppress Alarm" WA3252_FCV_0113_2B.almValveFailure.AEShelveTMRDN,440331.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Shelve Timer Done" WA3252_FCV_0113_2B.almValveFailure.Bad,440331.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Discrete Input condition indicating a Bad Signal condition" WA3252_FCV_0113_2B.almValveFailure.Suppress,440332.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Suppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.UnSuppress,440332.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: UnSuppress Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Shelve,440332.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Shelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.UnShelve,440332.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Unshelve Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Enable,440332.04,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Enable Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Disable,440332.05,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Disable Alarm Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Ack,440332.06,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Acknowlege Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Reset,440332.07,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Reset Command to AE Server" WA3252_FCV_0113_2B.almValveFailure.Suppressed,440332.08,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Suppressed Status from AE Server" WA3252_FCV_0113_2B.almValveFailure.Shelved,440332.09,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Shelved Status from AE Server" WA3252_FCV_0113_2B.almValveFailure.Disabled,440332.10,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Disabled Status from AE Server" WA3252_FCV_0113_2B.almValveFailure.Acked,440332.11,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Acknowledged Status from AE Server" WA3252_FCV_0113_2B.almValveFailure.Alarm,440332.12,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Command to AE Server" WA3252_AFD_0103_1_SI.Totalize.First_Scan,401148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_1_SI.Totalize.EnableTot,401148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_1_SI.Totalize.REST,401148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_1_SI.Totalize.RollDay,401148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_2_SI.Totalize.First_Scan,401348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_2_SI.Totalize.EnableTot,401348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_2_SI.Totalize.REST,401348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_2_SI.Totalize.RollDay,401348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_3_SI.Totalize.First_Scan,401548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_3_SI.Totalize.EnableTot,401548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_3_SI.Totalize.REST,401548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_3_SI.Totalize.RollDay,401548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_4_SI.Totalize.First_Scan,401748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_4_SI.Totalize.EnableTot,401748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_4_SI.Totalize.REST,401748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_4_SI.Totalize.RollDay,401748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_5_SI.Totalize.First_Scan,401948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_5_SI.Totalize.EnableTot,401948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_5_SI.Totalize.REST,401948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_5_SI.Totalize.RollDay,401948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_6_SI.Totalize.First_Scan,402148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_6_SI.Totalize.EnableTot,402148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_6_SI.Totalize.REST,402148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_6_SI.Totalize.RollDay,402148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_7_SI.Totalize.First_Scan,402348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_7_SI.Totalize.EnableTot,402348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_7_SI.Totalize.REST,402348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_7_SI.Totalize.RollDay,402348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_8_SI.Totalize.First_Scan,402548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_8_SI.Totalize.EnableTot,402548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_8_SI.Totalize.REST,402548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_8_SI.Totalize.RollDay,402548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_9_SI.Totalize.First_Scan,402748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_AFD_0103_9_SI.Totalize.EnableTot,402748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_AFD_0103_9_SI.Totalize.REST,402748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_AFD_0103_9_SI.Totalize.RollDay,402748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI1.Totalize.First_Scan,402948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI1.Totalize.EnableTot,402948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI1.Totalize.REST,402948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI1.Totalize.RollDay,402948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI2.Totalize.First_Scan,403148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI2.Totalize.EnableTot,403148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI2.Totalize.REST,403148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI2.Totalize.RollDay,403148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI3.Totalize.First_Scan,403348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI3.Totalize.EnableTot,403348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI3.Totalize.REST,403348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI3.Totalize.RollDay,403348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI4.Totalize.First_Scan,403548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI4.Totalize.EnableTot,403548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI4.Totalize.REST,403548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI4.Totalize.RollDay,403548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI5.Totalize.First_Scan,403748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI5.Totalize.EnableTot,403748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI5.Totalize.REST,403748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI5.Totalize.RollDay,403748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI6.Totalize.First_Scan,403948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI6.Totalize.EnableTot,403948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI6.Totalize.REST,403948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI6.Totalize.RollDay,403948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI7.Totalize.First_Scan,404148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI7.Totalize.EnableTot,404148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI7.Totalize.REST,404148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI7.Totalize.RollDay,404148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI8.Totalize.First_Scan,404348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI8.Totalize.EnableTot,404348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI8.Totalize.REST,404348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI8.Totalize.RollDay,404348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI9.Totalize.First_Scan,404548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_CP_0116_1_FI9.Totalize.EnableTot,404548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_CP_0116_1_FI9.Totalize.REST,404548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_CP_0116_1_FI9.Totalize.RollDay,404548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2A_ZI.Totalize.First_Scan,404748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FCV_0113_2A_ZI.Totalize.EnableTot,404748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FCV_0113_2A_ZI.Totalize.REST,404748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FCV_0113_2A_ZI.Totalize.RollDay,404748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2B_ZI.Totalize.First_Scan,404948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FCV_0113_2B_ZI.Totalize.EnableTot,404948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FCV_0113_2B_ZI.Totalize.REST,404948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FCV_0113_2B_ZI.Totalize.RollDay,404948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FIT_0113_2A_FI.Totalize.First_Scan,405148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FIT_0113_2A_FI.Totalize.EnableTot,405148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FIT_0113_2A_FI.Totalize.REST,405148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FIT_0113_2A_FI.Totalize.RollDay,405148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_1B_ZI.Totalize.First_Scan,405348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_1B_ZI.Totalize.EnableTot,405348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_1B_ZI.Totalize.REST,405348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_1B_ZI.Totalize.RollDay,405348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_2B_ZI.Totalize.First_Scan,405548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_2B_ZI.Totalize.EnableTot,405548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_2B_ZI.Totalize.REST,405548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_2B_ZI.Totalize.RollDay,405548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_3B_ZI.Totalize.First_Scan,405748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_3B_ZI.Totalize.EnableTot,405748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_3B_ZI.Totalize.REST,405748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_3B_ZI.Totalize.RollDay,405748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_4B_ZI.Totalize.First_Scan,405948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_4B_ZI.Totalize.EnableTot,405948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_4B_ZI.Totalize.REST,405948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_4B_ZI.Totalize.RollDay,405948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_5B_ZI.Totalize.First_Scan,406148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_5B_ZI.Totalize.EnableTot,406148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_5B_ZI.Totalize.REST,406148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_5B_ZI.Totalize.RollDay,406148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_6B_ZI.Totalize.First_Scan,406348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_6B_ZI.Totalize.EnableTot,406348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_6B_ZI.Totalize.REST,406348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_6B_ZI.Totalize.RollDay,406348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_7B_ZI.Totalize.First_Scan,406548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_7B_ZI.Totalize.EnableTot,406548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_7B_ZI.Totalize.REST,406548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_7B_ZI.Totalize.RollDay,406548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_8B_ZI.Totalize.First_Scan,406748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_8B_ZI.Totalize.EnableTot,406748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_8B_ZI.Totalize.REST,406748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_8B_ZI.Totalize.RollDay,406748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_9B_ZI.Totalize.First_Scan,406948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_FV_0103_9B_ZI.Totalize.EnableTot,406948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_FV_0103_9B_ZI.Totalize.REST,406948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_FV_0103_9B_ZI.Totalize.RollDay,406948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI1.Totalize.First_Scan,407148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_1_VI1.Totalize.EnableTot,407148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_1_VI1.Totalize.REST,407148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_1_VI1.Totalize.RollDay,407148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI2.Totalize.First_Scan,407348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_1_VI2.Totalize.EnableTot,407348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_1_VI2.Totalize.REST,407348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_1_VI2.Totalize.RollDay,407348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI3.Totalize.First_Scan,407548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_1_VI3.Totalize.EnableTot,407548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_1_VI3.Totalize.REST,407548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_1_VI3.Totalize.RollDay,407548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI4.Totalize.First_Scan,407748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_1_VI4.Totalize.EnableTot,407748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_1_VI4.Totalize.REST,407748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_1_VI4.Totalize.RollDay,407748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI1.Totalize.First_Scan,407948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_2_VI1.Totalize.EnableTot,407948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_2_VI1.Totalize.REST,407948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_2_VI1.Totalize.RollDay,407948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI2.Totalize.First_Scan,408148.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_2_VI2.Totalize.EnableTot,408148.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_2_VI2.Totalize.REST,408148.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_2_VI2.Totalize.RollDay,408148.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI3.Totalize.First_Scan,408348.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_2_VI3.Totalize.EnableTot,408348.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_2_VI3.Totalize.REST,408348.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_2_VI3.Totalize.RollDay,408348.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI4.Totalize.First_Scan,408548.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_2_VI4.Totalize.EnableTot,408548.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_2_VI4.Totalize.REST,408548.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_2_VI4.Totalize.RollDay,408548.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI1.Totalize.First_Scan,408748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_3_VI1.Totalize.EnableTot,408748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_3_VI1.Totalize.REST,408748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_3_VI1.Totalize.RollDay,408748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI2.Totalize.First_Scan,408948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_3_VI2.Totalize.EnableTot,408948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_3_VI2.Totalize.REST,408948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_3_VI2.Totalize.RollDay,408948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI3.Totalize.First_Scan,409148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_3_VI3.Totalize.EnableTot,409148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_3_VI3.Totalize.REST,409148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_3_VI3.Totalize.RollDay,409148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI4.Totalize.First_Scan,409348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_3_VI4.Totalize.EnableTot,409348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_3_VI4.Totalize.REST,409348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_3_VI4.Totalize.RollDay,409348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI1.Totalize.First_Scan,409548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_4_VI1.Totalize.EnableTot,409548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_4_VI1.Totalize.REST,409548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_4_VI1.Totalize.RollDay,409548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI2.Totalize.First_Scan,409748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_4_VI2.Totalize.EnableTot,409748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_4_VI2.Totalize.REST,409748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_4_VI2.Totalize.RollDay,409748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI3.Totalize.First_Scan,409948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_4_VI3.Totalize.EnableTot,409948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_4_VI3.Totalize.REST,409948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_4_VI3.Totalize.RollDay,409948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI4.Totalize.First_Scan,410148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_4_VI4.Totalize.EnableTot,410148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_4_VI4.Totalize.REST,410148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_4_VI4.Totalize.RollDay,410148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI1.Totalize.First_Scan,410348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_5_VI1.Totalize.EnableTot,410348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_5_VI1.Totalize.REST,410348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_5_VI1.Totalize.RollDay,410348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI2.Totalize.First_Scan,410548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_5_VI2.Totalize.EnableTot,410548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_5_VI2.Totalize.REST,410548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_5_VI2.Totalize.RollDay,410548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI3.Totalize.First_Scan,410748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_5_VI3.Totalize.EnableTot,410748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_5_VI3.Totalize.REST,410748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_5_VI3.Totalize.RollDay,410748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI4.Totalize.First_Scan,410948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_5_VI4.Totalize.EnableTot,410948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_5_VI4.Totalize.REST,410948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_5_VI4.Totalize.RollDay,410948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI1.Totalize.First_Scan,411148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_6_VI1.Totalize.EnableTot,411148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_6_VI1.Totalize.REST,411148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_6_VI1.Totalize.RollDay,411148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI2.Totalize.First_Scan,411348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_6_VI2.Totalize.EnableTot,411348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_6_VI2.Totalize.REST,411348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_6_VI2.Totalize.RollDay,411348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI3.Totalize.First_Scan,411548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_6_VI3.Totalize.EnableTot,411548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_6_VI3.Totalize.REST,411548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_6_VI3.Totalize.RollDay,411548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI4.Totalize.First_Scan,411748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_6_VI4.Totalize.EnableTot,411748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_6_VI4.Totalize.REST,411748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_6_VI4.Totalize.RollDay,411748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI1.Totalize.First_Scan,411948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_7_VI1.Totalize.EnableTot,411948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_7_VI1.Totalize.REST,411948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_7_VI1.Totalize.RollDay,411948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI2.Totalize.First_Scan,412148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_7_VI2.Totalize.EnableTot,412148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_7_VI2.Totalize.REST,412148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_7_VI2.Totalize.RollDay,412148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI3.Totalize.First_Scan,412348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_7_VI3.Totalize.EnableTot,412348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_7_VI3.Totalize.REST,412348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_7_VI3.Totalize.RollDay,412348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI4.Totalize.First_Scan,412548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_7_VI4.Totalize.EnableTot,412548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_7_VI4.Totalize.REST,412548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_7_VI4.Totalize.RollDay,412548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI1.Totalize.First_Scan,412748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_8_VI1.Totalize.EnableTot,412748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_8_VI1.Totalize.REST,412748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_8_VI1.Totalize.RollDay,412748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI2.Totalize.First_Scan,412948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_8_VI2.Totalize.EnableTot,412948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_8_VI2.Totalize.REST,412948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_8_VI2.Totalize.RollDay,412948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI3.Totalize.First_Scan,413148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_8_VI3.Totalize.EnableTot,413148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_8_VI3.Totalize.REST,413148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_8_VI3.Totalize.RollDay,413148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI4.Totalize.First_Scan,413348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_8_VI4.Totalize.EnableTot,413348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_8_VI4.Totalize.REST,413348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_8_VI4.Totalize.RollDay,413348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI1.Totalize.First_Scan,413548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_9_VI1.Totalize.EnableTot,413548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_9_VI1.Totalize.REST,413548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_9_VI1.Totalize.RollDay,413548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI2.Totalize.First_Scan,413748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_9_VI2.Totalize.EnableTot,413748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_9_VI2.Totalize.REST,413748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_9_VI2.Totalize.RollDay,413748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI3.Totalize.First_Scan,413948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_9_VI3.Totalize.EnableTot,413948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_9_VI3.Totalize.REST,413948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_9_VI3.Totalize.RollDay,413948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI4.Totalize.First_Scan,414148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_MTR_0103_9_VI4.Totalize.EnableTot,414148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_MTR_0103_9_VI4.Totalize.REST,414148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_MTR_0103_9_VI4.Totalize.RollDay,414148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_1_PI.Totalize.First_Scan,414348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0102_1_PI.Totalize.EnableTot,414348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0102_1_PI.Totalize.REST,414348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0102_1_PI.Totalize.RollDay,414348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_2_PI.Totalize.First_Scan,414548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0102_2_PI.Totalize.EnableTot,414548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0102_2_PI.Totalize.REST,414548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0102_2_PI.Totalize.RollDay,414548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_1_PI.Totalize.First_Scan,414748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_1_PI.Totalize.EnableTot,414748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_1_PI.Totalize.REST,414748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_1_PI.Totalize.RollDay,414748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_2_PI.Totalize.First_Scan,414948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_2_PI.Totalize.EnableTot,414948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_2_PI.Totalize.REST,414948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_2_PI.Totalize.RollDay,414948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_3_PI.Totalize.First_Scan,415148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_3_PI.Totalize.EnableTot,415148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_3_PI.Totalize.REST,415148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_3_PI.Totalize.RollDay,415148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_4_PI.Totalize.First_Scan,415348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_4_PI.Totalize.EnableTot,415348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_4_PI.Totalize.REST,415348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_4_PI.Totalize.RollDay,415348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_5_PI.Totalize.First_Scan,415548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_5_PI.Totalize.EnableTot,415548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_5_PI.Totalize.REST,415548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_5_PI.Totalize.RollDay,415548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_6_PI.Totalize.First_Scan,415748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_6_PI.Totalize.EnableTot,415748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_6_PI.Totalize.REST,415748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_6_PI.Totalize.RollDay,415748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_7_PI.Totalize.First_Scan,415948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_7_PI.Totalize.EnableTot,415948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_7_PI.Totalize.REST,415948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_7_PI.Totalize.RollDay,415948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_8_PI.Totalize.First_Scan,416148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_8_PI.Totalize.EnableTot,416148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_8_PI.Totalize.REST,416148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_8_PI.Totalize.RollDay,416148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_9_PI.Totalize.First_Scan,416348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0103_9_PI.Totalize.EnableTot,416348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0103_9_PI.Totalize.REST,416348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0103_9_PI.Totalize.RollDay,416348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0104_1_PI.Totalize.First_Scan,416548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PIT_0104_1_PI.Totalize.EnableTot,416548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PIT_0104_1_PI.Totalize.REST,416548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PIT_0104_1_PI.Totalize.RollDay,416548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI1.Totalize.First_Scan,416748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_1_VI1.Totalize.EnableTot,416748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_1_VI1.Totalize.REST,416748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_1_VI1.Totalize.RollDay,416748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI2.Totalize.First_Scan,416948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_1_VI2.Totalize.EnableTot,416948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_1_VI2.Totalize.REST,416948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_1_VI2.Totalize.RollDay,416948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI3.Totalize.First_Scan,417148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_1_VI3.Totalize.EnableTot,417148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_1_VI3.Totalize.REST,417148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_1_VI3.Totalize.RollDay,417148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI4.Totalize.First_Scan,417348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_1_VI4.Totalize.EnableTot,417348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_1_VI4.Totalize.REST,417348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_1_VI4.Totalize.RollDay,417348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI5.Totalize.First_Scan,417548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_1_VI5.Totalize.EnableTot,417548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_1_VI5.Totalize.REST,417548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_1_VI5.Totalize.RollDay,417548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI1.Totalize.First_Scan,417748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_2_VI1.Totalize.EnableTot,417748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_2_VI1.Totalize.REST,417748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_2_VI1.Totalize.RollDay,417748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI2.Totalize.First_Scan,417948.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_2_VI2.Totalize.EnableTot,417948.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_2_VI2.Totalize.REST,417948.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_2_VI2.Totalize.RollDay,417948.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI3.Totalize.First_Scan,418148.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_2_VI3.Totalize.EnableTot,418148.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_2_VI3.Totalize.REST,418148.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_2_VI3.Totalize.RollDay,418148.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI4.Totalize.First_Scan,418348.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_2_VI4.Totalize.EnableTot,418348.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_2_VI4.Totalize.REST,418348.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_2_VI4.Totalize.RollDay,418348.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI5.Totalize.First_Scan,418548.00,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_2_VI5.Totalize.EnableTot,418548.01,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_2_VI5.Totalize.REST,418548.02,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_2_VI5.Totalize.RollDay,418548.03,Boolean,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI1.Totalize.First_Scan,418748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_3_VI1.Totalize.EnableTot,418748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_3_VI1.Totalize.REST,418748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_3_VI1.Totalize.RollDay,418748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI2.Totalize.First_Scan,418948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_3_VI2.Totalize.EnableTot,418948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_3_VI2.Totalize.REST,418948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_3_VI2.Totalize.RollDay,418948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI3.Totalize.First_Scan,419148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_3_VI3.Totalize.EnableTot,419148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_3_VI3.Totalize.REST,419148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_3_VI3.Totalize.RollDay,419148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI4.Totalize.First_Scan,419348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_3_VI4.Totalize.EnableTot,419348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_3_VI4.Totalize.REST,419348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_3_VI4.Totalize.RollDay,419348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI5.Totalize.First_Scan,419548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_3_VI5.Totalize.EnableTot,419548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_3_VI5.Totalize.REST,419548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_3_VI5.Totalize.RollDay,419548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI1.Totalize.First_Scan,419748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_4_VI1.Totalize.EnableTot,419748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_4_VI1.Totalize.REST,419748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_4_VI1.Totalize.RollDay,419748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI2.Totalize.First_Scan,419948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_4_VI2.Totalize.EnableTot,419948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_4_VI2.Totalize.REST,419948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_4_VI2.Totalize.RollDay,419948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI3.Totalize.First_Scan,420148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_4_VI3.Totalize.EnableTot,420148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_4_VI3.Totalize.REST,420148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_4_VI3.Totalize.RollDay,420148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI4.Totalize.First_Scan,420348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_4_VI4.Totalize.EnableTot,420348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_4_VI4.Totalize.REST,420348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_4_VI4.Totalize.RollDay,420348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI5.Totalize.First_Scan,420548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_4_VI5.Totalize.EnableTot,420548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_4_VI5.Totalize.REST,420548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_4_VI5.Totalize.RollDay,420548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI1.Totalize.First_Scan,420748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_5_VI1.Totalize.EnableTot,420748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_5_VI1.Totalize.REST,420748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_5_VI1.Totalize.RollDay,420748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI2.Totalize.First_Scan,420948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_5_VI2.Totalize.EnableTot,420948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_5_VI2.Totalize.REST,420948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_5_VI2.Totalize.RollDay,420948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI3.Totalize.First_Scan,421148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_5_VI3.Totalize.EnableTot,421148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_5_VI3.Totalize.REST,421148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_5_VI3.Totalize.RollDay,421148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI4.Totalize.First_Scan,421348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_5_VI4.Totalize.EnableTot,421348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_5_VI4.Totalize.REST,421348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_5_VI4.Totalize.RollDay,421348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI5.Totalize.First_Scan,421548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_5_VI5.Totalize.EnableTot,421548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_5_VI5.Totalize.REST,421548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_5_VI5.Totalize.RollDay,421548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI1.Totalize.First_Scan,421748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_6_VI1.Totalize.EnableTot,421748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_6_VI1.Totalize.REST,421748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_6_VI1.Totalize.RollDay,421748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI2.Totalize.First_Scan,421948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_6_VI2.Totalize.EnableTot,421948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_6_VI2.Totalize.REST,421948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_6_VI2.Totalize.RollDay,421948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI3.Totalize.First_Scan,422148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_6_VI3.Totalize.EnableTot,422148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_6_VI3.Totalize.REST,422148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_6_VI3.Totalize.RollDay,422148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI4.Totalize.First_Scan,422348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_6_VI4.Totalize.EnableTot,422348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_6_VI4.Totalize.REST,422348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_6_VI4.Totalize.RollDay,422348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI5.Totalize.First_Scan,422548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_6_VI5.Totalize.EnableTot,422548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_6_VI5.Totalize.REST,422548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_6_VI5.Totalize.RollDay,422548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI1.Totalize.First_Scan,422748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_7_VI1.Totalize.EnableTot,422748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_7_VI1.Totalize.REST,422748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_7_VI1.Totalize.RollDay,422748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI2.Totalize.First_Scan,422948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_7_VI2.Totalize.EnableTot,422948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_7_VI2.Totalize.REST,422948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_7_VI2.Totalize.RollDay,422948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI3.Totalize.First_Scan,423148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_7_VI3.Totalize.EnableTot,423148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_7_VI3.Totalize.REST,423148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_7_VI3.Totalize.RollDay,423148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI4.Totalize.First_Scan,423348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_7_VI4.Totalize.EnableTot,423348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_7_VI4.Totalize.REST,423348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_7_VI4.Totalize.RollDay,423348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI5.Totalize.First_Scan,423548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_7_VI5.Totalize.EnableTot,423548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_7_VI5.Totalize.REST,423548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_7_VI5.Totalize.RollDay,423548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI1.Totalize.First_Scan,423748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_8_VI1.Totalize.EnableTot,423748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_8_VI1.Totalize.REST,423748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_8_VI1.Totalize.RollDay,423748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI2.Totalize.First_Scan,423948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_8_VI2.Totalize.EnableTot,423948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_8_VI2.Totalize.REST,423948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_8_VI2.Totalize.RollDay,423948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI3.Totalize.First_Scan,424148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_8_VI3.Totalize.EnableTot,424148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_8_VI3.Totalize.REST,424148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_8_VI3.Totalize.RollDay,424148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI4.Totalize.First_Scan,424348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_8_VI4.Totalize.EnableTot,424348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_8_VI4.Totalize.REST,424348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_8_VI4.Totalize.RollDay,424348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI5.Totalize.First_Scan,424548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_8_VI5.Totalize.EnableTot,424548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_8_VI5.Totalize.REST,424548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_8_VI5.Totalize.RollDay,424548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI1.Totalize.First_Scan,424748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_9_VI1.Totalize.EnableTot,424748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_9_VI1.Totalize.REST,424748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_9_VI1.Totalize.RollDay,424748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI2.Totalize.First_Scan,424948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_9_VI2.Totalize.EnableTot,424948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_9_VI2.Totalize.REST,424948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_9_VI2.Totalize.RollDay,424948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI3.Totalize.First_Scan,425148.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_9_VI3.Totalize.EnableTot,425148.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_9_VI3.Totalize.REST,425148.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_9_VI3.Totalize.RollDay,425148.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI4.Totalize.First_Scan,425348.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_9_VI4.Totalize.EnableTot,425348.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_9_VI4.Totalize.REST,425348.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_9_VI4.Totalize.RollDay,425348.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI5.Totalize.First_Scan,425548.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_PMP_0103_9_VI5.Totalize.EnableTot,425548.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_PMP_0103_9_VI5.Totalize.REST,425548.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_PMP_0103_9_VI5.Totalize.RollDay,425548.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0111_1_TI.Totalize.First_Scan,425748.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_TT_0111_1_TI.Totalize.EnableTot,425748.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_TT_0111_1_TI.Totalize.REST,425748.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_TT_0111_1_TI.Totalize.RollDay,425748.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0112_1_TI.Totalize.First_Scan,425948.00,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: This prescan routine is only exicuted before the first scan or on changes from program mode to run mode:" WA3252_TT_0112_1_TI.Totalize.EnableTot,425948.01,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Start Totalizing becasue flow is above the minimum" WA3252_TT_0112_1_TI.Totalize.REST,425948.02,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: HMI Command to Reset Flow Totals" WA3252_TT_0112_1_TI.Totalize.RollDay,425948.03,Boolean,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " Meter_Vault_PLC.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved Meter_Vault_PLC.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump1.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump1.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump2.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump2.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump9.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_Eaton_Pump9.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump1.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump1.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump2.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump2.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump9.Fresh_Reserved.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved RWPS_SEL710_Pump9.Fresh_Reserved.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[1],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[2],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[3],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[4],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[5],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[6],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[7],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[8],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[9],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[10],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[11],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[12],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[13],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[14],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[15],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[16],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[17],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[18],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[19],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[20],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[21],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[22],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[23],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[24],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[25],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[26],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[27],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[28],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[29],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[30],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_CNX_HEALTH.[31],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CRA health (Drop 1 to 31) BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[1],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[2],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[3],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[4],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[5],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[6],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[7],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects BMEP58_ECPU_EXT.CRA_SAFE_HEALTH.[8],,Byte,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health bits for CRA Safe Task objects WA3252_AFD_0103_1_SI.Totalize.TimeBase,401154,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_1_SI.Totalize.TwoMinuteCount,401192,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_2_SI.Totalize.TimeBase,401354,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_2_SI.Totalize.TwoMinuteCount,401392,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_3_SI.Totalize.TimeBase,401554,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_3_SI.Totalize.TwoMinuteCount,401592,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_4_SI.Totalize.TimeBase,401754,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_4_SI.Totalize.TwoMinuteCount,401792,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_5_SI.Totalize.TimeBase,401954,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_5_SI.Totalize.TwoMinuteCount,401992,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_6_SI.Totalize.TimeBase,402154,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_6_SI.Totalize.TwoMinuteCount,402192,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_7_SI.Totalize.TimeBase,402354,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_7_SI.Totalize.TwoMinuteCount,402392,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_8_SI.Totalize.TimeBase,402554,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_8_SI.Totalize.TwoMinuteCount,402592,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_9_SI.Totalize.TimeBase,402754,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_AFD_0103_9_SI.Totalize.TwoMinuteCount,402792,Long,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI1.Totalize.TimeBase,402954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI1.Totalize.TwoMinuteCount,402992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI2.Totalize.TimeBase,403154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI2.Totalize.TwoMinuteCount,403192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI3.Totalize.TimeBase,403354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI3.Totalize.TwoMinuteCount,403392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI4.Totalize.TimeBase,403554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI4.Totalize.TwoMinuteCount,403592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI5.Totalize.TimeBase,403754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI5.Totalize.TwoMinuteCount,403792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI6.Totalize.TimeBase,403954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI6.Totalize.TwoMinuteCount,403992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI7.Totalize.TimeBase,404154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI7.Totalize.TwoMinuteCount,404192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI8.Totalize.TimeBase,404354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI8.Totalize.TwoMinuteCount,404392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI9.Totalize.TimeBase,404554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_CP_0116_1_FI9.Totalize.TwoMinuteCount,404592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2A_ZI.Totalize.TimeBase,404754,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FCV_0113_2A_ZI.Totalize.TwoMinuteCount,404792,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2B_ZI.Totalize.TimeBase,404954,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FCV_0113_2B_ZI.Totalize.TwoMinuteCount,404992,Long,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FIT_0113_2A_FI.Totalize.TimeBase,405154,Long,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FIT_0113_2A_FI.Totalize.TwoMinuteCount,405192,Long,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_1B_ZI.Totalize.TimeBase,405354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_1B_ZI.Totalize.TwoMinuteCount,405392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_2B_ZI.Totalize.TimeBase,405554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_2B_ZI.Totalize.TwoMinuteCount,405592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_3B_ZI.Totalize.TimeBase,405754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_3B_ZI.Totalize.TwoMinuteCount,405792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_4B_ZI.Totalize.TimeBase,405954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_4B_ZI.Totalize.TwoMinuteCount,405992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_5B_ZI.Totalize.TimeBase,406154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_5B_ZI.Totalize.TwoMinuteCount,406192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_6B_ZI.Totalize.TimeBase,406354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_6B_ZI.Totalize.TwoMinuteCount,406392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_7B_ZI.Totalize.TimeBase,406554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_7B_ZI.Totalize.TwoMinuteCount,406592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_8B_ZI.Totalize.TimeBase,406754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_8B_ZI.Totalize.TwoMinuteCount,406792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_9B_ZI.Totalize.TimeBase,406954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_FV_0103_9B_ZI.Totalize.TwoMinuteCount,406992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI1.Totalize.TimeBase,407154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_1_VI1.Totalize.TwoMinuteCount,407192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI2.Totalize.TimeBase,407354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_1_VI2.Totalize.TwoMinuteCount,407392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI3.Totalize.TimeBase,407554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_1_VI3.Totalize.TwoMinuteCount,407592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI4.Totalize.TimeBase,407754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_1_VI4.Totalize.TwoMinuteCount,407792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI1.Totalize.TimeBase,407954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_2_VI1.Totalize.TwoMinuteCount,407992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI2.Totalize.TimeBase,408154,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_2_VI2.Totalize.TwoMinuteCount,408192,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI3.Totalize.TimeBase,408354,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_2_VI3.Totalize.TwoMinuteCount,408392,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI4.Totalize.TimeBase,408554,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_2_VI4.Totalize.TwoMinuteCount,408592,Long,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI1.Totalize.TimeBase,408754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_3_VI1.Totalize.TwoMinuteCount,408792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI2.Totalize.TimeBase,408954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_3_VI2.Totalize.TwoMinuteCount,408992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI3.Totalize.TimeBase,409154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_3_VI3.Totalize.TwoMinuteCount,409192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI4.Totalize.TimeBase,409354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_3_VI4.Totalize.TwoMinuteCount,409392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI1.Totalize.TimeBase,409554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_4_VI1.Totalize.TwoMinuteCount,409592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI2.Totalize.TimeBase,409754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_4_VI2.Totalize.TwoMinuteCount,409792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI3.Totalize.TimeBase,409954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_4_VI3.Totalize.TwoMinuteCount,409992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI4.Totalize.TimeBase,410154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_4_VI4.Totalize.TwoMinuteCount,410192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI1.Totalize.TimeBase,410354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_5_VI1.Totalize.TwoMinuteCount,410392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI2.Totalize.TimeBase,410554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_5_VI2.Totalize.TwoMinuteCount,410592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI3.Totalize.TimeBase,410754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_5_VI3.Totalize.TwoMinuteCount,410792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI4.Totalize.TimeBase,410954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_5_VI4.Totalize.TwoMinuteCount,410992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI1.Totalize.TimeBase,411154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_6_VI1.Totalize.TwoMinuteCount,411192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI2.Totalize.TimeBase,411354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_6_VI2.Totalize.TwoMinuteCount,411392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI3.Totalize.TimeBase,411554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_6_VI3.Totalize.TwoMinuteCount,411592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI4.Totalize.TimeBase,411754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_6_VI4.Totalize.TwoMinuteCount,411792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI1.Totalize.TimeBase,411954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_7_VI1.Totalize.TwoMinuteCount,411992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI2.Totalize.TimeBase,412154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_7_VI2.Totalize.TwoMinuteCount,412192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI3.Totalize.TimeBase,412354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_7_VI3.Totalize.TwoMinuteCount,412392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI4.Totalize.TimeBase,412554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_7_VI4.Totalize.TwoMinuteCount,412592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI1.Totalize.TimeBase,412754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_8_VI1.Totalize.TwoMinuteCount,412792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI2.Totalize.TimeBase,412954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_8_VI2.Totalize.TwoMinuteCount,412992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI3.Totalize.TimeBase,413154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_8_VI3.Totalize.TwoMinuteCount,413192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI4.Totalize.TimeBase,413354,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_8_VI4.Totalize.TwoMinuteCount,413392,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI1.Totalize.TimeBase,413554,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_9_VI1.Totalize.TwoMinuteCount,413592,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI2.Totalize.TimeBase,413754,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_9_VI2.Totalize.TwoMinuteCount,413792,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI3.Totalize.TimeBase,413954,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_9_VI3.Totalize.TwoMinuteCount,413992,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI4.Totalize.TimeBase,414154,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_MTR_0103_9_VI4.Totalize.TwoMinuteCount,414192,Long,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_1_PI.Totalize.TimeBase,414354,Long,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0102_1_PI.Totalize.TwoMinuteCount,414392,Long,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_2_PI.Totalize.TimeBase,414554,Long,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0102_2_PI.Totalize.TwoMinuteCount,414592,Long,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_1_PI.Totalize.TimeBase,414754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_1_PI.Totalize.TwoMinuteCount,414792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_2_PI.Totalize.TimeBase,414954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_2_PI.Totalize.TwoMinuteCount,414992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_3_PI.Totalize.TimeBase,415154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_3_PI.Totalize.TwoMinuteCount,415192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_4_PI.Totalize.TimeBase,415354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_4_PI.Totalize.TwoMinuteCount,415392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_5_PI.Totalize.TimeBase,415554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_5_PI.Totalize.TwoMinuteCount,415592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_6_PI.Totalize.TimeBase,415754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_6_PI.Totalize.TwoMinuteCount,415792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_7_PI.Totalize.TimeBase,415954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_7_PI.Totalize.TwoMinuteCount,415992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_8_PI.Totalize.TimeBase,416154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_8_PI.Totalize.TwoMinuteCount,416192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_9_PI.Totalize.TimeBase,416354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0103_9_PI.Totalize.TwoMinuteCount,416392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0104_1_PI.Totalize.TimeBase,416554,Long,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PIT_0104_1_PI.Totalize.TwoMinuteCount,416592,Long,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI1.Totalize.TimeBase,416754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_1_VI1.Totalize.TwoMinuteCount,416792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI2.Totalize.TimeBase,416954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_1_VI2.Totalize.TwoMinuteCount,416992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI3.Totalize.TimeBase,417154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_1_VI3.Totalize.TwoMinuteCount,417192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI4.Totalize.TimeBase,417354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_1_VI4.Totalize.TwoMinuteCount,417392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI5.Totalize.TimeBase,417554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_1_VI5.Totalize.TwoMinuteCount,417592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI1.Totalize.TimeBase,417754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_2_VI1.Totalize.TwoMinuteCount,417792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI2.Totalize.TimeBase,417954,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_2_VI2.Totalize.TwoMinuteCount,417992,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI3.Totalize.TimeBase,418154,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_2_VI3.Totalize.TwoMinuteCount,418192,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI4.Totalize.TimeBase,418354,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_2_VI4.Totalize.TwoMinuteCount,418392,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI5.Totalize.TimeBase,418554,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_2_VI5.Totalize.TwoMinuteCount,418592,Long,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI1.Totalize.TimeBase,418754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_3_VI1.Totalize.TwoMinuteCount,418792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI2.Totalize.TimeBase,418954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_3_VI2.Totalize.TwoMinuteCount,418992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI3.Totalize.TimeBase,419154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_3_VI3.Totalize.TwoMinuteCount,419192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI4.Totalize.TimeBase,419354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_3_VI4.Totalize.TwoMinuteCount,419392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI5.Totalize.TimeBase,419554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_3_VI5.Totalize.TwoMinuteCount,419592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI1.Totalize.TimeBase,419754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_4_VI1.Totalize.TwoMinuteCount,419792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI2.Totalize.TimeBase,419954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_4_VI2.Totalize.TwoMinuteCount,419992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI3.Totalize.TimeBase,420154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_4_VI3.Totalize.TwoMinuteCount,420192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI4.Totalize.TimeBase,420354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_4_VI4.Totalize.TwoMinuteCount,420392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI5.Totalize.TimeBase,420554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_4_VI5.Totalize.TwoMinuteCount,420592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI1.Totalize.TimeBase,420754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_5_VI1.Totalize.TwoMinuteCount,420792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI2.Totalize.TimeBase,420954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_5_VI2.Totalize.TwoMinuteCount,420992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI3.Totalize.TimeBase,421154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_5_VI3.Totalize.TwoMinuteCount,421192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI4.Totalize.TimeBase,421354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_5_VI4.Totalize.TwoMinuteCount,421392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI5.Totalize.TimeBase,421554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_5_VI5.Totalize.TwoMinuteCount,421592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI1.Totalize.TimeBase,421754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_6_VI1.Totalize.TwoMinuteCount,421792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI2.Totalize.TimeBase,421954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_6_VI2.Totalize.TwoMinuteCount,421992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI3.Totalize.TimeBase,422154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_6_VI3.Totalize.TwoMinuteCount,422192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI4.Totalize.TimeBase,422354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_6_VI4.Totalize.TwoMinuteCount,422392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI5.Totalize.TimeBase,422554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_6_VI5.Totalize.TwoMinuteCount,422592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI1.Totalize.TimeBase,422754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_7_VI1.Totalize.TwoMinuteCount,422792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI2.Totalize.TimeBase,422954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_7_VI2.Totalize.TwoMinuteCount,422992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI3.Totalize.TimeBase,423154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_7_VI3.Totalize.TwoMinuteCount,423192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI4.Totalize.TimeBase,423354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_7_VI4.Totalize.TwoMinuteCount,423392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI5.Totalize.TimeBase,423554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_7_VI5.Totalize.TwoMinuteCount,423592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI1.Totalize.TimeBase,423754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_8_VI1.Totalize.TwoMinuteCount,423792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI2.Totalize.TimeBase,423954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_8_VI2.Totalize.TwoMinuteCount,423992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI3.Totalize.TimeBase,424154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_8_VI3.Totalize.TwoMinuteCount,424192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI4.Totalize.TimeBase,424354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_8_VI4.Totalize.TwoMinuteCount,424392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI5.Totalize.TimeBase,424554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_8_VI5.Totalize.TwoMinuteCount,424592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI1.Totalize.TimeBase,424754,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_9_VI1.Totalize.TwoMinuteCount,424792,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI2.Totalize.TimeBase,424954,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_9_VI2.Totalize.TwoMinuteCount,424992,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI3.Totalize.TimeBase,425154,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_9_VI3.Totalize.TwoMinuteCount,425192,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI4.Totalize.TimeBase,425354,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_9_VI4.Totalize.TwoMinuteCount,425392,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI5.Totalize.TimeBase,425554,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_PMP_0103_9_VI5.Totalize.TwoMinuteCount,425592,Long,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0111_1_TI.Totalize.TimeBase,425754,Long,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_TT_0111_1_TI.Totalize.TwoMinuteCount,425792,Long,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0112_1_TI.Totalize.TimeBase,425954,Long,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time base of flow: 0 = per Second, 1 = per Minute, 2 = per Hour, 3 = per Day" WA3252_TT_0112_1_TI.Totalize.TwoMinuteCount,425992,Long,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " RWPS_Eaton_Pump1.Inputs.MSG_1_0,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_1,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_2,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_3,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_4,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_5,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_6,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_7,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_8,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_9,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_10,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_11,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_12,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_13,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_14,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_15,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_16,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_17,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_18,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_19,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_20,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_21,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_22,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_23,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_24,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_25,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_26,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_27,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_28,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_29,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_30,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_31,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_32,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_33,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_34,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_35,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_36,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_37,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_38,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_39,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_40,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_41,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_42,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_43,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_44,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_45,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_46,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_47,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_48,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump1.Inputs.MSG_1_49,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_0,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_1,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_2,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_3,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_4,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_5,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_6,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_7,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_8,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_9,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_10,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_11,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_12,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_13,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_14,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_15,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_16,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_17,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_18,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_19,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_20,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_21,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_22,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_23,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_24,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_25,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_26,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_27,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_28,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_29,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_30,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_31,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_32,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_33,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_34,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_35,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_36,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_37,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_38,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_39,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_40,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_41,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_42,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_43,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_44,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_45,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_46,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_47,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_48,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump2.Inputs.MSG_1_49,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_0,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_1,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_2,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_3,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_4,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_5,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_6,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_7,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_8,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_9,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_10,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_11,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_12,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_13,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_14,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_15,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_16,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_17,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_18,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_19,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_20,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_21,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_22,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_23,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_24,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_25,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_26,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_27,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_28,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_29,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_30,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_31,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_32,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_33,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_34,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_35,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_36,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_37,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_38,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_39,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_40,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_41,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_42,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_43,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_44,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_45,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_46,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_47,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_48,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_Eaton_Pump9.Inputs.MSG_1_49,,Long,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: WA3252_AFD_0103_1.RSRTTime.[0],436384,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSRTTime.[1],436385,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSRTTime.[2],436386,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSRTTime.[3],436387,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSRTTime.[4],436388,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSRTTime.[5],436389,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_1.RSSTTime.[0],436390,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.RSSTTime.[1],436391,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.RSSTTime.[2],436392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.RSSTTime.[3],436393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.RSSTTime.[4],436394,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.RSSTTime.[5],436395,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_1.TDAT.[0],436396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1.TDAT.[1],436397,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1.TDAT.[2],436398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1.TDAT.[3],436399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1.TDAT.[4],436400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1.TDAT.[5],436401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.RSRTTime.[0],436520,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSRTTime.[1],436521,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSRTTime.[2],436522,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSRTTime.[3],436523,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSRTTime.[4],436524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSRTTime.[5],436525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_2.RSSTTime.[0],436526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.RSSTTime.[1],436527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.RSSTTime.[2],436528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.RSSTTime.[3],436529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.RSSTTime.[4],436530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.RSSTTime.[5],436531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_2.TDAT.[0],436532,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.TDAT.[1],436533,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.TDAT.[2],436534,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.TDAT.[3],436535,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.TDAT.[4],436536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_2.TDAT.[5],436537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.RSRTTime.[0],436654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSRTTime.[1],436655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSRTTime.[2],436656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSRTTime.[3],436657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSRTTime.[4],436658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSRTTime.[5],436659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_3.RSSTTime.[0],436660,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.RSSTTime.[1],436661,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.RSSTTime.[2],436662,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.RSSTTime.[3],436663,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.RSSTTime.[4],436664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.RSSTTime.[5],436665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_3.TDAT.[0],436666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.TDAT.[1],436667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.TDAT.[2],436668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.TDAT.[3],436669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.TDAT.[4],436670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_3.TDAT.[5],436671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.RSRTTime.[0],436790,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSRTTime.[1],436791,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSRTTime.[2],436792,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSRTTime.[3],436793,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSRTTime.[4],436794,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSRTTime.[5],436795,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_4.RSSTTime.[0],436796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.RSSTTime.[1],436797,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.RSSTTime.[2],436798,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.RSSTTime.[3],436799,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.RSSTTime.[4],436800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.RSSTTime.[5],436801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_4.TDAT.[0],436802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.TDAT.[1],436803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.TDAT.[2],436804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.TDAT.[3],436805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.TDAT.[4],436806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_4.TDAT.[5],436807,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.RSRTTime.[0],436924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSRTTime.[1],436925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSRTTime.[2],436926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSRTTime.[3],436927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSRTTime.[4],436928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSRTTime.[5],436929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_5.RSSTTime.[0],436930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.RSSTTime.[1],436931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.RSSTTime.[2],436932,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.RSSTTime.[3],436933,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.RSSTTime.[4],436934,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.RSSTTime.[5],436935,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_5.TDAT.[0],436936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.TDAT.[1],436937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.TDAT.[2],436938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.TDAT.[3],436939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.TDAT.[4],436940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_5.TDAT.[5],436941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.RSRTTime.[0],437060,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSRTTime.[1],437061,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSRTTime.[2],437062,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSRTTime.[3],437063,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSRTTime.[4],437064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSRTTime.[5],437065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_6.RSSTTime.[0],437066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.RSSTTime.[1],437067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.RSSTTime.[2],437068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.RSSTTime.[3],437069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.RSSTTime.[4],437070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.RSSTTime.[5],437071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_6.TDAT.[0],437072,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.TDAT.[1],437073,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.TDAT.[2],437074,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.TDAT.[3],437075,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.TDAT.[4],437076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_6.TDAT.[5],437077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.RSRTTime.[0],437194,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSRTTime.[1],437195,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSRTTime.[2],437196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSRTTime.[3],437197,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSRTTime.[4],437198,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSRTTime.[5],437199,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_7.RSSTTime.[0],437200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.RSSTTime.[1],437201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.RSSTTime.[2],437202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.RSSTTime.[3],437203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.RSSTTime.[4],437204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.RSSTTime.[5],437205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_7.TDAT.[0],437206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.TDAT.[1],437207,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.TDAT.[2],437208,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.TDAT.[3],437209,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.TDAT.[4],437210,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_7.TDAT.[5],437211,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.RSRTTime.[0],437330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSRTTime.[1],437331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSRTTime.[2],437332,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSRTTime.[3],437333,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSRTTime.[4],437334,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSRTTime.[5],437335,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_8.RSSTTime.[0],437336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.RSSTTime.[1],437337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.RSSTTime.[2],437338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.RSSTTime.[3],437339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.RSSTTime.[4],437340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.RSSTTime.[5],437341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_8.TDAT.[0],437342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.TDAT.[1],437343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.TDAT.[2],437344,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.TDAT.[3],437345,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.TDAT.[4],437346,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_8.TDAT.[5],437347,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.RSRTTime.[0],437464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSRTTime.[1],437465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSRTTime.[2],437466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSRTTime.[3],437467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSRTTime.[4],437468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSRTTime.[5],437469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the runtime was last reset" WA3252_AFD_0103_9.RSSTTime.[0],437470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.RSSTTime.[1],437471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.RSSTTime.[2],437472,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.RSSTTime.[3],437473,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.RSSTTime.[4],437474,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.RSSTTime.[5],437475,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Time the starts counts was last reset" WA3252_AFD_0103_9.TDAT.[0],437476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.TDAT.[1],437477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.TDAT.[2],437478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.TDAT.[3],437479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.TDAT.[4],437480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_9.TDAT.[5],437481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.RSCTTime.[0],437588,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.RSCTTime.[1],437589,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.RSCTTime.[2],437590,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.RSCTTime.[3],437591,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.RSCTTime.[4],437592,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.RSCTTime.[5],437593,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1A.TDAT.[0],437596,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.TDAT.[1],437597,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.TDAT.[2],437598,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.TDAT.[3],437599,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.TDAT.[4],437600,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1A.TDAT.[5],437601,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.RSCTTime.[0],437668,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.RSCTTime.[1],437669,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.RSCTTime.[2],437670,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.RSCTTime.[3],437671,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.RSCTTime.[4],437672,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.RSCTTime.[5],437673,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_1B.TDAT.[0],437676,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.TDAT.[1],437677,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.TDAT.[2],437678,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.TDAT.[3],437679,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.TDAT.[4],437680,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_1B.TDAT.[5],437681,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.RSCTTime.[0],437748,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.RSCTTime.[1],437749,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.RSCTTime.[2],437750,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.RSCTTime.[3],437751,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.RSCTTime.[4],437752,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.RSCTTime.[5],437753,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2A.TDAT.[0],437756,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.TDAT.[1],437757,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.TDAT.[2],437758,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.TDAT.[3],437759,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.TDAT.[4],437760,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2A.TDAT.[5],437761,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.RSCTTime.[0],437828,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.RSCTTime.[1],437829,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.RSCTTime.[2],437830,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.RSCTTime.[3],437831,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.RSCTTime.[4],437832,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.RSCTTime.[5],437833,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0102_2B.TDAT.[0],437836,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.TDAT.[1],437837,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.TDAT.[2],437838,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.TDAT.[3],437839,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.TDAT.[4],437840,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0102_2B.TDAT.[5],437841,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.RSCTTime.[0],437908,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.RSCTTime.[1],437909,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.RSCTTime.[2],437910,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.RSCTTime.[3],437911,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.RSCTTime.[4],437912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.RSCTTime.[5],437913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1A.TDAT.[0],437916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.TDAT.[1],437917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.TDAT.[2],437918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.TDAT.[3],437919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.TDAT.[4],437920,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1A.TDAT.[5],437921,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.RSCTTime.[0],437988,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.RSCTTime.[1],437989,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.RSCTTime.[2],437990,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.RSCTTime.[3],437991,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.RSCTTime.[4],437992,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.RSCTTime.[5],437993,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_1C.TDAT.[0],437996,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.TDAT.[1],437997,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.TDAT.[2],437998,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.TDAT.[3],437999,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.TDAT.[4],438000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_1C.TDAT.[5],438001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.RSCTTime.[0],438068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.RSCTTime.[1],438069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.RSCTTime.[2],438070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.RSCTTime.[3],438071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.RSCTTime.[4],438072,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.RSCTTime.[5],438073,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2A.TDAT.[0],438076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.TDAT.[1],438077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.TDAT.[2],438078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.TDAT.[3],438079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.TDAT.[4],438080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2A.TDAT.[5],438081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.RSCTTime.[0],438148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.RSCTTime.[1],438149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.RSCTTime.[2],438150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.RSCTTime.[3],438151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.RSCTTime.[4],438152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.RSCTTime.[5],438153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_2C.TDAT.[0],438156,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.TDAT.[1],438157,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.TDAT.[2],438158,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.TDAT.[3],438159,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.TDAT.[4],438160,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_2C.TDAT.[5],438161,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.RSCTTime.[0],438228,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.RSCTTime.[1],438229,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.RSCTTime.[2],438230,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.RSCTTime.[3],438231,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.RSCTTime.[4],438232,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.RSCTTime.[5],438233,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3A.TDAT.[0],438236,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.TDAT.[1],438237,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.TDAT.[2],438238,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.TDAT.[3],438239,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.TDAT.[4],438240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3A.TDAT.[5],438241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.RSCTTime.[0],438308,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.RSCTTime.[1],438309,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.RSCTTime.[2],438310,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.RSCTTime.[3],438311,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.RSCTTime.[4],438312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.RSCTTime.[5],438313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3C.TDAT.[0],438316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.TDAT.[1],438317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.TDAT.[2],438318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.TDAT.[3],438319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.TDAT.[4],438320,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3C.TDAT.[5],438321,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.RSCTTime.[0],438388,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.RSCTTime.[1],438389,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.RSCTTime.[2],438390,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.RSCTTime.[3],438391,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.RSCTTime.[4],438392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.RSCTTime.[5],438393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_3D.TDAT.[0],438396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.TDAT.[1],438397,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.TDAT.[2],438398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.TDAT.[3],438399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.TDAT.[4],438400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_3D.TDAT.[5],438401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.RSCTTime.[0],438468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.RSCTTime.[1],438469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.RSCTTime.[2],438470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.RSCTTime.[3],438471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.RSCTTime.[4],438472,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.RSCTTime.[5],438473,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4A.TDAT.[0],438476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.TDAT.[1],438477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.TDAT.[2],438478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.TDAT.[3],438479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.TDAT.[4],438480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4A.TDAT.[5],438481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.RSCTTime.[0],438548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.RSCTTime.[1],438549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.RSCTTime.[2],438550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.RSCTTime.[3],438551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.RSCTTime.[4],438552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.RSCTTime.[5],438553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4C.TDAT.[0],438556,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.TDAT.[1],438557,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.TDAT.[2],438558,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.TDAT.[3],438559,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.TDAT.[4],438560,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4C.TDAT.[5],438561,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.RSCTTime.[0],438628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.RSCTTime.[1],438629,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.RSCTTime.[2],438630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.RSCTTime.[3],438631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.RSCTTime.[4],438632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.RSCTTime.[5],438633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_4D.TDAT.[0],438636,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.TDAT.[1],438637,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.TDAT.[2],438638,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.TDAT.[3],438639,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.TDAT.[4],438640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_4D.TDAT.[5],438641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.RSCTTime.[0],438708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.RSCTTime.[1],438709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.RSCTTime.[2],438710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.RSCTTime.[3],438711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.RSCTTime.[4],438712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.RSCTTime.[5],438713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5A.TDAT.[0],438716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.TDAT.[1],438717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.TDAT.[2],438718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.TDAT.[3],438719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.TDAT.[4],438720,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5A.TDAT.[5],438721,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.RSCTTime.[0],438788,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.RSCTTime.[1],438789,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.RSCTTime.[2],438790,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.RSCTTime.[3],438791,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.RSCTTime.[4],438792,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.RSCTTime.[5],438793,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5C.TDAT.[0],438796,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.TDAT.[1],438797,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.TDAT.[2],438798,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.TDAT.[3],438799,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.TDAT.[4],438800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5C.TDAT.[5],438801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.RSCTTime.[0],438868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.RSCTTime.[1],438869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.RSCTTime.[2],438870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.RSCTTime.[3],438871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.RSCTTime.[4],438872,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.RSCTTime.[5],438873,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_5D.TDAT.[0],438876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.TDAT.[1],438877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.TDAT.[2],438878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.TDAT.[3],438879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.TDAT.[4],438880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_5D.TDAT.[5],438881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.RSCTTime.[0],438948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.RSCTTime.[1],438949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.RSCTTime.[2],438950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.RSCTTime.[3],438951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.RSCTTime.[4],438952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.RSCTTime.[5],438953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6A.TDAT.[0],438956,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.TDAT.[1],438957,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.TDAT.[2],438958,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.TDAT.[3],438959,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.TDAT.[4],438960,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6A.TDAT.[5],438961,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.RSCTTime.[0],439028,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.RSCTTime.[1],439029,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.RSCTTime.[2],439030,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.RSCTTime.[3],439031,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.RSCTTime.[4],439032,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.RSCTTime.[5],439033,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6C.TDAT.[0],439036,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.TDAT.[1],439037,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.TDAT.[2],439038,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.TDAT.[3],439039,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.TDAT.[4],439040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6C.TDAT.[5],439041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.RSCTTime.[0],439108,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.RSCTTime.[1],439109,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.RSCTTime.[2],439110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.RSCTTime.[3],439111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.RSCTTime.[4],439112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.RSCTTime.[5],439113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_6D.TDAT.[0],439116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.TDAT.[1],439117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.TDAT.[2],439118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.TDAT.[3],439119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.TDAT.[4],439120,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_6D.TDAT.[5],439121,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.RSCTTime.[0],439188,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.RSCTTime.[1],439189,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.RSCTTime.[2],439190,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.RSCTTime.[3],439191,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.RSCTTime.[4],439192,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.RSCTTime.[5],439193,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7A.TDAT.[0],439196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.TDAT.[1],439197,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.TDAT.[2],439198,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.TDAT.[3],439199,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.TDAT.[4],439200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7A.TDAT.[5],439201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.RSCTTime.[0],439268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.RSCTTime.[1],439269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.RSCTTime.[2],439270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.RSCTTime.[3],439271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.RSCTTime.[4],439272,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.RSCTTime.[5],439273,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7C.TDAT.[0],439276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.TDAT.[1],439277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.TDAT.[2],439278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.TDAT.[3],439279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.TDAT.[4],439280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7C.TDAT.[5],439281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.RSCTTime.[0],439348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.RSCTTime.[1],439349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.RSCTTime.[2],439350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.RSCTTime.[3],439351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.RSCTTime.[4],439352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.RSCTTime.[5],439353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_7D.TDAT.[0],439356,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.TDAT.[1],439357,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.TDAT.[2],439358,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.TDAT.[3],439359,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.TDAT.[4],439360,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_7D.TDAT.[5],439361,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.RSCTTime.[0],439428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.RSCTTime.[1],439429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.RSCTTime.[2],439430,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.RSCTTime.[3],439431,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.RSCTTime.[4],439432,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.RSCTTime.[5],439433,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8A.TDAT.[0],439436,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.TDAT.[1],439437,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.TDAT.[2],439438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.TDAT.[3],439439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.TDAT.[4],439440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8A.TDAT.[5],439441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.RSCTTime.[0],439508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.RSCTTime.[1],439509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.RSCTTime.[2],439510,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.RSCTTime.[3],439511,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.RSCTTime.[4],439512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.RSCTTime.[5],439513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8C.TDAT.[0],439516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.TDAT.[1],439517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.TDAT.[2],439518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.TDAT.[3],439519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.TDAT.[4],439520,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8C.TDAT.[5],439521,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.RSCTTime.[0],439588,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.RSCTTime.[1],439589,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.RSCTTime.[2],439590,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.RSCTTime.[3],439591,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.RSCTTime.[4],439592,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.RSCTTime.[5],439593,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_8D.TDAT.[0],439596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.TDAT.[1],439597,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.TDAT.[2],439598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.TDAT.[3],439599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.TDAT.[4],439600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_8D.TDAT.[5],439601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.RSCTTime.[0],439668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.RSCTTime.[1],439669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.RSCTTime.[2],439670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.RSCTTime.[3],439671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.RSCTTime.[4],439672,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.RSCTTime.[5],439673,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9A.TDAT.[0],439676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.TDAT.[1],439677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.TDAT.[2],439678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.TDAT.[3],439679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.TDAT.[4],439680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9A.TDAT.[5],439681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.RSCTTime.[0],439748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.RSCTTime.[1],439749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.RSCTTime.[2],439750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.RSCTTime.[3],439751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.RSCTTime.[4],439752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.RSCTTime.[5],439753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0103_9C.TDAT.[0],439756,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.TDAT.[1],439757,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.TDAT.[2],439758,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.TDAT.[3],439759,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.TDAT.[4],439760,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0103_9C.TDAT.[5],439761,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.RSCTTime.[0],439828,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.RSCTTime.[1],439829,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.RSCTTime.[2],439830,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.RSCTTime.[3],439831,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.RSCTTime.[4],439832,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.RSCTTime.[5],439833,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2A.TDAT.[0],439836,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.TDAT.[1],439837,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.TDAT.[2],439838,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.TDAT.[3],439839,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.TDAT.[4],439840,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2A.TDAT.[5],439841,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.RSCTTime.[0],439908,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.RSCTTime.[1],439909,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.RSCTTime.[2],439910,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.RSCTTime.[3],439911,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.RSCTTime.[4],439912,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.RSCTTime.[5],439913,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2B.TDAT.[0],439916,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.TDAT.[1],439917,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.TDAT.[2],439918,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.TDAT.[3],439919,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.TDAT.[4],439920,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2B.TDAT.[5],439921,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.RSCTTime.[0],439988,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.RSCTTime.[1],439989,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.RSCTTime.[2],439990,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.RSCTTime.[3],439991,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.RSCTTime.[4],439992,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.RSCTTime.[5],439993,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2C.TDAT.[0],439996,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.TDAT.[1],439997,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.TDAT.[2],439998,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.TDAT.[3],439999,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.TDAT.[4],440000,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2C.TDAT.[5],440001,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.RSCTTime.[0],440068,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.RSCTTime.[1],440069,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.RSCTTime.[2],440070,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.RSCTTime.[3],440071,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.RSCTTime.[4],440072,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.RSCTTime.[5],440073,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Last Time Valve Cycle Count was Reset" WA3252_FV_0113_2D.TDAT.[0],440076,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.TDAT.[1],440077,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.TDAT.[2],440078,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.TDAT.[3],440079,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.TDAT.[4],440080,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_FV_0113_2D.TDAT.[5],440081,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Date Last Run for HMI display" WA3252_AFD_0103_1_SI.almHighHigh.BOOLS1,401040,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almHighHigh.BOOLS2,401041,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almHighHigh.AEBOOLS,401042,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almHighHigh.INT1,401043,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almHighHigh.INT2,401044,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almHighHigh.AENotify,401045,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almHighHigh.AESeverity,401046,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almHighHigh.AEShelveDuration,401047,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almHigh.BOOLS1,401052,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almHigh.BOOLS2,401053,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almHigh.AEBOOLS,401054,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almHigh.INT1,401055,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almHigh.INT2,401056,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almHigh.AENotify,401057,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almHigh.AESeverity,401058,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almHigh.AEShelveDuration,401059,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almLow.BOOLS1,401064,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almLow.BOOLS2,401065,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almLow.AEBOOLS,401066,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almLow.INT1,401067,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almLow.INT2,401068,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almLow.AENotify,401069,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almLow.AESeverity,401070,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almLow.AEShelveDuration,401071,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almLowLow.BOOLS1,401076,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almLowLow.BOOLS2,401077,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almLowLow.AEBOOLS,401078,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almLowLow.INT1,401079,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almLowLow.INT2,401080,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almLowLow.AENotify,401081,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almLowLow.AESeverity,401082,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almLowLow.AEShelveDuration,401083,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almBrokenLoop.BOOLS1,401088,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almBrokenLoop.BOOLS2,401089,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almBrokenLoop.AEBOOLS,401090,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almBrokenLoop.INT1,401091,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almBrokenLoop.INT2,401092,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almBrokenLoop.AENotify,401093,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almBrokenLoop.AESeverity,401094,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almBrokenLoop.AEShelveDuration,401095,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almOverRange.BOOLS1,401100,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almOverRange.BOOLS2,401101,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almOverRange.AEBOOLS,401102,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almOverRange.INT1,401103,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almOverRange.INT2,401104,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almOverRange.AENotify,401105,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almOverRange.AESeverity,401106,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almOverRange.AEShelveDuration,401107,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almUnderRange.BOOLS1,401112,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almUnderRange.BOOLS2,401113,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almUnderRange.AEBOOLS,401114,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almUnderRange.INT1,401115,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almUnderRange.INT2,401116,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almUnderRange.AENotify,401117,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almUnderRange.AESeverity,401118,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almUnderRange.AEShelveDuration,401119,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almRateOfChange.BOOLS1,401124,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almRateOfChange.BOOLS2,401125,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almRateOfChange.AEBOOLS,401126,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almRateOfChange.INT1,401127,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almRateOfChange.INT2,401128,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almRateOfChange.AENotify,401129,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almRateOfChange.AESeverity,401130,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almRateOfChange.AEShelveDuration,401131,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.almPLCFault.BOOLS1,401136,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_SI.almPLCFault.BOOLS2,401137,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_SI.almPLCFault.AEBOOLS,401138,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_SI.almPLCFault.INT1,401139,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almPLCFault.INT2,401140,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_SI.almPLCFault.AENotify,401141,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_SI.almPLCFault.AESeverity,401142,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_SI.almPLCFault.AEShelveDuration,401143,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almHighHigh.BOOLS1,401240,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almHighHigh.BOOLS2,401241,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almHighHigh.AEBOOLS,401242,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almHighHigh.INT1,401243,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almHighHigh.INT2,401244,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almHighHigh.AENotify,401245,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almHighHigh.AESeverity,401246,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almHighHigh.AEShelveDuration,401247,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almHigh.BOOLS1,401252,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almHigh.BOOLS2,401253,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almHigh.AEBOOLS,401254,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almHigh.INT1,401255,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almHigh.INT2,401256,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almHigh.AENotify,401257,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almHigh.AESeverity,401258,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almHigh.AEShelveDuration,401259,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almLow.BOOLS1,401264,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almLow.BOOLS2,401265,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almLow.AEBOOLS,401266,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almLow.INT1,401267,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almLow.INT2,401268,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almLow.AENotify,401269,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almLow.AESeverity,401270,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almLow.AEShelveDuration,401271,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almLowLow.BOOLS1,401276,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almLowLow.BOOLS2,401277,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almLowLow.AEBOOLS,401278,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almLowLow.INT1,401279,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almLowLow.INT2,401280,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almLowLow.AENotify,401281,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almLowLow.AESeverity,401282,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almLowLow.AEShelveDuration,401283,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almBrokenLoop.BOOLS1,401288,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almBrokenLoop.BOOLS2,401289,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almBrokenLoop.AEBOOLS,401290,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almBrokenLoop.INT1,401291,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almBrokenLoop.INT2,401292,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almBrokenLoop.AENotify,401293,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almBrokenLoop.AESeverity,401294,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almBrokenLoop.AEShelveDuration,401295,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almOverRange.BOOLS1,401300,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almOverRange.BOOLS2,401301,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almOverRange.AEBOOLS,401302,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almOverRange.INT1,401303,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almOverRange.INT2,401304,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almOverRange.AENotify,401305,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almOverRange.AESeverity,401306,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almOverRange.AEShelveDuration,401307,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almUnderRange.BOOLS1,401312,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almUnderRange.BOOLS2,401313,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almUnderRange.AEBOOLS,401314,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almUnderRange.INT1,401315,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almUnderRange.INT2,401316,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almUnderRange.AENotify,401317,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almUnderRange.AESeverity,401318,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almUnderRange.AEShelveDuration,401319,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almRateOfChange.BOOLS1,401324,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almRateOfChange.BOOLS2,401325,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almRateOfChange.AEBOOLS,401326,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almRateOfChange.INT1,401327,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almRateOfChange.INT2,401328,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almRateOfChange.AENotify,401329,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almRateOfChange.AESeverity,401330,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almRateOfChange.AEShelveDuration,401331,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_SI.almPLCFault.BOOLS1,401336,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_SI.almPLCFault.BOOLS2,401337,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_SI.almPLCFault.AEBOOLS,401338,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_SI.almPLCFault.INT1,401339,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almPLCFault.INT2,401340,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_SI.almPLCFault.AENotify,401341,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_SI.almPLCFault.AESeverity,401342,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_SI.almPLCFault.AEShelveDuration,401343,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almHighHigh.BOOLS1,401440,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almHighHigh.BOOLS2,401441,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almHighHigh.AEBOOLS,401442,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almHighHigh.INT1,401443,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almHighHigh.INT2,401444,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almHighHigh.AENotify,401445,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almHighHigh.AESeverity,401446,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almHighHigh.AEShelveDuration,401447,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almHigh.BOOLS1,401452,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almHigh.BOOLS2,401453,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almHigh.AEBOOLS,401454,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almHigh.INT1,401455,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almHigh.INT2,401456,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almHigh.AENotify,401457,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almHigh.AESeverity,401458,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almHigh.AEShelveDuration,401459,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almLow.BOOLS1,401464,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almLow.BOOLS2,401465,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almLow.AEBOOLS,401466,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almLow.INT1,401467,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almLow.INT2,401468,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almLow.AENotify,401469,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almLow.AESeverity,401470,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almLow.AEShelveDuration,401471,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almLowLow.BOOLS1,401476,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almLowLow.BOOLS2,401477,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almLowLow.AEBOOLS,401478,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almLowLow.INT1,401479,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almLowLow.INT2,401480,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almLowLow.AENotify,401481,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almLowLow.AESeverity,401482,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almLowLow.AEShelveDuration,401483,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almBrokenLoop.BOOLS1,401488,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almBrokenLoop.BOOLS2,401489,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almBrokenLoop.AEBOOLS,401490,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almBrokenLoop.INT1,401491,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almBrokenLoop.INT2,401492,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almBrokenLoop.AENotify,401493,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almBrokenLoop.AESeverity,401494,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almBrokenLoop.AEShelveDuration,401495,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almOverRange.BOOLS1,401500,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almOverRange.BOOLS2,401501,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almOverRange.AEBOOLS,401502,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almOverRange.INT1,401503,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almOverRange.INT2,401504,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almOverRange.AENotify,401505,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almOverRange.AESeverity,401506,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almOverRange.AEShelveDuration,401507,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almUnderRange.BOOLS1,401512,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almUnderRange.BOOLS2,401513,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almUnderRange.AEBOOLS,401514,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almUnderRange.INT1,401515,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almUnderRange.INT2,401516,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almUnderRange.AENotify,401517,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almUnderRange.AESeverity,401518,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almUnderRange.AEShelveDuration,401519,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almRateOfChange.BOOLS1,401524,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almRateOfChange.BOOLS2,401525,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almRateOfChange.AEBOOLS,401526,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almRateOfChange.INT1,401527,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almRateOfChange.INT2,401528,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almRateOfChange.AENotify,401529,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almRateOfChange.AESeverity,401530,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almRateOfChange.AEShelveDuration,401531,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_SI.almPLCFault.BOOLS1,401536,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_SI.almPLCFault.BOOLS2,401537,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_SI.almPLCFault.AEBOOLS,401538,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_SI.almPLCFault.INT1,401539,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almPLCFault.INT2,401540,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_SI.almPLCFault.AENotify,401541,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_SI.almPLCFault.AESeverity,401542,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_SI.almPLCFault.AEShelveDuration,401543,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almHighHigh.BOOLS1,401640,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almHighHigh.BOOLS2,401641,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almHighHigh.AEBOOLS,401642,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almHighHigh.INT1,401643,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almHighHigh.INT2,401644,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almHighHigh.AENotify,401645,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almHighHigh.AESeverity,401646,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almHighHigh.AEShelveDuration,401647,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almHigh.BOOLS1,401652,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almHigh.BOOLS2,401653,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almHigh.AEBOOLS,401654,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almHigh.INT1,401655,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almHigh.INT2,401656,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almHigh.AENotify,401657,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almHigh.AESeverity,401658,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almHigh.AEShelveDuration,401659,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almLow.BOOLS1,401664,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almLow.BOOLS2,401665,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almLow.AEBOOLS,401666,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almLow.INT1,401667,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almLow.INT2,401668,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almLow.AENotify,401669,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almLow.AESeverity,401670,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almLow.AEShelveDuration,401671,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almLowLow.BOOLS1,401676,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almLowLow.BOOLS2,401677,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almLowLow.AEBOOLS,401678,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almLowLow.INT1,401679,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almLowLow.INT2,401680,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almLowLow.AENotify,401681,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almLowLow.AESeverity,401682,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almLowLow.AEShelveDuration,401683,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almBrokenLoop.BOOLS1,401688,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almBrokenLoop.BOOLS2,401689,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almBrokenLoop.AEBOOLS,401690,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almBrokenLoop.INT1,401691,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almBrokenLoop.INT2,401692,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almBrokenLoop.AENotify,401693,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almBrokenLoop.AESeverity,401694,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almBrokenLoop.AEShelveDuration,401695,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almOverRange.BOOLS1,401700,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almOverRange.BOOLS2,401701,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almOverRange.AEBOOLS,401702,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almOverRange.INT1,401703,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almOverRange.INT2,401704,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almOverRange.AENotify,401705,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almOverRange.AESeverity,401706,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almOverRange.AEShelveDuration,401707,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almUnderRange.BOOLS1,401712,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almUnderRange.BOOLS2,401713,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almUnderRange.AEBOOLS,401714,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almUnderRange.INT1,401715,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almUnderRange.INT2,401716,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almUnderRange.AENotify,401717,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almUnderRange.AESeverity,401718,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almUnderRange.AEShelveDuration,401719,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almRateOfChange.BOOLS1,401724,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almRateOfChange.BOOLS2,401725,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almRateOfChange.AEBOOLS,401726,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almRateOfChange.INT1,401727,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almRateOfChange.INT2,401728,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almRateOfChange.AENotify,401729,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almRateOfChange.AESeverity,401730,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almRateOfChange.AEShelveDuration,401731,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_SI.almPLCFault.BOOLS1,401736,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_SI.almPLCFault.BOOLS2,401737,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_SI.almPLCFault.AEBOOLS,401738,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_SI.almPLCFault.INT1,401739,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almPLCFault.INT2,401740,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_SI.almPLCFault.AENotify,401741,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_SI.almPLCFault.AESeverity,401742,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_SI.almPLCFault.AEShelveDuration,401743,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almHighHigh.BOOLS1,401840,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almHighHigh.BOOLS2,401841,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almHighHigh.AEBOOLS,401842,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almHighHigh.INT1,401843,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almHighHigh.INT2,401844,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almHighHigh.AENotify,401845,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almHighHigh.AESeverity,401846,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almHighHigh.AEShelveDuration,401847,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almHigh.BOOLS1,401852,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almHigh.BOOLS2,401853,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almHigh.AEBOOLS,401854,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almHigh.INT1,401855,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almHigh.INT2,401856,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almHigh.AENotify,401857,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almHigh.AESeverity,401858,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almHigh.AEShelveDuration,401859,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almLow.BOOLS1,401864,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almLow.BOOLS2,401865,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almLow.AEBOOLS,401866,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almLow.INT1,401867,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almLow.INT2,401868,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almLow.AENotify,401869,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almLow.AESeverity,401870,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almLow.AEShelveDuration,401871,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almLowLow.BOOLS1,401876,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almLowLow.BOOLS2,401877,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almLowLow.AEBOOLS,401878,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almLowLow.INT1,401879,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almLowLow.INT2,401880,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almLowLow.AENotify,401881,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almLowLow.AESeverity,401882,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almLowLow.AEShelveDuration,401883,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almBrokenLoop.BOOLS1,401888,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almBrokenLoop.BOOLS2,401889,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almBrokenLoop.AEBOOLS,401890,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almBrokenLoop.INT1,401891,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almBrokenLoop.INT2,401892,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almBrokenLoop.AENotify,401893,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almBrokenLoop.AESeverity,401894,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almBrokenLoop.AEShelveDuration,401895,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almOverRange.BOOLS1,401900,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almOverRange.BOOLS2,401901,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almOverRange.AEBOOLS,401902,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almOverRange.INT1,401903,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almOverRange.INT2,401904,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almOverRange.AENotify,401905,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almOverRange.AESeverity,401906,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almOverRange.AEShelveDuration,401907,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almUnderRange.BOOLS1,401912,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almUnderRange.BOOLS2,401913,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almUnderRange.AEBOOLS,401914,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almUnderRange.INT1,401915,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almUnderRange.INT2,401916,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almUnderRange.AENotify,401917,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almUnderRange.AESeverity,401918,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almUnderRange.AEShelveDuration,401919,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almRateOfChange.BOOLS1,401924,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almRateOfChange.BOOLS2,401925,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almRateOfChange.AEBOOLS,401926,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almRateOfChange.INT1,401927,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almRateOfChange.INT2,401928,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almRateOfChange.AENotify,401929,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almRateOfChange.AESeverity,401930,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almRateOfChange.AEShelveDuration,401931,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_SI.almPLCFault.BOOLS1,401936,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_SI.almPLCFault.BOOLS2,401937,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_SI.almPLCFault.AEBOOLS,401938,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_SI.almPLCFault.INT1,401939,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almPLCFault.INT2,401940,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_SI.almPLCFault.AENotify,401941,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_SI.almPLCFault.AESeverity,401942,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_SI.almPLCFault.AEShelveDuration,401943,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almHighHigh.BOOLS1,402040,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almHighHigh.BOOLS2,402041,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almHighHigh.AEBOOLS,402042,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almHighHigh.INT1,402043,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almHighHigh.INT2,402044,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almHighHigh.AENotify,402045,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almHighHigh.AESeverity,402046,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almHighHigh.AEShelveDuration,402047,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almHigh.BOOLS1,402052,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almHigh.BOOLS2,402053,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almHigh.AEBOOLS,402054,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almHigh.INT1,402055,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almHigh.INT2,402056,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almHigh.AENotify,402057,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almHigh.AESeverity,402058,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almHigh.AEShelveDuration,402059,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almLow.BOOLS1,402064,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almLow.BOOLS2,402065,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almLow.AEBOOLS,402066,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almLow.INT1,402067,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almLow.INT2,402068,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almLow.AENotify,402069,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almLow.AESeverity,402070,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almLow.AEShelveDuration,402071,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almLowLow.BOOLS1,402076,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almLowLow.BOOLS2,402077,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almLowLow.AEBOOLS,402078,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almLowLow.INT1,402079,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almLowLow.INT2,402080,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almLowLow.AENotify,402081,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almLowLow.AESeverity,402082,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almLowLow.AEShelveDuration,402083,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almBrokenLoop.BOOLS1,402088,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almBrokenLoop.BOOLS2,402089,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almBrokenLoop.AEBOOLS,402090,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almBrokenLoop.INT1,402091,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almBrokenLoop.INT2,402092,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almBrokenLoop.AENotify,402093,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almBrokenLoop.AESeverity,402094,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almBrokenLoop.AEShelveDuration,402095,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almOverRange.BOOLS1,402100,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almOverRange.BOOLS2,402101,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almOverRange.AEBOOLS,402102,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almOverRange.INT1,402103,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almOverRange.INT2,402104,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almOverRange.AENotify,402105,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almOverRange.AESeverity,402106,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almOverRange.AEShelveDuration,402107,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almUnderRange.BOOLS1,402112,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almUnderRange.BOOLS2,402113,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almUnderRange.AEBOOLS,402114,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almUnderRange.INT1,402115,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almUnderRange.INT2,402116,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almUnderRange.AENotify,402117,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almUnderRange.AESeverity,402118,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almUnderRange.AEShelveDuration,402119,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almRateOfChange.BOOLS1,402124,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almRateOfChange.BOOLS2,402125,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almRateOfChange.AEBOOLS,402126,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almRateOfChange.INT1,402127,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almRateOfChange.INT2,402128,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almRateOfChange.AENotify,402129,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almRateOfChange.AESeverity,402130,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almRateOfChange.AEShelveDuration,402131,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_SI.almPLCFault.BOOLS1,402136,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_SI.almPLCFault.BOOLS2,402137,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_SI.almPLCFault.AEBOOLS,402138,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_SI.almPLCFault.INT1,402139,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almPLCFault.INT2,402140,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_SI.almPLCFault.AENotify,402141,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_SI.almPLCFault.AESeverity,402142,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_SI.almPLCFault.AEShelveDuration,402143,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almHighHigh.BOOLS1,402240,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almHighHigh.BOOLS2,402241,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almHighHigh.AEBOOLS,402242,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almHighHigh.INT1,402243,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almHighHigh.INT2,402244,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almHighHigh.AENotify,402245,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almHighHigh.AESeverity,402246,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almHighHigh.AEShelveDuration,402247,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almHigh.BOOLS1,402252,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almHigh.BOOLS2,402253,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almHigh.AEBOOLS,402254,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almHigh.INT1,402255,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almHigh.INT2,402256,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almHigh.AENotify,402257,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almHigh.AESeverity,402258,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almHigh.AEShelveDuration,402259,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almLow.BOOLS1,402264,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almLow.BOOLS2,402265,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almLow.AEBOOLS,402266,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almLow.INT1,402267,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almLow.INT2,402268,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almLow.AENotify,402269,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almLow.AESeverity,402270,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almLow.AEShelveDuration,402271,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almLowLow.BOOLS1,402276,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almLowLow.BOOLS2,402277,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almLowLow.AEBOOLS,402278,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almLowLow.INT1,402279,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almLowLow.INT2,402280,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almLowLow.AENotify,402281,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almLowLow.AESeverity,402282,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almLowLow.AEShelveDuration,402283,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almBrokenLoop.BOOLS1,402288,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almBrokenLoop.BOOLS2,402289,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almBrokenLoop.AEBOOLS,402290,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almBrokenLoop.INT1,402291,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almBrokenLoop.INT2,402292,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almBrokenLoop.AENotify,402293,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almBrokenLoop.AESeverity,402294,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almBrokenLoop.AEShelveDuration,402295,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almOverRange.BOOLS1,402300,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almOverRange.BOOLS2,402301,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almOverRange.AEBOOLS,402302,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almOverRange.INT1,402303,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almOverRange.INT2,402304,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almOverRange.AENotify,402305,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almOverRange.AESeverity,402306,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almOverRange.AEShelveDuration,402307,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almUnderRange.BOOLS1,402312,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almUnderRange.BOOLS2,402313,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almUnderRange.AEBOOLS,402314,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almUnderRange.INT1,402315,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almUnderRange.INT2,402316,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almUnderRange.AENotify,402317,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almUnderRange.AESeverity,402318,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almUnderRange.AEShelveDuration,402319,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almRateOfChange.BOOLS1,402324,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almRateOfChange.BOOLS2,402325,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almRateOfChange.AEBOOLS,402326,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almRateOfChange.INT1,402327,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almRateOfChange.INT2,402328,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almRateOfChange.AENotify,402329,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almRateOfChange.AESeverity,402330,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almRateOfChange.AEShelveDuration,402331,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_SI.almPLCFault.BOOLS1,402336,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_SI.almPLCFault.BOOLS2,402337,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_SI.almPLCFault.AEBOOLS,402338,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_SI.almPLCFault.INT1,402339,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almPLCFault.INT2,402340,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_SI.almPLCFault.AENotify,402341,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_SI.almPLCFault.AESeverity,402342,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_SI.almPLCFault.AEShelveDuration,402343,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almHighHigh.BOOLS1,402440,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almHighHigh.BOOLS2,402441,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almHighHigh.AEBOOLS,402442,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almHighHigh.INT1,402443,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almHighHigh.INT2,402444,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almHighHigh.AENotify,402445,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almHighHigh.AESeverity,402446,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almHighHigh.AEShelveDuration,402447,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almHigh.BOOLS1,402452,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almHigh.BOOLS2,402453,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almHigh.AEBOOLS,402454,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almHigh.INT1,402455,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almHigh.INT2,402456,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almHigh.AENotify,402457,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almHigh.AESeverity,402458,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almHigh.AEShelveDuration,402459,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almLow.BOOLS1,402464,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almLow.BOOLS2,402465,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almLow.AEBOOLS,402466,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almLow.INT1,402467,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almLow.INT2,402468,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almLow.AENotify,402469,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almLow.AESeverity,402470,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almLow.AEShelveDuration,402471,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almLowLow.BOOLS1,402476,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almLowLow.BOOLS2,402477,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almLowLow.AEBOOLS,402478,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almLowLow.INT1,402479,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almLowLow.INT2,402480,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almLowLow.AENotify,402481,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almLowLow.AESeverity,402482,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almLowLow.AEShelveDuration,402483,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almBrokenLoop.BOOLS1,402488,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almBrokenLoop.BOOLS2,402489,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almBrokenLoop.AEBOOLS,402490,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almBrokenLoop.INT1,402491,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almBrokenLoop.INT2,402492,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almBrokenLoop.AENotify,402493,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almBrokenLoop.AESeverity,402494,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almBrokenLoop.AEShelveDuration,402495,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almOverRange.BOOLS1,402500,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almOverRange.BOOLS2,402501,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almOverRange.AEBOOLS,402502,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almOverRange.INT1,402503,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almOverRange.INT2,402504,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almOverRange.AENotify,402505,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almOverRange.AESeverity,402506,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almOverRange.AEShelveDuration,402507,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almUnderRange.BOOLS1,402512,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almUnderRange.BOOLS2,402513,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almUnderRange.AEBOOLS,402514,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almUnderRange.INT1,402515,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almUnderRange.INT2,402516,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almUnderRange.AENotify,402517,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almUnderRange.AESeverity,402518,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almUnderRange.AEShelveDuration,402519,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almRateOfChange.BOOLS1,402524,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almRateOfChange.BOOLS2,402525,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almRateOfChange.AEBOOLS,402526,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almRateOfChange.INT1,402527,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almRateOfChange.INT2,402528,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almRateOfChange.AENotify,402529,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almRateOfChange.AESeverity,402530,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almRateOfChange.AEShelveDuration,402531,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_SI.almPLCFault.BOOLS1,402536,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_SI.almPLCFault.BOOLS2,402537,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_SI.almPLCFault.AEBOOLS,402538,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_SI.almPLCFault.INT1,402539,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almPLCFault.INT2,402540,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_SI.almPLCFault.AENotify,402541,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_SI.almPLCFault.AESeverity,402542,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_SI.almPLCFault.AEShelveDuration,402543,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almHighHigh.BOOLS1,402640,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almHighHigh.BOOLS2,402641,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almHighHigh.AEBOOLS,402642,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almHighHigh.INT1,402643,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almHighHigh.INT2,402644,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almHighHigh.AENotify,402645,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almHighHigh.AESeverity,402646,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almHighHigh.AEShelveDuration,402647,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almHigh.BOOLS1,402652,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almHigh.BOOLS2,402653,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almHigh.AEBOOLS,402654,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almHigh.INT1,402655,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almHigh.INT2,402656,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almHigh.AENotify,402657,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almHigh.AESeverity,402658,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almHigh.AEShelveDuration,402659,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almLow.BOOLS1,402664,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almLow.BOOLS2,402665,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almLow.AEBOOLS,402666,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almLow.INT1,402667,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almLow.INT2,402668,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almLow.AENotify,402669,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almLow.AESeverity,402670,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almLow.AEShelveDuration,402671,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almLowLow.BOOLS1,402676,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almLowLow.BOOLS2,402677,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almLowLow.AEBOOLS,402678,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almLowLow.INT1,402679,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almLowLow.INT2,402680,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almLowLow.AENotify,402681,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almLowLow.AESeverity,402682,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almLowLow.AEShelveDuration,402683,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almBrokenLoop.BOOLS1,402688,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almBrokenLoop.BOOLS2,402689,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almBrokenLoop.AEBOOLS,402690,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almBrokenLoop.INT1,402691,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almBrokenLoop.INT2,402692,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almBrokenLoop.AENotify,402693,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almBrokenLoop.AESeverity,402694,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almBrokenLoop.AEShelveDuration,402695,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almOverRange.BOOLS1,402700,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almOverRange.BOOLS2,402701,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almOverRange.AEBOOLS,402702,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almOverRange.INT1,402703,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almOverRange.INT2,402704,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almOverRange.AENotify,402705,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almOverRange.AESeverity,402706,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almOverRange.AEShelveDuration,402707,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almUnderRange.BOOLS1,402712,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almUnderRange.BOOLS2,402713,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almUnderRange.AEBOOLS,402714,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almUnderRange.INT1,402715,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almUnderRange.INT2,402716,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almUnderRange.AENotify,402717,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almUnderRange.AESeverity,402718,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almUnderRange.AEShelveDuration,402719,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almRateOfChange.BOOLS1,402724,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almRateOfChange.BOOLS2,402725,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almRateOfChange.AEBOOLS,402726,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almRateOfChange.INT1,402727,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almRateOfChange.INT2,402728,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almRateOfChange.AENotify,402729,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almRateOfChange.AESeverity,402730,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almRateOfChange.AEShelveDuration,402731,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_SI.almPLCFault.BOOLS1,402736,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_SI.almPLCFault.BOOLS2,402737,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_SI.almPLCFault.AEBOOLS,402738,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_SI.almPLCFault.INT1,402739,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almPLCFault.INT2,402740,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_SI.almPLCFault.AENotify,402741,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_SI.almPLCFault.AESeverity,402742,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_SI.almPLCFault.AEShelveDuration,402743,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almHighHigh.BOOLS1,402840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almHighHigh.BOOLS2,402841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almHighHigh.AEBOOLS,402842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almHighHigh.INT1,402843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almHighHigh.INT2,402844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almHighHigh.AENotify,402845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almHighHigh.AESeverity,402846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almHighHigh.AEShelveDuration,402847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almHigh.BOOLS1,402852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almHigh.BOOLS2,402853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almHigh.AEBOOLS,402854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almHigh.INT1,402855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almHigh.INT2,402856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almHigh.AENotify,402857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almHigh.AESeverity,402858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almHigh.AEShelveDuration,402859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almLow.BOOLS1,402864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almLow.BOOLS2,402865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almLow.AEBOOLS,402866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almLow.INT1,402867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almLow.INT2,402868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almLow.AENotify,402869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almLow.AESeverity,402870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almLow.AEShelveDuration,402871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almLowLow.BOOLS1,402876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almLowLow.BOOLS2,402877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almLowLow.AEBOOLS,402878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almLowLow.INT1,402879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almLowLow.INT2,402880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almLowLow.AENotify,402881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almLowLow.AESeverity,402882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almLowLow.AEShelveDuration,402883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almBrokenLoop.BOOLS1,402888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almBrokenLoop.BOOLS2,402889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almBrokenLoop.AEBOOLS,402890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almBrokenLoop.INT1,402891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almBrokenLoop.INT2,402892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almBrokenLoop.AENotify,402893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almBrokenLoop.AESeverity,402894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almBrokenLoop.AEShelveDuration,402895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almOverRange.BOOLS1,402900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almOverRange.BOOLS2,402901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almOverRange.AEBOOLS,402902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almOverRange.INT1,402903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almOverRange.INT2,402904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almOverRange.AENotify,402905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almOverRange.AESeverity,402906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almOverRange.AEShelveDuration,402907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almUnderRange.BOOLS1,402912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almUnderRange.BOOLS2,402913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almUnderRange.AEBOOLS,402914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almUnderRange.INT1,402915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almUnderRange.INT2,402916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almUnderRange.AENotify,402917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almUnderRange.AESeverity,402918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almUnderRange.AEShelveDuration,402919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almRateOfChange.BOOLS1,402924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almRateOfChange.BOOLS2,402925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almRateOfChange.AEBOOLS,402926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almRateOfChange.INT1,402927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almRateOfChange.INT2,402928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almRateOfChange.AENotify,402929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almRateOfChange.AESeverity,402930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almRateOfChange.AEShelveDuration,402931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI1.almPLCFault.BOOLS1,402936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI1.almPLCFault.BOOLS2,402937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI1.almPLCFault.AEBOOLS,402938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI1.almPLCFault.INT1,402939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almPLCFault.INT2,402940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI1.almPLCFault.AENotify,402941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI1.almPLCFault.AESeverity,402942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI1.almPLCFault.AEShelveDuration,402943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almHighHigh.BOOLS1,403040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almHighHigh.BOOLS2,403041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almHighHigh.AEBOOLS,403042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almHighHigh.INT1,403043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almHighHigh.INT2,403044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almHighHigh.AENotify,403045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almHighHigh.AESeverity,403046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almHighHigh.AEShelveDuration,403047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almHigh.BOOLS1,403052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almHigh.BOOLS2,403053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almHigh.AEBOOLS,403054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almHigh.INT1,403055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almHigh.INT2,403056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almHigh.AENotify,403057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almHigh.AESeverity,403058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almHigh.AEShelveDuration,403059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almLow.BOOLS1,403064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almLow.BOOLS2,403065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almLow.AEBOOLS,403066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almLow.INT1,403067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almLow.INT2,403068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almLow.AENotify,403069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almLow.AESeverity,403070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almLow.AEShelveDuration,403071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almLowLow.BOOLS1,403076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almLowLow.BOOLS2,403077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almLowLow.AEBOOLS,403078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almLowLow.INT1,403079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almLowLow.INT2,403080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almLowLow.AENotify,403081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almLowLow.AESeverity,403082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almLowLow.AEShelveDuration,403083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almBrokenLoop.BOOLS1,403088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almBrokenLoop.BOOLS2,403089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almBrokenLoop.AEBOOLS,403090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almBrokenLoop.INT1,403091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almBrokenLoop.INT2,403092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almBrokenLoop.AENotify,403093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almBrokenLoop.AESeverity,403094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almBrokenLoop.AEShelveDuration,403095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almOverRange.BOOLS1,403100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almOverRange.BOOLS2,403101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almOverRange.AEBOOLS,403102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almOverRange.INT1,403103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almOverRange.INT2,403104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almOverRange.AENotify,403105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almOverRange.AESeverity,403106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almOverRange.AEShelveDuration,403107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almUnderRange.BOOLS1,403112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almUnderRange.BOOLS2,403113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almUnderRange.AEBOOLS,403114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almUnderRange.INT1,403115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almUnderRange.INT2,403116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almUnderRange.AENotify,403117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almUnderRange.AESeverity,403118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almUnderRange.AEShelveDuration,403119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almRateOfChange.BOOLS1,403124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almRateOfChange.BOOLS2,403125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almRateOfChange.AEBOOLS,403126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almRateOfChange.INT1,403127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almRateOfChange.INT2,403128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almRateOfChange.AENotify,403129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almRateOfChange.AESeverity,403130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almRateOfChange.AEShelveDuration,403131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI2.almPLCFault.BOOLS1,403136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI2.almPLCFault.BOOLS2,403137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI2.almPLCFault.AEBOOLS,403138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI2.almPLCFault.INT1,403139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almPLCFault.INT2,403140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI2.almPLCFault.AENotify,403141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI2.almPLCFault.AESeverity,403142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI2.almPLCFault.AEShelveDuration,403143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almHighHigh.BOOLS1,403240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almHighHigh.BOOLS2,403241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almHighHigh.AEBOOLS,403242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almHighHigh.INT1,403243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almHighHigh.INT2,403244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almHighHigh.AENotify,403245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almHighHigh.AESeverity,403246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almHighHigh.AEShelveDuration,403247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almHigh.BOOLS1,403252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almHigh.BOOLS2,403253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almHigh.AEBOOLS,403254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almHigh.INT1,403255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almHigh.INT2,403256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almHigh.AENotify,403257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almHigh.AESeverity,403258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almHigh.AEShelveDuration,403259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almLow.BOOLS1,403264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almLow.BOOLS2,403265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almLow.AEBOOLS,403266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almLow.INT1,403267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almLow.INT2,403268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almLow.AENotify,403269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almLow.AESeverity,403270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almLow.AEShelveDuration,403271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almLowLow.BOOLS1,403276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almLowLow.BOOLS2,403277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almLowLow.AEBOOLS,403278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almLowLow.INT1,403279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almLowLow.INT2,403280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almLowLow.AENotify,403281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almLowLow.AESeverity,403282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almLowLow.AEShelveDuration,403283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almBrokenLoop.BOOLS1,403288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almBrokenLoop.BOOLS2,403289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almBrokenLoop.AEBOOLS,403290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almBrokenLoop.INT1,403291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almBrokenLoop.INT2,403292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almBrokenLoop.AENotify,403293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almBrokenLoop.AESeverity,403294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almBrokenLoop.AEShelveDuration,403295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almOverRange.BOOLS1,403300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almOverRange.BOOLS2,403301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almOverRange.AEBOOLS,403302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almOverRange.INT1,403303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almOverRange.INT2,403304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almOverRange.AENotify,403305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almOverRange.AESeverity,403306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almOverRange.AEShelveDuration,403307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almUnderRange.BOOLS1,403312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almUnderRange.BOOLS2,403313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almUnderRange.AEBOOLS,403314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almUnderRange.INT1,403315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almUnderRange.INT2,403316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almUnderRange.AENotify,403317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almUnderRange.AESeverity,403318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almUnderRange.AEShelveDuration,403319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almRateOfChange.BOOLS1,403324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almRateOfChange.BOOLS2,403325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almRateOfChange.AEBOOLS,403326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almRateOfChange.INT1,403327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almRateOfChange.INT2,403328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almRateOfChange.AENotify,403329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almRateOfChange.AESeverity,403330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almRateOfChange.AEShelveDuration,403331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI3.almPLCFault.BOOLS1,403336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI3.almPLCFault.BOOLS2,403337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI3.almPLCFault.AEBOOLS,403338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI3.almPLCFault.INT1,403339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almPLCFault.INT2,403340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI3.almPLCFault.AENotify,403341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI3.almPLCFault.AESeverity,403342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI3.almPLCFault.AEShelveDuration,403343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almHighHigh.BOOLS1,403440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almHighHigh.BOOLS2,403441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almHighHigh.AEBOOLS,403442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almHighHigh.INT1,403443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almHighHigh.INT2,403444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almHighHigh.AENotify,403445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almHighHigh.AESeverity,403446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almHighHigh.AEShelveDuration,403447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almHigh.BOOLS1,403452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almHigh.BOOLS2,403453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almHigh.AEBOOLS,403454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almHigh.INT1,403455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almHigh.INT2,403456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almHigh.AENotify,403457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almHigh.AESeverity,403458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almHigh.AEShelveDuration,403459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almLow.BOOLS1,403464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almLow.BOOLS2,403465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almLow.AEBOOLS,403466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almLow.INT1,403467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almLow.INT2,403468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almLow.AENotify,403469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almLow.AESeverity,403470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almLow.AEShelveDuration,403471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almLowLow.BOOLS1,403476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almLowLow.BOOLS2,403477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almLowLow.AEBOOLS,403478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almLowLow.INT1,403479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almLowLow.INT2,403480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almLowLow.AENotify,403481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almLowLow.AESeverity,403482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almLowLow.AEShelveDuration,403483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almBrokenLoop.BOOLS1,403488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almBrokenLoop.BOOLS2,403489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almBrokenLoop.AEBOOLS,403490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almBrokenLoop.INT1,403491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almBrokenLoop.INT2,403492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almBrokenLoop.AENotify,403493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almBrokenLoop.AESeverity,403494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almBrokenLoop.AEShelveDuration,403495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almOverRange.BOOLS1,403500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almOverRange.BOOLS2,403501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almOverRange.AEBOOLS,403502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almOverRange.INT1,403503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almOverRange.INT2,403504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almOverRange.AENotify,403505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almOverRange.AESeverity,403506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almOverRange.AEShelveDuration,403507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almUnderRange.BOOLS1,403512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almUnderRange.BOOLS2,403513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almUnderRange.AEBOOLS,403514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almUnderRange.INT1,403515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almUnderRange.INT2,403516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almUnderRange.AENotify,403517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almUnderRange.AESeverity,403518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almUnderRange.AEShelveDuration,403519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almRateOfChange.BOOLS1,403524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almRateOfChange.BOOLS2,403525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almRateOfChange.AEBOOLS,403526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almRateOfChange.INT1,403527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almRateOfChange.INT2,403528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almRateOfChange.AENotify,403529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almRateOfChange.AESeverity,403530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almRateOfChange.AEShelveDuration,403531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI4.almPLCFault.BOOLS1,403536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI4.almPLCFault.BOOLS2,403537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI4.almPLCFault.AEBOOLS,403538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI4.almPLCFault.INT1,403539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almPLCFault.INT2,403540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI4.almPLCFault.AENotify,403541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI4.almPLCFault.AESeverity,403542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI4.almPLCFault.AEShelveDuration,403543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almHighHigh.BOOLS1,403640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almHighHigh.BOOLS2,403641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almHighHigh.AEBOOLS,403642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almHighHigh.INT1,403643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almHighHigh.INT2,403644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almHighHigh.AENotify,403645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almHighHigh.AESeverity,403646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almHighHigh.AEShelveDuration,403647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almHigh.BOOLS1,403652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almHigh.BOOLS2,403653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almHigh.AEBOOLS,403654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almHigh.INT1,403655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almHigh.INT2,403656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almHigh.AENotify,403657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almHigh.AESeverity,403658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almHigh.AEShelveDuration,403659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almLow.BOOLS1,403664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almLow.BOOLS2,403665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almLow.AEBOOLS,403666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almLow.INT1,403667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almLow.INT2,403668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almLow.AENotify,403669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almLow.AESeverity,403670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almLow.AEShelveDuration,403671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almLowLow.BOOLS1,403676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almLowLow.BOOLS2,403677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almLowLow.AEBOOLS,403678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almLowLow.INT1,403679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almLowLow.INT2,403680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almLowLow.AENotify,403681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almLowLow.AESeverity,403682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almLowLow.AEShelveDuration,403683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almBrokenLoop.BOOLS1,403688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almBrokenLoop.BOOLS2,403689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almBrokenLoop.AEBOOLS,403690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almBrokenLoop.INT1,403691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almBrokenLoop.INT2,403692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almBrokenLoop.AENotify,403693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almBrokenLoop.AESeverity,403694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almBrokenLoop.AEShelveDuration,403695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almOverRange.BOOLS1,403700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almOverRange.BOOLS2,403701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almOverRange.AEBOOLS,403702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almOverRange.INT1,403703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almOverRange.INT2,403704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almOverRange.AENotify,403705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almOverRange.AESeverity,403706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almOverRange.AEShelveDuration,403707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almUnderRange.BOOLS1,403712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almUnderRange.BOOLS2,403713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almUnderRange.AEBOOLS,403714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almUnderRange.INT1,403715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almUnderRange.INT2,403716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almUnderRange.AENotify,403717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almUnderRange.AESeverity,403718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almUnderRange.AEShelveDuration,403719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almRateOfChange.BOOLS1,403724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almRateOfChange.BOOLS2,403725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almRateOfChange.AEBOOLS,403726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almRateOfChange.INT1,403727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almRateOfChange.INT2,403728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almRateOfChange.AENotify,403729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almRateOfChange.AESeverity,403730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almRateOfChange.AEShelveDuration,403731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI5.almPLCFault.BOOLS1,403736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI5.almPLCFault.BOOLS2,403737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI5.almPLCFault.AEBOOLS,403738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI5.almPLCFault.INT1,403739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almPLCFault.INT2,403740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI5.almPLCFault.AENotify,403741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI5.almPLCFault.AESeverity,403742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI5.almPLCFault.AEShelveDuration,403743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almHighHigh.BOOLS1,403840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almHighHigh.BOOLS2,403841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almHighHigh.AEBOOLS,403842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almHighHigh.INT1,403843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almHighHigh.INT2,403844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almHighHigh.AENotify,403845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almHighHigh.AESeverity,403846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almHighHigh.AEShelveDuration,403847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almHigh.BOOLS1,403852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almHigh.BOOLS2,403853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almHigh.AEBOOLS,403854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almHigh.INT1,403855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almHigh.INT2,403856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almHigh.AENotify,403857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almHigh.AESeverity,403858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almHigh.AEShelveDuration,403859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almLow.BOOLS1,403864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almLow.BOOLS2,403865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almLow.AEBOOLS,403866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almLow.INT1,403867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almLow.INT2,403868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almLow.AENotify,403869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almLow.AESeverity,403870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almLow.AEShelveDuration,403871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almLowLow.BOOLS1,403876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almLowLow.BOOLS2,403877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almLowLow.AEBOOLS,403878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almLowLow.INT1,403879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almLowLow.INT2,403880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almLowLow.AENotify,403881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almLowLow.AESeverity,403882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almLowLow.AEShelveDuration,403883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almBrokenLoop.BOOLS1,403888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almBrokenLoop.BOOLS2,403889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almBrokenLoop.AEBOOLS,403890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almBrokenLoop.INT1,403891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almBrokenLoop.INT2,403892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almBrokenLoop.AENotify,403893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almBrokenLoop.AESeverity,403894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almBrokenLoop.AEShelveDuration,403895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almOverRange.BOOLS1,403900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almOverRange.BOOLS2,403901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almOverRange.AEBOOLS,403902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almOverRange.INT1,403903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almOverRange.INT2,403904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almOverRange.AENotify,403905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almOverRange.AESeverity,403906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almOverRange.AEShelveDuration,403907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almUnderRange.BOOLS1,403912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almUnderRange.BOOLS2,403913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almUnderRange.AEBOOLS,403914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almUnderRange.INT1,403915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almUnderRange.INT2,403916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almUnderRange.AENotify,403917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almUnderRange.AESeverity,403918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almUnderRange.AEShelveDuration,403919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almRateOfChange.BOOLS1,403924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almRateOfChange.BOOLS2,403925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almRateOfChange.AEBOOLS,403926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almRateOfChange.INT1,403927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almRateOfChange.INT2,403928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almRateOfChange.AENotify,403929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almRateOfChange.AESeverity,403930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almRateOfChange.AEShelveDuration,403931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI6.almPLCFault.BOOLS1,403936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI6.almPLCFault.BOOLS2,403937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI6.almPLCFault.AEBOOLS,403938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI6.almPLCFault.INT1,403939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almPLCFault.INT2,403940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI6.almPLCFault.AENotify,403941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI6.almPLCFault.AESeverity,403942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI6.almPLCFault.AEShelveDuration,403943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almHighHigh.BOOLS1,404040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almHighHigh.BOOLS2,404041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almHighHigh.AEBOOLS,404042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almHighHigh.INT1,404043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almHighHigh.INT2,404044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almHighHigh.AENotify,404045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almHighHigh.AESeverity,404046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almHighHigh.AEShelveDuration,404047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almHigh.BOOLS1,404052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almHigh.BOOLS2,404053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almHigh.AEBOOLS,404054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almHigh.INT1,404055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almHigh.INT2,404056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almHigh.AENotify,404057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almHigh.AESeverity,404058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almHigh.AEShelveDuration,404059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almLow.BOOLS1,404064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almLow.BOOLS2,404065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almLow.AEBOOLS,404066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almLow.INT1,404067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almLow.INT2,404068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almLow.AENotify,404069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almLow.AESeverity,404070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almLow.AEShelveDuration,404071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almLowLow.BOOLS1,404076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almLowLow.BOOLS2,404077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almLowLow.AEBOOLS,404078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almLowLow.INT1,404079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almLowLow.INT2,404080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almLowLow.AENotify,404081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almLowLow.AESeverity,404082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almLowLow.AEShelveDuration,404083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almBrokenLoop.BOOLS1,404088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almBrokenLoop.BOOLS2,404089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almBrokenLoop.AEBOOLS,404090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almBrokenLoop.INT1,404091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almBrokenLoop.INT2,404092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almBrokenLoop.AENotify,404093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almBrokenLoop.AESeverity,404094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almBrokenLoop.AEShelveDuration,404095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almOverRange.BOOLS1,404100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almOverRange.BOOLS2,404101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almOverRange.AEBOOLS,404102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almOverRange.INT1,404103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almOverRange.INT2,404104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almOverRange.AENotify,404105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almOverRange.AESeverity,404106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almOverRange.AEShelveDuration,404107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almUnderRange.BOOLS1,404112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almUnderRange.BOOLS2,404113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almUnderRange.AEBOOLS,404114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almUnderRange.INT1,404115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almUnderRange.INT2,404116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almUnderRange.AENotify,404117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almUnderRange.AESeverity,404118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almUnderRange.AEShelveDuration,404119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almRateOfChange.BOOLS1,404124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almRateOfChange.BOOLS2,404125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almRateOfChange.AEBOOLS,404126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almRateOfChange.INT1,404127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almRateOfChange.INT2,404128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almRateOfChange.AENotify,404129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almRateOfChange.AESeverity,404130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almRateOfChange.AEShelveDuration,404131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI7.almPLCFault.BOOLS1,404136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI7.almPLCFault.BOOLS2,404137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI7.almPLCFault.AEBOOLS,404138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI7.almPLCFault.INT1,404139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almPLCFault.INT2,404140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI7.almPLCFault.AENotify,404141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI7.almPLCFault.AESeverity,404142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI7.almPLCFault.AEShelveDuration,404143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almHighHigh.BOOLS1,404240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almHighHigh.BOOLS2,404241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almHighHigh.AEBOOLS,404242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almHighHigh.INT1,404243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almHighHigh.INT2,404244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almHighHigh.AENotify,404245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almHighHigh.AESeverity,404246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almHighHigh.AEShelveDuration,404247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almHigh.BOOLS1,404252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almHigh.BOOLS2,404253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almHigh.AEBOOLS,404254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almHigh.INT1,404255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almHigh.INT2,404256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almHigh.AENotify,404257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almHigh.AESeverity,404258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almHigh.AEShelveDuration,404259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almLow.BOOLS1,404264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almLow.BOOLS2,404265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almLow.AEBOOLS,404266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almLow.INT1,404267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almLow.INT2,404268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almLow.AENotify,404269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almLow.AESeverity,404270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almLow.AEShelveDuration,404271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almLowLow.BOOLS1,404276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almLowLow.BOOLS2,404277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almLowLow.AEBOOLS,404278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almLowLow.INT1,404279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almLowLow.INT2,404280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almLowLow.AENotify,404281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almLowLow.AESeverity,404282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almLowLow.AEShelveDuration,404283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almBrokenLoop.BOOLS1,404288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almBrokenLoop.BOOLS2,404289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almBrokenLoop.AEBOOLS,404290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almBrokenLoop.INT1,404291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almBrokenLoop.INT2,404292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almBrokenLoop.AENotify,404293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almBrokenLoop.AESeverity,404294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almBrokenLoop.AEShelveDuration,404295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almOverRange.BOOLS1,404300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almOverRange.BOOLS2,404301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almOverRange.AEBOOLS,404302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almOverRange.INT1,404303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almOverRange.INT2,404304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almOverRange.AENotify,404305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almOverRange.AESeverity,404306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almOverRange.AEShelveDuration,404307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almUnderRange.BOOLS1,404312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almUnderRange.BOOLS2,404313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almUnderRange.AEBOOLS,404314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almUnderRange.INT1,404315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almUnderRange.INT2,404316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almUnderRange.AENotify,404317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almUnderRange.AESeverity,404318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almUnderRange.AEShelveDuration,404319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almRateOfChange.BOOLS1,404324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almRateOfChange.BOOLS2,404325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almRateOfChange.AEBOOLS,404326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almRateOfChange.INT1,404327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almRateOfChange.INT2,404328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almRateOfChange.AENotify,404329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almRateOfChange.AESeverity,404330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almRateOfChange.AEShelveDuration,404331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI8.almPLCFault.BOOLS1,404336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI8.almPLCFault.BOOLS2,404337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI8.almPLCFault.AEBOOLS,404338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI8.almPLCFault.INT1,404339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almPLCFault.INT2,404340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI8.almPLCFault.AENotify,404341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI8.almPLCFault.AESeverity,404342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI8.almPLCFault.AEShelveDuration,404343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almHighHigh.BOOLS1,404440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almHighHigh.BOOLS2,404441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almHighHigh.AEBOOLS,404442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almHighHigh.INT1,404443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almHighHigh.INT2,404444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almHighHigh.AENotify,404445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almHighHigh.AESeverity,404446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almHighHigh.AEShelveDuration,404447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almHigh.BOOLS1,404452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almHigh.BOOLS2,404453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almHigh.AEBOOLS,404454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almHigh.INT1,404455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almHigh.INT2,404456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almHigh.AENotify,404457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almHigh.AESeverity,404458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almHigh.AEShelveDuration,404459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almLow.BOOLS1,404464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almLow.BOOLS2,404465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almLow.AEBOOLS,404466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almLow.INT1,404467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almLow.INT2,404468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almLow.AENotify,404469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almLow.AESeverity,404470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almLow.AEShelveDuration,404471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almLowLow.BOOLS1,404476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almLowLow.BOOLS2,404477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almLowLow.AEBOOLS,404478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almLowLow.INT1,404479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almLowLow.INT2,404480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almLowLow.AENotify,404481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almLowLow.AESeverity,404482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almLowLow.AEShelveDuration,404483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almBrokenLoop.BOOLS1,404488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almBrokenLoop.BOOLS2,404489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almBrokenLoop.AEBOOLS,404490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almBrokenLoop.INT1,404491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almBrokenLoop.INT2,404492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almBrokenLoop.AENotify,404493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almBrokenLoop.AESeverity,404494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almBrokenLoop.AEShelveDuration,404495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almOverRange.BOOLS1,404500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almOverRange.BOOLS2,404501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almOverRange.AEBOOLS,404502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almOverRange.INT1,404503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almOverRange.INT2,404504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almOverRange.AENotify,404505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almOverRange.AESeverity,404506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almOverRange.AEShelveDuration,404507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almUnderRange.BOOLS1,404512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almUnderRange.BOOLS2,404513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almUnderRange.AEBOOLS,404514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almUnderRange.INT1,404515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almUnderRange.INT2,404516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almUnderRange.AENotify,404517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almUnderRange.AESeverity,404518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almUnderRange.AEShelveDuration,404519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almRateOfChange.BOOLS1,404524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almRateOfChange.BOOLS2,404525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almRateOfChange.AEBOOLS,404526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almRateOfChange.INT1,404527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almRateOfChange.INT2,404528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almRateOfChange.AENotify,404529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almRateOfChange.AESeverity,404530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almRateOfChange.AEShelveDuration,404531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0116_1_FI9.almPLCFault.BOOLS1,404536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0116_1_FI9.almPLCFault.BOOLS2,404537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0116_1_FI9.almPLCFault.AEBOOLS,404538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0116_1_FI9.almPLCFault.INT1,404539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almPLCFault.INT2,404540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0116_1_FI9.almPLCFault.AENotify,404541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0116_1_FI9.almPLCFault.AESeverity,404542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0116_1_FI9.almPLCFault.AEShelveDuration,404543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almHighHigh.BOOLS1,404640,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almHighHigh.BOOLS2,404641,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almHighHigh.AEBOOLS,404642,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almHighHigh.INT1,404643,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almHighHigh.INT2,404644,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almHighHigh.AENotify,404645,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almHighHigh.AESeverity,404646,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almHighHigh.AEShelveDuration,404647,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almHigh.BOOLS1,404652,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almHigh.BOOLS2,404653,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almHigh.AEBOOLS,404654,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almHigh.INT1,404655,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almHigh.INT2,404656,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almHigh.AENotify,404657,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almHigh.AESeverity,404658,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almHigh.AEShelveDuration,404659,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almLow.BOOLS1,404664,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almLow.BOOLS2,404665,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almLow.AEBOOLS,404666,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almLow.INT1,404667,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almLow.INT2,404668,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almLow.AENotify,404669,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almLow.AESeverity,404670,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almLow.AEShelveDuration,404671,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almLowLow.BOOLS1,404676,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almLowLow.BOOLS2,404677,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almLowLow.AEBOOLS,404678,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almLowLow.INT1,404679,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almLowLow.INT2,404680,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almLowLow.AENotify,404681,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almLowLow.AESeverity,404682,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almLowLow.AEShelveDuration,404683,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almBrokenLoop.BOOLS1,404688,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almBrokenLoop.BOOLS2,404689,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almBrokenLoop.AEBOOLS,404690,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almBrokenLoop.INT1,404691,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almBrokenLoop.INT2,404692,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almBrokenLoop.AENotify,404693,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almBrokenLoop.AESeverity,404694,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almBrokenLoop.AEShelveDuration,404695,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almOverRange.BOOLS1,404700,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almOverRange.BOOLS2,404701,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almOverRange.AEBOOLS,404702,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almOverRange.INT1,404703,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almOverRange.INT2,404704,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almOverRange.AENotify,404705,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almOverRange.AESeverity,404706,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almOverRange.AEShelveDuration,404707,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almUnderRange.BOOLS1,404712,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almUnderRange.BOOLS2,404713,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almUnderRange.AEBOOLS,404714,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almUnderRange.INT1,404715,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almUnderRange.INT2,404716,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almUnderRange.AENotify,404717,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almUnderRange.AESeverity,404718,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almUnderRange.AEShelveDuration,404719,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almRateOfChange.BOOLS1,404724,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almRateOfChange.BOOLS2,404725,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almRateOfChange.AEBOOLS,404726,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almRateOfChange.INT1,404727,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almRateOfChange.INT2,404728,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almRateOfChange.AENotify,404729,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almRateOfChange.AESeverity,404730,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almRateOfChange.AEShelveDuration,404731,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_ZI.almPLCFault.BOOLS1,404736,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almPLCFault.BOOLS2,404737,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_ZI.almPLCFault.AEBOOLS,404738,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_ZI.almPLCFault.INT1,404739,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almPLCFault.INT2,404740,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_ZI.almPLCFault.AENotify,404741,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_ZI.almPLCFault.AESeverity,404742,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_ZI.almPLCFault.AEShelveDuration,404743,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almHighHigh.BOOLS1,404840,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almHighHigh.BOOLS2,404841,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almHighHigh.AEBOOLS,404842,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almHighHigh.INT1,404843,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almHighHigh.INT2,404844,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almHighHigh.AENotify,404845,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almHighHigh.AESeverity,404846,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almHighHigh.AEShelveDuration,404847,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almHigh.BOOLS1,404852,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almHigh.BOOLS2,404853,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almHigh.AEBOOLS,404854,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almHigh.INT1,404855,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almHigh.INT2,404856,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almHigh.AENotify,404857,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almHigh.AESeverity,404858,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almHigh.AEShelveDuration,404859,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almLow.BOOLS1,404864,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almLow.BOOLS2,404865,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almLow.AEBOOLS,404866,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almLow.INT1,404867,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almLow.INT2,404868,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almLow.AENotify,404869,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almLow.AESeverity,404870,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almLow.AEShelveDuration,404871,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almLowLow.BOOLS1,404876,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almLowLow.BOOLS2,404877,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almLowLow.AEBOOLS,404878,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almLowLow.INT1,404879,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almLowLow.INT2,404880,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almLowLow.AENotify,404881,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almLowLow.AESeverity,404882,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almLowLow.AEShelveDuration,404883,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almBrokenLoop.BOOLS1,404888,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almBrokenLoop.BOOLS2,404889,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almBrokenLoop.AEBOOLS,404890,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almBrokenLoop.INT1,404891,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almBrokenLoop.INT2,404892,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almBrokenLoop.AENotify,404893,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almBrokenLoop.AESeverity,404894,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almBrokenLoop.AEShelveDuration,404895,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almOverRange.BOOLS1,404900,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almOverRange.BOOLS2,404901,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almOverRange.AEBOOLS,404902,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almOverRange.INT1,404903,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almOverRange.INT2,404904,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almOverRange.AENotify,404905,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almOverRange.AESeverity,404906,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almOverRange.AEShelveDuration,404907,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almUnderRange.BOOLS1,404912,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almUnderRange.BOOLS2,404913,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almUnderRange.AEBOOLS,404914,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almUnderRange.INT1,404915,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almUnderRange.INT2,404916,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almUnderRange.AENotify,404917,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almUnderRange.AESeverity,404918,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almUnderRange.AEShelveDuration,404919,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almRateOfChange.BOOLS1,404924,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almRateOfChange.BOOLS2,404925,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almRateOfChange.AEBOOLS,404926,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almRateOfChange.INT1,404927,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almRateOfChange.INT2,404928,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almRateOfChange.AENotify,404929,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almRateOfChange.AESeverity,404930,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almRateOfChange.AEShelveDuration,404931,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_ZI.almPLCFault.BOOLS1,404936,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almPLCFault.BOOLS2,404937,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_ZI.almPLCFault.AEBOOLS,404938,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_ZI.almPLCFault.INT1,404939,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almPLCFault.INT2,404940,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_ZI.almPLCFault.AENotify,404941,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_ZI.almPLCFault.AESeverity,404942,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_ZI.almPLCFault.AEShelveDuration,404943,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almHighHigh.BOOLS1,405040,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almHighHigh.BOOLS2,405041,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almHighHigh.AEBOOLS,405042,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almHighHigh.INT1,405043,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almHighHigh.INT2,405044,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almHighHigh.AENotify,405045,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almHighHigh.AESeverity,405046,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almHighHigh.AEShelveDuration,405047,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almHigh.BOOLS1,405052,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almHigh.BOOLS2,405053,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almHigh.AEBOOLS,405054,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almHigh.INT1,405055,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almHigh.INT2,405056,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almHigh.AENotify,405057,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almHigh.AESeverity,405058,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almHigh.AEShelveDuration,405059,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almLow.BOOLS1,405064,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almLow.BOOLS2,405065,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almLow.AEBOOLS,405066,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almLow.INT1,405067,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almLow.INT2,405068,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almLow.AENotify,405069,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almLow.AESeverity,405070,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almLow.AEShelveDuration,405071,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almLowLow.BOOLS1,405076,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almLowLow.BOOLS2,405077,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almLowLow.AEBOOLS,405078,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almLowLow.INT1,405079,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almLowLow.INT2,405080,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almLowLow.AENotify,405081,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almLowLow.AESeverity,405082,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almLowLow.AEShelveDuration,405083,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almBrokenLoop.BOOLS1,405088,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almBrokenLoop.BOOLS2,405089,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almBrokenLoop.AEBOOLS,405090,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almBrokenLoop.INT1,405091,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almBrokenLoop.INT2,405092,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almBrokenLoop.AENotify,405093,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almBrokenLoop.AESeverity,405094,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almBrokenLoop.AEShelveDuration,405095,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almOverRange.BOOLS1,405100,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almOverRange.BOOLS2,405101,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almOverRange.AEBOOLS,405102,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almOverRange.INT1,405103,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almOverRange.INT2,405104,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almOverRange.AENotify,405105,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almOverRange.AESeverity,405106,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almOverRange.AEShelveDuration,405107,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almUnderRange.BOOLS1,405112,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almUnderRange.BOOLS2,405113,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almUnderRange.AEBOOLS,405114,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almUnderRange.INT1,405115,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almUnderRange.INT2,405116,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almUnderRange.AENotify,405117,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almUnderRange.AESeverity,405118,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almUnderRange.AEShelveDuration,405119,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almRateOfChange.BOOLS1,405124,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almRateOfChange.BOOLS2,405125,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almRateOfChange.AEBOOLS,405126,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almRateOfChange.INT1,405127,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almRateOfChange.INT2,405128,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almRateOfChange.AENotify,405129,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almRateOfChange.AESeverity,405130,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almRateOfChange.AEShelveDuration,405131,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FIT_0113_2A_FI.almPLCFault.BOOLS1,405136,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FIT_0113_2A_FI.almPLCFault.BOOLS2,405137,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FIT_0113_2A_FI.almPLCFault.AEBOOLS,405138,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FIT_0113_2A_FI.almPLCFault.INT1,405139,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almPLCFault.INT2,405140,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FIT_0113_2A_FI.almPLCFault.AENotify,405141,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FIT_0113_2A_FI.almPLCFault.AESeverity,405142,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FIT_0113_2A_FI.almPLCFault.AEShelveDuration,405143,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almHighHigh.BOOLS1,405240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almHighHigh.BOOLS2,405241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almHighHigh.AEBOOLS,405242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almHighHigh.INT1,405243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almHighHigh.INT2,405244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almHighHigh.AENotify,405245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almHighHigh.AESeverity,405246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almHighHigh.AEShelveDuration,405247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almHigh.BOOLS1,405252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almHigh.BOOLS2,405253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almHigh.AEBOOLS,405254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almHigh.INT1,405255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almHigh.INT2,405256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almHigh.AENotify,405257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almHigh.AESeverity,405258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almHigh.AEShelveDuration,405259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almLow.BOOLS1,405264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almLow.BOOLS2,405265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almLow.AEBOOLS,405266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almLow.INT1,405267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almLow.INT2,405268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almLow.AENotify,405269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almLow.AESeverity,405270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almLow.AEShelveDuration,405271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almLowLow.BOOLS1,405276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almLowLow.BOOLS2,405277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almLowLow.AEBOOLS,405278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almLowLow.INT1,405279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almLowLow.INT2,405280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almLowLow.AENotify,405281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almLowLow.AESeverity,405282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almLowLow.AEShelveDuration,405283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almBrokenLoop.BOOLS1,405288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almBrokenLoop.BOOLS2,405289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almBrokenLoop.AEBOOLS,405290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almBrokenLoop.INT1,405291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almBrokenLoop.INT2,405292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almBrokenLoop.AENotify,405293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almBrokenLoop.AESeverity,405294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almBrokenLoop.AEShelveDuration,405295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almOverRange.BOOLS1,405300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almOverRange.BOOLS2,405301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almOverRange.AEBOOLS,405302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almOverRange.INT1,405303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almOverRange.INT2,405304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almOverRange.AENotify,405305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almOverRange.AESeverity,405306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almOverRange.AEShelveDuration,405307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almUnderRange.BOOLS1,405312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almUnderRange.BOOLS2,405313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almUnderRange.AEBOOLS,405314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almUnderRange.INT1,405315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almUnderRange.INT2,405316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almUnderRange.AENotify,405317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almUnderRange.AESeverity,405318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almUnderRange.AEShelveDuration,405319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almRateOfChange.BOOLS1,405324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almRateOfChange.BOOLS2,405325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almRateOfChange.AEBOOLS,405326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almRateOfChange.INT1,405327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almRateOfChange.INT2,405328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almRateOfChange.AENotify,405329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almRateOfChange.AESeverity,405330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almRateOfChange.AEShelveDuration,405331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZI.almPLCFault.BOOLS1,405336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZI.almPLCFault.BOOLS2,405337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZI.almPLCFault.AEBOOLS,405338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZI.almPLCFault.INT1,405339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almPLCFault.INT2,405340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZI.almPLCFault.AENotify,405341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZI.almPLCFault.AESeverity,405342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZI.almPLCFault.AEShelveDuration,405343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almHighHigh.BOOLS1,405440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almHighHigh.BOOLS2,405441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almHighHigh.AEBOOLS,405442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almHighHigh.INT1,405443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almHighHigh.INT2,405444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almHighHigh.AENotify,405445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almHighHigh.AESeverity,405446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almHighHigh.AEShelveDuration,405447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almHigh.BOOLS1,405452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almHigh.BOOLS2,405453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almHigh.AEBOOLS,405454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almHigh.INT1,405455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almHigh.INT2,405456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almHigh.AENotify,405457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almHigh.AESeverity,405458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almHigh.AEShelveDuration,405459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almLow.BOOLS1,405464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almLow.BOOLS2,405465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almLow.AEBOOLS,405466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almLow.INT1,405467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almLow.INT2,405468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almLow.AENotify,405469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almLow.AESeverity,405470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almLow.AEShelveDuration,405471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almLowLow.BOOLS1,405476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almLowLow.BOOLS2,405477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almLowLow.AEBOOLS,405478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almLowLow.INT1,405479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almLowLow.INT2,405480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almLowLow.AENotify,405481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almLowLow.AESeverity,405482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almLowLow.AEShelveDuration,405483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almBrokenLoop.BOOLS1,405488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almBrokenLoop.BOOLS2,405489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almBrokenLoop.AEBOOLS,405490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almBrokenLoop.INT1,405491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almBrokenLoop.INT2,405492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almBrokenLoop.AENotify,405493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almBrokenLoop.AESeverity,405494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almBrokenLoop.AEShelveDuration,405495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almOverRange.BOOLS1,405500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almOverRange.BOOLS2,405501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almOverRange.AEBOOLS,405502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almOverRange.INT1,405503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almOverRange.INT2,405504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almOverRange.AENotify,405505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almOverRange.AESeverity,405506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almOverRange.AEShelveDuration,405507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almUnderRange.BOOLS1,405512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almUnderRange.BOOLS2,405513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almUnderRange.AEBOOLS,405514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almUnderRange.INT1,405515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almUnderRange.INT2,405516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almUnderRange.AENotify,405517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almUnderRange.AESeverity,405518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almUnderRange.AEShelveDuration,405519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almRateOfChange.BOOLS1,405524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almRateOfChange.BOOLS2,405525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almRateOfChange.AEBOOLS,405526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almRateOfChange.INT1,405527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almRateOfChange.INT2,405528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almRateOfChange.AENotify,405529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almRateOfChange.AESeverity,405530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almRateOfChange.AEShelveDuration,405531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZI.almPLCFault.BOOLS1,405536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZI.almPLCFault.BOOLS2,405537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZI.almPLCFault.AEBOOLS,405538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZI.almPLCFault.INT1,405539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almPLCFault.INT2,405540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZI.almPLCFault.AENotify,405541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZI.almPLCFault.AESeverity,405542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZI.almPLCFault.AEShelveDuration,405543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almHighHigh.BOOLS1,405640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almHighHigh.BOOLS2,405641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almHighHigh.AEBOOLS,405642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almHighHigh.INT1,405643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almHighHigh.INT2,405644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almHighHigh.AENotify,405645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almHighHigh.AESeverity,405646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almHighHigh.AEShelveDuration,405647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almHigh.BOOLS1,405652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almHigh.BOOLS2,405653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almHigh.AEBOOLS,405654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almHigh.INT1,405655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almHigh.INT2,405656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almHigh.AENotify,405657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almHigh.AESeverity,405658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almHigh.AEShelveDuration,405659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almLow.BOOLS1,405664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almLow.BOOLS2,405665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almLow.AEBOOLS,405666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almLow.INT1,405667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almLow.INT2,405668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almLow.AENotify,405669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almLow.AESeverity,405670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almLow.AEShelveDuration,405671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almLowLow.BOOLS1,405676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almLowLow.BOOLS2,405677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almLowLow.AEBOOLS,405678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almLowLow.INT1,405679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almLowLow.INT2,405680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almLowLow.AENotify,405681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almLowLow.AESeverity,405682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almLowLow.AEShelveDuration,405683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almBrokenLoop.BOOLS1,405688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almBrokenLoop.BOOLS2,405689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almBrokenLoop.AEBOOLS,405690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almBrokenLoop.INT1,405691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almBrokenLoop.INT2,405692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almBrokenLoop.AENotify,405693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almBrokenLoop.AESeverity,405694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almBrokenLoop.AEShelveDuration,405695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almOverRange.BOOLS1,405700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almOverRange.BOOLS2,405701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almOverRange.AEBOOLS,405702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almOverRange.INT1,405703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almOverRange.INT2,405704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almOverRange.AENotify,405705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almOverRange.AESeverity,405706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almOverRange.AEShelveDuration,405707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almUnderRange.BOOLS1,405712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almUnderRange.BOOLS2,405713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almUnderRange.AEBOOLS,405714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almUnderRange.INT1,405715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almUnderRange.INT2,405716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almUnderRange.AENotify,405717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almUnderRange.AESeverity,405718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almUnderRange.AEShelveDuration,405719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almRateOfChange.BOOLS1,405724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almRateOfChange.BOOLS2,405725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almRateOfChange.AEBOOLS,405726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almRateOfChange.INT1,405727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almRateOfChange.INT2,405728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almRateOfChange.AENotify,405729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almRateOfChange.AESeverity,405730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almRateOfChange.AEShelveDuration,405731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZI.almPLCFault.BOOLS1,405736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZI.almPLCFault.BOOLS2,405737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZI.almPLCFault.AEBOOLS,405738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZI.almPLCFault.INT1,405739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almPLCFault.INT2,405740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZI.almPLCFault.AENotify,405741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZI.almPLCFault.AESeverity,405742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZI.almPLCFault.AEShelveDuration,405743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almHighHigh.BOOLS1,405840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almHighHigh.BOOLS2,405841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almHighHigh.AEBOOLS,405842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almHighHigh.INT1,405843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almHighHigh.INT2,405844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almHighHigh.AENotify,405845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almHighHigh.AESeverity,405846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almHighHigh.AEShelveDuration,405847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almHigh.BOOLS1,405852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almHigh.BOOLS2,405853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almHigh.AEBOOLS,405854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almHigh.INT1,405855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almHigh.INT2,405856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almHigh.AENotify,405857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almHigh.AESeverity,405858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almHigh.AEShelveDuration,405859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almLow.BOOLS1,405864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almLow.BOOLS2,405865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almLow.AEBOOLS,405866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almLow.INT1,405867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almLow.INT2,405868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almLow.AENotify,405869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almLow.AESeverity,405870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almLow.AEShelveDuration,405871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almLowLow.BOOLS1,405876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almLowLow.BOOLS2,405877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almLowLow.AEBOOLS,405878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almLowLow.INT1,405879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almLowLow.INT2,405880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almLowLow.AENotify,405881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almLowLow.AESeverity,405882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almLowLow.AEShelveDuration,405883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almBrokenLoop.BOOLS1,405888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almBrokenLoop.BOOLS2,405889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almBrokenLoop.AEBOOLS,405890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almBrokenLoop.INT1,405891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almBrokenLoop.INT2,405892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almBrokenLoop.AENotify,405893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almBrokenLoop.AESeverity,405894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almBrokenLoop.AEShelveDuration,405895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almOverRange.BOOLS1,405900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almOverRange.BOOLS2,405901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almOverRange.AEBOOLS,405902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almOverRange.INT1,405903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almOverRange.INT2,405904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almOverRange.AENotify,405905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almOverRange.AESeverity,405906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almOverRange.AEShelveDuration,405907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almUnderRange.BOOLS1,405912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almUnderRange.BOOLS2,405913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almUnderRange.AEBOOLS,405914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almUnderRange.INT1,405915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almUnderRange.INT2,405916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almUnderRange.AENotify,405917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almUnderRange.AESeverity,405918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almUnderRange.AEShelveDuration,405919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almRateOfChange.BOOLS1,405924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almRateOfChange.BOOLS2,405925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almRateOfChange.AEBOOLS,405926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almRateOfChange.INT1,405927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almRateOfChange.INT2,405928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almRateOfChange.AENotify,405929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almRateOfChange.AESeverity,405930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almRateOfChange.AEShelveDuration,405931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZI.almPLCFault.BOOLS1,405936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZI.almPLCFault.BOOLS2,405937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZI.almPLCFault.AEBOOLS,405938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZI.almPLCFault.INT1,405939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almPLCFault.INT2,405940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZI.almPLCFault.AENotify,405941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZI.almPLCFault.AESeverity,405942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZI.almPLCFault.AEShelveDuration,405943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almHighHigh.BOOLS1,406040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almHighHigh.BOOLS2,406041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almHighHigh.AEBOOLS,406042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almHighHigh.INT1,406043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almHighHigh.INT2,406044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almHighHigh.AENotify,406045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almHighHigh.AESeverity,406046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almHighHigh.AEShelveDuration,406047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almHigh.BOOLS1,406052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almHigh.BOOLS2,406053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almHigh.AEBOOLS,406054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almHigh.INT1,406055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almHigh.INT2,406056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almHigh.AENotify,406057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almHigh.AESeverity,406058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almHigh.AEShelveDuration,406059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almLow.BOOLS1,406064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almLow.BOOLS2,406065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almLow.AEBOOLS,406066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almLow.INT1,406067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almLow.INT2,406068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almLow.AENotify,406069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almLow.AESeverity,406070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almLow.AEShelveDuration,406071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almLowLow.BOOLS1,406076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almLowLow.BOOLS2,406077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almLowLow.AEBOOLS,406078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almLowLow.INT1,406079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almLowLow.INT2,406080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almLowLow.AENotify,406081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almLowLow.AESeverity,406082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almLowLow.AEShelveDuration,406083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almBrokenLoop.BOOLS1,406088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almBrokenLoop.BOOLS2,406089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almBrokenLoop.AEBOOLS,406090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almBrokenLoop.INT1,406091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almBrokenLoop.INT2,406092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almBrokenLoop.AENotify,406093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almBrokenLoop.AESeverity,406094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almBrokenLoop.AEShelveDuration,406095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almOverRange.BOOLS1,406100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almOverRange.BOOLS2,406101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almOverRange.AEBOOLS,406102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almOverRange.INT1,406103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almOverRange.INT2,406104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almOverRange.AENotify,406105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almOverRange.AESeverity,406106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almOverRange.AEShelveDuration,406107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almUnderRange.BOOLS1,406112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almUnderRange.BOOLS2,406113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almUnderRange.AEBOOLS,406114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almUnderRange.INT1,406115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almUnderRange.INT2,406116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almUnderRange.AENotify,406117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almUnderRange.AESeverity,406118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almUnderRange.AEShelveDuration,406119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almRateOfChange.BOOLS1,406124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almRateOfChange.BOOLS2,406125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almRateOfChange.AEBOOLS,406126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almRateOfChange.INT1,406127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almRateOfChange.INT2,406128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almRateOfChange.AENotify,406129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almRateOfChange.AESeverity,406130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almRateOfChange.AEShelveDuration,406131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZI.almPLCFault.BOOLS1,406136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZI.almPLCFault.BOOLS2,406137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZI.almPLCFault.AEBOOLS,406138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZI.almPLCFault.INT1,406139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almPLCFault.INT2,406140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZI.almPLCFault.AENotify,406141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZI.almPLCFault.AESeverity,406142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZI.almPLCFault.AEShelveDuration,406143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almHighHigh.BOOLS1,406240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almHighHigh.BOOLS2,406241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almHighHigh.AEBOOLS,406242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almHighHigh.INT1,406243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almHighHigh.INT2,406244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almHighHigh.AENotify,406245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almHighHigh.AESeverity,406246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almHighHigh.AEShelveDuration,406247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almHigh.BOOLS1,406252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almHigh.BOOLS2,406253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almHigh.AEBOOLS,406254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almHigh.INT1,406255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almHigh.INT2,406256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almHigh.AENotify,406257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almHigh.AESeverity,406258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almHigh.AEShelveDuration,406259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almLow.BOOLS1,406264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almLow.BOOLS2,406265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almLow.AEBOOLS,406266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almLow.INT1,406267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almLow.INT2,406268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almLow.AENotify,406269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almLow.AESeverity,406270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almLow.AEShelveDuration,406271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almLowLow.BOOLS1,406276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almLowLow.BOOLS2,406277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almLowLow.AEBOOLS,406278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almLowLow.INT1,406279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almLowLow.INT2,406280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almLowLow.AENotify,406281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almLowLow.AESeverity,406282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almLowLow.AEShelveDuration,406283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almBrokenLoop.BOOLS1,406288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almBrokenLoop.BOOLS2,406289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almBrokenLoop.AEBOOLS,406290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almBrokenLoop.INT1,406291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almBrokenLoop.INT2,406292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almBrokenLoop.AENotify,406293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almBrokenLoop.AESeverity,406294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almBrokenLoop.AEShelveDuration,406295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almOverRange.BOOLS1,406300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almOverRange.BOOLS2,406301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almOverRange.AEBOOLS,406302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almOverRange.INT1,406303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almOverRange.INT2,406304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almOverRange.AENotify,406305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almOverRange.AESeverity,406306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almOverRange.AEShelveDuration,406307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almUnderRange.BOOLS1,406312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almUnderRange.BOOLS2,406313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almUnderRange.AEBOOLS,406314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almUnderRange.INT1,406315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almUnderRange.INT2,406316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almUnderRange.AENotify,406317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almUnderRange.AESeverity,406318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almUnderRange.AEShelveDuration,406319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almRateOfChange.BOOLS1,406324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almRateOfChange.BOOLS2,406325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almRateOfChange.AEBOOLS,406326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almRateOfChange.INT1,406327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almRateOfChange.INT2,406328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almRateOfChange.AENotify,406329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almRateOfChange.AESeverity,406330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almRateOfChange.AEShelveDuration,406331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZI.almPLCFault.BOOLS1,406336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZI.almPLCFault.BOOLS2,406337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZI.almPLCFault.AEBOOLS,406338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZI.almPLCFault.INT1,406339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almPLCFault.INT2,406340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZI.almPLCFault.AENotify,406341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZI.almPLCFault.AESeverity,406342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZI.almPLCFault.AEShelveDuration,406343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almHighHigh.BOOLS1,406440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almHighHigh.BOOLS2,406441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almHighHigh.AEBOOLS,406442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almHighHigh.INT1,406443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almHighHigh.INT2,406444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almHighHigh.AENotify,406445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almHighHigh.AESeverity,406446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almHighHigh.AEShelveDuration,406447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almHigh.BOOLS1,406452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almHigh.BOOLS2,406453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almHigh.AEBOOLS,406454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almHigh.INT1,406455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almHigh.INT2,406456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almHigh.AENotify,406457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almHigh.AESeverity,406458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almHigh.AEShelveDuration,406459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almLow.BOOLS1,406464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almLow.BOOLS2,406465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almLow.AEBOOLS,406466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almLow.INT1,406467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almLow.INT2,406468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almLow.AENotify,406469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almLow.AESeverity,406470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almLow.AEShelveDuration,406471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almLowLow.BOOLS1,406476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almLowLow.BOOLS2,406477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almLowLow.AEBOOLS,406478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almLowLow.INT1,406479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almLowLow.INT2,406480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almLowLow.AENotify,406481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almLowLow.AESeverity,406482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almLowLow.AEShelveDuration,406483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almBrokenLoop.BOOLS1,406488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almBrokenLoop.BOOLS2,406489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almBrokenLoop.AEBOOLS,406490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almBrokenLoop.INT1,406491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almBrokenLoop.INT2,406492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almBrokenLoop.AENotify,406493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almBrokenLoop.AESeverity,406494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almBrokenLoop.AEShelveDuration,406495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almOverRange.BOOLS1,406500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almOverRange.BOOLS2,406501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almOverRange.AEBOOLS,406502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almOverRange.INT1,406503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almOverRange.INT2,406504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almOverRange.AENotify,406505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almOverRange.AESeverity,406506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almOverRange.AEShelveDuration,406507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almUnderRange.BOOLS1,406512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almUnderRange.BOOLS2,406513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almUnderRange.AEBOOLS,406514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almUnderRange.INT1,406515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almUnderRange.INT2,406516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almUnderRange.AENotify,406517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almUnderRange.AESeverity,406518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almUnderRange.AEShelveDuration,406519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almRateOfChange.BOOLS1,406524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almRateOfChange.BOOLS2,406525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almRateOfChange.AEBOOLS,406526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almRateOfChange.INT1,406527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almRateOfChange.INT2,406528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almRateOfChange.AENotify,406529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almRateOfChange.AESeverity,406530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almRateOfChange.AEShelveDuration,406531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZI.almPLCFault.BOOLS1,406536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZI.almPLCFault.BOOLS2,406537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZI.almPLCFault.AEBOOLS,406538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZI.almPLCFault.INT1,406539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almPLCFault.INT2,406540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZI.almPLCFault.AENotify,406541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZI.almPLCFault.AESeverity,406542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZI.almPLCFault.AEShelveDuration,406543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almHighHigh.BOOLS1,406640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almHighHigh.BOOLS2,406641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almHighHigh.AEBOOLS,406642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almHighHigh.INT1,406643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almHighHigh.INT2,406644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almHighHigh.AENotify,406645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almHighHigh.AESeverity,406646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almHighHigh.AEShelveDuration,406647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almHigh.BOOLS1,406652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almHigh.BOOLS2,406653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almHigh.AEBOOLS,406654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almHigh.INT1,406655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almHigh.INT2,406656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almHigh.AENotify,406657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almHigh.AESeverity,406658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almHigh.AEShelveDuration,406659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almLow.BOOLS1,406664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almLow.BOOLS2,406665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almLow.AEBOOLS,406666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almLow.INT1,406667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almLow.INT2,406668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almLow.AENotify,406669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almLow.AESeverity,406670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almLow.AEShelveDuration,406671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almLowLow.BOOLS1,406676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almLowLow.BOOLS2,406677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almLowLow.AEBOOLS,406678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almLowLow.INT1,406679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almLowLow.INT2,406680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almLowLow.AENotify,406681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almLowLow.AESeverity,406682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almLowLow.AEShelveDuration,406683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almBrokenLoop.BOOLS1,406688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almBrokenLoop.BOOLS2,406689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almBrokenLoop.AEBOOLS,406690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almBrokenLoop.INT1,406691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almBrokenLoop.INT2,406692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almBrokenLoop.AENotify,406693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almBrokenLoop.AESeverity,406694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almBrokenLoop.AEShelveDuration,406695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almOverRange.BOOLS1,406700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almOverRange.BOOLS2,406701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almOverRange.AEBOOLS,406702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almOverRange.INT1,406703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almOverRange.INT2,406704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almOverRange.AENotify,406705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almOverRange.AESeverity,406706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almOverRange.AEShelveDuration,406707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almUnderRange.BOOLS1,406712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almUnderRange.BOOLS2,406713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almUnderRange.AEBOOLS,406714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almUnderRange.INT1,406715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almUnderRange.INT2,406716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almUnderRange.AENotify,406717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almUnderRange.AESeverity,406718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almUnderRange.AEShelveDuration,406719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almRateOfChange.BOOLS1,406724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almRateOfChange.BOOLS2,406725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almRateOfChange.AEBOOLS,406726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almRateOfChange.INT1,406727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almRateOfChange.INT2,406728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almRateOfChange.AENotify,406729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almRateOfChange.AESeverity,406730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almRateOfChange.AEShelveDuration,406731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZI.almPLCFault.BOOLS1,406736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZI.almPLCFault.BOOLS2,406737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZI.almPLCFault.AEBOOLS,406738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZI.almPLCFault.INT1,406739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almPLCFault.INT2,406740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZI.almPLCFault.AENotify,406741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZI.almPLCFault.AESeverity,406742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZI.almPLCFault.AEShelveDuration,406743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almHighHigh.BOOLS1,406840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almHighHigh.BOOLS2,406841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almHighHigh.AEBOOLS,406842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almHighHigh.INT1,406843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almHighHigh.INT2,406844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almHighHigh.AENotify,406845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almHighHigh.AESeverity,406846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almHighHigh.AEShelveDuration,406847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almHigh.BOOLS1,406852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almHigh.BOOLS2,406853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almHigh.AEBOOLS,406854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almHigh.INT1,406855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almHigh.INT2,406856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almHigh.AENotify,406857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almHigh.AESeverity,406858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almHigh.AEShelveDuration,406859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almLow.BOOLS1,406864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almLow.BOOLS2,406865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almLow.AEBOOLS,406866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almLow.INT1,406867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almLow.INT2,406868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almLow.AENotify,406869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almLow.AESeverity,406870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almLow.AEShelveDuration,406871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almLowLow.BOOLS1,406876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almLowLow.BOOLS2,406877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almLowLow.AEBOOLS,406878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almLowLow.INT1,406879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almLowLow.INT2,406880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almLowLow.AENotify,406881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almLowLow.AESeverity,406882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almLowLow.AEShelveDuration,406883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almBrokenLoop.BOOLS1,406888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almBrokenLoop.BOOLS2,406889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almBrokenLoop.AEBOOLS,406890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almBrokenLoop.INT1,406891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almBrokenLoop.INT2,406892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almBrokenLoop.AENotify,406893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almBrokenLoop.AESeverity,406894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almBrokenLoop.AEShelveDuration,406895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almOverRange.BOOLS1,406900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almOverRange.BOOLS2,406901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almOverRange.AEBOOLS,406902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almOverRange.INT1,406903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almOverRange.INT2,406904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almOverRange.AENotify,406905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almOverRange.AESeverity,406906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almOverRange.AEShelveDuration,406907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almUnderRange.BOOLS1,406912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almUnderRange.BOOLS2,406913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almUnderRange.AEBOOLS,406914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almUnderRange.INT1,406915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almUnderRange.INT2,406916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almUnderRange.AENotify,406917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almUnderRange.AESeverity,406918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almUnderRange.AEShelveDuration,406919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almRateOfChange.BOOLS1,406924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almRateOfChange.BOOLS2,406925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almRateOfChange.AEBOOLS,406926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almRateOfChange.INT1,406927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almRateOfChange.INT2,406928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almRateOfChange.AENotify,406929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almRateOfChange.AESeverity,406930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almRateOfChange.AEShelveDuration,406931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZI.almPLCFault.BOOLS1,406936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZI.almPLCFault.BOOLS2,406937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZI.almPLCFault.AEBOOLS,406938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZI.almPLCFault.INT1,406939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almPLCFault.INT2,406940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZI.almPLCFault.AENotify,406941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZI.almPLCFault.AESeverity,406942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZI.almPLCFault.AEShelveDuration,406943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almHighHigh.BOOLS1,407040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almHighHigh.BOOLS2,407041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almHighHigh.AEBOOLS,407042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almHighHigh.INT1,407043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almHighHigh.INT2,407044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almHighHigh.AENotify,407045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almHighHigh.AESeverity,407046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almHighHigh.AEShelveDuration,407047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almHigh.BOOLS1,407052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almHigh.BOOLS2,407053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almHigh.AEBOOLS,407054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almHigh.INT1,407055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almHigh.INT2,407056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almHigh.AENotify,407057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almHigh.AESeverity,407058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almHigh.AEShelveDuration,407059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almLow.BOOLS1,407064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almLow.BOOLS2,407065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almLow.AEBOOLS,407066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almLow.INT1,407067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almLow.INT2,407068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almLow.AENotify,407069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almLow.AESeverity,407070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almLow.AEShelveDuration,407071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almLowLow.BOOLS1,407076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almLowLow.BOOLS2,407077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almLowLow.AEBOOLS,407078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almLowLow.INT1,407079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almLowLow.INT2,407080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almLowLow.AENotify,407081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almLowLow.AESeverity,407082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almLowLow.AEShelveDuration,407083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almBrokenLoop.BOOLS1,407088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almBrokenLoop.BOOLS2,407089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almBrokenLoop.AEBOOLS,407090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almBrokenLoop.INT1,407091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almBrokenLoop.INT2,407092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almBrokenLoop.AENotify,407093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almBrokenLoop.AESeverity,407094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almBrokenLoop.AEShelveDuration,407095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almOverRange.BOOLS1,407100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almOverRange.BOOLS2,407101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almOverRange.AEBOOLS,407102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almOverRange.INT1,407103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almOverRange.INT2,407104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almOverRange.AENotify,407105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almOverRange.AESeverity,407106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almOverRange.AEShelveDuration,407107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almUnderRange.BOOLS1,407112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almUnderRange.BOOLS2,407113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almUnderRange.AEBOOLS,407114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almUnderRange.INT1,407115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almUnderRange.INT2,407116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almUnderRange.AENotify,407117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almUnderRange.AESeverity,407118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almUnderRange.AEShelveDuration,407119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almRateOfChange.BOOLS1,407124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almRateOfChange.BOOLS2,407125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almRateOfChange.AEBOOLS,407126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almRateOfChange.INT1,407127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almRateOfChange.INT2,407128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almRateOfChange.AENotify,407129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almRateOfChange.AESeverity,407130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almRateOfChange.AEShelveDuration,407131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI1.almPLCFault.BOOLS1,407136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI1.almPLCFault.BOOLS2,407137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI1.almPLCFault.AEBOOLS,407138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI1.almPLCFault.INT1,407139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almPLCFault.INT2,407140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI1.almPLCFault.AENotify,407141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI1.almPLCFault.AESeverity,407142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI1.almPLCFault.AEShelveDuration,407143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almHighHigh.BOOLS1,407240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almHighHigh.BOOLS2,407241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almHighHigh.AEBOOLS,407242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almHighHigh.INT1,407243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almHighHigh.INT2,407244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almHighHigh.AENotify,407245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almHighHigh.AESeverity,407246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almHighHigh.AEShelveDuration,407247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almHigh.BOOLS1,407252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almHigh.BOOLS2,407253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almHigh.AEBOOLS,407254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almHigh.INT1,407255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almHigh.INT2,407256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almHigh.AENotify,407257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almHigh.AESeverity,407258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almHigh.AEShelveDuration,407259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almLow.BOOLS1,407264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almLow.BOOLS2,407265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almLow.AEBOOLS,407266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almLow.INT1,407267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almLow.INT2,407268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almLow.AENotify,407269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almLow.AESeverity,407270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almLow.AEShelveDuration,407271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almLowLow.BOOLS1,407276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almLowLow.BOOLS2,407277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almLowLow.AEBOOLS,407278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almLowLow.INT1,407279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almLowLow.INT2,407280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almLowLow.AENotify,407281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almLowLow.AESeverity,407282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almLowLow.AEShelveDuration,407283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almBrokenLoop.BOOLS1,407288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almBrokenLoop.BOOLS2,407289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almBrokenLoop.AEBOOLS,407290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almBrokenLoop.INT1,407291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almBrokenLoop.INT2,407292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almBrokenLoop.AENotify,407293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almBrokenLoop.AESeverity,407294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almBrokenLoop.AEShelveDuration,407295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almOverRange.BOOLS1,407300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almOverRange.BOOLS2,407301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almOverRange.AEBOOLS,407302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almOverRange.INT1,407303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almOverRange.INT2,407304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almOverRange.AENotify,407305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almOverRange.AESeverity,407306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almOverRange.AEShelveDuration,407307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almUnderRange.BOOLS1,407312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almUnderRange.BOOLS2,407313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almUnderRange.AEBOOLS,407314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almUnderRange.INT1,407315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almUnderRange.INT2,407316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almUnderRange.AENotify,407317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almUnderRange.AESeverity,407318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almUnderRange.AEShelveDuration,407319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almRateOfChange.BOOLS1,407324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almRateOfChange.BOOLS2,407325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almRateOfChange.AEBOOLS,407326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almRateOfChange.INT1,407327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almRateOfChange.INT2,407328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almRateOfChange.AENotify,407329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almRateOfChange.AESeverity,407330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almRateOfChange.AEShelveDuration,407331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI2.almPLCFault.BOOLS1,407336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI2.almPLCFault.BOOLS2,407337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI2.almPLCFault.AEBOOLS,407338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI2.almPLCFault.INT1,407339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almPLCFault.INT2,407340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI2.almPLCFault.AENotify,407341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI2.almPLCFault.AESeverity,407342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI2.almPLCFault.AEShelveDuration,407343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almHighHigh.BOOLS1,407440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almHighHigh.BOOLS2,407441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almHighHigh.AEBOOLS,407442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almHighHigh.INT1,407443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almHighHigh.INT2,407444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almHighHigh.AENotify,407445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almHighHigh.AESeverity,407446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almHighHigh.AEShelveDuration,407447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almHigh.BOOLS1,407452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almHigh.BOOLS2,407453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almHigh.AEBOOLS,407454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almHigh.INT1,407455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almHigh.INT2,407456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almHigh.AENotify,407457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almHigh.AESeverity,407458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almHigh.AEShelveDuration,407459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almLow.BOOLS1,407464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almLow.BOOLS2,407465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almLow.AEBOOLS,407466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almLow.INT1,407467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almLow.INT2,407468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almLow.AENotify,407469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almLow.AESeverity,407470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almLow.AEShelveDuration,407471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almLowLow.BOOLS1,407476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almLowLow.BOOLS2,407477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almLowLow.AEBOOLS,407478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almLowLow.INT1,407479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almLowLow.INT2,407480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almLowLow.AENotify,407481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almLowLow.AESeverity,407482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almLowLow.AEShelveDuration,407483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almBrokenLoop.BOOLS1,407488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almBrokenLoop.BOOLS2,407489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almBrokenLoop.AEBOOLS,407490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almBrokenLoop.INT1,407491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almBrokenLoop.INT2,407492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almBrokenLoop.AENotify,407493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almBrokenLoop.AESeverity,407494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almBrokenLoop.AEShelveDuration,407495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almOverRange.BOOLS1,407500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almOverRange.BOOLS2,407501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almOverRange.AEBOOLS,407502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almOverRange.INT1,407503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almOverRange.INT2,407504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almOverRange.AENotify,407505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almOverRange.AESeverity,407506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almOverRange.AEShelveDuration,407507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almUnderRange.BOOLS1,407512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almUnderRange.BOOLS2,407513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almUnderRange.AEBOOLS,407514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almUnderRange.INT1,407515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almUnderRange.INT2,407516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almUnderRange.AENotify,407517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almUnderRange.AESeverity,407518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almUnderRange.AEShelveDuration,407519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almRateOfChange.BOOLS1,407524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almRateOfChange.BOOLS2,407525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almRateOfChange.AEBOOLS,407526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almRateOfChange.INT1,407527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almRateOfChange.INT2,407528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almRateOfChange.AENotify,407529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almRateOfChange.AESeverity,407530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almRateOfChange.AEShelveDuration,407531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI3.almPLCFault.BOOLS1,407536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI3.almPLCFault.BOOLS2,407537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI3.almPLCFault.AEBOOLS,407538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI3.almPLCFault.INT1,407539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almPLCFault.INT2,407540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI3.almPLCFault.AENotify,407541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI3.almPLCFault.AESeverity,407542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI3.almPLCFault.AEShelveDuration,407543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almHighHigh.BOOLS1,407640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almHighHigh.BOOLS2,407641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almHighHigh.AEBOOLS,407642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almHighHigh.INT1,407643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almHighHigh.INT2,407644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almHighHigh.AENotify,407645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almHighHigh.AESeverity,407646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almHighHigh.AEShelveDuration,407647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almHigh.BOOLS1,407652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almHigh.BOOLS2,407653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almHigh.AEBOOLS,407654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almHigh.INT1,407655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almHigh.INT2,407656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almHigh.AENotify,407657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almHigh.AESeverity,407658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almHigh.AEShelveDuration,407659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almLow.BOOLS1,407664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almLow.BOOLS2,407665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almLow.AEBOOLS,407666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almLow.INT1,407667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almLow.INT2,407668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almLow.AENotify,407669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almLow.AESeverity,407670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almLow.AEShelveDuration,407671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almLowLow.BOOLS1,407676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almLowLow.BOOLS2,407677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almLowLow.AEBOOLS,407678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almLowLow.INT1,407679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almLowLow.INT2,407680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almLowLow.AENotify,407681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almLowLow.AESeverity,407682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almLowLow.AEShelveDuration,407683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almBrokenLoop.BOOLS1,407688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almBrokenLoop.BOOLS2,407689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almBrokenLoop.AEBOOLS,407690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almBrokenLoop.INT1,407691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almBrokenLoop.INT2,407692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almBrokenLoop.AENotify,407693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almBrokenLoop.AESeverity,407694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almBrokenLoop.AEShelveDuration,407695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almOverRange.BOOLS1,407700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almOverRange.BOOLS2,407701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almOverRange.AEBOOLS,407702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almOverRange.INT1,407703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almOverRange.INT2,407704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almOverRange.AENotify,407705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almOverRange.AESeverity,407706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almOverRange.AEShelveDuration,407707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almUnderRange.BOOLS1,407712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almUnderRange.BOOLS2,407713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almUnderRange.AEBOOLS,407714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almUnderRange.INT1,407715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almUnderRange.INT2,407716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almUnderRange.AENotify,407717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almUnderRange.AESeverity,407718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almUnderRange.AEShelveDuration,407719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almRateOfChange.BOOLS1,407724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almRateOfChange.BOOLS2,407725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almRateOfChange.AEBOOLS,407726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almRateOfChange.INT1,407727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almRateOfChange.INT2,407728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almRateOfChange.AENotify,407729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almRateOfChange.AESeverity,407730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almRateOfChange.AEShelveDuration,407731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_1_VI4.almPLCFault.BOOLS1,407736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_1_VI4.almPLCFault.BOOLS2,407737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_1_VI4.almPLCFault.AEBOOLS,407738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_1_VI4.almPLCFault.INT1,407739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almPLCFault.INT2,407740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_1_VI4.almPLCFault.AENotify,407741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_1_VI4.almPLCFault.AESeverity,407742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_1_VI4.almPLCFault.AEShelveDuration,407743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almHighHigh.BOOLS1,407840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almHighHigh.BOOLS2,407841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almHighHigh.AEBOOLS,407842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almHighHigh.INT1,407843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almHighHigh.INT2,407844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almHighHigh.AENotify,407845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almHighHigh.AESeverity,407846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almHighHigh.AEShelveDuration,407847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almHigh.BOOLS1,407852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almHigh.BOOLS2,407853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almHigh.AEBOOLS,407854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almHigh.INT1,407855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almHigh.INT2,407856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almHigh.AENotify,407857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almHigh.AESeverity,407858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almHigh.AEShelveDuration,407859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almLow.BOOLS1,407864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almLow.BOOLS2,407865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almLow.AEBOOLS,407866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almLow.INT1,407867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almLow.INT2,407868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almLow.AENotify,407869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almLow.AESeverity,407870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almLow.AEShelveDuration,407871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almLowLow.BOOLS1,407876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almLowLow.BOOLS2,407877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almLowLow.AEBOOLS,407878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almLowLow.INT1,407879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almLowLow.INT2,407880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almLowLow.AENotify,407881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almLowLow.AESeverity,407882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almLowLow.AEShelveDuration,407883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almBrokenLoop.BOOLS1,407888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almBrokenLoop.BOOLS2,407889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almBrokenLoop.AEBOOLS,407890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almBrokenLoop.INT1,407891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almBrokenLoop.INT2,407892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almBrokenLoop.AENotify,407893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almBrokenLoop.AESeverity,407894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almBrokenLoop.AEShelveDuration,407895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almOverRange.BOOLS1,407900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almOverRange.BOOLS2,407901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almOverRange.AEBOOLS,407902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almOverRange.INT1,407903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almOverRange.INT2,407904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almOverRange.AENotify,407905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almOverRange.AESeverity,407906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almOverRange.AEShelveDuration,407907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almUnderRange.BOOLS1,407912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almUnderRange.BOOLS2,407913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almUnderRange.AEBOOLS,407914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almUnderRange.INT1,407915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almUnderRange.INT2,407916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almUnderRange.AENotify,407917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almUnderRange.AESeverity,407918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almUnderRange.AEShelveDuration,407919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almRateOfChange.BOOLS1,407924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almRateOfChange.BOOLS2,407925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almRateOfChange.AEBOOLS,407926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almRateOfChange.INT1,407927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almRateOfChange.INT2,407928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almRateOfChange.AENotify,407929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almRateOfChange.AESeverity,407930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almRateOfChange.AEShelveDuration,407931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI1.almPLCFault.BOOLS1,407936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI1.almPLCFault.BOOLS2,407937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI1.almPLCFault.AEBOOLS,407938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI1.almPLCFault.INT1,407939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almPLCFault.INT2,407940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI1.almPLCFault.AENotify,407941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI1.almPLCFault.AESeverity,407942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI1.almPLCFault.AEShelveDuration,407943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almHighHigh.BOOLS1,408040,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almHighHigh.BOOLS2,408041,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almHighHigh.AEBOOLS,408042,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almHighHigh.INT1,408043,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almHighHigh.INT2,408044,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almHighHigh.AENotify,408045,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almHighHigh.AESeverity,408046,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almHighHigh.AEShelveDuration,408047,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almHigh.BOOLS1,408052,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almHigh.BOOLS2,408053,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almHigh.AEBOOLS,408054,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almHigh.INT1,408055,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almHigh.INT2,408056,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almHigh.AENotify,408057,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almHigh.AESeverity,408058,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almHigh.AEShelveDuration,408059,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almLow.BOOLS1,408064,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almLow.BOOLS2,408065,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almLow.AEBOOLS,408066,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almLow.INT1,408067,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almLow.INT2,408068,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almLow.AENotify,408069,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almLow.AESeverity,408070,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almLow.AEShelveDuration,408071,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almLowLow.BOOLS1,408076,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almLowLow.BOOLS2,408077,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almLowLow.AEBOOLS,408078,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almLowLow.INT1,408079,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almLowLow.INT2,408080,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almLowLow.AENotify,408081,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almLowLow.AESeverity,408082,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almLowLow.AEShelveDuration,408083,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almBrokenLoop.BOOLS1,408088,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almBrokenLoop.BOOLS2,408089,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almBrokenLoop.AEBOOLS,408090,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almBrokenLoop.INT1,408091,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almBrokenLoop.INT2,408092,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almBrokenLoop.AENotify,408093,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almBrokenLoop.AESeverity,408094,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almBrokenLoop.AEShelveDuration,408095,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almOverRange.BOOLS1,408100,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almOverRange.BOOLS2,408101,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almOverRange.AEBOOLS,408102,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almOverRange.INT1,408103,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almOverRange.INT2,408104,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almOverRange.AENotify,408105,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almOverRange.AESeverity,408106,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almOverRange.AEShelveDuration,408107,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almUnderRange.BOOLS1,408112,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almUnderRange.BOOLS2,408113,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almUnderRange.AEBOOLS,408114,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almUnderRange.INT1,408115,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almUnderRange.INT2,408116,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almUnderRange.AENotify,408117,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almUnderRange.AESeverity,408118,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almUnderRange.AEShelveDuration,408119,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almRateOfChange.BOOLS1,408124,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almRateOfChange.BOOLS2,408125,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almRateOfChange.AEBOOLS,408126,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almRateOfChange.INT1,408127,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almRateOfChange.INT2,408128,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almRateOfChange.AENotify,408129,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almRateOfChange.AESeverity,408130,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almRateOfChange.AEShelveDuration,408131,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI2.almPLCFault.BOOLS1,408136,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI2.almPLCFault.BOOLS2,408137,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI2.almPLCFault.AEBOOLS,408138,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI2.almPLCFault.INT1,408139,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almPLCFault.INT2,408140,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI2.almPLCFault.AENotify,408141,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI2.almPLCFault.AESeverity,408142,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI2.almPLCFault.AEShelveDuration,408143,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almHighHigh.BOOLS1,408240,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almHighHigh.BOOLS2,408241,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almHighHigh.AEBOOLS,408242,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almHighHigh.INT1,408243,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almHighHigh.INT2,408244,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almHighHigh.AENotify,408245,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almHighHigh.AESeverity,408246,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almHighHigh.AEShelveDuration,408247,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almHigh.BOOLS1,408252,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almHigh.BOOLS2,408253,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almHigh.AEBOOLS,408254,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almHigh.INT1,408255,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almHigh.INT2,408256,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almHigh.AENotify,408257,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almHigh.AESeverity,408258,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almHigh.AEShelveDuration,408259,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almLow.BOOLS1,408264,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almLow.BOOLS2,408265,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almLow.AEBOOLS,408266,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almLow.INT1,408267,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almLow.INT2,408268,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almLow.AENotify,408269,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almLow.AESeverity,408270,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almLow.AEShelveDuration,408271,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almLowLow.BOOLS1,408276,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almLowLow.BOOLS2,408277,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almLowLow.AEBOOLS,408278,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almLowLow.INT1,408279,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almLowLow.INT2,408280,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almLowLow.AENotify,408281,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almLowLow.AESeverity,408282,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almLowLow.AEShelveDuration,408283,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almBrokenLoop.BOOLS1,408288,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almBrokenLoop.BOOLS2,408289,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almBrokenLoop.AEBOOLS,408290,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almBrokenLoop.INT1,408291,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almBrokenLoop.INT2,408292,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almBrokenLoop.AENotify,408293,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almBrokenLoop.AESeverity,408294,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almBrokenLoop.AEShelveDuration,408295,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almOverRange.BOOLS1,408300,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almOverRange.BOOLS2,408301,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almOverRange.AEBOOLS,408302,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almOverRange.INT1,408303,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almOverRange.INT2,408304,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almOverRange.AENotify,408305,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almOverRange.AESeverity,408306,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almOverRange.AEShelveDuration,408307,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almUnderRange.BOOLS1,408312,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almUnderRange.BOOLS2,408313,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almUnderRange.AEBOOLS,408314,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almUnderRange.INT1,408315,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almUnderRange.INT2,408316,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almUnderRange.AENotify,408317,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almUnderRange.AESeverity,408318,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almUnderRange.AEShelveDuration,408319,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almRateOfChange.BOOLS1,408324,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almRateOfChange.BOOLS2,408325,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almRateOfChange.AEBOOLS,408326,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almRateOfChange.INT1,408327,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almRateOfChange.INT2,408328,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almRateOfChange.AENotify,408329,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almRateOfChange.AESeverity,408330,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almRateOfChange.AEShelveDuration,408331,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI3.almPLCFault.BOOLS1,408336,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI3.almPLCFault.BOOLS2,408337,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI3.almPLCFault.AEBOOLS,408338,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI3.almPLCFault.INT1,408339,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almPLCFault.INT2,408340,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI3.almPLCFault.AENotify,408341,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI3.almPLCFault.AESeverity,408342,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI3.almPLCFault.AEShelveDuration,408343,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almHighHigh.BOOLS1,408440,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almHighHigh.BOOLS2,408441,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almHighHigh.AEBOOLS,408442,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almHighHigh.INT1,408443,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almHighHigh.INT2,408444,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almHighHigh.AENotify,408445,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almHighHigh.AESeverity,408446,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almHighHigh.AEShelveDuration,408447,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almHigh.BOOLS1,408452,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almHigh.BOOLS2,408453,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almHigh.AEBOOLS,408454,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almHigh.INT1,408455,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almHigh.INT2,408456,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almHigh.AENotify,408457,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almHigh.AESeverity,408458,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almHigh.AEShelveDuration,408459,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almLow.BOOLS1,408464,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almLow.BOOLS2,408465,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almLow.AEBOOLS,408466,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almLow.INT1,408467,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almLow.INT2,408468,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almLow.AENotify,408469,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almLow.AESeverity,408470,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almLow.AEShelveDuration,408471,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almLowLow.BOOLS1,408476,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almLowLow.BOOLS2,408477,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almLowLow.AEBOOLS,408478,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almLowLow.INT1,408479,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almLowLow.INT2,408480,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almLowLow.AENotify,408481,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almLowLow.AESeverity,408482,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almLowLow.AEShelveDuration,408483,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almBrokenLoop.BOOLS1,408488,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almBrokenLoop.BOOLS2,408489,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almBrokenLoop.AEBOOLS,408490,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almBrokenLoop.INT1,408491,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almBrokenLoop.INT2,408492,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almBrokenLoop.AENotify,408493,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almBrokenLoop.AESeverity,408494,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almBrokenLoop.AEShelveDuration,408495,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almOverRange.BOOLS1,408500,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almOverRange.BOOLS2,408501,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almOverRange.AEBOOLS,408502,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almOverRange.INT1,408503,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almOverRange.INT2,408504,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almOverRange.AENotify,408505,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almOverRange.AESeverity,408506,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almOverRange.AEShelveDuration,408507,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almUnderRange.BOOLS1,408512,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almUnderRange.BOOLS2,408513,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almUnderRange.AEBOOLS,408514,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almUnderRange.INT1,408515,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almUnderRange.INT2,408516,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almUnderRange.AENotify,408517,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almUnderRange.AESeverity,408518,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almUnderRange.AEShelveDuration,408519,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almRateOfChange.BOOLS1,408524,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almRateOfChange.BOOLS2,408525,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almRateOfChange.AEBOOLS,408526,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almRateOfChange.INT1,408527,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almRateOfChange.INT2,408528,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almRateOfChange.AENotify,408529,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almRateOfChange.AESeverity,408530,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almRateOfChange.AEShelveDuration,408531,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_2_VI4.almPLCFault.BOOLS1,408536,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_2_VI4.almPLCFault.BOOLS2,408537,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_2_VI4.almPLCFault.AEBOOLS,408538,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_2_VI4.almPLCFault.INT1,408539,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almPLCFault.INT2,408540,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_2_VI4.almPLCFault.AENotify,408541,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_2_VI4.almPLCFault.AESeverity,408542,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_2_VI4.almPLCFault.AEShelveDuration,408543,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almHighHigh.BOOLS1,408640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almHighHigh.BOOLS2,408641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almHighHigh.AEBOOLS,408642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almHighHigh.INT1,408643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almHighHigh.INT2,408644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almHighHigh.AENotify,408645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almHighHigh.AESeverity,408646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almHighHigh.AEShelveDuration,408647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almHigh.BOOLS1,408652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almHigh.BOOLS2,408653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almHigh.AEBOOLS,408654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almHigh.INT1,408655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almHigh.INT2,408656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almHigh.AENotify,408657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almHigh.AESeverity,408658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almHigh.AEShelveDuration,408659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almLow.BOOLS1,408664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almLow.BOOLS2,408665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almLow.AEBOOLS,408666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almLow.INT1,408667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almLow.INT2,408668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almLow.AENotify,408669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almLow.AESeverity,408670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almLow.AEShelveDuration,408671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almLowLow.BOOLS1,408676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almLowLow.BOOLS2,408677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almLowLow.AEBOOLS,408678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almLowLow.INT1,408679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almLowLow.INT2,408680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almLowLow.AENotify,408681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almLowLow.AESeverity,408682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almLowLow.AEShelveDuration,408683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almBrokenLoop.BOOLS1,408688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almBrokenLoop.BOOLS2,408689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almBrokenLoop.AEBOOLS,408690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almBrokenLoop.INT1,408691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almBrokenLoop.INT2,408692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almBrokenLoop.AENotify,408693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almBrokenLoop.AESeverity,408694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almBrokenLoop.AEShelveDuration,408695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almOverRange.BOOLS1,408700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almOverRange.BOOLS2,408701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almOverRange.AEBOOLS,408702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almOverRange.INT1,408703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almOverRange.INT2,408704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almOverRange.AENotify,408705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almOverRange.AESeverity,408706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almOverRange.AEShelveDuration,408707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almUnderRange.BOOLS1,408712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almUnderRange.BOOLS2,408713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almUnderRange.AEBOOLS,408714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almUnderRange.INT1,408715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almUnderRange.INT2,408716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almUnderRange.AENotify,408717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almUnderRange.AESeverity,408718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almUnderRange.AEShelveDuration,408719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almRateOfChange.BOOLS1,408724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almRateOfChange.BOOLS2,408725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almRateOfChange.AEBOOLS,408726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almRateOfChange.INT1,408727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almRateOfChange.INT2,408728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almRateOfChange.AENotify,408729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almRateOfChange.AESeverity,408730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almRateOfChange.AEShelveDuration,408731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI1.almPLCFault.BOOLS1,408736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI1.almPLCFault.BOOLS2,408737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI1.almPLCFault.AEBOOLS,408738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI1.almPLCFault.INT1,408739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almPLCFault.INT2,408740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI1.almPLCFault.AENotify,408741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI1.almPLCFault.AESeverity,408742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI1.almPLCFault.AEShelveDuration,408743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almHighHigh.BOOLS1,408840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almHighHigh.BOOLS2,408841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almHighHigh.AEBOOLS,408842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almHighHigh.INT1,408843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almHighHigh.INT2,408844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almHighHigh.AENotify,408845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almHighHigh.AESeverity,408846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almHighHigh.AEShelveDuration,408847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almHigh.BOOLS1,408852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almHigh.BOOLS2,408853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almHigh.AEBOOLS,408854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almHigh.INT1,408855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almHigh.INT2,408856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almHigh.AENotify,408857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almHigh.AESeverity,408858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almHigh.AEShelveDuration,408859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almLow.BOOLS1,408864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almLow.BOOLS2,408865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almLow.AEBOOLS,408866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almLow.INT1,408867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almLow.INT2,408868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almLow.AENotify,408869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almLow.AESeverity,408870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almLow.AEShelveDuration,408871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almLowLow.BOOLS1,408876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almLowLow.BOOLS2,408877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almLowLow.AEBOOLS,408878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almLowLow.INT1,408879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almLowLow.INT2,408880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almLowLow.AENotify,408881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almLowLow.AESeverity,408882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almLowLow.AEShelveDuration,408883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almBrokenLoop.BOOLS1,408888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almBrokenLoop.BOOLS2,408889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almBrokenLoop.AEBOOLS,408890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almBrokenLoop.INT1,408891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almBrokenLoop.INT2,408892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almBrokenLoop.AENotify,408893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almBrokenLoop.AESeverity,408894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almBrokenLoop.AEShelveDuration,408895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almOverRange.BOOLS1,408900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almOverRange.BOOLS2,408901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almOverRange.AEBOOLS,408902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almOverRange.INT1,408903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almOverRange.INT2,408904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almOverRange.AENotify,408905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almOverRange.AESeverity,408906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almOverRange.AEShelveDuration,408907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almUnderRange.BOOLS1,408912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almUnderRange.BOOLS2,408913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almUnderRange.AEBOOLS,408914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almUnderRange.INT1,408915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almUnderRange.INT2,408916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almUnderRange.AENotify,408917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almUnderRange.AESeverity,408918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almUnderRange.AEShelveDuration,408919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almRateOfChange.BOOLS1,408924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almRateOfChange.BOOLS2,408925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almRateOfChange.AEBOOLS,408926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almRateOfChange.INT1,408927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almRateOfChange.INT2,408928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almRateOfChange.AENotify,408929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almRateOfChange.AESeverity,408930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almRateOfChange.AEShelveDuration,408931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI2.almPLCFault.BOOLS1,408936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI2.almPLCFault.BOOLS2,408937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI2.almPLCFault.AEBOOLS,408938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI2.almPLCFault.INT1,408939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almPLCFault.INT2,408940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI2.almPLCFault.AENotify,408941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI2.almPLCFault.AESeverity,408942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI2.almPLCFault.AEShelveDuration,408943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almHighHigh.BOOLS1,409040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almHighHigh.BOOLS2,409041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almHighHigh.AEBOOLS,409042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almHighHigh.INT1,409043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almHighHigh.INT2,409044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almHighHigh.AENotify,409045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almHighHigh.AESeverity,409046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almHighHigh.AEShelveDuration,409047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almHigh.BOOLS1,409052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almHigh.BOOLS2,409053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almHigh.AEBOOLS,409054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almHigh.INT1,409055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almHigh.INT2,409056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almHigh.AENotify,409057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almHigh.AESeverity,409058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almHigh.AEShelveDuration,409059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almLow.BOOLS1,409064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almLow.BOOLS2,409065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almLow.AEBOOLS,409066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almLow.INT1,409067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almLow.INT2,409068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almLow.AENotify,409069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almLow.AESeverity,409070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almLow.AEShelveDuration,409071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almLowLow.BOOLS1,409076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almLowLow.BOOLS2,409077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almLowLow.AEBOOLS,409078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almLowLow.INT1,409079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almLowLow.INT2,409080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almLowLow.AENotify,409081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almLowLow.AESeverity,409082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almLowLow.AEShelveDuration,409083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almBrokenLoop.BOOLS1,409088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almBrokenLoop.BOOLS2,409089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almBrokenLoop.AEBOOLS,409090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almBrokenLoop.INT1,409091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almBrokenLoop.INT2,409092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almBrokenLoop.AENotify,409093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almBrokenLoop.AESeverity,409094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almBrokenLoop.AEShelveDuration,409095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almOverRange.BOOLS1,409100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almOverRange.BOOLS2,409101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almOverRange.AEBOOLS,409102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almOverRange.INT1,409103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almOverRange.INT2,409104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almOverRange.AENotify,409105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almOverRange.AESeverity,409106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almOverRange.AEShelveDuration,409107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almUnderRange.BOOLS1,409112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almUnderRange.BOOLS2,409113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almUnderRange.AEBOOLS,409114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almUnderRange.INT1,409115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almUnderRange.INT2,409116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almUnderRange.AENotify,409117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almUnderRange.AESeverity,409118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almUnderRange.AEShelveDuration,409119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almRateOfChange.BOOLS1,409124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almRateOfChange.BOOLS2,409125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almRateOfChange.AEBOOLS,409126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almRateOfChange.INT1,409127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almRateOfChange.INT2,409128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almRateOfChange.AENotify,409129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almRateOfChange.AESeverity,409130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almRateOfChange.AEShelveDuration,409131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI3.almPLCFault.BOOLS1,409136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI3.almPLCFault.BOOLS2,409137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI3.almPLCFault.AEBOOLS,409138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI3.almPLCFault.INT1,409139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almPLCFault.INT2,409140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI3.almPLCFault.AENotify,409141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI3.almPLCFault.AESeverity,409142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI3.almPLCFault.AEShelveDuration,409143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almHighHigh.BOOLS1,409240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almHighHigh.BOOLS2,409241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almHighHigh.AEBOOLS,409242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almHighHigh.INT1,409243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almHighHigh.INT2,409244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almHighHigh.AENotify,409245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almHighHigh.AESeverity,409246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almHighHigh.AEShelveDuration,409247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almHigh.BOOLS1,409252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almHigh.BOOLS2,409253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almHigh.AEBOOLS,409254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almHigh.INT1,409255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almHigh.INT2,409256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almHigh.AENotify,409257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almHigh.AESeverity,409258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almHigh.AEShelveDuration,409259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almLow.BOOLS1,409264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almLow.BOOLS2,409265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almLow.AEBOOLS,409266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almLow.INT1,409267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almLow.INT2,409268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almLow.AENotify,409269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almLow.AESeverity,409270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almLow.AEShelveDuration,409271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almLowLow.BOOLS1,409276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almLowLow.BOOLS2,409277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almLowLow.AEBOOLS,409278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almLowLow.INT1,409279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almLowLow.INT2,409280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almLowLow.AENotify,409281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almLowLow.AESeverity,409282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almLowLow.AEShelveDuration,409283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almBrokenLoop.BOOLS1,409288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almBrokenLoop.BOOLS2,409289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almBrokenLoop.AEBOOLS,409290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almBrokenLoop.INT1,409291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almBrokenLoop.INT2,409292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almBrokenLoop.AENotify,409293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almBrokenLoop.AESeverity,409294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almBrokenLoop.AEShelveDuration,409295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almOverRange.BOOLS1,409300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almOverRange.BOOLS2,409301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almOverRange.AEBOOLS,409302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almOverRange.INT1,409303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almOverRange.INT2,409304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almOverRange.AENotify,409305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almOverRange.AESeverity,409306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almOverRange.AEShelveDuration,409307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almUnderRange.BOOLS1,409312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almUnderRange.BOOLS2,409313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almUnderRange.AEBOOLS,409314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almUnderRange.INT1,409315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almUnderRange.INT2,409316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almUnderRange.AENotify,409317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almUnderRange.AESeverity,409318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almUnderRange.AEShelveDuration,409319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almRateOfChange.BOOLS1,409324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almRateOfChange.BOOLS2,409325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almRateOfChange.AEBOOLS,409326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almRateOfChange.INT1,409327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almRateOfChange.INT2,409328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almRateOfChange.AENotify,409329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almRateOfChange.AESeverity,409330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almRateOfChange.AEShelveDuration,409331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_3_VI4.almPLCFault.BOOLS1,409336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_3_VI4.almPLCFault.BOOLS2,409337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_3_VI4.almPLCFault.AEBOOLS,409338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_3_VI4.almPLCFault.INT1,409339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almPLCFault.INT2,409340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_3_VI4.almPLCFault.AENotify,409341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_3_VI4.almPLCFault.AESeverity,409342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_3_VI4.almPLCFault.AEShelveDuration,409343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almHighHigh.BOOLS1,409440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almHighHigh.BOOLS2,409441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almHighHigh.AEBOOLS,409442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almHighHigh.INT1,409443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almHighHigh.INT2,409444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almHighHigh.AENotify,409445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almHighHigh.AESeverity,409446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almHighHigh.AEShelveDuration,409447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almHigh.BOOLS1,409452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almHigh.BOOLS2,409453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almHigh.AEBOOLS,409454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almHigh.INT1,409455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almHigh.INT2,409456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almHigh.AENotify,409457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almHigh.AESeverity,409458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almHigh.AEShelveDuration,409459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almLow.BOOLS1,409464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almLow.BOOLS2,409465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almLow.AEBOOLS,409466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almLow.INT1,409467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almLow.INT2,409468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almLow.AENotify,409469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almLow.AESeverity,409470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almLow.AEShelveDuration,409471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almLowLow.BOOLS1,409476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almLowLow.BOOLS2,409477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almLowLow.AEBOOLS,409478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almLowLow.INT1,409479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almLowLow.INT2,409480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almLowLow.AENotify,409481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almLowLow.AESeverity,409482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almLowLow.AEShelveDuration,409483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almBrokenLoop.BOOLS1,409488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almBrokenLoop.BOOLS2,409489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almBrokenLoop.AEBOOLS,409490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almBrokenLoop.INT1,409491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almBrokenLoop.INT2,409492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almBrokenLoop.AENotify,409493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almBrokenLoop.AESeverity,409494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almBrokenLoop.AEShelveDuration,409495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almOverRange.BOOLS1,409500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almOverRange.BOOLS2,409501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almOverRange.AEBOOLS,409502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almOverRange.INT1,409503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almOverRange.INT2,409504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almOverRange.AENotify,409505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almOverRange.AESeverity,409506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almOverRange.AEShelveDuration,409507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almUnderRange.BOOLS1,409512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almUnderRange.BOOLS2,409513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almUnderRange.AEBOOLS,409514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almUnderRange.INT1,409515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almUnderRange.INT2,409516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almUnderRange.AENotify,409517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almUnderRange.AESeverity,409518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almUnderRange.AEShelveDuration,409519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almRateOfChange.BOOLS1,409524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almRateOfChange.BOOLS2,409525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almRateOfChange.AEBOOLS,409526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almRateOfChange.INT1,409527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almRateOfChange.INT2,409528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almRateOfChange.AENotify,409529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almRateOfChange.AESeverity,409530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almRateOfChange.AEShelveDuration,409531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI1.almPLCFault.BOOLS1,409536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI1.almPLCFault.BOOLS2,409537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI1.almPLCFault.AEBOOLS,409538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI1.almPLCFault.INT1,409539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almPLCFault.INT2,409540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI1.almPLCFault.AENotify,409541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI1.almPLCFault.AESeverity,409542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI1.almPLCFault.AEShelveDuration,409543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almHighHigh.BOOLS1,409640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almHighHigh.BOOLS2,409641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almHighHigh.AEBOOLS,409642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almHighHigh.INT1,409643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almHighHigh.INT2,409644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almHighHigh.AENotify,409645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almHighHigh.AESeverity,409646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almHighHigh.AEShelveDuration,409647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almHigh.BOOLS1,409652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almHigh.BOOLS2,409653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almHigh.AEBOOLS,409654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almHigh.INT1,409655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almHigh.INT2,409656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almHigh.AENotify,409657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almHigh.AESeverity,409658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almHigh.AEShelveDuration,409659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almLow.BOOLS1,409664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almLow.BOOLS2,409665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almLow.AEBOOLS,409666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almLow.INT1,409667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almLow.INT2,409668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almLow.AENotify,409669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almLow.AESeverity,409670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almLow.AEShelveDuration,409671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almLowLow.BOOLS1,409676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almLowLow.BOOLS2,409677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almLowLow.AEBOOLS,409678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almLowLow.INT1,409679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almLowLow.INT2,409680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almLowLow.AENotify,409681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almLowLow.AESeverity,409682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almLowLow.AEShelveDuration,409683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almBrokenLoop.BOOLS1,409688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almBrokenLoop.BOOLS2,409689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almBrokenLoop.AEBOOLS,409690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almBrokenLoop.INT1,409691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almBrokenLoop.INT2,409692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almBrokenLoop.AENotify,409693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almBrokenLoop.AESeverity,409694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almBrokenLoop.AEShelveDuration,409695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almOverRange.BOOLS1,409700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almOverRange.BOOLS2,409701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almOverRange.AEBOOLS,409702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almOverRange.INT1,409703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almOverRange.INT2,409704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almOverRange.AENotify,409705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almOverRange.AESeverity,409706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almOverRange.AEShelveDuration,409707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almUnderRange.BOOLS1,409712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almUnderRange.BOOLS2,409713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almUnderRange.AEBOOLS,409714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almUnderRange.INT1,409715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almUnderRange.INT2,409716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almUnderRange.AENotify,409717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almUnderRange.AESeverity,409718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almUnderRange.AEShelveDuration,409719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almRateOfChange.BOOLS1,409724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almRateOfChange.BOOLS2,409725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almRateOfChange.AEBOOLS,409726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almRateOfChange.INT1,409727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almRateOfChange.INT2,409728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almRateOfChange.AENotify,409729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almRateOfChange.AESeverity,409730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almRateOfChange.AEShelveDuration,409731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI2.almPLCFault.BOOLS1,409736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI2.almPLCFault.BOOLS2,409737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI2.almPLCFault.AEBOOLS,409738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI2.almPLCFault.INT1,409739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almPLCFault.INT2,409740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI2.almPLCFault.AENotify,409741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI2.almPLCFault.AESeverity,409742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI2.almPLCFault.AEShelveDuration,409743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almHighHigh.BOOLS1,409840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almHighHigh.BOOLS2,409841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almHighHigh.AEBOOLS,409842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almHighHigh.INT1,409843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almHighHigh.INT2,409844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almHighHigh.AENotify,409845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almHighHigh.AESeverity,409846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almHighHigh.AEShelveDuration,409847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almHigh.BOOLS1,409852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almHigh.BOOLS2,409853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almHigh.AEBOOLS,409854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almHigh.INT1,409855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almHigh.INT2,409856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almHigh.AENotify,409857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almHigh.AESeverity,409858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almHigh.AEShelveDuration,409859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almLow.BOOLS1,409864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almLow.BOOLS2,409865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almLow.AEBOOLS,409866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almLow.INT1,409867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almLow.INT2,409868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almLow.AENotify,409869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almLow.AESeverity,409870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almLow.AEShelveDuration,409871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almLowLow.BOOLS1,409876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almLowLow.BOOLS2,409877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almLowLow.AEBOOLS,409878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almLowLow.INT1,409879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almLowLow.INT2,409880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almLowLow.AENotify,409881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almLowLow.AESeverity,409882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almLowLow.AEShelveDuration,409883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almBrokenLoop.BOOLS1,409888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almBrokenLoop.BOOLS2,409889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almBrokenLoop.AEBOOLS,409890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almBrokenLoop.INT1,409891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almBrokenLoop.INT2,409892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almBrokenLoop.AENotify,409893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almBrokenLoop.AESeverity,409894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almBrokenLoop.AEShelveDuration,409895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almOverRange.BOOLS1,409900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almOverRange.BOOLS2,409901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almOverRange.AEBOOLS,409902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almOverRange.INT1,409903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almOverRange.INT2,409904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almOverRange.AENotify,409905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almOverRange.AESeverity,409906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almOverRange.AEShelveDuration,409907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almUnderRange.BOOLS1,409912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almUnderRange.BOOLS2,409913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almUnderRange.AEBOOLS,409914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almUnderRange.INT1,409915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almUnderRange.INT2,409916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almUnderRange.AENotify,409917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almUnderRange.AESeverity,409918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almUnderRange.AEShelveDuration,409919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almRateOfChange.BOOLS1,409924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almRateOfChange.BOOLS2,409925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almRateOfChange.AEBOOLS,409926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almRateOfChange.INT1,409927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almRateOfChange.INT2,409928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almRateOfChange.AENotify,409929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almRateOfChange.AESeverity,409930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almRateOfChange.AEShelveDuration,409931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI3.almPLCFault.BOOLS1,409936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI3.almPLCFault.BOOLS2,409937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI3.almPLCFault.AEBOOLS,409938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI3.almPLCFault.INT1,409939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almPLCFault.INT2,409940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI3.almPLCFault.AENotify,409941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI3.almPLCFault.AESeverity,409942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI3.almPLCFault.AEShelveDuration,409943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almHighHigh.BOOLS1,410040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almHighHigh.BOOLS2,410041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almHighHigh.AEBOOLS,410042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almHighHigh.INT1,410043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almHighHigh.INT2,410044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almHighHigh.AENotify,410045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almHighHigh.AESeverity,410046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almHighHigh.AEShelveDuration,410047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almHigh.BOOLS1,410052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almHigh.BOOLS2,410053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almHigh.AEBOOLS,410054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almHigh.INT1,410055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almHigh.INT2,410056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almHigh.AENotify,410057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almHigh.AESeverity,410058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almHigh.AEShelveDuration,410059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almLow.BOOLS1,410064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almLow.BOOLS2,410065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almLow.AEBOOLS,410066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almLow.INT1,410067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almLow.INT2,410068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almLow.AENotify,410069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almLow.AESeverity,410070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almLow.AEShelveDuration,410071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almLowLow.BOOLS1,410076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almLowLow.BOOLS2,410077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almLowLow.AEBOOLS,410078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almLowLow.INT1,410079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almLowLow.INT2,410080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almLowLow.AENotify,410081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almLowLow.AESeverity,410082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almLowLow.AEShelveDuration,410083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almBrokenLoop.BOOLS1,410088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almBrokenLoop.BOOLS2,410089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almBrokenLoop.AEBOOLS,410090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almBrokenLoop.INT1,410091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almBrokenLoop.INT2,410092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almBrokenLoop.AENotify,410093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almBrokenLoop.AESeverity,410094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almBrokenLoop.AEShelveDuration,410095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almOverRange.BOOLS1,410100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almOverRange.BOOLS2,410101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almOverRange.AEBOOLS,410102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almOverRange.INT1,410103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almOverRange.INT2,410104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almOverRange.AENotify,410105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almOverRange.AESeverity,410106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almOverRange.AEShelveDuration,410107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almUnderRange.BOOLS1,410112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almUnderRange.BOOLS2,410113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almUnderRange.AEBOOLS,410114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almUnderRange.INT1,410115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almUnderRange.INT2,410116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almUnderRange.AENotify,410117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almUnderRange.AESeverity,410118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almUnderRange.AEShelveDuration,410119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almRateOfChange.BOOLS1,410124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almRateOfChange.BOOLS2,410125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almRateOfChange.AEBOOLS,410126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almRateOfChange.INT1,410127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almRateOfChange.INT2,410128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almRateOfChange.AENotify,410129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almRateOfChange.AESeverity,410130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almRateOfChange.AEShelveDuration,410131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_4_VI4.almPLCFault.BOOLS1,410136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_4_VI4.almPLCFault.BOOLS2,410137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_4_VI4.almPLCFault.AEBOOLS,410138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_4_VI4.almPLCFault.INT1,410139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almPLCFault.INT2,410140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_4_VI4.almPLCFault.AENotify,410141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_4_VI4.almPLCFault.AESeverity,410142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_4_VI4.almPLCFault.AEShelveDuration,410143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almHighHigh.BOOLS1,410240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almHighHigh.BOOLS2,410241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almHighHigh.AEBOOLS,410242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almHighHigh.INT1,410243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almHighHigh.INT2,410244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almHighHigh.AENotify,410245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almHighHigh.AESeverity,410246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almHighHigh.AEShelveDuration,410247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almHigh.BOOLS1,410252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almHigh.BOOLS2,410253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almHigh.AEBOOLS,410254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almHigh.INT1,410255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almHigh.INT2,410256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almHigh.AENotify,410257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almHigh.AESeverity,410258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almHigh.AEShelveDuration,410259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almLow.BOOLS1,410264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almLow.BOOLS2,410265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almLow.AEBOOLS,410266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almLow.INT1,410267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almLow.INT2,410268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almLow.AENotify,410269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almLow.AESeverity,410270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almLow.AEShelveDuration,410271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almLowLow.BOOLS1,410276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almLowLow.BOOLS2,410277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almLowLow.AEBOOLS,410278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almLowLow.INT1,410279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almLowLow.INT2,410280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almLowLow.AENotify,410281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almLowLow.AESeverity,410282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almLowLow.AEShelveDuration,410283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almBrokenLoop.BOOLS1,410288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almBrokenLoop.BOOLS2,410289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almBrokenLoop.AEBOOLS,410290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almBrokenLoop.INT1,410291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almBrokenLoop.INT2,410292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almBrokenLoop.AENotify,410293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almBrokenLoop.AESeverity,410294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almBrokenLoop.AEShelveDuration,410295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almOverRange.BOOLS1,410300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almOverRange.BOOLS2,410301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almOverRange.AEBOOLS,410302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almOverRange.INT1,410303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almOverRange.INT2,410304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almOverRange.AENotify,410305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almOverRange.AESeverity,410306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almOverRange.AEShelveDuration,410307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almUnderRange.BOOLS1,410312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almUnderRange.BOOLS2,410313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almUnderRange.AEBOOLS,410314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almUnderRange.INT1,410315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almUnderRange.INT2,410316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almUnderRange.AENotify,410317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almUnderRange.AESeverity,410318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almUnderRange.AEShelveDuration,410319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almRateOfChange.BOOLS1,410324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almRateOfChange.BOOLS2,410325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almRateOfChange.AEBOOLS,410326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almRateOfChange.INT1,410327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almRateOfChange.INT2,410328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almRateOfChange.AENotify,410329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almRateOfChange.AESeverity,410330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almRateOfChange.AEShelveDuration,410331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI1.almPLCFault.BOOLS1,410336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI1.almPLCFault.BOOLS2,410337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI1.almPLCFault.AEBOOLS,410338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI1.almPLCFault.INT1,410339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almPLCFault.INT2,410340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI1.almPLCFault.AENotify,410341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI1.almPLCFault.AESeverity,410342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI1.almPLCFault.AEShelveDuration,410343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almHighHigh.BOOLS1,410440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almHighHigh.BOOLS2,410441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almHighHigh.AEBOOLS,410442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almHighHigh.INT1,410443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almHighHigh.INT2,410444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almHighHigh.AENotify,410445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almHighHigh.AESeverity,410446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almHighHigh.AEShelveDuration,410447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almHigh.BOOLS1,410452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almHigh.BOOLS2,410453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almHigh.AEBOOLS,410454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almHigh.INT1,410455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almHigh.INT2,410456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almHigh.AENotify,410457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almHigh.AESeverity,410458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almHigh.AEShelveDuration,410459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almLow.BOOLS1,410464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almLow.BOOLS2,410465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almLow.AEBOOLS,410466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almLow.INT1,410467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almLow.INT2,410468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almLow.AENotify,410469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almLow.AESeverity,410470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almLow.AEShelveDuration,410471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almLowLow.BOOLS1,410476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almLowLow.BOOLS2,410477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almLowLow.AEBOOLS,410478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almLowLow.INT1,410479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almLowLow.INT2,410480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almLowLow.AENotify,410481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almLowLow.AESeverity,410482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almLowLow.AEShelveDuration,410483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almBrokenLoop.BOOLS1,410488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almBrokenLoop.BOOLS2,410489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almBrokenLoop.AEBOOLS,410490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almBrokenLoop.INT1,410491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almBrokenLoop.INT2,410492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almBrokenLoop.AENotify,410493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almBrokenLoop.AESeverity,410494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almBrokenLoop.AEShelveDuration,410495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almOverRange.BOOLS1,410500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almOverRange.BOOLS2,410501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almOverRange.AEBOOLS,410502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almOverRange.INT1,410503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almOverRange.INT2,410504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almOverRange.AENotify,410505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almOverRange.AESeverity,410506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almOverRange.AEShelveDuration,410507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almUnderRange.BOOLS1,410512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almUnderRange.BOOLS2,410513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almUnderRange.AEBOOLS,410514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almUnderRange.INT1,410515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almUnderRange.INT2,410516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almUnderRange.AENotify,410517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almUnderRange.AESeverity,410518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almUnderRange.AEShelveDuration,410519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almRateOfChange.BOOLS1,410524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almRateOfChange.BOOLS2,410525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almRateOfChange.AEBOOLS,410526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almRateOfChange.INT1,410527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almRateOfChange.INT2,410528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almRateOfChange.AENotify,410529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almRateOfChange.AESeverity,410530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almRateOfChange.AEShelveDuration,410531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI2.almPLCFault.BOOLS1,410536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI2.almPLCFault.BOOLS2,410537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI2.almPLCFault.AEBOOLS,410538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI2.almPLCFault.INT1,410539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almPLCFault.INT2,410540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI2.almPLCFault.AENotify,410541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI2.almPLCFault.AESeverity,410542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI2.almPLCFault.AEShelveDuration,410543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almHighHigh.BOOLS1,410640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almHighHigh.BOOLS2,410641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almHighHigh.AEBOOLS,410642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almHighHigh.INT1,410643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almHighHigh.INT2,410644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almHighHigh.AENotify,410645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almHighHigh.AESeverity,410646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almHighHigh.AEShelveDuration,410647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almHigh.BOOLS1,410652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almHigh.BOOLS2,410653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almHigh.AEBOOLS,410654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almHigh.INT1,410655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almHigh.INT2,410656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almHigh.AENotify,410657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almHigh.AESeverity,410658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almHigh.AEShelveDuration,410659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almLow.BOOLS1,410664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almLow.BOOLS2,410665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almLow.AEBOOLS,410666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almLow.INT1,410667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almLow.INT2,410668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almLow.AENotify,410669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almLow.AESeverity,410670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almLow.AEShelveDuration,410671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almLowLow.BOOLS1,410676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almLowLow.BOOLS2,410677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almLowLow.AEBOOLS,410678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almLowLow.INT1,410679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almLowLow.INT2,410680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almLowLow.AENotify,410681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almLowLow.AESeverity,410682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almLowLow.AEShelveDuration,410683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almBrokenLoop.BOOLS1,410688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almBrokenLoop.BOOLS2,410689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almBrokenLoop.AEBOOLS,410690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almBrokenLoop.INT1,410691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almBrokenLoop.INT2,410692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almBrokenLoop.AENotify,410693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almBrokenLoop.AESeverity,410694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almBrokenLoop.AEShelveDuration,410695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almOverRange.BOOLS1,410700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almOverRange.BOOLS2,410701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almOverRange.AEBOOLS,410702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almOverRange.INT1,410703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almOverRange.INT2,410704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almOverRange.AENotify,410705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almOverRange.AESeverity,410706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almOverRange.AEShelveDuration,410707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almUnderRange.BOOLS1,410712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almUnderRange.BOOLS2,410713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almUnderRange.AEBOOLS,410714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almUnderRange.INT1,410715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almUnderRange.INT2,410716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almUnderRange.AENotify,410717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almUnderRange.AESeverity,410718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almUnderRange.AEShelveDuration,410719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almRateOfChange.BOOLS1,410724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almRateOfChange.BOOLS2,410725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almRateOfChange.AEBOOLS,410726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almRateOfChange.INT1,410727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almRateOfChange.INT2,410728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almRateOfChange.AENotify,410729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almRateOfChange.AESeverity,410730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almRateOfChange.AEShelveDuration,410731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI3.almPLCFault.BOOLS1,410736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI3.almPLCFault.BOOLS2,410737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI3.almPLCFault.AEBOOLS,410738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI3.almPLCFault.INT1,410739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almPLCFault.INT2,410740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI3.almPLCFault.AENotify,410741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI3.almPLCFault.AESeverity,410742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI3.almPLCFault.AEShelveDuration,410743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almHighHigh.BOOLS1,410840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almHighHigh.BOOLS2,410841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almHighHigh.AEBOOLS,410842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almHighHigh.INT1,410843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almHighHigh.INT2,410844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almHighHigh.AENotify,410845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almHighHigh.AESeverity,410846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almHighHigh.AEShelveDuration,410847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almHigh.BOOLS1,410852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almHigh.BOOLS2,410853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almHigh.AEBOOLS,410854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almHigh.INT1,410855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almHigh.INT2,410856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almHigh.AENotify,410857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almHigh.AESeverity,410858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almHigh.AEShelveDuration,410859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almLow.BOOLS1,410864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almLow.BOOLS2,410865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almLow.AEBOOLS,410866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almLow.INT1,410867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almLow.INT2,410868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almLow.AENotify,410869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almLow.AESeverity,410870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almLow.AEShelveDuration,410871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almLowLow.BOOLS1,410876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almLowLow.BOOLS2,410877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almLowLow.AEBOOLS,410878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almLowLow.INT1,410879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almLowLow.INT2,410880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almLowLow.AENotify,410881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almLowLow.AESeverity,410882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almLowLow.AEShelveDuration,410883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almBrokenLoop.BOOLS1,410888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almBrokenLoop.BOOLS2,410889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almBrokenLoop.AEBOOLS,410890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almBrokenLoop.INT1,410891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almBrokenLoop.INT2,410892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almBrokenLoop.AENotify,410893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almBrokenLoop.AESeverity,410894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almBrokenLoop.AEShelveDuration,410895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almOverRange.BOOLS1,410900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almOverRange.BOOLS2,410901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almOverRange.AEBOOLS,410902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almOverRange.INT1,410903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almOverRange.INT2,410904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almOverRange.AENotify,410905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almOverRange.AESeverity,410906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almOverRange.AEShelveDuration,410907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almUnderRange.BOOLS1,410912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almUnderRange.BOOLS2,410913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almUnderRange.AEBOOLS,410914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almUnderRange.INT1,410915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almUnderRange.INT2,410916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almUnderRange.AENotify,410917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almUnderRange.AESeverity,410918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almUnderRange.AEShelveDuration,410919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almRateOfChange.BOOLS1,410924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almRateOfChange.BOOLS2,410925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almRateOfChange.AEBOOLS,410926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almRateOfChange.INT1,410927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almRateOfChange.INT2,410928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almRateOfChange.AENotify,410929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almRateOfChange.AESeverity,410930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almRateOfChange.AEShelveDuration,410931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_5_VI4.almPLCFault.BOOLS1,410936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_5_VI4.almPLCFault.BOOLS2,410937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_5_VI4.almPLCFault.AEBOOLS,410938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_5_VI4.almPLCFault.INT1,410939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almPLCFault.INT2,410940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_5_VI4.almPLCFault.AENotify,410941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_5_VI4.almPLCFault.AESeverity,410942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_5_VI4.almPLCFault.AEShelveDuration,410943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almHighHigh.BOOLS1,411040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almHighHigh.BOOLS2,411041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almHighHigh.AEBOOLS,411042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almHighHigh.INT1,411043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almHighHigh.INT2,411044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almHighHigh.AENotify,411045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almHighHigh.AESeverity,411046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almHighHigh.AEShelveDuration,411047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almHigh.BOOLS1,411052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almHigh.BOOLS2,411053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almHigh.AEBOOLS,411054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almHigh.INT1,411055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almHigh.INT2,411056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almHigh.AENotify,411057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almHigh.AESeverity,411058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almHigh.AEShelveDuration,411059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almLow.BOOLS1,411064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almLow.BOOLS2,411065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almLow.AEBOOLS,411066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almLow.INT1,411067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almLow.INT2,411068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almLow.AENotify,411069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almLow.AESeverity,411070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almLow.AEShelveDuration,411071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almLowLow.BOOLS1,411076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almLowLow.BOOLS2,411077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almLowLow.AEBOOLS,411078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almLowLow.INT1,411079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almLowLow.INT2,411080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almLowLow.AENotify,411081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almLowLow.AESeverity,411082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almLowLow.AEShelveDuration,411083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almBrokenLoop.BOOLS1,411088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almBrokenLoop.BOOLS2,411089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almBrokenLoop.AEBOOLS,411090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almBrokenLoop.INT1,411091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almBrokenLoop.INT2,411092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almBrokenLoop.AENotify,411093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almBrokenLoop.AESeverity,411094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almBrokenLoop.AEShelveDuration,411095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almOverRange.BOOLS1,411100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almOverRange.BOOLS2,411101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almOverRange.AEBOOLS,411102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almOverRange.INT1,411103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almOverRange.INT2,411104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almOverRange.AENotify,411105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almOverRange.AESeverity,411106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almOverRange.AEShelveDuration,411107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almUnderRange.BOOLS1,411112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almUnderRange.BOOLS2,411113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almUnderRange.AEBOOLS,411114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almUnderRange.INT1,411115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almUnderRange.INT2,411116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almUnderRange.AENotify,411117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almUnderRange.AESeverity,411118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almUnderRange.AEShelveDuration,411119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almRateOfChange.BOOLS1,411124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almRateOfChange.BOOLS2,411125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almRateOfChange.AEBOOLS,411126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almRateOfChange.INT1,411127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almRateOfChange.INT2,411128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almRateOfChange.AENotify,411129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almRateOfChange.AESeverity,411130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almRateOfChange.AEShelveDuration,411131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI1.almPLCFault.BOOLS1,411136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI1.almPLCFault.BOOLS2,411137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI1.almPLCFault.AEBOOLS,411138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI1.almPLCFault.INT1,411139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almPLCFault.INT2,411140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI1.almPLCFault.AENotify,411141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI1.almPLCFault.AESeverity,411142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI1.almPLCFault.AEShelveDuration,411143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almHighHigh.BOOLS1,411240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almHighHigh.BOOLS2,411241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almHighHigh.AEBOOLS,411242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almHighHigh.INT1,411243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almHighHigh.INT2,411244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almHighHigh.AENotify,411245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almHighHigh.AESeverity,411246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almHighHigh.AEShelveDuration,411247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almHigh.BOOLS1,411252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almHigh.BOOLS2,411253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almHigh.AEBOOLS,411254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almHigh.INT1,411255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almHigh.INT2,411256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almHigh.AENotify,411257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almHigh.AESeverity,411258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almHigh.AEShelveDuration,411259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almLow.BOOLS1,411264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almLow.BOOLS2,411265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almLow.AEBOOLS,411266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almLow.INT1,411267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almLow.INT2,411268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almLow.AENotify,411269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almLow.AESeverity,411270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almLow.AEShelveDuration,411271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almLowLow.BOOLS1,411276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almLowLow.BOOLS2,411277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almLowLow.AEBOOLS,411278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almLowLow.INT1,411279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almLowLow.INT2,411280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almLowLow.AENotify,411281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almLowLow.AESeverity,411282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almLowLow.AEShelveDuration,411283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almBrokenLoop.BOOLS1,411288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almBrokenLoop.BOOLS2,411289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almBrokenLoop.AEBOOLS,411290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almBrokenLoop.INT1,411291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almBrokenLoop.INT2,411292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almBrokenLoop.AENotify,411293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almBrokenLoop.AESeverity,411294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almBrokenLoop.AEShelveDuration,411295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almOverRange.BOOLS1,411300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almOverRange.BOOLS2,411301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almOverRange.AEBOOLS,411302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almOverRange.INT1,411303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almOverRange.INT2,411304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almOverRange.AENotify,411305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almOverRange.AESeverity,411306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almOverRange.AEShelveDuration,411307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almUnderRange.BOOLS1,411312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almUnderRange.BOOLS2,411313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almUnderRange.AEBOOLS,411314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almUnderRange.INT1,411315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almUnderRange.INT2,411316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almUnderRange.AENotify,411317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almUnderRange.AESeverity,411318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almUnderRange.AEShelveDuration,411319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almRateOfChange.BOOLS1,411324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almRateOfChange.BOOLS2,411325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almRateOfChange.AEBOOLS,411326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almRateOfChange.INT1,411327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almRateOfChange.INT2,411328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almRateOfChange.AENotify,411329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almRateOfChange.AESeverity,411330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almRateOfChange.AEShelveDuration,411331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI2.almPLCFault.BOOLS1,411336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI2.almPLCFault.BOOLS2,411337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI2.almPLCFault.AEBOOLS,411338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI2.almPLCFault.INT1,411339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almPLCFault.INT2,411340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI2.almPLCFault.AENotify,411341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI2.almPLCFault.AESeverity,411342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI2.almPLCFault.AEShelveDuration,411343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almHighHigh.BOOLS1,411440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almHighHigh.BOOLS2,411441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almHighHigh.AEBOOLS,411442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almHighHigh.INT1,411443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almHighHigh.INT2,411444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almHighHigh.AENotify,411445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almHighHigh.AESeverity,411446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almHighHigh.AEShelveDuration,411447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almHigh.BOOLS1,411452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almHigh.BOOLS2,411453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almHigh.AEBOOLS,411454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almHigh.INT1,411455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almHigh.INT2,411456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almHigh.AENotify,411457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almHigh.AESeverity,411458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almHigh.AEShelveDuration,411459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almLow.BOOLS1,411464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almLow.BOOLS2,411465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almLow.AEBOOLS,411466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almLow.INT1,411467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almLow.INT2,411468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almLow.AENotify,411469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almLow.AESeverity,411470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almLow.AEShelveDuration,411471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almLowLow.BOOLS1,411476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almLowLow.BOOLS2,411477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almLowLow.AEBOOLS,411478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almLowLow.INT1,411479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almLowLow.INT2,411480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almLowLow.AENotify,411481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almLowLow.AESeverity,411482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almLowLow.AEShelveDuration,411483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almBrokenLoop.BOOLS1,411488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almBrokenLoop.BOOLS2,411489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almBrokenLoop.AEBOOLS,411490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almBrokenLoop.INT1,411491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almBrokenLoop.INT2,411492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almBrokenLoop.AENotify,411493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almBrokenLoop.AESeverity,411494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almBrokenLoop.AEShelveDuration,411495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almOverRange.BOOLS1,411500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almOverRange.BOOLS2,411501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almOverRange.AEBOOLS,411502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almOverRange.INT1,411503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almOverRange.INT2,411504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almOverRange.AENotify,411505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almOverRange.AESeverity,411506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almOverRange.AEShelveDuration,411507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almUnderRange.BOOLS1,411512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almUnderRange.BOOLS2,411513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almUnderRange.AEBOOLS,411514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almUnderRange.INT1,411515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almUnderRange.INT2,411516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almUnderRange.AENotify,411517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almUnderRange.AESeverity,411518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almUnderRange.AEShelveDuration,411519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almRateOfChange.BOOLS1,411524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almRateOfChange.BOOLS2,411525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almRateOfChange.AEBOOLS,411526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almRateOfChange.INT1,411527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almRateOfChange.INT2,411528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almRateOfChange.AENotify,411529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almRateOfChange.AESeverity,411530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almRateOfChange.AEShelveDuration,411531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI3.almPLCFault.BOOLS1,411536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI3.almPLCFault.BOOLS2,411537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI3.almPLCFault.AEBOOLS,411538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI3.almPLCFault.INT1,411539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almPLCFault.INT2,411540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI3.almPLCFault.AENotify,411541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI3.almPLCFault.AESeverity,411542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI3.almPLCFault.AEShelveDuration,411543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almHighHigh.BOOLS1,411640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almHighHigh.BOOLS2,411641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almHighHigh.AEBOOLS,411642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almHighHigh.INT1,411643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almHighHigh.INT2,411644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almHighHigh.AENotify,411645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almHighHigh.AESeverity,411646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almHighHigh.AEShelveDuration,411647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almHigh.BOOLS1,411652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almHigh.BOOLS2,411653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almHigh.AEBOOLS,411654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almHigh.INT1,411655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almHigh.INT2,411656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almHigh.AENotify,411657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almHigh.AESeverity,411658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almHigh.AEShelveDuration,411659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almLow.BOOLS1,411664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almLow.BOOLS2,411665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almLow.AEBOOLS,411666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almLow.INT1,411667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almLow.INT2,411668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almLow.AENotify,411669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almLow.AESeverity,411670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almLow.AEShelveDuration,411671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almLowLow.BOOLS1,411676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almLowLow.BOOLS2,411677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almLowLow.AEBOOLS,411678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almLowLow.INT1,411679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almLowLow.INT2,411680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almLowLow.AENotify,411681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almLowLow.AESeverity,411682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almLowLow.AEShelveDuration,411683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almBrokenLoop.BOOLS1,411688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almBrokenLoop.BOOLS2,411689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almBrokenLoop.AEBOOLS,411690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almBrokenLoop.INT1,411691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almBrokenLoop.INT2,411692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almBrokenLoop.AENotify,411693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almBrokenLoop.AESeverity,411694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almBrokenLoop.AEShelveDuration,411695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almOverRange.BOOLS1,411700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almOverRange.BOOLS2,411701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almOverRange.AEBOOLS,411702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almOverRange.INT1,411703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almOverRange.INT2,411704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almOverRange.AENotify,411705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almOverRange.AESeverity,411706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almOverRange.AEShelveDuration,411707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almUnderRange.BOOLS1,411712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almUnderRange.BOOLS2,411713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almUnderRange.AEBOOLS,411714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almUnderRange.INT1,411715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almUnderRange.INT2,411716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almUnderRange.AENotify,411717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almUnderRange.AESeverity,411718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almUnderRange.AEShelveDuration,411719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almRateOfChange.BOOLS1,411724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almRateOfChange.BOOLS2,411725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almRateOfChange.AEBOOLS,411726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almRateOfChange.INT1,411727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almRateOfChange.INT2,411728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almRateOfChange.AENotify,411729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almRateOfChange.AESeverity,411730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almRateOfChange.AEShelveDuration,411731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_6_VI4.almPLCFault.BOOLS1,411736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_6_VI4.almPLCFault.BOOLS2,411737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_6_VI4.almPLCFault.AEBOOLS,411738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_6_VI4.almPLCFault.INT1,411739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almPLCFault.INT2,411740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_6_VI4.almPLCFault.AENotify,411741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_6_VI4.almPLCFault.AESeverity,411742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_6_VI4.almPLCFault.AEShelveDuration,411743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almHighHigh.BOOLS1,411840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almHighHigh.BOOLS2,411841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almHighHigh.AEBOOLS,411842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almHighHigh.INT1,411843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almHighHigh.INT2,411844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almHighHigh.AENotify,411845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almHighHigh.AESeverity,411846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almHighHigh.AEShelveDuration,411847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almHigh.BOOLS1,411852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almHigh.BOOLS2,411853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almHigh.AEBOOLS,411854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almHigh.INT1,411855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almHigh.INT2,411856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almHigh.AENotify,411857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almHigh.AESeverity,411858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almHigh.AEShelveDuration,411859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almLow.BOOLS1,411864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almLow.BOOLS2,411865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almLow.AEBOOLS,411866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almLow.INT1,411867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almLow.INT2,411868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almLow.AENotify,411869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almLow.AESeverity,411870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almLow.AEShelveDuration,411871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almLowLow.BOOLS1,411876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almLowLow.BOOLS2,411877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almLowLow.AEBOOLS,411878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almLowLow.INT1,411879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almLowLow.INT2,411880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almLowLow.AENotify,411881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almLowLow.AESeverity,411882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almLowLow.AEShelveDuration,411883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almBrokenLoop.BOOLS1,411888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almBrokenLoop.BOOLS2,411889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almBrokenLoop.AEBOOLS,411890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almBrokenLoop.INT1,411891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almBrokenLoop.INT2,411892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almBrokenLoop.AENotify,411893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almBrokenLoop.AESeverity,411894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almBrokenLoop.AEShelveDuration,411895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almOverRange.BOOLS1,411900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almOverRange.BOOLS2,411901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almOverRange.AEBOOLS,411902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almOverRange.INT1,411903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almOverRange.INT2,411904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almOverRange.AENotify,411905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almOverRange.AESeverity,411906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almOverRange.AEShelveDuration,411907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almUnderRange.BOOLS1,411912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almUnderRange.BOOLS2,411913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almUnderRange.AEBOOLS,411914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almUnderRange.INT1,411915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almUnderRange.INT2,411916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almUnderRange.AENotify,411917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almUnderRange.AESeverity,411918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almUnderRange.AEShelveDuration,411919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almRateOfChange.BOOLS1,411924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almRateOfChange.BOOLS2,411925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almRateOfChange.AEBOOLS,411926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almRateOfChange.INT1,411927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almRateOfChange.INT2,411928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almRateOfChange.AENotify,411929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almRateOfChange.AESeverity,411930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almRateOfChange.AEShelveDuration,411931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI1.almPLCFault.BOOLS1,411936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI1.almPLCFault.BOOLS2,411937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI1.almPLCFault.AEBOOLS,411938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI1.almPLCFault.INT1,411939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almPLCFault.INT2,411940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI1.almPLCFault.AENotify,411941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI1.almPLCFault.AESeverity,411942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI1.almPLCFault.AEShelveDuration,411943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almHighHigh.BOOLS1,412040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almHighHigh.BOOLS2,412041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almHighHigh.AEBOOLS,412042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almHighHigh.INT1,412043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almHighHigh.INT2,412044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almHighHigh.AENotify,412045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almHighHigh.AESeverity,412046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almHighHigh.AEShelveDuration,412047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almHigh.BOOLS1,412052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almHigh.BOOLS2,412053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almHigh.AEBOOLS,412054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almHigh.INT1,412055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almHigh.INT2,412056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almHigh.AENotify,412057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almHigh.AESeverity,412058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almHigh.AEShelveDuration,412059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almLow.BOOLS1,412064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almLow.BOOLS2,412065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almLow.AEBOOLS,412066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almLow.INT1,412067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almLow.INT2,412068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almLow.AENotify,412069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almLow.AESeverity,412070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almLow.AEShelveDuration,412071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almLowLow.BOOLS1,412076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almLowLow.BOOLS2,412077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almLowLow.AEBOOLS,412078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almLowLow.INT1,412079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almLowLow.INT2,412080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almLowLow.AENotify,412081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almLowLow.AESeverity,412082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almLowLow.AEShelveDuration,412083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almBrokenLoop.BOOLS1,412088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almBrokenLoop.BOOLS2,412089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almBrokenLoop.AEBOOLS,412090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almBrokenLoop.INT1,412091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almBrokenLoop.INT2,412092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almBrokenLoop.AENotify,412093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almBrokenLoop.AESeverity,412094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almBrokenLoop.AEShelveDuration,412095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almOverRange.BOOLS1,412100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almOverRange.BOOLS2,412101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almOverRange.AEBOOLS,412102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almOverRange.INT1,412103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almOverRange.INT2,412104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almOverRange.AENotify,412105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almOverRange.AESeverity,412106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almOverRange.AEShelveDuration,412107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almUnderRange.BOOLS1,412112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almUnderRange.BOOLS2,412113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almUnderRange.AEBOOLS,412114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almUnderRange.INT1,412115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almUnderRange.INT2,412116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almUnderRange.AENotify,412117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almUnderRange.AESeverity,412118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almUnderRange.AEShelveDuration,412119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almRateOfChange.BOOLS1,412124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almRateOfChange.BOOLS2,412125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almRateOfChange.AEBOOLS,412126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almRateOfChange.INT1,412127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almRateOfChange.INT2,412128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almRateOfChange.AENotify,412129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almRateOfChange.AESeverity,412130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almRateOfChange.AEShelveDuration,412131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI2.almPLCFault.BOOLS1,412136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI2.almPLCFault.BOOLS2,412137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI2.almPLCFault.AEBOOLS,412138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI2.almPLCFault.INT1,412139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almPLCFault.INT2,412140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI2.almPLCFault.AENotify,412141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI2.almPLCFault.AESeverity,412142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI2.almPLCFault.AEShelveDuration,412143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almHighHigh.BOOLS1,412240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almHighHigh.BOOLS2,412241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almHighHigh.AEBOOLS,412242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almHighHigh.INT1,412243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almHighHigh.INT2,412244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almHighHigh.AENotify,412245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almHighHigh.AESeverity,412246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almHighHigh.AEShelveDuration,412247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almHigh.BOOLS1,412252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almHigh.BOOLS2,412253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almHigh.AEBOOLS,412254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almHigh.INT1,412255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almHigh.INT2,412256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almHigh.AENotify,412257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almHigh.AESeverity,412258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almHigh.AEShelveDuration,412259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almLow.BOOLS1,412264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almLow.BOOLS2,412265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almLow.AEBOOLS,412266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almLow.INT1,412267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almLow.INT2,412268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almLow.AENotify,412269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almLow.AESeverity,412270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almLow.AEShelveDuration,412271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almLowLow.BOOLS1,412276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almLowLow.BOOLS2,412277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almLowLow.AEBOOLS,412278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almLowLow.INT1,412279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almLowLow.INT2,412280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almLowLow.AENotify,412281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almLowLow.AESeverity,412282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almLowLow.AEShelveDuration,412283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almBrokenLoop.BOOLS1,412288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almBrokenLoop.BOOLS2,412289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almBrokenLoop.AEBOOLS,412290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almBrokenLoop.INT1,412291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almBrokenLoop.INT2,412292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almBrokenLoop.AENotify,412293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almBrokenLoop.AESeverity,412294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almBrokenLoop.AEShelveDuration,412295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almOverRange.BOOLS1,412300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almOverRange.BOOLS2,412301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almOverRange.AEBOOLS,412302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almOverRange.INT1,412303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almOverRange.INT2,412304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almOverRange.AENotify,412305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almOverRange.AESeverity,412306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almOverRange.AEShelveDuration,412307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almUnderRange.BOOLS1,412312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almUnderRange.BOOLS2,412313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almUnderRange.AEBOOLS,412314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almUnderRange.INT1,412315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almUnderRange.INT2,412316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almUnderRange.AENotify,412317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almUnderRange.AESeverity,412318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almUnderRange.AEShelveDuration,412319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almRateOfChange.BOOLS1,412324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almRateOfChange.BOOLS2,412325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almRateOfChange.AEBOOLS,412326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almRateOfChange.INT1,412327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almRateOfChange.INT2,412328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almRateOfChange.AENotify,412329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almRateOfChange.AESeverity,412330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almRateOfChange.AEShelveDuration,412331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI3.almPLCFault.BOOLS1,412336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI3.almPLCFault.BOOLS2,412337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI3.almPLCFault.AEBOOLS,412338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI3.almPLCFault.INT1,412339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almPLCFault.INT2,412340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI3.almPLCFault.AENotify,412341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI3.almPLCFault.AESeverity,412342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI3.almPLCFault.AEShelveDuration,412343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almHighHigh.BOOLS1,412440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almHighHigh.BOOLS2,412441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almHighHigh.AEBOOLS,412442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almHighHigh.INT1,412443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almHighHigh.INT2,412444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almHighHigh.AENotify,412445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almHighHigh.AESeverity,412446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almHighHigh.AEShelveDuration,412447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almHigh.BOOLS1,412452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almHigh.BOOLS2,412453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almHigh.AEBOOLS,412454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almHigh.INT1,412455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almHigh.INT2,412456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almHigh.AENotify,412457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almHigh.AESeverity,412458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almHigh.AEShelveDuration,412459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almLow.BOOLS1,412464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almLow.BOOLS2,412465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almLow.AEBOOLS,412466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almLow.INT1,412467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almLow.INT2,412468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almLow.AENotify,412469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almLow.AESeverity,412470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almLow.AEShelveDuration,412471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almLowLow.BOOLS1,412476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almLowLow.BOOLS2,412477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almLowLow.AEBOOLS,412478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almLowLow.INT1,412479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almLowLow.INT2,412480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almLowLow.AENotify,412481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almLowLow.AESeverity,412482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almLowLow.AEShelveDuration,412483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almBrokenLoop.BOOLS1,412488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almBrokenLoop.BOOLS2,412489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almBrokenLoop.AEBOOLS,412490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almBrokenLoop.INT1,412491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almBrokenLoop.INT2,412492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almBrokenLoop.AENotify,412493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almBrokenLoop.AESeverity,412494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almBrokenLoop.AEShelveDuration,412495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almOverRange.BOOLS1,412500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almOverRange.BOOLS2,412501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almOverRange.AEBOOLS,412502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almOverRange.INT1,412503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almOverRange.INT2,412504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almOverRange.AENotify,412505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almOverRange.AESeverity,412506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almOverRange.AEShelveDuration,412507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almUnderRange.BOOLS1,412512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almUnderRange.BOOLS2,412513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almUnderRange.AEBOOLS,412514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almUnderRange.INT1,412515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almUnderRange.INT2,412516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almUnderRange.AENotify,412517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almUnderRange.AESeverity,412518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almUnderRange.AEShelveDuration,412519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almRateOfChange.BOOLS1,412524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almRateOfChange.BOOLS2,412525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almRateOfChange.AEBOOLS,412526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almRateOfChange.INT1,412527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almRateOfChange.INT2,412528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almRateOfChange.AENotify,412529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almRateOfChange.AESeverity,412530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almRateOfChange.AEShelveDuration,412531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_7_VI4.almPLCFault.BOOLS1,412536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_7_VI4.almPLCFault.BOOLS2,412537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_7_VI4.almPLCFault.AEBOOLS,412538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_7_VI4.almPLCFault.INT1,412539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almPLCFault.INT2,412540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_7_VI4.almPLCFault.AENotify,412541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_7_VI4.almPLCFault.AESeverity,412542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_7_VI4.almPLCFault.AEShelveDuration,412543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almHighHigh.BOOLS1,412640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almHighHigh.BOOLS2,412641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almHighHigh.AEBOOLS,412642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almHighHigh.INT1,412643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almHighHigh.INT2,412644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almHighHigh.AENotify,412645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almHighHigh.AESeverity,412646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almHighHigh.AEShelveDuration,412647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almHigh.BOOLS1,412652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almHigh.BOOLS2,412653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almHigh.AEBOOLS,412654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almHigh.INT1,412655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almHigh.INT2,412656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almHigh.AENotify,412657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almHigh.AESeverity,412658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almHigh.AEShelveDuration,412659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almLow.BOOLS1,412664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almLow.BOOLS2,412665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almLow.AEBOOLS,412666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almLow.INT1,412667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almLow.INT2,412668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almLow.AENotify,412669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almLow.AESeverity,412670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almLow.AEShelveDuration,412671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almLowLow.BOOLS1,412676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almLowLow.BOOLS2,412677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almLowLow.AEBOOLS,412678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almLowLow.INT1,412679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almLowLow.INT2,412680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almLowLow.AENotify,412681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almLowLow.AESeverity,412682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almLowLow.AEShelveDuration,412683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almBrokenLoop.BOOLS1,412688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almBrokenLoop.BOOLS2,412689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almBrokenLoop.AEBOOLS,412690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almBrokenLoop.INT1,412691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almBrokenLoop.INT2,412692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almBrokenLoop.AENotify,412693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almBrokenLoop.AESeverity,412694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almBrokenLoop.AEShelveDuration,412695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almOverRange.BOOLS1,412700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almOverRange.BOOLS2,412701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almOverRange.AEBOOLS,412702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almOverRange.INT1,412703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almOverRange.INT2,412704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almOverRange.AENotify,412705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almOverRange.AESeverity,412706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almOverRange.AEShelveDuration,412707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almUnderRange.BOOLS1,412712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almUnderRange.BOOLS2,412713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almUnderRange.AEBOOLS,412714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almUnderRange.INT1,412715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almUnderRange.INT2,412716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almUnderRange.AENotify,412717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almUnderRange.AESeverity,412718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almUnderRange.AEShelveDuration,412719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almRateOfChange.BOOLS1,412724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almRateOfChange.BOOLS2,412725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almRateOfChange.AEBOOLS,412726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almRateOfChange.INT1,412727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almRateOfChange.INT2,412728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almRateOfChange.AENotify,412729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almRateOfChange.AESeverity,412730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almRateOfChange.AEShelveDuration,412731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI1.almPLCFault.BOOLS1,412736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI1.almPLCFault.BOOLS2,412737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI1.almPLCFault.AEBOOLS,412738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI1.almPLCFault.INT1,412739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almPLCFault.INT2,412740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI1.almPLCFault.AENotify,412741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI1.almPLCFault.AESeverity,412742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI1.almPLCFault.AEShelveDuration,412743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almHighHigh.BOOLS1,412840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almHighHigh.BOOLS2,412841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almHighHigh.AEBOOLS,412842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almHighHigh.INT1,412843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almHighHigh.INT2,412844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almHighHigh.AENotify,412845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almHighHigh.AESeverity,412846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almHighHigh.AEShelveDuration,412847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almHigh.BOOLS1,412852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almHigh.BOOLS2,412853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almHigh.AEBOOLS,412854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almHigh.INT1,412855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almHigh.INT2,412856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almHigh.AENotify,412857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almHigh.AESeverity,412858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almHigh.AEShelveDuration,412859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almLow.BOOLS1,412864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almLow.BOOLS2,412865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almLow.AEBOOLS,412866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almLow.INT1,412867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almLow.INT2,412868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almLow.AENotify,412869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almLow.AESeverity,412870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almLow.AEShelveDuration,412871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almLowLow.BOOLS1,412876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almLowLow.BOOLS2,412877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almLowLow.AEBOOLS,412878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almLowLow.INT1,412879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almLowLow.INT2,412880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almLowLow.AENotify,412881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almLowLow.AESeverity,412882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almLowLow.AEShelveDuration,412883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almBrokenLoop.BOOLS1,412888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almBrokenLoop.BOOLS2,412889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almBrokenLoop.AEBOOLS,412890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almBrokenLoop.INT1,412891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almBrokenLoop.INT2,412892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almBrokenLoop.AENotify,412893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almBrokenLoop.AESeverity,412894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almBrokenLoop.AEShelveDuration,412895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almOverRange.BOOLS1,412900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almOverRange.BOOLS2,412901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almOverRange.AEBOOLS,412902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almOverRange.INT1,412903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almOverRange.INT2,412904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almOverRange.AENotify,412905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almOverRange.AESeverity,412906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almOverRange.AEShelveDuration,412907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almUnderRange.BOOLS1,412912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almUnderRange.BOOLS2,412913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almUnderRange.AEBOOLS,412914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almUnderRange.INT1,412915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almUnderRange.INT2,412916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almUnderRange.AENotify,412917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almUnderRange.AESeverity,412918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almUnderRange.AEShelveDuration,412919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almRateOfChange.BOOLS1,412924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almRateOfChange.BOOLS2,412925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almRateOfChange.AEBOOLS,412926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almRateOfChange.INT1,412927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almRateOfChange.INT2,412928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almRateOfChange.AENotify,412929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almRateOfChange.AESeverity,412930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almRateOfChange.AEShelveDuration,412931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI2.almPLCFault.BOOLS1,412936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI2.almPLCFault.BOOLS2,412937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI2.almPLCFault.AEBOOLS,412938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI2.almPLCFault.INT1,412939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almPLCFault.INT2,412940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI2.almPLCFault.AENotify,412941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI2.almPLCFault.AESeverity,412942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI2.almPLCFault.AEShelveDuration,412943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almHighHigh.BOOLS1,413040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almHighHigh.BOOLS2,413041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almHighHigh.AEBOOLS,413042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almHighHigh.INT1,413043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almHighHigh.INT2,413044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almHighHigh.AENotify,413045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almHighHigh.AESeverity,413046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almHighHigh.AEShelveDuration,413047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almHigh.BOOLS1,413052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almHigh.BOOLS2,413053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almHigh.AEBOOLS,413054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almHigh.INT1,413055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almHigh.INT2,413056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almHigh.AENotify,413057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almHigh.AESeverity,413058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almHigh.AEShelveDuration,413059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almLow.BOOLS1,413064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almLow.BOOLS2,413065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almLow.AEBOOLS,413066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almLow.INT1,413067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almLow.INT2,413068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almLow.AENotify,413069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almLow.AESeverity,413070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almLow.AEShelveDuration,413071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almLowLow.BOOLS1,413076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almLowLow.BOOLS2,413077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almLowLow.AEBOOLS,413078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almLowLow.INT1,413079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almLowLow.INT2,413080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almLowLow.AENotify,413081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almLowLow.AESeverity,413082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almLowLow.AEShelveDuration,413083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almBrokenLoop.BOOLS1,413088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almBrokenLoop.BOOLS2,413089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almBrokenLoop.AEBOOLS,413090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almBrokenLoop.INT1,413091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almBrokenLoop.INT2,413092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almBrokenLoop.AENotify,413093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almBrokenLoop.AESeverity,413094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almBrokenLoop.AEShelveDuration,413095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almOverRange.BOOLS1,413100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almOverRange.BOOLS2,413101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almOverRange.AEBOOLS,413102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almOverRange.INT1,413103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almOverRange.INT2,413104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almOverRange.AENotify,413105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almOverRange.AESeverity,413106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almOverRange.AEShelveDuration,413107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almUnderRange.BOOLS1,413112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almUnderRange.BOOLS2,413113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almUnderRange.AEBOOLS,413114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almUnderRange.INT1,413115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almUnderRange.INT2,413116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almUnderRange.AENotify,413117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almUnderRange.AESeverity,413118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almUnderRange.AEShelveDuration,413119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almRateOfChange.BOOLS1,413124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almRateOfChange.BOOLS2,413125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almRateOfChange.AEBOOLS,413126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almRateOfChange.INT1,413127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almRateOfChange.INT2,413128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almRateOfChange.AENotify,413129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almRateOfChange.AESeverity,413130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almRateOfChange.AEShelveDuration,413131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI3.almPLCFault.BOOLS1,413136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI3.almPLCFault.BOOLS2,413137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI3.almPLCFault.AEBOOLS,413138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI3.almPLCFault.INT1,413139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almPLCFault.INT2,413140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI3.almPLCFault.AENotify,413141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI3.almPLCFault.AESeverity,413142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI3.almPLCFault.AEShelveDuration,413143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almHighHigh.BOOLS1,413240,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almHighHigh.BOOLS2,413241,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almHighHigh.AEBOOLS,413242,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almHighHigh.INT1,413243,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almHighHigh.INT2,413244,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almHighHigh.AENotify,413245,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almHighHigh.AESeverity,413246,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almHighHigh.AEShelveDuration,413247,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almHigh.BOOLS1,413252,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almHigh.BOOLS2,413253,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almHigh.AEBOOLS,413254,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almHigh.INT1,413255,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almHigh.INT2,413256,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almHigh.AENotify,413257,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almHigh.AESeverity,413258,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almHigh.AEShelveDuration,413259,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almLow.BOOLS1,413264,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almLow.BOOLS2,413265,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almLow.AEBOOLS,413266,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almLow.INT1,413267,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almLow.INT2,413268,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almLow.AENotify,413269,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almLow.AESeverity,413270,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almLow.AEShelveDuration,413271,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almLowLow.BOOLS1,413276,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almLowLow.BOOLS2,413277,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almLowLow.AEBOOLS,413278,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almLowLow.INT1,413279,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almLowLow.INT2,413280,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almLowLow.AENotify,413281,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almLowLow.AESeverity,413282,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almLowLow.AEShelveDuration,413283,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almBrokenLoop.BOOLS1,413288,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almBrokenLoop.BOOLS2,413289,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almBrokenLoop.AEBOOLS,413290,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almBrokenLoop.INT1,413291,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almBrokenLoop.INT2,413292,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almBrokenLoop.AENotify,413293,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almBrokenLoop.AESeverity,413294,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almBrokenLoop.AEShelveDuration,413295,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almOverRange.BOOLS1,413300,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almOverRange.BOOLS2,413301,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almOverRange.AEBOOLS,413302,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almOverRange.INT1,413303,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almOverRange.INT2,413304,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almOverRange.AENotify,413305,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almOverRange.AESeverity,413306,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almOverRange.AEShelveDuration,413307,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almUnderRange.BOOLS1,413312,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almUnderRange.BOOLS2,413313,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almUnderRange.AEBOOLS,413314,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almUnderRange.INT1,413315,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almUnderRange.INT2,413316,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almUnderRange.AENotify,413317,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almUnderRange.AESeverity,413318,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almUnderRange.AEShelveDuration,413319,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almRateOfChange.BOOLS1,413324,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almRateOfChange.BOOLS2,413325,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almRateOfChange.AEBOOLS,413326,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almRateOfChange.INT1,413327,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almRateOfChange.INT2,413328,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almRateOfChange.AENotify,413329,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almRateOfChange.AESeverity,413330,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almRateOfChange.AEShelveDuration,413331,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_8_VI4.almPLCFault.BOOLS1,413336,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_8_VI4.almPLCFault.BOOLS2,413337,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_8_VI4.almPLCFault.AEBOOLS,413338,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_8_VI4.almPLCFault.INT1,413339,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almPLCFault.INT2,413340,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_8_VI4.almPLCFault.AENotify,413341,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_8_VI4.almPLCFault.AESeverity,413342,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_8_VI4.almPLCFault.AEShelveDuration,413343,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almHighHigh.BOOLS1,413440,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almHighHigh.BOOLS2,413441,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almHighHigh.AEBOOLS,413442,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almHighHigh.INT1,413443,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almHighHigh.INT2,413444,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almHighHigh.AENotify,413445,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almHighHigh.AESeverity,413446,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almHighHigh.AEShelveDuration,413447,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almHigh.BOOLS1,413452,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almHigh.BOOLS2,413453,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almHigh.AEBOOLS,413454,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almHigh.INT1,413455,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almHigh.INT2,413456,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almHigh.AENotify,413457,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almHigh.AESeverity,413458,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almHigh.AEShelveDuration,413459,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almLow.BOOLS1,413464,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almLow.BOOLS2,413465,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almLow.AEBOOLS,413466,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almLow.INT1,413467,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almLow.INT2,413468,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almLow.AENotify,413469,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almLow.AESeverity,413470,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almLow.AEShelveDuration,413471,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almLowLow.BOOLS1,413476,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almLowLow.BOOLS2,413477,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almLowLow.AEBOOLS,413478,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almLowLow.INT1,413479,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almLowLow.INT2,413480,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almLowLow.AENotify,413481,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almLowLow.AESeverity,413482,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almLowLow.AEShelveDuration,413483,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almBrokenLoop.BOOLS1,413488,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almBrokenLoop.BOOLS2,413489,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almBrokenLoop.AEBOOLS,413490,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almBrokenLoop.INT1,413491,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almBrokenLoop.INT2,413492,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almBrokenLoop.AENotify,413493,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almBrokenLoop.AESeverity,413494,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almBrokenLoop.AEShelveDuration,413495,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almOverRange.BOOLS1,413500,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almOverRange.BOOLS2,413501,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almOverRange.AEBOOLS,413502,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almOverRange.INT1,413503,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almOverRange.INT2,413504,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almOverRange.AENotify,413505,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almOverRange.AESeverity,413506,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almOverRange.AEShelveDuration,413507,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almUnderRange.BOOLS1,413512,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almUnderRange.BOOLS2,413513,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almUnderRange.AEBOOLS,413514,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almUnderRange.INT1,413515,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almUnderRange.INT2,413516,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almUnderRange.AENotify,413517,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almUnderRange.AESeverity,413518,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almUnderRange.AEShelveDuration,413519,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almRateOfChange.BOOLS1,413524,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almRateOfChange.BOOLS2,413525,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almRateOfChange.AEBOOLS,413526,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almRateOfChange.INT1,413527,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almRateOfChange.INT2,413528,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almRateOfChange.AENotify,413529,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almRateOfChange.AESeverity,413530,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almRateOfChange.AEShelveDuration,413531,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI1.almPLCFault.BOOLS1,413536,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI1.almPLCFault.BOOLS2,413537,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI1.almPLCFault.AEBOOLS,413538,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI1.almPLCFault.INT1,413539,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almPLCFault.INT2,413540,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI1.almPLCFault.AENotify,413541,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI1.almPLCFault.AESeverity,413542,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI1.almPLCFault.AEShelveDuration,413543,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almHighHigh.BOOLS1,413640,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almHighHigh.BOOLS2,413641,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almHighHigh.AEBOOLS,413642,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almHighHigh.INT1,413643,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almHighHigh.INT2,413644,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almHighHigh.AENotify,413645,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almHighHigh.AESeverity,413646,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almHighHigh.AEShelveDuration,413647,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almHigh.BOOLS1,413652,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almHigh.BOOLS2,413653,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almHigh.AEBOOLS,413654,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almHigh.INT1,413655,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almHigh.INT2,413656,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almHigh.AENotify,413657,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almHigh.AESeverity,413658,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almHigh.AEShelveDuration,413659,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almLow.BOOLS1,413664,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almLow.BOOLS2,413665,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almLow.AEBOOLS,413666,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almLow.INT1,413667,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almLow.INT2,413668,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almLow.AENotify,413669,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almLow.AESeverity,413670,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almLow.AEShelveDuration,413671,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almLowLow.BOOLS1,413676,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almLowLow.BOOLS2,413677,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almLowLow.AEBOOLS,413678,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almLowLow.INT1,413679,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almLowLow.INT2,413680,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almLowLow.AENotify,413681,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almLowLow.AESeverity,413682,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almLowLow.AEShelveDuration,413683,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almBrokenLoop.BOOLS1,413688,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almBrokenLoop.BOOLS2,413689,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almBrokenLoop.AEBOOLS,413690,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almBrokenLoop.INT1,413691,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almBrokenLoop.INT2,413692,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almBrokenLoop.AENotify,413693,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almBrokenLoop.AESeverity,413694,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almBrokenLoop.AEShelveDuration,413695,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almOverRange.BOOLS1,413700,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almOverRange.BOOLS2,413701,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almOverRange.AEBOOLS,413702,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almOverRange.INT1,413703,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almOverRange.INT2,413704,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almOverRange.AENotify,413705,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almOverRange.AESeverity,413706,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almOverRange.AEShelveDuration,413707,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almUnderRange.BOOLS1,413712,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almUnderRange.BOOLS2,413713,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almUnderRange.AEBOOLS,413714,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almUnderRange.INT1,413715,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almUnderRange.INT2,413716,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almUnderRange.AENotify,413717,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almUnderRange.AESeverity,413718,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almUnderRange.AEShelveDuration,413719,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almRateOfChange.BOOLS1,413724,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almRateOfChange.BOOLS2,413725,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almRateOfChange.AEBOOLS,413726,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almRateOfChange.INT1,413727,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almRateOfChange.INT2,413728,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almRateOfChange.AENotify,413729,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almRateOfChange.AESeverity,413730,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almRateOfChange.AEShelveDuration,413731,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI2.almPLCFault.BOOLS1,413736,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI2.almPLCFault.BOOLS2,413737,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI2.almPLCFault.AEBOOLS,413738,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI2.almPLCFault.INT1,413739,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almPLCFault.INT2,413740,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI2.almPLCFault.AENotify,413741,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI2.almPLCFault.AESeverity,413742,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI2.almPLCFault.AEShelveDuration,413743,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almHighHigh.BOOLS1,413840,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almHighHigh.BOOLS2,413841,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almHighHigh.AEBOOLS,413842,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almHighHigh.INT1,413843,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almHighHigh.INT2,413844,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almHighHigh.AENotify,413845,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almHighHigh.AESeverity,413846,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almHighHigh.AEShelveDuration,413847,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almHigh.BOOLS1,413852,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almHigh.BOOLS2,413853,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almHigh.AEBOOLS,413854,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almHigh.INT1,413855,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almHigh.INT2,413856,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almHigh.AENotify,413857,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almHigh.AESeverity,413858,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almHigh.AEShelveDuration,413859,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almLow.BOOLS1,413864,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almLow.BOOLS2,413865,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almLow.AEBOOLS,413866,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almLow.INT1,413867,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almLow.INT2,413868,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almLow.AENotify,413869,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almLow.AESeverity,413870,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almLow.AEShelveDuration,413871,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almLowLow.BOOLS1,413876,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almLowLow.BOOLS2,413877,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almLowLow.AEBOOLS,413878,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almLowLow.INT1,413879,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almLowLow.INT2,413880,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almLowLow.AENotify,413881,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almLowLow.AESeverity,413882,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almLowLow.AEShelveDuration,413883,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almBrokenLoop.BOOLS1,413888,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almBrokenLoop.BOOLS2,413889,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almBrokenLoop.AEBOOLS,413890,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almBrokenLoop.INT1,413891,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almBrokenLoop.INT2,413892,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almBrokenLoop.AENotify,413893,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almBrokenLoop.AESeverity,413894,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almBrokenLoop.AEShelveDuration,413895,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almOverRange.BOOLS1,413900,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almOverRange.BOOLS2,413901,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almOverRange.AEBOOLS,413902,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almOverRange.INT1,413903,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almOverRange.INT2,413904,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almOverRange.AENotify,413905,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almOverRange.AESeverity,413906,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almOverRange.AEShelveDuration,413907,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almUnderRange.BOOLS1,413912,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almUnderRange.BOOLS2,413913,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almUnderRange.AEBOOLS,413914,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almUnderRange.INT1,413915,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almUnderRange.INT2,413916,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almUnderRange.AENotify,413917,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almUnderRange.AESeverity,413918,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almUnderRange.AEShelveDuration,413919,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almRateOfChange.BOOLS1,413924,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almRateOfChange.BOOLS2,413925,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almRateOfChange.AEBOOLS,413926,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almRateOfChange.INT1,413927,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almRateOfChange.INT2,413928,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almRateOfChange.AENotify,413929,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almRateOfChange.AESeverity,413930,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almRateOfChange.AEShelveDuration,413931,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI3.almPLCFault.BOOLS1,413936,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI3.almPLCFault.BOOLS2,413937,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI3.almPLCFault.AEBOOLS,413938,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI3.almPLCFault.INT1,413939,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almPLCFault.INT2,413940,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI3.almPLCFault.AENotify,413941,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI3.almPLCFault.AESeverity,413942,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI3.almPLCFault.AEShelveDuration,413943,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almHighHigh.BOOLS1,414040,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almHighHigh.BOOLS2,414041,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almHighHigh.AEBOOLS,414042,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almHighHigh.INT1,414043,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almHighHigh.INT2,414044,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almHighHigh.AENotify,414045,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almHighHigh.AESeverity,414046,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almHighHigh.AEShelveDuration,414047,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almHigh.BOOLS1,414052,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almHigh.BOOLS2,414053,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almHigh.AEBOOLS,414054,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almHigh.INT1,414055,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almHigh.INT2,414056,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almHigh.AENotify,414057,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almHigh.AESeverity,414058,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almHigh.AEShelveDuration,414059,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almLow.BOOLS1,414064,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almLow.BOOLS2,414065,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almLow.AEBOOLS,414066,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almLow.INT1,414067,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almLow.INT2,414068,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almLow.AENotify,414069,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almLow.AESeverity,414070,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almLow.AEShelveDuration,414071,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almLowLow.BOOLS1,414076,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almLowLow.BOOLS2,414077,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almLowLow.AEBOOLS,414078,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almLowLow.INT1,414079,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almLowLow.INT2,414080,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almLowLow.AENotify,414081,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almLowLow.AESeverity,414082,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almLowLow.AEShelveDuration,414083,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almBrokenLoop.BOOLS1,414088,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almBrokenLoop.BOOLS2,414089,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almBrokenLoop.AEBOOLS,414090,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almBrokenLoop.INT1,414091,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almBrokenLoop.INT2,414092,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almBrokenLoop.AENotify,414093,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almBrokenLoop.AESeverity,414094,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almBrokenLoop.AEShelveDuration,414095,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almOverRange.BOOLS1,414100,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almOverRange.BOOLS2,414101,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almOverRange.AEBOOLS,414102,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almOverRange.INT1,414103,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almOverRange.INT2,414104,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almOverRange.AENotify,414105,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almOverRange.AESeverity,414106,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almOverRange.AEShelveDuration,414107,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almUnderRange.BOOLS1,414112,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almUnderRange.BOOLS2,414113,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almUnderRange.AEBOOLS,414114,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almUnderRange.INT1,414115,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almUnderRange.INT2,414116,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almUnderRange.AENotify,414117,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almUnderRange.AESeverity,414118,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almUnderRange.AEShelveDuration,414119,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almRateOfChange.BOOLS1,414124,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almRateOfChange.BOOLS2,414125,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almRateOfChange.AEBOOLS,414126,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almRateOfChange.INT1,414127,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almRateOfChange.INT2,414128,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almRateOfChange.AENotify,414129,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almRateOfChange.AESeverity,414130,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almRateOfChange.AEShelveDuration,414131,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_MTR_0103_9_VI4.almPLCFault.BOOLS1,414136,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_MTR_0103_9_VI4.almPLCFault.BOOLS2,414137,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_MTR_0103_9_VI4.almPLCFault.AEBOOLS,414138,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_MTR_0103_9_VI4.almPLCFault.INT1,414139,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almPLCFault.INT2,414140,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_MTR_0103_9_VI4.almPLCFault.AENotify,414141,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_MTR_0103_9_VI4.almPLCFault.AESeverity,414142,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_MTR_0103_9_VI4.almPLCFault.AEShelveDuration,414143,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almHighHigh.BOOLS1,414240,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almHighHigh.BOOLS2,414241,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almHighHigh.AEBOOLS,414242,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almHighHigh.INT1,414243,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almHighHigh.INT2,414244,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almHighHigh.AENotify,414245,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almHighHigh.AESeverity,414246,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almHighHigh.AEShelveDuration,414247,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almHigh.BOOLS1,414252,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almHigh.BOOLS2,414253,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almHigh.AEBOOLS,414254,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almHigh.INT1,414255,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almHigh.INT2,414256,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almHigh.AENotify,414257,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almHigh.AESeverity,414258,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almHigh.AEShelveDuration,414259,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almLow.BOOLS1,414264,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almLow.BOOLS2,414265,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almLow.AEBOOLS,414266,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almLow.INT1,414267,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almLow.INT2,414268,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almLow.AENotify,414269,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almLow.AESeverity,414270,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almLow.AEShelveDuration,414271,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almLowLow.BOOLS1,414276,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almLowLow.BOOLS2,414277,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almLowLow.AEBOOLS,414278,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almLowLow.INT1,414279,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almLowLow.INT2,414280,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almLowLow.AENotify,414281,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almLowLow.AESeverity,414282,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almLowLow.AEShelveDuration,414283,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almBrokenLoop.BOOLS1,414288,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almBrokenLoop.BOOLS2,414289,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almBrokenLoop.AEBOOLS,414290,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almBrokenLoop.INT1,414291,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almBrokenLoop.INT2,414292,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almBrokenLoop.AENotify,414293,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almBrokenLoop.AESeverity,414294,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almBrokenLoop.AEShelveDuration,414295,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almOverRange.BOOLS1,414300,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almOverRange.BOOLS2,414301,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almOverRange.AEBOOLS,414302,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almOverRange.INT1,414303,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almOverRange.INT2,414304,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almOverRange.AENotify,414305,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almOverRange.AESeverity,414306,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almOverRange.AEShelveDuration,414307,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almUnderRange.BOOLS1,414312,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almUnderRange.BOOLS2,414313,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almUnderRange.AEBOOLS,414314,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almUnderRange.INT1,414315,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almUnderRange.INT2,414316,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almUnderRange.AENotify,414317,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almUnderRange.AESeverity,414318,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almUnderRange.AEShelveDuration,414319,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almRateOfChange.BOOLS1,414324,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almRateOfChange.BOOLS2,414325,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almRateOfChange.AEBOOLS,414326,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almRateOfChange.INT1,414327,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almRateOfChange.INT2,414328,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almRateOfChange.AENotify,414329,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almRateOfChange.AESeverity,414330,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almRateOfChange.AEShelveDuration,414331,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PI.almPLCFault.BOOLS1,414336,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PI.almPLCFault.BOOLS2,414337,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PI.almPLCFault.AEBOOLS,414338,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PI.almPLCFault.INT1,414339,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almPLCFault.INT2,414340,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PI.almPLCFault.AENotify,414341,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PI.almPLCFault.AESeverity,414342,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PI.almPLCFault.AEShelveDuration,414343,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almHighHigh.BOOLS1,414440,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almHighHigh.BOOLS2,414441,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almHighHigh.AEBOOLS,414442,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almHighHigh.INT1,414443,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almHighHigh.INT2,414444,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almHighHigh.AENotify,414445,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almHighHigh.AESeverity,414446,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almHighHigh.AEShelveDuration,414447,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almHigh.BOOLS1,414452,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almHigh.BOOLS2,414453,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almHigh.AEBOOLS,414454,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almHigh.INT1,414455,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almHigh.INT2,414456,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almHigh.AENotify,414457,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almHigh.AESeverity,414458,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almHigh.AEShelveDuration,414459,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almLow.BOOLS1,414464,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almLow.BOOLS2,414465,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almLow.AEBOOLS,414466,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almLow.INT1,414467,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almLow.INT2,414468,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almLow.AENotify,414469,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almLow.AESeverity,414470,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almLow.AEShelveDuration,414471,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almLowLow.BOOLS1,414476,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almLowLow.BOOLS2,414477,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almLowLow.AEBOOLS,414478,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almLowLow.INT1,414479,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almLowLow.INT2,414480,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almLowLow.AENotify,414481,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almLowLow.AESeverity,414482,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almLowLow.AEShelveDuration,414483,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almBrokenLoop.BOOLS1,414488,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almBrokenLoop.BOOLS2,414489,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almBrokenLoop.AEBOOLS,414490,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almBrokenLoop.INT1,414491,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almBrokenLoop.INT2,414492,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almBrokenLoop.AENotify,414493,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almBrokenLoop.AESeverity,414494,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almBrokenLoop.AEShelveDuration,414495,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almOverRange.BOOLS1,414500,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almOverRange.BOOLS2,414501,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almOverRange.AEBOOLS,414502,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almOverRange.INT1,414503,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almOverRange.INT2,414504,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almOverRange.AENotify,414505,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almOverRange.AESeverity,414506,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almOverRange.AEShelveDuration,414507,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almUnderRange.BOOLS1,414512,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almUnderRange.BOOLS2,414513,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almUnderRange.AEBOOLS,414514,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almUnderRange.INT1,414515,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almUnderRange.INT2,414516,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almUnderRange.AENotify,414517,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almUnderRange.AESeverity,414518,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almUnderRange.AEShelveDuration,414519,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almRateOfChange.BOOLS1,414524,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almRateOfChange.BOOLS2,414525,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almRateOfChange.AEBOOLS,414526,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almRateOfChange.INT1,414527,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almRateOfChange.INT2,414528,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almRateOfChange.AENotify,414529,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almRateOfChange.AESeverity,414530,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almRateOfChange.AEShelveDuration,414531,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PI.almPLCFault.BOOLS1,414536,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PI.almPLCFault.BOOLS2,414537,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PI.almPLCFault.AEBOOLS,414538,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PI.almPLCFault.INT1,414539,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almPLCFault.INT2,414540,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PI.almPLCFault.AENotify,414541,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PI.almPLCFault.AESeverity,414542,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PI.almPLCFault.AEShelveDuration,414543,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almHighHigh.BOOLS1,414640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almHighHigh.BOOLS2,414641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almHighHigh.AEBOOLS,414642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almHighHigh.INT1,414643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almHighHigh.INT2,414644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almHighHigh.AENotify,414645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almHighHigh.AESeverity,414646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almHighHigh.AEShelveDuration,414647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almHigh.BOOLS1,414652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almHigh.BOOLS2,414653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almHigh.AEBOOLS,414654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almHigh.INT1,414655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almHigh.INT2,414656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almHigh.AENotify,414657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almHigh.AESeverity,414658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almHigh.AEShelveDuration,414659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almLow.BOOLS1,414664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almLow.BOOLS2,414665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almLow.AEBOOLS,414666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almLow.INT1,414667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almLow.INT2,414668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almLow.AENotify,414669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almLow.AESeverity,414670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almLow.AEShelveDuration,414671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almLowLow.BOOLS1,414676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almLowLow.BOOLS2,414677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almLowLow.AEBOOLS,414678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almLowLow.INT1,414679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almLowLow.INT2,414680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almLowLow.AENotify,414681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almLowLow.AESeverity,414682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almLowLow.AEShelveDuration,414683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almBrokenLoop.BOOLS1,414688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almBrokenLoop.BOOLS2,414689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almBrokenLoop.AEBOOLS,414690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almBrokenLoop.INT1,414691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almBrokenLoop.INT2,414692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almBrokenLoop.AENotify,414693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almBrokenLoop.AESeverity,414694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almBrokenLoop.AEShelveDuration,414695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almOverRange.BOOLS1,414700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almOverRange.BOOLS2,414701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almOverRange.AEBOOLS,414702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almOverRange.INT1,414703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almOverRange.INT2,414704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almOverRange.AENotify,414705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almOverRange.AESeverity,414706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almOverRange.AEShelveDuration,414707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almUnderRange.BOOLS1,414712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almUnderRange.BOOLS2,414713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almUnderRange.AEBOOLS,414714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almUnderRange.INT1,414715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almUnderRange.INT2,414716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almUnderRange.AENotify,414717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almUnderRange.AESeverity,414718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almUnderRange.AEShelveDuration,414719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almRateOfChange.BOOLS1,414724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almRateOfChange.BOOLS2,414725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almRateOfChange.AEBOOLS,414726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almRateOfChange.INT1,414727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almRateOfChange.INT2,414728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almRateOfChange.AENotify,414729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almRateOfChange.AESeverity,414730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almRateOfChange.AEShelveDuration,414731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_1_PI.almPLCFault.BOOLS1,414736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_1_PI.almPLCFault.BOOLS2,414737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_1_PI.almPLCFault.AEBOOLS,414738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_1_PI.almPLCFault.INT1,414739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almPLCFault.INT2,414740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_1_PI.almPLCFault.AENotify,414741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_1_PI.almPLCFault.AESeverity,414742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_1_PI.almPLCFault.AEShelveDuration,414743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almHighHigh.BOOLS1,414840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almHighHigh.BOOLS2,414841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almHighHigh.AEBOOLS,414842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almHighHigh.INT1,414843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almHighHigh.INT2,414844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almHighHigh.AENotify,414845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almHighHigh.AESeverity,414846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almHighHigh.AEShelveDuration,414847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almHigh.BOOLS1,414852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almHigh.BOOLS2,414853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almHigh.AEBOOLS,414854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almHigh.INT1,414855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almHigh.INT2,414856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almHigh.AENotify,414857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almHigh.AESeverity,414858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almHigh.AEShelveDuration,414859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almLow.BOOLS1,414864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almLow.BOOLS2,414865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almLow.AEBOOLS,414866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almLow.INT1,414867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almLow.INT2,414868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almLow.AENotify,414869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almLow.AESeverity,414870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almLow.AEShelveDuration,414871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almLowLow.BOOLS1,414876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almLowLow.BOOLS2,414877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almLowLow.AEBOOLS,414878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almLowLow.INT1,414879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almLowLow.INT2,414880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almLowLow.AENotify,414881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almLowLow.AESeverity,414882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almLowLow.AEShelveDuration,414883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almBrokenLoop.BOOLS1,414888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almBrokenLoop.BOOLS2,414889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almBrokenLoop.AEBOOLS,414890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almBrokenLoop.INT1,414891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almBrokenLoop.INT2,414892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almBrokenLoop.AENotify,414893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almBrokenLoop.AESeverity,414894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almBrokenLoop.AEShelveDuration,414895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almOverRange.BOOLS1,414900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almOverRange.BOOLS2,414901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almOverRange.AEBOOLS,414902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almOverRange.INT1,414903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almOverRange.INT2,414904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almOverRange.AENotify,414905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almOverRange.AESeverity,414906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almOverRange.AEShelveDuration,414907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almUnderRange.BOOLS1,414912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almUnderRange.BOOLS2,414913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almUnderRange.AEBOOLS,414914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almUnderRange.INT1,414915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almUnderRange.INT2,414916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almUnderRange.AENotify,414917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almUnderRange.AESeverity,414918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almUnderRange.AEShelveDuration,414919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almRateOfChange.BOOLS1,414924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almRateOfChange.BOOLS2,414925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almRateOfChange.AEBOOLS,414926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almRateOfChange.INT1,414927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almRateOfChange.INT2,414928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almRateOfChange.AENotify,414929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almRateOfChange.AESeverity,414930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almRateOfChange.AEShelveDuration,414931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_2_PI.almPLCFault.BOOLS1,414936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_2_PI.almPLCFault.BOOLS2,414937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_2_PI.almPLCFault.AEBOOLS,414938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_2_PI.almPLCFault.INT1,414939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almPLCFault.INT2,414940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_2_PI.almPLCFault.AENotify,414941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_2_PI.almPLCFault.AESeverity,414942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_2_PI.almPLCFault.AEShelveDuration,414943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almHighHigh.BOOLS1,415040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almHighHigh.BOOLS2,415041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almHighHigh.AEBOOLS,415042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almHighHigh.INT1,415043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almHighHigh.INT2,415044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almHighHigh.AENotify,415045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almHighHigh.AESeverity,415046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almHighHigh.AEShelveDuration,415047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almHigh.BOOLS1,415052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almHigh.BOOLS2,415053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almHigh.AEBOOLS,415054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almHigh.INT1,415055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almHigh.INT2,415056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almHigh.AENotify,415057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almHigh.AESeverity,415058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almHigh.AEShelveDuration,415059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almLow.BOOLS1,415064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almLow.BOOLS2,415065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almLow.AEBOOLS,415066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almLow.INT1,415067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almLow.INT2,415068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almLow.AENotify,415069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almLow.AESeverity,415070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almLow.AEShelveDuration,415071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almLowLow.BOOLS1,415076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almLowLow.BOOLS2,415077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almLowLow.AEBOOLS,415078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almLowLow.INT1,415079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almLowLow.INT2,415080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almLowLow.AENotify,415081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almLowLow.AESeverity,415082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almLowLow.AEShelveDuration,415083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almBrokenLoop.BOOLS1,415088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almBrokenLoop.BOOLS2,415089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almBrokenLoop.AEBOOLS,415090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almBrokenLoop.INT1,415091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almBrokenLoop.INT2,415092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almBrokenLoop.AENotify,415093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almBrokenLoop.AESeverity,415094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almBrokenLoop.AEShelveDuration,415095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almOverRange.BOOLS1,415100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almOverRange.BOOLS2,415101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almOverRange.AEBOOLS,415102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almOverRange.INT1,415103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almOverRange.INT2,415104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almOverRange.AENotify,415105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almOverRange.AESeverity,415106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almOverRange.AEShelveDuration,415107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almUnderRange.BOOLS1,415112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almUnderRange.BOOLS2,415113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almUnderRange.AEBOOLS,415114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almUnderRange.INT1,415115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almUnderRange.INT2,415116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almUnderRange.AENotify,415117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almUnderRange.AESeverity,415118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almUnderRange.AEShelveDuration,415119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almRateOfChange.BOOLS1,415124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almRateOfChange.BOOLS2,415125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almRateOfChange.AEBOOLS,415126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almRateOfChange.INT1,415127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almRateOfChange.INT2,415128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almRateOfChange.AENotify,415129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almRateOfChange.AESeverity,415130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almRateOfChange.AEShelveDuration,415131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_3_PI.almPLCFault.BOOLS1,415136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_3_PI.almPLCFault.BOOLS2,415137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_3_PI.almPLCFault.AEBOOLS,415138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_3_PI.almPLCFault.INT1,415139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almPLCFault.INT2,415140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_3_PI.almPLCFault.AENotify,415141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_3_PI.almPLCFault.AESeverity,415142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_3_PI.almPLCFault.AEShelveDuration,415143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almHighHigh.BOOLS1,415240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almHighHigh.BOOLS2,415241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almHighHigh.AEBOOLS,415242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almHighHigh.INT1,415243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almHighHigh.INT2,415244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almHighHigh.AENotify,415245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almHighHigh.AESeverity,415246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almHighHigh.AEShelveDuration,415247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almHigh.BOOLS1,415252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almHigh.BOOLS2,415253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almHigh.AEBOOLS,415254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almHigh.INT1,415255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almHigh.INT2,415256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almHigh.AENotify,415257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almHigh.AESeverity,415258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almHigh.AEShelveDuration,415259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almLow.BOOLS1,415264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almLow.BOOLS2,415265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almLow.AEBOOLS,415266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almLow.INT1,415267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almLow.INT2,415268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almLow.AENotify,415269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almLow.AESeverity,415270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almLow.AEShelveDuration,415271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almLowLow.BOOLS1,415276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almLowLow.BOOLS2,415277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almLowLow.AEBOOLS,415278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almLowLow.INT1,415279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almLowLow.INT2,415280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almLowLow.AENotify,415281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almLowLow.AESeverity,415282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almLowLow.AEShelveDuration,415283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almBrokenLoop.BOOLS1,415288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almBrokenLoop.BOOLS2,415289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almBrokenLoop.AEBOOLS,415290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almBrokenLoop.INT1,415291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almBrokenLoop.INT2,415292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almBrokenLoop.AENotify,415293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almBrokenLoop.AESeverity,415294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almBrokenLoop.AEShelveDuration,415295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almOverRange.BOOLS1,415300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almOverRange.BOOLS2,415301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almOverRange.AEBOOLS,415302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almOverRange.INT1,415303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almOverRange.INT2,415304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almOverRange.AENotify,415305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almOverRange.AESeverity,415306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almOverRange.AEShelveDuration,415307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almUnderRange.BOOLS1,415312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almUnderRange.BOOLS2,415313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almUnderRange.AEBOOLS,415314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almUnderRange.INT1,415315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almUnderRange.INT2,415316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almUnderRange.AENotify,415317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almUnderRange.AESeverity,415318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almUnderRange.AEShelveDuration,415319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almRateOfChange.BOOLS1,415324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almRateOfChange.BOOLS2,415325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almRateOfChange.AEBOOLS,415326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almRateOfChange.INT1,415327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almRateOfChange.INT2,415328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almRateOfChange.AENotify,415329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almRateOfChange.AESeverity,415330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almRateOfChange.AEShelveDuration,415331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_4_PI.almPLCFault.BOOLS1,415336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_4_PI.almPLCFault.BOOLS2,415337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_4_PI.almPLCFault.AEBOOLS,415338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_4_PI.almPLCFault.INT1,415339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almPLCFault.INT2,415340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_4_PI.almPLCFault.AENotify,415341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_4_PI.almPLCFault.AESeverity,415342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_4_PI.almPLCFault.AEShelveDuration,415343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almHighHigh.BOOLS1,415440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almHighHigh.BOOLS2,415441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almHighHigh.AEBOOLS,415442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almHighHigh.INT1,415443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almHighHigh.INT2,415444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almHighHigh.AENotify,415445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almHighHigh.AESeverity,415446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almHighHigh.AEShelveDuration,415447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almHigh.BOOLS1,415452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almHigh.BOOLS2,415453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almHigh.AEBOOLS,415454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almHigh.INT1,415455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almHigh.INT2,415456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almHigh.AENotify,415457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almHigh.AESeverity,415458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almHigh.AEShelveDuration,415459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almLow.BOOLS1,415464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almLow.BOOLS2,415465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almLow.AEBOOLS,415466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almLow.INT1,415467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almLow.INT2,415468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almLow.AENotify,415469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almLow.AESeverity,415470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almLow.AEShelveDuration,415471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almLowLow.BOOLS1,415476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almLowLow.BOOLS2,415477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almLowLow.AEBOOLS,415478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almLowLow.INT1,415479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almLowLow.INT2,415480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almLowLow.AENotify,415481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almLowLow.AESeverity,415482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almLowLow.AEShelveDuration,415483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almBrokenLoop.BOOLS1,415488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almBrokenLoop.BOOLS2,415489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almBrokenLoop.AEBOOLS,415490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almBrokenLoop.INT1,415491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almBrokenLoop.INT2,415492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almBrokenLoop.AENotify,415493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almBrokenLoop.AESeverity,415494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almBrokenLoop.AEShelveDuration,415495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almOverRange.BOOLS1,415500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almOverRange.BOOLS2,415501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almOverRange.AEBOOLS,415502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almOverRange.INT1,415503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almOverRange.INT2,415504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almOverRange.AENotify,415505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almOverRange.AESeverity,415506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almOverRange.AEShelveDuration,415507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almUnderRange.BOOLS1,415512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almUnderRange.BOOLS2,415513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almUnderRange.AEBOOLS,415514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almUnderRange.INT1,415515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almUnderRange.INT2,415516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almUnderRange.AENotify,415517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almUnderRange.AESeverity,415518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almUnderRange.AEShelveDuration,415519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almRateOfChange.BOOLS1,415524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almRateOfChange.BOOLS2,415525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almRateOfChange.AEBOOLS,415526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almRateOfChange.INT1,415527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almRateOfChange.INT2,415528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almRateOfChange.AENotify,415529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almRateOfChange.AESeverity,415530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almRateOfChange.AEShelveDuration,415531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_5_PI.almPLCFault.BOOLS1,415536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_5_PI.almPLCFault.BOOLS2,415537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_5_PI.almPLCFault.AEBOOLS,415538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_5_PI.almPLCFault.INT1,415539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almPLCFault.INT2,415540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_5_PI.almPLCFault.AENotify,415541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_5_PI.almPLCFault.AESeverity,415542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_5_PI.almPLCFault.AEShelveDuration,415543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almHighHigh.BOOLS1,415640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almHighHigh.BOOLS2,415641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almHighHigh.AEBOOLS,415642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almHighHigh.INT1,415643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almHighHigh.INT2,415644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almHighHigh.AENotify,415645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almHighHigh.AESeverity,415646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almHighHigh.AEShelveDuration,415647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almHigh.BOOLS1,415652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almHigh.BOOLS2,415653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almHigh.AEBOOLS,415654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almHigh.INT1,415655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almHigh.INT2,415656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almHigh.AENotify,415657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almHigh.AESeverity,415658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almHigh.AEShelveDuration,415659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almLow.BOOLS1,415664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almLow.BOOLS2,415665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almLow.AEBOOLS,415666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almLow.INT1,415667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almLow.INT2,415668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almLow.AENotify,415669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almLow.AESeverity,415670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almLow.AEShelveDuration,415671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almLowLow.BOOLS1,415676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almLowLow.BOOLS2,415677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almLowLow.AEBOOLS,415678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almLowLow.INT1,415679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almLowLow.INT2,415680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almLowLow.AENotify,415681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almLowLow.AESeverity,415682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almLowLow.AEShelveDuration,415683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almBrokenLoop.BOOLS1,415688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almBrokenLoop.BOOLS2,415689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almBrokenLoop.AEBOOLS,415690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almBrokenLoop.INT1,415691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almBrokenLoop.INT2,415692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almBrokenLoop.AENotify,415693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almBrokenLoop.AESeverity,415694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almBrokenLoop.AEShelveDuration,415695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almOverRange.BOOLS1,415700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almOverRange.BOOLS2,415701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almOverRange.AEBOOLS,415702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almOverRange.INT1,415703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almOverRange.INT2,415704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almOverRange.AENotify,415705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almOverRange.AESeverity,415706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almOverRange.AEShelveDuration,415707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almUnderRange.BOOLS1,415712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almUnderRange.BOOLS2,415713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almUnderRange.AEBOOLS,415714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almUnderRange.INT1,415715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almUnderRange.INT2,415716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almUnderRange.AENotify,415717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almUnderRange.AESeverity,415718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almUnderRange.AEShelveDuration,415719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almRateOfChange.BOOLS1,415724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almRateOfChange.BOOLS2,415725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almRateOfChange.AEBOOLS,415726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almRateOfChange.INT1,415727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almRateOfChange.INT2,415728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almRateOfChange.AENotify,415729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almRateOfChange.AESeverity,415730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almRateOfChange.AEShelveDuration,415731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_6_PI.almPLCFault.BOOLS1,415736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_6_PI.almPLCFault.BOOLS2,415737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_6_PI.almPLCFault.AEBOOLS,415738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_6_PI.almPLCFault.INT1,415739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almPLCFault.INT2,415740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_6_PI.almPLCFault.AENotify,415741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_6_PI.almPLCFault.AESeverity,415742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_6_PI.almPLCFault.AEShelveDuration,415743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almHighHigh.BOOLS1,415840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almHighHigh.BOOLS2,415841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almHighHigh.AEBOOLS,415842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almHighHigh.INT1,415843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almHighHigh.INT2,415844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almHighHigh.AENotify,415845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almHighHigh.AESeverity,415846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almHighHigh.AEShelveDuration,415847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almHigh.BOOLS1,415852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almHigh.BOOLS2,415853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almHigh.AEBOOLS,415854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almHigh.INT1,415855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almHigh.INT2,415856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almHigh.AENotify,415857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almHigh.AESeverity,415858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almHigh.AEShelveDuration,415859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almLow.BOOLS1,415864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almLow.BOOLS2,415865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almLow.AEBOOLS,415866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almLow.INT1,415867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almLow.INT2,415868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almLow.AENotify,415869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almLow.AESeverity,415870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almLow.AEShelveDuration,415871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almLowLow.BOOLS1,415876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almLowLow.BOOLS2,415877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almLowLow.AEBOOLS,415878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almLowLow.INT1,415879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almLowLow.INT2,415880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almLowLow.AENotify,415881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almLowLow.AESeverity,415882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almLowLow.AEShelveDuration,415883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almBrokenLoop.BOOLS1,415888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almBrokenLoop.BOOLS2,415889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almBrokenLoop.AEBOOLS,415890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almBrokenLoop.INT1,415891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almBrokenLoop.INT2,415892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almBrokenLoop.AENotify,415893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almBrokenLoop.AESeverity,415894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almBrokenLoop.AEShelveDuration,415895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almOverRange.BOOLS1,415900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almOverRange.BOOLS2,415901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almOverRange.AEBOOLS,415902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almOverRange.INT1,415903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almOverRange.INT2,415904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almOverRange.AENotify,415905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almOverRange.AESeverity,415906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almOverRange.AEShelveDuration,415907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almUnderRange.BOOLS1,415912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almUnderRange.BOOLS2,415913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almUnderRange.AEBOOLS,415914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almUnderRange.INT1,415915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almUnderRange.INT2,415916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almUnderRange.AENotify,415917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almUnderRange.AESeverity,415918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almUnderRange.AEShelveDuration,415919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almRateOfChange.BOOLS1,415924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almRateOfChange.BOOLS2,415925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almRateOfChange.AEBOOLS,415926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almRateOfChange.INT1,415927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almRateOfChange.INT2,415928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almRateOfChange.AENotify,415929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almRateOfChange.AESeverity,415930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almRateOfChange.AEShelveDuration,415931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_7_PI.almPLCFault.BOOLS1,415936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_7_PI.almPLCFault.BOOLS2,415937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_7_PI.almPLCFault.AEBOOLS,415938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_7_PI.almPLCFault.INT1,415939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almPLCFault.INT2,415940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_7_PI.almPLCFault.AENotify,415941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_7_PI.almPLCFault.AESeverity,415942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_7_PI.almPLCFault.AEShelveDuration,415943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almHighHigh.BOOLS1,416040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almHighHigh.BOOLS2,416041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almHighHigh.AEBOOLS,416042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almHighHigh.INT1,416043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almHighHigh.INT2,416044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almHighHigh.AENotify,416045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almHighHigh.AESeverity,416046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almHighHigh.AEShelveDuration,416047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almHigh.BOOLS1,416052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almHigh.BOOLS2,416053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almHigh.AEBOOLS,416054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almHigh.INT1,416055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almHigh.INT2,416056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almHigh.AENotify,416057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almHigh.AESeverity,416058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almHigh.AEShelveDuration,416059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almLow.BOOLS1,416064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almLow.BOOLS2,416065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almLow.AEBOOLS,416066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almLow.INT1,416067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almLow.INT2,416068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almLow.AENotify,416069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almLow.AESeverity,416070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almLow.AEShelveDuration,416071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almLowLow.BOOLS1,416076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almLowLow.BOOLS2,416077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almLowLow.AEBOOLS,416078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almLowLow.INT1,416079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almLowLow.INT2,416080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almLowLow.AENotify,416081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almLowLow.AESeverity,416082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almLowLow.AEShelveDuration,416083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almBrokenLoop.BOOLS1,416088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almBrokenLoop.BOOLS2,416089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almBrokenLoop.AEBOOLS,416090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almBrokenLoop.INT1,416091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almBrokenLoop.INT2,416092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almBrokenLoop.AENotify,416093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almBrokenLoop.AESeverity,416094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almBrokenLoop.AEShelveDuration,416095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almOverRange.BOOLS1,416100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almOverRange.BOOLS2,416101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almOverRange.AEBOOLS,416102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almOverRange.INT1,416103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almOverRange.INT2,416104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almOverRange.AENotify,416105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almOverRange.AESeverity,416106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almOverRange.AEShelveDuration,416107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almUnderRange.BOOLS1,416112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almUnderRange.BOOLS2,416113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almUnderRange.AEBOOLS,416114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almUnderRange.INT1,416115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almUnderRange.INT2,416116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almUnderRange.AENotify,416117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almUnderRange.AESeverity,416118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almUnderRange.AEShelveDuration,416119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almRateOfChange.BOOLS1,416124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almRateOfChange.BOOLS2,416125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almRateOfChange.AEBOOLS,416126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almRateOfChange.INT1,416127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almRateOfChange.INT2,416128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almRateOfChange.AENotify,416129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almRateOfChange.AESeverity,416130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almRateOfChange.AEShelveDuration,416131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_8_PI.almPLCFault.BOOLS1,416136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_8_PI.almPLCFault.BOOLS2,416137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_8_PI.almPLCFault.AEBOOLS,416138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_8_PI.almPLCFault.INT1,416139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almPLCFault.INT2,416140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_8_PI.almPLCFault.AENotify,416141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_8_PI.almPLCFault.AESeverity,416142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_8_PI.almPLCFault.AEShelveDuration,416143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almHighHigh.BOOLS1,416240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almHighHigh.BOOLS2,416241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almHighHigh.AEBOOLS,416242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almHighHigh.INT1,416243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almHighHigh.INT2,416244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almHighHigh.AENotify,416245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almHighHigh.AESeverity,416246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almHighHigh.AEShelveDuration,416247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almHigh.BOOLS1,416252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almHigh.BOOLS2,416253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almHigh.AEBOOLS,416254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almHigh.INT1,416255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almHigh.INT2,416256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almHigh.AENotify,416257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almHigh.AESeverity,416258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almHigh.AEShelveDuration,416259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almLow.BOOLS1,416264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almLow.BOOLS2,416265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almLow.AEBOOLS,416266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almLow.INT1,416267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almLow.INT2,416268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almLow.AENotify,416269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almLow.AESeverity,416270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almLow.AEShelveDuration,416271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almLowLow.BOOLS1,416276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almLowLow.BOOLS2,416277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almLowLow.AEBOOLS,416278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almLowLow.INT1,416279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almLowLow.INT2,416280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almLowLow.AENotify,416281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almLowLow.AESeverity,416282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almLowLow.AEShelveDuration,416283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almBrokenLoop.BOOLS1,416288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almBrokenLoop.BOOLS2,416289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almBrokenLoop.AEBOOLS,416290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almBrokenLoop.INT1,416291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almBrokenLoop.INT2,416292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almBrokenLoop.AENotify,416293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almBrokenLoop.AESeverity,416294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almBrokenLoop.AEShelveDuration,416295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almOverRange.BOOLS1,416300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almOverRange.BOOLS2,416301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almOverRange.AEBOOLS,416302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almOverRange.INT1,416303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almOverRange.INT2,416304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almOverRange.AENotify,416305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almOverRange.AESeverity,416306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almOverRange.AEShelveDuration,416307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almUnderRange.BOOLS1,416312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almUnderRange.BOOLS2,416313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almUnderRange.AEBOOLS,416314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almUnderRange.INT1,416315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almUnderRange.INT2,416316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almUnderRange.AENotify,416317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almUnderRange.AESeverity,416318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almUnderRange.AEShelveDuration,416319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almRateOfChange.BOOLS1,416324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almRateOfChange.BOOLS2,416325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almRateOfChange.AEBOOLS,416326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almRateOfChange.INT1,416327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almRateOfChange.INT2,416328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almRateOfChange.AENotify,416329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almRateOfChange.AESeverity,416330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almRateOfChange.AEShelveDuration,416331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0103_9_PI.almPLCFault.BOOLS1,416336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0103_9_PI.almPLCFault.BOOLS2,416337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0103_9_PI.almPLCFault.AEBOOLS,416338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0103_9_PI.almPLCFault.INT1,416339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almPLCFault.INT2,416340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0103_9_PI.almPLCFault.AENotify,416341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0103_9_PI.almPLCFault.AESeverity,416342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0103_9_PI.almPLCFault.AEShelveDuration,416343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almHighHigh.BOOLS1,416440,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almHighHigh.BOOLS2,416441,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almHighHigh.AEBOOLS,416442,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almHighHigh.INT1,416443,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almHighHigh.INT2,416444,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almHighHigh.AENotify,416445,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almHighHigh.AESeverity,416446,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almHighHigh.AEShelveDuration,416447,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almHigh.BOOLS1,416452,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almHigh.BOOLS2,416453,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almHigh.AEBOOLS,416454,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almHigh.INT1,416455,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almHigh.INT2,416456,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almHigh.AENotify,416457,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almHigh.AESeverity,416458,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almHigh.AEShelveDuration,416459,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almLow.BOOLS1,416464,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almLow.BOOLS2,416465,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almLow.AEBOOLS,416466,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almLow.INT1,416467,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almLow.INT2,416468,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almLow.AENotify,416469,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almLow.AESeverity,416470,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almLow.AEShelveDuration,416471,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almLowLow.BOOLS1,416476,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almLowLow.BOOLS2,416477,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almLowLow.AEBOOLS,416478,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almLowLow.INT1,416479,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almLowLow.INT2,416480,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almLowLow.AENotify,416481,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almLowLow.AESeverity,416482,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almLowLow.AEShelveDuration,416483,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almBrokenLoop.BOOLS1,416488,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almBrokenLoop.BOOLS2,416489,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almBrokenLoop.AEBOOLS,416490,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almBrokenLoop.INT1,416491,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almBrokenLoop.INT2,416492,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almBrokenLoop.AENotify,416493,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almBrokenLoop.AESeverity,416494,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almBrokenLoop.AEShelveDuration,416495,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almOverRange.BOOLS1,416500,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almOverRange.BOOLS2,416501,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almOverRange.AEBOOLS,416502,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almOverRange.INT1,416503,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almOverRange.INT2,416504,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almOverRange.AENotify,416505,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almOverRange.AESeverity,416506,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almOverRange.AEShelveDuration,416507,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almUnderRange.BOOLS1,416512,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almUnderRange.BOOLS2,416513,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almUnderRange.AEBOOLS,416514,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almUnderRange.INT1,416515,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almUnderRange.INT2,416516,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almUnderRange.AENotify,416517,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almUnderRange.AESeverity,416518,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almUnderRange.AEShelveDuration,416519,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almRateOfChange.BOOLS1,416524,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almRateOfChange.BOOLS2,416525,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almRateOfChange.AEBOOLS,416526,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almRateOfChange.INT1,416527,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almRateOfChange.INT2,416528,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almRateOfChange.AENotify,416529,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almRateOfChange.AESeverity,416530,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almRateOfChange.AEShelveDuration,416531,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0104_1_PI.almPLCFault.BOOLS1,416536,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0104_1_PI.almPLCFault.BOOLS2,416537,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0104_1_PI.almPLCFault.AEBOOLS,416538,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0104_1_PI.almPLCFault.INT1,416539,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almPLCFault.INT2,416540,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0104_1_PI.almPLCFault.AENotify,416541,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0104_1_PI.almPLCFault.AESeverity,416542,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0104_1_PI.almPLCFault.AEShelveDuration,416543,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almHighHigh.BOOLS1,416640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almHighHigh.BOOLS2,416641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almHighHigh.AEBOOLS,416642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almHighHigh.INT1,416643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almHighHigh.INT2,416644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almHighHigh.AENotify,416645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almHighHigh.AESeverity,416646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almHighHigh.AEShelveDuration,416647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almHigh.BOOLS1,416652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almHigh.BOOLS2,416653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almHigh.AEBOOLS,416654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almHigh.INT1,416655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almHigh.INT2,416656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almHigh.AENotify,416657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almHigh.AESeverity,416658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almHigh.AEShelveDuration,416659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almLow.BOOLS1,416664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almLow.BOOLS2,416665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almLow.AEBOOLS,416666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almLow.INT1,416667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almLow.INT2,416668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almLow.AENotify,416669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almLow.AESeverity,416670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almLow.AEShelveDuration,416671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almLowLow.BOOLS1,416676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almLowLow.BOOLS2,416677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almLowLow.AEBOOLS,416678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almLowLow.INT1,416679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almLowLow.INT2,416680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almLowLow.AENotify,416681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almLowLow.AESeverity,416682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almLowLow.AEShelveDuration,416683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almBrokenLoop.BOOLS1,416688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almBrokenLoop.BOOLS2,416689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almBrokenLoop.AEBOOLS,416690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almBrokenLoop.INT1,416691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almBrokenLoop.INT2,416692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almBrokenLoop.AENotify,416693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almBrokenLoop.AESeverity,416694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almBrokenLoop.AEShelveDuration,416695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almOverRange.BOOLS1,416700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almOverRange.BOOLS2,416701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almOverRange.AEBOOLS,416702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almOverRange.INT1,416703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almOverRange.INT2,416704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almOverRange.AENotify,416705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almOverRange.AESeverity,416706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almOverRange.AEShelveDuration,416707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almUnderRange.BOOLS1,416712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almUnderRange.BOOLS2,416713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almUnderRange.AEBOOLS,416714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almUnderRange.INT1,416715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almUnderRange.INT2,416716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almUnderRange.AENotify,416717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almUnderRange.AESeverity,416718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almUnderRange.AEShelveDuration,416719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almRateOfChange.BOOLS1,416724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almRateOfChange.BOOLS2,416725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almRateOfChange.AEBOOLS,416726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almRateOfChange.INT1,416727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almRateOfChange.INT2,416728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almRateOfChange.AENotify,416729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almRateOfChange.AESeverity,416730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almRateOfChange.AEShelveDuration,416731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI1.almPLCFault.BOOLS1,416736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI1.almPLCFault.BOOLS2,416737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI1.almPLCFault.AEBOOLS,416738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI1.almPLCFault.INT1,416739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almPLCFault.INT2,416740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI1.almPLCFault.AENotify,416741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI1.almPLCFault.AESeverity,416742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI1.almPLCFault.AEShelveDuration,416743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almHighHigh.BOOLS1,416840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almHighHigh.BOOLS2,416841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almHighHigh.AEBOOLS,416842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almHighHigh.INT1,416843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almHighHigh.INT2,416844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almHighHigh.AENotify,416845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almHighHigh.AESeverity,416846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almHighHigh.AEShelveDuration,416847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almHigh.BOOLS1,416852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almHigh.BOOLS2,416853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almHigh.AEBOOLS,416854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almHigh.INT1,416855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almHigh.INT2,416856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almHigh.AENotify,416857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almHigh.AESeverity,416858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almHigh.AEShelveDuration,416859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almLow.BOOLS1,416864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almLow.BOOLS2,416865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almLow.AEBOOLS,416866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almLow.INT1,416867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almLow.INT2,416868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almLow.AENotify,416869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almLow.AESeverity,416870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almLow.AEShelveDuration,416871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almLowLow.BOOLS1,416876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almLowLow.BOOLS2,416877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almLowLow.AEBOOLS,416878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almLowLow.INT1,416879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almLowLow.INT2,416880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almLowLow.AENotify,416881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almLowLow.AESeverity,416882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almLowLow.AEShelveDuration,416883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almBrokenLoop.BOOLS1,416888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almBrokenLoop.BOOLS2,416889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almBrokenLoop.AEBOOLS,416890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almBrokenLoop.INT1,416891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almBrokenLoop.INT2,416892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almBrokenLoop.AENotify,416893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almBrokenLoop.AESeverity,416894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almBrokenLoop.AEShelveDuration,416895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almOverRange.BOOLS1,416900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almOverRange.BOOLS2,416901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almOverRange.AEBOOLS,416902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almOverRange.INT1,416903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almOverRange.INT2,416904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almOverRange.AENotify,416905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almOverRange.AESeverity,416906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almOverRange.AEShelveDuration,416907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almUnderRange.BOOLS1,416912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almUnderRange.BOOLS2,416913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almUnderRange.AEBOOLS,416914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almUnderRange.INT1,416915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almUnderRange.INT2,416916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almUnderRange.AENotify,416917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almUnderRange.AESeverity,416918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almUnderRange.AEShelveDuration,416919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almRateOfChange.BOOLS1,416924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almRateOfChange.BOOLS2,416925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almRateOfChange.AEBOOLS,416926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almRateOfChange.INT1,416927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almRateOfChange.INT2,416928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almRateOfChange.AENotify,416929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almRateOfChange.AESeverity,416930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almRateOfChange.AEShelveDuration,416931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI2.almPLCFault.BOOLS1,416936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI2.almPLCFault.BOOLS2,416937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI2.almPLCFault.AEBOOLS,416938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI2.almPLCFault.INT1,416939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almPLCFault.INT2,416940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI2.almPLCFault.AENotify,416941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI2.almPLCFault.AESeverity,416942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI2.almPLCFault.AEShelveDuration,416943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almHighHigh.BOOLS1,417040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almHighHigh.BOOLS2,417041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almHighHigh.AEBOOLS,417042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almHighHigh.INT1,417043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almHighHigh.INT2,417044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almHighHigh.AENotify,417045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almHighHigh.AESeverity,417046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almHighHigh.AEShelveDuration,417047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almHigh.BOOLS1,417052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almHigh.BOOLS2,417053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almHigh.AEBOOLS,417054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almHigh.INT1,417055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almHigh.INT2,417056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almHigh.AENotify,417057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almHigh.AESeverity,417058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almHigh.AEShelveDuration,417059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almLow.BOOLS1,417064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almLow.BOOLS2,417065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almLow.AEBOOLS,417066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almLow.INT1,417067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almLow.INT2,417068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almLow.AENotify,417069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almLow.AESeverity,417070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almLow.AEShelveDuration,417071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almLowLow.BOOLS1,417076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almLowLow.BOOLS2,417077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almLowLow.AEBOOLS,417078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almLowLow.INT1,417079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almLowLow.INT2,417080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almLowLow.AENotify,417081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almLowLow.AESeverity,417082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almLowLow.AEShelveDuration,417083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almBrokenLoop.BOOLS1,417088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almBrokenLoop.BOOLS2,417089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almBrokenLoop.AEBOOLS,417090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almBrokenLoop.INT1,417091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almBrokenLoop.INT2,417092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almBrokenLoop.AENotify,417093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almBrokenLoop.AESeverity,417094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almBrokenLoop.AEShelveDuration,417095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almOverRange.BOOLS1,417100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almOverRange.BOOLS2,417101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almOverRange.AEBOOLS,417102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almOverRange.INT1,417103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almOverRange.INT2,417104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almOverRange.AENotify,417105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almOverRange.AESeverity,417106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almOverRange.AEShelveDuration,417107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almUnderRange.BOOLS1,417112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almUnderRange.BOOLS2,417113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almUnderRange.AEBOOLS,417114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almUnderRange.INT1,417115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almUnderRange.INT2,417116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almUnderRange.AENotify,417117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almUnderRange.AESeverity,417118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almUnderRange.AEShelveDuration,417119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almRateOfChange.BOOLS1,417124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almRateOfChange.BOOLS2,417125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almRateOfChange.AEBOOLS,417126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almRateOfChange.INT1,417127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almRateOfChange.INT2,417128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almRateOfChange.AENotify,417129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almRateOfChange.AESeverity,417130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almRateOfChange.AEShelveDuration,417131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI3.almPLCFault.BOOLS1,417136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI3.almPLCFault.BOOLS2,417137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI3.almPLCFault.AEBOOLS,417138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI3.almPLCFault.INT1,417139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almPLCFault.INT2,417140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI3.almPLCFault.AENotify,417141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI3.almPLCFault.AESeverity,417142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI3.almPLCFault.AEShelveDuration,417143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almHighHigh.BOOLS1,417240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almHighHigh.BOOLS2,417241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almHighHigh.AEBOOLS,417242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almHighHigh.INT1,417243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almHighHigh.INT2,417244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almHighHigh.AENotify,417245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almHighHigh.AESeverity,417246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almHighHigh.AEShelveDuration,417247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almHigh.BOOLS1,417252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almHigh.BOOLS2,417253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almHigh.AEBOOLS,417254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almHigh.INT1,417255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almHigh.INT2,417256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almHigh.AENotify,417257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almHigh.AESeverity,417258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almHigh.AEShelveDuration,417259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almLow.BOOLS1,417264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almLow.BOOLS2,417265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almLow.AEBOOLS,417266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almLow.INT1,417267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almLow.INT2,417268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almLow.AENotify,417269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almLow.AESeverity,417270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almLow.AEShelveDuration,417271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almLowLow.BOOLS1,417276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almLowLow.BOOLS2,417277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almLowLow.AEBOOLS,417278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almLowLow.INT1,417279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almLowLow.INT2,417280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almLowLow.AENotify,417281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almLowLow.AESeverity,417282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almLowLow.AEShelveDuration,417283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almBrokenLoop.BOOLS1,417288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almBrokenLoop.BOOLS2,417289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almBrokenLoop.AEBOOLS,417290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almBrokenLoop.INT1,417291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almBrokenLoop.INT2,417292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almBrokenLoop.AENotify,417293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almBrokenLoop.AESeverity,417294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almBrokenLoop.AEShelveDuration,417295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almOverRange.BOOLS1,417300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almOverRange.BOOLS2,417301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almOverRange.AEBOOLS,417302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almOverRange.INT1,417303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almOverRange.INT2,417304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almOverRange.AENotify,417305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almOverRange.AESeverity,417306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almOverRange.AEShelveDuration,417307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almUnderRange.BOOLS1,417312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almUnderRange.BOOLS2,417313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almUnderRange.AEBOOLS,417314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almUnderRange.INT1,417315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almUnderRange.INT2,417316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almUnderRange.AENotify,417317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almUnderRange.AESeverity,417318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almUnderRange.AEShelveDuration,417319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almRateOfChange.BOOLS1,417324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almRateOfChange.BOOLS2,417325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almRateOfChange.AEBOOLS,417326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almRateOfChange.INT1,417327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almRateOfChange.INT2,417328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almRateOfChange.AENotify,417329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almRateOfChange.AESeverity,417330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almRateOfChange.AEShelveDuration,417331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI4.almPLCFault.BOOLS1,417336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI4.almPLCFault.BOOLS2,417337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI4.almPLCFault.AEBOOLS,417338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI4.almPLCFault.INT1,417339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almPLCFault.INT2,417340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI4.almPLCFault.AENotify,417341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI4.almPLCFault.AESeverity,417342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI4.almPLCFault.AEShelveDuration,417343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almHighHigh.BOOLS1,417440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almHighHigh.BOOLS2,417441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almHighHigh.AEBOOLS,417442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almHighHigh.INT1,417443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almHighHigh.INT2,417444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almHighHigh.AENotify,417445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almHighHigh.AESeverity,417446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almHighHigh.AEShelveDuration,417447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almHigh.BOOLS1,417452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almHigh.BOOLS2,417453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almHigh.AEBOOLS,417454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almHigh.INT1,417455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almHigh.INT2,417456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almHigh.AENotify,417457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almHigh.AESeverity,417458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almHigh.AEShelveDuration,417459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almLow.BOOLS1,417464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almLow.BOOLS2,417465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almLow.AEBOOLS,417466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almLow.INT1,417467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almLow.INT2,417468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almLow.AENotify,417469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almLow.AESeverity,417470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almLow.AEShelveDuration,417471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almLowLow.BOOLS1,417476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almLowLow.BOOLS2,417477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almLowLow.AEBOOLS,417478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almLowLow.INT1,417479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almLowLow.INT2,417480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almLowLow.AENotify,417481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almLowLow.AESeverity,417482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almLowLow.AEShelveDuration,417483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almBrokenLoop.BOOLS1,417488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almBrokenLoop.BOOLS2,417489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almBrokenLoop.AEBOOLS,417490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almBrokenLoop.INT1,417491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almBrokenLoop.INT2,417492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almBrokenLoop.AENotify,417493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almBrokenLoop.AESeverity,417494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almBrokenLoop.AEShelveDuration,417495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almOverRange.BOOLS1,417500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almOverRange.BOOLS2,417501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almOverRange.AEBOOLS,417502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almOverRange.INT1,417503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almOverRange.INT2,417504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almOverRange.AENotify,417505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almOverRange.AESeverity,417506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almOverRange.AEShelveDuration,417507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almUnderRange.BOOLS1,417512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almUnderRange.BOOLS2,417513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almUnderRange.AEBOOLS,417514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almUnderRange.INT1,417515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almUnderRange.INT2,417516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almUnderRange.AENotify,417517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almUnderRange.AESeverity,417518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almUnderRange.AEShelveDuration,417519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almRateOfChange.BOOLS1,417524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almRateOfChange.BOOLS2,417525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almRateOfChange.AEBOOLS,417526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almRateOfChange.INT1,417527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almRateOfChange.INT2,417528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almRateOfChange.AENotify,417529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almRateOfChange.AESeverity,417530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almRateOfChange.AEShelveDuration,417531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_1_VI5.almPLCFault.BOOLS1,417536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_1_VI5.almPLCFault.BOOLS2,417537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_1_VI5.almPLCFault.AEBOOLS,417538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_1_VI5.almPLCFault.INT1,417539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almPLCFault.INT2,417540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_1_VI5.almPLCFault.AENotify,417541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_1_VI5.almPLCFault.AESeverity,417542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_1_VI5.almPLCFault.AEShelveDuration,417543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almHighHigh.BOOLS1,417640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almHighHigh.BOOLS2,417641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almHighHigh.AEBOOLS,417642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almHighHigh.INT1,417643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almHighHigh.INT2,417644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almHighHigh.AENotify,417645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almHighHigh.AESeverity,417646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almHighHigh.AEShelveDuration,417647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almHigh.BOOLS1,417652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almHigh.BOOLS2,417653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almHigh.AEBOOLS,417654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almHigh.INT1,417655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almHigh.INT2,417656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almHigh.AENotify,417657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almHigh.AESeverity,417658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almHigh.AEShelveDuration,417659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almLow.BOOLS1,417664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almLow.BOOLS2,417665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almLow.AEBOOLS,417666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almLow.INT1,417667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almLow.INT2,417668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almLow.AENotify,417669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almLow.AESeverity,417670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almLow.AEShelveDuration,417671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almLowLow.BOOLS1,417676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almLowLow.BOOLS2,417677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almLowLow.AEBOOLS,417678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almLowLow.INT1,417679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almLowLow.INT2,417680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almLowLow.AENotify,417681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almLowLow.AESeverity,417682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almLowLow.AEShelveDuration,417683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almBrokenLoop.BOOLS1,417688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almBrokenLoop.BOOLS2,417689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almBrokenLoop.AEBOOLS,417690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almBrokenLoop.INT1,417691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almBrokenLoop.INT2,417692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almBrokenLoop.AENotify,417693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almBrokenLoop.AESeverity,417694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almBrokenLoop.AEShelveDuration,417695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almOverRange.BOOLS1,417700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almOverRange.BOOLS2,417701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almOverRange.AEBOOLS,417702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almOverRange.INT1,417703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almOverRange.INT2,417704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almOverRange.AENotify,417705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almOverRange.AESeverity,417706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almOverRange.AEShelveDuration,417707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almUnderRange.BOOLS1,417712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almUnderRange.BOOLS2,417713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almUnderRange.AEBOOLS,417714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almUnderRange.INT1,417715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almUnderRange.INT2,417716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almUnderRange.AENotify,417717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almUnderRange.AESeverity,417718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almUnderRange.AEShelveDuration,417719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almRateOfChange.BOOLS1,417724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almRateOfChange.BOOLS2,417725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almRateOfChange.AEBOOLS,417726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almRateOfChange.INT1,417727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almRateOfChange.INT2,417728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almRateOfChange.AENotify,417729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almRateOfChange.AESeverity,417730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almRateOfChange.AEShelveDuration,417731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI1.almPLCFault.BOOLS1,417736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI1.almPLCFault.BOOLS2,417737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI1.almPLCFault.AEBOOLS,417738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI1.almPLCFault.INT1,417739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almPLCFault.INT2,417740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI1.almPLCFault.AENotify,417741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI1.almPLCFault.AESeverity,417742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI1.almPLCFault.AEShelveDuration,417743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almHighHigh.BOOLS1,417840,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almHighHigh.BOOLS2,417841,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almHighHigh.AEBOOLS,417842,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almHighHigh.INT1,417843,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almHighHigh.INT2,417844,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almHighHigh.AENotify,417845,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almHighHigh.AESeverity,417846,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almHighHigh.AEShelveDuration,417847,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almHigh.BOOLS1,417852,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almHigh.BOOLS2,417853,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almHigh.AEBOOLS,417854,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almHigh.INT1,417855,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almHigh.INT2,417856,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almHigh.AENotify,417857,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almHigh.AESeverity,417858,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almHigh.AEShelveDuration,417859,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almLow.BOOLS1,417864,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almLow.BOOLS2,417865,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almLow.AEBOOLS,417866,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almLow.INT1,417867,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almLow.INT2,417868,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almLow.AENotify,417869,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almLow.AESeverity,417870,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almLow.AEShelveDuration,417871,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almLowLow.BOOLS1,417876,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almLowLow.BOOLS2,417877,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almLowLow.AEBOOLS,417878,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almLowLow.INT1,417879,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almLowLow.INT2,417880,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almLowLow.AENotify,417881,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almLowLow.AESeverity,417882,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almLowLow.AEShelveDuration,417883,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almBrokenLoop.BOOLS1,417888,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almBrokenLoop.BOOLS2,417889,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almBrokenLoop.AEBOOLS,417890,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almBrokenLoop.INT1,417891,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almBrokenLoop.INT2,417892,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almBrokenLoop.AENotify,417893,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almBrokenLoop.AESeverity,417894,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almBrokenLoop.AEShelveDuration,417895,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almOverRange.BOOLS1,417900,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almOverRange.BOOLS2,417901,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almOverRange.AEBOOLS,417902,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almOverRange.INT1,417903,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almOverRange.INT2,417904,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almOverRange.AENotify,417905,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almOverRange.AESeverity,417906,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almOverRange.AEShelveDuration,417907,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almUnderRange.BOOLS1,417912,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almUnderRange.BOOLS2,417913,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almUnderRange.AEBOOLS,417914,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almUnderRange.INT1,417915,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almUnderRange.INT2,417916,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almUnderRange.AENotify,417917,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almUnderRange.AESeverity,417918,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almUnderRange.AEShelveDuration,417919,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almRateOfChange.BOOLS1,417924,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almRateOfChange.BOOLS2,417925,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almRateOfChange.AEBOOLS,417926,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almRateOfChange.INT1,417927,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almRateOfChange.INT2,417928,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almRateOfChange.AENotify,417929,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almRateOfChange.AESeverity,417930,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almRateOfChange.AEShelveDuration,417931,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI2.almPLCFault.BOOLS1,417936,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI2.almPLCFault.BOOLS2,417937,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI2.almPLCFault.AEBOOLS,417938,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI2.almPLCFault.INT1,417939,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almPLCFault.INT2,417940,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI2.almPLCFault.AENotify,417941,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI2.almPLCFault.AESeverity,417942,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI2.almPLCFault.AEShelveDuration,417943,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almHighHigh.BOOLS1,418040,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almHighHigh.BOOLS2,418041,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almHighHigh.AEBOOLS,418042,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almHighHigh.INT1,418043,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almHighHigh.INT2,418044,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almHighHigh.AENotify,418045,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almHighHigh.AESeverity,418046,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almHighHigh.AEShelveDuration,418047,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almHigh.BOOLS1,418052,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almHigh.BOOLS2,418053,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almHigh.AEBOOLS,418054,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almHigh.INT1,418055,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almHigh.INT2,418056,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almHigh.AENotify,418057,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almHigh.AESeverity,418058,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almHigh.AEShelveDuration,418059,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almLow.BOOLS1,418064,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almLow.BOOLS2,418065,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almLow.AEBOOLS,418066,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almLow.INT1,418067,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almLow.INT2,418068,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almLow.AENotify,418069,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almLow.AESeverity,418070,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almLow.AEShelveDuration,418071,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almLowLow.BOOLS1,418076,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almLowLow.BOOLS2,418077,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almLowLow.AEBOOLS,418078,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almLowLow.INT1,418079,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almLowLow.INT2,418080,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almLowLow.AENotify,418081,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almLowLow.AESeverity,418082,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almLowLow.AEShelveDuration,418083,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almBrokenLoop.BOOLS1,418088,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almBrokenLoop.BOOLS2,418089,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almBrokenLoop.AEBOOLS,418090,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almBrokenLoop.INT1,418091,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almBrokenLoop.INT2,418092,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almBrokenLoop.AENotify,418093,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almBrokenLoop.AESeverity,418094,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almBrokenLoop.AEShelveDuration,418095,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almOverRange.BOOLS1,418100,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almOverRange.BOOLS2,418101,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almOverRange.AEBOOLS,418102,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almOverRange.INT1,418103,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almOverRange.INT2,418104,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almOverRange.AENotify,418105,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almOverRange.AESeverity,418106,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almOverRange.AEShelveDuration,418107,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almUnderRange.BOOLS1,418112,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almUnderRange.BOOLS2,418113,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almUnderRange.AEBOOLS,418114,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almUnderRange.INT1,418115,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almUnderRange.INT2,418116,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almUnderRange.AENotify,418117,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almUnderRange.AESeverity,418118,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almUnderRange.AEShelveDuration,418119,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almRateOfChange.BOOLS1,418124,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almRateOfChange.BOOLS2,418125,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almRateOfChange.AEBOOLS,418126,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almRateOfChange.INT1,418127,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almRateOfChange.INT2,418128,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almRateOfChange.AENotify,418129,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almRateOfChange.AESeverity,418130,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almRateOfChange.AEShelveDuration,418131,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI3.almPLCFault.BOOLS1,418136,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI3.almPLCFault.BOOLS2,418137,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI3.almPLCFault.AEBOOLS,418138,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI3.almPLCFault.INT1,418139,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almPLCFault.INT2,418140,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI3.almPLCFault.AENotify,418141,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI3.almPLCFault.AESeverity,418142,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI3.almPLCFault.AEShelveDuration,418143,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almHighHigh.BOOLS1,418240,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almHighHigh.BOOLS2,418241,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almHighHigh.AEBOOLS,418242,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almHighHigh.INT1,418243,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almHighHigh.INT2,418244,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almHighHigh.AENotify,418245,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almHighHigh.AESeverity,418246,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almHighHigh.AEShelveDuration,418247,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almHigh.BOOLS1,418252,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almHigh.BOOLS2,418253,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almHigh.AEBOOLS,418254,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almHigh.INT1,418255,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almHigh.INT2,418256,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almHigh.AENotify,418257,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almHigh.AESeverity,418258,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almHigh.AEShelveDuration,418259,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almLow.BOOLS1,418264,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almLow.BOOLS2,418265,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almLow.AEBOOLS,418266,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almLow.INT1,418267,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almLow.INT2,418268,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almLow.AENotify,418269,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almLow.AESeverity,418270,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almLow.AEShelveDuration,418271,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almLowLow.BOOLS1,418276,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almLowLow.BOOLS2,418277,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almLowLow.AEBOOLS,418278,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almLowLow.INT1,418279,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almLowLow.INT2,418280,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almLowLow.AENotify,418281,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almLowLow.AESeverity,418282,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almLowLow.AEShelveDuration,418283,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almBrokenLoop.BOOLS1,418288,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almBrokenLoop.BOOLS2,418289,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almBrokenLoop.AEBOOLS,418290,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almBrokenLoop.INT1,418291,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almBrokenLoop.INT2,418292,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almBrokenLoop.AENotify,418293,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almBrokenLoop.AESeverity,418294,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almBrokenLoop.AEShelveDuration,418295,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almOverRange.BOOLS1,418300,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almOverRange.BOOLS2,418301,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almOverRange.AEBOOLS,418302,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almOverRange.INT1,418303,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almOverRange.INT2,418304,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almOverRange.AENotify,418305,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almOverRange.AESeverity,418306,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almOverRange.AEShelveDuration,418307,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almUnderRange.BOOLS1,418312,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almUnderRange.BOOLS2,418313,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almUnderRange.AEBOOLS,418314,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almUnderRange.INT1,418315,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almUnderRange.INT2,418316,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almUnderRange.AENotify,418317,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almUnderRange.AESeverity,418318,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almUnderRange.AEShelveDuration,418319,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almRateOfChange.BOOLS1,418324,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almRateOfChange.BOOLS2,418325,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almRateOfChange.AEBOOLS,418326,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almRateOfChange.INT1,418327,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almRateOfChange.INT2,418328,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almRateOfChange.AENotify,418329,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almRateOfChange.AESeverity,418330,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almRateOfChange.AEShelveDuration,418331,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI4.almPLCFault.BOOLS1,418336,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI4.almPLCFault.BOOLS2,418337,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI4.almPLCFault.AEBOOLS,418338,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI4.almPLCFault.INT1,418339,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almPLCFault.INT2,418340,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI4.almPLCFault.AENotify,418341,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI4.almPLCFault.AESeverity,418342,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI4.almPLCFault.AEShelveDuration,418343,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almHighHigh.BOOLS1,418440,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almHighHigh.BOOLS2,418441,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almHighHigh.AEBOOLS,418442,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almHighHigh.INT1,418443,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almHighHigh.INT2,418444,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almHighHigh.AENotify,418445,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almHighHigh.AESeverity,418446,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almHighHigh.AEShelveDuration,418447,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almHigh.BOOLS1,418452,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almHigh.BOOLS2,418453,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almHigh.AEBOOLS,418454,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almHigh.INT1,418455,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almHigh.INT2,418456,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almHigh.AENotify,418457,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almHigh.AESeverity,418458,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almHigh.AEShelveDuration,418459,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almLow.BOOLS1,418464,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almLow.BOOLS2,418465,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almLow.AEBOOLS,418466,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almLow.INT1,418467,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almLow.INT2,418468,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almLow.AENotify,418469,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almLow.AESeverity,418470,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almLow.AEShelveDuration,418471,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almLowLow.BOOLS1,418476,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almLowLow.BOOLS2,418477,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almLowLow.AEBOOLS,418478,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almLowLow.INT1,418479,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almLowLow.INT2,418480,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almLowLow.AENotify,418481,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almLowLow.AESeverity,418482,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almLowLow.AEShelveDuration,418483,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almBrokenLoop.BOOLS1,418488,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almBrokenLoop.BOOLS2,418489,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almBrokenLoop.AEBOOLS,418490,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almBrokenLoop.INT1,418491,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almBrokenLoop.INT2,418492,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almBrokenLoop.AENotify,418493,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almBrokenLoop.AESeverity,418494,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almBrokenLoop.AEShelveDuration,418495,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almOverRange.BOOLS1,418500,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almOverRange.BOOLS2,418501,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almOverRange.AEBOOLS,418502,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almOverRange.INT1,418503,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almOverRange.INT2,418504,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almOverRange.AENotify,418505,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almOverRange.AESeverity,418506,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almOverRange.AEShelveDuration,418507,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almUnderRange.BOOLS1,418512,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almUnderRange.BOOLS2,418513,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almUnderRange.AEBOOLS,418514,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almUnderRange.INT1,418515,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almUnderRange.INT2,418516,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almUnderRange.AENotify,418517,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almUnderRange.AESeverity,418518,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almUnderRange.AEShelveDuration,418519,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almRateOfChange.BOOLS1,418524,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almRateOfChange.BOOLS2,418525,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almRateOfChange.AEBOOLS,418526,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almRateOfChange.INT1,418527,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almRateOfChange.INT2,418528,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almRateOfChange.AENotify,418529,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almRateOfChange.AESeverity,418530,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almRateOfChange.AEShelveDuration,418531,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_2_VI5.almPLCFault.BOOLS1,418536,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_2_VI5.almPLCFault.BOOLS2,418537,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_2_VI5.almPLCFault.AEBOOLS,418538,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_2_VI5.almPLCFault.INT1,418539,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almPLCFault.INT2,418540,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_2_VI5.almPLCFault.AENotify,418541,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_2_VI5.almPLCFault.AESeverity,418542,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_2_VI5.almPLCFault.AEShelveDuration,418543,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almHighHigh.BOOLS1,418640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almHighHigh.BOOLS2,418641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almHighHigh.AEBOOLS,418642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almHighHigh.INT1,418643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almHighHigh.INT2,418644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almHighHigh.AENotify,418645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almHighHigh.AESeverity,418646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almHighHigh.AEShelveDuration,418647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almHigh.BOOLS1,418652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almHigh.BOOLS2,418653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almHigh.AEBOOLS,418654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almHigh.INT1,418655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almHigh.INT2,418656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almHigh.AENotify,418657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almHigh.AESeverity,418658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almHigh.AEShelveDuration,418659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almLow.BOOLS1,418664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almLow.BOOLS2,418665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almLow.AEBOOLS,418666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almLow.INT1,418667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almLow.INT2,418668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almLow.AENotify,418669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almLow.AESeverity,418670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almLow.AEShelveDuration,418671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almLowLow.BOOLS1,418676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almLowLow.BOOLS2,418677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almLowLow.AEBOOLS,418678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almLowLow.INT1,418679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almLowLow.INT2,418680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almLowLow.AENotify,418681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almLowLow.AESeverity,418682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almLowLow.AEShelveDuration,418683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almBrokenLoop.BOOLS1,418688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almBrokenLoop.BOOLS2,418689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almBrokenLoop.AEBOOLS,418690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almBrokenLoop.INT1,418691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almBrokenLoop.INT2,418692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almBrokenLoop.AENotify,418693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almBrokenLoop.AESeverity,418694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almBrokenLoop.AEShelveDuration,418695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almOverRange.BOOLS1,418700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almOverRange.BOOLS2,418701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almOverRange.AEBOOLS,418702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almOverRange.INT1,418703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almOverRange.INT2,418704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almOverRange.AENotify,418705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almOverRange.AESeverity,418706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almOverRange.AEShelveDuration,418707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almUnderRange.BOOLS1,418712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almUnderRange.BOOLS2,418713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almUnderRange.AEBOOLS,418714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almUnderRange.INT1,418715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almUnderRange.INT2,418716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almUnderRange.AENotify,418717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almUnderRange.AESeverity,418718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almUnderRange.AEShelveDuration,418719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almRateOfChange.BOOLS1,418724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almRateOfChange.BOOLS2,418725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almRateOfChange.AEBOOLS,418726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almRateOfChange.INT1,418727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almRateOfChange.INT2,418728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almRateOfChange.AENotify,418729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almRateOfChange.AESeverity,418730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almRateOfChange.AEShelveDuration,418731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI1.almPLCFault.BOOLS1,418736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI1.almPLCFault.BOOLS2,418737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI1.almPLCFault.AEBOOLS,418738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI1.almPLCFault.INT1,418739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almPLCFault.INT2,418740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI1.almPLCFault.AENotify,418741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI1.almPLCFault.AESeverity,418742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI1.almPLCFault.AEShelveDuration,418743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almHighHigh.BOOLS1,418840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almHighHigh.BOOLS2,418841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almHighHigh.AEBOOLS,418842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almHighHigh.INT1,418843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almHighHigh.INT2,418844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almHighHigh.AENotify,418845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almHighHigh.AESeverity,418846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almHighHigh.AEShelveDuration,418847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almHigh.BOOLS1,418852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almHigh.BOOLS2,418853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almHigh.AEBOOLS,418854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almHigh.INT1,418855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almHigh.INT2,418856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almHigh.AENotify,418857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almHigh.AESeverity,418858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almHigh.AEShelveDuration,418859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almLow.BOOLS1,418864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almLow.BOOLS2,418865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almLow.AEBOOLS,418866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almLow.INT1,418867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almLow.INT2,418868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almLow.AENotify,418869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almLow.AESeverity,418870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almLow.AEShelveDuration,418871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almLowLow.BOOLS1,418876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almLowLow.BOOLS2,418877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almLowLow.AEBOOLS,418878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almLowLow.INT1,418879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almLowLow.INT2,418880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almLowLow.AENotify,418881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almLowLow.AESeverity,418882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almLowLow.AEShelveDuration,418883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almBrokenLoop.BOOLS1,418888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almBrokenLoop.BOOLS2,418889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almBrokenLoop.AEBOOLS,418890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almBrokenLoop.INT1,418891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almBrokenLoop.INT2,418892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almBrokenLoop.AENotify,418893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almBrokenLoop.AESeverity,418894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almBrokenLoop.AEShelveDuration,418895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almOverRange.BOOLS1,418900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almOverRange.BOOLS2,418901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almOverRange.AEBOOLS,418902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almOverRange.INT1,418903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almOverRange.INT2,418904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almOverRange.AENotify,418905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almOverRange.AESeverity,418906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almOverRange.AEShelveDuration,418907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almUnderRange.BOOLS1,418912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almUnderRange.BOOLS2,418913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almUnderRange.AEBOOLS,418914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almUnderRange.INT1,418915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almUnderRange.INT2,418916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almUnderRange.AENotify,418917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almUnderRange.AESeverity,418918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almUnderRange.AEShelveDuration,418919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almRateOfChange.BOOLS1,418924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almRateOfChange.BOOLS2,418925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almRateOfChange.AEBOOLS,418926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almRateOfChange.INT1,418927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almRateOfChange.INT2,418928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almRateOfChange.AENotify,418929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almRateOfChange.AESeverity,418930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almRateOfChange.AEShelveDuration,418931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI2.almPLCFault.BOOLS1,418936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI2.almPLCFault.BOOLS2,418937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI2.almPLCFault.AEBOOLS,418938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI2.almPLCFault.INT1,418939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almPLCFault.INT2,418940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI2.almPLCFault.AENotify,418941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI2.almPLCFault.AESeverity,418942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI2.almPLCFault.AEShelveDuration,418943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almHighHigh.BOOLS1,419040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almHighHigh.BOOLS2,419041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almHighHigh.AEBOOLS,419042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almHighHigh.INT1,419043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almHighHigh.INT2,419044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almHighHigh.AENotify,419045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almHighHigh.AESeverity,419046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almHighHigh.AEShelveDuration,419047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almHigh.BOOLS1,419052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almHigh.BOOLS2,419053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almHigh.AEBOOLS,419054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almHigh.INT1,419055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almHigh.INT2,419056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almHigh.AENotify,419057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almHigh.AESeverity,419058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almHigh.AEShelveDuration,419059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almLow.BOOLS1,419064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almLow.BOOLS2,419065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almLow.AEBOOLS,419066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almLow.INT1,419067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almLow.INT2,419068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almLow.AENotify,419069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almLow.AESeverity,419070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almLow.AEShelveDuration,419071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almLowLow.BOOLS1,419076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almLowLow.BOOLS2,419077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almLowLow.AEBOOLS,419078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almLowLow.INT1,419079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almLowLow.INT2,419080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almLowLow.AENotify,419081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almLowLow.AESeverity,419082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almLowLow.AEShelveDuration,419083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almBrokenLoop.BOOLS1,419088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almBrokenLoop.BOOLS2,419089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almBrokenLoop.AEBOOLS,419090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almBrokenLoop.INT1,419091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almBrokenLoop.INT2,419092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almBrokenLoop.AENotify,419093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almBrokenLoop.AESeverity,419094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almBrokenLoop.AEShelveDuration,419095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almOverRange.BOOLS1,419100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almOverRange.BOOLS2,419101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almOverRange.AEBOOLS,419102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almOverRange.INT1,419103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almOverRange.INT2,419104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almOverRange.AENotify,419105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almOverRange.AESeverity,419106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almOverRange.AEShelveDuration,419107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almUnderRange.BOOLS1,419112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almUnderRange.BOOLS2,419113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almUnderRange.AEBOOLS,419114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almUnderRange.INT1,419115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almUnderRange.INT2,419116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almUnderRange.AENotify,419117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almUnderRange.AESeverity,419118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almUnderRange.AEShelveDuration,419119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almRateOfChange.BOOLS1,419124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almRateOfChange.BOOLS2,419125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almRateOfChange.AEBOOLS,419126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almRateOfChange.INT1,419127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almRateOfChange.INT2,419128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almRateOfChange.AENotify,419129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almRateOfChange.AESeverity,419130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almRateOfChange.AEShelveDuration,419131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI3.almPLCFault.BOOLS1,419136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI3.almPLCFault.BOOLS2,419137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI3.almPLCFault.AEBOOLS,419138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI3.almPLCFault.INT1,419139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almPLCFault.INT2,419140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI3.almPLCFault.AENotify,419141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI3.almPLCFault.AESeverity,419142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI3.almPLCFault.AEShelveDuration,419143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almHighHigh.BOOLS1,419240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almHighHigh.BOOLS2,419241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almHighHigh.AEBOOLS,419242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almHighHigh.INT1,419243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almHighHigh.INT2,419244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almHighHigh.AENotify,419245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almHighHigh.AESeverity,419246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almHighHigh.AEShelveDuration,419247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almHigh.BOOLS1,419252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almHigh.BOOLS2,419253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almHigh.AEBOOLS,419254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almHigh.INT1,419255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almHigh.INT2,419256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almHigh.AENotify,419257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almHigh.AESeverity,419258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almHigh.AEShelveDuration,419259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almLow.BOOLS1,419264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almLow.BOOLS2,419265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almLow.AEBOOLS,419266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almLow.INT1,419267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almLow.INT2,419268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almLow.AENotify,419269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almLow.AESeverity,419270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almLow.AEShelveDuration,419271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almLowLow.BOOLS1,419276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almLowLow.BOOLS2,419277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almLowLow.AEBOOLS,419278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almLowLow.INT1,419279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almLowLow.INT2,419280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almLowLow.AENotify,419281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almLowLow.AESeverity,419282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almLowLow.AEShelveDuration,419283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almBrokenLoop.BOOLS1,419288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almBrokenLoop.BOOLS2,419289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almBrokenLoop.AEBOOLS,419290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almBrokenLoop.INT1,419291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almBrokenLoop.INT2,419292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almBrokenLoop.AENotify,419293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almBrokenLoop.AESeverity,419294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almBrokenLoop.AEShelveDuration,419295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almOverRange.BOOLS1,419300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almOverRange.BOOLS2,419301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almOverRange.AEBOOLS,419302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almOverRange.INT1,419303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almOverRange.INT2,419304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almOverRange.AENotify,419305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almOverRange.AESeverity,419306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almOverRange.AEShelveDuration,419307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almUnderRange.BOOLS1,419312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almUnderRange.BOOLS2,419313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almUnderRange.AEBOOLS,419314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almUnderRange.INT1,419315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almUnderRange.INT2,419316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almUnderRange.AENotify,419317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almUnderRange.AESeverity,419318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almUnderRange.AEShelveDuration,419319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almRateOfChange.BOOLS1,419324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almRateOfChange.BOOLS2,419325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almRateOfChange.AEBOOLS,419326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almRateOfChange.INT1,419327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almRateOfChange.INT2,419328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almRateOfChange.AENotify,419329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almRateOfChange.AESeverity,419330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almRateOfChange.AEShelveDuration,419331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI4.almPLCFault.BOOLS1,419336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI4.almPLCFault.BOOLS2,419337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI4.almPLCFault.AEBOOLS,419338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI4.almPLCFault.INT1,419339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almPLCFault.INT2,419340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI4.almPLCFault.AENotify,419341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI4.almPLCFault.AESeverity,419342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI4.almPLCFault.AEShelveDuration,419343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almHighHigh.BOOLS1,419440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almHighHigh.BOOLS2,419441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almHighHigh.AEBOOLS,419442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almHighHigh.INT1,419443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almHighHigh.INT2,419444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almHighHigh.AENotify,419445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almHighHigh.AESeverity,419446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almHighHigh.AEShelveDuration,419447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almHigh.BOOLS1,419452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almHigh.BOOLS2,419453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almHigh.AEBOOLS,419454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almHigh.INT1,419455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almHigh.INT2,419456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almHigh.AENotify,419457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almHigh.AESeverity,419458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almHigh.AEShelveDuration,419459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almLow.BOOLS1,419464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almLow.BOOLS2,419465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almLow.AEBOOLS,419466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almLow.INT1,419467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almLow.INT2,419468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almLow.AENotify,419469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almLow.AESeverity,419470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almLow.AEShelveDuration,419471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almLowLow.BOOLS1,419476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almLowLow.BOOLS2,419477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almLowLow.AEBOOLS,419478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almLowLow.INT1,419479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almLowLow.INT2,419480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almLowLow.AENotify,419481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almLowLow.AESeverity,419482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almLowLow.AEShelveDuration,419483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almBrokenLoop.BOOLS1,419488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almBrokenLoop.BOOLS2,419489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almBrokenLoop.AEBOOLS,419490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almBrokenLoop.INT1,419491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almBrokenLoop.INT2,419492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almBrokenLoop.AENotify,419493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almBrokenLoop.AESeverity,419494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almBrokenLoop.AEShelveDuration,419495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almOverRange.BOOLS1,419500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almOverRange.BOOLS2,419501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almOverRange.AEBOOLS,419502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almOverRange.INT1,419503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almOverRange.INT2,419504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almOverRange.AENotify,419505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almOverRange.AESeverity,419506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almOverRange.AEShelveDuration,419507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almUnderRange.BOOLS1,419512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almUnderRange.BOOLS2,419513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almUnderRange.AEBOOLS,419514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almUnderRange.INT1,419515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almUnderRange.INT2,419516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almUnderRange.AENotify,419517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almUnderRange.AESeverity,419518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almUnderRange.AEShelveDuration,419519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almRateOfChange.BOOLS1,419524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almRateOfChange.BOOLS2,419525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almRateOfChange.AEBOOLS,419526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almRateOfChange.INT1,419527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almRateOfChange.INT2,419528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almRateOfChange.AENotify,419529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almRateOfChange.AESeverity,419530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almRateOfChange.AEShelveDuration,419531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_3_VI5.almPLCFault.BOOLS1,419536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_3_VI5.almPLCFault.BOOLS2,419537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_3_VI5.almPLCFault.AEBOOLS,419538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_3_VI5.almPLCFault.INT1,419539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almPLCFault.INT2,419540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_3_VI5.almPLCFault.AENotify,419541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_3_VI5.almPLCFault.AESeverity,419542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_3_VI5.almPLCFault.AEShelveDuration,419543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almHighHigh.BOOLS1,419640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almHighHigh.BOOLS2,419641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almHighHigh.AEBOOLS,419642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almHighHigh.INT1,419643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almHighHigh.INT2,419644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almHighHigh.AENotify,419645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almHighHigh.AESeverity,419646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almHighHigh.AEShelveDuration,419647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almHigh.BOOLS1,419652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almHigh.BOOLS2,419653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almHigh.AEBOOLS,419654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almHigh.INT1,419655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almHigh.INT2,419656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almHigh.AENotify,419657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almHigh.AESeverity,419658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almHigh.AEShelveDuration,419659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almLow.BOOLS1,419664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almLow.BOOLS2,419665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almLow.AEBOOLS,419666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almLow.INT1,419667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almLow.INT2,419668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almLow.AENotify,419669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almLow.AESeverity,419670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almLow.AEShelveDuration,419671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almLowLow.BOOLS1,419676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almLowLow.BOOLS2,419677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almLowLow.AEBOOLS,419678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almLowLow.INT1,419679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almLowLow.INT2,419680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almLowLow.AENotify,419681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almLowLow.AESeverity,419682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almLowLow.AEShelveDuration,419683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almBrokenLoop.BOOLS1,419688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almBrokenLoop.BOOLS2,419689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almBrokenLoop.AEBOOLS,419690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almBrokenLoop.INT1,419691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almBrokenLoop.INT2,419692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almBrokenLoop.AENotify,419693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almBrokenLoop.AESeverity,419694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almBrokenLoop.AEShelveDuration,419695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almOverRange.BOOLS1,419700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almOverRange.BOOLS2,419701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almOverRange.AEBOOLS,419702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almOverRange.INT1,419703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almOverRange.INT2,419704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almOverRange.AENotify,419705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almOverRange.AESeverity,419706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almOverRange.AEShelveDuration,419707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almUnderRange.BOOLS1,419712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almUnderRange.BOOLS2,419713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almUnderRange.AEBOOLS,419714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almUnderRange.INT1,419715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almUnderRange.INT2,419716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almUnderRange.AENotify,419717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almUnderRange.AESeverity,419718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almUnderRange.AEShelveDuration,419719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almRateOfChange.BOOLS1,419724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almRateOfChange.BOOLS2,419725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almRateOfChange.AEBOOLS,419726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almRateOfChange.INT1,419727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almRateOfChange.INT2,419728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almRateOfChange.AENotify,419729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almRateOfChange.AESeverity,419730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almRateOfChange.AEShelveDuration,419731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI1.almPLCFault.BOOLS1,419736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI1.almPLCFault.BOOLS2,419737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI1.almPLCFault.AEBOOLS,419738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI1.almPLCFault.INT1,419739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almPLCFault.INT2,419740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI1.almPLCFault.AENotify,419741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI1.almPLCFault.AESeverity,419742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI1.almPLCFault.AEShelveDuration,419743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almHighHigh.BOOLS1,419840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almHighHigh.BOOLS2,419841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almHighHigh.AEBOOLS,419842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almHighHigh.INT1,419843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almHighHigh.INT2,419844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almHighHigh.AENotify,419845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almHighHigh.AESeverity,419846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almHighHigh.AEShelveDuration,419847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almHigh.BOOLS1,419852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almHigh.BOOLS2,419853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almHigh.AEBOOLS,419854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almHigh.INT1,419855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almHigh.INT2,419856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almHigh.AENotify,419857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almHigh.AESeverity,419858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almHigh.AEShelveDuration,419859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almLow.BOOLS1,419864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almLow.BOOLS2,419865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almLow.AEBOOLS,419866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almLow.INT1,419867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almLow.INT2,419868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almLow.AENotify,419869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almLow.AESeverity,419870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almLow.AEShelveDuration,419871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almLowLow.BOOLS1,419876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almLowLow.BOOLS2,419877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almLowLow.AEBOOLS,419878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almLowLow.INT1,419879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almLowLow.INT2,419880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almLowLow.AENotify,419881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almLowLow.AESeverity,419882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almLowLow.AEShelveDuration,419883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almBrokenLoop.BOOLS1,419888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almBrokenLoop.BOOLS2,419889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almBrokenLoop.AEBOOLS,419890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almBrokenLoop.INT1,419891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almBrokenLoop.INT2,419892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almBrokenLoop.AENotify,419893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almBrokenLoop.AESeverity,419894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almBrokenLoop.AEShelveDuration,419895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almOverRange.BOOLS1,419900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almOverRange.BOOLS2,419901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almOverRange.AEBOOLS,419902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almOverRange.INT1,419903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almOverRange.INT2,419904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almOverRange.AENotify,419905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almOverRange.AESeverity,419906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almOverRange.AEShelveDuration,419907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almUnderRange.BOOLS1,419912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almUnderRange.BOOLS2,419913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almUnderRange.AEBOOLS,419914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almUnderRange.INT1,419915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almUnderRange.INT2,419916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almUnderRange.AENotify,419917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almUnderRange.AESeverity,419918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almUnderRange.AEShelveDuration,419919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almRateOfChange.BOOLS1,419924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almRateOfChange.BOOLS2,419925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almRateOfChange.AEBOOLS,419926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almRateOfChange.INT1,419927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almRateOfChange.INT2,419928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almRateOfChange.AENotify,419929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almRateOfChange.AESeverity,419930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almRateOfChange.AEShelveDuration,419931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI2.almPLCFault.BOOLS1,419936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI2.almPLCFault.BOOLS2,419937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI2.almPLCFault.AEBOOLS,419938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI2.almPLCFault.INT1,419939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almPLCFault.INT2,419940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI2.almPLCFault.AENotify,419941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI2.almPLCFault.AESeverity,419942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI2.almPLCFault.AEShelveDuration,419943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almHighHigh.BOOLS1,420040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almHighHigh.BOOLS2,420041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almHighHigh.AEBOOLS,420042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almHighHigh.INT1,420043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almHighHigh.INT2,420044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almHighHigh.AENotify,420045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almHighHigh.AESeverity,420046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almHighHigh.AEShelveDuration,420047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almHigh.BOOLS1,420052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almHigh.BOOLS2,420053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almHigh.AEBOOLS,420054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almHigh.INT1,420055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almHigh.INT2,420056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almHigh.AENotify,420057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almHigh.AESeverity,420058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almHigh.AEShelveDuration,420059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almLow.BOOLS1,420064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almLow.BOOLS2,420065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almLow.AEBOOLS,420066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almLow.INT1,420067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almLow.INT2,420068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almLow.AENotify,420069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almLow.AESeverity,420070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almLow.AEShelveDuration,420071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almLowLow.BOOLS1,420076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almLowLow.BOOLS2,420077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almLowLow.AEBOOLS,420078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almLowLow.INT1,420079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almLowLow.INT2,420080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almLowLow.AENotify,420081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almLowLow.AESeverity,420082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almLowLow.AEShelveDuration,420083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almBrokenLoop.BOOLS1,420088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almBrokenLoop.BOOLS2,420089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almBrokenLoop.AEBOOLS,420090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almBrokenLoop.INT1,420091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almBrokenLoop.INT2,420092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almBrokenLoop.AENotify,420093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almBrokenLoop.AESeverity,420094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almBrokenLoop.AEShelveDuration,420095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almOverRange.BOOLS1,420100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almOverRange.BOOLS2,420101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almOverRange.AEBOOLS,420102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almOverRange.INT1,420103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almOverRange.INT2,420104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almOverRange.AENotify,420105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almOverRange.AESeverity,420106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almOverRange.AEShelveDuration,420107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almUnderRange.BOOLS1,420112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almUnderRange.BOOLS2,420113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almUnderRange.AEBOOLS,420114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almUnderRange.INT1,420115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almUnderRange.INT2,420116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almUnderRange.AENotify,420117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almUnderRange.AESeverity,420118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almUnderRange.AEShelveDuration,420119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almRateOfChange.BOOLS1,420124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almRateOfChange.BOOLS2,420125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almRateOfChange.AEBOOLS,420126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almRateOfChange.INT1,420127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almRateOfChange.INT2,420128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almRateOfChange.AENotify,420129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almRateOfChange.AESeverity,420130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almRateOfChange.AEShelveDuration,420131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI3.almPLCFault.BOOLS1,420136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI3.almPLCFault.BOOLS2,420137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI3.almPLCFault.AEBOOLS,420138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI3.almPLCFault.INT1,420139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almPLCFault.INT2,420140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI3.almPLCFault.AENotify,420141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI3.almPLCFault.AESeverity,420142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI3.almPLCFault.AEShelveDuration,420143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almHighHigh.BOOLS1,420240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almHighHigh.BOOLS2,420241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almHighHigh.AEBOOLS,420242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almHighHigh.INT1,420243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almHighHigh.INT2,420244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almHighHigh.AENotify,420245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almHighHigh.AESeverity,420246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almHighHigh.AEShelveDuration,420247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almHigh.BOOLS1,420252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almHigh.BOOLS2,420253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almHigh.AEBOOLS,420254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almHigh.INT1,420255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almHigh.INT2,420256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almHigh.AENotify,420257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almHigh.AESeverity,420258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almHigh.AEShelveDuration,420259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almLow.BOOLS1,420264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almLow.BOOLS2,420265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almLow.AEBOOLS,420266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almLow.INT1,420267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almLow.INT2,420268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almLow.AENotify,420269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almLow.AESeverity,420270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almLow.AEShelveDuration,420271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almLowLow.BOOLS1,420276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almLowLow.BOOLS2,420277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almLowLow.AEBOOLS,420278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almLowLow.INT1,420279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almLowLow.INT2,420280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almLowLow.AENotify,420281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almLowLow.AESeverity,420282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almLowLow.AEShelveDuration,420283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almBrokenLoop.BOOLS1,420288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almBrokenLoop.BOOLS2,420289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almBrokenLoop.AEBOOLS,420290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almBrokenLoop.INT1,420291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almBrokenLoop.INT2,420292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almBrokenLoop.AENotify,420293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almBrokenLoop.AESeverity,420294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almBrokenLoop.AEShelveDuration,420295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almOverRange.BOOLS1,420300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almOverRange.BOOLS2,420301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almOverRange.AEBOOLS,420302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almOverRange.INT1,420303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almOverRange.INT2,420304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almOverRange.AENotify,420305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almOverRange.AESeverity,420306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almOverRange.AEShelveDuration,420307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almUnderRange.BOOLS1,420312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almUnderRange.BOOLS2,420313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almUnderRange.AEBOOLS,420314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almUnderRange.INT1,420315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almUnderRange.INT2,420316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almUnderRange.AENotify,420317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almUnderRange.AESeverity,420318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almUnderRange.AEShelveDuration,420319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almRateOfChange.BOOLS1,420324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almRateOfChange.BOOLS2,420325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almRateOfChange.AEBOOLS,420326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almRateOfChange.INT1,420327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almRateOfChange.INT2,420328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almRateOfChange.AENotify,420329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almRateOfChange.AESeverity,420330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almRateOfChange.AEShelveDuration,420331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI4.almPLCFault.BOOLS1,420336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI4.almPLCFault.BOOLS2,420337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI4.almPLCFault.AEBOOLS,420338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI4.almPLCFault.INT1,420339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almPLCFault.INT2,420340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI4.almPLCFault.AENotify,420341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI4.almPLCFault.AESeverity,420342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI4.almPLCFault.AEShelveDuration,420343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almHighHigh.BOOLS1,420440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almHighHigh.BOOLS2,420441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almHighHigh.AEBOOLS,420442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almHighHigh.INT1,420443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almHighHigh.INT2,420444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almHighHigh.AENotify,420445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almHighHigh.AESeverity,420446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almHighHigh.AEShelveDuration,420447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almHigh.BOOLS1,420452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almHigh.BOOLS2,420453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almHigh.AEBOOLS,420454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almHigh.INT1,420455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almHigh.INT2,420456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almHigh.AENotify,420457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almHigh.AESeverity,420458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almHigh.AEShelveDuration,420459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almLow.BOOLS1,420464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almLow.BOOLS2,420465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almLow.AEBOOLS,420466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almLow.INT1,420467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almLow.INT2,420468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almLow.AENotify,420469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almLow.AESeverity,420470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almLow.AEShelveDuration,420471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almLowLow.BOOLS1,420476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almLowLow.BOOLS2,420477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almLowLow.AEBOOLS,420478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almLowLow.INT1,420479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almLowLow.INT2,420480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almLowLow.AENotify,420481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almLowLow.AESeverity,420482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almLowLow.AEShelveDuration,420483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almBrokenLoop.BOOLS1,420488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almBrokenLoop.BOOLS2,420489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almBrokenLoop.AEBOOLS,420490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almBrokenLoop.INT1,420491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almBrokenLoop.INT2,420492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almBrokenLoop.AENotify,420493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almBrokenLoop.AESeverity,420494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almBrokenLoop.AEShelveDuration,420495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almOverRange.BOOLS1,420500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almOverRange.BOOLS2,420501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almOverRange.AEBOOLS,420502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almOverRange.INT1,420503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almOverRange.INT2,420504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almOverRange.AENotify,420505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almOverRange.AESeverity,420506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almOverRange.AEShelveDuration,420507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almUnderRange.BOOLS1,420512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almUnderRange.BOOLS2,420513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almUnderRange.AEBOOLS,420514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almUnderRange.INT1,420515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almUnderRange.INT2,420516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almUnderRange.AENotify,420517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almUnderRange.AESeverity,420518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almUnderRange.AEShelveDuration,420519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almRateOfChange.BOOLS1,420524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almRateOfChange.BOOLS2,420525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almRateOfChange.AEBOOLS,420526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almRateOfChange.INT1,420527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almRateOfChange.INT2,420528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almRateOfChange.AENotify,420529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almRateOfChange.AESeverity,420530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almRateOfChange.AEShelveDuration,420531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_4_VI5.almPLCFault.BOOLS1,420536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_4_VI5.almPLCFault.BOOLS2,420537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_4_VI5.almPLCFault.AEBOOLS,420538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_4_VI5.almPLCFault.INT1,420539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almPLCFault.INT2,420540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_4_VI5.almPLCFault.AENotify,420541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_4_VI5.almPLCFault.AESeverity,420542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_4_VI5.almPLCFault.AEShelveDuration,420543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almHighHigh.BOOLS1,420640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almHighHigh.BOOLS2,420641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almHighHigh.AEBOOLS,420642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almHighHigh.INT1,420643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almHighHigh.INT2,420644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almHighHigh.AENotify,420645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almHighHigh.AESeverity,420646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almHighHigh.AEShelveDuration,420647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almHigh.BOOLS1,420652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almHigh.BOOLS2,420653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almHigh.AEBOOLS,420654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almHigh.INT1,420655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almHigh.INT2,420656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almHigh.AENotify,420657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almHigh.AESeverity,420658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almHigh.AEShelveDuration,420659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almLow.BOOLS1,420664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almLow.BOOLS2,420665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almLow.AEBOOLS,420666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almLow.INT1,420667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almLow.INT2,420668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almLow.AENotify,420669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almLow.AESeverity,420670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almLow.AEShelveDuration,420671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almLowLow.BOOLS1,420676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almLowLow.BOOLS2,420677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almLowLow.AEBOOLS,420678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almLowLow.INT1,420679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almLowLow.INT2,420680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almLowLow.AENotify,420681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almLowLow.AESeverity,420682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almLowLow.AEShelveDuration,420683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almBrokenLoop.BOOLS1,420688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almBrokenLoop.BOOLS2,420689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almBrokenLoop.AEBOOLS,420690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almBrokenLoop.INT1,420691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almBrokenLoop.INT2,420692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almBrokenLoop.AENotify,420693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almBrokenLoop.AESeverity,420694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almBrokenLoop.AEShelveDuration,420695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almOverRange.BOOLS1,420700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almOverRange.BOOLS2,420701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almOverRange.AEBOOLS,420702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almOverRange.INT1,420703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almOverRange.INT2,420704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almOverRange.AENotify,420705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almOverRange.AESeverity,420706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almOverRange.AEShelveDuration,420707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almUnderRange.BOOLS1,420712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almUnderRange.BOOLS2,420713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almUnderRange.AEBOOLS,420714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almUnderRange.INT1,420715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almUnderRange.INT2,420716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almUnderRange.AENotify,420717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almUnderRange.AESeverity,420718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almUnderRange.AEShelveDuration,420719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almRateOfChange.BOOLS1,420724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almRateOfChange.BOOLS2,420725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almRateOfChange.AEBOOLS,420726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almRateOfChange.INT1,420727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almRateOfChange.INT2,420728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almRateOfChange.AENotify,420729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almRateOfChange.AESeverity,420730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almRateOfChange.AEShelveDuration,420731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI1.almPLCFault.BOOLS1,420736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI1.almPLCFault.BOOLS2,420737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI1.almPLCFault.AEBOOLS,420738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI1.almPLCFault.INT1,420739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almPLCFault.INT2,420740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI1.almPLCFault.AENotify,420741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI1.almPLCFault.AESeverity,420742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI1.almPLCFault.AEShelveDuration,420743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almHighHigh.BOOLS1,420840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almHighHigh.BOOLS2,420841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almHighHigh.AEBOOLS,420842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almHighHigh.INT1,420843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almHighHigh.INT2,420844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almHighHigh.AENotify,420845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almHighHigh.AESeverity,420846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almHighHigh.AEShelveDuration,420847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almHigh.BOOLS1,420852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almHigh.BOOLS2,420853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almHigh.AEBOOLS,420854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almHigh.INT1,420855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almHigh.INT2,420856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almHigh.AENotify,420857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almHigh.AESeverity,420858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almHigh.AEShelveDuration,420859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almLow.BOOLS1,420864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almLow.BOOLS2,420865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almLow.AEBOOLS,420866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almLow.INT1,420867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almLow.INT2,420868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almLow.AENotify,420869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almLow.AESeverity,420870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almLow.AEShelveDuration,420871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almLowLow.BOOLS1,420876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almLowLow.BOOLS2,420877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almLowLow.AEBOOLS,420878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almLowLow.INT1,420879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almLowLow.INT2,420880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almLowLow.AENotify,420881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almLowLow.AESeverity,420882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almLowLow.AEShelveDuration,420883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almBrokenLoop.BOOLS1,420888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almBrokenLoop.BOOLS2,420889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almBrokenLoop.AEBOOLS,420890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almBrokenLoop.INT1,420891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almBrokenLoop.INT2,420892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almBrokenLoop.AENotify,420893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almBrokenLoop.AESeverity,420894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almBrokenLoop.AEShelveDuration,420895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almOverRange.BOOLS1,420900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almOverRange.BOOLS2,420901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almOverRange.AEBOOLS,420902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almOverRange.INT1,420903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almOverRange.INT2,420904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almOverRange.AENotify,420905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almOverRange.AESeverity,420906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almOverRange.AEShelveDuration,420907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almUnderRange.BOOLS1,420912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almUnderRange.BOOLS2,420913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almUnderRange.AEBOOLS,420914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almUnderRange.INT1,420915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almUnderRange.INT2,420916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almUnderRange.AENotify,420917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almUnderRange.AESeverity,420918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almUnderRange.AEShelveDuration,420919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almRateOfChange.BOOLS1,420924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almRateOfChange.BOOLS2,420925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almRateOfChange.AEBOOLS,420926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almRateOfChange.INT1,420927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almRateOfChange.INT2,420928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almRateOfChange.AENotify,420929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almRateOfChange.AESeverity,420930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almRateOfChange.AEShelveDuration,420931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI2.almPLCFault.BOOLS1,420936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI2.almPLCFault.BOOLS2,420937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI2.almPLCFault.AEBOOLS,420938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI2.almPLCFault.INT1,420939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almPLCFault.INT2,420940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI2.almPLCFault.AENotify,420941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI2.almPLCFault.AESeverity,420942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI2.almPLCFault.AEShelveDuration,420943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almHighHigh.BOOLS1,421040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almHighHigh.BOOLS2,421041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almHighHigh.AEBOOLS,421042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almHighHigh.INT1,421043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almHighHigh.INT2,421044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almHighHigh.AENotify,421045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almHighHigh.AESeverity,421046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almHighHigh.AEShelveDuration,421047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almHigh.BOOLS1,421052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almHigh.BOOLS2,421053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almHigh.AEBOOLS,421054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almHigh.INT1,421055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almHigh.INT2,421056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almHigh.AENotify,421057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almHigh.AESeverity,421058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almHigh.AEShelveDuration,421059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almLow.BOOLS1,421064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almLow.BOOLS2,421065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almLow.AEBOOLS,421066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almLow.INT1,421067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almLow.INT2,421068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almLow.AENotify,421069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almLow.AESeverity,421070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almLow.AEShelveDuration,421071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almLowLow.BOOLS1,421076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almLowLow.BOOLS2,421077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almLowLow.AEBOOLS,421078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almLowLow.INT1,421079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almLowLow.INT2,421080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almLowLow.AENotify,421081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almLowLow.AESeverity,421082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almLowLow.AEShelveDuration,421083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almBrokenLoop.BOOLS1,421088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almBrokenLoop.BOOLS2,421089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almBrokenLoop.AEBOOLS,421090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almBrokenLoop.INT1,421091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almBrokenLoop.INT2,421092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almBrokenLoop.AENotify,421093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almBrokenLoop.AESeverity,421094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almBrokenLoop.AEShelveDuration,421095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almOverRange.BOOLS1,421100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almOverRange.BOOLS2,421101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almOverRange.AEBOOLS,421102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almOverRange.INT1,421103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almOverRange.INT2,421104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almOverRange.AENotify,421105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almOverRange.AESeverity,421106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almOverRange.AEShelveDuration,421107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almUnderRange.BOOLS1,421112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almUnderRange.BOOLS2,421113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almUnderRange.AEBOOLS,421114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almUnderRange.INT1,421115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almUnderRange.INT2,421116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almUnderRange.AENotify,421117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almUnderRange.AESeverity,421118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almUnderRange.AEShelveDuration,421119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almRateOfChange.BOOLS1,421124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almRateOfChange.BOOLS2,421125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almRateOfChange.AEBOOLS,421126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almRateOfChange.INT1,421127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almRateOfChange.INT2,421128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almRateOfChange.AENotify,421129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almRateOfChange.AESeverity,421130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almRateOfChange.AEShelveDuration,421131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI3.almPLCFault.BOOLS1,421136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI3.almPLCFault.BOOLS2,421137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI3.almPLCFault.AEBOOLS,421138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI3.almPLCFault.INT1,421139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almPLCFault.INT2,421140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI3.almPLCFault.AENotify,421141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI3.almPLCFault.AESeverity,421142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI3.almPLCFault.AEShelveDuration,421143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almHighHigh.BOOLS1,421240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almHighHigh.BOOLS2,421241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almHighHigh.AEBOOLS,421242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almHighHigh.INT1,421243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almHighHigh.INT2,421244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almHighHigh.AENotify,421245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almHighHigh.AESeverity,421246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almHighHigh.AEShelveDuration,421247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almHigh.BOOLS1,421252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almHigh.BOOLS2,421253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almHigh.AEBOOLS,421254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almHigh.INT1,421255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almHigh.INT2,421256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almHigh.AENotify,421257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almHigh.AESeverity,421258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almHigh.AEShelveDuration,421259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almLow.BOOLS1,421264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almLow.BOOLS2,421265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almLow.AEBOOLS,421266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almLow.INT1,421267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almLow.INT2,421268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almLow.AENotify,421269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almLow.AESeverity,421270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almLow.AEShelveDuration,421271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almLowLow.BOOLS1,421276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almLowLow.BOOLS2,421277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almLowLow.AEBOOLS,421278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almLowLow.INT1,421279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almLowLow.INT2,421280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almLowLow.AENotify,421281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almLowLow.AESeverity,421282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almLowLow.AEShelveDuration,421283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almBrokenLoop.BOOLS1,421288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almBrokenLoop.BOOLS2,421289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almBrokenLoop.AEBOOLS,421290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almBrokenLoop.INT1,421291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almBrokenLoop.INT2,421292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almBrokenLoop.AENotify,421293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almBrokenLoop.AESeverity,421294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almBrokenLoop.AEShelveDuration,421295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almOverRange.BOOLS1,421300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almOverRange.BOOLS2,421301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almOverRange.AEBOOLS,421302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almOverRange.INT1,421303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almOverRange.INT2,421304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almOverRange.AENotify,421305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almOverRange.AESeverity,421306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almOverRange.AEShelveDuration,421307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almUnderRange.BOOLS1,421312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almUnderRange.BOOLS2,421313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almUnderRange.AEBOOLS,421314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almUnderRange.INT1,421315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almUnderRange.INT2,421316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almUnderRange.AENotify,421317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almUnderRange.AESeverity,421318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almUnderRange.AEShelveDuration,421319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almRateOfChange.BOOLS1,421324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almRateOfChange.BOOLS2,421325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almRateOfChange.AEBOOLS,421326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almRateOfChange.INT1,421327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almRateOfChange.INT2,421328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almRateOfChange.AENotify,421329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almRateOfChange.AESeverity,421330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almRateOfChange.AEShelveDuration,421331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI4.almPLCFault.BOOLS1,421336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI4.almPLCFault.BOOLS2,421337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI4.almPLCFault.AEBOOLS,421338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI4.almPLCFault.INT1,421339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almPLCFault.INT2,421340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI4.almPLCFault.AENotify,421341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI4.almPLCFault.AESeverity,421342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI4.almPLCFault.AEShelveDuration,421343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almHighHigh.BOOLS1,421440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almHighHigh.BOOLS2,421441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almHighHigh.AEBOOLS,421442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almHighHigh.INT1,421443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almHighHigh.INT2,421444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almHighHigh.AENotify,421445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almHighHigh.AESeverity,421446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almHighHigh.AEShelveDuration,421447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almHigh.BOOLS1,421452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almHigh.BOOLS2,421453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almHigh.AEBOOLS,421454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almHigh.INT1,421455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almHigh.INT2,421456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almHigh.AENotify,421457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almHigh.AESeverity,421458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almHigh.AEShelveDuration,421459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almLow.BOOLS1,421464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almLow.BOOLS2,421465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almLow.AEBOOLS,421466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almLow.INT1,421467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almLow.INT2,421468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almLow.AENotify,421469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almLow.AESeverity,421470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almLow.AEShelveDuration,421471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almLowLow.BOOLS1,421476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almLowLow.BOOLS2,421477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almLowLow.AEBOOLS,421478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almLowLow.INT1,421479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almLowLow.INT2,421480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almLowLow.AENotify,421481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almLowLow.AESeverity,421482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almLowLow.AEShelveDuration,421483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almBrokenLoop.BOOLS1,421488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almBrokenLoop.BOOLS2,421489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almBrokenLoop.AEBOOLS,421490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almBrokenLoop.INT1,421491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almBrokenLoop.INT2,421492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almBrokenLoop.AENotify,421493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almBrokenLoop.AESeverity,421494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almBrokenLoop.AEShelveDuration,421495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almOverRange.BOOLS1,421500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almOverRange.BOOLS2,421501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almOverRange.AEBOOLS,421502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almOverRange.INT1,421503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almOverRange.INT2,421504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almOverRange.AENotify,421505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almOverRange.AESeverity,421506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almOverRange.AEShelveDuration,421507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almUnderRange.BOOLS1,421512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almUnderRange.BOOLS2,421513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almUnderRange.AEBOOLS,421514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almUnderRange.INT1,421515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almUnderRange.INT2,421516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almUnderRange.AENotify,421517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almUnderRange.AESeverity,421518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almUnderRange.AEShelveDuration,421519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almRateOfChange.BOOLS1,421524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almRateOfChange.BOOLS2,421525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almRateOfChange.AEBOOLS,421526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almRateOfChange.INT1,421527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almRateOfChange.INT2,421528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almRateOfChange.AENotify,421529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almRateOfChange.AESeverity,421530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almRateOfChange.AEShelveDuration,421531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_5_VI5.almPLCFault.BOOLS1,421536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_5_VI5.almPLCFault.BOOLS2,421537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_5_VI5.almPLCFault.AEBOOLS,421538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_5_VI5.almPLCFault.INT1,421539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almPLCFault.INT2,421540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_5_VI5.almPLCFault.AENotify,421541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_5_VI5.almPLCFault.AESeverity,421542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_5_VI5.almPLCFault.AEShelveDuration,421543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almHighHigh.BOOLS1,421640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almHighHigh.BOOLS2,421641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almHighHigh.AEBOOLS,421642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almHighHigh.INT1,421643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almHighHigh.INT2,421644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almHighHigh.AENotify,421645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almHighHigh.AESeverity,421646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almHighHigh.AEShelveDuration,421647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almHigh.BOOLS1,421652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almHigh.BOOLS2,421653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almHigh.AEBOOLS,421654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almHigh.INT1,421655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almHigh.INT2,421656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almHigh.AENotify,421657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almHigh.AESeverity,421658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almHigh.AEShelveDuration,421659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almLow.BOOLS1,421664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almLow.BOOLS2,421665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almLow.AEBOOLS,421666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almLow.INT1,421667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almLow.INT2,421668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almLow.AENotify,421669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almLow.AESeverity,421670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almLow.AEShelveDuration,421671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almLowLow.BOOLS1,421676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almLowLow.BOOLS2,421677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almLowLow.AEBOOLS,421678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almLowLow.INT1,421679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almLowLow.INT2,421680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almLowLow.AENotify,421681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almLowLow.AESeverity,421682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almLowLow.AEShelveDuration,421683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almBrokenLoop.BOOLS1,421688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almBrokenLoop.BOOLS2,421689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almBrokenLoop.AEBOOLS,421690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almBrokenLoop.INT1,421691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almBrokenLoop.INT2,421692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almBrokenLoop.AENotify,421693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almBrokenLoop.AESeverity,421694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almBrokenLoop.AEShelveDuration,421695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almOverRange.BOOLS1,421700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almOverRange.BOOLS2,421701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almOverRange.AEBOOLS,421702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almOverRange.INT1,421703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almOverRange.INT2,421704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almOverRange.AENotify,421705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almOverRange.AESeverity,421706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almOverRange.AEShelveDuration,421707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almUnderRange.BOOLS1,421712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almUnderRange.BOOLS2,421713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almUnderRange.AEBOOLS,421714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almUnderRange.INT1,421715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almUnderRange.INT2,421716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almUnderRange.AENotify,421717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almUnderRange.AESeverity,421718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almUnderRange.AEShelveDuration,421719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almRateOfChange.BOOLS1,421724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almRateOfChange.BOOLS2,421725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almRateOfChange.AEBOOLS,421726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almRateOfChange.INT1,421727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almRateOfChange.INT2,421728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almRateOfChange.AENotify,421729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almRateOfChange.AESeverity,421730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almRateOfChange.AEShelveDuration,421731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI1.almPLCFault.BOOLS1,421736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI1.almPLCFault.BOOLS2,421737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI1.almPLCFault.AEBOOLS,421738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI1.almPLCFault.INT1,421739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almPLCFault.INT2,421740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI1.almPLCFault.AENotify,421741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI1.almPLCFault.AESeverity,421742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI1.almPLCFault.AEShelveDuration,421743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almHighHigh.BOOLS1,421840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almHighHigh.BOOLS2,421841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almHighHigh.AEBOOLS,421842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almHighHigh.INT1,421843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almHighHigh.INT2,421844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almHighHigh.AENotify,421845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almHighHigh.AESeverity,421846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almHighHigh.AEShelveDuration,421847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almHigh.BOOLS1,421852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almHigh.BOOLS2,421853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almHigh.AEBOOLS,421854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almHigh.INT1,421855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almHigh.INT2,421856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almHigh.AENotify,421857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almHigh.AESeverity,421858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almHigh.AEShelveDuration,421859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almLow.BOOLS1,421864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almLow.BOOLS2,421865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almLow.AEBOOLS,421866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almLow.INT1,421867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almLow.INT2,421868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almLow.AENotify,421869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almLow.AESeverity,421870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almLow.AEShelveDuration,421871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almLowLow.BOOLS1,421876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almLowLow.BOOLS2,421877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almLowLow.AEBOOLS,421878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almLowLow.INT1,421879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almLowLow.INT2,421880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almLowLow.AENotify,421881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almLowLow.AESeverity,421882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almLowLow.AEShelveDuration,421883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almBrokenLoop.BOOLS1,421888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almBrokenLoop.BOOLS2,421889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almBrokenLoop.AEBOOLS,421890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almBrokenLoop.INT1,421891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almBrokenLoop.INT2,421892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almBrokenLoop.AENotify,421893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almBrokenLoop.AESeverity,421894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almBrokenLoop.AEShelveDuration,421895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almOverRange.BOOLS1,421900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almOverRange.BOOLS2,421901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almOverRange.AEBOOLS,421902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almOverRange.INT1,421903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almOverRange.INT2,421904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almOverRange.AENotify,421905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almOverRange.AESeverity,421906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almOverRange.AEShelveDuration,421907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almUnderRange.BOOLS1,421912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almUnderRange.BOOLS2,421913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almUnderRange.AEBOOLS,421914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almUnderRange.INT1,421915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almUnderRange.INT2,421916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almUnderRange.AENotify,421917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almUnderRange.AESeverity,421918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almUnderRange.AEShelveDuration,421919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almRateOfChange.BOOLS1,421924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almRateOfChange.BOOLS2,421925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almRateOfChange.AEBOOLS,421926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almRateOfChange.INT1,421927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almRateOfChange.INT2,421928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almRateOfChange.AENotify,421929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almRateOfChange.AESeverity,421930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almRateOfChange.AEShelveDuration,421931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI2.almPLCFault.BOOLS1,421936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI2.almPLCFault.BOOLS2,421937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI2.almPLCFault.AEBOOLS,421938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI2.almPLCFault.INT1,421939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almPLCFault.INT2,421940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI2.almPLCFault.AENotify,421941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI2.almPLCFault.AESeverity,421942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI2.almPLCFault.AEShelveDuration,421943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almHighHigh.BOOLS1,422040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almHighHigh.BOOLS2,422041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almHighHigh.AEBOOLS,422042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almHighHigh.INT1,422043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almHighHigh.INT2,422044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almHighHigh.AENotify,422045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almHighHigh.AESeverity,422046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almHighHigh.AEShelveDuration,422047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almHigh.BOOLS1,422052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almHigh.BOOLS2,422053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almHigh.AEBOOLS,422054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almHigh.INT1,422055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almHigh.INT2,422056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almHigh.AENotify,422057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almHigh.AESeverity,422058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almHigh.AEShelveDuration,422059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almLow.BOOLS1,422064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almLow.BOOLS2,422065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almLow.AEBOOLS,422066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almLow.INT1,422067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almLow.INT2,422068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almLow.AENotify,422069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almLow.AESeverity,422070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almLow.AEShelveDuration,422071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almLowLow.BOOLS1,422076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almLowLow.BOOLS2,422077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almLowLow.AEBOOLS,422078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almLowLow.INT1,422079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almLowLow.INT2,422080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almLowLow.AENotify,422081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almLowLow.AESeverity,422082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almLowLow.AEShelveDuration,422083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almBrokenLoop.BOOLS1,422088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almBrokenLoop.BOOLS2,422089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almBrokenLoop.AEBOOLS,422090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almBrokenLoop.INT1,422091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almBrokenLoop.INT2,422092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almBrokenLoop.AENotify,422093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almBrokenLoop.AESeverity,422094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almBrokenLoop.AEShelveDuration,422095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almOverRange.BOOLS1,422100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almOverRange.BOOLS2,422101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almOverRange.AEBOOLS,422102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almOverRange.INT1,422103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almOverRange.INT2,422104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almOverRange.AENotify,422105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almOverRange.AESeverity,422106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almOverRange.AEShelveDuration,422107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almUnderRange.BOOLS1,422112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almUnderRange.BOOLS2,422113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almUnderRange.AEBOOLS,422114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almUnderRange.INT1,422115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almUnderRange.INT2,422116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almUnderRange.AENotify,422117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almUnderRange.AESeverity,422118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almUnderRange.AEShelveDuration,422119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almRateOfChange.BOOLS1,422124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almRateOfChange.BOOLS2,422125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almRateOfChange.AEBOOLS,422126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almRateOfChange.INT1,422127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almRateOfChange.INT2,422128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almRateOfChange.AENotify,422129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almRateOfChange.AESeverity,422130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almRateOfChange.AEShelveDuration,422131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI3.almPLCFault.BOOLS1,422136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI3.almPLCFault.BOOLS2,422137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI3.almPLCFault.AEBOOLS,422138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI3.almPLCFault.INT1,422139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almPLCFault.INT2,422140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI3.almPLCFault.AENotify,422141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI3.almPLCFault.AESeverity,422142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI3.almPLCFault.AEShelveDuration,422143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almHighHigh.BOOLS1,422240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almHighHigh.BOOLS2,422241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almHighHigh.AEBOOLS,422242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almHighHigh.INT1,422243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almHighHigh.INT2,422244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almHighHigh.AENotify,422245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almHighHigh.AESeverity,422246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almHighHigh.AEShelveDuration,422247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almHigh.BOOLS1,422252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almHigh.BOOLS2,422253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almHigh.AEBOOLS,422254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almHigh.INT1,422255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almHigh.INT2,422256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almHigh.AENotify,422257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almHigh.AESeverity,422258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almHigh.AEShelveDuration,422259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almLow.BOOLS1,422264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almLow.BOOLS2,422265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almLow.AEBOOLS,422266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almLow.INT1,422267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almLow.INT2,422268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almLow.AENotify,422269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almLow.AESeverity,422270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almLow.AEShelveDuration,422271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almLowLow.BOOLS1,422276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almLowLow.BOOLS2,422277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almLowLow.AEBOOLS,422278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almLowLow.INT1,422279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almLowLow.INT2,422280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almLowLow.AENotify,422281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almLowLow.AESeverity,422282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almLowLow.AEShelveDuration,422283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almBrokenLoop.BOOLS1,422288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almBrokenLoop.BOOLS2,422289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almBrokenLoop.AEBOOLS,422290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almBrokenLoop.INT1,422291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almBrokenLoop.INT2,422292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almBrokenLoop.AENotify,422293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almBrokenLoop.AESeverity,422294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almBrokenLoop.AEShelveDuration,422295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almOverRange.BOOLS1,422300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almOverRange.BOOLS2,422301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almOverRange.AEBOOLS,422302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almOverRange.INT1,422303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almOverRange.INT2,422304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almOverRange.AENotify,422305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almOverRange.AESeverity,422306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almOverRange.AEShelveDuration,422307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almUnderRange.BOOLS1,422312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almUnderRange.BOOLS2,422313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almUnderRange.AEBOOLS,422314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almUnderRange.INT1,422315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almUnderRange.INT2,422316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almUnderRange.AENotify,422317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almUnderRange.AESeverity,422318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almUnderRange.AEShelveDuration,422319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almRateOfChange.BOOLS1,422324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almRateOfChange.BOOLS2,422325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almRateOfChange.AEBOOLS,422326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almRateOfChange.INT1,422327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almRateOfChange.INT2,422328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almRateOfChange.AENotify,422329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almRateOfChange.AESeverity,422330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almRateOfChange.AEShelveDuration,422331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI4.almPLCFault.BOOLS1,422336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI4.almPLCFault.BOOLS2,422337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI4.almPLCFault.AEBOOLS,422338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI4.almPLCFault.INT1,422339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almPLCFault.INT2,422340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI4.almPLCFault.AENotify,422341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI4.almPLCFault.AESeverity,422342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI4.almPLCFault.AEShelveDuration,422343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almHighHigh.BOOLS1,422440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almHighHigh.BOOLS2,422441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almHighHigh.AEBOOLS,422442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almHighHigh.INT1,422443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almHighHigh.INT2,422444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almHighHigh.AENotify,422445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almHighHigh.AESeverity,422446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almHighHigh.AEShelveDuration,422447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almHigh.BOOLS1,422452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almHigh.BOOLS2,422453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almHigh.AEBOOLS,422454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almHigh.INT1,422455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almHigh.INT2,422456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almHigh.AENotify,422457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almHigh.AESeverity,422458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almHigh.AEShelveDuration,422459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almLow.BOOLS1,422464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almLow.BOOLS2,422465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almLow.AEBOOLS,422466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almLow.INT1,422467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almLow.INT2,422468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almLow.AENotify,422469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almLow.AESeverity,422470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almLow.AEShelveDuration,422471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almLowLow.BOOLS1,422476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almLowLow.BOOLS2,422477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almLowLow.AEBOOLS,422478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almLowLow.INT1,422479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almLowLow.INT2,422480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almLowLow.AENotify,422481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almLowLow.AESeverity,422482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almLowLow.AEShelveDuration,422483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almBrokenLoop.BOOLS1,422488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almBrokenLoop.BOOLS2,422489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almBrokenLoop.AEBOOLS,422490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almBrokenLoop.INT1,422491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almBrokenLoop.INT2,422492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almBrokenLoop.AENotify,422493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almBrokenLoop.AESeverity,422494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almBrokenLoop.AEShelveDuration,422495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almOverRange.BOOLS1,422500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almOverRange.BOOLS2,422501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almOverRange.AEBOOLS,422502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almOverRange.INT1,422503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almOverRange.INT2,422504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almOverRange.AENotify,422505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almOverRange.AESeverity,422506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almOverRange.AEShelveDuration,422507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almUnderRange.BOOLS1,422512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almUnderRange.BOOLS2,422513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almUnderRange.AEBOOLS,422514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almUnderRange.INT1,422515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almUnderRange.INT2,422516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almUnderRange.AENotify,422517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almUnderRange.AESeverity,422518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almUnderRange.AEShelveDuration,422519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almRateOfChange.BOOLS1,422524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almRateOfChange.BOOLS2,422525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almRateOfChange.AEBOOLS,422526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almRateOfChange.INT1,422527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almRateOfChange.INT2,422528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almRateOfChange.AENotify,422529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almRateOfChange.AESeverity,422530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almRateOfChange.AEShelveDuration,422531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_6_VI5.almPLCFault.BOOLS1,422536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_6_VI5.almPLCFault.BOOLS2,422537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_6_VI5.almPLCFault.AEBOOLS,422538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_6_VI5.almPLCFault.INT1,422539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almPLCFault.INT2,422540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_6_VI5.almPLCFault.AENotify,422541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_6_VI5.almPLCFault.AESeverity,422542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_6_VI5.almPLCFault.AEShelveDuration,422543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almHighHigh.BOOLS1,422640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almHighHigh.BOOLS2,422641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almHighHigh.AEBOOLS,422642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almHighHigh.INT1,422643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almHighHigh.INT2,422644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almHighHigh.AENotify,422645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almHighHigh.AESeverity,422646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almHighHigh.AEShelveDuration,422647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almHigh.BOOLS1,422652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almHigh.BOOLS2,422653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almHigh.AEBOOLS,422654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almHigh.INT1,422655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almHigh.INT2,422656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almHigh.AENotify,422657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almHigh.AESeverity,422658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almHigh.AEShelveDuration,422659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almLow.BOOLS1,422664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almLow.BOOLS2,422665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almLow.AEBOOLS,422666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almLow.INT1,422667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almLow.INT2,422668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almLow.AENotify,422669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almLow.AESeverity,422670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almLow.AEShelveDuration,422671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almLowLow.BOOLS1,422676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almLowLow.BOOLS2,422677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almLowLow.AEBOOLS,422678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almLowLow.INT1,422679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almLowLow.INT2,422680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almLowLow.AENotify,422681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almLowLow.AESeverity,422682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almLowLow.AEShelveDuration,422683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almBrokenLoop.BOOLS1,422688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almBrokenLoop.BOOLS2,422689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almBrokenLoop.AEBOOLS,422690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almBrokenLoop.INT1,422691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almBrokenLoop.INT2,422692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almBrokenLoop.AENotify,422693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almBrokenLoop.AESeverity,422694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almBrokenLoop.AEShelveDuration,422695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almOverRange.BOOLS1,422700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almOverRange.BOOLS2,422701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almOverRange.AEBOOLS,422702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almOverRange.INT1,422703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almOverRange.INT2,422704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almOverRange.AENotify,422705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almOverRange.AESeverity,422706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almOverRange.AEShelveDuration,422707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almUnderRange.BOOLS1,422712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almUnderRange.BOOLS2,422713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almUnderRange.AEBOOLS,422714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almUnderRange.INT1,422715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almUnderRange.INT2,422716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almUnderRange.AENotify,422717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almUnderRange.AESeverity,422718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almUnderRange.AEShelveDuration,422719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almRateOfChange.BOOLS1,422724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almRateOfChange.BOOLS2,422725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almRateOfChange.AEBOOLS,422726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almRateOfChange.INT1,422727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almRateOfChange.INT2,422728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almRateOfChange.AENotify,422729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almRateOfChange.AESeverity,422730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almRateOfChange.AEShelveDuration,422731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI1.almPLCFault.BOOLS1,422736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI1.almPLCFault.BOOLS2,422737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI1.almPLCFault.AEBOOLS,422738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI1.almPLCFault.INT1,422739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almPLCFault.INT2,422740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI1.almPLCFault.AENotify,422741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI1.almPLCFault.AESeverity,422742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI1.almPLCFault.AEShelveDuration,422743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almHighHigh.BOOLS1,422840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almHighHigh.BOOLS2,422841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almHighHigh.AEBOOLS,422842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almHighHigh.INT1,422843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almHighHigh.INT2,422844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almHighHigh.AENotify,422845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almHighHigh.AESeverity,422846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almHighHigh.AEShelveDuration,422847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almHigh.BOOLS1,422852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almHigh.BOOLS2,422853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almHigh.AEBOOLS,422854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almHigh.INT1,422855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almHigh.INT2,422856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almHigh.AENotify,422857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almHigh.AESeverity,422858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almHigh.AEShelveDuration,422859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almLow.BOOLS1,422864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almLow.BOOLS2,422865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almLow.AEBOOLS,422866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almLow.INT1,422867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almLow.INT2,422868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almLow.AENotify,422869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almLow.AESeverity,422870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almLow.AEShelveDuration,422871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almLowLow.BOOLS1,422876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almLowLow.BOOLS2,422877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almLowLow.AEBOOLS,422878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almLowLow.INT1,422879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almLowLow.INT2,422880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almLowLow.AENotify,422881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almLowLow.AESeverity,422882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almLowLow.AEShelveDuration,422883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almBrokenLoop.BOOLS1,422888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almBrokenLoop.BOOLS2,422889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almBrokenLoop.AEBOOLS,422890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almBrokenLoop.INT1,422891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almBrokenLoop.INT2,422892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almBrokenLoop.AENotify,422893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almBrokenLoop.AESeverity,422894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almBrokenLoop.AEShelveDuration,422895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almOverRange.BOOLS1,422900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almOverRange.BOOLS2,422901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almOverRange.AEBOOLS,422902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almOverRange.INT1,422903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almOverRange.INT2,422904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almOverRange.AENotify,422905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almOverRange.AESeverity,422906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almOverRange.AEShelveDuration,422907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almUnderRange.BOOLS1,422912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almUnderRange.BOOLS2,422913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almUnderRange.AEBOOLS,422914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almUnderRange.INT1,422915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almUnderRange.INT2,422916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almUnderRange.AENotify,422917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almUnderRange.AESeverity,422918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almUnderRange.AEShelveDuration,422919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almRateOfChange.BOOLS1,422924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almRateOfChange.BOOLS2,422925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almRateOfChange.AEBOOLS,422926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almRateOfChange.INT1,422927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almRateOfChange.INT2,422928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almRateOfChange.AENotify,422929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almRateOfChange.AESeverity,422930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almRateOfChange.AEShelveDuration,422931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI2.almPLCFault.BOOLS1,422936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI2.almPLCFault.BOOLS2,422937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI2.almPLCFault.AEBOOLS,422938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI2.almPLCFault.INT1,422939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almPLCFault.INT2,422940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI2.almPLCFault.AENotify,422941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI2.almPLCFault.AESeverity,422942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI2.almPLCFault.AEShelveDuration,422943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almHighHigh.BOOLS1,423040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almHighHigh.BOOLS2,423041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almHighHigh.AEBOOLS,423042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almHighHigh.INT1,423043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almHighHigh.INT2,423044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almHighHigh.AENotify,423045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almHighHigh.AESeverity,423046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almHighHigh.AEShelveDuration,423047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almHigh.BOOLS1,423052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almHigh.BOOLS2,423053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almHigh.AEBOOLS,423054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almHigh.INT1,423055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almHigh.INT2,423056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almHigh.AENotify,423057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almHigh.AESeverity,423058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almHigh.AEShelveDuration,423059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almLow.BOOLS1,423064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almLow.BOOLS2,423065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almLow.AEBOOLS,423066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almLow.INT1,423067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almLow.INT2,423068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almLow.AENotify,423069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almLow.AESeverity,423070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almLow.AEShelveDuration,423071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almLowLow.BOOLS1,423076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almLowLow.BOOLS2,423077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almLowLow.AEBOOLS,423078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almLowLow.INT1,423079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almLowLow.INT2,423080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almLowLow.AENotify,423081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almLowLow.AESeverity,423082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almLowLow.AEShelveDuration,423083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almBrokenLoop.BOOLS1,423088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almBrokenLoop.BOOLS2,423089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almBrokenLoop.AEBOOLS,423090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almBrokenLoop.INT1,423091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almBrokenLoop.INT2,423092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almBrokenLoop.AENotify,423093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almBrokenLoop.AESeverity,423094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almBrokenLoop.AEShelveDuration,423095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almOverRange.BOOLS1,423100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almOverRange.BOOLS2,423101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almOverRange.AEBOOLS,423102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almOverRange.INT1,423103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almOverRange.INT2,423104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almOverRange.AENotify,423105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almOverRange.AESeverity,423106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almOverRange.AEShelveDuration,423107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almUnderRange.BOOLS1,423112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almUnderRange.BOOLS2,423113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almUnderRange.AEBOOLS,423114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almUnderRange.INT1,423115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almUnderRange.INT2,423116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almUnderRange.AENotify,423117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almUnderRange.AESeverity,423118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almUnderRange.AEShelveDuration,423119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almRateOfChange.BOOLS1,423124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almRateOfChange.BOOLS2,423125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almRateOfChange.AEBOOLS,423126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almRateOfChange.INT1,423127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almRateOfChange.INT2,423128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almRateOfChange.AENotify,423129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almRateOfChange.AESeverity,423130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almRateOfChange.AEShelveDuration,423131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI3.almPLCFault.BOOLS1,423136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI3.almPLCFault.BOOLS2,423137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI3.almPLCFault.AEBOOLS,423138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI3.almPLCFault.INT1,423139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almPLCFault.INT2,423140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI3.almPLCFault.AENotify,423141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI3.almPLCFault.AESeverity,423142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI3.almPLCFault.AEShelveDuration,423143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almHighHigh.BOOLS1,423240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almHighHigh.BOOLS2,423241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almHighHigh.AEBOOLS,423242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almHighHigh.INT1,423243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almHighHigh.INT2,423244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almHighHigh.AENotify,423245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almHighHigh.AESeverity,423246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almHighHigh.AEShelveDuration,423247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almHigh.BOOLS1,423252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almHigh.BOOLS2,423253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almHigh.AEBOOLS,423254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almHigh.INT1,423255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almHigh.INT2,423256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almHigh.AENotify,423257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almHigh.AESeverity,423258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almHigh.AEShelveDuration,423259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almLow.BOOLS1,423264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almLow.BOOLS2,423265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almLow.AEBOOLS,423266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almLow.INT1,423267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almLow.INT2,423268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almLow.AENotify,423269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almLow.AESeverity,423270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almLow.AEShelveDuration,423271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almLowLow.BOOLS1,423276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almLowLow.BOOLS2,423277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almLowLow.AEBOOLS,423278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almLowLow.INT1,423279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almLowLow.INT2,423280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almLowLow.AENotify,423281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almLowLow.AESeverity,423282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almLowLow.AEShelveDuration,423283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almBrokenLoop.BOOLS1,423288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almBrokenLoop.BOOLS2,423289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almBrokenLoop.AEBOOLS,423290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almBrokenLoop.INT1,423291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almBrokenLoop.INT2,423292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almBrokenLoop.AENotify,423293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almBrokenLoop.AESeverity,423294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almBrokenLoop.AEShelveDuration,423295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almOverRange.BOOLS1,423300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almOverRange.BOOLS2,423301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almOverRange.AEBOOLS,423302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almOverRange.INT1,423303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almOverRange.INT2,423304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almOverRange.AENotify,423305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almOverRange.AESeverity,423306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almOverRange.AEShelveDuration,423307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almUnderRange.BOOLS1,423312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almUnderRange.BOOLS2,423313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almUnderRange.AEBOOLS,423314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almUnderRange.INT1,423315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almUnderRange.INT2,423316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almUnderRange.AENotify,423317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almUnderRange.AESeverity,423318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almUnderRange.AEShelveDuration,423319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almRateOfChange.BOOLS1,423324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almRateOfChange.BOOLS2,423325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almRateOfChange.AEBOOLS,423326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almRateOfChange.INT1,423327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almRateOfChange.INT2,423328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almRateOfChange.AENotify,423329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almRateOfChange.AESeverity,423330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almRateOfChange.AEShelveDuration,423331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI4.almPLCFault.BOOLS1,423336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI4.almPLCFault.BOOLS2,423337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI4.almPLCFault.AEBOOLS,423338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI4.almPLCFault.INT1,423339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almPLCFault.INT2,423340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI4.almPLCFault.AENotify,423341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI4.almPLCFault.AESeverity,423342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI4.almPLCFault.AEShelveDuration,423343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almHighHigh.BOOLS1,423440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almHighHigh.BOOLS2,423441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almHighHigh.AEBOOLS,423442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almHighHigh.INT1,423443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almHighHigh.INT2,423444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almHighHigh.AENotify,423445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almHighHigh.AESeverity,423446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almHighHigh.AEShelveDuration,423447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almHigh.BOOLS1,423452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almHigh.BOOLS2,423453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almHigh.AEBOOLS,423454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almHigh.INT1,423455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almHigh.INT2,423456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almHigh.AENotify,423457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almHigh.AESeverity,423458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almHigh.AEShelveDuration,423459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almLow.BOOLS1,423464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almLow.BOOLS2,423465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almLow.AEBOOLS,423466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almLow.INT1,423467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almLow.INT2,423468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almLow.AENotify,423469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almLow.AESeverity,423470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almLow.AEShelveDuration,423471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almLowLow.BOOLS1,423476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almLowLow.BOOLS2,423477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almLowLow.AEBOOLS,423478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almLowLow.INT1,423479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almLowLow.INT2,423480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almLowLow.AENotify,423481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almLowLow.AESeverity,423482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almLowLow.AEShelveDuration,423483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almBrokenLoop.BOOLS1,423488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almBrokenLoop.BOOLS2,423489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almBrokenLoop.AEBOOLS,423490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almBrokenLoop.INT1,423491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almBrokenLoop.INT2,423492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almBrokenLoop.AENotify,423493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almBrokenLoop.AESeverity,423494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almBrokenLoop.AEShelveDuration,423495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almOverRange.BOOLS1,423500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almOverRange.BOOLS2,423501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almOverRange.AEBOOLS,423502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almOverRange.INT1,423503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almOverRange.INT2,423504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almOverRange.AENotify,423505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almOverRange.AESeverity,423506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almOverRange.AEShelveDuration,423507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almUnderRange.BOOLS1,423512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almUnderRange.BOOLS2,423513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almUnderRange.AEBOOLS,423514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almUnderRange.INT1,423515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almUnderRange.INT2,423516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almUnderRange.AENotify,423517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almUnderRange.AESeverity,423518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almUnderRange.AEShelveDuration,423519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almRateOfChange.BOOLS1,423524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almRateOfChange.BOOLS2,423525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almRateOfChange.AEBOOLS,423526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almRateOfChange.INT1,423527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almRateOfChange.INT2,423528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almRateOfChange.AENotify,423529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almRateOfChange.AESeverity,423530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almRateOfChange.AEShelveDuration,423531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_7_VI5.almPLCFault.BOOLS1,423536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_7_VI5.almPLCFault.BOOLS2,423537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_7_VI5.almPLCFault.AEBOOLS,423538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_7_VI5.almPLCFault.INT1,423539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almPLCFault.INT2,423540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_7_VI5.almPLCFault.AENotify,423541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_7_VI5.almPLCFault.AESeverity,423542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_7_VI5.almPLCFault.AEShelveDuration,423543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almHighHigh.BOOLS1,423640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almHighHigh.BOOLS2,423641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almHighHigh.AEBOOLS,423642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almHighHigh.INT1,423643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almHighHigh.INT2,423644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almHighHigh.AENotify,423645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almHighHigh.AESeverity,423646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almHighHigh.AEShelveDuration,423647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almHigh.BOOLS1,423652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almHigh.BOOLS2,423653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almHigh.AEBOOLS,423654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almHigh.INT1,423655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almHigh.INT2,423656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almHigh.AENotify,423657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almHigh.AESeverity,423658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almHigh.AEShelveDuration,423659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almLow.BOOLS1,423664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almLow.BOOLS2,423665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almLow.AEBOOLS,423666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almLow.INT1,423667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almLow.INT2,423668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almLow.AENotify,423669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almLow.AESeverity,423670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almLow.AEShelveDuration,423671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almLowLow.BOOLS1,423676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almLowLow.BOOLS2,423677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almLowLow.AEBOOLS,423678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almLowLow.INT1,423679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almLowLow.INT2,423680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almLowLow.AENotify,423681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almLowLow.AESeverity,423682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almLowLow.AEShelveDuration,423683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almBrokenLoop.BOOLS1,423688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almBrokenLoop.BOOLS2,423689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almBrokenLoop.AEBOOLS,423690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almBrokenLoop.INT1,423691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almBrokenLoop.INT2,423692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almBrokenLoop.AENotify,423693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almBrokenLoop.AESeverity,423694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almBrokenLoop.AEShelveDuration,423695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almOverRange.BOOLS1,423700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almOverRange.BOOLS2,423701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almOverRange.AEBOOLS,423702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almOverRange.INT1,423703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almOverRange.INT2,423704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almOverRange.AENotify,423705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almOverRange.AESeverity,423706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almOverRange.AEShelveDuration,423707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almUnderRange.BOOLS1,423712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almUnderRange.BOOLS2,423713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almUnderRange.AEBOOLS,423714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almUnderRange.INT1,423715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almUnderRange.INT2,423716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almUnderRange.AENotify,423717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almUnderRange.AESeverity,423718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almUnderRange.AEShelveDuration,423719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almRateOfChange.BOOLS1,423724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almRateOfChange.BOOLS2,423725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almRateOfChange.AEBOOLS,423726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almRateOfChange.INT1,423727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almRateOfChange.INT2,423728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almRateOfChange.AENotify,423729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almRateOfChange.AESeverity,423730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almRateOfChange.AEShelveDuration,423731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI1.almPLCFault.BOOLS1,423736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI1.almPLCFault.BOOLS2,423737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI1.almPLCFault.AEBOOLS,423738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI1.almPLCFault.INT1,423739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almPLCFault.INT2,423740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI1.almPLCFault.AENotify,423741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI1.almPLCFault.AESeverity,423742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI1.almPLCFault.AEShelveDuration,423743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almHighHigh.BOOLS1,423840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almHighHigh.BOOLS2,423841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almHighHigh.AEBOOLS,423842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almHighHigh.INT1,423843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almHighHigh.INT2,423844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almHighHigh.AENotify,423845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almHighHigh.AESeverity,423846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almHighHigh.AEShelveDuration,423847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almHigh.BOOLS1,423852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almHigh.BOOLS2,423853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almHigh.AEBOOLS,423854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almHigh.INT1,423855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almHigh.INT2,423856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almHigh.AENotify,423857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almHigh.AESeverity,423858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almHigh.AEShelveDuration,423859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almLow.BOOLS1,423864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almLow.BOOLS2,423865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almLow.AEBOOLS,423866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almLow.INT1,423867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almLow.INT2,423868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almLow.AENotify,423869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almLow.AESeverity,423870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almLow.AEShelveDuration,423871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almLowLow.BOOLS1,423876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almLowLow.BOOLS2,423877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almLowLow.AEBOOLS,423878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almLowLow.INT1,423879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almLowLow.INT2,423880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almLowLow.AENotify,423881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almLowLow.AESeverity,423882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almLowLow.AEShelveDuration,423883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almBrokenLoop.BOOLS1,423888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almBrokenLoop.BOOLS2,423889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almBrokenLoop.AEBOOLS,423890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almBrokenLoop.INT1,423891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almBrokenLoop.INT2,423892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almBrokenLoop.AENotify,423893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almBrokenLoop.AESeverity,423894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almBrokenLoop.AEShelveDuration,423895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almOverRange.BOOLS1,423900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almOverRange.BOOLS2,423901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almOverRange.AEBOOLS,423902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almOverRange.INT1,423903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almOverRange.INT2,423904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almOverRange.AENotify,423905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almOverRange.AESeverity,423906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almOverRange.AEShelveDuration,423907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almUnderRange.BOOLS1,423912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almUnderRange.BOOLS2,423913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almUnderRange.AEBOOLS,423914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almUnderRange.INT1,423915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almUnderRange.INT2,423916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almUnderRange.AENotify,423917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almUnderRange.AESeverity,423918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almUnderRange.AEShelveDuration,423919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almRateOfChange.BOOLS1,423924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almRateOfChange.BOOLS2,423925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almRateOfChange.AEBOOLS,423926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almRateOfChange.INT1,423927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almRateOfChange.INT2,423928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almRateOfChange.AENotify,423929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almRateOfChange.AESeverity,423930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almRateOfChange.AEShelveDuration,423931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI2.almPLCFault.BOOLS1,423936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI2.almPLCFault.BOOLS2,423937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI2.almPLCFault.AEBOOLS,423938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI2.almPLCFault.INT1,423939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almPLCFault.INT2,423940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI2.almPLCFault.AENotify,423941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI2.almPLCFault.AESeverity,423942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI2.almPLCFault.AEShelveDuration,423943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almHighHigh.BOOLS1,424040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almHighHigh.BOOLS2,424041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almHighHigh.AEBOOLS,424042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almHighHigh.INT1,424043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almHighHigh.INT2,424044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almHighHigh.AENotify,424045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almHighHigh.AESeverity,424046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almHighHigh.AEShelveDuration,424047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almHigh.BOOLS1,424052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almHigh.BOOLS2,424053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almHigh.AEBOOLS,424054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almHigh.INT1,424055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almHigh.INT2,424056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almHigh.AENotify,424057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almHigh.AESeverity,424058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almHigh.AEShelveDuration,424059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almLow.BOOLS1,424064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almLow.BOOLS2,424065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almLow.AEBOOLS,424066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almLow.INT1,424067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almLow.INT2,424068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almLow.AENotify,424069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almLow.AESeverity,424070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almLow.AEShelveDuration,424071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almLowLow.BOOLS1,424076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almLowLow.BOOLS2,424077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almLowLow.AEBOOLS,424078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almLowLow.INT1,424079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almLowLow.INT2,424080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almLowLow.AENotify,424081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almLowLow.AESeverity,424082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almLowLow.AEShelveDuration,424083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almBrokenLoop.BOOLS1,424088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almBrokenLoop.BOOLS2,424089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almBrokenLoop.AEBOOLS,424090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almBrokenLoop.INT1,424091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almBrokenLoop.INT2,424092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almBrokenLoop.AENotify,424093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almBrokenLoop.AESeverity,424094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almBrokenLoop.AEShelveDuration,424095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almOverRange.BOOLS1,424100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almOverRange.BOOLS2,424101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almOverRange.AEBOOLS,424102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almOverRange.INT1,424103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almOverRange.INT2,424104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almOverRange.AENotify,424105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almOverRange.AESeverity,424106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almOverRange.AEShelveDuration,424107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almUnderRange.BOOLS1,424112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almUnderRange.BOOLS2,424113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almUnderRange.AEBOOLS,424114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almUnderRange.INT1,424115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almUnderRange.INT2,424116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almUnderRange.AENotify,424117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almUnderRange.AESeverity,424118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almUnderRange.AEShelveDuration,424119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almRateOfChange.BOOLS1,424124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almRateOfChange.BOOLS2,424125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almRateOfChange.AEBOOLS,424126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almRateOfChange.INT1,424127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almRateOfChange.INT2,424128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almRateOfChange.AENotify,424129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almRateOfChange.AESeverity,424130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almRateOfChange.AEShelveDuration,424131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI3.almPLCFault.BOOLS1,424136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI3.almPLCFault.BOOLS2,424137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI3.almPLCFault.AEBOOLS,424138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI3.almPLCFault.INT1,424139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almPLCFault.INT2,424140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI3.almPLCFault.AENotify,424141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI3.almPLCFault.AESeverity,424142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI3.almPLCFault.AEShelveDuration,424143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almHighHigh.BOOLS1,424240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almHighHigh.BOOLS2,424241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almHighHigh.AEBOOLS,424242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almHighHigh.INT1,424243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almHighHigh.INT2,424244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almHighHigh.AENotify,424245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almHighHigh.AESeverity,424246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almHighHigh.AEShelveDuration,424247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almHigh.BOOLS1,424252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almHigh.BOOLS2,424253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almHigh.AEBOOLS,424254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almHigh.INT1,424255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almHigh.INT2,424256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almHigh.AENotify,424257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almHigh.AESeverity,424258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almHigh.AEShelveDuration,424259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almLow.BOOLS1,424264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almLow.BOOLS2,424265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almLow.AEBOOLS,424266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almLow.INT1,424267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almLow.INT2,424268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almLow.AENotify,424269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almLow.AESeverity,424270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almLow.AEShelveDuration,424271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almLowLow.BOOLS1,424276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almLowLow.BOOLS2,424277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almLowLow.AEBOOLS,424278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almLowLow.INT1,424279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almLowLow.INT2,424280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almLowLow.AENotify,424281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almLowLow.AESeverity,424282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almLowLow.AEShelveDuration,424283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almBrokenLoop.BOOLS1,424288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almBrokenLoop.BOOLS2,424289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almBrokenLoop.AEBOOLS,424290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almBrokenLoop.INT1,424291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almBrokenLoop.INT2,424292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almBrokenLoop.AENotify,424293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almBrokenLoop.AESeverity,424294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almBrokenLoop.AEShelveDuration,424295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almOverRange.BOOLS1,424300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almOverRange.BOOLS2,424301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almOverRange.AEBOOLS,424302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almOverRange.INT1,424303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almOverRange.INT2,424304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almOverRange.AENotify,424305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almOverRange.AESeverity,424306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almOverRange.AEShelveDuration,424307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almUnderRange.BOOLS1,424312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almUnderRange.BOOLS2,424313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almUnderRange.AEBOOLS,424314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almUnderRange.INT1,424315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almUnderRange.INT2,424316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almUnderRange.AENotify,424317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almUnderRange.AESeverity,424318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almUnderRange.AEShelveDuration,424319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almRateOfChange.BOOLS1,424324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almRateOfChange.BOOLS2,424325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almRateOfChange.AEBOOLS,424326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almRateOfChange.INT1,424327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almRateOfChange.INT2,424328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almRateOfChange.AENotify,424329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almRateOfChange.AESeverity,424330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almRateOfChange.AEShelveDuration,424331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI4.almPLCFault.BOOLS1,424336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI4.almPLCFault.BOOLS2,424337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI4.almPLCFault.AEBOOLS,424338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI4.almPLCFault.INT1,424339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almPLCFault.INT2,424340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI4.almPLCFault.AENotify,424341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI4.almPLCFault.AESeverity,424342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI4.almPLCFault.AEShelveDuration,424343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almHighHigh.BOOLS1,424440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almHighHigh.BOOLS2,424441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almHighHigh.AEBOOLS,424442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almHighHigh.INT1,424443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almHighHigh.INT2,424444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almHighHigh.AENotify,424445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almHighHigh.AESeverity,424446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almHighHigh.AEShelveDuration,424447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almHigh.BOOLS1,424452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almHigh.BOOLS2,424453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almHigh.AEBOOLS,424454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almHigh.INT1,424455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almHigh.INT2,424456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almHigh.AENotify,424457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almHigh.AESeverity,424458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almHigh.AEShelveDuration,424459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almLow.BOOLS1,424464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almLow.BOOLS2,424465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almLow.AEBOOLS,424466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almLow.INT1,424467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almLow.INT2,424468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almLow.AENotify,424469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almLow.AESeverity,424470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almLow.AEShelveDuration,424471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almLowLow.BOOLS1,424476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almLowLow.BOOLS2,424477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almLowLow.AEBOOLS,424478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almLowLow.INT1,424479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almLowLow.INT2,424480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almLowLow.AENotify,424481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almLowLow.AESeverity,424482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almLowLow.AEShelveDuration,424483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almBrokenLoop.BOOLS1,424488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almBrokenLoop.BOOLS2,424489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almBrokenLoop.AEBOOLS,424490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almBrokenLoop.INT1,424491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almBrokenLoop.INT2,424492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almBrokenLoop.AENotify,424493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almBrokenLoop.AESeverity,424494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almBrokenLoop.AEShelveDuration,424495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almOverRange.BOOLS1,424500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almOverRange.BOOLS2,424501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almOverRange.AEBOOLS,424502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almOverRange.INT1,424503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almOverRange.INT2,424504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almOverRange.AENotify,424505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almOverRange.AESeverity,424506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almOverRange.AEShelveDuration,424507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almUnderRange.BOOLS1,424512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almUnderRange.BOOLS2,424513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almUnderRange.AEBOOLS,424514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almUnderRange.INT1,424515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almUnderRange.INT2,424516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almUnderRange.AENotify,424517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almUnderRange.AESeverity,424518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almUnderRange.AEShelveDuration,424519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almRateOfChange.BOOLS1,424524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almRateOfChange.BOOLS2,424525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almRateOfChange.AEBOOLS,424526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almRateOfChange.INT1,424527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almRateOfChange.INT2,424528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almRateOfChange.AENotify,424529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almRateOfChange.AESeverity,424530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almRateOfChange.AEShelveDuration,424531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_8_VI5.almPLCFault.BOOLS1,424536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_8_VI5.almPLCFault.BOOLS2,424537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_8_VI5.almPLCFault.AEBOOLS,424538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_8_VI5.almPLCFault.INT1,424539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almPLCFault.INT2,424540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_8_VI5.almPLCFault.AENotify,424541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_8_VI5.almPLCFault.AESeverity,424542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_8_VI5.almPLCFault.AEShelveDuration,424543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almHighHigh.BOOLS1,424640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almHighHigh.BOOLS2,424641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almHighHigh.AEBOOLS,424642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almHighHigh.INT1,424643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almHighHigh.INT2,424644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almHighHigh.AENotify,424645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almHighHigh.AESeverity,424646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almHighHigh.AEShelveDuration,424647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almHigh.BOOLS1,424652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almHigh.BOOLS2,424653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almHigh.AEBOOLS,424654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almHigh.INT1,424655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almHigh.INT2,424656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almHigh.AENotify,424657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almHigh.AESeverity,424658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almHigh.AEShelveDuration,424659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almLow.BOOLS1,424664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almLow.BOOLS2,424665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almLow.AEBOOLS,424666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almLow.INT1,424667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almLow.INT2,424668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almLow.AENotify,424669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almLow.AESeverity,424670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almLow.AEShelveDuration,424671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almLowLow.BOOLS1,424676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almLowLow.BOOLS2,424677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almLowLow.AEBOOLS,424678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almLowLow.INT1,424679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almLowLow.INT2,424680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almLowLow.AENotify,424681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almLowLow.AESeverity,424682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almLowLow.AEShelveDuration,424683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almBrokenLoop.BOOLS1,424688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almBrokenLoop.BOOLS2,424689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almBrokenLoop.AEBOOLS,424690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almBrokenLoop.INT1,424691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almBrokenLoop.INT2,424692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almBrokenLoop.AENotify,424693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almBrokenLoop.AESeverity,424694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almBrokenLoop.AEShelveDuration,424695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almOverRange.BOOLS1,424700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almOverRange.BOOLS2,424701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almOverRange.AEBOOLS,424702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almOverRange.INT1,424703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almOverRange.INT2,424704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almOverRange.AENotify,424705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almOverRange.AESeverity,424706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almOverRange.AEShelveDuration,424707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almUnderRange.BOOLS1,424712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almUnderRange.BOOLS2,424713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almUnderRange.AEBOOLS,424714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almUnderRange.INT1,424715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almUnderRange.INT2,424716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almUnderRange.AENotify,424717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almUnderRange.AESeverity,424718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almUnderRange.AEShelveDuration,424719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almRateOfChange.BOOLS1,424724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almRateOfChange.BOOLS2,424725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almRateOfChange.AEBOOLS,424726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almRateOfChange.INT1,424727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almRateOfChange.INT2,424728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almRateOfChange.AENotify,424729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almRateOfChange.AESeverity,424730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almRateOfChange.AEShelveDuration,424731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI1.almPLCFault.BOOLS1,424736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI1.almPLCFault.BOOLS2,424737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI1.almPLCFault.AEBOOLS,424738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI1.almPLCFault.INT1,424739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almPLCFault.INT2,424740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI1.almPLCFault.AENotify,424741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI1.almPLCFault.AESeverity,424742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI1.almPLCFault.AEShelveDuration,424743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almHighHigh.BOOLS1,424840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almHighHigh.BOOLS2,424841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almHighHigh.AEBOOLS,424842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almHighHigh.INT1,424843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almHighHigh.INT2,424844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almHighHigh.AENotify,424845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almHighHigh.AESeverity,424846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almHighHigh.AEShelveDuration,424847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almHigh.BOOLS1,424852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almHigh.BOOLS2,424853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almHigh.AEBOOLS,424854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almHigh.INT1,424855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almHigh.INT2,424856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almHigh.AENotify,424857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almHigh.AESeverity,424858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almHigh.AEShelveDuration,424859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almLow.BOOLS1,424864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almLow.BOOLS2,424865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almLow.AEBOOLS,424866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almLow.INT1,424867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almLow.INT2,424868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almLow.AENotify,424869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almLow.AESeverity,424870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almLow.AEShelveDuration,424871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almLowLow.BOOLS1,424876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almLowLow.BOOLS2,424877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almLowLow.AEBOOLS,424878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almLowLow.INT1,424879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almLowLow.INT2,424880,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almLowLow.AENotify,424881,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almLowLow.AESeverity,424882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almLowLow.AEShelveDuration,424883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almBrokenLoop.BOOLS1,424888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almBrokenLoop.BOOLS2,424889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almBrokenLoop.AEBOOLS,424890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almBrokenLoop.INT1,424891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almBrokenLoop.INT2,424892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almBrokenLoop.AENotify,424893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almBrokenLoop.AESeverity,424894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almBrokenLoop.AEShelveDuration,424895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almOverRange.BOOLS1,424900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almOverRange.BOOLS2,424901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almOverRange.AEBOOLS,424902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almOverRange.INT1,424903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almOverRange.INT2,424904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almOverRange.AENotify,424905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almOverRange.AESeverity,424906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almOverRange.AEShelveDuration,424907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almUnderRange.BOOLS1,424912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almUnderRange.BOOLS2,424913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almUnderRange.AEBOOLS,424914,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almUnderRange.INT1,424915,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almUnderRange.INT2,424916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almUnderRange.AENotify,424917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almUnderRange.AESeverity,424918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almUnderRange.AEShelveDuration,424919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almRateOfChange.BOOLS1,424924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almRateOfChange.BOOLS2,424925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almRateOfChange.AEBOOLS,424926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almRateOfChange.INT1,424927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almRateOfChange.INT2,424928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almRateOfChange.AENotify,424929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almRateOfChange.AESeverity,424930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almRateOfChange.AEShelveDuration,424931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI2.almPLCFault.BOOLS1,424936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI2.almPLCFault.BOOLS2,424937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI2.almPLCFault.AEBOOLS,424938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI2.almPLCFault.INT1,424939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almPLCFault.INT2,424940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI2.almPLCFault.AENotify,424941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI2.almPLCFault.AESeverity,424942,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI2.almPLCFault.AEShelveDuration,424943,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almHighHigh.BOOLS1,425040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almHighHigh.BOOLS2,425041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almHighHigh.AEBOOLS,425042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almHighHigh.INT1,425043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almHighHigh.INT2,425044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almHighHigh.AENotify,425045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almHighHigh.AESeverity,425046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almHighHigh.AEShelveDuration,425047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almHigh.BOOLS1,425052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almHigh.BOOLS2,425053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almHigh.AEBOOLS,425054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almHigh.INT1,425055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almHigh.INT2,425056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almHigh.AENotify,425057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almHigh.AESeverity,425058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almHigh.AEShelveDuration,425059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almLow.BOOLS1,425064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almLow.BOOLS2,425065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almLow.AEBOOLS,425066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almLow.INT1,425067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almLow.INT2,425068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almLow.AENotify,425069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almLow.AESeverity,425070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almLow.AEShelveDuration,425071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almLowLow.BOOLS1,425076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almLowLow.BOOLS2,425077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almLowLow.AEBOOLS,425078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almLowLow.INT1,425079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almLowLow.INT2,425080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almLowLow.AENotify,425081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almLowLow.AESeverity,425082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almLowLow.AEShelveDuration,425083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almBrokenLoop.BOOLS1,425088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almBrokenLoop.BOOLS2,425089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almBrokenLoop.AEBOOLS,425090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almBrokenLoop.INT1,425091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almBrokenLoop.INT2,425092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almBrokenLoop.AENotify,425093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almBrokenLoop.AESeverity,425094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almBrokenLoop.AEShelveDuration,425095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almOverRange.BOOLS1,425100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almOverRange.BOOLS2,425101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almOverRange.AEBOOLS,425102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almOverRange.INT1,425103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almOverRange.INT2,425104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almOverRange.AENotify,425105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almOverRange.AESeverity,425106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almOverRange.AEShelveDuration,425107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almUnderRange.BOOLS1,425112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almUnderRange.BOOLS2,425113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almUnderRange.AEBOOLS,425114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almUnderRange.INT1,425115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almUnderRange.INT2,425116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almUnderRange.AENotify,425117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almUnderRange.AESeverity,425118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almUnderRange.AEShelveDuration,425119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almRateOfChange.BOOLS1,425124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almRateOfChange.BOOLS2,425125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almRateOfChange.AEBOOLS,425126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almRateOfChange.INT1,425127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almRateOfChange.INT2,425128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almRateOfChange.AENotify,425129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almRateOfChange.AESeverity,425130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almRateOfChange.AEShelveDuration,425131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI3.almPLCFault.BOOLS1,425136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI3.almPLCFault.BOOLS2,425137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI3.almPLCFault.AEBOOLS,425138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI3.almPLCFault.INT1,425139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almPLCFault.INT2,425140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI3.almPLCFault.AENotify,425141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI3.almPLCFault.AESeverity,425142,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI3.almPLCFault.AEShelveDuration,425143,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almHighHigh.BOOLS1,425240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almHighHigh.BOOLS2,425241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almHighHigh.AEBOOLS,425242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almHighHigh.INT1,425243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almHighHigh.INT2,425244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almHighHigh.AENotify,425245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almHighHigh.AESeverity,425246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almHighHigh.AEShelveDuration,425247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almHigh.BOOLS1,425252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almHigh.BOOLS2,425253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almHigh.AEBOOLS,425254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almHigh.INT1,425255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almHigh.INT2,425256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almHigh.AENotify,425257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almHigh.AESeverity,425258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almHigh.AEShelveDuration,425259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almLow.BOOLS1,425264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almLow.BOOLS2,425265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almLow.AEBOOLS,425266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almLow.INT1,425267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almLow.INT2,425268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almLow.AENotify,425269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almLow.AESeverity,425270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almLow.AEShelveDuration,425271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almLowLow.BOOLS1,425276,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almLowLow.BOOLS2,425277,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almLowLow.AEBOOLS,425278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almLowLow.INT1,425279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almLowLow.INT2,425280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almLowLow.AENotify,425281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almLowLow.AESeverity,425282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almLowLow.AEShelveDuration,425283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almBrokenLoop.BOOLS1,425288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almBrokenLoop.BOOLS2,425289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almBrokenLoop.AEBOOLS,425290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almBrokenLoop.INT1,425291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almBrokenLoop.INT2,425292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almBrokenLoop.AENotify,425293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almBrokenLoop.AESeverity,425294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almBrokenLoop.AEShelveDuration,425295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almOverRange.BOOLS1,425300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almOverRange.BOOLS2,425301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almOverRange.AEBOOLS,425302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almOverRange.INT1,425303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almOverRange.INT2,425304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almOverRange.AENotify,425305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almOverRange.AESeverity,425306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almOverRange.AEShelveDuration,425307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almUnderRange.BOOLS1,425312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almUnderRange.BOOLS2,425313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almUnderRange.AEBOOLS,425314,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almUnderRange.INT1,425315,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almUnderRange.INT2,425316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almUnderRange.AENotify,425317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almUnderRange.AESeverity,425318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almUnderRange.AEShelveDuration,425319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almRateOfChange.BOOLS1,425324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almRateOfChange.BOOLS2,425325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almRateOfChange.AEBOOLS,425326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almRateOfChange.INT1,425327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almRateOfChange.INT2,425328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almRateOfChange.AENotify,425329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almRateOfChange.AESeverity,425330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almRateOfChange.AEShelveDuration,425331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI4.almPLCFault.BOOLS1,425336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI4.almPLCFault.BOOLS2,425337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI4.almPLCFault.AEBOOLS,425338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI4.almPLCFault.INT1,425339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almPLCFault.INT2,425340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI4.almPLCFault.AENotify,425341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI4.almPLCFault.AESeverity,425342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI4.almPLCFault.AEShelveDuration,425343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almHighHigh.BOOLS1,425440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almHighHigh.BOOLS2,425441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almHighHigh.AEBOOLS,425442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almHighHigh.INT1,425443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almHighHigh.INT2,425444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almHighHigh.AENotify,425445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almHighHigh.AESeverity,425446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almHighHigh.AEShelveDuration,425447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almHigh.BOOLS1,425452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almHigh.BOOLS2,425453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almHigh.AEBOOLS,425454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almHigh.INT1,425455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almHigh.INT2,425456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almHigh.AENotify,425457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almHigh.AESeverity,425458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almHigh.AEShelveDuration,425459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almLow.BOOLS1,425464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almLow.BOOLS2,425465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almLow.AEBOOLS,425466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almLow.INT1,425467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almLow.INT2,425468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almLow.AENotify,425469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almLow.AESeverity,425470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almLow.AEShelveDuration,425471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almLowLow.BOOLS1,425476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almLowLow.BOOLS2,425477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almLowLow.AEBOOLS,425478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almLowLow.INT1,425479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almLowLow.INT2,425480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almLowLow.AENotify,425481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almLowLow.AESeverity,425482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almLowLow.AEShelveDuration,425483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almBrokenLoop.BOOLS1,425488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almBrokenLoop.BOOLS2,425489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almBrokenLoop.AEBOOLS,425490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almBrokenLoop.INT1,425491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almBrokenLoop.INT2,425492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almBrokenLoop.AENotify,425493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almBrokenLoop.AESeverity,425494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almBrokenLoop.AEShelveDuration,425495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almOverRange.BOOLS1,425500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almOverRange.BOOLS2,425501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almOverRange.AEBOOLS,425502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almOverRange.INT1,425503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almOverRange.INT2,425504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almOverRange.AENotify,425505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almOverRange.AESeverity,425506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almOverRange.AEShelveDuration,425507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almUnderRange.BOOLS1,425512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almUnderRange.BOOLS2,425513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almUnderRange.AEBOOLS,425514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almUnderRange.INT1,425515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almUnderRange.INT2,425516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almUnderRange.AENotify,425517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almUnderRange.AESeverity,425518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almUnderRange.AEShelveDuration,425519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almRateOfChange.BOOLS1,425524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almRateOfChange.BOOLS2,425525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almRateOfChange.AEBOOLS,425526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almRateOfChange.INT1,425527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almRateOfChange.INT2,425528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almRateOfChange.AENotify,425529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almRateOfChange.AESeverity,425530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almRateOfChange.AEShelveDuration,425531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PMP_0103_9_VI5.almPLCFault.BOOLS1,425536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PMP_0103_9_VI5.almPLCFault.BOOLS2,425537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PMP_0103_9_VI5.almPLCFault.AEBOOLS,425538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PMP_0103_9_VI5.almPLCFault.INT1,425539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almPLCFault.INT2,425540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PMP_0103_9_VI5.almPLCFault.AENotify,425541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PMP_0103_9_VI5.almPLCFault.AESeverity,425542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PMP_0103_9_VI5.almPLCFault.AEShelveDuration,425543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almHighHigh.BOOLS1,425640,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almHighHigh.BOOLS2,425641,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almHighHigh.AEBOOLS,425642,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almHighHigh.INT1,425643,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almHighHigh.INT2,425644,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almHighHigh.AENotify,425645,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almHighHigh.AESeverity,425646,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almHighHigh.AEShelveDuration,425647,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almHigh.BOOLS1,425652,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almHigh.BOOLS2,425653,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almHigh.AEBOOLS,425654,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almHigh.INT1,425655,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almHigh.INT2,425656,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almHigh.AENotify,425657,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almHigh.AESeverity,425658,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almHigh.AEShelveDuration,425659,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almLow.BOOLS1,425664,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almLow.BOOLS2,425665,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almLow.AEBOOLS,425666,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almLow.INT1,425667,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almLow.INT2,425668,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almLow.AENotify,425669,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almLow.AESeverity,425670,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almLow.AEShelveDuration,425671,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almLowLow.BOOLS1,425676,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almLowLow.BOOLS2,425677,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almLowLow.AEBOOLS,425678,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almLowLow.INT1,425679,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almLowLow.INT2,425680,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almLowLow.AENotify,425681,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almLowLow.AESeverity,425682,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almLowLow.AEShelveDuration,425683,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almBrokenLoop.BOOLS1,425688,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almBrokenLoop.BOOLS2,425689,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almBrokenLoop.AEBOOLS,425690,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almBrokenLoop.INT1,425691,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almBrokenLoop.INT2,425692,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almBrokenLoop.AENotify,425693,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almBrokenLoop.AESeverity,425694,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almBrokenLoop.AEShelveDuration,425695,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almOverRange.BOOLS1,425700,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almOverRange.BOOLS2,425701,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almOverRange.AEBOOLS,425702,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almOverRange.INT1,425703,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almOverRange.INT2,425704,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almOverRange.AENotify,425705,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almOverRange.AESeverity,425706,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almOverRange.AEShelveDuration,425707,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almUnderRange.BOOLS1,425712,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almUnderRange.BOOLS2,425713,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almUnderRange.AEBOOLS,425714,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almUnderRange.INT1,425715,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almUnderRange.INT2,425716,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almUnderRange.AENotify,425717,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almUnderRange.AESeverity,425718,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almUnderRange.AEShelveDuration,425719,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almRateOfChange.BOOLS1,425724,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almRateOfChange.BOOLS2,425725,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almRateOfChange.AEBOOLS,425726,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almRateOfChange.INT1,425727,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almRateOfChange.INT2,425728,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almRateOfChange.AENotify,425729,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almRateOfChange.AESeverity,425730,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almRateOfChange.AEShelveDuration,425731,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0111_1_TI.almPLCFault.BOOLS1,425736,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0111_1_TI.almPLCFault.BOOLS2,425737,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0111_1_TI.almPLCFault.AEBOOLS,425738,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0111_1_TI.almPLCFault.INT1,425739,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almPLCFault.INT2,425740,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0111_1_TI.almPLCFault.AENotify,425741,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0111_1_TI.almPLCFault.AESeverity,425742,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0111_1_TI.almPLCFault.AEShelveDuration,425743,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almHighHigh.BOOLS1,425840,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almHighHigh.BOOLS2,425841,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almHighHigh.AEBOOLS,425842,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almHighHigh.INT1,425843,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almHighHigh.INT2,425844,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almHighHigh.AENotify,425845,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almHighHigh.AESeverity,425846,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almHighHigh.AEShelveDuration,425847,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almHigh.BOOLS1,425852,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almHigh.BOOLS2,425853,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almHigh.AEBOOLS,425854,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almHigh.INT1,425855,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almHigh.INT2,425856,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almHigh.AENotify,425857,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almHigh.AESeverity,425858,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almHigh.AEShelveDuration,425859,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almLow.BOOLS1,425864,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almLow.BOOLS2,425865,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almLow.AEBOOLS,425866,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almLow.INT1,425867,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almLow.INT2,425868,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almLow.AENotify,425869,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almLow.AESeverity,425870,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almLow.AEShelveDuration,425871,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almLowLow.BOOLS1,425876,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almLowLow.BOOLS2,425877,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almLowLow.AEBOOLS,425878,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almLowLow.INT1,425879,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almLowLow.INT2,425880,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almLowLow.AENotify,425881,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almLowLow.AESeverity,425882,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almLowLow.AEShelveDuration,425883,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almBrokenLoop.BOOLS1,425888,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almBrokenLoop.BOOLS2,425889,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almBrokenLoop.AEBOOLS,425890,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almBrokenLoop.INT1,425891,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almBrokenLoop.INT2,425892,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almBrokenLoop.AENotify,425893,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almBrokenLoop.AESeverity,425894,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almBrokenLoop.AEShelveDuration,425895,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almOverRange.BOOLS1,425900,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almOverRange.BOOLS2,425901,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almOverRange.AEBOOLS,425902,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almOverRange.INT1,425903,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almOverRange.INT2,425904,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almOverRange.AENotify,425905,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almOverRange.AESeverity,425906,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almOverRange.AEShelveDuration,425907,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almUnderRange.BOOLS1,425912,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almUnderRange.BOOLS2,425913,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almUnderRange.AEBOOLS,425914,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almUnderRange.INT1,425915,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almUnderRange.INT2,425916,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almUnderRange.AENotify,425917,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almUnderRange.AESeverity,425918,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almUnderRange.AEShelveDuration,425919,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almRateOfChange.BOOLS1,425924,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almRateOfChange.BOOLS2,425925,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almRateOfChange.AEBOOLS,425926,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almRateOfChange.INT1,425927,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almRateOfChange.INT2,425928,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almRateOfChange.AENotify,425929,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almRateOfChange.AESeverity,425930,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almRateOfChange.AEShelveDuration,425931,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TT_0112_1_TI.almPLCFault.BOOLS1,425936,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TT_0112_1_TI.almPLCFault.BOOLS2,425937,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TT_0112_1_TI.almPLCFault.AEBOOLS,425938,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TT_0112_1_TI.almPLCFault.INT1,425939,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almPLCFault.INT2,425940,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TT_0112_1_TI.almPLCFault.AENotify,425941,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TT_0112_1_TI.almPLCFault.AESeverity,425942,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TT_0112_1_TI.almPLCFault.AEShelveDuration,425943,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_FA.Alarm.BOOLS1,426006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_FA.Alarm.BOOLS2,426007,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_FA.Alarm.AEBOOLS,426008,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_FA.Alarm.INT1,426009,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_FA.Alarm.INT2,426010,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_FA.Alarm.AENotify,426011,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_FA.Alarm.AESeverity,426012,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_FA.Alarm.AEShelveDuration,426013,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_FA.almPLCFault.BOOLS1,426018,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_FA.almPLCFault.BOOLS2,426019,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_FA.almPLCFault.AEBOOLS,426020,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_FA.almPLCFault.INT1,426021,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_FA.almPLCFault.INT2,426022,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_FA.almPLCFault.AENotify,426023,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_FA.almPLCFault.AESeverity,426024,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_FA.almPLCFault.AEShelveDuration,426025,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_MF.Alarm.BOOLS1,426042,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_MF.Alarm.BOOLS2,426043,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_MF.Alarm.AEBOOLS,426044,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_MF.Alarm.INT1,426045,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MF.Alarm.INT2,426046,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MF.Alarm.AENotify,426047,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_MF.Alarm.AESeverity,426048,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_MF.Alarm.AEShelveDuration,426049,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_MF.almPLCFault.BOOLS1,426054,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_MF.almPLCFault.BOOLS2,426055,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_MF.almPLCFault.AEBOOLS,426056,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_MF.almPLCFault.INT1,426057,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MF.almPLCFault.INT2,426058,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MF.almPLCFault.AENotify,426059,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_MF.almPLCFault.AESeverity,426060,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_MF.almPLCFault.AEShelveDuration,426061,Short,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_MY.Alarm.BOOLS1,426076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_MY.Alarm.BOOLS2,426077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_MY.Alarm.AEBOOLS,426078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_MY.Alarm.INT1,426079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MY.Alarm.INT2,426080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MY.Alarm.AENotify,426081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_MY.Alarm.AESeverity,426082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_MY.Alarm.AEShelveDuration,426083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_MY.almPLCFault.BOOLS1,426088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_MY.almPLCFault.BOOLS2,426089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_MY.almPLCFault.AEBOOLS,426090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_MY.almPLCFault.INT1,426091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MY.almPLCFault.INT2,426092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_MY.almPLCFault.AENotify,426093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_MY.almPLCFault.AESeverity,426094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_MY.almPLCFault.AEShelveDuration,426095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UA.Alarm.BOOLS1,426112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UA.Alarm.BOOLS2,426113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UA.Alarm.AEBOOLS,426114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UA.Alarm.INT1,426115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UA.Alarm.INT2,426116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UA.Alarm.AENotify,426117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UA.Alarm.AESeverity,426118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UA.Alarm.AEShelveDuration,426119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UA.almPLCFault.BOOLS1,426124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UA.almPLCFault.BOOLS2,426125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UA.almPLCFault.AEBOOLS,426126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UA.almPLCFault.INT1,426127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UA.almPLCFault.INT2,426128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UA.almPLCFault.AENotify,426129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UA.almPLCFault.AESeverity,426130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UA.almPLCFault.AEShelveDuration,426131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UH.Alarm.BOOLS1,426146,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UH.Alarm.BOOLS2,426147,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UH.Alarm.AEBOOLS,426148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UH.Alarm.INT1,426149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UH.Alarm.INT2,426150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UH.Alarm.AENotify,426151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UH.Alarm.AESeverity,426152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UH.Alarm.AEShelveDuration,426153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UH.almPLCFault.BOOLS1,426158,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UH.almPLCFault.BOOLS2,426159,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UH.almPLCFault.AEBOOLS,426160,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UH.almPLCFault.INT1,426161,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UH.almPLCFault.INT2,426162,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UH.almPLCFault.AENotify,426163,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UH.almPLCFault.AESeverity,426164,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UH.almPLCFault.AEShelveDuration,426165,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UY.Alarm.BOOLS1,426182,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UY.Alarm.BOOLS2,426183,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UY.Alarm.AEBOOLS,426184,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UY.Alarm.INT1,426185,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UY.Alarm.INT2,426186,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UY.Alarm.AENotify,426187,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UY.Alarm.AESeverity,426188,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UY.Alarm.AEShelveDuration,426189,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_UY.almPLCFault.BOOLS1,426194,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_UY.almPLCFault.BOOLS2,426195,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_UY.almPLCFault.AEBOOLS,426196,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_UY.almPLCFault.INT1,426197,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UY.almPLCFault.INT2,426198,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_UY.almPLCFault.AENotify,426199,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_UY.almPLCFault.AESeverity,426200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_UY.almPLCFault.AEShelveDuration,426201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_XF.Alarm.BOOLS1,426216,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_XF.Alarm.BOOLS2,426217,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_XF.Alarm.AEBOOLS,426218,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_XF.Alarm.INT1,426219,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_XF.Alarm.INT2,426220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_XF.Alarm.AENotify,426221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_XF.Alarm.AESeverity,426222,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_XF.Alarm.AEShelveDuration,426223,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_XF.almPLCFault.BOOLS1,426228,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_XF.almPLCFault.BOOLS2,426229,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_XF.almPLCFault.AEBOOLS,426230,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_XF.almPLCFault.INT1,426231,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_XF.almPLCFault.INT2,426232,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_XF.almPLCFault.AENotify,426233,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_XF.almPLCFault.AESeverity,426234,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_XF.almPLCFault.AEShelveDuration,426235,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_YA.Alarm.BOOLS1,426252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_YA.Alarm.BOOLS2,426253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_YA.Alarm.AEBOOLS,426254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_YA.Alarm.INT1,426255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_YA.Alarm.INT2,426256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_YA.Alarm.AENotify,426257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_YA.Alarm.AESeverity,426258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_YA.Alarm.AEShelveDuration,426259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_YA.almPLCFault.BOOLS1,426264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1_YA.almPLCFault.BOOLS2,426265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1_YA.almPLCFault.AEBOOLS,426266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1_YA.almPLCFault.INT1,426267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_YA.almPLCFault.INT2,426268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1_YA.almPLCFault.AENotify,426269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1_YA.almPLCFault.AESeverity,426270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1_YA.almPLCFault.AEShelveDuration,426271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_FA.Alarm.BOOLS1,426286,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_FA.Alarm.BOOLS2,426287,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_FA.Alarm.AEBOOLS,426288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_FA.Alarm.INT1,426289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_FA.Alarm.INT2,426290,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_FA.Alarm.AENotify,426291,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_FA.Alarm.AESeverity,426292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_FA.Alarm.AEShelveDuration,426293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_FA.almPLCFault.BOOLS1,426298,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_FA.almPLCFault.BOOLS2,426299,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_FA.almPLCFault.AEBOOLS,426300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_FA.almPLCFault.INT1,426301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_FA.almPLCFault.INT2,426302,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_FA.almPLCFault.AENotify,426303,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_FA.almPLCFault.AESeverity,426304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_FA.almPLCFault.AEShelveDuration,426305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_MF.Alarm.BOOLS1,426322,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_MF.Alarm.BOOLS2,426323,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_MF.Alarm.AEBOOLS,426324,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_MF.Alarm.INT1,426325,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MF.Alarm.INT2,426326,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MF.Alarm.AENotify,426327,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_MF.Alarm.AESeverity,426328,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_MF.Alarm.AEShelveDuration,426329,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_MF.almPLCFault.BOOLS1,426334,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_MF.almPLCFault.BOOLS2,426335,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_MF.almPLCFault.AEBOOLS,426336,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_MF.almPLCFault.INT1,426337,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MF.almPLCFault.INT2,426338,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MF.almPLCFault.AENotify,426339,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_MF.almPLCFault.AESeverity,426340,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_MF.almPLCFault.AEShelveDuration,426341,Short,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_MY.Alarm.BOOLS1,426356,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_MY.Alarm.BOOLS2,426357,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_MY.Alarm.AEBOOLS,426358,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_MY.Alarm.INT1,426359,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MY.Alarm.INT2,426360,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MY.Alarm.AENotify,426361,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_MY.Alarm.AESeverity,426362,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_MY.Alarm.AEShelveDuration,426363,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_MY.almPLCFault.BOOLS1,426368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_MY.almPLCFault.BOOLS2,426369,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_MY.almPLCFault.AEBOOLS,426370,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_MY.almPLCFault.INT1,426371,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MY.almPLCFault.INT2,426372,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_MY.almPLCFault.AENotify,426373,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_MY.almPLCFault.AESeverity,426374,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_MY.almPLCFault.AEShelveDuration,426375,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UA.Alarm.BOOLS1,426392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UA.Alarm.BOOLS2,426393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UA.Alarm.AEBOOLS,426394,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UA.Alarm.INT1,426395,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UA.Alarm.INT2,426396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UA.Alarm.AENotify,426397,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UA.Alarm.AESeverity,426398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UA.Alarm.AEShelveDuration,426399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UA.almPLCFault.BOOLS1,426404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UA.almPLCFault.BOOLS2,426405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UA.almPLCFault.AEBOOLS,426406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UA.almPLCFault.INT1,426407,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UA.almPLCFault.INT2,426408,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UA.almPLCFault.AENotify,426409,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UA.almPLCFault.AESeverity,426410,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UA.almPLCFault.AEShelveDuration,426411,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UH.Alarm.BOOLS1,426426,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UH.Alarm.BOOLS2,426427,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UH.Alarm.AEBOOLS,426428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UH.Alarm.INT1,426429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UH.Alarm.INT2,426430,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UH.Alarm.AENotify,426431,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UH.Alarm.AESeverity,426432,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UH.Alarm.AEShelveDuration,426433,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UH.almPLCFault.BOOLS1,426438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UH.almPLCFault.BOOLS2,426439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UH.almPLCFault.AEBOOLS,426440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UH.almPLCFault.INT1,426441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UH.almPLCFault.INT2,426442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UH.almPLCFault.AENotify,426443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UH.almPLCFault.AESeverity,426444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UH.almPLCFault.AEShelveDuration,426445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UY.Alarm.BOOLS1,426462,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UY.Alarm.BOOLS2,426463,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UY.Alarm.AEBOOLS,426464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UY.Alarm.INT1,426465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UY.Alarm.INT2,426466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UY.Alarm.AENotify,426467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UY.Alarm.AESeverity,426468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UY.Alarm.AEShelveDuration,426469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_UY.almPLCFault.BOOLS1,426474,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_UY.almPLCFault.BOOLS2,426475,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_UY.almPLCFault.AEBOOLS,426476,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_UY.almPLCFault.INT1,426477,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UY.almPLCFault.INT2,426478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_UY.almPLCFault.AENotify,426479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_UY.almPLCFault.AESeverity,426480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_UY.almPLCFault.AEShelveDuration,426481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_XF.Alarm.BOOLS1,426496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_XF.Alarm.BOOLS2,426497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_XF.Alarm.AEBOOLS,426498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_XF.Alarm.INT1,426499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_XF.Alarm.INT2,426500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_XF.Alarm.AENotify,426501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_XF.Alarm.AESeverity,426502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_XF.Alarm.AEShelveDuration,426503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_XF.almPLCFault.BOOLS1,426508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_XF.almPLCFault.BOOLS2,426509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_XF.almPLCFault.AEBOOLS,426510,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_XF.almPLCFault.INT1,426511,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_XF.almPLCFault.INT2,426512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_XF.almPLCFault.AENotify,426513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_XF.almPLCFault.AESeverity,426514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_XF.almPLCFault.AEShelveDuration,426515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_YA.Alarm.BOOLS1,426532,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_YA.Alarm.BOOLS2,426533,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_YA.Alarm.AEBOOLS,426534,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_YA.Alarm.INT1,426535,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_YA.Alarm.INT2,426536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_YA.Alarm.AENotify,426537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_YA.Alarm.AESeverity,426538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_YA.Alarm.AEShelveDuration,426539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2_YA.almPLCFault.BOOLS1,426544,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2_YA.almPLCFault.BOOLS2,426545,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2_YA.almPLCFault.AEBOOLS,426546,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2_YA.almPLCFault.INT1,426547,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_YA.almPLCFault.INT2,426548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2_YA.almPLCFault.AENotify,426549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2_YA.almPLCFault.AESeverity,426550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2_YA.almPLCFault.AEShelveDuration,426551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_FA.Alarm.BOOLS1,426566,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_FA.Alarm.BOOLS2,426567,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_FA.Alarm.AEBOOLS,426568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_FA.Alarm.INT1,426569,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_FA.Alarm.INT2,426570,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_FA.Alarm.AENotify,426571,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_FA.Alarm.AESeverity,426572,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_FA.Alarm.AEShelveDuration,426573,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_FA.almPLCFault.BOOLS1,426578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_FA.almPLCFault.BOOLS2,426579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_FA.almPLCFault.AEBOOLS,426580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_FA.almPLCFault.INT1,426581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_FA.almPLCFault.INT2,426582,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_FA.almPLCFault.AENotify,426583,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_FA.almPLCFault.AESeverity,426584,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_FA.almPLCFault.AEShelveDuration,426585,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_MF.Alarm.BOOLS1,426602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_MF.Alarm.BOOLS2,426603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_MF.Alarm.AEBOOLS,426604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_MF.Alarm.INT1,426605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MF.Alarm.INT2,426606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MF.Alarm.AENotify,426607,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_MF.Alarm.AESeverity,426608,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_MF.Alarm.AEShelveDuration,426609,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_MF.almPLCFault.BOOLS1,426614,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_MF.almPLCFault.BOOLS2,426615,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_MF.almPLCFault.AEBOOLS,426616,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_MF.almPLCFault.INT1,426617,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MF.almPLCFault.INT2,426618,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MF.almPLCFault.AENotify,426619,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_MF.almPLCFault.AESeverity,426620,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_MF.almPLCFault.AEShelveDuration,426621,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_MY.Alarm.BOOLS1,426636,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_MY.Alarm.BOOLS2,426637,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_MY.Alarm.AEBOOLS,426638,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_MY.Alarm.INT1,426639,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MY.Alarm.INT2,426640,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MY.Alarm.AENotify,426641,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_MY.Alarm.AESeverity,426642,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_MY.Alarm.AEShelveDuration,426643,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_MY.almPLCFault.BOOLS1,426648,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_MY.almPLCFault.BOOLS2,426649,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_MY.almPLCFault.AEBOOLS,426650,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_MY.almPLCFault.INT1,426651,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MY.almPLCFault.INT2,426652,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_MY.almPLCFault.AENotify,426653,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_MY.almPLCFault.AESeverity,426654,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_MY.almPLCFault.AEShelveDuration,426655,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UA.Alarm.BOOLS1,426672,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UA.Alarm.BOOLS2,426673,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UA.Alarm.AEBOOLS,426674,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UA.Alarm.INT1,426675,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UA.Alarm.INT2,426676,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UA.Alarm.AENotify,426677,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UA.Alarm.AESeverity,426678,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UA.Alarm.AEShelveDuration,426679,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UA.almPLCFault.BOOLS1,426684,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UA.almPLCFault.BOOLS2,426685,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UA.almPLCFault.AEBOOLS,426686,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UA.almPLCFault.INT1,426687,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UA.almPLCFault.INT2,426688,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UA.almPLCFault.AENotify,426689,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UA.almPLCFault.AESeverity,426690,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UA.almPLCFault.AEShelveDuration,426691,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UH.Alarm.BOOLS1,426706,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UH.Alarm.BOOLS2,426707,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UH.Alarm.AEBOOLS,426708,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UH.Alarm.INT1,426709,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UH.Alarm.INT2,426710,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UH.Alarm.AENotify,426711,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UH.Alarm.AESeverity,426712,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UH.Alarm.AEShelveDuration,426713,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UH.almPLCFault.BOOLS1,426718,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UH.almPLCFault.BOOLS2,426719,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UH.almPLCFault.AEBOOLS,426720,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UH.almPLCFault.INT1,426721,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UH.almPLCFault.INT2,426722,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UH.almPLCFault.AENotify,426723,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UH.almPLCFault.AESeverity,426724,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UH.almPLCFault.AEShelveDuration,426725,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UY.Alarm.BOOLS1,426742,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UY.Alarm.BOOLS2,426743,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UY.Alarm.AEBOOLS,426744,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UY.Alarm.INT1,426745,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UY.Alarm.INT2,426746,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UY.Alarm.AENotify,426747,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UY.Alarm.AESeverity,426748,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UY.Alarm.AEShelveDuration,426749,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_UY.almPLCFault.BOOLS1,426754,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_UY.almPLCFault.BOOLS2,426755,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_UY.almPLCFault.AEBOOLS,426756,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_UY.almPLCFault.INT1,426757,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UY.almPLCFault.INT2,426758,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_UY.almPLCFault.AENotify,426759,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_UY.almPLCFault.AESeverity,426760,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_UY.almPLCFault.AEShelveDuration,426761,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_XF.Alarm.BOOLS1,426776,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_XF.Alarm.BOOLS2,426777,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_XF.Alarm.AEBOOLS,426778,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_XF.Alarm.INT1,426779,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_XF.Alarm.INT2,426780,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_XF.Alarm.AENotify,426781,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_XF.Alarm.AESeverity,426782,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_XF.Alarm.AEShelveDuration,426783,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_XF.almPLCFault.BOOLS1,426788,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_XF.almPLCFault.BOOLS2,426789,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_XF.almPLCFault.AEBOOLS,426790,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_XF.almPLCFault.INT1,426791,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_XF.almPLCFault.INT2,426792,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_XF.almPLCFault.AENotify,426793,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_XF.almPLCFault.AESeverity,426794,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_XF.almPLCFault.AEShelveDuration,426795,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_YA.Alarm.BOOLS1,426812,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_YA.Alarm.BOOLS2,426813,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_YA.Alarm.AEBOOLS,426814,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_YA.Alarm.INT1,426815,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_YA.Alarm.INT2,426816,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_YA.Alarm.AENotify,426817,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_YA.Alarm.AESeverity,426818,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_YA.Alarm.AEShelveDuration,426819,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3_YA.almPLCFault.BOOLS1,426824,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3_YA.almPLCFault.BOOLS2,426825,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3_YA.almPLCFault.AEBOOLS,426826,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3_YA.almPLCFault.INT1,426827,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_YA.almPLCFault.INT2,426828,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3_YA.almPLCFault.AENotify,426829,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3_YA.almPLCFault.AESeverity,426830,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3_YA.almPLCFault.AEShelveDuration,426831,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_FA.Alarm.BOOLS1,426846,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_FA.Alarm.BOOLS2,426847,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_FA.Alarm.AEBOOLS,426848,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_FA.Alarm.INT1,426849,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_FA.Alarm.INT2,426850,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_FA.Alarm.AENotify,426851,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_FA.Alarm.AESeverity,426852,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_FA.Alarm.AEShelveDuration,426853,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_FA.almPLCFault.BOOLS1,426858,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_FA.almPLCFault.BOOLS2,426859,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_FA.almPLCFault.AEBOOLS,426860,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_FA.almPLCFault.INT1,426861,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_FA.almPLCFault.INT2,426862,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_FA.almPLCFault.AENotify,426863,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_FA.almPLCFault.AESeverity,426864,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_FA.almPLCFault.AEShelveDuration,426865,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_MF.Alarm.BOOLS1,426882,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_MF.Alarm.BOOLS2,426883,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_MF.Alarm.AEBOOLS,426884,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_MF.Alarm.INT1,426885,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MF.Alarm.INT2,426886,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MF.Alarm.AENotify,426887,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_MF.Alarm.AESeverity,426888,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_MF.Alarm.AEShelveDuration,426889,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_MF.almPLCFault.BOOLS1,426894,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_MF.almPLCFault.BOOLS2,426895,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_MF.almPLCFault.AEBOOLS,426896,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_MF.almPLCFault.INT1,426897,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MF.almPLCFault.INT2,426898,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MF.almPLCFault.AENotify,426899,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_MF.almPLCFault.AESeverity,426900,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_MF.almPLCFault.AEShelveDuration,426901,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_MY.Alarm.BOOLS1,426916,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_MY.Alarm.BOOLS2,426917,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_MY.Alarm.AEBOOLS,426918,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_MY.Alarm.INT1,426919,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MY.Alarm.INT2,426920,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MY.Alarm.AENotify,426921,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_MY.Alarm.AESeverity,426922,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_MY.Alarm.AEShelveDuration,426923,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_MY.almPLCFault.BOOLS1,426928,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_MY.almPLCFault.BOOLS2,426929,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_MY.almPLCFault.AEBOOLS,426930,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_MY.almPLCFault.INT1,426931,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MY.almPLCFault.INT2,426932,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_MY.almPLCFault.AENotify,426933,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_MY.almPLCFault.AESeverity,426934,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_MY.almPLCFault.AEShelveDuration,426935,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UA.Alarm.BOOLS1,426952,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UA.Alarm.BOOLS2,426953,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UA.Alarm.AEBOOLS,426954,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UA.Alarm.INT1,426955,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UA.Alarm.INT2,426956,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UA.Alarm.AENotify,426957,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UA.Alarm.AESeverity,426958,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UA.Alarm.AEShelveDuration,426959,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UA.almPLCFault.BOOLS1,426964,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UA.almPLCFault.BOOLS2,426965,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UA.almPLCFault.AEBOOLS,426966,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UA.almPLCFault.INT1,426967,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UA.almPLCFault.INT2,426968,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UA.almPLCFault.AENotify,426969,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UA.almPLCFault.AESeverity,426970,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UA.almPLCFault.AEShelveDuration,426971,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UH.Alarm.BOOLS1,426986,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UH.Alarm.BOOLS2,426987,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UH.Alarm.AEBOOLS,426988,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UH.Alarm.INT1,426989,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UH.Alarm.INT2,426990,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UH.Alarm.AENotify,426991,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UH.Alarm.AESeverity,426992,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UH.Alarm.AEShelveDuration,426993,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UH.almPLCFault.BOOLS1,426998,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UH.almPLCFault.BOOLS2,426999,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UH.almPLCFault.AEBOOLS,427000,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UH.almPLCFault.INT1,427001,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UH.almPLCFault.INT2,427002,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UH.almPLCFault.AENotify,427003,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UH.almPLCFault.AESeverity,427004,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UH.almPLCFault.AEShelveDuration,427005,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UY.Alarm.BOOLS1,427022,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UY.Alarm.BOOLS2,427023,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UY.Alarm.AEBOOLS,427024,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UY.Alarm.INT1,427025,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UY.Alarm.INT2,427026,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UY.Alarm.AENotify,427027,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UY.Alarm.AESeverity,427028,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UY.Alarm.AEShelveDuration,427029,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_UY.almPLCFault.BOOLS1,427034,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_UY.almPLCFault.BOOLS2,427035,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_UY.almPLCFault.AEBOOLS,427036,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_UY.almPLCFault.INT1,427037,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UY.almPLCFault.INT2,427038,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_UY.almPLCFault.AENotify,427039,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_UY.almPLCFault.AESeverity,427040,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_UY.almPLCFault.AEShelveDuration,427041,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_XF.Alarm.BOOLS1,427056,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_XF.Alarm.BOOLS2,427057,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_XF.Alarm.AEBOOLS,427058,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_XF.Alarm.INT1,427059,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_XF.Alarm.INT2,427060,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_XF.Alarm.AENotify,427061,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_XF.Alarm.AESeverity,427062,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_XF.Alarm.AEShelveDuration,427063,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_XF.almPLCFault.BOOLS1,427068,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_XF.almPLCFault.BOOLS2,427069,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_XF.almPLCFault.AEBOOLS,427070,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_XF.almPLCFault.INT1,427071,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_XF.almPLCFault.INT2,427072,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_XF.almPLCFault.AENotify,427073,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_XF.almPLCFault.AESeverity,427074,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_XF.almPLCFault.AEShelveDuration,427075,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_YA.Alarm.BOOLS1,427092,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_YA.Alarm.BOOLS2,427093,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_YA.Alarm.AEBOOLS,427094,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_YA.Alarm.INT1,427095,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_YA.Alarm.INT2,427096,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_YA.Alarm.AENotify,427097,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_YA.Alarm.AESeverity,427098,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_YA.Alarm.AEShelveDuration,427099,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4_YA.almPLCFault.BOOLS1,427104,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4_YA.almPLCFault.BOOLS2,427105,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4_YA.almPLCFault.AEBOOLS,427106,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4_YA.almPLCFault.INT1,427107,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_YA.almPLCFault.INT2,427108,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4_YA.almPLCFault.AENotify,427109,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4_YA.almPLCFault.AESeverity,427110,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4_YA.almPLCFault.AEShelveDuration,427111,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_FA.Alarm.BOOLS1,427126,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_FA.Alarm.BOOLS2,427127,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_FA.Alarm.AEBOOLS,427128,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_FA.Alarm.INT1,427129,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_FA.Alarm.INT2,427130,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_FA.Alarm.AENotify,427131,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_FA.Alarm.AESeverity,427132,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_FA.Alarm.AEShelveDuration,427133,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_FA.almPLCFault.BOOLS1,427138,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_FA.almPLCFault.BOOLS2,427139,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_FA.almPLCFault.AEBOOLS,427140,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_FA.almPLCFault.INT1,427141,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_FA.almPLCFault.INT2,427142,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_FA.almPLCFault.AENotify,427143,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_FA.almPLCFault.AESeverity,427144,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_FA.almPLCFault.AEShelveDuration,427145,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_MF.Alarm.BOOLS1,427162,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_MF.Alarm.BOOLS2,427163,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_MF.Alarm.AEBOOLS,427164,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_MF.Alarm.INT1,427165,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MF.Alarm.INT2,427166,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MF.Alarm.AENotify,427167,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_MF.Alarm.AESeverity,427168,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_MF.Alarm.AEShelveDuration,427169,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_MF.almPLCFault.BOOLS1,427174,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_MF.almPLCFault.BOOLS2,427175,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_MF.almPLCFault.AEBOOLS,427176,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_MF.almPLCFault.INT1,427177,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MF.almPLCFault.INT2,427178,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MF.almPLCFault.AENotify,427179,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_MF.almPLCFault.AESeverity,427180,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_MF.almPLCFault.AEShelveDuration,427181,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_MY.Alarm.BOOLS1,427196,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_MY.Alarm.BOOLS2,427197,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_MY.Alarm.AEBOOLS,427198,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_MY.Alarm.INT1,427199,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MY.Alarm.INT2,427200,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MY.Alarm.AENotify,427201,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_MY.Alarm.AESeverity,427202,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_MY.Alarm.AEShelveDuration,427203,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_MY.almPLCFault.BOOLS1,427208,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_MY.almPLCFault.BOOLS2,427209,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_MY.almPLCFault.AEBOOLS,427210,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_MY.almPLCFault.INT1,427211,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MY.almPLCFault.INT2,427212,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_MY.almPLCFault.AENotify,427213,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_MY.almPLCFault.AESeverity,427214,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_MY.almPLCFault.AEShelveDuration,427215,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UA.Alarm.BOOLS1,427232,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UA.Alarm.BOOLS2,427233,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UA.Alarm.AEBOOLS,427234,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UA.Alarm.INT1,427235,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UA.Alarm.INT2,427236,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UA.Alarm.AENotify,427237,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UA.Alarm.AESeverity,427238,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UA.Alarm.AEShelveDuration,427239,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UA.almPLCFault.BOOLS1,427244,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UA.almPLCFault.BOOLS2,427245,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UA.almPLCFault.AEBOOLS,427246,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UA.almPLCFault.INT1,427247,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UA.almPLCFault.INT2,427248,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UA.almPLCFault.AENotify,427249,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UA.almPLCFault.AESeverity,427250,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UA.almPLCFault.AEShelveDuration,427251,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UH.Alarm.BOOLS1,427266,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UH.Alarm.BOOLS2,427267,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UH.Alarm.AEBOOLS,427268,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UH.Alarm.INT1,427269,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UH.Alarm.INT2,427270,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UH.Alarm.AENotify,427271,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UH.Alarm.AESeverity,427272,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UH.Alarm.AEShelveDuration,427273,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UH.almPLCFault.BOOLS1,427278,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UH.almPLCFault.BOOLS2,427279,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UH.almPLCFault.AEBOOLS,427280,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UH.almPLCFault.INT1,427281,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UH.almPLCFault.INT2,427282,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UH.almPLCFault.AENotify,427283,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UH.almPLCFault.AESeverity,427284,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UH.almPLCFault.AEShelveDuration,427285,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UY.Alarm.BOOLS1,427302,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UY.Alarm.BOOLS2,427303,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UY.Alarm.AEBOOLS,427304,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UY.Alarm.INT1,427305,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UY.Alarm.INT2,427306,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UY.Alarm.AENotify,427307,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UY.Alarm.AESeverity,427308,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UY.Alarm.AEShelveDuration,427309,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_UY.almPLCFault.BOOLS1,427314,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_UY.almPLCFault.BOOLS2,427315,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_UY.almPLCFault.AEBOOLS,427316,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_UY.almPLCFault.INT1,427317,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UY.almPLCFault.INT2,427318,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_UY.almPLCFault.AENotify,427319,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_UY.almPLCFault.AESeverity,427320,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_UY.almPLCFault.AEShelveDuration,427321,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_XF.Alarm.BOOLS1,427336,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_XF.Alarm.BOOLS2,427337,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_XF.Alarm.AEBOOLS,427338,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_XF.Alarm.INT1,427339,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_XF.Alarm.INT2,427340,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_XF.Alarm.AENotify,427341,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_XF.Alarm.AESeverity,427342,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_XF.Alarm.AEShelveDuration,427343,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_XF.almPLCFault.BOOLS1,427348,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_XF.almPLCFault.BOOLS2,427349,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_XF.almPLCFault.AEBOOLS,427350,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_XF.almPLCFault.INT1,427351,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_XF.almPLCFault.INT2,427352,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_XF.almPLCFault.AENotify,427353,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_XF.almPLCFault.AESeverity,427354,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_XF.almPLCFault.AEShelveDuration,427355,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_YA.Alarm.BOOLS1,427372,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_YA.Alarm.BOOLS2,427373,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_YA.Alarm.AEBOOLS,427374,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_YA.Alarm.INT1,427375,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_YA.Alarm.INT2,427376,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_YA.Alarm.AENotify,427377,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_YA.Alarm.AESeverity,427378,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_YA.Alarm.AEShelveDuration,427379,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5_YA.almPLCFault.BOOLS1,427384,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5_YA.almPLCFault.BOOLS2,427385,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5_YA.almPLCFault.AEBOOLS,427386,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5_YA.almPLCFault.INT1,427387,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_YA.almPLCFault.INT2,427388,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5_YA.almPLCFault.AENotify,427389,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5_YA.almPLCFault.AESeverity,427390,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5_YA.almPLCFault.AEShelveDuration,427391,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_FA.Alarm.BOOLS1,427406,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_FA.Alarm.BOOLS2,427407,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_FA.Alarm.AEBOOLS,427408,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_FA.Alarm.INT1,427409,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_FA.Alarm.INT2,427410,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_FA.Alarm.AENotify,427411,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_FA.Alarm.AESeverity,427412,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_FA.Alarm.AEShelveDuration,427413,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_FA.almPLCFault.BOOLS1,427418,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_FA.almPLCFault.BOOLS2,427419,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_FA.almPLCFault.AEBOOLS,427420,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_FA.almPLCFault.INT1,427421,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_FA.almPLCFault.INT2,427422,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_FA.almPLCFault.AENotify,427423,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_FA.almPLCFault.AESeverity,427424,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_FA.almPLCFault.AEShelveDuration,427425,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_MF.Alarm.BOOLS1,427442,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_MF.Alarm.BOOLS2,427443,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_MF.Alarm.AEBOOLS,427444,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_MF.Alarm.INT1,427445,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MF.Alarm.INT2,427446,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MF.Alarm.AENotify,427447,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_MF.Alarm.AESeverity,427448,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_MF.Alarm.AEShelveDuration,427449,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_MF.almPLCFault.BOOLS1,427454,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_MF.almPLCFault.BOOLS2,427455,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_MF.almPLCFault.AEBOOLS,427456,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_MF.almPLCFault.INT1,427457,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MF.almPLCFault.INT2,427458,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MF.almPLCFault.AENotify,427459,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_MF.almPLCFault.AESeverity,427460,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_MF.almPLCFault.AEShelveDuration,427461,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_MY.Alarm.BOOLS1,427476,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_MY.Alarm.BOOLS2,427477,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_MY.Alarm.AEBOOLS,427478,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_MY.Alarm.INT1,427479,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MY.Alarm.INT2,427480,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MY.Alarm.AENotify,427481,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_MY.Alarm.AESeverity,427482,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_MY.Alarm.AEShelveDuration,427483,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_MY.almPLCFault.BOOLS1,427488,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_MY.almPLCFault.BOOLS2,427489,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_MY.almPLCFault.AEBOOLS,427490,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_MY.almPLCFault.INT1,427491,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MY.almPLCFault.INT2,427492,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_MY.almPLCFault.AENotify,427493,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_MY.almPLCFault.AESeverity,427494,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_MY.almPLCFault.AEShelveDuration,427495,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UA.Alarm.BOOLS1,427512,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UA.Alarm.BOOLS2,427513,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UA.Alarm.AEBOOLS,427514,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UA.Alarm.INT1,427515,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UA.Alarm.INT2,427516,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UA.Alarm.AENotify,427517,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UA.Alarm.AESeverity,427518,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UA.Alarm.AEShelveDuration,427519,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UA.almPLCFault.BOOLS1,427524,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UA.almPLCFault.BOOLS2,427525,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UA.almPLCFault.AEBOOLS,427526,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UA.almPLCFault.INT1,427527,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UA.almPLCFault.INT2,427528,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UA.almPLCFault.AENotify,427529,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UA.almPLCFault.AESeverity,427530,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UA.almPLCFault.AEShelveDuration,427531,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UH.Alarm.BOOLS1,427546,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UH.Alarm.BOOLS2,427547,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UH.Alarm.AEBOOLS,427548,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UH.Alarm.INT1,427549,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UH.Alarm.INT2,427550,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UH.Alarm.AENotify,427551,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UH.Alarm.AESeverity,427552,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UH.Alarm.AEShelveDuration,427553,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UH.almPLCFault.BOOLS1,427558,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UH.almPLCFault.BOOLS2,427559,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UH.almPLCFault.AEBOOLS,427560,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UH.almPLCFault.INT1,427561,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UH.almPLCFault.INT2,427562,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UH.almPLCFault.AENotify,427563,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UH.almPLCFault.AESeverity,427564,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UH.almPLCFault.AEShelveDuration,427565,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UY.Alarm.BOOLS1,427582,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UY.Alarm.BOOLS2,427583,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UY.Alarm.AEBOOLS,427584,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UY.Alarm.INT1,427585,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UY.Alarm.INT2,427586,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UY.Alarm.AENotify,427587,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UY.Alarm.AESeverity,427588,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UY.Alarm.AEShelveDuration,427589,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_UY.almPLCFault.BOOLS1,427594,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_UY.almPLCFault.BOOLS2,427595,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_UY.almPLCFault.AEBOOLS,427596,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_UY.almPLCFault.INT1,427597,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UY.almPLCFault.INT2,427598,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_UY.almPLCFault.AENotify,427599,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_UY.almPLCFault.AESeverity,427600,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_UY.almPLCFault.AEShelveDuration,427601,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_XF.Alarm.BOOLS1,427616,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_XF.Alarm.BOOLS2,427617,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_XF.Alarm.AEBOOLS,427618,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_XF.Alarm.INT1,427619,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_XF.Alarm.INT2,427620,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_XF.Alarm.AENotify,427621,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_XF.Alarm.AESeverity,427622,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_XF.Alarm.AEShelveDuration,427623,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_XF.almPLCFault.BOOLS1,427628,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_XF.almPLCFault.BOOLS2,427629,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_XF.almPLCFault.AEBOOLS,427630,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_XF.almPLCFault.INT1,427631,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_XF.almPLCFault.INT2,427632,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_XF.almPLCFault.AENotify,427633,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_XF.almPLCFault.AESeverity,427634,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_XF.almPLCFault.AEShelveDuration,427635,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_YA.Alarm.BOOLS1,427652,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_YA.Alarm.BOOLS2,427653,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_YA.Alarm.AEBOOLS,427654,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_YA.Alarm.INT1,427655,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_YA.Alarm.INT2,427656,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_YA.Alarm.AENotify,427657,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_YA.Alarm.AESeverity,427658,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_YA.Alarm.AEShelveDuration,427659,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6_YA.almPLCFault.BOOLS1,427664,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6_YA.almPLCFault.BOOLS2,427665,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6_YA.almPLCFault.AEBOOLS,427666,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6_YA.almPLCFault.INT1,427667,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_YA.almPLCFault.INT2,427668,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6_YA.almPLCFault.AENotify,427669,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6_YA.almPLCFault.AESeverity,427670,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6_YA.almPLCFault.AEShelveDuration,427671,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_FA.Alarm.BOOLS1,427686,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_FA.Alarm.BOOLS2,427687,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_FA.Alarm.AEBOOLS,427688,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_FA.Alarm.INT1,427689,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_FA.Alarm.INT2,427690,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_FA.Alarm.AENotify,427691,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_FA.Alarm.AESeverity,427692,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_FA.Alarm.AEShelveDuration,427693,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_FA.almPLCFault.BOOLS1,427698,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_FA.almPLCFault.BOOLS2,427699,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_FA.almPLCFault.AEBOOLS,427700,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_FA.almPLCFault.INT1,427701,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_FA.almPLCFault.INT2,427702,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_FA.almPLCFault.AENotify,427703,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_FA.almPLCFault.AESeverity,427704,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_FA.almPLCFault.AEShelveDuration,427705,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_MF.Alarm.BOOLS1,427722,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_MF.Alarm.BOOLS2,427723,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_MF.Alarm.AEBOOLS,427724,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_MF.Alarm.INT1,427725,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MF.Alarm.INT2,427726,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MF.Alarm.AENotify,427727,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_MF.Alarm.AESeverity,427728,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_MF.Alarm.AEShelveDuration,427729,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_MF.almPLCFault.BOOLS1,427734,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_MF.almPLCFault.BOOLS2,427735,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_MF.almPLCFault.AEBOOLS,427736,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_MF.almPLCFault.INT1,427737,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MF.almPLCFault.INT2,427738,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MF.almPLCFault.AENotify,427739,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_MF.almPLCFault.AESeverity,427740,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_MF.almPLCFault.AEShelveDuration,427741,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_MY.Alarm.BOOLS1,427756,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_MY.Alarm.BOOLS2,427757,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_MY.Alarm.AEBOOLS,427758,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_MY.Alarm.INT1,427759,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MY.Alarm.INT2,427760,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MY.Alarm.AENotify,427761,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_MY.Alarm.AESeverity,427762,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_MY.Alarm.AEShelveDuration,427763,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_MY.almPLCFault.BOOLS1,427768,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_MY.almPLCFault.BOOLS2,427769,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_MY.almPLCFault.AEBOOLS,427770,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_MY.almPLCFault.INT1,427771,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MY.almPLCFault.INT2,427772,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_MY.almPLCFault.AENotify,427773,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_MY.almPLCFault.AESeverity,427774,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_MY.almPLCFault.AEShelveDuration,427775,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UA.Alarm.BOOLS1,427792,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UA.Alarm.BOOLS2,427793,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UA.Alarm.AEBOOLS,427794,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UA.Alarm.INT1,427795,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UA.Alarm.INT2,427796,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UA.Alarm.AENotify,427797,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UA.Alarm.AESeverity,427798,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UA.Alarm.AEShelveDuration,427799,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UA.almPLCFault.BOOLS1,427804,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UA.almPLCFault.BOOLS2,427805,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UA.almPLCFault.AEBOOLS,427806,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UA.almPLCFault.INT1,427807,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UA.almPLCFault.INT2,427808,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UA.almPLCFault.AENotify,427809,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UA.almPLCFault.AESeverity,427810,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UA.almPLCFault.AEShelveDuration,427811,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UH.Alarm.BOOLS1,427826,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UH.Alarm.BOOLS2,427827,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UH.Alarm.AEBOOLS,427828,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UH.Alarm.INT1,427829,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UH.Alarm.INT2,427830,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UH.Alarm.AENotify,427831,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UH.Alarm.AESeverity,427832,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UH.Alarm.AEShelveDuration,427833,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UH.almPLCFault.BOOLS1,427838,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UH.almPLCFault.BOOLS2,427839,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UH.almPLCFault.AEBOOLS,427840,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UH.almPLCFault.INT1,427841,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UH.almPLCFault.INT2,427842,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UH.almPLCFault.AENotify,427843,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UH.almPLCFault.AESeverity,427844,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UH.almPLCFault.AEShelveDuration,427845,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UY.Alarm.BOOLS1,427862,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UY.Alarm.BOOLS2,427863,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UY.Alarm.AEBOOLS,427864,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UY.Alarm.INT1,427865,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UY.Alarm.INT2,427866,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UY.Alarm.AENotify,427867,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UY.Alarm.AESeverity,427868,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UY.Alarm.AEShelveDuration,427869,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_UY.almPLCFault.BOOLS1,427874,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_UY.almPLCFault.BOOLS2,427875,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_UY.almPLCFault.AEBOOLS,427876,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_UY.almPLCFault.INT1,427877,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UY.almPLCFault.INT2,427878,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_UY.almPLCFault.AENotify,427879,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_UY.almPLCFault.AESeverity,427880,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_UY.almPLCFault.AEShelveDuration,427881,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_XF.Alarm.BOOLS1,427896,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_XF.Alarm.BOOLS2,427897,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_XF.Alarm.AEBOOLS,427898,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_XF.Alarm.INT1,427899,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_XF.Alarm.INT2,427900,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_XF.Alarm.AENotify,427901,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_XF.Alarm.AESeverity,427902,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_XF.Alarm.AEShelveDuration,427903,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_XF.almPLCFault.BOOLS1,427908,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_XF.almPLCFault.BOOLS2,427909,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_XF.almPLCFault.AEBOOLS,427910,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_XF.almPLCFault.INT1,427911,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_XF.almPLCFault.INT2,427912,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_XF.almPLCFault.AENotify,427913,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_XF.almPLCFault.AESeverity,427914,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_XF.almPLCFault.AEShelveDuration,427915,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_YA.Alarm.BOOLS1,427932,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_YA.Alarm.BOOLS2,427933,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_YA.Alarm.AEBOOLS,427934,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_YA.Alarm.INT1,427935,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_YA.Alarm.INT2,427936,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_YA.Alarm.AENotify,427937,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_YA.Alarm.AESeverity,427938,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_YA.Alarm.AEShelveDuration,427939,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7_YA.almPLCFault.BOOLS1,427944,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7_YA.almPLCFault.BOOLS2,427945,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7_YA.almPLCFault.AEBOOLS,427946,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7_YA.almPLCFault.INT1,427947,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_YA.almPLCFault.INT2,427948,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7_YA.almPLCFault.AENotify,427949,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7_YA.almPLCFault.AESeverity,427950,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7_YA.almPLCFault.AEShelveDuration,427951,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_FA.Alarm.BOOLS1,427966,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_FA.Alarm.BOOLS2,427967,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_FA.Alarm.AEBOOLS,427968,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_FA.Alarm.INT1,427969,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_FA.Alarm.INT2,427970,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_FA.Alarm.AENotify,427971,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_FA.Alarm.AESeverity,427972,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_FA.Alarm.AEShelveDuration,427973,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_FA.almPLCFault.BOOLS1,427978,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_FA.almPLCFault.BOOLS2,427979,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_FA.almPLCFault.AEBOOLS,427980,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_FA.almPLCFault.INT1,427981,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_FA.almPLCFault.INT2,427982,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_FA.almPLCFault.AENotify,427983,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_FA.almPLCFault.AESeverity,427984,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_FA.almPLCFault.AEShelveDuration,427985,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_MF.Alarm.BOOLS1,428002,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_MF.Alarm.BOOLS2,428003,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_MF.Alarm.AEBOOLS,428004,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_MF.Alarm.INT1,428005,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MF.Alarm.INT2,428006,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MF.Alarm.AENotify,428007,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_MF.Alarm.AESeverity,428008,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_MF.Alarm.AEShelveDuration,428009,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_MF.almPLCFault.BOOLS1,428014,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_MF.almPLCFault.BOOLS2,428015,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_MF.almPLCFault.AEBOOLS,428016,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_MF.almPLCFault.INT1,428017,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MF.almPLCFault.INT2,428018,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MF.almPLCFault.AENotify,428019,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_MF.almPLCFault.AESeverity,428020,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_MF.almPLCFault.AEShelveDuration,428021,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_MY.Alarm.BOOLS1,428036,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_MY.Alarm.BOOLS2,428037,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_MY.Alarm.AEBOOLS,428038,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_MY.Alarm.INT1,428039,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MY.Alarm.INT2,428040,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MY.Alarm.AENotify,428041,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_MY.Alarm.AESeverity,428042,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_MY.Alarm.AEShelveDuration,428043,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_MY.almPLCFault.BOOLS1,428048,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_MY.almPLCFault.BOOLS2,428049,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_MY.almPLCFault.AEBOOLS,428050,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_MY.almPLCFault.INT1,428051,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MY.almPLCFault.INT2,428052,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_MY.almPLCFault.AENotify,428053,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_MY.almPLCFault.AESeverity,428054,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_MY.almPLCFault.AEShelveDuration,428055,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UA.Alarm.BOOLS1,428072,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UA.Alarm.BOOLS2,428073,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UA.Alarm.AEBOOLS,428074,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UA.Alarm.INT1,428075,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UA.Alarm.INT2,428076,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UA.Alarm.AENotify,428077,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UA.Alarm.AESeverity,428078,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UA.Alarm.AEShelveDuration,428079,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UA.almPLCFault.BOOLS1,428084,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UA.almPLCFault.BOOLS2,428085,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UA.almPLCFault.AEBOOLS,428086,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UA.almPLCFault.INT1,428087,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UA.almPLCFault.INT2,428088,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UA.almPLCFault.AENotify,428089,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UA.almPLCFault.AESeverity,428090,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UA.almPLCFault.AEShelveDuration,428091,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UH.Alarm.BOOLS1,428106,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UH.Alarm.BOOLS2,428107,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UH.Alarm.AEBOOLS,428108,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UH.Alarm.INT1,428109,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UH.Alarm.INT2,428110,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UH.Alarm.AENotify,428111,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UH.Alarm.AESeverity,428112,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UH.Alarm.AEShelveDuration,428113,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UH.almPLCFault.BOOLS1,428118,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UH.almPLCFault.BOOLS2,428119,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UH.almPLCFault.AEBOOLS,428120,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UH.almPLCFault.INT1,428121,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UH.almPLCFault.INT2,428122,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UH.almPLCFault.AENotify,428123,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UH.almPLCFault.AESeverity,428124,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UH.almPLCFault.AEShelveDuration,428125,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UY.Alarm.BOOLS1,428142,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UY.Alarm.BOOLS2,428143,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UY.Alarm.AEBOOLS,428144,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UY.Alarm.INT1,428145,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UY.Alarm.INT2,428146,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UY.Alarm.AENotify,428147,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UY.Alarm.AESeverity,428148,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UY.Alarm.AEShelveDuration,428149,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_UY.almPLCFault.BOOLS1,428154,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_UY.almPLCFault.BOOLS2,428155,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_UY.almPLCFault.AEBOOLS,428156,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_UY.almPLCFault.INT1,428157,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UY.almPLCFault.INT2,428158,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_UY.almPLCFault.AENotify,428159,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_UY.almPLCFault.AESeverity,428160,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_UY.almPLCFault.AEShelveDuration,428161,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_XF.Alarm.BOOLS1,428176,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_XF.Alarm.BOOLS2,428177,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_XF.Alarm.AEBOOLS,428178,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_XF.Alarm.INT1,428179,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_XF.Alarm.INT2,428180,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_XF.Alarm.AENotify,428181,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_XF.Alarm.AESeverity,428182,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_XF.Alarm.AEShelveDuration,428183,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_XF.almPLCFault.BOOLS1,428188,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_XF.almPLCFault.BOOLS2,428189,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_XF.almPLCFault.AEBOOLS,428190,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_XF.almPLCFault.INT1,428191,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_XF.almPLCFault.INT2,428192,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_XF.almPLCFault.AENotify,428193,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_XF.almPLCFault.AESeverity,428194,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_XF.almPLCFault.AEShelveDuration,428195,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_YA.Alarm.BOOLS1,428212,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_YA.Alarm.BOOLS2,428213,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_YA.Alarm.AEBOOLS,428214,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_YA.Alarm.INT1,428215,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_YA.Alarm.INT2,428216,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_YA.Alarm.AENotify,428217,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_YA.Alarm.AESeverity,428218,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_YA.Alarm.AEShelveDuration,428219,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8_YA.almPLCFault.BOOLS1,428224,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8_YA.almPLCFault.BOOLS2,428225,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8_YA.almPLCFault.AEBOOLS,428226,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8_YA.almPLCFault.INT1,428227,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_YA.almPLCFault.INT2,428228,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8_YA.almPLCFault.AENotify,428229,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8_YA.almPLCFault.AESeverity,428230,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8_YA.almPLCFault.AEShelveDuration,428231,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_FA.Alarm.BOOLS1,428246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_FA.Alarm.BOOLS2,428247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_FA.Alarm.AEBOOLS,428248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_FA.Alarm.INT1,428249,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_FA.Alarm.INT2,428250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_FA.Alarm.AENotify,428251,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_FA.Alarm.AESeverity,428252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_FA.Alarm.AEShelveDuration,428253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_FA.almPLCFault.BOOLS1,428258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_FA.almPLCFault.BOOLS2,428259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_FA.almPLCFault.AEBOOLS,428260,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_FA.almPLCFault.INT1,428261,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_FA.almPLCFault.INT2,428262,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_FA.almPLCFault.AENotify,428263,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_FA.almPLCFault.AESeverity,428264,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_FA.almPLCFault.AEShelveDuration,428265,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_MF.Alarm.BOOLS1,428282,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_MF.Alarm.BOOLS2,428283,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_MF.Alarm.AEBOOLS,428284,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_MF.Alarm.INT1,428285,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MF.Alarm.INT2,428286,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MF.Alarm.AENotify,428287,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_MF.Alarm.AESeverity,428288,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_MF.Alarm.AEShelveDuration,428289,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_MF.almPLCFault.BOOLS1,428294,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_MF.almPLCFault.BOOLS2,428295,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_MF.almPLCFault.AEBOOLS,428296,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_MF.almPLCFault.INT1,428297,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MF.almPLCFault.INT2,428298,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MF.almPLCFault.AENotify,428299,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_MF.almPLCFault.AESeverity,428300,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_MF.almPLCFault.AEShelveDuration,428301,Short,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_MY.Alarm.BOOLS1,428316,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_MY.Alarm.BOOLS2,428317,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_MY.Alarm.AEBOOLS,428318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_MY.Alarm.INT1,428319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MY.Alarm.INT2,428320,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MY.Alarm.AENotify,428321,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_MY.Alarm.AESeverity,428322,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_MY.Alarm.AEShelveDuration,428323,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_MY.almPLCFault.BOOLS1,428328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_MY.almPLCFault.BOOLS2,428329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_MY.almPLCFault.AEBOOLS,428330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_MY.almPLCFault.INT1,428331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MY.almPLCFault.INT2,428332,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_MY.almPLCFault.AENotify,428333,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_MY.almPLCFault.AESeverity,428334,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_MY.almPLCFault.AEShelveDuration,428335,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UA.Alarm.BOOLS1,428352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UA.Alarm.BOOLS2,428353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UA.Alarm.AEBOOLS,428354,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UA.Alarm.INT1,428355,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UA.Alarm.INT2,428356,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UA.Alarm.AENotify,428357,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UA.Alarm.AESeverity,428358,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UA.Alarm.AEShelveDuration,428359,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UA.almPLCFault.BOOLS1,428364,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UA.almPLCFault.BOOLS2,428365,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UA.almPLCFault.AEBOOLS,428366,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UA.almPLCFault.INT1,428367,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UA.almPLCFault.INT2,428368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UA.almPLCFault.AENotify,428369,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UA.almPLCFault.AESeverity,428370,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UA.almPLCFault.AEShelveDuration,428371,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UH.Alarm.BOOLS1,428386,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UH.Alarm.BOOLS2,428387,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UH.Alarm.AEBOOLS,428388,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UH.Alarm.INT1,428389,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UH.Alarm.INT2,428390,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UH.Alarm.AENotify,428391,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UH.Alarm.AESeverity,428392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UH.Alarm.AEShelveDuration,428393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UH.almPLCFault.BOOLS1,428398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UH.almPLCFault.BOOLS2,428399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UH.almPLCFault.AEBOOLS,428400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UH.almPLCFault.INT1,428401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UH.almPLCFault.INT2,428402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UH.almPLCFault.AENotify,428403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UH.almPLCFault.AESeverity,428404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UH.almPLCFault.AEShelveDuration,428405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UY.Alarm.BOOLS1,428422,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UY.Alarm.BOOLS2,428423,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UY.Alarm.AEBOOLS,428424,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UY.Alarm.INT1,428425,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UY.Alarm.INT2,428426,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UY.Alarm.AENotify,428427,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UY.Alarm.AESeverity,428428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UY.Alarm.AEShelveDuration,428429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_UY.almPLCFault.BOOLS1,428434,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_UY.almPLCFault.BOOLS2,428435,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_UY.almPLCFault.AEBOOLS,428436,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_UY.almPLCFault.INT1,428437,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UY.almPLCFault.INT2,428438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_UY.almPLCFault.AENotify,428439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_UY.almPLCFault.AESeverity,428440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_UY.almPLCFault.AEShelveDuration,428441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_XF.Alarm.BOOLS1,428456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_XF.Alarm.BOOLS2,428457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_XF.Alarm.AEBOOLS,428458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_XF.Alarm.INT1,428459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_XF.Alarm.INT2,428460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_XF.Alarm.AENotify,428461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_XF.Alarm.AESeverity,428462,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_XF.Alarm.AEShelveDuration,428463,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_XF.almPLCFault.BOOLS1,428468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_XF.almPLCFault.BOOLS2,428469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_XF.almPLCFault.AEBOOLS,428470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_XF.almPLCFault.INT1,428471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_XF.almPLCFault.INT2,428472,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_XF.almPLCFault.AENotify,428473,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_XF.almPLCFault.AESeverity,428474,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_XF.almPLCFault.AEShelveDuration,428475,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_YA.Alarm.BOOLS1,428492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_YA.Alarm.BOOLS2,428493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_YA.Alarm.AEBOOLS,428494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_YA.Alarm.INT1,428495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_YA.Alarm.INT2,428496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_YA.Alarm.AENotify,428497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_YA.Alarm.AESeverity,428498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_YA.Alarm.AEShelveDuration,428499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9_YA.almPLCFault.BOOLS1,428504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9_YA.almPLCFault.BOOLS2,428505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9_YA.almPLCFault.AEBOOLS,428506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9_YA.almPLCFault.INT1,428507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_YA.almPLCFault.INT2,428508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9_YA.almPLCFault.AENotify,428509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9_YA.almPLCFault.AESeverity,428510,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9_YA.almPLCFault.AEShelveDuration,428511,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_1_JA.Alarm.BOOLS1,428526,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_1_JA.Alarm.BOOLS2,428527,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_1_JA.Alarm.AEBOOLS,428528,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_1_JA.Alarm.INT1,428529,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JA.Alarm.INT2,428530,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JA.Alarm.AENotify,428531,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_1_JA.Alarm.AESeverity,428532,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_1_JA.Alarm.AEShelveDuration,428533,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_1_JA.almPLCFault.BOOLS1,428538,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_1_JA.almPLCFault.BOOLS2,428539,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_1_JA.almPLCFault.AEBOOLS,428540,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_1_JA.almPLCFault.INT1,428541,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JA.almPLCFault.INT2,428542,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JA.almPLCFault.AENotify,428543,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_1_JA.almPLCFault.AESeverity,428544,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_1_JA.almPLCFault.AEShelveDuration,428545,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_1_JN1.Alarm.BOOLS1,428562,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_1_JN1.Alarm.BOOLS2,428563,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_1_JN1.Alarm.AEBOOLS,428564,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_1_JN1.Alarm.INT1,428565,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JN1.Alarm.INT2,428566,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JN1.Alarm.AENotify,428567,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_1_JN1.Alarm.AESeverity,428568,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_1_JN1.Alarm.AEShelveDuration,428569,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_1_JN1.almPLCFault.BOOLS1,428574,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_1_JN1.almPLCFault.BOOLS2,428575,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_1_JN1.almPLCFault.AEBOOLS,428576,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_1_JN1.almPLCFault.INT1,428577,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JN1.almPLCFault.INT2,428578,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_1_JN1.almPLCFault.AENotify,428579,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_1_JN1.almPLCFault.AESeverity,428580,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_1_JN1.almPLCFault.AEShelveDuration,428581,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_2_JA.Alarm.BOOLS1,428596,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_2_JA.Alarm.BOOLS2,428597,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_2_JA.Alarm.AEBOOLS,428598,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_2_JA.Alarm.INT1,428599,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JA.Alarm.INT2,428600,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JA.Alarm.AENotify,428601,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_2_JA.Alarm.AESeverity,428602,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_2_JA.Alarm.AEShelveDuration,428603,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_2_JA.almPLCFault.BOOLS1,428608,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_2_JA.almPLCFault.BOOLS2,428609,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_2_JA.almPLCFault.AEBOOLS,428610,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_2_JA.almPLCFault.INT1,428611,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JA.almPLCFault.INT2,428612,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JA.almPLCFault.AENotify,428613,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_2_JA.almPLCFault.AESeverity,428614,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_2_JA.almPLCFault.AEShelveDuration,428615,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_2_JN1.Alarm.BOOLS1,428632,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_2_JN1.Alarm.BOOLS2,428633,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_2_JN1.Alarm.AEBOOLS,428634,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_2_JN1.Alarm.INT1,428635,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JN1.Alarm.INT2,428636,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JN1.Alarm.AENotify,428637,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_2_JN1.Alarm.AESeverity,428638,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_2_JN1.Alarm.AEShelveDuration,428639,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0112_2_JN1.almPLCFault.BOOLS1,428644,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0112_2_JN1.almPLCFault.BOOLS2,428645,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0112_2_JN1.almPLCFault.AEBOOLS,428646,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0112_2_JN1.almPLCFault.INT1,428647,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JN1.almPLCFault.INT2,428648,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0112_2_JN1.almPLCFault.AENotify,428649,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0112_2_JN1.almPLCFault.AESeverity,428650,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0112_2_JN1.almPLCFault.AEShelveDuration,428651,Short,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0140_1_JA.Alarm.BOOLS1,428666,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0140_1_JA.Alarm.BOOLS2,428667,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0140_1_JA.Alarm.AEBOOLS,428668,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0140_1_JA.Alarm.INT1,428669,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_JA.Alarm.INT2,428670,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_JA.Alarm.AENotify,428671,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0140_1_JA.Alarm.AESeverity,428672,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0140_1_JA.Alarm.AEShelveDuration,428673,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0140_1_JA.almPLCFault.BOOLS1,428678,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0140_1_JA.almPLCFault.BOOLS2,428679,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0140_1_JA.almPLCFault.AEBOOLS,428680,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0140_1_JA.almPLCFault.INT1,428681,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_JA.almPLCFault.INT2,428682,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_JA.almPLCFault.AENotify,428683,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0140_1_JA.almPLCFault.AESeverity,428684,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0140_1_JA.almPLCFault.AEShelveDuration,428685,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0140_1_XA.Alarm.BOOLS1,428702,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0140_1_XA.Alarm.BOOLS2,428703,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0140_1_XA.Alarm.AEBOOLS,428704,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0140_1_XA.Alarm.INT1,428705,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_XA.Alarm.INT2,428706,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_XA.Alarm.AENotify,428707,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0140_1_XA.Alarm.AESeverity,428708,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0140_1_XA.Alarm.AEShelveDuration,428709,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_ATO_0140_1_XA.almPLCFault.BOOLS1,428714,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_ATO_0140_1_XA.almPLCFault.BOOLS2,428715,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_ATO_0140_1_XA.almPLCFault.AEBOOLS,428716,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_ATO_0140_1_XA.almPLCFault.INT1,428717,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_XA.almPLCFault.INT2,428718,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_ATO_0140_1_XA.almPLCFault.AENotify,428719,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_ATO_0140_1_XA.almPLCFault.AESeverity,428720,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_ATO_0140_1_XA.almPLCFault.AEShelveDuration,428721,Short,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_1_XA.Alarm.BOOLS1,428736,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_1_XA.Alarm.BOOLS2,428737,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_1_XA.Alarm.AEBOOLS,428738,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_1_XA.Alarm.INT1,428739,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_1_XA.Alarm.INT2,428740,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_1_XA.Alarm.AENotify,428741,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_1_XA.Alarm.AESeverity,428742,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_1_XA.Alarm.AEShelveDuration,428743,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_1_XA.almPLCFault.BOOLS1,428748,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_1_XA.almPLCFault.BOOLS2,428749,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_1_XA.almPLCFault.AEBOOLS,428750,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_1_XA.almPLCFault.INT1,428751,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_1_XA.almPLCFault.INT2,428752,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_1_XA.almPLCFault.AENotify,428753,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_1_XA.almPLCFault.AESeverity,428754,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_1_XA.almPLCFault.AEShelveDuration,428755,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_2_XA.Alarm.BOOLS1,428772,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_2_XA.Alarm.BOOLS2,428773,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_2_XA.Alarm.AEBOOLS,428774,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_2_XA.Alarm.INT1,428775,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_2_XA.Alarm.INT2,428776,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_2_XA.Alarm.AENotify,428777,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_2_XA.Alarm.AESeverity,428778,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_2_XA.Alarm.AEShelveDuration,428779,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_2_XA.almPLCFault.BOOLS1,428784,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_2_XA.almPLCFault.BOOLS2,428785,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_2_XA.almPLCFault.AEBOOLS,428786,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_2_XA.almPLCFault.INT1,428787,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_2_XA.almPLCFault.INT2,428788,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_2_XA.almPLCFault.AENotify,428789,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_2_XA.almPLCFault.AESeverity,428790,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_2_XA.almPLCFault.AEShelveDuration,428791,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_3_LH.Alarm.BOOLS1,428806,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_3_LH.Alarm.BOOLS2,428807,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_3_LH.Alarm.AEBOOLS,428808,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_3_LH.Alarm.INT1,428809,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_3_LH.Alarm.INT2,428810,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_3_LH.Alarm.AENotify,428811,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_3_LH.Alarm.AESeverity,428812,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_3_LH.Alarm.AEShelveDuration,428813,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0114_3_LH.almPLCFault.BOOLS1,428818,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0114_3_LH.almPLCFault.BOOLS2,428819,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0114_3_LH.almPLCFault.AEBOOLS,428820,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0114_3_LH.almPLCFault.INT1,428821,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_3_LH.almPLCFault.INT2,428822,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0114_3_LH.almPLCFault.AENotify,428823,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0114_3_LH.almPLCFault.AESeverity,428824,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0114_3_LH.almPLCFault.AEShelveDuration,428825,Short,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1A_MF.Alarm.BOOLS1,428842,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1A_MF.Alarm.BOOLS2,428843,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1A_MF.Alarm.AEBOOLS,428844,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1A_MF.Alarm.INT1,428845,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_MF.Alarm.INT2,428846,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_MF.Alarm.AENotify,428847,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1A_MF.Alarm.AESeverity,428848,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1A_MF.Alarm.AEShelveDuration,428849,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1A_MF.almPLCFault.BOOLS1,428854,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1A_MF.almPLCFault.BOOLS2,428855,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1A_MF.almPLCFault.AEBOOLS,428856,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1A_MF.almPLCFault.INT1,428857,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_MF.almPLCFault.INT2,428858,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_MF.almPLCFault.AENotify,428859,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1A_MF.almPLCFault.AESeverity,428860,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1A_MF.almPLCFault.AEShelveDuration,428861,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1A_XA.Alarm.BOOLS1,428876,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1A_XA.Alarm.BOOLS2,428877,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1A_XA.Alarm.AEBOOLS,428878,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1A_XA.Alarm.INT1,428879,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_XA.Alarm.INT2,428880,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_XA.Alarm.AENotify,428881,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1A_XA.Alarm.AESeverity,428882,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1A_XA.Alarm.AEShelveDuration,428883,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1A_XA.almPLCFault.BOOLS1,428888,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1A_XA.almPLCFault.BOOLS2,428889,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1A_XA.almPLCFault.AEBOOLS,428890,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1A_XA.almPLCFault.INT1,428891,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_XA.almPLCFault.INT2,428892,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1A_XA.almPLCFault.AENotify,428893,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1A_XA.almPLCFault.AESeverity,428894,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1A_XA.almPLCFault.AEShelveDuration,428895,Short,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1B_MF.Alarm.BOOLS1,428912,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1B_MF.Alarm.BOOLS2,428913,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1B_MF.Alarm.AEBOOLS,428914,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1B_MF.Alarm.INT1,428915,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_MF.Alarm.INT2,428916,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_MF.Alarm.AENotify,428917,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1B_MF.Alarm.AESeverity,428918,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1B_MF.Alarm.AEShelveDuration,428919,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1B_MF.almPLCFault.BOOLS1,428924,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1B_MF.almPLCFault.BOOLS2,428925,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1B_MF.almPLCFault.AEBOOLS,428926,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1B_MF.almPLCFault.INT1,428927,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_MF.almPLCFault.INT2,428928,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_MF.almPLCFault.AENotify,428929,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1B_MF.almPLCFault.AESeverity,428930,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1B_MF.almPLCFault.AEShelveDuration,428931,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1B_XA.Alarm.BOOLS1,428946,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1B_XA.Alarm.BOOLS2,428947,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1B_XA.Alarm.AEBOOLS,428948,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1B_XA.Alarm.INT1,428949,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_XA.Alarm.INT2,428950,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_XA.Alarm.AENotify,428951,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1B_XA.Alarm.AESeverity,428952,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1B_XA.Alarm.AEShelveDuration,428953,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1B_XA.almPLCFault.BOOLS1,428958,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1B_XA.almPLCFault.BOOLS2,428959,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1B_XA.almPLCFault.AEBOOLS,428960,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1B_XA.almPLCFault.INT1,428961,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_XA.almPLCFault.INT2,428962,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1B_XA.almPLCFault.AENotify,428963,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1B_XA.almPLCFault.AESeverity,428964,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1B_XA.almPLCFault.AEShelveDuration,428965,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1C_MF.Alarm.BOOLS1,428982,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1C_MF.Alarm.BOOLS2,428983,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1C_MF.Alarm.AEBOOLS,428984,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1C_MF.Alarm.INT1,428985,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_MF.Alarm.INT2,428986,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_MF.Alarm.AENotify,428987,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1C_MF.Alarm.AESeverity,428988,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1C_MF.Alarm.AEShelveDuration,428989,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1C_MF.almPLCFault.BOOLS1,428994,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1C_MF.almPLCFault.BOOLS2,428995,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1C_MF.almPLCFault.AEBOOLS,428996,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1C_MF.almPLCFault.INT1,428997,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_MF.almPLCFault.INT2,428998,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_MF.almPLCFault.AENotify,428999,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1C_MF.almPLCFault.AESeverity,429000,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1C_MF.almPLCFault.AEShelveDuration,429001,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1C_XA.Alarm.BOOLS1,429016,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1C_XA.Alarm.BOOLS2,429017,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1C_XA.Alarm.AEBOOLS,429018,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1C_XA.Alarm.INT1,429019,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_XA.Alarm.INT2,429020,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_XA.Alarm.AENotify,429021,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1C_XA.Alarm.AESeverity,429022,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1C_XA.Alarm.AEShelveDuration,429023,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1C_XA.almPLCFault.BOOLS1,429028,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1C_XA.almPLCFault.BOOLS2,429029,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1C_XA.almPLCFault.AEBOOLS,429030,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1C_XA.almPLCFault.INT1,429031,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_XA.almPLCFault.INT2,429032,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1C_XA.almPLCFault.AENotify,429033,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1C_XA.almPLCFault.AESeverity,429034,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1C_XA.almPLCFault.AEShelveDuration,429035,Short,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1DE_MF.Alarm.BOOLS1,429052,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1DE_MF.Alarm.BOOLS2,429053,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1DE_MF.Alarm.AEBOOLS,429054,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1DE_MF.Alarm.INT1,429055,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_MF.Alarm.INT2,429056,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_MF.Alarm.AENotify,429057,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1DE_MF.Alarm.AESeverity,429058,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1DE_MF.Alarm.AEShelveDuration,429059,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1DE_MF.almPLCFault.BOOLS1,429064,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1DE_MF.almPLCFault.BOOLS2,429065,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1DE_MF.almPLCFault.AEBOOLS,429066,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1DE_MF.almPLCFault.INT1,429067,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_MF.almPLCFault.INT2,429068,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_MF.almPLCFault.AENotify,429069,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1DE_MF.almPLCFault.AESeverity,429070,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1DE_MF.almPLCFault.AEShelveDuration,429071,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1DE_XA.Alarm.BOOLS1,429086,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1DE_XA.Alarm.BOOLS2,429087,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1DE_XA.Alarm.AEBOOLS,429088,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1DE_XA.Alarm.INT1,429089,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_XA.Alarm.INT2,429090,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_XA.Alarm.AENotify,429091,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1DE_XA.Alarm.AESeverity,429092,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1DE_XA.Alarm.AEShelveDuration,429093,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1DE_XA.almPLCFault.BOOLS1,429098,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1DE_XA.almPLCFault.BOOLS2,429099,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1DE_XA.almPLCFault.AEBOOLS,429100,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1DE_XA.almPLCFault.INT1,429101,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_XA.almPLCFault.INT2,429102,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1DE_XA.almPLCFault.AENotify,429103,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1DE_XA.almPLCFault.AESeverity,429104,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1DE_XA.almPLCFault.AEShelveDuration,429105,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1FG_MF.Alarm.BOOLS1,429122,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1FG_MF.Alarm.BOOLS2,429123,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1FG_MF.Alarm.AEBOOLS,429124,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1FG_MF.Alarm.INT1,429125,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_MF.Alarm.INT2,429126,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_MF.Alarm.AENotify,429127,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1FG_MF.Alarm.AESeverity,429128,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1FG_MF.Alarm.AEShelveDuration,429129,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1FG_MF.almPLCFault.BOOLS1,429134,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1FG_MF.almPLCFault.BOOLS2,429135,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1FG_MF.almPLCFault.AEBOOLS,429136,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1FG_MF.almPLCFault.INT1,429137,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_MF.almPLCFault.INT2,429138,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_MF.almPLCFault.AENotify,429139,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1FG_MF.almPLCFault.AESeverity,429140,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1FG_MF.almPLCFault.AEShelveDuration,429141,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1FG_XA.Alarm.BOOLS1,429156,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1FG_XA.Alarm.BOOLS2,429157,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1FG_XA.Alarm.AEBOOLS,429158,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1FG_XA.Alarm.INT1,429159,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_XA.Alarm.INT2,429160,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_XA.Alarm.AENotify,429161,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1FG_XA.Alarm.AESeverity,429162,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1FG_XA.Alarm.AEShelveDuration,429163,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1FG_XA.almPLCFault.BOOLS1,429168,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1FG_XA.almPLCFault.BOOLS2,429169,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1FG_XA.almPLCFault.AEBOOLS,429170,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1FG_XA.almPLCFault.INT1,429171,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_XA.almPLCFault.INT2,429172,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1FG_XA.almPLCFault.AENotify,429173,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1FG_XA.almPLCFault.AESeverity,429174,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1FG_XA.almPLCFault.AEShelveDuration,429175,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1H_MF.Alarm.BOOLS1,429192,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1H_MF.Alarm.BOOLS2,429193,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1H_MF.Alarm.AEBOOLS,429194,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1H_MF.Alarm.INT1,429195,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_MF.Alarm.INT2,429196,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_MF.Alarm.AENotify,429197,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1H_MF.Alarm.AESeverity,429198,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1H_MF.Alarm.AEShelveDuration,429199,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1H_MF.almPLCFault.BOOLS1,429204,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1H_MF.almPLCFault.BOOLS2,429205,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1H_MF.almPLCFault.AEBOOLS,429206,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1H_MF.almPLCFault.INT1,429207,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_MF.almPLCFault.INT2,429208,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_MF.almPLCFault.AENotify,429209,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1H_MF.almPLCFault.AESeverity,429210,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1H_MF.almPLCFault.AEShelveDuration,429211,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1H_XA.Alarm.BOOLS1,429226,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1H_XA.Alarm.BOOLS2,429227,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1H_XA.Alarm.AEBOOLS,429228,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1H_XA.Alarm.INT1,429229,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_XA.Alarm.INT2,429230,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_XA.Alarm.AENotify,429231,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1H_XA.Alarm.AESeverity,429232,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1H_XA.Alarm.AEShelveDuration,429233,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1H_XA.almPLCFault.BOOLS1,429238,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1H_XA.almPLCFault.BOOLS2,429239,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1H_XA.almPLCFault.AEBOOLS,429240,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1H_XA.almPLCFault.INT1,429241,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_XA.almPLCFault.INT2,429242,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1H_XA.almPLCFault.AENotify,429243,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1H_XA.almPLCFault.AESeverity,429244,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1H_XA.almPLCFault.AEShelveDuration,429245,Short,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1I_MF.Alarm.BOOLS1,429262,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1I_MF.Alarm.BOOLS2,429263,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1I_MF.Alarm.AEBOOLS,429264,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1I_MF.Alarm.INT1,429265,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_MF.Alarm.INT2,429266,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_MF.Alarm.AENotify,429267,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1I_MF.Alarm.AESeverity,429268,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1I_MF.Alarm.AEShelveDuration,429269,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1I_MF.almPLCFault.BOOLS1,429274,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1I_MF.almPLCFault.BOOLS2,429275,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1I_MF.almPLCFault.AEBOOLS,429276,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1I_MF.almPLCFault.INT1,429277,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_MF.almPLCFault.INT2,429278,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_MF.almPLCFault.AENotify,429279,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1I_MF.almPLCFault.AESeverity,429280,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1I_MF.almPLCFault.AEShelveDuration,429281,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1I_XA.Alarm.BOOLS1,429296,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1I_XA.Alarm.BOOLS2,429297,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1I_XA.Alarm.AEBOOLS,429298,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1I_XA.Alarm.INT1,429299,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_XA.Alarm.INT2,429300,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_XA.Alarm.AENotify,429301,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1I_XA.Alarm.AESeverity,429302,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1I_XA.Alarm.AEShelveDuration,429303,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1I_XA.almPLCFault.BOOLS1,429308,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1I_XA.almPLCFault.BOOLS2,429309,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1I_XA.almPLCFault.AEBOOLS,429310,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1I_XA.almPLCFault.INT1,429311,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_XA.almPLCFault.INT2,429312,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1I_XA.almPLCFault.AENotify,429313,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1I_XA.almPLCFault.AESeverity,429314,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1I_XA.almPLCFault.AEShelveDuration,429315,Short,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1J_MF.Alarm.BOOLS1,429332,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1J_MF.Alarm.BOOLS2,429333,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1J_MF.Alarm.AEBOOLS,429334,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1J_MF.Alarm.INT1,429335,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_MF.Alarm.INT2,429336,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_MF.Alarm.AENotify,429337,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1J_MF.Alarm.AESeverity,429338,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1J_MF.Alarm.AEShelveDuration,429339,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1J_MF.almPLCFault.BOOLS1,429344,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1J_MF.almPLCFault.BOOLS2,429345,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1J_MF.almPLCFault.AEBOOLS,429346,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1J_MF.almPLCFault.INT1,429347,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_MF.almPLCFault.INT2,429348,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_MF.almPLCFault.AENotify,429349,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1J_MF.almPLCFault.AESeverity,429350,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1J_MF.almPLCFault.AEShelveDuration,429351,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1J_XA.Alarm.BOOLS1,429366,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1J_XA.Alarm.BOOLS2,429367,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1J_XA.Alarm.AEBOOLS,429368,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1J_XA.Alarm.INT1,429369,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_XA.Alarm.INT2,429370,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_XA.Alarm.AENotify,429371,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1J_XA.Alarm.AESeverity,429372,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1J_XA.Alarm.AEShelveDuration,429373,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1J_XA.almPLCFault.BOOLS1,429378,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1J_XA.almPLCFault.BOOLS2,429379,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1J_XA.almPLCFault.AEBOOLS,429380,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1J_XA.almPLCFault.INT1,429381,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_XA.almPLCFault.INT2,429382,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1J_XA.almPLCFault.AENotify,429383,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1J_XA.almPLCFault.AESeverity,429384,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1J_XA.almPLCFault.AEShelveDuration,429385,Short,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1K_MF.Alarm.BOOLS1,429402,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1K_MF.Alarm.BOOLS2,429403,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1K_MF.Alarm.AEBOOLS,429404,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1K_MF.Alarm.INT1,429405,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_MF.Alarm.INT2,429406,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_MF.Alarm.AENotify,429407,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1K_MF.Alarm.AESeverity,429408,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1K_MF.Alarm.AEShelveDuration,429409,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1K_MF.almPLCFault.BOOLS1,429414,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1K_MF.almPLCFault.BOOLS2,429415,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1K_MF.almPLCFault.AEBOOLS,429416,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1K_MF.almPLCFault.INT1,429417,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_MF.almPLCFault.INT2,429418,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_MF.almPLCFault.AENotify,429419,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1K_MF.almPLCFault.AESeverity,429420,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1K_MF.almPLCFault.AEShelveDuration,429421,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1K_XA.Alarm.BOOLS1,429436,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1K_XA.Alarm.BOOLS2,429437,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1K_XA.Alarm.AEBOOLS,429438,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1K_XA.Alarm.INT1,429439,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_XA.Alarm.INT2,429440,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_XA.Alarm.AENotify,429441,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1K_XA.Alarm.AESeverity,429442,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1K_XA.Alarm.AEShelveDuration,429443,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_1K_XA.almPLCFault.BOOLS1,429448,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_1K_XA.almPLCFault.BOOLS2,429449,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_1K_XA.almPLCFault.AEBOOLS,429450,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_1K_XA.almPLCFault.INT1,429451,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_XA.almPLCFault.INT2,429452,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_1K_XA.almPLCFault.AENotify,429453,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_1K_XA.almPLCFault.AESeverity,429454,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_1K_XA.almPLCFault.AEShelveDuration,429455,Short,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_LH.Alarm.BOOLS1,429472,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_LH.Alarm.BOOLS2,429473,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_LH.Alarm.AEBOOLS,429474,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_LH.Alarm.INT1,429475,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_LH.Alarm.INT2,429476,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_LH.Alarm.AENotify,429477,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_LH.Alarm.AESeverity,429478,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_LH.Alarm.AEShelveDuration,429479,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_LH.almPLCFault.BOOLS1,429484,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_LH.almPLCFault.BOOLS2,429485,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_LH.almPLCFault.AEBOOLS,429486,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_LH.almPLCFault.INT1,429487,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_LH.almPLCFault.INT2,429488,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_LH.almPLCFault.AENotify,429489,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_LH.almPLCFault.AESeverity,429490,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_LH.almPLCFault.AEShelveDuration,429491,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF1.Alarm.BOOLS1,429506,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF1.Alarm.BOOLS2,429507,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF1.Alarm.AEBOOLS,429508,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF1.Alarm.INT1,429509,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF1.Alarm.INT2,429510,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF1.Alarm.AENotify,429511,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF1.Alarm.AESeverity,429512,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF1.Alarm.AEShelveDuration,429513,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF1.almPLCFault.BOOLS1,429518,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF1.almPLCFault.BOOLS2,429519,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF1.almPLCFault.AEBOOLS,429520,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF1.almPLCFault.INT1,429521,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF1.almPLCFault.INT2,429522,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF1.almPLCFault.AENotify,429523,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF1.almPLCFault.AESeverity,429524,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF1.almPLCFault.AEShelveDuration,429525,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF2.Alarm.BOOLS1,429542,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF2.Alarm.BOOLS2,429543,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF2.Alarm.AEBOOLS,429544,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF2.Alarm.INT1,429545,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF2.Alarm.INT2,429546,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF2.Alarm.AENotify,429547,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF2.Alarm.AESeverity,429548,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF2.Alarm.AEShelveDuration,429549,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF2.almPLCFault.BOOLS1,429554,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF2.almPLCFault.BOOLS2,429555,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF2.almPLCFault.AEBOOLS,429556,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF2.almPLCFault.INT1,429557,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF2.almPLCFault.INT2,429558,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF2.almPLCFault.AENotify,429559,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF2.almPLCFault.AESeverity,429560,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF2.almPLCFault.AEShelveDuration,429561,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF3.Alarm.BOOLS1,429576,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF3.Alarm.BOOLS2,429577,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF3.Alarm.AEBOOLS,429578,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF3.Alarm.INT1,429579,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF3.Alarm.INT2,429580,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF3.Alarm.AENotify,429581,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF3.Alarm.AESeverity,429582,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF3.Alarm.AEShelveDuration,429583,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF3.almPLCFault.BOOLS1,429588,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF3.almPLCFault.BOOLS2,429589,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF3.almPLCFault.AEBOOLS,429590,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF3.almPLCFault.INT1,429591,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF3.almPLCFault.INT2,429592,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF3.almPLCFault.AENotify,429593,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF3.almPLCFault.AESeverity,429594,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF3.almPLCFault.AEShelveDuration,429595,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF4.Alarm.BOOLS1,429612,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF4.Alarm.BOOLS2,429613,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF4.Alarm.AEBOOLS,429614,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF4.Alarm.INT1,429615,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF4.Alarm.INT2,429616,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF4.Alarm.AENotify,429617,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF4.Alarm.AESeverity,429618,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF4.Alarm.AEShelveDuration,429619,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_MF4.almPLCFault.BOOLS1,429624,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_MF4.almPLCFault.BOOLS2,429625,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_MF4.almPLCFault.AEBOOLS,429626,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_MF4.almPLCFault.INT1,429627,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF4.almPLCFault.INT2,429628,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_MF4.almPLCFault.AENotify,429629,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_MF4.almPLCFault.AESeverity,429630,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_MF4.almPLCFault.AEShelveDuration,429631,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_XA.Alarm.BOOLS1,429646,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_XA.Alarm.BOOLS2,429647,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_XA.Alarm.AEBOOLS,429648,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_XA.Alarm.INT1,429649,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_XA.Alarm.INT2,429650,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_XA.Alarm.AENotify,429651,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_XA.Alarm.AESeverity,429652,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_XA.Alarm.AEShelveDuration,429653,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2A_XA.almPLCFault.BOOLS1,429658,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2A_XA.almPLCFault.BOOLS2,429659,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2A_XA.almPLCFault.AEBOOLS,429660,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2A_XA.almPLCFault.INT1,429661,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_XA.almPLCFault.INT2,429662,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2A_XA.almPLCFault.AENotify,429663,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2A_XA.almPLCFault.AESeverity,429664,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2A_XA.almPLCFault.AEShelveDuration,429665,Short,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_LH.Alarm.BOOLS1,429682,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_LH.Alarm.BOOLS2,429683,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_LH.Alarm.AEBOOLS,429684,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_LH.Alarm.INT1,429685,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_LH.Alarm.INT2,429686,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_LH.Alarm.AENotify,429687,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_LH.Alarm.AESeverity,429688,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_LH.Alarm.AEShelveDuration,429689,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_LH.almPLCFault.BOOLS1,429694,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_LH.almPLCFault.BOOLS2,429695,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_LH.almPLCFault.AEBOOLS,429696,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_LH.almPLCFault.INT1,429697,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_LH.almPLCFault.INT2,429698,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_LH.almPLCFault.AENotify,429699,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_LH.almPLCFault.AESeverity,429700,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_LH.almPLCFault.AEShelveDuration,429701,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF1.Alarm.BOOLS1,429716,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF1.Alarm.BOOLS2,429717,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF1.Alarm.AEBOOLS,429718,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF1.Alarm.INT1,429719,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF1.Alarm.INT2,429720,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF1.Alarm.AENotify,429721,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF1.Alarm.AESeverity,429722,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF1.Alarm.AEShelveDuration,429723,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF1.almPLCFault.BOOLS1,429728,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF1.almPLCFault.BOOLS2,429729,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF1.almPLCFault.AEBOOLS,429730,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF1.almPLCFault.INT1,429731,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF1.almPLCFault.INT2,429732,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF1.almPLCFault.AENotify,429733,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF1.almPLCFault.AESeverity,429734,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF1.almPLCFault.AEShelveDuration,429735,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF2.Alarm.BOOLS1,429752,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF2.Alarm.BOOLS2,429753,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF2.Alarm.AEBOOLS,429754,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF2.Alarm.INT1,429755,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF2.Alarm.INT2,429756,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF2.Alarm.AENotify,429757,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF2.Alarm.AESeverity,429758,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF2.Alarm.AEShelveDuration,429759,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF2.almPLCFault.BOOLS1,429764,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF2.almPLCFault.BOOLS2,429765,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF2.almPLCFault.AEBOOLS,429766,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF2.almPLCFault.INT1,429767,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF2.almPLCFault.INT2,429768,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF2.almPLCFault.AENotify,429769,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF2.almPLCFault.AESeverity,429770,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF2.almPLCFault.AEShelveDuration,429771,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF3.Alarm.BOOLS1,429786,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF3.Alarm.BOOLS2,429787,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF3.Alarm.AEBOOLS,429788,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF3.Alarm.INT1,429789,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF3.Alarm.INT2,429790,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF3.Alarm.AENotify,429791,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF3.Alarm.AESeverity,429792,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF3.Alarm.AEShelveDuration,429793,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF3.almPLCFault.BOOLS1,429798,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF3.almPLCFault.BOOLS2,429799,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF3.almPLCFault.AEBOOLS,429800,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF3.almPLCFault.INT1,429801,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF3.almPLCFault.INT2,429802,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF3.almPLCFault.AENotify,429803,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF3.almPLCFault.AESeverity,429804,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF3.almPLCFault.AEShelveDuration,429805,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF4.Alarm.BOOLS1,429822,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF4.Alarm.BOOLS2,429823,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF4.Alarm.AEBOOLS,429824,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF4.Alarm.INT1,429825,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF4.Alarm.INT2,429826,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF4.Alarm.AENotify,429827,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF4.Alarm.AESeverity,429828,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF4.Alarm.AEShelveDuration,429829,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_MF4.almPLCFault.BOOLS1,429834,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_MF4.almPLCFault.BOOLS2,429835,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_MF4.almPLCFault.AEBOOLS,429836,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_MF4.almPLCFault.INT1,429837,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF4.almPLCFault.INT2,429838,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_MF4.almPLCFault.AENotify,429839,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_MF4.almPLCFault.AESeverity,429840,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_MF4.almPLCFault.AEShelveDuration,429841,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_XA.Alarm.BOOLS1,429856,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_XA.Alarm.BOOLS2,429857,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_XA.Alarm.AEBOOLS,429858,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_XA.Alarm.INT1,429859,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_XA.Alarm.INT2,429860,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_XA.Alarm.AENotify,429861,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_XA.Alarm.AESeverity,429862,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_XA.Alarm.AEShelveDuration,429863,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_2B_XA.almPLCFault.BOOLS1,429868,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_2B_XA.almPLCFault.BOOLS2,429869,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_2B_XA.almPLCFault.AEBOOLS,429870,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_2B_XA.almPLCFault.INT1,429871,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_XA.almPLCFault.INT2,429872,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_2B_XA.almPLCFault.AENotify,429873,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_2B_XA.almPLCFault.AESeverity,429874,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_2B_XA.almPLCFault.AEShelveDuration,429875,Short,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_3A_MF.Alarm.BOOLS1,429892,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_3A_MF.Alarm.BOOLS2,429893,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_3A_MF.Alarm.AEBOOLS,429894,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_3A_MF.Alarm.INT1,429895,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3A_MF.Alarm.INT2,429896,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3A_MF.Alarm.AENotify,429897,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_3A_MF.Alarm.AESeverity,429898,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_3A_MF.Alarm.AEShelveDuration,429899,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_3A_MF.almPLCFault.BOOLS1,429904,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_3A_MF.almPLCFault.BOOLS2,429905,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_3A_MF.almPLCFault.AEBOOLS,429906,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_3A_MF.almPLCFault.INT1,429907,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3A_MF.almPLCFault.INT2,429908,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3A_MF.almPLCFault.AENotify,429909,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_3A_MF.almPLCFault.AESeverity,429910,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_3A_MF.almPLCFault.AEShelveDuration,429911,Short,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_3B_XF.Alarm.BOOLS1,429926,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_3B_XF.Alarm.BOOLS2,429927,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_3B_XF.Alarm.AEBOOLS,429928,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_3B_XF.Alarm.INT1,429929,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3B_XF.Alarm.INT2,429930,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3B_XF.Alarm.AENotify,429931,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_3B_XF.Alarm.AESeverity,429932,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_3B_XF.Alarm.AEShelveDuration,429933,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0117_3B_XF.almPLCFault.BOOLS1,429938,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0117_3B_XF.almPLCFault.BOOLS2,429939,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0117_3B_XF.almPLCFault.AEBOOLS,429940,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0117_3B_XF.almPLCFault.INT1,429941,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3B_XF.almPLCFault.INT2,429942,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0117_3B_XF.almPLCFault.AENotify,429943,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0117_3B_XF.almPLCFault.AESeverity,429944,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0117_3B_XF.almPLCFault.AEShelveDuration,429945,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_LH1.Alarm.BOOLS1,429962,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_LH1.Alarm.BOOLS2,429963,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_LH1.Alarm.AEBOOLS,429964,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_LH1.Alarm.INT1,429965,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH1.Alarm.INT2,429966,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH1.Alarm.AENotify,429967,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_LH1.Alarm.AESeverity,429968,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_LH1.Alarm.AEShelveDuration,429969,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_LH1.almPLCFault.BOOLS1,429974,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_LH1.almPLCFault.BOOLS2,429975,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_LH1.almPLCFault.AEBOOLS,429976,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_LH1.almPLCFault.INT1,429977,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH1.almPLCFault.INT2,429978,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH1.almPLCFault.AENotify,429979,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_LH1.almPLCFault.AESeverity,429980,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_LH1.almPLCFault.AEShelveDuration,429981,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_LH2.Alarm.BOOLS1,429996,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_LH2.Alarm.BOOLS2,429997,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_LH2.Alarm.AEBOOLS,429998,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_LH2.Alarm.INT1,429999,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH2.Alarm.INT2,430000,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH2.Alarm.AENotify,430001,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_LH2.Alarm.AESeverity,430002,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_LH2.Alarm.AEShelveDuration,430003,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_LH2.almPLCFault.BOOLS1,430008,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_LH2.almPLCFault.BOOLS2,430009,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_LH2.almPLCFault.AEBOOLS,430010,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_LH2.almPLCFault.INT1,430011,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH2.almPLCFault.INT2,430012,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_LH2.almPLCFault.AENotify,430013,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_LH2.almPLCFault.AESeverity,430014,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_LH2.almPLCFault.AEShelveDuration,430015,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_XA.Alarm.BOOLS1,430032,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_XA.Alarm.BOOLS2,430033,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_XA.Alarm.AEBOOLS,430034,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_XA.Alarm.INT1,430035,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_XA.Alarm.INT2,430036,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_XA.Alarm.AENotify,430037,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_XA.Alarm.AESeverity,430038,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_XA.Alarm.AEShelveDuration,430039,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1_XA.almPLCFault.BOOLS1,430044,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1_XA.almPLCFault.BOOLS2,430045,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1_XA.almPLCFault.AEBOOLS,430046,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1_XA.almPLCFault.INT1,430047,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_XA.almPLCFault.INT2,430048,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1_XA.almPLCFault.AENotify,430049,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1_XA.almPLCFault.AESeverity,430050,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1_XA.almPLCFault.AEShelveDuration,430051,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1A_MF.Alarm.BOOLS1,430066,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1A_MF.Alarm.BOOLS2,430067,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1A_MF.Alarm.AEBOOLS,430068,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1A_MF.Alarm.INT1,430069,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1A_MF.Alarm.INT2,430070,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1A_MF.Alarm.AENotify,430071,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1A_MF.Alarm.AESeverity,430072,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1A_MF.Alarm.AEShelveDuration,430073,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1A_MF.almPLCFault.BOOLS1,430078,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1A_MF.almPLCFault.BOOLS2,430079,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1A_MF.almPLCFault.AEBOOLS,430080,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1A_MF.almPLCFault.INT1,430081,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1A_MF.almPLCFault.INT2,430082,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1A_MF.almPLCFault.AENotify,430083,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1A_MF.almPLCFault.AESeverity,430084,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1A_MF.almPLCFault.AEShelveDuration,430085,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1B_MF.Alarm.BOOLS1,430102,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1B_MF.Alarm.BOOLS2,430103,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1B_MF.Alarm.AEBOOLS,430104,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1B_MF.Alarm.INT1,430105,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1B_MF.Alarm.INT2,430106,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1B_MF.Alarm.AENotify,430107,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1B_MF.Alarm.AESeverity,430108,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1B_MF.Alarm.AEShelveDuration,430109,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_1B_MF.almPLCFault.BOOLS1,430114,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_1B_MF.almPLCFault.BOOLS2,430115,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_1B_MF.almPLCFault.AEBOOLS,430116,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_1B_MF.almPLCFault.INT1,430117,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1B_MF.almPLCFault.INT2,430118,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_1B_MF.almPLCFault.AENotify,430119,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_1B_MF.almPLCFault.AESeverity,430120,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_1B_MF.almPLCFault.AEShelveDuration,430121,Short,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_LH1.Alarm.BOOLS1,430136,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_LH1.Alarm.BOOLS2,430137,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_LH1.Alarm.AEBOOLS,430138,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_LH1.Alarm.INT1,430139,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH1.Alarm.INT2,430140,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH1.Alarm.AENotify,430141,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_LH1.Alarm.AESeverity,430142,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_LH1.Alarm.AEShelveDuration,430143,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_LH1.almPLCFault.BOOLS1,430148,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_LH1.almPLCFault.BOOLS2,430149,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_LH1.almPLCFault.AEBOOLS,430150,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_LH1.almPLCFault.INT1,430151,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH1.almPLCFault.INT2,430152,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH1.almPLCFault.AENotify,430153,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_LH1.almPLCFault.AESeverity,430154,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_LH1.almPLCFault.AEShelveDuration,430155,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_LH2.Alarm.BOOLS1,430172,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_LH2.Alarm.BOOLS2,430173,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_LH2.Alarm.AEBOOLS,430174,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_LH2.Alarm.INT1,430175,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH2.Alarm.INT2,430176,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH2.Alarm.AENotify,430177,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_LH2.Alarm.AESeverity,430178,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_LH2.Alarm.AEShelveDuration,430179,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_LH2.almPLCFault.BOOLS1,430184,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_LH2.almPLCFault.BOOLS2,430185,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_LH2.almPLCFault.AEBOOLS,430186,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_LH2.almPLCFault.INT1,430187,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH2.almPLCFault.INT2,430188,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_LH2.almPLCFault.AENotify,430189,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_LH2.almPLCFault.AESeverity,430190,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_LH2.almPLCFault.AEShelveDuration,430191,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_XA.Alarm.BOOLS1,430206,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_XA.Alarm.BOOLS2,430207,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_XA.Alarm.AEBOOLS,430208,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_XA.Alarm.INT1,430209,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_XA.Alarm.INT2,430210,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_XA.Alarm.AENotify,430211,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_XA.Alarm.AESeverity,430212,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_XA.Alarm.AEShelveDuration,430213,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2_XA.almPLCFault.BOOLS1,430218,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2_XA.almPLCFault.BOOLS2,430219,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2_XA.almPLCFault.AEBOOLS,430220,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2_XA.almPLCFault.INT1,430221,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_XA.almPLCFault.INT2,430222,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2_XA.almPLCFault.AENotify,430223,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2_XA.almPLCFault.AESeverity,430224,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2_XA.almPLCFault.AEShelveDuration,430225,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2A_MF.Alarm.BOOLS1,430242,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2A_MF.Alarm.BOOLS2,430243,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2A_MF.Alarm.AEBOOLS,430244,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2A_MF.Alarm.INT1,430245,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2A_MF.Alarm.INT2,430246,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2A_MF.Alarm.AENotify,430247,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2A_MF.Alarm.AESeverity,430248,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2A_MF.Alarm.AEShelveDuration,430249,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2A_MF.almPLCFault.BOOLS1,430254,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2A_MF.almPLCFault.BOOLS2,430255,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2A_MF.almPLCFault.AEBOOLS,430256,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2A_MF.almPLCFault.INT1,430257,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2A_MF.almPLCFault.INT2,430258,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2A_MF.almPLCFault.AENotify,430259,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2A_MF.almPLCFault.AESeverity,430260,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2A_MF.almPLCFault.AEShelveDuration,430261,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2B_MF.Alarm.BOOLS1,430276,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2B_MF.Alarm.BOOLS2,430277,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2B_MF.Alarm.AEBOOLS,430278,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2B_MF.Alarm.INT1,430279,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2B_MF.Alarm.INT2,430280,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2B_MF.Alarm.AENotify,430281,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2B_MF.Alarm.AESeverity,430282,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2B_MF.Alarm.AEShelveDuration,430283,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_CP_0118_2B_MF.almPLCFault.BOOLS1,430288,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_CP_0118_2B_MF.almPLCFault.BOOLS2,430289,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_CP_0118_2B_MF.almPLCFault.AEBOOLS,430290,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_CP_0118_2B_MF.almPLCFault.INT1,430291,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2B_MF.almPLCFault.INT2,430292,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_CP_0118_2B_MF.almPLCFault.AENotify,430293,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_CP_0118_2B_MF.almPLCFault.AESeverity,430294,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_CP_0118_2B_MF.almPLCFault.AEShelveDuration,430295,Short,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_WH.Alarm.BOOLS1,430312,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_WH.Alarm.BOOLS2,430313,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_WH.Alarm.AEBOOLS,430314,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_WH.Alarm.INT1,430315,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_WH.Alarm.INT2,430316,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_WH.Alarm.AENotify,430317,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_WH.Alarm.AESeverity,430318,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_WH.Alarm.AEShelveDuration,430319,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A_WH.almPLCFault.BOOLS1,430324,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A_WH.almPLCFault.BOOLS2,430325,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A_WH.almPLCFault.AEBOOLS,430326,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A_WH.almPLCFault.INT1,430327,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_WH.almPLCFault.INT2,430328,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A_WH.almPLCFault.AENotify,430329,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A_WH.almPLCFault.AESeverity,430330,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A_WH.almPLCFault.AEShelveDuration,430331,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_WH.Alarm.BOOLS1,430346,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_WH.Alarm.BOOLS2,430347,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_WH.Alarm.AEBOOLS,430348,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_WH.Alarm.INT1,430349,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_WH.Alarm.INT2,430350,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_WH.Alarm.AENotify,430351,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_WH.Alarm.AESeverity,430352,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_WH.Alarm.AEShelveDuration,430353,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B_WH.almPLCFault.BOOLS1,430358,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B_WH.almPLCFault.BOOLS2,430359,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B_WH.almPLCFault.AEBOOLS,430360,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B_WH.almPLCFault.INT1,430361,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_WH.almPLCFault.INT2,430362,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B_WH.almPLCFault.AENotify,430363,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B_WH.almPLCFault.AESeverity,430364,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B_WH.almPLCFault.AEShelveDuration,430365,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FLT_0112_1_XA.Alarm.BOOLS1,430382,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FLT_0112_1_XA.Alarm.BOOLS2,430383,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FLT_0112_1_XA.Alarm.AEBOOLS,430384,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FLT_0112_1_XA.Alarm.INT1,430385,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_1_XA.Alarm.INT2,430386,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_1_XA.Alarm.AENotify,430387,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FLT_0112_1_XA.Alarm.AESeverity,430388,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FLT_0112_1_XA.Alarm.AEShelveDuration,430389,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FLT_0112_1_XA.almPLCFault.BOOLS1,430394,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FLT_0112_1_XA.almPLCFault.BOOLS2,430395,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FLT_0112_1_XA.almPLCFault.AEBOOLS,430396,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FLT_0112_1_XA.almPLCFault.INT1,430397,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_1_XA.almPLCFault.INT2,430398,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_1_XA.almPLCFault.AENotify,430399,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FLT_0112_1_XA.almPLCFault.AESeverity,430400,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FLT_0112_1_XA.almPLCFault.AEShelveDuration,430401,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FLT_0112_2_XA.Alarm.BOOLS1,430416,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FLT_0112_2_XA.Alarm.BOOLS2,430417,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FLT_0112_2_XA.Alarm.AEBOOLS,430418,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FLT_0112_2_XA.Alarm.INT1,430419,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_2_XA.Alarm.INT2,430420,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_2_XA.Alarm.AENotify,430421,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FLT_0112_2_XA.Alarm.AESeverity,430422,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FLT_0112_2_XA.Alarm.AEShelveDuration,430423,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FLT_0112_2_XA.almPLCFault.BOOLS1,430428,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FLT_0112_2_XA.almPLCFault.BOOLS2,430429,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FLT_0112_2_XA.almPLCFault.AEBOOLS,430430,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FLT_0112_2_XA.almPLCFault.INT1,430431,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_2_XA.almPLCFault.INT2,430432,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FLT_0112_2_XA.almPLCFault.AENotify,430433,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FLT_0112_2_XA.almPLCFault.AESeverity,430434,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FLT_0112_2_XA.almPLCFault.AEShelveDuration,430435,Short,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A_WH.Alarm.BOOLS1,430452,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A_WH.Alarm.BOOLS2,430453,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A_WH.Alarm.AEBOOLS,430454,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A_WH.Alarm.INT1,430455,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A_WH.Alarm.INT2,430456,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A_WH.Alarm.AENotify,430457,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A_WH.Alarm.AESeverity,430458,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A_WH.Alarm.AEShelveDuration,430459,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A_WH.almPLCFault.BOOLS1,430464,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A_WH.almPLCFault.BOOLS2,430465,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A_WH.almPLCFault.AEBOOLS,430466,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A_WH.almPLCFault.INT1,430467,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A_WH.almPLCFault.INT2,430468,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A_WH.almPLCFault.AENotify,430469,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A_WH.almPLCFault.AESeverity,430470,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A_WH.almPLCFault.AEShelveDuration,430471,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B_WH.Alarm.BOOLS1,430486,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B_WH.Alarm.BOOLS2,430487,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B_WH.Alarm.AEBOOLS,430488,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B_WH.Alarm.INT1,430489,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B_WH.Alarm.INT2,430490,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B_WH.Alarm.AENotify,430491,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B_WH.Alarm.AESeverity,430492,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B_WH.Alarm.AEShelveDuration,430493,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B_WH.almPLCFault.BOOLS1,430498,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B_WH.almPLCFault.BOOLS2,430499,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B_WH.almPLCFault.AEBOOLS,430500,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B_WH.almPLCFault.INT1,430501,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B_WH.almPLCFault.INT2,430502,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B_WH.almPLCFault.AENotify,430503,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B_WH.almPLCFault.AESeverity,430504,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B_WH.almPLCFault.AEShelveDuration,430505,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A_WH.Alarm.BOOLS1,430522,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A_WH.Alarm.BOOLS2,430523,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A_WH.Alarm.AEBOOLS,430524,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A_WH.Alarm.INT1,430525,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A_WH.Alarm.INT2,430526,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A_WH.Alarm.AENotify,430527,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A_WH.Alarm.AESeverity,430528,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A_WH.Alarm.AEShelveDuration,430529,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A_WH.almPLCFault.BOOLS1,430534,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A_WH.almPLCFault.BOOLS2,430535,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A_WH.almPLCFault.AEBOOLS,430536,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A_WH.almPLCFault.INT1,430537,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A_WH.almPLCFault.INT2,430538,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A_WH.almPLCFault.AENotify,430539,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A_WH.almPLCFault.AESeverity,430540,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A_WH.almPLCFault.AEShelveDuration,430541,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B_WH.Alarm.BOOLS1,430556,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B_WH.Alarm.BOOLS2,430557,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B_WH.Alarm.AEBOOLS,430558,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B_WH.Alarm.INT1,430559,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B_WH.Alarm.INT2,430560,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B_WH.Alarm.AENotify,430561,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B_WH.Alarm.AESeverity,430562,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B_WH.Alarm.AEShelveDuration,430563,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B_WH.almPLCFault.BOOLS1,430568,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B_WH.almPLCFault.BOOLS2,430569,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B_WH.almPLCFault.AEBOOLS,430570,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B_WH.almPLCFault.INT1,430571,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B_WH.almPLCFault.INT2,430572,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B_WH.almPLCFault.AENotify,430573,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B_WH.almPLCFault.AESeverity,430574,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B_WH.almPLCFault.AEShelveDuration,430575,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A_WH.Alarm.BOOLS1,430592,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A_WH.Alarm.BOOLS2,430593,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A_WH.Alarm.AEBOOLS,430594,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A_WH.Alarm.INT1,430595,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A_WH.Alarm.INT2,430596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A_WH.Alarm.AENotify,430597,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A_WH.Alarm.AESeverity,430598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A_WH.Alarm.AEShelveDuration,430599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A_WH.almPLCFault.BOOLS1,430604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A_WH.almPLCFault.BOOLS2,430605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A_WH.almPLCFault.AEBOOLS,430606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A_WH.almPLCFault.INT1,430607,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A_WH.almPLCFault.INT2,430608,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A_WH.almPLCFault.AENotify,430609,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A_WH.almPLCFault.AESeverity,430610,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A_WH.almPLCFault.AEShelveDuration,430611,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZF.Alarm.BOOLS1,430626,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZF.Alarm.BOOLS2,430627,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZF.Alarm.AEBOOLS,430628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZF.Alarm.INT1,430629,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF.Alarm.INT2,430630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF.Alarm.AENotify,430631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZF.Alarm.AESeverity,430632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZF.Alarm.AEShelveDuration,430633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZF.almPLCFault.BOOLS1,430638,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZF.almPLCFault.BOOLS2,430639,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZF.almPLCFault.AEBOOLS,430640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZF.almPLCFault.INT1,430641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF.almPLCFault.INT2,430642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF.almPLCFault.AENotify,430643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZF.almPLCFault.AESeverity,430644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZF.almPLCFault.AEShelveDuration,430645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZF2.Alarm.BOOLS1,430662,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZF2.Alarm.BOOLS2,430663,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZF2.Alarm.AEBOOLS,430664,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZF2.Alarm.INT1,430665,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF2.Alarm.INT2,430666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF2.Alarm.AENotify,430667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZF2.Alarm.AESeverity,430668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZF2.Alarm.AEShelveDuration,430669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1B_ZF2.almPLCFault.BOOLS1,430674,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1B_ZF2.almPLCFault.BOOLS2,430675,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1B_ZF2.almPLCFault.AEBOOLS,430676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1B_ZF2.almPLCFault.INT1,430677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF2.almPLCFault.INT2,430678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1B_ZF2.almPLCFault.AENotify,430679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1B_ZF2.almPLCFault.AESeverity,430680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1B_ZF2.almPLCFault.AEShelveDuration,430681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C_WH.Alarm.BOOLS1,430696,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C_WH.Alarm.BOOLS2,430697,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C_WH.Alarm.AEBOOLS,430698,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C_WH.Alarm.INT1,430699,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C_WH.Alarm.INT2,430700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C_WH.Alarm.AENotify,430701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C_WH.Alarm.AESeverity,430702,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C_WH.Alarm.AEShelveDuration,430703,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C_WH.almPLCFault.BOOLS1,430708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C_WH.almPLCFault.BOOLS2,430709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C_WH.almPLCFault.AEBOOLS,430710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C_WH.almPLCFault.INT1,430711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C_WH.almPLCFault.INT2,430712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C_WH.almPLCFault.AENotify,430713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C_WH.almPLCFault.AESeverity,430714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C_WH.almPLCFault.AEShelveDuration,430715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A_WH.Alarm.BOOLS1,430732,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A_WH.Alarm.BOOLS2,430733,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A_WH.Alarm.AEBOOLS,430734,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A_WH.Alarm.INT1,430735,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A_WH.Alarm.INT2,430736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A_WH.Alarm.AENotify,430737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A_WH.Alarm.AESeverity,430738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A_WH.Alarm.AEShelveDuration,430739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A_WH.almPLCFault.BOOLS1,430744,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A_WH.almPLCFault.BOOLS2,430745,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A_WH.almPLCFault.AEBOOLS,430746,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A_WH.almPLCFault.INT1,430747,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A_WH.almPLCFault.INT2,430748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A_WH.almPLCFault.AENotify,430749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A_WH.almPLCFault.AESeverity,430750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A_WH.almPLCFault.AEShelveDuration,430751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZF.Alarm.BOOLS1,430766,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZF.Alarm.BOOLS2,430767,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZF.Alarm.AEBOOLS,430768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZF.Alarm.INT1,430769,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF.Alarm.INT2,430770,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF.Alarm.AENotify,430771,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZF.Alarm.AESeverity,430772,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZF.Alarm.AEShelveDuration,430773,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZF.almPLCFault.BOOLS1,430778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZF.almPLCFault.BOOLS2,430779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZF.almPLCFault.AEBOOLS,430780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZF.almPLCFault.INT1,430781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF.almPLCFault.INT2,430782,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF.almPLCFault.AENotify,430783,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZF.almPLCFault.AESeverity,430784,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZF.almPLCFault.AEShelveDuration,430785,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZF2.Alarm.BOOLS1,430802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZF2.Alarm.BOOLS2,430803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZF2.Alarm.AEBOOLS,430804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZF2.Alarm.INT1,430805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF2.Alarm.INT2,430806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF2.Alarm.AENotify,430807,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZF2.Alarm.AESeverity,430808,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZF2.Alarm.AEShelveDuration,430809,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2B_ZF2.almPLCFault.BOOLS1,430814,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2B_ZF2.almPLCFault.BOOLS2,430815,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2B_ZF2.almPLCFault.AEBOOLS,430816,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2B_ZF2.almPLCFault.INT1,430817,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF2.almPLCFault.INT2,430818,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2B_ZF2.almPLCFault.AENotify,430819,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2B_ZF2.almPLCFault.AESeverity,430820,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2B_ZF2.almPLCFault.AEShelveDuration,430821,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C_WH.Alarm.BOOLS1,430836,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C_WH.Alarm.BOOLS2,430837,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C_WH.Alarm.AEBOOLS,430838,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C_WH.Alarm.INT1,430839,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C_WH.Alarm.INT2,430840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C_WH.Alarm.AENotify,430841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C_WH.Alarm.AESeverity,430842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C_WH.Alarm.AEShelveDuration,430843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C_WH.almPLCFault.BOOLS1,430848,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C_WH.almPLCFault.BOOLS2,430849,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C_WH.almPLCFault.AEBOOLS,430850,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C_WH.almPLCFault.INT1,430851,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C_WH.almPLCFault.INT2,430852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C_WH.almPLCFault.AENotify,430853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C_WH.almPLCFault.AESeverity,430854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C_WH.almPLCFault.AEShelveDuration,430855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A_WH.Alarm.BOOLS1,430872,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A_WH.Alarm.BOOLS2,430873,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A_WH.Alarm.AEBOOLS,430874,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A_WH.Alarm.INT1,430875,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A_WH.Alarm.INT2,430876,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A_WH.Alarm.AENotify,430877,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A_WH.Alarm.AESeverity,430878,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A_WH.Alarm.AEShelveDuration,430879,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A_WH.almPLCFault.BOOLS1,430884,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A_WH.almPLCFault.BOOLS2,430885,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A_WH.almPLCFault.AEBOOLS,430886,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A_WH.almPLCFault.INT1,430887,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A_WH.almPLCFault.INT2,430888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A_WH.almPLCFault.AENotify,430889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A_WH.almPLCFault.AESeverity,430890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A_WH.almPLCFault.AEShelveDuration,430891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF.Alarm.BOOLS1,430906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF.Alarm.BOOLS2,430907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF.Alarm.AEBOOLS,430908,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF.Alarm.INT1,430909,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF.Alarm.INT2,430910,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF.Alarm.AENotify,430911,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF.Alarm.AESeverity,430912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF.Alarm.AEShelveDuration,430913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF.almPLCFault.BOOLS1,430918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF.almPLCFault.BOOLS2,430919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF.almPLCFault.AEBOOLS,430920,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF.almPLCFault.INT1,430921,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF.almPLCFault.INT2,430922,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF.almPLCFault.AENotify,430923,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF.almPLCFault.AESeverity,430924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF.almPLCFault.AEShelveDuration,430925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF3.Alarm.BOOLS1,430942,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF3.Alarm.BOOLS2,430943,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF3.Alarm.AEBOOLS,430944,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF3.Alarm.INT1,430945,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF3.Alarm.INT2,430946,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF3.Alarm.AENotify,430947,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF3.Alarm.AESeverity,430948,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF3.Alarm.AEShelveDuration,430949,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF3.almPLCFault.BOOLS1,430954,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF3.almPLCFault.BOOLS2,430955,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF3.almPLCFault.AEBOOLS,430956,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF3.almPLCFault.INT1,430957,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF3.almPLCFault.INT2,430958,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF3.almPLCFault.AENotify,430959,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF3.almPLCFault.AESeverity,430960,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF3.almPLCFault.AEShelveDuration,430961,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF4.Alarm.BOOLS1,430976,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF4.Alarm.BOOLS2,430977,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF4.Alarm.AEBOOLS,430978,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF4.Alarm.INT1,430979,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF4.Alarm.INT2,430980,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF4.Alarm.AENotify,430981,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF4.Alarm.AESeverity,430982,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF4.Alarm.AEShelveDuration,430983,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3B_ZF4.almPLCFault.BOOLS1,430988,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3B_ZF4.almPLCFault.BOOLS2,430989,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3B_ZF4.almPLCFault.AEBOOLS,430990,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3B_ZF4.almPLCFault.INT1,430991,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF4.almPLCFault.INT2,430992,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3B_ZF4.almPLCFault.AENotify,430993,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3B_ZF4.almPLCFault.AESeverity,430994,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3B_ZF4.almPLCFault.AEShelveDuration,430995,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C_WH.Alarm.BOOLS1,431012,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C_WH.Alarm.BOOLS2,431013,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C_WH.Alarm.AEBOOLS,431014,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C_WH.Alarm.INT1,431015,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C_WH.Alarm.INT2,431016,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C_WH.Alarm.AENotify,431017,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C_WH.Alarm.AESeverity,431018,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C_WH.Alarm.AEShelveDuration,431019,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C_WH.almPLCFault.BOOLS1,431024,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C_WH.almPLCFault.BOOLS2,431025,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C_WH.almPLCFault.AEBOOLS,431026,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C_WH.almPLCFault.INT1,431027,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C_WH.almPLCFault.INT2,431028,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C_WH.almPLCFault.AENotify,431029,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C_WH.almPLCFault.AESeverity,431030,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C_WH.almPLCFault.AEShelveDuration,431031,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D_WH.Alarm.BOOLS1,431046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D_WH.Alarm.BOOLS2,431047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D_WH.Alarm.AEBOOLS,431048,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D_WH.Alarm.INT1,431049,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D_WH.Alarm.INT2,431050,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D_WH.Alarm.AENotify,431051,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D_WH.Alarm.AESeverity,431052,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D_WH.Alarm.AEShelveDuration,431053,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D_WH.almPLCFault.BOOLS1,431058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D_WH.almPLCFault.BOOLS2,431059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D_WH.almPLCFault.AEBOOLS,431060,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D_WH.almPLCFault.INT1,431061,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D_WH.almPLCFault.INT2,431062,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D_WH.almPLCFault.AENotify,431063,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D_WH.almPLCFault.AESeverity,431064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D_WH.almPLCFault.AEShelveDuration,431065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A_WH.Alarm.BOOLS1,431082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A_WH.Alarm.BOOLS2,431083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A_WH.Alarm.AEBOOLS,431084,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A_WH.Alarm.INT1,431085,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A_WH.Alarm.INT2,431086,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A_WH.Alarm.AENotify,431087,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A_WH.Alarm.AESeverity,431088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A_WH.Alarm.AEShelveDuration,431089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A_WH.almPLCFault.BOOLS1,431094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A_WH.almPLCFault.BOOLS2,431095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A_WH.almPLCFault.AEBOOLS,431096,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A_WH.almPLCFault.INT1,431097,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A_WH.almPLCFault.INT2,431098,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A_WH.almPLCFault.AENotify,431099,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A_WH.almPLCFault.AESeverity,431100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A_WH.almPLCFault.AEShelveDuration,431101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF.Alarm.BOOLS1,431116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF.Alarm.BOOLS2,431117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF.Alarm.AEBOOLS,431118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF.Alarm.INT1,431119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF.Alarm.INT2,431120,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF.Alarm.AENotify,431121,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF.Alarm.AESeverity,431122,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF.Alarm.AEShelveDuration,431123,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF.almPLCFault.BOOLS1,431128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF.almPLCFault.BOOLS2,431129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF.almPLCFault.AEBOOLS,431130,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF.almPLCFault.INT1,431131,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF.almPLCFault.INT2,431132,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF.almPLCFault.AENotify,431133,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF.almPLCFault.AESeverity,431134,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF.almPLCFault.AEShelveDuration,431135,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF3.Alarm.BOOLS1,431152,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF3.Alarm.BOOLS2,431153,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF3.Alarm.AEBOOLS,431154,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF3.Alarm.INT1,431155,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF3.Alarm.INT2,431156,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF3.Alarm.AENotify,431157,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF3.Alarm.AESeverity,431158,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF3.Alarm.AEShelveDuration,431159,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF3.almPLCFault.BOOLS1,431164,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF3.almPLCFault.BOOLS2,431165,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF3.almPLCFault.AEBOOLS,431166,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF3.almPLCFault.INT1,431167,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF3.almPLCFault.INT2,431168,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF3.almPLCFault.AENotify,431169,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF3.almPLCFault.AESeverity,431170,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF3.almPLCFault.AEShelveDuration,431171,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF4.Alarm.BOOLS1,431186,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF4.Alarm.BOOLS2,431187,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF4.Alarm.AEBOOLS,431188,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF4.Alarm.INT1,431189,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF4.Alarm.INT2,431190,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF4.Alarm.AENotify,431191,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF4.Alarm.AESeverity,431192,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF4.Alarm.AEShelveDuration,431193,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4B_ZF4.almPLCFault.BOOLS1,431198,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4B_ZF4.almPLCFault.BOOLS2,431199,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4B_ZF4.almPLCFault.AEBOOLS,431200,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4B_ZF4.almPLCFault.INT1,431201,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF4.almPLCFault.INT2,431202,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4B_ZF4.almPLCFault.AENotify,431203,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4B_ZF4.almPLCFault.AESeverity,431204,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4B_ZF4.almPLCFault.AEShelveDuration,431205,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C_WH.Alarm.BOOLS1,431222,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C_WH.Alarm.BOOLS2,431223,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C_WH.Alarm.AEBOOLS,431224,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C_WH.Alarm.INT1,431225,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C_WH.Alarm.INT2,431226,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C_WH.Alarm.AENotify,431227,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C_WH.Alarm.AESeverity,431228,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C_WH.Alarm.AEShelveDuration,431229,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C_WH.almPLCFault.BOOLS1,431234,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C_WH.almPLCFault.BOOLS2,431235,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C_WH.almPLCFault.AEBOOLS,431236,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C_WH.almPLCFault.INT1,431237,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C_WH.almPLCFault.INT2,431238,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C_WH.almPLCFault.AENotify,431239,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C_WH.almPLCFault.AESeverity,431240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C_WH.almPLCFault.AEShelveDuration,431241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D_WH.Alarm.BOOLS1,431256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D_WH.Alarm.BOOLS2,431257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D_WH.Alarm.AEBOOLS,431258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D_WH.Alarm.INT1,431259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D_WH.Alarm.INT2,431260,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D_WH.Alarm.AENotify,431261,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D_WH.Alarm.AESeverity,431262,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D_WH.Alarm.AEShelveDuration,431263,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D_WH.almPLCFault.BOOLS1,431268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D_WH.almPLCFault.BOOLS2,431269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D_WH.almPLCFault.AEBOOLS,431270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D_WH.almPLCFault.INT1,431271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D_WH.almPLCFault.INT2,431272,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D_WH.almPLCFault.AENotify,431273,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D_WH.almPLCFault.AESeverity,431274,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D_WH.almPLCFault.AEShelveDuration,431275,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A_WH.Alarm.BOOLS1,431292,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A_WH.Alarm.BOOLS2,431293,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A_WH.Alarm.AEBOOLS,431294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A_WH.Alarm.INT1,431295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A_WH.Alarm.INT2,431296,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A_WH.Alarm.AENotify,431297,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A_WH.Alarm.AESeverity,431298,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A_WH.Alarm.AEShelveDuration,431299,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A_WH.almPLCFault.BOOLS1,431304,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A_WH.almPLCFault.BOOLS2,431305,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A_WH.almPLCFault.AEBOOLS,431306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A_WH.almPLCFault.INT1,431307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A_WH.almPLCFault.INT2,431308,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A_WH.almPLCFault.AENotify,431309,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A_WH.almPLCFault.AESeverity,431310,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A_WH.almPLCFault.AEShelveDuration,431311,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF.Alarm.BOOLS1,431326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF.Alarm.BOOLS2,431327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF.Alarm.AEBOOLS,431328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF.Alarm.INT1,431329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF.Alarm.INT2,431330,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF.Alarm.AENotify,431331,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF.Alarm.AESeverity,431332,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF.Alarm.AEShelveDuration,431333,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF.almPLCFault.BOOLS1,431338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF.almPLCFault.BOOLS2,431339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF.almPLCFault.AEBOOLS,431340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF.almPLCFault.INT1,431341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF.almPLCFault.INT2,431342,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF.almPLCFault.AENotify,431343,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF.almPLCFault.AESeverity,431344,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF.almPLCFault.AEShelveDuration,431345,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF3.Alarm.BOOLS1,431362,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF3.Alarm.BOOLS2,431363,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF3.Alarm.AEBOOLS,431364,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF3.Alarm.INT1,431365,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF3.Alarm.INT2,431366,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF3.Alarm.AENotify,431367,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF3.Alarm.AESeverity,431368,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF3.Alarm.AEShelveDuration,431369,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF3.almPLCFault.BOOLS1,431374,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF3.almPLCFault.BOOLS2,431375,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF3.almPLCFault.AEBOOLS,431376,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF3.almPLCFault.INT1,431377,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF3.almPLCFault.INT2,431378,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF3.almPLCFault.AENotify,431379,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF3.almPLCFault.AESeverity,431380,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF3.almPLCFault.AEShelveDuration,431381,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF4.Alarm.BOOLS1,431396,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF4.Alarm.BOOLS2,431397,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF4.Alarm.AEBOOLS,431398,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF4.Alarm.INT1,431399,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF4.Alarm.INT2,431400,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF4.Alarm.AENotify,431401,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF4.Alarm.AESeverity,431402,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF4.Alarm.AEShelveDuration,431403,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5B_ZF4.almPLCFault.BOOLS1,431408,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5B_ZF4.almPLCFault.BOOLS2,431409,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5B_ZF4.almPLCFault.AEBOOLS,431410,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5B_ZF4.almPLCFault.INT1,431411,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF4.almPLCFault.INT2,431412,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5B_ZF4.almPLCFault.AENotify,431413,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5B_ZF4.almPLCFault.AESeverity,431414,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5B_ZF4.almPLCFault.AEShelveDuration,431415,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C_WH.Alarm.BOOLS1,431432,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C_WH.Alarm.BOOLS2,431433,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C_WH.Alarm.AEBOOLS,431434,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C_WH.Alarm.INT1,431435,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C_WH.Alarm.INT2,431436,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C_WH.Alarm.AENotify,431437,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C_WH.Alarm.AESeverity,431438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C_WH.Alarm.AEShelveDuration,431439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C_WH.almPLCFault.BOOLS1,431444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C_WH.almPLCFault.BOOLS2,431445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C_WH.almPLCFault.AEBOOLS,431446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C_WH.almPLCFault.INT1,431447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C_WH.almPLCFault.INT2,431448,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C_WH.almPLCFault.AENotify,431449,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C_WH.almPLCFault.AESeverity,431450,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C_WH.almPLCFault.AEShelveDuration,431451,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D_WH.Alarm.BOOLS1,431466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D_WH.Alarm.BOOLS2,431467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D_WH.Alarm.AEBOOLS,431468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D_WH.Alarm.INT1,431469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D_WH.Alarm.INT2,431470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D_WH.Alarm.AENotify,431471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D_WH.Alarm.AESeverity,431472,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D_WH.Alarm.AEShelveDuration,431473,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D_WH.almPLCFault.BOOLS1,431478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D_WH.almPLCFault.BOOLS2,431479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D_WH.almPLCFault.AEBOOLS,431480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D_WH.almPLCFault.INT1,431481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D_WH.almPLCFault.INT2,431482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D_WH.almPLCFault.AENotify,431483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D_WH.almPLCFault.AESeverity,431484,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D_WH.almPLCFault.AEShelveDuration,431485,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A_WH.Alarm.BOOLS1,431502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A_WH.Alarm.BOOLS2,431503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A_WH.Alarm.AEBOOLS,431504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A_WH.Alarm.INT1,431505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A_WH.Alarm.INT2,431506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A_WH.Alarm.AENotify,431507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A_WH.Alarm.AESeverity,431508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A_WH.Alarm.AEShelveDuration,431509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A_WH.almPLCFault.BOOLS1,431514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A_WH.almPLCFault.BOOLS2,431515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A_WH.almPLCFault.AEBOOLS,431516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A_WH.almPLCFault.INT1,431517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A_WH.almPLCFault.INT2,431518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A_WH.almPLCFault.AENotify,431519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A_WH.almPLCFault.AESeverity,431520,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A_WH.almPLCFault.AEShelveDuration,431521,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF.Alarm.BOOLS1,431536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF.Alarm.BOOLS2,431537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF.Alarm.AEBOOLS,431538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF.Alarm.INT1,431539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF.Alarm.INT2,431540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF.Alarm.AENotify,431541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF.Alarm.AESeverity,431542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF.Alarm.AEShelveDuration,431543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF.almPLCFault.BOOLS1,431548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF.almPLCFault.BOOLS2,431549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF.almPLCFault.AEBOOLS,431550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF.almPLCFault.INT1,431551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF.almPLCFault.INT2,431552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF.almPLCFault.AENotify,431553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF.almPLCFault.AESeverity,431554,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF.almPLCFault.AEShelveDuration,431555,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF3.Alarm.BOOLS1,431572,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF3.Alarm.BOOLS2,431573,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF3.Alarm.AEBOOLS,431574,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF3.Alarm.INT1,431575,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF3.Alarm.INT2,431576,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF3.Alarm.AENotify,431577,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF3.Alarm.AESeverity,431578,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF3.Alarm.AEShelveDuration,431579,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF3.almPLCFault.BOOLS1,431584,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF3.almPLCFault.BOOLS2,431585,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF3.almPLCFault.AEBOOLS,431586,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF3.almPLCFault.INT1,431587,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF3.almPLCFault.INT2,431588,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF3.almPLCFault.AENotify,431589,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF3.almPLCFault.AESeverity,431590,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF3.almPLCFault.AEShelveDuration,431591,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF4.Alarm.BOOLS1,431606,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF4.Alarm.BOOLS2,431607,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF4.Alarm.AEBOOLS,431608,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF4.Alarm.INT1,431609,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF4.Alarm.INT2,431610,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF4.Alarm.AENotify,431611,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF4.Alarm.AESeverity,431612,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF4.Alarm.AEShelveDuration,431613,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6B_ZF4.almPLCFault.BOOLS1,431618,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6B_ZF4.almPLCFault.BOOLS2,431619,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6B_ZF4.almPLCFault.AEBOOLS,431620,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6B_ZF4.almPLCFault.INT1,431621,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF4.almPLCFault.INT2,431622,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6B_ZF4.almPLCFault.AENotify,431623,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6B_ZF4.almPLCFault.AESeverity,431624,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6B_ZF4.almPLCFault.AEShelveDuration,431625,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C_WH.Alarm.BOOLS1,431642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C_WH.Alarm.BOOLS2,431643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C_WH.Alarm.AEBOOLS,431644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C_WH.Alarm.INT1,431645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C_WH.Alarm.INT2,431646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C_WH.Alarm.AENotify,431647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C_WH.Alarm.AESeverity,431648,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C_WH.Alarm.AEShelveDuration,431649,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C_WH.almPLCFault.BOOLS1,431654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C_WH.almPLCFault.BOOLS2,431655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C_WH.almPLCFault.AEBOOLS,431656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C_WH.almPLCFault.INT1,431657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C_WH.almPLCFault.INT2,431658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C_WH.almPLCFault.AENotify,431659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C_WH.almPLCFault.AESeverity,431660,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C_WH.almPLCFault.AEShelveDuration,431661,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D_WH.Alarm.BOOLS1,431676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D_WH.Alarm.BOOLS2,431677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D_WH.Alarm.AEBOOLS,431678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D_WH.Alarm.INT1,431679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D_WH.Alarm.INT2,431680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D_WH.Alarm.AENotify,431681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D_WH.Alarm.AESeverity,431682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D_WH.Alarm.AEShelveDuration,431683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D_WH.almPLCFault.BOOLS1,431688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D_WH.almPLCFault.BOOLS2,431689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D_WH.almPLCFault.AEBOOLS,431690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D_WH.almPLCFault.INT1,431691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D_WH.almPLCFault.INT2,431692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D_WH.almPLCFault.AENotify,431693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D_WH.almPLCFault.AESeverity,431694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D_WH.almPLCFault.AEShelveDuration,431695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A_WH.Alarm.BOOLS1,431712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A_WH.Alarm.BOOLS2,431713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A_WH.Alarm.AEBOOLS,431714,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A_WH.Alarm.INT1,431715,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A_WH.Alarm.INT2,431716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A_WH.Alarm.AENotify,431717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A_WH.Alarm.AESeverity,431718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A_WH.Alarm.AEShelveDuration,431719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A_WH.almPLCFault.BOOLS1,431724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A_WH.almPLCFault.BOOLS2,431725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A_WH.almPLCFault.AEBOOLS,431726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A_WH.almPLCFault.INT1,431727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A_WH.almPLCFault.INT2,431728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A_WH.almPLCFault.AENotify,431729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A_WH.almPLCFault.AESeverity,431730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A_WH.almPLCFault.AEShelveDuration,431731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF.Alarm.BOOLS1,431746,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF.Alarm.BOOLS2,431747,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF.Alarm.AEBOOLS,431748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF.Alarm.INT1,431749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF.Alarm.INT2,431750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF.Alarm.AENotify,431751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF.Alarm.AESeverity,431752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF.Alarm.AEShelveDuration,431753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF.almPLCFault.BOOLS1,431758,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF.almPLCFault.BOOLS2,431759,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF.almPLCFault.AEBOOLS,431760,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF.almPLCFault.INT1,431761,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF.almPLCFault.INT2,431762,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF.almPLCFault.AENotify,431763,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF.almPLCFault.AESeverity,431764,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF.almPLCFault.AEShelveDuration,431765,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF3.Alarm.BOOLS1,431782,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF3.Alarm.BOOLS2,431783,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF3.Alarm.AEBOOLS,431784,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF3.Alarm.INT1,431785,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF3.Alarm.INT2,431786,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF3.Alarm.AENotify,431787,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF3.Alarm.AESeverity,431788,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF3.Alarm.AEShelveDuration,431789,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF3.almPLCFault.BOOLS1,431794,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF3.almPLCFault.BOOLS2,431795,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF3.almPLCFault.AEBOOLS,431796,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF3.almPLCFault.INT1,431797,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF3.almPLCFault.INT2,431798,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF3.almPLCFault.AENotify,431799,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF3.almPLCFault.AESeverity,431800,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF3.almPLCFault.AEShelveDuration,431801,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF4.Alarm.BOOLS1,431816,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF4.Alarm.BOOLS2,431817,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF4.Alarm.AEBOOLS,431818,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF4.Alarm.INT1,431819,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF4.Alarm.INT2,431820,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF4.Alarm.AENotify,431821,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF4.Alarm.AESeverity,431822,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF4.Alarm.AEShelveDuration,431823,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7B_ZF4.almPLCFault.BOOLS1,431828,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7B_ZF4.almPLCFault.BOOLS2,431829,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7B_ZF4.almPLCFault.AEBOOLS,431830,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7B_ZF4.almPLCFault.INT1,431831,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF4.almPLCFault.INT2,431832,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7B_ZF4.almPLCFault.AENotify,431833,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7B_ZF4.almPLCFault.AESeverity,431834,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7B_ZF4.almPLCFault.AEShelveDuration,431835,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C_WH.Alarm.BOOLS1,431852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C_WH.Alarm.BOOLS2,431853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C_WH.Alarm.AEBOOLS,431854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C_WH.Alarm.INT1,431855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C_WH.Alarm.INT2,431856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C_WH.Alarm.AENotify,431857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C_WH.Alarm.AESeverity,431858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C_WH.Alarm.AEShelveDuration,431859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C_WH.almPLCFault.BOOLS1,431864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C_WH.almPLCFault.BOOLS2,431865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C_WH.almPLCFault.AEBOOLS,431866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C_WH.almPLCFault.INT1,431867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C_WH.almPLCFault.INT2,431868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C_WH.almPLCFault.AENotify,431869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C_WH.almPLCFault.AESeverity,431870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C_WH.almPLCFault.AEShelveDuration,431871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D_WH.Alarm.BOOLS1,431886,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D_WH.Alarm.BOOLS2,431887,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D_WH.Alarm.AEBOOLS,431888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D_WH.Alarm.INT1,431889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D_WH.Alarm.INT2,431890,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D_WH.Alarm.AENotify,431891,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D_WH.Alarm.AESeverity,431892,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D_WH.Alarm.AEShelveDuration,431893,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D_WH.almPLCFault.BOOLS1,431898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D_WH.almPLCFault.BOOLS2,431899,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D_WH.almPLCFault.AEBOOLS,431900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D_WH.almPLCFault.INT1,431901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D_WH.almPLCFault.INT2,431902,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D_WH.almPLCFault.AENotify,431903,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D_WH.almPLCFault.AESeverity,431904,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D_WH.almPLCFault.AEShelveDuration,431905,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A_WH.Alarm.BOOLS1,431922,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A_WH.Alarm.BOOLS2,431923,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A_WH.Alarm.AEBOOLS,431924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A_WH.Alarm.INT1,431925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A_WH.Alarm.INT2,431926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A_WH.Alarm.AENotify,431927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A_WH.Alarm.AESeverity,431928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A_WH.Alarm.AEShelveDuration,431929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A_WH.almPLCFault.BOOLS1,431934,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A_WH.almPLCFault.BOOLS2,431935,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A_WH.almPLCFault.AEBOOLS,431936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A_WH.almPLCFault.INT1,431937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A_WH.almPLCFault.INT2,431938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A_WH.almPLCFault.AENotify,431939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A_WH.almPLCFault.AESeverity,431940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A_WH.almPLCFault.AEShelveDuration,431941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF.Alarm.BOOLS1,431956,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF.Alarm.BOOLS2,431957,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF.Alarm.AEBOOLS,431958,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF.Alarm.INT1,431959,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF.Alarm.INT2,431960,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF.Alarm.AENotify,431961,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF.Alarm.AESeverity,431962,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF.Alarm.AEShelveDuration,431963,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF.almPLCFault.BOOLS1,431968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF.almPLCFault.BOOLS2,431969,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF.almPLCFault.AEBOOLS,431970,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF.almPLCFault.INT1,431971,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF.almPLCFault.INT2,431972,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF.almPLCFault.AENotify,431973,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF.almPLCFault.AESeverity,431974,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF.almPLCFault.AEShelveDuration,431975,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF3.Alarm.BOOLS1,431992,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF3.Alarm.BOOLS2,431993,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF3.Alarm.AEBOOLS,431994,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF3.Alarm.INT1,431995,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF3.Alarm.INT2,431996,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF3.Alarm.AENotify,431997,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF3.Alarm.AESeverity,431998,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF3.Alarm.AEShelveDuration,431999,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF3.almPLCFault.BOOLS1,432004,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF3.almPLCFault.BOOLS2,432005,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF3.almPLCFault.AEBOOLS,432006,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF3.almPLCFault.INT1,432007,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF3.almPLCFault.INT2,432008,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF3.almPLCFault.AENotify,432009,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF3.almPLCFault.AESeverity,432010,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF3.almPLCFault.AEShelveDuration,432011,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF4.Alarm.BOOLS1,432026,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF4.Alarm.BOOLS2,432027,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF4.Alarm.AEBOOLS,432028,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF4.Alarm.INT1,432029,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF4.Alarm.INT2,432030,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF4.Alarm.AENotify,432031,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF4.Alarm.AESeverity,432032,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF4.Alarm.AEShelveDuration,432033,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8B_ZF4.almPLCFault.BOOLS1,432038,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8B_ZF4.almPLCFault.BOOLS2,432039,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8B_ZF4.almPLCFault.AEBOOLS,432040,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8B_ZF4.almPLCFault.INT1,432041,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF4.almPLCFault.INT2,432042,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8B_ZF4.almPLCFault.AENotify,432043,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8B_ZF4.almPLCFault.AESeverity,432044,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8B_ZF4.almPLCFault.AEShelveDuration,432045,Short,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C_WH.Alarm.BOOLS1,432062,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C_WH.Alarm.BOOLS2,432063,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C_WH.Alarm.AEBOOLS,432064,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C_WH.Alarm.INT1,432065,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C_WH.Alarm.INT2,432066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C_WH.Alarm.AENotify,432067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C_WH.Alarm.AESeverity,432068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C_WH.Alarm.AEShelveDuration,432069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C_WH.almPLCFault.BOOLS1,432074,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C_WH.almPLCFault.BOOLS2,432075,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C_WH.almPLCFault.AEBOOLS,432076,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C_WH.almPLCFault.INT1,432077,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C_WH.almPLCFault.INT2,432078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C_WH.almPLCFault.AENotify,432079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C_WH.almPLCFault.AESeverity,432080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C_WH.almPLCFault.AEShelveDuration,432081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D_WH.Alarm.BOOLS1,432096,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D_WH.Alarm.BOOLS2,432097,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D_WH.Alarm.AEBOOLS,432098,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D_WH.Alarm.INT1,432099,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D_WH.Alarm.INT2,432100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D_WH.Alarm.AENotify,432101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D_WH.Alarm.AESeverity,432102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D_WH.Alarm.AEShelveDuration,432103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D_WH.almPLCFault.BOOLS1,432108,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D_WH.almPLCFault.BOOLS2,432109,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D_WH.almPLCFault.AEBOOLS,432110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D_WH.almPLCFault.INT1,432111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D_WH.almPLCFault.INT2,432112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D_WH.almPLCFault.AENotify,432113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D_WH.almPLCFault.AESeverity,432114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D_WH.almPLCFault.AEShelveDuration,432115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A_WH.Alarm.BOOLS1,432132,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A_WH.Alarm.BOOLS2,432133,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A_WH.Alarm.AEBOOLS,432134,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A_WH.Alarm.INT1,432135,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A_WH.Alarm.INT2,432136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A_WH.Alarm.AENotify,432137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A_WH.Alarm.AESeverity,432138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A_WH.Alarm.AEShelveDuration,432139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A_WH.almPLCFault.BOOLS1,432144,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A_WH.almPLCFault.BOOLS2,432145,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A_WH.almPLCFault.AEBOOLS,432146,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A_WH.almPLCFault.INT1,432147,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A_WH.almPLCFault.INT2,432148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A_WH.almPLCFault.AENotify,432149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A_WH.almPLCFault.AESeverity,432150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A_WH.almPLCFault.AEShelveDuration,432151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZF.Alarm.BOOLS1,432166,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZF.Alarm.BOOLS2,432167,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZF.Alarm.AEBOOLS,432168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZF.Alarm.INT1,432169,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF.Alarm.INT2,432170,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF.Alarm.AENotify,432171,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZF.Alarm.AESeverity,432172,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZF.Alarm.AEShelveDuration,432173,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZF.almPLCFault.BOOLS1,432178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZF.almPLCFault.BOOLS2,432179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZF.almPLCFault.AEBOOLS,432180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZF.almPLCFault.INT1,432181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF.almPLCFault.INT2,432182,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF.almPLCFault.AENotify,432183,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZF.almPLCFault.AESeverity,432184,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZF.almPLCFault.AEShelveDuration,432185,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZF2.Alarm.BOOLS1,432202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZF2.Alarm.BOOLS2,432203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZF2.Alarm.AEBOOLS,432204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZF2.Alarm.INT1,432205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF2.Alarm.INT2,432206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF2.Alarm.AENotify,432207,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZF2.Alarm.AESeverity,432208,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZF2.Alarm.AEShelveDuration,432209,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9B_ZF2.almPLCFault.BOOLS1,432214,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9B_ZF2.almPLCFault.BOOLS2,432215,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9B_ZF2.almPLCFault.AEBOOLS,432216,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9B_ZF2.almPLCFault.INT1,432217,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF2.almPLCFault.INT2,432218,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9B_ZF2.almPLCFault.AENotify,432219,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9B_ZF2.almPLCFault.AESeverity,432220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9B_ZF2.almPLCFault.AEShelveDuration,432221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C_WH.Alarm.BOOLS1,432236,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C_WH.Alarm.BOOLS2,432237,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C_WH.Alarm.AEBOOLS,432238,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C_WH.Alarm.INT1,432239,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C_WH.Alarm.INT2,432240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C_WH.Alarm.AENotify,432241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C_WH.Alarm.AESeverity,432242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C_WH.Alarm.AEShelveDuration,432243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C_WH.almPLCFault.BOOLS1,432248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C_WH.almPLCFault.BOOLS2,432249,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C_WH.almPLCFault.AEBOOLS,432250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C_WH.almPLCFault.INT1,432251,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C_WH.almPLCFault.INT2,432252,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C_WH.almPLCFault.AENotify,432253,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C_WH.almPLCFault.AESeverity,432254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C_WH.almPLCFault.AEShelveDuration,432255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A_WH.Alarm.BOOLS1,432272,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A_WH.Alarm.BOOLS2,432273,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A_WH.Alarm.AEBOOLS,432274,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A_WH.Alarm.INT1,432275,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A_WH.Alarm.INT2,432276,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A_WH.Alarm.AENotify,432277,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A_WH.Alarm.AESeverity,432278,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A_WH.Alarm.AEShelveDuration,432279,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A_WH.almPLCFault.BOOLS1,432284,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A_WH.almPLCFault.BOOLS2,432285,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A_WH.almPLCFault.AEBOOLS,432286,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A_WH.almPLCFault.INT1,432287,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A_WH.almPLCFault.INT2,432288,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A_WH.almPLCFault.AENotify,432289,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A_WH.almPLCFault.AESeverity,432290,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A_WH.almPLCFault.AEShelveDuration,432291,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B_WH.Alarm.BOOLS1,432306,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B_WH.Alarm.BOOLS2,432307,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B_WH.Alarm.AEBOOLS,432308,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B_WH.Alarm.INT1,432309,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B_WH.Alarm.INT2,432310,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B_WH.Alarm.AENotify,432311,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B_WH.Alarm.AESeverity,432312,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B_WH.Alarm.AEShelveDuration,432313,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B_WH.almPLCFault.BOOLS1,432318,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B_WH.almPLCFault.BOOLS2,432319,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B_WH.almPLCFault.AEBOOLS,432320,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B_WH.almPLCFault.INT1,432321,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B_WH.almPLCFault.INT2,432322,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B_WH.almPLCFault.AENotify,432323,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B_WH.almPLCFault.AESeverity,432324,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B_WH.almPLCFault.AEShelveDuration,432325,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C_WH.Alarm.BOOLS1,432342,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C_WH.Alarm.BOOLS2,432343,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C_WH.Alarm.AEBOOLS,432344,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C_WH.Alarm.INT1,432345,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C_WH.Alarm.INT2,432346,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C_WH.Alarm.AENotify,432347,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C_WH.Alarm.AESeverity,432348,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C_WH.Alarm.AEShelveDuration,432349,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C_WH.almPLCFault.BOOLS1,432354,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C_WH.almPLCFault.BOOLS2,432355,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C_WH.almPLCFault.AEBOOLS,432356,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C_WH.almPLCFault.INT1,432357,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C_WH.almPLCFault.INT2,432358,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C_WH.almPLCFault.AENotify,432359,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C_WH.almPLCFault.AESeverity,432360,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C_WH.almPLCFault.AEShelveDuration,432361,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D_WH.Alarm.BOOLS1,432376,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D_WH.Alarm.BOOLS2,432377,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D_WH.Alarm.AEBOOLS,432378,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D_WH.Alarm.INT1,432379,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D_WH.Alarm.INT2,432380,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D_WH.Alarm.AENotify,432381,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D_WH.Alarm.AESeverity,432382,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D_WH.Alarm.AEShelveDuration,432383,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D_WH.almPLCFault.BOOLS1,432388,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D_WH.almPLCFault.BOOLS2,432389,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D_WH.almPLCFault.AEBOOLS,432390,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D_WH.almPLCFault.INT1,432391,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D_WH.almPLCFault.INT2,432392,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D_WH.almPLCFault.AENotify,432393,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D_WH.almPLCFault.AESeverity,432394,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D_WH.almPLCFault.AEShelveDuration,432395,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_LL.Alarm.BOOLS1,432412,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_LL.Alarm.BOOLS2,432413,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_LL.Alarm.AEBOOLS,432414,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_LL.Alarm.INT1,432415,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_LL.Alarm.INT2,432416,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_LL.Alarm.AENotify,432417,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_LL.Alarm.AESeverity,432418,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_LL.Alarm.AEShelveDuration,432419,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_LL.almPLCFault.BOOLS1,432424,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_LL.almPLCFault.BOOLS2,432425,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_LL.almPLCFault.AEBOOLS,432426,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_LL.almPLCFault.INT1,432427,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_LL.almPLCFault.INT2,432428,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_LL.almPLCFault.AENotify,432429,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_LL.almPLCFault.AESeverity,432430,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_LL.almPLCFault.AEShelveDuration,432431,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_PL.Alarm.BOOLS1,432446,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_PL.Alarm.BOOLS2,432447,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_PL.Alarm.AEBOOLS,432448,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_PL.Alarm.INT1,432449,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_PL.Alarm.INT2,432450,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_PL.Alarm.AENotify,432451,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_PL.Alarm.AESeverity,432452,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_PL.Alarm.AEShelveDuration,432453,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_PL.almPLCFault.BOOLS1,432458,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_PL.almPLCFault.BOOLS2,432459,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_PL.almPLCFault.AEBOOLS,432460,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_PL.almPLCFault.INT1,432461,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_PL.almPLCFault.INT2,432462,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_PL.almPLCFault.AENotify,432463,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_PL.almPLCFault.AESeverity,432464,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_PL.almPLCFault.AEShelveDuration,432465,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_SH.Alarm.BOOLS1,432482,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_SH.Alarm.BOOLS2,432483,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_SH.Alarm.AEBOOLS,432484,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_SH.Alarm.INT1,432485,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_SH.Alarm.INT2,432486,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_SH.Alarm.AENotify,432487,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_SH.Alarm.AESeverity,432488,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_SH.Alarm.AEShelveDuration,432489,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_SH.almPLCFault.BOOLS1,432494,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_SH.almPLCFault.BOOLS2,432495,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_SH.almPLCFault.AEBOOLS,432496,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_SH.almPLCFault.INT1,432497,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_SH.almPLCFault.INT2,432498,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_SH.almPLCFault.AENotify,432499,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_SH.almPLCFault.AESeverity,432500,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_SH.almPLCFault.AEShelveDuration,432501,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_TH.Alarm.BOOLS1,432516,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_TH.Alarm.BOOLS2,432517,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_TH.Alarm.AEBOOLS,432518,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_TH.Alarm.INT1,432519,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_TH.Alarm.INT2,432520,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_TH.Alarm.AENotify,432521,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_TH.Alarm.AESeverity,432522,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_TH.Alarm.AEShelveDuration,432523,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_TH.almPLCFault.BOOLS1,432528,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_TH.almPLCFault.BOOLS2,432529,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_TH.almPLCFault.AEBOOLS,432530,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_TH.almPLCFault.INT1,432531,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_TH.almPLCFault.INT2,432532,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_TH.almPLCFault.AENotify,432533,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_TH.almPLCFault.AESeverity,432534,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_TH.almPLCFault.AEShelveDuration,432535,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_XA1.Alarm.BOOLS1,432552,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_XA1.Alarm.BOOLS2,432553,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_XA1.Alarm.AEBOOLS,432554,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_XA1.Alarm.INT1,432555,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA1.Alarm.INT2,432556,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA1.Alarm.AENotify,432557,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_XA1.Alarm.AESeverity,432558,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_XA1.Alarm.AEShelveDuration,432559,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_XA1.almPLCFault.BOOLS1,432564,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_XA1.almPLCFault.BOOLS2,432565,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_XA1.almPLCFault.AEBOOLS,432566,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_XA1.almPLCFault.INT1,432567,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA1.almPLCFault.INT2,432568,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA1.almPLCFault.AENotify,432569,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_XA1.almPLCFault.AESeverity,432570,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_XA1.almPLCFault.AEShelveDuration,432571,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_XA2.Alarm.BOOLS1,432586,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_XA2.Alarm.BOOLS2,432587,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_XA2.Alarm.AEBOOLS,432588,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_XA2.Alarm.INT1,432589,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA2.Alarm.INT2,432590,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA2.Alarm.AENotify,432591,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_XA2.Alarm.AESeverity,432592,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_XA2.Alarm.AEShelveDuration,432593,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_GEN_0131_1_XA2.almPLCFault.BOOLS1,432598,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_GEN_0131_1_XA2.almPLCFault.BOOLS2,432599,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_GEN_0131_1_XA2.almPLCFault.AEBOOLS,432600,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_GEN_0131_1_XA2.almPLCFault.INT1,432601,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA2.almPLCFault.INT2,432602,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_GEN_0131_1_XA2.almPLCFault.AENotify,432603,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_GEN_0131_1_XA2.almPLCFault.AESeverity,432604,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_GEN_0131_1_XA2.almPLCFault.AEShelveDuration,432605,Short,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_FA.Alarm.BOOLS1,432622,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_FA.Alarm.BOOLS2,432623,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_FA.Alarm.AEBOOLS,432624,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_FA.Alarm.INT1,432625,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FA.Alarm.INT2,432626,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FA.Alarm.AENotify,432627,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_FA.Alarm.AESeverity,432628,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_FA.Alarm.AEShelveDuration,432629,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_FA.almPLCFault.BOOLS1,432634,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_FA.almPLCFault.BOOLS2,432635,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_FA.almPLCFault.AEBOOLS,432636,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_FA.almPLCFault.INT1,432637,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FA.almPLCFault.INT2,432638,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FA.almPLCFault.AENotify,432639,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_FA.almPLCFault.AESeverity,432640,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_FA.almPLCFault.AEShelveDuration,432641,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_FH.Alarm.BOOLS1,432656,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_FH.Alarm.BOOLS2,432657,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_FH.Alarm.AEBOOLS,432658,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_FH.Alarm.INT1,432659,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FH.Alarm.INT2,432660,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FH.Alarm.AENotify,432661,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_FH.Alarm.AESeverity,432662,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_FH.Alarm.AEShelveDuration,432663,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_FH.almPLCFault.BOOLS1,432668,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_FH.almPLCFault.BOOLS2,432669,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_FH.almPLCFault.AEBOOLS,432670,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_FH.almPLCFault.INT1,432671,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FH.almPLCFault.INT2,432672,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_FH.almPLCFault.AENotify,432673,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_FH.almPLCFault.AESeverity,432674,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_FH.almPLCFault.AEShelveDuration,432675,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_PH.Alarm.BOOLS1,432692,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_PH.Alarm.BOOLS2,432693,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_PH.Alarm.AEBOOLS,432694,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_PH.Alarm.INT1,432695,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_PH.Alarm.INT2,432696,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_PH.Alarm.AENotify,432697,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_PH.Alarm.AESeverity,432698,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_PH.Alarm.AEShelveDuration,432699,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_PH.almPLCFault.BOOLS1,432704,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_PH.almPLCFault.BOOLS2,432705,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_PH.almPLCFault.AEBOOLS,432706,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_PH.almPLCFault.INT1,432707,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_PH.almPLCFault.INT2,432708,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_PH.almPLCFault.AENotify,432709,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_PH.almPLCFault.AESeverity,432710,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_PH.almPLCFault.AEShelveDuration,432711,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH1.Alarm.BOOLS1,432726,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH1.Alarm.BOOLS2,432727,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH1.Alarm.AEBOOLS,432728,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH1.Alarm.INT1,432729,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH1.Alarm.INT2,432730,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH1.Alarm.AENotify,432731,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH1.Alarm.AESeverity,432732,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH1.Alarm.AEShelveDuration,432733,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH1.almPLCFault.BOOLS1,432738,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH1.almPLCFault.BOOLS2,432739,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH1.almPLCFault.AEBOOLS,432740,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH1.almPLCFault.INT1,432741,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH1.almPLCFault.INT2,432742,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH1.almPLCFault.AENotify,432743,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH1.almPLCFault.AESeverity,432744,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH1.almPLCFault.AEShelveDuration,432745,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH2.Alarm.BOOLS1,432762,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH2.Alarm.BOOLS2,432763,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH2.Alarm.AEBOOLS,432764,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH2.Alarm.INT1,432765,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH2.Alarm.INT2,432766,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH2.Alarm.AENotify,432767,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH2.Alarm.AESeverity,432768,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH2.Alarm.AEShelveDuration,432769,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH2.almPLCFault.BOOLS1,432774,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH2.almPLCFault.BOOLS2,432775,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH2.almPLCFault.AEBOOLS,432776,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH2.almPLCFault.INT1,432777,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH2.almPLCFault.INT2,432778,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH2.almPLCFault.AENotify,432779,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH2.almPLCFault.AESeverity,432780,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH2.almPLCFault.AEShelveDuration,432781,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH3.Alarm.BOOLS1,432796,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH3.Alarm.BOOLS2,432797,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH3.Alarm.AEBOOLS,432798,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH3.Alarm.INT1,432799,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH3.Alarm.INT2,432800,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH3.Alarm.AENotify,432801,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH3.Alarm.AESeverity,432802,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH3.Alarm.AEShelveDuration,432803,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TH3.almPLCFault.BOOLS1,432808,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TH3.almPLCFault.BOOLS2,432809,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TH3.almPLCFault.AEBOOLS,432810,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TH3.almPLCFault.INT1,432811,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH3.almPLCFault.INT2,432812,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TH3.almPLCFault.AENotify,432813,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TH3.almPLCFault.AESeverity,432814,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TH3.almPLCFault.AEShelveDuration,432815,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TL1.Alarm.BOOLS1,432832,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TL1.Alarm.BOOLS2,432833,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TL1.Alarm.AEBOOLS,432834,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TL1.Alarm.INT1,432835,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL1.Alarm.INT2,432836,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL1.Alarm.AENotify,432837,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TL1.Alarm.AESeverity,432838,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TL1.Alarm.AEShelveDuration,432839,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TL1.almPLCFault.BOOLS1,432844,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TL1.almPLCFault.BOOLS2,432845,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TL1.almPLCFault.AEBOOLS,432846,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TL1.almPLCFault.INT1,432847,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL1.almPLCFault.INT2,432848,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL1.almPLCFault.AENotify,432849,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TL1.almPLCFault.AESeverity,432850,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TL1.almPLCFault.AEShelveDuration,432851,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TL2.Alarm.BOOLS1,432866,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TL2.Alarm.BOOLS2,432867,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TL2.Alarm.AEBOOLS,432868,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TL2.Alarm.INT1,432869,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL2.Alarm.INT2,432870,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL2.Alarm.AENotify,432871,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TL2.Alarm.AESeverity,432872,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TL2.Alarm.AEShelveDuration,432873,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_TL2.almPLCFault.BOOLS1,432878,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_TL2.almPLCFault.BOOLS2,432879,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_TL2.almPLCFault.AEBOOLS,432880,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_TL2.almPLCFault.INT1,432881,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL2.almPLCFault.INT2,432882,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_TL2.almPLCFault.AENotify,432883,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_TL2.almPLCFault.AESeverity,432884,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_TL2.almPLCFault.AEShelveDuration,432885,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA1.Alarm.BOOLS1,432902,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA1.Alarm.BOOLS2,432903,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA1.Alarm.AEBOOLS,432904,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA1.Alarm.INT1,432905,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA1.Alarm.INT2,432906,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA1.Alarm.AENotify,432907,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA1.Alarm.AESeverity,432908,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA1.Alarm.AEShelveDuration,432909,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA1.almPLCFault.BOOLS1,432914,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA1.almPLCFault.BOOLS2,432915,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA1.almPLCFault.AEBOOLS,432916,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA1.almPLCFault.INT1,432917,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA1.almPLCFault.INT2,432918,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA1.almPLCFault.AENotify,432919,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA1.almPLCFault.AESeverity,432920,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA1.almPLCFault.AEShelveDuration,432921,Short,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA2.Alarm.BOOLS1,432936,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA2.Alarm.BOOLS2,432937,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA2.Alarm.AEBOOLS,432938,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA2.Alarm.INT1,432939,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA2.Alarm.INT2,432940,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA2.Alarm.AENotify,432941,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA2.Alarm.AESeverity,432942,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA2.Alarm.AEShelveDuration,432943,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA2.almPLCFault.BOOLS1,432948,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA2.almPLCFault.BOOLS2,432949,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA2.almPLCFault.AEBOOLS,432950,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA2.almPLCFault.INT1,432951,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA2.almPLCFault.INT2,432952,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA2.almPLCFault.AENotify,432953,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA2.almPLCFault.AESeverity,432954,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA2.almPLCFault.AEShelveDuration,432955,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA3.Alarm.BOOLS1,432972,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA3.Alarm.BOOLS2,432973,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA3.Alarm.AEBOOLS,432974,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA3.Alarm.INT1,432975,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA3.Alarm.INT2,432976,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA3.Alarm.AENotify,432977,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA3.Alarm.AESeverity,432978,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA3.Alarm.AEShelveDuration,432979,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA3.almPLCFault.BOOLS1,432984,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA3.almPLCFault.BOOLS2,432985,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA3.almPLCFault.AEBOOLS,432986,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA3.almPLCFault.INT1,432987,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA3.almPLCFault.INT2,432988,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA3.almPLCFault.AENotify,432989,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA3.almPLCFault.AESeverity,432990,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA3.almPLCFault.AEShelveDuration,432991,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA4.Alarm.BOOLS1,433006,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA4.Alarm.BOOLS2,433007,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA4.Alarm.AEBOOLS,433008,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA4.Alarm.INT1,433009,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA4.Alarm.INT2,433010,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA4.Alarm.AENotify,433011,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA4.Alarm.AESeverity,433012,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA4.Alarm.AEShelveDuration,433013,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA4.almPLCFault.BOOLS1,433018,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA4.almPLCFault.BOOLS2,433019,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA4.almPLCFault.AEBOOLS,433020,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA4.almPLCFault.INT1,433021,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA4.almPLCFault.INT2,433022,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA4.almPLCFault.AENotify,433023,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA4.almPLCFault.AESeverity,433024,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA4.almPLCFault.AEShelveDuration,433025,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA5.Alarm.BOOLS1,433042,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA5.Alarm.BOOLS2,433043,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA5.Alarm.AEBOOLS,433044,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA5.Alarm.INT1,433045,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA5.Alarm.INT2,433046,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA5.Alarm.AENotify,433047,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA5.Alarm.AESeverity,433048,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA5.Alarm.AEShelveDuration,433049,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA5.almPLCFault.BOOLS1,433054,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA5.almPLCFault.BOOLS2,433055,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA5.almPLCFault.AEBOOLS,433056,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA5.almPLCFault.INT1,433057,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA5.almPLCFault.INT2,433058,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA5.almPLCFault.AENotify,433059,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA5.almPLCFault.AESeverity,433060,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA5.almPLCFault.AEShelveDuration,433061,Short,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA6.Alarm.BOOLS1,433076,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA6.Alarm.BOOLS2,433077,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA6.Alarm.AEBOOLS,433078,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA6.Alarm.INT1,433079,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA6.Alarm.INT2,433080,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA6.Alarm.AENotify,433081,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA6.Alarm.AESeverity,433082,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA6.Alarm.AEShelveDuration,433083,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA6.almPLCFault.BOOLS1,433088,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA6.almPLCFault.BOOLS2,433089,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA6.almPLCFault.AEBOOLS,433090,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA6.almPLCFault.INT1,433091,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA6.almPLCFault.INT2,433092,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA6.almPLCFault.AENotify,433093,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA6.almPLCFault.AESeverity,433094,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA6.almPLCFault.AEShelveDuration,433095,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA7.Alarm.BOOLS1,433112,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA7.Alarm.BOOLS2,433113,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA7.Alarm.AEBOOLS,433114,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA7.Alarm.INT1,433115,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA7.Alarm.INT2,433116,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA7.Alarm.AENotify,433117,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA7.Alarm.AESeverity,433118,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA7.Alarm.AEShelveDuration,433119,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA7.almPLCFault.BOOLS1,433124,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA7.almPLCFault.BOOLS2,433125,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA7.almPLCFault.AEBOOLS,433126,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA7.almPLCFault.INT1,433127,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA7.almPLCFault.INT2,433128,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA7.almPLCFault.AENotify,433129,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA7.almPLCFault.AESeverity,433130,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA7.almPLCFault.AEShelveDuration,433131,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA8.Alarm.BOOLS1,433146,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA8.Alarm.BOOLS2,433147,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA8.Alarm.AEBOOLS,433148,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA8.Alarm.INT1,433149,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA8.Alarm.INT2,433150,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA8.Alarm.AENotify,433151,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA8.Alarm.AESeverity,433152,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA8.Alarm.AEShelveDuration,433153,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA8.almPLCFault.BOOLS1,433158,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA8.almPLCFault.BOOLS2,433159,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA8.almPLCFault.AEBOOLS,433160,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA8.almPLCFault.INT1,433161,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA8.almPLCFault.INT2,433162,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA8.almPLCFault.AENotify,433163,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA8.almPLCFault.AESeverity,433164,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA8.almPLCFault.AEShelveDuration,433165,Short,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA9.Alarm.BOOLS1,433182,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA9.Alarm.BOOLS2,433183,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA9.Alarm.AEBOOLS,433184,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA9.Alarm.INT1,433185,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA9.Alarm.INT2,433186,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA9.Alarm.AENotify,433187,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA9.Alarm.AESeverity,433188,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA9.Alarm.AEShelveDuration,433189,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA9.almPLCFault.BOOLS1,433194,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA9.almPLCFault.BOOLS2,433195,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA9.almPLCFault.AEBOOLS,433196,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA9.almPLCFault.INT1,433197,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA9.almPLCFault.INT2,433198,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA9.almPLCFault.AENotify,433199,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA9.almPLCFault.AESeverity,433200,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA9.almPLCFault.AEShelveDuration,433201,Short,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA10.Alarm.BOOLS1,433216,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA10.Alarm.BOOLS2,433217,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA10.Alarm.AEBOOLS,433218,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA10.Alarm.INT1,433219,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA10.Alarm.INT2,433220,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA10.Alarm.AENotify,433221,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA10.Alarm.AESeverity,433222,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA10.Alarm.AEShelveDuration,433223,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA10.almPLCFault.BOOLS1,433228,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA10.almPLCFault.BOOLS2,433229,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA10.almPLCFault.AEBOOLS,433230,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA10.almPLCFault.INT1,433231,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA10.almPLCFault.INT2,433232,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA10.almPLCFault.AENotify,433233,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA10.almPLCFault.AESeverity,433234,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA10.almPLCFault.AEShelveDuration,433235,Short,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA11.Alarm.BOOLS1,433252,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA11.Alarm.BOOLS2,433253,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA11.Alarm.AEBOOLS,433254,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA11.Alarm.INT1,433255,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA11.Alarm.INT2,433256,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA11.Alarm.AENotify,433257,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA11.Alarm.AESeverity,433258,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA11.Alarm.AEShelveDuration,433259,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA11.almPLCFault.BOOLS1,433264,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA11.almPLCFault.BOOLS2,433265,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA11.almPLCFault.AEBOOLS,433266,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA11.almPLCFault.INT1,433267,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA11.almPLCFault.INT2,433268,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA11.almPLCFault.AENotify,433269,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA11.almPLCFault.AESeverity,433270,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA11.almPLCFault.AEShelveDuration,433271,Short,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA12.Alarm.BOOLS1,433286,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA12.Alarm.BOOLS2,433287,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA12.Alarm.AEBOOLS,433288,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA12.Alarm.INT1,433289,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA12.Alarm.INT2,433290,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA12.Alarm.AENotify,433291,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA12.Alarm.AESeverity,433292,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA12.Alarm.AEShelveDuration,433293,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_HCP_001_1_XA12.almPLCFault.BOOLS1,433298,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_HCP_001_1_XA12.almPLCFault.BOOLS2,433299,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_HCP_001_1_XA12.almPLCFault.AEBOOLS,433300,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_HCP_001_1_XA12.almPLCFault.INT1,433301,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA12.almPLCFault.INT2,433302,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_HCP_001_1_XA12.almPLCFault.AENotify,433303,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_HCP_001_1_XA12.almPLCFault.AESeverity,433304,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_HCP_001_1_XA12.almPLCFault.AEShelveDuration,433305,Short,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_LSH_0113_1_LH.Alarm.BOOLS1,433322,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_LSH_0113_1_LH.Alarm.BOOLS2,433323,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_LSH_0113_1_LH.Alarm.AEBOOLS,433324,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_LSH_0113_1_LH.Alarm.INT1,433325,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_1_LH.Alarm.INT2,433326,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_1_LH.Alarm.AENotify,433327,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_LSH_0113_1_LH.Alarm.AESeverity,433328,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_LSH_0113_1_LH.Alarm.AEShelveDuration,433329,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_LSH_0113_1_LH.almPLCFault.BOOLS1,433334,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_LSH_0113_1_LH.almPLCFault.BOOLS2,433335,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_LSH_0113_1_LH.almPLCFault.AEBOOLS,433336,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_LSH_0113_1_LH.almPLCFault.INT1,433337,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_1_LH.almPLCFault.INT2,433338,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_1_LH.almPLCFault.AENotify,433339,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_LSH_0113_1_LH.almPLCFault.AESeverity,433340,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_LSH_0113_1_LH.almPLCFault.AEShelveDuration,433341,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_LSH_0113_2_LH.Alarm.BOOLS1,433356,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_LSH_0113_2_LH.Alarm.BOOLS2,433357,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_LSH_0113_2_LH.Alarm.AEBOOLS,433358,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_LSH_0113_2_LH.Alarm.INT1,433359,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_2_LH.Alarm.INT2,433360,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_2_LH.Alarm.AENotify,433361,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_LSH_0113_2_LH.Alarm.AESeverity,433362,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_LSH_0113_2_LH.Alarm.AEShelveDuration,433363,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_LSH_0113_2_LH.almPLCFault.BOOLS1,433368,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_LSH_0113_2_LH.almPLCFault.BOOLS2,433369,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_LSH_0113_2_LH.almPLCFault.AEBOOLS,433370,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_LSH_0113_2_LH.almPLCFault.INT1,433371,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_2_LH.almPLCFault.INT2,433372,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_LSH_0113_2_LH.almPLCFault.AENotify,433373,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_LSH_0113_2_LH.almPLCFault.AESeverity,433374,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_LSH_0113_2_LH.almPLCFault.AEShelveDuration,433375,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_NET_001_1_JA.Alarm.BOOLS1,433392,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_NET_001_1_JA.Alarm.BOOLS2,433393,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_NET_001_1_JA.Alarm.AEBOOLS,433394,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_NET_001_1_JA.Alarm.INT1,433395,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_JA.Alarm.INT2,433396,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_JA.Alarm.AENotify,433397,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_NET_001_1_JA.Alarm.AESeverity,433398,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_NET_001_1_JA.Alarm.AEShelveDuration,433399,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_NET_001_1_JA.almPLCFault.BOOLS1,433404,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_NET_001_1_JA.almPLCFault.BOOLS2,433405,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_NET_001_1_JA.almPLCFault.AEBOOLS,433406,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_NET_001_1_JA.almPLCFault.INT1,433407,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_JA.almPLCFault.INT2,433408,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_JA.almPLCFault.AENotify,433409,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_NET_001_1_JA.almPLCFault.AESeverity,433410,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_NET_001_1_JA.almPLCFault.AEShelveDuration,433411,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_NET_001_1_ZS.Alarm.BOOLS1,433426,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_NET_001_1_ZS.Alarm.BOOLS2,433427,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_NET_001_1_ZS.Alarm.AEBOOLS,433428,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_NET_001_1_ZS.Alarm.INT1,433429,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_ZS.Alarm.INT2,433430,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_ZS.Alarm.AENotify,433431,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_NET_001_1_ZS.Alarm.AESeverity,433432,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_NET_001_1_ZS.Alarm.AEShelveDuration,433433,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_NET_001_1_ZS.almPLCFault.BOOLS1,433438,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_NET_001_1_ZS.almPLCFault.BOOLS2,433439,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_NET_001_1_ZS.almPLCFault.AEBOOLS,433440,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_NET_001_1_ZS.almPLCFault.INT1,433441,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_ZS.almPLCFault.INT2,433442,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_NET_001_1_ZS.almPLCFault.AENotify,433443,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_NET_001_1_ZS.almPLCFault.AESeverity,433444,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_NET_001_1_ZS.almPLCFault.AEShelveDuration,433445,Short,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PFC_0112_INHIBIT.Alarm.BOOLS1,433462,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PFC_0112_INHIBIT.Alarm.BOOLS2,433463,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PFC_0112_INHIBIT.Alarm.AEBOOLS,433464,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PFC_0112_INHIBIT.Alarm.INT1,433465,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PFC_0112_INHIBIT.Alarm.INT2,433466,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PFC_0112_INHIBIT.Alarm.AENotify,433467,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PFC_0112_INHIBIT.Alarm.AESeverity,433468,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PFC_0112_INHIBIT.Alarm.AEShelveDuration,433469,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PFC_0112_INHIBIT.almPLCFault.BOOLS1,433474,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PFC_0112_INHIBIT.almPLCFault.BOOLS2,433475,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PFC_0112_INHIBIT.almPLCFault.AEBOOLS,433476,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PFC_0112_INHIBIT.almPLCFault.INT1,433477,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PFC_0112_INHIBIT.almPLCFault.INT2,433478,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PFC_0112_INHIBIT.almPLCFault.AENotify,433479,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PFC_0112_INHIBIT.almPLCFault.AESeverity,433480,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PFC_0112_INHIBIT.almPLCFault.AEShelveDuration,433481,Short,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PL.Alarm.BOOLS1,433496,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PL.Alarm.BOOLS2,433497,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PL.Alarm.AEBOOLS,433498,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PL.Alarm.INT1,433499,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PL.Alarm.INT2,433500,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PL.Alarm.AENotify,433501,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PL.Alarm.AESeverity,433502,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PL.Alarm.AEShelveDuration,433503,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_1_PL.almPLCFault.BOOLS1,433508,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_1_PL.almPLCFault.BOOLS2,433509,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_1_PL.almPLCFault.AEBOOLS,433510,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_1_PL.almPLCFault.INT1,433511,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PL.almPLCFault.INT2,433512,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_1_PL.almPLCFault.AENotify,433513,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_1_PL.almPLCFault.AESeverity,433514,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_1_PL.almPLCFault.AEShelveDuration,433515,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PL.Alarm.BOOLS1,433532,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PL.Alarm.BOOLS2,433533,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PL.Alarm.AEBOOLS,433534,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PL.Alarm.INT1,433535,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PL.Alarm.INT2,433536,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PL.Alarm.AENotify,433537,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PL.Alarm.AESeverity,433538,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PL.Alarm.AEShelveDuration,433539,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PIT_0102_2_PL.almPLCFault.BOOLS1,433544,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PIT_0102_2_PL.almPLCFault.BOOLS2,433545,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PIT_0102_2_PL.almPLCFault.AEBOOLS,433546,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PIT_0102_2_PL.almPLCFault.INT1,433547,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PL.almPLCFault.INT2,433548,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PIT_0102_2_PL.almPLCFault.AENotify,433549,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PIT_0102_2_PL.almPLCFault.AESeverity,433550,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PIT_0102_2_PL.almPLCFault.AEShelveDuration,433551,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PLC_001_1_JA.Alarm.BOOLS1,433566,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PLC_001_1_JA.Alarm.BOOLS2,433567,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PLC_001_1_JA.Alarm.AEBOOLS,433568,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PLC_001_1_JA.Alarm.INT1,433569,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_JA.Alarm.INT2,433570,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_JA.Alarm.AENotify,433571,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PLC_001_1_JA.Alarm.AESeverity,433572,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PLC_001_1_JA.Alarm.AEShelveDuration,433573,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PLC_001_1_JA.almPLCFault.BOOLS1,433578,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PLC_001_1_JA.almPLCFault.BOOLS2,433579,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PLC_001_1_JA.almPLCFault.AEBOOLS,433580,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PLC_001_1_JA.almPLCFault.INT1,433581,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_JA.almPLCFault.INT2,433582,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_JA.almPLCFault.AENotify,433583,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PLC_001_1_JA.almPLCFault.AESeverity,433584,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PLC_001_1_JA.almPLCFault.AEShelveDuration,433585,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PLC_001_1_ZS.Alarm.BOOLS1,433602,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PLC_001_1_ZS.Alarm.BOOLS2,433603,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PLC_001_1_ZS.Alarm.AEBOOLS,433604,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PLC_001_1_ZS.Alarm.INT1,433605,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_ZS.Alarm.INT2,433606,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_ZS.Alarm.AENotify,433607,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PLC_001_1_ZS.Alarm.AESeverity,433608,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PLC_001_1_ZS.Alarm.AEShelveDuration,433609,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PLC_001_1_ZS.almPLCFault.BOOLS1,433614,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PLC_001_1_ZS.almPLCFault.BOOLS2,433615,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PLC_001_1_ZS.almPLCFault.AEBOOLS,433616,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PLC_001_1_ZS.almPLCFault.INT1,433617,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_ZS.almPLCFault.INT2,433618,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PLC_001_1_ZS.almPLCFault.AENotify,433619,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PLC_001_1_ZS.almPLCFault.AESeverity,433620,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PLC_001_1_ZS.almPLCFault.AEShelveDuration,433621,Short,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_1_PL.Alarm.BOOLS1,433636,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_1_PL.Alarm.BOOLS2,433637,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_1_PL.Alarm.AEBOOLS,433638,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_1_PL.Alarm.INT1,433639,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_1_PL.Alarm.INT2,433640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_1_PL.Alarm.AENotify,433641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_1_PL.Alarm.AESeverity,433642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_1_PL.Alarm.AEShelveDuration,433643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_1_PL.almPLCFault.BOOLS1,433648,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_1_PL.almPLCFault.BOOLS2,433649,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_1_PL.almPLCFault.AEBOOLS,433650,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_1_PL.almPLCFault.INT1,433651,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_1_PL.almPLCFault.INT2,433652,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_1_PL.almPLCFault.AENotify,433653,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_1_PL.almPLCFault.AESeverity,433654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_1_PL.almPLCFault.AEShelveDuration,433655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_2_PL.Alarm.BOOLS1,433672,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_2_PL.Alarm.BOOLS2,433673,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_2_PL.Alarm.AEBOOLS,433674,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_2_PL.Alarm.INT1,433675,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_2_PL.Alarm.INT2,433676,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_2_PL.Alarm.AENotify,433677,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_2_PL.Alarm.AESeverity,433678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_2_PL.Alarm.AEShelveDuration,433679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_2_PL.almPLCFault.BOOLS1,433684,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_2_PL.almPLCFault.BOOLS2,433685,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_2_PL.almPLCFault.AEBOOLS,433686,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_2_PL.almPLCFault.INT1,433687,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_2_PL.almPLCFault.INT2,433688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_2_PL.almPLCFault.AENotify,433689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_2_PL.almPLCFault.AESeverity,433690,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_2_PL.almPLCFault.AEShelveDuration,433691,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_3_PL.Alarm.BOOLS1,433706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_3_PL.Alarm.BOOLS2,433707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_3_PL.Alarm.AEBOOLS,433708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_3_PL.Alarm.INT1,433709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_3_PL.Alarm.INT2,433710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_3_PL.Alarm.AENotify,433711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_3_PL.Alarm.AESeverity,433712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_3_PL.Alarm.AEShelveDuration,433713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_3_PL.almPLCFault.BOOLS1,433718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_3_PL.almPLCFault.BOOLS2,433719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_3_PL.almPLCFault.AEBOOLS,433720,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_3_PL.almPLCFault.INT1,433721,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_3_PL.almPLCFault.INT2,433722,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_3_PL.almPLCFault.AENotify,433723,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_3_PL.almPLCFault.AESeverity,433724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_3_PL.almPLCFault.AEShelveDuration,433725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_4_PL.Alarm.BOOLS1,433742,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_4_PL.Alarm.BOOLS2,433743,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_4_PL.Alarm.AEBOOLS,433744,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_4_PL.Alarm.INT1,433745,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_4_PL.Alarm.INT2,433746,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_4_PL.Alarm.AENotify,433747,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_4_PL.Alarm.AESeverity,433748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_4_PL.Alarm.AEShelveDuration,433749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_4_PL.almPLCFault.BOOLS1,433754,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_4_PL.almPLCFault.BOOLS2,433755,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_4_PL.almPLCFault.AEBOOLS,433756,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_4_PL.almPLCFault.INT1,433757,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_4_PL.almPLCFault.INT2,433758,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_4_PL.almPLCFault.AENotify,433759,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_4_PL.almPLCFault.AESeverity,433760,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_4_PL.almPLCFault.AEShelveDuration,433761,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_5_PL.Alarm.BOOLS1,433776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_5_PL.Alarm.BOOLS2,433777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_5_PL.Alarm.AEBOOLS,433778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_5_PL.Alarm.INT1,433779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_5_PL.Alarm.INT2,433780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_5_PL.Alarm.AENotify,433781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_5_PL.Alarm.AESeverity,433782,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_5_PL.Alarm.AEShelveDuration,433783,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_5_PL.almPLCFault.BOOLS1,433788,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_5_PL.almPLCFault.BOOLS2,433789,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_5_PL.almPLCFault.AEBOOLS,433790,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_5_PL.almPLCFault.INT1,433791,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_5_PL.almPLCFault.INT2,433792,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_5_PL.almPLCFault.AENotify,433793,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_5_PL.almPLCFault.AESeverity,433794,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_5_PL.almPLCFault.AEShelveDuration,433795,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_6_PL.Alarm.BOOLS1,433812,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_6_PL.Alarm.BOOLS2,433813,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_6_PL.Alarm.AEBOOLS,433814,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_6_PL.Alarm.INT1,433815,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_6_PL.Alarm.INT2,433816,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_6_PL.Alarm.AENotify,433817,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_6_PL.Alarm.AESeverity,433818,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_6_PL.Alarm.AEShelveDuration,433819,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_6_PL.almPLCFault.BOOLS1,433824,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_6_PL.almPLCFault.BOOLS2,433825,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_6_PL.almPLCFault.AEBOOLS,433826,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_6_PL.almPLCFault.INT1,433827,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_6_PL.almPLCFault.INT2,433828,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_6_PL.almPLCFault.AENotify,433829,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_6_PL.almPLCFault.AESeverity,433830,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_6_PL.almPLCFault.AEShelveDuration,433831,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_7_PL.Alarm.BOOLS1,433846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_7_PL.Alarm.BOOLS2,433847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_7_PL.Alarm.AEBOOLS,433848,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_7_PL.Alarm.INT1,433849,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_7_PL.Alarm.INT2,433850,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_7_PL.Alarm.AENotify,433851,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_7_PL.Alarm.AESeverity,433852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_7_PL.Alarm.AEShelveDuration,433853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_7_PL.almPLCFault.BOOLS1,433858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_7_PL.almPLCFault.BOOLS2,433859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_7_PL.almPLCFault.AEBOOLS,433860,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_7_PL.almPLCFault.INT1,433861,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_7_PL.almPLCFault.INT2,433862,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_7_PL.almPLCFault.AENotify,433863,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_7_PL.almPLCFault.AESeverity,433864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_7_PL.almPLCFault.AEShelveDuration,433865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_8_PL.Alarm.BOOLS1,433882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_8_PL.Alarm.BOOLS2,433883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_8_PL.Alarm.AEBOOLS,433884,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_8_PL.Alarm.INT1,433885,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_8_PL.Alarm.INT2,433886,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_8_PL.Alarm.AENotify,433887,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_8_PL.Alarm.AESeverity,433888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_8_PL.Alarm.AEShelveDuration,433889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_8_PL.almPLCFault.BOOLS1,433894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_8_PL.almPLCFault.BOOLS2,433895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_8_PL.almPLCFault.AEBOOLS,433896,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_8_PL.almPLCFault.INT1,433897,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_8_PL.almPLCFault.INT2,433898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_8_PL.almPLCFault.AENotify,433899,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_8_PL.almPLCFault.AESeverity,433900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_8_PL.almPLCFault.AEShelveDuration,433901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_9_PL.Alarm.BOOLS1,433916,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_9_PL.Alarm.BOOLS2,433917,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_9_PL.Alarm.AEBOOLS,433918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_9_PL.Alarm.INT1,433919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_9_PL.Alarm.INT2,433920,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_9_PL.Alarm.AENotify,433921,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_9_PL.Alarm.AESeverity,433922,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_9_PL.Alarm.AEShelveDuration,433923,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_PS_0103_9_PL.almPLCFault.BOOLS1,433928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_PS_0103_9_PL.almPLCFault.BOOLS2,433929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_PS_0103_9_PL.almPLCFault.AEBOOLS,433930,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_PS_0103_9_PL.almPLCFault.INT1,433931,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_9_PL.almPLCFault.INT2,433932,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_PS_0103_9_PL.almPLCFault.AENotify,433933,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_PS_0103_9_PL.almPLCFault.AESeverity,433934,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_PS_0103_9_PL.almPLCFault.AEShelveDuration,433935,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_1_XA.Alarm.BOOLS1,433952,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_1_XA.Alarm.BOOLS2,433953,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_1_XA.Alarm.AEBOOLS,433954,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_1_XA.Alarm.INT1,433955,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_1_XA.Alarm.INT2,433956,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_1_XA.Alarm.AENotify,433957,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_1_XA.Alarm.AESeverity,433958,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_1_XA.Alarm.AEShelveDuration,433959,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_1_XA.almPLCFault.BOOLS1,433964,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_1_XA.almPLCFault.BOOLS2,433965,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_1_XA.almPLCFault.AEBOOLS,433966,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_1_XA.almPLCFault.INT1,433967,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_1_XA.almPLCFault.INT2,433968,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_1_XA.almPLCFault.AENotify,433969,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_1_XA.almPLCFault.AESeverity,433970,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_1_XA.almPLCFault.AEShelveDuration,433971,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_2_XA.Alarm.BOOLS1,433986,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_2_XA.Alarm.BOOLS2,433987,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_2_XA.Alarm.AEBOOLS,433988,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_2_XA.Alarm.INT1,433989,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_2_XA.Alarm.INT2,433990,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_2_XA.Alarm.AENotify,433991,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_2_XA.Alarm.AESeverity,433992,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_2_XA.Alarm.AEShelveDuration,433993,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_2_XA.almPLCFault.BOOLS1,433998,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_2_XA.almPLCFault.BOOLS2,433999,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_2_XA.almPLCFault.AEBOOLS,434000,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_2_XA.almPLCFault.INT1,434001,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_2_XA.almPLCFault.INT2,434002,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_2_XA.almPLCFault.AENotify,434003,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_2_XA.almPLCFault.AESeverity,434004,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_2_XA.almPLCFault.AEShelveDuration,434005,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_3_XA.Alarm.BOOLS1,434022,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_3_XA.Alarm.BOOLS2,434023,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_3_XA.Alarm.AEBOOLS,434024,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_3_XA.Alarm.INT1,434025,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_3_XA.Alarm.INT2,434026,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_3_XA.Alarm.AENotify,434027,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_3_XA.Alarm.AESeverity,434028,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_3_XA.Alarm.AEShelveDuration,434029,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_3_XA.almPLCFault.BOOLS1,434034,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_3_XA.almPLCFault.BOOLS2,434035,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_3_XA.almPLCFault.AEBOOLS,434036,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_3_XA.almPLCFault.INT1,434037,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_3_XA.almPLCFault.INT2,434038,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_3_XA.almPLCFault.AENotify,434039,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_3_XA.almPLCFault.AESeverity,434040,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_3_XA.almPLCFault.AEShelveDuration,434041,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_4_XA.Alarm.BOOLS1,434056,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_4_XA.Alarm.BOOLS2,434057,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_4_XA.Alarm.AEBOOLS,434058,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_4_XA.Alarm.INT1,434059,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_4_XA.Alarm.INT2,434060,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_4_XA.Alarm.AENotify,434061,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_4_XA.Alarm.AESeverity,434062,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_4_XA.Alarm.AEShelveDuration,434063,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_REC_0131_4_XA.almPLCFault.BOOLS1,434068,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_REC_0131_4_XA.almPLCFault.BOOLS2,434069,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_REC_0131_4_XA.almPLCFault.AEBOOLS,434070,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_REC_0131_4_XA.almPLCFault.INT1,434071,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_4_XA.almPLCFault.INT2,434072,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_REC_0131_4_XA.almPLCFault.AENotify,434073,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_REC_0131_4_XA.almPLCFault.AESeverity,434074,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_REC_0131_4_XA.almPLCFault.AEShelveDuration,434075,Short,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0112_1_XA.Alarm.BOOLS1,434092,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0112_1_XA.Alarm.BOOLS2,434093,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0112_1_XA.Alarm.AEBOOLS,434094,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0112_1_XA.Alarm.INT1,434095,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0112_1_XA.Alarm.INT2,434096,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0112_1_XA.Alarm.AENotify,434097,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0112_1_XA.Alarm.AESeverity,434098,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0112_1_XA.Alarm.AEShelveDuration,434099,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0112_1_XA.almPLCFault.BOOLS1,434104,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0112_1_XA.almPLCFault.BOOLS2,434105,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0112_1_XA.almPLCFault.AEBOOLS,434106,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0112_1_XA.almPLCFault.INT1,434107,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0112_1_XA.almPLCFault.INT2,434108,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0112_1_XA.almPLCFault.AENotify,434109,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0112_1_XA.almPLCFault.AESeverity,434110,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0112_1_XA.almPLCFault.AEShelveDuration,434111,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0113_1_XA.Alarm.BOOLS1,434126,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0113_1_XA.Alarm.BOOLS2,434127,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0113_1_XA.Alarm.AEBOOLS,434128,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0113_1_XA.Alarm.INT1,434129,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_1_XA.Alarm.INT2,434130,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_1_XA.Alarm.AENotify,434131,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0113_1_XA.Alarm.AESeverity,434132,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0113_1_XA.Alarm.AEShelveDuration,434133,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0113_1_XA.almPLCFault.BOOLS1,434138,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0113_1_XA.almPLCFault.BOOLS2,434139,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0113_1_XA.almPLCFault.AEBOOLS,434140,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0113_1_XA.almPLCFault.INT1,434141,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_1_XA.almPLCFault.INT2,434142,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_1_XA.almPLCFault.AENotify,434143,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0113_1_XA.almPLCFault.AESeverity,434144,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0113_1_XA.almPLCFault.AEShelveDuration,434145,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0113_2_XA.Alarm.BOOLS1,434162,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0113_2_XA.Alarm.BOOLS2,434163,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0113_2_XA.Alarm.AEBOOLS,434164,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0113_2_XA.Alarm.INT1,434165,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_2_XA.Alarm.INT2,434166,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_2_XA.Alarm.AENotify,434167,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0113_2_XA.Alarm.AESeverity,434168,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0113_2_XA.Alarm.AEShelveDuration,434169,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0113_2_XA.almPLCFault.BOOLS1,434174,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0113_2_XA.almPLCFault.BOOLS2,434175,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0113_2_XA.almPLCFault.AEBOOLS,434176,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0113_2_XA.almPLCFault.INT1,434177,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_2_XA.almPLCFault.INT2,434178,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0113_2_XA.almPLCFault.AENotify,434179,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0113_2_XA.almPLCFault.AESeverity,434180,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0113_2_XA.almPLCFault.AEShelveDuration,434181,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0114_1_XA.Alarm.BOOLS1,434196,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0114_1_XA.Alarm.BOOLS2,434197,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0114_1_XA.Alarm.AEBOOLS,434198,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0114_1_XA.Alarm.INT1,434199,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_1_XA.Alarm.INT2,434200,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_1_XA.Alarm.AENotify,434201,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0114_1_XA.Alarm.AESeverity,434202,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0114_1_XA.Alarm.AEShelveDuration,434203,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0114_1_XA.almPLCFault.BOOLS1,434208,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0114_1_XA.almPLCFault.BOOLS2,434209,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0114_1_XA.almPLCFault.AEBOOLS,434210,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0114_1_XA.almPLCFault.INT1,434211,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_1_XA.almPLCFault.INT2,434212,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_1_XA.almPLCFault.AENotify,434213,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0114_1_XA.almPLCFault.AESeverity,434214,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0114_1_XA.almPLCFault.AEShelveDuration,434215,Short,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0114_2_XA.Alarm.BOOLS1,434232,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0114_2_XA.Alarm.BOOLS2,434233,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0114_2_XA.Alarm.AEBOOLS,434234,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0114_2_XA.Alarm.INT1,434235,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_2_XA.Alarm.INT2,434236,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_2_XA.Alarm.AENotify,434237,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0114_2_XA.Alarm.AESeverity,434238,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0114_2_XA.Alarm.AEShelveDuration,434239,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SD_0114_2_XA.almPLCFault.BOOLS1,434244,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SD_0114_2_XA.almPLCFault.BOOLS2,434245,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SD_0114_2_XA.almPLCFault.AEBOOLS,434246,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SD_0114_2_XA.almPLCFault.INT1,434247,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_2_XA.almPLCFault.INT2,434248,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SD_0114_2_XA.almPLCFault.AENotify,434249,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SD_0114_2_XA.almPLCFault.AESeverity,434250,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SD_0114_2_XA.almPLCFault.AEShelveDuration,434251,Short,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_1_XA.Alarm.BOOLS1,434266,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_1_XA.Alarm.BOOLS2,434267,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_1_XA.Alarm.AEBOOLS,434268,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_1_XA.Alarm.INT1,434269,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_1_XA.Alarm.INT2,434270,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_1_XA.Alarm.AENotify,434271,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_1_XA.Alarm.AESeverity,434272,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_1_XA.Alarm.AEShelveDuration,434273,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_1_XA.almPLCFault.BOOLS1,434278,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_1_XA.almPLCFault.BOOLS2,434279,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_1_XA.almPLCFault.AEBOOLS,434280,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_1_XA.almPLCFault.INT1,434281,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_1_XA.almPLCFault.INT2,434282,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_1_XA.almPLCFault.AENotify,434283,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_1_XA.almPLCFault.AESeverity,434284,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_1_XA.almPLCFault.AEShelveDuration,434285,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_2_XA.Alarm.BOOLS1,434302,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_2_XA.Alarm.BOOLS2,434303,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_2_XA.Alarm.AEBOOLS,434304,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_2_XA.Alarm.INT1,434305,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_2_XA.Alarm.INT2,434306,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_2_XA.Alarm.AENotify,434307,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_2_XA.Alarm.AESeverity,434308,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_2_XA.Alarm.AEShelveDuration,434309,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_2_XA.almPLCFault.BOOLS1,434314,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_2_XA.almPLCFault.BOOLS2,434315,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_2_XA.almPLCFault.AEBOOLS,434316,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_2_XA.almPLCFault.INT1,434317,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_2_XA.almPLCFault.INT2,434318,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_2_XA.almPLCFault.AENotify,434319,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_2_XA.almPLCFault.AESeverity,434320,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_2_XA.almPLCFault.AEShelveDuration,434321,Short,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3_XA1.Alarm.BOOLS1,434336,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3_XA1.Alarm.BOOLS2,434337,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3_XA1.Alarm.AEBOOLS,434338,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3_XA1.Alarm.INT1,434339,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3_XA1.Alarm.INT2,434340,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3_XA1.Alarm.AENotify,434341,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3_XA1.Alarm.AESeverity,434342,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3_XA1.Alarm.AEShelveDuration,434343,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3_XA1.almPLCFault.BOOLS1,434348,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3_XA1.almPLCFault.BOOLS2,434349,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3_XA1.almPLCFault.AEBOOLS,434350,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3_XA1.almPLCFault.INT1,434351,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3_XA1.almPLCFault.INT2,434352,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3_XA1.almPLCFault.AENotify,434353,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3_XA1.almPLCFault.AESeverity,434354,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3_XA1.almPLCFault.AEShelveDuration,434355,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3A_XA.Alarm.BOOLS1,434372,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3A_XA.Alarm.BOOLS2,434373,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3A_XA.Alarm.AEBOOLS,434374,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3A_XA.Alarm.INT1,434375,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3A_XA.Alarm.INT2,434376,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3A_XA.Alarm.AENotify,434377,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3A_XA.Alarm.AESeverity,434378,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3A_XA.Alarm.AEShelveDuration,434379,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3A_XA.almPLCFault.BOOLS1,434384,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3A_XA.almPLCFault.BOOLS2,434385,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3A_XA.almPLCFault.AEBOOLS,434386,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3A_XA.almPLCFault.INT1,434387,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3A_XA.almPLCFault.INT2,434388,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3A_XA.almPLCFault.AENotify,434389,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3A_XA.almPLCFault.AESeverity,434390,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3A_XA.almPLCFault.AEShelveDuration,434391,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3B_XA.Alarm.BOOLS1,434406,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3B_XA.Alarm.BOOLS2,434407,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3B_XA.Alarm.AEBOOLS,434408,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3B_XA.Alarm.INT1,434409,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3B_XA.Alarm.INT2,434410,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3B_XA.Alarm.AENotify,434411,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3B_XA.Alarm.AESeverity,434412,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3B_XA.Alarm.AEShelveDuration,434413,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_3B_XA.almPLCFault.BOOLS1,434418,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_3B_XA.almPLCFault.BOOLS2,434419,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_3B_XA.almPLCFault.AEBOOLS,434420,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_3B_XA.almPLCFault.INT1,434421,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3B_XA.almPLCFault.INT2,434422,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_3B_XA.almPLCFault.AENotify,434423,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_3B_XA.almPLCFault.AESeverity,434424,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_3B_XA.almPLCFault.AEShelveDuration,434425,Short,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_4_XA.Alarm.BOOLS1,434442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_4_XA.Alarm.BOOLS2,434443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_4_XA.Alarm.AEBOOLS,434444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_4_XA.Alarm.INT1,434445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA.Alarm.INT2,434446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA.Alarm.AENotify,434447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_4_XA.Alarm.AESeverity,434448,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_4_XA.Alarm.AEShelveDuration,434449,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_4_XA.almPLCFault.BOOLS1,434454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_4_XA.almPLCFault.BOOLS2,434455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_4_XA.almPLCFault.AEBOOLS,434456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_4_XA.almPLCFault.INT1,434457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA.almPLCFault.INT2,434458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA.almPLCFault.AENotify,434459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_4_XA.almPLCFault.AESeverity,434460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_4_XA.almPLCFault.AEShelveDuration,434461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_4_XA1.Alarm.BOOLS1,434476,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_4_XA1.Alarm.BOOLS2,434477,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_4_XA1.Alarm.AEBOOLS,434478,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_4_XA1.Alarm.INT1,434479,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA1.Alarm.INT2,434480,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA1.Alarm.AENotify,434481,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_4_XA1.Alarm.AESeverity,434482,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_4_XA1.Alarm.AEShelveDuration,434483,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_4_XA1.almPLCFault.BOOLS1,434488,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_4_XA1.almPLCFault.BOOLS2,434489,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_4_XA1.almPLCFault.AEBOOLS,434490,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_4_XA1.almPLCFault.INT1,434491,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA1.almPLCFault.INT2,434492,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_4_XA1.almPLCFault.AENotify,434493,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_4_XA1.almPLCFault.AESeverity,434494,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_4_XA1.almPLCFault.AEShelveDuration,434495,Short,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_5_XA.Alarm.BOOLS1,434512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_5_XA.Alarm.BOOLS2,434513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_5_XA.Alarm.AEBOOLS,434514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_5_XA.Alarm.INT1,434515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_5_XA.Alarm.INT2,434516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_5_XA.Alarm.AENotify,434517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_5_XA.Alarm.AESeverity,434518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_5_XA.Alarm.AEShelveDuration,434519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_5_XA.almPLCFault.BOOLS1,434524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_5_XA.almPLCFault.BOOLS2,434525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_5_XA.almPLCFault.AEBOOLS,434526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_5_XA.almPLCFault.INT1,434527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_5_XA.almPLCFault.INT2,434528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_5_XA.almPLCFault.AENotify,434529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_5_XA.almPLCFault.AESeverity,434530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_5_XA.almPLCFault.AEShelveDuration,434531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_6_XA.Alarm.BOOLS1,434546,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_6_XA.Alarm.BOOLS2,434547,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_6_XA.Alarm.AEBOOLS,434548,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_6_XA.Alarm.INT1,434549,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_6_XA.Alarm.INT2,434550,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_6_XA.Alarm.AENotify,434551,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_6_XA.Alarm.AESeverity,434552,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_6_XA.Alarm.AEShelveDuration,434553,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0112_6_XA.almPLCFault.BOOLS1,434558,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0112_6_XA.almPLCFault.BOOLS2,434559,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0112_6_XA.almPLCFault.AEBOOLS,434560,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0112_6_XA.almPLCFault.INT1,434561,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_6_XA.almPLCFault.INT2,434562,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0112_6_XA.almPLCFault.AENotify,434563,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0112_6_XA.almPLCFault.AESeverity,434564,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0112_6_XA.almPLCFault.AEShelveDuration,434565,Short,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0113_1_XA.Alarm.BOOLS1,434582,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0113_1_XA.Alarm.BOOLS2,434583,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0113_1_XA.Alarm.AEBOOLS,434584,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0113_1_XA.Alarm.INT1,434585,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_1_XA.Alarm.INT2,434586,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_1_XA.Alarm.AENotify,434587,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0113_1_XA.Alarm.AESeverity,434588,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0113_1_XA.Alarm.AEShelveDuration,434589,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0113_1_XA.almPLCFault.BOOLS1,434594,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0113_1_XA.almPLCFault.BOOLS2,434595,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0113_1_XA.almPLCFault.AEBOOLS,434596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0113_1_XA.almPLCFault.INT1,434597,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_1_XA.almPLCFault.INT2,434598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_1_XA.almPLCFault.AENotify,434599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0113_1_XA.almPLCFault.AESeverity,434600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0113_1_XA.almPLCFault.AEShelveDuration,434601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0113_2_XA.Alarm.BOOLS1,434616,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0113_2_XA.Alarm.BOOLS2,434617,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0113_2_XA.Alarm.AEBOOLS,434618,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0113_2_XA.Alarm.INT1,434619,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_2_XA.Alarm.INT2,434620,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_2_XA.Alarm.AENotify,434621,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0113_2_XA.Alarm.AESeverity,434622,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0113_2_XA.Alarm.AEShelveDuration,434623,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_SPD_0113_2_XA.almPLCFault.BOOLS1,434628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_SPD_0113_2_XA.almPLCFault.BOOLS2,434629,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_SPD_0113_2_XA.almPLCFault.AEBOOLS,434630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_SPD_0113_2_XA.almPLCFault.INT1,434631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_2_XA.almPLCFault.INT2,434632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_SPD_0113_2_XA.almPLCFault.AENotify,434633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_SPD_0113_2_XA.almPLCFault.AESeverity,434634,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_SPD_0113_2_XA.almPLCFault.AEShelveDuration,434635,Short,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0111_1_TH.Alarm.BOOLS1,434652,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0111_1_TH.Alarm.BOOLS2,434653,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0111_1_TH.Alarm.AEBOOLS,434654,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0111_1_TH.Alarm.INT1,434655,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0111_1_TH.Alarm.INT2,434656,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0111_1_TH.Alarm.AENotify,434657,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0111_1_TH.Alarm.AESeverity,434658,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0111_1_TH.Alarm.AEShelveDuration,434659,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0111_1_TH.almPLCFault.BOOLS1,434664,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0111_1_TH.almPLCFault.BOOLS2,434665,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0111_1_TH.almPLCFault.AEBOOLS,434666,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0111_1_TH.almPLCFault.INT1,434667,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0111_1_TH.almPLCFault.INT2,434668,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0111_1_TH.almPLCFault.AENotify,434669,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0111_1_TH.almPLCFault.AESeverity,434670,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0111_1_TH.almPLCFault.AEShelveDuration,434671,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0112_1_TH.Alarm.BOOLS1,434686,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0112_1_TH.Alarm.BOOLS2,434687,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0112_1_TH.Alarm.AEBOOLS,434688,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0112_1_TH.Alarm.INT1,434689,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0112_1_TH.Alarm.INT2,434690,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0112_1_TH.Alarm.AENotify,434691,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0112_1_TH.Alarm.AESeverity,434692,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0112_1_TH.Alarm.AEShelveDuration,434693,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0112_1_TH.almPLCFault.BOOLS1,434698,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0112_1_TH.almPLCFault.BOOLS2,434699,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0112_1_TH.almPLCFault.AEBOOLS,434700,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0112_1_TH.almPLCFault.INT1,434701,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0112_1_TH.almPLCFault.INT2,434702,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0112_1_TH.almPLCFault.AENotify,434703,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0112_1_TH.almPLCFault.AESeverity,434704,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0112_1_TH.almPLCFault.AEShelveDuration,434705,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0113_1_TH.Alarm.BOOLS1,434722,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0113_1_TH.Alarm.BOOLS2,434723,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0113_1_TH.Alarm.AEBOOLS,434724,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0113_1_TH.Alarm.INT1,434725,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_1_TH.Alarm.INT2,434726,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_1_TH.Alarm.AENotify,434727,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0113_1_TH.Alarm.AESeverity,434728,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0113_1_TH.Alarm.AEShelveDuration,434729,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0113_1_TH.almPLCFault.BOOLS1,434734,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0113_1_TH.almPLCFault.BOOLS2,434735,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0113_1_TH.almPLCFault.AEBOOLS,434736,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0113_1_TH.almPLCFault.INT1,434737,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_1_TH.almPLCFault.INT2,434738,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_1_TH.almPLCFault.AENotify,434739,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0113_1_TH.almPLCFault.AESeverity,434740,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0113_1_TH.almPLCFault.AEShelveDuration,434741,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0113_2_TH.Alarm.BOOLS1,434756,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0113_2_TH.Alarm.BOOLS2,434757,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0113_2_TH.Alarm.AEBOOLS,434758,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0113_2_TH.Alarm.INT1,434759,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_2_TH.Alarm.INT2,434760,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_2_TH.Alarm.AENotify,434761,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0113_2_TH.Alarm.AESeverity,434762,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0113_2_TH.Alarm.AEShelveDuration,434763,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0113_2_TH.almPLCFault.BOOLS1,434768,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0113_2_TH.almPLCFault.BOOLS2,434769,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0113_2_TH.almPLCFault.AEBOOLS,434770,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0113_2_TH.almPLCFault.INT1,434771,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_2_TH.almPLCFault.INT2,434772,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0113_2_TH.almPLCFault.AENotify,434773,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0113_2_TH.almPLCFault.AESeverity,434774,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0113_2_TH.almPLCFault.AEShelveDuration,434775,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0114_1_TH.Alarm.BOOLS1,434792,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0114_1_TH.Alarm.BOOLS2,434793,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0114_1_TH.Alarm.AEBOOLS,434794,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0114_1_TH.Alarm.INT1,434795,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_1_TH.Alarm.INT2,434796,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_1_TH.Alarm.AENotify,434797,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0114_1_TH.Alarm.AESeverity,434798,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0114_1_TH.Alarm.AEShelveDuration,434799,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0114_1_TH.almPLCFault.BOOLS1,434804,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0114_1_TH.almPLCFault.BOOLS2,434805,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0114_1_TH.almPLCFault.AEBOOLS,434806,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0114_1_TH.almPLCFault.INT1,434807,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_1_TH.almPLCFault.INT2,434808,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_1_TH.almPLCFault.AENotify,434809,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0114_1_TH.almPLCFault.AESeverity,434810,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0114_1_TH.almPLCFault.AEShelveDuration,434811,Short,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0114_2_TH.Alarm.BOOLS1,434826,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0114_2_TH.Alarm.BOOLS2,434827,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0114_2_TH.Alarm.AEBOOLS,434828,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0114_2_TH.Alarm.INT1,434829,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_2_TH.Alarm.INT2,434830,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_2_TH.Alarm.AENotify,434831,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0114_2_TH.Alarm.AESeverity,434832,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0114_2_TH.Alarm.AEShelveDuration,434833,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TE_0114_2_TH.almPLCFault.BOOLS1,434838,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TE_0114_2_TH.almPLCFault.BOOLS2,434839,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TE_0114_2_TH.almPLCFault.AEBOOLS,434840,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TE_0114_2_TH.almPLCFault.INT1,434841,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_2_TH.almPLCFault.INT2,434842,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TE_0114_2_TH.almPLCFault.AENotify,434843,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TE_0114_2_TH.almPLCFault.AESeverity,434844,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TE_0114_2_TH.almPLCFault.AEShelveDuration,434845,Short,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_LL.Alarm.BOOLS1,434862,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_LL.Alarm.BOOLS2,434863,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_LL.Alarm.AEBOOLS,434864,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_LL.Alarm.INT1,434865,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_LL.Alarm.INT2,434866,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_LL.Alarm.AENotify,434867,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_LL.Alarm.AESeverity,434868,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_LL.Alarm.AEShelveDuration,434869,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_LL.almPLCFault.BOOLS1,434874,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_LL.almPLCFault.BOOLS2,434875,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_LL.almPLCFault.AEBOOLS,434876,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_LL.almPLCFault.INT1,434877,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_LL.almPLCFault.INT2,434878,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_LL.almPLCFault.AENotify,434879,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_LL.almPLCFault.AESeverity,434880,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_LL.almPLCFault.AEShelveDuration,434881,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_TH1.Alarm.BOOLS1,434896,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_TH1.Alarm.BOOLS2,434897,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_TH1.Alarm.AEBOOLS,434898,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_TH1.Alarm.INT1,434899,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH1.Alarm.INT2,434900,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH1.Alarm.AENotify,434901,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_TH1.Alarm.AESeverity,434902,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_TH1.Alarm.AEShelveDuration,434903,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_TH1.almPLCFault.BOOLS1,434908,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_TH1.almPLCFault.BOOLS2,434909,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_TH1.almPLCFault.AEBOOLS,434910,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_TH1.almPLCFault.INT1,434911,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH1.almPLCFault.INT2,434912,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH1.almPLCFault.AENotify,434913,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_TH1.almPLCFault.AESeverity,434914,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_TH1.almPLCFault.AEShelveDuration,434915,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_TH2.Alarm.BOOLS1,434932,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_TH2.Alarm.BOOLS2,434933,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_TH2.Alarm.AEBOOLS,434934,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_TH2.Alarm.INT1,434935,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH2.Alarm.INT2,434936,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH2.Alarm.AENotify,434937,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_TH2.Alarm.AESeverity,434938,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_TH2.Alarm.AEShelveDuration,434939,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_TH2.almPLCFault.BOOLS1,434944,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_TH2.almPLCFault.BOOLS2,434945,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_TH2.almPLCFault.AEBOOLS,434946,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_TH2.almPLCFault.INT1,434947,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH2.almPLCFault.INT2,434948,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_TH2.almPLCFault.AENotify,434949,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_TH2.almPLCFault.AESeverity,434950,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_TH2.almPLCFault.AEShelveDuration,434951,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_XA.Alarm.BOOLS1,434966,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_XA.Alarm.BOOLS2,434967,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_XA.Alarm.AEBOOLS,434968,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_XA.Alarm.INT1,434969,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_XA.Alarm.INT2,434970,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_XA.Alarm.AENotify,434971,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_XA.Alarm.AESeverity,434972,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_XA.Alarm.AEShelveDuration,434973,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_1_XA.almPLCFault.BOOLS1,434978,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_1_XA.almPLCFault.BOOLS2,434979,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_1_XA.almPLCFault.AEBOOLS,434980,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_1_XA.almPLCFault.INT1,434981,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_XA.almPLCFault.INT2,434982,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_1_XA.almPLCFault.AENotify,434983,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_1_XA.almPLCFault.AESeverity,434984,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_1_XA.almPLCFault.AEShelveDuration,434985,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_LL.Alarm.BOOLS1,435002,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_LL.Alarm.BOOLS2,435003,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_LL.Alarm.AEBOOLS,435004,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_LL.Alarm.INT1,435005,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_LL.Alarm.INT2,435006,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_LL.Alarm.AENotify,435007,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_LL.Alarm.AESeverity,435008,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_LL.Alarm.AEShelveDuration,435009,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_LL.almPLCFault.BOOLS1,435014,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_LL.almPLCFault.BOOLS2,435015,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_LL.almPLCFault.AEBOOLS,435016,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_LL.almPLCFault.INT1,435017,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_LL.almPLCFault.INT2,435018,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_LL.almPLCFault.AENotify,435019,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_LL.almPLCFault.AESeverity,435020,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_LL.almPLCFault.AEShelveDuration,435021,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_TH1.Alarm.BOOLS1,435036,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_TH1.Alarm.BOOLS2,435037,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_TH1.Alarm.AEBOOLS,435038,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_TH1.Alarm.INT1,435039,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH1.Alarm.INT2,435040,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH1.Alarm.AENotify,435041,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_TH1.Alarm.AESeverity,435042,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_TH1.Alarm.AEShelveDuration,435043,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_TH1.almPLCFault.BOOLS1,435048,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_TH1.almPLCFault.BOOLS2,435049,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_TH1.almPLCFault.AEBOOLS,435050,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_TH1.almPLCFault.INT1,435051,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH1.almPLCFault.INT2,435052,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH1.almPLCFault.AENotify,435053,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_TH1.almPLCFault.AESeverity,435054,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_TH1.almPLCFault.AEShelveDuration,435055,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_TH2.Alarm.BOOLS1,435072,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_TH2.Alarm.BOOLS2,435073,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_TH2.Alarm.AEBOOLS,435074,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_TH2.Alarm.INT1,435075,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH2.Alarm.INT2,435076,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH2.Alarm.AENotify,435077,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_TH2.Alarm.AESeverity,435078,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_TH2.Alarm.AEShelveDuration,435079,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_TH2.almPLCFault.BOOLS1,435084,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_TH2.almPLCFault.BOOLS2,435085,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_TH2.almPLCFault.AEBOOLS,435086,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_TH2.almPLCFault.INT1,435087,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH2.almPLCFault.INT2,435088,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_TH2.almPLCFault.AENotify,435089,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_TH2.almPLCFault.AESeverity,435090,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_TH2.almPLCFault.AEShelveDuration,435091,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_XA.Alarm.BOOLS1,435106,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_XA.Alarm.BOOLS2,435107,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_XA.Alarm.AEBOOLS,435108,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_XA.Alarm.INT1,435109,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_XA.Alarm.INT2,435110,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_XA.Alarm.AENotify,435111,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_XA.Alarm.AESeverity,435112,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_XA.Alarm.AEShelveDuration,435113,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_TFR_0131_2_XA.almPLCFault.BOOLS1,435118,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_TFR_0131_2_XA.almPLCFault.BOOLS2,435119,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_TFR_0131_2_XA.almPLCFault.AEBOOLS,435120,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_TFR_0131_2_XA.almPLCFault.INT1,435121,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_XA.almPLCFault.INT2,435122,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_TFR_0131_2_XA.almPLCFault.AENotify,435123,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_TFR_0131_2_XA.almPLCFault.AESeverity,435124,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_TFR_0131_2_XA.almPLCFault.AEShelveDuration,435125,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_1_JA.Alarm.BOOLS1,435142,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_1_JA.Alarm.BOOLS2,435143,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_1_JA.Alarm.AEBOOLS,435144,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_1_JA.Alarm.INT1,435145,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_JA.Alarm.INT2,435146,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_JA.Alarm.AENotify,435147,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_1_JA.Alarm.AESeverity,435148,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_1_JA.Alarm.AEShelveDuration,435149,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_1_JA.almPLCFault.BOOLS1,435154,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_1_JA.almPLCFault.BOOLS2,435155,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_1_JA.almPLCFault.AEBOOLS,435156,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_1_JA.almPLCFault.INT1,435157,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_JA.almPLCFault.INT2,435158,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_JA.almPLCFault.AENotify,435159,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_1_JA.almPLCFault.AESeverity,435160,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_1_JA.almPLCFault.AEShelveDuration,435161,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_1_ZS.Alarm.BOOLS1,435176,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_1_ZS.Alarm.BOOLS2,435177,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_1_ZS.Alarm.AEBOOLS,435178,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_1_ZS.Alarm.INT1,435179,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_ZS.Alarm.INT2,435180,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_ZS.Alarm.AENotify,435181,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_1_ZS.Alarm.AESeverity,435182,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_1_ZS.Alarm.AEShelveDuration,435183,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_1_ZS.almPLCFault.BOOLS1,435188,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_1_ZS.almPLCFault.BOOLS2,435189,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_1_ZS.almPLCFault.AEBOOLS,435190,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_1_ZS.almPLCFault.INT1,435191,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_ZS.almPLCFault.INT2,435192,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_1_ZS.almPLCFault.AENotify,435193,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_1_ZS.almPLCFault.AESeverity,435194,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_1_ZS.almPLCFault.AEShelveDuration,435195,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_2_JA.Alarm.BOOLS1,435212,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_2_JA.Alarm.BOOLS2,435213,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_2_JA.Alarm.AEBOOLS,435214,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_2_JA.Alarm.INT1,435215,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_JA.Alarm.INT2,435216,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_JA.Alarm.AENotify,435217,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_2_JA.Alarm.AESeverity,435218,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_2_JA.Alarm.AEShelveDuration,435219,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_2_JA.almPLCFault.BOOLS1,435224,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_2_JA.almPLCFault.BOOLS2,435225,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_2_JA.almPLCFault.AEBOOLS,435226,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_2_JA.almPLCFault.INT1,435227,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_JA.almPLCFault.INT2,435228,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_JA.almPLCFault.AENotify,435229,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_2_JA.almPLCFault.AESeverity,435230,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_2_JA.almPLCFault.AEShelveDuration,435231,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_2_ZS.Alarm.BOOLS1,435246,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_2_ZS.Alarm.BOOLS2,435247,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_2_ZS.Alarm.AEBOOLS,435248,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_2_ZS.Alarm.INT1,435249,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_ZS.Alarm.INT2,435250,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_ZS.Alarm.AENotify,435251,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_2_ZS.Alarm.AESeverity,435252,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_2_ZS.Alarm.AEShelveDuration,435253,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_UPS_001_2_ZS.almPLCFault.BOOLS1,435258,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_UPS_001_2_ZS.almPLCFault.BOOLS2,435259,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_UPS_001_2_ZS.almPLCFault.AEBOOLS,435260,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_UPS_001_2_ZS.almPLCFault.INT1,435261,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_ZS.almPLCFault.INT2,435262,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_UPS_001_2_ZS.almPLCFault.AENotify,435263,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_UPS_001_2_ZS.almPLCFault.AESeverity,435264,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_UPS_001_2_ZS.almPLCFault.AEShelveDuration,435265,Short,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0112_1A_ZA.Alarm.BOOLS1,435282,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0112_1A_ZA.Alarm.BOOLS2,435283,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0112_1A_ZA.Alarm.AEBOOLS,435284,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0112_1A_ZA.Alarm.INT1,435285,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0112_1A_ZA.Alarm.INT2,435286,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0112_1A_ZA.Alarm.AENotify,435287,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0112_1A_ZA.Alarm.AESeverity,435288,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0112_1A_ZA.Alarm.AEShelveDuration,435289,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0112_1A_ZA.almPLCFault.BOOLS1,435294,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0112_1A_ZA.almPLCFault.BOOLS2,435295,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0112_1A_ZA.almPLCFault.AEBOOLS,435296,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0112_1A_ZA.almPLCFault.INT1,435297,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0112_1A_ZA.almPLCFault.INT2,435298,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0112_1A_ZA.almPLCFault.AENotify,435299,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0112_1A_ZA.almPLCFault.AESeverity,435300,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0112_1A_ZA.almPLCFault.AEShelveDuration,435301,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_1A_ZA.Alarm.BOOLS1,435316,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_1A_ZA.Alarm.BOOLS2,435317,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_1A_ZA.Alarm.AEBOOLS,435318,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_1A_ZA.Alarm.INT1,435319,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1A_ZA.Alarm.INT2,435320,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1A_ZA.Alarm.AENotify,435321,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_1A_ZA.Alarm.AESeverity,435322,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_1A_ZA.Alarm.AEShelveDuration,435323,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_1A_ZA.almPLCFault.BOOLS1,435328,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_1A_ZA.almPLCFault.BOOLS2,435329,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_1A_ZA.almPLCFault.AEBOOLS,435330,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_1A_ZA.almPLCFault.INT1,435331,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1A_ZA.almPLCFault.INT2,435332,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1A_ZA.almPLCFault.AENotify,435333,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_1A_ZA.almPLCFault.AESeverity,435334,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_1A_ZA.almPLCFault.AEShelveDuration,435335,Short,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_1B_ZA.Alarm.BOOLS1,435352,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_1B_ZA.Alarm.BOOLS2,435353,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_1B_ZA.Alarm.AEBOOLS,435354,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_1B_ZA.Alarm.INT1,435355,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1B_ZA.Alarm.INT2,435356,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1B_ZA.Alarm.AENotify,435357,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_1B_ZA.Alarm.AESeverity,435358,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_1B_ZA.Alarm.AEShelveDuration,435359,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_1B_ZA.almPLCFault.BOOLS1,435364,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_1B_ZA.almPLCFault.BOOLS2,435365,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_1B_ZA.almPLCFault.AEBOOLS,435366,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_1B_ZA.almPLCFault.INT1,435367,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1B_ZA.almPLCFault.INT2,435368,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_1B_ZA.almPLCFault.AENotify,435369,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_1B_ZA.almPLCFault.AESeverity,435370,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_1B_ZA.almPLCFault.AEShelveDuration,435371,Short,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_2A_ZA.Alarm.BOOLS1,435386,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_2A_ZA.Alarm.BOOLS2,435387,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_2A_ZA.Alarm.AEBOOLS,435388,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_2A_ZA.Alarm.INT1,435389,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2A_ZA.Alarm.INT2,435390,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2A_ZA.Alarm.AENotify,435391,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_2A_ZA.Alarm.AESeverity,435392,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_2A_ZA.Alarm.AEShelveDuration,435393,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_2A_ZA.almPLCFault.BOOLS1,435398,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_2A_ZA.almPLCFault.BOOLS2,435399,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_2A_ZA.almPLCFault.AEBOOLS,435400,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_2A_ZA.almPLCFault.INT1,435401,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2A_ZA.almPLCFault.INT2,435402,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2A_ZA.almPLCFault.AENotify,435403,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_2A_ZA.almPLCFault.AESeverity,435404,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_2A_ZA.almPLCFault.AEShelveDuration,435405,Short,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_2B_ZA.Alarm.BOOLS1,435422,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_2B_ZA.Alarm.BOOLS2,435423,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_2B_ZA.Alarm.AEBOOLS,435424,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_2B_ZA.Alarm.INT1,435425,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2B_ZA.Alarm.INT2,435426,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2B_ZA.Alarm.AENotify,435427,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_2B_ZA.Alarm.AESeverity,435428,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_2B_ZA.Alarm.AEShelveDuration,435429,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XE_0113_2B_ZA.almPLCFault.BOOLS1,435434,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XE_0113_2B_ZA.almPLCFault.BOOLS2,435435,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XE_0113_2B_ZA.almPLCFault.AEBOOLS,435436,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XE_0113_2B_ZA.almPLCFault.INT1,435437,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2B_ZA.almPLCFault.INT2,435438,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XE_0113_2B_ZA.almPLCFault.AENotify,435439,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XE_0113_2B_ZA.almPLCFault.AESeverity,435440,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XE_0113_2B_ZA.almPLCFault.AEShelveDuration,435441,Short,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_LL.Alarm.BOOLS1,435456,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_LL.Alarm.BOOLS2,435457,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_LL.Alarm.AEBOOLS,435458,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_LL.Alarm.INT1,435459,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_LL.Alarm.INT2,435460,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_LL.Alarm.AENotify,435461,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_LL.Alarm.AESeverity,435462,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_LL.Alarm.AEShelveDuration,435463,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_LL.almPLCFault.BOOLS1,435468,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_LL.almPLCFault.BOOLS2,435469,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_LL.almPLCFault.AEBOOLS,435470,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_LL.almPLCFault.INT1,435471,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_LL.almPLCFault.INT2,435472,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_LL.almPLCFault.AENotify,435473,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_LL.almPLCFault.AESeverity,435474,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_LL.almPLCFault.AEShelveDuration,435475,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_TH1.Alarm.BOOLS1,435492,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_TH1.Alarm.BOOLS2,435493,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_TH1.Alarm.AEBOOLS,435494,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_TH1.Alarm.INT1,435495,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH1.Alarm.INT2,435496,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH1.Alarm.AENotify,435497,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_TH1.Alarm.AESeverity,435498,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_TH1.Alarm.AEShelveDuration,435499,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_TH1.almPLCFault.BOOLS1,435504,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_TH1.almPLCFault.BOOLS2,435505,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_TH1.almPLCFault.AEBOOLS,435506,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_TH1.almPLCFault.INT1,435507,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH1.almPLCFault.INT2,435508,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH1.almPLCFault.AENotify,435509,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_TH1.almPLCFault.AESeverity,435510,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_TH1.almPLCFault.AEShelveDuration,435511,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_TH2.Alarm.BOOLS1,435526,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_TH2.Alarm.BOOLS2,435527,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_TH2.Alarm.AEBOOLS,435528,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_TH2.Alarm.INT1,435529,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH2.Alarm.INT2,435530,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH2.Alarm.AENotify,435531,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_TH2.Alarm.AESeverity,435532,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_TH2.Alarm.AEShelveDuration,435533,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_TH2.almPLCFault.BOOLS1,435538,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_TH2.almPLCFault.BOOLS2,435539,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_TH2.almPLCFault.AEBOOLS,435540,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_TH2.almPLCFault.INT1,435541,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH2.almPLCFault.INT2,435542,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_TH2.almPLCFault.AENotify,435543,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_TH2.almPLCFault.AESeverity,435544,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_TH2.almPLCFault.AEShelveDuration,435545,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_XA.Alarm.BOOLS1,435562,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_XA.Alarm.BOOLS2,435563,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_XA.Alarm.AEBOOLS,435564,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_XA.Alarm.INT1,435565,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_XA.Alarm.INT2,435566,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_XA.Alarm.AENotify,435567,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_XA.Alarm.AESeverity,435568,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_XA.Alarm.AEShelveDuration,435569,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_3_XA.almPLCFault.BOOLS1,435574,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_3_XA.almPLCFault.BOOLS2,435575,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_3_XA.almPLCFault.AEBOOLS,435576,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_3_XA.almPLCFault.INT1,435577,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_XA.almPLCFault.INT2,435578,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_3_XA.almPLCFault.AENotify,435579,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_3_XA.almPLCFault.AESeverity,435580,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_3_XA.almPLCFault.AEShelveDuration,435581,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_LL.Alarm.BOOLS1,435596,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_LL.Alarm.BOOLS2,435597,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_LL.Alarm.AEBOOLS,435598,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_LL.Alarm.INT1,435599,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_LL.Alarm.INT2,435600,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_LL.Alarm.AENotify,435601,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_LL.Alarm.AESeverity,435602,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_LL.Alarm.AEShelveDuration,435603,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_LL.almPLCFault.BOOLS1,435608,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_LL.almPLCFault.BOOLS2,435609,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_LL.almPLCFault.AEBOOLS,435610,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_LL.almPLCFault.INT1,435611,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_LL.almPLCFault.INT2,435612,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_LL.almPLCFault.AENotify,435613,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_LL.almPLCFault.AESeverity,435614,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_LL.almPLCFault.AEShelveDuration,435615,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_TH1.Alarm.BOOLS1,435632,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_TH1.Alarm.BOOLS2,435633,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_TH1.Alarm.AEBOOLS,435634,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_TH1.Alarm.INT1,435635,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH1.Alarm.INT2,435636,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH1.Alarm.AENotify,435637,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_TH1.Alarm.AESeverity,435638,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_TH1.Alarm.AEShelveDuration,435639,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_TH1.almPLCFault.BOOLS1,435644,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_TH1.almPLCFault.BOOLS2,435645,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_TH1.almPLCFault.AEBOOLS,435646,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_TH1.almPLCFault.INT1,435647,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH1.almPLCFault.INT2,435648,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH1.almPLCFault.AENotify,435649,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_TH1.almPLCFault.AESeverity,435650,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_TH1.almPLCFault.AEShelveDuration,435651,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_TH2.Alarm.BOOLS1,435666,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_TH2.Alarm.BOOLS2,435667,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_TH2.Alarm.AEBOOLS,435668,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_TH2.Alarm.INT1,435669,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH2.Alarm.INT2,435670,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH2.Alarm.AENotify,435671,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_TH2.Alarm.AESeverity,435672,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_TH2.Alarm.AEShelveDuration,435673,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_TH2.almPLCFault.BOOLS1,435678,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_TH2.almPLCFault.BOOLS2,435679,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_TH2.almPLCFault.AEBOOLS,435680,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_TH2.almPLCFault.INT1,435681,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH2.almPLCFault.INT2,435682,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_TH2.almPLCFault.AENotify,435683,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_TH2.almPLCFault.AESeverity,435684,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_TH2.almPLCFault.AEShelveDuration,435685,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_XA.Alarm.BOOLS1,435702,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_XA.Alarm.BOOLS2,435703,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_XA.Alarm.AEBOOLS,435704,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_XA.Alarm.INT1,435705,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_XA.Alarm.INT2,435706,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_XA.Alarm.AENotify,435707,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_XA.Alarm.AESeverity,435708,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_XA.Alarm.AEShelveDuration,435709,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_4_XA.almPLCFault.BOOLS1,435714,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_4_XA.almPLCFault.BOOLS2,435715,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_4_XA.almPLCFault.AEBOOLS,435716,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_4_XA.almPLCFault.INT1,435717,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_XA.almPLCFault.INT2,435718,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_4_XA.almPLCFault.AENotify,435719,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_4_XA.almPLCFault.AESeverity,435720,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_4_XA.almPLCFault.AEShelveDuration,435721,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_LL.Alarm.BOOLS1,435736,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_LL.Alarm.BOOLS2,435737,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_LL.Alarm.AEBOOLS,435738,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_LL.Alarm.INT1,435739,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_LL.Alarm.INT2,435740,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_LL.Alarm.AENotify,435741,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_LL.Alarm.AESeverity,435742,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_LL.Alarm.AEShelveDuration,435743,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_LL.almPLCFault.BOOLS1,435748,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_LL.almPLCFault.BOOLS2,435749,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_LL.almPLCFault.AEBOOLS,435750,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_LL.almPLCFault.INT1,435751,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_LL.almPLCFault.INT2,435752,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_LL.almPLCFault.AENotify,435753,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_LL.almPLCFault.AESeverity,435754,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_LL.almPLCFault.AEShelveDuration,435755,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_TH1.Alarm.BOOLS1,435772,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_TH1.Alarm.BOOLS2,435773,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_TH1.Alarm.AEBOOLS,435774,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_TH1.Alarm.INT1,435775,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH1.Alarm.INT2,435776,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH1.Alarm.AENotify,435777,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_TH1.Alarm.AESeverity,435778,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_TH1.Alarm.AEShelveDuration,435779,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_TH1.almPLCFault.BOOLS1,435784,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_TH1.almPLCFault.BOOLS2,435785,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_TH1.almPLCFault.AEBOOLS,435786,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_TH1.almPLCFault.INT1,435787,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH1.almPLCFault.INT2,435788,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH1.almPLCFault.AENotify,435789,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_TH1.almPLCFault.AESeverity,435790,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_TH1.almPLCFault.AEShelveDuration,435791,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_TH2.Alarm.BOOLS1,435806,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_TH2.Alarm.BOOLS2,435807,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_TH2.Alarm.AEBOOLS,435808,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_TH2.Alarm.INT1,435809,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH2.Alarm.INT2,435810,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH2.Alarm.AENotify,435811,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_TH2.Alarm.AESeverity,435812,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_TH2.Alarm.AEShelveDuration,435813,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_TH2.almPLCFault.BOOLS1,435818,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_TH2.almPLCFault.BOOLS2,435819,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_TH2.almPLCFault.AEBOOLS,435820,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_TH2.almPLCFault.INT1,435821,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH2.almPLCFault.INT2,435822,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_TH2.almPLCFault.AENotify,435823,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_TH2.almPLCFault.AESeverity,435824,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_TH2.almPLCFault.AEShelveDuration,435825,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_XA.Alarm.BOOLS1,435842,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_XA.Alarm.BOOLS2,435843,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_XA.Alarm.AEBOOLS,435844,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_XA.Alarm.INT1,435845,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_XA.Alarm.INT2,435846,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_XA.Alarm.AENotify,435847,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_XA.Alarm.AESeverity,435848,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_XA.Alarm.AEShelveDuration,435849,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_5_XA.almPLCFault.BOOLS1,435854,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_5_XA.almPLCFault.BOOLS2,435855,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_5_XA.almPLCFault.AEBOOLS,435856,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_5_XA.almPLCFault.INT1,435857,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_XA.almPLCFault.INT2,435858,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_5_XA.almPLCFault.AENotify,435859,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_5_XA.almPLCFault.AESeverity,435860,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_5_XA.almPLCFault.AEShelveDuration,435861,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_LL.Alarm.BOOLS1,435876,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_LL.Alarm.BOOLS2,435877,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_LL.Alarm.AEBOOLS,435878,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_LL.Alarm.INT1,435879,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_LL.Alarm.INT2,435880,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_LL.Alarm.AENotify,435881,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_LL.Alarm.AESeverity,435882,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_LL.Alarm.AEShelveDuration,435883,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_LL.almPLCFault.BOOLS1,435888,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_LL.almPLCFault.BOOLS2,435889,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_LL.almPLCFault.AEBOOLS,435890,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_LL.almPLCFault.INT1,435891,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_LL.almPLCFault.INT2,435892,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_LL.almPLCFault.AENotify,435893,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_LL.almPLCFault.AESeverity,435894,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_LL.almPLCFault.AEShelveDuration,435895,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_TH1.Alarm.BOOLS1,435912,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_TH1.Alarm.BOOLS2,435913,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_TH1.Alarm.AEBOOLS,435914,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_TH1.Alarm.INT1,435915,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH1.Alarm.INT2,435916,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH1.Alarm.AENotify,435917,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_TH1.Alarm.AESeverity,435918,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_TH1.Alarm.AEShelveDuration,435919,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_TH1.almPLCFault.BOOLS1,435924,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_TH1.almPLCFault.BOOLS2,435925,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_TH1.almPLCFault.AEBOOLS,435926,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_TH1.almPLCFault.INT1,435927,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH1.almPLCFault.INT2,435928,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH1.almPLCFault.AENotify,435929,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_TH1.almPLCFault.AESeverity,435930,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_TH1.almPLCFault.AEShelveDuration,435931,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_TH2.Alarm.BOOLS1,435946,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_TH2.Alarm.BOOLS2,435947,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_TH2.Alarm.AEBOOLS,435948,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_TH2.Alarm.INT1,435949,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH2.Alarm.INT2,435950,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH2.Alarm.AENotify,435951,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_TH2.Alarm.AESeverity,435952,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_TH2.Alarm.AEShelveDuration,435953,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_TH2.almPLCFault.BOOLS1,435958,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_TH2.almPLCFault.BOOLS2,435959,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_TH2.almPLCFault.AEBOOLS,435960,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_TH2.almPLCFault.INT1,435961,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH2.almPLCFault.INT2,435962,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_TH2.almPLCFault.AENotify,435963,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_TH2.almPLCFault.AESeverity,435964,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_TH2.almPLCFault.AEShelveDuration,435965,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_XA.Alarm.BOOLS1,435982,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_XA.Alarm.BOOLS2,435983,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_XA.Alarm.AEBOOLS,435984,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_XA.Alarm.INT1,435985,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_XA.Alarm.INT2,435986,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_XA.Alarm.AENotify,435987,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_XA.Alarm.AESeverity,435988,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_XA.Alarm.AEShelveDuration,435989,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_XFR_0131_6_XA.almPLCFault.BOOLS1,435994,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_XFR_0131_6_XA.almPLCFault.BOOLS2,435995,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_XFR_0131_6_XA.almPLCFault.AEBOOLS,435996,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_XFR_0131_6_XA.almPLCFault.INT1,435997,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_XA.almPLCFault.INT2,435998,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_XFR_0131_6_XA.almPLCFault.AENotify,435999,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_XFR_0131_6_XA.almPLCFault.AESeverity,436000,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_XFR_0131_6_XA.almPLCFault.AEShelveDuration,436001,Short,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EASTMICRO_FAIL.Alarm.BOOLS1,436016,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EASTMICRO_FAIL.Alarm.BOOLS2,436017,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EASTMICRO_FAIL.Alarm.AEBOOLS,436018,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EASTMICRO_FAIL.Alarm.INT1,436019,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EASTMICRO_FAIL.Alarm.INT2,436020,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EASTMICRO_FAIL.Alarm.AENotify,436021,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EASTMICRO_FAIL.Alarm.AESeverity,436022,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EASTMICRO_FAIL.Alarm.AEShelveDuration,436023,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.BOOLS1,436028,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.BOOLS2,436029,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AEBOOLS,436030,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.INT1,436031,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.INT2,436032,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AENotify,436033,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AESeverity,436034,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.AEShelveDuration,436035,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.BOOLS1,436052,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.BOOLS2,436053,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AEBOOLS,436054,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.INT1,436055,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.INT2,436056,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AENotify,436057,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AESeverity,436058,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.AEShelveDuration,436059,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.BOOLS1,436064,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.BOOLS2,436065,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AEBOOLS,436066,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.INT1,436067,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.INT2,436068,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AENotify,436069,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AESeverity,436070,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.AEShelveDuration,436071,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.BOOLS1,436086,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.BOOLS2,436087,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AEBOOLS,436088,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.INT1,436089,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.INT2,436090,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AENotify,436091,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AESeverity,436092,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.AEShelveDuration,436093,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.BOOLS1,436098,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.BOOLS2,436099,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AEBOOLS,436100,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.INT1,436101,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.INT2,436102,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AENotify,436103,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AESeverity,436104,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.AEShelveDuration,436105,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.BOOLS1,436122,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.BOOLS2,436123,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AEBOOLS,436124,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.INT1,436125,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.INT2,436126,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AENotify,436127,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AESeverity,436128,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.AEShelveDuration,436129,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.BOOLS1,436134,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.BOOLS2,436135,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AEBOOLS,436136,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.INT1,436137,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.INT2,436138,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AENotify,436139,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AESeverity,436140,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.AEShelveDuration,436141,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_METER_VAULT_FAIL.Alarm.BOOLS1,436156,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_METER_VAULT_FAIL.Alarm.BOOLS2,436157,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_METER_VAULT_FAIL.Alarm.AEBOOLS,436158,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_METER_VAULT_FAIL.Alarm.INT1,436159,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_METER_VAULT_FAIL.Alarm.INT2,436160,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_METER_VAULT_FAIL.Alarm.AENotify,436161,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_METER_VAULT_FAIL.Alarm.AESeverity,436162,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_METER_VAULT_FAIL.Alarm.AEShelveDuration,436163,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.BOOLS1,436168,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.BOOLS2,436169,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AEBOOLS,436170,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.INT1,436171,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.INT2,436172,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AENotify,436173,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AESeverity,436174,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.AEShelveDuration,436175,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.BOOLS1,436192,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.BOOLS2,436193,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AEBOOLS,436194,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.INT1,436195,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.INT2,436196,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AENotify,436197,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AESeverity,436198,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.AEShelveDuration,436199,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.BOOLS1,436204,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.BOOLS2,436205,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AEBOOLS,436206,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.INT1,436207,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.INT2,436208,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AENotify,436209,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AESeverity,436210,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.AEShelveDuration,436211,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.BOOLS1,436226,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.BOOLS2,436227,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AEBOOLS,436228,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.INT1,436229,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.INT2,436230,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AENotify,436231,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AESeverity,436232,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.AEShelveDuration,436233,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.BOOLS1,436238,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.BOOLS2,436239,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AEBOOLS,436240,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.INT1,436241,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.INT2,436242,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AENotify,436243,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AESeverity,436244,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.AEShelveDuration,436245,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.BOOLS1,436262,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.BOOLS2,436263,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AEBOOLS,436264,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.INT1,436265,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.INT2,436266,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AENotify,436267,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AESeverity,436268,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.AEShelveDuration,436269,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.BOOLS1,436274,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.BOOLS2,436275,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AEBOOLS,436276,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.INT1,436277,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.INT2,436278,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AENotify,436279,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AESeverity,436280,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.AEShelveDuration,436281,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_TSR_PLC_FAIL.Alarm.BOOLS1,436296,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_TSR_PLC_FAIL.Alarm.BOOLS2,436297,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_TSR_PLC_FAIL.Alarm.AEBOOLS,436298,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_TSR_PLC_FAIL.Alarm.INT1,436299,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_TSR_PLC_FAIL.Alarm.INT2,436300,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_TSR_PLC_FAIL.Alarm.AENotify,436301,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_TSR_PLC_FAIL.Alarm.AESeverity,436302,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_TSR_PLC_FAIL.Alarm.AEShelveDuration,436303,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.BOOLS1,436308,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.BOOLS2,436309,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AEBOOLS,436310,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.INT1,436311,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.INT2,436312,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AENotify,436313,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AESeverity,436314,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.AEShelveDuration,436315,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_WESTMICRO_FAIL.Alarm.BOOLS1,436332,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_WESTMICRO_FAIL.Alarm.BOOLS2,436333,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_WESTMICRO_FAIL.Alarm.AEBOOLS,436334,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_WESTMICRO_FAIL.Alarm.INT1,436335,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_WESTMICRO_FAIL.Alarm.INT2,436336,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_WESTMICRO_FAIL.Alarm.AENotify,436337,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_WESTMICRO_FAIL.Alarm.AESeverity,436338,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_WESTMICRO_FAIL.Alarm.AEShelveDuration,436339,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.BOOLS1,436344,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.BOOLS2,436345,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AEBOOLS,436346,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.INT1,436347,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.INT2,436348,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AENotify,436349,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AESeverity,436350,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.AEShelveDuration,436351,Short,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1.almFailToStrt.BOOLS1,436410,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.almFailToStrt.BOOLS2,436411,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.almFailToStrt.AEBOOLS,436412,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1.almFailToStrt.INT1,436413,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almFailToStrt.INT2,436414,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almFailToStrt.AENotify,436415,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1.almFailToStrt.AESeverity,436416,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1.almFailToStrt.AEShelveDuration,436417,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1.almFailToStop.BOOLS1,436422,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.almFailToStop.BOOLS2,436423,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.almFailToStop.AEBOOLS,436424,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1.almFailToStop.INT1,436425,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almFailToStop.INT2,436426,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almFailToStop.AENotify,436427,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1.almFailToStop.AESeverity,436428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1.almFailToStop.AEShelveDuration,436429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1.almMotorFailure.BOOLS1,436434,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.almMotorFailure.BOOLS2,436435,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.almMotorFailure.AEBOOLS,436436,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1.almMotorFailure.INT1,436437,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almMotorFailure.INT2,436438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almMotorFailure.AENotify,436439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1.almMotorFailure.AESeverity,436440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1.almMotorFailure.AEShelveDuration,436441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1.almPLCFault.BOOLS1,436446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.almPLCFault.BOOLS2,436447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.almPLCFault.AEBOOLS,436448,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1.almPLCFault.INT1,436449,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almPLCFault.INT2,436450,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almPLCFault.AENotify,436451,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1.almPLCFault.AESeverity,436452,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1.almPLCFault.AEShelveDuration,436453,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1.almSpeedDeviation.BOOLS1,436458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_1.almSpeedDeviation.BOOLS2,436459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_1.almSpeedDeviation.AEBOOLS,436460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_1.almSpeedDeviation.INT1,436461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almSpeedDeviation.INT2,436462,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_1.almSpeedDeviation.AENotify,436463,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_1.almSpeedDeviation.AESeverity,436464,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_1.almSpeedDeviation.AEShelveDuration,436465,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2.almFailToStrt.BOOLS1,436546,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.almFailToStrt.BOOLS2,436547,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.almFailToStrt.AEBOOLS,436548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2.almFailToStrt.INT1,436549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almFailToStrt.INT2,436550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almFailToStrt.AENotify,436551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2.almFailToStrt.AESeverity,436552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2.almFailToStrt.AEShelveDuration,436553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2.almFailToStop.BOOLS1,436558,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.almFailToStop.BOOLS2,436559,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.almFailToStop.AEBOOLS,436560,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2.almFailToStop.INT1,436561,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almFailToStop.INT2,436562,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almFailToStop.AENotify,436563,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2.almFailToStop.AESeverity,436564,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2.almFailToStop.AEShelveDuration,436565,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2.almMotorFailure.BOOLS1,436570,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.almMotorFailure.BOOLS2,436571,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.almMotorFailure.AEBOOLS,436572,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2.almMotorFailure.INT1,436573,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almMotorFailure.INT2,436574,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almMotorFailure.AENotify,436575,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2.almMotorFailure.AESeverity,436576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2.almMotorFailure.AEShelveDuration,436577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2.almPLCFault.BOOLS1,436582,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.almPLCFault.BOOLS2,436583,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.almPLCFault.AEBOOLS,436584,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2.almPLCFault.INT1,436585,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almPLCFault.INT2,436586,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almPLCFault.AENotify,436587,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2.almPLCFault.AESeverity,436588,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2.almPLCFault.AEShelveDuration,436589,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_2.almSpeedDeviation.BOOLS1,436594,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_2.almSpeedDeviation.BOOLS2,436595,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_2.almSpeedDeviation.AEBOOLS,436596,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_2.almSpeedDeviation.INT1,436597,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almSpeedDeviation.INT2,436598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_2.almSpeedDeviation.AENotify,436599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_2.almSpeedDeviation.AESeverity,436600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_2.almSpeedDeviation.AEShelveDuration,436601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3.almFailToStrt.BOOLS1,436680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.almFailToStrt.BOOLS2,436681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.almFailToStrt.AEBOOLS,436682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3.almFailToStrt.INT1,436683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almFailToStrt.INT2,436684,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almFailToStrt.AENotify,436685,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3.almFailToStrt.AESeverity,436686,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3.almFailToStrt.AEShelveDuration,436687,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3.almFailToStop.BOOLS1,436692,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.almFailToStop.BOOLS2,436693,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.almFailToStop.AEBOOLS,436694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3.almFailToStop.INT1,436695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almFailToStop.INT2,436696,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almFailToStop.AENotify,436697,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3.almFailToStop.AESeverity,436698,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3.almFailToStop.AEShelveDuration,436699,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3.almMotorFailure.BOOLS1,436704,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.almMotorFailure.BOOLS2,436705,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.almMotorFailure.AEBOOLS,436706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3.almMotorFailure.INT1,436707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almMotorFailure.INT2,436708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almMotorFailure.AENotify,436709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3.almMotorFailure.AESeverity,436710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3.almMotorFailure.AEShelveDuration,436711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3.almPLCFault.BOOLS1,436716,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.almPLCFault.BOOLS2,436717,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.almPLCFault.AEBOOLS,436718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3.almPLCFault.INT1,436719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almPLCFault.INT2,436720,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almPLCFault.AENotify,436721,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3.almPLCFault.AESeverity,436722,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3.almPLCFault.AEShelveDuration,436723,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_3.almSpeedDeviation.BOOLS1,436728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_3.almSpeedDeviation.BOOLS2,436729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_3.almSpeedDeviation.AEBOOLS,436730,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_3.almSpeedDeviation.INT1,436731,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almSpeedDeviation.INT2,436732,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_3.almSpeedDeviation.AENotify,436733,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_3.almSpeedDeviation.AESeverity,436734,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_3.almSpeedDeviation.AEShelveDuration,436735,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4.almFailToStrt.BOOLS1,436816,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.almFailToStrt.BOOLS2,436817,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.almFailToStrt.AEBOOLS,436818,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4.almFailToStrt.INT1,436819,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almFailToStrt.INT2,436820,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almFailToStrt.AENotify,436821,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4.almFailToStrt.AESeverity,436822,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4.almFailToStrt.AEShelveDuration,436823,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4.almFailToStop.BOOLS1,436828,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.almFailToStop.BOOLS2,436829,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.almFailToStop.AEBOOLS,436830,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4.almFailToStop.INT1,436831,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almFailToStop.INT2,436832,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almFailToStop.AENotify,436833,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4.almFailToStop.AESeverity,436834,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4.almFailToStop.AEShelveDuration,436835,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4.almMotorFailure.BOOLS1,436840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.almMotorFailure.BOOLS2,436841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.almMotorFailure.AEBOOLS,436842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4.almMotorFailure.INT1,436843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almMotorFailure.INT2,436844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almMotorFailure.AENotify,436845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4.almMotorFailure.AESeverity,436846,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4.almMotorFailure.AEShelveDuration,436847,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4.almPLCFault.BOOLS1,436852,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.almPLCFault.BOOLS2,436853,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.almPLCFault.AEBOOLS,436854,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4.almPLCFault.INT1,436855,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almPLCFault.INT2,436856,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almPLCFault.AENotify,436857,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4.almPLCFault.AESeverity,436858,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4.almPLCFault.AEShelveDuration,436859,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_4.almSpeedDeviation.BOOLS1,436864,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_4.almSpeedDeviation.BOOLS2,436865,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_4.almSpeedDeviation.AEBOOLS,436866,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_4.almSpeedDeviation.INT1,436867,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almSpeedDeviation.INT2,436868,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_4.almSpeedDeviation.AENotify,436869,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_4.almSpeedDeviation.AESeverity,436870,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_4.almSpeedDeviation.AEShelveDuration,436871,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5.almFailToStrt.BOOLS1,436950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.almFailToStrt.BOOLS2,436951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.almFailToStrt.AEBOOLS,436952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5.almFailToStrt.INT1,436953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almFailToStrt.INT2,436954,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almFailToStrt.AENotify,436955,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5.almFailToStrt.AESeverity,436956,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5.almFailToStrt.AEShelveDuration,436957,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5.almFailToStop.BOOLS1,436962,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.almFailToStop.BOOLS2,436963,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.almFailToStop.AEBOOLS,436964,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5.almFailToStop.INT1,436965,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almFailToStop.INT2,436966,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almFailToStop.AENotify,436967,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5.almFailToStop.AESeverity,436968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5.almFailToStop.AEShelveDuration,436969,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5.almMotorFailure.BOOLS1,436974,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.almMotorFailure.BOOLS2,436975,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.almMotorFailure.AEBOOLS,436976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5.almMotorFailure.INT1,436977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almMotorFailure.INT2,436978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almMotorFailure.AENotify,436979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5.almMotorFailure.AESeverity,436980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5.almMotorFailure.AEShelveDuration,436981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5.almPLCFault.BOOLS1,436986,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.almPLCFault.BOOLS2,436987,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.almPLCFault.AEBOOLS,436988,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5.almPLCFault.INT1,436989,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almPLCFault.INT2,436990,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almPLCFault.AENotify,436991,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5.almPLCFault.AESeverity,436992,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5.almPLCFault.AEShelveDuration,436993,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_5.almSpeedDeviation.BOOLS1,436998,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_5.almSpeedDeviation.BOOLS2,436999,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_5.almSpeedDeviation.AEBOOLS,437000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_5.almSpeedDeviation.INT1,437001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almSpeedDeviation.INT2,437002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_5.almSpeedDeviation.AENotify,437003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_5.almSpeedDeviation.AESeverity,437004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_5.almSpeedDeviation.AEShelveDuration,437005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6.almFailToStrt.BOOLS1,437086,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.almFailToStrt.BOOLS2,437087,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.almFailToStrt.AEBOOLS,437088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6.almFailToStrt.INT1,437089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almFailToStrt.INT2,437090,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almFailToStrt.AENotify,437091,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6.almFailToStrt.AESeverity,437092,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6.almFailToStrt.AEShelveDuration,437093,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6.almFailToStop.BOOLS1,437098,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.almFailToStop.BOOLS2,437099,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.almFailToStop.AEBOOLS,437100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6.almFailToStop.INT1,437101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almFailToStop.INT2,437102,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almFailToStop.AENotify,437103,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6.almFailToStop.AESeverity,437104,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6.almFailToStop.AEShelveDuration,437105,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6.almMotorFailure.BOOLS1,437110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.almMotorFailure.BOOLS2,437111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.almMotorFailure.AEBOOLS,437112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6.almMotorFailure.INT1,437113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almMotorFailure.INT2,437114,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almMotorFailure.AENotify,437115,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6.almMotorFailure.AESeverity,437116,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6.almMotorFailure.AEShelveDuration,437117,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6.almPLCFault.BOOLS1,437122,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.almPLCFault.BOOLS2,437123,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.almPLCFault.AEBOOLS,437124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6.almPLCFault.INT1,437125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almPLCFault.INT2,437126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almPLCFault.AENotify,437127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6.almPLCFault.AESeverity,437128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6.almPLCFault.AEShelveDuration,437129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_6.almSpeedDeviation.BOOLS1,437134,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_6.almSpeedDeviation.BOOLS2,437135,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_6.almSpeedDeviation.AEBOOLS,437136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_6.almSpeedDeviation.INT1,437137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almSpeedDeviation.INT2,437138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_6.almSpeedDeviation.AENotify,437139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_6.almSpeedDeviation.AESeverity,437140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_6.almSpeedDeviation.AEShelveDuration,437141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7.almFailToStrt.BOOLS1,437220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.almFailToStrt.BOOLS2,437221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.almFailToStrt.AEBOOLS,437222,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7.almFailToStrt.INT1,437223,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almFailToStrt.INT2,437224,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almFailToStrt.AENotify,437225,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7.almFailToStrt.AESeverity,437226,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7.almFailToStrt.AEShelveDuration,437227,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7.almFailToStop.BOOLS1,437232,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.almFailToStop.BOOLS2,437233,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.almFailToStop.AEBOOLS,437234,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7.almFailToStop.INT1,437235,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almFailToStop.INT2,437236,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almFailToStop.AENotify,437237,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7.almFailToStop.AESeverity,437238,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7.almFailToStop.AEShelveDuration,437239,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7.almMotorFailure.BOOLS1,437244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.almMotorFailure.BOOLS2,437245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.almMotorFailure.AEBOOLS,437246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7.almMotorFailure.INT1,437247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almMotorFailure.INT2,437248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almMotorFailure.AENotify,437249,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7.almMotorFailure.AESeverity,437250,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7.almMotorFailure.AEShelveDuration,437251,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7.almPLCFault.BOOLS1,437256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.almPLCFault.BOOLS2,437257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.almPLCFault.AEBOOLS,437258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7.almPLCFault.INT1,437259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almPLCFault.INT2,437260,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almPLCFault.AENotify,437261,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7.almPLCFault.AESeverity,437262,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7.almPLCFault.AEShelveDuration,437263,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_7.almSpeedDeviation.BOOLS1,437268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_7.almSpeedDeviation.BOOLS2,437269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_7.almSpeedDeviation.AEBOOLS,437270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_7.almSpeedDeviation.INT1,437271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almSpeedDeviation.INT2,437272,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_7.almSpeedDeviation.AENotify,437273,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_7.almSpeedDeviation.AESeverity,437274,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_7.almSpeedDeviation.AEShelveDuration,437275,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8.almFailToStrt.BOOLS1,437356,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.almFailToStrt.BOOLS2,437357,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.almFailToStrt.AEBOOLS,437358,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8.almFailToStrt.INT1,437359,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almFailToStrt.INT2,437360,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almFailToStrt.AENotify,437361,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8.almFailToStrt.AESeverity,437362,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8.almFailToStrt.AEShelveDuration,437363,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8.almFailToStop.BOOLS1,437368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.almFailToStop.BOOLS2,437369,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.almFailToStop.AEBOOLS,437370,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8.almFailToStop.INT1,437371,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almFailToStop.INT2,437372,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almFailToStop.AENotify,437373,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8.almFailToStop.AESeverity,437374,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8.almFailToStop.AEShelveDuration,437375,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8.almMotorFailure.BOOLS1,437380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.almMotorFailure.BOOLS2,437381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.almMotorFailure.AEBOOLS,437382,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8.almMotorFailure.INT1,437383,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almMotorFailure.INT2,437384,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almMotorFailure.AENotify,437385,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8.almMotorFailure.AESeverity,437386,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8.almMotorFailure.AEShelveDuration,437387,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8.almPLCFault.BOOLS1,437392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.almPLCFault.BOOLS2,437393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.almPLCFault.AEBOOLS,437394,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8.almPLCFault.INT1,437395,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almPLCFault.INT2,437396,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almPLCFault.AENotify,437397,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8.almPLCFault.AESeverity,437398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8.almPLCFault.AEShelveDuration,437399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_8.almSpeedDeviation.BOOLS1,437404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_8.almSpeedDeviation.BOOLS2,437405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_8.almSpeedDeviation.AEBOOLS,437406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_8.almSpeedDeviation.INT1,437407,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almSpeedDeviation.INT2,437408,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_8.almSpeedDeviation.AENotify,437409,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_8.almSpeedDeviation.AESeverity,437410,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_8.almSpeedDeviation.AEShelveDuration,437411,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9.almFailToStrt.BOOLS1,437490,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.almFailToStrt.BOOLS2,437491,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.almFailToStrt.AEBOOLS,437492,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9.almFailToStrt.INT1,437493,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almFailToStrt.INT2,437494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almFailToStrt.AENotify,437495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9.almFailToStrt.AESeverity,437496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9.almFailToStrt.AEShelveDuration,437497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9.almFailToStop.BOOLS1,437502,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.almFailToStop.BOOLS2,437503,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.almFailToStop.AEBOOLS,437504,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9.almFailToStop.INT1,437505,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almFailToStop.INT2,437506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almFailToStop.AENotify,437507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9.almFailToStop.AESeverity,437508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9.almFailToStop.AEShelveDuration,437509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9.almMotorFailure.BOOLS1,437514,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.almMotorFailure.BOOLS2,437515,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.almMotorFailure.AEBOOLS,437516,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9.almMotorFailure.INT1,437517,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almMotorFailure.INT2,437518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almMotorFailure.AENotify,437519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9.almMotorFailure.AESeverity,437520,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9.almMotorFailure.AEShelveDuration,437521,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9.almPLCFault.BOOLS1,437526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.almPLCFault.BOOLS2,437527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.almPLCFault.AEBOOLS,437528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9.almPLCFault.INT1,437529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almPLCFault.INT2,437530,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almPLCFault.AENotify,437531,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9.almPLCFault.AESeverity,437532,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9.almPLCFault.AEShelveDuration,437533,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_9.almSpeedDeviation.BOOLS1,437538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_AFD_0103_9.almSpeedDeviation.BOOLS2,437539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_AFD_0103_9.almSpeedDeviation.AEBOOLS,437540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_AFD_0103_9.almSpeedDeviation.INT1,437541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almSpeedDeviation.INT2,437542,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_AFD_0103_9.almSpeedDeviation.AENotify,437543,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_AFD_0103_9.almSpeedDeviation.AESeverity,437544,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_AFD_0103_9.almSpeedDeviation.AEShelveDuration,437545,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A.almFailToOpen.BOOLS1,437602,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A.almFailToOpen.BOOLS2,437603,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A.almFailToOpen.AEBOOLS,437604,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A.almFailToOpen.INT1,437605,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almFailToOpen.INT2,437606,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almFailToOpen.AENotify,437607,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A.almFailToOpen.AESeverity,437608,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A.almFailToOpen.AEShelveDuration,437609,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A.almFailToClose.BOOLS1,437614,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A.almFailToClose.BOOLS2,437615,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A.almFailToClose.AEBOOLS,437616,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A.almFailToClose.INT1,437617,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almFailToClose.INT2,437618,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almFailToClose.AENotify,437619,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A.almFailToClose.AESeverity,437620,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A.almFailToClose.AEShelveDuration,437621,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A.almActuatorFault.BOOLS1,437626,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A.almActuatorFault.BOOLS2,437627,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A.almActuatorFault.AEBOOLS,437628,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A.almActuatorFault.INT1,437629,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almActuatorFault.INT2,437630,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almActuatorFault.AENotify,437631,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A.almActuatorFault.AESeverity,437632,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A.almActuatorFault.AEShelveDuration,437633,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1A.almPLCFault.BOOLS1,437638,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1A.almPLCFault.BOOLS2,437639,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1A.almPLCFault.AEBOOLS,437640,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1A.almPLCFault.INT1,437641,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almPLCFault.INT2,437642,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1A.almPLCFault.AENotify,437643,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1A.almPLCFault.AESeverity,437644,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1A.almPLCFault.AEShelveDuration,437645,Short,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B.almFailToOpen.BOOLS1,437682,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B.almFailToOpen.BOOLS2,437683,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B.almFailToOpen.AEBOOLS,437684,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B.almFailToOpen.INT1,437685,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almFailToOpen.INT2,437686,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almFailToOpen.AENotify,437687,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B.almFailToOpen.AESeverity,437688,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B.almFailToOpen.AEShelveDuration,437689,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B.almFailToClose.BOOLS1,437694,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B.almFailToClose.BOOLS2,437695,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B.almFailToClose.AEBOOLS,437696,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B.almFailToClose.INT1,437697,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almFailToClose.INT2,437698,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almFailToClose.AENotify,437699,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B.almFailToClose.AESeverity,437700,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B.almFailToClose.AEShelveDuration,437701,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B.almActuatorFault.BOOLS1,437706,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B.almActuatorFault.BOOLS2,437707,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B.almActuatorFault.AEBOOLS,437708,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B.almActuatorFault.INT1,437709,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almActuatorFault.INT2,437710,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almActuatorFault.AENotify,437711,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B.almActuatorFault.AESeverity,437712,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B.almActuatorFault.AEShelveDuration,437713,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_1B.almPLCFault.BOOLS1,437718,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_1B.almPLCFault.BOOLS2,437719,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_1B.almPLCFault.AEBOOLS,437720,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_1B.almPLCFault.INT1,437721,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almPLCFault.INT2,437722,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_1B.almPLCFault.AENotify,437723,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_1B.almPLCFault.AESeverity,437724,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_1B.almPLCFault.AEShelveDuration,437725,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A.almFailToOpen.BOOLS1,437762,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A.almFailToOpen.BOOLS2,437763,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A.almFailToOpen.AEBOOLS,437764,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A.almFailToOpen.INT1,437765,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almFailToOpen.INT2,437766,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almFailToOpen.AENotify,437767,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A.almFailToOpen.AESeverity,437768,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A.almFailToOpen.AEShelveDuration,437769,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A.almFailToClose.BOOLS1,437774,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A.almFailToClose.BOOLS2,437775,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A.almFailToClose.AEBOOLS,437776,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A.almFailToClose.INT1,437777,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almFailToClose.INT2,437778,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almFailToClose.AENotify,437779,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A.almFailToClose.AESeverity,437780,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A.almFailToClose.AEShelveDuration,437781,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A.almActuatorFault.BOOLS1,437786,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A.almActuatorFault.BOOLS2,437787,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A.almActuatorFault.AEBOOLS,437788,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A.almActuatorFault.INT1,437789,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almActuatorFault.INT2,437790,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almActuatorFault.AENotify,437791,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A.almActuatorFault.AESeverity,437792,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A.almActuatorFault.AEShelveDuration,437793,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2A.almPLCFault.BOOLS1,437798,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2A.almPLCFault.BOOLS2,437799,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2A.almPLCFault.AEBOOLS,437800,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2A.almPLCFault.INT1,437801,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almPLCFault.INT2,437802,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2A.almPLCFault.AENotify,437803,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2A.almPLCFault.AESeverity,437804,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2A.almPLCFault.AEShelveDuration,437805,Short,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B.almFailToOpen.BOOLS1,437842,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B.almFailToOpen.BOOLS2,437843,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B.almFailToOpen.AEBOOLS,437844,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B.almFailToOpen.INT1,437845,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almFailToOpen.INT2,437846,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almFailToOpen.AENotify,437847,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B.almFailToOpen.AESeverity,437848,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B.almFailToOpen.AEShelveDuration,437849,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B.almFailToClose.BOOLS1,437854,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B.almFailToClose.BOOLS2,437855,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B.almFailToClose.AEBOOLS,437856,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B.almFailToClose.INT1,437857,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almFailToClose.INT2,437858,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almFailToClose.AENotify,437859,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B.almFailToClose.AESeverity,437860,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B.almFailToClose.AEShelveDuration,437861,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B.almActuatorFault.BOOLS1,437866,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B.almActuatorFault.BOOLS2,437867,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B.almActuatorFault.AEBOOLS,437868,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B.almActuatorFault.INT1,437869,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almActuatorFault.INT2,437870,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almActuatorFault.AENotify,437871,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B.almActuatorFault.AESeverity,437872,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B.almActuatorFault.AEShelveDuration,437873,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0102_2B.almPLCFault.BOOLS1,437878,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0102_2B.almPLCFault.BOOLS2,437879,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0102_2B.almPLCFault.AEBOOLS,437880,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0102_2B.almPLCFault.INT1,437881,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almPLCFault.INT2,437882,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0102_2B.almPLCFault.AENotify,437883,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0102_2B.almPLCFault.AESeverity,437884,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0102_2B.almPLCFault.AEShelveDuration,437885,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A.almFailToOpen.BOOLS1,437922,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A.almFailToOpen.BOOLS2,437923,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A.almFailToOpen.AEBOOLS,437924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A.almFailToOpen.INT1,437925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almFailToOpen.INT2,437926,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almFailToOpen.AENotify,437927,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A.almFailToOpen.AESeverity,437928,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A.almFailToOpen.AEShelveDuration,437929,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A.almFailToClose.BOOLS1,437934,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A.almFailToClose.BOOLS2,437935,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A.almFailToClose.AEBOOLS,437936,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A.almFailToClose.INT1,437937,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almFailToClose.INT2,437938,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almFailToClose.AENotify,437939,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A.almFailToClose.AESeverity,437940,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A.almFailToClose.AEShelveDuration,437941,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A.almActuatorFault.BOOLS1,437946,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A.almActuatorFault.BOOLS2,437947,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A.almActuatorFault.AEBOOLS,437948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A.almActuatorFault.INT1,437949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almActuatorFault.INT2,437950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almActuatorFault.AENotify,437951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A.almActuatorFault.AESeverity,437952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A.almActuatorFault.AEShelveDuration,437953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1A.almPLCFault.BOOLS1,437958,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1A.almPLCFault.BOOLS2,437959,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1A.almPLCFault.AEBOOLS,437960,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1A.almPLCFault.INT1,437961,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almPLCFault.INT2,437962,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1A.almPLCFault.AENotify,437963,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1A.almPLCFault.AESeverity,437964,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1A.almPLCFault.AEShelveDuration,437965,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C.almFailToOpen.BOOLS1,438002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C.almFailToOpen.BOOLS2,438003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C.almFailToOpen.AEBOOLS,438004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C.almFailToOpen.INT1,438005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almFailToOpen.INT2,438006,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almFailToOpen.AENotify,438007,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C.almFailToOpen.AESeverity,438008,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C.almFailToOpen.AEShelveDuration,438009,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C.almFailToClose.BOOLS1,438014,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C.almFailToClose.BOOLS2,438015,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C.almFailToClose.AEBOOLS,438016,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C.almFailToClose.INT1,438017,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almFailToClose.INT2,438018,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almFailToClose.AENotify,438019,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C.almFailToClose.AESeverity,438020,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C.almFailToClose.AEShelveDuration,438021,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C.almActuatorFault.BOOLS1,438026,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C.almActuatorFault.BOOLS2,438027,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C.almActuatorFault.AEBOOLS,438028,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C.almActuatorFault.INT1,438029,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almActuatorFault.INT2,438030,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almActuatorFault.AENotify,438031,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C.almActuatorFault.AESeverity,438032,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C.almActuatorFault.AEShelveDuration,438033,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_1C.almPLCFault.BOOLS1,438038,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_1C.almPLCFault.BOOLS2,438039,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_1C.almPLCFault.AEBOOLS,438040,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_1C.almPLCFault.INT1,438041,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almPLCFault.INT2,438042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_1C.almPLCFault.AENotify,438043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_1C.almPLCFault.AESeverity,438044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_1C.almPLCFault.AEShelveDuration,438045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A.almFailToOpen.BOOLS1,438082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A.almFailToOpen.BOOLS2,438083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A.almFailToOpen.AEBOOLS,438084,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A.almFailToOpen.INT1,438085,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almFailToOpen.INT2,438086,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almFailToOpen.AENotify,438087,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A.almFailToOpen.AESeverity,438088,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A.almFailToOpen.AEShelveDuration,438089,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A.almFailToClose.BOOLS1,438094,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A.almFailToClose.BOOLS2,438095,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A.almFailToClose.AEBOOLS,438096,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A.almFailToClose.INT1,438097,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almFailToClose.INT2,438098,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almFailToClose.AENotify,438099,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A.almFailToClose.AESeverity,438100,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A.almFailToClose.AEShelveDuration,438101,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A.almActuatorFault.BOOLS1,438106,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A.almActuatorFault.BOOLS2,438107,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A.almActuatorFault.AEBOOLS,438108,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A.almActuatorFault.INT1,438109,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almActuatorFault.INT2,438110,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almActuatorFault.AENotify,438111,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A.almActuatorFault.AESeverity,438112,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A.almActuatorFault.AEShelveDuration,438113,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2A.almPLCFault.BOOLS1,438118,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2A.almPLCFault.BOOLS2,438119,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2A.almPLCFault.AEBOOLS,438120,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2A.almPLCFault.INT1,438121,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almPLCFault.INT2,438122,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2A.almPLCFault.AENotify,438123,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2A.almPLCFault.AESeverity,438124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2A.almPLCFault.AEShelveDuration,438125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C.almFailToOpen.BOOLS1,438162,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C.almFailToOpen.BOOLS2,438163,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C.almFailToOpen.AEBOOLS,438164,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C.almFailToOpen.INT1,438165,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almFailToOpen.INT2,438166,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almFailToOpen.AENotify,438167,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C.almFailToOpen.AESeverity,438168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C.almFailToOpen.AEShelveDuration,438169,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C.almFailToClose.BOOLS1,438174,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C.almFailToClose.BOOLS2,438175,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C.almFailToClose.AEBOOLS,438176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C.almFailToClose.INT1,438177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almFailToClose.INT2,438178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almFailToClose.AENotify,438179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C.almFailToClose.AESeverity,438180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C.almFailToClose.AEShelveDuration,438181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C.almActuatorFault.BOOLS1,438186,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C.almActuatorFault.BOOLS2,438187,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C.almActuatorFault.AEBOOLS,438188,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C.almActuatorFault.INT1,438189,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almActuatorFault.INT2,438190,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almActuatorFault.AENotify,438191,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C.almActuatorFault.AESeverity,438192,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C.almActuatorFault.AEShelveDuration,438193,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_2C.almPLCFault.BOOLS1,438198,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_2C.almPLCFault.BOOLS2,438199,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_2C.almPLCFault.AEBOOLS,438200,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_2C.almPLCFault.INT1,438201,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almPLCFault.INT2,438202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_2C.almPLCFault.AENotify,438203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_2C.almPLCFault.AESeverity,438204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_2C.almPLCFault.AEShelveDuration,438205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A.almFailToOpen.BOOLS1,438242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A.almFailToOpen.BOOLS2,438243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A.almFailToOpen.AEBOOLS,438244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A.almFailToOpen.INT1,438245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almFailToOpen.INT2,438246,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almFailToOpen.AENotify,438247,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A.almFailToOpen.AESeverity,438248,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A.almFailToOpen.AEShelveDuration,438249,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A.almFailToClose.BOOLS1,438254,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A.almFailToClose.BOOLS2,438255,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A.almFailToClose.AEBOOLS,438256,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A.almFailToClose.INT1,438257,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almFailToClose.INT2,438258,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almFailToClose.AENotify,438259,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A.almFailToClose.AESeverity,438260,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A.almFailToClose.AEShelveDuration,438261,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A.almActuatorFault.BOOLS1,438266,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A.almActuatorFault.BOOLS2,438267,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A.almActuatorFault.AEBOOLS,438268,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A.almActuatorFault.INT1,438269,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almActuatorFault.INT2,438270,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almActuatorFault.AENotify,438271,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A.almActuatorFault.AESeverity,438272,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A.almActuatorFault.AEShelveDuration,438273,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3A.almPLCFault.BOOLS1,438278,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3A.almPLCFault.BOOLS2,438279,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3A.almPLCFault.AEBOOLS,438280,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3A.almPLCFault.INT1,438281,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almPLCFault.INT2,438282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3A.almPLCFault.AENotify,438283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3A.almPLCFault.AESeverity,438284,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3A.almPLCFault.AEShelveDuration,438285,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C.almFailToOpen.BOOLS1,438322,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C.almFailToOpen.BOOLS2,438323,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C.almFailToOpen.AEBOOLS,438324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C.almFailToOpen.INT1,438325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almFailToOpen.INT2,438326,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almFailToOpen.AENotify,438327,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C.almFailToOpen.AESeverity,438328,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C.almFailToOpen.AEShelveDuration,438329,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C.almFailToClose.BOOLS1,438334,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C.almFailToClose.BOOLS2,438335,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C.almFailToClose.AEBOOLS,438336,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C.almFailToClose.INT1,438337,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almFailToClose.INT2,438338,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almFailToClose.AENotify,438339,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C.almFailToClose.AESeverity,438340,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C.almFailToClose.AEShelveDuration,438341,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C.almActuatorFault.BOOLS1,438346,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C.almActuatorFault.BOOLS2,438347,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C.almActuatorFault.AEBOOLS,438348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C.almActuatorFault.INT1,438349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almActuatorFault.INT2,438350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almActuatorFault.AENotify,438351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C.almActuatorFault.AESeverity,438352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C.almActuatorFault.AEShelveDuration,438353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3C.almPLCFault.BOOLS1,438358,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3C.almPLCFault.BOOLS2,438359,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3C.almPLCFault.AEBOOLS,438360,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3C.almPLCFault.INT1,438361,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almPLCFault.INT2,438362,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3C.almPLCFault.AENotify,438363,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3C.almPLCFault.AESeverity,438364,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3C.almPLCFault.AEShelveDuration,438365,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D.almFailToOpen.BOOLS1,438402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D.almFailToOpen.BOOLS2,438403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D.almFailToOpen.AEBOOLS,438404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D.almFailToOpen.INT1,438405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almFailToOpen.INT2,438406,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almFailToOpen.AENotify,438407,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D.almFailToOpen.AESeverity,438408,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D.almFailToOpen.AEShelveDuration,438409,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D.almFailToClose.BOOLS1,438414,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D.almFailToClose.BOOLS2,438415,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D.almFailToClose.AEBOOLS,438416,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D.almFailToClose.INT1,438417,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almFailToClose.INT2,438418,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almFailToClose.AENotify,438419,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D.almFailToClose.AESeverity,438420,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D.almFailToClose.AEShelveDuration,438421,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D.almActuatorFault.BOOLS1,438426,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D.almActuatorFault.BOOLS2,438427,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D.almActuatorFault.AEBOOLS,438428,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D.almActuatorFault.INT1,438429,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almActuatorFault.INT2,438430,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almActuatorFault.AENotify,438431,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D.almActuatorFault.AESeverity,438432,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D.almActuatorFault.AEShelveDuration,438433,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_3D.almPLCFault.BOOLS1,438438,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_3D.almPLCFault.BOOLS2,438439,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_3D.almPLCFault.AEBOOLS,438440,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_3D.almPLCFault.INT1,438441,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almPLCFault.INT2,438442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_3D.almPLCFault.AENotify,438443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_3D.almPLCFault.AESeverity,438444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_3D.almPLCFault.AEShelveDuration,438445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A.almFailToOpen.BOOLS1,438482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A.almFailToOpen.BOOLS2,438483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A.almFailToOpen.AEBOOLS,438484,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A.almFailToOpen.INT1,438485,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almFailToOpen.INT2,438486,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almFailToOpen.AENotify,438487,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A.almFailToOpen.AESeverity,438488,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A.almFailToOpen.AEShelveDuration,438489,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A.almFailToClose.BOOLS1,438494,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A.almFailToClose.BOOLS2,438495,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A.almFailToClose.AEBOOLS,438496,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A.almFailToClose.INT1,438497,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almFailToClose.INT2,438498,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almFailToClose.AENotify,438499,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A.almFailToClose.AESeverity,438500,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A.almFailToClose.AEShelveDuration,438501,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A.almActuatorFault.BOOLS1,438506,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A.almActuatorFault.BOOLS2,438507,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A.almActuatorFault.AEBOOLS,438508,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A.almActuatorFault.INT1,438509,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almActuatorFault.INT2,438510,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almActuatorFault.AENotify,438511,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A.almActuatorFault.AESeverity,438512,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A.almActuatorFault.AEShelveDuration,438513,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4A.almPLCFault.BOOLS1,438518,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4A.almPLCFault.BOOLS2,438519,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4A.almPLCFault.AEBOOLS,438520,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4A.almPLCFault.INT1,438521,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almPLCFault.INT2,438522,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4A.almPLCFault.AENotify,438523,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4A.almPLCFault.AESeverity,438524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4A.almPLCFault.AEShelveDuration,438525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C.almFailToOpen.BOOLS1,438562,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C.almFailToOpen.BOOLS2,438563,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C.almFailToOpen.AEBOOLS,438564,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C.almFailToOpen.INT1,438565,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almFailToOpen.INT2,438566,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almFailToOpen.AENotify,438567,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C.almFailToOpen.AESeverity,438568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C.almFailToOpen.AEShelveDuration,438569,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C.almFailToClose.BOOLS1,438574,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C.almFailToClose.BOOLS2,438575,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C.almFailToClose.AEBOOLS,438576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C.almFailToClose.INT1,438577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almFailToClose.INT2,438578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almFailToClose.AENotify,438579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C.almFailToClose.AESeverity,438580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C.almFailToClose.AEShelveDuration,438581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C.almActuatorFault.BOOLS1,438586,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C.almActuatorFault.BOOLS2,438587,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C.almActuatorFault.AEBOOLS,438588,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C.almActuatorFault.INT1,438589,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almActuatorFault.INT2,438590,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almActuatorFault.AENotify,438591,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C.almActuatorFault.AESeverity,438592,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C.almActuatorFault.AEShelveDuration,438593,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4C.almPLCFault.BOOLS1,438598,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4C.almPLCFault.BOOLS2,438599,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4C.almPLCFault.AEBOOLS,438600,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4C.almPLCFault.INT1,438601,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almPLCFault.INT2,438602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4C.almPLCFault.AENotify,438603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4C.almPLCFault.AESeverity,438604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4C.almPLCFault.AEShelveDuration,438605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D.almFailToOpen.BOOLS1,438642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D.almFailToOpen.BOOLS2,438643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D.almFailToOpen.AEBOOLS,438644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D.almFailToOpen.INT1,438645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almFailToOpen.INT2,438646,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almFailToOpen.AENotify,438647,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D.almFailToOpen.AESeverity,438648,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D.almFailToOpen.AEShelveDuration,438649,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D.almFailToClose.BOOLS1,438654,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D.almFailToClose.BOOLS2,438655,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D.almFailToClose.AEBOOLS,438656,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D.almFailToClose.INT1,438657,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almFailToClose.INT2,438658,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almFailToClose.AENotify,438659,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D.almFailToClose.AESeverity,438660,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D.almFailToClose.AEShelveDuration,438661,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D.almActuatorFault.BOOLS1,438666,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D.almActuatorFault.BOOLS2,438667,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D.almActuatorFault.AEBOOLS,438668,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D.almActuatorFault.INT1,438669,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almActuatorFault.INT2,438670,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almActuatorFault.AENotify,438671,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D.almActuatorFault.AESeverity,438672,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D.almActuatorFault.AEShelveDuration,438673,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_4D.almPLCFault.BOOLS1,438678,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_4D.almPLCFault.BOOLS2,438679,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_4D.almPLCFault.AEBOOLS,438680,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_4D.almPLCFault.INT1,438681,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almPLCFault.INT2,438682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_4D.almPLCFault.AENotify,438683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_4D.almPLCFault.AESeverity,438684,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_4D.almPLCFault.AEShelveDuration,438685,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A.almFailToOpen.BOOLS1,438722,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A.almFailToOpen.BOOLS2,438723,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A.almFailToOpen.AEBOOLS,438724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A.almFailToOpen.INT1,438725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almFailToOpen.INT2,438726,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almFailToOpen.AENotify,438727,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A.almFailToOpen.AESeverity,438728,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A.almFailToOpen.AEShelveDuration,438729,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A.almFailToClose.BOOLS1,438734,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A.almFailToClose.BOOLS2,438735,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A.almFailToClose.AEBOOLS,438736,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A.almFailToClose.INT1,438737,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almFailToClose.INT2,438738,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almFailToClose.AENotify,438739,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A.almFailToClose.AESeverity,438740,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A.almFailToClose.AEShelveDuration,438741,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A.almActuatorFault.BOOLS1,438746,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A.almActuatorFault.BOOLS2,438747,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A.almActuatorFault.AEBOOLS,438748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A.almActuatorFault.INT1,438749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almActuatorFault.INT2,438750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almActuatorFault.AENotify,438751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A.almActuatorFault.AESeverity,438752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A.almActuatorFault.AEShelveDuration,438753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5A.almPLCFault.BOOLS1,438758,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5A.almPLCFault.BOOLS2,438759,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5A.almPLCFault.AEBOOLS,438760,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5A.almPLCFault.INT1,438761,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almPLCFault.INT2,438762,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5A.almPLCFault.AENotify,438763,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5A.almPLCFault.AESeverity,438764,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5A.almPLCFault.AEShelveDuration,438765,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C.almFailToOpen.BOOLS1,438802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C.almFailToOpen.BOOLS2,438803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C.almFailToOpen.AEBOOLS,438804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C.almFailToOpen.INT1,438805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almFailToOpen.INT2,438806,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almFailToOpen.AENotify,438807,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C.almFailToOpen.AESeverity,438808,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C.almFailToOpen.AEShelveDuration,438809,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C.almFailToClose.BOOLS1,438814,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C.almFailToClose.BOOLS2,438815,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C.almFailToClose.AEBOOLS,438816,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C.almFailToClose.INT1,438817,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almFailToClose.INT2,438818,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almFailToClose.AENotify,438819,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C.almFailToClose.AESeverity,438820,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C.almFailToClose.AEShelveDuration,438821,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C.almActuatorFault.BOOLS1,438826,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C.almActuatorFault.BOOLS2,438827,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C.almActuatorFault.AEBOOLS,438828,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C.almActuatorFault.INT1,438829,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almActuatorFault.INT2,438830,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almActuatorFault.AENotify,438831,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C.almActuatorFault.AESeverity,438832,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C.almActuatorFault.AEShelveDuration,438833,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5C.almPLCFault.BOOLS1,438838,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5C.almPLCFault.BOOLS2,438839,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5C.almPLCFault.AEBOOLS,438840,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5C.almPLCFault.INT1,438841,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almPLCFault.INT2,438842,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5C.almPLCFault.AENotify,438843,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5C.almPLCFault.AESeverity,438844,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5C.almPLCFault.AEShelveDuration,438845,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D.almFailToOpen.BOOLS1,438882,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D.almFailToOpen.BOOLS2,438883,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D.almFailToOpen.AEBOOLS,438884,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D.almFailToOpen.INT1,438885,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almFailToOpen.INT2,438886,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almFailToOpen.AENotify,438887,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D.almFailToOpen.AESeverity,438888,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D.almFailToOpen.AEShelveDuration,438889,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D.almFailToClose.BOOLS1,438894,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D.almFailToClose.BOOLS2,438895,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D.almFailToClose.AEBOOLS,438896,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D.almFailToClose.INT1,438897,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almFailToClose.INT2,438898,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almFailToClose.AENotify,438899,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D.almFailToClose.AESeverity,438900,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D.almFailToClose.AEShelveDuration,438901,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D.almActuatorFault.BOOLS1,438906,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D.almActuatorFault.BOOLS2,438907,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D.almActuatorFault.AEBOOLS,438908,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D.almActuatorFault.INT1,438909,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almActuatorFault.INT2,438910,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almActuatorFault.AENotify,438911,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D.almActuatorFault.AESeverity,438912,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D.almActuatorFault.AEShelveDuration,438913,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_5D.almPLCFault.BOOLS1,438918,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_5D.almPLCFault.BOOLS2,438919,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_5D.almPLCFault.AEBOOLS,438920,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_5D.almPLCFault.INT1,438921,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almPLCFault.INT2,438922,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_5D.almPLCFault.AENotify,438923,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_5D.almPLCFault.AESeverity,438924,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_5D.almPLCFault.AEShelveDuration,438925,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A.almFailToOpen.BOOLS1,438962,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A.almFailToOpen.BOOLS2,438963,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A.almFailToOpen.AEBOOLS,438964,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A.almFailToOpen.INT1,438965,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almFailToOpen.INT2,438966,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almFailToOpen.AENotify,438967,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A.almFailToOpen.AESeverity,438968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A.almFailToOpen.AEShelveDuration,438969,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A.almFailToClose.BOOLS1,438974,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A.almFailToClose.BOOLS2,438975,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A.almFailToClose.AEBOOLS,438976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A.almFailToClose.INT1,438977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almFailToClose.INT2,438978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almFailToClose.AENotify,438979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A.almFailToClose.AESeverity,438980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A.almFailToClose.AEShelveDuration,438981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A.almActuatorFault.BOOLS1,438986,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A.almActuatorFault.BOOLS2,438987,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A.almActuatorFault.AEBOOLS,438988,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A.almActuatorFault.INT1,438989,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almActuatorFault.INT2,438990,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almActuatorFault.AENotify,438991,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A.almActuatorFault.AESeverity,438992,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A.almActuatorFault.AEShelveDuration,438993,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6A.almPLCFault.BOOLS1,438998,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6A.almPLCFault.BOOLS2,438999,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6A.almPLCFault.AEBOOLS,439000,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6A.almPLCFault.INT1,439001,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almPLCFault.INT2,439002,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6A.almPLCFault.AENotify,439003,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6A.almPLCFault.AESeverity,439004,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6A.almPLCFault.AEShelveDuration,439005,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C.almFailToOpen.BOOLS1,439042,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C.almFailToOpen.BOOLS2,439043,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C.almFailToOpen.AEBOOLS,439044,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C.almFailToOpen.INT1,439045,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almFailToOpen.INT2,439046,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almFailToOpen.AENotify,439047,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C.almFailToOpen.AESeverity,439048,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C.almFailToOpen.AEShelveDuration,439049,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C.almFailToClose.BOOLS1,439054,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C.almFailToClose.BOOLS2,439055,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C.almFailToClose.AEBOOLS,439056,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C.almFailToClose.INT1,439057,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almFailToClose.INT2,439058,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almFailToClose.AENotify,439059,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C.almFailToClose.AESeverity,439060,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C.almFailToClose.AEShelveDuration,439061,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C.almActuatorFault.BOOLS1,439066,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C.almActuatorFault.BOOLS2,439067,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C.almActuatorFault.AEBOOLS,439068,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C.almActuatorFault.INT1,439069,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almActuatorFault.INT2,439070,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almActuatorFault.AENotify,439071,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C.almActuatorFault.AESeverity,439072,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C.almActuatorFault.AEShelveDuration,439073,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6C.almPLCFault.BOOLS1,439078,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6C.almPLCFault.BOOLS2,439079,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6C.almPLCFault.AEBOOLS,439080,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6C.almPLCFault.INT1,439081,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almPLCFault.INT2,439082,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6C.almPLCFault.AENotify,439083,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6C.almPLCFault.AESeverity,439084,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6C.almPLCFault.AEShelveDuration,439085,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D.almFailToOpen.BOOLS1,439122,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D.almFailToOpen.BOOLS2,439123,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D.almFailToOpen.AEBOOLS,439124,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D.almFailToOpen.INT1,439125,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almFailToOpen.INT2,439126,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almFailToOpen.AENotify,439127,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D.almFailToOpen.AESeverity,439128,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D.almFailToOpen.AEShelveDuration,439129,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D.almFailToClose.BOOLS1,439134,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D.almFailToClose.BOOLS2,439135,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D.almFailToClose.AEBOOLS,439136,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D.almFailToClose.INT1,439137,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almFailToClose.INT2,439138,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almFailToClose.AENotify,439139,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D.almFailToClose.AESeverity,439140,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D.almFailToClose.AEShelveDuration,439141,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D.almActuatorFault.BOOLS1,439146,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D.almActuatorFault.BOOLS2,439147,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D.almActuatorFault.AEBOOLS,439148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D.almActuatorFault.INT1,439149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almActuatorFault.INT2,439150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almActuatorFault.AENotify,439151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D.almActuatorFault.AESeverity,439152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D.almActuatorFault.AEShelveDuration,439153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_6D.almPLCFault.BOOLS1,439158,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_6D.almPLCFault.BOOLS2,439159,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_6D.almPLCFault.AEBOOLS,439160,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_6D.almPLCFault.INT1,439161,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almPLCFault.INT2,439162,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_6D.almPLCFault.AENotify,439163,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_6D.almPLCFault.AESeverity,439164,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_6D.almPLCFault.AEShelveDuration,439165,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A.almFailToOpen.BOOLS1,439202,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A.almFailToOpen.BOOLS2,439203,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A.almFailToOpen.AEBOOLS,439204,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A.almFailToOpen.INT1,439205,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almFailToOpen.INT2,439206,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almFailToOpen.AENotify,439207,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A.almFailToOpen.AESeverity,439208,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A.almFailToOpen.AEShelveDuration,439209,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A.almFailToClose.BOOLS1,439214,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A.almFailToClose.BOOLS2,439215,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A.almFailToClose.AEBOOLS,439216,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A.almFailToClose.INT1,439217,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almFailToClose.INT2,439218,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almFailToClose.AENotify,439219,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A.almFailToClose.AESeverity,439220,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A.almFailToClose.AEShelveDuration,439221,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A.almActuatorFault.BOOLS1,439226,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A.almActuatorFault.BOOLS2,439227,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A.almActuatorFault.AEBOOLS,439228,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A.almActuatorFault.INT1,439229,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almActuatorFault.INT2,439230,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almActuatorFault.AENotify,439231,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A.almActuatorFault.AESeverity,439232,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A.almActuatorFault.AEShelveDuration,439233,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7A.almPLCFault.BOOLS1,439238,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7A.almPLCFault.BOOLS2,439239,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7A.almPLCFault.AEBOOLS,439240,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7A.almPLCFault.INT1,439241,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almPLCFault.INT2,439242,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7A.almPLCFault.AENotify,439243,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7A.almPLCFault.AESeverity,439244,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7A.almPLCFault.AEShelveDuration,439245,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C.almFailToOpen.BOOLS1,439282,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C.almFailToOpen.BOOLS2,439283,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C.almFailToOpen.AEBOOLS,439284,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C.almFailToOpen.INT1,439285,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almFailToOpen.INT2,439286,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almFailToOpen.AENotify,439287,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C.almFailToOpen.AESeverity,439288,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C.almFailToOpen.AEShelveDuration,439289,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C.almFailToClose.BOOLS1,439294,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C.almFailToClose.BOOLS2,439295,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C.almFailToClose.AEBOOLS,439296,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C.almFailToClose.INT1,439297,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almFailToClose.INT2,439298,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almFailToClose.AENotify,439299,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C.almFailToClose.AESeverity,439300,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C.almFailToClose.AEShelveDuration,439301,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C.almActuatorFault.BOOLS1,439306,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C.almActuatorFault.BOOLS2,439307,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C.almActuatorFault.AEBOOLS,439308,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C.almActuatorFault.INT1,439309,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almActuatorFault.INT2,439310,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almActuatorFault.AENotify,439311,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C.almActuatorFault.AESeverity,439312,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C.almActuatorFault.AEShelveDuration,439313,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7C.almPLCFault.BOOLS1,439318,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7C.almPLCFault.BOOLS2,439319,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7C.almPLCFault.AEBOOLS,439320,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7C.almPLCFault.INT1,439321,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almPLCFault.INT2,439322,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7C.almPLCFault.AENotify,439323,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7C.almPLCFault.AESeverity,439324,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7C.almPLCFault.AEShelveDuration,439325,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D.almFailToOpen.BOOLS1,439362,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D.almFailToOpen.BOOLS2,439363,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D.almFailToOpen.AEBOOLS,439364,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D.almFailToOpen.INT1,439365,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almFailToOpen.INT2,439366,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almFailToOpen.AENotify,439367,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D.almFailToOpen.AESeverity,439368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D.almFailToOpen.AEShelveDuration,439369,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D.almFailToClose.BOOLS1,439374,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D.almFailToClose.BOOLS2,439375,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D.almFailToClose.AEBOOLS,439376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D.almFailToClose.INT1,439377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almFailToClose.INT2,439378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almFailToClose.AENotify,439379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D.almFailToClose.AESeverity,439380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D.almFailToClose.AEShelveDuration,439381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D.almActuatorFault.BOOLS1,439386,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D.almActuatorFault.BOOLS2,439387,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D.almActuatorFault.AEBOOLS,439388,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D.almActuatorFault.INT1,439389,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almActuatorFault.INT2,439390,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almActuatorFault.AENotify,439391,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D.almActuatorFault.AESeverity,439392,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D.almActuatorFault.AEShelveDuration,439393,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_7D.almPLCFault.BOOLS1,439398,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_7D.almPLCFault.BOOLS2,439399,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_7D.almPLCFault.AEBOOLS,439400,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_7D.almPLCFault.INT1,439401,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almPLCFault.INT2,439402,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_7D.almPLCFault.AENotify,439403,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_7D.almPLCFault.AESeverity,439404,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_7D.almPLCFault.AEShelveDuration,439405,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A.almFailToOpen.BOOLS1,439442,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A.almFailToOpen.BOOLS2,439443,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A.almFailToOpen.AEBOOLS,439444,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A.almFailToOpen.INT1,439445,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almFailToOpen.INT2,439446,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almFailToOpen.AENotify,439447,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A.almFailToOpen.AESeverity,439448,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A.almFailToOpen.AEShelveDuration,439449,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A.almFailToClose.BOOLS1,439454,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A.almFailToClose.BOOLS2,439455,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A.almFailToClose.AEBOOLS,439456,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A.almFailToClose.INT1,439457,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almFailToClose.INT2,439458,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almFailToClose.AENotify,439459,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A.almFailToClose.AESeverity,439460,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A.almFailToClose.AEShelveDuration,439461,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A.almActuatorFault.BOOLS1,439466,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A.almActuatorFault.BOOLS2,439467,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A.almActuatorFault.AEBOOLS,439468,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A.almActuatorFault.INT1,439469,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almActuatorFault.INT2,439470,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almActuatorFault.AENotify,439471,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A.almActuatorFault.AESeverity,439472,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A.almActuatorFault.AEShelveDuration,439473,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8A.almPLCFault.BOOLS1,439478,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8A.almPLCFault.BOOLS2,439479,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8A.almPLCFault.AEBOOLS,439480,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8A.almPLCFault.INT1,439481,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almPLCFault.INT2,439482,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8A.almPLCFault.AENotify,439483,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8A.almPLCFault.AESeverity,439484,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8A.almPLCFault.AEShelveDuration,439485,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C.almFailToOpen.BOOLS1,439522,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C.almFailToOpen.BOOLS2,439523,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C.almFailToOpen.AEBOOLS,439524,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C.almFailToOpen.INT1,439525,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almFailToOpen.INT2,439526,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almFailToOpen.AENotify,439527,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C.almFailToOpen.AESeverity,439528,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C.almFailToOpen.AEShelveDuration,439529,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C.almFailToClose.BOOLS1,439534,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C.almFailToClose.BOOLS2,439535,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C.almFailToClose.AEBOOLS,439536,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C.almFailToClose.INT1,439537,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almFailToClose.INT2,439538,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almFailToClose.AENotify,439539,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C.almFailToClose.AESeverity,439540,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C.almFailToClose.AEShelveDuration,439541,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C.almActuatorFault.BOOLS1,439546,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C.almActuatorFault.BOOLS2,439547,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C.almActuatorFault.AEBOOLS,439548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C.almActuatorFault.INT1,439549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almActuatorFault.INT2,439550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almActuatorFault.AENotify,439551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C.almActuatorFault.AESeverity,439552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C.almActuatorFault.AEShelveDuration,439553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8C.almPLCFault.BOOLS1,439558,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8C.almPLCFault.BOOLS2,439559,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8C.almPLCFault.AEBOOLS,439560,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8C.almPLCFault.INT1,439561,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almPLCFault.INT2,439562,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8C.almPLCFault.AENotify,439563,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8C.almPLCFault.AESeverity,439564,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8C.almPLCFault.AEShelveDuration,439565,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D.almFailToOpen.BOOLS1,439602,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D.almFailToOpen.BOOLS2,439603,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D.almFailToOpen.AEBOOLS,439604,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D.almFailToOpen.INT1,439605,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almFailToOpen.INT2,439606,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almFailToOpen.AENotify,439607,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D.almFailToOpen.AESeverity,439608,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D.almFailToOpen.AEShelveDuration,439609,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D.almFailToClose.BOOLS1,439614,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D.almFailToClose.BOOLS2,439615,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D.almFailToClose.AEBOOLS,439616,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D.almFailToClose.INT1,439617,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almFailToClose.INT2,439618,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almFailToClose.AENotify,439619,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D.almFailToClose.AESeverity,439620,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D.almFailToClose.AEShelveDuration,439621,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D.almActuatorFault.BOOLS1,439626,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D.almActuatorFault.BOOLS2,439627,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D.almActuatorFault.AEBOOLS,439628,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D.almActuatorFault.INT1,439629,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almActuatorFault.INT2,439630,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almActuatorFault.AENotify,439631,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D.almActuatorFault.AESeverity,439632,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D.almActuatorFault.AEShelveDuration,439633,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_8D.almPLCFault.BOOLS1,439638,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_8D.almPLCFault.BOOLS2,439639,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_8D.almPLCFault.AEBOOLS,439640,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_8D.almPLCFault.INT1,439641,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almPLCFault.INT2,439642,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_8D.almPLCFault.AENotify,439643,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_8D.almPLCFault.AESeverity,439644,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_8D.almPLCFault.AEShelveDuration,439645,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A.almFailToOpen.BOOLS1,439682,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A.almFailToOpen.BOOLS2,439683,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A.almFailToOpen.AEBOOLS,439684,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A.almFailToOpen.INT1,439685,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almFailToOpen.INT2,439686,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almFailToOpen.AENotify,439687,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A.almFailToOpen.AESeverity,439688,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A.almFailToOpen.AEShelveDuration,439689,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A.almFailToClose.BOOLS1,439694,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A.almFailToClose.BOOLS2,439695,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A.almFailToClose.AEBOOLS,439696,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A.almFailToClose.INT1,439697,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almFailToClose.INT2,439698,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almFailToClose.AENotify,439699,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A.almFailToClose.AESeverity,439700,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A.almFailToClose.AEShelveDuration,439701,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A.almActuatorFault.BOOLS1,439706,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A.almActuatorFault.BOOLS2,439707,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A.almActuatorFault.AEBOOLS,439708,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A.almActuatorFault.INT1,439709,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almActuatorFault.INT2,439710,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almActuatorFault.AENotify,439711,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A.almActuatorFault.AESeverity,439712,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A.almActuatorFault.AEShelveDuration,439713,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9A.almPLCFault.BOOLS1,439718,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9A.almPLCFault.BOOLS2,439719,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9A.almPLCFault.AEBOOLS,439720,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9A.almPLCFault.INT1,439721,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almPLCFault.INT2,439722,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9A.almPLCFault.AENotify,439723,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9A.almPLCFault.AESeverity,439724,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9A.almPLCFault.AEShelveDuration,439725,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C.almFailToOpen.BOOLS1,439762,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C.almFailToOpen.BOOLS2,439763,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C.almFailToOpen.AEBOOLS,439764,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C.almFailToOpen.INT1,439765,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almFailToOpen.INT2,439766,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almFailToOpen.AENotify,439767,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C.almFailToOpen.AESeverity,439768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C.almFailToOpen.AEShelveDuration,439769,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C.almFailToClose.BOOLS1,439774,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C.almFailToClose.BOOLS2,439775,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C.almFailToClose.AEBOOLS,439776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C.almFailToClose.INT1,439777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almFailToClose.INT2,439778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almFailToClose.AENotify,439779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C.almFailToClose.AESeverity,439780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C.almFailToClose.AEShelveDuration,439781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C.almActuatorFault.BOOLS1,439786,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C.almActuatorFault.BOOLS2,439787,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C.almActuatorFault.AEBOOLS,439788,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C.almActuatorFault.INT1,439789,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almActuatorFault.INT2,439790,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almActuatorFault.AENotify,439791,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C.almActuatorFault.AESeverity,439792,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C.almActuatorFault.AEShelveDuration,439793,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0103_9C.almPLCFault.BOOLS1,439798,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0103_9C.almPLCFault.BOOLS2,439799,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0103_9C.almPLCFault.AEBOOLS,439800,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0103_9C.almPLCFault.INT1,439801,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almPLCFault.INT2,439802,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0103_9C.almPLCFault.AENotify,439803,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0103_9C.almPLCFault.AESeverity,439804,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0103_9C.almPLCFault.AEShelveDuration,439805,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A.almFailToOpen.BOOLS1,439842,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A.almFailToOpen.BOOLS2,439843,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A.almFailToOpen.AEBOOLS,439844,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A.almFailToOpen.INT1,439845,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almFailToOpen.INT2,439846,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almFailToOpen.AENotify,439847,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A.almFailToOpen.AESeverity,439848,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A.almFailToOpen.AEShelveDuration,439849,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A.almFailToClose.BOOLS1,439854,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A.almFailToClose.BOOLS2,439855,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A.almFailToClose.AEBOOLS,439856,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A.almFailToClose.INT1,439857,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almFailToClose.INT2,439858,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almFailToClose.AENotify,439859,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A.almFailToClose.AESeverity,439860,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A.almFailToClose.AEShelveDuration,439861,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A.almActuatorFault.BOOLS1,439866,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A.almActuatorFault.BOOLS2,439867,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A.almActuatorFault.AEBOOLS,439868,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A.almActuatorFault.INT1,439869,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almActuatorFault.INT2,439870,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almActuatorFault.AENotify,439871,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A.almActuatorFault.AESeverity,439872,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A.almActuatorFault.AEShelveDuration,439873,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2A.almPLCFault.BOOLS1,439878,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2A.almPLCFault.BOOLS2,439879,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2A.almPLCFault.AEBOOLS,439880,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2A.almPLCFault.INT1,439881,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almPLCFault.INT2,439882,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2A.almPLCFault.AENotify,439883,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2A.almPLCFault.AESeverity,439884,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2A.almPLCFault.AEShelveDuration,439885,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B.almFailToOpen.BOOLS1,439922,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B.almFailToOpen.BOOLS2,439923,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B.almFailToOpen.AEBOOLS,439924,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B.almFailToOpen.INT1,439925,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almFailToOpen.INT2,439926,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almFailToOpen.AENotify,439927,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B.almFailToOpen.AESeverity,439928,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B.almFailToOpen.AEShelveDuration,439929,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B.almFailToClose.BOOLS1,439934,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B.almFailToClose.BOOLS2,439935,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B.almFailToClose.AEBOOLS,439936,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B.almFailToClose.INT1,439937,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almFailToClose.INT2,439938,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almFailToClose.AENotify,439939,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B.almFailToClose.AESeverity,439940,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B.almFailToClose.AEShelveDuration,439941,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B.almActuatorFault.BOOLS1,439946,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B.almActuatorFault.BOOLS2,439947,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B.almActuatorFault.AEBOOLS,439948,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B.almActuatorFault.INT1,439949,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almActuatorFault.INT2,439950,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almActuatorFault.AENotify,439951,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B.almActuatorFault.AESeverity,439952,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B.almActuatorFault.AEShelveDuration,439953,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2B.almPLCFault.BOOLS1,439958,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2B.almPLCFault.BOOLS2,439959,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2B.almPLCFault.AEBOOLS,439960,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2B.almPLCFault.INT1,439961,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almPLCFault.INT2,439962,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2B.almPLCFault.AENotify,439963,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2B.almPLCFault.AESeverity,439964,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2B.almPLCFault.AEShelveDuration,439965,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C.almFailToOpen.BOOLS1,440002,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C.almFailToOpen.BOOLS2,440003,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C.almFailToOpen.AEBOOLS,440004,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C.almFailToOpen.INT1,440005,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almFailToOpen.INT2,440006,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almFailToOpen.AENotify,440007,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C.almFailToOpen.AESeverity,440008,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C.almFailToOpen.AEShelveDuration,440009,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C.almFailToClose.BOOLS1,440014,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C.almFailToClose.BOOLS2,440015,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C.almFailToClose.AEBOOLS,440016,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C.almFailToClose.INT1,440017,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almFailToClose.INT2,440018,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almFailToClose.AENotify,440019,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C.almFailToClose.AESeverity,440020,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C.almFailToClose.AEShelveDuration,440021,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C.almActuatorFault.BOOLS1,440026,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C.almActuatorFault.BOOLS2,440027,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C.almActuatorFault.AEBOOLS,440028,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C.almActuatorFault.INT1,440029,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almActuatorFault.INT2,440030,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almActuatorFault.AENotify,440031,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C.almActuatorFault.AESeverity,440032,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C.almActuatorFault.AEShelveDuration,440033,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2C.almPLCFault.BOOLS1,440038,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2C.almPLCFault.BOOLS2,440039,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2C.almPLCFault.AEBOOLS,440040,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2C.almPLCFault.INT1,440041,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almPLCFault.INT2,440042,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2C.almPLCFault.AENotify,440043,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2C.almPLCFault.AESeverity,440044,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2C.almPLCFault.AEShelveDuration,440045,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D.almFailToOpen.BOOLS1,440082,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D.almFailToOpen.BOOLS2,440083,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D.almFailToOpen.AEBOOLS,440084,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D.almFailToOpen.INT1,440085,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almFailToOpen.INT2,440086,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almFailToOpen.AENotify,440087,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D.almFailToOpen.AESeverity,440088,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D.almFailToOpen.AEShelveDuration,440089,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D.almFailToClose.BOOLS1,440094,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D.almFailToClose.BOOLS2,440095,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D.almFailToClose.AEBOOLS,440096,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D.almFailToClose.INT1,440097,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almFailToClose.INT2,440098,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almFailToClose.AENotify,440099,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D.almFailToClose.AESeverity,440100,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D.almFailToClose.AEShelveDuration,440101,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D.almActuatorFault.BOOLS1,440106,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D.almActuatorFault.BOOLS2,440107,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D.almActuatorFault.AEBOOLS,440108,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D.almActuatorFault.INT1,440109,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almActuatorFault.INT2,440110,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almActuatorFault.AENotify,440111,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D.almActuatorFault.AESeverity,440112,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D.almActuatorFault.AEShelveDuration,440113,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FV_0113_2D.almPLCFault.BOOLS1,440118,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FV_0113_2D.almPLCFault.BOOLS2,440119,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FV_0113_2D.almPLCFault.AEBOOLS,440120,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FV_0113_2D.almPLCFault.INT1,440121,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almPLCFault.INT2,440122,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FV_0113_2D.almPLCFault.AENotify,440123,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FV_0113_2D.almPLCFault.AESeverity,440124,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FV_0113_2D.almPLCFault.AEShelveDuration,440125,Short,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almBrokenLoop.BOOLS1,440160,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almBrokenLoop.BOOLS2,440161,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almBrokenLoop.AEBOOLS,440162,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almBrokenLoop.INT1,440163,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almBrokenLoop.INT2,440164,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almBrokenLoop.AENotify,440165,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almBrokenLoop.AESeverity,440166,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almBrokenLoop.AEShelveDuration,440167,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almUnderRange.BOOLS1,440172,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almUnderRange.BOOLS2,440173,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almUnderRange.AEBOOLS,440174,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almUnderRange.INT1,440175,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almUnderRange.INT2,440176,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almUnderRange.AENotify,440177,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almUnderRange.AESeverity,440178,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almUnderRange.AEShelveDuration,440179,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almOverRange.BOOLS1,440184,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almOverRange.BOOLS2,440185,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almOverRange.AEBOOLS,440186,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almOverRange.INT1,440187,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almOverRange.INT2,440188,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almOverRange.AENotify,440189,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almOverRange.AESeverity,440190,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almOverRange.AEShelveDuration,440191,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almPositionFailure.BOOLS1,440196,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almPositionFailure.BOOLS2,440197,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almPositionFailure.AEBOOLS,440198,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almPositionFailure.INT1,440199,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almPositionFailure.INT2,440200,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almPositionFailure.AENotify,440201,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almPositionFailure.AESeverity,440202,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almPositionFailure.AEShelveDuration,440203,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almPLCFault.BOOLS1,440208,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almPLCFault.BOOLS2,440209,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almPLCFault.AEBOOLS,440210,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almPLCFault.INT1,440211,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almPLCFault.INT2,440212,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almPLCFault.AENotify,440213,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almPLCFault.AESeverity,440214,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almPLCFault.AEShelveDuration,440215,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2A.almValveFailure.BOOLS1,440220,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2A.almValveFailure.BOOLS2,440221,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2A.almValveFailure.AEBOOLS,440222,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2A.almValveFailure.INT1,440223,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almValveFailure.INT2,440224,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2A.almValveFailure.AENotify,440225,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2A.almValveFailure.AESeverity,440226,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2A.almValveFailure.AEShelveDuration,440227,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almBrokenLoop.BOOLS1,440270,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almBrokenLoop.BOOLS2,440271,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almBrokenLoop.AEBOOLS,440272,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almBrokenLoop.INT1,440273,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almBrokenLoop.INT2,440274,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almBrokenLoop.AENotify,440275,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almBrokenLoop.AESeverity,440276,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almBrokenLoop.AEShelveDuration,440277,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almUnderRange.BOOLS1,440282,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almUnderRange.BOOLS2,440283,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almUnderRange.AEBOOLS,440284,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almUnderRange.INT1,440285,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almUnderRange.INT2,440286,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almUnderRange.AENotify,440287,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almUnderRange.AESeverity,440288,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almUnderRange.AEShelveDuration,440289,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almOverRange.BOOLS1,440294,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almOverRange.BOOLS2,440295,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almOverRange.AEBOOLS,440296,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almOverRange.INT1,440297,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almOverRange.INT2,440298,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almOverRange.AENotify,440299,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almOverRange.AESeverity,440300,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almOverRange.AEShelveDuration,440301,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almPositionFailure.BOOLS1,440306,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almPositionFailure.BOOLS2,440307,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almPositionFailure.AEBOOLS,440308,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almPositionFailure.INT1,440309,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almPositionFailure.INT2,440310,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almPositionFailure.AENotify,440311,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almPositionFailure.AESeverity,440312,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almPositionFailure.AEShelveDuration,440313,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almPLCFault.BOOLS1,440318,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almPLCFault.BOOLS2,440319,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almPLCFault.AEBOOLS,440320,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almPLCFault.INT1,440321,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almPLCFault.INT2,440322,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almPLCFault.AENotify,440323,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almPLCFault.AESeverity,440324,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almPLCFault.AEShelveDuration,440325,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_FCV_0113_2B.almValveFailure.BOOLS1,440330,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: First Integer of packed Bits" WA3252_FCV_0113_2B.almValveFailure.BOOLS2,440331,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Second Integer of packed Bits" WA3252_FCV_0113_2B.almValveFailure.AEBOOLS,440332,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Bools" WA3252_FCV_0113_2B.almValveFailure.INT1,440333,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almValveFailure.INT2,440334,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Spare Int" WA3252_FCV_0113_2B.almValveFailure.AENotify,440335,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Value Notification for Alarm and Event Server" WA3252_FCV_0113_2B.almValveFailure.AESeverity,440336,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Severity (0-1000)" WA3252_FCV_0113_2B.almValveFailure.AEShelveDuration,440337,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm and Events Suppress Duration Setpoint" WA3252_AFD_0103_1_SI.Totalize.BOOLS1,401148,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_1_SI.Totalize.BOOLS2,401149,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_1_SI.Totalize.BOOLS3,401150,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_1_SI.Totalize.BOOLS4,401151,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_1_SI.Totalize.INT1,401152,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_1_SI.Totalize.INT2,401153,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_1_SI.Totalize.Day500,401168,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_2_SI.Totalize.BOOLS1,401348,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_2_SI.Totalize.BOOLS2,401349,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_2_SI.Totalize.BOOLS3,401350,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_2_SI.Totalize.BOOLS4,401351,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_2_SI.Totalize.INT1,401352,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_2_SI.Totalize.INT2,401353,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_2_SI.Totalize.Day500,401368,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_3_SI.Totalize.BOOLS1,401548,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_3_SI.Totalize.BOOLS2,401549,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_3_SI.Totalize.BOOLS3,401550,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_3_SI.Totalize.BOOLS4,401551,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_3_SI.Totalize.INT1,401552,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_3_SI.Totalize.INT2,401553,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_3_SI.Totalize.Day500,401568,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_4_SI.Totalize.BOOLS1,401748,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_4_SI.Totalize.BOOLS2,401749,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_4_SI.Totalize.BOOLS3,401750,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_4_SI.Totalize.BOOLS4,401751,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_4_SI.Totalize.INT1,401752,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_4_SI.Totalize.INT2,401753,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_4_SI.Totalize.Day500,401768,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_5_SI.Totalize.BOOLS1,401948,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_5_SI.Totalize.BOOLS2,401949,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_5_SI.Totalize.BOOLS3,401950,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_5_SI.Totalize.BOOLS4,401951,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_5_SI.Totalize.INT1,401952,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_5_SI.Totalize.INT2,401953,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_5_SI.Totalize.Day500,401968,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_6_SI.Totalize.BOOLS1,402148,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_6_SI.Totalize.BOOLS2,402149,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_6_SI.Totalize.BOOLS3,402150,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_6_SI.Totalize.BOOLS4,402151,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_6_SI.Totalize.INT1,402152,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_6_SI.Totalize.INT2,402153,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_6_SI.Totalize.Day500,402168,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_7_SI.Totalize.BOOLS1,402348,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_7_SI.Totalize.BOOLS2,402349,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_7_SI.Totalize.BOOLS3,402350,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_7_SI.Totalize.BOOLS4,402351,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_7_SI.Totalize.INT1,402352,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_7_SI.Totalize.INT2,402353,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_7_SI.Totalize.Day500,402368,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_8_SI.Totalize.BOOLS1,402548,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_8_SI.Totalize.BOOLS2,402549,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_8_SI.Totalize.BOOLS3,402550,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_8_SI.Totalize.BOOLS4,402551,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_8_SI.Totalize.INT1,402552,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_8_SI.Totalize.INT2,402553,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_8_SI.Totalize.Day500,402568,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_AFD_0103_9_SI.Totalize.BOOLS1,402748,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_AFD_0103_9_SI.Totalize.BOOLS2,402749,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_9_SI.Totalize.BOOLS3,402750,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_9_SI.Totalize.BOOLS4,402751,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_AFD_0103_9_SI.Totalize.INT1,402752,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_9_SI.Totalize.INT2,402753,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_AFD_0103_9_SI.Totalize.Day500,402768,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI1.Totalize.BOOLS1,402948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI1.Totalize.BOOLS2,402949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI1.Totalize.BOOLS3,402950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI1.Totalize.BOOLS4,402951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI1.Totalize.INT1,402952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI1.Totalize.INT2,402953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI1.Totalize.Day500,402968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI2.Totalize.BOOLS1,403148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI2.Totalize.BOOLS2,403149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI2.Totalize.BOOLS3,403150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI2.Totalize.BOOLS4,403151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI2.Totalize.INT1,403152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI2.Totalize.INT2,403153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI2.Totalize.Day500,403168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI3.Totalize.BOOLS1,403348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI3.Totalize.BOOLS2,403349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI3.Totalize.BOOLS3,403350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI3.Totalize.BOOLS4,403351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI3.Totalize.INT1,403352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI3.Totalize.INT2,403353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI3.Totalize.Day500,403368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI4.Totalize.BOOLS1,403548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI4.Totalize.BOOLS2,403549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI4.Totalize.BOOLS3,403550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI4.Totalize.BOOLS4,403551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI4.Totalize.INT1,403552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI4.Totalize.INT2,403553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI4.Totalize.Day500,403568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI5.Totalize.BOOLS1,403748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI5.Totalize.BOOLS2,403749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI5.Totalize.BOOLS3,403750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI5.Totalize.BOOLS4,403751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI5.Totalize.INT1,403752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI5.Totalize.INT2,403753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI5.Totalize.Day500,403768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI6.Totalize.BOOLS1,403948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI6.Totalize.BOOLS2,403949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI6.Totalize.BOOLS3,403950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI6.Totalize.BOOLS4,403951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI6.Totalize.INT1,403952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI6.Totalize.INT2,403953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI6.Totalize.Day500,403968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI7.Totalize.BOOLS1,404148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI7.Totalize.BOOLS2,404149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI7.Totalize.BOOLS3,404150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI7.Totalize.BOOLS4,404151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI7.Totalize.INT1,404152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI7.Totalize.INT2,404153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI7.Totalize.Day500,404168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI8.Totalize.BOOLS1,404348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI8.Totalize.BOOLS2,404349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI8.Totalize.BOOLS3,404350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI8.Totalize.BOOLS4,404351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI8.Totalize.INT1,404352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI8.Totalize.INT2,404353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI8.Totalize.Day500,404368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_CP_0116_1_FI9.Totalize.BOOLS1,404548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_CP_0116_1_FI9.Totalize.BOOLS2,404549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI9.Totalize.BOOLS3,404550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI9.Totalize.BOOLS4,404551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_CP_0116_1_FI9.Totalize.INT1,404552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI9.Totalize.INT2,404553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_CP_0116_1_FI9.Totalize.Day500,404568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FCV_0113_2A_ZI.Totalize.BOOLS1,404748,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FCV_0113_2A_ZI.Totalize.BOOLS2,404749,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2A_ZI.Totalize.BOOLS3,404750,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2A_ZI.Totalize.BOOLS4,404751,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2A_ZI.Totalize.INT1,404752,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FCV_0113_2A_ZI.Totalize.INT2,404753,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FCV_0113_2A_ZI.Totalize.Day500,404768,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FCV_0113_2B_ZI.Totalize.BOOLS1,404948,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FCV_0113_2B_ZI.Totalize.BOOLS2,404949,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2B_ZI.Totalize.BOOLS3,404950,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2B_ZI.Totalize.BOOLS4,404951,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FCV_0113_2B_ZI.Totalize.INT1,404952,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FCV_0113_2B_ZI.Totalize.INT2,404953,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FCV_0113_2B_ZI.Totalize.Day500,404968,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FIT_0113_2A_FI.Totalize.BOOLS1,405148,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FIT_0113_2A_FI.Totalize.BOOLS2,405149,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FIT_0113_2A_FI.Totalize.BOOLS3,405150,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FIT_0113_2A_FI.Totalize.BOOLS4,405151,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FIT_0113_2A_FI.Totalize.INT1,405152,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FIT_0113_2A_FI.Totalize.INT2,405153,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FIT_0113_2A_FI.Totalize.Day500,405168,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_1B_ZI.Totalize.BOOLS1,405348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_1B_ZI.Totalize.BOOLS2,405349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_1B_ZI.Totalize.BOOLS3,405350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_1B_ZI.Totalize.BOOLS4,405351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_1B_ZI.Totalize.INT1,405352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_1B_ZI.Totalize.INT2,405353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_1B_ZI.Totalize.Day500,405368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_2B_ZI.Totalize.BOOLS1,405548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_2B_ZI.Totalize.BOOLS2,405549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_2B_ZI.Totalize.BOOLS3,405550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_2B_ZI.Totalize.BOOLS4,405551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_2B_ZI.Totalize.INT1,405552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_2B_ZI.Totalize.INT2,405553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_2B_ZI.Totalize.Day500,405568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_3B_ZI.Totalize.BOOLS1,405748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_3B_ZI.Totalize.BOOLS2,405749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3B_ZI.Totalize.BOOLS3,405750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3B_ZI.Totalize.BOOLS4,405751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_3B_ZI.Totalize.INT1,405752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_3B_ZI.Totalize.INT2,405753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_3B_ZI.Totalize.Day500,405768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_4B_ZI.Totalize.BOOLS1,405948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_4B_ZI.Totalize.BOOLS2,405949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4B_ZI.Totalize.BOOLS3,405950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4B_ZI.Totalize.BOOLS4,405951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_4B_ZI.Totalize.INT1,405952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_4B_ZI.Totalize.INT2,405953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_4B_ZI.Totalize.Day500,405968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_5B_ZI.Totalize.BOOLS1,406148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_5B_ZI.Totalize.BOOLS2,406149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5B_ZI.Totalize.BOOLS3,406150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5B_ZI.Totalize.BOOLS4,406151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_5B_ZI.Totalize.INT1,406152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_5B_ZI.Totalize.INT2,406153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_5B_ZI.Totalize.Day500,406168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_6B_ZI.Totalize.BOOLS1,406348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_6B_ZI.Totalize.BOOLS2,406349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6B_ZI.Totalize.BOOLS3,406350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6B_ZI.Totalize.BOOLS4,406351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_6B_ZI.Totalize.INT1,406352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_6B_ZI.Totalize.INT2,406353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_6B_ZI.Totalize.Day500,406368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_7B_ZI.Totalize.BOOLS1,406548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_7B_ZI.Totalize.BOOLS2,406549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7B_ZI.Totalize.BOOLS3,406550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7B_ZI.Totalize.BOOLS4,406551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_7B_ZI.Totalize.INT1,406552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_7B_ZI.Totalize.INT2,406553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_7B_ZI.Totalize.Day500,406568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_8B_ZI.Totalize.BOOLS1,406748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_8B_ZI.Totalize.BOOLS2,406749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8B_ZI.Totalize.BOOLS3,406750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8B_ZI.Totalize.BOOLS4,406751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_8B_ZI.Totalize.INT1,406752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_8B_ZI.Totalize.INT2,406753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_8B_ZI.Totalize.Day500,406768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_FV_0103_9B_ZI.Totalize.BOOLS1,406948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_FV_0103_9B_ZI.Totalize.BOOLS2,406949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_FV_0103_9B_ZI.Totalize.BOOLS3,406950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_FV_0103_9B_ZI.Totalize.BOOLS4,406951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_FV_0103_9B_ZI.Totalize.INT1,406952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_9B_ZI.Totalize.INT2,406953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_FV_0103_9B_ZI.Totalize.Day500,406968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_1_VI1.Totalize.BOOLS1,407148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_1_VI1.Totalize.BOOLS2,407149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI1.Totalize.BOOLS3,407150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI1.Totalize.BOOLS4,407151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI1.Totalize.INT1,407152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI1.Totalize.INT2,407153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI1.Totalize.Day500,407168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_1_VI2.Totalize.BOOLS1,407348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_1_VI2.Totalize.BOOLS2,407349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI2.Totalize.BOOLS3,407350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI2.Totalize.BOOLS4,407351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI2.Totalize.INT1,407352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI2.Totalize.INT2,407353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI2.Totalize.Day500,407368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_1_VI3.Totalize.BOOLS1,407548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_1_VI3.Totalize.BOOLS2,407549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI3.Totalize.BOOLS3,407550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI3.Totalize.BOOLS4,407551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI3.Totalize.INT1,407552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI3.Totalize.INT2,407553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI3.Totalize.Day500,407568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_1_VI4.Totalize.BOOLS1,407748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_1_VI4.Totalize.BOOLS2,407749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI4.Totalize.BOOLS3,407750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI4.Totalize.BOOLS4,407751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_1_VI4.Totalize.INT1,407752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI4.Totalize.INT2,407753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_1_VI4.Totalize.Day500,407768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_2_VI1.Totalize.BOOLS1,407948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_2_VI1.Totalize.BOOLS2,407949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI1.Totalize.BOOLS3,407950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI1.Totalize.BOOLS4,407951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI1.Totalize.INT1,407952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI1.Totalize.INT2,407953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI1.Totalize.Day500,407968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_2_VI2.Totalize.BOOLS1,408148,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_2_VI2.Totalize.BOOLS2,408149,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI2.Totalize.BOOLS3,408150,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI2.Totalize.BOOLS4,408151,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI2.Totalize.INT1,408152,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI2.Totalize.INT2,408153,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI2.Totalize.Day500,408168,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_2_VI3.Totalize.BOOLS1,408348,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_2_VI3.Totalize.BOOLS2,408349,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI3.Totalize.BOOLS3,408350,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI3.Totalize.BOOLS4,408351,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI3.Totalize.INT1,408352,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI3.Totalize.INT2,408353,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI3.Totalize.Day500,408368,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_2_VI4.Totalize.BOOLS1,408548,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_2_VI4.Totalize.BOOLS2,408549,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI4.Totalize.BOOLS3,408550,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI4.Totalize.BOOLS4,408551,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_2_VI4.Totalize.INT1,408552,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI4.Totalize.INT2,408553,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_2_VI4.Totalize.Day500,408568,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_3_VI1.Totalize.BOOLS1,408748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_3_VI1.Totalize.BOOLS2,408749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI1.Totalize.BOOLS3,408750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI1.Totalize.BOOLS4,408751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI1.Totalize.INT1,408752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI1.Totalize.INT2,408753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI1.Totalize.Day500,408768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_3_VI2.Totalize.BOOLS1,408948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_3_VI2.Totalize.BOOLS2,408949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI2.Totalize.BOOLS3,408950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI2.Totalize.BOOLS4,408951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI2.Totalize.INT1,408952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI2.Totalize.INT2,408953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI2.Totalize.Day500,408968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_3_VI3.Totalize.BOOLS1,409148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_3_VI3.Totalize.BOOLS2,409149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI3.Totalize.BOOLS3,409150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI3.Totalize.BOOLS4,409151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI3.Totalize.INT1,409152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI3.Totalize.INT2,409153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI3.Totalize.Day500,409168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_3_VI4.Totalize.BOOLS1,409348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_3_VI4.Totalize.BOOLS2,409349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI4.Totalize.BOOLS3,409350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI4.Totalize.BOOLS4,409351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_3_VI4.Totalize.INT1,409352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI4.Totalize.INT2,409353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_3_VI4.Totalize.Day500,409368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_4_VI1.Totalize.BOOLS1,409548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_4_VI1.Totalize.BOOLS2,409549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI1.Totalize.BOOLS3,409550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI1.Totalize.BOOLS4,409551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI1.Totalize.INT1,409552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI1.Totalize.INT2,409553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI1.Totalize.Day500,409568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_4_VI2.Totalize.BOOLS1,409748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_4_VI2.Totalize.BOOLS2,409749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI2.Totalize.BOOLS3,409750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI2.Totalize.BOOLS4,409751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI2.Totalize.INT1,409752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI2.Totalize.INT2,409753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI2.Totalize.Day500,409768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_4_VI3.Totalize.BOOLS1,409948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_4_VI3.Totalize.BOOLS2,409949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI3.Totalize.BOOLS3,409950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI3.Totalize.BOOLS4,409951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI3.Totalize.INT1,409952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI3.Totalize.INT2,409953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI3.Totalize.Day500,409968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_4_VI4.Totalize.BOOLS1,410148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_4_VI4.Totalize.BOOLS2,410149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI4.Totalize.BOOLS3,410150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI4.Totalize.BOOLS4,410151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_4_VI4.Totalize.INT1,410152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI4.Totalize.INT2,410153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_4_VI4.Totalize.Day500,410168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_5_VI1.Totalize.BOOLS1,410348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_5_VI1.Totalize.BOOLS2,410349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI1.Totalize.BOOLS3,410350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI1.Totalize.BOOLS4,410351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI1.Totalize.INT1,410352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI1.Totalize.INT2,410353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI1.Totalize.Day500,410368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_5_VI2.Totalize.BOOLS1,410548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_5_VI2.Totalize.BOOLS2,410549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI2.Totalize.BOOLS3,410550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI2.Totalize.BOOLS4,410551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI2.Totalize.INT1,410552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI2.Totalize.INT2,410553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI2.Totalize.Day500,410568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_5_VI3.Totalize.BOOLS1,410748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_5_VI3.Totalize.BOOLS2,410749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI3.Totalize.BOOLS3,410750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI3.Totalize.BOOLS4,410751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI3.Totalize.INT1,410752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI3.Totalize.INT2,410753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI3.Totalize.Day500,410768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_5_VI4.Totalize.BOOLS1,410948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_5_VI4.Totalize.BOOLS2,410949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI4.Totalize.BOOLS3,410950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI4.Totalize.BOOLS4,410951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_5_VI4.Totalize.INT1,410952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI4.Totalize.INT2,410953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_5_VI4.Totalize.Day500,410968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_6_VI1.Totalize.BOOLS1,411148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_6_VI1.Totalize.BOOLS2,411149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI1.Totalize.BOOLS3,411150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI1.Totalize.BOOLS4,411151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI1.Totalize.INT1,411152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI1.Totalize.INT2,411153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI1.Totalize.Day500,411168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_6_VI2.Totalize.BOOLS1,411348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_6_VI2.Totalize.BOOLS2,411349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI2.Totalize.BOOLS3,411350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI2.Totalize.BOOLS4,411351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI2.Totalize.INT1,411352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI2.Totalize.INT2,411353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI2.Totalize.Day500,411368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_6_VI3.Totalize.BOOLS1,411548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_6_VI3.Totalize.BOOLS2,411549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI3.Totalize.BOOLS3,411550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI3.Totalize.BOOLS4,411551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI3.Totalize.INT1,411552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI3.Totalize.INT2,411553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI3.Totalize.Day500,411568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_6_VI4.Totalize.BOOLS1,411748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_6_VI4.Totalize.BOOLS2,411749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI4.Totalize.BOOLS3,411750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI4.Totalize.BOOLS4,411751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_6_VI4.Totalize.INT1,411752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI4.Totalize.INT2,411753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_6_VI4.Totalize.Day500,411768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_7_VI1.Totalize.BOOLS1,411948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_7_VI1.Totalize.BOOLS2,411949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI1.Totalize.BOOLS3,411950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI1.Totalize.BOOLS4,411951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI1.Totalize.INT1,411952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI1.Totalize.INT2,411953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI1.Totalize.Day500,411968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_7_VI2.Totalize.BOOLS1,412148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_7_VI2.Totalize.BOOLS2,412149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI2.Totalize.BOOLS3,412150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI2.Totalize.BOOLS4,412151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI2.Totalize.INT1,412152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI2.Totalize.INT2,412153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI2.Totalize.Day500,412168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_7_VI3.Totalize.BOOLS1,412348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_7_VI3.Totalize.BOOLS2,412349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI3.Totalize.BOOLS3,412350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI3.Totalize.BOOLS4,412351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI3.Totalize.INT1,412352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI3.Totalize.INT2,412353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI3.Totalize.Day500,412368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_7_VI4.Totalize.BOOLS1,412548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_7_VI4.Totalize.BOOLS2,412549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI4.Totalize.BOOLS3,412550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI4.Totalize.BOOLS4,412551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_7_VI4.Totalize.INT1,412552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI4.Totalize.INT2,412553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_7_VI4.Totalize.Day500,412568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_8_VI1.Totalize.BOOLS1,412748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_8_VI1.Totalize.BOOLS2,412749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI1.Totalize.BOOLS3,412750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI1.Totalize.BOOLS4,412751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI1.Totalize.INT1,412752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI1.Totalize.INT2,412753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI1.Totalize.Day500,412768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_8_VI2.Totalize.BOOLS1,412948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_8_VI2.Totalize.BOOLS2,412949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI2.Totalize.BOOLS3,412950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI2.Totalize.BOOLS4,412951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI2.Totalize.INT1,412952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI2.Totalize.INT2,412953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI2.Totalize.Day500,412968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_8_VI3.Totalize.BOOLS1,413148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_8_VI3.Totalize.BOOLS2,413149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI3.Totalize.BOOLS3,413150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI3.Totalize.BOOLS4,413151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI3.Totalize.INT1,413152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI3.Totalize.INT2,413153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI3.Totalize.Day500,413168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_8_VI4.Totalize.BOOLS1,413348,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_8_VI4.Totalize.BOOLS2,413349,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI4.Totalize.BOOLS3,413350,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI4.Totalize.BOOLS4,413351,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_8_VI4.Totalize.INT1,413352,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI4.Totalize.INT2,413353,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_8_VI4.Totalize.Day500,413368,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_9_VI1.Totalize.BOOLS1,413548,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_9_VI1.Totalize.BOOLS2,413549,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI1.Totalize.BOOLS3,413550,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI1.Totalize.BOOLS4,413551,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI1.Totalize.INT1,413552,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI1.Totalize.INT2,413553,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI1.Totalize.Day500,413568,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_9_VI2.Totalize.BOOLS1,413748,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_9_VI2.Totalize.BOOLS2,413749,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI2.Totalize.BOOLS3,413750,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI2.Totalize.BOOLS4,413751,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI2.Totalize.INT1,413752,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI2.Totalize.INT2,413753,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI2.Totalize.Day500,413768,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_9_VI3.Totalize.BOOLS1,413948,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_9_VI3.Totalize.BOOLS2,413949,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI3.Totalize.BOOLS3,413950,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI3.Totalize.BOOLS4,413951,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI3.Totalize.INT1,413952,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI3.Totalize.INT2,413953,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI3.Totalize.Day500,413968,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_MTR_0103_9_VI4.Totalize.BOOLS1,414148,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_MTR_0103_9_VI4.Totalize.BOOLS2,414149,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI4.Totalize.BOOLS3,414150,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI4.Totalize.BOOLS4,414151,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_MTR_0103_9_VI4.Totalize.INT1,414152,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI4.Totalize.INT2,414153,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_MTR_0103_9_VI4.Totalize.Day500,414168,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0102_1_PI.Totalize.BOOLS1,414348,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0102_1_PI.Totalize.BOOLS2,414349,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_1_PI.Totalize.BOOLS3,414350,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_1_PI.Totalize.BOOLS4,414351,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_1_PI.Totalize.INT1,414352,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0102_1_PI.Totalize.INT2,414353,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0102_1_PI.Totalize.Day500,414368,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0102_2_PI.Totalize.BOOLS1,414548,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0102_2_PI.Totalize.BOOLS2,414549,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_2_PI.Totalize.BOOLS3,414550,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_2_PI.Totalize.BOOLS4,414551,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0102_2_PI.Totalize.INT1,414552,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0102_2_PI.Totalize.INT2,414553,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0102_2_PI.Totalize.Day500,414568,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_1_PI.Totalize.BOOLS1,414748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_1_PI.Totalize.BOOLS2,414749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_1_PI.Totalize.BOOLS3,414750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_1_PI.Totalize.BOOLS4,414751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_1_PI.Totalize.INT1,414752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_1_PI.Totalize.INT2,414753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_1_PI.Totalize.Day500,414768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_2_PI.Totalize.BOOLS1,414948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_2_PI.Totalize.BOOLS2,414949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_2_PI.Totalize.BOOLS3,414950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_2_PI.Totalize.BOOLS4,414951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_2_PI.Totalize.INT1,414952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_2_PI.Totalize.INT2,414953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_2_PI.Totalize.Day500,414968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_3_PI.Totalize.BOOLS1,415148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_3_PI.Totalize.BOOLS2,415149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_3_PI.Totalize.BOOLS3,415150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_3_PI.Totalize.BOOLS4,415151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_3_PI.Totalize.INT1,415152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_3_PI.Totalize.INT2,415153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_3_PI.Totalize.Day500,415168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_4_PI.Totalize.BOOLS1,415348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_4_PI.Totalize.BOOLS2,415349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_4_PI.Totalize.BOOLS3,415350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_4_PI.Totalize.BOOLS4,415351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_4_PI.Totalize.INT1,415352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_4_PI.Totalize.INT2,415353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_4_PI.Totalize.Day500,415368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_5_PI.Totalize.BOOLS1,415548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_5_PI.Totalize.BOOLS2,415549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_5_PI.Totalize.BOOLS3,415550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_5_PI.Totalize.BOOLS4,415551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_5_PI.Totalize.INT1,415552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_5_PI.Totalize.INT2,415553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_5_PI.Totalize.Day500,415568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_6_PI.Totalize.BOOLS1,415748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_6_PI.Totalize.BOOLS2,415749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_6_PI.Totalize.BOOLS3,415750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_6_PI.Totalize.BOOLS4,415751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_6_PI.Totalize.INT1,415752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_6_PI.Totalize.INT2,415753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_6_PI.Totalize.Day500,415768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_7_PI.Totalize.BOOLS1,415948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_7_PI.Totalize.BOOLS2,415949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_7_PI.Totalize.BOOLS3,415950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_7_PI.Totalize.BOOLS4,415951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_7_PI.Totalize.INT1,415952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_7_PI.Totalize.INT2,415953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_7_PI.Totalize.Day500,415968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_8_PI.Totalize.BOOLS1,416148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_8_PI.Totalize.BOOLS2,416149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_8_PI.Totalize.BOOLS3,416150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_8_PI.Totalize.BOOLS4,416151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_8_PI.Totalize.INT1,416152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_8_PI.Totalize.INT2,416153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_8_PI.Totalize.Day500,416168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0103_9_PI.Totalize.BOOLS1,416348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0103_9_PI.Totalize.BOOLS2,416349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_9_PI.Totalize.BOOLS3,416350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_9_PI.Totalize.BOOLS4,416351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0103_9_PI.Totalize.INT1,416352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_9_PI.Totalize.INT2,416353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0103_9_PI.Totalize.Day500,416368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PIT_0104_1_PI.Totalize.BOOLS1,416548,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PIT_0104_1_PI.Totalize.BOOLS2,416549,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PIT_0104_1_PI.Totalize.BOOLS3,416550,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PIT_0104_1_PI.Totalize.BOOLS4,416551,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PIT_0104_1_PI.Totalize.INT1,416552,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0104_1_PI.Totalize.INT2,416553,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PIT_0104_1_PI.Totalize.Day500,416568,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_1_VI1.Totalize.BOOLS1,416748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_1_VI1.Totalize.BOOLS2,416749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI1.Totalize.BOOLS3,416750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI1.Totalize.BOOLS4,416751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI1.Totalize.INT1,416752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI1.Totalize.INT2,416753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI1.Totalize.Day500,416768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_1_VI2.Totalize.BOOLS1,416948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_1_VI2.Totalize.BOOLS2,416949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI2.Totalize.BOOLS3,416950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI2.Totalize.BOOLS4,416951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI2.Totalize.INT1,416952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI2.Totalize.INT2,416953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI2.Totalize.Day500,416968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_1_VI3.Totalize.BOOLS1,417148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_1_VI3.Totalize.BOOLS2,417149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI3.Totalize.BOOLS3,417150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI3.Totalize.BOOLS4,417151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI3.Totalize.INT1,417152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI3.Totalize.INT2,417153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI3.Totalize.Day500,417168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_1_VI4.Totalize.BOOLS1,417348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_1_VI4.Totalize.BOOLS2,417349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI4.Totalize.BOOLS3,417350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI4.Totalize.BOOLS4,417351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI4.Totalize.INT1,417352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI4.Totalize.INT2,417353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI4.Totalize.Day500,417368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_1_VI5.Totalize.BOOLS1,417548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_1_VI5.Totalize.BOOLS2,417549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI5.Totalize.BOOLS3,417550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI5.Totalize.BOOLS4,417551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_1_VI5.Totalize.INT1,417552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI5.Totalize.INT2,417553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_1_VI5.Totalize.Day500,417568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_2_VI1.Totalize.BOOLS1,417748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_2_VI1.Totalize.BOOLS2,417749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI1.Totalize.BOOLS3,417750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI1.Totalize.BOOLS4,417751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI1.Totalize.INT1,417752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI1.Totalize.INT2,417753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI1.Totalize.Day500,417768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_2_VI2.Totalize.BOOLS1,417948,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_2_VI2.Totalize.BOOLS2,417949,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI2.Totalize.BOOLS3,417950,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI2.Totalize.BOOLS4,417951,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI2.Totalize.INT1,417952,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI2.Totalize.INT2,417953,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI2.Totalize.Day500,417968,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_2_VI3.Totalize.BOOLS1,418148,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_2_VI3.Totalize.BOOLS2,418149,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI3.Totalize.BOOLS3,418150,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI3.Totalize.BOOLS4,418151,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI3.Totalize.INT1,418152,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI3.Totalize.INT2,418153,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI3.Totalize.Day500,418168,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_2_VI4.Totalize.BOOLS1,418348,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_2_VI4.Totalize.BOOLS2,418349,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI4.Totalize.BOOLS3,418350,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI4.Totalize.BOOLS4,418351,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI4.Totalize.INT1,418352,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI4.Totalize.INT2,418353,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI4.Totalize.Day500,418368,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_2_VI5.Totalize.BOOLS1,418548,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_2_VI5.Totalize.BOOLS2,418549,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI5.Totalize.BOOLS3,418550,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI5.Totalize.BOOLS4,418551,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_2_VI5.Totalize.INT1,418552,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI5.Totalize.INT2,418553,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_2_VI5.Totalize.Day500,418568,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_3_VI1.Totalize.BOOLS1,418748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_3_VI1.Totalize.BOOLS2,418749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI1.Totalize.BOOLS3,418750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI1.Totalize.BOOLS4,418751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI1.Totalize.INT1,418752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI1.Totalize.INT2,418753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI1.Totalize.Day500,418768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_3_VI2.Totalize.BOOLS1,418948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_3_VI2.Totalize.BOOLS2,418949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI2.Totalize.BOOLS3,418950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI2.Totalize.BOOLS4,418951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI2.Totalize.INT1,418952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI2.Totalize.INT2,418953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI2.Totalize.Day500,418968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_3_VI3.Totalize.BOOLS1,419148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_3_VI3.Totalize.BOOLS2,419149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI3.Totalize.BOOLS3,419150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI3.Totalize.BOOLS4,419151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI3.Totalize.INT1,419152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI3.Totalize.INT2,419153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI3.Totalize.Day500,419168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_3_VI4.Totalize.BOOLS1,419348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_3_VI4.Totalize.BOOLS2,419349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI4.Totalize.BOOLS3,419350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI4.Totalize.BOOLS4,419351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI4.Totalize.INT1,419352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI4.Totalize.INT2,419353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI4.Totalize.Day500,419368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_3_VI5.Totalize.BOOLS1,419548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_3_VI5.Totalize.BOOLS2,419549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI5.Totalize.BOOLS3,419550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI5.Totalize.BOOLS4,419551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_3_VI5.Totalize.INT1,419552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI5.Totalize.INT2,419553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_3_VI5.Totalize.Day500,419568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_4_VI1.Totalize.BOOLS1,419748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_4_VI1.Totalize.BOOLS2,419749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI1.Totalize.BOOLS3,419750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI1.Totalize.BOOLS4,419751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI1.Totalize.INT1,419752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI1.Totalize.INT2,419753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI1.Totalize.Day500,419768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_4_VI2.Totalize.BOOLS1,419948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_4_VI2.Totalize.BOOLS2,419949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI2.Totalize.BOOLS3,419950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI2.Totalize.BOOLS4,419951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI2.Totalize.INT1,419952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI2.Totalize.INT2,419953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI2.Totalize.Day500,419968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_4_VI3.Totalize.BOOLS1,420148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_4_VI3.Totalize.BOOLS2,420149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI3.Totalize.BOOLS3,420150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI3.Totalize.BOOLS4,420151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI3.Totalize.INT1,420152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI3.Totalize.INT2,420153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI3.Totalize.Day500,420168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_4_VI4.Totalize.BOOLS1,420348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_4_VI4.Totalize.BOOLS2,420349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI4.Totalize.BOOLS3,420350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI4.Totalize.BOOLS4,420351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI4.Totalize.INT1,420352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI4.Totalize.INT2,420353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI4.Totalize.Day500,420368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_4_VI5.Totalize.BOOLS1,420548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_4_VI5.Totalize.BOOLS2,420549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI5.Totalize.BOOLS3,420550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI5.Totalize.BOOLS4,420551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_4_VI5.Totalize.INT1,420552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI5.Totalize.INT2,420553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_4_VI5.Totalize.Day500,420568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_5_VI1.Totalize.BOOLS1,420748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_5_VI1.Totalize.BOOLS2,420749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI1.Totalize.BOOLS3,420750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI1.Totalize.BOOLS4,420751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI1.Totalize.INT1,420752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI1.Totalize.INT2,420753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI1.Totalize.Day500,420768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_5_VI2.Totalize.BOOLS1,420948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_5_VI2.Totalize.BOOLS2,420949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI2.Totalize.BOOLS3,420950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI2.Totalize.BOOLS4,420951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI2.Totalize.INT1,420952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI2.Totalize.INT2,420953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI2.Totalize.Day500,420968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_5_VI3.Totalize.BOOLS1,421148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_5_VI3.Totalize.BOOLS2,421149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI3.Totalize.BOOLS3,421150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI3.Totalize.BOOLS4,421151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI3.Totalize.INT1,421152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI3.Totalize.INT2,421153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI3.Totalize.Day500,421168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_5_VI4.Totalize.BOOLS1,421348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_5_VI4.Totalize.BOOLS2,421349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI4.Totalize.BOOLS3,421350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI4.Totalize.BOOLS4,421351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI4.Totalize.INT1,421352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI4.Totalize.INT2,421353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI4.Totalize.Day500,421368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_5_VI5.Totalize.BOOLS1,421548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_5_VI5.Totalize.BOOLS2,421549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI5.Totalize.BOOLS3,421550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI5.Totalize.BOOLS4,421551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_5_VI5.Totalize.INT1,421552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI5.Totalize.INT2,421553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_5_VI5.Totalize.Day500,421568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_6_VI1.Totalize.BOOLS1,421748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_6_VI1.Totalize.BOOLS2,421749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI1.Totalize.BOOLS3,421750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI1.Totalize.BOOLS4,421751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI1.Totalize.INT1,421752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI1.Totalize.INT2,421753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI1.Totalize.Day500,421768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_6_VI2.Totalize.BOOLS1,421948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_6_VI2.Totalize.BOOLS2,421949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI2.Totalize.BOOLS3,421950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI2.Totalize.BOOLS4,421951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI2.Totalize.INT1,421952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI2.Totalize.INT2,421953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI2.Totalize.Day500,421968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_6_VI3.Totalize.BOOLS1,422148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_6_VI3.Totalize.BOOLS2,422149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI3.Totalize.BOOLS3,422150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI3.Totalize.BOOLS4,422151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI3.Totalize.INT1,422152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI3.Totalize.INT2,422153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI3.Totalize.Day500,422168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_6_VI4.Totalize.BOOLS1,422348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_6_VI4.Totalize.BOOLS2,422349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI4.Totalize.BOOLS3,422350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI4.Totalize.BOOLS4,422351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI4.Totalize.INT1,422352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI4.Totalize.INT2,422353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI4.Totalize.Day500,422368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_6_VI5.Totalize.BOOLS1,422548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_6_VI5.Totalize.BOOLS2,422549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI5.Totalize.BOOLS3,422550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI5.Totalize.BOOLS4,422551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_6_VI5.Totalize.INT1,422552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI5.Totalize.INT2,422553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_6_VI5.Totalize.Day500,422568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_7_VI1.Totalize.BOOLS1,422748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_7_VI1.Totalize.BOOLS2,422749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI1.Totalize.BOOLS3,422750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI1.Totalize.BOOLS4,422751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI1.Totalize.INT1,422752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI1.Totalize.INT2,422753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI1.Totalize.Day500,422768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_7_VI2.Totalize.BOOLS1,422948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_7_VI2.Totalize.BOOLS2,422949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI2.Totalize.BOOLS3,422950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI2.Totalize.BOOLS4,422951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI2.Totalize.INT1,422952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI2.Totalize.INT2,422953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI2.Totalize.Day500,422968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_7_VI3.Totalize.BOOLS1,423148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_7_VI3.Totalize.BOOLS2,423149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI3.Totalize.BOOLS3,423150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI3.Totalize.BOOLS4,423151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI3.Totalize.INT1,423152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI3.Totalize.INT2,423153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI3.Totalize.Day500,423168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_7_VI4.Totalize.BOOLS1,423348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_7_VI4.Totalize.BOOLS2,423349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI4.Totalize.BOOLS3,423350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI4.Totalize.BOOLS4,423351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI4.Totalize.INT1,423352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI4.Totalize.INT2,423353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI4.Totalize.Day500,423368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_7_VI5.Totalize.BOOLS1,423548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_7_VI5.Totalize.BOOLS2,423549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI5.Totalize.BOOLS3,423550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI5.Totalize.BOOLS4,423551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_7_VI5.Totalize.INT1,423552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI5.Totalize.INT2,423553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_7_VI5.Totalize.Day500,423568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_8_VI1.Totalize.BOOLS1,423748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_8_VI1.Totalize.BOOLS2,423749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI1.Totalize.BOOLS3,423750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI1.Totalize.BOOLS4,423751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI1.Totalize.INT1,423752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI1.Totalize.INT2,423753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI1.Totalize.Day500,423768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_8_VI2.Totalize.BOOLS1,423948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_8_VI2.Totalize.BOOLS2,423949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI2.Totalize.BOOLS3,423950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI2.Totalize.BOOLS4,423951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI2.Totalize.INT1,423952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI2.Totalize.INT2,423953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI2.Totalize.Day500,423968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_8_VI3.Totalize.BOOLS1,424148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_8_VI3.Totalize.BOOLS2,424149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI3.Totalize.BOOLS3,424150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI3.Totalize.BOOLS4,424151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI3.Totalize.INT1,424152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI3.Totalize.INT2,424153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI3.Totalize.Day500,424168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_8_VI4.Totalize.BOOLS1,424348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_8_VI4.Totalize.BOOLS2,424349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI4.Totalize.BOOLS3,424350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI4.Totalize.BOOLS4,424351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI4.Totalize.INT1,424352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI4.Totalize.INT2,424353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI4.Totalize.Day500,424368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_8_VI5.Totalize.BOOLS1,424548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_8_VI5.Totalize.BOOLS2,424549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI5.Totalize.BOOLS3,424550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI5.Totalize.BOOLS4,424551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_8_VI5.Totalize.INT1,424552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI5.Totalize.INT2,424553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_8_VI5.Totalize.Day500,424568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_9_VI1.Totalize.BOOLS1,424748,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_9_VI1.Totalize.BOOLS2,424749,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI1.Totalize.BOOLS3,424750,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI1.Totalize.BOOLS4,424751,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI1.Totalize.INT1,424752,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI1.Totalize.INT2,424753,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI1.Totalize.Day500,424768,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_9_VI2.Totalize.BOOLS1,424948,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_9_VI2.Totalize.BOOLS2,424949,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI2.Totalize.BOOLS3,424950,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI2.Totalize.BOOLS4,424951,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI2.Totalize.INT1,424952,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI2.Totalize.INT2,424953,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI2.Totalize.Day500,424968,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_9_VI3.Totalize.BOOLS1,425148,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_9_VI3.Totalize.BOOLS2,425149,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI3.Totalize.BOOLS3,425150,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI3.Totalize.BOOLS4,425151,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI3.Totalize.INT1,425152,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI3.Totalize.INT2,425153,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI3.Totalize.Day500,425168,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_9_VI4.Totalize.BOOLS1,425348,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_9_VI4.Totalize.BOOLS2,425349,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI4.Totalize.BOOLS3,425350,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI4.Totalize.BOOLS4,425351,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI4.Totalize.INT1,425352,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI4.Totalize.INT2,425353,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI4.Totalize.Day500,425368,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_PMP_0103_9_VI5.Totalize.BOOLS1,425548,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_PMP_0103_9_VI5.Totalize.BOOLS2,425549,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI5.Totalize.BOOLS3,425550,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI5.Totalize.BOOLS4,425551,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_PMP_0103_9_VI5.Totalize.INT1,425552,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI5.Totalize.INT2,425553,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_PMP_0103_9_VI5.Totalize.Day500,425568,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_TT_0111_1_TI.Totalize.BOOLS1,425748,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_TT_0111_1_TI.Totalize.BOOLS2,425749,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_TT_0111_1_TI.Totalize.BOOLS3,425750,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_TT_0111_1_TI.Totalize.BOOLS4,425751,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_TT_0111_1_TI.Totalize.INT1,425752,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_TT_0111_1_TI.Totalize.INT2,425753,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_TT_0111_1_TI.Totalize.Day500,425768,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" WA3252_TT_0112_1_TI.Totalize.BOOLS1,425948,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: First Integer of Packed Bits." WA3252_TT_0112_1_TI.Totalize.BOOLS2,425949,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Second Integer of Packed Bits. (SPARE)" WA3252_TT_0112_1_TI.Totalize.BOOLS3,425950,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Third Integer of Packed Bits. (SPARE)" WA3252_TT_0112_1_TI.Totalize.BOOLS4,425951,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Fourth Integer of Packed Bits. (SPARE)" WA3252_TT_0112_1_TI.Totalize.INT1,425952,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_TT_0112_1_TI.Totalize.INT2,425953,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Spare Integer" WA3252_TT_0112_1_TI.Totalize.Day500,425968,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Counts 500 days" Meter_Vault_PLC.Inputs.MV_INT_0,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Meter_Vault_PLC.Inputs.MV_INT_1,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Meter_Vault_PLC.Inputs.MV_INT_2,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Meter_Vault_PLC.Inputs.MV_INT_3,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Meter_Vault_PLC.Inputs.MV_INT_4,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump1.Inputs.P1_Power,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump1.Inputs.P1_ReactivePower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump1.Inputs.P1_ApparentPower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump1.Inputs.P1_PowerFactor,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump1.Inputs.P1_Frequency,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump2.Inputs.P2_Power,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump2.Inputs.P2_ReactivePower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump2.Inputs.P2_ApparentPower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump2.Inputs.P2_PowerFactor,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump2.Inputs.P2_Frequency,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump9.Inputs.P9_Power,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump9.Inputs.P9_ReactivePower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump9.Inputs.P9_ApparentPower,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump9.Inputs.P9_PowerFactor,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: RWPS_SEL710_Pump9.Inputs.P9_Frequency,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: TSR_PLC.Inputs.TSR_LSH,,Short,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: WA3252_AFD_0103_1_SI.almHighHigh.ALDL,401048,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almHighHigh.ATRM,401050,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almHigh.ALDL,401060,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almHigh.ATRM,401062,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almLow.ALDL,401072,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almLow.ATRM,401074,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almLowLow.ALDL,401084,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almLowLow.ATRM,401086,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almBrokenLoop.ALDL,401096,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almBrokenLoop.ATRM,401098,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almOverRange.ALDL,401108,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almOverRange.ATRM,401110,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almUnderRange.ALDL,401120,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almUnderRange.ATRM,401122,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almRateOfChange.ALDL,401132,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almRateOfChange.ATRM,401134,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.almPLCFault.ALDL,401144,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_SI.almPLCFault.ATRM,401146,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almHighHigh.ALDL,401248,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almHighHigh.ATRM,401250,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almHigh.ALDL,401260,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almHigh.ATRM,401262,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almLow.ALDL,401272,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almLow.ATRM,401274,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almLowLow.ALDL,401284,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almLowLow.ATRM,401286,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almBrokenLoop.ALDL,401296,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almBrokenLoop.ATRM,401298,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almOverRange.ALDL,401308,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almOverRange.ATRM,401310,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almUnderRange.ALDL,401320,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almUnderRange.ATRM,401322,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almRateOfChange.ALDL,401332,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almRateOfChange.ATRM,401334,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_SI.almPLCFault.ALDL,401344,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_SI.almPLCFault.ATRM,401346,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almHighHigh.ALDL,401448,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almHighHigh.ATRM,401450,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almHigh.ALDL,401460,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almHigh.ATRM,401462,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almLow.ALDL,401472,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almLow.ATRM,401474,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almLowLow.ALDL,401484,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almLowLow.ATRM,401486,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almBrokenLoop.ALDL,401496,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almBrokenLoop.ATRM,401498,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almOverRange.ALDL,401508,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almOverRange.ATRM,401510,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almUnderRange.ALDL,401520,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almUnderRange.ATRM,401522,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almRateOfChange.ALDL,401532,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almRateOfChange.ATRM,401534,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_SI.almPLCFault.ALDL,401544,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_SI.almPLCFault.ATRM,401546,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almHighHigh.ALDL,401648,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almHighHigh.ATRM,401650,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almHigh.ALDL,401660,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almHigh.ATRM,401662,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almLow.ALDL,401672,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almLow.ATRM,401674,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almLowLow.ALDL,401684,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almLowLow.ATRM,401686,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almBrokenLoop.ALDL,401696,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almBrokenLoop.ATRM,401698,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almOverRange.ALDL,401708,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almOverRange.ATRM,401710,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almUnderRange.ALDL,401720,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almUnderRange.ATRM,401722,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almRateOfChange.ALDL,401732,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almRateOfChange.ATRM,401734,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_SI.almPLCFault.ALDL,401744,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_SI.almPLCFault.ATRM,401746,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almHighHigh.ALDL,401848,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almHighHigh.ATRM,401850,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almHigh.ALDL,401860,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almHigh.ATRM,401862,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almLow.ALDL,401872,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almLow.ATRM,401874,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almLowLow.ALDL,401884,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almLowLow.ATRM,401886,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almBrokenLoop.ALDL,401896,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almBrokenLoop.ATRM,401898,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almOverRange.ALDL,401908,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almOverRange.ATRM,401910,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almUnderRange.ALDL,401920,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almUnderRange.ATRM,401922,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almRateOfChange.ALDL,401932,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almRateOfChange.ATRM,401934,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_SI.almPLCFault.ALDL,401944,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_SI.almPLCFault.ATRM,401946,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almHighHigh.ALDL,402048,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almHighHigh.ATRM,402050,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almHigh.ALDL,402060,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almHigh.ATRM,402062,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almLow.ALDL,402072,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almLow.ATRM,402074,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almLowLow.ALDL,402084,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almLowLow.ATRM,402086,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almBrokenLoop.ALDL,402096,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almBrokenLoop.ATRM,402098,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almOverRange.ALDL,402108,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almOverRange.ATRM,402110,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almUnderRange.ALDL,402120,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almUnderRange.ATRM,402122,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almRateOfChange.ALDL,402132,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almRateOfChange.ATRM,402134,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_SI.almPLCFault.ALDL,402144,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_SI.almPLCFault.ATRM,402146,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almHighHigh.ALDL,402248,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almHighHigh.ATRM,402250,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almHigh.ALDL,402260,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almHigh.ATRM,402262,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almLow.ALDL,402272,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almLow.ATRM,402274,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almLowLow.ALDL,402284,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almLowLow.ATRM,402286,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almBrokenLoop.ALDL,402296,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almBrokenLoop.ATRM,402298,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almOverRange.ALDL,402308,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almOverRange.ATRM,402310,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almUnderRange.ALDL,402320,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almUnderRange.ATRM,402322,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almRateOfChange.ALDL,402332,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almRateOfChange.ATRM,402334,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_SI.almPLCFault.ALDL,402344,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_SI.almPLCFault.ATRM,402346,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almHighHigh.ALDL,402448,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almHighHigh.ATRM,402450,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almHigh.ALDL,402460,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almHigh.ATRM,402462,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almLow.ALDL,402472,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almLow.ATRM,402474,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almLowLow.ALDL,402484,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almLowLow.ATRM,402486,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almBrokenLoop.ALDL,402496,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almBrokenLoop.ATRM,402498,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almOverRange.ALDL,402508,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almOverRange.ATRM,402510,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almUnderRange.ALDL,402520,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almUnderRange.ATRM,402522,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almRateOfChange.ALDL,402532,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almRateOfChange.ATRM,402534,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_SI.almPLCFault.ALDL,402544,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_SI.almPLCFault.ATRM,402546,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almHighHigh.ALDL,402648,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almHighHigh.ATRM,402650,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almHigh.ALDL,402660,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almHigh.ATRM,402662,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almLow.ALDL,402672,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almLow.ATRM,402674,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almLowLow.ALDL,402684,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almLowLow.ATRM,402686,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almBrokenLoop.ALDL,402696,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almBrokenLoop.ATRM,402698,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almOverRange.ALDL,402708,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almOverRange.ATRM,402710,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almUnderRange.ALDL,402720,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almUnderRange.ATRM,402722,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almRateOfChange.ALDL,402732,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almRateOfChange.ATRM,402734,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_SI.almPLCFault.ALDL,402744,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_SI.almPLCFault.ATRM,402746,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almHighHigh.ALDL,402848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almHighHigh.ATRM,402850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almHigh.ALDL,402860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almHigh.ATRM,402862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almLow.ALDL,402872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almLow.ATRM,402874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almLowLow.ALDL,402884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almLowLow.ATRM,402886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almBrokenLoop.ALDL,402896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almBrokenLoop.ATRM,402898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almOverRange.ALDL,402908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almOverRange.ATRM,402910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almUnderRange.ALDL,402920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almUnderRange.ATRM,402922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almRateOfChange.ALDL,402932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almRateOfChange.ATRM,402934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI1.almPLCFault.ALDL,402944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI1.almPLCFault.ATRM,402946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almHighHigh.ALDL,403048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almHighHigh.ATRM,403050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almHigh.ALDL,403060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almHigh.ATRM,403062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almLow.ALDL,403072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almLow.ATRM,403074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almLowLow.ALDL,403084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almLowLow.ATRM,403086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almBrokenLoop.ALDL,403096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almBrokenLoop.ATRM,403098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almOverRange.ALDL,403108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almOverRange.ATRM,403110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almUnderRange.ALDL,403120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almUnderRange.ATRM,403122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almRateOfChange.ALDL,403132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almRateOfChange.ATRM,403134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI2.almPLCFault.ALDL,403144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI2.almPLCFault.ATRM,403146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almHighHigh.ALDL,403248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almHighHigh.ATRM,403250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almHigh.ALDL,403260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almHigh.ATRM,403262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almLow.ALDL,403272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almLow.ATRM,403274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almLowLow.ALDL,403284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almLowLow.ATRM,403286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almBrokenLoop.ALDL,403296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almBrokenLoop.ATRM,403298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almOverRange.ALDL,403308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almOverRange.ATRM,403310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almUnderRange.ALDL,403320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almUnderRange.ATRM,403322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almRateOfChange.ALDL,403332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almRateOfChange.ATRM,403334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI3.almPLCFault.ALDL,403344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI3.almPLCFault.ATRM,403346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almHighHigh.ALDL,403448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almHighHigh.ATRM,403450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almHigh.ALDL,403460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almHigh.ATRM,403462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almLow.ALDL,403472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almLow.ATRM,403474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almLowLow.ALDL,403484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almLowLow.ATRM,403486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almBrokenLoop.ALDL,403496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almBrokenLoop.ATRM,403498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almOverRange.ALDL,403508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almOverRange.ATRM,403510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almUnderRange.ALDL,403520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almUnderRange.ATRM,403522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almRateOfChange.ALDL,403532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almRateOfChange.ATRM,403534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI4.almPLCFault.ALDL,403544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI4.almPLCFault.ATRM,403546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almHighHigh.ALDL,403648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almHighHigh.ATRM,403650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almHigh.ALDL,403660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almHigh.ATRM,403662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almLow.ALDL,403672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almLow.ATRM,403674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almLowLow.ALDL,403684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almLowLow.ATRM,403686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almBrokenLoop.ALDL,403696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almBrokenLoop.ATRM,403698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almOverRange.ALDL,403708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almOverRange.ATRM,403710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almUnderRange.ALDL,403720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almUnderRange.ATRM,403722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almRateOfChange.ALDL,403732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almRateOfChange.ATRM,403734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI5.almPLCFault.ALDL,403744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI5.almPLCFault.ATRM,403746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almHighHigh.ALDL,403848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almHighHigh.ATRM,403850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almHigh.ALDL,403860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almHigh.ATRM,403862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almLow.ALDL,403872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almLow.ATRM,403874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almLowLow.ALDL,403884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almLowLow.ATRM,403886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almBrokenLoop.ALDL,403896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almBrokenLoop.ATRM,403898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almOverRange.ALDL,403908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almOverRange.ATRM,403910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almUnderRange.ALDL,403920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almUnderRange.ATRM,403922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almRateOfChange.ALDL,403932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almRateOfChange.ATRM,403934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI6.almPLCFault.ALDL,403944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI6.almPLCFault.ATRM,403946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almHighHigh.ALDL,404048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almHighHigh.ATRM,404050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almHigh.ALDL,404060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almHigh.ATRM,404062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almLow.ALDL,404072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almLow.ATRM,404074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almLowLow.ALDL,404084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almLowLow.ATRM,404086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almBrokenLoop.ALDL,404096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almBrokenLoop.ATRM,404098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almOverRange.ALDL,404108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almOverRange.ATRM,404110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almUnderRange.ALDL,404120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almUnderRange.ATRM,404122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almRateOfChange.ALDL,404132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almRateOfChange.ATRM,404134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI7.almPLCFault.ALDL,404144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI7.almPLCFault.ATRM,404146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almHighHigh.ALDL,404248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almHighHigh.ATRM,404250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almHigh.ALDL,404260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almHigh.ATRM,404262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almLow.ALDL,404272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almLow.ATRM,404274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almLowLow.ALDL,404284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almLowLow.ATRM,404286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almBrokenLoop.ALDL,404296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almBrokenLoop.ATRM,404298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almOverRange.ALDL,404308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almOverRange.ATRM,404310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almUnderRange.ALDL,404320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almUnderRange.ATRM,404322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almRateOfChange.ALDL,404332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almRateOfChange.ATRM,404334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI8.almPLCFault.ALDL,404344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI8.almPLCFault.ATRM,404346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almHighHigh.ALDL,404448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almHighHigh.ATRM,404450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almHigh.ALDL,404460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almHigh.ATRM,404462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almLow.ALDL,404472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almLow.ATRM,404474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almLowLow.ALDL,404484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almLowLow.ATRM,404486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almBrokenLoop.ALDL,404496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almBrokenLoop.ATRM,404498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almOverRange.ALDL,404508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almOverRange.ATRM,404510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almUnderRange.ALDL,404520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almUnderRange.ATRM,404522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almRateOfChange.ALDL,404532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almRateOfChange.ATRM,404534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0116_1_FI9.almPLCFault.ALDL,404544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0116_1_FI9.almPLCFault.ATRM,404546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almHighHigh.ALDL,404648,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almHighHigh.ATRM,404650,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almHigh.ALDL,404660,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almHigh.ATRM,404662,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almLow.ALDL,404672,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almLow.ATRM,404674,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almLowLow.ALDL,404684,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almLowLow.ATRM,404686,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almBrokenLoop.ALDL,404696,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almBrokenLoop.ATRM,404698,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almOverRange.ALDL,404708,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almOverRange.ATRM,404710,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almUnderRange.ALDL,404720,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almUnderRange.ATRM,404722,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almRateOfChange.ALDL,404732,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almRateOfChange.ATRM,404734,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_ZI.almPLCFault.ALDL,404744,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_ZI.almPLCFault.ATRM,404746,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almHighHigh.ALDL,404848,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almHighHigh.ATRM,404850,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almHigh.ALDL,404860,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almHigh.ATRM,404862,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almLow.ALDL,404872,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almLow.ATRM,404874,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almLowLow.ALDL,404884,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almLowLow.ATRM,404886,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almBrokenLoop.ALDL,404896,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almBrokenLoop.ATRM,404898,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almOverRange.ALDL,404908,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almOverRange.ATRM,404910,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almUnderRange.ALDL,404920,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almUnderRange.ATRM,404922,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almRateOfChange.ALDL,404932,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almRateOfChange.ATRM,404934,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_ZI.almPLCFault.ALDL,404944,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_ZI.almPLCFault.ATRM,404946,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almHighHigh.ALDL,405048,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almHighHigh.ATRM,405050,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almHigh.ALDL,405060,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almHigh.ATRM,405062,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almLow.ALDL,405072,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almLow.ATRM,405074,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almLowLow.ALDL,405084,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almLowLow.ATRM,405086,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almBrokenLoop.ALDL,405096,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almBrokenLoop.ATRM,405098,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almOverRange.ALDL,405108,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almOverRange.ATRM,405110,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almUnderRange.ALDL,405120,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almUnderRange.ATRM,405122,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almRateOfChange.ALDL,405132,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almRateOfChange.ATRM,405134,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FIT_0113_2A_FI.almPLCFault.ALDL,405144,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FIT_0113_2A_FI.almPLCFault.ATRM,405146,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almHighHigh.ALDL,405248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almHighHigh.ATRM,405250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almHigh.ALDL,405260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almHigh.ATRM,405262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almLow.ALDL,405272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almLow.ATRM,405274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almLowLow.ALDL,405284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almLowLow.ATRM,405286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almBrokenLoop.ALDL,405296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almBrokenLoop.ATRM,405298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almOverRange.ALDL,405308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almOverRange.ATRM,405310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almUnderRange.ALDL,405320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almUnderRange.ATRM,405322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almRateOfChange.ALDL,405332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almRateOfChange.ATRM,405334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZI.almPLCFault.ALDL,405344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZI.almPLCFault.ATRM,405346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almHighHigh.ALDL,405448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almHighHigh.ATRM,405450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almHigh.ALDL,405460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almHigh.ATRM,405462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almLow.ALDL,405472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almLow.ATRM,405474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almLowLow.ALDL,405484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almLowLow.ATRM,405486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almBrokenLoop.ALDL,405496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almBrokenLoop.ATRM,405498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almOverRange.ALDL,405508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almOverRange.ATRM,405510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almUnderRange.ALDL,405520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almUnderRange.ATRM,405522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almRateOfChange.ALDL,405532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almRateOfChange.ATRM,405534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZI.almPLCFault.ALDL,405544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZI.almPLCFault.ATRM,405546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almHighHigh.ALDL,405648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almHighHigh.ATRM,405650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almHigh.ALDL,405660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almHigh.ATRM,405662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almLow.ALDL,405672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almLow.ATRM,405674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almLowLow.ALDL,405684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almLowLow.ATRM,405686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almBrokenLoop.ALDL,405696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almBrokenLoop.ATRM,405698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almOverRange.ALDL,405708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almOverRange.ATRM,405710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almUnderRange.ALDL,405720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almUnderRange.ATRM,405722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almRateOfChange.ALDL,405732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almRateOfChange.ATRM,405734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZI.almPLCFault.ALDL,405744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZI.almPLCFault.ATRM,405746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almHighHigh.ALDL,405848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almHighHigh.ATRM,405850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almHigh.ALDL,405860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almHigh.ATRM,405862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almLow.ALDL,405872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almLow.ATRM,405874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almLowLow.ALDL,405884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almLowLow.ATRM,405886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almBrokenLoop.ALDL,405896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almBrokenLoop.ATRM,405898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almOverRange.ALDL,405908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almOverRange.ATRM,405910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almUnderRange.ALDL,405920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almUnderRange.ATRM,405922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almRateOfChange.ALDL,405932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almRateOfChange.ATRM,405934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZI.almPLCFault.ALDL,405944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZI.almPLCFault.ATRM,405946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almHighHigh.ALDL,406048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almHighHigh.ATRM,406050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almHigh.ALDL,406060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almHigh.ATRM,406062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almLow.ALDL,406072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almLow.ATRM,406074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almLowLow.ALDL,406084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almLowLow.ATRM,406086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almBrokenLoop.ALDL,406096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almBrokenLoop.ATRM,406098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almOverRange.ALDL,406108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almOverRange.ATRM,406110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almUnderRange.ALDL,406120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almUnderRange.ATRM,406122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almRateOfChange.ALDL,406132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almRateOfChange.ATRM,406134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZI.almPLCFault.ALDL,406144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZI.almPLCFault.ATRM,406146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almHighHigh.ALDL,406248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almHighHigh.ATRM,406250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almHigh.ALDL,406260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almHigh.ATRM,406262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almLow.ALDL,406272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almLow.ATRM,406274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almLowLow.ALDL,406284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almLowLow.ATRM,406286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almBrokenLoop.ALDL,406296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almBrokenLoop.ATRM,406298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almOverRange.ALDL,406308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almOverRange.ATRM,406310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almUnderRange.ALDL,406320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almUnderRange.ATRM,406322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almRateOfChange.ALDL,406332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almRateOfChange.ATRM,406334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZI.almPLCFault.ALDL,406344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZI.almPLCFault.ATRM,406346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almHighHigh.ALDL,406448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almHighHigh.ATRM,406450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almHigh.ALDL,406460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almHigh.ATRM,406462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almLow.ALDL,406472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almLow.ATRM,406474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almLowLow.ALDL,406484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almLowLow.ATRM,406486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almBrokenLoop.ALDL,406496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almBrokenLoop.ATRM,406498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almOverRange.ALDL,406508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almOverRange.ATRM,406510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almUnderRange.ALDL,406520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almUnderRange.ATRM,406522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almRateOfChange.ALDL,406532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almRateOfChange.ATRM,406534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZI.almPLCFault.ALDL,406544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZI.almPLCFault.ATRM,406546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almHighHigh.ALDL,406648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almHighHigh.ATRM,406650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almHigh.ALDL,406660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almHigh.ATRM,406662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almLow.ALDL,406672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almLow.ATRM,406674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almLowLow.ALDL,406684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almLowLow.ATRM,406686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almBrokenLoop.ALDL,406696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almBrokenLoop.ATRM,406698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almOverRange.ALDL,406708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almOverRange.ATRM,406710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almUnderRange.ALDL,406720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almUnderRange.ATRM,406722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almRateOfChange.ALDL,406732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almRateOfChange.ATRM,406734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZI.almPLCFault.ALDL,406744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZI.almPLCFault.ATRM,406746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almHighHigh.ALDL,406848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almHighHigh.ATRM,406850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almHigh.ALDL,406860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almHigh.ATRM,406862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almLow.ALDL,406872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almLow.ATRM,406874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almLowLow.ALDL,406884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almLowLow.ATRM,406886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almBrokenLoop.ALDL,406896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almBrokenLoop.ATRM,406898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almOverRange.ALDL,406908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almOverRange.ATRM,406910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almUnderRange.ALDL,406920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almUnderRange.ATRM,406922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almRateOfChange.ALDL,406932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almRateOfChange.ATRM,406934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZI.almPLCFault.ALDL,406944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZI.almPLCFault.ATRM,406946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almHighHigh.ALDL,407048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almHighHigh.ATRM,407050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almHigh.ALDL,407060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almHigh.ATRM,407062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almLow.ALDL,407072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almLow.ATRM,407074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almLowLow.ALDL,407084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almLowLow.ATRM,407086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almBrokenLoop.ALDL,407096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almBrokenLoop.ATRM,407098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almOverRange.ALDL,407108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almOverRange.ATRM,407110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almUnderRange.ALDL,407120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almUnderRange.ATRM,407122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almRateOfChange.ALDL,407132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almRateOfChange.ATRM,407134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI1.almPLCFault.ALDL,407144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI1.almPLCFault.ATRM,407146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almHighHigh.ALDL,407248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almHighHigh.ATRM,407250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almHigh.ALDL,407260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almHigh.ATRM,407262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almLow.ALDL,407272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almLow.ATRM,407274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almLowLow.ALDL,407284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almLowLow.ATRM,407286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almBrokenLoop.ALDL,407296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almBrokenLoop.ATRM,407298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almOverRange.ALDL,407308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almOverRange.ATRM,407310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almUnderRange.ALDL,407320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almUnderRange.ATRM,407322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almRateOfChange.ALDL,407332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almRateOfChange.ATRM,407334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI2.almPLCFault.ALDL,407344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI2.almPLCFault.ATRM,407346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almHighHigh.ALDL,407448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almHighHigh.ATRM,407450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almHigh.ALDL,407460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almHigh.ATRM,407462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almLow.ALDL,407472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almLow.ATRM,407474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almLowLow.ALDL,407484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almLowLow.ATRM,407486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almBrokenLoop.ALDL,407496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almBrokenLoop.ATRM,407498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almOverRange.ALDL,407508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almOverRange.ATRM,407510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almUnderRange.ALDL,407520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almUnderRange.ATRM,407522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almRateOfChange.ALDL,407532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almRateOfChange.ATRM,407534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI3.almPLCFault.ALDL,407544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI3.almPLCFault.ATRM,407546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almHighHigh.ALDL,407648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almHighHigh.ATRM,407650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almHigh.ALDL,407660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almHigh.ATRM,407662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almLow.ALDL,407672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almLow.ATRM,407674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almLowLow.ALDL,407684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almLowLow.ATRM,407686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almBrokenLoop.ALDL,407696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almBrokenLoop.ATRM,407698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almOverRange.ALDL,407708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almOverRange.ATRM,407710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almUnderRange.ALDL,407720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almUnderRange.ATRM,407722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almRateOfChange.ALDL,407732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almRateOfChange.ATRM,407734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_1_VI4.almPLCFault.ALDL,407744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_1_VI4.almPLCFault.ATRM,407746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almHighHigh.ALDL,407848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almHighHigh.ATRM,407850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almHigh.ALDL,407860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almHigh.ATRM,407862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almLow.ALDL,407872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almLow.ATRM,407874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almLowLow.ALDL,407884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almLowLow.ATRM,407886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almBrokenLoop.ALDL,407896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almBrokenLoop.ATRM,407898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almOverRange.ALDL,407908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almOverRange.ATRM,407910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almUnderRange.ALDL,407920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almUnderRange.ATRM,407922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almRateOfChange.ALDL,407932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almRateOfChange.ATRM,407934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI1.almPLCFault.ALDL,407944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI1.almPLCFault.ATRM,407946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almHighHigh.ALDL,408048,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almHighHigh.ATRM,408050,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almHigh.ALDL,408060,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almHigh.ATRM,408062,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almLow.ALDL,408072,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almLow.ATRM,408074,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almLowLow.ALDL,408084,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almLowLow.ATRM,408086,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almBrokenLoop.ALDL,408096,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almBrokenLoop.ATRM,408098,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almOverRange.ALDL,408108,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almOverRange.ATRM,408110,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almUnderRange.ALDL,408120,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almUnderRange.ATRM,408122,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almRateOfChange.ALDL,408132,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almRateOfChange.ATRM,408134,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI2.almPLCFault.ALDL,408144,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI2.almPLCFault.ATRM,408146,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almHighHigh.ALDL,408248,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almHighHigh.ATRM,408250,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almHigh.ALDL,408260,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almHigh.ATRM,408262,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almLow.ALDL,408272,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almLow.ATRM,408274,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almLowLow.ALDL,408284,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almLowLow.ATRM,408286,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almBrokenLoop.ALDL,408296,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almBrokenLoop.ATRM,408298,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almOverRange.ALDL,408308,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almOverRange.ATRM,408310,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almUnderRange.ALDL,408320,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almUnderRange.ATRM,408322,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almRateOfChange.ALDL,408332,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almRateOfChange.ATRM,408334,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI3.almPLCFault.ALDL,408344,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI3.almPLCFault.ATRM,408346,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almHighHigh.ALDL,408448,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almHighHigh.ATRM,408450,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almHigh.ALDL,408460,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almHigh.ATRM,408462,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almLow.ALDL,408472,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almLow.ATRM,408474,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almLowLow.ALDL,408484,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almLowLow.ATRM,408486,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almBrokenLoop.ALDL,408496,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almBrokenLoop.ATRM,408498,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almOverRange.ALDL,408508,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almOverRange.ATRM,408510,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almUnderRange.ALDL,408520,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almUnderRange.ATRM,408522,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almRateOfChange.ALDL,408532,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almRateOfChange.ATRM,408534,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_2_VI4.almPLCFault.ALDL,408544,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_2_VI4.almPLCFault.ATRM,408546,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almHighHigh.ALDL,408648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almHighHigh.ATRM,408650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almHigh.ALDL,408660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almHigh.ATRM,408662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almLow.ALDL,408672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almLow.ATRM,408674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almLowLow.ALDL,408684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almLowLow.ATRM,408686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almBrokenLoop.ALDL,408696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almBrokenLoop.ATRM,408698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almOverRange.ALDL,408708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almOverRange.ATRM,408710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almUnderRange.ALDL,408720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almUnderRange.ATRM,408722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almRateOfChange.ALDL,408732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almRateOfChange.ATRM,408734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI1.almPLCFault.ALDL,408744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI1.almPLCFault.ATRM,408746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almHighHigh.ALDL,408848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almHighHigh.ATRM,408850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almHigh.ALDL,408860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almHigh.ATRM,408862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almLow.ALDL,408872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almLow.ATRM,408874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almLowLow.ALDL,408884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almLowLow.ATRM,408886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almBrokenLoop.ALDL,408896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almBrokenLoop.ATRM,408898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almOverRange.ALDL,408908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almOverRange.ATRM,408910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almUnderRange.ALDL,408920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almUnderRange.ATRM,408922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almRateOfChange.ALDL,408932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almRateOfChange.ATRM,408934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI2.almPLCFault.ALDL,408944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI2.almPLCFault.ATRM,408946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almHighHigh.ALDL,409048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almHighHigh.ATRM,409050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almHigh.ALDL,409060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almHigh.ATRM,409062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almLow.ALDL,409072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almLow.ATRM,409074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almLowLow.ALDL,409084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almLowLow.ATRM,409086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almBrokenLoop.ALDL,409096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almBrokenLoop.ATRM,409098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almOverRange.ALDL,409108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almOverRange.ATRM,409110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almUnderRange.ALDL,409120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almUnderRange.ATRM,409122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almRateOfChange.ALDL,409132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almRateOfChange.ATRM,409134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI3.almPLCFault.ALDL,409144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI3.almPLCFault.ATRM,409146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almHighHigh.ALDL,409248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almHighHigh.ATRM,409250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almHigh.ALDL,409260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almHigh.ATRM,409262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almLow.ALDL,409272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almLow.ATRM,409274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almLowLow.ALDL,409284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almLowLow.ATRM,409286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almBrokenLoop.ALDL,409296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almBrokenLoop.ATRM,409298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almOverRange.ALDL,409308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almOverRange.ATRM,409310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almUnderRange.ALDL,409320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almUnderRange.ATRM,409322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almRateOfChange.ALDL,409332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almRateOfChange.ATRM,409334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_3_VI4.almPLCFault.ALDL,409344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_3_VI4.almPLCFault.ATRM,409346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almHighHigh.ALDL,409448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almHighHigh.ATRM,409450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almHigh.ALDL,409460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almHigh.ATRM,409462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almLow.ALDL,409472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almLow.ATRM,409474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almLowLow.ALDL,409484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almLowLow.ATRM,409486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almBrokenLoop.ALDL,409496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almBrokenLoop.ATRM,409498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almOverRange.ALDL,409508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almOverRange.ATRM,409510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almUnderRange.ALDL,409520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almUnderRange.ATRM,409522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almRateOfChange.ALDL,409532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almRateOfChange.ATRM,409534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI1.almPLCFault.ALDL,409544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI1.almPLCFault.ATRM,409546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almHighHigh.ALDL,409648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almHighHigh.ATRM,409650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almHigh.ALDL,409660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almHigh.ATRM,409662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almLow.ALDL,409672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almLow.ATRM,409674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almLowLow.ALDL,409684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almLowLow.ATRM,409686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almBrokenLoop.ALDL,409696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almBrokenLoop.ATRM,409698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almOverRange.ALDL,409708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almOverRange.ATRM,409710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almUnderRange.ALDL,409720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almUnderRange.ATRM,409722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almRateOfChange.ALDL,409732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almRateOfChange.ATRM,409734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI2.almPLCFault.ALDL,409744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI2.almPLCFault.ATRM,409746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almHighHigh.ALDL,409848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almHighHigh.ATRM,409850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almHigh.ALDL,409860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almHigh.ATRM,409862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almLow.ALDL,409872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almLow.ATRM,409874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almLowLow.ALDL,409884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almLowLow.ATRM,409886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almBrokenLoop.ALDL,409896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almBrokenLoop.ATRM,409898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almOverRange.ALDL,409908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almOverRange.ATRM,409910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almUnderRange.ALDL,409920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almUnderRange.ATRM,409922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almRateOfChange.ALDL,409932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almRateOfChange.ATRM,409934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI3.almPLCFault.ALDL,409944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI3.almPLCFault.ATRM,409946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almHighHigh.ALDL,410048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almHighHigh.ATRM,410050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almHigh.ALDL,410060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almHigh.ATRM,410062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almLow.ALDL,410072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almLow.ATRM,410074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almLowLow.ALDL,410084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almLowLow.ATRM,410086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almBrokenLoop.ALDL,410096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almBrokenLoop.ATRM,410098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almOverRange.ALDL,410108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almOverRange.ATRM,410110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almUnderRange.ALDL,410120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almUnderRange.ATRM,410122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almRateOfChange.ALDL,410132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almRateOfChange.ATRM,410134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_4_VI4.almPLCFault.ALDL,410144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_4_VI4.almPLCFault.ATRM,410146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almHighHigh.ALDL,410248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almHighHigh.ATRM,410250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almHigh.ALDL,410260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almHigh.ATRM,410262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almLow.ALDL,410272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almLow.ATRM,410274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almLowLow.ALDL,410284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almLowLow.ATRM,410286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almBrokenLoop.ALDL,410296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almBrokenLoop.ATRM,410298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almOverRange.ALDL,410308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almOverRange.ATRM,410310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almUnderRange.ALDL,410320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almUnderRange.ATRM,410322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almRateOfChange.ALDL,410332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almRateOfChange.ATRM,410334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI1.almPLCFault.ALDL,410344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI1.almPLCFault.ATRM,410346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almHighHigh.ALDL,410448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almHighHigh.ATRM,410450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almHigh.ALDL,410460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almHigh.ATRM,410462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almLow.ALDL,410472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almLow.ATRM,410474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almLowLow.ALDL,410484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almLowLow.ATRM,410486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almBrokenLoop.ALDL,410496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almBrokenLoop.ATRM,410498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almOverRange.ALDL,410508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almOverRange.ATRM,410510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almUnderRange.ALDL,410520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almUnderRange.ATRM,410522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almRateOfChange.ALDL,410532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almRateOfChange.ATRM,410534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI2.almPLCFault.ALDL,410544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI2.almPLCFault.ATRM,410546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almHighHigh.ALDL,410648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almHighHigh.ATRM,410650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almHigh.ALDL,410660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almHigh.ATRM,410662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almLow.ALDL,410672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almLow.ATRM,410674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almLowLow.ALDL,410684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almLowLow.ATRM,410686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almBrokenLoop.ALDL,410696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almBrokenLoop.ATRM,410698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almOverRange.ALDL,410708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almOverRange.ATRM,410710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almUnderRange.ALDL,410720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almUnderRange.ATRM,410722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almRateOfChange.ALDL,410732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almRateOfChange.ATRM,410734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI3.almPLCFault.ALDL,410744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI3.almPLCFault.ATRM,410746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almHighHigh.ALDL,410848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almHighHigh.ATRM,410850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almHigh.ALDL,410860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almHigh.ATRM,410862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almLow.ALDL,410872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almLow.ATRM,410874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almLowLow.ALDL,410884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almLowLow.ATRM,410886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almBrokenLoop.ALDL,410896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almBrokenLoop.ATRM,410898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almOverRange.ALDL,410908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almOverRange.ATRM,410910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almUnderRange.ALDL,410920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almUnderRange.ATRM,410922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almRateOfChange.ALDL,410932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almRateOfChange.ATRM,410934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_5_VI4.almPLCFault.ALDL,410944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_5_VI4.almPLCFault.ATRM,410946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almHighHigh.ALDL,411048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almHighHigh.ATRM,411050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almHigh.ALDL,411060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almHigh.ATRM,411062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almLow.ALDL,411072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almLow.ATRM,411074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almLowLow.ALDL,411084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almLowLow.ATRM,411086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almBrokenLoop.ALDL,411096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almBrokenLoop.ATRM,411098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almOverRange.ALDL,411108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almOverRange.ATRM,411110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almUnderRange.ALDL,411120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almUnderRange.ATRM,411122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almRateOfChange.ALDL,411132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almRateOfChange.ATRM,411134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI1.almPLCFault.ALDL,411144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI1.almPLCFault.ATRM,411146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almHighHigh.ALDL,411248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almHighHigh.ATRM,411250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almHigh.ALDL,411260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almHigh.ATRM,411262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almLow.ALDL,411272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almLow.ATRM,411274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almLowLow.ALDL,411284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almLowLow.ATRM,411286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almBrokenLoop.ALDL,411296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almBrokenLoop.ATRM,411298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almOverRange.ALDL,411308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almOverRange.ATRM,411310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almUnderRange.ALDL,411320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almUnderRange.ATRM,411322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almRateOfChange.ALDL,411332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almRateOfChange.ATRM,411334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI2.almPLCFault.ALDL,411344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI2.almPLCFault.ATRM,411346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almHighHigh.ALDL,411448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almHighHigh.ATRM,411450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almHigh.ALDL,411460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almHigh.ATRM,411462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almLow.ALDL,411472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almLow.ATRM,411474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almLowLow.ALDL,411484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almLowLow.ATRM,411486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almBrokenLoop.ALDL,411496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almBrokenLoop.ATRM,411498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almOverRange.ALDL,411508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almOverRange.ATRM,411510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almUnderRange.ALDL,411520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almUnderRange.ATRM,411522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almRateOfChange.ALDL,411532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almRateOfChange.ATRM,411534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI3.almPLCFault.ALDL,411544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI3.almPLCFault.ATRM,411546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almHighHigh.ALDL,411648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almHighHigh.ATRM,411650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almHigh.ALDL,411660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almHigh.ATRM,411662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almLow.ALDL,411672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almLow.ATRM,411674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almLowLow.ALDL,411684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almLowLow.ATRM,411686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almBrokenLoop.ALDL,411696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almBrokenLoop.ATRM,411698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almOverRange.ALDL,411708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almOverRange.ATRM,411710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almUnderRange.ALDL,411720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almUnderRange.ATRM,411722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almRateOfChange.ALDL,411732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almRateOfChange.ATRM,411734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_6_VI4.almPLCFault.ALDL,411744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_6_VI4.almPLCFault.ATRM,411746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almHighHigh.ALDL,411848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almHighHigh.ATRM,411850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almHigh.ALDL,411860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almHigh.ATRM,411862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almLow.ALDL,411872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almLow.ATRM,411874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almLowLow.ALDL,411884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almLowLow.ATRM,411886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almBrokenLoop.ALDL,411896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almBrokenLoop.ATRM,411898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almOverRange.ALDL,411908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almOverRange.ATRM,411910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almUnderRange.ALDL,411920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almUnderRange.ATRM,411922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almRateOfChange.ALDL,411932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almRateOfChange.ATRM,411934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI1.almPLCFault.ALDL,411944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI1.almPLCFault.ATRM,411946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almHighHigh.ALDL,412048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almHighHigh.ATRM,412050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almHigh.ALDL,412060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almHigh.ATRM,412062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almLow.ALDL,412072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almLow.ATRM,412074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almLowLow.ALDL,412084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almLowLow.ATRM,412086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almBrokenLoop.ALDL,412096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almBrokenLoop.ATRM,412098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almOverRange.ALDL,412108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almOverRange.ATRM,412110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almUnderRange.ALDL,412120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almUnderRange.ATRM,412122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almRateOfChange.ALDL,412132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almRateOfChange.ATRM,412134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI2.almPLCFault.ALDL,412144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI2.almPLCFault.ATRM,412146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almHighHigh.ALDL,412248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almHighHigh.ATRM,412250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almHigh.ALDL,412260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almHigh.ATRM,412262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almLow.ALDL,412272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almLow.ATRM,412274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almLowLow.ALDL,412284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almLowLow.ATRM,412286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almBrokenLoop.ALDL,412296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almBrokenLoop.ATRM,412298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almOverRange.ALDL,412308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almOverRange.ATRM,412310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almUnderRange.ALDL,412320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almUnderRange.ATRM,412322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almRateOfChange.ALDL,412332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almRateOfChange.ATRM,412334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI3.almPLCFault.ALDL,412344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI3.almPLCFault.ATRM,412346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almHighHigh.ALDL,412448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almHighHigh.ATRM,412450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almHigh.ALDL,412460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almHigh.ATRM,412462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almLow.ALDL,412472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almLow.ATRM,412474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almLowLow.ALDL,412484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almLowLow.ATRM,412486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almBrokenLoop.ALDL,412496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almBrokenLoop.ATRM,412498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almOverRange.ALDL,412508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almOverRange.ATRM,412510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almUnderRange.ALDL,412520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almUnderRange.ATRM,412522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almRateOfChange.ALDL,412532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almRateOfChange.ATRM,412534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_7_VI4.almPLCFault.ALDL,412544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_7_VI4.almPLCFault.ATRM,412546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almHighHigh.ALDL,412648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almHighHigh.ATRM,412650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almHigh.ALDL,412660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almHigh.ATRM,412662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almLow.ALDL,412672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almLow.ATRM,412674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almLowLow.ALDL,412684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almLowLow.ATRM,412686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almBrokenLoop.ALDL,412696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almBrokenLoop.ATRM,412698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almOverRange.ALDL,412708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almOverRange.ATRM,412710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almUnderRange.ALDL,412720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almUnderRange.ATRM,412722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almRateOfChange.ALDL,412732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almRateOfChange.ATRM,412734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI1.almPLCFault.ALDL,412744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI1.almPLCFault.ATRM,412746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almHighHigh.ALDL,412848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almHighHigh.ATRM,412850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almHigh.ALDL,412860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almHigh.ATRM,412862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almLow.ALDL,412872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almLow.ATRM,412874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almLowLow.ALDL,412884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almLowLow.ATRM,412886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almBrokenLoop.ALDL,412896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almBrokenLoop.ATRM,412898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almOverRange.ALDL,412908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almOverRange.ATRM,412910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almUnderRange.ALDL,412920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almUnderRange.ATRM,412922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almRateOfChange.ALDL,412932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almRateOfChange.ATRM,412934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI2.almPLCFault.ALDL,412944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI2.almPLCFault.ATRM,412946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almHighHigh.ALDL,413048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almHighHigh.ATRM,413050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almHigh.ALDL,413060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almHigh.ATRM,413062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almLow.ALDL,413072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almLow.ATRM,413074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almLowLow.ALDL,413084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almLowLow.ATRM,413086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almBrokenLoop.ALDL,413096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almBrokenLoop.ATRM,413098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almOverRange.ALDL,413108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almOverRange.ATRM,413110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almUnderRange.ALDL,413120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almUnderRange.ATRM,413122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almRateOfChange.ALDL,413132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almRateOfChange.ATRM,413134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI3.almPLCFault.ALDL,413144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI3.almPLCFault.ATRM,413146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almHighHigh.ALDL,413248,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almHighHigh.ATRM,413250,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almHigh.ALDL,413260,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almHigh.ATRM,413262,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almLow.ALDL,413272,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almLow.ATRM,413274,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almLowLow.ALDL,413284,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almLowLow.ATRM,413286,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almBrokenLoop.ALDL,413296,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almBrokenLoop.ATRM,413298,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almOverRange.ALDL,413308,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almOverRange.ATRM,413310,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almUnderRange.ALDL,413320,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almUnderRange.ATRM,413322,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almRateOfChange.ALDL,413332,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almRateOfChange.ATRM,413334,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_8_VI4.almPLCFault.ALDL,413344,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_8_VI4.almPLCFault.ATRM,413346,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almHighHigh.ALDL,413448,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almHighHigh.ATRM,413450,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almHigh.ALDL,413460,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almHigh.ATRM,413462,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almLow.ALDL,413472,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almLow.ATRM,413474,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almLowLow.ALDL,413484,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almLowLow.ATRM,413486,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almBrokenLoop.ALDL,413496,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almBrokenLoop.ATRM,413498,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almOverRange.ALDL,413508,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almOverRange.ATRM,413510,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almUnderRange.ALDL,413520,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almUnderRange.ATRM,413522,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almRateOfChange.ALDL,413532,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almRateOfChange.ATRM,413534,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI1.almPLCFault.ALDL,413544,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI1.almPLCFault.ATRM,413546,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almHighHigh.ALDL,413648,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almHighHigh.ATRM,413650,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almHigh.ALDL,413660,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almHigh.ATRM,413662,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almLow.ALDL,413672,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almLow.ATRM,413674,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almLowLow.ALDL,413684,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almLowLow.ATRM,413686,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almBrokenLoop.ALDL,413696,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almBrokenLoop.ATRM,413698,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almOverRange.ALDL,413708,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almOverRange.ATRM,413710,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almUnderRange.ALDL,413720,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almUnderRange.ATRM,413722,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almRateOfChange.ALDL,413732,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almRateOfChange.ATRM,413734,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI2.almPLCFault.ALDL,413744,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI2.almPLCFault.ATRM,413746,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almHighHigh.ALDL,413848,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almHighHigh.ATRM,413850,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almHigh.ALDL,413860,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almHigh.ATRM,413862,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almLow.ALDL,413872,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almLow.ATRM,413874,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almLowLow.ALDL,413884,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almLowLow.ATRM,413886,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almBrokenLoop.ALDL,413896,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almBrokenLoop.ATRM,413898,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almOverRange.ALDL,413908,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almOverRange.ATRM,413910,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almUnderRange.ALDL,413920,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almUnderRange.ATRM,413922,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almRateOfChange.ALDL,413932,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almRateOfChange.ATRM,413934,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI3.almPLCFault.ALDL,413944,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI3.almPLCFault.ATRM,413946,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almHighHigh.ALDL,414048,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almHighHigh.ATRM,414050,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almHigh.ALDL,414060,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almHigh.ATRM,414062,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almLow.ALDL,414072,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almLow.ATRM,414074,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almLowLow.ALDL,414084,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almLowLow.ATRM,414086,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almBrokenLoop.ALDL,414096,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almBrokenLoop.ATRM,414098,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almOverRange.ALDL,414108,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almOverRange.ATRM,414110,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almUnderRange.ALDL,414120,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almUnderRange.ATRM,414122,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almRateOfChange.ALDL,414132,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almRateOfChange.ATRM,414134,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_MTR_0103_9_VI4.almPLCFault.ALDL,414144,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_MTR_0103_9_VI4.almPLCFault.ATRM,414146,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almHighHigh.ALDL,414248,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almHighHigh.ATRM,414250,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almHigh.ALDL,414260,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almHigh.ATRM,414262,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almLow.ALDL,414272,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almLow.ATRM,414274,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almLowLow.ALDL,414284,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almLowLow.ATRM,414286,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almBrokenLoop.ALDL,414296,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almBrokenLoop.ATRM,414298,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almOverRange.ALDL,414308,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almOverRange.ATRM,414310,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almUnderRange.ALDL,414320,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almUnderRange.ATRM,414322,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almRateOfChange.ALDL,414332,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almRateOfChange.ATRM,414334,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PI.almPLCFault.ALDL,414344,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PI.almPLCFault.ATRM,414346,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almHighHigh.ALDL,414448,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almHighHigh.ATRM,414450,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almHigh.ALDL,414460,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almHigh.ATRM,414462,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almLow.ALDL,414472,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almLow.ATRM,414474,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almLowLow.ALDL,414484,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almLowLow.ATRM,414486,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almBrokenLoop.ALDL,414496,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almBrokenLoop.ATRM,414498,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almOverRange.ALDL,414508,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almOverRange.ATRM,414510,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almUnderRange.ALDL,414520,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almUnderRange.ATRM,414522,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almRateOfChange.ALDL,414532,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almRateOfChange.ATRM,414534,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PI.almPLCFault.ALDL,414544,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PI.almPLCFault.ATRM,414546,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almHighHigh.ALDL,414648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almHighHigh.ATRM,414650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almHigh.ALDL,414660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almHigh.ATRM,414662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almLow.ALDL,414672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almLow.ATRM,414674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almLowLow.ALDL,414684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almLowLow.ATRM,414686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almBrokenLoop.ALDL,414696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almBrokenLoop.ATRM,414698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almOverRange.ALDL,414708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almOverRange.ATRM,414710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almUnderRange.ALDL,414720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almUnderRange.ATRM,414722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almRateOfChange.ALDL,414732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almRateOfChange.ATRM,414734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_1_PI.almPLCFault.ALDL,414744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_1_PI.almPLCFault.ATRM,414746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almHighHigh.ALDL,414848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almHighHigh.ATRM,414850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almHigh.ALDL,414860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almHigh.ATRM,414862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almLow.ALDL,414872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almLow.ATRM,414874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almLowLow.ALDL,414884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almLowLow.ATRM,414886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almBrokenLoop.ALDL,414896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almBrokenLoop.ATRM,414898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almOverRange.ALDL,414908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almOverRange.ATRM,414910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almUnderRange.ALDL,414920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almUnderRange.ATRM,414922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almRateOfChange.ALDL,414932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almRateOfChange.ATRM,414934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_2_PI.almPLCFault.ALDL,414944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_2_PI.almPLCFault.ATRM,414946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almHighHigh.ALDL,415048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almHighHigh.ATRM,415050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almHigh.ALDL,415060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almHigh.ATRM,415062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almLow.ALDL,415072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almLow.ATRM,415074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almLowLow.ALDL,415084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almLowLow.ATRM,415086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almBrokenLoop.ALDL,415096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almBrokenLoop.ATRM,415098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almOverRange.ALDL,415108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almOverRange.ATRM,415110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almUnderRange.ALDL,415120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almUnderRange.ATRM,415122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almRateOfChange.ALDL,415132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almRateOfChange.ATRM,415134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_3_PI.almPLCFault.ALDL,415144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_3_PI.almPLCFault.ATRM,415146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almHighHigh.ALDL,415248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almHighHigh.ATRM,415250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almHigh.ALDL,415260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almHigh.ATRM,415262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almLow.ALDL,415272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almLow.ATRM,415274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almLowLow.ALDL,415284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almLowLow.ATRM,415286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almBrokenLoop.ALDL,415296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almBrokenLoop.ATRM,415298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almOverRange.ALDL,415308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almOverRange.ATRM,415310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almUnderRange.ALDL,415320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almUnderRange.ATRM,415322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almRateOfChange.ALDL,415332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almRateOfChange.ATRM,415334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_4_PI.almPLCFault.ALDL,415344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_4_PI.almPLCFault.ATRM,415346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almHighHigh.ALDL,415448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almHighHigh.ATRM,415450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almHigh.ALDL,415460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almHigh.ATRM,415462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almLow.ALDL,415472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almLow.ATRM,415474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almLowLow.ALDL,415484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almLowLow.ATRM,415486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almBrokenLoop.ALDL,415496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almBrokenLoop.ATRM,415498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almOverRange.ALDL,415508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almOverRange.ATRM,415510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almUnderRange.ALDL,415520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almUnderRange.ATRM,415522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almRateOfChange.ALDL,415532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almRateOfChange.ATRM,415534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_5_PI.almPLCFault.ALDL,415544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_5_PI.almPLCFault.ATRM,415546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almHighHigh.ALDL,415648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almHighHigh.ATRM,415650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almHigh.ALDL,415660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almHigh.ATRM,415662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almLow.ALDL,415672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almLow.ATRM,415674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almLowLow.ALDL,415684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almLowLow.ATRM,415686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almBrokenLoop.ALDL,415696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almBrokenLoop.ATRM,415698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almOverRange.ALDL,415708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almOverRange.ATRM,415710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almUnderRange.ALDL,415720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almUnderRange.ATRM,415722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almRateOfChange.ALDL,415732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almRateOfChange.ATRM,415734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_6_PI.almPLCFault.ALDL,415744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_6_PI.almPLCFault.ATRM,415746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almHighHigh.ALDL,415848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almHighHigh.ATRM,415850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almHigh.ALDL,415860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almHigh.ATRM,415862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almLow.ALDL,415872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almLow.ATRM,415874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almLowLow.ALDL,415884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almLowLow.ATRM,415886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almBrokenLoop.ALDL,415896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almBrokenLoop.ATRM,415898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almOverRange.ALDL,415908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almOverRange.ATRM,415910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almUnderRange.ALDL,415920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almUnderRange.ATRM,415922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almRateOfChange.ALDL,415932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almRateOfChange.ATRM,415934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_7_PI.almPLCFault.ALDL,415944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_7_PI.almPLCFault.ATRM,415946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almHighHigh.ALDL,416048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almHighHigh.ATRM,416050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almHigh.ALDL,416060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almHigh.ATRM,416062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almLow.ALDL,416072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almLow.ATRM,416074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almLowLow.ALDL,416084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almLowLow.ATRM,416086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almBrokenLoop.ALDL,416096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almBrokenLoop.ATRM,416098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almOverRange.ALDL,416108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almOverRange.ATRM,416110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almUnderRange.ALDL,416120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almUnderRange.ATRM,416122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almRateOfChange.ALDL,416132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almRateOfChange.ATRM,416134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_8_PI.almPLCFault.ALDL,416144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_8_PI.almPLCFault.ATRM,416146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almHighHigh.ALDL,416248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almHighHigh.ATRM,416250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almHigh.ALDL,416260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almHigh.ATRM,416262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almLow.ALDL,416272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almLow.ATRM,416274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almLowLow.ALDL,416284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almLowLow.ATRM,416286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almBrokenLoop.ALDL,416296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almBrokenLoop.ATRM,416298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almOverRange.ALDL,416308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almOverRange.ATRM,416310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almUnderRange.ALDL,416320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almUnderRange.ATRM,416322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almRateOfChange.ALDL,416332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almRateOfChange.ATRM,416334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0103_9_PI.almPLCFault.ALDL,416344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0103_9_PI.almPLCFault.ATRM,416346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almHighHigh.ALDL,416448,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almHighHigh.ATRM,416450,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almHigh.ALDL,416460,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almHigh.ATRM,416462,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almLow.ALDL,416472,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almLow.ATRM,416474,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almLowLow.ALDL,416484,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almLowLow.ATRM,416486,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almBrokenLoop.ALDL,416496,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almBrokenLoop.ATRM,416498,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almOverRange.ALDL,416508,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almOverRange.ATRM,416510,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almUnderRange.ALDL,416520,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almUnderRange.ATRM,416522,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almRateOfChange.ALDL,416532,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almRateOfChange.ATRM,416534,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0104_1_PI.almPLCFault.ALDL,416544,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0104_1_PI.almPLCFault.ATRM,416546,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almHighHigh.ALDL,416648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almHighHigh.ATRM,416650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almHigh.ALDL,416660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almHigh.ATRM,416662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almLow.ALDL,416672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almLow.ATRM,416674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almLowLow.ALDL,416684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almLowLow.ATRM,416686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almBrokenLoop.ALDL,416696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almBrokenLoop.ATRM,416698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almOverRange.ALDL,416708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almOverRange.ATRM,416710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almUnderRange.ALDL,416720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almUnderRange.ATRM,416722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almRateOfChange.ALDL,416732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almRateOfChange.ATRM,416734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI1.almPLCFault.ALDL,416744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI1.almPLCFault.ATRM,416746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almHighHigh.ALDL,416848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almHighHigh.ATRM,416850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almHigh.ALDL,416860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almHigh.ATRM,416862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almLow.ALDL,416872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almLow.ATRM,416874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almLowLow.ALDL,416884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almLowLow.ATRM,416886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almBrokenLoop.ALDL,416896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almBrokenLoop.ATRM,416898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almOverRange.ALDL,416908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almOverRange.ATRM,416910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almUnderRange.ALDL,416920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almUnderRange.ATRM,416922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almRateOfChange.ALDL,416932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almRateOfChange.ATRM,416934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI2.almPLCFault.ALDL,416944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI2.almPLCFault.ATRM,416946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almHighHigh.ALDL,417048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almHighHigh.ATRM,417050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almHigh.ALDL,417060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almHigh.ATRM,417062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almLow.ALDL,417072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almLow.ATRM,417074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almLowLow.ALDL,417084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almLowLow.ATRM,417086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almBrokenLoop.ALDL,417096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almBrokenLoop.ATRM,417098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almOverRange.ALDL,417108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almOverRange.ATRM,417110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almUnderRange.ALDL,417120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almUnderRange.ATRM,417122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almRateOfChange.ALDL,417132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almRateOfChange.ATRM,417134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI3.almPLCFault.ALDL,417144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI3.almPLCFault.ATRM,417146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almHighHigh.ALDL,417248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almHighHigh.ATRM,417250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almHigh.ALDL,417260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almHigh.ATRM,417262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almLow.ALDL,417272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almLow.ATRM,417274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almLowLow.ALDL,417284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almLowLow.ATRM,417286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almBrokenLoop.ALDL,417296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almBrokenLoop.ATRM,417298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almOverRange.ALDL,417308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almOverRange.ATRM,417310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almUnderRange.ALDL,417320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almUnderRange.ATRM,417322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almRateOfChange.ALDL,417332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almRateOfChange.ATRM,417334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI4.almPLCFault.ALDL,417344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI4.almPLCFault.ATRM,417346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almHighHigh.ALDL,417448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almHighHigh.ATRM,417450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almHigh.ALDL,417460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almHigh.ATRM,417462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almLow.ALDL,417472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almLow.ATRM,417474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almLowLow.ALDL,417484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almLowLow.ATRM,417486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almBrokenLoop.ALDL,417496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almBrokenLoop.ATRM,417498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almOverRange.ALDL,417508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almOverRange.ATRM,417510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almUnderRange.ALDL,417520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almUnderRange.ATRM,417522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almRateOfChange.ALDL,417532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almRateOfChange.ATRM,417534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_1_VI5.almPLCFault.ALDL,417544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_1_VI5.almPLCFault.ATRM,417546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almHighHigh.ALDL,417648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almHighHigh.ATRM,417650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almHigh.ALDL,417660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almHigh.ATRM,417662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almLow.ALDL,417672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almLow.ATRM,417674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almLowLow.ALDL,417684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almLowLow.ATRM,417686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almBrokenLoop.ALDL,417696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almBrokenLoop.ATRM,417698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almOverRange.ALDL,417708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almOverRange.ATRM,417710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almUnderRange.ALDL,417720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almUnderRange.ATRM,417722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almRateOfChange.ALDL,417732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almRateOfChange.ATRM,417734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI1.almPLCFault.ALDL,417744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI1.almPLCFault.ATRM,417746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almHighHigh.ALDL,417848,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almHighHigh.ATRM,417850,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almHigh.ALDL,417860,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almHigh.ATRM,417862,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almLow.ALDL,417872,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almLow.ATRM,417874,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almLowLow.ALDL,417884,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almLowLow.ATRM,417886,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almBrokenLoop.ALDL,417896,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almBrokenLoop.ATRM,417898,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almOverRange.ALDL,417908,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almOverRange.ATRM,417910,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almUnderRange.ALDL,417920,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almUnderRange.ATRM,417922,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almRateOfChange.ALDL,417932,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almRateOfChange.ATRM,417934,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI2.almPLCFault.ALDL,417944,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI2.almPLCFault.ATRM,417946,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almHighHigh.ALDL,418048,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almHighHigh.ATRM,418050,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almHigh.ALDL,418060,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almHigh.ATRM,418062,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almLow.ALDL,418072,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almLow.ATRM,418074,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almLowLow.ALDL,418084,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almLowLow.ATRM,418086,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almBrokenLoop.ALDL,418096,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almBrokenLoop.ATRM,418098,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almOverRange.ALDL,418108,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almOverRange.ATRM,418110,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almUnderRange.ALDL,418120,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almUnderRange.ATRM,418122,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almRateOfChange.ALDL,418132,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almRateOfChange.ATRM,418134,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI3.almPLCFault.ALDL,418144,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI3.almPLCFault.ATRM,418146,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almHighHigh.ALDL,418248,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almHighHigh.ATRM,418250,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almHigh.ALDL,418260,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almHigh.ATRM,418262,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almLow.ALDL,418272,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almLow.ATRM,418274,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almLowLow.ALDL,418284,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almLowLow.ATRM,418286,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almBrokenLoop.ALDL,418296,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almBrokenLoop.ATRM,418298,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almOverRange.ALDL,418308,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almOverRange.ATRM,418310,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almUnderRange.ALDL,418320,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almUnderRange.ATRM,418322,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almRateOfChange.ALDL,418332,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almRateOfChange.ATRM,418334,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI4.almPLCFault.ALDL,418344,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI4.almPLCFault.ATRM,418346,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almHighHigh.ALDL,418448,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almHighHigh.ATRM,418450,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almHigh.ALDL,418460,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almHigh.ATRM,418462,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almLow.ALDL,418472,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almLow.ATRM,418474,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almLowLow.ALDL,418484,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almLowLow.ATRM,418486,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almBrokenLoop.ALDL,418496,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almBrokenLoop.ATRM,418498,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almOverRange.ALDL,418508,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almOverRange.ATRM,418510,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almUnderRange.ALDL,418520,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almUnderRange.ATRM,418522,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almRateOfChange.ALDL,418532,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almRateOfChange.ATRM,418534,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_2_VI5.almPLCFault.ALDL,418544,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_2_VI5.almPLCFault.ATRM,418546,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almHighHigh.ALDL,418648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almHighHigh.ATRM,418650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almHigh.ALDL,418660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almHigh.ATRM,418662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almLow.ALDL,418672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almLow.ATRM,418674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almLowLow.ALDL,418684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almLowLow.ATRM,418686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almBrokenLoop.ALDL,418696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almBrokenLoop.ATRM,418698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almOverRange.ALDL,418708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almOverRange.ATRM,418710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almUnderRange.ALDL,418720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almUnderRange.ATRM,418722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almRateOfChange.ALDL,418732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almRateOfChange.ATRM,418734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI1.almPLCFault.ALDL,418744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI1.almPLCFault.ATRM,418746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almHighHigh.ALDL,418848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almHighHigh.ATRM,418850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almHigh.ALDL,418860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almHigh.ATRM,418862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almLow.ALDL,418872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almLow.ATRM,418874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almLowLow.ALDL,418884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almLowLow.ATRM,418886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almBrokenLoop.ALDL,418896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almBrokenLoop.ATRM,418898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almOverRange.ALDL,418908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almOverRange.ATRM,418910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almUnderRange.ALDL,418920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almUnderRange.ATRM,418922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almRateOfChange.ALDL,418932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almRateOfChange.ATRM,418934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI2.almPLCFault.ALDL,418944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI2.almPLCFault.ATRM,418946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almHighHigh.ALDL,419048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almHighHigh.ATRM,419050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almHigh.ALDL,419060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almHigh.ATRM,419062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almLow.ALDL,419072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almLow.ATRM,419074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almLowLow.ALDL,419084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almLowLow.ATRM,419086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almBrokenLoop.ALDL,419096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almBrokenLoop.ATRM,419098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almOverRange.ALDL,419108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almOverRange.ATRM,419110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almUnderRange.ALDL,419120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almUnderRange.ATRM,419122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almRateOfChange.ALDL,419132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almRateOfChange.ATRM,419134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI3.almPLCFault.ALDL,419144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI3.almPLCFault.ATRM,419146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almHighHigh.ALDL,419248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almHighHigh.ATRM,419250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almHigh.ALDL,419260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almHigh.ATRM,419262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almLow.ALDL,419272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almLow.ATRM,419274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almLowLow.ALDL,419284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almLowLow.ATRM,419286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almBrokenLoop.ALDL,419296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almBrokenLoop.ATRM,419298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almOverRange.ALDL,419308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almOverRange.ATRM,419310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almUnderRange.ALDL,419320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almUnderRange.ATRM,419322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almRateOfChange.ALDL,419332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almRateOfChange.ATRM,419334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI4.almPLCFault.ALDL,419344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI4.almPLCFault.ATRM,419346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almHighHigh.ALDL,419448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almHighHigh.ATRM,419450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almHigh.ALDL,419460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almHigh.ATRM,419462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almLow.ALDL,419472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almLow.ATRM,419474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almLowLow.ALDL,419484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almLowLow.ATRM,419486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almBrokenLoop.ALDL,419496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almBrokenLoop.ATRM,419498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almOverRange.ALDL,419508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almOverRange.ATRM,419510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almUnderRange.ALDL,419520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almUnderRange.ATRM,419522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almRateOfChange.ALDL,419532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almRateOfChange.ATRM,419534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_3_VI5.almPLCFault.ALDL,419544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_3_VI5.almPLCFault.ATRM,419546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almHighHigh.ALDL,419648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almHighHigh.ATRM,419650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almHigh.ALDL,419660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almHigh.ATRM,419662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almLow.ALDL,419672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almLow.ATRM,419674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almLowLow.ALDL,419684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almLowLow.ATRM,419686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almBrokenLoop.ALDL,419696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almBrokenLoop.ATRM,419698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almOverRange.ALDL,419708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almOverRange.ATRM,419710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almUnderRange.ALDL,419720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almUnderRange.ATRM,419722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almRateOfChange.ALDL,419732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almRateOfChange.ATRM,419734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI1.almPLCFault.ALDL,419744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI1.almPLCFault.ATRM,419746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almHighHigh.ALDL,419848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almHighHigh.ATRM,419850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almHigh.ALDL,419860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almHigh.ATRM,419862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almLow.ALDL,419872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almLow.ATRM,419874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almLowLow.ALDL,419884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almLowLow.ATRM,419886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almBrokenLoop.ALDL,419896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almBrokenLoop.ATRM,419898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almOverRange.ALDL,419908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almOverRange.ATRM,419910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almUnderRange.ALDL,419920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almUnderRange.ATRM,419922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almRateOfChange.ALDL,419932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almRateOfChange.ATRM,419934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI2.almPLCFault.ALDL,419944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI2.almPLCFault.ATRM,419946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almHighHigh.ALDL,420048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almHighHigh.ATRM,420050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almHigh.ALDL,420060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almHigh.ATRM,420062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almLow.ALDL,420072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almLow.ATRM,420074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almLowLow.ALDL,420084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almLowLow.ATRM,420086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almBrokenLoop.ALDL,420096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almBrokenLoop.ATRM,420098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almOverRange.ALDL,420108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almOverRange.ATRM,420110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almUnderRange.ALDL,420120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almUnderRange.ATRM,420122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almRateOfChange.ALDL,420132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almRateOfChange.ATRM,420134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI3.almPLCFault.ALDL,420144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI3.almPLCFault.ATRM,420146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almHighHigh.ALDL,420248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almHighHigh.ATRM,420250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almHigh.ALDL,420260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almHigh.ATRM,420262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almLow.ALDL,420272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almLow.ATRM,420274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almLowLow.ALDL,420284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almLowLow.ATRM,420286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almBrokenLoop.ALDL,420296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almBrokenLoop.ATRM,420298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almOverRange.ALDL,420308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almOverRange.ATRM,420310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almUnderRange.ALDL,420320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almUnderRange.ATRM,420322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almRateOfChange.ALDL,420332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almRateOfChange.ATRM,420334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI4.almPLCFault.ALDL,420344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI4.almPLCFault.ATRM,420346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almHighHigh.ALDL,420448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almHighHigh.ATRM,420450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almHigh.ALDL,420460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almHigh.ATRM,420462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almLow.ALDL,420472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almLow.ATRM,420474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almLowLow.ALDL,420484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almLowLow.ATRM,420486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almBrokenLoop.ALDL,420496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almBrokenLoop.ATRM,420498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almOverRange.ALDL,420508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almOverRange.ATRM,420510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almUnderRange.ALDL,420520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almUnderRange.ATRM,420522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almRateOfChange.ALDL,420532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almRateOfChange.ATRM,420534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_4_VI5.almPLCFault.ALDL,420544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_4_VI5.almPLCFault.ATRM,420546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almHighHigh.ALDL,420648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almHighHigh.ATRM,420650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almHigh.ALDL,420660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almHigh.ATRM,420662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almLow.ALDL,420672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almLow.ATRM,420674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almLowLow.ALDL,420684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almLowLow.ATRM,420686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almBrokenLoop.ALDL,420696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almBrokenLoop.ATRM,420698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almOverRange.ALDL,420708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almOverRange.ATRM,420710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almUnderRange.ALDL,420720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almUnderRange.ATRM,420722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almRateOfChange.ALDL,420732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almRateOfChange.ATRM,420734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI1.almPLCFault.ALDL,420744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI1.almPLCFault.ATRM,420746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almHighHigh.ALDL,420848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almHighHigh.ATRM,420850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almHigh.ALDL,420860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almHigh.ATRM,420862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almLow.ALDL,420872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almLow.ATRM,420874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almLowLow.ALDL,420884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almLowLow.ATRM,420886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almBrokenLoop.ALDL,420896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almBrokenLoop.ATRM,420898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almOverRange.ALDL,420908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almOverRange.ATRM,420910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almUnderRange.ALDL,420920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almUnderRange.ATRM,420922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almRateOfChange.ALDL,420932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almRateOfChange.ATRM,420934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI2.almPLCFault.ALDL,420944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI2.almPLCFault.ATRM,420946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almHighHigh.ALDL,421048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almHighHigh.ATRM,421050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almHigh.ALDL,421060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almHigh.ATRM,421062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almLow.ALDL,421072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almLow.ATRM,421074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almLowLow.ALDL,421084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almLowLow.ATRM,421086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almBrokenLoop.ALDL,421096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almBrokenLoop.ATRM,421098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almOverRange.ALDL,421108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almOverRange.ATRM,421110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almUnderRange.ALDL,421120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almUnderRange.ATRM,421122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almRateOfChange.ALDL,421132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almRateOfChange.ATRM,421134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI3.almPLCFault.ALDL,421144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI3.almPLCFault.ATRM,421146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almHighHigh.ALDL,421248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almHighHigh.ATRM,421250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almHigh.ALDL,421260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almHigh.ATRM,421262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almLow.ALDL,421272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almLow.ATRM,421274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almLowLow.ALDL,421284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almLowLow.ATRM,421286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almBrokenLoop.ALDL,421296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almBrokenLoop.ATRM,421298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almOverRange.ALDL,421308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almOverRange.ATRM,421310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almUnderRange.ALDL,421320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almUnderRange.ATRM,421322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almRateOfChange.ALDL,421332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almRateOfChange.ATRM,421334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI4.almPLCFault.ALDL,421344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI4.almPLCFault.ATRM,421346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almHighHigh.ALDL,421448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almHighHigh.ATRM,421450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almHigh.ALDL,421460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almHigh.ATRM,421462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almLow.ALDL,421472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almLow.ATRM,421474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almLowLow.ALDL,421484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almLowLow.ATRM,421486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almBrokenLoop.ALDL,421496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almBrokenLoop.ATRM,421498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almOverRange.ALDL,421508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almOverRange.ATRM,421510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almUnderRange.ALDL,421520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almUnderRange.ATRM,421522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almRateOfChange.ALDL,421532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almRateOfChange.ATRM,421534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_5_VI5.almPLCFault.ALDL,421544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_5_VI5.almPLCFault.ATRM,421546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almHighHigh.ALDL,421648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almHighHigh.ATRM,421650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almHigh.ALDL,421660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almHigh.ATRM,421662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almLow.ALDL,421672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almLow.ATRM,421674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almLowLow.ALDL,421684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almLowLow.ATRM,421686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almBrokenLoop.ALDL,421696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almBrokenLoop.ATRM,421698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almOverRange.ALDL,421708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almOverRange.ATRM,421710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almUnderRange.ALDL,421720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almUnderRange.ATRM,421722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almRateOfChange.ALDL,421732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almRateOfChange.ATRM,421734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI1.almPLCFault.ALDL,421744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI1.almPLCFault.ATRM,421746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almHighHigh.ALDL,421848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almHighHigh.ATRM,421850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almHigh.ALDL,421860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almHigh.ATRM,421862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almLow.ALDL,421872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almLow.ATRM,421874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almLowLow.ALDL,421884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almLowLow.ATRM,421886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almBrokenLoop.ALDL,421896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almBrokenLoop.ATRM,421898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almOverRange.ALDL,421908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almOverRange.ATRM,421910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almUnderRange.ALDL,421920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almUnderRange.ATRM,421922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almRateOfChange.ALDL,421932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almRateOfChange.ATRM,421934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI2.almPLCFault.ALDL,421944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI2.almPLCFault.ATRM,421946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almHighHigh.ALDL,422048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almHighHigh.ATRM,422050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almHigh.ALDL,422060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almHigh.ATRM,422062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almLow.ALDL,422072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almLow.ATRM,422074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almLowLow.ALDL,422084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almLowLow.ATRM,422086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almBrokenLoop.ALDL,422096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almBrokenLoop.ATRM,422098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almOverRange.ALDL,422108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almOverRange.ATRM,422110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almUnderRange.ALDL,422120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almUnderRange.ATRM,422122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almRateOfChange.ALDL,422132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almRateOfChange.ATRM,422134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI3.almPLCFault.ALDL,422144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI3.almPLCFault.ATRM,422146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almHighHigh.ALDL,422248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almHighHigh.ATRM,422250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almHigh.ALDL,422260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almHigh.ATRM,422262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almLow.ALDL,422272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almLow.ATRM,422274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almLowLow.ALDL,422284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almLowLow.ATRM,422286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almBrokenLoop.ALDL,422296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almBrokenLoop.ATRM,422298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almOverRange.ALDL,422308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almOverRange.ATRM,422310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almUnderRange.ALDL,422320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almUnderRange.ATRM,422322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almRateOfChange.ALDL,422332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almRateOfChange.ATRM,422334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI4.almPLCFault.ALDL,422344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI4.almPLCFault.ATRM,422346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almHighHigh.ALDL,422448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almHighHigh.ATRM,422450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almHigh.ALDL,422460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almHigh.ATRM,422462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almLow.ALDL,422472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almLow.ATRM,422474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almLowLow.ALDL,422484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almLowLow.ATRM,422486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almBrokenLoop.ALDL,422496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almBrokenLoop.ATRM,422498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almOverRange.ALDL,422508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almOverRange.ATRM,422510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almUnderRange.ALDL,422520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almUnderRange.ATRM,422522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almRateOfChange.ALDL,422532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almRateOfChange.ATRM,422534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_6_VI5.almPLCFault.ALDL,422544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_6_VI5.almPLCFault.ATRM,422546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almHighHigh.ALDL,422648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almHighHigh.ATRM,422650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almHigh.ALDL,422660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almHigh.ATRM,422662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almLow.ALDL,422672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almLow.ATRM,422674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almLowLow.ALDL,422684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almLowLow.ATRM,422686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almBrokenLoop.ALDL,422696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almBrokenLoop.ATRM,422698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almOverRange.ALDL,422708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almOverRange.ATRM,422710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almUnderRange.ALDL,422720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almUnderRange.ATRM,422722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almRateOfChange.ALDL,422732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almRateOfChange.ATRM,422734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI1.almPLCFault.ALDL,422744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI1.almPLCFault.ATRM,422746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almHighHigh.ALDL,422848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almHighHigh.ATRM,422850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almHigh.ALDL,422860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almHigh.ATRM,422862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almLow.ALDL,422872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almLow.ATRM,422874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almLowLow.ALDL,422884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almLowLow.ATRM,422886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almBrokenLoop.ALDL,422896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almBrokenLoop.ATRM,422898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almOverRange.ALDL,422908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almOverRange.ATRM,422910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almUnderRange.ALDL,422920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almUnderRange.ATRM,422922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almRateOfChange.ALDL,422932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almRateOfChange.ATRM,422934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI2.almPLCFault.ALDL,422944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI2.almPLCFault.ATRM,422946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almHighHigh.ALDL,423048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almHighHigh.ATRM,423050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almHigh.ALDL,423060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almHigh.ATRM,423062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almLow.ALDL,423072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almLow.ATRM,423074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almLowLow.ALDL,423084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almLowLow.ATRM,423086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almBrokenLoop.ALDL,423096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almBrokenLoop.ATRM,423098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almOverRange.ALDL,423108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almOverRange.ATRM,423110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almUnderRange.ALDL,423120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almUnderRange.ATRM,423122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almRateOfChange.ALDL,423132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almRateOfChange.ATRM,423134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI3.almPLCFault.ALDL,423144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI3.almPLCFault.ATRM,423146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almHighHigh.ALDL,423248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almHighHigh.ATRM,423250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almHigh.ALDL,423260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almHigh.ATRM,423262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almLow.ALDL,423272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almLow.ATRM,423274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almLowLow.ALDL,423284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almLowLow.ATRM,423286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almBrokenLoop.ALDL,423296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almBrokenLoop.ATRM,423298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almOverRange.ALDL,423308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almOverRange.ATRM,423310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almUnderRange.ALDL,423320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almUnderRange.ATRM,423322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almRateOfChange.ALDL,423332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almRateOfChange.ATRM,423334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI4.almPLCFault.ALDL,423344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI4.almPLCFault.ATRM,423346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almHighHigh.ALDL,423448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almHighHigh.ATRM,423450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almHigh.ALDL,423460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almHigh.ATRM,423462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almLow.ALDL,423472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almLow.ATRM,423474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almLowLow.ALDL,423484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almLowLow.ATRM,423486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almBrokenLoop.ALDL,423496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almBrokenLoop.ATRM,423498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almOverRange.ALDL,423508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almOverRange.ATRM,423510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almUnderRange.ALDL,423520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almUnderRange.ATRM,423522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almRateOfChange.ALDL,423532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almRateOfChange.ATRM,423534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_7_VI5.almPLCFault.ALDL,423544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_7_VI5.almPLCFault.ATRM,423546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almHighHigh.ALDL,423648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almHighHigh.ATRM,423650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almHigh.ALDL,423660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almHigh.ATRM,423662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almLow.ALDL,423672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almLow.ATRM,423674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almLowLow.ALDL,423684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almLowLow.ATRM,423686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almBrokenLoop.ALDL,423696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almBrokenLoop.ATRM,423698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almOverRange.ALDL,423708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almOverRange.ATRM,423710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almUnderRange.ALDL,423720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almUnderRange.ATRM,423722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almRateOfChange.ALDL,423732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almRateOfChange.ATRM,423734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI1.almPLCFault.ALDL,423744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI1.almPLCFault.ATRM,423746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almHighHigh.ALDL,423848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almHighHigh.ATRM,423850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almHigh.ALDL,423860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almHigh.ATRM,423862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almLow.ALDL,423872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almLow.ATRM,423874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almLowLow.ALDL,423884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almLowLow.ATRM,423886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almBrokenLoop.ALDL,423896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almBrokenLoop.ATRM,423898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almOverRange.ALDL,423908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almOverRange.ATRM,423910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almUnderRange.ALDL,423920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almUnderRange.ATRM,423922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almRateOfChange.ALDL,423932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almRateOfChange.ATRM,423934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI2.almPLCFault.ALDL,423944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI2.almPLCFault.ATRM,423946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almHighHigh.ALDL,424048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almHighHigh.ATRM,424050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almHigh.ALDL,424060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almHigh.ATRM,424062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almLow.ALDL,424072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almLow.ATRM,424074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almLowLow.ALDL,424084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almLowLow.ATRM,424086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almBrokenLoop.ALDL,424096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almBrokenLoop.ATRM,424098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almOverRange.ALDL,424108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almOverRange.ATRM,424110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almUnderRange.ALDL,424120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almUnderRange.ATRM,424122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almRateOfChange.ALDL,424132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almRateOfChange.ATRM,424134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI3.almPLCFault.ALDL,424144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI3.almPLCFault.ATRM,424146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almHighHigh.ALDL,424248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almHighHigh.ATRM,424250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almHigh.ALDL,424260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almHigh.ATRM,424262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almLow.ALDL,424272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almLow.ATRM,424274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almLowLow.ALDL,424284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almLowLow.ATRM,424286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almBrokenLoop.ALDL,424296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almBrokenLoop.ATRM,424298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almOverRange.ALDL,424308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almOverRange.ATRM,424310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almUnderRange.ALDL,424320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almUnderRange.ATRM,424322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almRateOfChange.ALDL,424332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almRateOfChange.ATRM,424334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI4.almPLCFault.ALDL,424344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI4.almPLCFault.ATRM,424346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almHighHigh.ALDL,424448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almHighHigh.ATRM,424450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almHigh.ALDL,424460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almHigh.ATRM,424462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almLow.ALDL,424472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almLow.ATRM,424474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almLowLow.ALDL,424484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almLowLow.ATRM,424486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almBrokenLoop.ALDL,424496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almBrokenLoop.ATRM,424498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almOverRange.ALDL,424508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almOverRange.ATRM,424510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almUnderRange.ALDL,424520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almUnderRange.ATRM,424522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almRateOfChange.ALDL,424532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almRateOfChange.ATRM,424534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_8_VI5.almPLCFault.ALDL,424544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_8_VI5.almPLCFault.ATRM,424546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almHighHigh.ALDL,424648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almHighHigh.ATRM,424650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almHigh.ALDL,424660,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almHigh.ATRM,424662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almLow.ALDL,424672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almLow.ATRM,424674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almLowLow.ALDL,424684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almLowLow.ATRM,424686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almBrokenLoop.ALDL,424696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almBrokenLoop.ATRM,424698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almOverRange.ALDL,424708,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almOverRange.ATRM,424710,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almUnderRange.ALDL,424720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almUnderRange.ATRM,424722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almRateOfChange.ALDL,424732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almRateOfChange.ATRM,424734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI1.almPLCFault.ALDL,424744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI1.almPLCFault.ATRM,424746,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almHighHigh.ALDL,424848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almHighHigh.ATRM,424850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almHigh.ALDL,424860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almHigh.ATRM,424862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almLow.ALDL,424872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almLow.ATRM,424874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almLowLow.ALDL,424884,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almLowLow.ATRM,424886,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almBrokenLoop.ALDL,424896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almBrokenLoop.ATRM,424898,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almOverRange.ALDL,424908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almOverRange.ATRM,424910,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almUnderRange.ALDL,424920,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almUnderRange.ATRM,424922,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almRateOfChange.ALDL,424932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almRateOfChange.ATRM,424934,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI2.almPLCFault.ALDL,424944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI2.almPLCFault.ATRM,424946,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almHighHigh.ALDL,425048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almHighHigh.ATRM,425050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almHigh.ALDL,425060,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almHigh.ATRM,425062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almLow.ALDL,425072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almLow.ATRM,425074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almLowLow.ALDL,425084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almLowLow.ATRM,425086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almBrokenLoop.ALDL,425096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almBrokenLoop.ATRM,425098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almOverRange.ALDL,425108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almOverRange.ATRM,425110,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almUnderRange.ALDL,425120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almUnderRange.ATRM,425122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almRateOfChange.ALDL,425132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almRateOfChange.ATRM,425134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI3.almPLCFault.ALDL,425144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI3.almPLCFault.ATRM,425146,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almHighHigh.ALDL,425248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almHighHigh.ATRM,425250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almHigh.ALDL,425260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almHigh.ATRM,425262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almLow.ALDL,425272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almLow.ATRM,425274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almLowLow.ALDL,425284,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almLowLow.ATRM,425286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almBrokenLoop.ALDL,425296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almBrokenLoop.ATRM,425298,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almOverRange.ALDL,425308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almOverRange.ATRM,425310,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almUnderRange.ALDL,425320,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almUnderRange.ATRM,425322,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almRateOfChange.ALDL,425332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almRateOfChange.ATRM,425334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI4.almPLCFault.ALDL,425344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI4.almPLCFault.ATRM,425346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almHighHigh.ALDL,425448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almHighHigh.ATRM,425450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almHigh.ALDL,425460,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almHigh.ATRM,425462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almLow.ALDL,425472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almLow.ATRM,425474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almLowLow.ALDL,425484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almLowLow.ATRM,425486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almBrokenLoop.ALDL,425496,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almBrokenLoop.ATRM,425498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almOverRange.ALDL,425508,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almOverRange.ATRM,425510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almUnderRange.ALDL,425520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almUnderRange.ATRM,425522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almRateOfChange.ALDL,425532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almRateOfChange.ATRM,425534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PMP_0103_9_VI5.almPLCFault.ALDL,425544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PMP_0103_9_VI5.almPLCFault.ATRM,425546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almHighHigh.ALDL,425648,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almHighHigh.ATRM,425650,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almHigh.ALDL,425660,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almHigh.ATRM,425662,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almLow.ALDL,425672,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almLow.ATRM,425674,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almLowLow.ALDL,425684,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almLowLow.ATRM,425686,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almBrokenLoop.ALDL,425696,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almBrokenLoop.ATRM,425698,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almOverRange.ALDL,425708,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almOverRange.ATRM,425710,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almUnderRange.ALDL,425720,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almUnderRange.ATRM,425722,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almRateOfChange.ALDL,425732,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almRateOfChange.ATRM,425734,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0111_1_TI.almPLCFault.ALDL,425744,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0111_1_TI.almPLCFault.ATRM,425746,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almHighHigh.ALDL,425848,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almHighHigh.ATRM,425850,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almHigh.ALDL,425860,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almHigh.ATRM,425862,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: High Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almLow.ALDL,425872,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almLow.ATRM,425874,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almLowLow.ALDL,425884,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almLowLow.ATRM,425886,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Low Low Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almBrokenLoop.ALDL,425896,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almBrokenLoop.ATRM,425898,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almOverRange.ALDL,425908,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almOverRange.ATRM,425910,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almUnderRange.ALDL,425920,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almUnderRange.ATRM,425922,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almRateOfChange.ALDL,425932,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almRateOfChange.ATRM,425934,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Rate Of Change Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TT_0112_1_TI.almPLCFault.ALDL,425944,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TT_0112_1_TI.almPLCFault.ATRM,425946,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_FA.Alarm.ALDL,426014,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_FA.Alarm.ATRM,426016,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_FA.almPLCFault.ALDL,426026,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_FA.almPLCFault.ATRM,426028,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_MF.Alarm.ALDL,426050,Float,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_MF.Alarm.ATRM,426052,Float,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_MF.almPLCFault.ALDL,426062,Float,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_MF.almPLCFault.ATRM,426064,Float,1,R/W,1000,,,,,,,,,,"Pump 1 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_MY.Alarm.ALDL,426084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_MY.Alarm.ATRM,426086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_MY.almPLCFault.ALDL,426096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_MY.almPLCFault.ATRM,426098,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UA.Alarm.ALDL,426120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UA.Alarm.ATRM,426122,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UA.almPLCFault.ALDL,426132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UA.almPLCFault.ATRM,426134,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UH.Alarm.ALDL,426154,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UH.Alarm.ATRM,426156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UH.almPLCFault.ALDL,426166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UH.almPLCFault.ATRM,426168,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UY.Alarm.ALDL,426190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UY.Alarm.ATRM,426192,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_UY.almPLCFault.ALDL,426202,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_UY.almPLCFault.ATRM,426204,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_XF.Alarm.ALDL,426224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_XF.Alarm.ATRM,426226,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_XF.almPLCFault.ALDL,426236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_XF.almPLCFault.ATRM,426238,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_YA.Alarm.ALDL,426260,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_YA.Alarm.ATRM,426262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_YA.almPLCFault.ALDL,426272,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1_YA.almPLCFault.ATRM,426274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_FA.Alarm.ALDL,426294,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_FA.Alarm.ATRM,426296,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_FA.almPLCFault.ALDL,426306,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_FA.almPLCFault.ATRM,426308,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_MF.Alarm.ALDL,426330,Float,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_MF.Alarm.ATRM,426332,Float,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_MF.almPLCFault.ALDL,426342,Float,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_MF.almPLCFault.ATRM,426344,Float,1,R/W,1000,,,,,,,,,,"Pump 2 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_MY.Alarm.ALDL,426364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_MY.Alarm.ATRM,426366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_MY.almPLCFault.ALDL,426376,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_MY.almPLCFault.ATRM,426378,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UA.Alarm.ALDL,426400,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UA.Alarm.ATRM,426402,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UA.almPLCFault.ALDL,426412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UA.almPLCFault.ATRM,426414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UH.Alarm.ALDL,426434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UH.Alarm.ATRM,426436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UH.almPLCFault.ALDL,426446,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UH.almPLCFault.ATRM,426448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 High Rtd Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UY.Alarm.ALDL,426470,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UY.Alarm.ATRM,426472,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_UY.almPLCFault.ALDL,426482,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_UY.almPLCFault.ATRM,426484,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 MPR Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_XF.Alarm.ALDL,426504,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_XF.Alarm.ATRM,426506,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_XF.almPLCFault.ALDL,426516,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_XF.almPLCFault.ATRM,426518,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_YA.Alarm.ALDL,426540,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_YA.Alarm.ATRM,426542,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2_YA.almPLCFault.ALDL,426552,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2_YA.almPLCFault.ATRM,426554,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 AFD E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_FA.Alarm.ALDL,426574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_FA.Alarm.ATRM,426576,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_FA.almPLCFault.ALDL,426586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_FA.almPLCFault.ATRM,426588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_MF.Alarm.ALDL,426610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_MF.Alarm.ATRM,426612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_MF.almPLCFault.ALDL,426622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_MF.almPLCFault.ATRM,426624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 TEWAC Motor Leak Sensor: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_MY.Alarm.ALDL,426644,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_MY.Alarm.ATRM,426646,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_MY.almPLCFault.ALDL,426656,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_MY.almPLCFault.ATRM,426658,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UA.Alarm.ALDL,426680,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UA.Alarm.ATRM,426682,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UA.almPLCFault.ALDL,426692,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UA.almPLCFault.ATRM,426694,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UH.Alarm.ALDL,426714,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UH.Alarm.ATRM,426716,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UH.almPLCFault.ALDL,426726,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UH.almPLCFault.ATRM,426728,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UY.Alarm.ALDL,426750,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UY.Alarm.ATRM,426752,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_UY.almPLCFault.ALDL,426762,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_UY.almPLCFault.ATRM,426764,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_XF.Alarm.ALDL,426784,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_XF.Alarm.ATRM,426786,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_XF.almPLCFault.ALDL,426796,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_XF.almPLCFault.ATRM,426798,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_YA.Alarm.ALDL,426820,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_YA.Alarm.ATRM,426822,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3_YA.almPLCFault.ALDL,426832,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3_YA.almPLCFault.ATRM,426834,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_FA.Alarm.ALDL,426854,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_FA.Alarm.ATRM,426856,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_FA.almPLCFault.ALDL,426866,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_FA.almPLCFault.ATRM,426868,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_MF.Alarm.ALDL,426890,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_MF.Alarm.ATRM,426892,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_MF.almPLCFault.ALDL,426902,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_MF.almPLCFault.ATRM,426904,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_MY.Alarm.ALDL,426924,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_MY.Alarm.ATRM,426926,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_MY.almPLCFault.ALDL,426936,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_MY.almPLCFault.ATRM,426938,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UA.Alarm.ALDL,426960,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UA.Alarm.ATRM,426962,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UA.almPLCFault.ALDL,426972,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UA.almPLCFault.ATRM,426974,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UH.Alarm.ALDL,426994,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UH.Alarm.ATRM,426996,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UH.almPLCFault.ALDL,427006,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UH.almPLCFault.ATRM,427008,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UY.Alarm.ALDL,427030,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UY.Alarm.ATRM,427032,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_UY.almPLCFault.ALDL,427042,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_UY.almPLCFault.ATRM,427044,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_XF.Alarm.ALDL,427064,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_XF.Alarm.ATRM,427066,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_XF.almPLCFault.ALDL,427076,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_XF.almPLCFault.ATRM,427078,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_YA.Alarm.ALDL,427100,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_YA.Alarm.ATRM,427102,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4_YA.almPLCFault.ALDL,427112,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4_YA.almPLCFault.ATRM,427114,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_FA.Alarm.ALDL,427134,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_FA.Alarm.ATRM,427136,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_FA.almPLCFault.ALDL,427146,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_FA.almPLCFault.ATRM,427148,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_MF.Alarm.ALDL,427170,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_MF.Alarm.ATRM,427172,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_MF.almPLCFault.ALDL,427182,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_MF.almPLCFault.ATRM,427184,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_MY.Alarm.ALDL,427204,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_MY.Alarm.ATRM,427206,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_MY.almPLCFault.ALDL,427216,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_MY.almPLCFault.ATRM,427218,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UA.Alarm.ALDL,427240,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UA.Alarm.ATRM,427242,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UA.almPLCFault.ALDL,427252,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UA.almPLCFault.ATRM,427254,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UH.Alarm.ALDL,427274,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UH.Alarm.ATRM,427276,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UH.almPLCFault.ALDL,427286,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UH.almPLCFault.ATRM,427288,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UY.Alarm.ALDL,427310,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UY.Alarm.ATRM,427312,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_UY.almPLCFault.ALDL,427322,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_UY.almPLCFault.ATRM,427324,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_XF.Alarm.ALDL,427344,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_XF.Alarm.ATRM,427346,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_XF.almPLCFault.ALDL,427356,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_XF.almPLCFault.ATRM,427358,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_YA.Alarm.ALDL,427380,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_YA.Alarm.ATRM,427382,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5_YA.almPLCFault.ALDL,427392,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5_YA.almPLCFault.ATRM,427394,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_FA.Alarm.ALDL,427414,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_FA.Alarm.ATRM,427416,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_FA.almPLCFault.ALDL,427426,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_FA.almPLCFault.ATRM,427428,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_MF.Alarm.ALDL,427450,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_MF.Alarm.ATRM,427452,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_MF.almPLCFault.ALDL,427462,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_MF.almPLCFault.ATRM,427464,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_MY.Alarm.ALDL,427484,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_MY.Alarm.ATRM,427486,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_MY.almPLCFault.ALDL,427496,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_MY.almPLCFault.ATRM,427498,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UA.Alarm.ALDL,427520,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UA.Alarm.ATRM,427522,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UA.almPLCFault.ALDL,427532,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UA.almPLCFault.ATRM,427534,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UH.Alarm.ALDL,427554,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UH.Alarm.ATRM,427556,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UH.almPLCFault.ALDL,427566,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UH.almPLCFault.ATRM,427568,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UY.Alarm.ALDL,427590,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UY.Alarm.ATRM,427592,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_UY.almPLCFault.ALDL,427602,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_UY.almPLCFault.ATRM,427604,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_XF.Alarm.ALDL,427624,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_XF.Alarm.ATRM,427626,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_XF.almPLCFault.ALDL,427636,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_XF.almPLCFault.ATRM,427638,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_YA.Alarm.ALDL,427660,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_YA.Alarm.ATRM,427662,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6_YA.almPLCFault.ALDL,427672,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6_YA.almPLCFault.ATRM,427674,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_FA.Alarm.ALDL,427694,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_FA.Alarm.ATRM,427696,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_FA.almPLCFault.ALDL,427706,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_FA.almPLCFault.ATRM,427708,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_MF.Alarm.ALDL,427730,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_MF.Alarm.ATRM,427732,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_MF.almPLCFault.ALDL,427742,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_MF.almPLCFault.ATRM,427744,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_MY.Alarm.ALDL,427764,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_MY.Alarm.ATRM,427766,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_MY.almPLCFault.ALDL,427776,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_MY.almPLCFault.ATRM,427778,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UA.Alarm.ALDL,427800,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UA.Alarm.ATRM,427802,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UA.almPLCFault.ALDL,427812,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UA.almPLCFault.ATRM,427814,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UH.Alarm.ALDL,427834,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UH.Alarm.ATRM,427836,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UH.almPLCFault.ALDL,427846,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UH.almPLCFault.ATRM,427848,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UY.Alarm.ALDL,427870,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UY.Alarm.ATRM,427872,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_UY.almPLCFault.ALDL,427882,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_UY.almPLCFault.ATRM,427884,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_XF.Alarm.ALDL,427904,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_XF.Alarm.ATRM,427906,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_XF.almPLCFault.ALDL,427916,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_XF.almPLCFault.ATRM,427918,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_YA.Alarm.ALDL,427940,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_YA.Alarm.ATRM,427942,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7_YA.almPLCFault.ALDL,427952,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7_YA.almPLCFault.ATRM,427954,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_FA.Alarm.ALDL,427974,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_FA.Alarm.ATRM,427976,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_FA.almPLCFault.ALDL,427986,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_FA.almPLCFault.ATRM,427988,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 COOLING WATER FLOW FAILURE: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_MF.Alarm.ALDL,428010,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_MF.Alarm.ATRM,428012,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_MF.almPLCFault.ALDL,428022,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_MF.almPLCFault.ATRM,428024,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 TEWAC MOTOR LEAK SENSOR: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_MY.Alarm.ALDL,428044,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_MY.Alarm.ATRM,428046,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_MY.almPLCFault.ALDL,428056,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_MY.almPLCFault.ATRM,428058,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UA.Alarm.ALDL,428080,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UA.Alarm.ATRM,428082,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UA.almPLCFault.ALDL,428092,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UA.almPLCFault.ATRM,428094,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR ALARM: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UH.Alarm.ALDL,428114,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UH.Alarm.ATRM,428116,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UH.almPLCFault.ALDL,428126,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UH.almPLCFault.ATRM,428128,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 HIGH RTD TEMP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UY.Alarm.ALDL,428150,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UY.Alarm.ATRM,428152,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_UY.almPLCFault.ALDL,428162,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_UY.almPLCFault.ATRM,428164,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 MPR TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_XF.Alarm.ALDL,428184,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_XF.Alarm.ATRM,428186,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_XF.almPLCFault.ALDL,428196,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_XF.almPLCFault.ATRM,428198,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_YA.Alarm.ALDL,428220,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_YA.Alarm.ATRM,428222,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8_YA.almPLCFault.ALDL,428232,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8_YA.almPLCFault.ATRM,428234,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 AFD E. STOP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_FA.Alarm.ALDL,428254,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_FA.Alarm.ATRM,428256,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_FA.almPLCFault.ALDL,428266,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_FA.almPLCFault.ATRM,428268,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_MF.Alarm.ALDL,428290,Float,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_MF.Alarm.ATRM,428292,Float,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_MF.almPLCFault.ALDL,428302,Float,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_MF.almPLCFault.ATRM,428304,Float,1,R/W,1000,,,,,,,,,,"Pump 9 Motor Seal Leak: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_MY.Alarm.ALDL,428324,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_MY.Alarm.ATRM,428326,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_MY.almPLCFault.ALDL,428336,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_MY.almPLCFault.ATRM,428338,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 E. Stop : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UA.Alarm.ALDL,428360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UA.Alarm.ATRM,428362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UA.almPLCFault.ALDL,428372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UA.almPLCFault.ATRM,428374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UH.Alarm.ALDL,428394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UH.Alarm.ATRM,428396,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UH.almPLCFault.ALDL,428406,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UH.almPLCFault.ATRM,428408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 High Rtd Temp: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UY.Alarm.ALDL,428430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UY.Alarm.ATRM,428432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_UY.almPLCFault.ALDL,428442,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_UY.almPLCFault.ATRM,428444,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 MPR Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_XF.Alarm.ALDL,428464,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_XF.Alarm.ATRM,428466,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_XF.almPLCFault.ALDL,428476,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_XF.almPLCFault.ATRM,428478,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_YA.Alarm.ALDL,428500,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_YA.Alarm.ATRM,428502,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9_YA.almPLCFault.ALDL,428512,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9_YA.almPLCFault.ATRM,428514,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 AFD E. Stop: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_1_JA.Alarm.ALDL,428534,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_1_JA.Alarm.ATRM,428536,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_1_JA.almPLCFault.ALDL,428546,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_1_JA.almPLCFault.ATRM,428548,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_1_JN1.Alarm.ALDL,428570,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_1_JN1.Alarm.ATRM,428572,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_1_JN1.almPLCFault.ALDL,428582,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_1_JN1.almPLCFault.ATRM,428584,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-1 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_2_JA.Alarm.ALDL,428604,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_2_JA.Alarm.ATRM,428606,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_2_JA.almPLCFault.ALDL,428616,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_2_JA.almPLCFault.ATRM,428618,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_2_JN1.Alarm.ALDL,428640,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_2_JN1.Alarm.ATRM,428642,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0112_2_JN1.almPLCFault.ALDL,428652,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0112_2_JN1.almPLCFault.ATRM,428654,Float,1,R/W,1000,,,,,,,,,,"RWPS Switchgear 0112-2 Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0140_1_JA.Alarm.ALDL,428674,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0140_1_JA.Alarm.ATRM,428676,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0140_1_JA.almPLCFault.ALDL,428686,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0140_1_JA.almPLCFault.ATRM,428688,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Transfer Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0140_1_XA.Alarm.ALDL,428710,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0140_1_XA.Alarm.ATRM,428712,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_ATO_0140_1_XA.almPLCFault.ALDL,428722,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_ATO_0140_1_XA.almPLCFault.ATRM,428724,Float,1,R/W,1000,,,,,,,,,,"RWPS 480V Switchgear Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_1_XA.Alarm.ALDL,428744,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_1_XA.Alarm.ATRM,428746,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_1_XA.almPLCFault.ALDL,428756,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_1_XA.almPLCFault.ATRM,428758,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_2_XA.Alarm.ALDL,428780,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_2_XA.Alarm.ATRM,428782,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_2_XA.almPLCFault.ALDL,428792,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_2_XA.almPLCFault.ATRM,428794,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_3_LH.Alarm.ALDL,428814,Float,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_3_LH.Alarm.ATRM,428816,Float,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0114_3_LH.almPLCFault.ALDL,428826,Float,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0114_3_LH.almPLCFault.ATRM,428828,Float,1,R/W,1000,,,,,,,,,,"RWPS Elevator Pit Common High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1A_MF.Alarm.ALDL,428850,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1A_MF.Alarm.ATRM,428852,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1A_MF.almPLCFault.ALDL,428862,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1A_MF.almPLCFault.ATRM,428864,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1A_XA.Alarm.ALDL,428884,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1A_XA.Alarm.ATRM,428886,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1A_XA.almPLCFault.ALDL,428896,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1A_XA.almPLCFault.ATRM,428898,Float,1,R/W,1000,,,,,,,,,,"RWPS Northwest Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1B_MF.Alarm.ALDL,428920,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1B_MF.Alarm.ATRM,428922,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1B_MF.almPLCFault.ALDL,428932,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1B_MF.almPLCFault.ATRM,428934,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Fault: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1B_XA.Alarm.ALDL,428954,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1B_XA.Alarm.ATRM,428956,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1B_XA.almPLCFault.ALDL,428966,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1B_XA.almPLCFault.ATRM,428968,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 1 Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1C_MF.Alarm.ALDL,428990,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1C_MF.Alarm.ATRM,428992,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1C_MF.almPLCFault.ALDL,429002,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1C_MF.almPLCFault.ATRM,429004,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1C_XA.Alarm.ALDL,429024,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1C_XA.Alarm.ATRM,429026,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1C_XA.almPLCFault.ALDL,429036,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1C_XA.almPLCFault.ATRM,429038,Float,1,R/W,1000,,,,,,,,,,"RWPS Southwest By Pump 4 Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1DE_MF.Alarm.ALDL,429060,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1DE_MF.Alarm.ATRM,429062,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1DE_MF.almPLCFault.ALDL,429072,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1DE_MF.almPLCFault.ATRM,429074,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1DE_XA.Alarm.ALDL,429094,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1DE_XA.Alarm.ATRM,429096,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1DE_XA.almPLCFault.ALDL,429106,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1DE_XA.almPLCFault.ATRM,429108,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1FG_MF.Alarm.ALDL,429130,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1FG_MF.Alarm.ATRM,429132,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1FG_MF.almPLCFault.ALDL,429142,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1FG_MF.almPLCFault.ATRM,429144,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1FG_XA.Alarm.ALDL,429164,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1FG_XA.Alarm.ATRM,429166,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1FG_XA.almPLCFault.ALDL,429176,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1FG_XA.almPLCFault.ATRM,429178,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1H_MF.Alarm.ALDL,429200,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1H_MF.Alarm.ATRM,429202,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1H_MF.almPLCFault.ALDL,429212,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1H_MF.almPLCFault.ATRM,429214,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1H_XA.Alarm.ALDL,429234,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1H_XA.Alarm.ATRM,429236,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1H_XA.almPLCFault.ALDL,429246,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1H_XA.almPLCFault.ATRM,429248,Float,1,R/W,1000,,,,,,,,,,"RWPS Southeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1I_MF.Alarm.ALDL,429270,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1I_MF.Alarm.ATRM,429272,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1I_MF.almPLCFault.ALDL,429282,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1I_MF.almPLCFault.ATRM,429284,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1I_XA.Alarm.ALDL,429304,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1I_XA.Alarm.ATRM,429306,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1I_XA.almPLCFault.ALDL,429316,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1I_XA.almPLCFault.ATRM,429318,Float,1,R/W,1000,,,,,,,,,,"RWPS Northeast Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1J_MF.Alarm.ALDL,429340,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1J_MF.Alarm.ATRM,429342,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1J_MF.almPLCFault.ALDL,429352,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1J_MF.almPLCFault.ATRM,429354,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1J_XA.Alarm.ALDL,429374,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1J_XA.Alarm.ATRM,429376,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1J_XA.almPLCFault.ALDL,429386,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1J_XA.almPLCFault.ATRM,429388,Float,1,R/W,1000,,,,,,,,,,"RWPS East Elevator Sump Pump Control Power Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1K_MF.Alarm.ALDL,429410,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1K_MF.Alarm.ATRM,429412,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1K_MF.almPLCFault.ALDL,429422,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1K_MF.almPLCFault.ATRM,429424,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1K_XA.Alarm.ALDL,429444,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1K_XA.Alarm.ATRM,429446,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_1K_XA.almPLCFault.ALDL,429456,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_1K_XA.almPLCFault.ATRM,429458,Float,1,R/W,1000,,,,,,,,,,"RWPS West Elevator Sump Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_LH.Alarm.ALDL,429480,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_LH.Alarm.ATRM,429482,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_LH.almPLCFault.ALDL,429492,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_LH.almPLCFault.ATRM,429494,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF1.Alarm.ALDL,429514,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF1.Alarm.ATRM,429516,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF1.almPLCFault.ALDL,429526,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF1.almPLCFault.ATRM,429528,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF2.Alarm.ALDL,429550,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF2.Alarm.ATRM,429552,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF2.almPLCFault.ALDL,429562,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF2.almPLCFault.ATRM,429564,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVS A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF3.Alarm.ALDL,429584,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF3.Alarm.ATRM,429586,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF3.almPLCFault.ALDL,429596,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF3.almPLCFault.ATRM,429598,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF4.Alarm.ALDL,429620,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF4.Alarm.ATRM,429622,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_MF4.almPLCFault.ALDL,429632,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_MF4.almPLCFault.ATRM,429634,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering SSRVSB Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_XA.Alarm.ALDL,429654,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_XA.Alarm.ATRM,429656,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2A_XA.almPLCFault.ALDL,429666,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2A_XA.almPLCFault.ATRM,429668,Float,1,R/W,1000,,,,,,,,,,"RWPS West Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_LH.Alarm.ALDL,429690,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_LH.Alarm.ATRM,429692,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_LH.almPLCFault.ALDL,429702,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_LH.almPLCFault.ATRM,429704,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF1.Alarm.ALDL,429724,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF1.Alarm.ATRM,429726,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF1.almPLCFault.ALDL,429736,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF1.almPLCFault.ATRM,429738,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump C Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF2.Alarm.ALDL,429760,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF2.Alarm.ATRM,429762,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF2.almPLCFault.ALDL,429772,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF2.almPLCFault.ATRM,429774,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSC Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF3.Alarm.ALDL,429794,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF3.Alarm.ATRM,429796,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF3.almPLCFault.ALDL,429806,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF3.almPLCFault.ATRM,429808,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Pump D Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF4.Alarm.ALDL,429830,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF4.Alarm.ATRM,429832,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_MF4.almPLCFault.ALDL,429842,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_MF4.almPLCFault.ATRM,429844,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering SSRVSD Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_XA.Alarm.ALDL,429864,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_XA.Alarm.ATRM,429866,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_2B_XA.almPLCFault.ALDL,429876,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_2B_XA.almPLCFault.ATRM,429878,Float,1,R/W,1000,,,,,,,,,,"RWPS East Secondary Dewatering Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_3A_MF.Alarm.ALDL,429900,Float,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_3A_MF.Alarm.ATRM,429902,Float,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_3A_MF.almPLCFault.ALDL,429912,Float,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_3A_MF.almPLCFault.ATRM,429914,Float,1,R/W,1000,,,,,,,,,,"RWPS Intake Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_3B_XF.Alarm.ALDL,429934,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_3B_XF.Alarm.ATRM,429936,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0117_3B_XF.almPLCFault.ALDL,429946,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0117_3B_XF.almPLCFault.ATRM,429948,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Maintenance Dewatering Pump Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_LH1.Alarm.ALDL,429970,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_LH1.Alarm.ATRM,429972,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_LH1.almPLCFault.ALDL,429982,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_LH1.almPLCFault.ATRM,429984,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_LH2.Alarm.ALDL,430004,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_LH2.Alarm.ATRM,430006,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_LH2.almPLCFault.ALDL,430016,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_LH2.almPLCFault.ATRM,430018,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_XA.Alarm.ALDL,430040,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_XA.Alarm.ATRM,430042,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1_XA.almPLCFault.ALDL,430052,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1_XA.almPLCFault.ATRM,430054,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1A_MF.Alarm.ALDL,430074,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1A_MF.Alarm.ATRM,430076,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1A_MF.almPLCFault.ALDL,430086,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1A_MF.almPLCFault.ATRM,430088,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1B_MF.Alarm.ALDL,430110,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1B_MF.Alarm.ATRM,430112,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_1B_MF.almPLCFault.ALDL,430122,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_1B_MF.almPLCFault.ATRM,430124,Float,1,R/W,1000,,,,,,,,,,"RWPS West Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_LH1.Alarm.ALDL,430144,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_LH1.Alarm.ATRM,430146,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_LH1.almPLCFault.ALDL,430156,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_LH1.almPLCFault.ATRM,430158,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_LH2.Alarm.ALDL,430180,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_LH2.Alarm.ATRM,430182,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_LH2.almPLCFault.ALDL,430192,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_LH2.almPLCFault.ATRM,430194,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Wet Well High-High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_XA.Alarm.ALDL,430214,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_XA.Alarm.ATRM,430216,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2_XA.almPLCFault.ALDL,430226,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2_XA.almPLCFault.ATRM,430228,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump Control Power Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2A_MF.Alarm.ALDL,430250,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2A_MF.Alarm.ATRM,430252,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2A_MF.almPLCFault.ALDL,430262,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2A_MF.almPLCFault.ATRM,430264,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump A Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2B_MF.Alarm.ALDL,430284,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2B_MF.Alarm.ATRM,430286,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_CP_0118_2B_MF.almPLCFault.ALDL,430296,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_CP_0118_2B_MF.almPLCFault.ATRM,430298,Float,1,R/W,1000,,,,,,,,,,"RWPS East Dam Collector Pump B Fault : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_WH.Alarm.ALDL,430320,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_WH.Alarm.ATRM,430322,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A_WH.almPLCFault.ALDL,430332,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A_WH.almPLCFault.ATRM,430334,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_WH.Alarm.ALDL,430354,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_WH.Alarm.ATRM,430356,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B_WH.almPLCFault.ALDL,430366,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B_WH.almPLCFault.ATRM,430368,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Sleeve Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FLT_0112_1_XA.Alarm.ALDL,430390,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FLT_0112_1_XA.Alarm.ATRM,430392,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FLT_0112_1_XA.almPLCFault.ALDL,430402,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FLT_0112_1_XA.almPLCFault.ATRM,430404,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FLT_0112_2_XA.Alarm.ALDL,430424,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FLT_0112_2_XA.Alarm.ATRM,430426,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FLT_0112_2_XA.almPLCFault.ALDL,430436,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FLT_0112_2_XA.almPLCFault.ATRM,430438,Float,1,R/W,1000,,,,,,,,,,"Active Harmonic Filter Common Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A_WH.Alarm.ALDL,430460,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A_WH.Alarm.ATRM,430462,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A_WH.almPLCFault.ALDL,430472,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A_WH.almPLCFault.ATRM,430474,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B_WH.Alarm.ALDL,430494,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B_WH.Alarm.ATRM,430496,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B_WH.almPLCFault.ALDL,430506,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B_WH.almPLCFault.ATRM,430508,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A_WH.Alarm.ALDL,430530,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A_WH.Alarm.ATRM,430532,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A_WH.almPLCFault.ALDL,430542,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A_WH.almPLCFault.ATRM,430544,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B_WH.Alarm.ALDL,430564,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B_WH.Alarm.ATRM,430566,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B_WH.almPLCFault.ALDL,430576,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B_WH.almPLCFault.ATRM,430578,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A_WH.Alarm.ALDL,430600,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A_WH.Alarm.ATRM,430602,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A_WH.almPLCFault.ALDL,430612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A_WH.almPLCFault.ATRM,430614,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZF.Alarm.ALDL,430634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZF.Alarm.ATRM,430636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZF.almPLCFault.ALDL,430646,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZF.almPLCFault.ATRM,430648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZF2.Alarm.ALDL,430670,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZF2.Alarm.ATRM,430672,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1B_ZF2.almPLCFault.ALDL,430682,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1B_ZF2.almPLCFault.ATRM,430684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C_WH.Alarm.ALDL,430704,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C_WH.Alarm.ATRM,430706,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C_WH.almPLCFault.ALDL,430716,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C_WH.almPLCFault.ATRM,430718,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A_WH.Alarm.ALDL,430740,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A_WH.Alarm.ATRM,430742,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A_WH.almPLCFault.ALDL,430752,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A_WH.almPLCFault.ATRM,430754,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZF.Alarm.ALDL,430774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZF.Alarm.ATRM,430776,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZF.almPLCFault.ALDL,430786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZF.almPLCFault.ATRM,430788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZF2.Alarm.ALDL,430810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZF2.Alarm.ATRM,430812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2B_ZF2.almPLCFault.ALDL,430822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2B_ZF2.almPLCFault.ATRM,430824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C_WH.Alarm.ALDL,430844,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C_WH.Alarm.ATRM,430846,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C_WH.almPLCFault.ALDL,430856,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C_WH.almPLCFault.ATRM,430858,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A_WH.Alarm.ALDL,430880,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A_WH.Alarm.ATRM,430882,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A_WH.almPLCFault.ALDL,430892,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A_WH.almPLCFault.ATRM,430894,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF.Alarm.ALDL,430914,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF.Alarm.ATRM,430916,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF.almPLCFault.ALDL,430926,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF.almPLCFault.ATRM,430928,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF3.Alarm.ALDL,430950,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF3.Alarm.ATRM,430952,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF3.almPLCFault.ALDL,430962,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF3.almPLCFault.ATRM,430964,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF4.Alarm.ALDL,430984,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF4.Alarm.ATRM,430986,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3B_ZF4.almPLCFault.ALDL,430996,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3B_ZF4.almPLCFault.ATRM,430998,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 3 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C_WH.Alarm.ALDL,431020,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C_WH.Alarm.ATRM,431022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C_WH.almPLCFault.ALDL,431032,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C_WH.almPLCFault.ATRM,431034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D_WH.Alarm.ALDL,431054,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D_WH.Alarm.ATRM,431056,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D_WH.almPLCFault.ALDL,431066,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D_WH.almPLCFault.ATRM,431068,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A_WH.Alarm.ALDL,431090,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A_WH.Alarm.ATRM,431092,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A_WH.almPLCFault.ALDL,431102,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A_WH.almPLCFault.ATRM,431104,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF.Alarm.ALDL,431124,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF.Alarm.ATRM,431126,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF.almPLCFault.ALDL,431136,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF.almPLCFault.ATRM,431138,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF3.Alarm.ALDL,431160,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF3.Alarm.ATRM,431162,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF3.almPLCFault.ALDL,431172,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF3.almPLCFault.ATRM,431174,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF4.Alarm.ALDL,431194,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF4.Alarm.ATRM,431196,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4B_ZF4.almPLCFault.ALDL,431206,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4B_ZF4.almPLCFault.ATRM,431208,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 4 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C_WH.Alarm.ALDL,431230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C_WH.Alarm.ATRM,431232,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C_WH.almPLCFault.ALDL,431242,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C_WH.almPLCFault.ATRM,431244,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D_WH.Alarm.ALDL,431264,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D_WH.Alarm.ATRM,431266,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D_WH.almPLCFault.ALDL,431276,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D_WH.almPLCFault.ATRM,431278,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A_WH.Alarm.ALDL,431300,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A_WH.Alarm.ATRM,431302,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A_WH.almPLCFault.ALDL,431312,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A_WH.almPLCFault.ATRM,431314,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF.Alarm.ALDL,431334,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF.Alarm.ATRM,431336,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF.almPLCFault.ALDL,431346,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF.almPLCFault.ATRM,431348,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF3.Alarm.ALDL,431370,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF3.Alarm.ATRM,431372,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF3.almPLCFault.ALDL,431382,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF3.almPLCFault.ATRM,431384,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF4.Alarm.ALDL,431404,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF4.Alarm.ATRM,431406,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5B_ZF4.almPLCFault.ALDL,431416,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5B_ZF4.almPLCFault.ATRM,431418,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 5 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C_WH.Alarm.ALDL,431440,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C_WH.Alarm.ATRM,431442,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C_WH.almPLCFault.ALDL,431452,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C_WH.almPLCFault.ATRM,431454,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D_WH.Alarm.ALDL,431474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D_WH.Alarm.ATRM,431476,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D_WH.almPLCFault.ALDL,431486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D_WH.almPLCFault.ATRM,431488,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A_WH.Alarm.ALDL,431510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A_WH.Alarm.ATRM,431512,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A_WH.almPLCFault.ALDL,431522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A_WH.almPLCFault.ATRM,431524,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF.Alarm.ALDL,431544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF.Alarm.ATRM,431546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF.almPLCFault.ALDL,431556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF.almPLCFault.ATRM,431558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF3.Alarm.ALDL,431580,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF3.Alarm.ATRM,431582,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF3.almPLCFault.ALDL,431592,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF3.almPLCFault.ATRM,431594,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF4.Alarm.ALDL,431614,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF4.Alarm.ATRM,431616,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6B_ZF4.almPLCFault.ALDL,431626,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6B_ZF4.almPLCFault.ATRM,431628,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 6 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C_WH.Alarm.ALDL,431650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C_WH.Alarm.ATRM,431652,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C_WH.almPLCFault.ALDL,431662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C_WH.almPLCFault.ATRM,431664,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D_WH.Alarm.ALDL,431684,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D_WH.Alarm.ATRM,431686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D_WH.almPLCFault.ALDL,431696,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D_WH.almPLCFault.ATRM,431698,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A_WH.Alarm.ALDL,431720,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A_WH.Alarm.ATRM,431722,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A_WH.almPLCFault.ALDL,431732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A_WH.almPLCFault.ATRM,431734,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF.Alarm.ALDL,431754,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF.Alarm.ATRM,431756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF.almPLCFault.ALDL,431766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF.almPLCFault.ATRM,431768,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF3.Alarm.ALDL,431790,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF3.Alarm.ATRM,431792,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF3.almPLCFault.ALDL,431802,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF3.almPLCFault.ATRM,431804,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF4.Alarm.ALDL,431824,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF4.Alarm.ATRM,431826,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7B_ZF4.almPLCFault.ALDL,431836,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7B_ZF4.almPLCFault.ATRM,431838,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 7 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C_WH.Alarm.ALDL,431860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C_WH.Alarm.ATRM,431862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C_WH.almPLCFault.ALDL,431872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C_WH.almPLCFault.ATRM,431874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D_WH.Alarm.ALDL,431894,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D_WH.Alarm.ATRM,431896,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D_WH.almPLCFault.ALDL,431906,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D_WH.almPLCFault.ATRM,431908,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A_WH.Alarm.ALDL,431930,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A_WH.Alarm.ATRM,431932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A_WH.almPLCFault.ALDL,431942,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A_WH.almPLCFault.ATRM,431944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF.Alarm.ALDL,431964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF.Alarm.ATRM,431966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF.almPLCFault.ALDL,431976,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF.almPLCFault.ATRM,431978,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF3.Alarm.ALDL,432000,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF3.Alarm.ATRM,432002,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF3.almPLCFault.ALDL,432012,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF3.almPLCFault.ATRM,432014,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL TRIP: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF4.Alarm.ALDL,432034,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF4.Alarm.ATRM,432036,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8B_ZF4.almPLCFault.ALDL,432046,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8B_ZF4.almPLCFault.ATRM,432048,Float,1,R/W,1000,,,,,,,,,,"RWPS PUMP 8 CONTROL VALVE PANEL WARNING: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C_WH.Alarm.ALDL,432070,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C_WH.Alarm.ATRM,432072,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C_WH.almPLCFault.ALDL,432082,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C_WH.almPLCFault.ATRM,432084,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D_WH.Alarm.ALDL,432104,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D_WH.Alarm.ATRM,432106,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D_WH.almPLCFault.ALDL,432116,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D_WH.almPLCFault.ATRM,432118,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A_WH.Alarm.ALDL,432140,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A_WH.Alarm.ATRM,432142,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A_WH.almPLCFault.ALDL,432152,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A_WH.almPLCFault.ATRM,432154,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZF.Alarm.ALDL,432174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZF.Alarm.ATRM,432176,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZF.almPLCFault.ALDL,432186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZF.almPLCFault.ATRM,432188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Failure: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZF2.Alarm.ALDL,432210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZF2.Alarm.ATRM,432212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9B_ZF2.almPLCFault.ALDL,432222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9B_ZF2.almPLCFault.ATRM,432224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 PCV Not Ready Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C_WH.Alarm.ALDL,432244,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C_WH.Alarm.ATRM,432246,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C_WH.almPLCFault.ALDL,432256,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C_WH.almPLCFault.ATRM,432258,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A_WH.Alarm.ALDL,432280,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A_WH.Alarm.ATRM,432282,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A_WH.almPLCFault.ALDL,432292,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A_WH.almPLCFault.ATRM,432294,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B_WH.Alarm.ALDL,432314,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B_WH.Alarm.ATRM,432316,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B_WH.almPLCFault.ALDL,432326,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B_WH.almPLCFault.ATRM,432328,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C_WH.Alarm.ALDL,432350,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C_WH.Alarm.ATRM,432352,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C_WH.almPLCFault.ALDL,432362,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C_WH.almPLCFault.ATRM,432364,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D_WH.Alarm.ALDL,432384,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D_WH.Alarm.ATRM,432386,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D_WH.almPLCFault.ALDL,432396,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D_WH.almPLCFault.ATRM,432398,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve High Torque : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_LL.Alarm.ALDL,432420,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_LL.Alarm.ATRM,432422,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_LL.almPLCFault.ALDL,432432,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_LL.almPLCFault.ATRM,432434,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Fuel : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_PL.Alarm.ALDL,432454,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_PL.Alarm.ATRM,432456,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_PL.almPLCFault.ALDL,432466,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_PL.almPLCFault.ATRM,432468,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Low Oil Pressure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_SH.Alarm.ALDL,432490,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_SH.Alarm.ATRM,432492,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_SH.almPLCFault.ALDL,432502,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_SH.almPLCFault.ATRM,432504,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Over Speed : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_TH.Alarm.ALDL,432524,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_TH.Alarm.ATRM,432526,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_TH.almPLCFault.ALDL,432536,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_TH.almPLCFault.ATRM,432538,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator High Water Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_XA1.Alarm.ALDL,432560,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_XA1.Alarm.ATRM,432562,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_XA1.almPLCFault.ALDL,432572,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_XA1.almPLCFault.ATRM,432574,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Common Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_XA2.Alarm.ALDL,432594,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_XA2.Alarm.ATRM,432596,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_GEN_0131_1_XA2.almPLCFault.ALDL,432606,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_GEN_0131_1_XA2.almPLCFault.ATRM,432608,Float,1,R/W,1000,,,,,,,,,,"RWPS Stand-By Generator Battery Sys Malfunction : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_FA.Alarm.ALDL,432630,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_FA.Alarm.ATRM,432632,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_FA.almPLCFault.ALDL,432642,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_FA.almPLCFault.ATRM,432644,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Cooling Water No Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_FH.Alarm.ALDL,432664,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_FH.Alarm.ATRM,432666,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_FH.almPLCFault.ALDL,432676,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_FH.almPLCFault.ATRM,432678,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Condensate Overflow Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_PH.Alarm.ALDL,432700,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_PH.Alarm.ATRM,432702,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_PH.almPLCFault.ALDL,432712,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_PH.almPLCFault.ATRM,432714,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Filter High Diff Pressure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH1.Alarm.ALDL,432734,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH1.Alarm.ATRM,432736,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH1.almPLCFault.ALDL,432746,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH1.almPLCFault.ATRM,432748,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) High Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH2.Alarm.ALDL,432770,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH2.Alarm.ATRM,432772,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH2.almPLCFault.ALDL,432782,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH2.almPLCFault.ATRM,432784,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Supply High Temp Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH3.Alarm.ALDL,432804,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH3.Alarm.ATRM,432806,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TH3.almPLCFault.ALDL,432816,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TH3.almPLCFault.ATRM,432818,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air High Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TL1.Alarm.ALDL,432840,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TL1.Alarm.ATRM,432842,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TL1.almPLCFault.ALDL,432852,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TL1.almPLCFault.ATRM,432854,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Freeze Protection Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TL2.Alarm.ALDL,432874,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TL2.Alarm.ATRM,432876,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_TL2.almPLCFault.ALDL,432886,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_TL2.almPLCFault.ATRM,432888,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Air Low Temp : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA1.Alarm.ALDL,432910,Float,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA1.Alarm.ATRM,432912,Float,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA1.almPLCFault.ALDL,432922,Float,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA1.almPLCFault.ATRM,432924,Float,1,R/W,1000,,,,,,,,,,"RWPS Emergency Hvac Shutdown : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA2.Alarm.ALDL,432944,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA2.Alarm.ATRM,432946,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA2.almPLCFault.ALDL,432956,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA2.almPLCFault.ATRM,432958,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA3.Alarm.ALDL,432980,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA3.Alarm.ATRM,432982,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA3.almPLCFault.ALDL,432992,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA3.almPLCFault.ATRM,432994,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Space Temperature Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA4.Alarm.ALDL,433014,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA4.Alarm.ATRM,433016,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA4.almPLCFault.ALDL,433026,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA4.almPLCFault.ATRM,433028,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Dirty Filter Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA5.Alarm.ALDL,433050,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA5.Alarm.ATRM,433052,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA5.almPLCFault.ALDL,433062,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA5.almPLCFault.ATRM,433064,Float,1,R/W,1000,,,,,,,,,,"RWPS (AUH SYS Com) Smoke Detector Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA6.Alarm.ALDL,433084,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA6.Alarm.ATRM,433086,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA6.almPLCFault.ALDL,433096,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA6.almPLCFault.ATRM,433098,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Proof Of Flow : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA7.Alarm.ALDL,433120,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA7.Alarm.ATRM,433122,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA7.almPLCFault.ALDL,433132,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA7.almPLCFault.ATRM,433134,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chilled Water Pump Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA8.Alarm.ALDL,433154,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA8.Alarm.ATRM,433156,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA8.almPLCFault.ALDL,433166,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA8.almPLCFault.ATRM,433168,Float,1,R/W,1000,,,,,,,,,,"RWPS (Chiller SYS Com) Chiller Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA9.Alarm.ALDL,433190,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA9.Alarm.ATRM,433192,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA9.almPLCFault.ALDL,433202,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA9.almPLCFault.ATRM,433204,Float,1,R/W,1000,,,,,,,,,,"RWPS (Doas SYS Com) Supply Fan Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA10.Alarm.ALDL,433224,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA10.Alarm.ATRM,433226,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA10.almPLCFault.ALDL,433236,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA10.almPLCFault.ATRM,433238,Float,1,R/W,1000,,,,,,,,,,"RWPS (FCU Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA11.Alarm.ALDL,433260,Float,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA11.Alarm.ATRM,433262,Float,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA11.almPLCFault.ALDL,433272,Float,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA11.almPLCFault.ATRM,433274,Float,1,R/W,1000,,,,,,,,,,"RWPS (EF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA12.Alarm.ALDL,433294,Float,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA12.Alarm.ATRM,433296,Float,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_HCP_001_1_XA12.almPLCFault.ALDL,433306,Float,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_HCP_001_1_XA12.almPLCFault.ATRM,433308,Float,1,R/W,1000,,,,,,,,,,"RWPS (SF Com) Fan Failure Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_LSH_0113_1_LH.Alarm.ALDL,433330,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_LSH_0113_1_LH.Alarm.ATRM,433332,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_LSH_0113_1_LH.almPLCFault.ALDL,433342,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_LSH_0113_1_LH.almPLCFault.ATRM,433344,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_LSH_0113_2_LH.Alarm.ALDL,433364,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_LSH_0113_2_LH.Alarm.ATRM,433366,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_LSH_0113_2_LH.almPLCFault.ALDL,433376,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_LSH_0113_2_LH.almPLCFault.ATRM,433378,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room High Level Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_NET_001_1_JA.Alarm.ALDL,433400,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_NET_001_1_JA.Alarm.ATRM,433402,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_NET_001_1_JA.almPLCFault.ALDL,433412,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_NET_001_1_JA.almPLCFault.ATRM,433414,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel DC Power Ok: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_NET_001_1_ZS.Alarm.ALDL,433434,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_NET_001_1_ZS.Alarm.ATRM,433436,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_NET_001_1_ZS.almPLCFault.ALDL,433446,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_NET_001_1_ZS.almPLCFault.ATRM,433448,Float,1,R/W,1000,,,,,,,,,,"RWPS Net Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PFC_0112_INHIBIT.Alarm.ALDL,433470,Float,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PFC_0112_INHIBIT.Alarm.ATRM,433472,Float,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PFC_0112_INHIBIT.almPLCFault.ALDL,433482,Float,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PFC_0112_INHIBIT.almPLCFault.ATRM,433484,Float,1,R/W,1000,,,,,,,,,,"PFCC Inhibit Signal Active Warning: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PL.Alarm.ALDL,433504,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PL.Alarm.ATRM,433506,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_1_PL.almPLCFault.ALDL,433516,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_1_PL.almPLCFault.ATRM,433518,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PL.Alarm.ALDL,433540,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PL.Alarm.ATRM,433542,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PIT_0102_2_PL.almPLCFault.ALDL,433552,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PIT_0102_2_PL.almPLCFault.ATRM,433554,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Low Pressure Lockout : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PLC_001_1_JA.Alarm.ALDL,433574,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PLC_001_1_JA.Alarm.ATRM,433576,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PLC_001_1_JA.almPLCFault.ALDL,433586,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PLC_001_1_JA.almPLCFault.ATRM,433588,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel DC Power Ok : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PLC_001_1_ZS.Alarm.ALDL,433610,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PLC_001_1_ZS.Alarm.ATRM,433612,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PLC_001_1_ZS.almPLCFault.ALDL,433622,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PLC_001_1_ZS.almPLCFault.ATRM,433624,Float,1,R/W,1000,,,,,,,,,,"RWPS Plc Panel Door Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_1_PL.Alarm.ALDL,433644,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_1_PL.Alarm.ATRM,433646,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_1_PL.almPLCFault.ALDL,433656,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_1_PL.almPLCFault.ATRM,433658,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_2_PL.Alarm.ALDL,433680,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_2_PL.Alarm.ATRM,433682,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_2_PL.almPLCFault.ALDL,433692,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_2_PL.almPLCFault.ATRM,433694,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_3_PL.Alarm.ALDL,433714,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_3_PL.Alarm.ATRM,433716,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_3_PL.almPLCFault.ALDL,433726,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_3_PL.almPLCFault.ATRM,433728,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_4_PL.Alarm.ALDL,433750,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_4_PL.Alarm.ATRM,433752,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_4_PL.almPLCFault.ALDL,433762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_4_PL.almPLCFault.ATRM,433764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_5_PL.Alarm.ALDL,433784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_5_PL.Alarm.ATRM,433786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_5_PL.almPLCFault.ALDL,433796,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_5_PL.almPLCFault.ATRM,433798,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_6_PL.Alarm.ALDL,433820,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_6_PL.Alarm.ATRM,433822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_6_PL.almPLCFault.ALDL,433832,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_6_PL.almPLCFault.ATRM,433834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_7_PL.Alarm.ALDL,433854,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_7_PL.Alarm.ATRM,433856,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_7_PL.almPLCFault.ALDL,433866,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_7_PL.almPLCFault.ATRM,433868,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_8_PL.Alarm.ALDL,433890,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_8_PL.Alarm.ATRM,433892,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_8_PL.almPLCFault.ALDL,433902,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_8_PL.almPLCFault.ATRM,433904,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Pressure Loss : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_9_PL.Alarm.ALDL,433924,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_9_PL.Alarm.ATRM,433926,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_PS_0103_9_PL.almPLCFault.ALDL,433936,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_PS_0103_9_PL.almPLCFault.ATRM,433938,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Pressure Loss: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_1_XA.Alarm.ALDL,433960,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_1_XA.Alarm.ATRM,433962,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_1_XA.almPLCFault.ALDL,433972,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_1_XA.almPLCFault.ATRM,433974,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 1 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_2_XA.Alarm.ALDL,433994,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_2_XA.Alarm.ATRM,433996,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_2_XA.almPLCFault.ALDL,434006,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_2_XA.almPLCFault.ATRM,434008,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 2 Trip: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_3_XA.Alarm.ALDL,434030,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_3_XA.Alarm.ATRM,434032,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_3_XA.almPLCFault.ALDL,434042,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_3_XA.almPLCFault.ATRM,434044,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 3 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_4_XA.Alarm.ALDL,434064,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_4_XA.Alarm.ATRM,434066,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_REC_0131_4_XA.almPLCFault.ALDL,434076,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_REC_0131_4_XA.almPLCFault.ATRM,434078,Float,1,R/W,1000,,,,,,,,,,"RWPS Recloser 4 Trip : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0112_1_XA.Alarm.ALDL,434100,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0112_1_XA.Alarm.ATRM,434102,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0112_1_XA.almPLCFault.ALDL,434112,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0112_1_XA.almPLCFault.ATRM,434114,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Smoke Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0113_1_XA.Alarm.ALDL,434134,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0113_1_XA.Alarm.ATRM,434136,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0113_1_XA.almPLCFault.ALDL,434146,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0113_1_XA.almPLCFault.ATRM,434148,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0113_2_XA.Alarm.ALDL,434170,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0113_2_XA.Alarm.ATRM,434172,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0113_2_XA.almPLCFault.ALDL,434182,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0113_2_XA.almPLCFault.ATRM,434184,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Smoke Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0114_1_XA.Alarm.ALDL,434204,Float,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0114_1_XA.Alarm.ATRM,434206,Float,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0114_1_XA.almPLCFault.ALDL,434216,Float,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0114_1_XA.almPLCFault.ATRM,434218,Float,1,R/W,1000,,,,,,,,,,"RWPS West Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0114_2_XA.Alarm.ALDL,434240,Float,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0114_2_XA.Alarm.ATRM,434242,Float,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SD_0114_2_XA.almPLCFault.ALDL,434252,Float,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SD_0114_2_XA.almPLCFault.ATRM,434254,Float,1,R/W,1000,,,,,,,,,,"RWPS East Stairwell Smoke Detected : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_1_XA.Alarm.ALDL,434274,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_1_XA.Alarm.ATRM,434276,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_1_XA.almPLCFault.ALDL,434286,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_1_XA.almPLCFault.ATRM,434288,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_2_XA.Alarm.ALDL,434310,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_2_XA.Alarm.ATRM,434312,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_2_XA.almPLCFault.ALDL,434322,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_2_XA.almPLCFault.ATRM,434324,Float,1,R/W,1000,,,,,,,,,,"RWPS Swb-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3_XA1.Alarm.ALDL,434344,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3_XA1.Alarm.ATRM,434346,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3_XA1.almPLCFault.ALDL,434356,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3_XA1.almPLCFault.ATRM,434358,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-3 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3A_XA.Alarm.ALDL,434380,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3A_XA.Alarm.ATRM,434382,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3A_XA.almPLCFault.ALDL,434392,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3A_XA.almPLCFault.ATRM,434394,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3A SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3B_XA.Alarm.ALDL,434414,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3B_XA.Alarm.ATRM,434416,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_3B_XA.almPLCFault.ALDL,434426,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_3B_XA.almPLCFault.ATRM,434428,Float,1,R/W,1000,,,,,,,,,,"RWPS Swg-0112-3B SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_4_XA.Alarm.ALDL,434450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_4_XA.Alarm.ATRM,434452,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_4_XA.almPLCFault.ALDL,434462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_4_XA.almPLCFault.ATRM,434464,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_4_XA1.Alarm.ALDL,434484,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_4_XA1.Alarm.ATRM,434486,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_4_XA1.almPLCFault.ALDL,434496,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_4_XA1.almPLCFault.ATRM,434498,Float,1,R/W,1000,,,,,,,,,,"RWPS LP-0112-4 SPD Maintenance Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_5_XA.Alarm.ALDL,434520,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_5_XA.Alarm.ATRM,434522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_5_XA.almPLCFault.ALDL,434532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_5_XA.almPLCFault.ATRM,434534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0112-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_6_XA.Alarm.ALDL,434554,Float,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_6_XA.Alarm.ATRM,434556,Float,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0112_6_XA.almPLCFault.ALDL,434566,Float,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0112_6_XA.almPLCFault.ATRM,434568,Float,1,R/W,1000,,,,,,,,,,"RWPS Lp-0112-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0113_1_XA.Alarm.ALDL,434590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0113_1_XA.Alarm.ATRM,434592,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0113_1_XA.almPLCFault.ALDL,434602,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0113_1_XA.almPLCFault.ATRM,434604,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-1 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0113_2_XA.Alarm.ALDL,434624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0113_2_XA.Alarm.ATRM,434626,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_SPD_0113_2_XA.almPLCFault.ALDL,434636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_SPD_0113_2_XA.almPLCFault.ATRM,434638,Float,1,R/W,1000,,,,,,,,,,"RWPS Pp-0113-2 SPD Maintenance Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0111_1_TH.Alarm.ALDL,434660,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0111_1_TH.Alarm.ATRM,434662,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0111_1_TH.almPLCFault.ALDL,434672,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0111_1_TH.almPLCFault.ATRM,434674,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0112_1_TH.Alarm.ALDL,434694,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0112_1_TH.Alarm.ATRM,434696,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0112_1_TH.almPLCFault.ALDL,434706,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0112_1_TH.almPLCFault.ATRM,434708,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0113_1_TH.Alarm.ALDL,434730,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0113_1_TH.Alarm.ATRM,434732,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0113_1_TH.almPLCFault.ALDL,434742,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0113_1_TH.almPLCFault.ATRM,434744,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0113_2_TH.Alarm.ALDL,434764,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0113_2_TH.Alarm.ATRM,434766,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0113_2_TH.almPLCFault.ALDL,434776,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0113_2_TH.almPLCFault.ATRM,434778,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Room Heat Alarm : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0114_1_TH.Alarm.ALDL,434800,Float,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0114_1_TH.Alarm.ATRM,434802,Float,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0114_1_TH.almPLCFault.ALDL,434812,Float,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0114_1_TH.almPLCFault.ATRM,434814,Float,1,R/W,1000,,,,,,,,,,"RWPS West Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0114_2_TH.Alarm.ALDL,434834,Float,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0114_2_TH.Alarm.ATRM,434836,Float,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TE_0114_2_TH.almPLCFault.ALDL,434846,Float,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TE_0114_2_TH.almPLCFault.ATRM,434848,Float,1,R/W,1000,,,,,,,,,,"RWPS East Hoistway Heat Detector : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_LL.Alarm.ALDL,434870,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_LL.Alarm.ATRM,434872,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_LL.almPLCFault.ALDL,434882,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_LL.almPLCFault.ATRM,434884,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_TH1.Alarm.ALDL,434904,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_TH1.Alarm.ATRM,434906,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_TH1.almPLCFault.ALDL,434916,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_TH1.almPLCFault.ATRM,434918,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_TH2.Alarm.ALDL,434940,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_TH2.Alarm.ATRM,434942,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_TH2.almPLCFault.ALDL,434952,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_TH2.almPLCFault.ATRM,434954,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_XA.Alarm.ALDL,434974,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_XA.Alarm.ATRM,434976,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_1_XA.almPLCFault.ALDL,434986,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_1_XA.almPLCFault.ATRM,434988,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 1 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_LL.Alarm.ALDL,435010,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_LL.Alarm.ATRM,435012,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_LL.almPLCFault.ALDL,435022,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_LL.almPLCFault.ATRM,435024,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_TH1.Alarm.ALDL,435044,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_TH1.Alarm.ATRM,435046,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_TH1.almPLCFault.ALDL,435056,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_TH1.almPLCFault.ATRM,435058,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Oil High Temperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_TH2.Alarm.ALDL,435080,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_TH2.Alarm.ATRM,435082,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_TH2.almPLCFault.ALDL,435092,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_TH2.almPLCFault.ATRM,435094,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Winding High Temperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_XA.Alarm.ALDL,435114,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_XA.Alarm.ATRM,435116,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_TFR_0131_2_XA.almPLCFault.ALDL,435126,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_TFR_0131_2_XA.almPLCFault.ATRM,435128,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 2 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_1_JA.Alarm.ALDL,435150,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_1_JA.Alarm.ATRM,435152,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_1_JA.almPLCFault.ALDL,435162,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_1_JA.almPLCFault.ATRM,435164,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_1_ZS.Alarm.ALDL,435184,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_1_ZS.Alarm.ATRM,435186,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_1_ZS.almPLCFault.ALDL,435196,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_1_ZS.almPLCFault.ATRM,435198,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_2_JA.Alarm.ALDL,435220,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_2_JA.Alarm.ATRM,435222,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_2_JA.almPLCFault.ALDL,435232,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_2_JA.almPLCFault.ATRM,435234,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel UPS Alarm: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_2_ZS.Alarm.ALDL,435254,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_2_ZS.Alarm.ATRM,435256,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_UPS_001_2_ZS.almPLCFault.ALDL,435266,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_UPS_001_2_ZS.almPLCFault.ATRM,435268,Float,1,R/W,1000,,,,,,,,,,"RWPS Security UPS Panel Door Open: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0112_1A_ZA.Alarm.ALDL,435290,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0112_1A_ZA.Alarm.ATRM,435292,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0112_1A_ZA.almPLCFault.ALDL,435302,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0112_1A_ZA.almPLCFault.ATRM,435304,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Building Intrusion : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_1A_ZA.Alarm.ALDL,435324,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_1A_ZA.Alarm.ATRM,435326,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_1A_ZA.almPLCFault.ALDL,435336,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_1A_ZA.almPLCFault.ATRM,435338,Float,1,R/W,1000,,,,,,,,,,"RWPS West Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_1B_ZA.Alarm.ALDL,435360,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_1B_ZA.Alarm.ATRM,435362,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_1B_ZA.almPLCFault.ALDL,435372,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_1B_ZA.almPLCFault.ATRM,435374,Float,1,R/W,1000,,,,,,,,,,"RWPS West Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_2A_ZA.Alarm.ALDL,435394,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_2A_ZA.Alarm.ATRM,435396,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_2A_ZA.almPLCFault.ALDL,435406,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_2A_ZA.almPLCFault.ATRM,435408,Float,1,R/W,1000,,,,,,,,,,"RWPS East Pump Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_2B_ZA.Alarm.ALDL,435430,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_2B_ZA.Alarm.ATRM,435432,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XE_0113_2B_ZA.almPLCFault.ALDL,435442,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XE_0113_2B_ZA.almPLCFault.ATRM,435444,Float,1,R/W,1000,,,,,,,,,,"RWPS East Alcove Hatch Open : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_LL.Alarm.ALDL,435464,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_LL.Alarm.ATRM,435466,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_LL.almPLCFault.ALDL,435476,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_LL.almPLCFault.ATRM,435478,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Low Oil Level - 'LL-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_TH1.Alarm.ALDL,435500,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_TH1.Alarm.ATRM,435502,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_TH1.almPLCFault.ALDL,435512,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_TH1.almPLCFault.ATRM,435514,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Oil High Temperature - 'LT-1 (S-1)': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_TH2.Alarm.ALDL,435534,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_TH2.Alarm.ATRM,435536,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_TH2.almPLCFault.ALDL,435546,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_TH2.almPLCFault.ATRM,435548,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Winding High Temperature - 'WT1-1 (S-2): DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_XA.Alarm.ALDL,435570,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_XA.Alarm.ATRM,435572,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_3_XA.almPLCFault.ALDL,435582,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_3_XA.almPLCFault.ATRM,435584,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 3 Pressure Relief Device Activation - 'PRD-1': DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_LL.Alarm.ALDL,435604,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_LL.Alarm.ATRM,435606,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_LL.almPLCFault.ALDL,435616,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_LL.almPLCFault.ATRM,435618,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_TH1.Alarm.ALDL,435640,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_TH1.Alarm.ATRM,435642,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_TH1.almPLCFault.ALDL,435652,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_TH1.almPLCFault.ATRM,435654,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_TH2.Alarm.ALDL,435674,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_TH2.Alarm.ATRM,435676,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_TH2.almPLCFault.ALDL,435686,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_TH2.almPLCFault.ATRM,435688,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Winding High Teperature: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_XA.Alarm.ALDL,435710,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_XA.Alarm.ATRM,435712,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_4_XA.almPLCFault.ALDL,435722,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_4_XA.almPLCFault.ATRM,435724,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 4 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_LL.Alarm.ALDL,435744,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_LL.Alarm.ATRM,435746,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_LL.almPLCFault.ALDL,435756,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_LL.almPLCFault.ATRM,435758,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_TH1.Alarm.ALDL,435780,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_TH1.Alarm.ATRM,435782,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_TH1.almPLCFault.ALDL,435792,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_TH1.almPLCFault.ATRM,435794,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_TH2.Alarm.ALDL,435814,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_TH2.Alarm.ATRM,435816,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_TH2.almPLCFault.ALDL,435826,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_TH2.almPLCFault.ATRM,435828,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_XA.Alarm.ALDL,435850,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_XA.Alarm.ATRM,435852,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_5_XA.almPLCFault.ALDL,435862,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_5_XA.almPLCFault.ATRM,435864,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 5 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_LL.Alarm.ALDL,435884,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_LL.Alarm.ATRM,435886,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_LL.almPLCFault.ALDL,435896,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_LL.almPLCFault.ATRM,435898,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Low Oil Level : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_TH1.Alarm.ALDL,435920,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_TH1.Alarm.ATRM,435922,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_TH1.almPLCFault.ALDL,435932,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_TH1.almPLCFault.ATRM,435934,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Oil High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_TH2.Alarm.ALDL,435954,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_TH2.Alarm.ATRM,435956,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_TH2.almPLCFault.ALDL,435966,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_TH2.almPLCFault.ATRM,435968,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Winding High Teperature : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_XA.Alarm.ALDL,435990,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_XA.Alarm.ATRM,435992,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_XFR_0131_6_XA.almPLCFault.ALDL,436002,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_XFR_0131_6_XA.almPLCFault.ATRM,436004,Float,1,R/W,1000,,,,,,,,,,"RWPS Substation Transformer 6 Pressure Relief Device Activation: DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EASTMICRO_FAIL.Alarm.ALDL,436024,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EASTMICRO_FAIL.Alarm.ATRM,436026,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EASTMICRO_FAIL.almPLCFault.ALDL,436036,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EASTMICRO_FAIL.almPLCFault.ATRM,436038,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP1_FAIL.Alarm.ALDL,436060,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP1_FAIL.Alarm.ATRM,436062,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.ALDL,436072,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP1_FAIL.almPLCFault.ATRM,436074,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP2_FAIL.Alarm.ALDL,436094,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP2_FAIL.Alarm.ATRM,436096,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.ALDL,436106,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP2_FAIL.almPLCFault.ATRM,436108,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP9_FAIL.Alarm.ALDL,436130,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP9_FAIL.Alarm.ATRM,436132,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.ALDL,436142,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_EATON_PUMP9_FAIL.almPLCFault.ATRM,436144,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Easton Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_METER_VAULT_FAIL.Alarm.ALDL,436164,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_METER_VAULT_FAIL.Alarm.ATRM,436166,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_METER_VAULT_FAIL.almPLCFault.ALDL,436176,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_METER_VAULT_FAIL.almPLCFault.ATRM,436178,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To Meter Vault PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.ALDL,436200,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP1_FAIL.Alarm.ATRM,436202,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.ALDL,436212,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP1_FAIL.almPLCFault.ATRM,436214,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL710 Pump 1 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.ALDL,436234,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP2_FAIL.Alarm.ATRM,436236,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.ALDL,436246,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP2_FAIL.almPLCFault.ATRM,436248,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 2 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.ALDL,436270,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP9_FAIL.Alarm.ATRM,436272,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.ALDL,436282,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_SEL710_PUMP9_FAIL.almPLCFault.ATRM,436284,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To SEL 710 Pump 9 Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_TSR_PLC_FAIL.Alarm.ALDL,436304,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_TSR_PLC_FAIL.Alarm.ATRM,436306,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_TSR_PLC_FAIL.almPLCFault.ALDL,436316,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_TSR_PLC_FAIL.almPLCFault.ATRM,436318,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To TSR PLC Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_WESTMICRO_FAIL.Alarm.ALDL,436340,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_WESTMICRO_FAIL.Alarm.ATRM,436342,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: ddt_Alarm for handling alarms: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3260_COMM_WESTMICRO_FAIL.almPLCFault.ALDL,436352,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3260_COMM_WESTMICRO_FAIL.almPLCFault.ATRM,436354,Float,1,R/W,1000,,,,,,,,,,"RWPS PLC Communication To East Micro Pump Station Failure : DDT for DI Ladder DFB: Digital input fault routing - ladder based, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1.almFailToStrt.ALDL,436418,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1.almFailToStrt.ATRM,436420,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1.almFailToStop.ALDL,436430,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1.almFailToStop.ATRM,436432,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1.almMotorFailure.ALDL,436442,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1.almMotorFailure.ATRM,436444,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1.almPLCFault.ALDL,436454,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1.almPLCFault.ATRM,436456,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1.almSpeedDeviation.ALDL,436466,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_1.almSpeedDeviation.ATRM,436468,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2.almFailToStrt.ALDL,436554,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2.almFailToStrt.ATRM,436556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2.almFailToStop.ALDL,436566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2.almFailToStop.ATRM,436568,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2.almMotorFailure.ALDL,436578,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2.almMotorFailure.ATRM,436580,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2.almPLCFault.ALDL,436590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2.almPLCFault.ATRM,436592,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_2.almSpeedDeviation.ALDL,436602,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_2.almSpeedDeviation.ATRM,436604,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3.almFailToStrt.ALDL,436688,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3.almFailToStrt.ATRM,436690,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3.almFailToStop.ALDL,436700,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3.almFailToStop.ATRM,436702,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3.almMotorFailure.ALDL,436712,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3.almMotorFailure.ATRM,436714,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3.almPLCFault.ALDL,436724,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3.almPLCFault.ATRM,436726,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_3.almSpeedDeviation.ALDL,436736,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_3.almSpeedDeviation.ATRM,436738,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4.almFailToStrt.ALDL,436824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4.almFailToStrt.ATRM,436826,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4.almFailToStop.ALDL,436836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4.almFailToStop.ATRM,436838,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4.almMotorFailure.ALDL,436848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4.almMotorFailure.ATRM,436850,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4.almPLCFault.ALDL,436860,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4.almPLCFault.ATRM,436862,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_4.almSpeedDeviation.ALDL,436872,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_4.almSpeedDeviation.ATRM,436874,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5.almFailToStrt.ALDL,436958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5.almFailToStrt.ATRM,436960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5.almFailToStop.ALDL,436970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5.almFailToStop.ATRM,436972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5.almMotorFailure.ALDL,436982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5.almMotorFailure.ATRM,436984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5.almPLCFault.ALDL,436994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5.almPLCFault.ATRM,436996,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_5.almSpeedDeviation.ALDL,437006,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_5.almSpeedDeviation.ATRM,437008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6.almFailToStrt.ALDL,437094,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6.almFailToStrt.ATRM,437096,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6.almFailToStop.ALDL,437106,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6.almFailToStop.ATRM,437108,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6.almMotorFailure.ALDL,437118,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6.almMotorFailure.ATRM,437120,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6.almPLCFault.ALDL,437130,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6.almPLCFault.ATRM,437132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_6.almSpeedDeviation.ALDL,437142,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_6.almSpeedDeviation.ATRM,437144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7.almFailToStrt.ALDL,437228,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7.almFailToStrt.ATRM,437230,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7.almFailToStop.ALDL,437240,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7.almFailToStop.ATRM,437242,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7.almMotorFailure.ALDL,437252,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7.almMotorFailure.ATRM,437254,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7.almPLCFault.ALDL,437264,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7.almPLCFault.ATRM,437266,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_7.almSpeedDeviation.ALDL,437276,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_7.almSpeedDeviation.ATRM,437278,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8.almFailToStrt.ALDL,437364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8.almFailToStrt.ATRM,437366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8.almFailToStop.ALDL,437376,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8.almFailToStop.ATRM,437378,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8.almMotorFailure.ALDL,437388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8.almMotorFailure.ATRM,437390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8.almPLCFault.ALDL,437400,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8.almPLCFault.ATRM,437402,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_8.almSpeedDeviation.ALDL,437412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_8.almSpeedDeviation.ATRM,437414,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9.almFailToStrt.ALDL,437498,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9.almFailToStrt.ATRM,437500,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Start Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9.almFailToStop.ALDL,437510,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9.almFailToStop.ATRM,437512,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Fail to Sop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9.almMotorFailure.ALDL,437522,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9.almMotorFailure.ATRM,437524,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Motor Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9.almPLCFault.ALDL,437534,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9.almPLCFault.ATRM,437536,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_9.almSpeedDeviation.ALDL,437546,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_AFD_0103_9.almSpeedDeviation.ATRM,437548,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9: DDT for MTR VFD Ladder DFB: Motor with Variable Speed Motor, No Strings: Speed Deviation Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A.almFailToOpen.ALDL,437610,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A.almFailToOpen.ATRM,437612,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A.almFailToClose.ALDL,437622,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A.almFailToClose.ATRM,437624,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A.almActuatorFault.ALDL,437634,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A.almActuatorFault.ATRM,437636,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1A.almPLCFault.ALDL,437646,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1A.almPLCFault.ATRM,437648,Float,1,R/W,1000,,,,,,,,,,"RWPS West Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B.almFailToOpen.ALDL,437690,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B.almFailToOpen.ATRM,437692,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B.almFailToClose.ALDL,437702,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B.almFailToClose.ATRM,437704,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B.almActuatorFault.ALDL,437714,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B.almActuatorFault.ATRM,437716,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_1B.almPLCFault.ALDL,437726,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_1B.almPLCFault.ATRM,437728,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A.almFailToOpen.ALDL,437770,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A.almFailToOpen.ATRM,437772,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A.almFailToClose.ALDL,437782,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A.almFailToClose.ATRM,437784,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A.almActuatorFault.ALDL,437794,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A.almActuatorFault.ATRM,437796,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2A.almPLCFault.ALDL,437806,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2A.almPLCFault.ATRM,437808,Float,1,R/W,1000,,,,,,,,,,"RWPS East Intake Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B.almFailToOpen.ALDL,437850,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B.almFailToOpen.ATRM,437852,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B.almFailToClose.ALDL,437862,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B.almFailToClose.ATRM,437864,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B.almActuatorFault.ALDL,437874,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B.almActuatorFault.ATRM,437876,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0102_2B.almPLCFault.ALDL,437886,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0102_2B.almPLCFault.ATRM,437888,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A.almFailToOpen.ALDL,437930,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A.almFailToOpen.ATRM,437932,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A.almFailToClose.ALDL,437942,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A.almFailToClose.ATRM,437944,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A.almActuatorFault.ALDL,437954,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A.almActuatorFault.ATRM,437956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1A.almPLCFault.ALDL,437966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1A.almPLCFault.ATRM,437968,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C.almFailToOpen.ALDL,438010,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C.almFailToOpen.ATRM,438012,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C.almFailToClose.ALDL,438022,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C.almFailToClose.ATRM,438024,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C.almActuatorFault.ALDL,438034,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C.almActuatorFault.ATRM,438036,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_1C.almPLCFault.ALDL,438046,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_1C.almPLCFault.ATRM,438048,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A.almFailToOpen.ALDL,438090,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A.almFailToOpen.ATRM,438092,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A.almFailToClose.ALDL,438102,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A.almFailToClose.ATRM,438104,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A.almActuatorFault.ALDL,438114,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A.almActuatorFault.ATRM,438116,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2A.almPLCFault.ALDL,438126,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2A.almPLCFault.ATRM,438128,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C.almFailToOpen.ALDL,438170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C.almFailToOpen.ATRM,438172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C.almFailToClose.ALDL,438182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C.almFailToClose.ATRM,438184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C.almActuatorFault.ALDL,438194,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C.almActuatorFault.ATRM,438196,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_2C.almPLCFault.ALDL,438206,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_2C.almPLCFault.ATRM,438208,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A.almFailToOpen.ALDL,438250,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A.almFailToOpen.ATRM,438252,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A.almFailToClose.ALDL,438262,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A.almFailToClose.ATRM,438264,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A.almActuatorFault.ALDL,438274,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A.almActuatorFault.ATRM,438276,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3A.almPLCFault.ALDL,438286,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3A.almPLCFault.ATRM,438288,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C.almFailToOpen.ALDL,438330,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C.almFailToOpen.ATRM,438332,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C.almFailToClose.ALDL,438342,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C.almFailToClose.ATRM,438344,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C.almActuatorFault.ALDL,438354,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C.almActuatorFault.ATRM,438356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3C.almPLCFault.ALDL,438366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3C.almPLCFault.ATRM,438368,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D.almFailToOpen.ALDL,438410,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D.almFailToOpen.ATRM,438412,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D.almFailToClose.ALDL,438422,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D.almFailToClose.ATRM,438424,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D.almActuatorFault.ALDL,438434,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D.almActuatorFault.ATRM,438436,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_3D.almPLCFault.ALDL,438446,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_3D.almPLCFault.ATRM,438448,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A.almFailToOpen.ALDL,438490,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A.almFailToOpen.ATRM,438492,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A.almFailToClose.ALDL,438502,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A.almFailToClose.ATRM,438504,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A.almActuatorFault.ALDL,438514,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A.almActuatorFault.ATRM,438516,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4A.almPLCFault.ALDL,438526,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4A.almPLCFault.ATRM,438528,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C.almFailToOpen.ALDL,438570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C.almFailToOpen.ATRM,438572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C.almFailToClose.ALDL,438582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C.almFailToClose.ATRM,438584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C.almActuatorFault.ALDL,438594,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C.almActuatorFault.ATRM,438596,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4C.almPLCFault.ALDL,438606,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4C.almPLCFault.ATRM,438608,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D.almFailToOpen.ALDL,438650,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D.almFailToOpen.ATRM,438652,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D.almFailToClose.ALDL,438662,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D.almFailToClose.ATRM,438664,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D.almActuatorFault.ALDL,438674,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D.almActuatorFault.ATRM,438676,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_4D.almPLCFault.ALDL,438686,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_4D.almPLCFault.ATRM,438688,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A.almFailToOpen.ALDL,438730,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A.almFailToOpen.ATRM,438732,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A.almFailToClose.ALDL,438742,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A.almFailToClose.ATRM,438744,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A.almActuatorFault.ALDL,438754,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A.almActuatorFault.ATRM,438756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5A.almPLCFault.ALDL,438766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5A.almPLCFault.ATRM,438768,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C.almFailToOpen.ALDL,438810,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C.almFailToOpen.ATRM,438812,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C.almFailToClose.ALDL,438822,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C.almFailToClose.ATRM,438824,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C.almActuatorFault.ALDL,438834,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C.almActuatorFault.ATRM,438836,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5C.almPLCFault.ALDL,438846,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5C.almPLCFault.ATRM,438848,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D.almFailToOpen.ALDL,438890,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D.almFailToOpen.ATRM,438892,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D.almFailToClose.ALDL,438902,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D.almFailToClose.ATRM,438904,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D.almActuatorFault.ALDL,438914,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D.almActuatorFault.ATRM,438916,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_5D.almPLCFault.ALDL,438926,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_5D.almPLCFault.ATRM,438928,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A.almFailToOpen.ALDL,438970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A.almFailToOpen.ATRM,438972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A.almFailToClose.ALDL,438982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A.almFailToClose.ATRM,438984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A.almActuatorFault.ALDL,438994,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A.almActuatorFault.ATRM,438996,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6A.almPLCFault.ALDL,439006,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6A.almPLCFault.ATRM,439008,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C.almFailToOpen.ALDL,439050,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C.almFailToOpen.ATRM,439052,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C.almFailToClose.ALDL,439062,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C.almFailToClose.ATRM,439064,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C.almActuatorFault.ALDL,439074,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C.almActuatorFault.ATRM,439076,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6C.almPLCFault.ALDL,439086,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6C.almPLCFault.ATRM,439088,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D.almFailToOpen.ALDL,439130,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D.almFailToOpen.ATRM,439132,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D.almFailToClose.ALDL,439142,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D.almFailToClose.ATRM,439144,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D.almActuatorFault.ALDL,439154,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D.almActuatorFault.ATRM,439156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_6D.almPLCFault.ALDL,439166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_6D.almPLCFault.ATRM,439168,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A.almFailToOpen.ALDL,439210,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A.almFailToOpen.ATRM,439212,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A.almFailToClose.ALDL,439222,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A.almFailToClose.ATRM,439224,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A.almActuatorFault.ALDL,439234,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A.almActuatorFault.ATRM,439236,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7A.almPLCFault.ALDL,439246,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7A.almPLCFault.ATRM,439248,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C.almFailToOpen.ALDL,439290,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C.almFailToOpen.ATRM,439292,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C.almFailToClose.ALDL,439302,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C.almFailToClose.ATRM,439304,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C.almActuatorFault.ALDL,439314,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C.almActuatorFault.ATRM,439316,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7C.almPLCFault.ALDL,439326,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7C.almPLCFault.ATRM,439328,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D.almFailToOpen.ALDL,439370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D.almFailToOpen.ATRM,439372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D.almFailToClose.ALDL,439382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D.almFailToClose.ATRM,439384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D.almActuatorFault.ALDL,439394,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D.almActuatorFault.ATRM,439396,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_7D.almPLCFault.ALDL,439406,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_7D.almPLCFault.ATRM,439408,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A.almFailToOpen.ALDL,439450,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A.almFailToOpen.ATRM,439452,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A.almFailToClose.ALDL,439462,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A.almFailToClose.ATRM,439464,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A.almActuatorFault.ALDL,439474,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A.almActuatorFault.ATRM,439476,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8A.almPLCFault.ALDL,439486,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8A.almPLCFault.ATRM,439488,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C.almFailToOpen.ALDL,439530,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C.almFailToOpen.ATRM,439532,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C.almFailToClose.ALDL,439542,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C.almFailToClose.ATRM,439544,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C.almActuatorFault.ALDL,439554,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C.almActuatorFault.ATRM,439556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8C.almPLCFault.ALDL,439566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8C.almPLCFault.ATRM,439568,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D.almFailToOpen.ALDL,439610,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D.almFailToOpen.ATRM,439612,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D.almFailToClose.ALDL,439622,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D.almFailToClose.ATRM,439624,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D.almActuatorFault.ALDL,439634,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D.almActuatorFault.ATRM,439636,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_8D.almPLCFault.ALDL,439646,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_8D.almPLCFault.ATRM,439648,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Suction Bypass Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A.almFailToOpen.ALDL,439690,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A.almFailToOpen.ATRM,439692,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A.almFailToClose.ALDL,439702,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A.almFailToClose.ATRM,439704,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A.almActuatorFault.ALDL,439714,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A.almActuatorFault.ATRM,439716,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9A.almPLCFault.ALDL,439726,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9A.almPLCFault.ATRM,439728,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C.almFailToOpen.ALDL,439770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C.almFailToOpen.ATRM,439772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C.almFailToClose.ALDL,439782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C.almFailToClose.ATRM,439784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C.almActuatorFault.ALDL,439794,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C.almActuatorFault.ATRM,439796,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0103_9C.almPLCFault.ALDL,439806,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0103_9C.almPLCFault.ATRM,439808,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A.almFailToOpen.ALDL,439850,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A.almFailToOpen.ATRM,439852,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A.almFailToClose.ALDL,439862,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A.almFailToClose.ATRM,439864,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A.almActuatorFault.ALDL,439874,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A.almActuatorFault.ATRM,439876,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2A.almPLCFault.ALDL,439886,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2A.almPLCFault.ATRM,439888,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B.almFailToOpen.ALDL,439930,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B.almFailToOpen.ATRM,439932,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B.almFailToClose.ALDL,439942,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B.almFailToClose.ATRM,439944,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B.almActuatorFault.ALDL,439954,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B.almActuatorFault.ATRM,439956,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2B.almPLCFault.ALDL,439966,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2B.almPLCFault.ATRM,439968,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir West Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C.almFailToOpen.ALDL,440010,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C.almFailToOpen.ATRM,440012,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C.almFailToClose.ALDL,440022,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C.almFailToClose.ATRM,440024,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C.almActuatorFault.ALDL,440034,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C.almActuatorFault.ATRM,440036,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2C.almPLCFault.ALDL,440046,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2C.almPLCFault.ATRM,440048,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Suction Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D.almFailToOpen.ALDL,440090,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D.almFailToOpen.ATRM,440092,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Open Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D.almFailToClose.ALDL,440102,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D.almFailToClose.ATRM,440104,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Fail To Close Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D.almActuatorFault.ALDL,440114,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D.almActuatorFault.ATRM,440116,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: Actuator Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FV_0113_2D.almPLCFault.ALDL,440126,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FV_0113_2D.almPLCFault.ATRM,440128,Float,1,R/W,1000,,,,,,,,,,"RWPS To Reservoir East Discharge Valve: DDT for VLV2C Ladder DFB: Two Output Valve w/ Actuator Fault and Program Override, No Strings: PLC Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almBrokenLoop.ALDL,440168,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almBrokenLoop.ATRM,440170,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almUnderRange.ALDL,440180,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almUnderRange.ATRM,440182,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almOverRange.ALDL,440192,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almOverRange.ATRM,440194,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almPositionFailure.ALDL,440204,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almPositionFailure.ATRM,440206,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almPLCFault.ALDL,440216,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almPLCFault.ATRM,440218,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2A.almValveFailure.ALDL,440228,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2A.almValveFailure.ATRM,440230,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almBrokenLoop.ALDL,440278,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almBrokenLoop.ATRM,440280,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Broken Loop Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almUnderRange.ALDL,440290,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almUnderRange.ATRM,440292,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Under Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almOverRange.ALDL,440302,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almOverRange.ATRM,440304,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Over Range Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almPositionFailure.ALDL,440314,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almPositionFailure.ATRM,440316,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Position Failure DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almPLCFault.ALDL,440326,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almPLCFault.ATRM,440328,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: PLC IO Fault Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_FCV_0113_2B.almValveFailure.ALDL,440338,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Delay: Seconds before a fault will progress to alarm state." WA3252_FCV_0113_2B.almValveFailure.ATRM,440340,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side: DDT for VLVM Ladder DFB: Variable Speed Motor, No Strings: Valve Failure Alarm DDT: DDT for Alarm DFB, No Strings: Alarm Time Remaining: Seconds Remaining Until Alarm is Tripped" WA3252_AFD_0103_1_SI.Totalize.VALU,401156,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_1_SI.Totalize.VMAX,401158,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_1_SI.Totalize.LFCO,401160,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_1_SI.Totalize.FTTD,401162,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_1_SI.Totalize.FTYD,401164,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_1_SI.Totalize.FLOT,401166,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_1_SI.Totalize.DayTotal500,401170,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_1_SI.Totalize.FTTotal500,401172,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_1_SI.Totalize.LowFlowCutoff,401174,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_1_SI.Totalize.TimeDivider,401182,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_1_SI.Totalize.Total2Minute,401184,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_1_SI.Totalize.Total5thSec,401186,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_1_SI.Totalize.TotalToday,401188,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_1_SI.Totalize.TotalTotal,401190,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_2_SI.Totalize.VALU,401356,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_2_SI.Totalize.VMAX,401358,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_2_SI.Totalize.LFCO,401360,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_2_SI.Totalize.FTTD,401362,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_2_SI.Totalize.FTYD,401364,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_2_SI.Totalize.FLOT,401366,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_2_SI.Totalize.DayTotal500,401370,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_2_SI.Totalize.FTTotal500,401372,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_2_SI.Totalize.LowFlowCutoff,401374,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_2_SI.Totalize.TimeDivider,401382,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_2_SI.Totalize.Total2Minute,401384,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_2_SI.Totalize.Total5thSec,401386,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_2_SI.Totalize.TotalToday,401388,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_2_SI.Totalize.TotalTotal,401390,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_3_SI.Totalize.VALU,401556,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_3_SI.Totalize.VMAX,401558,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_3_SI.Totalize.LFCO,401560,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_3_SI.Totalize.FTTD,401562,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_3_SI.Totalize.FTYD,401564,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_3_SI.Totalize.FLOT,401566,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_3_SI.Totalize.DayTotal500,401570,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_3_SI.Totalize.FTTotal500,401572,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_3_SI.Totalize.LowFlowCutoff,401574,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_3_SI.Totalize.TimeDivider,401582,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_3_SI.Totalize.Total2Minute,401584,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_3_SI.Totalize.Total5thSec,401586,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_3_SI.Totalize.TotalToday,401588,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_3_SI.Totalize.TotalTotal,401590,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_4_SI.Totalize.VALU,401756,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_4_SI.Totalize.VMAX,401758,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_4_SI.Totalize.LFCO,401760,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_4_SI.Totalize.FTTD,401762,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_4_SI.Totalize.FTYD,401764,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_4_SI.Totalize.FLOT,401766,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_4_SI.Totalize.DayTotal500,401770,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_4_SI.Totalize.FTTotal500,401772,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_4_SI.Totalize.LowFlowCutoff,401774,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_4_SI.Totalize.TimeDivider,401782,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_4_SI.Totalize.Total2Minute,401784,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_4_SI.Totalize.Total5thSec,401786,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_4_SI.Totalize.TotalToday,401788,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_4_SI.Totalize.TotalTotal,401790,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_5_SI.Totalize.VALU,401956,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_5_SI.Totalize.VMAX,401958,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_5_SI.Totalize.LFCO,401960,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_5_SI.Totalize.FTTD,401962,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_5_SI.Totalize.FTYD,401964,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_5_SI.Totalize.FLOT,401966,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_5_SI.Totalize.DayTotal500,401970,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_5_SI.Totalize.FTTotal500,401972,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_5_SI.Totalize.LowFlowCutoff,401974,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_5_SI.Totalize.TimeDivider,401982,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_5_SI.Totalize.Total2Minute,401984,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_5_SI.Totalize.Total5thSec,401986,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_5_SI.Totalize.TotalToday,401988,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_5_SI.Totalize.TotalTotal,401990,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_6_SI.Totalize.VALU,402156,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_6_SI.Totalize.VMAX,402158,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_6_SI.Totalize.LFCO,402160,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_6_SI.Totalize.FTTD,402162,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_6_SI.Totalize.FTYD,402164,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_6_SI.Totalize.FLOT,402166,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_6_SI.Totalize.DayTotal500,402170,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_6_SI.Totalize.FTTotal500,402172,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_6_SI.Totalize.LowFlowCutoff,402174,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_6_SI.Totalize.TimeDivider,402182,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_6_SI.Totalize.Total2Minute,402184,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_6_SI.Totalize.Total5thSec,402186,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_6_SI.Totalize.TotalToday,402188,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_6_SI.Totalize.TotalTotal,402190,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_7_SI.Totalize.VALU,402356,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_7_SI.Totalize.VMAX,402358,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_7_SI.Totalize.LFCO,402360,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_7_SI.Totalize.FTTD,402362,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_7_SI.Totalize.FTYD,402364,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_7_SI.Totalize.FLOT,402366,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_7_SI.Totalize.DayTotal500,402370,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_7_SI.Totalize.FTTotal500,402372,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_7_SI.Totalize.LowFlowCutoff,402374,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_7_SI.Totalize.TimeDivider,402382,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_7_SI.Totalize.Total2Minute,402384,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_7_SI.Totalize.Total5thSec,402386,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_7_SI.Totalize.TotalToday,402388,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_7_SI.Totalize.TotalTotal,402390,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_8_SI.Totalize.VALU,402556,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_8_SI.Totalize.VMAX,402558,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_8_SI.Totalize.LFCO,402560,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_8_SI.Totalize.FTTD,402562,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_8_SI.Totalize.FTYD,402564,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_8_SI.Totalize.FLOT,402566,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_8_SI.Totalize.DayTotal500,402570,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_8_SI.Totalize.FTTotal500,402572,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_8_SI.Totalize.LowFlowCutoff,402574,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_8_SI.Totalize.TimeDivider,402582,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_8_SI.Totalize.Total2Minute,402584,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_8_SI.Totalize.Total5thSec,402586,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_8_SI.Totalize.TotalToday,402588,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_8_SI.Totalize.TotalTotal,402590,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_AFD_0103_9_SI.Totalize.VALU,402756,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_AFD_0103_9_SI.Totalize.VMAX,402758,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_AFD_0103_9_SI.Totalize.LFCO,402760,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_AFD_0103_9_SI.Totalize.FTTD,402762,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_AFD_0103_9_SI.Totalize.FTYD,402764,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_AFD_0103_9_SI.Totalize.FLOT,402766,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_AFD_0103_9_SI.Totalize.DayTotal500,402770,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_AFD_0103_9_SI.Totalize.FTTotal500,402772,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_AFD_0103_9_SI.Totalize.LowFlowCutoff,402774,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_AFD_0103_9_SI.Totalize.TimeDivider,402782,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_AFD_0103_9_SI.Totalize.Total2Minute,402784,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_AFD_0103_9_SI.Totalize.Total5thSec,402786,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_AFD_0103_9_SI.Totalize.TotalToday,402788,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_AFD_0103_9_SI.Totalize.TotalTotal,402790,Float,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI1.Totalize.VALU,402956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI1.Totalize.VMAX,402958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI1.Totalize.LFCO,402960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI1.Totalize.FTTD,402962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI1.Totalize.FTYD,402964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI1.Totalize.FLOT,402966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI1.Totalize.DayTotal500,402970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI1.Totalize.FTTotal500,402972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI1.Totalize.LowFlowCutoff,402974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI1.Totalize.TimeDivider,402982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI1.Totalize.Total2Minute,402984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI1.Totalize.Total5thSec,402986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI1.Totalize.TotalToday,402988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI1.Totalize.TotalTotal,402990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI2.Totalize.VALU,403156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI2.Totalize.VMAX,403158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI2.Totalize.LFCO,403160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI2.Totalize.FTTD,403162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI2.Totalize.FTYD,403164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI2.Totalize.FLOT,403166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI2.Totalize.DayTotal500,403170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI2.Totalize.FTTotal500,403172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI2.Totalize.LowFlowCutoff,403174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI2.Totalize.TimeDivider,403182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI2.Totalize.Total2Minute,403184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI2.Totalize.Total5thSec,403186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI2.Totalize.TotalToday,403188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI2.Totalize.TotalTotal,403190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI3.Totalize.VALU,403356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI3.Totalize.VMAX,403358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI3.Totalize.LFCO,403360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI3.Totalize.FTTD,403362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI3.Totalize.FTYD,403364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI3.Totalize.FLOT,403366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI3.Totalize.DayTotal500,403370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI3.Totalize.FTTotal500,403372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI3.Totalize.LowFlowCutoff,403374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI3.Totalize.TimeDivider,403382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI3.Totalize.Total2Minute,403384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI3.Totalize.Total5thSec,403386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI3.Totalize.TotalToday,403388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI3.Totalize.TotalTotal,403390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI4.Totalize.VALU,403556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI4.Totalize.VMAX,403558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI4.Totalize.LFCO,403560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI4.Totalize.FTTD,403562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI4.Totalize.FTYD,403564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI4.Totalize.FLOT,403566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI4.Totalize.DayTotal500,403570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI4.Totalize.FTTotal500,403572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI4.Totalize.LowFlowCutoff,403574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI4.Totalize.TimeDivider,403582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI4.Totalize.Total2Minute,403584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI4.Totalize.Total5thSec,403586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI4.Totalize.TotalToday,403588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI4.Totalize.TotalTotal,403590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI5.Totalize.VALU,403756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI5.Totalize.VMAX,403758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI5.Totalize.LFCO,403760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI5.Totalize.FTTD,403762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI5.Totalize.FTYD,403764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI5.Totalize.FLOT,403766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI5.Totalize.DayTotal500,403770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI5.Totalize.FTTotal500,403772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI5.Totalize.LowFlowCutoff,403774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI5.Totalize.TimeDivider,403782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI5.Totalize.Total2Minute,403784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI5.Totalize.Total5thSec,403786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI5.Totalize.TotalToday,403788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI5.Totalize.TotalTotal,403790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI6.Totalize.VALU,403956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI6.Totalize.VMAX,403958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI6.Totalize.LFCO,403960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI6.Totalize.FTTD,403962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI6.Totalize.FTYD,403964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI6.Totalize.FLOT,403966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI6.Totalize.DayTotal500,403970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI6.Totalize.FTTotal500,403972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI6.Totalize.LowFlowCutoff,403974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI6.Totalize.TimeDivider,403982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI6.Totalize.Total2Minute,403984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI6.Totalize.Total5thSec,403986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI6.Totalize.TotalToday,403988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI6.Totalize.TotalTotal,403990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI7.Totalize.VALU,404156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI7.Totalize.VMAX,404158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI7.Totalize.LFCO,404160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI7.Totalize.FTTD,404162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI7.Totalize.FTYD,404164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI7.Totalize.FLOT,404166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI7.Totalize.DayTotal500,404170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI7.Totalize.FTTotal500,404172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI7.Totalize.LowFlowCutoff,404174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI7.Totalize.TimeDivider,404182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI7.Totalize.Total2Minute,404184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI7.Totalize.Total5thSec,404186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI7.Totalize.TotalToday,404188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI7.Totalize.TotalTotal,404190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI8.Totalize.VALU,404356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI8.Totalize.VMAX,404358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI8.Totalize.LFCO,404360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI8.Totalize.FTTD,404362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI8.Totalize.FTYD,404364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI8.Totalize.FLOT,404366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI8.Totalize.DayTotal500,404370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI8.Totalize.FTTotal500,404372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI8.Totalize.LowFlowCutoff,404374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI8.Totalize.TimeDivider,404382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI8.Totalize.Total2Minute,404384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI8.Totalize.Total5thSec,404386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI8.Totalize.TotalToday,404388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI8.Totalize.TotalTotal,404390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_CP_0116_1_FI9.Totalize.VALU,404556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_CP_0116_1_FI9.Totalize.VMAX,404558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_CP_0116_1_FI9.Totalize.LFCO,404560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_CP_0116_1_FI9.Totalize.FTTD,404562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_CP_0116_1_FI9.Totalize.FTYD,404564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_CP_0116_1_FI9.Totalize.FLOT,404566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_CP_0116_1_FI9.Totalize.DayTotal500,404570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_CP_0116_1_FI9.Totalize.FTTotal500,404572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_CP_0116_1_FI9.Totalize.LowFlowCutoff,404574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_CP_0116_1_FI9.Totalize.TimeDivider,404582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_CP_0116_1_FI9.Totalize.Total2Minute,404584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_CP_0116_1_FI9.Totalize.Total5thSec,404586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_CP_0116_1_FI9.Totalize.TotalToday,404588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_CP_0116_1_FI9.Totalize.TotalTotal,404590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FCV_0113_2A_ZI.Totalize.VALU,404756,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FCV_0113_2A_ZI.Totalize.VMAX,404758,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FCV_0113_2A_ZI.Totalize.LFCO,404760,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FCV_0113_2A_ZI.Totalize.FTTD,404762,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FCV_0113_2A_ZI.Totalize.FTYD,404764,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FCV_0113_2A_ZI.Totalize.FLOT,404766,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FCV_0113_2A_ZI.Totalize.DayTotal500,404770,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FCV_0113_2A_ZI.Totalize.FTTotal500,404772,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2A_ZI.Totalize.LowFlowCutoff,404774,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FCV_0113_2A_ZI.Totalize.TimeDivider,404782,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FCV_0113_2A_ZI.Totalize.Total2Minute,404784,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FCV_0113_2A_ZI.Totalize.Total5thSec,404786,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FCV_0113_2A_ZI.Totalize.TotalToday,404788,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FCV_0113_2A_ZI.Totalize.TotalTotal,404790,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FCV_0113_2B_ZI.Totalize.VALU,404956,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FCV_0113_2B_ZI.Totalize.VMAX,404958,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FCV_0113_2B_ZI.Totalize.LFCO,404960,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FCV_0113_2B_ZI.Totalize.FTTD,404962,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FCV_0113_2B_ZI.Totalize.FTYD,404964,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FCV_0113_2B_ZI.Totalize.FLOT,404966,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FCV_0113_2B_ZI.Totalize.DayTotal500,404970,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FCV_0113_2B_ZI.Totalize.FTTotal500,404972,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FCV_0113_2B_ZI.Totalize.LowFlowCutoff,404974,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FCV_0113_2B_ZI.Totalize.TimeDivider,404982,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FCV_0113_2B_ZI.Totalize.Total2Minute,404984,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FCV_0113_2B_ZI.Totalize.Total5thSec,404986,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FCV_0113_2B_ZI.Totalize.TotalToday,404988,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FCV_0113_2B_ZI.Totalize.TotalTotal,404990,Float,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FIT_0113_2A_FI.Totalize.VALU,405156,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FIT_0113_2A_FI.Totalize.VMAX,405158,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FIT_0113_2A_FI.Totalize.LFCO,405160,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FIT_0113_2A_FI.Totalize.FTTD,405162,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FIT_0113_2A_FI.Totalize.FTYD,405164,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FIT_0113_2A_FI.Totalize.FLOT,405166,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FIT_0113_2A_FI.Totalize.DayTotal500,405170,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FIT_0113_2A_FI.Totalize.FTTotal500,405172,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FIT_0113_2A_FI.Totalize.LowFlowCutoff,405174,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FIT_0113_2A_FI.Totalize.TimeDivider,405182,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FIT_0113_2A_FI.Totalize.Total2Minute,405184,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FIT_0113_2A_FI.Totalize.Total5thSec,405186,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FIT_0113_2A_FI.Totalize.TotalToday,405188,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FIT_0113_2A_FI.Totalize.TotalTotal,405190,Float,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_1B_ZI.Totalize.VALU,405356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_1B_ZI.Totalize.VMAX,405358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_1B_ZI.Totalize.LFCO,405360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_1B_ZI.Totalize.FTTD,405362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_1B_ZI.Totalize.FTYD,405364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_1B_ZI.Totalize.FLOT,405366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_1B_ZI.Totalize.DayTotal500,405370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_1B_ZI.Totalize.FTTotal500,405372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_1B_ZI.Totalize.LowFlowCutoff,405374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_1B_ZI.Totalize.TimeDivider,405382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_1B_ZI.Totalize.Total2Minute,405384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_1B_ZI.Totalize.Total5thSec,405386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_1B_ZI.Totalize.TotalToday,405388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_1B_ZI.Totalize.TotalTotal,405390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_2B_ZI.Totalize.VALU,405556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_2B_ZI.Totalize.VMAX,405558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_2B_ZI.Totalize.LFCO,405560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_2B_ZI.Totalize.FTTD,405562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_2B_ZI.Totalize.FTYD,405564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_2B_ZI.Totalize.FLOT,405566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_2B_ZI.Totalize.DayTotal500,405570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_2B_ZI.Totalize.FTTotal500,405572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_2B_ZI.Totalize.LowFlowCutoff,405574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_2B_ZI.Totalize.TimeDivider,405582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_2B_ZI.Totalize.Total2Minute,405584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_2B_ZI.Totalize.Total5thSec,405586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_2B_ZI.Totalize.TotalToday,405588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_2B_ZI.Totalize.TotalTotal,405590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_3B_ZI.Totalize.VALU,405756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_3B_ZI.Totalize.VMAX,405758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_3B_ZI.Totalize.LFCO,405760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_3B_ZI.Totalize.FTTD,405762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_3B_ZI.Totalize.FTYD,405764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_3B_ZI.Totalize.FLOT,405766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_3B_ZI.Totalize.DayTotal500,405770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_3B_ZI.Totalize.FTTotal500,405772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_3B_ZI.Totalize.LowFlowCutoff,405774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_3B_ZI.Totalize.TimeDivider,405782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_3B_ZI.Totalize.Total2Minute,405784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_3B_ZI.Totalize.Total5thSec,405786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_3B_ZI.Totalize.TotalToday,405788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_3B_ZI.Totalize.TotalTotal,405790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_4B_ZI.Totalize.VALU,405956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_4B_ZI.Totalize.VMAX,405958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_4B_ZI.Totalize.LFCO,405960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_4B_ZI.Totalize.FTTD,405962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_4B_ZI.Totalize.FTYD,405964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_4B_ZI.Totalize.FLOT,405966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_4B_ZI.Totalize.DayTotal500,405970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_4B_ZI.Totalize.FTTotal500,405972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_4B_ZI.Totalize.LowFlowCutoff,405974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_4B_ZI.Totalize.TimeDivider,405982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_4B_ZI.Totalize.Total2Minute,405984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_4B_ZI.Totalize.Total5thSec,405986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_4B_ZI.Totalize.TotalToday,405988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_4B_ZI.Totalize.TotalTotal,405990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_5B_ZI.Totalize.VALU,406156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_5B_ZI.Totalize.VMAX,406158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_5B_ZI.Totalize.LFCO,406160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_5B_ZI.Totalize.FTTD,406162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_5B_ZI.Totalize.FTYD,406164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_5B_ZI.Totalize.FLOT,406166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_5B_ZI.Totalize.DayTotal500,406170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_5B_ZI.Totalize.FTTotal500,406172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_5B_ZI.Totalize.LowFlowCutoff,406174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_5B_ZI.Totalize.TimeDivider,406182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_5B_ZI.Totalize.Total2Minute,406184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_5B_ZI.Totalize.Total5thSec,406186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_5B_ZI.Totalize.TotalToday,406188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_5B_ZI.Totalize.TotalTotal,406190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_6B_ZI.Totalize.VALU,406356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_6B_ZI.Totalize.VMAX,406358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_6B_ZI.Totalize.LFCO,406360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_6B_ZI.Totalize.FTTD,406362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_6B_ZI.Totalize.FTYD,406364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_6B_ZI.Totalize.FLOT,406366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_6B_ZI.Totalize.DayTotal500,406370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_6B_ZI.Totalize.FTTotal500,406372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_6B_ZI.Totalize.LowFlowCutoff,406374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_6B_ZI.Totalize.TimeDivider,406382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_6B_ZI.Totalize.Total2Minute,406384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_6B_ZI.Totalize.Total5thSec,406386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_6B_ZI.Totalize.TotalToday,406388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_6B_ZI.Totalize.TotalTotal,406390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_7B_ZI.Totalize.VALU,406556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_7B_ZI.Totalize.VMAX,406558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_7B_ZI.Totalize.LFCO,406560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_7B_ZI.Totalize.FTTD,406562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_7B_ZI.Totalize.FTYD,406564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_7B_ZI.Totalize.FLOT,406566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_7B_ZI.Totalize.DayTotal500,406570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_7B_ZI.Totalize.FTTotal500,406572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_7B_ZI.Totalize.LowFlowCutoff,406574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_7B_ZI.Totalize.TimeDivider,406582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_7B_ZI.Totalize.Total2Minute,406584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_7B_ZI.Totalize.Total5thSec,406586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_7B_ZI.Totalize.TotalToday,406588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_7B_ZI.Totalize.TotalTotal,406590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_8B_ZI.Totalize.VALU,406756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_8B_ZI.Totalize.VMAX,406758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_8B_ZI.Totalize.LFCO,406760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_8B_ZI.Totalize.FTTD,406762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_8B_ZI.Totalize.FTYD,406764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_8B_ZI.Totalize.FLOT,406766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_8B_ZI.Totalize.DayTotal500,406770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_8B_ZI.Totalize.FTTotal500,406772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_8B_ZI.Totalize.LowFlowCutoff,406774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_8B_ZI.Totalize.TimeDivider,406782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_8B_ZI.Totalize.Total2Minute,406784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_8B_ZI.Totalize.Total5thSec,406786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_8B_ZI.Totalize.TotalToday,406788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_8B_ZI.Totalize.TotalTotal,406790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_FV_0103_9B_ZI.Totalize.VALU,406956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_FV_0103_9B_ZI.Totalize.VMAX,406958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_FV_0103_9B_ZI.Totalize.LFCO,406960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_FV_0103_9B_ZI.Totalize.FTTD,406962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_FV_0103_9B_ZI.Totalize.FTYD,406964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_FV_0103_9B_ZI.Totalize.FLOT,406966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_FV_0103_9B_ZI.Totalize.DayTotal500,406970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_FV_0103_9B_ZI.Totalize.FTTotal500,406972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_FV_0103_9B_ZI.Totalize.LowFlowCutoff,406974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_FV_0103_9B_ZI.Totalize.TimeDivider,406982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_FV_0103_9B_ZI.Totalize.Total2Minute,406984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_FV_0103_9B_ZI.Totalize.Total5thSec,406986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_FV_0103_9B_ZI.Totalize.TotalToday,406988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_FV_0103_9B_ZI.Totalize.TotalTotal,406990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_1_VI1.Totalize.VALU,407156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_1_VI1.Totalize.VMAX,407158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_1_VI1.Totalize.LFCO,407160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_1_VI1.Totalize.FTTD,407162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_1_VI1.Totalize.FTYD,407164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_1_VI1.Totalize.FLOT,407166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_1_VI1.Totalize.DayTotal500,407170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_1_VI1.Totalize.FTTotal500,407172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI1.Totalize.LowFlowCutoff,407174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_1_VI1.Totalize.TimeDivider,407182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_1_VI1.Totalize.Total2Minute,407184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_1_VI1.Totalize.Total5thSec,407186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_1_VI1.Totalize.TotalToday,407188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_1_VI1.Totalize.TotalTotal,407190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_1_VI2.Totalize.VALU,407356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_1_VI2.Totalize.VMAX,407358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_1_VI2.Totalize.LFCO,407360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_1_VI2.Totalize.FTTD,407362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_1_VI2.Totalize.FTYD,407364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_1_VI2.Totalize.FLOT,407366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_1_VI2.Totalize.DayTotal500,407370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_1_VI2.Totalize.FTTotal500,407372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI2.Totalize.LowFlowCutoff,407374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_1_VI2.Totalize.TimeDivider,407382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_1_VI2.Totalize.Total2Minute,407384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_1_VI2.Totalize.Total5thSec,407386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_1_VI2.Totalize.TotalToday,407388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_1_VI2.Totalize.TotalTotal,407390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_1_VI3.Totalize.VALU,407556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_1_VI3.Totalize.VMAX,407558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_1_VI3.Totalize.LFCO,407560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_1_VI3.Totalize.FTTD,407562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_1_VI3.Totalize.FTYD,407564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_1_VI3.Totalize.FLOT,407566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_1_VI3.Totalize.DayTotal500,407570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_1_VI3.Totalize.FTTotal500,407572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI3.Totalize.LowFlowCutoff,407574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_1_VI3.Totalize.TimeDivider,407582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_1_VI3.Totalize.Total2Minute,407584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_1_VI3.Totalize.Total5thSec,407586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_1_VI3.Totalize.TotalToday,407588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_1_VI3.Totalize.TotalTotal,407590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_1_VI4.Totalize.VALU,407756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_1_VI4.Totalize.VMAX,407758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_1_VI4.Totalize.LFCO,407760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_1_VI4.Totalize.FTTD,407762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_1_VI4.Totalize.FTYD,407764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_1_VI4.Totalize.FLOT,407766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_1_VI4.Totalize.DayTotal500,407770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_1_VI4.Totalize.FTTotal500,407772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_1_VI4.Totalize.LowFlowCutoff,407774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_1_VI4.Totalize.TimeDivider,407782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_1_VI4.Totalize.Total2Minute,407784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_1_VI4.Totalize.Total5thSec,407786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_1_VI4.Totalize.TotalToday,407788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_1_VI4.Totalize.TotalTotal,407790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_2_VI1.Totalize.VALU,407956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_2_VI1.Totalize.VMAX,407958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_2_VI1.Totalize.LFCO,407960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_2_VI1.Totalize.FTTD,407962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_2_VI1.Totalize.FTYD,407964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_2_VI1.Totalize.FLOT,407966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_2_VI1.Totalize.DayTotal500,407970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_2_VI1.Totalize.FTTotal500,407972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI1.Totalize.LowFlowCutoff,407974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_2_VI1.Totalize.TimeDivider,407982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_2_VI1.Totalize.Total2Minute,407984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_2_VI1.Totalize.Total5thSec,407986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_2_VI1.Totalize.TotalToday,407988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_2_VI1.Totalize.TotalTotal,407990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_2_VI2.Totalize.VALU,408156,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_2_VI2.Totalize.VMAX,408158,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_2_VI2.Totalize.LFCO,408160,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_2_VI2.Totalize.FTTD,408162,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_2_VI2.Totalize.FTYD,408164,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_2_VI2.Totalize.FLOT,408166,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_2_VI2.Totalize.DayTotal500,408170,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_2_VI2.Totalize.FTTotal500,408172,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI2.Totalize.LowFlowCutoff,408174,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_2_VI2.Totalize.TimeDivider,408182,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_2_VI2.Totalize.Total2Minute,408184,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_2_VI2.Totalize.Total5thSec,408186,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_2_VI2.Totalize.TotalToday,408188,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_2_VI2.Totalize.TotalTotal,408190,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_2_VI3.Totalize.VALU,408356,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_2_VI3.Totalize.VMAX,408358,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_2_VI3.Totalize.LFCO,408360,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_2_VI3.Totalize.FTTD,408362,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_2_VI3.Totalize.FTYD,408364,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_2_VI3.Totalize.FLOT,408366,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_2_VI3.Totalize.DayTotal500,408370,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_2_VI3.Totalize.FTTotal500,408372,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI3.Totalize.LowFlowCutoff,408374,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_2_VI3.Totalize.TimeDivider,408382,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_2_VI3.Totalize.Total2Minute,408384,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_2_VI3.Totalize.Total5thSec,408386,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_2_VI3.Totalize.TotalToday,408388,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_2_VI3.Totalize.TotalTotal,408390,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_2_VI4.Totalize.VALU,408556,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_2_VI4.Totalize.VMAX,408558,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_2_VI4.Totalize.LFCO,408560,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_2_VI4.Totalize.FTTD,408562,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_2_VI4.Totalize.FTYD,408564,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_2_VI4.Totalize.FLOT,408566,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_2_VI4.Totalize.DayTotal500,408570,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_2_VI4.Totalize.FTTotal500,408572,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_2_VI4.Totalize.LowFlowCutoff,408574,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_2_VI4.Totalize.TimeDivider,408582,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_2_VI4.Totalize.Total2Minute,408584,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_2_VI4.Totalize.Total5thSec,408586,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_2_VI4.Totalize.TotalToday,408588,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_2_VI4.Totalize.TotalTotal,408590,Float,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_3_VI1.Totalize.VALU,408756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_3_VI1.Totalize.VMAX,408758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_3_VI1.Totalize.LFCO,408760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_3_VI1.Totalize.FTTD,408762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_3_VI1.Totalize.FTYD,408764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_3_VI1.Totalize.FLOT,408766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_3_VI1.Totalize.DayTotal500,408770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_3_VI1.Totalize.FTTotal500,408772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI1.Totalize.LowFlowCutoff,408774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_3_VI1.Totalize.TimeDivider,408782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_3_VI1.Totalize.Total2Minute,408784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_3_VI1.Totalize.Total5thSec,408786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_3_VI1.Totalize.TotalToday,408788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_3_VI1.Totalize.TotalTotal,408790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_3_VI2.Totalize.VALU,408956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_3_VI2.Totalize.VMAX,408958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_3_VI2.Totalize.LFCO,408960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_3_VI2.Totalize.FTTD,408962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_3_VI2.Totalize.FTYD,408964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_3_VI2.Totalize.FLOT,408966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_3_VI2.Totalize.DayTotal500,408970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_3_VI2.Totalize.FTTotal500,408972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI2.Totalize.LowFlowCutoff,408974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_3_VI2.Totalize.TimeDivider,408982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_3_VI2.Totalize.Total2Minute,408984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_3_VI2.Totalize.Total5thSec,408986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_3_VI2.Totalize.TotalToday,408988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_3_VI2.Totalize.TotalTotal,408990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_3_VI3.Totalize.VALU,409156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_3_VI3.Totalize.VMAX,409158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_3_VI3.Totalize.LFCO,409160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_3_VI3.Totalize.FTTD,409162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_3_VI3.Totalize.FTYD,409164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_3_VI3.Totalize.FLOT,409166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_3_VI3.Totalize.DayTotal500,409170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_3_VI3.Totalize.FTTotal500,409172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI3.Totalize.LowFlowCutoff,409174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_3_VI3.Totalize.TimeDivider,409182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_3_VI3.Totalize.Total2Minute,409184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_3_VI3.Totalize.Total5thSec,409186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_3_VI3.Totalize.TotalToday,409188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_3_VI3.Totalize.TotalTotal,409190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_3_VI4.Totalize.VALU,409356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_3_VI4.Totalize.VMAX,409358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_3_VI4.Totalize.LFCO,409360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_3_VI4.Totalize.FTTD,409362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_3_VI4.Totalize.FTYD,409364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_3_VI4.Totalize.FLOT,409366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_3_VI4.Totalize.DayTotal500,409370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_3_VI4.Totalize.FTTotal500,409372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_3_VI4.Totalize.LowFlowCutoff,409374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_3_VI4.Totalize.TimeDivider,409382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_3_VI4.Totalize.Total2Minute,409384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_3_VI4.Totalize.Total5thSec,409386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_3_VI4.Totalize.TotalToday,409388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_3_VI4.Totalize.TotalTotal,409390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_4_VI1.Totalize.VALU,409556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_4_VI1.Totalize.VMAX,409558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_4_VI1.Totalize.LFCO,409560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_4_VI1.Totalize.FTTD,409562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_4_VI1.Totalize.FTYD,409564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_4_VI1.Totalize.FLOT,409566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_4_VI1.Totalize.DayTotal500,409570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_4_VI1.Totalize.FTTotal500,409572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI1.Totalize.LowFlowCutoff,409574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_4_VI1.Totalize.TimeDivider,409582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_4_VI1.Totalize.Total2Minute,409584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_4_VI1.Totalize.Total5thSec,409586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_4_VI1.Totalize.TotalToday,409588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_4_VI1.Totalize.TotalTotal,409590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_4_VI2.Totalize.VALU,409756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_4_VI2.Totalize.VMAX,409758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_4_VI2.Totalize.LFCO,409760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_4_VI2.Totalize.FTTD,409762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_4_VI2.Totalize.FTYD,409764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_4_VI2.Totalize.FLOT,409766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_4_VI2.Totalize.DayTotal500,409770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_4_VI2.Totalize.FTTotal500,409772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI2.Totalize.LowFlowCutoff,409774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_4_VI2.Totalize.TimeDivider,409782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_4_VI2.Totalize.Total2Minute,409784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_4_VI2.Totalize.Total5thSec,409786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_4_VI2.Totalize.TotalToday,409788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_4_VI2.Totalize.TotalTotal,409790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_4_VI3.Totalize.VALU,409956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_4_VI3.Totalize.VMAX,409958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_4_VI3.Totalize.LFCO,409960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_4_VI3.Totalize.FTTD,409962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_4_VI3.Totalize.FTYD,409964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_4_VI3.Totalize.FLOT,409966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_4_VI3.Totalize.DayTotal500,409970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_4_VI3.Totalize.FTTotal500,409972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI3.Totalize.LowFlowCutoff,409974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_4_VI3.Totalize.TimeDivider,409982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_4_VI3.Totalize.Total2Minute,409984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_4_VI3.Totalize.Total5thSec,409986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_4_VI3.Totalize.TotalToday,409988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_4_VI3.Totalize.TotalTotal,409990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_4_VI4.Totalize.VALU,410156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_4_VI4.Totalize.VMAX,410158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_4_VI4.Totalize.LFCO,410160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_4_VI4.Totalize.FTTD,410162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_4_VI4.Totalize.FTYD,410164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_4_VI4.Totalize.FLOT,410166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_4_VI4.Totalize.DayTotal500,410170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_4_VI4.Totalize.FTTotal500,410172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_4_VI4.Totalize.LowFlowCutoff,410174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_4_VI4.Totalize.TimeDivider,410182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_4_VI4.Totalize.Total2Minute,410184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_4_VI4.Totalize.Total5thSec,410186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_4_VI4.Totalize.TotalToday,410188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_4_VI4.Totalize.TotalTotal,410190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_5_VI1.Totalize.VALU,410356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_5_VI1.Totalize.VMAX,410358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_5_VI1.Totalize.LFCO,410360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_5_VI1.Totalize.FTTD,410362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_5_VI1.Totalize.FTYD,410364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_5_VI1.Totalize.FLOT,410366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_5_VI1.Totalize.DayTotal500,410370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_5_VI1.Totalize.FTTotal500,410372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI1.Totalize.LowFlowCutoff,410374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_5_VI1.Totalize.TimeDivider,410382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_5_VI1.Totalize.Total2Minute,410384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_5_VI1.Totalize.Total5thSec,410386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_5_VI1.Totalize.TotalToday,410388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_5_VI1.Totalize.TotalTotal,410390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_5_VI2.Totalize.VALU,410556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_5_VI2.Totalize.VMAX,410558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_5_VI2.Totalize.LFCO,410560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_5_VI2.Totalize.FTTD,410562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_5_VI2.Totalize.FTYD,410564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_5_VI2.Totalize.FLOT,410566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_5_VI2.Totalize.DayTotal500,410570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_5_VI2.Totalize.FTTotal500,410572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI2.Totalize.LowFlowCutoff,410574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_5_VI2.Totalize.TimeDivider,410582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_5_VI2.Totalize.Total2Minute,410584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_5_VI2.Totalize.Total5thSec,410586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_5_VI2.Totalize.TotalToday,410588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_5_VI2.Totalize.TotalTotal,410590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_5_VI3.Totalize.VALU,410756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_5_VI3.Totalize.VMAX,410758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_5_VI3.Totalize.LFCO,410760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_5_VI3.Totalize.FTTD,410762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_5_VI3.Totalize.FTYD,410764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_5_VI3.Totalize.FLOT,410766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_5_VI3.Totalize.DayTotal500,410770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_5_VI3.Totalize.FTTotal500,410772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI3.Totalize.LowFlowCutoff,410774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_5_VI3.Totalize.TimeDivider,410782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_5_VI3.Totalize.Total2Minute,410784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_5_VI3.Totalize.Total5thSec,410786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_5_VI3.Totalize.TotalToday,410788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_5_VI3.Totalize.TotalTotal,410790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_5_VI4.Totalize.VALU,410956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_5_VI4.Totalize.VMAX,410958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_5_VI4.Totalize.LFCO,410960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_5_VI4.Totalize.FTTD,410962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_5_VI4.Totalize.FTYD,410964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_5_VI4.Totalize.FLOT,410966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_5_VI4.Totalize.DayTotal500,410970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_5_VI4.Totalize.FTTotal500,410972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_5_VI4.Totalize.LowFlowCutoff,410974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_5_VI4.Totalize.TimeDivider,410982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_5_VI4.Totalize.Total2Minute,410984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_5_VI4.Totalize.Total5thSec,410986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_5_VI4.Totalize.TotalToday,410988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_5_VI4.Totalize.TotalTotal,410990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_6_VI1.Totalize.VALU,411156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_6_VI1.Totalize.VMAX,411158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_6_VI1.Totalize.LFCO,411160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_6_VI1.Totalize.FTTD,411162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_6_VI1.Totalize.FTYD,411164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_6_VI1.Totalize.FLOT,411166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_6_VI1.Totalize.DayTotal500,411170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_6_VI1.Totalize.FTTotal500,411172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI1.Totalize.LowFlowCutoff,411174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_6_VI1.Totalize.TimeDivider,411182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_6_VI1.Totalize.Total2Minute,411184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_6_VI1.Totalize.Total5thSec,411186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_6_VI1.Totalize.TotalToday,411188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_6_VI1.Totalize.TotalTotal,411190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_6_VI2.Totalize.VALU,411356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_6_VI2.Totalize.VMAX,411358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_6_VI2.Totalize.LFCO,411360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_6_VI2.Totalize.FTTD,411362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_6_VI2.Totalize.FTYD,411364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_6_VI2.Totalize.FLOT,411366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_6_VI2.Totalize.DayTotal500,411370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_6_VI2.Totalize.FTTotal500,411372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI2.Totalize.LowFlowCutoff,411374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_6_VI2.Totalize.TimeDivider,411382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_6_VI2.Totalize.Total2Minute,411384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_6_VI2.Totalize.Total5thSec,411386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_6_VI2.Totalize.TotalToday,411388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_6_VI2.Totalize.TotalTotal,411390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_6_VI3.Totalize.VALU,411556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_6_VI3.Totalize.VMAX,411558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_6_VI3.Totalize.LFCO,411560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_6_VI3.Totalize.FTTD,411562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_6_VI3.Totalize.FTYD,411564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_6_VI3.Totalize.FLOT,411566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_6_VI3.Totalize.DayTotal500,411570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_6_VI3.Totalize.FTTotal500,411572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI3.Totalize.LowFlowCutoff,411574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_6_VI3.Totalize.TimeDivider,411582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_6_VI3.Totalize.Total2Minute,411584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_6_VI3.Totalize.Total5thSec,411586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_6_VI3.Totalize.TotalToday,411588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_6_VI3.Totalize.TotalTotal,411590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_6_VI4.Totalize.VALU,411756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_6_VI4.Totalize.VMAX,411758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_6_VI4.Totalize.LFCO,411760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_6_VI4.Totalize.FTTD,411762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_6_VI4.Totalize.FTYD,411764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_6_VI4.Totalize.FLOT,411766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_6_VI4.Totalize.DayTotal500,411770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_6_VI4.Totalize.FTTotal500,411772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_6_VI4.Totalize.LowFlowCutoff,411774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_6_VI4.Totalize.TimeDivider,411782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_6_VI4.Totalize.Total2Minute,411784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_6_VI4.Totalize.Total5thSec,411786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_6_VI4.Totalize.TotalToday,411788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_6_VI4.Totalize.TotalTotal,411790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_7_VI1.Totalize.VALU,411956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_7_VI1.Totalize.VMAX,411958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_7_VI1.Totalize.LFCO,411960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_7_VI1.Totalize.FTTD,411962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_7_VI1.Totalize.FTYD,411964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_7_VI1.Totalize.FLOT,411966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_7_VI1.Totalize.DayTotal500,411970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_7_VI1.Totalize.FTTotal500,411972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI1.Totalize.LowFlowCutoff,411974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_7_VI1.Totalize.TimeDivider,411982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_7_VI1.Totalize.Total2Minute,411984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_7_VI1.Totalize.Total5thSec,411986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_7_VI1.Totalize.TotalToday,411988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_7_VI1.Totalize.TotalTotal,411990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_7_VI2.Totalize.VALU,412156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_7_VI2.Totalize.VMAX,412158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_7_VI2.Totalize.LFCO,412160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_7_VI2.Totalize.FTTD,412162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_7_VI2.Totalize.FTYD,412164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_7_VI2.Totalize.FLOT,412166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_7_VI2.Totalize.DayTotal500,412170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_7_VI2.Totalize.FTTotal500,412172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI2.Totalize.LowFlowCutoff,412174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_7_VI2.Totalize.TimeDivider,412182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_7_VI2.Totalize.Total2Minute,412184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_7_VI2.Totalize.Total5thSec,412186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_7_VI2.Totalize.TotalToday,412188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_7_VI2.Totalize.TotalTotal,412190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_7_VI3.Totalize.VALU,412356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_7_VI3.Totalize.VMAX,412358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_7_VI3.Totalize.LFCO,412360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_7_VI3.Totalize.FTTD,412362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_7_VI3.Totalize.FTYD,412364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_7_VI3.Totalize.FLOT,412366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_7_VI3.Totalize.DayTotal500,412370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_7_VI3.Totalize.FTTotal500,412372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI3.Totalize.LowFlowCutoff,412374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_7_VI3.Totalize.TimeDivider,412382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_7_VI3.Totalize.Total2Minute,412384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_7_VI3.Totalize.Total5thSec,412386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_7_VI3.Totalize.TotalToday,412388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_7_VI3.Totalize.TotalTotal,412390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_7_VI4.Totalize.VALU,412556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_7_VI4.Totalize.VMAX,412558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_7_VI4.Totalize.LFCO,412560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_7_VI4.Totalize.FTTD,412562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_7_VI4.Totalize.FTYD,412564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_7_VI4.Totalize.FLOT,412566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_7_VI4.Totalize.DayTotal500,412570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_7_VI4.Totalize.FTTotal500,412572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_7_VI4.Totalize.LowFlowCutoff,412574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_7_VI4.Totalize.TimeDivider,412582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_7_VI4.Totalize.Total2Minute,412584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_7_VI4.Totalize.Total5thSec,412586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_7_VI4.Totalize.TotalToday,412588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_7_VI4.Totalize.TotalTotal,412590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_8_VI1.Totalize.VALU,412756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_8_VI1.Totalize.VMAX,412758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_8_VI1.Totalize.LFCO,412760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_8_VI1.Totalize.FTTD,412762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_8_VI1.Totalize.FTYD,412764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_8_VI1.Totalize.FLOT,412766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_8_VI1.Totalize.DayTotal500,412770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_8_VI1.Totalize.FTTotal500,412772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI1.Totalize.LowFlowCutoff,412774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_8_VI1.Totalize.TimeDivider,412782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_8_VI1.Totalize.Total2Minute,412784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_8_VI1.Totalize.Total5thSec,412786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_8_VI1.Totalize.TotalToday,412788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_8_VI1.Totalize.TotalTotal,412790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_8_VI2.Totalize.VALU,412956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_8_VI2.Totalize.VMAX,412958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_8_VI2.Totalize.LFCO,412960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_8_VI2.Totalize.FTTD,412962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_8_VI2.Totalize.FTYD,412964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_8_VI2.Totalize.FLOT,412966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_8_VI2.Totalize.DayTotal500,412970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_8_VI2.Totalize.FTTotal500,412972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI2.Totalize.LowFlowCutoff,412974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_8_VI2.Totalize.TimeDivider,412982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_8_VI2.Totalize.Total2Minute,412984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_8_VI2.Totalize.Total5thSec,412986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_8_VI2.Totalize.TotalToday,412988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_8_VI2.Totalize.TotalTotal,412990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_8_VI3.Totalize.VALU,413156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_8_VI3.Totalize.VMAX,413158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_8_VI3.Totalize.LFCO,413160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_8_VI3.Totalize.FTTD,413162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_8_VI3.Totalize.FTYD,413164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_8_VI3.Totalize.FLOT,413166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_8_VI3.Totalize.DayTotal500,413170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_8_VI3.Totalize.FTTotal500,413172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI3.Totalize.LowFlowCutoff,413174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_8_VI3.Totalize.TimeDivider,413182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_8_VI3.Totalize.Total2Minute,413184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_8_VI3.Totalize.Total5thSec,413186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_8_VI3.Totalize.TotalToday,413188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_8_VI3.Totalize.TotalTotal,413190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_8_VI4.Totalize.VALU,413356,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_8_VI4.Totalize.VMAX,413358,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_8_VI4.Totalize.LFCO,413360,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_8_VI4.Totalize.FTTD,413362,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_8_VI4.Totalize.FTYD,413364,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_8_VI4.Totalize.FLOT,413366,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_8_VI4.Totalize.DayTotal500,413370,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_8_VI4.Totalize.FTTotal500,413372,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_8_VI4.Totalize.LowFlowCutoff,413374,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_8_VI4.Totalize.TimeDivider,413382,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_8_VI4.Totalize.Total2Minute,413384,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_8_VI4.Totalize.Total5thSec,413386,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_8_VI4.Totalize.TotalToday,413388,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_8_VI4.Totalize.TotalTotal,413390,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_9_VI1.Totalize.VALU,413556,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_9_VI1.Totalize.VMAX,413558,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_9_VI1.Totalize.LFCO,413560,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_9_VI1.Totalize.FTTD,413562,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_9_VI1.Totalize.FTYD,413564,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_9_VI1.Totalize.FLOT,413566,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_9_VI1.Totalize.DayTotal500,413570,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_9_VI1.Totalize.FTTotal500,413572,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI1.Totalize.LowFlowCutoff,413574,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_9_VI1.Totalize.TimeDivider,413582,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_9_VI1.Totalize.Total2Minute,413584,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_9_VI1.Totalize.Total5thSec,413586,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_9_VI1.Totalize.TotalToday,413588,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_9_VI1.Totalize.TotalTotal,413590,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_9_VI2.Totalize.VALU,413756,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_9_VI2.Totalize.VMAX,413758,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_9_VI2.Totalize.LFCO,413760,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_9_VI2.Totalize.FTTD,413762,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_9_VI2.Totalize.FTYD,413764,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_9_VI2.Totalize.FLOT,413766,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_9_VI2.Totalize.DayTotal500,413770,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_9_VI2.Totalize.FTTotal500,413772,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI2.Totalize.LowFlowCutoff,413774,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_9_VI2.Totalize.TimeDivider,413782,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_9_VI2.Totalize.Total2Minute,413784,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_9_VI2.Totalize.Total5thSec,413786,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_9_VI2.Totalize.TotalToday,413788,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_9_VI2.Totalize.TotalTotal,413790,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_9_VI3.Totalize.VALU,413956,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_9_VI3.Totalize.VMAX,413958,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_9_VI3.Totalize.LFCO,413960,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_9_VI3.Totalize.FTTD,413962,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_9_VI3.Totalize.FTYD,413964,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_9_VI3.Totalize.FLOT,413966,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_9_VI3.Totalize.DayTotal500,413970,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_9_VI3.Totalize.FTTotal500,413972,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI3.Totalize.LowFlowCutoff,413974,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_9_VI3.Totalize.TimeDivider,413982,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_9_VI3.Totalize.Total2Minute,413984,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_9_VI3.Totalize.Total5thSec,413986,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_9_VI3.Totalize.TotalToday,413988,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_9_VI3.Totalize.TotalTotal,413990,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_MTR_0103_9_VI4.Totalize.VALU,414156,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_MTR_0103_9_VI4.Totalize.VMAX,414158,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_MTR_0103_9_VI4.Totalize.LFCO,414160,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_MTR_0103_9_VI4.Totalize.FTTD,414162,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_MTR_0103_9_VI4.Totalize.FTYD,414164,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_MTR_0103_9_VI4.Totalize.FLOT,414166,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_MTR_0103_9_VI4.Totalize.DayTotal500,414170,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_MTR_0103_9_VI4.Totalize.FTTotal500,414172,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_MTR_0103_9_VI4.Totalize.LowFlowCutoff,414174,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_MTR_0103_9_VI4.Totalize.TimeDivider,414182,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_MTR_0103_9_VI4.Totalize.Total2Minute,414184,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_MTR_0103_9_VI4.Totalize.Total5thSec,414186,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_MTR_0103_9_VI4.Totalize.TotalToday,414188,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_MTR_0103_9_VI4.Totalize.TotalTotal,414190,Float,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0102_1_PI.Totalize.VALU,414356,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0102_1_PI.Totalize.VMAX,414358,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0102_1_PI.Totalize.LFCO,414360,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0102_1_PI.Totalize.FTTD,414362,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0102_1_PI.Totalize.FTYD,414364,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0102_1_PI.Totalize.FLOT,414366,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0102_1_PI.Totalize.DayTotal500,414370,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0102_1_PI.Totalize.FTTotal500,414372,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_1_PI.Totalize.LowFlowCutoff,414374,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0102_1_PI.Totalize.TimeDivider,414382,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0102_1_PI.Totalize.Total2Minute,414384,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0102_1_PI.Totalize.Total5thSec,414386,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0102_1_PI.Totalize.TotalToday,414388,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0102_1_PI.Totalize.TotalTotal,414390,Float,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0102_2_PI.Totalize.VALU,414556,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0102_2_PI.Totalize.VMAX,414558,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0102_2_PI.Totalize.LFCO,414560,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0102_2_PI.Totalize.FTTD,414562,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0102_2_PI.Totalize.FTYD,414564,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0102_2_PI.Totalize.FLOT,414566,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0102_2_PI.Totalize.DayTotal500,414570,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0102_2_PI.Totalize.FTTotal500,414572,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0102_2_PI.Totalize.LowFlowCutoff,414574,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0102_2_PI.Totalize.TimeDivider,414582,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0102_2_PI.Totalize.Total2Minute,414584,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0102_2_PI.Totalize.Total5thSec,414586,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0102_2_PI.Totalize.TotalToday,414588,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0102_2_PI.Totalize.TotalTotal,414590,Float,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_1_PI.Totalize.VALU,414756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_1_PI.Totalize.VMAX,414758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_1_PI.Totalize.LFCO,414760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_1_PI.Totalize.FTTD,414762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_1_PI.Totalize.FTYD,414764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_1_PI.Totalize.FLOT,414766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_1_PI.Totalize.DayTotal500,414770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_1_PI.Totalize.FTTotal500,414772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_1_PI.Totalize.LowFlowCutoff,414774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_1_PI.Totalize.TimeDivider,414782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_1_PI.Totalize.Total2Minute,414784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_1_PI.Totalize.Total5thSec,414786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_1_PI.Totalize.TotalToday,414788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_1_PI.Totalize.TotalTotal,414790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_2_PI.Totalize.VALU,414956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_2_PI.Totalize.VMAX,414958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_2_PI.Totalize.LFCO,414960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_2_PI.Totalize.FTTD,414962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_2_PI.Totalize.FTYD,414964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_2_PI.Totalize.FLOT,414966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_2_PI.Totalize.DayTotal500,414970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_2_PI.Totalize.FTTotal500,414972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_2_PI.Totalize.LowFlowCutoff,414974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_2_PI.Totalize.TimeDivider,414982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_2_PI.Totalize.Total2Minute,414984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_2_PI.Totalize.Total5thSec,414986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_2_PI.Totalize.TotalToday,414988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_2_PI.Totalize.TotalTotal,414990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_3_PI.Totalize.VALU,415156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_3_PI.Totalize.VMAX,415158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_3_PI.Totalize.LFCO,415160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_3_PI.Totalize.FTTD,415162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_3_PI.Totalize.FTYD,415164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_3_PI.Totalize.FLOT,415166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_3_PI.Totalize.DayTotal500,415170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_3_PI.Totalize.FTTotal500,415172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_3_PI.Totalize.LowFlowCutoff,415174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_3_PI.Totalize.TimeDivider,415182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_3_PI.Totalize.Total2Minute,415184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_3_PI.Totalize.Total5thSec,415186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_3_PI.Totalize.TotalToday,415188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_3_PI.Totalize.TotalTotal,415190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_4_PI.Totalize.VALU,415356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_4_PI.Totalize.VMAX,415358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_4_PI.Totalize.LFCO,415360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_4_PI.Totalize.FTTD,415362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_4_PI.Totalize.FTYD,415364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_4_PI.Totalize.FLOT,415366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_4_PI.Totalize.DayTotal500,415370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_4_PI.Totalize.FTTotal500,415372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_4_PI.Totalize.LowFlowCutoff,415374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_4_PI.Totalize.TimeDivider,415382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_4_PI.Totalize.Total2Minute,415384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_4_PI.Totalize.Total5thSec,415386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_4_PI.Totalize.TotalToday,415388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_4_PI.Totalize.TotalTotal,415390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_5_PI.Totalize.VALU,415556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_5_PI.Totalize.VMAX,415558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_5_PI.Totalize.LFCO,415560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_5_PI.Totalize.FTTD,415562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_5_PI.Totalize.FTYD,415564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_5_PI.Totalize.FLOT,415566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_5_PI.Totalize.DayTotal500,415570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_5_PI.Totalize.FTTotal500,415572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_5_PI.Totalize.LowFlowCutoff,415574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_5_PI.Totalize.TimeDivider,415582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_5_PI.Totalize.Total2Minute,415584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_5_PI.Totalize.Total5thSec,415586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_5_PI.Totalize.TotalToday,415588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_5_PI.Totalize.TotalTotal,415590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_6_PI.Totalize.VALU,415756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_6_PI.Totalize.VMAX,415758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_6_PI.Totalize.LFCO,415760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_6_PI.Totalize.FTTD,415762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_6_PI.Totalize.FTYD,415764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_6_PI.Totalize.FLOT,415766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_6_PI.Totalize.DayTotal500,415770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_6_PI.Totalize.FTTotal500,415772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_6_PI.Totalize.LowFlowCutoff,415774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_6_PI.Totalize.TimeDivider,415782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_6_PI.Totalize.Total2Minute,415784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_6_PI.Totalize.Total5thSec,415786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_6_PI.Totalize.TotalToday,415788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_6_PI.Totalize.TotalTotal,415790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_7_PI.Totalize.VALU,415956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_7_PI.Totalize.VMAX,415958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_7_PI.Totalize.LFCO,415960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_7_PI.Totalize.FTTD,415962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_7_PI.Totalize.FTYD,415964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_7_PI.Totalize.FLOT,415966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_7_PI.Totalize.DayTotal500,415970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_7_PI.Totalize.FTTotal500,415972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_7_PI.Totalize.LowFlowCutoff,415974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_7_PI.Totalize.TimeDivider,415982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_7_PI.Totalize.Total2Minute,415984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_7_PI.Totalize.Total5thSec,415986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_7_PI.Totalize.TotalToday,415988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_7_PI.Totalize.TotalTotal,415990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_8_PI.Totalize.VALU,416156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_8_PI.Totalize.VMAX,416158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_8_PI.Totalize.LFCO,416160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_8_PI.Totalize.FTTD,416162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_8_PI.Totalize.FTYD,416164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_8_PI.Totalize.FLOT,416166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_8_PI.Totalize.DayTotal500,416170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_8_PI.Totalize.FTTotal500,416172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_8_PI.Totalize.LowFlowCutoff,416174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_8_PI.Totalize.TimeDivider,416182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_8_PI.Totalize.Total2Minute,416184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_8_PI.Totalize.Total5thSec,416186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_8_PI.Totalize.TotalToday,416188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_8_PI.Totalize.TotalTotal,416190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0103_9_PI.Totalize.VALU,416356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0103_9_PI.Totalize.VMAX,416358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0103_9_PI.Totalize.LFCO,416360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0103_9_PI.Totalize.FTTD,416362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0103_9_PI.Totalize.FTYD,416364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0103_9_PI.Totalize.FLOT,416366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0103_9_PI.Totalize.DayTotal500,416370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0103_9_PI.Totalize.FTTotal500,416372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0103_9_PI.Totalize.LowFlowCutoff,416374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0103_9_PI.Totalize.TimeDivider,416382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0103_9_PI.Totalize.Total2Minute,416384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0103_9_PI.Totalize.Total5thSec,416386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0103_9_PI.Totalize.TotalToday,416388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0103_9_PI.Totalize.TotalTotal,416390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PIT_0104_1_PI.Totalize.VALU,416556,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PIT_0104_1_PI.Totalize.VMAX,416558,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PIT_0104_1_PI.Totalize.LFCO,416560,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PIT_0104_1_PI.Totalize.FTTD,416562,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PIT_0104_1_PI.Totalize.FTYD,416564,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PIT_0104_1_PI.Totalize.FLOT,416566,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PIT_0104_1_PI.Totalize.DayTotal500,416570,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PIT_0104_1_PI.Totalize.FTTotal500,416572,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PIT_0104_1_PI.Totalize.LowFlowCutoff,416574,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PIT_0104_1_PI.Totalize.TimeDivider,416582,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PIT_0104_1_PI.Totalize.Total2Minute,416584,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PIT_0104_1_PI.Totalize.Total5thSec,416586,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PIT_0104_1_PI.Totalize.TotalToday,416588,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PIT_0104_1_PI.Totalize.TotalTotal,416590,Float,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_1_VI1.Totalize.VALU,416756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_1_VI1.Totalize.VMAX,416758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_1_VI1.Totalize.LFCO,416760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_1_VI1.Totalize.FTTD,416762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_1_VI1.Totalize.FTYD,416764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_1_VI1.Totalize.FLOT,416766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_1_VI1.Totalize.DayTotal500,416770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_1_VI1.Totalize.FTTotal500,416772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI1.Totalize.LowFlowCutoff,416774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_1_VI1.Totalize.TimeDivider,416782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_1_VI1.Totalize.Total2Minute,416784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_1_VI1.Totalize.Total5thSec,416786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_1_VI1.Totalize.TotalToday,416788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_1_VI1.Totalize.TotalTotal,416790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_1_VI2.Totalize.VALU,416956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_1_VI2.Totalize.VMAX,416958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_1_VI2.Totalize.LFCO,416960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_1_VI2.Totalize.FTTD,416962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_1_VI2.Totalize.FTYD,416964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_1_VI2.Totalize.FLOT,416966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_1_VI2.Totalize.DayTotal500,416970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_1_VI2.Totalize.FTTotal500,416972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI2.Totalize.LowFlowCutoff,416974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_1_VI2.Totalize.TimeDivider,416982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_1_VI2.Totalize.Total2Minute,416984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_1_VI2.Totalize.Total5thSec,416986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_1_VI2.Totalize.TotalToday,416988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_1_VI2.Totalize.TotalTotal,416990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_1_VI3.Totalize.VALU,417156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_1_VI3.Totalize.VMAX,417158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_1_VI3.Totalize.LFCO,417160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_1_VI3.Totalize.FTTD,417162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_1_VI3.Totalize.FTYD,417164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_1_VI3.Totalize.FLOT,417166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_1_VI3.Totalize.DayTotal500,417170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_1_VI3.Totalize.FTTotal500,417172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI3.Totalize.LowFlowCutoff,417174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_1_VI3.Totalize.TimeDivider,417182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_1_VI3.Totalize.Total2Minute,417184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_1_VI3.Totalize.Total5thSec,417186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_1_VI3.Totalize.TotalToday,417188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_1_VI3.Totalize.TotalTotal,417190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_1_VI4.Totalize.VALU,417356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_1_VI4.Totalize.VMAX,417358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_1_VI4.Totalize.LFCO,417360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_1_VI4.Totalize.FTTD,417362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_1_VI4.Totalize.FTYD,417364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_1_VI4.Totalize.FLOT,417366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_1_VI4.Totalize.DayTotal500,417370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_1_VI4.Totalize.FTTotal500,417372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI4.Totalize.LowFlowCutoff,417374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_1_VI4.Totalize.TimeDivider,417382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_1_VI4.Totalize.Total2Minute,417384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_1_VI4.Totalize.Total5thSec,417386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_1_VI4.Totalize.TotalToday,417388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_1_VI4.Totalize.TotalTotal,417390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_1_VI5.Totalize.VALU,417556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_1_VI5.Totalize.VMAX,417558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_1_VI5.Totalize.LFCO,417560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_1_VI5.Totalize.FTTD,417562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_1_VI5.Totalize.FTYD,417564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_1_VI5.Totalize.FLOT,417566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_1_VI5.Totalize.DayTotal500,417570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_1_VI5.Totalize.FTTotal500,417572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_1_VI5.Totalize.LowFlowCutoff,417574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_1_VI5.Totalize.TimeDivider,417582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_1_VI5.Totalize.Total2Minute,417584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_1_VI5.Totalize.Total5thSec,417586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_1_VI5.Totalize.TotalToday,417588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_1_VI5.Totalize.TotalTotal,417590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_2_VI1.Totalize.VALU,417756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_2_VI1.Totalize.VMAX,417758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_2_VI1.Totalize.LFCO,417760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_2_VI1.Totalize.FTTD,417762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_2_VI1.Totalize.FTYD,417764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_2_VI1.Totalize.FLOT,417766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_2_VI1.Totalize.DayTotal500,417770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_2_VI1.Totalize.FTTotal500,417772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI1.Totalize.LowFlowCutoff,417774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_2_VI1.Totalize.TimeDivider,417782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_2_VI1.Totalize.Total2Minute,417784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_2_VI1.Totalize.Total5thSec,417786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_2_VI1.Totalize.TotalToday,417788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_2_VI1.Totalize.TotalTotal,417790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_2_VI2.Totalize.VALU,417956,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_2_VI2.Totalize.VMAX,417958,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_2_VI2.Totalize.LFCO,417960,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_2_VI2.Totalize.FTTD,417962,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_2_VI2.Totalize.FTYD,417964,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_2_VI2.Totalize.FLOT,417966,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_2_VI2.Totalize.DayTotal500,417970,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_2_VI2.Totalize.FTTotal500,417972,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI2.Totalize.LowFlowCutoff,417974,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_2_VI2.Totalize.TimeDivider,417982,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_2_VI2.Totalize.Total2Minute,417984,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_2_VI2.Totalize.Total5thSec,417986,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_2_VI2.Totalize.TotalToday,417988,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_2_VI2.Totalize.TotalTotal,417990,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_2_VI3.Totalize.VALU,418156,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_2_VI3.Totalize.VMAX,418158,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_2_VI3.Totalize.LFCO,418160,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_2_VI3.Totalize.FTTD,418162,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_2_VI3.Totalize.FTYD,418164,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_2_VI3.Totalize.FLOT,418166,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_2_VI3.Totalize.DayTotal500,418170,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_2_VI3.Totalize.FTTotal500,418172,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI3.Totalize.LowFlowCutoff,418174,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_2_VI3.Totalize.TimeDivider,418182,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_2_VI3.Totalize.Total2Minute,418184,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_2_VI3.Totalize.Total5thSec,418186,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_2_VI3.Totalize.TotalToday,418188,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_2_VI3.Totalize.TotalTotal,418190,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_2_VI4.Totalize.VALU,418356,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_2_VI4.Totalize.VMAX,418358,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_2_VI4.Totalize.LFCO,418360,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_2_VI4.Totalize.FTTD,418362,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_2_VI4.Totalize.FTYD,418364,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_2_VI4.Totalize.FLOT,418366,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_2_VI4.Totalize.DayTotal500,418370,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_2_VI4.Totalize.FTTotal500,418372,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI4.Totalize.LowFlowCutoff,418374,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_2_VI4.Totalize.TimeDivider,418382,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_2_VI4.Totalize.Total2Minute,418384,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_2_VI4.Totalize.Total5thSec,418386,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_2_VI4.Totalize.TotalToday,418388,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_2_VI4.Totalize.TotalTotal,418390,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_2_VI5.Totalize.VALU,418556,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_2_VI5.Totalize.VMAX,418558,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_2_VI5.Totalize.LFCO,418560,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_2_VI5.Totalize.FTTD,418562,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_2_VI5.Totalize.FTYD,418564,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_2_VI5.Totalize.FLOT,418566,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_2_VI5.Totalize.DayTotal500,418570,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_2_VI5.Totalize.FTTotal500,418572,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_2_VI5.Totalize.LowFlowCutoff,418574,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_2_VI5.Totalize.TimeDivider,418582,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_2_VI5.Totalize.Total2Minute,418584,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_2_VI5.Totalize.Total5thSec,418586,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_2_VI5.Totalize.TotalToday,418588,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_2_VI5.Totalize.TotalTotal,418590,Float,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_3_VI1.Totalize.VALU,418756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_3_VI1.Totalize.VMAX,418758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_3_VI1.Totalize.LFCO,418760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_3_VI1.Totalize.FTTD,418762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_3_VI1.Totalize.FTYD,418764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_3_VI1.Totalize.FLOT,418766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_3_VI1.Totalize.DayTotal500,418770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_3_VI1.Totalize.FTTotal500,418772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI1.Totalize.LowFlowCutoff,418774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_3_VI1.Totalize.TimeDivider,418782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_3_VI1.Totalize.Total2Minute,418784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_3_VI1.Totalize.Total5thSec,418786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_3_VI1.Totalize.TotalToday,418788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_3_VI1.Totalize.TotalTotal,418790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_3_VI2.Totalize.VALU,418956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_3_VI2.Totalize.VMAX,418958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_3_VI2.Totalize.LFCO,418960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_3_VI2.Totalize.FTTD,418962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_3_VI2.Totalize.FTYD,418964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_3_VI2.Totalize.FLOT,418966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_3_VI2.Totalize.DayTotal500,418970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_3_VI2.Totalize.FTTotal500,418972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI2.Totalize.LowFlowCutoff,418974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_3_VI2.Totalize.TimeDivider,418982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_3_VI2.Totalize.Total2Minute,418984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_3_VI2.Totalize.Total5thSec,418986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_3_VI2.Totalize.TotalToday,418988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_3_VI2.Totalize.TotalTotal,418990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_3_VI3.Totalize.VALU,419156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_3_VI3.Totalize.VMAX,419158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_3_VI3.Totalize.LFCO,419160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_3_VI3.Totalize.FTTD,419162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_3_VI3.Totalize.FTYD,419164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_3_VI3.Totalize.FLOT,419166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_3_VI3.Totalize.DayTotal500,419170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_3_VI3.Totalize.FTTotal500,419172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI3.Totalize.LowFlowCutoff,419174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_3_VI3.Totalize.TimeDivider,419182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_3_VI3.Totalize.Total2Minute,419184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_3_VI3.Totalize.Total5thSec,419186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_3_VI3.Totalize.TotalToday,419188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_3_VI3.Totalize.TotalTotal,419190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_3_VI4.Totalize.VALU,419356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_3_VI4.Totalize.VMAX,419358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_3_VI4.Totalize.LFCO,419360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_3_VI4.Totalize.FTTD,419362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_3_VI4.Totalize.FTYD,419364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_3_VI4.Totalize.FLOT,419366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_3_VI4.Totalize.DayTotal500,419370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_3_VI4.Totalize.FTTotal500,419372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI4.Totalize.LowFlowCutoff,419374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_3_VI4.Totalize.TimeDivider,419382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_3_VI4.Totalize.Total2Minute,419384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_3_VI4.Totalize.Total5thSec,419386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_3_VI4.Totalize.TotalToday,419388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_3_VI4.Totalize.TotalTotal,419390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_3_VI5.Totalize.VALU,419556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_3_VI5.Totalize.VMAX,419558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_3_VI5.Totalize.LFCO,419560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_3_VI5.Totalize.FTTD,419562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_3_VI5.Totalize.FTYD,419564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_3_VI5.Totalize.FLOT,419566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_3_VI5.Totalize.DayTotal500,419570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_3_VI5.Totalize.FTTotal500,419572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_3_VI5.Totalize.LowFlowCutoff,419574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_3_VI5.Totalize.TimeDivider,419582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_3_VI5.Totalize.Total2Minute,419584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_3_VI5.Totalize.Total5thSec,419586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_3_VI5.Totalize.TotalToday,419588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_3_VI5.Totalize.TotalTotal,419590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_4_VI1.Totalize.VALU,419756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_4_VI1.Totalize.VMAX,419758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_4_VI1.Totalize.LFCO,419760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_4_VI1.Totalize.FTTD,419762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_4_VI1.Totalize.FTYD,419764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_4_VI1.Totalize.FLOT,419766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_4_VI1.Totalize.DayTotal500,419770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_4_VI1.Totalize.FTTotal500,419772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI1.Totalize.LowFlowCutoff,419774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_4_VI1.Totalize.TimeDivider,419782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_4_VI1.Totalize.Total2Minute,419784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_4_VI1.Totalize.Total5thSec,419786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_4_VI1.Totalize.TotalToday,419788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_4_VI1.Totalize.TotalTotal,419790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_4_VI2.Totalize.VALU,419956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_4_VI2.Totalize.VMAX,419958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_4_VI2.Totalize.LFCO,419960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_4_VI2.Totalize.FTTD,419962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_4_VI2.Totalize.FTYD,419964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_4_VI2.Totalize.FLOT,419966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_4_VI2.Totalize.DayTotal500,419970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_4_VI2.Totalize.FTTotal500,419972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI2.Totalize.LowFlowCutoff,419974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_4_VI2.Totalize.TimeDivider,419982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_4_VI2.Totalize.Total2Minute,419984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_4_VI2.Totalize.Total5thSec,419986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_4_VI2.Totalize.TotalToday,419988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_4_VI2.Totalize.TotalTotal,419990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_4_VI3.Totalize.VALU,420156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_4_VI3.Totalize.VMAX,420158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_4_VI3.Totalize.LFCO,420160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_4_VI3.Totalize.FTTD,420162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_4_VI3.Totalize.FTYD,420164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_4_VI3.Totalize.FLOT,420166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_4_VI3.Totalize.DayTotal500,420170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_4_VI3.Totalize.FTTotal500,420172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI3.Totalize.LowFlowCutoff,420174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_4_VI3.Totalize.TimeDivider,420182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_4_VI3.Totalize.Total2Minute,420184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_4_VI3.Totalize.Total5thSec,420186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_4_VI3.Totalize.TotalToday,420188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_4_VI3.Totalize.TotalTotal,420190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_4_VI4.Totalize.VALU,420356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_4_VI4.Totalize.VMAX,420358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_4_VI4.Totalize.LFCO,420360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_4_VI4.Totalize.FTTD,420362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_4_VI4.Totalize.FTYD,420364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_4_VI4.Totalize.FLOT,420366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_4_VI4.Totalize.DayTotal500,420370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_4_VI4.Totalize.FTTotal500,420372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI4.Totalize.LowFlowCutoff,420374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_4_VI4.Totalize.TimeDivider,420382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_4_VI4.Totalize.Total2Minute,420384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_4_VI4.Totalize.Total5thSec,420386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_4_VI4.Totalize.TotalToday,420388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_4_VI4.Totalize.TotalTotal,420390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_4_VI5.Totalize.VALU,420556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_4_VI5.Totalize.VMAX,420558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_4_VI5.Totalize.LFCO,420560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_4_VI5.Totalize.FTTD,420562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_4_VI5.Totalize.FTYD,420564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_4_VI5.Totalize.FLOT,420566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_4_VI5.Totalize.DayTotal500,420570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_4_VI5.Totalize.FTTotal500,420572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_4_VI5.Totalize.LowFlowCutoff,420574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_4_VI5.Totalize.TimeDivider,420582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_4_VI5.Totalize.Total2Minute,420584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_4_VI5.Totalize.Total5thSec,420586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_4_VI5.Totalize.TotalToday,420588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_4_VI5.Totalize.TotalTotal,420590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_5_VI1.Totalize.VALU,420756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_5_VI1.Totalize.VMAX,420758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_5_VI1.Totalize.LFCO,420760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_5_VI1.Totalize.FTTD,420762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_5_VI1.Totalize.FTYD,420764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_5_VI1.Totalize.FLOT,420766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_5_VI1.Totalize.DayTotal500,420770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_5_VI1.Totalize.FTTotal500,420772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI1.Totalize.LowFlowCutoff,420774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_5_VI1.Totalize.TimeDivider,420782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_5_VI1.Totalize.Total2Minute,420784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_5_VI1.Totalize.Total5thSec,420786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_5_VI1.Totalize.TotalToday,420788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_5_VI1.Totalize.TotalTotal,420790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_5_VI2.Totalize.VALU,420956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_5_VI2.Totalize.VMAX,420958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_5_VI2.Totalize.LFCO,420960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_5_VI2.Totalize.FTTD,420962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_5_VI2.Totalize.FTYD,420964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_5_VI2.Totalize.FLOT,420966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_5_VI2.Totalize.DayTotal500,420970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_5_VI2.Totalize.FTTotal500,420972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI2.Totalize.LowFlowCutoff,420974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_5_VI2.Totalize.TimeDivider,420982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_5_VI2.Totalize.Total2Minute,420984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_5_VI2.Totalize.Total5thSec,420986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_5_VI2.Totalize.TotalToday,420988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_5_VI2.Totalize.TotalTotal,420990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_5_VI3.Totalize.VALU,421156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_5_VI3.Totalize.VMAX,421158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_5_VI3.Totalize.LFCO,421160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_5_VI3.Totalize.FTTD,421162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_5_VI3.Totalize.FTYD,421164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_5_VI3.Totalize.FLOT,421166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_5_VI3.Totalize.DayTotal500,421170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_5_VI3.Totalize.FTTotal500,421172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI3.Totalize.LowFlowCutoff,421174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_5_VI3.Totalize.TimeDivider,421182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_5_VI3.Totalize.Total2Minute,421184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_5_VI3.Totalize.Total5thSec,421186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_5_VI3.Totalize.TotalToday,421188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_5_VI3.Totalize.TotalTotal,421190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_5_VI4.Totalize.VALU,421356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_5_VI4.Totalize.VMAX,421358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_5_VI4.Totalize.LFCO,421360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_5_VI4.Totalize.FTTD,421362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_5_VI4.Totalize.FTYD,421364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_5_VI4.Totalize.FLOT,421366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_5_VI4.Totalize.DayTotal500,421370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_5_VI4.Totalize.FTTotal500,421372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI4.Totalize.LowFlowCutoff,421374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_5_VI4.Totalize.TimeDivider,421382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_5_VI4.Totalize.Total2Minute,421384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_5_VI4.Totalize.Total5thSec,421386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_5_VI4.Totalize.TotalToday,421388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_5_VI4.Totalize.TotalTotal,421390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_5_VI5.Totalize.VALU,421556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_5_VI5.Totalize.VMAX,421558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_5_VI5.Totalize.LFCO,421560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_5_VI5.Totalize.FTTD,421562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_5_VI5.Totalize.FTYD,421564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_5_VI5.Totalize.FLOT,421566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_5_VI5.Totalize.DayTotal500,421570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_5_VI5.Totalize.FTTotal500,421572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_5_VI5.Totalize.LowFlowCutoff,421574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_5_VI5.Totalize.TimeDivider,421582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_5_VI5.Totalize.Total2Minute,421584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_5_VI5.Totalize.Total5thSec,421586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_5_VI5.Totalize.TotalToday,421588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_5_VI5.Totalize.TotalTotal,421590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_6_VI1.Totalize.VALU,421756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_6_VI1.Totalize.VMAX,421758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_6_VI1.Totalize.LFCO,421760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_6_VI1.Totalize.FTTD,421762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_6_VI1.Totalize.FTYD,421764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_6_VI1.Totalize.FLOT,421766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_6_VI1.Totalize.DayTotal500,421770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_6_VI1.Totalize.FTTotal500,421772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI1.Totalize.LowFlowCutoff,421774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_6_VI1.Totalize.TimeDivider,421782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_6_VI1.Totalize.Total2Minute,421784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_6_VI1.Totalize.Total5thSec,421786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_6_VI1.Totalize.TotalToday,421788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_6_VI1.Totalize.TotalTotal,421790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_6_VI2.Totalize.VALU,421956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_6_VI2.Totalize.VMAX,421958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_6_VI2.Totalize.LFCO,421960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_6_VI2.Totalize.FTTD,421962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_6_VI2.Totalize.FTYD,421964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_6_VI2.Totalize.FLOT,421966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_6_VI2.Totalize.DayTotal500,421970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_6_VI2.Totalize.FTTotal500,421972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI2.Totalize.LowFlowCutoff,421974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_6_VI2.Totalize.TimeDivider,421982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_6_VI2.Totalize.Total2Minute,421984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_6_VI2.Totalize.Total5thSec,421986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_6_VI2.Totalize.TotalToday,421988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_6_VI2.Totalize.TotalTotal,421990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_6_VI3.Totalize.VALU,422156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_6_VI3.Totalize.VMAX,422158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_6_VI3.Totalize.LFCO,422160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_6_VI3.Totalize.FTTD,422162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_6_VI3.Totalize.FTYD,422164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_6_VI3.Totalize.FLOT,422166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_6_VI3.Totalize.DayTotal500,422170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_6_VI3.Totalize.FTTotal500,422172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI3.Totalize.LowFlowCutoff,422174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_6_VI3.Totalize.TimeDivider,422182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_6_VI3.Totalize.Total2Minute,422184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_6_VI3.Totalize.Total5thSec,422186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_6_VI3.Totalize.TotalToday,422188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_6_VI3.Totalize.TotalTotal,422190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_6_VI4.Totalize.VALU,422356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_6_VI4.Totalize.VMAX,422358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_6_VI4.Totalize.LFCO,422360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_6_VI4.Totalize.FTTD,422362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_6_VI4.Totalize.FTYD,422364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_6_VI4.Totalize.FLOT,422366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_6_VI4.Totalize.DayTotal500,422370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_6_VI4.Totalize.FTTotal500,422372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI4.Totalize.LowFlowCutoff,422374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_6_VI4.Totalize.TimeDivider,422382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_6_VI4.Totalize.Total2Minute,422384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_6_VI4.Totalize.Total5thSec,422386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_6_VI4.Totalize.TotalToday,422388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_6_VI4.Totalize.TotalTotal,422390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_6_VI5.Totalize.VALU,422556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_6_VI5.Totalize.VMAX,422558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_6_VI5.Totalize.LFCO,422560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_6_VI5.Totalize.FTTD,422562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_6_VI5.Totalize.FTYD,422564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_6_VI5.Totalize.FLOT,422566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_6_VI5.Totalize.DayTotal500,422570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_6_VI5.Totalize.FTTotal500,422572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_6_VI5.Totalize.LowFlowCutoff,422574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_6_VI5.Totalize.TimeDivider,422582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_6_VI5.Totalize.Total2Minute,422584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_6_VI5.Totalize.Total5thSec,422586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_6_VI5.Totalize.TotalToday,422588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_6_VI5.Totalize.TotalTotal,422590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_7_VI1.Totalize.VALU,422756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_7_VI1.Totalize.VMAX,422758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_7_VI1.Totalize.LFCO,422760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_7_VI1.Totalize.FTTD,422762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_7_VI1.Totalize.FTYD,422764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_7_VI1.Totalize.FLOT,422766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_7_VI1.Totalize.DayTotal500,422770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_7_VI1.Totalize.FTTotal500,422772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI1.Totalize.LowFlowCutoff,422774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_7_VI1.Totalize.TimeDivider,422782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_7_VI1.Totalize.Total2Minute,422784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_7_VI1.Totalize.Total5thSec,422786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_7_VI1.Totalize.TotalToday,422788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_7_VI1.Totalize.TotalTotal,422790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_7_VI2.Totalize.VALU,422956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_7_VI2.Totalize.VMAX,422958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_7_VI2.Totalize.LFCO,422960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_7_VI2.Totalize.FTTD,422962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_7_VI2.Totalize.FTYD,422964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_7_VI2.Totalize.FLOT,422966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_7_VI2.Totalize.DayTotal500,422970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_7_VI2.Totalize.FTTotal500,422972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI2.Totalize.LowFlowCutoff,422974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_7_VI2.Totalize.TimeDivider,422982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_7_VI2.Totalize.Total2Minute,422984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_7_VI2.Totalize.Total5thSec,422986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_7_VI2.Totalize.TotalToday,422988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_7_VI2.Totalize.TotalTotal,422990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_7_VI3.Totalize.VALU,423156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_7_VI3.Totalize.VMAX,423158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_7_VI3.Totalize.LFCO,423160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_7_VI3.Totalize.FTTD,423162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_7_VI3.Totalize.FTYD,423164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_7_VI3.Totalize.FLOT,423166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_7_VI3.Totalize.DayTotal500,423170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_7_VI3.Totalize.FTTotal500,423172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI3.Totalize.LowFlowCutoff,423174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_7_VI3.Totalize.TimeDivider,423182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_7_VI3.Totalize.Total2Minute,423184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_7_VI3.Totalize.Total5thSec,423186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_7_VI3.Totalize.TotalToday,423188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_7_VI3.Totalize.TotalTotal,423190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_7_VI4.Totalize.VALU,423356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_7_VI4.Totalize.VMAX,423358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_7_VI4.Totalize.LFCO,423360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_7_VI4.Totalize.FTTD,423362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_7_VI4.Totalize.FTYD,423364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_7_VI4.Totalize.FLOT,423366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_7_VI4.Totalize.DayTotal500,423370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_7_VI4.Totalize.FTTotal500,423372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI4.Totalize.LowFlowCutoff,423374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_7_VI4.Totalize.TimeDivider,423382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_7_VI4.Totalize.Total2Minute,423384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_7_VI4.Totalize.Total5thSec,423386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_7_VI4.Totalize.TotalToday,423388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_7_VI4.Totalize.TotalTotal,423390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_7_VI5.Totalize.VALU,423556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_7_VI5.Totalize.VMAX,423558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_7_VI5.Totalize.LFCO,423560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_7_VI5.Totalize.FTTD,423562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_7_VI5.Totalize.FTYD,423564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_7_VI5.Totalize.FLOT,423566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_7_VI5.Totalize.DayTotal500,423570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_7_VI5.Totalize.FTTotal500,423572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_7_VI5.Totalize.LowFlowCutoff,423574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_7_VI5.Totalize.TimeDivider,423582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_7_VI5.Totalize.Total2Minute,423584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_7_VI5.Totalize.Total5thSec,423586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_7_VI5.Totalize.TotalToday,423588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_7_VI5.Totalize.TotalTotal,423590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_8_VI1.Totalize.VALU,423756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_8_VI1.Totalize.VMAX,423758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_8_VI1.Totalize.LFCO,423760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_8_VI1.Totalize.FTTD,423762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_8_VI1.Totalize.FTYD,423764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_8_VI1.Totalize.FLOT,423766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_8_VI1.Totalize.DayTotal500,423770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_8_VI1.Totalize.FTTotal500,423772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI1.Totalize.LowFlowCutoff,423774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_8_VI1.Totalize.TimeDivider,423782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_8_VI1.Totalize.Total2Minute,423784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_8_VI1.Totalize.Total5thSec,423786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_8_VI1.Totalize.TotalToday,423788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_8_VI1.Totalize.TotalTotal,423790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_8_VI2.Totalize.VALU,423956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_8_VI2.Totalize.VMAX,423958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_8_VI2.Totalize.LFCO,423960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_8_VI2.Totalize.FTTD,423962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_8_VI2.Totalize.FTYD,423964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_8_VI2.Totalize.FLOT,423966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_8_VI2.Totalize.DayTotal500,423970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_8_VI2.Totalize.FTTotal500,423972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI2.Totalize.LowFlowCutoff,423974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_8_VI2.Totalize.TimeDivider,423982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_8_VI2.Totalize.Total2Minute,423984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_8_VI2.Totalize.Total5thSec,423986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_8_VI2.Totalize.TotalToday,423988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_8_VI2.Totalize.TotalTotal,423990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_8_VI3.Totalize.VALU,424156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_8_VI3.Totalize.VMAX,424158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_8_VI3.Totalize.LFCO,424160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_8_VI3.Totalize.FTTD,424162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_8_VI3.Totalize.FTYD,424164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_8_VI3.Totalize.FLOT,424166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_8_VI3.Totalize.DayTotal500,424170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_8_VI3.Totalize.FTTotal500,424172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI3.Totalize.LowFlowCutoff,424174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_8_VI3.Totalize.TimeDivider,424182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_8_VI3.Totalize.Total2Minute,424184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_8_VI3.Totalize.Total5thSec,424186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_8_VI3.Totalize.TotalToday,424188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_8_VI3.Totalize.TotalTotal,424190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_8_VI4.Totalize.VALU,424356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_8_VI4.Totalize.VMAX,424358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_8_VI4.Totalize.LFCO,424360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_8_VI4.Totalize.FTTD,424362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_8_VI4.Totalize.FTYD,424364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_8_VI4.Totalize.FLOT,424366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_8_VI4.Totalize.DayTotal500,424370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_8_VI4.Totalize.FTTotal500,424372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI4.Totalize.LowFlowCutoff,424374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_8_VI4.Totalize.TimeDivider,424382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_8_VI4.Totalize.Total2Minute,424384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_8_VI4.Totalize.Total5thSec,424386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_8_VI4.Totalize.TotalToday,424388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_8_VI4.Totalize.TotalTotal,424390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_8_VI5.Totalize.VALU,424556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_8_VI5.Totalize.VMAX,424558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_8_VI5.Totalize.LFCO,424560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_8_VI5.Totalize.FTTD,424562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_8_VI5.Totalize.FTYD,424564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_8_VI5.Totalize.FLOT,424566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_8_VI5.Totalize.DayTotal500,424570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_8_VI5.Totalize.FTTotal500,424572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_8_VI5.Totalize.LowFlowCutoff,424574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_8_VI5.Totalize.TimeDivider,424582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_8_VI5.Totalize.Total2Minute,424584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_8_VI5.Totalize.Total5thSec,424586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_8_VI5.Totalize.TotalToday,424588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_8_VI5.Totalize.TotalTotal,424590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_9_VI1.Totalize.VALU,424756,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_9_VI1.Totalize.VMAX,424758,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_9_VI1.Totalize.LFCO,424760,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_9_VI1.Totalize.FTTD,424762,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_9_VI1.Totalize.FTYD,424764,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_9_VI1.Totalize.FLOT,424766,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_9_VI1.Totalize.DayTotal500,424770,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_9_VI1.Totalize.FTTotal500,424772,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI1.Totalize.LowFlowCutoff,424774,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_9_VI1.Totalize.TimeDivider,424782,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_9_VI1.Totalize.Total2Minute,424784,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_9_VI1.Totalize.Total5thSec,424786,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_9_VI1.Totalize.TotalToday,424788,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_9_VI1.Totalize.TotalTotal,424790,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_9_VI2.Totalize.VALU,424956,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_9_VI2.Totalize.VMAX,424958,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_9_VI2.Totalize.LFCO,424960,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_9_VI2.Totalize.FTTD,424962,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_9_VI2.Totalize.FTYD,424964,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_9_VI2.Totalize.FLOT,424966,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_9_VI2.Totalize.DayTotal500,424970,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_9_VI2.Totalize.FTTotal500,424972,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI2.Totalize.LowFlowCutoff,424974,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_9_VI2.Totalize.TimeDivider,424982,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_9_VI2.Totalize.Total2Minute,424984,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_9_VI2.Totalize.Total5thSec,424986,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_9_VI2.Totalize.TotalToday,424988,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_9_VI2.Totalize.TotalTotal,424990,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_9_VI3.Totalize.VALU,425156,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_9_VI3.Totalize.VMAX,425158,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_9_VI3.Totalize.LFCO,425160,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_9_VI3.Totalize.FTTD,425162,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_9_VI3.Totalize.FTYD,425164,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_9_VI3.Totalize.FLOT,425166,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_9_VI3.Totalize.DayTotal500,425170,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_9_VI3.Totalize.FTTotal500,425172,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI3.Totalize.LowFlowCutoff,425174,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_9_VI3.Totalize.TimeDivider,425182,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_9_VI3.Totalize.Total2Minute,425184,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_9_VI3.Totalize.Total5thSec,425186,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_9_VI3.Totalize.TotalToday,425188,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_9_VI3.Totalize.TotalTotal,425190,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_9_VI4.Totalize.VALU,425356,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_9_VI4.Totalize.VMAX,425358,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_9_VI4.Totalize.LFCO,425360,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_9_VI4.Totalize.FTTD,425362,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_9_VI4.Totalize.FTYD,425364,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_9_VI4.Totalize.FLOT,425366,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_9_VI4.Totalize.DayTotal500,425370,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_9_VI4.Totalize.FTTotal500,425372,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI4.Totalize.LowFlowCutoff,425374,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_9_VI4.Totalize.TimeDivider,425382,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_9_VI4.Totalize.Total2Minute,425384,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_9_VI4.Totalize.Total5thSec,425386,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_9_VI4.Totalize.TotalToday,425388,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_9_VI4.Totalize.TotalTotal,425390,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_PMP_0103_9_VI5.Totalize.VALU,425556,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_PMP_0103_9_VI5.Totalize.VMAX,425558,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_PMP_0103_9_VI5.Totalize.LFCO,425560,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_PMP_0103_9_VI5.Totalize.FTTD,425562,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_PMP_0103_9_VI5.Totalize.FTYD,425564,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_PMP_0103_9_VI5.Totalize.FLOT,425566,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_PMP_0103_9_VI5.Totalize.DayTotal500,425570,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_PMP_0103_9_VI5.Totalize.FTTotal500,425572,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_PMP_0103_9_VI5.Totalize.LowFlowCutoff,425574,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_PMP_0103_9_VI5.Totalize.TimeDivider,425582,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_PMP_0103_9_VI5.Totalize.Total2Minute,425584,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_PMP_0103_9_VI5.Totalize.Total5thSec,425586,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_PMP_0103_9_VI5.Totalize.TotalToday,425588,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_PMP_0103_9_VI5.Totalize.TotalTotal,425590,Float,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_TT_0111_1_TI.Totalize.VALU,425756,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_TT_0111_1_TI.Totalize.VMAX,425758,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_TT_0111_1_TI.Totalize.LFCO,425760,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_TT_0111_1_TI.Totalize.FTTD,425762,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_TT_0111_1_TI.Totalize.FTYD,425764,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_TT_0111_1_TI.Totalize.FLOT,425766,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_TT_0111_1_TI.Totalize.DayTotal500,425770,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_TT_0111_1_TI.Totalize.FTTotal500,425772,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0111_1_TI.Totalize.LowFlowCutoff,425774,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_TT_0111_1_TI.Totalize.TimeDivider,425782,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_TT_0111_1_TI.Totalize.Total2Minute,425784,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_TT_0111_1_TI.Totalize.Total5thSec,425786,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_TT_0111_1_TI.Totalize.TotalToday,425788,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_TT_0111_1_TI.Totalize.TotalTotal,425790,Float,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" WA3252_TT_0112_1_TI.Totalize.VALU,425956,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Scaled Analog Value" WA3252_TT_0112_1_TI.Totalize.VMAX,425958,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Max Scaled Analog Value" WA3252_TT_0112_1_TI.Totalize.LFCO,425960,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Low Flow Cut Off Percent of Max Flow That Stops Totaling" WA3252_TT_0112_1_TI.Totalize.FTTD,425962,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Today's Total Flow" WA3252_TT_0112_1_TI.Totalize.FTYD,425964,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Yesterday's Total Flow" WA3252_TT_0112_1_TI.Totalize.FLOT,425966,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total FLow Since Last Reset" WA3252_TT_0112_1_TI.Totalize.DayTotal500,425970,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Keep total for past 500 days" WA3252_TT_0112_1_TI.Totalize.FTTotal500,425972,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: " WA3252_TT_0112_1_TI.Totalize.LowFlowCutoff,425974,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: In flow units" WA3252_TT_0112_1_TI.Totalize.TimeDivider,425982,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: How often per unit of time is analog value sampled" WA3252_TT_0112_1_TI.Totalize.Total2Minute,425984,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for the Current Minute" WA3252_TT_0112_1_TI.Totalize.Total5thSec,425986,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow for One 5th of One Second" WA3252_TT_0112_1_TI.Totalize.TotalToday,425988,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Total Flow of all Completed Minutes Today" WA3252_TT_0112_1_TI.Totalize.TotalTotal,425990,Float,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Totalized Value" RWPS_East_MicroSt.Outputs.Suction_Press,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_East_MicroSt.Outputs.Disch_Press,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_East_MicroSt.Outputs.P9_Power,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_East_MicroSt.Outputs.P9_Speed,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_East_MicroSt.Outputs.Friction_Coeff,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.Suction_Press,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.Disch_Press,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.P1_Power,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.P2_Power,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.P1_Speed,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.P2_Speed,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: RWPS_West_MicroSt.Outputs.Friction_Coeff,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Output Variables: TSR_PLC.Inputs.TRS_flow,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: TSR_PLC.Inputs.TSR_LI,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: TSR_PLC.Inputs.Spare1,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: TSR_PLC.Inputs.SPARE2,,Float,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: BMENOC0311_4.DEVICE_CNX_HEALTH.[0],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.DEVICE_CNX_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: DIO device health (1 bit per DIO up to 128 DIO) BMENOC0311_4.RESERVED2.[0],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[1],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[2],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[3],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[4],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[5],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[6],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMENOC0311_4.RESERVED2.[7],,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Reserved BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[0],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DEVICE_CNX_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): DIO device health (1 bit per DIO up to 128 DIO) BMEP58_ECPU_EXT.DID_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[8],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[9],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[10],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[11],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[12],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[13],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[14],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[15],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.DID_HEALTH.[16],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): Health for DIO (New field name) BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[1],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[2],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[3],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[4],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[5],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[6],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[7],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[8],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[9],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[10],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[11],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[12],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[13],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[14],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[15],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[16],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[17],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[18],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[19],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[20],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[21],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[22],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[23],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMEP58_ECPU_EXT.CIxR_OBJ_HEALTH.[24],,Word,1,R/W,1000,,,,,,,,,,Enhanced Device DDT for embedded M580 DTM (with standalone PLC): CIMR/CIDR Object health bits BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_2_17,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 2 to 17 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_18_33,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 18 to 33 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_34_49,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 34 to 49 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_50_65,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 50 to 65 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_66_81,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 66 to 81 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_82_97,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 82 to 97 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_98_113,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 98 to 113 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_114_129,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 114 to 129 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_130_145,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 130 to 145 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_146_161,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 146 to 161 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_162_177,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 162 to 511 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_178_193,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 178 to 193 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_194_209,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 194 to 209 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_210_225,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 210 to 225 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_226_241,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 226 to 241 BMENOC0311_4.DID_HEALTH.DEVICE_CNX_HEALTH_242_257,,Word,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Health for DIO Objects: Health of Distributed IO Objects: Device Connection health bits 242 to 257 AI_R2_S10.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S10.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S10.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S10.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S10.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S10.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S10.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S10.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S10.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S10.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S10.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S10.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S10.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S10.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S10.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S10.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S10.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S10.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S10.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S10.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S10.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S10.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S10.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S10.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S10.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S10.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S10.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S10.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S10.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S10.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S10.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S10.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S10.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S10.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S10.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S10.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S10.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R3_S9.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R3_S9.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R3_S9.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R3_S9.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R3_S9.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R3_S9.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R3_S9.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R3_S9.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R3_S9.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R0_S9.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R0_S9.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R0_S9.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R0_S9.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R0_S9.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R0_S9.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R0_S9.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R0_S9.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R0_S9.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R1_S9.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R1_S9.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R1_S9.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R1_S9.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R1_S9.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R1_S9.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R1_S9.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R1_S9.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R1_S9.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R2_S9.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R2_S9.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R2_S9.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R2_S9.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R2_S9.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R2_S9.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R2_S9.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R2_S9.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R2_S9.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S6.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S6.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S6.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S6.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S6.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S6.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S6.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S6.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S6.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S7.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S7.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S7.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S7.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S7.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S7.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S7.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S7.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S7.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R4_S8.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R4_S8.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R4_S8.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R4_S8.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R4_S8.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R4_S8.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R4_S8.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R4_S8.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R4_S8.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S5.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S5.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S5.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S5.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S5.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S5.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S5.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S5.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S5.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S8.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S8.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S8.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S8.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S8.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S8.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S8.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S8.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S8.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S6.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S6.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S6.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S6.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S6.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S6.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S6.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S6.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S6.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R5_S7.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R5_S7.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R5_S7.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R5_S7.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R5_S7.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R5_S7.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R5_S7.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R5_S7.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R5_S7.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S6.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S6.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S6.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S6.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S6.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S6.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S6.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S6.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S6.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[0].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[0].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[0].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[0].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[0].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[0].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[0].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[0].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[1].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[1].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[1].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[1].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[1].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[1].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[1].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[1].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[2].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[2].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[2].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[2].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[2].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[2].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[2].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[2].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[3].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[3].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[3].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[3].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[3].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[3].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[3].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[3].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[4].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[4].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[4].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[4].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[4].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[4].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[4].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[4].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[5].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[5].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[5].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[5].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[5].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[5].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[5].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[5].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[6].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[6].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[6].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[6].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[6].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[6].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[6].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[6].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AI_R6_S7.ANA_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AI_R6_S7.ANA_CH_IN.[7].CH_WARNING,,Boolean,1,R/W,1000,,,,,,,,,,Channel warning AI_R6_S7.ANA_CH_IN.[7].CH_ALIGNED,,Boolean,1,R/W,1000,,,,,,,,,,Aligned channel AI_R6_S7.ANA_CH_IN.[7].LOWER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within lower tolerance zone AI_R6_S7.ANA_CH_IN.[7].UPPER_LIMIT,,Boolean,1,R/W,1000,,,,,,,,,,Measurement within upper tolerance zone AI_R6_S7.ANA_CH_IN.[7].INT_OFFSET_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal offset error AI_R6_S7.ANA_CH_IN.[7].INT_REF_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Internal reference error AI_R6_S7.ANA_CH_IN.[7].POWER_SUP_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,Power supply error AI_R6_S7.ANA_CH_IN.[7].SPI_COM_ERROR,,Boolean,1,R/W,1000,,,,,,,,,,SPI communication error AO_R1_S11.ANA_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R1_S11.ANA_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R1_S11.ANA_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R1_S11.ANA_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R2_S11.ANA_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R2_S11.ANA_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R2_S11.ANA_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R2_S11.ANA_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R3_S11.ANA_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R3_S11.ANA_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R3_S11.ANA_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R3_S11.ANA_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R6_S8.ANA_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R6_S8.ANA_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R6_S8.ANA_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health AO_R6_S8.ANA_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S6.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S6.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S6.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R2_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S6.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R3_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R0_S7.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R1_S7.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S5.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R4_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R5_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S4.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S0.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S1.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S2.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DI_R6_S3.DIS_CH_IN.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S8.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S8.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S8.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R1_S8.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R0_S11.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R2_S7.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R3_S7.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[0].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[1].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[2].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[3].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[4].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[5].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[6].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[7].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[8].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[9].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[10].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[11].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[12].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[13].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[14].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health DO_R6_S5.DIS_CH_OUT.[15].CH_HEALTH,,Boolean,1,R/W,1000,,,,,,,,,,Channel health Meter_Vault_PLC.Inputs.Free0.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable Meter_Vault_PLC.Inputs.Free0.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump1.Inputs.Free0.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump1.Inputs.Free0.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump2.Inputs.Free0.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump2.Inputs.Free0.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump9.Inputs.Free0.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable RWPS_SEL710_Pump9.Inputs.Free0.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable TSR_PLC.Inputs.Free0.[0],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable TSR_PLC.Inputs.Free0.[1],,Byte,1,R/W,1000,,,,,,,,,,Device DDT For BME NOC Factory Cast: Input Variables: Unused Variable DI_R0_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S6.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S6.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S6.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R2_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S6.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R3_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R0_S7.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R1_S7.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S5.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R4_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R5_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S4.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S0.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S1.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S2.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DI_R6_S3.DIS_CH_IN.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete input value DO_R0_S8.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S8.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S8.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S8.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R1_S8.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R0_S11.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R2_S7.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R3_S7.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[0].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[1].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[2].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[3].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[4].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[5].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[6].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[7].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[8].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[9].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[10].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[11].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[12].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[13].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[14].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value DO_R6_S5.DIS_CH_OUT.[15].VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Discrete output value WA3252_AFD_0103_1_SI.Totalize.RESTTime.[0],401176,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_1_SI.Totalize.RESTTime.[1],401177,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_1_SI.Totalize.RESTTime.[2],401178,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_1_SI.Totalize.RESTTime.[3],401179,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_1_SI.Totalize.RESTTime.[4],401180,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_1_SI.Totalize.RESTTime.[5],401181,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 1 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[0],401376,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[1],401377,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[2],401378,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[3],401379,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[4],401380,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_2_SI.Totalize.RESTTime.[5],401381,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 2 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[0],401576,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[1],401577,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[2],401578,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[3],401579,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[4],401580,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_3_SI.Totalize.RESTTime.[5],401581,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 3 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[0],401776,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[1],401777,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[2],401778,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[3],401779,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[4],401780,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_4_SI.Totalize.RESTTime.[5],401781,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 4 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[0],401976,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[1],401977,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[2],401978,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[3],401979,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[4],401980,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_5_SI.Totalize.RESTTime.[5],401981,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 5 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[0],402176,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[1],402177,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[2],402178,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[3],402179,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[4],402180,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_6_SI.Totalize.RESTTime.[5],402181,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 6 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[0],402376,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[1],402377,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[2],402378,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[3],402379,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[4],402380,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_7_SI.Totalize.RESTTime.[5],402381,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 7 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[0],402576,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[1],402577,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[2],402578,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[3],402579,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[4],402580,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_8_SI.Totalize.RESTTime.[5],402581,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD PUMP 8 SPEED: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[0],402776,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[1],402777,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[2],402778,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[3],402779,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[4],402780,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_AFD_0103_9_SI.Totalize.RESTTime.[5],402781,Short,1,R/W,1000,,,,,,,,,,"RWPS AFD Pump 9 Speed : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[0],402976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[1],402977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[2],402978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[3],402979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[4],402980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI1.Totalize.RESTTime.[5],402981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[0],403176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[1],403177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[2],403178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[3],403179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[4],403180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI2.Totalize.RESTTime.[5],403181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[0],403376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[1],403377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[2],403378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[3],403379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[4],403380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI3.Totalize.RESTTime.[5],403381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[0],403576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[1],403577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[2],403578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[3],403579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[4],403580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI4.Totalize.RESTTime.[5],403581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[0],403776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[1],403777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[2],403778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[3],403779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[4],403780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI5.Totalize.RESTTime.[5],403781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[0],403976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[1],403977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[2],403978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[3],403979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[4],403980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI6.Totalize.RESTTime.[5],403981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[0],404176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[1],404177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[2],404178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[3],404179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[4],404180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI7.Totalize.RESTTime.[5],404181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[0],404376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[1],404377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[2],404378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[3],404379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[4],404380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI8.Totalize.RESTTime.[5],404381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[0],404576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[1],404577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[2],404578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[3],404579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[4],404580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_CP_0116_1_FI9.Totalize.RESTTime.[5],404581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Cooling Water Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[0],404776,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[1],404777,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[2],404778,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[3],404779,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[4],404780,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2A_ZI.Totalize.RESTTime.[5],404781,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve West Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[0],404976,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[1],404977,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[2],404978,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[3],404979,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[4],404980,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FCV_0113_2B_ZI.Totalize.RESTTime.[5],404981,Short,1,R/W,1000,,,,,,,,,,"RWPS Reservoir Valve East Side Position Indication : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[0],405176,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[1],405177,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[2],405178,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[3],405179,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[4],405180,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FIT_0113_2A_FI.Totalize.RESTTime.[5],405181,Short,1,R/W,1000,,,,,,,,,,"RWPS Flow To Reservoir Release Flow : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[0],405376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[1],405377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[2],405378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[3],405379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[4],405380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_1B_ZI.Totalize.RESTTime.[5],405381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[0],405576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[1],405577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[2],405578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[3],405579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[4],405580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_2B_ZI.Totalize.RESTTime.[5],405581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[0],405776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[1],405777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[2],405778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[3],405779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[4],405780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_3B_ZI.Totalize.RESTTime.[5],405781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[0],405976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[1],405977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[2],405978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[3],405979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[4],405980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_4B_ZI.Totalize.RESTTime.[5],405981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[0],406176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[1],406177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[2],406178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[3],406179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[4],406180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_5B_ZI.Totalize.RESTTime.[5],406181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[0],406376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[1],406377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[2],406378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[3],406379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[4],406380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_6B_ZI.Totalize.RESTTime.[5],406381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[0],406576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[1],406577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[2],406578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[3],406579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[4],406580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_7B_ZI.Totalize.RESTTime.[5],406581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[0],406776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[1],406777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[2],406778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[3],406779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[4],406780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_8B_ZI.Totalize.RESTTime.[5],406781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[0],406976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[1],406977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[2],406978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[3],406979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[4],406980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_FV_0103_9B_ZI.Totalize.RESTTime.[5],406981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Control Valve Position Feedback: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[0],407176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[1],407177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[2],407178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[3],407179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[4],407180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI1.Totalize.RESTTime.[5],407181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[0],407376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[1],407377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[2],407378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[3],407379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[4],407380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI2.Totalize.RESTTime.[5],407381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[0],407576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[1],407577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[2],407578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[3],407579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[4],407580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI3.Totalize.RESTTime.[5],407581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[0],407776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[1],407777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[2],407778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[3],407779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[4],407780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_1_VI4.Totalize.RESTTime.[5],407781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 1 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[0],407976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[1],407977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[2],407978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[3],407979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[4],407980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI1.Totalize.RESTTime.[5],407981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 2 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[0],408176,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[1],408177,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[2],408178,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[3],408179,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[4],408180,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI2.Totalize.RESTTime.[5],408181,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[0],408376,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[1],408377,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[2],408378,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[3],408379,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[4],408380,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI3.Totalize.RESTTime.[5],408381,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[0],408576,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[1],408577,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[2],408578,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[3],408579,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[4],408580,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_2_VI4.Totalize.RESTTime.[5],408581,Short,1,R/W,1000,,,,,,,,,,"Rwps Motor 2 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[0],408776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[1],408777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[2],408778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[3],408779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[4],408780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI1.Totalize.RESTTime.[5],408781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[0],408976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[1],408977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[2],408978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[3],408979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[4],408980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI2.Totalize.RESTTime.[5],408981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[0],409176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[1],409177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[2],409178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[3],409179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[4],409180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI3.Totalize.RESTTime.[5],409181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[0],409376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[1],409377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[2],409378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[3],409379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[4],409380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_3_VI4.Totalize.RESTTime.[5],409381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 3 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[0],409576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[1],409577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[2],409578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[3],409579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[4],409580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI1.Totalize.RESTTime.[5],409581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[0],409776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[1],409777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[2],409778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[3],409779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[4],409780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI2.Totalize.RESTTime.[5],409781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[0],409976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[1],409977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[2],409978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[3],409979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[4],409980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI3.Totalize.RESTTime.[5],409981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[0],410176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[1],410177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[2],410178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[3],410179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[4],410180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_4_VI4.Totalize.RESTTime.[5],410181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 4 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[0],410376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[1],410377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[2],410378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[3],410379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[4],410380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI1.Totalize.RESTTime.[5],410381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[0],410576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[1],410577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[2],410578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[3],410579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[4],410580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI2.Totalize.RESTTime.[5],410581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[0],410776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[1],410777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[2],410778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[3],410779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[4],410780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI3.Totalize.RESTTime.[5],410781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[0],410976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[1],410977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[2],410978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[3],410979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[4],410980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_5_VI4.Totalize.RESTTime.[5],410981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 5 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[0],411176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[1],411177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[2],411178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[3],411179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[4],411180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI1.Totalize.RESTTime.[5],411181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[0],411376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[1],411377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[2],411378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[3],411379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[4],411380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI2.Totalize.RESTTime.[5],411381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[0],411576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[1],411577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[2],411578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[3],411579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[4],411580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI3.Totalize.RESTTime.[5],411581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[0],411776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[1],411777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[2],411778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[3],411779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[4],411780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_6_VI4.Totalize.RESTTime.[5],411781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 6 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[0],411976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[1],411977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[2],411978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[3],411979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[4],411980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI1.Totalize.RESTTime.[5],411981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[0],412176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[1],412177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[2],412178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[3],412179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[4],412180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI2.Totalize.RESTTime.[5],412181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[0],412376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[1],412377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[2],412378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[3],412379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[4],412380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI3.Totalize.RESTTime.[5],412381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[0],412576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[1],412577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[2],412578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[3],412579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[4],412580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_7_VI4.Totalize.RESTTime.[5],412581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 7 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[0],412776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[1],412777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[2],412778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[3],412779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[4],412780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI1.Totalize.RESTTime.[5],412781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[0],412976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[1],412977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[2],412978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[3],412979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[4],412980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI2.Totalize.RESTTime.[5],412981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[0],413176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[1],413177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[2],413178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[3],413179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[4],413180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI3.Totalize.RESTTime.[5],413181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 X-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[0],413376,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[1],413377,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[2],413378,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[3],413379,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[4],413380,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_8_VI4.Totalize.RESTTime.[5],413381,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 8 Y-Direction Vibration Non-Drive End Bearing: DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[0],413576,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[1],413577,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[2],413578,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[3],413579,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[4],413580,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI1.Totalize.RESTTime.[5],413581,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[0],413776,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[1],413777,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[2],413778,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[3],413779,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[4],413780,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI2.Totalize.RESTTime.[5],413781,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[0],413976,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[1],413977,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[2],413978,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[3],413979,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[4],413980,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI3.Totalize.RESTTime.[5],413981,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 X-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[0],414176,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[1],414177,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[2],414178,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[3],414179,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[4],414180,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_MTR_0103_9_VI4.Totalize.RESTTime.[5],414181,Short,1,R/W,1000,,,,,,,,,,"RWPS Motor 9 Y-Direction Vibration Non-Drive End Bearing : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[0],414376,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[1],414377,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[2],414378,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[3],414379,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[4],414380,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_1_PI.Totalize.RESTTime.[5],414381,Short,1,R/W,1000,,,,,,,,,,"RWPS West Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[0],414576,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[1],414577,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[2],414578,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[3],414579,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[4],414580,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0102_2_PI.Totalize.RESTTime.[5],414581,Short,1,R/W,1000,,,,,,,,,,"RWPS East Suction Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[0],414776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[1],414777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[2],414778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[3],414779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[4],414780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_1_PI.Totalize.RESTTime.[5],414781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[0],414976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[1],414977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[2],414978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[3],414979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[4],414980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_2_PI.Totalize.RESTTime.[5],414981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[0],415176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[1],415177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[2],415178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[3],415179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[4],415180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_3_PI.Totalize.RESTTime.[5],415181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[0],415376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[1],415377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[2],415378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[3],415379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[4],415380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_4_PI.Totalize.RESTTime.[5],415381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[0],415576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[1],415577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[2],415578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[3],415579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[4],415580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_5_PI.Totalize.RESTTime.[5],415581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[0],415776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[1],415777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[2],415778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[3],415779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[4],415780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_6_PI.Totalize.RESTTime.[5],415781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[0],415976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[1],415977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[2],415978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[3],415979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[4],415980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_7_PI.Totalize.RESTTime.[5],415981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[0],416176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[1],416177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[2],416178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[3],416179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[4],416180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_8_PI.Totalize.RESTTime.[5],416181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[0],416376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[1],416377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[2],416378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[3],416379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[4],416380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0103_9_PI.Totalize.RESTTime.[5],416381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[0],416576,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[1],416577,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[2],416578,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[3],416579,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[4],416580,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PIT_0104_1_PI.Totalize.RESTTime.[5],416581,Short,1,R/W,1000,,,,,,,,,,"RWPS Discharge Pressure : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[0],416776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[1],416777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[2],416778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[3],416779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[4],416780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI1.Totalize.RESTTime.[5],416781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[0],416976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[1],416977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[2],416978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[3],416979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[4],416980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI2.Totalize.RESTTime.[5],416981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[0],417176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[1],417177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[2],417178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[3],417179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[4],417180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI3.Totalize.RESTTime.[5],417181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[0],417376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[1],417377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[2],417378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[3],417379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[4],417380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI4.Totalize.RESTTime.[5],417381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[0],417576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[1],417577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[2],417578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[3],417579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[4],417580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_1_VI5.Totalize.RESTTime.[5],417581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 1 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[0],417776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[1],417777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[2],417778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[3],417779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[4],417780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI1.Totalize.RESTTime.[5],417781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 2 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[0],417976,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[1],417977,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[2],417978,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[3],417979,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[4],417980,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI2.Totalize.RESTTime.[5],417981,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[0],418176,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[1],418177,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[2],418178,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[3],418179,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[4],418180,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI3.Totalize.RESTTime.[5],418181,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[0],418376,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[1],418377,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[2],418378,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[3],418379,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[4],418380,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI4.Totalize.RESTTime.[5],418381,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[0],418576,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[1],418577,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[2],418578,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[3],418579,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[4],418580,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_2_VI5.Totalize.RESTTime.[5],418581,Short,1,R/W,1000,,,,,,,,,,"Rwps Pump 2 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[0],418776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[1],418777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[2],418778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[3],418779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[4],418780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI1.Totalize.RESTTime.[5],418781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[0],418976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[1],418977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[2],418978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[3],418979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[4],418980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI2.Totalize.RESTTime.[5],418981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[0],419176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[1],419177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[2],419178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[3],419179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[4],419180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI3.Totalize.RESTTime.[5],419181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[0],419376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[1],419377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[2],419378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[3],419379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[4],419380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI4.Totalize.RESTTime.[5],419381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[0],419576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[1],419577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[2],419578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[3],419579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[4],419580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_3_VI5.Totalize.RESTTime.[5],419581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 3 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[0],419776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[1],419777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[2],419778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[3],419779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[4],419780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI1.Totalize.RESTTime.[5],419781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[0],419976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[1],419977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[2],419978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[3],419979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[4],419980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI2.Totalize.RESTTime.[5],419981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[0],420176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[1],420177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[2],420178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[3],420179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[4],420180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI3.Totalize.RESTTime.[5],420181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[0],420376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[1],420377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[2],420378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[3],420379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[4],420380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI4.Totalize.RESTTime.[5],420381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[0],420576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[1],420577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[2],420578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[3],420579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[4],420580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_4_VI5.Totalize.RESTTime.[5],420581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 4 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[0],420776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[1],420777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[2],420778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[3],420779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[4],420780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI1.Totalize.RESTTime.[5],420781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[0],420976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[1],420977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[2],420978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[3],420979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[4],420980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI2.Totalize.RESTTime.[5],420981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[0],421176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[1],421177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[2],421178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[3],421179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[4],421180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI3.Totalize.RESTTime.[5],421181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[0],421376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[1],421377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[2],421378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[3],421379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[4],421380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI4.Totalize.RESTTime.[5],421381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[0],421576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[1],421577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[2],421578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[3],421579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[4],421580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_5_VI5.Totalize.RESTTime.[5],421581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 5 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[0],421776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[1],421777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[2],421778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[3],421779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[4],421780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI1.Totalize.RESTTime.[5],421781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[0],421976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[1],421977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[2],421978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[3],421979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[4],421980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI2.Totalize.RESTTime.[5],421981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[0],422176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[1],422177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[2],422178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[3],422179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[4],422180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI3.Totalize.RESTTime.[5],422181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[0],422376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[1],422377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[2],422378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[3],422379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[4],422380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI4.Totalize.RESTTime.[5],422381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[0],422576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[1],422577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[2],422578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[3],422579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[4],422580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_6_VI5.Totalize.RESTTime.[5],422581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 6 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[0],422776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[1],422777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[2],422778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[3],422779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[4],422780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI1.Totalize.RESTTime.[5],422781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[0],422976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[1],422977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[2],422978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[3],422979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[4],422980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI2.Totalize.RESTTime.[5],422981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[0],423176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[1],423177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[2],423178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[3],423179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[4],423180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI3.Totalize.RESTTime.[5],423181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[0],423376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[1],423377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[2],423378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[3],423379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[4],423380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI4.Totalize.RESTTime.[5],423381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[0],423576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[1],423577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[2],423578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[3],423579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[4],423580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_7_VI5.Totalize.RESTTime.[5],423581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 7 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[0],423776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[1],423777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[2],423778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[3],423779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[4],423780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI1.Totalize.RESTTime.[5],423781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[0],423976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[1],423977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[2],423978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[3],423979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[4],423980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI2.Totalize.RESTTime.[5],423981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Ce): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[0],424176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[1],424177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[2],424178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[3],424179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[4],424180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI3.Totalize.RESTTime.[5],424181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 X-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[0],424376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[1],424377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[2],424378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[3],424379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[4],424380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI4.Totalize.RESTTime.[5],424381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Y-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[0],424576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[1],424577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[2],424578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[3],424579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[4],424580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_8_VI5.Totalize.RESTTime.[5],424581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 8 Z-Direction Vibration (Obe): DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[0],424776,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[1],424777,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[2],424778,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[3],424779,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[4],424780,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI1.Totalize.RESTTime.[5],424781,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[0],424976,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[1],424977,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[2],424978,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[3],424979,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[4],424980,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI2.Totalize.RESTTime.[5],424981,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Ce) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[0],425176,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[1],425177,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[2],425178,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[3],425179,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[4],425180,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI3.Totalize.RESTTime.[5],425181,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 X-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[0],425376,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[1],425377,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[2],425378,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[3],425379,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[4],425380,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI4.Totalize.RESTTime.[5],425381,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Y-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[0],425576,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[1],425577,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[2],425578,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[3],425579,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[4],425580,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_PMP_0103_9_VI5.Totalize.RESTTime.[5],425581,Short,1,R/W,1000,,,,,,,,,,"RWPS Pump 9 Z-Direction Vibration (Obe) : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[0],425776,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[1],425777,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[2],425778,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[3],425779,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[4],425780,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0111_1_TI.Totalize.RESTTime.[5],425781,Short,1,R/W,1000,,,,,,,,,,"RWPS Scada Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[0],425976,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[1],425977,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[2],425978,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[3],425979,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[4],425980,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" WA3252_TT_0112_1_TI.Totalize.RESTTime.[5],425981,Short,1,R/W,1000,,,,,,,,,,"RWPS Electrical Room Ambient Temperature : DDT for Analog DFB: Analog Inputs, No Strings: Totalizer DDT: DDT for Tot Ladder DFB: Totalizes analog value, provides increased precision compared to built in totalizer, No Strings: Time the total was last reset" AI_R2_S10.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S10.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S10.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S10.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R3_S9.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R0_S9.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R1_S9.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S9.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S6.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S7.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R4_S8.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S5.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S8.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S6.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R5_S7.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S6.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[0].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[1].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[2].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[3].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[4].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[5].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[6].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R6_S7.ANA_CH_IN.[7].MEASURE_STS,,Short,1,R/W,1000,,,,,,,,,,Measurement status word AI_R2_S10.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S10.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S10.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S10.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R3_S9.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R0_S9.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R1_S9.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S9.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S6.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S7.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R4_S8.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S5.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S8.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S6.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R5_S7.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S6.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[4].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[5].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[6].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R6_S7.ANA_CH_IN.[7].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R1_S11.ANA_CH_OUT.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R1_S11.ANA_CH_OUT.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R1_S11.ANA_CH_OUT.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R1_S11.ANA_CH_OUT.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R2_S11.ANA_CH_OUT.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R2_S11.ANA_CH_OUT.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R2_S11.ANA_CH_OUT.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R2_S11.ANA_CH_OUT.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R3_S11.ANA_CH_OUT.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R3_S11.ANA_CH_OUT.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R3_S11.ANA_CH_OUT.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R3_S11.ANA_CH_OUT.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R6_S8.ANA_CH_OUT.[0].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R6_S8.ANA_CH_OUT.[1].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R6_S8.ANA_CH_OUT.[2].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AO_R6_S8.ANA_CH_OUT.[3].FCT_TYPE,,Word,1,R/W,1000,,,,,,,,,,Function type AI_R2_S10.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S10.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S10.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S10.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S10.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S10.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S10.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S10.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S10.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S10.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S10.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S10.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S10.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S10.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S10.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S10.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S10.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S10.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S10.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S10.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S10.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R3_S9.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R3_S9.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R3_S9.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R3_S9.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R3_S9.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R0_S9.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R0_S9.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R0_S9.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R0_S9.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R0_S9.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R1_S9.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R1_S9.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R1_S9.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R1_S9.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R1_S9.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R2_S9.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R2_S9.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R2_S9.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R2_S9.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R2_S9.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S6.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S6.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S6.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S6.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S6.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S7.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S7.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S7.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S7.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S7.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R4_S8.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R4_S8.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R4_S8.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R4_S8.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R4_S8.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S5.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S5.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S5.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S5.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S5.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S8.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S8.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S8.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S8.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S8.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S6.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S6.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S6.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S6.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S6.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R5_S7.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R5_S7.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R5_S7.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R5_S7.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R5_S7.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S6.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S6.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S6.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S6.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S6.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[0].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[1].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[2].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[3].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[4].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[4].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[4].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[4].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[4].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[5].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[5].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[5].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[5].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[5].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[6].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[6].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[6].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[6].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[6].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AI_R6_S7.ANA_CH_IN.[7].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog input value AI_R6_S7.ANA_CH_IN.[7].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced value AI_R6_S7.ANA_CH_IN.[7].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AI_R6_S7.ANA_CH_IN.[7].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AI_R6_S7.ANA_CH_IN.[7].ANA.TRUE_VALUE,,Boolean,1,R/W,1000,,,,,,,,,,Physical value AO_R1_S11.ANA_CH_OUT.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R1_S11.ANA_CH_OUT.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R1_S11.ANA_CH_OUT.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R1_S11.ANA_CH_OUT.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R1_S11.ANA_CH_OUT.[0].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R1_S11.ANA_CH_OUT.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R1_S11.ANA_CH_OUT.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R1_S11.ANA_CH_OUT.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R1_S11.ANA_CH_OUT.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R1_S11.ANA_CH_OUT.[1].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R1_S11.ANA_CH_OUT.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R1_S11.ANA_CH_OUT.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R1_S11.ANA_CH_OUT.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R1_S11.ANA_CH_OUT.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R1_S11.ANA_CH_OUT.[2].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R1_S11.ANA_CH_OUT.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R1_S11.ANA_CH_OUT.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R1_S11.ANA_CH_OUT.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R1_S11.ANA_CH_OUT.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R1_S11.ANA_CH_OUT.[3].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R2_S11.ANA_CH_OUT.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R2_S11.ANA_CH_OUT.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R2_S11.ANA_CH_OUT.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R2_S11.ANA_CH_OUT.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R2_S11.ANA_CH_OUT.[0].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R2_S11.ANA_CH_OUT.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R2_S11.ANA_CH_OUT.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R2_S11.ANA_CH_OUT.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R2_S11.ANA_CH_OUT.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R2_S11.ANA_CH_OUT.[1].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R2_S11.ANA_CH_OUT.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R2_S11.ANA_CH_OUT.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R2_S11.ANA_CH_OUT.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R2_S11.ANA_CH_OUT.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R2_S11.ANA_CH_OUT.[2].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R2_S11.ANA_CH_OUT.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R2_S11.ANA_CH_OUT.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R2_S11.ANA_CH_OUT.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R2_S11.ANA_CH_OUT.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R2_S11.ANA_CH_OUT.[3].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R3_S11.ANA_CH_OUT.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R3_S11.ANA_CH_OUT.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R3_S11.ANA_CH_OUT.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R3_S11.ANA_CH_OUT.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R3_S11.ANA_CH_OUT.[0].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R3_S11.ANA_CH_OUT.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R3_S11.ANA_CH_OUT.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R3_S11.ANA_CH_OUT.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R3_S11.ANA_CH_OUT.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R3_S11.ANA_CH_OUT.[1].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R3_S11.ANA_CH_OUT.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R3_S11.ANA_CH_OUT.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R3_S11.ANA_CH_OUT.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R3_S11.ANA_CH_OUT.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R3_S11.ANA_CH_OUT.[2].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R3_S11.ANA_CH_OUT.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R3_S11.ANA_CH_OUT.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R3_S11.ANA_CH_OUT.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R3_S11.ANA_CH_OUT.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R3_S11.ANA_CH_OUT.[3].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R6_S8.ANA_CH_OUT.[0].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R6_S8.ANA_CH_OUT.[0].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R6_S8.ANA_CH_OUT.[0].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R6_S8.ANA_CH_OUT.[0].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R6_S8.ANA_CH_OUT.[0].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R6_S8.ANA_CH_OUT.[1].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R6_S8.ANA_CH_OUT.[1].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R6_S8.ANA_CH_OUT.[1].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R6_S8.ANA_CH_OUT.[1].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R6_S8.ANA_CH_OUT.[1].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R6_S8.ANA_CH_OUT.[2].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R6_S8.ANA_CH_OUT.[2].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R6_S8.ANA_CH_OUT.[2].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R6_S8.ANA_CH_OUT.[2].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R6_S8.ANA_CH_OUT.[2].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value AO_R6_S8.ANA_CH_OUT.[3].ANA.VALUE,,Short,1,R/W,1000,,,,,,,,,,Analog output value AO_R6_S8.ANA_CH_OUT.[3].ANA.FORCED_VALUE,,Short,1,R/W,1000,,,,,,,,,,Forced Value AO_R6_S8.ANA_CH_OUT.[3].ANA.FORCE_CMD,,Boolean,1,R/W,1000,,,,,,,,,,Force command AO_R6_S8.ANA_CH_OUT.[3].ANA.FORCED_STATE,,Boolean,1,R/W,1000,,,,,,,,,,Forced state AO_R6_S8.ANA_CH_OUT.[3].ANA.TRUE_VALUE,,Short,1,R/W,1000,,,,,,,,,,Physical value